#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../../dbd/MotionControl.dbd")
#! DBDEND


# motor channel Hy8601-01/0
record(motor, "WIRE:LI11:614:MOTR") {
  field(DESC, "WS11614 Wire Scanner Motion")
  field(SCAN, "Passive")
  field(DIR, "Neg")
  field(DTYP, "asynMotor")
  field(VELO, "850")
  field(VBAS, "250")
  field(VMAX, "850")
  field(ACCL, "0.1")
  field(OUT, "@asyn( Hy8601-01, 0)")
  field(MRES, "0.15625")
  field(SREV, "400")
  field(PREC, "0")
  field(EGU, "microns")
  field(DHLM, "28104")
  field(HOPR, "28104")
  field(DLLM, "-36500")
  field(LOPR, "-36500")
  field(DLY, "0")
  field(TWV, "1000")
  field(SET, "1")
  field(RDBD, "2")
  field(FOFF, "Frozen")
  field(FLNK, "WIRE:LI11:614:MOTRVALREST")
  field(PINI, "YES")
  field(PRIO, "HIGH")
  field(BDST, "0")
  field(BVEL, "250")
  field(BACC, "0.5")
  field(RDBL, "WIRE:LI11:614:LVPOS")
  info(autosaveFields, "DESC DIR VELO VBAS VMAX ACCL SREV PREC EGU DLY TWV RDBD BDST BVEL BACC RDBL RRES RTRY URIP HIHI LOLO HIGH LOW HHSV LLSV HSV LSV")
}

# Position of motor on WIRE:LI11:614
# updated regularly, when a specific event arrives
# from the event timing system, indicating that
# beam has arrived.  This is unused for collimators
# or other simple motion devices; it is important
# for wire scanners and other beam-synchronous
# devices.
# WARNING: The EVNT field is changed when calibrations
# are performed.  If problems are suspected with this,
# check the save and restore code in the sequencer,
# under calibrate.st, in the READY_TO_PROFILE state.
record(ai, "WIRE:LI11:614:POSN") {
  field(DESC, "WS11614 Current Position")
  field(DTYP, "asynInt32")
  field(EGU, "microns")
  field(INP, "@asyn(Hy8601-01 0)MOTOR_POSITION")
  field(SCAN, "Event")
  field(PRIO, "HIGH")
  field(EVNT, "201")
  field(LINR, "SLOPE")
  field(ROFF, "0")
  field(EOFF, "0")
  field(ESLO, "0.15625")
  field(FLNK, "WIRE:LI11:614:EFPOSN")
  field(PREC, "0")
  field(TSE, "-1")
}

#
# This record contains a simple value that changes per
# beam pulse; when WIRE:LI11:614 (WS11614)
# is scanning, it will have a non-zero value, and when
# moving to a start position or positioning to confirm
# an LVDT value, it will be zero.
#
record(ao, "WIRE:LI11:614:MASK") {
  field(DESC, "WS11614 Scan Mask")
  field(OMSL, "supervisory")
  field(SCAN, "Event")
  field(PRIO, "HIGH")
  field(EVNT, "201")
  field(DRVH, "4000000000")
  field(DRVL, "-4000000000")
  field(FLNK, "WIRE:LI11:614:EFMASK")
  field(TSE, "-1")
}

#
# This record takes the calibration offset from
# WIRE:LI11:614 (WS11614) and pushes
# it to the EOFF field in the POSN record, above.
# It is triggered by the state machine after a
# calibration is complete, or when the IOC starts.
#
record(ao, "WIRE:LI11:614:NEWOFFS") {
  field(DESC, "New WS11614 Cal")
  field(EGU, "microns")
  field(OMSL, "closed_loop")
  field(OIF, "Full")
  field(DOL, "WIRE:LI11:614:MOTR.OFF PP")
  field(DRVH, "4000000000")
  field(DRVL, "-4000000000")
  field(SCAN, "Passive")
  field(OUT, "WIRE:LI11:614:POSN.EOFF")
}

record(ao, "WIRE:LI11:614:MOTRVAL") {
  field(DESC, "WS11614 Value Proxy")
  field(EGU, "microns")
  field(OMSL, "supervisory")
  field(DRVH, "28104")
  field(DRVL, "-36500")
  field(SCAN, "Passive")
  field(OUT, "WIRE:LI11:614:MOTR.VAL")
  field(FLNK, "WIRE:LI11:614:MOTR")
}

record(ao, "WIRE:LI11:614:MOTRHI") {
  field(DESC, "Move WS11614 High")
  field(EGU, "microns")
  field(OMSL, "closed_loop")
  field(OIF, "Full")
  field(DOL, "WIRE:LI11:614:MOTR.HLM")
  field(DRVH, "4000000000")
  field(DRVL, "-4000000000")
  field(SCAN, "Passive")
  field(OUT, "WIRE:LI11:614:MOTR.VAL")
  field(FLNK, "WIRE:LI11:614:MOTR")
}

record(ao, "WIRE:LI11:614:MOTRLO") {
  field(DESC, "Move WS11614 Low")
  field(EGU, "microns")
  field(OMSL, "closed_loop")
  field(OIF, "Full")
  field(DOL, "WIRE:LI11:614:MOTR.LLM")
  field(DRVH, "4000000000")
  field(DRVL, "-4000000000")
  field(SCAN, "Passive")
  field(OUT, "WIRE:LI11:614:MOTR.VAL")
  field(FLNK, "WIRE:LI11:614:MOTR")
}

record(ao, "WIRE:LI11:614:RETRACT") {
  field(DESC, "WS11614 Retract")
  field(EGU, "microns")
  field(OMSL, "closed_loop")
  field(DOL, "WIRE:LI11:614:RETRACT_POSN")
  field(DRVH, "28104")
  field(DRVL, "-36500")
  field(SCAN, "Passive")
  field(OUT, "WIRE:LI11:614:MOTR.VAL")
  field(FLNK, "WIRE:LI11:614:MOTR")
}

record(ai, "WIRE:LI11:614:RETRACT_POSN") {
  field(DESC, "WS11614 Retract Position")
  field(VAL, "-36500")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

record(mbbo, "WIRE:LI11:614:MOTRVELCHOICE") {
  field(DESC, "WS11614 Value Proxy")
  field(OMSL, "supervisory")
  field(SCAN, "Passive")
  field(DTYP, "Raw Soft Channel")
  field(NOBT, "32")
  field(OUT, "WIRE:LI11:614:MOTR.VELO")
  field(ZRST, "Normal")
  field(ZRVL, "500")
  field(ONST, "Maximum")
  field(ONVL, "850")
  field(TWST, "Medium")
  field(TWVL, "500")
  field(THST, "Slow")
  field(THVL, "250")
}

record(fanout, "WIRE:LI11:614:SYNCMOTPROFILE") {
  field(DESC, "WS11614 Calib Profile Sync")
  field(SCAN, "Passive")
  field(SELM, "Mask")
  field(SELL, "7")
  field(LNK1, "WIRE:LI11:614:MOTPROFILE")
  field(LNK2, "WIRE:LI11:614:LVDTPROFILE")
  field(LNK3, "WIRE:LI11:614:CALIBSYNC")
}

#
# This record is processed at the end of an acquisition
# sequence.  The calibration state machine waits for it
# to become 0.  Specifically, it awaits processing.
#
record(event, "WIRE:LI11:614:CALIBSYNC") {
  field(DESC, "WS11614 Cal Delay Sync")
  field(VAL, "0")
  field(SCAN, "Passive")
  field(PINI, "YES")
}

record(compress, "WIRE:LI11:614:MOTPROFILE") {
  field(DESC, "WS11614 Motion Profile")
  field(SCAN, "Passive")
  field(ALG, "Circular Buffer")
  field(NSAM, "200")
  field(INP, "WIRE:LI11:614:POSN PP")
}

record(compress, "WIRE:LI11:614:LVDTPROFILE") {
  field(DESC, "WS11614 Measured Profile")
  field(SCAN, "Passive")
  field(ALG, "Circular Buffer")
  field(NSAM, "200")
  field(INP, "WIRE:LI11:614:LVRAW PP")
}

record(subArray, "WIRE:LI11:614:SUBLPROF") {
  field(DESC, "WS11614 Distance Region")
  field(SCAN, "Passive")
  field(MALM, "200")
  field(NELM, "200")
  field(INDX, "0")
  field(FTVL, "DOUBLE")
  field(INP, "WIRE:LI11:614:PLVDTPROFILE.VAL")
}

record(subArray, "WIRE:LI11:614:SUBMPROF") {
  field(DESC, "WS11614 Motion Region")
  field(SCAN, "Passive")
  field(MALM, "200")
  field(NELM, "200")
  field(INDX, "0")
  field(FTVL, "DOUBLE")
  field(INP, "WIRE:LI11:614:PMOTPROFILE.VAL")
}

record(waveform, "WIRE:LI11:614:PMOTPROFILE") {
  field(DESC, "WS11614 Prev Motion Profile")
  field(SCAN, "Passive")
  field(FTVL, "DOUBLE")
  field(EGU, "microns")
  field(NELM, "200")
  field(INP, "WIRE:LI11:614:MOTPROFILE")
  field(FLNK, "WIRE:LI11:614:SUBMPROF")
}

record(waveform, "WIRE:LI11:614:PLVDTPROFILE") {
  field(DESC, "WS11614 Prev Measured Profl")
  field(SCAN, "Passive")
  field(FTVL, "DOUBLE")
  field(EGU, "microns")
  field(NELM, "200")
  field(INP, "WIRE:LI11:614:LVDTPROFILE")
  field(FLNK, "WIRE:LI11:614:SUBLPROF")
}

