#! Generated by VisualDCT v2.6 #! DBDSTART #! DBD("../../../../dbd/mgntSoft.dbd") #! DBDEND record(seq, "$(DEV):STDZINIT") { field(DESC, "Proc. Stdz PVs on boot") field(PINI, "YES") field(DOL1, "1") field(DOL2, "1") field(DOL3, "1") field(LNK1, "$(DEV):DEBUG.PROC PP") field(LNK2, "$(DEV):STDZCYCLENUM.PROC PP") field(LNK3, "$(DEV):STDZDISABLE.PROC PP") field(LNK4, "$(DEV):STDZSUB.DISV PP") field(ASG, "Internal") } # Inputs: # A - minimum current set point # B - maximum current set point # C - final current set point # D - Number of cycles, where one cycle is min to max for stdzdirect=up (0) # or from imax to imin for stdzdirect=down (1). # The total number of set points would be 2*D+1 # E - Standardize direction (up=0,down=1). The standardize direction # is defined by magnet measurements (MMF). For lcls, all magnets # are standardized in the up direction, which means that the standardize # cycle would starts at imin to imax. If the direction was down, then the standardize # cycle would start from imax to imin. # F - Standardize disabled (0=enabled, 1=disabled) # G - Debug flag from the pv :DEBUG # # The standardize function is available for all controllable devices, but it is # typically only used for larger magnets (steel), powered by high current # supplies. These magnets tend to build up a residual field over time. This would # typically dipoles and quadrupoles. Saying this, the undulator quadrupoles, powered by 2A supplies # and these magnets are standardized. Therefore, to get a complete list of magnets that # should bestandardized for consulte the LCLS PRD 1.1-015, which provides a list, This # document also provides a list of standardize magnet groups, number of cycles, standardize # ramprates and settle times. # # A: :STDZIMIN # B: :STDZIMAX # C: :STDZIFINAL # D: :STDZCYCLENUM # E: :STDZDIRECT # F: :STDZDISABLE # G: :DEBUG # # The success or failure of the standardize function is set # in the pv :STDZOK, and the magnet is restored to the # desired b-field :BDES. # # :STDZOK (1=successfuly completed, 0=failed) # # The standardize function is available for individual magnets, # or the main (defined in db) of a string. Some indiviaul magnets are grouped # with a magnet string, such as boosts, trims or sometimes magnets # nearby a large magnet string. These groupings are defined in the # PRD 1.1-015. # # This PV is processed by :STDZIFINAL record(aSub, "$(DEV):STDZSUB") { field(DESC, "Stdz subroutine") field(INAM, "mgntStdzInit") field(SNAM, "mgntStdz") field(BRSV, "INVALID") field(INPA, "$(DEV):STDZIMIN NPP NMS") field(INPB, "$(DEV):STDZIMAX NPP NMS") field(INPC, "$(DEV):STDZIFINAL NPP NMS") field(INPD, "$(DEV):STDZCYCLENUM NPP NMS") field(INPE, "$(DEV):STDZDIRECT.RVAL NPP NMS") field(INPF, "$(DEV):STDZDISABLE.RVAL CPP NMS") field(INPG, "$(DEV):DEBUG.RVAL NPP NMS") field(FTA, "DOUBLE") field(FTB, "DOUBLE") field(FTC, "DOUBLE") field(FTD, "LONG") field(FTE, "ULONG") field(FTE, "ULONG") field(FTG, "ULONG") # Outputs: # OUTA: set point waveform # OUTB: mgntStdz status message # Note: the aSub sets the NORD field fo the # waveform record based on the value in NOVA. # # If NOVA changes, make sure that :STDZWF.NELM # is equal or greater than :STDZSUB.NOVA # field(OUTA, "$(DEV):STDZWF PP") field(OUTB, "$(DEV):STDZMSG PP") field(FTVA, "DOUBLE") field(FTVB, "USHORT") field(NOVA, "21") # On boot disable this PV from processing, # enabled processing from the pv # :STDZINIT, after all input pvs # have been processed. field(DISV, "0") field(FLNK, "$(DEV):STDZWF") } record(mbbo, "$(DEV):STDZMSG") { field(DESC, "STDZSUB pv status") field(NOBT, "2") field(ZRST, "Success") field(ONST, "None") field(TWST, "Wf too small") field(THST, "Unexepcted data type") } # This is the standardize waveform, generated by # the :STDZSUB # Note: :STDZWF.NELM must be equal or greater than :STDZSUB.NOVA record(waveform, "$(DEV):STDZWF") { field(DESC, "Stdz Setpts") field(NELM, "21") field(FTVL, "DOUBLE") } # # METHOD TO RESTORE A MULTI-BIT BINARY OUT and BO's # 1. DON'T DEFINE DOL # 2. SET PINI TO YES # 3. RESTORE THE VAL FIELD # ON THE VERY FIRST BOOT YOU MUST DO # A CAPUT TO THE MBBO AND THEN ON REBOOT # THE UDF WILL BE SET TO 0 AND THE VALUE # WILL BE RESTORED PROPERLY. # # IMPORTANT: # IF YOU DO NOT DO A CAPUT ON THE VERY FIRST BOOT, THE UDF # WILL BE SET TO 1 AND THE STAT/SEVR WILL BE # SET TO INVALID. THE INVALID STATE IS LOOKED # AT ON REBOOT BY THE RESTORE PROGRAM AND THE MBBO # WILL NOT BE RESTORED. SO IT'S VERY IMPORTANT TO DO # THE INITAL CAPUT. THIS METHOD ALSO WORKS FOR BOs. # NOTE THAT ANALOG OUTUPTS ARE ARE RESTORED IN THE # SAME MANNER SO THE VAL CAN BE RESTORED PROPERLY. # record(bo, "$(DEV):STDZMAINPS") { field(DESC, "Stdz by main or self") field(PINI, "YES") field(DTYP, "Soft Channel") field(ZNAM, "SELF") field(ONAM, "MAIN") } record(bo, "$(DEV):STDZPS") { field(DESC, "PS state after Stdz") field(PINI, "YES") field(ZNAM, "On") field(ONAM, "Off") field(DTYP, "Soft Channel") } # This pv is processed when starting and completing a standardize or degauss # function. At the start of each function the trims and/or related magnets are zeroed (2) # After the function has completed the trims and/or related magnets are trimmed (1). # # For strings with related magnets, such as trim coils or # nearby magents, specifed in the Magnet standardize PRD. # In this case, the string main the pv # STDZSLAVESGO is defined using the template # mgnt_string_ctrl.template, where the INP argument is set to # STDZGO.RVAL CPP, processing on change. record(mbbo, "$(DEV):STDZGO") { field(DESC, "Stdz trims") field(NOBT, "2") field(ZRST, "Ready") field(ONST, "TRIM") field(TWST, "DAC_ZERO") field(ZRVL, "0") field(ONVL, "1") field(TWVL, "8") } record(bo, "$(DEV):STDZOK") { field(DESC, "Standarize Successful") field(DTYP, "Raw Soft Channel") field(PINI, "YES") field(DTYP, "Soft Channel") field(ZNAM, "NO") field(ONAM, "YES") info(autosaveFields,"VAL RVAL") } record(stringout, "$(DEV):STDZTOD") { field(DESC, "Successful Standardize Time") field(PINI, "YES") field(DTYP, "Soft