June 13 2013 Per Cater#108919 Regarding mitigating potential B4C damage while running low energy. In attendance were Rad Physics, Paul Miller, John Arthur, Roger, Jim Turner, and M. Stanek. The interim solution for allowing low energy running without a BAS 2 mJ limit was an agreement that we would not allow photons on the ST0 B4C piece at all. Sayed Rokni accepted that as an interim measure, we would use MPS to ensure this condition. What is need required: If ST1/ST2 = Not OUT, Zero rate fault the Gun. This fault should have an 'ignore condition' when TDUND is in, D2 is in, TD11 is in, BX01/02 is NOT ON, YAG BL211 is IN, BXG is ON. sdiff -stb 2013-06-13-a/doc/MPSLogicDocumentation.txt 2013-06-15-a/doc/MPSLogicDocumentation.txt .. title:: MPS Logic 2013-06-13-a | .. title:: MPS Logic 2013-06-15-a > Stopper: ST1/ST2 Position > ------------------------- > ====== = = ==================== ==================== ========== > Name B A Pockels Cell Mechanical Shutter BYK > ====== = = ==================== ==================== ========== > Moving F F 0 Hz 0 Hz > Out F T 120 Hz 120 Hz > In T F 0 Hz 0 Hz > Broken T T 0 Hz 0 Hz > ====== = = ==================== ==================== ========== > > Where:: > > A = STPR_FEE1_1_ST1ST2OUT_POSITION > B = STPR_FEE1_1_ST1ST2IN_POSITION > > ST1/ST2 Position < ---------------- < ====== = = ==================== ==================== ========== < Name B A Pockels Cell Mechanical Shutter BYK < ====== = = ==================== ==================== ========== < Moving F F 0 Hz 0 Hz < Out F T -- -- < In T F -- -- < Broken T T 0 Hz 0 Hz < ====== = = ==================== ==================== ========== < < Where:: < < A = STPR_FEE1_1_ST1ST2OUT_POSITION < B = STPR_FEE1_1_ST1ST2IN_POSITION < < <