record(stringin, "ACSW:UNDS:NW01:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:UNDS:NW01) acsw-unds-nw01")
  field(FLNK, "ACSW:UNDS:NW01:GETINFO")
}

record(stringin, "ACSW:UNDS:NW01:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:UNDS:NW01) acsw-unds-nw01")
  field(FLNK, "ACSW:UNDS:NW01:GETINIT")
}

record(stringin, "ACSW:UNDS:NW01:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:UNDS:NW01:NETFWVERSION")
  field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW01:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:UNDS:NW01:SITEID")
  field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW01:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:UNDS:NW01:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState8(ACSW:UNDS:NW01) acsw-unds-nw01")
}

record(stringin, "ACSW:UNDS:NW01:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState8(ACSW:UNDS:NW01) acsw-unds-nw01")
}

record(ai, "ACSW:UNDS:NW01:TYPE") {
  field(DESC, "APC 8 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "10")
}

record(stringin, "ACSW:UNDS:NW01:LOC") {
  field(PINI, "YES")
  field(VAL, "B920-01S")
  field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:UNDS:NW01:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-unds-nw01")
}

record(calcout, "ACSW:UNDS:NW01:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:UNDS:NW01:DISCONN.DISA")
  field(INPB, "ACSW:UNDS:NW01:DISCONN.DISV")
  field(INPC, "ACSW:UNDS:NW01:GETSTATUS.DISA")
  field(INPD, "ACSW:UNDS:NW01:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:UNDS:NW01:CONNSTA PP")
}

record(bi, "ACSW:UNDS:NW01:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:UNDS:NW01:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:UNDS:NW01:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:UNDS:NW01:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:UNDS:NW01:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:UNDS:NW01:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:UNDS:NW01:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:UNDS:NW01:UPTIMEHOUR") {
  field(FLNK, "ACSW:UNDS:NW01:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:UNDS:NW01:UPTIMEDAY") {
  field(FLNK, "ACSW:UNDS:NW01:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:UNDS:NW01:UPTIMEMINUTE") {
  field(FLNK, "ACSW:UNDS:NW01:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:UNDS:NW01:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW01:1POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW01:1POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW01:1POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW01:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW01:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW01:1POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW01:1POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW01:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW01:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-unds-nw01")
}

record(bo, "ACSW:UNDS:NW01:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-unds-nw01")
}

record(bo, "ACSW:UNDS:NW01:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-unds-nw01")
}

record(stringin, "ACSW:UNDS:NW01:1NAMESET") {
  field(FLNK, "ACSW:UNDS:NW01:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW01:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-unds-nw01")
  field(DOL, "ACSW:UNDS:NW01:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW01:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-unds-nw01")
  field(FLNK, "ACSW:UNDS:NW01:GETINIT")
}

record(bo, "ACSW:UNDS:NW01:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-unds-nw01")
  field(FLNK, "ACSW:UNDS:NW01:GETINIT")
}

record(stringin, "ACSW:UNDS:NW01:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW01:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW01:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW01:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW01:1INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW01:1INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW01:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW01:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW01:2POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW01:2POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW01:2POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW01:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW01:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW01:2POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW01:2POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW01:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW01:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-unds-nw01")
}

record(bo, "ACSW:UNDS:NW01:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-unds-nw01")
}

record(bo, "ACSW:UNDS:NW01:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-unds-nw01")
}

record(stringin, "ACSW:UNDS:NW01:2NAMESET") {
  field(FLNK, "ACSW:UNDS:NW01:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW01:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-unds-nw01")
  field(DOL, "ACSW:UNDS:NW01:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW01:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-unds-nw01")
  field(FLNK, "ACSW:UNDS:NW01:GETINIT")
}

record(bo, "ACSW:UNDS:NW01:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-unds-nw01")
  field(FLNK, "ACSW:UNDS:NW01:GETINIT")
}

record(stringin, "ACSW:UNDS:NW01:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW01:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW01:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW01:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW01:2INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW01:2INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW01:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW01:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW01:3POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW01:3POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW01:3POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW01:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW01:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW01:3POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW01:3POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW01:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW01:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-unds-nw01")
}

record(bo, "ACSW:UNDS:NW01:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-unds-nw01")
}

record(bo, "ACSW:UNDS:NW01:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-unds-nw01")
}

record(stringin, "ACSW:UNDS:NW01:3NAMESET") {
  field(FLNK, "ACSW:UNDS:NW01:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW01:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-unds-nw01")
  field(DOL, "ACSW:UNDS:NW01:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW01:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-unds-nw01")
  field(FLNK, "ACSW:UNDS:NW01:GETINIT")
}

record(bo, "ACSW:UNDS:NW01:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-unds-nw01")
  field(FLNK, "ACSW:UNDS:NW01:GETINIT")
}

record(stringin, "ACSW:UNDS:NW01:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW01:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW01:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW01:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW01:3INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW01:3INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW01:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW01:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW01:4POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW01:4POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW01:4POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW01:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW01:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW01:4POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW01:4POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW01:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW01:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-unds-nw01")
}

record(bo, "ACSW:UNDS:NW01:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-unds-nw01")
}

record(bo, "ACSW:UNDS:NW01:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-unds-nw01")
}

record(stringin, "ACSW:UNDS:NW01:4NAMESET") {
  field(FLNK, "ACSW:UNDS:NW01:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW01:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-unds-nw01")
  field(DOL, "ACSW:UNDS:NW01:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW01:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-unds-nw01")
  field(FLNK, "ACSW:UNDS:NW01:GETINIT")
}

record(bo, "ACSW:UNDS:NW01:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-unds-nw01")
  field(FLNK, "ACSW:UNDS:NW01:GETINIT")
}

record(stringin, "ACSW:UNDS:NW01:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW01:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW01:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW01:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW01:4INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW01:4INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW01:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW01:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW01:5POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW01:5POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW01:5POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW01:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW01:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW01:5POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW01:5POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW01:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW01:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-unds-nw01")
}

record(bo, "ACSW:UNDS:NW01:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-unds-nw01")
}

record(bo, "ACSW:UNDS:NW01:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-unds-nw01")
}

record(stringin, "ACSW:UNDS:NW01:5NAMESET") {
  field(FLNK, "ACSW:UNDS:NW01:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW01:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-unds-nw01")
  field(DOL, "ACSW:UNDS:NW01:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW01:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-unds-nw01")
  field(FLNK, "ACSW:UNDS:NW01:GETINIT")
}

record(bo, "ACSW:UNDS:NW01:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-unds-nw01")
  field(FLNK, "ACSW:UNDS:NW01:GETINIT")
}

record(stringin, "ACSW:UNDS:NW01:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW01:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW01:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW01:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW01:5INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW01:5INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW01:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW01:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW01:6POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW01:6POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW01:6POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW01:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW01:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW01:6POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW01:6POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW01:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW01:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-unds-nw01")
}

record(bo, "ACSW:UNDS:NW01:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-unds-nw01")
}

record(bo, "ACSW:UNDS:NW01:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-unds-nw01")
}

record(stringin, "ACSW:UNDS:NW01:6NAMESET") {
  field(FLNK, "ACSW:UNDS:NW01:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW01:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-unds-nw01")
  field(DOL, "ACSW:UNDS:NW01:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW01:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-unds-nw01")
  field(FLNK, "ACSW:UNDS:NW01:GETINIT")
}

record(bo, "ACSW:UNDS:NW01:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-unds-nw01")
  field(FLNK, "ACSW:UNDS:NW01:GETINIT")
}

record(stringin, "ACSW:UNDS:NW01:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW01:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW01:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW01:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW01:6INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW01:6INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW01:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW01:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW01:7POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW01:7POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW01:7POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW01:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW01:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW01:7POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW01:7POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW01:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW01:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-unds-nw01")
}

record(bo, "ACSW:UNDS:NW01:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-unds-nw01")
}

record(bo, "ACSW:UNDS:NW01:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-unds-nw01")
}

record(stringin, "ACSW:UNDS:NW01:7NAMESET") {
  field(FLNK, "ACSW:UNDS:NW01:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW01:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-unds-nw01")
  field(DOL, "ACSW:UNDS:NW01:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW01:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-unds-nw01")
  field(FLNK, "ACSW:UNDS:NW01:GETINIT")
}

record(bo, "ACSW:UNDS:NW01:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-unds-nw01")
  field(FLNK, "ACSW:UNDS:NW01:GETINIT")
}

record(stringin, "ACSW:UNDS:NW01:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW01:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW01:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW01:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW01:7INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW01:7INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW01:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW01:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW01:8POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW01:8POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW01:8POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW01:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW01:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW01:8POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW01:8POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW01:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW01:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-unds-nw01")
}

record(bo, "ACSW:UNDS:NW01:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-unds-nw01")
}

record(bo, "ACSW:UNDS:NW01:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-unds-nw01")
}

record(stringin, "ACSW:UNDS:NW01:8NAMESET") {
  field(FLNK, "ACSW:UNDS:NW01:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW01:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-unds-nw01")
  field(DOL, "ACSW:UNDS:NW01:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW01:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-unds-nw01")
  field(FLNK, "ACSW:UNDS:NW01:GETINIT")
}

record(bo, "ACSW:UNDS:NW01:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-unds-nw01")
  field(FLNK, "ACSW:UNDS:NW01:GETINIT")
}

record(stringin, "ACSW:UNDS:NW01:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW01:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW01:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW01:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW01:8INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW01:8INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW01:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW01:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW26:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:UNDS:NW26) acsw-unds-nw26")
  field(FLNK, "ACSW:UNDS:NW26:GETINFO")
}

record(stringin, "ACSW:UNDS:NW26:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:UNDS:NW26) acsw-unds-nw26")
  field(FLNK, "ACSW:UNDS:NW26:GETINIT")
}

record(stringin, "ACSW:UNDS:NW26:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:UNDS:NW26:NETFWVERSION")
  field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW26:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:UNDS:NW26:SITEID")
  field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW26:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:UNDS:NW26:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState8(ACSW:UNDS:NW26) acsw-unds-nw26")
}

record(stringin, "ACSW:UNDS:NW26:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState8(ACSW:UNDS:NW26) acsw-unds-nw26")
}

record(ai, "ACSW:UNDS:NW26:TYPE") {
  field(DESC, "APC 8 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "10")
}

record(stringin, "ACSW:UNDS:NW26:LOC") {
  field(PINI, "YES")
  field(VAL, "B920-26S")
  field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:UNDS:NW26:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-unds-nw26")
}

record(calcout, "ACSW:UNDS:NW26:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:UNDS:NW26:DISCONN.DISA")
  field(INPB, "ACSW:UNDS:NW26:DISCONN.DISV")
  field(INPC, "ACSW:UNDS:NW26:GETSTATUS.DISA")
  field(INPD, "ACSW:UNDS:NW26:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:UNDS:NW26:CONNSTA PP")
}

record(bi, "ACSW:UNDS:NW26:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:UNDS:NW26:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:UNDS:NW26:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:UNDS:NW26:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:UNDS:NW26:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:UNDS:NW26:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:UNDS:NW26:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:UNDS:NW26:UPTIMEHOUR") {
  field(FLNK, "ACSW:UNDS:NW26:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:UNDS:NW26:UPTIMEDAY") {
  field(FLNK, "ACSW:UNDS:NW26:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:UNDS:NW26:UPTIMEMINUTE") {
  field(FLNK, "ACSW:UNDS:NW26:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:UNDS:NW26:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW26:1POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW26:1POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW26:1POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW26:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW26:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW26:1POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW26:1POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW26:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW26:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-unds-nw26")
}

record(bo, "ACSW:UNDS:NW26:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-unds-nw26")
}

record(bo, "ACSW:UNDS:NW26:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-unds-nw26")
}

record(stringin, "ACSW:UNDS:NW26:1NAMESET") {
  field(FLNK, "ACSW:UNDS:NW26:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW26:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-unds-nw26")
  field(DOL, "ACSW:UNDS:NW26:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW26:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-unds-nw26")
  field(FLNK, "ACSW:UNDS:NW26:GETINIT")
}

record(bo, "ACSW:UNDS:NW26:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-unds-nw26")
  field(FLNK, "ACSW:UNDS:NW26:GETINIT")
}

record(stringin, "ACSW:UNDS:NW26:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW26:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW26:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW26:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW26:1INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW26:1INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW26:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW26:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW26:2POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW26:2POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW26:2POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW26:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW26:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW26:2POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW26:2POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW26:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW26:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-unds-nw26")
}

record(bo, "ACSW:UNDS:NW26:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-unds-nw26")
}

record(bo, "ACSW:UNDS:NW26:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-unds-nw26")
}

record(stringin, "ACSW:UNDS:NW26:2NAMESET") {
  field(FLNK, "ACSW:UNDS:NW26:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW26:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-unds-nw26")
  field(DOL, "ACSW:UNDS:NW26:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW26:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-unds-nw26")
  field(FLNK, "ACSW:UNDS:NW26:GETINIT")
}

record(bo, "ACSW:UNDS:NW26:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-unds-nw26")
  field(FLNK, "ACSW:UNDS:NW26:GETINIT")
}

record(stringin, "ACSW:UNDS:NW26:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW26:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW26:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW26:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW26:2INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW26:2INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW26:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW26:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW26:3POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW26:3POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW26:3POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW26:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW26:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW26:3POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW26:3POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW26:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW26:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-unds-nw26")
}

record(bo, "ACSW:UNDS:NW26:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-unds-nw26")
}

record(bo, "ACSW:UNDS:NW26:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-unds-nw26")
}

record(stringin, "ACSW:UNDS:NW26:3NAMESET") {
  field(FLNK, "ACSW:UNDS:NW26:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW26:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-unds-nw26")
  field(DOL, "ACSW:UNDS:NW26:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW26:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-unds-nw26")
  field(FLNK, "ACSW:UNDS:NW26:GETINIT")
}

record(bo, "ACSW:UNDS:NW26:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-unds-nw26")
  field(FLNK, "ACSW:UNDS:NW26:GETINIT")
}

record(stringin, "ACSW:UNDS:NW26:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW26:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW26:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW26:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW26:3INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW26:3INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW26:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW26:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW26:4POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW26:4POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW26:4POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW26:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW26:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW26:4POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW26:4POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW26:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW26:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-unds-nw26")
}

record(bo, "ACSW:UNDS:NW26:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-unds-nw26")
}

record(bo, "ACSW:UNDS:NW26:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-unds-nw26")
}

record(stringin, "ACSW:UNDS:NW26:4NAMESET") {
  field(FLNK, "ACSW:UNDS:NW26:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW26:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-unds-nw26")
  field(DOL, "ACSW:UNDS:NW26:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW26:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-unds-nw26")
  field(FLNK, "ACSW:UNDS:NW26:GETINIT")
}

record(bo, "ACSW:UNDS:NW26:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-unds-nw26")
  field(FLNK, "ACSW:UNDS:NW26:GETINIT")
}

record(stringin, "ACSW:UNDS:NW26:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW26:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW26:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW26:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW26:4INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW26:4INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW26:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW26:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW26:5POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW26:5POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW26:5POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW26:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW26:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW26:5POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW26:5POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW26:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW26:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-unds-nw26")
}

record(bo, "ACSW:UNDS:NW26:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-unds-nw26")
}

record(bo, "ACSW:UNDS:NW26:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-unds-nw26")
}

record(stringin, "ACSW:UNDS:NW26:5NAMESET") {
  field(FLNK, "ACSW:UNDS:NW26:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW26:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-unds-nw26")
  field(DOL, "ACSW:UNDS:NW26:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW26:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-unds-nw26")
  field(FLNK, "ACSW:UNDS:NW26:GETINIT")
}

record(bo, "ACSW:UNDS:NW26:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-unds-nw26")
  field(FLNK, "ACSW:UNDS:NW26:GETINIT")
}

record(stringin, "ACSW:UNDS:NW26:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW26:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW26:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW26:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW26:5INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW26:5INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW26:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW26:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW26:6POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW26:6POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW26:6POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW26:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW26:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW26:6POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW26:6POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW26:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW26:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-unds-nw26")
}

record(bo, "ACSW:UNDS:NW26:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-unds-nw26")
}

record(bo, "ACSW:UNDS:NW26:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-unds-nw26")
}

record(stringin, "ACSW:UNDS:NW26:6NAMESET") {
  field(FLNK, "ACSW:UNDS:NW26:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW26:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-unds-nw26")
  field(DOL, "ACSW:UNDS:NW26:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW26:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-unds-nw26")
  field(FLNK, "ACSW:UNDS:NW26:GETINIT")
}

record(bo, "ACSW:UNDS:NW26:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-unds-nw26")
  field(FLNK, "ACSW:UNDS:NW26:GETINIT")
}

record(stringin, "ACSW:UNDS:NW26:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW26:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW26:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW26:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW26:6INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW26:6INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW26:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW26:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW26:7POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW26:7POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW26:7POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW26:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW26:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW26:7POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW26:7POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW26:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW26:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-unds-nw26")
}

record(bo, "ACSW:UNDS:NW26:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-unds-nw26")
}

record(bo, "ACSW:UNDS:NW26:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-unds-nw26")
}

record(stringin, "ACSW:UNDS:NW26:7NAMESET") {
  field(FLNK, "ACSW:UNDS:NW26:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW26:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-unds-nw26")
  field(DOL, "ACSW:UNDS:NW26:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW26:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-unds-nw26")
  field(FLNK, "ACSW:UNDS:NW26:GETINIT")
}

record(bo, "ACSW:UNDS:NW26:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-unds-nw26")
  field(FLNK, "ACSW:UNDS:NW26:GETINIT")
}

record(stringin, "ACSW:UNDS:NW26:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW26:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW26:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW26:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW26:7INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW26:7INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW26:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW26:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW26:8POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW26:8POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW26:8POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW26:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW26:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW26:8POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW26:8POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW26:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW26:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-unds-nw26")
}

record(bo, "ACSW:UNDS:NW26:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-unds-nw26")
}

record(bo, "ACSW:UNDS:NW26:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-unds-nw26")
}

record(stringin, "ACSW:UNDS:NW26:8NAMESET") {
  field(FLNK, "ACSW:UNDS:NW26:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW26:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-unds-nw26")
  field(DOL, "ACSW:UNDS:NW26:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW26:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-unds-nw26")
  field(FLNK, "ACSW:UNDS:NW26:GETINIT")
}

record(bo, "ACSW:UNDS:NW26:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-unds-nw26")
  field(FLNK, "ACSW:UNDS:NW26:GETINIT")
}

record(stringin, "ACSW:UNDS:NW26:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW26:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW26:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW26:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW26:8INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW26:8INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW26:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW26:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW27:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:UNDS:NW27) acsw-unds-nw27")
  field(FLNK, "ACSW:UNDS:NW27:GETINFO")
}

record(stringin, "ACSW:UNDS:NW27:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:UNDS:NW27) acsw-unds-nw27")
  field(FLNK, "ACSW:UNDS:NW27:GETINIT")
}

record(stringin, "ACSW:UNDS:NW27:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:UNDS:NW27:NETFWVERSION")
  field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW27:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:UNDS:NW27:SITEID")
  field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW27:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:UNDS:NW27:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState8(ACSW:UNDS:NW27) acsw-unds-nw27")
}

record(stringin, "ACSW:UNDS:NW27:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState8(ACSW:UNDS:NW27) acsw-unds-nw27")
}

record(ai, "ACSW:UNDS:NW27:TYPE") {
  field(DESC, "APC 8 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "10")
}

record(stringin, "ACSW:UNDS:NW27:LOC") {
  field(PINI, "YES")
  field(VAL, "B920-27S")
  field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:UNDS:NW27:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-unds-nw27")
}

record(calcout, "ACSW:UNDS:NW27:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:UNDS:NW27:DISCONN.DISA")
  field(INPB, "ACSW:UNDS:NW27:DISCONN.DISV")
  field(INPC, "ACSW:UNDS:NW27:GETSTATUS.DISA")
  field(INPD, "ACSW:UNDS:NW27:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:UNDS:NW27:CONNSTA PP")
}

record(bi, "ACSW:UNDS:NW27:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:UNDS:NW27:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:UNDS:NW27:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:UNDS:NW27:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:UNDS:NW27:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:UNDS:NW27:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:UNDS:NW27:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:UNDS:NW27:UPTIMEHOUR") {
  field(FLNK, "ACSW:UNDS:NW27:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:UNDS:NW27:UPTIMEDAY") {
  field(FLNK, "ACSW:UNDS:NW27:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:UNDS:NW27:UPTIMEMINUTE") {
  field(FLNK, "ACSW:UNDS:NW27:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:UNDS:NW27:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW27:1POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW27:1POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW27:1POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW27:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW27:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW27:1POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW27:1POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW27:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW27:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-unds-nw27")
}

record(bo, "ACSW:UNDS:NW27:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-unds-nw27")
}

record(bo, "ACSW:UNDS:NW27:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-unds-nw27")
}

record(stringin, "ACSW:UNDS:NW27:1NAMESET") {
  field(FLNK, "ACSW:UNDS:NW27:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW27:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-unds-nw27")
  field(DOL, "ACSW:UNDS:NW27:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW27:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-unds-nw27")
  field(FLNK, "ACSW:UNDS:NW27:GETINIT")
}

record(bo, "ACSW:UNDS:NW27:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-unds-nw27")
  field(FLNK, "ACSW:UNDS:NW27:GETINIT")
}

record(stringin, "ACSW:UNDS:NW27:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW27:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW27:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW27:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW27:1INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW27:1INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW27:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW27:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW27:2POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW27:2POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW27:2POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW27:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW27:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW27:2POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW27:2POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW27:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW27:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-unds-nw27")
}

record(bo, "ACSW:UNDS:NW27:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-unds-nw27")
}

record(bo, "ACSW:UNDS:NW27:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-unds-nw27")
}

record(stringin, "ACSW:UNDS:NW27:2NAMESET") {
  field(FLNK, "ACSW:UNDS:NW27:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW27:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-unds-nw27")
  field(DOL, "ACSW:UNDS:NW27:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW27:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-unds-nw27")
  field(FLNK, "ACSW:UNDS:NW27:GETINIT")
}

record(bo, "ACSW:UNDS:NW27:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-unds-nw27")
  field(FLNK, "ACSW:UNDS:NW27:GETINIT")
}

record(stringin, "ACSW:UNDS:NW27:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW27:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW27:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW27:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW27:2INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW27:2INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW27:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW27:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW27:3POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW27:3POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW27:3POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW27:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW27:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW27:3POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW27:3POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW27:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW27:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-unds-nw27")
}

record(bo, "ACSW:UNDS:NW27:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-unds-nw27")
}

record(bo, "ACSW:UNDS:NW27:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-unds-nw27")
}

record(stringin, "ACSW:UNDS:NW27:3NAMESET") {
  field(FLNK, "ACSW:UNDS:NW27:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW27:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-unds-nw27")
  field(DOL, "ACSW:UNDS:NW27:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW27:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-unds-nw27")
  field(FLNK, "ACSW:UNDS:NW27:GETINIT")
}

record(bo, "ACSW:UNDS:NW27:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-unds-nw27")
  field(FLNK, "ACSW:UNDS:NW27:GETINIT")
}

record(stringin, "ACSW:UNDS:NW27:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW27:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW27:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW27:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW27:3INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW27:3INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW27:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW27:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW27:4POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW27:4POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW27:4POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW27:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW27:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW27:4POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW27:4POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW27:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW27:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-unds-nw27")
}

record(bo, "ACSW:UNDS:NW27:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-unds-nw27")
}

record(bo, "ACSW:UNDS:NW27:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-unds-nw27")
}

record(stringin, "ACSW:UNDS:NW27:4NAMESET") {
  field(FLNK, "ACSW:UNDS:NW27:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW27:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-unds-nw27")
  field(DOL, "ACSW:UNDS:NW27:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW27:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-unds-nw27")
  field(FLNK, "ACSW:UNDS:NW27:GETINIT")
}

record(bo, "ACSW:UNDS:NW27:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-unds-nw27")
  field(FLNK, "ACSW:UNDS:NW27:GETINIT")
}

record(stringin, "ACSW:UNDS:NW27:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW27:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW27:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW27:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW27:4INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW27:4INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW27:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW27:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW27:5POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW27:5POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW27:5POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW27:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW27:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW27:5POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW27:5POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW27:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW27:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-unds-nw27")
}

record(bo, "ACSW:UNDS:NW27:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-unds-nw27")
}

record(bo, "ACSW:UNDS:NW27:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-unds-nw27")
}

record(stringin, "ACSW:UNDS:NW27:5NAMESET") {
  field(FLNK, "ACSW:UNDS:NW27:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW27:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-unds-nw27")
  field(DOL, "ACSW:UNDS:NW27:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW27:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-unds-nw27")
  field(FLNK, "ACSW:UNDS:NW27:GETINIT")
}

record(bo, "ACSW:UNDS:NW27:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-unds-nw27")
  field(FLNK, "ACSW:UNDS:NW27:GETINIT")
}

record(stringin, "ACSW:UNDS:NW27:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW27:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW27:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW27:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW27:5INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW27:5INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW27:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW27:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW27:6POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW27:6POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW27:6POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW27:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW27:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW27:6POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW27:6POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW27:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW27:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-unds-nw27")
}

record(bo, "ACSW:UNDS:NW27:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-unds-nw27")
}

record(bo, "ACSW:UNDS:NW27:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-unds-nw27")
}

record(stringin, "ACSW:UNDS:NW27:6NAMESET") {
  field(FLNK, "ACSW:UNDS:NW27:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW27:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-unds-nw27")
  field(DOL, "ACSW:UNDS:NW27:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW27:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-unds-nw27")
  field(FLNK, "ACSW:UNDS:NW27:GETINIT")
}

record(bo, "ACSW:UNDS:NW27:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-unds-nw27")
  field(FLNK, "ACSW:UNDS:NW27:GETINIT")
}

record(stringin, "ACSW:UNDS:NW27:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW27:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW27:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW27:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW27:6INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW27:6INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW27:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW27:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW27:7POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW27:7POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW27:7POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW27:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW27:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW27:7POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW27:7POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW27:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW27:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-unds-nw27")
}

record(bo, "ACSW:UNDS:NW27:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-unds-nw27")
}

record(bo, "ACSW:UNDS:NW27:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-unds-nw27")
}

record(stringin, "ACSW:UNDS:NW27:7NAMESET") {
  field(FLNK, "ACSW:UNDS:NW27:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW27:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-unds-nw27")
  field(DOL, "ACSW:UNDS:NW27:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW27:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-unds-nw27")
  field(FLNK, "ACSW:UNDS:NW27:GETINIT")
}

record(bo, "ACSW:UNDS:NW27:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-unds-nw27")
  field(FLNK, "ACSW:UNDS:NW27:GETINIT")
}

record(stringin, "ACSW:UNDS:NW27:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW27:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW27:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW27:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW27:7INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW27:7INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW27:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW27:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW27:8POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW27:8POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW27:8POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW27:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW27:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW27:8POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW27:8POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW27:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW27:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-unds-nw27")
}

record(bo, "ACSW:UNDS:NW27:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-unds-nw27")
}

record(bo, "ACSW:UNDS:NW27:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-unds-nw27")
}

record(stringin, "ACSW:UNDS:NW27:8NAMESET") {
  field(FLNK, "ACSW:UNDS:NW27:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW27:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-unds-nw27")
  field(DOL, "ACSW:UNDS:NW27:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW27:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-unds-nw27")
  field(FLNK, "ACSW:UNDS:NW27:GETINIT")
}

record(bo, "ACSW:UNDS:NW27:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-unds-nw27")
  field(FLNK, "ACSW:UNDS:NW27:GETINIT")
}

record(stringin, "ACSW:UNDS:NW27:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW27:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW27:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW27:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW27:8INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW27:8INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW27:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW27:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW28:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:UNDS:NW28) acsw-unds-nw28")
  field(FLNK, "ACSW:UNDS:NW28:GETINFO")
}

