# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN13:BC01:INFO") {
  field(DESC, "SIOC:BPN13:BC01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN13:BC01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Garth Brown (gwbrown)  ")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN13:BC01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN13:BC01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN13:BC01:TODDIFF")
}

record(longin, "SIOC:BPN13:BC01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN13:BC01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN13:BC01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN13:BC01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN13:BC01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN13:BC01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN13:BC01:TODSUM")
}

record(bo, "SIOC:BPN13:BC01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN13:BC01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN13:BC01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN13:BC01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:BC01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN13:BC01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN13:BC01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN13:BC01:HEARTBEATE01")
  field(INP, "SIOC:BPN13:BC01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN13:BC01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN13:BC01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN13:BC01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN13:BC01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN13:BC01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN13:BC01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN13:BC01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN13:BC01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN13:BC01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN13:BC01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN13:BC01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN13:BC01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN13:BC01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN13:BC01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:BC01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN13:BC01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN13:BC01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN13:BC01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:BC01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN13:BC01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN13:BC01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN13:BC01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:BC01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN13:BC01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN13:BC01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN13:BC01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:BC01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN13:BC01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN13:BC01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN13:BC01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:BC01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN13:BC01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN13:BC01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN13:BC01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:BC01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN13:BC01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN13:BC01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN13:BC01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:BC01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN13:BC01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN13:BC01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN13:BC01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:BC01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN13:BC01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN13:BC01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN13:BC01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:BC01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN13:BC01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN13:BC01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN13:BC01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN13:BC01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN13:BC01:HEARTBEATCLC")
  field(INP, "SIOC:BPN13:BC01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN13:BC01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN13:BC01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:BC01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN13:BC01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN13:BC01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN13:BC01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN13:BC01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN13:BC01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN13:BC01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "BCS LBLMs")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN13:BC01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "BCS LBLMs")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN13:BC01:LOC") {
  field(PINI, "YES")
  field(VAL, "lcls-daemon1")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN14:BC01:INFO") {
  field(DESC, "SIOC:BPN14:BC01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN14:BC01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Mike Dunning (mdunning)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN14:BC01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN14:BC01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN14:BC01:TODDIFF")
}

record(longin, "SIOC:BPN14:BC01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN14:BC01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN14:BC01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN14:BC01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN14:BC01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN14:BC01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN14:BC01:TODSUM")
}

record(bo, "SIOC:BPN14:BC01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN14:BC01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN14:BC01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN14:BC01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:BC01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN14:BC01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN14:BC01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN14:BC01:HEARTBEATE01")
  field(INP, "SIOC:BPN14:BC01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN14:BC01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN14:BC01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN14:BC01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN14:BC01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN14:BC01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN14:BC01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN14:BC01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN14:BC01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN14:BC01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN14:BC01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN14:BC01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN14:BC01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN14:BC01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN14:BC01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:BC01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN14:BC01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN14:BC01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN14:BC01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:BC01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN14:BC01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN14:BC01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN14:BC01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:BC01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN14:BC01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN14:BC01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN14:BC01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:BC01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN14:BC01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN14:BC01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN14:BC01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:BC01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN14:BC01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN14:BC01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN14:BC01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:BC01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN14:BC01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN14:BC01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN14:BC01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:BC01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN14:BC01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN14:BC01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN14:BC01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:BC01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN14:BC01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN14:BC01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN14:BC01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:BC01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN14:BC01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN14:BC01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN14:BC01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN14:BC01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN14:BC01:HEARTBEATCLC")
  field(INP, "SIOC:BPN14:BC01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN14:BC01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN14:BC01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:BC01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN14:BC01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN14:BC01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN14:BC01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN14:BC01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN14:BC01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN14:BC01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "BCS DSC")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN14:BC01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "BCS DSC")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN14:BC01:LOC") {
  field(PINI, "YES")
  field(VAL, "lcls-daemon0")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN20:BC01:INFO") {
  field(DESC, "SIOC:BPN20:BC01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN20:BC01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Mike Dunning (mdunning)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN20:BC01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN20:BC01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN20:BC01:TODDIFF")
}

record(longin, "SIOC:BPN20:BC01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN20:BC01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN20:BC01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN20:BC01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN20:BC01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN20:BC01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN20:BC01:TODSUM")
}

record(bo, "SIOC:BPN20:BC01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN20:BC01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN20:BC01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN20:BC01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN20:BC01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN20:BC01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN20:BC01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN20:BC01:HEARTBEATE01")
  field(INP, "SIOC:BPN20:BC01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN20:BC01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN20:BC01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN20:BC01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN20:BC01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN20:BC01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN20:BC01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN20:BC01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN20:BC01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN20:BC01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN20:BC01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN20:BC01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN20:BC01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN20:BC01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN20:BC01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN20:BC01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN20:BC01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN20:BC01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN20:BC01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN20:BC01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN20:BC01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN20:BC01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN20:BC01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN20:BC01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN20:BC01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN20:BC01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN20:BC01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN20:BC01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN20:BC01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN20:BC01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN20:BC01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN20:BC01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN20:BC01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN20:BC01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN20:BC01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN20:BC01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN20:BC01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN20:BC01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN20:BC01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN20:BC01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN20:BC01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN20:BC01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN20:BC01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN20:BC01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN20:BC01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN20:BC01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN20:BC01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN20:BC01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN20:BC01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN20:BC01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN20:BC01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN20:BC01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN20:BC01:HEARTBEATCLC")
  field(INP, "SIOC:BPN20:BC01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN20:BC01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN20:BC01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN20:BC01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN20:BC01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN20:BC01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN20:BC01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN20:BC01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN20:BC01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN20:BC01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "BCS DSC")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN20:BC01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "BCS DSC")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN20:BC01:LOC") {
  field(PINI, "YES")
  field(VAL, "lcls-daemon0")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN26:BC01:INFO") {
  field(DESC, "SIOC:BPN26:BC01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN26:BC01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Mike Dunning (mdunning)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN26:BC01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN26:BC01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN26:BC01:TODDIFF")
}

record(longin, "SIOC:BPN26:BC01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN26:BC01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN26:BC01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN26:BC01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN26:BC01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN26:BC01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN26:BC01:TODSUM")
}

record(bo, "SIOC:BPN26:BC01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN26:BC01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN26:BC01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN26:BC01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN26:BC01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN26:BC01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN26:BC01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN26:BC01:HEARTBEATE01")
  field(INP, "SIOC:BPN26:BC01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN26:BC01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN26:BC01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN26:BC01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN26:BC01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN26:BC01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN26:BC01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN26:BC01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN26:BC01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN26:BC01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN26:BC01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN26:BC01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN26:BC01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN26:BC01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN26:BC01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN26:BC01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN26:BC01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN26:BC01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN26:BC01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN26:BC01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN26:BC01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN26:BC01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN26:BC01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN26:BC01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN26:BC01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN26:BC01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN26:BC01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN26:BC01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN26:BC01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN26:BC01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN26:BC01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN26:BC01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN26:BC01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN26:BC01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN26:BC01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN26:BC01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN26:BC01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN26:BC01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN26:BC01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN26:BC01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN26:BC01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN26:BC01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN26:BC01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN26:BC01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN26:BC01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN26:BC01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN26:BC01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN26:BC01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN26:BC01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN26:BC01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN26:BC01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN26:BC01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN26:BC01:HEARTBEATCLC")
  field(INP, "SIOC:BPN26:BC01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN26:BC01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN26:BC01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN26:BC01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN26:BC01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN26:BC01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN26:BC01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN26:BC01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN26:BC01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN26:BC01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "BCS DSC")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN26:BC01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "BCS DSC")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN26:BC01:LOC") {
  field(PINI, "YES")
  field(VAL, "lcls-daemon0")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN13:BP01:INFO") {
  field(DESC, "SIOC:BPN13:BP01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN13:BP01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Sonya Hoobler (sonya)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN13:BP01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN13:BP01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN13:BP01:TODDIFF")
}

record(longin, "SIOC:BPN13:BP01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN13:BP01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN13:BP01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN13:BP01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN13:BP01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN13:BP01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN13:BP01:TODSUM")
}

record(bo, "SIOC:BPN13:BP01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN13:BP01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN13:BP01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN13:BP01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:BP01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN13:BP01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN13:BP01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN13:BP01:HEARTBEATE01")
  field(INP, "SIOC:BPN13:BP01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN13:BP01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN13:BP01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN13:BP01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN13:BP01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN13:BP01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN13:BP01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN13:BP01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN13:BP01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN13:BP01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN13:BP01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN13:BP01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN13:BP01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN13:BP01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN13:BP01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:BP01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN13:BP01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN13:BP01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN13:BP01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:BP01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN13:BP01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN13:BP01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN13:BP01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:BP01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN13:BP01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN13:BP01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN13:BP01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:BP01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN13:BP01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN13:BP01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN13:BP01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:BP01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN13:BP01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN13:BP01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN13:BP01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:BP01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN13:BP01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN13:BP01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN13:BP01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:BP01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN13:BP01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN13:BP01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN13:BP01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:BP01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN13:BP01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN13:BP01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN13:BP01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:BP01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN13:BP01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN13:BP01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN13:BP01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN13:BP01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN13:BP01:HEARTBEATCLC")
  field(INP, "SIOC:BPN13:BP01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN13:BP01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN13:BP01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:BP01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN13:BP01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN13:BP01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN13:BP01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN13:BP01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN13:BP01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN13:BP01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "BPN13 400")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN13:BP01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "BPN13 400")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN13:BP01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn13-sp01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN14:BP01:INFO") {
  field(DESC, "SIOC:BPN14:BP01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN14:BP01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Sonya Hoobler (sonya)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN14:BP01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN14:BP01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN14:BP01:TODDIFF")
}

record(longin, "SIOC:BPN14:BP01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN14:BP01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN14:BP01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN14:BP01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN14:BP01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN14:BP01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN14:BP01:TODSUM")
}

record(bo, "SIOC:BPN14:BP01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN14:BP01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN14:BP01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN14:BP01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:BP01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN14:BP01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN14:BP01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN14:BP01:HEARTBEATE01")
  field(INP, "SIOC:BPN14:BP01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN14:BP01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN14:BP01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN14:BP01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN14:BP01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN14:BP01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN14:BP01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN14:BP01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN14:BP01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN14:BP01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN14:BP01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN14:BP01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN14:BP01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN14:BP01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN14:BP01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:BP01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN14:BP01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN14:BP01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN14:BP01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:BP01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN14:BP01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN14:BP01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN14:BP01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:BP01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN14:BP01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN14:BP01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN14:BP01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:BP01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN14:BP01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN14:BP01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN14:BP01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:BP01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN14:BP01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN14:BP01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN14:BP01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:BP01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN14:BP01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN14:BP01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN14:BP01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:BP01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN14:BP01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN14:BP01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN14:BP01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:BP01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN14:BP01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN14:BP01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN14:BP01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:BP01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN14:BP01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN14:BP01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN14:BP01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN14:BP01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN14:BP01:HEARTBEATCLC")
  field(INP, "SIOC:BPN14:BP01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN14:BP01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN14:BP01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:BP01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN14:BP01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN14:BP01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN14:BP01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN14:BP01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN14:BP01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN14:BP01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "BPN14 400")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN14:BP01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "BPN14 400")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN14:BP01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn14-sp01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN15:BP01:INFO") {
  field(DESC, "SIOC:BPN15:BP01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN15:BP01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Sonya Hoobler (sonya)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN15:BP01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN15:BP01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN15:BP01:TODDIFF")
}

record(longin, "SIOC:BPN15:BP01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN15:BP01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN15:BP01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN15:BP01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN15:BP01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN15:BP01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN15:BP01:TODSUM")
}

record(bo, "SIOC:BPN15:BP01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN15:BP01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN15:BP01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN15:BP01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:BP01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN15:BP01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN15:BP01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN15:BP01:HEARTBEATE01")
  field(INP, "SIOC:BPN15:BP01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN15:BP01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN15:BP01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN15:BP01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN15:BP01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN15:BP01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN15:BP01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN15:BP01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN15:BP01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN15:BP01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN15:BP01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN15:BP01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN15:BP01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN15:BP01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN15:BP01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:BP01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN15:BP01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN15:BP01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN15:BP01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:BP01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN15:BP01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN15:BP01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN15:BP01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:BP01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN15:BP01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN15:BP01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN15:BP01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:BP01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN15:BP01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN15:BP01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN15:BP01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:BP01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN15:BP01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN15:BP01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN15:BP01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:BP01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN15:BP01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN15:BP01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN15:BP01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:BP01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN15:BP01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN15:BP01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN15:BP01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:BP01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN15:BP01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN15:BP01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN15:BP01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:BP01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN15:BP01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN15:BP01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN15:BP01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN15:BP01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN15:BP01:HEARTBEATCLC")
  field(INP, "SIOC:BPN15:BP01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN15:BP01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN15:BP01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:BP01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN15:BP01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN15:BP01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN15:BP01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN15:BP01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN15:BP01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN15:BP01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "BPN15 400")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN15:BP01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "BPN15 400")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN15:BP01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn15-sp01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN16:BP01:INFO") {
  field(DESC, "SIOC:BPN16:BP01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN16:BP01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Sonya Hoobler (sonya)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN16:BP01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN16:BP01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN16:BP01:TODDIFF")
}

record(longin, "SIOC:BPN16:BP01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN16:BP01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN16:BP01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN16:BP01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN16:BP01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN16:BP01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN16:BP01:TODSUM")
}

