***** Non-linear logic that is only to be used for LTU Dechirper Commissioning ***** Based on 2015-09-04-a with changes shown below. Add new commissioning logic for LTU Dechirper (except for BLF logic, added in previous release). Details can be found here: https://slacspace.slac.stanford.edu/sites/controls/specialprojects/dechirper/Documents/Dechirper%20MPS/Dechirper_MPS.docx [sonya@lcls-dev2 algorithm]$ sdiff -bs 2015-09-08-z/doc/MPSLogicDocumentation.txt 2015-09-04-a/doc/MPSLogicDocumentation.txt .. title:: MPS Logic 2015-09-08-z | .. title:: MPS Logic 2015-09-04-a LTU Dechirper Commissioning - BPM 550 Watchdog < ---------------------------------------------- < ==================== = ==================== ================= < Name A Pockels Cell Mechanical Shutt < ==================== = ==================== ================= < BPM 550 not updating F 0 Hz 0 < Ok T 120 Hz 120 < ==================== = ==================== ================= < < Where:: < < A = DCHP_LTU1_545_WDOG_SUM_STATE < < < LTU Dechirper Commissioning - BPM 550 X/Y Position < -------------------------------------------------- < ========== = ==================== ==================== ====== < Name A Pockels Cell Mechanical Shutter < ========== = ==================== ==================== ====== < Out of tol F 0 Hz 0 Hz < Ok T 120 Hz 120 Hz < ========== = ==================== ==================== ====== < < Where:: < < A = DCHP_LTU1_545_BPM_INTOL_THRESHOLD < < < LTU Dechirper Commissioning - TDUND Must Be In < ---------------------------------------------- < ====== = ==================== ==================== ========== < Name A Pockels Cell Mechanical Shutter BYK < ====== = ==================== ==================== ========== < Not In F 0 Hz 0 Hz < In T 10 Hz 10 Hz < ====== = ==================== ==================== ========== < < Where:: < < A = TDUND_IN_POSITION < < <