record(stringin, "ACSW:UNDS:NW28:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:UNDS:NW28) acsw-unds-nw28")
  field(FLNK, "ACSW:UNDS:NW28:GETINIT")
}

record(stringin, "ACSW:UNDS:NW28:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:UNDS:NW28:NETFWVERSION")
  field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW28:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:UNDS:NW28:SITEID")
  field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW28:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:UNDS:NW28:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState8(ACSW:UNDS:NW28) acsw-unds-nw28")
}

record(stringin, "ACSW:UNDS:NW28:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState8(ACSW:UNDS:NW28) acsw-unds-nw28")
}

record(ai, "ACSW:UNDS:NW28:TYPE") {
  field(DESC, "APC 8 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "10")
}

record(stringin, "ACSW:UNDS:NW28:LOC") {
  field(PINI, "YES")
  field(VAL, "B920-28S")
  field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:UNDS:NW28:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-unds-nw28")
}

record(calcout, "ACSW:UNDS:NW28:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:UNDS:NW28:DISCONN.DISA")
  field(INPB, "ACSW:UNDS:NW28:DISCONN.DISV")
  field(INPC, "ACSW:UNDS:NW28:GETSTATUS.DISA")
  field(INPD, "ACSW:UNDS:NW28:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:UNDS:NW28:CONNSTA PP")
}

record(bi, "ACSW:UNDS:NW28:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:UNDS:NW28:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:UNDS:NW28:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:UNDS:NW28:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:UNDS:NW28:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:UNDS:NW28:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:UNDS:NW28:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:UNDS:NW28:UPTIMEHOUR") {
  field(FLNK, "ACSW:UNDS:NW28:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:UNDS:NW28:UPTIMEDAY") {
  field(FLNK, "ACSW:UNDS:NW28:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:UNDS:NW28:UPTIMEMINUTE") {
  field(FLNK, "ACSW:UNDS:NW28:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:UNDS:NW28:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW28:1POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW28:1POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW28:1POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW28:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW28:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW28:1POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW28:1POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW28:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW28:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-unds-nw28")
}

record(bo, "ACSW:UNDS:NW28:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-unds-nw28")
}

record(bo, "ACSW:UNDS:NW28:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-unds-nw28")
}

record(stringin, "ACSW:UNDS:NW28:1NAMESET") {
  field(FLNK, "ACSW:UNDS:NW28:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW28:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-unds-nw28")
  field(DOL, "ACSW:UNDS:NW28:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW28:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-unds-nw28")
  field(FLNK, "ACSW:UNDS:NW28:GETINIT")
}

record(bo, "ACSW:UNDS:NW28:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-unds-nw28")
  field(FLNK, "ACSW:UNDS:NW28:GETINIT")
}

record(stringin, "ACSW:UNDS:NW28:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW28:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW28:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW28:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW28:1INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW28:1INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW28:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW28:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW28:2POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW28:2POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW28:2POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW28:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW28:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW28:2POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW28:2POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW28:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW28:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-unds-nw28")
}

record(bo, "ACSW:UNDS:NW28:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-unds-nw28")
}

record(bo, "ACSW:UNDS:NW28:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-unds-nw28")
}

record(stringin, "ACSW:UNDS:NW28:2NAMESET") {
  field(FLNK, "ACSW:UNDS:NW28:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW28:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-unds-nw28")
  field(DOL, "ACSW:UNDS:NW28:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW28:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-unds-nw28")
  field(FLNK, "ACSW:UNDS:NW28:GETINIT")
}

record(bo, "ACSW:UNDS:NW28:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-unds-nw28")
  field(FLNK, "ACSW:UNDS:NW28:GETINIT")
}

record(stringin, "ACSW:UNDS:NW28:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW28:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW28:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW28:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW28:2INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW28:2INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW28:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW28:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW28:3POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW28:3POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW28:3POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW28:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW28:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW28:3POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW28:3POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW28:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW28:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-unds-nw28")
}

record(bo, "ACSW:UNDS:NW28:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-unds-nw28")
}

record(bo, "ACSW:UNDS:NW28:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-unds-nw28")
}

record(stringin, "ACSW:UNDS:NW28:3NAMESET") {
  field(FLNK, "ACSW:UNDS:NW28:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW28:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-unds-nw28")
  field(DOL, "ACSW:UNDS:NW28:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW28:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-unds-nw28")
  field(FLNK, "ACSW:UNDS:NW28:GETINIT")
}

record(bo, "ACSW:UNDS:NW28:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-unds-nw28")
  field(FLNK, "ACSW:UNDS:NW28:GETINIT")
}

record(stringin, "ACSW:UNDS:NW28:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW28:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW28:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW28:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW28:3INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW28:3INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW28:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW28:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW28:4POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW28:4POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW28:4POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW28:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW28:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW28:4POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW28:4POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW28:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW28:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-unds-nw28")
}

record(bo, "ACSW:UNDS:NW28:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-unds-nw28")
}

record(bo, "ACSW:UNDS:NW28:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-unds-nw28")
}

record(stringin, "ACSW:UNDS:NW28:4NAMESET") {
  field(FLNK, "ACSW:UNDS:NW28:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW28:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-unds-nw28")
  field(DOL, "ACSW:UNDS:NW28:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW28:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-unds-nw28")
  field(FLNK, "ACSW:UNDS:NW28:GETINIT")
}

record(bo, "ACSW:UNDS:NW28:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-unds-nw28")
  field(FLNK, "ACSW:UNDS:NW28:GETINIT")
}

record(stringin, "ACSW:UNDS:NW28:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW28:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW28:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW28:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW28:4INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW28:4INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW28:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW28:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW28:5POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW28:5POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW28:5POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW28:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW28:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW28:5POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW28:5POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW28:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW28:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-unds-nw28")
}

record(bo, "ACSW:UNDS:NW28:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-unds-nw28")
}

record(bo, "ACSW:UNDS:NW28:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-unds-nw28")
}

record(stringin, "ACSW:UNDS:NW28:5NAMESET") {
  field(FLNK, "ACSW:UNDS:NW28:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW28:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-unds-nw28")
  field(DOL, "ACSW:UNDS:NW28:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW28:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-unds-nw28")
  field(FLNK, "ACSW:UNDS:NW28:GETINIT")
}

record(bo, "ACSW:UNDS:NW28:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-unds-nw28")
  field(FLNK, "ACSW:UNDS:NW28:GETINIT")
}

record(stringin, "ACSW:UNDS:NW28:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW28:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW28:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW28:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW28:5INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW28:5INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW28:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW28:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW28:6POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW28:6POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW28:6POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW28:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW28:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW28:6POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW28:6POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW28:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW28:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-unds-nw28")
}

record(bo, "ACSW:UNDS:NW28:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-unds-nw28")
}

record(bo, "ACSW:UNDS:NW28:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-unds-nw28")
}

record(stringin, "ACSW:UNDS:NW28:6NAMESET") {
  field(FLNK, "ACSW:UNDS:NW28:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW28:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-unds-nw28")
  field(DOL, "ACSW:UNDS:NW28:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW28:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-unds-nw28")
  field(FLNK, "ACSW:UNDS:NW28:GETINIT")
}

record(bo, "ACSW:UNDS:NW28:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-unds-nw28")
  field(FLNK, "ACSW:UNDS:NW28:GETINIT")
}

record(stringin, "ACSW:UNDS:NW28:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW28:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW28:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW28:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW28:6INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW28:6INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW28:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW28:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW28:7POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW28:7POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW28:7POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW28:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW28:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW28:7POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW28:7POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW28:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW28:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-unds-nw28")
}

record(bo, "ACSW:UNDS:NW28:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-unds-nw28")
}

record(bo, "ACSW:UNDS:NW28:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-unds-nw28")
}

record(stringin, "ACSW:UNDS:NW28:7NAMESET") {
  field(FLNK, "ACSW:UNDS:NW28:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW28:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-unds-nw28")
  field(DOL, "ACSW:UNDS:NW28:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW28:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-unds-nw28")
  field(FLNK, "ACSW:UNDS:NW28:GETINIT")
}

record(bo, "ACSW:UNDS:NW28:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-unds-nw28")
  field(FLNK, "ACSW:UNDS:NW28:GETINIT")
}

record(stringin, "ACSW:UNDS:NW28:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW28:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW28:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW28:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW28:7INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW28:7INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW28:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW28:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW28:8POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW28:8POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW28:8POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW28:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW28:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW28:8POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW28:8POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW28:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW28:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-unds-nw28")
}

record(bo, "ACSW:UNDS:NW28:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-unds-nw28")
}

record(bo, "ACSW:UNDS:NW28:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-unds-nw28")
}

record(stringin, "ACSW:UNDS:NW28:8NAMESET") {
  field(FLNK, "ACSW:UNDS:NW28:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW28:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-unds-nw28")
  field(DOL, "ACSW:UNDS:NW28:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW28:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-unds-nw28")
  field(FLNK, "ACSW:UNDS:NW28:GETINIT")
}

record(bo, "ACSW:UNDS:NW28:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-unds-nw28")
  field(FLNK, "ACSW:UNDS:NW28:GETINIT")
}

record(stringin, "ACSW:UNDS:NW28:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW28:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW28:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW28:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW28:8INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW28:8INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW28:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW28:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW29:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:UNDS:NW29) acsw-unds-nw29")
  field(FLNK, "ACSW:UNDS:NW29:GETINFO")
}

record(stringin, "ACSW:UNDS:NW29:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:UNDS:NW29) acsw-unds-nw29")
  field(FLNK, "ACSW:UNDS:NW29:GETINIT")
}

record(stringin, "ACSW:UNDS:NW29:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:UNDS:NW29:NETFWVERSION")
  field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW29:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:UNDS:NW29:SITEID")
  field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW29:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:UNDS:NW29:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState8(ACSW:UNDS:NW29) acsw-unds-nw29")
}

record(stringin, "ACSW:UNDS:NW29:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState8(ACSW:UNDS:NW29) acsw-unds-nw29")
}

record(ai, "ACSW:UNDS:NW29:TYPE") {
  field(DESC, "APC 8 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "10")
}

record(stringin, "ACSW:UNDS:NW29:LOC") {
  field(PINI, "YES")
  field(VAL, "B920-29S")
  field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:UNDS:NW29:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-unds-nw29")
}

record(calcout, "ACSW:UNDS:NW29:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:UNDS:NW29:DISCONN.DISA")
  field(INPB, "ACSW:UNDS:NW29:DISCONN.DISV")
  field(INPC, "ACSW:UNDS:NW29:GETSTATUS.DISA")
  field(INPD, "ACSW:UNDS:NW29:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:UNDS:NW29:CONNSTA PP")
}

record(bi, "ACSW:UNDS:NW29:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:UNDS:NW29:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:UNDS:NW29:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:UNDS:NW29:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:UNDS:NW29:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:UNDS:NW29:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:UNDS:NW29:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:UNDS:NW29:UPTIMEHOUR") {
  field(FLNK, "ACSW:UNDS:NW29:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:UNDS:NW29:UPTIMEDAY") {
  field(FLNK, "ACSW:UNDS:NW29:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:UNDS:NW29:UPTIMEMINUTE") {
  field(FLNK, "ACSW:UNDS:NW29:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:UNDS:NW29:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW29:1POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW29:1POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW29:1POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW29:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW29:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW29:1POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW29:1POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW29:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW29:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-unds-nw29")
}

record(bo, "ACSW:UNDS:NW29:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-unds-nw29")
}

record(bo, "ACSW:UNDS:NW29:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-unds-nw29")
}

record(stringin, "ACSW:UNDS:NW29:1NAMESET") {
  field(FLNK, "ACSW:UNDS:NW29:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW29:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-unds-nw29")
  field(DOL, "ACSW:UNDS:NW29:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW29:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-unds-nw29")
  field(FLNK, "ACSW:UNDS:NW29:GETINIT")
}

record(bo, "ACSW:UNDS:NW29:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-unds-nw29")
  field(FLNK, "ACSW:UNDS:NW29:GETINIT")
}

record(stringin, "ACSW:UNDS:NW29:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW29:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW29:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW29:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW29:1INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW29:1INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW29:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW29:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW29:2POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW29:2POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW29:2POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW29:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW29:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW29:2POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW29:2POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW29:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW29:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-unds-nw29")
}

record(bo, "ACSW:UNDS:NW29:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-unds-nw29")
}

record(bo, "ACSW:UNDS:NW29:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-unds-nw29")
}

record(stringin, "ACSW:UNDS:NW29:2NAMESET") {
  field(FLNK, "ACSW:UNDS:NW29:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW29:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-unds-nw29")
  field(DOL, "ACSW:UNDS:NW29:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW29:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-unds-nw29")
  field(FLNK, "ACSW:UNDS:NW29:GETINIT")
}

record(bo, "ACSW:UNDS:NW29:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-unds-nw29")
  field(FLNK, "ACSW:UNDS:NW29:GETINIT")
}

record(stringin, "ACSW:UNDS:NW29:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW29:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW29:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW29:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW29:2INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW29:2INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW29:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW29:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW29:3POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW29:3POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW29:3POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW29:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW29:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW29:3POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW29:3POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW29:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW29:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-unds-nw29")
}

record(bo, "ACSW:UNDS:NW29:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-unds-nw29")
}

record(bo, "ACSW:UNDS:NW29:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-unds-nw29")
}

record(stringin, "ACSW:UNDS:NW29:3NAMESET") {
  field(FLNK, "ACSW:UNDS:NW29:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW29:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-unds-nw29")
  field(DOL, "ACSW:UNDS:NW29:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW29:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-unds-nw29")
  field(FLNK, "ACSW:UNDS:NW29:GETINIT")
}

record(bo, "ACSW:UNDS:NW29:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-unds-nw29")
  field(FLNK, "ACSW:UNDS:NW29:GETINIT")
}

record(stringin, "ACSW:UNDS:NW29:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW29:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW29:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW29:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW29:3INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW29:3INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW29:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW29:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW29:4POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW29:4POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW29:4POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW29:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW29:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW29:4POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW29:4POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW29:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW29:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-unds-nw29")
}

record(bo, "ACSW:UNDS:NW29:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-unds-nw29")
}

record(bo, "ACSW:UNDS:NW29:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-unds-nw29")
}

record(stringin, "ACSW:UNDS:NW29:4NAMESET") {
  field(FLNK, "ACSW:UNDS:NW29:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW29:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-unds-nw29")
  field(DOL, "ACSW:UNDS:NW29:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW29:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-unds-nw29")
  field(FLNK, "ACSW:UNDS:NW29:GETINIT")
}

record(bo, "ACSW:UNDS:NW29:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-unds-nw29")
  field(FLNK, "ACSW:UNDS:NW29:GETINIT")
}

record(stringin, "ACSW:UNDS:NW29:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW29:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW29:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW29:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW29:4INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW29:4INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW29:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW29:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW29:5POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW29:5POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW29:5POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW29:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW29:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW29:5POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW29:5POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW29:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW29:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-unds-nw29")
}

record(bo, "ACSW:UNDS:NW29:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-unds-nw29")
}

record(bo, "ACSW:UNDS:NW29:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-unds-nw29")
}

record(stringin, "ACSW:UNDS:NW29:5NAMESET") {
  field(FLNK, "ACSW:UNDS:NW29:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW29:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-unds-nw29")
  field(DOL, "ACSW:UNDS:NW29:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW29:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-unds-nw29")
  field(FLNK, "ACSW:UNDS:NW29:GETINIT")
}

record(bo, "ACSW:UNDS:NW29:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-unds-nw29")
  field(FLNK, "ACSW:UNDS:NW29:GETINIT")
}

record(stringin, "ACSW:UNDS:NW29:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW29:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW29:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW29:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW29:5INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW29:5INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW29:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW29:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW29:6POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW29:6POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW29:6POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW29:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW29:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW29:6POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW29:6POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW29:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW29:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-unds-nw29")
}

record(bo, "ACSW:UNDS:NW29:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-unds-nw29")
}

record(bo, "ACSW:UNDS:NW29:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-unds-nw29")
}

record(stringin, "ACSW:UNDS:NW29:6NAMESET") {
  field(FLNK, "ACSW:UNDS:NW29:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW29:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-unds-nw29")
  field(DOL, "ACSW:UNDS:NW29:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW29:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-unds-nw29")
  field(FLNK, "ACSW:UNDS:NW29:GETINIT")
}

record(bo, "ACSW:UNDS:NW29:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-unds-nw29")
  field(FLNK, "ACSW:UNDS:NW29:GETINIT")
}

record(stringin, "ACSW:UNDS:NW29:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW29:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW29:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW29:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW29:6INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW29:6INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW29:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW29:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW29:7POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW29:7POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW29:7POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW29:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW29:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW29:7POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW29:7POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW29:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW29:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-unds-nw29")
}

record(bo, "ACSW:UNDS:NW29:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-unds-nw29")
}

record(bo, "ACSW:UNDS:NW29:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-unds-nw29")
}

record(stringin, "ACSW:UNDS:NW29:7NAMESET") {
  field(FLNK, "ACSW:UNDS:NW29:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW29:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-unds-nw29")
  field(DOL, "ACSW:UNDS:NW29:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW29:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-unds-nw29")
  field(FLNK, "ACSW:UNDS:NW29:GETINIT")
}

record(bo, "ACSW:UNDS:NW29:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-unds-nw29")
  field(FLNK, "ACSW:UNDS:NW29:GETINIT")
}

record(stringin, "ACSW:UNDS:NW29:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW29:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW29:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW29:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW29:7INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW29:7INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW29:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW29:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW29:8POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW29:8POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW29:8POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW29:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW29:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW29:8POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW29:8POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW29:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW29:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-unds-nw29")
}

record(bo, "ACSW:UNDS:NW29:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-unds-nw29")
}

record(bo, "ACSW:UNDS:NW29:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-unds-nw29")
}

record(stringin, "ACSW:UNDS:NW29:8NAMESET") {
  field(FLNK, "ACSW:UNDS:NW29:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW29:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-unds-nw29")
  field(DOL, "ACSW:UNDS:NW29:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW29:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-unds-nw29")
  field(FLNK, "ACSW:UNDS:NW29:GETINIT")
}

record(bo, "ACSW:UNDS:NW29:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-unds-nw29")
  field(FLNK, "ACSW:UNDS:NW29:GETINIT")
}

record(stringin, "ACSW:UNDS:NW29:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW29:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW29:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW29:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW29:8INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW29:8INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW29:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW29:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW30:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:UNDS:NW30) acsw-unds-nw30")
  field(FLNK, "ACSW:UNDS:NW30:GETINFO")
}

record(stringin, "ACSW:UNDS:NW30:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:UNDS:NW30) acsw-unds-nw30")
  field(FLNK, "ACSW:UNDS:NW30:GETINIT")
}

record(stringin, "ACSW:UNDS:NW30:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:UNDS:NW30:NETFWVERSION")
  field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW30:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:UNDS:NW30:SITEID")
  field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW30:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:UNDS:NW30:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState8(ACSW:UNDS:NW30) acsw-unds-nw30")
}

record(stringin, "ACSW:UNDS:NW30:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState8(ACSW:UNDS:NW30) acsw-unds-nw30")
}

record(ai, "ACSW:UNDS:NW30:TYPE") {
  field(DESC, "APC 8 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "10")
}

record(stringin, "ACSW:UNDS:NW30:LOC") {
  field(PINI, "YES")
  field(VAL, "B920-30S")
  field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:UNDS:NW30:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-unds-nw30")
}

record(calcout, "ACSW:UNDS:NW30:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:UNDS:NW30:DISCONN.DISA")
  field(INPB, "ACSW:UNDS:NW30:DISCONN.DISV")
  field(INPC, "ACSW:UNDS:NW30:GETSTATUS.DISA")
  field(INPD, "ACSW:UNDS:NW30:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:UNDS:NW30:CONNSTA PP")
}

record(bi, "ACSW:UNDS:NW30:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:UNDS:NW30:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:UNDS:NW30:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:UNDS:NW30:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:UNDS:NW30:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:UNDS:NW30:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:UNDS:NW30:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:UNDS:NW30:UPTIMEHOUR") {
  field(FLNK, "ACSW:UNDS:NW30:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:UNDS:NW30:UPTIMEDAY") {
  field(FLNK, "ACSW:UNDS:NW30:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:UNDS:NW30:UPTIMEMINUTE") {
  field(FLNK, "ACSW:UNDS:NW30:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:UNDS:NW30:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW30:1POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW30:1POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW30:1POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW30:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW30:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW30:1POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW30:1POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW30:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW30:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-unds-nw30")
}

record(bo, "ACSW:UNDS:NW30:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-unds-nw30")
}

record(bo, "ACSW:UNDS:NW30:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-unds-nw30")
}

record(stringin, "ACSW:UNDS:NW30:1NAMESET") {
  field(FLNK, "ACSW:UNDS:NW30:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW30:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-unds-nw30")
  field(DOL, "ACSW:UNDS:NW30:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW30:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-unds-nw30")
  field(FLNK, "ACSW:UNDS:NW30:GETINIT")
}

record(bo, "ACSW:UNDS:NW30:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-unds-nw30")
  field(FLNK, "ACSW:UNDS:NW30:GETINIT")
}

record(stringin, "ACSW:UNDS:NW30:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW30:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW30:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW30:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW30:1INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW30:1INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW30:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW30:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW30:2POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW30:2POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW30:2POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW30:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW30:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW30:2POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW30:2POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW30:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW30:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-unds-nw30")
}

record(bo, "ACSW:UNDS:NW30:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-unds-nw30")
}

record(bo, "ACSW:UNDS:NW30:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-unds-nw30")
}

record(stringin, "ACSW:UNDS:NW30:2NAMESET") {
  field(FLNK, "ACSW:UNDS:NW30:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW30:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-unds-nw30")
  field(DOL, "ACSW:UNDS:NW30:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW30:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-unds-nw30")
  field(FLNK, "ACSW:UNDS:NW30:GETINIT")
}

record(bo, "ACSW:UNDS:NW30:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-unds-nw30")
  field(FLNK, "ACSW:UNDS:NW30:GETINIT")
}

record(stringin, "ACSW:UNDS:NW30:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW30:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW30:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW30:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW30:2INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW30:2INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW30:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW30:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW30:3POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW30:3POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW30:3POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW30:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW30:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW30:3POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW30:3POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW30:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW30:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-unds-nw30")
}

record(bo, "ACSW:UNDS:NW30:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-unds-nw30")
}

record(bo, "ACSW:UNDS:NW30:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-unds-nw30")
}

record(stringin, "ACSW:UNDS:NW30:3NAMESET") {
  field(FLNK, "ACSW:UNDS:NW30:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW30:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-unds-nw30")
  field(DOL, "ACSW:UNDS:NW30:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW30:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-unds-nw30")
  field(FLNK, "ACSW:UNDS:NW30:GETINIT")
}

record(bo, "ACSW:UNDS:NW30:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-unds-nw30")
  field(FLNK, "ACSW:UNDS:NW30:GETINIT")
}

record(stringin, "ACSW:UNDS:NW30:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW30:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW30:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW30:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW30:3INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW30:3INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW30:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW30:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW30:4POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW30:4POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW30:4POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW30:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW30:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW30:4POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW30:4POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW30:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW30:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-unds-nw30")
}

record(bo, "ACSW:UNDS:NW30:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-unds-nw30")
}

record(bo, "ACSW:UNDS:NW30:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-unds-nw30")
}

record(stringin, "ACSW:UNDS:NW30:4NAMESET") {
  field(FLNK, "ACSW:UNDS:NW30:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW30:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-unds-nw30")
  field(DOL, "ACSW:UNDS:NW30:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW30:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-unds-nw30")
  field(FLNK, "ACSW:UNDS:NW30:GETINIT")
}

record(bo, "ACSW:UNDS:NW30:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-unds-nw30")
  field(FLNK, "ACSW:UNDS:NW30:GETINIT")
}

record(stringin, "ACSW:UNDS:NW30:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW30:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW30:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW30:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW30:4INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW30:4INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW30:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW30:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW30:5POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW30:5POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW30:5POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW30:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW30:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW30:5POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW30:5POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW30:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW30:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-unds-nw30")
}

record(bo, "ACSW:UNDS:NW30:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-unds-nw30")
}

record(bo, "ACSW:UNDS:NW30:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-unds-nw30")
}

record(stringin, "ACSW:UNDS:NW30:5NAMESET") {
  field(FLNK, "ACSW:UNDS:NW30:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW30:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-unds-nw30")
  field(DOL, "ACSW:UNDS:NW30:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW30:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-unds-nw30")
  field(FLNK, "ACSW:UNDS:NW30:GETINIT")
}

record(bo, "ACSW:UNDS:NW30:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-unds-nw30")
  field(FLNK, "ACSW:UNDS:NW30:GETINIT")
}

record(stringin, "ACSW:UNDS:NW30:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW30:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW30:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW30:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW30:5INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW30:5INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW30:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW30:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW30:6POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW30:6POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW30:6POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW30:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW30:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW30:6POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW30:6POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW30:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW30:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-unds-nw30")
}

record(bo, "ACSW:UNDS:NW30:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-unds-nw30")
}

record(bo, "ACSW:UNDS:NW30:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-unds-nw30")
}

record(stringin, "ACSW:UNDS:NW30:6NAMESET") {
  field(FLNK, "ACSW:UNDS:NW30:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW30:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-unds-nw30")
  field(DOL, "ACSW:UNDS:NW30:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW30:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-unds-nw30")
  field(FLNK, "ACSW:UNDS:NW30:GETINIT")
}

record(bo, "ACSW:UNDS:NW30:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-unds-nw30")
  field(FLNK, "ACSW:UNDS:NW30:GETINIT")
}

record(stringin, "ACSW:UNDS:NW30:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW30:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW30:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW30:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW30:6INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW30:6INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW30:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW30:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW30:7POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW30:7POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW30:7POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW30:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW30:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW30:7POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW30:7POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW30:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW30:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-unds-nw30")
}

record(bo, "ACSW:UNDS:NW30:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-unds-nw30")
}

record(bo, "ACSW:UNDS:NW30:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-unds-nw30")
}

record(stringin, "ACSW:UNDS:NW30:7NAMESET") {
  field(FLNK, "ACSW:UNDS:NW30:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW30:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-unds-nw30")
  field(DOL, "ACSW:UNDS:NW30:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW30:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-unds-nw30")
  field(FLNK, "ACSW:UNDS:NW30:GETINIT")
}

record(bo, "ACSW:UNDS:NW30:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-unds-nw30")
  field(FLNK, "ACSW:UNDS:NW30:GETINIT")
}

record(stringin, "ACSW:UNDS:NW30:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW30:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW30:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW30:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW30:7INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW30:7INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW30:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW30:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW30:8POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW30:8POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW30:8POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW30:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW30:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW30:8POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW30:8POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW30:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW30:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-unds-nw30")
}

record(bo, "ACSW:UNDS:NW30:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-unds-nw30")
}

record(bo, "ACSW:UNDS:NW30:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-unds-nw30")
}

record(stringin, "ACSW:UNDS:NW30:8NAMESET") {
  field(FLNK, "ACSW:UNDS:NW30:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW30:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-unds-nw30")
  field(DOL, "ACSW:UNDS:NW30:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW30:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-unds-nw30")
  field(FLNK, "ACSW:UNDS:NW30:GETINIT")
}

record(bo, "ACSW:UNDS:NW30:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-unds-nw30")
  field(FLNK, "ACSW:UNDS:NW30:GETINIT")
}

record(stringin, "ACSW:UNDS:NW30:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW30:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW30:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW30:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW30:8INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW30:8INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW30:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW30:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW31:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:UNDS:NW31) acsw-unds-nw31")
  field(FLNK, "ACSW:UNDS:NW31:GETINFO")
}

