record(ai, "CWIC:CP$(CP)4:1520:ORBV") { field(DESC, "PID ORBV") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) EHTR41520.ORBV") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(ai, "CWIC:CP$(CP)4:1520:OVAL") { field(DESC, "PID OVAL") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) EHTR41520.OVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(ai, "CWIC:CP$(CP)4:1520:OUTPUT") { field(DESC, "PID Output") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) EHTR41520O") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(ai, "CWIC:CP$(CP)4:1520:CVAL") { field(DESC, "PID CVAL") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) EHTR41520.CVAL") field(PREC, "2") field(EGU, "K") field(ADEL, "0") } record(ao, "CWIC:CP$(CP)4:1520:MAX") { field(DESC, "PID SP Max") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) EHTR41520_OVH.MAX_X") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CWIC:CP$(CP)4:1520:DMIN") { field(DESC, "PID SP DMIN") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) EHTR41520_OVH.DMIN_X") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CWIC:CP$(CP)4:1520:DMAX") { field(DESC, "PID SP DMAX") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) EHTR41520_OVH.DMAX_X") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CWIC:CP$(CP)4:1520:MDT") { field(DESC, "PID ST MDT") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) EHTR41520_OVH.ST_X") field(PREC, "2") field(EGU, "Sec") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CWIC:CP$(CP)4:1520:KP") { field(DESC, "PID Proportional Gain Kp") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) EHTR41520_OVH.GAINP_X") field(PREC, "4") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CWIC:CP$(CP)4:1520:KI") { field(DESC, "PID Integral Gain Ki") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) EHTR41520_OVH.GAINI_X") field(PREC, "4") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CWIC:CP$(CP)4:1520:KD") { field(DESC, "PID Derivative Gain Kd") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) EHTR41520_OVH.GAIND_X") field(PREC, "4") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(stringout, "CWIC:CP$(CP)4:1520:S") { field(DESC, "PID Mode String") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) EHTR41520_OVH.PV_String_X S 2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CWIC:CP$(CP)4:1520:SP_RQST") { field(DESC, "C$(CP)-WIC-41520 PID SP request") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) EHTR41520_OVH.SP_Rqst") field(PREC, "2") field(EGU, "K") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CWIC:CP$(CP)4:1520:MIN") { field(DESC, "PID SP Min") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) EHTR41520_OVH.MIN_X") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(stringin, "CWIC:CP$(CP)4:1520:PIDTAG") { field(DESC, "2kcb Heater") field(PINI, "YES") field(VAL, "C$(CP)-WIC-41520") } record(ao, "CWIC:CP$(CP)4:1520:PEVAL") { field(DESC, "PID Fail Safe V Pos.") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) EHTR41520.PEVAL") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bo, "CWIC:CP$(CP)4:1520:FSB") { field(DESC, "PID Fail Safe bit") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) EHTR41520.FSB B 0") field(ZNAM, "Last Cmd Val") field(ONAM, "Fail Safe Val") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CWIC:CP$(CP)4:1520:NOMATCH") { field(DESC, "PID inp var no match") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) EHTR41520_OVH.NoMatch") field(ZNAM, "Match") field(ONAM, "Nomatch") } record(bi, "CWIC:CP$(CP)4:1520:CHFAULT") { field(DESC, "PID inp ch fault") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) EHTR41520_OVH.CHFault") field(ZNAM, "Ok") field(ONAM, "Fault") } record(ao, "CWIC:CP$(CP)4:1520:MANPOS_RQST") { field(DESC, "PID Manual Posn request") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) EHTR41520_OVH.ManPos_Rqst") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ai, "CWIC:CP$(CP)4:1520:MODE_STATUS") { field(DESC, "PID Mode Status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) EHTR41520_OVH.Mode_Status") field(HIHI, "4") field(HIGH, "3") field(HHSV, "MAJOR") field(HSV, "MAJOR") } record(bi, "CWIC:CP$(CP)4:1520:INTERLOCK") { field(DESC, "PID Interlock Condition") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) EHTR41520.Interlock_Condition") field(ZNAM, "OK") field(ONAM, "Interlocked") } record(ai, "CWIC:CP$(CP)4:1520:IVAL") { field(DESC, "PID Interlock output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) EHTR41520.IVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(ai, "CWIC:CP$(CP)4:1520:SVAL") { field(DESC, "PID Sequencer output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) EHTR41520.SVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(bi, "CWIC:CP$(CP)4:1520:MMOD") { field(DESC, "PID Manual Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) EHTR41520.mmod") field(ZNAM, "Not Manual") field(ONAM, "Manual") } record(bi, "CWIC:CP$(CP)4:1520:SMOD") { field(DESC, "PID Sequencer Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) EHTR41520.smod") field(ZNAM, "Not Sequencer") field(ONAM, "Sequencer") } record(ai, "CWIC:CP$(CP)4:1520:MODE") { field(DESC, "PIDloop mode (man,auto,seq)") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) EHTR41520.MODE") } record(stringin, "CWIC:CP$(CP)4:1520:MODE_STRING") { field(DESC, "PID Mode String") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) EHTR41520_OVH.Mode_String") } record(bi, "CWIC:CP$(CP)4:1520:PMOD") { field(DESC, "PID Protector Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) EHTR41520.pmod") field(ZNAM, "Not Protector") field(ONAM, "Protector") } record(bi, "CWIC:CP$(CP)4:1520:IMOD") { field(DESC, "PID Interlock Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) EHTR41520.imod") field(ZNAM, "No Interlock") field(ONAM, "Interlock") } record(stringin, "CWIC:CP$(CP)4:1520:ACTUATOR") { field(DESC, "actuator name for the pid loop") field(PINI, "YES") field(VAL, "EHTR-41520") } record(ai, "CWIC:CP$(CP)4:1520:PVAL") { field(DESC, "PID Protector output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) EHTR41520.PVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(stringin, "CWIC:CP$(CP)4:1520:TEXT1") { field(DESC, "PID Information 1") field(PINI, "YES") field(DTYP, "Soft Channel") info(autosaveFields, "VAL") } record(ai, "CWIC:CP$(CP)4:1520:MVAL") { field(DESC, "PID manual mode output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) EHTR41520.MVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(bi, "CWIC:CP$(CP)4:1520:AMOD") { field(DESC, "PID Auto Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) EHTR41520.amod") field(ZNAM, "Not Auto") field(ONAM, "Auto") } record(ai, "CWIC:CP$(CP)4:1520:AVAL") { field(DESC, "PID Auto mode output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) EHTR41520.AVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(bi, "CWIC:CP$(CP)4:1520:IL_LATCH") { field(DESC, "interlock latched indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) EHTR41520.Interlock_Condition_L") field(ZNAM, "Ok") field(ONAM, "Latched") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CWIC:CP$(CP)4:1520:IL_RESET") { field(DESC, "Interlock Latch Reset") field(DTYP, "EtherIP") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Reset") field(ONAM, "Reset") field(OUT, "@$(PLC_NAME) EHTR41520.Interlock_Condition_Reset B 0") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CWIC:CP$(CP)4:1520:MANUAL") { field(DESC, "Manual Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Manual") field(ONAM, "Manual") field(OUT, "@$(PLC_NAME) EHTR41520_OVH.Manual B 0") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CWIC:CP$(CP)4:1520:SEQUENCER") { field(DESC, "SequencerMode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Sequencer") field(ONAM, "Sequencer") field(OUT, "@$(PLC_NAME) EHTR41520_OVH.Sequencer B 0") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CWIC:CP$(CP)4:1520:AUTO") { field(DESC, "Auto Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "not Auto") field(ONAM, "Auto") field(OUT, "@$(PLC_NAME) EHTR41520_OVH.Auto B 0") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CWIC:CP$(CP)4:1520:OVERRIDE") { field(DESC, "Override state select") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) EHTR41520.Override B 0") field(ZNAM, "Not Override") field(ONAM, "Override") field(ASG, "CRYO") } record(bi, "CWIC:CP$(CP)4:1520:OMOD") { field(DESC, "Override state