From Mark Arndt, 22 June 2011 Things that need to be added: =============================== * Logic for new XCS devices. See attached patch logic file. * New definition for ignore device "Diag Stopper XCS SB1 Is In" based on XCS_SB1_STP_01_CLS_DI_POSITION = True. * New definition for ignore device "XCS Is Not In Main Line" based on XCS_SB_POS_HARD_POSITION = False. Things that need to be removed: ================================ * Logic for "DG2 Diagnostic Stopper Poistion". See my enclosed patch file for replacement logic for this device. (sonya: to do later) * Logic for "UM6 Diagnostic Stopper Poistion". See my enclosed patch file for replacement logic for this device. (sonya: to do later) * Logic for "NEH AMO Beam Shutter Summary". Device is no longer motorized and is safe in beam. * Logic "HFX:MON:VGC:03 Gate Valve Position". This is on the XCS/mono line and the instrument scientists have determined that monochromatic beam cannot damage the device. Things that need to be modified: =================================== * Correct the misspelling in title of section "PPS Stopper S5B Poistion". This obviously can be done later. In the next couple of weeks I'd like to come over with you or Matt at hand and use the GUI tp go through and make various title/label corrections. (sonya: to do later) --------------------------------------------------- From Mark Arndt, 24 June 2011 Logic for "XCS SB1 Diagnostic Stopper Position" should be ignored when "XCS Is Not In Main Line". This stopper can be moved in and out like the nearby valves. The instrument scientists say it's completely safe in the XCS/mono line. Sonya: I manually added this "ignore when" condition using the Java GUI. Hence XCS_MPS_Patch_Logic_File_June2011_r1.json will not reflect this change in logic.