******************************************* **************** Logic Add **************** ******************************************* Device 'MPS_UNDS_1_SXRSS_GUARDIAN_ON_STATE' added to the logic database. Device 'MPS_UNDS_1_SXRSS_GUARDIAN_OK_STATE' added to the logic database. Device 'MPS_UNDS_1_CBLM_RMON_STATE_STATE' added to the logic database. Device 'MPS_UNDH_1_CBLM_RMON_STATE_STATE' added to the logic database. Device 'MPS_UNDH_1_CBLM_WDOG_STATE_STATE' added to the logic database. Device 'MPS_UNDS_1_CBLM_WDOG_STATE_STATE' added to the logic database. ====================================== Adding SXRSS Guardian OK Added truth table "SXRSS Guardian OK" (2052) Ignored when STCLTS Is In Ignored when TD11 Is In Ignored when TDUNDB Is In Ignored when YAG01 Is In Ignored when YAG02 Is In Ignored when SXRSS SLIT Is Out Input 0: MPS_UNDS_1_SXRSS_GUARDIAN_OK_STATE Adding state "Not OK" Gun Linac: None Mechanical Shutter: None BYKIK: None Laser Heater Shutter: None Gun HXR: None Gun SXR: None BYKIKS: 0 Adding state "OK" Gun Linac: None Mechanical Shutter: None BYKIK: None Laser Heater Shutter: None Gun HXR: None Gun SXR: None BYKIKS: 120 Adding SXRSS Guardian ON Added truth table "SXRSS Guardian ON" (2053) Ignored when STCLTS Is In Ignored when TD11 Is In Ignored when TDUNDB Is In Ignored when YAG01 Is In Ignored when YAG02 Is In Ignored when SXRSS SLIT Is Out Input 0: MPS_UNDS_1_SXRSS_GUARDIAN_ON_STATE Adding state "Not OK" Gun Linac: None Mechanical Shutter: None BYKIK: None Laser Heater Shutter: None Gun HXR: None Gun SXR: None BYKIKS: 0 Adding state "OK" Gun Linac: None Mechanical Shutter: None BYKIK: None Laser Heater Shutter: None Gun HXR: None Gun SXR: None BYKIKS: 120 Adding SXR CBLM PMT High Voltage Added truth table "SXR CBLM PMT High Voltage" (2054) Ignored when STCLTS Is In Ignored when TD11 Is In Ignored when TDUNDB Is In Ignored when YAG01 Is In Ignored when YAG02 Is In Input 0: MPS_UNDS_1_CBLM_RMON_STATE_STATE Adding state "Not OK" Gun Linac: None Mechanical Shutter: None BYKIK: None Laser Heater Shutter: None Gun HXR: None Gun SXR: None BYKIKS: 0 Adding state "OK" Gun Linac: None Mechanical Shutter: None BYKIK: None Laser Heater Shutter: None Gun HXR: None Gun SXR: None BYKIKS: 120 Adding SXR CBLM Alive and Updating Added truth table "SXR CBLM Alive and Updating" (2055) Ignored when STCLTS Is In Ignored when TD11 Is In Ignored when TDUNDB Is In Ignored when YAG01 Is In Ignored when YAG02 Is In Input 0: MPS_UNDS_1_CBLM_WDOG_STATE_STATE Adding state "Not OK" Gun Linac: None Mechanical Shutter: None BYKIK: None Laser Heater Shutter: None Gun HXR: None Gun SXR: None BYKIKS: 0 Adding state "OK" Gun