record(stringin, "ACSW:LI20:NW01:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:LI20:NW01) acsw-li20-nw01")
  field(FLNK, "ACSW:LI20:NW01:GETINFO")
}

record(stringin, "ACSW:LI20:NW01:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:LI20:NW01) acsw-li20-nw01")
  field(FLNK, "ACSW:LI20:NW01:GETINIT")
}

record(stringin, "ACSW:LI20:NW01:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:LI20:NW01:NETFWVERSION")
  field(SDIS, "ACSW:LI20:NW01:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:LI20:NW01:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:LI20:NW01:SITEID")
  field(SDIS, "ACSW:LI20:NW01:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:LI20:NW01:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:LI20:NW01:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:LI20:NW01:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState8(ACSW:LI20:NW01) acsw-li20-nw01")
}

record(stringin, "ACSW:LI20:NW01:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState8(ACSW:LI20:NW01) acsw-li20-nw01")
}

record(ai, "ACSW:LI20:NW01:TYPE") {
  field(DESC, "APC 8 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "10")
}

record(stringin, "ACSW:LI20:NW01:LOC") {
  field(PINI, "YES")
  field(VAL, "FKG20-2326")
  field(SDIS, "ACSW:LI20:NW01:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:LI20:NW01:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-li20-nw01")
}

record(calcout, "ACSW:LI20:NW01:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:LI20:NW01:DISCONN.DISA")
  field(INPB, "ACSW:LI20:NW01:DISCONN.DISV")
  field(INPC, "ACSW:LI20:NW01:GETSTATUS.DISA")
  field(INPD, "ACSW:LI20:NW01:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:LI20:NW01:CONNSTA PP")
}

record(bi, "ACSW:LI20:NW01:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:LI20:NW01:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:LI20:NW01:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:LI20:NW01:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:LI20:NW01:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:LI20:NW01:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:LI20:NW01:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:LI20:NW01:UPTIMEHOUR") {
  field(FLNK, "ACSW:LI20:NW01:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:LI20:NW01:UPTIMEDAY") {
  field(FLNK, "ACSW:LI20:NW01:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:LI20:NW01:UPTIMEMINUTE") {
  field(FLNK, "ACSW:LI20:NW01:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:LI20:NW01:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW01:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW01:1POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW01:1POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW01:1POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW01:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW01:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW01:1POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW01:1POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW01:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW01:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW01:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW01:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-li20-nw01")
}

record(bo, "ACSW:LI20:NW01:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-li20-nw01")
}

record(bo, "ACSW:LI20:NW01:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-li20-nw01")
}

record(stringin, "ACSW:LI20:NW01:1NAMESET") {
  field(FLNK, "ACSW:LI20:NW01:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW01:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-li20-nw01")
  field(DOL, "ACSW:LI20:NW01:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW01:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-li20-nw01")
  field(FLNK, "ACSW:LI20:NW01:GETINIT")
}

record(bo, "ACSW:LI20:NW01:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-li20-nw01")
  field(FLNK, "ACSW:LI20:NW01:GETINIT")
}

record(stringin, "ACSW:LI20:NW01:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW01:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW01:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW01:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW01:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW01:1INITSTATE")
}

record(mbbi, "ACSW:LI20:NW01:1INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW01:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW01:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW01:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW01:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW01:2POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW01:2POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW01:2POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW01:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW01:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW01:2POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW01:2POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW01:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW01:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW01:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW01:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-li20-nw01")
}

record(bo, "ACSW:LI20:NW01:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-li20-nw01")
}

record(bo, "ACSW:LI20:NW01:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-li20-nw01")
}

record(stringin, "ACSW:LI20:NW01:2NAMESET") {
  field(FLNK, "ACSW:LI20:NW01:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW01:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-li20-nw01")
  field(DOL, "ACSW:LI20:NW01:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW01:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-li20-nw01")
  field(FLNK, "ACSW:LI20:NW01:GETINIT")
}

record(bo, "ACSW:LI20:NW01:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-li20-nw01")
  field(FLNK, "ACSW:LI20:NW01:GETINIT")
}

record(stringin, "ACSW:LI20:NW01:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW01:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW01:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW01:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW01:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW01:2INITSTATE")
}

record(mbbi, "ACSW:LI20:NW01:2INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW01:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW01:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW01:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW01:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW01:3POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW01:3POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW01:3POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW01:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW01:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW01:3POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW01:3POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW01:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW01:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW01:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW01:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-li20-nw01")
}

record(bo, "ACSW:LI20:NW01:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-li20-nw01")
}

record(bo, "ACSW:LI20:NW01:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-li20-nw01")
}

record(stringin, "ACSW:LI20:NW01:3NAMESET") {
  field(FLNK, "ACSW:LI20:NW01:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW01:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-li20-nw01")
  field(DOL, "ACSW:LI20:NW01:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW01:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-li20-nw01")
  field(FLNK, "ACSW:LI20:NW01:GETINIT")
}

record(bo, "ACSW:LI20:NW01:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-li20-nw01")
  field(FLNK, "ACSW:LI20:NW01:GETINIT")
}

record(stringin, "ACSW:LI20:NW01:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW01:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW01:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW01:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW01:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW01:3INITSTATE")
}

record(mbbi, "ACSW:LI20:NW01:3INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW01:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW01:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW01:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW01:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW01:4POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW01:4POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW01:4POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW01:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW01:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW01:4POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW01:4POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW01:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW01:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW01:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW01:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-li20-nw01")
}

record(bo, "ACSW:LI20:NW01:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-li20-nw01")
}

record(bo, "ACSW:LI20:NW01:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-li20-nw01")
}

record(stringin, "ACSW:LI20:NW01:4NAMESET") {
  field(FLNK, "ACSW:LI20:NW01:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW01:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-li20-nw01")
  field(DOL, "ACSW:LI20:NW01:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW01:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-li20-nw01")
  field(FLNK, "ACSW:LI20:NW01:GETINIT")
}

record(bo, "ACSW:LI20:NW01:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-li20-nw01")
  field(FLNK, "ACSW:LI20:NW01:GETINIT")
}

record(stringin, "ACSW:LI20:NW01:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW01:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW01:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW01:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW01:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW01:4INITSTATE")
}

record(mbbi, "ACSW:LI20:NW01:4INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW01:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW01:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW01:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW01:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW01:5POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW01:5POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW01:5POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW01:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW01:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW01:5POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW01:5POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW01:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW01:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW01:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW01:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-li20-nw01")
}

record(bo, "ACSW:LI20:NW01:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-li20-nw01")
}

record(bo, "ACSW:LI20:NW01:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-li20-nw01")
}

record(stringin, "ACSW:LI20:NW01:5NAMESET") {
  field(FLNK, "ACSW:LI20:NW01:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW01:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-li20-nw01")
  field(DOL, "ACSW:LI20:NW01:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW01:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-li20-nw01")
  field(FLNK, "ACSW:LI20:NW01:GETINIT")
}

record(bo, "ACSW:LI20:NW01:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-li20-nw01")
  field(FLNK, "ACSW:LI20:NW01:GETINIT")
}

record(stringin, "ACSW:LI20:NW01:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW01:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW01:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW01:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW01:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW01:5INITSTATE")
}

record(mbbi, "ACSW:LI20:NW01:5INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW01:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW01:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW01:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW01:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW01:6POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW01:6POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW01:6POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW01:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW01:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW01:6POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW01:6POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW01:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW01:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW01:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW01:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-li20-nw01")
}

record(bo, "ACSW:LI20:NW01:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-li20-nw01")
}

record(bo, "ACSW:LI20:NW01:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-li20-nw01")
}

record(stringin, "ACSW:LI20:NW01:6NAMESET") {
  field(FLNK, "ACSW:LI20:NW01:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW01:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-li20-nw01")
  field(DOL, "ACSW:LI20:NW01:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW01:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-li20-nw01")
  field(FLNK, "ACSW:LI20:NW01:GETINIT")
}

record(bo, "ACSW:LI20:NW01:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-li20-nw01")
  field(FLNK, "ACSW:LI20:NW01:GETINIT")
}

record(stringin, "ACSW:LI20:NW01:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW01:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW01:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW01:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW01:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW01:6INITSTATE")
}

record(mbbi, "ACSW:LI20:NW01:6INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW01:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW01:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW01:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW01:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW01:7POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW01:7POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW01:7POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW01:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW01:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW01:7POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW01:7POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW01:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW01:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW01:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW01:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-li20-nw01")
}

record(bo, "ACSW:LI20:NW01:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-li20-nw01")
}

record(bo, "ACSW:LI20:NW01:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-li20-nw01")
}

record(stringin, "ACSW:LI20:NW01:7NAMESET") {
  field(FLNK, "ACSW:LI20:NW01:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW01:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-li20-nw01")
  field(DOL, "ACSW:LI20:NW01:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW01:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-li20-nw01")
  field(FLNK, "ACSW:LI20:NW01:GETINIT")
}

record(bo, "ACSW:LI20:NW01:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-li20-nw01")
  field(FLNK, "ACSW:LI20:NW01:GETINIT")
}

record(stringin, "ACSW:LI20:NW01:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW01:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW01:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW01:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW01:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW01:7INITSTATE")
}

record(mbbi, "ACSW:LI20:NW01:7INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW01:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW01:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW01:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW01:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW01:8POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW01:8POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW01:8POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW01:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW01:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW01:8POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW01:8POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW01:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW01:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW01:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW01:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-li20-nw01")
}

record(bo, "ACSW:LI20:NW01:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-li20-nw01")
}

record(bo, "ACSW:LI20:NW01:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-li20-nw01")
}

record(stringin, "ACSW:LI20:NW01:8NAMESET") {
  field(FLNK, "ACSW:LI20:NW01:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW01:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-li20-nw01")
  field(DOL, "ACSW:LI20:NW01:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW01:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-li20-nw01")
  field(FLNK, "ACSW:LI20:NW01:GETINIT")
}

record(bo, "ACSW:LI20:NW01:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-li20-nw01")
  field(FLNK, "ACSW:LI20:NW01:GETINIT")
}

record(stringin, "ACSW:LI20:NW01:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW01:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW01:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW01:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW01:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW01:8INITSTATE")
}

record(mbbi, "ACSW:LI20:NW01:8INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW01:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW01:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW08:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:LI20:NW08) acsw-li20-nw08")
  field(FLNK, "ACSW:LI20:NW08:GETINFO")
}

record(stringin, "ACSW:LI20:NW08:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:LI20:NW08) acsw-li20-nw08")
  field(FLNK, "ACSW:LI20:NW08:GETINIT")
}

record(stringin, "ACSW:LI20:NW08:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:LI20:NW08:NETFWVERSION")
  field(SDIS, "ACSW:LI20:NW08:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:LI20:NW08:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:LI20:NW08:SITEID")
  field(SDIS, "ACSW:LI20:NW08:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:LI20:NW08:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:LI20:NW08:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:LI20:NW08:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState8(ACSW:LI20:NW08) acsw-li20-nw08")
}

record(stringin, "ACSW:LI20:NW08:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState8(ACSW:LI20:NW08) acsw-li20-nw08")
}

record(ai, "ACSW:LI20:NW08:TYPE") {
  field(DESC, "APC 8 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "10")
}

record(stringin, "ACSW:LI20:NW08:LOC") {
  field(PINI, "YES")
  field(VAL, "FKG20-0121B")
  field(SDIS, "ACSW:LI20:NW08:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:LI20:NW08:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-li20-nw08")
}

record(calcout, "ACSW:LI20:NW08:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:LI20:NW08:DISCONN.DISA")
  field(INPB, "ACSW:LI20:NW08:DISCONN.DISV")
  field(INPC, "ACSW:LI20:NW08:GETSTATUS.DISA")
  field(INPD, "ACSW:LI20:NW08:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:LI20:NW08:CONNSTA PP")
}

record(bi, "ACSW:LI20:NW08:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:LI20:NW08:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:LI20:NW08:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:LI20:NW08:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:LI20:NW08:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:LI20:NW08:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:LI20:NW08:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:LI20:NW08:UPTIMEHOUR") {
  field(FLNK, "ACSW:LI20:NW08:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:LI20:NW08:UPTIMEDAY") {
  field(FLNK, "ACSW:LI20:NW08:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:LI20:NW08:UPTIMEMINUTE") {
  field(FLNK, "ACSW:LI20:NW08:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:LI20:NW08:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW08:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW08:1POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW08:1POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW08:1POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW08:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW08:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW08:1POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW08:1POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW08:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW08:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW08:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW08:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-li20-nw08")
}

record(bo, "ACSW:LI20:NW08:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-li20-nw08")
}

record(bo, "ACSW:LI20:NW08:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-li20-nw08")
}

record(stringin, "ACSW:LI20:NW08:1NAMESET") {
  field(FLNK, "ACSW:LI20:NW08:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW08:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-li20-nw08")
  field(DOL, "ACSW:LI20:NW08:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW08:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-li20-nw08")
  field(FLNK, "ACSW:LI20:NW08:GETINIT")
}

record(bo, "ACSW:LI20:NW08:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-li20-nw08")
  field(FLNK, "ACSW:LI20:NW08:GETINIT")
}

record(stringin, "ACSW:LI20:NW08:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW08:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW08:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW08:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW08:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW08:1INITSTATE")
}

record(mbbi, "ACSW:LI20:NW08:1INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW08:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW08:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW08:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW08:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW08:2POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW08:2POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW08:2POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW08:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW08:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW08:2POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW08:2POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW08:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW08:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW08:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW08:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-li20-nw08")
}

record(bo, "ACSW:LI20:NW08:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-li20-nw08")
}

record(bo, "ACSW:LI20:NW08:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-li20-nw08")
}

record(stringin, "ACSW:LI20:NW08:2NAMESET") {
  field(FLNK, "ACSW:LI20:NW08:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW08:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-li20-nw08")
  field(DOL, "ACSW:LI20:NW08:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW08:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-li20-nw08")
  field(FLNK, "ACSW:LI20:NW08:GETINIT")
}

record(bo, "ACSW:LI20:NW08:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-li20-nw08")
  field(FLNK, "ACSW:LI20:NW08:GETINIT")
}

record(stringin, "ACSW:LI20:NW08:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW08:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW08:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW08:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW08:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW08:2INITSTATE")
}

record(mbbi, "ACSW:LI20:NW08:2INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW08:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW08:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW08:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW08:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW08:3POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW08:3POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW08:3POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW08:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW08:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW08:3POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW08:3POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW08:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW08:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW08:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW08:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-li20-nw08")
}

record(bo, "ACSW:LI20:NW08:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-li20-nw08")
}

record(bo, "ACSW:LI20:NW08:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-li20-nw08")
}

record(stringin, "ACSW:LI20:NW08:3NAMESET") {
  field(FLNK, "ACSW:LI20:NW08:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW08:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-li20-nw08")
  field(DOL, "ACSW:LI20:NW08:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW08:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-li20-nw08")
  field(FLNK, "ACSW:LI20:NW08:GETINIT")
}

record(bo, "ACSW:LI20:NW08:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-li20-nw08")
  field(FLNK, "ACSW:LI20:NW08:GETINIT")
}

record(stringin, "ACSW:LI20:NW08:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW08:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW08:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW08:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW08:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW08:3INITSTATE")
}

record(mbbi, "ACSW:LI20:NW08:3INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW08:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW08:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW08:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW08:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW08:4POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW08:4POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW08:4POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW08:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW08:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW08:4POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW08:4POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW08:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW08:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW08:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW08:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-li20-nw08")
}

record(bo, "ACSW:LI20:NW08:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-li20-nw08")
}

record(bo, "ACSW:LI20:NW08:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-li20-nw08")
}

record(stringin, "ACSW:LI20:NW08:4NAMESET") {
  field(FLNK, "ACSW:LI20:NW08:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW08:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-li20-nw08")
  field(DOL, "ACSW:LI20:NW08:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW08:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-li20-nw08")
  field(FLNK, "ACSW:LI20:NW08:GETINIT")
}

record(bo, "ACSW:LI20:NW08:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-li20-nw08")
  field(FLNK, "ACSW:LI20:NW08:GETINIT")
}

record(stringin, "ACSW:LI20:NW08:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW08:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW08:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW08:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW08:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW08:4INITSTATE")
}

record(mbbi, "ACSW:LI20:NW08:4INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW08:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW08:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW08:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW08:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW08:5POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW08:5POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW08:5POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW08:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW08:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW08:5POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW08:5POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW08:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW08:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW08:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW08:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-li20-nw08")
}

record(bo, "ACSW:LI20:NW08:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-li20-nw08")
}

record(bo, "ACSW:LI20:NW08:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-li20-nw08")
}

record(stringin, "ACSW:LI20:NW08:5NAMESET") {
  field(FLNK, "ACSW:LI20:NW08:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW08:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-li20-nw08")
  field(DOL, "ACSW:LI20:NW08:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW08:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-li20-nw08")
  field(FLNK, "ACSW:LI20:NW08:GETINIT")
}

record(bo, "ACSW:LI20:NW08:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-li20-nw08")
  field(FLNK, "ACSW:LI20:NW08:GETINIT")
}

record(stringin, "ACSW:LI20:NW08:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW08:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW08:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW08:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW08:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW08:5INITSTATE")
}

record(mbbi, "ACSW:LI20:NW08:5INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW08:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW08:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW08:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW08:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW08:6POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW08:6POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW08:6POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW08:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW08:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW08:6POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW08:6POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW08:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW08:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW08:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW08:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-li20-nw08")
}

record(bo, "ACSW:LI20:NW08:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-li20-nw08")
}

record(bo, "ACSW:LI20:NW08:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-li20-nw08")
}

record(stringin, "ACSW:LI20:NW08:6NAMESET") {
  field(FLNK, "ACSW:LI20:NW08:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW08:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-li20-nw08")
  field(DOL, "ACSW:LI20:NW08:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW08:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-li20-nw08")
  field(FLNK, "ACSW:LI20:NW08:GETINIT")
}

record(bo, "ACSW:LI20:NW08:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-li20-nw08")
  field(FLNK, "ACSW:LI20:NW08:GETINIT")
}

record(stringin, "ACSW:LI20:NW08:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW08:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW08:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW08:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW08:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW08:6INITSTATE")
}

record(mbbi, "ACSW:LI20:NW08:6INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW08:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW08:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW08:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW08:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW08:7POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW08:7POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW08:7POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW08:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW08:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW08:7POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW08:7POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW08:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW08:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW08:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW08:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-li20-nw08")
}

record(bo, "ACSW:LI20:NW08:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-li20-nw08")
}

record(bo, "ACSW:LI20:NW08:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-li20-nw08")
}

record(stringin, "ACSW:LI20:NW08:7NAMESET") {
  field(FLNK, "ACSW:LI20:NW08:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW08:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-li20-nw08")
  field(DOL, "ACSW:LI20:NW08:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW08:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-li20-nw08")
  field(FLNK, "ACSW:LI20:NW08:GETINIT")
}

record(bo, "ACSW:LI20:NW08:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-li20-nw08")
  field(FLNK, "ACSW:LI20:NW08:GETINIT")
}

record(stringin, "ACSW:LI20:NW08:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW08:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW08:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW08:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW08:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW08:7INITSTATE")
}

record(mbbi, "ACSW:LI20:NW08:7INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW08:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW08:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW08:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW08:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW08:8POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW08:8POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW08:8POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW08:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW08:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW08:8POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW08:8POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW08:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW08:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW08:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW08:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-li20-nw08")
}

record(bo, "ACSW:LI20:NW08:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-li20-nw08")
}

record(bo, "ACSW:LI20:NW08:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-li20-nw08")
}

record(stringin, "ACSW:LI20:NW08:8NAMESET") {
  field(FLNK, "ACSW:LI20:NW08:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW08:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-li20-nw08")
  field(DOL, "ACSW:LI20:NW08:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW08:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-li20-nw08")
  field(FLNK, "ACSW:LI20:NW08:GETINIT")
}

record(bo, "ACSW:LI20:NW08:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-li20-nw08")
  field(FLNK, "ACSW:LI20:NW08:GETINIT")
}

record(stringin, "ACSW:LI20:NW08:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW08:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW08:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW08:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW08:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW08:8INITSTATE")
}

record(mbbi, "ACSW:LI20:NW08:8INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW08:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW08:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW09:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:LI20:NW09) acsw-li20-nw09")
  field(FLNK, "ACSW:LI20:NW09:GETINFO")
}

record(stringin, "ACSW:LI20:NW09:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:LI20:NW09) acsw-li20-nw09")
  field(FLNK, "ACSW:LI20:NW09:GETINIT")
}

record(stringin, "ACSW:LI20:NW09:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:LI20:NW09:NETFWVERSION")
  field(SDIS, "ACSW:LI20:NW09:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:LI20:NW09:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:LI20:NW09:SITEID")
  field(SDIS, "ACSW:LI20:NW09:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:LI20:NW09:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:LI20:NW09:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:LI20:NW09:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState8(ACSW:LI20:NW09) acsw-li20-nw09")
}

record(stringin, "ACSW:LI20:NW09:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState8(ACSW:LI20:NW09) acsw-li20-nw09")
}

record(ai, "ACSW:LI20:NW09:TYPE") {
  field(DESC, "APC 8 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "10")
}

record(stringin, "ACSW:LI20:NW09:LOC") {
  field(PINI, "YES")
  field(VAL, "KF20-4B32")
  field(SDIS, "ACSW:LI20:NW09:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:LI20:NW09:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-li20-nw09")
}

record(calcout, "ACSW:LI20:NW09:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:LI20:NW09:DISCONN.DISA")
  field(INPB, "ACSW:LI20:NW09:DISCONN.DISV")
  field(INPC, "ACSW:LI20:NW09:GETSTATUS.DISA")
  field(INPD, "ACSW:LI20:NW09:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:LI20:NW09:CONNSTA PP")
}

record(bi, "ACSW:LI20:NW09:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:LI20:NW09:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:LI20:NW09:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:LI20:NW09:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:LI20:NW09:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:LI20:NW09:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:LI20:NW09:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:LI20:NW09:UPTIMEHOUR") {
  field(FLNK, "ACSW:LI20:NW09:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:LI20:NW09:UPTIMEDAY") {
  field(FLNK, "ACSW:LI20:NW09:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:LI20:NW09:UPTIMEMINUTE") {
  field(FLNK, "ACSW:LI20:NW09:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:LI20:NW09:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW09:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW09:1POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW09:1POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW09:1POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW09:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW09:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW09:1POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW09:1POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW09:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW09:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW09:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW09:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-li20-nw09")
}

record(bo, "ACSW:LI20:NW09:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-li20-nw09")
}

record(bo, "ACSW:LI20:NW09:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-li20-nw09")
}

record(stringin, "ACSW:LI20:NW09:1NAMESET") {
  field(FLNK, "ACSW:LI20:NW09:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW09:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-li20-nw09")
  field(DOL, "ACSW:LI20:NW09:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW09:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-li20-nw09")
  field(FLNK, "ACSW:LI20:NW09:GETINIT")
}

record(bo, "ACSW:LI20:NW09:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-li20-nw09")
  field(FLNK, "ACSW:LI20:NW09:GETINIT")
}

record(stringin, "ACSW:LI20:NW09:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW09:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW09:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW09:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW09:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW09:1INITSTATE")
}

record(mbbi, "ACSW:LI20:NW09:1INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW09:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW09:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW09:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW09:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW09:2POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW09:2POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW09:2POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW09:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW09:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW09:2POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW09:2POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW09:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW09:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW09:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW09:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-li20-nw09")
}

record(bo, "ACSW:LI20:NW09:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-li20-nw09")
}

record(bo, "ACSW:LI20:NW09:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-li20-nw09")
}

record(stringin, "ACSW:LI20:NW09:2NAMESET") {
  field(FLNK, "ACSW:LI20:NW09:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW09:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-li20-nw09")
  field(DOL, "ACSW:LI20:NW09:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW09:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-li20-nw09")
  field(FLNK, "ACSW:LI20:NW09:GETINIT")
}

record(bo, "ACSW:LI20:NW09:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-li20-nw09")
  field(FLNK, "ACSW:LI20:NW09:GETINIT")
}

record(stringin, "ACSW:LI20:NW09:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW09:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW09:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW09:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW09:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW09:2INITSTATE")
}

record(mbbi, "ACSW:LI20:NW09:2INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW09:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW09:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW09:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW09:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW09:3POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW09:3POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW09:3POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW09:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW09:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW09:3POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW09:3POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW09:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW09:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW09:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW09:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-li20-nw09")
}

record(bo, "ACSW:LI20:NW09:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-li20-nw09")
}

record(bo, "ACSW:LI20:NW09:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-li20-nw09")
}

record(stringin, "ACSW:LI20:NW09:3NAMESET") {
  field(FLNK, "ACSW:LI20:NW09:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW09:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-li20-nw09")
  field(DOL, "ACSW:LI20:NW09:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW09:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-li20-nw09")
  field(FLNK, "ACSW:LI20:NW09:GETINIT")
}

record(bo, "ACSW:LI20:NW09:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-li20-nw09")
  field(FLNK, "ACSW:LI20:NW09:GETINIT")
}

record(stringin, "ACSW:LI20:NW09:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW09:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW09:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW09:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW09:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW09:3INITSTATE")
}

record(mbbi, "ACSW:LI20:NW09:3INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW09:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW09:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW09:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW09:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW09:4POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW09:4POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW09:4POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW09:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW09:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW09:4POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW09:4POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW09:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW09:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW09:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW09:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-li20-nw09")
}

record(bo, "ACSW:LI20:NW09:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-li20-nw09")
}

record(bo, "ACSW:LI20:NW09:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-li20-nw09")
}

record(stringin, "ACSW:LI20:NW09:4NAMESET") {
  field(FLNK, "ACSW:LI20:NW09:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW09:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-li20-nw09")
  field(DOL, "ACSW:LI20:NW09:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW09:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-li20-nw09")
  field(FLNK, "ACSW:LI20:NW09:GETINIT")
}

record(bo, "ACSW:LI20:NW09:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-li20-nw09")
  field(FLNK, "ACSW:LI20:NW09:GETINIT")
}

record(stringin, "ACSW:LI20:NW09:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW09:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW09:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW09:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW09:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW09:4INITSTATE")
}

record(mbbi, "ACSW:LI20:NW09:4INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW09:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW09:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW09:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW09:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW09:5POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW09:5POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW09:5POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW09:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW09:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW09:5POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW09:5POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW09:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW09:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW09:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW09:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-li20-nw09")
}

record(bo, "ACSW:LI20:NW09:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-li20-nw09")
}

record(bo, "ACSW:LI20:NW09:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-li20-nw09")
}

record(stringin, "ACSW:LI20:NW09:5NAMESET") {
  field(FLNK, "ACSW:LI20:NW09:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW09:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-li20-nw09")
  field(DOL, "ACSW:LI20:NW09:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW09:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-li20-nw09")
  field(FLNK, "ACSW:LI20:NW09:GETINIT")
}

record(bo, "ACSW:LI20:NW09:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-li20-nw09")
  field(FLNK, "ACSW:LI20:NW09:GETINIT")
}

record(stringin, "ACSW:LI20:NW09:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW09:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW09:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW09:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW09:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW09:5INITSTATE")
}

record(mbbi, "ACSW:LI20:NW09:5INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW09:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW09:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW09:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW09:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW09:6POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW09:6POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW09:6POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW09:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW09:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW09:6POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW09:6POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW09:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW09:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW09:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW09:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-li20-nw09")
}

record(bo, "ACSW:LI20:NW09:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-li20-nw09")
}

record(bo, "ACSW:LI20:NW09:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-li20-nw09")
}

record(stringin, "ACSW:LI20:NW09:6NAMESET") {
  field(FLNK, "ACSW:LI20:NW09:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW09:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-li20-nw09")
  field(DOL, "ACSW:LI20:NW09:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW09:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-li20-nw09")
  field(FLNK, "ACSW:LI20:NW09:GETINIT")
}

record(bo, "ACSW:LI20:NW09:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-li20-nw09")
  field(FLNK, "ACSW:LI20:NW09:GETINIT")
}

record(stringin, "ACSW:LI20:NW09:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW09:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW09:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW09:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW09:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW09:6INITSTATE")
}

record(mbbi, "ACSW:LI20:NW09:6INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW09:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW09:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW09:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW09:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW09:7POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW09:7POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW09:7POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW09:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW09:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW09:7POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW09:7POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW09:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW09:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW09:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW09:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-li20-nw09")
}

record(bo, "ACSW:LI20:NW09:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-li20-nw09")
}

record(bo, "ACSW:LI20:NW09:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-li20-nw09")
}

record(stringin, "ACSW:LI20:NW09:7NAMESET") {
  field(FLNK, "ACSW:LI20:NW09:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW09:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-li20-nw09")
  field(DOL, "ACSW:LI20:NW09:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW09:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-li20-nw09")
  field(FLNK, "ACSW:LI20:NW09:GETINIT")
}

record(bo, "ACSW:LI20:NW09:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-li20-nw09")
  field(FLNK, "ACSW:LI20:NW09:GETINIT")
}

record(stringin, "ACSW:LI20:NW09:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW09:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW09:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW09:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW09:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW09:7INITSTATE")
}

record(mbbi, "ACSW:LI20:NW09:7INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW09:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW09:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW09:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW09:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW09:8POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW09:8POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW09:8POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW09:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW09:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW09:8POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW09:8POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW09:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW09:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW09:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW09:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-li20-nw09")
}