Channel") field(VAL, " ") info(autosaveFields,"VAL") } record(stringout, "$(DEV):STDZLOSTTOD") { field(DESC, "Standardize Lost Time") field(PINI, "YES") field(DTYP, "Soft Channel") field(VAL, " ") info(autosaveFields,"VAL") } record(longout, "$(DEV):STDZCYCLECNT") { field(DESC, "Cycle Count") field(PINI, "YES") } record(longout, "$(DEV):STDZCYCLENUM") { field(DESC, "No. Standardize Cycles") field(VAL, "$(NCYC=3)") field(HOPR, "10") field(LOPR, "0") field(DRVH, "10") field(DRVL, "0") field(PINI, "YES") field(FLNK, "$(DEV):STDZDIRECT") } # The default standardize direction is "UP" for # all LCLS Magnets.. record(bo, "$(DEV):STDZDIRECT") { field(DESC, "Standardize Direction ") field(ZNAM, "UP") field(ONAM, "DOWN") field(VAL, "0") field(FLNK, "$(DEV):STDZIMIN") } record(ao, "$(DEV):STDZIMIN") { field(DESC, "Min-STDZ Current") field(PREC, "1") field(EGU, "A") field(HOPR, "$(HIHI)") field(LOPR, "$(LOLO)") field(VAL, "$(LOLO)") field(FLNK, "$(DEV):STDZIMAX") } record(ao, "$(DEV):STDZIMAX") { field(DESC, "Max. Standarize Current") field(DTYP, "Soft Channel") field(PREC, "1") field(EGU, "A") field(HOPR, "$(HIHI)") field(LOPR, "$(LOLO)") field(VAL, "$(HIHI)") field(FLNK, "$(DEV):STDZIFINAL") } record(ao, "$(DEV):STDZIFINAL") { field(DESC, "Final SDTZ Current") field(DTYP, "Soft Channel") field(PREC, "1") field(EGU, "A") field(HOPR, "$(HIHI)") field(LOPR, "$(LOLO)") field(VAL, "$(LOLO)") field(FLNK, "$(DEV):STDZSUB") } # Loose tolerance on desired current-ADC measured current. # used for calibration and standardize. This is an # absolute tolerance with the default set to 10 percent. # Note: in slc ATOL(1), absolute tolerance record(ao, "$(DEV):STDZITOLR") { field(DESC, "Stdz tolerance min") field(DTYP, "Soft Channel") field(PREC, "5") field(DRVL, "0.05") field(DRVH, "10.0") field(VAL, "0.1") field(EGU, "%") field(PINI, "YES") } # Loose tolerance on desired current-adc measured current. # used for calibration and standardize. The tolerance # is a percentage (INPC=5%) of the maximum current. Note that # we have bipolar supplies, so the absolute value of # the min and max current is taken. # Note: in slc ATOL(2), fractional tolerance record(calc, "$(DEV):STDZITOL") { field(DESC, "Stdz min tolerance") field(PREC, "5") field(CALC, "MAX(ABS(A),ABS(B))*C") field(INPA, "$(DEV):STDZIMIN CP NMS") field(INPB, "$(DEV):STDZIMAX CP MMS") field(INPC, "0.05") field(INPD, "$(DEV):STDZITOLR CP MMS") field(EGU, "A") field(FLNK, "$(DEV):IDELTAS") field(PINI, "YES") } # D - factor (3.154/2 = 1.577) for EPSC, otherwise, set to 1.0 record(calc, "$(DEV):STDZDLY") { field(DESC, "Ramp time for stdz cycle") field(CALC, "C>0?MAX(1,ABS((A-B)/C)*D):0") field(INPA, "$(DEV):STDZIMIN CP NMS") field(INPB, "$(DEV):STDZIMAX CP NMS") field(INPC, "$(DEV):TRIMRAMPRATE CP NMS") field(INPD, "$(MULT=1.0)") field(PREC, "5") field(EGU, "sec") field(PINI, "YES") } record(calc, "$(DEV):STDZRAMPDLY") { field(DESC, "Ramp delay total") field(CALC, "MAX(1,((A/100)*B+B))") field(PREC, "5") field(INPA, "$(DEV):TRIMDLYPCT