#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(longout, "MGNT:IN10:1:CTRLSWITCH") {
}

# The LNK# (1-8) MUST corresponsds to the magent
# type definition found in the file mgntCtrl.h.
# For example, MGNT_TYPE_BEND is defined as 2 and is LNK2 below.
# If the LNK order is changes you will need to make the
# corresponding change the pv <device>:<type>CTRL which is
# found in the files mgnt_ctrl_allstar.substitutions
# The field FFVL value in MGNT:<LOCA>:1: CTRLCLEAR MUST be set
# to the value for MGNT_TYPE_ALL which is defined as 1 in mgntCtrl.h
# so that it can be used properly by the the PV  MGNT:LI21:1:ALLSWITCH
#
record(seq, "MGNT:IN10:1:CTRLCLEAR") {
  field(DESC, "All function go")
  field(DOL1, "0")
  field(DOL2, "0")
  field(DOL3, "0")
  field(DOL4, "0")
  field(DOL5, "0")
  field(DOL6, "0")
  field(DOL7, "0")
  field(DOL8, "0")
  field(DOL9, "0")
  field(DOLA, "0")
  field(LNK1, "MGNT:IN10:1:CTRL CA PP")
  field(LNK2, "MGNT:IN10:1:BENDCTRL CA PP")
  field(LNK3, "MGNT:IN10:1:BTRMCTRL CA PP")
  field(LNK4, "MGNT:IN10:1:LGPSCTRL CA PP")
  field(LNK5, "MGNT:IN10:1:QUADCTRL CA PP")
  field(LNK6, "MGNT:IN10:1:XCORCTRL CA PP")
  field(LNK7, "MGNT:IN10:1:YCORCTRL CA PP")
  field(LNK8, "MGNT:IN10:1:SOLNCTRL CA PP")
  field(LNK9, "MGNT:IN10:1:KICKCTRL CA PP")
  field(LNKA, "MGNT:IN10:1:SEXTCTRL CA PP")
}

record(mbbo, "MGNT:IN10:1:CTRL") {
  field(DESC, "All Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "1")
  field(FLNK, "MGNT:IN10:1:ALLSWITCH")
}

record(seq, "MGNT:IN10:1:ALLSWITCH") {
  field(DOL1, "MGNT:IN10:1:CTRL.FFVL")
  field(LNK1, "MGNT:IN10:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:IN10:1:ALLFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:IN10:1:CTRL")
}

record(bo, "MGNT:IN10:1:ALLSTAR") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(PINI, "YES")
  field(FLNK, "MGNT:IN10:1:ALLSTARGO")
}

record(fanout, "MGNT:IN10:1:ALLSTARGO") {
  field(LNK1, "MGNT:IN10:1:ALLBENDSGO")
  field(LNK2, "MGNT:IN10:1:ALLBTRMSGO")
  field(LNK3, "MGNT:IN10:1:ALLLGPSSGO")
  field(LNK4, "MGNT:IN10:1:ALLQUADSGO")
  field(LNK5, "MGNT:IN10:1:ALLXCORSGO")
  field(LNK6, "MGNT:IN10:1:ALLYCORSGO")
  field(FLNK, "MGNT:IN10:1:ALLSTARGO_2")
}
record(fanout, "MGNT:IN10:1:ALLSTARGO_2") {
  field(LNK1, "MGNT:IN10:1:ALLSOLNSGO")
  field(LNK2, "MGNT:IN10:1:ALLKICKSGO")
  field(LNK3, "MGNT:IN10:1:ALLSEXTSGO")
}

#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:BENDCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_BEND so that it can be
# used properly by the the PV <device>:BENDSWITCH

record(mbbo, "MGNT:IN10:1:BENDCTRL") {
  field(DESC, "All BEND Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "2")
  field(FLNK, "MGNT:IN10:1:BENDSWITCH")
}

record(seq, "MGNT:IN10:1:BENDSWITCH") {
  field(DOL1, "MGNT:IN10:1:BENDCTRL.FFVL")
  field(LNK1, "MGNT:IN10:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:IN10:1:BENDFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:IN10:1:BENDCTRL")
}

record(seq, "MGNT:IN10:1:ALLBENDSGO") {
  field(DOL1, "MGNT:IN10:1:ALLSTAR")
  field(LNK1, "MGNT:IN10:1:ALLBENDS PP NMS")
}

record(bo, "MGNT:IN10:1:ALLBENDS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:IN10:1:ALLBENDSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:IN10:1:BENDCTRL",20,10,0,0,"MGNT:IN10:1:BENDCTRL")
#! Field("MGNT:IN10:1:BENDCTRL.FLNK",16777215,1,"MGNT:IN10:1:BENDCTRL.FLNK")
#! Link("MGNT:IN10:1:BENDCTRL.FLNK","MGNT:IN10:1:BENDSWITCH")
#! Field("MGNT:IN10:1:BENDCTRL.FFVL",16777215,1,"MGNT:IN10:1:BENDCTRL.FFVL")
#! Record("MGNT:IN10:1:BENDSWITCH",460,322,0,0,"MGNT:IN10:1:BENDSWITCH")
#! Field("MGNT:IN10:1:BENDSWITCH.DOL1",16777215,0,"MGNT:IN10:1:BENDSWITCH.DOL1")
#! Link("MGNT:IN10:1:BENDSWITCH.DOL1","MGNT:IN10:1:BENDCTRL.FFVL")
#! Field("MGNT:IN10:1:BENDSWITCH.LNK1",16777215,1,"MGNT:IN10:1:BENDSWITCH.LNK1")
#! Field("MGNT:IN10:1:BENDSWITCH.FLNK",16777215,1,"MGNT:IN10:1:BENDSWITCH.FLNK")
#! Record("MGNT:IN10:1:ALLBENDSGO",240,96,0,0,"MGNT:IN10:1:ALLBENDSGO")
#! Field("MGNT:IN10:1:ALLBENDSGO.DOL1",16777215,1,"MGNT:IN10:1:ALLBENDSGO.DOL1")
#! Field("MGNT:IN10:1:ALLBENDSGO.LNK1",16777215,1,"MGNT:IN10:1:ALLBENDSGO.LNK1")
#! Link("MGNT:IN10:1:ALLBENDSGO.LNK1","MGNT:IN10:1:ALLBENDS.VAL")
#! Record("MGNT:IN10:1:ALLBENDS",540,102,0,0,"MGNT:IN10:1:ALLBENDS")
#! Field("MGNT:IN10:1:ALLBENDS.VAL",16777215,0,"MGNT:IN10:1:ALLBENDS.VAL")
#! Field("MGNT:IN10:1:ALLBENDS.FLNK",16777215,1,"MGNT:IN10:1:ALLBENDS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:BTRMCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_BTRM so that it can be
# used properly by the the PV <device>:BTRMSWITCH

record(mbbo, "MGNT:IN10:1:BTRMCTRL") {
  field(DESC, "All BTRM Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "3")
  field(FLNK, "MGNT:IN10:1:BTRMSWITCH")
}

record(seq, "MGNT:IN10:1:BTRMSWITCH") {
  field(DOL1, "MGNT:IN10:1:BTRMCTRL.FFVL")
  field(LNK1, "MGNT:IN10:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:IN10:1:BTRMFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:IN10:1:BTRMCTRL")
}

record(seq, "MGNT:IN10:1:ALLBTRMSGO") {
  field(DOL1, "MGNT:IN10:1:ALLSTAR")
  field(LNK1, "MGNT:IN10:1:ALLBTRMS PP NMS")
}

record(bo, "MGNT:IN10:1:ALLBTRMS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:IN10:1:ALLBTRMSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:IN10:1:BTRMCTRL",20,10,0,0,"MGNT:IN10:1:BTRMCTRL")
#! Field("MGNT:IN10:1:BTRMCTRL.FLNK",16777215,1,"MGNT:IN10:1:BTRMCTRL.FLNK")
#! Link("MGNT:IN10:1:BTRMCTRL.FLNK","MGNT:IN10:1:BTRMSWITCH")
#! Field("MGNT:IN10:1:BTRMCTRL.FFVL",16777215,1,"MGNT:IN10:1:BTRMCTRL.FFVL")
#! Record("MGNT:IN10:1:BTRMSWITCH",460,322,0,0,"MGNT:IN10:1:BTRMSWITCH")
#! Field("MGNT:IN10:1:BTRMSWITCH.DOL1",16777215,0,"MGNT:IN10:1:BTRMSWITCH.DOL1")
#! Link("MGNT:IN10:1:BTRMSWITCH.DOL1","MGNT:IN10:1:BTRMCTRL.FFVL")
#! Field("MGNT:IN10:1:BTRMSWITCH.LNK1",16777215,1,"MGNT:IN10:1:BTRMSWITCH.LNK1")
#! Field("MGNT:IN10:1:BTRMSWITCH.FLNK",16777215,1,"MGNT:IN10:1:BTRMSWITCH.FLNK")
#! Record("MGNT:IN10:1:ALLBTRMSGO",240,96,0,0,"MGNT:IN10:1:ALLBTRMSGO")
#! Field("MGNT:IN10:1:ALLBTRMSGO.DOL1",16777215,1,"MGNT:IN10:1:ALLBTRMSGO.DOL1")
#! Field("MGNT:IN10:1:ALLBTRMSGO.LNK1",16777215,1,"MGNT:IN10:1:ALLBTRMSGO.LNK1")
#! Link("MGNT:IN10:1:ALLBTRMSGO.LNK1","MGNT:IN10:1:ALLBTRMS.VAL")
#! Record("MGNT:IN10:1:ALLBTRMS",540,102,0,0,"MGNT:IN10:1:ALLBTRMS")
#! Field("MGNT:IN10:1:ALLBTRMS.VAL",16777215,0,"MGNT:IN10:1:ALLBTRMS.VAL")
#! Field("MGNT:IN10:1:ALLBTRMS.FLNK",16777215,1,"MGNT:IN10:1:ALLBTRMS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:LGPSCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_LGPS so that it can be
# used properly by the the PV <device>:LGPSSWITCH

record(mbbo, "MGNT:IN10:1:LGPSCTRL") {
  field(DESC, "All LGPS Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "3")
  field(FLNK, "MGNT:IN10:1:LGPSSWITCH")
}

record(seq, "MGNT:IN10:1:LGPSSWITCH") {
  field(DOL1, "MGNT:IN10:1:LGPSCTRL.FFVL")
  field(LNK1, "MGNT:IN10:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:IN10:1:LGPSFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:IN10:1:LGPSCTRL")
}

record(seq, "MGNT:IN10:1:ALLLGPSSGO") {
  field(DOL1, "MGNT:IN10:1:ALLSTAR")
  field(LNK1, "MGNT:IN10:1:ALLLGPSS PP NMS")
}

record(bo, "MGNT:IN10:1:ALLLGPSS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:IN10:1:ALLLGPSSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:IN10:1:LGPSCTRL",20,10,0,0,"MGNT:IN10:1:LGPSCTRL")
#! Field("MGNT:IN10:1:LGPSCTRL.FLNK",16777215,1,"MGNT:IN10:1:LGPSCTRL.FLNK")
#! Link("MGNT:IN10:1:LGPSCTRL.FLNK","MGNT:IN10:1:LGPSSWITCH")
#! Field("MGNT:IN10:1:LGPSCTRL.FFVL",16777215,1,"MGNT:IN10:1:LGPSCTRL.FFVL")
#! Record("MGNT:IN10:1:LGPSSWITCH",460,322,0,0,"MGNT:IN10:1:LGPSSWITCH")
#! Field("MGNT:IN10:1:LGPSSWITCH.DOL1",16777215,0,"MGNT:IN10:1:LGPSSWITCH.DOL1")
#! Link("MGNT:IN10:1:LGPSSWITCH.DOL1","MGNT:IN10:1:LGPSCTRL.FFVL")
#! Field("MGNT:IN10:1:LGPSSWITCH.LNK1",16777215,1,"MGNT:IN10:1:LGPSSWITCH.LNK1")
#! Field("MGNT:IN10:1:LGPSSWITCH.FLNK",16777215,1,"MGNT:IN10:1:LGPSSWITCH.FLNK")
#! Record("MGNT:IN10:1:ALLLGPSSGO",240,96,0,0,"MGNT:IN10:1:ALLLGPSSGO")
#! Field("MGNT:IN10:1:ALLLGPSSGO.DOL1",16777215,1,"MGNT:IN10:1:ALLLGPSSGO.DOL1")
#! Field("MGNT:IN10:1:ALLLGPSSGO.LNK1",16777215,1,"MGNT:IN10:1:ALLLGPSSGO.LNK1")
#! Link("MGNT:IN10:1:ALLLGPSSGO.LNK1","MGNT:IN10:1:ALLLGPSS.VAL")
#! Record("MGNT:IN10:1:ALLLGPSS",540,102,0,0,"MGNT:IN10:1:ALLLGPSS")
#! Field("MGNT:IN10:1:ALLLGPSS.VAL",16777215,0,"MGNT:IN10:1:ALLLGPSS.VAL")
#! Field("MGNT:IN10:1:ALLLGPSS.FLNK",16777215,1,"MGNT:IN10:1:ALLLGPSS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:QUADCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_QUAD so that it can be
# used properly by the the PV <device>:QUADSWITCH

record(mbbo, "MGNT:IN10:1:QUADCTRL") {
  field(DESC, "All QUAD Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "5")
  field(FLNK, "MGNT:IN10:1:QUADSWITCH")
}

record(seq, "MGNT:IN10:1:QUADSWITCH") {
  field(DOL1, "MGNT:IN10:1:QUADCTRL.FFVL")
  field(LNK1, "MGNT:IN10:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:IN10:1:QUADFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:IN10:1:QUADCTRL")
}

record(seq, "MGNT:IN10:1:ALLQUADSGO") {
  field(DOL1, "MGNT:IN10:1:ALLSTAR")
  field(LNK1, "MGNT:IN10:1:ALLQUADS PP NMS")
}

record(bo, "MGNT:IN10:1:ALLQUADS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:IN10:1:ALLQUADSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:IN10:1:QUADCTRL",20,10,0,0,"MGNT:IN10:1:QUADCTRL")
#! Field("MGNT:IN10:1:QUADCTRL.FLNK",16777215,1,"MGNT:IN10:1:QUADCTRL.FLNK")
#! Link("MGNT:IN10:1:QUADCTRL.FLNK","MGNT:IN10:1:QUADSWITCH")
#! Field("MGNT:IN10:1:QUADCTRL.FFVL",16777215,1,"MGNT:IN10:1:QUADCTRL.FFVL")
#! Record("MGNT:IN10:1:QUADSWITCH",460,322,0,0,"MGNT:IN10:1:QUADSWITCH")
#! Field("MGNT:IN10:1:QUADSWITCH.DOL1",16777215,0,"MGNT:IN10:1:QUADSWITCH.DOL1")
#! Link("MGNT:IN10:1:QUADSWITCH.DOL1","MGNT:IN10:1:QUADCTRL.FFVL")
#! Field("MGNT:IN10:1:QUADSWITCH.LNK1",16777215,1,"MGNT:IN10:1:QUADSWITCH.LNK1")
#! Field("MGNT:IN10:1:QUADSWITCH.FLNK",16777215,1,"MGNT:IN10:1:QUADSWITCH.FLNK")
#! Record("MGNT:IN10:1:ALLQUADSGO",240,96,0,0,"MGNT:IN10:1:ALLQUADSGO")
#! Field("MGNT:IN10:1:ALLQUADSGO.DOL1",16777215,1,"MGNT:IN10:1:ALLQUADSGO.DOL1")
#! Field("MGNT:IN10:1:ALLQUADSGO.LNK1",16777215,1,"MGNT:IN10:1:ALLQUADSGO.LNK1")
#! Link("MGNT:IN10:1:ALLQUADSGO.LNK1","MGNT:IN10:1:ALLQUADS.VAL")
#! Record("MGNT:IN10:1:ALLQUADS",540,102,0,0,"MGNT:IN10:1:ALLQUADS")
#! Field("MGNT:IN10:1:ALLQUADS.VAL",16777215,0,"MGNT:IN10:1:ALLQUADS.VAL")
#! Field("MGNT:IN10:1:ALLQUADS.FLNK",16777215,1,"MGNT:IN10:1:ALLQUADS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:XCORCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_XCOR so that it can be
# used properly by the the PV <device>:XCORSWITCH

record(mbbo, "MGNT:IN10:1:XCORCTRL") {
  field(DESC, "All XCOR Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "6")
  field(FLNK, "MGNT:IN10:1:XCORSWITCH")
}

record(seq, "MGNT:IN10:1:XCORSWITCH") {
  field(DOL1, "MGNT:IN10:1:XCORCTRL.FFVL")
  field(LNK1, "MGNT:IN10:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:IN10:1:XCORFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:IN10:1:XCORCTRL")
}

record(seq, "MGNT:IN10:1:ALLXCORSGO") {
  field(DOL1, "MGNT:IN10:1:ALLSTAR")
  field(LNK1, "MGNT:IN10:1:ALLXCORS PP NMS")
}

record(bo, "MGNT:IN10:1:ALLXCORS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:IN10:1:ALLXCORSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:IN10:1:XCORCTRL",20,10,0,0,"MGNT:IN10:1:XCORCTRL")
#! Field("MGNT:IN10:1:XCORCTRL.FLNK",16777215,1,"MGNT:IN10:1:XCORCTRL.FLNK")
#! Link("MGNT:IN10:1:XCORCTRL.FLNK","MGNT:IN10:1:XCORSWITCH")
#! Field("MGNT:IN10:1:XCORCTRL.FFVL",16777215,1,"MGNT:IN10:1:XCORCTRL.FFVL")
#! Record("MGNT:IN10:1:XCORSWITCH",460,322,0,0,"MGNT:IN10:1:XCORSWITCH")
#! Field("MGNT:IN10:1:XCORSWITCH.DOL1",16777215,0,"MGNT:IN10:1:XCORSWITCH.DOL1")
#! Link("MGNT:IN10:1:XCORSWITCH.DOL1","MGNT:IN10:1:XCORCTRL.FFVL")
#! Field("MGNT:IN10:1:XCORSWITCH.LNK1",16777215,1,"MGNT:IN10:1:XCORSWITCH.LNK1")
#! Field("MGNT:IN10:1:XCORSWITCH.FLNK",16777215,1,"MGNT:IN10:1:XCORSWITCH.FLNK")
#! Record("MGNT:IN10:1:ALLXCORSGO",240,96,0,0,"MGNT:IN10:1:ALLXCORSGO")
#! Field("MGNT:IN10:1:ALLXCORSGO.DOL1",16777215,1,"MGNT:IN10:1:ALLXCORSGO.DOL1")
#! Field("MGNT:IN10:1:ALLXCORSGO.LNK1",16777215,1,"MGNT:IN10:1:ALLXCORSGO.LNK1")
#! Link("MGNT:IN10:1:ALLXCORSGO.LNK1","MGNT:IN10:1:ALLXCORS.VAL")
#! Record("MGNT:IN10:1:ALLXCORS",540,102,0,0,"MGNT:IN10:1:ALLXCORS")
#! Field("MGNT:IN10:1:ALLXCORS.VAL",16777215,0,"MGNT:IN10:1:ALLXCORS.VAL")
#! Field("MGNT:IN10:1:ALLXCORS.FLNK",16777215,1,"MGNT:IN10:1:ALLXCORS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:YCORCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_YCOR so that it can be
# used properly by the the PV <device>:YCORSWITCH

record(mbbo, "MGNT:IN10:1:YCORCTRL") {
  field(DESC, "All YCOR Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "7")
  field(FLNK, "MGNT:IN10:1:YCORSWITCH")
}

record(seq, "MGNT:IN10:1:YCORSWITCH") {
  field(DOL1, "MGNT:IN10:1:YCORCTRL.FFVL")
  field(LNK1, "MGNT:IN10:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:IN10:1:YCORFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:IN10:1:YCORCTRL")
}

record(seq, "MGNT:IN10:1:ALLYCORSGO") {
  field(DOL1, "MGNT:IN10:1:ALLSTAR")
  field(LNK1, "MGNT:IN10:1:ALLYCORS PP NMS")
}

record(bo, "MGNT:IN10:1:ALLYCORS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:IN10:1:ALLYCORSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:IN10:1:YCORCTRL",20,10,0,0,"MGNT:IN10:1:YCORCTRL")
#! Field("MGNT:IN10:1:YCORCTRL.FLNK",16777215,1,"MGNT:IN10:1:YCORCTRL.FLNK")
#! Link("MGNT:IN10:1:YCORCTRL.FLNK","MGNT:IN10:1:YCORSWITCH")
#! Field("MGNT:IN10:1:YCORCTRL.FFVL",16777215,1,"MGNT:IN10:1:YCORCTRL.FFVL")
#! Record("MGNT:IN10:1:YCORSWITCH",460,322,0,0,"MGNT:IN10:1:YCORSWITCH")
#! Field("MGNT:IN10:1:YCORSWITCH.DOL1",16777215,0,"MGNT:IN10:1:YCORSWITCH.DOL1")
#! Link("MGNT:IN10:1:YCORSWITCH.DOL1","MGNT:IN10:1:YCORCTRL.FFVL")
#! Field("MGNT:IN10:1:YCORSWITCH.LNK1",16777215,1,"MGNT:IN10:1:YCORSWITCH.LNK1")
#! Field("MGNT:IN10:1:YCORSWITCH.FLNK",16777215,1,"MGNT:IN10:1:YCORSWITCH.FLNK")
#! Record("MGNT:IN10:1:ALLYCORSGO",240,96,0,0,"MGNT:IN10:1:ALLYCORSGO")
#! Field("MGNT:IN10:1:ALLYCORSGO.DOL1",16777215,1,"MGNT:IN10:1:ALLYCORSGO.DOL1")
#! Field("MGNT:IN10:1:ALLYCORSGO.LNK1",16777215,1,"MGNT:IN10:1:ALLYCORSGO.LNK1")
#! Link("MGNT:IN10:1:ALLYCORSGO.LNK1","MGNT:IN10:1:ALLYCORS.VAL")
#! Record("MGNT:IN10:1:ALLYCORS",540,102,0,0,"MGNT:IN10:1:ALLYCORS")
#! Field("MGNT:IN10:1:ALLYCORS.VAL",16777215,0,"MGNT:IN10:1:ALLYCORS.VAL")
#! Field("MGNT:IN10:1:ALLYCORS.FLNK",16777215,1,"MGNT:IN10:1:ALLYCORS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:SOLNCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_SOLN so that it can be
# used properly by the the PV <device>:SOLNSWITCH

record(mbbo, "MGNT:IN10:1:SOLNCTRL") {
  field(DESC, "All SOLN Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "8")
  field(FLNK, "MGNT:IN10:1:SOLNSWITCH")
}

record(seq, "MGNT:IN10:1:SOLNSWITCH") {
  field(DOL1, "MGNT:IN10:1:SOLNCTRL.FFVL")
  field(LNK1, "MGNT:IN10:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:IN10:1:SOLNFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:IN10:1:SOLNCTRL")
}

record(seq, "MGNT:IN10:1:ALLSOLNSGO") {
  field(DOL1, "MGNT:IN10:1:ALLSTAR")
  field(LNK1, "MGNT:IN10:1:ALLSOLNS PP NMS")
}

record(bo, "MGNT:IN10:1:ALLSOLNS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:IN10:1:ALLSOLNSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:IN10:1:SOLNCTRL",20,10,0,0,"MGNT:IN10:1:SOLNCTRL")
#! Field("MGNT:IN10:1:SOLNCTRL.FLNK",16777215,1,"MGNT:IN10:1:SOLNCTRL.FLNK")
#! Link("MGNT:IN10:1:SOLNCTRL.FLNK","MGNT:IN10:1:SOLNSWITCH")
#! Field("MGNT:IN10:1:SOLNCTRL.FFVL",16777215,1,"MGNT:IN10:1:SOLNCTRL.FFVL")
#! Record("MGNT:IN10:1:SOLNSWITCH",460,322,0,0,"MGNT:IN10:1:SOLNSWITCH")
#! Field("MGNT:IN10:1:SOLNSWITCH.DOL1",16777215,0,"MGNT:IN10:1:SOLNSWITCH.DOL1")
#! Link("MGNT:IN10:1:SOLNSWITCH.DOL1","MGNT:IN10:1:SOLNCTRL.FFVL")
#! Field("MGNT:IN10:1:SOLNSWITCH.LNK1",16777215,1,"MGNT:IN10:1:SOLNSWITCH.LNK1")
#! Field("MGNT:IN10:1:SOLNSWITCH.FLNK",16777215,1,"MGNT:IN10:1:SOLNSWITCH.FLNK")
#! Record("MGNT:IN10:1:ALLSOLNSGO",240,96,0,0,"MGNT:IN10:1:ALLSOLNSGO")
#! Field("MGNT:IN10:1:ALLSOLNSGO.DOL1",16777215,1,"MGNT:IN10:1:ALLSOLNSGO.DOL1")
#! Field("MGNT:IN10:1:ALLSOLNSGO.LNK1",16777215,1,"MGNT:IN10:1:ALLSOLNSGO.LNK1")
#! Link("MGNT:IN10:1:ALLSOLNSGO.LNK1","MGNT:IN10:1:ALLSOLNS.VAL")
#! Record("MGNT:IN10:1:ALLSOLNS",540,102,0,0,"MGNT:IN10:1:ALLSOLNS")
#! Field("MGNT:IN10:1:ALLSOLNS.VAL",16777215,0,"MGNT:IN10:1:ALLSOLNS.VAL")
#! Field("MGNT:IN10:1:ALLSOLNS.FLNK",16777215,1,"MGNT:IN10:1:ALLSOLNS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:KICKCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_KICK so that it can be
# used properly by the the PV <device>:KICKSWITCH

record(mbbo, "MGNT:IN10:1:KICKCTRL") {
  field(DESC, "All KICK Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "9")
  field(FLNK, "MGNT:IN10:1:KICKSWITCH")
}

record(seq, "MGNT:IN10:1:KICKSWITCH") {
  field(DOL1, "MGNT:IN10:1:KICKCTRL.FFVL")
  field(LNK1, "MGNT:IN10:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:IN10:1:KICKFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:IN10:1:KICKCTRL")
}

record(seq, "MGNT:IN10:1:ALLKICKSGO") {
  field(DOL1, "MGNT:IN10:1:ALLSTAR")
  field(LNK1, "MGNT:IN10:1:ALLKICKS PP NMS")
}

record(bo, "MGNT:IN10:1:ALLKICKS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:IN10:1:ALLKICKSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:IN10:1:KICKCTRL",20,10,0,0,"MGNT:IN10:1:KICKCTRL")
#! Field("MGNT:IN10:1:KICKCTRL.FLNK",16777215,1,"MGNT:IN10:1:KICKCTRL.FLNK")
#! Link("MGNT:IN10:1:KICKCTRL.FLNK","MGNT:IN10:1:KICKSWITCH")
#! Field("MGNT:IN10:1:KICKCTRL.FFVL",16777215,1,"MGNT:IN10:1:KICKCTRL.FFVL")
#! Record("MGNT:IN10:1:KICKSWITCH",460,322,0,0,"MGNT:IN10:1:KICKSWITCH")
#! Field("MGNT:IN10:1:KICKSWITCH.DOL1",16777215,0,"MGNT:IN10:1:KICKSWITCH.DOL1")
#! Link("MGNT:IN10:1:KICKSWITCH.DOL1","MGNT:IN10:1:KICKCTRL.FFVL")
#! Field("MGNT:IN10:1:KICKSWITCH.LNK1",16777215,1,"MGNT:IN10:1:KICKSWITCH.LNK1")
#! Field("MGNT:IN10:1:KICKSWITCH.FLNK",16777215,1,"MGNT:IN10:1:KICKSWITCH.FLNK")
#! Record("MGNT:IN10:1:ALLKICKSGO",240,96,0,0,"MGNT:IN10:1:ALLKICKSGO")
#! Field("MGNT:IN10:1:ALLKICKSGO.DOL1",16777215,1,"MGNT:IN10:1:ALLKICKSGO.DOL1")
#! Field("MGNT:IN10:1:ALLKICKSGO.LNK1",16777215,1,"MGNT:IN10:1:ALLKICKSGO.LNK1")
#! Link("MGNT:IN10:1:ALLKICKSGO.LNK1","MGNT:IN10:1:ALLKICKS.VAL")
#! Record("MGNT:IN10:1:ALLKICKS",540,102,0,0,"MGNT:IN10:1:ALLKICKS")
#! Field("MGNT:IN10:1:ALLKICKS.VAL",16777215,0,"MGNT:IN10:1:ALLKICKS.VAL")
#! Field("MGNT:IN10:1:ALLKICKS.FLNK",16777215,1,"MGNT:IN10:1:ALLKICKS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:SEXTCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_SEXT so that it can be
# used properly by the the PV <device>:SEXTSWITCH

record(mbbo, "MGNT:IN10:1:SEXTCTRL") {
  field(DESC, "All SEXT Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "10")
  field(FLNK, "MGNT:IN10:1:SEXTSWITCH")
}

record(seq, "MGNT:IN10:1:SEXTSWITCH") {
  field(DOL1, "MGNT:IN10:1:SEXTCTRL.FFVL")
  field(LNK1, "MGNT:IN10:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:IN10:1:SEXTFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:IN10:1:SEXTCTRL")
}

record(seq, "MGNT:IN10:1:ALLSEXTSGO") {
  field(DOL1, "MGNT:IN10:1:ALLSTAR")
  field(LNK1, "MGNT:IN10:1:ALLSEXTS PP NMS")
}

record(bo, "MGNT:IN10:1:ALLSEXTS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:IN10:1:ALLSEXTSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:IN10:1:SEXTCTRL",20,10,0,0,"MGNT:IN10:1:SEXTCTRL")
#! Field("MGNT:IN10:1:SEXTCTRL.FLNK",16777215,1,"MGNT:IN10:1:SEXTCTRL.FLNK")
#! Link("MGNT:IN10:1:SEXTCTRL.FLNK","MGNT:IN10:1:SEXTSWITCH")
#! Field("MGNT:IN10:1:SEXTCTRL.FFVL",16777215,1,"MGNT:IN10:1:SEXTCTRL.FFVL")
#! Record("MGNT:IN10:1:SEXTSWITCH",460,322,0,0,"MGNT:IN10:1:SEXTSWITCH")
#! Field("MGNT:IN10:1:SEXTSWITCH.DOL1",16777215,0,"MGNT:IN10:1:SEXTSWITCH.DOL1")
#! Link("MGNT:IN10:1:SEXTSWITCH.DOL1","MGNT:IN10:1:SEXTCTRL.FFVL")
#! Field("MGNT:IN10:1:SEXTSWITCH.LNK1",16777215,1,"MGNT:IN10:1:SEXTSWITCH.LNK1")
#! Field("MGNT:IN10:1:SEXTSWITCH.FLNK",16777215,1,"MGNT:IN10:1:SEXTSWITCH.FLNK")
#! Record("MGNT:IN10:1:ALLSEXTSGO",240,96,0,0,"MGNT:IN10:1:ALLSEXTSGO")
#! Field("MGNT:IN10:1:ALLSEXTSGO.DOL1",16777215,1,"MGNT:IN10:1:ALLSEXTSGO.DOL1")
#! Field("MGNT:IN10:1:ALLSEXTSGO.LNK1",16777215,1,"MGNT:IN10:1:ALLSEXTSGO.LNK1")
#! Link("MGNT:IN10:1:ALLSEXTSGO.LNK1","MGNT:IN10:1:ALLSEXTS.VAL")
#! Record("MGNT:IN10:1:ALLSEXTS",540,102,0,0,"MGNT:IN10:1:ALLSEXTS")
#! Field("MGNT:IN10:1:ALLSEXTS.VAL",16777215,0,"MGNT:IN10:1:ALLSEXTS.VAL")
#! Field("MGNT:IN10:1:ALLSEXTS.FLNK",16777215,1,"MGNT:IN10:1:ALLSEXTS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(longout, "MGNT:LI11:1:CTRLSWITCH") {
}

# The LNK# (1-8) MUST corresponsds to the magent
# type definition found in the file mgntCtrl.h.
# For example, MGNT_TYPE_BEND is defined as 2 and is LNK2 below.
# If the LNK order is changes you will need to make the
# corresponding change the pv <device>:<type>CTRL which is
# found in the files mgnt_ctrl_allstar.substitutions
# The field FFVL value in MGNT:<LOCA>:1: CTRLCLEAR MUST be set
# to the value for MGNT_TYPE_ALL which is defined as 1 in mgntCtrl.h
# so that it can be used properly by the the PV  MGNT:LI21:1:ALLSWITCH
#
record(seq, "MGNT:LI11:1:CTRLCLEAR") {
  field(DESC, "All function go")
  field(DOL1, "0")
  field(DOL2, "0")
  field(DOL3, "0")
  field(DOL4, "0")
  field(DOL5, "0")
  field(DOL6, "0")
  field(DOL7, "0")
  field(DOL8, "0")
  field(DOL9, "0")
  field(DOLA, "0")
  field(LNK1, "MGNT:LI11:1:CTRL CA PP")
  field(LNK2, "MGNT:LI11:1:BENDCTRL CA PP")
  field(LNK3, "MGNT:LI11:1:BTRMCTRL CA PP")
  field(LNK4, "MGNT:LI11:1:LGPSCTRL CA PP")
  field(LNK5, "MGNT:LI11:1:QUADCTRL CA PP")
  field(LNK6, "MGNT:LI11:1:XCORCTRL CA PP")
  field(LNK7, "MGNT:LI11:1:YCORCTRL CA PP")
  field(LNK8, "MGNT:LI11:1:SOLNCTRL CA PP")
  field(LNK9, "MGNT:LI11:1:KICKCTRL CA PP")
  field(LNKA, "MGNT:LI11:1:SEXTCTRL CA PP")
}

record(mbbo, "MGNT:LI11:1:CTRL") {
  field(DESC, "All Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "1")
  field(FLNK, "MGNT:LI11:1:ALLSWITCH")
}

record(seq, "MGNT:LI11:1:ALLSWITCH") {
  field(DOL1, "MGNT:LI11:1:CTRL.FFVL")
  field(LNK1, "MGNT:LI11:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:LI11:1:ALLFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:LI11:1:CTRL")
}

record(bo, "MGNT:LI11:1:ALLSTAR") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(PINI, "YES")
  field(FLNK, "MGNT:LI11:1:ALLSTARGO")
}

record(fanout, "MGNT:LI11:1:ALLSTARGO") {
  field(LNK1, "MGNT:LI11:1:ALLBENDSGO")
  field(LNK2, "MGNT:LI11:1:ALLBTRMSGO")
  field(LNK3, "MGNT:LI11:1:ALLLGPSSGO")
  field(LNK4, "MGNT:LI11:1:ALLQUADSGO")
  field(LNK5, "MGNT:LI11:1:ALLXCORSGO")
  field(LNK6, "MGNT:LI11:1:ALLYCORSGO")
  field(FLNK, "MGNT:LI11:1:ALLSTARGO_2")
}
record(fanout, "MGNT:LI11:1:ALLSTARGO_2") {
  field(LNK1, "MGNT:LI11:1:ALLSOLNSGO")
  field(LNK2, "MGNT:LI11:1:ALLKICKSGO")
  field(LNK3, "MGNT:LI11:1:ALLSEXTSGO")
}

#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:BENDCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_BEND so that it can be
# used properly by the the PV <device>:BENDSWITCH

record(mbbo, "MGNT:LI11:1:BENDCTRL") {
  field(DESC, "All BEND Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "2")
  field(FLNK, "MGNT:LI11:1:BENDSWITCH")
}

record(seq, "MGNT:LI11:1:BENDSWITCH") {
  field(DOL1, "MGNT:LI11:1:BENDCTRL.FFVL")
  field(LNK1, "MGNT:LI11:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:LI11:1:BENDFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:LI11:1:BENDCTRL")
}

record(seq, "MGNT:LI11:1:ALLBENDSGO") {
  field(DOL1, "MGNT:LI11:1:ALLSTAR")
  field(LNK1, "MGNT:LI11:1:ALLBENDS PP NMS")
}

record(bo, "MGNT:LI11:1:ALLBENDS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:LI11:1:ALLBENDSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:LI11:1:BENDCTRL",20,10,0,0,"MGNT:LI11:1:BENDCTRL")
#! Field("MGNT:LI11:1:BENDCTRL.FLNK",16777215,1,"MGNT:LI11:1:BENDCTRL.FLNK")
#! Link("MGNT:LI11:1:BENDCTRL.FLNK","MGNT:LI11:1:BENDSWITCH")
#! Field("MGNT:LI11:1:BENDCTRL.FFVL",16777215,1,"MGNT:LI11:1:BENDCTRL.FFVL")
#! Record("MGNT:LI11:1:BENDSWITCH",460,322,0,0,"MGNT:LI11:1:BENDSWITCH")
#! Field("MGNT:LI11:1:BENDSWITCH.DOL1",16777215,0,"MGNT:LI11:1:BENDSWITCH.DOL1")
#! Link("MGNT:LI11:1:BENDSWITCH.DOL1","MGNT:LI11:1:BENDCTRL.FFVL")
#! Field("MGNT:LI11:1:BENDSWITCH.LNK1",16777215,1,"MGNT:LI11:1:BENDSWITCH.LNK1")
#! Field("MGNT:LI11:1:BENDSWITCH.FLNK",16777215,1,"MGNT:LI11:1:BENDSWITCH.FLNK")
#! Record("MGNT:LI11:1:ALLBENDSGO",240,96,0,0,"MGNT:LI11:1:ALLBENDSGO")
#! Field("MGNT:LI11:1:ALLBENDSGO.DOL1",16777215,1,"MGNT:LI11:1:ALLBENDSGO.DOL1")
#! Field("MGNT:LI11:1:ALLBENDSGO.LNK1",16777215,1,"MGNT:LI11:1:ALLBENDSGO.LNK1")
#! Link("MGNT:LI11:1:ALLBENDSGO.LNK1","MGNT:LI11:1:ALLBENDS.VAL")
#! Record("MGNT:LI11:1:ALLBENDS",540,102,0,0,"MGNT:LI11:1:ALLBENDS")
#! Field("MGNT:LI11:1:ALLBENDS.VAL",16777215,0,"MGNT:LI11:1:ALLBENDS.VAL")
#! Field("MGNT:LI11:1:ALLBENDS.FLNK",16777215,1,"MGNT:LI11:1:ALLBENDS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:BTRMCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_BTRM so that it can be
# used properly by the the PV <device>:BTRMSWITCH

record(mbbo, "MGNT:LI11:1:BTRMCTRL") {
  field(DESC, "All BTRM Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "3")
  field(FLNK, "MGNT:LI11:1:BTRMSWITCH")
}

record(seq, "MGNT:LI11:1:BTRMSWITCH") {
  field(DOL1, "MGNT:LI11:1:BTRMCTRL.FFVL")
  field(LNK1, "MGNT:LI11:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:LI11:1:BTRMFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:LI11:1:BTRMCTRL")
}

record(seq, "MGNT:LI11:1:ALLBTRMSGO") {
  field(DOL1, "MGNT:LI11:1:ALLSTAR")
  field(LNK1, "MGNT:LI11:1:ALLBTRMS PP NMS")
}

record(bo, "MGNT:LI11:1:ALLBTRMS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:LI11:1:ALLBTRMSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:LI11:1:BTRMCTRL",20,10,0,0,"MGNT:LI11:1:BTRMCTRL")
#! Field("MGNT:LI11:1:BTRMCTRL.FLNK",16777215,1,"MGNT:LI11:1:BTRMCTRL.FLNK")
#! Link("MGNT:LI11:1:BTRMCTRL.FLNK","MGNT:LI11:1:BTRMSWITCH")
#! Field("MGNT:LI11:1:BTRMCTRL.FFVL",16777215,1,"MGNT:LI11:1:BTRMCTRL.FFVL")
#! Record("MGNT:LI11:1:BTRMSWITCH",460,322,0,0,"MGNT:LI11:1:BTRMSWITCH")
#! Field("MGNT:LI11:1:BTRMSWITCH.DOL1",16777215,0,"MGNT:LI11:1:BTRMSWITCH.DOL1")
#! Link("MGNT:LI11:1:BTRMSWITCH.DOL1","MGNT:LI11:1:BTRMCTRL.FFVL")
#! Field("MGNT:LI11:1:BTRMSWITCH.LNK1",16777215,1,"MGNT:LI11:1:BTRMSWITCH.LNK1")
#! Field("MGNT:LI11:1:BTRMSWITCH.FLNK",16777215,1,"MGNT:LI11:1:BTRMSWITCH.FLNK")
#! Record("MGNT:LI11:1:ALLBTRMSGO",240,96,0,0,"MGNT:LI11:1:ALLBTRMSGO")
#! Field("MGNT:LI11:1:ALLBTRMSGO.DOL1",16777215,1,"MGNT:LI11:1:ALLBTRMSGO.DOL1")
#! Field("MGNT:LI11:1:ALLBTRMSGO.LNK1",16777215,1,"MGNT:LI11:1:ALLBTRMSGO.LNK1")
#! Link("MGNT:LI11:1:ALLBTRMSGO.LNK1","MGNT:LI11:1:ALLBTRMS.VAL")
#! Record("MGNT:LI11:1:ALLBTRMS",540,102,0,0,"MGNT:LI11:1:ALLBTRMS")
#! Field("MGNT:LI11:1:ALLBTRMS.VAL",16777215,0,"MGNT:LI11:1:ALLBTRMS.VAL")
#! Field("MGNT:LI11:1:ALLBTRMS.FLNK",16777215,1,"MGNT:LI11:1:ALLBTRMS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:LGPSCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_LGPS so that it can be
# used properly by the the PV <device>:LGPSSWITCH

record(mbbo, "MGNT:LI11:1:LGPSCTRL") {
  field(DESC, "All LGPS Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "3")
  field(FLNK, "MGNT:LI11:1:LGPSSWITCH")
}

record(seq, "MGNT:LI11:1:LGPSSWITCH") {
  field(DOL1, "MGNT:LI11:1:LGPSCTRL.FFVL")
  field(LNK1, "MGNT:LI11:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:LI11:1:LGPSFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:LI11:1:LGPSCTRL")
}

record(seq, "MGNT:LI11:1:ALLLGPSSGO") {
  field(DOL1, "MGNT:LI11:1:ALLSTAR")
  field(LNK1, "MGNT:LI11:1:ALLLGPSS PP NMS")
}

record(bo, "MGNT:LI11:1:ALLLGPSS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:LI11:1:ALLLGPSSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:LI11:1:LGPSCTRL",20,10,0,0,"MGNT:LI11:1:LGPSCTRL")
#! Field("MGNT:LI11:1:LGPSCTRL.FLNK",16777215,1,"MGNT:LI11:1:LGPSCTRL.FLNK")
#! Link("MGNT:LI11:1:LGPSCTRL.FLNK","MGNT:LI11:1:LGPSSWITCH")
#! Field("MGNT:LI11:1:LGPSCTRL.FFVL",16777215,1,"MGNT:LI11:1:LGPSCTRL.FFVL")
#! Record("MGNT:LI11:1:LGPSSWITCH",460,322,0,0,"MGNT:LI11:1:LGPSSWITCH")
#! Field("MGNT:LI11:1:LGPSSWITCH.DOL1",16777215,0,"MGNT:LI11:1:LGPSSWITCH.DOL1")
#! Link("MGNT:LI11:1:LGPSSWITCH.DOL1","MGNT:LI11:1:LGPSCTRL.FFVL")
#! Field("MGNT:LI11:1:LGPSSWITCH.LNK1",16777215,1,"MGNT:LI11:1:LGPSSWITCH.LNK1")
#! Field("MGNT:LI11:1:LGPSSWITCH.FLNK",16777215,1,"MGNT:LI11:1:LGPSSWITCH.FLNK")
#! Record("MGNT:LI11:1:ALLLGPSSGO",240,96,0,0,"MGNT:LI11:1:ALLLGPSSGO")
#! Field("MGNT:LI11:1:ALLLGPSSGO.DOL1",16777215,1,"MGNT:LI11:1:ALLLGPSSGO.DOL1")
#! Field("MGNT:LI11:1:ALLLGPSSGO.LNK1",16777215,1,"MGNT:LI11:1:ALLLGPSSGO.LNK1")
#! Link("MGNT:LI11:1:ALLLGPSSGO.LNK1","MGNT:LI11:1:ALLLGPSS.VAL")
#! Record("MGNT:LI11:1:ALLLGPSS",540,102,0,0,"MGNT:LI11:1:ALLLGPSS")
#! Field("MGNT:LI11:1:ALLLGPSS.VAL",16777215,0,"MGNT:LI11:1:ALLLGPSS.VAL")
#! Field("MGNT:LI11:1:ALLLGPSS.FLNK",16777215,1,"MGNT:LI11:1:ALLLGPSS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:QUADCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_QUAD so that it can be
# used properly by the the PV <device>:QUADSWITCH

record(mbbo, "MGNT:LI11:1:QUADCTRL") {
  field(DESC, "All QUAD Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "5")
  field(FLNK, "MGNT:LI11:1:QUADSWITCH")
}

record(seq, "MGNT:LI11:1:QUADSWITCH") {
  field(DOL1, "MGNT:LI11:1:QUADCTRL.FFVL")
  field(LNK1, "MGNT:LI11:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:LI11:1:QUADFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:LI11:1:QUADCTRL")
}

record(seq, "MGNT:LI11:1:ALLQUADSGO") {
  field(DOL1, "MGNT:LI11:1:ALLSTAR")
  field(LNK1, "MGNT:LI11:1:ALLQUADS PP NMS")
}

record(bo, "MGNT:LI11:1:ALLQUADS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:LI11:1:ALLQUADSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:LI11:1:QUADCTRL",20,10,0,0,"MGNT:LI11:1:QUADCTRL")
#! Field("MGNT:LI11:1:QUADCTRL.FLNK",16777215,1,"MGNT:LI11:1:QUADCTRL.FLNK")
#! Link("MGNT:LI11:1:QUADCTRL.FLNK","MGNT:LI11:1:QUADSWITCH")
#! Field("MGNT:LI11:1:QUADCTRL.FFVL",16777215,1,"MGNT:LI11:1:QUADCTRL.FFVL")
#! Record("MGNT:LI11:1:QUADSWITCH",460,322,0,0,"MGNT:LI11:1:QUADSWITCH")
#! Field("MGNT:LI11:1:QUADSWITCH.DOL1",16777215,0,"MGNT:LI11:1:QUADSWITCH.DOL1")
#! Link("MGNT:LI11:1:QUADSWITCH.DOL1","MGNT:LI11:1:QUADCTRL.FFVL")
#! Field("MGNT:LI11:1:QUADSWITCH.LNK1",16777215,1,"MGNT:LI11:1:QUADSWITCH.LNK1")
#! Field("MGNT:LI11:1:QUADSWITCH.FLNK",16777215,1,"MGNT:LI11:1:QUADSWITCH.FLNK")
#! Record("MGNT:LI11:1:ALLQUADSGO",240,96,0,0,"MGNT:LI11:1:ALLQUADSGO")
#! Field("MGNT:LI11:1:ALLQUADSGO.DOL1",16777215,1,"MGNT:LI11:1:ALLQUADSGO.DOL1")
#! Field("MGNT:LI11:1:ALLQUADSGO.LNK1",16777215,1,"MGNT:LI11:1:ALLQUADSGO.LNK1")
#! Link("MGNT:LI11:1:ALLQUADSGO.LNK1","MGNT:LI11:1:ALLQUADS.VAL")
#! Record("MGNT:LI11:1:ALLQUADS",540,102,0,0,"MGNT:LI11:1:ALLQUADS")
#! Field("MGNT:LI11:1:ALLQUADS.VAL",16777215,0,"MGNT:LI11:1:ALLQUADS.VAL")
#! Field("MGNT:LI11:1:ALLQUADS.FLNK",16777215,1,"MGNT:LI11:1:ALLQUADS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:XCORCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_XCOR so that it can be
# used properly by the the PV <device>:XCORSWITCH

record(mbbo, "MGNT:LI11:1:XCORCTRL") {
  field(DESC, "All XCOR Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "6")
  field(FLNK, "MGNT:LI11:1:XCORSWITCH")
}

record(seq, "MGNT:LI11:1:XCORSWITCH") {
  field(DOL1, "MGNT:LI11:1:XCORCTRL.FFVL")
  field(LNK1, "MGNT:LI11:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:LI11:1:XCORFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:LI11:1:XCORCTRL")
}

record(seq, "MGNT:LI11:1:ALLXCORSGO") {
  field(DOL1, "MGNT:LI11:1:ALLSTAR")
  field(LNK1, "MGNT:LI11:1:ALLXCORS PP NMS")
}

record(bo, "MGNT:LI11:1:ALLXCORS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:LI11:1:ALLXCORSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:LI11:1:XCORCTRL",20,10,0,0,"MGNT:LI11:1:XCORCTRL")
#! Field("MGNT:LI11:1:XCORCTRL.FLNK",16777215,1,"MGNT:LI11:1:XCORCTRL.FLNK")
#! Link("MGNT:LI11:1:XCORCTRL.FLNK","MGNT:LI11:1:XCORSWITCH")
#! Field("MGNT:LI11:1:XCORCTRL.FFVL",16777215,1,"MGNT:LI11:1:XCORCTRL.FFVL")
#! Record("MGNT:LI11:1:XCORSWITCH",460,322,0,0,"MGNT:LI11:1:XCORSWITCH")
#! Field("MGNT:LI11:1:XCORSWITCH.DOL1",16777215,0,"MGNT:LI11:1:XCORSWITCH.DOL1")
#! Link("MGNT:LI11:1:XCORSWITCH.DOL1","MGNT:LI11:1:XCORCTRL.FFVL")
#! Field("MGNT:LI11:1:XCORSWITCH.LNK1",16777215,1,"MGNT:LI11:1:XCORSWITCH.LNK1")
#! Field("MGNT:LI11:1:XCORSWITCH.FLNK",16777215,1,"MGNT:LI11:1:XCORSWITCH.FLNK")
#! Record("MGNT:LI11:1:ALLXCORSGO",240,96,0,0,"MGNT:LI11:1:ALLXCORSGO")
#! Field("MGNT:LI11:1:ALLXCORSGO.DOL1",16777215,1,"MGNT:LI11:1:ALLXCORSGO.DOL1")
#! Field("MGNT:LI11:1:ALLXCORSGO.LNK1",16777215,1,"MGNT:LI11:1:ALLXCORSGO.LNK1")
#! Link("MGNT:LI11:1:ALLXCORSGO.LNK1","MGNT:LI11:1:ALLXCORS.VAL")
#! Record("MGNT:LI11:1:ALLXCORS",540,102,0,0,"MGNT:LI11:1:ALLXCORS")
#! Field("MGNT:LI11:1:ALLXCORS.VAL",16777215,0,"MGNT:LI11:1:ALLXCORS.VAL")
#! Field("MGNT:LI11:1:ALLXCORS.FLNK",16777215,1,"MGNT:LI11:1:ALLXCORS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:YCORCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_YCOR so that it can be
# used properly by the the PV <device>:YCORSWITCH

record(mbbo, "MGNT:LI11:1:YCORCTRL") {
  field(DESC, "All YCOR Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "7")
  field(FLNK, "MGNT:LI11:1:YCORSWITCH")
}

record(seq, "MGNT:LI11:1:YCORSWITCH") {
  field(DOL1, "MGNT:LI11:1:YCORCTRL.FFVL")
  field(LNK1, "MGNT:LI11:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:LI11:1:YCORFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:LI11:1:YCORCTRL")
}

record(seq, "MGNT:LI11:1:ALLYCORSGO") {
  field(DOL1, "MGNT:LI11:1:ALLSTAR")
  field(LNK1, "MGNT:LI11:1:ALLYCORS PP NMS")
}

record(bo, "MGNT:LI11:1:ALLYCORS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:LI11:1:ALLYCORSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:LI11:1:YCORCTRL",20,10,0,0,"MGNT:LI11:1:YCORCTRL")
#! Field("MGNT:LI11:1:YCORCTRL.FLNK",16777215,1,"MGNT:LI11:1:YCORCTRL.FLNK")
#! Link("MGNT:LI11:1:YCORCTRL.FLNK","MGNT:LI11:1:YCORSWITCH")
#! Field("MGNT:LI11:1:YCORCTRL.FFVL",16777215,1,"MGNT:LI11:1:YCORCTRL.FFVL")
#! Record("MGNT:LI11:1:YCORSWITCH",460,322,0,0,"MGNT:LI11:1:YCORSWITCH")
#! Field("MGNT:LI11:1:YCORSWITCH.DOL1",16777215,0,"MGNT:LI11:1:YCORSWITCH.DOL1")
#! Link("MGNT:LI11:1:YCORSWITCH.DOL1","MGNT:LI11:1:YCORCTRL.FFVL")
#! Field("MGNT:LI11:1:YCORSWITCH.LNK1",16777215,1,"MGNT:LI11:1:YCORSWITCH.LNK1")
#! Field("MGNT:LI11:1:YCORSWITCH.FLNK",16777215,1,"MGNT:LI11:1:YCORSWITCH.FLNK")
#! Record("MGNT:LI11:1:ALLYCORSGO",240,96,0,0,"MGNT:LI11:1:ALLYCORSGO")
#! Field("MGNT:LI11:1:ALLYCORSGO.DOL1",16777215,1,"MGNT:LI11:1:ALLYCORSGO.DOL1")
#! Field("MGNT:LI11:1:ALLYCORSGO.LNK1",16777215,1,"MGNT:LI11:1:ALLYCORSGO.LNK1")
#! Link("MGNT:LI11:1:ALLYCORSGO.LNK1","MGNT:LI11:1:ALLYCORS.VAL")
#! Record("MGNT:LI11:1:ALLYCORS",540,102,0,0,"MGNT:LI11:1:ALLYCORS")
#! Field("MGNT:LI11:1:ALLYCORS.VAL",16777215,0,"MGNT:LI11:1:ALLYCORS.VAL")
#! Field("MGNT:LI11:1:ALLYCORS.FLNK",16777215,1,"MGNT:LI11:1:ALLYCORS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:SOLNCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_SOLN so that it can be
# used properly by the the PV <device>:SOLNSWITCH

record(mbbo, "MGNT:LI11:1:SOLNCTRL") {
  field(DESC, "All SOLN Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "8")
  field(FLNK, "MGNT:LI11:1:SOLNSWITCH")
}

record(seq, "MGNT:LI11:1:SOLNSWITCH") {
  field(DOL1, "MGNT:LI11:1:SOLNCTRL.FFVL")
  field(LNK1, "MGNT:LI11:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:LI11:1:SOLNFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:LI11:1:SOLNCTRL")
}

record(seq, "MGNT:LI11:1:ALLSOLNSGO") {
  field(DOL1, "MGNT:LI11:1:ALLSTAR")
  field(LNK1, "MGNT:LI11:1:ALLSOLNS PP NMS")
}

record(bo, "MGNT:LI11:1:ALLSOLNS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:LI11:1:ALLSOLNSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:LI11:1:SOLNCTRL",20,10,0,0,"MGNT:LI11:1:SOLNCTRL")
#! Field("MGNT:LI11:1:SOLNCTRL.FLNK",16777215,1,"MGNT:LI11:1:SOLNCTRL.FLNK")
#! Link("MGNT:LI11:1:SOLNCTRL.FLNK","MGNT:LI11:1:SOLNSWITCH")
#! Field("MGNT:LI11:1:SOLNCTRL.FFVL",16777215,1,"MGNT:LI11:1:SOLNCTRL.FFVL")
#! Record("MGNT:LI11:1:SOLNSWITCH",460,322,0,0,"MGNT:LI11:1:SOLNSWITCH")
#! Field("MGNT:LI11:1:SOLNSWITCH.DOL1",16777215,0,"MGNT:LI11:1:SOLNSWITCH.DOL1")
#! Link("MGNT:LI11:1:SOLNSWITCH.DOL1","MGNT:LI11:1:SOLNCTRL.FFVL")
#! Field("MGNT:LI11:1:SOLNSWITCH.LNK1",16777215,1,"MGNT:LI11:1:SOLNSWITCH.LNK1")
#! Field("MGNT:LI11:1:SOLNSWITCH.FLNK",16777215,1,"MGNT:LI11:1:SOLNSWITCH.FLNK")
#! Record("MGNT:LI11:1:ALLSOLNSGO",240,96,0,0,"MGNT:LI11:1:ALLSOLNSGO")
#! Field("MGNT:LI11:1:ALLSOLNSGO.DOL1",16777215,1,"MGNT:LI11:1:ALLSOLNSGO.DOL1")
#! Field("MGNT:LI11:1:ALLSOLNSGO.LNK1",16777215,1,"MGNT:LI11:1:ALLSOLNSGO.LNK1")
#! Link("MGNT:LI11:1:ALLSOLNSGO.LNK1","MGNT:LI11:1:ALLSOLNS.VAL")
#! Record("MGNT:LI11:1:ALLSOLNS",540,102,0,0,"MGNT:LI11:1:ALLSOLNS")
#! Field("MGNT:LI11:1:ALLSOLNS.VAL",16777215,0,"MGNT:LI11:1:ALLSOLNS.VAL")
#! Field("MGNT:LI11:1:ALLSOLNS.FLNK",16777215,1,"MGNT:LI11:1:ALLSOLNS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:KICKCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_KICK so that it can be
# used properly by the the PV <device>:KICKSWITCH

record(mbbo, "MGNT:LI11:1:KICKCTRL") {
  field(DESC, "All KICK Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "9")
  field(FLNK, "MGNT:LI11:1:KICKSWITCH")
}

record(seq, "MGNT:LI11:1:KICKSWITCH") {
  field(DOL1, "MGNT:LI11:1:KICKCTRL.FFVL")
  field(LNK1, "MGNT:LI11:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:LI11:1:KICKFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:LI11:1:KICKCTRL")
}

record(seq, "MGNT:LI11:1:ALLKICKSGO") {
  field(DOL1, "MGNT:LI11:1:ALLSTAR")
  field(LNK1, "MGNT:LI11:1:ALLKICKS PP NMS")
}

record(bo, "MGNT:LI11:1:ALLKICKS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:LI11:1:ALLKICKSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:LI11:1:KICKCTRL",20,10,0,0,"MGNT:LI11:1:KICKCTRL")
#! Field("MGNT:LI11:1:KICKCTRL.FLNK",16777215,1,"MGNT:LI11:1:KICKCTRL.FLNK")
#! Link("MGNT:LI11:1:KICKCTRL.FLNK","MGNT:LI11:1:KICKSWITCH")
#! Field("MGNT:LI11:1:KICKCTRL.FFVL",16777215,1,"MGNT:LI11:1:KICKCTRL.FFVL")
#! Record("MGNT:LI11:1:KICKSWITCH",460,322,0,0,"MGNT:LI11:1:KICKSWITCH")
#! Field("MGNT:LI11:1:KICKSWITCH.DOL1",16777215,0,"MGNT:LI11:1:KICKSWITCH.DOL1")
#! Link("MGNT:LI11:1:KICKSWITCH.DOL1","MGNT:LI11:1:KICKCTRL.FFVL")
#! Field("MGNT:LI11:1:KICKSWITCH.LNK1",16777215,1,"MGNT:LI11:1:KICKSWITCH.LNK1")
#! Field("MGNT:LI11:1:KICKSWITCH.FLNK",16777215,1,"MGNT:LI11:1:KICKSWITCH.FLNK")
#! Record("MGNT:LI11:1:ALLKICKSGO",240,96,0,0,"MGNT:LI11:1:ALLKICKSGO")
#! Field("MGNT:LI11:1:ALLKICKSGO.DOL1",16777215,1,"MGNT:LI11:1:ALLKICKSGO.DOL1")
#! Field("MGNT:LI11:1:ALLKICKSGO.LNK1",16777215,1,"MGNT:LI11:1:ALLKICKSGO.LNK1")
#! Link("MGNT:LI11:1:ALLKICKSGO.LNK1","MGNT:LI11:1:ALLKICKS.VAL")
#! Record("MGNT:LI11:1:ALLKICKS",540,102,0,0,"MGNT:LI11:1:ALLKICKS")
#! Field("MGNT:LI11:1:ALLKICKS.VAL",16777215,0,"MGNT:LI11:1:ALLKICKS.VAL")
#! Field("MGNT:LI11:1:ALLKICKS.FLNK",16777215,1,"MGNT:LI11:1:ALLKICKS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:SEXTCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_SEXT so that it can be
# used properly by the the PV <device>:SEXTSWITCH

record(mbbo, "MGNT:LI11:1:SEXTCTRL") {
  field(DESC, "All SEXT Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "10")
  field(FLNK, "MGNT:LI11:1:SEXTSWITCH")
}

record(seq, "MGNT:LI11:1:SEXTSWITCH") {
  field(DOL1, "MGNT:LI11:1:SEXTCTRL.FFVL")
  field(LNK1, "MGNT:LI11:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:LI11:1:SEXTFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:LI11:1:SEXTCTRL")
}

record(seq, "MGNT:LI11:1:ALLSEXTSGO") {
  field(DOL1, "MGNT:LI11:1:ALLSTAR")
  field(LNK1, "MGNT:LI11:1:ALLSEXTS PP NMS")
}

record(bo, "MGNT:LI11:1:ALLSEXTS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:LI11:1:ALLSEXTSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:LI11:1:SEXTCTRL",20,10,0,0,"MGNT:LI11:1:SEXTCTRL")
#! Field("MGNT:LI11:1:SEXTCTRL.FLNK",16777215,1,"MGNT:LI11:1:SEXTCTRL.FLNK")
#! Link("MGNT:LI11:1:SEXTCTRL.FLNK","MGNT:LI11:1:SEXTSWITCH")
#! Field("MGNT:LI11:1:SEXTCTRL.FFVL",16777215,1,"MGNT:LI11:1:SEXTCTRL.FFVL")
#! Record("MGNT:LI11:1:SEXTSWITCH",460,322,0,0,"MGNT:LI11:1:SEXTSWITCH")
#! Field("MGNT:LI11:1:SEXTSWITCH.DOL1",16777215,0,"MGNT:LI11:1:SEXTSWITCH.DOL1")
#! Link("MGNT:LI11:1:SEXTSWITCH.DOL1","MGNT:LI11:1:SEXTCTRL.FFVL")
#! Field("MGNT:LI11:1:SEXTSWITCH.LNK1",16777215,1,"MGNT:LI11:1:SEXTSWITCH.LNK1")
#! Field("MGNT:LI11:1:SEXTSWITCH.FLNK",16777215,1,"MGNT:LI11:1:SEXTSWITCH.FLNK")
#! Record("MGNT:LI11:1:ALLSEXTSGO",240,96,0,0,"MGNT:LI11:1:ALLSEXTSGO")
#! Field("MGNT:LI11:1:ALLSEXTSGO.DOL1",16777215,1,"MGNT:LI11:1:ALLSEXTSGO.DOL1")
#! Field("MGNT:LI11:1:ALLSEXTSGO.LNK1",16777215,1,"MGNT:LI11:1:ALLSEXTSGO.LNK1")
#! Link("MGNT:LI11:1:ALLSEXTSGO.LNK1","MGNT:LI11:1:ALLSEXTS.VAL")
#! Record("MGNT:LI11:1:ALLSEXTS",540,102,0,0,"MGNT:LI11:1:ALLSEXTS")
#! Field("MGNT:LI11:1:ALLSEXTS.VAL",16777215,0,"MGNT:LI11:1:ALLSEXTS.VAL")
#! Field("MGNT:LI11:1:ALLSEXTS.FLNK",16777215,1,"MGNT:LI11:1:ALLSEXTS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(longout, "MGNT:LI14:1:CTRLSWITCH") {
}