record(bo, "ACSW:LI20:NW09:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-li20-nw09")
}

record(bo, "ACSW:LI20:NW09:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-li20-nw09")
}

record(stringin, "ACSW:LI20:NW09:8NAMESET") {
  field(FLNK, "ACSW:LI20:NW09:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW09:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-li20-nw09")
  field(DOL, "ACSW:LI20:NW09:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW09:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-li20-nw09")
  field(FLNK, "ACSW:LI20:NW09:GETINIT")
}

record(bo, "ACSW:LI20:NW09:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-li20-nw09")
  field(FLNK, "ACSW:LI20:NW09:GETINIT")
}

record(stringin, "ACSW:LI20:NW09:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW09:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW09:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW09:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW09:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW09:8INITSTATE")
}

record(mbbi, "ACSW:LI20:NW09:8INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW09:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW09:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW17:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:LI20:NW17) acsw-li20-nw17")
  field(FLNK, "ACSW:LI20:NW17:GETINFO")
}

record(stringin, "ACSW:LI20:NW17:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:LI20:NW17) acsw-li20-nw17")
  field(FLNK, "ACSW:LI20:NW17:GETINIT")
}

record(stringin, "ACSW:LI20:NW17:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:LI20:NW17:NETFWVERSION")
  field(SDIS, "ACSW:LI20:NW17:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:LI20:NW17:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:LI20:NW17:SITEID")
  field(SDIS, "ACSW:LI20:NW17:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:LI20:NW17:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:LI20:NW17:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:LI20:NW17:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState8(ACSW:LI20:NW17) acsw-li20-nw17")
}

record(stringin, "ACSW:LI20:NW17:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState8(ACSW:LI20:NW17) acsw-li20-nw17")
}

record(ai, "ACSW:LI20:NW17:TYPE") {
  field(DESC, "APC 8 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "10")
}

record(stringin, "ACSW:LI20:NW17:LOC") {
  field(PINI, "YES")
  field(VAL, "Pen 20-11")
  field(SDIS, "ACSW:LI20:NW17:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:LI20:NW17:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-li20-nw17")
}

record(calcout, "ACSW:LI20:NW17:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:LI20:NW17:DISCONN.DISA")
  field(INPB, "ACSW:LI20:NW17:DISCONN.DISV")
  field(INPC, "ACSW:LI20:NW17:GETSTATUS.DISA")
  field(INPD, "ACSW:LI20:NW17:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:LI20:NW17:CONNSTA PP")
}

record(bi, "ACSW:LI20:NW17:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:LI20:NW17:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:LI20:NW17:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:LI20:NW17:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:LI20:NW17:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:LI20:NW17:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:LI20:NW17:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:LI20:NW17:UPTIMEHOUR") {
  field(FLNK, "ACSW:LI20:NW17:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:LI20:NW17:UPTIMEDAY") {
  field(FLNK, "ACSW:LI20:NW17:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:LI20:NW17:UPTIMEMINUTE") {
  field(FLNK, "ACSW:LI20:NW17:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:LI20:NW17:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW17:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW17:1POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW17:1POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW17:1POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW17:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW17:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW17:1POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW17:1POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW17:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW17:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW17:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW17:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-li20-nw17")
}

record(bo, "ACSW:LI20:NW17:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-li20-nw17")
}

record(bo, "ACSW:LI20:NW17:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-li20-nw17")
}

record(stringin, "ACSW:LI20:NW17:1NAMESET") {
  field(FLNK, "ACSW:LI20:NW17:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW17:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-li20-nw17")
  field(DOL, "ACSW:LI20:NW17:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW17:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-li20-nw17")
  field(FLNK, "ACSW:LI20:NW17:GETINIT")
}

record(bo, "ACSW:LI20:NW17:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-li20-nw17")
  field(FLNK, "ACSW:LI20:NW17:GETINIT")
}

record(stringin, "ACSW:LI20:NW17:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW17:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW17:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW17:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW17:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW17:1INITSTATE")
}

record(mbbi, "ACSW:LI20:NW17:1INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW17:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW17:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW17:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW17:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW17:2POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW17:2POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW17:2POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW17:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW17:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW17:2POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW17:2POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW17:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW17:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW17:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW17:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-li20-nw17")
}

record(bo, "ACSW:LI20:NW17:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-li20-nw17")
}

record(bo, "ACSW:LI20:NW17:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-li20-nw17")
}

record(stringin, "ACSW:LI20:NW17:2NAMESET") {
  field(FLNK, "ACSW:LI20:NW17:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW17:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-li20-nw17")
  field(DOL, "ACSW:LI20:NW17:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW17:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-li20-nw17")
  field(FLNK, "ACSW:LI20:NW17:GETINIT")
}

record(bo, "ACSW:LI20:NW17:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-li20-nw17")
  field(FLNK, "ACSW:LI20:NW17:GETINIT")
}

record(stringin, "ACSW:LI20:NW17:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW17:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW17:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW17:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW17:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW17:2INITSTATE")
}

record(mbbi, "ACSW:LI20:NW17:2INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW17:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW17:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW17:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW17:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW17:3POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW17:3POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW17:3POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW17:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW17:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW17:3POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW17:3POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW17:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW17:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW17:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW17:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-li20-nw17")
}

record(bo, "ACSW:LI20:NW17:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-li20-nw17")
}

record(bo, "ACSW:LI20:NW17:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-li20-nw17")
}

record(stringin, "ACSW:LI20:NW17:3NAMESET") {
  field(FLNK, "ACSW:LI20:NW17:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW17:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-li20-nw17")
  field(DOL, "ACSW:LI20:NW17:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW17:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-li20-nw17")
  field(FLNK, "ACSW:LI20:NW17:GETINIT")
}

record(bo, "ACSW:LI20:NW17:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-li20-nw17")
  field(FLNK, "ACSW:LI20:NW17:GETINIT")
}

record(stringin, "ACSW:LI20:NW17:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW17:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW17:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW17:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW17:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW17:3INITSTATE")
}

record(mbbi, "ACSW:LI20:NW17:3INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW17:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW17:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW17:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW17:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW17:4POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW17:4POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW17:4POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW17:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW17:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW17:4POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW17:4POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW17:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW17:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW17:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW17:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-li20-nw17")
}

record(bo, "ACSW:LI20:NW17:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-li20-nw17")
}

record(bo, "ACSW:LI20:NW17:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-li20-nw17")
}

record(stringin, "ACSW:LI20:NW17:4NAMESET") {
  field(FLNK, "ACSW:LI20:NW17:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW17:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-li20-nw17")
  field(DOL, "ACSW:LI20:NW17:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW17:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-li20-nw17")
  field(FLNK, "ACSW:LI20:NW17:GETINIT")
}

record(bo, "ACSW:LI20:NW17:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-li20-nw17")
  field(FLNK, "ACSW:LI20:NW17:GETINIT")
}

record(stringin, "ACSW:LI20:NW17:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW17:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW17:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW17:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW17:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW17:4INITSTATE")
}

record(mbbi, "ACSW:LI20:NW17:4INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW17:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW17:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW17:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW17:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW17:5POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW17:5POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW17:5POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW17:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW17:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW17:5POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW17:5POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW17:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW17:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW17:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW17:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-li20-nw17")
}

record(bo, "ACSW:LI20:NW17:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-li20-nw17")
}

record(bo, "ACSW:LI20:NW17:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-li20-nw17")
}

record(stringin, "ACSW:LI20:NW17:5NAMESET") {
  field(FLNK, "ACSW:LI20:NW17:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW17:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-li20-nw17")
  field(DOL, "ACSW:LI20:NW17:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW17:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-li20-nw17")
  field(FLNK, "ACSW:LI20:NW17:GETINIT")
}

record(bo, "ACSW:LI20:NW17:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-li20-nw17")
  field(FLNK, "ACSW:LI20:NW17:GETINIT")
}

record(stringin, "ACSW:LI20:NW17:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW17:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW17:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW17:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW17:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW17:5INITSTATE")
}

record(mbbi, "ACSW:LI20:NW17:5INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW17:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW17:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW17:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW17:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW17:6POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW17:6POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW17:6POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW17:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW17:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW17:6POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW17:6POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW17:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW17:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW17:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW17:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-li20-nw17")
}

record(bo, "ACSW:LI20:NW17:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-li20-nw17")
}

record(bo, "ACSW:LI20:NW17:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-li20-nw17")
}

record(stringin, "ACSW:LI20:NW17:6NAMESET") {
  field(FLNK, "ACSW:LI20:NW17:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW17:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-li20-nw17")
  field(DOL, "ACSW:LI20:NW17:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW17:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-li20-nw17")
  field(FLNK, "ACSW:LI20:NW17:GETINIT")
}

record(bo, "ACSW:LI20:NW17:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-li20-nw17")
  field(FLNK, "ACSW:LI20:NW17:GETINIT")
}

record(stringin, "ACSW:LI20:NW17:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW17:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW17:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW17:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW17:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW17:6INITSTATE")
}

record(mbbi, "ACSW:LI20:NW17:6INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW17:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW17:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW17:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW17:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW17:7POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW17:7POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW17:7POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW17:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW17:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW17:7POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW17:7POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW17:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW17:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW17:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW17:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-li20-nw17")
}

record(bo, "ACSW:LI20:NW17:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-li20-nw17")
}

record(bo, "ACSW:LI20:NW17:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-li20-nw17")
}

record(stringin, "ACSW:LI20:NW17:7NAMESET") {
  field(FLNK, "ACSW:LI20:NW17:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW17:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-li20-nw17")
  field(DOL, "ACSW:LI20:NW17:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW17:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-li20-nw17")
  field(FLNK, "ACSW:LI20:NW17:GETINIT")
}

record(bo, "ACSW:LI20:NW17:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-li20-nw17")
  field(FLNK, "ACSW:LI20:NW17:GETINIT")
}

record(stringin, "ACSW:LI20:NW17:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW17:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW17:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW17:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW17:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW17:7INITSTATE")
}

record(mbbi, "ACSW:LI20:NW17:7INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW17:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW17:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW17:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW17:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW17:8POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW17:8POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW17:8POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW17:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW17:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW17:8POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW17:8POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW17:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW17:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW17:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW17:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-li20-nw17")
}

record(bo, "ACSW:LI20:NW17:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-li20-nw17")
}

record(bo, "ACSW:LI20:NW17:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-li20-nw17")
}

record(stringin, "ACSW:LI20:NW17:8NAMESET") {
  field(FLNK, "ACSW:LI20:NW17:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW17:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-li20-nw17")
  field(DOL, "ACSW:LI20:NW17:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW17:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-li20-nw17")
  field(FLNK, "ACSW:LI20:NW17:GETINIT")
}

record(bo, "ACSW:LI20:NW17:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-li20-nw17")
  field(FLNK, "ACSW:LI20:NW17:GETINIT")
}

record(stringin, "ACSW:LI20:NW17:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW17:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW17:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW17:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW17:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW17:8INITSTATE")
}

record(mbbi, "ACSW:LI20:NW17:8INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW17:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW17:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW18:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:LI20:NW18) acsw-li20-nw18")
  field(FLNK, "ACSW:LI20:NW18:GETINFO")
}

record(stringin, "ACSW:LI20:NW18:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:LI20:NW18) acsw-li20-nw18")
  field(FLNK, "ACSW:LI20:NW18:GETINIT")
}

record(stringin, "ACSW:LI20:NW18:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:LI20:NW18:NETFWVERSION")
  field(SDIS, "ACSW:LI20:NW18:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:LI20:NW18:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:LI20:NW18:SITEID")
  field(SDIS, "ACSW:LI20:NW18:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:LI20:NW18:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:LI20:NW18:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:LI20:NW18:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState8(ACSW:LI20:NW18) acsw-li20-nw18")
}

record(stringin, "ACSW:LI20:NW18:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState8(ACSW:LI20:NW18) acsw-li20-nw18")
}

record(ai, "ACSW:LI20:NW18:TYPE") {
  field(DESC, "APC 8 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "10")
}

record(stringin, "ACSW:LI20:NW18:LOC") {
  field(PINI, "YES")
  field(VAL, "FKG20-01xx")
  field(SDIS, "ACSW:LI20:NW18:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:LI20:NW18:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-li20-nw18")
}

record(calcout, "ACSW:LI20:NW18:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:LI20:NW18:DISCONN.DISA")
  field(INPB, "ACSW:LI20:NW18:DISCONN.DISV")
  field(INPC, "ACSW:LI20:NW18:GETSTATUS.DISA")
  field(INPD, "ACSW:LI20:NW18:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:LI20:NW18:CONNSTA PP")
}

record(bi, "ACSW:LI20:NW18:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:LI20:NW18:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:LI20:NW18:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:LI20:NW18:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:LI20:NW18:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:LI20:NW18:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:LI20:NW18:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:LI20:NW18:UPTIMEHOUR") {
  field(FLNK, "ACSW:LI20:NW18:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:LI20:NW18:UPTIMEDAY") {
  field(FLNK, "ACSW:LI20:NW18:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:LI20:NW18:UPTIMEMINUTE") {
  field(FLNK, "ACSW:LI20:NW18:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:LI20:NW18:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW18:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW18:1POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW18:1POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW18:1POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW18:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW18:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW18:1POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW18:1POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW18:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW18:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW18:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW18:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-li20-nw18")
}

record(bo, "ACSW:LI20:NW18:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-li20-nw18")
}

record(bo, "ACSW:LI20:NW18:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-li20-nw18")
}

record(stringin, "ACSW:LI20:NW18:1NAMESET") {
  field(FLNK, "ACSW:LI20:NW18:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW18:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-li20-nw18")
  field(DOL, "ACSW:LI20:NW18:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW18:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-li20-nw18")
  field(FLNK, "ACSW:LI20:NW18:GETINIT")
}

record(bo, "ACSW:LI20:NW18:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-li20-nw18")
  field(FLNK, "ACSW:LI20:NW18:GETINIT")
}

record(stringin, "ACSW:LI20:NW18:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW18:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW18:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW18:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW18:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW18:1INITSTATE")
}

record(mbbi, "ACSW:LI20:NW18:1INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW18:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW18:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW18:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW18:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW18:2POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW18:2POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW18:2POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW18:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW18:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW18:2POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW18:2POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW18:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW18:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW18:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW18:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-li20-nw18")
}

record(bo, "ACSW:LI20:NW18:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-li20-nw18")
}

record(bo, "ACSW:LI20:NW18:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-li20-nw18")
}

record(stringin, "ACSW:LI20:NW18:2NAMESET") {
  field(FLNK, "ACSW:LI20:NW18:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW18:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-li20-nw18")
  field(DOL, "ACSW:LI20:NW18:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW18:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-li20-nw18")
  field(FLNK, "ACSW:LI20:NW18:GETINIT")
}

record(bo, "ACSW:LI20:NW18:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-li20-nw18")
  field(FLNK, "ACSW:LI20:NW18:GETINIT")
}

record(stringin, "ACSW:LI20:NW18:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW18:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW18:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW18:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW18:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW18:2INITSTATE")
}

record(mbbi, "ACSW:LI20:NW18:2INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW18:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW18:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW18:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW18:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW18:3POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW18:3POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW18:3POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW18:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW18:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW18:3POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW18:3POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW18:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW18:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW18:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW18:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-li20-nw18")
}

record(bo, "ACSW:LI20:NW18:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-li20-nw18")
}

record(bo, "ACSW:LI20:NW18:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-li20-nw18")
}

record(stringin, "ACSW:LI20:NW18:3NAMESET") {
  field(FLNK, "ACSW:LI20:NW18:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW18:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-li20-nw18")
  field(DOL, "ACSW:LI20:NW18:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW18:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-li20-nw18")
  field(FLNK, "ACSW:LI20:NW18:GETINIT")
}

record(bo, "ACSW:LI20:NW18:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-li20-nw18")
  field(FLNK, "ACSW:LI20:NW18:GETINIT")
}

record(stringin, "ACSW:LI20:NW18:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW18:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW18:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW18:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW18:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW18:3INITSTATE")
}

record(mbbi, "ACSW:LI20:NW18:3INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW18:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW18:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW18:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW18:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW18:4POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW18:4POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW18:4POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW18:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW18:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW18:4POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW18:4POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW18:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW18:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW18:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW18:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-li20-nw18")
}

record(bo, "ACSW:LI20:NW18:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-li20-nw18")
}

record(bo, "ACSW:LI20:NW18:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-li20-nw18")
}

record(stringin, "ACSW:LI20:NW18:4NAMESET") {
  field(FLNK, "ACSW:LI20:NW18:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW18:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-li20-nw18")
  field(DOL, "ACSW:LI20:NW18:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW18:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-li20-nw18")
  field(FLNK, "ACSW:LI20:NW18:GETINIT")
}

record(bo, "ACSW:LI20:NW18:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-li20-nw18")
  field(FLNK, "ACSW:LI20:NW18:GETINIT")
}

record(stringin, "ACSW:LI20:NW18:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW18:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW18:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW18:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW18:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW18:4INITSTATE")
}

record(mbbi, "ACSW:LI20:NW18:4INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW18:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW18:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW18:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW18:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW18:5POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW18:5POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW18:5POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW18:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW18:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW18:5POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW18:5POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW18:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW18:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW18:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW18:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-li20-nw18")
}

record(bo, "ACSW:LI20:NW18:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-li20-nw18")
}

record(bo, "ACSW:LI20:NW18:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-li20-nw18")
}

record(stringin, "ACSW:LI20:NW18:5NAMESET") {
  field(FLNK, "ACSW:LI20:NW18:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW18:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-li20-nw18")
  field(DOL, "ACSW:LI20:NW18:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW18:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-li20-nw18")
  field(FLNK, "ACSW:LI20:NW18:GETINIT")
}

record(bo, "ACSW:LI20:NW18:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-li20-nw18")
  field(FLNK, "ACSW:LI20:NW18:GETINIT")
}

record(stringin, "ACSW:LI20:NW18:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW18:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW18:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW18:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW18:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW18:5INITSTATE")
}

record(mbbi, "ACSW:LI20:NW18:5INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW18:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW18:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW18:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW18:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW18:6POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW18:6POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW18:6POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW18:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW18:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW18:6POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW18:6POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW18:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW18:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW18:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW18:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-li20-nw18")
}

record(bo, "ACSW:LI20:NW18:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-li20-nw18")
}

record(bo, "ACSW:LI20:NW18:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-li20-nw18")
}

record(stringin, "ACSW:LI20:NW18:6NAMESET") {
  field(FLNK, "ACSW:LI20:NW18:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW18:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-li20-nw18")
  field(DOL, "ACSW:LI20:NW18:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW18:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-li20-nw18")
  field(FLNK, "ACSW:LI20:NW18:GETINIT")
}

record(bo, "ACSW:LI20:NW18:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-li20-nw18")
  field(FLNK, "ACSW:LI20:NW18:GETINIT")
}

record(stringin, "ACSW:LI20:NW18:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW18:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW18:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW18:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW18:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW18:6INITSTATE")
}

record(mbbi, "ACSW:LI20:NW18:6INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW18:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW18:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW18:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW18:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW18:7POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW18:7POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW18:7POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW18:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW18:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW18:7POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW18:7POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW18:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW18:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW18:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW18:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-li20-nw18")
}

record(bo, "ACSW:LI20:NW18:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-li20-nw18")
}

record(bo, "ACSW:LI20:NW18:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-li20-nw18")
}

record(stringin, "ACSW:LI20:NW18:7NAMESET") {
  field(FLNK, "ACSW:LI20:NW18:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW18:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-li20-nw18")
  field(DOL, "ACSW:LI20:NW18:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW18:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-li20-nw18")
  field(FLNK, "ACSW:LI20:NW18:GETINIT")
}

record(bo, "ACSW:LI20:NW18:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-li20-nw18")
  field(FLNK, "ACSW:LI20:NW18:GETINIT")
}

record(stringin, "ACSW:LI20:NW18:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW18:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW18:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW18:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW18:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW18:7INITSTATE")
}

record(mbbi, "ACSW:LI20:NW18:7INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW18:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW18:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW18:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW18:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW18:8POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW18:8POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW18:8POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW18:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW18:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW18:8POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW18:8POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW18:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW18:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW18:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW18:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-li20-nw18")
}

record(bo, "ACSW:LI20:NW18:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-li20-nw18")
}

record(bo, "ACSW:LI20:NW18:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-li20-nw18")
}

record(stringin, "ACSW:LI20:NW18:8NAMESET") {
  field(FLNK, "ACSW:LI20:NW18:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW18:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-li20-nw18")
  field(DOL, "ACSW:LI20:NW18:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW18:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-li20-nw18")
  field(FLNK, "ACSW:LI20:NW18:GETINIT")
}

record(bo, "ACSW:LI20:NW18:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-li20-nw18")
  field(FLNK, "ACSW:LI20:NW18:GETINIT")
}

record(stringin, "ACSW:LI20:NW18:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW18:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW18:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW18:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW18:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW18:8INITSTATE")
}

record(mbbi, "ACSW:LI20:NW18:8INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW18:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW18:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW19:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:LI20:NW19) acsw-li20-nw19")
  field(FLNK, "ACSW:LI20:NW19:GETINFO")
}

record(stringin, "ACSW:LI20:NW19:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:LI20:NW19) acsw-li20-nw19")
  field(FLNK, "ACSW:LI20:NW19:GETINIT")
}

record(stringin, "ACSW:LI20:NW19:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:LI20:NW19:NETFWVERSION")
  field(SDIS, "ACSW:LI20:NW19:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:LI20:NW19:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:LI20:NW19:SITEID")
  field(SDIS, "ACSW:LI20:NW19:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:LI20:NW19:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:LI20:NW19:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:LI20:NW19:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState8(ACSW:LI20:NW19) acsw-li20-nw19")
}

record(stringin, "ACSW:LI20:NW19:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState8(ACSW:LI20:NW19) acsw-li20-nw19")
}

record(ai, "ACSW:LI20:NW19:TYPE") {
  field(DESC, "APC 8 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "10")
}

record(stringin, "ACSW:LI20:NW19:LOC") {
  field(PINI, "YES")
  field(VAL, "FKG20-0138")
  field(SDIS, "ACSW:LI20:NW19:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:LI20:NW19:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-li20-nw19")
}

record(calcout, "ACSW:LI20:NW19:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:LI20:NW19:DISCONN.DISA")
  field(INPB, "ACSW:LI20:NW19:DISCONN.DISV")
  field(INPC, "ACSW:LI20:NW19:GETSTATUS.DISA")
  field(INPD, "ACSW:LI20:NW19:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:LI20:NW19:CONNSTA PP")
}

record(bi, "ACSW:LI20:NW19:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:LI20:NW19:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:LI20:NW19:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:LI20:NW19:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:LI20:NW19:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:LI20:NW19:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:LI20:NW19:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:LI20:NW19:UPTIMEHOUR") {
  field(FLNK, "ACSW:LI20:NW19:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:LI20:NW19:UPTIMEDAY") {
  field(FLNK, "ACSW:LI20:NW19:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:LI20:NW19:UPTIMEMINUTE") {
  field(FLNK, "ACSW:LI20:NW19:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:LI20:NW19:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW19:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW19:1POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW19:1POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW19:1POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW19:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW19:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW19:1POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW19:1POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW19:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW19:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW19:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW19:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-li20-nw19")
}

record(bo, "ACSW:LI20:NW19:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-li20-nw19")
}

record(bo, "ACSW:LI20:NW19:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-li20-nw19")
}

record(stringin, "ACSW:LI20:NW19:1NAMESET") {
  field(FLNK, "ACSW:LI20:NW19:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW19:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-li20-nw19")
  field(DOL, "ACSW:LI20:NW19:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW19:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-li20-nw19")
  field(FLNK, "ACSW:LI20:NW19:GETINIT")
}

record(bo, "ACSW:LI20:NW19:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-li20-nw19")
  field(FLNK, "ACSW:LI20:NW19:GETINIT")
}

record(stringin, "ACSW:LI20:NW19:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW19:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW19:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW19:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW19:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW19:1INITSTATE")
}

record(mbbi, "ACSW:LI20:NW19:1INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW19:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW19:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW19:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW19:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW19:2POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW19:2POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW19:2POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW19:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW19:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW19:2POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW19:2POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW19:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW19:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW19:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW19:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-li20-nw19")
}

record(bo, "ACSW:LI20:NW19:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-li20-nw19")
}

record(bo, "ACSW:LI20:NW19:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-li20-nw19")
}

record(stringin, "ACSW:LI20:NW19:2NAMESET") {
  field(FLNK, "ACSW:LI20:NW19:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW19:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-li20-nw19")
  field(DOL, "ACSW:LI20:NW19:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW19:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-li20-nw19")
  field(FLNK, "ACSW:LI20:NW19:GETINIT")
}

record(bo, "ACSW:LI20:NW19:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-li20-nw19")
  field(FLNK, "ACSW:LI20:NW19:GETINIT")
}

record(stringin, "ACSW:LI20:NW19:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW19:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW19:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW19:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW19:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW19:2INITSTATE")
}

record(mbbi, "ACSW:LI20:NW19:2INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW19:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW19:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW19:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW19:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW19:3POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW19:3POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW19:3POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW19:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW19:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW19:3POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW19:3POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW19:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW19:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW19:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW19:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-li20-nw19")
}

record(bo, "ACSW:LI20:NW19:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-li20-nw19")
}

record(bo, "ACSW:LI20:NW19:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-li20-nw19")
}

record(stringin, "ACSW:LI20:NW19:3NAMESET") {
  field(FLNK, "ACSW:LI20:NW19:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW19:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-li20-nw19")
  field(DOL, "ACSW:LI20:NW19:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW19:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-li20-nw19")
  field(FLNK, "ACSW:LI20:NW19:GETINIT")
}

record(bo, "ACSW:LI20:NW19:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-li20-nw19")
  field(FLNK, "ACSW:LI20:NW19:GETINIT")
}

record(stringin, "ACSW:LI20:NW19:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW19:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW19:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW19:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW19:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW19:3INITSTATE")
}

record(mbbi, "ACSW:LI20:NW19:3INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW19:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW19:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW19:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW19:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW19:4POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW19:4POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW19:4POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW19:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW19:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW19:4POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW19:4POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW19:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW19:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW19:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW19:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-li20-nw19")
}

record(bo, "ACSW:LI20:NW19:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-li20-nw19")
}

record(bo, "ACSW:LI20:NW19:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-li20-nw19")
}

record(stringin, "ACSW:LI20:NW19:4NAMESET") {
  field(FLNK, "ACSW:LI20:NW19:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW19:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-li20-nw19")
  field(DOL, "ACSW:LI20:NW19:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW19:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-li20-nw19")
  field(FLNK, "ACSW:LI20:NW19:GETINIT")
}

record(bo, "ACSW:LI20:NW19:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-li20-nw19")
  field(FLNK, "ACSW:LI20:NW19:GETINIT")
}

record(stringin, "ACSW:LI20:NW19:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW19:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW19:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW19:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW19:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW19:4INITSTATE")
}

record(mbbi, "ACSW:LI20:NW19:4INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW19:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW19:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW19:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW19:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW19:5POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW19:5POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW19:5POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW19:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW19:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW19:5POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW19:5POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW19:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW19:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW19:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW19:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-li20-nw19")
}

record(bo, "ACSW:LI20:NW19:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-li20-nw19")
}

record(bo, "ACSW:LI20:NW19:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-li20-nw19")
}

record(stringin, "ACSW:LI20:NW19:5NAMESET") {
  field(FLNK, "ACSW:LI20:NW19:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW19:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-li20-nw19")
  field(DOL, "ACSW:LI20:NW19:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW19:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-li20-nw19")
  field(FLNK, "ACSW:LI20:NW19:GETINIT")
}

record(bo, "ACSW:LI20:NW19:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-li20-nw19")
  field(FLNK, "ACSW:LI20:NW19:GETINIT")
}

record(stringin, "ACSW:LI20:NW19:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW19:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW19:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW19:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW19:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW19:5INITSTATE")
}

record(mbbi, "ACSW:LI20:NW19:5INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW19:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW19:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW19:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW19:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW19:6POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW19:6POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW19:6POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW19:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW19:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW19:6POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW19:6POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW19:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW19:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW19:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW19:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-li20-nw19")
}

record(bo, "ACSW:LI20:NW19:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-li20-nw19")
}

record(bo, "ACSW:LI20:NW19:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-li20-nw19")
}

record(stringin, "ACSW:LI20:NW19:6NAMESET") {
  field(FLNK, "ACSW:LI20:NW19:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW19:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-li20-nw19")
  field(DOL, "ACSW:LI20:NW19:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW19:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-li20-nw19")
  field(FLNK, "ACSW:LI20:NW19:GETINIT")
}

record(bo, "ACSW:LI20:NW19:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-li20-nw19")
  field(FLNK, "ACSW:LI20:NW19:GETINIT")
}

record(stringin, "ACSW:LI20:NW19:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW19:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW19:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW19:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW19:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW19:6INITSTATE")
}

record(mbbi, "ACSW:LI20:NW19:6INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW19:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW19:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW19:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW19:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW19:7POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW19:7POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW19:7POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW19:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW19:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW19:7POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW19:7POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW19:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW19:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW19:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW19:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-li20-nw19")
}

record(bo, "ACSW:LI20:NW19:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-li20-nw19")
}

record(bo, "ACSW:LI20:NW19:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-li20-nw19")
}