record(bo, "SIOC:BPN16:BP01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN16:BP01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN16:BP01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN16:BP01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:BP01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN16:BP01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN16:BP01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN16:BP01:HEARTBEATE01")
  field(INP, "SIOC:BPN16:BP01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN16:BP01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN16:BP01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN16:BP01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN16:BP01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN16:BP01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN16:BP01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN16:BP01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN16:BP01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN16:BP01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN16:BP01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN16:BP01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN16:BP01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN16:BP01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN16:BP01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:BP01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN16:BP01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN16:BP01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN16:BP01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:BP01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN16:BP01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN16:BP01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN16:BP01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:BP01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN16:BP01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN16:BP01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN16:BP01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:BP01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN16:BP01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN16:BP01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN16:BP01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:BP01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN16:BP01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN16:BP01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN16:BP01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:BP01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN16:BP01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN16:BP01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN16:BP01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:BP01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN16:BP01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN16:BP01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN16:BP01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:BP01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN16:BP01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN16:BP01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN16:BP01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:BP01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN16:BP01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN16:BP01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN16:BP01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN16:BP01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN16:BP01:HEARTBEATCLC")
  field(INP, "SIOC:BPN16:BP01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN16:BP01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN16:BP01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:BP01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN16:BP01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN16:BP01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN16:BP01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN16:BP01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN16:BP01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN16:BP01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "BPN16 400")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN16:BP01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "BPN16 400")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN16:BP01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn16-sp01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN17:BP01:INFO") {
  field(DESC, "SIOC:BPN17:BP01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN17:BP01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Sonya Hoobler (sonya)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN17:BP01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN17:BP01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN17:BP01:TODDIFF")
}

record(longin, "SIOC:BPN17:BP01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN17:BP01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN17:BP01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN17:BP01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN17:BP01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN17:BP01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN17:BP01:TODSUM")
}

record(bo, "SIOC:BPN17:BP01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN17:BP01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN17:BP01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN17:BP01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:BP01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN17:BP01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN17:BP01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN17:BP01:HEARTBEATE01")
  field(INP, "SIOC:BPN17:BP01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN17:BP01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN17:BP01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN17:BP01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN17:BP01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN17:BP01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN17:BP01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN17:BP01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN17:BP01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN17:BP01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN17:BP01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN17:BP01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN17:BP01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN17:BP01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN17:BP01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:BP01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN17:BP01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN17:BP01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN17:BP01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:BP01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN17:BP01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN17:BP01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN17:BP01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:BP01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN17:BP01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN17:BP01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN17:BP01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:BP01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN17:BP01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN17:BP01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN17:BP01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:BP01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN17:BP01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN17:BP01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN17:BP01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:BP01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN17:BP01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN17:BP01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN17:BP01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:BP01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN17:BP01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN17:BP01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN17:BP01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:BP01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN17:BP01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN17:BP01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN17:BP01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:BP01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN17:BP01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN17:BP01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN17:BP01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN17:BP01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN17:BP01:HEARTBEATCLC")
  field(INP, "SIOC:BPN17:BP01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN17:BP01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN17:BP01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:BP01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN17:BP01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN17:BP01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN17:BP01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN17:BP01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN17:BP01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN17:BP01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "BPN17 400")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN17:BP01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "BPN17 400")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN17:BP01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn17-sp01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN18:BP01:INFO") {
  field(DESC, "SIOC:BPN18:BP01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN18:BP01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Sonya Hoobler (sonya)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN18:BP01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN18:BP01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN18:BP01:TODDIFF")
}

record(longin, "SIOC:BPN18:BP01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN18:BP01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN18:BP01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN18:BP01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN18:BP01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN18:BP01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN18:BP01:TODSUM")
}

record(bo, "SIOC:BPN18:BP01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN18:BP01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN18:BP01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN18:BP01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN18:BP01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN18:BP01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN18:BP01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN18:BP01:HEARTBEATE01")
  field(INP, "SIOC:BPN18:BP01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN18:BP01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN18:BP01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN18:BP01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN18:BP01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN18:BP01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN18:BP01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN18:BP01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN18:BP01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN18:BP01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN18:BP01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN18:BP01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN18:BP01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN18:BP01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN18:BP01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN18:BP01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN18:BP01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN18:BP01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN18:BP01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN18:BP01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN18:BP01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN18:BP01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN18:BP01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN18:BP01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN18:BP01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN18:BP01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN18:BP01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN18:BP01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN18:BP01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN18:BP01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN18:BP01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN18:BP01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN18:BP01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN18:BP01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN18:BP01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN18:BP01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN18:BP01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN18:BP01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN18:BP01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN18:BP01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN18:BP01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN18:BP01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN18:BP01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN18:BP01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN18:BP01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN18:BP01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN18:BP01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN18:BP01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN18:BP01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN18:BP01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN18:BP01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN18:BP01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN18:BP01:HEARTBEATCLC")
  field(INP, "SIOC:BPN18:BP01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN18:BP01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN18:BP01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN18:BP01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN18:BP01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN18:BP01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN18:BP01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN18:BP01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN18:BP01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN18:BP01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "BPN18 400")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN18:BP01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "BPN18 400")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN18:BP01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn18-sp01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN19:BP01:INFO") {
  field(DESC, "SIOC:BPN19:BP01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN19:BP01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Sonya Hoobler (sonya)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN19:BP01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN19:BP01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN19:BP01:TODDIFF")
}

record(longin, "SIOC:BPN19:BP01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN19:BP01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN19:BP01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN19:BP01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN19:BP01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN19:BP01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN19:BP01:TODSUM")
}

record(bo, "SIOC:BPN19:BP01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN19:BP01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN19:BP01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN19:BP01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN19:BP01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN19:BP01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN19:BP01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN19:BP01:HEARTBEATE01")
  field(INP, "SIOC:BPN19:BP01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN19:BP01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN19:BP01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN19:BP01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN19:BP01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN19:BP01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN19:BP01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN19:BP01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN19:BP01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN19:BP01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN19:BP01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN19:BP01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN19:BP01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN19:BP01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN19:BP01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN19:BP01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN19:BP01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN19:BP01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN19:BP01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN19:BP01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN19:BP01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN19:BP01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN19:BP01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN19:BP01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN19:BP01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN19:BP01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN19:BP01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN19:BP01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN19:BP01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN19:BP01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN19:BP01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN19:BP01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN19:BP01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN19:BP01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN19:BP01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN19:BP01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN19:BP01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN19:BP01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN19:BP01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN19:BP01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN19:BP01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN19:BP01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN19:BP01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN19:BP01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN19:BP01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN19:BP01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN19:BP01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN19:BP01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN19:BP01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN19:BP01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN19:BP01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN19:BP01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN19:BP01:HEARTBEATCLC")
  field(INP, "SIOC:BPN19:BP01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN19:BP01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN19:BP01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN19:BP01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN19:BP01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN19:BP01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN19:BP01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN19:BP01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN19:BP01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN19:BP01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "BPN19 400")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN19:BP01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "BPN19 400")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN19:BP01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn19-sp01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN20:BP01:INFO") {
  field(DESC, "SIOC:BPN20:BP01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN20:BP01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Sonya Hoobler (sonya)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN20:BP01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN20:BP01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN20:BP01:TODDIFF")
}

record(longin, "SIOC:BPN20:BP01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN20:BP01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN20:BP01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN20:BP01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN20:BP01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN20:BP01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN20:BP01:TODSUM")
}

record(bo, "SIOC:BPN20:BP01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN20:BP01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN20:BP01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN20:BP01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN20:BP01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN20:BP01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN20:BP01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN20:BP01:HEARTBEATE01")
  field(INP, "SIOC:BPN20:BP01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN20:BP01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN20:BP01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN20:BP01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN20:BP01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN20:BP01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN20:BP01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN20:BP01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN20:BP01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN20:BP01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN20:BP01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN20:BP01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN20:BP01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN20:BP01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN20:BP01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN20:BP01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN20:BP01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN20:BP01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN20:BP01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN20:BP01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN20:BP01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN20:BP01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN20:BP01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN20:BP01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN20:BP01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN20:BP01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN20:BP01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN20:BP01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN20:BP01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN20:BP01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN20:BP01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN20:BP01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN20:BP01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN20:BP01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN20:BP01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN20:BP01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN20:BP01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN20:BP01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN20:BP01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN20:BP01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN20:BP01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN20:BP01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN20:BP01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN20:BP01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN20:BP01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN20:BP01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN20:BP01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN20:BP01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN20:BP01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN20:BP01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN20:BP01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN20:BP01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN20:BP01:HEARTBEATCLC")
  field(INP, "SIOC:BPN20:BP01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN20:BP01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN20:BP01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN20:BP01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN20:BP01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN20:BP01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN20:BP01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN20:BP01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN20:BP01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN20:BP01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "BPN20 400")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN20:BP01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "BPN20 400")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN20:BP01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn20-sp01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN21:BP01:INFO") {
  field(DESC, "SIOC:BPN21:BP01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN21:BP01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Sonya Hoobler (sonya)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN21:BP01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN21:BP01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN21:BP01:TODDIFF")
}

record(longin, "SIOC:BPN21:BP01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN21:BP01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN21:BP01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN21:BP01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN21:BP01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN21:BP01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN21:BP01:TODSUM")
}

record(bo, "SIOC:BPN21:BP01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN21:BP01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN21:BP01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN21:BP01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:BP01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN21:BP01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN21:BP01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN21:BP01:HEARTBEATE01")
  field(INP, "SIOC:BPN21:BP01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN21:BP01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN21:BP01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN21:BP01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN21:BP01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN21:BP01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN21:BP01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN21:BP01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN21:BP01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN21:BP01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN21:BP01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN21:BP01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN21:BP01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN21:BP01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN21:BP01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:BP01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN21:BP01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN21:BP01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN21:BP01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:BP01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN21:BP01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN21:BP01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN21:BP01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:BP01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN21:BP01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN21:BP01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN21:BP01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:BP01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN21:BP01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN21:BP01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN21:BP01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:BP01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN21:BP01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN21:BP01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN21:BP01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:BP01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN21:BP01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN21:BP01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN21:BP01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:BP01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN21:BP01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN21:BP01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN21:BP01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:BP01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN21:BP01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN21:BP01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN21:BP01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:BP01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN21:BP01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN21:BP01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN21:BP01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN21:BP01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN21:BP01:HEARTBEATCLC")
  field(INP, "SIOC:BPN21:BP01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN21:BP01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN21:BP01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:BP01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN21:BP01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN21:BP01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN21:BP01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN21:BP01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN21:BP01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN21:BP01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "BPN21 400")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN21:BP01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "BPN21 400")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN21:BP01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn21-sp01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN22:BP01:INFO") {
  field(DESC, "SIOC:BPN22:BP01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN22:BP01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Sonya Hoobler (sonya)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN22:BP01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN22:BP01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN22:BP01:TODDIFF")
}

record(longin, "SIOC:BPN22:BP01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN22:BP01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN22:BP01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN22:BP01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN22:BP01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN22:BP01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN22:BP01:TODSUM")
}

record(bo, "SIOC:BPN22:BP01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN22:BP01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN22:BP01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN22:BP01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN22:BP01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN22:BP01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN22:BP01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN22:BP01:HEARTBEATE01")
  field(INP, "SIOC:BPN22:BP01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN22:BP01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN22:BP01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN22:BP01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN22:BP01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN22:BP01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN22:BP01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN22:BP01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN22:BP01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN22:BP01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN22:BP01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN22:BP01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN22:BP01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN22:BP01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN22:BP01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN22:BP01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN22:BP01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN22:BP01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN22:BP01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN22:BP01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN22:BP01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN22:BP01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN22:BP01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN22:BP01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN22:BP01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN22:BP01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN22:BP01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN22:BP01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN22:BP01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN22:BP01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN22:BP01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN22:BP01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN22:BP01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN22:BP01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN22:BP01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN22:BP01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN22:BP01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN22:BP01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN22:BP01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN22:BP01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN22:BP01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN22:BP01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN22:BP01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN22:BP01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN22:BP01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN22:BP01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN22:BP01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN22:BP01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN22:BP01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN22:BP01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN22:BP01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN22:BP01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN22:BP01:HEARTBEATCLC")
  field(INP, "SIOC:BPN22:BP01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN22:BP01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN22:BP01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN22:BP01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN22:BP01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN22:BP01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN22:BP01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN22:BP01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN22:BP01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN22:BP01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "BPN22 400")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN22:BP01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "BPN22 400")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN22:BP01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn22-sp01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN23:BP01:INFO") {
  field(DESC, "SIOC:BPN23:BP01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN23:BP01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Sonya Hoobler (sonya)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN23:BP01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN23:BP01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN23:BP01:TODDIFF")
}

record(longin, "SIOC:BPN23:BP01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN23:BP01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN23:BP01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN23:BP01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN23:BP01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN23:BP01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN23:BP01:TODSUM")
}

