#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(longout, "MGNT:$(LOCA):1:CTRLSWITCH") {
}

# The LNK# (1-8) MUST corresponsds to the magent
# type definition found in the file mgntCtrl.h.
# For example, MGNT_TYPE_BEND is defined as 2 and is LNK2 below.
# If the LNK order is changes you will need to make the
# corresponding change the pv <device>:<type>CTRL which is
# found in the files mgnt_ctrl_allstar.substitutions
# The field FFVL value in MGNT:<LOCA>:1: CTRLCLEAR MUST be set
# to the value for MGNT_TYPE_ALL which is defined as 1 in mgntCtrl.h
# so that it can be used properly by the the PV  MGNT:LI21:1:ALLSWITCH
#
record(seq, "MGNT:$(LOCA):1:CTRLCLEAR") {
  field(DESC, "All function go")
  field(DOL1, "0")
  field(DOL2, "0")
  field(DOL3, "0")
  field(DOL4, "0")
  field(DOL5, "0")
  field(DOL6, "0")
  field(DOL7, "0")
  field(DOL8, "0")
  field(DOL9, "0")
  field(DOLA, "0")
  field(LNK1, "MGNT:$(LOCA):1:CTRL CA PP")
  field(LNK2, "MGNT:$(LOCA):1:BENDCTRL CA PP")
  field(LNK3, "MGNT:$(LOCA):1:BTRMCTRL CA PP")
  field(LNK4, "MGNT:$(LOCA):1:LGPSCTRL CA PP")
  field(LNK5, "MGNT:$(LOCA):1:QUADCTRL CA PP")
  field(LNK6, "MGNT:$(LOCA):1:XCORCTRL CA PP")
  field(LNK7, "MGNT:$(LOCA):1:YCORCTRL CA PP")
  field(LNK8, "MGNT:$(LOCA):1:SOLNCTRL CA PP")
  field(LNK9, "MGNT:$(LOCA):1:KICKCTRL CA PP")
  field(LNKA, "MGNT:$(LOCA):1:SEXTCTRL CA PP")
}

record(mbbo, "MGNT:$(LOCA):1:CTRL") {
  field(DESC, "All Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "1")
  field(FLNK, "MGNT:$(LOCA):1:ALLSWITCH")
}

record(seq, "MGNT:$(LOCA):1:ALLSWITCH") {
  field(DOL1, "MGNT:$(LOCA):1:CTRL.FFVL")
  field(LNK1, "MGNT:$(LOCA):1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:$(LOCA):1:ALLFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:$(LOCA):1:CTRL")
}

record(bo, "MGNT:$(LOCA):1:ALLSTAR") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(PINI, "YES")
  field(FLNK, "MGNT:$(LOCA):1:ALLSTARGO")
}

record(fanout, "MGNT:$(LOCA):1:ALLSTARGO") {
  field(LNK1, "MGNT:$(LOCA):1:ALLBENDSGO")
  field(LNK2, "MGNT:$(LOCA):1:ALLBTRMSGO")
  field(LNK3, "MGNT:$(LOCA):1:ALLLGPSSGO")
  field(LNK4, "MGNT:$(LOCA):1:ALLQUADSGO")
  field(LNK5, "MGNT:$(LOCA):1:ALLXCORSGO")
  field(LNK6, "MGNT:$(LOCA):1:ALLYCORSGO")
  field(FLNK, "MGNT:$(LOCA):1:ALLSTARGO_2")
}
record(fanout, "MGNT:$(LOCA):1:ALLSTARGO_2") {
  field(LNK1, "MGNT:$(LOCA):1:ALLSOLNSGO")
  field(LNK2, "MGNT:$(LOCA):1:ALLKICKSGO")
  field(LNK3, "MGNT:$(LOCA):1:ALLSEXTSGO")
}

#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:BENDCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_BEND so that it can be
# used properly by the the PV <device>:BENDSWITCH

record(mbbo, "MGNT:$(LOCA):1:BENDCTRL") {
  field(DESC, "All BEND Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "2")
  field(FLNK, "MGNT:$(LOCA):1:BENDSWITCH")
}

record(seq, "MGNT:$(LOCA):1:BENDSWITCH") {
  field(DOL1, "MGNT:$(LOCA):1:BENDCTRL.FFVL")
  field(LNK1, "MGNT:$(LOCA):1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:$(LOCA):1:BENDFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:$(LOCA):1:BENDCTRL")
}

record(seq, "MGNT:$(LOCA):1:ALLBENDSGO") {
  field(DOL1, "MGNT:$(LOCA):1:ALLSTAR")
  field(LNK1, "MGNT:$(LOCA):1:ALLBENDS PP NMS")
}

record(bo, "MGNT:$(LOCA):1:ALLBENDS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:$(LOCA):1:ALLBENDSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:$(LOCA):1:BENDCTRL",20,10,0,0,"MGNT:$(LOCA):1:BENDCTRL")
#! Field("MGNT:$(LOCA):1:BENDCTRL.FLNK",16777215,1,"MGNT:$(LOCA):1:BENDCTRL.FLNK")
#! Link("MGNT:$(LOCA):1:BENDCTRL.FLNK","MGNT:$(LOCA):1:BENDSWITCH")
#! Field("MGNT:$(LOCA):1:BENDCTRL.FFVL",16777215,1,"MGNT:$(LOCA):1:BENDCTRL.FFVL")
#! Record("MGNT:$(LOCA):1:BENDSWITCH",460,322,0,0,"MGNT:$(LOCA):1:BENDSWITCH")
#! Field("MGNT:$(LOCA):1:BENDSWITCH.DOL1",16777215,0,"MGNT:$(LOCA):1:BENDSWITCH.DOL1")
#! Link("MGNT:$(LOCA):1:BENDSWITCH.DOL1","MGNT:$(LOCA):1:BENDCTRL.FFVL")
#! Field("MGNT:$(LOCA):1:BENDSWITCH.LNK1",16777215,1,"MGNT:$(LOCA):1:BENDSWITCH.LNK1")
#! Field("MGNT:$(LOCA):1:BENDSWITCH.FLNK",16777215,1,"MGNT:$(LOCA):1:BENDSWITCH.FLNK")
#! Record("MGNT:$(LOCA):1:ALLBENDSGO",240,96,0,0,"MGNT:$(LOCA):1:ALLBENDSGO")
#! Field("MGNT:$(LOCA):1:ALLBENDSGO.DOL1",16777215,1,"MGNT:$(LOCA):1:ALLBENDSGO.DOL1")
#! Field("MGNT:$(LOCA):1:ALLBENDSGO.LNK1",16777215,1,"MGNT:$(LOCA):1:ALLBENDSGO.LNK1")
#! Link("MGNT:$(LOCA):1:ALLBENDSGO.LNK1","MGNT:$(LOCA):1:ALLBENDS.VAL")
#! Record("MGNT:$(LOCA):1:ALLBENDS",540,102,0,0,"MGNT:$(LOCA):1:ALLBENDS")
#! Field("MGNT:$(LOCA):1:ALLBENDS.VAL",16777215,0,"MGNT:$(LOCA):1:ALLBENDS.VAL")
#! Field("MGNT:$(LOCA):1:ALLBENDS.FLNK",16777215,1,"MGNT:$(LOCA):1:ALLBENDS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:BTRMCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_BTRM so that it can be
# used properly by the the PV <device>:BTRMSWITCH