Linac: None Mechanical Shutter: None BYKIK: None Laser Heater Shutter: None Gun HXR: None Gun SXR: None BYKIKS: 120 Adding HXR CBLM Alive and Updating Added truth table "HXR CBLM Alive and Updating" (2056) Ignored when Stopper: BSY D2 Summary Is In Ignored when TD11 Is In Ignored when TDUND Is In Ignored when YAG01 Is In Ignored when YAG02 Is In Input 0: MPS_UNDH_1_CBLM_WDOG_STATE_STATE Adding state "Not OK" Gun Linac: None Mechanical Shutter: None BYKIK: None Laser Heater Shutter: None Gun HXR: None Gun SXR: None BYKIKS: 0 Adding state "OK" Gun Linac: None Mechanical Shutter: None BYKIK: None Laser Heater Shutter: None Gun HXR: None Gun SXR: None BYKIKS: 120 Adding HXR CBLM PMT High Voltage Added truth table "HXR CBLM PMT High Voltage" (2057) Ignored when Stopper: BSY D2 Summary Is In Ignored when TD11 Is In Ignored when TDUND Is In Ignored when YAG01 Is In Ignored when YAG02 Is In Input 0: MPS_UNDH_1_CBLM_RMON_STATE_STATE Adding state "Not OK" Gun Linac: None Mechanical Shutter: None BYKIK: None Laser Heater Shutter: None Gun HXR: None Gun SXR: None BYKIKS: 0 Adding state "OK" Gun Linac: None Mechanical Shutter: None BYKIK: None Laser Heater Shutter: None Gun HXR: None Gun SXR: None BYKIKS: 120 ====================================== Device 'MPLN_FEES_1_CRIXMCFASTFLT_STATE' added to the logic database. Device 'MPLN_FEES_1_CRIXVACFASTFLT_STATE' added to the logic database. Device 'MPLN_FEES_1_QRIXMCFASTFLT_STATE' added to the logic database. Device 'MPLN_FEES_1_QRIXVACFASTFLT_STATE' added to the logic database. Device 'MPLN_FEES_1_TXIVACFASTFLT_STATE' added to the logic database. Device 'MPLN_FEES_2_TXIVACFASTFLT_STATE' added to the logic database. Device 'MPLN_FEES_1_TXIMCFASTFLT_STATE' added to the logic database. Device 'MPLN_FEES_1_TXIOPTFASTFLT_STATE' added to the logic database. ====================================== ====================================== ******************************************** **************** Device Add **************** ******************************************** The following devices will be added: 138 2 16 MPS UNDS 1SXRSS_GUARDIAN_ON STATE IS_FAULTED IS_OK true MPS_UNDS_1_SXRSS_GUARDIAN_ON_STATE 138 2 1 MPS UNDS 1SXRSS_GUARDIAN_OK STATE IS_FAULTED IS_OK true MPS_UNDS_1_SXRSS_GUARDIAN_OK_STATE 138 2 2 MPS UNDS 1 CBLM_RMON_STATE STATE IS_FAULTED IS_OK true MPS_UNDS_1_CBLM_RMON_STATE_STATE 139 2 10 MPS UNDH 1 CBLM_RMON_STATE STATE IS_FAULTED IS_OK true MPS_UNDH_1_CBLM_RMON_STATE_STATE 139 2 11 MPS UNDH 1 CBLM_WDOG_STATE STATE IS_FAULTED IS_OK true MPS_UNDH_1_CBLM_WDOG_STATE_STATE 138 2 3 MPS UNDS 1 CBLM_WDOG_STATE STATE IS_FAULTED IS_OK true MPS_UNDS_1_CBLM_WDOG_STATE_STATE