#! Generated by VisualDCT v2.5 #! DBDSTART #! DBDEND record(bi, "CRAT:IN20:PM01:POWERSTATE") { field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ZNAM, "OFF") field(ONAM, "ON") field(SDIS, "CRAT:IN20:PM01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bi, "CRAT:IN20:PM01:FANTRAY") { field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ONAM, "OK") field(SDIS, "CRAT:IN20:PM01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:PM01:FANSPEED") { field(EGU, "RPM") field(LOLO, "1150") field(HHSV, "NO_ALARM") field(LLSV, "MAJOR") field(HSV, "NO_ALARM") field(LSV, "NO_ALARM") field(SDIS, "CRAT:IN20:PM01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:PM01:CHU0_I") { field(PREC, "1") field(EGU, "A") field(SDIS, "CRAT:IN20:PM01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(stringin, "CRAT:IN20:PM01:CHU0_NAME") { field(SDIS, "CRAT:IN20:PM01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bi, "CRAT:IN20:PM01:CHU0_STATUS") { field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ONAM, "OK") field(SDIS, "CRAT:IN20:PM01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:PM01:CHU0_V") { field(PREC, "2") field(EGU, "V") field(HOPR, "15") field(LOPR, "0") field(HIHI, "5.25") field(LOLO, "4.875") field(HIGH, "5.2") field(LOW, "4.9") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:PM01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(stringin, "CRAT:IN20:PM01:CHU1_NAME") { field(SDIS, "CRAT:IN20:PM01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:PM01:CHU1_V") { field(PREC, "1") field(EGU, "V") field(HOPR, "15") field(LOPR, "0") field(HIHI, "12.6") field(LOLO, "11.7") field(HIGH, "12.48") field(LOW, "11.76") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:PM01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:PM01:CHU1_I") { field(PREC, "1") field(EGU, "A") field(SDIS, "CRAT:IN20:PM01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bi, "CRAT:IN20:PM01:CHU1_STATUS") { field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ONAM, "OK") field(SDIS, "CRAT:IN20:PM01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(stringin, "CRAT:IN20:PM01:CHU3_NAME") { field(SDIS, "CRAT:IN20:PM01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:PM01:CHU3_V") { field(PREC, "2") field(EGU, "V") field(HOPR, "15") field(LOPR, "0") field(HIHI, "3.465") field(LOLO, "3.2175") field(HIGH, "3.432") field(LOW, "3.234") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:PM01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:PM01:CHU3_I") { field(PREC, "1") field(EGU, "A") field(SDIS, "CRAT:IN20:PM01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bi, "CRAT:IN20:PM01:CHU3_STATUS") { field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ONAM, "OK") field(SDIS, "CRAT:IN20:PM01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(stringin, "CRAT:IN20:PM01:CHU5_NAME") { field(SDIS, "CRAT:IN20:PM01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:PM01:CHU5_I") { field(PREC, "1") field(EGU, "A") field(SDIS, "CRAT:IN20:PM01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bi, "CRAT:IN20:PM01:CHU5_STATUS") { field(FLNK, "CRAT:IN20:PM01:POWERCALC") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ONAM, "OK") field(SDIS, "CRAT:IN20:PM01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bo, "CRAT:IN20:PM01:MAINPOWER") { field(DTYP, "stream") field(OUT, "@crat_wiener_21slot.proto.db setMainPower crat-in20-pm01") } record(bo, "CRAT:IN20:PM01:VMERESET") { field(DTYP, "stream") field(OUT, "@crat_wiener_21slot.proto.db setVmeSysReset crat-in20-pm01") } record(bo, "CRAT:IN20:PM01:FANSLOWER") { field(DTYP, "stream") field(OUT, "@crat_wiener_21slot.proto.db setFanSlower crat-in20-pm01") } record(bo, "CRAT:IN20:PM01:FANFASTER") { field(DTYP, "stream") field(OUT, "@crat_wiener_21slot.proto.db setFanFaster crat-in20-pm01") } record(ai, "CRAT:IN20:PM01:CHU5_V") { field(PREC, "1") field(EGU, "V") field(HOPR, "15") field(LOPR, "0") field(HIHI, "12.6") field(LOLO, "11.7") field(HIGH, "12.48") field(LOW, "11.76") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:PM01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(seq, "CRAT:IN20:PM01:POWERSEQ1") { field(SELM, "Specified") field(SELL, "CRAT:IN20:PM01:POWERCALC") field(LNK1, "CRAT:IN20:PM01:MAINPOWER PP") field(FLNK, "CRAT:IN20:PM01:POWERMSGCALC") } record(calc, "CRAT:IN20:PM01:POWERCALC") { field(FLNK, "CRAT:IN20:PM01:POWERSEQ1") field(CALC, "A=1&&B=1&&C=0?1:A=0&&B=0&&C=1?1:0") field(INPA, "CRAT:IN20:PM01:POWERSTATE") } record(bo, "CRAT:IN20:PM01:POWEROFF") { field(HIGH, "9") field(OUT, "CRAT:IN20:PM01:POWERCALC.B") field(FLNK, "CRAT:IN20:PM01:POWERMSGCALC") } record(bo, "CRAT:IN20:PM01:POWERON") { field(OUT, "CRAT:IN20:PM01:POWERCALC.C") field(HIGH, "9") field(FLNK, "CRAT:IN20:PM01:POWERMSGCALC") } record(seq, "CRAT:IN20:PM01:HARDRESETSEQ") { field(SELM, "All") field(LNK1, "CRAT:IN20:PM01:POWEROFF PP") field(DOL1, "1") field(DLY2, "10") field(DOL2, "1") field(LNK2, "CRAT:IN20:PM01:POWERON PP") field(DLY3, "10") field(DOL3, "0") field(LNK3, "CRAT:IN20:PM01:HARDRESET PP") } record(bo, "CRAT:IN20:PM01:HARDRESET") { field(OUT, "CRAT:IN20:PM01:HARDRESETSEQ.PROC PP") field(FLNK, "CRAT:IN20:PM01:POWERMSGCALC") } record(calc, "CRAT:IN20:PM01:POWERMSGCALC") { field(FLNK, "CRAT:IN20:PM01:POWERMSG") field(CALC, "C?3:A=1&&B=0?0:A=0&&B=1?1:A=1&&B=1?2:4") field(INPA, "CRAT:IN20:PM01:POWERCALC.B") field(INPB, "CRAT:IN20:PM01:POWERCALC.C") field(INPC, "CRAT:IN20:PM01:HARDRESET") } record(mbbi, "CRAT:IN20:PM01:POWERMSG") { field(INP, "CRAT:IN20:PM01:POWERMSGCALC.VAL") field(ZRST, "TURNING_OFF") field(ONST, "TURNING_ON") field(TWST, "ERROR") field(THST, "HARD_RESETTING") field(FRST, " ") field(ZRSV, "MINOR") field(ONSV, "MINOR") field(TWSV, "MAJOR") field(THSV, "MINOR") field(FRSV, "NO_ALARM") } record(ai, "CRAT:IN20:PM01:TYPE") { field(DESC, "Wiener 21 Slot VME Crate") field(PINI, "YES") field(VAL, "2") } record(stringin, "CRAT:IN20:PM01:2NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:PM01:3NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:PM01:4NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:PM01:5NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:PM01:6NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:PM01:7NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:PM01:1NAME") { field(PINI, "YES") field(VAL, "IOC:IN20:PM01") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:PM01:8NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:PM01:9NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:PM01:10NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:PM01:11NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:PM01:12NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:PM01:13NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:PM01:14NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:PM01:15NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:PM01:16NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:PM01:17NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:PM01:18NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:PM01:19NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:PM01:20NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:PM01:21NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(calc, "CRAT:IN20:PM01:FANTEMP") { field(SCAN, "Passive") field(CALC, "A>0?(A-0)/1:A") field(EGU, "DegF") field(PREC, "0") field(HOPR, "120") field(LOPR, "20") field(HIHI, "131") field(LOLO, "-1") field(HIGH, "113") field(LOW, "-1") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(ADEL, "1") field(MDEL, "1") field(SDIS, "CRAT:IN20:PM01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(stringin, "CRAT:IN20:PM01:FWVERSION") { field(SCAN, "5 second") field(DTYP, "stream") field(INP, "@crat_wiener_21slot.proto.db getStatus(CRAT:IN20:PM01) crat-in20-pm01") } record(stringin, "CRAT:IN20:PM01:LOC") { field(PINI, "YES") field(VAL, "LKG-1410") info(autosaveFields,"VAL") } record(calc, "CRAT:IN20:PM01:STATSUMY") { field(DESC, "Alarm summary for crate") field(INPA, "CRAT:IN20:PM01:FWVERSION.SEVR NPP MS") field(INPB, "CRAT:IN20:PM01:FANTEMP.SEVR NPP MS") field(INPC, "CRAT:IN20:PM01:CHU0_V.SEVR NPP MS") field(INPD, "CRAT:IN20:PM01:CHU1_V.SEVR NPP MS") field(INPE, "CRAT:IN20:PM01:CHU3_V.SEVR NPP MS") field(INPF, "CRAT:IN20:PM01:CHU5_V.SEVR NPP MS") field(INPG, "CRAT:IN20:PM01:FANSPEED.SEVR NPP MS") field(INPH, "CRAT:IN20:PM01:FANTRAY.SEVR NPP MS") field(SCAN, "1 second") field(CALC, "A+B+C+D+E+F+G+H") } #! Further lines contain data used by VisualDCT #! View(653,461,0.6) #! Record("CRAT:IN20:PM01:POWERSTATE",860,92,0,0,"CRAT:IN20:PM01:POWERSTATE") #! Field("CRAT:IN20:PM01:POWERSTATE.FLNK",16777215,1,"CRAT:IN20:PM01:POWERSTATE.FLNK") #! Link("CRAT:IN20:PM01:POWERSTATE.FLNK","CRAT:IN20:PM01:FANTRAY") #! Field("CRAT:IN20:PM01:POWERSTATE.VAL",16777215,0,"CRAT:IN20:PM01:POWERSTATE.VAL") #! Record("CRAT:IN20:PM01:FANTRAY",1360,107,0,0,"CRAT:IN20:PM01:FANTRAY") #! Field("CRAT:IN20:PM01:FANTRAY.FLNK",16777215,1,"CRAT:IN20:PM01:FANTRAY.FLNK") #! Link("CRAT:IN20:PM01:FANTRAY.FLNK","CRAT:IN20:PM01:FANSPEED") #! Record("CRAT:IN20:PM01:FANSPEED",1640,64,0,0,"CRAT:IN20:PM01:FANSPEED") #! Field("CRAT:IN20:PM01:FANSPEED.FLNK",16777215,1,"CRAT:IN20:PM01:FANSPEED.FLNK") #! Link("CRAT:IN20:PM01:FANSPEED.FLNK","CRAT:IN20:PM01:FANTEMP") #! Field("CRAT:IN20:PM01:FANSPEED.SEVR",16777215,1,"CRAT:IN20:PM01:FANSPEED.SEVR") #! Record("CRAT:IN20:PM01:CHU0_I",1420,362,0,0,"CRAT:IN20:PM01:CHU0_I") #! Field("CRAT:IN20:PM01:CHU0_I.FLNK",16777215,1,"CRAT:IN20:PM01:CHU0_I.FLNK") #! Link("CRAT:IN20:PM01:CHU0_I.FLNK","CRAT:IN20:PM01:CHU0_STATUS") #! Record("CRAT:IN20:PM01:CHU0_NAME",840,390,0,1,"CRAT:IN20:PM01:CHU0_NAME") #! Field("CRAT:IN20:PM01:CHU0_NAME.FLNK",16777215,1,"CRAT:IN20:PM01:CHU0_NAME.FLNK") #! Link("CRAT:IN20:PM01:CHU0_NAME.FLNK","CRAT:IN20:PM01:CHU0_V") #! Record("CRAT:IN20:PM01:CHU0_STATUS",1680,367,0,0,"CRAT:IN20:PM01:CHU0_STATUS") #! Field("CRAT:IN20:PM01:CHU0_STATUS.FLNK",16777215,0,"CRAT:IN20:PM01:CHU0_STATUS.FLNK") #! Link("CRAT:IN20:PM01:CHU0_STATUS.FLNK","CRAT:IN20:PM01:CHU1_NAME") #! Record("CRAT:IN20:PM01:CHU0_V",1160,197,0,0,"CRAT:IN20:PM01:CHU0_V") #! Field("CRAT:IN20:PM01:CHU0_V.FLNK",16777215,1,"CRAT:IN20:PM01:CHU0_V.FLNK") #! Link("CRAT:IN20:PM01:CHU0_V.FLNK","CRAT:IN20:PM01:CHU0_I") #! Field("CRAT:IN20:PM01:CHU0_V.SEVR",16777215,1,"CRAT:IN20:PM01:CHU0_V.SEVR") #! Record("CRAT:IN20:PM01:CHU1_NAME",840,710,0,1,"CRAT:IN20:PM01:CHU1_NAME") #! Field("CRAT:IN20:PM01:CHU1_NAME.FLNK",16777215,1,"CRAT:IN20:PM01:CHU1_NAME.FLNK") #! Link("CRAT:IN20:PM01:CHU1_NAME.FLNK","CRAT:IN20:PM01:CHU1_V") #! Record("CRAT:IN20:PM01:CHU1_V",1140,517,0,0,"CRAT:IN20:PM01:CHU1_V") #! Field("CRAT:IN20:PM01:CHU1_V.FLNK",16777215,1,"CRAT:IN20:PM01:CHU1_V.FLNK") #! Link("CRAT:IN20:PM01:CHU1_V.FLNK","CRAT:IN20:PM01:CHU1_I") #! Field("CRAT:IN20:PM01:CHU1_V.SEVR",16777215,1,"CRAT:IN20:PM01:CHU1_V.SEVR") #! Record("CRAT:IN20:PM01:CHU1_I",1420,682,0,0,"CRAT:IN20:PM01:CHU1_I") #! Field("CRAT:IN20:PM01:CHU1_I.FLNK",16777215,1,"CRAT:IN20:PM01:CHU1_I.FLNK") #! Link("CRAT:IN20:PM01:CHU1_I.FLNK","CRAT:IN20:PM01:CHU1_STATUS") #! Record("CRAT:IN20:PM01:CHU1_STATUS",1680,687,0,0,"CRAT:IN20:PM01:CHU1_STATUS") #! Field("CRAT:IN20:PM01:CHU1_STATUS.FLNK",16777215,0,"CRAT:IN20:PM01:CHU1_STATUS.FLNK") #! Link("CRAT:IN20:PM01:CHU1_STATUS.FLNK","CRAT:IN20:PM01:CHU3_NAME") #! Record("CRAT:IN20:PM01:CHU3_NAME",840,1030,0,1,"CRAT:IN20:PM01:CHU3_NAME") #! Field("CRAT:IN20:PM01:CHU3_NAME.FLNK",16777215,1,"CRAT:IN20:PM01:CHU3_NAME.FLNK") #! Link("CRAT:IN20:PM01:CHU3_NAME.FLNK","CRAT:IN20:PM01:CHU3_V") #! Record("CRAT:IN20:PM01:CHU3_V",1120,837,0,0,"CRAT:IN20:PM01:CHU3_V") #! Field("CRAT:IN20:PM01:CHU3_V.FLNK",16777215,1,"CRAT:IN20:PM01:CHU3_V.FLNK") #! Link("CRAT:IN20:PM01:CHU3_V.FLNK","CRAT:IN20:PM01:CHU3_I") #! Field("CRAT:IN20:PM01:CHU3_V.SEVR",16777215,1,"CRAT:IN20:PM01:CHU3_V.SEVR") #! Record("CRAT:IN20:PM01:CHU3_I",1420,1002,0,0,"CRAT:IN20:PM01:CHU3_I") #! Field("CRAT:IN20:PM01:CHU3_I.FLNK",16777215,1,"CRAT:IN20:PM01:CHU3_I.FLNK") #! Link("CRAT:IN20:PM01:CHU3_I.FLNK","CRAT:IN20:PM01:CHU3_STATUS") #! Record("CRAT:IN20:PM01:CHU3_STATUS",1680,1007,0,0,"CRAT:IN20:PM01:CHU3_STATUS") #! Field("CRAT:IN20:PM01:CHU3_STATUS.FLNK",16777215,0,"CRAT:IN20:PM01:CHU3_STATUS.FLNK") #! Link("CRAT:IN20:PM01:CHU3_STATUS.FLNK","CRAT:IN20:PM01:CHU5_NAME") #! Record("CRAT:IN20:PM01:CHU5_NAME",840,1370,0,1,"CRAT:IN20:PM01:CHU5_NAME") #! Field("CRAT:IN20:PM01:CHU5_NAME.FLNK",16777215,1,"CRAT:IN20:PM01:CHU5_NAME.FLNK") #! Link("CRAT:IN20:PM01:CHU5_NAME.FLNK","CRAT:IN20:PM01:CHU5_V") #! Record("CRAT:IN20:PM01:CHU5_I",1420,1342,0,0,"CRAT:IN20:PM01:CHU5_I") #! Field("CRAT:IN20:PM01:CHU5_I.FLNK",16777215,1,"CRAT:IN20:PM01:CHU5_I.FLNK") #! Link("CRAT:IN20:PM01:CHU5_I.FLNK","CRAT:IN20:PM01:CHU5_STATUS") #! Record("CRAT:IN20:PM01:CHU5_STATUS",1680,1367,0,0,"CRAT:IN20:PM01:CHU5_STATUS") #! Field("CRAT:IN20:PM01:CHU5_STATUS.FLNK",16777215,0,"CRAT:IN20:PM01:CHU5_STATUS.FLNK") #! Link("CRAT:IN20:PM01:CHU5_STATUS.FLNK","CRAT:IN20:PM01:POWERCALC") #! Record("CRAT:IN20:PM01:MAINPOWER",1740,1875,0,1,"CRAT:IN20:PM01:MAINPOWER") #! Field("CRAT:IN20:PM01:MAINPOWER.VAL",16777215,0,"CRAT:IN20:PM01:MAINPOWER.VAL") #! Record("CRAT:IN20:PM01:VMERESET",360,115,0,1,"CRAT:IN20:PM01:VMERESET") #! Record("CRAT:IN20:PM01:FANSLOWER",360,315,0,1,"CRAT:IN20:PM01:FANSLOWER") #! Record("CRAT:IN20:PM01:FANFASTER",360,215,0,1,"CRAT:IN20:PM01:FANFASTER") #! Record("CRAT:IN20:PM01:CHU5_V",1100,1197,0,0,"CRAT:IN20:PM01:CHU5_V") #! Field("CRAT:IN20:PM01:CHU5_V.FLNK",16777215,1,"CRAT:IN20:PM01:CHU5_V.FLNK") #! Link("CRAT:IN20:PM01:CHU5_V.FLNK","CRAT:IN20:PM01:CHU5_I") #! Field("CRAT:IN20:PM01:CHU5_V.SEVR",16777215,1,"CRAT:IN20:PM01:CHU5_V.SEVR") #! Record("CRAT:IN20:PM01:POWERSEQ1",1420,1707,0,0,"CRAT:IN20:PM01:POWERSEQ1") #! Field("CRAT:IN20:PM01:POWERSEQ1.LNK1",16777215,1,"CRAT:IN20:PM01:POWERSEQ1.LNK1") #! Link("CRAT:IN20:PM01:POWERSEQ1.LNK1","CRAT:IN20:PM01:MAINPOWER.VAL") #! Field("CRAT:IN20:PM01:POWERSEQ1.SELL",16777215,0,"CRAT:IN20:PM01:POWERSEQ1.SELL") #! Link("CRAT:IN20:PM01:POWERSEQ1.SELL","CRAT:IN20:PM01:POWERCALC.VAL") #! Field("CRAT:IN20:PM01:POWERSEQ1.FLNK",16777215,0,"CRAT:IN20:PM01:POWERSEQ1.FLNK") #! Link("CRAT:IN20:PM01:POWERSEQ1.FLNK","CRAT:IN20:PM01:POWERMSGCALC") #! Record("CRAT:IN20:PM01:POWERCALC",960,1702,0,1,"CRAT:IN20:PM01:POWERCALC") #! Field("CRAT:IN20:PM01:POWERCALC.INPA",16777215,0,"CRAT:IN20:PM01:POWERCALC.INPA") #! Link("CRAT:IN20:PM01:POWERCALC.INPA","CRAT:IN20:PM01:POWERSTATE.VAL") #! Field("CRAT:IN20:PM01:POWERCALC.FLNK",16777215,1,"CRAT:IN20:PM01:POWERCALC.FLNK") #! Link("CRAT:IN20:PM01:POWERCALC.FLNK","CRAT:IN20:PM01:POWERSEQ1") #! Field("CRAT:IN20:PM01:POWERCALC.VAL",16777215,1,"CRAT:IN20:PM01:POWERCALC.VAL") #! Field("CRAT:IN20:PM01:POWERCALC.B",16777215,0,"CRAT:IN20:PM01:POWERCALC.B") #! Field("CRAT:IN20:PM01:POWERCALC.C",16777215,0,"CRAT:IN20:PM01:POWERCALC.C") #! Record("CRAT:IN20:PM01:POWEROFF",620,1762,0,1,"CRAT:IN20:PM01:POWEROFF") #! Field("CRAT:IN20:PM01:POWEROFF.OUT",16777215,1,"CRAT:IN20:PM01:POWEROFF.OUT") #! Link("CRAT:IN20:PM01:POWEROFF.OUT","CRAT:IN20:PM01:POWERCALC.B") #! Field("CRAT:IN20:PM01:POWEROFF.VAL",16777215,0,"CRAT:IN20:PM01:POWEROFF.VAL") #! Field("CRAT:IN20:PM01:POWEROFF.FLNK",16777215,1,"CRAT:IN20:PM01:POWEROFF.FLNK") #! Link("CRAT:IN20:PM01:POWEROFF.FLNK","CRAT:IN20:PM01:POWERMSGCALC") #! Record("CRAT:IN20:PM01:POWERON",620,1942,0,1,"CRAT:IN20:PM01:POWERON") #! Field("CRAT:IN20:PM01:POWERON.VAL",16777215,0,"CRAT:IN20:PM01:POWERON.VAL") #! Field("CRAT:IN20:PM01:POWERON.OUT",16777215,1,"CRAT:IN20:PM01:POWERON.OUT") #! Link("CRAT:IN20:PM01:POWERON.OUT","CRAT:IN20:PM01:POWERCALC.C") #! Field("CRAT:IN20:PM01:POWERON.FLNK",16777215,1,"CRAT:IN20:PM01:POWERON.FLNK") #! Link("CRAT:IN20:PM01:POWERON.FLNK","CRAT:IN20:PM01:POWERMSGCALC") #! Record("CRAT:IN20:PM01:HARDRESETSEQ",340,1735,0,1,"CRAT:IN20:PM01:HARDRESETSEQ") #! Field("CRAT:IN20:PM01:HARDRESETSEQ.LNK1",16777215,1,"CRAT:IN20:PM01:HARDRESETSEQ.LNK1") #! Link("CRAT:IN20:PM01:HARDRESETSEQ.LNK1","CRAT:IN20:PM01:POWEROFF.VAL") #! Field("CRAT:IN20:PM01:HARDRESETSEQ.LNK2",16777215,1,"CRAT:IN20:PM01:HARDRESETSEQ.LNK2") #! Link("CRAT:IN20:PM01:HARDRESETSEQ.LNK2","CRAT:IN20:PM01:POWERON.VAL") #! Field("CRAT:IN20:PM01:HARDRESETSEQ.PROC",16777215,0,"CRAT:IN20:PM01:HARDRESETSEQ.PROC") #! Field("CRAT:IN20:PM01:HARDRESETSEQ.LNK3",16777215,0,"CRAT:IN20:PM01:HARDRESETSEQ.LNK3") #! Link("CRAT:IN20:PM01:HARDRESETSEQ.LNK3","CRAT:IN20:PM01:HARDRESET.VAL") #! Record("CRAT:IN20:PM01:HARDRESET",20,1975,0,1,"CRAT:IN20:PM01:HARDRESET") #! Field("CRAT:IN20:PM01:HARDRESET.OUT",16777215,1,"CRAT:IN20:PM01:HARDRESET.OUT") #! Link("CRAT:IN20:PM01:HARDRESET.OUT","CRAT:IN20:PM01:HARDRESETSEQ.PROC") #! Field("CRAT:IN20:PM01:HARDRESET.VAL",16777215,1,"CRAT:IN20:PM01:HARDRESET.VAL") #! Field("CRAT:IN20:PM01:HARDRESET.FLNK",16777215,1,"CRAT:IN20:PM01:HARDRESET.FLNK") #! Link("CRAT:IN20:PM01:HARDRESET.FLNK","CRAT:IN20:PM01:POWERMSGCALC") #! Record("CRAT:IN20:PM01:POWERMSGCALC",1020,2172,0,1,"CRAT:IN20:PM01:POWERMSGCALC") #! Field("CRAT:IN20:PM01:POWERMSGCALC.INPA",16777215,0,"CRAT:IN20:PM01:POWERMSGCALC.INPA") #! Link("CRAT:IN20:PM01:POWERMSGCALC.INPA","CRAT:IN20:PM01:POWERCALC.B") #! Field("CRAT:IN20:PM01:POWERMSGCALC.INPB",16777215,0,"CRAT:IN20:PM01:POWERMSGCALC.INPB") #! Link("CRAT:IN20:PM01:POWERMSGCALC.INPB","CRAT:IN20:PM01:POWERCALC.C") #! Field("CRAT:IN20:PM01:POWERMSGCALC.INPC",16777215,0,"CRAT:IN20:PM01:POWERMSGCALC.INPC") #! Link("CRAT:IN20:PM01:POWERMSGCALC.INPC","CRAT:IN20:PM01:HARDRESET.VAL") #! Field("CRAT:IN20:PM01:POWERMSGCALC.FLNK",16777215,1,"CRAT:IN20:PM01:POWERMSGCALC.FLNK") #! Link("CRAT:IN20:PM01:POWERMSGCALC.FLNK","CRAT:IN20:PM01:POWERMSG") #! Field("CRAT:IN20:PM01:POWERMSGCALC.VAL",16777215,1,"CRAT:IN20:PM01:POWERMSGCALC.VAL") #! Record("CRAT:IN20:PM01:POWERMSG",1360,2167,0,0,"CRAT:IN20:PM01:POWERMSG") #! Field("CRAT:IN20:PM01:POWERMSG.INP",16777215,0,"CRAT:IN20:PM01:POWERMSG.INP") #! Link("CRAT:IN20:PM01:POWERMSG.INP","CRAT:IN20:PM01:POWERMSGCALC.VAL") #! Record("CRAT:IN20:PM01:TYPE",360,502,0,1,"CRAT:IN20:PM01:TYPE") #! Record("CRAT:IN20:PM01:2NAME",40,775,0,1,"CRAT:IN20:PM01:2NAME") #! Record("CRAT:IN20:PM01:3NAME",40,875,0,1,"CRAT:IN20:PM01:3NAME") #! Record("CRAT:IN20:PM01:4NAME",40,975,0,1,"CRAT:IN20:PM01:4NAME") #! Record("CRAT:IN20:PM01:5NAME",40,1075,0,1,"CRAT:IN20:PM01:5NAME") #! Record("CRAT:IN20:PM01:6NAME",40,1175,0,1,"CRAT:IN20:PM01:6NAME") #! Record("CRAT:IN20:PM01:7NAME",40,1275,0,1,"CRAT:IN20:PM01:7NAME") #! Record("CRAT:IN20:PM01:1NAME",40,675,0,1,"CRAT:IN20:PM01:1NAME") #! Record("CRAT:IN20:PM01:8NAME",240,675,0,1,"CRAT:IN20:PM01:8NAME") #! Record("CRAT:IN20:PM01:9NAME",240,775,0,1,"CRAT:IN20:PM01:9NAME") #! Record("CRAT:IN20:PM01:10NAME",240,875,0,1,"CRAT:IN20:PM01:10NAME") #! Record("CRAT:IN20:PM01:11NAME",240,975,0,1,"CRAT:IN20:PM01:11NAME") #! Record("CRAT:IN20:PM01:12NAME",240,1075,0,1,"CRAT:IN20:PM01:12NAME") #! Record("CRAT:IN20:PM01:13NAME",240,1175,0,1,"CRAT:IN20:PM01:13NAME") #! Record("CRAT:IN20:PM01:14NAME",240,1275,0,1,"CRAT:IN20:PM01:14NAME") #! Record("CRAT:IN20:PM01:15NAME",440,675,0,1,"CRAT:IN20:PM01:15NAME") #! Record("CRAT:IN20:PM01:16NAME",440,775,0,1,"CRAT:IN20:PM01:16NAME") #! Record("CRAT:IN20:PM01:17NAME",440,875,0,1,"CRAT:IN20:PM01:17NAME") #! Record("CRAT:IN20:PM01:18NAME",440,975,0,1,"CRAT:IN20:PM01:18NAME") #! Record("CRAT:IN20:PM01:19NAME",440,1075,0,1,"CRAT:IN20:PM01:19NAME") #! Record("CRAT:IN20:PM01:20NAME",440,1175,0,1,"CRAT:IN20:PM01:20NAME") #! Record("CRAT:IN20:PM01:21NAME",440,1275,0,1,"CRAT:IN20:PM01:21NAME") #! Record("CRAT:IN20:PM01:FANTEMP",1940,14,0,0,"CRAT:IN20:PM01:FANTEMP") #! Field("CRAT:IN20:PM01:FANTEMP.FLNK",16777215,0,"CRAT:IN20:PM01:FANTEMP.FLNK") #! Link("CRAT:IN20:PM01:FANTEMP.FLNK","CRAT:IN20:PM01:CHU0_NAME") #! Field("CRAT:IN20:PM01:FANTEMP.SEVR",16777215,1,"CRAT:IN20:PM01:FANTEMP.SEVR") #! Record("CRAT:IN20:PM01:FWVERSION",560,67,0,1,"CRAT:IN20:PM01:FWVERSION") #! Field("CRAT:IN20:PM01:FWVERSION.FLNK",16777215,1,"CRAT:IN20:PM01:FWVERSION.FLNK") #! Link("CRAT:IN20:PM01:FWVERSION.FLNK","CRAT:IN20:PM01:POWERSTATE") #! Field("CRAT:IN20:PM01:FWVERSION.SEVR",16777215,1,"CRAT:IN20:PM01:FWVERSION.SEVR") #! Record("CRAT:IN20:PM01:LOC",120,155,0,1,"CRAT:IN20:PM01:LOC") #! Record("CRAT:IN20:PM01:STATSUMY",2380,1380,0,1,"CRAT:IN20:PM01:STATSUMY") #! Field("CRAT:IN20:PM01:STATSUMY.INPA",16777215,0,"CRAT:IN20:PM01:STATSUMY.INPA") #! Link("CRAT:IN20:PM01:STATSUMY.INPA","CRAT:IN20:PM01:FWVERSION.SEVR") #! Field("CRAT:IN20:PM01:STATSUMY.INPB",16777215,0,"CRAT:IN20:PM01:STATSUMY.INPB") #! Link("CRAT:IN20:PM01:STATSUMY.INPB","CRAT:IN20:PM01:FANTEMP.SEVR") #! Field("CRAT:IN20:PM01:STATSUMY.INPC",16777215,0,"CRAT:IN20:PM01:STATSUMY.INPC") #! Link("CRAT:IN20:PM01:STATSUMY.INPC","CRAT:IN20:PM01:CHU0_V.SEVR") #! Field("CRAT:IN20:PM01:STATSUMY.INPD",16777215,0,"CRAT:IN20:PM01:STATSUMY.INPD") #! Link("CRAT:IN20:PM01:STATSUMY.INPD","CRAT:IN20:PM01:CHU1_V.SEVR") #! Field("CRAT:IN20:PM01:STATSUMY.INPE",16777215,0,"CRAT:IN20:PM01:STATSUMY.INPE") #! Link("CRAT:IN20:PM01:STATSUMY.INPE","CRAT:IN20:PM01:CHU3_V.SEVR") #! Field("CRAT:IN20:PM01:STATSUMY.INPF",16777215,0,"CRAT:IN20:PM01:STATSUMY.INPF") #! Link("CRAT:IN20:PM01:STATSUMY.INPF","CRAT:IN20:PM01:CHU5_V.SEVR") #! Field("CRAT:IN20:PM01:STATSUMY.INPG",16777215,0,"CRAT:IN20:PM01:STATSUMY.INPG") #! Link("CRAT:IN20:PM01:STATSUMY.INPG","CRAT:IN20:PM01:FANSPEED.SEVR") #! TextBox(TB0,40,1420,480,1740,1,"Dialog",12,1,16777215,"The web interface for this crate only provides a \"toggle power\" button.\nThere is no way to send a command to turn the power on or turn the power off.\nThe purpose of all these PVs is to provide POWERON and POWEROFF \nbuttons rather than the inferior toggle button.\n\nProcessing the POWERON record when the crate is off will turn it on. \nProcessing the POWEROFF record when the crate is on will turn it off.\nProcessing the HARDRESET record will first force the POWEROFF record\nto process, then it will force the POWERON record to process.\n\nThe POWERON and POWEROFF steps take about 10 seconds each: First the IOC\nmust wait to get new on/off status (which takes five seconds) before deciding\nwhether or not to toggle the crate power. Then it sends the toggle command\nand it takes another 5 seconds to see the change in on/off status.\n\nPOWERMSG contains a string that describes what is currently happening.\nIt is normally empty, but contains text if the power is being turned on, off, or \nreset.",null) #! Generated by VisualDCT v2.5 #! DBDSTART #! DBDEND record(bi, "CRAT:IN20:BP02:POWERSTATE") { field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ZNAM, "OFF") field(ONAM, "ON") field(SDIS, "CRAT:IN20:BP02:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bi, "CRAT:IN20:BP02:FANTRAY") { field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ONAM, "OK") field(SDIS, "CRAT:IN20:BP02:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:BP02:FANSPEED") { field(EGU, "RPM") field(LOLO, "1150") field(HHSV, "NO_ALARM") field(LLSV, "MAJOR") field(HSV, "NO_ALARM") field(LSV, "NO_ALARM") field(SDIS, "CRAT:IN20:BP02:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:BP02:CHU0_I") { field(PREC, "1") field(EGU, "A") field(SDIS, "CRAT:IN20:BP02:FWVERSION.SEVR CP MS") field(DISV, "20") } record(stringin, "CRAT:IN20:BP02:CHU0_NAME") { field(SDIS, "CRAT:IN20:BP02:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bi, "CRAT:IN20:BP02:CHU0_STATUS") { field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ONAM, "OK") field(SDIS, "CRAT:IN20:BP02:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:BP02:CHU0_V") { field(PREC, "2") field(EGU, "V") field(HOPR, "15") field(LOPR, "0") field(HIHI, "5.25") field(LOLO, "4.875") field(HIGH, "5.2") field(LOW, "4.9") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:BP02:FWVERSION.SEVR CP MS") field(DISV, "20") } record(stringin, "CRAT:IN20:BP02:CHU1_NAME") { field(SDIS, "CRAT:IN20:BP02:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:BP02:CHU1_V") { field(PREC, "1") field(EGU, "V") field(HOPR, "15") field(LOPR, "0") field(HIHI, "12.6") field(LOLO, "11.7") field(HIGH, "12.48") field(LOW, "11.76") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:BP02:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:BP02:CHU1_I") { field(PREC, "1") field(EGU, "A") field(SDIS, "CRAT:IN20:BP02:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bi, "CRAT:IN20:BP02:CHU1_STATUS") { field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ONAM, "OK") field(SDIS, "CRAT:IN20:BP02:FWVERSION.SEVR CP MS") field(DISV, "20") } record(stringin, "CRAT:IN20:BP02:CHU3_NAME") { field(SDIS, "CRAT:IN20:BP02:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:BP02:CHU3_V") { field(PREC, "2") field(EGU, "V") field(HOPR, "15") field(LOPR, "0") field(HIHI, "3.465") field(LOLO, "3.2175") field(HIGH, "3.432") field(LOW, "3.234") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:BP02:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:BP02:CHU3_I") { field(PREC, "1") field(EGU, "A") field(SDIS, "CRAT:IN20:BP02:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bi, "CRAT:IN20:BP02:CHU3_STATUS") { field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ONAM, "OK") field(SDIS, "CRAT:IN20:BP02:FWVERSION.SEVR CP MS") field(DISV, "20") } record(stringin, "CRAT:IN20:BP02:CHU5_NAME") { field(SDIS, "CRAT:IN20:BP02:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:BP02:CHU5_I") { field(PREC, "1") field(EGU, "A") field(SDIS, "CRAT:IN20:BP02:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bi, "CRAT:IN20:BP02:CHU5_STATUS") { field(FLNK, "CRAT:IN20:BP02:POWERCALC") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ONAM, "OK") field(SDIS, "CRAT:IN20:BP02:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bo, "CRAT:IN20:BP02:MAINPOWER") { field(DTYP, "stream") field(OUT, "@crat_wiener_21slot.proto.db setMainPower crat-in20-bp02") } record(bo, "CRAT:IN20:BP02:VMERESET") { field(DTYP, "stream") field(OUT, "@crat_wiener_21slot.proto.db setVmeSysReset crat-in20-bp02") } record(bo, "CRAT:IN20:BP02:FANSLOWER") { field(DTYP, "stream") field(OUT, "@crat_wiener_21slot.proto.db setFanSlower crat-in20-bp02") } record(bo, "CRAT:IN20:BP02:FANFASTER") { field(DTYP, "stream") field(OUT, "@crat_wiener_21slot.proto.db setFanFaster crat-in20-bp02") } record(ai, "CRAT:IN20:BP02:CHU5_V") { field(PREC, "1") field(EGU, "V") field(HOPR, "15") field(LOPR, "0") field(HIHI, "12.6") field(LOLO, "11.7") field(HIGH, "12.48") field(LOW, "11.76") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:BP02:FWVERSION.SEVR CP MS") field(DISV, "20") } record(seq, "CRAT:IN20:BP02:POWERSEQ1") { field(SELM, "Specified") field(SELL, "CRAT:IN20:BP02:POWERCALC") field(LNK1, "CRAT:IN20:BP02:MAINPOWER PP") field(FLNK, "CRAT:IN20:BP02:POWERMSGCALC") } record(calc, "CRAT:IN20:BP02:POWERCALC") { field(FLNK, "CRAT:IN20:BP02:POWERSEQ1") field(CALC, "A=1&&B=1&&C=0?1:A=0&&B=0&&C=1?1:0") field(INPA, "CRAT:IN20:BP02:POWERSTATE") } record(bo, "CRAT:IN20:BP02:POWEROFF") { field(HIGH, "9") field(OUT, "CRAT:IN20:BP02:POWERCALC.B") field(FLNK, "CRAT:IN20:BP02:POWERMSGCALC") } record(bo, "CRAT:IN20:BP02:POWERON") { field(OUT, "CRAT:IN20:BP02:POWERCALC.C") field(HIGH, "9") field(FLNK, "CRAT:IN20:BP02:POWERMSGCALC") } record(seq, "CRAT:IN20:BP02:HARDRESETSEQ") { field(SELM, "All") field(LNK1, "CRAT:IN20:BP02:POWEROFF PP") field(DOL1, "1") field(DLY2, "10") field(DOL2, "1") field(LNK2, "CRAT:IN20:BP02:POWERON PP") field(DLY3, "10") field(DOL3, "0") field(LNK3, "CRAT:IN20:BP02:HARDRESET PP") } record(bo, "CRAT:IN20:BP02:HARDRESET") { field(OUT, "CRAT:IN20:BP02:HARDRESETSEQ.PROC PP") field(FLNK, "CRAT:IN20:BP02:POWERMSGCALC") } record(calc, "CRAT:IN20:BP02:POWERMSGCALC") { field(FLNK, "CRAT:IN20:BP02:POWERMSG") field(CALC, "C?3:A=1&&B=0?0:A=0&&B=1?1:A=1&&B=1?2:4") field(INPA, "CRAT:IN20:BP02:POWERCALC.B") field(INPB, "CRAT:IN20:BP02:POWERCALC.C") field(INPC, "CRAT:IN20:BP02:HARDRESET") } record(mbbi, "CRAT:IN20:BP02:POWERMSG") { field(INP, "CRAT:IN20:BP02:POWERMSGCALC.VAL") field(ZRST, "TURNING_OFF") field(ONST, "TURNING_ON") field(TWST, "ERROR") field(THST, "HARD_RESETTING") field(FRST, " ") field(ZRSV, "MINOR") field(ONSV, "MINOR") field(TWSV, "MAJOR") field(THSV, "MINOR") field(FRSV, "NO_ALARM") } record(ai, "CRAT:IN20:BP02:TYPE") { field(DESC, "Wiener 21 Slot VME Crate") field(PINI, "YES") field(VAL, "2") } record(stringin, "CRAT:IN20:BP02:2NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:BP02:3NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:BP02:4NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:BP02:5NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:BP02:6NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:BP02:7NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:BP02:1NAME") { field(PINI, "YES") field(VAL, "IOC:IN20:BP02") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:BP02:8NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:BP02:9NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:BP02:10NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:BP02:11NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:BP02:12NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:BP02:13NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:BP02:14NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:BP02:15NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:BP02:16NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:BP02:17NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:BP02:18NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:BP02:19NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:BP02:20NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:BP02:21NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(calc, "CRAT:IN20:BP02:FANTEMP") { field(SCAN, "Passive") field(CALC, "A>0?