# The LNK# (1-8) MUST corresponsds to the magent
# type definition found in the file mgntCtrl.h.
# For example, MGNT_TYPE_BEND is defined as 2 and is LNK2 below.
# If the LNK order is changes you will need to make the
# corresponding change the pv <device>:<type>CTRL which is
# found in the files mgnt_ctrl_allstar.substitutions
# The field FFVL value in MGNT:<LOCA>:1: CTRLCLEAR MUST be set
# to the value for MGNT_TYPE_ALL which is defined as 1 in mgntCtrl.h
# so that it can be used properly by the the PV  MGNT:LI21:1:ALLSWITCH
#
record(seq, "MGNT:LI14:1:CTRLCLEAR") {
  field(DESC, "All function go")
  field(DOL1, "0")
  field(DOL2, "0")
  field(DOL3, "0")
  field(DOL4, "0")
  field(DOL5, "0")
  field(DOL6, "0")
  field(DOL7, "0")
  field(DOL8, "0")
  field(DOL9, "0")
  field(DOLA, "0")
  field(LNK1, "MGNT:LI14:1:CTRL CA PP")
  field(LNK2, "MGNT:LI14:1:BENDCTRL CA PP")
  field(LNK3, "MGNT:LI14:1:BTRMCTRL CA PP")
  field(LNK4, "MGNT:LI14:1:LGPSCTRL CA PP")
  field(LNK5, "MGNT:LI14:1:QUADCTRL CA PP")
  field(LNK6, "MGNT:LI14:1:XCORCTRL CA PP")
  field(LNK7, "MGNT:LI14:1:YCORCTRL CA PP")
  field(LNK8, "MGNT:LI14:1:SOLNCTRL CA PP")
  field(LNK9, "MGNT:LI14:1:KICKCTRL CA PP")
  field(LNKA, "MGNT:LI14:1:SEXTCTRL CA PP")
}

record(mbbo, "MGNT:LI14:1:CTRL") {
  field(DESC, "All Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "1")
  field(FLNK, "MGNT:LI14:1:ALLSWITCH")
}

record(seq, "MGNT:LI14:1:ALLSWITCH") {
  field(DOL1, "MGNT:LI14:1:CTRL.FFVL")
  field(LNK1, "MGNT:LI14:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:LI14:1:ALLFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:LI14:1:CTRL")
}

record(bo, "MGNT:LI14:1:ALLSTAR") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(PINI, "YES")
  field(FLNK, "MGNT:LI14:1:ALLSTARGO")
}

record(fanout, "MGNT:LI14:1:ALLSTARGO") {
  field(LNK1, "MGNT:LI14:1:ALLBENDSGO")
  field(LNK2, "MGNT:LI14:1:ALLBTRMSGO")
  field(LNK3, "MGNT:LI14:1:ALLLGPSSGO")
  field(LNK4, "MGNT:LI14:1:ALLQUADSGO")
  field(LNK5, "MGNT:LI14:1:ALLXCORSGO")
  field(LNK6, "MGNT:LI14:1:ALLYCORSGO")
  field(FLNK, "MGNT:LI14:1:ALLSTARGO_2")
}
record(fanout, "MGNT:LI14:1:ALLSTARGO_2") {
  field(LNK1, "MGNT:LI14:1:ALLSOLNSGO")
  field(LNK2, "MGNT:LI14:1:ALLKICKSGO")
  field(LNK3, "MGNT:LI14:1:ALLSEXTSGO")
}

#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:BENDCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_BEND so that it can be
# used properly by the the PV <device>:BENDSWITCH

record(mbbo, "MGNT:LI14:1:BENDCTRL") {
  field(DESC, "All BEND Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "2")
  field(FLNK, "MGNT:LI14:1:BENDSWITCH")
}

record(seq, "MGNT:LI14:1:BENDSWITCH") {
  field(DOL1, "MGNT:LI14:1:BENDCTRL.FFVL")
  field(LNK1, "MGNT:LI14:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:LI14:1:BENDFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:LI14:1:BENDCTRL")
}

record(seq, "MGNT:LI14:1:ALLBENDSGO") {
  field(DOL1, "MGNT:LI14:1:ALLSTAR")
  field(LNK1, "MGNT:LI14:1:ALLBENDS PP NMS")
}

record(bo, "MGNT:LI14:1:ALLBENDS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:LI14:1:ALLBENDSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:LI14:1:BENDCTRL",20,10,0,0,"MGNT:LI14:1:BENDCTRL")
#! Field("MGNT:LI14:1:BENDCTRL.FLNK",16777215,1,"MGNT:LI14:1:BENDCTRL.FLNK")
#! Link("MGNT:LI14:1:BENDCTRL.FLNK","MGNT:LI14:1:BENDSWITCH")
#! Field("MGNT:LI14:1:BENDCTRL.FFVL",16777215,1,"MGNT:LI14:1:BENDCTRL.FFVL")
#! Record("MGNT:LI14:1:BENDSWITCH",460,322,0,0,"MGNT:LI14:1:BENDSWITCH")
#! Field("MGNT:LI14:1:BENDSWITCH.DOL1",16777215,0,"MGNT:LI14:1:BENDSWITCH.DOL1")
#! Link("MGNT:LI14:1:BENDSWITCH.DOL1","MGNT:LI14:1:BENDCTRL.FFVL")
#! Field("MGNT:LI14:1:BENDSWITCH.LNK1",16777215,1,"MGNT:LI14:1:BENDSWITCH.LNK1")
#! Field("MGNT:LI14:1:BENDSWITCH.FLNK",16777215,1,"MGNT:LI14:1:BENDSWITCH.FLNK")
#! Record("MGNT:LI14:1:ALLBENDSGO",240,96,0,0,"MGNT:LI14:1:ALLBENDSGO")
#! Field("MGNT:LI14:1:ALLBENDSGO.DOL1",16777215,1,"MGNT:LI14:1:ALLBENDSGO.DOL1")
#! Field("MGNT:LI14:1:ALLBENDSGO.LNK1",16777215,1,"MGNT:LI14:1:ALLBENDSGO.LNK1")
#! Link("MGNT:LI14:1:ALLBENDSGO.LNK1","MGNT:LI14:1:ALLBENDS.VAL")
#! Record("MGNT:LI14:1:ALLBENDS",540,102,0,0,"MGNT:LI14:1:ALLBENDS")
#! Field("MGNT:LI14:1:ALLBENDS.VAL",16777215,0,"MGNT:LI14:1:ALLBENDS.VAL")
#! Field("MGNT:LI14:1:ALLBENDS.FLNK",16777215,1,"MGNT:LI14:1:ALLBENDS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:BTRMCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_BTRM so that it can be
# used properly by the the PV <device>:BTRMSWITCH

record(mbbo, "MGNT:LI14:1:BTRMCTRL") {
  field(DESC, "All BTRM Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "3")
  field(FLNK, "MGNT:LI14:1:BTRMSWITCH")
}

record(seq, "MGNT:LI14:1:BTRMSWITCH") {
  field(DOL1, "MGNT:LI14:1:BTRMCTRL.FFVL")
  field(LNK1, "MGNT:LI14:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:LI14:1:BTRMFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:LI14:1:BTRMCTRL")
}

record(seq, "MGNT:LI14:1:ALLBTRMSGO") {
  field(DOL1, "MGNT:LI14:1:ALLSTAR")
  field(LNK1, "MGNT:LI14:1:ALLBTRMS PP NMS")
}

record(bo, "MGNT:LI14:1:ALLBTRMS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:LI14:1:ALLBTRMSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:LI14:1:BTRMCTRL",20,10,0,0,"MGNT:LI14:1:BTRMCTRL")
#! Field("MGNT:LI14:1:BTRMCTRL.FLNK",16777215,1,"MGNT:LI14:1:BTRMCTRL.FLNK")
#! Link("MGNT:LI14:1:BTRMCTRL.FLNK","MGNT:LI14:1:BTRMSWITCH")
#! Field("MGNT:LI14:1:BTRMCTRL.FFVL",16777215,1,"MGNT:LI14:1:BTRMCTRL.FFVL")
#! Record("MGNT:LI14:1:BTRMSWITCH",460,322,0,0,"MGNT:LI14:1:BTRMSWITCH")
#! Field("MGNT:LI14:1:BTRMSWITCH.DOL1",16777215,0,"MGNT:LI14:1:BTRMSWITCH.DOL1")
#! Link("MGNT:LI14:1:BTRMSWITCH.DOL1","MGNT:LI14:1:BTRMCTRL.FFVL")
#! Field("MGNT:LI14:1:BTRMSWITCH.LNK1",16777215,1,"MGNT:LI14:1:BTRMSWITCH.LNK1")
#! Field("MGNT:LI14:1:BTRMSWITCH.FLNK",16777215,1,"MGNT:LI14:1:BTRMSWITCH.FLNK")
#! Record("MGNT:LI14:1:ALLBTRMSGO",240,96,0,0,"MGNT:LI14:1:ALLBTRMSGO")
#! Field("MGNT:LI14:1:ALLBTRMSGO.DOL1",16777215,1,"MGNT:LI14:1:ALLBTRMSGO.DOL1")
#! Field("MGNT:LI14:1:ALLBTRMSGO.LNK1",16777215,1,"MGNT:LI14:1:ALLBTRMSGO.LNK1")
#! Link("MGNT:LI14:1:ALLBTRMSGO.LNK1","MGNT:LI14:1:ALLBTRMS.VAL")
#! Record("MGNT:LI14:1:ALLBTRMS",540,102,0,0,"MGNT:LI14:1:ALLBTRMS")
#! Field("MGNT:LI14:1:ALLBTRMS.VAL",16777215,0,"MGNT:LI14:1:ALLBTRMS.VAL")
#! Field("MGNT:LI14:1:ALLBTRMS.FLNK",16777215,1,"MGNT:LI14:1:ALLBTRMS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:LGPSCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_LGPS so that it can be
# used properly by the the PV <device>:LGPSSWITCH

record(mbbo, "MGNT:LI14:1:LGPSCTRL") {
  field(DESC, "All LGPS Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "3")
  field(FLNK, "MGNT:LI14:1:LGPSSWITCH")
}

record(seq, "MGNT:LI14:1:LGPSSWITCH") {
  field(DOL1, "MGNT:LI14:1:LGPSCTRL.FFVL")
  field(LNK1, "MGNT:LI14:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:LI14:1:LGPSFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:LI14:1:LGPSCTRL")
}

record(seq, "MGNT:LI14:1:ALLLGPSSGO") {
  field(DOL1, "MGNT:LI14:1:ALLSTAR")
  field(LNK1, "MGNT:LI14:1:ALLLGPSS PP NMS")
}

record(bo, "MGNT:LI14:1:ALLLGPSS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:LI14:1:ALLLGPSSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:LI14:1:LGPSCTRL",20,10,0,0,"MGNT:LI14:1:LGPSCTRL")
#! Field("MGNT:LI14:1:LGPSCTRL.FLNK",16777215,1,"MGNT:LI14:1:LGPSCTRL.FLNK")
#! Link("MGNT:LI14:1:LGPSCTRL.FLNK","MGNT:LI14:1:LGPSSWITCH")
#! Field("MGNT:LI14:1:LGPSCTRL.FFVL",16777215,1,"MGNT:LI14:1:LGPSCTRL.FFVL")
#! Record("MGNT:LI14:1:LGPSSWITCH",460,322,0,0,"MGNT:LI14:1:LGPSSWITCH")
#! Field("MGNT:LI14:1:LGPSSWITCH.DOL1",16777215,0,"MGNT:LI14:1:LGPSSWITCH.DOL1")
#! Link("MGNT:LI14:1:LGPSSWITCH.DOL1","MGNT:LI14:1:LGPSCTRL.FFVL")
#! Field("MGNT:LI14:1:LGPSSWITCH.LNK1",16777215,1,"MGNT:LI14:1:LGPSSWITCH.LNK1")
#! Field("MGNT:LI14:1:LGPSSWITCH.FLNK",16777215,1,"MGNT:LI14:1:LGPSSWITCH.FLNK")
#! Record("MGNT:LI14:1:ALLLGPSSGO",240,96,0,0,"MGNT:LI14:1:ALLLGPSSGO")
#! Field("MGNT:LI14:1:ALLLGPSSGO.DOL1",16777215,1,"MGNT:LI14:1:ALLLGPSSGO.DOL1")
#! Field("MGNT:LI14:1:ALLLGPSSGO.LNK1",16777215,1,"MGNT:LI14:1:ALLLGPSSGO.LNK1")
#! Link("MGNT:LI14:1:ALLLGPSSGO.LNK1","MGNT:LI14:1:ALLLGPSS.VAL")
#! Record("MGNT:LI14:1:ALLLGPSS",540,102,0,0,"MGNT:LI14:1:ALLLGPSS")
#! Field("MGNT:LI14:1:ALLLGPSS.VAL",16777215,0,"MGNT:LI14:1:ALLLGPSS.VAL")
#! Field("MGNT:LI14:1:ALLLGPSS.FLNK",16777215,1,"MGNT:LI14:1:ALLLGPSS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:QUADCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_QUAD so that it can be
# used properly by the the PV <device>:QUADSWITCH

record(mbbo, "MGNT:LI14:1:QUADCTRL") {
  field(DESC, "All QUAD Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "5")
  field(FLNK, "MGNT:LI14:1:QUADSWITCH")
}

record(seq, "MGNT:LI14:1:QUADSWITCH") {
  field(DOL1, "MGNT:LI14:1:QUADCTRL.FFVL")
  field(LNK1, "MGNT:LI14:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:LI14:1:QUADFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:LI14:1:QUADCTRL")
}

record(seq, "MGNT:LI14:1:ALLQUADSGO") {
  field(DOL1, "MGNT:LI14:1:ALLSTAR")
  field(LNK1, "MGNT:LI14:1:ALLQUADS PP NMS")
}

record(bo, "MGNT:LI14:1:ALLQUADS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:LI14:1:ALLQUADSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:LI14:1:QUADCTRL",20,10,0,0,"MGNT:LI14:1:QUADCTRL")
#! Field("MGNT:LI14:1:QUADCTRL.FLNK",16777215,1,"MGNT:LI14:1:QUADCTRL.FLNK")
#! Link("MGNT:LI14:1:QUADCTRL.FLNK","MGNT:LI14:1:QUADSWITCH")
#! Field("MGNT:LI14:1:QUADCTRL.FFVL",16777215,1,"MGNT:LI14:1:QUADCTRL.FFVL")
#! Record("MGNT:LI14:1:QUADSWITCH",460,322,0,0,"MGNT:LI14:1:QUADSWITCH")
#! Field("MGNT:LI14:1:QUADSWITCH.DOL1",16777215,0,"MGNT:LI14:1:QUADSWITCH.DOL1")
#! Link("MGNT:LI14:1:QUADSWITCH.DOL1","MGNT:LI14:1:QUADCTRL.FFVL")
#! Field("MGNT:LI14:1:QUADSWITCH.LNK1",16777215,1,"MGNT:LI14:1:QUADSWITCH.LNK1")
#! Field("MGNT:LI14:1:QUADSWITCH.FLNK",16777215,1,"MGNT:LI14:1:QUADSWITCH.FLNK")
#! Record("MGNT:LI14:1:ALLQUADSGO",240,96,0,0,"MGNT:LI14:1:ALLQUADSGO")
#! Field("MGNT:LI14:1:ALLQUADSGO.DOL1",16777215,1,"MGNT:LI14:1:ALLQUADSGO.DOL1")
#! Field("MGNT:LI14:1:ALLQUADSGO.LNK1",16777215,1,"MGNT:LI14:1:ALLQUADSGO.LNK1")
#! Link("MGNT:LI14:1:ALLQUADSGO.LNK1","MGNT:LI14:1:ALLQUADS.VAL")
#! Record("MGNT:LI14:1:ALLQUADS",540,102,0,0,"MGNT:LI14:1:ALLQUADS")
#! Field("MGNT:LI14:1:ALLQUADS.VAL",16777215,0,"MGNT:LI14:1:ALLQUADS.VAL")
#! Field("MGNT:LI14:1:ALLQUADS.FLNK",16777215,1,"MGNT:LI14:1:ALLQUADS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:XCORCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_XCOR so that it can be
# used properly by the the PV <device>:XCORSWITCH

record(mbbo, "MGNT:LI14:1:XCORCTRL") {
  field(DESC, "All XCOR Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "6")
  field(FLNK, "MGNT:LI14:1:XCORSWITCH")
}

record(seq, "MGNT:LI14:1:XCORSWITCH") {
  field(DOL1, "MGNT:LI14:1:XCORCTRL.FFVL")
  field(LNK1, "MGNT:LI14:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:LI14:1:XCORFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:LI14:1:XCORCTRL")
}

record(seq, "MGNT:LI14:1:ALLXCORSGO") {
  field(DOL1, "MGNT:LI14:1:ALLSTAR")
  field(LNK1, "MGNT:LI14:1:ALLXCORS PP NMS")
}

record(bo, "MGNT:LI14:1:ALLXCORS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:LI14:1:ALLXCORSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:LI14:1:XCORCTRL",20,10,0,0,"MGNT:LI14:1:XCORCTRL")
#! Field("MGNT:LI14:1:XCORCTRL.FLNK",16777215,1,"MGNT:LI14:1:XCORCTRL.FLNK")
#! Link("MGNT:LI14:1:XCORCTRL.FLNK","MGNT:LI14:1:XCORSWITCH")
#! Field("MGNT:LI14:1:XCORCTRL.FFVL",16777215,1,"MGNT:LI14:1:XCORCTRL.FFVL")
#! Record("MGNT:LI14:1:XCORSWITCH",460,322,0,0,"MGNT:LI14:1:XCORSWITCH")
#! Field("MGNT:LI14:1:XCORSWITCH.DOL1",16777215,0,"MGNT:LI14:1:XCORSWITCH.DOL1")
#! Link("MGNT:LI14:1:XCORSWITCH.DOL1","MGNT:LI14:1:XCORCTRL.FFVL")
#! Field("MGNT:LI14:1:XCORSWITCH.LNK1",16777215,1,"MGNT:LI14:1:XCORSWITCH.LNK1")
#! Field("MGNT:LI14:1:XCORSWITCH.FLNK",16777215,1,"MGNT:LI14:1:XCORSWITCH.FLNK")
#! Record("MGNT:LI14:1:ALLXCORSGO",240,96,0,0,"MGNT:LI14:1:ALLXCORSGO")
#! Field("MGNT:LI14:1:ALLXCORSGO.DOL1",16777215,1,"MGNT:LI14:1:ALLXCORSGO.DOL1")
#! Field("MGNT:LI14:1:ALLXCORSGO.LNK1",16777215,1,"MGNT:LI14:1:ALLXCORSGO.LNK1")
#! Link("MGNT:LI14:1:ALLXCORSGO.LNK1","MGNT:LI14:1:ALLXCORS.VAL")
#! Record("MGNT:LI14:1:ALLXCORS",540,102,0,0,"MGNT:LI14:1:ALLXCORS")
#! Field("MGNT:LI14:1:ALLXCORS.VAL",16777215,0,"MGNT:LI14:1:ALLXCORS.VAL")
#! Field("MGNT:LI14:1:ALLXCORS.FLNK",16777215,1,"MGNT:LI14:1:ALLXCORS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:YCORCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_YCOR so that it can be
# used properly by the the PV <device>:YCORSWITCH

record(mbbo, "MGNT:LI14:1:YCORCTRL") {
  field(DESC, "All YCOR Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "7")
  field(FLNK, "MGNT:LI14:1:YCORSWITCH")
}

record(seq, "MGNT:LI14:1:YCORSWITCH") {
  field(DOL1, "MGNT:LI14:1:YCORCTRL.FFVL")
  field(LNK1, "MGNT:LI14:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:LI14:1:YCORFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:LI14:1:YCORCTRL")
}

record(seq, "MGNT:LI14:1:ALLYCORSGO") {
  field(DOL1, "MGNT:LI14:1:ALLSTAR")
  field(LNK1, "MGNT:LI14:1:ALLYCORS PP NMS")
}

record(bo, "MGNT:LI14:1:ALLYCORS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:LI14:1:ALLYCORSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:LI14:1:YCORCTRL",20,10,0,0,"MGNT:LI14:1:YCORCTRL")
#! Field("MGNT:LI14:1:YCORCTRL.FLNK",16777215,1,"MGNT:LI14:1:YCORCTRL.FLNK")
#! Link("MGNT:LI14:1:YCORCTRL.FLNK","MGNT:LI14:1:YCORSWITCH")
#! Field("MGNT:LI14:1:YCORCTRL.FFVL",16777215,1,"MGNT:LI14:1:YCORCTRL.FFVL")
#! Record("MGNT:LI14:1:YCORSWITCH",460,322,0,0,"MGNT:LI14:1:YCORSWITCH")
#! Field("MGNT:LI14:1:YCORSWITCH.DOL1",16777215,0,"MGNT:LI14:1:YCORSWITCH.DOL1")
#! Link("MGNT:LI14:1:YCORSWITCH.DOL1","MGNT:LI14:1:YCORCTRL.FFVL")
#! Field("MGNT:LI14:1:YCORSWITCH.LNK1",16777215,1,"MGNT:LI14:1:YCORSWITCH.LNK1")
#! Field("MGNT:LI14:1:YCORSWITCH.FLNK",16777215,1,"MGNT:LI14:1:YCORSWITCH.FLNK")
#! Record("MGNT:LI14:1:ALLYCORSGO",240,96,0,0,"MGNT:LI14:1:ALLYCORSGO")
#! Field("MGNT:LI14:1:ALLYCORSGO.DOL1",16777215,1,"MGNT:LI14:1:ALLYCORSGO.DOL1")
#! Field("MGNT:LI14:1:ALLYCORSGO.LNK1",16777215,1,"MGNT:LI14:1:ALLYCORSGO.LNK1")
#! Link("MGNT:LI14:1:ALLYCORSGO.LNK1","MGNT:LI14:1:ALLYCORS.VAL")
#! Record("MGNT:LI14:1:ALLYCORS",540,102,0,0,"MGNT:LI14:1:ALLYCORS")
#! Field("MGNT:LI14:1:ALLYCORS.VAL",16777215,0,"MGNT:LI14:1:ALLYCORS.VAL")
#! Field("MGNT:LI14:1:ALLYCORS.FLNK",16777215,1,"MGNT:LI14:1:ALLYCORS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:SOLNCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_SOLN so that it can be
# used properly by the the PV <device>:SOLNSWITCH

record(mbbo, "MGNT:LI14:1:SOLNCTRL") {
  field(DESC, "All SOLN Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "8")
  field(FLNK, "MGNT:LI14:1:SOLNSWITCH")
}

record(seq, "MGNT:LI14:1:SOLNSWITCH") {
  field(DOL1, "MGNT:LI14:1:SOLNCTRL.FFVL")
  field(LNK1, "MGNT:LI14:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:LI14:1:SOLNFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:LI14:1:SOLNCTRL")
}

record(seq, "MGNT:LI14:1:ALLSOLNSGO") {
  field(DOL1, "MGNT:LI14:1:ALLSTAR")
  field(LNK1, "MGNT:LI14:1:ALLSOLNS PP NMS")
}

record(bo, "MGNT:LI14:1:ALLSOLNS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:LI14:1:ALLSOLNSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:LI14:1:SOLNCTRL",20,10,0,0,"MGNT:LI14:1:SOLNCTRL")
#! Field("MGNT:LI14:1:SOLNCTRL.FLNK",16777215,1,"MGNT:LI14:1:SOLNCTRL.FLNK")
#! Link("MGNT:LI14:1:SOLNCTRL.FLNK","MGNT:LI14:1:SOLNSWITCH")
#! Field("MGNT:LI14:1:SOLNCTRL.FFVL",16777215,1,"MGNT:LI14:1:SOLNCTRL.FFVL")
#! Record("MGNT:LI14:1:SOLNSWITCH",460,322,0,0,"MGNT:LI14:1:SOLNSWITCH")
#! Field("MGNT:LI14:1:SOLNSWITCH.DOL1",16777215,0,"MGNT:LI14:1:SOLNSWITCH.DOL1")
#! Link("MGNT:LI14:1:SOLNSWITCH.DOL1","MGNT:LI14:1:SOLNCTRL.FFVL")
#! Field("MGNT:LI14:1:SOLNSWITCH.LNK1",16777215,1,"MGNT:LI14:1:SOLNSWITCH.LNK1")
#! Field("MGNT:LI14:1:SOLNSWITCH.FLNK",16777215,1,"MGNT:LI14:1:SOLNSWITCH.FLNK")
#! Record("MGNT:LI14:1:ALLSOLNSGO",240,96,0,0,"MGNT:LI14:1:ALLSOLNSGO")
#! Field("MGNT:LI14:1:ALLSOLNSGO.DOL1",16777215,1,"MGNT:LI14:1:ALLSOLNSGO.DOL1")
#! Field("MGNT:LI14:1:ALLSOLNSGO.LNK1",16777215,1,"MGNT:LI14:1:ALLSOLNSGO.LNK1")
#! Link("MGNT:LI14:1:ALLSOLNSGO.LNK1","MGNT:LI14:1:ALLSOLNS.VAL")
#! Record("MGNT:LI14:1:ALLSOLNS",540,102,0,0,"MGNT:LI14:1:ALLSOLNS")
#! Field("MGNT:LI14:1:ALLSOLNS.VAL",16777215,0,"MGNT:LI14:1:ALLSOLNS.VAL")
#! Field("MGNT:LI14:1:ALLSOLNS.FLNK",16777215,1,"MGNT:LI14:1:ALLSOLNS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:KICKCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_KICK so that it can be
# used properly by the the PV <device>:KICKSWITCH

record(mbbo, "MGNT:LI14:1:KICKCTRL") {
  field(DESC, "All KICK Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "9")
  field(FLNK, "MGNT:LI14:1:KICKSWITCH")
}

record(seq, "MGNT:LI14:1:KICKSWITCH") {
  field(DOL1, "MGNT:LI14:1:KICKCTRL.FFVL")
  field(LNK1, "MGNT:LI14:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:LI14:1:KICKFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:LI14:1:KICKCTRL")
}

record(seq, "MGNT:LI14:1:ALLKICKSGO") {
  field(DOL1, "MGNT:LI14:1:ALLSTAR")
  field(LNK1, "MGNT:LI14:1:ALLKICKS PP NMS")
}

record(bo, "MGNT:LI14:1:ALLKICKS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:LI14:1:ALLKICKSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:LI14:1:KICKCTRL",20,10,0,0,"MGNT:LI14:1:KICKCTRL")
#! Field("MGNT:LI14:1:KICKCTRL.FLNK",16777215,1,"MGNT:LI14:1:KICKCTRL.FLNK")
#! Link("MGNT:LI14:1:KICKCTRL.FLNK","MGNT:LI14:1:KICKSWITCH")
#! Field("MGNT:LI14:1:KICKCTRL.FFVL",16777215,1,"MGNT:LI14:1:KICKCTRL.FFVL")
#! Record("MGNT:LI14:1:KICKSWITCH",460,322,0,0,"MGNT:LI14:1:KICKSWITCH")
#! Field("MGNT:LI14:1:KICKSWITCH.DOL1",16777215,0,"MGNT:LI14:1:KICKSWITCH.DOL1")
#! Link("MGNT:LI14:1:KICKSWITCH.DOL1","MGNT:LI14:1:KICKCTRL.FFVL")
#! Field("MGNT:LI14:1:KICKSWITCH.LNK1",16777215,1,"MGNT:LI14:1:KICKSWITCH.LNK1")
#! Field("MGNT:LI14:1:KICKSWITCH.FLNK",16777215,1,"MGNT:LI14:1:KICKSWITCH.FLNK")
#! Record("MGNT:LI14:1:ALLKICKSGO",240,96,0,0,"MGNT:LI14:1:ALLKICKSGO")
#! Field("MGNT:LI14:1:ALLKICKSGO.DOL1",16777215,1,"MGNT:LI14:1:ALLKICKSGO.DOL1")
#! Field("MGNT:LI14:1:ALLKICKSGO.LNK1",16777215,1,"MGNT:LI14:1:ALLKICKSGO.LNK1")
#! Link("MGNT:LI14:1:ALLKICKSGO.LNK1","MGNT:LI14:1:ALLKICKS.VAL")
#! Record("MGNT:LI14:1:ALLKICKS",540,102,0,0,"MGNT:LI14:1:ALLKICKS")
#! Field("MGNT:LI14:1:ALLKICKS.VAL",16777215,0,"MGNT:LI14:1:ALLKICKS.VAL")
#! Field("MGNT:LI14:1:ALLKICKS.FLNK",16777215,1,"MGNT:LI14:1:ALLKICKS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:SEXTCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_SEXT so that it can be
# used properly by the the PV <device>:SEXTSWITCH

record(mbbo, "MGNT:LI14:1:SEXTCTRL") {
  field(DESC, "All SEXT Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "10")
  field(FLNK, "MGNT:LI14:1:SEXTSWITCH")
}

record(seq, "MGNT:LI14:1:SEXTSWITCH") {
  field(DOL1, "MGNT:LI14:1:SEXTCTRL.FFVL")
  field(LNK1, "MGNT:LI14:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:LI14:1:SEXTFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:LI14:1:SEXTCTRL")
}

record(seq, "MGNT:LI14:1:ALLSEXTSGO") {
  field(DOL1, "MGNT:LI14:1:ALLSTAR")
  field(LNK1, "MGNT:LI14:1:ALLSEXTS PP NMS")
}

record(bo, "MGNT:LI14:1:ALLSEXTS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:LI14:1:ALLSEXTSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:LI14:1:SEXTCTRL",20,10,0,0,"MGNT:LI14:1:SEXTCTRL")
#! Field("MGNT:LI14:1:SEXTCTRL.FLNK",16777215,1,"MGNT:LI14:1:SEXTCTRL.FLNK")
#! Link("MGNT:LI14:1:SEXTCTRL.FLNK","MGNT:LI14:1:SEXTSWITCH")
#! Field("MGNT:LI14:1:SEXTCTRL.FFVL",16777215,1,"MGNT:LI14:1:SEXTCTRL.FFVL")
#! Record("MGNT:LI14:1:SEXTSWITCH",460,322,0,0,"MGNT:LI14:1:SEXTSWITCH")
#! Field("MGNT:LI14:1:SEXTSWITCH.DOL1",16777215,0,"MGNT:LI14:1:SEXTSWITCH.DOL1")
#! Link("MGNT:LI14:1:SEXTSWITCH.DOL1","MGNT:LI14:1:SEXTCTRL.FFVL")
#! Field("MGNT:LI14:1:SEXTSWITCH.LNK1",16777215,1,"MGNT:LI14:1:SEXTSWITCH.LNK1")
#! Field("MGNT:LI14:1:SEXTSWITCH.FLNK",16777215,1,"MGNT:LI14:1:SEXTSWITCH.FLNK")
#! Record("MGNT:LI14:1:ALLSEXTSGO",240,96,0,0,"MGNT:LI14:1:ALLSEXTSGO")
#! Field("MGNT:LI14:1:ALLSEXTSGO.DOL1",16777215,1,"MGNT:LI14:1:ALLSEXTSGO.DOL1")
#! Field("MGNT:LI14:1:ALLSEXTSGO.LNK1",16777215,1,"MGNT:LI14:1:ALLSEXTSGO.LNK1")
#! Link("MGNT:LI14:1:ALLSEXTSGO.LNK1","MGNT:LI14:1:ALLSEXTS.VAL")
#! Record("MGNT:LI14:1:ALLSEXTS",540,102,0,0,"MGNT:LI14:1:ALLSEXTS")
#! Field("MGNT:LI14:1:ALLSEXTS.VAL",16777215,0,"MGNT:LI14:1:ALLSEXTS.VAL")
#! Field("MGNT:LI14:1:ALLSEXTS.FLNK",16777215,1,"MGNT:LI14:1:ALLSEXTS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(longout, "MGNT:LI19:1:CTRLSWITCH") {
}

# The LNK# (1-8) MUST corresponsds to the magent
# type definition found in the file mgntCtrl.h.
# For example, MGNT_TYPE_BEND is defined as 2 and is LNK2 below.
# If the LNK order is changes you will need to make the
# corresponding change the pv <device>:<type>CTRL which is
# found in the files mgnt_ctrl_allstar.substitutions
# The field FFVL value in MGNT:<LOCA>:1: CTRLCLEAR MUST be set
# to the value for MGNT_TYPE_ALL which is defined as 1 in mgntCtrl.h
# so that it can be used properly by the the PV  MGNT:LI21:1:ALLSWITCH
#
record(seq, "MGNT:LI19:1:CTRLCLEAR") {
  field(DESC, "All function go")
  field(DOL1, "0")
  field(DOL2, "0")
  field(DOL3, "0")
  field(DOL4, "0")
  field(DOL5, "0")
  field(DOL6, "0")
  field(DOL7, "0")
  field(DOL8, "0")
  field(DOL9, "0")
  field(DOLA, "0")
  field(LNK1, "MGNT:LI19:1:CTRL CA PP")
  field(LNK2, "MGNT:LI19:1:BENDCTRL CA PP")
  field(LNK3, "MGNT:LI19:1:BTRMCTRL CA PP")
  field(LNK4, "MGNT:LI19:1:LGPSCTRL CA PP")
  field(LNK5, "MGNT:LI19:1:QUADCTRL CA PP")
  field(LNK6, "MGNT:LI19:1:XCORCTRL CA PP")
  field(LNK7, "MGNT:LI19:1:YCORCTRL CA PP")
  field(LNK8, "MGNT:LI19:1:SOLNCTRL CA PP")
  field(LNK9, "MGNT:LI19:1:KICKCTRL CA PP")
  field(LNKA, "MGNT:LI19:1:SEXTCTRL CA PP")
}

record(mbbo, "MGNT:LI19:1:CTRL") {
  field(DESC, "All Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "1")
  field(FLNK, "MGNT:LI19:1:ALLSWITCH")
}

record(seq, "MGNT:LI19:1:ALLSWITCH") {
  field(DOL1, "MGNT:LI19:1:CTRL.FFVL")
  field(LNK1, "MGNT:LI19:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:LI19:1:ALLFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:LI19:1:CTRL")
}

record(bo, "MGNT:LI19:1:ALLSTAR") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(PINI, "YES")
  field(FLNK, "MGNT:LI19:1:ALLSTARGO")
}

record(fanout, "MGNT:LI19:1:ALLSTARGO") {
  field(LNK1, "MGNT:LI19:1:ALLBENDSGO")
  field(LNK2, "MGNT:LI19:1:ALLBTRMSGO")
  field(LNK3, "MGNT:LI19:1:ALLLGPSSGO")
  field(LNK4, "MGNT:LI19:1:ALLQUADSGO")
  field(LNK5, "MGNT:LI19:1:ALLXCORSGO")
  field(LNK6, "MGNT:LI19:1:ALLYCORSGO")
  field(FLNK, "MGNT:LI19:1:ALLSTARGO_2")
}
record(fanout, "MGNT:LI19:1:ALLSTARGO_2") {
  field(LNK1, "MGNT:LI19:1:ALLSOLNSGO")
  field(LNK2, "MGNT:LI19:1:ALLKICKSGO")
  field(LNK3, "MGNT:LI19:1:ALLSEXTSGO")
}

#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:BENDCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_BEND so that it can be
# used properly by the the PV <device>:BENDSWITCH

record(mbbo, "MGNT:LI19:1:BENDCTRL") {
  field(DESC, "All BEND Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "2")
  field(FLNK, "MGNT:LI19:1:BENDSWITCH")
}

record(seq, "MGNT:LI19:1:BENDSWITCH") {
  field(DOL1, "MGNT:LI19:1:BENDCTRL.FFVL")
  field(LNK1, "MGNT:LI19:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:LI19:1:BENDFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:LI19:1:BENDCTRL")
}

record(seq, "MGNT:LI19:1:ALLBENDSGO") {
  field(DOL1, "MGNT:LI19:1:ALLSTAR")
  field(LNK1, "MGNT:LI19:1:ALLBENDS PP NMS")
}

record(bo, "MGNT:LI19:1:ALLBENDS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:LI19:1:ALLBENDSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:LI19:1:BENDCTRL",20,10,0,0,"MGNT:LI19:1:BENDCTRL")
#! Field("MGNT:LI19:1:BENDCTRL.FLNK",16777215,1,"MGNT:LI19:1:BENDCTRL.FLNK")
#! Link("MGNT:LI19:1:BENDCTRL.FLNK","MGNT:LI19:1:BENDSWITCH")
#! Field("MGNT:LI19:1:BENDCTRL.FFVL",16777215,1,"MGNT:LI19:1:BENDCTRL.FFVL")
#! Record("MGNT:LI19:1:BENDSWITCH",460,322,0,0,"MGNT:LI19:1:BENDSWITCH")
#! Field("MGNT:LI19:1:BENDSWITCH.DOL1",16777215,0,"MGNT:LI19:1:BENDSWITCH.DOL1")
#! Link("MGNT:LI19:1:BENDSWITCH.DOL1","MGNT:LI19:1:BENDCTRL.FFVL")
#! Field("MGNT:LI19:1:BENDSWITCH.LNK1",16777215,1,"MGNT:LI19:1:BENDSWITCH.LNK1")
#! Field("MGNT:LI19:1:BENDSWITCH.FLNK",16777215,1,"MGNT:LI19:1:BENDSWITCH.FLNK")
#! Record("MGNT:LI19:1:ALLBENDSGO",240,96,0,0,"MGNT:LI19:1:ALLBENDSGO")
#! Field("MGNT:LI19:1:ALLBENDSGO.DOL1",16777215,1,"MGNT:LI19:1:ALLBENDSGO.DOL1")
#! Field("MGNT:LI19:1:ALLBENDSGO.LNK1",16777215,1,"MGNT:LI19:1:ALLBENDSGO.LNK1")
#! Link("MGNT:LI19:1:ALLBENDSGO.LNK1","MGNT:LI19:1:ALLBENDS.VAL")
#! Record("MGNT:LI19:1:ALLBENDS",540,102,0,0,"MGNT:LI19:1:ALLBENDS")
#! Field("MGNT:LI19:1:ALLBENDS.VAL",16777215,0,"MGNT:LI19:1:ALLBENDS.VAL")
#! Field("MGNT:LI19:1:ALLBENDS.FLNK",16777215,1,"MGNT:LI19:1:ALLBENDS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:BTRMCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_BTRM so that it can be
# used properly by the the PV <device>:BTRMSWITCH

record(mbbo, "MGNT:LI19:1:BTRMCTRL") {
  field(DESC, "All BTRM Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "3")
  field(FLNK, "MGNT:LI19:1:BTRMSWITCH")
}

record(seq, "MGNT:LI19:1:BTRMSWITCH") {
  field(DOL1, "MGNT:LI19:1:BTRMCTRL.FFVL")
  field(LNK1, "MGNT:LI19:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:LI19:1:BTRMFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:LI19:1:BTRMCTRL")
}

record(seq, "MGNT:LI19:1:ALLBTRMSGO") {
  field(DOL1, "MGNT:LI19:1:ALLSTAR")
  field(LNK1, "MGNT:LI19:1:ALLBTRMS PP NMS")
}

record(bo, "MGNT:LI19:1:ALLBTRMS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:LI19:1:ALLBTRMSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:LI19:1:BTRMCTRL",20,10,0,0,"MGNT:LI19:1:BTRMCTRL")
#! Field("MGNT:LI19:1:BTRMCTRL.FLNK",16777215,1,"MGNT:LI19:1:BTRMCTRL.FLNK")
#! Link("MGNT:LI19:1:BTRMCTRL.FLNK","MGNT:LI19:1:BTRMSWITCH")
#! Field("MGNT:LI19:1:BTRMCTRL.FFVL",16777215,1,"MGNT:LI19:1:BTRMCTRL.FFVL")
#! Record("MGNT:LI19:1:BTRMSWITCH",460,322,0,0,"MGNT:LI19:1:BTRMSWITCH")
#! Field("MGNT:LI19:1:BTRMSWITCH.DOL1",16777215,0,"MGNT:LI19:1:BTRMSWITCH.DOL1")
#! Link("MGNT:LI19:1:BTRMSWITCH.DOL1","MGNT:LI19:1:BTRMCTRL.FFVL")
#! Field("MGNT:LI19:1:BTRMSWITCH.LNK1",16777215,1,"MGNT:LI19:1:BTRMSWITCH.LNK1")
#! Field("MGNT:LI19:1:BTRMSWITCH.FLNK",16777215,1,"MGNT:LI19:1:BTRMSWITCH.FLNK")
#! Record("MGNT:LI19:1:ALLBTRMSGO",240,96,0,0,"MGNT:LI19:1:ALLBTRMSGO")
#! Field("MGNT:LI19:1:ALLBTRMSGO.DOL1",16777215,1,"MGNT:LI19:1:ALLBTRMSGO.DOL1")
#! Field("MGNT:LI19:1:ALLBTRMSGO.LNK1",16777215,1,"MGNT:LI19:1:ALLBTRMSGO.LNK1")
#! Link("MGNT:LI19:1:ALLBTRMSGO.LNK1","MGNT:LI19:1:ALLBTRMS.VAL")
#! Record("MGNT:LI19:1:ALLBTRMS",540,102,0,0,"MGNT:LI19:1:ALLBTRMS")
#! Field("MGNT:LI19:1:ALLBTRMS.VAL",16777215,0,"MGNT:LI19:1:ALLBTRMS.VAL")
#! Field("MGNT:LI19:1:ALLBTRMS.FLNK",16777215,1,"MGNT:LI19:1:ALLBTRMS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:LGPSCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_LGPS so that it can be
# used properly by the the PV <device>:LGPSSWITCH

record(mbbo, "MGNT:LI19:1:LGPSCTRL") {
  field(DESC, "All LGPS Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "3")
  field(FLNK, "MGNT:LI19:1:LGPSSWITCH")
}

record(seq, "MGNT:LI19:1:LGPSSWITCH") {
  field(DOL1, "MGNT:LI19:1:LGPSCTRL.FFVL")
  field(LNK1, "MGNT:LI19:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:LI19:1:LGPSFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:LI19:1:LGPSCTRL")
}

record(seq, "MGNT:LI19:1:ALLLGPSSGO") {
  field(DOL1, "MGNT:LI19:1:ALLSTAR")
  field(LNK1, "MGNT:LI19:1:ALLLGPSS PP NMS")
}

record(bo, "MGNT:LI19:1:ALLLGPSS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:LI19:1:ALLLGPSSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:LI19:1:LGPSCTRL",20,10,0,0,"MGNT:LI19:1:LGPSCTRL")
#! Field("MGNT:LI19:1:LGPSCTRL.FLNK",16777215,1,"MGNT:LI19:1:LGPSCTRL.FLNK")
#! Link("MGNT:LI19:1:LGPSCTRL.FLNK","MGNT:LI19:1:LGPSSWITCH")
#! Field("MGNT:LI19:1:LGPSCTRL.FFVL",16777215,1,"MGNT:LI19:1:LGPSCTRL.FFVL")
#! Record("MGNT:LI19:1:LGPSSWITCH",460,322,0,0,"MGNT:LI19:1:LGPSSWITCH")
#! Field("MGNT:LI19:1:LGPSSWITCH.DOL1",16777215,0,"MGNT:LI19:1:LGPSSWITCH.DOL1")
#! Link("MGNT:LI19:1:LGPSSWITCH.DOL1","MGNT:LI19:1:LGPSCTRL.FFVL")
#! Field("MGNT:LI19:1:LGPSSWITCH.LNK1",16777215,1,"MGNT:LI19:1:LGPSSWITCH.LNK1")
#! Field("MGNT:LI19:1:LGPSSWITCH.FLNK",16777215,1,"MGNT:LI19:1:LGPSSWITCH.FLNK")
#! Record("MGNT:LI19:1:ALLLGPSSGO",240,96,0,0,"MGNT:LI19:1:ALLLGPSSGO")
#! Field("MGNT:LI19:1:ALLLGPSSGO.DOL1",16777215,1,"MGNT:LI19:1:ALLLGPSSGO.DOL1")
#! Field("MGNT:LI19:1:ALLLGPSSGO.LNK1",16777215,1,"MGNT:LI19:1:ALLLGPSSGO.LNK1")
#! Link("MGNT:LI19:1:ALLLGPSSGO.LNK1","MGNT:LI19:1:ALLLGPSS.VAL")
#! Record("MGNT:LI19:1:ALLLGPSS",540,102,0,0,"MGNT:LI19:1:ALLLGPSS")
#! Field("MGNT:LI19:1:ALLLGPSS.VAL",16777215,0,"MGNT:LI19:1:ALLLGPSS.VAL")
#! Field("MGNT:LI19:1:ALLLGPSS.FLNK",16777215,1,"MGNT:LI19:1:ALLLGPSS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:QUADCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_QUAD so that it can be
# used properly by the the PV <device>:QUADSWITCH

record(mbbo, "MGNT:LI19:1:QUADCTRL") {
  field(DESC, "All QUAD Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "5")
  field(FLNK, "MGNT:LI19:1:QUADSWITCH")
}

record(seq, "MGNT:LI19:1:QUADSWITCH") {
  field(DOL1, "MGNT:LI19:1:QUADCTRL.FFVL")
  field(LNK1, "MGNT:LI19:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:LI19:1:QUADFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:LI19:1:QUADCTRL")
}

record(seq, "MGNT:LI19:1:ALLQUADSGO") {
  field(DOL1, "MGNT:LI19:1:ALLSTAR")
  field(LNK1, "MGNT:LI19:1:ALLQUADS PP NMS")
}

record(bo, "MGNT:LI19:1:ALLQUADS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:LI19:1:ALLQUADSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:LI19:1:QUADCTRL",20,10,0,0,"MGNT:LI19:1:QUADCTRL")
#! Field("MGNT:LI19:1:QUADCTRL.FLNK",16777215,1,"MGNT:LI19:1:QUADCTRL.FLNK")
#! Link("MGNT:LI19:1:QUADCTRL.FLNK","MGNT:LI19:1:QUADSWITCH")
#! Field("MGNT:LI19:1:QUADCTRL.FFVL",16777215,1,"MGNT:LI19:1:QUADCTRL.FFVL")
#! Record("MGNT:LI19:1:QUADSWITCH",460,322,0,0,"MGNT:LI19:1:QUADSWITCH")
#! Field("MGNT:LI19:1:QUADSWITCH.DOL1",16777215,0,"MGNT:LI19:1:QUADSWITCH.DOL1")
#! Link("MGNT:LI19:1:QUADSWITCH.DOL1","MGNT:LI19:1:QUADCTRL.FFVL")
#! Field("MGNT:LI19:1:QUADSWITCH.LNK1",16777215,1,"MGNT:LI19:1:QUADSWITCH.LNK1")
#! Field("MGNT:LI19:1:QUADSWITCH.FLNK",16777215,1,"MGNT:LI19:1:QUADSWITCH.FLNK")
#! Record("MGNT:LI19:1:ALLQUADSGO",240,96,0,0,"MGNT:LI19:1:ALLQUADSGO")
#! Field("MGNT:LI19:1:ALLQUADSGO.DOL1",16777215,1,"MGNT:LI19:1:ALLQUADSGO.DOL1")
#! Field("MGNT:LI19:1:ALLQUADSGO.LNK1",16777215,1,"MGNT:LI19:1:ALLQUADSGO.LNK1")
#! Link("MGNT:LI19:1:ALLQUADSGO.LNK1","MGNT:LI19:1:ALLQUADS.VAL")
#! Record("MGNT:LI19:1:ALLQUADS",540,102,0,0,"MGNT:LI19:1:ALLQUADS")
#! Field("MGNT:LI19:1:ALLQUADS.VAL",16777215,0,"MGNT:LI19:1:ALLQUADS.VAL")
#! Field("MGNT:LI19:1:ALLQUADS.FLNK",16777215,1,"MGNT:LI19:1:ALLQUADS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:XCORCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_XCOR so that it can be
# used properly by the the PV <device>:XCORSWITCH

record(mbbo, "MGNT:LI19:1:XCORCTRL") {
  field(DESC, "All XCOR Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "6")
  field(FLNK, "MGNT:LI19:1:XCORSWITCH")
}

record(seq, "MGNT:LI19:1:XCORSWITCH") {
  field(DOL1, "MGNT:LI19:1:XCORCTRL.FFVL")
  field(LNK1, "MGNT:LI19:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:LI19:1:XCORFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:LI19:1:XCORCTRL")
}

record(seq, "MGNT:LI19:1:ALLXCORSGO") {
  field(DOL1, "MGNT:LI19:1:ALLSTAR")
  field(LNK1, "MGNT:LI19:1:ALLXCORS PP NMS")
}

record(bo, "MGNT:LI19:1:ALLXCORS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:LI19:1:ALLXCORSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:LI19:1:XCORCTRL",20,10,0,0,"MGNT:LI19:1:XCORCTRL")
#! Field("MGNT:LI19:1:XCORCTRL.FLNK",16777215,1,"MGNT:LI19:1:XCORCTRL.FLNK")
#! Link("MGNT:LI19:1:XCORCTRL.FLNK","MGNT:LI19:1:XCORSWITCH")
#! Field("MGNT:LI19:1:XCORCTRL.FFVL",16777215,1,"MGNT:LI19:1:XCORCTRL.FFVL")
#! Record("MGNT:LI19:1:XCORSWITCH",460,322,0,0,"MGNT:LI19:1:XCORSWITCH")
#! Field("MGNT:LI19:1:XCORSWITCH.DOL1",16777215,0,"MGNT:LI19:1:XCORSWITCH.DOL1")
#! Link("MGNT:LI19:1:XCORSWITCH.DOL1","MGNT:LI19:1:XCORCTRL.FFVL")
#! Field("MGNT:LI19:1:XCORSWITCH.LNK1",16777215,1,"MGNT:LI19:1:XCORSWITCH.LNK1")
#! Field("MGNT:LI19:1:XCORSWITCH.FLNK",16777215,1,"MGNT:LI19:1:XCORSWITCH.FLNK")
#! Record("MGNT:LI19:1:ALLXCORSGO",240,96,0,0,"MGNT:LI19:1:ALLXCORSGO")
#! Field("MGNT:LI19:1:ALLXCORSGO.DOL1",16777215,1,"MGNT:LI19:1:ALLXCORSGO.DOL1")
#! Field("MGNT:LI19:1:ALLXCORSGO.LNK1",16777215,1,"MGNT:LI19:1:ALLXCORSGO.LNK1")
#! Link("MGNT:LI19:1:ALLXCORSGO.LNK1","MGNT:LI19:1:ALLXCORS.VAL")
#! Record("MGNT:LI19:1:ALLXCORS",540,102,0,0,"MGNT:LI19:1:ALLXCORS")
#! Field("MGNT:LI19:1:ALLXCORS.VAL",16777215,0,"MGNT:LI19:1:ALLXCORS.VAL")
#! Field("MGNT:LI19:1:ALLXCORS.FLNK",16777215,1,"MGNT:LI19:1:ALLXCORS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:YCORCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_YCOR so that it can be
# used properly by the the PV <device>:YCORSWITCH

record(mbbo, "MGNT:LI19:1:YCORCTRL") {
  field(DESC, "All YCOR Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "7")
  field(FLNK, "MGNT:LI19:1:YCORSWITCH")
}

record(seq, "MGNT:LI19:1:YCORSWITCH") {
  field(DOL1, "MGNT:LI19:1:YCORCTRL.FFVL")
  field(LNK1, "MGNT:LI19:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:LI19:1:YCORFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:LI19:1:YCORCTRL")
}

record(seq, "MGNT:LI19:1:ALLYCORSGO") {
  field(DOL1, "MGNT:LI19:1:ALLSTAR")
  field(LNK1, "MGNT:LI19:1:ALLYCORS PP NMS")
}

record(bo, "MGNT:LI19:1:ALLYCORS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:LI19:1:ALLYCORSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:LI19:1:YCORCTRL",20,10,0,0,"MGNT:LI19:1:YCORCTRL")
#! Field("MGNT:LI19:1:YCORCTRL.FLNK",16777215,1,"MGNT:LI19:1:YCORCTRL.FLNK")
#! Link("MGNT:LI19:1:YCORCTRL.FLNK","MGNT:LI19:1:YCORSWITCH")
#! Field("MGNT:LI19:1:YCORCTRL.FFVL",16777215,1,"MGNT:LI19:1:YCORCTRL.FFVL")
#! Record("MGNT:LI19:1:YCORSWITCH",460,322,0,0,"MGNT:LI19:1:YCORSWITCH")
#! Field("MGNT:LI19:1:YCORSWITCH.DOL1",16777215,0,"MGNT:LI19:1:YCORSWITCH.DOL1")
#! Link("MGNT:LI19:1:YCORSWITCH.DOL1","MGNT:LI19:1:YCORCTRL.FFVL")
#! Field("MGNT:LI19:1:YCORSWITCH.LNK1",16777215,1,"MGNT:LI19:1:YCORSWITCH.LNK1")
#! Field("MGNT:LI19:1:YCORSWITCH.FLNK",16777215,1,"MGNT:LI19:1:YCORSWITCH.FLNK")
#! Record("MGNT:LI19:1:ALLYCORSGO",240,96,0,0,"MGNT:LI19:1:ALLYCORSGO")
#! Field("MGNT:LI19:1:ALLYCORSGO.DOL1",16777215,1,"MGNT:LI19:1:ALLYCORSGO.DOL1")
#! Field("MGNT:LI19:1:ALLYCORSGO.LNK1",16777215,1,"MGNT:LI19:1:ALLYCORSGO.LNK1")
#! Link("MGNT:LI19:1:ALLYCORSGO.LNK1","MGNT:LI19:1:ALLYCORS.VAL")
#! Record("MGNT:LI19:1:ALLYCORS",540,102,0,0,"MGNT:LI19:1:ALLYCORS")
#! Field("MGNT:LI19:1:ALLYCORS.VAL",16777215,0,"MGNT:LI19:1:ALLYCORS.VAL")
#! Field("MGNT:LI19:1:ALLYCORS.FLNK",16777215,1,"MGNT:LI19:1:ALLYCORS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:SOLNCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_SOLN so that it can be
# used properly by the the PV <device>:SOLNSWITCH

record(mbbo, "MGNT:LI19:1:SOLNCTRL") {
  field(DESC, "All SOLN Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "8")
  field(FLNK, "MGNT:LI19:1:SOLNSWITCH")
}

record(seq, "MGNT:LI19:1:SOLNSWITCH") {
  field(DOL1, "MGNT:LI19:1:SOLNCTRL.FFVL")
  field(LNK1, "MGNT:LI19:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:LI19:1:SOLNFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:LI19:1:SOLNCTRL")
}

record(seq, "MGNT:LI19:1:ALLSOLNSGO") {
  field(DOL1, "MGNT:LI19:1:ALLSTAR")
  field(LNK1, "MGNT:LI19:1:ALLSOLNS PP NMS")
}

record(bo, "MGNT:LI19:1:ALLSOLNS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:LI19:1:ALLSOLNSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:LI19:1:SOLNCTRL",20,10,0,0,"MGNT:LI19:1:SOLNCTRL")
#! Field("MGNT:LI19:1:SOLNCTRL.FLNK",16777215,1,"MGNT:LI19:1:SOLNCTRL.FLNK")
#! Link("MGNT:LI19:1:SOLNCTRL.FLNK","MGNT:LI19:1:SOLNSWITCH")
#! Field("MGNT:LI19:1:SOLNCTRL.FFVL",16777215,1,"MGNT:LI19:1:SOLNCTRL.FFVL")
#! Record("MGNT:LI19:1:SOLNSWITCH",460,322,0,0,"MGNT:LI19:1:SOLNSWITCH")
#! Field("MGNT:LI19:1:SOLNSWITCH.DOL1",16777215,0,"MGNT:LI19:1:SOLNSWITCH.DOL1")
#! Link("MGNT:LI19:1:SOLNSWITCH.DOL1","MGNT:LI19:1:SOLNCTRL.FFVL")
#! Field("MGNT:LI19:1:SOLNSWITCH.LNK1",16777215,1,"MGNT:LI19:1:SOLNSWITCH.LNK1")
#! Field("MGNT:LI19:1:SOLNSWITCH.FLNK",16777215,1,"MGNT:LI19:1:SOLNSWITCH.FLNK")
#! Record("MGNT:LI19:1:ALLSOLNSGO",240,96,0,0,"MGNT:LI19:1:ALLSOLNSGO")
#! Field("MGNT:LI19:1:ALLSOLNSGO.DOL1",16777215,1,"MGNT:LI19:1:ALLSOLNSGO.DOL1")
#! Field("MGNT:LI19:1:ALLSOLNSGO.LNK1",16777215,1,"MGNT:LI19:1:ALLSOLNSGO.LNK1")
#! Link("MGNT:LI19:1:ALLSOLNSGO.LNK1","MGNT:LI19:1:ALLSOLNS.VAL")
#! Record("MGNT:LI19:1:ALLSOLNS",540,102,0,0,"MGNT:LI19:1:ALLSOLNS")
#! Field("MGNT:LI19:1:ALLSOLNS.VAL",16777215,0,"MGNT:LI19:1:ALLSOLNS.VAL")
#! Field("MGNT:LI19:1:ALLSOLNS.FLNK",16777215,1,"MGNT:LI19:1:ALLSOLNS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:KICKCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_KICK so that it can be
# used properly by the the PV <device>:KICKSWITCH