record(mbbo, "MGNT:$(LOCA):1:BTRMCTRL") {
  field(DESC, "All BTRM Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "3")
  field(FLNK, "MGNT:$(LOCA):1:BTRMSWITCH")
}

record(seq, "MGNT:$(LOCA):1:BTRMSWITCH") {
  field(DOL1, "MGNT:$(LOCA):1:BTRMCTRL.FFVL")
  field(LNK1, "MGNT:$(LOCA):1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:$(LOCA):1:BTRMFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:$(LOCA):1:BTRMCTRL")
}

record(seq, "MGNT:$(LOCA):1:ALLBTRMSGO") {
  field(DOL1, "MGNT:$(LOCA):1:ALLSTAR")
  field(LNK1, "MGNT:$(LOCA):1:ALLBTRMS PP NMS")
}

record(bo, "MGNT:$(LOCA):1:ALLBTRMS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:$(LOCA):1:ALLBTRMSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:$(LOCA):1:BTRMCTRL",20,10,0,0,"MGNT:$(LOCA):1:BTRMCTRL")
#! Field("MGNT:$(LOCA):1:BTRMCTRL.FLNK",16777215,1,"MGNT:$(LOCA):1:BTRMCTRL.FLNK")
#! Link("MGNT:$(LOCA):1:BTRMCTRL.FLNK","MGNT:$(LOCA):1:BTRMSWITCH")
#! Field("MGNT:$(LOCA):1:BTRMCTRL.FFVL",16777215,1,"MGNT:$(LOCA):1:BTRMCTRL.FFVL")
#! Record("MGNT:$(LOCA):1:BTRMSWITCH",460,322,0,0,"MGNT:$(LOCA):1:BTRMSWITCH")
#! Field("MGNT:$(LOCA):1:BTRMSWITCH.DOL1",16777215,0,"MGNT:$(LOCA):1:BTRMSWITCH.DOL1")
#! Link("MGNT:$(LOCA):1:BTRMSWITCH.DOL1","MGNT:$(LOCA):1:BTRMCTRL.FFVL")
#! Field("MGNT:$(LOCA):1:BTRMSWITCH.LNK1",16777215,1,"MGNT:$(LOCA):1:BTRMSWITCH.LNK1")
#! Field("MGNT:$(LOCA):1:BTRMSWITCH.FLNK",16777215,1,"MGNT:$(LOCA):1:BTRMSWITCH.FLNK")
#! Record("MGNT:$(LOCA):1:ALLBTRMSGO",240,96,0,0,"MGNT:$(LOCA):1:ALLBTRMSGO")
#! Field("MGNT:$(LOCA):1:ALLBTRMSGO.DOL1",16777215,1,"MGNT:$(LOCA):1:ALLBTRMSGO.DOL1")
#! Field("MGNT:$(LOCA):1:ALLBTRMSGO.LNK1",16777215,1,"MGNT:$(LOCA):1:ALLBTRMSGO.LNK1")
#! Link("MGNT:$(LOCA):1:ALLBTRMSGO.LNK1","MGNT:$(LOCA):1:ALLBTRMS.VAL")
#! Record("MGNT:$(LOCA):1:ALLBTRMS",540,102,0,0,"MGNT:$(LOCA):1:ALLBTRMS")
#! Field("MGNT:$(LOCA):1:ALLBTRMS.VAL",16777215,0,"MGNT:$(LOCA):1:ALLBTRMS.VAL")
#! Field("MGNT:$(LOCA):1:ALLBTRMS.FLNK",16777215,1,"MGNT:$(LOCA):1:ALLBTRMS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:LGPSCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_LGPS so that it can be
# used properly by the the PV <device>:LGPSSWITCH

record(mbbo, "MGNT:$(LOCA):1:LGPSCTRL") {
  field(DESC, "All LGPS Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "3")
  field(FLNK, "MGNT:$(LOCA):1:LGPSSWITCH")
}

record(seq, "MGNT:$(LOCA):1:LGPSSWITCH") {
  field(DOL1, "MGNT:$(LOCA):1:LGPSCTRL.FFVL")
  field(LNK1, "MGNT:$(LOCA):1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:$(LOCA):1:LGPSFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:$(LOCA):1:LGPSCTRL")
}

record(seq, "MGNT:$(LOCA):1:ALLLGPSSGO") {
  field(DOL1, "MGNT:$(LOCA):1:ALLSTAR")
  field(LNK1, "MGNT:$(LOCA):1:ALLLGPSS PP NMS")
}

record(bo, "MGNT:$(LOCA):1:ALLLGPSS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:$(LOCA):1:ALLLGPSSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:$(LOCA):1:LGPSCTRL",20,10,0,0,"MGNT:$(LOCA):1:LGPSCTRL")
#! Field("MGNT:$(LOCA):1:LGPSCTRL.FLNK",16777215,1,"MGNT:$(LOCA):1:LGPSCTRL.FLNK")
#! Link("MGNT:$(LOCA):1:LGPSCTRL.FLNK","MGNT:$(LOCA):1:LGPSSWITCH")
#! Field("MGNT:$(LOCA):1:LGPSCTRL.FFVL",16777215,1,"MGNT:$(LOCA):1:LGPSCTRL.FFVL")
#! Record("MGNT:$(LOCA):1:LGPSSWITCH",460,322,0,0,"MGNT:$(LOCA):1:LGPSSWITCH")
#! Field("MGNT:$(LOCA):1:LGPSSWITCH.DOL1",16777215,0,"MGNT:$(LOCA):1:LGPSSWITCH.DOL1")
#! Link("MGNT:$(LOCA):1:LGPSSWITCH.DOL1","MGNT:$(LOCA):1:LGPSCTRL.FFVL")
#! Field("MGNT:$(LOCA):1:LGPSSWITCH.LNK1",16777215,1,"MGNT:$(LOCA):1:LGPSSWITCH.LNK1")
#! Field("MGNT:$(LOCA):1:LGPSSWITCH.FLNK",16777215,1,"MGNT:$(LOCA):1:LGPSSWITCH.FLNK")
#! Record("MGNT:$(LOCA):1:ALLLGPSSGO",240,96,0,0,"MGNT:$(LOCA):1:ALLLGPSSGO")
#! Field("MGNT:$(LOCA):1:ALLLGPSSGO.DOL1",16777215,1,"MGNT:$(LOCA):1:ALLLGPSSGO.DOL1")
#! Field("MGNT:$(LOCA):1:ALLLGPSSGO.LNK1",16777215,1,"MGNT:$(LOCA):1:ALLLGPSSGO.LNK1")
#! Link("MGNT:$(LOCA):1:ALLLGPSSGO.LNK1","MGNT:$(LOCA):1:ALLLGPSS.VAL")
#! Record("MGNT:$(LOCA):1:ALLLGPSS",540,102,0,0,"MGNT:$(LOCA):1:ALLLGPSS")
#! Field("MGNT:$(LOCA):1:ALLLGPSS.VAL",16777215,0,"MGNT:$(LOCA):1:ALLLGPSS.VAL")
#! Field("MGNT:$(LOCA):1:ALLLGPSS.FLNK",16777215,1,"MGNT:$(LOCA):1:ALLLGPSS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:QUADCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_QUAD so that it can be
# used properly by the the PV <device>:QUADSWITCH