record(ai, "WIRE:LI11:614:MOTRVALREST") {
  field(INP, "WIRE:LI11:614:MOTR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,0.5)
#! Record("WIRE:LI11:614:MOTR",160,62,0,0,"WIRE:LI11:614:MOTR")
#! Field("WIRE:LI11:614:MOTR.FLNK",16777215,1,"WIRE:LI11:614:MOTR.FLNK")
#! Field("WIRE:LI11:614:MOTR.RDBL",16777215,1,"WIRE:LI11:614:MOTR.RDBL")
#! Field("WIRE:LI11:614:MOTR.OFF",16777215,1,"WIRE:LI11:614:MOTR.OFF")
#! Field("WIRE:LI11:614:MOTR.HLM",16777215,1,"WIRE:LI11:614:MOTR.HLM")
#! Field("WIRE:LI11:614:MOTR.LLM",16777215,1,"WIRE:LI11:614:MOTR.LLM")
#! Field("WIRE:LI11:614:MOTR.VELO",16777215,1,"WIRE:LI11:614:MOTR.VELO")
#! Field("WIRE:LI11:614:MOTR.VAL",16777215,1,"WIRE:LI11:614:MOTR.VAL")
#! Record("WIRE:LI11:614:POSN",1000,544,0,0,"WIRE:LI11:614:POSN")
#! Field("WIRE:LI11:614:POSN.FLNK",16777215,1,"WIRE:LI11:614:POSN.FLNK")
#! Field("WIRE:LI11:614:POSN.EOFF",16777215,0,"WIRE:LI11:614:POSN.EOFF")
#! Field("WIRE:LI11:614:POSN.VAL",16777215,1,"WIRE:LI11:614:POSN.VAL")
#! Record("WIRE:LI11:614:MASK",1340,1352,0,0,"WIRE:LI11:614:MASK")
#! Field("WIRE:LI11:614:MASK.FLNK",16777215,1,"WIRE:LI11:614:MASK.FLNK")
#! Record("WIRE:LI11:614:NEWOFFS",720,612,0,0,"WIRE:LI11:614:NEWOFFS")
#! Field("WIRE:LI11:614:NEWOFFS.DOL",16777215,0,"WIRE:LI11:614:NEWOFFS.DOL")
#! Link("WIRE:LI11:614:NEWOFFS.DOL","WIRE:LI11:614:MOTR.OFF")
#! Field("WIRE:LI11:614:NEWOFFS.OUT",16777215,1,"WIRE:LI11:614:NEWOFFS.OUT")
#! Link("WIRE:LI11:614:NEWOFFS.OUT","WIRE:LI11:614:POSN.EOFF")
#! Record("WIRE:LI11:614:MOTRVAL",860,986,0,0,"WIRE:LI11:614:MOTRVAL")
#! Field("WIRE:LI11:614:MOTRVAL.OUT",16777215,0,"WIRE:LI11:614:MOTRVAL.OUT")
#! Link("WIRE:LI11:614:MOTRVAL.OUT","WIRE:LI11:614:MOTR.VAL")
#! Field("WIRE:LI11:614:MOTRVAL.FLNK",16777215,0,"WIRE:LI11:614:MOTRVAL.FLNK")
#! Link("WIRE:LI11:614:MOTRVAL.FLNK","WIRE:LI11:614:MOTR")
#! Record("WIRE:LI11:614:MOTRHI",860,1238,0,0,"WIRE:LI11:614:MOTRHI")
#! Field("WIRE:LI11:614:MOTRHI.DOL",16777215,0,"WIRE:LI11:614:MOTRHI.DOL")
#! Link("WIRE:LI11:614:MOTRHI.DOL","WIRE:LI11:614:MOTR.HLM")
#! Field("WIRE:LI11:614:MOTRHI.OUT",16777215,0,"WIRE:LI11:614:MOTRHI.OUT")
#! Link("WIRE:LI11:614:MOTRHI.OUT","WIRE:LI11:614:MOTR.VAL")
#! Field("WIRE:LI11:614:MOTRHI.FLNK",16777215,0,"WIRE:LI11:614:MOTRHI.FLNK")
#! Link("WIRE:LI11:614:MOTRHI.FLNK","WIRE:LI11:614:MOTR")
#! Record("WIRE:LI11:614:MOTRLO",860,1558,0,0,"WIRE:LI11:614:MOTRLO")
#! Field("WIRE:LI11:614:MOTRLO.DOL",16777215,0,"WIRE:LI11:614:MOTRLO.DOL")
#! Link("WIRE:LI11:614:MOTRLO.DOL","WIRE:LI11:614:MOTR.LLM")
#! Field("WIRE:LI11:614:MOTRLO.OUT",16777215,0,"WIRE:LI11:614:MOTRLO.OUT")
#! Link("WIRE:LI11:614:MOTRLO.OUT","WIRE:LI11:614:MOTR.VAL")
#! Field("WIRE:LI11:614:MOTRLO.FLNK",16777215,0,"WIRE:LI11:614:MOTRLO.FLNK")
#! Link("WIRE:LI11:614:MOTRLO.FLNK","WIRE:LI11:614:MOTR")
#! Record("WIRE:LI11:614:MOTRVELCHOICE",840,1884,0,0,"WIRE:LI11:614:MOTRVELCHOICE")
#! Field("WIRE:LI11:614:MOTRVELCHOICE.OUT",16777215,0,"WIRE:LI11:614:MOTRVELCHOICE.OUT")
#! Link("WIRE:LI11:614:MOTRVELCHOICE.OUT","WIRE:LI11:614:MOTR.VELO")
#! Record("WIRE:LI11:614:SYNCMOTPROFILE",1700,598,0,0,"WIRE:LI11:614:SYNCMOTPROFILE")
#! Field("WIRE:LI11:614:SYNCMOTPROFILE.LNK1",16777215,0,"WIRE:LI11:614:SYNCMOTPROFILE.LNK1")
#! Link("WIRE:LI11:614:SYNCMOTPROFILE.LNK1","WIRE:LI11:614:MOTPROFILE")
#! Field("WIRE:LI11:614:SYNCMOTPROFILE.LNK2",16777215,1,"WIRE:LI11:614:SYNCMOTPROFILE.LNK2")
#! Link("WIRE:LI11:614:SYNCMOTPROFILE.LNK2","WIRE:LI11:614:LVDTPROFILE")
#! Field("WIRE:LI11:614:SYNCMOTPROFILE.LNK3",16777215,1,"WIRE:LI11:614:SYNCMOTPROFILE.LNK3")
#! Link("WIRE:LI11:614:SYNCMOTPROFILE.LNK3","WIRE:LI11:614:CALIBSYNC")
#! Record("WIRE:LI11:614:CALIBSYNC",1980,860,0,0,"WIRE:LI11:614:CALIBSYNC")
#! Record("WIRE:LI11:614:MOTPROFILE",1380,706,0,1,"WIRE:LI11:614:MOTPROFILE")
#! Field("WIRE:LI11:614:MOTPROFILE.INP",16777215,0,"WIRE:LI11:614:MOTPROFILE.INP")
#! Link("WIRE:LI11:614:MOTPROFILE.INP","WIRE:LI11:614:POSN.VAL")
#! Field("WIRE:LI11:614:MOTPROFILE.VAL",16777215,0,"WIRE:LI11:614:MOTPROFILE.VAL")
#! Record("WIRE:LI11:614:LVDTPROFILE",2000,566,0,0,"WIRE:LI11:614:LVDTPROFILE")
#! Field("WIRE:LI11:614:LVDTPROFILE.INP",16777215,1,"WIRE:LI11:614:LVDTPROFILE.INP")
#! Field("WIRE:LI11:614:LVDTPROFILE.VAL",16777215,1,"WIRE:LI11:614:LVDTPROFILE.VAL")
#! Record("WIRE:LI11:614:SUBLPROF",2560,698,0,0,"WIRE:LI11:614:SUBLPROF")
#! Field("WIRE:LI11:614:SUBLPROF.INP",16777215,0,"WIRE:LI11:614:SUBLPROF.INP")
#! Link("WIRE:LI11:614:SUBLPROF.INP","WIRE:LI11:614:PLVDTPROFILE.VAL")
#! Record("WIRE:LI11:614:SUBMPROF",1700,1078,0,0,"WIRE:LI11:614:SUBMPROF")
#! Field("WIRE:LI11:614:SUBMPROF.INP",16777215,0,"WIRE:LI11:614:SUBMPROF.INP")
#! Link("WIRE:LI11:614:SUBMPROF.INP","WIRE:LI11:614:PMOTPROFILE.VAL")
#! Record("WIRE:LI11:614:PMOTPROFILE",1380,998,0,0,"WIRE:LI11:614:PMOTPROFILE")
#! Field("WIRE:LI11:614:PMOTPROFILE.FLNK",16777215,1,"WIRE:LI11:614:PMOTPROFILE.FLNK")
#! Link("WIRE:LI11:614:PMOTPROFILE.FLNK","WIRE:LI11:614:SUBMPROF")
#! Field("WIRE:LI11:614:PMOTPROFILE.VAL",16777215,1,"WIRE:LI11:614:PMOTPROFILE.VAL")
#! Field("WIRE:LI11:614:PMOTPROFILE.INP",16777215,0,"WIRE:LI11:614:PMOTPROFILE.INP")
#! Link("WIRE:LI11:614:PMOTPROFILE.INP","WIRE:LI11:614:MOTPROFILE.VAL")
#! Record("WIRE:LI11:614:PLVDTPROFILE",2280,578,0,0,"WIRE:LI11:614:PLVDTPROFILE")
#! Field("WIRE:LI11:614:PLVDTPROFILE.INP",16777215,0,"WIRE:LI11:614:PLVDTPROFILE.INP")
#! Link("WIRE:LI11:614:PLVDTPROFILE.INP","WIRE:LI11:614:LVDTPROFILE.VAL")
#! Field("WIRE:LI11:614:PLVDTPROFILE.FLNK",16777215,1,"WIRE:LI11:614:PLVDTPROFILE.FLNK")
#! Link("WIRE:LI11:614:PLVDTPROFILE.FLNK","WIRE:LI11:614:SUBLPROF")
#! Field("WIRE:LI11:614:PLVDTPROFILE.VAL",16777215,1,"WIRE:LI11:614:PLVDTPROFILE.VAL")
#! Record("WIRE:LI11:614:MOTRVALREST",500,914,0,0,"WIRE:LI11:614:MOTRVALREST")
#! Field("WIRE:LI11:614:MOTRVALREST.INP",16777215,0,"WIRE:LI11:614:MOTRVALREST.INP")
#! Link("WIRE:LI11:614:MOTRVALREST.INP","WIRE:LI11:614:MOTR.VAL")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../../dbd/MotionControl.dbd")
#! DBDEND