record(stringin, "ACSW:UNDS:NW31:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:UNDS:NW31) acsw-unds-nw31")
  field(FLNK, "ACSW:UNDS:NW31:GETINIT")
}

record(stringin, "ACSW:UNDS:NW31:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:UNDS:NW31:NETFWVERSION")
  field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW31:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:UNDS:NW31:SITEID")
  field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW31:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:UNDS:NW31:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState8(ACSW:UNDS:NW31) acsw-unds-nw31")
}

record(stringin, "ACSW:UNDS:NW31:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState8(ACSW:UNDS:NW31) acsw-unds-nw31")
}

record(ai, "ACSW:UNDS:NW31:TYPE") {
  field(DESC, "APC 8 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "10")
}

record(stringin, "ACSW:UNDS:NW31:LOC") {
  field(PINI, "YES")
  field(VAL, "B920-31S")
  field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:UNDS:NW31:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-unds-nw31")
}

record(calcout, "ACSW:UNDS:NW31:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:UNDS:NW31:DISCONN.DISA")
  field(INPB, "ACSW:UNDS:NW31:DISCONN.DISV")
  field(INPC, "ACSW:UNDS:NW31:GETSTATUS.DISA")
  field(INPD, "ACSW:UNDS:NW31:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:UNDS:NW31:CONNSTA PP")
}

record(bi, "ACSW:UNDS:NW31:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:UNDS:NW31:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:UNDS:NW31:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:UNDS:NW31:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:UNDS:NW31:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:UNDS:NW31:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:UNDS:NW31:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:UNDS:NW31:UPTIMEHOUR") {
  field(FLNK, "ACSW:UNDS:NW31:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:UNDS:NW31:UPTIMEDAY") {
  field(FLNK, "ACSW:UNDS:NW31:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:UNDS:NW31:UPTIMEMINUTE") {
  field(FLNK, "ACSW:UNDS:NW31:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:UNDS:NW31:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW31:1POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW31:1POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW31:1POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW31:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW31:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW31:1POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW31:1POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW31:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW31:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-unds-nw31")
}

record(bo, "ACSW:UNDS:NW31:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-unds-nw31")
}

record(bo, "ACSW:UNDS:NW31:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-unds-nw31")
}

record(stringin, "ACSW:UNDS:NW31:1NAMESET") {
  field(FLNK, "ACSW:UNDS:NW31:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW31:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-unds-nw31")
  field(DOL, "ACSW:UNDS:NW31:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW31:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-unds-nw31")
  field(FLNK, "ACSW:UNDS:NW31:GETINIT")
}

record(bo, "ACSW:UNDS:NW31:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-unds-nw31")
  field(FLNK, "ACSW:UNDS:NW31:GETINIT")
}

record(stringin, "ACSW:UNDS:NW31:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW31:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW31:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW31:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW31:1INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW31:1INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW31:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW31:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW31:2POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW31:2POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW31:2POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW31:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW31:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW31:2POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW31:2POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW31:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW31:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-unds-nw31")
}

record(bo, "ACSW:UNDS:NW31:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-unds-nw31")
}

record(bo, "ACSW:UNDS:NW31:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-unds-nw31")
}

record(stringin, "ACSW:UNDS:NW31:2NAMESET") {
  field(FLNK, "ACSW:UNDS:NW31:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW31:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-unds-nw31")
  field(DOL, "ACSW:UNDS:NW31:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW31:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-unds-nw31")
  field(FLNK, "ACSW:UNDS:NW31:GETINIT")
}

record(bo, "ACSW:UNDS:NW31:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-unds-nw31")
  field(FLNK, "ACSW:UNDS:NW31:GETINIT")
}

record(stringin, "ACSW:UNDS:NW31:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW31:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW31:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW31:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW31:2INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW31:2INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW31:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW31:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW31:3POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW31:3POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW31:3POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW31:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW31:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW31:3POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW31:3POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW31:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW31:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-unds-nw31")
}

record(bo, "ACSW:UNDS:NW31:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-unds-nw31")
}

record(bo, "ACSW:UNDS:NW31:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-unds-nw31")
}

record(stringin, "ACSW:UNDS:NW31:3NAMESET") {
  field(FLNK, "ACSW:UNDS:NW31:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW31:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-unds-nw31")
  field(DOL, "ACSW:UNDS:NW31:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW31:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-unds-nw31")
  field(FLNK, "ACSW:UNDS:NW31:GETINIT")
}

record(bo, "ACSW:UNDS:NW31:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-unds-nw31")
  field(FLNK, "ACSW:UNDS:NW31:GETINIT")
}

record(stringin, "ACSW:UNDS:NW31:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW31:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW31:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW31:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW31:3INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW31:3INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW31:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW31:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW31:4POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW31:4POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW31:4POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW31:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW31:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW31:4POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW31:4POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW31:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW31:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-unds-nw31")
}

record(bo, "ACSW:UNDS:NW31:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-unds-nw31")
}

record(bo, "ACSW:UNDS:NW31:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-unds-nw31")
}

record(stringin, "ACSW:UNDS:NW31:4NAMESET") {
  field(FLNK, "ACSW:UNDS:NW31:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW31:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-unds-nw31")
  field(DOL, "ACSW:UNDS:NW31:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW31:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-unds-nw31")
  field(FLNK, "ACSW:UNDS:NW31:GETINIT")
}

record(bo, "ACSW:UNDS:NW31:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-unds-nw31")
  field(FLNK, "ACSW:UNDS:NW31:GETINIT")
}

record(stringin, "ACSW:UNDS:NW31:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW31:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW31:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW31:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW31:4INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW31:4INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW31:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW31:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW31:5POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW31:5POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW31:5POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW31:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW31:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW31:5POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW31:5POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW31:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW31:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-unds-nw31")
}

record(bo, "ACSW:UNDS:NW31:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-unds-nw31")
}

record(bo, "ACSW:UNDS:NW31:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-unds-nw31")
}

record(stringin, "ACSW:UNDS:NW31:5NAMESET") {
  field(FLNK, "ACSW:UNDS:NW31:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW31:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-unds-nw31")
  field(DOL, "ACSW:UNDS:NW31:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW31:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-unds-nw31")
  field(FLNK, "ACSW:UNDS:NW31:GETINIT")
}

record(bo, "ACSW:UNDS:NW31:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-unds-nw31")
  field(FLNK, "ACSW:UNDS:NW31:GETINIT")
}

record(stringin, "ACSW:UNDS:NW31:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW31:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW31:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW31:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW31:5INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW31:5INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW31:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW31:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW31:6POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW31:6POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW31:6POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW31:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW31:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW31:6POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW31:6POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW31:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW31:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-unds-nw31")
}

record(bo, "ACSW:UNDS:NW31:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-unds-nw31")
}

record(bo, "ACSW:UNDS:NW31:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-unds-nw31")
}

record(stringin, "ACSW:UNDS:NW31:6NAMESET") {
  field(FLNK, "ACSW:UNDS:NW31:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW31:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-unds-nw31")
  field(DOL, "ACSW:UNDS:NW31:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW31:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-unds-nw31")
  field(FLNK, "ACSW:UNDS:NW31:GETINIT")
}

record(bo, "ACSW:UNDS:NW31:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-unds-nw31")
  field(FLNK, "ACSW:UNDS:NW31:GETINIT")
}

record(stringin, "ACSW:UNDS:NW31:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW31:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW31:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW31:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW31:6INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW31:6INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW31:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW31:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW31:7POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW31:7POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW31:7POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW31:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW31:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW31:7POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW31:7POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW31:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW31:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-unds-nw31")
}

record(bo, "ACSW:UNDS:NW31:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-unds-nw31")
}

record(bo, "ACSW:UNDS:NW31:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-unds-nw31")
}

record(stringin, "ACSW:UNDS:NW31:7NAMESET") {
  field(FLNK, "ACSW:UNDS:NW31:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW31:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-unds-nw31")
  field(DOL, "ACSW:UNDS:NW31:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW31:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-unds-nw31")
  field(FLNK, "ACSW:UNDS:NW31:GETINIT")
}

record(bo, "ACSW:UNDS:NW31:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-unds-nw31")
  field(FLNK, "ACSW:UNDS:NW31:GETINIT")
}

record(stringin, "ACSW:UNDS:NW31:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW31:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW31:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW31:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW31:7INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW31:7INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW31:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW31:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW31:8POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW31:8POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW31:8POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW31:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW31:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW31:8POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW31:8POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW31:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW31:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-unds-nw31")
}

record(bo, "ACSW:UNDS:NW31:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-unds-nw31")
}

record(bo, "ACSW:UNDS:NW31:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-unds-nw31")
}

record(stringin, "ACSW:UNDS:NW31:8NAMESET") {
  field(FLNK, "ACSW:UNDS:NW31:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW31:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-unds-nw31")
  field(DOL, "ACSW:UNDS:NW31:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW31:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-unds-nw31")
  field(FLNK, "ACSW:UNDS:NW31:GETINIT")
}

record(bo, "ACSW:UNDS:NW31:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-unds-nw31")
  field(FLNK, "ACSW:UNDS:NW31:GETINIT")
}

record(stringin, "ACSW:UNDS:NW31:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW31:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW31:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW31:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW31:8INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW31:8INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW31:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW31:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW32:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:UNDS:NW32) acsw-unds-nw32")
  field(FLNK, "ACSW:UNDS:NW32:GETINFO")
}

record(stringin, "ACSW:UNDS:NW32:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:UNDS:NW32) acsw-unds-nw32")
  field(FLNK, "ACSW:UNDS:NW32:GETINIT")
}

record(stringin, "ACSW:UNDS:NW32:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:UNDS:NW32:NETFWVERSION")
  field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW32:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:UNDS:NW32:SITEID")
  field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW32:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:UNDS:NW32:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState8(ACSW:UNDS:NW32) acsw-unds-nw32")
}

record(stringin, "ACSW:UNDS:NW32:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState8(ACSW:UNDS:NW32) acsw-unds-nw32")
}

record(ai, "ACSW:UNDS:NW32:TYPE") {
  field(DESC, "APC 8 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "10")
}

record(stringin, "ACSW:UNDS:NW32:LOC") {
  field(PINI, "YES")
  field(VAL, "B920-32S")
  field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:UNDS:NW32:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-unds-nw32")
}

record(calcout, "ACSW:UNDS:NW32:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:UNDS:NW32:DISCONN.DISA")
  field(INPB, "ACSW:UNDS:NW32:DISCONN.DISV")
  field(INPC, "ACSW:UNDS:NW32:GETSTATUS.DISA")
  field(INPD, "ACSW:UNDS:NW32:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:UNDS:NW32:CONNSTA PP")
}

record(bi, "ACSW:UNDS:NW32:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:UNDS:NW32:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:UNDS:NW32:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:UNDS:NW32:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:UNDS:NW32:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:UNDS:NW32:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:UNDS:NW32:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:UNDS:NW32:UPTIMEHOUR") {
  field(FLNK, "ACSW:UNDS:NW32:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:UNDS:NW32:UPTIMEDAY") {
  field(FLNK, "ACSW:UNDS:NW32:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:UNDS:NW32:UPTIMEMINUTE") {
  field(FLNK, "ACSW:UNDS:NW32:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:UNDS:NW32:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW32:1POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW32:1POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW32:1POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW32:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW32:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW32:1POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW32:1POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW32:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW32:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-unds-nw32")
}

record(bo, "ACSW:UNDS:NW32:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-unds-nw32")
}

record(bo, "ACSW:UNDS:NW32:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-unds-nw32")
}

record(stringin, "ACSW:UNDS:NW32:1NAMESET") {
  field(FLNK, "ACSW:UNDS:NW32:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW32:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-unds-nw32")
  field(DOL, "ACSW:UNDS:NW32:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW32:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-unds-nw32")
  field(FLNK, "ACSW:UNDS:NW32:GETINIT")
}

record(bo, "ACSW:UNDS:NW32:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-unds-nw32")
  field(FLNK, "ACSW:UNDS:NW32:GETINIT")
}

record(stringin, "ACSW:UNDS:NW32:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW32:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW32:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW32:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW32:1INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW32:1INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW32:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW32:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW32:2POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW32:2POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW32:2POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW32:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW32:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW32:2POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW32:2POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW32:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW32:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-unds-nw32")
}

record(bo, "ACSW:UNDS:NW32:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-unds-nw32")
}

record(bo, "ACSW:UNDS:NW32:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-unds-nw32")
}

record(stringin, "ACSW:UNDS:NW32:2NAMESET") {
  field(FLNK, "ACSW:UNDS:NW32:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW32:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-unds-nw32")
  field(DOL, "ACSW:UNDS:NW32:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW32:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-unds-nw32")
  field(FLNK, "ACSW:UNDS:NW32:GETINIT")
}

record(bo, "ACSW:UNDS:NW32:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-unds-nw32")
  field(FLNK, "ACSW:UNDS:NW32:GETINIT")
}

record(stringin, "ACSW:UNDS:NW32:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW32:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW32:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW32:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW32:2INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW32:2INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW32:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW32:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW32:3POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW32:3POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW32:3POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW32:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW32:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW32:3POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW32:3POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW32:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW32:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-unds-nw32")
}

record(bo, "ACSW:UNDS:NW32:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-unds-nw32")
}

record(bo, "ACSW:UNDS:NW32:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-unds-nw32")
}

record(stringin, "ACSW:UNDS:NW32:3NAMESET") {
  field(FLNK, "ACSW:UNDS:NW32:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW32:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-unds-nw32")
  field(DOL, "ACSW:UNDS:NW32:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW32:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-unds-nw32")
  field(FLNK, "ACSW:UNDS:NW32:GETINIT")
}

record(bo, "ACSW:UNDS:NW32:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-unds-nw32")
  field(FLNK, "ACSW:UNDS:NW32:GETINIT")
}

record(stringin, "ACSW:UNDS:NW32:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW32:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW32:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW32:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW32:3INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW32:3INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW32:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW32:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW32:4POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW32:4POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW32:4POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW32:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW32:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW32:4POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW32:4POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW32:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW32:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-unds-nw32")
}

record(bo, "ACSW:UNDS:NW32:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-unds-nw32")
}

record(bo, "ACSW:UNDS:NW32:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-unds-nw32")
}

record(stringin, "ACSW:UNDS:NW32:4NAMESET") {
  field(FLNK, "ACSW:UNDS:NW32:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW32:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-unds-nw32")
  field(DOL, "ACSW:UNDS:NW32:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW32:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-unds-nw32")
  field(FLNK, "ACSW:UNDS:NW32:GETINIT")
}

record(bo, "ACSW:UNDS:NW32:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-unds-nw32")
  field(FLNK, "ACSW:UNDS:NW32:GETINIT")
}

record(stringin, "ACSW:UNDS:NW32:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW32:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW32:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW32:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW32:4INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW32:4INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW32:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW32:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW32:5POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW32:5POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW32:5POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW32:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW32:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW32:5POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW32:5POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW32:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW32:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-unds-nw32")
}

record(bo, "ACSW:UNDS:NW32:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-unds-nw32")
}

record(bo, "ACSW:UNDS:NW32:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-unds-nw32")
}

record(stringin, "ACSW:UNDS:NW32:5NAMESET") {
  field(FLNK, "ACSW:UNDS:NW32:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW32:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-unds-nw32")
  field(DOL, "ACSW:UNDS:NW32:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW32:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-unds-nw32")
  field(FLNK, "ACSW:UNDS:NW32:GETINIT")
}

record(bo, "ACSW:UNDS:NW32:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-unds-nw32")
  field(FLNK, "ACSW:UNDS:NW32:GETINIT")
}

record(stringin, "ACSW:UNDS:NW32:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW32:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW32:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW32:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW32:5INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW32:5INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW32:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW32:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW32:6POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW32:6POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW32:6POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW32:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW32:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW32:6POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW32:6POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW32:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW32:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-unds-nw32")
}

record(bo, "ACSW:UNDS:NW32:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-unds-nw32")
}

record(bo, "ACSW:UNDS:NW32:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-unds-nw32")
}

record(stringin, "ACSW:UNDS:NW32:6NAMESET") {
  field(FLNK, "ACSW:UNDS:NW32:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW32:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-unds-nw32")
  field(DOL, "ACSW:UNDS:NW32:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW32:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-unds-nw32")
  field(FLNK, "ACSW:UNDS:NW32:GETINIT")
}

record(bo, "ACSW:UNDS:NW32:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-unds-nw32")
  field(FLNK, "ACSW:UNDS:NW32:GETINIT")
}

record(stringin, "ACSW:UNDS:NW32:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW32:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW32:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW32:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW32:6INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW32:6INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW32:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW32:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW32:7POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW32:7POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW32:7POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW32:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW32:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW32:7POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW32:7POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW32:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW32:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-unds-nw32")
}

record(bo, "ACSW:UNDS:NW32:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-unds-nw32")
}

record(bo, "ACSW:UNDS:NW32:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-unds-nw32")
}

record(stringin, "ACSW:UNDS:NW32:7NAMESET") {
  field(FLNK, "ACSW:UNDS:NW32:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW32:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-unds-nw32")
  field(DOL, "ACSW:UNDS:NW32:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW32:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-unds-nw32")
  field(FLNK, "ACSW:UNDS:NW32:GETINIT")
}

record(bo, "ACSW:UNDS:NW32:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-unds-nw32")
  field(FLNK, "ACSW:UNDS:NW32:GETINIT")
}

record(stringin, "ACSW:UNDS:NW32:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW32:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW32:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW32:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW32:7INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW32:7INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW32:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW32:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW32:8POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW32:8POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW32:8POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW32:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW32:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW32:8POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW32:8POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW32:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW32:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-unds-nw32")
}

record(bo, "ACSW:UNDS:NW32:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-unds-nw32")
}

record(bo, "ACSW:UNDS:NW32:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-unds-nw32")
}

record(stringin, "ACSW:UNDS:NW32:8NAMESET") {
  field(FLNK, "ACSW:UNDS:NW32:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW32:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-unds-nw32")
  field(DOL, "ACSW:UNDS:NW32:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW32:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-unds-nw32")
  field(FLNK, "ACSW:UNDS:NW32:GETINIT")
}

record(bo, "ACSW:UNDS:NW32:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-unds-nw32")
  field(FLNK, "ACSW:UNDS:NW32:GETINIT")
}

record(stringin, "ACSW:UNDS:NW32:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW32:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW32:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW32:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW32:8INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW32:8INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW32:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW32:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW33:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:UNDS:NW33) acsw-unds-nw33")
  field(FLNK, "ACSW:UNDS:NW33:GETINFO")
}

record(stringin, "ACSW:UNDS:NW33:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:UNDS:NW33) acsw-unds-nw33")
  field(FLNK, "ACSW:UNDS:NW33:GETINIT")
}

record(stringin, "ACSW:UNDS:NW33:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:UNDS:NW33:NETFWVERSION")
  field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW33:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:UNDS:NW33:SITEID")
  field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW33:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:UNDS:NW33:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState8(ACSW:UNDS:NW33) acsw-unds-nw33")
}

record(stringin, "ACSW:UNDS:NW33:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState8(ACSW:UNDS:NW33) acsw-unds-nw33")
}

record(ai, "ACSW:UNDS:NW33:TYPE") {
  field(DESC, "APC 8 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "10")
}

record(stringin, "ACSW:UNDS:NW33:LOC") {
  field(PINI, "YES")
  field(VAL, "B920-33S")
  field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:UNDS:NW33:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-unds-nw33")
}

record(calcout, "ACSW:UNDS:NW33:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:UNDS:NW33:DISCONN.DISA")
  field(INPB, "ACSW:UNDS:NW33:DISCONN.DISV")
  field(INPC, "ACSW:UNDS:NW33:GETSTATUS.DISA")
  field(INPD, "ACSW:UNDS:NW33:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:UNDS:NW33:CONNSTA PP")
}

record(bi, "ACSW:UNDS:NW33:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:UNDS:NW33:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:UNDS:NW33:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:UNDS:NW33:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:UNDS:NW33:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:UNDS:NW33:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:UNDS:NW33:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:UNDS:NW33:UPTIMEHOUR") {
  field(FLNK, "ACSW:UNDS:NW33:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:UNDS:NW33:UPTIMEDAY") {
  field(FLNK, "ACSW:UNDS:NW33:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:UNDS:NW33:UPTIMEMINUTE") {
  field(FLNK, "ACSW:UNDS:NW33:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:UNDS:NW33:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW33:1POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW33:1POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW33:1POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW33:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW33:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW33:1POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW33:1POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW33:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW33:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-unds-nw33")
}

record(bo, "ACSW:UNDS:NW33:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-unds-nw33")
}

record(bo, "ACSW:UNDS:NW33:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-unds-nw33")
}

record(stringin, "ACSW:UNDS:NW33:1NAMESET") {
  field(FLNK, "ACSW:UNDS:NW33:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW33:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-unds-nw33")
  field(DOL, "ACSW:UNDS:NW33:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW33:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-unds-nw33")
  field(FLNK, "ACSW:UNDS:NW33:GETINIT")
}

record(bo, "ACSW:UNDS:NW33:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-unds-nw33")
  field(FLNK, "ACSW:UNDS:NW33:GETINIT")
}

record(stringin, "ACSW:UNDS:NW33:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW33:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW33:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW33:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW33:1INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW33:1INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW33:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW33:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW33:2POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW33:2POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW33:2POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW33:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW33:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW33:2POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW33:2POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW33:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW33:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-unds-nw33")
}

record(bo, "ACSW:UNDS:NW33:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-unds-nw33")
}

record(bo, "ACSW:UNDS:NW33:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-unds-nw33")
}

record(stringin, "ACSW:UNDS:NW33:2NAMESET") {
  field(FLNK, "ACSW:UNDS:NW33:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW33:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-unds-nw33")
  field(DOL, "ACSW:UNDS:NW33:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW33:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-unds-nw33")
  field(FLNK, "ACSW:UNDS:NW33:GETINIT")
}

record(bo, "ACSW:UNDS:NW33:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-unds-nw33")
  field(FLNK, "ACSW:UNDS:NW33:GETINIT")
}

record(stringin, "ACSW:UNDS:NW33:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW33:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW33:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW33:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW33:2INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW33:2INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW33:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW33:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW33:3POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW33:3POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW33:3POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW33:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW33:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW33:3POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW33:3POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW33:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW33:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-unds-nw33")
}

record(bo, "ACSW:UNDS:NW33:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-unds-nw33")
}

record(bo, "ACSW:UNDS:NW33:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-unds-nw33")
}

record(stringin, "ACSW:UNDS:NW33:3NAMESET") {
  field(FLNK, "ACSW:UNDS:NW33:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW33:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-unds-nw33")
  field(DOL, "ACSW:UNDS:NW33:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW33:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-unds-nw33")
  field(FLNK, "ACSW:UNDS:NW33:GETINIT")
}

record(bo, "ACSW:UNDS:NW33:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-unds-nw33")
  field(FLNK, "ACSW:UNDS:NW33:GETINIT")
}

record(stringin, "ACSW:UNDS:NW33:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW33:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW33:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW33:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW33:3INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW33:3INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW33:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW33:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW33:4POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW33:4POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW33:4POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW33:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW33:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW33:4POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW33:4POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW33:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW33:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-unds-nw33")
}

record(bo, "ACSW:UNDS:NW33:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-unds-nw33")
}

record(bo, "ACSW:UNDS:NW33:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-unds-nw33")
}

record(stringin, "ACSW:UNDS:NW33:4NAMESET") {
  field(FLNK, "ACSW:UNDS:NW33:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW33:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-unds-nw33")
  field(DOL, "ACSW:UNDS:NW33:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW33:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-unds-nw33")
  field(FLNK, "ACSW:UNDS:NW33:GETINIT")
}

record(bo, "ACSW:UNDS:NW33:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-unds-nw33")
  field(FLNK, "ACSW:UNDS:NW33:GETINIT")
}

record(stringin, "ACSW:UNDS:NW33:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW33:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW33:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW33:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW33:4INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW33:4INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW33:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW33:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW33:5POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW33:5POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW33:5POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW33:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW33:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW33:5POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW33:5POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW33:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW33:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-unds-nw33")
}

record(bo, "ACSW:UNDS:NW33:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-unds-nw33")
}

record(bo, "ACSW:UNDS:NW33:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-unds-nw33")
}

record(stringin, "ACSW:UNDS:NW33:5NAMESET") {
  field(FLNK, "ACSW:UNDS:NW33:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW33:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-unds-nw33")
  field(DOL, "ACSW:UNDS:NW33:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW33:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-unds-nw33")
  field(FLNK, "ACSW:UNDS:NW33:GETINIT")
}

record(bo, "ACSW:UNDS:NW33:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-unds-nw33")
  field(FLNK, "ACSW:UNDS:NW33:GETINIT")
}

record(stringin, "ACSW:UNDS:NW33:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW33:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW33:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW33:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW33:5INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW33:5INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW33:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW33:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW33:6POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW33:6POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW33:6POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW33:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW33:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW33:6POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW33:6POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW33:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW33:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-unds-nw33")
}

record(bo, "ACSW:UNDS:NW33:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-unds-nw33")
}

record(bo, "ACSW:UNDS:NW33:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-unds-nw33")
}

record(stringin, "ACSW:UNDS:NW33:6NAMESET") {
  field(FLNK, "ACSW:UNDS:NW33:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW33:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-unds-nw33")
  field(DOL, "ACSW:UNDS:NW33:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW33:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-unds-nw33")
  field(FLNK, "ACSW:UNDS:NW33:GETINIT")
}

record(bo, "ACSW:UNDS:NW33:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-unds-nw33")
  field(FLNK, "ACSW:UNDS:NW33:GETINIT")
}

record(stringin, "ACSW:UNDS:NW33:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW33:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW33:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW33:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW33:6INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW33:6INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW33:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW33:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW33:7POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW33:7POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW33:7POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW33:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW33:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW33:7POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW33:7POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW33:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW33:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-unds-nw33")
}

record(bo, "ACSW:UNDS:NW33:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-unds-nw33")
}

record(bo, "ACSW:UNDS:NW33:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-unds-nw33")
}

record(stringin, "ACSW:UNDS:NW33:7NAMESET") {
  field(FLNK, "ACSW:UNDS:NW33:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW33:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-unds-nw33")
  field(DOL, "ACSW:UNDS:NW33:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW33:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-unds-nw33")
  field(FLNK, "ACSW:UNDS:NW33:GETINIT")
}

record(bo, "ACSW:UNDS:NW33:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-unds-nw33")
  field(FLNK, "ACSW:UNDS:NW33:GETINIT")
}

record(stringin, "ACSW:UNDS:NW33:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW33:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW33:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW33:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW33:7INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW33:7INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW33:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW33:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW33:8POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW33:8POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW33:8POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW33:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW33:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW33:8POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW33:8POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW33:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW33:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-unds-nw33")
}

record(bo, "ACSW:UNDS:NW33:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-unds-nw33")
}

record(bo, "ACSW:UNDS:NW33:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-unds-nw33")
}

record(stringin, "ACSW:UNDS:NW33:8NAMESET") {
  field(FLNK, "ACSW:UNDS:NW33:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW33:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-unds-nw33")
  field(DOL, "ACSW:UNDS:NW33:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW33:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-unds-nw33")
  field(FLNK, "ACSW:UNDS:NW33:GETINIT")
}

record(bo, "ACSW:UNDS:NW33:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-unds-nw33")
  field(FLNK, "ACSW:UNDS:NW33:GETINIT")
}

record(stringin, "ACSW:UNDS:NW33:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW33:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW33:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW33:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW33:8INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW33:8INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW33:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW33:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW34:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:UNDS:NW34) acsw-unds-nw34")
  field(FLNK, "ACSW:UNDS:NW34:GETINFO")
}