status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) EHTR41520.omod") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(ai, "CWIC:CP$(CP)4:1520:OMAX") { field(DESC, "Maximum output limit in all modes") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) EHTR41520.Output_Limit") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(bi, "CWIC:CP$(CP)4:1520:OMAX_EN") { field(DESC, "Maximum output limit enforced") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) EHTR41520.Output_Limit_EN") field(ZNAM, "Not Enforced") field(ONAM, "Enforced") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(ao, "CWIC:CP$(CP)4:1520:PI_SP") { field(DESC, "SP PID Parameter Input") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) EHTR41520.Parameter_Input B 0") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CWIC:CP$(CP)4:1520:PI_MIN") { field(DESC, "MIN PID Parameter Input") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) EHTR41520.Parameter_Input B 1") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CWIC:CP$(CP)4:1520:PI_MAX") { field(DESC, "MAX PID Parameter Input") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) EHTR41520.Parameter_Input B 2") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CWIC:CP$(CP)4:1520:ALM") { field(DESC, "Readback vs output discrepancy") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) EHTR41520.ER") field(ZNAM, "No Error") field(ONAM, "Error") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(ai, "CPIC:CP$(CP)4:1212:ORBV") { field(DESC, "PID ORBV") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41212.ORBV") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(ai, "CPIC:CP$(CP)4:1212:OVAL") { field(DESC, "PID OVAL") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41212.OVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(ai, "CPIC:CP$(CP)4:1212:OUTPUT") { field(DESC, "PID Output") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41212O") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(ai, "CPIC:CP$(CP)4:1212:CVAL") { field(DESC, "PID CVAL") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41212.CVAL") field(PREC, "2") field(EGU, "bara") field(ADEL, "0") } record(ao, "CPIC:CP$(CP)4:1212:MAX") { field(DESC, "PID SP Max") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41212_OVH.MAX_X") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPIC:CP$(CP)4:1212:DMIN") { field(DESC, "PID SP DMIN") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41212_OVH.DMIN_X") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPIC:CP$(CP)4:1212:DMAX") { field(DESC, "PID SP DMAX") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41212_OVH.DMAX_X") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPIC:CP$(CP)4:1212:MDT") { field(DESC, "PID ST MDT") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41212_OVH.ST_X") field(PREC, "2") field(EGU, "Sec") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPIC:CP$(CP)4:1212:KP") { field(DESC, "PID Proportional Gain Kp") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41212_OVH.GAINP_X") field(PREC, "4") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPIC:CP$(CP)4:1212:KI") { field(DESC, "PID Integral Gain Ki") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41212_OVH.GAINI_X") field(PREC, "4") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPIC:CP$(CP)4:1212:KD") { field(DESC, "PID Derivative Gain Kd") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41212_OVH.GAIND_X") field(PREC, "4") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(stringout, "CPIC:CP$(CP)4:1212:S") { field(DESC, "PID Mode String") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41212_OVH.PV_String_X S 2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPIC:CP$(CP)4:1212:SP_RQST") { field(DESC, "C$(CP)-PIC-41212 PID SP request") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41212_OVH.SP_Rqst") field(PREC, "2") field(EGU, "bara") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPIC:CP$(CP)4:1212:MIN") { field(DESC, "PID SP Min") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41212_OVH.MIN_X") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(stringin, "CPIC:CP$(CP)4:1212:PIDTAG") { field(DESC, "CC Bypass") field(PINI, "YES") field(VAL, "C$(CP)-PIC-41212") } record(ao, "CPIC:CP$(CP)4:1212:PEVAL") { field(DESC, "PID Fail Safe V Pos.") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41212.PEVAL") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bo, "CPIC:CP$(CP)4:1212:FSB") { field(DESC, "PID Fail Safe bit") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41212.FSB B 0") field(ZNAM, "Last Cmd Val") field(ONAM, "Fail Safe Val") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CPIC:CP$(CP)4:1212:NOMATCH") { field(DESC, "PID inp var no match") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41212_OVH.NoMatch") field(ZNAM, "Match") field(ONAM, "Nomatch") } record(bi, "CPIC:CP$(CP)4:1212:CHFAULT") { field(DESC, "PID inp ch fault") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41212_OVH.CHFault") field(ZNAM, "Ok") field(ONAM, "Fault") } record(ao, "CPIC:CP$(CP)4:1212:MANPOS_RQST") { field(DESC, "PID Manual Posn request") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41212_OVH.ManPos_Rqst") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ai, "CPIC:CP$(CP)4:1212:MODE_STATUS") { field(DESC, "PID Mode Status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41212_OVH.Mode_Status") field(HIHI, "4") field(HIGH, "3") field(HHSV, "MAJOR") field(HSV, "MAJOR") } record(bi, "CPIC:CP$(CP)4:1212:INTERLOCK") { field(DESC, "PID Interlock Condition") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41212.Interlock_Condition") field(ZNAM, "OK") field(ONAM, "Interlocked") } record(ai, "CPIC:CP$(CP)4:1212:IVAL") { field(DESC, "PID Interlock output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41212.IVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(ai, "CPIC:CP$(CP)4:1212:SVAL") { field(DESC, "PID Sequencer output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41212.SVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(bi, "CPIC:CP$(CP)4:1212:MMOD") { field(DESC, "PID Manual Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41212.mmod") field(ZNAM, "Not Manual") field(ONAM, "Manual") } record(bi, "CPIC:CP$(CP)4:1212:SMOD") { field(DESC, "PID Sequencer Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41212.smod") field(ZNAM, "Not Sequencer") field(ONAM, "Sequencer") } record(ai, "CPIC:CP$(CP)4:1212:MODE") { field(DESC, "PIDloop mode (man,auto,seq)") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41212.MODE") } record(stringin, "CPIC:CP$(CP)4:1212:MODE_STRING") { field(DESC, "PID Mode String") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41212_OVH.Mode_String") } record(bi, "CPIC:CP$(CP)4:1212:PMOD") { field(DESC, "PID Protector Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41212.pmod") field(ZNAM, "Not Protector") field(ONAM, "Protector") } record(bi, "CPIC:CP$(CP)4:1212:IMOD") { field(DESC, "PID Interlock Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41212.imod") field(ZNAM, "No Interlock") field(ONAM, "Interlock") } record(stringin, "CPIC:CP$(CP)4:1212:ACTUATOR") { field(DESC, "actuator name for the pid loop") field(PINI, "YES") field(VAL, "PV-41212") } record(ai, "CPIC:CP$(CP)4:1212:PVAL") { field(DESC, "PID Protector output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41212.PVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(stringin, "CPIC:CP$(CP)4:1212:TEXT1") { field(DESC, "PID Information 1") field(PINI, "YES") field(DTYP, "Soft Channel") info(autosaveFields, "VAL") } record(ai, "CPIC:CP$(CP)4:1212:MVAL") { field(DESC, "PID manual mode output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41212.MVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(bi, "CPIC:CP$(CP)4:1212:AMOD") { field(DESC, "PID Auto Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41212.amod") field(ZNAM, "Not Auto") field(ONAM, "Auto") } record(ai, "CPIC:CP$(CP)4:1212:AVAL") { field(DESC, "PID Auto mode output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41212.AVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(bi, "CPIC:CP$(CP)4:1212:IL_LATCH") { field(DESC, "interlock latched indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41212.Interlock_Condition_L") field(ZNAM, "Ok") field(ONAM, "Latched") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CPIC:CP$(CP)4:1212:IL_RESET") { field(DESC, "Interlock Latch