Logic 2016-10-18-a
-------------
* Remove truth tables:
  Profile Monitor BSY0 45 Position When D2 or TDUND Not In
  Profile Monitor BSY0 45 Position

Logic 2016-10-17-a
-------------
* New MFX interlocks
* Add new analog link node inputs (not yet used in logic)

Logic 2016-08-25-a
-------------
* Build against database 2016-08-25-a in order to test analog
  link node inputs. No logic changes.

Logic 2016-05-10-a
-------------
* Again, minor change to state names for these truth tables:
  FEE Spectrometer Crystal - Beam Energy Too Low When Crystal Not Out
  FEE Spectrometer Crystal - Pulse Energy Too High When Crystal Not Out 
  Gas Detector Problem When FEE Spectrometer Crystal Not Out


Logic 2016-05-02-a
-------------
* Remove unused and obsolete device
   TIUKEYSW aka TIU:IN20:1:KEY_SWITCH_STATE
* Rename Spoiler: SP0 DMP1 765 Position to Spoiler SP0 DMP1 765 Position



Logic 2016-04-29-a
-------------
* Minor change to state names for these truth tables:
  FEE Spectrometer Crystal - Beam Energy Too Low When Crystal Not Out
  FEE Spectrometer Crystal - Pulse Energy Too High When Crystal Not Out 
  Gas Detector Problem When FEE Spectrometer Crystal Not Out
Logic 2016-04-26-a
-------------
* New truth tables for FEE spectrometer crystal protection
  FEE Spectrometer Crystal - Pulse Energy Too High When Crystal Not Out
  Gas Detector Problem When FEE Spectrometer Crystal Not Out
**Linear parent logic unless otherwise noted**

Logic 2016-04-24-a
-------------
* No logic changes. Modify Makfile to use scripts/version1-0-6

Logic 2016-03-01-a
-------------
* "FEE Solid Attenuators - Gas Pressure Interlock": allow SATTs 3 and 4 
  to be IN

Logic 2016-02-26-a
-------------
* Remove obsolete inputs and associated logic - should not affect algorithm

Logic 2016-02-25-a
-------------
* Remove obsolete inputs and associated logic - should not affect algorithm

Logic 2016-02-24-a
-------------
* Remove Dechirper BPM interlocks
* Remove dangling unused database objects - should not affect algorithm

Logic 2016-02-12-a
-------------
* Update LTU Horizontal Dechirper Gap truth table now that
  we have 2 independent gap switches

Logic 2016-01-22-b
-------------
Remove LTU Dechirper - 10 Hz Rate Limit if Dechirper Not Out

Logic 2016-01-22-a - BASED ON 2015-12-17-a
-------------
Rename some inputs to match their PV names. See changes.log
for details.

Logic 2015-12-17-b
-------------
Remove LTU Dechirper - 10 Hz Rate Limit if Dechirper Not Out

Logic 2015-12-17-a - BASED ON 2015-11-09-a
-------------
* Remove unused duplicate truth table
* Fix XRT S5 state names (Moving and Broken were swapped)
* Update LTU Vertical Dechirper Gap truth table now that
  we have 2 independent gap switches

Logic 2015-11-09-b
-------------
Remove LTU Dechirper - 10 Hz Rate Limit if Dechirper Not Out

Logic 2015-11-09-a - BASED ON 2015-10-10-a
-------------
* Remove photon logic:
	  HXX:HXM:VGC:01 Gate Valve Position
          HXX:HXM:VGC:02 Gate Valve Position
          HXX:HXM:VGC:03 Gate Valve Position
	  XRT HXRAY MXT Isolation Valve HXX-MXT-VGC-01
	  NEH AMO Focusing Optics Entrance Gate Valve KBO-VGC-01
	  NEH AMO Focusing Optics Exit Gate Valve KBO-VGC-02
	  NEH AMO LAMP Gate Valve VGC 30 Position
	  NEH AMO LAMP Gate Valve VGC 30 Is In Beam
	  NEH AMO LAMP Gate Valve VGC 30 Is Out of Beam
* Add photon logic:
	  NEH AMO Valves Ok for Beam - Summary From PLC	
	  MEC BXL VGC 01 Gate Valve Position
	  XRT HXRAY MXT Gate Valve HXX:MXT:VGC:01
	  XRT HXRAY MXT Gate Valve HXX:MXT:VGC:02
	  XRT HXRAY MXT Gate Valve HXX:MXT:VGC:03
	  XRT HXRAY MXT Gate Valve HXX:MXT:VGC:05 
* Add ignore devices to  TDUND Position 
* Remove B4C Position
* Remove Temperature RTD Summary: North Arc