record(bo, "SIOC:BPN23:BP01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN23:BP01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN23:BP01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN23:BP01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN23:BP01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN23:BP01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN23:BP01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN23:BP01:HEARTBEATE01")
  field(INP, "SIOC:BPN23:BP01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN23:BP01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN23:BP01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN23:BP01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN23:BP01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN23:BP01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN23:BP01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN23:BP01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN23:BP01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN23:BP01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN23:BP01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN23:BP01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN23:BP01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN23:BP01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN23:BP01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN23:BP01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN23:BP01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN23:BP01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN23:BP01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN23:BP01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN23:BP01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN23:BP01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN23:BP01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN23:BP01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN23:BP01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN23:BP01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN23:BP01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN23:BP01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN23:BP01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN23:BP01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN23:BP01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN23:BP01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN23:BP01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN23:BP01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN23:BP01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN23:BP01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN23:BP01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN23:BP01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN23:BP01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN23:BP01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN23:BP01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN23:BP01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN23:BP01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN23:BP01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN23:BP01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN23:BP01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN23:BP01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN23:BP01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN23:BP01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN23:BP01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN23:BP01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN23:BP01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN23:BP01:HEARTBEATCLC")
  field(INP, "SIOC:BPN23:BP01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN23:BP01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN23:BP01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN23:BP01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN23:BP01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN23:BP01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN23:BP01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN23:BP01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN23:BP01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN23:BP01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "BPN23 400")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN23:BP01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "BPN23 400")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN23:BP01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn23-sp01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN24:BP01:INFO") {
  field(DESC, "SIOC:BPN24:BP01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN24:BP01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Sonya Hoobler (sonya)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN24:BP01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN24:BP01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN24:BP01:TODDIFF")
}

record(longin, "SIOC:BPN24:BP01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN24:BP01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN24:BP01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN24:BP01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN24:BP01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN24:BP01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN24:BP01:TODSUM")
}

record(bo, "SIOC:BPN24:BP01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN24:BP01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN24:BP01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN24:BP01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN24:BP01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN24:BP01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN24:BP01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN24:BP01:HEARTBEATE01")
  field(INP, "SIOC:BPN24:BP01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN24:BP01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN24:BP01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN24:BP01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN24:BP01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN24:BP01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN24:BP01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN24:BP01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN24:BP01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN24:BP01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN24:BP01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN24:BP01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN24:BP01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN24:BP01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN24:BP01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN24:BP01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN24:BP01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN24:BP01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN24:BP01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN24:BP01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN24:BP01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN24:BP01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN24:BP01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN24:BP01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN24:BP01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN24:BP01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN24:BP01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN24:BP01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN24:BP01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN24:BP01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN24:BP01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN24:BP01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN24:BP01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN24:BP01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN24:BP01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN24:BP01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN24:BP01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN24:BP01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN24:BP01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN24:BP01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN24:BP01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN24:BP01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN24:BP01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN24:BP01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN24:BP01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN24:BP01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN24:BP01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN24:BP01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN24:BP01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN24:BP01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN24:BP01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN24:BP01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN24:BP01:HEARTBEATCLC")
  field(INP, "SIOC:BPN24:BP01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN24:BP01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN24:BP01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN24:BP01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN24:BP01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN24:BP01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN24:BP01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN24:BP01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN24:BP01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN24:BP01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "BPN24 400")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN24:BP01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "BPN24 400")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN24:BP01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn24-sp01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN25:BP01:INFO") {
  field(DESC, "SIOC:BPN25:BP01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN25:BP01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Sonya Hoobler (sonya)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN25:BP01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN25:BP01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN25:BP01:TODDIFF")
}

record(longin, "SIOC:BPN25:BP01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN25:BP01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN25:BP01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN25:BP01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN25:BP01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN25:BP01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN25:BP01:TODSUM")
}

record(bo, "SIOC:BPN25:BP01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN25:BP01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN25:BP01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN25:BP01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN25:BP01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN25:BP01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN25:BP01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN25:BP01:HEARTBEATE01")
  field(INP, "SIOC:BPN25:BP01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN25:BP01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN25:BP01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN25:BP01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN25:BP01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN25:BP01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN25:BP01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN25:BP01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN25:BP01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN25:BP01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN25:BP01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN25:BP01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN25:BP01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN25:BP01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN25:BP01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN25:BP01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN25:BP01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN25:BP01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN25:BP01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN25:BP01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN25:BP01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN25:BP01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN25:BP01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN25:BP01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN25:BP01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN25:BP01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN25:BP01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN25:BP01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN25:BP01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN25:BP01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN25:BP01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN25:BP01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN25:BP01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN25:BP01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN25:BP01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN25:BP01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN25:BP01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN25:BP01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN25:BP01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN25:BP01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN25:BP01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN25:BP01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN25:BP01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN25:BP01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN25:BP01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN25:BP01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN25:BP01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN25:BP01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN25:BP01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN25:BP01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN25:BP01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN25:BP01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN25:BP01:HEARTBEATCLC")
  field(INP, "SIOC:BPN25:BP01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN25:BP01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN25:BP01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN25:BP01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN25:BP01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN25:BP01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN25:BP01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN25:BP01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN25:BP01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN25:BP01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "BPN25 400")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN25:BP01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "BPN25 400")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN25:BP01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn25-sp01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN26:BP01:INFO") {
  field(DESC, "SIOC:BPN26:BP01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN26:BP01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Sonya Hoobler (sonya)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN26:BP01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN26:BP01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN26:BP01:TODDIFF")
}

record(longin, "SIOC:BPN26:BP01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN26:BP01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN26:BP01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN26:BP01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN26:BP01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN26:BP01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN26:BP01:TODSUM")
}

record(bo, "SIOC:BPN26:BP01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN26:BP01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN26:BP01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN26:BP01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN26:BP01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN26:BP01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN26:BP01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN26:BP01:HEARTBEATE01")
  field(INP, "SIOC:BPN26:BP01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN26:BP01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN26:BP01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN26:BP01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN26:BP01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN26:BP01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN26:BP01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN26:BP01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN26:BP01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN26:BP01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN26:BP01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN26:BP01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN26:BP01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN26:BP01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN26:BP01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN26:BP01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN26:BP01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN26:BP01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN26:BP01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN26:BP01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN26:BP01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN26:BP01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN26:BP01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN26:BP01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN26:BP01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN26:BP01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN26:BP01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN26:BP01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN26:BP01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN26:BP01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN26:BP01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN26:BP01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN26:BP01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN26:BP01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN26:BP01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN26:BP01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN26:BP01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN26:BP01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN26:BP01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN26:BP01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN26:BP01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN26:BP01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN26:BP01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN26:BP01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN26:BP01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN26:BP01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN26:BP01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN26:BP01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN26:BP01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN26:BP01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN26:BP01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN26:BP01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN26:BP01:HEARTBEATCLC")
  field(INP, "SIOC:BPN26:BP01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN26:BP01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN26:BP01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN26:BP01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN26:BP01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN26:BP01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN26:BP01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN26:BP01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN26:BP01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN26:BP01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "BPN26 400")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN26:BP01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "BPN26 400")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN26:BP01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn26-sp01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN27:BP01:INFO") {
  field(DESC, "SIOC:BPN27:BP01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN27:BP01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Sonya Hoobler (sonya)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN27:BP01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN27:BP01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN27:BP01:TODDIFF")
}

record(longin, "SIOC:BPN27:BP01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN27:BP01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN27:BP01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN27:BP01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN27:BP01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN27:BP01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN27:BP01:TODSUM")
}

record(bo, "SIOC:BPN27:BP01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN27:BP01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN27:BP01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN27:BP01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN27:BP01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN27:BP01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN27:BP01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN27:BP01:HEARTBEATE01")
  field(INP, "SIOC:BPN27:BP01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN27:BP01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN27:BP01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN27:BP01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN27:BP01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN27:BP01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN27:BP01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN27:BP01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN27:BP01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN27:BP01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN27:BP01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN27:BP01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN27:BP01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN27:BP01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN27:BP01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN27:BP01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN27:BP01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN27:BP01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN27:BP01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN27:BP01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN27:BP01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN27:BP01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN27:BP01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN27:BP01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN27:BP01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN27:BP01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN27:BP01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN27:BP01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN27:BP01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN27:BP01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN27:BP01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN27:BP01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN27:BP01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN27:BP01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN27:BP01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN27:BP01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN27:BP01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN27:BP01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN27:BP01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN27:BP01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN27:BP01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN27:BP01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN27:BP01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN27:BP01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN27:BP01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN27:BP01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN27:BP01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN27:BP01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN27:BP01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN27:BP01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN27:BP01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN27:BP01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN27:BP01:HEARTBEATCLC")
  field(INP, "SIOC:BPN27:BP01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN27:BP01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN27:BP01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN27:BP01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN27:BP01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN27:BP01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN27:BP01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN27:BP01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN27:BP01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN27:BP01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "BPN27 400")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN27:BP01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "BPN27 400")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN27:BP01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn27-sp01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN28:BP01:INFO") {
  field(DESC, "SIOC:BPN28:BP01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN28:BP01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Sonya Hoobler (sonya)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN28:BP01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN28:BP01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN28:BP01:TODDIFF")
}

record(longin, "SIOC:BPN28:BP01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN28:BP01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN28:BP01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN28:BP01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN28:BP01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN28:BP01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN28:BP01:TODSUM")
}

record(bo, "SIOC:BPN28:BP01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN28:BP01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN28:BP01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN28:BP01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN28:BP01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN28:BP01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN28:BP01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN28:BP01:HEARTBEATE01")
  field(INP, "SIOC:BPN28:BP01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN28:BP01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN28:BP01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN28:BP01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN28:BP01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN28:BP01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN28:BP01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN28:BP01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN28:BP01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN28:BP01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN28:BP01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN28:BP01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN28:BP01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN28:BP01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN28:BP01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN28:BP01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN28:BP01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN28:BP01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN28:BP01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN28:BP01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN28:BP01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN28:BP01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN28:BP01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN28:BP01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN28:BP01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN28:BP01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN28:BP01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN28:BP01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN28:BP01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN28:BP01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN28:BP01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN28:BP01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN28:BP01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN28:BP01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN28:BP01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN28:BP01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN28:BP01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN28:BP01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN28:BP01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN28:BP01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN28:BP01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN28:BP01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN28:BP01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN28:BP01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN28:BP01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN28:BP01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN28:BP01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN28:BP01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN28:BP01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN28:BP01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN28:BP01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN28:BP01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN28:BP01:HEARTBEATCLC")
  field(INP, "SIOC:BPN28:BP01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN28:BP01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN28:BP01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN28:BP01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN28:BP01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN28:BP01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN28:BP01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN28:BP01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN28:BP01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN28:BP01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "BPN28 200,400")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN28:BP01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "BPN28 200,400")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN28:BP01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn28-sp01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN28:BP99:INFO") {
  field(DESC, "SIOC:BPN28:BP99 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN28:BP99:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Sonya Hoobler (sonya)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN28:BP99:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN28:BP99:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN28:BP99:TODDIFF")
}

record(longin, "SIOC:BPN28:BP99:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN28:BP99:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN28:BP99:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN28:BP99:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN28:BP99:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN28:BP99:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN28:BP99:TODSUM")
}

record(bo, "SIOC:BPN28:BP99:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN28:BP99:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN28:BP99:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN28:BP99:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN28:BP99:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN28:BP99:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN28:BP99:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN28:BP99:HEARTBEATE01")
  field(INP, "SIOC:BPN28:BP99:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN28:BP99:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN28:BP99:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN28:BP99:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN28:BP99:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN28:BP99:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN28:BP99:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN28:BP99:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN28:BP99:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN28:BP99:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN28:BP99:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN28:BP99:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN28:BP99:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN28:BP99:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN28:BP99:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN28:BP99:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN28:BP99:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN28:BP99:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN28:BP99:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN28:BP99:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN28:BP99:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN28:BP99:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN28:BP99:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN28:BP99:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN28:BP99:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN28:BP99:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN28:BP99:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN28:BP99:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN28:BP99:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN28:BP99:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN28:BP99:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN28:BP99:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN28:BP99:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN28:BP99:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN28:BP99:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN28:BP99:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN28:BP99:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN28:BP99:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN28:BP99:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN28:BP99:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN28:BP99:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN28:BP99:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN28:BP99:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN28:BP99:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN28:BP99:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN28:BP99:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN28:BP99:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN28:BP99:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN28:BP99:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN28:BP99:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN28:BP99:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN28:BP99:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN28:BP99:HEARTBEATCLC")
  field(INP, "SIOC:BPN28:BP99:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN28:BP99:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN28:BP99:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN28:BP99:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN28:BP99:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN28:BP99:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN28:BP99:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN28:BP99:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN28:BP99:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN28:BP99:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "BPM test stand")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN28:BP99:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "BPM test stand")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN28:BP99:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn28-sp02")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN17:MG01:INFO") {
  field(DESC, "SIOC:BPN17:MG01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN17:MG01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "An Le (anle)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN17:MG01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN17:MG01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN17:MG01:TODDIFF")
}

record(longin, "SIOC:BPN17:MG01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN17:MG01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN17:MG01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN17:MG01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN17:MG01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN17:MG01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN17:MG01:TODSUM")
}