Reset") field(DTYP, "EtherIP") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Reset") field(ONAM, "Reset") field(OUT, "@$(PLC_NAME) PV41212.Interlock_Condition_Reset B 0") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CPIC:CP$(CP)4:1212:MANUAL") { field(DESC, "Manual Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Manual") field(ONAM, "Manual") field(OUT, "@$(PLC_NAME) PV41212_OVH.Manual B 0") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CPIC:CP$(CP)4:1212:SEQUENCER") { field(DESC, "SequencerMode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Sequencer") field(ONAM, "Sequencer") field(OUT, "@$(PLC_NAME) PV41212_OVH.Sequencer B 0") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CPIC:CP$(CP)4:1212:AUTO") { field(DESC, "Auto Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "not Auto") field(ONAM, "Auto") field(OUT, "@$(PLC_NAME) PV41212_OVH.Auto B 0") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CPIC:CP$(CP)4:1212:OVERRIDE") { field(DESC, "Override state select") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41212.Override B 0") field(ZNAM, "Not Override") field(ONAM, "Override") field(ASG, "CRYO") } record(bi, "CPIC:CP$(CP)4:1212:OMOD") { field(DESC, "Override state status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41212.omod") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(ai, "CPIC:CP$(CP)4:1212:OMAX") { field(DESC, "Maximum output limit in all modes") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41212.Output_Limit") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(bi, "CPIC:CP$(CP)4:1212:OMAX_EN") { field(DESC, "Maximum output limit enforced") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41212.Output_Limit_EN") field(ZNAM, "Not Enforced") field(ONAM, "Enforced") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(ao, "CPIC:CP$(CP)4:1212:PI_SP") { field(DESC, "SP PID Parameter Input") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41212.Parameter_Input B 0") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPIC:CP$(CP)4:1212:PI_MIN") { field(DESC, "MIN PID Parameter Input") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41212.Parameter_Input B 1") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPIC:CP$(CP)4:1212:PI_MAX") { field(DESC, "MAX PID Parameter Input") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41212.Parameter_Input B 2") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CPIC:CP$(CP)4:1212:ALM") { field(DESC, "Readback vs output discrepancy") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41212.ER") field(ZNAM, "No Error") field(ONAM, "Error") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(ai, "CFIC:CP$(CP)4:1160:ORBV") { field(DESC, "PID ORBV") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41160.ORBV") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(ai, "CFIC:CP$(CP)4:1160:OVAL") { field(DESC, "PID OVAL") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41160.OVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(ai, "CFIC:CP$(CP)4:1160:OUTPUT") { field(DESC, "PID Output") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41160O") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(ai, "CFIC:CP$(CP)4:1160:CVAL") { field(DESC, "PID CVAL") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41160.CVAL") field(PREC, "2") field(EGU, "g/s") field(ADEL, "0") } record(ao, "CFIC:CP$(CP)4:1160:MAX") { field(DESC, "PID SP Max") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41160_OVH.MAX_X") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:1160:DMIN") { field(DESC, "PID SP DMIN") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41160_OVH.DMIN_X") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:1160:DMAX") { field(DESC, "PID SP DMAX") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41160_OVH.DMAX_X") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:1160:MDT") { field(DESC, "PID ST MDT") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41160_OVH.ST_X") field(PREC, "2") field(EGU, "Sec") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:1160:KP") { field(DESC, "PID Proportional Gain Kp") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41160_OVH.GAINP_X") field(PREC, "4") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:1160:KI") { field(DESC, "PID Integral Gain Ki") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41160_OVH.GAINI_X") field(PREC, "4") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:1160:KD") { field(DESC, "PID Derivative Gain Kd") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41160_OVH.GAIND_X") field(PREC, "4") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(stringout, "CFIC:CP$(CP)4:1160:S") { field(DESC, "PID Mode String") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41160_OVH.PV_String_X S 2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:1160:SP_RQST") { field(DESC, "C$(CP)-FIC-41160 PID SP request") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41160_OVH.SP_Rqst") field(PREC, "2") field(EGU, "g/s") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:1160:MIN") { field(DESC, "PID SP Min") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41160_OVH.MIN_X") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(stringin, "CFIC:CP$(CP)4:1160:PIDTAG") { field(DESC, "CC6 Outlet Valve") field(PINI, "YES") field(VAL, "C$(CP)-FIC-41160") } record(ao, "CFIC:CP$(CP)4:1160:PEVAL") { field(DESC, "PID Fail Safe V Pos.") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41160.PEVAL") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bo, "CFIC:CP$(CP)4:1160:FSB") { field(DESC, "PID Fail Safe bit") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41160.FSB B 0") field(ZNAM, "Last Cmd Val") field(ONAM, "Fail Safe Val") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CFIC:CP$(CP)4:1160:NOMATCH") { field(DESC, "PID inp var no match") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41160_OVH.NoMatch") field(ZNAM, "Match") field(ONAM, "Nomatch") } record(bi, "CFIC:CP$(CP)4:1160:CHFAULT") { field(DESC, "PID inp ch fault") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41160_OVH.CHFault") field(ZNAM, "Ok") field(ONAM, "Fault") } record(ao, "CFIC:CP$(CP)4:1160:MANPOS_RQST") { field(DESC, "PID Manual Posn request") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41160_OVH.ManPos_Rqst") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ai, "CFIC:CP$(CP)4:1160:MODE_STATUS") { field(DESC, "PID Mode Status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41160_OVH.Mode_Status") field(HIHI, "4") field(HIGH, "3") field(HHSV, "MAJOR") field(HSV, "MAJOR") } record(bi, "CFIC:CP$(CP)4:1160:INTERLOCK") { field(DESC, "PID Interlock Condition") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41160.Interlock_Condition") field(ZNAM, "OK") field(ONAM, "Interlocked") } record(ai, "CFIC:CP$(CP)4:1160:IVAL") { field(DESC, "PID Interlock output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41160.IVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(ai, "CFIC:CP$(CP)4:1160:SVAL") { field(DESC, "PID Sequencer output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41160.SVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(bi, "CFIC:CP$(CP)4:1160:MMOD") { field(DESC, "PID Manual Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41160.mmod") field(ZNAM, "Not Manual") field(ONAM, "Manual") } record(bi, "CFIC:CP$(CP)4:1160:SMOD") { field(DESC, "PID Sequencer Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41160.smod") field(ZNAM, "Not Sequencer") field(ONAM, "Sequencer") } record(ai, "CFIC:CP$(CP)4:1160:MODE") { field(DESC, "PIDloop mode (man,auto,seq)") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41160.MODE") } record(stringin, "CFIC:CP$(CP)4:1160:MODE_STRING") { field(DESC, "PID Mode String") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41160_OVH.Mode_String") } record(bi, "CFIC:CP$(CP)4:1160:PMOD") { field(DESC, "PID Protector Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41160.pmod") field(ZNAM, "Not Protector") field(ONAM, "Protector") } record(bi, "CFIC:CP$(CP)4:1160:IMOD") { field(DESC, "PID Interlock Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41160.imod") field(ZNAM, "No Interlock") field(ONAM, "Interlock") } record(stringin, "CFIC:CP$(CP)4:1160:ACTUATOR") { field(DESC, "actuator name for the pid loop") field(PINI, "YES") field(VAL, "PV-41160") } record(ai, "CFIC:CP$(CP)4:1160:PVAL") { field(DESC, "PID Protector