Logic 2015-10-10-b
-------------
Remove LTU Dechirper - 10 Hz Rate Limit if Dechirper Not Out

Logic 2015-10-10-a
-------------
Remove LTU Dechirper - Undulators Must Be Out If Dechirper Not Out

Logic 2015-10-09-a - BASED ON 2015-09-08-a
-------------
Add MEC DV4 VCG 01 Gate Valve Position
Use database version 2015-10-09-a

Logic 2015-09-08-z: NON-LINEAR LOGIC
-------------
This is a version to be used ONLY for LTU Dechirper commissioning.
It is based on 2015-09-04-a with these changes:
* Add commissioning Dechirper logic:
  LTU Dechirper Commissioning - BPM 550 Watchdog
  LTU Dechirper Commissioning - BPM 550 X/Y Position
  LTU Dechirper Commissioning - TDUND Must Be In

Logic 2015-09-08-a
-------------
* Add production Dechirper logic:
  LTU Dechirper - Undulators Must Be Out If Dechirper In
  LTU Dechirper - 10 Hz Raw Limit if Jaws Not Out
  LTU Dechirper - BPM 550 Watchdog
  LTU Dechirper - BPM 550 X/Y Position
  LTU Dechirper - Horizontal Gap Too Small
  LTU Dechirper - Vertical Gap Too Small
  Ignore device: LTU Dechirper Is Out

Logic 2015-09-04-a
-------------
* Add truth table "MFX Gate Valves Not All Open - PLC Summary Status"

Logic 2015-09-03-a
-------------
* Add truth table "VVFV IN20 785 Position"
* Add Dechirper BLF truth tables:
    "BLM Heartbeat: Dechirper LTU1 BLF545"  
    "BLM Pedestal Thresholds: Dechirper LTU1 BLF545"
    "BLM Raw Charge Thresholds: Dechirper LTU1 BLF545"
* Set "XPP CS-PAD 1 Detector Damage Fault" inactive

Logic 2015-07-13-b
-------------
* Explicity add inputs for is-code logic (those that were missing)
  to support MPS GUI improvements
* Update logic for CXI:SC3:VGC:01. See changelog for details.

Logic 2015-07-13-a
-------------
* Add new truth table for CXI gate valve: 
    "CXI:SC3:VGC:01 Gate Valve Position"
* Modify BC1 toroid comparator state names to reflect new threshold

Logic 2015-05-18-a
-------------
* Add new truth table FEE Solid Attenuators - Gas Pressure Interlock
* Modify ignore device lists for: 
    HXR - Beam Energy Too Low With M1S Out
    FEE Spectrometer Crystal - Beam Energy Too Low When Crystal Not Out

Logic 2015-05-04-a
-------------
* Add new devices: LN42 trigger; LTU dechirper BLF
* Add truth table PIC Trigger Missed (LN42)
* Remove duplicate truth table Mirror BL21 Position 
* Per CATER request, add MAD names to OTR/YAG truth tables.
  Then, to be consistent, add unit numbers to other OTR/YAG
  truth tables

Logic 2015-03-04-a
-------------
* Add TD11 Position truth table to fault moving/broken state

Logic 2015-03-02-c
-------------
* Remove BX01/BX02 and BXG from ignore device lists
  for truth tables also ignored by TD11
* Remove duplicate Flowswitch: COLL BSYA 1015 (PC10)
* Rename BSY GLAST Target to BSY GLAST Target Position
* Remove duplicate Linac slow and fast valves

Logic 2015-03-02-b
-------------
* Rename TIU, flow switch, IMPS Heartbeat, Pockels Cell
  truth tables for clarity and consistency

Logic 2015-03-02-a
-------------
* Remove duplicate truth tables:
  TIU: DPS Temperature
  TIU: Fast Shutter 2 Position: LI30
  TIU: Fast Shutter 2A Position: LI30
  YG BL241 Position
  YG BL351 Position
* Change TIU:MCC Emergency Radiation Stopper
  to be always evaluated (never ignored)
* Add D2 as ignore device for HXRSS logic