(A-0)/1:A") field(EGU, "DegF") field(PREC, "0") field(HOPR, "120") field(LOPR, "20") field(HIHI, "131") field(LOLO, "-1") field(HIGH, "113") field(LOW, "-1") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(ADEL, "1") field(MDEL, "1") field(SDIS, "CRAT:IN20:BP02:FWVERSION.SEVR CP MS") field(DISV, "20") } record(stringin, "CRAT:IN20:BP02:FWVERSION") { field(SCAN, "5 second") field(DTYP, "stream") field(INP, "@crat_wiener_21slot.proto.db getStatus(CRAT:IN20:BP02) crat-in20-bp02") } record(stringin, "CRAT:IN20:BP02:LOC") { field(PINI, "YES") field(VAL, "RF Hut LKG-2225") info(autosaveFields,"VAL") } record(calc, "CRAT:IN20:BP02:STATSUMY") { field(DESC, "Alarm summary for crate") field(INPA, "CRAT:IN20:BP02:FWVERSION.SEVR NPP MS") field(INPB, "CRAT:IN20:BP02:FANTEMP.SEVR NPP MS") field(INPC, "CRAT:IN20:BP02:CHU0_V.SEVR NPP MS") field(INPD, "CRAT:IN20:BP02:CHU1_V.SEVR NPP MS") field(INPE, "CRAT:IN20:BP02:CHU3_V.SEVR NPP MS") field(INPF, "CRAT:IN20:BP02:CHU5_V.SEVR NPP MS") field(INPG, "CRAT:IN20:BP02:FANSPEED.SEVR NPP MS") field(INPH, "CRAT:IN20:BP02:FANTRAY.SEVR NPP MS") field(SCAN, "1 second") field(CALC, "A+B+C+D+E+F+G+H") } #! Further lines contain data used by VisualDCT #! View(653,461,0.6) #! Record("CRAT:IN20:BP02:POWERSTATE",860,92,0,0,"CRAT:IN20:BP02:POWERSTATE") #! Field("CRAT:IN20:BP02:POWERSTATE.FLNK",16777215,1,"CRAT:IN20:BP02:POWERSTATE.FLNK") #! Link("CRAT:IN20:BP02:POWERSTATE.FLNK","CRAT:IN20:BP02:FANTRAY") #! Field("CRAT:IN20:BP02:POWERSTATE.VAL",16777215,0,"CRAT:IN20:BP02:POWERSTATE.VAL") #! Record("CRAT:IN20:BP02:FANTRAY",1360,107,0,0,"CRAT:IN20:BP02:FANTRAY") #! Field("CRAT:IN20:BP02:FANTRAY.FLNK",16777215,1,"CRAT:IN20:BP02:FANTRAY.FLNK") #! Link("CRAT:IN20:BP02:FANTRAY.FLNK","CRAT:IN20:BP02:FANSPEED") #! Record("CRAT:IN20:BP02:FANSPEED",1640,64,0,0,"CRAT:IN20:BP02:FANSPEED") #! Field("CRAT:IN20:BP02:FANSPEED.FLNK",16777215,1,"CRAT:IN20:BP02:FANSPEED.FLNK") #! Link("CRAT:IN20:BP02:FANSPEED.FLNK","CRAT:IN20:BP02:FANTEMP") #! Field("CRAT:IN20:BP02:FANSPEED.SEVR",16777215,1,"CRAT:IN20:BP02:FANSPEED.SEVR") #! Record("CRAT:IN20:BP02:CHU0_I",1420,362,0,0,"CRAT:IN20:BP02:CHU0_I") #! Field("CRAT:IN20:BP02:CHU0_I.FLNK",16777215,1,"CRAT:IN20:BP02:CHU0_I.FLNK") #! Link("CRAT:IN20:BP02:CHU0_I.FLNK","CRAT:IN20:BP02:CHU0_STATUS") #! Record("CRAT:IN20:BP02:CHU0_NAME",840,390,0,1,"CRAT:IN20:BP02:CHU0_NAME") #! Field("CRAT:IN20:BP02:CHU0_NAME.FLNK",16777215,1,"CRAT:IN20:BP02:CHU0_NAME.FLNK") #! Link("CRAT:IN20:BP02:CHU0_NAME.FLNK","CRAT:IN20:BP02:CHU0_V") #! Record("CRAT:IN20:BP02:CHU0_STATUS",1680,367,0,0,"CRAT:IN20:BP02:CHU0_STATUS") #! Field("CRAT:IN20:BP02:CHU0_STATUS.FLNK",16777215,0,"CRAT:IN20:BP02:CHU0_STATUS.FLNK") #! Link("CRAT:IN20:BP02:CHU0_STATUS.FLNK","CRAT:IN20:BP02:CHU1_NAME") #! Record("CRAT:IN20:BP02:CHU0_V",1160,197,0,0,"CRAT:IN20:BP02:CHU0_V") #! Field("CRAT:IN20:BP02:CHU0_V.FLNK",16777215,1,"CRAT:IN20:BP02:CHU0_V.FLNK") #! Link("CRAT:IN20:BP02:CHU0_V.FLNK","CRAT:IN20:BP02:CHU0_I") #! Field("CRAT:IN20:BP02:CHU0_V.SEVR",16777215,1,"CRAT:IN20:BP02:CHU0_V.SEVR") #! Record("CRAT:IN20:BP02:CHU1_NAME",840,710,0,1,"CRAT:IN20:BP02:CHU1_NAME") #! Field("CRAT:IN20:BP02:CHU1_NAME.FLNK",16777215,1,"CRAT:IN20:BP02:CHU1_NAME.FLNK") #! Link("CRAT:IN20:BP02:CHU1_NAME.FLNK","CRAT:IN20:BP02:CHU1_V") #! Record("CRAT:IN20:BP02:CHU1_V",1140,517,0,0,"CRAT:IN20:BP02:CHU1_V") #! Field("CRAT:IN20:BP02:CHU1_V.FLNK",16777215,1,"CRAT:IN20:BP02:CHU1_V.FLNK") #! Link("CRAT:IN20:BP02:CHU1_V.FLNK","CRAT:IN20:BP02:CHU1_I") #! Field("CRAT:IN20:BP02:CHU1_V.SEVR",16777215,1,"CRAT:IN20:BP02:CHU1_V.SEVR") #! Record("CRAT:IN20:BP02:CHU1_I",1420,682,0,0,"CRAT:IN20:BP02:CHU1_I") #! Field("CRAT:IN20:BP02:CHU1_I.FLNK",16777215,1,"CRAT:IN20:BP02:CHU1_I.FLNK") #! Link("CRAT:IN20:BP02:CHU1_I.FLNK","CRAT:IN20:BP02:CHU1_STATUS") #! Record("CRAT:IN20:BP02:CHU1_STATUS",1680,687,0,0,"CRAT:IN20:BP02:CHU1_STATUS") #! Field("CRAT:IN20:BP02:CHU1_STATUS.FLNK",16777215,0,"CRAT:IN20:BP02:CHU1_STATUS.FLNK") #! Link("CRAT:IN20:BP02:CHU1_STATUS.FLNK","CRAT:IN20:BP02:CHU3_NAME") #! Record("CRAT:IN20:BP02:CHU3_NAME",840,1030,0,1,"CRAT:IN20:BP02:CHU3_NAME") #! Field("CRAT:IN20:BP02:CHU3_NAME.FLNK",16777215,1,"CRAT:IN20:BP02:CHU3_NAME.FLNK") #! Link("CRAT:IN20:BP02:CHU3_NAME.FLNK","CRAT:IN20:BP02:CHU3_V") #! Record("CRAT:IN20:BP02:CHU3_V",1120,837,0,0,"CRAT:IN20:BP02:CHU3_V") #! Field("CRAT:IN20:BP02:CHU3_V.FLNK",16777215,1,"CRAT:IN20:BP02:CHU3_V.FLNK") #! Link("CRAT:IN20:BP02:CHU3_V.FLNK","CRAT:IN20:BP02:CHU3_I") #! Field("CRAT:IN20:BP02:CHU3_V.SEVR",16777215,1,"CRAT:IN20:BP02:CHU3_V.SEVR") #! Record("CRAT:IN20:BP02:CHU3_I",1420,1002,0,0,"CRAT:IN20:BP02:CHU3_I") #! Field("CRAT:IN20:BP02:CHU3_I.FLNK",16777215,1,"CRAT:IN20:BP02:CHU3_I.FLNK") #! Link("CRAT:IN20:BP02:CHU3_I.FLNK","CRAT:IN20:BP02:CHU3_STATUS") #! Record("CRAT:IN20:BP02:CHU3_STATUS",1680,1007,0,0,"CRAT:IN20:BP02:CHU3_STATUS") #! Field("CRAT:IN20:BP02:CHU3_STATUS.FLNK",16777215,0,"CRAT:IN20:BP02:CHU3_STATUS.FLNK") #! Link("CRAT:IN20:BP02:CHU3_STATUS.FLNK","CRAT:IN20:BP02:CHU5_NAME") #! Record("CRAT:IN20:BP02:CHU5_NAME",840,1370,0,1,"CRAT:IN20:BP02:CHU5_NAME") #! Field("CRAT:IN20:BP02:CHU5_NAME.FLNK",16777215,1,"CRAT:IN20:BP02:CHU5_NAME.FLNK") #! Link("CRAT:IN20:BP02:CHU5_NAME.FLNK","CRAT:IN20:BP02:CHU5_V") #! Record("CRAT:IN20:BP02:CHU5_I",1420,1342,0,0,"CRAT:IN20:BP02:CHU5_I") #! Field("CRAT:IN20:BP02:CHU5_I.FLNK",16777215,1,"CRAT:IN20:BP02:CHU5_I.FLNK") #! Link("CRAT:IN20:BP02:CHU5_I.FLNK","CRAT:IN20:BP02:CHU5_STATUS") #! Record("CRAT:IN20:BP02:CHU5_STATUS",1680,1367,0,0,"CRAT:IN20:BP02:CHU5_STATUS") #! Field("CRAT:IN20:BP02:CHU5_STATUS.FLNK",16777215,0,"CRAT:IN20:BP02:CHU5_STATUS.FLNK") #! Link("CRAT:IN20:BP02:CHU5_STATUS.FLNK","CRAT:IN20:BP02:POWERCALC") #! Record("CRAT:IN20:BP02:MAINPOWER",1740,1875,0,1,"CRAT:IN20:BP02:MAINPOWER") #! Field("CRAT:IN20:BP02:MAINPOWER.VAL",16777215,0,"CRAT:IN20:BP02:MAINPOWER.VAL") #! Record("CRAT:IN20:BP02:VMERESET",360,115,0,1,"CRAT:IN20:BP02:VMERESET") #! Record("CRAT:IN20:BP02:FANSLOWER",360,315,0,1,"CRAT:IN20:BP02:FANSLOWER") #! Record("CRAT:IN20:BP02:FANFASTER",360,215,0,1,"CRAT:IN20:BP02:FANFASTER") #! Record("CRAT:IN20:BP02:CHU5_V",1100,1197,0,0,"CRAT:IN20:BP02:CHU5_V") #! Field("CRAT:IN20:BP02:CHU5_V.FLNK",16777215,1,"CRAT:IN20:BP02:CHU5_V.FLNK") #! Link("CRAT:IN20:BP02:CHU5_V.FLNK","CRAT:IN20:BP02:CHU5_I") #! Field("CRAT:IN20:BP02:CHU5_V.SEVR",16777215,1,"CRAT:IN20:BP02:CHU5_V.SEVR") #! Record("CRAT:IN20:BP02:POWERSEQ1",1420,1707,0,0,"CRAT:IN20:BP02:POWERSEQ1") #! Field("CRAT:IN20:BP02:POWERSEQ1.LNK1",16777215,1,"CRAT:IN20:BP02:POWERSEQ1.LNK1") #! Link("CRAT:IN20:BP02:POWERSEQ1.LNK1","CRAT:IN20:BP02:MAINPOWER.VAL") #! Field("CRAT:IN20:BP02:POWERSEQ1.SELL",16777215,0,"CRAT:IN20:BP02:POWERSEQ1.SELL") #! Link("CRAT:IN20:BP02:POWERSEQ1.SELL","CRAT:IN20:BP02:POWERCALC.VAL") #! Field("CRAT:IN20:BP02:POWERSEQ1.FLNK",16777215,0,"CRAT:IN20:BP02:POWERSEQ1.FLNK") #! Link("CRAT:IN20:BP02:POWERSEQ1.FLNK","CRAT:IN20:BP02:POWERMSGCALC") #! Record("CRAT:IN20:BP02:POWERCALC",960,1702,0,1,"CRAT:IN20:BP02:POWERCALC") #! Field("CRAT:IN20:BP02:POWERCALC.INPA",16777215,0,"CRAT:IN20:BP02:POWERCALC.INPA") #! Link("CRAT:IN20:BP02:POWERCALC.INPA","CRAT:IN20:BP02:POWERSTATE.VAL") #! Field("CRAT:IN20:BP02:POWERCALC.FLNK",16777215,1,"CRAT:IN20:BP02:POWERCALC.FLNK") #! Link("CRAT:IN20:BP02:POWERCALC.FLNK","CRAT:IN20:BP02:POWERSEQ1") #! Field("CRAT:IN20:BP02:POWERCALC.VAL",16777215,1,"CRAT:IN20:BP02:POWERCALC.VAL") #! Field("CRAT:IN20:BP02:POWERCALC.B",16777215,0,"CRAT:IN20:BP02:POWERCALC.B") #! Field("CRAT:IN20:BP02:POWERCALC.C",16777215,0,"CRAT:IN20:BP02:POWERCALC.C") #! Record("CRAT:IN20:BP02:POWEROFF",620,1762,0,1,"CRAT:IN20:BP02:POWEROFF") #! Field("CRAT:IN20:BP02:POWEROFF.OUT",16777215,1,"CRAT:IN20:BP02:POWEROFF.OUT") #! Link("CRAT:IN20:BP02:POWEROFF.OUT","CRAT:IN20:BP02:POWERCALC.B") #! Field("CRAT:IN20:BP02:POWEROFF.VAL",16777215,0,"CRAT:IN20:BP02:POWEROFF.VAL") #! Field("CRAT:IN20:BP02:POWEROFF.FLNK",16777215,1,"CRAT:IN20:BP02:POWEROFF.FLNK") #! Link("CRAT:IN20:BP02:POWEROFF.FLNK","CRAT:IN20:BP02:POWERMSGCALC") #! Record("CRAT:IN20:BP02:POWERON",620,1942,0,1,"CRAT:IN20:BP02:POWERON") #! Field("CRAT:IN20:BP02:POWERON.VAL",16777215,0,"CRAT:IN20:BP02:POWERON.VAL") #! Field("CRAT:IN20:BP02:POWERON.OUT",16777215,1,"CRAT:IN20:BP02:POWERON.OUT") #! Link("CRAT:IN20:BP02:POWERON.OUT","CRAT:IN20:BP02:POWERCALC.C") #! Field("CRAT:IN20:BP02:POWERON.FLNK",16777215,1,"CRAT:IN20:BP02:POWERON.FLNK") #! Link("CRAT:IN20:BP02:POWERON.FLNK","CRAT:IN20:BP02:POWERMSGCALC") #! Record("CRAT:IN20:BP02:HARDRESETSEQ",340,1735,0,1,"CRAT:IN20:BP02:HARDRESETSEQ") #! Field("CRAT:IN20:BP02:HARDRESETSEQ.LNK1",16777215,1,"CRAT:IN20:BP02:HARDRESETSEQ.LNK1") #! Link("CRAT:IN20:BP02:HARDRESETSEQ.LNK1","CRAT:IN20:BP02:POWEROFF.VAL") #! Field("CRAT:IN20:BP02:HARDRESETSEQ.LNK2",16777215,1,"CRAT:IN20:BP02:HARDRESETSEQ.LNK2") #! Link("CRAT:IN20:BP02:HARDRESETSEQ.LNK2","CRAT:IN20:BP02:POWERON.VAL") #! Field("CRAT:IN20:BP02:HARDRESETSEQ.PROC",16777215,0,"CRAT:IN20:BP02:HARDRESETSEQ.PROC") #! Field("CRAT:IN20:BP02:HARDRESETSEQ.LNK3",16777215,0,"CRAT:IN20:BP02:HARDRESETSEQ.LNK3") #! Link("CRAT:IN20:BP02:HARDRESETSEQ.LNK3","CRAT:IN20:BP02:HARDRESET.VAL") #! Record("CRAT:IN20:BP02:HARDRESET",20,1975,0,1,"CRAT:IN20:BP02:HARDRESET") #! Field("CRAT:IN20:BP02:HARDRESET.OUT",16777215,1,"CRAT:IN20:BP02:HARDRESET.OUT") #! Link("CRAT:IN20:BP02:HARDRESET.OUT","CRAT:IN20:BP02:HARDRESETSEQ.PROC") #! Field("CRAT:IN20:BP02:HARDRESET.VAL",16777215,1,"CRAT:IN20:BP02:HARDRESET.VAL") #! Field("CRAT:IN20:BP02:HARDRESET.FLNK",16777215,1,"CRAT:IN20:BP02:HARDRESET.FLNK") #! Link("CRAT:IN20:BP02:HARDRESET.FLNK","CRAT:IN20:BP02:POWERMSGCALC") #! Record("CRAT:IN20:BP02:POWERMSGCALC",1020,2172,0,1,"CRAT:IN20:BP02:POWERMSGCALC") #! Field("CRAT:IN20:BP02:POWERMSGCALC.INPA",16777215,0,"CRAT:IN20:BP02:POWERMSGCALC.INPA") #! Link("CRAT:IN20:BP02:POWERMSGCALC.INPA","CRAT:IN20:BP02:POWERCALC.B") #! Field("CRAT:IN20:BP02:POWERMSGCALC.INPB",16777215,0,"CRAT:IN20:BP02:POWERMSGCALC.INPB") #! Link("CRAT:IN20:BP02:POWERMSGCALC.INPB","CRAT:IN20:BP02:POWERCALC.C") #! Field("CRAT:IN20:BP02:POWERMSGCALC.INPC",16777215,0,"CRAT:IN20:BP02:POWERMSGCALC.INPC") #! Link("CRAT:IN20:BP02:POWERMSGCALC.INPC","CRAT:IN20:BP02:HARDRESET.VAL") #! Field("CRAT:IN20:BP02:POWERMSGCALC.FLNK",16777215,1,"CRAT:IN20:BP02:POWERMSGCALC.FLNK") #! Link("CRAT:IN20:BP02:POWERMSGCALC.FLNK","CRAT:IN20:BP02:POWERMSG") #! Field("CRAT:IN20:BP02:POWERMSGCALC.VAL",16777215,1,"CRAT:IN20:BP02:POWERMSGCALC.VAL") #! Record("CRAT:IN20:BP02:POWERMSG",1360,2167,0,0,"CRAT:IN20:BP02:POWERMSG") #! Field("CRAT:IN20:BP02:POWERMSG.INP",16777215,0,"CRAT:IN20:BP02:POWERMSG.INP") #! Link("CRAT:IN20:BP02:POWERMSG.INP","CRAT:IN20:BP02:POWERMSGCALC.VAL") #! Record("CRAT:IN20:BP02:TYPE",360,502,0,1,"CRAT:IN20:BP02:TYPE") #! Record("CRAT:IN20:BP02:2NAME",40,775,0,1,"CRAT:IN20:BP02:2NAME") #! Record("CRAT:IN20:BP02:3NAME",40,875,0,1,"CRAT:IN20:BP02:3NAME") #! Record("CRAT:IN20:BP02:4NAME",40,975,0,1,"CRAT:IN20:BP02:4NAME") #! Record("CRAT:IN20:BP02:5NAME",40,1075,0,1,"CRAT:IN20:BP02:5NAME") #! Record("CRAT:IN20:BP02:6NAME",40,1175,0,1,"CRAT:IN20:BP02:6NAME") #! Record("CRAT:IN20:BP02:7NAME",40,1275,0,1,"CRAT:IN20:BP02:7NAME") #! Record("CRAT:IN20:BP02:1NAME",40,675,0,1,"CRAT:IN20:BP02:1NAME") #! Record("CRAT:IN20:BP02:8NAME",240,675,0,1,"CRAT:IN20:BP02:8NAME") #! Record("CRAT:IN20:BP02:9NAME",240,775,0,1,"CRAT:IN20:BP02:9NAME") #! Record("CRAT:IN20:BP02:10NAME",240,875,0,1,"CRAT:IN20:BP02:10NAME") #! Record("CRAT:IN20:BP02:11NAME",240,975,0,1,"CRAT:IN20:BP02:11NAME") #! Record("CRAT:IN20:BP02:12NAME",240,1075,0,1,"CRAT:IN20:BP02:12NAME") #! Record("CRAT:IN20:BP02:13NAME",240,1175,0,1,"CRAT:IN20:BP02:13NAME") #! Record("CRAT:IN20:BP02:14NAME",240,1275,0,1,"CRAT:IN20:BP02:14NAME") #! Record("CRAT:IN20:BP02:15NAME",440,675,0,1,"CRAT:IN20:BP02:15NAME") #! Record("CRAT:IN20:BP02:16NAME",440,775,0,1,"CRAT:IN20:BP02:16NAME") #! Record("CRAT:IN20:BP02:17NAME",440,875,0,1,"CRAT:IN20:BP02:17NAME") #! Record("CRAT:IN20:BP02:18NAME",440,975,0,1,"CRAT:IN20:BP02:18NAME") #! Record("CRAT:IN20:BP02:19NAME",440,1075,0,1,"CRAT:IN20:BP02:19NAME") #! Record("CRAT:IN20:BP02:20NAME",440,1175,0,1,"CRAT:IN20:BP02:20NAME") #! Record("CRAT:IN20:BP02:21NAME",440,1275,0,1,"CRAT:IN20:BP02:21NAME") #! Record("CRAT:IN20:BP02:FANTEMP",1940,14,0,0,"CRAT:IN20:BP02:FANTEMP") #! Field("CRAT:IN20:BP02:FANTEMP.FLNK",16777215,0,"CRAT:IN20:BP02:FANTEMP.FLNK") #! Link("CRAT:IN20:BP02:FANTEMP.FLNK","CRAT:IN20:BP02:CHU0_NAME") #! Field("CRAT:IN20:BP02:FANTEMP.SEVR",16777215,1,"CRAT:IN20:BP02:FANTEMP.SEVR") #! Record("CRAT:IN20:BP02:FWVERSION",560,67,0,1,"CRAT:IN20:BP02:FWVERSION") #! Field("CRAT:IN20:BP02:FWVERSION.FLNK",16777215,1,"CRAT:IN20:BP02:FWVERSION.FLNK") #! Link("CRAT:IN20:BP02:FWVERSION.FLNK","CRAT:IN20:BP02:POWERSTATE") #! Field("CRAT:IN20:BP02:FWVERSION.SEVR",16777215,1,"CRAT:IN20:BP02:FWVERSION.SEVR") #! Record("CRAT:IN20:BP02:LOC",120,155,0,1,"CRAT:IN20:BP02:LOC") #! Record("CRAT:IN20:BP02:STATSUMY",2380,1380,0,1,"CRAT:IN20:BP02:STATSUMY") #! Field("CRAT:IN20:BP02:STATSUMY.INPA",16777215,0,"CRAT:IN20:BP02:STATSUMY.INPA") #! Link("CRAT:IN20:BP02:STATSUMY.INPA","CRAT:IN20:BP02:FWVERSION.SEVR") #! Field("CRAT:IN20:BP02:STATSUMY.INPB",16777215,0,"CRAT:IN20:BP02:STATSUMY.INPB") #! Link("CRAT:IN20:BP02:STATSUMY.INPB","CRAT:IN20:BP02:FANTEMP.SEVR") #! Field("CRAT:IN20:BP02:STATSUMY.INPC",16777215,0,"CRAT:IN20:BP02:STATSUMY.INPC") #! Link("CRAT:IN20:BP02:STATSUMY.INPC","CRAT:IN20:BP02:CHU0_V.SEVR") #! Field("CRAT:IN20:BP02:STATSUMY.INPD",16777215,0,"CRAT:IN20:BP02:STATSUMY.INPD") #! Link("CRAT:IN20:BP02:STATSUMY.INPD","CRAT:IN20:BP02:CHU1_V.SEVR") #! Field("CRAT:IN20:BP02:STATSUMY.INPE",16777215,0,"CRAT:IN20:BP02:STATSUMY.INPE") #! Link("CRAT:IN20:BP02:STATSUMY.INPE","CRAT:IN20:BP02:CHU3_V.SEVR") #! Field("CRAT:IN20:BP02:STATSUMY.INPF",16777215,0,"CRAT:IN20:BP02:STATSUMY.INPF") #! Link("CRAT:IN20:BP02:STATSUMY.INPF","CRAT:IN20:BP02:CHU5_V.SEVR") #! Field("CRAT:IN20:BP02:STATSUMY.INPG",16777215,0,"CRAT:IN20:BP02:STATSUMY.INPG") #! Link("CRAT:IN20:BP02:STATSUMY.INPG","CRAT:IN20:BP02:FANSPEED.SEVR") #! TextBox(TB0,40,1420,480,1740,1,"Dialog",12,1,16777215,"The web interface for this crate only provides a \"toggle power\" button.\nThere is no way to send a command to turn the power on or turn the power off.\nThe purpose of all these PVs is to provide POWERON and POWEROFF \nbuttons rather than the inferior toggle button.\n\nProcessing the POWERON record when the crate is off will turn it on. \nProcessing the POWEROFF record when the crate is on will turn it off.\nProcessing the HARDRESET record will first force the POWEROFF record\nto process, then it will force the POWERON record to process.\n\nThe POWERON and POWEROFF steps take about 10 seconds each: First the IOC\nmust wait to get new on/off status (which takes five seconds) before deciding\nwhether or not to toggle the crate power. Then it sends the toggle command\nand it takes another 5 seconds to see the change in on/off status.\n\nPOWERMSG contains a string that describes what is currently happening.\nIt is normally empty, but contains text if the power is being turned on, off, or \nreset.",null) #! Generated by VisualDCT v2.5 #! DBDSTART #! DBDEND record(bi, "CRAT:IN20:EV01:POWERSTATE") { field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ZNAM, "OFF") field(ONAM, "ON") field(SDIS, "CRAT:IN20:EV01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bi, "CRAT:IN20:EV01:FANTRAY") { field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ONAM, "OK") field(SDIS, "CRAT:IN20:EV01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:EV01:FANSPEED") { field(EGU, "RPM") field(LOLO, "1150") field(HHSV, "NO_ALARM") field(LLSV, "MAJOR") field(HSV, "NO_ALARM") field(LSV, "NO_ALARM") field(SDIS, "CRAT:IN20:EV01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:EV01:CHU0_I") { field(PREC, "1") field(EGU, "A") field(SDIS, "CRAT:IN20:EV01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(stringin, "CRAT:IN20:EV01:CHU0_NAME") { field(SDIS, "CRAT:IN20:EV01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bi, "CRAT:IN20:EV01:CHU0_STATUS") { field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ONAM, "OK") field(SDIS, "CRAT:IN20:EV01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:EV01:CHU0_V") { field(PREC, "2") field(EGU, "V") field(HOPR, "15") field(LOPR, "0") field(HIHI, "5.25") field(LOLO, "4.875") field(HIGH, "5.2") field(LOW, "4.9") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:EV01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(stringin, "CRAT:IN20:EV01:CHU1_NAME") { field(SDIS, "CRAT:IN20:EV01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:EV01:CHU1_V") { field(PREC, "1") field(EGU, "V") field(HOPR, "15") field(LOPR, "0") field(HIHI, "12.6") field(LOLO, "11.7") field(HIGH, "12.48") field(LOW, "11.76") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:EV01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:EV01:CHU1_I") { field(PREC, "1") field(EGU, "A") field(SDIS, "CRAT:IN20:EV01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bi, "CRAT:IN20:EV01:CHU1_STATUS") { field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ONAM, "OK") field(SDIS, "CRAT:IN20:EV01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(stringin, "CRAT:IN20:EV01:CHU3_NAME") { field(SDIS, "CRAT:IN20:EV01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:EV01:CHU3_V") { field(PREC, "2") field(EGU, "V") field(HOPR, "15") field(LOPR, "0") field(HIHI, "3.465") field(LOLO, "3.2175") field(HIGH, "3.432") field(LOW, "3.234") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:EV01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:EV01:CHU3_I") { field(PREC, "1") field(EGU, "A") field(SDIS, "CRAT:IN20:EV01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bi, "CRAT:IN20:EV01:CHU3_STATUS") { field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ONAM, "OK") field(SDIS, "CRAT:IN20:EV01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(stringin, "CRAT:IN20:EV01:CHU5_NAME") { field(SDIS, "CRAT:IN20:EV01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:EV01:CHU5_I") { field(PREC, "1") field(EGU, "A") field(SDIS, "CRAT:IN20:EV01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bi, "CRAT:IN20:EV01:CHU5_STATUS") { field(FLNK, "CRAT:IN20:EV01:POWERCALC") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ONAM, "OK") field(SDIS, "CRAT:IN20:EV01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bo, "CRAT:IN20:EV01:MAINPOWER") { field(DTYP, "stream") field(OUT, "@crat_wiener_21slot.proto.db setMainPower crat-in20-ev01") } record(bo, "CRAT:IN20:EV01:VMERESET") { field(DTYP, "stream") field(OUT, "@crat_wiener_21slot.proto.db setVmeSysReset crat-in20-ev01") } record(bo, "CRAT:IN20:EV01:FANSLOWER") { field(DTYP, "stream") field(OUT, "@crat_wiener_21slot.proto.db setFanSlower crat-in20-ev01") } record(bo, "CRAT:IN20:EV01:FANFASTER") { field(DTYP, "stream") field(OUT, "@crat_wiener_21slot.proto.db setFanFaster crat-in20-ev01") } record(ai, "CRAT:IN20:EV01:CHU5_V") { field(PREC, "1") field(EGU, "V") field(HOPR, "15") field(LOPR, "0") field(HIHI, "12.6") field(LOLO, "11.7") field(HIGH, "12.48") field(LOW, "11.76") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:EV01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(seq, "CRAT:IN20:EV01:POWERSEQ1") { field(SELM, "Specified") field(SELL, "CRAT:IN20:EV01:POWERCALC") field(LNK1, "CRAT:IN20:EV01:MAINPOWER PP") field(FLNK, "CRAT:IN20:EV01:POWERMSGCALC") } record(calc, "CRAT:IN20:EV01:POWERCALC") { field(FLNK, "CRAT:IN20:EV01:POWERSEQ1") field(CALC, "A=1&&B=1&&C=0?1:A=0&&B=0&&C=1?1:0") field(INPA, "CRAT:IN20:EV01:POWERSTATE") } record(bo, "CRAT:IN20:EV01:POWEROFF") { field(HIGH, "9") field(OUT, "CRAT:IN20:EV01:POWERCALC.B") field(FLNK, "CRAT:IN20:EV01:POWERMSGCALC") } record(bo, "CRAT:IN20:EV01:POWERON") { field(OUT, "CRAT:IN20:EV01:POWERCALC.C") field(HIGH, "9") field(FLNK, "CRAT:IN20:EV01:POWERMSGCALC") } record(seq, "CRAT:IN20:EV01:HARDRESETSEQ") { field(SELM, "All") field(LNK1, "CRAT:IN20:EV01:POWEROFF PP") field(DOL1, "1") field(DLY2, "10") field(DOL2, "1") field(LNK2, "CRAT:IN20:EV01:POWERON PP") field(DLY3, "10") field(DOL3, "0") field(LNK3, "CRAT:IN20:EV01:HARDRESET PP") } record(bo, "CRAT:IN20:EV01:HARDRESET") { field(OUT, "CRAT:IN20:EV01:HARDRESETSEQ.PROC PP") field(FLNK, "CRAT:IN20:EV01:POWERMSGCALC") } record(calc, "CRAT:IN20:EV01:POWERMSGCALC") { field(FLNK, "CRAT:IN20:EV01:POWERMSG") field(CALC, "C?3:A=1&&B=0?0:A=0&&B=1?1:A=1&&B=1?2:4") field(INPA, "CRAT:IN20:EV01:POWERCALC.B") field(INPB, "CRAT:IN20:EV01:POWERCALC.C") field(INPC, "CRAT:IN20:EV01:HARDRESET") } record(mbbi, "CRAT:IN20:EV01:POWERMSG") { field(INP, "CRAT:IN20:EV01:POWERMSGCALC.VAL") field(ZRST, "TURNING_OFF") field(ONST, "TURNING_ON") field(TWST, "ERROR") field(THST, "HARD_RESETTING") field(FRST, " ") field(ZRSV, "MINOR") field(ONSV, "MINOR") field(TWSV, "MAJOR") field(THSV, "MINOR") field(FRSV, "NO_ALARM") } record(ai, "CRAT:IN20:EV01:TYPE") { field(DESC, "Wiener 21 Slot VME Crate") field(PINI, "YES") field(VAL, "2") } record(stringin, "CRAT:IN20:EV01:2NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:EV01:3NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:EV01:4NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:EV01:5NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:EV01:6NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:EV01:7NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:EV01:1NAME") { field(PINI, "YES") field(VAL, "IOC:IN20:EV01") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:EV01:8NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:EV01:9NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:EV01:10NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:EV01:11NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:EV01:12NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:EV01:13NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:EV01:14NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:EV01:15NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:EV01:16NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:EV01:17NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:EV01:18NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:EV01:19NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:EV01:20NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:EV01:21NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(calc, "CRAT:IN20:EV01:FANTEMP") { field(SCAN, "Passive") field(CALC, "A>0?(A-0)/1:A") field(EGU, "DegF") field(PREC, "0") field(HOPR, "120") field(LOPR, "20") field(HIHI, "131") field(LOLO, "-1") field(HIGH, "113") field(LOW, "-1") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(ADEL, "1") field(MDEL, "1") field(SDIS, "CRAT:IN20:EV01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(stringin, "CRAT:IN20:EV01:FWVERSION") { field(SCAN, "5 second") field(DTYP, "stream") field(INP, "@crat_wiener_21slot.proto.db getStatus(CRAT:IN20:EV01) crat-in20-ev01") } record(stringin, "CRAT:IN20:EV01:LOC") { field(PINI, "YES") field(VAL, "RF Hut LKG-2121") info(autosaveFields,"VAL") } record(calc, "CRAT:IN20:EV01:STATSUMY") { field(DESC, "Alarm summary for crate") field(INPA, "CRAT:IN20:EV01:FWVERSION.SEVR NPP MS") field(INPB, "CRAT:IN20:EV01:FANTEMP.SEVR NPP MS") field(INPC, "CRAT:IN20:EV01:CHU0_V.SEVR NPP MS") field(INPD, "CRAT:IN20:EV01:CHU1_V.SEVR NPP MS") field(INPE, "CRAT:IN20:EV01:CHU3_V.SEVR NPP MS") field(INPF, "CRAT:IN20:EV01:CHU5_V.SEVR NPP MS") field(INPG, "CRAT:IN20:EV01:FANSPEED.SEVR NPP MS") field(INPH, "CRAT:IN20:EV01:FANTRAY.SEVR NPP MS") field(SCAN, "1 second") field(CALC, "A+B+C+D+E+F+G+H") } #! Further lines contain data used by VisualDCT #! View(653,461,0.6) #! Record("CRAT:IN20:EV01:POWERSTATE",860,92,0,0,"CRAT:IN20:EV01:POWERSTATE") #! Field("CRAT:IN20:EV01:POWERSTATE.FLNK",16777215,1,"CRAT:IN20:EV01:POWERSTATE.FLNK") #! Link("CRAT:IN20:EV01:POWERSTATE.FLNK","CRAT:IN20:EV01:FANTRAY") #! Field("CRAT:IN20:EV01:POWERSTATE.VAL",16777215,0,"CRAT:IN20:EV01:POWERSTATE.VAL") #! Record("CRAT:IN20:EV01:FANTRAY",1360,107,0,0,"CRAT:IN20:EV01:FANTRAY") #! Field("CRAT:IN20:EV01:FANTRAY.FLNK",16777215,1,"CRAT:IN20:EV01:FANTRAY.FLNK") #! Link("CRAT:IN20:EV01:FANTRAY.FLNK","CRAT:IN20:EV01:FANSPEED") #! Record("CRAT:IN20:EV01:FANSPEED",1640,64,0,0,"CRAT:IN20:EV01:FANSPEED") #! Field("CRAT:IN20:EV01:FANSPEED.FLNK",16777215,1,"CRAT:IN20:EV01:FANSPEED.FLNK") #! Link("CRAT:IN20:EV01:FANSPEED.FLNK","CRAT:IN20:EV01:FANTEMP") #! Field("CRAT:IN20:EV01:FANSPEED.SEVR",16777215,1,"CRAT:IN20:EV01:FANSPEED.SEVR") #! Record("CRAT:IN20:EV01:CHU0_I",1420,362,0,0,"CRAT:IN20:EV01:CHU0_I") #! Field("CRAT:IN20:EV01:CHU0_I.FLNK",16777215,1,"CRAT:IN20:EV01:CHU0_I.FLNK") #! Link("CRAT:IN20:EV01:CHU0_I.FLNK","CRAT:IN20:EV01:CHU0_STATUS") #! Record("CRAT:IN20:EV01:CHU0_NAME",840,390,0,1,"CRAT:IN20:EV01:CHU0_NAME") #! Field("CRAT:IN20:EV01:CHU0_NAME.FLNK",16777215,1,"CRAT:IN20:EV01:CHU0_NAME.FLNK") #! Link("CRAT:IN20:EV01:CHU0_NAME.FLNK","CRAT:IN20:EV01:CHU0_V") #! Record("CRAT:IN20:EV01:CHU0_STATUS",1680,367,0,0,"CRAT:IN20:EV01:CHU0_STATUS") #! Field("CRAT:IN20:EV01:CHU0_STATUS.FLNK",16777215,0,"CRAT:IN20:EV01:CHU0_STATUS.FLNK") #! Link("CRAT:IN20:EV01:CHU0_STATUS.FLNK","CRAT:IN20:EV01:CHU1_NAME") #! Record("CRAT:IN20:EV01:CHU0_V",1160,197,0,0,"CRAT:IN20:EV01:CHU0_V") #! Field("CRAT:IN20:EV01:CHU0_V.FLNK",16777215,1,"CRAT:IN20:EV01:CHU0_V.FLNK") #! Link("CRAT:IN20:EV01:CHU0_V.FLNK","CRAT:IN20:EV01:CHU0_I") #! Field("CRAT:IN20:EV01:CHU0_V.SEVR",16777215,1,"CRAT:IN20:EV01:CHU0_V.SEVR") #! Record("CRAT:IN20:EV01:CHU1_NAME",840,710,0,1,"CRAT:IN20:EV01:CHU1_NAME") #! Field("CRAT:IN20:EV01:CHU1_NAME.FLNK",16777215,1,"CRAT:IN20:EV01:CHU1_NAME.FLNK") #! Link("CRAT:IN20:EV01:CHU1_NAME.FLNK","CRAT:IN20:EV01:CHU1_V") #! Record("CRAT:IN20:EV01:CHU1_V",1140,517,0,0,"CRAT:IN20:EV01:CHU1_V") #! Field("CRAT:IN20:EV01:CHU1_V.FLNK",16777215,1,"CRAT:IN20:EV01:CHU1_V.FLNK") #! Link("CRAT:IN20:EV01:CHU1_V.FLNK","CRAT:IN20:EV01:CHU1_I") #! Field("CRAT:IN20:EV01:CHU1_V.SEVR",16777215,1,"CRAT:IN20:EV01:CHU1_V.SEVR") #! Record("CRAT:IN20:EV01:CHU1_I",1420,682,0,0,"CRAT:IN20:EV01:CHU1_I") #! Field("CRAT:IN20:EV01:CHU1_I.FLNK",16777215,1,"CRAT:IN20:EV01:CHU1_I.FLNK") #! Link("CRAT:IN20:EV01:CHU1_I.FLNK","CRAT:IN20:EV01:CHU1_STATUS") #! Record("CRAT:IN20:EV01:CHU1_STATUS",1680,687,0,0,"CRAT:IN20:EV01:CHU1_STATUS") #! Field("CRAT:IN20:EV01:CHU1_STATUS.FLNK",16777215,0,"CRAT:IN20:EV01:CHU1_STATUS.FLNK") #! Link("CRAT:IN20:EV01:CHU1_STATUS.FLNK","CRAT:IN20:EV01:CHU3_NAME") #! Record("CRAT:IN20:EV01:CHU3_NAME",840,1030,0,1,"CRAT:IN20:EV01:CHU3_NAME") #! Field("CRAT:IN20:EV01:CHU3_NAME.FLNK",16777215,1,"CRAT:IN20:EV01:CHU3_NAME.FLNK") #! Link("CRAT:IN20:EV01:CHU3_NAME.FLNK","CRAT:IN20:EV01:CHU3_V") #! Record("CRAT:IN20:EV01:CHU3_V",1120,837,0,0,"CRAT:IN20:EV01:CHU3_V") #! Field("CRAT:IN20:EV01:CHU3_V.FLNK",16777215,1,"CRAT:IN20:EV01:CHU3_V.FLNK") #! Link("CRAT:IN20:EV01:CHU3_V.FLNK","CRAT:IN20:EV01:CHU3_I") #! Field("CRAT:IN20:EV01:CHU3_V.SEVR",16777215,1,"CRAT:IN20:EV01:CHU3_V.SEVR") #! Record("CRAT:IN20:EV01:CHU3_I",1420,1002,0,0,"CRAT:IN20:EV01:CHU3_I") #! Field("CRAT:IN20:EV01:CHU3_I.FLNK",16777215,1,"CRAT:IN20:EV01:CHU3_I.FLNK") #! Link("CRAT:IN20:EV01:CHU3_I.FLNK","CRAT:IN20:EV01:CHU3_STATUS") #! Record("CRAT:IN20:EV01:CHU3_STATUS",1680,1007,0,0,"CRAT:IN20:EV01:CHU3_STATUS") #! Field("CRAT:IN20:EV01:CHU3_STATUS.FLNK",16777215,0,"CRAT:IN20:EV01:CHU3_STATUS.FLNK") #! Link("CRAT:IN20:EV01:CHU3_STATUS.FLNK","CRAT:IN20:EV01:CHU5_NAME") #! Record("CRAT:IN20:EV01:CHU5_NAME",840,1370,0,1,"CRAT:IN20:EV01:CHU5_NAME") #! Field("CRAT:IN20:EV01:CHU5_NAME.FLNK",16777215,1,"CRAT:IN20:EV01:CHU5_NAME.FLNK") #! Link("CRAT:IN20:EV01:CHU5_NAME.FLNK","CRAT:IN20:EV01:CHU5_V") #! Record("CRAT:IN20:EV01:CHU5_I",1420,1342,0,0,"CRAT:IN20:EV01:CHU5_I") #! Field("CRAT:IN20:EV01:CHU5_I.FLNK",16777215,1,"CRAT:IN20:EV01:CHU5_I.FLNK") #! Link("CRAT:IN20:EV01:CHU5_I.FLNK","CRAT:IN20:EV01:CHU5_STATUS") #! Record("CRAT:IN20:EV01:CHU5_STATUS",1680,1367,0,0,"CRAT:IN20:EV01:CHU5_STATUS") #! Field("CRAT:IN20:EV01:CHU5_STATUS.FLNK",16777215,0,"CRAT:IN20:EV01:CHU5_STATUS.FLNK") #! Link("CRAT:IN20:EV01:CHU5_STATUS.FLNK","CRAT:IN20:EV01:POWERCALC") #! Record("CRAT:IN20:EV01:MAINPOWER",1740,1875,0,1,"CRAT:IN20:EV01:MAINPOWER") #! Field("CRAT:IN20:EV01:MAINPOWER.VAL",16777215,0,"CRAT:IN20:EV01:MAINPOWER.VAL") #! Record("CRAT:IN20:EV01:VMERESET",360,115,0,1,"CRAT:IN20:EV01:VMERESET") #! Record("CRAT:IN20:EV01:FANSLOWER",360,315,0,1,"CRAT:IN20:EV01:FANSLOWER") #! Record("CRAT:IN20:EV01:FANFASTER",360,215,0,1,"CRAT:IN20:EV01:FANFASTER") #! Record("CRAT:IN20:EV01:CHU5_V",1100,1197,0,0,"CRAT:IN20:EV01:CHU5_V") #! Field("CRAT:IN20:EV01:CHU5_V.FLNK",16777215,1,"CRAT:IN20:EV01:CHU5_V.FLNK") #! Link("CRAT:IN20:EV01:CHU5_V.FLNK","CRAT:IN20:EV01:CHU5_I") #! Field("CRAT:IN20:EV01:CHU5_V.SEVR",16777215,1,"CRAT:IN20:EV01:CHU5_V.SEVR") #! Record("CRAT:IN20:EV01:POWERSEQ1",1420,1707,0,0,"CRAT:IN20:EV01:POWERSEQ1") #! Field("CRAT:IN20:EV01:POWERSEQ1.LNK1",16777215,1,"CRAT:IN20:EV01:POWERSEQ1.LNK1") #! Link("CRAT:IN20:EV01:POWERSEQ1.LNK1","CRAT:IN20:EV01:MAINPOWER.VAL") #! Field("CRAT:IN20:EV01:POWERSEQ1.SELL",16777215,0,"CRAT:IN20:EV01:POWERSEQ1.SELL") #! Link("CRAT:IN20:EV01:POWERSEQ1.SELL","CRAT:IN20:EV01:POWERCALC.VAL") #! Field("CRAT:IN20:EV01:POWERSEQ1.FLNK",16777215,0,"CRAT:IN20:EV01:POWERSEQ1.FLNK") #! Link("CRAT:IN20:EV01:POWERSEQ1.FLNK","CRAT:IN20:EV01:POWERMSGCALC") #! Record("CRAT:IN20:EV01:POWERCALC",960,1702,0,1,"CRAT:IN20:EV01:POWERCALC") #! Field("CRAT:IN20:EV01:POWERCALC.INPA",16777215,0,"CRAT:IN20:EV01:POWERCALC.INPA") #! Link("CRAT:IN20:EV01:POWERCALC.INPA","CRAT:IN20:EV01:POWERSTATE.VAL") #! Field("CRAT:IN20:EV01:POWERCALC.FLNK",16777215,1,"CRAT:IN20:EV01:POWERCALC.FLNK") #! Link("CRAT:IN20:EV01:POWERCALC.FLNK","CRAT:IN20:EV01:POWERSEQ1") #! Field("CRAT:IN20:EV01:POWERCALC.VAL",16777215,1,"CRAT:IN20:EV01:POWERCALC.VAL") #! Field("CRAT:IN20:EV01:POWERCALC.B",16777215,0,"CRAT:IN20:EV01:POWERCALC.B") #! Field("CRAT:IN20:EV01:POWERCALC.C",16777215,0,"CRAT:IN20:EV01:POWERCALC.C") #! Record("CRAT:IN20:EV01:POWEROFF",620,1762,0,1,"CRAT:IN20:EV01:POWEROFF") #! Field("CRAT:IN20:EV01:POWEROFF.OUT",16777215,1,"CRAT:IN20:EV01:POWEROFF.OUT") #! Link("CRAT:IN20:EV01:POWEROFF.OUT","CRAT:IN20:EV01:POWERCALC.B") #! Field("CRAT:IN20:EV01:POWEROFF.VAL",16777215,0,"CRAT:IN20:EV01:POWEROFF.VAL") #! Field("CRAT:IN20:EV01:POWEROFF.FLNK",16777215,1,"CRAT:IN20:EV01:POWEROFF.FLNK") #! Link("CRAT:IN20:EV01:POWEROFF.FLNK","CRAT:IN20:EV01:POWERMSGCALC") #! Record("CRAT:IN20:EV01:POWERON",620,1942,0,1,"CRAT:IN20:EV01:POWERON") #! Field("CRAT:IN20:EV01:POWERON.VAL",16777215,0,"CRAT:IN20:EV01:POWERON.VAL") #! Field("CRAT:IN20:EV01:POWERON.OUT",16777215,1,"CRAT:IN20:EV01:POWERON.OUT") #! Link("CRAT:IN20:EV01:POWERON.OUT","CRAT:IN20:EV01:POWERCALC.C") #! Field("CRAT:IN20:EV01:POWERON.FLNK",16777215,1,"CRAT:IN20:EV01:POWERON.FLNK") #! Link("CRAT:IN20:EV01:POWERON.FLNK","CRAT:IN20:EV01:POWERMSGCALC") #! Record("CRAT:IN20:EV01:HARDRESETSEQ",340,1735,0,1,"CRAT:IN20:EV01:HARDRESETSEQ") #! Field("CRAT:IN20:EV01:HARDRESETSEQ.LNK1",16777215,1,"CRAT:IN20:EV01:HARDRESETSEQ.LNK1") #! Link("CRAT:IN20:EV01:HARDRESETSEQ.LNK1","CRAT:IN20:EV01:POWEROFF.VAL") #! Field("CRAT:IN20:EV01:HARDRESETSEQ.LNK2",16777215,1,"CRAT:IN20:EV01:HARDRESETSEQ.LNK2") #! Link("CRAT:IN20:EV01:HARDRESETSEQ.LNK2","CRAT:IN20:EV01:POWERON.VAL") #! Field("CRAT:IN20:EV01:HARDRESETSEQ.PROC",16777215,0,"CRAT:IN20:EV01:HARDRESETSEQ.PROC") #! Field("CRAT:IN20:EV01:HARDRESETSEQ.LNK3",16777215,0,"CRAT:IN20:EV01:HARDRESETSEQ.LNK3") #! Link("CRAT:IN20:EV01:HARDRESETSEQ.LNK3","CRAT:IN20:EV01:HARDRESET.VAL") #! Record("CRAT:IN20:EV01:HARDRESET",20,1975,0,1,"CRAT:IN20:EV01:HARDRESET") #! Field("CRAT:IN20:EV01:HARDRESET.OUT",16777215,1,"CRAT:IN20:EV01:HARDRESET.OUT") #! Link("CRAT:IN20:EV01:HARDRESET.OUT","CRAT:IN20:EV01:HARDRESETSEQ.PROC") #! Field("CRAT:IN20:EV01:HARDRESET.VAL",16777215,1,"CRAT:IN20:EV01:HARDRESET.VAL") #! Field("CRAT:IN20:EV01:HARDRESET.FLNK",16777215,1,"CRAT:IN20:EV01:HARDRESET.FLNK") #! Link("CRAT:IN20:EV01:HARDRESET.FLNK","CRAT:IN20:EV01:POWERMSGCALC") #! Record("CRAT:IN20:EV01:POWERMSGCALC",1020,2172,0,1,"CRAT:IN20:EV01:POWERMSGCALC") #! Field("CRAT:IN20:EV01:POWERMSGCALC.INPA",16777215,0,"CRAT:IN20:EV01:POWERMSGCALC.INPA") #! Link("CRAT:IN20:EV01:POWERMSGCALC.INPA","CRAT:IN20:EV01:POWERCALC.B") #! Field("CRAT:IN20:EV01:POWERMSGCALC.INPB",16777215,0,"CRAT:IN20:EV01:POWERMSGCALC.INPB") #! Link("CRAT:IN20:EV01:POWERMSGCALC.INPB","CRAT:IN20:EV01:POWERCALC.C") #! Field("CRAT:IN20:EV01:POWERMSGCALC.INPC",16777215,0,"CRAT:IN20:EV01:POWERMSGCALC.INPC") #! Link("CRAT:IN20:EV01:POWERMSGCALC.INPC","CRAT:IN20:EV01:HARDRESET.VAL") #! Field("CRAT:IN20:EV01:POWERMSGCALC.FLNK",16777215,1,"CRAT:IN20:EV01:POWERMSGCALC.FLNK") #! Link("CRAT:IN20:EV01:POWERMSGCALC.FLNK","CRAT:IN20:EV01:POWERMSG") #! Field("CRAT:IN20:EV01:POWERMSGCALC.VAL",16777215,1,"CRAT:IN20:EV01:POWERMSGCALC.VAL") #! Record("CRAT:IN20:EV01:POWERMSG",1360,2167,0,0,"CRAT:IN20:EV01:POWERMSG") #! Field("CRAT:IN20:EV01:POWERMSG.INP",16777215,0,"CRAT:IN20:EV01:POWERMSG.INP") #! Link("CRAT:IN20:EV01:POWERMSG.INP","CRAT:IN20:EV01:POWERMSGCALC.VAL") #! Record("CRAT:IN20:EV01:TYPE",360,502,0,1,"CRAT:IN20:EV01:TYPE") #! Record("CRAT:IN20:EV01:2NAME",40,775,0,1,"CRAT:IN20:EV01:2NAME") #! Record("CRAT:IN20:EV01:3NAME",40,875,0,1,"CRAT:IN20:EV01:3NAME") #! Record("CRAT:IN20:EV01:4NAME",40,975,0,1,"CRAT:IN20:EV01:4NAME") #! Record("CRAT:IN20:EV01:5NAME",40,1075,0,1,"CRAT:IN20:EV01:5NAME") #! Record("CRAT:IN20:EV01:6NAME",40,1175,0,1,"CRAT:IN20:EV01:6NAME") #! Record("CRAT:IN20:EV01:7NAME",40,1275,0,1,"CRAT:IN20:EV01:7NAME") #! Record("CRAT:IN20:EV01:1NAME",40,675,0,1,"CRAT:IN20:EV01:1NAME") #! Record("CRAT:IN20:EV01:8NAME",240,675,0,1,"CRAT:IN20:EV01:8NAME") #! Record("CRAT:IN20:EV01:9NAME",240,775,0,1,"CRAT:IN20:EV01:9NAME") #! Record("CRAT:IN20:EV01:10NAME",240,875,0,1,"CRAT:IN20:EV01:10NAME") #! Record("CRAT:IN20:EV01:11NAME",240,975,0,1,"CRAT:IN20:EV01:11NAME") #! Record("CRAT:IN20:EV01:12NAME",240,1075,0,1,"CRAT:IN20:EV01:12NAME") #! Record("CRAT:IN20:EV01:13NAME",240,1175,0,1,"CRAT:IN20:EV01:13NAME") #! Record("CRAT:IN20:EV01:14NAME",240,1275,0,1,"CRAT:IN20:EV01:14NAME") #! Record("CRAT:IN20:EV01:15NAME",440,675,0,1,"CRAT:IN20:EV01:15NAME") #! Record("CRAT:IN20:EV01:16NAME",440,775,0,1,"CRAT:IN20:EV01:16NAME") #! Record("CRAT:IN20:EV01:17NAME",440,875,0,1,"CRAT:IN20:EV01:17NAME") #! Record("CRAT:IN20:EV01:18NAME",440,975,0,1,"CRAT:IN20:EV01:18NAME") #! Record("CRAT:IN20:EV01:19NAME",440,1075,0,1,"CRAT:IN20:EV01:19NAME") #! Record("CRAT:IN20:EV01:20NAME",440,1175,0,1,"CRAT:IN20:EV01:20NAME") #! Record("CRAT:IN20:EV01:21NAME",440,1275,0,1,"CRAT:IN20:EV01:21NAME") #! Record("CRAT:IN20:EV01:FANTEMP",1940,14,0,0,"CRAT:IN20:EV01:FANTEMP") #! Field("CRAT:IN20:EV01:FANTEMP.FLNK",16777215,0,"CRAT:IN20:EV01:FANTEMP.FLNK") #! Link("CRAT:IN20:EV01:FANTEMP.FLNK","CRAT:IN20:EV01:CHU0_NAME") #! Field("CRAT:IN20:EV01:FANTEMP.SEVR",16777215,1,"CRAT:IN20:EV01:FANTEMP.SEVR") #! Record("CRAT:IN20:EV01:FWVERSION",560,67,0,1,"CRAT:IN20:EV01:FWVERSION") #! Field("CRAT:IN20:EV01:FWVERSION.FLNK",16777215,1,"CRAT:IN20:EV01:FWVERSION.FLNK") #! Link("CRAT:IN20:EV01:FWVERSION.FLNK","CRAT:IN20:EV01:POWERSTATE") #! Field("CRAT:IN20:EV01:FWVERSION.SEVR",16777215,1,"CRAT:IN20:EV01:FWVERSION.SEVR") #! Record("CRAT:IN20:EV01:LOC",120,155,0,1,"CRAT:IN20:EV01:LOC") #! Record("CRAT:IN20:EV01:STATSUMY",2380,1380,0,1,"CRAT:IN20:EV01:STATSUMY") #! Field("CRAT:IN20:EV01:STATSUMY.INPA",16777215,0,"CRAT:IN20:EV01:STATSUMY.INPA") #! Link("CRAT:IN20:EV01:STATSUMY.INPA","CRAT:IN20:EV01:FWVERSION.SEVR") #! Field("CRAT:IN20:EV01:STATSUMY.INPB",16777215,0,"CRAT:IN20:EV01:STATSUMY.INPB") #! Link("CRAT:IN20:EV01:STATSUMY.INPB","CRAT:IN20:EV01:FANTEMP.SEVR") #! Field("CRAT:IN20:EV01:STATSUMY.INPC",16777215,0,"CRAT:IN20:EV01:STATSUMY.INPC") #! Link("CRAT:IN20:EV01:STATSUMY.INPC","CRAT:IN20:EV01:CHU0_V.SEVR") #! Field("CRAT:IN20:EV01:STATSUMY.INPD",16777215,0,"CRAT:IN20:EV01:STATSUMY.INPD") #! Link("CRAT:IN20:EV01:STATSUMY.INPD","CRAT:IN20:EV01:CHU1_V.SEVR") #! Field("CRAT:IN20:EV01:STATSUMY.INPE",16777215,0,"CRAT:IN20:EV01:STATSUMY.INPE") #! Link("CRAT:IN20:EV01:STATSUMY.INPE","CRAT:IN20:EV01:CHU3_V.SEVR") #! Field("CRAT:IN20:EV01:STATSUMY.INPF",16777215,0,"CRAT:IN20:EV01:STATSUMY.INPF") #! Link("CRAT:IN20:EV01:STATSUMY.INPF","CRAT:IN20:EV01:CHU5_V.SEVR") #! Field("CRAT:IN20:EV01:STATSUMY.INPG",16777215,0,"CRAT:IN20:EV01:STATSUMY.INPG") #! Link("CRAT:IN20:EV01:STATSUMY.INPG","CRAT:IN20:EV01:FANSPEED.SEVR") #! TextBox(TB0,40,1420,480,1740,1,"Dialog",12,1,16777215,"The web interface for this crate only provides a \"toggle power\" button.