#! DBDSTART #! DBD("../../../dbd/mgntSoft.dbd") #! DBDEND # This database is used for MCOR PLCs # If the magnet is cooled by water then # consider interlock status for D,E,F # the value must be either 0 or a zero. record(calc, "$(PS):INTLKSUMYAIR") { field(DESC, "Air Cooled Mag Intlks") field(SCAN, "1 second") field(CALC, "A|B|C?1:0") field(INPA, "$(PS):IGNDSTATE.SEVR NPP MS") field(INPB, "$(PS):VOVERSTATE.SEVR NPP MS") field(INPC, "$(PS):VUNDERSTATE.SEVR NPP MS") field(FLNK, "$(PS):INTLKSUMYH20") field(ASG, "Internal") } record(calc, "$(PS):INTLKSUMYH20") { field(DESC, "Water Cooled Mag Intlks") field(SCAN, "Passive") field(CALC, "A|B|C|D|E|F?1:0") field(INPA, "$(PS):IGNDSTATE.SEVR NPP MS") field(INPB, "$(PS):VOVERSTATE.SEVR NPP MS") field(INPC, "$(PS):VUNDERSTATE.SEVR NPP MS") field(INPD, "$(PLCPV):THERMSWSTATE.SEVR NPP MS") field(INPE, "$(PLCPV):FLOWSWSTATE.SEVR NPP MS") field(INPF, "$(PLCPV):FLOWSW2STATE.SEVR NPP MS") field(FLNK, "$(PS):INTLKSUMYCALC") field(ASG, "Internal") } record(calc, "$(PS):INTLKSUMYCALC") { field(DESC, "Interlock Summary") field(SCAN, "Passive") field(CALC, "A?1:0") field(INPA, "$(PS):INTLKSUMYAIR") field(INPB, "$(PS):INTLKSUMYH20") field(INPC, "$(PS):COOLING") field(FLNK, "$(PS):INTLKSUMY") field(ASG, "Internal") } record(bi, "$(PS):INTLKSUMY") { field(DESC, "Interlock Summary") field(DTYP, "Raw Soft Channel") field(ZNAM, "OK") field(ONAM, "FAULT") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") field(INP, "$(PS):INTLKSUMYCALC") field(FLNK, "$(MDEV1)INTLKSUMY$(G)") info(autosaveFields,"RVAL") } record(bo, "$(PS):RESET") { field(DESC, "Interlock Latch Reset") field(DTYP, "Raw Soft Channel") field(ZNAM, "NORESET") field(ONAM, "RESET") field(OUT, "$(PLCPV):RESETCALC.A PP") } record(bo, "$(PS):COOLING") { field(DESC, "Type of cooling") field(OUT, " $(MDEV1)COOLING$(G) PP") field(ZNAM, "AIR") field(ONAM, "WATER") field(PINI, "YES") } #! Generated by VisualDCT v2.5 #! DBDSTART #! DBDEND #! DBD("../../../dbd/mgntSoft.dbd") record(bi, "$(PS):IGNDSTATE") { field(DESC, "Ground Fault Status") field(SCAN, "1 second") field(DTYP, "EtherIP") field(INP, "@$(NODE) STATUS_BITS[$(NUM)] B 0 S 1") field(ZNAM, "OK") field(ONAM, "FAULT") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") field(FLNK, "") info(autosaveFields,"RVAL") } #! Generated by VisualDCT v2.5 #! DBDSTART #! DBDEND #! DBD("../../../dbd/mgntSoft.dbd") record(bi, "$(PS):VOVERSTATE") { field(DESC, "Over Voltage Fault") field(SCAN, "1 second") field(DTYP, "EtherIP") field(INP, "@$(NODE) STATUS_BITS[$(NUM)] B 1 S 1") field(ZNAM, "OK") field(ONAM, "FAULT") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") field(FLNK, "") info(autosaveFields,"RVAL") } #! Generated by VisualDCT v2.5 #! DBDSTART #! DBDEND #! DBD("../../../dbd/mgntSoft.dbd") record(bi, "$(PS):VUNDERSTATE") { field(DESC, "Under Voltage Fault") field(SCAN, "1 second") field(DTYP, "EtherIP") field(INP, "@$(NODE) STATUS_BITS[$(NUM)] B 2 S 1") field(ZNAM, "OK") field(ONAM, "FAULT") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") field(FLNK, "") info(autosaveFields,"RVAL") } #! Generated by VisualDCT v2.5 #! DBDSTART #! DBDEND #! DBD("../../../dbd/mgntSoft.dbd") record(bi, "$(PS):STATE") { field(DESC, "PS On/Off Status") field(SCAN, "1 second") field(DTYP, "EtherIP") field(INP, "@$(NODE) STATUS_BITS[$(NUM)] B 3 S 1") field(ZNAM, "OFF") field(ONAM, "ON") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(FLNK, "$(MDEV1)STATE$(G)") info(autosaveFields,"RVAL") } #! Generated by VisualDCT v2.5 #! DBDSTART #! DBDEND #! DBD("../../../dbd/mgntSoft.dbd") record(bi, "$(PS):MODE") { field(DESC, "Local/Remote Ctrl") field(SCAN, "1 second") field(DTYP, "EtherIP") field(INP, "@$(NODE) STATUS_BITS[$(NUM)] B 4 S 1") field(ZNAM, "LOCAL") field(ONAM, "REMOTE") field(ZSV, "MINOR") field(OSV, "NO_ALARM") field(FLNK, "") info(autosaveFields,"RVAL") } #! Generated by VisualDCT v2.5 #! DBDSTART #! DBDEND #! DBD("../../../dbd/mgntSoft.dbd") record(bi, "$(PS):RAMPSTATE") { field(DESC, "PS Ramp Status") field(SCAN, "1 second") field(DTYP, "EtherIP") field(INP, "@$(NODE) STATUS_BITS[$(NUM)] B 5 S 1") field(ZNAM, "IDLE") field(ONAM, "RAMPING") field(ZSV, "NO_ALARM") field(OSV, "MINOR") field(FLNK, "$(MDEV1)RAMPSTATE$(G)") info(autosaveFields,"RVAL") } #! Generated by VisualDCT v2.5 #! DBDSTART #! DBDEND #! DBD("../../../dbd/mgntSoft.dbd") record(bo, "$(PS):STATESETPT") { field(DESC, "PS On/Off Control") field(DTYP, "EtherIP") field(OUT, "@$(NODE) REMOTE_CONTROL[$(NUM)] B 1 S 1") field(ZNAM, "OFF") field(ONAM, "ON") field(PINI, "NO") info(autosaveFields,"VAL") } #! Generated by VisualDCT v2.5 #! DBDSTART #! DBD("../../../dbd/mgntSoft.dbd") #! DBDEND record(ai, "$(PS):IGNDRAW") { field(DESC, "Ground Current") field(DTYP, "EtherIP") field(SCAN, "1 second") field(INP, "@$(NODE) FLOATING_VALUES[3$(NUM)] S 1") field(EGU, "mA") field(PREC, "6") field(LINR, "NO CONVERSION") field(HOPR, "12.5") field(LOPR, "0.0") field(HIHI, "20.0") field(HIGH, "25.0") field(FLNK, "$(PS):IGNDULIM") } record(calcout, "$(PS):IGNDULIM") { field(DESC, "Gnd Current Alarm") field(CALC, "(D&&E)&&(H=0)?MAX(A,D*B):F+1") field(EGU, "mA") field(PREC, "6") field(INPA, "1") field(INPB, "0.0001") field(INPD, "$(PS):IACT NPP NMS") field(INPE, "$(PS):STATE NPP NMS") field(INPF, "$(PS):IGND.HOPR NPP NMS") # If H=1 then alarms are disabled. field(INPH, "0") field(OUT, "$(PS):IGND.HIGH PP") } record(calc, "$(PS):IGND") { field(DESC, "Scaled Ground Current") field(CALC, "A*B") field(INPA, "$(PS):IGNDRAW") field(INPB, "$(S2)") field(PREC, "6") field(EGU, "mA") field(HOPR, "12.5") field(HSV, "MINOR") field(FLNK, "$(MDEV1)IGND PP MS") } record(calc, "$(PS):VINP") { field(DESC, "Scaled Input Voltage") field(CALC, "A*B") field(INPA, "$(PS):VINPRAW") field(INPB, "$(S1)") field(PREC, "6") field(HOPR, "$(VMAX)") field(LOPR, "0.0") field(EGU, "V") } record(ai, "$(PS):VINPRAW") { field(DESC, "Input Voltage") field(SCAN, "1 second") field(DTYP, "EtherIP") field(INP, "@$(NODE) FLOATING_VALUES[$(NUM)] S 1") field(EGU, "V") field(HOPR, "$(VMAX)") field(LOPR, "0.0") field(PREC, "6") field(ADEL, "0.10") field(MDEL, "0.01") field(LINR, "NO CONVERSION") } record(calc, "$(PS):VACT") { field(DESC, "Scaled Voltage