record(bo, "SIOC:BPN17:MG01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN17:MG01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN17:MG01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN17:MG01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:MG01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN17:MG01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN17:MG01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN17:MG01:HEARTBEATE01")
  field(INP, "SIOC:BPN17:MG01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN17:MG01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN17:MG01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN17:MG01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN17:MG01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN17:MG01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN17:MG01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN17:MG01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN17:MG01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN17:MG01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN17:MG01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN17:MG01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN17:MG01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN17:MG01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN17:MG01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:MG01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN17:MG01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN17:MG01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN17:MG01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:MG01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN17:MG01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN17:MG01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN17:MG01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:MG01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN17:MG01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN17:MG01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN17:MG01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:MG01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN17:MG01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN17:MG01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN17:MG01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:MG01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN17:MG01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN17:MG01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN17:MG01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:MG01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN17:MG01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN17:MG01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN17:MG01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:MG01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN17:MG01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN17:MG01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN17:MG01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:MG01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN17:MG01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN17:MG01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN17:MG01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:MG01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN17:MG01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN17:MG01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN17:MG01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN17:MG01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN17:MG01:HEARTBEATCLC")
  field(INP, "SIOC:BPN17:MG01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN17:MG01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN17:MG01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:MG01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN17:MG01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN17:MG01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN17:MG01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN17:MG01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN17:MG01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN17:MG01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "L2KG18-5112")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN17:MG01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "L2KG18-5112")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN17:MG01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn17-mg01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN21:MG01:INFO") {
  field(DESC, "SIOC:BPN21:MG01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN21:MG01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "An Le (anle)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN21:MG01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN21:MG01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN21:MG01:TODDIFF")
}

record(longin, "SIOC:BPN21:MG01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN21:MG01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN21:MG01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN21:MG01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN21:MG01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN21:MG01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN21:MG01:TODSUM")
}

record(bo, "SIOC:BPN21:MG01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN21:MG01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN21:MG01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN21:MG01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:MG01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN21:MG01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN21:MG01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN21:MG01:HEARTBEATE01")
  field(INP, "SIOC:BPN21:MG01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN21:MG01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN21:MG01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN21:MG01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN21:MG01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN21:MG01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN21:MG01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN21:MG01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN21:MG01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN21:MG01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN21:MG01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN21:MG01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN21:MG01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN21:MG01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN21:MG01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:MG01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN21:MG01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN21:MG01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN21:MG01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:MG01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN21:MG01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN21:MG01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN21:MG01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:MG01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN21:MG01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN21:MG01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN21:MG01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:MG01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN21:MG01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN21:MG01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN21:MG01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:MG01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN21:MG01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN21:MG01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN21:MG01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:MG01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN21:MG01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN21:MG01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN21:MG01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:MG01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN21:MG01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN21:MG01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN21:MG01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:MG01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN21:MG01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN21:MG01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN21:MG01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:MG01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN21:MG01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN21:MG01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN21:MG01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN21:MG01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN21:MG01:HEARTBEATCLC")
  field(INP, "SIOC:BPN21:MG01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN21:MG01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN21:MG01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:MG01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN21:MG01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN21:MG01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN21:MG01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN21:MG01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN21:MG01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN21:MG01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "L2KG22-5112")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN21:MG01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "L2KG22-5112")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN21:MG01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn21-mg01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN25:MG01:INFO") {
  field(DESC, "SIOC:BPN25:MG01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN25:MG01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "An Le (anle)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN25:MG01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN25:MG01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN25:MG01:TODDIFF")
}

record(longin, "SIOC:BPN25:MG01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN25:MG01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN25:MG01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN25:MG01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN25:MG01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN25:MG01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN25:MG01:TODSUM")
}

record(bo, "SIOC:BPN25:MG01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN25:MG01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN25:MG01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN25:MG01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN25:MG01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN25:MG01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN25:MG01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN25:MG01:HEARTBEATE01")
  field(INP, "SIOC:BPN25:MG01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN25:MG01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN25:MG01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN25:MG01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN25:MG01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN25:MG01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN25:MG01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN25:MG01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN25:MG01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN25:MG01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN25:MG01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN25:MG01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN25:MG01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN25:MG01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN25:MG01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN25:MG01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN25:MG01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN25:MG01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN25:MG01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN25:MG01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN25:MG01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN25:MG01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN25:MG01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN25:MG01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN25:MG01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN25:MG01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN25:MG01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN25:MG01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN25:MG01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN25:MG01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN25:MG01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN25:MG01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN25:MG01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN25:MG01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN25:MG01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN25:MG01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN25:MG01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN25:MG01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN25:MG01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN25:MG01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN25:MG01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN25:MG01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN25:MG01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN25:MG01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN25:MG01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN25:MG01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN25:MG01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN25:MG01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN25:MG01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN25:MG01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN25:MG01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN25:MG01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN25:MG01:HEARTBEATCLC")
  field(INP, "SIOC:BPN25:MG01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN25:MG01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN25:MG01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN25:MG01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN25:MG01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN25:MG01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN25:MG01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN25:MG01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN25:MG01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN25:MG01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "L2KG26-5112")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN25:MG01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "L2KG26-5112")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN25:MG01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn25-mg01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN12:MC01:INFO") {
  field(DESC, "SIOC:BPN12:MC01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN12:MC01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Namrata Balakrishnan (namrata)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN12:MC01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN12:MC01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN12:MC01:TODDIFF")
}

record(longin, "SIOC:BPN12:MC01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN12:MC01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN12:MC01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN12:MC01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN12:MC01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN12:MC01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN12:MC01:TODSUM")
}

record(bo, "SIOC:BPN12:MC01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN12:MC01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN12:MC01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN12:MC01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN12:MC01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN12:MC01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN12:MC01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN12:MC01:HEARTBEATE01")
  field(INP, "SIOC:BPN12:MC01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN12:MC01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN12:MC01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN12:MC01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN12:MC01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN12:MC01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN12:MC01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN12:MC01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN12:MC01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN12:MC01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN12:MC01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN12:MC01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN12:MC01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN12:MC01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN12:MC01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN12:MC01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN12:MC01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN12:MC01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN12:MC01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN12:MC01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN12:MC01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN12:MC01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN12:MC01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN12:MC01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN12:MC01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN12:MC01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN12:MC01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN12:MC01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN12:MC01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN12:MC01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN12:MC01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN12:MC01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN12:MC01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN12:MC01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN12:MC01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN12:MC01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN12:MC01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN12:MC01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN12:MC01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN12:MC01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN12:MC01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN12:MC01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN12:MC01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN12:MC01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN12:MC01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN12:MC01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN12:MC01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN12:MC01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN12:MC01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN12:MC01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN12:MC01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN12:MC01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN12:MC01:HEARTBEATCLC")
  field(INP, "SIOC:BPN12:MC01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN12:MC01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN12:MC01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN12:MC01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN12:MC01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN12:MC01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN12:MC01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN12:MC01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN12:MC01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN12:MC01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "WSBP2")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN12:MC01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "WSBP2")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN12:MC01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-dog-sp05")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN13:MC01:INFO") {
  field(DESC, "SIOC:BPN13:MC01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN13:MC01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Namrata Balakrishnan (namrata)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN13:MC01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN13:MC01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN13:MC01:TODDIFF")
}

record(longin, "SIOC:BPN13:MC01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN13:MC01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN13:MC01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN13:MC01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN13:MC01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN13:MC01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN13:MC01:TODSUM")
}

record(bo, "SIOC:BPN13:MC01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN13:MC01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN13:MC01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN13:MC01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:MC01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN13:MC01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN13:MC01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN13:MC01:HEARTBEATE01")
  field(INP, "SIOC:BPN13:MC01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN13:MC01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN13:MC01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN13:MC01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN13:MC01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN13:MC01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN13:MC01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN13:MC01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN13:MC01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN13:MC01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN13:MC01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN13:MC01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN13:MC01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN13:MC01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN13:MC01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:MC01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN13:MC01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN13:MC01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN13:MC01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:MC01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN13:MC01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN13:MC01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN13:MC01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:MC01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN13:MC01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN13:MC01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN13:MC01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:MC01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN13:MC01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN13:MC01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN13:MC01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:MC01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN13:MC01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN13:MC01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN13:MC01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:MC01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN13:MC01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN13:MC01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN13:MC01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:MC01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN13:MC01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN13:MC01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN13:MC01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:MC01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN13:MC01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN13:MC01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN13:MC01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:MC01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN13:MC01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN13:MC01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN13:MC01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN13:MC01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN13:MC01:HEARTBEATCLC")
  field(INP, "SIOC:BPN13:MC01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN13:MC01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN13:MC01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:MC01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN13:MC01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN13:MC01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN13:MC01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN13:MC01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN13:MC01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN13:MC01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "LBLM12A")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN13:MC01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "LBLM12A")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN13:MC01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn15-sp01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN14:MC01:INFO") {
  field(DESC, "SIOC:BPN14:MC01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN14:MC01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Namrata Balakrishnan (namrata)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN14:MC01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN14:MC01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN14:MC01:TODDIFF")
}

record(longin, "SIOC:BPN14:MC01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN14:MC01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN14:MC01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN14:MC01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN14:MC01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN14:MC01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN14:MC01:TODSUM")
}

record(bo, "SIOC:BPN14:MC01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN14:MC01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN14:MC01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN14:MC01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:MC01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN14:MC01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN14:MC01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN14:MC01:HEARTBEATE01")
  field(INP, "SIOC:BPN14:MC01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN14:MC01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN14:MC01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN14:MC01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN14:MC01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN14:MC01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN14:MC01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN14:MC01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN14:MC01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN14:MC01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN14:MC01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN14:MC01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN14:MC01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN14:MC01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN14:MC01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:MC01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN14:MC01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN14:MC01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN14:MC01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:MC01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN14:MC01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN14:MC01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN14:MC01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:MC01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN14:MC01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN14:MC01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN14:MC01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:MC01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN14:MC01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN14:MC01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN14:MC01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:MC01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN14:MC01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN14:MC01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN14:MC01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:MC01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN14:MC01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN14:MC01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN14:MC01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:MC01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN14:MC01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN14:MC01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN14:MC01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:MC01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN14:MC01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN14:MC01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN14:MC01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:MC01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN14:MC01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN14:MC01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN14:MC01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN14:MC01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN14:MC01:HEARTBEATCLC")
  field(INP, "SIOC:BPN14:MC01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN14:MC01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN14:MC01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:MC01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN14:MC01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN14:MC01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN14:MC01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN14:MC01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN14:MC01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN14:MC01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "WSBP3")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN14:MC01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "WSBP3")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN14:MC01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn14-sp01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN15:MC01:INFO") {
  field(DESC, "SIOC:BPN15:MC01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN15:MC01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Namrata Balakrishnan (namrata)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN15:MC01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN15:MC01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN15:MC01:TODDIFF")
}

record(longin, "SIOC:BPN15:MC01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN15:MC01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN15:MC01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN15:MC01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN15:MC01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN15:MC01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN15:MC01:TODSUM")
}

record(bo, "SIOC:BPN15:MC01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN15:MC01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN15:MC01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN15:MC01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:MC01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN15:MC01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN15:MC01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN15:MC01:HEARTBEATE01")
  field(INP, "SIOC:BPN15:MC01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN15:MC01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN15:MC01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN15:MC01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN15:MC01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN15:MC01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN15:MC01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN15:MC01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN15:MC01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN15:MC01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN15:MC01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN15:MC01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN15:MC01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN15:MC01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN15:MC01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:MC01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN15:MC01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN15:MC01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN15:MC01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:MC01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN15:MC01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN15:MC01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN15:MC01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:MC01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN15:MC01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN15:MC01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN15:MC01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:MC01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN15:MC01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN15:MC01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN15:MC01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:MC01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN15:MC01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN15:MC01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN15:MC01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:MC01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN15:MC01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN15:MC01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN15:MC01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:MC01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN15:MC01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN15:MC01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN15:MC01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:MC01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN15:MC01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN15:MC01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN15:MC01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:MC01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN15:MC01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN15:MC01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN15:MC01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN15:MC01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN15:MC01:HEARTBEATCLC")
  field(INP, "SIOC:BPN15:MC01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN15:MC01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN15:MC01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:MC01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN15:MC01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN15:MC01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN15:MC01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN15:MC01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN15:MC01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN15:MC01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "LBLM13A")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN15:MC01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "LBLM13A")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN15:MC01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn17-sp01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN16:MC01:INFO") {
  field(DESC, "SIOC:BPN16:MC01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN16:MC01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Namrata Balakrishnan (namrata)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN16:MC01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN16:MC01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN16:MC01:TODDIFF")
}

record(longin, "SIOC:BPN16:MC01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN16:MC01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN16:MC01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN16:MC01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN16:MC01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN16:MC01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN16:MC01:TODSUM")
}

record(bo, "SIOC:BPN16:MC01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN16:MC01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN16:MC01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN16:MC01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:MC01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN16:MC01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN16:MC01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN16:MC01:HEARTBEATE01")
  field(INP, "SIOC:BPN16:MC01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN16:MC01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN16:MC01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN16:MC01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN16:MC01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN16:MC01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN16:MC01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN16:MC01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN16:MC01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN16:MC01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN16:MC01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN16:MC01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN16:MC01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN16:MC01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN16:MC01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:MC01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN16:MC01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN16:MC01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN16:MC01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:MC01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN16:MC01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN16:MC01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN16:MC01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:MC01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN16:MC01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN16:MC01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN16:MC01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:MC01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN16:MC01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN16:MC01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN16:MC01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:MC01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN16:MC01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN16:MC01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN16:MC01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:MC01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN16:MC01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN16:MC01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN16:MC01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:MC01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN16:MC01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN16:MC01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN16:MC01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:MC01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN16:MC01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN16:MC01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN16:MC01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:MC01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN16:MC01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN16:MC01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN16:MC01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN16:MC01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN16:MC01:HEARTBEATCLC")
  field(INP, "SIOC:BPN16:MC01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN16:MC01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN16:MC01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:MC01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN16:MC01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN16:MC01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN16:MC01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN16:MC01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN16:MC01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN16:MC01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "WSBP4")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN16:MC01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "WSBP4")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN16:MC01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn16-sp01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN17:MC01:INFO") {
  field(DESC, "SIOC:BPN17:MC01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN17:MC01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Namrata Balakrishnan (namrata)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN17:MC01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN17:MC01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN17:MC01:TODDIFF")
}