not lp is lp fault is false Adding new Link Node Channel 138.2.16 to database Check if already in ZFAULT: ZDEVICE=MPS_UNDS_1_SXRSS_GUARDIAN_ON and ZNAME=STATE Not found, so adding PV Fault"MPS_UNDS_1_SXRSS_GUARDIAN_ON" STATE Added Channel 138 2 16 -- MPS_UNDS_1_SXRSS_GUARDIAN_ON STATE not lp is lp fault is false Adding new Link Node Channel 138.2.1 to database Check if already in ZFAULT: ZDEVICE=MPS_UNDS_1_SXRSS_GUARDIAN_OK and ZNAME=STATE Not found, so adding PV Fault"MPS_UNDS_1_SXRSS_GUARDIAN_OK" STATE Added Channel 138 2 1 -- MPS_UNDS_1_SXRSS_GUARDIAN_OK STATE not lp is lp fault is false Adding new Link Node Channel 138.2.2 to database Check if already in ZFAULT: ZDEVICE=MPS_UNDS_1_CBLM_RMON_STATE and ZNAME=STATE Not found, so adding PV Fault"MPS_UNDS_1_CBLM_RMON_STATE" STATE Added Channel 138 2 2 -- MPS_UNDS_1_CBLM_RMON_STATE STATE not lp is lp fault is false Adding new Link Node Channel 139.2.10 to database Check if already in ZFAULT: ZDEVICE=MPS_UNDH_1_CBLM_RMON_STATE and ZNAME=STATE Not found, so adding PV Fault"MPS_UNDH_1_CBLM_RMON_STATE" STATE Added Channel 139 2 10 -- MPS_UNDH_1_CBLM_RMON_STATE STATE not lp is lp fault is false Adding new Link Node Channel 139.2.11 to database Check if already in ZFAULT: ZDEVICE=MPS_UNDH_1_CBLM_WDOG_STATE and ZNAME=STATE Not found, so adding PV Fault"MPS_UNDH_1_CBLM_WDOG_STATE" STATE Added Channel 139 2 11 -- MPS_UNDH_1_CBLM_WDOG_STATE STATE not lp is lp fault is false Adding new Link Node Channel 138.2.3 to database Check if already in ZFAULT: ZDEVICE=MPS_UNDS_1_CBLM_WDOG_STATE and ZNAME=STATE Not found, so adding PV Fault"MPS_UNDS_1_CBLM_WDOG_STATE" STATE Added Channel 138 2 3 -- MPS_UNDS_1_CBLM_WDOG_STATE STATE ====================================== The following devices will be added: 216 2 9 MPLN FEES 1 CRIXMCFASTFLT STATE IS_FAULTED IS_OK true CRIX Motion Fast Fault 216 2 10 MPLN FEES 1 CRIXVACFASTFLT STATE IS_FAULTED IS_OK true CRIX Vac Fast Fault 216 2 11 MPLN FEES 1 QRIXMCFASTFLT STATE IS_FAULTED IS_OK true QRIX Motion Fast Fault 216 2 12 MPLN FEES 1 QRIXVACFASTFLT STATE IS_FAULTED IS_OK true QRIX Vac Fast Fault 216 2 13 MPLN FEES 1 TXIVACFASTFLT STATE IS_FAULTED IS_OK true TXI Vac Fast Fault 1 216 2 14 MPLN FEES 2 TXIVACFASTFLT STATE IS_FAULTED IS_OK true TXI Vac Fast Fault 2 216 2 15 MPLN FEES 1 TXIMCFASTFLT STATE IS_FAULTED IS_OK true TXI Motion Fast Fault 216 2 16 MPLN FEES 1 TXIOPTFASTFLT STATE IS_FAULTED IS_OK true TXI Optics Fast Fault not lp is lp fault is false Adding new Link Node Card 216.2 to database Adding new Link Node Channel 216.2.9 to database Check if already in ZFAULT: ZDEVICE=MPLN_FEES_1_CRIXMCFASTFLT and ZNAME=STATE Not