#! Generated by VisualDCT v2.6 #! DBDSTART #! DBD("../../../dbd/mgntSoft.dbd") #! DBDEND record(sSub, "$(DEV):HSTASUB") { field(DESC, "Transform EPICS to SLC HSTA") field(SCAN, "2 second") field(INAM, "mgntInit") field(SNAM, "mgntHstaEncode") # Inputs: # A = not used # B = ps type 0=bipolar, 1=unipolar, 2=unipolar w/polarity switch, no pwr supply # C = ps turned off by operator 0=no, 1=yes # D = magnet configuration 0=main,1=string-slave,2=string-main. # E = ps catagory 0=small,1=intermediate,2=bulk,3=modulator,4=none. # F = Interlock status (0=OK, s1=FAULT) # J = PS On/Off state # # Outputs: # Z = SLC HSTA bitmask # field(INPB, "$(DEV):PSTYPE.RVAL") field(INPC, "$(DEV):TURNEDOFF.RVAL") field(INPD, "$(DEV):CONFIG.RVAL") field(INPE, "$(DEV):PSCATEGORY.RVAL") field(INPF, "$(DEV):INTLKSUMY") # For EF Correctors if set to 1 field(INPG, "$(DEV):AUTOCTRL.RVAL") field(INPJ, "$(DEV):OUTOFSERVICE.RVAL") field(INPL, "$(DEV):STATE.RVAL") # This pv flags matlab feedback control field(INPN, "$(DEV):FBCKENABLE.RVAL") # This pv flags pattern aware. field(INPO, "$(PAU=$(DEV):PAU)") field(INPP, "$(DEV):CALBDISABLE.RVAL") field(INPQ, "$(DEV):PTRBDISABLE.RVAL") field(INPR, "$(DEV):TRIMDISABLE.RVAL") field(INPS, "$(DEV):STDZDISABLE.RVAL)") # added FBCK to HSTA, which flags fast feedback control field(INPT, "$(DEV):FBCK") field(INPU, "$(DEV):TRIMTYPE.RVAL") field(INPV, "$(STDZD=$(DEV):STDZDIRECT.RVAL)") field(INPW, "$(DEGAU=$(DEV):DEGAUSENABLE.RVAL)") field(FLNK, "$(DEV):HSTA") } record(longin, "$(DEV):HSTA") { field(DESC, "HSTA from EPICS") field(INP, "$(DEV):HSTASUB") } # Only magnets with bipolary power supplies can be degaussed. record(bo, "$(DEV):DEGAUSENABLE") { field(DESC, "Degauss Enable") field(DTYP, "Raw Soft Channel") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(PINI, "YES") field(VAL, "$(DENB=0)") info(autosaveFields,"VAL RVAL") } # This is currently only used for cryo magnets. # If the a the degauss is enabled and degauss # will be lost when upon a trim request, a # degauss will be preformed proir the trim # if this pv is enabled. record(bo, "$(DEV):DEGAUSAUTOENABLE") { field(DESC, "Auto DEGAUS Enable") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(VAL, "$(MDENB=0)") field(PINI, "YES") } # EPSC's have auto a calibration in firmware running continuously. # So for EPSC's the default is for calibration to be enabled. However, # For MCOR's the DAC calibration is performed in software (mgntCtrl.st) # record(bo, "$(DEV):CALBDISABLE") { field(DESC, "DAC Calb Disabled") field(DTYP, "Raw Soft Channel") field(ZNAM, "Enabled") field(ONAM, "Disabled") field(VAL, "$(CDIS=1)") field(PINI, "YES") info(autosaveFields,"VAL RVAL") } record(bo, "$(DEV):PTRBDISABLE") { field(DESC, "Perturb Function") field(DTYP, "Raw Soft Channel") field(ZNAM, "Enabled") field(ONAM, "Disabled") field(VAL, "$(PDIS=0)") field(PINI, "YES") info(autosaveFields,"VAL RVAL") } record(bo, "$(DEV):TRIMDISABLE") { field(DESC, "Trim Function") field(DTYP, "Raw Soft