output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41160.PVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(stringin, "CFIC:CP$(CP)4:1160:TEXT1") { field(DESC, "PID Information 1") field(PINI, "YES") field(DTYP, "Soft Channel") info(autosaveFields, "VAL") } record(ai, "CFIC:CP$(CP)4:1160:MVAL") { field(DESC, "PID manual mode output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41160.MVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(bi, "CFIC:CP$(CP)4:1160:AMOD") { field(DESC, "PID Auto Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41160.amod") field(ZNAM, "Not Auto") field(ONAM, "Auto") } record(ai, "CFIC:CP$(CP)4:1160:AVAL") { field(DESC, "PID Auto mode output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41160.AVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(bi, "CFIC:CP$(CP)4:1160:IL_LATCH") { field(DESC, "interlock latched indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41160.Interlock_Condition_L") field(ZNAM, "Ok") field(ONAM, "Latched") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CFIC:CP$(CP)4:1160:IL_RESET") { field(DESC, "Interlock Latch Reset") field(DTYP, "EtherIP") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Reset") field(ONAM, "Reset") field(OUT, "@$(PLC_NAME) PV41160.Interlock_Condition_Reset B 0") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CFIC:CP$(CP)4:1160:MANUAL") { field(DESC, "Manual Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Manual") field(ONAM, "Manual") field(OUT, "@$(PLC_NAME) PV41160_OVH.Manual B 0") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CFIC:CP$(CP)4:1160:SEQUENCER") { field(DESC, "SequencerMode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Sequencer") field(ONAM, "Sequencer") field(OUT, "@$(PLC_NAME) PV41160_OVH.Sequencer B 0") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CFIC:CP$(CP)4:1160:AUTO") { field(DESC, "Auto Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "not Auto") field(ONAM, "Auto") field(OUT, "@$(PLC_NAME) PV41160_OVH.Auto B 0") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CFIC:CP$(CP)4:1160:OVERRIDE") { field(DESC, "Override state select") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41160.Override B 0") field(ZNAM, "Not Override") field(ONAM, "Override") field(ASG, "CRYO") } record(bi, "CFIC:CP$(CP)4:1160:OMOD") { field(DESC, "Override state status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41160.omod") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(ai, "CFIC:CP$(CP)4:1160:OMAX") { field(DESC, "Maximum output limit in all modes") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41160.Output_Limit") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(bi, "CFIC:CP$(CP)4:1160:OMAX_EN") { field(DESC, "Maximum output limit enforced") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41160.Output_Limit_EN") field(ZNAM, "Not Enforced") field(ONAM, "Enforced") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(ao, "CFIC:CP$(CP)4:1160:PI_SP") { field(DESC, "SP PID Parameter Input") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41160.Parameter_Input B 0") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:1160:PI_MIN") { field(DESC, "MIN PID Parameter Input") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41160.Parameter_Input B 1") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:1160:PI_MAX") { field(DESC, "MAX PID Parameter Input") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41160.Parameter_Input B 2") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CFIC:CP$(CP)4:1160:ALM") { field(DESC, "Readback vs output discrepancy") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41160.ER") field(ZNAM, "No Error") field(ONAM, "Error") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(ai, "CFIC:CP$(CP)4:1170:ORBV") { field(DESC, "PID ORBV") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41170.ORBV") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(ai, "CFIC:CP$(CP)4:1170:OVAL") { field(DESC, "PID OVAL") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41170.OVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(ai, "CFIC:CP$(CP)4:1170:OUTPUT") { field(DESC, "PID Output") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41170O") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(ai, "CFIC:CP$(CP)4:1170:CVAL") { field(DESC, "PID CVAL") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41170.CVAL") field(PREC, "2") field(EGU, "g/s") field(ADEL, "0") } record(ao, "CFIC:CP$(CP)4:1170:MAX") { field(DESC, "PID SP Max") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41170_OVH.MAX_X") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:1170:DMIN") { field(DESC, "PID SP DMIN") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41170_OVH.DMIN_X") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:1170:DMAX") { field(DESC, "PID SP DMAX") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41170_OVH.DMAX_X") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:1170:MDT") { field(DESC, "PID ST MDT") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41170_OVH.ST_X") field(PREC, "2") field(EGU, "Sec") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:1170:KP") { field(DESC, "PID Proportional Gain Kp") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41170_OVH.GAINP_X") field(PREC, "4") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:1170:KI") { field(DESC, "PID Integral Gain Ki") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41170_OVH.GAINI_X") field(PREC, "4") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:1170:KD") { field(DESC, "PID Derivative Gain Kd") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41170_OVH.GAIND_X") field(PREC, "4") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(stringout, "CFIC:CP$(CP)4:1170:S") { field(DESC, "PID Mode String") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41170_OVH.PV_String_X S 2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:1170:SP_RQST") { field(DESC, "C$(CP)-FIC-41170 PID SP request") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41170_OVH.SP_Rqst") field(PREC, "2") field(EGU, "g/s") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:1170:MIN") { field(DESC, "PID SP Min") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41170_OVH.MIN_X") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(stringin, "CFIC:CP$(CP)4:1170:PIDTAG") { field(DESC, "Cold Box Outlet Valve") field(PINI, "YES") field(VAL, "C$(CP)-FIC-41170") } record(ao, "CFIC:CP$(CP)4:1170:PEVAL") { field(DESC, "PID Fail Safe V Pos.") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41170.PEVAL") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bo, "CFIC:CP$(CP)4:1170:FSB") { field(DESC, "PID Fail Safe bit") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41170.FSB B 0") field(ZNAM, "Last Cmd Val") field(ONAM, "Fail Safe Val") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CFIC:CP$(CP)4:1170:NOMATCH") { field(DESC, "PID inp var no match") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41170_OVH.NoMatch") field(ZNAM, "Match") field(ONAM, "Nomatch") } record(bi, "CFIC:CP$(CP)4:1170:CHFAULT") { field(DESC, "PID inp ch fault") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41170_OVH.CHFault") field(ZNAM, "Ok") field(ONAM, "Fault") } record(ao, "CFIC:CP$(CP)4:1170:MANPOS_RQST") { field(DESC, "PID Manual Posn request") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41170_OVH.ManPos_Rqst") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ai, "CFIC:CP$(CP)4:1170:MODE_STATUS") { field(DESC, "PID Mode Status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41170_OVH.Mode_Status") field(HIHI, "4") field(HIGH, "3") field(HHSV, "MAJOR") field(HSV, "MAJOR") } record(bi, "CFIC:CP$(CP)4:1170:INTERLOCK") { field(DESC, "PID Interlock Condition") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41170.Interlock_Condition") field(ZNAM, "OK") field(ONAM, "Interlocked") } record(ai, "CFIC:CP$(CP)4:1170:IVAL") { field(DESC, "PID Interlock output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41170.IVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(ai, "CFIC:CP$(CP)4:1170:SVAL") { field(DESC, "PID Sequencer output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41170.SVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(bi, "CFIC:CP$(CP)4:1170:MMOD") { field(DESC, "PID Manual Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41170.mmod") field(ZNAM, "Not Manual") field(ONAM, "Manual") } record(bi, "CFIC:CP$(CP)4:1170:SMOD") { field(DESC, "PID