found, so adding PV Fault"MPLN_FEES_1_CRIXMCFASTFLT" STATE Added Channel 216 2 9 -- MPLN_FEES_1_CRIXMCFASTFLT STATE not lp is lp fault is false Adding new Link Node Channel 216.2.10 to database Check if already in ZFAULT: ZDEVICE=MPLN_FEES_1_CRIXVACFASTFLT and ZNAME=STATE Not found, so adding PV Fault"MPLN_FEES_1_CRIXVACFASTFLT" STATE Added Channel 216 2 10 -- MPLN_FEES_1_CRIXVACFASTFLT STATE not lp is lp fault is false Adding new Link Node Channel 216.2.11 to database Check if already in ZFAULT: ZDEVICE=MPLN_FEES_1_QRIXMCFASTFLT and ZNAME=STATE Not found, so adding PV Fault"MPLN_FEES_1_QRIXMCFASTFLT" STATE Added Channel 216 2 11 -- MPLN_FEES_1_QRIXMCFASTFLT STATE not lp is lp fault is false Adding new Link Node Channel 216.2.12 to database Check if already in ZFAULT: ZDEVICE=MPLN_FEES_1_QRIXVACFASTFLT and ZNAME=STATE Not found, so adding PV Fault"MPLN_FEES_1_QRIXVACFASTFLT" STATE Added Channel 216 2 12 -- MPLN_FEES_1_QRIXVACFASTFLT STATE not lp is lp fault is false Adding new Link Node Channel 216.2.13 to database Check if already in ZFAULT: ZDEVICE=MPLN_FEES_1_TXIVACFASTFLT and ZNAME=STATE Not found, so adding PV Fault"MPLN_FEES_1_TXIVACFASTFLT" STATE Added Channel 216 2 13 -- MPLN_FEES_1_TXIVACFASTFLT STATE not lp is lp fault is false Adding new Link Node Channel 216.2.14 to database Check if already in ZFAULT: ZDEVICE=MPLN_FEES_2_TXIVACFASTFLT and ZNAME=STATE Not found, so adding PV Fault"MPLN_FEES_2_TXIVACFASTFLT" STATE Added Channel 216 2 14 -- MPLN_FEES_2_TXIVACFASTFLT STATE not lp is lp fault is false Adding new Link Node Channel 216.2.15 to database Check if already in ZFAULT: ZDEVICE=MPLN_FEES_1_TXIMCFASTFLT and ZNAME=STATE Not found, so adding PV Fault"MPLN_FEES_1_TXIMCFASTFLT" STATE Added Channel 216 2 15 -- MPLN_FEES_1_TXIMCFASTFLT STATE not lp is lp fault is false Adding new Link Node Channel 216.2.16 to database Check if already in ZFAULT: ZDEVICE=MPLN_FEES_1_TXIOPTFASTFLT and ZNAME=STATE Not found, so adding PV Fault"MPLN_FEES_1_TXIOPTFASTFLT" STATE Added Channel 216 2 16 -- MPLN_FEES_1_TXIOPTFASTFLT STATE ====================================== ***************************************************** **************** Device/Logic Delete **************** ***************************************************** Changes report ------------------ Deleted devices and their deleted associated logic: CBLM_UNDS_4410_ALIVE CBLM UNDS 4410 ALIVE CBLM_UNDH_1675_ALIVE CBLM UNDH 1675 ALIVE CBLM_UNDS_3410_ALIVE CBLM UNDS 3410 ALIVE CBLM_UNDS_3210_ALIVE CBLM UNDS 3210 ALIVE CBLM_UNDS_3110_ALIVE CBLM UNDS 3110 ALIVE CBLM_UNDH_3175_ALIVE CBLM UNDH 3175 ALIVE CBLM_UNDH_3675_ALIVE CBLM UNDH 3675 ALIVE CBLM_UNDS_2610_ALIVE