record(mbbo, "MGNT:LI19:1:KICKCTRL") {
  field(DESC, "All KICK Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "9")
  field(FLNK, "MGNT:LI19:1:KICKSWITCH")
}

record(seq, "MGNT:LI19:1:KICKSWITCH") {
  field(DOL1, "MGNT:LI19:1:KICKCTRL.FFVL")
  field(LNK1, "MGNT:LI19:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:LI19:1:KICKFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:LI19:1:KICKCTRL")
}

record(seq, "MGNT:LI19:1:ALLKICKSGO") {
  field(DOL1, "MGNT:LI19:1:ALLSTAR")
  field(LNK1, "MGNT:LI19:1:ALLKICKS PP NMS")
}

record(bo, "MGNT:LI19:1:ALLKICKS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:LI19:1:ALLKICKSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:LI19:1:KICKCTRL",20,10,0,0,"MGNT:LI19:1:KICKCTRL")
#! Field("MGNT:LI19:1:KICKCTRL.FLNK",16777215,1,"MGNT:LI19:1:KICKCTRL.FLNK")
#! Link("MGNT:LI19:1:KICKCTRL.FLNK","MGNT:LI19:1:KICKSWITCH")
#! Field("MGNT:LI19:1:KICKCTRL.FFVL",16777215,1,"MGNT:LI19:1:KICKCTRL.FFVL")
#! Record("MGNT:LI19:1:KICKSWITCH",460,322,0,0,"MGNT:LI19:1:KICKSWITCH")
#! Field("MGNT:LI19:1:KICKSWITCH.DOL1",16777215,0,"MGNT:LI19:1:KICKSWITCH.DOL1")
#! Link("MGNT:LI19:1:KICKSWITCH.DOL1","MGNT:LI19:1:KICKCTRL.FFVL")
#! Field("MGNT:LI19:1:KICKSWITCH.LNK1",16777215,1,"MGNT:LI19:1:KICKSWITCH.LNK1")
#! Field("MGNT:LI19:1:KICKSWITCH.FLNK",16777215,1,"MGNT:LI19:1:KICKSWITCH.FLNK")
#! Record("MGNT:LI19:1:ALLKICKSGO",240,96,0,0,"MGNT:LI19:1:ALLKICKSGO")
#! Field("MGNT:LI19:1:ALLKICKSGO.DOL1",16777215,1,"MGNT:LI19:1:ALLKICKSGO.DOL1")
#! Field("MGNT:LI19:1:ALLKICKSGO.LNK1",16777215,1,"MGNT:LI19:1:ALLKICKSGO.LNK1")
#! Link("MGNT:LI19:1:ALLKICKSGO.LNK1","MGNT:LI19:1:ALLKICKS.VAL")
#! Record("MGNT:LI19:1:ALLKICKS",540,102,0,0,"MGNT:LI19:1:ALLKICKS")
#! Field("MGNT:LI19:1:ALLKICKS.VAL",16777215,0,"MGNT:LI19:1:ALLKICKS.VAL")
#! Field("MGNT:LI19:1:ALLKICKS.FLNK",16777215,1,"MGNT:LI19:1:ALLKICKS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:SEXTCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_SEXT so that it can be
# used properly by the the PV <device>:SEXTSWITCH

record(mbbo, "MGNT:LI19:1:SEXTCTRL") {
  field(DESC, "All SEXT Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "10")
  field(FLNK, "MGNT:LI19:1:SEXTSWITCH")
}

record(seq, "MGNT:LI19:1:SEXTSWITCH") {
  field(DOL1, "MGNT:LI19:1:SEXTCTRL.FFVL")
  field(LNK1, "MGNT:LI19:1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:LI19:1:SEXTFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:LI19:1:SEXTCTRL")
}

record(seq, "MGNT:LI19:1:ALLSEXTSGO") {
  field(DOL1, "MGNT:LI19:1:ALLSTAR")
  field(LNK1, "MGNT:LI19:1:ALLSEXTS PP NMS")
}

record(bo, "MGNT:LI19:1:ALLSEXTS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:LI19:1:ALLSEXTSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:LI19:1:SEXTCTRL",20,10,0,0,"MGNT:LI19:1:SEXTCTRL")
#! Field("MGNT:LI19:1:SEXTCTRL.FLNK",16777215,1,"MGNT:LI19:1:SEXTCTRL.FLNK")
#! Link("MGNT:LI19:1:SEXTCTRL.FLNK","MGNT:LI19:1:SEXTSWITCH")
#! Field("MGNT:LI19:1:SEXTCTRL.FFVL",16777215,1,"MGNT:LI19:1:SEXTCTRL.FFVL")
#! Record("MGNT:LI19:1:SEXTSWITCH",460,322,0,0,"MGNT:LI19:1:SEXTSWITCH")
#! Field("MGNT:LI19:1:SEXTSWITCH.DOL1",16777215,0,"MGNT:LI19:1:SEXTSWITCH.DOL1")
#! Link("MGNT:LI19:1:SEXTSWITCH.DOL1","MGNT:LI19:1:SEXTCTRL.FFVL")
#! Field("MGNT:LI19:1:SEXTSWITCH.LNK1",16777215,1,"MGNT:LI19:1:SEXTSWITCH.LNK1")
#! Field("MGNT:LI19:1:SEXTSWITCH.FLNK",16777215,1,"MGNT:LI19:1:SEXTSWITCH.FLNK")
#! Record("MGNT:LI19:1:ALLSEXTSGO",240,96,0,0,"MGNT:LI19:1:ALLSEXTSGO")
#! Field("MGNT:LI19:1:ALLSEXTSGO.DOL1",16777215,1,"MGNT:LI19:1:ALLSEXTSGO.DOL1")
#! Field("MGNT:LI19:1:ALLSEXTSGO.LNK1",16777215,1,"MGNT:LI19:1:ALLSEXTSGO.LNK1")
#! Link("MGNT:LI19:1:ALLSEXTSGO.LNK1","MGNT:LI19:1:ALLSEXTS.VAL")
#! Record("MGNT:LI19:1:ALLSEXTS",540,102,0,0,"MGNT:LI19:1:ALLSEXTS")
#! Field("MGNT:LI19:1:ALLSEXTS.VAL",16777215,0,"MGNT:LI19:1:ALLSEXTS.VAL")
#! Field("MGNT:LI19:1:ALLSEXTS.FLNK",16777215,1,"MGNT:LI19:1:ALLSEXTS.FLNK")
record (seq, "MGNT:IN10:1:ALLBENDSSEL"){
  field (DESC, "Select All BENDs")
  field (DOL1,  "MGNT:IN10:1:ALLBENDS")
  field (DOL2,  "MGNT:IN10:1:ALLBENDS")
  field (LNK1, "BEND:IN10:751:SELECT CPP NMS")
  field (LNK2, "BEND:IN10:461:SELECT CPP NMS")
}
record (seq, "MGNT:IN10:1:ALLBTRMSSEL"){
  field (DESC, "Select All BTRMs")
  field (DOL1,  "MGNT:IN10:1:ALLBTRMS")
  field (DOL2,  "MGNT:IN10:1:ALLBTRMS")
  field (DOL3,  "MGNT:IN10:1:ALLBTRMS")
  field (DOL4,  "MGNT:IN10:1:ALLBTRMS")
  field (LNK1, "BTRM:IN10:451:SELECT CPP NMS")
  field (LNK2, "BTRM:IN10:475:SELECT CPP NMS")
  field (LNK3, "BTRM:IN10:481:SELECT CPP NMS")
  field (LNK4, "BTRM:IN10:661:SELECT CPP NMS")
}
record (seq, "MGNT:IN10:1:ALLLGPSSSEL"){
  field (DESC, "Select All LGPSs")
  field (DOL1,  "MGNT:IN10:1:ALLLGPSS")
  field (LNK1, "LGPS:IN10:1:SELECT CPP NMS")
}
record (seq, "MGNT:IN10:1:ALLQUADSSEL"){
  field (DESC, "Select All QUADs")
  field (DOL1,  "MGNT:IN10:1:ALLQUADS")
  field (DOL2,  "MGNT:IN10:1:ALLQUADS")
  field (DOL3,  "MGNT:IN10:1:ALLQUADS")
  field (DOL4,  "MGNT:IN10:1:ALLQUADS")
  field (DOL5,  "MGNT:IN10:1:ALLQUADS")
  field (DOL6,  "MGNT:IN10:1:ALLQUADS")
  field (DOL7,  "MGNT:IN10:1:ALLQUADS")
  field (DOL8,  "MGNT:IN10:1:ALLQUADS")
  field (LNK1, "QUAD:IN10:121:SELECT CPP NMS")
  field (LNK2, "QUAD:IN10:122:SELECT CPP NMS")
  field (LNK3, "QUAD:IN10:361:SELECT CPP NMS")
  field (LNK4, "QUAD:IN10:371:SELECT CPP NMS")
  field (LNK5, "QUAD:IN10:425:SELECT CPP NMS")
  field (LNK6, "QUAD:IN10:441:SELECT CPP NMS")
  field (LNK7, "QUAD:IN10:511:SELECT CPP NMS")
  field (LNK8, "QUAD:IN10:525:SELECT CPP NMS")
  field (FLNK, "MGNT:IN10:1:ALLQUADSSEL_2")
}
record (seq, "MGNT:IN10:1:ALLQUADSSEL_2"){
  field (DESC, "Select All QUADs")
  field (DOL1,  "MGNT:IN10:1:ALLQUADS")
  field (DOL2,  "MGNT:IN10:1:ALLQUADS")
  field (DOL3,  "MGNT:IN10:1:ALLQUADS")
  field (DOL4,  "MGNT:IN10:1:ALLQUADS")
  field (DOL5,  "MGNT:IN10:1:ALLQUADS")
  field (LNK1, "QUAD:IN10:631:SELECT CPP NMS")
  field (LNK2, "QUAD:IN10:651:SELECT CPP NMS")
  field (LNK3, "QUAD:IN10:731:SELECT CPP NMS")
  field (LNK4, "QUAD:IN10:771:SELECT CPP NMS")
  field (LNK5, "QUAD:IN10:781:SELECT CPP NMS")
}
record (seq, "MGNT:IN10:1:ALLXCORSSEL"){
  field (DESC, "Select All XCORs")
  field (DOL1,  "MGNT:IN10:1:ALLXCORS")
  field (DOL2,  "MGNT:IN10:1:ALLXCORS")
  field (DOL3,  "MGNT:IN10:1:ALLXCORS")
  field (DOL4,  "MGNT:IN10:1:ALLXCORS")
  field (DOL5,  "MGNT:IN10:1:ALLXCORS")
  field (DOL6,  "MGNT:IN10:1:ALLXCORS")
  field (DOL7,  "MGNT:IN10:1:ALLXCORS")
  field (DOL8,  "MGNT:IN10:1:ALLXCORS")
  field (LNK1, "XCOR:IN10:121:SELECT CPP NMS")
  field (LNK2, "XCOR:IN10:221:SELECT CPP NMS")
  field (LNK3, "XCOR:IN10:311:SELECT CPP NMS")
  field (LNK4, "XCOR:IN10:381:SELECT CPP NMS")
  field (LNK5, "XCOR:IN10:411:SELECT CPP NMS")
  field (LNK6, "XCOR:IN10:491:SELECT CPP NMS")
  field (LNK7, "XCOR:IN10:521:SELECT CPP NMS")
  field (LNK8, "XCOR:IN10:641:SELECT CPP NMS")
  field (FLNK,  "MGNT:IN10:1:ALLXCORSSEL_2")
}
record (seq, "MGNT:IN10:1:ALLXCORSSEL_2"){
  field (DESC, "Select All XCORs")
  field (DOL1,  "MGNT:IN10:1:ALLXCORS")
  field (DOL2,  "MGNT:IN10:1:ALLXCORS")
  field (LNK1, "XCOR:IN10:721:SELECT CPP NMS")
  field (LNK2, "XCOR:IN10:761:SELECT CPP NMS")
}
record (seq, "MGNT:IN10:1:ALLYCORSSEL"){
  field (DESC, "Select All YCORs")
  field (DOL1,  "MGNT:IN10:1:ALLYCORS")
  field (DOL2,  "MGNT:IN10:1:ALLYCORS")
  field (DOL3,  "MGNT:IN10:1:ALLYCORS")
  field (DOL4,  "MGNT:IN10:1:ALLYCORS")
  field (DOL5,  "MGNT:IN10:1:ALLYCORS")
  field (DOL6,  "MGNT:IN10:1:ALLYCORS")
  field (DOL7,  "MGNT:IN10:1:ALLYCORS")
  field (DOL8,  "MGNT:IN10:1:ALLYCORS")
  field (LNK1, "YCOR:IN10:122:SELECT CPP NMS")
  field (LNK2, "YCOR:IN10:222:SELECT CPP NMS")
  field (LNK3, "YCOR:IN10:312:SELECT CPP NMS")
  field (LNK4, "YCOR:IN10:382:SELECT CPP NMS")
  field (LNK5, "YCOR:IN10:412:SELECT CPP NMS")
  field (LNK6, "YCOR:IN10:492:SELECT CPP NMS")
  field (LNK7, "YCOR:IN10:522:SELECT CPP NMS")
  field (LNK8, "YCOR:IN10:642:SELECT CPP NMS")
  field (FLNK, "MGNT:IN10:1:ALLYCORSSEL_2")
}
record (seq, "MGNT:IN10:1:ALLYCORSSEL_2"){
  field (DESC, "Select All YCORs")
  field (DOL1,  "MGNT:IN10:1:ALLYCORS")
  field (DOL2,  "MGNT:IN10:1:ALLYCORS")
  field (LNK1, "YCOR:IN10:722:SELECT CPP NMS")
  field (LNK2, "YCOR:IN10:762:SELECT CPP NMS")
}
record (seq, "MGNT:IN10:1:ALLSOLNSSEL"){
  field (DESC, "Select All SOLNs")
  field (DOL1, "MGNT:IN10:1:ALLSOLNS")
  field (DOL2, "MGNT:IN10:1:ALLSOLNS")
  field (LNK1, "SOLN:IN10:111:SELECT CPP NMS")
  field (LNK2, "SOLN:IN10:121:SELECT CPP NMS")
}
record (seq, "MGNT:IN10:1:ALLKICKSSEL"){
  field (DESC, "Select All KICKs")
}
record (seq, "MGNT:IN10:1:ALLSEXTSSEL"){
  field (DESC, "Select All SEXTs")
}
record (seq, "MGNT:IN10:1:ALLFUNCGO") {
  field (DESC, "Process CTRL func")
  field (DOL1, "0")
  field (DOL2, "1")
  field (DOL3, "1")
  field (DOL4, "1")
  field (DOL5, "1")
  field (DOL6, "1")
  field (LNK1, "MGNT:IN10:1:CTRLCLEAR.DISV")
  field (LNK2, "MGNT:IN10:1:SOLNFUNCGO.PROC")
  field (LNK3, "MGNT:IN10:1:QUADFUNCGO.PROC")
  field (LNK4, "MGNT:IN10:1:XCORFUNCGO.PROC")
  field (LNK5, "MGNT:IN10:1:YCORFUNCGO.PROC")
  field (LNK6, "MGNT:IN10:1:LGPSFUNCGO.PROC")
  field (FLNK, "MGNT:IN10:1:ALLFUNCGO_2")
}
record (seq, "MGNT:IN10:1:ALLFUNCGO_2") {
  field (DESC, "Process CTRL func")
  field (DOL1, "1")
  field (DOL2, "1")
  field (DOL3, "1")
  field (DOL4, "1")
  field (DOL5, "1")
  field (LNK1, "MGNT:IN10:1:BENDFUNCGO.PROC")
  field (LNK2, "MGNT:IN10:1:BTRMFUNCGO.PROC")
  field (LNK3, "MGNT:IN10:1:KICKFUNCGO.PROC")
  field (LNK4, "MGNT:IN10:1:SEXTFUNCGO.PROC")
  field (LNK5, "MGNT:IN10:1:CTRLCLEAR.DISV")
  field (FLNK, "MGNT:IN10:1:CTRLCLEAR")
}
record (fanout, "MGNT:IN10:1:BENDFUNCGO") {
  field (DESC, "Process All BENDs")
  field (LNK1, "BEND:IN10:751:ALLFUNCGO")
  field (LNK2, "BEND:IN10:461:ALLFUNCGO")
  field (FLNK, "MGNT:IN10:1:CTRLCLEAR")
}
record (fanout, "MGNT:IN10:1:BTRMFUNCGO") {
  field (DESC, "Process All BTRMs")
  field (LNK1, "BTRM:IN10:451:ALLFUNCGO")
  field (LNK2, "BTRM:IN10:475:ALLFUNCGO")
  field (LNK3, "BTRM:IN10:481:ALLFUNCGO")
  field (LNK4, "BTRM:IN10:661:ALLFUNCGO")
  field (FLNK, "MGNT:IN10:1:CTRLCLEAR")
}
record (fanout, "MGNT:IN10:1:SOLNFUNCGO") {
  field (DESC, "Process All SOLNs")
  field (LNK1, "SOLN:IN10:111:ALLFUNCGO")
  field (LNK2, "SOLN:IN10:121:ALLFUNCGO")
  field (FLNK, "MGNT:IN10:1:CTRLCLEAR")
}
record (fanout, "MGNT:IN10:1:KICKFUNCGO") {
  field (DESC, "Process All KICKs")
  field (FLNK, "MGNT:IN10:1:CTRLCLEAR")
}
record (fanout, "MGNT:IN10:1:SEXTFUNCGO") {
  field (DESC, "Process All SEXTs")
  field (FLNK, "MGNT:IN10:1:CTRLCLEAR")
}
record (fanout, "MGNT:IN10:1:QUADFUNCGO"){
  field (DESC, "Process All QUADs")
  field (LNK1, "QUAD:IN10:121:ALLFUNCGO")
  field (LNK2, "QUAD:IN10:122:ALLFUNCGO")
  field (LNK3, "QUAD:IN10:361:ALLFUNCGO")
  field (LNK4, "QUAD:IN10:371:ALLFUNCGO")
  field (LNK5, "QUAD:IN10:425:ALLFUNCGO")
  field (LNK6, "QUAD:IN10:441:ALLFUNCGO")
  field (FLNK, "MGNT:IN10:1:QUADFUNCGO_2")
}
record (fanout, "MGNT:IN10:1:QUADFUNCGO_2"){
  field (DESC, "Process All QUADs")
  field (LNK1, "QUAD:IN10:511:ALLFUNCGO")
  field (LNK2, "QUAD:IN10:525:ALLFUNCGO")
  field (LNK3, "QUAD:IN10:631:ALLFUNCGO")
  field (LNK4, "QUAD:IN10:651:ALLFUNCGO")
  field (LNK5, "QUAD:IN10:731:ALLFUNCGO")
  field (LNK6, "QUAD:IN10:771:ALLFUNCGO")
  field (FLNK, "MGNT:IN10:1:QUADFUNCGO_3")
}
record (fanout, "MGNT:IN10:1:QUADFUNCGO_3"){
  field (DESC, "Process All QUADs")
  field (LNK1, "QUAD:IN10:781:ALLFUNCGO")
  field (FLNK, "MGNT:IN10:1:CTRLCLEAR")
}

record (fanout, "MGNT:IN10:1:XCORFUNCGO"){
  field (DESC, "Process All XCORs")
  field (LNK1, "XCOR:IN10:121:ALLFUNCGO")
  field (LNK2, "XCOR:IN10:221:ALLFUNCGO")
  field (LNK3, "XCOR:IN10:311:ALLFUNCGO")
  field (LNK4, "XCOR:IN10:381:ALLFUNCGO")
  field (LNK5, "XCOR:IN10:411:ALLFUNCGO")
  field (LNK6, "XCOR:IN10:491:ALLFUNCGO")
  field (FLNK,  "MGNT:IN10:1:XCORFUNCGO_2")
}
record (fanout, "MGNT:IN10:1:XCORFUNCGO_2"){
  field (DESC, "Process All XCORs")
  field (LNK1, "XCOR:IN10:521:ALLFUNCGO")
  field (LNK2, "XCOR:IN10:641:ALLFUNCGO")
  field (LNK3, "XCOR:IN10:721:ALLFUNCGO")
  field (LNK4, "XCOR:IN10:761:ALLFUNCGO")
  field (FLNK, "MGNT:IN10:1:CTRLCLEAR")
}
record (fanout, "MGNT:IN10:1:YCORFUNCGO"){
  field (DESC, "Process All YCORs")
  field (LNK1, "YCOR:IN10:122:ALLFUNCGO")
  field (LNK2, "YCOR:IN10:222:ALLFUNCGO")
  field (LNK3, "YCOR:IN10:312:ALLFUNCGO")
  field (LNK4, "YCOR:IN10:382:ALLFUNCGO")
  field (LNK5, "YCOR:IN10:412:ALLFUNCGO")
  field (LNK6, "YCOR:IN10:492:ALLFUNCGO")
  field (FLNK, "MGNT:IN10:1:YCORFUNCGO_2")
}
record (fanout, "MGNT:IN10:1:YCORFUNCGO_2"){
  field (DESC, "Process All YCORs")
  field (LNK1, "YCOR:IN10:522:ALLFUNCGO")
  field (LNK2, "YCOR:IN10:642:ALLFUNCGO")
  field (LNK3, "YCOR:IN10:722:ALLFUNCGO")
  field (LNK4, "YCOR:IN10:762:ALLFUNCGO")
  field (FLNK, "MGNT:IN10:1:CTRLCLEAR")
}
record (fanout, "MGNT:IN10:1:LGPSFUNCGO"){
  field (DESC, "Process All LGPSs")
  field (LNK1, "LGPS:IN10:1:ALLFUNCGO")
  field (FLNK, "MGNT:IN10:1:CTRLCLEAR")
}

record (seq, "MGNT:LI11:1:ALLBENDSSEL"){
  field (DESC, "Select All BENDs")
  field (DOL1, "MGNT:LI11:1:ALLBENDS")
  field (LNK1, "BEND:LI11:331:SELECT CPP NMS")
}
record (seq, "MGNT:LI11:1:ALLBTRMSSEL"){
  field (DESC, "Select All BTRMs")
  field (DOL1, "MGNT:LI11:1:ALLBTRMS")
  field (DOL2, "MGNT:LI11:1:ALLBTRMS")
  field (DOL3, "MGNT:LI11:1:ALLBTRMS")
  field (LNK1, "BTRM:LI11:314:SELECT CPP NMS")
  field (LNK2, "BTRM:LI11:338:SELECT CPP NMS")
  field (LNK3, "BTRM:LI11:355:SELECT CPP NMS")
}
record (seq, "MGNT:LI11:1:ALLLGPSSSEL"){
  field (DESC, "Select All LGPSs")
  field (DOL1, "MGNT:LI11:1:ALLLGPSS")
  field (LNK1, "LGPS:LI11:2:SELECT CPP NMS")
}
record (seq, "MGNT:LI11:1:ALLQUADSSEL"){
  field (DESC, "Select All QUADs")
  field (DOL1,  "MGNT:LI11:1:ALLQUADS")
  field (DOL2,  "MGNT:LI11:1:ALLQUADS")
  field (DOL3,  "MGNT:LI11:1:ALLQUADS")
  field (DOL4,  "MGNT:LI11:1:ALLQUADS")
  field (DOL5,  "MGNT:LI11:1:ALLQUADS")
  field (DOL6,  "MGNT:LI11:1:ALLQUADS")
  field (DOL7,  "MGNT:LI11:1:ALLQUADS")
  field (DOL8,  "MGNT:LI11:1:ALLQUADS")
  field (DOL9,  "MGNT:LI11:1:ALLQUADS")
  field (LNK2, "QUAD:LI11:132:SELECT CPP NMS")
  field (LNK3, "QUAD:LI11:393:SELECT CPP NMS")
  field (LNK4, "QUAD:LI11:201:SELECT CPP NMS")
  field (LNK5, "QUAD:LI11:265:SELECT CPP NMS")
  field (LNK6, "QUAD:LI11:301:SELECT CPP NMS")
  field (LNK7, "QUAD:LI11:312:SELECT CPP NMS")
  field (LNK8, "QUAD:LI11:317:SELECT CPP NMS")
  field (LNK9, "QUAD:LI11:340:SELECT CPP NMS")
  field (FLNK, "MGNT:LI11:1:ALLQUADSSEL2")
}
record (seq, "MGNT:LI11:1:ALLQUADSSEL2"){
  field (DESC, "Select All QUADs")
  field (DOL1,  "MGNT:LI11:1:ALLQUADS")
  field (DOL2,  "MGNT:LI11:1:ALLQUADS")
  field (DOL3,  "MGNT:LI11:1:ALLQUADS")
  field (DOL4,  "MGNT:LI11:1:ALLQUADS")
  field (LNK1, "QUAD:LI11:352:SELECT CPP NMS")
  field (LNK2, "QUAD:LI11:358:SELECT CPP NMS")
  field (LNK3, "QUAD:LI11:362:SELECT CPP NMS")
  field (LNK4, "QUAD:LI11:393:SELECT CPP NMS")
}

record (seq, "MGNT:LI11:1:ALLXCORSSEL"){
  field (DESC, "Select All XCORs")
  field (DOL1,  "MGNT:LI11:1:ALLXCORS")
  field (DOL2,  "MGNT:LI11:1:ALLXCORS")
  field (DOL3,  "MGNT:LI11:1:ALLXCORS")
  field (DOL4,  "MGNT:LI11:1:ALLXCORS")
  field (DOL5,  "MGNT:LI11:1:ALLXCORS")
  field (DOL6,  "MGNT:LI11:1:ALLXCORS")
  field (LNK1, "XCOR:LI11:104:SELECT CPP NMS")
  field (LNK2, "XCOR:LI11:140:SELECT CPP NMS")
  field (LNK3, "XCOR:LI11:202:SELECT CPP NMS")
  field (LNK4, "XCOR:LI11:272:SELECT CPP NMS")
  field (LNK5, "XCOR:LI11:304:SELECT CPP NMS")
  field (LNK6, "XCOR:LI11:398:SELECT CPP NMS")
}

record (seq, "MGNT:LI11:1:ALLYCORSSEL"){
  field (DESC, "Select All YCORs")
  field (DOL1,  "MGNT:LI11:1:ALLYCORS")
  field (DOL2,  "MGNT:LI11:1:ALLYCORS")
  field (DOL3,  "MGNT:LI11:1:ALLYCORS")
  field (DOL4,  "MGNT:LI11:1:ALLYCORS")
  field (DOL5,  "MGNT:LI11:1:ALLYCORS")
  field (DOL6,  "MGNT:LI11:1:ALLYCORS")
  field (DOL7,  "MGNT:LI11:1:ALLYCORS")
  field (DOL8,  "MGNT:LI11:1:ALLYCORS")
  field (LNK1, "YCOR:LI11:105:SELECT CPP NMS")
  field (LNK2, "YCOR:LI11:141:SELECT CPP NMS")
  field (LNK3, "YCOR:LI11:203:SELECT CPP NMS")
  field (LNK4, "YCOR:LI11:273:SELECT CPP NMS")
  field (LNK5, "YCOR:LI11:305:SELECT CPP NMS")
  field (LNK6, "YCOR:LI11:321:SELECT CPP NMS")
  field (LNK7, "YCOR:LI11:365:SELECT CPP NMS")
  field (LNK8, "YCOR:LI11:399:SELECT CPP NMS")
}

record (seq, "MGNT:LI11:1:ALLSOLNSSEL"){
  field (DESC, "Select All SOLNs")
}
record (seq, "MGNT:LI11:1:ALLKICKSSEL"){
  field (DESC, "Select All KICKs")
}
record (seq, "MGNT:LI11:1:ALLSEXTSSEL"){
  field (DESC, "Select All SEXTs")
}
record (seq, "MGNT:LI11:1:ALLFUNCGO") {
  field (DESC, "Process CTRL func")
  field (DOL1, "0")
  field (DOL2, "1")
  field (DOL3, "1")
  field (DOL4, "1")
  field (DOL5, "1")
  field (DOL6, "1")
  field (LNK1, "MGNT:LI11:1:CTRLCLEAR.DISV")
  field (LNK2, "MGNT:LI11:1:SOLNFUNCGO.PROC")
  field (LNK3, "MGNT:LI11:1:QUADFUNCGO.PROC")
  field (LNK4, "MGNT:LI11:1:XCORFUNCGO.PROC")
  field (LNK5, "MGNT:LI11:1:YCORFUNCGO.PROC")
  field (LNK6, "MGNT:LI11:1:LGPSFUNCGO.PROC")
  field (FLNK, "MGNT:LI11:1:ALLFUNCGO2")
}
record (seq, "MGNT:LI11:1:ALLFUNCGO2") {
  field (DESC, "Process CTRL func")
  field (DOL1, "1")
  field (DOL2, "1")
  field (DOL3, "1")
  field (DOL4, "1")
  field (DOL5, "1")
  field (LNK1, "MGNT:LI11:1:BENDFUNCGO.PROC")
  field (LNK2, "MGNT:LI11:1:BTRMFUNCGO.PROC")
  field (LNK3, "MGNT:LI11:1:KICKFUNCGO.PROC")
  field (LNK4, "MGNT:LI11:1:SEXTFUNCGO.PROC")
  field (LNK5, "MGNT:LI11:1:CTRLCLEAR.DISV")
  field (FLNK, "MGNT:LI11:1:CTRLCLEAR")
}

record (fanout, "MGNT:LI11:1:BENDFUNCGO") {
  field (DESC, "Process All BENDs")
  field (LNK1, "BEND:LI11:331:ALLFUNCGO")
  field (FLNK, "MGNT:LI11:1:CTRLCLEAR")
}
record (fanout, "MGNT:LI11:1:BTRMFUNCGO") {
  field (DESC, "Process All BENDs")
  field (LNK1, "BTRM:LI11:314:ALLFUNCGO")
  field (LNK2, "BTRM:LI11:338:ALLFUNCGO")
  field (LNK3, "BTRM:LI11:355:ALLFUNCGO")
  field (FLNK, "MGNT:LI11:1:CTRLCLEAR")
}
record (fanout, "MGNT:LI11:1:SOLNFUNCGO") {
  field (DESC, "Process All SOLNs")
  field (FLNK, "MGNT:LI11:1:CTRLCLEAR")
}
record (fanout, "MGNT:LI11:1:KICKFUNCGO") {
  field (DESC, "Process All KICKs")
  field (FLNK, "MGNT:LI11:1:CTRLCLEAR")
}
record (fanout, "MGNT:LI11:1:SEXTFUNCGO") {
  field (DESC, "Process All SEXTs")
  field (FLNK, "MGNT:LI11:1:CTRLCLEAR")
}
record (fanout, "MGNT:LI11:1:QUADFUNCGO"){
  field (DESC, "Process All QUADs")
  field (LNK1, "QUAD:LI11:132:ALLFUNCGO")
  field (LNK2, "QUAD:LI11:201:ALLFUNCGO")
  field (LNK3, "QUAD:LI11:265:ALLFUNCGO")
  field (LNK4, "QUAD:LI11:301:ALLFUNCGO")
  field (LNK5, "QUAD:LI11:312:ALLFUNCGO")
  field (LNK6, "QUAD:LI11:317:ALLFUNCGO")
  field (FLNK, "MGNT:LI11:1:QUADFUNCGO2")
}
record (fanout, "MGNT:LI11:1:QUADFUNCGO2"){
  field (DESC, "Process All QUADs")
  field (LNK1, "QUAD:LI11:340:ALLFUNCGO")
  field (LNK2, "QUAD:LI11:352:ALLFUNCGO")
  field (LNK3, "QUAD:LI11:358:ALLFUNCGO")
  field (LNK4, "QUAD:LI11:362:ALLFUNCGO")
  field (LNK5, "QUAD:LI11:393:ALLFUNCGO")
  field (FLNK, "MGNT:LI11:1:CTRLCLEAR")
}

record (fanout, "MGNT:LI11:1:XCORFUNCGO"){
  field (DESC, "Process All XCORs")
  field (LNK1, "XCOR:LI11:104:ALLFUNCGO")
  field (LNK2, "XCOR:LI11:140:ALLFUNCGO")
  field (LNK3, "XCOR:LI11:202:ALLFUNCGO")
  field (LNK4, "XCOR:LI11:272:ALLFUNCGO")
  field (LNK5, "XCOR:LI11:304:ALLFUNCGO")
  field (LNK6, "XCOR:LI11:398:ALLFUNCGO")
  field (FLNK, "MGNT:LI11:1:CTRLCLEAR")
}
record (fanout, "MGNT:LI11:1:YCORFUNCGO"){
  field (DESC, "Process All YCORs")
  field (LNK1, "YCOR:LI11:105:ALLFUNCGO")
  field (LNK2, "YCOR:LI11:141:ALLFUNCGO")
  field (LNK3, "YCOR:LI11:203:ALLFUNCGO")
  field (LNK4, "YCOR:LI11:273:ALLFUNCGO")
  field (LNK5, "YCOR:LI11:305:ALLFUNCGO")
  field (LNK6, "YCOR:LI11:321:ALLFUNCGO")
  field (FLNK, "MGNT:LI11:1:YCORFUNCGO2")
}
record (fanout, "MGNT:LI11:1:YCORFUNCGO2"){
  field (DESC, "Process All YCORs")
  field (LNK1, "YCOR:LI11:365:ALLFUNCGO")
  field (LNK2, "YCOR:LI11:399:ALLFUNCGO")
  field (FLNK, "MGNT:LI11:1:CTRLCLEAR")
}

record (fanout, "MGNT:LI11:1:LGPSFUNCGO"){
  field (DESC, "Process All LGPSs")
  field (LNK1, "LGPS:LI11:2:ALLFUNCGO")
  field (FLNK, "MGNT:LI11:1:CTRLCLEAR")
}

record (seq, "MGNT:LI14:1:ALLSOLNSSEL"){
  field (DESC, "Select All SOLNs")
}
record (seq, "MGNT:LI14:1:ALLKICKSSEL"){
  field (DESC, "Select All KICKs")
}
record (seq, "MGNT:LI14:1:ALLSEXTSSEL"){
  field (DESC, "Select All SEXTs")
}

record (seq, "MGNT:LI14:1:ALLBENDSSEL"){
  field (DESC, "Select All BENDs")
  field (DOL1,  "MGNT:LI14:1:ALLBENDS")
  field (LNK1, "BEND:LI14:720:SELECT CPP NMS")
}
record (seq, "MGNT:LI14:1:ALLBTRMSSEL"){
  field (DESC, "Select All BTRMs")
  field (DOL1,  "MGNT:LI14:1:ALLBTRMS")
  field (DOL2,  "MGNT:LI14:1:ALLBTRMS")
  field (DOL3,  "MGNT:LI14:1:ALLBTRMS")
  field (DOL4,  "MGNT:LI14:1:ALLBTRMS")
  field (DOL5,  "MGNT:LI14:1:ALLBTRMS")
  field (DOL6,  "MGNT:LI14:1:ALLBTRMS")
  field (LNK1, "BTRM:LI14:720:SELECT CPP NMS")
  field (LNK2, "BTRM:LI14:796:SELECT CPP NMS")
  field (LNK3, "BTRM:LI14:808:SELECT CPP NMS")
  field (LNK4, "BTRM:LI14:883:SELECT CPP NMS")
  field (LNK5, "BTRM:LI14:1796:SELECT CPP NMS")
  field (LNK6, "BTRM:LI14:1808:SELECT CPP NMS")
}
record (seq, "MGNT:LI14:1:ALLLGPSSSEL"){
  field (DESC, "Select All LGPSs")
  field (DOL1,  "MGNT:LI14:1:ALLLGPSS")
  field (LNK1, "LGPS:LI14:2:SELECT CPP NMS")
}
record (seq, "MGNT:LI14:1:ALLQUADSSEL"){
  field (DESC, "Select All QUADs")
  field (DOL1,  "MGNT:LI14:1:ALLQUADS")
  field (DOL2,  "MGNT:LI14:1:ALLQUADS")
  field (DOL3,  "MGNT:LI14:1:ALLQUADS")
  field (DOL4,  "MGNT:LI14:1:ALLQUADS")
  field (DOL5,  "MGNT:LI14:1:ALLQUADS")
  field (DOL6,  "MGNT:LI14:1:ALLQUADS")
  field (DOL7,  "MGNT:LI14:1:ALLQUADS")
  field (DOL8,  "MGNT:LI14:1:ALLQUADS")
  field (LNK1, "QUAD:LI14:738:SELECT CPP NMS")
  field (LNK2, "QUAD:LI14:1738:SELECT CPP NMS")
  field (LNK3, "QUAD:LI14:866:SELECT CPP NMS")
  field (LNK4, "QUAD:LI14:1866:SELECT CPP NMS")
  field (LNK5, "QUAD:LI14:701:SELECT CPP NMS")
  field (LNK6, "QUAD:LI14:715:SELECT CPP NMS")
  field (LNK7, "QUAD:LI14:891:SELECT CPP NMS")
  field (LNK8, "QUAD:LI14:901:SELECT CPP NMS")
}
record (seq, "MGNT:LI14:1:ALLXCORSSEL"){
  field (DESC, "Select All XCORs")
}
record (seq, "MGNT:LI14:1:ALLYCORSSEL"){
  field (DESC, "Select All YCORs")
  field (DOL1,  "MGNT:LI14:1:ALLYCORS")
  field (DOL2,  "MGNT:LI14:1:ALLYCORS")
  field (LNK1, "YCOR:LI14:780:SELECT CPP NMS")
  field (LNK2, "YCOR:LI14:1780:SELECT CPP NMS")
}
record (seq, "MGNT:LI14:1:ALLFUNCGO") {
  field (DESC, "Process CTRL func")
  field (DOL1, "0")
  field (DOL2, "1")
  field (DOL3, "1")
  field (DOL4, "1")
  field (DOL5, "1")
  field (DOL6, "1")
  field (LNK1, "MGNT:LI14:1:CTRLCLEAR.DISV")
  field (LNK2, "MGNT:LI14:1:SOLNFUNCGO.PROC")
  field (LNK3, "MGNT:LI14:1:QUADFUNCGO.PROC")
  field (LNK4, "MGNT:LI14:1:XCORFUNCGO.PROC")
  field (LNK5, "MGNT:LI14:1:YCORFUNCGO.PROC")
  field (LNK6, "MGNT:LI14:1:LGPSFUNCGO.PROC")
  field (FLNK, "MGNT:LI14:1:ALLFUNCGO2")
}
record (seq, "MGNT:LI14:1:ALLFUNCGO2") {
  field (DESC, "Process CTRL func")
  field (DOL1, "1")
  field (DOL2, "1")
  field (DOL3, "1")
  field (DOL4, "1")
  field (DOL5, "1")
  field (LNK1, "MGNT:LI14:1:BENDFUNCGO.PROC")
  field (LNK2, "MGNT:LI14:1:BTRMFUNCGO.PROC")
  field (LNK3, "MGNT:LI14:1:KICKFUNCGO.PROC")
  field (LNK4, "MGNT:LI14:1:SEXTFUNCGO.PROC")
  field (LNK5, "MGNT:LI14:1:CTRLCLEAR.DISV")
  field (FLNK, "MGNT:LI14:1:CTRLCLEAR")
}

record (fanout, "MGNT:LI14:1:BENDFUNCGO") {
  field (DESC, "Process All BENDs")
  field (LNK1, "BEND:LI14:720:ALLFUNCGO")
  field (FLNK, "MGNT:LI14:1:CTRLCLEAR")
}
record (fanout, "MGNT:LI14:1:BTRMFUNCGO") {
  field (DESC, "Process All BENDs")
  field (LNK1, "BTRM:LI14:720:ALLFUNCGO")
  field (LNK2, "BTRM:LI14:796:ALLFUNCGO")
  field (LNK3, "BTRM:LI14:808:ALLFUNCGO")
  field (LNK4, "BTRM:LI14:883:ALLFUNCGO")
  field (LNK5, "BTRM:LI14:1796:ALLFUNCGO")
  field (LNK6, "BTRM:LI14:1808:ALLFUNCGO")
  field (FLNK, "MGNT:LI14:1:CTRLCLEAR")
}
record (fanout, "MGNT:LI14:1:SOLNFUNCGO") {
  field (DESC, "Process All SOLNs")
  field (FLNK, "MGNT:LI14:1:CTRLCLEAR")
}
record (fanout, "MGNT:LI14:1:KICKFUNCGO") {
  field (DESC, "Process All KICKs")
  field (FLNK, "MGNT:LI14:1:CTRLCLEAR")
}
record (fanout, "MGNT:LI14:1:SEXTFUNCGO") {
  field (DESC, "Process All SEXTs")
  field (FLNK, "MGNT:LI14:1:CTRLCLEAR")
}
record (fanout, "MGNT:LI14:1:QUADFUNCGO"){
  field (DESC, "Process All QUADs")
  field (LNK1, "QUAD:LI14:738:ALLFUNCGO")
  field (LNK2, "QUAD:LI14:1738:ALLFUNCGO")
  field (LNK3, "QUAD:LI14:866:ALLFUNCGO")
  field (LNK4, "QUAD:LI14:1866:ALLFUNCGO")
  field (FLNK, "MGNT:LI14:1:QUADFUNCGO2")
}
record (fanout, "MGNT:LI14:1:QUADFUNCGO2"){
  field (DESC, "Process All QUADs")
  field (LNK1, "QUAD:LI14:701:ALLFUNCGO")
  field (LNK2, "QUAD:LI14:715:ALLFUNCGO")
  field (LNK3, "QUAD:LI14:891:ALLFUNCGO")
  field (LNK4, "QUAD:LI14:901:ALLFUNCGO")
  field (FLNK, "MGNT:LI14:1:CTRLCLEAR")
}

record (fanout, "MGNT:LI14:1:XCORFUNCGO"){
  field (DESC, "Process All XCORs")
  field (FLNK, "MGNT:LI14:1:CTRLCLEAR")
}
record (fanout, "MGNT:LI14:1:YCORFUNCGO"){
  field (DESC, "Process All YCORs")
  field (LNK1, "YCOR:LI14:780:ALLFUNCGO")
  field (LNK2, "YCOR:LI14:1780:ALLFUNCGO")
  field (FLNK, "MGNT:LI14:1:CTRLCLEAR")
}
record (fanout, "MGNT:LI14:1:LGPSFUNCGO"){
  field (DESC, "Process All LGPSs")
  field (LNK1, "LGPS:LI14:2:ALLFUNCGO")
  field (FLNK, "MGNT:LI14:1:CTRLCLEAR")
}

record (dfanout, "MGNT:LI19:1:ALLSOLNSSEL"){
  field (DESC, "Select All SOLNs")
}
record (seq, "MGNT:LI19:1:ALLKICKSSEL"){
  field (DESC, "Select All KICKs")
}
record (seq, "MGNT:LI19:1:ALLSEXTSSEL"){
  field (DESC, "Select All SEXTs")
}
record (seq, "MGNT:LI19:1:ALLBENDSSEL"){
  field (DESC, "Select All BENDs")
}
record (seq, "MGNT:LI19:1:ALLBTRMSSEL"){
  field (DESC, "Select All BTRMs")
}
record (seq, "MGNT:LI19:1:ALLLGPSSSEL"){
  field (DESC, "Select All LGPSs")
}
record (seq, "MGNT:LI19:1:ALLQUADSSEL"){
  field (DESC, "Select All QUADs")
  field (DOL1,  "MGNT:LI19:1:ALLQUADS")
  field (DOL2,  "MGNT:LI19:1:ALLQUADS")
  field (LNK1, "QUAD:LI19:851:SELECT CPP NMS")
  field (LNK2, "QUAD:LI19:871:SELECT CPP NMS")
}
record (seq, "MGNT:LI19:1:ALLXCORSSEL"){
  field (DESC, "Select All XCORs")
}
record (seq, "MGNT:LI19:1:ALLYCORSSEL"){
  field (DESC, "Select All YCORs")
}
record (seq, "MGNT:LI19:1:ALLFUNCGO") {
  field (DESC, "Process CTRL func")
  field (DOL1, "0")
  field (DOL2, "1")
  field (DOL3, "1")
  field (DOL4, "1")
  field (DOL5, "1")
  field (DOL6, "1")
  field (LNK1, "MGNT:LI19:1:CTRLCLEAR.DISV")
  field (LNK2, "MGNT:LI19:1:SOLNFUNCGO.PROC")
  field (LNK3, "MGNT:LI19:1:QUADFUNCGO.PROC")
  field (LNK4, "MGNT:LI19:1:XCORFUNCGO.PROC")
  field (LNK5, "MGNT:LI19:1:YCORFUNCGO.PROC")
  field (LNK6, "MGNT:LI19:1:LGPSFUNCGO.PROC")
  field (FLNK, "MGNT:LI19:1:ALLFUNCGO2")
}
record (seq, "MGNT:LI19:1:ALLFUNCGO2") {
  field (DESC, "Process CTRL func")
  field (DOL1, "1")
  field (DOL2, "1")
  field (DOL3, "1")
  field (DOL4, "1")
  field (DOL5, "1")
  field (LNK1, "MGNT:LI19:1:BENDFUNCGO.PROC")
  field (LNK2, "MGNT:LI19:1:BTRMFUNCGO.PROC")
  field (LNK3, "MGNT:LI19:1:KICKFUNCGO.PROC")
  field (LNK4, "MGNT:LI19:1:SEXTFUNCGO.PROC")
  field (LNK5, "MGNT:LI19:1:CTRLCLEAR.DISV")
  field (FLNK, "MGNT:LI19:1:CTRLCLEAR")
}

record (fanout, "MGNT:LI19:1:BENDFUNCGO") {
  field (DESC, "Process All BENDs")
  field (FLNK, "MGNT:LI19:1:CTRLCLEAR")
}
record (fanout, "MGNT:LI19:1:BTRMFUNCGO") {
  field (DESC, "Process All BENDs")
  field (FLNK, "MGNT:LI19:1:CTRLCLEAR")
}
record (fanout, "MGNT:LI19:1:SOLNFUNCGO") {
  field (DESC, "Process All SOLNs")
  field (FLNK, "MGNT:LI19:1:CTRLCLEAR")
}
record (fanout, "MGNT:LI19:1:KICKFUNCGO") {
  field (DESC, "Process All KICKs")
  field (FLNK, "MGNT:LI19:1:CTRLCLEAR")
}
record (fanout, "MGNT:LI19:1:SEXTFUNCGO") {
  field (DESC, "Process All SEXTs")
  field (FLNK, "MGNT:LI19:1:CTRLCLEAR")
}
record (fanout, "MGNT:LI19:1:QUADFUNCGO"){
  field (DESC, "Process All QUADs")
  field (LNK1, "QUAD:LI19:851:ALLFUNCGO")
  field (LNK2, "QUAD:LI19:871:ALLFUNCGO")
  field (FLNK, "MGNT:LI19:1:CTRLCLEAR")
}
record (fanout, "MGNT:LI19:1:XCORFUNCGO"){
  field (DESC, "Process All XCORs")
  field (FLNK, "MGNT:LI19:1:CTRLCLEAR")
}
record (fanout, "MGNT:LI19:1:YCORFUNCGO"){
  field (DESC, "Process All YCORs")
  field (FLNK, "MGNT:LI19:1:CTRLCLEAR")
}
record (fanout, "MGNT:LI19:1:LGPSFUNCGO"){
  field (DESC, "Process All LGPSs")
  field (FLNK, "MGNT:LI19:1:CTRLCLEAR")
}