\nThere is no way to send a command to turn the power on or turn the power off.\nThe purpose of all these PVs is to provide POWERON and POWEROFF \nbuttons rather than the inferior toggle button.\n\nProcessing the POWERON record when the crate is off will turn it on. \nProcessing the POWEROFF record when the crate is on will turn it off.\nProcessing the HARDRESET record will first force the POWEROFF record\nto process, then it will force the POWERON record to process.\n\nThe POWERON and POWEROFF steps take about 10 seconds each: First the IOC\nmust wait to get new on/off status (which takes five seconds) before deciding\nwhether or not to toggle the crate power. Then it sends the toggle command\nand it takes another 5 seconds to see the change in on/off status.\n\nPOWERMSG contains a string that describes what is currently happening.\nIt is normally empty, but contains text if the power is being turned on, off, or \nreset.",null) #! Generated by VisualDCT v2.5 #! DBDSTART #! DBDEND record(bi, "CRAT:IN20:RF01:POWERSTATE") { field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ZNAM, "OFF") field(ONAM, "ON") field(SDIS, "CRAT:IN20:RF01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bi, "CRAT:IN20:RF01:FANTRAY") { field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ONAM, "OK") field(SDIS, "CRAT:IN20:RF01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:RF01:FANSPEED") { field(EGU, "RPM") field(LOLO, "1150") field(HHSV, "NO_ALARM") field(LLSV, "MAJOR") field(HSV, "NO_ALARM") field(LSV, "NO_ALARM") field(SDIS, "CRAT:IN20:RF01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:RF01:CHU0_I") { field(PREC, "1") field(EGU, "A") field(SDIS, "CRAT:IN20:RF01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(stringin, "CRAT:IN20:RF01:CHU0_NAME") { field(SDIS, "CRAT:IN20:RF01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bi, "CRAT:IN20:RF01:CHU0_STATUS") { field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ONAM, "OK") field(SDIS, "CRAT:IN20:RF01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:RF01:CHU0_V") { field(PREC, "2") field(EGU, "V") field(HOPR, "15") field(LOPR, "0") field(HIHI, "5.25") field(LOLO, "4.875") field(HIGH, "5.2") field(LOW, "4.9") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:RF01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(stringin, "CRAT:IN20:RF01:CHU1_NAME") { field(SDIS, "CRAT:IN20:RF01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:RF01:CHU1_V") { field(PREC, "1") field(EGU, "V") field(HOPR, "15") field(LOPR, "0") field(HIHI, "12.6") field(LOLO, "11.7") field(HIGH, "12.48") field(LOW, "11.76") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:RF01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:RF01:CHU1_I") { field(PREC, "1") field(EGU, "A") field(SDIS, "CRAT:IN20:RF01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bi, "CRAT:IN20:RF01:CHU1_STATUS") { field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ONAM, "OK") field(SDIS, "CRAT:IN20:RF01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(stringin, "CRAT:IN20:RF01:CHU3_NAME") { field(SDIS, "CRAT:IN20:RF01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:RF01:CHU3_V") { field(PREC, "2") field(EGU, "V") field(HOPR, "15") field(LOPR, "0") field(HIHI, "3.465") field(LOLO, "3.2175") field(HIGH, "3.432") field(LOW, "3.234") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:RF01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:RF01:CHU3_I") { field(PREC, "1") field(EGU, "A") field(SDIS, "CRAT:IN20:RF01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bi, "CRAT:IN20:RF01:CHU3_STATUS") { field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ONAM, "OK") field(SDIS, "CRAT:IN20:RF01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(stringin, "CRAT:IN20:RF01:CHU5_NAME") { field(SDIS, "CRAT:IN20:RF01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:RF01:CHU5_I") { field(PREC, "1") field(EGU, "A") field(SDIS, "CRAT:IN20:RF01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bi, "CRAT:IN20:RF01:CHU5_STATUS") { field(FLNK, "CRAT:IN20:RF01:POWERCALC") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ONAM, "OK") field(SDIS, "CRAT:IN20:RF01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bo, "CRAT:IN20:RF01:MAINPOWER") { field(DTYP, "stream") field(OUT, "@crat_wiener_21slot.proto.db setMainPower crat-in20-rf01") } record(bo, "CRAT:IN20:RF01:VMERESET") { field(DTYP, "stream") field(OUT, "@crat_wiener_21slot.proto.db setVmeSysReset crat-in20-rf01") } record(bo, "CRAT:IN20:RF01:FANSLOWER") { field(DTYP, "stream") field(OUT, "@crat_wiener_21slot.proto.db setFanSlower crat-in20-rf01") } record(bo, "CRAT:IN20:RF01:FANFASTER") { field(DTYP, "stream") field(OUT, "@crat_wiener_21slot.proto.db setFanFaster crat-in20-rf01") } record(ai, "CRAT:IN20:RF01:CHU5_V") { field(PREC, "1") field(EGU, "V") field(HOPR, "15") field(LOPR, "0") field(HIHI, "12.6") field(LOLO, "11.7") field(HIGH, "12.48") field(LOW, "11.76") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:RF01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(seq, "CRAT:IN20:RF01:POWERSEQ1") { field(SELM, "Specified") field(SELL, "CRAT:IN20:RF01:POWERCALC") field(LNK1, "CRAT:IN20:RF01:MAINPOWER PP") field(FLNK, "CRAT:IN20:RF01:POWERMSGCALC") } record(calc, "CRAT:IN20:RF01:POWERCALC") { field(FLNK, "CRAT:IN20:RF01:POWERSEQ1") field(CALC, "A=1&&B=1&&C=0?1:A=0&&B=0&&C=1?1:0") field(INPA, "CRAT:IN20:RF01:POWERSTATE") } record(bo, "CRAT:IN20:RF01:POWEROFF") { field(HIGH, "9") field(OUT, "CRAT:IN20:RF01:POWERCALC.B") field(FLNK, "CRAT:IN20:RF01:POWERMSGCALC") } record(bo, "CRAT:IN20:RF01:POWERON") { field(OUT, "CRAT:IN20:RF01:POWERCALC.C") field(HIGH, "9") field(FLNK, "CRAT:IN20:RF01:POWERMSGCALC") } record(seq, "CRAT:IN20:RF01:HARDRESETSEQ") { field(SELM, "All") field(LNK1, "CRAT:IN20:RF01:POWEROFF PP") field(DOL1, "1") field(DLY2, "10") field(DOL2, "1") field(LNK2, "CRAT:IN20:RF01:POWERON PP") field(DLY3, "10") field(DOL3, "0") field(LNK3, "CRAT:IN20:RF01:HARDRESET PP") } record(bo, "CRAT:IN20:RF01:HARDRESET") { field(OUT, "CRAT:IN20:RF01:HARDRESETSEQ.PROC PP") field(FLNK, "CRAT:IN20:RF01:POWERMSGCALC") } record(calc, "CRAT:IN20:RF01:POWERMSGCALC") { field(FLNK, "CRAT:IN20:RF01:POWERMSG") field(CALC, "C?3:A=1&&B=0?0:A=0&&B=1?1:A=1&&B=1?2:4") field(INPA, "CRAT:IN20:RF01:POWERCALC.B") field(INPB, "CRAT:IN20:RF01:POWERCALC.C") field(INPC, "CRAT:IN20:RF01:HARDRESET") } record(mbbi, "CRAT:IN20:RF01:POWERMSG") { field(INP, "CRAT:IN20:RF01:POWERMSGCALC.VAL") field(ZRST, "TURNING_OFF") field(ONST, "TURNING_ON") field(TWST, "ERROR") field(THST, "HARD_RESETTING") field(FRST, " ") field(ZRSV, "MINOR") field(ONSV, "MINOR") field(TWSV, "MAJOR") field(THSV, "MINOR") field(FRSV, "NO_ALARM") } record(ai, "CRAT:IN20:RF01:TYPE") { field(DESC, "Wiener 21 Slot VME Crate") field(PINI, "YES") field(VAL, "2") } record(stringin, "CRAT:IN20:RF01:2NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:RF01:3NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:RF01:4NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:RF01:5NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:RF01:6NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:RF01:7NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:RF01:1NAME") { field(PINI, "YES") field(VAL, "IOC:IN20:RF01") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:RF01:8NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:RF01:9NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:RF01:10NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:RF01:11NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:RF01:12NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:RF01:13NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:RF01:14NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:RF01:15NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:RF01:16NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:RF01:17NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:RF01:18NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:RF01:19NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:RF01:20NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:RF01:21NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(calc, "CRAT:IN20:RF01:FANTEMP") { field(SCAN, "Passive") field(CALC, "A>0?(A-0)/1:A") field(EGU, "DegF") field(PREC, "0") field(HOPR, "120") field(LOPR, "20") field(HIHI, "131") field(LOLO, "-1") field(HIGH, "113") field(LOW, "-1") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(ADEL, "1") field(MDEL, "1") field(SDIS, "CRAT:IN20:RF01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(stringin, "CRAT:IN20:RF01:FWVERSION") { field(SCAN, "5 second") field(DTYP, "stream") field(INP, "@crat_wiener_21slot.proto.db getStatus(CRAT:IN20:RF01) crat-in20-rf01") } record(stringin, "CRAT:IN20:RF01:LOC") { field(PINI, "YES") field(VAL, "LKF24-1415") info(autosaveFields,"VAL") } record(calc, "CRAT:IN20:RF01:STATSUMY") { field(DESC, "Alarm summary for crate") field(INPA, "CRAT:IN20:RF01:FWVERSION.SEVR NPP MS") field(INPB, "CRAT:IN20:RF01:FANTEMP.SEVR NPP MS") field(INPC, "CRAT:IN20:RF01:CHU0_V.SEVR NPP MS") field(INPD, "CRAT:IN20:RF01:CHU1_V.SEVR NPP MS") field(INPE, "CRAT:IN20:RF01:CHU3_V.SEVR NPP MS") field(INPF, "CRAT:IN20:RF01:CHU5_V.SEVR NPP MS") field(INPG, "CRAT:IN20:RF01:FANSPEED.SEVR NPP MS") field(INPH, "CRAT:IN20:RF01:FANTRAY.SEVR NPP MS") field(SCAN, "1 second") field(CALC, "A+B+C+D+E+F+G+H") } #! Further lines contain data used by VisualDCT #! View(653,461,0.6) #! Record("CRAT:IN20:RF01:POWERSTATE",860,92,0,0,"CRAT:IN20:RF01:POWERSTATE") #! Field("CRAT:IN20:RF01:POWERSTATE.FLNK",16777215,1,"CRAT:IN20:RF01:POWERSTATE.FLNK") #! Link("CRAT:IN20:RF01:POWERSTATE.FLNK","CRAT:IN20:RF01:FANTRAY") #! Field("CRAT:IN20:RF01:POWERSTATE.VAL",16777215,0,"CRAT:IN20:RF01:POWERSTATE.VAL") #! Record("CRAT:IN20:RF01:FANTRAY",1360,107,0,0,"CRAT:IN20:RF01:FANTRAY") #! Field("CRAT:IN20:RF01:FANTRAY.FLNK",16777215,1,"CRAT:IN20:RF01:FANTRAY.FLNK") #! Link("CRAT:IN20:RF01:FANTRAY.FLNK","CRAT:IN20:RF01:FANSPEED") #! Record("CRAT:IN20:RF01:FANSPEED",1640,64,0,0,"CRAT:IN20:RF01:FANSPEED") #! Field("CRAT:IN20:RF01:FANSPEED.FLNK",16777215,1,"CRAT:IN20:RF01:FANSPEED.FLNK") #! Link("CRAT:IN20:RF01:FANSPEED.FLNK","CRAT:IN20:RF01:FANTEMP") #! Field("CRAT:IN20:RF01:FANSPEED.SEVR",16777215,1,"CRAT:IN20:RF01:FANSPEED.SEVR") #! Record("CRAT:IN20:RF01:CHU0_I",1420,362,0,0,"CRAT:IN20:RF01:CHU0_I") #! Field("CRAT:IN20:RF01:CHU0_I.FLNK",16777215,1,"CRAT:IN20:RF01:CHU0_I.FLNK") #! Link("CRAT:IN20:RF01:CHU0_I.FLNK","CRAT:IN20:RF01:CHU0_STATUS") #! Record("CRAT:IN20:RF01:CHU0_NAME",840,390,0,1,"CRAT:IN20:RF01:CHU0_NAME") #! Field("CRAT:IN20:RF01:CHU0_NAME.FLNK",16777215,1,"CRAT:IN20:RF01:CHU0_NAME.FLNK") #! Link("CRAT:IN20:RF01:CHU0_NAME.FLNK","CRAT:IN20:RF01:CHU0_V") #! Record("CRAT:IN20:RF01:CHU0_STATUS",1680,367,0,0,"CRAT:IN20:RF01:CHU0_STATUS") #! Field("CRAT:IN20:RF01:CHU0_STATUS.FLNK",16777215,0,"CRAT:IN20:RF01:CHU0_STATUS.FLNK") #! Link("CRAT:IN20:RF01:CHU0_STATUS.FLNK","CRAT:IN20:RF01:CHU1_NAME") #! Record("CRAT:IN20:RF01:CHU0_V",1160,197,0,0,"CRAT:IN20:RF01:CHU0_V") #! Field("CRAT:IN20:RF01:CHU0_V.FLNK",16777215,1,"CRAT:IN20:RF01:CHU0_V.FLNK") #! Link("CRAT:IN20:RF01:CHU0_V.FLNK","CRAT:IN20:RF01:CHU0_I") #! Field("CRAT:IN20:RF01:CHU0_V.SEVR",16777215,1,"CRAT:IN20:RF01:CHU0_V.SEVR") #! Record("CRAT:IN20:RF01:CHU1_NAME",840,710,0,1,"CRAT:IN20:RF01:CHU1_NAME") #! Field("CRAT:IN20:RF01:CHU1_NAME.FLNK",16777215,1,"CRAT:IN20:RF01:CHU1_NAME.FLNK") #! Link("CRAT:IN20:RF01:CHU1_NAME.FLNK","CRAT:IN20:RF01:CHU1_V") #! Record("CRAT:IN20:RF01:CHU1_V",1140,517,0,0,"CRAT:IN20:RF01:CHU1_V") #! Field("CRAT:IN20:RF01:CHU1_V.FLNK",16777215,1,"CRAT:IN20:RF01:CHU1_V.FLNK") #! Link("CRAT:IN20:RF01:CHU1_V.FLNK","CRAT:IN20:RF01:CHU1_I") #! Field("CRAT:IN20:RF01:CHU1_V.SEVR",16777215,1,"CRAT:IN20:RF01:CHU1_V.SEVR") #! Record("CRAT:IN20:RF01:CHU1_I",1420,682,0,0,"CRAT:IN20:RF01:CHU1_I") #! Field("CRAT:IN20:RF01:CHU1_I.FLNK",16777215,1,"CRAT:IN20:RF01:CHU1_I.FLNK") #! Link("CRAT:IN20:RF01:CHU1_I.FLNK","CRAT:IN20:RF01:CHU1_STATUS") #! Record("CRAT:IN20:RF01:CHU1_STATUS",1680,687,0,0,"CRAT:IN20:RF01:CHU1_STATUS") #! Field("CRAT:IN20:RF01:CHU1_STATUS.FLNK",16777215,0,"CRAT:IN20:RF01:CHU1_STATUS.FLNK") #! Link("CRAT:IN20:RF01:CHU1_STATUS.FLNK","CRAT:IN20:RF01:CHU3_NAME") #! Record("CRAT:IN20:RF01:CHU3_NAME",840,1030,0,1,"CRAT:IN20:RF01:CHU3_NAME") #! Field("CRAT:IN20:RF01:CHU3_NAME.FLNK",16777215,1,"CRAT:IN20:RF01:CHU3_NAME.FLNK") #! Link("CRAT:IN20:RF01:CHU3_NAME.FLNK","CRAT:IN20:RF01:CHU3_V") #! Record("CRAT:IN20:RF01:CHU3_V",1120,837,0,0,"CRAT:IN20:RF01:CHU3_V") #! Field("CRAT:IN20:RF01:CHU3_V.FLNK",16777215,1,"CRAT:IN20:RF01:CHU3_V.FLNK") #! Link("CRAT:IN20:RF01:CHU3_V.FLNK","CRAT:IN20:RF01:CHU3_I") #! Field("CRAT:IN20:RF01:CHU3_V.SEVR",16777215,1,"CRAT:IN20:RF01:CHU3_V.SEVR") #! Record("CRAT:IN20:RF01:CHU3_I",1420,1002,0,0,"CRAT:IN20:RF01:CHU3_I") #! Field("CRAT:IN20:RF01:CHU3_I.FLNK",16777215,1,"CRAT:IN20:RF01:CHU3_I.FLNK") #! Link("CRAT:IN20:RF01:CHU3_I.FLNK","CRAT:IN20:RF01:CHU3_STATUS") #! Record("CRAT:IN20:RF01:CHU3_STATUS",1680,1007,0,0,"CRAT:IN20:RF01:CHU3_STATUS") #! Field("CRAT:IN20:RF01:CHU3_STATUS.FLNK",16777215,0,"CRAT:IN20:RF01:CHU3_STATUS.FLNK") #! Link("CRAT:IN20:RF01:CHU3_STATUS.FLNK","CRAT:IN20:RF01:CHU5_NAME") #! Record("CRAT:IN20:RF01:CHU5_NAME",840,1370,0,1,"CRAT:IN20:RF01:CHU5_NAME") #! Field("CRAT:IN20:RF01:CHU5_NAME.FLNK",16777215,1,"CRAT:IN20:RF01:CHU5_NAME.FLNK") #! Link("CRAT:IN20:RF01:CHU5_NAME.FLNK","CRAT:IN20:RF01:CHU5_V") #! Record("CRAT:IN20:RF01:CHU5_I",1420,1342,0,0,"CRAT:IN20:RF01:CHU5_I") #! Field("CRAT:IN20:RF01:CHU5_I.FLNK",16777215,1,"CRAT:IN20:RF01:CHU5_I.FLNK") #! Link("CRAT:IN20:RF01:CHU5_I.FLNK","CRAT:IN20:RF01:CHU5_STATUS") #! Record("CRAT:IN20:RF01:CHU5_STATUS",1680,1367,0,0,"CRAT:IN20:RF01:CHU5_STATUS") #! Field("CRAT:IN20:RF01:CHU5_STATUS.FLNK",16777215,0,"CRAT:IN20:RF01:CHU5_STATUS.FLNK") #! Link("CRAT:IN20:RF01:CHU5_STATUS.FLNK","CRAT:IN20:RF01:POWERCALC") #! Record("CRAT:IN20:RF01:MAINPOWER",1740,1875,0,1,"CRAT:IN20:RF01:MAINPOWER") #! Field("CRAT:IN20:RF01:MAINPOWER.VAL",16777215,0,"CRAT:IN20:RF01:MAINPOWER.VAL") #! Record("CRAT:IN20:RF01:VMERESET",360,115,0,1,"CRAT:IN20:RF01:VMERESET") #! Record("CRAT:IN20:RF01:FANSLOWER",360,315,0,1,"CRAT:IN20:RF01:FANSLOWER") #! Record("CRAT:IN20:RF01:FANFASTER",360,215,0,1,"CRAT:IN20:RF01:FANFASTER") #! Record("CRAT:IN20:RF01:CHU5_V",1100,1197,0,0,"CRAT:IN20:RF01:CHU5_V") #! Field("CRAT:IN20:RF01:CHU5_V.FLNK",16777215,1,"CRAT:IN20:RF01:CHU5_V.FLNK") #! Link("CRAT:IN20:RF01:CHU5_V.FLNK","CRAT:IN20:RF01:CHU5_I") #! Field("CRAT:IN20:RF01:CHU5_V.SEVR",16777215,1,"CRAT:IN20:RF01:CHU5_V.SEVR") #! Record("CRAT:IN20:RF01:POWERSEQ1",1420,1707,0,0,"CRAT:IN20:RF01:POWERSEQ1") #! Field("CRAT:IN20:RF01:POWERSEQ1.LNK1",16777215,1,"CRAT:IN20:RF01:POWERSEQ1.LNK1") #! Link("CRAT:IN20:RF01:POWERSEQ1.LNK1","CRAT:IN20:RF01:MAINPOWER.VAL") #! Field("CRAT:IN20:RF01:POWERSEQ1.SELL",16777215,0,"CRAT:IN20:RF01:POWERSEQ1.SELL") #! Link("CRAT:IN20:RF01:POWERSEQ1.SELL","CRAT:IN20:RF01:POWERCALC.VAL") #! Field("CRAT:IN20:RF01:POWERSEQ1.FLNK",16777215,0,"CRAT:IN20:RF01:POWERSEQ1.FLNK") #! Link("CRAT:IN20:RF01:POWERSEQ1.FLNK","CRAT:IN20:RF01:POWERMSGCALC") #! Record("CRAT:IN20:RF01:POWERCALC",960,1702,0,1,"CRAT:IN20:RF01:POWERCALC") #! Field("CRAT:IN20:RF01:POWERCALC.INPA",16777215,0,"CRAT:IN20:RF01:POWERCALC.INPA") #! Link("CRAT:IN20:RF01:POWERCALC.INPA","CRAT:IN20:RF01:POWERSTATE.VAL") #! Field("CRAT:IN20:RF01:POWERCALC.FLNK",16777215,1,"CRAT:IN20:RF01:POWERCALC.FLNK") #! Link("CRAT:IN20:RF01:POWERCALC.FLNK","CRAT:IN20:RF01:POWERSEQ1") #! Field("CRAT:IN20:RF01:POWERCALC.VAL",16777215,1,"CRAT:IN20:RF01:POWERCALC.VAL") #! Field("CRAT:IN20:RF01:POWERCALC.B",16777215,0,"CRAT:IN20:RF01:POWERCALC.B") #! Field("CRAT:IN20:RF01:POWERCALC.C",16777215,0,"CRAT:IN20:RF01:POWERCALC.C") #! Record("CRAT:IN20:RF01:POWEROFF",620,1762,0,1,"CRAT:IN20:RF01:POWEROFF") #! Field("CRAT:IN20:RF01:POWEROFF.OUT",16777215,1,"CRAT:IN20:RF01:POWEROFF.OUT") #! Link("CRAT:IN20:RF01:POWEROFF.OUT","CRAT:IN20:RF01:POWERCALC.B") #! Field("CRAT:IN20:RF01:POWEROFF.VAL",16777215,0,"CRAT:IN20:RF01:POWEROFF.VAL") #! Field("CRAT:IN20:RF01:POWEROFF.FLNK",16777215,1,"CRAT:IN20:RF01:POWEROFF.FLNK") #! Link("CRAT:IN20:RF01:POWEROFF.FLNK","CRAT:IN20:RF01:POWERMSGCALC") #! Record("CRAT:IN20:RF01:POWERON",620,1942,0,1,"CRAT:IN20:RF01:POWERON") #! Field("CRAT:IN20:RF01:POWERON.VAL",16777215,0,"CRAT:IN20:RF01:POWERON.VAL") #! Field("CRAT:IN20:RF01:POWERON.OUT",16777215,1,"CRAT:IN20:RF01:POWERON.OUT") #! Link("CRAT:IN20:RF01:POWERON.OUT","CRAT:IN20:RF01:POWERCALC.C") #! Field("CRAT:IN20:RF01:POWERON.FLNK",16777215,1,"CRAT:IN20:RF01:POWERON.FLNK") #! Link("CRAT:IN20:RF01:POWERON.FLNK","CRAT:IN20:RF01:POWERMSGCALC") #! Record("CRAT:IN20:RF01:HARDRESETSEQ",340,1735,0,1,"CRAT:IN20:RF01:HARDRESETSEQ") #! Field("CRAT:IN20:RF01:HARDRESETSEQ.LNK1",16777215,1,"CRAT:IN20:RF01:HARDRESETSEQ.LNK1") #! Link("CRAT:IN20:RF01:HARDRESETSEQ.LNK1","CRAT:IN20:RF01:POWEROFF.VAL") #! Field("CRAT:IN20:RF01:HARDRESETSEQ.LNK2",16777215,1,"CRAT:IN20:RF01:HARDRESETSEQ.LNK2") #! Link("CRAT:IN20:RF01:HARDRESETSEQ.LNK2","CRAT:IN20:RF01:POWERON.VAL") #! Field("CRAT:IN20:RF01:HARDRESETSEQ.PROC",16777215,0,"CRAT:IN20:RF01:HARDRESETSEQ.PROC") #! Field("CRAT:IN20:RF01:HARDRESETSEQ.LNK3",16777215,0,"CRAT:IN20:RF01:HARDRESETSEQ.LNK3") #! Link("CRAT:IN20:RF01:HARDRESETSEQ.LNK3","CRAT:IN20:RF01:HARDRESET.VAL") #! Record("CRAT:IN20:RF01:HARDRESET",20,1975,0,1,"CRAT:IN20:RF01:HARDRESET") #! Field("CRAT:IN20:RF01:HARDRESET.OUT",16777215,1,"CRAT:IN20:RF01:HARDRESET.OUT") #! Link("CRAT:IN20:RF01:HARDRESET.OUT","CRAT:IN20:RF01:HARDRESETSEQ.PROC") #! Field("CRAT:IN20:RF01:HARDRESET.VAL",16777215,1,"CRAT:IN20:RF01:HARDRESET.VAL") #! Field("CRAT:IN20:RF01:HARDRESET.FLNK",16777215,1,"CRAT:IN20:RF01:HARDRESET.FLNK") #! Link("CRAT:IN20:RF01:HARDRESET.FLNK","CRAT:IN20:RF01:POWERMSGCALC") #! Record("CRAT:IN20:RF01:POWERMSGCALC",1020,2172,0,1,"CRAT:IN20:RF01:POWERMSGCALC") #! Field("CRAT:IN20:RF01:POWERMSGCALC.INPA",16777215,0,"CRAT:IN20:RF01:POWERMSGCALC.INPA") #! Link("CRAT:IN20:RF01:POWERMSGCALC.INPA","CRAT:IN20:RF01:POWERCALC.B") #! Field("CRAT:IN20:RF01:POWERMSGCALC.INPB",16777215,0,"CRAT:IN20:RF01:POWERMSGCALC.INPB") #! Link("CRAT:IN20:RF01:POWERMSGCALC.INPB","CRAT:IN20:RF01:POWERCALC.C") #! Field("CRAT:IN20:RF01:POWERMSGCALC.INPC",16777215,0,"CRAT:IN20:RF01:POWERMSGCALC.INPC") #! Link("CRAT:IN20:RF01:POWERMSGCALC.INPC","CRAT:IN20:RF01:HARDRESET.VAL") #! Field("CRAT:IN20:RF01:POWERMSGCALC.FLNK",16777215,1,"CRAT:IN20:RF01:POWERMSGCALC.FLNK") #! Link("CRAT:IN20:RF01:POWERMSGCALC.FLNK","CRAT:IN20:RF01:POWERMSG") #! Field("CRAT:IN20:RF01:POWERMSGCALC.VAL",16777215,1,"CRAT:IN20:RF01:POWERMSGCALC.VAL") #! Record("CRAT:IN20:RF01:POWERMSG",1360,2167,0,0,"CRAT:IN20:RF01:POWERMSG") #! Field("CRAT:IN20:RF01:POWERMSG.INP",16777215,0,"CRAT:IN20:RF01:POWERMSG.INP") #! Link("CRAT:IN20:RF01:POWERMSG.INP","CRAT:IN20:RF01:POWERMSGCALC.VAL") #! Record("CRAT:IN20:RF01:TYPE",360,502,0,1,"CRAT:IN20:RF01:TYPE") #! Record("CRAT:IN20:RF01:2NAME",40,775,0,1,"CRAT:IN20:RF01:2NAME") #! Record("CRAT:IN20:RF01:3NAME",40,875,0,1,"CRAT:IN20:RF01:3NAME") #! Record("CRAT:IN20:RF01:4NAME",40,975,0,1,"CRAT:IN20:RF01:4NAME") #! Record("CRAT:IN20:RF01:5NAME",40,1075,0,1,"CRAT:IN20:RF01:5NAME") #! Record("CRAT:IN20:RF01:6NAME",40,1175,0,1,"CRAT:IN20:RF01:6NAME") #! Record("CRAT:IN20:RF01:7NAME",40,1275,0,1,"CRAT:IN20:RF01:7NAME") #! Record("CRAT:IN20:RF01:1NAME",40,675,0,1,"CRAT:IN20:RF01:1NAME") #! Record("CRAT:IN20:RF01:8NAME",240,675,0,1,"CRAT:IN20:RF01:8NAME") #! Record("CRAT:IN20:RF01:9NAME",240,775,0,1,"CRAT:IN20:RF01:9NAME") #! Record("CRAT:IN20:RF01:10NAME",240,875,0,1,"CRAT:IN20:RF01:10NAME") #! Record("CRAT:IN20:RF01:11NAME",240,975,0,1,"CRAT:IN20:RF01:11NAME") #! Record("CRAT:IN20:RF01:12NAME",240,1075,0,1,"CRAT:IN20:RF01:12NAME") #! Record("CRAT:IN20:RF01:13NAME",240,1175,0,1,"CRAT:IN20:RF01:13NAME") #! Record("CRAT:IN20:RF01:14NAME",240,1275,0,1,"CRAT:IN20:RF01:14NAME") #! Record("CRAT:IN20:RF01:15NAME",440,675,0,1,"CRAT:IN20:RF01:15NAME") #! Record("CRAT:IN20:RF01:16NAME",440,775,0,1,"CRAT:IN20:RF01:16NAME") #! Record("CRAT:IN20:RF01:17NAME",440,875,0,1,"CRAT:IN20:RF01:17NAME") #! Record("CRAT:IN20:RF01:18NAME",440,975,0,1,"CRAT:IN20:RF01:18NAME") #! Record("CRAT:IN20:RF01:19NAME",440,1075,0,1,"CRAT:IN20:RF01:19NAME") #! Record("CRAT:IN20:RF01:20NAME",440,1175,0,1,"CRAT:IN20:RF01:20NAME") #! Record("CRAT:IN20:RF01:21NAME",440,1275,0,1,"CRAT:IN20:RF01:21NAME") #! Record("CRAT:IN20:RF01:FANTEMP",1940,14,0,0,"CRAT:IN20:RF01:FANTEMP") #! Field("CRAT:IN20:RF01:FANTEMP.FLNK",16777215,0,"CRAT:IN20:RF01:FANTEMP.FLNK") #! Link("CRAT:IN20:RF01:FANTEMP.FLNK","CRAT:IN20:RF01:CHU0_NAME") #! Field("CRAT:IN20:RF01:FANTEMP.SEVR",16777215,1,"CRAT:IN20:RF01:FANTEMP.SEVR") #! Record("CRAT:IN20:RF01:FWVERSION",560,67,0,1,"CRAT:IN20:RF01:FWVERSION") #! Field("CRAT:IN20:RF01:FWVERSION.FLNK",16777215,1,"CRAT:IN20:RF01:FWVERSION.FLNK") #! Link("CRAT:IN20:RF01:FWVERSION.FLNK","CRAT:IN20:RF01:POWERSTATE") #! Field("CRAT:IN20:RF01:FWVERSION.SEVR",16777215,1,"CRAT:IN20:RF01:FWVERSION.SEVR") #! Record("CRAT:IN20:RF01:LOC",120,155,0,1,"CRAT:IN20:RF01:LOC") #! Record("CRAT:IN20:RF01:STATSUMY",2380,1380,0,1,"CRAT:IN20:RF01:STATSUMY") #! Field("CRAT:IN20:RF01:STATSUMY.INPA",16777215,0,"CRAT:IN20:RF01:STATSUMY.INPA") #! Link("CRAT:IN20:RF01:STATSUMY.INPA","CRAT:IN20:RF01:FWVERSION.SEVR") #! Field("CRAT:IN20:RF01:STATSUMY.INPB",16777215,0,"CRAT:IN20:RF01:STATSUMY.INPB") #! Link("CRAT:IN20:RF01:STATSUMY.INPB","CRAT:IN20:RF01:FANTEMP.SEVR") #! Field("CRAT:IN20:RF01:STATSUMY.INPC",16777215,0,"CRAT:IN20:RF01:STATSUMY.INPC") #! Link("CRAT:IN20:RF01:STATSUMY.INPC","CRAT:IN20:RF01:CHU0_V.SEVR") #! Field("CRAT:IN20:RF01:STATSUMY.INPD",16777215,0,"CRAT:IN20:RF01:STATSUMY.INPD") #! Link("CRAT:IN20:RF01:STATSUMY.INPD","CRAT:IN20:RF01:CHU1_V.SEVR") #! Field("CRAT:IN20:RF01:STATSUMY.INPE",16777215,0,"CRAT:IN20:RF01:STATSUMY.INPE") #! Link("CRAT:IN20:RF01:STATSUMY.INPE","CRAT:IN20:RF01:CHU3_V.SEVR") #! Field("CRAT:IN20:RF01:STATSUMY.INPF",16777215,0,"CRAT:IN20:RF01:STATSUMY.INPF") #! Link("CRAT:IN20:RF01:STATSUMY.INPF","CRAT:IN20:RF01:CHU5_V.SEVR") #! Field("CRAT:IN20:RF01:STATSUMY.INPG",16777215,0,"CRAT:IN20:RF01:STATSUMY.INPG") #! Link("CRAT:IN20:RF01:STATSUMY.INPG","CRAT:IN20:RF01:FANSPEED.SEVR") #! TextBox(TB0,40,1420,480,1740,1,"Dialog",12,1,16777215,"The web interface for this crate only provides a \"toggle power\" button.\nThere is no way to send a command to turn the power on or turn the power off.\nThe purpose of all these PVs is to provide POWERON and POWEROFF \nbuttons rather than the inferior toggle button.\n\nProcessing the POWERON record when the crate is off will turn it on. \nProcessing the POWEROFF record when the crate is on will turn it off.\nProcessing the HARDRESET record will first force the POWEROFF record\nto process, then it will force the POWERON record to process.\n\nThe POWERON and POWEROFF steps take about 10 seconds each: First the IOC\nmust wait to get new on/off status (which takes five seconds) before deciding\nwhether or not to toggle the crate power. Then it sends the toggle command\nand it takes another 5 seconds to see the change in on/off status.\n\nPOWERMSG contains a string that describes what is currently happening.\nIt is normally empty, but contains text if the power is being turned on, off, or \nreset.",null) #! Generated by VisualDCT v2.5 #! DBDSTART #! DBDEND record(bi, "CRAT:IN20:LS11:POWERSTATE") { field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ZNAM, "OFF") field(ONAM, "ON") field(SDIS, "CRAT:IN20:LS11:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bi, "CRAT:IN20:LS11:FANTRAY") { field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ONAM, "OK") field(SDIS, "CRAT:IN20:LS11:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:LS11:FANSPEED") { field(EGU, "RPM") field(LOLO, "1150") field(HHSV, "NO_ALARM") field(LLSV, "MAJOR") field(HSV, "NO_ALARM") field(LSV, "NO_ALARM") field(SDIS, "CRAT:IN20:LS11:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:LS11:CHU0_I") { field(PREC, "1") field(EGU, "A") field(SDIS, "CRAT:IN20:LS11:FWVERSION.SEVR CP MS") field(DISV, "20") } record(stringin, "CRAT:IN20:LS11:CHU0_NAME") { field(SDIS, "CRAT:IN20:LS11:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bi, "CRAT:IN20:LS11:CHU0_STATUS") { field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ONAM, "OK") field(SDIS, "CRAT:IN20:LS11:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:LS11:CHU0_V") { field(PREC, "2") field(EGU, "V") field(HOPR, "15") field(LOPR, "0") field(HIHI, "5.25") field(LOLO, "4.875") field(HIGH, "5.2") field(LOW, "4.9") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:LS11:FWVERSION.SEVR CP MS") field(DISV, "20") } record(stringin, "CRAT:IN20:LS11:CHU1_NAME") { field(SDIS, "CRAT:IN20:LS11:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:LS11:CHU1_V") { field(PREC, "1") field(EGU, "V") field(HOPR, "15") field(LOPR, "0") field(HIHI, "12.6") field(LOLO, "11.7") field(HIGH, "12.48") field(LOW, "11.76") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:LS11:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:LS11:CHU1_I") { field(PREC, "1") field(EGU, "A") field(SDIS, "CRAT:IN20:LS11:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bi, "CRAT:IN20:LS11:CHU1_STATUS") { field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ONAM, "OK") field(SDIS, "CRAT:IN20:LS11:FWVERSION.SEVR CP MS") field(DISV, "20") } record(stringin, "CRAT:IN20:LS11:CHU3_NAME") { field(SDIS, "CRAT:IN20:LS11:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:LS11:CHU3_V") { field(PREC, "2") field(EGU, "V") field(HOPR, "15") field(LOPR, "0") field(HIHI, "3.465") field(LOLO, "3.2175") field(HIGH, "3.432") field(LOW, "3.234") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:LS11:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:LS11:CHU3_I") { field(PREC, "1") field(EGU, "A") field(SDIS, "CRAT:IN20:LS11:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bi, "CRAT:IN20:LS11:CHU3_STATUS") { field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ONAM, "OK") field(SDIS, "CRAT:IN20:LS11:FWVERSION.SEVR CP MS") field(DISV, "20") } record(stringin, "CRAT:IN20:LS11:CHU5_NAME") { field(SDIS, "CRAT:IN20:LS11:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:LS11:CHU5_I") { field(PREC, "1") field(EGU, "A") field(SDIS, "CRAT:IN20:LS11:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bi, "CRAT:IN20:LS11:CHU5_STATUS") { field(FLNK, "CRAT:IN20:LS11:POWERCALC") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ONAM, "OK") field(SDIS, "CRAT:IN20:LS11:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bo, "CRAT:IN20:LS11:MAINPOWER") { field(DTYP, "stream") field(OUT, "@crat_wiener_21slot.proto.db setMainPower crat-in20-ls11") } record(bo, "CRAT:IN20:LS11:VMERESET") { field(DTYP, "stream") field(OUT, "@crat_wiener_21slot.proto.db setVmeSysReset crat-in20-ls11") } record(bo, "CRAT:IN20:LS11:FANSLOWER") { field(DTYP, "stream") field(OUT, "@crat_wiener_21slot.proto.db setFanSlower crat-in20-ls11") } record(bo, "CRAT:IN20:LS11:FANFASTER") { field(DTYP, "stream") field(OUT, "@crat_wiener_21slot.proto.db setFanFaster crat-in20-ls11") } record(ai, "CRAT:IN20:LS11:CHU5_V") { field(PREC, "1") field(EGU, "V") field(HOPR, "15") field(LOPR, "0") field(HIHI, "12.6") field(LOLO, "11.7") field(HIGH, "12.48") field(LOW, "11.76") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:LS11:FWVERSION.SEVR CP MS") field(DISV, "20") } record(seq, "CRAT:IN20:LS11:POWERSEQ1") { field(SELM, "Specified") field(SELL, "CRAT:IN20:LS11:POWERCALC") field(LNK1, "CRAT:IN20:LS11:MAINPOWER PP") field(FLNK, "CRAT:IN20:LS11:POWERMSGCALC") } record(calc, "CRAT:IN20:LS11:POWERCALC") { field(FLNK, "CRAT:IN20:LS11:POWERSEQ1") field(CALC, "A=1&&B=1&&C=0?1:A=0&&B=0&&C=1?1:0") field(INPA, "CRAT:IN20:LS11:POWERSTATE") } record(bo, "CRAT:IN20:LS11:POWEROFF") { field(HIGH, "9") field(OUT, "CRAT:IN20:LS11:POWERCALC.B") field(FLNK, "CRAT:IN20:LS11:POWERMSGCALC") } record(bo, "CRAT:IN20:LS11:POWERON") { field(OUT, "CRAT:IN20:LS11:POWERCALC.C") field(HIGH, "9") field(FLNK, "CRAT:IN20:LS11:POWERMSGCALC") } record(seq, "CRAT:IN20:LS11:HARDRESETSEQ") { field(SELM, "All") field(LNK1, "CRAT:IN20:LS11:POWEROFF PP") field(DOL1, "1") field(DLY2, "10") field(DOL2, "1") field(LNK2, "CRAT:IN20:LS11:POWERON PP") field(DLY3, "10") field(DOL3, "0") field(LNK3, "CRAT:IN20:LS11:HARDRESET PP") } record(bo, "CRAT:IN20:LS11:HARDRESET") { field(OUT, "CRAT:IN20:LS11:HARDRESETSEQ.PROC PP") field(FLNK, "CRAT:IN20:LS11:POWERMSGCALC") } record(calc, "CRAT:IN20:LS11:POWERMSGCALC") { field(FLNK, "CRAT:IN20:LS11:POWERMSG") field(CALC, "C?3:A=1&&B=0?0:A=0&&B=1?1:A=1&&B=1?2:4") field(INPA, "CRAT:IN20:LS11:POWERCALC.B") field(INPB, "CRAT:IN20:LS11:POWERCALC.C") field(INPC, "CRAT:IN20:LS11:HARDRESET") } record(mbbi, "CRAT:IN20:LS11:POWERMSG") { field(INP, "CRAT:IN20:LS11:POWERMSGCALC.VAL") field(ZRST, "TURNING_OFF") field(ONST, "TURNING_ON") field(TWST, "ERROR") field(THST, "HARD_RESETTING") field(FRST, " ") field(ZRSV, "MINOR") field(ONSV, "MINOR") field(TWSV, "MAJOR") field(THSV, "MINOR") field(FRSV, "NO_ALARM") } record(ai, "CRAT:IN20:LS11:TYPE") { field(DESC, "Wiener 21 Slot VME Crate") field(PINI, "YES") field(VAL, "2") } record(stringin, "CRAT:IN20:LS11:2NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:LS11:3NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:LS11:4NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:LS11:5NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:LS11:6NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:LS11:7NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:LS11:1NAME") { field(PINI, "YES") field(VAL, "IOC:IN20:LS11") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:LS11:8NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:LS11:9NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:LS11:10NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:LS11:11NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:LS11:12NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:LS11:13NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:LS11:14NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:LS11:15NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:LS11:16NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:LS11:17NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:LS11:18NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:LS11:19NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:LS11:20NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:LS11:21NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(calc, "CRAT:IN20:LS11:FANTEMP") { field(SCAN, "Passive") field(CALC, "A>0?