Sequencer Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41170.smod") field(ZNAM, "Not Sequencer") field(ONAM, "Sequencer") } record(ai, "CFIC:CP$(CP)4:1170:MODE") { field(DESC, "PIDloop mode (man,auto,seq)") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41170.MODE") } record(stringin, "CFIC:CP$(CP)4:1170:MODE_STRING") { field(DESC, "PID Mode String") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41170_OVH.Mode_String") } record(bi, "CFIC:CP$(CP)4:1170:PMOD") { field(DESC, "PID Protector Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41170.pmod") field(ZNAM, "Not Protector") field(ONAM, "Protector") } record(bi, "CFIC:CP$(CP)4:1170:IMOD") { field(DESC, "PID Interlock Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41170.imod") field(ZNAM, "No Interlock") field(ONAM, "Interlock") } record(stringin, "CFIC:CP$(CP)4:1170:ACTUATOR") { field(DESC, "actuator name for the pid loop") field(PINI, "YES") field(VAL, "PV-41170") } record(ai, "CFIC:CP$(CP)4:1170:PVAL") { field(DESC, "PID Protector output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41170.PVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(stringin, "CFIC:CP$(CP)4:1170:TEXT1") { field(DESC, "PID Information 1") field(PINI, "YES") field(DTYP, "Soft Channel") info(autosaveFields, "VAL") } record(ai, "CFIC:CP$(CP)4:1170:MVAL") { field(DESC, "PID manual mode output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41170.MVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(bi, "CFIC:CP$(CP)4:1170:AMOD") { field(DESC, "PID Auto Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41170.amod") field(ZNAM, "Not Auto") field(ONAM, "Auto") } record(ai, "CFIC:CP$(CP)4:1170:AVAL") { field(DESC, "PID Auto mode output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41170.AVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(bi, "CFIC:CP$(CP)4:1170:IL_LATCH") { field(DESC, "interlock latched indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41170.Interlock_Condition_L") field(ZNAM, "Ok") field(ONAM, "Latched") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CFIC:CP$(CP)4:1170:IL_RESET") { field(DESC, "Interlock Latch Reset") field(DTYP, "EtherIP") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Reset") field(ONAM, "Reset") field(OUT, "@$(PLC_NAME) PV41170.Interlock_Condition_Reset B 0") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CFIC:CP$(CP)4:1170:MANUAL") { field(DESC, "Manual Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Manual") field(ONAM, "Manual") field(OUT, "@$(PLC_NAME) PV41170_OVH.Manual B 0") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CFIC:CP$(CP)4:1170:SEQUENCER") { field(DESC, "SequencerMode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Sequencer") field(ONAM, "Sequencer") field(OUT, "@$(PLC_NAME) PV41170_OVH.Sequencer B 0") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CFIC:CP$(CP)4:1170:AUTO") { field(DESC, "Auto Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "not Auto") field(ONAM, "Auto") field(OUT, "@$(PLC_NAME) PV41170_OVH.Auto B 0") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CFIC:CP$(CP)4:1170:OVERRIDE") { field(DESC, "Override state select") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41170.Override B 0") field(ZNAM, "Not Override") field(ONAM, "Override") field(ASG, "CRYO") } record(bi, "CFIC:CP$(CP)4:1170:OMOD") { field(DESC, "Override state status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41170.omod") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(ai, "CFIC:CP$(CP)4:1170:OMAX") { field(DESC, "Maximum output limit in all modes") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41170.Output_Limit") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(bi, "CFIC:CP$(CP)4:1170:OMAX_EN") { field(DESC, "Maximum output limit enforced") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41170.Output_Limit_EN") field(ZNAM, "Not Enforced") field(ONAM, "Enforced") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(ao, "CFIC:CP$(CP)4:1170:PI_SP") { field(DESC, "SP PID Parameter Input") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41170.Parameter_Input B 0") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:1170:PI_MIN") { field(DESC, "MIN PID Parameter Input") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41170.Parameter_Input B 1") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:1170:PI_MAX") { field(DESC, "MAX PID Parameter Input") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41170.Parameter_Input B 2") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CFIC:CP$(CP)4:1170:ALM") { field(DESC, "Readback vs output discrepancy") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41170.ER") field(ZNAM, "No Error") field(ONAM, "Error") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(ai, "CPIC:CP$(CP)4:1500:ORBV") { field(DESC, "PID ORBV") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41500.ORBV") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(ai, "CPIC:CP$(CP)4:1500:OVAL") { field(DESC, "PID OVAL") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41500.OVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(ai, "CPIC:CP$(CP)4:1500:OUTPUT") { field(DESC, "PID Output") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41500O") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(ai, "CPIC:CP$(CP)4:1500:CVAL") { field(DESC, "PID CVAL") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41500.CVAL") field(PREC, "2") field(EGU, "bara") field(ADEL, "0") } record(ao, "CPIC:CP$(CP)4:1500:MAX") { field(DESC, "PID SP Max") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41500_OVH.MAX_X") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPIC:CP$(CP)4:1500:DMIN") { field(DESC, "PID SP DMIN") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41500_OVH.DMIN_X") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPIC:CP$(CP)4:1500:DMAX") { field(DESC, "PID SP DMAX") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41500_OVH.DMAX_X") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPIC:CP$(CP)4:1500:MDT") { field(DESC, "PID ST MDT") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41500_OVH.ST_X") field(PREC, "2") field(EGU, "Sec") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPIC:CP$(CP)4:1500:KP") { field(DESC, "PID Proportional Gain Kp") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41500_OVH.GAINP_X") field(PREC, "4") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPIC:CP$(CP)4:1500:KI") { field(DESC, "PID Integral Gain Ki") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41500_OVH.GAINI_X") field(PREC, "4") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPIC:CP$(CP)4:1500:KD") { field(DESC, "PID Derivative Gain Kd") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41500_OVH.GAIND_X") field(PREC, "4") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(stringout, "CPIC:CP$(CP)4:1500:S") { field(DESC, "PID Mode String") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41500_OVH.PV_String_X S 2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPIC:CP$(CP)4:1500:SP_RQST") { field(DESC, "C$(CP)-PIC-41500 PID SP request") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41500_OVH.SP_Rqst") field(PREC, "2") field(EGU, "bara") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPIC:CP$(CP)4:1500:MIN") { field(DESC, "PID SP Min") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41500_OVH.MIN_X") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(stringin, "CPIC:CP$(CP)4:1500:PIDTAG") { field(DESC, "4K Inlet from Dewar") field(PINI, "YES") field(VAL, "C$(CP)-PIC-41500") } record(ao, "CPIC:CP$(CP)4:1500:PEVAL") { field(DESC, "PID Fail Safe V Pos.") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41500.PEVAL") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bo, "CPIC:CP$(CP)4:1500:FSB") { field(DESC, "PID Fail Safe bit") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41500.FSB B 0") field(ZNAM, "Last Cmd Val") field(ONAM, "Fail Safe Val") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CPIC:CP$(CP)4:1500:NOMATCH") { field(DESC, "PID inp var no match") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41500_OVH.NoMatch") field(ZNAM, "Match") field(ONAM, "Nomatch") } record(bi, "CPIC:CP$(CP)4:1500:CHFAULT") { field(DESC, "PID inp ch fault") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41500_OVH.CHFault") field(ZNAM, "Ok") field(ONAM, "Fault") } record(ao, "CPIC:CP$(CP)4:1500:MANPOS_RQST") { field(DESC, "PID Manual Posn request") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41500_OVH.ManPos_Rqst") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ai, "CPIC:CP$(CP)4:1500:MODE_STATUS") { field(DESC, "PID Mode Status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41500_OVH.Mode_Status") field(HIHI, "4") field(HIGH, "3") field(HHSV, "MAJOR") field(HSV, "MAJOR") } record(bi, "CPIC:CP$(CP)4:1500:INTERLOCK") { field(DESC, "PID Interlock Condition") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41500.Interlock_Condition") field(ZNAM, "OK") field(ONAM, "Interlocked") } record(ai, "CPIC:CP$(CP)4:1500:IVAL") { field(DESC, "PID Interlock output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41500.IVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(ai, "CPIC:CP$(CP)4:1500:SVAL") { field(DESC, "PID Sequencer output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41500.SVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(bi, "CPIC:CP$(CP)4:1500:MMOD") { field(DESC, "PID Manual Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41500.mmod") field(ZNAM, "Not Manual") field(ONAM, "Manual") } record(bi, "CPIC:CP$(CP)4:1500:SMOD") { field(DESC, "PID Sequencer Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41500.smod") field(ZNAM, "Not Sequencer") field(ONAM, "Sequencer") } record(ai, "CPIC:CP$(CP)4:1500:MODE") { field(DESC, "PIDloop mode (man,auto,seq)") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41500.MODE") } record(stringin, "CPIC:CP$(CP)4:1500:MODE_STRING") { field(DESC, "PID Mode String") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41500_OVH.Mode_String") } record(bi, "CPIC:CP$(CP)4:1500:PMOD") { field(DESC, "PID Protector Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41500.pmod") field(ZNAM, "Not Protector") field(ONAM, "Protector") } record(bi, "CPIC:CP$(CP)4:1500:IMOD") { field(DESC, "PID Interlock Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41500.imod") field(ZNAM, "No Interlock") field(ONAM, "Interlock") } record(stringin, "CPIC:CP$(CP)4:1500:ACTUATOR") { field(DESC, "actuator name for the pid loop") field(PINI, "YES") field(VAL, "PV-41500") } record(ai, "CPIC:CP$(CP)4:1500:PVAL") { field(DESC, "PID Protector output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41500.PVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(stringin, "CPIC:CP$(CP)4:1500:TEXT1") { field(DESC, "PID Information 1") field(PINI, "YES") field(DTYP, "Soft Channel") info(autosaveFields, "VAL") } record(ai, "CPIC:CP$(CP)4:1500:MVAL") { field(DESC, "PID manual mode output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41500.MVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(bi, "CPIC:CP$(CP)4:1500:AMOD") { field(DESC, "PID Auto Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41500.amod") field(ZNAM, "Not Auto") field(ONAM, "Auto") } record(ai, "CPIC:CP$(CP)4:1500:AVAL") { field(DESC, "PID Auto mode output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41500.AVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(bi, "CPIC:CP$(CP)4:1500:IL_LATCH") { field(DESC, "interlock latched indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41500.Interlock_Condition_L") field(ZNAM, "Ok") field(ONAM, "Latched") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CPIC:CP$(CP)4:1500:IL_RESET") { field(DESC, "Interlock Latch Reset") field(DTYP, "EtherIP") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Reset") field(ONAM, "Reset") field(OUT, "@$(PLC_NAME) PV41500.Interlock_Condition_Reset B 0") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CPIC:CP$(CP)4:1500:MANUAL") { field(DESC, "Manual Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Manual") field(ONAM, "Manual") field(OUT, "@$(PLC_NAME) PV41500_OVH.Manual B 0") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CPIC:CP$(CP)4:1500:SEQUENCER") { field(DESC, "SequencerMode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Sequencer") field(ONAM, "Sequencer") field(OUT, "@$(PLC_NAME) PV41500_OVH.Sequencer B 0") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CPIC:CP$(CP)4:1500:AUTO") { field(DESC, "Auto Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "not Auto") field(ONAM, "Auto") field(OUT, "@$(PLC_NAME) PV41500_OVH.Auto B 0") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CPIC:CP$(CP)4:1500:OVERRIDE") { field(DESC, "Override state select") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41500.Override B 0") field(ZNAM, "Not Override") field(ONAM, "Override") field(ASG, "CRYO") } record(bi, "CPIC:CP$(CP)4:1500:OMOD") { field(DESC, "Override state status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41500.omod") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(ai, "CPIC:CP$(CP)4:1500:OMAX") { field(DESC, "Maximum output limit in all modes") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41500.Output_Limit") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(bi, "CPIC:CP$(CP)4:1500:OMAX_EN") { field(DESC, "Maximum output limit enforced") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41500.Output_Limit_EN") field(ZNAM, "Not Enforced") field(ONAM, "Enforced") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(ao, "CPIC:CP$(CP)4:1500:PI_SP") { field(DESC, "SP PID Parameter Input") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41500.Parameter_Input B 0") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPIC:CP$(CP)4:1500:PI_MIN") { field(DESC, "MIN PID Parameter Input") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41500.Parameter_Input B 1") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPIC:CP$(CP)4:1500:PI_MAX") { field(DESC, "MAX PID Parameter Input") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41500.Parameter_Input B 2") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CPIC:CP$(CP)4:1500:ALM") { field(DESC, "Readback vs output discrepancy") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41500.ER") field(ZNAM, "No Error") field(ONAM, "Error") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(ai, "CFIC:CP$(CP)4:1565:ORBV") { field(DESC, "PID ORBV") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41565.ORBV") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(ai, "CFIC:CP$(CP)4:1565:OVAL") { field(DESC, "PID OVAL") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41565.OVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(ai, "CFIC:CP$(CP)4:1565:OUTPUT") { field(DESC, "PID Output") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41565O") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(ai, "CFIC:CP$(CP)4:1565:CVAL") { field(DESC, "PID CVAL") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41565.CVAL") field(PREC, "2") field(EGU, "g/s") field(ADEL, "0") } record(ao, "CFIC:CP$(CP)4:1565:MAX") { field(DESC, "PID SP Max") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41565_OVH.MAX_X") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:1565:DMIN") { field(DESC, "PID SP DMIN") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41565_OVH.DMIN_X") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:1565:DMAX") { field(DESC, "PID SP DMAX") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41565_OVH.DMAX_X") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:1565:MDT") { field(DESC, "PID ST MDT") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41565_OVH.ST_X") field(PREC, "2") field(EGU, "Sec") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:1565:KP") { field(DESC, "PID Proportional Gain Kp") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41565_OVH.GAINP_X") field(PREC, "4") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:1565:KI") { field(DESC, "PID Integral Gain Ki") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41565_OVH.GAINI_X") field(PREC, "4") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:1565:KD") { field(DESC, "PID Derivative Gain Kd") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41565_OVH.GAIND_X") field(PREC, "4") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(stringout, "CFIC:CP$(CP)4:1565:S") { field(DESC, "PID Mode String") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41565_OVH.PV_String_X S 2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:1565:SP_RQST") { field(DESC, "C$(CP)-FIC-41565 PID SP request") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41565_OVH.SP_Rqst") field(PREC, "2") field(EGU, "g/s") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:1565:MIN") { field(DESC, "PID SP Min") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41565_OVH.MIN_X") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(stringin, "CFIC:CP$(CP)4:1565:PIDTAG") { field(DESC, "CC5 Outlet") field(PINI, "YES") field(VAL, "C$(CP)-FIC-41565") } record(ao, "CFIC:CP$(CP)4:1565:PEVAL") { field(DESC, "PID Fail Safe V Pos.") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41565.PEVAL") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bo, "CFIC:CP$(CP)4:1565:FSB") { field(DESC, "PID Fail Safe bit") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41565.FSB B 0") field(ZNAM, "Last Cmd Val") field(ONAM, "Fail Safe Val") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CFIC:CP$(CP)4:1565:NOMATCH") { field(DESC, "PID inp var no match") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41565_OVH.NoMatch") field(ZNAM, "Match") field(ONAM, "Nomatch") } record(bi, "CFIC:CP$(CP)4:1565:CHFAULT") { field(DESC, "PID inp ch fault") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41565_OVH.CHFault") field(ZNAM, "Ok") field(ONAM, "Fault") } record(ao, "CFIC:CP$(CP)4:1565:MANPOS_RQST") { field(DESC, "PID Manual Posn request") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41565_OVH.ManPos_Rqst") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ai, "CFIC:CP$(CP)4:1565:MODE_STATUS") { field(DESC, "PID Mode Status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41565_OVH.Mode_Status") field(HIHI, "4") field(HIGH, "3") field(HHSV, "MAJOR") field(HSV, "MAJOR") } record(bi, "CFIC:CP$(CP)4:1565:INTERLOCK") { field(DESC, "PID Interlock Condition") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41565.Interlock_Condition") field(ZNAM, "OK") field(ONAM, "Interlocked") } record(ai, "CFIC:CP$(CP)4:1565:IVAL") { field(DESC, "PID Interlock output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41565.IVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(ai, "CFIC:CP$(CP)4:1565:SVAL") { field(DESC, "PID Sequencer output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41565.SVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(bi, "CFIC:CP$(CP)4:1565:MMOD") { field(DESC, "PID Manual Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41565.mmod") field(ZNAM, "Not Manual") field(ONAM, "Manual") } record(bi, "CFIC:CP$(CP)4:1565:SMOD") { field(DESC, "PID Sequencer Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41565.smod") field(ZNAM, "Not Sequencer") field(ONAM, "Sequencer") } record(ai, "CFIC:CP$(CP)4:1565:MODE") { field(DESC, "PIDloop mode (man,auto,seq)") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41565.MODE") } record(stringin, "CFIC:CP$(CP)4:1565:MODE_STRING") { field(DESC, "PID Mode String") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41565_OVH.Mode_String") } record(bi, "CFIC:CP$(CP)4:1565:PMOD") { field(DESC, "PID Protector Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41565.pmod") field(ZNAM, "Not Protector") field(ONAM, "Protector") } record(bi, "CFIC:CP$(CP)4:1565:IMOD") { field(DESC, "PID Interlock Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41565.imod") field(ZNAM, "No Interlock") field(ONAM, "Interlock") } record(stringin, "CFIC:CP$(CP)4:1565:ACTUATOR") { field(DESC, "actuator name for the pid loop") field(PINI, "YES") field(VAL, "PV-41565") } record(ai, "CFIC:CP$(CP)4:1565:PVAL") { field(DESC, "PID Protector output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41565.PVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(stringin, "CFIC:CP$(CP)4:1565:TEXT1") { field(DESC, "PID Information 1") field(PINI, "YES") field(DTYP, "Soft Channel") info(autosaveFields, "VAL") } record(ai, "CFIC:CP$(CP)4:1565:MVAL") { field(DESC, "PID manual mode output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41565.MVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(bi, "CFIC:CP$(CP)4:1565:AMOD") { field(DESC, "PID Auto Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41565.amod") field(ZNAM, "Not Auto") field(ONAM, "Auto") } record(ai, "CFIC:CP$(CP)4:1565:AVAL") { field(DESC, "PID Auto mode output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41565.AVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(bi, "CFIC:CP$(CP)4:1565:IL_LATCH") { field(DESC, "interlock latched indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41565.Interlock_Condition_L") field(ZNAM, "Ok") field(ONAM, "Latched") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CFIC:CP$(CP)4:1565:IL_RESET") { field(DESC, "Interlock Latch Reset") field(DTYP, "EtherIP") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Reset") field(ONAM, "Reset") field(OUT, "@$(PLC_NAME) PV41565.Interlock_Condition_Reset B 0") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CFIC:CP$(CP)4:1565:MANUAL") { field(DESC, "Manual Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Manual") field(ONAM, "Manual") field(OUT, "@$(PLC_NAME) PV41565_OVH.Manual B 0") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CFIC:CP$(CP)4:1565:SEQUENCER") { field(DESC, "SequencerMode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Sequencer") field(ONAM, "Sequencer") field(OUT, "@$(PLC_NAME) PV41565_OVH.Sequencer B 0") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CFIC:CP$(CP)4:1565:AUTO") { field(DESC, "Auto Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "not Auto") field(ONAM, "Auto") field(OUT, "@$(PLC_NAME) PV41565_OVH.Auto B 0") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CFIC:CP$(CP)4:1565:OVERRIDE") { field(DESC, "Override state select") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41565.Override B 0") field(ZNAM, "Not Override") field(ONAM, "Override") field(ASG, "CRYO") } record(bi, "CFIC:CP$(CP)4:1565:OMOD") { field(DESC, "Override state status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41565.omod") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(ai, "CFIC:CP$(CP)4:1565:OMAX") { field(DESC, "Maximum output limit in all modes") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41565.Output_Limit") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(bi, "CFIC:CP$(CP)4:1565:OMAX_EN") { field(DESC, "Maximum output limit enforced") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41565.Output_Limit_EN") field(ZNAM, "Not Enforced") field(ONAM, "Enforced") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(ao, "CFIC:CP$(CP)4:1565:PI_SP") { field(DESC, "SP PID Parameter Input") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41565.Parameter_Input B 0") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:1565:PI_MIN") { field(DESC, "MIN PID Parameter Input") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41565.Parameter_Input B 1") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:1565:PI_MAX") { field(DESC, "MAX PID Parameter Input") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) PV41565.Parameter_Input B 2") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CFIC:CP$(CP)4:1565:ALM") { field(DESC, "Readback vs output discrepancy") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) PV41565.ER") field(ZNAM, "No Error") field(ONAM, "Error") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(ai, "CFIC:CP$(CP)4:2K_CC:ORBV") { field(DESC, "PID ORBV") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) FIC_2K_CC.ORBV") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(ai, "CFIC:CP$(CP)4:2K_CC:OVAL") { field(DESC, "PID OVAL") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) FIC_2K_CC.OVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(ai, "CFIC:CP$(CP)4:2K_CC:OUTPUT") { field(DESC, "PID Output") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) FIC_2K_CCO") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(ai, "CFIC:CP$(CP)4:2K_CC:CVAL") { field(DESC, "PID CVAL") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) FIC_2K_CC.CVAL") field(PREC, "2") field(EGU, "g/s") field(ADEL, "0") } record(ao, "CFIC:CP$(CP)4:2K_CC:MAX") { field(DESC, "PID SP Max") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) FIC_2K_CC_OVH.MAX_X") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:2K_CC:DMIN") { field(DESC, "PID SP DMIN") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) FIC_2K_CC_OVH.DMIN_X") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:2K_CC:DMAX") { field(DESC, "PID SP DMAX") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) FIC_2K_CC_OVH.DMAX_X") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:2K_CC:MDT") { field(DESC, "PID ST MDT") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) FIC_2K_CC_OVH.ST_X") field(PREC, "2") field(EGU, "Sec") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:2K_CC:KP") { field(DESC, "PID