CBLM UNDS 2610 ALIVE CBLM_UNDS_4310_ALIVE CBLM UNDS 4310 ALIVE CBLM_UNDS_3810_ALIVE CBLM UNDS 3810 ALIVE CBLM_UNDS_2910_ALIVE CBLM UNDS 2910 ALIVE CBLM_UNDH_1475_ALIVE CBLM UNDH 1475 ALIVE CBLM_UNDH_4675_ALIVE CBLM UNDH 4675 ALIVE CBLM_UNDH_3975_ALIVE CBLM UNDH 3975 ALIVE CBLM_UNDH_4275_ALIVE CBLM UNDH 4275 ALIVE CBLM_UNDH_2275_ALIVE CBLM UNDH 2275 ALIVE CBLM_UNDH_4375_ALIVE CBLM UNDH 4375 ALIVE CBLM_UNDH_2975_ALIVE CBLM UNDH 2975 ALIVE CBLM_UNDS_4110_ALIVE CBLM UNDS 4110 ALIVE CBLM_UNDH_3775_ALIVE CBLM UNDH 3775 ALIVE CBLM_UNDH_3475_ALIVE CBLM UNDH 3475 ALIVE CBLM_UNDH_3375_ALIVE CBLM UNDH 3375 ALIVE CBLM_UNDH_2775_ALIVE CBLM UNDH 2775 ALIVE CBLM_UNDH_3275_ALIVE CBLM UNDH 3275 ALIVE CBLM_UNDH_4075_ALIVE CBLM UNDH 4075 ALIVE CBLM_UNDS_4510_ALIVE CBLM UNDS 4510 ALIVE CBLM_UNDH_1575_ALIVE CBLM UNDH 1575 ALIVE CBLM_UNDS_2810_ALIVE CBLM UNDS 2810 ALIVE CBLM_UNDH_1875_ALIVE CBLM UNDH 1875 ALIVE CBLM_UNDS_4810_ALIVE CBLM UNDS 4810 ALIVE CBLM_UNDH_2875_ALIVE CBLM UNDH 2875 ALIVE CBLM_UNDH_2675_ALIVE CBLM UNDH 2675 ALIVE CBLM_UNDS_3710_ALIVE CBLM UNDS 3710 ALIVE CBLM_UNDH_3875_ALIVE CBLM UNDH 3875 ALIVE CBLM_UNDS_4610_ALIVE CBLM UNDS 4610 ALIVE CBLM_UNDS_3610_ALIVE CBLM UNDS 3610 ALIVE CBLM_UNDH_1775_ALIVE CBLM UNDH 1775 ALIVE CBLM_UNDH_2175_ALIVE CBLM UNDH 2175 ALIVE CBLM_UNDS_3510_ALIVE CBLM UNDS 3510 ALIVE CBLM_UNDH_4475_ALIVE CBLM UNDH 4475 ALIVE CBLM_UNDS_4010_ALIVE CBLM UNDS 4010 ALIVE CBLM_UNDS_3010_ALIVE CBLM UNDS 3010 ALIVE CBLM_UNDH_1975_ALIVE CBLM UNDH 1975 ALIVE CBLM_UNDH_4575_ALIVE CBLM UNDH 4575 ALIVE CBLM_UNDS_3910_ALIVE CBLM UNDS 3910 ALIVE CBLM_UNDH_4175_ALIVE CBLM UNDH 4175 ALIVE CBLM_UNDH_3575_ALIVE CBLM UNDH 3575 ALIVE CBLM_UNDS_4710_ALIVE CBLM UNDS 4710 ALIVE CBLM_UNDS_2710_ALIVE CBLM UNDS 2710 ALIVE CBLM_UNDH_1375_ALIVE CBLM UNDH 1375 ALIVE CBLM_UNDH_2075_ALIVE CBLM UNDH 2075 ALIVE CBLM_UNDH_2375_ALIVE CBLM UNDH 2375 ALIVE CBLM_UNDS_3310_ALIVE CBLM UNDS 3310 ALIVE CBLM_UNDH_2475_ALIVE CBLM UNDH 2475 ALIVE CBLM_UNDH_3075_ALIVE CBLM UNDH 3075 ALIVE CBLM_UNDS_4210_ALIVE CBLM UNDS 4210 ALIVE CBLM_UNDH_2575_ALIVE CBLM UNDH 2575 ALIVE ====================================== Changes report ------------------ Deleted devices and their deleted associated logic: CBLM_UNDH_2575_RMON CBLM UNDH 2575 HV MONITOR CBLM_UNDH_3375_RMON CBLM UNDH 3375 HV MONITOR CBLM_UNDH_4175_RMON CBLM UNDH 4175 HV MONITOR CBLM_UNDH_1575_RMON CBLM UNDH 1575 HV MONITOR CBLM_UNDH_1375_RMON CBLM UNDH 1375 HV MONITOR CBLM_UNDH_4375_RMON CBLM UNDH 4375 HV MONITOR CBLM_UNDS_3610_RMON CBLM UNDS 3610 HV MONITOR CBLM_UNDH_2975_RMON CBLM UNDH 2975 HV MONITOR CBLM_UNDS_3110_RMON CBLM UNDS 3110 HV MONITOR CBLM_UNDH_2675_RMON CBLM