record(stringin, "ACSW:LI20:NW19:7NAMESET") {
  field(FLNK, "ACSW:LI20:NW19:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW19:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-li20-nw19")
  field(DOL, "ACSW:LI20:NW19:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW19:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-li20-nw19")
  field(FLNK, "ACSW:LI20:NW19:GETINIT")
}

record(bo, "ACSW:LI20:NW19:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-li20-nw19")
  field(FLNK, "ACSW:LI20:NW19:GETINIT")
}

record(stringin, "ACSW:LI20:NW19:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW19:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW19:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW19:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW19:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW19:7INITSTATE")
}

record(mbbi, "ACSW:LI20:NW19:7INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW19:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW19:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW19:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW19:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW19:8POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW19:8POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW19:8POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW19:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW19:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW19:8POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW19:8POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW19:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW19:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW19:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW19:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-li20-nw19")
}

record(bo, "ACSW:LI20:NW19:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-li20-nw19")
}

record(bo, "ACSW:LI20:NW19:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-li20-nw19")
}

record(stringin, "ACSW:LI20:NW19:8NAMESET") {
  field(FLNK, "ACSW:LI20:NW19:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW19:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-li20-nw19")
  field(DOL, "ACSW:LI20:NW19:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW19:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-li20-nw19")
  field(FLNK, "ACSW:LI20:NW19:GETINIT")
}

record(bo, "ACSW:LI20:NW19:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-li20-nw19")
  field(FLNK, "ACSW:LI20:NW19:GETINIT")
}

record(stringin, "ACSW:LI20:NW19:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW19:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW19:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW19:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW19:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW19:8INITSTATE")
}

record(mbbi, "ACSW:LI20:NW19:8INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW19:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW19:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW07:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:LI20:NW07) acsw-li20-nw07")
  field(FLNK, "ACSW:LI20:NW07:GETINFO")
}

record(stringin, "ACSW:LI20:NW07:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:LI20:NW07) acsw-li20-nw07")
  field(FLNK, "ACSW:LI20:NW07:GETINIT")
}

record(stringin, "ACSW:LI20:NW07:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:LI20:NW07:NETFWVERSION")
  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:LI20:NW07:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:LI20:NW07:SITEID")
  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:LI20:NW07:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:LI20:NW07:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState16(ACSW:LI20:NW07) acsw-li20-nw07")
}

record(stringin, "ACSW:LI20:NW07:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState16(ACSW:LI20:NW07) acsw-li20-nw07")
}

record(ai, "ACSW:LI20:NW07:TYPE") {
  field(DESC, "APC 16 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "18")
}

record(stringin, "ACSW:LI20:NW07:LOC") {
  field(PINI, "YES")
  field(VAL, "FKG20-3002")
  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:LI20:NW07:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-li20-nw07")
}

record(calcout, "ACSW:LI20:NW07:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:LI20:NW07:DISCONN.DISA")
  field(INPB, "ACSW:LI20:NW07:DISCONN.DISV")
  field(INPC, "ACSW:LI20:NW07:GETSTATUS.DISA")
  field(INPD, "ACSW:LI20:NW07:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:LI20:NW07:CONNSTA PP")
}

record(bi, "ACSW:LI20:NW07:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:LI20:NW07:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:LI20:NW07:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:LI20:NW07:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:LI20:NW07:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:LI20:NW07:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:LI20:NW07:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:LI20:NW07:UPTIMEHOUR") {
  field(FLNK, "ACSW:LI20:NW07:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:LI20:NW07:UPTIMEDAY") {
  field(FLNK, "ACSW:LI20:NW07:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:LI20:NW07:UPTIMEMINUTE") {
  field(FLNK, "ACSW:LI20:NW07:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:LI20:NW07:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW07:1POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW07:1POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW07:1POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW07:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW07:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW07:1POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW07:1POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW07:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW07:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-li20-nw07")
}

record(bo, "ACSW:LI20:NW07:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-li20-nw07")
}

record(bo, "ACSW:LI20:NW07:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-li20-nw07")
}

record(stringin, "ACSW:LI20:NW07:1NAMESET") {
  field(FLNK, "ACSW:LI20:NW07:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW07:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-li20-nw07")
  field(DOL, "ACSW:LI20:NW07:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW07:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-li20-nw07")
  field(FLNK, "ACSW:LI20:NW07:GETINIT")
}

record(bo, "ACSW:LI20:NW07:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-li20-nw07")
  field(FLNK, "ACSW:LI20:NW07:GETINIT")
}

record(stringin, "ACSW:LI20:NW07:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW07:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW07:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW07:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW07:1INITSTATE")
}

record(mbbi, "ACSW:LI20:NW07:1INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW07:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW07:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW07:2POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW07:2POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW07:2POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW07:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW07:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW07:2POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW07:2POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW07:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW07:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-li20-nw07")
}

record(bo, "ACSW:LI20:NW07:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-li20-nw07")
}

record(bo, "ACSW:LI20:NW07:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-li20-nw07")
}

record(stringin, "ACSW:LI20:NW07:2NAMESET") {
  field(FLNK, "ACSW:LI20:NW07:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW07:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-li20-nw07")
  field(DOL, "ACSW:LI20:NW07:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW07:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-li20-nw07")
  field(FLNK, "ACSW:LI20:NW07:GETINIT")
}

record(bo, "ACSW:LI20:NW07:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-li20-nw07")
  field(FLNK, "ACSW:LI20:NW07:GETINIT")
}

record(stringin, "ACSW:LI20:NW07:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW07:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW07:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW07:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW07:2INITSTATE")
}

record(mbbi, "ACSW:LI20:NW07:2INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW07:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW07:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW07:3POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW07:3POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW07:3POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW07:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW07:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW07:3POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW07:3POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW07:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW07:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-li20-nw07")
}

record(bo, "ACSW:LI20:NW07:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-li20-nw07")
}

record(bo, "ACSW:LI20:NW07:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-li20-nw07")
}

record(stringin, "ACSW:LI20:NW07:3NAMESET") {
  field(FLNK, "ACSW:LI20:NW07:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW07:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-li20-nw07")
  field(DOL, "ACSW:LI20:NW07:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW07:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-li20-nw07")
  field(FLNK, "ACSW:LI20:NW07:GETINIT")
}

record(bo, "ACSW:LI20:NW07:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-li20-nw07")
  field(FLNK, "ACSW:LI20:NW07:GETINIT")
}

record(stringin, "ACSW:LI20:NW07:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW07:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW07:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW07:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW07:3INITSTATE")
}

record(mbbi, "ACSW:LI20:NW07:3INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW07:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW07:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW07:4POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW07:4POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW07:4POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW07:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW07:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW07:4POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW07:4POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW07:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW07:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-li20-nw07")
}

record(bo, "ACSW:LI20:NW07:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-li20-nw07")
}

record(bo, "ACSW:LI20:NW07:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-li20-nw07")
}

record(stringin, "ACSW:LI20:NW07:4NAMESET") {
  field(FLNK, "ACSW:LI20:NW07:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW07:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-li20-nw07")
  field(DOL, "ACSW:LI20:NW07:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW07:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-li20-nw07")
  field(FLNK, "ACSW:LI20:NW07:GETINIT")
}

record(bo, "ACSW:LI20:NW07:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-li20-nw07")
  field(FLNK, "ACSW:LI20:NW07:GETINIT")
}

record(stringin, "ACSW:LI20:NW07:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW07:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW07:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW07:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW07:4INITSTATE")
}

record(mbbi, "ACSW:LI20:NW07:4INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW07:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW07:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW07:5POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW07:5POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW07:5POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW07:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW07:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW07:5POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW07:5POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW07:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW07:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-li20-nw07")
}

record(bo, "ACSW:LI20:NW07:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-li20-nw07")
}

record(bo, "ACSW:LI20:NW07:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-li20-nw07")
}

record(stringin, "ACSW:LI20:NW07:5NAMESET") {
  field(FLNK, "ACSW:LI20:NW07:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW07:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-li20-nw07")
  field(DOL, "ACSW:LI20:NW07:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW07:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-li20-nw07")
  field(FLNK, "ACSW:LI20:NW07:GETINIT")
}

record(bo, "ACSW:LI20:NW07:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-li20-nw07")
  field(FLNK, "ACSW:LI20:NW07:GETINIT")
}

record(stringin, "ACSW:LI20:NW07:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW07:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW07:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW07:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW07:5INITSTATE")
}

record(mbbi, "ACSW:LI20:NW07:5INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW07:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW07:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW07:6POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW07:6POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW07:6POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW07:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW07:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW07:6POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW07:6POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW07:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW07:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-li20-nw07")
}

record(bo, "ACSW:LI20:NW07:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-li20-nw07")
}

record(bo, "ACSW:LI20:NW07:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-li20-nw07")
}

record(stringin, "ACSW:LI20:NW07:6NAMESET") {
  field(FLNK, "ACSW:LI20:NW07:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW07:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-li20-nw07")
  field(DOL, "ACSW:LI20:NW07:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW07:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-li20-nw07")
  field(FLNK, "ACSW:LI20:NW07:GETINIT")
}

record(bo, "ACSW:LI20:NW07:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-li20-nw07")
  field(FLNK, "ACSW:LI20:NW07:GETINIT")
}

record(stringin, "ACSW:LI20:NW07:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW07:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW07:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW07:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW07:6INITSTATE")
}

record(mbbi, "ACSW:LI20:NW07:6INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW07:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW07:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW07:7POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW07:7POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW07:7POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW07:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW07:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW07:7POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW07:7POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW07:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW07:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-li20-nw07")
}

record(bo, "ACSW:LI20:NW07:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-li20-nw07")
}

record(bo, "ACSW:LI20:NW07:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-li20-nw07")
}

record(stringin, "ACSW:LI20:NW07:7NAMESET") {
  field(FLNK, "ACSW:LI20:NW07:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW07:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-li20-nw07")
  field(DOL, "ACSW:LI20:NW07:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW07:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-li20-nw07")
  field(FLNK, "ACSW:LI20:NW07:GETINIT")
}

record(bo, "ACSW:LI20:NW07:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-li20-nw07")
  field(FLNK, "ACSW:LI20:NW07:GETINIT")
}

record(stringin, "ACSW:LI20:NW07:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW07:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW07:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW07:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW07:7INITSTATE")
}

record(mbbi, "ACSW:LI20:NW07:7INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW07:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW07:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW07:8POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW07:8POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW07:8POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW07:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW07:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW07:8POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW07:8POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW07:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW07:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-li20-nw07")
}

record(bo, "ACSW:LI20:NW07:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-li20-nw07")
}

record(bo, "ACSW:LI20:NW07:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-li20-nw07")
}

record(stringin, "ACSW:LI20:NW07:8NAMESET") {
  field(FLNK, "ACSW:LI20:NW07:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW07:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-li20-nw07")
  field(DOL, "ACSW:LI20:NW07:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW07:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-li20-nw07")
  field(FLNK, "ACSW:LI20:NW07:GETINIT")
}

record(bo, "ACSW:LI20:NW07:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-li20-nw07")
  field(FLNK, "ACSW:LI20:NW07:GETINIT")
}

record(stringin, "ACSW:LI20:NW07:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW07:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW07:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW07:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW07:8INITSTATE")
}

record(mbbi, "ACSW:LI20:NW07:8INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW07:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW07:9NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW07:9POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW07:9POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW07:9POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW07:9POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW07:9POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW07:9POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW07:9POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW07:9POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW07:9POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(9) acsw-li20-nw07")
}

record(bo, "ACSW:LI20:NW07:9POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(9) acsw-li20-nw07")
}

record(bo, "ACSW:LI20:NW07:9HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(9) acsw-li20-nw07")
}

record(stringin, "ACSW:LI20:NW07:9NAMESET") {
  field(FLNK, "ACSW:LI20:NW07:9NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW07:9NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(9) acsw-li20-nw07")
  field(DOL, "ACSW:LI20:NW07:9NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW07:9SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(9) acsw-li20-nw07")
  field(FLNK, "ACSW:LI20:NW07:GETINIT")
}

record(bo, "ACSW:LI20:NW07:9SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(9) acsw-li20-nw07")
  field(FLNK, "ACSW:LI20:NW07:GETINIT")
}

record(stringin, "ACSW:LI20:NW07:9INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW07:9INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW07:9INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW07:9INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW07:9INITSTATE")
}

record(mbbi, "ACSW:LI20:NW07:9INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW07:9INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW07:10NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW07:10POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW07:10POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW07:10POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW07:10POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW07:10POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW07:10POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW07:10POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW07:10POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW07:10POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(10) acsw-li20-nw07")
}

record(bo, "ACSW:LI20:NW07:10POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(10) acsw-li20-nw07")
}

record(bo, "ACSW:LI20:NW07:10HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(10) acsw-li20-nw07")
}

record(stringin, "ACSW:LI20:NW07:10NAMESET") {
  field(FLNK, "ACSW:LI20:NW07:10NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW07:10NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(10) acsw-li20-nw07")
  field(DOL, "ACSW:LI20:NW07:10NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW07:10SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(10) acsw-li20-nw07")
  field(FLNK, "ACSW:LI20:NW07:GETINIT")
}

record(bo, "ACSW:LI20:NW07:10SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(10) acsw-li20-nw07")
  field(FLNK, "ACSW:LI20:NW07:GETINIT")
}

record(stringin, "ACSW:LI20:NW07:10INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW07:10INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW07:10INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW07:10INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW07:10INITSTATE")
}

record(mbbi, "ACSW:LI20:NW07:10INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW07:10INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW07:11NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW07:11POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW07:11POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW07:11POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW07:11POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW07:11POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW07:11POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW07:11POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW07:11POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW07:11POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(11) acsw-li20-nw07")
}

record(bo, "ACSW:LI20:NW07:11POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(11) acsw-li20-nw07")
}

record(bo, "ACSW:LI20:NW07:11HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(11) acsw-li20-nw07")
}

record(stringin, "ACSW:LI20:NW07:11NAMESET") {
  field(FLNK, "ACSW:LI20:NW07:11NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW07:11NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(11) acsw-li20-nw07")
  field(DOL, "ACSW:LI20:NW07:11NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW07:11SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(11) acsw-li20-nw07")
  field(FLNK, "ACSW:LI20:NW07:GETINIT")
}

record(bo, "ACSW:LI20:NW07:11SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(11) acsw-li20-nw07")
  field(FLNK, "ACSW:LI20:NW07:GETINIT")
}

record(stringin, "ACSW:LI20:NW07:11INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW07:11INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW07:11INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW07:11INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW07:11INITSTATE")
}

record(mbbi, "ACSW:LI20:NW07:11INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW07:11INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW07:12NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW07:12POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW07:12POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW07:12POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW07:12POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW07:12POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW07:12POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW07:12POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW07:12POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW07:12POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(12) acsw-li20-nw07")
}

record(bo, "ACSW:LI20:NW07:12POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(12) acsw-li20-nw07")
}

record(bo, "ACSW:LI20:NW07:12HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(12) acsw-li20-nw07")
}

record(stringin, "ACSW:LI20:NW07:12NAMESET") {
  field(FLNK, "ACSW:LI20:NW07:12NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW07:12NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(12) acsw-li20-nw07")
  field(DOL, "ACSW:LI20:NW07:12NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW07:12SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(12) acsw-li20-nw07")
  field(FLNK, "ACSW:LI20:NW07:GETINIT")
}

record(bo, "ACSW:LI20:NW07:12SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(12) acsw-li20-nw07")
  field(FLNK, "ACSW:LI20:NW07:GETINIT")
}

record(stringin, "ACSW:LI20:NW07:12INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW07:12INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW07:12INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW07:12INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW07:12INITSTATE")
}

record(mbbi, "ACSW:LI20:NW07:12INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW07:12INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW07:13NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW07:13POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW07:13POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW07:13POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW07:13POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW07:13POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW07:13POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW07:13POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW07:13POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW07:13POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(13) acsw-li20-nw07")
}

record(bo, "ACSW:LI20:NW07:13POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(13) acsw-li20-nw07")
}

record(bo, "ACSW:LI20:NW07:13HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(13) acsw-li20-nw07")
}

record(stringin, "ACSW:LI20:NW07:13NAMESET") {
  field(FLNK, "ACSW:LI20:NW07:13NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW07:13NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(13) acsw-li20-nw07")
  field(DOL, "ACSW:LI20:NW07:13NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW07:13SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(13) acsw-li20-nw07")
  field(FLNK, "ACSW:LI20:NW07:GETINIT")
}

record(bo, "ACSW:LI20:NW07:13SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(13) acsw-li20-nw07")
  field(FLNK, "ACSW:LI20:NW07:GETINIT")
}

record(stringin, "ACSW:LI20:NW07:13INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW07:13INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW07:13INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW07:13INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW07:13INITSTATE")
}

record(mbbi, "ACSW:LI20:NW07:13INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW07:13INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW07:14NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW07:14POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW07:14POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW07:14POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW07:14POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW07:14POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW07:14POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW07:14POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW07:14POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW07:14POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(14) acsw-li20-nw07")
}

record(bo, "ACSW:LI20:NW07:14POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(14) acsw-li20-nw07")
}

record(bo, "ACSW:LI20:NW07:14HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(14) acsw-li20-nw07")
}

record(stringin, "ACSW:LI20:NW07:14NAMESET") {
  field(FLNK, "ACSW:LI20:NW07:14NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW07:14NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(14) acsw-li20-nw07")
  field(DOL, "ACSW:LI20:NW07:14NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW07:14SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(14) acsw-li20-nw07")
  field(FLNK, "ACSW:LI20:NW07:GETINIT")
}

record(bo, "ACSW:LI20:NW07:14SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(14) acsw-li20-nw07")
  field(FLNK, "ACSW:LI20:NW07:GETINIT")
}

record(stringin, "ACSW:LI20:NW07:14INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW07:14INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW07:14INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW07:14INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW07:14INITSTATE")
}

record(mbbi, "ACSW:LI20:NW07:14INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW07:14INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW07:15NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW07:15POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW07:15POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW07:15POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW07:15POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW07:15POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW07:15POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW07:15POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW07:15POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW07:15POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(15) acsw-li20-nw07")
}

record(bo, "ACSW:LI20:NW07:15POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(15) acsw-li20-nw07")
}

record(bo, "ACSW:LI20:NW07:15HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(15) acsw-li20-nw07")
}

record(stringin, "ACSW:LI20:NW07:15NAMESET") {
  field(FLNK, "ACSW:LI20:NW07:15NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW07:15NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(15) acsw-li20-nw07")
  field(DOL, "ACSW:LI20:NW07:15NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW07:15SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(15) acsw-li20-nw07")
  field(FLNK, "ACSW:LI20:NW07:GETINIT")
}

record(bo, "ACSW:LI20:NW07:15SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(15) acsw-li20-nw07")
  field(FLNK, "ACSW:LI20:NW07:GETINIT")
}

record(stringin, "ACSW:LI20:NW07:15INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW07:15INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW07:15INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW07:15INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW07:15INITSTATE")
}

record(mbbi, "ACSW:LI20:NW07:15INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW07:15INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW07:16NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW07:16POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW07:16POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW07:16POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW07:16POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW07:16POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW07:16POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW07:16POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW07:16POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW07:16POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(16) acsw-li20-nw07")
}

record(bo, "ACSW:LI20:NW07:16POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(16) acsw-li20-nw07")
}

record(bo, "ACSW:LI20:NW07:16HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(16) acsw-li20-nw07")
}

record(stringin, "ACSW:LI20:NW07:16NAMESET") {
  field(FLNK, "ACSW:LI20:NW07:16NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW07:16NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(16) acsw-li20-nw07")
  field(DOL, "ACSW:LI20:NW07:16NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW07:16SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(16) acsw-li20-nw07")
  field(FLNK, "ACSW:LI20:NW07:GETINIT")
}

record(bo, "ACSW:LI20:NW07:16SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(16) acsw-li20-nw07")
  field(FLNK, "ACSW:LI20:NW07:GETINIT")
}

record(stringin, "ACSW:LI20:NW07:16INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW07:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW07:16INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW07:16INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW07:16INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW07:16INITSTATE")
}

record(mbbi, "ACSW:LI20:NW07:16INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW07:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW07:16INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW04:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:LI20:NW04) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINFO")
}

record(stringin, "ACSW:LI20:NW04:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:LI20:NW04) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(stringin, "ACSW:LI20:NW04:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:LI20:NW04:NETFWVERSION")
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:LI20:NW04:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:LI20:NW04:SITEID")
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:LI20:NW04:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:LI20:NW04:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState24(ACSW:LI20:NW04) acsw-li20-nw04")
}

record(stringin, "ACSW:LI20:NW04:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState24(ACSW:LI20:NW04) acsw-li20-nw04")
}

record(ai, "ACSW:LI20:NW04:TYPE") {
  field(DESC, "APC 24 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "17")
}

record(stringin, "ACSW:LI20:NW04:LOC") {
  field(PINI, "YES")
  field(VAL, "S20 Tunnel, THz table")
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:LI20:NW04:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-li20-nw04")
}

record(calcout, "ACSW:LI20:NW04:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:LI20:NW04:DISCONN.DISA")
  field(INPB, "ACSW:LI20:NW04:DISCONN.DISV")
  field(INPC, "ACSW:LI20:NW04:GETSTATUS.DISA")
  field(INPD, "ACSW:LI20:NW04:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:LI20:NW04:CONNSTA PP")
}

record(bi, "ACSW:LI20:NW04:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:LI20:NW04:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:LI20:NW04:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:LI20:NW04:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:LI20:NW04:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:LI20:NW04:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:LI20:NW04:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:LI20:NW04:UPTIMEHOUR") {
  field(FLNK, "ACSW:LI20:NW04:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:LI20:NW04:UPTIMEDAY") {
  field(FLNK, "ACSW:LI20:NW04:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:LI20:NW04:UPTIMEMINUTE") {
  field(FLNK, "ACSW:LI20:NW04:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:LI20:NW04:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:1POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW04:1POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW04:1POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW04:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW04:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW04:1POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW04:1POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW04:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-li20-nw04")
}

record(stringin, "ACSW:LI20:NW04:1NAMESET") {
  field(FLNK, "ACSW:LI20:NW04:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW04:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-li20-nw04")
  field(DOL, "ACSW:LI20:NW04:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW04:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(bo, "ACSW:LI20:NW04:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(stringin, "ACSW:LI20:NW04:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW04:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW04:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW04:1INITSTATE")
}

record(mbbi, "ACSW:LI20:NW04:1INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW04:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:2POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW04:2POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW04:2POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW04:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW04:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW04:2POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW04:2POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW04:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-li20-nw04")
}

record(stringin, "ACSW:LI20:NW04:2NAMESET") {
  field(FLNK, "ACSW:LI20:NW04:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW04:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-li20-nw04")
  field(DOL, "ACSW:LI20:NW04:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW04:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(bo, "ACSW:LI20:NW04:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(stringin, "ACSW:LI20:NW04:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW04:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW04:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW04:2INITSTATE")
}

record(mbbi, "ACSW:LI20:NW04:2INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW04:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:3POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW04:3POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW04:3POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW04:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW04:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW04:3POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW04:3POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW04:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-li20-nw04")
}

record(stringin, "ACSW:LI20:NW04:3NAMESET") {
  field(FLNK, "ACSW:LI20:NW04:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW04:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-li20-nw04")
  field(DOL, "ACSW:LI20:NW04:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW04:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(bo, "ACSW:LI20:NW04:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(stringin, "ACSW:LI20:NW04:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW04:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW04:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW04:3INITSTATE")
}

record(mbbi, "ACSW:LI20:NW04:3INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW04:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:4POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW04:4POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW04:4POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW04:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW04:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW04:4POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW04:4POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW04:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-li20-nw04")
}

record(stringin, "ACSW:LI20:NW04:4NAMESET") {
  field(FLNK, "ACSW:LI20:NW04:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW04:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-li20-nw04")
  field(DOL, "ACSW:LI20:NW04:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW04:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(bo, "ACSW:LI20:NW04:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(stringin, "ACSW:LI20:NW04:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW04:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW04:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW04:4INITSTATE")
}

record(mbbi, "ACSW:LI20:NW04:4INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW04:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:5POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW04:5POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW04:5POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW04:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW04:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW04:5POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW04:5POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW04:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-li20-nw04")
}

record(stringin, "ACSW:LI20:NW04:5NAMESET") {
  field(FLNK, "ACSW:LI20:NW04:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW04:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-li20-nw04")
  field(DOL, "ACSW:LI20:NW04:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW04:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(bo, "ACSW:LI20:NW04:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(stringin, "ACSW:LI20:NW04:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW04:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW04:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW04:5INITSTATE")
}

record(mbbi, "ACSW:LI20:NW04:5INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW04:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:6POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW04:6POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW04:6POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW04:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW04:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW04:6POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW04:6POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW04:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-li20-nw04")
}

record(stringin, "ACSW:LI20:NW04:6NAMESET") {
  field(FLNK, "ACSW:LI20:NW04:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW04:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-li20-nw04")
  field(DOL, "ACSW:LI20:NW04:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW04:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(bo, "ACSW:LI20:NW04:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(stringin, "ACSW:LI20:NW04:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW04:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW04:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW04:6INITSTATE")
}

record(mbbi, "ACSW:LI20:NW04:6INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW04:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:7POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW04:7POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW04:7POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW04:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW04:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW04:7POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW04:7POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW04:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-li20-nw04")
}

record(stringin, "ACSW:LI20:NW04:7NAMESET") {
  field(FLNK, "ACSW:LI20:NW04:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW04:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-li20-nw04")
  field(DOL, "ACSW:LI20:NW04:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW04:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(bo, "ACSW:LI20:NW04:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(stringin, "ACSW:LI20:NW04:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW04:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW04:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW04:7INITSTATE")
}

record(mbbi, "ACSW:LI20:NW04:7INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW04:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:8POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW04:8POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW04:8POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW04:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW04:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW04:8POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW04:8POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW04:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-li20-nw04")
}

record(stringin, "ACSW:LI20:NW04:8NAMESET") {
  field(FLNK, "ACSW:LI20:NW04:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW04:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-li20-nw04")
  field(DOL, "ACSW:LI20:NW04:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW04:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(bo, "ACSW:LI20:NW04:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(stringin, "ACSW:LI20:NW04:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW04:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW04:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW04:8INITSTATE")
}

record(mbbi, "ACSW:LI20:NW04:8INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW04:9NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:9POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW04:9POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW04:9POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW04:9POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW04:9POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW04:9POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW04:9POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:9POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW04:9POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(9) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:9POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(9) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:9HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(9) acsw-li20-nw04")
}

record(stringin, "ACSW:LI20:NW04:9NAMESET") {
  field(FLNK, "ACSW:LI20:NW04:9NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW04:9NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(9) acsw-li20-nw04")
  field(DOL, "ACSW:LI20:NW04:9NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW04:9SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(9) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(bo, "ACSW:LI20:NW04:9SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(9) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(stringin, "ACSW:LI20:NW04:9INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:9INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW04:9INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW04:9INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW04:9INITSTATE")
}

record(mbbi, "ACSW:LI20:NW04:9INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:9INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW04:10NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:10POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW04:10POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW04:10POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW04:10POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW04:10POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW04:10POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW04:10POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:10POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW04:10POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(10) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:10POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(10) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:10HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(10) acsw-li20-nw04")
}

record(stringin, "ACSW:LI20:NW04:10NAMESET") {
  field(FLNK, "ACSW:LI20:NW04:10NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW04:10NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(10) acsw-li20-nw04")
  field(DOL, "ACSW:LI20:NW04:10NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW04:10SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(10) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(bo, "ACSW:LI20:NW04:10SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(10) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(stringin, "ACSW:LI20:NW04:10INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:10INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW04:10INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW04:10INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW04:10INITSTATE")
}

record(mbbi, "ACSW:LI20:NW04:10INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:10INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW04:11NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:11POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW04:11POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW04:11POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW04:11POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW04:11POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW04:11POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW04:11POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:11POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW04:11POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(11) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:11POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(11) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:11HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(11) acsw-li20-nw04")
}

record(stringin, "ACSW:LI20:NW04:11NAMESET") {
  field(FLNK, "ACSW:LI20:NW04:11NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW04:11NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(11) acsw-li20-nw04")
  field(DOL, "ACSW:LI20:NW04:11NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW04:11SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(11) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(bo, "ACSW:LI20:NW04:11SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(11) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(stringin, "ACSW:LI20:NW04:11INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:11INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW04:11INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW04:11INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW04:11INITSTATE")
}

record(mbbi, "ACSW:LI20:NW04:11INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:11INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW04:12NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:12POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW04:12POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW04:12POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW04:12POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW04:12POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW04:12POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW04:12POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:12POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW04:12POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(12) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:12POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(12) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:12HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(12) acsw-li20-nw04")
}

record(stringin, "ACSW:LI20:NW04:12NAMESET") {
  field(FLNK, "ACSW:LI20:NW04:12NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW04:12NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(12) acsw-li20-nw04")
  field(DOL, "ACSW:LI20:NW04:12NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW04:12SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(12) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(bo, "ACSW:LI20:NW04:12SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(12) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(stringin, "ACSW:LI20:NW04:12INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:12INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW04:12INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW04:12INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW04:12INITSTATE")
}