record(stringin, "ACSW:UNDS:NW34:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:UNDS:NW34) acsw-unds-nw34")
  field(FLNK, "ACSW:UNDS:NW34:GETINIT")
}

record(stringin, "ACSW:UNDS:NW34:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:UNDS:NW34:NETFWVERSION")
  field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW34:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:UNDS:NW34:SITEID")
  field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW34:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:UNDS:NW34:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState8(ACSW:UNDS:NW34) acsw-unds-nw34")
}

record(stringin, "ACSW:UNDS:NW34:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState8(ACSW:UNDS:NW34) acsw-unds-nw34")
}

record(ai, "ACSW:UNDS:NW34:TYPE") {
  field(DESC, "APC 8 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "10")
}

record(stringin, "ACSW:UNDS:NW34:LOC") {
  field(PINI, "YES")
  field(VAL, "B920-34S")
  field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:UNDS:NW34:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-unds-nw34")
}

record(calcout, "ACSW:UNDS:NW34:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:UNDS:NW34:DISCONN.DISA")
  field(INPB, "ACSW:UNDS:NW34:DISCONN.DISV")
  field(INPC, "ACSW:UNDS:NW34:GETSTATUS.DISA")
  field(INPD, "ACSW:UNDS:NW34:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:UNDS:NW34:CONNSTA PP")
}

record(bi, "ACSW:UNDS:NW34:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:UNDS:NW34:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:UNDS:NW34:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:UNDS:NW34:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:UNDS:NW34:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:UNDS:NW34:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:UNDS:NW34:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:UNDS:NW34:UPTIMEHOUR") {
  field(FLNK, "ACSW:UNDS:NW34:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:UNDS:NW34:UPTIMEDAY") {
  field(FLNK, "ACSW:UNDS:NW34:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:UNDS:NW34:UPTIMEMINUTE") {
  field(FLNK, "ACSW:UNDS:NW34:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:UNDS:NW34:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW34:1POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW34:1POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW34:1POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW34:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW34:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW34:1POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW34:1POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW34:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW34:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-unds-nw34")
}

record(bo, "ACSW:UNDS:NW34:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-unds-nw34")
}

record(bo, "ACSW:UNDS:NW34:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-unds-nw34")
}

record(stringin, "ACSW:UNDS:NW34:1NAMESET") {
  field(FLNK, "ACSW:UNDS:NW34:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW34:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-unds-nw34")
  field(DOL, "ACSW:UNDS:NW34:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW34:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-unds-nw34")
  field(FLNK, "ACSW:UNDS:NW34:GETINIT")
}

record(bo, "ACSW:UNDS:NW34:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-unds-nw34")
  field(FLNK, "ACSW:UNDS:NW34:GETINIT")
}

record(stringin, "ACSW:UNDS:NW34:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW34:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW34:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW34:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW34:1INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW34:1INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW34:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW34:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW34:2POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW34:2POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW34:2POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW34:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW34:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW34:2POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW34:2POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW34:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW34:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-unds-nw34")
}

record(bo, "ACSW:UNDS:NW34:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-unds-nw34")
}

record(bo, "ACSW:UNDS:NW34:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-unds-nw34")
}

record(stringin, "ACSW:UNDS:NW34:2NAMESET") {
  field(FLNK, "ACSW:UNDS:NW34:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW34:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-unds-nw34")
  field(DOL, "ACSW:UNDS:NW34:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW34:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-unds-nw34")
  field(FLNK, "ACSW:UNDS:NW34:GETINIT")
}

record(bo, "ACSW:UNDS:NW34:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-unds-nw34")
  field(FLNK, "ACSW:UNDS:NW34:GETINIT")
}

record(stringin, "ACSW:UNDS:NW34:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW34:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW34:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW34:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW34:2INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW34:2INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW34:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW34:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW34:3POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW34:3POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW34:3POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW34:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW34:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW34:3POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW34:3POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW34:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW34:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-unds-nw34")
}

record(bo, "ACSW:UNDS:NW34:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-unds-nw34")
}

record(bo, "ACSW:UNDS:NW34:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-unds-nw34")
}

record(stringin, "ACSW:UNDS:NW34:3NAMESET") {
  field(FLNK, "ACSW:UNDS:NW34:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW34:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-unds-nw34")
  field(DOL, "ACSW:UNDS:NW34:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW34:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-unds-nw34")
  field(FLNK, "ACSW:UNDS:NW34:GETINIT")
}

record(bo, "ACSW:UNDS:NW34:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-unds-nw34")
  field(FLNK, "ACSW:UNDS:NW34:GETINIT")
}

record(stringin, "ACSW:UNDS:NW34:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW34:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW34:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW34:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW34:3INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW34:3INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW34:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW34:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW34:4POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW34:4POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW34:4POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW34:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW34:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW34:4POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW34:4POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW34:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW34:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-unds-nw34")
}

record(bo, "ACSW:UNDS:NW34:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-unds-nw34")
}

record(bo, "ACSW:UNDS:NW34:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-unds-nw34")
}

record(stringin, "ACSW:UNDS:NW34:4NAMESET") {
  field(FLNK, "ACSW:UNDS:NW34:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW34:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-unds-nw34")
  field(DOL, "ACSW:UNDS:NW34:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW34:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-unds-nw34")
  field(FLNK, "ACSW:UNDS:NW34:GETINIT")
}

record(bo, "ACSW:UNDS:NW34:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-unds-nw34")
  field(FLNK, "ACSW:UNDS:NW34:GETINIT")
}

record(stringin, "ACSW:UNDS:NW34:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW34:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW34:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW34:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW34:4INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW34:4INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW34:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW34:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW34:5POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW34:5POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW34:5POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW34:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW34:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW34:5POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW34:5POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW34:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW34:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-unds-nw34")
}

record(bo, "ACSW:UNDS:NW34:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-unds-nw34")
}

record(bo, "ACSW:UNDS:NW34:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-unds-nw34")
}

record(stringin, "ACSW:UNDS:NW34:5NAMESET") {
  field(FLNK, "ACSW:UNDS:NW34:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW34:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-unds-nw34")
  field(DOL, "ACSW:UNDS:NW34:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW34:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-unds-nw34")
  field(FLNK, "ACSW:UNDS:NW34:GETINIT")
}

record(bo, "ACSW:UNDS:NW34:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-unds-nw34")
  field(FLNK, "ACSW:UNDS:NW34:GETINIT")
}

record(stringin, "ACSW:UNDS:NW34:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW34:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW34:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW34:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW34:5INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW34:5INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW34:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW34:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW34:6POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW34:6POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW34:6POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW34:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW34:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW34:6POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW34:6POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW34:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW34:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-unds-nw34")
}

record(bo, "ACSW:UNDS:NW34:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-unds-nw34")
}

record(bo, "ACSW:UNDS:NW34:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-unds-nw34")
}

record(stringin, "ACSW:UNDS:NW34:6NAMESET") {
  field(FLNK, "ACSW:UNDS:NW34:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW34:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-unds-nw34")
  field(DOL, "ACSW:UNDS:NW34:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW34:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-unds-nw34")
  field(FLNK, "ACSW:UNDS:NW34:GETINIT")
}

record(bo, "ACSW:UNDS:NW34:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-unds-nw34")
  field(FLNK, "ACSW:UNDS:NW34:GETINIT")
}

record(stringin, "ACSW:UNDS:NW34:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW34:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW34:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW34:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW34:6INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW34:6INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW34:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW34:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW34:7POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW34:7POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW34:7POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW34:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW34:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW34:7POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW34:7POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW34:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW34:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-unds-nw34")
}

record(bo, "ACSW:UNDS:NW34:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-unds-nw34")
}

record(bo, "ACSW:UNDS:NW34:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-unds-nw34")
}

record(stringin, "ACSW:UNDS:NW34:7NAMESET") {
  field(FLNK, "ACSW:UNDS:NW34:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW34:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-unds-nw34")
  field(DOL, "ACSW:UNDS:NW34:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW34:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-unds-nw34")
  field(FLNK, "ACSW:UNDS:NW34:GETINIT")
}

record(bo, "ACSW:UNDS:NW34:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-unds-nw34")
  field(FLNK, "ACSW:UNDS:NW34:GETINIT")
}

record(stringin, "ACSW:UNDS:NW34:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW34:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW34:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW34:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW34:7INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW34:7INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW34:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW34:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW34:8POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW34:8POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW34:8POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW34:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW34:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW34:8POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW34:8POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW34:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW34:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-unds-nw34")
}

record(bo, "ACSW:UNDS:NW34:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-unds-nw34")
}

record(bo, "ACSW:UNDS:NW34:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-unds-nw34")
}

record(stringin, "ACSW:UNDS:NW34:8NAMESET") {
  field(FLNK, "ACSW:UNDS:NW34:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW34:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-unds-nw34")
  field(DOL, "ACSW:UNDS:NW34:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW34:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-unds-nw34")
  field(FLNK, "ACSW:UNDS:NW34:GETINIT")
}

record(bo, "ACSW:UNDS:NW34:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-unds-nw34")
  field(FLNK, "ACSW:UNDS:NW34:GETINIT")
}

record(stringin, "ACSW:UNDS:NW34:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW34:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW34:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW34:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW34:8INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW34:8INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW34:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW34:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW35:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:UNDS:NW35) acsw-unds-nw35")
  field(FLNK, "ACSW:UNDS:NW35:GETINFO")
}

record(stringin, "ACSW:UNDS:NW35:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:UNDS:NW35) acsw-unds-nw35")
  field(FLNK, "ACSW:UNDS:NW35:GETINIT")
}

record(stringin, "ACSW:UNDS:NW35:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:UNDS:NW35:NETFWVERSION")
  field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW35:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:UNDS:NW35:SITEID")
  field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW35:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:UNDS:NW35:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState8(ACSW:UNDS:NW35) acsw-unds-nw35")
}

record(stringin, "ACSW:UNDS:NW35:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState8(ACSW:UNDS:NW35) acsw-unds-nw35")
}

record(ai, "ACSW:UNDS:NW35:TYPE") {
  field(DESC, "APC 8 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "10")
}

record(stringin, "ACSW:UNDS:NW35:LOC") {
  field(PINI, "YES")
  field(VAL, "B920-35S")
  field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:UNDS:NW35:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-unds-nw35")
}

record(calcout, "ACSW:UNDS:NW35:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:UNDS:NW35:DISCONN.DISA")
  field(INPB, "ACSW:UNDS:NW35:DISCONN.DISV")
  field(INPC, "ACSW:UNDS:NW35:GETSTATUS.DISA")
  field(INPD, "ACSW:UNDS:NW35:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:UNDS:NW35:CONNSTA PP")
}

record(bi, "ACSW:UNDS:NW35:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:UNDS:NW35:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:UNDS:NW35:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:UNDS:NW35:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:UNDS:NW35:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:UNDS:NW35:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:UNDS:NW35:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:UNDS:NW35:UPTIMEHOUR") {
  field(FLNK, "ACSW:UNDS:NW35:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:UNDS:NW35:UPTIMEDAY") {
  field(FLNK, "ACSW:UNDS:NW35:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:UNDS:NW35:UPTIMEMINUTE") {
  field(FLNK, "ACSW:UNDS:NW35:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:UNDS:NW35:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW35:1POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW35:1POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW35:1POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW35:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW35:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW35:1POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW35:1POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW35:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW35:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-unds-nw35")
}

record(bo, "ACSW:UNDS:NW35:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-unds-nw35")
}

record(bo, "ACSW:UNDS:NW35:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-unds-nw35")
}

record(stringin, "ACSW:UNDS:NW35:1NAMESET") {
  field(FLNK, "ACSW:UNDS:NW35:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW35:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-unds-nw35")
  field(DOL, "ACSW:UNDS:NW35:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW35:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-unds-nw35")
  field(FLNK, "ACSW:UNDS:NW35:GETINIT")
}

record(bo, "ACSW:UNDS:NW35:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-unds-nw35")
  field(FLNK, "ACSW:UNDS:NW35:GETINIT")
}

record(stringin, "ACSW:UNDS:NW35:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW35:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW35:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW35:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW35:1INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW35:1INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW35:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW35:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW35:2POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW35:2POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW35:2POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW35:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW35:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW35:2POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW35:2POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW35:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW35:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-unds-nw35")
}

record(bo, "ACSW:UNDS:NW35:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-unds-nw35")
}

record(bo, "ACSW:UNDS:NW35:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-unds-nw35")
}

record(stringin, "ACSW:UNDS:NW35:2NAMESET") {
  field(FLNK, "ACSW:UNDS:NW35:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW35:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-unds-nw35")
  field(DOL, "ACSW:UNDS:NW35:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW35:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-unds-nw35")
  field(FLNK, "ACSW:UNDS:NW35:GETINIT")
}

record(bo, "ACSW:UNDS:NW35:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-unds-nw35")
  field(FLNK, "ACSW:UNDS:NW35:GETINIT")
}

record(stringin, "ACSW:UNDS:NW35:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW35:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW35:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW35:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW35:2INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW35:2INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW35:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW35:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW35:3POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW35:3POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW35:3POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW35:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW35:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW35:3POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW35:3POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW35:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW35:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-unds-nw35")
}

record(bo, "ACSW:UNDS:NW35:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-unds-nw35")
}

record(bo, "ACSW:UNDS:NW35:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-unds-nw35")
}

record(stringin, "ACSW:UNDS:NW35:3NAMESET") {
  field(FLNK, "ACSW:UNDS:NW35:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW35:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-unds-nw35")
  field(DOL, "ACSW:UNDS:NW35:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW35:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-unds-nw35")
  field(FLNK, "ACSW:UNDS:NW35:GETINIT")
}

record(bo, "ACSW:UNDS:NW35:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-unds-nw35")
  field(FLNK, "ACSW:UNDS:NW35:GETINIT")
}

record(stringin, "ACSW:UNDS:NW35:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW35:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW35:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW35:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW35:3INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW35:3INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW35:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW35:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW35:4POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW35:4POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW35:4POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW35:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW35:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW35:4POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW35:4POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW35:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW35:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-unds-nw35")
}

record(bo, "ACSW:UNDS:NW35:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-unds-nw35")
}

record(bo, "ACSW:UNDS:NW35:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-unds-nw35")
}

record(stringin, "ACSW:UNDS:NW35:4NAMESET") {
  field(FLNK, "ACSW:UNDS:NW35:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW35:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-unds-nw35")
  field(DOL, "ACSW:UNDS:NW35:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW35:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-unds-nw35")
  field(FLNK, "ACSW:UNDS:NW35:GETINIT")
}

record(bo, "ACSW:UNDS:NW35:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-unds-nw35")
  field(FLNK, "ACSW:UNDS:NW35:GETINIT")
}

record(stringin, "ACSW:UNDS:NW35:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW35:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW35:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW35:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW35:4INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW35:4INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW35:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW35:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW35:5POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW35:5POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW35:5POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW35:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW35:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW35:5POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW35:5POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW35:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW35:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-unds-nw35")
}

record(bo, "ACSW:UNDS:NW35:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-unds-nw35")
}

record(bo, "ACSW:UNDS:NW35:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-unds-nw35")
}

record(stringin, "ACSW:UNDS:NW35:5NAMESET") {
  field(FLNK, "ACSW:UNDS:NW35:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW35:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-unds-nw35")
  field(DOL, "ACSW:UNDS:NW35:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW35:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-unds-nw35")
  field(FLNK, "ACSW:UNDS:NW35:GETINIT")
}

record(bo, "ACSW:UNDS:NW35:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-unds-nw35")
  field(FLNK, "ACSW:UNDS:NW35:GETINIT")
}

record(stringin, "ACSW:UNDS:NW35:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW35:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW35:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW35:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW35:5INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW35:5INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW35:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW35:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW35:6POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW35:6POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW35:6POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW35:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW35:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW35:6POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW35:6POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW35:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW35:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-unds-nw35")
}

record(bo, "ACSW:UNDS:NW35:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-unds-nw35")
}

record(bo, "ACSW:UNDS:NW35:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-unds-nw35")
}

record(stringin, "ACSW:UNDS:NW35:6NAMESET") {
  field(FLNK, "ACSW:UNDS:NW35:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW35:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-unds-nw35")
  field(DOL, "ACSW:UNDS:NW35:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW35:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-unds-nw35")
  field(FLNK, "ACSW:UNDS:NW35:GETINIT")
}

record(bo, "ACSW:UNDS:NW35:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-unds-nw35")
  field(FLNK, "ACSW:UNDS:NW35:GETINIT")
}

record(stringin, "ACSW:UNDS:NW35:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW35:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW35:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW35:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW35:6INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW35:6INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW35:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW35:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW35:7POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW35:7POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW35:7POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW35:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW35:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW35:7POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW35:7POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW35:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW35:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-unds-nw35")
}

record(bo, "ACSW:UNDS:NW35:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-unds-nw35")
}

record(bo, "ACSW:UNDS:NW35:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-unds-nw35")
}

record(stringin, "ACSW:UNDS:NW35:7NAMESET") {
  field(FLNK, "ACSW:UNDS:NW35:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW35:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-unds-nw35")
  field(DOL, "ACSW:UNDS:NW35:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW35:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-unds-nw35")
  field(FLNK, "ACSW:UNDS:NW35:GETINIT")
}

record(bo, "ACSW:UNDS:NW35:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-unds-nw35")
  field(FLNK, "ACSW:UNDS:NW35:GETINIT")
}

record(stringin, "ACSW:UNDS:NW35:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW35:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW35:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW35:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW35:7INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW35:7INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW35:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW35:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW35:8POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW35:8POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW35:8POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW35:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW35:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW35:8POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW35:8POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW35:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW35:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-unds-nw35")
}

record(bo, "ACSW:UNDS:NW35:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-unds-nw35")
}

record(bo, "ACSW:UNDS:NW35:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-unds-nw35")
}

record(stringin, "ACSW:UNDS:NW35:8NAMESET") {
  field(FLNK, "ACSW:UNDS:NW35:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW35:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-unds-nw35")
  field(DOL, "ACSW:UNDS:NW35:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW35:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-unds-nw35")
  field(FLNK, "ACSW:UNDS:NW35:GETINIT")
}

record(bo, "ACSW:UNDS:NW35:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-unds-nw35")
  field(FLNK, "ACSW:UNDS:NW35:GETINIT")
}

record(stringin, "ACSW:UNDS:NW35:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW35:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW35:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW35:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW35:8INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW35:8INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW35:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW35:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW36:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:UNDS:NW36) acsw-unds-nw36")
  field(FLNK, "ACSW:UNDS:NW36:GETINFO")
}

record(stringin, "ACSW:UNDS:NW36:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:UNDS:NW36) acsw-unds-nw36")
  field(FLNK, "ACSW:UNDS:NW36:GETINIT")
}

record(stringin, "ACSW:UNDS:NW36:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:UNDS:NW36:NETFWVERSION")
  field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW36:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:UNDS:NW36:SITEID")
  field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW36:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:UNDS:NW36:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState8(ACSW:UNDS:NW36) acsw-unds-nw36")
}

record(stringin, "ACSW:UNDS:NW36:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState8(ACSW:UNDS:NW36) acsw-unds-nw36")
}

record(ai, "ACSW:UNDS:NW36:TYPE") {
  field(DESC, "APC 8 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "10")
}

record(stringin, "ACSW:UNDS:NW36:LOC") {
  field(PINI, "YES")
  field(VAL, "B920-36S")
  field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:UNDS:NW36:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-unds-nw36")
}

record(calcout, "ACSW:UNDS:NW36:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:UNDS:NW36:DISCONN.DISA")
  field(INPB, "ACSW:UNDS:NW36:DISCONN.DISV")
  field(INPC, "ACSW:UNDS:NW36:GETSTATUS.DISA")
  field(INPD, "ACSW:UNDS:NW36:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:UNDS:NW36:CONNSTA PP")
}

record(bi, "ACSW:UNDS:NW36:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:UNDS:NW36:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:UNDS:NW36:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:UNDS:NW36:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:UNDS:NW36:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:UNDS:NW36:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:UNDS:NW36:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:UNDS:NW36:UPTIMEHOUR") {
  field(FLNK, "ACSW:UNDS:NW36:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:UNDS:NW36:UPTIMEDAY") {
  field(FLNK, "ACSW:UNDS:NW36:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:UNDS:NW36:UPTIMEMINUTE") {
  field(FLNK, "ACSW:UNDS:NW36:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:UNDS:NW36:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW36:1POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW36:1POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW36:1POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW36:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW36:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW36:1POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW36:1POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW36:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW36:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-unds-nw36")
}

record(bo, "ACSW:UNDS:NW36:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-unds-nw36")
}

record(bo, "ACSW:UNDS:NW36:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-unds-nw36")
}

record(stringin, "ACSW:UNDS:NW36:1NAMESET") {
  field(FLNK, "ACSW:UNDS:NW36:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW36:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-unds-nw36")
  field(DOL, "ACSW:UNDS:NW36:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW36:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-unds-nw36")
  field(FLNK, "ACSW:UNDS:NW36:GETINIT")
}

record(bo, "ACSW:UNDS:NW36:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-unds-nw36")
  field(FLNK, "ACSW:UNDS:NW36:GETINIT")
}

record(stringin, "ACSW:UNDS:NW36:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW36:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW36:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW36:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW36:1INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW36:1INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW36:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW36:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW36:2POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW36:2POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW36:2POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW36:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW36:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW36:2POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW36:2POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW36:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW36:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-unds-nw36")
}

record(bo, "ACSW:UNDS:NW36:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-unds-nw36")
}

record(bo, "ACSW:UNDS:NW36:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-unds-nw36")
}

record(stringin, "ACSW:UNDS:NW36:2NAMESET") {
  field(FLNK, "ACSW:UNDS:NW36:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW36:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-unds-nw36")
  field(DOL, "ACSW:UNDS:NW36:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW36:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-unds-nw36")
  field(FLNK, "ACSW:UNDS:NW36:GETINIT")
}

record(bo, "ACSW:UNDS:NW36:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-unds-nw36")
  field(FLNK, "ACSW:UNDS:NW36:GETINIT")
}

record(stringin, "ACSW:UNDS:NW36:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW36:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW36:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW36:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW36:2INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW36:2INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW36:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW36:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW36:3POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW36:3POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW36:3POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW36:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW36:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW36:3POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW36:3POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW36:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW36:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-unds-nw36")
}

record(bo, "ACSW:UNDS:NW36:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-unds-nw36")
}

record(bo, "ACSW:UNDS:NW36:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-unds-nw36")
}

record(stringin, "ACSW:UNDS:NW36:3NAMESET") {
  field(FLNK, "ACSW:UNDS:NW36:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW36:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-unds-nw36")
  field(DOL, "ACSW:UNDS:NW36:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW36:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-unds-nw36")
  field(FLNK, "ACSW:UNDS:NW36:GETINIT")
}

record(bo, "ACSW:UNDS:NW36:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-unds-nw36")
  field(FLNK, "ACSW:UNDS:NW36:GETINIT")
}

record(stringin, "ACSW:UNDS:NW36:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW36:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW36:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW36:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW36:3INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW36:3INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW36:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW36:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW36:4POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW36:4POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW36:4POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW36:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW36:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW36:4POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW36:4POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW36:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW36:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-unds-nw36")
}

record(bo, "ACSW:UNDS:NW36:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-unds-nw36")
}

record(bo, "ACSW:UNDS:NW36:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-unds-nw36")
}

record(stringin, "ACSW:UNDS:NW36:4NAMESET") {
  field(FLNK, "ACSW:UNDS:NW36:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW36:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-unds-nw36")
  field(DOL, "ACSW:UNDS:NW36:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW36:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-unds-nw36")
  field(FLNK, "ACSW:UNDS:NW36:GETINIT")
}

record(bo, "ACSW:UNDS:NW36:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-unds-nw36")
  field(FLNK, "ACSW:UNDS:NW36:GETINIT")
}

record(stringin, "ACSW:UNDS:NW36:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW36:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW36:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW36:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW36:4INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW36:4INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW36:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW36:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW36:5POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW36:5POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW36:5POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW36:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW36:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW36:5POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW36:5POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW36:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW36:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-unds-nw36")
}

record(bo, "ACSW:UNDS:NW36:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-unds-nw36")
}

record(bo, "ACSW:UNDS:NW36:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-unds-nw36")
}

record(stringin, "ACSW:UNDS:NW36:5NAMESET") {
  field(FLNK, "ACSW:UNDS:NW36:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW36:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-unds-nw36")
  field(DOL, "ACSW:UNDS:NW36:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW36:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-unds-nw36")
  field(FLNK, "ACSW:UNDS:NW36:GETINIT")
}

record(bo, "ACSW:UNDS:NW36:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-unds-nw36")
  field(FLNK, "ACSW:UNDS:NW36:GETINIT")
}

record(stringin, "ACSW:UNDS:NW36:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW36:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW36:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW36:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW36:5INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW36:5INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW36:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW36:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW36:6POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW36:6POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW36:6POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW36:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW36:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW36:6POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW36:6POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW36:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW36:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-unds-nw36")
}

record(bo, "ACSW:UNDS:NW36:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-unds-nw36")
}

record(bo, "ACSW:UNDS:NW36:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-unds-nw36")
}

record(stringin, "ACSW:UNDS:NW36:6NAMESET") {
  field(FLNK, "ACSW:UNDS:NW36:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW36:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-unds-nw36")
  field(DOL, "ACSW:UNDS:NW36:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW36:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-unds-nw36")
  field(FLNK, "ACSW:UNDS:NW36:GETINIT")
}

record(bo, "ACSW:UNDS:NW36:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-unds-nw36")
  field(FLNK, "ACSW:UNDS:NW36:GETINIT")
}

record(stringin, "ACSW:UNDS:NW36:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW36:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW36:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW36:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW36:6INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW36:6INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW36:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW36:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW36:7POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW36:7POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW36:7POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW36:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW36:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW36:7POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW36:7POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW36:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW36:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-unds-nw36")
}

record(bo, "ACSW:UNDS:NW36:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-unds-nw36")
}

record(bo, "ACSW:UNDS:NW36:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-unds-nw36")
}

record(stringin, "ACSW:UNDS:NW36:7NAMESET") {
  field(FLNK, "ACSW:UNDS:NW36:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW36:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-unds-nw36")
  field(DOL, "ACSW:UNDS:NW36:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW36:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-unds-nw36")
  field(FLNK, "ACSW:UNDS:NW36:GETINIT")
}

record(bo, "ACSW:UNDS:NW36:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-unds-nw36")
  field(FLNK, "ACSW:UNDS:NW36:GETINIT")
}

record(stringin, "ACSW:UNDS:NW36:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW36:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW36:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW36:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW36:7INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW36:7INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW36:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW36:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW36:8POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW36:8POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW36:8POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW36:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW36:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW36:8POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW36:8POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW36:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW36:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-unds-nw36")
}

record(bo, "ACSW:UNDS:NW36:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-unds-nw36")
}

record(bo, "ACSW:UNDS:NW36:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-unds-nw36")
}

record(stringin, "ACSW:UNDS:NW36:8NAMESET") {
  field(FLNK, "ACSW:UNDS:NW36:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW36:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-unds-nw36")
  field(DOL, "ACSW:UNDS:NW36:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW36:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-unds-nw36")
  field(FLNK, "ACSW:UNDS:NW36:GETINIT")
}

record(bo, "ACSW:UNDS:NW36:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-unds-nw36")
  field(FLNK, "ACSW:UNDS:NW36:GETINIT")
}

record(stringin, "ACSW:UNDS:NW36:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW36:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW36:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW36:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW36:8INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW36:8INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW36:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW36:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW37:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:UNDS:NW37) acsw-unds-nw37")
  field(FLNK, "ACSW:UNDS:NW37:GETINFO")
}

record(stringin, "ACSW:UNDS:NW37:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:UNDS:NW37) acsw-unds-nw37")
  field(FLNK, "ACSW:UNDS:NW37:GETINIT")
}