Channel") field(ZNAM, "Enabled") field(ONAM, "Disabled") field(VAL, "$(TDIS=0)") field(PINI, "YES") info(autosaveFields,"VAL RVAL") } record(bo, "$(DEV):STDZDISABLE") { field(DTYP, "Raw Soft Channel") field(ZNAM, "NO") field(ONAM, "YES") field(DESC, "Standardize Function") field(VAL, "$(SDIS=1)") field(PINI, "YES") info(autosaveFields,"VAL RVAL") } # This PV has been replaced by $(DEV):FBCK. # Only the matlab feedback currently uses this PV as of 11/07/2012. # The feedback controller software only uses $(DEV):FBCK. # This PV should be replaced by $(DEV):FBCK in the matlab feedback # and removed from the magnets sequence mgntCtrl.st and database. # The matlab feeback should do the same thing as the feedback controller # software for non-fast feedback devices, which use the CA subnet and # note the fast-feedback subnet FCOM to control the magnets.. # record(bo, "$(DEV):FBCKENABLE") { field(DESC, "Feedback Enable") field(DTYP, "Raw Soft Channel") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(PINI, "YES") field(VAL, "$(FENB=0)") info(autosaveFields,"VAL RVAL") } # Note: this pv iset seot to Enabled for # earth field correctors. record(bo, "$(DEV):AUTOCTRL") { field(DESC, "Automatically controlled") field(DTYP, "Raw Soft Channel") field(PINI, "YES") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") field(VAL, "$(AUTO=0)") } record(bo, "$(DEV):OUTOFSERVICE") { field(DESC, "Device Offline flag") field(DTYP, "Raw Soft Channel") field(PINI, "YES") field(ZNAM, "In-Service") field(ONAM, "Out-of-Service") field(DOL, "$(OFFLINE="")") field(OMSL, "$(OMSL=supervisory)") field(OUT, "$(OUT="")") field(FLNK, "$(DEV):ONLINECALC") info(autosaveFields,"VAL RVAL") } record(calcout,"$(DEV):ONLINECALC") { field(DESC, "Device online status") field(ASG, "Internal") field(CALC, "A?0:1") field(INPA, "$(DEV):OUTOFSERVICE NPP NMS") field(OUT, "$(DEV):ONLINE PP") } record(bo, "$(DEV):ONLINE") { field(DESC, "PS Online Status") field(DTYP, "Raw Soft Channel") field(ZNAM, "OFFLINE") field(ONAM, "ONLINE") } record(bo, "$(DEV):ONOFFCTRL") { field(DESC, "PS on/off ctrl avail") field(DTYP, "Raw Soft Channel") field(PINI, "YES") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") field(VAL, "$(ONOF=0)") } record(bo, "$(DEV):RESETCTRL") { field(DESC, "PS fault reset ctrl avail") field(DTYP, "Raw Soft Channel") field(PINI, "YES") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") field(VAL, "$(RESET=1)") } record(bo, "$(DEV):NOANLGCTRL") { field(DESC, "No analog control of ps") field(DTYP, "Raw Soft Channel") field(PINI, "YES") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") field(VAL, "$(NOANLG=0)") } # This PV is modified by :STATSUB.U record(bo, "$(DEV):UNAVAIL") { field(DESC, "Not avail for control") field(DTYP, "Raw Soft Channel") field(SCAN, "Passive") field(PINI, "YES") field(ZNAM, "Available") field(ONAM, "Unavailable") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") } record(bo, "$(DEV):PPS") { field(DESC, "Monitored by PPS") field(ONAM, "YES") field(ZNAM, "NO") field(PINI, "YES") field(ASG, "NOWRITE") info(autosaveFields,"VAL") } # 