record(mbbo, "MGNT:$(LOCA):1:QUADCTRL") {
  field(DESC, "All QUAD Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "5")
  field(FLNK, "MGNT:$(LOCA):1:QUADSWITCH")
}

record(seq, "MGNT:$(LOCA):1:QUADSWITCH") {
  field(DOL1, "MGNT:$(LOCA):1:QUADCTRL.FFVL")
  field(LNK1, "MGNT:$(LOCA):1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:$(LOCA):1:QUADFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:$(LOCA):1:QUADCTRL")
}

record(seq, "MGNT:$(LOCA):1:ALLQUADSGO") {
  field(DOL1, "MGNT:$(LOCA):1:ALLSTAR")
  field(LNK1, "MGNT:$(LOCA):1:ALLQUADS PP NMS")
}

record(bo, "MGNT:$(LOCA):1:ALLQUADS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:$(LOCA):1:ALLQUADSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:$(LOCA):1:QUADCTRL",20,10,0,0,"MGNT:$(LOCA):1:QUADCTRL")
#! Field("MGNT:$(LOCA):1:QUADCTRL.FLNK",16777215,1,"MGNT:$(LOCA):1:QUADCTRL.FLNK")
#! Link("MGNT:$(LOCA):1:QUADCTRL.FLNK","MGNT:$(LOCA):1:QUADSWITCH")
#! Field("MGNT:$(LOCA):1:QUADCTRL.FFVL",16777215,1,"MGNT:$(LOCA):1:QUADCTRL.FFVL")
#! Record("MGNT:$(LOCA):1:QUADSWITCH",460,322,0,0,"MGNT:$(LOCA):1:QUADSWITCH")
#! Field("MGNT:$(LOCA):1:QUADSWITCH.DOL1",16777215,0,"MGNT:$(LOCA):1:QUADSWITCH.DOL1")
#! Link("MGNT:$(LOCA):1:QUADSWITCH.DOL1","MGNT:$(LOCA):1:QUADCTRL.FFVL")
#! Field("MGNT:$(LOCA):1:QUADSWITCH.LNK1",16777215,1,"MGNT:$(LOCA):1:QUADSWITCH.LNK1")
#! Field("MGNT:$(LOCA):1:QUADSWITCH.FLNK",16777215,1,"MGNT:$(LOCA):1:QUADSWITCH.FLNK")
#! Record("MGNT:$(LOCA):1:ALLQUADSGO",240,96,0,0,"MGNT:$(LOCA):1:ALLQUADSGO")
#! Field("MGNT:$(LOCA):1:ALLQUADSGO.DOL1",16777215,1,"MGNT:$(LOCA):1:ALLQUADSGO.DOL1")
#! Field("MGNT:$(LOCA):1:ALLQUADSGO.LNK1",16777215,1,"MGNT:$(LOCA):1:ALLQUADSGO.LNK1")
#! Link("MGNT:$(LOCA):1:ALLQUADSGO.LNK1","MGNT:$(LOCA):1:ALLQUADS.VAL")
#! Record("MGNT:$(LOCA):1:ALLQUADS",540,102,0,0,"MGNT:$(LOCA):1:ALLQUADS")
#! Field("MGNT:$(LOCA):1:ALLQUADS.VAL",16777215,0,"MGNT:$(LOCA):1:ALLQUADS.VAL")
#! Field("MGNT:$(LOCA):1:ALLQUADS.FLNK",16777215,1,"MGNT:$(LOCA):1:ALLQUADS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:XCORCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_XCOR so that it can be
# used properly by the the PV <device>:XCORSWITCH

record(mbbo, "MGNT:$(LOCA):1:XCORCTRL") {
  field(DESC, "All XCOR Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "6")
  field(FLNK, "MGNT:$(LOCA):1:XCORSWITCH")
}

record(seq, "MGNT:$(LOCA):1:XCORSWITCH") {
  field(DOL1, "MGNT:$(LOCA):1:XCORCTRL.FFVL")
  field(LNK1, "MGNT:$(LOCA):1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:$(LOCA):1:XCORFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:$(LOCA):1:XCORCTRL")
}

record(seq, "MGNT:$(LOCA):1:ALLXCORSGO") {
  field(DOL1, "MGNT:$(LOCA):1:ALLSTAR")
  field(LNK1, "MGNT:$(LOCA):1:ALLXCORS PP NMS")
}

record(bo, "MGNT:$(LOCA):1:ALLXCORS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:$(LOCA):1:ALLXCORSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:$(LOCA):1:XCORCTRL",20,10,0,0,"MGNT:$(LOCA):1:XCORCTRL")
#! Field("MGNT:$(LOCA):1:XCORCTRL.FLNK",16777215,1,"MGNT:$(LOCA):1:XCORCTRL.FLNK")
#! Link("MGNT:$(LOCA):1:XCORCTRL.FLNK","MGNT:$(LOCA):1:XCORSWITCH")
#! Field("MGNT:$(LOCA):1:XCORCTRL.FFVL",16777215,1,"MGNT:$(LOCA):1:XCORCTRL.FFVL")
#! Record("MGNT:$(LOCA):1:XCORSWITCH",460,322,0,0,"MGNT:$(LOCA):1:XCORSWITCH")
#! Field("MGNT:$(LOCA):1:XCORSWITCH.DOL1",16777215,0,"MGNT:$(LOCA):1:XCORSWITCH.DOL1")
#! Link("MGNT:$(LOCA):1:XCORSWITCH.DOL1","MGNT:$(LOCA):1:XCORCTRL.FFVL")
#! Field("MGNT:$(LOCA):1:XCORSWITCH.LNK1",16777215,1,"MGNT:$(LOCA):1:XCORSWITCH.LNK1")
#! Field("MGNT:$(LOCA):1:XCORSWITCH.FLNK",16777215,1,"MGNT:$(LOCA):1:XCORSWITCH.FLNK")
#! Record("MGNT:$(LOCA):1:ALLXCORSGO",240,96,0,0,"MGNT:$(LOCA):1:ALLXCORSGO")
#! Field("MGNT:$(LOCA):1:ALLXCORSGO.DOL1",16777215,1,"MGNT:$(LOCA):1:ALLXCORSGO.DOL1")
#! Field("MGNT:$(LOCA):1:ALLXCORSGO.LNK1",16777215,1,"MGNT:$(LOCA):1:ALLXCORSGO.LNK1")
#! Link("MGNT:$(LOCA):1:ALLXCORSGO.LNK1","MGNT:$(LOCA):1:ALLXCORS.VAL")
#! Record("MGNT:$(LOCA):1:ALLXCORS",540,102,0,0,"MGNT:$(LOCA):1:ALLXCORS")
#! Field("MGNT:$(LOCA):1:ALLXCORS.VAL",16777215,0,"MGNT:$(LOCA):1:ALLXCORS.VAL")
#! Field("MGNT:$(LOCA):1:ALLXCORS.FLNK",16777215,1,"MGNT:$(LOCA):1:ALLXCORS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:YCORCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_YCOR so that it can be
# used properly by the the PV <device>:YCORSWITCH