# motor channel Hy8601-01/1
record(motor, "WIRE:LI11:744:MOTR") {
  field(DESC, "WS11744 Wire Scanner Motion")
  field(SCAN, "Passive")
  field(DIR, "Neg")
  field(DTYP, "asynMotor")
  field(VELO, "850")
  field(VBAS, "250")
  field(VMAX, "850")
  field(ACCL, "0.1")
  field(OUT, "@asyn( Hy8601-01, 1)")
  field(MRES, "0.2")
  field(SREV, "400")
  field(PREC, "0")
  field(EGU, "microns")
  field(DHLM, "28104")
  field(HOPR, "28104")
  field(DLLM, "-36500")
  field(LOPR, "-36500")
  field(DLY, "0")
  field(TWV, "1000")
  field(SET, "1")
  field(RDBD, "2")
  field(FOFF, "Frozen")
  field(FLNK, "WIRE:LI11:744:MOTRVALREST")
  field(PINI, "YES")
  field(PRIO, "HIGH")
  field(BDST, "0")
  field(BVEL, "250")
  field(BACC, "0.5")
  field(RDBL, "WIRE:LI11:744:LVPOS")
  info(autosaveFields, "DESC DIR VELO VBAS VMAX ACCL SREV PREC EGU DLY TWV RDBD BDST BVEL BACC RDBL RRES RTRY URIP HIHI LOLO HIGH LOW HHSV LLSV HSV LSV")
}

# Position of motor on WIRE:LI11:744
# updated regularly, when a specific event arrives
# from the event timing system, indicating that
# beam has arrived.  This is unused for collimators
# or other simple motion devices; it is important
# for wire scanners and other beam-synchronous
# devices.
# WARNING: The EVNT field is changed when calibrations
# are performed.  If problems are suspected with this,
# check the save and restore code in the sequencer,
# under calibrate.st, in the READY_TO_PROFILE state.
record(ai, "WIRE:LI11:744:POSN") {
  field(DESC, "WS11744 Current Position")
  field(DTYP, "asynInt32")
  field(EGU, "microns")
  field(INP, "@asyn(Hy8601-01 1)MOTOR_POSITION")
  field(SCAN, "Event")
  field(PRIO, "HIGH")
  field(EVNT, "201")
  field(LINR, "SLOPE")
  field(ROFF, "0")
  field(EOFF, "0")
  field(ESLO, "0.2")
  field(FLNK, "WIRE:LI11:744:EFPOSN")
  field(PREC, "0")
  field(TSE, "-1")
}

#
# This record contains a simple value that changes per
# beam pulse; when WIRE:LI11:744 (WS11744)
# is scanning, it will have a non-zero value, and when
# moving to a start position or positioning to confirm
# an LVDT value, it will be zero.
#
record(ao, "WIRE:LI11:744:MASK") {
  field(DESC, "WS11744 Scan Mask")
  field(OMSL, "supervisory")
  field(SCAN, "Event")
  field(PRIO, "HIGH")
  field(EVNT, "201")
  field(DRVH, "4000000000")
  field(DRVL, "-4000000000")
  field(FLNK, "WIRE:LI11:744:EFMASK")
  field(TSE, "-1")
}

#
# This record takes the calibration offset from
# WIRE:LI11:744 (WS11744) and pushes
# it to the EOFF field in the POSN record, above.
# It is triggered by the state machine after a
# calibration is complete, or when the IOC starts.
#
record(ao, "WIRE:LI11:744:NEWOFFS") {
  field(DESC, "New WS11744 Cal")
  field(EGU, "microns")
  field(OMSL, "closed_loop")
  field(OIF, "Full")
  field(DOL, "WIRE:LI11:744:MOTR.OFF PP")
  field(DRVH, "4000000000")
  field(DRVL, "-4000000000")
  field(SCAN, "Passive")
  field(OUT, "WIRE:LI11:744:POSN.EOFF")
}

record(ao, "WIRE:LI11:744:MOTRVAL") {
  field(DESC, "WS11744 Value Proxy")
  field(EGU, "microns")
  field(OMSL, "supervisory")
  field(DRVH, "28104")
  field(DRVL, "-36500")
  field(SCAN, "Passive")
  field(OUT, "WIRE:LI11:744:MOTR.VAL")
  field(FLNK, "WIRE:LI11:744:MOTR")
}

record(ao, "WIRE:LI11:744:MOTRHI") {
  field(DESC, "Move WS11744 High")
  field(EGU, "microns")
  field(OMSL, "closed_loop")
  field(OIF, "Full")
  field(DOL, "WIRE:LI11:744:MOTR.HLM")
  field(DRVH, "4000000000")
  field(DRVL, "-4000000000")
  field(SCAN, "Passive")
  field(OUT, "WIRE:LI11:744:MOTR.VAL")
  field(FLNK, "WIRE:LI11:744:MOTR")
}

record(ao, "WIRE:LI11:744:MOTRLO") {
  field(DESC, "Move WS11744 Low")
  field(EGU, "microns")
  field(OMSL, "closed_loop")
  field(OIF, "Full")
  field(DOL, "WIRE:LI11:744:MOTR.LLM")
  field(DRVH, "4000000000")
  field(DRVL, "-4000000000")
  field(SCAN, "Passive")
  field(OUT, "WIRE:LI11:744:MOTR.VAL")
  field(FLNK, "WIRE:LI11:744:MOTR")
}

record(ao, "WIRE:LI11:744:RETRACT") {
  field(DESC, "WS11744 Retract")
  field(EGU, "microns")
  field(OMSL, "closed_loop")
  field(DOL, "WIRE:LI11:744:RETRACT_POSN")
  field(DRVH, "28104")
  field(DRVL, "-36500")
  field(SCAN, "Passive")
  field(OUT, "WIRE:LI11:744:MOTR.VAL")
  field(FLNK, "WIRE:LI11:744:MOTR")
}

record(ai, "WIRE:LI11:744:RETRACT_POSN") {
  field(DESC, "WS11744 Retract Position")
  field(VAL, "-36500")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

record(mbbo, "WIRE:LI11:744:MOTRVELCHOICE") {
  field(DESC, "WS11744 Value Proxy")
  field(OMSL, "supervisory")
  field(SCAN, "Passive")
  field(DTYP, "Raw Soft Channel")
  field(NOBT, "32")
  field(OUT, "WIRE:LI11:744:MOTR.VELO")
  field(ZRST, "Normal")
  field(ZRVL, "500")
  field(ONST, "Maximum")
  field(ONVL, "850")
  field(TWST, "Medium")
  field(TWVL, "500")
  field(THST, "Slow")
  field(THVL, "250")
}

record(fanout, "WIRE:LI11:744:SYNCMOTPROFILE") {
  field(DESC, "WS11744 Calib Profile Sync")
  field(SCAN, "Passive")
  field(SELM, "Mask")
  field(SELL, "7")
  field(LNK1, "WIRE:LI11:744:MOTPROFILE")
  field(LNK2, "WIRE:LI11:744:LVDTPROFILE")
  field(LNK3, "WIRE:LI11:744:CALIBSYNC")
}

#
# This record is processed at the end of an acquisition
# sequence.  The calibration state machine waits for it
# to become 0.  Specifically, it awaits processing.
#
record(event, "WIRE:LI11:744:CALIBSYNC") {
  field(DESC, "WS11744 Cal Delay Sync")
  field(VAL, "0")
  field(SCAN, "Passive")
  field(PINI, "YES")
}

record(compress, "WIRE:LI11:744:MOTPROFILE") {
  field(DESC, "WS11744 Motion Profile")
  field(SCAN, "Passive")
  field(ALG, "Circular Buffer")
  field(NSAM, "200")
  field(INP, "WIRE:LI11:744:POSN PP")
}

record(compress, "WIRE:LI11:744:LVDTPROFILE") {
  field(DESC, "WS11744 Measured Profile")
  field(SCAN, "Passive")
  field(ALG, "Circular Buffer")
  field(NSAM, "200")
  field(INP, "WIRE:LI11:744:LVRAW PP")
}

record(subArray, "WIRE:LI11:744:SUBLPROF") {
  field(DESC, "WS11744 Distance Region")
  field(SCAN, "Passive")
  field(MALM, "200")
  field(NELM, "200")
  field(INDX, "0")
  field(FTVL, "DOUBLE")
  field(INP, "WIRE:LI11:744:PLVDTPROFILE.VAL")
}

record(subArray, "WIRE:LI11:744:SUBMPROF") {
  field(DESC, "WS11744 Motion Region")
  field(SCAN, "Passive")
  field(MALM, "200")
  field(NELM, "200")
  field(INDX, "0")
  field(FTVL, "DOUBLE")
  field(INP, "WIRE:LI11:744:PMOTPROFILE.VAL")
}

record(waveform, "WIRE:LI11:744:PMOTPROFILE") {
  field(DESC, "WS11744 Prev Motion Profile")
  field(SCAN, "Passive")
  field(FTVL, "DOUBLE")
  field(EGU, "microns")
  field(NELM, "200")
  field(INP, "WIRE:LI11:744:MOTPROFILE")
  field(FLNK, "WIRE:LI11:744:SUBMPROF")
}