21-Aug-2013: K. Luchini # Set channel access security so that # users cannot easily enable/disable MPS. # This pv is need for binary status # pvs in magnet databases, which are # are accessd the MPS Link Node over # Channel Access. record(mbbo, "$(DEV):MPS") { field(DESC, "Monitored by MPS") field(PINI, "YES") field(ZRVL, "0") field(ONVL, "1") field(TWVL, "2") field(ZRST, "NONE") field(ONST, "PSON_MON") field(TWST, "PSON_BACT_MON") field(NOBT, "2") field(ASG, "EOICDESK") info(autosaveFields,"VAL") } # Informational only. record(bo, "$(DEV):BCS") { field(DESC, "Monitored by BCS") field(ONAM, "YES") field(ZNAM, "NO") field(PINI, "YES") field(ASG, "NOWRITE") info(autosaveFields,"VAL RVAL") } # Please note that option 3 "NONE" is set for magnets # that are considered a slave in a string. record(mbbo, "$(DEV):PSTYPE") { field(DESC, "Power Supply Type") field(DTYP, "Raw Soft Channel") field(PINI, "YES") field(NOBT, "2") field(ZRST, "Bipolar") field(ONST, "Unipolar") field(TWST, "Unipolar_PolSW") field(THST, "NONE") field(ZRVL, "0") field(ONVL, "1") field(TWVL, "2") field(THVL, "3") field(VAL, "$(PSTYPE=0)") field(ASG, "NOWRITE") } record(mbbo, "$(DEV):PSCATEGORY"){ field(DESC, "Power Supply Category") field(DTYP, "Raw Soft Channel") field(PINI, "YES") field(NOBT, "3") field(ZRST, "Small") field(ONST, "Intermediate") field(TWST, "Bulk") field(THST, "Modulator") field(FRST, "NONE") field(ZRVL, "0") field(ONVL, "1") field(TWVL, "2") field(THVL, "3") field(FRVL, "4") field(FVSV, "INVALID") field(SXSV, "INVALID") field(VAL, "$(PSCAT=0)") field(ASG, "NOWRITE") } record(mbbo, "$(DEV):PSCONTROLLER") { field(DESC, "Power Supply Controller") field(DTYP, "Raw Soft Channel") field(PINI, "YES") field(NOBT, "3") field(ZRST, "MCOR") field(ONST, "EMCOR") field(TWST, "EPSC") field(THST, "PLC") field(FRST, "BECKHOFF") field(FVST, "SERIAL") field(SXST, "NONE") field(ZRVL, "0") field(ONVL, "1") field(TWVL, "2") field(THVL, "3") field(FRVL, "4") field(FVVL, "5") field(SXVL, "6") field(SVVL, "7") field(SVSV, "INVALID") field(VAL, "$(PSC=0)") field(ASG, "NOWRITE") } record(mbbo, "$(DEV):CONFIG") { field(DESC, "Magnet Configuration") field(DTYP, "Raw Soft Channel") field(PINI, "YES") field(NOBT, "2") field(ZRST, "Individual") field(ONST, "String") field(TWST, "String Main") field(ZRVL, "0") field(ONVL, "1") field(TWVL, "2") field(THVL, "3") field(THSV, "INVALID") field(VAL, "$(CNF=0)") field(ASG, "NOWRITE") field(FLNK, "$(DEV):TRIMTYPE") } record(stringout, "$(DEV):MAIN") { field(DESC, "Magnet Main") field(ASG, "NOWRITE") field(PINI, "YES") field(DOL, "$(MAIN="$(DEV):MADNAME CPP NMS")") field(OMSL, "$(OMSL="closed_loop")") field(VAL, " ") } record(calcout, "$(DEV):TURNEDOFFCALC") { field(DESC, "Check if ps turned off") field(SCAN, "10 second") field(CALC, "A?0:B?0:1") field(INPA, "$(DEV):STATE.RVAL") field(INPB, "$(DEV):INTLKSUMY.RVAL") field(OUT, "$(DEV):TURNEDOFF PP") field(OOPT, "On Change") field(ASG, "Internal") } record(bo, "$(DEV):TURNEDOFF") { field(DESC, "Supply Turned Off by User") field(DTYP, "Raw Soft