Proportional Gain Kp") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) FIC_2K_CC_OVH.GAINP_X") field(PREC, "4") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:2K_CC:KI") { field(DESC, "PID Integral Gain Ki") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) FIC_2K_CC_OVH.GAINI_X") field(PREC, "4") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:2K_CC:KD") { field(DESC, "PID Derivative Gain Kd") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) FIC_2K_CC_OVH.GAIND_X") field(PREC, "4") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(stringout, "CFIC:CP$(CP)4:2K_CC:S") { field(DESC, "PID Mode String") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) FIC_2K_CC_OVH.PV_String_X S 2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:2K_CC:SP_RQST") { field(DESC, "C$(CP)-FIC-2K-CC PID SP request") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) FIC_2K_CC_OVH.SP_Rqst") field(PREC, "2") field(EGU, "g/s") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:2K_CC:MIN") { field(DESC, "PID SP Min") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) FIC_2K_CC_OVH.MIN_X") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(stringin, "CFIC:CP$(CP)4:2K_CC:PIDTAG") { field(DESC, "2K Cold Box Flow") field(PINI, "YES") field(VAL, "C$(CP)-FIC-2K-CC") } record(ao, "CFIC:CP$(CP)4:2K_CC:PEVAL") { field(DESC, "PID Fail Safe V Pos.") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) FIC_2K_CC.PEVAL") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bo, "CFIC:CP$(CP)4:2K_CC:FSB") { field(DESC, "PID Fail Safe bit") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) FIC_2K_CC.FSB B 0") field(ZNAM, "Last Cmd Val") field(ONAM, "Fail Safe Val") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CFIC:CP$(CP)4:2K_CC:NOMATCH") { field(DESC, "PID inp var no match") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) FIC_2K_CC_OVH.NoMatch") field(ZNAM, "Match") field(ONAM, "Nomatch") } record(bi, "CFIC:CP$(CP)4:2K_CC:CHFAULT") { field(DESC, "PID inp ch fault") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) FIC_2K_CC_OVH.CHFault") field(ZNAM, "Ok") field(ONAM, "Fault") } record(ao, "CFIC:CP$(CP)4:2K_CC:MANPOS_RQST") { field(DESC, "PID Manual Posn request") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) FIC_2K_CC_OVH.ManPos_Rqst") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ai, "CFIC:CP$(CP)4:2K_CC:MODE_STATUS") { field(DESC, "PID Mode Status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) FIC_2K_CC_OVH.Mode_Status") field(HIHI, "4") field(HIGH, "3") field(HHSV, "MAJOR") field(HSV, "MAJOR") } record(bi, "CFIC:CP$(CP)4:2K_CC:INTERLOCK") { field(DESC, "PID Interlock Condition") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) FIC_2K_CC.Interlock_Condition") field(ZNAM, "OK") field(ONAM, "Interlocked") } record(ai, "CFIC:CP$(CP)4:2K_CC:IVAL") { field(DESC, "PID Interlock output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) FIC_2K_CC.IVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(ai, "CFIC:CP$(CP)4:2K_CC:SVAL") { field(DESC, "PID Sequencer output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) FIC_2K_CC.SVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(bi, "CFIC:CP$(CP)4:2K_CC:MMOD") { field(DESC, "PID Manual Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) FIC_2K_CC.mmod") field(ZNAM, "Not Manual") field(ONAM, "Manual") } record(bi, "CFIC:CP$(CP)4:2K_CC:SMOD") { field(DESC, "PID Sequencer Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) FIC_2K_CC.smod") field(ZNAM, "Not Sequencer") field(ONAM, "Sequencer") } record(ai, "CFIC:CP$(CP)4:2K_CC:MODE") { field(DESC, "PIDloop mode (man,auto,seq)") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) FIC_2K_CC.MODE") } record(stringin, "CFIC:CP$(CP)4:2K_CC:MODE_STRING") { field(DESC, "PID Mode String") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) FIC_2K_CC_OVH.Mode_String") } record(bi, "CFIC:CP$(CP)4:2K_CC:PMOD") { field(DESC, "PID Protector Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) FIC_2K_CC.pmod") field(ZNAM, "Not Protector") field(ONAM, "Protector") } record(bi, "CFIC:CP$(CP)4:2K_CC:IMOD") { field(DESC, "PID Interlock Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) FIC_2K_CC.imod") field(ZNAM, "No Interlock") field(ONAM, "Interlock") } record(stringin, "CFIC:CP$(CP)4:2K_CC:ACTUATOR") { field(DESC, "actuator name for the pid loop") field(PINI, "YES") field(VAL, "CC411X0.SS_W") } record(ai, "CFIC:CP$(CP)4:2K_CC:PVAL") { field(DESC, "PID Protector output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) FIC_2K_CC.PVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(stringin, "CFIC:CP$(CP)4:2K_CC:TEXT1") { field(DESC, "PID Information 1") field(PINI, "YES") field(DTYP, "Soft Channel") info(autosaveFields, "VAL") } record(ai, "CFIC:CP$(CP)4:2K_CC:MVAL") { field(DESC, "PID manual mode output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) FIC_2K_CC.MVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(bi, "CFIC:CP$(CP)4:2K_CC:AMOD") { field(DESC, "PID Auto Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) FIC_2K_CC.amod") field(ZNAM, "Not Auto") field(ONAM, "Auto") } record(ai, "CFIC:CP$(CP)4:2K_CC:AVAL") { field(DESC, "PID Auto mode output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) FIC_2K_CC.AVAL") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(bi, "CFIC:CP$(CP)4:2K_CC:IL_LATCH") { field(DESC, "interlock latched indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) FIC_2K_CC.Interlock_Condition_L") field(ZNAM, "Ok") field(ONAM, "Latched") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CFIC:CP$(CP)4:2K_CC:IL_RESET") { field(DESC, "Interlock Latch Reset") field(DTYP, "EtherIP") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Reset") field(ONAM, "Reset") field(OUT, "@$(PLC_NAME) FIC_2K_CC.Interlock_Condition_Reset B 0") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CFIC:CP$(CP)4:2K_CC:MANUAL") { field(DESC, "Manual Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Manual") field(ONAM, "Manual") field(OUT, "@$(PLC_NAME) FIC_2K_CC_OVH.Manual B 0") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CFIC:CP$(CP)4:2K_CC:SEQUENCER") { field(DESC, "SequencerMode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Sequencer") field(ONAM, "Sequencer") field(OUT, "@$(PLC_NAME) FIC_2K_CC_OVH.Sequencer B 0") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CFIC:CP$(CP)4:2K_CC:AUTO") { field(DESC, "Auto Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "not Auto") field(ONAM, "Auto") field(OUT, "@$(PLC_NAME) FIC_2K_CC_OVH.Auto B 0") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CFIC:CP$(CP)4:2K_CC:OVERRIDE") { field(DESC, "Override state select") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) FIC_2K_CC.Override B 0") field(ZNAM, "Not Override") field(ONAM, "Override") field(ASG, "CRYO") } record(bi, "CFIC:CP$(CP)4:2K_CC:OMOD") { field(DESC, "Override state status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) FIC_2K_CC.omod") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(ai, "CFIC:CP$(CP)4:2K_CC:OMAX") { field(DESC, "Maximum output limit in all modes") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) FIC_2K_CC.Output_Limit") field(PREC, "2") field(EGU, "%") field(ADEL, "0") } record(bi, "CFIC:CP$(CP)4:2K_CC:OMAX_EN") { field(DESC, "Maximum output limit enforced") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) FIC_2K_CC.Output_Limit_EN") field(ZNAM, "Not Enforced") field(ONAM, "Enforced") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(ao, "CFIC:CP$(CP)4:2K_CC:PI_SP") { field(DESC, "SP PID Parameter Input") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) FIC_2K_CC.Parameter_Input B 0") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:2K_CC:PI_MIN") { field(DESC, "MIN PID Parameter Input") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) FIC_2K_CC.Parameter_Input B 1") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CFIC:CP$(CP)4:2K_CC:PI_MAX") { field(DESC, "MAX PID Parameter Input") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) FIC_2K_CC.Parameter_Input B 2") field(PREC, "2") field(EGU, "%") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CFIC:CP$(CP)4:2K_CC:ALM") { field(DESC, "Readback vs output discrepancy") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) FIC_2K_CC.ER") field(ZNAM, "No Error") field(ONAM, "Error") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") }