Logic 2015-02-27-a
-------------
* New truth table 'YAG02 Is In'
* New ignore device 'YAG02 Is In'
* Add 'YAG02 Is In' ignore device to all devices ignored by YAG01
  *except* 
	Wakefield Shield Gun Spectrometer
	Wakefield Shield Straight Ahead
	BXG Status
	Toroid Peak Current Monitor IM01
	YG BL241 Position
	YAG IN20 241 Position
* Change 'BLM/PIC Watchdog: IN20' and 'TIU: VVS: Circuit Breaker: LI20"
  to be always evaluated (previously ignored by YAG01)
* Remove obsolete truth table Profile Monitor BSY0 45 - Deprecated

Logic 2015-02-26-a
-------------
* Rename ignore device 'YG BL211 Is In' to 'YAG01 Is In'

*************Out-of-band release******************
Logic 2015-01-07-b
-------------
* NOTE: this version is a pseudo-branch, containing 
  just 2 changes from 2015-01-07-a. 
  Last-minute release to support LCLS MD activities:
    - Ignore 30-9 slow valve if TD11 is IN	 
  This algorithm was unloaded at the end of the MD
  and the logic changes in this release are NOT
  included in any subsequent releases
**************************************************

Logic 2015-01-07-a
-------------
* Add TDUND flow switch logic
* Reorganize Profile Monitor BSY0 45 logic to 
  take advantage of ignore devices instead of 
  using stopper positions as inputs to logic.
  Set 'Profile Monitor BSY0 45' logic to Not Active
  Add 2 new truth tables: 'Profile Monitor BSY0 45 Position'
  and 'Profile Monitor BSY0 45 Position When D2 or TDUND Not In'
* Fix typo in truth table name. Change 'FEE Spectrometer Crystal - 
  Beam Energy Too Low With Crystal Out' to 'FEE Spectrometer 
  Crystal - Beam Energy Too Low When Crystal Not Out'

Logic 2014-12-05-a
-------------
* Add logic to protect
  FEE spectrometer crystal
  from low energy beam

Logic 2014-10-24-a
------------
* Add truth tables
  XPP SB2 VGC 02 Gate Valve Position
  XPP SB2 VGC 03 Gate Valve Position

Logic 2014-10-16-a
------------
* BCS PIC RAW Charge Threshold DMP 997/998: 
  add D2 to ignore list
* OTR21/OTR22 Position:
  add TD11 To ignore list
* OTR30/OTR33 Position:
  add TD11 and D2 to ignore list

Logic 2014-10-10-a
------------
* Set 'Stopper: ST1/ST2 Position' to only
be ignored if D2 IN

Logic 2014-10-01-a
------------
* Add HXR Beam Energy with M1S Out truth table

Logic 2014-09-24-a
------------
* Cleanup of photon logic ignore device lists
  See changes.log for more information

Logic 2014-09-23-a
------------
* Add new ignore device SP0 spoiler, add it as
  ignore device to appropriate truth tables

Logic 2014-07-02-a
------------
* Modify D2 logic to rate-limit beam to 10 Hz 
  (from 120) when D2 is IN
* Update PIC HVPS input names to be consistent
* Add truth tables for missing PIC HVPS inputs: 
  LI20, LI24, BSY
* Fix ignore devices for LI24 BLM/PIC watchdog

Logic 2014-06-09-a
------------
* Added logic for DMP SP0 Spoiler Position

Logic 2014-05-30-a
------------
* Remove photon M3H from lists of ignore devices

Logic 2014-05-13-a
------------
* Remove CXI Detector Damage truth tables
* Set B4C Protection of ST1/ST2 inactive
* Update B4C Position
* BSY RTD truth table name cleanup
* Fix incorrect LHS mitigation rate assignment for 
  some non-LHS-related truth tables

Logic 2014-03-31-a
------------
* Update CXI valve logic per A. Wallace

Logic 2014-03-12-a
------------
* Update CXI Configurations 2 and 7 per A. Wallace

Logic 2014-02-28-a
------------
* Changed names and removed channels for CXI.
* Updated CXI configuration summary logic
* Added D2 as Ignore Device for many CXI truth tables

