.. title:: MPS Logic 2016-04-24-a | .. title:: MPS Logic 9999-99-99-z > FEE Spectrometer Crystal - Pulse Energy Too High When Crystal > ------------------------------------------------------------- > =============== = = ==================== ==================== > Name B A Pockels Cell Mechanical Shutter > =============== = = ==================== ==================== > Fault F F 0 Hz 0 Hz > Pulse Energy Ok F T 120 Hz 120 Hz > Crystal Out T F 120 Hz 120 Hz > Crystal Out T T 120 Hz 120 Hz > =============== = = ==================== ==================== > > Where:: > > A = XTAL_FEE1_441_PULSEENERGY_THRESHOLD > B = XTAL_FEE1_441_OUT_LIMSW_POSITION > > > Gas Detector Problem When FEE Spectrometer Crystal Not Out > ---------------------------------------------------------- > =============== = = ==================== ==================== > Name B A Pockels Cell Mechanical Shutter > =============== = = ==================== ==================== > Fault F F 0 Hz 0 Hz > Gas Detector Ok F T 120 Hz 120 Hz > Crystal Out T F 120 Hz 120 Hz > Crystal Out T T 120 Hz 120 Hz > =============== = = ==================== ==================== > > Where:: > > A = GDET_FEE1_1_CAL_OK_STATE > B = XTAL_FEE1_441_OUT_LIMSW_POSITION > >