record(longin, "SIOC:BPN17:MC01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN17:MC01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN17:MC01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN17:MC01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN17:MC01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN17:MC01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN17:MC01:TODSUM")
}

record(bo, "SIOC:BPN17:MC01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN17:MC01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN17:MC01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN17:MC01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:MC01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN17:MC01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN17:MC01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN17:MC01:HEARTBEATE01")
  field(INP, "SIOC:BPN17:MC01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN17:MC01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN17:MC01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN17:MC01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN17:MC01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN17:MC01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN17:MC01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN17:MC01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN17:MC01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN17:MC01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN17:MC01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN17:MC01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN17:MC01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN17:MC01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN17:MC01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:MC01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN17:MC01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN17:MC01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN17:MC01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:MC01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN17:MC01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN17:MC01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN17:MC01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:MC01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN17:MC01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN17:MC01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN17:MC01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:MC01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN17:MC01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN17:MC01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN17:MC01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:MC01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN17:MC01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN17:MC01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN17:MC01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:MC01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN17:MC01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN17:MC01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN17:MC01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:MC01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN17:MC01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN17:MC01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN17:MC01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:MC01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN17:MC01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN17:MC01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN17:MC01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:MC01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN17:MC01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN17:MC01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN17:MC01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN17:MC01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN17:MC01:HEARTBEATCLC")
  field(INP, "SIOC:BPN17:MC01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN17:MC01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN17:MC01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:MC01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN17:MC01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN17:MC01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN17:MC01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN17:MC01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN17:MC01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN17:MC01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "LBLM_BPN17_517A")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN17:MC01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "LBLM_BPN17_517A")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN17:MC01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn19-sp01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN21:MC01:INFO") {
  field(DESC, "SIOC:BPN21:MC01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN21:MC01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Namrata Balakrishnan (namrata)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN21:MC01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN21:MC01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN21:MC01:TODDIFF")
}

record(longin, "SIOC:BPN21:MC01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN21:MC01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN21:MC01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN21:MC01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN21:MC01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN21:MC01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN21:MC01:TODSUM")
}

record(bo, "SIOC:BPN21:MC01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN21:MC01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN21:MC01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN21:MC01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:MC01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN21:MC01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN21:MC01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN21:MC01:HEARTBEATE01")
  field(INP, "SIOC:BPN21:MC01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN21:MC01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN21:MC01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN21:MC01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN21:MC01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN21:MC01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN21:MC01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN21:MC01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN21:MC01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN21:MC01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN21:MC01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN21:MC01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN21:MC01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN21:MC01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN21:MC01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:MC01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN21:MC01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN21:MC01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN21:MC01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:MC01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN21:MC01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN21:MC01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN21:MC01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:MC01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN21:MC01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN21:MC01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN21:MC01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:MC01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN21:MC01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN21:MC01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN21:MC01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:MC01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN21:MC01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN21:MC01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN21:MC01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:MC01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN21:MC01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN21:MC01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN21:MC01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:MC01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN21:MC01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN21:MC01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN21:MC01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:MC01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN21:MC01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN21:MC01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN21:MC01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:MC01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN21:MC01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN21:MC01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN21:MC01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN21:MC01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN21:MC01:HEARTBEATCLC")
  field(INP, "SIOC:BPN21:MC01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN21:MC01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN21:MC01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:MC01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN21:MC01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN21:MC01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN21:MC01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN21:MC01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN21:MC01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN21:MC01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "All BYP COLLs")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN21:MC01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "All BYP COLLs")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN21:MC01:LOC") {
  field(PINI, "YES")
  field(VAL, "lcls-daemon1")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN16:TM01:INFO") {
  field(DESC, "SIOC:BPN16:TM01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN16:TM01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Ziyu Huang (zyhuang)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN16:TM01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN16:TM01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN16:TM01:TODDIFF")
}

record(longin, "SIOC:BPN16:TM01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN16:TM01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN16:TM01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN16:TM01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN16:TM01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN16:TM01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN16:TM01:TODSUM")
}

record(bo, "SIOC:BPN16:TM01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN16:TM01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN16:TM01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN16:TM01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:TM01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN16:TM01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN16:TM01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN16:TM01:HEARTBEATE01")
  field(INP, "SIOC:BPN16:TM01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN16:TM01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN16:TM01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN16:TM01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN16:TM01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN16:TM01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN16:TM01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN16:TM01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN16:TM01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN16:TM01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN16:TM01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN16:TM01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN16:TM01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN16:TM01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN16:TM01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:TM01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN16:TM01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN16:TM01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN16:TM01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:TM01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN16:TM01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN16:TM01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN16:TM01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:TM01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN16:TM01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN16:TM01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN16:TM01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:TM01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN16:TM01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN16:TM01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN16:TM01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:TM01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN16:TM01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN16:TM01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN16:TM01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:TM01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN16:TM01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN16:TM01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN16:TM01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:TM01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN16:TM01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN16:TM01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN16:TM01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:TM01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN16:TM01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN16:TM01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN16:TM01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:TM01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN16:TM01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN16:TM01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN16:TM01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN16:TM01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN16:TM01:HEARTBEATCLC")
  field(INP, "SIOC:BPN16:TM01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN16:TM01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN16:TM01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:TM01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN16:TM01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN16:TM01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN16:TM01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN16:TM01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN16:TM01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN16:TM01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN16:TM01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN16:TM01:LOC") {
  field(PINI, "YES")
  field(VAL, "lcls-daemon1")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN15:VA01:INFO") {
  field(DESC, "SIOC:BPN15:VA01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN15:VA01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Shweta Saraf (shweta)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN15:VA01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN15:VA01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN15:VA01:TODDIFF")
}

record(longin, "SIOC:BPN15:VA01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN15:VA01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN15:VA01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN15:VA01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN15:VA01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN15:VA01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN15:VA01:TODSUM")
}

record(bo, "SIOC:BPN15:VA01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN15:VA01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN15:VA01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN15:VA01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:VA01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN15:VA01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN15:VA01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN15:VA01:HEARTBEATE01")
  field(INP, "SIOC:BPN15:VA01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN15:VA01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN15:VA01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN15:VA01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN15:VA01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN15:VA01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN15:VA01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN15:VA01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN15:VA01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN15:VA01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN15:VA01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN15:VA01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN15:VA01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN15:VA01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN15:VA01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:VA01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN15:VA01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN15:VA01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN15:VA01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:VA01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN15:VA01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN15:VA01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN15:VA01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:VA01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN15:VA01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN15:VA01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN15:VA01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:VA01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN15:VA01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN15:VA01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN15:VA01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:VA01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN15:VA01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN15:VA01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN15:VA01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:VA01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN15:VA01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN15:VA01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN15:VA01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:VA01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN15:VA01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN15:VA01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN15:VA01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:VA01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN15:VA01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN15:VA01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN15:VA01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:VA01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN15:VA01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN15:VA01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN15:VA01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN15:VA01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN15:VA01:HEARTBEATCLC")
  field(INP, "SIOC:BPN15:VA01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN15:VA01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN15:VA01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:VA01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN15:VA01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN15:VA01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN15:VA01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN15:VA01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN15:VA01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN15:VA01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN15:VA01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN15:VA01:LOC") {
  field(PINI, "YES")
  field(VAL, "lcls-daemon0")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN22:VA01:INFO") {
  field(DESC, "SIOC:BPN22:VA01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN22:VA01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Shweta Saraf (shweta)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN22:VA01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN22:VA01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN22:VA01:TODDIFF")
}

record(longin, "SIOC:BPN22:VA01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN22:VA01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN22:VA01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN22:VA01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN22:VA01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN22:VA01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN22:VA01:TODSUM")
}

record(bo, "SIOC:BPN22:VA01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN22:VA01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN22:VA01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN22:VA01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN22:VA01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN22:VA01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN22:VA01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN22:VA01:HEARTBEATE01")
  field(INP, "SIOC:BPN22:VA01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN22:VA01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN22:VA01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN22:VA01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN22:VA01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN22:VA01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN22:VA01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN22:VA01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN22:VA01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN22:VA01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN22:VA01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN22:VA01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN22:VA01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN22:VA01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN22:VA01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN22:VA01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN22:VA01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN22:VA01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN22:VA01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN22:VA01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN22:VA01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN22:VA01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN22:VA01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN22:VA01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN22:VA01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN22:VA01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN22:VA01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN22:VA01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN22:VA01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN22:VA01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN22:VA01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN22:VA01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN22:VA01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN22:VA01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN22:VA01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN22:VA01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN22:VA01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN22:VA01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN22:VA01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN22:VA01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN22:VA01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN22:VA01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN22:VA01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN22:VA01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN22:VA01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN22:VA01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN22:VA01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN22:VA01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN22:VA01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN22:VA01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN22:VA01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN22:VA01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN22:VA01:HEARTBEATCLC")
  field(INP, "SIOC:BPN22:VA01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN22:VA01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN22:VA01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN22:VA01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN22:VA01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN22:VA01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN22:VA01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN22:VA01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN22:VA01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN22:VA01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN22:VA01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN22:VA01:LOC") {
  field(PINI, "YES")
  field(VAL, "lcls-daemon0")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN13:MP00:INFO") {
  field(DESC, "SIOC:BPN13:MP00 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN13:MP00:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Jeremy Mock (jmock)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN13:MP00:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN13:MP00:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN13:MP00:TODDIFF")
}

record(longin, "SIOC:BPN13:MP00:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN13:MP00:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN13:MP00:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN13:MP00:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN13:MP00:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN13:MP00:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN13:MP00:TODSUM")
}

record(bo, "SIOC:BPN13:MP00:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN13:MP00:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN13:MP00:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN13:MP00:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:MP00:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN13:MP00:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN13:MP00:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN13:MP00:HEARTBEATE01")
  field(INP, "SIOC:BPN13:MP00:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN13:MP00:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN13:MP00:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN13:MP00:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN13:MP00:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN13:MP00:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN13:MP00:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN13:MP00:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN13:MP00:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN13:MP00:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN13:MP00:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN13:MP00:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN13:MP00:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN13:MP00:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN13:MP00:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:MP00:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN13:MP00:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN13:MP00:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN13:MP00:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:MP00:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN13:MP00:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN13:MP00:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN13:MP00:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:MP00:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN13:MP00:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN13:MP00:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN13:MP00:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:MP00:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN13:MP00:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN13:MP00:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN13:MP00:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:MP00:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN13:MP00:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN13:MP00:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN13:MP00:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:MP00:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN13:MP00:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN13:MP00:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN13:MP00:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:MP00:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN13:MP00:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN13:MP00:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN13:MP00:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:MP00:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN13:MP00:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN13:MP00:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN13:MP00:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:MP00:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN13:MP00:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN13:MP00:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN13:MP00:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN13:MP00:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN13:MP00:HEARTBEATCLC")
  field(INP, "SIOC:BPN13:MP00:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN13:MP00:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN13:MP00:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:MP00:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN13:MP00:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN13:MP00:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN13:MP00:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN13:MP00:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN13:MP00:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN13:MP00:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN13:MP00:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN13:MP00:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-sys0-mp03")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN13:MP01:INFO") {
  field(DESC, "SIOC:BPN13:MP01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN13:MP01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Jeremy Mock (jmock)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN13:MP01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN13:MP01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN13:MP01:TODDIFF")
}

record(longin, "SIOC:BPN13:MP01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN13:MP01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN13:MP01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN13:MP01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN13:MP01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN13:MP01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN13:MP01:TODSUM")
}

record(bo, "SIOC:BPN13:MP01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN13:MP01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN13:MP01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN13:MP01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:MP01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN13:MP01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN13:MP01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN13:MP01:HEARTBEATE01")
  field(INP, "SIOC:BPN13:MP01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN13:MP01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN13:MP01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN13:MP01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN13:MP01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN13:MP01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN13:MP01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN13:MP01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN13:MP01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN13:MP01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN13:MP01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN13:MP01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN13:MP01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN13:MP01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN13:MP01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:MP01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN13:MP01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN13:MP01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN13:MP01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:MP01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN13:MP01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN13:MP01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN13:MP01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:MP01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN13:MP01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN13:MP01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN13:MP01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:MP01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN13:MP01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN13:MP01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN13:MP01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:MP01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN13:MP01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN13:MP01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN13:MP01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:MP01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN13:MP01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN13:MP01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN13:MP01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:MP01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN13:MP01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN13:MP01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN13:MP01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:MP01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN13:MP01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN13:MP01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN13:MP01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:MP01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN13:MP01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN13:MP01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN13:MP01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN13:MP01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN13:MP01:HEARTBEATCLC")
  field(INP, "SIOC:BPN13:MP01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN13:MP01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN13:MP01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN13:MP01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN13:MP01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN13:MP01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN13:MP01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN13:MP01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN13:MP01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN13:MP01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN13:MP01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN13:MP01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn13-sp01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN14:MP01:INFO") {
  field(DESC, "SIOC:BPN14:MP01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN14:MP01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Jeremy Mock (jmock)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN14:MP01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN14:MP01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN14:MP01:TODDIFF")
}

record(longin, "SIOC:BPN14:MP01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN14:MP01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN14:MP01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN14:MP01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN14:MP01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN14:MP01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN14:MP01:TODSUM")
}