Logic 2014-02-26-a
------------
* Update SXRSS Mode logic; remove temporary mode truth tables that
  were created for commissioning

Logic 2014-02-21-a
------------
* Cleaned up FEE1 M1S Mirror Beam Energy Upper Limit truth table

Logic 2014-02-06-a
------------
* No logic changes
* Use database 2014-01-06-a to pick up databaseCommon/version1-0-4,
  which adds channel access security to MPS bypasses

Logic 2014-01-06-a
------------
* 50PC30, 50PC45, PC0119 - no longer ignore when 
  A-Line B1/B2 Is Not On AND A-Line Kicker Is Not Enabled
  (never should have been the case)
* SXRSS: Add individual truth tables for each insertable device;
  Modify mode logic to take advantage of these new tables

Logic 2013-12-17-a
------------
* SXRSS Mode: Seeded Mode: Allow M3 to be either IN or OUT
  (previously required to be IN)

Logic 2013-12-02-a
------------
* Modifications to HXR Beam Energy Lower Limit for future use and
  set inactive for now
* Add FEE1 M1S Mirror State to check for inconsistencies
* Add S5B to ignore list for HF4 LAM VGC 01 Gate Valve Position
* Add D2  to ignore list for B4C Protection of ST1/ST2  

Logic 2013-11-11-a
------------
* Enable production SXRSS Mode State; 
  disable temporary SXRSS Mode State - Chicane, Slit, and M3 Active

Logic 2013-10-28-a
------------
* A-line IV40: Ignore when 'SL10 Closed' or 'B1/B2 Off and
  A-line Kicker not enabled'

Logic 2013-10-15-a
------------
* Changes for next AMO run:
  -Remove NEH AMO Diagnostics Chamber Gate Valve
  -Remove ANEH AMO HFP Beam Stop
  -Remove NEH AMO End Station Ready
  -Remove NEH AMO High Field Physics Chamber Gate Valve Summary
  -Add NEH AMO LAMP VGC 30 Position truth tables

Logic 2013-10-10-a
------------
* Modify PSI Profile Monitor truth table to use YAGS:LTU1:743 inputs
  instead of OTRS:LTU1:743 inputs; changed truth table name to use 
  YAG instead of OTR

Logic 2013-10-04-a
------------
* Add logic for SXRSS with Chicane, Slit, and M3 Active (for M3 test)
* Remove previous M3 standalone logic; not needed
* Add LTU PSI profile monitor logic

Logic 2013-09-24-a
------------
* Add logic for BSY GLAST Target Flow Switch
* Add logic for SXRSS M3 (temporary for test of mirror only)
* Modify logic for BSY collimator 65, 67, 69, 71, 73, 75) flow switches
  so that they are not masked by "A-Line B1/B2 Is Not On AND A-Line Kicker Is Not Enabled"
* Revive Inactive BSY GLAST Target Klixon with new logic

Logic 2013-08-28-a
------------
* Modify Ignore Device A-Line B1/B2 Is Not ON and A-Line Kicker Is Not Enabled:
  - Replace power supply ON status with 2 new OFF status inputs from PPS
* Per R. Iverson, modify BSY PR45 logic to require D2 or TDUND to be IN if PR45 IN
* Per R. Iverson, M. Stanek remove SXR lower energy limit

Logic 2013-08-02-a
------------
* Add SXRSS logic and devices
* Active SXRSS logic assumes only slit and chicane are installed
* Inactive SXRSS logic added for potential future use:
  - All SXRSS devices installed
  - slit, chicane, M2, M3 installed

Logic 2013-07-19-a
------------
* Per CATER 109696, add fault if A-line IV26 NOT_OUT
* Add missing state names for B4C protection

Logic 2013-07-08-a
------------
* Per CATER request 109199, add fault if B4C IN 
  Existing B4C and ST1_ST2 interlocks remain in place
* Add protection of M1S mirror; cause fault if energy high and mirror not out

Logic 2013-06-15-a
------------
* Per Cater#108919
	Regarding mitigating potential B4C damage while running low energy.  
	In attendance were Rad Physics, Paul Miller, John Arthur, Roger, 
	Jim Turner, and M. Stanek.