record(mbbi, "ACSW:LI20:NW04:12INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:12INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW04:13NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:13POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW04:13POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW04:13POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW04:13POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW04:13POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW04:13POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW04:13POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:13POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW04:13POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(13) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:13POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(13) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:13HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(13) acsw-li20-nw04")
}

record(stringin, "ACSW:LI20:NW04:13NAMESET") {
  field(FLNK, "ACSW:LI20:NW04:13NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW04:13NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(13) acsw-li20-nw04")
  field(DOL, "ACSW:LI20:NW04:13NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW04:13SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(13) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(bo, "ACSW:LI20:NW04:13SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(13) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(stringin, "ACSW:LI20:NW04:13INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:13INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW04:13INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW04:13INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW04:13INITSTATE")
}

record(mbbi, "ACSW:LI20:NW04:13INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:13INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW04:14NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:14POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW04:14POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW04:14POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW04:14POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW04:14POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW04:14POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW04:14POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:14POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW04:14POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(14) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:14POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(14) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:14HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(14) acsw-li20-nw04")
}

record(stringin, "ACSW:LI20:NW04:14NAMESET") {
  field(FLNK, "ACSW:LI20:NW04:14NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW04:14NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(14) acsw-li20-nw04")
  field(DOL, "ACSW:LI20:NW04:14NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW04:14SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(14) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(bo, "ACSW:LI20:NW04:14SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(14) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(stringin, "ACSW:LI20:NW04:14INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:14INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW04:14INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW04:14INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW04:14INITSTATE")
}

record(mbbi, "ACSW:LI20:NW04:14INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:14INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW04:15NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:15POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW04:15POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW04:15POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW04:15POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW04:15POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW04:15POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW04:15POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:15POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW04:15POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(15) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:15POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(15) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:15HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(15) acsw-li20-nw04")
}

record(stringin, "ACSW:LI20:NW04:15NAMESET") {
  field(FLNK, "ACSW:LI20:NW04:15NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW04:15NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(15) acsw-li20-nw04")
  field(DOL, "ACSW:LI20:NW04:15NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW04:15SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(15) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(bo, "ACSW:LI20:NW04:15SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(15) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(stringin, "ACSW:LI20:NW04:15INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:15INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW04:15INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW04:15INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW04:15INITSTATE")
}

record(mbbi, "ACSW:LI20:NW04:15INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:15INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW04:16NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:16POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW04:16POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW04:16POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW04:16POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW04:16POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW04:16POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW04:16POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:16POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW04:16POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(16) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:16POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(16) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:16HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(16) acsw-li20-nw04")
}

record(stringin, "ACSW:LI20:NW04:16NAMESET") {
  field(FLNK, "ACSW:LI20:NW04:16NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW04:16NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(16) acsw-li20-nw04")
  field(DOL, "ACSW:LI20:NW04:16NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW04:16SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(16) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(bo, "ACSW:LI20:NW04:16SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(16) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(stringin, "ACSW:LI20:NW04:16INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:16INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW04:16INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW04:16INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW04:16INITSTATE")
}

record(mbbi, "ACSW:LI20:NW04:16INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:16INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW04:17NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:17POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW04:17POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW04:17POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW04:17POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW04:17POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW04:17POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW04:17POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:17POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW04:17POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(17) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:17POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(17) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:17HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(17) acsw-li20-nw04")
}

record(stringin, "ACSW:LI20:NW04:17NAMESET") {
  field(FLNK, "ACSW:LI20:NW04:17NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW04:17NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(17) acsw-li20-nw04")
  field(DOL, "ACSW:LI20:NW04:17NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW04:17SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(17) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(bo, "ACSW:LI20:NW04:17SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(17) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(stringin, "ACSW:LI20:NW04:17INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:17INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW04:17INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW04:17INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW04:17INITSTATE")
}

record(mbbi, "ACSW:LI20:NW04:17INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:17INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW04:18NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:18POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW04:18POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW04:18POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW04:18POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW04:18POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW04:18POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW04:18POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:18POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW04:18POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(18) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:18POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(18) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:18HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(18) acsw-li20-nw04")
}

record(stringin, "ACSW:LI20:NW04:18NAMESET") {
  field(FLNK, "ACSW:LI20:NW04:18NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW04:18NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(18) acsw-li20-nw04")
  field(DOL, "ACSW:LI20:NW04:18NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW04:18SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(18) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(bo, "ACSW:LI20:NW04:18SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(18) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(stringin, "ACSW:LI20:NW04:18INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:18INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW04:18INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW04:18INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW04:18INITSTATE")
}

record(mbbi, "ACSW:LI20:NW04:18INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:18INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW04:19NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:19POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW04:19POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW04:19POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW04:19POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW04:19POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW04:19POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW04:19POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:19POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW04:19POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(19) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:19POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(19) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:19HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(19) acsw-li20-nw04")
}

record(stringin, "ACSW:LI20:NW04:19NAMESET") {
  field(FLNK, "ACSW:LI20:NW04:19NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW04:19NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(19) acsw-li20-nw04")
  field(DOL, "ACSW:LI20:NW04:19NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW04:19SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(19) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(bo, "ACSW:LI20:NW04:19SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(19) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(stringin, "ACSW:LI20:NW04:19INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:19INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW04:19INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW04:19INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW04:19INITSTATE")
}

record(mbbi, "ACSW:LI20:NW04:19INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:19INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW04:20NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:20POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW04:20POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW04:20POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW04:20POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW04:20POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW04:20POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW04:20POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:20POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW04:20POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(20) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:20POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(20) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:20HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(20) acsw-li20-nw04")
}

record(stringin, "ACSW:LI20:NW04:20NAMESET") {
  field(FLNK, "ACSW:LI20:NW04:20NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW04:20NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(20) acsw-li20-nw04")
  field(DOL, "ACSW:LI20:NW04:20NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW04:20SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(20) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(bo, "ACSW:LI20:NW04:20SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(20) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(stringin, "ACSW:LI20:NW04:20INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:20INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW04:20INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW04:20INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW04:20INITSTATE")
}

record(mbbi, "ACSW:LI20:NW04:20INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:20INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW04:21NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:21POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW04:21POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW04:21POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW04:21POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW04:21POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW04:21POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW04:21POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:21POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW04:21POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(21) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:21POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(21) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:21HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(21) acsw-li20-nw04")
}

record(stringin, "ACSW:LI20:NW04:21NAMESET") {
  field(FLNK, "ACSW:LI20:NW04:21NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW04:21NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(21) acsw-li20-nw04")
  field(DOL, "ACSW:LI20:NW04:21NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW04:21SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(21) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(bo, "ACSW:LI20:NW04:21SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(21) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(stringin, "ACSW:LI20:NW04:21INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:21INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW04:21INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW04:21INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW04:21INITSTATE")
}

record(mbbi, "ACSW:LI20:NW04:21INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:21INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW04:22NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:22POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW04:22POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW04:22POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW04:22POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW04:22POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW04:22POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW04:22POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:22POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW04:22POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(22) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:22POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(22) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:22HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(22) acsw-li20-nw04")
}

record(stringin, "ACSW:LI20:NW04:22NAMESET") {
  field(FLNK, "ACSW:LI20:NW04:22NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW04:22NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(22) acsw-li20-nw04")
  field(DOL, "ACSW:LI20:NW04:22NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW04:22SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(22) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(bo, "ACSW:LI20:NW04:22SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(22) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(stringin, "ACSW:LI20:NW04:22INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:22INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW04:22INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW04:22INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW04:22INITSTATE")
}

record(mbbi, "ACSW:LI20:NW04:22INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:22INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW04:23NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:23POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW04:23POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW04:23POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW04:23POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW04:23POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW04:23POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW04:23POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:23POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW04:23POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(23) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:23POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(23) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:23HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(23) acsw-li20-nw04")
}

record(stringin, "ACSW:LI20:NW04:23NAMESET") {
  field(FLNK, "ACSW:LI20:NW04:23NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW04:23NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(23) acsw-li20-nw04")
  field(DOL, "ACSW:LI20:NW04:23NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW04:23SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(23) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(bo, "ACSW:LI20:NW04:23SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(23) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(stringin, "ACSW:LI20:NW04:23INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:23INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW04:23INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW04:23INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW04:23INITSTATE")
}

record(mbbi, "ACSW:LI20:NW04:23INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:23INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW04:24NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:24POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW04:24POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW04:24POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW04:24POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW04:24POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW04:24POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW04:24POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:24POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW04:24POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(24) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:24POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(24) acsw-li20-nw04")
}

record(bo, "ACSW:LI20:NW04:24HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(24) acsw-li20-nw04")
}

record(stringin, "ACSW:LI20:NW04:24NAMESET") {
  field(FLNK, "ACSW:LI20:NW04:24NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW04:24NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(24) acsw-li20-nw04")
  field(DOL, "ACSW:LI20:NW04:24NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW04:24SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(24) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(bo, "ACSW:LI20:NW04:24SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(24) acsw-li20-nw04")
  field(FLNK, "ACSW:LI20:NW04:GETINIT")
}

record(stringin, "ACSW:LI20:NW04:24INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW04:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW04:24INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW04:24INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW04:24INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW04:24INITSTATE")
}

record(mbbi, "ACSW:LI20:NW04:24INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW04:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW04:24INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW05:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:LI20:NW05) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINFO")
}

record(stringin, "ACSW:LI20:NW05:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:LI20:NW05) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(stringin, "ACSW:LI20:NW05:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:LI20:NW05:NETFWVERSION")
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:LI20:NW05:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:LI20:NW05:SITEID")
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:LI20:NW05:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:LI20:NW05:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState24(ACSW:LI20:NW05) acsw-li20-nw05")
}

record(stringin, "ACSW:LI20:NW05:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState24(ACSW:LI20:NW05) acsw-li20-nw05")
}

record(ai, "ACSW:LI20:NW05:TYPE") {
  field(DESC, "APC 24 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "17")
}

record(stringin, "ACSW:LI20:NW05:LOC") {
  field(PINI, "YES")
  field(VAL, "S20 Tunnel, IP1 table")
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:LI20:NW05:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-li20-nw05")
}

record(calcout, "ACSW:LI20:NW05:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:LI20:NW05:DISCONN.DISA")
  field(INPB, "ACSW:LI20:NW05:DISCONN.DISV")
  field(INPC, "ACSW:LI20:NW05:GETSTATUS.DISA")
  field(INPD, "ACSW:LI20:NW05:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:LI20:NW05:CONNSTA PP")
}

record(bi, "ACSW:LI20:NW05:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:LI20:NW05:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:LI20:NW05:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:LI20:NW05:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:LI20:NW05:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:LI20:NW05:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:LI20:NW05:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:LI20:NW05:UPTIMEHOUR") {
  field(FLNK, "ACSW:LI20:NW05:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:LI20:NW05:UPTIMEDAY") {
  field(FLNK, "ACSW:LI20:NW05:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:LI20:NW05:UPTIMEMINUTE") {
  field(FLNK, "ACSW:LI20:NW05:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:LI20:NW05:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:1POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW05:1POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW05:1POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW05:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW05:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW05:1POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW05:1POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW05:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-li20-nw05")
}

record(stringin, "ACSW:LI20:NW05:1NAMESET") {
  field(FLNK, "ACSW:LI20:NW05:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW05:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-li20-nw05")
  field(DOL, "ACSW:LI20:NW05:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW05:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(bo, "ACSW:LI20:NW05:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(stringin, "ACSW:LI20:NW05:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW05:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW05:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW05:1INITSTATE")
}

record(mbbi, "ACSW:LI20:NW05:1INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW05:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:2POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW05:2POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW05:2POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW05:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW05:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW05:2POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW05:2POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW05:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-li20-nw05")
}

record(stringin, "ACSW:LI20:NW05:2NAMESET") {
  field(FLNK, "ACSW:LI20:NW05:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW05:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-li20-nw05")
  field(DOL, "ACSW:LI20:NW05:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW05:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(bo, "ACSW:LI20:NW05:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(stringin, "ACSW:LI20:NW05:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW05:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW05:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW05:2INITSTATE")
}

record(mbbi, "ACSW:LI20:NW05:2INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW05:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:3POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW05:3POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW05:3POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW05:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW05:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW05:3POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW05:3POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW05:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-li20-nw05")
}

record(stringin, "ACSW:LI20:NW05:3NAMESET") {
  field(FLNK, "ACSW:LI20:NW05:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW05:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-li20-nw05")
  field(DOL, "ACSW:LI20:NW05:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW05:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(bo, "ACSW:LI20:NW05:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(stringin, "ACSW:LI20:NW05:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW05:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW05:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW05:3INITSTATE")
}

record(mbbi, "ACSW:LI20:NW05:3INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW05:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:4POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW05:4POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW05:4POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW05:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW05:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW05:4POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW05:4POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW05:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-li20-nw05")
}

record(stringin, "ACSW:LI20:NW05:4NAMESET") {
  field(FLNK, "ACSW:LI20:NW05:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW05:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-li20-nw05")
  field(DOL, "ACSW:LI20:NW05:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW05:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(bo, "ACSW:LI20:NW05:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(stringin, "ACSW:LI20:NW05:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW05:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW05:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW05:4INITSTATE")
}

record(mbbi, "ACSW:LI20:NW05:4INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW05:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:5POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW05:5POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW05:5POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW05:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW05:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW05:5POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW05:5POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW05:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-li20-nw05")
}

record(stringin, "ACSW:LI20:NW05:5NAMESET") {
  field(FLNK, "ACSW:LI20:NW05:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW05:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-li20-nw05")
  field(DOL, "ACSW:LI20:NW05:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW05:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(bo, "ACSW:LI20:NW05:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(stringin, "ACSW:LI20:NW05:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW05:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW05:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW05:5INITSTATE")
}

record(mbbi, "ACSW:LI20:NW05:5INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW05:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:6POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW05:6POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW05:6POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW05:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW05:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW05:6POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW05:6POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW05:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-li20-nw05")
}

record(stringin, "ACSW:LI20:NW05:6NAMESET") {
  field(FLNK, "ACSW:LI20:NW05:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW05:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-li20-nw05")
  field(DOL, "ACSW:LI20:NW05:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW05:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(bo, "ACSW:LI20:NW05:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(stringin, "ACSW:LI20:NW05:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW05:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW05:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW05:6INITSTATE")
}

record(mbbi, "ACSW:LI20:NW05:6INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW05:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:7POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW05:7POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW05:7POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW05:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW05:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW05:7POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW05:7POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW05:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-li20-nw05")
}

record(stringin, "ACSW:LI20:NW05:7NAMESET") {
  field(FLNK, "ACSW:LI20:NW05:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW05:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-li20-nw05")
  field(DOL, "ACSW:LI20:NW05:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW05:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(bo, "ACSW:LI20:NW05:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(stringin, "ACSW:LI20:NW05:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW05:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW05:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW05:7INITSTATE")
}

record(mbbi, "ACSW:LI20:NW05:7INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW05:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:8POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW05:8POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW05:8POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW05:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW05:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW05:8POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW05:8POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW05:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-li20-nw05")
}

record(stringin, "ACSW:LI20:NW05:8NAMESET") {
  field(FLNK, "ACSW:LI20:NW05:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW05:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-li20-nw05")
  field(DOL, "ACSW:LI20:NW05:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW05:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(bo, "ACSW:LI20:NW05:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(stringin, "ACSW:LI20:NW05:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW05:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW05:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW05:8INITSTATE")
}

record(mbbi, "ACSW:LI20:NW05:8INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW05:9NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:9POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW05:9POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW05:9POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW05:9POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW05:9POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW05:9POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW05:9POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:9POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW05:9POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(9) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:9POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(9) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:9HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(9) acsw-li20-nw05")
}

record(stringin, "ACSW:LI20:NW05:9NAMESET") {
  field(FLNK, "ACSW:LI20:NW05:9NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW05:9NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(9) acsw-li20-nw05")
  field(DOL, "ACSW:LI20:NW05:9NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW05:9SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(9) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(bo, "ACSW:LI20:NW05:9SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(9) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(stringin, "ACSW:LI20:NW05:9INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:9INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW05:9INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW05:9INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW05:9INITSTATE")
}

record(mbbi, "ACSW:LI20:NW05:9INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:9INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW05:10NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:10POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW05:10POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW05:10POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW05:10POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW05:10POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW05:10POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW05:10POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:10POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW05:10POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(10) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:10POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(10) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:10HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(10) acsw-li20-nw05")
}

record(stringin, "ACSW:LI20:NW05:10NAMESET") {
  field(FLNK, "ACSW:LI20:NW05:10NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW05:10NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(10) acsw-li20-nw05")
  field(DOL, "ACSW:LI20:NW05:10NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW05:10SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(10) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(bo, "ACSW:LI20:NW05:10SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(10) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(stringin, "ACSW:LI20:NW05:10INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:10INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW05:10INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW05:10INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW05:10INITSTATE")
}

record(mbbi, "ACSW:LI20:NW05:10INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:10INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW05:11NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:11POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW05:11POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW05:11POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW05:11POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW05:11POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW05:11POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW05:11POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:11POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW05:11POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(11) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:11POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(11) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:11HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(11) acsw-li20-nw05")
}

record(stringin, "ACSW:LI20:NW05:11NAMESET") {
  field(FLNK, "ACSW:LI20:NW05:11NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW05:11NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(11) acsw-li20-nw05")
  field(DOL, "ACSW:LI20:NW05:11NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW05:11SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(11) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(bo, "ACSW:LI20:NW05:11SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(11) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(stringin, "ACSW:LI20:NW05:11INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:11INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW05:11INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW05:11INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW05:11INITSTATE")
}

record(mbbi, "ACSW:LI20:NW05:11INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:11INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW05:12NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:12POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW05:12POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW05:12POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW05:12POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW05:12POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW05:12POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW05:12POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:12POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW05:12POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(12) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:12POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(12) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:12HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(12) acsw-li20-nw05")
}

record(stringin, "ACSW:LI20:NW05:12NAMESET") {
  field(FLNK, "ACSW:LI20:NW05:12NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW05:12NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(12) acsw-li20-nw05")
  field(DOL, "ACSW:LI20:NW05:12NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW05:12SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(12) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(bo, "ACSW:LI20:NW05:12SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(12) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(stringin, "ACSW:LI20:NW05:12INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:12INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW05:12INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW05:12INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW05:12INITSTATE")
}

record(mbbi, "ACSW:LI20:NW05:12INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:12INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW05:13NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:13POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW05:13POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW05:13POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW05:13POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW05:13POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW05:13POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW05:13POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:13POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW05:13POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(13) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:13POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(13) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:13HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(13) acsw-li20-nw05")
}

record(stringin, "ACSW:LI20:NW05:13NAMESET") {
  field(FLNK, "ACSW:LI20:NW05:13NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW05:13NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(13) acsw-li20-nw05")
  field(DOL, "ACSW:LI20:NW05:13NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW05:13SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(13) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(bo, "ACSW:LI20:NW05:13SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(13) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(stringin, "ACSW:LI20:NW05:13INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:13INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW05:13INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW05:13INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW05:13INITSTATE")
}

record(mbbi, "ACSW:LI20:NW05:13INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:13INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW05:14NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:14POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW05:14POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW05:14POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW05:14POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW05:14POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW05:14POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW05:14POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:14POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW05:14POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(14) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:14POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(14) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:14HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(14) acsw-li20-nw05")
}

record(stringin, "ACSW:LI20:NW05:14NAMESET") {
  field(FLNK, "ACSW:LI20:NW05:14NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW05:14NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(14) acsw-li20-nw05")
  field(DOL, "ACSW:LI20:NW05:14NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW05:14SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(14) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(bo, "ACSW:LI20:NW05:14SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(14) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(stringin, "ACSW:LI20:NW05:14INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:14INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW05:14INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW05:14INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW05:14INITSTATE")
}

record(mbbi, "ACSW:LI20:NW05:14INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:14INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW05:15NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:15POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW05:15POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW05:15POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW05:15POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW05:15POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW05:15POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW05:15POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:15POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW05:15POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(15) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:15POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(15) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:15HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(15) acsw-li20-nw05")
}

record(stringin, "ACSW:LI20:NW05:15NAMESET") {
  field(FLNK, "ACSW:LI20:NW05:15NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW05:15NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(15) acsw-li20-nw05")
  field(DOL, "ACSW:LI20:NW05:15NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW05:15SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(15) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(bo, "ACSW:LI20:NW05:15SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(15) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(stringin, "ACSW:LI20:NW05:15INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:15INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW05:15INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW05:15INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW05:15INITSTATE")
}

record(mbbi, "ACSW:LI20:NW05:15INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:15INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW05:16NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:16POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW05:16POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW05:16POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW05:16POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW05:16POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW05:16POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW05:16POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:16POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW05:16POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(16) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:16POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(16) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:16HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(16) acsw-li20-nw05")
}

record(stringin, "ACSW:LI20:NW05:16NAMESET") {
  field(FLNK, "ACSW:LI20:NW05:16NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW05:16NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(16) acsw-li20-nw05")
  field(DOL, "ACSW:LI20:NW05:16NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW05:16SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(16) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(bo, "ACSW:LI20:NW05:16SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(16) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(stringin, "ACSW:LI20:NW05:16INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:16INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW05:16INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW05:16INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW05:16INITSTATE")
}

record(mbbi, "ACSW:LI20:NW05:16INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:16INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW05:17NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:17POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW05:17POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW05:17POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW05:17POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW05:17POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW05:17POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW05:17POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:17POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW05:17POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(17) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:17POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(17) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:17HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(17) acsw-li20-nw05")
}

record(stringin, "ACSW:LI20:NW05:17NAMESET") {
  field(FLNK, "ACSW:LI20:NW05:17NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW05:17NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(17) acsw-li20-nw05")
  field(DOL, "ACSW:LI20:NW05:17NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW05:17SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(17) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(bo, "ACSW:LI20:NW05:17SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(17) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(stringin, "ACSW:LI20:NW05:17INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:17INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW05:17INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW05:17INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW05:17INITSTATE")
}

record(mbbi, "ACSW:LI20:NW05:17INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:17INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW05:18NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:18POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW05:18POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW05:18POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW05:18POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW05:18POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW05:18POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW05:18POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:18POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW05:18POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(18) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:18POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(18) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:18HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(18) acsw-li20-nw05")
}

record(stringin, "ACSW:LI20:NW05:18NAMESET") {
  field(FLNK, "ACSW:LI20:NW05:18NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW05:18NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(18) acsw-li20-nw05")
  field(DOL, "ACSW:LI20:NW05:18NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW05:18SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(18) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(bo, "ACSW:LI20:NW05:18SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(18) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(stringin, "ACSW:LI20:NW05:18INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:18INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW05:18INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW05:18INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW05:18INITSTATE")
}

record(mbbi, "ACSW:LI20:NW05:18INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:18INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW05:19NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:19POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW05:19POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW05:19POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW05:19POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW05:19POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW05:19POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW05:19POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:19POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW05:19POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(19) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:19POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(19) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:19HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(19) acsw-li20-nw05")
}

record(stringin, "ACSW:LI20:NW05:19NAMESET") {
  field(FLNK, "ACSW:LI20:NW05:19NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW05:19NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(19) acsw-li20-nw05")
  field(DOL, "ACSW:LI20:NW05:19NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW05:19SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(19) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(bo, "ACSW:LI20:NW05:19SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(19) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(stringin, "ACSW:LI20:NW05:19INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:19INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW05:19INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW05:19INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW05:19INITSTATE")
}

record(mbbi, "ACSW:LI20:NW05:19INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:19INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW05:20NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:20POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW05:20POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW05:20POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW05:20POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW05:20POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW05:20POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW05:20POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:20POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW05:20POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(20) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:20POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(20) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:20HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(20) acsw-li20-nw05")
}

record(stringin, "ACSW:LI20:NW05:20NAMESET") {
  field(FLNK, "ACSW:LI20:NW05:20NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW05:20NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(20) acsw-li20-nw05")
  field(DOL, "ACSW:LI20:NW05:20NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW05:20SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(20) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(bo, "ACSW:LI20:NW05:20SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(20) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(stringin, "ACSW:LI20:NW05:20INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:20INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW05:20INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW05:20INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW05:20INITSTATE")
}

record(mbbi, "ACSW:LI20:NW05:20INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:20INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW05:21NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:21POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW05:21POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW05:21POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW05:21POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW05:21POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW05:21POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW05:21POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:21POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW05:21POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(21) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:21POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(21) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:21HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(21) acsw-li20-nw05")
}

record(stringin, "ACSW:LI20:NW05:21NAMESET") {
  field(FLNK, "ACSW:LI20:NW05:21NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW05:21NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(21) acsw-li20-nw05")
  field(DOL, "ACSW:LI20:NW05:21NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW05:21SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(21) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(bo, "ACSW:LI20:NW05:21SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(21) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(stringin, "ACSW:LI20:NW05:21INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:21INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW05:21INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW05:21INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW05:21INITSTATE")
}

record(mbbi, "ACSW:LI20:NW05:21INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:21INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW05:22NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:22POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW05:22POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW05:22POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW05:22POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW05:22POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW05:22POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW05:22POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:22POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW05:22POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(22) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:22POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(22) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:22HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(22) acsw-li20-nw05")
}

record(stringin, "ACSW:LI20:NW05:22NAMESET") {
  field(FLNK, "ACSW:LI20:NW05:22NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW05:22NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(22) acsw-li20-nw05")
  field(DOL, "ACSW:LI20:NW05:22NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW05:22SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(22) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(bo, "ACSW:LI20:NW05:22SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(22) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(stringin, "ACSW:LI20:NW05:22INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:22INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW05:22INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW05:22INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW05:22INITSTATE")
}

record(mbbi, "ACSW:LI20:NW05:22INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:22INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW05:23NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:23POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW05:23POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW05:23POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW05:23POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW05:23POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW05:23POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW05:23POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:23POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW05:23POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(23) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:23POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(23) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:23HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(23) acsw-li20-nw05")
}

record(stringin, "ACSW:LI20:NW05:23NAMESET") {
  field(FLNK, "ACSW:LI20:NW05:23NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW05:23NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(23) acsw-li20-nw05")
  field(DOL, "ACSW:LI20:NW05:23NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW05:23SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(23) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(bo, "ACSW:LI20:NW05:23SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(23) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(stringin, "ACSW:LI20:NW05:23INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:23INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW05:23INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW05:23INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW05:23INITSTATE")
}

record(mbbi, "ACSW:LI20:NW05:23INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:23INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW05:24NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:24POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW05:24POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW05:24POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW05:24POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW05:24POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW05:24POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW05:24POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:24POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW05:24POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(24) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:24POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(24) acsw-li20-nw05")
}

record(bo, "ACSW:LI20:NW05:24HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(24) acsw-li20-nw05")
}

record(stringin, "ACSW:LI20:NW05:24NAMESET") {
  field(FLNK, "ACSW:LI20:NW05:24NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW05:24NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(24) acsw-li20-nw05")
  field(DOL, "ACSW:LI20:NW05:24NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW05:24SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(24) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(bo, "ACSW:LI20:NW05:24SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(24) acsw-li20-nw05")
  field(FLNK, "ACSW:LI20:NW05:GETINIT")
}

record(stringin, "ACSW:LI20:NW05:24INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW05:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW05:24INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW05:24INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW05:24INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW05:24INITSTATE")
}

record(mbbi, "ACSW:LI20:NW05:24INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW05:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW05:24INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW06:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:LI20:NW06) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINFO")
}

record(stringin, "ACSW:LI20:NW06:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:LI20:NW06) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(stringin, "ACSW:LI20:NW06:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:LI20:NW06:NETFWVERSION")
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:LI20:NW06:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:LI20:NW06:SITEID")
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:LI20:NW06:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:LI20:NW06:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState24(ACSW:LI20:NW06) acsw-li20-nw06")
}

record(stringin, "ACSW:LI20:NW06:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState24(ACSW:LI20:NW06) acsw-li20-nw06")
}

record(ai, "ACSW:LI20:NW06:TYPE") {
  field(DESC, "APC 24 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "17")
}

record(stringin, "ACSW:LI20:NW06:LOC") {
  field(PINI, "YES")
  field(VAL, "S20 Tunnel, IP2 table")
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:LI20:NW06:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-li20-nw06")
}