record(bo, "SIOC:BPN14:MP01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN14:MP01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN14:MP01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN14:MP01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:MP01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN14:MP01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN14:MP01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN14:MP01:HEARTBEATE01")
  field(INP, "SIOC:BPN14:MP01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN14:MP01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN14:MP01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN14:MP01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN14:MP01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN14:MP01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN14:MP01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN14:MP01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN14:MP01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN14:MP01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN14:MP01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN14:MP01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN14:MP01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN14:MP01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN14:MP01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:MP01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN14:MP01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN14:MP01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN14:MP01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:MP01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN14:MP01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN14:MP01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN14:MP01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:MP01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN14:MP01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN14:MP01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN14:MP01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:MP01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN14:MP01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN14:MP01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN14:MP01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:MP01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN14:MP01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN14:MP01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN14:MP01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:MP01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN14:MP01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN14:MP01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN14:MP01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:MP01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN14:MP01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN14:MP01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN14:MP01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:MP01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN14:MP01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN14:MP01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN14:MP01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:MP01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN14:MP01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN14:MP01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN14:MP01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN14:MP01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN14:MP01:HEARTBEATCLC")
  field(INP, "SIOC:BPN14:MP01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN14:MP01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN14:MP01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN14:MP01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN14:MP01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN14:MP01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN14:MP01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN14:MP01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN14:MP01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN14:MP01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN14:MP01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN14:MP01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn14-sp01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN15:MP01:INFO") {
  field(DESC, "SIOC:BPN15:MP01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN15:MP01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Jeremy Mock (jmock)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN15:MP01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN15:MP01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN15:MP01:TODDIFF")
}

record(longin, "SIOC:BPN15:MP01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN15:MP01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN15:MP01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN15:MP01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN15:MP01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN15:MP01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN15:MP01:TODSUM")
}

record(bo, "SIOC:BPN15:MP01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN15:MP01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN15:MP01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN15:MP01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:MP01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN15:MP01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN15:MP01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN15:MP01:HEARTBEATE01")
  field(INP, "SIOC:BPN15:MP01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN15:MP01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN15:MP01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN15:MP01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN15:MP01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN15:MP01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN15:MP01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN15:MP01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN15:MP01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN15:MP01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN15:MP01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN15:MP01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN15:MP01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN15:MP01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN15:MP01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:MP01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN15:MP01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN15:MP01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN15:MP01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:MP01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN15:MP01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN15:MP01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN15:MP01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:MP01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN15:MP01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN15:MP01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN15:MP01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:MP01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN15:MP01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN15:MP01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN15:MP01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:MP01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN15:MP01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN15:MP01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN15:MP01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:MP01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN15:MP01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN15:MP01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN15:MP01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:MP01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN15:MP01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN15:MP01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN15:MP01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:MP01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN15:MP01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN15:MP01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN15:MP01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:MP01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN15:MP01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN15:MP01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN15:MP01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN15:MP01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN15:MP01:HEARTBEATCLC")
  field(INP, "SIOC:BPN15:MP01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN15:MP01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN15:MP01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN15:MP01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN15:MP01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN15:MP01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN15:MP01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN15:MP01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN15:MP01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN15:MP01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN15:MP01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN15:MP01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn15-sp01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN16:MP01:INFO") {
  field(DESC, "SIOC:BPN16:MP01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN16:MP01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Jeremy Mock (jmock)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN16:MP01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN16:MP01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN16:MP01:TODDIFF")
}

record(longin, "SIOC:BPN16:MP01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN16:MP01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN16:MP01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN16:MP01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN16:MP01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN16:MP01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN16:MP01:TODSUM")
}

record(bo, "SIOC:BPN16:MP01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN16:MP01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN16:MP01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN16:MP01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:MP01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN16:MP01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN16:MP01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN16:MP01:HEARTBEATE01")
  field(INP, "SIOC:BPN16:MP01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN16:MP01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN16:MP01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN16:MP01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN16:MP01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN16:MP01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN16:MP01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN16:MP01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN16:MP01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN16:MP01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN16:MP01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN16:MP01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN16:MP01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN16:MP01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN16:MP01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:MP01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN16:MP01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN16:MP01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN16:MP01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:MP01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN16:MP01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN16:MP01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN16:MP01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:MP01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN16:MP01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN16:MP01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN16:MP01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:MP01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN16:MP01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN16:MP01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN16:MP01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:MP01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN16:MP01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN16:MP01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN16:MP01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:MP01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN16:MP01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN16:MP01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN16:MP01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:MP01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN16:MP01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN16:MP01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN16:MP01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:MP01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN16:MP01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN16:MP01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN16:MP01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:MP01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN16:MP01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN16:MP01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN16:MP01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN16:MP01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN16:MP01:HEARTBEATCLC")
  field(INP, "SIOC:BPN16:MP01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN16:MP01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN16:MP01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:MP01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN16:MP01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN16:MP01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN16:MP01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN16:MP01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN16:MP01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN16:MP01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN16:MP01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN16:MP01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn16-sp01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN17:MP01:INFO") {
  field(DESC, "SIOC:BPN17:MP01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN17:MP01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Jeremy Mock (jmock)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN17:MP01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN17:MP01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN17:MP01:TODDIFF")
}

record(longin, "SIOC:BPN17:MP01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN17:MP01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN17:MP01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN17:MP01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN17:MP01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN17:MP01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN17:MP01:TODSUM")
}

record(bo, "SIOC:BPN17:MP01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN17:MP01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN17:MP01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN17:MP01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:MP01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN17:MP01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN17:MP01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN17:MP01:HEARTBEATE01")
  field(INP, "SIOC:BPN17:MP01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN17:MP01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN17:MP01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN17:MP01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN17:MP01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN17:MP01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN17:MP01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN17:MP01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN17:MP01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN17:MP01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN17:MP01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN17:MP01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN17:MP01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN17:MP01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN17:MP01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:MP01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN17:MP01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN17:MP01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN17:MP01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:MP01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN17:MP01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN17:MP01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN17:MP01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:MP01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN17:MP01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN17:MP01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN17:MP01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:MP01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN17:MP01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN17:MP01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN17:MP01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:MP01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN17:MP01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN17:MP01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN17:MP01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:MP01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN17:MP01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN17:MP01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN17:MP01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:MP01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN17:MP01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN17:MP01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN17:MP01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:MP01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN17:MP01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN17:MP01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN17:MP01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:MP01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN17:MP01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN17:MP01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN17:MP01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN17:MP01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN17:MP01:HEARTBEATCLC")
  field(INP, "SIOC:BPN17:MP01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN17:MP01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN17:MP01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN17:MP01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN17:MP01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN17:MP01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN17:MP01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN17:MP01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN17:MP01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN17:MP01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN17:MP01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN17:MP01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn17-sp01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN18:MP01:INFO") {
  field(DESC, "SIOC:BPN18:MP01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN18:MP01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Jeremy Mock (jmock)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN18:MP01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN18:MP01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN18:MP01:TODDIFF")
}

record(longin, "SIOC:BPN18:MP01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN18:MP01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN18:MP01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN18:MP01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN18:MP01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN18:MP01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN18:MP01:TODSUM")
}

record(bo, "SIOC:BPN18:MP01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN18:MP01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN18:MP01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN18:MP01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN18:MP01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN18:MP01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN18:MP01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN18:MP01:HEARTBEATE01")
  field(INP, "SIOC:BPN18:MP01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN18:MP01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN18:MP01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN18:MP01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN18:MP01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN18:MP01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN18:MP01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN18:MP01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN18:MP01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN18:MP01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN18:MP01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN18:MP01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN18:MP01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN18:MP01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN18:MP01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN18:MP01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN18:MP01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN18:MP01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN18:MP01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN18:MP01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN18:MP01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN18:MP01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN18:MP01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN18:MP01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN18:MP01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN18:MP01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN18:MP01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN18:MP01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN18:MP01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN18:MP01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN18:MP01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN18:MP01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN18:MP01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN18:MP01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN18:MP01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN18:MP01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN18:MP01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN18:MP01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN18:MP01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN18:MP01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN18:MP01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN18:MP01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN18:MP01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN18:MP01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN18:MP01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN18:MP01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN18:MP01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN18:MP01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN18:MP01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN18:MP01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN18:MP01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN18:MP01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN18:MP01:HEARTBEATCLC")
  field(INP, "SIOC:BPN18:MP01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN18:MP01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN18:MP01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN18:MP01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN18:MP01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN18:MP01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN18:MP01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN18:MP01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN18:MP01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN18:MP01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN18:MP01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN18:MP01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn18-sp01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN19:MP01:INFO") {
  field(DESC, "SIOC:BPN19:MP01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN19:MP01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Jeremy Mock (jmock)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN19:MP01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN19:MP01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN19:MP01:TODDIFF")
}

record(longin, "SIOC:BPN19:MP01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN19:MP01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN19:MP01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN19:MP01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN19:MP01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN19:MP01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN19:MP01:TODSUM")
}

record(bo, "SIOC:BPN19:MP01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN19:MP01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN19:MP01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN19:MP01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN19:MP01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN19:MP01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN19:MP01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN19:MP01:HEARTBEATE01")
  field(INP, "SIOC:BPN19:MP01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN19:MP01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN19:MP01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN19:MP01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN19:MP01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN19:MP01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN19:MP01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN19:MP01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN19:MP01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN19:MP01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN19:MP01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN19:MP01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN19:MP01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN19:MP01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN19:MP01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN19:MP01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN19:MP01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN19:MP01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN19:MP01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN19:MP01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN19:MP01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN19:MP01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN19:MP01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN19:MP01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN19:MP01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN19:MP01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN19:MP01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN19:MP01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN19:MP01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN19:MP01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN19:MP01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN19:MP01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN19:MP01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN19:MP01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN19:MP01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN19:MP01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN19:MP01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN19:MP01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN19:MP01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN19:MP01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN19:MP01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN19:MP01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN19:MP01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN19:MP01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN19:MP01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN19:MP01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN19:MP01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN19:MP01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN19:MP01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN19:MP01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN19:MP01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN19:MP01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN19:MP01:HEARTBEATCLC")
  field(INP, "SIOC:BPN19:MP01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN19:MP01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN19:MP01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN19:MP01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN19:MP01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN19:MP01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN19:MP01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN19:MP01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN19:MP01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN19:MP01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN19:MP01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN19:MP01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn19-sp01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN20:MP01:INFO") {
  field(DESC, "SIOC:BPN20:MP01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN20:MP01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Jeremy Mock (jmock)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN20:MP01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN20:MP01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN20:MP01:TODDIFF")
}

record(longin, "SIOC:BPN20:MP01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN20:MP01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN20:MP01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN20:MP01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN20:MP01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN20:MP01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN20:MP01:TODSUM")
}

record(bo, "SIOC:BPN20:MP01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN20:MP01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN20:MP01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN20:MP01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN20:MP01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN20:MP01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN20:MP01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN20:MP01:HEARTBEATE01")
  field(INP, "SIOC:BPN20:MP01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN20:MP01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN20:MP01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN20:MP01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN20:MP01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN20:MP01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN20:MP01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN20:MP01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN20:MP01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN20:MP01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN20:MP01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN20:MP01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN20:MP01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN20:MP01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN20:MP01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN20:MP01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN20:MP01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN20:MP01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN20:MP01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN20:MP01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN20:MP01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN20:MP01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN20:MP01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN20:MP01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN20:MP01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN20:MP01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN20:MP01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN20:MP01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN20:MP01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN20:MP01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN20:MP01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN20:MP01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN20:MP01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN20:MP01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN20:MP01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN20:MP01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN20:MP01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN20:MP01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN20:MP01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN20:MP01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN20:MP01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN20:MP01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN20:MP01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN20:MP01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN20:MP01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN20:MP01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN20:MP01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN20:MP01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN20:MP01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN20:MP01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN20:MP01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN20:MP01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN20:MP01:HEARTBEATCLC")
  field(INP, "SIOC:BPN20:MP01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN20:MP01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN20:MP01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN20:MP01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN20:MP01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN20:MP01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN20:MP01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN20:MP01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN20:MP01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN20:MP01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN20:MP01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN20:MP01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn20-sp01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN21:MP01:INFO") {
  field(DESC, "SIOC:BPN21:MP01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN21:MP01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Jeremy Mock (jmock)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN21:MP01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN21:MP01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN21:MP01:TODDIFF")
}

record(longin, "SIOC:BPN21:MP01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN21:MP01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN21:MP01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN21:MP01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN21:MP01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN21:MP01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN21:MP01:TODSUM")
}

record(bo, "SIOC:BPN21:MP01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN21:MP01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN21:MP01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN21:MP01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:MP01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN21:MP01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN21:MP01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN21:MP01:HEARTBEATE01")
  field(INP, "SIOC:BPN21:MP01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN21:MP01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN21:MP01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN21:MP01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN21:MP01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN21:MP01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN21:MP01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN21:MP01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN21:MP01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN21:MP01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN21:MP01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN21:MP01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN21:MP01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN21:MP01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN21:MP01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:MP01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN21:MP01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN21:MP01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN21:MP01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:MP01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN21:MP01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN21:MP01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN21:MP01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:MP01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN21:MP01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN21:MP01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN21:MP01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:MP01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN21:MP01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN21:MP01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN21:MP01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:MP01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN21:MP01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN21:MP01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN21:MP01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:MP01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN21:MP01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN21:MP01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN21:MP01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:MP01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN21:MP01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN21:MP01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN21:MP01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:MP01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN21:MP01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN21:MP01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN21:MP01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:MP01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN21:MP01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN21:MP01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN21:MP01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN21:MP01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN21:MP01:HEARTBEATCLC")
  field(INP, "SIOC:BPN21:MP01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN21:MP01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN21:MP01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN21:MP01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN21:MP01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN21:MP01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN21:MP01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN21:MP01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN21:MP01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN21:MP01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN21:MP01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN21:MP01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn21-sp01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN22:MP01:INFO") {
  field(DESC, "SIOC:BPN22:MP01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN22:MP01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Jeremy Mock (jmock)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN22:MP01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN22:MP01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN22:MP01:TODDIFF")
}