record(stringin, "ACSW:UNDS:NW37:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:UNDS:NW37:NETFWVERSION")
  field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW37:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:UNDS:NW37:SITEID")
  field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW37:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:UNDS:NW37:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState8(ACSW:UNDS:NW37) acsw-unds-nw37")
}

record(stringin, "ACSW:UNDS:NW37:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState8(ACSW:UNDS:NW37) acsw-unds-nw37")
}

record(ai, "ACSW:UNDS:NW37:TYPE") {
  field(DESC, "APC 8 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "10")
}

record(stringin, "ACSW:UNDS:NW37:LOC") {
  field(PINI, "YES")
  field(VAL, "B920-37S")
  field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:UNDS:NW37:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-unds-nw37")
}

record(calcout, "ACSW:UNDS:NW37:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:UNDS:NW37:DISCONN.DISA")
  field(INPB, "ACSW:UNDS:NW37:DISCONN.DISV")
  field(INPC, "ACSW:UNDS:NW37:GETSTATUS.DISA")
  field(INPD, "ACSW:UNDS:NW37:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:UNDS:NW37:CONNSTA PP")
}

record(bi, "ACSW:UNDS:NW37:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:UNDS:NW37:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:UNDS:NW37:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:UNDS:NW37:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:UNDS:NW37:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:UNDS:NW37:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:UNDS:NW37:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:UNDS:NW37:UPTIMEHOUR") {
  field(FLNK, "ACSW:UNDS:NW37:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:UNDS:NW37:UPTIMEDAY") {
  field(FLNK, "ACSW:UNDS:NW37:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:UNDS:NW37:UPTIMEMINUTE") {
  field(FLNK, "ACSW:UNDS:NW37:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:UNDS:NW37:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW37:1POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW37:1POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW37:1POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW37:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW37:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW37:1POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW37:1POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW37:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW37:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-unds-nw37")
}

record(bo, "ACSW:UNDS:NW37:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-unds-nw37")
}

record(bo, "ACSW:UNDS:NW37:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-unds-nw37")
}

record(stringin, "ACSW:UNDS:NW37:1NAMESET") {
  field(FLNK, "ACSW:UNDS:NW37:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW37:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-unds-nw37")
  field(DOL, "ACSW:UNDS:NW37:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW37:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-unds-nw37")
  field(FLNK, "ACSW:UNDS:NW37:GETINIT")
}

record(bo, "ACSW:UNDS:NW37:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-unds-nw37")
  field(FLNK, "ACSW:UNDS:NW37:GETINIT")
}

record(stringin, "ACSW:UNDS:NW37:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW37:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW37:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW37:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW37:1INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW37:1INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW37:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW37:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW37:2POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW37:2POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW37:2POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW37:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW37:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW37:2POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW37:2POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW37:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW37:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-unds-nw37")
}

record(bo, "ACSW:UNDS:NW37:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-unds-nw37")
}

record(bo, "ACSW:UNDS:NW37:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-unds-nw37")
}

record(stringin, "ACSW:UNDS:NW37:2NAMESET") {
  field(FLNK, "ACSW:UNDS:NW37:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW37:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-unds-nw37")
  field(DOL, "ACSW:UNDS:NW37:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW37:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-unds-nw37")
  field(FLNK, "ACSW:UNDS:NW37:GETINIT")
}

record(bo, "ACSW:UNDS:NW37:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-unds-nw37")
  field(FLNK, "ACSW:UNDS:NW37:GETINIT")
}

record(stringin, "ACSW:UNDS:NW37:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW37:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW37:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW37:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW37:2INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW37:2INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW37:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW37:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW37:3POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW37:3POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW37:3POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW37:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW37:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW37:3POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW37:3POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW37:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW37:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-unds-nw37")
}

record(bo, "ACSW:UNDS:NW37:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-unds-nw37")
}

record(bo, "ACSW:UNDS:NW37:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-unds-nw37")
}

record(stringin, "ACSW:UNDS:NW37:3NAMESET") {
  field(FLNK, "ACSW:UNDS:NW37:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW37:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-unds-nw37")
  field(DOL, "ACSW:UNDS:NW37:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW37:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-unds-nw37")
  field(FLNK, "ACSW:UNDS:NW37:GETINIT")
}

record(bo, "ACSW:UNDS:NW37:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-unds-nw37")
  field(FLNK, "ACSW:UNDS:NW37:GETINIT")
}

record(stringin, "ACSW:UNDS:NW37:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW37:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW37:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW37:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW37:3INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW37:3INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW37:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW37:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW37:4POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW37:4POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW37:4POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW37:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW37:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW37:4POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW37:4POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW37:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW37:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-unds-nw37")
}

record(bo, "ACSW:UNDS:NW37:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-unds-nw37")
}

record(bo, "ACSW:UNDS:NW37:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-unds-nw37")
}

record(stringin, "ACSW:UNDS:NW37:4NAMESET") {
  field(FLNK, "ACSW:UNDS:NW37:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW37:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-unds-nw37")
  field(DOL, "ACSW:UNDS:NW37:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW37:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-unds-nw37")
  field(FLNK, "ACSW:UNDS:NW37:GETINIT")
}

record(bo, "ACSW:UNDS:NW37:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-unds-nw37")
  field(FLNK, "ACSW:UNDS:NW37:GETINIT")
}

record(stringin, "ACSW:UNDS:NW37:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW37:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW37:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW37:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW37:4INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW37:4INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW37:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW37:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW37:5POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW37:5POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW37:5POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW37:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW37:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW37:5POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW37:5POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW37:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW37:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-unds-nw37")
}

record(bo, "ACSW:UNDS:NW37:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-unds-nw37")
}

record(bo, "ACSW:UNDS:NW37:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-unds-nw37")
}

record(stringin, "ACSW:UNDS:NW37:5NAMESET") {
  field(FLNK, "ACSW:UNDS:NW37:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW37:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-unds-nw37")
  field(DOL, "ACSW:UNDS:NW37:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW37:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-unds-nw37")
  field(FLNK, "ACSW:UNDS:NW37:GETINIT")
}

record(bo, "ACSW:UNDS:NW37:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-unds-nw37")
  field(FLNK, "ACSW:UNDS:NW37:GETINIT")
}

record(stringin, "ACSW:UNDS:NW37:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW37:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW37:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW37:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW37:5INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW37:5INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW37:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW37:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW37:6POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW37:6POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW37:6POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW37:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW37:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW37:6POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW37:6POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW37:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW37:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-unds-nw37")
}

record(bo, "ACSW:UNDS:NW37:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-unds-nw37")
}

record(bo, "ACSW:UNDS:NW37:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-unds-nw37")
}

record(stringin, "ACSW:UNDS:NW37:6NAMESET") {
  field(FLNK, "ACSW:UNDS:NW37:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW37:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-unds-nw37")
  field(DOL, "ACSW:UNDS:NW37:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW37:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-unds-nw37")
  field(FLNK, "ACSW:UNDS:NW37:GETINIT")
}

record(bo, "ACSW:UNDS:NW37:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-unds-nw37")
  field(FLNK, "ACSW:UNDS:NW37:GETINIT")
}

record(stringin, "ACSW:UNDS:NW37:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW37:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW37:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW37:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW37:6INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW37:6INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW37:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW37:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW37:7POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW37:7POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW37:7POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW37:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW37:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW37:7POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW37:7POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW37:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW37:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-unds-nw37")
}

record(bo, "ACSW:UNDS:NW37:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-unds-nw37")
}

record(bo, "ACSW:UNDS:NW37:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-unds-nw37")
}

record(stringin, "ACSW:UNDS:NW37:7NAMESET") {
  field(FLNK, "ACSW:UNDS:NW37:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW37:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-unds-nw37")
  field(DOL, "ACSW:UNDS:NW37:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW37:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-unds-nw37")
  field(FLNK, "ACSW:UNDS:NW37:GETINIT")
}

record(bo, "ACSW:UNDS:NW37:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-unds-nw37")
  field(FLNK, "ACSW:UNDS:NW37:GETINIT")
}

record(stringin, "ACSW:UNDS:NW37:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW37:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW37:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW37:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW37:7INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW37:7INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW37:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW37:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW37:8POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW37:8POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW37:8POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW37:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW37:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW37:8POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW37:8POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW37:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW37:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-unds-nw37")
}

record(bo, "ACSW:UNDS:NW37:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-unds-nw37")
}

record(bo, "ACSW:UNDS:NW37:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-unds-nw37")
}

record(stringin, "ACSW:UNDS:NW37:8NAMESET") {
  field(FLNK, "ACSW:UNDS:NW37:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW37:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-unds-nw37")
  field(DOL, "ACSW:UNDS:NW37:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW37:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-unds-nw37")
  field(FLNK, "ACSW:UNDS:NW37:GETINIT")
}

record(bo, "ACSW:UNDS:NW37:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-unds-nw37")
  field(FLNK, "ACSW:UNDS:NW37:GETINIT")
}

record(stringin, "ACSW:UNDS:NW37:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW37:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW37:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW37:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW37:8INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW37:8INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW37:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW37:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW38:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:UNDS:NW38) acsw-unds-nw38")
  field(FLNK, "ACSW:UNDS:NW38:GETINFO")
}

record(stringin, "ACSW:UNDS:NW38:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:UNDS:NW38) acsw-unds-nw38")
  field(FLNK, "ACSW:UNDS:NW38:GETINIT")
}

record(stringin, "ACSW:UNDS:NW38:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:UNDS:NW38:NETFWVERSION")
  field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW38:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:UNDS:NW38:SITEID")
  field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW38:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:UNDS:NW38:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState8(ACSW:UNDS:NW38) acsw-unds-nw38")
}

record(stringin, "ACSW:UNDS:NW38:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState8(ACSW:UNDS:NW38) acsw-unds-nw38")
}

record(ai, "ACSW:UNDS:NW38:TYPE") {
  field(DESC, "APC 8 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "10")
}

record(stringin, "ACSW:UNDS:NW38:LOC") {
  field(PINI, "YES")
  field(VAL, "B920-38S")
  field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:UNDS:NW38:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-unds-nw38")
}

record(calcout, "ACSW:UNDS:NW38:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:UNDS:NW38:DISCONN.DISA")
  field(INPB, "ACSW:UNDS:NW38:DISCONN.DISV")
  field(INPC, "ACSW:UNDS:NW38:GETSTATUS.DISA")
  field(INPD, "ACSW:UNDS:NW38:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:UNDS:NW38:CONNSTA PP")
}

record(bi, "ACSW:UNDS:NW38:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:UNDS:NW38:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:UNDS:NW38:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:UNDS:NW38:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:UNDS:NW38:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:UNDS:NW38:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:UNDS:NW38:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:UNDS:NW38:UPTIMEHOUR") {
  field(FLNK, "ACSW:UNDS:NW38:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:UNDS:NW38:UPTIMEDAY") {
  field(FLNK, "ACSW:UNDS:NW38:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:UNDS:NW38:UPTIMEMINUTE") {
  field(FLNK, "ACSW:UNDS:NW38:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:UNDS:NW38:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW38:1POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW38:1POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW38:1POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW38:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW38:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW38:1POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW38:1POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW38:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW38:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-unds-nw38")
}

record(bo, "ACSW:UNDS:NW38:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-unds-nw38")
}

record(bo, "ACSW:UNDS:NW38:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-unds-nw38")
}

record(stringin, "ACSW:UNDS:NW38:1NAMESET") {
  field(FLNK, "ACSW:UNDS:NW38:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW38:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-unds-nw38")
  field(DOL, "ACSW:UNDS:NW38:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW38:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-unds-nw38")
  field(FLNK, "ACSW:UNDS:NW38:GETINIT")
}

record(bo, "ACSW:UNDS:NW38:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-unds-nw38")
  field(FLNK, "ACSW:UNDS:NW38:GETINIT")
}

record(stringin, "ACSW:UNDS:NW38:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW38:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW38:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW38:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW38:1INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW38:1INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW38:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW38:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW38:2POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW38:2POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW38:2POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW38:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW38:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW38:2POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW38:2POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW38:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW38:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-unds-nw38")
}

record(bo, "ACSW:UNDS:NW38:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-unds-nw38")
}

record(bo, "ACSW:UNDS:NW38:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-unds-nw38")
}

record(stringin, "ACSW:UNDS:NW38:2NAMESET") {
  field(FLNK, "ACSW:UNDS:NW38:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW38:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-unds-nw38")
  field(DOL, "ACSW:UNDS:NW38:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW38:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-unds-nw38")
  field(FLNK, "ACSW:UNDS:NW38:GETINIT")
}

record(bo, "ACSW:UNDS:NW38:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-unds-nw38")
  field(FLNK, "ACSW:UNDS:NW38:GETINIT")
}

record(stringin, "ACSW:UNDS:NW38:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW38:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW38:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW38:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW38:2INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW38:2INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW38:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW38:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW38:3POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW38:3POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW38:3POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW38:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW38:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW38:3POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW38:3POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW38:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW38:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-unds-nw38")
}

record(bo, "ACSW:UNDS:NW38:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-unds-nw38")
}

record(bo, "ACSW:UNDS:NW38:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-unds-nw38")
}

record(stringin, "ACSW:UNDS:NW38:3NAMESET") {
  field(FLNK, "ACSW:UNDS:NW38:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW38:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-unds-nw38")
  field(DOL, "ACSW:UNDS:NW38:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW38:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-unds-nw38")
  field(FLNK, "ACSW:UNDS:NW38:GETINIT")
}

record(bo, "ACSW:UNDS:NW38:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-unds-nw38")
  field(FLNK, "ACSW:UNDS:NW38:GETINIT")
}

record(stringin, "ACSW:UNDS:NW38:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW38:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW38:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW38:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW38:3INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW38:3INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW38:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW38:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW38:4POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW38:4POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW38:4POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW38:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW38:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW38:4POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW38:4POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW38:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW38:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-unds-nw38")
}

record(bo, "ACSW:UNDS:NW38:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-unds-nw38")
}

record(bo, "ACSW:UNDS:NW38:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-unds-nw38")
}

record(stringin, "ACSW:UNDS:NW38:4NAMESET") {
  field(FLNK, "ACSW:UNDS:NW38:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW38:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-unds-nw38")
  field(DOL, "ACSW:UNDS:NW38:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW38:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-unds-nw38")
  field(FLNK, "ACSW:UNDS:NW38:GETINIT")
}

record(bo, "ACSW:UNDS:NW38:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-unds-nw38")
  field(FLNK, "ACSW:UNDS:NW38:GETINIT")
}

record(stringin, "ACSW:UNDS:NW38:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW38:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW38:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW38:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW38:4INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW38:4INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW38:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW38:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW38:5POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW38:5POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW38:5POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW38:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW38:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW38:5POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW38:5POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW38:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW38:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-unds-nw38")
}

record(bo, "ACSW:UNDS:NW38:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-unds-nw38")
}

record(bo, "ACSW:UNDS:NW38:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-unds-nw38")
}

record(stringin, "ACSW:UNDS:NW38:5NAMESET") {
  field(FLNK, "ACSW:UNDS:NW38:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW38:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-unds-nw38")
  field(DOL, "ACSW:UNDS:NW38:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW38:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-unds-nw38")
  field(FLNK, "ACSW:UNDS:NW38:GETINIT")
}

record(bo, "ACSW:UNDS:NW38:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-unds-nw38")
  field(FLNK, "ACSW:UNDS:NW38:GETINIT")
}

record(stringin, "ACSW:UNDS:NW38:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW38:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW38:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW38:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW38:5INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW38:5INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW38:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW38:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW38:6POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW38:6POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW38:6POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW38:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW38:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW38:6POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW38:6POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW38:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW38:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-unds-nw38")
}

record(bo, "ACSW:UNDS:NW38:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-unds-nw38")
}

record(bo, "ACSW:UNDS:NW38:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-unds-nw38")
}

record(stringin, "ACSW:UNDS:NW38:6NAMESET") {
  field(FLNK, "ACSW:UNDS:NW38:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW38:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-unds-nw38")
  field(DOL, "ACSW:UNDS:NW38:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW38:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-unds-nw38")
  field(FLNK, "ACSW:UNDS:NW38:GETINIT")
}

record(bo, "ACSW:UNDS:NW38:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-unds-nw38")
  field(FLNK, "ACSW:UNDS:NW38:GETINIT")
}

record(stringin, "ACSW:UNDS:NW38:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW38:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW38:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW38:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW38:6INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW38:6INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW38:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW38:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW38:7POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW38:7POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW38:7POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW38:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW38:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW38:7POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW38:7POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW38:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW38:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-unds-nw38")
}

record(bo, "ACSW:UNDS:NW38:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-unds-nw38")
}

record(bo, "ACSW:UNDS:NW38:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-unds-nw38")
}

record(stringin, "ACSW:UNDS:NW38:7NAMESET") {
  field(FLNK, "ACSW:UNDS:NW38:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW38:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-unds-nw38")
  field(DOL, "ACSW:UNDS:NW38:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW38:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-unds-nw38")
  field(FLNK, "ACSW:UNDS:NW38:GETINIT")
}

record(bo, "ACSW:UNDS:NW38:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-unds-nw38")
  field(FLNK, "ACSW:UNDS:NW38:GETINIT")
}

record(stringin, "ACSW:UNDS:NW38:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW38:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW38:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW38:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW38:7INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW38:7INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW38:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW38:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW38:8POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW38:8POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW38:8POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW38:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW38:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW38:8POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW38:8POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW38:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW38:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-unds-nw38")
}

record(bo, "ACSW:UNDS:NW38:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-unds-nw38")
}

record(bo, "ACSW:UNDS:NW38:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-unds-nw38")
}

record(stringin, "ACSW:UNDS:NW38:8NAMESET") {
  field(FLNK, "ACSW:UNDS:NW38:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW38:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-unds-nw38")
  field(DOL, "ACSW:UNDS:NW38:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW38:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-unds-nw38")
  field(FLNK, "ACSW:UNDS:NW38:GETINIT")
}

record(bo, "ACSW:UNDS:NW38:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-unds-nw38")
  field(FLNK, "ACSW:UNDS:NW38:GETINIT")
}

record(stringin, "ACSW:UNDS:NW38:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW38:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW38:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW38:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW38:8INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW38:8INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW38:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW38:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW39:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:UNDS:NW39) acsw-unds-nw39")
  field(FLNK, "ACSW:UNDS:NW39:GETINFO")
}

record(stringin, "ACSW:UNDS:NW39:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:UNDS:NW39) acsw-unds-nw39")
  field(FLNK, "ACSW:UNDS:NW39:GETINIT")
}

record(stringin, "ACSW:UNDS:NW39:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:UNDS:NW39:NETFWVERSION")
  field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW39:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:UNDS:NW39:SITEID")
  field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW39:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:UNDS:NW39:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState8(ACSW:UNDS:NW39) acsw-unds-nw39")
}

record(stringin, "ACSW:UNDS:NW39:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState8(ACSW:UNDS:NW39) acsw-unds-nw39")
}

record(ai, "ACSW:UNDS:NW39:TYPE") {
  field(DESC, "APC 8 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "10")
}

record(stringin, "ACSW:UNDS:NW39:LOC") {
  field(PINI, "YES")
  field(VAL, "B920-39S")
  field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:UNDS:NW39:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-unds-nw39")
}

record(calcout, "ACSW:UNDS:NW39:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:UNDS:NW39:DISCONN.DISA")
  field(INPB, "ACSW:UNDS:NW39:DISCONN.DISV")
  field(INPC, "ACSW:UNDS:NW39:GETSTATUS.DISA")
  field(INPD, "ACSW:UNDS:NW39:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:UNDS:NW39:CONNSTA PP")
}

record(bi, "ACSW:UNDS:NW39:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:UNDS:NW39:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:UNDS:NW39:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:UNDS:NW39:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:UNDS:NW39:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:UNDS:NW39:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:UNDS:NW39:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:UNDS:NW39:UPTIMEHOUR") {
  field(FLNK, "ACSW:UNDS:NW39:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:UNDS:NW39:UPTIMEDAY") {
  field(FLNK, "ACSW:UNDS:NW39:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:UNDS:NW39:UPTIMEMINUTE") {
  field(FLNK, "ACSW:UNDS:NW39:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:UNDS:NW39:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW39:1POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW39:1POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW39:1POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW39:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW39:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW39:1POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW39:1POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW39:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW39:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-unds-nw39")
}

record(bo, "ACSW:UNDS:NW39:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-unds-nw39")
}

record(bo, "ACSW:UNDS:NW39:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-unds-nw39")
}

record(stringin, "ACSW:UNDS:NW39:1NAMESET") {
  field(FLNK, "ACSW:UNDS:NW39:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW39:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-unds-nw39")
  field(DOL, "ACSW:UNDS:NW39:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW39:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-unds-nw39")
  field(FLNK, "ACSW:UNDS:NW39:GETINIT")
}

record(bo, "ACSW:UNDS:NW39:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-unds-nw39")
  field(FLNK, "ACSW:UNDS:NW39:GETINIT")
}

record(stringin, "ACSW:UNDS:NW39:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW39:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW39:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW39:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW39:1INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW39:1INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW39:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW39:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW39:2POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW39:2POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW39:2POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW39:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW39:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW39:2POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW39:2POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW39:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW39:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-unds-nw39")
}

record(bo, "ACSW:UNDS:NW39:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-unds-nw39")
}

record(bo, "ACSW:UNDS:NW39:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-unds-nw39")
}

record(stringin, "ACSW:UNDS:NW39:2NAMESET") {
  field(FLNK, "ACSW:UNDS:NW39:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW39:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-unds-nw39")
  field(DOL, "ACSW:UNDS:NW39:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW39:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-unds-nw39")
  field(FLNK, "ACSW:UNDS:NW39:GETINIT")
}

record(bo, "ACSW:UNDS:NW39:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-unds-nw39")
  field(FLNK, "ACSW:UNDS:NW39:GETINIT")
}

record(stringin, "ACSW:UNDS:NW39:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW39:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW39:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW39:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW39:2INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW39:2INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW39:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW39:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW39:3POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW39:3POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW39:3POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW39:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW39:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW39:3POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW39:3POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW39:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW39:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-unds-nw39")
}

record(bo, "ACSW:UNDS:NW39:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-unds-nw39")
}

record(bo, "ACSW:UNDS:NW39:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-unds-nw39")
}

record(stringin, "ACSW:UNDS:NW39:3NAMESET") {
  field(FLNK, "ACSW:UNDS:NW39:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW39:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-unds-nw39")
  field(DOL, "ACSW:UNDS:NW39:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW39:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-unds-nw39")
  field(FLNK, "ACSW:UNDS:NW39:GETINIT")
}

record(bo, "ACSW:UNDS:NW39:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-unds-nw39")
  field(FLNK, "ACSW:UNDS:NW39:GETINIT")
}

record(stringin, "ACSW:UNDS:NW39:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW39:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW39:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW39:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW39:3INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW39:3INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW39:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW39:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW39:4POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW39:4POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW39:4POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW39:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW39:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW39:4POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW39:4POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW39:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW39:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-unds-nw39")
}

record(bo, "ACSW:UNDS:NW39:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-unds-nw39")
}

record(bo, "ACSW:UNDS:NW39:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-unds-nw39")
}

record(stringin, "ACSW:UNDS:NW39:4NAMESET") {
  field(FLNK, "ACSW:UNDS:NW39:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW39:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-unds-nw39")
  field(DOL, "ACSW:UNDS:NW39:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW39:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-unds-nw39")
  field(FLNK, "ACSW:UNDS:NW39:GETINIT")
}

record(bo, "ACSW:UNDS:NW39:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-unds-nw39")
  field(FLNK, "ACSW:UNDS:NW39:GETINIT")
}

record(stringin, "ACSW:UNDS:NW39:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW39:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW39:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW39:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW39:4INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW39:4INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW39:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW39:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW39:5POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW39:5POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW39:5POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW39:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW39:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW39:5POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW39:5POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW39:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW39:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-unds-nw39")
}

record(bo, "ACSW:UNDS:NW39:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-unds-nw39")
}

record(bo, "ACSW:UNDS:NW39:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-unds-nw39")
}

record(stringin, "ACSW:UNDS:NW39:5NAMESET") {
  field(FLNK, "ACSW:UNDS:NW39:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW39:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-unds-nw39")
  field(DOL, "ACSW:UNDS:NW39:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW39:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-unds-nw39")
  field(FLNK, "ACSW:UNDS:NW39:GETINIT")
}

record(bo, "ACSW:UNDS:NW39:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-unds-nw39")
  field(FLNK, "ACSW:UNDS:NW39:GETINIT")
}

record(stringin, "ACSW:UNDS:NW39:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW39:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW39:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW39:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW39:5INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW39:5INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW39:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW39:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW39:6POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW39:6POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW39:6POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW39:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW39:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW39:6POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW39:6POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW39:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW39:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-unds-nw39")
}

record(bo, "ACSW:UNDS:NW39:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-unds-nw39")
}

record(bo, "ACSW:UNDS:NW39:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-unds-nw39")
}

record(stringin, "ACSW:UNDS:NW39:6NAMESET") {
  field(FLNK, "ACSW:UNDS:NW39:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW39:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-unds-nw39")
  field(DOL, "ACSW:UNDS:NW39:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW39:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-unds-nw39")
  field(FLNK, "ACSW:UNDS:NW39:GETINIT")
}

record(bo, "ACSW:UNDS:NW39:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-unds-nw39")
  field(FLNK, "ACSW:UNDS:NW39:GETINIT")
}

record(stringin, "ACSW:UNDS:NW39:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW39:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW39:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW39:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW39:6INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW39:6INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW39:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW39:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW39:7POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW39:7POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW39:7POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW39:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW39:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW39:7POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW39:7POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW39:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW39:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-unds-nw39")
}

record(bo, "ACSW:UNDS:NW39:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-unds-nw39")
}

record(bo, "ACSW:UNDS:NW39:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-unds-nw39")
}

record(stringin, "ACSW:UNDS:NW39:7NAMESET") {
  field(FLNK, "ACSW:UNDS:NW39:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW39:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-unds-nw39")
  field(DOL, "ACSW:UNDS:NW39:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW39:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-unds-nw39")
  field(FLNK, "ACSW:UNDS:NW39:GETINIT")
}

record(bo, "ACSW:UNDS:NW39:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-unds-nw39")
  field(FLNK, "ACSW:UNDS:NW39:GETINIT")
}

record(stringin, "ACSW:UNDS:NW39:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW39:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW39:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW39:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW39:7INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW39:7INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW39:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW39:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW39:8POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW39:8POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW39:8POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW39:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW39:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW39:8POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW39:8POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW39:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW39:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-unds-nw39")
}

record(bo, "ACSW:UNDS:NW39:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-unds-nw39")
}

record(bo, "ACSW:UNDS:NW39:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-unds-nw39")
}

record(stringin, "ACSW:UNDS:NW39:8NAMESET") {
  field(FLNK, "ACSW:UNDS:NW39:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW39:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-unds-nw39")
  field(DOL, "ACSW:UNDS:NW39:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW39:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-unds-nw39")
  field(FLNK, "ACSW:UNDS:NW39:GETINIT")
}

record(bo, "ACSW:UNDS:NW39:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-unds-nw39")
  field(FLNK, "ACSW:UNDS:NW39:GETINIT")
}

record(stringin, "ACSW:UNDS:NW39:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW39:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW39:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW39:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW39:8INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW39:8INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW39:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW39:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW40:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:UNDS:NW40) acsw-unds-nw40")
  field(FLNK, "ACSW:UNDS:NW40:GETINFO")
}

record(stringin, "ACSW:UNDS:NW40:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:UNDS:NW40) acsw-unds-nw40")
  field(FLNK, "ACSW:UNDS:NW40:GETINIT")
}