#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "SOLN:IN10:111:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "SOLN:IN10:111:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "SOLN:IN10:111:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "SOLN:IN10:111:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "SOLN:IN10:111:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "SOLN:IN10:111:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "SOLN:IN10:111:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "SOLN:IN10:111:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "SOLN:IN10:111:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "SOLN:IN10:111:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "SOLN:IN10:111:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "SOLN:IN10:111:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "SOLN:IN10:111:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "SOLN:IN10:111:EDES.PROC PP")
    field(LNK2, "SOLN:IN10:111:EACT.PROC PP")
    field(LNK3, "SOLN:IN10:111:EERR.DISA PP")
    field(LNK4, "SOLN:IN10:111:ECON.PROC PP")
    field(LNK5, "SOLN:IN10:111:BMAGX.PROC PP")
    field(LNK6, "SOLN:IN10:111:BMAGY.PROC PP")
    field(LNK7, "SOLN:IN10:111:BLEM.PROC PP")
    field(LNK8, "SOLN:IN10:111:BMOD.PROC PP")
    field(LNK9, "SOLN:IN10:111:EDESSAVE.PROC PP")
    field(LNKA, "SOLN:IN10:111:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"SOLN:IN10:111:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "SOLN:IN10:111:BMAX")
  field(DOL2, "SOLN:IN10:111:BMAX")
  field(DOL3, "SOLN:IN10:111:BMAX")
  field(DOL4, "SOLN:IN10:111:BMIN")
  field(DOL5, "SOLN:IN10:111:BMIN")
  field(DOL6, "SOLN:IN10:111:BMIN")
  field(LNK1, "SOLN:IN10:111:BMAGX.HOPR")
  field(LNK2, "SOLN:IN10:111:BMAGY.HOPR")
  field(LNK3, "SOLN:IN10:111:BLEM.HOPR")
  field(LNK4, "SOLN:IN10:111:BMAGX.LOPR PP")
  field(LNK5, "SOLN:IN10:111:BMAGY.LOPR PP")
  field(LNK6, "SOLN:IN10:111:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "SOLN:IN10:111:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "SOLN:IN10:111:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "SOLN:IN10:111:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "SOLN:IN10:111:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "SOLN:IN10:111:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "SOLN:IN10:111:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "SOLN:IN10:111:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "SOLN:IN10:111:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "SOLN:IN10:111:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "SOLN:IN10:111:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "SOLN:IN10:111:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "SOLN:IN10:111:EDES NPP MS")
  field(INPB, "SOLN:IN10:111:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "SOLN:IN10:121:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "SOLN:IN10:121:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "SOLN:IN10:121:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "SOLN:IN10:121:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "SOLN:IN10:121:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "SOLN:IN10:121:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "SOLN:IN10:121:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "SOLN:IN10:121:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "SOLN:IN10:121:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "SOLN:IN10:121:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "SOLN:IN10:121:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "SOLN:IN10:121:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "SOLN:IN10:121:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "SOLN:IN10:121:EDES.PROC PP")
    field(LNK2, "SOLN:IN10:121:EACT.PROC PP")
    field(LNK3, "SOLN:IN10:121:EERR.DISA PP")
    field(LNK4, "SOLN:IN10:121:ECON.PROC PP")
    field(LNK5, "SOLN:IN10:121:BMAGX.PROC PP")
    field(LNK6, "SOLN:IN10:121:BMAGY.PROC PP")
    field(LNK7, "SOLN:IN10:121:BLEM.PROC PP")
    field(LNK8, "SOLN:IN10:121:BMOD.PROC PP")
    field(LNK9, "SOLN:IN10:121:EDESSAVE.PROC PP")
    field(LNKA, "SOLN:IN10:121:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"SOLN:IN10:121:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "SOLN:IN10:121:BMAX")
  field(DOL2, "SOLN:IN10:121:BMAX")
  field(DOL3, "SOLN:IN10:121:BMAX")
  field(DOL4, "SOLN:IN10:121:BMIN")
  field(DOL5, "SOLN:IN10:121:BMIN")
  field(DOL6, "SOLN:IN10:121:BMIN")
  field(LNK1, "SOLN:IN10:121:BMAGX.HOPR")
  field(LNK2, "SOLN:IN10:121:BMAGY.HOPR")
  field(LNK3, "SOLN:IN10:121:BLEM.HOPR")
  field(LNK4, "SOLN:IN10:121:BMAGX.LOPR PP")
  field(LNK5, "SOLN:IN10:121:BMAGY.LOPR PP")
  field(LNK6, "SOLN:IN10:121:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "SOLN:IN10:121:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "SOLN:IN10:121:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "SOLN:IN10:121:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "SOLN:IN10:121:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "SOLN:IN10:121:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "SOLN:IN10:121:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "SOLN:IN10:121:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "SOLN:IN10:121:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "SOLN:IN10:121:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "SOLN:IN10:121:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "SOLN:IN10:121:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "SOLN:IN10:121:EDES NPP MS")
  field(INPB, "SOLN:IN10:121:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "QUAD:IN10:121:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "QUAD:IN10:121:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "QUAD:IN10:121:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "QUAD:IN10:121:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "QUAD:IN10:121:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "QUAD:IN10:121:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "QUAD:IN10:121:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "QUAD:IN10:121:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "QUAD:IN10:121:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "QUAD:IN10:121:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "QUAD:IN10:121:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "QUAD:IN10:121:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "QUAD:IN10:121:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "QUAD:IN10:121:EDES.PROC PP")
    field(LNK2, "QUAD:IN10:121:EACT.PROC PP")
    field(LNK3, "QUAD:IN10:121:EERR.DISA PP")
    field(LNK4, "QUAD:IN10:121:ECON.PROC PP")
    field(LNK5, "QUAD:IN10:121:BMAGX.PROC PP")
    field(LNK6, "QUAD:IN10:121:BMAGY.PROC PP")
    field(LNK7, "QUAD:IN10:121:BLEM.PROC PP")
    field(LNK8, "QUAD:IN10:121:BMOD.PROC PP")
    field(LNK9, "QUAD:IN10:121:EDESSAVE.PROC PP")
    field(LNKA, "QUAD:IN10:121:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"QUAD:IN10:121:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "QUAD:IN10:121:BMAX")
  field(DOL2, "QUAD:IN10:121:BMAX")
  field(DOL3, "QUAD:IN10:121:BMAX")
  field(DOL4, "QUAD:IN10:121:BMIN")
  field(DOL5, "QUAD:IN10:121:BMIN")
  field(DOL6, "QUAD:IN10:121:BMIN")
  field(LNK1, "QUAD:IN10:121:BMAGX.HOPR")
  field(LNK2, "QUAD:IN10:121:BMAGY.HOPR")
  field(LNK3, "QUAD:IN10:121:BLEM.HOPR")
  field(LNK4, "QUAD:IN10:121:BMAGX.LOPR PP")
  field(LNK5, "QUAD:IN10:121:BMAGY.LOPR PP")
  field(LNK6, "QUAD:IN10:121:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "QUAD:IN10:121:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "QUAD:IN10:121:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "QUAD:IN10:121:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "QUAD:IN10:121:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "QUAD:IN10:121:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:121:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:121:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:IN10:121:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:121:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:IN10:121:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "QUAD:IN10:121:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "QUAD:IN10:121:EDES NPP MS")
  field(INPB, "QUAD:IN10:121:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "QUAD:IN10:122:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "QUAD:IN10:122:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "QUAD:IN10:122:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "QUAD:IN10:122:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "QUAD:IN10:122:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "QUAD:IN10:122:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "QUAD:IN10:122:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "QUAD:IN10:122:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "QUAD:IN10:122:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "QUAD:IN10:122:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "QUAD:IN10:122:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "QUAD:IN10:122:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "QUAD:IN10:122:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "QUAD:IN10:122:EDES.PROC PP")
    field(LNK2, "QUAD:IN10:122:EACT.PROC PP")
    field(LNK3, "QUAD:IN10:122:EERR.DISA PP")
    field(LNK4, "QUAD:IN10:122:ECON.PROC PP")
    field(LNK5, "QUAD:IN10:122:BMAGX.PROC PP")
    field(LNK6, "QUAD:IN10:122:BMAGY.PROC PP")
    field(LNK7, "QUAD:IN10:122:BLEM.PROC PP")
    field(LNK8, "QUAD:IN10:122:BMOD.PROC PP")
    field(LNK9, "QUAD:IN10:122:EDESSAVE.PROC PP")
    field(LNKA, "QUAD:IN10:122:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"QUAD:IN10:122:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "QUAD:IN10:122:BMAX")
  field(DOL2, "QUAD:IN10:122:BMAX")
  field(DOL3, "QUAD:IN10:122:BMAX")
  field(DOL4, "QUAD:IN10:122:BMIN")
  field(DOL5, "QUAD:IN10:122:BMIN")
  field(DOL6, "QUAD:IN10:122:BMIN")
  field(LNK1, "QUAD:IN10:122:BMAGX.HOPR")
  field(LNK2, "QUAD:IN10:122:BMAGY.HOPR")
  field(LNK3, "QUAD:IN10:122:BLEM.HOPR")
  field(LNK4, "QUAD:IN10:122:BMAGX.LOPR PP")
  field(LNK5, "QUAD:IN10:122:BMAGY.LOPR PP")
  field(LNK6, "QUAD:IN10:122:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "QUAD:IN10:122:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "QUAD:IN10:122:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "QUAD:IN10:122:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "QUAD:IN10:122:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "QUAD:IN10:122:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:122:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:122:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:IN10:122:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:122:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:IN10:122:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "QUAD:IN10:122:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "QUAD:IN10:122:EDES NPP MS")
  field(INPB, "QUAD:IN10:122:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "QUAD:IN10:361:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "QUAD:IN10:361:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "QUAD:IN10:361:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "QUAD:IN10:361:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "QUAD:IN10:361:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "QUAD:IN10:361:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "QUAD:IN10:361:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "QUAD:IN10:361:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "QUAD:IN10:361:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "QUAD:IN10:361:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "QUAD:IN10:361:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "QUAD:IN10:361:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "QUAD:IN10:361:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "QUAD:IN10:361:EDES.PROC PP")
    field(LNK2, "QUAD:IN10:361:EACT.PROC PP")
    field(LNK3, "QUAD:IN10:361:EERR.DISA PP")
    field(LNK4, "QUAD:IN10:361:ECON.PROC PP")
    field(LNK5, "QUAD:IN10:361:BMAGX.PROC PP")
    field(LNK6, "QUAD:IN10:361:BMAGY.PROC PP")
    field(LNK7, "QUAD:IN10:361:BLEM.PROC PP")
    field(LNK8, "QUAD:IN10:361:BMOD.PROC PP")
    field(LNK9, "QUAD:IN10:361:EDESSAVE.PROC PP")
    field(LNKA, "QUAD:IN10:361:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"QUAD:IN10:361:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "QUAD:IN10:361:BMAX")
  field(DOL2, "QUAD:IN10:361:BMAX")
  field(DOL3, "QUAD:IN10:361:BMAX")
  field(DOL4, "QUAD:IN10:361:BMIN")
  field(DOL5, "QUAD:IN10:361:BMIN")
  field(DOL6, "QUAD:IN10:361:BMIN")
  field(LNK1, "QUAD:IN10:361:BMAGX.HOPR")
  field(LNK2, "QUAD:IN10:361:BMAGY.HOPR")
  field(LNK3, "QUAD:IN10:361:BLEM.HOPR")
  field(LNK4, "QUAD:IN10:361:BMAGX.LOPR PP")
  field(LNK5, "QUAD:IN10:361:BMAGY.LOPR PP")
  field(LNK6, "QUAD:IN10:361:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "QUAD:IN10:361:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "QUAD:IN10:361:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "QUAD:IN10:361:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "QUAD:IN10:361:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "QUAD:IN10:361:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:361:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:361:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:IN10:361:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:361:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:IN10:361:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "QUAD:IN10:361:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "QUAD:IN10:361:EDES NPP MS")
  field(INPB, "QUAD:IN10:361:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "QUAD:IN10:371:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "QUAD:IN10:371:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "QUAD:IN10:371:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "QUAD:IN10:371:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "QUAD:IN10:371:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "QUAD:IN10:371:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "QUAD:IN10:371:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "QUAD:IN10:371:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "QUAD:IN10:371:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "QUAD:IN10:371:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "QUAD:IN10:371:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "QUAD:IN10:371:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "QUAD:IN10:371:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "QUAD:IN10:371:EDES.PROC PP")
    field(LNK2, "QUAD:IN10:371:EACT.PROC PP")
    field(LNK3, "QUAD:IN10:371:EERR.DISA PP")
    field(LNK4, "QUAD:IN10:371:ECON.PROC PP")
    field(LNK5, "QUAD:IN10:371:BMAGX.PROC PP")
    field(LNK6, "QUAD:IN10:371:BMAGY.PROC PP")
    field(LNK7, "QUAD:IN10:371:BLEM.PROC PP")
    field(LNK8, "QUAD:IN10:371:BMOD.PROC PP")
    field(LNK9, "QUAD:IN10:371:EDESSAVE.PROC PP")
    field(LNKA, "QUAD:IN10:371:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"QUAD:IN10:371:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "QUAD:IN10:371:BMAX")
  field(DOL2, "QUAD:IN10:371:BMAX")
  field(DOL3, "QUAD:IN10:371:BMAX")
  field(DOL4, "QUAD:IN10:371:BMIN")
  field(DOL5, "QUAD:IN10:371:BMIN")
  field(DOL6, "QUAD:IN10:371:BMIN")
  field(LNK1, "QUAD:IN10:371:BMAGX.HOPR")
  field(LNK2, "QUAD:IN10:371:BMAGY.HOPR")
  field(LNK3, "QUAD:IN10:371:BLEM.HOPR")
  field(LNK4, "QUAD:IN10:371:BMAGX.LOPR PP")
  field(LNK5, "QUAD:IN10:371:BMAGY.LOPR PP")
  field(LNK6, "QUAD:IN10:371:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "QUAD:IN10:371:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "QUAD:IN10:371:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "QUAD:IN10:371:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "QUAD:IN10:371:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "QUAD:IN10:371:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:371:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:371:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:IN10:371:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:371:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:IN10:371:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "QUAD:IN10:371:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "QUAD:IN10:371:EDES NPP MS")
  field(INPB, "QUAD:IN10:371:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "QUAD:IN10:425:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "QUAD:IN10:425:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "QUAD:IN10:425:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "QUAD:IN10:425:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "QUAD:IN10:425:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "QUAD:IN10:425:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "QUAD:IN10:425:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "QUAD:IN10:425:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "QUAD:IN10:425:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "QUAD:IN10:425:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "QUAD:IN10:425:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "QUAD:IN10:425:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "QUAD:IN10:425:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "QUAD:IN10:425:EDES.PROC PP")
    field(LNK2, "QUAD:IN10:425:EACT.PROC PP")
    field(LNK3, "QUAD:IN10:425:EERR.DISA PP")
    field(LNK4, "QUAD:IN10:425:ECON.PROC PP")
    field(LNK5, "QUAD:IN10:425:BMAGX.PROC PP")
    field(LNK6, "QUAD:IN10:425:BMAGY.PROC PP")
    field(LNK7, "QUAD:IN10:425:BLEM.PROC PP")
    field(LNK8, "QUAD:IN10:425:BMOD.PROC PP")
    field(LNK9, "QUAD:IN10:425:EDESSAVE.PROC PP")
    field(LNKA, "QUAD:IN10:425:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"QUAD:IN10:425:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "QUAD:IN10:425:BMAX")
  field(DOL2, "QUAD:IN10:425:BMAX")
  field(DOL3, "QUAD:IN10:425:BMAX")
  field(DOL4, "QUAD:IN10:425:BMIN")
  field(DOL5, "QUAD:IN10:425:BMIN")
  field(DOL6, "QUAD:IN10:425:BMIN")
  field(LNK1, "QUAD:IN10:425:BMAGX.HOPR")
  field(LNK2, "QUAD:IN10:425:BMAGY.HOPR")
  field(LNK3, "QUAD:IN10:425:BLEM.HOPR")
  field(LNK4, "QUAD:IN10:425:BMAGX.LOPR PP")
  field(LNK5, "QUAD:IN10:425:BMAGY.LOPR PP")
  field(LNK6, "QUAD:IN10:425:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "QUAD:IN10:425:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "QUAD:IN10:425:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "QUAD:IN10:425:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "QUAD:IN10:425:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "QUAD:IN10:425:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:425:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:425:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:IN10:425:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:425:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:IN10:425:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "QUAD:IN10:425:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "QUAD:IN10:425:EDES NPP MS")
  field(INPB, "QUAD:IN10:425:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "QUAD:IN10:441:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "QUAD:IN10:441:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "QUAD:IN10:441:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "QUAD:IN10:441:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "QUAD:IN10:441:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "QUAD:IN10:441:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "QUAD:IN10:441:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "QUAD:IN10:441:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "QUAD:IN10:441:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "QUAD:IN10:441:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "QUAD:IN10:441:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "QUAD:IN10:441:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "QUAD:IN10:441:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "QUAD:IN10:441:EDES.PROC PP")
    field(LNK2, "QUAD:IN10:441:EACT.PROC PP")
    field(LNK3, "QUAD:IN10:441:EERR.DISA PP")
    field(LNK4, "QUAD:IN10:441:ECON.PROC PP")
    field(LNK5, "QUAD:IN10:441:BMAGX.PROC PP")
    field(LNK6, "QUAD:IN10:441:BMAGY.PROC PP")
    field(LNK7, "QUAD:IN10:441:BLEM.PROC PP")
    field(LNK8, "QUAD:IN10:441:BMOD.PROC PP")
    field(LNK9, "QUAD:IN10:441:EDESSAVE.PROC PP")
    field(LNKA, "QUAD:IN10:441:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"QUAD:IN10:441:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "QUAD:IN10:441:BMAX")
  field(DOL2, "QUAD:IN10:441:BMAX")
  field(DOL3, "QUAD:IN10:441:BMAX")
  field(DOL4, "QUAD:IN10:441:BMIN")
  field(DOL5, "QUAD:IN10:441:BMIN")
  field(DOL6, "QUAD:IN10:441:BMIN")
  field(LNK1, "QUAD:IN10:441:BMAGX.HOPR")
  field(LNK2, "QUAD:IN10:441:BMAGY.HOPR")
  field(LNK3, "QUAD:IN10:441:BLEM.HOPR")
  field(LNK4, "QUAD:IN10:441:BMAGX.LOPR PP")
  field(LNK5, "QUAD:IN10:441:BMAGY.LOPR PP")
  field(LNK6, "QUAD:IN10:441:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "QUAD:IN10:441:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "QUAD:IN10:441:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "QUAD:IN10:441:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "QUAD:IN10:441:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "QUAD:IN10:441:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:441:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:441:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:IN10:441:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:441:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:IN10:441:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "QUAD:IN10:441:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "QUAD:IN10:441:EDES NPP MS")
  field(INPB, "QUAD:IN10:441:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "QUAD:IN10:511:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "QUAD:IN10:511:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "QUAD:IN10:511:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "QUAD:IN10:511:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "QUAD:IN10:511:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "QUAD:IN10:511:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "QUAD:IN10:511:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "QUAD:IN10:511:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "QUAD:IN10:511:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "QUAD:IN10:511:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "QUAD:IN10:511:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "QUAD:IN10:511:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "QUAD:IN10:511:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "QUAD:IN10:511:EDES.PROC PP")
    field(LNK2, "QUAD:IN10:511:EACT.PROC PP")
    field(LNK3, "QUAD:IN10:511:EERR.DISA PP")
    field(LNK4, "QUAD:IN10:511:ECON.PROC PP")
    field(LNK5, "QUAD:IN10:511:BMAGX.PROC PP")
    field(LNK6, "QUAD:IN10:511:BMAGY.PROC PP")
    field(LNK7, "QUAD:IN10:511:BLEM.PROC PP")
    field(LNK8, "QUAD:IN10:511:BMOD.PROC PP")
    field(LNK9, "QUAD:IN10:511:EDESSAVE.PROC PP")
    field(LNKA, "QUAD:IN10:511:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"QUAD:IN10:511:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "QUAD:IN10:511:BMAX")
  field(DOL2, "QUAD:IN10:511:BMAX")
  field(DOL3, "QUAD:IN10:511:BMAX")
  field(DOL4, "QUAD:IN10:511:BMIN")
  field(DOL5, "QUAD:IN10:511:BMIN")
  field(DOL6, "QUAD:IN10:511:BMIN")
  field(LNK1, "QUAD:IN10:511:BMAGX.HOPR")
  field(LNK2, "QUAD:IN10:511:BMAGY.HOPR")
  field(LNK3, "QUAD:IN10:511:BLEM.HOPR")
  field(LNK4, "QUAD:IN10:511:BMAGX.LOPR PP")
  field(LNK5, "QUAD:IN10:511:BMAGY.LOPR PP")
  field(LNK6, "QUAD:IN10:511:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "QUAD:IN10:511:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "QUAD:IN10:511:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "QUAD:IN10:511:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "QUAD:IN10:511:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "QUAD:IN10:511:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:511:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:511:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:IN10:511:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:511:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:IN10:511:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "QUAD:IN10:511:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "QUAD:IN10:511:EDES NPP MS")
  field(INPB, "QUAD:IN10:511:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "QUAD:IN10:525:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "QUAD:IN10:525:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "QUAD:IN10:525:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "QUAD:IN10:525:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "QUAD:IN10:525:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "QUAD:IN10:525:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "QUAD:IN10:525:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "QUAD:IN10:525:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "QUAD:IN10:525:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "QUAD:IN10:525:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "QUAD:IN10:525:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "QUAD:IN10:525:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "QUAD:IN10:525:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "QUAD:IN10:525:EDES.PROC PP")
    field(LNK2, "QUAD:IN10:525:EACT.PROC PP")
    field(LNK3, "QUAD:IN10:525:EERR.DISA PP")
    field(LNK4, "QUAD:IN10:525:ECON.PROC PP")
    field(LNK5, "QUAD:IN10:525:BMAGX.PROC PP")
    field(LNK6, "QUAD:IN10:525:BMAGY.PROC PP")
    field(LNK7, "QUAD:IN10:525:BLEM.PROC PP")
    field(LNK8, "QUAD:IN10:525:BMOD.PROC PP")
    field(LNK9, "QUAD:IN10:525:EDESSAVE.PROC PP")
    field(LNKA, "QUAD:IN10:525:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"QUAD:IN10:525:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "QUAD:IN10:525:BMAX")
  field(DOL2, "QUAD:IN10:525:BMAX")
  field(DOL3, "QUAD:IN10:525:BMAX")
  field(DOL4, "QUAD:IN10:525:BMIN")
  field(DOL5, "QUAD:IN10:525:BMIN")
  field(DOL6, "QUAD:IN10:525:BMIN")
  field(LNK1, "QUAD:IN10:525:BMAGX.HOPR")
  field(LNK2, "QUAD:IN10:525:BMAGY.HOPR")
  field(LNK3, "QUAD:IN10:525:BLEM.HOPR")
  field(LNK4, "QUAD:IN10:525:BMAGX.LOPR PP")
  field(LNK5, "QUAD:IN10:525:BMAGY.LOPR PP")
  field(LNK6, "QUAD:IN10:525:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "QUAD:IN10:525:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "QUAD:IN10:525:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "QUAD:IN10:525:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "QUAD:IN10:525:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "QUAD:IN10:525:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:525:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:525:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:IN10:525:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:525:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:IN10:525:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "QUAD:IN10:525:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "QUAD:IN10:525:EDES NPP MS")
  field(INPB, "QUAD:IN10:525:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "QUAD:IN10:631:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "QUAD:IN10:631:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "QUAD:IN10:631:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "QUAD:IN10:631:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "QUAD:IN10:631:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "QUAD:IN10:631:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "QUAD:IN10:631:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "QUAD:IN10:631:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "QUAD:IN10:631:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "QUAD:IN10:631:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "QUAD:IN10:631:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "QUAD:IN10:631:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "QUAD:IN10:631:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "QUAD:IN10:631:EDES.PROC PP")
    field(LNK2, "QUAD:IN10:631:EACT.PROC PP")
    field(LNK3, "QUAD:IN10:631:EERR.DISA PP")
    field(LNK4, "QUAD:IN10:631:ECON.PROC PP")
    field(LNK5, "QUAD:IN10:631:BMAGX.PROC PP")
    field(LNK6, "QUAD:IN10:631:BMAGY.PROC PP")
    field(LNK7, "QUAD:IN10:631:BLEM.PROC PP")
    field(LNK8, "QUAD:IN10:631:BMOD.PROC PP")
    field(LNK9, "QUAD:IN10:631:EDESSAVE.PROC PP")
    field(LNKA, "QUAD:IN10:631:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"QUAD:IN10:631:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "QUAD:IN10:631:BMAX")
  field(DOL2, "QUAD:IN10:631:BMAX")
  field(DOL3, "QUAD:IN10:631:BMAX")
  field(DOL4, "QUAD:IN10:631:BMIN")
  field(DOL5, "QUAD:IN10:631:BMIN")
  field(DOL6, "QUAD:IN10:631:BMIN")
  field(LNK1, "QUAD:IN10:631:BMAGX.HOPR")
  field(LNK2, "QUAD:IN10:631:BMAGY.HOPR")
  field(LNK3, "QUAD:IN10:631:BLEM.HOPR")
  field(LNK4, "QUAD:IN10:631:BMAGX.LOPR PP")
  field(LNK5, "QUAD:IN10:631:BMAGY.LOPR PP")
  field(LNK6, "QUAD:IN10:631:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "QUAD:IN10:631:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "QUAD:IN10:631:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "QUAD:IN10:631:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "QUAD:IN10:631:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "QUAD:IN10:631:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:631:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:631:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:IN10:631:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:631:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:IN10:631:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "QUAD:IN10:631:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "QUAD:IN10:631:EDES NPP MS")
  field(INPB, "QUAD:IN10:631:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "QUAD:IN10:651:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "QUAD:IN10:651:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "QUAD:IN10:651:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "QUAD:IN10:651:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "QUAD:IN10:651:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "QUAD:IN10:651:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "QUAD:IN10:651:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "QUAD:IN10:651:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "QUAD:IN10:651:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "QUAD:IN10:651:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "QUAD:IN10:651:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "QUAD:IN10:651:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "QUAD:IN10:651:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "QUAD:IN10:651:EDES.PROC PP")
    field(LNK2, "QUAD:IN10:651:EACT.PROC PP")
    field(LNK3, "QUAD:IN10:651:EERR.DISA PP")
    field(LNK4, "QUAD:IN10:651:ECON.PROC PP")
    field(LNK5, "QUAD:IN10:651:BMAGX.PROC PP")
    field(LNK6, "QUAD:IN10:651:BMAGY.PROC PP")
    field(LNK7, "QUAD:IN10:651:BLEM.PROC PP")
    field(LNK8, "QUAD:IN10:651:BMOD.PROC PP")
    field(LNK9, "QUAD:IN10:651:EDESSAVE.PROC PP")
    field(LNKA, "QUAD:IN10:651:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"QUAD:IN10:651:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "QUAD:IN10:651:BMAX")
  field(DOL2, "QUAD:IN10:651:BMAX")
  field(DOL3, "QUAD:IN10:651:BMAX")
  field(DOL4, "QUAD:IN10:651:BMIN")
  field(DOL5, "QUAD:IN10:651:BMIN")
  field(DOL6, "QUAD:IN10:651:BMIN")
  field(LNK1, "QUAD:IN10:651:BMAGX.HOPR")
  field(LNK2, "QUAD:IN10:651:BMAGY.HOPR")
  field(LNK3, "QUAD:IN10:651:BLEM.HOPR")
  field(LNK4, "QUAD:IN10:651:BMAGX.LOPR PP")
  field(LNK5, "QUAD:IN10:651:BMAGY.LOPR PP")
  field(LNK6, "QUAD:IN10:651:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "QUAD:IN10:651:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "QUAD:IN10:651:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "QUAD:IN10:651:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "QUAD:IN10:651:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "QUAD:IN10:651:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:651:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:651:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:IN10:651:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:651:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:IN10:651:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "QUAD:IN10:651:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "QUAD:IN10:651:EDES NPP MS")
  field(INPB, "QUAD:IN10:651:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "QUAD:IN10:731:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "QUAD:IN10:731:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "QUAD:IN10:731:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "QUAD:IN10:731:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "QUAD:IN10:731:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "QUAD:IN10:731:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "QUAD:IN10:731:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "QUAD:IN10:731:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "QUAD:IN10:731:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "QUAD:IN10:731:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "QUAD:IN10:731:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "QUAD:IN10:731:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "QUAD:IN10:731:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "QUAD:IN10:731:EDES.PROC PP")
    field(LNK2, "QUAD:IN10:731:EACT.PROC PP")
    field(LNK3, "QUAD:IN10:731:EERR.DISA PP")
    field(LNK4, "QUAD:IN10:731:ECON.PROC PP")
    field(LNK5, "QUAD:IN10:731:BMAGX.PROC PP")
    field(LNK6, "QUAD:IN10:731:BMAGY.PROC PP")
    field(LNK7, "QUAD:IN10:731:BLEM.PROC PP")
    field(LNK8, "QUAD:IN10:731:BMOD.PROC PP")
    field(LNK9, "QUAD:IN10:731:EDESSAVE.PROC PP")
    field(LNKA, "QUAD:IN10:731:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"QUAD:IN10:731:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "QUAD:IN10:731:BMAX")
  field(DOL2, "QUAD:IN10:731:BMAX")
  field(DOL3, "QUAD:IN10:731:BMAX")
  field(DOL4, "QUAD:IN10:731:BMIN")
  field(DOL5, "QUAD:IN10:731:BMIN")
  field(DOL6, "QUAD:IN10:731:BMIN")
  field(LNK1, "QUAD:IN10:731:BMAGX.HOPR")
  field(LNK2, "QUAD:IN10:731:BMAGY.HOPR")
  field(LNK3, "QUAD:IN10:731:BLEM.HOPR")
  field(LNK4, "QUAD:IN10:731:BMAGX.LOPR PP")
  field(LNK5, "QUAD:IN10:731:BMAGY.LOPR PP")
  field(LNK6, "QUAD:IN10:731:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "QUAD:IN10:731:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "QUAD:IN10:731:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "QUAD:IN10:731:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "QUAD:IN10:731:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "QUAD:IN10:731:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:731:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:731:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:IN10:731:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:731:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:IN10:731:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "QUAD:IN10:731:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "QUAD:IN10:731:EDES NPP MS")
  field(INPB, "QUAD:IN10:731:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "QUAD:IN10:771:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "QUAD:IN10:771:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "QUAD:IN10:771:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "QUAD:IN10:771:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "QUAD:IN10:771:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "QUAD:IN10:771:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "QUAD:IN10:771:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "QUAD:IN10:771:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "QUAD:IN10:771:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "QUAD:IN10:771:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "QUAD:IN10:771:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "QUAD:IN10:771:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "QUAD:IN10:771:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "QUAD:IN10:771:EDES.PROC PP")
    field(LNK2, "QUAD:IN10:771:EACT.PROC PP")
    field(LNK3, "QUAD:IN10:771:EERR.DISA PP")
    field(LNK4, "QUAD:IN10:771:ECON.PROC PP")
    field(LNK5, "QUAD:IN10:771:BMAGX.PROC PP")
    field(LNK6, "QUAD:IN10:771:BMAGY.PROC PP")
    field(LNK7, "QUAD:IN10:771:BLEM.PROC PP")
    field(LNK8, "QUAD:IN10:771:BMOD.PROC PP")
    field(LNK9, "QUAD:IN10:771:EDESSAVE.PROC PP")
    field(LNKA, "QUAD:IN10:771:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"QUAD:IN10:771:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "QUAD:IN10:771:BMAX")
  field(DOL2, "QUAD:IN10:771:BMAX")
  field(DOL3, "QUAD:IN10:771:BMAX")
  field(DOL4, "QUAD:IN10:771:BMIN")
  field(DOL5, "QUAD:IN10:771:BMIN")
  field(DOL6, "QUAD:IN10:771:BMIN")
  field(LNK1, "QUAD:IN10:771:BMAGX.HOPR")
  field(LNK2, "QUAD:IN10:771:BMAGY.HOPR")
  field(LNK3, "QUAD:IN10:771:BLEM.HOPR")
  field(LNK4, "QUAD:IN10:771:BMAGX.LOPR PP")
  field(LNK5, "QUAD:IN10:771:BMAGY.LOPR PP")
  field(LNK6, "QUAD:IN10:771:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "QUAD:IN10:771:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "QUAD:IN10:771:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "QUAD:IN10:771:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "QUAD:IN10:771:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "QUAD:IN10:771:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:771:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:771:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:IN10:771:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:771:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:IN10:771:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "QUAD:IN10:771:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "QUAD:IN10:771:EDES NPP MS")
  field(INPB, "QUAD:IN10:771:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "QUAD:IN10:781:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "QUAD:IN10:781:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "QUAD:IN10:781:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "QUAD:IN10:781:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "QUAD:IN10:781:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "QUAD:IN10:781:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "QUAD:IN10:781:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "QUAD:IN10:781:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "QUAD:IN10:781:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "QUAD:IN10:781:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "QUAD:IN10:781:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "QUAD:IN10:781:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "QUAD:IN10:781:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "QUAD:IN10:781:EDES.PROC PP")
    field(LNK2, "QUAD:IN10:781:EACT.PROC PP")
    field(LNK3, "QUAD:IN10:781:EERR.DISA PP")
    field(LNK4, "QUAD:IN10:781:ECON.PROC PP")
    field(LNK5, "QUAD:IN10:781:BMAGX.PROC PP")
    field(LNK6, "QUAD:IN10:781:BMAGY.PROC PP")
    field(LNK7, "QUAD:IN10:781:BLEM.PROC PP")
    field(LNK8, "QUAD:IN10:781:BMOD.PROC PP")
    field(LNK9, "QUAD:IN10:781:EDESSAVE.PROC PP")
    field(LNKA, "QUAD:IN10:781:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"QUAD:IN10:781:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "QUAD:IN10:781:BMAX")
  field(DOL2, "QUAD:IN10:781:BMAX")
  field(DOL3, "QUAD:IN10:781:BMAX")
  field(DOL4, "QUAD:IN10:781:BMIN")
  field(DOL5, "QUAD:IN10:781:BMIN")
  field(DOL6, "QUAD:IN10:781:BMIN")
  field(LNK1, "QUAD:IN10:781:BMAGX.HOPR")
  field(LNK2, "QUAD:IN10:781:BMAGY.HOPR")
  field(LNK3, "QUAD:IN10:781:BLEM.HOPR")
  field(LNK4, "QUAD:IN10:781:BMAGX.LOPR PP")
  field(LNK5, "QUAD:IN10:781:BMAGY.LOPR PP")
  field(LNK6, "QUAD:IN10:781:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "QUAD:IN10:781:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "QUAD:IN10:781:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "QUAD:IN10:781:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "QUAD:IN10:781:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "QUAD:IN10:781:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:781:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:781:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:IN10:781:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:IN10:781:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:IN10:781:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "QUAD:IN10:781:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "QUAD:IN10:781:EDES NPP MS")
  field(INPB, "QUAD:IN10:781:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "XCOR:IN10:121:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "XCOR:IN10:121:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "XCOR:IN10:121:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "XCOR:IN10:121:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "XCOR:IN10:121:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "XCOR:IN10:121:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "XCOR:IN10:121:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "XCOR:IN10:121:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "XCOR:IN10:121:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "XCOR:IN10:121:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "XCOR:IN10:121:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "XCOR:IN10:121:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "XCOR:IN10:121:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "XCOR:IN10:121:EDES.PROC PP")
    field(LNK2, "XCOR:IN10:121:EACT.PROC PP")
    field(LNK3, "XCOR:IN10:121:EERR.DISA PP")
    field(LNK4, "XCOR:IN10:121:ECON.PROC PP")
    field(LNK5, "XCOR:IN10:121:BMAGX.PROC PP")
    field(LNK6, "XCOR:IN10:121:BMAGY.PROC PP")
    field(LNK7, "XCOR:IN10:121:BLEM.PROC PP")
    field(LNK8, "XCOR:IN10:121:BMOD.PROC PP")
    field(LNK9, "XCOR:IN10:121:EDESSAVE.PROC PP")
    field(LNKA, "XCOR:IN10:121:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"XCOR:IN10:121:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "XCOR:IN10:121:BMAX")
  field(DOL2, "XCOR:IN10:121:BMAX")
  field(DOL3, "XCOR:IN10:121:BMAX")
  field(DOL4, "XCOR:IN10:121:BMIN")
  field(DOL5, "XCOR:IN10:121:BMIN")
  field(DOL6, "XCOR:IN10:121:BMIN")
  field(LNK1, "XCOR:IN10:121:BMAGX.HOPR")
  field(LNK2, "XCOR:IN10:121:BMAGY.HOPR")
  field(LNK3, "XCOR:IN10:121:BLEM.HOPR")
  field(LNK4, "XCOR:IN10:121:BMAGX.LOPR PP")
  field(LNK5, "XCOR:IN10:121:BMAGY.LOPR PP")
  field(LNK6, "XCOR:IN10:121:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "XCOR:IN10:121:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "XCOR:IN10:121:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "XCOR:IN10:121:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "XCOR:IN10:121:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "XCOR:IN10:121:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:IN10:121:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:IN10:121:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "XCOR:IN10:121:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:IN10:121:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "XCOR:IN10:121:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "XCOR:IN10:121:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "XCOR:IN10:121:EDES NPP MS")
  field(INPB, "XCOR:IN10:121:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "XCOR:IN10:221:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "XCOR:IN10:221:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "XCOR:IN10:221:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "XCOR:IN10:221:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "XCOR:IN10:221:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "XCOR:IN10:221:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "XCOR:IN10:221:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "XCOR:IN10:221:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "XCOR:IN10:221:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "XCOR:IN10:221:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "XCOR:IN10:221:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "XCOR:IN10:221:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "XCOR:IN10:221:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "XCOR:IN10:221:EDES.PROC PP")
    field(LNK2, "XCOR:IN10:221:EACT.PROC PP")
    field(LNK3, "XCOR:IN10:221:EERR.DISA PP")
    field(LNK4, "XCOR:IN10:221:ECON.PROC PP")
    field(LNK5, "XCOR:IN10:221:BMAGX.PROC PP")
    field(LNK6, "XCOR:IN10:221:BMAGY.PROC PP")
    field(LNK7, "XCOR:IN10:221:BLEM.PROC PP")
    field(LNK8, "XCOR:IN10:221:BMOD.PROC PP")
    field(LNK9, "XCOR:IN10:221:EDESSAVE.PROC PP")
    field(LNKA, "XCOR:IN10:221:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"XCOR:IN10:221:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "XCOR:IN10:221:BMAX")
  field(DOL2, "XCOR:IN10:221:BMAX")
  field(DOL3, "XCOR:IN10:221:BMAX")
  field(DOL4, "XCOR:IN10:221:BMIN")
  field(DOL5, "XCOR:IN10:221:BMIN")
  field(DOL6, "XCOR:IN10:221:BMIN")
  field(LNK1, "XCOR:IN10:221:BMAGX.HOPR")
  field(LNK2, "XCOR:IN10:221:BMAGY.HOPR")
  field(LNK3, "XCOR:IN10:221:BLEM.HOPR")
  field(LNK4, "XCOR:IN10:221:BMAGX.LOPR PP")
  field(LNK5, "XCOR:IN10:221:BMAGY.LOPR PP")
  field(LNK6, "XCOR:IN10:221:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "XCOR:IN10:221:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "XCOR:IN10:221:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "XCOR:IN10:221:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "XCOR:IN10:221:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "XCOR:IN10:221:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:IN10:221:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:IN10:221:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "XCOR:IN10:221:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:IN10:221:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "XCOR:IN10:221:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "XCOR:IN10:221:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "XCOR:IN10:221:EDES NPP MS")
  field(INPB, "XCOR:IN10:221:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "XCOR:IN10:311:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "XCOR:IN10:311:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "XCOR:IN10:311:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "XCOR:IN10:311:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "XCOR:IN10:311:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "XCOR:IN10:311:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "XCOR:IN10:311:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "XCOR:IN10:311:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "XCOR:IN10:311:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "XCOR:IN10:311:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "XCOR:IN10:311:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "XCOR:IN10:311:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "XCOR:IN10:311:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "XCOR:IN10:311:EDES.PROC PP")
    field(LNK2, "XCOR:IN10:311:EACT.PROC PP")
    field(LNK3, "XCOR:IN10:311:EERR.DISA PP")
    field(LNK4, "XCOR:IN10:311:ECON.PROC PP")
    field(LNK5, "XCOR:IN10:311:BMAGX.PROC PP")
    field(LNK6, "XCOR:IN10:311:BMAGY.PROC PP")
    field(LNK7, "XCOR:IN10:311:BLEM.PROC PP")
    field(LNK8, "XCOR:IN10:311:BMOD.PROC PP")
    field(LNK9, "XCOR:IN10:311:EDESSAVE.PROC PP")
    field(LNKA, "XCOR:IN10:311:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"XCOR:IN10:311:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "XCOR:IN10:311:BMAX")
  field(DOL2, "XCOR:IN10:311:BMAX")
  field(DOL3, "XCOR:IN10:311:BMAX")
  field(DOL4, "XCOR:IN10:311:BMIN")
  field(DOL5, "XCOR:IN10:311:BMIN")
  field(DOL6, "XCOR:IN10:311:BMIN")
  field(LNK1, "XCOR:IN10:311:BMAGX.HOPR")
  field(LNK2, "XCOR:IN10:311:BMAGY.HOPR")
  field(LNK3, "XCOR:IN10:311:BLEM.HOPR")
  field(LNK4, "XCOR:IN10:311:BMAGX.LOPR PP")
  field(LNK5, "XCOR:IN10:311:BMAGY.LOPR PP")
  field(LNK6, "XCOR:IN10:311:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "XCOR:IN10:311:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "XCOR:IN10:311:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "XCOR:IN10:311:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "XCOR:IN10:311:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "XCOR:IN10:311:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:IN10:311:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:IN10:311:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "XCOR:IN10:311:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:IN10:311:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "XCOR:IN10:311:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "XCOR:IN10:311:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "XCOR:IN10:311:EDES NPP MS")
  field(INPB, "XCOR:IN10:311:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "XCOR:IN10:381:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "XCOR:IN10:381:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "XCOR:IN10:381:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "XCOR:IN10:381:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "XCOR:IN10:381:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "XCOR:IN10:381:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "XCOR:IN10:381:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "XCOR:IN10:381:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "XCOR:IN10:381:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "XCOR:IN10:381:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "XCOR:IN10:381:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "XCOR:IN10:381:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "XCOR:IN10:381:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "XCOR:IN10:381:EDES.PROC PP")
    field(LNK2, "XCOR:IN10:381:EACT.PROC PP")
    field(LNK3, "XCOR:IN10:381:EERR.DISA PP")
    field(LNK4, "XCOR:IN10:381:ECON.PROC PP")
    field(LNK5, "XCOR:IN10:381:BMAGX.PROC PP")
    field(LNK6, "XCOR:IN10:381:BMAGY.PROC PP")
    field(LNK7, "XCOR:IN10:381:BLEM.PROC PP")
    field(LNK8, "XCOR:IN10:381:BMOD.PROC PP")
    field(LNK9, "XCOR:IN10:381:EDESSAVE.PROC PP")
    field(LNKA, "XCOR:IN10:381:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"XCOR:IN10:381:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "XCOR:IN10:381:BMAX")
  field(DOL2, "XCOR:IN10:381:BMAX")
  field(DOL3, "XCOR:IN10:381:BMAX")
  field(DOL4, "XCOR:IN10:381:BMIN")
  field(DOL5, "XCOR:IN10:381:BMIN")
  field(DOL6, "XCOR:IN10:381:BMIN")
  field(LNK1, "XCOR:IN10:381:BMAGX.HOPR")
  field(LNK2, "XCOR:IN10:381:BMAGY.HOPR")
  field(LNK3, "XCOR:IN10:381:BLEM.HOPR")
  field(LNK4, "XCOR:IN10:381:BMAGX.LOPR PP")
  field(LNK5, "XCOR:IN10:381:BMAGY.LOPR PP")
  field(LNK6, "XCOR:IN10:381:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "XCOR:IN10:381:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "XCOR:IN10:381:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "XCOR:IN10:381:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "XCOR:IN10:381:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "XCOR:IN10:381:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:IN10:381:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:IN10:381:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "XCOR:IN10:381:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:IN10:381:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "XCOR:IN10:381:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "XCOR:IN10:381:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "XCOR:IN10:381:EDES NPP MS")
  field(INPB, "XCOR:IN10:381:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "XCOR:IN10:411:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "XCOR:IN10:411:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "XCOR:IN10:411:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "XCOR:IN10:411:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "XCOR:IN10:411:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "XCOR:IN10:411:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "XCOR:IN10:411:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "XCOR:IN10:411:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "XCOR:IN10:411:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "XCOR:IN10:411:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "XCOR:IN10:411:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "XCOR:IN10:411:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "XCOR:IN10:411:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "XCOR:IN10:411:EDES.PROC PP")
    field(LNK2, "XCOR:IN10:411:EACT.PROC PP")
    field(LNK3, "XCOR:IN10:411:EERR.DISA PP")
    field(LNK4, "XCOR:IN10:411:ECON.PROC PP")
    field(LNK5, "XCOR:IN10:411:BMAGX.PROC PP")
    field(LNK6, "XCOR:IN10:411:BMAGY.PROC PP")
    field(LNK7, "XCOR:IN10:411:BLEM.PROC PP")
    field(LNK8, "XCOR:IN10:411:BMOD.PROC PP")
    field(LNK9, "XCOR:IN10:411:EDESSAVE.PROC PP")
    field(LNKA, "XCOR:IN10:411:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"XCOR:IN10:411:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "XCOR:IN10:411:BMAX")
  field(DOL2, "XCOR:IN10:411:BMAX")
  field(DOL3, "XCOR:IN10:411:BMAX")
  field(DOL4, "XCOR:IN10:411:BMIN")
  field(DOL5, "XCOR:IN10:411:BMIN")
  field(DOL6, "XCOR:IN10:411:BMIN")
  field(LNK1, "XCOR:IN10:411:BMAGX.HOPR")
  field(LNK2, "XCOR:IN10:411:BMAGY.HOPR")
  field(LNK3, "XCOR:IN10:411:BLEM.HOPR")
  field(LNK4, "XCOR:IN10:411:BMAGX.LOPR PP")
  field(LNK5, "XCOR:IN10:411:BMAGY.LOPR PP")
  field(LNK6, "XCOR:IN10:411:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "XCOR:IN10:411:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "XCOR:IN10:411:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "XCOR:IN10:411:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "XCOR:IN10:411:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "XCOR:IN10:411:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:IN10:411:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:IN10:411:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "XCOR:IN10:411:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:IN10:411:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "XCOR:IN10:411:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "XCOR:IN10:411:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "XCOR:IN10:411:EDES NPP MS")
  field(INPB, "XCOR:IN10:411:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "XCOR:IN10:491:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "XCOR:IN10:491:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "XCOR:IN10:491:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "XCOR:IN10:491:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "XCOR:IN10:491:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "XCOR:IN10:491:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "XCOR:IN10:491:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "XCOR:IN10:491:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "XCOR:IN10:491:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "XCOR:IN10:491:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "XCOR:IN10:491:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "XCOR:IN10:491:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "XCOR:IN10:491:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "XCOR:IN10:491:EDES.PROC PP")
    field(LNK2, "XCOR:IN10:491:EACT.PROC PP")
    field(LNK3, "XCOR:IN10:491:EERR.DISA PP")
    field(LNK4, "XCOR:IN10:491:ECON.PROC PP")
    field(LNK5, "XCOR:IN10:491:BMAGX.PROC PP")
    field(LNK6, "XCOR:IN10:491:BMAGY.PROC PP")
    field(LNK7, "XCOR:IN10:491:BLEM.PROC PP")
    field(LNK8, "XCOR:IN10:491:BMOD.PROC PP")
    field(LNK9, "XCOR:IN10:491:EDESSAVE.PROC PP")
    field(LNKA, "XCOR:IN10:491:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"XCOR:IN10:491:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "XCOR:IN10:491:BMAX")
  field(DOL2, "XCOR:IN10:491:BMAX")
  field(DOL3, "XCOR:IN10:491:BMAX")
  field(DOL4, "XCOR:IN10:491:BMIN")
  field(DOL5, "XCOR:IN10:491:BMIN")
  field(DOL6, "XCOR:IN10:491:BMIN")
  field(LNK1, "XCOR:IN10:491:BMAGX.HOPR")
  field(LNK2, "XCOR:IN10:491:BMAGY.HOPR")
  field(LNK3, "XCOR:IN10:491:BLEM.HOPR")
  field(LNK4, "XCOR:IN10:491:BMAGX.LOPR PP")
  field(LNK5, "XCOR:IN10:491:BMAGY.LOPR PP")
  field(LNK6, "XCOR:IN10:491:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "XCOR:IN10:491:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "XCOR:IN10:491:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "XCOR:IN10:491:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "XCOR:IN10:491:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "XCOR:IN10:491:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:IN10:491:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:IN10:491:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "XCOR:IN10:491:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:IN10:491:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "XCOR:IN10:491:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "XCOR:IN10:491:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "XCOR:IN10:491:EDES NPP MS")
  field(INPB, "XCOR:IN10:491:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "XCOR:IN10:521:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "XCOR:IN10:521:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "XCOR:IN10:521:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "XCOR:IN10:521:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "XCOR:IN10:521:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "XCOR:IN10:521:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "XCOR:IN10:521:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "XCOR:IN10:521:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "XCOR:IN10:521:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "XCOR:IN10:521:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "XCOR:IN10:521:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "XCOR:IN10:521:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "XCOR:IN10:521:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "XCOR:IN10:521:EDES.PROC PP")
    field(LNK2, "XCOR:IN10:521:EACT.PROC PP")
    field(LNK3, "XCOR:IN10:521:EERR.DISA PP")
    field(LNK4, "XCOR:IN10:521:ECON.PROC PP")
    field(LNK5, "XCOR:IN10:521:BMAGX.PROC PP")
    field(LNK6, "XCOR:IN10:521:BMAGY.PROC PP")
    field(LNK7, "XCOR:IN10:521:BLEM.PROC PP")
    field(LNK8, "XCOR:IN10:521:BMOD.PROC PP")
    field(LNK9, "XCOR:IN10:521:EDESSAVE.PROC PP")
    field(LNKA, "XCOR:IN10:521:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"XCOR:IN10:521:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "XCOR:IN10:521:BMAX")
  field(DOL2, "XCOR:IN10:521:BMAX")
  field(DOL3, "XCOR:IN10:521:BMAX")
  field(DOL4, "XCOR:IN10:521:BMIN")
  field(DOL5, "XCOR:IN10:521:BMIN")
  field(DOL6, "XCOR:IN10:521:BMIN")
  field(LNK1, "XCOR:IN10:521:BMAGX.HOPR")
  field(LNK2, "XCOR:IN10:521:BMAGY.HOPR")
  field(LNK3, "XCOR:IN10:521:BLEM.HOPR")
  field(LNK4, "XCOR:IN10:521:BMAGX.LOPR PP")
  field(LNK5, "XCOR:IN10:521:BMAGY.LOPR PP")