record(longin, "SIOC:BPN22:MP01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN22:MP01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN22:MP01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN22:MP01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN22:MP01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN22:MP01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN22:MP01:TODSUM")
}

record(bo, "SIOC:BPN22:MP01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN22:MP01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN22:MP01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN22:MP01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN22:MP01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN22:MP01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN22:MP01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN22:MP01:HEARTBEATE01")
  field(INP, "SIOC:BPN22:MP01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN22:MP01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN22:MP01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN22:MP01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN22:MP01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN22:MP01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN22:MP01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN22:MP01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN22:MP01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN22:MP01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN22:MP01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN22:MP01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN22:MP01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN22:MP01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN22:MP01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN22:MP01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN22:MP01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN22:MP01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN22:MP01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN22:MP01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN22:MP01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN22:MP01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN22:MP01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN22:MP01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN22:MP01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN22:MP01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN22:MP01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN22:MP01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN22:MP01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN22:MP01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN22:MP01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN22:MP01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN22:MP01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN22:MP01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN22:MP01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN22:MP01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN22:MP01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN22:MP01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN22:MP01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN22:MP01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN22:MP01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN22:MP01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN22:MP01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN22:MP01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN22:MP01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN22:MP01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN22:MP01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN22:MP01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN22:MP01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN22:MP01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN22:MP01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN22:MP01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN22:MP01:HEARTBEATCLC")
  field(INP, "SIOC:BPN22:MP01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN22:MP01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN22:MP01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN22:MP01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN22:MP01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN22:MP01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN22:MP01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN22:MP01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN22:MP01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN22:MP01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN22:MP01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN22:MP01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn22-sp01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN23:MP01:INFO") {
  field(DESC, "SIOC:BPN23:MP01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN23:MP01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Jeremy Mock (jmock)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN23:MP01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN23:MP01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN23:MP01:TODDIFF")
}

record(longin, "SIOC:BPN23:MP01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN23:MP01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN23:MP01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN23:MP01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN23:MP01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN23:MP01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN23:MP01:TODSUM")
}

record(bo, "SIOC:BPN23:MP01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN23:MP01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN23:MP01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN23:MP01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN23:MP01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN23:MP01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN23:MP01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN23:MP01:HEARTBEATE01")
  field(INP, "SIOC:BPN23:MP01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN23:MP01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN23:MP01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN23:MP01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN23:MP01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN23:MP01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN23:MP01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN23:MP01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN23:MP01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN23:MP01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN23:MP01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN23:MP01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN23:MP01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN23:MP01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN23:MP01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN23:MP01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN23:MP01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN23:MP01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN23:MP01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN23:MP01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN23:MP01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN23:MP01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN23:MP01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN23:MP01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN23:MP01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN23:MP01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN23:MP01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN23:MP01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN23:MP01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN23:MP01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN23:MP01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN23:MP01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN23:MP01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN23:MP01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN23:MP01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN23:MP01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN23:MP01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN23:MP01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN23:MP01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN23:MP01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN23:MP01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN23:MP01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN23:MP01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN23:MP01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN23:MP01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN23:MP01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN23:MP01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN23:MP01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN23:MP01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN23:MP01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN23:MP01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN23:MP01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN23:MP01:HEARTBEATCLC")
  field(INP, "SIOC:BPN23:MP01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN23:MP01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN23:MP01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN23:MP01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN23:MP01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN23:MP01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN23:MP01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN23:MP01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN23:MP01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN23:MP01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN23:MP01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN23:MP01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn23-sp01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN24:MP01:INFO") {
  field(DESC, "SIOC:BPN24:MP01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN24:MP01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Jeremy Mock (jmock)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN24:MP01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN24:MP01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN24:MP01:TODDIFF")
}

record(longin, "SIOC:BPN24:MP01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN24:MP01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN24:MP01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN24:MP01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN24:MP01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN24:MP01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN24:MP01:TODSUM")
}

record(bo, "SIOC:BPN24:MP01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN24:MP01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN24:MP01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN24:MP01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN24:MP01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN24:MP01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN24:MP01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN24:MP01:HEARTBEATE01")
  field(INP, "SIOC:BPN24:MP01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN24:MP01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN24:MP01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN24:MP01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN24:MP01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN24:MP01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN24:MP01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN24:MP01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN24:MP01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN24:MP01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN24:MP01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN24:MP01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN24:MP01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN24:MP01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN24:MP01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN24:MP01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN24:MP01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN24:MP01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN24:MP01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN24:MP01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN24:MP01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN24:MP01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN24:MP01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN24:MP01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN24:MP01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN24:MP01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN24:MP01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN24:MP01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN24:MP01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN24:MP01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN24:MP01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN24:MP01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN24:MP01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN24:MP01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN24:MP01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN24:MP01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN24:MP01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN24:MP01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN24:MP01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN24:MP01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN24:MP01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN24:MP01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN24:MP01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN24:MP01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN24:MP01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN24:MP01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN24:MP01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN24:MP01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN24:MP01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN24:MP01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN24:MP01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN24:MP01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN24:MP01:HEARTBEATCLC")
  field(INP, "SIOC:BPN24:MP01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN24:MP01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN24:MP01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN24:MP01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN24:MP01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN24:MP01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN24:MP01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN24:MP01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN24:MP01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN24:MP01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN24:MP01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN24:MP01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn24-sp01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN25:MP01:INFO") {
  field(DESC, "SIOC:BPN25:MP01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN25:MP01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Jeremy Mock (jmock)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN25:MP01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN25:MP01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN25:MP01:TODDIFF")
}

record(longin, "SIOC:BPN25:MP01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN25:MP01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN25:MP01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN25:MP01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN25:MP01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN25:MP01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN25:MP01:TODSUM")
}

record(bo, "SIOC:BPN25:MP01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN25:MP01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN25:MP01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN25:MP01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN25:MP01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN25:MP01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN25:MP01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN25:MP01:HEARTBEATE01")
  field(INP, "SIOC:BPN25:MP01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN25:MP01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN25:MP01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN25:MP01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN25:MP01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN25:MP01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN25:MP01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN25:MP01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN25:MP01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN25:MP01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN25:MP01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN25:MP01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN25:MP01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN25:MP01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN25:MP01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN25:MP01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN25:MP01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN25:MP01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN25:MP01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN25:MP01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN25:MP01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN25:MP01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN25:MP01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN25:MP01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN25:MP01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN25:MP01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN25:MP01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN25:MP01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN25:MP01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN25:MP01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN25:MP01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN25:MP01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN25:MP01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN25:MP01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN25:MP01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN25:MP01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN25:MP01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN25:MP01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN25:MP01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN25:MP01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN25:MP01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN25:MP01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN25:MP01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN25:MP01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN25:MP01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN25:MP01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN25:MP01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN25:MP01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN25:MP01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN25:MP01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN25:MP01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN25:MP01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN25:MP01:HEARTBEATCLC")
  field(INP, "SIOC:BPN25:MP01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN25:MP01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN25:MP01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN25:MP01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN25:MP01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN25:MP01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN25:MP01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN25:MP01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN25:MP01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN25:MP01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN25:MP01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN25:MP01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn25-sp01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN26:MP01:INFO") {
  field(DESC, "SIOC:BPN26:MP01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN26:MP01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Jeremy Mock (jmock)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN26:MP01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN26:MP01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN26:MP01:TODDIFF")
}

record(longin, "SIOC:BPN26:MP01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN26:MP01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN26:MP01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN26:MP01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN26:MP01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN26:MP01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN26:MP01:TODSUM")
}

record(bo, "SIOC:BPN26:MP01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN26:MP01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN26:MP01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN26:MP01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN26:MP01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN26:MP01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN26:MP01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN26:MP01:HEARTBEATE01")
  field(INP, "SIOC:BPN26:MP01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN26:MP01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN26:MP01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN26:MP01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN26:MP01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN26:MP01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN26:MP01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN26:MP01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN26:MP01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN26:MP01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN26:MP01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN26:MP01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN26:MP01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN26:MP01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN26:MP01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN26:MP01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN26:MP01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN26:MP01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN26:MP01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN26:MP01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN26:MP01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN26:MP01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN26:MP01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN26:MP01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN26:MP01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN26:MP01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN26:MP01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN26:MP01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN26:MP01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN26:MP01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN26:MP01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN26:MP01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN26:MP01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN26:MP01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN26:MP01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN26:MP01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN26:MP01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN26:MP01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN26:MP01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN26:MP01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN26:MP01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN26:MP01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN26:MP01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN26:MP01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN26:MP01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN26:MP01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN26:MP01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN26:MP01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN26:MP01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN26:MP01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN26:MP01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN26:MP01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN26:MP01:HEARTBEATCLC")
  field(INP, "SIOC:BPN26:MP01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN26:MP01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN26:MP01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN26:MP01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN26:MP01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN26:MP01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN26:MP01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN26:MP01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN26:MP01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN26:MP01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN26:MP01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN26:MP01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn26-sp01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN27:MP01:INFO") {
  field(DESC, "SIOC:BPN27:MP01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN27:MP01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Jeremy Mock (jmock)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN27:MP01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN27:MP01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN27:MP01:TODDIFF")
}

record(longin, "SIOC:BPN27:MP01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN27:MP01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN27:MP01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN27:MP01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN27:MP01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN27:MP01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN27:MP01:TODSUM")
}

record(bo, "SIOC:BPN27:MP01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN27:MP01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN27:MP01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN27:MP01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN27:MP01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN27:MP01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN27:MP01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN27:MP01:HEARTBEATE01")
  field(INP, "SIOC:BPN27:MP01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN27:MP01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN27:MP01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN27:MP01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN27:MP01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN27:MP01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN27:MP01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN27:MP01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN27:MP01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN27:MP01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN27:MP01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN27:MP01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN27:MP01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN27:MP01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN27:MP01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN27:MP01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN27:MP01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN27:MP01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN27:MP01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN27:MP01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN27:MP01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN27:MP01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN27:MP01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN27:MP01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN27:MP01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN27:MP01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN27:MP01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN27:MP01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN27:MP01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN27:MP01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN27:MP01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN27:MP01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN27:MP01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN27:MP01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN27:MP01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN27:MP01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN27:MP01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN27:MP01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN27:MP01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN27:MP01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN27:MP01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN27:MP01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN27:MP01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN27:MP01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN27:MP01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN27:MP01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN27:MP01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN27:MP01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN27:MP01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN27:MP01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN27:MP01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN27:MP01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN27:MP01:HEARTBEATCLC")
  field(INP, "SIOC:BPN27:MP01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN27:MP01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN27:MP01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN27:MP01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN27:MP01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN27:MP01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN27:MP01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN27:MP01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN27:MP01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN27:MP01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN27:MP01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN27:MP01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn27-sp01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN28:MP01:INFO") {
  field(DESC, "SIOC:BPN28:MP01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN28:MP01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Jeremy Mock (jmock)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN28:MP01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN28:MP01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN28:MP01:TODDIFF")
}

record(longin, "SIOC:BPN28:MP01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN28:MP01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN28:MP01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN28:MP01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN28:MP01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN28:MP01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN28:MP01:TODSUM")
}

record(bo, "SIOC:BPN28:MP01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN28:MP01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN28:MP01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN28:MP01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN28:MP01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN28:MP01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN28:MP01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN28:MP01:HEARTBEATE01")
  field(INP, "SIOC:BPN28:MP01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN28:MP01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN28:MP01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN28:MP01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN28:MP01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN28:MP01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN28:MP01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN28:MP01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN28:MP01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN28:MP01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN28:MP01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN28:MP01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN28:MP01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN28:MP01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN28:MP01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN28:MP01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN28:MP01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN28:MP01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN28:MP01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN28:MP01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN28:MP01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN28:MP01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN28:MP01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN28:MP01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN28:MP01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN28:MP01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN28:MP01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN28:MP01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN28:MP01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN28:MP01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN28:MP01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN28:MP01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN28:MP01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN28:MP01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN28:MP01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN28:MP01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN28:MP01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN28:MP01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN28:MP01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN28:MP01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN28:MP01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN28:MP01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN28:MP01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN28:MP01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN28:MP01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN28:MP01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN28:MP01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN28:MP01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN28:MP01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN28:MP01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN28:MP01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN28:MP01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN28:MP01:HEARTBEATCLC")
  field(INP, "SIOC:BPN28:MP01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN28:MP01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN28:MP01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN28:MP01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN28:MP01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN28:MP01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN28:MP01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN28:MP01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN28:MP01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN28:MP01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN28:MP01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN28:MP01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn28-sp01")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:BPN16:TR01:INFO") {
  field(DESC, "SIOC:BPN16:TR01 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN16:TR01:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Jeremy Mock (jmock)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:BPN16:TR01:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:BPN16:TR01:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:BPN16:TR01:TODDIFF")
}