Readback") field(CALC, "A*B") field(INPA, "$(PS):VACTRAW") field(INPB, "$(S1)") field(PREC, "6") field(HOPR, "$(VMAX)") field(LOPR, "0.0") field(EGU, "V") field(FLNK, "$(PS):IACT") } record(ai, "$(PS):VACTRAW") { field(DESC, "Voltage Readback") field(SCAN, "1 second") field(DTYP, "EtherIP") field(INP, "@$(NODE) FLOATING_VALUES[2$(NUM)] S 1") field(PREC, "3") field(EGU, "V") field(HOPR, "$(VMAX)") field(LOPR, "0.0") field(FLNK, "$(PS):VACT") } record(ai, "$(PS):IACT") { field(DESC, "Actual Current") field(DTYP, "Soft Channel") field(INP, "$(PS):VACT") field(PREC, "3") field(LINR, "NO CONVERSION") field(ADEL, "0.10") field(MDEL, "0.01") field(HOPR, "$(VMAX)") field(LOPR, "0.0") field(EGU, "A") field(FLNK, "$(MDEV1)IACT") } record(ao, "$(PS):ISETPT") { field(DESC, "Current Setpoint") field(DTYP, "Soft Channel") field(OUT, "$(PS):VSETPT PP MS") field(PREC, "6") field(LINR, "NO CONVERSION") field(EGU, "A") field(DRVH, "$(VMAX)") field(HOPR, "$(VMAX)") } record(ao, "$(PS):VSETPT") { field(DESC, "Voltage Setpoint") field(DTYP, "Soft Channel") field(PREC, "3") field(LINR, "NO CONVERSION") field(EGU, "V") field(DRVH, "$(VMAX)") field(HOPR, "$(VMAX)") } #! Further lines contain data used by VisualDCT #! View(221,27,0.6) #! Record("$(PS):IGNDRAW",380,1052,0,0,"$(PS):IGNDRAW") #! Field("$(PS):IGNDRAW.FLNK",16777215,1,"$(PS):IGNDRAW.FLNK") #! Link("$(PS):IGNDRAW.FLNK","$(PS):IGND") #! Field("$(PS):IGNDRAW.VAL",16777215,1,"$(PS):IGNDRAW.VAL") #! Record("$(PS):IGND",660,1120,0,0,"$(PS):IGND") #! Field("$(PS):IGND.INPA",16777215,0,"$(PS):IGND.INPA") #! Link("$(PS):IGND.INPA","$(PS):IGNDRAW.VAL") #! Field("$(PS):IGND.INPB",16777215,1,"$(PS):IGND.INPB") #! Record("$(PS):VINP",800,749,0,0,"$(PS):VINP") #! Field("$(PS):VINP.INPA",16777215,0,"$(PS):VINP.INPA") #! Link("$(PS):VINP.INPA","$(PS):VINPRAW.VAL") #! Field("$(PS):VINP.INPB",16777215,1,"$(PS):VINP.INPB") #! Record("$(PS):VINPRAW",440,707,0,0,"$(PS):VINPRAW") #! Field("$(PS):VINPRAW.VAL",16777215,1,"$(PS):VINPRAW.VAL") #! Record("$(PS):VACT",1160,615,0,0,"$(PS):VACT") #! Field("$(PS):VACT.INPA",16777215,1,"$(PS):VACT.INPA") #! Link("$(PS):VACT.INPA","$(PS):VACTRAW.VAL") #! Field("$(PS):VACT.INPB",16777215,1,"$(PS):VACT.INPB") #! Field("$(PS):VACT.FLNK",16777215,0,"$(PS):VACT.FLNK") #! Link("$(PS):VACT.FLNK","$(PS):IACT") #! Field("$(PS):VACT.VAL",16777215,0,"$(PS):VACT.VAL") #! Record("$(PS):VACTRAW",1180,295,0,0,"$(PS):VACTRAW") #! Field("$(PS):VACTRAW.VAL",16777215,1,"$(PS):VACTRAW.VAL") #! Field("$(PS):VACTRAW.FLNK",16777215,0,"$(PS):VACTRAW.FLNK") #! Link("$(PS):VACTRAW.FLNK","$(PS):VACT") #! Record("$(PS):IACT",1180,927,0,0,"$(PS):IACT") #! Field("$(PS):IACT.INP",16777215,0,"$(PS):IACT.INP") #! Link("$(PS):IACT.INP","$(PS):VACT.VAL") #! Field("$(PS):IACT.FLNK",16777215,1,"$(PS):IACT.FLNK") #! Record("$(PS):VSETPT",1640,595,0,0,"$(PS):VSETPT") #! Record("$(PS):ISETPT",1660,220,0,0,"$(PS):ISETPT") #! Field("$(PS):ISETPT.FLNK",16777215,0,"$(PS):ISETPT.FLNK") #! Link("$(PS):ISETPT.FLNK","$(PS):VSETPT") record(calcout, "$(PS):StateCheck") { # Do nothing if the state is invalid. # If the state setpoint is invalid, then set state setpoint to state. # If the state and setpoint