record(mbbo, "MGNT:$(LOCA):1:YCORCTRL") {
  field(DESC, "All YCOR Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "7")
  field(FLNK, "MGNT:$(LOCA):1:YCORSWITCH")
}

record(seq, "MGNT:$(LOCA):1:YCORSWITCH") {
  field(DOL1, "MGNT:$(LOCA):1:YCORCTRL.FFVL")
  field(LNK1, "MGNT:$(LOCA):1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:$(LOCA):1:YCORFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:$(LOCA):1:YCORCTRL")
}

record(seq, "MGNT:$(LOCA):1:ALLYCORSGO") {
  field(DOL1, "MGNT:$(LOCA):1:ALLSTAR")
  field(LNK1, "MGNT:$(LOCA):1:ALLYCORS PP NMS")
}

record(bo, "MGNT:$(LOCA):1:ALLYCORS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:$(LOCA):1:ALLYCORSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:$(LOCA):1:YCORCTRL",20,10,0,0,"MGNT:$(LOCA):1:YCORCTRL")
#! Field("MGNT:$(LOCA):1:YCORCTRL.FLNK",16777215,1,"MGNT:$(LOCA):1:YCORCTRL.FLNK")
#! Link("MGNT:$(LOCA):1:YCORCTRL.FLNK","MGNT:$(LOCA):1:YCORSWITCH")
#! Field("MGNT:$(LOCA):1:YCORCTRL.FFVL",16777215,1,"MGNT:$(LOCA):1:YCORCTRL.FFVL")
#! Record("MGNT:$(LOCA):1:YCORSWITCH",460,322,0,0,"MGNT:$(LOCA):1:YCORSWITCH")
#! Field("MGNT:$(LOCA):1:YCORSWITCH.DOL1",16777215,0,"MGNT:$(LOCA):1:YCORSWITCH.DOL1")
#! Link("MGNT:$(LOCA):1:YCORSWITCH.DOL1","MGNT:$(LOCA):1:YCORCTRL.FFVL")
#! Field("MGNT:$(LOCA):1:YCORSWITCH.LNK1",16777215,1,"MGNT:$(LOCA):1:YCORSWITCH.LNK1")
#! Field("MGNT:$(LOCA):1:YCORSWITCH.FLNK",16777215,1,"MGNT:$(LOCA):1:YCORSWITCH.FLNK")
#! Record("MGNT:$(LOCA):1:ALLYCORSGO",240,96,0,0,"MGNT:$(LOCA):1:ALLYCORSGO")
#! Field("MGNT:$(LOCA):1:ALLYCORSGO.DOL1",16777215,1,"MGNT:$(LOCA):1:ALLYCORSGO.DOL1")
#! Field("MGNT:$(LOCA):1:ALLYCORSGO.LNK1",16777215,1,"MGNT:$(LOCA):1:ALLYCORSGO.LNK1")
#! Link("MGNT:$(LOCA):1:ALLYCORSGO.LNK1","MGNT:$(LOCA):1:ALLYCORS.VAL")
#! Record("MGNT:$(LOCA):1:ALLYCORS",540,102,0,0,"MGNT:$(LOCA):1:ALLYCORS")
#! Field("MGNT:$(LOCA):1:ALLYCORS.VAL",16777215,0,"MGNT:$(LOCA):1:ALLYCORS.VAL")
#! Field("MGNT:$(LOCA):1:ALLYCORS.FLNK",16777215,1,"MGNT:$(LOCA):1:ALLYCORS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:SOLNCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_SOLN so that it can be
# used properly by the the PV <device>:SOLNSWITCH

record(mbbo, "MGNT:$(LOCA):1:SOLNCTRL") {
  field(DESC, "All SOLN Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "8")
  field(FLNK, "MGNT:$(LOCA):1:SOLNSWITCH")
}

record(seq, "MGNT:$(LOCA):1:SOLNSWITCH") {
  field(DOL1, "MGNT:$(LOCA):1:SOLNCTRL.FFVL")
  field(LNK1, "MGNT:$(LOCA):1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:$(LOCA):1:SOLNFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:$(LOCA):1:SOLNCTRL")
}

record(seq, "MGNT:$(LOCA):1:ALLSOLNSGO") {
  field(DOL1, "MGNT:$(LOCA):1:ALLSTAR")
  field(LNK1, "MGNT:$(LOCA):1:ALLSOLNS PP NMS")
}

record(bo, "MGNT:$(LOCA):1:ALLSOLNS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:$(LOCA):1:ALLSOLNSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:$(LOCA):1:SOLNCTRL",20,10,0,0,"MGNT:$(LOCA):1:SOLNCTRL")
#! Field("MGNT:$(LOCA):1:SOLNCTRL.FLNK",16777215,1,"MGNT:$(LOCA):1:SOLNCTRL.FLNK")
#! Link("MGNT:$(LOCA):1:SOLNCTRL.FLNK","MGNT:$(LOCA):1:SOLNSWITCH")
#! Field("MGNT:$(LOCA):1:SOLNCTRL.FFVL",16777215,1,"MGNT:$(LOCA):1:SOLNCTRL.FFVL")
#! Record("MGNT:$(LOCA):1:SOLNSWITCH",460,322,0,0,"MGNT:$(LOCA):1:SOLNSWITCH")
#! Field("MGNT:$(LOCA):1:SOLNSWITCH.DOL1",16777215,0,"MGNT:$(LOCA):1:SOLNSWITCH.DOL1")
#! Link("MGNT:$(LOCA):1:SOLNSWITCH.DOL1","MGNT:$(LOCA):1:SOLNCTRL.FFVL")
#! Field("MGNT:$(LOCA):1:SOLNSWITCH.LNK1",16777215,1,"MGNT:$(LOCA):1:SOLNSWITCH.LNK1")
#! Field("MGNT:$(LOCA):1:SOLNSWITCH.FLNK",16777215,1,"MGNT:$(LOCA):1:SOLNSWITCH.FLNK")
#! Record("MGNT:$(LOCA):1:ALLSOLNSGO",240,96,0,0,"MGNT:$(LOCA):1:ALLSOLNSGO")
#! Field("MGNT:$(LOCA):1:ALLSOLNSGO.DOL1",16777215,1,"MGNT:$(LOCA):1:ALLSOLNSGO.DOL1")
#! Field("MGNT:$(LOCA):1:ALLSOLNSGO.LNK1",16777215,1,"MGNT:$(LOCA):1:ALLSOLNSGO.LNK1")
#! Link("MGNT:$(LOCA):1:ALLSOLNSGO.LNK1","MGNT:$(LOCA):1:ALLSOLNS.VAL")
#! Record("MGNT:$(LOCA):1:ALLSOLNS",540,102,0,0,"MGNT:$(LOCA):1:ALLSOLNS")
#! Field("MGNT:$(LOCA):1:ALLSOLNS.VAL",16777215,0,"MGNT:$(LOCA):1:ALLSOLNS.VAL")
#! Field("MGNT:$(LOCA):1:ALLSOLNS.FLNK",16777215,1,"MGNT:$(LOCA):1:ALLSOLNS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:KICKCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_KICK so that it can be
# used properly by the the PV <device>:KICKSWITCH