record(longin, "SIOC:BPN16:TR01:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:BPN16:TR01:TODCHECK.VALA MS")
  field(FLNK, "SIOC:BPN16:TR01:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:BPN16:TR01:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:BPN16:TR01:TODCHECK.SEVR")
  field(INPB, "SIOC:BPN16:TR01:TODCHECK.VALB")
  field(FLNK, "SIOC:BPN16:TR01:TODSUM")
}

record(bo, "SIOC:BPN16:TR01:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:BPN16:TR01:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:BPN16:TR01:HEARTBEATCALC") {
  field(FLNK, "SIOC:BPN16:TR01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:TR01:HEARTBEAT CA MS")
  field(INPB, "SIOC:BPN16:TR01:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:BPN16:TR01:HEARTBEATOK") {
  field(FLNK, "SIOC:BPN16:TR01:HEARTBEATE01")
  field(INP, "SIOC:BPN16:TR01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:BPN16:TR01:HEARTBEATECT") {
  field(FLNK, "SIOC:BPN16:TR01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:BPN16:TR01:HEARTBEATE01.VAL")
  field(INPB, "SIOC:BPN16:TR01:HEARTBEATE02.VAL")
  field(INPC, "SIOC:BPN16:TR01:HEARTBEATE03.VAL")
  field(INPD, "SIOC:BPN16:TR01:HEARTBEATE04.VAL")
  field(INPE, "SIOC:BPN16:TR01:HEARTBEATE05.VAL")
  field(INPF, "SIOC:BPN16:TR01:HEARTBEATE06.VAL")
  field(INPG, "SIOC:BPN16:TR01:HEARTBEATE07.VAL")
  field(INPH, "SIOC:BPN16:TR01:HEARTBEATE08.VAL")
  field(INPI, "SIOC:BPN16:TR01:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:BPN16:TR01:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:BPN16:TR01:HEARTBEATE09") {
  field(FLNK, "SIOC:BPN16:TR01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:TR01:HEARTBEATE08.B")
  field(INPB, "SIOC:BPN16:TR01:HEARTBEATE09.VAL")
}

record(calc, "SIOC:BPN16:TR01:HEARTBEATE08") {
  field(FLNK, "SIOC:BPN16:TR01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:TR01:HEARTBEATE07.B")
  field(INPB, "SIOC:BPN16:TR01:HEARTBEATE08.VAL")
}

record(calc, "SIOC:BPN16:TR01:HEARTBEATE07") {
  field(FLNK, "SIOC:BPN16:TR01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:TR01:HEARTBEATE06.B")
  field(INPB, "SIOC:BPN16:TR01:HEARTBEATE07.VAL")
}

record(calc, "SIOC:BPN16:TR01:HEARTBEATE06") {
  field(FLNK, "SIOC:BPN16:TR01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:TR01:HEARTBEATE05.B")
  field(INPB, "SIOC:BPN16:TR01:HEARTBEATE06.VAL")
}

record(calc, "SIOC:BPN16:TR01:HEARTBEATE05") {
  field(FLNK, "SIOC:BPN16:TR01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:TR01:HEARTBEATE04.B")
  field(INPB, "SIOC:BPN16:TR01:HEARTBEATE05.VAL")
}

record(calc, "SIOC:BPN16:TR01:HEARTBEATE04") {
  field(FLNK, "SIOC:BPN16:TR01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:TR01:HEARTBEATE03.B")
  field(INPB, "SIOC:BPN16:TR01:HEARTBEATE04.VAL")
}

record(calc, "SIOC:BPN16:TR01:HEARTBEATE03") {
  field(FLNK, "SIOC:BPN16:TR01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:TR01:HEARTBEATE02.B")
  field(INPB, "SIOC:BPN16:TR01:HEARTBEATE03.VAL")
}

record(calc, "SIOC:BPN16:TR01:HEARTBEATE02") {
  field(FLNK, "SIOC:BPN16:TR01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:TR01:HEARTBEATE01.B")
  field(INPB, "SIOC:BPN16:TR01:HEARTBEATE02.VAL")
}

record(calc, "SIOC:BPN16:TR01:HEARTBEATE01") {
  field(FLNK, "SIOC:BPN16:TR01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:TR01:HEARTBEATERR.VAL")
  field(INPB, "SIOC:BPN16:TR01:HEARTBEATE01.VAL")
}

record(calc, "SIOC:BPN16:TR01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:BPN16:TR01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:BPN16:TR01:HEARTBEATSUM") {
  field(FLNK, "SIOC:BPN16:TR01:HEARTBEATCLC")
  field(INP, "SIOC:BPN16:TR01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:BPN16:TR01:HEARTBEATE10") {
  field(FLNK, "SIOC:BPN16:TR01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:BPN16:TR01:HEARTBEATE09.B")
  field(INPB, "SIOC:BPN16:TR01:HEARTBEATE10.VAL")
}

record(calc, "SIOC:BPN16:TR01:HEARTBEATERR") {
  field(FLNK, "SIOC:BPN16:TR01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:BPN16:TR01:HEARTBEATCALC.A")
  field(INPB, "SIOC:BPN16:TR01:HEARTBEATCALC.B")
}

record(stringin, "SIOC:BPN16:TR01:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:BPN16:TR01:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:BPN16:TR01:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-sys0-fb03")
  info(autosaveFields,"VAL")
}

# String record to hold info about ioc, for example
# impact of rebooting. (Ideally we would have longer
# string for this. To be implemented later.)
record(stringout, "SIOC:IN20:TS04:INFO") {
  field(DESC, "SIOC:IN20:TS04 Info")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:IN20:TS04:CONTACT") {
  field(DESC, "IOC responsible engineer")
  field(VAL, "Carolina B Mattison (carolina)")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

# TODCHECK and TODSUM are used to compare the 
# IOC time-of-day with IOCManager's time-of-day
# and raise an alarm if the difference is 10 
# seconds or greater. See IOCManagerApp/src/todCheckSub.c
# for more details. TODDIFF stores the time difference.

record(aSub, "SIOC:IN20:TS04:TODCHECK") {
  field(SCAN, "2 second")
  field(SNAM, "TODCheck")
  field(FTA, "STRING")
  field(FTB, "STRING")
  field(FTC, "LONG")
  field(INPA, "$(iocmanager):TOD MS")
  field(INPB, "SIOC:IN20:TS04:TOD CA")
  field(INPC, "10")
# VALA holds difference between A and B (in seconds)
  field(FTVA, "LONG")
# VALB is 1 for ok, 0 for not synchronized
  field(FTVB, "LONG")
  field(FLNK, "SIOC:IN20:TS04:TODDIFF")
}

record(longin, "SIOC:IN20:TS04:TODDIFF") {
  field(DESC, "TOD error in seconds")
  field(ADEL, "1")
  field(INP,  "SIOC:IN20:TS04:TODCHECK.VALA MS")
  field(FLNK, "SIOC:IN20:TS04:TODCHECKVALID")
}

# If <ioc> is offline, TODCHECK
# does not execute subroutine,
# so check TODCHECK.SEVR. If INVALID,
# assume <ioc> offline and 
# set TODSUM to "Not synchronized"
record(calc, "SIOC:IN20:TS04:TODCHECKVALID") {
  field(CALC, "A=3?0:B")
  field(INPA, "SIOC:IN20:TS04:TODCHECK.SEVR")
  field(INPB, "SIOC:IN20:TS04:TODCHECK.VALB")
  field(FLNK, "SIOC:IN20:TS04:TODSUM")
}

record(bo, "SIOC:IN20:TS04:TODSUM") {
  field(DESC, "IOC timeofday status")
  field(DOL, "SIOC:IN20:TS04:TODCHECKVALID MS")
  field(OMSL, "closed_loop")
  field(ZNAM, "Not synchronized")
  field(ONAM, "Synchronized")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(calc, "SIOC:IN20:TS04:HEARTBEATCALC") {
  field(FLNK, "SIOC:IN20:TS04:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "SIOC:IN20:TS04:HEARTBEAT CA MS")
  field(INPB, "SIOC:IN20:TS04:HEARTBEATCALC.VAL")
  field(SCAN, "2 second")
}

record(bi, "SIOC:IN20:TS04:HEARTBEATOK") {
  field(FLNK, "SIOC:IN20:TS04:HEARTBEATE01")
  field(INP, "SIOC:IN20:TS04:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "SIOC:IN20:TS04:HEARTBEATECT") {
  field(FLNK, "SIOC:IN20:TS04:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "SIOC:IN20:TS04:HEARTBEATE01.VAL")
  field(INPB, "SIOC:IN20:TS04:HEARTBEATE02.VAL")
  field(INPC, "SIOC:IN20:TS04:HEARTBEATE03.VAL")
  field(INPD, "SIOC:IN20:TS04:HEARTBEATE04.VAL")
  field(INPE, "SIOC:IN20:TS04:HEARTBEATE05.VAL")
  field(INPF, "SIOC:IN20:TS04:HEARTBEATE06.VAL")
  field(INPG, "SIOC:IN20:TS04:HEARTBEATE07.VAL")
  field(INPH, "SIOC:IN20:TS04:HEARTBEATE08.VAL")
  field(INPI, "SIOC:IN20:TS04:HEARTBEATE09.VAL")
  field(INPJ, "SIOC:IN20:TS04:HEARTBEATE10.VAL")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HIGH, "2")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "SIOC:IN20:TS04:HEARTBEATE09") {
  field(FLNK, "SIOC:IN20:TS04:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "SIOC:IN20:TS04:HEARTBEATE08.B")
  field(INPB, "SIOC:IN20:TS04:HEARTBEATE09.VAL")
}

record(calc, "SIOC:IN20:TS04:HEARTBEATE08") {
  field(FLNK, "SIOC:IN20:TS04:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "SIOC:IN20:TS04:HEARTBEATE07.B")
  field(INPB, "SIOC:IN20:TS04:HEARTBEATE08.VAL")
}

record(calc, "SIOC:IN20:TS04:HEARTBEATE07") {
  field(FLNK, "SIOC:IN20:TS04:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "SIOC:IN20:TS04:HEARTBEATE06.B")
  field(INPB, "SIOC:IN20:TS04:HEARTBEATE07.VAL")
}

record(calc, "SIOC:IN20:TS04:HEARTBEATE06") {
  field(FLNK, "SIOC:IN20:TS04:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "SIOC:IN20:TS04:HEARTBEATE05.B")
  field(INPB, "SIOC:IN20:TS04:HEARTBEATE06.VAL")
}

record(calc, "SIOC:IN20:TS04:HEARTBEATE05") {
  field(FLNK, "SIOC:IN20:TS04:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "SIOC:IN20:TS04:HEARTBEATE04.B")
  field(INPB, "SIOC:IN20:TS04:HEARTBEATE05.VAL")
}

record(calc, "SIOC:IN20:TS04:HEARTBEATE04") {
  field(FLNK, "SIOC:IN20:TS04:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "SIOC:IN20:TS04:HEARTBEATE03.B")
  field(INPB, "SIOC:IN20:TS04:HEARTBEATE04.VAL")
}

record(calc, "SIOC:IN20:TS04:HEARTBEATE03") {
  field(FLNK, "SIOC:IN20:TS04:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "SIOC:IN20:TS04:HEARTBEATE02.B")
  field(INPB, "SIOC:IN20:TS04:HEARTBEATE03.VAL")
}

record(calc, "SIOC:IN20:TS04:HEARTBEATE02") {
  field(FLNK, "SIOC:IN20:TS04:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "SIOC:IN20:TS04:HEARTBEATE01.B")
  field(INPB, "SIOC:IN20:TS04:HEARTBEATE02.VAL")
}

record(calc, "SIOC:IN20:TS04:HEARTBEATE01") {
  field(FLNK, "SIOC:IN20:TS04:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "SIOC:IN20:TS04:HEARTBEATERR.VAL")
  field(INPB, "SIOC:IN20:TS04:HEARTBEATE01.VAL")
}

record(calc, "SIOC:IN20:TS04:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "SIOC:IN20:TS04:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "SIOC:IN20:TS04:HEARTBEATSUM") {
  field(FLNK, "SIOC:IN20:TS04:HEARTBEATCLC")
  field(INP, "SIOC:IN20:TS04:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(calc, "SIOC:IN20:TS04:HEARTBEATE10") {
  field(FLNK, "SIOC:IN20:TS04:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "SIOC:IN20:TS04:HEARTBEATE09.B")
  field(INPB, "SIOC:IN20:TS04:HEARTBEATE10.VAL")
}

record(calc, "SIOC:IN20:TS04:HEARTBEATERR") {
  field(FLNK, "SIOC:IN20:TS04:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "SIOC:IN20:TS04:HEARTBEATCALC.A")
  field(INPB, "SIOC:IN20:TS04:HEARTBEATCALC.B")
}

record(stringin, "SIOC:IN20:TS04:ALIAS") {
  field(DESC, "Device")
  field(PINI, "YES")
  field(VAL, "S20")
  info(autosaveFields,"VAL")
}

# To be deprecated; replaced by ALIAS
record(stringin, "SIOC:IN20:TS04:SLCNAME") {
  field(PINI, "YES")
  field(VAL, "S20")
  info(autosaveFields,"VAL")
}

record(stringin, "SIOC:IN20:TS04:LOC") {
  field(PINI, "YES")
  field(VAL, "cpu-bpn20-sp01")
  info(autosaveFields,"VAL")
}