#! Generated by VisualDCT v2.5 #! DBDSTART #! DBDEND # Initialize model pvs on boot record(seq, "$(DEV):BMAGINIT") { field(DOL1, "1") field(DOL2, "1") field(DOL3, "0") field(DOL4, "1") field(DOL5, "1") field(DOL6, "1") field(DOL7, "1") field(DOL8, "1") field(DLY8, "1") field(DOL9, "1") field(DOLA, "1") field(LNK1, "$(DEV):EDES.PROC PP") field(LNK2, "$(DEV):EACT.PROC PP") field(LNK3, "$(DEV):EERR.DISA PP") field(LNK4, "$(DEV):ECON.PROC PP") field(LNK5, "$(DEV):BMAGX.PROC PP") field(LNK6, "$(DEV):BMAGY.PROC PP") field(LNK7, "$(DEV):BLEM.PROC PP") field(LNK8, "$(DEV):BMOD.PROC PP") field(LNK9, "$(DEV):EDESSAVE.PROC PP") field(LNKA, "$(DEV):BMAGLIMITS.PROC PP") field(PINI, "YES") } record(seq,"$(DEV):BMAGLIMITS") { field(DESC, "BMAG Limits") field(DOL1, "$(DEV):BMAX") field(DOL2, "$(DEV):BMAX") field(DOL3, "$(DEV):BMAX") field(DOL4, "$(DEV):BMIN") field(DOL5, "$(DEV):BMIN") field(DOL6, "$(DEV):BMIN") field(LNK1, "$(DEV):BMAGX.HOPR") field(LNK2, "$(DEV):BMAGY.HOPR") field(LNK3, "$(DEV):BLEM.HOPR") field(LNK4, "$(DEV):BMAGX.LOPR PP") field(LNK5, "$(DEV):BMAGY.LOPR PP") field(LNK6, "$(DEV):BLEM.LOPR PP") } # No EGU as per Henrik record(ao, "$(DEV):BMAGX") { field(DESC, "Calc Horiz B-field") field(DTYP, "Soft Channel") field(PREC, "7") info(autosaveFields,"VAL") } # No EGU as per Henrik record(ao, "$(DEV):BMAGY") { field(DESC, "Calc Vert B-field") field(DTYP, "Soft Channel") field(PREC, "7") info(autosaveFields,"VAL") } # BLEM value can change when we change eh setting in LEM # BMOD is always caluated using same formula record(ao, "$(DEV):BLEM") { field(DESC, "Calc LEM B-field") field(DTYP, "Soft Channel") field(EGU, "$(EGU)") field(PREC, "7") info(autosaveFields,"VAL") } record(ao, "$(DEV):BMOD") { field(DESC, "Calc LEM B-field") field(DTYP, "Soft Channel") field(EGU, "$(EGU)") field(PREC, "7") info(autosaveFields,"VAL") } # Beam Energy PVs record(ao, "$(DEV):EDESSAVE") { field(DESC, "edes for save/load") field(DTYP, "Soft Channel") field(EGU, "GeV/c)") field(HOPR, "50.0") field(DRVH, "50.0") field(PREC, "7") info(autosaveFields,"VAL") } record(ao, "$(DEV):ECON") { field(DESC, "Energy Config") field(DTYP, "Soft Channel") field(DRVH, "50.0") field(DRVL, "0.0") field(EGU, "GeV/c") field(HOPR, "50.0") field(LOPR, "0.0") field(PREC, "6") $(LNK=#) field(DOL, "$(CON="")") field(OMSL, "$(OMSL=supervisory")") info(autosaveFields,"VAL") } record(ao, "$(DEV):EDES") { field(DESC, "Desired Energy") field(DTYP, "Soft Channel") field(DRVH, "50.0") field(HOPR, "50.0") field(EGU, "GeV/c") field(PREC, "6") $(LNK=#) field(DOL, "$(DES="")") field(OMSL, "$(OMSL=supervisory")") field(FLNK, "$(DEV):EERR") info(autosaveFields,"VAL") } record(ao, "$(DEV):EACT") { field(DESC, "Actual Energy") field(DTYP, "Soft Channel") field(DRVH, "50.0") field(DRVL, "0.0") field(EGU, "Gev/c") field(HOPR, "50.0") field(LOPR, "0.0") field(PREC, "6") $(LNK=#) field(DOL, "$(ACT="")") field(OMSL, "$(OMSL=supervisory")") field(FLNK, "$(DEV):EERR") info(autosaveFields,"VAL") } # This is the error of EACT-EDES used by the LEM CUD # The error is 0.5% of EDES, unless EDES=0 then # the error is 0. record(calc, "$(DEV):EERR") { field(DESC, "LEM Error") field(CALC, "A?((B-A)/A):0") field(INPA, "$(DEV):EDES NPP MS") field(INPB, "$(DEV):EACT NPP MS") field(HIHI, "0.005") field(HIGH, "0.005") field(LOLO, "-0.005") field(LOW, "-0.005") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MAJOR") field(LSV, "MAJOR") field(DISA, "1") }