# bulk Ground Fault Current Threshold Settings and Readings
# scondam: 24-Sept-2021: Per T.Beukers, Ground Fault Current can be equated to Ground voltage (sort of)
#                        It is possibly not the same scale factor as bulk voltage but use the same calculation for now.
#          28-Sept-2021: M.Lavoie's tests:
#                              Created a ground fault on CH0, and saw that the 'Bulk Gnd Flt Curr' field displayed a value slightly over 10% higher 
#                              than what I measured directly across the load resistor when using several different resistive loads (30 and 7.5 ohms). 
#                              Max. ground fault currents were in the low 40mA range, and did not see the 'Bulk Gnd Fault' change state at any time. 
#                              BTW - would be good to include units of mA in the 'Bulk Gnd Flt Curr' field.
#		   29-Sept-2021:  M.Lavoie repeated test. Concluded that the CALC field reading is in mA
#						       He induced a Gnd Flt Curr of 30.1mA and BULK_GNDFLT_CURR was reading -31 mA and is reasonably stable. 
#                              BULK_GNDCURR_FLT_THLD_S threhsold could not be set. No matter what, _S and _R always reads zero.
#							   Thus was unable to set a threshold to try and trip the Bulk PS on a Ground Current Fault.
#							   Bulk Ground Fault current state BULKGNDCURRFLTSTATE did not change at any time.
#
record(calc, "$(crate):BULK_GNDFLT_CURR") {
  field(DESC, "Bulk PS Ground Fault Curr")
  field(CALC, "((((A*40.0)/262144.0)*12.0)*0.9)")
  field(INPA, "$(crate):BULK_GNDFLT_CURR_R")
  field(EGU,  "mA")
  field(PREC, "4")
  field(HIHI, "25")
  field(HIGH, "22")
  field(LOW,  "-22")
  field(LOLO, "-25")
  field(HOPR, "25")
  field(LOPR, "-25")
  field(HYST, "0")
  field(LLSV, "MAJOR")  
  field(LSV,  "MINOR")
  field(HSV,  "MINOR")  
  field(HHSV, "MAJOR")   
  field(PINI, "YES")  
  field(FLNK, "$(crate):BulkGndCurrCheck")
}

# InhibitSetpt is set only by user to uninhibit after fault condition clears
record(bo, "$(crate):InhibitSetpt") {
        field(DESC, "Unhinhibit all")
        field(ONAM, "Uninhibit")
        field(ZNAM, "Inhibit")
        field(ZSV,  "MAJOR")
        field(PINI, "YES")	
		field(FLNK, "$(crate):UnInhibitAllCalc")	
}

record(calcout, "$(crate):UnInhibitAllCalc") {
	    field(ASG, "Internal")
		field(CALC, "(A<2)&&B?0:1")
	    field(INPA, "$(crate):BULK_GNDFLT_CURR.SEVR")
	    field(INPB, "$(crate):InhibitSetpt")		
		field(OUT, "$(crate):UnInhibitAll.DISA")	
		field(FLNK, "$(crate):UnInhibitAll")				
}

record(bi, "$(crate):Inhibit") {
        field(DESC, "Inhibit State")
        field(ONAM, "Uninhibit")
        field(ZNAM, "Inhibit")
		field(INP,  "$(crate):InhibitSetpt CP MS")	
}

# State is red if the crate is inhibited due to a ground fault.
# The status check is done every 1 seconds so we run at 
# 1 second but at a higher PHAS so it's done after GndFault status.
#

record(calcout, "$(crate):BulkGndCurrCheck") {
	field(DESC, "Bulk Gnd Current Check")
	field(ASG, "Internal")
	field(CALC, "(C!=2)||(A>D+1)?0:((A<D)?A+1:D+1)")
	field(INPA, "$(crate):BulkGndCurrCheck")
	field(INPC, "$(crate):BULK_GNDFLT_CURR.SEVR")
	field(INPD, "5")
	field(OUT,  "$(crate):StateCalc.SELN")
    field(FLNK,  "$(crate):StateCalc")	
}

record(seq, "$(crate):StateCalc")
{
	field(ASG, "Internal")
	field(DESC, "State Calculation")
    field(SELM, "Specified")
	field(SELL, "$(crate):StateCalc.SELN")
	field(DO5,  "1")
    field(LNK5,  "$(crate):CurrSetptLatch1.PROC") 		
	field(FLNK,  "$(crate):State")
}

record(bi, "$(crate):State")
{
	field(DESC, "State")
	field(INP,  "$(crate):StateCalc NPP MS")
	field(ZNAM, "On")
	field(ONAM, "Off")
	field(OSV,  "MAJOR")
}

# scondam: 13-Apr-2022 MAJOR (2) sevrity of bulk ground fault current will set $(crate):GndFault status to Fault. Else no fault.