record(mbbo, "MGNT:$(LOCA):1:KICKCTRL") {
  field(DESC, "All KICK Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "9")
  field(FLNK, "MGNT:$(LOCA):1:KICKSWITCH")
}

record(seq, "MGNT:$(LOCA):1:KICKSWITCH") {
  field(DOL1, "MGNT:$(LOCA):1:KICKCTRL.FFVL")
  field(LNK1, "MGNT:$(LOCA):1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:$(LOCA):1:KICKFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:$(LOCA):1:KICKCTRL")
}

record(seq, "MGNT:$(LOCA):1:ALLKICKSGO") {
  field(DOL1, "MGNT:$(LOCA):1:ALLSTAR")
  field(LNK1, "MGNT:$(LOCA):1:ALLKICKS PP NMS")
}

record(bo, "MGNT:$(LOCA):1:ALLKICKS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:$(LOCA):1:ALLKICKSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:$(LOCA):1:KICKCTRL",20,10,0,0,"MGNT:$(LOCA):1:KICKCTRL")
#! Field("MGNT:$(LOCA):1:KICKCTRL.FLNK",16777215,1,"MGNT:$(LOCA):1:KICKCTRL.FLNK")
#! Link("MGNT:$(LOCA):1:KICKCTRL.FLNK","MGNT:$(LOCA):1:KICKSWITCH")
#! Field("MGNT:$(LOCA):1:KICKCTRL.FFVL",16777215,1,"MGNT:$(LOCA):1:KICKCTRL.FFVL")
#! Record("MGNT:$(LOCA):1:KICKSWITCH",460,322,0,0,"MGNT:$(LOCA):1:KICKSWITCH")
#! Field("MGNT:$(LOCA):1:KICKSWITCH.DOL1",16777215,0,"MGNT:$(LOCA):1:KICKSWITCH.DOL1")
#! Link("MGNT:$(LOCA):1:KICKSWITCH.DOL1","MGNT:$(LOCA):1:KICKCTRL.FFVL")
#! Field("MGNT:$(LOCA):1:KICKSWITCH.LNK1",16777215,1,"MGNT:$(LOCA):1:KICKSWITCH.LNK1")
#! Field("MGNT:$(LOCA):1:KICKSWITCH.FLNK",16777215,1,"MGNT:$(LOCA):1:KICKSWITCH.FLNK")
#! Record("MGNT:$(LOCA):1:ALLKICKSGO",240,96,0,0,"MGNT:$(LOCA):1:ALLKICKSGO")
#! Field("MGNT:$(LOCA):1:ALLKICKSGO.DOL1",16777215,1,"MGNT:$(LOCA):1:ALLKICKSGO.DOL1")
#! Field("MGNT:$(LOCA):1:ALLKICKSGO.LNK1",16777215,1,"MGNT:$(LOCA):1:ALLKICKSGO.LNK1")
#! Link("MGNT:$(LOCA):1:ALLKICKSGO.LNK1","MGNT:$(LOCA):1:ALLKICKS.VAL")
#! Record("MGNT:$(LOCA):1:ALLKICKS",540,102,0,0,"MGNT:$(LOCA):1:ALLKICKS")
#! Field("MGNT:$(LOCA):1:ALLKICKS.VAL",16777215,0,"MGNT:$(LOCA):1:ALLKICKS.VAL")
#! Field("MGNT:$(LOCA):1:ALLKICKS.FLNK",16777215,1,"MGNT:$(LOCA):1:ALLKICKS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# In the PV MGNT:<LOCA>:1:CTRLCLEAR LNK# (1-8)
# MUST corresponsds to the magent type defined
# in the file mgntCtrl.h.  Specifically,
# MGNT_TYPE_XCOR equals 6 and is LNK6
# in the above PV. Below in the pv <device>:SEXTCTRL
# the field FFVL value MUST be set to the value
# defined for MGNT_TYPE_SEXT so that it can be
# used properly by the the PV <device>:SEXTSWITCH

record(mbbo, "MGNT:$(LOCA):1:SEXTCTRL") {
  field(DESC, "All SEXT Function Control")
  field(PINI, "YES")
  field(DOL, "0")
  field(ZRST, "Ready")
  field(ONST, "TRIM")
  field(TWST, "PERTURB")
  field(THST, "BCON_TO_BDES")
  field(FRST, "BACT_TO_BDES")
  field(FVST, "SAVE_BDES")
  field(SXST, "LOAD_BDES")
  field(SVST, "UNDO_BDES")
  field(EIST, "DAC_ZERO")
  field(NIST, "STDZ")
  field(TEST, "CALIB")
  field(ELST, "DEGAUSS")
  field(TVST, "RESET")
  field(TTST, "TURN_ON")
  field(FTST, "TURN_OFF")
  field(ZRVL, "0")
  field(ONVL, "2")
  field(TWVL, "6")
  field(THVL, "15")
  field(FRVL, "14")
  field(FVVL, "11")
  field(SXVL, "12")
  field(SVVL, "13")
  field(EIVL, "7")
  field(NIVL, "4")
  field(TEVL, "3")
  field(ELVL, "5")
  field(TVVL, "8")
  field(TTVL, "9")
  field(FTVL, "10")
  field(FFVL, "10")
  field(FLNK, "MGNT:$(LOCA):1:SEXTSWITCH")
}

record(seq, "MGNT:$(LOCA):1:SEXTSWITCH") {
  field(DOL1, "MGNT:$(LOCA):1:SEXTCTRL.FFVL")
  field(LNK1, "MGNT:$(LOCA):1:CTRLSWITCH PP NMS")
  field(FLNK, "MGNT:$(LOCA):1:SEXTFUNCGO PP NMS")
  field(DISV, "0")
  field(SDIS, "MGNT:$(LOCA):1:SEXTCTRL")
}

record(seq, "MGNT:$(LOCA):1:ALLSEXTSGO") {
  field(DOL1, "MGNT:$(LOCA):1:ALLSTAR")
  field(LNK1, "MGNT:$(LOCA):1:ALLSEXTS PP NMS")
}