  field(LNK6, "XCOR:IN10:521:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "XCOR:IN10:521:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "XCOR:IN10:521:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "XCOR:IN10:521:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "XCOR:IN10:521:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "XCOR:IN10:521:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:IN10:521:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:IN10:521:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "XCOR:IN10:521:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:IN10:521:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "XCOR:IN10:521:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "XCOR:IN10:521:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "XCOR:IN10:521:EDES NPP MS")
  field(INPB, "XCOR:IN10:521:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "XCOR:IN10:641:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "XCOR:IN10:641:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "XCOR:IN10:641:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "XCOR:IN10:641:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "XCOR:IN10:641:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "XCOR:IN10:641:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "XCOR:IN10:641:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "XCOR:IN10:641:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "XCOR:IN10:641:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "XCOR:IN10:641:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "XCOR:IN10:641:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "XCOR:IN10:641:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "XCOR:IN10:641:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "XCOR:IN10:641:EDES.PROC PP")
    field(LNK2, "XCOR:IN10:641:EACT.PROC PP")
    field(LNK3, "XCOR:IN10:641:EERR.DISA PP")
    field(LNK4, "XCOR:IN10:641:ECON.PROC PP")
    field(LNK5, "XCOR:IN10:641:BMAGX.PROC PP")
    field(LNK6, "XCOR:IN10:641:BMAGY.PROC PP")
    field(LNK7, "XCOR:IN10:641:BLEM.PROC PP")
    field(LNK8, "XCOR:IN10:641:BMOD.PROC PP")
    field(LNK9, "XCOR:IN10:641:EDESSAVE.PROC PP")
    field(LNKA, "XCOR:IN10:641:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"XCOR:IN10:641:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "XCOR:IN10:641:BMAX")
  field(DOL2, "XCOR:IN10:641:BMAX")
  field(DOL3, "XCOR:IN10:641:BMAX")
  field(DOL4, "XCOR:IN10:641:BMIN")
  field(DOL5, "XCOR:IN10:641:BMIN")
  field(DOL6, "XCOR:IN10:641:BMIN")
  field(LNK1, "XCOR:IN10:641:BMAGX.HOPR")
  field(LNK2, "XCOR:IN10:641:BMAGY.HOPR")
  field(LNK3, "XCOR:IN10:641:BLEM.HOPR")
  field(LNK4, "XCOR:IN10:641:BMAGX.LOPR PP")
  field(LNK5, "XCOR:IN10:641:BMAGY.LOPR PP")
  field(LNK6, "XCOR:IN10:641:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "XCOR:IN10:641:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "XCOR:IN10:641:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "XCOR:IN10:641:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "XCOR:IN10:641:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "XCOR:IN10:641:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:IN10:641:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:IN10:641:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "XCOR:IN10:641:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:IN10:641:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "XCOR:IN10:641:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "XCOR:IN10:641:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "XCOR:IN10:641:EDES NPP MS")
  field(INPB, "XCOR:IN10:641:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "XCOR:IN10:721:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "XCOR:IN10:721:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "XCOR:IN10:721:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "XCOR:IN10:721:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "XCOR:IN10:721:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "XCOR:IN10:721:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "XCOR:IN10:721:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "XCOR:IN10:721:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "XCOR:IN10:721:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "XCOR:IN10:721:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "XCOR:IN10:721:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "XCOR:IN10:721:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "XCOR:IN10:721:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "XCOR:IN10:721:EDES.PROC PP")
    field(LNK2, "XCOR:IN10:721:EACT.PROC PP")
    field(LNK3, "XCOR:IN10:721:EERR.DISA PP")
    field(LNK4, "XCOR:IN10:721:ECON.PROC PP")
    field(LNK5, "XCOR:IN10:721:BMAGX.PROC PP")
    field(LNK6, "XCOR:IN10:721:BMAGY.PROC PP")
    field(LNK7, "XCOR:IN10:721:BLEM.PROC PP")
    field(LNK8, "XCOR:IN10:721:BMOD.PROC PP")
    field(LNK9, "XCOR:IN10:721:EDESSAVE.PROC PP")
    field(LNKA, "XCOR:IN10:721:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"XCOR:IN10:721:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "XCOR:IN10:721:BMAX")
  field(DOL2, "XCOR:IN10:721:BMAX")
  field(DOL3, "XCOR:IN10:721:BMAX")
  field(DOL4, "XCOR:IN10:721:BMIN")
  field(DOL5, "XCOR:IN10:721:BMIN")
  field(DOL6, "XCOR:IN10:721:BMIN")
  field(LNK1, "XCOR:IN10:721:BMAGX.HOPR")
  field(LNK2, "XCOR:IN10:721:BMAGY.HOPR")
  field(LNK3, "XCOR:IN10:721:BLEM.HOPR")
  field(LNK4, "XCOR:IN10:721:BMAGX.LOPR PP")
  field(LNK5, "XCOR:IN10:721:BMAGY.LOPR PP")
  field(LNK6, "XCOR:IN10:721:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "XCOR:IN10:721:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "XCOR:IN10:721:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "XCOR:IN10:721:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "XCOR:IN10:721:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "XCOR:IN10:721:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:IN10:721:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:IN10:721:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "XCOR:IN10:721:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:IN10:721:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "XCOR:IN10:721:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "XCOR:IN10:721:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "XCOR:IN10:721:EDES NPP MS")
  field(INPB, "XCOR:IN10:721:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "XCOR:IN10:761:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "XCOR:IN10:761:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "XCOR:IN10:761:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "XCOR:IN10:761:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "XCOR:IN10:761:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "XCOR:IN10:761:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "XCOR:IN10:761:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "XCOR:IN10:761:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "XCOR:IN10:761:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "XCOR:IN10:761:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "XCOR:IN10:761:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "XCOR:IN10:761:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "XCOR:IN10:761:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "XCOR:IN10:761:EDES.PROC PP")
    field(LNK2, "XCOR:IN10:761:EACT.PROC PP")
    field(LNK3, "XCOR:IN10:761:EERR.DISA PP")
    field(LNK4, "XCOR:IN10:761:ECON.PROC PP")
    field(LNK5, "XCOR:IN10:761:BMAGX.PROC PP")
    field(LNK6, "XCOR:IN10:761:BMAGY.PROC PP")
    field(LNK7, "XCOR:IN10:761:BLEM.PROC PP")
    field(LNK8, "XCOR:IN10:761:BMOD.PROC PP")
    field(LNK9, "XCOR:IN10:761:EDESSAVE.PROC PP")
    field(LNKA, "XCOR:IN10:761:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"XCOR:IN10:761:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "XCOR:IN10:761:BMAX")
  field(DOL2, "XCOR:IN10:761:BMAX")
  field(DOL3, "XCOR:IN10:761:BMAX")
  field(DOL4, "XCOR:IN10:761:BMIN")
  field(DOL5, "XCOR:IN10:761:BMIN")
  field(DOL6, "XCOR:IN10:761:BMIN")
  field(LNK1, "XCOR:IN10:761:BMAGX.HOPR")
  field(LNK2, "XCOR:IN10:761:BMAGY.HOPR")
  field(LNK3, "XCOR:IN10:761:BLEM.HOPR")
  field(LNK4, "XCOR:IN10:761:BMAGX.LOPR PP")
  field(LNK5, "XCOR:IN10:761:BMAGY.LOPR PP")
  field(LNK6, "XCOR:IN10:761:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "XCOR:IN10:761:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "XCOR:IN10:761:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "XCOR:IN10:761:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "XCOR:IN10:761:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "XCOR:IN10:761:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:IN10:761:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:IN10:761:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "XCOR:IN10:761:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:IN10:761:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "XCOR:IN10:761:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "XCOR:IN10:761:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "XCOR:IN10:761:EDES NPP MS")
  field(INPB, "XCOR:IN10:761:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "YCOR:IN10:122:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "YCOR:IN10:122:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "YCOR:IN10:122:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "YCOR:IN10:122:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "YCOR:IN10:122:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "YCOR:IN10:122:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "YCOR:IN10:122:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "YCOR:IN10:122:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "YCOR:IN10:122:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "YCOR:IN10:122:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "YCOR:IN10:122:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "YCOR:IN10:122:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "YCOR:IN10:122:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "YCOR:IN10:122:EDES.PROC PP")
    field(LNK2, "YCOR:IN10:122:EACT.PROC PP")
    field(LNK3, "YCOR:IN10:122:EERR.DISA PP")
    field(LNK4, "YCOR:IN10:122:ECON.PROC PP")
    field(LNK5, "YCOR:IN10:122:BMAGX.PROC PP")
    field(LNK6, "YCOR:IN10:122:BMAGY.PROC PP")
    field(LNK7, "YCOR:IN10:122:BLEM.PROC PP")
    field(LNK8, "YCOR:IN10:122:BMOD.PROC PP")
    field(LNK9, "YCOR:IN10:122:EDESSAVE.PROC PP")
    field(LNKA, "YCOR:IN10:122:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"YCOR:IN10:122:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "YCOR:IN10:122:BMAX")
  field(DOL2, "YCOR:IN10:122:BMAX")
  field(DOL3, "YCOR:IN10:122:BMAX")
  field(DOL4, "YCOR:IN10:122:BMIN")
  field(DOL5, "YCOR:IN10:122:BMIN")
  field(DOL6, "YCOR:IN10:122:BMIN")
  field(LNK1, "YCOR:IN10:122:BMAGX.HOPR")
  field(LNK2, "YCOR:IN10:122:BMAGY.HOPR")
  field(LNK3, "YCOR:IN10:122:BLEM.HOPR")
  field(LNK4, "YCOR:IN10:122:BMAGX.LOPR PP")
  field(LNK5, "YCOR:IN10:122:BMAGY.LOPR PP")
  field(LNK6, "YCOR:IN10:122:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "YCOR:IN10:122:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "YCOR:IN10:122:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "YCOR:IN10:122:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "YCOR:IN10:122:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "YCOR:IN10:122:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:IN10:122:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:IN10:122:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:IN10:122:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:IN10:122:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:IN10:122:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "YCOR:IN10:122:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "YCOR:IN10:122:EDES NPP MS")
  field(INPB, "YCOR:IN10:122:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "YCOR:IN10:222:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "YCOR:IN10:222:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "YCOR:IN10:222:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "YCOR:IN10:222:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "YCOR:IN10:222:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "YCOR:IN10:222:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "YCOR:IN10:222:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "YCOR:IN10:222:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "YCOR:IN10:222:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "YCOR:IN10:222:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "YCOR:IN10:222:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "YCOR:IN10:222:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "YCOR:IN10:222:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "YCOR:IN10:222:EDES.PROC PP")
    field(LNK2, "YCOR:IN10:222:EACT.PROC PP")
    field(LNK3, "YCOR:IN10:222:EERR.DISA PP")
    field(LNK4, "YCOR:IN10:222:ECON.PROC PP")
    field(LNK5, "YCOR:IN10:222:BMAGX.PROC PP")
    field(LNK6, "YCOR:IN10:222:BMAGY.PROC PP")
    field(LNK7, "YCOR:IN10:222:BLEM.PROC PP")
    field(LNK8, "YCOR:IN10:222:BMOD.PROC PP")
    field(LNK9, "YCOR:IN10:222:EDESSAVE.PROC PP")
    field(LNKA, "YCOR:IN10:222:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"YCOR:IN10:222:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "YCOR:IN10:222:BMAX")
  field(DOL2, "YCOR:IN10:222:BMAX")
  field(DOL3, "YCOR:IN10:222:BMAX")
  field(DOL4, "YCOR:IN10:222:BMIN")
  field(DOL5, "YCOR:IN10:222:BMIN")
  field(DOL6, "YCOR:IN10:222:BMIN")
  field(LNK1, "YCOR:IN10:222:BMAGX.HOPR")
  field(LNK2, "YCOR:IN10:222:BMAGY.HOPR")
  field(LNK3, "YCOR:IN10:222:BLEM.HOPR")
  field(LNK4, "YCOR:IN10:222:BMAGX.LOPR PP")
  field(LNK5, "YCOR:IN10:222:BMAGY.LOPR PP")
  field(LNK6, "YCOR:IN10:222:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "YCOR:IN10:222:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "YCOR:IN10:222:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "YCOR:IN10:222:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "YCOR:IN10:222:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "YCOR:IN10:222:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:IN10:222:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:IN10:222:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:IN10:222:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:IN10:222:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:IN10:222:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "YCOR:IN10:222:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "YCOR:IN10:222:EDES NPP MS")
  field(INPB, "YCOR:IN10:222:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "YCOR:IN10:312:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "YCOR:IN10:312:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "YCOR:IN10:312:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "YCOR:IN10:312:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "YCOR:IN10:312:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "YCOR:IN10:312:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "YCOR:IN10:312:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "YCOR:IN10:312:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "YCOR:IN10:312:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "YCOR:IN10:312:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "YCOR:IN10:312:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "YCOR:IN10:312:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "YCOR:IN10:312:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "YCOR:IN10:312:EDES.PROC PP")
    field(LNK2, "YCOR:IN10:312:EACT.PROC PP")
    field(LNK3, "YCOR:IN10:312:EERR.DISA PP")
    field(LNK4, "YCOR:IN10:312:ECON.PROC PP")
    field(LNK5, "YCOR:IN10:312:BMAGX.PROC PP")
    field(LNK6, "YCOR:IN10:312:BMAGY.PROC PP")
    field(LNK7, "YCOR:IN10:312:BLEM.PROC PP")
    field(LNK8, "YCOR:IN10:312:BMOD.PROC PP")
    field(LNK9, "YCOR:IN10:312:EDESSAVE.PROC PP")
    field(LNKA, "YCOR:IN10:312:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"YCOR:IN10:312:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "YCOR:IN10:312:BMAX")
  field(DOL2, "YCOR:IN10:312:BMAX")
  field(DOL3, "YCOR:IN10:312:BMAX")
  field(DOL4, "YCOR:IN10:312:BMIN")
  field(DOL5, "YCOR:IN10:312:BMIN")
  field(DOL6, "YCOR:IN10:312:BMIN")
  field(LNK1, "YCOR:IN10:312:BMAGX.HOPR")
  field(LNK2, "YCOR:IN10:312:BMAGY.HOPR")
  field(LNK3, "YCOR:IN10:312:BLEM.HOPR")
  field(LNK4, "YCOR:IN10:312:BMAGX.LOPR PP")
  field(LNK5, "YCOR:IN10:312:BMAGY.LOPR PP")
  field(LNK6, "YCOR:IN10:312:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "YCOR:IN10:312:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "YCOR:IN10:312:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "YCOR:IN10:312:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "YCOR:IN10:312:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "YCOR:IN10:312:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:IN10:312:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:IN10:312:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:IN10:312:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:IN10:312:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:IN10:312:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "YCOR:IN10:312:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "YCOR:IN10:312:EDES NPP MS")
  field(INPB, "YCOR:IN10:312:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "YCOR:IN10:382:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "YCOR:IN10:382:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "YCOR:IN10:382:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "YCOR:IN10:382:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "YCOR:IN10:382:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "YCOR:IN10:382:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "YCOR:IN10:382:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "YCOR:IN10:382:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "YCOR:IN10:382:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "YCOR:IN10:382:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "YCOR:IN10:382:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "YCOR:IN10:382:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "YCOR:IN10:382:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "YCOR:IN10:382:EDES.PROC PP")
    field(LNK2, "YCOR:IN10:382:EACT.PROC PP")
    field(LNK3, "YCOR:IN10:382:EERR.DISA PP")
    field(LNK4, "YCOR:IN10:382:ECON.PROC PP")
    field(LNK5, "YCOR:IN10:382:BMAGX.PROC PP")
    field(LNK6, "YCOR:IN10:382:BMAGY.PROC PP")
    field(LNK7, "YCOR:IN10:382:BLEM.PROC PP")
    field(LNK8, "YCOR:IN10:382:BMOD.PROC PP")
    field(LNK9, "YCOR:IN10:382:EDESSAVE.PROC PP")
    field(LNKA, "YCOR:IN10:382:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"YCOR:IN10:382:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "YCOR:IN10:382:BMAX")
  field(DOL2, "YCOR:IN10:382:BMAX")
  field(DOL3, "YCOR:IN10:382:BMAX")
  field(DOL4, "YCOR:IN10:382:BMIN")
  field(DOL5, "YCOR:IN10:382:BMIN")
  field(DOL6, "YCOR:IN10:382:BMIN")
  field(LNK1, "YCOR:IN10:382:BMAGX.HOPR")
  field(LNK2, "YCOR:IN10:382:BMAGY.HOPR")
  field(LNK3, "YCOR:IN10:382:BLEM.HOPR")
  field(LNK4, "YCOR:IN10:382:BMAGX.LOPR PP")
  field(LNK5, "YCOR:IN10:382:BMAGY.LOPR PP")
  field(LNK6, "YCOR:IN10:382:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "YCOR:IN10:382:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "YCOR:IN10:382:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "YCOR:IN10:382:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "YCOR:IN10:382:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "YCOR:IN10:382:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:IN10:382:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:IN10:382:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:IN10:382:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:IN10:382:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:IN10:382:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "YCOR:IN10:382:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "YCOR:IN10:382:EDES NPP MS")
  field(INPB, "YCOR:IN10:382:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "YCOR:IN10:412:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "YCOR:IN10:412:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "YCOR:IN10:412:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "YCOR:IN10:412:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "YCOR:IN10:412:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "YCOR:IN10:412:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "YCOR:IN10:412:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "YCOR:IN10:412:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "YCOR:IN10:412:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "YCOR:IN10:412:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "YCOR:IN10:412:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "YCOR:IN10:412:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "YCOR:IN10:412:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "YCOR:IN10:412:EDES.PROC PP")
    field(LNK2, "YCOR:IN10:412:EACT.PROC PP")
    field(LNK3, "YCOR:IN10:412:EERR.DISA PP")
    field(LNK4, "YCOR:IN10:412:ECON.PROC PP")
    field(LNK5, "YCOR:IN10:412:BMAGX.PROC PP")
    field(LNK6, "YCOR:IN10:412:BMAGY.PROC PP")
    field(LNK7, "YCOR:IN10:412:BLEM.PROC PP")
    field(LNK8, "YCOR:IN10:412:BMOD.PROC PP")
    field(LNK9, "YCOR:IN10:412:EDESSAVE.PROC PP")
    field(LNKA, "YCOR:IN10:412:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"YCOR:IN10:412:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "YCOR:IN10:412:BMAX")
  field(DOL2, "YCOR:IN10:412:BMAX")
  field(DOL3, "YCOR:IN10:412:BMAX")
  field(DOL4, "YCOR:IN10:412:BMIN")
  field(DOL5, "YCOR:IN10:412:BMIN")
  field(DOL6, "YCOR:IN10:412:BMIN")
  field(LNK1, "YCOR:IN10:412:BMAGX.HOPR")
  field(LNK2, "YCOR:IN10:412:BMAGY.HOPR")
  field(LNK3, "YCOR:IN10:412:BLEM.HOPR")
  field(LNK4, "YCOR:IN10:412:BMAGX.LOPR PP")
  field(LNK5, "YCOR:IN10:412:BMAGY.LOPR PP")
  field(LNK6, "YCOR:IN10:412:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "YCOR:IN10:412:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "YCOR:IN10:412:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "YCOR:IN10:412:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "YCOR:IN10:412:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "YCOR:IN10:412:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:IN10:412:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:IN10:412:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:IN10:412:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:IN10:412:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:IN10:412:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "YCOR:IN10:412:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "YCOR:IN10:412:EDES NPP MS")
  field(INPB, "YCOR:IN10:412:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "YCOR:IN10:492:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "YCOR:IN10:492:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "YCOR:IN10:492:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "YCOR:IN10:492:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "YCOR:IN10:492:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "YCOR:IN10:492:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "YCOR:IN10:492:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "YCOR:IN10:492:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "YCOR:IN10:492:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "YCOR:IN10:492:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "YCOR:IN10:492:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "YCOR:IN10:492:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "YCOR:IN10:492:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "YCOR:IN10:492:EDES.PROC PP")
    field(LNK2, "YCOR:IN10:492:EACT.PROC PP")
    field(LNK3, "YCOR:IN10:492:EERR.DISA PP")
    field(LNK4, "YCOR:IN10:492:ECON.PROC PP")
    field(LNK5, "YCOR:IN10:492:BMAGX.PROC PP")
    field(LNK6, "YCOR:IN10:492:BMAGY.PROC PP")
    field(LNK7, "YCOR:IN10:492:BLEM.PROC PP")
    field(LNK8, "YCOR:IN10:492:BMOD.PROC PP")
    field(LNK9, "YCOR:IN10:492:EDESSAVE.PROC PP")
    field(LNKA, "YCOR:IN10:492:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"YCOR:IN10:492:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "YCOR:IN10:492:BMAX")
  field(DOL2, "YCOR:IN10:492:BMAX")
  field(DOL3, "YCOR:IN10:492:BMAX")
  field(DOL4, "YCOR:IN10:492:BMIN")
  field(DOL5, "YCOR:IN10:492:BMIN")
  field(DOL6, "YCOR:IN10:492:BMIN")
  field(LNK1, "YCOR:IN10:492:BMAGX.HOPR")
  field(LNK2, "YCOR:IN10:492:BMAGY.HOPR")
  field(LNK3, "YCOR:IN10:492:BLEM.HOPR")
  field(LNK4, "YCOR:IN10:492:BMAGX.LOPR PP")
  field(LNK5, "YCOR:IN10:492:BMAGY.LOPR PP")
  field(LNK6, "YCOR:IN10:492:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "YCOR:IN10:492:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "YCOR:IN10:492:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "YCOR:IN10:492:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "YCOR:IN10:492:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "YCOR:IN10:492:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:IN10:492:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:IN10:492:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:IN10:492:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:IN10:492:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:IN10:492:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "YCOR:IN10:492:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "YCOR:IN10:492:EDES NPP MS")
  field(INPB, "YCOR:IN10:492:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "YCOR:IN10:522:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "YCOR:IN10:522:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "YCOR:IN10:522:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "YCOR:IN10:522:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "YCOR:IN10:522:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "YCOR:IN10:522:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "YCOR:IN10:522:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "YCOR:IN10:522:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "YCOR:IN10:522:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "YCOR:IN10:522:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "YCOR:IN10:522:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "YCOR:IN10:522:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "YCOR:IN10:522:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "YCOR:IN10:522:EDES.PROC PP")
    field(LNK2, "YCOR:IN10:522:EACT.PROC PP")
    field(LNK3, "YCOR:IN10:522:EERR.DISA PP")
    field(LNK4, "YCOR:IN10:522:ECON.PROC PP")
    field(LNK5, "YCOR:IN10:522:BMAGX.PROC PP")
    field(LNK6, "YCOR:IN10:522:BMAGY.PROC PP")
    field(LNK7, "YCOR:IN10:522:BLEM.PROC PP")
    field(LNK8, "YCOR:IN10:522:BMOD.PROC PP")
    field(LNK9, "YCOR:IN10:522:EDESSAVE.PROC PP")
    field(LNKA, "YCOR:IN10:522:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"YCOR:IN10:522:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "YCOR:IN10:522:BMAX")
  field(DOL2, "YCOR:IN10:522:BMAX")
  field(DOL3, "YCOR:IN10:522:BMAX")
  field(DOL4, "YCOR:IN10:522:BMIN")
  field(DOL5, "YCOR:IN10:522:BMIN")
  field(DOL6, "YCOR:IN10:522:BMIN")
  field(LNK1, "YCOR:IN10:522:BMAGX.HOPR")
  field(LNK2, "YCOR:IN10:522:BMAGY.HOPR")
  field(LNK3, "YCOR:IN10:522:BLEM.HOPR")
  field(LNK4, "YCOR:IN10:522:BMAGX.LOPR PP")
  field(LNK5, "YCOR:IN10:522:BMAGY.LOPR PP")
  field(LNK6, "YCOR:IN10:522:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "YCOR:IN10:522:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "YCOR:IN10:522:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "YCOR:IN10:522:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "YCOR:IN10:522:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "YCOR:IN10:522:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:IN10:522:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:IN10:522:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:IN10:522:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:IN10:522:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:IN10:522:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "YCOR:IN10:522:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "YCOR:IN10:522:EDES NPP MS")
  field(INPB, "YCOR:IN10:522:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "YCOR:IN10:642:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "YCOR:IN10:642:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "YCOR:IN10:642:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "YCOR:IN10:642:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "YCOR:IN10:642:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "YCOR:IN10:642:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "YCOR:IN10:642:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "YCOR:IN10:642:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "YCOR:IN10:642:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "YCOR:IN10:642:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "YCOR:IN10:642:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "YCOR:IN10:642:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "YCOR:IN10:642:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "YCOR:IN10:642:EDES.PROC PP")
    field(LNK2, "YCOR:IN10:642:EACT.PROC PP")
    field(LNK3, "YCOR:IN10:642:EERR.DISA PP")
    field(LNK4, "YCOR:IN10:642:ECON.PROC PP")
    field(LNK5, "YCOR:IN10:642:BMAGX.PROC PP")
    field(LNK6, "YCOR:IN10:642:BMAGY.PROC PP")
    field(LNK7, "YCOR:IN10:642:BLEM.PROC PP")
    field(LNK8, "YCOR:IN10:642:BMOD.PROC PP")
    field(LNK9, "YCOR:IN10:642:EDESSAVE.PROC PP")
    field(LNKA, "YCOR:IN10:642:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"YCOR:IN10:642:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "YCOR:IN10:642:BMAX")
  field(DOL2, "YCOR:IN10:642:BMAX")
  field(DOL3, "YCOR:IN10:642:BMAX")
  field(DOL4, "YCOR:IN10:642:BMIN")
  field(DOL5, "YCOR:IN10:642:BMIN")
  field(DOL6, "YCOR:IN10:642:BMIN")
  field(LNK1, "YCOR:IN10:642:BMAGX.HOPR")
  field(LNK2, "YCOR:IN10:642:BMAGY.HOPR")
  field(LNK3, "YCOR:IN10:642:BLEM.HOPR")
  field(LNK4, "YCOR:IN10:642:BMAGX.LOPR PP")
  field(LNK5, "YCOR:IN10:642:BMAGY.LOPR PP")
  field(LNK6, "YCOR:IN10:642:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "YCOR:IN10:642:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "YCOR:IN10:642:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "YCOR:IN10:642:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "YCOR:IN10:642:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "YCOR:IN10:642:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:IN10:642:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:IN10:642:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:IN10:642:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:IN10:642:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:IN10:642:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "YCOR:IN10:642:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "YCOR:IN10:642:EDES NPP MS")
  field(INPB, "YCOR:IN10:642:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "YCOR:IN10:722:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "YCOR:IN10:722:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "YCOR:IN10:722:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "YCOR:IN10:722:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "YCOR:IN10:722:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "YCOR:IN10:722:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "YCOR:IN10:722:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "YCOR:IN10:722:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "YCOR:IN10:722:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "YCOR:IN10:722:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "YCOR:IN10:722:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "YCOR:IN10:722:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "YCOR:IN10:722:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "YCOR:IN10:722:EDES.PROC PP")
    field(LNK2, "YCOR:IN10:722:EACT.PROC PP")
    field(LNK3, "YCOR:IN10:722:EERR.DISA PP")
    field(LNK4, "YCOR:IN10:722:ECON.PROC PP")
    field(LNK5, "YCOR:IN10:722:BMAGX.PROC PP")
    field(LNK6, "YCOR:IN10:722:BMAGY.PROC PP")
    field(LNK7, "YCOR:IN10:722:BLEM.PROC PP")
    field(LNK8, "YCOR:IN10:722:BMOD.PROC PP")
    field(LNK9, "YCOR:IN10:722:EDESSAVE.PROC PP")
    field(LNKA, "YCOR:IN10:722:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"YCOR:IN10:722:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "YCOR:IN10:722:BMAX")
  field(DOL2, "YCOR:IN10:722:BMAX")
  field(DOL3, "YCOR:IN10:722:BMAX")
  field(DOL4, "YCOR:IN10:722:BMIN")
  field(DOL5, "YCOR:IN10:722:BMIN")
  field(DOL6, "YCOR:IN10:722:BMIN")
  field(LNK1, "YCOR:IN10:722:BMAGX.HOPR")
  field(LNK2, "YCOR:IN10:722:BMAGY.HOPR")
  field(LNK3, "YCOR:IN10:722:BLEM.HOPR")
  field(LNK4, "YCOR:IN10:722:BMAGX.LOPR PP")
  field(LNK5, "YCOR:IN10:722:BMAGY.LOPR PP")
  field(LNK6, "YCOR:IN10:722:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "YCOR:IN10:722:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "YCOR:IN10:722:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "YCOR:IN10:722:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "YCOR:IN10:722:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "YCOR:IN10:722:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:IN10:722:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:IN10:722:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:IN10:722:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:IN10:722:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:IN10:722:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "YCOR:IN10:722:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "YCOR:IN10:722:EDES NPP MS")
  field(INPB, "YCOR:IN10:722:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "YCOR:IN10:762:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "YCOR:IN10:762:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "YCOR:IN10:762:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "YCOR:IN10:762:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "YCOR:IN10:762:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "YCOR:IN10:762:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "YCOR:IN10:762:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "YCOR:IN10:762:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "YCOR:IN10:762:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "YCOR:IN10:762:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "YCOR:IN10:762:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "YCOR:IN10:762:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "YCOR:IN10:762:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "YCOR:IN10:762:EDES.PROC PP")
    field(LNK2, "YCOR:IN10:762:EACT.PROC PP")
    field(LNK3, "YCOR:IN10:762:EERR.DISA PP")
    field(LNK4, "YCOR:IN10:762:ECON.PROC PP")
    field(LNK5, "YCOR:IN10:762:BMAGX.PROC PP")
    field(LNK6, "YCOR:IN10:762:BMAGY.PROC PP")
    field(LNK7, "YCOR:IN10:762:BLEM.PROC PP")
    field(LNK8, "YCOR:IN10:762:BMOD.PROC PP")
    field(LNK9, "YCOR:IN10:762:EDESSAVE.PROC PP")
    field(LNKA, "YCOR:IN10:762:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"YCOR:IN10:762:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "YCOR:IN10:762:BMAX")
  field(DOL2, "YCOR:IN10:762:BMAX")
  field(DOL3, "YCOR:IN10:762:BMAX")
  field(DOL4, "YCOR:IN10:762:BMIN")
  field(DOL5, "YCOR:IN10:762:BMIN")
  field(DOL6, "YCOR:IN10:762:BMIN")
  field(LNK1, "YCOR:IN10:762:BMAGX.HOPR")
  field(LNK2, "YCOR:IN10:762:BMAGY.HOPR")
  field(LNK3, "YCOR:IN10:762:BLEM.HOPR")
  field(LNK4, "YCOR:IN10:762:BMAGX.LOPR PP")
  field(LNK5, "YCOR:IN10:762:BMAGY.LOPR PP")
  field(LNK6, "YCOR:IN10:762:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "YCOR:IN10:762:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "YCOR:IN10:762:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "YCOR:IN10:762:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "YCOR:IN10:762:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "YCOR:IN10:762:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:IN10:762:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:IN10:762:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:IN10:762:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:IN10:762:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:IN10:762:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "YCOR:IN10:762:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "YCOR:IN10:762:EDES NPP MS")
  field(INPB, "YCOR:IN10:762:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "BEND:IN10:461:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "BEND:IN10:461:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "BEND:IN10:461:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "BEND:IN10:461:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "BEND:IN10:461:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "BEND:IN10:461:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "BEND:IN10:461:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "BEND:IN10:461:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "BEND:IN10:461:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "BEND:IN10:461:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "BEND:IN10:461:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "BEND:IN10:461:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "BEND:IN10:461:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "BEND:IN10:461:EDES.PROC PP")
    field(LNK2, "BEND:IN10:461:EACT.PROC PP")
    field(LNK3, "BEND:IN10:461:EERR.DISA PP")
    field(LNK4, "BEND:IN10:461:ECON.PROC PP")
    field(LNK5, "BEND:IN10:461:BMAGX.PROC PP")
    field(LNK6, "BEND:IN10:461:BMAGY.PROC PP")
    field(LNK7, "BEND:IN10:461:BLEM.PROC PP")
    field(LNK8, "BEND:IN10:461:BMOD.PROC PP")
    field(LNK9, "BEND:IN10:461:EDESSAVE.PROC PP")
    field(LNKA, "BEND:IN10:461:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"BEND:IN10:461:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "BEND:IN10:461:BMAX")
  field(DOL2, "BEND:IN10:461:BMAX")
  field(DOL3, "BEND:IN10:461:BMAX")
  field(DOL4, "BEND:IN10:461:BMIN")
  field(DOL5, "BEND:IN10:461:BMIN")
  field(DOL6, "BEND:IN10:461:BMIN")
  field(LNK1, "BEND:IN10:461:BMAGX.HOPR")
  field(LNK2, "BEND:IN10:461:BMAGY.HOPR")
  field(LNK3, "BEND:IN10:461:BLEM.HOPR")
  field(LNK4, "BEND:IN10:461:BMAGX.LOPR PP")
  field(LNK5, "BEND:IN10:461:BMAGY.LOPR PP")
  field(LNK6, "BEND:IN10:461:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "BEND:IN10:461:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "BEND:IN10:461:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "BEND:IN10:461:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "BEND:IN10:461:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "BEND:IN10:461:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:IN10:461:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:IN10:461:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "BEND:IN10:461:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:IN10:461:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "BEND:IN10:461:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "BEND:IN10:461:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "BEND:IN10:461:EDES NPP MS")
  field(INPB, "BEND:IN10:461:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "BEND:IN10:751:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "BEND:IN10:751:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "BEND:IN10:751:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "BEND:IN10:751:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "BEND:IN10:751:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "BEND:IN10:751:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "BEND:IN10:751:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "BEND:IN10:751:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "BEND:IN10:751:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "BEND:IN10:751:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "BEND:IN10:751:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "BEND:IN10:751:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "BEND:IN10:751:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "BEND:IN10:751:EDES.PROC PP")
    field(LNK2, "BEND:IN10:751:EACT.PROC PP")
    field(LNK3, "BEND:IN10:751:EERR.DISA PP")
    field(LNK4, "BEND:IN10:751:ECON.PROC PP")
    field(LNK5, "BEND:IN10:751:BMAGX.PROC PP")
    field(LNK6, "BEND:IN10:751:BMAGY.PROC PP")
    field(LNK7, "BEND:IN10:751:BLEM.PROC PP")
    field(LNK8, "BEND:IN10:751:BMOD.PROC PP")
    field(LNK9, "BEND:IN10:751:EDESSAVE.PROC PP")
    field(LNKA, "BEND:IN10:751:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"BEND:IN10:751:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "BEND:IN10:751:BMAX")
  field(DOL2, "BEND:IN10:751:BMAX")
  field(DOL3, "BEND:IN10:751:BMAX")
  field(DOL4, "BEND:IN10:751:BMIN")
  field(DOL5, "BEND:IN10:751:BMIN")
  field(DOL6, "BEND:IN10:751:BMIN")
  field(LNK1, "BEND:IN10:751:BMAGX.HOPR")
  field(LNK2, "BEND:IN10:751:BMAGY.HOPR")
  field(LNK3, "BEND:IN10:751:BLEM.HOPR")
  field(LNK4, "BEND:IN10:751:BMAGX.LOPR PP")
  field(LNK5, "BEND:IN10:751:BMAGY.LOPR PP")
  field(LNK6, "BEND:IN10:751:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "BEND:IN10:751:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "BEND:IN10:751:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "BEND:IN10:751:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "BEND:IN10:751:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "BEND:IN10:751:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:IN10:751:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:IN10:751:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "BEND:IN10:751:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:IN10:751:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "BEND:IN10:751:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "BEND:IN10:751:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "BEND:IN10:751:EDES NPP MS")
  field(INPB, "BEND:IN10:751:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "BTRM:IN10:451:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "BTRM:IN10:451:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "BTRM:IN10:451:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "BTRM:IN10:451:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "BTRM:IN10:451:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "BTRM:IN10:451:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "BTRM:IN10:451:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "BTRM:IN10:451:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "BTRM:IN10:451:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "BTRM:IN10:451:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "BTRM:IN10:451:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "BTRM:IN10:451:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "BTRM:IN10:451:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "BTRM:IN10:451:EDES.PROC PP")
    field(LNK2, "BTRM:IN10:451:EACT.PROC PP")
    field(LNK3, "BTRM:IN10:451:EERR.DISA PP")
    field(LNK4, "BTRM:IN10:451:ECON.PROC PP")
    field(LNK5, "BTRM:IN10:451:BMAGX.PROC PP")
    field(LNK6, "BTRM:IN10:451:BMAGY.PROC PP")
    field(LNK7, "BTRM:IN10:451:BLEM.PROC PP")
    field(LNK8, "BTRM:IN10:451:BMOD.PROC PP")
    field(LNK9, "BTRM:IN10:451:EDESSAVE.PROC PP")
    field(LNKA, "BTRM:IN10:451:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"BTRM:IN10:451:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "BTRM:IN10:451:BMAX")
  field(DOL2, "BTRM:IN10:451:BMAX")
  field(DOL3, "BTRM:IN10:451:BMAX")
  field(DOL4, "BTRM:IN10:451:BMIN")
  field(DOL5, "BTRM:IN10:451:BMIN")
  field(DOL6, "BTRM:IN10:451:BMIN")
  field(LNK1, "BTRM:IN10:451:BMAGX.HOPR")
  field(LNK2, "BTRM:IN10:451:BMAGY.HOPR")
  field(LNK3, "BTRM:IN10:451:BLEM.HOPR")
  field(LNK4, "BTRM:IN10:451:BMAGX.LOPR PP")
  field(LNK5, "BTRM:IN10:451:BMAGY.LOPR PP")
  field(LNK6, "BTRM:IN10:451:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "BTRM:IN10:451:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "BTRM:IN10:451:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "BTRM:IN10:451:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "Amain")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "BTRM:IN10:451:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "Amain")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "BTRM:IN10:451:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:IN10:451:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:IN10:451:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "BTRM:IN10:451:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:IN10:451:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "BTRM:IN10:451:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "BTRM:IN10:451:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "BTRM:IN10:451:EDES NPP MS")
  field(INPB, "BTRM:IN10:451:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "BTRM:IN10:475:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "BTRM:IN10:475:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "BTRM:IN10:475:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "BTRM:IN10:475:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "BTRM:IN10:475:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "BTRM:IN10:475:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "BTRM:IN10:475:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "BTRM:IN10:475:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "BTRM:IN10:475:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "BTRM:IN10:475:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "BTRM:IN10:475:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "BTRM:IN10:475:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "BTRM:IN10:475:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "BTRM:IN10:475:EDES.PROC PP")
    field(LNK2, "BTRM:IN10:475:EACT.PROC PP")
    field(LNK3, "BTRM:IN10:475:EERR.DISA PP")
    field(LNK4, "BTRM:IN10:475:ECON.PROC PP")
    field(LNK5, "BTRM:IN10:475:BMAGX.PROC PP")
    field(LNK6, "BTRM:IN10:475:BMAGY.PROC PP")
    field(LNK7, "BTRM:IN10:475:BLEM.PROC PP")
    field(LNK8, "BTRM:IN10:475:BMOD.PROC PP")
    field(LNK9, "BTRM:IN10:475:EDESSAVE.PROC PP")
    field(LNKA, "BTRM:IN10:475:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"BTRM:IN10:475:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "BTRM:IN10:475:BMAX")
  field(DOL2, "BTRM:IN10:475:BMAX")
  field(DOL3, "BTRM:IN10:475:BMAX")
  field(DOL4, "BTRM:IN10:475:BMIN")
  field(DOL5, "BTRM:IN10:475:BMIN")
  field(DOL6, "BTRM:IN10:475:BMIN")
  field(LNK1, "BTRM:IN10:475:BMAGX.HOPR")
  field(LNK2, "BTRM:IN10:475:BMAGY.HOPR")
  field(LNK3, "BTRM:IN10:475:BLEM.HOPR")
  field(LNK4, "BTRM:IN10:475:BMAGX.LOPR PP")
  field(LNK5, "BTRM:IN10:475:BMAGY.LOPR PP")
  field(LNK6, "BTRM:IN10:475:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "BTRM:IN10:475:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "BTRM:IN10:475:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "BTRM:IN10:475:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "Amain")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "BTRM:IN10:475:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "Amain")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "BTRM:IN10:475:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:IN10:475:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:IN10:475:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "BTRM:IN10:475:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:IN10:475:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "BTRM:IN10:475:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "BTRM:IN10:475:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "BTRM:IN10:475:EDES NPP MS")
  field(INPB, "BTRM:IN10:475:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "BTRM:IN10:481:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "BTRM:IN10:481:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "BTRM:IN10:481:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "BTRM:IN10:481:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "BTRM:IN10:481:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "BTRM:IN10:481:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "BTRM:IN10:481:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "BTRM:IN10:481:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "BTRM:IN10:481:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "BTRM:IN10:481:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "BTRM:IN10:481:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "BTRM:IN10:481:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "BTRM:IN10:481:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "BTRM:IN10:481:EDES.PROC PP")
    field(LNK2, "BTRM:IN10:481:EACT.PROC PP")
    field(LNK3, "BTRM:IN10:481:EERR.DISA PP")
    field(LNK4, "BTRM:IN10:481:ECON.PROC PP")
    field(LNK5, "BTRM:IN10:481:BMAGX.PROC PP")
    field(LNK6, "BTRM:IN10:481:BMAGY.PROC PP")
    field(LNK7, "BTRM:IN10:481:BLEM.PROC PP")
    field(LNK8, "BTRM:IN10:481:BMOD.PROC PP")
    field(LNK9, "BTRM:IN10:481:EDESSAVE.PROC PP")
    field(LNKA, "BTRM:IN10:481:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"BTRM:IN10:481:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "BTRM:IN10:481:BMAX")
  field(DOL2, "BTRM:IN10:481:BMAX")
  field(DOL3, "BTRM:IN10:481:BMAX")
  field(DOL4, "BTRM:IN10:481:BMIN")
  field(DOL5, "BTRM:IN10:481:BMIN")
  field(DOL6, "BTRM:IN10:481:BMIN")
  field(LNK1, "BTRM:IN10:481:BMAGX.HOPR")
  field(LNK2, "BTRM:IN10:481:BMAGY.HOPR")
  field(LNK3, "BTRM:IN10:481:BLEM.HOPR")
  field(LNK4, "BTRM:IN10:481:BMAGX.LOPR PP")
  field(LNK5, "BTRM:IN10:481:BMAGY.LOPR PP")
  field(LNK6, "BTRM:IN10:481:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "BTRM:IN10:481:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "BTRM:IN10:481:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "BTRM:IN10:481:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "Amain")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "BTRM:IN10:481:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "Amain")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "BTRM:IN10:481:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:IN10:481:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:IN10:481:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "BTRM:IN10:481:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:IN10:481:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "BTRM:IN10:481:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "BTRM:IN10:481:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "BTRM:IN10:481:EDES NPP MS")
  field(INPB, "BTRM:IN10:481:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "BTRM:IN10:661:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "BTRM:IN10:661:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "BTRM:IN10:661:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "BTRM:IN10:661:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "BTRM:IN10:661:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "BTRM:IN10:661:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "BTRM:IN10:661:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "BTRM:IN10:661:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "BTRM:IN10:661:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "BTRM:IN10:661:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "BTRM:IN10:661:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "BTRM:IN10:661:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "BTRM:IN10:661:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "BTRM:IN10:661:EDES.PROC PP")
    field(LNK2, "BTRM:IN10:661:EACT.PROC PP")
    field(LNK3, "BTRM:IN10:661:EERR.DISA PP")
    field(LNK4, "BTRM:IN10:661:ECON.PROC PP")
    field(LNK5, "BTRM:IN10:661:BMAGX.PROC PP")
    field(LNK6, "BTRM:IN10:661:BMAGY.PROC PP")
    field(LNK7, "BTRM:IN10:661:BLEM.PROC PP")
    field(LNK8, "BTRM:IN10:661:BMOD.PROC PP")
    field(LNK9, "BTRM:IN10:661:EDESSAVE.PROC PP")
    field(LNKA, "BTRM:IN10:661:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"BTRM:IN10:661:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "BTRM:IN10:661:BMAX")
  field(DOL2, "BTRM:IN10:661:BMAX")
  field(DOL3, "BTRM:IN10:661:BMAX")
  field(DOL4, "BTRM:IN10:661:BMIN")
  field(DOL5, "BTRM:IN10:661:BMIN")
  field(DOL6, "BTRM:IN10:661:BMIN")
  field(LNK1, "BTRM:IN10:661:BMAGX.HOPR")
  field(LNK2, "BTRM:IN10:661:BMAGY.HOPR")
  field(LNK3, "BTRM:IN10:661:BLEM.HOPR")
  field(LNK4, "BTRM:IN10:661:BMAGX.LOPR PP")
  field(LNK5, "BTRM:IN10:661:BMAGY.LOPR PP")
  field(LNK6, "BTRM:IN10:661:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "BTRM:IN10:661:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "BTRM:IN10:661:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "BTRM:IN10:661:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "BTRM:IN10:661:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "BTRM:IN10:661:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:IN10:661:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:IN10:661:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "BTRM:IN10:661:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:IN10:661:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "BTRM:IN10:661:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "BTRM:IN10:661:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "BTRM:IN10:661:EDES NPP MS")
  field(INPB, "BTRM:IN10:661:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "LGPS:IN10:1:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "LGPS:IN10:1:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "LGPS:IN10:1:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "LGPS:IN10:1:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "LGPS:IN10:1:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "LGPS:IN10:1:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "LGPS:IN10:1:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "LGPS:IN10:1:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "LGPS:IN10:1:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "LGPS:IN10:1:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "LGPS:IN10:1:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "LGPS:IN10:1:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "LGPS:IN10:1:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "LGPS:IN10:1:EDES.PROC PP")
    field(LNK2, "LGPS:IN10:1:EACT.PROC PP")
    field(LNK3, "LGPS:IN10:1:EERR.DISA PP")
    field(LNK4, "LGPS:IN10:1:ECON.PROC PP")
    field(LNK5, "LGPS:IN10:1:BMAGX.PROC PP")
    field(LNK6, "LGPS:IN10:1:BMAGY.PROC PP")
    field(LNK7, "LGPS:IN10:1:BLEM.PROC PP")
    field(LNK8, "LGPS:IN10:1:BMOD.PROC PP")
    field(LNK9, "LGPS:IN10:1:EDESSAVE.PROC PP")
    field(LNKA, "LGPS:IN10:1:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"LGPS:IN10:1:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "LGPS:IN10:1:BMAX")
  field(DOL2, "LGPS:IN10:1:BMAX")
  field(DOL3, "LGPS:IN10:1:BMAX")
  field(DOL4, "LGPS:IN10:1:BMIN")
  field(DOL5, "LGPS:IN10:1:BMIN")
  field(DOL6, "LGPS:IN10:1:BMIN")
  field(LNK1, "LGPS:IN10:1:BMAGX.HOPR")
  field(LNK2, "LGPS:IN10:1:BMAGY.HOPR")
  field(LNK3, "LGPS:IN10:1:BLEM.HOPR")
  field(LNK4, "LGPS:IN10:1:BMAGX.LOPR PP")
  field(LNK5, "LGPS:IN10:1:BMAGY.LOPR PP")
  field(LNK6, "LGPS:IN10:1:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "LGPS:IN10:1:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "LGPS:IN10:1:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "LGPS:IN10:1:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "Volts")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "LGPS:IN10:1:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "Volts")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "LGPS:IN10:1:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "LGPS:IN10:1:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "LGPS:IN10:1:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "LGPS:IN10:1:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "LGPS:IN10:1:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "LGPS:IN10:1:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "LGPS:IN10:1:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "LGPS:IN10:1:EDES NPP MS")
  field(INPB, "LGPS:IN10:1:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "XCOR:LI11:104:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI11:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI11:1:CTRL.RVAL")
  field(LNK1, "XCOR:LI11:104:FUNC CA PP")
  field(DOL2, "MGNT:LI11:1:BENDCTRL.RVAL")
  field(LNK2, "XCOR:LI11:104:FUNC CA PP")
  field(DOL3, "MGNT:LI11:1:BTRMCTRL.RVAL")
  field(LNK3, "XCOR:LI11:104:FUNC CA PP")
  field(DOL4, "MGNT:LI11:1:LGPSCTRL.RVAL")
  field(LNK4, "XCOR:LI11:104:FUNC CA PP")
  field(DOL5, "MGNT:LI11:1:QUADCTRL.RVAL")
  field(LNK5, "XCOR:LI11:104:FUNC CA PP")
  field(DOL6, "MGNT:LI11:1:XCORCTRL.RVAL")
  field(LNK6, "XCOR:LI11:104:FUNC CA PP")
  field(DOL7, "MGNT:LI11:1:YCORCTRL.RVAL")
  field(LNK7, "XCOR:LI11:104:FUNC CA PP")
  field(DOL8, "MGNT:LI11:1:SOLNCTRL.RVAL")
  field(LNK8, "XCOR:LI11:104:FUNC CA PP")
  field(DOL9, "MGNT:LI11:1:KICKCTRL.RVAL")
  field(LNK9, "XCOR:LI11:104:FUNC CA PP")
  field(DOLA, "MGNT:LI11:1:SEXTCTRL.RVAL")
  field(LNKA, "XCOR:LI11:104:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "XCOR:LI11:104:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "XCOR:LI11:104:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "XCOR:LI11:104:EDES.PROC PP")
    field(LNK2, "XCOR:LI11:104:EACT.PROC PP")
    field(LNK3, "XCOR:LI11:104:EERR.DISA PP")
    field(LNK4, "XCOR:LI11:104:ECON.PROC PP")
    field(LNK5, "XCOR:LI11:104:BMAGX.PROC PP")
    field(LNK6, "XCOR:LI11:104:BMAGY.PROC PP")
    field(LNK7, "XCOR:LI11:104:BLEM.PROC PP")
    field(LNK8, "XCOR:LI11:104:BMOD.PROC PP")
    field(LNK9, "XCOR:LI11:104:EDESSAVE.PROC PP")
    field(LNKA, "XCOR:LI11:104:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"XCOR:LI11:104:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "XCOR:LI11:104:BMAX")
  field(DOL2, "XCOR:LI11:104:BMAX")
  field(DOL3, "XCOR:LI11:104:BMAX")
  field(DOL4, "XCOR:LI11:104:BMIN")
  field(DOL5, "XCOR:LI11:104:BMIN")
  field(DOL6, "XCOR:LI11:104:BMIN")
  field(LNK1, "XCOR:LI11:104:BMAGX.HOPR")
  field(LNK2, "XCOR:LI11:104:BMAGY.HOPR")
  field(LNK3, "XCOR:LI11:104:BLEM.HOPR")
  field(LNK4, "XCOR:LI11:104:BMAGX.LOPR PP")
  field(LNK5, "XCOR:LI11:104:BMAGY.LOPR PP")
  field(LNK6, "XCOR:LI11:104:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "XCOR:LI11:104:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "XCOR:LI11:104:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "XCOR:LI11:104:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "XCOR:LI11:104:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "XCOR:LI11:104:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:LI11:104:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:LI11:104:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "XCOR:LI11:104:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:LI11:104:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "XCOR:LI11:104:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "XCOR:LI11:104:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "XCOR:LI11:104:EDES NPP MS")
  field(INPB, "XCOR:LI11:104:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "XCOR:LI11:140:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI11:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI11:1:CTRL.RVAL")
  field(LNK1, "XCOR:LI11:140:FUNC CA PP")
  field(DOL2, "MGNT:LI11:1:BENDCTRL.RVAL")
  field(LNK2, "XCOR:LI11:140:FUNC CA PP")
  field(DOL3, "MGNT:LI11:1:BTRMCTRL.RVAL")
  field(LNK3, "XCOR:LI11:140:FUNC CA PP")
  field(DOL4, "MGNT:LI11:1:LGPSCTRL.RVAL")
  field(LNK4, "XCOR:LI11:140:FUNC CA PP")
  field(DOL5, "MGNT:LI11:1:QUADCTRL.RVAL")
  field(LNK5, "XCOR:LI11:140:FUNC CA PP")
  field(DOL6, "MGNT:LI11:1:XCORCTRL.RVAL")
  field(LNK6, "XCOR:LI11:140:FUNC CA PP")
  field(DOL7, "MGNT:LI11:1:YCORCTRL.RVAL")
