# # Records for calculating and archiving He and LN2 total Inventory in # the Cryogenic Systems # # Perhaps these should be on the UTIL sioc-cp08-cr01, for now # we have them on sioc-cp00-cr02 Integration # # records to calc He storage tank inventory record(calc, "CST:CP01:1100:INVENTORY"){ field(DESC, "He Tank1 inventory") field(SCAN, "1 second") field(INPA, "CPT:CP01:1100:PRESS NPP") field(PREC, "0") field(EGU, "kg") field(CALC, "A*18") } record(calc, "CST:CP01:1200:INVENTORY"){ field(DESC, "He Tank2 inventory") field(SCAN, "1 second") field(INPA, "CPT:CP01:1200:PRESS NPP") field(PREC, "0") field(EGU, "kg") field(CALC, "A*18") } record(calc, "CST:CP01:1300:INVENTORY"){ field(DESC, "He Tank3 inventory") field(SCAN, "1 second") field(INPA, "CPT:CP01:1300:PRESS NPP") field(PREC, "0") field(EGU, "kg") field(CALC, "A*18") } record(calc, "CST:CP01:1400:INVENTORY"){ field(DESC, "He Tank4 inventory") field(SCAN, "1 second") field(INPA, "CPT:CP01:1400:PRESS NPP") field(PREC, "0") field(EGU, "kg") field(CALC, "A*18") } record(calc, "CST:CP01:1500:INVENTORY"){ field(DESC, "He Tank5 inventory") field(SCAN, "1 second") field(INPA, "CPT:CP01:1500:PRESS NPP") field(PREC, "0") field(EGU, "kg") field(CALC, "A*18") } record(calc, "CST:CP01:1600:INVENTORY"){ field(DESC, "He Tank6 inventory") field(SCAN, "1 second") field(INPA, "CPT:CP01:1600:PRESS NPP") field(PREC, "0") field(EGU, "kg") field(CALC, "A*18") } #total He Storage tank inventory record(calc, "CST:CP01:1000:INVENTORY"){ field(DESC, "Total He Tank inventory") field(SCAN, "1 second") field(INPA, "CST:CP01:1100:INVENTORY NPP") field(INPB, "CST:CP01:1200:INVENTORY NPP") field(INPC, "CST:CP01:1300:INVENTORY NPP") field(INPD, "CST:CP01:1400:INVENTORY NPP") field(INPE, "CST:CP01:1500:INVENTORY NPP") field(INPF, "CST:CP01:1600:INVENTORY NPP") field(PREC, "0") field(EGU, "kg") field(CALC, "A+B+C+D+E+F") } # calc record for 4KCB sub cooler inventory record(calc, "CSC:CP12:2195:INVENTORY"){ field(DESC, "4K CB Subcooler inventory") field(SCAN, "1 second") field(INPA, "CLT:CP12:2195:A:LEVEL NPP") field(PREC, "0") field(EGU, "kg") field(CALC, "A*240/100+((1-(A/100))*50)") } # calc record for 4KCB dewar inventory record(calc, "CHED:CP13:1000:INVENTORY"){ field(DESC, "4K CB dewar inventory") field(SCAN, "1 second") field(INPA, "CLT:CP13:1005:LEVEL NPP") field(PREC, "0") field(EGU, "kg") field(CALC, "A*1200/100+((1-(A/100))*250)") } # calc record for C2 4KCB sub cooler inventory - comment out for now #record(calc, "CSC:CP22:2195:INVENTORY"){ # field(DESC, "4K CB Subcooler inventory") # field(SCAN, "1 second") # field(INPA, "CLT:CP22:2195:A:LEVEL NPP") # field(PREC, "0") # field(EGU, "kg") # field(CALC, "A*240/100+((1-(A/100))*50)") #} # calc record for C2 4KCB dewar inventory #record(calc, "CHED:CP23:1000:INVENTORY"){ # field(DESC, "4K CB dewar inventory") # field(SCAN, "1 second") # field(INPA, "CLT:CP23:1005:LEVEL NPP") # field(PREC, "0") # field(EGU, "kg") # field(CALC, "A*1200/100+((1-(A/100))*250)") #} #total He inventory in system - need to add C2 subcooler and dewar record(calc, "CRYO:CP00:0000:HE_INVENTORY"){ field(DESC, "Total He inventory") field(SCAN, "1 second") field(INPA, "CST:CP01:1000:INVENTORY NPP") field(INPB, "CSC:CP12:2195:INVENTORY NPP") field(INPC, "CHED:CP13:1000:INVENTORY NPP") # field(INPD, "CSC:CP22:2195:INVENTORY NPP") add later # field(INPE, "CHED:CP23:1000:INVENTORY NPP") add later field(PREC, "0") field(EGU, "kg") field(CALC, "A+B+C") } #records to calc LN2 tank inventory record(calc, "CLND:CP08:8101:INVENTORY"){ field(DESC, "LN2 Storage Tank inventory") field(SCAN, "1 second") field(INPA, "CLT:CP08:8101:LEVEL NPP") field(PREC, "0") field(EGU, "Lt") field(CALC, "(77.323*A+.00000166305)*1000/100") } record(calc, "CLND:CP08:8201:INVENTORY"){ field(DESC, "LN2 Storage Tank inventory") field(SCAN, "1 second") field(INPA, "CLT:CP08:8201:LEVEL NPP") field(PREC, "0") field(EGU, "Lt") field(CALC, "(77.323*A+.00000166305)*1000/100") }