	The interim solution for allowing low energy running without a BAS 2 mJ 
	limit was an agreement that we would not allow photons on the ST0 B4C piece 
	at all.  Sayed Rokni accepted that as an interim measure, we would use MPS 
	to ensure this condition.  

 	What is need required:
	If ST1/ST2 = Not OUT,  Zero rate fault the Gun.
 	This fault should have an 'ignore condition' when TDUND is in, 
	D2 is in, TD11 is in, BX01/02 is NOT ON, YAG BL211 is IN, BXG is ON.
	
	Existing B4C ST1_ST2 shall stay in place.




Logic 2013-06-13-a
------------
* Change D2 Stopper State Strings. Bit 0 and 1 were reversed. Change does not affect logic only readback status string

Logic 2013-06-03-a
------------
* Add logic for GLAST Target in BSY
* Add logic for Vac Valve BSY 4005 (IV40)

Logic 2013-05-27-a
------------
* Add New STPR 60 System C-code logic, all must be IN or OUT. 
	Change Ignore logic status to use new D2 IN bits and
	De-Activate D2 Logic from BCS
* Add TDUND IN to Prof BSY 45 logic per R.Iverson
* De-Activate A-Line LGPS/COR magnets from A-Line logic per R. Iverson and J. Nelson
	- lgps ab01 1010, 1090, 1950, 2050, 2750, 2850, and xcor 2890, 3212, 
	and ycor 2911, 3313.
* De-Activate A-Line GLAST Klixon per R. Iverson and J. Nelson



Logic 2012-12-10-a
------------
* Change logic for HXRSS Mode logic per Heinz-Dieter Nuhn:
	- HXRSS bend lints changed from 12.7<E < 14.2 to 10<E <15
	- Changed Seeded Mode definition to require Crystal to be IN
	- Changed Phase Shifter Mode to all HXRSS Bend to be at ANY state

Logic 2012-11-12-a
------------
* Add THZR:LTU1:741:IN_LMTSW, OUT_LMSW limit switches for new THZ-2
* removed a spare vacuum valve on LN 31, card 1, ch 9 so that we could add
  these limit switches

Logic    2012-10-a5-a
---------------------
* Add new logic to set lower limit of Beam Energy for Undulator per R. Iverson. 
	Interlocks monitors BEND:DMP1:400:INTOL_BLIM and will prevent E<2.3 GeV from
	Undulator.



Logic    2012-09-30-a
---------------------
* Modify logic for SXR:GMD:VGC_01, add S2 Stopper to ignore logic and renamed 
	logic table to include NEH at the beginning like the rest of NEH tables.
* Included upstream beam destinations to BCS PIC/LION inputs per HVS,
	and changed the logic name to BCS PIC/LION Raw Charge Threshold


Logic   2012-09-25-a from 2012-09-18-a
------------
* add new NEH SXR GMD Vacuum valve per Photon controls

Logic   2012-09-25-a DO NOT USE THIS VERSION
------------
* add new Dump PICMs 380, 381 at X-TCAV
* add new NEH SXR GMD Vacuum valve per Photon controls

Logic   2012-09-18-a
------------
* add new Dump Vacuum valve 355 at X-TCAV
* add new NEH XPP SH3 stopper status (no logic yet) per Photon controls

Logic   2012-06-29-a
------------
* Fixed bug in SL10 IS IN state, state # is 15 (ie 1111) not 4.
* Fixed a bug in HXRSS Mode Logic (is code=True) became false in Logic 2012-06-25-a, 
	Logic 2012-06-25-a should NO Longer be used!!

Logic   2012-06-25-a
------------
* De-activate some BSYA logic  per R. Iverson and C. hast
* Added PPS STOPPER Inputs	
* De-Activated A-Line Profile Monitor Summary logic per R. Iverson 

Logic   2012-06-05-a
------------
* De-activate some BSY PICS in Logic per R. Iverson
	PIC Unit numbers:
	LCLS  SLC 
	65	145	Trips often if PM1 is on-bypassed			
	67	155				
	69	165				
	71	175				
	73	185				
	75	195				
	76	205	

2012-05-21-a
------------
* Changes for CXI and MEC
* Logic for A-Line, removed unused inputs