  field(LNK7, "XCOR:LI11:140:FUNC CA PP")
  field(DOL8, "MGNT:LI11:1:SOLNCTRL.RVAL")
  field(LNK8, "XCOR:LI11:140:FUNC CA PP")
  field(DOL9, "MGNT:LI11:1:KICKCTRL.RVAL")
  field(LNK9, "XCOR:LI11:140:FUNC CA PP")
  field(DOLA, "MGNT:LI11:1:SEXTCTRL.RVAL")
  field(LNKA, "XCOR:LI11:140:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "XCOR:LI11:140:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "XCOR:LI11:140:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "XCOR:LI11:140:EDES.PROC PP")
    field(LNK2, "XCOR:LI11:140:EACT.PROC PP")
    field(LNK3, "XCOR:LI11:140:EERR.DISA PP")
    field(LNK4, "XCOR:LI11:140:ECON.PROC PP")
    field(LNK5, "XCOR:LI11:140:BMAGX.PROC PP")
    field(LNK6, "XCOR:LI11:140:BMAGY.PROC PP")
    field(LNK7, "XCOR:LI11:140:BLEM.PROC PP")
    field(LNK8, "XCOR:LI11:140:BMOD.PROC PP")
    field(LNK9, "XCOR:LI11:140:EDESSAVE.PROC PP")
    field(LNKA, "XCOR:LI11:140:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"XCOR:LI11:140:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "XCOR:LI11:140:BMAX")
  field(DOL2, "XCOR:LI11:140:BMAX")
  field(DOL3, "XCOR:LI11:140:BMAX")
  field(DOL4, "XCOR:LI11:140:BMIN")
  field(DOL5, "XCOR:LI11:140:BMIN")
  field(DOL6, "XCOR:LI11:140:BMIN")
  field(LNK1, "XCOR:LI11:140:BMAGX.HOPR")
  field(LNK2, "XCOR:LI11:140:BMAGY.HOPR")
  field(LNK3, "XCOR:LI11:140:BLEM.HOPR")
  field(LNK4, "XCOR:LI11:140:BMAGX.LOPR PP")
  field(LNK5, "XCOR:LI11:140:BMAGY.LOPR PP")
  field(LNK6, "XCOR:LI11:140:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "XCOR:LI11:140:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "XCOR:LI11:140:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "XCOR:LI11:140:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "XCOR:LI11:140:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "XCOR:LI11:140:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:LI11:140:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:LI11:140:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "XCOR:LI11:140:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:LI11:140:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "XCOR:LI11:140:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "XCOR:LI11:140:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "XCOR:LI11:140:EDES NPP MS")
  field(INPB, "XCOR:LI11:140:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "XCOR:LI11:202:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI11:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI11:1:CTRL.RVAL")
  field(LNK1, "XCOR:LI11:202:FUNC CA PP")
  field(DOL2, "MGNT:LI11:1:BENDCTRL.RVAL")
  field(LNK2, "XCOR:LI11:202:FUNC CA PP")
  field(DOL3, "MGNT:LI11:1:BTRMCTRL.RVAL")
  field(LNK3, "XCOR:LI11:202:FUNC CA PP")
  field(DOL4, "MGNT:LI11:1:LGPSCTRL.RVAL")
  field(LNK4, "XCOR:LI11:202:FUNC CA PP")
  field(DOL5, "MGNT:LI11:1:QUADCTRL.RVAL")
  field(LNK5, "XCOR:LI11:202:FUNC CA PP")
  field(DOL6, "MGNT:LI11:1:XCORCTRL.RVAL")
  field(LNK6, "XCOR:LI11:202:FUNC CA PP")
  field(DOL7, "MGNT:LI11:1:YCORCTRL.RVAL")
  field(LNK7, "XCOR:LI11:202:FUNC CA PP")
  field(DOL8, "MGNT:LI11:1:SOLNCTRL.RVAL")
  field(LNK8, "XCOR:LI11:202:FUNC CA PP")
  field(DOL9, "MGNT:LI11:1:KICKCTRL.RVAL")
  field(LNK9, "XCOR:LI11:202:FUNC CA PP")
  field(DOLA, "MGNT:LI11:1:SEXTCTRL.RVAL")
  field(LNKA, "XCOR:LI11:202:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "XCOR:LI11:202:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "XCOR:LI11:202:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "XCOR:LI11:202:EDES.PROC PP")
    field(LNK2, "XCOR:LI11:202:EACT.PROC PP")
    field(LNK3, "XCOR:LI11:202:EERR.DISA PP")
    field(LNK4, "XCOR:LI11:202:ECON.PROC PP")
    field(LNK5, "XCOR:LI11:202:BMAGX.PROC PP")
    field(LNK6, "XCOR:LI11:202:BMAGY.PROC PP")
    field(LNK7, "XCOR:LI11:202:BLEM.PROC PP")
    field(LNK8, "XCOR:LI11:202:BMOD.PROC PP")
    field(LNK9, "XCOR:LI11:202:EDESSAVE.PROC PP")
    field(LNKA, "XCOR:LI11:202:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"XCOR:LI11:202:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "XCOR:LI11:202:BMAX")
  field(DOL2, "XCOR:LI11:202:BMAX")
  field(DOL3, "XCOR:LI11:202:BMAX")
  field(DOL4, "XCOR:LI11:202:BMIN")
  field(DOL5, "XCOR:LI11:202:BMIN")
  field(DOL6, "XCOR:LI11:202:BMIN")
  field(LNK1, "XCOR:LI11:202:BMAGX.HOPR")
  field(LNK2, "XCOR:LI11:202:BMAGY.HOPR")
  field(LNK3, "XCOR:LI11:202:BLEM.HOPR")
  field(LNK4, "XCOR:LI11:202:BMAGX.LOPR PP")
  field(LNK5, "XCOR:LI11:202:BMAGY.LOPR PP")
  field(LNK6, "XCOR:LI11:202:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "XCOR:LI11:202:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "XCOR:LI11:202:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "XCOR:LI11:202:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "XCOR:LI11:202:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "XCOR:LI11:202:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:LI11:202:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:LI11:202:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "XCOR:LI11:202:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:LI11:202:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "XCOR:LI11:202:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "XCOR:LI11:202:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "XCOR:LI11:202:EDES NPP MS")
  field(INPB, "XCOR:LI11:202:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "XCOR:LI11:272:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI11:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI11:1:CTRL.RVAL")
  field(LNK1, "XCOR:LI11:272:FUNC CA PP")
  field(DOL2, "MGNT:LI11:1:BENDCTRL.RVAL")
  field(LNK2, "XCOR:LI11:272:FUNC CA PP")
  field(DOL3, "MGNT:LI11:1:BTRMCTRL.RVAL")
  field(LNK3, "XCOR:LI11:272:FUNC CA PP")
  field(DOL4, "MGNT:LI11:1:LGPSCTRL.RVAL")
  field(LNK4, "XCOR:LI11:272:FUNC CA PP")
  field(DOL5, "MGNT:LI11:1:QUADCTRL.RVAL")
  field(LNK5, "XCOR:LI11:272:FUNC CA PP")
  field(DOL6, "MGNT:LI11:1:XCORCTRL.RVAL")
  field(LNK6, "XCOR:LI11:272:FUNC CA PP")
  field(DOL7, "MGNT:LI11:1:YCORCTRL.RVAL")
  field(LNK7, "XCOR:LI11:272:FUNC CA PP")
  field(DOL8, "MGNT:LI11:1:SOLNCTRL.RVAL")
  field(LNK8, "XCOR:LI11:272:FUNC CA PP")
  field(DOL9, "MGNT:LI11:1:KICKCTRL.RVAL")
  field(LNK9, "XCOR:LI11:272:FUNC CA PP")
  field(DOLA, "MGNT:LI11:1:SEXTCTRL.RVAL")
  field(LNKA, "XCOR:LI11:272:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "XCOR:LI11:272:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "XCOR:LI11:272:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "XCOR:LI11:272:EDES.PROC PP")
    field(LNK2, "XCOR:LI11:272:EACT.PROC PP")
    field(LNK3, "XCOR:LI11:272:EERR.DISA PP")
    field(LNK4, "XCOR:LI11:272:ECON.PROC PP")
    field(LNK5, "XCOR:LI11:272:BMAGX.PROC PP")
    field(LNK6, "XCOR:LI11:272:BMAGY.PROC PP")
    field(LNK7, "XCOR:LI11:272:BLEM.PROC PP")
    field(LNK8, "XCOR:LI11:272:BMOD.PROC PP")
    field(LNK9, "XCOR:LI11:272:EDESSAVE.PROC PP")
    field(LNKA, "XCOR:LI11:272:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"XCOR:LI11:272:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "XCOR:LI11:272:BMAX")
  field(DOL2, "XCOR:LI11:272:BMAX")
  field(DOL3, "XCOR:LI11:272:BMAX")
  field(DOL4, "XCOR:LI11:272:BMIN")
  field(DOL5, "XCOR:LI11:272:BMIN")
  field(DOL6, "XCOR:LI11:272:BMIN")
  field(LNK1, "XCOR:LI11:272:BMAGX.HOPR")
  field(LNK2, "XCOR:LI11:272:BMAGY.HOPR")
  field(LNK3, "XCOR:LI11:272:BLEM.HOPR")
  field(LNK4, "XCOR:LI11:272:BMAGX.LOPR PP")
  field(LNK5, "XCOR:LI11:272:BMAGY.LOPR PP")
  field(LNK6, "XCOR:LI11:272:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "XCOR:LI11:272:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "XCOR:LI11:272:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "XCOR:LI11:272:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "XCOR:LI11:272:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "XCOR:LI11:272:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:LI11:272:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:LI11:272:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "XCOR:LI11:272:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:LI11:272:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "XCOR:LI11:272:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "XCOR:LI11:272:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "XCOR:LI11:272:EDES NPP MS")
  field(INPB, "XCOR:LI11:272:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "XCOR:LI11:304:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI11:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI11:1:CTRL.RVAL")
  field(LNK1, "XCOR:LI11:304:FUNC CA PP")
  field(DOL2, "MGNT:LI11:1:BENDCTRL.RVAL")
  field(LNK2, "XCOR:LI11:304:FUNC CA PP")
  field(DOL3, "MGNT:LI11:1:BTRMCTRL.RVAL")
  field(LNK3, "XCOR:LI11:304:FUNC CA PP")
  field(DOL4, "MGNT:LI11:1:LGPSCTRL.RVAL")
  field(LNK4, "XCOR:LI11:304:FUNC CA PP")
  field(DOL5, "MGNT:LI11:1:QUADCTRL.RVAL")
  field(LNK5, "XCOR:LI11:304:FUNC CA PP")
  field(DOL6, "MGNT:LI11:1:XCORCTRL.RVAL")
  field(LNK6, "XCOR:LI11:304:FUNC CA PP")
  field(DOL7, "MGNT:LI11:1:YCORCTRL.RVAL")
  field(LNK7, "XCOR:LI11:304:FUNC CA PP")
  field(DOL8, "MGNT:LI11:1:SOLNCTRL.RVAL")
  field(LNK8, "XCOR:LI11:304:FUNC CA PP")
  field(DOL9, "MGNT:LI11:1:KICKCTRL.RVAL")
  field(LNK9, "XCOR:LI11:304:FUNC CA PP")
  field(DOLA, "MGNT:LI11:1:SEXTCTRL.RVAL")
  field(LNKA, "XCOR:LI11:304:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "XCOR:LI11:304:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "XCOR:LI11:304:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "XCOR:LI11:304:EDES.PROC PP")
    field(LNK2, "XCOR:LI11:304:EACT.PROC PP")
    field(LNK3, "XCOR:LI11:304:EERR.DISA PP")
    field(LNK4, "XCOR:LI11:304:ECON.PROC PP")
    field(LNK5, "XCOR:LI11:304:BMAGX.PROC PP")
    field(LNK6, "XCOR:LI11:304:BMAGY.PROC PP")
    field(LNK7, "XCOR:LI11:304:BLEM.PROC PP")
    field(LNK8, "XCOR:LI11:304:BMOD.PROC PP")
    field(LNK9, "XCOR:LI11:304:EDESSAVE.PROC PP")
    field(LNKA, "XCOR:LI11:304:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"XCOR:LI11:304:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "XCOR:LI11:304:BMAX")
  field(DOL2, "XCOR:LI11:304:BMAX")
  field(DOL3, "XCOR:LI11:304:BMAX")
  field(DOL4, "XCOR:LI11:304:BMIN")
  field(DOL5, "XCOR:LI11:304:BMIN")
  field(DOL6, "XCOR:LI11:304:BMIN")
  field(LNK1, "XCOR:LI11:304:BMAGX.HOPR")
  field(LNK2, "XCOR:LI11:304:BMAGY.HOPR")
  field(LNK3, "XCOR:LI11:304:BLEM.HOPR")
  field(LNK4, "XCOR:LI11:304:BMAGX.LOPR PP")
  field(LNK5, "XCOR:LI11:304:BMAGY.LOPR PP")
  field(LNK6, "XCOR:LI11:304:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "XCOR:LI11:304:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "XCOR:LI11:304:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "XCOR:LI11:304:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "XCOR:LI11:304:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "XCOR:LI11:304:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:LI11:304:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:LI11:304:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "XCOR:LI11:304:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:LI11:304:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "XCOR:LI11:304:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "XCOR:LI11:304:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "XCOR:LI11:304:EDES NPP MS")
  field(INPB, "XCOR:LI11:304:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "XCOR:LI11:398:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI11:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI11:1:CTRL.RVAL")
  field(LNK1, "XCOR:LI11:398:FUNC CA PP")
  field(DOL2, "MGNT:LI11:1:BENDCTRL.RVAL")
  field(LNK2, "XCOR:LI11:398:FUNC CA PP")
  field(DOL3, "MGNT:LI11:1:BTRMCTRL.RVAL")
  field(LNK3, "XCOR:LI11:398:FUNC CA PP")
  field(DOL4, "MGNT:LI11:1:LGPSCTRL.RVAL")
  field(LNK4, "XCOR:LI11:398:FUNC CA PP")
  field(DOL5, "MGNT:LI11:1:QUADCTRL.RVAL")
  field(LNK5, "XCOR:LI11:398:FUNC CA PP")
  field(DOL6, "MGNT:LI11:1:XCORCTRL.RVAL")
  field(LNK6, "XCOR:LI11:398:FUNC CA PP")
  field(DOL7, "MGNT:LI11:1:YCORCTRL.RVAL")
  field(LNK7, "XCOR:LI11:398:FUNC CA PP")
  field(DOL8, "MGNT:LI11:1:SOLNCTRL.RVAL")
  field(LNK8, "XCOR:LI11:398:FUNC CA PP")
  field(DOL9, "MGNT:LI11:1:KICKCTRL.RVAL")
  field(LNK9, "XCOR:LI11:398:FUNC CA PP")
  field(DOLA, "MGNT:LI11:1:SEXTCTRL.RVAL")
  field(LNKA, "XCOR:LI11:398:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "XCOR:LI11:398:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "XCOR:LI11:398:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "XCOR:LI11:398:EDES.PROC PP")
    field(LNK2, "XCOR:LI11:398:EACT.PROC PP")
    field(LNK3, "XCOR:LI11:398:EERR.DISA PP")
    field(LNK4, "XCOR:LI11:398:ECON.PROC PP")
    field(LNK5, "XCOR:LI11:398:BMAGX.PROC PP")
    field(LNK6, "XCOR:LI11:398:BMAGY.PROC PP")
    field(LNK7, "XCOR:LI11:398:BLEM.PROC PP")
    field(LNK8, "XCOR:LI11:398:BMOD.PROC PP")
    field(LNK9, "XCOR:LI11:398:EDESSAVE.PROC PP")
    field(LNKA, "XCOR:LI11:398:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"XCOR:LI11:398:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "XCOR:LI11:398:BMAX")
  field(DOL2, "XCOR:LI11:398:BMAX")
  field(DOL3, "XCOR:LI11:398:BMAX")
  field(DOL4, "XCOR:LI11:398:BMIN")
  field(DOL5, "XCOR:LI11:398:BMIN")
  field(DOL6, "XCOR:LI11:398:BMIN")
  field(LNK1, "XCOR:LI11:398:BMAGX.HOPR")
  field(LNK2, "XCOR:LI11:398:BMAGY.HOPR")
  field(LNK3, "XCOR:LI11:398:BLEM.HOPR")
  field(LNK4, "XCOR:LI11:398:BMAGX.LOPR PP")
  field(LNK5, "XCOR:LI11:398:BMAGY.LOPR PP")
  field(LNK6, "XCOR:LI11:398:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "XCOR:LI11:398:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "XCOR:LI11:398:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "XCOR:LI11:398:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "XCOR:LI11:398:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "XCOR:LI11:398:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:LI11:398:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:LI11:398:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "XCOR:LI11:398:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:LI11:398:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "XCOR:LI11:398:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "XCOR:LI11:398:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "XCOR:LI11:398:EDES NPP MS")
  field(INPB, "XCOR:LI11:398:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "YCOR:LI11:105:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI11:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI11:1:CTRL.RVAL")
  field(LNK1, "YCOR:LI11:105:FUNC CA PP")
  field(DOL2, "MGNT:LI11:1:BENDCTRL.RVAL")
  field(LNK2, "YCOR:LI11:105:FUNC CA PP")
  field(DOL3, "MGNT:LI11:1:BTRMCTRL.RVAL")
  field(LNK3, "YCOR:LI11:105:FUNC CA PP")
  field(DOL4, "MGNT:LI11:1:LGPSCTRL.RVAL")
  field(LNK4, "YCOR:LI11:105:FUNC CA PP")
  field(DOL5, "MGNT:LI11:1:QUADCTRL.RVAL")
  field(LNK5, "YCOR:LI11:105:FUNC CA PP")
  field(DOL6, "MGNT:LI11:1:XCORCTRL.RVAL")
  field(LNK6, "YCOR:LI11:105:FUNC CA PP")
  field(DOL7, "MGNT:LI11:1:YCORCTRL.RVAL")
  field(LNK7, "YCOR:LI11:105:FUNC CA PP")
  field(DOL8, "MGNT:LI11:1:SOLNCTRL.RVAL")
  field(LNK8, "YCOR:LI11:105:FUNC CA PP")
  field(DOL9, "MGNT:LI11:1:KICKCTRL.RVAL")
  field(LNK9, "YCOR:LI11:105:FUNC CA PP")
  field(DOLA, "MGNT:LI11:1:SEXTCTRL.RVAL")
  field(LNKA, "YCOR:LI11:105:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "YCOR:LI11:105:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "YCOR:LI11:105:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "YCOR:LI11:105:EDES.PROC PP")
    field(LNK2, "YCOR:LI11:105:EACT.PROC PP")
    field(LNK3, "YCOR:LI11:105:EERR.DISA PP")
    field(LNK4, "YCOR:LI11:105:ECON.PROC PP")
    field(LNK5, "YCOR:LI11:105:BMAGX.PROC PP")
    field(LNK6, "YCOR:LI11:105:BMAGY.PROC PP")
    field(LNK7, "YCOR:LI11:105:BLEM.PROC PP")
    field(LNK8, "YCOR:LI11:105:BMOD.PROC PP")
    field(LNK9, "YCOR:LI11:105:EDESSAVE.PROC PP")
    field(LNKA, "YCOR:LI11:105:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"YCOR:LI11:105:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "YCOR:LI11:105:BMAX")
  field(DOL2, "YCOR:LI11:105:BMAX")
  field(DOL3, "YCOR:LI11:105:BMAX")
  field(DOL4, "YCOR:LI11:105:BMIN")
  field(DOL5, "YCOR:LI11:105:BMIN")
  field(DOL6, "YCOR:LI11:105:BMIN")
  field(LNK1, "YCOR:LI11:105:BMAGX.HOPR")
  field(LNK2, "YCOR:LI11:105:BMAGY.HOPR")
  field(LNK3, "YCOR:LI11:105:BLEM.HOPR")
  field(LNK4, "YCOR:LI11:105:BMAGX.LOPR PP")
  field(LNK5, "YCOR:LI11:105:BMAGY.LOPR PP")
  field(LNK6, "YCOR:LI11:105:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "YCOR:LI11:105:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "YCOR:LI11:105:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "YCOR:LI11:105:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "YCOR:LI11:105:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "YCOR:LI11:105:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:LI11:105:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:LI11:105:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:LI11:105:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:LI11:105:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:LI11:105:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "YCOR:LI11:105:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "YCOR:LI11:105:EDES NPP MS")
  field(INPB, "YCOR:LI11:105:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "YCOR:LI11:141:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI11:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI11:1:CTRL.RVAL")
  field(LNK1, "YCOR:LI11:141:FUNC CA PP")
  field(DOL2, "MGNT:LI11:1:BENDCTRL.RVAL")
  field(LNK2, "YCOR:LI11:141:FUNC CA PP")
  field(DOL3, "MGNT:LI11:1:BTRMCTRL.RVAL")
  field(LNK3, "YCOR:LI11:141:FUNC CA PP")
  field(DOL4, "MGNT:LI11:1:LGPSCTRL.RVAL")
  field(LNK4, "YCOR:LI11:141:FUNC CA PP")
  field(DOL5, "MGNT:LI11:1:QUADCTRL.RVAL")
  field(LNK5, "YCOR:LI11:141:FUNC CA PP")
  field(DOL6, "MGNT:LI11:1:XCORCTRL.RVAL")
  field(LNK6, "YCOR:LI11:141:FUNC CA PP")
  field(DOL7, "MGNT:LI11:1:YCORCTRL.RVAL")
  field(LNK7, "YCOR:LI11:141:FUNC CA PP")
  field(DOL8, "MGNT:LI11:1:SOLNCTRL.RVAL")
  field(LNK8, "YCOR:LI11:141:FUNC CA PP")
  field(DOL9, "MGNT:LI11:1:KICKCTRL.RVAL")
  field(LNK9, "YCOR:LI11:141:FUNC CA PP")
  field(DOLA, "MGNT:LI11:1:SEXTCTRL.RVAL")
  field(LNKA, "YCOR:LI11:141:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "YCOR:LI11:141:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "YCOR:LI11:141:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "YCOR:LI11:141:EDES.PROC PP")
    field(LNK2, "YCOR:LI11:141:EACT.PROC PP")
    field(LNK3, "YCOR:LI11:141:EERR.DISA PP")
    field(LNK4, "YCOR:LI11:141:ECON.PROC PP")
    field(LNK5, "YCOR:LI11:141:BMAGX.PROC PP")
    field(LNK6, "YCOR:LI11:141:BMAGY.PROC PP")
    field(LNK7, "YCOR:LI11:141:BLEM.PROC PP")
    field(LNK8, "YCOR:LI11:141:BMOD.PROC PP")
    field(LNK9, "YCOR:LI11:141:EDESSAVE.PROC PP")
    field(LNKA, "YCOR:LI11:141:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"YCOR:LI11:141:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "YCOR:LI11:141:BMAX")
  field(DOL2, "YCOR:LI11:141:BMAX")
  field(DOL3, "YCOR:LI11:141:BMAX")
  field(DOL4, "YCOR:LI11:141:BMIN")
  field(DOL5, "YCOR:LI11:141:BMIN")
  field(DOL6, "YCOR:LI11:141:BMIN")
  field(LNK1, "YCOR:LI11:141:BMAGX.HOPR")
  field(LNK2, "YCOR:LI11:141:BMAGY.HOPR")
  field(LNK3, "YCOR:LI11:141:BLEM.HOPR")
  field(LNK4, "YCOR:LI11:141:BMAGX.LOPR PP")
  field(LNK5, "YCOR:LI11:141:BMAGY.LOPR PP")
  field(LNK6, "YCOR:LI11:141:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "YCOR:LI11:141:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "YCOR:LI11:141:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "YCOR:LI11:141:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "YCOR:LI11:141:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "YCOR:LI11:141:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:LI11:141:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:LI11:141:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:LI11:141:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:LI11:141:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:LI11:141:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "YCOR:LI11:141:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "YCOR:LI11:141:EDES NPP MS")
  field(INPB, "YCOR:LI11:141:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "YCOR:LI11:203:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI11:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI11:1:CTRL.RVAL")
  field(LNK1, "YCOR:LI11:203:FUNC CA PP")
  field(DOL2, "MGNT:LI11:1:BENDCTRL.RVAL")
  field(LNK2, "YCOR:LI11:203:FUNC CA PP")
  field(DOL3, "MGNT:LI11:1:BTRMCTRL.RVAL")
  field(LNK3, "YCOR:LI11:203:FUNC CA PP")
  field(DOL4, "MGNT:LI11:1:LGPSCTRL.RVAL")
  field(LNK4, "YCOR:LI11:203:FUNC CA PP")
  field(DOL5, "MGNT:LI11:1:QUADCTRL.RVAL")
  field(LNK5, "YCOR:LI11:203:FUNC CA PP")
  field(DOL6, "MGNT:LI11:1:XCORCTRL.RVAL")
  field(LNK6, "YCOR:LI11:203:FUNC CA PP")
  field(DOL7, "MGNT:LI11:1:YCORCTRL.RVAL")
  field(LNK7, "YCOR:LI11:203:FUNC CA PP")
  field(DOL8, "MGNT:LI11:1:SOLNCTRL.RVAL")
  field(LNK8, "YCOR:LI11:203:FUNC CA PP")
  field(DOL9, "MGNT:LI11:1:KICKCTRL.RVAL")
  field(LNK9, "YCOR:LI11:203:FUNC CA PP")
  field(DOLA, "MGNT:LI11:1:SEXTCTRL.RVAL")
  field(LNKA, "YCOR:LI11:203:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "YCOR:LI11:203:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "YCOR:LI11:203:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "YCOR:LI11:203:EDES.PROC PP")
    field(LNK2, "YCOR:LI11:203:EACT.PROC PP")
    field(LNK3, "YCOR:LI11:203:EERR.DISA PP")
    field(LNK4, "YCOR:LI11:203:ECON.PROC PP")
    field(LNK5, "YCOR:LI11:203:BMAGX.PROC PP")
    field(LNK6, "YCOR:LI11:203:BMAGY.PROC PP")
    field(LNK7, "YCOR:LI11:203:BLEM.PROC PP")
    field(LNK8, "YCOR:LI11:203:BMOD.PROC PP")
    field(LNK9, "YCOR:LI11:203:EDESSAVE.PROC PP")
    field(LNKA, "YCOR:LI11:203:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"YCOR:LI11:203:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "YCOR:LI11:203:BMAX")
  field(DOL2, "YCOR:LI11:203:BMAX")
  field(DOL3, "YCOR:LI11:203:BMAX")
  field(DOL4, "YCOR:LI11:203:BMIN")
  field(DOL5, "YCOR:LI11:203:BMIN")
  field(DOL6, "YCOR:LI11:203:BMIN")
  field(LNK1, "YCOR:LI11:203:BMAGX.HOPR")
  field(LNK2, "YCOR:LI11:203:BMAGY.HOPR")
  field(LNK3, "YCOR:LI11:203:BLEM.HOPR")
  field(LNK4, "YCOR:LI11:203:BMAGX.LOPR PP")
  field(LNK5, "YCOR:LI11:203:BMAGY.LOPR PP")
  field(LNK6, "YCOR:LI11:203:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "YCOR:LI11:203:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "YCOR:LI11:203:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "YCOR:LI11:203:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "YCOR:LI11:203:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "YCOR:LI11:203:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:LI11:203:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:LI11:203:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:LI11:203:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:LI11:203:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:LI11:203:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "YCOR:LI11:203:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "YCOR:LI11:203:EDES NPP MS")
  field(INPB, "YCOR:LI11:203:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "YCOR:LI11:273:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI11:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI11:1:CTRL.RVAL")
  field(LNK1, "YCOR:LI11:273:FUNC CA PP")
  field(DOL2, "MGNT:LI11:1:BENDCTRL.RVAL")
  field(LNK2, "YCOR:LI11:273:FUNC CA PP")
  field(DOL3, "MGNT:LI11:1:BTRMCTRL.RVAL")
  field(LNK3, "YCOR:LI11:273:FUNC CA PP")
  field(DOL4, "MGNT:LI11:1:LGPSCTRL.RVAL")
  field(LNK4, "YCOR:LI11:273:FUNC CA PP")
  field(DOL5, "MGNT:LI11:1:QUADCTRL.RVAL")
  field(LNK5, "YCOR:LI11:273:FUNC CA PP")
  field(DOL6, "MGNT:LI11:1:XCORCTRL.RVAL")
  field(LNK6, "YCOR:LI11:273:FUNC CA PP")
  field(DOL7, "MGNT:LI11:1:YCORCTRL.RVAL")
  field(LNK7, "YCOR:LI11:273:FUNC CA PP")
  field(DOL8, "MGNT:LI11:1:SOLNCTRL.RVAL")
  field(LNK8, "YCOR:LI11:273:FUNC CA PP")
  field(DOL9, "MGNT:LI11:1:KICKCTRL.RVAL")
  field(LNK9, "YCOR:LI11:273:FUNC CA PP")
  field(DOLA, "MGNT:LI11:1:SEXTCTRL.RVAL")
  field(LNKA, "YCOR:LI11:273:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "YCOR:LI11:273:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "YCOR:LI11:273:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "YCOR:LI11:273:EDES.PROC PP")
    field(LNK2, "YCOR:LI11:273:EACT.PROC PP")
    field(LNK3, "YCOR:LI11:273:EERR.DISA PP")
    field(LNK4, "YCOR:LI11:273:ECON.PROC PP")
    field(LNK5, "YCOR:LI11:273:BMAGX.PROC PP")
    field(LNK6, "YCOR:LI11:273:BMAGY.PROC PP")
    field(LNK7, "YCOR:LI11:273:BLEM.PROC PP")
    field(LNK8, "YCOR:LI11:273:BMOD.PROC PP")
    field(LNK9, "YCOR:LI11:273:EDESSAVE.PROC PP")
    field(LNKA, "YCOR:LI11:273:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"YCOR:LI11:273:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "YCOR:LI11:273:BMAX")
  field(DOL2, "YCOR:LI11:273:BMAX")
  field(DOL3, "YCOR:LI11:273:BMAX")
  field(DOL4, "YCOR:LI11:273:BMIN")
  field(DOL5, "YCOR:LI11:273:BMIN")
  field(DOL6, "YCOR:LI11:273:BMIN")
  field(LNK1, "YCOR:LI11:273:BMAGX.HOPR")
  field(LNK2, "YCOR:LI11:273:BMAGY.HOPR")
  field(LNK3, "YCOR:LI11:273:BLEM.HOPR")
  field(LNK4, "YCOR:LI11:273:BMAGX.LOPR PP")
  field(LNK5, "YCOR:LI11:273:BMAGY.LOPR PP")
  field(LNK6, "YCOR:LI11:273:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "YCOR:LI11:273:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "YCOR:LI11:273:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "YCOR:LI11:273:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "YCOR:LI11:273:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "YCOR:LI11:273:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:LI11:273:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:LI11:273:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:LI11:273:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:LI11:273:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:LI11:273:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "YCOR:LI11:273:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "YCOR:LI11:273:EDES NPP MS")
  field(INPB, "YCOR:LI11:273:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "YCOR:LI11:305:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI11:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI11:1:CTRL.RVAL")
  field(LNK1, "YCOR:LI11:305:FUNC CA PP")
  field(DOL2, "MGNT:LI11:1:BENDCTRL.RVAL")
  field(LNK2, "YCOR:LI11:305:FUNC CA PP")
  field(DOL3, "MGNT:LI11:1:BTRMCTRL.RVAL")
  field(LNK3, "YCOR:LI11:305:FUNC CA PP")
  field(DOL4, "MGNT:LI11:1:LGPSCTRL.RVAL")
  field(LNK4, "YCOR:LI11:305:FUNC CA PP")
  field(DOL5, "MGNT:LI11:1:QUADCTRL.RVAL")
  field(LNK5, "YCOR:LI11:305:FUNC CA PP")
  field(DOL6, "MGNT:LI11:1:XCORCTRL.RVAL")
  field(LNK6, "YCOR:LI11:305:FUNC CA PP")
  field(DOL7, "MGNT:LI11:1:YCORCTRL.RVAL")
  field(LNK7, "YCOR:LI11:305:FUNC CA PP")
  field(DOL8, "MGNT:LI11:1:SOLNCTRL.RVAL")
  field(LNK8, "YCOR:LI11:305:FUNC CA PP")
  field(DOL9, "MGNT:LI11:1:KICKCTRL.RVAL")
  field(LNK9, "YCOR:LI11:305:FUNC CA PP")
  field(DOLA, "MGNT:LI11:1:SEXTCTRL.RVAL")
  field(LNKA, "YCOR:LI11:305:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "YCOR:LI11:305:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "YCOR:LI11:305:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "YCOR:LI11:305:EDES.PROC PP")
    field(LNK2, "YCOR:LI11:305:EACT.PROC PP")
    field(LNK3, "YCOR:LI11:305:EERR.DISA PP")
    field(LNK4, "YCOR:LI11:305:ECON.PROC PP")
    field(LNK5, "YCOR:LI11:305:BMAGX.PROC PP")
    field(LNK6, "YCOR:LI11:305:BMAGY.PROC PP")
    field(LNK7, "YCOR:LI11:305:BLEM.PROC PP")
    field(LNK8, "YCOR:LI11:305:BMOD.PROC PP")
    field(LNK9, "YCOR:LI11:305:EDESSAVE.PROC PP")
    field(LNKA, "YCOR:LI11:305:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"YCOR:LI11:305:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "YCOR:LI11:305:BMAX")
  field(DOL2, "YCOR:LI11:305:BMAX")
  field(DOL3, "YCOR:LI11:305:BMAX")
  field(DOL4, "YCOR:LI11:305:BMIN")
  field(DOL5, "YCOR:LI11:305:BMIN")
  field(DOL6, "YCOR:LI11:305:BMIN")
  field(LNK1, "YCOR:LI11:305:BMAGX.HOPR")
  field(LNK2, "YCOR:LI11:305:BMAGY.HOPR")
  field(LNK3, "YCOR:LI11:305:BLEM.HOPR")
  field(LNK4, "YCOR:LI11:305:BMAGX.LOPR PP")
  field(LNK5, "YCOR:LI11:305:BMAGY.LOPR PP")
  field(LNK6, "YCOR:LI11:305:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "YCOR:LI11:305:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "YCOR:LI11:305:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "YCOR:LI11:305:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "YCOR:LI11:305:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "YCOR:LI11:305:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:LI11:305:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:LI11:305:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:LI11:305:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:LI11:305:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:LI11:305:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "YCOR:LI11:305:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "YCOR:LI11:305:EDES NPP MS")
  field(INPB, "YCOR:LI11:305:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "YCOR:LI11:321:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI11:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI11:1:CTRL.RVAL")
  field(LNK1, "YCOR:LI11:321:FUNC CA PP")
  field(DOL2, "MGNT:LI11:1:BENDCTRL.RVAL")
  field(LNK2, "YCOR:LI11:321:FUNC CA PP")
  field(DOL3, "MGNT:LI11:1:BTRMCTRL.RVAL")
  field(LNK3, "YCOR:LI11:321:FUNC CA PP")
  field(DOL4, "MGNT:LI11:1:LGPSCTRL.RVAL")
  field(LNK4, "YCOR:LI11:321:FUNC CA PP")
  field(DOL5, "MGNT:LI11:1:QUADCTRL.RVAL")
  field(LNK5, "YCOR:LI11:321:FUNC CA PP")
  field(DOL6, "MGNT:LI11:1:XCORCTRL.RVAL")
  field(LNK6, "YCOR:LI11:321:FUNC CA PP")
  field(DOL7, "MGNT:LI11:1:YCORCTRL.RVAL")
  field(LNK7, "YCOR:LI11:321:FUNC CA PP")
  field(DOL8, "MGNT:LI11:1:SOLNCTRL.RVAL")
  field(LNK8, "YCOR:LI11:321:FUNC CA PP")
  field(DOL9, "MGNT:LI11:1:KICKCTRL.RVAL")
  field(LNK9, "YCOR:LI11:321:FUNC CA PP")
  field(DOLA, "MGNT:LI11:1:SEXTCTRL.RVAL")
  field(LNKA, "YCOR:LI11:321:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "YCOR:LI11:321:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "YCOR:LI11:321:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "YCOR:LI11:321:EDES.PROC PP")
    field(LNK2, "YCOR:LI11:321:EACT.PROC PP")
    field(LNK3, "YCOR:LI11:321:EERR.DISA PP")
    field(LNK4, "YCOR:LI11:321:ECON.PROC PP")
    field(LNK5, "YCOR:LI11:321:BMAGX.PROC PP")
    field(LNK6, "YCOR:LI11:321:BMAGY.PROC PP")
    field(LNK7, "YCOR:LI11:321:BLEM.PROC PP")
    field(LNK8, "YCOR:LI11:321:BMOD.PROC PP")
    field(LNK9, "YCOR:LI11:321:EDESSAVE.PROC PP")
    field(LNKA, "YCOR:LI11:321:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"YCOR:LI11:321:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "YCOR:LI11:321:BMAX")
  field(DOL2, "YCOR:LI11:321:BMAX")
  field(DOL3, "YCOR:LI11:321:BMAX")
  field(DOL4, "YCOR:LI11:321:BMIN")
  field(DOL5, "YCOR:LI11:321:BMIN")
  field(DOL6, "YCOR:LI11:321:BMIN")
  field(LNK1, "YCOR:LI11:321:BMAGX.HOPR")
  field(LNK2, "YCOR:LI11:321:BMAGY.HOPR")
  field(LNK3, "YCOR:LI11:321:BLEM.HOPR")
  field(LNK4, "YCOR:LI11:321:BMAGX.LOPR PP")
  field(LNK5, "YCOR:LI11:321:BMAGY.LOPR PP")
  field(LNK6, "YCOR:LI11:321:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "YCOR:LI11:321:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "YCOR:LI11:321:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "YCOR:LI11:321:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "YCOR:LI11:321:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "YCOR:LI11:321:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:LI11:321:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:LI11:321:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:LI11:321:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:LI11:321:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:LI11:321:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "YCOR:LI11:321:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "YCOR:LI11:321:EDES NPP MS")
  field(INPB, "YCOR:LI11:321:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "YCOR:LI11:365:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI11:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI11:1:CTRL.RVAL")
  field(LNK1, "YCOR:LI11:365:FUNC CA PP")
  field(DOL2, "MGNT:LI11:1:BENDCTRL.RVAL")
  field(LNK2, "YCOR:LI11:365:FUNC CA PP")
  field(DOL3, "MGNT:LI11:1:BTRMCTRL.RVAL")
  field(LNK3, "YCOR:LI11:365:FUNC CA PP")
  field(DOL4, "MGNT:LI11:1:LGPSCTRL.RVAL")
  field(LNK4, "YCOR:LI11:365:FUNC CA PP")
  field(DOL5, "MGNT:LI11:1:QUADCTRL.RVAL")
  field(LNK5, "YCOR:LI11:365:FUNC CA PP")
  field(DOL6, "MGNT:LI11:1:XCORCTRL.RVAL")
  field(LNK6, "YCOR:LI11:365:FUNC CA PP")
  field(DOL7, "MGNT:LI11:1:YCORCTRL.RVAL")
  field(LNK7, "YCOR:LI11:365:FUNC CA PP")
  field(DOL8, "MGNT:LI11:1:SOLNCTRL.RVAL")
  field(LNK8, "YCOR:LI11:365:FUNC CA PP")
  field(DOL9, "MGNT:LI11:1:KICKCTRL.RVAL")
  field(LNK9, "YCOR:LI11:365:FUNC CA PP")
  field(DOLA, "MGNT:LI11:1:SEXTCTRL.RVAL")
  field(LNKA, "YCOR:LI11:365:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "YCOR:LI11:365:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "YCOR:LI11:365:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "YCOR:LI11:365:EDES.PROC PP")
    field(LNK2, "YCOR:LI11:365:EACT.PROC PP")
    field(LNK3, "YCOR:LI11:365:EERR.DISA PP")
    field(LNK4, "YCOR:LI11:365:ECON.PROC PP")
    field(LNK5, "YCOR:LI11:365:BMAGX.PROC PP")
    field(LNK6, "YCOR:LI11:365:BMAGY.PROC PP")
    field(LNK7, "YCOR:LI11:365:BLEM.PROC PP")
    field(LNK8, "YCOR:LI11:365:BMOD.PROC PP")
    field(LNK9, "YCOR:LI11:365:EDESSAVE.PROC PP")
    field(LNKA, "YCOR:LI11:365:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"YCOR:LI11:365:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "YCOR:LI11:365:BMAX")
  field(DOL2, "YCOR:LI11:365:BMAX")
  field(DOL3, "YCOR:LI11:365:BMAX")
  field(DOL4, "YCOR:LI11:365:BMIN")
  field(DOL5, "YCOR:LI11:365:BMIN")
  field(DOL6, "YCOR:LI11:365:BMIN")
  field(LNK1, "YCOR:LI11:365:BMAGX.HOPR")
  field(LNK2, "YCOR:LI11:365:BMAGY.HOPR")
  field(LNK3, "YCOR:LI11:365:BLEM.HOPR")
  field(LNK4, "YCOR:LI11:365:BMAGX.LOPR PP")
  field(LNK5, "YCOR:LI11:365:BMAGY.LOPR PP")
  field(LNK6, "YCOR:LI11:365:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "YCOR:LI11:365:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "YCOR:LI11:365:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "YCOR:LI11:365:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "YCOR:LI11:365:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "YCOR:LI11:365:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:LI11:365:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:LI11:365:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:LI11:365:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:LI11:365:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:LI11:365:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "YCOR:LI11:365:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "YCOR:LI11:365:EDES NPP MS")
  field(INPB, "YCOR:LI11:365:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "YCOR:LI11:399:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI11:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI11:1:CTRL.RVAL")
  field(LNK1, "YCOR:LI11:399:FUNC CA PP")
  field(DOL2, "MGNT:LI11:1:BENDCTRL.RVAL")
  field(LNK2, "YCOR:LI11:399:FUNC CA PP")
  field(DOL3, "MGNT:LI11:1:BTRMCTRL.RVAL")
  field(LNK3, "YCOR:LI11:399:FUNC CA PP")
  field(DOL4, "MGNT:LI11:1:LGPSCTRL.RVAL")
  field(LNK4, "YCOR:LI11:399:FUNC CA PP")
  field(DOL5, "MGNT:LI11:1:QUADCTRL.RVAL")
  field(LNK5, "YCOR:LI11:399:FUNC CA PP")
  field(DOL6, "MGNT:LI11:1:XCORCTRL.RVAL")
  field(LNK6, "YCOR:LI11:399:FUNC CA PP")
  field(DOL7, "MGNT:LI11:1:YCORCTRL.RVAL")
  field(LNK7, "YCOR:LI11:399:FUNC CA PP")
  field(DOL8, "MGNT:LI11:1:SOLNCTRL.RVAL")
  field(LNK8, "YCOR:LI11:399:FUNC CA PP")
  field(DOL9, "MGNT:LI11:1:KICKCTRL.RVAL")
  field(LNK9, "YCOR:LI11:399:FUNC CA PP")
  field(DOLA, "MGNT:LI11:1:SEXTCTRL.RVAL")
  field(LNKA, "YCOR:LI11:399:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "YCOR:LI11:399:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "YCOR:LI11:399:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "YCOR:LI11:399:EDES.PROC PP")
    field(LNK2, "YCOR:LI11:399:EACT.PROC PP")
    field(LNK3, "YCOR:LI11:399:EERR.DISA PP")
    field(LNK4, "YCOR:LI11:399:ECON.PROC PP")
    field(LNK5, "YCOR:LI11:399:BMAGX.PROC PP")
    field(LNK6, "YCOR:LI11:399:BMAGY.PROC PP")
    field(LNK7, "YCOR:LI11:399:BLEM.PROC PP")
    field(LNK8, "YCOR:LI11:399:BMOD.PROC PP")
    field(LNK9, "YCOR:LI11:399:EDESSAVE.PROC PP")
    field(LNKA, "YCOR:LI11:399:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"YCOR:LI11:399:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "YCOR:LI11:399:BMAX")
  field(DOL2, "YCOR:LI11:399:BMAX")
  field(DOL3, "YCOR:LI11:399:BMAX")
  field(DOL4, "YCOR:LI11:399:BMIN")
  field(DOL5, "YCOR:LI11:399:BMIN")
  field(DOL6, "YCOR:LI11:399:BMIN")
  field(LNK1, "YCOR:LI11:399:BMAGX.HOPR")
  field(LNK2, "YCOR:LI11:399:BMAGY.HOPR")
  field(LNK3, "YCOR:LI11:399:BLEM.HOPR")
  field(LNK4, "YCOR:LI11:399:BMAGX.LOPR PP")
  field(LNK5, "YCOR:LI11:399:BMAGY.LOPR PP")
  field(LNK6, "YCOR:LI11:399:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "YCOR:LI11:399:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "YCOR:LI11:399:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "YCOR:LI11:399:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "YCOR:LI11:399:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "YCOR:LI11:399:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:LI11:399:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:LI11:399:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:LI11:399:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:LI11:399:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:LI11:399:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "YCOR:LI11:399:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "YCOR:LI11:399:EDES NPP MS")
  field(INPB, "YCOR:LI11:399:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "QUAD:LI11:132:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI11:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI11:1:CTRL.RVAL")
  field(LNK1, "QUAD:LI11:132:FUNC CA PP")
  field(DOL2, "MGNT:LI11:1:BENDCTRL.RVAL")
  field(LNK2, "QUAD:LI11:132:FUNC CA PP")
  field(DOL3, "MGNT:LI11:1:BTRMCTRL.RVAL")
  field(LNK3, "QUAD:LI11:132:FUNC CA PP")
  field(DOL4, "MGNT:LI11:1:LGPSCTRL.RVAL")
  field(LNK4, "QUAD:LI11:132:FUNC CA PP")
  field(DOL5, "MGNT:LI11:1:QUADCTRL.RVAL")
  field(LNK5, "QUAD:LI11:132:FUNC CA PP")
  field(DOL6, "MGNT:LI11:1:XCORCTRL.RVAL")
  field(LNK6, "QUAD:LI11:132:FUNC CA PP")
  field(DOL7, "MGNT:LI11:1:YCORCTRL.RVAL")
  field(LNK7, "QUAD:LI11:132:FUNC CA PP")
  field(DOL8, "MGNT:LI11:1:SOLNCTRL.RVAL")
  field(LNK8, "QUAD:LI11:132:FUNC CA PP")
  field(DOL9, "MGNT:LI11:1:KICKCTRL.RVAL")
  field(LNK9, "QUAD:LI11:132:FUNC CA PP")
  field(DOLA, "MGNT:LI11:1:SEXTCTRL.RVAL")
  field(LNKA, "QUAD:LI11:132:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "QUAD:LI11:132:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "QUAD:LI11:132:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "QUAD:LI11:132:EDES.PROC PP")
    field(LNK2, "QUAD:LI11:132:EACT.PROC PP")
    field(LNK3, "QUAD:LI11:132:EERR.DISA PP")
    field(LNK4, "QUAD:LI11:132:ECON.PROC PP")
    field(LNK5, "QUAD:LI11:132:BMAGX.PROC PP")
    field(LNK6, "QUAD:LI11:132:BMAGY.PROC PP")
    field(LNK7, "QUAD:LI11:132:BLEM.PROC PP")
    field(LNK8, "QUAD:LI11:132:BMOD.PROC PP")
    field(LNK9, "QUAD:LI11:132:EDESSAVE.PROC PP")
    field(LNKA, "QUAD:LI11:132:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"QUAD:LI11:132:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "QUAD:LI11:132:BMAX")
  field(DOL2, "QUAD:LI11:132:BMAX")
  field(DOL3, "QUAD:LI11:132:BMAX")
  field(DOL4, "QUAD:LI11:132:BMIN")
  field(DOL5, "QUAD:LI11:132:BMIN")
  field(DOL6, "QUAD:LI11:132:BMIN")
  field(LNK1, "QUAD:LI11:132:BMAGX.HOPR")
  field(LNK2, "QUAD:LI11:132:BMAGY.HOPR")
  field(LNK3, "QUAD:LI11:132:BLEM.HOPR")
  field(LNK4, "QUAD:LI11:132:BMAGX.LOPR PP")
  field(LNK5, "QUAD:LI11:132:BMAGY.LOPR PP")
  field(LNK6, "QUAD:LI11:132:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "QUAD:LI11:132:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "QUAD:LI11:132:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "QUAD:LI11:132:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "QUAD:LI11:132:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "QUAD:LI11:132:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI11:132:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI11:132:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI11:132:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI11:132:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI11:132:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "QUAD:LI11:132:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "QUAD:LI11:132:EDES NPP MS")
  field(INPB, "QUAD:LI11:132:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "QUAD:LI11:201:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI11:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI11:1:CTRL.RVAL")
  field(LNK1, "QUAD:LI11:201:FUNC CA PP")
  field(DOL2, "MGNT:LI11:1:BENDCTRL.RVAL")
  field(LNK2, "QUAD:LI11:201:FUNC CA PP")
  field(DOL3, "MGNT:LI11:1:BTRMCTRL.RVAL")
  field(LNK3, "QUAD:LI11:201:FUNC CA PP")
  field(DOL4, "MGNT:LI11:1:LGPSCTRL.RVAL")
  field(LNK4, "QUAD:LI11:201:FUNC CA PP")
  field(DOL5, "MGNT:LI11:1:QUADCTRL.RVAL")
  field(LNK5, "QUAD:LI11:201:FUNC CA PP")
  field(DOL6, "MGNT:LI11:1:XCORCTRL.RVAL")
  field(LNK6, "QUAD:LI11:201:FUNC CA PP")
  field(DOL7, "MGNT:LI11:1:YCORCTRL.RVAL")
  field(LNK7, "QUAD:LI11:201:FUNC CA PP")
  field(DOL8, "MGNT:LI11:1:SOLNCTRL.RVAL")
  field(LNK8, "QUAD:LI11:201:FUNC CA PP")
  field(DOL9, "MGNT:LI11:1:KICKCTRL.RVAL")
  field(LNK9, "QUAD:LI11:201:FUNC CA PP")
  field(DOLA, "MGNT:LI11:1:SEXTCTRL.RVAL")
  field(LNKA, "QUAD:LI11:201:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "QUAD:LI11:201:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "QUAD:LI11:201:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "QUAD:LI11:201:EDES.PROC PP")
    field(LNK2, "QUAD:LI11:201:EACT.PROC PP")
    field(LNK3, "QUAD:LI11:201:EERR.DISA PP")
    field(LNK4, "QUAD:LI11:201:ECON.PROC PP")
    field(LNK5, "QUAD:LI11:201:BMAGX.PROC PP")
    field(LNK6, "QUAD:LI11:201:BMAGY.PROC PP")
    field(LNK7, "QUAD:LI11:201:BLEM.PROC PP")
    field(LNK8, "QUAD:LI11:201:BMOD.PROC PP")
    field(LNK9, "QUAD:LI11:201:EDESSAVE.PROC PP")
    field(LNKA, "QUAD:LI11:201:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"QUAD:LI11:201:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "QUAD:LI11:201:BMAX")
  field(DOL2, "QUAD:LI11:201:BMAX")
  field(DOL3, "QUAD:LI11:201:BMAX")
  field(DOL4, "QUAD:LI11:201:BMIN")
  field(DOL5, "QUAD:LI11:201:BMIN")
  field(DOL6, "QUAD:LI11:201:BMIN")
  field(LNK1, "QUAD:LI11:201:BMAGX.HOPR")
  field(LNK2, "QUAD:LI11:201:BMAGY.HOPR")
  field(LNK3, "QUAD:LI11:201:BLEM.HOPR")
  field(LNK4, "QUAD:LI11:201:BMAGX.LOPR PP")
  field(LNK5, "QUAD:LI11:201:BMAGY.LOPR PP")
  field(LNK6, "QUAD:LI11:201:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "QUAD:LI11:201:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "QUAD:LI11:201:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "QUAD:LI11:201:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "QUAD:LI11:201:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "QUAD:LI11:201:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI11:201:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI11:201:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI11:201:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI11:201:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI11:201:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "QUAD:LI11:201:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "QUAD:LI11:201:EDES NPP MS")
  field(INPB, "QUAD:LI11:201:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "QUAD:LI11:265:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI11:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI11:1:CTRL.RVAL")
  field(LNK1, "QUAD:LI11:265:FUNC CA PP")
  field(DOL2, "MGNT:LI11:1:BENDCTRL.RVAL")
  field(LNK2, "QUAD:LI11:265:FUNC CA PP")
  field(DOL3, "MGNT:LI11:1:BTRMCTRL.RVAL")
  field(LNK3, "QUAD:LI11:265:FUNC CA PP")
  field(DOL4, "MGNT:LI11:1:LGPSCTRL.RVAL")
  field(LNK4, "QUAD:LI11:265:FUNC CA PP")
  field(DOL5, "MGNT:LI11:1:QUADCTRL.RVAL")
  field(LNK5, "QUAD:LI11:265:FUNC CA PP")
  field(DOL6, "MGNT:LI11:1:XCORCTRL.RVAL")
  field(LNK6, "QUAD:LI11:265:FUNC CA PP")
  field(DOL7, "MGNT:LI11:1:YCORCTRL.RVAL")
  field(LNK7, "QUAD:LI11:265:FUNC CA PP")
  field(DOL8, "MGNT:LI11:1:SOLNCTRL.RVAL")
  field(LNK8, "QUAD:LI11:265:FUNC CA PP")
  field(DOL9, "MGNT:LI11:1:KICKCTRL.RVAL")
  field(LNK9, "QUAD:LI11:265:FUNC CA PP")
  field(DOLA, "MGNT:LI11:1:SEXTCTRL.RVAL")
  field(LNKA, "QUAD:LI11:265:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "QUAD:LI11:265:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "QUAD:LI11:265:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "QUAD:LI11:265:EDES.PROC PP")
    field(LNK2, "QUAD:LI11:265:EACT.PROC PP")
    field(LNK3, "QUAD:LI11:265:EERR.DISA PP")
    field(LNK4, "QUAD:LI11:265:ECON.PROC PP")
    field(LNK5, "QUAD:LI11:265:BMAGX.PROC PP")
    field(LNK6, "QUAD:LI11:265:BMAGY.PROC PP")
    field(LNK7, "QUAD:LI11:265:BLEM.PROC PP")
    field(LNK8, "QUAD:LI11:265:BMOD.PROC PP")
    field(LNK9, "QUAD:LI11:265:EDESSAVE.PROC PP")
    field(LNKA, "QUAD:LI11:265:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"QUAD:LI11:265:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "QUAD:LI11:265:BMAX")
  field(DOL2, "QUAD:LI11:265:BMAX")
  field(DOL3, "QUAD:LI11:265:BMAX")
  field(DOL4, "QUAD:LI11:265:BMIN")
  field(DOL5, "QUAD:LI11:265:BMIN")
  field(DOL6, "QUAD:LI11:265:BMIN")
  field(LNK1, "QUAD:LI11:265:BMAGX.HOPR")
  field(LNK2, "QUAD:LI11:265:BMAGY.HOPR")
  field(LNK3, "QUAD:LI11:265:BLEM.HOPR")
  field(LNK4, "QUAD:LI11:265:BMAGX.LOPR PP")
  field(LNK5, "QUAD:LI11:265:BMAGY.LOPR PP")
  field(LNK6, "QUAD:LI11:265:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "QUAD:LI11:265:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "QUAD:LI11:265:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "QUAD:LI11:265:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "QUAD:LI11:265:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "QUAD:LI11:265:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI11:265:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI11:265:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI11:265:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI11:265:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI11:265:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "QUAD:LI11:265:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "QUAD:LI11:265:EDES NPP MS")
  field(INPB, "QUAD:LI11:265:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "QUAD:LI11:301:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI11:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI11:1:CTRL.RVAL")
  field(LNK1, "QUAD:LI11:301:FUNC CA PP")
  field(DOL2, "MGNT:LI11:1:BENDCTRL.RVAL")
  field(LNK2, "QUAD:LI11:301:FUNC CA PP")
  field(DOL3, "MGNT:LI11:1:BTRMCTRL.RVAL")
  field(LNK3, "QUAD:LI11:301:FUNC CA PP")
  field(DOL4, "MGNT:LI11:1:LGPSCTRL.RVAL")
  field(LNK4, "QUAD:LI11:301:FUNC CA PP")
  field(DOL5, "MGNT:LI11:1:QUADCTRL.RVAL")
  field(LNK5, "QUAD:LI11:301:FUNC CA PP")
  field(DOL6, "MGNT:LI11:1:XCORCTRL.RVAL")
  field(LNK6, "QUAD:LI11:301:FUNC CA PP")
  field(DOL7, "MGNT:LI11:1:YCORCTRL.RVAL")
  field(LNK7, "QUAD:LI11:301:FUNC CA PP")
  field(DOL8, "MGNT:LI11:1:SOLNCTRL.RVAL")
  field(LNK8, "QUAD:LI11:301:FUNC CA PP")
  field(DOL9, "MGNT:LI11:1:KICKCTRL.RVAL")
  field(LNK9, "QUAD:LI11:301:FUNC CA PP")
  field(DOLA, "MGNT:LI11:1:SEXTCTRL.RVAL")
  field(LNKA, "QUAD:LI11:301:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "QUAD:LI11:301:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "QUAD:LI11:301:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "QUAD:LI11:301:EDES.PROC PP")
    field(LNK2, "QUAD:LI11:301:EACT.PROC PP")
    field(LNK3, "QUAD:LI11:301:EERR.DISA PP")
    field(LNK4, "QUAD:LI11:301:ECON.PROC PP")
    field(LNK5, "QUAD:LI11:301:BMAGX.PROC PP")
    field(LNK6, "QUAD:LI11:301:BMAGY.PROC PP")
    field(LNK7, "QUAD:LI11:301:BLEM.PROC PP")
    field(LNK8, "QUAD:LI11:301:BMOD.PROC PP")
    field(LNK9, "QUAD:LI11:301:EDESSAVE.PROC PP")
    field(LNKA, "QUAD:LI11:301:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"QUAD:LI11:301:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "QUAD:LI11:301:BMAX")
  field(DOL2, "QUAD:LI11:301:BMAX")
  field(DOL3, "QUAD:LI11:301:BMAX")
  field(DOL4, "QUAD:LI11:301:BMIN")
  field(DOL5, "QUAD:LI11:301:BMIN")
  field(DOL6, "QUAD:LI11:301:BMIN")
  field(LNK1, "QUAD:LI11:301:BMAGX.HOPR")
  field(LNK2, "QUAD:LI11:301:BMAGY.HOPR")
  field(LNK3, "QUAD:LI11:301:BLEM.HOPR")
  field(LNK4, "QUAD:LI11:301:BMAGX.LOPR PP")
  field(LNK5, "QUAD:LI11:301:BMAGY.LOPR PP")
  field(LNK6, "QUAD:LI11:301:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "QUAD:LI11:301:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "QUAD:LI11:301:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "QUAD:LI11:301:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "QUAD:LI11:301:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "QUAD:LI11:301:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI11:301:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI11:301:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI11:301:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI11:301:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI11:301:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "QUAD:LI11:301:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "QUAD:LI11:301:EDES NPP MS")
  field(INPB, "QUAD:LI11:301:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "QUAD:LI11:312:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI11:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI11:1:CTRL.RVAL")
  field(LNK1, "QUAD:LI11:312:FUNC CA PP")
  field(DOL2, "MGNT:LI11:1:BENDCTRL.RVAL")
  field(LNK2, "QUAD:LI11:312:FUNC CA PP")
  field(DOL3, "MGNT:LI11:1:BTRMCTRL.RVAL")
  field(LNK3, "QUAD:LI11:312:FUNC CA PP")
  field(DOL4, "MGNT:LI11:1:LGPSCTRL.RVAL")
  field(LNK4, "QUAD:LI11:312:FUNC CA PP")
  field(DOL5, "MGNT:LI11:1:QUADCTRL.RVAL")
  field(LNK5, "QUAD:LI11:312:FUNC CA PP")
  field(DOL6, "MGNT:LI11:1:XCORCTRL.RVAL")
  field(LNK6, "QUAD:LI11:312:FUNC CA PP")
  field(DOL7, "MGNT:LI11:1:YCORCTRL.RVAL")
  field(LNK7, "QUAD:LI11:312:FUNC CA PP")
  field(DOL8, "MGNT:LI11:1:SOLNCTRL.RVAL")
  field(LNK8, "QUAD:LI11:312:FUNC CA PP")
  field(DOL9, "MGNT:LI11:1:KICKCTRL.RVAL")
  field(LNK9, "QUAD:LI11:312:FUNC CA PP")
  field(DOLA, "MGNT:LI11:1:SEXTCTRL.RVAL")
  field(LNKA, "QUAD:LI11:312:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "QUAD:LI11:312:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "QUAD:LI11:312:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "QUAD:LI11:312:EDES.PROC PP")
    field(LNK2, "QUAD:LI11:312:EACT.PROC PP")
    field(LNK3, "QUAD:LI11:312:EERR.DISA PP")
    field(LNK4, "QUAD:LI11:312:ECON.PROC PP")
    field(LNK5, "QUAD:LI11:312:BMAGX.PROC PP")
    field(LNK6, "QUAD:LI11:312:BMAGY.PROC PP")
    field(LNK7, "QUAD:LI11:312:BLEM.PROC PP")
    field(LNK8, "QUAD:LI11:312:BMOD.PROC PP")
    field(LNK9, "QUAD:LI11:312:EDESSAVE.PROC PP")
    field(LNKA, "QUAD:LI11:312:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"QUAD:LI11:312:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "QUAD:LI11:312:BMAX")
  field(DOL2, "QUAD:LI11:312:BMAX")
  field(DOL3, "QUAD:LI11:312:BMAX")
  field(DOL4, "QUAD:LI11:312:BMIN")
  field(DOL5, "QUAD:LI11:312:BMIN")
  field(DOL6, "QUAD:LI11:312:BMIN")
  field(LNK1, "QUAD:LI11:312:BMAGX.HOPR")
  field(LNK2, "QUAD:LI11:312:BMAGY.HOPR")
  field(LNK3, "QUAD:LI11:312:BLEM.HOPR")
  field(LNK4, "QUAD:LI11:312:BMAGX.LOPR PP")
  field(LNK5, "QUAD:LI11:312:BMAGY.LOPR PP")
  field(LNK6, "QUAD:LI11:312:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "QUAD:LI11:312:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "QUAD:LI11:312:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "QUAD:LI11:312:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "QUAD:LI11:312:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "QUAD:LI11:312:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI11:312:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI11:312:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI11:312:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI11:312:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI11:312:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "QUAD:LI11:312:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "QUAD:LI11:312:EDES NPP MS")
  field(INPB, "QUAD:LI11:312:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "QUAD:LI11:317:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI11:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI11:1:CTRL.RVAL")
  field(LNK1, "QUAD:LI11:317:FUNC CA PP")
  field(DOL2, "MGNT:LI11:1:BENDCTRL.RVAL")
  field(LNK2, "QUAD:LI11:317:FUNC CA PP")
  field(DOL3, "MGNT:LI11:1:BTRMCTRL.RVAL")
  field(LNK3, "QUAD:LI11:317:FUNC CA PP")
  field(DOL4, "MGNT:LI11:1:LGPSCTRL.RVAL")
  field(LNK4, "QUAD:LI11:317:FUNC CA PP")
  field(DOL5, "MGNT:LI11:1:QUADCTRL.RVAL")
  field(LNK5, "QUAD:LI11:317:FUNC CA PP")
  field(DOL6, "MGNT:LI11:1:XCORCTRL.RVAL")
  field(LNK6, "QUAD:LI11:317:FUNC CA PP")
  field(DOL7, "MGNT:LI11:1:YCORCTRL.RVAL")
  field(LNK7, "QUAD:LI11:317:FUNC CA PP")
  field(DOL8, "MGNT:LI11:1:SOLNCTRL.RVAL")
  field(LNK8, "QUAD:LI11:317:FUNC CA PP")
  field(DOL9, "MGNT:LI11:1:KICKCTRL.RVAL")
  field(LNK9, "QUAD:LI11:317:FUNC CA PP")
  field(DOLA, "MGNT:LI11:1:SEXTCTRL.RVAL")
  field(LNKA, "QUAD:LI11:317:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "QUAD:LI11:317:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "QUAD:LI11:317:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "QUAD:LI11:317:EDES.PROC PP")
    field(LNK2, "QUAD:LI11:317:EACT.PROC PP")
    field(LNK3, "QUAD:LI11:317:EERR.DISA PP")
    field(LNK4, "QUAD:LI11:317:ECON.PROC PP")
    field(LNK5, "QUAD:LI11:317:BMAGX.PROC PP")
    field(LNK6, "QUAD:LI11:317:BMAGY.PROC PP")
    field(LNK7, "QUAD:LI11:317:BLEM.PROC PP")
    field(LNK8, "QUAD:LI11:317:BMOD.PROC PP")
    field(LNK9, "QUAD:LI11:317:EDESSAVE.PROC PP")
    field(LNKA, "QUAD:LI11:317:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"QUAD:LI11:317:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "QUAD:LI11:317:BMAX")
  field(DOL2, "QUAD:LI11:317:BMAX")
  field(DOL3, "QUAD:LI11:317:BMAX")
  field(DOL4, "QUAD:LI11:317:BMIN")
  field(DOL5, "QUAD:LI11:317:BMIN")
  field(DOL6, "QUAD:LI11:317:BMIN")
  field(LNK1, "QUAD:LI11:317:BMAGX.HOPR")
  field(LNK2, "QUAD:LI11:317:BMAGY.HOPR")
  field(LNK3, "QUAD:LI11:317:BLEM.HOPR")
  field(LNK4, "QUAD:LI11:317:BMAGX.LOPR PP")
  field(LNK5, "QUAD:LI11:317:BMAGY.LOPR PP")
  field(LNK6, "QUAD:LI11:317:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "QUAD:LI11:317:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "QUAD:LI11:317:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "QUAD:LI11:317:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "QUAD:LI11:317:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "QUAD:LI11:317:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI11:317:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI11:317:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI11:317:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI11:317:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI11:317:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "QUAD:LI11:317:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "QUAD:LI11:317:EDES NPP MS")
  field(INPB, "QUAD:LI11:317:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "QUAD:LI11:340:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI11:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI11:1:CTRL.RVAL")
  field(LNK1, "QUAD:LI11:340:FUNC CA PP")
  field(DOL2, "MGNT:LI11:1:BENDCTRL.RVAL")
  field(LNK2, "QUAD:LI11:340:FUNC CA PP")
  field(DOL3, "MGNT:LI11:1:BTRMCTRL.RVAL")
  field(LNK3, "QUAD:LI11:340:FUNC CA PP")
  field(DOL4, "MGNT:LI11:1:LGPSCTRL.RVAL")
  field(LNK4, "QUAD:LI11:340:FUNC CA PP")
  field(DOL5, "MGNT:LI11:1:QUADCTRL.RVAL")
  field(LNK5, "QUAD:LI11:340:FUNC CA PP")
  field(DOL6, "MGNT:LI11:1:XCORCTRL.RVAL")
  field(LNK6, "QUAD:LI11:340:FUNC CA PP")
  field(DOL7, "MGNT:LI11:1:YCORCTRL.RVAL")
  field(LNK7, "QUAD:LI11:340:FUNC CA PP")
  field(DOL8, "MGNT:LI11:1:SOLNCTRL.RVAL")
  field(LNK8, "QUAD:LI11:340:FUNC CA PP")
  field(DOL9, "MGNT:LI11:1:KICKCTRL.RVAL")
  field(LNK9, "QUAD:LI11:340:FUNC CA PP")
  field(DOLA, "MGNT:LI11:1:SEXTCTRL.RVAL")
  field(LNKA, "QUAD:LI11:340:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "QUAD:LI11:340:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "QUAD:LI11:340:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "QUAD:LI11:340:EDES.PROC PP")
    field(LNK2, "QUAD:LI11:340:EACT.PROC PP")
    field(LNK3, "QUAD:LI11:340:EERR.DISA PP")
    field(LNK4, "QUAD:LI11:340:ECON.PROC PP")
    field(LNK5, "QUAD:LI11:340:BMAGX.PROC PP")
    field(LNK6, "QUAD:LI11:340:BMAGY.PROC PP")
    field(LNK7, "QUAD:LI11:340:BLEM.PROC PP")
    field(LNK8, "QUAD:LI11:340:BMOD.PROC PP")
    field(LNK9, "QUAD:LI11:340:EDESSAVE.PROC PP")
    field(LNKA, "QUAD:LI11:340:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"QUAD:LI11:340:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "QUAD:LI11:340:BMAX")
  field(DOL2, "QUAD:LI11:340:BMAX")
  field(DOL3, "QUAD:LI11:340:BMAX")
  field(DOL4, "QUAD:LI11:340:BMIN")
  field(DOL5, "QUAD:LI11:340:BMIN")
  field(DOL6, "QUAD:LI11:340:BMIN")
  field(LNK1, "QUAD:LI11:340:BMAGX.HOPR")
  field(LNK2, "QUAD:LI11:340:BMAGY.HOPR")
  field(LNK3, "QUAD:LI11:340:BLEM.HOPR")
  field(LNK4, "QUAD:LI11:340:BMAGX.LOPR PP")
  field(LNK5, "QUAD:LI11:340:BMAGY.LOPR PP")
  field(LNK6, "QUAD:LI11:340:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "QUAD:LI11:340:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "QUAD:LI11:340:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "QUAD:LI11:340:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "QUAD:LI11:340:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "QUAD:LI11:340:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI11:340:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI11:340:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI11:340:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI11:340:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI11:340:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "QUAD:LI11:340:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "QUAD:LI11:340:EDES NPP MS")
  field(INPB, "QUAD:LI11:340:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "QUAD:LI11:352:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI11:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI11:1:CTRL.RVAL")
  field(LNK1, "QUAD:LI11:352:FUNC CA PP")
  field(DOL2, "MGNT:LI11:1:BENDCTRL.RVAL")
  field(LNK2, "QUAD:LI11:352:FUNC CA PP")
  field(DOL3, "MGNT:LI11:1:BTRMCTRL.RVAL")
  field(LNK3, "QUAD:LI11:352:FUNC CA PP")
  field(DOL4, "MGNT:LI11:1:LGPSCTRL.RVAL")
  field(LNK4, "QUAD:LI11:352:FUNC CA PP")
  field(DOL5, "MGNT:LI11:1:QUADCTRL.RVAL")
  field(LNK5, "QUAD:LI11:352:FUNC CA PP")
  field(DOL6, "MGNT:LI11:1:XCORCTRL.RVAL")
  field(LNK6, "QUAD:LI11:352:FUNC CA PP")
  field(DOL7, "MGNT:LI11:1:YCORCTRL.RVAL")
  field(LNK7, "QUAD:LI11:352:FUNC CA PP")
  field(DOL8, "MGNT:LI11:1:SOLNCTRL.RVAL")
