1. LTU vertical dechirper gap limit switch change. Previously both gap switches were AND-ed into single link node input. Now there are 2 new switches with independent status. Update logic accordingly. Switch status comes through motion control system and is not fail-safe if motion control panel loses power. Rick Iverson verbally approved this. Email sent to him: Date: Mon, 14 Dec 2015 11:15:19 -0800 (PST) From: Sonya Hoobler To: Richard H. Iverson Cc: Ziga Oven Subject: dechirper gap limit switches Hi Rick, A couple things: 1. Ziga and Mark have been working on the modifications to the motion control -> MPS panel for the gap limit switches and have identified a failure mode that would not be fail-safe: If the motion control chassis is powered off, the gap limit switch inputs to the MPS will appear 'OK'. We prefer all MPS failure modes to be fail-safe, but this one is not because we receive these inputs via the motion control system. Ideally, MPS would have its own dedicated switches. Please let me know if you think this is acceptable. 2. Mark would like to pull the existing panel from the field in order to modify it before the January PAMM. To do this, we would have to bypass the MPS protection for the minimum gap until 1/6. (All other dechirper interlocks would still be active.) I asked Ziga if he could do something to make it harder for someone to inadvertently move the dechirpers and he suggested powering off the motion control chassis. It is possible that something could be done in software instead. Please let us know if you think this is reasonable. Thanks, Sonya 2. Fix XRT S5 state names: moving and broken were reversed 3. Remove inactive and duplicate truth table 'VVMG LTU1 505 Position' [sonya@lcls-dev2 algorithm]$ sdiff -bs 2015-11-09-a/doc/MPSLogicDocumentation.txt 2015-12-17-a/doc/MPSLogicDocumentation.txt .. title:: MPS Logic 2015-11-09-a | .. title:: MPS Logic 2015-12-17-a Broken F F 0 Hz 0 Hz | Moving F F 0 Hz 0 Hz Moving T T 0 Hz 0 Hz | Broken T T 0 Hz 0 Hz ============= = ==================== ==================== === | ============================ = = ==================== ======= Name A Pockels Cell Mechanical Shutter | Name B A Pockels Cell Mechan ============= = ==================== ==================== === | ============================ = = ==================== ======= Gap too small F 0 Hz 0 Hz | Both ends gap too small F F 0 Hz Gap Ok T 120 Hz 120 Hz | Downstream end gap too small F T 0 Hz ============= = ==================== ==================== === | Upstream end gap too small T F 0 Hz > Gap ok T T 120 Hz > ============================ = = ==================== ======= > B = DCHP_LTU1_545_GAP_LIMSW_POSZ_POSITION