2012-05-05-a
------------
    Add A-line FAST Valve VVFS:BSYA:2855 logic (past SL10)
    De-Activate 20-9 Slow Valve logic CATER # 99890
    A-Line_PICM_Logic_patch.json
    A-Line_Patch_Logic_Past_SL10_Apr2012_r1.json
    A-Line_Patch_Logic_Past_SL10_Apr2012_2_r1.json
    A-Line_Patch_Logic_Past_SL10_Apr2012_3_r1.json
    A-Line_Patch_Logic_Pre_SL10_Apr2012_r1.json
    MEC_XRT_Patch_Logic_File_May2012_R1.json
    XCOR BSYA  database input and logic
       
    A-LINE Devices that have not been implemented in Logic
    ######################################################
    #VGFS_BSYA_1410_FSG22_OK_STATE
    #VGFS_BSYA_3320_FSG29_OK_STATE  



2012-03-20-b
------------
* based on 2012-03-20-a and includes new CXI valve logic

2012-03-20-a
------------
* same logic as 2012-01-06-a but includes the config typo fix

2012-01-03-b
------------
* Added VVFS:DMP1:107 Fast Shutter
* New MEC Stopper XRT S6 Is In ignore device and logic


2011-11-29-b
------------
Same as 2011-11-29-a but all HXRSS logic Active.

2011-11-29-a
------------
* Logic Based of 2011-11-15-b, but De-Activated HXRSS not installed device logic
* Added new MEC Logic per Mark Arndt
* Add veto condition "M3H Mirror Is In Beam" to the following logic sections:
	** CXI KB2 VGC 02 Gate Valve Position
	** HF4 LAM VGC 01 Gate Valve Position

*And make one change to a description:
	* The logic in Section 18.2 of the 2011-11-15a version of the logic doc should be retitled "MEC XRT Attenuator Inspection Mirror Position".


2011-11-15-b
------------
*Same as 2011-11-07-b, but added CXI_MEC logic patch from 2011-11-15-a
*New devices inputs for A-LINK Kicker included in database 2011-11-15-a was not added to logic input list

2011-11-15-a
------------
*Same as 2011-11-07-a, but added new CXI_MEC logic patch 
*New devices inputs for A-LINK Kicker included in database 2011-11-15-a was not added to logic input list

2011-11-07-b
------------
*Same as 2011-10-31-b, 
*corrects "BXG is On" 0 bit input error which was set to BEND_IN20_751_OFF, corrected it to be BEND_IN20_231_OFF.
* Add new CXI and MEC inputs, but no associated logic.
* De-Activated TIU Sub-booster Ready for LI23 and LI24 per Stanek, these are now solid state and logic is not needed.

2011-11-07-a
------------
Same as 2011-10-31-a but HXRSS logic is all Activate
*corrects "BXG is On" 0 bit input error which was set to BEND_IN20_751_OFF, corrected it to be BEND_IN20_231_OFF.
* Add new CXI and MEC inputs, but no associated logic.
* De-Activated TIU Sub-booster Ready for LI23 and LI24 per Stanek, these are now solid state and logic is not needed.

2011-10-31-b
------------
Same as 2011-10-31-a but HXRSS logic is all Activate

2011-10-31-a
------------
Add HXRSS logic, but De-Activate all logic expect Raft (BMLN) IN/OUT logic table and Chicane Bend ON/OFF

2011-09-19-a
------------
Per Mark Arndt:
* New logic patch file for one new MEC logic loop.

* A diamond window was put in on XPP. We need to change the logic in "XPP SB2 VGC 01 Gate Valve Position" such that beam is allowed up to 120 Hz when the valve is Open or Closed, but dumped when Moving or Broken.


2011-08-10-a
------------
Fixed error in M3H Ignore logic definitions. 

2011-08-09-a
------------
* Per Mark Arndt, made lots of edits to CXI, XPP,MEC logic tables and added new ignore devices M3H Mirror Is In Beam and M3H Mirror Is Out of Beam. See 2011-08-09-a/logic_log for details.