record(waveform, "WIRE:LI11:744:PLVDTPROFILE") {
  field(DESC, "WS11744 Prev Measured Profl")
  field(SCAN, "Passive")
  field(FTVL, "DOUBLE")
  field(EGU, "microns")
  field(NELM, "200")
  field(INP, "WIRE:LI11:744:LVDTPROFILE")
  field(FLNK, "WIRE:LI11:744:SUBLPROF")
}

record(ai, "WIRE:LI11:744:MOTRVALREST") {
  field(INP, "WIRE:LI11:744:MOTR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,0.5)
#! Record("WIRE:LI11:744:MOTR",160,62,0,0,"WIRE:LI11:744:MOTR")
#! Field("WIRE:LI11:744:MOTR.FLNK",16777215,1,"WIRE:LI11:744:MOTR.FLNK")
#! Field("WIRE:LI11:744:MOTR.RDBL",16777215,1,"WIRE:LI11:744:MOTR.RDBL")
#! Field("WIRE:LI11:744:MOTR.OFF",16777215,1,"WIRE:LI11:744:MOTR.OFF")
#! Field("WIRE:LI11:744:MOTR.HLM",16777215,1,"WIRE:LI11:744:MOTR.HLM")
#! Field("WIRE:LI11:744:MOTR.LLM",16777215,1,"WIRE:LI11:744:MOTR.LLM")
#! Field("WIRE:LI11:744:MOTR.VELO",16777215,1,"WIRE:LI11:744:MOTR.VELO")
#! Field("WIRE:LI11:744:MOTR.VAL",16777215,1,"WIRE:LI11:744:MOTR.VAL")
#! Record("WIRE:LI11:744:POSN",1000,544,0,0,"WIRE:LI11:744:POSN")
#! Field("WIRE:LI11:744:POSN.FLNK",16777215,1,"WIRE:LI11:744:POSN.FLNK")
#! Field("WIRE:LI11:744:POSN.EOFF",16777215,0,"WIRE:LI11:744:POSN.EOFF")
#! Field("WIRE:LI11:744:POSN.VAL",16777215,1,"WIRE:LI11:744:POSN.VAL")
#! Record("WIRE:LI11:744:MASK",1340,1352,0,0,"WIRE:LI11:744:MASK")
#! Field("WIRE:LI11:744:MASK.FLNK",16777215,1,"WIRE:LI11:744:MASK.FLNK")
#! Record("WIRE:LI11:744:NEWOFFS",720,612,0,0,"WIRE:LI11:744:NEWOFFS")
#! Field("WIRE:LI11:744:NEWOFFS.DOL",16777215,0,"WIRE:LI11:744:NEWOFFS.DOL")
#! Link("WIRE:LI11:744:NEWOFFS.DOL","WIRE:LI11:744:MOTR.OFF")
#! Field("WIRE:LI11:744:NEWOFFS.OUT",16777215,1,"WIRE:LI11:744:NEWOFFS.OUT")
#! Link("WIRE:LI11:744:NEWOFFS.OUT","WIRE:LI11:744:POSN.EOFF")
#! Record("WIRE:LI11:744:MOTRVAL",860,986,0,0,"WIRE:LI11:744:MOTRVAL")
#! Field("WIRE:LI11:744:MOTRVAL.OUT",16777215,0,"WIRE:LI11:744:MOTRVAL.OUT")
#! Link("WIRE:LI11:744:MOTRVAL.OUT","WIRE:LI11:744:MOTR.VAL")
#! Field("WIRE:LI11:744:MOTRVAL.FLNK",16777215,0,"WIRE:LI11:744:MOTRVAL.FLNK")
#! Link("WIRE:LI11:744:MOTRVAL.FLNK","WIRE:LI11:744:MOTR")
#! Record("WIRE:LI11:744:MOTRHI",860,1238,0,0,"WIRE:LI11:744:MOTRHI")
#! Field("WIRE:LI11:744:MOTRHI.DOL",16777215,0,"WIRE:LI11:744:MOTRHI.DOL")
#! Link("WIRE:LI11:744:MOTRHI.DOL","WIRE:LI11:744:MOTR.HLM")
#! Field("WIRE:LI11:744:MOTRHI.OUT",16777215,0,"WIRE:LI11:744:MOTRHI.OUT")
#! Link("WIRE:LI11:744:MOTRHI.OUT","WIRE:LI11:744:MOTR.VAL")
#! Field("WIRE:LI11:744:MOTRHI.FLNK",16777215,0,"WIRE:LI11:744:MOTRHI.FLNK")
#! Link("WIRE:LI11:744:MOTRHI.FLNK","WIRE:LI11:744:MOTR")
#! Record("WIRE:LI11:744:MOTRLO",860,1558,0,0,"WIRE:LI11:744:MOTRLO")
#! Field("WIRE:LI11:744:MOTRLO.DOL",16777215,0,"WIRE:LI11:744:MOTRLO.DOL")
#! Link("WIRE:LI11:744:MOTRLO.DOL","WIRE:LI11:744:MOTR.LLM")
#! Field("WIRE:LI11:744:MOTRLO.OUT",16777215,0,"WIRE:LI11:744:MOTRLO.OUT")
#! Link("WIRE:LI11:744:MOTRLO.OUT","WIRE:LI11:744:MOTR.VAL")
#! Field("WIRE:LI11:744:MOTRLO.FLNK",16777215,0,"WIRE:LI11:744:MOTRLO.FLNK")
#! Link("WIRE:LI11:744:MOTRLO.FLNK","WIRE:LI11:744:MOTR")
#! Record("WIRE:LI11:744:MOTRVELCHOICE",840,1884,0,0,"WIRE:LI11:744:MOTRVELCHOICE")
#! Field("WIRE:LI11:744:MOTRVELCHOICE.OUT",16777215,0,"WIRE:LI11:744:MOTRVELCHOICE.OUT")
#! Link("WIRE:LI11:744:MOTRVELCHOICE.OUT","WIRE:LI11:744:MOTR.VELO")
#! Record("WIRE:LI11:744:SYNCMOTPROFILE",1700,598,0,0,"WIRE:LI11:744:SYNCMOTPROFILE")
#! Field("WIRE:LI11:744:SYNCMOTPROFILE.LNK1",16777215,0,"WIRE:LI11:744:SYNCMOTPROFILE.LNK1")
#! Link("WIRE:LI11:744:SYNCMOTPROFILE.LNK1","WIRE:LI11:744:MOTPROFILE")
#! Field("WIRE:LI11:744:SYNCMOTPROFILE.LNK2",16777215,1,"WIRE:LI11:744:SYNCMOTPROFILE.LNK2")
#! Link("WIRE:LI11:744:SYNCMOTPROFILE.LNK2","WIRE:LI11:744:LVDTPROFILE")
#! Field("WIRE:LI11:744:SYNCMOTPROFILE.LNK3",16777215,1,"WIRE:LI11:744:SYNCMOTPROFILE.LNK3")
#! Link("WIRE:LI11:744:SYNCMOTPROFILE.LNK3","WIRE:LI11:744:CALIBSYNC")
#! Record("WIRE:LI11:744:CALIBSYNC",1980,860,0,0,"WIRE:LI11:744:CALIBSYNC")
#! Record("WIRE:LI11:744:MOTPROFILE",1380,706,0,1,"WIRE:LI11:744:MOTPROFILE")
#! Field("WIRE:LI11:744:MOTPROFILE.INP",16777215,0,"WIRE:LI11:744:MOTPROFILE.INP")
#! Link("WIRE:LI11:744:MOTPROFILE.INP","WIRE:LI11:744:POSN.VAL")
#! Field("WIRE:LI11:744:MOTPROFILE.VAL",16777215,0,"WIRE:LI11:744:MOTPROFILE.VAL")
#! Record("WIRE:LI11:744:LVDTPROFILE",2000,566,0,0,"WIRE:LI11:744:LVDTPROFILE")
#! Field("WIRE:LI11:744:LVDTPROFILE.INP",16777215,1,"WIRE:LI11:744:LVDTPROFILE.INP")
#! Field("WIRE:LI11:744:LVDTPROFILE.VAL",16777215,1,"WIRE:LI11:744:LVDTPROFILE.VAL")
#! Record("WIRE:LI11:744:SUBLPROF",2560,698,0,0,"WIRE:LI11:744:SUBLPROF")
#! Field("WIRE:LI11:744:SUBLPROF.INP",16777215,0,"WIRE:LI11:744:SUBLPROF.INP")
#! Link("WIRE:LI11:744:SUBLPROF.INP","WIRE:LI11:744:PLVDTPROFILE.VAL")
#! Record("WIRE:LI11:744:SUBMPROF",1700,1078,0,0,"WIRE:LI11:744:SUBMPROF")
#! Field("WIRE:LI11:744:SUBMPROF.INP",16777215,0,"WIRE:LI11:744:SUBMPROF.INP")
#! Link("WIRE:LI11:744:SUBMPROF.INP","WIRE:LI11:744:PMOTPROFILE.VAL")
#! Record("WIRE:LI11:744:PMOTPROFILE",1380,998,0,0,"WIRE:LI11:744:PMOTPROFILE")
#! Field("WIRE:LI11:744:PMOTPROFILE.FLNK",16777215,1,"WIRE:LI11:744:PMOTPROFILE.FLNK")
#! Link("WIRE:LI11:744:PMOTPROFILE.FLNK","WIRE:LI11:744:SUBMPROF")
#! Field("WIRE:LI11:744:PMOTPROFILE.VAL",16777215,1,"WIRE:LI11:744:PMOTPROFILE.VAL")
#! Field("WIRE:LI11:744:PMOTPROFILE.INP",16777215,0,"WIRE:LI11:744:PMOTPROFILE.INP")
#! Link("WIRE:LI11:744:PMOTPROFILE.INP","WIRE:LI11:744:MOTPROFILE.VAL")
#! Record("WIRE:LI11:744:PLVDTPROFILE",2280,578,0,0,"WIRE:LI11:744:PLVDTPROFILE")
#! Field("WIRE:LI11:744:PLVDTPROFILE.INP",16777215,0,"WIRE:LI11:744:PLVDTPROFILE.INP")
#! Link("WIRE:LI11:744:PLVDTPROFILE.INP","WIRE:LI11:744:LVDTPROFILE.VAL")
#! Field("WIRE:LI11:744:PLVDTPROFILE.FLNK",16777215,1,"WIRE:LI11:744:PLVDTPROFILE.FLNK")
#! Link("WIRE:LI11:744:PLVDTPROFILE.FLNK","WIRE:LI11:744:SUBLPROF")
#! Field("WIRE:LI11:744:PLVDTPROFILE.VAL",16777215,1,"WIRE:LI11:744:PLVDTPROFILE.VAL")
#! Record("WIRE:LI11:744:MOTRVALREST",500,914,0,0,"WIRE:LI11:744:MOTRVALREST")
#! Field("WIRE:LI11:744:MOTRVALREST.INP",16777215,0,"WIRE:LI11:744:MOTRVALREST.INP")
#! Link("WIRE:LI11:744:MOTRVALREST.INP","WIRE:LI11:744:MOTR.VAL")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../../dbd/MotionControl.dbd")
#! DBDEND