record(calcout, "ACSW:LI20:NW06:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:LI20:NW06:DISCONN.DISA")
  field(INPB, "ACSW:LI20:NW06:DISCONN.DISV")
  field(INPC, "ACSW:LI20:NW06:GETSTATUS.DISA")
  field(INPD, "ACSW:LI20:NW06:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:LI20:NW06:CONNSTA PP")
}

record(bi, "ACSW:LI20:NW06:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:LI20:NW06:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:LI20:NW06:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:LI20:NW06:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:LI20:NW06:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:LI20:NW06:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:LI20:NW06:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:LI20:NW06:UPTIMEHOUR") {
  field(FLNK, "ACSW:LI20:NW06:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:LI20:NW06:UPTIMEDAY") {
  field(FLNK, "ACSW:LI20:NW06:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:LI20:NW06:UPTIMEMINUTE") {
  field(FLNK, "ACSW:LI20:NW06:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:LI20:NW06:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:1POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW06:1POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW06:1POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW06:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW06:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW06:1POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW06:1POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW06:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-li20-nw06")
}

record(stringin, "ACSW:LI20:NW06:1NAMESET") {
  field(FLNK, "ACSW:LI20:NW06:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW06:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-li20-nw06")
  field(DOL, "ACSW:LI20:NW06:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW06:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(bo, "ACSW:LI20:NW06:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(stringin, "ACSW:LI20:NW06:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW06:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW06:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW06:1INITSTATE")
}

record(mbbi, "ACSW:LI20:NW06:1INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW06:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:2POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW06:2POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW06:2POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW06:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW06:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW06:2POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW06:2POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW06:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-li20-nw06")
}

record(stringin, "ACSW:LI20:NW06:2NAMESET") {
  field(FLNK, "ACSW:LI20:NW06:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW06:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-li20-nw06")
  field(DOL, "ACSW:LI20:NW06:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW06:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(bo, "ACSW:LI20:NW06:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(stringin, "ACSW:LI20:NW06:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW06:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW06:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW06:2INITSTATE")
}

record(mbbi, "ACSW:LI20:NW06:2INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW06:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:3POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW06:3POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW06:3POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW06:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW06:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW06:3POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW06:3POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW06:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-li20-nw06")
}

record(stringin, "ACSW:LI20:NW06:3NAMESET") {
  field(FLNK, "ACSW:LI20:NW06:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW06:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-li20-nw06")
  field(DOL, "ACSW:LI20:NW06:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW06:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(bo, "ACSW:LI20:NW06:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(stringin, "ACSW:LI20:NW06:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW06:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW06:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW06:3INITSTATE")
}

record(mbbi, "ACSW:LI20:NW06:3INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW06:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:4POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW06:4POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW06:4POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW06:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW06:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW06:4POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW06:4POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW06:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-li20-nw06")
}

record(stringin, "ACSW:LI20:NW06:4NAMESET") {
  field(FLNK, "ACSW:LI20:NW06:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW06:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-li20-nw06")
  field(DOL, "ACSW:LI20:NW06:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW06:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(bo, "ACSW:LI20:NW06:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(stringin, "ACSW:LI20:NW06:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW06:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW06:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW06:4INITSTATE")
}

record(mbbi, "ACSW:LI20:NW06:4INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW06:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:5POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW06:5POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW06:5POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW06:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW06:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW06:5POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW06:5POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW06:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-li20-nw06")
}

record(stringin, "ACSW:LI20:NW06:5NAMESET") {
  field(FLNK, "ACSW:LI20:NW06:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW06:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-li20-nw06")
  field(DOL, "ACSW:LI20:NW06:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW06:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(bo, "ACSW:LI20:NW06:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(stringin, "ACSW:LI20:NW06:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW06:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW06:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW06:5INITSTATE")
}

record(mbbi, "ACSW:LI20:NW06:5INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW06:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:6POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW06:6POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW06:6POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW06:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW06:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW06:6POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW06:6POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW06:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-li20-nw06")
}

record(stringin, "ACSW:LI20:NW06:6NAMESET") {
  field(FLNK, "ACSW:LI20:NW06:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW06:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-li20-nw06")
  field(DOL, "ACSW:LI20:NW06:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW06:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(bo, "ACSW:LI20:NW06:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(stringin, "ACSW:LI20:NW06:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW06:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW06:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW06:6INITSTATE")
}

record(mbbi, "ACSW:LI20:NW06:6INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW06:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:7POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW06:7POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW06:7POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW06:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW06:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW06:7POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW06:7POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW06:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-li20-nw06")
}

record(stringin, "ACSW:LI20:NW06:7NAMESET") {
  field(FLNK, "ACSW:LI20:NW06:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW06:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-li20-nw06")
  field(DOL, "ACSW:LI20:NW06:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW06:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(bo, "ACSW:LI20:NW06:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(stringin, "ACSW:LI20:NW06:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW06:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW06:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW06:7INITSTATE")
}

record(mbbi, "ACSW:LI20:NW06:7INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW06:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:8POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW06:8POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW06:8POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW06:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW06:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW06:8POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW06:8POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW06:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-li20-nw06")
}

record(stringin, "ACSW:LI20:NW06:8NAMESET") {
  field(FLNK, "ACSW:LI20:NW06:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW06:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-li20-nw06")
  field(DOL, "ACSW:LI20:NW06:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW06:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(bo, "ACSW:LI20:NW06:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(stringin, "ACSW:LI20:NW06:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW06:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW06:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW06:8INITSTATE")
}

record(mbbi, "ACSW:LI20:NW06:8INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW06:9NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:9POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW06:9POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW06:9POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW06:9POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW06:9POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW06:9POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW06:9POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:9POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW06:9POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(9) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:9POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(9) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:9HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(9) acsw-li20-nw06")
}

record(stringin, "ACSW:LI20:NW06:9NAMESET") {
  field(FLNK, "ACSW:LI20:NW06:9NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW06:9NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(9) acsw-li20-nw06")
  field(DOL, "ACSW:LI20:NW06:9NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW06:9SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(9) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(bo, "ACSW:LI20:NW06:9SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(9) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(stringin, "ACSW:LI20:NW06:9INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:9INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW06:9INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW06:9INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW06:9INITSTATE")
}

record(mbbi, "ACSW:LI20:NW06:9INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:9INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW06:10NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:10POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW06:10POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW06:10POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW06:10POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW06:10POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW06:10POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW06:10POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:10POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW06:10POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(10) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:10POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(10) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:10HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(10) acsw-li20-nw06")
}

record(stringin, "ACSW:LI20:NW06:10NAMESET") {
  field(FLNK, "ACSW:LI20:NW06:10NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW06:10NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(10) acsw-li20-nw06")
  field(DOL, "ACSW:LI20:NW06:10NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW06:10SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(10) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(bo, "ACSW:LI20:NW06:10SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(10) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(stringin, "ACSW:LI20:NW06:10INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:10INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW06:10INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW06:10INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW06:10INITSTATE")
}

record(mbbi, "ACSW:LI20:NW06:10INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:10INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW06:11NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:11POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW06:11POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW06:11POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW06:11POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW06:11POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW06:11POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW06:11POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:11POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW06:11POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(11) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:11POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(11) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:11HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(11) acsw-li20-nw06")
}

record(stringin, "ACSW:LI20:NW06:11NAMESET") {
  field(FLNK, "ACSW:LI20:NW06:11NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW06:11NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(11) acsw-li20-nw06")
  field(DOL, "ACSW:LI20:NW06:11NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW06:11SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(11) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(bo, "ACSW:LI20:NW06:11SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(11) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(stringin, "ACSW:LI20:NW06:11INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:11INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW06:11INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW06:11INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW06:11INITSTATE")
}

record(mbbi, "ACSW:LI20:NW06:11INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:11INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW06:12NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:12POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW06:12POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW06:12POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW06:12POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW06:12POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW06:12POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW06:12POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:12POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW06:12POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(12) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:12POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(12) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:12HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(12) acsw-li20-nw06")
}

record(stringin, "ACSW:LI20:NW06:12NAMESET") {
  field(FLNK, "ACSW:LI20:NW06:12NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW06:12NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(12) acsw-li20-nw06")
  field(DOL, "ACSW:LI20:NW06:12NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW06:12SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(12) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(bo, "ACSW:LI20:NW06:12SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(12) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(stringin, "ACSW:LI20:NW06:12INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:12INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW06:12INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW06:12INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW06:12INITSTATE")
}

record(mbbi, "ACSW:LI20:NW06:12INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:12INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW06:13NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:13POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW06:13POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW06:13POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW06:13POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW06:13POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW06:13POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW06:13POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:13POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW06:13POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(13) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:13POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(13) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:13HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(13) acsw-li20-nw06")
}

record(stringin, "ACSW:LI20:NW06:13NAMESET") {
  field(FLNK, "ACSW:LI20:NW06:13NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW06:13NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(13) acsw-li20-nw06")
  field(DOL, "ACSW:LI20:NW06:13NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW06:13SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(13) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(bo, "ACSW:LI20:NW06:13SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(13) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(stringin, "ACSW:LI20:NW06:13INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:13INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW06:13INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW06:13INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW06:13INITSTATE")
}

record(mbbi, "ACSW:LI20:NW06:13INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:13INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW06:14NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:14POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW06:14POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW06:14POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW06:14POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW06:14POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW06:14POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW06:14POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:14POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW06:14POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(14) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:14POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(14) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:14HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(14) acsw-li20-nw06")
}

record(stringin, "ACSW:LI20:NW06:14NAMESET") {
  field(FLNK, "ACSW:LI20:NW06:14NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW06:14NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(14) acsw-li20-nw06")
  field(DOL, "ACSW:LI20:NW06:14NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW06:14SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(14) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(bo, "ACSW:LI20:NW06:14SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(14) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(stringin, "ACSW:LI20:NW06:14INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:14INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW06:14INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW06:14INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW06:14INITSTATE")
}

record(mbbi, "ACSW:LI20:NW06:14INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:14INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW06:15NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:15POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW06:15POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW06:15POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW06:15POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW06:15POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW06:15POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW06:15POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:15POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW06:15POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(15) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:15POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(15) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:15HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(15) acsw-li20-nw06")
}

record(stringin, "ACSW:LI20:NW06:15NAMESET") {
  field(FLNK, "ACSW:LI20:NW06:15NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW06:15NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(15) acsw-li20-nw06")
  field(DOL, "ACSW:LI20:NW06:15NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW06:15SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(15) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(bo, "ACSW:LI20:NW06:15SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(15) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(stringin, "ACSW:LI20:NW06:15INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:15INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW06:15INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW06:15INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW06:15INITSTATE")
}

record(mbbi, "ACSW:LI20:NW06:15INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:15INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW06:16NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:16POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW06:16POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW06:16POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW06:16POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW06:16POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW06:16POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW06:16POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:16POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW06:16POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(16) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:16POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(16) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:16HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(16) acsw-li20-nw06")
}

record(stringin, "ACSW:LI20:NW06:16NAMESET") {
  field(FLNK, "ACSW:LI20:NW06:16NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW06:16NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(16) acsw-li20-nw06")
  field(DOL, "ACSW:LI20:NW06:16NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW06:16SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(16) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(bo, "ACSW:LI20:NW06:16SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(16) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(stringin, "ACSW:LI20:NW06:16INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:16INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW06:16INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW06:16INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW06:16INITSTATE")
}

record(mbbi, "ACSW:LI20:NW06:16INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:16INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW06:17NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:17POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW06:17POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW06:17POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW06:17POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW06:17POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW06:17POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW06:17POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:17POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW06:17POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(17) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:17POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(17) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:17HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(17) acsw-li20-nw06")
}

record(stringin, "ACSW:LI20:NW06:17NAMESET") {
  field(FLNK, "ACSW:LI20:NW06:17NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW06:17NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(17) acsw-li20-nw06")
  field(DOL, "ACSW:LI20:NW06:17NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW06:17SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(17) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(bo, "ACSW:LI20:NW06:17SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(17) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(stringin, "ACSW:LI20:NW06:17INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:17INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW06:17INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW06:17INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW06:17INITSTATE")
}

record(mbbi, "ACSW:LI20:NW06:17INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:17INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW06:18NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:18POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW06:18POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW06:18POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW06:18POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW06:18POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW06:18POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW06:18POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:18POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW06:18POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(18) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:18POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(18) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:18HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(18) acsw-li20-nw06")
}

record(stringin, "ACSW:LI20:NW06:18NAMESET") {
  field(FLNK, "ACSW:LI20:NW06:18NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW06:18NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(18) acsw-li20-nw06")
  field(DOL, "ACSW:LI20:NW06:18NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW06:18SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(18) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(bo, "ACSW:LI20:NW06:18SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(18) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(stringin, "ACSW:LI20:NW06:18INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:18INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW06:18INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW06:18INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW06:18INITSTATE")
}

record(mbbi, "ACSW:LI20:NW06:18INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:18INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW06:19NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:19POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW06:19POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW06:19POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW06:19POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW06:19POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW06:19POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW06:19POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:19POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW06:19POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(19) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:19POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(19) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:19HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(19) acsw-li20-nw06")
}

record(stringin, "ACSW:LI20:NW06:19NAMESET") {
  field(FLNK, "ACSW:LI20:NW06:19NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW06:19NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(19) acsw-li20-nw06")
  field(DOL, "ACSW:LI20:NW06:19NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW06:19SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(19) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(bo, "ACSW:LI20:NW06:19SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(19) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(stringin, "ACSW:LI20:NW06:19INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:19INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW06:19INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW06:19INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW06:19INITSTATE")
}

record(mbbi, "ACSW:LI20:NW06:19INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:19INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW06:20NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:20POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW06:20POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW06:20POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW06:20POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW06:20POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW06:20POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW06:20POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:20POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW06:20POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(20) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:20POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(20) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:20HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(20) acsw-li20-nw06")
}

record(stringin, "ACSW:LI20:NW06:20NAMESET") {
  field(FLNK, "ACSW:LI20:NW06:20NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW06:20NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(20) acsw-li20-nw06")
  field(DOL, "ACSW:LI20:NW06:20NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW06:20SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(20) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(bo, "ACSW:LI20:NW06:20SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(20) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(stringin, "ACSW:LI20:NW06:20INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:20INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW06:20INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW06:20INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW06:20INITSTATE")
}

record(mbbi, "ACSW:LI20:NW06:20INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:20INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW06:21NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:21POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW06:21POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW06:21POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW06:21POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW06:21POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW06:21POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW06:21POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:21POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW06:21POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(21) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:21POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(21) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:21HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(21) acsw-li20-nw06")
}

record(stringin, "ACSW:LI20:NW06:21NAMESET") {
  field(FLNK, "ACSW:LI20:NW06:21NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW06:21NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(21) acsw-li20-nw06")
  field(DOL, "ACSW:LI20:NW06:21NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW06:21SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(21) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(bo, "ACSW:LI20:NW06:21SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(21) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(stringin, "ACSW:LI20:NW06:21INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:21INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW06:21INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW06:21INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW06:21INITSTATE")
}

record(mbbi, "ACSW:LI20:NW06:21INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:21INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW06:22NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:22POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW06:22POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW06:22POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW06:22POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW06:22POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW06:22POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW06:22POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:22POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW06:22POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(22) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:22POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(22) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:22HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(22) acsw-li20-nw06")
}

record(stringin, "ACSW:LI20:NW06:22NAMESET") {
  field(FLNK, "ACSW:LI20:NW06:22NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW06:22NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(22) acsw-li20-nw06")
  field(DOL, "ACSW:LI20:NW06:22NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW06:22SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(22) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(bo, "ACSW:LI20:NW06:22SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(22) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(stringin, "ACSW:LI20:NW06:22INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:22INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW06:22INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW06:22INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW06:22INITSTATE")
}

record(mbbi, "ACSW:LI20:NW06:22INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:22INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW06:23NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:23POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW06:23POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW06:23POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW06:23POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW06:23POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW06:23POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW06:23POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:23POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW06:23POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(23) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:23POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(23) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:23HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(23) acsw-li20-nw06")
}

record(stringin, "ACSW:LI20:NW06:23NAMESET") {
  field(FLNK, "ACSW:LI20:NW06:23NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW06:23NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(23) acsw-li20-nw06")
  field(DOL, "ACSW:LI20:NW06:23NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW06:23SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(23) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(bo, "ACSW:LI20:NW06:23SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(23) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(stringin, "ACSW:LI20:NW06:23INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:23INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW06:23INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW06:23INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW06:23INITSTATE")
}

record(mbbi, "ACSW:LI20:NW06:23INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:23INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW06:24NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:24POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW06:24POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW06:24POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW06:24POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW06:24POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW06:24POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW06:24POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:24POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW06:24POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(24) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:24POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(24) acsw-li20-nw06")
}

record(bo, "ACSW:LI20:NW06:24HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(24) acsw-li20-nw06")
}

record(stringin, "ACSW:LI20:NW06:24NAMESET") {
  field(FLNK, "ACSW:LI20:NW06:24NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW06:24NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(24) acsw-li20-nw06")
  field(DOL, "ACSW:LI20:NW06:24NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW06:24SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(24) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(bo, "ACSW:LI20:NW06:24SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(24) acsw-li20-nw06")
  field(FLNK, "ACSW:LI20:NW06:GETINIT")
}

record(stringin, "ACSW:LI20:NW06:24INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW06:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW06:24INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW06:24INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW06:24INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW06:24INITSTATE")
}

record(mbbi, "ACSW:LI20:NW06:24INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW06:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW06:24INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW11:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:LI20:NW11) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINFO")
}

record(stringin, "ACSW:LI20:NW11:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:LI20:NW11) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(stringin, "ACSW:LI20:NW11:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:LI20:NW11:NETFWVERSION")
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:LI20:NW11:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:LI20:NW11:SITEID")
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:LI20:NW11:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:LI20:NW11:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState24(ACSW:LI20:NW11) acsw-li20-nw11")
}

record(stringin, "ACSW:LI20:NW11:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState24(ACSW:LI20:NW11) acsw-li20-nw11")
}

record(ai, "ACSW:LI20:NW11:TYPE") {
  field(DESC, "APC 24 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "17")
}

record(stringin, "ACSW:LI20:NW11:LOC") {
  field(PINI, "YES")
  field(VAL, "FKG20-26")
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:LI20:NW11:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-li20-nw11")
}

record(calcout, "ACSW:LI20:NW11:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:LI20:NW11:DISCONN.DISA")
  field(INPB, "ACSW:LI20:NW11:DISCONN.DISV")
  field(INPC, "ACSW:LI20:NW11:GETSTATUS.DISA")
  field(INPD, "ACSW:LI20:NW11:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:LI20:NW11:CONNSTA PP")
}

record(bi, "ACSW:LI20:NW11:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:LI20:NW11:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:LI20:NW11:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:LI20:NW11:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:LI20:NW11:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:LI20:NW11:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:LI20:NW11:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:LI20:NW11:UPTIMEHOUR") {
  field(FLNK, "ACSW:LI20:NW11:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:LI20:NW11:UPTIMEDAY") {
  field(FLNK, "ACSW:LI20:NW11:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:LI20:NW11:UPTIMEMINUTE") {
  field(FLNK, "ACSW:LI20:NW11:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:LI20:NW11:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:1POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW11:1POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW11:1POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW11:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW11:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW11:1POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW11:1POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW11:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-li20-nw11")
}

record(stringin, "ACSW:LI20:NW11:1NAMESET") {
  field(FLNK, "ACSW:LI20:NW11:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW11:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-li20-nw11")
  field(DOL, "ACSW:LI20:NW11:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW11:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(bo, "ACSW:LI20:NW11:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(stringin, "ACSW:LI20:NW11:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW11:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW11:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW11:1INITSTATE")
}

record(mbbi, "ACSW:LI20:NW11:1INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW11:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:2POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW11:2POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW11:2POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW11:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW11:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW11:2POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW11:2POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW11:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-li20-nw11")
}

record(stringin, "ACSW:LI20:NW11:2NAMESET") {
  field(FLNK, "ACSW:LI20:NW11:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW11:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-li20-nw11")
  field(DOL, "ACSW:LI20:NW11:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW11:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(bo, "ACSW:LI20:NW11:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(stringin, "ACSW:LI20:NW11:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW11:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW11:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW11:2INITSTATE")
}

record(mbbi, "ACSW:LI20:NW11:2INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW11:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:3POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW11:3POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW11:3POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW11:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW11:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW11:3POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW11:3POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW11:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-li20-nw11")
}

record(stringin, "ACSW:LI20:NW11:3NAMESET") {
  field(FLNK, "ACSW:LI20:NW11:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW11:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-li20-nw11")
  field(DOL, "ACSW:LI20:NW11:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW11:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(bo, "ACSW:LI20:NW11:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(stringin, "ACSW:LI20:NW11:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW11:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW11:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW11:3INITSTATE")
}

record(mbbi, "ACSW:LI20:NW11:3INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW11:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:4POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW11:4POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW11:4POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW11:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW11:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW11:4POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW11:4POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW11:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-li20-nw11")
}

record(stringin, "ACSW:LI20:NW11:4NAMESET") {
  field(FLNK, "ACSW:LI20:NW11:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW11:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-li20-nw11")
  field(DOL, "ACSW:LI20:NW11:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW11:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(bo, "ACSW:LI20:NW11:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(stringin, "ACSW:LI20:NW11:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW11:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW11:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW11:4INITSTATE")
}

record(mbbi, "ACSW:LI20:NW11:4INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW11:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:5POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW11:5POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW11:5POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW11:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW11:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW11:5POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW11:5POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW11:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-li20-nw11")
}

record(stringin, "ACSW:LI20:NW11:5NAMESET") {
  field(FLNK, "ACSW:LI20:NW11:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW11:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-li20-nw11")
  field(DOL, "ACSW:LI20:NW11:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW11:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(bo, "ACSW:LI20:NW11:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(stringin, "ACSW:LI20:NW11:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW11:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW11:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW11:5INITSTATE")
}

record(mbbi, "ACSW:LI20:NW11:5INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW11:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:6POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW11:6POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW11:6POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW11:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW11:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW11:6POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW11:6POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW11:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-li20-nw11")
}

record(stringin, "ACSW:LI20:NW11:6NAMESET") {
  field(FLNK, "ACSW:LI20:NW11:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW11:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-li20-nw11")
  field(DOL, "ACSW:LI20:NW11:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW11:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(bo, "ACSW:LI20:NW11:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(stringin, "ACSW:LI20:NW11:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW11:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW11:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW11:6INITSTATE")
}

record(mbbi, "ACSW:LI20:NW11:6INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW11:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:7POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW11:7POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW11:7POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW11:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW11:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW11:7POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW11:7POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW11:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-li20-nw11")
}

record(stringin, "ACSW:LI20:NW11:7NAMESET") {
  field(FLNK, "ACSW:LI20:NW11:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW11:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-li20-nw11")
  field(DOL, "ACSW:LI20:NW11:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW11:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(bo, "ACSW:LI20:NW11:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(stringin, "ACSW:LI20:NW11:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW11:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW11:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW11:7INITSTATE")
}

record(mbbi, "ACSW:LI20:NW11:7INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW11:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:8POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW11:8POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW11:8POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW11:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW11:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW11:8POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW11:8POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW11:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-li20-nw11")
}

record(stringin, "ACSW:LI20:NW11:8NAMESET") {
  field(FLNK, "ACSW:LI20:NW11:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW11:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-li20-nw11")
  field(DOL, "ACSW:LI20:NW11:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW11:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(bo, "ACSW:LI20:NW11:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(stringin, "ACSW:LI20:NW11:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW11:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW11:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW11:8INITSTATE")
}

record(mbbi, "ACSW:LI20:NW11:8INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW11:9NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:9POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW11:9POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW11:9POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW11:9POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW11:9POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW11:9POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW11:9POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:9POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW11:9POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(9) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:9POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(9) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:9HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(9) acsw-li20-nw11")
}

record(stringin, "ACSW:LI20:NW11:9NAMESET") {
  field(FLNK, "ACSW:LI20:NW11:9NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW11:9NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(9) acsw-li20-nw11")
  field(DOL, "ACSW:LI20:NW11:9NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW11:9SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(9) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(bo, "ACSW:LI20:NW11:9SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(9) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(stringin, "ACSW:LI20:NW11:9INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:9INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW11:9INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW11:9INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW11:9INITSTATE")
}

record(mbbi, "ACSW:LI20:NW11:9INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:9INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW11:10NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:10POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW11:10POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW11:10POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW11:10POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW11:10POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW11:10POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW11:10POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:10POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW11:10POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(10) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:10POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(10) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:10HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(10) acsw-li20-nw11")
}

record(stringin, "ACSW:LI20:NW11:10NAMESET") {
  field(FLNK, "ACSW:LI20:NW11:10NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW11:10NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(10) acsw-li20-nw11")
  field(DOL, "ACSW:LI20:NW11:10NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW11:10SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(10) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(bo, "ACSW:LI20:NW11:10SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(10) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(stringin, "ACSW:LI20:NW11:10INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:10INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW11:10INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW11:10INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW11:10INITSTATE")
}

record(mbbi, "ACSW:LI20:NW11:10INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:10INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW11:11NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:11POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW11:11POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW11:11POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW11:11POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW11:11POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW11:11POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW11:11POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:11POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW11:11POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(11) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:11POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(11) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:11HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(11) acsw-li20-nw11")
}

record(stringin, "ACSW:LI20:NW11:11NAMESET") {
  field(FLNK, "ACSW:LI20:NW11:11NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW11:11NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(11) acsw-li20-nw11")
  field(DOL, "ACSW:LI20:NW11:11NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW11:11SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(11) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(bo, "ACSW:LI20:NW11:11SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(11) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(stringin, "ACSW:LI20:NW11:11INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:11INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW11:11INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW11:11INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW11:11INITSTATE")
}

record(mbbi, "ACSW:LI20:NW11:11INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:11INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW11:12NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:12POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW11:12POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW11:12POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW11:12POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW11:12POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW11:12POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW11:12POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:12POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW11:12POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(12) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:12POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(12) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:12HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(12) acsw-li20-nw11")
}

record(stringin, "ACSW:LI20:NW11:12NAMESET") {
  field(FLNK, "ACSW:LI20:NW11:12NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW11:12NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(12) acsw-li20-nw11")
  field(DOL, "ACSW:LI20:NW11:12NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW11:12SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(12) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(bo, "ACSW:LI20:NW11:12SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(12) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(stringin, "ACSW:LI20:NW11:12INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:12INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW11:12INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW11:12INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW11:12INITSTATE")
}

record(mbbi, "ACSW:LI20:NW11:12INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:12INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW11:13NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:13POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW11:13POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW11:13POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW11:13POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW11:13POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW11:13POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW11:13POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:13POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW11:13POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(13) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:13POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(13) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:13HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(13) acsw-li20-nw11")
}

record(stringin, "ACSW:LI20:NW11:13NAMESET") {
  field(FLNK, "ACSW:LI20:NW11:13NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW11:13NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(13) acsw-li20-nw11")
  field(DOL, "ACSW:LI20:NW11:13NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW11:13SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(13) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(bo, "ACSW:LI20:NW11:13SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(13) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(stringin, "ACSW:LI20:NW11:13INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:13INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW11:13INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW11:13INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW11:13INITSTATE")
}

record(mbbi, "ACSW:LI20:NW11:13INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:13INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW11:14NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:14POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW11:14POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW11:14POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW11:14POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW11:14POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW11:14POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW11:14POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:14POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW11:14POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(14) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:14POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(14) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:14HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(14) acsw-li20-nw11")
}

record(stringin, "ACSW:LI20:NW11:14NAMESET") {
  field(FLNK, "ACSW:LI20:NW11:14NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW11:14NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(14) acsw-li20-nw11")
  field(DOL, "ACSW:LI20:NW11:14NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW11:14SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(14) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(bo, "ACSW:LI20:NW11:14SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(14) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(stringin, "ACSW:LI20:NW11:14INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:14INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW11:14INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW11:14INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW11:14INITSTATE")
}

record(mbbi, "ACSW:LI20:NW11:14INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:14INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW11:15NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:15POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW11:15POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW11:15POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW11:15POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW11:15POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW11:15POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW11:15POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:15POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW11:15POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(15) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:15POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(15) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:15HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(15) acsw-li20-nw11")
}

record(stringin, "ACSW:LI20:NW11:15NAMESET") {
  field(FLNK, "ACSW:LI20:NW11:15NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW11:15NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(15) acsw-li20-nw11")
  field(DOL, "ACSW:LI20:NW11:15NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW11:15SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(15) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(bo, "ACSW:LI20:NW11:15SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(15) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(stringin, "ACSW:LI20:NW11:15INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:15INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW11:15INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW11:15INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW11:15INITSTATE")
}