2011-08-01-a
------------
* Per Iverson, updated logic for "BYKIK Readback Signal" to be ignored when D2 is IN
* Updated the following logic table names to fix typo
	DG2 Diagnostic Stopper Position  from	DG2 Diagnostic Stopper Poistion
	UM6 Diagnostic Stopper Position	 from	UM6 Diagnostic Stopper Poistion
	PPS Stopper S5B Position	 from 	PPS Stopper S5B Poistion

2011-07-12-a
------------
* Per Mark Arndt, 
Config and Logic changes are:

Link Node 40 card 1, channel 16  is now CXI_DSU_MMM_07_B_POSITION 
	becomes   CXI_DSD_MMS_07_B_POSITION
Link Node 40 card 6, channel 2   is now XCS_DG3_VGC_01_OPN_DI_POSITION
	becomes   CXI_DSU_MMS_07_B_POSITION

*XCS_DG3_VGC_01_OPN_DI_POSITION is removed from configuration 
	DB and logic DB device list. It was not used on any
	logic tables.

* Add new device (rename a junk name to new device
	CXI_DSD_MMS_07_B_POSITION)
* Change name of CXI_DSU_MMM_07_B_POSITION to CXI_DSU_MMS_07_B_POSITION
* Add revised CXI_Config4 logic C code
* Update CXI_Config5 with name modification (CXI_DSU_MMM_07_B_POSITION 
	to CXI_DSU_MMS_07_B_POSITION)


2011-07-05-a
------------
* Per Mark Arndt, add ignore devices:

  to "UM6 Diagnostic Stopper Poistion" [sic]:
    "Stopper SH1 Is In",
    "Stopper SH2 Is In",
    "TD11 Is In",
    "TDUND Is In",
    "ST1/ST2 Are In"  

  to "DG2 Diagnostic Stopper Poistion" [sic]:
    "Stopper SH1 Is In",
    "Stopper SH2 Is In",
    "TD11 Is In",
    "TDUND Is In",
    "ST1/ST2 Are In",
    "Diag Stopper HFX UM6 Is In"  

  to "XCS SB1 VGC 01 Gate Valve Position":
    "Stopper XRT S5 Is In"

  to "XCS SB1 VGC 02 Gate Valve Position":
    "Stopper XRT S5 Is In"

  to "XCS SB2 VGC 01 Gate Valve Position":
    "Stopper XRT S5 Is In"

  to "XCS SB1 Diagnostic Stopper Position":
    "Stopper XRT S5 Is In"

  and add new devices:

    HXX_HXM_MMS_01_B_POSITION
    HXX_MPS_PLC_01_OK_STATUS
    STPR_XRT1_1_S4IN_POSITION
    STPR_XRT1_1_S4OUT_POSITION
    STPR_XRT1_1_S6IN_POSITION
    STPR_XRT1_1_S6OUT_POSITION
    XCS_MPS_PLC_01_OK_STATUS
    XPP_MPS_PLC_01_OK_STATUS

2011-06-28-a
------------
* Per Mark Arndt, add logic tables:

"XCS SB1 VGC 01 Gate Valve Position"
"XCS SB1 VGC 02 Gate Valve Position"
"XCS SB2 VGC 01 Gate Valve Position"
"XCS SB1 Diagnostic Stopper Position"

  and remove logic tables:

"NEH AMO Beam Shutter Summary"
"HFX:MON:VGC:03 Gate Valve Position"

  and add ignore devices:

"Diag Stopper XCS SB1 Is In"
"XCS Is Not In Main Line"

2011-06-17-a
------------
* Fix bug introduced in 2011-06-15-a:
  Remove ignore condition XPP SB2 VGC 01 Gate Valve Position

2011-06-16-a **Bug in this version; DO NOT USE**
------------
* Fix bug introduced in 2011-06-15-a:
  Restored ignore condition XPP-NH3-POS-00 Beamline Is In, which had been inadvertently deleted.
   

2011-06-15-a **Bug in this version; DO NOT USE**
------------
* Per Mark Arndt
* Add XPP logic table:
  "XPP SB2 BGC 01 Gate Valve Position"
* Add ignore condition:
  "XPP-NH3-POS0-00 Beamline Is Not In" 
* Remove obsolete CXI logic table:
  "CXI CS PAD Damage Fault"

2011-05-31-a
------------
* Per Mark Arndt and XPP, add logic tables:
"HX3 MON VGC 01 Gate Valve Position" 
"HX2 UVD VGC 01 Gate Valve Position"

2011-05-25-b
------------
* Per Mark Arndt and CXI request, added new CXI inputs. 
*Added D2 stopper inputs,  Add D2 as ignore logic device.
*RTD past D2.
*ADD TD11 to Ignore logic for BSY valves per Iverson.