(A-0)/1:A") field(EGU, "DegF") field(PREC, "0") field(HOPR, "120") field(LOPR, "20") field(HIHI, "131") field(LOLO, "-1") field(HIGH, "113") field(LOW, "-1") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(ADEL, "1") field(MDEL, "1") field(SDIS, "CRAT:IN20:LS11:FWVERSION.SEVR CP MS") field(DISV, "20") } record(stringin, "CRAT:IN20:LS11:FWVERSION") { field(SCAN, "5 second") field(DTYP, "stream") field(INP, "@crat_wiener_21slot.proto.db getStatus(CRAT:IN20:LS11) crat-in20-ls11") } record(stringin, "CRAT:IN20:LS11:LOC") { field(PINI, "YES") field(VAL, "LIT-0123") info(autosaveFields,"VAL") } record(calc, "CRAT:IN20:LS11:STATSUMY") { field(DESC, "Alarm summary for crate") field(INPA, "CRAT:IN20:LS11:FWVERSION.SEVR NPP MS") field(INPB, "CRAT:IN20:LS11:FANTEMP.SEVR NPP MS") field(INPC, "CRAT:IN20:LS11:CHU0_V.SEVR NPP MS") field(INPD, "CRAT:IN20:LS11:CHU1_V.SEVR NPP MS") field(INPE, "CRAT:IN20:LS11:CHU3_V.SEVR NPP MS") field(INPF, "CRAT:IN20:LS11:CHU5_V.SEVR NPP MS") field(INPG, "CRAT:IN20:LS11:FANSPEED.SEVR NPP MS") field(INPH, "CRAT:IN20:LS11:FANTRAY.SEVR NPP MS") field(SCAN, "1 second") field(CALC, "A+B+C+D+E+F+G+H") } #! Further lines contain data used by VisualDCT #! View(653,461,0.6) #! Record("CRAT:IN20:LS11:POWERSTATE",860,92,0,0,"CRAT:IN20:LS11:POWERSTATE") #! Field("CRAT:IN20:LS11:POWERSTATE.FLNK",16777215,1,"CRAT:IN20:LS11:POWERSTATE.FLNK") #! Link("CRAT:IN20:LS11:POWERSTATE.FLNK","CRAT:IN20:LS11:FANTRAY") #! Field("CRAT:IN20:LS11:POWERSTATE.VAL",16777215,0,"CRAT:IN20:LS11:POWERSTATE.VAL") #! Record("CRAT:IN20:LS11:FANTRAY",1360,107,0,0,"CRAT:IN20:LS11:FANTRAY") #! Field("CRAT:IN20:LS11:FANTRAY.FLNK",16777215,1,"CRAT:IN20:LS11:FANTRAY.FLNK") #! Link("CRAT:IN20:LS11:FANTRAY.FLNK","CRAT:IN20:LS11:FANSPEED") #! Record("CRAT:IN20:LS11:FANSPEED",1640,64,0,0,"CRAT:IN20:LS11:FANSPEED") #! Field("CRAT:IN20:LS11:FANSPEED.FLNK",16777215,1,"CRAT:IN20:LS11:FANSPEED.FLNK") #! Link("CRAT:IN20:LS11:FANSPEED.FLNK","CRAT:IN20:LS11:FANTEMP") #! Field("CRAT:IN20:LS11:FANSPEED.SEVR",16777215,1,"CRAT:IN20:LS11:FANSPEED.SEVR") #! Record("CRAT:IN20:LS11:CHU0_I",1420,362,0,0,"CRAT:IN20:LS11:CHU0_I") #! Field("CRAT:IN20:LS11:CHU0_I.FLNK",16777215,1,"CRAT:IN20:LS11:CHU0_I.FLNK") #! Link("CRAT:IN20:LS11:CHU0_I.FLNK","CRAT:IN20:LS11:CHU0_STATUS") #! Record("CRAT:IN20:LS11:CHU0_NAME",840,390,0,1,"CRAT:IN20:LS11:CHU0_NAME") #! Field("CRAT:IN20:LS11:CHU0_NAME.FLNK",16777215,1,"CRAT:IN20:LS11:CHU0_NAME.FLNK") #! Link("CRAT:IN20:LS11:CHU0_NAME.FLNK","CRAT:IN20:LS11:CHU0_V") #! Record("CRAT:IN20:LS11:CHU0_STATUS",1680,367,0,0,"CRAT:IN20:LS11:CHU0_STATUS") #! Field("CRAT:IN20:LS11:CHU0_STATUS.FLNK",16777215,0,"CRAT:IN20:LS11:CHU0_STATUS.FLNK") #! Link("CRAT:IN20:LS11:CHU0_STATUS.FLNK","CRAT:IN20:LS11:CHU1_NAME") #! Record("CRAT:IN20:LS11:CHU0_V",1160,197,0,0,"CRAT:IN20:LS11:CHU0_V") #! Field("CRAT:IN20:LS11:CHU0_V.FLNK",16777215,1,"CRAT:IN20:LS11:CHU0_V.FLNK") #! Link("CRAT:IN20:LS11:CHU0_V.FLNK","CRAT:IN20:LS11:CHU0_I") #! Field("CRAT:IN20:LS11:CHU0_V.SEVR",16777215,1,"CRAT:IN20:LS11:CHU0_V.SEVR") #! Record("CRAT:IN20:LS11:CHU1_NAME",840,710,0,1,"CRAT:IN20:LS11:CHU1_NAME") #! Field("CRAT:IN20:LS11:CHU1_NAME.FLNK",16777215,1,"CRAT:IN20:LS11:CHU1_NAME.FLNK") #! Link("CRAT:IN20:LS11:CHU1_NAME.FLNK","CRAT:IN20:LS11:CHU1_V") #! Record("CRAT:IN20:LS11:CHU1_V",1140,517,0,0,"CRAT:IN20:LS11:CHU1_V") #! Field("CRAT:IN20:LS11:CHU1_V.FLNK",16777215,1,"CRAT:IN20:LS11:CHU1_V.FLNK") #! Link("CRAT:IN20:LS11:CHU1_V.FLNK","CRAT:IN20:LS11:CHU1_I") #! Field("CRAT:IN20:LS11:CHU1_V.SEVR",16777215,1,"CRAT:IN20:LS11:CHU1_V.SEVR") #! Record("CRAT:IN20:LS11:CHU1_I",1420,682,0,0,"CRAT:IN20:LS11:CHU1_I") #! Field("CRAT:IN20:LS11:CHU1_I.FLNK",16777215,1,"CRAT:IN20:LS11:CHU1_I.FLNK") #! Link("CRAT:IN20:LS11:CHU1_I.FLNK","CRAT:IN20:LS11:CHU1_STATUS") #! Record("CRAT:IN20:LS11:CHU1_STATUS",1680,687,0,0,"CRAT:IN20:LS11:CHU1_STATUS") #! Field("CRAT:IN20:LS11:CHU1_STATUS.FLNK",16777215,0,"CRAT:IN20:LS11:CHU1_STATUS.FLNK") #! Link("CRAT:IN20:LS11:CHU1_STATUS.FLNK","CRAT:IN20:LS11:CHU3_NAME") #! Record("CRAT:IN20:LS11:CHU3_NAME",840,1030,0,1,"CRAT:IN20:LS11:CHU3_NAME") #! Field("CRAT:IN20:LS11:CHU3_NAME.FLNK",16777215,1,"CRAT:IN20:LS11:CHU3_NAME.FLNK") #! Link("CRAT:IN20:LS11:CHU3_NAME.FLNK","CRAT:IN20:LS11:CHU3_V") #! Record("CRAT:IN20:LS11:CHU3_V",1120,837,0,0,"CRAT:IN20:LS11:CHU3_V") #! Field("CRAT:IN20:LS11:CHU3_V.FLNK",16777215,1,"CRAT:IN20:LS11:CHU3_V.FLNK") #! Link("CRAT:IN20:LS11:CHU3_V.FLNK","CRAT:IN20:LS11:CHU3_I") #! Field("CRAT:IN20:LS11:CHU3_V.SEVR",16777215,1,"CRAT:IN20:LS11:CHU3_V.SEVR") #! Record("CRAT:IN20:LS11:CHU3_I",1420,1002,0,0,"CRAT:IN20:LS11:CHU3_I") #! Field("CRAT:IN20:LS11:CHU3_I.FLNK",16777215,1,"CRAT:IN20:LS11:CHU3_I.FLNK") #! Link("CRAT:IN20:LS11:CHU3_I.FLNK","CRAT:IN20:LS11:CHU3_STATUS") #! Record("CRAT:IN20:LS11:CHU3_STATUS",1680,1007,0,0,"CRAT:IN20:LS11:CHU3_STATUS") #! Field("CRAT:IN20:LS11:CHU3_STATUS.FLNK",16777215,0,"CRAT:IN20:LS11:CHU3_STATUS.FLNK") #! Link("CRAT:IN20:LS11:CHU3_STATUS.FLNK","CRAT:IN20:LS11:CHU5_NAME") #! Record("CRAT:IN20:LS11:CHU5_NAME",840,1370,0,1,"CRAT:IN20:LS11:CHU5_NAME") #! Field("CRAT:IN20:LS11:CHU5_NAME.FLNK",16777215,1,"CRAT:IN20:LS11:CHU5_NAME.FLNK") #! Link("CRAT:IN20:LS11:CHU5_NAME.FLNK","CRAT:IN20:LS11:CHU5_V") #! Record("CRAT:IN20:LS11:CHU5_I",1420,1342,0,0,"CRAT:IN20:LS11:CHU5_I") #! Field("CRAT:IN20:LS11:CHU5_I.FLNK",16777215,1,"CRAT:IN20:LS11:CHU5_I.FLNK") #! Link("CRAT:IN20:LS11:CHU5_I.FLNK","CRAT:IN20:LS11:CHU5_STATUS") #! Record("CRAT:IN20:LS11:CHU5_STATUS",1680,1367,0,0,"CRAT:IN20:LS11:CHU5_STATUS") #! Field("CRAT:IN20:LS11:CHU5_STATUS.FLNK",16777215,0,"CRAT:IN20:LS11:CHU5_STATUS.FLNK") #! Link("CRAT:IN20:LS11:CHU5_STATUS.FLNK","CRAT:IN20:LS11:POWERCALC") #! Record("CRAT:IN20:LS11:MAINPOWER",1740,1875,0,1,"CRAT:IN20:LS11:MAINPOWER") #! Field("CRAT:IN20:LS11:MAINPOWER.VAL",16777215,0,"CRAT:IN20:LS11:MAINPOWER.VAL") #! Record("CRAT:IN20:LS11:VMERESET",360,115,0,1,"CRAT:IN20:LS11:VMERESET") #! Record("CRAT:IN20:LS11:FANSLOWER",360,315,0,1,"CRAT:IN20:LS11:FANSLOWER") #! Record("CRAT:IN20:LS11:FANFASTER",360,215,0,1,"CRAT:IN20:LS11:FANFASTER") #! Record("CRAT:IN20:LS11:CHU5_V",1100,1197,0,0,"CRAT:IN20:LS11:CHU5_V") #! Field("CRAT:IN20:LS11:CHU5_V.FLNK",16777215,1,"CRAT:IN20:LS11:CHU5_V.FLNK") #! Link("CRAT:IN20:LS11:CHU5_V.FLNK","CRAT:IN20:LS11:CHU5_I") #! Field("CRAT:IN20:LS11:CHU5_V.SEVR",16777215,1,"CRAT:IN20:LS11:CHU5_V.SEVR") #! Record("CRAT:IN20:LS11:POWERSEQ1",1420,1707,0,0,"CRAT:IN20:LS11:POWERSEQ1") #! Field("CRAT:IN20:LS11:POWERSEQ1.LNK1",16777215,1,"CRAT:IN20:LS11:POWERSEQ1.LNK1") #! Link("CRAT:IN20:LS11:POWERSEQ1.LNK1","CRAT:IN20:LS11:MAINPOWER.VAL") #! Field("CRAT:IN20:LS11:POWERSEQ1.SELL",16777215,0,"CRAT:IN20:LS11:POWERSEQ1.SELL") #! Link("CRAT:IN20:LS11:POWERSEQ1.SELL","CRAT:IN20:LS11:POWERCALC.VAL") #! Field("CRAT:IN20:LS11:POWERSEQ1.FLNK",16777215,0,"CRAT:IN20:LS11:POWERSEQ1.FLNK") #! Link("CRAT:IN20:LS11:POWERSEQ1.FLNK","CRAT:IN20:LS11:POWERMSGCALC") #! Record("CRAT:IN20:LS11:POWERCALC",960,1702,0,1,"CRAT:IN20:LS11:POWERCALC") #! Field("CRAT:IN20:LS11:POWERCALC.INPA",16777215,0,"CRAT:IN20:LS11:POWERCALC.INPA") #! Link("CRAT:IN20:LS11:POWERCALC.INPA","CRAT:IN20:LS11:POWERSTATE.VAL") #! Field("CRAT:IN20:LS11:POWERCALC.FLNK",16777215,1,"CRAT:IN20:LS11:POWERCALC.FLNK") #! Link("CRAT:IN20:LS11:POWERCALC.FLNK","CRAT:IN20:LS11:POWERSEQ1") #! Field("CRAT:IN20:LS11:POWERCALC.VAL",16777215,1,"CRAT:IN20:LS11:POWERCALC.VAL") #! Field("CRAT:IN20:LS11:POWERCALC.B",16777215,0,"CRAT:IN20:LS11:POWERCALC.B") #! Field("CRAT:IN20:LS11:POWERCALC.C",16777215,0,"CRAT:IN20:LS11:POWERCALC.C") #! Record("CRAT:IN20:LS11:POWEROFF",620,1762,0,1,"CRAT:IN20:LS11:POWEROFF") #! Field("CRAT:IN20:LS11:POWEROFF.OUT",16777215,1,"CRAT:IN20:LS11:POWEROFF.OUT") #! Link("CRAT:IN20:LS11:POWEROFF.OUT","CRAT:IN20:LS11:POWERCALC.B") #! Field("CRAT:IN20:LS11:POWEROFF.VAL",16777215,0,"CRAT:IN20:LS11:POWEROFF.VAL") #! Field("CRAT:IN20:LS11:POWEROFF.FLNK",16777215,1,"CRAT:IN20:LS11:POWEROFF.FLNK") #! Link("CRAT:IN20:LS11:POWEROFF.FLNK","CRAT:IN20:LS11:POWERMSGCALC") #! Record("CRAT:IN20:LS11:POWERON",620,1942,0,1,"CRAT:IN20:LS11:POWERON") #! Field("CRAT:IN20:LS11:POWERON.VAL",16777215,0,"CRAT:IN20:LS11:POWERON.VAL") #! Field("CRAT:IN20:LS11:POWERON.OUT",16777215,1,"CRAT:IN20:LS11:POWERON.OUT") #! Link("CRAT:IN20:LS11:POWERON.OUT","CRAT:IN20:LS11:POWERCALC.C") #! Field("CRAT:IN20:LS11:POWERON.FLNK",16777215,1,"CRAT:IN20:LS11:POWERON.FLNK") #! Link("CRAT:IN20:LS11:POWERON.FLNK","CRAT:IN20:LS11:POWERMSGCALC") #! Record("CRAT:IN20:LS11:HARDRESETSEQ",340,1735,0,1,"CRAT:IN20:LS11:HARDRESETSEQ") #! Field("CRAT:IN20:LS11:HARDRESETSEQ.LNK1",16777215,1,"CRAT:IN20:LS11:HARDRESETSEQ.LNK1") #! Link("CRAT:IN20:LS11:HARDRESETSEQ.LNK1","CRAT:IN20:LS11:POWEROFF.VAL") #! Field("CRAT:IN20:LS11:HARDRESETSEQ.LNK2",16777215,1,"CRAT:IN20:LS11:HARDRESETSEQ.LNK2") #! Link("CRAT:IN20:LS11:HARDRESETSEQ.LNK2","CRAT:IN20:LS11:POWERON.VAL") #! Field("CRAT:IN20:LS11:HARDRESETSEQ.PROC",16777215,0,"CRAT:IN20:LS11:HARDRESETSEQ.PROC") #! Field("CRAT:IN20:LS11:HARDRESETSEQ.LNK3",16777215,0,"CRAT:IN20:LS11:HARDRESETSEQ.LNK3") #! Link("CRAT:IN20:LS11:HARDRESETSEQ.LNK3","CRAT:IN20:LS11:HARDRESET.VAL") #! Record("CRAT:IN20:LS11:HARDRESET",20,1975,0,1,"CRAT:IN20:LS11:HARDRESET") #! Field("CRAT:IN20:LS11:HARDRESET.OUT",16777215,1,"CRAT:IN20:LS11:HARDRESET.OUT") #! Link("CRAT:IN20:LS11:HARDRESET.OUT","CRAT:IN20:LS11:HARDRESETSEQ.PROC") #! Field("CRAT:IN20:LS11:HARDRESET.VAL",16777215,1,"CRAT:IN20:LS11:HARDRESET.VAL") #! Field("CRAT:IN20:LS11:HARDRESET.FLNK",16777215,1,"CRAT:IN20:LS11:HARDRESET.FLNK") #! Link("CRAT:IN20:LS11:HARDRESET.FLNK","CRAT:IN20:LS11:POWERMSGCALC") #! Record("CRAT:IN20:LS11:POWERMSGCALC",1020,2172,0,1,"CRAT:IN20:LS11:POWERMSGCALC") #! Field("CRAT:IN20:LS11:POWERMSGCALC.INPA",16777215,0,"CRAT:IN20:LS11:POWERMSGCALC.INPA") #! Link("CRAT:IN20:LS11:POWERMSGCALC.INPA","CRAT:IN20:LS11:POWERCALC.B") #! Field("CRAT:IN20:LS11:POWERMSGCALC.INPB",16777215,0,"CRAT:IN20:LS11:POWERMSGCALC.INPB") #! Link("CRAT:IN20:LS11:POWERMSGCALC.INPB","CRAT:IN20:LS11:POWERCALC.C") #! Field("CRAT:IN20:LS11:POWERMSGCALC.INPC",16777215,0,"CRAT:IN20:LS11:POWERMSGCALC.INPC") #! Link("CRAT:IN20:LS11:POWERMSGCALC.INPC","CRAT:IN20:LS11:HARDRESET.VAL") #! Field("CRAT:IN20:LS11:POWERMSGCALC.FLNK",16777215,1,"CRAT:IN20:LS11:POWERMSGCALC.FLNK") #! Link("CRAT:IN20:LS11:POWERMSGCALC.FLNK","CRAT:IN20:LS11:POWERMSG") #! Field("CRAT:IN20:LS11:POWERMSGCALC.VAL",16777215,1,"CRAT:IN20:LS11:POWERMSGCALC.VAL") #! Record("CRAT:IN20:LS11:POWERMSG",1360,2167,0,0,"CRAT:IN20:LS11:POWERMSG") #! Field("CRAT:IN20:LS11:POWERMSG.INP",16777215,0,"CRAT:IN20:LS11:POWERMSG.INP") #! Link("CRAT:IN20:LS11:POWERMSG.INP","CRAT:IN20:LS11:POWERMSGCALC.VAL") #! Record("CRAT:IN20:LS11:TYPE",360,502,0,1,"CRAT:IN20:LS11:TYPE") #! Record("CRAT:IN20:LS11:2NAME",40,775,0,1,"CRAT:IN20:LS11:2NAME") #! Record("CRAT:IN20:LS11:3NAME",40,875,0,1,"CRAT:IN20:LS11:3NAME") #! Record("CRAT:IN20:LS11:4NAME",40,975,0,1,"CRAT:IN20:LS11:4NAME") #! Record("CRAT:IN20:LS11:5NAME",40,1075,0,1,"CRAT:IN20:LS11:5NAME") #! Record("CRAT:IN20:LS11:6NAME",40,1175,0,1,"CRAT:IN20:LS11:6NAME") #! Record("CRAT:IN20:LS11:7NAME",40,1275,0,1,"CRAT:IN20:LS11:7NAME") #! Record("CRAT:IN20:LS11:1NAME",40,675,0,1,"CRAT:IN20:LS11:1NAME") #! Record("CRAT:IN20:LS11:8NAME",240,675,0,1,"CRAT:IN20:LS11:8NAME") #! Record("CRAT:IN20:LS11:9NAME",240,775,0,1,"CRAT:IN20:LS11:9NAME") #! Record("CRAT:IN20:LS11:10NAME",240,875,0,1,"CRAT:IN20:LS11:10NAME") #! Record("CRAT:IN20:LS11:11NAME",240,975,0,1,"CRAT:IN20:LS11:11NAME") #! Record("CRAT:IN20:LS11:12NAME",240,1075,0,1,"CRAT:IN20:LS11:12NAME") #! Record("CRAT:IN20:LS11:13NAME",240,1175,0,1,"CRAT:IN20:LS11:13NAME") #! Record("CRAT:IN20:LS11:14NAME",240,1275,0,1,"CRAT:IN20:LS11:14NAME") #! Record("CRAT:IN20:LS11:15NAME",440,675,0,1,"CRAT:IN20:LS11:15NAME") #! Record("CRAT:IN20:LS11:16NAME",440,775,0,1,"CRAT:IN20:LS11:16NAME") #! Record("CRAT:IN20:LS11:17NAME",440,875,0,1,"CRAT:IN20:LS11:17NAME") #! Record("CRAT:IN20:LS11:18NAME",440,975,0,1,"CRAT:IN20:LS11:18NAME") #! Record("CRAT:IN20:LS11:19NAME",440,1075,0,1,"CRAT:IN20:LS11:19NAME") #! Record("CRAT:IN20:LS11:20NAME",440,1175,0,1,"CRAT:IN20:LS11:20NAME") #! Record("CRAT:IN20:LS11:21NAME",440,1275,0,1,"CRAT:IN20:LS11:21NAME") #! Record("CRAT:IN20:LS11:FANTEMP",1940,14,0,0,"CRAT:IN20:LS11:FANTEMP") #! Field("CRAT:IN20:LS11:FANTEMP.FLNK",16777215,0,"CRAT:IN20:LS11:FANTEMP.FLNK") #! Link("CRAT:IN20:LS11:FANTEMP.FLNK","CRAT:IN20:LS11:CHU0_NAME") #! Field("CRAT:IN20:LS11:FANTEMP.SEVR",16777215,1,"CRAT:IN20:LS11:FANTEMP.SEVR") #! Record("CRAT:IN20:LS11:FWVERSION",560,67,0,1,"CRAT:IN20:LS11:FWVERSION") #! Field("CRAT:IN20:LS11:FWVERSION.FLNK",16777215,1,"CRAT:IN20:LS11:FWVERSION.FLNK") #! Link("CRAT:IN20:LS11:FWVERSION.FLNK","CRAT:IN20:LS11:POWERSTATE") #! Field("CRAT:IN20:LS11:FWVERSION.SEVR",16777215,1,"CRAT:IN20:LS11:FWVERSION.SEVR") #! Record("CRAT:IN20:LS11:LOC",120,155,0,1,"CRAT:IN20:LS11:LOC") #! Record("CRAT:IN20:LS11:STATSUMY",2380,1380,0,1,"CRAT:IN20:LS11:STATSUMY") #! Field("CRAT:IN20:LS11:STATSUMY.INPA",16777215,0,"CRAT:IN20:LS11:STATSUMY.INPA") #! Link("CRAT:IN20:LS11:STATSUMY.INPA","CRAT:IN20:LS11:FWVERSION.SEVR") #! Field("CRAT:IN20:LS11:STATSUMY.INPB",16777215,0,"CRAT:IN20:LS11:STATSUMY.INPB") #! Link("CRAT:IN20:LS11:STATSUMY.INPB","CRAT:IN20:LS11:FANTEMP.SEVR") #! Field("CRAT:IN20:LS11:STATSUMY.INPC",16777215,0,"CRAT:IN20:LS11:STATSUMY.INPC") #! Link("CRAT:IN20:LS11:STATSUMY.INPC","CRAT:IN20:LS11:CHU0_V.SEVR") #! Field("CRAT:IN20:LS11:STATSUMY.INPD",16777215,0,"CRAT:IN20:LS11:STATSUMY.INPD") #! Link("CRAT:IN20:LS11:STATSUMY.INPD","CRAT:IN20:LS11:CHU1_V.SEVR") #! Field("CRAT:IN20:LS11:STATSUMY.INPE",16777215,0,"CRAT:IN20:LS11:STATSUMY.INPE") #! Link("CRAT:IN20:LS11:STATSUMY.INPE","CRAT:IN20:LS11:CHU3_V.SEVR") #! Field("CRAT:IN20:LS11:STATSUMY.INPF",16777215,0,"CRAT:IN20:LS11:STATSUMY.INPF") #! Link("CRAT:IN20:LS11:STATSUMY.INPF","CRAT:IN20:LS11:CHU5_V.SEVR") #! Field("CRAT:IN20:LS11:STATSUMY.INPG",16777215,0,"CRAT:IN20:LS11:STATSUMY.INPG") #! Link("CRAT:IN20:LS11:STATSUMY.INPG","CRAT:IN20:LS11:FANSPEED.SEVR") #! TextBox(TB0,40,1420,480,1740,1,"Dialog",12,1,16777215,"The web interface for this crate only provides a \"toggle power\" button.\nThere is no way to send a command to turn the power on or turn the power off.\nThe purpose of all these PVs is to provide POWERON and POWEROFF \nbuttons rather than the inferior toggle button.\n\nProcessing the POWERON record when the crate is off will turn it on. \nProcessing the POWEROFF record when the crate is on will turn it off.\nProcessing the HARDRESET record will first force the POWEROFF record\nto process, then it will force the POWERON record to process.\n\nThe POWERON and POWEROFF steps take about 10 seconds each: First the IOC\nmust wait to get new on/off status (which takes five seconds) before deciding\nwhether or not to toggle the crate power. Then it sends the toggle command\nand it takes another 5 seconds to see the change in on/off status.\n\nPOWERMSG contains a string that describes what is currently happening.\nIt is normally empty, but contains text if the power is being turned on, off, or \nreset.",null) #! Generated by VisualDCT v2.5 #! DBDSTART #! DBDEND record(bi, "CRAT:IN20:BC01:POWERSTATE") { field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ZNAM, "OFF") field(ONAM, "ON") field(SDIS, "CRAT:IN20:BC01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bi, "CRAT:IN20:BC01:FANTRAY") { field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ONAM, "OK") field(SDIS, "CRAT:IN20:BC01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:BC01:FANSPEED") { field(EGU, "RPM") field(LOLO, "1150") field(HHSV, "NO_ALARM") field(LLSV, "MAJOR") field(HSV, "NO_ALARM") field(LSV, "NO_ALARM") field(SDIS, "CRAT:IN20:BC01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:BC01:CHU0_I") { field(PREC, "1") field(EGU, "A") field(SDIS, "CRAT:IN20:BC01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(stringin, "CRAT:IN20:BC01:CHU0_NAME") { field(SDIS, "CRAT:IN20:BC01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bi, "CRAT:IN20:BC01:CHU0_STATUS") { field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ONAM, "OK") field(SDIS, "CRAT:IN20:BC01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:BC01:CHU0_V") { field(PREC, "2") field(EGU, "V") field(HOPR, "15") field(LOPR, "0") field(HIHI, "5.25") field(LOLO, "4.875") field(HIGH, "5.2") field(LOW, "4.9") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:BC01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(stringin, "CRAT:IN20:BC01:CHU1_NAME") { field(SDIS, "CRAT:IN20:BC01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:BC01:CHU1_V") { field(PREC, "1") field(EGU, "V") field(HOPR, "15") field(LOPR, "0") field(HIHI, "12.6") field(LOLO, "11.7") field(HIGH, "12.48") field(LOW, "11.76") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:BC01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:BC01:CHU1_I") { field(PREC, "1") field(EGU, "A") field(SDIS, "CRAT:IN20:BC01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bi, "CRAT:IN20:BC01:CHU1_STATUS") { field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ONAM, "OK") field(SDIS, "CRAT:IN20:BC01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(stringin, "CRAT:IN20:BC01:CHU3_NAME") { field(SDIS, "CRAT:IN20:BC01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:BC01:CHU3_V") { field(PREC, "2") field(EGU, "V") field(HOPR, "15") field(LOPR, "0") field(HIHI, "3.465") field(LOLO, "3.2175") field(HIGH, "3.432") field(LOW, "3.234") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:BC01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:BC01:CHU3_I") { field(PREC, "1") field(EGU, "A") field(SDIS, "CRAT:IN20:BC01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bi, "CRAT:IN20:BC01:CHU3_STATUS") { field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ONAM, "OK") field(SDIS, "CRAT:IN20:BC01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(stringin, "CRAT:IN20:BC01:CHU5_NAME") { field(SDIS, "CRAT:IN20:BC01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:BC01:CHU5_I") { field(PREC, "1") field(EGU, "A") field(SDIS, "CRAT:IN20:BC01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bi, "CRAT:IN20:BC01:CHU5_STATUS") { field(FLNK, "CRAT:IN20:BC01:UPDATE2") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ONAM, "OK") field(SDIS, "CRAT:IN20:BC01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(calc, "CRAT:IN20:BC01:TEMP2") { field(CALC, "A>0?(A-0)/1:A") field(EGU, "DegF") field(PREC, "0") field(HOPR, "120") field(LOPR, "20") field(HIHI, "131") field(LOLO, "-1") field(HIGH, "113") field(LOW, "-1") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:BC01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(calc, "CRAT:IN20:BC01:TEMP3") { field(CALC, "A>0?(A-0)/1:A") field(EGU, "DegF") field(PREC, "0") field(HOPR, "120") field(LOPR, "20") field(HIHI, "131") field(LOLO, "-1") field(HIGH, "113") field(LOW, "-1") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:BC01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(calc, "CRAT:IN20:BC01:TEMP4") { field(CALC, "A>0?(A-0)/1:A") field(EGU, "DegF") field(PREC, "0") field(HOPR, "120") field(LOPR, "20") field(HIHI, "131") field(LOLO, "-1") field(HIGH, "113") field(LOW, "-1") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:BC01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bo, "CRAT:IN20:BC01:MAINPOWER") { field(DTYP, "stream") field(OUT, "@crat_wiener_7slot.proto.db setMainPower crat-in20-bc01") } record(bo, "CRAT:IN20:BC01:VMERESET") { field(DTYP, "stream") field(OUT, "@crat_wiener_7slot.proto.db setVmeSysReset crat-in20-bc01") } record(bo, "CRAT:IN20:BC01:FANSLOWER") { field(DTYP, "stream") field(OUT, "@crat_wiener_7slot.proto.db setFanSlower crat-in20-bc01") } record(bo, "CRAT:IN20:BC01:FANFASTER") { field(DTYP, "stream") field(OUT, "@crat_wiener_7slot.proto.db setFanFaster crat-in20-bc01") } record(calc, "CRAT:IN20:BC01:TEMP1") { field(CALC, "A>0?(A-0)/1:A") field(SCAN, "Passive") field(EGU, "DegF") field(PREC, "0") field(HOPR, "120") field(LOPR, "20") field(HIHI, "131") field(LOLO, "-1") field(HIGH, "113") field(LOW, "-1") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:BC01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:BC01:CHU5_V") { field(PREC, "1") field(EGU, "V") field(HOPR, "15") field(LOPR, "0") field(HIHI, "12.6") field(LOLO, "11.7") field(HIGH, "12.48") field(LOW, "11.76") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:BC01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bi, "CRAT:IN20:BC01:UPDATE2") { field(SCAN, "Passive") field(DTYP, "stream") field(INP, "@crat_wiener_7slot.proto.db getTemp(CRAT:IN20:BC01) crat-in20-bc01") } record(seq, "CRAT:IN20:BC01:POWERSEQ1") { field(SELM, "Specified") field(SELL, "CRAT:IN20:BC01:POWERCALC") field(LNK1, "CRAT:IN20:BC01:MAINPOWER PP") field(FLNK, "CRAT:IN20:BC01:POWERMSGCALC") } record(calc, "CRAT:IN20:BC01:POWERCALC") { field(FLNK, "CRAT:IN20:BC01:POWERSEQ1") field(CALC, "A=1&&B=1&&C=0?1:A=0&&B=0&&C=1?1:0") field(INPA, "CRAT:IN20:BC01:POWERSTATE") } record(bo, "CRAT:IN20:BC01:POWEROFF") { field(HIGH, "9") field(OUT, "CRAT:IN20:BC01:POWERCALC.B") field(FLNK, "CRAT:IN20:BC01:POWERMSGCALC") } record(bo, "CRAT:IN20:BC01:POWERON") { field(OUT, "CRAT:IN20:BC01:POWERCALC.C") field(HIGH, "9") field(FLNK, "CRAT:IN20:BC01:POWERMSGCALC") } record(seq, "CRAT:IN20:BC01:HARDRESETSEQ") { field(SELM, "All") field(LNK1, "CRAT:IN20:BC01:POWEROFF PP") field(DOL1, "1") field(DLY2, "10") field(DOL2, "1") field(LNK2, "CRAT:IN20:BC01:POWERON PP") field(DLY3, "10") field(DOL3, "0") field(LNK3, "CRAT:IN20:BC01:HARDRESET PP") } record(bo, "CRAT:IN20:BC01:HARDRESET") { field(OUT, "CRAT:IN20:BC01:HARDRESETSEQ.PROC PP") field(FLNK, "CRAT:IN20:BC01:POWERMSGCALC") } record(calc, "CRAT:IN20:BC01:POWERMSGCALC") { field(FLNK, "CRAT:IN20:BC01:POWERMSG") field(CALC, "C?3:A=1&&B=0?0:A=0&&B=1?1:A=1&&B=1?2:4") field(INPA, "CRAT:IN20:BC01:POWERCALC.B") field(INPB, "CRAT:IN20:BC01:POWERCALC.C") field(INPC, "CRAT:IN20:BC01:HARDRESET") } record(mbbi, "CRAT:IN20:BC01:POWERMSG") { field(INP, "CRAT:IN20:BC01:POWERMSGCALC.VAL") field(ZRST, "TURNING_OFF") field(ONST, "TURNING_ON") field(TWST, "ERROR") field(THST, "HARD_RESETTING") field(FRST, " ") field(ZRSV, "MINOR") field(ONSV, "MINOR") field(TWSV, "MAJOR") field(THSV, "MINOR") field(FRSV, "NO_ALARM") } record(ai, "CRAT:IN20:BC01:TYPE") { field(DESC, "Wiener 7 Slot VME Crate") field(PINI, "YES") field(VAL, "1") } record(stringin, "CRAT:IN20:BC01:2NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:BC01:3NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:BC01:4NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:BC01:5NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:BC01:6NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:BC01:7NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:BC01:1NAME") { field(PINI, "YES") field(VAL, "IOC:IN20:BC01") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:BC01:FWVERSION") { field(SCAN, "5 second") field(DTYP, "stream") field(INP, "@crat_wiener_7slot.proto.db getStatus(CRAT:IN20:BC01) crat-in20-bc01") } record(stringin, "CRAT:IN20:BC01:LOC") { field(PINI, "YES") field(VAL, "LKG-1735") info(autosaveFields,"VAL") } record(calc, "CRAT:IN20:BC01:TEMPSUM") { field(DESC, "Temperature alarm summary") field(CALC, "A+B+C+D+E+F+G+H") field(INPA, "CRAT:IN20:BC01:TEMP1.SEVR NPP MS") field(INPB, "CRAT:IN20:BC01:TEMP2.SEVR NPP MS") field(INPC, "CRAT:IN20:BC01:TEMP3.SEVR NPP MS") field(INPD, "CRAT:IN20:BC01:TEMP4.SEVR NPP MS") field(INPE, "CRAT:IN20:BC01:TEMP5.SEVR NPP MS") field(INPF, "CRAT:IN20:BC01:TEMP6.SEVR NPP MS") field(INPG, "CRAT:IN20:BC01:TEMP7.SEVR NPP MS") field(INPH, "CRAT:IN20:BC01:TEMP8.SEVR NPP MS") field(SCAN, "1 second") } record(calc, "CRAT:IN20:BC01:STATSUMY") { field(DESC, "Alarm summary for crate") field(INPA, "CRAT:IN20:BC01:FWVERSION.SEVR NPP MS") field(INPB, "CRAT:IN20:BC01:TEMPSUM.SEVR NPP MS") field(INPC, "CRAT:IN20:BC01:CHU0_V.SEVR NPP MS") field(INPD, "CRAT:IN20:BC01:CHU1_V.SEVR NPP MS") field(INPE, "CRAT:IN20:BC01:CHU3_V.SEVR NPP MS") field(INPF, "CRAT:IN20:BC01:CHU5_V.SEVR NPP MS") field(INPG, "CRAT:IN20:BC01:FANSPEED.SEVR NPP MS") field(INPH, "CRAT:IN20:BC01:FANTRAY.SEVR NPP MS") field(SCAN, "1 second") field(CALC, "A+B+C+D+E+F+G+H") } record(calc, "CRAT:IN20:BC01:TEMP5") { field(CALC, "A>0?(A-0)/1:A") field(EGU, "DegF") field(PREC, "0") field(HOPR, "120") field(LOPR, "20") field(HIHI, "131") field(LOLO, "-1") field(HIGH, "113") field(LOW, "-1") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:BC01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(calc, "CRAT:IN20:BC01:TEMP6") { field(CALC, "A>0?(A-0)/1:A") field(EGU, "DegF") field(PREC, "0") field(HOPR, "120") field(LOPR, "20") field(HIHI, "131") field(LOLO, "-1") field(HIGH, "113") field(LOW, "-1") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:BC01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(calc, "CRAT:IN20:BC01:TEMP7") { field(CALC, "A>0?(A-0)/1:A") field(EGU, "DegF") field(PREC, "0") field(HOPR, "120") field(LOPR, "20") field(HIHI, "131") field(LOLO, "-1") field(HIGH, "113") field(LOW, "-1") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:BC01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(calc, "CRAT:IN20:BC01:TEMP8") { field(CALC, "A>0?(A-0)/1:A") field(FLNK, "CRAT:IN20:BC01:POWERCALC") field(EGU, "DegF") field(PREC, "0") field(HOPR, "120") field(LOPR, "20") field(HIHI, "131") field(LOLO, "-1") field(HIGH, "113") field(LOW, "-1") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:BC01:FWVERSION.SEVR CP MS") field(DISV, "20") } #! Further lines contain data used by VisualDCT #! View(0,235,0.3) #! Record("CRAT:IN20:BC01:POWERSTATE",860,180,0,0,"CRAT:IN20:BC01:POWERSTATE") #! Field("CRAT:IN20:BC01:POWERSTATE.FLNK",16777215,1,"CRAT:IN20:BC01:POWERSTATE.FLNK") #! Link("CRAT:IN20:BC01:POWERSTATE.FLNK","CRAT:IN20:BC01:FANTRAY") #! Field("CRAT:IN20:BC01:POWERSTATE.VAL",16777215,0,"CRAT:IN20:BC01:POWERSTATE.VAL") #! Record("CRAT:IN20:BC01:FANTRAY",1360,194,0,0,"CRAT:IN20:BC01:FANTRAY") #! Field("CRAT:IN20:BC01:FANTRAY.FLNK",16777215,1,"CRAT:IN20:BC01:FANTRAY.FLNK") #! Link("CRAT:IN20:BC01:FANTRAY.FLNK","CRAT:IN20:BC01:FANSPEED") #! Record("CRAT:IN20:BC01:FANSPEED",1620,174,0,0,"CRAT:IN20:BC01:FANSPEED") #! Field("CRAT:IN20:BC01:FANSPEED.FLNK",16777215,0,"CRAT:IN20:BC01:FANSPEED.FLNK") #! Link("CRAT:IN20:BC01:FANSPEED.FLNK","CRAT:IN20:BC01:CHU0_NAME") #! Field("CRAT:IN20:BC01:FANSPEED.SEVR",16777215,1,"CRAT:IN20:BC01:FANSPEED.SEVR") #! Record("CRAT:IN20:BC01:CHU0_I",1360,507,0,0,"CRAT:IN20:BC01:CHU0_I") #! Field("CRAT:IN20:BC01:CHU0_I.FLNK",16777215,1,"CRAT:IN20:BC01:CHU0_I.FLNK") #! Link("CRAT:IN20:BC01:CHU0_I.FLNK","CRAT:IN20:BC01:CHU0_STATUS") #! Record("CRAT:IN20:BC01:CHU0_NAME",840,534,0,1,"CRAT:IN20:BC01:CHU0_NAME") #! Field("CRAT:IN20:BC01:CHU0_NAME.FLNK",16777215,1,"CRAT:IN20:BC01:CHU0_NAME.FLNK") #! Link("CRAT:IN20:BC01:CHU0_NAME.FLNK","CRAT:IN20:BC01:CHU0_V") #! Record("CRAT:IN20:BC01:CHU0_STATUS",1620,514,0,0,"CRAT:IN20:BC01:CHU0_STATUS") #! Field("CRAT:IN20:BC01:CHU0_STATUS.FLNK",16777215,0,"CRAT:IN20:BC01:CHU0_STATUS.FLNK") #! Link("CRAT:IN20:BC01:CHU0_STATUS.FLNK","CRAT:IN20:BC01:CHU1_NAME") #! Record("CRAT:IN20:BC01:CHU0_V",1100,370,0,0,"CRAT:IN20:BC01:CHU0_V") #! Field("CRAT:IN20:BC01:CHU0_V.FLNK",16777215,1,"CRAT:IN20:BC01:CHU0_V.FLNK") #! Link("CRAT:IN20:BC01:CHU0_V.FLNK","CRAT:IN20:BC01:CHU0_I") #! Field("CRAT:IN20:BC01:CHU0_V.SEVR",16777215,1,"CRAT:IN20:BC01:CHU0_V.SEVR") #! Record("CRAT:IN20:BC01:CHU1_NAME",840,834,0,1,"CRAT:IN20:BC01:CHU1_NAME") #! Field("CRAT:IN20:BC01:CHU1_NAME.FLNK",16777215,1,"CRAT:IN20:BC01:CHU1_NAME.FLNK") #! Link("CRAT:IN20:BC01:CHU1_NAME.FLNK","CRAT:IN20:BC01:CHU1_V") #! Record("CRAT:IN20:BC01:CHU1_V",1100,670,0,0,"CRAT:IN20:BC01:CHU1_V") #! Field("CRAT:IN20:BC01:CHU1_V.FLNK",16777215,1,"CRAT:IN20:BC01:CHU1_V.FLNK") #! Link("CRAT:IN20:BC01:CHU1_V.FLNK","CRAT:IN20:BC01:CHU1_I") #! Field("CRAT:IN20:BC01:CHU1_V.SEVR",16777215,1,"CRAT:IN20:BC01:CHU1_V.SEVR") #! Record("CRAT:IN20:BC01:CHU1_I",1360,807,0,0,"CRAT:IN20:BC01:CHU1_I") #! Field("CRAT:IN20:BC01:CHU1_I.FLNK",16777215,1,"CRAT:IN20:BC01:CHU1_I.FLNK") #! Link("CRAT:IN20:BC01:CHU1_I.FLNK","CRAT:IN20:BC01:CHU1_STATUS") #! Record("CRAT:IN20:BC01:CHU1_STATUS",1620,814,0,0,"CRAT:IN20:BC01:CHU1_STATUS") #! Field("CRAT:IN20:BC01:CHU1_STATUS.FLNK",16777215,0,"CRAT:IN20:BC01:CHU1_STATUS.FLNK") #! Link("CRAT:IN20:BC01:CHU1_STATUS.FLNK","CRAT:IN20:BC01:CHU3_NAME") #! Record("CRAT:IN20:BC01:CHU3_NAME",840,1134,0,1,"CRAT:IN20:BC01:CHU3_NAME") #! Field("CRAT:IN20:BC01:CHU3_NAME.FLNK",16777215,1,"CRAT:IN20:BC01:CHU3_NAME.FLNK") #! Link("CRAT:IN20:BC01:CHU3_NAME.FLNK","CRAT:IN20:BC01:CHU3_V") #! Record("CRAT:IN20:BC01:CHU3_V",1100,970,0,0,"CRAT:IN20:BC01:CHU3_V") #! Field("CRAT:IN20:BC01:CHU3_V.FLNK",16777215,1,"CRAT:IN20:BC01:CHU3_V.FLNK") #! Link("CRAT:IN20:BC01:CHU3_V.FLNK","CRAT:IN20:BC01:CHU3_I") #! Field("CRAT:IN20:BC01:CHU3_V.SEVR",16777215,1,"CRAT:IN20:BC01:CHU3_V.SEVR") #! Record("CRAT:IN20:BC01:CHU3_I",1360,1107,0,0,"CRAT:IN20:BC01:CHU3_I") #! Field("CRAT:IN20:BC01:CHU3_I.FLNK",16777215,1,"CRAT:IN20:BC01:CHU3_I.FLNK") #! Link("CRAT:IN20:BC01:CHU3_I.FLNK","CRAT:IN20:BC01:CHU3_STATUS") #! Record("CRAT:IN20:BC01:CHU3_STATUS",1620,1114,0,0,"CRAT:IN20:BC01:CHU3_STATUS") #! Field("CRAT:IN20:BC01:CHU3_STATUS.FLNK",16777215,0,"CRAT:IN20:BC01:CHU3_STATUS.FLNK") #! Link("CRAT:IN20:BC01:CHU3_STATUS.FLNK","CRAT:IN20:BC01:CHU5_NAME") #! Record("CRAT:IN20:BC01:CHU5_NAME",840,1454,0,1,"CRAT:IN20:BC01:CHU5_NAME") #! Field("CRAT:IN20:BC01:CHU5_NAME.FLNK",16777215,1,"CRAT:IN20:BC01:CHU5_NAME.FLNK") #! Link("CRAT:IN20:BC01:CHU5_NAME.FLNK","CRAT:IN20:BC01:CHU5_V") #! Record("CRAT:IN20:BC01:CHU5_I",1360,1427,0,0,"CRAT:IN20:BC01:CHU5_I") #! Field("CRAT:IN20:BC01:CHU5_I.FLNK",16777215,1,"CRAT:IN20:BC01:CHU5_I.FLNK") #! Link("CRAT:IN20:BC01:CHU5_I.FLNK","CRAT:IN20:BC01:CHU5_STATUS") #! Record("CRAT:IN20:BC01:CHU5_STATUS",1620,1454,0,0,"CRAT:IN20:BC01:CHU5_STATUS") #! Field("CRAT:IN20:BC01:CHU5_STATUS.FLNK",16777215,0,"CRAT:IN20:BC01:CHU5_STATUS.FLNK") #! Link("CRAT:IN20:BC01:CHU5_STATUS.FLNK","CRAT:IN20:BC01:UPDATE2") #! Record("CRAT:IN20:BC01:TEMP2",1120,1770,0,1,"CRAT:IN20:BC01:TEMP2") #! Field("CRAT:IN20:BC01:TEMP2.FLNK",16777215,1,"CRAT:IN20:BC01:TEMP2.FLNK") #! Link("CRAT:IN20:BC01:TEMP2.FLNK","CRAT:IN20:BC01:TEMP3") #! Field("CRAT:IN20:BC01:TEMP2.SEVR",16777215,1,"CRAT:IN20:BC01:TEMP2.SEVR") #! Record("CRAT:IN20:BC01:TEMP3",1380,1770,0,0,"CRAT:IN20:BC01:TEMP3") #! Field("CRAT:IN20:BC01:TEMP3.FLNK",16777215,1,"CRAT:IN20:BC01:TEMP3.FLNK") #! Link("CRAT:IN20:BC01:TEMP3.FLNK","CRAT:IN20:BC01:TEMP4") #! Field("CRAT:IN20:BC01:TEMP3.SEVR",16777215,1,"CRAT:IN20:BC01:TEMP3.SEVR") #! Record("CRAT:IN20:BC01:TEMP4",1640,1790,0,0,"CRAT:IN20:BC01:TEMP4") #! Field("CRAT:IN20:BC01:TEMP4.FLNK",16777215,0,"CRAT:IN20:BC01:TEMP4.FLNK") #! Link("CRAT:IN20:BC01:TEMP4.FLNK","CRAT:IN20:BC01:TEMP5") #! Field("CRAT:IN20:BC01:TEMP4.SEVR",16777215,1,"CRAT:IN20:BC01:TEMP4.SEVR") #! Record("CRAT:IN20:BC01:MAINPOWER",1740,2860,0,1,"CRAT:IN20:BC01:MAINPOWER") #! Field("CRAT:IN20:BC01:MAINPOWER.VAL",16777215,0,"CRAT:IN20:BC01:MAINPOWER.VAL") #! Record("CRAT:IN20:BC01:VMERESET",360,520,0,1,"CRAT:IN20:BC01:VMERESET") #! Record("CRAT:IN20:BC01:FANSLOWER",360,720,0,1,"CRAT:IN20:BC01:FANSLOWER") #! Record("CRAT:IN20:BC01:FANFASTER",360,620,0,1,"CRAT:IN20:BC01:FANFASTER") #! Record("CRAT:IN20:BC01:TEMP1",880,1757,0,0,"CRAT:IN20:BC01:TEMP1") #! Field("CRAT:IN20:BC01:TEMP1.FLNK",16777215,1,"CRAT:IN20:BC01:TEMP1.FLNK") #! Link("CRAT:IN20:BC01:TEMP1.FLNK","CRAT:IN20:BC01:TEMP2") #! Field("CRAT:IN20:BC01:TEMP1.SEVR",16777215,1,"CRAT:IN20:BC01:TEMP1.SEVR") #! Record("CRAT:IN20:BC01:CHU5_V",1100,1290,0,0,"CRAT:IN20:BC01:CHU5_V") #! Field("CRAT:IN20:BC01:CHU5_V.FLNK",16777215,1,"CRAT:IN20:BC01:CHU5_V.FLNK") #! Link("CRAT:IN20:BC01:CHU5_V.FLNK","CRAT:IN20:BC01:CHU5_I") #! Field("CRAT:IN20:BC01:CHU5_V.SEVR",16777215,1,"CRAT:IN20:BC01:CHU5_V.SEVR") #! Record("CRAT:IN20:BC01:UPDATE2",920,1580,0,1,"CRAT:IN20:BC01:UPDATE2") #! Field("CRAT:IN20:BC01:UPDATE2.FLNK",16777215,0,"CRAT:IN20:BC01:UPDATE2.FLNK") #! Link("CRAT:IN20:BC01:UPDATE2.FLNK","CRAT:IN20:BC01:TEMP1") #! Record("CRAT:IN20:BC01:POWERSEQ1",1420,2694,0,0,"CRAT:IN20:BC01:POWERSEQ1") #! Field("CRAT:IN20:BC01:POWERSEQ1.LNK1",16777215,1,"CRAT:IN20:BC01:POWERSEQ1.LNK1") #! Link("CRAT:IN20:BC01:POWERSEQ1.LNK1","CRAT:IN20:BC01:MAINPOWER.VAL") #! Field("CRAT:IN20:BC01:POWERSEQ1.SELL",16777215,0,"CRAT:IN20:BC01:POWERSEQ1.SELL") #! Link("CRAT:IN20:BC01:POWERSEQ1.SELL","CRAT:IN20:BC01:POWERCALC.VAL") #! Field("CRAT:IN20:BC01:POWERSEQ1.FLNK",16777215,0,"CRAT:IN20:BC01:POWERSEQ1.FLNK") #! Link("CRAT:IN20:BC01:POWERSEQ1.FLNK","CRAT:IN20:BC01:POWERMSGCALC") #! Record("CRAT:IN20:BC01:POWERCALC",960,2687,0,1,"CRAT:IN20:BC01:POWERCALC") #! Field("CRAT:IN20:BC01:POWERCALC.INPA",16777215,0,"CRAT:IN20:BC01:POWERCALC.INPA") #! Link("CRAT:IN20:BC01:POWERCALC.INPA","CRAT:IN20:BC01:POWERSTATE.VAL") #! Field("CRAT:IN20:BC01:POWERCALC.FLNK",16777215,1,"CRAT:IN20:BC01:POWERCALC.FLNK") #! Link("CRAT:IN20:BC01:POWERCALC.FLNK","CRAT:IN20:BC01:POWERSEQ1") #! Field("CRAT:IN20:BC01:POWERCALC.VAL",16777215,1,"CRAT:IN20:BC01:POWERCALC.VAL") #! Field("CRAT:IN20:BC01:POWERCALC.B",16777215,0,"CRAT:IN20:BC01:POWERCALC.B") #! Field("CRAT:IN20:BC01:POWERCALC.C",16777215,0,"CRAT:IN20:BC01:POWERCALC.C") #! Record("CRAT:IN20:BC01:POWEROFF",620,2747,0,1,"CRAT:IN20:BC01:POWEROFF") #! Field("CRAT:IN20:BC01:POWEROFF.OUT",16777215,1,"CRAT:IN20:BC01:POWEROFF.OUT") #! Link("CRAT:IN20:BC01:POWEROFF.OUT","CRAT:IN20:BC01:POWERCALC.B") #! Field("CRAT:IN20:BC01:POWEROFF.VAL",16777215,0,"CRAT:IN20:BC01:POWEROFF.VAL") #! Field("CRAT:IN20:BC01:POWEROFF.FLNK",16777215,1,"CRAT:IN20:BC01:POWEROFF.FLNK") #! Link("CRAT:IN20:BC01:POWEROFF.FLNK","CRAT:IN20:BC01:POWERMSGCALC") #! Record("CRAT:IN20:BC01:POWERON",620,2927,0,1,"CRAT:IN20:BC01:POWERON") #! Field("CRAT:IN20:BC01:POWERON.VAL",16777215,0,"CRAT:IN20:BC01:POWERON.VAL") #! Field("CRAT:IN20:BC01:POWERON.OUT",16777215,1,"CRAT:IN20:BC01:POWERON.OUT") #! Link("CRAT:IN20:BC01:POWERON.OUT","CRAT:IN20:BC