record(mbbi, "ACSW:LI20:NW11:15INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:15INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW11:16NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:16POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW11:16POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW11:16POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW11:16POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW11:16POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW11:16POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW11:16POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:16POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW11:16POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(16) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:16POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(16) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:16HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(16) acsw-li20-nw11")
}

record(stringin, "ACSW:LI20:NW11:16NAMESET") {
  field(FLNK, "ACSW:LI20:NW11:16NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW11:16NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(16) acsw-li20-nw11")
  field(DOL, "ACSW:LI20:NW11:16NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW11:16SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(16) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(bo, "ACSW:LI20:NW11:16SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(16) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(stringin, "ACSW:LI20:NW11:16INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:16INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW11:16INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW11:16INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW11:16INITSTATE")
}

record(mbbi, "ACSW:LI20:NW11:16INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:16INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW11:17NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:17POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW11:17POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW11:17POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW11:17POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW11:17POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW11:17POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW11:17POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:17POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW11:17POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(17) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:17POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(17) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:17HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(17) acsw-li20-nw11")
}

record(stringin, "ACSW:LI20:NW11:17NAMESET") {
  field(FLNK, "ACSW:LI20:NW11:17NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW11:17NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(17) acsw-li20-nw11")
  field(DOL, "ACSW:LI20:NW11:17NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW11:17SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(17) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(bo, "ACSW:LI20:NW11:17SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(17) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(stringin, "ACSW:LI20:NW11:17INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:17INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW11:17INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW11:17INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW11:17INITSTATE")
}

record(mbbi, "ACSW:LI20:NW11:17INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:17INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW11:18NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:18POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW11:18POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW11:18POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW11:18POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW11:18POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW11:18POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW11:18POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:18POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW11:18POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(18) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:18POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(18) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:18HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(18) acsw-li20-nw11")
}

record(stringin, "ACSW:LI20:NW11:18NAMESET") {
  field(FLNK, "ACSW:LI20:NW11:18NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW11:18NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(18) acsw-li20-nw11")
  field(DOL, "ACSW:LI20:NW11:18NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW11:18SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(18) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(bo, "ACSW:LI20:NW11:18SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(18) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(stringin, "ACSW:LI20:NW11:18INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:18INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW11:18INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW11:18INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW11:18INITSTATE")
}

record(mbbi, "ACSW:LI20:NW11:18INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:18INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW11:19NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:19POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW11:19POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW11:19POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW11:19POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW11:19POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW11:19POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW11:19POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:19POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW11:19POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(19) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:19POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(19) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:19HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(19) acsw-li20-nw11")
}

record(stringin, "ACSW:LI20:NW11:19NAMESET") {
  field(FLNK, "ACSW:LI20:NW11:19NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW11:19NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(19) acsw-li20-nw11")
  field(DOL, "ACSW:LI20:NW11:19NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW11:19SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(19) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(bo, "ACSW:LI20:NW11:19SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(19) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(stringin, "ACSW:LI20:NW11:19INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:19INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW11:19INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW11:19INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW11:19INITSTATE")
}

record(mbbi, "ACSW:LI20:NW11:19INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:19INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW11:20NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:20POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW11:20POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW11:20POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW11:20POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW11:20POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW11:20POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW11:20POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:20POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW11:20POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(20) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:20POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(20) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:20HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(20) acsw-li20-nw11")
}

record(stringin, "ACSW:LI20:NW11:20NAMESET") {
  field(FLNK, "ACSW:LI20:NW11:20NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW11:20NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(20) acsw-li20-nw11")
  field(DOL, "ACSW:LI20:NW11:20NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW11:20SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(20) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(bo, "ACSW:LI20:NW11:20SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(20) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(stringin, "ACSW:LI20:NW11:20INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:20INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW11:20INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW11:20INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW11:20INITSTATE")
}

record(mbbi, "ACSW:LI20:NW11:20INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:20INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW11:21NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:21POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW11:21POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW11:21POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW11:21POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW11:21POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW11:21POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW11:21POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:21POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW11:21POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(21) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:21POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(21) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:21HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(21) acsw-li20-nw11")
}

record(stringin, "ACSW:LI20:NW11:21NAMESET") {
  field(FLNK, "ACSW:LI20:NW11:21NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW11:21NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(21) acsw-li20-nw11")
  field(DOL, "ACSW:LI20:NW11:21NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW11:21SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(21) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(bo, "ACSW:LI20:NW11:21SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(21) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(stringin, "ACSW:LI20:NW11:21INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:21INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW11:21INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW11:21INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW11:21INITSTATE")
}

record(mbbi, "ACSW:LI20:NW11:21INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:21INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW11:22NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:22POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW11:22POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW11:22POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW11:22POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW11:22POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW11:22POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW11:22POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:22POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW11:22POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(22) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:22POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(22) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:22HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(22) acsw-li20-nw11")
}

record(stringin, "ACSW:LI20:NW11:22NAMESET") {
  field(FLNK, "ACSW:LI20:NW11:22NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW11:22NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(22) acsw-li20-nw11")
  field(DOL, "ACSW:LI20:NW11:22NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW11:22SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(22) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(bo, "ACSW:LI20:NW11:22SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(22) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(stringin, "ACSW:LI20:NW11:22INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:22INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW11:22INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW11:22INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW11:22INITSTATE")
}

record(mbbi, "ACSW:LI20:NW11:22INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:22INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW11:23NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:23POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW11:23POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW11:23POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW11:23POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW11:23POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW11:23POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW11:23POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:23POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW11:23POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(23) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:23POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(23) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:23HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(23) acsw-li20-nw11")
}

record(stringin, "ACSW:LI20:NW11:23NAMESET") {
  field(FLNK, "ACSW:LI20:NW11:23NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW11:23NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(23) acsw-li20-nw11")
  field(DOL, "ACSW:LI20:NW11:23NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW11:23SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(23) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(bo, "ACSW:LI20:NW11:23SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(23) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(stringin, "ACSW:LI20:NW11:23INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:23INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW11:23INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW11:23INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW11:23INITSTATE")
}

record(mbbi, "ACSW:LI20:NW11:23INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:23INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW11:24NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:24POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW11:24POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW11:24POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW11:24POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW11:24POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW11:24POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW11:24POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:24POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW11:24POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(24) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:24POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(24) acsw-li20-nw11")
}

record(bo, "ACSW:LI20:NW11:24HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(24) acsw-li20-nw11")
}

record(stringin, "ACSW:LI20:NW11:24NAMESET") {
  field(FLNK, "ACSW:LI20:NW11:24NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW11:24NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(24) acsw-li20-nw11")
  field(DOL, "ACSW:LI20:NW11:24NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW11:24SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(24) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(bo, "ACSW:LI20:NW11:24SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(24) acsw-li20-nw11")
  field(FLNK, "ACSW:LI20:NW11:GETINIT")
}

record(stringin, "ACSW:LI20:NW11:24INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW11:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW11:24INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW11:24INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW11:24INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW11:24INITSTATE")
}

record(mbbi, "ACSW:LI20:NW11:24INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW11:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW11:24INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW12:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:LI20:NW12) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINFO")
}

record(stringin, "ACSW:LI20:NW12:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:LI20:NW12) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(stringin, "ACSW:LI20:NW12:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:LI20:NW12:NETFWVERSION")
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:LI20:NW12:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:LI20:NW12:SITEID")
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:LI20:NW12:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:LI20:NW12:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState24(ACSW:LI20:NW12) acsw-li20-nw12")
}

record(stringin, "ACSW:LI20:NW12:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState24(ACSW:LI20:NW12) acsw-li20-nw12")
}

record(ai, "ACSW:LI20:NW12:TYPE") {
  field(DESC, "APC 24 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "17")
}

record(stringin, "ACSW:LI20:NW12:LOC") {
  field(PINI, "YES")
  field(VAL, "FKG20-27")
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:LI20:NW12:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-li20-nw12")
}

record(calcout, "ACSW:LI20:NW12:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:LI20:NW12:DISCONN.DISA")
  field(INPB, "ACSW:LI20:NW12:DISCONN.DISV")
  field(INPC, "ACSW:LI20:NW12:GETSTATUS.DISA")
  field(INPD, "ACSW:LI20:NW12:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:LI20:NW12:CONNSTA PP")
}

record(bi, "ACSW:LI20:NW12:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:LI20:NW12:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:LI20:NW12:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:LI20:NW12:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:LI20:NW12:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:LI20:NW12:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:LI20:NW12:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:LI20:NW12:UPTIMEHOUR") {
  field(FLNK, "ACSW:LI20:NW12:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:LI20:NW12:UPTIMEDAY") {
  field(FLNK, "ACSW:LI20:NW12:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:LI20:NW12:UPTIMEMINUTE") {
  field(FLNK, "ACSW:LI20:NW12:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:LI20:NW12:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:1POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW12:1POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW12:1POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW12:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW12:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW12:1POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW12:1POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW12:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-li20-nw12")
}

record(stringin, "ACSW:LI20:NW12:1NAMESET") {
  field(FLNK, "ACSW:LI20:NW12:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW12:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-li20-nw12")
  field(DOL, "ACSW:LI20:NW12:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW12:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(bo, "ACSW:LI20:NW12:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(stringin, "ACSW:LI20:NW12:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW12:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW12:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW12:1INITSTATE")
}

record(mbbi, "ACSW:LI20:NW12:1INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW12:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:2POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW12:2POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW12:2POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW12:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW12:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW12:2POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW12:2POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW12:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-li20-nw12")
}

record(stringin, "ACSW:LI20:NW12:2NAMESET") {
  field(FLNK, "ACSW:LI20:NW12:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW12:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-li20-nw12")
  field(DOL, "ACSW:LI20:NW12:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW12:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(bo, "ACSW:LI20:NW12:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(stringin, "ACSW:LI20:NW12:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW12:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW12:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW12:2INITSTATE")
}

record(mbbi, "ACSW:LI20:NW12:2INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW12:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:3POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW12:3POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW12:3POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW12:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW12:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW12:3POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW12:3POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW12:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-li20-nw12")
}

record(stringin, "ACSW:LI20:NW12:3NAMESET") {
  field(FLNK, "ACSW:LI20:NW12:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW12:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-li20-nw12")
  field(DOL, "ACSW:LI20:NW12:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW12:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(bo, "ACSW:LI20:NW12:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(stringin, "ACSW:LI20:NW12:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW12:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW12:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW12:3INITSTATE")
}

record(mbbi, "ACSW:LI20:NW12:3INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW12:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:4POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW12:4POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW12:4POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW12:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW12:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW12:4POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW12:4POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW12:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-li20-nw12")
}

record(stringin, "ACSW:LI20:NW12:4NAMESET") {
  field(FLNK, "ACSW:LI20:NW12:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW12:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-li20-nw12")
  field(DOL, "ACSW:LI20:NW12:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW12:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(bo, "ACSW:LI20:NW12:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(stringin, "ACSW:LI20:NW12:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW12:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW12:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW12:4INITSTATE")
}

record(mbbi, "ACSW:LI20:NW12:4INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW12:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:5POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW12:5POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW12:5POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW12:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW12:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW12:5POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW12:5POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW12:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-li20-nw12")
}

record(stringin, "ACSW:LI20:NW12:5NAMESET") {
  field(FLNK, "ACSW:LI20:NW12:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW12:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-li20-nw12")
  field(DOL, "ACSW:LI20:NW12:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW12:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(bo, "ACSW:LI20:NW12:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(stringin, "ACSW:LI20:NW12:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW12:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW12:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW12:5INITSTATE")
}

record(mbbi, "ACSW:LI20:NW12:5INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW12:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:6POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW12:6POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW12:6POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW12:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW12:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW12:6POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW12:6POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW12:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-li20-nw12")
}

record(stringin, "ACSW:LI20:NW12:6NAMESET") {
  field(FLNK, "ACSW:LI20:NW12:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW12:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-li20-nw12")
  field(DOL, "ACSW:LI20:NW12:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW12:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(bo, "ACSW:LI20:NW12:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(stringin, "ACSW:LI20:NW12:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW12:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW12:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW12:6INITSTATE")
}

record(mbbi, "ACSW:LI20:NW12:6INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW12:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:7POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW12:7POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW12:7POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW12:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW12:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW12:7POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW12:7POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW12:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-li20-nw12")
}

record(stringin, "ACSW:LI20:NW12:7NAMESET") {
  field(FLNK, "ACSW:LI20:NW12:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW12:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-li20-nw12")
  field(DOL, "ACSW:LI20:NW12:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW12:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(bo, "ACSW:LI20:NW12:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(stringin, "ACSW:LI20:NW12:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW12:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW12:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW12:7INITSTATE")
}

record(mbbi, "ACSW:LI20:NW12:7INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW12:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:8POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW12:8POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW12:8POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW12:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW12:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW12:8POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW12:8POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW12:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-li20-nw12")
}

record(stringin, "ACSW:LI20:NW12:8NAMESET") {
  field(FLNK, "ACSW:LI20:NW12:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW12:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-li20-nw12")
  field(DOL, "ACSW:LI20:NW12:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW12:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(bo, "ACSW:LI20:NW12:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(stringin, "ACSW:LI20:NW12:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW12:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW12:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW12:8INITSTATE")
}

record(mbbi, "ACSW:LI20:NW12:8INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW12:9NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:9POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW12:9POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW12:9POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW12:9POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW12:9POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW12:9POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW12:9POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:9POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW12:9POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(9) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:9POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(9) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:9HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(9) acsw-li20-nw12")
}

record(stringin, "ACSW:LI20:NW12:9NAMESET") {
  field(FLNK, "ACSW:LI20:NW12:9NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW12:9NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(9) acsw-li20-nw12")
  field(DOL, "ACSW:LI20:NW12:9NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW12:9SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(9) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(bo, "ACSW:LI20:NW12:9SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(9) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(stringin, "ACSW:LI20:NW12:9INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:9INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW12:9INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW12:9INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW12:9INITSTATE")
}

record(mbbi, "ACSW:LI20:NW12:9INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:9INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW12:10NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:10POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW12:10POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW12:10POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW12:10POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW12:10POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW12:10POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW12:10POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:10POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW12:10POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(10) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:10POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(10) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:10HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(10) acsw-li20-nw12")
}

record(stringin, "ACSW:LI20:NW12:10NAMESET") {
  field(FLNK, "ACSW:LI20:NW12:10NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW12:10NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(10) acsw-li20-nw12")
  field(DOL, "ACSW:LI20:NW12:10NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW12:10SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(10) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(bo, "ACSW:LI20:NW12:10SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(10) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(stringin, "ACSW:LI20:NW12:10INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:10INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW12:10INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW12:10INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW12:10INITSTATE")
}

record(mbbi, "ACSW:LI20:NW12:10INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:10INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW12:11NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:11POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW12:11POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW12:11POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW12:11POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW12:11POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW12:11POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW12:11POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:11POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW12:11POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(11) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:11POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(11) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:11HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(11) acsw-li20-nw12")
}

record(stringin, "ACSW:LI20:NW12:11NAMESET") {
  field(FLNK, "ACSW:LI20:NW12:11NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW12:11NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(11) acsw-li20-nw12")
  field(DOL, "ACSW:LI20:NW12:11NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW12:11SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(11) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(bo, "ACSW:LI20:NW12:11SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(11) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(stringin, "ACSW:LI20:NW12:11INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:11INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW12:11INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW12:11INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW12:11INITSTATE")
}

record(mbbi, "ACSW:LI20:NW12:11INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:11INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW12:12NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:12POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW12:12POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW12:12POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW12:12POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW12:12POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW12:12POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW12:12POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:12POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW12:12POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(12) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:12POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(12) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:12HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(12) acsw-li20-nw12")
}

record(stringin, "ACSW:LI20:NW12:12NAMESET") {
  field(FLNK, "ACSW:LI20:NW12:12NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW12:12NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(12) acsw-li20-nw12")
  field(DOL, "ACSW:LI20:NW12:12NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW12:12SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(12) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(bo, "ACSW:LI20:NW12:12SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(12) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(stringin, "ACSW:LI20:NW12:12INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:12INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW12:12INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW12:12INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW12:12INITSTATE")
}

record(mbbi, "ACSW:LI20:NW12:12INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:12INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW12:13NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:13POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW12:13POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW12:13POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW12:13POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW12:13POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW12:13POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW12:13POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:13POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW12:13POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(13) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:13POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(13) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:13HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(13) acsw-li20-nw12")
}

record(stringin, "ACSW:LI20:NW12:13NAMESET") {
  field(FLNK, "ACSW:LI20:NW12:13NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW12:13NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(13) acsw-li20-nw12")
  field(DOL, "ACSW:LI20:NW12:13NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW12:13SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(13) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(bo, "ACSW:LI20:NW12:13SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(13) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(stringin, "ACSW:LI20:NW12:13INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:13INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW12:13INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW12:13INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW12:13INITSTATE")
}

record(mbbi, "ACSW:LI20:NW12:13INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:13INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW12:14NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:14POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW12:14POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW12:14POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW12:14POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW12:14POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW12:14POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW12:14POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:14POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW12:14POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(14) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:14POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(14) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:14HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(14) acsw-li20-nw12")
}

record(stringin, "ACSW:LI20:NW12:14NAMESET") {
  field(FLNK, "ACSW:LI20:NW12:14NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW12:14NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(14) acsw-li20-nw12")
  field(DOL, "ACSW:LI20:NW12:14NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW12:14SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(14) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(bo, "ACSW:LI20:NW12:14SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(14) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(stringin, "ACSW:LI20:NW12:14INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:14INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW12:14INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW12:14INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW12:14INITSTATE")
}

record(mbbi, "ACSW:LI20:NW12:14INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:14INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW12:15NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:15POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW12:15POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW12:15POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW12:15POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW12:15POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW12:15POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW12:15POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:15POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW12:15POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(15) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:15POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(15) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:15HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(15) acsw-li20-nw12")
}

record(stringin, "ACSW:LI20:NW12:15NAMESET") {
  field(FLNK, "ACSW:LI20:NW12:15NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW12:15NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(15) acsw-li20-nw12")
  field(DOL, "ACSW:LI20:NW12:15NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW12:15SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(15) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(bo, "ACSW:LI20:NW12:15SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(15) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(stringin, "ACSW:LI20:NW12:15INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:15INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW12:15INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW12:15INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW12:15INITSTATE")
}

record(mbbi, "ACSW:LI20:NW12:15INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:15INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW12:16NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:16POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW12:16POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW12:16POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW12:16POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW12:16POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW12:16POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW12:16POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:16POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW12:16POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(16) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:16POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(16) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:16HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(16) acsw-li20-nw12")
}

record(stringin, "ACSW:LI20:NW12:16NAMESET") {
  field(FLNK, "ACSW:LI20:NW12:16NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW12:16NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(16) acsw-li20-nw12")
  field(DOL, "ACSW:LI20:NW12:16NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW12:16SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(16) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(bo, "ACSW:LI20:NW12:16SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(16) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(stringin, "ACSW:LI20:NW12:16INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:16INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW12:16INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW12:16INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW12:16INITSTATE")
}

record(mbbi, "ACSW:LI20:NW12:16INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:16INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW12:17NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:17POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW12:17POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW12:17POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW12:17POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW12:17POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW12:17POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW12:17POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:17POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW12:17POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(17) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:17POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(17) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:17HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(17) acsw-li20-nw12")
}

record(stringin, "ACSW:LI20:NW12:17NAMESET") {
  field(FLNK, "ACSW:LI20:NW12:17NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW12:17NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(17) acsw-li20-nw12")
  field(DOL, "ACSW:LI20:NW12:17NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW12:17SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(17) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(bo, "ACSW:LI20:NW12:17SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(17) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(stringin, "ACSW:LI20:NW12:17INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:17INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW12:17INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW12:17INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW12:17INITSTATE")
}

record(mbbi, "ACSW:LI20:NW12:17INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:17INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW12:18NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:18POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW12:18POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW12:18POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW12:18POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW12:18POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW12:18POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW12:18POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:18POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW12:18POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(18) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:18POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(18) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:18HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(18) acsw-li20-nw12")
}

record(stringin, "ACSW:LI20:NW12:18NAMESET") {
  field(FLNK, "ACSW:LI20:NW12:18NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW12:18NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(18) acsw-li20-nw12")
  field(DOL, "ACSW:LI20:NW12:18NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW12:18SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(18) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(bo, "ACSW:LI20:NW12:18SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(18) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(stringin, "ACSW:LI20:NW12:18INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:18INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW12:18INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW12:18INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW12:18INITSTATE")
}

record(mbbi, "ACSW:LI20:NW12:18INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:18INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW12:19NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:19POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW12:19POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW12:19POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW12:19POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW12:19POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW12:19POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW12:19POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:19POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW12:19POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(19) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:19POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(19) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:19HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(19) acsw-li20-nw12")
}

record(stringin, "ACSW:LI20:NW12:19NAMESET") {
  field(FLNK, "ACSW:LI20:NW12:19NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW12:19NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(19) acsw-li20-nw12")
  field(DOL, "ACSW:LI20:NW12:19NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW12:19SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(19) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(bo, "ACSW:LI20:NW12:19SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(19) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(stringin, "ACSW:LI20:NW12:19INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:19INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW12:19INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW12:19INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW12:19INITSTATE")
}

record(mbbi, "ACSW:LI20:NW12:19INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:19INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW12:20NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:20POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW12:20POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW12:20POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW12:20POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW12:20POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW12:20POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW12:20POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:20POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW12:20POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(20) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:20POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(20) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:20HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(20) acsw-li20-nw12")
}

record(stringin, "ACSW:LI20:NW12:20NAMESET") {
  field(FLNK, "ACSW:LI20:NW12:20NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW12:20NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(20) acsw-li20-nw12")
  field(DOL, "ACSW:LI20:NW12:20NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW12:20SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(20) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(bo, "ACSW:LI20:NW12:20SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(20) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(stringin, "ACSW:LI20:NW12:20INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:20INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW12:20INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW12:20INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW12:20INITSTATE")
}

record(mbbi, "ACSW:LI20:NW12:20INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:20INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW12:21NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:21POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW12:21POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW12:21POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW12:21POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW12:21POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW12:21POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW12:21POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:21POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW12:21POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(21) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:21POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(21) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:21HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(21) acsw-li20-nw12")
}

record(stringin, "ACSW:LI20:NW12:21NAMESET") {
  field(FLNK, "ACSW:LI20:NW12:21NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW12:21NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(21) acsw-li20-nw12")
  field(DOL, "ACSW:LI20:NW12:21NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW12:21SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(21) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(bo, "ACSW:LI20:NW12:21SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(21) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(stringin, "ACSW:LI20:NW12:21INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:21INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW12:21INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW12:21INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW12:21INITSTATE")
}

record(mbbi, "ACSW:LI20:NW12:21INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:21INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW12:22NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:22POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW12:22POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW12:22POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW12:22POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW12:22POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW12:22POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW12:22POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:22POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW12:22POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(22) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:22POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(22) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:22HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(22) acsw-li20-nw12")
}

record(stringin, "ACSW:LI20:NW12:22NAMESET") {
  field(FLNK, "ACSW:LI20:NW12:22NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW12:22NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(22) acsw-li20-nw12")
  field(DOL, "ACSW:LI20:NW12:22NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW12:22SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(22) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(bo, "ACSW:LI20:NW12:22SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(22) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(stringin, "ACSW:LI20:NW12:22INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:22INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW12:22INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW12:22INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW12:22INITSTATE")
}

record(mbbi, "ACSW:LI20:NW12:22INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:22INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW12:23NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:23POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW12:23POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW12:23POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW12:23POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW12:23POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW12:23POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW12:23POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:23POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW12:23POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(23) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:23POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(23) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:23HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(23) acsw-li20-nw12")
}

record(stringin, "ACSW:LI20:NW12:23NAMESET") {
  field(FLNK, "ACSW:LI20:NW12:23NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW12:23NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(23) acsw-li20-nw12")
  field(DOL, "ACSW:LI20:NW12:23NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW12:23SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(23) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(bo, "ACSW:LI20:NW12:23SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(23) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(stringin, "ACSW:LI20:NW12:23INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:23INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW12:23INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW12:23INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW12:23INITSTATE")
}

record(mbbi, "ACSW:LI20:NW12:23INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:23INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW12:24NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:24POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW12:24POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW12:24POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW12:24POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW12:24POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW12:24POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW12:24POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:24POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW12:24POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(24) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:24POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(24) acsw-li20-nw12")
}

record(bo, "ACSW:LI20:NW12:24HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(24) acsw-li20-nw12")
}

record(stringin, "ACSW:LI20:NW12:24NAMESET") {
  field(FLNK, "ACSW:LI20:NW12:24NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW12:24NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(24) acsw-li20-nw12")
  field(DOL, "ACSW:LI20:NW12:24NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW12:24SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(24) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(bo, "ACSW:LI20:NW12:24SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(24) acsw-li20-nw12")
  field(FLNK, "ACSW:LI20:NW12:GETINIT")
}

record(stringin, "ACSW:LI20:NW12:24INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW12:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW12:24INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW12:24INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW12:24INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW12:24INITSTATE")
}

record(mbbi, "ACSW:LI20:NW12:24INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW12:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW12:24INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW13:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:LI20:NW13) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINFO")
}

record(stringin, "ACSW:LI20:NW13:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:LI20:NW13) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(stringin, "ACSW:LI20:NW13:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:LI20:NW13:NETFWVERSION")
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:LI20:NW13:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:LI20:NW13:SITEID")
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:LI20:NW13:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:LI20:NW13:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState24(ACSW:LI20:NW13) acsw-li20-nw13")
}

record(stringin, "ACSW:LI20:NW13:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState24(ACSW:LI20:NW13) acsw-li20-nw13")
}

record(ai, "ACSW:LI20:NW13:TYPE") {
  field(DESC, "APC 24 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "17")
}

record(stringin, "ACSW:LI20:NW13:LOC") {
  field(PINI, "YES")
  field(VAL, "FKG20-20")
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:LI20:NW13:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-li20-nw13")
}

record(calcout, "ACSW:LI20:NW13:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:LI20:NW13:DISCONN.DISA")
  field(INPB, "ACSW:LI20:NW13:DISCONN.DISV")
  field(INPC, "ACSW:LI20:NW13:GETSTATUS.DISA")
  field(INPD, "ACSW:LI20:NW13:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:LI20:NW13:CONNSTA PP")
}

record(bi, "ACSW:LI20:NW13:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:LI20:NW13:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:LI20:NW13:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:LI20:NW13:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:LI20:NW13:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:LI20:NW13:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:LI20:NW13:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:LI20:NW13:UPTIMEHOUR") {
  field(FLNK, "ACSW:LI20:NW13:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:LI20:NW13:UPTIMEDAY") {
  field(FLNK, "ACSW:LI20:NW13:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:LI20:NW13:UPTIMEMINUTE") {
  field(FLNK, "ACSW:LI20:NW13:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:LI20:NW13:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:1POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW13:1POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW13:1POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW13:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW13:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW13:1POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW13:1POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW13:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-li20-nw13")
}

record(stringin, "ACSW:LI20:NW13:1NAMESET") {
  field(FLNK, "ACSW:LI20:NW13:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW13:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-li20-nw13")
  field(DOL, "ACSW:LI20:NW13:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW13:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(bo, "ACSW:LI20:NW13:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(stringin, "ACSW:LI20:NW13:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW13:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW13:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW13:1INITSTATE")
}

record(mbbi, "ACSW:LI20:NW13:1INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW13:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:2POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW13:2POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW13:2POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW13:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW13:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW13:2POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW13:2POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW13:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-li20-nw13")
}

record(stringin, "ACSW:LI20:NW13:2NAMESET") {
  field(FLNK, "ACSW:LI20:NW13:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW13:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-li20-nw13")
  field(DOL, "ACSW:LI20:NW13:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW13:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(bo, "ACSW:LI20:NW13:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(stringin, "ACSW:LI20:NW13:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW13:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW13:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW13:2INITSTATE")
}

record(mbbi, "ACSW:LI20:NW13:2INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW13:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:3POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW13:3POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW13:3POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW13:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW13:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW13:3POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW13:3POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW13:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-li20-nw13")
}

record(stringin, "ACSW:LI20:NW13:3NAMESET") {
  field(FLNK, "ACSW:LI20:NW13:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW13:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-li20-nw13")
  field(DOL, "ACSW:LI20:NW13:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW13:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(bo, "ACSW:LI20:NW13:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(stringin, "ACSW:LI20:NW13:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW13:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW13:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW13:3INITSTATE")
}

record(mbbi, "ACSW:LI20:NW13:3INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW13:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:4POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW13:4POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW13:4POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW13:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW13:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW13:4POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW13:4POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW13:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-li20-nw13")
}