2011-05-25-a
------------
*IMPORTANT IMPORTANT IMPORTANT 
	NOTE: reverted back to logic 2010-09-28-a because 
	everything in logic sqlite files from then till 
	now was malformed. Recreated all logic changes 
	so that logic 2011-02-26-a and 2011-05-25-a 
	are equivalent, but 2011-05-25-a has db issues 
	resolve and extra S5 Position Logic. Added 
	AutoIncroment to sqlite Mpslogic.mpl tables.

2011-02-26-a
------------
* Per Mark Arndt and CXI request, reverted back to CXI MPS CFG 4 CONFID logic from "CXI Configuration 4 Summary". Created new logic for "CXI CS-PAD-Damge Fault" based on EPICS input. After down input should move to hardwired. This logic is based on parent logic 2011-02-02-a.

2011-02-25-a
------------
* Per Mark Arndt and CXI request, temporarily changed CXI MPS CFG 4 CONFID logic from "CXI Configuration 4 Summary" to "CXI CS-PAD-Damge Fault". Changes should be backed out when CXI changes can support a proper protection design.

2011-02-02-a
------------
* Deactivate "PR1_2 Prof Summary" and "Dev 50PR3 Prof" from active logic per R. Iverson Jan 2011.

2011-01-08-a
------------
* Changed logic table for  table "Gun RF Peak Power 20-6", signal is OK in the low state and FAULTED in high state.

2010-12-06-a
------------
* Add logic for CXI Config 1-7 and PLC_OK Status logic 


2010-12-01-a
------------
* Removed extra HXX:MXT:VGC_01:OPN_DI Position input and removed from logic 


2010-11-29-a
------------
* Added CXI logic per Mark Arndt,
* De-activated logic table TIU:PLIC Summary in LI29

2010-09-28-a
------------
* Changed name of input TRHZ:DMP1:310 to THZR:DMP1:350

2010-09-24-a
------------
* Add new VVMG:DMP1:743
* UnActivate Logic for, BSY Fast Gauges G1, G10, G12, G4 
* UnActivate Logic for, BSY BEND B11 (new supple not connected)

2010-08-30-a
------------
* Modified "NEH2 HXRAY StrongBack 1 Isolation Valve HX2:SB1:VGC:01" to inactive 
* Added "NEH AMO End Station Ready AMO-EXP-MPS-01"

2010-08-17-a
------------
* Added BYKICK Watchdog (no logic added, only device)

2010-08-11-a
------------
* Added BSYA PICS 1701A and 1701B

2010-08-09-a
------------
* Modified BSYA device logic to ignore BYKICK rates.

2010-08-05-a
------------
* Modified LN25 BSYA PIC truth tables to be ignored when BSYA B1/B2 is NOT_ON
* Added BSYA Prof Summary

2010-07-09-b
------------
* Added LN25 PIC truth tables

2010-07-09-a
------------
* Added LN11 and LN22 PIC truth tables

2010-07-06-a
------------
* Added LN16 PIC truth tables

2010-06-30-a
------------
* !!! Parent: 2010-06-21-a
* !!! Does not include updates from 2010-06-22-a
* Corrects "Flowswitch CE11" logic

2010-06-22-a
------------
* Added PIC truth tables for LNs 11, 16, and 22

2010-06-21-a
------------
* Renamed truth tables

2010-06-14-a
------------
* Combined toroid comparator logic tables.
* Updated toroid comparator logic table and state names.
* Ignoring IM02/IM03 when BX01/BX02 is off.

2010-05-25-a
------------
* Reversed "MPS Mechanical Shutter Position" logic.  Device is not fail-safe.

2010-05-20-a
------------
* Applied patch patch-bsy.json

2010-05-19-b
------------
* Added BLM:UND1:4 timing check

2010-05-19-a
------------
* Wakefield shield straight ahead is ignored when BXG is on

2010-05-18-b
------------
* Corrected toroid logic polarity

2010-05-18-a
------------
* Added patch patch-in20-li24

2010-05-17-a
------------
* Added BX01/BX02 and BXG on/off ignore conditions and rate limiting

2010-05-12-a
------------
* Removed "Fast Valve VVFS LI20 Position"