01:POWERCALC.C") #! Field("CRAT:IN20:BC01:POWERON.FLNK",16777215,1,"CRAT:IN20:BC01:POWERON.FLNK") #! Link("CRAT:IN20:BC01:POWERON.FLNK","CRAT:IN20:BC01:POWERMSGCALC") #! Record("CRAT:IN20:BC01:HARDRESETSEQ",340,2724,0,1,"CRAT:IN20:BC01:HARDRESETSEQ") #! Field("CRAT:IN20:BC01:HARDRESETSEQ.LNK1",16777215,1,"CRAT:IN20:BC01:HARDRESETSEQ.LNK1") #! Link("CRAT:IN20:BC01:HARDRESETSEQ.LNK1","CRAT:IN20:BC01:POWEROFF.VAL") #! Field("CRAT:IN20:BC01:HARDRESETSEQ.LNK2",16777215,1,"CRAT:IN20:BC01:HARDRESETSEQ.LNK2") #! Link("CRAT:IN20:BC01:HARDRESETSEQ.LNK2","CRAT:IN20:BC01:POWERON.VAL") #! Field("CRAT:IN20:BC01:HARDRESETSEQ.PROC",16777215,0,"CRAT:IN20:BC01:HARDRESETSEQ.PROC") #! Field("CRAT:IN20:BC01:HARDRESETSEQ.LNK3",16777215,0,"CRAT:IN20:BC01:HARDRESETSEQ.LNK3") #! Link("CRAT:IN20:BC01:HARDRESETSEQ.LNK3","CRAT:IN20:BC01:HARDRESET.VAL") #! Record("CRAT:IN20:BC01:HARDRESET",20,2960,0,1,"CRAT:IN20:BC01:HARDRESET") #! Field("CRAT:IN20:BC01:HARDRESET.OUT",16777215,1,"CRAT:IN20:BC01:HARDRESET.OUT") #! Link("CRAT:IN20:BC01:HARDRESET.OUT","CRAT:IN20:BC01:HARDRESETSEQ.PROC") #! Field("CRAT:IN20:BC01:HARDRESET.VAL",16777215,1,"CRAT:IN20:BC01:HARDRESET.VAL") #! Field("CRAT:IN20:BC01:HARDRESET.FLNK",16777215,1,"CRAT:IN20:BC01:HARDRESET.FLNK") #! Link("CRAT:IN20:BC01:HARDRESET.FLNK","CRAT:IN20:BC01:POWERMSGCALC") #! Record("CRAT:IN20:BC01:POWERMSGCALC",1040,3160,0,1,"CRAT:IN20:BC01:POWERMSGCALC") #! Field("CRAT:IN20:BC01:POWERMSGCALC.INPA",16777215,0,"CRAT:IN20:BC01:POWERMSGCALC.INPA") #! Link("CRAT:IN20:BC01:POWERMSGCALC.INPA","CRAT:IN20:BC01:POWERCALC.B") #! Field("CRAT:IN20:BC01:POWERMSGCALC.INPB",16777215,0,"CRAT:IN20:BC01:POWERMSGCALC.INPB") #! Link("CRAT:IN20:BC01:POWERMSGCALC.INPB","CRAT:IN20:BC01:POWERCALC.C") #! Field("CRAT:IN20:BC01:POWERMSGCALC.INPC",16777215,0,"CRAT:IN20:BC01:POWERMSGCALC.INPC") #! Link("CRAT:IN20:BC01:POWERMSGCALC.INPC","CRAT:IN20:BC01:HARDRESET.VAL") #! Field("CRAT:IN20:BC01:POWERMSGCALC.VAL",16777215,0,"CRAT:IN20:BC01:POWERMSGCALC.VAL") #! Field("CRAT:IN20:BC01:POWERMSGCALC.FLNK",16777215,1,"CRAT:IN20:BC01:POWERMSGCALC.FLNK") #! Link("CRAT:IN20:BC01:POWERMSGCALC.FLNK","CRAT:IN20:BC01:POWERMSG") #! Record("CRAT:IN20:BC01:POWERMSG",1300,3137,0,1,"CRAT:IN20:BC01:POWERMSG") #! Field("CRAT:IN20:BC01:POWERMSG.INP",16777215,0,"CRAT:IN20:BC01:POWERMSG.INP") #! Link("CRAT:IN20:BC01:POWERMSG.INP","CRAT:IN20:BC01:POWERMSGCALC.VAL") #! Record("CRAT:IN20:BC01:TYPE",360,907,0,1,"CRAT:IN20:BC01:TYPE") #! Record("CRAT:IN20:BC01:2NAME",140,1080,0,1,"CRAT:IN20:BC01:2NAME") #! Record("CRAT:IN20:BC01:3NAME",140,1180,0,1,"CRAT:IN20:BC01:3NAME") #! Record("CRAT:IN20:BC01:4NAME",140,1280,0,1,"CRAT:IN20:BC01:4NAME") #! Record("CRAT:IN20:BC01:5NAME",140,1380,0,1,"CRAT:IN20:BC01:5NAME") #! Record("CRAT:IN20:BC01:6NAME",140,1480,0,1,"CRAT:IN20:BC01:6NAME") #! Record("CRAT:IN20:BC01:7NAME",140,1580,0,1,"CRAT:IN20:BC01:7NAME") #! Record("CRAT:IN20:BC01:1NAME",140,980,0,1,"CRAT:IN20:BC01:1NAME") #! Record("CRAT:IN20:BC01:FWVERSION",600,214,0,1,"CRAT:IN20:BC01:FWVERSION") #! Field("CRAT:IN20:BC01:FWVERSION.FLNK",16777215,1,"CRAT:IN20:BC01:FWVERSION.FLNK") #! Link("CRAT:IN20:BC01:FWVERSION.FLNK","CRAT:IN20:BC01:POWERSTATE") #! Field("CRAT:IN20:BC01:FWVERSION.SEVR",16777215,1,"CRAT:IN20:BC01:FWVERSION.SEVR") #! Record("CRAT:IN20:BC01:LOC",100,580,0,1,"CRAT:IN20:BC01:LOC") #! Record("CRAT:IN20:BC01:TEMPSUM",2640,1837,0,0,"CRAT:IN20:BC01:TEMPSUM") #! Field("CRAT:IN20:BC01:TEMPSUM.INPA",16777215,0,"CRAT:IN20:BC01:TEMPSUM.INPA") #! Link("CRAT:IN20:BC01:TEMPSUM.INPA","CRAT:IN20:BC01:TEMP1.SEVR") #! Field("CRAT:IN20:BC01:TEMPSUM.INPB",16777215,0,"CRAT:IN20:BC01:TEMPSUM.INPB") #! Link("CRAT:IN20:BC01:TEMPSUM.INPB","CRAT:IN20:BC01:TEMP2.SEVR") #! Field("CRAT:IN20:BC01:TEMPSUM.INPC",16777215,0,"CRAT:IN20:BC01:TEMPSUM.INPC") #! Link("CRAT:IN20:BC01:TEMPSUM.INPC","CRAT:IN20:BC01:TEMP3.SEVR") #! Field("CRAT:IN20:BC01:TEMPSUM.INPD",16777215,0,"CRAT:IN20:BC01:TEMPSUM.INPD") #! Link("CRAT:IN20:BC01:TEMPSUM.INPD","CRAT:IN20:BC01:TEMP4.SEVR") #! Field("CRAT:IN20:BC01:TEMPSUM.INPE",16777215,0,"CRAT:IN20:BC01:TEMPSUM.INPE") #! Link("CRAT:IN20:BC01:TEMPSUM.INPE","CRAT:IN20:BC01:TEMP5.SEVR") #! Field("CRAT:IN20:BC01:TEMPSUM.INPF",16777215,0,"CRAT:IN20:BC01:TEMPSUM.INPF") #! Link("CRAT:IN20:BC01:TEMPSUM.INPF","CRAT:IN20:BC01:TEMP6.SEVR") #! Field("CRAT:IN20:BC01:TEMPSUM.INPG",16777215,0,"CRAT:IN20:BC01:TEMPSUM.INPG") #! Link("CRAT:IN20:BC01:TEMPSUM.INPG","CRAT:IN20:BC01:TEMP7.SEVR") #! Field("CRAT:IN20:BC01:TEMPSUM.INPH",16777215,0,"CRAT:IN20:BC01:TEMPSUM.INPH") #! Link("CRAT:IN20:BC01:TEMPSUM.INPH","CRAT:IN20:BC01:TEMP8.SEVR") #! Field("CRAT:IN20:BC01:TEMPSUM.SEVR",16777215,0,"CRAT:IN20:BC01:TEMPSUM.SEVR") #! Record("CRAT:IN20:BC01:STATSUMY",2620,1430,0,1,"CRAT:IN20:BC01:STATSUMY") #! Field("CRAT:IN20:BC01:STATSUMY.INPA",16777215,0,"CRAT:IN20:BC01:STATSUMY.INPA") #! Link("CRAT:IN20:BC01:STATSUMY.INPA","CRAT:IN20:BC01:FWVERSION.SEVR") #! Field("CRAT:IN20:BC01:STATSUMY.INPB",16777215,0,"CRAT:IN20:BC01:STATSUMY.INPB") #! Link("CRAT:IN20:BC01:STATSUMY.INPB","CRAT:IN20:BC01:TEMPSUM.SEVR") #! Field("CRAT:IN20:BC01:STATSUMY.INPC",16777215,0,"CRAT:IN20:BC01:STATSUMY.INPC") #! Link("CRAT:IN20:BC01:STATSUMY.INPC","CRAT:IN20:BC01:CHU0_V.SEVR") #! Field("CRAT:IN20:BC01:STATSUMY.INPD",16777215,0,"CRAT:IN20:BC01:STATSUMY.INPD") #! Link("CRAT:IN20:BC01:STATSUMY.INPD","CRAT:IN20:BC01:CHU1_V.SEVR") #! Field("CRAT:IN20:BC01:STATSUMY.INPE",16777215,0,"CRAT:IN20:BC01:STATSUMY.INPE") #! Link("CRAT:IN20:BC01:STATSUMY.INPE","CRAT:IN20:BC01:CHU3_V.SEVR") #! Field("CRAT:IN20:BC01:STATSUMY.INPF",16777215,0,"CRAT:IN20:BC01:STATSUMY.INPF") #! Link("CRAT:IN20:BC01:STATSUMY.INPF","CRAT:IN20:BC01:CHU5_V.SEVR") #! Field("CRAT:IN20:BC01:STATSUMY.INPG",16777215,0,"CRAT:IN20:BC01:STATSUMY.INPG") #! Link("CRAT:IN20:BC01:STATSUMY.INPG","CRAT:IN20:BC01:FANSPEED.SEVR") #! Record("CRAT:IN20:BC01:TEMP5",820,2230,0,1,"CRAT:IN20:BC01:TEMP5") #! Field("CRAT:IN20:BC01:TEMP5.FLNK",16777215,1,"CRAT:IN20:BC01:TEMP5.FLNK") #! Link("CRAT:IN20:BC01:TEMP5.FLNK","CRAT:IN20:BC01:TEMP6") #! Field("CRAT:IN20:BC01:TEMP5.SEVR",16777215,1,"CRAT:IN20:BC01:TEMP5.SEVR") #! Record("CRAT:IN20:BC01:TEMP6",1100,2190,0,0,"CRAT:IN20:BC01:TEMP6") #! Field("CRAT:IN20:BC01:TEMP6.FLNK",16777215,1,"CRAT:IN20:BC01:TEMP6.FLNK") #! Link("CRAT:IN20:BC01:TEMP6.FLNK","CRAT:IN20:BC01:TEMP7") #! Field("CRAT:IN20:BC01:TEMP6.SEVR",16777215,1,"CRAT:IN20:BC01:TEMP6.SEVR") #! Record("CRAT:IN20:BC01:TEMP7",1360,2190,0,0,"CRAT:IN20:BC01:TEMP7") #! Field("CRAT:IN20:BC01:TEMP7.FLNK",16777215,1,"CRAT:IN20:BC01:TEMP7.FLNK") #! Link("CRAT:IN20:BC01:TEMP7.FLNK","CRAT:IN20:BC01:TEMP8") #! Field("CRAT:IN20:BC01:TEMP7.SEVR",16777215,1,"CRAT:IN20:BC01:TEMP7.SEVR") #! Record("CRAT:IN20:BC01:TEMP8",1640,2250,0,0,"CRAT:IN20:BC01:TEMP8") #! Field("CRAT:IN20:BC01:TEMP8.FLNK",16777215,0,"CRAT:IN20:BC01:TEMP8.FLNK") #! Link("CRAT:IN20:BC01:TEMP8.FLNK","CRAT:IN20:BC01:POWERCALC") #! Field("CRAT:IN20:BC01:TEMP8.SEVR",16777215,1,"CRAT:IN20:BC01:TEMP8.SEVR") #! TextBox(TB0,40,2400,480,2720,1,"Dialog",12,1,16777215,"The web interface for this crate only provides a \"toggle power\" button.\nThere is no way to send a command to turn the power on or turn the power off.\nThe purpose of all these PVs is to provide POWERON and POWEROFF \nbuttons rather than the inferior toggle button.\n\nProcessing the POWERON record when the crate is off will turn it on. \nProcessing the POWEROFF record when the crate is on will turn it off.\nProcessing the HARDRESET record will first force the POWEROFF record\nto process, then it will force the POWERON record to process.\n\nThe POWERON and POWEROFF steps take about 10 seconds each: First the IOC\nmust wait to get new on/off status (which takes five seconds) before deciding\nwhether or not to toggle the crate power. Then it sends the toggle command\nand it takes another 5 seconds to see the change in on/off status.\n\nPOWERMSG contains a string that describes what is currently happening.\nIt is normally empty, but contains text if the power is being turned on, off, or \nreset.",null) #! Generated by VisualDCT v2.5 #! DBDSTART #! DBDEND record(bi, "CRAT:IN20:BP01:POWERSTATE") { field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ZNAM, "OFF") field(ONAM, "ON") field(SDIS, "CRAT:IN20:BP01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bi, "CRAT:IN20:BP01:FANTRAY") { field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ONAM, "OK") field(SDIS, "CRAT:IN20:BP01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:BP01:FANSPEED") { field(EGU, "RPM") field(LOLO, "1150") field(HHSV, "NO_ALARM") field(LLSV, "MAJOR") field(HSV, "NO_ALARM") field(LSV, "NO_ALARM") field(SDIS, "CRAT:IN20:BP01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:BP01:CHU0_I") { field(PREC, "1") field(EGU, "A") field(SDIS, "CRAT:IN20:BP01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(stringin, "CRAT:IN20:BP01:CHU0_NAME") { field(SDIS, "CRAT:IN20:BP01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bi, "CRAT:IN20:BP01:CHU0_STATUS") { field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ONAM, "OK") field(SDIS, "CRAT:IN20:BP01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:BP01:CHU0_V") { field(PREC, "2") field(EGU, "V") field(HOPR, "15") field(LOPR, "0") field(HIHI, "5.25") field(LOLO, "4.875") field(HIGH, "5.2") field(LOW, "4.9") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:BP01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(stringin, "CRAT:IN20:BP01:CHU1_NAME") { field(SDIS, "CRAT:IN20:BP01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:BP01:CHU1_V") { field(PREC, "1") field(EGU, "V") field(HOPR, "15") field(LOPR, "0") field(HIHI, "12.6") field(LOLO, "11.7") field(HIGH, "12.48") field(LOW, "11.76") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:BP01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:BP01:CHU1_I") { field(PREC, "1") field(EGU, "A") field(SDIS, "CRAT:IN20:BP01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bi, "CRAT:IN20:BP01:CHU1_STATUS") { field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ONAM, "OK") field(SDIS, "CRAT:IN20:BP01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(stringin, "CRAT:IN20:BP01:CHU3_NAME") { field(SDIS, "CRAT:IN20:BP01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:BP01:CHU3_V") { field(PREC, "2") field(EGU, "V") field(HOPR, "15") field(LOPR, "0") field(HIHI, "3.465") field(LOLO, "3.2175") field(HIGH, "3.432") field(LOW, "3.234") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:BP01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:BP01:CHU3_I") { field(PREC, "1") field(EGU, "A") field(SDIS, "CRAT:IN20:BP01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bi, "CRAT:IN20:BP01:CHU3_STATUS") { field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ONAM, "OK") field(SDIS, "CRAT:IN20:BP01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(stringin, "CRAT:IN20:BP01:CHU5_NAME") { field(SDIS, "CRAT:IN20:BP01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:BP01:CHU5_I") { field(PREC, "1") field(EGU, "A") field(SDIS, "CRAT:IN20:BP01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bi, "CRAT:IN20:BP01:CHU5_STATUS") { field(FLNK, "CRAT:IN20:BP01:UPDATE2") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ONAM, "OK") field(SDIS, "CRAT:IN20:BP01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(calc, "CRAT:IN20:BP01:TEMP2") { field(CALC, "A>0?(A-0)/1:A") field(EGU, "DegF") field(PREC, "0") field(HOPR, "120") field(LOPR, "20") field(HIHI, "131") field(LOLO, "-1") field(HIGH, "113") field(LOW, "-1") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:BP01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(calc, "CRAT:IN20:BP01:TEMP3") { field(CALC, "A>0?(A-0)/1:A") field(EGU, "DegF") field(PREC, "0") field(HOPR, "120") field(LOPR, "20") field(HIHI, "131") field(LOLO, "-1") field(HIGH, "113") field(LOW, "-1") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:BP01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(calc, "CRAT:IN20:BP01:TEMP4") { field(CALC, "A>0?(A-0)/1:A") field(EGU, "DegF") field(PREC, "0") field(HOPR, "120") field(LOPR, "20") field(HIHI, "131") field(LOLO, "-1") field(HIGH, "113") field(LOW, "-1") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:BP01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bo, "CRAT:IN20:BP01:MAINPOWER") { field(DTYP, "stream") field(OUT, "@crat_wiener_7slot.proto.db setMainPower crat-in20-bp01") } record(bo, "CRAT:IN20:BP01:VMERESET") { field(DTYP, "stream") field(OUT, "@crat_wiener_7slot.proto.db setVmeSysReset crat-in20-bp01") } record(bo, "CRAT:IN20:BP01:FANSLOWER") { field(DTYP, "stream") field(OUT, "@crat_wiener_7slot.proto.db setFanSlower crat-in20-bp01") } record(bo, "CRAT:IN20:BP01:FANFASTER") { field(DTYP, "stream") field(OUT, "@crat_wiener_7slot.proto.db setFanFaster crat-in20-bp01") } record(calc, "CRAT:IN20:BP01:TEMP1") { field(CALC, "A>0?(A-0)/1:A") field(SCAN, "Passive") field(EGU, "DegF") field(PREC, "0") field(HOPR, "120") field(LOPR, "20") field(HIHI, "131") field(LOLO, "-1") field(HIGH, "113") field(LOW, "-1") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:BP01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(ai, "CRAT:IN20:BP01:CHU5_V") { field(PREC, "1") field(EGU, "V") field(HOPR, "15") field(LOPR, "0") field(HIHI, "12.6") field(LOLO, "11.7") field(HIGH, "12.48") field(LOW, "11.76") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:BP01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(bi, "CRAT:IN20:BP01:UPDATE2") { field(SCAN, "Passive") field(DTYP, "stream") field(INP, "@crat_wiener_7slot.proto.db getTemp(CRAT:IN20:BP01) crat-in20-bp01") } record(seq, "CRAT:IN20:BP01:POWERSEQ1") { field(SELM, "Specified") field(SELL, "CRAT:IN20:BP01:POWERCALC") field(LNK1, "CRAT:IN20:BP01:MAINPOWER PP") field(FLNK, "CRAT:IN20:BP01:POWERMSGCALC") } record(calc, "CRAT:IN20:BP01:POWERCALC") { field(FLNK, "CRAT:IN20:BP01:POWERSEQ1") field(CALC, "A=1&&B=1&&C=0?1:A=0&&B=0&&C=1?1:0") field(INPA, "CRAT:IN20:BP01:POWERSTATE") } record(bo, "CRAT:IN20:BP01:POWEROFF") { field(HIGH, "9") field(OUT, "CRAT:IN20:BP01:POWERCALC.B") field(FLNK, "CRAT:IN20:BP01:POWERMSGCALC") } record(bo, "CRAT:IN20:BP01:POWERON") { field(OUT, "CRAT:IN20:BP01:POWERCALC.C") field(HIGH, "9") field(FLNK, "CRAT:IN20:BP01:POWERMSGCALC") } record(seq, "CRAT:IN20:BP01:HARDRESETSEQ") { field(SELM, "All") field(LNK1, "CRAT:IN20:BP01:POWEROFF PP") field(DOL1, "1") field(DLY2, "10") field(DOL2, "1") field(LNK2, "CRAT:IN20:BP01:POWERON PP") field(DLY3, "10") field(DOL3, "0") field(LNK3, "CRAT:IN20:BP01:HARDRESET PP") } record(bo, "CRAT:IN20:BP01:HARDRESET") { field(OUT, "CRAT:IN20:BP01:HARDRESETSEQ.PROC PP") field(FLNK, "CRAT:IN20:BP01:POWERMSGCALC") } record(calc, "CRAT:IN20:BP01:POWERMSGCALC") { field(FLNK, "CRAT:IN20:BP01:POWERMSG") field(CALC, "C?3:A=1&&B=0?0:A=0&&B=1?1:A=1&&B=1?2:4") field(INPA, "CRAT:IN20:BP01:POWERCALC.B") field(INPB, "CRAT:IN20:BP01:POWERCALC.C") field(INPC, "CRAT:IN20:BP01:HARDRESET") } record(mbbi, "CRAT:IN20:BP01:POWERMSG") { field(INP, "CRAT:IN20:BP01:POWERMSGCALC.VAL") field(ZRST, "TURNING_OFF") field(ONST, "TURNING_ON") field(TWST, "ERROR") field(THST, "HARD_RESETTING") field(FRST, " ") field(ZRSV, "MINOR") field(ONSV, "MINOR") field(TWSV, "MAJOR") field(THSV, "MINOR") field(FRSV, "NO_ALARM") } record(ai, "CRAT:IN20:BP01:TYPE") { field(DESC, "Wiener 7 Slot VME Crate") field(PINI, "YES") field(VAL, "1") } record(stringin, "CRAT:IN20:BP01:2NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:BP01:3NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:BP01:4NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:BP01:5NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:BP01:6NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:BP01:7NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:BP01:1NAME") { field(PINI, "YES") field(VAL, "IOC:IN20:BP01") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:BP01:FWVERSION") { field(SCAN, "5 second") field(DTYP, "stream") field(INP, "@crat_wiener_7slot.proto.db getStatus(CRAT:IN20:BP01) crat-in20-bp01") } record(stringin, "CRAT:IN20:BP01:LOC") { field(PINI, "YES") field(VAL, "RF Hut LKG-2109") info(autosaveFields,"VAL") } record(calc, "CRAT:IN20:BP01:TEMPSUM") { field(DESC, "Temperature alarm summary") field(CALC, "A+B+C+D+E+F+G+H") field(INPA, "CRAT:IN20:BP01:TEMP1.SEVR NPP MS") field(INPB, "CRAT:IN20:BP01:TEMP2.SEVR NPP MS") field(INPC, "CRAT:IN20:BP01:TEMP3.SEVR NPP MS") field(INPD, "CRAT:IN20:BP01:TEMP4.SEVR NPP MS") field(INPE, "CRAT:IN20:BP01:TEMP5.SEVR NPP MS") field(INPF, "CRAT:IN20:BP01:TEMP6.SEVR NPP MS") field(INPG, "CRAT:IN20:BP01:TEMP7.SEVR NPP MS") field(INPH, "CRAT:IN20:BP01:TEMP8.SEVR NPP MS") field(SCAN, "1 second") } record(calc, "CRAT:IN20:BP01:STATSUMY") { field(DESC, "Alarm summary for crate") field(INPA, "CRAT:IN20:BP01:FWVERSION.SEVR NPP MS") field(INPB, "CRAT:IN20:BP01:TEMPSUM.SEVR NPP MS") field(INPC, "CRAT:IN20:BP01:CHU0_V.SEVR NPP MS") field(INPD, "CRAT:IN20:BP01:CHU1_V.SEVR NPP MS") field(INPE, "CRAT:IN20:BP01:CHU3_V.SEVR NPP MS") field(INPF, "CRAT:IN20:BP01:CHU5_V.SEVR NPP MS") field(INPG, "CRAT:IN20:BP01:FANSPEED.SEVR NPP MS") field(INPH, "CRAT:IN20:BP01:FANTRAY.SEVR NPP MS") field(SCAN, "1 second") field(CALC, "A+B+C+D+E+F+G+H") } record(calc, "CRAT:IN20:BP01:TEMP5") { field(CALC, "A>0?(A-0)/1:A") field(EGU, "DegF") field(PREC, "0") field(HOPR, "120") field(LOPR, "20") field(HIHI, "131") field(LOLO, "-1") field(HIGH, "113") field(LOW, "-1") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:BP01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(calc, "CRAT:IN20:BP01:TEMP6") { field(CALC, "A>0?(A-0)/1:A") field(EGU, "DegF") field(PREC, "0") field(HOPR, "120") field(LOPR, "20") field(HIHI, "131") field(LOLO, "-1") field(HIGH, "113") field(LOW, "-1") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:BP01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(calc, "CRAT:IN20:BP01:TEMP7") { field(CALC, "A>0?(A-0)/1:A") field(EGU, "DegF") field(PREC, "0") field(HOPR, "120") field(LOPR, "20") field(HIHI, "131") field(LOLO, "-1") field(HIGH, "113") field(LOW, "-1") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:BP01:FWVERSION.SEVR CP MS") field(DISV, "20") } record(calc, "CRAT:IN20:BP01:TEMP8") { field(CALC, "A>0?(A-0)/1:A") field(FLNK, "CRAT:IN20:BP01:POWERCALC") field(EGU, "DegF") field(PREC, "0") field(HOPR, "120") field(LOPR, "20") field(HIHI, "131") field(LOLO, "-1") field(HIGH, "113") field(LOW, "-1") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(SDIS, "CRAT:IN20:BP01:FWVERSION.SEVR CP MS") field(DISV, "20") } #! Further lines contain data used by VisualDCT #! View(0,235,0.3) #! Record("CRAT:IN20:BP01:POWERSTATE",860,180,0,0,"CRAT:IN20:BP01:POWERSTATE") #! Field("CRAT:IN20:BP01:POWERSTATE.FLNK",16777215,1,"CRAT:IN20:BP01:POWERSTATE.FLNK") #! Link("CRAT:IN20:BP01:POWERSTATE.FLNK","CRAT:IN20:BP01:FANTRAY") #! Field("CRAT:IN20:BP01:POWERSTATE.VAL",16777215,0,"CRAT:IN20:BP01:POWERSTATE.VAL") #! Record("CRAT:IN20:BP01:FANTRAY",1360,194,0,0,"CRAT:IN20:BP01:FANTRAY") #! Field("CRAT:IN20:BP01:FANTRAY.FLNK",16777215,1,"CRAT:IN20:BP01:FANTRAY.FLNK") #! Link("CRAT:IN20:BP01:FANTRAY.FLNK","CRAT:IN20:BP01:FANSPEED") #! Record("CRAT:IN20:BP01:FANSPEED",1620,174,0,0,"CRAT:IN20:BP01:FANSPEED") #! Field("CRAT:IN20:BP01:FANSPEED.FLNK",16777215,0,"CRAT:IN20:BP01:FANSPEED.FLNK") #! Link("CRAT:IN20:BP01:FANSPEED.FLNK","CRAT:IN20:BP01:CHU0_NAME") #! Field("CRAT:IN20:BP01:FANSPEED.SEVR",16777215,1,"CRAT:IN20:BP01:FANSPEED.SEVR") #! Record("CRAT:IN20:BP01:CHU0_I",1360,507,0,0,"CRAT:IN20:BP01:CHU0_I") #! Field("CRAT:IN20:BP01:CHU0_I.FLNK",16777215,1,"CRAT:IN20:BP01:CHU0_I.FLNK") #! Link("CRAT:IN20:BP01:CHU0_I.FLNK","CRAT:IN20:BP01:CHU0_STATUS") #! Record("CRAT:IN20:BP01:CHU0_NAME",840,534,0,1,"CRAT:IN20:BP01:CHU0_NAME") #! Field("CRAT:IN20:BP01:CHU0_NAME.FLNK",16777215,1,"CRAT:IN20:BP01:CHU0_NAME.FLNK") #! Link("CRAT:IN20:BP01:CHU0_NAME.FLNK","CRAT:IN20:BP01:CHU0_V") #! Record("CRAT:IN20:BP01:CHU0_STATUS",1620,514,0,0,"CRAT:IN20:BP01:CHU0_STATUS") #! Field("CRAT:IN20:BP01:CHU0_STATUS.FLNK",16777215,0,"CRAT:IN20:BP01:CHU0_STATUS.FLNK") #! Link("CRAT:IN20:BP01:CHU0_STATUS.FLNK","CRAT:IN20:BP01:CHU1_NAME") #! Record("CRAT:IN20:BP01:CHU0_V",1100,370,0,0,"CRAT:IN20:BP01:CHU0_V") #! Field("CRAT:IN20:BP01:CHU0_V.FLNK",16777215,1,"CRAT:IN20:BP01:CHU0_V.FLNK") #! Link("CRAT:IN20:BP01:CHU0_V.FLNK","CRAT:IN20:BP01:CHU0_I") #! Field("CRAT:IN20:BP01:CHU0_V.SEVR",16777215,1,"CRAT:IN20:BP01:CHU0_V.SEVR") #! Record("CRAT:IN20:BP01:CHU1_NAME",840,834,0,1,"CRAT:IN20:BP01:CHU1_NAME") #! Field("CRAT:IN20:BP01:CHU1_NAME.FLNK",16777215,1,"CRAT:IN20:BP01:CHU1_NAME.FLNK") #! Link("CRAT:IN20:BP01:CHU1_NAME.FLNK","CRAT:IN20:BP01:CHU1_V") #! Record("CRAT:IN20:BP01:CHU1_V",1100,670,0,0,"CRAT:IN20:BP01:CHU1_V") #! Field("CRAT:IN20:BP01:CHU1_V.FLNK",16777215,1,"CRAT:IN20:BP01:CHU1_V.FLNK") #! Link("CRAT:IN20:BP01:CHU1_V.FLNK","CRAT:IN20:BP01:CHU1_I") #! Field("CRAT:IN20:BP01:CHU1_V.SEVR",16777215,1,"CRAT:IN20:BP01:CHU1_V.SEVR") #! Record("CRAT:IN20:BP01:CHU1_I",1360,807,0,0,"CRAT:IN20:BP01:CHU1_I") #! Field("CRAT:IN20:BP01:CHU1_I.FLNK",16777215,1,"CRAT:IN20:BP01:CHU1_I.FLNK") #! Link("CRAT:IN20:BP01:CHU1_I.FLNK","CRAT:IN20:BP01:CHU1_STATUS") #! Record("CRAT:IN20:BP01:CHU1_STATUS",1620,814,0,0,"CRAT:IN20:BP01:CHU1_STATUS") #! Field("CRAT:IN20:BP01:CHU1_STATUS.FLNK",16777215,0,"CRAT:IN20:BP01:CHU1_STATUS.FLNK") #! Link("CRAT:IN20:BP01:CHU1_STATUS.FLNK","CRAT:IN20:BP01:CHU3_NAME") #! Record("CRAT:IN20:BP01:CHU3_NAME",840,1134,0,1,"CRAT:IN20:BP01:CHU3_NAME") #! Field("CRAT:IN20:BP01:CHU3_NAME.FLNK",16777215,1,"CRAT:IN20:BP01:CHU3_NAME.FLNK") #! Link("CRAT:IN20:BP01:CHU3_NAME.FLNK","CRAT:IN20:BP01:CHU3_V") #! Record("CRAT:IN20:BP01:CHU3_V",1100,970,0,0,"CRAT:IN20:BP01:CHU3_V") #! Field("CRAT:IN20:BP01:CHU3_V.FLNK",16777215,1,"CRAT:IN20:BP01:CHU3_V.FLNK") #! Link("CRAT:IN20:BP01:CHU3_V.FLNK","CRAT:IN20:BP01:CHU3_I") #! Field("CRAT:IN20:BP01:CHU3_V.SEVR",16777215,1,"CRAT:IN20:BP01:CHU3_V.SEVR") #! Record("CRAT:IN20:BP01:CHU3_I",1360,1107,0,0,"CRAT:IN20:BP01:CHU3_I") #! Field("CRAT:IN20:BP01:CHU3_I.FLNK",16777215,1,"CRAT:IN20:BP01:CHU3_I.FLNK") #! Link("CRAT:IN20:BP01:CHU3_I.FLNK","CRAT:IN20:BP01:CHU3_STATUS") #! Record("CRAT:IN20:BP01:CHU3_STATUS",1620,1114,0,0,"CRAT:IN20:BP01:CHU3_STATUS") #! Field("CRAT:IN20:BP01:CHU3_STATUS.FLNK",16777215,0,"CRAT:IN20:BP01:CHU3_STATUS.FLNK") #! Link("CRAT:IN20:BP01:CHU3_STATUS.FLNK","CRAT:IN20:BP01:CHU5_NAME") #! Record("CRAT:IN20:BP01:CHU5_NAME",840,1454,0,1,"CRAT:IN20:BP01:CHU5_NAME") #! Field("CRAT:IN20:BP01:CHU5_NAME.FLNK",16777215,1,"CRAT:IN20:BP01:CHU5_NAME.FLNK") #! Link("CRAT:IN20:BP01:CHU5_NAME.FLNK","CRAT:IN20:BP01:CHU5_V") #! Record("CRAT:IN20:BP01:CHU5_I",1360,1427,0,0,"CRAT:IN20:BP01:CHU5_I") #! Field("CRAT:IN20:BP01:CHU5_I.FLNK",16777215,1,"CRAT:IN20:BP01:CHU5_I.FLNK") #! Link("CRAT:IN20:BP01:CHU5_I.FLNK","CRAT:IN20:BP01:CHU5_STATUS") #! Record("CRAT:IN20:BP01:CHU5_STATUS",1620,1454,0,0,"CRAT:IN20:BP01:CHU5_STATUS") #! Field("CRAT:IN20:BP01:CHU5_STATUS.FLNK",16777215,0,"CRAT:IN20:BP01:CHU5_STATUS.FLNK") #! Link("CRAT:IN20:BP01:CHU5_STATUS.FLNK","CRAT:IN20:BP01:UPDATE2") #! Record("CRAT:IN20:BP01:TEMP2",1120,1770,0,1,"CRAT:IN20:BP01:TEMP2") #! Field("CRAT:IN20:BP01:TEMP2.FLNK",16777215,1,"CRAT:IN20:BP01:TEMP2.FLNK") #! Link("CRAT:IN20:BP01:TEMP2.FLNK","CRAT:IN20:BP01:TEMP3") #! Field("CRAT:IN20:BP01:TEMP2.SEVR",16777215,1,"CRAT:IN20:BP01:TEMP2.SEVR") #! Record("CRAT:IN20:BP01:TEMP3",1380,1770,0,0,"CRAT:IN20:BP01:TEMP3") #! Field("CRAT:IN20:BP01:TEMP3.FLNK",16777215,1,"CRAT:IN20:BP01:TEMP3.FLNK") #! Link("CRAT:IN20:BP01:TEMP3.FLNK","CRAT:IN20:BP01:TEMP4") #! Field("CRAT:IN20:BP01:TEMP3.SEVR",16777215,1,"CRAT:IN20:BP01:TEMP3.SEVR") #! Record("CRAT:IN20:BP01:TEMP4",1640,1790,0,0,"CRAT:IN20:BP01:TEMP4") #! Field("CRAT:IN20:BP01:TEMP4.FLNK",16777215,0,"CRAT:IN20:BP01:TEMP4.FLNK") #! Link("CRAT:IN20:BP01:TEMP4.FLNK","CRAT:IN20:BP01:TEMP5") #! Field("CRAT:IN20:BP01:TEMP4.SEVR",16777215,1,"CRAT:IN20:BP01:TEMP4.SEVR") #! Record("CRAT:IN20:BP01:MAINPOWER",1740,2860,0,1,"CRAT:IN20:BP01:MAINPOWER") #! Field("CRAT:IN20:BP01:MAINPOWER.VAL",16777215,0,"CRAT:IN20:BP01:MAINPOWER.VAL") #! Record("CRAT:IN20:BP01:VMERESET",360,520,0,1,"CRAT:IN20:BP01:VMERESET") #! Record("CRAT:IN20:BP01:FANSLOWER",360,720,0,1,"CRAT:IN20:BP01:FANSLOWER") #! Record("CRAT:IN20:BP01:FANFASTER",360,620,0,1,"CRAT:IN20:BP01:FANFASTER") #! Record("CRAT:IN20:BP01:TEMP1",880,1757,0,0,"CRAT:IN20:BP01:TEMP1") #! Field("CRAT:IN20:BP01:TEMP1.FLNK",16777215,1,"CRAT:IN20:BP01:TEMP1.FLNK") #! Link("CRAT:IN20:BP01:TEMP1.FLNK","CRAT:IN20:BP01:TEMP2") #! Field("CRAT:IN20:BP01:TEMP1.SEVR",16777215,1,"CRAT:IN20:BP01:TEMP1.SEVR") #! Record("CRAT:IN20:BP01:CHU5_V",1100,1290,0,0,"CRAT:IN20:BP01:CHU5_V") #! Field("CRAT:IN20:BP01:CHU5_V.FLNK",16777215,1,"CRAT:IN20:BP01:CHU5_V.FLNK") #! Link("CRAT:IN20:BP01:CHU5_V.FLNK","CRAT:IN20:BP01:CHU5_I") #! Field("CRAT:IN20:BP01:CHU5_V.SEVR",16777215,1,"CRAT:IN20:BP01:CHU5_V.SEVR") #! Record("CRAT:IN20:BP01:UPDATE2",920,1580,0,1,"CRAT:IN20:BP01:UPDATE2") #! Field("CRAT:IN20:BP01:UPDATE2.FLNK",16777215,0,"CRAT:IN20:BP01:UPDATE2.FLNK") #! Link("CRAT:IN20:BP01:UPDATE2.FLNK","CRAT:IN20:BP01:TEMP1") #! Record("CRAT:IN20:BP01:POWERSEQ1",1420,2694,0,0,"CRAT:IN20:BP01:POWERSEQ1") #! Field("CRAT:IN20:BP01:POWERSEQ1.LNK1",16777215,1,"CRAT:IN20:BP01:POWERSEQ1.LNK1") #! Link("CRAT:IN20:BP01:POWERSEQ1.LNK1","CRAT:IN20:BP01:MAINPOWER.VAL") #! Field("CRAT:IN20:BP01:POWERSEQ1.SELL",16777215,0,"CRAT:IN20:BP01:POWERSEQ1.SELL") #! Link("CRAT:IN20:BP01:POWERSEQ1.SELL","CRAT:IN20:BP01:POWERCALC.VAL") #! Field("CRAT:IN20:BP01:POWERSEQ1.FLNK",16777215,0,"CRAT:IN20:BP01:POWERSEQ1.FLNK") #! Link("CRAT:IN20:BP01:POWERSEQ1.FLNK","CRAT:IN20:BP01:POWERMSGCALC") #! Record("CRAT:IN20:BP01:POWERCALC",960,2687,0,1,"CRAT:IN20:BP01:POWERCALC") #! Field("CRAT:IN20:BP01:POWERCALC.INPA",16777215,0,"CRAT:IN20:BP01:POWERCALC.INPA") #! Link("CRAT:IN20:BP01:POWERCALC.INPA","CRAT:IN20:BP01:POWERSTATE.VAL") #! Field("CRAT:IN20:BP01:POWERCALC.FLNK",16777215,1,"CRAT:IN20:BP01:POWERCALC.FLNK") #! Link("CRAT:IN20:BP01:POWERCALC.FLNK","CRAT:IN20:BP01:POWERSEQ1") #! Field("CRAT:IN20:BP01:POWERCALC.VAL",16777215,1,"CRAT:IN20:BP01:POWERCALC.VAL") #! Field("CRAT:IN20:BP01:POWERCALC.B",16777215,0,"CRAT:IN20:BP01:POWERCALC.B") #! Field("CRAT:IN20:BP01:POWERCALC.C",16777215,0,"CRAT:IN20:BP01:POWERCALC.C") #! Record("CRAT:IN20:BP01:POWEROFF",620,2747,0,1,"CRAT:IN20:BP01:POWEROFF") #! Field("CRAT:IN20:BP01:POWEROFF.OUT",16777215,1,"CRAT:IN20:BP01:POWEROFF.OUT") #! Link("CRAT:IN20:BP01:POWEROFF.OUT","CRAT:IN20:BP01:POWERCALC.B") #! Field("CRAT:IN20:BP01:POWEROFF.VAL",16777215,0,"CRAT:IN20:BP01:POWEROFF.VAL") #! Field("CRAT:IN20:BP01:POWEROFF.FLNK",16777215,1,"CRAT:IN20:BP01:POWEROFF.FLNK") #! Link("CRAT:IN20:BP01:POWEROFF.FLNK","CRAT:IN20:BP01:POWERMSGCALC") #! Record("CRAT:IN20:BP01:POWERON",620,2927,0,1,"CRAT:IN20:BP01:POWERON") #! Field("CRAT:IN20:BP01:POWERON.VAL",16777215,0,"CRAT:IN20:BP01:POWERON.VAL") #! Field("CRAT:IN20:BP01:POWERON.OUT",16777215,1,"CRAT:IN20:BP01:POWERON.OUT") #! Link("CRAT:IN20:BP01:POWERON.OUT","CRAT:IN20:BP01:POWERCALC.C") #! Field("CRAT:IN20:BP01:POWERON.FLNK",16777215,1,"CRAT:IN20:BP01:POWERON.FLNK") #! Link("CRAT:IN20:BP01:POWERON.FLNK","CRAT:IN20:BP01:POWERMSGCALC") #! Record("CRAT:IN20:BP01:HARDRESETSEQ",340,2724,0,1,"CRAT:IN20:BP01:HARDRESETSEQ") #! Field("CRAT:IN20:BP01:HARDRESETSEQ.LNK1",16777215,1,"CRAT:IN20:BP01:HARDRESETSEQ.LNK1") #! Link("CRAT:IN20:BP01:HARDRESETSEQ.LNK1","CRAT:IN20:BP01:POWEROFF.VAL") #! Field("CRAT:IN20:BP01:HARDRESETSEQ.LNK2",16777215,1,"CRAT:IN20:BP01:HARDRESETSEQ.LNK2") #! Link("CRAT:IN20:BP01:HARDRESETSEQ.LNK2","CRAT:IN20:BP01:POWERON.VAL") #! Field("CRAT:IN20:BP01:HARDRESETSEQ.PROC",16777215,0,"CRAT:IN20:BP01:HARDRESETSEQ.PROC") #! Field("CRAT:IN20:BP01:HARDRESETSEQ.LNK3",16777215,0,"CRAT:IN20:BP01:HARDRESETSEQ.LNK3") #! Link("CRAT:IN20:BP01:HARDRESETSEQ.LNK3","CRAT:IN20:BP01:HARDRESET.VAL") #! Record("CRAT:IN20:BP01:HARDRESET",20,2960,0,1,"CRAT:IN20:BP01:HARDRESET") #! Field("CRAT:IN20:BP01:HARDRESET.OUT",16777215,1,"CRAT:IN20:BP01:HARDRESET.OUT") #! Link("CRAT:IN20:BP01:HARDRESET.OUT","CRAT:IN20:BP01:HARDRESETSEQ.PROC") #! Field("CRAT:IN20:BP01:HARDRESET.VAL",16777215,1,"CRAT:IN20:BP01:HARDRESET.VAL") #! Field("CRAT:IN20:BP01:HARDRESET.FLNK",16777215,1,"CRAT:IN20:BP01:HARDRESET.FLNK") #! Link("CRAT:IN20:BP01:HARDRESET.FLNK","CRAT:IN20:BP01:POWERMSGCALC") #! Record("CRAT:IN20:BP01:POWERMSGCALC",1040,3160,0,1,"CRAT:IN20:BP01:POWERMSGCALC") #! Field("CRAT:IN20:BP01:POWERMSGCALC.INPA",16777215,0,"CRAT:IN20:BP01:POWERMSGCALC.INPA") #! Link("CRAT:IN20:BP01:POWERMSGCALC.INPA","CRAT:IN20:BP01:POWERCALC.B") #! Field("CRAT:IN20:BP01:POWERMSGCALC.INPB",16777215,0,"CRAT:IN20:BP01:POWERMSGCALC.INPB") #! Link("CRAT:IN20:BP01:POWERMSGCALC.INPB","CRAT:IN20:BP01:POWERCALC.C") #! Field("CRAT:IN20:BP01:POWERMSGCALC.INPC",16777215,0,"CRAT:IN20:BP01:POWERMSGCALC.INPC") #! Link("CRAT:IN20:BP01:POWERMSGCALC.INPC","CRAT:IN20:BP01:HARDRESET.VAL") #! Field("CRAT:IN20:BP01:POWERMSGCALC.VAL",16777215,0,"CRAT:IN20:BP01:POWERMSGCALC.VAL") #! Field("CRAT:IN20:BP01:POWERMSGCALC.FLNK",16777215,1,"CRAT:IN20:BP01:POWERMSGCALC.FLNK") #! Link("CRAT:IN20:BP01:POWERMSGCALC.FLNK","CRAT:IN20:BP01:POWERMSG") #! Record("CRAT:IN20:BP01:POWERMSG",1300,3137,0,1,"CRAT:IN20:BP01:POWERMSG") #! Field("CRAT:IN20:BP01:POWERMSG.INP",16777215,0,"CRAT:IN20:BP01:POWERMSG.INP") #! Link("CRAT:IN20:BP01:POWERMSG.INP","CRAT:IN20:BP01:POWERMSGCALC.VAL") #! Record("CRAT:IN20:BP01:TYPE",360,907,0,1,"CRAT:IN20:BP01:TYPE") #! Record("CRAT:IN20:BP01:2NAME",140,1080,0,1,"CRAT:IN20:BP01:2NAME") #! Record("CRAT:IN20:BP01:3NAME",140,1180,0,1,"CRAT:IN20:BP01:3NAME") #! Record("CRAT:IN20:BP01:4NAME",140,1280,0,1,"CRAT:IN20:BP01:4NAME") #! Record("CRAT:IN20:BP01:5NAME",140,1380,0,1,"CRAT:IN20:BP01:5NAME") #! Record("CRAT:IN20:BP01:6NAME",140,1480,0,1,"CRAT:IN20:BP01:6NAME") #! Record("CRAT:IN20:BP01:7NAME",140,1580,0,1,"CRAT:IN20:BP01:7NAME") #! Record("CRAT:IN20:BP01:1NAME",140,980,0,1,"CRAT:IN20:BP01:1NAME") #! Record("CRAT:IN20:BP01:FWVERSION",600,214,0,1,"CRAT:IN20:BP01:FWVERSION") #! Field("CRAT:IN20:BP01:FWVERSION.FLNK",16777215,1,"CRAT:IN20:BP01:FWVERSION.FLNK") #! Link("CRAT:IN20:BP01:FWVERSION.FLNK","CRAT:IN20:BP01:POWERSTATE") #! Field("CRAT:IN20:BP01:FWVERSION.SEVR",16777215,1,"CRAT:IN20:BP01:FWVERSION.SEVR") #! Record("CRAT:IN20:BP01:LOC",100,580,0,1,"CRAT:IN20:BP01:LOC") #! Record("CRAT:IN20:BP01:TEMPSUM",2640,1837,0,0,"CRAT:IN20:BP01:TEMPSUM") #! Field("CRAT:IN20:BP01:TEMPSUM.INPA",16777215,0,"CRAT:IN20:BP01:TEMPSUM.INPA") #! Link("CRAT:IN20:BP01:TEMPSUM.INPA","CRAT:IN20:BP01:TEMP1.SEVR") #! Field("CRAT:IN20:BP01:TEMPSUM.INPB",16777215,0,"CRAT:IN20:BP01:TEMPSUM.INPB") #! Link("CRAT:IN20:BP01:TEMPSUM.INPB","CRAT:IN20:BP01:TEMP2.SEVR") #! Field("CRAT:IN20:BP01:TEMPSUM.INPC",16777215,0,"CRAT:IN20:BP01:TEMPSUM.INPC") #! Link("CRAT:IN20:BP01:TEMPSUM.INPC","CRAT:IN20:BP01:TEMP3.SEVR") #! Field("CRAT:IN20:BP01:TEMPSUM.INPD",16777215,0,"CRAT:IN20:BP01:TEMPSUM.INPD") #! Link("CRAT:IN20:BP01:TEMPSUM.INPD","CRAT:IN20:BP01:TEMP4.SEVR") #! Field("CRAT:IN20:BP01:TEMPSUM.INPE",16777215,0,"CRAT:IN20:BP01:TEMPSUM.INPE") #! Link("CRAT:IN20:BP01:TEMPSUM.INPE","CRAT:IN20:BP01:TEMP5.SEVR") #! Field("CRAT:IN20:BP01:TEMPSUM.INPF",16777215,0,"CRAT:IN20:BP01:TEMPSUM.INPF") #! Link("CRAT:IN20:BP01:TEMPSUM.INPF","CRAT:IN20:BP01:TEMP6.SEVR") #! Field("CRAT:IN20:BP01:TEMPSUM.INPG",16777215,0,"CRAT:IN20:BP01:TEMPSUM.INPG") #! Link("CRAT:IN20:BP01:TEMPSUM.INPG","CRAT:IN20:BP01:TEMP7.SEVR") #! Field("CRAT:IN20:BP01:TEMPSUM.INPH",16777215,0,"CRAT:IN20:BP01:TEMPSUM.INPH") #! Link("CRAT:IN20:BP01:TEMPSUM.INPH","CRAT:IN20:BP01:TEMP8.SEVR") #! Field("CRAT:IN20:BP01:TEMPSUM.SEVR",16777215,0,"CRAT:IN20:BP01:TEMPSUM.SEVR") #! Record("CRAT:IN20:BP01:STATSUMY",2620,1430,0,1,"CRAT:IN20:BP01:STATSUMY") #! Field("CRAT:IN20:BP01:STATSUMY.INPA",16777215,0,"CRAT:IN20:BP01:STATSUMY.INPA") #! Link("CRAT:IN20:BP01:STATSUMY.INPA","CRAT:IN20:BP01:FWVERSION.SEVR") #! Field("CRAT:IN20:BP01:STATSUMY.INPB",16777215,0,"CRAT:IN20:BP01:STATSUMY.INPB") #! Link("CRAT:IN20:BP01:STATSUMY.INPB","CRAT:IN20:BP01:TEMPSUM.SEVR") #! Field("CRAT:IN20:BP01:STATSUMY.INPC",16777215,0,"CRAT:IN20:BP01:STATSUMY.INPC") #! Link("CRAT:IN20:BP01:STATSUMY.INPC","CRAT:IN20:BP01:CHU0_V.SEVR") #! Field("CRAT:IN20:BP01:STATSUMY.INPD",16777215,0,"CRAT:IN20:BP01:STATSUMY.INPD") #! Link("CRAT:IN20:BP01:STATSUMY.INPD","CRAT:IN20:BP01:CHU1_V.SEVR") #! Field("CRAT:IN20:BP01:STATSUMY.INPE",16777215,0,"CRAT:IN20:BP01:STATSUMY.INPE") #! Link("CRAT:IN20:BP01:STATSUMY.INPE","CRAT:IN20:BP01:CHU3_V.SEVR") #! Field("CRAT:IN20:BP01:STATSUMY.INPF",16777215,0,"CRAT:IN20:BP01:STATSUMY.INPF") #! Link("CRAT:IN20:BP01:STATSUMY.INPF","CRAT:IN20:BP01:CHU5_V.SEVR") #! Field("CRAT:IN20:BP01:STATSUMY.INPG",16777215,0,"CRAT:IN20:BP01:STATSUMY.INPG") #! Link("CRAT:IN20:BP01:STATSUMY.INPG","CRAT:IN20:BP01:FANSPEED.SEVR") #! Record("CRAT:IN20:BP01:TEMP5",820,2230,0,1,"CRAT:IN20:BP01:TEMP5") #! Field("CRAT:IN20:BP01:TEMP5.FLNK",16777215,1,"CRAT:IN20:BP01:TEMP5.FLNK") #! Link("CRAT:IN20:BP01:TEMP5.FLNK","CRAT:IN20:BP01:TEMP6") #! Field("CRAT:IN20:BP01:TEMP5.SEVR",16777215,1,"CRAT:IN20:BP01:TEMP5.SEVR") #! Record("CRAT:IN20:BP01:TEMP6",1100,2190,0,0,"CRAT:IN20:BP01:TEMP6") #! Field("CRAT:IN20:BP01:TEMP6.FLNK",16777215,1,"CRAT:IN20:BP01:TEMP6.FLNK") #! Link("CRAT:IN20:BP01:TEMP6.FLNK","CRAT:IN20:BP01:TEMP7") #! Field("CRAT:IN20:BP01:TEMP6.SEVR",16777215,1,"CRAT:IN20:BP01:TEMP6.SEVR") #! Record("CRAT:IN20:BP01:TEMP7",1360,2190,0,0,"CRAT:IN20:BP01:TEMP7") #! Field("CRAT:IN20:BP01:TEMP7.FLNK",16777215,1,"CRAT:IN20:BP01:TEMP7.FLNK") #! Link("CRAT:IN20:BP01:TEMP7.FLNK","CRAT:IN20:BP01:TEMP8") #! Field("CRAT:IN20:BP01:TEMP7.SEVR",16777215,1,"CRAT:IN20:BP01:TEMP7.SEVR") #! Record("CRAT:IN20:BP01:TEMP8",1640,2250,0,0,"CRAT:IN20:BP01:TEMP8") #! Field("CRAT:IN20:BP01:TEMP8.FLNK",16777215,0,"CRAT:IN20:BP01:TEMP8.FLNK") #! Link("CRAT:IN20:BP01:TEMP8.FLNK","CRAT:IN20:BP01:POWERCALC") #! Field("CRAT:IN20:BP01:TEMP8.SEVR",16777215,1,"CRAT:IN20:BP01:TEMP8.SEVR") #! TextBox(TB0,40,2400,480,2720,1,"Dialog",12,1,16777215,"The web interface for this crate only provides a \"toggle power\" button.