record(stringin, "ACSW:UNDS:NW40:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:UNDS:NW40:NETFWVERSION")
  field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW40:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:UNDS:NW40:SITEID")
  field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW40:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:UNDS:NW40:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState8(ACSW:UNDS:NW40) acsw-unds-nw40")
}

record(stringin, "ACSW:UNDS:NW40:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState8(ACSW:UNDS:NW40) acsw-unds-nw40")
}

record(ai, "ACSW:UNDS:NW40:TYPE") {
  field(DESC, "APC 8 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "10")
}

record(stringin, "ACSW:UNDS:NW40:LOC") {
  field(PINI, "YES")
  field(VAL, "B920-40S")
  field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:UNDS:NW40:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-unds-nw40")
}

record(calcout, "ACSW:UNDS:NW40:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:UNDS:NW40:DISCONN.DISA")
  field(INPB, "ACSW:UNDS:NW40:DISCONN.DISV")
  field(INPC, "ACSW:UNDS:NW40:GETSTATUS.DISA")
  field(INPD, "ACSW:UNDS:NW40:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:UNDS:NW40:CONNSTA PP")
}

record(bi, "ACSW:UNDS:NW40:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:UNDS:NW40:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:UNDS:NW40:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:UNDS:NW40:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:UNDS:NW40:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:UNDS:NW40:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:UNDS:NW40:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:UNDS:NW40:UPTIMEHOUR") {
  field(FLNK, "ACSW:UNDS:NW40:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:UNDS:NW40:UPTIMEDAY") {
  field(FLNK, "ACSW:UNDS:NW40:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:UNDS:NW40:UPTIMEMINUTE") {
  field(FLNK, "ACSW:UNDS:NW40:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:UNDS:NW40:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW40:1POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW40:1POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW40:1POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW40:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW40:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW40:1POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW40:1POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW40:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW40:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-unds-nw40")
}

record(bo, "ACSW:UNDS:NW40:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-unds-nw40")
}

record(bo, "ACSW:UNDS:NW40:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-unds-nw40")
}

record(stringin, "ACSW:UNDS:NW40:1NAMESET") {
  field(FLNK, "ACSW:UNDS:NW40:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW40:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-unds-nw40")
  field(DOL, "ACSW:UNDS:NW40:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW40:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-unds-nw40")
  field(FLNK, "ACSW:UNDS:NW40:GETINIT")
}

record(bo, "ACSW:UNDS:NW40:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-unds-nw40")
  field(FLNK, "ACSW:UNDS:NW40:GETINIT")
}

record(stringin, "ACSW:UNDS:NW40:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW40:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW40:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW40:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW40:1INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW40:1INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW40:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW40:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW40:2POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW40:2POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW40:2POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW40:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW40:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW40:2POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW40:2POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW40:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW40:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-unds-nw40")
}

record(bo, "ACSW:UNDS:NW40:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-unds-nw40")
}

record(bo, "ACSW:UNDS:NW40:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-unds-nw40")
}

record(stringin, "ACSW:UNDS:NW40:2NAMESET") {
  field(FLNK, "ACSW:UNDS:NW40:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW40:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-unds-nw40")
  field(DOL, "ACSW:UNDS:NW40:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW40:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-unds-nw40")
  field(FLNK, "ACSW:UNDS:NW40:GETINIT")
}

record(bo, "ACSW:UNDS:NW40:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-unds-nw40")
  field(FLNK, "ACSW:UNDS:NW40:GETINIT")
}

record(stringin, "ACSW:UNDS:NW40:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW40:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW40:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW40:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW40:2INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW40:2INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW40:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW40:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW40:3POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW40:3POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW40:3POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW40:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW40:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW40:3POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW40:3POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW40:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW40:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-unds-nw40")
}

record(bo, "ACSW:UNDS:NW40:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-unds-nw40")
}

record(bo, "ACSW:UNDS:NW40:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-unds-nw40")
}

record(stringin, "ACSW:UNDS:NW40:3NAMESET") {
  field(FLNK, "ACSW:UNDS:NW40:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW40:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-unds-nw40")
  field(DOL, "ACSW:UNDS:NW40:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW40:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-unds-nw40")
  field(FLNK, "ACSW:UNDS:NW40:GETINIT")
}

record(bo, "ACSW:UNDS:NW40:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-unds-nw40")
  field(FLNK, "ACSW:UNDS:NW40:GETINIT")
}

record(stringin, "ACSW:UNDS:NW40:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW40:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW40:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW40:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW40:3INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW40:3INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW40:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW40:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW40:4POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW40:4POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW40:4POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW40:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW40:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW40:4POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW40:4POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW40:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW40:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-unds-nw40")
}

record(bo, "ACSW:UNDS:NW40:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-unds-nw40")
}

record(bo, "ACSW:UNDS:NW40:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-unds-nw40")
}

record(stringin, "ACSW:UNDS:NW40:4NAMESET") {
  field(FLNK, "ACSW:UNDS:NW40:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW40:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-unds-nw40")
  field(DOL, "ACSW:UNDS:NW40:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW40:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-unds-nw40")
  field(FLNK, "ACSW:UNDS:NW40:GETINIT")
}

record(bo, "ACSW:UNDS:NW40:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-unds-nw40")
  field(FLNK, "ACSW:UNDS:NW40:GETINIT")
}

record(stringin, "ACSW:UNDS:NW40:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW40:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW40:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW40:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW40:4INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW40:4INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW40:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW40:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW40:5POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW40:5POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW40:5POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW40:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW40:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW40:5POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW40:5POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW40:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW40:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-unds-nw40")
}

record(bo, "ACSW:UNDS:NW40:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-unds-nw40")
}

record(bo, "ACSW:UNDS:NW40:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-unds-nw40")
}

record(stringin, "ACSW:UNDS:NW40:5NAMESET") {
  field(FLNK, "ACSW:UNDS:NW40:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW40:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-unds-nw40")
  field(DOL, "ACSW:UNDS:NW40:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW40:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-unds-nw40")
  field(FLNK, "ACSW:UNDS:NW40:GETINIT")
}

record(bo, "ACSW:UNDS:NW40:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-unds-nw40")
  field(FLNK, "ACSW:UNDS:NW40:GETINIT")
}

record(stringin, "ACSW:UNDS:NW40:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW40:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW40:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW40:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW40:5INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW40:5INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW40:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW40:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW40:6POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW40:6POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW40:6POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW40:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW40:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW40:6POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW40:6POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW40:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW40:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-unds-nw40")
}

record(bo, "ACSW:UNDS:NW40:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-unds-nw40")
}

record(bo, "ACSW:UNDS:NW40:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-unds-nw40")
}

record(stringin, "ACSW:UNDS:NW40:6NAMESET") {
  field(FLNK, "ACSW:UNDS:NW40:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW40:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-unds-nw40")
  field(DOL, "ACSW:UNDS:NW40:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW40:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-unds-nw40")
  field(FLNK, "ACSW:UNDS:NW40:GETINIT")
}

record(bo, "ACSW:UNDS:NW40:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-unds-nw40")
  field(FLNK, "ACSW:UNDS:NW40:GETINIT")
}

record(stringin, "ACSW:UNDS:NW40:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW40:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW40:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW40:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW40:6INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW40:6INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW40:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW40:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW40:7POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW40:7POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW40:7POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW40:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW40:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW40:7POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW40:7POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW40:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW40:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-unds-nw40")
}

record(bo, "ACSW:UNDS:NW40:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-unds-nw40")
}

record(bo, "ACSW:UNDS:NW40:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-unds-nw40")
}

record(stringin, "ACSW:UNDS:NW40:7NAMESET") {
  field(FLNK, "ACSW:UNDS:NW40:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW40:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-unds-nw40")
  field(DOL, "ACSW:UNDS:NW40:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW40:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-unds-nw40")
  field(FLNK, "ACSW:UNDS:NW40:GETINIT")
}

record(bo, "ACSW:UNDS:NW40:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-unds-nw40")
  field(FLNK, "ACSW:UNDS:NW40:GETINIT")
}

record(stringin, "ACSW:UNDS:NW40:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW40:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW40:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW40:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW40:7INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW40:7INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW40:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW40:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW40:8POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW40:8POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW40:8POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW40:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW40:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW40:8POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW40:8POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW40:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW40:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-unds-nw40")
}

record(bo, "ACSW:UNDS:NW40:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-unds-nw40")
}

record(bo, "ACSW:UNDS:NW40:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-unds-nw40")
}

record(stringin, "ACSW:UNDS:NW40:8NAMESET") {
  field(FLNK, "ACSW:UNDS:NW40:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW40:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-unds-nw40")
  field(DOL, "ACSW:UNDS:NW40:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW40:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-unds-nw40")
  field(FLNK, "ACSW:UNDS:NW40:GETINIT")
}

record(bo, "ACSW:UNDS:NW40:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-unds-nw40")
  field(FLNK, "ACSW:UNDS:NW40:GETINIT")
}

record(stringin, "ACSW:UNDS:NW40:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW40:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW40:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW40:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW40:8INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW40:8INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW40:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW40:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW41:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:UNDS:NW41) acsw-unds-nw41")
  field(FLNK, "ACSW:UNDS:NW41:GETINFO")
}

record(stringin, "ACSW:UNDS:NW41:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:UNDS:NW41) acsw-unds-nw41")
  field(FLNK, "ACSW:UNDS:NW41:GETINIT")
}

record(stringin, "ACSW:UNDS:NW41:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:UNDS:NW41:NETFWVERSION")
  field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW41:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:UNDS:NW41:SITEID")
  field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW41:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:UNDS:NW41:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState8(ACSW:UNDS:NW41) acsw-unds-nw41")
}

record(stringin, "ACSW:UNDS:NW41:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState8(ACSW:UNDS:NW41) acsw-unds-nw41")
}

record(ai, "ACSW:UNDS:NW41:TYPE") {
  field(DESC, "APC 8 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "10")
}

record(stringin, "ACSW:UNDS:NW41:LOC") {
  field(PINI, "YES")
  field(VAL, "B920-41S")
  field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:UNDS:NW41:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-unds-nw41")
}

record(calcout, "ACSW:UNDS:NW41:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:UNDS:NW41:DISCONN.DISA")
  field(INPB, "ACSW:UNDS:NW41:DISCONN.DISV")
  field(INPC, "ACSW:UNDS:NW41:GETSTATUS.DISA")
  field(INPD, "ACSW:UNDS:NW41:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:UNDS:NW41:CONNSTA PP")
}

record(bi, "ACSW:UNDS:NW41:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:UNDS:NW41:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:UNDS:NW41:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:UNDS:NW41:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:UNDS:NW41:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:UNDS:NW41:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:UNDS:NW41:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:UNDS:NW41:UPTIMEHOUR") {
  field(FLNK, "ACSW:UNDS:NW41:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:UNDS:NW41:UPTIMEDAY") {
  field(FLNK, "ACSW:UNDS:NW41:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:UNDS:NW41:UPTIMEMINUTE") {
  field(FLNK, "ACSW:UNDS:NW41:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:UNDS:NW41:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW41:1POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW41:1POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW41:1POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW41:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW41:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW41:1POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW41:1POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW41:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW41:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-unds-nw41")
}

record(bo, "ACSW:UNDS:NW41:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-unds-nw41")
}

record(bo, "ACSW:UNDS:NW41:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-unds-nw41")
}

record(stringin, "ACSW:UNDS:NW41:1NAMESET") {
  field(FLNK, "ACSW:UNDS:NW41:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW41:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-unds-nw41")
  field(DOL, "ACSW:UNDS:NW41:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW41:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-unds-nw41")
  field(FLNK, "ACSW:UNDS:NW41:GETINIT")
}

record(bo, "ACSW:UNDS:NW41:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-unds-nw41")
  field(FLNK, "ACSW:UNDS:NW41:GETINIT")
}

record(stringin, "ACSW:UNDS:NW41:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW41:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW41:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW41:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW41:1INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW41:1INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW41:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW41:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW41:2POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW41:2POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW41:2POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW41:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW41:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW41:2POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW41:2POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW41:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW41:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-unds-nw41")
}

record(bo, "ACSW:UNDS:NW41:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-unds-nw41")
}

record(bo, "ACSW:UNDS:NW41:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-unds-nw41")
}

record(stringin, "ACSW:UNDS:NW41:2NAMESET") {
  field(FLNK, "ACSW:UNDS:NW41:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW41:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-unds-nw41")
  field(DOL, "ACSW:UNDS:NW41:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW41:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-unds-nw41")
  field(FLNK, "ACSW:UNDS:NW41:GETINIT")
}

record(bo, "ACSW:UNDS:NW41:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-unds-nw41")
  field(FLNK, "ACSW:UNDS:NW41:GETINIT")
}

record(stringin, "ACSW:UNDS:NW41:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW41:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW41:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW41:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW41:2INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW41:2INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW41:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW41:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW41:3POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW41:3POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW41:3POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW41:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW41:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW41:3POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW41:3POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW41:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW41:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-unds-nw41")
}

record(bo, "ACSW:UNDS:NW41:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-unds-nw41")
}

record(bo, "ACSW:UNDS:NW41:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-unds-nw41")
}

record(stringin, "ACSW:UNDS:NW41:3NAMESET") {
  field(FLNK, "ACSW:UNDS:NW41:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW41:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-unds-nw41")
  field(DOL, "ACSW:UNDS:NW41:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW41:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-unds-nw41")
  field(FLNK, "ACSW:UNDS:NW41:GETINIT")
}

record(bo, "ACSW:UNDS:NW41:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-unds-nw41")
  field(FLNK, "ACSW:UNDS:NW41:GETINIT")
}

record(stringin, "ACSW:UNDS:NW41:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW41:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW41:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW41:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW41:3INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW41:3INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW41:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW41:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW41:4POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW41:4POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW41:4POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW41:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW41:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW41:4POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW41:4POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW41:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW41:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-unds-nw41")
}

record(bo, "ACSW:UNDS:NW41:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-unds-nw41")
}

record(bo, "ACSW:UNDS:NW41:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-unds-nw41")
}

record(stringin, "ACSW:UNDS:NW41:4NAMESET") {
  field(FLNK, "ACSW:UNDS:NW41:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW41:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-unds-nw41")
  field(DOL, "ACSW:UNDS:NW41:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW41:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-unds-nw41")
  field(FLNK, "ACSW:UNDS:NW41:GETINIT")
}

record(bo, "ACSW:UNDS:NW41:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-unds-nw41")
  field(FLNK, "ACSW:UNDS:NW41:GETINIT")
}

record(stringin, "ACSW:UNDS:NW41:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW41:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW41:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW41:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW41:4INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW41:4INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW41:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW41:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW41:5POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW41:5POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW41:5POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW41:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW41:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW41:5POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW41:5POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW41:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW41:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-unds-nw41")
}

record(bo, "ACSW:UNDS:NW41:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-unds-nw41")
}

record(bo, "ACSW:UNDS:NW41:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-unds-nw41")
}

record(stringin, "ACSW:UNDS:NW41:5NAMESET") {
  field(FLNK, "ACSW:UNDS:NW41:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW41:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-unds-nw41")
  field(DOL, "ACSW:UNDS:NW41:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW41:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-unds-nw41")
  field(FLNK, "ACSW:UNDS:NW41:GETINIT")
}

record(bo, "ACSW:UNDS:NW41:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-unds-nw41")
  field(FLNK, "ACSW:UNDS:NW41:GETINIT")
}

record(stringin, "ACSW:UNDS:NW41:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW41:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW41:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW41:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW41:5INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW41:5INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW41:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW41:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW41:6POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW41:6POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW41:6POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW41:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW41:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW41:6POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW41:6POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW41:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW41:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-unds-nw41")
}

record(bo, "ACSW:UNDS:NW41:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-unds-nw41")
}

record(bo, "ACSW:UNDS:NW41:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-unds-nw41")
}

record(stringin, "ACSW:UNDS:NW41:6NAMESET") {
  field(FLNK, "ACSW:UNDS:NW41:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW41:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-unds-nw41")
  field(DOL, "ACSW:UNDS:NW41:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW41:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-unds-nw41")
  field(FLNK, "ACSW:UNDS:NW41:GETINIT")
}

record(bo, "ACSW:UNDS:NW41:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-unds-nw41")
  field(FLNK, "ACSW:UNDS:NW41:GETINIT")
}

record(stringin, "ACSW:UNDS:NW41:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW41:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW41:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW41:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW41:6INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW41:6INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW41:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW41:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW41:7POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW41:7POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW41:7POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW41:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW41:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW41:7POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW41:7POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW41:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW41:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-unds-nw41")
}

record(bo, "ACSW:UNDS:NW41:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-unds-nw41")
}

record(bo, "ACSW:UNDS:NW41:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-unds-nw41")
}

record(stringin, "ACSW:UNDS:NW41:7NAMESET") {
  field(FLNK, "ACSW:UNDS:NW41:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW41:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-unds-nw41")
  field(DOL, "ACSW:UNDS:NW41:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW41:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-unds-nw41")
  field(FLNK, "ACSW:UNDS:NW41:GETINIT")
}

record(bo, "ACSW:UNDS:NW41:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-unds-nw41")
  field(FLNK, "ACSW:UNDS:NW41:GETINIT")
}

record(stringin, "ACSW:UNDS:NW41:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW41:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW41:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW41:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW41:7INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW41:7INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW41:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW41:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW41:8POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW41:8POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW41:8POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW41:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW41:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW41:8POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW41:8POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW41:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW41:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-unds-nw41")
}

record(bo, "ACSW:UNDS:NW41:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-unds-nw41")
}

record(bo, "ACSW:UNDS:NW41:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-unds-nw41")
}

record(stringin, "ACSW:UNDS:NW41:8NAMESET") {
  field(FLNK, "ACSW:UNDS:NW41:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW41:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-unds-nw41")
  field(DOL, "ACSW:UNDS:NW41:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW41:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-unds-nw41")
  field(FLNK, "ACSW:UNDS:NW41:GETINIT")
}

record(bo, "ACSW:UNDS:NW41:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-unds-nw41")
  field(FLNK, "ACSW:UNDS:NW41:GETINIT")
}

record(stringin, "ACSW:UNDS:NW41:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW41:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW41:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW41:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW41:8INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW41:8INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW41:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW41:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW42:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:UNDS:NW42) acsw-unds-nw42")
  field(FLNK, "ACSW:UNDS:NW42:GETINFO")
}

record(stringin, "ACSW:UNDS:NW42:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:UNDS:NW42) acsw-unds-nw42")
  field(FLNK, "ACSW:UNDS:NW42:GETINIT")
}

record(stringin, "ACSW:UNDS:NW42:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:UNDS:NW42:NETFWVERSION")
  field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW42:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:UNDS:NW42:SITEID")
  field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW42:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:UNDS:NW42:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState8(ACSW:UNDS:NW42) acsw-unds-nw42")
}

record(stringin, "ACSW:UNDS:NW42:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState8(ACSW:UNDS:NW42) acsw-unds-nw42")
}

record(ai, "ACSW:UNDS:NW42:TYPE") {
  field(DESC, "APC 8 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "10")
}

record(stringin, "ACSW:UNDS:NW42:LOC") {
  field(PINI, "YES")
  field(VAL, "B920-42S")
  field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:UNDS:NW42:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-unds-nw42")
}

record(calcout, "ACSW:UNDS:NW42:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:UNDS:NW42:DISCONN.DISA")
  field(INPB, "ACSW:UNDS:NW42:DISCONN.DISV")
  field(INPC, "ACSW:UNDS:NW42:GETSTATUS.DISA")
  field(INPD, "ACSW:UNDS:NW42:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:UNDS:NW42:CONNSTA PP")
}

record(bi, "ACSW:UNDS:NW42:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:UNDS:NW42:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:UNDS:NW42:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:UNDS:NW42:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:UNDS:NW42:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:UNDS:NW42:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:UNDS:NW42:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:UNDS:NW42:UPTIMEHOUR") {
  field(FLNK, "ACSW:UNDS:NW42:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:UNDS:NW42:UPTIMEDAY") {
  field(FLNK, "ACSW:UNDS:NW42:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:UNDS:NW42:UPTIMEMINUTE") {
  field(FLNK, "ACSW:UNDS:NW42:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:UNDS:NW42:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW42:1POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW42:1POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW42:1POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW42:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW42:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW42:1POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW42:1POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW42:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW42:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-unds-nw42")
}

record(bo, "ACSW:UNDS:NW42:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-unds-nw42")
}

record(bo, "ACSW:UNDS:NW42:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-unds-nw42")
}

record(stringin, "ACSW:UNDS:NW42:1NAMESET") {
  field(FLNK, "ACSW:UNDS:NW42:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW42:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-unds-nw42")
  field(DOL, "ACSW:UNDS:NW42:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW42:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-unds-nw42")
  field(FLNK, "ACSW:UNDS:NW42:GETINIT")
}

record(bo, "ACSW:UNDS:NW42:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-unds-nw42")
  field(FLNK, "ACSW:UNDS:NW42:GETINIT")
}

record(stringin, "ACSW:UNDS:NW42:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW42:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW42:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW42:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW42:1INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW42:1INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW42:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW42:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW42:2POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW42:2POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW42:2POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW42:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW42:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW42:2POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW42:2POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW42:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW42:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-unds-nw42")
}

record(bo, "ACSW:UNDS:NW42:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-unds-nw42")
}

record(bo, "ACSW:UNDS:NW42:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-unds-nw42")
}

record(stringin, "ACSW:UNDS:NW42:2NAMESET") {
  field(FLNK, "ACSW:UNDS:NW42:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW42:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-unds-nw42")
  field(DOL, "ACSW:UNDS:NW42:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW42:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-unds-nw42")
  field(FLNK, "ACSW:UNDS:NW42:GETINIT")
}

record(bo, "ACSW:UNDS:NW42:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-unds-nw42")
  field(FLNK, "ACSW:UNDS:NW42:GETINIT")
}

record(stringin, "ACSW:UNDS:NW42:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW42:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW42:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW42:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW42:2INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW42:2INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW42:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW42:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW42:3POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW42:3POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW42:3POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW42:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW42:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW42:3POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW42:3POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW42:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW42:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-unds-nw42")
}

record(bo, "ACSW:UNDS:NW42:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-unds-nw42")
}

record(bo, "ACSW:UNDS:NW42:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-unds-nw42")
}

record(stringin, "ACSW:UNDS:NW42:3NAMESET") {
  field(FLNK, "ACSW:UNDS:NW42:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW42:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-unds-nw42")
  field(DOL, "ACSW:UNDS:NW42:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW42:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-unds-nw42")
  field(FLNK, "ACSW:UNDS:NW42:GETINIT")
}

record(bo, "ACSW:UNDS:NW42:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-unds-nw42")
  field(FLNK, "ACSW:UNDS:NW42:GETINIT")
}

record(stringin, "ACSW:UNDS:NW42:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW42:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW42:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW42:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW42:3INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW42:3INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW42:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW42:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW42:4POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW42:4POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW42:4POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW42:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW42:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW42:4POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW42:4POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW42:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW42:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-unds-nw42")
}

record(bo, "ACSW:UNDS:NW42:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-unds-nw42")
}

record(bo, "ACSW:UNDS:NW42:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-unds-nw42")
}

record(stringin, "ACSW:UNDS:NW42:4NAMESET") {
  field(FLNK, "ACSW:UNDS:NW42:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW42:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-unds-nw42")
  field(DOL, "ACSW:UNDS:NW42:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW42:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-unds-nw42")
  field(FLNK, "ACSW:UNDS:NW42:GETINIT")
}

record(bo, "ACSW:UNDS:NW42:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-unds-nw42")
  field(FLNK, "ACSW:UNDS:NW42:GETINIT")
}

record(stringin, "ACSW:UNDS:NW42:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW42:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW42:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW42:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW42:4INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW42:4INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW42:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW42:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW42:5POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW42:5POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW42:5POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW42:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW42:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW42:5POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW42:5POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW42:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW42:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-unds-nw42")
}

record(bo, "ACSW:UNDS:NW42:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-unds-nw42")
}

record(bo, "ACSW:UNDS:NW42:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-unds-nw42")
}

record(stringin, "ACSW:UNDS:NW42:5NAMESET") {
  field(FLNK, "ACSW:UNDS:NW42:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW42:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-unds-nw42")
  field(DOL, "ACSW:UNDS:NW42:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW42:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-unds-nw42")
  field(FLNK, "ACSW:UNDS:NW42:GETINIT")
}

record(bo, "ACSW:UNDS:NW42:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-unds-nw42")
  field(FLNK, "ACSW:UNDS:NW42:GETINIT")
}

record(stringin, "ACSW:UNDS:NW42:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW42:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW42:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW42:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW42:5INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW42:5INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW42:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW42:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW42:6POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW42:6POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW42:6POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW42:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW42:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW42:6POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW42:6POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW42:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW42:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-unds-nw42")
}

record(bo, "ACSW:UNDS:NW42:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-unds-nw42")
}

record(bo, "ACSW:UNDS:NW42:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-unds-nw42")
}

record(stringin, "ACSW:UNDS:NW42:6NAMESET") {
  field(FLNK, "ACSW:UNDS:NW42:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW42:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-unds-nw42")
  field(DOL, "ACSW:UNDS:NW42:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW42:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-unds-nw42")
  field(FLNK, "ACSW:UNDS:NW42:GETINIT")
}

record(bo, "ACSW:UNDS:NW42:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-unds-nw42")
  field(FLNK, "ACSW:UNDS:NW42:GETINIT")
}

record(stringin, "ACSW:UNDS:NW42:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW42:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW42:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW42:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW42:6INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW42:6INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW42:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW42:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW42:7POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW42:7POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW42:7POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW42:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW42:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW42:7POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW42:7POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW42:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW42:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-unds-nw42")
}

record(bo, "ACSW:UNDS:NW42:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-unds-nw42")
}

record(bo, "ACSW:UNDS:NW42:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-unds-nw42")
}

record(stringin, "ACSW:UNDS:NW42:7NAMESET") {
  field(FLNK, "ACSW:UNDS:NW42:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW42:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-unds-nw42")
  field(DOL, "ACSW:UNDS:NW42:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW42:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-unds-nw42")
  field(FLNK, "ACSW:UNDS:NW42:GETINIT")
}

record(bo, "ACSW:UNDS:NW42:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-unds-nw42")
  field(FLNK, "ACSW:UNDS:NW42:GETINIT")
}

record(stringin, "ACSW:UNDS:NW42:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW42:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW42:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW42:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW42:7INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW42:7INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW42:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW42:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW42:8POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW42:8POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW42:8POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW42:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW42:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW42:8POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW42:8POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW42:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW42:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-unds-nw42")
}

record(bo, "ACSW:UNDS:NW42:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-unds-nw42")
}

record(bo, "ACSW:UNDS:NW42:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-unds-nw42")
}

record(stringin, "ACSW:UNDS:NW42:8NAMESET") {
  field(FLNK, "ACSW:UNDS:NW42:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW42:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-unds-nw42")
  field(DOL, "ACSW:UNDS:NW42:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW42:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-unds-nw42")
  field(FLNK, "ACSW:UNDS:NW42:GETINIT")
}

record(bo, "ACSW:UNDS:NW42:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-unds-nw42")
  field(FLNK, "ACSW:UNDS:NW42:GETINIT")
}

record(stringin, "ACSW:UNDS:NW42:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW42:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW42:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW42:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW42:8INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW42:8INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW42:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW42:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW43:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:UNDS:NW43) acsw-unds-nw43")
  field(FLNK, "ACSW:UNDS:NW43:GETINFO")
}

record(stringin, "ACSW:UNDS:NW43:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:UNDS:NW43) acsw-unds-nw43")
  field(FLNK, "ACSW:UNDS:NW43:GETINIT")
}