record(bo, "MGNT:$(LOCA):1:ALLSEXTS") {
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(FLNK, "MGNT:$(LOCA):1:ALLSEXTSSEL")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("MGNT:$(LOCA):1:SEXTCTRL",20,10,0,0,"MGNT:$(LOCA):1:SEXTCTRL")
#! Field("MGNT:$(LOCA):1:SEXTCTRL.FLNK",16777215,1,"MGNT:$(LOCA):1:SEXTCTRL.FLNK")
#! Link("MGNT:$(LOCA):1:SEXTCTRL.FLNK","MGNT:$(LOCA):1:SEXTSWITCH")
#! Field("MGNT:$(LOCA):1:SEXTCTRL.FFVL",16777215,1,"MGNT:$(LOCA):1:SEXTCTRL.FFVL")
#! Record("MGNT:$(LOCA):1:SEXTSWITCH",460,322,0,0,"MGNT:$(LOCA):1:SEXTSWITCH")
#! Field("MGNT:$(LOCA):1:SEXTSWITCH.DOL1",16777215,0,"MGNT:$(LOCA):1:SEXTSWITCH.DOL1")
#! Link("MGNT:$(LOCA):1:SEXTSWITCH.DOL1","MGNT:$(LOCA):1:SEXTCTRL.FFVL")
#! Field("MGNT:$(LOCA):1:SEXTSWITCH.LNK1",16777215,1,"MGNT:$(LOCA):1:SEXTSWITCH.LNK1")
#! Field("MGNT:$(LOCA):1:SEXTSWITCH.FLNK",16777215,1,"MGNT:$(LOCA):1:SEXTSWITCH.FLNK")
#! Record("MGNT:$(LOCA):1:ALLSEXTSGO",240,96,0,0,"MGNT:$(LOCA):1:ALLSEXTSGO")
#! Field("MGNT:$(LOCA):1:ALLSEXTSGO.DOL1",16777215,1,"MGNT:$(LOCA):1:ALLSEXTSGO.DOL1")
#! Field("MGNT:$(LOCA):1:ALLSEXTSGO.LNK1",16777215,1,"MGNT:$(LOCA):1:ALLSEXTSGO.LNK1")
#! Link("MGNT:$(LOCA):1:ALLSEXTSGO.LNK1","MGNT:$(LOCA):1:ALLSEXTS.VAL")
#! Record("MGNT:$(LOCA):1:ALLSEXTS",540,102,0,0,"MGNT:$(LOCA):1:ALLSEXTS")
#! Field("MGNT:$(LOCA):1:ALLSEXTS.VAL",16777215,0,"MGNT:$(LOCA):1:ALLSEXTS.VAL")
#! Field("MGNT:$(LOCA):1:ALLSEXTS.FLNK",16777215,1,"MGNT:$(LOCA):1:ALLSEXTS.FLNK")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "QUAD:$(LOCA):$(ID)85:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:$(LOCA):1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:$(LOCA):1:CTRL.RVAL")
  field(LNK1, "QUAD:$(LOCA):$(ID)85:FUNC CA PP")
  field(DOL2, "MGNT:$(LOCA):1:BENDCTRL.RVAL")
  field(LNK2, "QUAD:$(LOCA):$(ID)85:FUNC CA PP")
  field(DOL3, "MGNT:$(LOCA):1:BTRMCTRL.RVAL")
  field(LNK3, "QUAD:$(LOCA):$(ID)85:FUNC CA PP")
  field(DOL4, "MGNT:$(LOCA):1:LGPSCTRL.RVAL")
  field(LNK4, "QUAD:$(LOCA):$(ID)85:FUNC CA PP")
  field(DOL5, "MGNT:$(LOCA):1:QUADCTRL.RVAL")
  field(LNK5, "QUAD:$(LOCA):$(ID)85:FUNC CA PP")
  field(DOL6, "MGNT:$(LOCA):1:XCORCTRL.RVAL")
  field(LNK6, "QUAD:$(LOCA):$(ID)85:FUNC CA PP")
  field(DOL7, "MGNT:$(LOCA):1:YCORCTRL.RVAL")
  field(LNK7, "QUAD:$(LOCA):$(ID)85:FUNC CA PP")
  field(DOL8, "MGNT:$(LOCA):1:SOLNCTRL.RVAL")
  field(LNK8, "QUAD:$(LOCA):$(ID)85:FUNC CA PP")
  field(DOL9, "MGNT:$(LOCA):1:KICKCTRL.RVAL")
  field(LNK9, "QUAD:$(LOCA):$(ID)85:FUNC CA PP")
  field(DOLA, "MGNT:$(LOCA):1:SEXTCTRL.RVAL")
  field(LNKA, "QUAD:$(LOCA):$(ID)85:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "QUAD:$(LOCA):$(ID)85:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "QUAD:$(LOCA):$(ID)85:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "QUAD:$(LOCA):$(ID)85:EDES.PROC PP")
    field(LNK2, "QUAD:$(LOCA):$(ID)85:EACT.PROC PP")
    field(LNK3, "QUAD:$(LOCA):$(ID)85:EERR.DISA PP")
    field(LNK4, "QUAD:$(LOCA):$(ID)85:ECON.PROC PP")
    field(LNK5, "QUAD:$(LOCA):$(ID)85:BMAGX.PROC PP")
    field(LNK6, "QUAD:$(LOCA):$(ID)85:BMAGY.PROC PP")
    field(LNK7, "QUAD:$(LOCA):$(ID)85:BLEM.PROC PP")
    field(LNK8, "QUAD:$(LOCA):$(ID)85:BMOD.PROC PP")
    field(LNK9, "QUAD:$(LOCA):$(ID)85:EDESSAVE.PROC PP")
    field(LNKA, "QUAD:$(LOCA):$(ID)85:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"QUAD:$(LOCA):$(ID)85:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "QUAD:$(LOCA):$(ID)85:BMAX")
  field(DOL2, "QUAD:$(LOCA):$(ID)85:BMAX")
  field(DOL3, "QUAD:$(LOCA):$(ID)85:BMAX")
  field(DOL4, "QUAD:$(LOCA):$(ID)85:BMIN")
  field(DOL5, "QUAD:$(LOCA):$(ID)85:BMIN")
  field(DOL6, "QUAD:$(LOCA):$(ID)85:BMIN")
  field(LNK1, "QUAD:$(LOCA):$(ID)85:BMAGX.HOPR")
  field(LNK2, "QUAD:$(LOCA):$(ID)85:BMAGY.HOPR")
  field(LNK3, "QUAD:$(LOCA):$(ID)85:BLEM.HOPR")
  field(LNK4, "QUAD:$(LOCA):$(ID)85:BMAGX.LOPR PP")
  field(LNK5, "QUAD:$(LOCA):$(ID)85:BMAGY.LOPR PP")
  field(LNK6, "QUAD:$(LOCA):$(ID)85:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "QUAD:$(LOCA):$(ID)85:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "QUAD:$(LOCA):$(ID)85:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "QUAD:$(LOCA):$(ID)85:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "QUAD:$(LOCA):$(ID)85:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "QUAD:$(LOCA):$(ID)85:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:$(LOCA):$(ID)85:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:$(LOCA):$(ID)85:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:$(LOCA):$(ID)85:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "QUAD:$(LOCA):$(ID)85:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "QUAD:$(LOCA):$(ID)85:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "QUAD:$(LOCA):$(ID)85:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "QUAD:$(LOCA):$(ID)85:EDES NPP MS")
  field(INPB, "QUAD:$(LOCA):$(ID)85:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "XCOR:$(LOCA):$(ID)85:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:$(LOCA):1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:$(LOCA):1:CTRL.RVAL")
  field(LNK1, "XCOR:$(LOCA):$(ID)85:FUNC CA PP")
  field(DOL2, "MGNT:$(LOCA):1:BENDCTRL.RVAL")
  field(LNK2, "XCOR:$(LOCA):$(ID)85:FUNC CA PP")
  field(DOL3, "MGNT:$(LOCA):1:BTRMCTRL.RVAL")
  field(LNK3, "XCOR:$(LOCA):$(ID)85:FUNC CA PP")
  field(DOL4, "MGNT:$(LOCA):1:LGPSCTRL.RVAL")
  field(LNK4, "XCOR:$(LOCA):$(ID)85:FUNC CA PP")
  field(DOL5, "MGNT:$(LOCA):1:QUADCTRL.RVAL")
  field(LNK5, "XCOR:$(LOCA):$(ID)85:FUNC CA PP")
  field(DOL6, "MGNT:$(LOCA):1:XCORCTRL.RVAL")
  field(LNK6, "XCOR:$(LOCA):$(ID)85:FUNC CA PP")
  field(DOL7, "MGNT:$(LOCA):1:YCORCTRL.RVAL")
  field(LNK7, "XCOR:$(LOCA):$(ID)85:FUNC CA PP")
  field(DOL8, "MGNT:$(LOCA):1:SOLNCTRL.RVAL")
  field(LNK8, "XCOR:$(LOCA):$(ID)85:FUNC CA PP")
  field(DOL9, "MGNT:$(LOCA):1:KICKCTRL.RVAL")
  field(LNK9, "XCOR:$(LOCA):$(ID)85:FUNC CA PP")
  field(DOLA, "MGNT:$(LOCA):1:SEXTCTRL.RVAL")
  field(LNKA, "XCOR:$(LOCA):$(ID)85:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "XCOR:$(LOCA):$(ID)85:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "XCOR:$(LOCA):$(ID)85:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "XCOR:$(LOCA):$(ID)85:EDES.PROC PP")
    field(LNK2, "XCOR:$(LOCA):$(ID)85:EACT.PROC PP")
    field(LNK3, "XCOR:$(LOCA):$(ID)85:EERR.DISA PP")
    field(LNK4, "XCOR:$(LOCA):$(ID)85:ECON.PROC PP")
    field(LNK5, "XCOR:$(LOCA):$(ID)85:BMAGX.PROC PP")
    field(LNK6, "XCOR:$(LOCA):$(ID)85:BMAGY.PROC PP")
    field(LNK7, "XCOR:$(LOCA):$(ID)85:BLEM.PROC PP")
    field(LNK8, "XCOR:$(LOCA):$(ID)85:BMOD.PROC PP")
    field(LNK9, "XCOR:$(LOCA):$(ID)85:EDESSAVE.PROC PP")
    field(LNKA, "XCOR:$(LOCA):$(ID)85:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"XCOR:$(LOCA):$(ID)85:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "XCOR:$(LOCA):$(ID)85:BMAX")
  field(DOL2, "XCOR:$(LOCA):$(ID)85:BMAX")
  field(DOL3, "XCOR:$(LOCA):$(ID)85:BMAX")
  field(DOL4, "XCOR:$(LOCA):$(ID)85:BMIN")
  field(DOL5, "XCOR:$(LOCA):$(ID)85:BMIN")
  field(DOL6, "XCOR:$(LOCA):$(ID)85:BMIN")
  field(LNK1, "XCOR:$(LOCA):$(ID)85:BMAGX.HOPR")
  field(LNK2, "XCOR:$(LOCA):$(ID)85:BMAGY.HOPR")
  field(LNK3, "XCOR:$(LOCA):$(ID)85:BLEM.HOPR")
  field(LNK4, "XCOR:$(LOCA):$(ID)85:BMAGX.LOPR PP")
  field(LNK5, "XCOR:$(LOCA):$(ID)85:BMAGY.LOPR PP")
  field(LNK6, "XCOR:$(LOCA):$(ID)85:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "XCOR:$(LOCA):$(ID)85:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "XCOR:$(LOCA):$(ID)85:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "XCOR:$(LOCA):$(ID)85:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "XCOR:$(LOCA):$(ID)85:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "XCOR:$(LOCA):$(ID)85:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:$(LOCA):$(ID)85:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:$(LOCA):$(ID)85:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "XCOR:$(LOCA):$(ID)85:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "XCOR:$(LOCA):$(ID)85:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "XCOR:$(LOCA):$(ID)85:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "XCOR:$(LOCA):$(ID)85:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "XCOR:$(LOCA):$(ID)85:EDES NPP MS")
  field(INPB, "XCOR:$(LOCA):$(ID)85:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../../dbd/mgntSoft.dbd")
#! DBDEND