  field(LNK8, "QUAD:LI11:352:FUNC CA PP")
  field(DOL9, "MGNT:LI11:1:KICKCTRL.RVAL")
  field(LNK9, "QUAD:LI11:352:FUNC CA PP")
  field(DOLA, "MGNT:LI11:1:SEXTCTRL.RVAL")
  field(LNKA, "QUAD:LI11:352:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "QUAD:LI11:352:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "QUAD:LI11:352:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "QUAD:LI11:352:EDES.PROC PP")
    field(LNK2, "QUAD:LI11:352:EACT.PROC PP")
    field(LNK3, "QUAD:LI11:352:EERR.DISA PP")
    field(LNK4, "QUAD:LI11:352:ECON.PROC PP")
    field(LNK5, "QUAD:LI11:352:BMAGX.PROC PP")
    field(LNK6, "QUAD:LI11:352:BMAGY.PROC PP")
    field(LNK7, "QUAD:LI11:352:BLEM.PROC PP")
    field(LNK8, "QUAD:LI11:352:BMOD.PROC PP")
    field(LNK9, "QUAD:LI11:352:EDESSAVE.PROC PP")
    field(LNKA, "QUAD:LI11:352:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"QUAD:LI11:352:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "QUAD:LI11:352:BMAX")
  field(DOL2, "QUAD:LI11:352:BMAX")
  field(DOL3, "QUAD:LI11:352:BMAX")
  field(DOL4, "QUAD:LI11:352:BMIN")
  field(DOL5, "QUAD:LI11:352:BMIN")
  field(DOL6, "QUAD:LI11:352:BMIN")
  field(LNK1, "QUAD:LI11:352:BMAGX.HOPR")
  field(LNK2, "QUAD:LI11:352:BMAGY.HOPR")
  field(LNK3, "QUAD:LI11:352:BLEM.HOPR")
  field(LNK4, "QUAD:LI11:352:BMAGX.LOPR PP")
  field(LNK5, "QUAD:LI11:352:BMAGY.LOPR PP")
  field(LNK6, "QUAD:LI11:352:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "QUAD:LI11:352:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "QUAD:LI11:352:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "QUAD:LI11:352:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "QUAD:LI11:352:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "QUAD:LI11:352:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI11:352:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI11:352:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI11:352:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI11:352:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI11:352:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "QUAD:LI11:352:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "QUAD:LI11:352:EDES NPP MS")
  field(INPB, "QUAD:LI11:352:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "QUAD:LI11:358:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI11:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI11:1:CTRL.RVAL")
  field(LNK1, "QUAD:LI11:358:FUNC CA PP")
  field(DOL2, "MGNT:LI11:1:BENDCTRL.RVAL")
  field(LNK2, "QUAD:LI11:358:FUNC CA PP")
  field(DOL3, "MGNT:LI11:1:BTRMCTRL.RVAL")
  field(LNK3, "QUAD:LI11:358:FUNC CA PP")
  field(DOL4, "MGNT:LI11:1:LGPSCTRL.RVAL")
  field(LNK4, "QUAD:LI11:358:FUNC CA PP")
  field(DOL5, "MGNT:LI11:1:QUADCTRL.RVAL")
  field(LNK5, "QUAD:LI11:358:FUNC CA PP")
  field(DOL6, "MGNT:LI11:1:XCORCTRL.RVAL")
  field(LNK6, "QUAD:LI11:358:FUNC CA PP")
  field(DOL7, "MGNT:LI11:1:YCORCTRL.RVAL")
  field(LNK7, "QUAD:LI11:358:FUNC CA PP")
  field(DOL8, "MGNT:LI11:1:SOLNCTRL.RVAL")
  field(LNK8, "QUAD:LI11:358:FUNC CA PP")
  field(DOL9, "MGNT:LI11:1:KICKCTRL.RVAL")
  field(LNK9, "QUAD:LI11:358:FUNC CA PP")
  field(DOLA, "MGNT:LI11:1:SEXTCTRL.RVAL")
  field(LNKA, "QUAD:LI11:358:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "QUAD:LI11:358:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "QUAD:LI11:358:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "QUAD:LI11:358:EDES.PROC PP")
    field(LNK2, "QUAD:LI11:358:EACT.PROC PP")
    field(LNK3, "QUAD:LI11:358:EERR.DISA PP")
    field(LNK4, "QUAD:LI11:358:ECON.PROC PP")
    field(LNK5, "QUAD:LI11:358:BMAGX.PROC PP")
    field(LNK6, "QUAD:LI11:358:BMAGY.PROC PP")
    field(LNK7, "QUAD:LI11:358:BLEM.PROC PP")
    field(LNK8, "QUAD:LI11:358:BMOD.PROC PP")
    field(LNK9, "QUAD:LI11:358:EDESSAVE.PROC PP")
    field(LNKA, "QUAD:LI11:358:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"QUAD:LI11:358:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "QUAD:LI11:358:BMAX")
  field(DOL2, "QUAD:LI11:358:BMAX")
  field(DOL3, "QUAD:LI11:358:BMAX")
  field(DOL4, "QUAD:LI11:358:BMIN")
  field(DOL5, "QUAD:LI11:358:BMIN")
  field(DOL6, "QUAD:LI11:358:BMIN")
  field(LNK1, "QUAD:LI11:358:BMAGX.HOPR")
  field(LNK2, "QUAD:LI11:358:BMAGY.HOPR")
  field(LNK3, "QUAD:LI11:358:BLEM.HOPR")
  field(LNK4, "QUAD:LI11:358:BMAGX.LOPR PP")
  field(LNK5, "QUAD:LI11:358:BMAGY.LOPR PP")
  field(LNK6, "QUAD:LI11:358:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "QUAD:LI11:358:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "QUAD:LI11:358:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "QUAD:LI11:358:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "QUAD:LI11:358:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "QUAD:LI11:358:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI11:358:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI11:358:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI11:358:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI11:358:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI11:358:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "QUAD:LI11:358:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "QUAD:LI11:358:EDES NPP MS")
  field(INPB, "QUAD:LI11:358:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "QUAD:LI11:362:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI11:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI11:1:CTRL.RVAL")
  field(LNK1, "QUAD:LI11:362:FUNC CA PP")
  field(DOL2, "MGNT:LI11:1:BENDCTRL.RVAL")
  field(LNK2, "QUAD:LI11:362:FUNC CA PP")
  field(DOL3, "MGNT:LI11:1:BTRMCTRL.RVAL")
  field(LNK3, "QUAD:LI11:362:FUNC CA PP")
  field(DOL4, "MGNT:LI11:1:LGPSCTRL.RVAL")
  field(LNK4, "QUAD:LI11:362:FUNC CA PP")
  field(DOL5, "MGNT:LI11:1:QUADCTRL.RVAL")
  field(LNK5, "QUAD:LI11:362:FUNC CA PP")
  field(DOL6, "MGNT:LI11:1:XCORCTRL.RVAL")
  field(LNK6, "QUAD:LI11:362:FUNC CA PP")
  field(DOL7, "MGNT:LI11:1:YCORCTRL.RVAL")
  field(LNK7, "QUAD:LI11:362:FUNC CA PP")
  field(DOL8, "MGNT:LI11:1:SOLNCTRL.RVAL")
  field(LNK8, "QUAD:LI11:362:FUNC CA PP")
  field(DOL9, "MGNT:LI11:1:KICKCTRL.RVAL")
  field(LNK9, "QUAD:LI11:362:FUNC CA PP")
  field(DOLA, "MGNT:LI11:1:SEXTCTRL.RVAL")
  field(LNKA, "QUAD:LI11:362:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "QUAD:LI11:362:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "QUAD:LI11:362:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "QUAD:LI11:362:EDES.PROC PP")
    field(LNK2, "QUAD:LI11:362:EACT.PROC PP")
    field(LNK3, "QUAD:LI11:362:EERR.DISA PP")
    field(LNK4, "QUAD:LI11:362:ECON.PROC PP")
    field(LNK5, "QUAD:LI11:362:BMAGX.PROC PP")
    field(LNK6, "QUAD:LI11:362:BMAGY.PROC PP")
    field(LNK7, "QUAD:LI11:362:BLEM.PROC PP")
    field(LNK8, "QUAD:LI11:362:BMOD.PROC PP")
    field(LNK9, "QUAD:LI11:362:EDESSAVE.PROC PP")
    field(LNKA, "QUAD:LI11:362:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"QUAD:LI11:362:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "QUAD:LI11:362:BMAX")
  field(DOL2, "QUAD:LI11:362:BMAX")
  field(DOL3, "QUAD:LI11:362:BMAX")
  field(DOL4, "QUAD:LI11:362:BMIN")
  field(DOL5, "QUAD:LI11:362:BMIN")
  field(DOL6, "QUAD:LI11:362:BMIN")
  field(LNK1, "QUAD:LI11:362:BMAGX.HOPR")
  field(LNK2, "QUAD:LI11:362:BMAGY.HOPR")
  field(LNK3, "QUAD:LI11:362:BLEM.HOPR")
  field(LNK4, "QUAD:LI11:362:BMAGX.LOPR PP")
  field(LNK5, "QUAD:LI11:362:BMAGY.LOPR PP")
  field(LNK6, "QUAD:LI11:362:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "QUAD:LI11:362:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "QUAD:LI11:362:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "QUAD:LI11:362:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "QUAD:LI11:362:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "QUAD:LI11:362:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI11:362:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI11:362:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI11:362:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI11:362:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI11:362:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "QUAD:LI11:362:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "QUAD:LI11:362:EDES NPP MS")
  field(INPB, "QUAD:LI11:362:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "QUAD:LI11:393:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI11:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI11:1:CTRL.RVAL")
  field(LNK1, "QUAD:LI11:393:FUNC CA PP")
  field(DOL2, "MGNT:LI11:1:BENDCTRL.RVAL")
  field(LNK2, "QUAD:LI11:393:FUNC CA PP")
  field(DOL3, "MGNT:LI11:1:BTRMCTRL.RVAL")
  field(LNK3, "QUAD:LI11:393:FUNC CA PP")
  field(DOL4, "MGNT:LI11:1:LGPSCTRL.RVAL")
  field(LNK4, "QUAD:LI11:393:FUNC CA PP")
  field(DOL5, "MGNT:LI11:1:QUADCTRL.RVAL")
  field(LNK5, "QUAD:LI11:393:FUNC CA PP")
  field(DOL6, "MGNT:LI11:1:XCORCTRL.RVAL")
  field(LNK6, "QUAD:LI11:393:FUNC CA PP")
  field(DOL7, "MGNT:LI11:1:YCORCTRL.RVAL")
  field(LNK7, "QUAD:LI11:393:FUNC CA PP")
  field(DOL8, "MGNT:LI11:1:SOLNCTRL.RVAL")
  field(LNK8, "QUAD:LI11:393:FUNC CA PP")
  field(DOL9, "MGNT:LI11:1:KICKCTRL.RVAL")
  field(LNK9, "QUAD:LI11:393:FUNC CA PP")
  field(DOLA, "MGNT:LI11:1:SEXTCTRL.RVAL")
  field(LNKA, "QUAD:LI11:393:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "QUAD:LI11:393:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "QUAD:LI11:393:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "QUAD:LI11:393:EDES.PROC PP")
    field(LNK2, "QUAD:LI11:393:EACT.PROC PP")
    field(LNK3, "QUAD:LI11:393:EERR.DISA PP")
    field(LNK4, "QUAD:LI11:393:ECON.PROC PP")
    field(LNK5, "QUAD:LI11:393:BMAGX.PROC PP")
    field(LNK6, "QUAD:LI11:393:BMAGY.PROC PP")
    field(LNK7, "QUAD:LI11:393:BLEM.PROC PP")
    field(LNK8, "QUAD:LI11:393:BMOD.PROC PP")
    field(LNK9, "QUAD:LI11:393:EDESSAVE.PROC PP")
    field(LNKA, "QUAD:LI11:393:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"QUAD:LI11:393:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "QUAD:LI11:393:BMAX")
  field(DOL2, "QUAD:LI11:393:BMAX")
  field(DOL3, "QUAD:LI11:393:BMAX")
  field(DOL4, "QUAD:LI11:393:BMIN")
  field(DOL5, "QUAD:LI11:393:BMIN")
  field(DOL6, "QUAD:LI11:393:BMIN")
  field(LNK1, "QUAD:LI11:393:BMAGX.HOPR")
  field(LNK2, "QUAD:LI11:393:BMAGY.HOPR")
  field(LNK3, "QUAD:LI11:393:BLEM.HOPR")
  field(LNK4, "QUAD:LI11:393:BMAGX.LOPR PP")
  field(LNK5, "QUAD:LI11:393:BMAGY.LOPR PP")
  field(LNK6, "QUAD:LI11:393:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "QUAD:LI11:393:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "QUAD:LI11:393:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "QUAD:LI11:393:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "QUAD:LI11:393:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "QUAD:LI11:393:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI11:393:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI11:393:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI11:393:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI11:393:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI11:393:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "QUAD:LI11:393:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "QUAD:LI11:393:EDES NPP MS")
  field(INPB, "QUAD:LI11:393:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "BEND:LI11:331:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI11:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI11:1:CTRL.RVAL")
  field(LNK1, "BEND:LI11:331:FUNC CA PP")
  field(DOL2, "MGNT:LI11:1:BENDCTRL.RVAL")
  field(LNK2, "BEND:LI11:331:FUNC CA PP")
  field(DOL3, "MGNT:LI11:1:BTRMCTRL.RVAL")
  field(LNK3, "BEND:LI11:331:FUNC CA PP")
  field(DOL4, "MGNT:LI11:1:LGPSCTRL.RVAL")
  field(LNK4, "BEND:LI11:331:FUNC CA PP")
  field(DOL5, "MGNT:LI11:1:QUADCTRL.RVAL")
  field(LNK5, "BEND:LI11:331:FUNC CA PP")
  field(DOL6, "MGNT:LI11:1:XCORCTRL.RVAL")
  field(LNK6, "BEND:LI11:331:FUNC CA PP")
  field(DOL7, "MGNT:LI11:1:YCORCTRL.RVAL")
  field(LNK7, "BEND:LI11:331:FUNC CA PP")
  field(DOL8, "MGNT:LI11:1:SOLNCTRL.RVAL")
  field(LNK8, "BEND:LI11:331:FUNC CA PP")
  field(DOL9, "MGNT:LI11:1:KICKCTRL.RVAL")
  field(LNK9, "BEND:LI11:331:FUNC CA PP")
  field(DOLA, "MGNT:LI11:1:SEXTCTRL.RVAL")
  field(LNKA, "BEND:LI11:331:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "BEND:LI11:331:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "BEND:LI11:331:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "BEND:LI11:331:EDES.PROC PP")
    field(LNK2, "BEND:LI11:331:EACT.PROC PP")
    field(LNK3, "BEND:LI11:331:EERR.DISA PP")
    field(LNK4, "BEND:LI11:331:ECON.PROC PP")
    field(LNK5, "BEND:LI11:331:BMAGX.PROC PP")
    field(LNK6, "BEND:LI11:331:BMAGY.PROC PP")
    field(LNK7, "BEND:LI11:331:BLEM.PROC PP")
    field(LNK8, "BEND:LI11:331:BMOD.PROC PP")
    field(LNK9, "BEND:LI11:331:EDESSAVE.PROC PP")
    field(LNKA, "BEND:LI11:331:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"BEND:LI11:331:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "BEND:LI11:331:BMAX")
  field(DOL2, "BEND:LI11:331:BMAX")
  field(DOL3, "BEND:LI11:331:BMAX")
  field(DOL4, "BEND:LI11:331:BMIN")
  field(DOL5, "BEND:LI11:331:BMIN")
  field(DOL6, "BEND:LI11:331:BMIN")
  field(LNK1, "BEND:LI11:331:BMAGX.HOPR")
  field(LNK2, "BEND:LI11:331:BMAGY.HOPR")
  field(LNK3, "BEND:LI11:331:BLEM.HOPR")
  field(LNK4, "BEND:LI11:331:BMAGX.LOPR PP")
  field(LNK5, "BEND:LI11:331:BMAGY.LOPR PP")
  field(LNK6, "BEND:LI11:331:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "BEND:LI11:331:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "BEND:LI11:331:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "BEND:LI11:331:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "BEND:LI11:331:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "BEND:LI11:331:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:LI11:331:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:LI11:331:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "BEND:LI11:331:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:LI11:331:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "BEND:LI11:331:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "BEND:LI11:331:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "BEND:LI11:331:EDES NPP MS")
  field(INPB, "BEND:LI11:331:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "BTRM:LI11:314:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI11:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI11:1:CTRL.RVAL")
  field(LNK1, "BTRM:LI11:314:FUNC CA PP")
  field(DOL2, "MGNT:LI11:1:BENDCTRL.RVAL")
  field(LNK2, "BTRM:LI11:314:FUNC CA PP")
  field(DOL3, "MGNT:LI11:1:BTRMCTRL.RVAL")
  field(LNK3, "BTRM:LI11:314:FUNC CA PP")
  field(DOL4, "MGNT:LI11:1:LGPSCTRL.RVAL")
  field(LNK4, "BTRM:LI11:314:FUNC CA PP")
  field(DOL5, "MGNT:LI11:1:QUADCTRL.RVAL")
  field(LNK5, "BTRM:LI11:314:FUNC CA PP")
  field(DOL6, "MGNT:LI11:1:XCORCTRL.RVAL")
  field(LNK6, "BTRM:LI11:314:FUNC CA PP")
  field(DOL7, "MGNT:LI11:1:YCORCTRL.RVAL")
  field(LNK7, "BTRM:LI11:314:FUNC CA PP")
  field(DOL8, "MGNT:LI11:1:SOLNCTRL.RVAL")
  field(LNK8, "BTRM:LI11:314:FUNC CA PP")
  field(DOL9, "MGNT:LI11:1:KICKCTRL.RVAL")
  field(LNK9, "BTRM:LI11:314:FUNC CA PP")
  field(DOLA, "MGNT:LI11:1:SEXTCTRL.RVAL")
  field(LNKA, "BTRM:LI11:314:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "BTRM:LI11:314:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "BTRM:LI11:314:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "BTRM:LI11:314:EDES.PROC PP")
    field(LNK2, "BTRM:LI11:314:EACT.PROC PP")
    field(LNK3, "BTRM:LI11:314:EERR.DISA PP")
    field(LNK4, "BTRM:LI11:314:ECON.PROC PP")
    field(LNK5, "BTRM:LI11:314:BMAGX.PROC PP")
    field(LNK6, "BTRM:LI11:314:BMAGY.PROC PP")
    field(LNK7, "BTRM:LI11:314:BLEM.PROC PP")
    field(LNK8, "BTRM:LI11:314:BMOD.PROC PP")
    field(LNK9, "BTRM:LI11:314:EDESSAVE.PROC PP")
    field(LNKA, "BTRM:LI11:314:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"BTRM:LI11:314:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "BTRM:LI11:314:BMAX")
  field(DOL2, "BTRM:LI11:314:BMAX")
  field(DOL3, "BTRM:LI11:314:BMAX")
  field(DOL4, "BTRM:LI11:314:BMIN")
  field(DOL5, "BTRM:LI11:314:BMIN")
  field(DOL6, "BTRM:LI11:314:BMIN")
  field(LNK1, "BTRM:LI11:314:BMAGX.HOPR")
  field(LNK2, "BTRM:LI11:314:BMAGY.HOPR")
  field(LNK3, "BTRM:LI11:314:BLEM.HOPR")
  field(LNK4, "BTRM:LI11:314:BMAGX.LOPR PP")
  field(LNK5, "BTRM:LI11:314:BMAGY.LOPR PP")
  field(LNK6, "BTRM:LI11:314:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "BTRM:LI11:314:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "BTRM:LI11:314:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "BTRM:LI11:314:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "Amain")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "BTRM:LI11:314:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "Amain")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "BTRM:LI11:314:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:LI11:314:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:LI11:314:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "BTRM:LI11:314:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:LI11:314:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "BTRM:LI11:314:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "BTRM:LI11:314:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "BTRM:LI11:314:EDES NPP MS")
  field(INPB, "BTRM:LI11:314:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "BTRM:LI11:338:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI11:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI11:1:CTRL.RVAL")
  field(LNK1, "BTRM:LI11:338:FUNC CA PP")
  field(DOL2, "MGNT:LI11:1:BENDCTRL.RVAL")
  field(LNK2, "BTRM:LI11:338:FUNC CA PP")
  field(DOL3, "MGNT:LI11:1:BTRMCTRL.RVAL")
  field(LNK3, "BTRM:LI11:338:FUNC CA PP")
  field(DOL4, "MGNT:LI11:1:LGPSCTRL.RVAL")
  field(LNK4, "BTRM:LI11:338:FUNC CA PP")
  field(DOL5, "MGNT:LI11:1:QUADCTRL.RVAL")
  field(LNK5, "BTRM:LI11:338:FUNC CA PP")
  field(DOL6, "MGNT:LI11:1:XCORCTRL.RVAL")
  field(LNK6, "BTRM:LI11:338:FUNC CA PP")
  field(DOL7, "MGNT:LI11:1:YCORCTRL.RVAL")
  field(LNK7, "BTRM:LI11:338:FUNC CA PP")
  field(DOL8, "MGNT:LI11:1:SOLNCTRL.RVAL")
  field(LNK8, "BTRM:LI11:338:FUNC CA PP")
  field(DOL9, "MGNT:LI11:1:KICKCTRL.RVAL")
  field(LNK9, "BTRM:LI11:338:FUNC CA PP")
  field(DOLA, "MGNT:LI11:1:SEXTCTRL.RVAL")
  field(LNKA, "BTRM:LI11:338:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "BTRM:LI11:338:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "BTRM:LI11:338:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "BTRM:LI11:338:EDES.PROC PP")
    field(LNK2, "BTRM:LI11:338:EACT.PROC PP")
    field(LNK3, "BTRM:LI11:338:EERR.DISA PP")
    field(LNK4, "BTRM:LI11:338:ECON.PROC PP")
    field(LNK5, "BTRM:LI11:338:BMAGX.PROC PP")
    field(LNK6, "BTRM:LI11:338:BMAGY.PROC PP")
    field(LNK7, "BTRM:LI11:338:BLEM.PROC PP")
    field(LNK8, "BTRM:LI11:338:BMOD.PROC PP")
    field(LNK9, "BTRM:LI11:338:EDESSAVE.PROC PP")
    field(LNKA, "BTRM:LI11:338:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"BTRM:LI11:338:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "BTRM:LI11:338:BMAX")
  field(DOL2, "BTRM:LI11:338:BMAX")
  field(DOL3, "BTRM:LI11:338:BMAX")
  field(DOL4, "BTRM:LI11:338:BMIN")
  field(DOL5, "BTRM:LI11:338:BMIN")
  field(DOL6, "BTRM:LI11:338:BMIN")
  field(LNK1, "BTRM:LI11:338:BMAGX.HOPR")
  field(LNK2, "BTRM:LI11:338:BMAGY.HOPR")
  field(LNK3, "BTRM:LI11:338:BLEM.HOPR")
  field(LNK4, "BTRM:LI11:338:BMAGX.LOPR PP")
  field(LNK5, "BTRM:LI11:338:BMAGY.LOPR PP")
  field(LNK6, "BTRM:LI11:338:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "BTRM:LI11:338:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "BTRM:LI11:338:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "BTRM:LI11:338:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "Amain")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "BTRM:LI11:338:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "Amain")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "BTRM:LI11:338:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:LI11:338:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:LI11:338:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "BTRM:LI11:338:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:LI11:338:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "BTRM:LI11:338:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "BTRM:LI11:338:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "BTRM:LI11:338:EDES NPP MS")
  field(INPB, "BTRM:LI11:338:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "BTRM:LI11:355:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI11:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI11:1:CTRL.RVAL")
  field(LNK1, "BTRM:LI11:355:FUNC CA PP")
  field(DOL2, "MGNT:LI11:1:BENDCTRL.RVAL")
  field(LNK2, "BTRM:LI11:355:FUNC CA PP")
  field(DOL3, "MGNT:LI11:1:BTRMCTRL.RVAL")
  field(LNK3, "BTRM:LI11:355:FUNC CA PP")
  field(DOL4, "MGNT:LI11:1:LGPSCTRL.RVAL")
  field(LNK4, "BTRM:LI11:355:FUNC CA PP")
  field(DOL5, "MGNT:LI11:1:QUADCTRL.RVAL")
  field(LNK5, "BTRM:LI11:355:FUNC CA PP")
  field(DOL6, "MGNT:LI11:1:XCORCTRL.RVAL")
  field(LNK6, "BTRM:LI11:355:FUNC CA PP")
  field(DOL7, "MGNT:LI11:1:YCORCTRL.RVAL")
  field(LNK7, "BTRM:LI11:355:FUNC CA PP")
  field(DOL8, "MGNT:LI11:1:SOLNCTRL.RVAL")
  field(LNK8, "BTRM:LI11:355:FUNC CA PP")
  field(DOL9, "MGNT:LI11:1:KICKCTRL.RVAL")
  field(LNK9, "BTRM:LI11:355:FUNC CA PP")
  field(DOLA, "MGNT:LI11:1:SEXTCTRL.RVAL")
  field(LNKA, "BTRM:LI11:355:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "BTRM:LI11:355:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "BTRM:LI11:355:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "BTRM:LI11:355:EDES.PROC PP")
    field(LNK2, "BTRM:LI11:355:EACT.PROC PP")
    field(LNK3, "BTRM:LI11:355:EERR.DISA PP")
    field(LNK4, "BTRM:LI11:355:ECON.PROC PP")
    field(LNK5, "BTRM:LI11:355:BMAGX.PROC PP")
    field(LNK6, "BTRM:LI11:355:BMAGY.PROC PP")
    field(LNK7, "BTRM:LI11:355:BLEM.PROC PP")
    field(LNK8, "BTRM:LI11:355:BMOD.PROC PP")
    field(LNK9, "BTRM:LI11:355:EDESSAVE.PROC PP")
    field(LNKA, "BTRM:LI11:355:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"BTRM:LI11:355:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "BTRM:LI11:355:BMAX")
  field(DOL2, "BTRM:LI11:355:BMAX")
  field(DOL3, "BTRM:LI11:355:BMAX")
  field(DOL4, "BTRM:LI11:355:BMIN")
  field(DOL5, "BTRM:LI11:355:BMIN")
  field(DOL6, "BTRM:LI11:355:BMIN")
  field(LNK1, "BTRM:LI11:355:BMAGX.HOPR")
  field(LNK2, "BTRM:LI11:355:BMAGY.HOPR")
  field(LNK3, "BTRM:LI11:355:BLEM.HOPR")
  field(LNK4, "BTRM:LI11:355:BMAGX.LOPR PP")
  field(LNK5, "BTRM:LI11:355:BMAGY.LOPR PP")
  field(LNK6, "BTRM:LI11:355:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "BTRM:LI11:355:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "BTRM:LI11:355:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "BTRM:LI11:355:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "Amain")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "BTRM:LI11:355:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "Amain")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "BTRM:LI11:355:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:LI11:355:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:LI11:355:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "BTRM:LI11:355:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:LI11:355:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "BTRM:LI11:355:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "BTRM:LI11:355:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "BTRM:LI11:355:EDES NPP MS")
  field(INPB, "BTRM:LI11:355:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "LGPS:LI11:2:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI11:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI11:1:CTRL.RVAL")
  field(LNK1, "LGPS:LI11:2:FUNC CA PP")
  field(DOL2, "MGNT:LI11:1:BENDCTRL.RVAL")
  field(LNK2, "LGPS:LI11:2:FUNC CA PP")
  field(DOL3, "MGNT:LI11:1:BTRMCTRL.RVAL")
  field(LNK3, "LGPS:LI11:2:FUNC CA PP")
  field(DOL4, "MGNT:LI11:1:LGPSCTRL.RVAL")
  field(LNK4, "LGPS:LI11:2:FUNC CA PP")
  field(DOL5, "MGNT:LI11:1:QUADCTRL.RVAL")
  field(LNK5, "LGPS:LI11:2:FUNC CA PP")
  field(DOL6, "MGNT:LI11:1:XCORCTRL.RVAL")
  field(LNK6, "LGPS:LI11:2:FUNC CA PP")
  field(DOL7, "MGNT:LI11:1:YCORCTRL.RVAL")
  field(LNK7, "LGPS:LI11:2:FUNC CA PP")
  field(DOL8, "MGNT:LI11:1:SOLNCTRL.RVAL")
  field(LNK8, "LGPS:LI11:2:FUNC CA PP")
  field(DOL9, "MGNT:LI11:1:KICKCTRL.RVAL")
  field(LNK9, "LGPS:LI11:2:FUNC CA PP")
  field(DOLA, "MGNT:LI11:1:SEXTCTRL.RVAL")
  field(LNKA, "LGPS:LI11:2:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "LGPS:LI11:2:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "LGPS:LI11:2:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "LGPS:LI11:2:EDES.PROC PP")
    field(LNK2, "LGPS:LI11:2:EACT.PROC PP")
    field(LNK3, "LGPS:LI11:2:EERR.DISA PP")
    field(LNK4, "LGPS:LI11:2:ECON.PROC PP")
    field(LNK5, "LGPS:LI11:2:BMAGX.PROC PP")
    field(LNK6, "LGPS:LI11:2:BMAGY.PROC PP")
    field(LNK7, "LGPS:LI11:2:BLEM.PROC PP")
    field(LNK8, "LGPS:LI11:2:BMOD.PROC PP")
    field(LNK9, "LGPS:LI11:2:EDESSAVE.PROC PP")
    field(LNKA, "LGPS:LI11:2:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"LGPS:LI11:2:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "LGPS:LI11:2:BMAX")
  field(DOL2, "LGPS:LI11:2:BMAX")
  field(DOL3, "LGPS:LI11:2:BMAX")
  field(DOL4, "LGPS:LI11:2:BMIN")
  field(DOL5, "LGPS:LI11:2:BMIN")
  field(DOL6, "LGPS:LI11:2:BMIN")
  field(LNK1, "LGPS:LI11:2:BMAGX.HOPR")
  field(LNK2, "LGPS:LI11:2:BMAGY.HOPR")
  field(LNK3, "LGPS:LI11:2:BLEM.HOPR")
  field(LNK4, "LGPS:LI11:2:BMAGX.LOPR PP")
  field(LNK5, "LGPS:LI11:2:BMAGY.LOPR PP")
  field(LNK6, "LGPS:LI11:2:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "LGPS:LI11:2:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "LGPS:LI11:2:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "LGPS:LI11:2:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "Volts")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "LGPS:LI11:2:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "Volts")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "LGPS:LI11:2:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "LGPS:LI11:2:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "LGPS:LI11:2:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "LGPS:LI11:2:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "LGPS:LI11:2:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "LGPS:LI11:2:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "LGPS:LI11:2:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "LGPS:LI11:2:EDES NPP MS")
  field(INPB, "LGPS:LI11:2:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "YCOR:LI14:780:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI14:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI14:1:CTRL.RVAL")
  field(LNK1, "YCOR:LI14:780:FUNC CA PP")
  field(DOL2, "MGNT:LI14:1:BENDCTRL.RVAL")
  field(LNK2, "YCOR:LI14:780:FUNC CA PP")
  field(DOL3, "MGNT:LI14:1:BTRMCTRL.RVAL")
  field(LNK3, "YCOR:LI14:780:FUNC CA PP")
  field(DOL4, "MGNT:LI14:1:LGPSCTRL.RVAL")
  field(LNK4, "YCOR:LI14:780:FUNC CA PP")
  field(DOL5, "MGNT:LI14:1:QUADCTRL.RVAL")
  field(LNK5, "YCOR:LI14:780:FUNC CA PP")
  field(DOL6, "MGNT:LI14:1:XCORCTRL.RVAL")
  field(LNK6, "YCOR:LI14:780:FUNC CA PP")
  field(DOL7, "MGNT:LI14:1:YCORCTRL.RVAL")
  field(LNK7, "YCOR:LI14:780:FUNC CA PP")
  field(DOL8, "MGNT:LI14:1:SOLNCTRL.RVAL")
  field(LNK8, "YCOR:LI14:780:FUNC CA PP")
  field(DOL9, "MGNT:LI14:1:KICKCTRL.RVAL")
  field(LNK9, "YCOR:LI14:780:FUNC CA PP")
  field(DOLA, "MGNT:LI14:1:SEXTCTRL.RVAL")
  field(LNKA, "YCOR:LI14:780:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "YCOR:LI14:780:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "YCOR:LI14:780:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "YCOR:LI14:780:EDES.PROC PP")
    field(LNK2, "YCOR:LI14:780:EACT.PROC PP")
    field(LNK3, "YCOR:LI14:780:EERR.DISA PP")
    field(LNK4, "YCOR:LI14:780:ECON.PROC PP")
    field(LNK5, "YCOR:LI14:780:BMAGX.PROC PP")
    field(LNK6, "YCOR:LI14:780:BMAGY.PROC PP")
    field(LNK7, "YCOR:LI14:780:BLEM.PROC PP")
    field(LNK8, "YCOR:LI14:780:BMOD.PROC PP")
    field(LNK9, "YCOR:LI14:780:EDESSAVE.PROC PP")
    field(LNKA, "YCOR:LI14:780:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"YCOR:LI14:780:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "YCOR:LI14:780:BMAX")
  field(DOL2, "YCOR:LI14:780:BMAX")
  field(DOL3, "YCOR:LI14:780:BMAX")
  field(DOL4, "YCOR:LI14:780:BMIN")
  field(DOL5, "YCOR:LI14:780:BMIN")
  field(DOL6, "YCOR:LI14:780:BMIN")
  field(LNK1, "YCOR:LI14:780:BMAGX.HOPR")
  field(LNK2, "YCOR:LI14:780:BMAGY.HOPR")
  field(LNK3, "YCOR:LI14:780:BLEM.HOPR")
  field(LNK4, "YCOR:LI14:780:BMAGX.LOPR PP")
  field(LNK5, "YCOR:LI14:780:BMAGY.LOPR PP")
  field(LNK6, "YCOR:LI14:780:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "YCOR:LI14:780:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "YCOR:LI14:780:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "YCOR:LI14:780:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "YCOR:LI14:780:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "YCOR:LI14:780:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:LI14:780:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:LI14:780:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:LI14:780:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:LI14:780:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:LI14:780:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "YCOR:LI14:780:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "YCOR:LI14:780:EDES NPP MS")
  field(INPB, "YCOR:LI14:780:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "YCOR:LI14:1780:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI14:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI14:1:CTRL.RVAL")
  field(LNK1, "YCOR:LI14:1780:FUNC CA PP")
  field(DOL2, "MGNT:LI14:1:BENDCTRL.RVAL")
  field(LNK2, "YCOR:LI14:1780:FUNC CA PP")
  field(DOL3, "MGNT:LI14:1:BTRMCTRL.RVAL")
  field(LNK3, "YCOR:LI14:1780:FUNC CA PP")
  field(DOL4, "MGNT:LI14:1:LGPSCTRL.RVAL")
  field(LNK4, "YCOR:LI14:1780:FUNC CA PP")
  field(DOL5, "MGNT:LI14:1:QUADCTRL.RVAL")
  field(LNK5, "YCOR:LI14:1780:FUNC CA PP")
  field(DOL6, "MGNT:LI14:1:XCORCTRL.RVAL")
  field(LNK6, "YCOR:LI14:1780:FUNC CA PP")
  field(DOL7, "MGNT:LI14:1:YCORCTRL.RVAL")
  field(LNK7, "YCOR:LI14:1780:FUNC CA PP")
  field(DOL8, "MGNT:LI14:1:SOLNCTRL.RVAL")
  field(LNK8, "YCOR:LI14:1780:FUNC CA PP")
  field(DOL9, "MGNT:LI14:1:KICKCTRL.RVAL")
  field(LNK9, "YCOR:LI14:1780:FUNC CA PP")
  field(DOLA, "MGNT:LI14:1:SEXTCTRL.RVAL")
  field(LNKA, "YCOR:LI14:1780:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "YCOR:LI14:1780:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "YCOR:LI14:1780:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "YCOR:LI14:1780:EDES.PROC PP")
    field(LNK2, "YCOR:LI14:1780:EACT.PROC PP")
    field(LNK3, "YCOR:LI14:1780:EERR.DISA PP")
    field(LNK4, "YCOR:LI14:1780:ECON.PROC PP")
    field(LNK5, "YCOR:LI14:1780:BMAGX.PROC PP")
    field(LNK6, "YCOR:LI14:1780:BMAGY.PROC PP")
    field(LNK7, "YCOR:LI14:1780:BLEM.PROC PP")
    field(LNK8, "YCOR:LI14:1780:BMOD.PROC PP")
    field(LNK9, "YCOR:LI14:1780:EDESSAVE.PROC PP")
    field(LNKA, "YCOR:LI14:1780:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"YCOR:LI14:1780:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "YCOR:LI14:1780:BMAX")
  field(DOL2, "YCOR:LI14:1780:BMAX")
  field(DOL3, "YCOR:LI14:1780:BMAX")
  field(DOL4, "YCOR:LI14:1780:BMIN")
  field(DOL5, "YCOR:LI14:1780:BMIN")
  field(DOL6, "YCOR:LI14:1780:BMIN")
  field(LNK1, "YCOR:LI14:1780:BMAGX.HOPR")
  field(LNK2, "YCOR:LI14:1780:BMAGY.HOPR")
  field(LNK3, "YCOR:LI14:1780:BLEM.HOPR")
  field(LNK4, "YCOR:LI14:1780:BMAGX.LOPR PP")
  field(LNK5, "YCOR:LI14:1780:BMAGY.LOPR PP")
  field(LNK6, "YCOR:LI14:1780:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "YCOR:LI14:1780:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "YCOR:LI14:1780:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "YCOR:LI14:1780:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "YCOR:LI14:1780:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "YCOR:LI14:1780:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:LI14:1780:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:LI14:1780:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:LI14:1780:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:LI14:1780:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:LI14:1780:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "YCOR:LI14:1780:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "YCOR:LI14:1780:EDES NPP MS")
  field(INPB, "YCOR:LI14:1780:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "QUAD:LI14:701:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI14:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI14:1:CTRL.RVAL")
  field(LNK1, "QUAD:LI14:701:FUNC CA PP")
  field(DOL2, "MGNT:LI14:1:BENDCTRL.RVAL")
  field(LNK2, "QUAD:LI14:701:FUNC CA PP")
  field(DOL3, "MGNT:LI14:1:BTRMCTRL.RVAL")
  field(LNK3, "QUAD:LI14:701:FUNC CA PP")
  field(DOL4, "MGNT:LI14:1:LGPSCTRL.RVAL")
  field(LNK4, "QUAD:LI14:701:FUNC CA PP")
  field(DOL5, "MGNT:LI14:1:QUADCTRL.RVAL")
  field(LNK5, "QUAD:LI14:701:FUNC CA PP")
  field(DOL6, "MGNT:LI14:1:XCORCTRL.RVAL")
  field(LNK6, "QUAD:LI14:701:FUNC CA PP")
  field(DOL7, "MGNT:LI14:1:YCORCTRL.RVAL")
  field(LNK7, "QUAD:LI14:701:FUNC CA PP")
  field(DOL8, "MGNT:LI14:1:SOLNCTRL.RVAL")
  field(LNK8, "QUAD:LI14:701:FUNC CA PP")
  field(DOL9, "MGNT:LI14:1:KICKCTRL.RVAL")
  field(LNK9, "QUAD:LI14:701:FUNC CA PP")
  field(DOLA, "MGNT:LI14:1:SEXTCTRL.RVAL")
  field(LNKA, "QUAD:LI14:701:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "QUAD:LI14:701:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "QUAD:LI14:701:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "QUAD:LI14:701:EDES.PROC PP")
    field(LNK2, "QUAD:LI14:701:EACT.PROC PP")
    field(LNK3, "QUAD:LI14:701:EERR.DISA PP")
    field(LNK4, "QUAD:LI14:701:ECON.PROC PP")
    field(LNK5, "QUAD:LI14:701:BMAGX.PROC PP")
    field(LNK6, "QUAD:LI14:701:BMAGY.PROC PP")
    field(LNK7, "QUAD:LI14:701:BLEM.PROC PP")
    field(LNK8, "QUAD:LI14:701:BMOD.PROC PP")
    field(LNK9, "QUAD:LI14:701:EDESSAVE.PROC PP")
    field(LNKA, "QUAD:LI14:701:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"QUAD:LI14:701:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "QUAD:LI14:701:BMAX")
  field(DOL2, "QUAD:LI14:701:BMAX")
  field(DOL3, "QUAD:LI14:701:BMAX")
  field(DOL4, "QUAD:LI14:701:BMIN")
  field(DOL5, "QUAD:LI14:701:BMIN")
  field(DOL6, "QUAD:LI14:701:BMIN")
  field(LNK1, "QUAD:LI14:701:BMAGX.HOPR")
  field(LNK2, "QUAD:LI14:701:BMAGY.HOPR")
  field(LNK3, "QUAD:LI14:701:BLEM.HOPR")
  field(LNK4, "QUAD:LI14:701:BMAGX.LOPR PP")
  field(LNK5, "QUAD:LI14:701:BMAGY.LOPR PP")
  field(LNK6, "QUAD:LI14:701:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "QUAD:LI14:701:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "QUAD:LI14:701:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "QUAD:LI14:701:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "QUAD:LI14:701:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "QUAD:LI14:701:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI14:701:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI14:701:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI14:701:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI14:701:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI14:701:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "QUAD:LI14:701:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "QUAD:LI14:701:EDES NPP MS")
  field(INPB, "QUAD:LI14:701:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "QUAD:LI14:715:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI14:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI14:1:CTRL.RVAL")
  field(LNK1, "QUAD:LI14:715:FUNC CA PP")
  field(DOL2, "MGNT:LI14:1:BENDCTRL.RVAL")
  field(LNK2, "QUAD:LI14:715:FUNC CA PP")
  field(DOL3, "MGNT:LI14:1:BTRMCTRL.RVAL")
  field(LNK3, "QUAD:LI14:715:FUNC CA PP")
  field(DOL4, "MGNT:LI14:1:LGPSCTRL.RVAL")
  field(LNK4, "QUAD:LI14:715:FUNC CA PP")
  field(DOL5, "MGNT:LI14:1:QUADCTRL.RVAL")
  field(LNK5, "QUAD:LI14:715:FUNC CA PP")
  field(DOL6, "MGNT:LI14:1:XCORCTRL.RVAL")
  field(LNK6, "QUAD:LI14:715:FUNC CA PP")
  field(DOL7, "MGNT:LI14:1:YCORCTRL.RVAL")
  field(LNK7, "QUAD:LI14:715:FUNC CA PP")
  field(DOL8, "MGNT:LI14:1:SOLNCTRL.RVAL")
  field(LNK8, "QUAD:LI14:715:FUNC CA PP")
  field(DOL9, "MGNT:LI14:1:KICKCTRL.RVAL")
  field(LNK9, "QUAD:LI14:715:FUNC CA PP")
  field(DOLA, "MGNT:LI14:1:SEXTCTRL.RVAL")
  field(LNKA, "QUAD:LI14:715:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "QUAD:LI14:715:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "QUAD:LI14:715:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "QUAD:LI14:715:EDES.PROC PP")
    field(LNK2, "QUAD:LI14:715:EACT.PROC PP")
    field(LNK3, "QUAD:LI14:715:EERR.DISA PP")
    field(LNK4, "QUAD:LI14:715:ECON.PROC PP")
    field(LNK5, "QUAD:LI14:715:BMAGX.PROC PP")
    field(LNK6, "QUAD:LI14:715:BMAGY.PROC PP")
    field(LNK7, "QUAD:LI14:715:BLEM.PROC PP")
    field(LNK8, "QUAD:LI14:715:BMOD.PROC PP")
    field(LNK9, "QUAD:LI14:715:EDESSAVE.PROC PP")
    field(LNKA, "QUAD:LI14:715:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"QUAD:LI14:715:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "QUAD:LI14:715:BMAX")
  field(DOL2, "QUAD:LI14:715:BMAX")
  field(DOL3, "QUAD:LI14:715:BMAX")
  field(DOL4, "QUAD:LI14:715:BMIN")
  field(DOL5, "QUAD:LI14:715:BMIN")
  field(DOL6, "QUAD:LI14:715:BMIN")
  field(LNK1, "QUAD:LI14:715:BMAGX.HOPR")
  field(LNK2, "QUAD:LI14:715:BMAGY.HOPR")
  field(LNK3, "QUAD:LI14:715:BLEM.HOPR")
  field(LNK4, "QUAD:LI14:715:BMAGX.LOPR PP")
  field(LNK5, "QUAD:LI14:715:BMAGY.LOPR PP")
  field(LNK6, "QUAD:LI14:715:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "QUAD:LI14:715:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "QUAD:LI14:715:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "QUAD:LI14:715:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "QUAD:LI14:715:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "QUAD:LI14:715:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI14:715:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI14:715:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI14:715:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI14:715:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI14:715:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "QUAD:LI14:715:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "QUAD:LI14:715:EDES NPP MS")
  field(INPB, "QUAD:LI14:715:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "QUAD:LI14:738:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI14:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI14:1:CTRL.RVAL")
  field(LNK1, "QUAD:LI14:738:FUNC CA PP")
  field(DOL2, "MGNT:LI14:1:BENDCTRL.RVAL")
  field(LNK2, "QUAD:LI14:738:FUNC CA PP")
  field(DOL3, "MGNT:LI14:1:BTRMCTRL.RVAL")
  field(LNK3, "QUAD:LI14:738:FUNC CA PP")
  field(DOL4, "MGNT:LI14:1:LGPSCTRL.RVAL")
  field(LNK4, "QUAD:LI14:738:FUNC CA PP")
  field(DOL5, "MGNT:LI14:1:QUADCTRL.RVAL")
  field(LNK5, "QUAD:LI14:738:FUNC CA PP")
  field(DOL6, "MGNT:LI14:1:XCORCTRL.RVAL")
  field(LNK6, "QUAD:LI14:738:FUNC CA PP")
  field(DOL7, "MGNT:LI14:1:YCORCTRL.RVAL")
  field(LNK7, "QUAD:LI14:738:FUNC CA PP")
  field(DOL8, "MGNT:LI14:1:SOLNCTRL.RVAL")
  field(LNK8, "QUAD:LI14:738:FUNC CA PP")
  field(DOL9, "MGNT:LI14:1:KICKCTRL.RVAL")
  field(LNK9, "QUAD:LI14:738:FUNC CA PP")
  field(DOLA, "MGNT:LI14:1:SEXTCTRL.RVAL")
  field(LNKA, "QUAD:LI14:738:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "QUAD:LI14:738:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "QUAD:LI14:738:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "QUAD:LI14:738:EDES.PROC PP")
    field(LNK2, "QUAD:LI14:738:EACT.PROC PP")
    field(LNK3, "QUAD:LI14:738:EERR.DISA PP")
    field(LNK4, "QUAD:LI14:738:ECON.PROC PP")
    field(LNK5, "QUAD:LI14:738:BMAGX.PROC PP")
    field(LNK6, "QUAD:LI14:738:BMAGY.PROC PP")
    field(LNK7, "QUAD:LI14:738:BLEM.PROC PP")
    field(LNK8, "QUAD:LI14:738:BMOD.PROC PP")
    field(LNK9, "QUAD:LI14:738:EDESSAVE.PROC PP")
    field(LNKA, "QUAD:LI14:738:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"QUAD:LI14:738:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "QUAD:LI14:738:BMAX")
  field(DOL2, "QUAD:LI14:738:BMAX")
  field(DOL3, "QUAD:LI14:738:BMAX")
  field(DOL4, "QUAD:LI14:738:BMIN")
  field(DOL5, "QUAD:LI14:738:BMIN")
  field(DOL6, "QUAD:LI14:738:BMIN")
  field(LNK1, "QUAD:LI14:738:BMAGX.HOPR")
  field(LNK2, "QUAD:LI14:738:BMAGY.HOPR")
  field(LNK3, "QUAD:LI14:738:BLEM.HOPR")
  field(LNK4, "QUAD:LI14:738:BMAGX.LOPR PP")
  field(LNK5, "QUAD:LI14:738:BMAGY.LOPR PP")
  field(LNK6, "QUAD:LI14:738:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "QUAD:LI14:738:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "QUAD:LI14:738:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "QUAD:LI14:738:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "QUAD:LI14:738:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "QUAD:LI14:738:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI14:738:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI14:738:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI14:738:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI14:738:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI14:738:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "QUAD:LI14:738:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "QUAD:LI14:738:EDES NPP MS")
  field(INPB, "QUAD:LI14:738:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "QUAD:LI14:866:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI14:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI14:1:CTRL.RVAL")
  field(LNK1, "QUAD:LI14:866:FUNC CA PP")
  field(DOL2, "MGNT:LI14:1:BENDCTRL.RVAL")
  field(LNK2, "QUAD:LI14:866:FUNC CA PP")
  field(DOL3, "MGNT:LI14:1:BTRMCTRL.RVAL")
  field(LNK3, "QUAD:LI14:866:FUNC CA PP")
  field(DOL4, "MGNT:LI14:1:LGPSCTRL.RVAL")
  field(LNK4, "QUAD:LI14:866:FUNC CA PP")
  field(DOL5, "MGNT:LI14:1:QUADCTRL.RVAL")
  field(LNK5, "QUAD:LI14:866:FUNC CA PP")
  field(DOL6, "MGNT:LI14:1:XCORCTRL.RVAL")
  field(LNK6, "QUAD:LI14:866:FUNC CA PP")
  field(DOL7, "MGNT:LI14:1:YCORCTRL.RVAL")
  field(LNK7, "QUAD:LI14:866:FUNC CA PP")
  field(DOL8, "MGNT:LI14:1:SOLNCTRL.RVAL")
  field(LNK8, "QUAD:LI14:866:FUNC CA PP")
  field(DOL9, "MGNT:LI14:1:KICKCTRL.RVAL")
  field(LNK9, "QUAD:LI14:866:FUNC CA PP")
  field(DOLA, "MGNT:LI14:1:SEXTCTRL.RVAL")
  field(LNKA, "QUAD:LI14:866:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "QUAD:LI14:866:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "QUAD:LI14:866:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "QUAD:LI14:866:EDES.PROC PP")
    field(LNK2, "QUAD:LI14:866:EACT.PROC PP")
    field(LNK3, "QUAD:LI14:866:EERR.DISA PP")
    field(LNK4, "QUAD:LI14:866:ECON.PROC PP")
    field(LNK5, "QUAD:LI14:866:BMAGX.PROC PP")
    field(LNK6, "QUAD:LI14:866:BMAGY.PROC PP")
    field(LNK7, "QUAD:LI14:866:BLEM.PROC PP")
    field(LNK8, "QUAD:LI14:866:BMOD.PROC PP")
    field(LNK9, "QUAD:LI14:866:EDESSAVE.PROC PP")
    field(LNKA, "QUAD:LI14:866:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"QUAD:LI14:866:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "QUAD:LI14:866:BMAX")
  field(DOL2, "QUAD:LI14:866:BMAX")
  field(DOL3, "QUAD:LI14:866:BMAX")
  field(DOL4, "QUAD:LI14:866:BMIN")
  field(DOL5, "QUAD:LI14:866:BMIN")
  field(DOL6, "QUAD:LI14:866:BMIN")
  field(LNK1, "QUAD:LI14:866:BMAGX.HOPR")
  field(LNK2, "QUAD:LI14:866:BMAGY.HOPR")
  field(LNK3, "QUAD:LI14:866:BLEM.HOPR")
  field(LNK4, "QUAD:LI14:866:BMAGX.LOPR PP")
  field(LNK5, "QUAD:LI14:866:BMAGY.LOPR PP")
  field(LNK6, "QUAD:LI14:866:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "QUAD:LI14:866:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "QUAD:LI14:866:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "QUAD:LI14:866:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "QUAD:LI14:866:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "QUAD:LI14:866:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI14:866:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI14:866:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI14:866:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI14:866:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI14:866:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "QUAD:LI14:866:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "QUAD:LI14:866:EDES NPP MS")
  field(INPB, "QUAD:LI14:866:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "QUAD:LI14:891:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI14:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI14:1:CTRL.RVAL")
  field(LNK1, "QUAD:LI14:891:FUNC CA PP")
  field(DOL2, "MGNT:LI14:1:BENDCTRL.RVAL")
  field(LNK2, "QUAD:LI14:891:FUNC CA PP")
  field(DOL3, "MGNT:LI14:1:BTRMCTRL.RVAL")
  field(LNK3, "QUAD:LI14:891:FUNC CA PP")
  field(DOL4, "MGNT:LI14:1:LGPSCTRL.RVAL")
  field(LNK4, "QUAD:LI14:891:FUNC CA PP")
  field(DOL5, "MGNT:LI14:1:QUADCTRL.RVAL")
  field(LNK5, "QUAD:LI14:891:FUNC CA PP")
  field(DOL6, "MGNT:LI14:1:XCORCTRL.RVAL")
  field(LNK6, "QUAD:LI14:891:FUNC CA PP")
  field(DOL7, "MGNT:LI14:1:YCORCTRL.RVAL")
  field(LNK7, "QUAD:LI14:891:FUNC CA PP")
  field(DOL8, "MGNT:LI14:1:SOLNCTRL.RVAL")
  field(LNK8, "QUAD:LI14:891:FUNC CA PP")
  field(DOL9, "MGNT:LI14:1:KICKCTRL.RVAL")
  field(LNK9, "QUAD:LI14:891:FUNC CA PP")
  field(DOLA, "MGNT:LI14:1:SEXTCTRL.RVAL")
  field(LNKA, "QUAD:LI14:891:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "QUAD:LI14:891:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "QUAD:LI14:891:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "QUAD:LI14:891:EDES.PROC PP")
    field(LNK2, "QUAD:LI14:891:EACT.PROC PP")
    field(LNK3, "QUAD:LI14:891:EERR.DISA PP")
    field(LNK4, "QUAD:LI14:891:ECON.PROC PP")
    field(LNK5, "QUAD:LI14:891:BMAGX.PROC PP")
    field(LNK6, "QUAD:LI14:891:BMAGY.PROC PP")
    field(LNK7, "QUAD:LI14:891:BLEM.PROC PP")
    field(LNK8, "QUAD:LI14:891:BMOD.PROC PP")
    field(LNK9, "QUAD:LI14:891:EDESSAVE.PROC PP")
    field(LNKA, "QUAD:LI14:891:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"QUAD:LI14:891:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "QUAD:LI14:891:BMAX")
  field(DOL2, "QUAD:LI14:891:BMAX")
  field(DOL3, "QUAD:LI14:891:BMAX")
  field(DOL4, "QUAD:LI14:891:BMIN")
  field(DOL5, "QUAD:LI14:891:BMIN")
  field(DOL6, "QUAD:LI14:891:BMIN")
  field(LNK1, "QUAD:LI14:891:BMAGX.HOPR")
  field(LNK2, "QUAD:LI14:891:BMAGY.HOPR")
  field(LNK3, "QUAD:LI14:891:BLEM.HOPR")
  field(LNK4, "QUAD:LI14:891:BMAGX.LOPR PP")
  field(LNK5, "QUAD:LI14:891:BMAGY.LOPR PP")
  field(LNK6, "QUAD:LI14:891:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "QUAD:LI14:891:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "QUAD:LI14:891:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "QUAD:LI14:891:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "QUAD:LI14:891:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "QUAD:LI14:891:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI14:891:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI14:891:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI14:891:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI14:891:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI14:891:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "QUAD:LI14:891:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "QUAD:LI14:891:EDES NPP MS")
  field(INPB, "QUAD:LI14:891:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "QUAD:LI14:901:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI14:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI14:1:CTRL.RVAL")
  field(LNK1, "QUAD:LI14:901:FUNC CA PP")
  field(DOL2, "MGNT:LI14:1:BENDCTRL.RVAL")
  field(LNK2, "QUAD:LI14:901:FUNC CA PP")
  field(DOL3, "MGNT:LI14:1:BTRMCTRL.RVAL")
  field(LNK3, "QUAD:LI14:901:FUNC CA PP")
  field(DOL4, "MGNT:LI14:1:LGPSCTRL.RVAL")
  field(LNK4, "QUAD:LI14:901:FUNC CA PP")
  field(DOL5, "MGNT:LI14:1:QUADCTRL.RVAL")
  field(LNK5, "QUAD:LI14:901:FUNC CA PP")
  field(DOL6, "MGNT:LI14:1:XCORCTRL.RVAL")
  field(LNK6, "QUAD:LI14:901:FUNC CA PP")
  field(DOL7, "MGNT:LI14:1:YCORCTRL.RVAL")
  field(LNK7, "QUAD:LI14:901:FUNC CA PP")
  field(DOL8, "MGNT:LI14:1:SOLNCTRL.RVAL")
  field(LNK8, "QUAD:LI14:901:FUNC CA PP")
  field(DOL9, "MGNT:LI14:1:KICKCTRL.RVAL")
  field(LNK9, "QUAD:LI14:901:FUNC CA PP")
  field(DOLA, "MGNT:LI14:1:SEXTCTRL.RVAL")
  field(LNKA, "QUAD:LI14:901:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "QUAD:LI14:901:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "QUAD:LI14:901:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "QUAD:LI14:901:EDES.PROC PP")
    field(LNK2, "QUAD:LI14:901:EACT.PROC PP")
    field(LNK3, "QUAD:LI14:901:EERR.DISA PP")
    field(LNK4, "QUAD:LI14:901:ECON.PROC PP")
    field(LNK5, "QUAD:LI14:901:BMAGX.PROC PP")
    field(LNK6, "QUAD:LI14:901:BMAGY.PROC PP")
    field(LNK7, "QUAD:LI14:901:BLEM.PROC PP")
    field(LNK8, "QUAD:LI14:901:BMOD.PROC PP")
    field(LNK9, "QUAD:LI14:901:EDESSAVE.PROC PP")
    field(LNKA, "QUAD:LI14:901:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"QUAD:LI14:901:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "QUAD:LI14:901:BMAX")
  field(DOL2, "QUAD:LI14:901:BMAX")
  field(DOL3, "QUAD:LI14:901:BMAX")
  field(DOL4, "QUAD:LI14:901:BMIN")
  field(DOL5, "QUAD:LI14:901:BMIN")
  field(DOL6, "QUAD:LI14:901:BMIN")
  field(LNK1, "QUAD:LI14:901:BMAGX.HOPR")
  field(LNK2, "QUAD:LI14:901:BMAGY.HOPR")
  field(LNK3, "QUAD:LI14:901:BLEM.HOPR")
  field(LNK4, "QUAD:LI14:901:BMAGX.LOPR PP")
  field(LNK5, "QUAD:LI14:901:BMAGY.LOPR PP")
  field(LNK6, "QUAD:LI14:901:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "QUAD:LI14:901:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "QUAD:LI14:901:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "QUAD:LI14:901:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "QUAD:LI14:901:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "QUAD:LI14:901:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI14:901:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI14:901:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI14:901:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI14:901:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI14:901:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "QUAD:LI14:901:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "QUAD:LI14:901:EDES NPP MS")
  field(INPB, "QUAD:LI14:901:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "QUAD:LI14:1738:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI14:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI14:1:CTRL.RVAL")
  field(LNK1, "QUAD:LI14:1738:FUNC CA PP")
  field(DOL2, "MGNT:LI14:1:BENDCTRL.RVAL")
  field(LNK2, "QUAD:LI14:1738:FUNC CA PP")
  field(DOL3, "MGNT:LI14:1:BTRMCTRL.RVAL")
  field(LNK3, "QUAD:LI14:1738:FUNC CA PP")
  field(DOL4, "MGNT:LI14:1:LGPSCTRL.RVAL")
  field(LNK4, "QUAD:LI14:1738:FUNC CA PP")
  field(DOL5, "MGNT:LI14:1:QUADCTRL.RVAL")
  field(LNK5, "QUAD:LI14:1738:FUNC CA PP")
  field(DOL6, "MGNT:LI14:1:XCORCTRL.RVAL")
  field(LNK6, "QUAD:LI14:1738:FUNC CA PP")
  field(DOL7, "MGNT:LI14:1:YCORCTRL.RVAL")
  field(LNK7, "QUAD:LI14:1738:FUNC CA PP")
  field(DOL8, "MGNT:LI14:1:SOLNCTRL.RVAL")
  field(LNK8, "QUAD:LI14:1738:FUNC CA PP")
  field(DOL9, "MGNT:LI14:1:KICKCTRL.RVAL")
  field(LNK9, "QUAD:LI14:1738:FUNC CA PP")
  field(DOLA, "MGNT:LI14:1:SEXTCTRL.RVAL")
  field(LNKA, "QUAD:LI14:1738:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "QUAD:LI14:1738:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "QUAD:LI14:1738:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "QUAD:LI14:1738:EDES.PROC PP")
    field(LNK2, "QUAD:LI14:1738:EACT.PROC PP")
    field(LNK3, "QUAD:LI14:1738:EERR.DISA PP")
    field(LNK4, "QUAD:LI14:1738:ECON.PROC PP")
    field(LNK5, "QUAD:LI14:1738:BMAGX.PROC PP")
    field(LNK6, "QUAD:LI14:1738:BMAGY.PROC PP")
    field(LNK7, "QUAD:LI14:1738:BLEM.PROC PP")
    field(LNK8, "QUAD:LI14:1738:BMOD.PROC PP")
    field(LNK9, "QUAD:LI14:1738:EDESSAVE.PROC PP")
    field(LNKA, "QUAD:LI14:1738:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"QUAD:LI14:1738:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "QUAD:LI14:1738:BMAX")
  field(DOL2, "QUAD:LI14:1738:BMAX")
  field(DOL3, "QUAD:LI14:1738:BMAX")
  field(DOL4, "QUAD:LI14:1738:BMIN")
  field(DOL5, "QUAD:LI14:1738:BMIN")
  field(DOL6, "QUAD:LI14:1738:BMIN")
  field(LNK1, "QUAD:LI14:1738:BMAGX.HOPR")
  field(LNK2, "QUAD:LI14:1738:BMAGY.HOPR")
  field(LNK3, "QUAD:LI14:1738:BLEM.HOPR")
  field(LNK4, "QUAD:LI14:1738:BMAGX.LOPR PP")
  field(LNK5, "QUAD:LI14:1738:BMAGY.LOPR PP")
  field(LNK6, "QUAD:LI14:1738:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "QUAD:LI14:1738:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "QUAD:LI14:1738:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "QUAD:LI14:1738:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "QUAD:LI14:1738:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "QUAD:LI14:1738:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI14:1738:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI14:1738:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI14:1738:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI14:1738:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI14:1738:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "QUAD:LI14:1738:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "QUAD:LI14:1738:EDES NPP MS")
  field(INPB, "QUAD:LI14:1738:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "QUAD:LI14:1866:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI14:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI14:1:CTRL.RVAL")
  field(LNK1, "QUAD:LI14:1866:FUNC CA PP")
  field(DOL2, "MGNT:LI14:1:BENDCTRL.RVAL")
  field(LNK2, "QUAD:LI14:1866:FUNC CA PP")
  field(DOL3, "MGNT:LI14:1:BTRMCTRL.RVAL")
  field(LNK3, "QUAD:LI14:1866:FUNC CA PP")
  field(DOL4, "MGNT:LI14:1:LGPSCTRL.RVAL")
  field(LNK4, "QUAD:LI14:1866:FUNC CA PP")
  field(DOL5, "MGNT:LI14:1:QUADCTRL.RVAL")
  field(LNK5, "QUAD:LI14:1866:FUNC CA PP")
  field(DOL6, "MGNT:LI14:1:XCORCTRL.RVAL")
  field(LNK6, "QUAD:LI14:1866:FUNC CA PP")
  field(DOL7, "MGNT:LI14:1:YCORCTRL.RVAL")
  field(LNK7, "QUAD:LI14:1866:FUNC CA PP")
  field(DOL8, "MGNT:LI14:1:SOLNCTRL.RVAL")
  field(LNK8, "QUAD:LI14:1866:FUNC CA PP")
  field(DOL9, "MGNT:LI14:1:KICKCTRL.RVAL")
  field(LNK9, "QUAD:LI14:1866:FUNC CA PP")
  field(DOLA, "MGNT:LI14:1:SEXTCTRL.RVAL")
  field(LNKA, "QUAD:LI14:1866:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "QUAD:LI14:1866:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "QUAD:LI14:1866:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "QUAD:LI14:1866:EDES.PROC PP")
    field(LNK2, "QUAD:LI14:1866:EACT.PROC PP")
    field(LNK3, "QUAD:LI14:1866:EERR.DISA PP")
    field(LNK4, "QUAD:LI14:1866:ECON.PROC PP")
    field(LNK5, "QUAD:LI14:1866:BMAGX.PROC PP")
    field(LNK6, "QUAD:LI14:1866:BMAGY.PROC PP")
    field(LNK7, "QUAD:LI14:1866:BLEM.PROC PP")
    field(LNK8, "QUAD:LI14:1866:BMOD.PROC PP")
    field(LNK9, "QUAD:LI14:1866:EDESSAVE.PROC PP")
    field(LNKA, "QUAD:LI14:1866:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"QUAD:LI14:1866:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "QUAD:LI14:1866:BMAX")
  field(DOL2, "QUAD:LI14:1866:BMAX")
  field(DOL3, "QUAD:LI14:1866:BMAX")
  field(DOL4, "QUAD:LI14:1866:BMIN")
  field(DOL5, "QUAD:LI14:1866:BMIN")
  field(DOL6, "QUAD:LI14:1866:BMIN")
  field(LNK1, "QUAD:LI14:1866:BMAGX.HOPR")
  field(LNK2, "QUAD:LI14:1866:BMAGY.HOPR")
  field(LNK3, "QUAD:LI14:1866:BLEM.HOPR")
  field(LNK4, "QUAD:LI14:1866:BMAGX.LOPR PP")
  field(LNK5, "QUAD:LI14:1866:BMAGY.LOPR PP")
  field(LNK6, "QUAD:LI14:1866:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "QUAD:LI14:1866:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "QUAD:LI14:1866:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "QUAD:LI14:1866:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "QUAD:LI14:1866:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "QUAD:LI14:1866:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI14:1866:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI14:1866:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI14:1866:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI14:1866:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI14:1866:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "QUAD:LI14:1866:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "QUAD:LI14:1866:EDES NPP MS")
  field(INPB, "QUAD:LI14:1866:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "BTRM:LI14:720:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI14:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI14:1:CTRL.RVAL")
  field(LNK1, "BTRM:LI14:720:FUNC CA PP")
  field(DOL2, "MGNT:LI14:1:BENDCTRL.RVAL")
  field(LNK2, "BTRM:LI14:720:FUNC CA PP")
  field(DOL3, "MGNT:LI14:1:BTRMCTRL.RVAL")
  field(LNK3, "BTRM:LI14:720:FUNC CA PP")
  field(DOL4, "MGNT:LI14:1:LGPSCTRL.RVAL")
  field(LNK4, "BTRM:LI14:720:FUNC CA PP")
  field(DOL5, "MGNT:LI14:1:QUADCTRL.RVAL")
  field(LNK5, "BTRM:LI14:720:FUNC CA PP")
  field(DOL6, "MGNT:LI14:1:XCORCTRL.RVAL")
  field(LNK6, "BTRM:LI14:720:FUNC CA PP")
  field(DOL7, "MGNT:LI14:1:YCORCTRL.RVAL")
  field(LNK7, "BTRM:LI14:720:FUNC CA PP")
  field(DOL8, "MGNT:LI14:1:SOLNCTRL.RVAL")
  field(LNK8, "BTRM:LI14:720:FUNC CA PP")
  field(DOL9, "MGNT:LI14:1:KICKCTRL.RVAL")
  field(LNK9, "BTRM:LI14:720:FUNC CA PP")
  field(DOLA, "MGNT:LI14:1:SEXTCTRL.RVAL")
  field(LNKA, "BTRM:LI14:720:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "BTRM:LI14:720:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "BTRM:LI14:720:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "BTRM:LI14:720:EDES.PROC PP")
    field(LNK2, "BTRM:LI14:720:EACT.PROC PP")
    field(LNK3, "BTRM:LI14:720:EERR.DISA PP")
    field(LNK4, "BTRM:LI14:720:ECON.PROC PP")
    field(LNK5, "BTRM:LI14:720:BMAGX.PROC PP")
    field(LNK6, "BTRM:LI14:720:BMAGY.PROC PP")
    field(LNK7, "BTRM:LI14:720:BLEM.PROC PP")
    field(LNK8, "BTRM:LI14:720:BMOD.PROC PP")
    field(LNK9, "BTRM:LI14:720:EDESSAVE.PROC PP")
    field(LNKA, "BTRM:LI14:720:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"BTRM:LI14:720:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "BTRM:LI14:720:BMAX")
  field(DOL2, "BTRM:LI14:720:BMAX")
  field(DOL3, "BTRM:LI14:720:BMAX")
  field(DOL4, "BTRM:LI14:720:BMIN")
  field(DOL5, "BTRM:LI14:720:BMIN")
  field(DOL6, "BTRM:LI14:720:BMIN")
  field(LNK1, "BTRM:LI14:720:BMAGX.HOPR")
  field(LNK2, "BTRM:LI14:720:BMAGY.HOPR")
  field(LNK3, "BTRM:LI14:720:BLEM.HOPR")
  field(LNK4, "BTRM:LI14:720:BMAGX.LOPR PP")
  field(LNK5, "BTRM:LI14:720:BMAGY.LOPR PP")
  field(LNK6, "BTRM:LI14:720:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "BTRM:LI14:720:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "BTRM:LI14:720:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "BTRM:LI14:720:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "Amain")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "BTRM:LI14:720:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "Amain")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "BTRM:LI14:720:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:LI14:720:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:LI14:720:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "BTRM:LI14:720:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:LI14:720:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "BTRM:LI14:720:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "BTRM:LI14:720:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "BTRM:LI14:720:EDES NPP MS")
  field(INPB, "BTRM:LI14:720:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "BTRM:LI14:796:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI14:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI14:1:CTRL.RVAL")