record(stringin, "ACSW:UNDS:NW43:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:UNDS:NW43:NETFWVERSION")
  field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW43:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:UNDS:NW43:SITEID")
  field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW43:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:UNDS:NW43:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState8(ACSW:UNDS:NW43) acsw-unds-nw43")
}

record(stringin, "ACSW:UNDS:NW43:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState8(ACSW:UNDS:NW43) acsw-unds-nw43")
}

record(ai, "ACSW:UNDS:NW43:TYPE") {
  field(DESC, "APC 8 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "10")
}

record(stringin, "ACSW:UNDS:NW43:LOC") {
  field(PINI, "YES")
  field(VAL, "B920-43S")
  field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:UNDS:NW43:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-unds-nw43")
}

record(calcout, "ACSW:UNDS:NW43:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:UNDS:NW43:DISCONN.DISA")
  field(INPB, "ACSW:UNDS:NW43:DISCONN.DISV")
  field(INPC, "ACSW:UNDS:NW43:GETSTATUS.DISA")
  field(INPD, "ACSW:UNDS:NW43:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:UNDS:NW43:CONNSTA PP")
}

record(bi, "ACSW:UNDS:NW43:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:UNDS:NW43:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:UNDS:NW43:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:UNDS:NW43:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:UNDS:NW43:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:UNDS:NW43:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:UNDS:NW43:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:UNDS:NW43:UPTIMEHOUR") {
  field(FLNK, "ACSW:UNDS:NW43:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:UNDS:NW43:UPTIMEDAY") {
  field(FLNK, "ACSW:UNDS:NW43:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:UNDS:NW43:UPTIMEMINUTE") {
  field(FLNK, "ACSW:UNDS:NW43:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:UNDS:NW43:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW43:1POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW43:1POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW43:1POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW43:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW43:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW43:1POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW43:1POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW43:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW43:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-unds-nw43")
}

record(bo, "ACSW:UNDS:NW43:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-unds-nw43")
}

record(bo, "ACSW:UNDS:NW43:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-unds-nw43")
}

record(stringin, "ACSW:UNDS:NW43:1NAMESET") {
  field(FLNK, "ACSW:UNDS:NW43:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW43:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-unds-nw43")
  field(DOL, "ACSW:UNDS:NW43:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW43:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-unds-nw43")
  field(FLNK, "ACSW:UNDS:NW43:GETINIT")
}

record(bo, "ACSW:UNDS:NW43:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-unds-nw43")
  field(FLNK, "ACSW:UNDS:NW43:GETINIT")
}

record(stringin, "ACSW:UNDS:NW43:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW43:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW43:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW43:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW43:1INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW43:1INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW43:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW43:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW43:2POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW43:2POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW43:2POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW43:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW43:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW43:2POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW43:2POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW43:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW43:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-unds-nw43")
}

record(bo, "ACSW:UNDS:NW43:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-unds-nw43")
}

record(bo, "ACSW:UNDS:NW43:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-unds-nw43")
}

record(stringin, "ACSW:UNDS:NW43:2NAMESET") {
  field(FLNK, "ACSW:UNDS:NW43:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW43:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-unds-nw43")
  field(DOL, "ACSW:UNDS:NW43:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW43:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-unds-nw43")
  field(FLNK, "ACSW:UNDS:NW43:GETINIT")
}

record(bo, "ACSW:UNDS:NW43:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-unds-nw43")
  field(FLNK, "ACSW:UNDS:NW43:GETINIT")
}

record(stringin, "ACSW:UNDS:NW43:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW43:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW43:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW43:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW43:2INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW43:2INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW43:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW43:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW43:3POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW43:3POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW43:3POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW43:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW43:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW43:3POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW43:3POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW43:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW43:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-unds-nw43")
}

record(bo, "ACSW:UNDS:NW43:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-unds-nw43")
}

record(bo, "ACSW:UNDS:NW43:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-unds-nw43")
}

record(stringin, "ACSW:UNDS:NW43:3NAMESET") {
  field(FLNK, "ACSW:UNDS:NW43:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW43:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-unds-nw43")
  field(DOL, "ACSW:UNDS:NW43:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW43:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-unds-nw43")
  field(FLNK, "ACSW:UNDS:NW43:GETINIT")
}

record(bo, "ACSW:UNDS:NW43:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-unds-nw43")
  field(FLNK, "ACSW:UNDS:NW43:GETINIT")
}

record(stringin, "ACSW:UNDS:NW43:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW43:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW43:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW43:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW43:3INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW43:3INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW43:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW43:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW43:4POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW43:4POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW43:4POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW43:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW43:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW43:4POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW43:4POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW43:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW43:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-unds-nw43")
}

record(bo, "ACSW:UNDS:NW43:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-unds-nw43")
}

record(bo, "ACSW:UNDS:NW43:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-unds-nw43")
}

record(stringin, "ACSW:UNDS:NW43:4NAMESET") {
  field(FLNK, "ACSW:UNDS:NW43:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW43:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-unds-nw43")
  field(DOL, "ACSW:UNDS:NW43:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW43:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-unds-nw43")
  field(FLNK, "ACSW:UNDS:NW43:GETINIT")
}

record(bo, "ACSW:UNDS:NW43:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-unds-nw43")
  field(FLNK, "ACSW:UNDS:NW43:GETINIT")
}

record(stringin, "ACSW:UNDS:NW43:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW43:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW43:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW43:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW43:4INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW43:4INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW43:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW43:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW43:5POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW43:5POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW43:5POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW43:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW43:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW43:5POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW43:5POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW43:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW43:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-unds-nw43")
}

record(bo, "ACSW:UNDS:NW43:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-unds-nw43")
}

record(bo, "ACSW:UNDS:NW43:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-unds-nw43")
}

record(stringin, "ACSW:UNDS:NW43:5NAMESET") {
  field(FLNK, "ACSW:UNDS:NW43:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW43:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-unds-nw43")
  field(DOL, "ACSW:UNDS:NW43:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW43:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-unds-nw43")
  field(FLNK, "ACSW:UNDS:NW43:GETINIT")
}

record(bo, "ACSW:UNDS:NW43:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-unds-nw43")
  field(FLNK, "ACSW:UNDS:NW43:GETINIT")
}

record(stringin, "ACSW:UNDS:NW43:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW43:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW43:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW43:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW43:5INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW43:5INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW43:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW43:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW43:6POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW43:6POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW43:6POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW43:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW43:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW43:6POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW43:6POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW43:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW43:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-unds-nw43")
}

record(bo, "ACSW:UNDS:NW43:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-unds-nw43")
}

record(bo, "ACSW:UNDS:NW43:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-unds-nw43")
}

record(stringin, "ACSW:UNDS:NW43:6NAMESET") {
  field(FLNK, "ACSW:UNDS:NW43:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW43:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-unds-nw43")
  field(DOL, "ACSW:UNDS:NW43:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW43:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-unds-nw43")
  field(FLNK, "ACSW:UNDS:NW43:GETINIT")
}

record(bo, "ACSW:UNDS:NW43:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-unds-nw43")
  field(FLNK, "ACSW:UNDS:NW43:GETINIT")
}

record(stringin, "ACSW:UNDS:NW43:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW43:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW43:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW43:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW43:6INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW43:6INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW43:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW43:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW43:7POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW43:7POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW43:7POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW43:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW43:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW43:7POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW43:7POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW43:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW43:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-unds-nw43")
}

record(bo, "ACSW:UNDS:NW43:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-unds-nw43")
}

record(bo, "ACSW:UNDS:NW43:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-unds-nw43")
}

record(stringin, "ACSW:UNDS:NW43:7NAMESET") {
  field(FLNK, "ACSW:UNDS:NW43:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW43:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-unds-nw43")
  field(DOL, "ACSW:UNDS:NW43:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW43:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-unds-nw43")
  field(FLNK, "ACSW:UNDS:NW43:GETINIT")
}

record(bo, "ACSW:UNDS:NW43:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-unds-nw43")
  field(FLNK, "ACSW:UNDS:NW43:GETINIT")
}

record(stringin, "ACSW:UNDS:NW43:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW43:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW43:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW43:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW43:7INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW43:7INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW43:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW43:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW43:8POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW43:8POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW43:8POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW43:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW43:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW43:8POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW43:8POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW43:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW43:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-unds-nw43")
}

record(bo, "ACSW:UNDS:NW43:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-unds-nw43")
}

record(bo, "ACSW:UNDS:NW43:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-unds-nw43")
}

record(stringin, "ACSW:UNDS:NW43:8NAMESET") {
  field(FLNK, "ACSW:UNDS:NW43:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW43:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-unds-nw43")
  field(DOL, "ACSW:UNDS:NW43:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW43:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-unds-nw43")
  field(FLNK, "ACSW:UNDS:NW43:GETINIT")
}

record(bo, "ACSW:UNDS:NW43:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-unds-nw43")
  field(FLNK, "ACSW:UNDS:NW43:GETINIT")
}

record(stringin, "ACSW:UNDS:NW43:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW43:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW43:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW43:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW43:8INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW43:8INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW43:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW43:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW44:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:UNDS:NW44) acsw-unds-nw44")
  field(FLNK, "ACSW:UNDS:NW44:GETINFO")
}

record(stringin, "ACSW:UNDS:NW44:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:UNDS:NW44) acsw-unds-nw44")
  field(FLNK, "ACSW:UNDS:NW44:GETINIT")
}

record(stringin, "ACSW:UNDS:NW44:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:UNDS:NW44:NETFWVERSION")
  field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW44:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:UNDS:NW44:SITEID")
  field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW44:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:UNDS:NW44:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState8(ACSW:UNDS:NW44) acsw-unds-nw44")
}

record(stringin, "ACSW:UNDS:NW44:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState8(ACSW:UNDS:NW44) acsw-unds-nw44")
}

record(ai, "ACSW:UNDS:NW44:TYPE") {
  field(DESC, "APC 8 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "10")
}

record(stringin, "ACSW:UNDS:NW44:LOC") {
  field(PINI, "YES")
  field(VAL, "B920-44S")
  field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:UNDS:NW44:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-unds-nw44")
}

record(calcout, "ACSW:UNDS:NW44:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:UNDS:NW44:DISCONN.DISA")
  field(INPB, "ACSW:UNDS:NW44:DISCONN.DISV")
  field(INPC, "ACSW:UNDS:NW44:GETSTATUS.DISA")
  field(INPD, "ACSW:UNDS:NW44:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:UNDS:NW44:CONNSTA PP")
}

record(bi, "ACSW:UNDS:NW44:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:UNDS:NW44:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:UNDS:NW44:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:UNDS:NW44:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:UNDS:NW44:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:UNDS:NW44:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:UNDS:NW44:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:UNDS:NW44:UPTIMEHOUR") {
  field(FLNK, "ACSW:UNDS:NW44:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:UNDS:NW44:UPTIMEDAY") {
  field(FLNK, "ACSW:UNDS:NW44:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:UNDS:NW44:UPTIMEMINUTE") {
  field(FLNK, "ACSW:UNDS:NW44:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:UNDS:NW44:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW44:1POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW44:1POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW44:1POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW44:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW44:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW44:1POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW44:1POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW44:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW44:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-unds-nw44")
}

record(bo, "ACSW:UNDS:NW44:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-unds-nw44")
}

record(bo, "ACSW:UNDS:NW44:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-unds-nw44")
}

record(stringin, "ACSW:UNDS:NW44:1NAMESET") {
  field(FLNK, "ACSW:UNDS:NW44:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW44:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-unds-nw44")
  field(DOL, "ACSW:UNDS:NW44:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW44:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-unds-nw44")
  field(FLNK, "ACSW:UNDS:NW44:GETINIT")
}

record(bo, "ACSW:UNDS:NW44:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-unds-nw44")
  field(FLNK, "ACSW:UNDS:NW44:GETINIT")
}

record(stringin, "ACSW:UNDS:NW44:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW44:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW44:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW44:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW44:1INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW44:1INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW44:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW44:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW44:2POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW44:2POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW44:2POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW44:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW44:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW44:2POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW44:2POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW44:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW44:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-unds-nw44")
}

record(bo, "ACSW:UNDS:NW44:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-unds-nw44")
}

record(bo, "ACSW:UNDS:NW44:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-unds-nw44")
}

record(stringin, "ACSW:UNDS:NW44:2NAMESET") {
  field(FLNK, "ACSW:UNDS:NW44:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW44:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-unds-nw44")
  field(DOL, "ACSW:UNDS:NW44:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW44:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-unds-nw44")
  field(FLNK, "ACSW:UNDS:NW44:GETINIT")
}

record(bo, "ACSW:UNDS:NW44:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-unds-nw44")
  field(FLNK, "ACSW:UNDS:NW44:GETINIT")
}

record(stringin, "ACSW:UNDS:NW44:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW44:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW44:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW44:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW44:2INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW44:2INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW44:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW44:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW44:3POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW44:3POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW44:3POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW44:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW44:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW44:3POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW44:3POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW44:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW44:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-unds-nw44")
}

record(bo, "ACSW:UNDS:NW44:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-unds-nw44")
}

record(bo, "ACSW:UNDS:NW44:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-unds-nw44")
}

record(stringin, "ACSW:UNDS:NW44:3NAMESET") {
  field(FLNK, "ACSW:UNDS:NW44:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW44:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-unds-nw44")
  field(DOL, "ACSW:UNDS:NW44:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW44:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-unds-nw44")
  field(FLNK, "ACSW:UNDS:NW44:GETINIT")
}

record(bo, "ACSW:UNDS:NW44:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-unds-nw44")
  field(FLNK, "ACSW:UNDS:NW44:GETINIT")
}

record(stringin, "ACSW:UNDS:NW44:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW44:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW44:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW44:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW44:3INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW44:3INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW44:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW44:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW44:4POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW44:4POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW44:4POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW44:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW44:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW44:4POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW44:4POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW44:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW44:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-unds-nw44")
}

record(bo, "ACSW:UNDS:NW44:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-unds-nw44")
}

record(bo, "ACSW:UNDS:NW44:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-unds-nw44")
}

record(stringin, "ACSW:UNDS:NW44:4NAMESET") {
  field(FLNK, "ACSW:UNDS:NW44:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW44:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-unds-nw44")
  field(DOL, "ACSW:UNDS:NW44:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW44:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-unds-nw44")
  field(FLNK, "ACSW:UNDS:NW44:GETINIT")
}

record(bo, "ACSW:UNDS:NW44:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-unds-nw44")
  field(FLNK, "ACSW:UNDS:NW44:GETINIT")
}

record(stringin, "ACSW:UNDS:NW44:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW44:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW44:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW44:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW44:4INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW44:4INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW44:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW44:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW44:5POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW44:5POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW44:5POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW44:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW44:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW44:5POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW44:5POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW44:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW44:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-unds-nw44")
}

record(bo, "ACSW:UNDS:NW44:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-unds-nw44")
}

record(bo, "ACSW:UNDS:NW44:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-unds-nw44")
}

record(stringin, "ACSW:UNDS:NW44:5NAMESET") {
  field(FLNK, "ACSW:UNDS:NW44:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW44:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-unds-nw44")
  field(DOL, "ACSW:UNDS:NW44:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW44:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-unds-nw44")
  field(FLNK, "ACSW:UNDS:NW44:GETINIT")
}

record(bo, "ACSW:UNDS:NW44:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-unds-nw44")
  field(FLNK, "ACSW:UNDS:NW44:GETINIT")
}

record(stringin, "ACSW:UNDS:NW44:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW44:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW44:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW44:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW44:5INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW44:5INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW44:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW44:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW44:6POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW44:6POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW44:6POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW44:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW44:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW44:6POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW44:6POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW44:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW44:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-unds-nw44")
}

record(bo, "ACSW:UNDS:NW44:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-unds-nw44")
}

record(bo, "ACSW:UNDS:NW44:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-unds-nw44")
}

record(stringin, "ACSW:UNDS:NW44:6NAMESET") {
  field(FLNK, "ACSW:UNDS:NW44:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW44:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-unds-nw44")
  field(DOL, "ACSW:UNDS:NW44:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW44:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-unds-nw44")
  field(FLNK, "ACSW:UNDS:NW44:GETINIT")
}

record(bo, "ACSW:UNDS:NW44:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-unds-nw44")
  field(FLNK, "ACSW:UNDS:NW44:GETINIT")
}

record(stringin, "ACSW:UNDS:NW44:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW44:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW44:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW44:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW44:6INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW44:6INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW44:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW44:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW44:7POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW44:7POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW44:7POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW44:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW44:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW44:7POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW44:7POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW44:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW44:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-unds-nw44")
}

record(bo, "ACSW:UNDS:NW44:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-unds-nw44")
}

record(bo, "ACSW:UNDS:NW44:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-unds-nw44")
}

record(stringin, "ACSW:UNDS:NW44:7NAMESET") {
  field(FLNK, "ACSW:UNDS:NW44:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW44:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-unds-nw44")
  field(DOL, "ACSW:UNDS:NW44:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW44:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-unds-nw44")
  field(FLNK, "ACSW:UNDS:NW44:GETINIT")
}

record(bo, "ACSW:UNDS:NW44:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-unds-nw44")
  field(FLNK, "ACSW:UNDS:NW44:GETINIT")
}

record(stringin, "ACSW:UNDS:NW44:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW44:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW44:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW44:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW44:7INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW44:7INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW44:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW44:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW44:8POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW44:8POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW44:8POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW44:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW44:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW44:8POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW44:8POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW44:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW44:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-unds-nw44")
}

record(bo, "ACSW:UNDS:NW44:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-unds-nw44")
}

record(bo, "ACSW:UNDS:NW44:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-unds-nw44")
}

record(stringin, "ACSW:UNDS:NW44:8NAMESET") {
  field(FLNK, "ACSW:UNDS:NW44:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW44:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-unds-nw44")
  field(DOL, "ACSW:UNDS:NW44:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW44:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-unds-nw44")
  field(FLNK, "ACSW:UNDS:NW44:GETINIT")
}

record(bo, "ACSW:UNDS:NW44:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-unds-nw44")
  field(FLNK, "ACSW:UNDS:NW44:GETINIT")
}

record(stringin, "ACSW:UNDS:NW44:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW44:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW44:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW44:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW44:8INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW44:8INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW44:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW44:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW45:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:UNDS:NW45) acsw-unds-nw45")
  field(FLNK, "ACSW:UNDS:NW45:GETINFO")
}

record(stringin, "ACSW:UNDS:NW45:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:UNDS:NW45) acsw-unds-nw45")
  field(FLNK, "ACSW:UNDS:NW45:GETINIT")
}

record(stringin, "ACSW:UNDS:NW45:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:UNDS:NW45:NETFWVERSION")
  field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW45:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:UNDS:NW45:SITEID")
  field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW45:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:UNDS:NW45:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState8(ACSW:UNDS:NW45) acsw-unds-nw45")
}

record(stringin, "ACSW:UNDS:NW45:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState8(ACSW:UNDS:NW45) acsw-unds-nw45")
}

record(ai, "ACSW:UNDS:NW45:TYPE") {
  field(DESC, "APC 8 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "10")
}

record(stringin, "ACSW:UNDS:NW45:LOC") {
  field(PINI, "YES")
  field(VAL, "B920-45S")
  field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:UNDS:NW45:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-unds-nw45")
}

record(calcout, "ACSW:UNDS:NW45:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:UNDS:NW45:DISCONN.DISA")
  field(INPB, "ACSW:UNDS:NW45:DISCONN.DISV")
  field(INPC, "ACSW:UNDS:NW45:GETSTATUS.DISA")
  field(INPD, "ACSW:UNDS:NW45:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:UNDS:NW45:CONNSTA PP")
}

record(bi, "ACSW:UNDS:NW45:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:UNDS:NW45:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:UNDS:NW45:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:UNDS:NW45:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:UNDS:NW45:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:UNDS:NW45:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:UNDS:NW45:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:UNDS:NW45:UPTIMEHOUR") {
  field(FLNK, "ACSW:UNDS:NW45:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:UNDS:NW45:UPTIMEDAY") {
  field(FLNK, "ACSW:UNDS:NW45:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:UNDS:NW45:UPTIMEMINUTE") {
  field(FLNK, "ACSW:UNDS:NW45:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:UNDS:NW45:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW45:1POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW45:1POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW45:1POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW45:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW45:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW45:1POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW45:1POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW45:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW45:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-unds-nw45")
}

record(bo, "ACSW:UNDS:NW45:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-unds-nw45")
}

record(bo, "ACSW:UNDS:NW45:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-unds-nw45")
}

record(stringin, "ACSW:UNDS:NW45:1NAMESET") {
  field(FLNK, "ACSW:UNDS:NW45:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW45:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-unds-nw45")
  field(DOL, "ACSW:UNDS:NW45:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW45:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-unds-nw45")
  field(FLNK, "ACSW:UNDS:NW45:GETINIT")
}

record(bo, "ACSW:UNDS:NW45:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-unds-nw45")
  field(FLNK, "ACSW:UNDS:NW45:GETINIT")
}

record(stringin, "ACSW:UNDS:NW45:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW45:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW45:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW45:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW45:1INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW45:1INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW45:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW45:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW45:2POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW45:2POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW45:2POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW45:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW45:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW45:2POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW45:2POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW45:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW45:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-unds-nw45")
}

record(bo, "ACSW:UNDS:NW45:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-unds-nw45")
}

record(bo, "ACSW:UNDS:NW45:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-unds-nw45")
}

record(stringin, "ACSW:UNDS:NW45:2NAMESET") {
  field(FLNK, "ACSW:UNDS:NW45:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW45:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-unds-nw45")
  field(DOL, "ACSW:UNDS:NW45:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW45:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-unds-nw45")
  field(FLNK, "ACSW:UNDS:NW45:GETINIT")
}

record(bo, "ACSW:UNDS:NW45:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-unds-nw45")
  field(FLNK, "ACSW:UNDS:NW45:GETINIT")
}

record(stringin, "ACSW:UNDS:NW45:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW45:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW45:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW45:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW45:2INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW45:2INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW45:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW45:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW45:3POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW45:3POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW45:3POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW45:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW45:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW45:3POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW45:3POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW45:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW45:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-unds-nw45")
}

record(bo, "ACSW:UNDS:NW45:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-unds-nw45")
}

record(bo, "ACSW:UNDS:NW45:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-unds-nw45")
}

record(stringin, "ACSW:UNDS:NW45:3NAMESET") {
  field(FLNK, "ACSW:UNDS:NW45:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW45:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-unds-nw45")
  field(DOL, "ACSW:UNDS:NW45:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW45:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-unds-nw45")
  field(FLNK, "ACSW:UNDS:NW45:GETINIT")
}

record(bo, "ACSW:UNDS:NW45:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-unds-nw45")
  field(FLNK, "ACSW:UNDS:NW45:GETINIT")
}

record(stringin, "ACSW:UNDS:NW45:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW45:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW45:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW45:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW45:3INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW45:3INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW45:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW45:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW45:4POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW45:4POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW45:4POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW45:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW45:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW45:4POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW45:4POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW45:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW45:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-unds-nw45")
}

record(bo, "ACSW:UNDS:NW45:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-unds-nw45")
}

record(bo, "ACSW:UNDS:NW45:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-unds-nw45")
}

record(stringin, "ACSW:UNDS:NW45:4NAMESET") {
  field(FLNK, "ACSW:UNDS:NW45:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW45:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-unds-nw45")
  field(DOL, "ACSW:UNDS:NW45:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW45:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-unds-nw45")
  field(FLNK, "ACSW:UNDS:NW45:GETINIT")
}

record(bo, "ACSW:UNDS:NW45:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-unds-nw45")
  field(FLNK, "ACSW:UNDS:NW45:GETINIT")
}

record(stringin, "ACSW:UNDS:NW45:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW45:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW45:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW45:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW45:4INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW45:4INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW45:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW45:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW45:5POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW45:5POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW45:5POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW45:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW45:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW45:5POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW45:5POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW45:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW45:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-unds-nw45")
}

record(bo, "ACSW:UNDS:NW45:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-unds-nw45")
}

record(bo, "ACSW:UNDS:NW45:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-unds-nw45")
}

record(stringin, "ACSW:UNDS:NW45:5NAMESET") {
  field(FLNK, "ACSW:UNDS:NW45:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW45:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-unds-nw45")
  field(DOL, "ACSW:UNDS:NW45:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW45:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-unds-nw45")
  field(FLNK, "ACSW:UNDS:NW45:GETINIT")
}

record(bo, "ACSW:UNDS:NW45:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-unds-nw45")
  field(FLNK, "ACSW:UNDS:NW45:GETINIT")
}

record(stringin, "ACSW:UNDS:NW45:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW45:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW45:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW45:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW45:5INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW45:5INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW45:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW45:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW45:6POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW45:6POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW45:6POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW45:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW45:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW45:6POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW45:6POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW45:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW45:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-unds-nw45")
}

record(bo, "ACSW:UNDS:NW45:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-unds-nw45")
}

record(bo, "ACSW:UNDS:NW45:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-unds-nw45")
}

record(stringin, "ACSW:UNDS:NW45:6NAMESET") {
  field(FLNK, "ACSW:UNDS:NW45:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW45:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-unds-nw45")
  field(DOL, "ACSW:UNDS:NW45:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW45:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-unds-nw45")
  field(FLNK, "ACSW:UNDS:NW45:GETINIT")
}

record(bo, "ACSW:UNDS:NW45:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-unds-nw45")
  field(FLNK, "ACSW:UNDS:NW45:GETINIT")
}

record(stringin, "ACSW:UNDS:NW45:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW45:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW45:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW45:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW45:6INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW45:6INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW45:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW45:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW45:7POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW45:7POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW45:7POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW45:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW45:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW45:7POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW45:7POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW45:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW45:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-unds-nw45")
}

record(bo, "ACSW:UNDS:NW45:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-unds-nw45")
}

record(bo, "ACSW:UNDS:NW45:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-unds-nw45")
}

record(stringin, "ACSW:UNDS:NW45:7NAMESET") {
  field(FLNK, "ACSW:UNDS:NW45:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW45:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-unds-nw45")
  field(DOL, "ACSW:UNDS:NW45:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW45:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-unds-nw45")
  field(FLNK, "ACSW:UNDS:NW45:GETINIT")
}

record(bo, "ACSW:UNDS:NW45:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-unds-nw45")
  field(FLNK, "ACSW:UNDS:NW45:GETINIT")
}

record(stringin, "ACSW:UNDS:NW45:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW45:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW45:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW45:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW45:7INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW45:7INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW45:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW45:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW45:8POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW45:8POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW45:8POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW45:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW45:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW45:8POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW45:8POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW45:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW45:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-unds-nw45")
}

record(bo, "ACSW:UNDS:NW45:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-unds-nw45")
}

record(bo, "ACSW:UNDS:NW45:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-unds-nw45")
}

record(stringin, "ACSW:UNDS:NW45:8NAMESET") {
  field(FLNK, "ACSW:UNDS:NW45:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW45:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-unds-nw45")
  field(DOL, "ACSW:UNDS:NW45:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW45:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-unds-nw45")
  field(FLNK, "ACSW:UNDS:NW45:GETINIT")
}

record(bo, "ACSW:UNDS:NW45:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-unds-nw45")
  field(FLNK, "ACSW:UNDS:NW45:GETINIT")
}

record(stringin, "ACSW:UNDS:NW45:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW45:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW45:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW45:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW45:8INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW45:8INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW45:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW45:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW46:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:UNDS:NW46) acsw-unds-nw46")
  field(FLNK, "ACSW:UNDS:NW46:GETINFO")
}

record(stringin, "ACSW:UNDS:NW46:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:UNDS:NW46) acsw-unds-nw46")
  field(FLNK, "ACSW:UNDS:NW46:GETINIT")
}

record(stringin, "ACSW:UNDS:NW46:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:UNDS:NW46:NETFWVERSION")
  field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW46:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:UNDS:NW46:SITEID")
  field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW46:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:UNDS:NW46:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState8(ACSW:UNDS:NW46) acsw-unds-nw46")
}