record(stringin, "ACSW:LI20:NW13:4NAMESET") {
  field(FLNK, "ACSW:LI20:NW13:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW13:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-li20-nw13")
  field(DOL, "ACSW:LI20:NW13:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW13:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(bo, "ACSW:LI20:NW13:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(stringin, "ACSW:LI20:NW13:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW13:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW13:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW13:4INITSTATE")
}

record(mbbi, "ACSW:LI20:NW13:4INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW13:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:5POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW13:5POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW13:5POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW13:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW13:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW13:5POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW13:5POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW13:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-li20-nw13")
}

record(stringin, "ACSW:LI20:NW13:5NAMESET") {
  field(FLNK, "ACSW:LI20:NW13:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW13:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-li20-nw13")
  field(DOL, "ACSW:LI20:NW13:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW13:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(bo, "ACSW:LI20:NW13:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(stringin, "ACSW:LI20:NW13:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW13:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW13:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW13:5INITSTATE")
}

record(mbbi, "ACSW:LI20:NW13:5INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW13:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:6POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW13:6POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW13:6POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW13:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW13:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW13:6POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW13:6POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW13:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-li20-nw13")
}

record(stringin, "ACSW:LI20:NW13:6NAMESET") {
  field(FLNK, "ACSW:LI20:NW13:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW13:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-li20-nw13")
  field(DOL, "ACSW:LI20:NW13:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW13:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(bo, "ACSW:LI20:NW13:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(stringin, "ACSW:LI20:NW13:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW13:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW13:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW13:6INITSTATE")
}

record(mbbi, "ACSW:LI20:NW13:6INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW13:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:7POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW13:7POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW13:7POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW13:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW13:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW13:7POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW13:7POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW13:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-li20-nw13")
}

record(stringin, "ACSW:LI20:NW13:7NAMESET") {
  field(FLNK, "ACSW:LI20:NW13:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW13:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-li20-nw13")
  field(DOL, "ACSW:LI20:NW13:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW13:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(bo, "ACSW:LI20:NW13:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(stringin, "ACSW:LI20:NW13:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW13:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW13:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW13:7INITSTATE")
}

record(mbbi, "ACSW:LI20:NW13:7INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW13:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:8POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW13:8POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW13:8POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW13:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW13:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW13:8POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW13:8POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW13:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-li20-nw13")
}

record(stringin, "ACSW:LI20:NW13:8NAMESET") {
  field(FLNK, "ACSW:LI20:NW13:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW13:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-li20-nw13")
  field(DOL, "ACSW:LI20:NW13:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW13:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(bo, "ACSW:LI20:NW13:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(stringin, "ACSW:LI20:NW13:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW13:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW13:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW13:8INITSTATE")
}

record(mbbi, "ACSW:LI20:NW13:8INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW13:9NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:9POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW13:9POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW13:9POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW13:9POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW13:9POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW13:9POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW13:9POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:9POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW13:9POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(9) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:9POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(9) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:9HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(9) acsw-li20-nw13")
}

record(stringin, "ACSW:LI20:NW13:9NAMESET") {
  field(FLNK, "ACSW:LI20:NW13:9NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW13:9NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(9) acsw-li20-nw13")
  field(DOL, "ACSW:LI20:NW13:9NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW13:9SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(9) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(bo, "ACSW:LI20:NW13:9SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(9) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(stringin, "ACSW:LI20:NW13:9INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:9INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW13:9INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW13:9INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW13:9INITSTATE")
}

record(mbbi, "ACSW:LI20:NW13:9INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:9INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW13:10NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:10POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW13:10POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW13:10POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW13:10POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW13:10POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW13:10POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW13:10POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:10POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW13:10POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(10) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:10POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(10) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:10HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(10) acsw-li20-nw13")
}

record(stringin, "ACSW:LI20:NW13:10NAMESET") {
  field(FLNK, "ACSW:LI20:NW13:10NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW13:10NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(10) acsw-li20-nw13")
  field(DOL, "ACSW:LI20:NW13:10NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW13:10SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(10) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(bo, "ACSW:LI20:NW13:10SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(10) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(stringin, "ACSW:LI20:NW13:10INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:10INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW13:10INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW13:10INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW13:10INITSTATE")
}

record(mbbi, "ACSW:LI20:NW13:10INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:10INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW13:11NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:11POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW13:11POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW13:11POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW13:11POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW13:11POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW13:11POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW13:11POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:11POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW13:11POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(11) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:11POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(11) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:11HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(11) acsw-li20-nw13")
}

record(stringin, "ACSW:LI20:NW13:11NAMESET") {
  field(FLNK, "ACSW:LI20:NW13:11NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW13:11NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(11) acsw-li20-nw13")
  field(DOL, "ACSW:LI20:NW13:11NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW13:11SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(11) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(bo, "ACSW:LI20:NW13:11SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(11) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(stringin, "ACSW:LI20:NW13:11INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:11INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW13:11INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW13:11INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW13:11INITSTATE")
}

record(mbbi, "ACSW:LI20:NW13:11INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:11INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW13:12NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:12POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW13:12POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW13:12POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW13:12POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW13:12POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW13:12POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW13:12POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:12POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW13:12POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(12) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:12POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(12) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:12HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(12) acsw-li20-nw13")
}

record(stringin, "ACSW:LI20:NW13:12NAMESET") {
  field(FLNK, "ACSW:LI20:NW13:12NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW13:12NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(12) acsw-li20-nw13")
  field(DOL, "ACSW:LI20:NW13:12NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW13:12SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(12) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(bo, "ACSW:LI20:NW13:12SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(12) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(stringin, "ACSW:LI20:NW13:12INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:12INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW13:12INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW13:12INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW13:12INITSTATE")
}

record(mbbi, "ACSW:LI20:NW13:12INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:12INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW13:13NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:13POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW13:13POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW13:13POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW13:13POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW13:13POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW13:13POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW13:13POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:13POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW13:13POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(13) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:13POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(13) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:13HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(13) acsw-li20-nw13")
}

record(stringin, "ACSW:LI20:NW13:13NAMESET") {
  field(FLNK, "ACSW:LI20:NW13:13NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW13:13NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(13) acsw-li20-nw13")
  field(DOL, "ACSW:LI20:NW13:13NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW13:13SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(13) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(bo, "ACSW:LI20:NW13:13SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(13) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(stringin, "ACSW:LI20:NW13:13INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:13INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW13:13INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW13:13INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW13:13INITSTATE")
}

record(mbbi, "ACSW:LI20:NW13:13INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:13INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW13:14NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:14POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW13:14POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW13:14POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW13:14POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW13:14POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW13:14POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW13:14POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:14POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW13:14POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(14) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:14POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(14) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:14HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(14) acsw-li20-nw13")
}

record(stringin, "ACSW:LI20:NW13:14NAMESET") {
  field(FLNK, "ACSW:LI20:NW13:14NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW13:14NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(14) acsw-li20-nw13")
  field(DOL, "ACSW:LI20:NW13:14NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW13:14SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(14) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(bo, "ACSW:LI20:NW13:14SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(14) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(stringin, "ACSW:LI20:NW13:14INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:14INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW13:14INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW13:14INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW13:14INITSTATE")
}

record(mbbi, "ACSW:LI20:NW13:14INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:14INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW13:15NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:15POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW13:15POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW13:15POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW13:15POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW13:15POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW13:15POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW13:15POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:15POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW13:15POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(15) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:15POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(15) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:15HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(15) acsw-li20-nw13")
}

record(stringin, "ACSW:LI20:NW13:15NAMESET") {
  field(FLNK, "ACSW:LI20:NW13:15NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW13:15NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(15) acsw-li20-nw13")
  field(DOL, "ACSW:LI20:NW13:15NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW13:15SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(15) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(bo, "ACSW:LI20:NW13:15SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(15) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(stringin, "ACSW:LI20:NW13:15INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:15INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW13:15INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW13:15INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW13:15INITSTATE")
}

record(mbbi, "ACSW:LI20:NW13:15INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:15INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW13:16NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:16POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW13:16POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW13:16POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW13:16POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW13:16POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW13:16POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW13:16POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:16POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW13:16POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(16) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:16POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(16) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:16HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(16) acsw-li20-nw13")
}

record(stringin, "ACSW:LI20:NW13:16NAMESET") {
  field(FLNK, "ACSW:LI20:NW13:16NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW13:16NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(16) acsw-li20-nw13")
  field(DOL, "ACSW:LI20:NW13:16NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW13:16SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(16) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(bo, "ACSW:LI20:NW13:16SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(16) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(stringin, "ACSW:LI20:NW13:16INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:16INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW13:16INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW13:16INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW13:16INITSTATE")
}

record(mbbi, "ACSW:LI20:NW13:16INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:16INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW13:17NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:17POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW13:17POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW13:17POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW13:17POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW13:17POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW13:17POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW13:17POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:17POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW13:17POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(17) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:17POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(17) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:17HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(17) acsw-li20-nw13")
}

record(stringin, "ACSW:LI20:NW13:17NAMESET") {
  field(FLNK, "ACSW:LI20:NW13:17NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW13:17NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(17) acsw-li20-nw13")
  field(DOL, "ACSW:LI20:NW13:17NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW13:17SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(17) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(bo, "ACSW:LI20:NW13:17SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(17) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(stringin, "ACSW:LI20:NW13:17INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:17INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW13:17INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW13:17INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW13:17INITSTATE")
}

record(mbbi, "ACSW:LI20:NW13:17INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:17INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW13:18NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:18POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW13:18POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW13:18POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW13:18POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW13:18POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW13:18POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW13:18POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:18POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW13:18POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(18) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:18POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(18) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:18HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(18) acsw-li20-nw13")
}

record(stringin, "ACSW:LI20:NW13:18NAMESET") {
  field(FLNK, "ACSW:LI20:NW13:18NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW13:18NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(18) acsw-li20-nw13")
  field(DOL, "ACSW:LI20:NW13:18NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW13:18SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(18) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(bo, "ACSW:LI20:NW13:18SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(18) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(stringin, "ACSW:LI20:NW13:18INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:18INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW13:18INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW13:18INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW13:18INITSTATE")
}

record(mbbi, "ACSW:LI20:NW13:18INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:18INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW13:19NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:19POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW13:19POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW13:19POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW13:19POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW13:19POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW13:19POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW13:19POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:19POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW13:19POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(19) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:19POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(19) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:19HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(19) acsw-li20-nw13")
}

record(stringin, "ACSW:LI20:NW13:19NAMESET") {
  field(FLNK, "ACSW:LI20:NW13:19NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW13:19NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(19) acsw-li20-nw13")
  field(DOL, "ACSW:LI20:NW13:19NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW13:19SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(19) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(bo, "ACSW:LI20:NW13:19SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(19) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(stringin, "ACSW:LI20:NW13:19INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:19INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW13:19INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW13:19INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW13:19INITSTATE")
}

record(mbbi, "ACSW:LI20:NW13:19INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:19INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW13:20NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:20POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW13:20POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW13:20POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW13:20POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW13:20POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW13:20POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW13:20POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:20POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW13:20POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(20) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:20POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(20) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:20HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(20) acsw-li20-nw13")
}

record(stringin, "ACSW:LI20:NW13:20NAMESET") {
  field(FLNK, "ACSW:LI20:NW13:20NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW13:20NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(20) acsw-li20-nw13")
  field(DOL, "ACSW:LI20:NW13:20NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW13:20SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(20) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(bo, "ACSW:LI20:NW13:20SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(20) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(stringin, "ACSW:LI20:NW13:20INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:20INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW13:20INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW13:20INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW13:20INITSTATE")
}

record(mbbi, "ACSW:LI20:NW13:20INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:20INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW13:21NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:21POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW13:21POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW13:21POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW13:21POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW13:21POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW13:21POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW13:21POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:21POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW13:21POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(21) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:21POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(21) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:21HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(21) acsw-li20-nw13")
}

record(stringin, "ACSW:LI20:NW13:21NAMESET") {
  field(FLNK, "ACSW:LI20:NW13:21NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW13:21NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(21) acsw-li20-nw13")
  field(DOL, "ACSW:LI20:NW13:21NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW13:21SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(21) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(bo, "ACSW:LI20:NW13:21SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(21) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(stringin, "ACSW:LI20:NW13:21INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:21INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW13:21INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW13:21INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW13:21INITSTATE")
}

record(mbbi, "ACSW:LI20:NW13:21INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:21INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW13:22NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:22POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW13:22POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW13:22POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW13:22POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW13:22POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW13:22POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW13:22POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:22POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW13:22POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(22) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:22POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(22) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:22HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(22) acsw-li20-nw13")
}

record(stringin, "ACSW:LI20:NW13:22NAMESET") {
  field(FLNK, "ACSW:LI20:NW13:22NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW13:22NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(22) acsw-li20-nw13")
  field(DOL, "ACSW:LI20:NW13:22NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW13:22SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(22) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(bo, "ACSW:LI20:NW13:22SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(22) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(stringin, "ACSW:LI20:NW13:22INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:22INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW13:22INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW13:22INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW13:22INITSTATE")
}

record(mbbi, "ACSW:LI20:NW13:22INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:22INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW13:23NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:23POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW13:23POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW13:23POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW13:23POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW13:23POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW13:23POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW13:23POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:23POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW13:23POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(23) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:23POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(23) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:23HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(23) acsw-li20-nw13")
}

record(stringin, "ACSW:LI20:NW13:23NAMESET") {
  field(FLNK, "ACSW:LI20:NW13:23NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW13:23NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(23) acsw-li20-nw13")
  field(DOL, "ACSW:LI20:NW13:23NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW13:23SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(23) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(bo, "ACSW:LI20:NW13:23SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(23) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(stringin, "ACSW:LI20:NW13:23INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:23INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW13:23INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW13:23INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW13:23INITSTATE")
}

record(mbbi, "ACSW:LI20:NW13:23INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:23INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW13:24NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:24POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW13:24POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW13:24POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW13:24POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW13:24POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW13:24POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW13:24POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:24POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW13:24POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(24) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:24POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(24) acsw-li20-nw13")
}

record(bo, "ACSW:LI20:NW13:24HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(24) acsw-li20-nw13")
}

record(stringin, "ACSW:LI20:NW13:24NAMESET") {
  field(FLNK, "ACSW:LI20:NW13:24NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW13:24NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(24) acsw-li20-nw13")
  field(DOL, "ACSW:LI20:NW13:24NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW13:24SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(24) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(bo, "ACSW:LI20:NW13:24SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(24) acsw-li20-nw13")
  field(FLNK, "ACSW:LI20:NW13:GETINIT")
}

record(stringin, "ACSW:LI20:NW13:24INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW13:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW13:24INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW13:24INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW13:24INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW13:24INITSTATE")
}

record(mbbi, "ACSW:LI20:NW13:24INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW13:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW13:24INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW14:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:LI20:NW14) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINFO")
}

record(stringin, "ACSW:LI20:NW14:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:LI20:NW14) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(stringin, "ACSW:LI20:NW14:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:LI20:NW14:NETFWVERSION")
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:LI20:NW14:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:LI20:NW14:SITEID")
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:LI20:NW14:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:LI20:NW14:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState24(ACSW:LI20:NW14) acsw-li20-nw14")
}

record(stringin, "ACSW:LI20:NW14:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState24(ACSW:LI20:NW14) acsw-li20-nw14")
}

record(ai, "ACSW:LI20:NW14:TYPE") {
  field(DESC, "APC 24 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "17")
}

record(stringin, "ACSW:LI20:NW14:LOC") {
  field(PINI, "YES")
  field(VAL, "FKG20-20")
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:LI20:NW14:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-li20-nw14")
}

record(calcout, "ACSW:LI20:NW14:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:LI20:NW14:DISCONN.DISA")
  field(INPB, "ACSW:LI20:NW14:DISCONN.DISV")
  field(INPC, "ACSW:LI20:NW14:GETSTATUS.DISA")
  field(INPD, "ACSW:LI20:NW14:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:LI20:NW14:CONNSTA PP")
}

record(bi, "ACSW:LI20:NW14:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:LI20:NW14:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:LI20:NW14:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:LI20:NW14:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:LI20:NW14:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:LI20:NW14:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:LI20:NW14:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:LI20:NW14:UPTIMEHOUR") {
  field(FLNK, "ACSW:LI20:NW14:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:LI20:NW14:UPTIMEDAY") {
  field(FLNK, "ACSW:LI20:NW14:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:LI20:NW14:UPTIMEMINUTE") {
  field(FLNK, "ACSW:LI20:NW14:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:LI20:NW14:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:1POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW14:1POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW14:1POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW14:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW14:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW14:1POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW14:1POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW14:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-li20-nw14")
}

record(stringin, "ACSW:LI20:NW14:1NAMESET") {
  field(FLNK, "ACSW:LI20:NW14:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW14:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-li20-nw14")
  field(DOL, "ACSW:LI20:NW14:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW14:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(bo, "ACSW:LI20:NW14:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(stringin, "ACSW:LI20:NW14:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW14:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW14:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW14:1INITSTATE")
}

record(mbbi, "ACSW:LI20:NW14:1INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW14:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:2POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW14:2POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW14:2POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW14:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW14:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW14:2POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW14:2POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW14:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-li20-nw14")
}

record(stringin, "ACSW:LI20:NW14:2NAMESET") {
  field(FLNK, "ACSW:LI20:NW14:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW14:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-li20-nw14")
  field(DOL, "ACSW:LI20:NW14:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW14:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(bo, "ACSW:LI20:NW14:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(stringin, "ACSW:LI20:NW14:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW14:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW14:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW14:2INITSTATE")
}

record(mbbi, "ACSW:LI20:NW14:2INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW14:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:3POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW14:3POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW14:3POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW14:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW14:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW14:3POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW14:3POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW14:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-li20-nw14")
}

record(stringin, "ACSW:LI20:NW14:3NAMESET") {
  field(FLNK, "ACSW:LI20:NW14:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW14:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-li20-nw14")
  field(DOL, "ACSW:LI20:NW14:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW14:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(bo, "ACSW:LI20:NW14:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(stringin, "ACSW:LI20:NW14:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW14:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW14:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW14:3INITSTATE")
}

record(mbbi, "ACSW:LI20:NW14:3INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW14:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:4POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW14:4POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW14:4POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW14:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW14:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW14:4POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW14:4POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW14:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-li20-nw14")
}

record(stringin, "ACSW:LI20:NW14:4NAMESET") {
  field(FLNK, "ACSW:LI20:NW14:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW14:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-li20-nw14")
  field(DOL, "ACSW:LI20:NW14:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW14:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(bo, "ACSW:LI20:NW14:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(stringin, "ACSW:LI20:NW14:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW14:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW14:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW14:4INITSTATE")
}

record(mbbi, "ACSW:LI20:NW14:4INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW14:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:5POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW14:5POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW14:5POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW14:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW14:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW14:5POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW14:5POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW14:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-li20-nw14")
}

record(stringin, "ACSW:LI20:NW14:5NAMESET") {
  field(FLNK, "ACSW:LI20:NW14:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW14:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-li20-nw14")
  field(DOL, "ACSW:LI20:NW14:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW14:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(bo, "ACSW:LI20:NW14:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(stringin, "ACSW:LI20:NW14:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW14:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW14:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW14:5INITSTATE")
}

record(mbbi, "ACSW:LI20:NW14:5INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW14:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:6POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW14:6POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW14:6POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW14:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW14:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW14:6POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW14:6POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW14:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-li20-nw14")
}

record(stringin, "ACSW:LI20:NW14:6NAMESET") {
  field(FLNK, "ACSW:LI20:NW14:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW14:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-li20-nw14")
  field(DOL, "ACSW:LI20:NW14:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW14:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(bo, "ACSW:LI20:NW14:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(stringin, "ACSW:LI20:NW14:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW14:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW14:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW14:6INITSTATE")
}

record(mbbi, "ACSW:LI20:NW14:6INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW14:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:7POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW14:7POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW14:7POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW14:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW14:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW14:7POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW14:7POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW14:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-li20-nw14")
}

record(stringin, "ACSW:LI20:NW14:7NAMESET") {
  field(FLNK, "ACSW:LI20:NW14:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW14:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-li20-nw14")
  field(DOL, "ACSW:LI20:NW14:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW14:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(bo, "ACSW:LI20:NW14:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(stringin, "ACSW:LI20:NW14:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW14:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW14:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW14:7INITSTATE")
}

record(mbbi, "ACSW:LI20:NW14:7INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW14:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:8POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW14:8POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW14:8POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW14:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW14:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW14:8POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW14:8POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW14:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-li20-nw14")
}

record(stringin, "ACSW:LI20:NW14:8NAMESET") {
  field(FLNK, "ACSW:LI20:NW14:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW14:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-li20-nw14")
  field(DOL, "ACSW:LI20:NW14:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW14:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(bo, "ACSW:LI20:NW14:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(stringin, "ACSW:LI20:NW14:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW14:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW14:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW14:8INITSTATE")
}

record(mbbi, "ACSW:LI20:NW14:8INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW14:9NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:9POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW14:9POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW14:9POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW14:9POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW14:9POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW14:9POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW14:9POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:9POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW14:9POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(9) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:9POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(9) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:9HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(9) acsw-li20-nw14")
}

record(stringin, "ACSW:LI20:NW14:9NAMESET") {
  field(FLNK, "ACSW:LI20:NW14:9NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW14:9NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(9) acsw-li20-nw14")
  field(DOL, "ACSW:LI20:NW14:9NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW14:9SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(9) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(bo, "ACSW:LI20:NW14:9SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(9) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(stringin, "ACSW:LI20:NW14:9INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:9INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW14:9INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW14:9INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW14:9INITSTATE")
}

record(mbbi, "ACSW:LI20:NW14:9INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:9INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW14:10NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:10POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW14:10POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW14:10POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW14:10POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW14:10POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW14:10POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW14:10POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:10POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW14:10POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(10) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:10POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(10) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:10HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(10) acsw-li20-nw14")
}

record(stringin, "ACSW:LI20:NW14:10NAMESET") {
  field(FLNK, "ACSW:LI20:NW14:10NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW14:10NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(10) acsw-li20-nw14")
  field(DOL, "ACSW:LI20:NW14:10NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW14:10SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(10) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(bo, "ACSW:LI20:NW14:10SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(10) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(stringin, "ACSW:LI20:NW14:10INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:10INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW14:10INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW14:10INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW14:10INITSTATE")
}

record(mbbi, "ACSW:LI20:NW14:10INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:10INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW14:11NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:11POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW14:11POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW14:11POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW14:11POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW14:11POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW14:11POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW14:11POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:11POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW14:11POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(11) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:11POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(11) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:11HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(11) acsw-li20-nw14")
}

record(stringin, "ACSW:LI20:NW14:11NAMESET") {
  field(FLNK, "ACSW:LI20:NW14:11NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW14:11NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(11) acsw-li20-nw14")
  field(DOL, "ACSW:LI20:NW14:11NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW14:11SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(11) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(bo, "ACSW:LI20:NW14:11SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(11) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(stringin, "ACSW:LI20:NW14:11INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:11INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW14:11INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW14:11INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW14:11INITSTATE")
}

record(mbbi, "ACSW:LI20:NW14:11INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:11INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW14:12NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:12POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW14:12POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW14:12POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW14:12POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW14:12POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW14:12POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW14:12POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:12POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW14:12POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(12) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:12POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(12) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:12HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(12) acsw-li20-nw14")
}

record(stringin, "ACSW:LI20:NW14:12NAMESET") {
  field(FLNK, "ACSW:LI20:NW14:12NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW14:12NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(12) acsw-li20-nw14")
  field(DOL, "ACSW:LI20:NW14:12NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW14:12SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(12) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(bo, "ACSW:LI20:NW14:12SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(12) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(stringin, "ACSW:LI20:NW14:12INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:12INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW14:12INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW14:12INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW14:12INITSTATE")
}

record(mbbi, "ACSW:LI20:NW14:12INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:12INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW14:13NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:13POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW14:13POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW14:13POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW14:13POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW14:13POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW14:13POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW14:13POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:13POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW14:13POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(13) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:13POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(13) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:13HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(13) acsw-li20-nw14")
}

record(stringin, "ACSW:LI20:NW14:13NAMESET") {
  field(FLNK, "ACSW:LI20:NW14:13NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW14:13NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(13) acsw-li20-nw14")
  field(DOL, "ACSW:LI20:NW14:13NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW14:13SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(13) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(bo, "ACSW:LI20:NW14:13SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(13) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(stringin, "ACSW:LI20:NW14:13INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:13INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW14:13INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW14:13INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW14:13INITSTATE")
}

record(mbbi, "ACSW:LI20:NW14:13INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:13INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW14:14NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:14POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW14:14POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW14:14POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW14:14POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW14:14POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW14:14POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW14:14POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:14POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW14:14POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(14) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:14POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(14) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:14HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(14) acsw-li20-nw14")
}

record(stringin, "ACSW:LI20:NW14:14NAMESET") {
  field(FLNK, "ACSW:LI20:NW14:14NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW14:14NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(14) acsw-li20-nw14")
  field(DOL, "ACSW:LI20:NW14:14NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW14:14SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(14) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(bo, "ACSW:LI20:NW14:14SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(14) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(stringin, "ACSW:LI20:NW14:14INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:14INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW14:14INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW14:14INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW14:14INITSTATE")
}

record(mbbi, "ACSW:LI20:NW14:14INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:14INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW14:15NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:15POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW14:15POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW14:15POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW14:15POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW14:15POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW14:15POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW14:15POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:15POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW14:15POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(15) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:15POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(15) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:15HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(15) acsw-li20-nw14")
}

record(stringin, "ACSW:LI20:NW14:15NAMESET") {
  field(FLNK, "ACSW:LI20:NW14:15NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW14:15NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(15) acsw-li20-nw14")
  field(DOL, "ACSW:LI20:NW14:15NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW14:15SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(15) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(bo, "ACSW:LI20:NW14:15SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(15) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(stringin, "ACSW:LI20:NW14:15INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:15INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW14:15INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW14:15INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW14:15INITSTATE")
}

record(mbbi, "ACSW:LI20:NW14:15INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:15INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW14:16NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:16POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW14:16POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW14:16POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW14:16POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW14:16POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW14:16POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW14:16POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:16POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW14:16POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(16) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:16POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(16) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:16HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(16) acsw-li20-nw14")
}

record(stringin, "ACSW:LI20:NW14:16NAMESET") {
  field(FLNK, "ACSW:LI20:NW14:16NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW14:16NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(16) acsw-li20-nw14")
  field(DOL, "ACSW:LI20:NW14:16NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW14:16SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(16) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(bo, "ACSW:LI20:NW14:16SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(16) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(stringin, "ACSW:LI20:NW14:16INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:16INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW14:16INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW14:16INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW14:16INITSTATE")
}

record(mbbi, "ACSW:LI20:NW14:16INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:16INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW14:17NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:17POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW14:17POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW14:17POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW14:17POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW14:17POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW14:17POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW14:17POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:17POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW14:17POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(17) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:17POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(17) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:17HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(17) acsw-li20-nw14")
}

record(stringin, "ACSW:LI20:NW14:17NAMESET") {
  field(FLNK, "ACSW:LI20:NW14:17NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW14:17NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(17) acsw-li20-nw14")
  field(DOL, "ACSW:LI20:NW14:17NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW14:17SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(17) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(bo, "ACSW:LI20:NW14:17SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(17) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(stringin, "ACSW:LI20:NW14:17INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:17INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW14:17INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW14:17INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW14:17INITSTATE")
}

record(mbbi, "ACSW:LI20:NW14:17INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:17INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW14:18NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:18POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW14:18POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW14:18POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW14:18POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW14:18POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW14:18POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW14:18POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:18POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW14:18POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(18) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:18POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(18) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:18HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(18) acsw-li20-nw14")
}

record(stringin, "ACSW:LI20:NW14:18NAMESET") {
  field(FLNK, "ACSW:LI20:NW14:18NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW14:18NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(18) acsw-li20-nw14")
  field(DOL, "ACSW:LI20:NW14:18NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW14:18SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(18) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(bo, "ACSW:LI20:NW14:18SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(18) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(stringin, "ACSW:LI20:NW14:18INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:18INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW14:18INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW14:18INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW14:18INITSTATE")
}

record(mbbi, "ACSW:LI20:NW14:18INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:18INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW14:19NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:19POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW14:19POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW14:19POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW14:19POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW14:19POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW14:19POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW14:19POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:19POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW14:19POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(19) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:19POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(19) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:19HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(19) acsw-li20-nw14")
}