# motor channel Hy8601-01/2
record(motor, "WIRE:LI12:214:MOTR") {
  field(DESC, "WS12214 Wire Scanner Motion")
  field(SCAN, "Passive")
  field(DIR, "Neg")
  field(DTYP, "asynMotor")
  field(VELO, "850")
  field(VBAS, "250")
  field(VMAX, "850")
  field(ACCL, "0.1")
  field(OUT, "@asyn( Hy8601-01, 2)")
  field(MRES, "0.15625")
  field(SREV, "400")
  field(PREC, "0")
  field(EGU, "microns")
  field(DHLM, "28104")
  field(HOPR, "28104")
  field(DLLM, "-36500")
  field(LOPR, "-36500")
  field(DLY, "0")
  field(TWV, "1000")
  field(SET, "1")
  field(RDBD, "2")
  field(FOFF, "Frozen")
  field(FLNK, "WIRE:LI12:214:MOTRVALREST")
  field(PINI, "YES")
  field(PRIO, "HIGH")
  field(BDST, "0")
  field(BVEL, "250")
  field(BACC, "0.5")
  field(RDBL, "WIRE:LI12:214:LVPOS")
  info(autosaveFields, "DESC DIR VELO VBAS VMAX ACCL SREV PREC EGU DLY TWV RDBD BDST BVEL BACC RDBL RRES RTRY URIP HIHI LOLO HIGH LOW HHSV LLSV HSV LSV")
}

# Position of motor on WIRE:LI12:214
# updated regularly, when a specific event arrives
# from the event timing system, indicating that
# beam has arrived.  This is unused for collimators
# or other simple motion devices; it is important
# for wire scanners and other beam-synchronous
# devices.
# WARNING: The EVNT field is changed when calibrations
# are performed.  If problems are suspected with this,
# check the save and restore code in the sequencer,
# under calibrate.st, in the READY_TO_PROFILE state.
record(ai, "WIRE:LI12:214:POSN") {
  field(DESC, "WS12214 Current Position")
  field(DTYP, "asynInt32")
  field(EGU, "microns")
  field(INP, "@asyn(Hy8601-01 2)MOTOR_POSITION")
  field(SCAN, "Event")
  field(PRIO, "HIGH")
  field(EVNT, "201")
  field(LINR, "SLOPE")
  field(ROFF, "0")
  field(EOFF, "0")
  field(ESLO, "0.15625")
  field(FLNK, "WIRE:LI12:214:EFPOSN")
  field(PREC, "0")
  field(TSE, "-1")
}

#
# This record contains a simple value that changes per
# beam pulse; when WIRE:LI12:214 (WS12214)
# is scanning, it will have a non-zero value, and when
# moving to a start position or positioning to confirm
# an LVDT value, it will be zero.
#
record(ao, "WIRE:LI12:214:MASK") {
  field(DESC, "WS12214 Scan Mask")
  field(OMSL, "supervisory")
  field(SCAN, "Event")
  field(PRIO, "HIGH")
  field(EVNT, "201")
  field(DRVH, "4000000000")
  field(DRVL, "-4000000000")
  field(FLNK, "WIRE:LI12:214:EFMASK")
  field(TSE, "-1")
}

#
# This record takes the calibration offset from
# WIRE:LI12:214 (WS12214) and pushes
# it to the EOFF field in the POSN record, above.
# It is triggered by the state machine after a
# calibration is complete, or when the IOC starts.
#
record(ao, "WIRE:LI12:214:NEWOFFS") {
  field(DESC, "New WS12214 Cal")
  field(EGU, "microns")
  field(OMSL, "closed_loop")
  field(OIF, "Full")
  field(DOL, "WIRE:LI12:214:MOTR.OFF PP")
  field(DRVH, "4000000000")
  field(DRVL, "-4000000000")
  field(SCAN, "Passive")
  field(OUT, "WIRE:LI12:214:POSN.EOFF")
}

record(ao, "WIRE:LI12:214:MOTRVAL") {
  field(DESC, "WS12214 Value Proxy")
  field(EGU, "microns")
  field(OMSL, "supervisory")
  field(DRVH, "28104")
  field(DRVL, "-36500")
  field(SCAN, "Passive")
  field(OUT, "WIRE:LI12:214:MOTR.VAL")
  field(FLNK, "WIRE:LI12:214:MOTR")
}

record(ao, "WIRE:LI12:214:MOTRHI") {
  field(DESC, "Move WS12214 High")
  field(EGU, "microns")
  field(OMSL, "closed_loop")
  field(OIF, "Full")
  field(DOL, "WIRE:LI12:214:MOTR.HLM")
  field(DRVH, "4000000000")
  field(DRVL, "-4000000000")
  field(SCAN, "Passive")
  field(OUT, "WIRE:LI12:214:MOTR.VAL")
  field(FLNK, "WIRE:LI12:214:MOTR")
}

record(ao, "WIRE:LI12:214:MOTRLO") {
  field(DESC, "Move WS12214 Low")
  field(EGU, "microns")
  field(OMSL, "closed_loop")
  field(OIF, "Full")
  field(DOL, "WIRE:LI12:214:MOTR.LLM")
  field(DRVH, "4000000000")
  field(DRVL, "-4000000000")
  field(SCAN, "Passive")
  field(OUT, "WIRE:LI12:214:MOTR.VAL")
  field(FLNK, "WIRE:LI12:214:MOTR")
}

record(ao, "WIRE:LI12:214:RETRACT") {
  field(DESC, "WS12214 Retract")
  field(EGU, "microns")
  field(OMSL, "closed_loop")
  field(DOL, "WIRE:LI12:214:RETRACT_POSN")
  field(DRVH, "28104")
  field(DRVL, "-36500")
  field(SCAN, "Passive")
  field(OUT, "WIRE:LI12:214:MOTR.VAL")
  field(FLNK, "WIRE:LI12:214:MOTR")
}

record(ai, "WIRE:LI12:214:RETRACT_POSN") {
  field(DESC, "WS12214 Retract Position")
  field(VAL, "-36500")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

record(mbbo, "WIRE:LI12:214:MOTRVELCHOICE") {
  field(DESC, "WS12214 Value Proxy")
  field(OMSL, "supervisory")
  field(SCAN, "Passive")
  field(DTYP, "Raw Soft Channel")
  field(NOBT, "32")
  field(OUT, "WIRE:LI12:214:MOTR.VELO")
  field(ZRST, "Normal")
  field(ZRVL, "500")
  field(ONST, "Maximum")
  field(ONVL, "850")
  field(TWST, "Medium")
  field(TWVL, "500")
  field(THST, "Slow")
  field(THVL, "250")
}

record(fanout, "WIRE:LI12:214:SYNCMOTPROFILE") {
  field(DESC, "WS12214 Calib Profile Sync")
  field(SCAN, "Passive")
  field(SELM, "Mask")
  field(SELL, "7")
  field(LNK1, "WIRE:LI12:214:MOTPROFILE")
  field(LNK2, "WIRE:LI12:214:LVDTPROFILE")
  field(LNK3, "WIRE:LI12:214:CALIBSYNC")
}

#
# This record is processed at the end of an acquisition
# sequence.  The calibration state machine waits for it
# to become 0.  Specifically, it awaits processing.
#
record(event, "WIRE:LI12:214:CALIBSYNC") {
  field(DESC, "WS12214 Cal Delay Sync")
  field(VAL, "0")
  field(SCAN, "Passive")
  field(PINI, "YES")
}

record(compress, "WIRE:LI12:214:MOTPROFILE") {
  field(DESC, "WS12214 Motion Profile")
  field(SCAN, "Passive")
  field(ALG, "Circular Buffer")
  field(NSAM, "200")
  field(INP, "WIRE:LI12:214:POSN PP")
}

record(compress, "WIRE:LI12:214:LVDTPROFILE") {
  field(DESC, "WS12214 Measured Profile")
  field(SCAN, "Passive")
  field(ALG, "Circular Buffer")
  field(NSAM, "200")
  field(INP, "WIRE:LI12:214:LVRAW PP")
}

record(subArray, "WIRE:LI12:214:SUBLPROF") {
  field(DESC, "WS12214 Distance Region")
  field(SCAN, "Passive")
  field(MALM, "200")
  field(NELM, "200")
  field(INDX, "0")
  field(FTVL, "DOUBLE")
  field(INP, "WIRE:LI12:214:PLVDTPROFILE.VAL")
}

record(subArray, "WIRE:LI12:214:SUBMPROF") {
  field(DESC, "WS12214 Motion Region")
  field(SCAN, "Passive")
  field(MALM, "200")
  field(NELM, "200")
  field(INDX, "0")
  field(FTVL, "DOUBLE")
  field(INP, "WIRE:LI12:214:PMOTPROFILE.VAL")
}