\nThere is no way to send a command to turn the power on or turn the power off.\nThe purpose of all these PVs is to provide POWERON and POWEROFF \nbuttons rather than the inferior toggle button.\n\nProcessing the POWERON record when the crate is off will turn it on. \nProcessing the POWEROFF record when the crate is on will turn it off.\nProcessing the HARDRESET record will first force the POWEROFF record\nto process, then it will force the POWERON record to process.\n\nThe POWERON and POWEROFF steps take about 10 seconds each: First the IOC\nmust wait to get new on/off status (which takes five seconds) before deciding\nwhether or not to toggle the crate power. Then it sends the toggle command\nand it takes another 5 seconds to see the change in on/off status.\n\nPOWERMSG contains a string that describes what is currently happening.\nIt is normally empty, but contains text if the power is being turned on, off, or \nreset.",null) record(bo, "CRAT:IN20:TM01:LOGIN") { field(PINI, "YES") field(DTYP, "stream") field(OUT, "@crat_elma_8slot.proto.db setLogin crat-in20-tm01") } record(ai, "CRAT:IN20:TM01:V1") { field(SCAN, "1 second") field(DTYP, "stream") field(INP, "@crat_elma_8slot.proto.db getVoltage(CRAT:IN20:TM01,V2,V3,V4) crat-in20-tm01") field(PREC, "3") field(EGU, "Volts") field(HIHI, "5.25") field(LOLO, "4.875") field(HIGH, "5.20") field(LOW, "4.90") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:TM01:V2") { field(SDIS, "CRAT:IN20:TM01:V1.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "3") field(EGU, "Volts") field(HIHI, "3.465") field(LOLO, "3.2175") field(HIGH, "3.432") field(LOW, "3.234") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:TM01:V3") { field(SDIS, "CRAT:IN20:TM01:V1.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "3") field(EGU, "Volts") field(HIHI, "12.6") field(LOLO, "11.7") field(HIGH, "12.48") field(LOW, "11.76") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:TM01:V4") { field(SDIS, "CRAT:IN20:TM01:V1.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:TM01:TEMP1C") field(PREC, "3") field(EGU, "Volts") field(HIHI, "-11.76") field(LOLO, "-12.6") field(HIGH, "-11.7") field(LOW, "-12.48") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:TM01:TEMP1C") { field(DTYP, "stream") field(INP, "@crat_elma_8slot.proto.db getTemp(CRAT:IN20:TM01,TEMP2C) crat-in20-tm01") field(PREC, "0") field(EGU, "DegC") } record(ai, "CRAT:IN20:TM01:TEMP2C") { field(SDIS, "CRAT:IN20:TM01:TEMP1C.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:TM01:TEMP1") field(PREC, "0") field(EGU, "DegC") } record(ai, "CRAT:IN20:TM01:TEMP3C") { field(SDIS, "CRAT:IN20:TM01:TEMP1C.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:TM01:TEMP3") field(PREC, "0") field(EGU, "DegC") } record(ai, "CRAT:IN20:TM01:TEMP4C") { field(SDIS, "CRAT:IN20:TM01:TEMP1C.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:TM01:TEMP4") field(PREC, "0") field(EGU, "DegC") } record(calc, "CRAT:IN20:TM01:TEMP1") { field(FLNK, "CRAT:IN20:TM01:TEMP2") field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:TM01:TEMP1C NPP MS") field(EGU, "DegF") field(PREC, "0") field(HIHI, "145") field(HIGH, "137") field(HHSV, "MAJOR") field(HSV, "MINOR") } record(calc, "CRAT:IN20:TM01:TEMP2") { field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:TM01:TEMP2C NPP MS") field(EGU, "DegF") field(PREC, "0") field(HIHI, "145") field(HIGH, "137") field(HHSV, "MAJOR") field(HSV, "MINOR") } record(calc, "CRAT:IN20:TM01:TEMP3") { field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:TM01:TEMP3C.VAL NPP MS") field(EGU, "DegF") field(PREC, "0") field(HIHI, "145") field(HIGH, "137") field(HHSV, "MAJOR") field(HSV, "MINOR") } record(calc, "CRAT:IN20:TM01:TEMP4") { field(FLNK, "CRAT:IN20:TM01:TEMPMAXC") field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:TM01:TEMP2C NPP MS") field(EGU, "DegF") field(PREC, "0") field(HIHI, "145") field(HIGH, "137") field(HHSV, "MAJOR") field(HSV, "MINOR") } record(ai, "CRAT:IN20:TM01:FAN1SPEED") { field(DTYP, "stream") field(INP, "@crat_elma_8slot.proto.db getFan(CRAT:IN20:TM01) crat-in20-tm01") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:TM01:FAN2SPEED") { field(SDIS, "CRAT:IN20:TM01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:TM01:FAN3SPEED") { field(SDIS, "CRAT:IN20:TM01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:TM01:FAN4SPEED") { field(SDIS, "CRAT:IN20:TM01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:TM01:FAN5SPEED") { field(SDIS, "CRAT:IN20:TM01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:TM01:FAN6SPEED") { field(SDIS, "CRAT:IN20:TM01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:TM01:FAN7SPEED") { field(SDIS, "CRAT:IN20:TM01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:TM01:UPTIMEDAYS") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:TM01:UPTIMEDAYS") { field(DTYP, "stream") field(INP, "@crat_elma_8slot.proto.db getUptime(CRAT:IN20:TM01) crat-in20-tm01") field(EGU, "days") } record(bo, "CRAT:IN20:TM01:POWEROFF") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:TM01:POWEROFFSEQ") field(OUT, "@crat_elma_8slot.proto.db setPowerOff crat-in20-tm01") } record(bo, "CRAT:IN20:TM01:POWERON") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:TM01:POWERONSEQ") field(OUT, "@crat_elma_8slot.proto.db setPowerOn crat-in20-tm01") } record(seq, "CRAT:IN20:TM01:POWEROFFSEQ") { field(SELM, "All") field(DOL1, "1") field(LNK1, "CRAT:IN20:TM01:POWERMSG PP") field(DLY2, "5") field(DOL2, "0") field(LNK2, "CRAT:IN20:TM01:POWERMSG PP") } record(mbbo, "CRAT:IN20:TM01:POWERMSG") { field(ZRVL, "0") field(ONVL, "1") field(TWVL, "2") field(THVL, "3") field(ONST, "TURNING_OFF") field(TWST, "TURNING_ON") field(THST, "RESETTING") field(ZRSV, "NO_ALARM") field(ONSV, "MINOR") field(TWSV, "MINOR") field(THSV, "MINOR") field(PINI, "YES") } record(bo, "CRAT:IN20:TM01:HARDRESET") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:TM01:HARDRESETSEQ") field(OUT, "@crat_elma_8slot.proto.db setPowerReset crat-in20-tm01") } record(seq, "CRAT:IN20:TM01:POWERONSEQ") { field(SELM, "All") field(DOL1, "2") field(LNK1, "CRAT:IN20:TM01:POWERMSG PP") field(DLY2, "5") field(DOL2, "0") field(LNK2, "CRAT:IN20:TM01:POWERMSG PP") } record(seq, "CRAT:IN20:TM01:HARDRESETSEQ") { field(SELM, "All") field(DOL1, "3") field(LNK1, "CRAT:IN20:TM01:POWERMSG PP") field(DLY2, "5") field(DOL2, "0") field(LNK2, "CRAT:IN20:TM01:POWERMSG PP") } record(calc, "CRAT:IN20:TM01:TEMPHIGHSTATCALC") { field(SDIS, "CRAT:IN20:TM01:STATUSWORD1 NPP MS") field(FLNK, "CRAT:IN20:TM01:TEMPHIGHSTAT") field(CALC, "(A&B)=B?1:0") field(INPA, "CRAT:IN20:TM01:STATUSWORD1.VAL MS") field(INPB, "0x20") } record(bi, "CRAT:IN20:TM01:TEMPHIGHSTAT") { field(FLNK, "CRAT:IN20:TM01:STATUSWORD2") field(INP, "CRAT:IN20:TM01:TEMPHIGHSTATCALC.VAL NPP MS") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ZNAM, "FAULT") field(ONAM, "OK") } record(ai, "CRAT:IN20:TM01:TEMPMAXC") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:TM01:TEMPMAX") field(INP, "@crat_elma_8slot.proto.db getTempMax(CRAT:IN20:TM01) crat-in20-tm01") field(PREC, "0") field(EGU, "DegC") } record(calc, "CRAT:IN20:TM01:TEMPMAX") { field(FLNK, "CRAT:IN20:TM01:FAN1SPEED") field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:TM01:TEMPMAXC NPP MS") field(EGU, "DegF") field(PREC, "0") } record(longin, "CRAT:IN20:TM01:STATUSWORD1") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:TM01:TEMPHIGHSTATCALC") field(INP, "@crat_elma_8slot.proto.db getStatusWordA crat-in20-tm01") } record(longin, "CRAT:IN20:TM01:STATUSWORD2") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:TM01:POWERSTATECALC") field(INP, "@crat_elma_8slot.proto.db getStatusWordB crat-in20-tm01") } record(calc, "CRAT:IN20:TM01:FANSTATCALC") { field(SDIS, "CRAT:IN20:TM01:STATUSWORD2 NPP MS") field(FLNK, "CRAT:IN20:TM01:FANSTAT") field(CALC, "(A&B)=B?1:0") field(INPA, "CRAT:IN20:TM01:STATUSWORD2.VAL MS") field(INPB, "0x40") } record(bi, "CRAT:IN20:TM01:FANSTAT") { field(INP, "CRAT:IN20:TM01:FANSTATCALC.VAL NPP MS") field(ZSV, "MINOR") field(OSV, "NO_ALARM") field(ZNAM, "OFF") field(ONAM, "ON") } record(calc, "CRAT:IN20:TM01:POWERSTATECALC") { field(SDIS, "CRAT:IN20:TM01:STATUSWORD2 NPP MS") field(FLNK, "CRAT:IN20:TM01:POWERSTATE") field(CALC, "(A&B)=B?1:0") field(INPA, "CRAT:IN20:TM01:STATUSWORD2.VAL MS") field(INPB, "0x01") } record(bi, "CRAT:IN20:TM01:POWERSTATE") { field(FLNK, "CRAT:IN20:TM01:FANSTATCALC") field(INP, "CRAT:IN20:TM01:POWERSTATECALC.VAL NPP MS") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ZNAM, "OFF") field(ONAM, "ON") } record(stringin, "CRAT:IN20:TM01:UPTIMEHMS") { field(SDIS, "CRAT:IN20:TM01:UPTIMEDAYS.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:TM01:STATUSWORD1") } record(stringin, "CRAT:IN20:TM01:1NAME") { field(PINI, "YES") field(VAL, "VSAM") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:TM01:2NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:TM01:3NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:TM01:4NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:TM01:5NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:TM01:6NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:TM01:7NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:TM01:8NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:TM01:LOC") { field(PINI, "YES") field(VAL, "LKG-18") info(autosaveFields,"VAL") } record(ai, "CRAT:IN20:TM01:TYPE") { field(DESC, "Elma 8 Slot VME Crate") field(PINI, "YES") field(VAL, "6") } record(calc, "CRAT:IN20:TM01:STATSUMY") { field(SCAN, "1 second") field(CALC, "A+B+C+D+E+F+G+H+I=9?1:0") field(INPA, "CRAT:IN20:TM01:TEMP1.SEVR MS") field(INPB, "CRAT:IN20:TM01:TEMP2.SEVR MS") field(INPC, "CRAT:IN20:TM01:TEMP3.SEVR MS") field(INPD, "CRAT:IN20:TM01:TEMP4.SEVR MS") field(INPE, "CRAT:IN20:TM01:V1.SEVR MS") field(INPF, "CRAT:IN20:TM01:V2.SEVR MS") field(INPG, "CRAT:IN20:TM01:V3.SEVR MS") field(INPH, "CRAT:IN20:TM01:V4.SEVR MS") field(INPI, "CRAT:IN20:TM01:FANSUMY.SEVR MS") } record(calc, "CRAT:IN20:TM01:FANSUMY") { field(SCAN, "1 second") field(CALC, "A+B+C+D+E+F+G=7?1:0") field(INPA, "CRAT:IN20:TM01:FAN1SPEED.SEVR MS") field(INPB, "CRAT:IN20:TM01:FAN2SPEED.SEVR MS") field(INPC, "CRAT:IN20:TM01:FAN3SPEED.SEVR MS") field(INPD, "CRAT:IN20:TM01:FAN4SPEED.SEVR MS") field(INPE, "CRAT:IN20:TM01:FAN5SPEED.SEVR MS") field(INPF, "CRAT:IN20:TM01:FAN6SPEED.SEVR MS") field(INPG, "CRAT:IN20:TM01:FAN7SPEED.SEVR MS") } record(bo, "CRAT:IN20:RF04:LOGIN") { field(PINI, "YES") field(DTYP, "stream") field(OUT, "@crat_elma_8slot.proto.db setLogin crat-in20-rf04") } record(ai, "CRAT:IN20:RF04:V1") { field(SCAN, "1 second") field(DTYP, "stream") field(INP, "@crat_elma_8slot.proto.db getVoltage(CRAT:IN20:RF04,V2,V3,V4) crat-in20-rf04") field(PREC, "3") field(EGU, "Volts") field(HIHI, "5.25") field(LOLO, "4.875") field(HIGH, "5.20") field(LOW, "4.90") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:RF04:V2") { field(SDIS, "CRAT:IN20:RF04:V1.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "3") field(EGU, "Volts") field(HIHI, "3.465") field(LOLO, "3.2175") field(HIGH, "3.432") field(LOW, "3.234") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:RF04:V3") { field(SDIS, "CRAT:IN20:RF04:V1.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "3") field(EGU, "Volts") field(HIHI, "12.6") field(LOLO, "11.7") field(HIGH, "12.48") field(LOW, "11.76") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:RF04:V4") { field(SDIS, "CRAT:IN20:RF04:V1.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:RF04:TEMP1C") field(PREC, "3") field(EGU, "Volts") field(HIHI, "-11.76") field(LOLO, "-12.6") field(HIGH, "-11.7") field(LOW, "-12.48") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:RF04:TEMP1C") { field(DTYP, "stream") field(INP, "@crat_elma_8slot.proto.db getTemp(CRAT:IN20:RF04,TEMP2C) crat-in20-rf04") field(PREC, "0") field(EGU, "DegC") } record(ai, "CRAT:IN20:RF04:TEMP2C") { field(SDIS, "CRAT:IN20:RF04:TEMP1C.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:RF04:TEMP1") field(PREC, "0") field(EGU, "DegC") } record(ai, "CRAT:IN20:RF04:TEMP3C") { field(SDIS, "CRAT:IN20:RF04:TEMP1C.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:RF04:TEMP3") field(PREC, "0") field(EGU, "DegC") } record(ai, "CRAT:IN20:RF04:TEMP4C") { field(SDIS, "CRAT:IN20:RF04:TEMP1C.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:RF04:TEMP4") field(PREC, "0") field(EGU, "DegC") } record(calc, "CRAT:IN20:RF04:TEMP1") { field(FLNK, "CRAT:IN20:RF04:TEMP2") field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:RF04:TEMP1C NPP MS") field(EGU, "DegF") field(PREC, "0") field(HIHI, "145") field(HIGH, "137") field(HHSV, "MAJOR") field(HSV, "MINOR") } record(calc, "CRAT:IN20:RF04:TEMP2") { field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:RF04:TEMP2C NPP MS") field(EGU, "DegF") field(PREC, "0") field(HIHI, "145") field(HIGH, "137") field(HHSV, "MAJOR") field(HSV, "MINOR") } record(calc, "CRAT:IN20:RF04:TEMP3") { field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:RF04:TEMP3C.VAL NPP MS") field(EGU, "DegF") field(PREC, "0") field(HIHI, "145") field(HIGH, "137") field(HHSV, "MAJOR") field(HSV, "MINOR") } record(calc, "CRAT:IN20:RF04:TEMP4") { field(FLNK, "CRAT:IN20:RF04:TEMPMAXC") field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:RF04:TEMP2C NPP MS") field(EGU, "DegF") field(PREC, "0") field(HIHI, "145") field(HIGH, "137") field(HHSV, "MAJOR") field(HSV, "MINOR") } record(ai, "CRAT:IN20:RF04:FAN1SPEED") { field(DTYP, "stream") field(INP, "@crat_elma_8slot.proto.db getFan(CRAT:IN20:RF04) crat-in20-rf04") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:RF04:FAN2SPEED") { field(SDIS, "CRAT:IN20:RF04:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:RF04:FAN3SPEED") { field(SDIS, "CRAT:IN20:RF04:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:RF04:FAN4SPEED") { field(SDIS, "CRAT:IN20:RF04:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:RF04:FAN5SPEED") { field(SDIS, "CRAT:IN20:RF04:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:RF04:FAN6SPEED") { field(SDIS, "CRAT:IN20:RF04:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:RF04:FAN7SPEED") { field(SDIS, "CRAT:IN20:RF04:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:RF04:UPTIMEDAYS") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:RF04:UPTIMEDAYS") { field(DTYP, "stream") field(INP, "@crat_elma_8slot.proto.db getUptime(CRAT:IN20:RF04) crat-in20-rf04") field(EGU, "days") } record(bo, "CRAT:IN20:RF04:POWEROFF") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:RF04:POWEROFFSEQ") field(OUT, "@crat_elma_8slot.proto.db setPowerOff crat-in20-rf04") } record(bo, "CRAT:IN20:RF04:POWERON") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:RF04:POWERONSEQ") field(OUT, "@crat_elma_8slot.proto.db setPowerOn crat-in20-rf04") } record(seq, "CRAT:IN20:RF04:POWEROFFSEQ") { field(SELM, "All") field(DOL1, "1") field(LNK1, "CRAT:IN20:RF04:POWERMSG PP") field(DLY2, "5") field(DOL2, "0") field(LNK2, "CRAT:IN20:RF04:POWERMSG PP") } record(mbbo, "CRAT:IN20:RF04:POWERMSG") { field(ZRVL, "0") field(ONVL, "1") field(TWVL, "2") field(THVL, "3") field(ONST, "TURNING_OFF") field(TWST, "TURNING_ON") field(THST, "RESETTING") field(ZRSV, "NO_ALARM") field(ONSV, "MINOR") field(TWSV, "MINOR") field(THSV, "MINOR") field(PINI, "YES") } record(bo, "CRAT:IN20:RF04:HARDRESET") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:RF04:HARDRESETSEQ") field(OUT, "@crat_elma_8slot.proto.db setPowerReset crat-in20-rf04") } record(seq, "CRAT:IN20:RF04:POWERONSEQ") { field(SELM, "All") field(DOL1, "2") field(LNK1, "CRAT:IN20:RF04:POWERMSG PP") field(DLY2, "5") field(DOL2, "0") field(LNK2, "CRAT:IN20:RF04:POWERMSG PP") } record(seq, "CRAT:IN20:RF04:HARDRESETSEQ") { field(SELM, "All") field(DOL1, "3") field(LNK1, "CRAT:IN20:RF04:POWERMSG PP") field(DLY2, "5") field(DOL2, "0") field(LNK2, "CRAT:IN20:RF04:POWERMSG PP") } record(calc, "CRAT:IN20:RF04:TEMPHIGHSTATCALC") { field(SDIS, "CRAT:IN20:RF04:STATUSWORD1 NPP MS") field(FLNK, "CRAT:IN20:RF04:TEMPHIGHSTAT") field(CALC, "(A&B)=B?1:0") field(INPA, "CRAT:IN20:RF04:STATUSWORD1.VAL MS") field(INPB, "0x20") } record(bi, "CRAT:IN20:RF04:TEMPHIGHSTAT") { field(FLNK, "CRAT:IN20:RF04:STATUSWORD2") field(INP, "CRAT:IN20:RF04:TEMPHIGHSTATCALC.VAL NPP MS") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ZNAM, "FAULT") field(ONAM, "OK") } record(ai, "CRAT:IN20:RF04:TEMPMAXC") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:RF04:TEMPMAX") field(INP, "@crat_elma_8slot.proto.db getTempMax(CRAT:IN20:RF04) crat-in20-rf04") field(PREC, "0") field(EGU, "DegC") } record(calc, "CRAT:IN20:RF04:TEMPMAX") { field(FLNK, "CRAT:IN20:RF04:FAN1SPEED") field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:RF04:TEMPMAXC NPP MS") field(EGU, "DegF") field(PREC, "0") } record(longin, "CRAT:IN20:RF04:STATUSWORD1") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:RF04:TEMPHIGHSTATCALC") field(INP, "@crat_elma_8slot.proto.db getStatusWordA crat-in20-rf04") } record(longin, "CRAT:IN20:RF04:STATUSWORD2") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:RF04:POWERSTATECALC") field(INP, "@crat_elma_8slot.proto.db getStatusWordB crat-in20-rf04") } record(calc, "CRAT:IN20:RF04:FANSTATCALC") { field(SDIS, "CRAT:IN20:RF04:STATUSWORD2 NPP MS") field(FLNK, "CRAT:IN20:RF04:FANSTAT") field(CALC, "(A&B)=B?1:0") field(INPA, "CRAT:IN20:RF04:STATUSWORD2.VAL MS") field(INPB, "0x40") } record(bi, "CRAT:IN20:RF04:FANSTAT") { field(INP, "CRAT:IN20:RF04:FANSTATCALC.VAL NPP MS") field(ZSV, "MINOR") field(OSV, "NO_ALARM") field(ZNAM, "OFF") field(ONAM, "ON") } record(calc, "CRAT:IN20:RF04:POWERSTATECALC") { field(SDIS, "CRAT:IN20:RF04:STATUSWORD2 NPP MS") field(FLNK, "CRAT:IN20:RF04:POWERSTATE") field(CALC, "(A&B)=B?1:0") field(INPA, "CRAT:IN20:RF04:STATUSWORD2.VAL MS") field(INPB, "0x01") } record(bi, "CRAT:IN20:RF04:POWERSTATE") { field(FLNK, "CRAT:IN20:RF04:FANSTATCALC") field(INP, "CRAT:IN20:RF04:POWERSTATECALC.VAL NPP MS") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ZNAM, "OFF") field(ONAM, "ON") } record(stringin, "CRAT:IN20:RF04:UPTIMEHMS") { field(SDIS, "CRAT:IN20:RF04:UPTIMEDAYS.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:RF04:STATUSWORD1") } record(stringin, "CRAT:IN20:RF04:1NAME") { field(PINI, "YES") field(VAL, "IOC:IN20:RF04") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:RF04:2NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:RF04:3NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:RF04:4NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:RF04:5NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:RF04:6NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:RF04:7NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:RF04:8NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:RF04:LOC") { field(PINI, "YES") field(VAL, "LKG-2103") info(autosaveFields,"VAL") } record(ai, "CRAT:IN20:RF04:TYPE") { field(DESC, "Elma 8 Slot VME Crate") field(PINI, "YES") field(VAL, "6") } record(calc, "CRAT:IN20:RF04:STATSUMY") { field(SCAN, "1 second") field(CALC, "A+B+C+D+E+F+G+H+I=9?1:0") field(INPA, "CRAT:IN20:RF04:TEMP1.SEVR MS") field(INPB, "CRAT:IN20:RF04:TEMP2.SEVR MS") field(INPC, "CRAT:IN20:RF04:TEMP3.SEVR MS") field(INPD, "CRAT:IN20:RF04:TEMP4.SEVR MS") field(INPE, "CRAT:IN20:RF04:V1.SEVR MS") field(INPF, "CRAT:IN20:RF04:V2.SEVR MS") field(INPG, "CRAT:IN20:RF04:V3.SEVR MS") field(INPH, "CRAT:IN20:RF04:V4.SEVR MS") field(INPI, "CRAT:IN20:RF04:FANSUMY.SEVR MS") } record(calc, "CRAT:IN20:RF04:FANSUMY") { field(SCAN, "1 second") field(CALC, "A+B+C+D+E+F+G=7?1:0") field(INPA, "CRAT:IN20:RF04:FAN1SPEED.SEVR MS") field(INPB, "CRAT:IN20:RF04:FAN2SPEED.SEVR MS") field(INPC, "CRAT:IN20:RF04:FAN3SPEED.SEVR MS") field(INPD, "CRAT:IN20:RF04:FAN4SPEED.SEVR MS") field(INPE, "CRAT:IN20:RF04:FAN5SPEED.SEVR MS") field(INPF, "CRAT:IN20:RF04:FAN6SPEED.SEVR MS") field(INPG, "CRAT:IN20:RF04:FAN7SPEED.SEVR MS") } record(bo, "CRAT:IN20:MC01:LOGIN") { field(PINI, "YES") field(DTYP, "stream") field(OUT, "@crat_elma_8slot.proto.db setLogin crat-in20-mc01") } record(ai, "CRAT:IN20:MC01:V1") { field(SCAN, "1 second") field(DTYP, "stream") field(INP, "@crat_elma_8slot.proto.db getVoltage(CRAT:IN20:MC01,V2,V3,V4) crat-in20-mc01") field(PREC, "3") field(EGU, "Volts") field(HIHI, "5.25") field(LOLO, "4.875") field(HIGH, "5.20") field(LOW, "4.90") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:MC01:V2") { field(SDIS, "CRAT:IN20:MC01:V1.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "3") field(EGU, "Volts") field(HIHI, "3.465") field(LOLO, "3.2175") field(HIGH, "3.432") field(LOW, "3.234") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:MC01:V3") { field(SDIS, "CRAT:IN20:MC01:V1.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "3") field(EGU, "Volts") field(HIHI, "12.6") field(LOLO, "11.7") field(HIGH, "12.48") field(LOW, "11.76") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:MC01:V4") { field(SDIS, "CRAT:IN20:MC01:V1.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:MC01:TEMP1C") field(PREC, "3") field(EGU, "Volts") field(HIHI, "-11.76") field(LOLO, "-12.6") field(HIGH, "-11.7") field(LOW, "-12.48") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:MC01:TEMP1C") { field(DTYP, "stream") field(INP, "@crat_elma_8slot.proto.db getTemp(CRAT:IN20:MC01,TEMP2C) crat-in20-mc01") field(PREC, "0") field(EGU, "DegC") } record(ai, "CRAT:IN20:MC01:TEMP2C") { field(SDIS, "CRAT:IN20:MC01:TEMP1C.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:MC01:TEMP1") field(PREC, "0") field(EGU, "DegC") } record(ai, "CRAT:IN20:MC01:TEMP3C") { field(SDIS, "CRAT:IN20:MC01:TEMP1C.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:MC01:TEMP3") field(PREC, "0") field(EGU, "DegC") } record(ai, "CRAT:IN20:MC01:TEMP4C") { field(SDIS, "CRAT:IN20:MC01:TEMP1C.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:MC01:TEMP4") field(PREC, "0") field(EGU, "DegC") } record(calc, "CRAT:IN20:MC01:TEMP1") { field(FLNK, "CRAT:IN20:MC01:TEMP2") field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:MC01:TEMP1C NPP MS") field(EGU, "DegF") field(PREC, "0") field(HIHI, "145") field(HIGH, "137") field(HHSV, "MAJOR") field(HSV, "MINOR") } record(calc, "CRAT:IN20:MC01:TEMP2") { field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:MC01:TEMP2C NPP MS") field(EGU, "DegF") field(PREC, "0") field(HIHI, "145") field(HIGH, "137") field(HHSV, "MAJOR") field(HSV, "MINOR") } record(calc, "CRAT:IN20:MC01:TEMP3") { field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:MC01:TEMP3C.VAL NPP MS") field(EGU, "DegF") field(PREC, "0") field(HIHI, "145") field(HIGH, "137") field(HHSV, "MAJOR") field(HSV, "MINOR") } record(calc, "CRAT:IN20:MC01:TEMP4") { field(FLNK, "CRAT:IN20:MC01:TEMPMAXC") field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:MC01:TEMP2C NPP MS") field(EGU, "DegF") field(PREC, "0") field(HIHI, "145") field(HIGH, "137") field(HHSV, "MAJOR") field(HSV, "MINOR") } record(ai, "CRAT:IN20:MC01:FAN1SPEED") { field(DTYP, "stream") field(INP, "@crat_elma_8slot.proto.db getFan(CRAT:IN20:MC01) crat-in20-mc01") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:MC01:FAN2SPEED") { field(SDIS, "CRAT:IN20:MC01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:MC01:FAN3SPEED") { field(SDIS, "CRAT:IN20:MC01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:MC01:FAN4SPEED") { field(SDIS, "CRAT:IN20:MC01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:MC01:FAN5SPEED") { field(SDIS, "CRAT:IN20:MC01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:MC01:FAN6SPEED") { field(SDIS, "CRAT:IN20:MC01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:MC01:FAN7SPEED") { field(SDIS, "CRAT:IN20:MC01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:MC01:UPTIMEDAYS") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:MC01:UPTIMEDAYS") { field(DTYP, "stream") field(INP, "@crat_elma_8slot.proto.db getUptime(CRAT:IN20:MC01) crat-in20-mc01") field(EGU, "days") } record(bo, "CRAT:IN20:MC01:POWEROFF") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:MC01:POWEROFFSEQ") field(OUT, "@crat_elma_8slot.proto.db setPowerOff crat-in20-mc01") } record(bo, "CRAT:IN20:MC01:POWERON") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:MC01:POWERONSEQ") field(OUT, "@crat_elma_8slot.proto.db setPowerOn crat-in20-mc01") } record(seq, "CRAT:IN20:MC01:POWEROFFSEQ") { field(SELM, "All") field(DOL1, "1") field(LNK1, "CRAT:IN20:MC01:POWERMSG PP") field(DLY2, "5") field(DOL2, "0") field(LNK2, "CRAT:IN20:MC01:POWERMSG PP") } record(mbbo, "CRAT:IN20:MC01:POWERMSG") { field(ZRVL, "0") field(ONVL, "1") field(TWVL, "2") field(THVL, "3") field(ONST, "TURNING_OFF") field(TWST, "TURNING_ON") field(THST, "RESETTING") field(ZRSV, "NO_ALARM") field(ONSV, "MINOR") field(TWSV, "MINOR") field(THSV, "MINOR") field(PINI, "YES") } record(bo, "CRAT:IN20:MC01:HARDRESET") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:MC01:HARDRESETSEQ") field(OUT, "@crat_elma_8slot.proto.db setPowerReset crat-in20-mc01") } record(seq, "CRAT:IN20:MC01:POWERONSEQ") { field(SELM, "All") field(DOL1, "2") field(LNK1, "CRAT:IN20:MC01:POWERMSG PP") field(DLY2, "5") field(DOL2, "0") field(LNK2, "CRAT:IN20:MC01:POWERMSG PP") } record(seq, "CRAT:IN20:MC01:HARDRESETSEQ") { field(SELM, "All") field(DOL1, "3") field(LNK1, "CRAT:IN20:MC01:POWERMSG PP") field(DLY2, "5") field(DOL2, "0") field(LNK2, "CRAT:IN20:MC01:POWERMSG PP") } record(calc, "CRAT:IN20:MC01:TEMPHIGHSTATCALC") { field(SDIS, "CRAT:IN20:MC01:STATUSWORD1 NPP MS") field(FLNK, "CRAT:IN20:MC01:TEMPHIGHSTAT") field(CALC, "(A&B)=B?1:0") field(INPA, "CRAT:IN20:MC01:STATUSWORD1.VAL MS") field(INPB, "0x20") } record(bi, "CRAT:IN20:MC01:TEMPHIGHSTAT") { field(FLNK, "CRAT:IN20:MC01:STATUSWORD2") field(INP, "CRAT:IN20:MC01:TEMPHIGHSTATCALC.VAL NPP MS") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ZNAM, "FAULT") field(ONAM, "OK") } record(ai, "CRAT:IN20:MC01:TEMPMAXC") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:MC01:TEMPMAX") field(INP, "@crat_elma_8slot.proto.db getTempMax(CRAT:IN20:MC01) crat-in20-mc01") field(PREC, "0") field(EGU, "DegC") } record(calc, "CRAT:IN20:MC01:TEMPMAX") { field(FLNK, "CRAT:IN20:MC01:FAN1SPEED") field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:MC01:TEMPMAXC NPP MS") field(EGU, "DegF") field(PREC, "0") } record(longin, "CRAT:IN20:MC01:STATUSWORD1") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:MC01:TEMPHIGHSTATCALC") field(INP, "@crat_elma_8slot.proto.db getStatusWordA crat-in20-mc01") } record(longin, "CRAT:IN20:MC01:STATUSWORD2") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:MC01:POWERSTATECALC") field(INP, "@crat_elma_8slot.proto.db getStatusWordB crat-in20-mc01") } record(calc, "CRAT:IN20:MC01:FANSTATCALC") { field(SDIS, "CRAT:IN20:MC01:STATUSWORD2 NPP MS") field(FLNK, "CRAT:IN20:MC01:FANSTAT") field(CALC, "(A&B)=B?1:0") field(INPA, "CRAT:IN20:MC01:STATUSWORD2.VAL MS") field(INPB, "0x40") } record(bi, "CRAT:IN20:MC01:FANSTAT") { field(INP, "CRAT:IN20:MC01:FANSTATCALC.VAL NPP MS") field(ZSV, "MINOR") field(OSV, "NO_ALARM") field(ZNAM, "OFF") field(ONAM, "ON") } record(calc, "CRAT:IN20:MC01:POWERSTATECALC") { field(SDIS, "CRAT:IN20:MC01:STATUSWORD2 NPP MS") field(FLNK, "CRAT:IN20:MC01:POWERSTATE") field(CALC, "(A&B)=B?1:0") field(INPA, "CRAT:IN20:MC01:STATUSWORD2.VAL MS") field(INPB, "0x01") } record(bi, "CRAT:IN20:MC01:POWERSTATE") { field(FLNK, "CRAT:IN20:MC01:FANSTATCALC") field(INP, "CRAT:IN20:MC01:POWERSTATECALC.VAL NPP MS") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ZNAM, "OFF") field(ONAM, "ON") } record(stringin, "CRAT:IN20:MC01:UPTIMEHMS") { field(SDIS, "CRAT:IN20:MC01:UPTIMEDAYS.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:MC01:STATUSWORD1") } record(stringin, "CRAT:IN20:MC01:1NAME") { field(PINI, "YES") field(VAL, "IOC:IN20:MC01") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:MC01:2NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:MC01:3NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:MC01:4NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:MC01:5NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:MC01:6NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:MC01:7NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:MC01:8NAME") { field(PINI, "YES") field(VAL, "Empty") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:MC01:LOC") { field(PINI, "YES") field(VAL, "LKG-1127") info(autosaveFields,"VAL") } record(ai, "CRAT:IN20:MC01:TYPE") { field(DESC, "Elma 8 Slot VME Crate") field(PINI, "YES") field(VAL, "6") } record(calc, "CRAT:IN20:MC01:STATSUMY") { field(SCAN, "1 second") field(CALC, "A+B+C+D+E+F+G+H+I=9?1:0") field(INPA, "CRAT:IN20:MC01:TEMP1.SEVR MS") field(INPB, "CRAT:IN20:MC01:TEMP2.SEVR MS") field(INPC, "CRAT:IN20:MC01:TEMP3.SEVR MS") field(INPD, "CRAT:IN20:MC01:TEMP4.SEVR MS") field(INPE, "CRAT:IN20:MC01:V1.SEVR MS") field(INPF, "CRAT:IN20:MC01:V2.SEVR MS") field(INPG, "CRAT:IN20:MC01:V3.SEVR MS") field(INPH, "CRAT:IN20:MC01:V4.SEVR MS") field(INPI, "CRAT:IN20:MC01:FANSUMY.SEVR MS") } record(calc, "CRAT:IN20:MC01:FANSUMY") { field(SCAN, "1 second") field(CALC, "A+B+C+D+E+F+G=7?1:0") field(INPA, "CRAT:IN20:MC01:FAN1SPEED.SEVR MS") field(INPB, "CRAT:IN20:MC01:FAN2SPEED.SEVR MS") field(INPC, "CRAT:IN20:MC01:FAN3SPEED.SEVR MS") field(INPD, "CRAT:IN20:MC01:FAN4SPEED.SEVR MS") field(INPE, "CRAT:IN20:MC01:FAN5SPEED.SEVR MS") field(INPF, "CRAT:IN20:MC01:FAN6SPEED.SEVR MS") field(INPG, "CRAT:IN20:MC01:FAN7SPEED.SEVR MS") } record(bo, "CRAT:IN20:VA01:LOGIN") { field(PINI, "YES") field(DTYP, "stream") field(OUT, "@crat_elma_4slot.proto.db setLogin crat-in20-va01") } record(ai, "CRAT:IN20:VA01:V1") { field(SCAN, "1 second") field(DTYP, "stream") field(FLNK, "CRAT:IN20:VA01:V2") field(INP, "@crat_elma_4slot.proto.db getVoltage(CRAT:IN20:VA01,V2,V3,V4) crat-in20-va01") field(PREC, "3") field(EGU, "Volts") field(HIHI, "5.25") field(LOLO, "4.875") field(HIGH, "5.20") field(LOW, "4.90") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:VA01:V2") { field(SDIS, "CRAT:IN20:VA01:V1.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:VA01:V3") field(PREC, "3") field(EGU, "Volts") field(HIHI, "3.465") field(LOLO, "3.2175") field(HIGH, "3.432") field(LOW, "3.234") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:VA01:V3") { field(SDIS, "CRAT:IN20:VA01:V1.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:VA01:V4") field(PREC, "3") field(EGU, "Volts") field(HIHI, "12.6") field(LOLO, "11.7") field(HIGH, "12.48") field(LOW, "11.76") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:VA01:V4") { field(SDIS, "CRAT:IN20:VA01:V1.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:VA01:TEMP1C") field(PREC, "3") field(EGU, "Volts") field(HIHI, "-11.76") field(LOLO, "-12.6") field(HIGH, "-11.7") field(LOW, "-12.48") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:VA01:TEMP1C") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:VA01:TEMP2C") field(INP, "@crat_elma_4slot.proto.db getTemp(CRAT:IN20:VA01,TEMP2C) crat-in20-va01") field(PREC, "0") field(EGU, "DegC") } record(ai, "CRAT:IN20:VA01:TEMP2C") { field(SDIS, "CRAT:IN20:VA01:TEMP1C.