record(seq, "YCOR:$(LOCA):$(ID)85:ALLFUNCGO") {
  field(DESC, "All function go")
  field(SELL, "MGNT:$(LOCA):1:CTRLSWITCH")
  field(SELM, "Specified")
  field(DOL1, "MGNT:$(LOCA):1:CTRL.RVAL")
  field(LNK1, "YCOR:$(LOCA):$(ID)85:FUNC CA PP")
  field(DOL2, "MGNT:$(LOCA):1:BENDCTRL.RVAL")
  field(LNK2, "YCOR:$(LOCA):$(ID)85:FUNC CA PP")
  field(DOL3, "MGNT:$(LOCA):1:BTRMCTRL.RVAL")
  field(LNK3, "YCOR:$(LOCA):$(ID)85:FUNC CA PP")
  field(DOL4, "MGNT:$(LOCA):1:LGPSCTRL.RVAL")
  field(LNK4, "YCOR:$(LOCA):$(ID)85:FUNC CA PP")
  field(DOL5, "MGNT:$(LOCA):1:QUADCTRL.RVAL")
  field(LNK5, "YCOR:$(LOCA):$(ID)85:FUNC CA PP")
  field(DOL6, "MGNT:$(LOCA):1:XCORCTRL.RVAL")
  field(LNK6, "YCOR:$(LOCA):$(ID)85:FUNC CA PP")
  field(DOL7, "MGNT:$(LOCA):1:YCORCTRL.RVAL")
  field(LNK7, "YCOR:$(LOCA):$(ID)85:FUNC CA PP")
  field(DOL8, "MGNT:$(LOCA):1:SOLNCTRL.RVAL")
  field(LNK8, "YCOR:$(LOCA):$(ID)85:FUNC CA PP")
  field(DOL9, "MGNT:$(LOCA):1:KICKCTRL.RVAL")
  field(LNK9, "YCOR:$(LOCA):$(ID)85:FUNC CA PP")
  field(DOLA, "MGNT:$(LOCA):1:SEXTCTRL.RVAL")
  field(LNKA, "YCOR:$(LOCA):$(ID)85:FUNC CA PP")
  field(DISV, "0")
  field(SDIS, "YCOR:$(LOCA):$(ID)85:SELECT CPP")
}


