Only one change from last version in CVS. But many many changes since last version used in production (2015-01-07-a). To compare against that version, see directory logic_diff_review. 1. Add "TD11 Position" truth table Zero-rate if TD11 Moving or Broken (Not sure why this was not already in the logic.) [sonya@lcls-dev2 algorithm]$ sdiff -bs 2015-03-04-a/doc/MPSLogicDocumentation.txt 2015-03-02-c/doc/MPSLogicDocumentation.txt .. title:: MPS Logic 2015-03-04-a | .. title:: MPS Logic 2015-03-02-c TD11 Position < ------------- < ====== = = ==================== ==================== ======== < Name B A Pockels Cell Mechanical Shutter B < ====== = = ==================== ==================== ======== < Moving F F 0 Hz 0 Hz < Out F T 120 Hz 120 Hz < In T F 120 Hz 120 Hz < Broken T T 0 Hz 0 Hz < ====== = = ==================== ==================== ======== < < Where:: < < A = TD11_OUT_LIMIT_STATE < B = TD11_IN_LIMIT_STATE < < <