UNDH 2675 HV MONITOR CBLM_UNDS_3910_RMON CBLM UNDS 3910 HV MONITOR CBLM_UNDH_3775_RMON CBLM UNDH 3775 HV MONITOR CBLM_UNDS_2610_RMON CBLM UNDS 2610 HV MONITOR CBLM_UNDH_2275_RMON CBLM UNDH 2275 HV MONITOR CBLM_UNDS_3010_RMON CBLM UNDS 3010 HV MONITOR CBLM_UNDS_3310_RMON CBLM UNDS 3310 HV MONITOR CBLM_UNDH_1975_RMON CBLM UNDH 1975 HV MONITOR CBLM_UNDH_3475_RMON CBLM UNDH 3475 HV MONITOR CBLM_UNDS_4710_RMON CBLM UNDS 4710 HV MONITOR CBLM_UNDH_2775_RMON CBLM UNDH 2775 HV MONITOR CBLM_UNDS_4810_RMON CBLM UNDS 4810 HV MONITOR CBLM_UNDH_2175_RMON CBLM UNDH 2175 HV MONITOR CBLM_UNDS_2810_RMON CBLM UNDS 2810 HV MONITOR CBLM_UNDH_3275_RMON CBLM UNDH 3275 HV MONITOR CBLM_UNDS_4610_RMON CBLM UNDS 4610 HV MONITOR CBLM_UNDH_4575_RMON CBLM UNDH 4575 HV MONITOR CBLM_UNDH_2475_RMON CBLM UNDH 2475 HV MONITOR CBLM_UNDS_4510_RMON CBLM UNDS 4510 HV MONITOR CBLM_UNDS_4010_RMON CBLM UNDS 4010 HV MONITOR CBLM_UNDH_1875_RMON CBLM UNDH 1875 HV MONITOR CBLM_UNDH_3975_RMON CBLM UNDH 3975 HV MONITOR CBLM_UNDH_4275_RMON CBLM UNDH 4275 HV MONITOR CBLM_UNDS_2710_RMON CBLM UNDS 2710 HV MONITOR CBLM_UNDS_4210_RMON CBLM UNDS 4210 HV MONITOR CBLM_UNDS_4310_RMON CBLM UNDS 4310 HV MONITOR CBLM_UNDH_2875_RMON CBLM UNDH 2875 HV MONITOR CBLM_UNDS_4110_RMON CBLM UNDS 4110 HV MONITOR CBLM_UNDH_3175_RMON CBLM UNDH 3175 HV MONITOR CBLM_UNDS_2910_RMON CBLM UNDS 2910 HV MONITOR CBLM_UNDH_2075_RMON CBLM UNDH 2075 HV MONITOR CBLM_UNDS_3810_RMON CBLM UNDS 3810 HV MONITOR CBLM_UNDH_1775_RMON CBLM UNDH 1775 HV MONITOR CBLM_UNDS_3510_RMON CBLM UNDS 3510 HV MONITOR CBLM_UNDH_3575_RMON CBLM UNDH 3575 HV MONITOR CBLM_UNDS_3210_RMON CBLM UNDS 3210 HV MONITOR CBLM_UNDS_3710_RMON CBLM UNDS 3710 HV MONITOR CBLM_UNDH_1475_RMON CBLM UNDH 1475 HV MONITOR CBLM_UNDH_4075_RMON CBLM UNDH 4075 HV MONITOR CBLM_UNDH_3875_RMON CBLM UNDH 3875 HV MONITOR CBLM_UNDH_4675_RMON CBLM UNDH 4675 HV MONITOR CBLM_UNDH_2375_RMON CBLM UNDH 2375 HV MONITOR CBLM_UNDS_4410_RMON CBLM UNDS 4410 HV MONITOR CBLM_UNDH_4475_RMON CBLM UNDH 4475 HV MONITOR CBLM_UNDH_3075_RMON CBLM UNDH 3075 HV MONITOR CBLM_UNDS_3410_RMON CBLM UNDS 3410 HV MONITOR CBLM_UNDH_3675_RMON CBLM UNDH 3675 HV MONITOR CBLM_UNDH_1675_RMON CBLM UNDH 1675 HV MONITOR ====================================== [INFO] Macro with id:'755' associated with logic device 'MPS_UND1_950_SX_SS_UND_STATE' does not exist. Changes report ------------------ Deleted devices and their deleted associated logic: MPS_UND1_950_SX_SS_UND ====================================== Changes report ------------------ Deleted devices and their deleted associated logic: SIOC_FEES_MP01_HEARTBEAT SIOC FEES MP01 HEARTBEAT ======================================