are the same, set off if state is off, # otherwise, set state setpoint to state. # If the state setpoint has changed, go on or off. Otherwise, the state # must've changed externally so follow it. # field(DESC, "PS State Check") field(CALC, "C=3?0:D=3?3:(A#B)&&(B#E)?B+1:A=0?1:3") field(OUT, "$(PS):StateSeq.SELN PP") field(INPA, "$(PS):STATE CPP") field(INPB, "$(PS):STATESETPT CPP") field(INPC, "$(PS):STATE.SEVR") field(INPD, "$(PS):STATESETPT.SEVR") field(INPE, "$(PS):StateCheck.LB") field(ASG, "Internal") } record(seq, "$(PS):StateSeq") { field(DESC, "PS State Sequence") field(SELM, "Specified") field(LNK1, "$(PS):StateOffSetptSeq.PROC PP") field(LNK2, "$(PS):StateOnSetptSeq.PROC PP") field(DOL3, "$(PS):STATE") field(LNK3, "$(PS):StateSetptSeq PP") field(ASG, "Internal") } record(seq, "$(PS):StateOnSetptSeq") { # When turning on, reset the power supply, then # enable foldback protection, set the voltage to and current max, # and delay to let the currrent reach set point, # and set state to 1 (on). # field(DESC, "PS On Sequence") field(DOL1, "1") field(LNK1, "$(MDEV1)RESET PP") field(DOL2, "$(MDEV1)BCTRL.HOPR") field(LNK2, "$(MDEV1)BDES PP") field(DOL3, "$(MDEV1)BCTRL.HOPR") field(LNK3, "$(MDEV1)BCTRL PP") field(DLY4, "0.2") field(DOL4, "1") field(LNK4, "$(PS):StateSetptSeq PP") field(ASG, "Internal") } record(seq, "$(PS):StateOffSetptSeq") { # When turning off, set the current voltage to max, and delay to let the # current and voltage reach the set point, and set state to 0 (off). # Note: Under normal circumstances you'd set the current and volts to 0 # before turning off the supply, but power conversion wants to leave the # curren and volt set before turning off. field(DESC, "PS Off Sequence") field(LNK1, "$(MDEV1)ISETPT PP") field(DLY1, "0.2") field(LNK2, "$(PS):StateSetptSeq PP") field(DOL3, "$(MDEV1)BCTRL.HOPR") field(LNK3, "$(MDEV1)BDES PP") field(DOL4, "$(MDEV1)BCTRL.HOPR") field(LNK4, "$(MDEV1)BCTRL PP") field(ASG, "Internal") } record(seq, "$(PS):StateSetptSeq") { # Set both the desired and the actual setpoints to requested. # Renable status events in case of power-cycle. field(DESC, "PS State Setpt Sequence") field(DOL1, "$(PS):StateSetptSeq") field(LNK1, "$(MDEV1)STATESETPT PP") field(ASG, "Internal") } #! Generated by VisualDCT v2.5 #! DBDSTART #! DBD("../../../dbd/mgntSoft.dbd") #! DBDEND # Generic information record(stringout, "$(PS):LOCATION") { field(DESC, "Rack Location") field(PINI, "YES") field(DTYP, "Soft Channel") field(VAL, "B136-3031") } record(stringout, "$(PS):DRAWING") { field(DESC, "SODA Drawing No.") field(PINI, "YES") field(DTYP, "Soft Channel") field(VAL, "PR-376-531-00") } record(bo, "$(PS):RAMPSTATE") { field(DESC, "PS ramp status") field(OUT, "$(MDEV1)RAMPSTATE PP") field(ZNAM, "OFF") field(ONAM, "BUSY") field(PINI, "YES") field(VAL, "0") } record(mbbo, "$(PS):COOLING") { field(DESC, "Type of cooling") field(NOBT, "2") field(ZRST, "AIR") field(ONST, "WATER") field(TWST, "HELIUM") field(THST, "NONE") field(ZRVL, "0") field(ONVL, "1") field(TWVL, "2") field(THVL, "3") field(PINI, "YES") field(OUT, "$(MDEV1)COOLING PP") field(VAL, "3") }