record(waveform, "WIRE:LI12:214:PMOTPROFILE") {
  field(DESC, "WS12214 Prev Motion Profile")
  field(SCAN, "Passive")
  field(FTVL, "DOUBLE")
  field(EGU, "microns")
  field(NELM, "200")
  field(INP, "WIRE:LI12:214:MOTPROFILE")
  field(FLNK, "WIRE:LI12:214:SUBMPROF")
}

record(waveform, "WIRE:LI12:214:PLVDTPROFILE") {
  field(DESC, "WS12214 Prev Measured Profl")
  field(SCAN, "Passive")
  field(FTVL, "DOUBLE")
  field(EGU, "microns")
  field(NELM, "200")
  field(INP, "WIRE:LI12:214:LVDTPROFILE")
  field(FLNK, "WIRE:LI12:214:SUBLPROF")
}

record(ai, "WIRE:LI12:214:MOTRVALREST") {
  field(INP, "WIRE:LI12:214:MOTR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,0.5)
#! Record("WIRE:LI12:214:MOTR",160,62,0,0,"WIRE:LI12:214:MOTR")
#! Field("WIRE:LI12:214:MOTR.FLNK",16777215,1,"WIRE:LI12:214:MOTR.FLNK")
#! Field("WIRE:LI12:214:MOTR.RDBL",16777215,1,"WIRE:LI12:214:MOTR.RDBL")
#! Field("WIRE:LI12:214:MOTR.OFF",16777215,1,"WIRE:LI12:214:MOTR.OFF")
#! Field("WIRE:LI12:214:MOTR.HLM",16777215,1,"WIRE:LI12:214:MOTR.HLM")
#! Field("WIRE:LI12:214:MOTR.LLM",16777215,1,"WIRE:LI12:214:MOTR.LLM")
#! Field("WIRE:LI12:214:MOTR.VELO",16777215,1,"WIRE:LI12:214:MOTR.VELO")
#! Field("WIRE:LI12:214:MOTR.VAL",16777215,1,"WIRE:LI12:214:MOTR.VAL")
#! Record("WIRE:LI12:214:POSN",1000,544,0,0,"WIRE:LI12:214:POSN")
#! Field("WIRE:LI12:214:POSN.FLNK",16777215,1,"WIRE:LI12:214:POSN.FLNK")
#! Field("WIRE:LI12:214:POSN.EOFF",16777215,0,"WIRE:LI12:214:POSN.EOFF")
#! Field("WIRE:LI12:214:POSN.VAL",16777215,1,"WIRE:LI12:214:POSN.VAL")
#! Record("WIRE:LI12:214:MASK",1340,1352,0,0,"WIRE:LI12:214:MASK")
#! Field("WIRE:LI12:214:MASK.FLNK",16777215,1,"WIRE:LI12:214:MASK.FLNK")
#! Record("WIRE:LI12:214:NEWOFFS",720,612,0,0,"WIRE:LI12:214:NEWOFFS")
#! Field("WIRE:LI12:214:NEWOFFS.DOL",16777215,0,"WIRE:LI12:214:NEWOFFS.DOL")
#! Link("WIRE:LI12:214:NEWOFFS.DOL","WIRE:LI12:214:MOTR.OFF")
#! Field("WIRE:LI12:214:NEWOFFS.OUT",16777215,1,"WIRE:LI12:214:NEWOFFS.OUT")
#! Link("WIRE:LI12:214:NEWOFFS.OUT","WIRE:LI12:214:POSN.EOFF")
#! Record("WIRE:LI12:214:MOTRVAL",860,986,0,0,"WIRE:LI12:214:MOTRVAL")
#! Field("WIRE:LI12:214:MOTRVAL.OUT",16777215,0,"WIRE:LI12:214:MOTRVAL.OUT")
#! Link("WIRE:LI12:214:MOTRVAL.OUT","WIRE:LI12:214:MOTR.VAL")
#! Field("WIRE:LI12:214:MOTRVAL.FLNK",16777215,0,"WIRE:LI12:214:MOTRVAL.FLNK")
#! Link("WIRE:LI12:214:MOTRVAL.FLNK","WIRE:LI12:214:MOTR")
#! Record("WIRE:LI12:214:MOTRHI",860,1238,0,0,"WIRE:LI12:214:MOTRHI")
#! Field("WIRE:LI12:214:MOTRHI.DOL",16777215,0,"WIRE:LI12:214:MOTRHI.DOL")
#! Link("WIRE:LI12:214:MOTRHI.DOL","WIRE:LI12:214:MOTR.HLM")
#! Field("WIRE:LI12:214:MOTRHI.OUT",16777215,0,"WIRE:LI12:214:MOTRHI.OUT")
#! Link("WIRE:LI12:214:MOTRHI.OUT","WIRE:LI12:214:MOTR.VAL")
#! Field("WIRE:LI12:214:MOTRHI.FLNK",16777215,0,"WIRE:LI12:214:MOTRHI.FLNK")
#! Link("WIRE:LI12:214:MOTRHI.FLNK","WIRE:LI12:214:MOTR")
#! Record("WIRE:LI12:214:MOTRLO",860,1558,0,0,"WIRE:LI12:214:MOTRLO")
#! Field("WIRE:LI12:214:MOTRLO.DOL",16777215,0,"WIRE:LI12:214:MOTRLO.DOL")
#! Link("WIRE:LI12:214:MOTRLO.DOL","WIRE:LI12:214:MOTR.LLM")
#! Field("WIRE:LI12:214:MOTRLO.OUT",16777215,0,"WIRE:LI12:214:MOTRLO.OUT")
#! Link("WIRE:LI12:214:MOTRLO.OUT","WIRE:LI12:214:MOTR.VAL")
#! Field("WIRE:LI12:214:MOTRLO.FLNK",16777215,0,"WIRE:LI12:214:MOTRLO.FLNK")
#! Link("WIRE:LI12:214:MOTRLO.FLNK","WIRE:LI12:214:MOTR")
#! Record("WIRE:LI12:214:MOTRVELCHOICE",840,1884,0,0,"WIRE:LI12:214:MOTRVELCHOICE")
#! Field("WIRE:LI12:214:MOTRVELCHOICE.OUT",16777215,0,"WIRE:LI12:214:MOTRVELCHOICE.OUT")
#! Link("WIRE:LI12:214:MOTRVELCHOICE.OUT","WIRE:LI12:214:MOTR.VELO")
#! Record("WIRE:LI12:214:SYNCMOTPROFILE",1700,598,0,0,"WIRE:LI12:214:SYNCMOTPROFILE")
#! Field("WIRE:LI12:214:SYNCMOTPROFILE.LNK1",16777215,0,"WIRE:LI12:214:SYNCMOTPROFILE.LNK1")
#! Link("WIRE:LI12:214:SYNCMOTPROFILE.LNK1","WIRE:LI12:214:MOTPROFILE")
#! Field("WIRE:LI12:214:SYNCMOTPROFILE.LNK2",16777215,1,"WIRE:LI12:214:SYNCMOTPROFILE.LNK2")
#! Link("WIRE:LI12:214:SYNCMOTPROFILE.LNK2","WIRE:LI12:214:LVDTPROFILE")
#! Field("WIRE:LI12:214:SYNCMOTPROFILE.LNK3",16777215,1,"WIRE:LI12:214:SYNCMOTPROFILE.LNK3")
#! Link("WIRE:LI12:214:SYNCMOTPROFILE.LNK3","WIRE:LI12:214:CALIBSYNC")
#! Record("WIRE:LI12:214:CALIBSYNC",1980,860,0,0,"WIRE:LI12:214:CALIBSYNC")
#! Record("WIRE:LI12:214:MOTPROFILE",1380,706,0,1,"WIRE:LI12:214:MOTPROFILE")
#! Field("WIRE:LI12:214:MOTPROFILE.INP",16777215,0,"WIRE:LI12:214:MOTPROFILE.INP")
#! Link("WIRE:LI12:214:MOTPROFILE.INP","WIRE:LI12:214:POSN.VAL")
#! Field("WIRE:LI12:214:MOTPROFILE.VAL",16777215,0,"WIRE:LI12:214:MOTPROFILE.VAL")
#! Record("WIRE:LI12:214:LVDTPROFILE",2000,566,0,0,"WIRE:LI12:214:LVDTPROFILE")
#! Field("WIRE:LI12:214:LVDTPROFILE.INP",16777215,1,"WIRE:LI12:214:LVDTPROFILE.INP")
#! Field("WIRE:LI12:214:LVDTPROFILE.VAL",16777215,1,"WIRE:LI12:214:LVDTPROFILE.VAL")
#! Record("WIRE:LI12:214:SUBLPROF",2560,698,0,0,"WIRE:LI12:214:SUBLPROF")
#! Field("WIRE:LI12:214:SUBLPROF.INP",16777215,0,"WIRE:LI12:214:SUBLPROF.INP")
#! Link("WIRE:LI12:214:SUBLPROF.INP","WIRE:LI12:214:PLVDTPROFILE.VAL")
#! Record("WIRE:LI12:214:SUBMPROF",1700,1078,0,0,"WIRE:LI12:214:SUBMPROF")
#! Field("WIRE:LI12:214:SUBMPROF.INP",16777215,0,"WIRE:LI12:214:SUBMPROF.INP")
#! Link("WIRE:LI12:214:SUBMPROF.INP","WIRE:LI12:214:PMOTPROFILE.VAL")
#! Record("WIRE:LI12:214:PMOTPROFILE",1380,998,0,0,"WIRE:LI12:214:PMOTPROFILE")
#! Field("WIRE:LI12:214:PMOTPROFILE.FLNK",16777215,1,"WIRE:LI12:214:PMOTPROFILE.FLNK")
#! Link("WIRE:LI12:214:PMOTPROFILE.FLNK","WIRE:LI12:214:SUBMPROF")
#! Field("WIRE:LI12:214:PMOTPROFILE.VAL",16777215,1,"WIRE:LI12:214:PMOTPROFILE.VAL")
#! Field("WIRE:LI12:214:PMOTPROFILE.INP",16777215,0,"WIRE:LI12:214:PMOTPROFILE.INP")
#! Link("WIRE:LI12:214:PMOTPROFILE.INP","WIRE:LI12:214:MOTPROFILE.VAL")
#! Record("WIRE:LI12:214:PLVDTPROFILE",2280,578,0,0,"WIRE:LI12:214:PLVDTPROFILE")
#! Field("WIRE:LI12:214:PLVDTPROFILE.INP",16777215,0,"WIRE:LI12:214:PLVDTPROFILE.INP")
#! Link("WIRE:LI12:214:PLVDTPROFILE.INP","WIRE:LI12:214:LVDTPROFILE.VAL")
#! Field("WIRE:LI12:214:PLVDTPROFILE.FLNK",16777215,1,"WIRE:LI12:214:PLVDTPROFILE.FLNK")
#! Link("WIRE:LI12:214:PLVDTPROFILE.FLNK","WIRE:LI12:214:SUBLPROF")
#! Field("WIRE:LI12:214:PLVDTPROFILE.VAL",16777215,1,"WIRE:LI12:214:PLVDTPROFILE.VAL")
#! Record("WIRE:LI12:214:MOTRVALREST",500,914,0,0,"WIRE:LI12:214:MOTRVALREST")
#! Field("WIRE:LI12:214:MOTRVALREST.INP",16777215,0,"WIRE:LI12:214:MOTRVALREST.INP")
#! Link("WIRE:LI12:214:MOTRVALREST.INP","WIRE:LI12:214:MOTR.VAL")
record(bi,"WIRE:LI11:614:CORRECT")
{
  field(DESC, "CORRECT Button")
  field(DTYP, "Soft Channel")
  field(OSV, "MINOR")
  field(ZSV, "NO_ALARM")
  field(PINI, "YES")
  field(INP, "0")
  field(ZNAM, "OFF")
  field(ONAM, "On")
}
record(bi,"WIRE:LI11:614:VERIFY")
{
  field(DESC, "VERIFY Button")
  field(DTYP, "Soft Channel")
  field(OSV, "MINOR")
  field(ZSV, "NO_ALARM")
  field(PINI, "YES")
  field(INP, "0")
  field(ZNAM, "OFF")
  field(ONAM, "On")
}