# If there is a ground current fault:
#		(1) latch all current setpoints
#		(2) output 0 A to all of them
#		(3) disable all the setpoint pvs.
# Else do nothing.
#
# CurrSetpt are always latched into CurrSetptLatch as soon as CurrSept changes (mcorCurr.db)
# The $(crate):StateCalc is processed once per second.
# Its output changes to 1 only when GndFault changes to 1 (Fault) which happens when there is a ground current fault so CurrSetptLatch1 is processed.
# When GndFault is 0 (OK) then (crate):StateCalc does not output anything and CurrSetptLatch1 is not processed.
# When the output changes to 1 CurrSetptLatch.PROC is processed. 
# When CurrSetptLatch1 and 2 are processed the latest setpoints are latched.
#

# if there is a Gnd Current fault, first latch all the CurrSetpt values in CurrSetptLatch PVs
record(fanout, "$(crate):CurrSetptLatch1") {
   field(DESC, "Latch all Ch Curr Setpts")
   field(ASG,  "Internal")  
   field(LNK1, "01G-QSS4:CurrSetptLatch PP")
   field(LNK2, "02G-QSS3:CurrSetptLatch PP")
   field(LNK3, "03G-QSS3:CurrSetptLatch PP")
   field(LNK4, "05G-QSS3:CurrSetptLatch PP")
   field(FLNK,  "$(crate):CurrSetptLatch2")
}

record(fanout, "$(crate):CurrSetptLatch2") {
   field(DESC, "Latch all Ch Curr Setpts")
   field(ASG,  "Internal")  
   field(LNK1, "07G-QSS2:CurrSetptLatch PP")
   field(LNK2, "08G-QSS2:CurrSetptLatch PP")
   field(LNK3, "09G-QSS1:CurrSetptLatch PP")
   field(LNK4, "04G-QSS3:CurrSetptLatch PP")
   field(FLNK, "$(crate):CurrSetptLatchDisable")
}

# next disable the CurrSetptLatch PVs such that when CurrSetpts are zeroed out, these do not overwrite the last CurrSetpts values
record(seq, "$(crate):CurrSetptLatchDisable") {
  field(DESC, "Disable Ch Latch Setpts")
  field(ASG,  "Internal")   
  field(DO1, "1")
  field(DO2, "1")
  field(DO3, "1")
  field(DO4, "1")
  field(DO5, "1")
  field(DO6, "1")
  field(DO7, "1")
  field(DO8, "1")
  field(LNK1, "01G-QSS4:CurrSetptLatch.DISA PP")
  field(LNK2, "02G-QSS3:CurrSetptLatch.DISA PP")
  field(LNK3, "03G-QSS3:CurrSetptLatch.DISA PP")
  field(LNK4, "05G-QSS3:CurrSetptLatch.DISA PP")
  field(LNK5, "07G-QSS2:CurrSetptLatch.DISA PP")
  field(LNK6, "08G-QSS2:CurrSetptLatch.DISA PP")
  field(LNK7, "09G-QSS1:CurrSetptLatch.DISA PP")
  field(LNK8, "04G-QSS3:CurrSetptLatch.DISA PP")
  field(FLNK, "$(crate):CurrSetptZero")  
}

# Then set all CurrSetpt PVs to 0
record(seq, "$(crate):CurrSetptZero") {
  field(DESC, "All Ch Setpt Curr = 0")
  field(ASG,  "Internal")    
  field(DO1, "0")
  field(DO2, "0")
  field(DO3, "0")
  field(DO4, "0")
  field(DO5, "0")
  field(DO6, "0")
  field(DO7, "0")
  field(DO8, "0")
  field(LNK1, "01G-QSS4:CurrSetpt PP")
  field(LNK2, "02G-QSS3:CurrSetpt PP")
  field(LNK3, "03G-QSS3:CurrSetpt PP")
  field(LNK4, "05G-QSS3:CurrSetpt PP")
  field(LNK5, "07G-QSS2:CurrSetpt PP")
  field(LNK6, "08G-QSS2:CurrSetpt PP")
  field(LNK7, "09G-QSS1:CurrSetpt PP")
  field(LNK8, "04G-QSS3:CurrSetpt PP")
  field(FLNK, "$(crate):InhibitAll")  
}