record(stringin, "ACSW:UNDS:NW46:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState8(ACSW:UNDS:NW46) acsw-unds-nw46")
}

record(ai, "ACSW:UNDS:NW46:TYPE") {
  field(DESC, "APC 8 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "10")
}

record(stringin, "ACSW:UNDS:NW46:LOC") {
  field(PINI, "YES")
  field(VAL, "B920-46S")
  field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:UNDS:NW46:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-unds-nw46")
}

record(calcout, "ACSW:UNDS:NW46:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:UNDS:NW46:DISCONN.DISA")
  field(INPB, "ACSW:UNDS:NW46:DISCONN.DISV")
  field(INPC, "ACSW:UNDS:NW46:GETSTATUS.DISA")
  field(INPD, "ACSW:UNDS:NW46:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:UNDS:NW46:CONNSTA PP")
}

record(bi, "ACSW:UNDS:NW46:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:UNDS:NW46:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:UNDS:NW46:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:UNDS:NW46:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:UNDS:NW46:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:UNDS:NW46:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:UNDS:NW46:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:UNDS:NW46:UPTIMEHOUR") {
  field(FLNK, "ACSW:UNDS:NW46:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:UNDS:NW46:UPTIMEDAY") {
  field(FLNK, "ACSW:UNDS:NW46:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:UNDS:NW46:UPTIMEMINUTE") {
  field(FLNK, "ACSW:UNDS:NW46:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:UNDS:NW46:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW46:1POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW46:1POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW46:1POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW46:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW46:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW46:1POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW46:1POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW46:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW46:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-unds-nw46")
}

record(bo, "ACSW:UNDS:NW46:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-unds-nw46")
}

record(bo, "ACSW:UNDS:NW46:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-unds-nw46")
}

record(stringin, "ACSW:UNDS:NW46:1NAMESET") {
  field(FLNK, "ACSW:UNDS:NW46:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW46:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-unds-nw46")
  field(DOL, "ACSW:UNDS:NW46:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW46:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-unds-nw46")
  field(FLNK, "ACSW:UNDS:NW46:GETINIT")
}

record(bo, "ACSW:UNDS:NW46:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-unds-nw46")
  field(FLNK, "ACSW:UNDS:NW46:GETINIT")
}

record(stringin, "ACSW:UNDS:NW46:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW46:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW46:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW46:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW46:1INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW46:1INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW46:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW46:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW46:2POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW46:2POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW46:2POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW46:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW46:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW46:2POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW46:2POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW46:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW46:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-unds-nw46")
}

record(bo, "ACSW:UNDS:NW46:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-unds-nw46")
}

record(bo, "ACSW:UNDS:NW46:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-unds-nw46")
}

record(stringin, "ACSW:UNDS:NW46:2NAMESET") {
  field(FLNK, "ACSW:UNDS:NW46:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW46:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-unds-nw46")
  field(DOL, "ACSW:UNDS:NW46:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW46:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-unds-nw46")
  field(FLNK, "ACSW:UNDS:NW46:GETINIT")
}

record(bo, "ACSW:UNDS:NW46:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-unds-nw46")
  field(FLNK, "ACSW:UNDS:NW46:GETINIT")
}

record(stringin, "ACSW:UNDS:NW46:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW46:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW46:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW46:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW46:2INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW46:2INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW46:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW46:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW46:3POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW46:3POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW46:3POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW46:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW46:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW46:3POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW46:3POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW46:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW46:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-unds-nw46")
}

record(bo, "ACSW:UNDS:NW46:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-unds-nw46")
}

record(bo, "ACSW:UNDS:NW46:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-unds-nw46")
}

record(stringin, "ACSW:UNDS:NW46:3NAMESET") {
  field(FLNK, "ACSW:UNDS:NW46:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW46:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-unds-nw46")
  field(DOL, "ACSW:UNDS:NW46:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW46:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-unds-nw46")
  field(FLNK, "ACSW:UNDS:NW46:GETINIT")
}

record(bo, "ACSW:UNDS:NW46:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-unds-nw46")
  field(FLNK, "ACSW:UNDS:NW46:GETINIT")
}

record(stringin, "ACSW:UNDS:NW46:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW46:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW46:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW46:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW46:3INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW46:3INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW46:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW46:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW46:4POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW46:4POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW46:4POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW46:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW46:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW46:4POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW46:4POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW46:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW46:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-unds-nw46")
}

record(bo, "ACSW:UNDS:NW46:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-unds-nw46")
}

record(bo, "ACSW:UNDS:NW46:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-unds-nw46")
}

record(stringin, "ACSW:UNDS:NW46:4NAMESET") {
  field(FLNK, "ACSW:UNDS:NW46:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW46:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-unds-nw46")
  field(DOL, "ACSW:UNDS:NW46:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW46:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-unds-nw46")
  field(FLNK, "ACSW:UNDS:NW46:GETINIT")
}

record(bo, "ACSW:UNDS:NW46:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-unds-nw46")
  field(FLNK, "ACSW:UNDS:NW46:GETINIT")
}

record(stringin, "ACSW:UNDS:NW46:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW46:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW46:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW46:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW46:4INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW46:4INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW46:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW46:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW46:5POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW46:5POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW46:5POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW46:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW46:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW46:5POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW46:5POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW46:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW46:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-unds-nw46")
}

record(bo, "ACSW:UNDS:NW46:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-unds-nw46")
}

record(bo, "ACSW:UNDS:NW46:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-unds-nw46")
}

record(stringin, "ACSW:UNDS:NW46:5NAMESET") {
  field(FLNK, "ACSW:UNDS:NW46:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW46:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-unds-nw46")
  field(DOL, "ACSW:UNDS:NW46:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW46:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-unds-nw46")
  field(FLNK, "ACSW:UNDS:NW46:GETINIT")
}

record(bo, "ACSW:UNDS:NW46:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-unds-nw46")
  field(FLNK, "ACSW:UNDS:NW46:GETINIT")
}

record(stringin, "ACSW:UNDS:NW46:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW46:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW46:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW46:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW46:5INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW46:5INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW46:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW46:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW46:6POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW46:6POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW46:6POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW46:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW46:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW46:6POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW46:6POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW46:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW46:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-unds-nw46")
}

record(bo, "ACSW:UNDS:NW46:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-unds-nw46")
}

record(bo, "ACSW:UNDS:NW46:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-unds-nw46")
}

record(stringin, "ACSW:UNDS:NW46:6NAMESET") {
  field(FLNK, "ACSW:UNDS:NW46:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW46:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-unds-nw46")
  field(DOL, "ACSW:UNDS:NW46:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW46:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-unds-nw46")
  field(FLNK, "ACSW:UNDS:NW46:GETINIT")
}

record(bo, "ACSW:UNDS:NW46:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-unds-nw46")
  field(FLNK, "ACSW:UNDS:NW46:GETINIT")
}

record(stringin, "ACSW:UNDS:NW46:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW46:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW46:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW46:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW46:6INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW46:6INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW46:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW46:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW46:7POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW46:7POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW46:7POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW46:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW46:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW46:7POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW46:7POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW46:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW46:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-unds-nw46")
}

record(bo, "ACSW:UNDS:NW46:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-unds-nw46")
}

record(bo, "ACSW:UNDS:NW46:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-unds-nw46")
}

record(stringin, "ACSW:UNDS:NW46:7NAMESET") {
  field(FLNK, "ACSW:UNDS:NW46:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW46:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-unds-nw46")
  field(DOL, "ACSW:UNDS:NW46:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW46:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-unds-nw46")
  field(FLNK, "ACSW:UNDS:NW46:GETINIT")
}

record(bo, "ACSW:UNDS:NW46:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-unds-nw46")
  field(FLNK, "ACSW:UNDS:NW46:GETINIT")
}

record(stringin, "ACSW:UNDS:NW46:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW46:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW46:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW46:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW46:7INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW46:7INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW46:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW46:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW46:8POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW46:8POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW46:8POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW46:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW46:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW46:8POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW46:8POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW46:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW46:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-unds-nw46")
}

record(bo, "ACSW:UNDS:NW46:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-unds-nw46")
}

record(bo, "ACSW:UNDS:NW46:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-unds-nw46")
}

record(stringin, "ACSW:UNDS:NW46:8NAMESET") {
  field(FLNK, "ACSW:UNDS:NW46:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW46:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-unds-nw46")
  field(DOL, "ACSW:UNDS:NW46:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW46:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-unds-nw46")
  field(FLNK, "ACSW:UNDS:NW46:GETINIT")
}

record(bo, "ACSW:UNDS:NW46:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-unds-nw46")
  field(FLNK, "ACSW:UNDS:NW46:GETINIT")
}

record(stringin, "ACSW:UNDS:NW46:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW46:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW46:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW46:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW46:8INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW46:8INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW46:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW46:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW47:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:UNDS:NW47) acsw-unds-nw47")
  field(FLNK, "ACSW:UNDS:NW47:GETINFO")
}

record(stringin, "ACSW:UNDS:NW47:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:UNDS:NW47) acsw-unds-nw47")
  field(FLNK, "ACSW:UNDS:NW47:GETINIT")
}

record(stringin, "ACSW:UNDS:NW47:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:UNDS:NW47:NETFWVERSION")
  field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW47:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:UNDS:NW47:SITEID")
  field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW47:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:UNDS:NW47:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState8(ACSW:UNDS:NW47) acsw-unds-nw47")
}

record(stringin, "ACSW:UNDS:NW47:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState8(ACSW:UNDS:NW47) acsw-unds-nw47")
}

record(ai, "ACSW:UNDS:NW47:TYPE") {
  field(DESC, "APC 8 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "10")
}

record(stringin, "ACSW:UNDS:NW47:LOC") {
  field(PINI, "YES")
  field(VAL, "B920-47S")
  field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:UNDS:NW47:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-unds-nw47")
}

record(calcout, "ACSW:UNDS:NW47:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:UNDS:NW47:DISCONN.DISA")
  field(INPB, "ACSW:UNDS:NW47:DISCONN.DISV")
  field(INPC, "ACSW:UNDS:NW47:GETSTATUS.DISA")
  field(INPD, "ACSW:UNDS:NW47:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:UNDS:NW47:CONNSTA PP")
}

record(bi, "ACSW:UNDS:NW47:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:UNDS:NW47:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:UNDS:NW47:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:UNDS:NW47:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:UNDS:NW47:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:UNDS:NW47:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:UNDS:NW47:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:UNDS:NW47:UPTIMEHOUR") {
  field(FLNK, "ACSW:UNDS:NW47:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:UNDS:NW47:UPTIMEDAY") {
  field(FLNK, "ACSW:UNDS:NW47:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:UNDS:NW47:UPTIMEMINUTE") {
  field(FLNK, "ACSW:UNDS:NW47:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:UNDS:NW47:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW47:1POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW47:1POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW47:1POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW47:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW47:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW47:1POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW47:1POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW47:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW47:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-unds-nw47")
}

record(bo, "ACSW:UNDS:NW47:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-unds-nw47")
}

record(bo, "ACSW:UNDS:NW47:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-unds-nw47")
}

record(stringin, "ACSW:UNDS:NW47:1NAMESET") {
  field(FLNK, "ACSW:UNDS:NW47:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW47:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-unds-nw47")
  field(DOL, "ACSW:UNDS:NW47:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW47:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-unds-nw47")
  field(FLNK, "ACSW:UNDS:NW47:GETINIT")
}

record(bo, "ACSW:UNDS:NW47:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-unds-nw47")
  field(FLNK, "ACSW:UNDS:NW47:GETINIT")
}

record(stringin, "ACSW:UNDS:NW47:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW47:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW47:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW47:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW47:1INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW47:1INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW47:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW47:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW47:2POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW47:2POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW47:2POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW47:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW47:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW47:2POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW47:2POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW47:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW47:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-unds-nw47")
}

record(bo, "ACSW:UNDS:NW47:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-unds-nw47")
}

record(bo, "ACSW:UNDS:NW47:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-unds-nw47")
}

record(stringin, "ACSW:UNDS:NW47:2NAMESET") {
  field(FLNK, "ACSW:UNDS:NW47:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW47:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-unds-nw47")
  field(DOL, "ACSW:UNDS:NW47:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW47:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-unds-nw47")
  field(FLNK, "ACSW:UNDS:NW47:GETINIT")
}

record(bo, "ACSW:UNDS:NW47:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-unds-nw47")
  field(FLNK, "ACSW:UNDS:NW47:GETINIT")
}

record(stringin, "ACSW:UNDS:NW47:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW47:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW47:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW47:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW47:2INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW47:2INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW47:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW47:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW47:3POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW47:3POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW47:3POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW47:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW47:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW47:3POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW47:3POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW47:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW47:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-unds-nw47")
}

record(bo, "ACSW:UNDS:NW47:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-unds-nw47")
}

record(bo, "ACSW:UNDS:NW47:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-unds-nw47")
}

record(stringin, "ACSW:UNDS:NW47:3NAMESET") {
  field(FLNK, "ACSW:UNDS:NW47:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW47:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-unds-nw47")
  field(DOL, "ACSW:UNDS:NW47:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW47:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-unds-nw47")
  field(FLNK, "ACSW:UNDS:NW47:GETINIT")
}

record(bo, "ACSW:UNDS:NW47:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-unds-nw47")
  field(FLNK, "ACSW:UNDS:NW47:GETINIT")
}

record(stringin, "ACSW:UNDS:NW47:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW47:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW47:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW47:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW47:3INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW47:3INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW47:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW47:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW47:4POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW47:4POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW47:4POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW47:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW47:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW47:4POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW47:4POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW47:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW47:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-unds-nw47")
}

record(bo, "ACSW:UNDS:NW47:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-unds-nw47")
}

record(bo, "ACSW:UNDS:NW47:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-unds-nw47")
}

record(stringin, "ACSW:UNDS:NW47:4NAMESET") {
  field(FLNK, "ACSW:UNDS:NW47:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW47:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-unds-nw47")
  field(DOL, "ACSW:UNDS:NW47:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW47:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-unds-nw47")
  field(FLNK, "ACSW:UNDS:NW47:GETINIT")
}

record(bo, "ACSW:UNDS:NW47:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-unds-nw47")
  field(FLNK, "ACSW:UNDS:NW47:GETINIT")
}

record(stringin, "ACSW:UNDS:NW47:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW47:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW47:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW47:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW47:4INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW47:4INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW47:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW47:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW47:5POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW47:5POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW47:5POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW47:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW47:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW47:5POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW47:5POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW47:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW47:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-unds-nw47")
}

record(bo, "ACSW:UNDS:NW47:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-unds-nw47")
}

record(bo, "ACSW:UNDS:NW47:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-unds-nw47")
}

record(stringin, "ACSW:UNDS:NW47:5NAMESET") {
  field(FLNK, "ACSW:UNDS:NW47:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW47:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-unds-nw47")
  field(DOL, "ACSW:UNDS:NW47:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW47:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-unds-nw47")
  field(FLNK, "ACSW:UNDS:NW47:GETINIT")
}

record(bo, "ACSW:UNDS:NW47:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-unds-nw47")
  field(FLNK, "ACSW:UNDS:NW47:GETINIT")
}

record(stringin, "ACSW:UNDS:NW47:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW47:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW47:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW47:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW47:5INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW47:5INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW47:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW47:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW47:6POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW47:6POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW47:6POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW47:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW47:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW47:6POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW47:6POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW47:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW47:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-unds-nw47")
}

record(bo, "ACSW:UNDS:NW47:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-unds-nw47")
}

record(bo, "ACSW:UNDS:NW47:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-unds-nw47")
}

record(stringin, "ACSW:UNDS:NW47:6NAMESET") {
  field(FLNK, "ACSW:UNDS:NW47:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW47:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-unds-nw47")
  field(DOL, "ACSW:UNDS:NW47:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW47:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-unds-nw47")
  field(FLNK, "ACSW:UNDS:NW47:GETINIT")
}

record(bo, "ACSW:UNDS:NW47:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-unds-nw47")
  field(FLNK, "ACSW:UNDS:NW47:GETINIT")
}

record(stringin, "ACSW:UNDS:NW47:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW47:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW47:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW47:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW47:6INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW47:6INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW47:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW47:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW47:7POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW47:7POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW47:7POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW47:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW47:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW47:7POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW47:7POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW47:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW47:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-unds-nw47")
}

record(bo, "ACSW:UNDS:NW47:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-unds-nw47")
}

record(bo, "ACSW:UNDS:NW47:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-unds-nw47")
}

record(stringin, "ACSW:UNDS:NW47:7NAMESET") {
  field(FLNK, "ACSW:UNDS:NW47:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW47:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-unds-nw47")
  field(DOL, "ACSW:UNDS:NW47:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW47:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-unds-nw47")
  field(FLNK, "ACSW:UNDS:NW47:GETINIT")
}

record(bo, "ACSW:UNDS:NW47:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-unds-nw47")
  field(FLNK, "ACSW:UNDS:NW47:GETINIT")
}

record(stringin, "ACSW:UNDS:NW47:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW47:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW47:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW47:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW47:7INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW47:7INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW47:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW47:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW47:8POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW47:8POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW47:8POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW47:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW47:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW47:8POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW47:8POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW47:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW47:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-unds-nw47")
}

record(bo, "ACSW:UNDS:NW47:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-unds-nw47")
}

record(bo, "ACSW:UNDS:NW47:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-unds-nw47")
}

record(stringin, "ACSW:UNDS:NW47:8NAMESET") {
  field(FLNK, "ACSW:UNDS:NW47:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW47:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-unds-nw47")
  field(DOL, "ACSW:UNDS:NW47:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW47:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-unds-nw47")
  field(FLNK, "ACSW:UNDS:NW47:GETINIT")
}

record(bo, "ACSW:UNDS:NW47:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-unds-nw47")
  field(FLNK, "ACSW:UNDS:NW47:GETINIT")
}

record(stringin, "ACSW:UNDS:NW47:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW47:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW47:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW47:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW47:8INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW47:8INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW47:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW47:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW50:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:UNDS:NW50) acsw-unds-nw50")
  field(FLNK, "ACSW:UNDS:NW50:GETINFO")
}

record(stringin, "ACSW:UNDS:NW50:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:UNDS:NW50) acsw-unds-nw50")
  field(FLNK, "ACSW:UNDS:NW50:GETINIT")
}

record(stringin, "ACSW:UNDS:NW50:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:UNDS:NW50:NETFWVERSION")
  field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW50:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:UNDS:NW50:SITEID")
  field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:UNDS:NW50:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:UNDS:NW50:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState8(ACSW:UNDS:NW50) acsw-unds-nw50")
}

record(stringin, "ACSW:UNDS:NW50:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState8(ACSW:UNDS:NW50) acsw-unds-nw50")
}

record(ai, "ACSW:UNDS:NW50:TYPE") {
  field(DESC, "APC 8 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "10")
}

record(stringin, "ACSW:UNDS:NW50:LOC") {
  field(PINI, "YES")
  field(VAL, "B920-50S")
  field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:UNDS:NW50:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-unds-nw50")
}

record(calcout, "ACSW:UNDS:NW50:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:UNDS:NW50:DISCONN.DISA")
  field(INPB, "ACSW:UNDS:NW50:DISCONN.DISV")
  field(INPC, "ACSW:UNDS:NW50:GETSTATUS.DISA")
  field(INPD, "ACSW:UNDS:NW50:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:UNDS:NW50:CONNSTA PP")
}

record(bi, "ACSW:UNDS:NW50:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:UNDS:NW50:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:UNDS:NW50:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:UNDS:NW50:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:UNDS:NW50:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:UNDS:NW50:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:UNDS:NW50:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:UNDS:NW50:UPTIMEHOUR") {
  field(FLNK, "ACSW:UNDS:NW50:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:UNDS:NW50:UPTIMEDAY") {
  field(FLNK, "ACSW:UNDS:NW50:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:UNDS:NW50:UPTIMEMINUTE") {
  field(FLNK, "ACSW:UNDS:NW50:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:UNDS:NW50:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW50:1POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW50:1POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW50:1POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW50:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW50:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW50:1POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW50:1POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW50:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW50:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-unds-nw50")
}

record(bo, "ACSW:UNDS:NW50:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-unds-nw50")
}

record(bo, "ACSW:UNDS:NW50:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-unds-nw50")
}

record(stringin, "ACSW:UNDS:NW50:1NAMESET") {
  field(FLNK, "ACSW:UNDS:NW50:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW50:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-unds-nw50")
  field(DOL, "ACSW:UNDS:NW50:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW50:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-unds-nw50")
  field(FLNK, "ACSW:UNDS:NW50:GETINIT")
}

record(bo, "ACSW:UNDS:NW50:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-unds-nw50")
  field(FLNK, "ACSW:UNDS:NW50:GETINIT")
}

record(stringin, "ACSW:UNDS:NW50:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW50:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW50:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW50:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW50:1INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW50:1INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW50:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW50:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW50:2POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW50:2POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW50:2POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW50:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW50:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW50:2POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW50:2POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW50:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW50:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-unds-nw50")
}

record(bo, "ACSW:UNDS:NW50:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-unds-nw50")
}

record(bo, "ACSW:UNDS:NW50:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-unds-nw50")
}

record(stringin, "ACSW:UNDS:NW50:2NAMESET") {
  field(FLNK, "ACSW:UNDS:NW50:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW50:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-unds-nw50")
  field(DOL, "ACSW:UNDS:NW50:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW50:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-unds-nw50")
  field(FLNK, "ACSW:UNDS:NW50:GETINIT")
}

record(bo, "ACSW:UNDS:NW50:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-unds-nw50")
  field(FLNK, "ACSW:UNDS:NW50:GETINIT")
}

record(stringin, "ACSW:UNDS:NW50:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW50:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW50:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW50:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW50:2INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW50:2INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW50:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW50:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW50:3POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW50:3POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW50:3POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW50:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW50:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW50:3POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW50:3POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW50:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW50:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-unds-nw50")
}

record(bo, "ACSW:UNDS:NW50:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-unds-nw50")
}

record(bo, "ACSW:UNDS:NW50:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-unds-nw50")
}

record(stringin, "ACSW:UNDS:NW50:3NAMESET") {
  field(FLNK, "ACSW:UNDS:NW50:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW50:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-unds-nw50")
  field(DOL, "ACSW:UNDS:NW50:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW50:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-unds-nw50")
  field(FLNK, "ACSW:UNDS:NW50:GETINIT")
}

record(bo, "ACSW:UNDS:NW50:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-unds-nw50")
  field(FLNK, "ACSW:UNDS:NW50:GETINIT")
}

record(stringin, "ACSW:UNDS:NW50:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW50:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW50:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW50:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW50:3INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW50:3INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW50:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW50:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW50:4POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW50:4POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW50:4POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW50:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW50:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW50:4POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW50:4POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW50:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW50:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-unds-nw50")
}

record(bo, "ACSW:UNDS:NW50:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-unds-nw50")
}

record(bo, "ACSW:UNDS:NW50:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-unds-nw50")
}

record(stringin, "ACSW:UNDS:NW50:4NAMESET") {
  field(FLNK, "ACSW:UNDS:NW50:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW50:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-unds-nw50")
  field(DOL, "ACSW:UNDS:NW50:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW50:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-unds-nw50")
  field(FLNK, "ACSW:UNDS:NW50:GETINIT")
}

record(bo, "ACSW:UNDS:NW50:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-unds-nw50")
  field(FLNK, "ACSW:UNDS:NW50:GETINIT")
}

record(stringin, "ACSW:UNDS:NW50:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW50:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW50:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW50:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW50:4INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW50:4INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW50:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW50:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW50:5POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW50:5POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW50:5POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW50:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW50:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW50:5POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW50:5POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW50:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW50:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-unds-nw50")
}

record(bo, "ACSW:UNDS:NW50:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-unds-nw50")
}

record(bo, "ACSW:UNDS:NW50:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-unds-nw50")
}

record(stringin, "ACSW:UNDS:NW50:5NAMESET") {
  field(FLNK, "ACSW:UNDS:NW50:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW50:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-unds-nw50")
  field(DOL, "ACSW:UNDS:NW50:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW50:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-unds-nw50")
  field(FLNK, "ACSW:UNDS:NW50:GETINIT")
}

record(bo, "ACSW:UNDS:NW50:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-unds-nw50")
  field(FLNK, "ACSW:UNDS:NW50:GETINIT")
}

record(stringin, "ACSW:UNDS:NW50:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW50:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW50:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW50:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW50:5INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW50:5INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW50:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW50:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW50:6POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW50:6POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW50:6POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW50:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW50:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW50:6POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW50:6POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW50:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW50:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-unds-nw50")
}

record(bo, "ACSW:UNDS:NW50:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-unds-nw50")
}

record(bo, "ACSW:UNDS:NW50:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-unds-nw50")
}

record(stringin, "ACSW:UNDS:NW50:6NAMESET") {
  field(FLNK, "ACSW:UNDS:NW50:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW50:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-unds-nw50")
  field(DOL, "ACSW:UNDS:NW50:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW50:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-unds-nw50")
  field(FLNK, "ACSW:UNDS:NW50:GETINIT")
}

record(bo, "ACSW:UNDS:NW50:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-unds-nw50")
  field(FLNK, "ACSW:UNDS:NW50:GETINIT")
}

record(stringin, "ACSW:UNDS:NW50:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW50:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW50:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW50:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW50:6INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW50:6INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW50:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW50:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW50:7POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW50:7POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW50:7POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW50:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW50:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW50:7POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW50:7POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW50:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW50:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-unds-nw50")
}

record(bo, "ACSW:UNDS:NW50:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-unds-nw50")
}

record(bo, "ACSW:UNDS:NW50:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-unds-nw50")
}

record(stringin, "ACSW:UNDS:NW50:7NAMESET") {
  field(FLNK, "ACSW:UNDS:NW50:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW50:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-unds-nw50")
  field(DOL, "ACSW:UNDS:NW50:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW50:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-unds-nw50")
  field(FLNK, "ACSW:UNDS:NW50:GETINIT")
}

record(bo, "ACSW:UNDS:NW50:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-unds-nw50")
  field(FLNK, "ACSW:UNDS:NW50:GETINIT")
}

record(stringin, "ACSW:UNDS:NW50:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW50:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW50:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW50:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW50:7INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW50:7INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW50:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:UNDS:NW50:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW50:8POWERSTATEIN")
}

record(stringin, "ACSW:UNDS:NW50:8POWERSTATEIN") {
  field(FLNK, "ACSW:UNDS:NW50:8POWERSTATESV")
}

record(scalcout, "ACSW:UNDS:NW50:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:UNDS:NW50:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:UNDS:NW50:8POWERSTATE")
}

record(mbbi, "ACSW:UNDS:NW50:8POWERSTATE") {
  field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW50:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:UNDS:NW50:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-unds-nw50")
}

record(bo, "ACSW:UNDS:NW50:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-unds-nw50")
}

record(bo, "ACSW:UNDS:NW50:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-unds-nw50")
}

record(stringin, "ACSW:UNDS:NW50:8NAMESET") {
  field(FLNK, "ACSW:UNDS:NW50:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:UNDS:NW50:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-unds-nw50")
  field(DOL, "ACSW:UNDS:NW50:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:UNDS:NW50:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-unds-nw50")
  field(FLNK, "ACSW:UNDS:NW50:GETINIT")
}

record(bo, "ACSW:UNDS:NW50:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-unds-nw50")
  field(FLNK, "ACSW:UNDS:NW50:GETINIT")
}

record(stringin, "ACSW:UNDS:NW50:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:UNDS:NW50:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:UNDS:NW50:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:UNDS:NW50:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:UNDS:NW50:8INITSTATE")
}

record(mbbi, "ACSW:UNDS:NW50:8INITSTATE") {
#  field(SDIS, "ACSW:UNDS:NW50:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:UNDS:NW50:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}