record(bi,"WIRE:LI11:614:SETMODEALARM")
{
  field(DESC, "Set Button Alarm")
  field(DTYP, "Soft Channel")
  field(OSV, "MAJOR")
  field(ZSV, "NO_ALARM")
  field(PINI, "YES")
  field(INP, "0")
  field(ZNAM, "OFF")
  field(ONAM, "On")
}
record(bi,"WIRE:LI11:744:CORRECT")
{
  field(DESC, "CORRECT Button")
  field(DTYP, "Soft Channel")
  field(OSV, "MINOR")
  field(ZSV, "NO_ALARM")
  field(PINI, "YES")
  field(INP, "0")
  field(ZNAM, "OFF")
  field(ONAM, "On")
}
record(bi,"WIRE:LI11:744:VERIFY")
{
  field(DESC, "VERIFY Button")
  field(DTYP, "Soft Channel")
  field(OSV, "MINOR")
  field(ZSV, "NO_ALARM")
  field(PINI, "YES")
  field(INP, "0")
  field(ZNAM, "OFF")
  field(ONAM, "On")
}

record(bi,"WIRE:LI11:744:SETMODEALARM")
{
  field(DESC, "Set Button Alarm")
  field(DTYP, "Soft Channel")
  field(OSV, "MAJOR")
  field(ZSV, "NO_ALARM")
  field(PINI, "YES")
  field(INP, "0")
  field(ZNAM, "OFF")
  field(ONAM, "On")
}
record(bi,"WIRE:LI12:214:CORRECT")
{
  field(DESC, "CORRECT Button")
  field(DTYP, "Soft Channel")
  field(OSV, "MINOR")
  field(ZSV, "NO_ALARM")
  field(PINI, "YES")
  field(INP, "0")
  field(ZNAM, "OFF")
  field(ONAM, "On")
}
record(bi,"WIRE:LI12:214:VERIFY")
{
  field(DESC, "VERIFY Button")
  field(DTYP, "Soft Channel")
  field(OSV, "MINOR")
  field(ZSV, "NO_ALARM")
  field(PINI, "YES")
  field(INP, "0")
  field(ZNAM, "OFF")
  field(ONAM, "On")
}

record(bi,"WIRE:LI12:214:SETMODEALARM")
{
  field(DESC, "Set Button Alarm")
  field(DTYP, "Soft Channel")
  field(OSV, "MAJOR")
  field(ZSV, "NO_ALARM")
  field(PINI, "YES")
  field(INP, "0")
  field(ZNAM, "OFF")
  field(ONAM, "On")
}
record(calcout, "WIRE:LI11:614:MOTRERROR") {
  field(DESC, "LVDT-MOTOR error calc")
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(CALC, "A-B")
  field(INPA, "WIRE:LI11:614:MOTR.RBV")
  field(INPB, "WIRE:LI11:614:LVPOS")
  field(HIGH, "200.0")
  field(LOW, "-200.0")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(PINI, "YES")
  info(autosaveFields, "LOW LOLO HIGH HIHI")
}

record(calcout, "WIRE:LI11:614:MOTRACTIVE") {
  field(DESC, "Motor In Use")
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(CALC, "A")
  field(INPA, "WIRE:LI11:614:MOTR.DMOV")
  field(HIGH, "200.0")
  field(LOW, "-200.0")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(PINI, "YES")
  info(autosaveFields, "LOW LOLO HIGH HIHI")
}

record(calcout, "WIRE:LI11:744:MOTRERROR") {
  field(DESC, "LVDT-MOTOR error calc")
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(CALC, "A-B")
  field(INPA, "WIRE:LI11:744:MOTR.RBV")
  field(INPB, "WIRE:LI11:744:LVPOS")
  field(HIGH, "200.0")
  field(LOW, "-200.0")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(PINI, "YES")
  info(autosaveFields, "LOW LOLO HIGH HIHI")
}

record(calcout, "WIRE:LI11:744:MOTRACTIVE") {
  field(DESC, "Motor In Use")
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(CALC, "A")
  field(INPA, "WIRE:LI11:744:MOTR.DMOV")
  field(HIGH, "200.0")
  field(LOW, "-200.0")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(PINI, "YES")
  info(autosaveFields, "LOW LOLO HIGH HIHI")
}

record(calcout, "WIRE:LI12:214:MOTRERROR") {
  field(DESC, "LVDT-MOTOR error calc")
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(CALC, "A-B")
  field(INPA, "WIRE:LI12:214:MOTR.RBV")
  field(INPB, "WIRE:LI12:214:LVPOS")
  field(HIGH, "200.0")
  field(LOW, "-200.0")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(PINI, "YES")
  info(autosaveFields, "LOW LOLO HIGH HIHI")
}

record(calcout, "WIRE:LI12:214:MOTRACTIVE") {
  field(DESC, "Motor In Use")
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(CALC, "A")
  field(INPA, "WIRE:LI12:214:MOTR.DMOV")
  field(HIGH, "200.0")
  field(LOW, "-200.0")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(PINI, "YES")
  info(autosaveFields, "LOW LOLO HIGH HIHI")
}

#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBDEND


record(bo, "WIRE:LI11:614:POWER") {
  field(DTYP, "asynInt32")
  field(OUT, "@asyn(Hy8601-01 0)HYTEC_POWER")
  field(VAL, "1")
  field(ZNAM, "On")
  field(ONAM, "Off")
}

record(bo, "WIRE:LI11:614:BRAKE") {
  field(DTYP, "asynInt32")
  field(OUT, "@asyn(Hy8601-01 0)HYTEC_BRAKE")
  field(VAL, "1")
  field(ZNAM, "Set")
  field(ONAM, "Rls")
}

record(ai, "WIRE:LI11:614:FIRMWARE_VERSION") {
  field(PINI, "YES")
  field(DTYP, "asynInt32")
  field(INP, "@asyn(Hy8601-01 0)HYTEC_FWVERSION")
  field(SCAN, "1 second")
}

record(ai, "WIRE:LI11:614:EN_POSN") {
  field(PINI, "YES")
  field(DTYP, "asynInt32")
  field(INP, "@asyn(Hy8601-01 0)MOTOR_ENCODER_POSITION")
  field(SCAN, "1 second")
}

record(ai, "WIRE:LI11:614:LOWLMT") {
  field(SCAN, "I/O Intr")
  field(DTYP, "asynInt32")
  field(INP, "@asyn(Hy8601-01 0) MOTOR_STATUS_LOW_LIMIT")
}

record(ai, "WIRE:LI11:614:HIGHLMT") {
  field(SCAN, "I/O Intr")
  field(DTYP, "asynInt32")
  field(INP, "@asyn(Hy8601-01 0) MOTOR_STATUS_HIGH_LIMIT")
}

record(ai, "WIRE:LI11:614:DONE") {
  field(SCAN, "I/O Intr")
  field(DTYP, "asynInt32")
  field(INP, "@asyn(Hy8601-01 0) MOTOR_STATUS_DONE")
}

record(ai, "WIRE:LI11:614:HOMELMT") {
  field(SCAN, "I/O Intr")
  field(DTYP, "asynInt32")
  field(INP, "@asyn(Hy8601-01 0) MOTOR_STATUS_AT_HOME")
}

record(ai, "WIRE:LI11:614:FAULT") {
  field(SCAN, "I/O Intr")
  field(DTYP, "asynInt32")
  field(INP, "@asyn(Hy8601-01 0) MOTOR_STATUS_PROBLEM")
}