Channel") field(PINI, "YES") field(ZNAM, "NO") field(ONAM, "YES") info(autosaveFields,"VAL RVAL") } # If PSs is on then clear Tripped flag. # Otherise, if the ps is off and the # the ps wasn't turned off intentionally, # then consider that the ps has tripped. record(calcout, "$(DEV):TRIPPEDCALC") { field(DESC, "Check if ps tripped") field(SCAN, "10 second") field(CALC, "A?0:B?1:0") field(INPA, "$(DEV):STATE.RVAL") field(INPB, "$(DEV):INTLKSUMY.RVAL") field(OUT, "$(DEV):TRIPPED PP") field(OOPT, "On Change") field(ASG, "Internal") } record(bo, "$(DEV):TRIPPED") { field(DESC, "Supply Tripped") field(PINI, "YES") field(ZNAM, "NO") field(ONAM, "YES") info(autosaveFields,"VAL RVAL") } record(ao, "$(DEV):PSONDLY") { field(DESC, "Turn On delay") field(PINI, "YES") field(PREC, "4") field(EGU, "secs") field(VAL, "$(ONDLY=20)") } record(ao, "$(DEV):PSOFFDLY") { field(DESC, "Turn Off delay") field(PINI, "YES") field(PREC, "4") field(EGU, "secs") field(VAL, "$(OFDLY=10)") } # Note: This pv is only used for EPSCs and EMCOR's # and 50b1 seems to like this set to 20 sec. record(ao, "$(DEV):RAMPSTARTDLY") { field(DESC, "Tansition to ramp delay") field(PINI, "YES") field(PREC, "4") field(EGU, "secs") field(VAL, "$(RDLY=0)") } ######### For PSTYPE=2 Only ############# record(mbbo, "$(DEV):REVSWSTATE") { field(DESC, "Reversing Switch Status") field(DTYP, "Raw Soft Channel") field(PINI, "YES") field(NOBT, "2") field(ZRST, "NORMAL") field(ONST, "REVERSE") field(TWST, "MOVING") field(THST, "Not Available") field(TWSV, "MINOR") field(ZRVL, "0") field(ONVL, "1") field(TWVL, "2") field(THVL, "3") # # If PSTYPE=2 (unipolar supply with polarity switch) # then change DOL=:REVSWSTATE field(DOL, "2") field(OMSL, "closed_loop") } record(bo, "$(DEV):REVSWSET") { field(DESC, "Reversing Switch Set") field(DTYP, "Raw Soft Channel") field(ZNAM, "NORMAL") field(ONAM, "REVERSE") field(PINI, "YES") } #! TextBox(TB0,1860,1540,2180,1600,0,"Dialog",12,1,16777215,"SLC aware code writes SLC HSTA to HSTACTRL",null) #! TextBox(TB5,1940,2160,2200,2280,0,"Dialog",12,1,16777215,"Macros:\nDEV = DEVICE:AREA:POSN\nDEVICE = BEND, QUAD, *COR, etc\nMGNT = MGNT\nAREA = area\nPOSN = position\n",null) #! TextBox(TB3,1880,2000,2300,2120,0,"Dialog",14,1,16777215,"HSTA - hardware status\n\nHSTACTRL contains HSTA from SLC\nHSTACTRLSUB parses significant bits \nHSTACTRLSEQ links to the control bo's - fill in later - only 3 connected now\n\n\n\n",null) #! TextBox(TB1,1880,1660,2180,1980,0,"Dialog",12,1,16777215,"$(DEV):HSTACTRLSUB \nDecode HSTACTRL & link to significant bo's:\ns \nOutputs:\nI - Completely Happy\nJ - Out of Service\nK - In Trouble\nL - Turned off by Operator\nM - Polarity Reversed\nN - Feedback Control\nO - Mini-Stdz Required(always mini-stdz on trim if stdz enabled)\nP - Calib Disabled\nQ - Perturb Disabled\nR - Trim Disabled\nS - Stdz Disabled\nT - No retry on Trim - hook to trimtype\nU - IVBUp(=o) down(=1)\nV - Shunt/booster \nW - No AUTO TRIM (not used)\n",null) #! Record("$(DEV):TURNEDOFF",3140,1907,0,1,"$(DEV):TURNEDOFF")