# finally disable all the CurrSetpt PVs such that they cannot be changed via CA unless Fault condition clears and user Unhibits.
record(seq, "$(crate):InhibitAll") {
  field(DESC, "Disable or Enable all Ch Setpts")
  field(ASG,  "Internal")    
  field(DO1, "1")
  field(DO2, "1")
  field(DO3, "1")
  field(DO4, "1")
  field(DO5, "1")
  field(DO6, "1")
  field(DO7, "1")
  field(DO8, "1")
  field(LNK1, "01G-QSS4:CurrSetpt.DISA PP")
  field(LNK2, "02G-QSS3:CurrSetpt.DISA PP")
  field(LNK3, "03G-QSS3:CurrSetpt.DISA PP")
  field(LNK4, "05G-QSS3:CurrSetpt.DISA PP")
  field(LNK5, "07G-QSS2:CurrSetpt.DISA PP")
  field(LNK6, "08G-QSS2:CurrSetpt.DISA PP")
  field(LNK7, "09G-QSS1:CurrSetpt.DISA PP")
  field(LNK8, "04G-QSS3:CurrSetpt.DISA PP")
}

record(seq, "$(crate):UnInhibitAll") {
  field(DESC, "Disable or Enable all Ch Setpts")
  field(ASG,  "Internal")    
  field(DO1, "0")
  field(DO2, "0")
  field(DO3, "0")
  field(DO4, "0")
  field(DO5, "0")
  field(DO6, "0")
  field(DO7, "0")
  field(DO8, "0")
  field(LNK1, "01G-QSS4:CurrSetpt.DISA PP")
  field(LNK2, "02G-QSS3:CurrSetpt.DISA PP")
  field(LNK3, "03G-QSS3:CurrSetpt.DISA PP")
  field(LNK4, "05G-QSS3:CurrSetpt.DISA PP")
  field(LNK5, "07G-QSS2:CurrSetpt.DISA PP")
  field(LNK6, "08G-QSS2:CurrSetpt.DISA PP")
  field(LNK7, "09G-QSS1:CurrSetpt.DISA PP")
  field(LNK8, "04G-QSS3:CurrSetpt.DISA PP")
  field(FLNK, "$(crate):CurrSetptRestore")
}

record(seq, "$(crate):CurrSetptRestore") {
  field(DESC, "Restore all Ch Curr Setpts")
  field(ASG,  "Internal")  
  field(DOL1, "01G-QSS4:CurrSetptLatch PP")
  field(DOL2, "02G-QSS3:CurrSetptLatch PP")
  field(DOL3, "03G-QSS3:CurrSetptLatch PP")
  field(DOL4, "05G-QSS3:CurrSetptLatch PP")
  field(DOL5, "07G-QSS2:CurrSetptLatch PP")
  field(DOL6, "08G-QSS2:CurrSetptLatch PP")
  field(DOL7, "09G-QSS1:CurrSetptLatch PP")
  field(DOL8, "04G-QSS3:CurrSetptLatch PP")  
  field(LNK1, "01G-QSS4:CurrSetpt PP")
  field(LNK2, "02G-QSS3:CurrSetpt PP")
  field(LNK3, "03G-QSS3:CurrSetpt PP")
  field(LNK4, "05G-QSS3:CurrSetpt PP")
  field(LNK5, "07G-QSS2:CurrSetpt PP")
  field(LNK6, "08G-QSS2:CurrSetpt PP")
  field(LNK7, "09G-QSS1:CurrSetpt PP")
  field(LNK8, "04G-QSS3:CurrSetpt PP")
  field(FLNK, "$(crate):CurrSetptLatchEnable")  
}

record(seq, "$(crate):CurrSetptLatchEnable") {
  field(DESC, "Enable Ch Latch Setpts")
  field(ASG,  "Internal")   
  field(DO1, "0")
  field(DO2, "0")
  field(DO3, "0")
  field(DO4, "0")
  field(DO5, "0")
  field(DO6, "0")
  field(DO7, "0")
  field(DO8, "0")
  field(LNK1, "01G-QSS4:CurrSetptLatch.DISA PP")
  field(LNK2, "02G-QSS3:CurrSetptLatch.DISA PP")
  field(LNK3, "03G-QSS3:CurrSetptLatch.DISA PP")
  field(LNK4, "05G-QSS3:CurrSetptLatch.DISA PP")
  field(LNK5, "07G-QSS2:CurrSetptLatch.DISA PP")
  field(LNK6, "08G-QSS2:CurrSetptLatch.DISA PP")
  field(LNK7, "09G-QSS1:CurrSetptLatch.DISA PP")
  field(LNK8, "04G-QSS3:CurrSetptLatch.DISA PP")
}