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:VA01:TEMP1") field(PREC, "0") field(EGU, "DegC") } record(calc, "CRAT:IN20:VA01:TEMP1") { field(FLNK, "CRAT:IN20:VA01:TEMP2") field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:VA01:TEMP1C NPP MS") field(EGU, "DegF") field(PREC, "0") field(HIHI, "145") field(HIGH, "137") field(HHSV, "MAJOR") field(HSV, "MINOR") } record(calc, "CRAT:IN20:VA01:TEMP2") { field(FLNK, "CRAT:IN20:VA01:TEMPMAXC") field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:VA01:TEMP2C NPP MS") field(EGU, "DegF") field(PREC, "0") field(HIHI, "145") field(HIGH, "137") field(HHSV, "MAJOR") field(HSV, "MINOR") } record(ai, "CRAT:IN20:VA01:FAN1SPEED") { field(DTYP, "stream") field(INP, "@crat_elma_4slot.proto.db getFan(CRAT:IN20:VA01) crat-in20-va01") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:VA01:FAN2SPEED") { field(SDIS, "CRAT:IN20:VA01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:VA01:FAN3SPEED") { field(SDIS, "CRAT:IN20:VA01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:VA01:FAN4SPEED") { field(SDIS, "CRAT:IN20:VA01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:VA01:FAN5SPEED") { field(SDIS, "CRAT:IN20:VA01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:VA01:FAN6SPEED") { field(SDIS, "CRAT:IN20:VA01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:VA01:UPTIMEDAYS") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:VA01:UPTIMEDAYS") { field(DTYP, "stream") field(INP, "@crat_elma_4slot.proto.db getUptime(CRAT:IN20:VA01) crat-in20-va01") field(EGU, "days") } record(bo, "CRAT:IN20:VA01:POWEROFF") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:VA01:POWEROFFSEQ") field(OUT, "@crat_elma_4slot.proto.db setPowerOff crat-in20-va01") } record(bo, "CRAT:IN20:VA01:POWERON") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:VA01:POWERONSEQ") field(OUT, "@crat_elma_4slot.proto.db setPowerOn crat-in20-va01") } record(seq, "CRAT:IN20:VA01:POWEROFFSEQ") { field(SELM, "All") field(DOL1, "1") field(LNK1, "CRAT:IN20:VA01:POWERMSG PP") field(DLY2, "5") field(DOL2, "0") field(LNK2, "CRAT:IN20:VA01:POWERMSG PP") } record(mbbo, "CRAT:IN20:VA01:POWERMSG") { field(ZRVL, "0") field(ONVL, "1") field(TWVL, "2") field(THVL, "3") field(ONST, "TURNING_OFF") field(TWST, "TURNING_ON") field(THST, "RESETTING") field(ZRSV, "NO_ALARM") field(ONSV, "MINOR") field(TWSV, "MINOR") field(THSV, "MINOR") } record(bo, "CRAT:IN20:VA01:HARDRESET") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:VA01:HARDRESETSEQ") field(OUT, "@crat_elma_4slot.proto.db setPowerReset crat-in20-va01") } record(seq, "CRAT:IN20:VA01:POWERONSEQ") { field(SELM, "All") field(DOL1, "2") field(LNK1, "CRAT:IN20:VA01:POWERMSG PP") field(DLY2, "5") field(DOL2, "0") field(LNK2, "CRAT:IN20:VA01:POWERMSG PP") } record(seq, "CRAT:IN20:VA01:HARDRESETSEQ") { field(SELM, "All") field(DOL1, "3") field(LNK1, "CRAT:IN20:VA01:POWERMSG PP") field(DLY2, "5") field(DOL2, "0") field(LNK2, "CRAT:IN20:VA01:POWERMSG PP") } record(calc, "CRAT:IN20:VA01:TEMPHIGHSTATCALC") { field(SDIS, "CRAT:IN20:VA01:STATUSWORD1 NPP MS") field(FLNK, "CRAT:IN20:VA01:TEMPHIGHSTAT") field(CALC, "(A&B)=B?1:0") field(INPA, "CRAT:IN20:VA01:STATUSWORD1.VAL MS") field(INPB, "0x20") } record(bi, "CRAT:IN20:VA01:TEMPHIGHSTAT") { field(FLNK, "CRAT:IN20:VA01:STATUSWORD2") field(INP, "CRAT:IN20:VA01:TEMPHIGHSTATCALC.VAL NPP MS") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ZNAM, "FAULT") field(ONAM, "OK") } record(ai, "CRAT:IN20:VA01:TEMPMAXC") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:VA01:TEMPMAX") field(INP, "@crat_elma_4slot.proto.db getTempMax(CRAT:IN20:VA01) crat-in20-va01") field(PREC, "0") field(EGU, "DegC") } record(calc, "CRAT:IN20:VA01:TEMPMAX") { field(FLNK, "CRAT:IN20:VA01:FAN1SPEED") field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:VA01:TEMPMAXC NPP MS") field(EGU, "DegF") field(PREC, "0") } record(longin, "CRAT:IN20:VA01:STATUSWORD1") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:VA01:TEMPHIGHSTATCALC") field(INP, "@crat_elma_4slot.proto.db getStatusWordA crat-in20-va01") } record(longin, "CRAT:IN20:VA01:STATUSWORD2") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:VA01:POWERSTATECALC") field(INP, "@crat_elma_4slot.proto.db getStatusWordB crat-in20-va01") } record(calc, "CRAT:IN20:VA01:FANSTATCALC") { field(SDIS, "CRAT:IN20:VA01:STATUSWORD2 NPP MS") field(FLNK, "CRAT:IN20:VA01:FANSTAT") field(CALC, "(A&B)=B?1:0") field(INPA, "CRAT:IN20:VA01:STATUSWORD2.VAL MS") field(INPB, "0x40") } record(bi, "CRAT:IN20:VA01:FANSTAT") { field(INP, "CRAT:IN20:VA01:FANSTATCALC.VAL NPP MS") field(ZSV, "MINOR") field(OSV, "NO_ALARM") field(ZNAM, "OFF") field(ONAM, "ON") } record(calc, "CRAT:IN20:VA01:POWERSTATECALC") { field(SDIS, "CRAT:IN20:VA01:STATUSWORD2 NPP MS") field(FLNK, "CRAT:IN20:VA01:POWERSTATE") field(CALC, "(A&B)=B?1:0") field(INPA, "CRAT:IN20:VA01:STATUSWORD2.VAL MS") field(INPB, "0x01") } record(bi, "CRAT:IN20:VA01:POWERSTATE") { field(FLNK, "CRAT:IN20:VA01:FANSTATCALC") field(INP, "CRAT:IN20:VA01:POWERSTATECALC.VAL NPP MS") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ZNAM, "OFF") field(ONAM, "ON") } record(stringin, "CRAT:IN20:VA01:UPTIMEHMS") { field(SDIS, "CRAT:IN20:VA01:UPTIMEDAYS.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:VA01:STATUSWORD1") } record(stringin, "CRAT:IN20:VA01:1NAME") { field(PINI, "YES") field(VAL, "IOC:IN20:VA01") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:VA01:2NAME") { field(PINI, "YES") field(VAL, "") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:VA01:3NAME") { field(PINI, "YES") field(VAL, "") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:VA01:4NAME") { field(PINI, "YES") field(VAL, "") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:VA01:LOC") { field(PINI, "YES") field(VAL, "LKG-1213") info(autosaveFields,"VAL") } record(ai, "CRAT:IN20:VA01:TYPE") { field(DESC, "Elma 4 Slot VME Crate") field(PINI, "YES") field(VAL, "5") } record(calc, "CRAT:IN20:VA01:STATSUMY") { field(SCAN, "1 second") field(CALC, "A+B+C+D+E+F+G+H+I+J+K+L=12?1:0") field(INPA, "CRAT:IN20:VA01:TEMP1.SEVR MS") field(INPB, "CRAT:IN20:VA01:TEMP2.SEVR MS") field(INPC, "CRAT:IN20:VA01:V1.SEVR MS") field(INPD, "CRAT:IN20:VA01:V2.SEVR MS") field(INPE, "CRAT:IN20:VA01:V3.SEVR MS") field(INPF, "CRAT:IN20:VA01:V4.SEVR MS") field(INPG, "CRAT:IN20:VA01:FAN1SPEED.SEVR MS") field(INPH, "CRAT:IN20:VA01:FAN2SPEED.SEVR MS") field(INPI, "CRAT:IN20:VA01:FAN3SPEED.SEVR MS") field(INPJ, "CRAT:IN20:VA01:FAN4SPEED.SEVR MS") field(INPK, "CRAT:IN20:VA01:FAN5SPEED.SEVR MS") field(INPL, "CRAT:IN20:VA01:FAN6SPEED.SEVR MS") } record(bo, "CRAT:IN20:RF02:LOGIN") { field(PINI, "YES") field(DTYP, "stream") field(OUT, "@crat_elma_4slot.proto.db setLogin crat-in20-rf02") } record(ai, "CRAT:IN20:RF02:V1") { field(SCAN, "1 second") field(DTYP, "stream") field(FLNK, "CRAT:IN20:RF02:V2") field(INP, "@crat_elma_4slot.proto.db getVoltage(CRAT:IN20:RF02,V2,V3,V4) crat-in20-rf02") field(PREC, "3") field(EGU, "Volts") field(HIHI, "5.25") field(LOLO, "4.875") field(HIGH, "5.20") field(LOW, "4.90") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:RF02:V2") { field(SDIS, "CRAT:IN20:RF02:V1.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:RF02:V3") field(PREC, "3") field(EGU, "Volts") field(HIHI, "3.465") field(LOLO, "3.2175") field(HIGH, "3.432") field(LOW, "3.234") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:RF02:V3") { field(SDIS, "CRAT:IN20:RF02:V1.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:RF02:V4") field(PREC, "3") field(EGU, "Volts") field(HIHI, "12.6") field(LOLO, "11.7") field(HIGH, "12.48") field(LOW, "11.76") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:RF02:V4") { field(SDIS, "CRAT:IN20:RF02:V1.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:RF02:TEMP1C") field(PREC, "3") field(EGU, "Volts") field(HIHI, "-11.76") field(LOLO, "-12.6") field(HIGH, "-11.7") field(LOW, "-12.48") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:RF02:TEMP1C") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:RF02:TEMP2C") field(INP, "@crat_elma_4slot.proto.db getTemp(CRAT:IN20:RF02,TEMP2C) crat-in20-rf02") field(PREC, "0") field(EGU, "DegC") } record(ai, "CRAT:IN20:RF02:TEMP2C") { field(SDIS, "CRAT:IN20:RF02:TEMP1C.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:RF02:TEMP1") field(PREC, "0") field(EGU, "DegC") } record(calc, "CRAT:IN20:RF02:TEMP1") { field(FLNK, "CRAT:IN20:RF02:TEMP2") field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:RF02:TEMP1C NPP MS") field(EGU, "DegF") field(PREC, "0") field(HIHI, "145") field(HIGH, "137") field(HHSV, "MAJOR") field(HSV, "MINOR") } record(calc, "CRAT:IN20:RF02:TEMP2") { field(FLNK, "CRAT:IN20:RF02:TEMPMAXC") field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:RF02:TEMP2C NPP MS") field(EGU, "DegF") field(PREC, "0") field(HIHI, "145") field(HIGH, "137") field(HHSV, "MAJOR") field(HSV, "MINOR") } record(ai, "CRAT:IN20:RF02:FAN1SPEED") { field(DTYP, "stream") field(INP, "@crat_elma_4slot.proto.db getFan(CRAT:IN20:RF02) crat-in20-rf02") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:RF02:FAN2SPEED") { field(SDIS, "CRAT:IN20:RF02:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:RF02:FAN3SPEED") { field(SDIS, "CRAT:IN20:RF02:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:RF02:FAN4SPEED") { field(SDIS, "CRAT:IN20:RF02:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:RF02:FAN5SPEED") { field(SDIS, "CRAT:IN20:RF02:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:RF02:FAN6SPEED") { field(SDIS, "CRAT:IN20:RF02:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:RF02:UPTIMEDAYS") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:RF02:UPTIMEDAYS") { field(DTYP, "stream") field(INP, "@crat_elma_4slot.proto.db getUptime(CRAT:IN20:RF02) crat-in20-rf02") field(EGU, "days") } record(bo, "CRAT:IN20:RF02:POWEROFF") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:RF02:POWEROFFSEQ") field(OUT, "@crat_elma_4slot.proto.db setPowerOff crat-in20-rf02") } record(bo, "CRAT:IN20:RF02:POWERON") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:RF02:POWERONSEQ") field(OUT, "@crat_elma_4slot.proto.db setPowerOn crat-in20-rf02") } record(seq, "CRAT:IN20:RF02:POWEROFFSEQ") { field(SELM, "All") field(DOL1, "1") field(LNK1, "CRAT:IN20:RF02:POWERMSG PP") field(DLY2, "5") field(DOL2, "0") field(LNK2, "CRAT:IN20:RF02:POWERMSG PP") } record(mbbo, "CRAT:IN20:RF02:POWERMSG") { field(ZRVL, "0") field(ONVL, "1") field(TWVL, "2") field(THVL, "3") field(ONST, "TURNING_OFF") field(TWST, "TURNING_ON") field(THST, "RESETTING") field(ZRSV, "NO_ALARM") field(ONSV, "MINOR") field(TWSV, "MINOR") field(THSV, "MINOR") } record(bo, "CRAT:IN20:RF02:HARDRESET") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:RF02:HARDRESETSEQ") field(OUT, "@crat_elma_4slot.proto.db setPowerReset crat-in20-rf02") } record(seq, "CRAT:IN20:RF02:POWERONSEQ") { field(SELM, "All") field(DOL1, "2") field(LNK1, "CRAT:IN20:RF02:POWERMSG PP") field(DLY2, "5") field(DOL2, "0") field(LNK2, "CRAT:IN20:RF02:POWERMSG PP") } record(seq, "CRAT:IN20:RF02:HARDRESETSEQ") { field(SELM, "All") field(DOL1, "3") field(LNK1, "CRAT:IN20:RF02:POWERMSG PP") field(DLY2, "5") field(DOL2, "0") field(LNK2, "CRAT:IN20:RF02:POWERMSG PP") } record(calc, "CRAT:IN20:RF02:TEMPHIGHSTATCALC") { field(SDIS, "CRAT:IN20:RF02:STATUSWORD1 NPP MS") field(FLNK, "CRAT:IN20:RF02:TEMPHIGHSTAT") field(CALC, "(A&B)=B?1:0") field(INPA, "CRAT:IN20:RF02:STATUSWORD1.VAL MS") field(INPB, "0x20") } record(bi, "CRAT:IN20:RF02:TEMPHIGHSTAT") { field(FLNK, "CRAT:IN20:RF02:STATUSWORD2") field(INP, "CRAT:IN20:RF02:TEMPHIGHSTATCALC.VAL NPP MS") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ZNAM, "FAULT") field(ONAM, "OK") } record(ai, "CRAT:IN20:RF02:TEMPMAXC") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:RF02:TEMPMAX") field(INP, "@crat_elma_4slot.proto.db getTempMax(CRAT:IN20:RF02) crat-in20-rf02") field(PREC, "0") field(EGU, "DegC") } record(calc, "CRAT:IN20:RF02:TEMPMAX") { field(FLNK, "CRAT:IN20:RF02:FAN1SPEED") field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:RF02:TEMPMAXC NPP MS") field(EGU, "DegF") field(PREC, "0") } record(longin, "CRAT:IN20:RF02:STATUSWORD1") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:RF02:TEMPHIGHSTATCALC") field(INP, "@crat_elma_4slot.proto.db getStatusWordA crat-in20-rf02") } record(longin, "CRAT:IN20:RF02:STATUSWORD2") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:RF02:POWERSTATECALC") field(INP, "@crat_elma_4slot.proto.db getStatusWordB crat-in20-rf02") } record(calc, "CRAT:IN20:RF02:FANSTATCALC") { field(SDIS, "CRAT:IN20:RF02:STATUSWORD2 NPP MS") field(FLNK, "CRAT:IN20:RF02:FANSTAT") field(CALC, "(A&B)=B?1:0") field(INPA, "CRAT:IN20:RF02:STATUSWORD2.VAL MS") field(INPB, "0x40") } record(bi, "CRAT:IN20:RF02:FANSTAT") { field(INP, "CRAT:IN20:RF02:FANSTATCALC.VAL NPP MS") field(ZSV, "MINOR") field(OSV, "NO_ALARM") field(ZNAM, "OFF") field(ONAM, "ON") } record(calc, "CRAT:IN20:RF02:POWERSTATECALC") { field(SDIS, "CRAT:IN20:RF02:STATUSWORD2 NPP MS") field(FLNK, "CRAT:IN20:RF02:POWERSTATE") field(CALC, "(A&B)=B?1:0") field(INPA, "CRAT:IN20:RF02:STATUSWORD2.VAL MS") field(INPB, "0x01") } record(bi, "CRAT:IN20:RF02:POWERSTATE") { field(FLNK, "CRAT:IN20:RF02:FANSTATCALC") field(INP, "CRAT:IN20:RF02:POWERSTATECALC.VAL NPP MS") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ZNAM, "OFF") field(ONAM, "ON") } record(stringin, "CRAT:IN20:RF02:UPTIMEHMS") { field(SDIS, "CRAT:IN20:RF02:UPTIMEDAYS.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:RF02:STATUSWORD1") } record(stringin, "CRAT:IN20:RF02:1NAME") { field(PINI, "YES") field(VAL, "IOC:IN20:RF02") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:RF02:2NAME") { field(PINI, "YES") field(VAL, "") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:RF02:3NAME") { field(PINI, "YES") field(VAL, "") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:RF02:4NAME") { field(PINI, "YES") field(VAL, "") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:RF02:LOC") { field(PINI, "YES") field(VAL, "LKG-2601") info(autosaveFields,"VAL") } record(ai, "CRAT:IN20:RF02:TYPE") { field(DESC, "Elma 4 Slot VME Crate") field(PINI, "YES") field(VAL, "5") } record(calc, "CRAT:IN20:RF02:STATSUMY") { field(SCAN, "1 second") field(CALC, "A+B+C+D+E+F+G+H+I+J+K+L=12?1:0") field(INPA, "CRAT:IN20:RF02:TEMP1.SEVR MS") field(INPB, "CRAT:IN20:RF02:TEMP2.SEVR MS") field(INPC, "CRAT:IN20:RF02:V1.SEVR MS") field(INPD, "CRAT:IN20:RF02:V2.SEVR MS") field(INPE, "CRAT:IN20:RF02:V3.SEVR MS") field(INPF, "CRAT:IN20:RF02:V4.SEVR MS") field(INPG, "CRAT:IN20:RF02:FAN1SPEED.SEVR MS") field(INPH, "CRAT:IN20:RF02:FAN2SPEED.SEVR MS") field(INPI, "CRAT:IN20:RF02:FAN3SPEED.SEVR MS") field(INPJ, "CRAT:IN20:RF02:FAN4SPEED.SEVR MS") field(INPK, "CRAT:IN20:RF02:FAN5SPEED.SEVR MS") field(INPL, "CRAT:IN20:RF02:FAN6SPEED.SEVR MS") } record(bo, "CRAT:IN20:RF03:LOGIN") { field(PINI, "YES") field(DTYP, "stream") field(OUT, "@crat_elma_4slot.proto.db setLogin crat-in20-rf03") } record(ai, "CRAT:IN20:RF03:V1") { field(SCAN, "1 second") field(DTYP, "stream") field(FLNK, "CRAT:IN20:RF03:V2") field(INP, "@crat_elma_4slot.proto.db getVoltage(CRAT:IN20:RF03,V2,V3,V4) crat-in20-rf03") field(PREC, "3") field(EGU, "Volts") field(HIHI, "5.25") field(LOLO, "4.875") field(HIGH, "5.20") field(LOW, "4.90") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:RF03:V2") { field(SDIS, "CRAT:IN20:RF03:V1.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:RF03:V3") field(PREC, "3") field(EGU, "Volts") field(HIHI, "3.465") field(LOLO, "3.2175") field(HIGH, "3.432") field(LOW, "3.234") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:RF03:V3") { field(SDIS, "CRAT:IN20:RF03:V1.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:RF03:V4") field(PREC, "3") field(EGU, "Volts") field(HIHI, "12.6") field(LOLO, "11.7") field(HIGH, "12.48") field(LOW, "11.76") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:RF03:V4") { field(SDIS, "CRAT:IN20:RF03:V1.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:RF03:TEMP1C") field(PREC, "3") field(EGU, "Volts") field(HIHI, "-11.76") field(LOLO, "-12.6") field(HIGH, "-11.7") field(LOW, "-12.48") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:RF03:TEMP1C") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:RF03:TEMP2C") field(INP, "@crat_elma_4slot.proto.db getTemp(CRAT:IN20:RF03,TEMP2C) crat-in20-rf03") field(PREC, "0") field(EGU, "DegC") } record(ai, "CRAT:IN20:RF03:TEMP2C") { field(SDIS, "CRAT:IN20:RF03:TEMP1C.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:RF03:TEMP1") field(PREC, "0") field(EGU, "DegC") } record(calc, "CRAT:IN20:RF03:TEMP1") { field(FLNK, "CRAT:IN20:RF03:TEMP2") field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:RF03:TEMP1C NPP MS") field(EGU, "DegF") field(PREC, "0") field(HIHI, "145") field(HIGH, "137") field(HHSV, "MAJOR") field(HSV, "MINOR") } record(calc, "CRAT:IN20:RF03:TEMP2") { field(FLNK, "CRAT:IN20:RF03:TEMPMAXC") field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:RF03:TEMP2C NPP MS") field(EGU, "DegF") field(PREC, "0") field(HIHI, "145") field(HIGH, "137") field(HHSV, "MAJOR") field(HSV, "MINOR") } record(ai, "CRAT:IN20:RF03:FAN1SPEED") { field(DTYP, "stream") field(INP, "@crat_elma_4slot.proto.db getFan(CRAT:IN20:RF03) crat-in20-rf03") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:RF03:FAN2SPEED") { field(SDIS, "CRAT:IN20:RF03:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:RF03:FAN3SPEED") { field(SDIS, "CRAT:IN20:RF03:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:RF03:FAN4SPEED") { field(SDIS, "CRAT:IN20:RF03:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:RF03:FAN5SPEED") { field(SDIS, "CRAT:IN20:RF03:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:RF03:FAN6SPEED") { field(SDIS, "CRAT:IN20:RF03:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:RF03:UPTIMEDAYS") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:RF03:UPTIMEDAYS") { field(DTYP, "stream") field(INP, "@crat_elma_4slot.proto.db getUptime(CRAT:IN20:RF03) crat-in20-rf03") field(EGU, "days") } record(bo, "CRAT:IN20:RF03:POWEROFF") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:RF03:POWEROFFSEQ") field(OUT, "@crat_elma_4slot.proto.db setPowerOff crat-in20-rf03") } record(bo, "CRAT:IN20:RF03:POWERON") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:RF03:POWERONSEQ") field(OUT, "@crat_elma_4slot.proto.db setPowerOn crat-in20-rf03") } record(seq, "CRAT:IN20:RF03:POWEROFFSEQ") { field(SELM, "All") field(DOL1, "1") field(LNK1, "CRAT:IN20:RF03:POWERMSG PP") field(DLY2, "5") field(DOL2, "0") field(LNK2, "CRAT:IN20:RF03:POWERMSG PP") } record(mbbo, "CRAT:IN20:RF03:POWERMSG") { field(ZRVL, "0") field(ONVL, "1") field(TWVL, "2") field(THVL, "3") field(ONST, "TURNING_OFF") field(TWST, "TURNING_ON") field(THST, "RESETTING") field(ZRSV, "NO_ALARM") field(ONSV, "MINOR") field(TWSV, "MINOR") field(THSV, "MINOR") } record(bo, "CRAT:IN20:RF03:HARDRESET") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:RF03:HARDRESETSEQ") field(OUT, "@crat_elma_4slot.proto.db setPowerReset crat-in20-rf03") } record(seq, "CRAT:IN20:RF03:POWERONSEQ") { field(SELM, "All") field(DOL1, "2") field(LNK1, "CRAT:IN20:RF03:POWERMSG PP") field(DLY2, "5") field(DOL2, "0") field(LNK2, "CRAT:IN20:RF03:POWERMSG PP") } record(seq, "CRAT:IN20:RF03:HARDRESETSEQ") { field(SELM, "All") field(DOL1, "3") field(LNK1, "CRAT:IN20:RF03:POWERMSG PP") field(DLY2, "5") field(DOL2, "0") field(LNK2, "CRAT:IN20:RF03:POWERMSG PP") } record(calc, "CRAT:IN20:RF03:TEMPHIGHSTATCALC") { field(SDIS, "CRAT:IN20:RF03:STATUSWORD1 NPP MS") field(FLNK, "CRAT:IN20:RF03:TEMPHIGHSTAT") field(CALC, "(A&B)=B?1:0") field(INPA, "CRAT:IN20:RF03:STATUSWORD1.VAL MS") field(INPB, "0x20") } record(bi, "CRAT:IN20:RF03:TEMPHIGHSTAT") { field(FLNK, "CRAT:IN20:RF03:STATUSWORD2") field(INP, "CRAT:IN20:RF03:TEMPHIGHSTATCALC.VAL NPP MS") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ZNAM, "FAULT") field(ONAM, "OK") } record(ai, "CRAT:IN20:RF03:TEMPMAXC") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:RF03:TEMPMAX") field(INP, "@crat_elma_4slot.proto.db getTempMax(CRAT:IN20:RF03) crat-in20-rf03") field(PREC, "0") field(EGU, "DegC") } record(calc, "CRAT:IN20:RF03:TEMPMAX") { field(FLNK, "CRAT:IN20:RF03:FAN1SPEED") field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:RF03:TEMPMAXC NPP MS") field(EGU, "DegF") field(PREC, "0") } record(longin, "CRAT:IN20:RF03:STATUSWORD1") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:RF03:TEMPHIGHSTATCALC") field(INP, "@crat_elma_4slot.proto.db getStatusWordA crat-in20-rf03") } record(longin, "CRAT:IN20:RF03:STATUSWORD2") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:RF03:POWERSTATECALC") field(INP, "@crat_elma_4slot.proto.db getStatusWordB crat-in20-rf03") } record(calc, "CRAT:IN20:RF03:FANSTATCALC") { field(SDIS, "CRAT:IN20:RF03:STATUSWORD2 NPP MS") field(FLNK, "CRAT:IN20:RF03:FANSTAT") field(CALC, "(A&B)=B?1:0") field(INPA, "CRAT:IN20:RF03:STATUSWORD2.VAL MS") field(INPB, "0x40") } record(bi, "CRAT:IN20:RF03:FANSTAT") { field(INP, "CRAT:IN20:RF03:FANSTATCALC.VAL NPP MS") field(ZSV, "MINOR") field(OSV, "NO_ALARM") field(ZNAM, "OFF") field(ONAM, "ON") } record(calc, "CRAT:IN20:RF03:POWERSTATECALC") { field(SDIS, "CRAT:IN20:RF03:STATUSWORD2 NPP MS") field(FLNK, "CRAT:IN20:RF03:POWERSTATE") field(CALC, "(A&B)=B?1:0") field(INPA, "CRAT:IN20:RF03:STATUSWORD2.VAL MS") field(INPB, "0x01") } record(bi, "CRAT:IN20:RF03:POWERSTATE") { field(FLNK, "CRAT:IN20:RF03:FANSTATCALC") field(INP, "CRAT:IN20:RF03:POWERSTATECALC.VAL NPP MS") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ZNAM, "OFF") field(ONAM, "ON") } record(stringin, "CRAT:IN20:RF03:UPTIMEHMS") { field(SDIS, "CRAT:IN20:RF03:UPTIMEDAYS.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:RF03:STATUSWORD1") } record(stringin, "CRAT:IN20:RF03:1NAME") { field(PINI, "YES") field(VAL, "IOC:IN20:RF03") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:RF03:2NAME") { field(PINI, "YES") field(VAL, "") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:RF03:3NAME") { field(PINI, "YES") field(VAL, "") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:RF03:4NAME") { field(PINI, "YES") field(VAL, "") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:RF03:LOC") { field(PINI, "YES") field(VAL, "LKG-2701") info(autosaveFields,"VAL") } record(ai, "CRAT:IN20:RF03:TYPE") { field(DESC, "Elma 4 Slot VME Crate") field(PINI, "YES") field(VAL, "5") } record(calc, "CRAT:IN20:RF03:STATSUMY") { field(SCAN, "1 second") field(CALC, "A+B+C+D+E+F+G+H+I+J+K+L=12?1:0") field(INPA, "CRAT:IN20:RF03:TEMP1.SEVR MS") field(INPB, "CRAT:IN20:RF03:TEMP2.SEVR MS") field(INPC, "CRAT:IN20:RF03:V1.SEVR MS") field(INPD, "CRAT:IN20:RF03:V2.SEVR MS") field(INPE, "CRAT:IN20:RF03:V3.SEVR MS") field(INPF, "CRAT:IN20:RF03:V4.SEVR MS") field(INPG, "CRAT:IN20:RF03:FAN1SPEED.SEVR MS") field(INPH, "CRAT:IN20:RF03:FAN2SPEED.SEVR MS") field(INPI, "CRAT:IN20:RF03:FAN3SPEED.SEVR MS") field(INPJ, "CRAT:IN20:RF03:FAN4SPEED.SEVR MS") field(INPK, "CRAT:IN20:RF03:FAN5SPEED.SEVR MS") field(INPL, "CRAT:IN20:RF03:FAN6SPEED.SEVR MS") } record(bo, "CRAT:IN20:AM01:LOGIN") { field(PINI, "YES") field(DTYP, "stream") field(OUT, "@crat_elma_4slot.proto.db setLogin crat-in20-am01") } record(ai, "CRAT:IN20:AM01:V1") { field(SCAN, "1 second") field(DTYP, "stream") field(FLNK, "CRAT:IN20:AM01:V2") field(INP, "@crat_elma_4slot.proto.db getVoltage(CRAT:IN20:AM01,V2,V3,V4) crat-in20-am01") field(PREC, "3") field(EGU, "Volts") field(HIHI, "5.25") field(LOLO, "4.875") field(HIGH, "5.20") field(LOW, "4.90") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:AM01:V2") { field(SDIS, "CRAT:IN20:AM01:V1.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:AM01:V3") field(PREC, "3") field(EGU, "Volts") field(HIHI, "3.465") field(LOLO, "3.2175") field(HIGH, "3.432") field(LOW, "3.234") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:AM01:V3") { field(SDIS, "CRAT:IN20:AM01:V1.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:AM01:V4") field(PREC, "3") field(EGU, "Volts") field(HIHI, "12.6") field(LOLO, "11.7") field(HIGH, "12.48") field(LOW, "11.76") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:AM01:V4") { field(SDIS, "CRAT:IN20:AM01:V1.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:AM01:TEMP1C") field(PREC, "3") field(EGU, "Volts") field(HIHI, "-11.76") field(LOLO, "-12.6") field(HIGH, "-11.7") field(LOW, "-12.48") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:AM01:TEMP1C") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:AM01:TEMP2C") field(INP, "@crat_elma_4slot.proto.db getTemp(CRAT:IN20:AM01,TEMP2C) crat-in20-am01") field(PREC, "0") field(EGU, "DegC") } record(ai, "CRAT:IN20:AM01:TEMP2C") { field(SDIS, "CRAT:IN20:AM01:TEMP1C.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:AM01:TEMP1") field(PREC, "0") field(EGU, "DegC") } record(calc, "CRAT:IN20:AM01:TEMP1") { field(FLNK, "CRAT:IN20:AM01:TEMP2") field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:AM01:TEMP1C NPP MS") field(EGU, "DegF") field(PREC, "0") field(HIHI, "145") field(HIGH, "137") field(HHSV, "MAJOR") field(HSV, "MINOR") } record(calc, "CRAT:IN20:AM01:TEMP2") { field(FLNK, "CRAT:IN20:AM01:TEMPMAXC") field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:AM01:TEMP2C NPP MS") field(EGU, "DegF") field(PREC, "0") field(HIHI, "145") field(HIGH, "137") field(HHSV, "MAJOR") field(HSV, "MINOR") } record(ai, "CRAT:IN20:AM01:FAN1SPEED") { field(DTYP, "stream") field(INP, "@crat_elma_4slot.proto.db getFan(CRAT:IN20:AM01) crat-in20-am01") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:AM01:FAN2SPEED") { field(SDIS, "CRAT:IN20:AM01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:AM01:FAN3SPEED") { field(SDIS, "CRAT:IN20:AM01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:AM01:FAN4SPEED") { field(SDIS, "CRAT:IN20:AM01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:AM01:FAN5SPEED") { field(SDIS, "CRAT:IN20:AM01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:AM01:FAN6SPEED") { field(SDIS, "CRAT:IN20:AM01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:AM01:UPTIMEDAYS") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:AM01:UPTIMEDAYS") { field(DTYP, "stream") field(INP, "@crat_elma_4slot.proto.db getUptime(CRAT:IN20:AM01) crat-in20-am01") field(EGU, "days") } record(bo, "CRAT:IN20:AM01:POWEROFF") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:AM01:POWEROFFSEQ") field(OUT, "@crat_elma_4slot.proto.db setPowerOff crat-in20-am01") } record(bo, "CRAT:IN20:AM01:POWERON") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:AM01:POWERONSEQ") field(OUT, "@crat_elma_4slot.proto.db setPowerOn crat-in20-am01") } record(seq, "CRAT:IN20:AM01:POWEROFFSEQ") { field(SELM, "All") field(DOL1, "1") field(LNK1, "CRAT:IN20:AM01:POWERMSG PP") field(DLY2, "5") field(DOL2, "0") field(LNK2, "CRAT:IN20:AM01:POWERMSG PP") } record(mbbo, "CRAT:IN20:AM01:POWERMSG") { field(ZRVL, "0") field(ONVL, "1") field(TWVL, "2") field(THVL, "3") field(ONST, "TURNING_OFF") field(TWST, "TURNING_ON") field(THST, "RESETTING") field(ZRSV, "NO_ALARM") field(ONSV, "MINOR") field(TWSV, "MINOR") field(THSV, "MINOR") } record(bo, "CRAT:IN20:AM01:HARDRESET") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:AM01:HARDRESETSEQ") field(OUT, "@crat_elma_4slot.proto.db setPowerReset crat-in20-am01") } record(seq, "CRAT:IN20:AM01:POWERONSEQ") { field(SELM, "All") field(DOL1, "2") field(LNK1, "CRAT:IN20:AM01:POWERMSG PP") field(DLY2, "5") field(DOL2, "0") field(LNK2, "CRAT:IN20:AM01:POWERMSG PP") } record(seq, "CRAT:IN20:AM01:HARDRESETSEQ") { field(SELM, "All") field(DOL1, "3") field(LNK1, "CRAT:IN20:AM01:POWERMSG PP") field(DLY2, "5") field(DOL2, "0") field(LNK2, "CRAT:IN20:AM01:POWERMSG PP") } record(calc, "CRAT:IN20:AM01:TEMPHIGHSTATCALC") { field(SDIS, "CRAT:IN20:AM01:STATUSWORD1 NPP MS") field(FLNK, "CRAT:IN20:AM01:TEMPHIGHSTAT") field(CALC, "(A&B)=B?1:0") field(INPA, "CRAT:IN20:AM01:STATUSWORD1.VAL MS") field(INPB, "0x20") } record(bi, "CRAT:IN20:AM01:TEMPHIGHSTAT") { field(FLNK, "CRAT:IN20:AM01:STATUSWORD2") field(INP, "CRAT:IN20:AM01:TEMPHIGHSTATCALC.VAL NPP MS") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ZNAM, "FAULT") field(ONAM, "OK") } record(ai, "CRAT:IN20:AM01:TEMPMAXC") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:AM01:TEMPMAX") field(INP, "@crat_elma_4slot.proto.db getTempMax(CRAT:IN20:AM01) crat-in20-am01") field(PREC, "0") field(EGU, "DegC") } record(calc, "CRAT:IN20:AM01:TEMPMAX") { field(FLNK, "CRAT:IN20:AM01:FAN1SPEED") field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:AM01:TEMPMAXC NPP MS") field(EGU, "DegF") field(PREC, "0") } record(longin, "CRAT:IN20:AM01:STATUSWORD1") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:AM01:TEMPHIGHSTATCALC") field(INP, "@crat_elma_4slot.proto.db getStatusWordA crat-in20-am01") } record(longin, "CRAT:IN20:AM01:STATUSWORD2") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:AM01:POWERSTATECALC") field(INP, "@crat_elma_4slot.proto.db getStatusWordB crat-in20-am01") } record(calc, "CRAT:IN20:AM01:FANSTATCALC") { field(SDIS, "CRAT:IN20:AM01:STATUSWORD2 NPP MS") field(FLNK, "CRAT:IN20:AM01:FANSTAT") field(CALC, "(A&B)=B?1:0") field(INPA, "CRAT:IN20:AM01:STATUSWORD2.VAL MS") field(INPB, "0x40") } record(bi, "CRAT:IN20:AM01:FANSTAT") { field(INP, "CRAT:IN20:AM01:FANSTATCALC.VAL NPP MS") field(ZSV, "MINOR") field(OSV, "NO_ALARM") field(ZNAM, "OFF") field(ONAM, "ON") } record(calc, "CRAT:IN20:AM01:POWERSTATECALC") { field(SDIS, "CRAT:IN20:AM01:STATUSWORD2 NPP MS") field(FLNK, "CRAT:IN20:AM01:POWERSTATE") field(CALC, "(A&B)=B?1:0") field(INPA, "CRAT:IN20:AM01:STATUSWORD2.VAL MS") field(INPB, "0x01") } record(bi, "CRAT:IN20:AM01:POWERSTATE") { field(FLNK, "CRAT:IN20:AM01:FANSTATCALC") field(INP, "CRAT:IN20:AM01:POWERSTATECALC.VAL NPP MS") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ZNAM, "OFF") field(ONAM, "ON") } record(stringin, "CRAT:IN20:AM01:UPTIMEHMS") { field(SDIS, "CRAT:IN20:AM01:UPTIMEDAYS.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:AM01:STATUSWORD1") } record(stringin, "CRAT:IN20:AM01:1NAME") { field(PINI, "YES") field(VAL, "IOC:IN20:AM01") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:AM01:2NAME") { field(PINI, "YES") field(VAL, "") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:AM01:3NAME") { field(PINI, "YES") field(VAL, "") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:AM01:4NAME") { field(PINI, "YES") field(VAL, "") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:AM01:LOC") { field(PINI, "YES") field(VAL, "LIT-0110") info(autosaveFields,"VAL") } record(ai, "CRAT:IN20:AM01:TYPE") { field(DESC, "Elma 4 Slot VME Crate") field(PINI, "YES") field(VAL, "5") } record(calc, "CRAT:IN20:AM01:STATSUMY") { field(SCAN, "1 second") field(CALC, "A+B+C+D+E+F+G+H+I+J+K+L=12?1:0") field(INPA, "CRAT:IN20:AM01:TEMP1.SEVR MS") field(INPB, "CRAT:IN20:AM01:TEMP2.SEVR MS") field(INPC, "CRAT:IN20:AM01:V1.SEVR MS") field(INPD, "CRAT:IN20:AM01:V2.SEVR MS") field(INPE, "CRAT:IN20:AM01:V3.SEVR MS") field(INPF, "CRAT:IN20:AM01:V4.SEVR MS") field(INPG, "CRAT:IN20:AM01:FAN1SPEED.SEVR MS") field(INPH, "CRAT:IN20:AM01:FAN2SPEED.SEVR MS") field(INPI, "CRAT:IN20:AM01:FAN3SPEED.SEVR MS") field(INPJ, "CRAT:IN20:AM01:FAN4SPEED.SEVR MS") field(INPK, "CRAT:IN20:AM01:FAN5SPEED.SEVR MS") field(INPL, "CRAT:IN20:AM01:FAN6SPEED.SEVR MS") } record(bo, "CRAT:IN20:EV51:LOGIN") { field(PINI, "YES") field(DTYP, "stream") field(OUT, "@crat_elma_4slot.proto.db setLogin crat-in20-ev51") } record(ai, "CRAT:IN20:EV51:V1") { field(SCAN, "1 second") field(DTYP, "stream") field(FLNK, "CRAT:IN20:EV51:V2") field(INP, "@crat_elma_4slot.proto.db getVoltage(CRAT:IN20:EV51,V2,V3,V4) crat-in20-ev51") field(PREC, "3") field(EGU, "Volts") field(HIHI, "5.25") field(LOLO, "4.875") field(HIGH, "5.20") field(LOW, "4.90") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:EV51:V2") { field(SDIS, "CRAT:IN20:EV51:V1.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:EV51:V3") field(PREC, "3") field(EGU, "Volts") field(HIHI, "3.465") field(LOLO, "3.2175") field(HIGH, "3.432") field(LOW, "3.234") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:EV51:V3") { field(SDIS, "CRAT:IN20:EV51:V1.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:EV51:V4") field(PREC, "3") field(EGU, "Volts") field(HIHI, "12.6") field(LOLO, "11.7") field(HIGH, "12.48") field(LOW, "11.76") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:EV51:V4") { field(SDIS, "CRAT:IN20:EV51:V1.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:EV51:TEMP1C") field(PREC, "3") field(EGU, "Volts") field(HIHI, "-11.76") field(LOLO, "-12.6") field(HIGH, "-11.7") field(LOW, "-12.48") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:EV51:TEMP1C") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:EV51:TEMP2C") field(INP, "@crat_elma_4slot.proto.db getTemp(CRAT:IN20:EV51,TEMP2C) crat-in20-ev51") field(PREC, "0") field(EGU, "DegC") } record(ai, "CRAT:IN20:EV51:TEMP2C") { field(SDIS, "CRAT:IN20:EV51:TEMP1C.