CP MS") field(INPB, "$(DEV):STDZDLY CP MS") field(EGU, "sec") } # Meeting 4/22/2011 Loos, Sullivan decided to wait 1 sec # Note: see note in mgntCtrl.st, mgntCtrl_settle_wait record(calc, "$(DEV):STDZMINIDLY") { field(DESC, "Mini-stdz delay") field(CALC, "A") field(PREC, "5") field(A, "1.0") field(EGU, "sec") field(PINI, "YES") } record(ao, "$(DEV):STDZMINIPCT") { field(DESC, "Mini Stdz percent") field(DTYP, "Soft Channel") field(VAL, "5.0") field(EGU, "%") field(PREC, "2") field(DRVH, "15.0") field(DRVL, "0.0") field(HOPR, "15.0") field(LOPR, "0.0") field(PINI, "YES") } record(calc, "$(DEV):STDZMINIDELTA") { field(DESC, "Stdz mini % of IMAX") field(CALC, "(B/100)*(A-C)") field(INPA, "$(DEV):IDES.HOPR") field(INPB, "$(DEV):STDZMINIPCT CPP NMS") field(INPC, "$(DEV):IDES.LOPR") field(PREC, "5") } record(calc, "$(DEV):STDZMINISETPT") { field(DESC, "Mini Stdz delta") field(CALC, "C==0?MAX(E-D,B):MIN(E+D,A)") field(INPA, "$(DEV):IDES.HOPR") field(INPB, "$(DEV):IDES.LOPR") field(INPC, "$(DEV):STDZDIRECT.RVAL") field(INPD, "$(DEV):STDZMINIDELTA") field(INPE, "$(DEV):IDES") field(PREC, "5") field(FLNK, "$(DEV):STDZMINISETPTOOR") } # This PV is 1 if STDZMINISETPT is out of range (greater than # IDES.HOPR or less than IDES.LOPR) and 0 otherwise. record(calc, "$(DEV):STDZMINISETPTOOR") { field(DESC, "Mini Stdz setpoint out of range") field(CALC, "C==0?(E-DA)") field(INPA, "$(DEV):IDES.HOPR") field(INPB, "$(DEV):IDES.LOPR") field(INPC, "$(DEV):STDZDIRECT.RVAL") field(INPD, "$(DEV):STDZMINIDELTA") field(INPE, "$(DEV):IDES") field(PREC, "5") } # DR 4/2011 add these 2 records for perturb slider # If currently standardized and we are moving opposite # to the direction of standardization, then clear STDZOK # and not the time that standardize was lost in STDZTOD. # However, if standardization has already been lost don't # change the standardize lost date or bother to clear STDZOK. # To enable STDZ, STDZDISABLE = 0 = Enabled # # AL 7/2022 lose standardize only if out of tolerance # AL 10/2022 do not lose standardize if IACT is invalid # AL 10/2023 lose standardize if turned off even if not # out of tolerance # # This PV is processed by :BCTRLGO and a change in :STATE record(calcout, "$(DEV):CHECKSTDZLOST") { field(DESC, "Check if stdz is lost") field(CALC, "(G=3||I=3)?0:C=1&&D=0&&((H=1&&A#B)||(E=0))?3:0") field(INPA, "$(DEV):IADJUST.RVAL") field(INPB, "$(DEV):STDZDIRECT.RVAL") field(INPC, "$(DEV):STDZOK.RVAL") field(INPD, "$(DEV):STDZDISABLE.RVAL") field(INPE, "$(DEV):STATE.RVAL CPP NMS") field(INPF, "$(DEV):ICTRL.RVAL") field(INPG, "$(DEV):STATE.SEVR") field(INPH, "$(DEV):BDELTAS.M") field(INPI, "$(DEV):IACT.SEVR") field(OUT, "$(DEV):STDZLOSTGO.SELN PP NMS") field(OOPT, "Transition To Non-zero") field(FLNK, "$(DEV):STDZLOSTGO") } record(seq, "$(DEV):STDZLOSTGO") { field(DESC, "Process lost stdz") field(SELM, "Mask") field(SELL, "$(DEV):CHECKSTDZLOST") field(DOL1, "1") field(DOL2, "0") field(LNK1, "$(DEV):STDZLOSTTOD.PROC") field(LNK2, "$(DEV):STDZOK PP") }