record(ai, "WIRE:LI11:614:HASENCODER") {
  field(SCAN, "I/O Intr")
  field(DTYP, "asynInt32")
  field(INP, "@asyn(Hy8601-01 0) MOTOR_STATUS_HAS_ENCODER")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("WIRE:LI11:614:POWER",20,14,0,0,"WIRE:LI11:614:POWER")
#! Record("WIRE:LI11:614:BRAKE",260,14,0,0,"WIRE:LI11:614:BRAKE")
#! Record("WIRE:LI11:614:POSN",500,5,0,0,"WIRE:LI11:614:POSN")
#! Field("WIRE:LI11:614:POSN.FLNK",16777215,1,"WIRE:LI11:614:POSN.FLNK")
#! Record("WIRE:LI11:614:FIRMWARE_VERSION",740,28,0,0,"WIRE:LI11:614:FIRMWARE_VERSION")
#! Record("WIRE:LI11:614:EN_POSN",980,28,0,0,"WIRE:LI11:614:EN_POSN")
#! Record("WIRE:LI11:614:LOWLMT",1220,22,0,0,"WIRE:LI11:614:LOWLMT")
#! Record("WIRE:LI11:614:HIGHLMT",1460,22,0,0,"WIRE:LI11:614:HIGHLMT")
#! Record("WIRE:LI11:614:DONE",1700,22,0,0,"WIRE:LI11:614:DONE")
#! Record("WIRE:LI11:614:HOMELMT",1940,22,0,0,"WIRE:LI11:614:HOMELMT")
#! Record("WIRE:LI11:614:FAULT",2180,22,0,0,"WIRE:LI11:614:FAULT")
#! Record("WIRE:LI11:614:HASENCODER",2420,22,0,0,"WIRE:LI11:614:HASENCODER")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBDEND


record(bo, "WIRE:LI11:744:POWER") {
  field(DTYP, "asynInt32")
  field(OUT, "@asyn(Hy8601-01 1)HYTEC_POWER")
  field(VAL, "1")
  field(ZNAM, "On")
  field(ONAM, "Off")
}

record(bo, "WIRE:LI11:744:BRAKE") {
  field(DTYP, "asynInt32")
  field(OUT, "@asyn(Hy8601-01 1)HYTEC_BRAKE")
  field(VAL, "1")
  field(ZNAM, "Set")
  field(ONAM, "Rls")
}

record(ai, "WIRE:LI11:744:FIRMWARE_VERSION") {
  field(PINI, "YES")
  field(DTYP, "asynInt32")
  field(INP, "@asyn(Hy8601-01 1)HYTEC_FWVERSION")
  field(SCAN, "1 second")
}

record(ai, "WIRE:LI11:744:EN_POSN") {
  field(PINI, "YES")
  field(DTYP, "asynInt32")
  field(INP, "@asyn(Hy8601-01 1)MOTOR_ENCODER_POSITION")
  field(SCAN, "1 second")
}

record(ai, "WIRE:LI11:744:LOWLMT") {
  field(SCAN, "I/O Intr")
  field(DTYP, "asynInt32")
  field(INP, "@asyn(Hy8601-01 1) MOTOR_STATUS_LOW_LIMIT")
}

record(ai, "WIRE:LI11:744:HIGHLMT") {
  field(SCAN, "I/O Intr")
  field(DTYP, "asynInt32")
  field(INP, "@asyn(Hy8601-01 1) MOTOR_STATUS_HIGH_LIMIT")
}

record(ai, "WIRE:LI11:744:DONE") {
  field(SCAN, "I/O Intr")
  field(DTYP, "asynInt32")
  field(INP, "@asyn(Hy8601-01 1) MOTOR_STATUS_DONE")
}

record(ai, "WIRE:LI11:744:HOMELMT") {
  field(SCAN, "I/O Intr")
  field(DTYP, "asynInt32")
  field(INP, "@asyn(Hy8601-01 1) MOTOR_STATUS_AT_HOME")
}

record(ai, "WIRE:LI11:744:FAULT") {
  field(SCAN, "I/O Intr")
  field(DTYP, "asynInt32")
  field(INP, "@asyn(Hy8601-01 1) MOTOR_STATUS_PROBLEM")
}

record(ai, "WIRE:LI11:744:HASENCODER") {
  field(SCAN, "I/O Intr")
  field(DTYP, "asynInt32")
  field(INP, "@asyn(Hy8601-01 1) MOTOR_STATUS_HAS_ENCODER")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("WIRE:LI11:744:POWER",20,14,0,0,"WIRE:LI11:744:POWER")
#! Record("WIRE:LI11:744:BRAKE",260,14,0,0,"WIRE:LI11:744:BRAKE")
#! Record("WIRE:LI11:744:POSN",500,5,0,0,"WIRE:LI11:744:POSN")
#! Field("WIRE:LI11:744:POSN.FLNK",16777215,1,"WIRE:LI11:744:POSN.FLNK")
#! Record("WIRE:LI11:744:FIRMWARE_VERSION",740,28,0,0,"WIRE:LI11:744:FIRMWARE_VERSION")
#! Record("WIRE:LI11:744:EN_POSN",980,28,0,0,"WIRE:LI11:744:EN_POSN")
#! Record("WIRE:LI11:744:LOWLMT",1220,22,0,0,"WIRE:LI11:744:LOWLMT")
#! Record("WIRE:LI11:744:HIGHLMT",1460,22,0,0,"WIRE:LI11:744:HIGHLMT")
#! Record("WIRE:LI11:744:DONE",1700,22,0,0,"WIRE:LI11:744:DONE")
#! Record("WIRE:LI11:744:HOMELMT",1940,22,0,0,"WIRE:LI11:744:HOMELMT")
#! Record("WIRE:LI11:744:FAULT",2180,22,0,0,"WIRE:LI11:744:FAULT")
#! Record("WIRE:LI11:744:HASENCODER",2420,22,0,0,"WIRE:LI11:744:HASENCODER")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBDEND


record(bo, "WIRE:LI12:214:POWER") {
  field(DTYP, "asynInt32")
  field(OUT, "@asyn(Hy8601-01 2)HYTEC_POWER")
  field(VAL, "1")
  field(ZNAM, "On")
  field(ONAM, "Off")
}

record(bo, "WIRE:LI12:214:BRAKE") {
  field(DTYP, "asynInt32")
  field(OUT, "@asyn(Hy8601-01 2)HYTEC_BRAKE")
  field(VAL, "1")
  field(ZNAM, "Set")
  field(ONAM, "Rls")
}

record(ai, "WIRE:LI12:214:FIRMWARE_VERSION") {
  field(PINI, "YES")
  field(DTYP, "asynInt32")
  field(INP, "@asyn(Hy8601-01 2)HYTEC_FWVERSION")
  field(SCAN, "1 second")
}

record(ai, "WIRE:LI12:214:EN_POSN") {
  field(PINI, "YES")
  field(DTYP, "asynInt32")
  field(INP, "@asyn(Hy8601-01 2)MOTOR_ENCODER_POSITION")
  field(SCAN, "1 second")
}

record(ai, "WIRE:LI12:214:LOWLMT") {
  field(SCAN, "I/O Intr")
  field(DTYP, "asynInt32")
  field(INP, "@asyn(Hy8601-01 2) MOTOR_STATUS_LOW_LIMIT")
}

record(ai, "WIRE:LI12:214:HIGHLMT") {
  field(SCAN, "I/O Intr")
  field(DTYP, "asynInt32")
  field(INP, "@asyn(Hy8601-01 2) MOTOR_STATUS_HIGH_LIMIT")
}

record(ai, "WIRE:LI12:214:DONE") {
  field(SCAN, "I/O Intr")
  field(DTYP, "asynInt32")
  field(INP, "@asyn(Hy8601-01 2) MOTOR_STATUS_DONE")
}

record(ai, "WIRE:LI12:214:HOMELMT") {
  field(SCAN, "I/O Intr")
  field(DTYP, "asynInt32")
  field(INP, "@asyn(Hy8601-01 2) MOTOR_STATUS_AT_HOME")
}

record(ai, "WIRE:LI12:214:FAULT") {
  field(SCAN, "I/O Intr")
  field(DTYP, "asynInt32")
  field(INP, "@asyn(Hy8601-01 2) MOTOR_STATUS_PROBLEM")
}

record(ai, "WIRE:LI12:214:HASENCODER") {
  field(SCAN, "I/O Intr")
  field(DTYP, "asynInt32")
  field(INP, "@asyn(Hy8601-01 2) MOTOR_STATUS_HAS_ENCODER")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("WIRE:LI12:214:POWER",20,14,0,0,"WIRE:LI12:214:POWER")
#! Record("WIRE:LI12:214:BRAKE",260,14,0,0,"WIRE:LI12:214:BRAKE")
#! Record("WIRE:LI12:214:POSN",500,5,0,0,"WIRE:LI12:214:POSN")
#! Field("WIRE:LI12:214:POSN.FLNK",16777215,1,"WIRE:LI12:214:POSN.FLNK")
#! Record("WIRE:LI12:214:FIRMWARE_VERSION",740,28,0,0,"WIRE:LI12:214:FIRMWARE_VERSION")
#! Record("WIRE:LI12:214:EN_POSN",980,28,0,0,"WIRE:LI12:214:EN_POSN")
#! Record("WIRE:LI12:214:LOWLMT",1220,22,0,0,"WIRE:LI12:214:LOWLMT")
#! Record("WIRE:LI12:214:HIGHLMT",1460,22,0,0,"WIRE:LI12:214:HIGHLMT")
#! Record("WIRE:LI12:214:DONE",1700,22,0,0,"WIRE:LI12:214:DONE")
#! Record("WIRE:LI12:214:HOMELMT",1940,22,0,0,"WIRE:LI12:214:HOMELMT")
#! Record("WIRE:LI12:214:FAULT",2180,22,0,0,"WIRE:LI12:214:FAULT")
#! Record("WIRE:LI12:214:HASENCODER",2420,22,0,0,"WIRE:LI12:214:HASENCODER")