record(stringin, "ACSW:LI20:NW14:19NAMESET") {
  field(FLNK, "ACSW:LI20:NW14:19NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW14:19NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(19) acsw-li20-nw14")
  field(DOL, "ACSW:LI20:NW14:19NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW14:19SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(19) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(bo, "ACSW:LI20:NW14:19SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(19) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(stringin, "ACSW:LI20:NW14:19INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:19INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW14:19INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW14:19INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW14:19INITSTATE")
}

record(mbbi, "ACSW:LI20:NW14:19INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:19INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW14:20NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:20POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW14:20POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW14:20POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW14:20POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW14:20POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW14:20POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW14:20POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:20POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW14:20POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(20) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:20POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(20) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:20HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(20) acsw-li20-nw14")
}

record(stringin, "ACSW:LI20:NW14:20NAMESET") {
  field(FLNK, "ACSW:LI20:NW14:20NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW14:20NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(20) acsw-li20-nw14")
  field(DOL, "ACSW:LI20:NW14:20NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW14:20SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(20) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(bo, "ACSW:LI20:NW14:20SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(20) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(stringin, "ACSW:LI20:NW14:20INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:20INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW14:20INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW14:20INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW14:20INITSTATE")
}

record(mbbi, "ACSW:LI20:NW14:20INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:20INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW14:21NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:21POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW14:21POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW14:21POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW14:21POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW14:21POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW14:21POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW14:21POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:21POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW14:21POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(21) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:21POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(21) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:21HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(21) acsw-li20-nw14")
}

record(stringin, "ACSW:LI20:NW14:21NAMESET") {
  field(FLNK, "ACSW:LI20:NW14:21NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW14:21NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(21) acsw-li20-nw14")
  field(DOL, "ACSW:LI20:NW14:21NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW14:21SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(21) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(bo, "ACSW:LI20:NW14:21SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(21) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(stringin, "ACSW:LI20:NW14:21INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:21INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW14:21INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW14:21INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW14:21INITSTATE")
}

record(mbbi, "ACSW:LI20:NW14:21INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:21INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW14:22NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:22POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW14:22POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW14:22POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW14:22POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW14:22POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW14:22POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW14:22POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:22POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW14:22POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(22) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:22POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(22) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:22HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(22) acsw-li20-nw14")
}

record(stringin, "ACSW:LI20:NW14:22NAMESET") {
  field(FLNK, "ACSW:LI20:NW14:22NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW14:22NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(22) acsw-li20-nw14")
  field(DOL, "ACSW:LI20:NW14:22NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW14:22SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(22) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(bo, "ACSW:LI20:NW14:22SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(22) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(stringin, "ACSW:LI20:NW14:22INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:22INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW14:22INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW14:22INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW14:22INITSTATE")
}

record(mbbi, "ACSW:LI20:NW14:22INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:22INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW14:23NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:23POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW14:23POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW14:23POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW14:23POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW14:23POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW14:23POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW14:23POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:23POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW14:23POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(23) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:23POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(23) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:23HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(23) acsw-li20-nw14")
}

record(stringin, "ACSW:LI20:NW14:23NAMESET") {
  field(FLNK, "ACSW:LI20:NW14:23NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW14:23NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(23) acsw-li20-nw14")
  field(DOL, "ACSW:LI20:NW14:23NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW14:23SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(23) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(bo, "ACSW:LI20:NW14:23SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(23) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(stringin, "ACSW:LI20:NW14:23INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:23INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW14:23INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW14:23INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW14:23INITSTATE")
}

record(mbbi, "ACSW:LI20:NW14:23INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:23INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW14:24NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:24POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW14:24POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW14:24POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW14:24POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW14:24POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW14:24POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW14:24POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:24POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW14:24POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(24) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:24POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(24) acsw-li20-nw14")
}

record(bo, "ACSW:LI20:NW14:24HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(24) acsw-li20-nw14")
}

record(stringin, "ACSW:LI20:NW14:24NAMESET") {
  field(FLNK, "ACSW:LI20:NW14:24NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW14:24NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(24) acsw-li20-nw14")
  field(DOL, "ACSW:LI20:NW14:24NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW14:24SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(24) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(bo, "ACSW:LI20:NW14:24SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(24) acsw-li20-nw14")
  field(FLNK, "ACSW:LI20:NW14:GETINIT")
}

record(stringin, "ACSW:LI20:NW14:24INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW14:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW14:24INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW14:24INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW14:24INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW14:24INITSTATE")
}

record(mbbi, "ACSW:LI20:NW14:24INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW14:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW14:24INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW16:LOGIN") {
  field(PINI, "YES")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db setLogin(ACSW:LI20:NW16) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINFO")
}

record(stringin, "ACSW:LI20:NW16:GETINFO") {
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getInfo(ACSW:LI20:NW16) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(stringin, "ACSW:LI20:NW16:FWVERSION") {
  field(SCAN, "10 second")
  field(FLNK, "ACSW:LI20:NW16:NETFWVERSION")
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:LI20:NW16:NETFWVERSION") {
  field(DESC, "Network adapter fw vers")
  field(FLNK, "ACSW:LI20:NW16:SITEID")
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(stringin, "ACSW:LI20:NW16:SITEID") {
  field(DESC, "ACSW node name")
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")

}

record(bo, "ACSW:LI20:NW16:GETINIT") {
  field(DESC, "Get outlet init states")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db getOutletInitState24(ACSW:LI20:NW16) acsw-li20-nw16")
}

record(stringin, "ACSW:LI20:NW16:GETSTATUS") {
  field(SCAN, "2 second")
  field(DTYP, "stream")
  field(INP, "@acsw_apc.proto.db getOutletState24(ACSW:LI20:NW16) acsw-li20-nw16")
}

record(ai, "ACSW:LI20:NW16:TYPE") {
  field(DESC, "APC 24 Port AC Power Switch")
  field(PINI, "YES")
  field(VAL, "17")
}

record(stringin, "ACSW:LI20:NW16:LOC") {
  field(PINI, "YES")
  field(VAL, "FKG20-20xx")
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
  info(autosaveFields,"VAL")
}

record(bo, "ACSW:LI20:NW16:DISCONN") {
  field(DESC, "Disconn to allow access")
  field(DISA, "1")
  field(DISS, "NO_ALARM")
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setDisconnect acsw-li20-nw16")
}

record(calcout, "ACSW:LI20:NW16:CONNCALC") {
  field(CALC, "A=B && C#D")
  field(SCAN, "2 second")
  field(INPA, "ACSW:LI20:NW16:DISCONN.DISA")
  field(INPB, "ACSW:LI20:NW16:DISCONN.DISV")
  field(INPC, "ACSW:LI20:NW16:GETSTATUS.DISA")
  field(INPD, "ACSW:LI20:NW16:GETSTATUS.DISV")
  field(OOPT, "On Change")
  field(OUT, "ACSW:LI20:NW16:CONNSTA PP")
}

record(bi, "ACSW:LI20:NW16:CONNSTA") {
  field(ZNAM, "Not connected")
  field(ONAM, "Connected")
  field(ZSV, "MINOR")
  field(OSV, "NO_ALARM")
}

# Disconnect from ACSW to allow
# other clients access to ACSW
record(seq, "ACSW:LI20:NW16:ACCSTART") {
  field(SELM, "All")
  field(DOL1, "1")
  field(LNK1, "ACSW:LI20:NW16:GETSTATUS.DISA")
  field(DOL2, "0")
  field(LNK2, "ACSW:LI20:NW16:DISCONN.DISA PP")
}

# Reconnect to ACSW
record(seq, "ACSW:LI20:NW16:ACCSTOP") {
  field(SELM, "All")
  field(DOL1, "0")
  field(LNK1, "ACSW:LI20:NW16:GETSTATUS.DISA")
  field(DOL2, "1")
  field(LNK2, "ACSW:LI20:NW16:DISCONN.DISA")
}

#Not in use since using CLI
record(ai, "ACSW:LI20:NW16:UPTIMEHOUR") {
  field(FLNK, "ACSW:LI20:NW16:UPTIMEMINUTE")
  field(EGU, "Hours")
}
record(ai, "ACSW:LI20:NW16:UPTIMEDAY") {
  field(FLNK, "ACSW:LI20:NW16:UPTIMEHOUR")
  field(EGU, "Days")
}
record(ai, "ACSW:LI20:NW16:UPTIMEMINUTE") {
  field(FLNK, "ACSW:LI20:NW16:1NAME")
  field(EGU, "Minutes")
}

record(stringin, "ACSW:LI20:NW16:1NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:1POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW16:1POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW16:1POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW16:1POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW16:1POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW16:1POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW16:1POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:1POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW16:1POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(1) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:1POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(1) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:1HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(1) acsw-li20-nw16")
}

record(stringin, "ACSW:LI20:NW16:1NAMESET") {
  field(FLNK, "ACSW:LI20:NW16:1NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW16:1NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(1) acsw-li20-nw16")
  field(DOL, "ACSW:LI20:NW16:1NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW16:1SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(1) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(bo, "ACSW:LI20:NW16:1SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(1) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(stringin, "ACSW:LI20:NW16:1INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:1INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW16:1INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW16:1INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW16:1INITSTATE")
}

record(mbbi, "ACSW:LI20:NW16:1INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:1INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW16:2NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:2POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW16:2POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW16:2POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW16:2POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW16:2POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW16:2POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW16:2POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:2POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW16:2POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(2) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:2POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(2) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:2HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(2) acsw-li20-nw16")
}

record(stringin, "ACSW:LI20:NW16:2NAMESET") {
  field(FLNK, "ACSW:LI20:NW16:2NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW16:2NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(2) acsw-li20-nw16")
  field(DOL, "ACSW:LI20:NW16:2NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW16:2SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(2) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(bo, "ACSW:LI20:NW16:2SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(2) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(stringin, "ACSW:LI20:NW16:2INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:2INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW16:2INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW16:2INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW16:2INITSTATE")
}

record(mbbi, "ACSW:LI20:NW16:2INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:2INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW16:3NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:3POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW16:3POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW16:3POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW16:3POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW16:3POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW16:3POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW16:3POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:3POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW16:3POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(3) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:3POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(3) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:3HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(3) acsw-li20-nw16")
}

record(stringin, "ACSW:LI20:NW16:3NAMESET") {
  field(FLNK, "ACSW:LI20:NW16:3NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW16:3NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(3) acsw-li20-nw16")
  field(DOL, "ACSW:LI20:NW16:3NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW16:3SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(3) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(bo, "ACSW:LI20:NW16:3SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(3) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(stringin, "ACSW:LI20:NW16:3INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:3INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW16:3INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW16:3INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW16:3INITSTATE")
}

record(mbbi, "ACSW:LI20:NW16:3INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:3INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW16:4NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:4POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW16:4POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW16:4POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW16:4POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW16:4POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW16:4POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW16:4POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:4POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW16:4POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(4) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:4POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(4) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:4HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(4) acsw-li20-nw16")
}

record(stringin, "ACSW:LI20:NW16:4NAMESET") {
  field(FLNK, "ACSW:LI20:NW16:4NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW16:4NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(4) acsw-li20-nw16")
  field(DOL, "ACSW:LI20:NW16:4NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW16:4SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(4) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(bo, "ACSW:LI20:NW16:4SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(4) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(stringin, "ACSW:LI20:NW16:4INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:4INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW16:4INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW16:4INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW16:4INITSTATE")
}

record(mbbi, "ACSW:LI20:NW16:4INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:4INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW16:5NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:5POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW16:5POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW16:5POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW16:5POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW16:5POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW16:5POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW16:5POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:5POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW16:5POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(5) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:5POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(5) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:5HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(5) acsw-li20-nw16")
}

record(stringin, "ACSW:LI20:NW16:5NAMESET") {
  field(FLNK, "ACSW:LI20:NW16:5NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW16:5NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(5) acsw-li20-nw16")
  field(DOL, "ACSW:LI20:NW16:5NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW16:5SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(5) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(bo, "ACSW:LI20:NW16:5SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(5) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(stringin, "ACSW:LI20:NW16:5INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:5INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW16:5INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW16:5INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW16:5INITSTATE")
}

record(mbbi, "ACSW:LI20:NW16:5INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:5INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW16:6NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:6POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW16:6POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW16:6POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW16:6POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW16:6POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW16:6POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW16:6POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:6POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW16:6POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(6) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:6POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(6) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:6HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(6) acsw-li20-nw16")
}

record(stringin, "ACSW:LI20:NW16:6NAMESET") {
  field(FLNK, "ACSW:LI20:NW16:6NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW16:6NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(6) acsw-li20-nw16")
  field(DOL, "ACSW:LI20:NW16:6NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW16:6SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(6) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(bo, "ACSW:LI20:NW16:6SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(6) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(stringin, "ACSW:LI20:NW16:6INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:6INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW16:6INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW16:6INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW16:6INITSTATE")
}

record(mbbi, "ACSW:LI20:NW16:6INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:6INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW16:7NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:7POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW16:7POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW16:7POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW16:7POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW16:7POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW16:7POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW16:7POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:7POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW16:7POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(7) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:7POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(7) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:7HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(7) acsw-li20-nw16")
}

record(stringin, "ACSW:LI20:NW16:7NAMESET") {
  field(FLNK, "ACSW:LI20:NW16:7NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW16:7NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(7) acsw-li20-nw16")
  field(DOL, "ACSW:LI20:NW16:7NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW16:7SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(7) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(bo, "ACSW:LI20:NW16:7SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(7) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(stringin, "ACSW:LI20:NW16:7INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:7INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW16:7INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW16:7INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW16:7INITSTATE")
}

record(mbbi, "ACSW:LI20:NW16:7INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:7INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW16:8NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:8POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW16:8POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW16:8POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW16:8POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW16:8POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW16:8POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW16:8POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:8POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW16:8POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(8) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:8POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(8) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:8HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(8) acsw-li20-nw16")
}

record(stringin, "ACSW:LI20:NW16:8NAMESET") {
  field(FLNK, "ACSW:LI20:NW16:8NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW16:8NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(8) acsw-li20-nw16")
  field(DOL, "ACSW:LI20:NW16:8NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW16:8SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(8) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(bo, "ACSW:LI20:NW16:8SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(8) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(stringin, "ACSW:LI20:NW16:8INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:8INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW16:8INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW16:8INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW16:8INITSTATE")
}

record(mbbi, "ACSW:LI20:NW16:8INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:8INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW16:9NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:9POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW16:9POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW16:9POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW16:9POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW16:9POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW16:9POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW16:9POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:9POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW16:9POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(9) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:9POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(9) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:9HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(9) acsw-li20-nw16")
}

record(stringin, "ACSW:LI20:NW16:9NAMESET") {
  field(FLNK, "ACSW:LI20:NW16:9NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW16:9NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(9) acsw-li20-nw16")
  field(DOL, "ACSW:LI20:NW16:9NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW16:9SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(9) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(bo, "ACSW:LI20:NW16:9SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(9) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(stringin, "ACSW:LI20:NW16:9INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:9INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW16:9INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW16:9INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW16:9INITSTATE")
}

record(mbbi, "ACSW:LI20:NW16:9INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:9INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW16:10NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:10POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW16:10POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW16:10POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW16:10POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW16:10POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW16:10POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW16:10POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:10POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW16:10POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(10) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:10POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(10) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:10HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(10) acsw-li20-nw16")
}

record(stringin, "ACSW:LI20:NW16:10NAMESET") {
  field(FLNK, "ACSW:LI20:NW16:10NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW16:10NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(10) acsw-li20-nw16")
  field(DOL, "ACSW:LI20:NW16:10NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW16:10SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(10) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(bo, "ACSW:LI20:NW16:10SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(10) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(stringin, "ACSW:LI20:NW16:10INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:10INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW16:10INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW16:10INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW16:10INITSTATE")
}

record(mbbi, "ACSW:LI20:NW16:10INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:10INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW16:11NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:11POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW16:11POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW16:11POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW16:11POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW16:11POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW16:11POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW16:11POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:11POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW16:11POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(11) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:11POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(11) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:11HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(11) acsw-li20-nw16")
}

record(stringin, "ACSW:LI20:NW16:11NAMESET") {
  field(FLNK, "ACSW:LI20:NW16:11NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW16:11NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(11) acsw-li20-nw16")
  field(DOL, "ACSW:LI20:NW16:11NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW16:11SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(11) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(bo, "ACSW:LI20:NW16:11SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(11) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(stringin, "ACSW:LI20:NW16:11INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:11INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW16:11INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW16:11INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW16:11INITSTATE")
}

record(mbbi, "ACSW:LI20:NW16:11INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:11INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW16:12NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:12POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW16:12POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW16:12POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW16:12POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW16:12POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW16:12POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW16:12POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:12POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW16:12POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(12) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:12POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(12) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:12HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(12) acsw-li20-nw16")
}

record(stringin, "ACSW:LI20:NW16:12NAMESET") {
  field(FLNK, "ACSW:LI20:NW16:12NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW16:12NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(12) acsw-li20-nw16")
  field(DOL, "ACSW:LI20:NW16:12NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW16:12SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(12) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(bo, "ACSW:LI20:NW16:12SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(12) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(stringin, "ACSW:LI20:NW16:12INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:12INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW16:12INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW16:12INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW16:12INITSTATE")
}

record(mbbi, "ACSW:LI20:NW16:12INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:12INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW16:13NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:13POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW16:13POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW16:13POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW16:13POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW16:13POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW16:13POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW16:13POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:13POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW16:13POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(13) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:13POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(13) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:13HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(13) acsw-li20-nw16")
}

record(stringin, "ACSW:LI20:NW16:13NAMESET") {
  field(FLNK, "ACSW:LI20:NW16:13NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW16:13NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(13) acsw-li20-nw16")
  field(DOL, "ACSW:LI20:NW16:13NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW16:13SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(13) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(bo, "ACSW:LI20:NW16:13SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(13) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(stringin, "ACSW:LI20:NW16:13INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:13INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW16:13INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW16:13INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW16:13INITSTATE")
}

record(mbbi, "ACSW:LI20:NW16:13INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:13INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW16:14NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:14POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW16:14POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW16:14POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW16:14POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW16:14POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW16:14POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW16:14POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:14POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW16:14POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(14) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:14POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(14) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:14HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(14) acsw-li20-nw16")
}

record(stringin, "ACSW:LI20:NW16:14NAMESET") {
  field(FLNK, "ACSW:LI20:NW16:14NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW16:14NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(14) acsw-li20-nw16")
  field(DOL, "ACSW:LI20:NW16:14NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW16:14SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(14) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(bo, "ACSW:LI20:NW16:14SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(14) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(stringin, "ACSW:LI20:NW16:14INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:14INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW16:14INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW16:14INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW16:14INITSTATE")
}

record(mbbi, "ACSW:LI20:NW16:14INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:14INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW16:15NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:15POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW16:15POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW16:15POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW16:15POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW16:15POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW16:15POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW16:15POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:15POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW16:15POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(15) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:15POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(15) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:15HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(15) acsw-li20-nw16")
}

record(stringin, "ACSW:LI20:NW16:15NAMESET") {
  field(FLNK, "ACSW:LI20:NW16:15NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW16:15NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(15) acsw-li20-nw16")
  field(DOL, "ACSW:LI20:NW16:15NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW16:15SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(15) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(bo, "ACSW:LI20:NW16:15SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(15) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(stringin, "ACSW:LI20:NW16:15INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:15INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW16:15INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW16:15INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW16:15INITSTATE")
}

record(mbbi, "ACSW:LI20:NW16:15INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:15INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW16:16NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:16POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW16:16POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW16:16POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW16:16POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW16:16POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW16:16POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW16:16POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:16POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW16:16POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(16) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:16POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(16) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:16HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(16) acsw-li20-nw16")
}

record(stringin, "ACSW:LI20:NW16:16NAMESET") {
  field(FLNK, "ACSW:LI20:NW16:16NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW16:16NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(16) acsw-li20-nw16")
  field(DOL, "ACSW:LI20:NW16:16NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW16:16SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(16) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(bo, "ACSW:LI20:NW16:16SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(16) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(stringin, "ACSW:LI20:NW16:16INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:16INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW16:16INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW16:16INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW16:16INITSTATE")
}

record(mbbi, "ACSW:LI20:NW16:16INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:16INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW16:17NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:17POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW16:17POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW16:17POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW16:17POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW16:17POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW16:17POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW16:17POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:17POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW16:17POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(17) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:17POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(17) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:17HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(17) acsw-li20-nw16")
}

record(stringin, "ACSW:LI20:NW16:17NAMESET") {
  field(FLNK, "ACSW:LI20:NW16:17NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW16:17NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(17) acsw-li20-nw16")
  field(DOL, "ACSW:LI20:NW16:17NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW16:17SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(17) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(bo, "ACSW:LI20:NW16:17SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(17) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(stringin, "ACSW:LI20:NW16:17INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:17INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW16:17INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW16:17INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW16:17INITSTATE")
}

record(mbbi, "ACSW:LI20:NW16:17INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:17INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW16:18NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:18POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW16:18POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW16:18POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW16:18POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW16:18POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW16:18POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW16:18POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:18POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW16:18POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(18) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:18POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(18) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:18HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(18) acsw-li20-nw16")
}

record(stringin, "ACSW:LI20:NW16:18NAMESET") {
  field(FLNK, "ACSW:LI20:NW16:18NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW16:18NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(18) acsw-li20-nw16")
  field(DOL, "ACSW:LI20:NW16:18NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW16:18SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(18) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(bo, "ACSW:LI20:NW16:18SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(18) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(stringin, "ACSW:LI20:NW16:18INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:18INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW16:18INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW16:18INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW16:18INITSTATE")
}

record(mbbi, "ACSW:LI20:NW16:18INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:18INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW16:19NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:19POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW16:19POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW16:19POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW16:19POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW16:19POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW16:19POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW16:19POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:19POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW16:19POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(19) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:19POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(19) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:19HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(19) acsw-li20-nw16")
}

record(stringin, "ACSW:LI20:NW16:19NAMESET") {
  field(FLNK, "ACSW:LI20:NW16:19NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW16:19NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(19) acsw-li20-nw16")
  field(DOL, "ACSW:LI20:NW16:19NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW16:19SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(19) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(bo, "ACSW:LI20:NW16:19SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(19) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(stringin, "ACSW:LI20:NW16:19INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:19INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW16:19INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW16:19INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW16:19INITSTATE")
}

record(mbbi, "ACSW:LI20:NW16:19INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:19INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW16:20NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:20POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW16:20POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW16:20POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW16:20POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW16:20POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW16:20POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW16:20POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:20POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW16:20POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(20) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:20POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(20) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:20HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(20) acsw-li20-nw16")
}

record(stringin, "ACSW:LI20:NW16:20NAMESET") {
  field(FLNK, "ACSW:LI20:NW16:20NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW16:20NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(20) acsw-li20-nw16")
  field(DOL, "ACSW:LI20:NW16:20NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW16:20SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(20) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(bo, "ACSW:LI20:NW16:20SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(20) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(stringin, "ACSW:LI20:NW16:20INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:20INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW16:20INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW16:20INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW16:20INITSTATE")
}

record(mbbi, "ACSW:LI20:NW16:20INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:20INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW16:21NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:21POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW16:21POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW16:21POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW16:21POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW16:21POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW16:21POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW16:21POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:21POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW16:21POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(21) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:21POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(21) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:21HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(21) acsw-li20-nw16")
}

record(stringin, "ACSW:LI20:NW16:21NAMESET") {
  field(FLNK, "ACSW:LI20:NW16:21NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW16:21NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(21) acsw-li20-nw16")
  field(DOL, "ACSW:LI20:NW16:21NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW16:21SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(21) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(bo, "ACSW:LI20:NW16:21SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(21) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(stringin, "ACSW:LI20:NW16:21INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:21INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW16:21INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW16:21INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW16:21INITSTATE")
}

record(mbbi, "ACSW:LI20:NW16:21INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:21INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW16:22NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:22POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW16:22POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW16:22POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW16:22POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW16:22POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW16:22POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW16:22POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:22POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW16:22POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(22) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:22POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(22) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:22HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(22) acsw-li20-nw16")
}

record(stringin, "ACSW:LI20:NW16:22NAMESET") {
  field(FLNK, "ACSW:LI20:NW16:22NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW16:22NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(22) acsw-li20-nw16")
  field(DOL, "ACSW:LI20:NW16:22NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW16:22SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(22) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(bo, "ACSW:LI20:NW16:22SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(22) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(stringin, "ACSW:LI20:NW16:22INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:22INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW16:22INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW16:22INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW16:22INITSTATE")
}

record(mbbi, "ACSW:LI20:NW16:22INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:22INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW16:23NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:23POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW16:23POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW16:23POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW16:23POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW16:23POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW16:23POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW16:23POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:23POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW16:23POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(23) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:23POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(23) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:23HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(23) acsw-li20-nw16")
}

record(stringin, "ACSW:LI20:NW16:23NAMESET") {
  field(FLNK, "ACSW:LI20:NW16:23NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW16:23NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(23) acsw-li20-nw16")
  field(DOL, "ACSW:LI20:NW16:23NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW16:23SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(23) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(bo, "ACSW:LI20:NW16:23SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(23) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(stringin, "ACSW:LI20:NW16:23INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:23INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW16:23INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW16:23INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW16:23INITSTATE")
}

record(mbbi, "ACSW:LI20:NW16:23INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:23INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}
record(stringin, "ACSW:LI20:NW16:24NAME") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:24POWERSTATEIN")
}

record(stringin, "ACSW:LI20:NW16:24POWERSTATEIN") {
  field(FLNK, "ACSW:LI20:NW16:24POWERSTATESV")
}

record(scalcout, "ACSW:LI20:NW16:24POWERSTATESV") {
  field(CALC,  "AA==BB?0:(AA==CC?1):(AA==DD?2):3")
  field(INAA, "ACSW:LI20:NW16:24POWERSTATEIN")
  field(BB, "ON")
  field(CC, "OFF*")
  field(DD, "OFF")
  field(FLNK, "ACSW:LI20:NW16:24POWERSTATE")
}

record(mbbi, "ACSW:LI20:NW16:24POWERSTATE") {
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:24POWERSTATESV")
  field(FLNK, "")
  field(ZRST, "ON")
  field(ONST, "OFF*")
  field(TWST, "OFF")
  field(THST, "UNKNOWN")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR CPP MS")
  field(DISV, "20")
}

record(bo, "ACSW:LI20:NW16:24POWEROFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOff(24) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:24POWERON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletOn(24) acsw-li20-nw16")
}

record(bo, "ACSW:LI20:NW16:24HARDRESET") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletHardReset(24) acsw-li20-nw16")
}

record(stringin, "ACSW:LI20:NW16:24NAMESET") {
  field(FLNK, "ACSW:LI20:NW16:24NAMESETGO")
  field(VAL, "")
}

record(stringout, "ACSW:LI20:NW16:24NAMESETGO") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletName(24) acsw-li20-nw16")
  field(DOL, "ACSW:LI20:NW16:24NAMESET")
  field(OMSL, "closed_loop")
}

record(bo, "ACSW:LI20:NW16:24SETINITOFF") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOff(24) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(bo, "ACSW:LI20:NW16:24SETINITON") {
  field(DTYP, "stream")
  field(OUT, "@acsw_apc.proto.db setOutletInitOn(24) acsw-li20-nw16")
  field(FLNK, "ACSW:LI20:NW16:GETINIT")
}

record(stringin, "ACSW:LI20:NW16:24INITSTATEIN") {
   field(DESC, "Plug device name")
   field(SDIS, "ACSW:LI20:NW16:GETSTATUS.SEVR")
   field(DISV, "3")
   field(DISS, "INVALID")
   field(PINI, "YES")
   field(FLNK, "ACSW:LI20:NW16:24INITSTATESV")
}

# Currently, power on delay is always 0 or never, 
# so our 2 initial states are 'on' or 'off'.
# If we start using delays, we should modify this
# logic to display the delay. 
record(scalcout, "ACSW:LI20:NW16:24INITSTATESV") {
  field(CALC, "AA==BB?1:0")
  field(INAA, "ACSW:LI20:NW16:24INITSTATEIN NPP MS")
  field(BB, "never")
  field(FLNK, "ACSW:LI20:NW16:24INITSTATE")
}

record(mbbi, "ACSW:LI20:NW16:24INITSTATE") {
#  field(SDIS, "ACSW:LI20:NW16:GETSTATUS.DISA NPP MS")
#  field(DISS, "INVALID")
  field(INP, "ACSW:LI20:NW16:24INITSTATESV NPP MS")
  field(ZRST, "ON")
  field(ONST, "OFF")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
}