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:EV51:TEMP1") field(PREC, "0") field(EGU, "DegC") } record(calc, "CRAT:IN20:EV51:TEMP1") { field(FLNK, "CRAT:IN20:EV51:TEMP2") field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:EV51:TEMP1C NPP MS") field(EGU, "DegF") field(PREC, "0") field(HIHI, "145") field(HIGH, "137") field(HHSV, "MAJOR") field(HSV, "MINOR") } record(calc, "CRAT:IN20:EV51:TEMP2") { field(FLNK, "CRAT:IN20:EV51:TEMPMAXC") field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:EV51:TEMP2C NPP MS") field(EGU, "DegF") field(PREC, "0") field(HIHI, "145") field(HIGH, "137") field(HHSV, "MAJOR") field(HSV, "MINOR") } record(ai, "CRAT:IN20:EV51:FAN1SPEED") { field(DTYP, "stream") field(INP, "@crat_elma_4slot.proto.db getFan(CRAT:IN20:EV51) crat-in20-ev51") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:EV51:FAN2SPEED") { field(SDIS, "CRAT:IN20:EV51:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:EV51:FAN3SPEED") { field(SDIS, "CRAT:IN20:EV51:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:EV51:FAN4SPEED") { field(SDIS, "CRAT:IN20:EV51:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:EV51:FAN5SPEED") { field(SDIS, "CRAT:IN20:EV51:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:EV51:FAN6SPEED") { field(SDIS, "CRAT:IN20:EV51:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:EV51:UPTIMEDAYS") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:EV51:UPTIMEDAYS") { field(DTYP, "stream") field(INP, "@crat_elma_4slot.proto.db getUptime(CRAT:IN20:EV51) crat-in20-ev51") field(EGU, "days") } record(bo, "CRAT:IN20:EV51:POWEROFF") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:EV51:POWEROFFSEQ") field(OUT, "@crat_elma_4slot.proto.db setPowerOff crat-in20-ev51") } record(bo, "CRAT:IN20:EV51:POWERON") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:EV51:POWERONSEQ") field(OUT, "@crat_elma_4slot.proto.db setPowerOn crat-in20-ev51") } record(seq, "CRAT:IN20:EV51:POWEROFFSEQ") { field(SELM, "All") field(DOL1, "1") field(LNK1, "CRAT:IN20:EV51:POWERMSG PP") field(DLY2, "5") field(DOL2, "0") field(LNK2, "CRAT:IN20:EV51:POWERMSG PP") } record(mbbo, "CRAT:IN20:EV51:POWERMSG") { field(ZRVL, "0") field(ONVL, "1") field(TWVL, "2") field(THVL, "3") field(ONST, "TURNING_OFF") field(TWST, "TURNING_ON") field(THST, "RESETTING") field(ZRSV, "NO_ALARM") field(ONSV, "MINOR") field(TWSV, "MINOR") field(THSV, "MINOR") } record(bo, "CRAT:IN20:EV51:HARDRESET") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:EV51:HARDRESETSEQ") field(OUT, "@crat_elma_4slot.proto.db setPowerReset crat-in20-ev51") } record(seq, "CRAT:IN20:EV51:POWERONSEQ") { field(SELM, "All") field(DOL1, "2") field(LNK1, "CRAT:IN20:EV51:POWERMSG PP") field(DLY2, "5") field(DOL2, "0") field(LNK2, "CRAT:IN20:EV51:POWERMSG PP") } record(seq, "CRAT:IN20:EV51:HARDRESETSEQ") { field(SELM, "All") field(DOL1, "3") field(LNK1, "CRAT:IN20:EV51:POWERMSG PP") field(DLY2, "5") field(DOL2, "0") field(LNK2, "CRAT:IN20:EV51:POWERMSG PP") } record(calc, "CRAT:IN20:EV51:TEMPHIGHSTATCALC") { field(SDIS, "CRAT:IN20:EV51:STATUSWORD1 NPP MS") field(FLNK, "CRAT:IN20:EV51:TEMPHIGHSTAT") field(CALC, "(A&B)=B?1:0") field(INPA, "CRAT:IN20:EV51:STATUSWORD1.VAL MS") field(INPB, "0x20") } record(bi, "CRAT:IN20:EV51:TEMPHIGHSTAT") { field(FLNK, "CRAT:IN20:EV51:STATUSWORD2") field(INP, "CRAT:IN20:EV51:TEMPHIGHSTATCALC.VAL NPP MS") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ZNAM, "FAULT") field(ONAM, "OK") } record(ai, "CRAT:IN20:EV51:TEMPMAXC") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:EV51:TEMPMAX") field(INP, "@crat_elma_4slot.proto.db getTempMax(CRAT:IN20:EV51) crat-in20-ev51") field(PREC, "0") field(EGU, "DegC") } record(calc, "CRAT:IN20:EV51:TEMPMAX") { field(FLNK, "CRAT:IN20:EV51:FAN1SPEED") field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:EV51:TEMPMAXC NPP MS") field(EGU, "DegF") field(PREC, "0") } record(longin, "CRAT:IN20:EV51:STATUSWORD1") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:EV51:TEMPHIGHSTATCALC") field(INP, "@crat_elma_4slot.proto.db getStatusWordA crat-in20-ev51") } record(longin, "CRAT:IN20:EV51:STATUSWORD2") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:EV51:POWERSTATECALC") field(INP, "@crat_elma_4slot.proto.db getStatusWordB crat-in20-ev51") } record(calc, "CRAT:IN20:EV51:FANSTATCALC") { field(SDIS, "CRAT:IN20:EV51:STATUSWORD2 NPP MS") field(FLNK, "CRAT:IN20:EV51:FANSTAT") field(CALC, "(A&B)=B?1:0") field(INPA, "CRAT:IN20:EV51:STATUSWORD2.VAL MS") field(INPB, "0x40") } record(bi, "CRAT:IN20:EV51:FANSTAT") { field(INP, "CRAT:IN20:EV51:FANSTATCALC.VAL NPP MS") field(ZSV, "MINOR") field(OSV, "NO_ALARM") field(ZNAM, "OFF") field(ONAM, "ON") } record(calc, "CRAT:IN20:EV51:POWERSTATECALC") { field(SDIS, "CRAT:IN20:EV51:STATUSWORD2 NPP MS") field(FLNK, "CRAT:IN20:EV51:POWERSTATE") field(CALC, "(A&B)=B?1:0") field(INPA, "CRAT:IN20:EV51:STATUSWORD2.VAL MS") field(INPB, "0x01") } record(bi, "CRAT:IN20:EV51:POWERSTATE") { field(FLNK, "CRAT:IN20:EV51:FANSTATCALC") field(INP, "CRAT:IN20:EV51:POWERSTATECALC.VAL NPP MS") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ZNAM, "OFF") field(ONAM, "ON") } record(stringin, "CRAT:IN20:EV51:UPTIMEHMS") { field(SDIS, "CRAT:IN20:EV51:UPTIMEDAYS.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:EV51:STATUSWORD1") } record(stringin, "CRAT:IN20:EV51:1NAME") { field(PINI, "YES") field(VAL, "Timing fanout") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:EV51:2NAME") { field(PINI, "YES") field(VAL, "") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:EV51:3NAME") { field(PINI, "YES") field(VAL, "") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:EV51:4NAME") { field(PINI, "YES") field(VAL, "") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:EV51:LOC") { field(PINI, "YES") field(VAL, "RF Hut") info(autosaveFields,"VAL") } record(ai, "CRAT:IN20:EV51:TYPE") { field(DESC, "Elma 4 Slot VME Crate") field(PINI, "YES") field(VAL, "5") } record(calc, "CRAT:IN20:EV51:STATSUMY") { field(SCAN, "1 second") field(CALC, "A+B+C+D+E+F+G+H+I+J+K+L=12?1:0") field(INPA, "CRAT:IN20:EV51:TEMP1.SEVR MS") field(INPB, "CRAT:IN20:EV51:TEMP2.SEVR MS") field(INPC, "CRAT:IN20:EV51:V1.SEVR MS") field(INPD, "CRAT:IN20:EV51:V2.SEVR MS") field(INPE, "CRAT:IN20:EV51:V3.SEVR MS") field(INPF, "CRAT:IN20:EV51:V4.SEVR MS") field(INPG, "CRAT:IN20:EV51:FAN1SPEED.SEVR MS") field(INPH, "CRAT:IN20:EV51:FAN2SPEED.SEVR MS") field(INPI, "CRAT:IN20:EV51:FAN3SPEED.SEVR MS") field(INPJ, "CRAT:IN20:EV51:FAN4SPEED.SEVR MS") field(INPK, "CRAT:IN20:EV51:FAN5SPEED.SEVR MS") field(INPL, "CRAT:IN20:EV51:FAN6SPEED.SEVR MS") } record(bo, "CRAT:IN20:MP01:LOGIN") { field(PINI, "YES") field(DTYP, "stream") field(OUT, "@crat_elma_4slot.proto.db setLogin crat-in20-mp01") } record(ai, "CRAT:IN20:MP01:V1") { field(SCAN, "1 second") field(DTYP, "stream") field(FLNK, "CRAT:IN20:MP01:V2") field(INP, "@crat_elma_4slot.proto.db getVoltage(CRAT:IN20:MP01,V2,V3,V4) crat-in20-mp01") field(PREC, "3") field(EGU, "Volts") field(HIHI, "5.25") field(LOLO, "4.875") field(HIGH, "5.20") field(LOW, "4.90") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:MP01:V2") { field(SDIS, "CRAT:IN20:MP01:V1.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:MP01:V3") field(PREC, "3") field(EGU, "Volts") field(HIHI, "3.465") field(LOLO, "3.2175") field(HIGH, "3.432") field(LOW, "3.234") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:MP01:V3") { field(SDIS, "CRAT:IN20:MP01:V1.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:MP01:V4") field(PREC, "3") field(EGU, "Volts") field(HIHI, "12.6") field(LOLO, "11.7") field(HIGH, "12.48") field(LOW, "11.76") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:MP01:V4") { field(SDIS, "CRAT:IN20:MP01:V1.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:MP01:TEMP1C") field(PREC, "3") field(EGU, "Volts") field(HIHI, "-11.76") field(LOLO, "-12.6") field(HIGH, "-11.7") field(LOW, "-12.48") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:MP01:TEMP1C") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:MP01:TEMP2C") field(INP, "@crat_elma_4slot.proto.db getTemp(CRAT:IN20:MP01,TEMP2C) crat-in20-mp01") field(PREC, "0") field(EGU, "DegC") } record(ai, "CRAT:IN20:MP01:TEMP2C") { field(SDIS, "CRAT:IN20:MP01:TEMP1C.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:MP01:TEMP1") field(PREC, "0") field(EGU, "DegC") } record(calc, "CRAT:IN20:MP01:TEMP1") { field(FLNK, "CRAT:IN20:MP01:TEMP2") field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:MP01:TEMP1C NPP MS") field(EGU, "DegF") field(PREC, "0") field(HIHI, "145") field(HIGH, "137") field(HHSV, "MAJOR") field(HSV, "MINOR") } record(calc, "CRAT:IN20:MP01:TEMP2") { field(FLNK, "CRAT:IN20:MP01:TEMPMAXC") field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:MP01:TEMP2C NPP MS") field(EGU, "DegF") field(PREC, "0") field(HIHI, "145") field(HIGH, "137") field(HHSV, "MAJOR") field(HSV, "MINOR") } record(ai, "CRAT:IN20:MP01:FAN1SPEED") { field(DTYP, "stream") field(INP, "@crat_elma_4slot.proto.db getFan(CRAT:IN20:MP01) crat-in20-mp01") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:MP01:FAN2SPEED") { field(SDIS, "CRAT:IN20:MP01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:MP01:FAN3SPEED") { field(SDIS, "CRAT:IN20:MP01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:MP01:FAN4SPEED") { field(SDIS, "CRAT:IN20:MP01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:MP01:FAN5SPEED") { field(SDIS, "CRAT:IN20:MP01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:MP01:FAN6SPEED") { field(SDIS, "CRAT:IN20:MP01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:MP01:UPTIMEDAYS") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:MP01:UPTIMEDAYS") { field(DTYP, "stream") field(INP, "@crat_elma_4slot.proto.db getUptime(CRAT:IN20:MP01) crat-in20-mp01") field(EGU, "days") } record(bo, "CRAT:IN20:MP01:POWEROFF") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:MP01:POWEROFFSEQ") field(OUT, "@crat_elma_4slot.proto.db setPowerOff crat-in20-mp01") } record(bo, "CRAT:IN20:MP01:POWERON") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:MP01:POWERONSEQ") field(OUT, "@crat_elma_4slot.proto.db setPowerOn crat-in20-mp01") } record(seq, "CRAT:IN20:MP01:POWEROFFSEQ") { field(SELM, "All") field(DOL1, "1") field(LNK1, "CRAT:IN20:MP01:POWERMSG PP") field(DLY2, "5") field(DOL2, "0") field(LNK2, "CRAT:IN20:MP01:POWERMSG PP") } record(mbbo, "CRAT:IN20:MP01:POWERMSG") { field(ZRVL, "0") field(ONVL, "1") field(TWVL, "2") field(THVL, "3") field(ONST, "TURNING_OFF") field(TWST, "TURNING_ON") field(THST, "RESETTING") field(ZRSV, "NO_ALARM") field(ONSV, "MINOR") field(TWSV, "MINOR") field(THSV, "MINOR") } record(bo, "CRAT:IN20:MP01:HARDRESET") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:MP01:HARDRESETSEQ") field(OUT, "@crat_elma_4slot.proto.db setPowerReset crat-in20-mp01") } record(seq, "CRAT:IN20:MP01:POWERONSEQ") { field(SELM, "All") field(DOL1, "2") field(LNK1, "CRAT:IN20:MP01:POWERMSG PP") field(DLY2, "5") field(DOL2, "0") field(LNK2, "CRAT:IN20:MP01:POWERMSG PP") } record(seq, "CRAT:IN20:MP01:HARDRESETSEQ") { field(SELM, "All") field(DOL1, "3") field(LNK1, "CRAT:IN20:MP01:POWERMSG PP") field(DLY2, "5") field(DOL2, "0") field(LNK2, "CRAT:IN20:MP01:POWERMSG PP") } record(calc, "CRAT:IN20:MP01:TEMPHIGHSTATCALC") { field(SDIS, "CRAT:IN20:MP01:STATUSWORD1 NPP MS") field(FLNK, "CRAT:IN20:MP01:TEMPHIGHSTAT") field(CALC, "(A&B)=B?1:0") field(INPA, "CRAT:IN20:MP01:STATUSWORD1.VAL MS") field(INPB, "0x20") } record(bi, "CRAT:IN20:MP01:TEMPHIGHSTAT") { field(FLNK, "CRAT:IN20:MP01:STATUSWORD2") field(INP, "CRAT:IN20:MP01:TEMPHIGHSTATCALC.VAL NPP MS") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ZNAM, "FAULT") field(ONAM, "OK") } record(ai, "CRAT:IN20:MP01:TEMPMAXC") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:MP01:TEMPMAX") field(INP, "@crat_elma_4slot.proto.db getTempMax(CRAT:IN20:MP01) crat-in20-mp01") field(PREC, "0") field(EGU, "DegC") } record(calc, "CRAT:IN20:MP01:TEMPMAX") { field(FLNK, "CRAT:IN20:MP01:FAN1SPEED") field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:MP01:TEMPMAXC NPP MS") field(EGU, "DegF") field(PREC, "0") } record(longin, "CRAT:IN20:MP01:STATUSWORD1") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:MP01:TEMPHIGHSTATCALC") field(INP, "@crat_elma_4slot.proto.db getStatusWordA crat-in20-mp01") } record(longin, "CRAT:IN20:MP01:STATUSWORD2") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:MP01:POWERSTATECALC") field(INP, "@crat_elma_4slot.proto.db getStatusWordB crat-in20-mp01") } record(calc, "CRAT:IN20:MP01:FANSTATCALC") { field(SDIS, "CRAT:IN20:MP01:STATUSWORD2 NPP MS") field(FLNK, "CRAT:IN20:MP01:FANSTAT") field(CALC, "(A&B)=B?1:0") field(INPA, "CRAT:IN20:MP01:STATUSWORD2.VAL MS") field(INPB, "0x40") } record(bi, "CRAT:IN20:MP01:FANSTAT") { field(INP, "CRAT:IN20:MP01:FANSTATCALC.VAL NPP MS") field(ZSV, "MINOR") field(OSV, "NO_ALARM") field(ZNAM, "OFF") field(ONAM, "ON") } record(calc, "CRAT:IN20:MP01:POWERSTATECALC") { field(SDIS, "CRAT:IN20:MP01:STATUSWORD2 NPP MS") field(FLNK, "CRAT:IN20:MP01:POWERSTATE") field(CALC, "(A&B)=B?1:0") field(INPA, "CRAT:IN20:MP01:STATUSWORD2.VAL MS") field(INPB, "0x01") } record(bi, "CRAT:IN20:MP01:POWERSTATE") { field(FLNK, "CRAT:IN20:MP01:FANSTATCALC") field(INP, "CRAT:IN20:MP01:POWERSTATECALC.VAL NPP MS") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ZNAM, "OFF") field(ONAM, "ON") } record(stringin, "CRAT:IN20:MP01:UPTIMEHMS") { field(SDIS, "CRAT:IN20:MP01:UPTIMEDAYS.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:MP01:STATUSWORD1") } record(stringin, "CRAT:IN20:MP01:1NAME") { field(PINI, "YES") field(VAL, "IOC:IN20:MP01") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:MP01:2NAME") { field(PINI, "YES") field(VAL, "") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:MP01:3NAME") { field(PINI, "YES") field(VAL, "") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:MP01:4NAME") { field(PINI, "YES") field(VAL, "") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:MP01:LOC") { field(PINI, "YES") field(VAL, "LKG-1532") info(autosaveFields,"VAL") } record(ai, "CRAT:IN20:MP01:TYPE") { field(DESC, "Elma 4 Slot VME Crate") field(PINI, "YES") field(VAL, "5") } record(calc, "CRAT:IN20:MP01:STATSUMY") { field(SCAN, "1 second") field(CALC, "A+B+C+D+E+F+G+H+I+J+K+L=12?1:0") field(INPA, "CRAT:IN20:MP01:TEMP1.SEVR MS") field(INPB, "CRAT:IN20:MP01:TEMP2.SEVR MS") field(INPC, "CRAT:IN20:MP01:V1.SEVR MS") field(INPD, "CRAT:IN20:MP01:V2.SEVR MS") field(INPE, "CRAT:IN20:MP01:V3.SEVR MS") field(INPF, "CRAT:IN20:MP01:V4.SEVR MS") field(INPG, "CRAT:IN20:MP01:FAN1SPEED.SEVR MS") field(INPH, "CRAT:IN20:MP01:FAN2SPEED.SEVR MS") field(INPI, "CRAT:IN20:MP01:FAN3SPEED.SEVR MS") field(INPJ, "CRAT:IN20:MP01:FAN4SPEED.SEVR MS") field(INPK, "CRAT:IN20:MP01:FAN5SPEED.SEVR MS") field(INPL, "CRAT:IN20:MP01:FAN6SPEED.SEVR MS") } record(bo, "CRAT:IN20:IM01:LOGIN") { field(PINI, "YES") field(DTYP, "stream") field(OUT, "@crat_elma_4slot.proto.db setLogin crat-in20-im01") } record(ai, "CRAT:IN20:IM01:V1") { field(SCAN, "1 second") field(DTYP, "stream") field(FLNK, "CRAT:IN20:IM01:V2") field(INP, "@crat_elma_4slot.proto.db getVoltage(CRAT:IN20:IM01,V2,V3,V4) crat-in20-im01") field(PREC, "3") field(EGU, "Volts") field(HIHI, "5.25") field(LOLO, "4.875") field(HIGH, "5.20") field(LOW, "4.90") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:IM01:V2") { field(SDIS, "CRAT:IN20:IM01:V1.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:IM01:V3") field(PREC, "3") field(EGU, "Volts") field(HIHI, "3.465") field(LOLO, "3.2175") field(HIGH, "3.432") field(LOW, "3.234") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:IM01:V3") { field(SDIS, "CRAT:IN20:IM01:V1.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:IM01:V4") field(PREC, "3") field(EGU, "Volts") field(HIHI, "12.6") field(LOLO, "11.7") field(HIGH, "12.48") field(LOW, "11.76") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:IM01:V4") { field(SDIS, "CRAT:IN20:IM01:V1.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:IM01:TEMP1C") field(PREC, "3") field(EGU, "Volts") field(HIHI, "-11.76") field(LOLO, "-12.6") field(HIGH, "-11.7") field(LOW, "-12.48") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:IM01:TEMP1C") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:IM01:TEMP2C") field(INP, "@crat_elma_4slot.proto.db getTemp(CRAT:IN20:IM01,TEMP2C) crat-in20-im01") field(PREC, "0") field(EGU, "DegC") } record(ai, "CRAT:IN20:IM01:TEMP2C") { field(SDIS, "CRAT:IN20:IM01:TEMP1C.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:IM01:TEMP1") field(PREC, "0") field(EGU, "DegC") } record(calc, "CRAT:IN20:IM01:TEMP1") { field(FLNK, "CRAT:IN20:IM01:TEMP2") field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:IM01:TEMP1C NPP MS") field(EGU, "DegF") field(PREC, "0") field(HIHI, "145") field(HIGH, "137") field(HHSV, "MAJOR") field(HSV, "MINOR") } record(calc, "CRAT:IN20:IM01:TEMP2") { field(FLNK, "CRAT:IN20:IM01:TEMPMAXC") field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:IM01:TEMP2C NPP MS") field(EGU, "DegF") field(PREC, "0") field(HIHI, "145") field(HIGH, "137") field(HHSV, "MAJOR") field(HSV, "MINOR") } record(ai, "CRAT:IN20:IM01:FAN1SPEED") { field(DTYP, "stream") field(INP, "@crat_elma_4slot.proto.db getFan(CRAT:IN20:IM01) crat-in20-im01") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:IM01:FAN2SPEED") { field(SDIS, "CRAT:IN20:IM01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:IM01:FAN3SPEED") { field(SDIS, "CRAT:IN20:IM01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:IM01:FAN4SPEED") { field(SDIS, "CRAT:IN20:IM01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:IM01:FAN5SPEED") { field(SDIS, "CRAT:IN20:IM01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:IM01:FAN6SPEED") { field(SDIS, "CRAT:IN20:IM01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:IM01:UPTIMEDAYS") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:IM01:UPTIMEDAYS") { field(DTYP, "stream") field(INP, "@crat_elma_4slot.proto.db getUptime(CRAT:IN20:IM01) crat-in20-im01") field(EGU, "days") } record(bo, "CRAT:IN20:IM01:POWEROFF") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:IM01:POWEROFFSEQ") field(OUT, "@crat_elma_4slot.proto.db setPowerOff crat-in20-im01") } record(bo, "CRAT:IN20:IM01:POWERON") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:IM01:POWERONSEQ") field(OUT, "@crat_elma_4slot.proto.db setPowerOn crat-in20-im01") } record(seq, "CRAT:IN20:IM01:POWEROFFSEQ") { field(SELM, "All") field(DOL1, "1") field(LNK1, "CRAT:IN20:IM01:POWERMSG PP") field(DLY2, "5") field(DOL2, "0") field(LNK2, "CRAT:IN20:IM01:POWERMSG PP") } record(mbbo, "CRAT:IN20:IM01:POWERMSG") { field(ZRVL, "0") field(ONVL, "1") field(TWVL, "2") field(THVL, "3") field(ONST, "TURNING_OFF") field(TWST, "TURNING_ON") field(THST, "RESETTING") field(ZRSV, "NO_ALARM") field(ONSV, "MINOR") field(TWSV, "MINOR") field(THSV, "MINOR") } record(bo, "CRAT:IN20:IM01:HARDRESET") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:IM01:HARDRESETSEQ") field(OUT, "@crat_elma_4slot.proto.db setPowerReset crat-in20-im01") } record(seq, "CRAT:IN20:IM01:POWERONSEQ") { field(SELM, "All") field(DOL1, "2") field(LNK1, "CRAT:IN20:IM01:POWERMSG PP") field(DLY2, "5") field(DOL2, "0") field(LNK2, "CRAT:IN20:IM01:POWERMSG PP") } record(seq, "CRAT:IN20:IM01:HARDRESETSEQ") { field(SELM, "All") field(DOL1, "3") field(LNK1, "CRAT:IN20:IM01:POWERMSG PP") field(DLY2, "5") field(DOL2, "0") field(LNK2, "CRAT:IN20:IM01:POWERMSG PP") } record(calc, "CRAT:IN20:IM01:TEMPHIGHSTATCALC") { field(SDIS, "CRAT:IN20:IM01:STATUSWORD1 NPP MS") field(FLNK, "CRAT:IN20:IM01:TEMPHIGHSTAT") field(CALC, "(A&B)=B?1:0") field(INPA, "CRAT:IN20:IM01:STATUSWORD1.VAL MS") field(INPB, "0x20") } record(bi, "CRAT:IN20:IM01:TEMPHIGHSTAT") { field(FLNK, "CRAT:IN20:IM01:STATUSWORD2") field(INP, "CRAT:IN20:IM01:TEMPHIGHSTATCALC.VAL NPP MS") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ZNAM, "FAULT") field(ONAM, "OK") } record(ai, "CRAT:IN20:IM01:TEMPMAXC") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:IM01:TEMPMAX") field(INP, "@crat_elma_4slot.proto.db getTempMax(CRAT:IN20:IM01) crat-in20-im01") field(PREC, "0") field(EGU, "DegC") } record(calc, "CRAT:IN20:IM01:TEMPMAX") { field(FLNK, "CRAT:IN20:IM01:FAN1SPEED") field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:IM01:TEMPMAXC NPP MS") field(EGU, "DegF") field(PREC, "0") } record(longin, "CRAT:IN20:IM01:STATUSWORD1") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:IM01:TEMPHIGHSTATCALC") field(INP, "@crat_elma_4slot.proto.db getStatusWordA crat-in20-im01") } record(longin, "CRAT:IN20:IM01:STATUSWORD2") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:IM01:POWERSTATECALC") field(INP, "@crat_elma_4slot.proto.db getStatusWordB crat-in20-im01") } record(calc, "CRAT:IN20:IM01:FANSTATCALC") { field(SDIS, "CRAT:IN20:IM01:STATUSWORD2 NPP MS") field(FLNK, "CRAT:IN20:IM01:FANSTAT") field(CALC, "(A&B)=B?1:0") field(INPA, "CRAT:IN20:IM01:STATUSWORD2.VAL MS") field(INPB, "0x40") } record(bi, "CRAT:IN20:IM01:FANSTAT") { field(INP, "CRAT:IN20:IM01:FANSTATCALC.VAL NPP MS") field(ZSV, "MINOR") field(OSV, "NO_ALARM") field(ZNAM, "OFF") field(ONAM, "ON") } record(calc, "CRAT:IN20:IM01:POWERSTATECALC") { field(SDIS, "CRAT:IN20:IM01:STATUSWORD2 NPP MS") field(FLNK, "CRAT:IN20:IM01:POWERSTATE") field(CALC, "(A&B)=B?1:0") field(INPA, "CRAT:IN20:IM01:STATUSWORD2.VAL MS") field(INPB, "0x01") } record(bi, "CRAT:IN20:IM01:POWERSTATE") { field(FLNK, "CRAT:IN20:IM01:FANSTATCALC") field(INP, "CRAT:IN20:IM01:POWERSTATECALC.VAL NPP MS") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ZNAM, "OFF") field(ONAM, "ON") } record(stringin, "CRAT:IN20:IM01:UPTIMEHMS") { field(SDIS, "CRAT:IN20:IM01:UPTIMEDAYS.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:IM01:STATUSWORD1") } record(stringin, "CRAT:IN20:IM01:1NAME") { field(PINI, "YES") field(VAL, "IOC:IN20:IM01") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:IM01:2NAME") { field(PINI, "YES") field(VAL, "") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:IM01:3NAME") { field(PINI, "YES") field(VAL, "") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:IM01:4NAME") { field(PINI, "YES") field(VAL, "") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:IM01:LOC") { field(PINI, "YES") field(VAL, "LKG-1327") info(autosaveFields,"VAL") } record(ai, "CRAT:IN20:IM01:TYPE") { field(DESC, "Elma 4 Slot VME Crate") field(PINI, "YES") field(VAL, "5") } record(calc, "CRAT:IN20:IM01:STATSUMY") { field(SCAN, "1 second") field(CALC, "A+B+C+D+E+F+G+H+I+J+K+L=12?1:0") field(INPA, "CRAT:IN20:IM01:TEMP1.SEVR MS") field(INPB, "CRAT:IN20:IM01:TEMP2.SEVR MS") field(INPC, "CRAT:IN20:IM01:V1.SEVR MS") field(INPD, "CRAT:IN20:IM01:V2.SEVR MS") field(INPE, "CRAT:IN20:IM01:V3.SEVR MS") field(INPF, "CRAT:IN20:IM01:V4.SEVR MS") field(INPG, "CRAT:IN20:IM01:FAN1SPEED.SEVR MS") field(INPH, "CRAT:IN20:IM01:FAN2SPEED.SEVR MS") field(INPI, "CRAT:IN20:IM01:FAN3SPEED.SEVR MS") field(INPJ, "CRAT:IN20:IM01:FAN4SPEED.SEVR MS") field(INPK, "CRAT:IN20:IM01:FAN5SPEED.SEVR MS") field(INPL, "CRAT:IN20:IM01:FAN6SPEED.SEVR MS") } record(bo, "CRAT:IN20:PP01:LOGIN") { field(PINI, "YES") field(DTYP, "stream") field(OUT, "@crat_elma_4slot_v2.proto.db setLogin crat-in20-pp01") } record(ai, "CRAT:IN20:PP01:V2") { field(SCAN, "1 second") field(DTYP, "stream") field(FLNK, "CRAT:IN20:PP01:V1") field(INP, "@crat_elma_4slot_v2.proto.db getVoltage(CRAT:IN20:PP01,V1,V3,V4) crat-in20-pp01") field(PREC, "3") field(EGU, "Volts") field(HIHI, "3.465") field(LOLO, "3.2175") field(HIGH, "3.432") field(LOW, "3.234") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:PP01:V1") { field(SDIS, "CRAT:IN20:PP01:V2.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:PP01:V3") field(PREC, "3") field(EGU, "Volts") field(HIHI, "5.25") field(LOLO, "4.875") field(HIGH, "5.2") field(LOW, "4.9") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:PP01:V3") { field(SDIS, "CRAT:IN20:PP01:V2.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:PP01:V4") field(PREC, "3") field(EGU, "Volts") field(HIHI, "12.6") field(LOLO, "11.7") field(HIGH, "12.48") field(LOW, "11.76") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:PP01:V4") { field(SDIS, "CRAT:IN20:PP01:V2.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:PP01:TEMP1C") field(PREC, "3") field(EGU, "Volts") field(HIHI, "-11.76") field(LOLO, "-12.6") field(HIGH, "-11.7") field(LOW, "-12.48") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") } record(ai, "CRAT:IN20:PP01:TEMP1C") { field(DTYP, "stream") field(INP, "@crat_elma_4slot_v2.proto.db getTemp(CRAT:IN20:PP01) crat-in20-pp01") field(PREC, "0") field(EGU, "DegC") } record(ai, "CRAT:IN20:PP01:TEMP2C") { field(SDIS, "CRAT:IN20:PP01:TEMP1C.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "DegC") } record(ai, "CRAT:IN20:PP01:TEMP3C") { field(SDIS, "CRAT:IN20:PP01:TEMP1C.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "DegC") } record(ai, "CRAT:IN20:PP01:TEMP4C") { field(SDIS, "CRAT:IN20:PP01:TEMP1C.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "DegC") } record(bi, "CRAT:IN20:PP01:TEMP1OK") { field(SDIS, "CRAT:IN20:PP01:TEMP1C.SEVR") field(DISV, "3") field(DISS, "INVALID") field(ZNAM, "Upper") field(ONAM, "Ok") } record(bi, "CRAT:IN20:PP01:TEMP2OK") { field(SDIS, "CRAT:IN20:PP01:TEMP1C.SEVR") field(DISV, "3") field(DISS, "INVALID") field(ZNAM, "Upper") field(ONAM, "Ok") } record(bi, "CRAT:IN20:PP01:TEMP3OK") { field(SDIS, "CRAT:IN20:PP01:TEMP1C.SEVR") field(DISV, "3") field(DISS, "INVALID") field(ZNAM, "Upper") field(ONAM, "Ok") } record(bi, "CRAT:IN20:PP01:TEMP4OK") { field(SDIS, "CRAT:IN20:PP01:TEMP1C.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:PP01:TEMPSTATCALC") field(ZNAM, "Upper") field(ONAM, "Ok") } record(calc, "CRAT:IN20:PP01:TEMPSTATCALC") { #field(SDIS, "CRAT:IN20:PP01:STATUSWORD2 NPP MS") field(FLNK, "CRAT:IN20:PP01:TEMPHIGHSTAT") field(CALC, "(A&&B&&C&&D)") field(INPA, "CRAT:IN20:PP01:FAN1OK.VAL MS") field(INPB, "CRAT:IN20:PP01:FAN2OK.VAL MS") field(INPC, "CRAT:IN20:PP01:FAN3OK.VAL MS") field(INPD, "CRAT:IN20:PP01:FAN4OK.VAL MS") } record(bi, "CRAT:IN20:PP01:TEMPHIGHSTAT") { field(INP, "CRAT:IN20:PP01:TEMPSTATCALC NPP MS") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ZNAM, "FAULT") field(ONAM, "OK") } record(ai, "CRAT:IN20:PP01:TEMPSENS") { field(SDIS, "CRAT:IN20:PP01:TEMP1C.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:PP01:TEMP1") field(PREC, "0") field(EGU, "DegC") } record(calc, "CRAT:IN20:PP01:TEMP1") { field(FLNK, "CRAT:IN20:PP01:TEMP2") field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:PP01:TEMP1C NPP MS") field(EGU, "DegF") field(PREC, "0") field(HIHI, "145") field(HIGH, "137") field(HHSV, "MAJOR") field(HSV, "MINOR") } record(calc, "CRAT:IN20:PP01:TEMP2") { field(FLNK, "CRAT:IN20:PP01:TEMP3") field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:PP01:TEMP2C NPP MS") field(EGU, "DegF") field(PREC, "0") field(HIHI, "145") field(HIGH, "137") field(HHSV, "MAJOR") field(HSV, "MINOR") } record(calc, "CRAT:IN20:PP01:TEMP3") { field(FLNK, "CRAT:IN20:PP01:TEMP4") field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:PP01:TEMP3C NPP MS") field(EGU, "DegF") field(PREC, "0") field(HIHI, "145") field(HIGH, "137") field(HHSV, "MAJOR") field(HSV, "MINOR") } record(calc, "CRAT:IN20:PP01:TEMP4") { field(FLNK, "CRAT:IN20:PP01:TEMPMAXC") field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:PP01:TEMP4C NPP MS") field(EGU, "DegF") field(PREC, "0") field(HIHI, "145") field(HIGH, "137") field(HHSV, "MAJOR") field(HSV, "MINOR") } record(ai, "CRAT:IN20:PP01:TEMPMAXC") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:PP01:TEMPMAX") field(INP, "@crat_elma_4slot_v2.proto.db getSensorMax(CRAT:IN20:PP01) crat-in20-pp01") field(PREC, "0") field(EGU, "DegC") } record(calc, "CRAT:IN20:PP01:TEMPMAX") { field(FLNK, "CRAT:IN20:PP01:FAN1SPEED") field(CALC, "A*1.8+32") field(INPA, "CRAT:IN20:PP01:TEMPMAXC NPP MS") field(EGU, "DegF") field(PREC, "0") } record(ai, "CRAT:IN20:PP01:FAN1SPEED") { field(DTYP, "stream") field(INP, "@crat_elma_4slot_v2.proto.db getFan(CRAT:IN20:PP01) crat-in20-pp01") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:PP01:FAN2SPEED") { field(SDIS, "CRAT:IN20:PP01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:PP01:FAN3SPEED") { field(SDIS, "CRAT:IN20:PP01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(ai, "CRAT:IN20:PP01:FAN4SPEED") { field(SDIS, "CRAT:IN20:PP01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(PREC, "0") field(EGU, "RPM") field(LOLO, "700") field(LLSV, "MAJOR") } record(bi, "CRAT:IN20:PP01:FAN1OK") { field(SDIS, "CRAT:IN20:PP01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(ZNAM, "Lower") field(ONAM, "Ok") } record(bi, "CRAT:IN20:PP01:FAN2OK") { field(SDIS, "CRAT:IN20:PP01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(ZNAM, "Lower") field(ONAM, "Ok") } record(bi, "CRAT:IN20:PP01:FAN3OK") { field(SDIS, "CRAT:IN20:PP01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(ZNAM, "Lower") field(ONAM, "Ok") } record(bi, "CRAT:IN20:PP01:FAN4OK") { field(SDIS, "CRAT:IN20:PP01:FAN1SPEED.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:PP01:FANSTATCALC") field(ZNAM, "Lower") field(ONAM, "Ok") } record(calc, "CRAT:IN20:PP01:FANSTATCALC") { #field(SDIS, "CRAT:IN20:PP01:STATUSWORD2 NPP MS") field(FLNK, "CRAT:IN20:PP01:FANSTAT") field(CALC, "(A&&B&&C&&D)") field(INPA, "CRAT:IN20:PP01:FAN1OK.VAL MS") field(INPB, "CRAT:IN20:PP01:FAN2OK.VAL MS") field(INPC, "CRAT:IN20:PP01:FAN3OK.VAL MS") field(INPD, "CRAT:IN20:PP01:FAN4OK.VAL MS") } record(bi, "CRAT:IN20:PP01:FANSTAT") { field(INP, "CRAT:IN20:PP01:FANSTATCALC NPP MS") field(ZSV, "MINOR") field(OSV, "NO_ALARM") field(ZNAM, "OFF") field(ONAM, "ON") field(FLNK, "CRAT:IN20:PP01:UPTIMEDAYS") } record(ai, "CRAT:IN20:PP01:UPTIMEDAYS") { field(SCAN, "Passive") field(DTYP, "stream") field(INP, "@crat_elma_4slot_v2.proto.db getUptime(CRAT:IN20:PP01) crat-in20-pp01") field(EGU, "days") } record(stringin, "CRAT:IN20:PP01:UPTIMEHMS") { field(SDIS, "CRAT:IN20:PP01:UPTIMEDAYS.SEVR") field(DISV, "3") field(DISS, "INVALID") field(FLNK, "CRAT:IN20:PP01:STATUSWORD2") } record(longin, "CRAT:IN20:PP01:STATUSWORD2") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:PP01:POWERSTATE") field(INP, "@crat_elma_4slot_v2.proto.db getPowerState crat-in20-pp01") } record(bi, "CRAT:IN20:PP01:POWERSTATE") { #field(FLNK, "CRAT:IN20:PP01:FANSTATCALC") field(INP, "CRAT:IN20:PP01:STATUSWORD2.VAL NPP MS") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") field(ZNAM, "ON") field(ONAM, "OFF") } record(stringin, "CRAT:IN20:PP01:1NAME") { field(PINI, "YES") field(VAL, "IOC:IN20:PP01") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:PP01:2NAME") { field(PINI, "YES") field(VAL, "") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:PP01:3NAME") { field(PINI, "YES") field(VAL, "") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:PP01:4NAME") { field(PINI, "YES") field(VAL, "") info(autosaveFields,"VAL") } record(stringin, "CRAT:IN20:PP01:LOC") { field(PINI, "YES") field(VAL, "LKG-1940") info(autosaveFields,"VAL") } record(ai, "CRAT:IN20:PP01:TYPE") { field(DESC, "Elma 4 Slot VME Crate v2") field(PINI, "YES") field(VAL, "29") } record(bo, "CRAT:IN20:PP01:POWEROFF") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:PP01:POWEROFFSEQ") field(OUT, "@crat_elma_4slot_v2.proto.db setPowerOff crat-in20-pp01") } record(bo, "CRAT:IN20:PP01:POWERON") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:PP01:POWERONSEQ") field(OUT, "@crat_elma_4slot_v2.proto.db setPowerOn crat-in20-pp01") } record(seq, "CRAT:IN20:PP01:POWEROFFSEQ") { field(SELM, "All") field(DOL1, "1") field(LNK1, "CRAT:IN20:PP01:POWERMSG PP") field(DLY2, "5") field(DOL2, "0") field(LNK2, "CRAT:IN20:PP01:POWERMSG PP") } record(mbbo, "CRAT:IN20:PP01:POWERMSG") { field(ZRVL, "0") field(ONVL, "1") field(TWVL, "2") field(THVL, "3") field(ONST, "TURNING_OFF") field(TWST, "TURNING_ON") field(THST, "RESETTING") field(ZRSV, "NO_ALARM") field(ONSV, "MINOR") field(TWSV, "MINOR") field(THSV, "MINOR") } record(bo, "CRAT:IN20:PP01:HARDRESET") { field(DTYP, "stream") field(FLNK, "CRAT:IN20:PP01:HARDRESETSEQ") field(OUT, "@crat_elma_4slot_v2.proto.db setPowerReset crat-in20-pp01") } record(seq, "CRAT:IN20:PP01:POWERONSEQ") { field(SELM, "All") field(DOL1, "2") field(LNK1, "CRAT:IN20:PP01:POWERMSG PP") field(DLY2, "5") field(DOL2, "0") field(LNK2, "CRAT:IN20:PP01:POWERMSG PP") } record(seq, "CRAT:IN20:PP01:HARDRESETSEQ") { field(SELM, "All") field(DOL1, "3") field(LNK1, "CRAT:IN20:PP01:POWERMSG PP") field(DLY2, "5") field(DOL2, "0") field(LNK2, "CRAT:IN20:PP01:POWERMSG PP") } record(calc, "CRAT:IN20:PP01:STATSUMY") { field(SCAN, "1 second") field(CALC, "A+B+C+D+E+F+G+H+I+J+K+L=12?1:0") field(INPA, "CRAT:IN20:PP01:TEMP1.SEVR MS") field(INPB, "CRAT:IN20:PP01:TEMP2.SEVR MS") field(INPC, "CRAT:IN20:PP01:TEMP3.SEVR MS") field(INPD, "CRAT:IN20:PP01:TEMP4.SEVR MS") field(INPE, "CRAT:IN20:PP01:V1.SEVR MS") field(INPF, "CRAT:IN20:PP01:V2.SEVR MS") field(INPG, "CRAT:IN20:PP01:V3.SEVR MS") field(INPH, "CRAT:IN20:PP01:V4.SEVR MS") field(INPI, "CRAT:IN20:PP01:FAN1SPEED.SEVR MS") field(INPJ, "CRAT:IN20:PP01:FAN2SPEED.SEVR MS") field(INPK, "CRAT:IN20:PP01:FAN3SPEED.SEVR MS") field(INPL, "CRAT:IN20:PP01:FAN4SPEED.SEVR MS") }