Date: Fri, 18 Oct 2013 11:14:57 -0700 (PDT) From: Sonya Hoobler To: Alex Wallace Subject: Re: AMO MPS Update Hi Alex, Since these may be used again, I think I will only remove the link node channels that are being replaced: High End Field Physics Chamber Gate Valve Summary LN 39 Card 1 Ch 9-10 AMO_HFP_VGC_02A AMO_HFP_VGC_02B Thanks again, Sonya On Fri, 18 Oct 2013, Alex Wallace wrote: > Hi Sonya, > > Good question. It is likely AMO will use these inputs again at some point, but to keep things simple can we add them back when > needed? So far as I understand it, they will not need them for a while. > > Best, > -Alex > > > On 10/18/13 10:07, Sonya Hoobler wrote: > > Hi Alex, > > > > Just want to confirm: > > > > For NEH AMO Diagnostics Chamber Gate Valve and NEH AMO End Station Ready, > > do you want to remove the link node inputs for these as well as the MPS > > logic for them (i.e. they will never be used again)? > > > > Thanks, > > Sonya Date: Tue, 15 Oct 2013 08:39:43 -0700 From: Alex Wallace To: Sonya Hoobler Subject: Re: AMO MPS Update Parts/Attachments: 1.1 Shown 72 lines Text 1.2 OK 123 lines Text 2 1.2 KB Application 3 456 bytes Application ---------------------------------------- Hi Sonya, Here's the scoop: Please remove the following from MPS: NEH AMO Diagnostics Chamber Gate Valve: Open NEH AMO Diagnostics Chamber Gate Valve: Closed NEH AMO HFP Beam Stop: Fully In NEH AMO HFP Beam Stop: Fully Out Please remove the HFP:MPA:STP:02 as a veto device (and a device all together). Please remove all faults vetoed by this device. So basically all of section 22 from revision 2012-09-26-a (here ) Attached are some json files for the new faults and devices. Hopefully they were done correctly. I do this so infrequently I am sorry to say I often forget how to write them. I need a better example for my notes :). Thanks and best regards, -Alex [sonya@lcls-dev2 algorithm]$ sdiff -bs 2013-10-10-a/doc/MPSLogicDocumentation.txt 2013-10-15-a/doc/MPSLogicDocumentation.txt .. title:: MPS Logic 2013-10-10-a | .. title:: MPS Logic 2013-10-15-a Ignored when ST1/ST2 Are In, Stopper HFP-MPA-02 Is In, Stoppe | Ignored when ST1/ST2 Are In, Stopper S1 Is In, Stopper: BSY D ============================================================= | ============================================================= < NEH AMO Diagnostics Chamber Gate Valve Summary < ---------------------------------------------- < ====== = = ==================== ==================== ======== < Name B A Pockels Cell Mechanical Shutter B < ====== = = ==================== ==================== ======== < Moving F F 0 Hz 0 Hz < Closed F T 0 Hz 0 Hz < Open T F 120 Hz 120 Hz < Broken T T 0 Hz 0 Hz < ====== = = ==================== ==================== ======== < < Where:: < < A = AMO_DIA_VGC_02A_POSITION < B = AMO_DIA_VGC_02B_POSITION < < < NEH AMO End Station Ready < ------------------------- < ========= = ==================== ==================== ======= < Name A Pockels Cell Mechanical Shutter < ========= = ==================== ==================== ======= < NOT_READY F 0 Hz 0 Hz < READY T 120 Hz 120 Hz < ========= = ==================== ==================== ======= < < Where:: < < A = AMO_EXP_MPS_01_STATE < | NEH AMO LAMP VGC 30 Position NEH AMO High Field Physics Chamber Gate Valve Summary | ---------------------------- ----------------------------------------------------- < Moving F F 0 Hz 0 Hz | Moving F F 0 Hz 0 Hz Closed F T 0 Hz 0 Hz | In F T 120 Hz 120 Hz Open T F 120 Hz 120 Hz | Out T F 120 Hz 120 Hz Broken T T 0 Hz 0 Hz | Broken T T 0 Hz 0 Hz A = AMO_HFP_VGC_02A_POSITION | A = AMO_LMP_VGC_30_CLS_DI_POSITION B = AMO_HFP_VGC_02B_POSITION | B = AMO_LMP_VGC_30_OPN_DI_POSITION > NEH AMO LAMP VGC 30 Is In Beam > ------------------------------ > ======= = ==================== ==================== ========= > Name A Pockels Cell Mechanical Shutter BY > ======= = ==================== ==================== ========= > In beam T -- -- > ======= = ==================== ==================== ========= > > Where:: > > A = AMO_LMP_VGC_30_CLS_DI_POSITION > > > NEH AMO LAMP VGC 30 Is Out of Beam > ---------------------------------- > =========== = ==================== ==================== ===== > Name A Pockels Cell Mechanical Shutter > =========== = ==================== ==================== ===== > Out of beam T -- -- > =========== = ==================== ==================== ===== > > Where:: > > A = AMO_LMP_VGC_30_OPN_DI_POSITION > > Stopper HFP-MPA-02 Is In < ------------------------ < ==== = = ==================== ==================== ========== < Name B A Pockels Cell Mechanical Shutter BYK < ==== = = ==================== ==================== ========== < In T F -- -- < ==== = = ==================== ==================== ========== < < Where:: < < A = AMO_HFP_MPA_02B_POSITION < B = AMO_HFP_MPA_02A_POSITION < < <