#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND

# Initialize model pvs on boot
record(seq, "YCOR:$(LOCA):$(ID)85:BMAGINIT") {
    field(DOL1, "1")
    field(DOL2, "1")
    field(DOL3, "0")
    field(DOL4, "1")
    field(DOL5, "1")
    field(DOL6, "1")
    field(DOL7, "1")
    field(DOL8, "1")
    field(DLY8, "1")
    field(DOL9, "1")
    field(DOLA, "1")
    field(LNK1, "YCOR:$(LOCA):$(ID)85:EDES.PROC PP")
    field(LNK2, "YCOR:$(LOCA):$(ID)85:EACT.PROC PP")
    field(LNK3, "YCOR:$(LOCA):$(ID)85:EERR.DISA PP")
    field(LNK4, "YCOR:$(LOCA):$(ID)85:ECON.PROC PP")
    field(LNK5, "YCOR:$(LOCA):$(ID)85:BMAGX.PROC PP")
    field(LNK6, "YCOR:$(LOCA):$(ID)85:BMAGY.PROC PP")
    field(LNK7, "YCOR:$(LOCA):$(ID)85:BLEM.PROC PP")
    field(LNK8, "YCOR:$(LOCA):$(ID)85:BMOD.PROC PP")
    field(LNK9, "YCOR:$(LOCA):$(ID)85:EDESSAVE.PROC PP")
    field(LNKA, "YCOR:$(LOCA):$(ID)85:BMAGLIMITS.PROC PP")
    field(PINI, "YES")
}

record(seq,"YCOR:$(LOCA):$(ID)85:BMAGLIMITS") {
  field(DESC, "BMAG Limits")
  field(DOL1, "YCOR:$(LOCA):$(ID)85:BMAX")
  field(DOL2, "YCOR:$(LOCA):$(ID)85:BMAX")
  field(DOL3, "YCOR:$(LOCA):$(ID)85:BMAX")
  field(DOL4, "YCOR:$(LOCA):$(ID)85:BMIN")
  field(DOL5, "YCOR:$(LOCA):$(ID)85:BMIN")
  field(DOL6, "YCOR:$(LOCA):$(ID)85:BMIN")
  field(LNK1, "YCOR:$(LOCA):$(ID)85:BMAGX.HOPR")
  field(LNK2, "YCOR:$(LOCA):$(ID)85:BMAGY.HOPR")
  field(LNK3, "YCOR:$(LOCA):$(ID)85:BLEM.HOPR")
  field(LNK4, "YCOR:$(LOCA):$(ID)85:BMAGX.LOPR PP")
  field(LNK5, "YCOR:$(LOCA):$(ID)85:BMAGY.LOPR PP")
  field(LNK6, "YCOR:$(LOCA):$(ID)85:BLEM.LOPR PP")
}

# No EGU as per Henrik
record(ao, "YCOR:$(LOCA):$(ID)85:BMAGX") {
  field(DESC, "Calc Horiz B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# No EGU as per Henrik
record(ao, "YCOR:$(LOCA):$(ID)85:BMAGY") {
  field(DESC, "Calc Vert B-field")
  field(DTYP, "Soft Channel")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# BLEM value can change when we change eh setting in LEM
# BMOD is always caluated using same formula
record(ao, "YCOR:$(LOCA):$(ID)85:BLEM") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}
record(ao, "YCOR:$(LOCA):$(ID)85:BMOD") {
  field(DESC, "Calc LEM B-field")
  field(DTYP, "Soft Channel")
  field(EGU,  "kG-m")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

# Beam Energy PVs
record(ao, "YCOR:$(LOCA):$(ID)85:EDESSAVE") {
  field(DESC, "edes for save/load")
  field(DTYP, "Soft Channel")
  field(EGU,  "GeV/c)")
  field(HOPR, "50.0")
  field(DRVH, "50.0")
  field(PREC, "7")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:$(LOCA):$(ID)85:ECON") {
  field(DESC, "Energy Config")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "GeV/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#  field(DOL,  "")
  field(OMSL, "supervisory")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:$(LOCA):$(ID)85:EDES") {
  field(DESC, "Desired Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(HOPR, "50.0")
  field(EGU,  "GeV/c")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:$(LOCA):$(ID)85:EERR")
  info(autosaveFields,"VAL")
}

record(ao, "YCOR:$(LOCA):$(ID)85:EACT") {
  field(DESC, "Actual Energy")
  field(DTYP, "Soft Channel")
  field(DRVH, "50.0")
  field(DRVL, "0.0")
  field(EGU, "Gev/c")
  field(HOPR, "50.0")
  field(LOPR, "0.0")
  field(PREC, "6")
#   field(DOL,  "")
  field(OMSL, "supervisory")
  field(FLNK, "YCOR:$(LOCA):$(ID)85:EERR")
  info(autosaveFields,"VAL")
}

# This is the error of EACT-EDES used by the LEM CUD
# The error is 0.5% of EDES, unless EDES=0 then
# the error is 0.
record(calc,  "YCOR:$(LOCA):$(ID)85:EERR") {
  field(DESC, "LEM Error")
  field(CALC, "A?((B-A)/A):0")
  field(INPA, "YCOR:$(LOCA):$(ID)85:EDES NPP MS")
  field(INPB, "YCOR:$(LOCA):$(ID)85:EACT NPP MS")
  field(HIHI, "0.005")
  field(HIGH, "0.005")
  field(LOLO, "-0.005")
  field(LOW,  "-0.005")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV,  "MAJOR")
  field(LSV,  "MAJOR")
  field(DISA, "1")
}
# Cryo Module Identification PV

record(longout, "CM:$(LOCA):$(ID)85:ID") {
  field(DESC, "Cryo Module ID")
  field(PINI, "YES")
  field(DRVL, "0")
  field(DRVH, "40")
  field(VAL, "0")
  info(autosaveFields,"VAL")
}
# Control Cryo Module Magnet PS On/Off PVs

record(bo, "CM:$(LOCA):$(ID)85:STATESETPT") {
  field(DESC, "Turn Off/On Supplies")
  field(ZNAM, "OFF")
  field(ONAM, "ON")
  field(OUT, "CM:$(LOCA):$(ID)85:STATESETPT_CALC.A PP")
}

record(calc, "CM:$(LOCA):$(ID)85:STATESETPT_CALC") {
  field(DESC, "Convert on/off to ctrl func")
  field(CALC, "A?9:10")
  field(INPA, "CM:$(LOCA):$(ID)85:STATESETPT NPP NMS") 
  field(FLNK,  "CM:$(LOCA):$(ID)85:STATESETPT_SEQ")
}

record(seq,"CM:$(LOCA):$(ID)85:STATESETPT_SEQ") {
  field(DESC, "All Supplies Off")
  field(DOL1, "CM:$(LOCA):$(ID)85:STATESETPT_CALC")
  field(DOL2, "CM:$(LOCA):$(ID)85:STATESETPT_CALC")
  field(DOL3, "CM:$(LOCA):$(ID)85:STATESETPT_CALC")
  field(LNK1, "QUAD:$(LOCA):$(ID)85:FUNC PP")
  field(LNK2, "XCOR:$(LOCA):$(ID)85:FUNC PP")
  field(LNK3, "YCOR:$(LOCA):$(ID)85:FUNC PP")
}