  field(LNK1, "BTRM:LI14:796:FUNC CA PP")
  field(DOL2, "MGNT:LI14:1:BENDCTRL.RVAL")
  field(LNK2, "BTRM:LI14:796:FUNC CA PP")
  field(DOL3, "MGNT:LI14:1:BTRMCTRL.RVAL")
  field(LNK3, "BTRM:LI14:796:FUNC CA PP")
  field(DOL4, "MGNT:LI14:1:LGPSCTRL.RVAL")
  field(LNK4, "BTRM:LI14:796:FUNC CA PP")
  field(DOL5, "MGNT:LI14:1:QUADCTRL.RVAL")
  field(LNK5, "BTRM:LI14:796:FUNC CA PP")
  field(DOL6, "MGNT:LI14:1:XCORCTRL.RVAL")
  field(LNK6, "BTRM:LI14:796:FUNC CA PP")
  field(DOL7, "MGNT:LI14:1:YCORCTRL.RVAL")
  field(LNK7, "BTRM:LI14:796:FUNC CA PP")
  field(DOL8, "MGNT:LI14:1:SOLNCTRL.RVAL")
  field(LNK8, "BTRM:LI14:796:FUNC CA PP")
  field(DOL9, "MGNT:LI14:1:KICKCTRL.RVAL")
  field(LNK9, "BTRM:LI14:796:FUNC CA PP")
  field(DOLA, "MGNT:LI14:1:SEXTCTRL.RVAL")
  field(LNKA, "BTRM:LI14:796:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "BTRM:LI14:796:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "BTRM:LI14:796:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "BTRM:LI14:796:EDES.PROC PP")
    field(LNK2, "BTRM:LI14:796:EACT.PROC PP")
    field(LNK3, "BTRM:LI14:796:EERR.DISA PP")
    field(LNK4, "BTRM:LI14:796:ECON.PROC PP")
    field(LNK5, "BTRM:LI14:796:BMAGX.PROC PP")
    field(LNK6, "BTRM:LI14:796:BMAGY.PROC PP")
    field(LNK7, "BTRM:LI14:796:BLEM.PROC PP")
    field(LNK8, "BTRM:LI14:796:BMOD.PROC PP")
    field(LNK9, "BTRM:LI14:796:EDESSAVE.PROC PP")
    field(LNKA, "BTRM:LI14:796:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"BTRM:LI14:796:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "BTRM:LI14:796:BMAX")
  field(DOL2, "BTRM:LI14:796:BMAX")
  field(DOL3, "BTRM:LI14:796:BMAX")
  field(DOL4, "BTRM:LI14:796:BMIN")
  field(DOL5, "BTRM:LI14:796:BMIN")
  field(DOL6, "BTRM:LI14:796:BMIN")
  field(LNK1, "BTRM:LI14:796:BMAGX.HOPR")
  field(LNK2, "BTRM:LI14:796:BMAGY.HOPR")
  field(LNK3, "BTRM:LI14:796:BLEM.HOPR")
  field(LNK4, "BTRM:LI14:796:BMAGX.LOPR PP")
  field(LNK5, "BTRM:LI14:796:BMAGY.LOPR PP")
  field(LNK6, "BTRM:LI14:796:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "BTRM:LI14:796:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "BTRM:LI14:796:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "BTRM:LI14:796:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "Amain")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "BTRM:LI14:796:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "Amain")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "BTRM:LI14:796:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:LI14:796:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:LI14:796:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "BTRM:LI14:796:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:LI14:796:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "BTRM:LI14:796:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "BTRM:LI14:796:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "BTRM:LI14:796:EDES NPP MS")
  field(INPB, "BTRM:LI14:796:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "BTRM:LI14:808:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI14:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI14:1:CTRL.RVAL")
  field(LNK1, "BTRM:LI14:808:FUNC CA PP")
  field(DOL2, "MGNT:LI14:1:BENDCTRL.RVAL")
  field(LNK2, "BTRM:LI14:808:FUNC CA PP")
  field(DOL3, "MGNT:LI14:1:BTRMCTRL.RVAL")
  field(LNK3, "BTRM:LI14:808:FUNC CA PP")
  field(DOL4, "MGNT:LI14:1:LGPSCTRL.RVAL")
  field(LNK4, "BTRM:LI14:808:FUNC CA PP")
  field(DOL5, "MGNT:LI14:1:QUADCTRL.RVAL")
  field(LNK5, "BTRM:LI14:808:FUNC CA PP")
  field(DOL6, "MGNT:LI14:1:XCORCTRL.RVAL")
  field(LNK6, "BTRM:LI14:808:FUNC CA PP")
  field(DOL7, "MGNT:LI14:1:YCORCTRL.RVAL")
  field(LNK7, "BTRM:LI14:808:FUNC CA PP")
  field(DOL8, "MGNT:LI14:1:SOLNCTRL.RVAL")
  field(LNK8, "BTRM:LI14:808:FUNC CA PP")
  field(DOL9, "MGNT:LI14:1:KICKCTRL.RVAL")
  field(LNK9, "BTRM:LI14:808:FUNC CA PP")
  field(DOLA, "MGNT:LI14:1:SEXTCTRL.RVAL")
  field(LNKA, "BTRM:LI14:808:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "BTRM:LI14:808:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "BTRM:LI14:808:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "BTRM:LI14:808:EDES.PROC PP")
    field(LNK2, "BTRM:LI14:808:EACT.PROC PP")
    field(LNK3, "BTRM:LI14:808:EERR.DISA PP")
    field(LNK4, "BTRM:LI14:808:ECON.PROC PP")
    field(LNK5, "BTRM:LI14:808:BMAGX.PROC PP")
    field(LNK6, "BTRM:LI14:808:BMAGY.PROC PP")
    field(LNK7, "BTRM:LI14:808:BLEM.PROC PP")
    field(LNK8, "BTRM:LI14:808:BMOD.PROC PP")
    field(LNK9, "BTRM:LI14:808:EDESSAVE.PROC PP")
    field(LNKA, "BTRM:LI14:808:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"BTRM:LI14:808:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "BTRM:LI14:808:BMAX")
  field(DOL2, "BTRM:LI14:808:BMAX")
  field(DOL3, "BTRM:LI14:808:BMAX")
  field(DOL4, "BTRM:LI14:808:BMIN")
  field(DOL5, "BTRM:LI14:808:BMIN")
  field(DOL6, "BTRM:LI14:808:BMIN")
  field(LNK1, "BTRM:LI14:808:BMAGX.HOPR")
  field(LNK2, "BTRM:LI14:808:BMAGY.HOPR")
  field(LNK3, "BTRM:LI14:808:BLEM.HOPR")
  field(LNK4, "BTRM:LI14:808:BMAGX.LOPR PP")
  field(LNK5, "BTRM:LI14:808:BMAGY.LOPR PP")
  field(LNK6, "BTRM:LI14:808:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "BTRM:LI14:808:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "BTRM:LI14:808:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "BTRM:LI14:808:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "Amain")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "BTRM:LI14:808:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "Amain")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "BTRM:LI14:808:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:LI14:808:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:LI14:808:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "BTRM:LI14:808:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:LI14:808:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "BTRM:LI14:808:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "BTRM:LI14:808:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "BTRM:LI14:808:EDES NPP MS")
  field(INPB, "BTRM:LI14:808:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "BTRM:LI14:883:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI14:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI14:1:CTRL.RVAL")
  field(LNK1, "BTRM:LI14:883:FUNC CA PP")
  field(DOL2, "MGNT:LI14:1:BENDCTRL.RVAL")
  field(LNK2, "BTRM:LI14:883:FUNC CA PP")
  field(DOL3, "MGNT:LI14:1:BTRMCTRL.RVAL")
  field(LNK3, "BTRM:LI14:883:FUNC CA PP")
  field(DOL4, "MGNT:LI14:1:LGPSCTRL.RVAL")
  field(LNK4, "BTRM:LI14:883:FUNC CA PP")
  field(DOL5, "MGNT:LI14:1:QUADCTRL.RVAL")
  field(LNK5, "BTRM:LI14:883:FUNC CA PP")
  field(DOL6, "MGNT:LI14:1:XCORCTRL.RVAL")
  field(LNK6, "BTRM:LI14:883:FUNC CA PP")
  field(DOL7, "MGNT:LI14:1:YCORCTRL.RVAL")
  field(LNK7, "BTRM:LI14:883:FUNC CA PP")
  field(DOL8, "MGNT:LI14:1:SOLNCTRL.RVAL")
  field(LNK8, "BTRM:LI14:883:FUNC CA PP")
  field(DOL9, "MGNT:LI14:1:KICKCTRL.RVAL")
  field(LNK9, "BTRM:LI14:883:FUNC CA PP")
  field(DOLA, "MGNT:LI14:1:SEXTCTRL.RVAL")
  field(LNKA, "BTRM:LI14:883:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "BTRM:LI14:883:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "BTRM:LI14:883:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "BTRM:LI14:883:EDES.PROC PP")
    field(LNK2, "BTRM:LI14:883:EACT.PROC PP")
    field(LNK3, "BTRM:LI14:883:EERR.DISA PP")
    field(LNK4, "BTRM:LI14:883:ECON.PROC PP")
    field(LNK5, "BTRM:LI14:883:BMAGX.PROC PP")
    field(LNK6, "BTRM:LI14:883:BMAGY.PROC PP")
    field(LNK7, "BTRM:LI14:883:BLEM.PROC PP")
    field(LNK8, "BTRM:LI14:883:BMOD.PROC PP")
    field(LNK9, "BTRM:LI14:883:EDESSAVE.PROC PP")
    field(LNKA, "BTRM:LI14:883:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"BTRM:LI14:883:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "BTRM:LI14:883:BMAX")
  field(DOL2, "BTRM:LI14:883:BMAX")
  field(DOL3, "BTRM:LI14:883:BMAX")
  field(DOL4, "BTRM:LI14:883:BMIN")
  field(DOL5, "BTRM:LI14:883:BMIN")
  field(DOL6, "BTRM:LI14:883:BMIN")
  field(LNK1, "BTRM:LI14:883:BMAGX.HOPR")
  field(LNK2, "BTRM:LI14:883:BMAGY.HOPR")
  field(LNK3, "BTRM:LI14:883:BLEM.HOPR")
  field(LNK4, "BTRM:LI14:883:BMAGX.LOPR PP")
  field(LNK5, "BTRM:LI14:883:BMAGY.LOPR PP")
  field(LNK6, "BTRM:LI14:883:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "BTRM:LI14:883:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "BTRM:LI14:883:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "BTRM:LI14:883:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "Amain")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "BTRM:LI14:883:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "Amain")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "BTRM:LI14:883:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:LI14:883:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:LI14:883:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "BTRM:LI14:883:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:LI14:883:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "BTRM:LI14:883:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "BTRM:LI14:883:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "BTRM:LI14:883:EDES NPP MS")
  field(INPB, "BTRM:LI14:883:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "BTRM:LI14:1796:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI14:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI14:1:CTRL.RVAL")
  field(LNK1, "BTRM:LI14:1796:FUNC CA PP")
  field(DOL2, "MGNT:LI14:1:BENDCTRL.RVAL")
  field(LNK2, "BTRM:LI14:1796:FUNC CA PP")
  field(DOL3, "MGNT:LI14:1:BTRMCTRL.RVAL")
  field(LNK3, "BTRM:LI14:1796:FUNC CA PP")
  field(DOL4, "MGNT:LI14:1:LGPSCTRL.RVAL")
  field(LNK4, "BTRM:LI14:1796:FUNC CA PP")
  field(DOL5, "MGNT:LI14:1:QUADCTRL.RVAL")
  field(LNK5, "BTRM:LI14:1796:FUNC CA PP")
  field(DOL6, "MGNT:LI14:1:XCORCTRL.RVAL")
  field(LNK6, "BTRM:LI14:1796:FUNC CA PP")
  field(DOL7, "MGNT:LI14:1:YCORCTRL.RVAL")
  field(LNK7, "BTRM:LI14:1796:FUNC CA PP")
  field(DOL8, "MGNT:LI14:1:SOLNCTRL.RVAL")
  field(LNK8, "BTRM:LI14:1796:FUNC CA PP")
  field(DOL9, "MGNT:LI14:1:KICKCTRL.RVAL")
  field(LNK9, "BTRM:LI14:1796:FUNC CA PP")
  field(DOLA, "MGNT:LI14:1:SEXTCTRL.RVAL")
  field(LNKA, "BTRM:LI14:1796:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "BTRM:LI14:1796:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "BTRM:LI14:1796:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "BTRM:LI14:1796:EDES.PROC PP")
    field(LNK2, "BTRM:LI14:1796:EACT.PROC PP")
    field(LNK3, "BTRM:LI14:1796:EERR.DISA PP")
    field(LNK4, "BTRM:LI14:1796:ECON.PROC PP")
    field(LNK5, "BTRM:LI14:1796:BMAGX.PROC PP")
    field(LNK6, "BTRM:LI14:1796:BMAGY.PROC PP")
    field(LNK7, "BTRM:LI14:1796:BLEM.PROC PP")
    field(LNK8, "BTRM:LI14:1796:BMOD.PROC PP")
    field(LNK9, "BTRM:LI14:1796:EDESSAVE.PROC PP")
    field(LNKA, "BTRM:LI14:1796:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"BTRM:LI14:1796:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "BTRM:LI14:1796:BMAX")
  field(DOL2, "BTRM:LI14:1796:BMAX")
  field(DOL3, "BTRM:LI14:1796:BMAX")
  field(DOL4, "BTRM:LI14:1796:BMIN")
  field(DOL5, "BTRM:LI14:1796:BMIN")
  field(DOL6, "BTRM:LI14:1796:BMIN")
  field(LNK1, "BTRM:LI14:1796:BMAGX.HOPR")
  field(LNK2, "BTRM:LI14:1796:BMAGY.HOPR")
  field(LNK3, "BTRM:LI14:1796:BLEM.HOPR")
  field(LNK4, "BTRM:LI14:1796:BMAGX.LOPR PP")
  field(LNK5, "BTRM:LI14:1796:BMAGY.LOPR PP")
  field(LNK6, "BTRM:LI14:1796:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "BTRM:LI14:1796:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "BTRM:LI14:1796:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "BTRM:LI14:1796:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "Amain")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "BTRM:LI14:1796:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "Amain")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "BTRM:LI14:1796:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:LI14:1796:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:LI14:1796:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "BTRM:LI14:1796:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:LI14:1796:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "BTRM:LI14:1796:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "BTRM:LI14:1796:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "BTRM:LI14:1796:EDES NPP MS")
  field(INPB, "BTRM:LI14:1796:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "BTRM:LI14:1808:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI14:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI14:1:CTRL.RVAL")
  field(LNK1, "BTRM:LI14:1808:FUNC CA PP")
  field(DOL2, "MGNT:LI14:1:BENDCTRL.RVAL")
  field(LNK2, "BTRM:LI14:1808:FUNC CA PP")
  field(DOL3, "MGNT:LI14:1:BTRMCTRL.RVAL")
  field(LNK3, "BTRM:LI14:1808:FUNC CA PP")
  field(DOL4, "MGNT:LI14:1:LGPSCTRL.RVAL")
  field(LNK4, "BTRM:LI14:1808:FUNC CA PP")
  field(DOL5, "MGNT:LI14:1:QUADCTRL.RVAL")
  field(LNK5, "BTRM:LI14:1808:FUNC CA PP")
  field(DOL6, "MGNT:LI14:1:XCORCTRL.RVAL")
  field(LNK6, "BTRM:LI14:1808:FUNC CA PP")
  field(DOL7, "MGNT:LI14:1:YCORCTRL.RVAL")
  field(LNK7, "BTRM:LI14:1808:FUNC CA PP")
  field(DOL8, "MGNT:LI14:1:SOLNCTRL.RVAL")
  field(LNK8, "BTRM:LI14:1808:FUNC CA PP")
  field(DOL9, "MGNT:LI14:1:KICKCTRL.RVAL")
  field(LNK9, "BTRM:LI14:1808:FUNC CA PP")
  field(DOLA, "MGNT:LI14:1:SEXTCTRL.RVAL")
  field(LNKA, "BTRM:LI14:1808:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "BTRM:LI14:1808:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "BTRM:LI14:1808:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "BTRM:LI14:1808:EDES.PROC PP")
    field(LNK2, "BTRM:LI14:1808:EACT.PROC PP")
    field(LNK3, "BTRM:LI14:1808:EERR.DISA PP")
    field(LNK4, "BTRM:LI14:1808:ECON.PROC PP")
    field(LNK5, "BTRM:LI14:1808:BMAGX.PROC PP")
    field(LNK6, "BTRM:LI14:1808:BMAGY.PROC PP")
    field(LNK7, "BTRM:LI14:1808:BLEM.PROC PP")
    field(LNK8, "BTRM:LI14:1808:BMOD.PROC PP")
    field(LNK9, "BTRM:LI14:1808:EDESSAVE.PROC PP")
    field(LNKA, "BTRM:LI14:1808:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"BTRM:LI14:1808:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "BTRM:LI14:1808:BMAX")
  field(DOL2, "BTRM:LI14:1808:BMAX")
  field(DOL3, "BTRM:LI14:1808:BMAX")
  field(DOL4, "BTRM:LI14:1808:BMIN")
  field(DOL5, "BTRM:LI14:1808:BMIN")
  field(DOL6, "BTRM:LI14:1808:BMIN")
  field(LNK1, "BTRM:LI14:1808:BMAGX.HOPR")
  field(LNK2, "BTRM:LI14:1808:BMAGY.HOPR")
  field(LNK3, "BTRM:LI14:1808:BLEM.HOPR")
  field(LNK4, "BTRM:LI14:1808:BMAGX.LOPR PP")
  field(LNK5, "BTRM:LI14:1808:BMAGY.LOPR PP")
  field(LNK6, "BTRM:LI14:1808:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "BTRM:LI14:1808:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "BTRM:LI14:1808:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "BTRM:LI14:1808:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "Amain")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "BTRM:LI14:1808:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "Amain")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "BTRM:LI14:1808:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:LI14:1808:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:LI14:1808:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "BTRM:LI14:1808:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "BTRM:LI14:1808:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "BTRM:LI14:1808:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "BTRM:LI14:1808:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "BTRM:LI14:1808:EDES NPP MS")
  field(INPB, "BTRM:LI14:1808:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "BEND:LI14:796:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI14:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI14:1:CTRL.RVAL")
  field(LNK1, "BEND:LI14:796:FUNC CA PP")
  field(DOL2, "MGNT:LI14:1:BENDCTRL.RVAL")
  field(LNK2, "BEND:LI14:796:FUNC CA PP")
  field(DOL3, "MGNT:LI14:1:BTRMCTRL.RVAL")
  field(LNK3, "BEND:LI14:796:FUNC CA PP")
  field(DOL4, "MGNT:LI14:1:LGPSCTRL.RVAL")
  field(LNK4, "BEND:LI14:796:FUNC CA PP")
  field(DOL5, "MGNT:LI14:1:QUADCTRL.RVAL")
  field(LNK5, "BEND:LI14:796:FUNC CA PP")
  field(DOL6, "MGNT:LI14:1:XCORCTRL.RVAL")
  field(LNK6, "BEND:LI14:796:FUNC CA PP")
  field(DOL7, "MGNT:LI14:1:YCORCTRL.RVAL")
  field(LNK7, "BEND:LI14:796:FUNC CA PP")
  field(DOL8, "MGNT:LI14:1:SOLNCTRL.RVAL")
  field(LNK8, "BEND:LI14:796:FUNC CA PP")
  field(DOL9, "MGNT:LI14:1:KICKCTRL.RVAL")
  field(LNK9, "BEND:LI14:796:FUNC CA PP")
  field(DOLA, "MGNT:LI14:1:SEXTCTRL.RVAL")
  field(LNKA, "BEND:LI14:796:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "BEND:LI14:796:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "BEND:LI14:796:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "BEND:LI14:796:EDES.PROC PP")
    field(LNK2, "BEND:LI14:796:EACT.PROC PP")
    field(LNK3, "BEND:LI14:796:EERR.DISA PP")
    field(LNK4, "BEND:LI14:796:ECON.PROC PP")
    field(LNK5, "BEND:LI14:796:BMAGX.PROC PP")
    field(LNK6, "BEND:LI14:796:BMAGY.PROC PP")
    field(LNK7, "BEND:LI14:796:BLEM.PROC PP")
    field(LNK8, "BEND:LI14:796:BMOD.PROC PP")
    field(LNK9, "BEND:LI14:796:EDESSAVE.PROC PP")
    field(LNKA, "BEND:LI14:796:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"BEND:LI14:796:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "BEND:LI14:796:BMAX")
  field(DOL2, "BEND:LI14:796:BMAX")
  field(DOL3, "BEND:LI14:796:BMAX")
  field(DOL4, "BEND:LI14:796:BMIN")
  field(DOL5, "BEND:LI14:796:BMIN")
  field(DOL6, "BEND:LI14:796:BMIN")
  field(LNK1, "BEND:LI14:796:BMAGX.HOPR")
  field(LNK2, "BEND:LI14:796:BMAGY.HOPR")
  field(LNK3, "BEND:LI14:796:BLEM.HOPR")
  field(LNK4, "BEND:LI14:796:BMAGX.LOPR PP")
  field(LNK5, "BEND:LI14:796:BMAGY.LOPR PP")
  field(LNK6, "BEND:LI14:796:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "BEND:LI14:796:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "BEND:LI14:796:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "BEND:LI14:796:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "BEND:LI14:796:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "BEND:LI14:796:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:LI14:796:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:LI14:796:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "BEND:LI14:796:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:LI14:796:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "BEND:LI14:796:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "BEND:LI14:796:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "BEND:LI14:796:EDES NPP MS")
  field(INPB, "BEND:LI14:796:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "LGPS:LI14:2:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI14:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI14:1:CTRL.RVAL")
  field(LNK1, "LGPS:LI14:2:FUNC CA PP")
  field(DOL2, "MGNT:LI14:1:BENDCTRL.RVAL")
  field(LNK2, "LGPS:LI14:2:FUNC CA PP")
  field(DOL3, "MGNT:LI14:1:BTRMCTRL.RVAL")
  field(LNK3, "LGPS:LI14:2:FUNC CA PP")
  field(DOL4, "MGNT:LI14:1:LGPSCTRL.RVAL")
  field(LNK4, "LGPS:LI14:2:FUNC CA PP")
  field(DOL5, "MGNT:LI14:1:QUADCTRL.RVAL")
  field(LNK5, "LGPS:LI14:2:FUNC CA PP")
  field(DOL6, "MGNT:LI14:1:XCORCTRL.RVAL")
  field(LNK6, "LGPS:LI14:2:FUNC CA PP")
  field(DOL7, "MGNT:LI14:1:YCORCTRL.RVAL")
  field(LNK7, "LGPS:LI14:2:FUNC CA PP")
  field(DOL8, "MGNT:LI14:1:SOLNCTRL.RVAL")
  field(LNK8, "LGPS:LI14:2:FUNC CA PP")
  field(DOL9, "MGNT:LI14:1:KICKCTRL.RVAL")
  field(LNK9, "LGPS:LI14:2:FUNC CA PP")
  field(DOLA, "MGNT:LI14:1:SEXTCTRL.RVAL")
  field(LNKA, "LGPS:LI14:2:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "LGPS:LI14:2:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "LGPS:LI14:2:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "LGPS:LI14:2:EDES.PROC PP")
    field(LNK2, "LGPS:LI14:2:EACT.PROC PP")
    field(LNK3, "LGPS:LI14:2:EERR.DISA PP")
    field(LNK4, "LGPS:LI14:2:ECON.PROC PP")
    field(LNK5, "LGPS:LI14:2:BMAGX.PROC PP")
    field(LNK6, "LGPS:LI14:2:BMAGY.PROC PP")
    field(LNK7, "LGPS:LI14:2:BLEM.PROC PP")
    field(LNK8, "LGPS:LI14:2:BMOD.PROC PP")
    field(LNK9, "LGPS:LI14:2:EDESSAVE.PROC PP")
    field(LNKA, "LGPS:LI14:2:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"LGPS:LI14:2:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "LGPS:LI14:2:BMAX")
  field(DOL2, "LGPS:LI14:2:BMAX")
  field(DOL3, "LGPS:LI14:2:BMAX")
  field(DOL4, "LGPS:LI14:2:BMIN")
  field(DOL5, "LGPS:LI14:2:BMIN")
  field(DOL6, "LGPS:LI14:2:BMIN")
  field(LNK1, "LGPS:LI14:2:BMAGX.HOPR")
  field(LNK2, "LGPS:LI14:2:BMAGY.HOPR")
  field(LNK3, "LGPS:LI14:2:BLEM.HOPR")
  field(LNK4, "LGPS:LI14:2:BMAGX.LOPR PP")
  field(LNK5, "LGPS:LI14:2:BMAGY.LOPR PP")
  field(LNK6, "LGPS:LI14:2:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "LGPS:LI14:2:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "LGPS:LI14:2:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "LGPS:LI14:2:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "Volts")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "LGPS:LI14:2:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "Volts")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "LGPS:LI14:2:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "LGPS:LI14:2:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "LGPS:LI14:2:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "LGPS:LI14:2:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "LGPS:LI14:2:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "LGPS:LI14:2:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "LGPS:LI14:2:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "LGPS:LI14:2:EDES NPP MS")
  field(INPB, "LGPS:LI14:2:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "QUAD:LI19:851:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI19:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI19:1:CTRL.RVAL")
  field(LNK1, "QUAD:LI19:851:FUNC CA PP")
  field(DOL2, "MGNT:LI19:1:BENDCTRL.RVAL")
  field(LNK2, "QUAD:LI19:851:FUNC CA PP")
  field(DOL3, "MGNT:LI19:1:BTRMCTRL.RVAL")
  field(LNK3, "QUAD:LI19:851:FUNC CA PP")
  field(DOL4, "MGNT:LI19:1:LGPSCTRL.RVAL")
  field(LNK4, "QUAD:LI19:851:FUNC CA PP")
  field(DOL5, "MGNT:LI19:1:QUADCTRL.RVAL")
  field(LNK5, "QUAD:LI19:851:FUNC CA PP")
  field(DOL6, "MGNT:LI19:1:XCORCTRL.RVAL")
  field(LNK6, "QUAD:LI19:851:FUNC CA PP")
  field(DOL7, "MGNT:LI19:1:YCORCTRL.RVAL")
  field(LNK7, "QUAD:LI19:851:FUNC CA PP")
  field(DOL8, "MGNT:LI19:1:SOLNCTRL.RVAL")
  field(LNK8, "QUAD:LI19:851:FUNC CA PP")
  field(DOL9, "MGNT:LI19:1:KICKCTRL.RVAL")
  field(LNK9, "QUAD:LI19:851:FUNC CA PP")
  field(DOLA, "MGNT:LI19:1:SEXTCTRL.RVAL")
  field(LNKA, "QUAD:LI19:851:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "QUAD:LI19:851:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "QUAD:LI19:851:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "QUAD:LI19:851:EDES.PROC PP")
    field(LNK2, "QUAD:LI19:851:EACT.PROC PP")
    field(LNK3, "QUAD:LI19:851:EERR.DISA PP")
    field(LNK4, "QUAD:LI19:851:ECON.PROC PP")
    field(LNK5, "QUAD:LI19:851:BMAGX.PROC PP")
    field(LNK6, "QUAD:LI19:851:BMAGY.PROC PP")
    field(LNK7, "QUAD:LI19:851:BLEM.PROC PP")
    field(LNK8, "QUAD:LI19:851:BMOD.PROC PP")
    field(LNK9, "QUAD:LI19:851:EDESSAVE.PROC PP")
    field(LNKA, "QUAD:LI19:851:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"QUAD:LI19:851:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "QUAD:LI19:851:BMAX")
  field(DOL2, "QUAD:LI19:851:BMAX")
  field(DOL3, "QUAD:LI19:851:BMAX")
  field(DOL4, "QUAD:LI19:851:BMIN")
  field(DOL5, "QUAD:LI19:851:BMIN")
  field(DOL6, "QUAD:LI19:851:BMIN")
  field(LNK1, "QUAD:LI19:851:BMAGX.HOPR")
  field(LNK2, "QUAD:LI19:851:BMAGY.HOPR")
  field(LNK3, "QUAD:LI19:851:BLEM.HOPR")
  field(LNK4, "QUAD:LI19:851:BMAGX.LOPR PP")
  field(LNK5, "QUAD:LI19:851:BMAGY.LOPR PP")
  field(LNK6, "QUAD:LI19:851:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "QUAD:LI19:851:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "QUAD:LI19:851:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "QUAD:LI19:851:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "QUAD:LI19:851:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "QUAD:LI19:851:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI19:851:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI19:851:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI19:851:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI19:851:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI19:851:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "QUAD:LI19:851:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "QUAD:LI19:851:EDES NPP MS")
  field(INPB, "QUAD:LI19:851:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "QUAD:LI19:871:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI19:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI19:1:CTRL.RVAL")
  field(LNK1, "QUAD:LI19:871:FUNC CA PP")
  field(DOL2, "MGNT:LI19:1:BENDCTRL.RVAL")
  field(LNK2, "QUAD:LI19:871:FUNC CA PP")
  field(DOL3, "MGNT:LI19:1:BTRMCTRL.RVAL")
  field(LNK3, "QUAD:LI19:871:FUNC CA PP")
  field(DOL4, "MGNT:LI19:1:LGPSCTRL.RVAL")
  field(LNK4, "QUAD:LI19:871:FUNC CA PP")
  field(DOL5, "MGNT:LI19:1:QUADCTRL.RVAL")
  field(LNK5, "QUAD:LI19:871:FUNC CA PP")
  field(DOL6, "MGNT:LI19:1:XCORCTRL.RVAL")
  field(LNK6, "QUAD:LI19:871:FUNC CA PP")
  field(DOL7, "MGNT:LI19:1:YCORCTRL.RVAL")
  field(LNK7, "QUAD:LI19:871:FUNC CA PP")
  field(DOL8, "MGNT:LI19:1:SOLNCTRL.RVAL")
  field(LNK8, "QUAD:LI19:871:FUNC CA PP")
  field(DOL9, "MGNT:LI19:1:KICKCTRL.RVAL")
  field(LNK9, "QUAD:LI19:871:FUNC CA PP")
  field(DOLA, "MGNT:LI19:1:SEXTCTRL.RVAL")
  field(LNKA, "QUAD:LI19:871:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "QUAD:LI19:871:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "QUAD:LI19:871:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "QUAD:LI19:871:EDES.PROC PP")
    field(LNK2, "QUAD:LI19:871:EACT.PROC PP")
    field(LNK3, "QUAD:LI19:871:EERR.DISA PP")
    field(LNK4, "QUAD:LI19:871:ECON.PROC PP")
    field(LNK5, "QUAD:LI19:871:BMAGX.PROC PP")
    field(LNK6, "QUAD:LI19:871:BMAGY.PROC PP")
    field(LNK7, "QUAD:LI19:871:BLEM.PROC PP")
    field(LNK8, "QUAD:LI19:871:BMOD.PROC PP")
    field(LNK9, "QUAD:LI19:871:EDESSAVE.PROC PP")
    field(LNKA, "QUAD:LI19:871:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"QUAD:LI19:871:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "QUAD:LI19:871:BMAX")
  field(DOL2, "QUAD:LI19:871:BMAX")
  field(DOL3, "QUAD:LI19:871:BMAX")
  field(DOL4, "QUAD:LI19:871:BMIN")
  field(DOL5, "QUAD:LI19:871:BMIN")
  field(DOL6, "QUAD:LI19:871:BMIN")
  field(LNK1, "QUAD:LI19:871:BMAGX.HOPR")
  field(LNK2, "QUAD:LI19:871:BMAGY.HOPR")
  field(LNK3, "QUAD:LI19:871:BLEM.HOPR")
  field(LNK4, "QUAD:LI19:871:BMAGX.LOPR PP")
  field(LNK5, "QUAD:LI19:871:BMAGY.LOPR PP")
  field(LNK6, "QUAD:LI19:871:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "QUAD:LI19:871:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "QUAD:LI19:871:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "QUAD:LI19:871:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "QUAD:LI19:871:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "QUAD:LI19:871:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI19:871:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI19:871:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI19:871:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:LI19:871:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:LI19:871:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "QUAD:LI19:871:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "QUAD:LI19:871:EDES NPP MS")
  field(INPB, "QUAD:LI19:871:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "BEND:IN10:451:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "BEND:IN10:451:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "BEND:IN10:451:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "BEND:IN10:451:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "BEND:IN10:451:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "BEND:IN10:451:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "BEND:IN10:451:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "BEND:IN10:451:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "BEND:IN10:451:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "BEND:IN10:451:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "BEND:IN10:451:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "BEND:IN10:451:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "BEND:IN10:451:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "BEND:IN10:451:EDES.PROC PP")
    field(LNK2, "BEND:IN10:451:EACT.PROC PP")
    field(LNK3, "BEND:IN10:451:EERR.DISA PP")
    field(LNK4, "BEND:IN10:451:ECON.PROC PP")
    field(LNK5, "BEND:IN10:451:BMAGX.PROC PP")
    field(LNK6, "BEND:IN10:451:BMAGY.PROC PP")
    field(LNK7, "BEND:IN10:451:BLEM.PROC PP")
    field(LNK8, "BEND:IN10:451:BMOD.PROC PP")
    field(LNK9, "BEND:IN10:451:EDESSAVE.PROC PP")
    field(LNKA, "BEND:IN10:451:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"BEND:IN10:451:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "BEND:IN10:451:BMAX")
  field(DOL2, "BEND:IN10:451:BMAX")
  field(DOL3, "BEND:IN10:451:BMAX")
  field(DOL4, "BEND:IN10:451:BMIN")
  field(DOL5, "BEND:IN10:451:BMIN")
  field(DOL6, "BEND:IN10:451:BMIN")
  field(LNK1, "BEND:IN10:451:BMAGX.HOPR")
  field(LNK2, "BEND:IN10:451:BMAGY.HOPR")
  field(LNK3, "BEND:IN10:451:BLEM.HOPR")
  field(LNK4, "BEND:IN10:451:BMAGX.LOPR PP")
  field(LNK5, "BEND:IN10:451:BMAGY.LOPR PP")
  field(LNK6, "BEND:IN10:451:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "BEND:IN10:451:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "BEND:IN10:451:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "BEND:IN10:451:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "BEND:IN10:451:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "BEND:IN10:451:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:IN10:451:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
  field(DOL,  "BEND:IN10:461:ECON CP MS")
  field(OMSL, "closed_loop")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:IN10:451:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
   field(DOL,  "BEND:IN10:461:EDES CP MS")
  field(OMSL, "closed_loop")
  field(FLNK, "BEND:IN10:451:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:IN10:451:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
   field(DOL,  "BEND:IN10:461:EACT CP MS")
  field(OMSL, "closed_loop")
  field(FLNK, "BEND:IN10:451:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "BEND:IN10:451:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "BEND:IN10:451:EDES NPP MS")
  field(INPB, "BEND:IN10:451:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "BEND:IN10:475:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "BEND:IN10:475:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "BEND:IN10:475:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "BEND:IN10:475:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "BEND:IN10:475:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "BEND:IN10:475:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "BEND:IN10:475:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "BEND:IN10:475:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "BEND:IN10:475:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "BEND:IN10:475:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "BEND:IN10:475:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "BEND:IN10:475:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "BEND:IN10:475:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "BEND:IN10:475:EDES.PROC PP")
    field(LNK2, "BEND:IN10:475:EACT.PROC PP")
    field(LNK3, "BEND:IN10:475:EERR.DISA PP")
    field(LNK4, "BEND:IN10:475:ECON.PROC PP")
    field(LNK5, "BEND:IN10:475:BMAGX.PROC PP")
    field(LNK6, "BEND:IN10:475:BMAGY.PROC PP")
    field(LNK7, "BEND:IN10:475:BLEM.PROC PP")
    field(LNK8, "BEND:IN10:475:BMOD.PROC PP")
    field(LNK9, "BEND:IN10:475:EDESSAVE.PROC PP")
    field(LNKA, "BEND:IN10:475:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"BEND:IN10:475:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "BEND:IN10:475:BMAX")
  field(DOL2, "BEND:IN10:475:BMAX")
  field(DOL3, "BEND:IN10:475:BMAX")
  field(DOL4, "BEND:IN10:475:BMIN")
  field(DOL5, "BEND:IN10:475:BMIN")
  field(DOL6, "BEND:IN10:475:BMIN")
  field(LNK1, "BEND:IN10:475:BMAGX.HOPR")
  field(LNK2, "BEND:IN10:475:BMAGY.HOPR")
  field(LNK3, "BEND:IN10:475:BLEM.HOPR")
  field(LNK4, "BEND:IN10:475:BMAGX.LOPR PP")
  field(LNK5, "BEND:IN10:475:BMAGY.LOPR PP")
  field(LNK6, "BEND:IN10:475:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "BEND:IN10:475:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "BEND:IN10:475:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "BEND:IN10:475:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "BEND:IN10:475:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "BEND:IN10:475:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:IN10:475:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
  field(DOL,  "BEND:IN10:461:ECON CP MS")
  field(OMSL, "closed_loop")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:IN10:475:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
   field(DOL,  "BEND:IN10:461:EDES CP MS")
  field(OMSL, "closed_loop")
  field(FLNK, "BEND:IN10:475:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:IN10:475:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
   field(DOL,  "BEND:IN10:461:EACT CP MS")
  field(OMSL, "closed_loop")
  field(FLNK, "BEND:IN10:475:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "BEND:IN10:475:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "BEND:IN10:475:EDES NPP MS")
  field(INPB, "BEND:IN10:475:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "BEND:IN10:481:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "BEND:IN10:481:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "BEND:IN10:481:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "BEND:IN10:481:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "BEND:IN10:481:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "BEND:IN10:481:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "BEND:IN10:481:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "BEND:IN10:481:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "BEND:IN10:481:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "BEND:IN10:481:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "BEND:IN10:481:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "BEND:IN10:481:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "BEND:IN10:481:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "BEND:IN10:481:EDES.PROC PP")
    field(LNK2, "BEND:IN10:481:EACT.PROC PP")
    field(LNK3, "BEND:IN10:481:EERR.DISA PP")
    field(LNK4, "BEND:IN10:481:ECON.PROC PP")
    field(LNK5, "BEND:IN10:481:BMAGX.PROC PP")
    field(LNK6, "BEND:IN10:481:BMAGY.PROC PP")
    field(LNK7, "BEND:IN10:481:BLEM.PROC PP")
    field(LNK8, "BEND:IN10:481:BMOD.PROC PP")
    field(LNK9, "BEND:IN10:481:EDESSAVE.PROC PP")
    field(LNKA, "BEND:IN10:481:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"BEND:IN10:481:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "BEND:IN10:481:BMAX")
  field(DOL2, "BEND:IN10:481:BMAX")
  field(DOL3, "BEND:IN10:481:BMAX")
  field(DOL4, "BEND:IN10:481:BMIN")
  field(DOL5, "BEND:IN10:481:BMIN")
  field(DOL6, "BEND:IN10:481:BMIN")
  field(LNK1, "BEND:IN10:481:BMAGX.HOPR")
  field(LNK2, "BEND:IN10:481:BMAGY.HOPR")
  field(LNK3, "BEND:IN10:481:BLEM.HOPR")
  field(LNK4, "BEND:IN10:481:BMAGX.LOPR PP")
  field(LNK5, "BEND:IN10:481:BMAGY.LOPR PP")
  field(LNK6, "BEND:IN10:481:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "BEND:IN10:481:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "BEND:IN10:481:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "BEND:IN10:481:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "BEND:IN10:481:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "BEND:IN10:481:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:IN10:481:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
  field(DOL,  "BEND:IN10:461:ECON CP MS")
  field(OMSL, "closed_loop")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:IN10:481:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
   field(DOL,  "BEND:IN10:461:EDES CP MS")
  field(OMSL, "closed_loop")
  field(FLNK, "BEND:IN10:481:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:IN10:481:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
   field(DOL,  "BEND:IN10:461:EACT CP MS")
  field(OMSL, "closed_loop")
  field(FLNK, "BEND:IN10:481:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "BEND:IN10:481:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "BEND:IN10:481:EDES NPP MS")
  field(INPB, "BEND:IN10:481:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "BEND:IN10:661:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:IN10:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:IN10:1:CTRL.RVAL")
  field(LNK1, "BEND:IN10:661:FUNC CA PP")
  field(DOL2, "MGNT:IN10:1:BENDCTRL.RVAL")
  field(LNK2, "BEND:IN10:661:FUNC CA PP")
  field(DOL3, "MGNT:IN10:1:BTRMCTRL.RVAL")
  field(LNK3, "BEND:IN10:661:FUNC CA PP")
  field(DOL4, "MGNT:IN10:1:LGPSCTRL.RVAL")
  field(LNK4, "BEND:IN10:661:FUNC CA PP")
  field(DOL5, "MGNT:IN10:1:QUADCTRL.RVAL")
  field(LNK5, "BEND:IN10:661:FUNC CA PP")
  field(DOL6, "MGNT:IN10:1:XCORCTRL.RVAL")
  field(LNK6, "BEND:IN10:661:FUNC CA PP")
  field(DOL7, "MGNT:IN10:1:YCORCTRL.RVAL")
  field(LNK7, "BEND:IN10:661:FUNC CA PP")
  field(DOL8, "MGNT:IN10:1:SOLNCTRL.RVAL")
  field(LNK8, "BEND:IN10:661:FUNC CA PP")
  field(DOL9, "MGNT:IN10:1:KICKCTRL.RVAL")
  field(LNK9, "BEND:IN10:661:FUNC CA PP")
  field(DOLA, "MGNT:IN10:1:SEXTCTRL.RVAL")
  field(LNKA, "BEND:IN10:661:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "BEND:IN10:661:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "BEND:IN10:661:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "BEND:IN10:661:EDES.PROC PP")
    field(LNK2, "BEND:IN10:661:EACT.PROC PP")
    field(LNK3, "BEND:IN10:661:EERR.DISA PP")
    field(LNK4, "BEND:IN10:661:ECON.PROC PP")
    field(LNK5, "BEND:IN10:661:BMAGX.PROC PP")
    field(LNK6, "BEND:IN10:661:BMAGY.PROC PP")
    field(LNK7, "BEND:IN10:661:BLEM.PROC PP")
    field(LNK8, "BEND:IN10:661:BMOD.PROC PP")
    field(LNK9, "BEND:IN10:661:EDESSAVE.PROC PP")
    field(LNKA, "BEND:IN10:661:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"BEND:IN10:661:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "BEND:IN10:661:BMAX")
  field(DOL2, "BEND:IN10:661:BMAX")
  field(DOL3, "BEND:IN10:661:BMAX")
  field(DOL4, "BEND:IN10:661:BMIN")
  field(DOL5, "BEND:IN10:661:BMIN")
  field(DOL6, "BEND:IN10:661:BMIN")
  field(LNK1, "BEND:IN10:661:BMAGX.HOPR")
  field(LNK2, "BEND:IN10:661:BMAGY.HOPR")
  field(LNK3, "BEND:IN10:661:BLEM.HOPR")
  field(LNK4, "BEND:IN10:661:BMAGX.LOPR PP")
  field(LNK5, "BEND:IN10:661:BMAGY.LOPR PP")
  field(LNK6, "BEND:IN10:661:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "BEND:IN10:661:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "BEND:IN10:661:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "BEND:IN10:661:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "BEND:IN10:661:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "BEND:IN10:661:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:IN10:661:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
  field(DOL,  "BEND:IN10:751:ECON CP MS")
  field(OMSL, "closed_loop")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:IN10:661:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
   field(DOL,  "BEND:IN10:751:EDES CP MS")
  field(OMSL, "closed_loop")
  field(FLNK, "BEND:IN10:661:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:IN10:661:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
   field(DOL,  "BEND:IN10:751:EACT CP MS")
  field(OMSL, "closed_loop")
  field(FLNK, "BEND:IN10:661:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "BEND:IN10:661:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "BEND:IN10:661:EDES NPP MS")
  field(INPB, "BEND:IN10:661:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "BEND:LI11:314:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI11:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI11:1:CTRL.RVAL")
  field(LNK1, "BEND:LI11:314:FUNC CA PP")
  field(DOL2, "MGNT:LI11:1:BENDCTRL.RVAL")
  field(LNK2, "BEND:LI11:314:FUNC CA PP")
  field(DOL3, "MGNT:LI11:1:BTRMCTRL.RVAL")
  field(LNK3, "BEND:LI11:314:FUNC CA PP")
  field(DOL4, "MGNT:LI11:1:LGPSCTRL.RVAL")
  field(LNK4, "BEND:LI11:314:FUNC CA PP")
  field(DOL5, "MGNT:LI11:1:QUADCTRL.RVAL")
  field(LNK5, "BEND:LI11:314:FUNC CA PP")
  field(DOL6, "MGNT:LI11:1:XCORCTRL.RVAL")
  field(LNK6, "BEND:LI11:314:FUNC CA PP")
  field(DOL7, "MGNT:LI11:1:YCORCTRL.RVAL")
  field(LNK7, "BEND:LI11:314:FUNC CA PP")
  field(DOL8, "MGNT:LI11:1:SOLNCTRL.RVAL")
  field(LNK8, "BEND:LI11:314:FUNC CA PP")
  field(DOL9, "MGNT:LI11:1:KICKCTRL.RVAL")
  field(LNK9, "BEND:LI11:314:FUNC CA PP")
  field(DOLA, "MGNT:LI11:1:SEXTCTRL.RVAL")
  field(LNKA, "BEND:LI11:314:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "BEND:LI11:314:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "BEND:LI11:314:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "BEND:LI11:314:EDES.PROC PP")
    field(LNK2, "BEND:LI11:314:EACT.PROC PP")
    field(LNK3, "BEND:LI11:314:EERR.DISA PP")
    field(LNK4, "BEND:LI11:314:ECON.PROC PP")
    field(LNK5, "BEND:LI11:314:BMAGX.PROC PP")
    field(LNK6, "BEND:LI11:314:BMAGY.PROC PP")
    field(LNK7, "BEND:LI11:314:BLEM.PROC PP")
    field(LNK8, "BEND:LI11:314:BMOD.PROC PP")
    field(LNK9, "BEND:LI11:314:EDESSAVE.PROC PP")
    field(LNKA, "BEND:LI11:314:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"BEND:LI11:314:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "BEND:LI11:314:BMAX")
  field(DOL2, "BEND:LI11:314:BMAX")
  field(DOL3, "BEND:LI11:314:BMAX")
  field(DOL4, "BEND:LI11:314:BMIN")
  field(DOL5, "BEND:LI11:314:BMIN")
  field(DOL6, "BEND:LI11:314:BMIN")
  field(LNK1, "BEND:LI11:314:BMAGX.HOPR")
  field(LNK2, "BEND:LI11:314:BMAGY.HOPR")
  field(LNK3, "BEND:LI11:314:BLEM.HOPR")
  field(LNK4, "BEND:LI11:314:BMAGX.LOPR PP")
  field(LNK5, "BEND:LI11:314:BMAGY.LOPR PP")
  field(LNK6, "BEND:LI11:314:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "BEND:LI11:314:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "BEND:LI11:314:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "BEND:LI11:314:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "BEND:LI11:314:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "BEND:LI11:314:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:LI11:314:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
  field(DOL,  "BEND:LI11:331:ECON CP MS")
  field(OMSL, "closed_loop")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:LI11:314:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
   field(DOL,  "BEND:LI11:331:EDES CP MS")
  field(OMSL, "closed_loop")
  field(FLNK, "BEND:LI11:314:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:LI11:314:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
   field(DOL,  "BEND:LI11:331:EACT CP MS")
  field(OMSL, "closed_loop")
  field(FLNK, "BEND:LI11:314:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "BEND:LI11:314:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "BEND:LI11:314:EDES NPP MS")
  field(INPB, "BEND:LI11:314:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "BEND:LI11:338:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI11:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI11:1:CTRL.RVAL")
  field(LNK1, "BEND:LI11:338:FUNC CA PP")
  field(DOL2, "MGNT:LI11:1:BENDCTRL.RVAL")
  field(LNK2, "BEND:LI11:338:FUNC CA PP")
  field(DOL3, "MGNT:LI11:1:BTRMCTRL.RVAL")
  field(LNK3, "BEND:LI11:338:FUNC CA PP")
  field(DOL4, "MGNT:LI11:1:LGPSCTRL.RVAL")
  field(LNK4, "BEND:LI11:338:FUNC CA PP")
  field(DOL5, "MGNT:LI11:1:QUADCTRL.RVAL")
  field(LNK5, "BEND:LI11:338:FUNC CA PP")
  field(DOL6, "MGNT:LI11:1:XCORCTRL.RVAL")
  field(LNK6, "BEND:LI11:338:FUNC CA PP")
  field(DOL7, "MGNT:LI11:1:YCORCTRL.RVAL")
  field(LNK7, "BEND:LI11:338:FUNC CA PP")
  field(DOL8, "MGNT:LI11:1:SOLNCTRL.RVAL")
  field(LNK8, "BEND:LI11:338:FUNC CA PP")
  field(DOL9, "MGNT:LI11:1:KICKCTRL.RVAL")
  field(LNK9, "BEND:LI11:338:FUNC CA PP")
  field(DOLA, "MGNT:LI11:1:SEXTCTRL.RVAL")
  field(LNKA, "BEND:LI11:338:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "BEND:LI11:338:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "BEND:LI11:338:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "BEND:LI11:338:EDES.PROC PP")
    field(LNK2, "BEND:LI11:338:EACT.PROC PP")
    field(LNK3, "BEND:LI11:338:EERR.DISA PP")
    field(LNK4, "BEND:LI11:338:ECON.PROC PP")
    field(LNK5, "BEND:LI11:338:BMAGX.PROC PP")
    field(LNK6, "BEND:LI11:338:BMAGY.PROC PP")
    field(LNK7, "BEND:LI11:338:BLEM.PROC PP")
    field(LNK8, "BEND:LI11:338:BMOD.PROC PP")
    field(LNK9, "BEND:LI11:338:EDESSAVE.PROC PP")
    field(LNKA, "BEND:LI11:338:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"BEND:LI11:338:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "BEND:LI11:338:BMAX")
  field(DOL2, "BEND:LI11:338:BMAX")
  field(DOL3, "BEND:LI11:338:BMAX")
  field(DOL4, "BEND:LI11:338:BMIN")
  field(DOL5, "BEND:LI11:338:BMIN")
  field(DOL6, "BEND:LI11:338:BMIN")
  field(LNK1, "BEND:LI11:338:BMAGX.HOPR")
  field(LNK2, "BEND:LI11:338:BMAGY.HOPR")
  field(LNK3, "BEND:LI11:338:BLEM.HOPR")
  field(LNK4, "BEND:LI11:338:BMAGX.LOPR PP")
  field(LNK5, "BEND:LI11:338:BMAGY.LOPR PP")
  field(LNK6, "BEND:LI11:338:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "BEND:LI11:338:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "BEND:LI11:338:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "BEND:LI11:338:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "BEND:LI11:338:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "BEND:LI11:338:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:LI11:338:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
  field(DOL,  "BEND:LI11:331:ECON CP MS")
  field(OMSL, "closed_loop")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:LI11:338:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
   field(DOL,  "BEND:LI11:331:EDES CP MS")
  field(OMSL, "closed_loop")
  field(FLNK, "BEND:LI11:338:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:LI11:338:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
   field(DOL,  "BEND:LI11:331:EACT CP MS")
  field(OMSL, "closed_loop")
  field(FLNK, "BEND:LI11:338:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "BEND:LI11:338:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "BEND:LI11:338:EDES NPP MS")
  field(INPB, "BEND:LI11:338:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "BEND:LI11:355:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI11:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI11:1:CTRL.RVAL")
  field(LNK1, "BEND:LI11:355:FUNC CA PP")
  field(DOL2, "MGNT:LI11:1:BENDCTRL.RVAL")
  field(LNK2, "BEND:LI11:355:FUNC CA PP")
  field(DOL3, "MGNT:LI11:1:BTRMCTRL.RVAL")
  field(LNK3, "BEND:LI11:355:FUNC CA PP")
  field(DOL4, "MGNT:LI11:1:LGPSCTRL.RVAL")
  field(LNK4, "BEND:LI11:355:FUNC CA PP")
  field(DOL5, "MGNT:LI11:1:QUADCTRL.RVAL")
  field(LNK5, "BEND:LI11:355:FUNC CA PP")
  field(DOL6, "MGNT:LI11:1:XCORCTRL.RVAL")
  field(LNK6, "BEND:LI11:355:FUNC CA PP")
  field(DOL7, "MGNT:LI11:1:YCORCTRL.RVAL")
  field(LNK7, "BEND:LI11:355:FUNC CA PP")
  field(DOL8, "MGNT:LI11:1:SOLNCTRL.RVAL")
  field(LNK8, "BEND:LI11:355:FUNC CA PP")
  field(DOL9, "MGNT:LI11:1:KICKCTRL.RVAL")
  field(LNK9, "BEND:LI11:355:FUNC CA PP")
  field(DOLA, "MGNT:LI11:1:SEXTCTRL.RVAL")
  field(LNKA, "BEND:LI11:355:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "BEND:LI11:355:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "BEND:LI11:355:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "BEND:LI11:355:EDES.PROC PP")
    field(LNK2, "BEND:LI11:355:EACT.PROC PP")
    field(LNK3, "BEND:LI11:355:EERR.DISA PP")
    field(LNK4, "BEND:LI11:355:ECON.PROC PP")
    field(LNK5, "BEND:LI11:355:BMAGX.PROC PP")
    field(LNK6, "BEND:LI11:355:BMAGY.PROC PP")
    field(LNK7, "BEND:LI11:355:BLEM.PROC PP")
    field(LNK8, "BEND:LI11:355:BMOD.PROC PP")
    field(LNK9, "BEND:LI11:355:EDESSAVE.PROC PP")
    field(LNKA, "BEND:LI11:355:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"BEND:LI11:355:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "BEND:LI11:355:BMAX")
  field(DOL2, "BEND:LI11:355:BMAX")
  field(DOL3, "BEND:LI11:355:BMAX")
  field(DOL4, "BEND:LI11:355:BMIN")
  field(DOL5, "BEND:LI11:355:BMIN")
  field(DOL6, "BEND:LI11:355:BMIN")
  field(LNK1, "BEND:LI11:355:BMAGX.HOPR")
  field(LNK2, "BEND:LI11:355:BMAGY.HOPR")
  field(LNK3, "BEND:LI11:355:BLEM.HOPR")
  field(LNK4, "BEND:LI11:355:BMAGX.LOPR PP")
  field(LNK5, "BEND:LI11:355:BMAGY.LOPR PP")
  field(LNK6, "BEND:LI11:355:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "BEND:LI11:355:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "BEND:LI11:355:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "BEND:LI11:355:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "BEND:LI11:355:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "BEND:LI11:355:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:LI11:355:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
  field(DOL,  "BEND:LI11:331:ECON CP MS")
  field(OMSL, "closed_loop")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:LI11:355:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
   field(DOL,  "BEND:LI11:331:EDES CP MS")
  field(OMSL, "closed_loop")
  field(FLNK, "BEND:LI11:355:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:LI11:355:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
   field(DOL,  "BEND:LI11:331:EACT CP MS")
  field(OMSL, "closed_loop")
  field(FLNK, "BEND:LI11:355:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "BEND:LI11:355:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "BEND:LI11:355:EDES NPP MS")
  field(INPB, "BEND:LI11:355:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "BEND:LI14:720:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI14:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI14:1:CTRL.RVAL")
  field(LNK1, "BEND:LI14:720:FUNC CA PP")
  field(DOL2, "MGNT:LI14:1:BENDCTRL.RVAL")
  field(LNK2, "BEND:LI14:720:FUNC CA PP")
  field(DOL3, "MGNT:LI14:1:BTRMCTRL.RVAL")
  field(LNK3, "BEND:LI14:720:FUNC CA PP")
  field(DOL4, "MGNT:LI14:1:LGPSCTRL.RVAL")
  field(LNK4, "BEND:LI14:720:FUNC CA PP")
  field(DOL5, "MGNT:LI14:1:QUADCTRL.RVAL")
  field(LNK5, "BEND:LI14:720:FUNC CA PP")
  field(DOL6, "MGNT:LI14:1:XCORCTRL.RVAL")
  field(LNK6, "BEND:LI14:720:FUNC CA PP")
  field(DOL7, "MGNT:LI14:1:YCORCTRL.RVAL")
  field(LNK7, "BEND:LI14:720:FUNC CA PP")
  field(DOL8, "MGNT:LI14:1:SOLNCTRL.RVAL")
  field(LNK8, "BEND:LI14:720:FUNC CA PP")
  field(DOL9, "MGNT:LI14:1:KICKCTRL.RVAL")
  field(LNK9, "BEND:LI14:720:FUNC CA PP")
  field(DOLA, "MGNT:LI14:1:SEXTCTRL.RVAL")
  field(LNKA, "BEND:LI14:720:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "BEND:LI14:720:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "BEND:LI14:720:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "BEND:LI14:720:EDES.PROC PP")
    field(LNK2, "BEND:LI14:720:EACT.PROC PP")
    field(LNK3, "BEND:LI14:720:EERR.DISA PP")
    field(LNK4, "BEND:LI14:720:ECON.PROC PP")
    field(LNK5, "BEND:LI14:720:BMAGX.PROC PP")
    field(LNK6, "BEND:LI14:720:BMAGY.PROC PP")
    field(LNK7, "BEND:LI14:720:BLEM.PROC PP")
    field(LNK8, "BEND:LI14:720:BMOD.PROC PP")
    field(LNK9, "BEND:LI14:720:EDESSAVE.PROC PP")
    field(LNKA, "BEND:LI14:720:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"BEND:LI14:720:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "BEND:LI14:720:BMAX")
  field(DOL2, "BEND:LI14:720:BMAX")
  field(DOL3, "BEND:LI14:720:BMAX")
  field(DOL4, "BEND:LI14:720:BMIN")
  field(DOL5, "BEND:LI14:720:BMIN")
  field(DOL6, "BEND:LI14:720:BMIN")
  field(LNK1, "BEND:LI14:720:BMAGX.HOPR")
  field(LNK2, "BEND:LI14:720:BMAGY.HOPR")
  field(LNK3, "BEND:LI14:720:BLEM.HOPR")
  field(LNK4, "BEND:LI14:720:BMAGX.LOPR PP")
  field(LNK5, "BEND:LI14:720:BMAGY.LOPR PP")
  field(LNK6, "BEND:LI14:720:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "BEND:LI14:720:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "BEND:LI14:720:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "BEND:LI14:720:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "BEND:LI14:720:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "BEND:LI14:720:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:LI14:720:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
  field(DOL,  "BEND:LI14:796:ECON CP MS")
  field(OMSL, "closed_loop")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:LI14:720:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
   field(DOL,  "BEND:LI14:796:EDES CP MS")
  field(OMSL, "closed_loop")
  field(FLNK, "BEND:LI14:720:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:LI14:720:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
   field(DOL,  "BEND:LI14:796:EACT CP MS")
  field(OMSL, "closed_loop")
  field(FLNK, "BEND:LI14:720:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "BEND:LI14:720:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "BEND:LI14:720:EDES NPP MS")
  field(INPB, "BEND:LI14:720:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "BEND:LI14:808:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI14:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI14:1:CTRL.RVAL")
  field(LNK1, "BEND:LI14:808:FUNC CA PP")
  field(DOL2, "MGNT:LI14:1:BENDCTRL.RVAL")
  field(LNK2, "BEND:LI14:808:FUNC CA PP")
  field(DOL3, "MGNT:LI14:1:BTRMCTRL.RVAL")
  field(LNK3, "BEND:LI14:808:FUNC CA PP")
  field(DOL4, "MGNT:LI14:1:LGPSCTRL.RVAL")
  field(LNK4, "BEND:LI14:808:FUNC CA PP")
  field(DOL5, "MGNT:LI14:1:QUADCTRL.RVAL")
  field(LNK5, "BEND:LI14:808:FUNC CA PP")
  field(DOL6, "MGNT:LI14:1:XCORCTRL.RVAL")
  field(LNK6, "BEND:LI14:808:FUNC CA PP")
  field(DOL7, "MGNT:LI14:1:YCORCTRL.RVAL")
  field(LNK7, "BEND:LI14:808:FUNC CA PP")
  field(DOL8, "MGNT:LI14:1:SOLNCTRL.RVAL")
  field(LNK8, "BEND:LI14:808:FUNC CA PP")
  field(DOL9, "MGNT:LI14:1:KICKCTRL.RVAL")
  field(LNK9, "BEND:LI14:808:FUNC CA PP")
  field(DOLA, "MGNT:LI14:1:SEXTCTRL.RVAL")
  field(LNKA, "BEND:LI14:808:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "BEND:LI14:808:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "BEND:LI14:808:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "BEND:LI14:808:EDES.PROC PP")
    field(LNK2, "BEND:LI14:808:EACT.PROC PP")
    field(LNK3, "BEND:LI14:808:EERR.DISA PP")
    field(LNK4, "BEND:LI14:808:ECON.PROC PP")
    field(LNK5, "BEND:LI14:808:BMAGX.PROC PP")
    field(LNK6, "BEND:LI14:808:BMAGY.PROC PP")
    field(LNK7, "BEND:LI14:808:BLEM.PROC PP")
    field(LNK8, "BEND:LI14:808:BMOD.PROC PP")
    field(LNK9, "BEND:LI14:808:EDESSAVE.PROC PP")
    field(LNKA, "BEND:LI14:808:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"BEND:LI14:808:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "BEND:LI14:808:BMAX")
  field(DOL2, "BEND:LI14:808:BMAX")
  field(DOL3, "BEND:LI14:808:BMAX")
  field(DOL4, "BEND:LI14:808:BMIN")
  field(DOL5, "BEND:LI14:808:BMIN")
  field(DOL6, "BEND:LI14:808:BMIN")
  field(LNK1, "BEND:LI14:808:BMAGX.HOPR")
  field(LNK2, "BEND:LI14:808:BMAGY.HOPR")
  field(LNK3, "BEND:LI14:808:BLEM.HOPR")
  field(LNK4, "BEND:LI14:808:BMAGX.LOPR PP")
  field(LNK5, "BEND:LI14:808:BMAGY.LOPR PP")
  field(LNK6, "BEND:LI14:808:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "BEND:LI14:808:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "BEND:LI14:808:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "BEND:LI14:808:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "BEND:LI14:808:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "BEND:LI14:808:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:LI14:808:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
  field(DOL,  "BEND:LI14:796:ECON CP MS")
  field(OMSL, "closed_loop")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:LI14:808:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
   field(DOL,  "BEND:LI14:796:EDES CP MS")
  field(OMSL, "closed_loop")
  field(FLNK, "BEND:LI14:808:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:LI14:808:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
   field(DOL,  "BEND:LI14:796:EACT CP MS")
  field(OMSL, "closed_loop")
  field(FLNK, "BEND:LI14:808:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "BEND:LI14:808:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "BEND:LI14:808:EDES NPP MS")
  field(INPB, "BEND:LI14:808:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "BEND:LI14:883:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:LI14:1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:LI14:1:CTRL.RVAL")
  field(LNK1, "BEND:LI14:883:FUNC CA PP")
  field(DOL2, "MGNT:LI14:1:BENDCTRL.RVAL")
  field(LNK2, "BEND:LI14:883:FUNC CA PP")
  field(DOL3, "MGNT:LI14:1:BTRMCTRL.RVAL")
  field(LNK3, "BEND:LI14:883:FUNC CA PP")
  field(DOL4, "MGNT:LI14:1:LGPSCTRL.RVAL")
  field(LNK4, "BEND:LI14:883:FUNC CA PP")
  field(DOL5, "MGNT:LI14:1:QUADCTRL.RVAL")
  field(LNK5, "BEND:LI14:883:FUNC CA PP")
  field(DOL6, "MGNT:LI14:1:XCORCTRL.RVAL")
  field(LNK6, "BEND:LI14:883:FUNC CA PP")
  field(DOL7, "MGNT:LI14:1:YCORCTRL.RVAL")
  field(LNK7, "BEND:LI14:883:FUNC CA PP")
  field(DOL8, "MGNT:LI14:1:SOLNCTRL.RVAL")
  field(LNK8, "BEND:LI14:883:FUNC CA PP")
  field(DOL9, "MGNT:LI14:1:KICKCTRL.RVAL")
  field(LNK9, "BEND:LI14:883:FUNC CA PP")
  field(DOLA, "MGNT:LI14:1:SEXTCTRL.RVAL")
  field(LNKA, "BEND:LI14:883:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "BEND:LI14:883:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "BEND:LI14:883:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "BEND:LI14:883:EDES.PROC PP")
    field(LNK2, "BEND:LI14:883:EACT.PROC PP")
    field(LNK3, "BEND:LI14:883:EERR.DISA PP")
    field(LNK4, "BEND:LI14:883:ECON.PROC PP")
    field(LNK5, "BEND:LI14:883:BMAGX.PROC PP")
    field(LNK6, "BEND:LI14:883:BMAGY.PROC PP")
    field(LNK7, "BEND:LI14:883:BLEM.PROC PP")
    field(LNK8, "BEND:LI14:883:BMOD.PROC PP")
    field(LNK9, "BEND:LI14:883:EDESSAVE.PROC PP")
    field(LNKA, "BEND:LI14:883:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"BEND:LI14:883:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "BEND:LI14:883:BMAX")
  field(DOL2, "BEND:LI14:883:BMAX")
  field(DOL3, "BEND:LI14:883:BMAX")
  field(DOL4, "BEND:LI14:883:BMIN")
  field(DOL5, "BEND:LI14:883:BMIN")
  field(DOL6, "BEND:LI14:883:BMIN")
  field(LNK1, "BEND:LI14:883:BMAGX.HOPR")
  field(LNK2, "BEND:LI14:883:BMAGY.HOPR")
  field(LNK3, "BEND:LI14:883:BLEM.HOPR")
  field(LNK4, "BEND:LI14:883:BMAGX.LOPR PP")
  field(LNK5, "BEND:LI14:883:BMAGY.LOPR PP")
  field(LNK6, "BEND:LI14:883:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "BEND:LI14:883:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "BEND:LI14:883:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "BEND:LI14:883:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "BEND:LI14:883:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "BEND:LI14:883:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:LI14:883:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
  field(DOL,  "BEND:LI14:796:ECON CP MS")
  field(OMSL, "closed_loop")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:LI14:883:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
   field(DOL,  "BEND:LI14:796:EDES CP MS")
  field(OMSL, "closed_loop")
  field(FLNK, "BEND:LI14:883:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "BEND:LI14:883:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
   field(DOL,  "BEND:LI14:796:EACT CP MS")
  field(OMSL, "closed_loop")
  field(FLNK, "BEND:LI14:883:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "BEND:LI14:883:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "BEND:LI14:883:EDES NPP MS")
  field(INPB, "BEND:LI14:883:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}