record(bo, "CXY:PSI4:5413:ORDER_ON") { field(DESC, "K-Pump #1 Rem Start order on") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Ordered On") field(ONAM, "Ordered On") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CXY:PSI4:5413:ON_CNCL") { field(DESC, "K-Pump #1 Rem Start Cancel ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CXY:PSI4:5413:ORDER_OFF") { field(DESC, "K-Pump #1 Rem Start order off") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Order Off") field(ONAM, "Order Off") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CXY:PSI4:5413:OFF_CNCL") { field(DESC, "K-Pump #1 Rem Start Cancel OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CXY:PSI4:5413:ON_CFRM") { field(DESC, "K-Pump #1 Rem Start confirm ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CXY:PSI4:5413:OFF_CFRM") { field(DESC, "K-Pump #1 Rem Start confirm OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CXY:PSI4:5413:RQST_ON") { field(DESC, "K-Pump #1 Rem Start Rqst On") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P1_XY45413.EN B 0") field(HIGH, "1") field(ASG, "NOWRITE") } record(bo, "CXY:PSI4:5413:RQST_OFF") { field(DESC, "K-Pump #1 Rem Start Rqst Off") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P1_XY45413.DIS B 0") field(HIGH, "1") field(OMSL, "supervisory") field(ASG, "NOWRITE") } record(sub, "CXY:PSI4:5413:ORDER_ONL") { field(DESC, "K-Pump #1 Rem Start") field(SCAN, ".5 second") field(PINI, "NO") field(FLNK, "CXY:PSI4:5413:ORDER_ONT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "CXY:PSI4:5413:ORDER_ON") field(INPB, "CXY:PSI4:5413:ON_CFRM") field(INPC, "CXY:PSI4:5413:ON_CNCL") field(ASG, "NOWRITE") } record(bo, "CXY:PSI4:5413:ORDER_ONT") { field(DESC, "K-Pump #1 Rem Start") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "closed_loop") field(DOL, "CXY:PSI4:5413:ORDER_ONL") field(OUT, "CXY:PSI4:5413:RQST_ON") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } record(sub, "CXY:PSI4:5413:ORDER_OFFL") { field(DESC, "K-Pump #1 Rem Start") field(PINI, "NO") field(SCAN, ".5 second") field(FLNK, "CXY:PSI4:5413:ORDER_OFFT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "CXY:PSI4:5413:ORDER_OFF") field(INPB, "CXY:PSI4:5413:OFF_CFRM") field(INPC, "CXY:PSI4:5413:OFF_CNCL") field(ASG, "NOWRITE") } record(bo, "CXY:PSI4:5413:ORDER_OFFT") { field(DESC, "K-Pump #1 Rem Start") field(DTYP, "Soft Channel") field(PINI, "NO") field(SCAN, "Passive") field(OMSL, "closed_loop") field(DOL, "CXY:PSI4:5413:ORDER_OFFL") field(OUT, "CXY:PSI4:5413:RQST_OFF") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } # End of file record(bo, "CXY:PSI4:5414:ORDER_ON") { field(DESC, "K-Pump #1 Rem Stop order on") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Ordered On") field(ONAM, "Ordered On") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CXY:PSI4:5414:ON_CNCL") { field(DESC, "K-Pump #1 Rem Stop Cancel ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CXY:PSI4:5414:ORDER_OFF") { field(DESC, "K-Pump #1 Rem Stop order off") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Order Off") field(ONAM, "Order Off") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CXY:PSI4:5414:OFF_CNCL") { field(DESC, "K-Pump #1 Rem Stop Cancel OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CXY:PSI4:5414:ON_CFRM") { field(DESC, "K-Pump #1 Rem Stop confirm ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CXY:PSI4:5414:OFF_CFRM") { field(DESC, "K-Pump #1 Rem Stop confirm OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CXY:PSI4:5414:RQST_ON") { field(DESC, "K-Pump #1 Rem Stop Rqst On") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P1_XY45414.EN B 0") field(HIGH, "1") field(ASG, "NOWRITE") } record(bo, "CXY:PSI4:5414:RQST_OFF") { field(DESC, "K-Pump #1 Rem Stop Rqst Off") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P1_XY45414.DIS B 0") field(HIGH, "1") field(OMSL, "supervisory") field(ASG, "NOWRITE") } record(sub, "CXY:PSI4:5414:ORDER_ONL") { field(DESC, "K-Pump #1 Rem Stop") field(SCAN, ".5 second") field(PINI, "NO") field(FLNK, "CXY:PSI4:5414:ORDER_ONT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "CXY:PSI4:5414:ORDER_ON") field(INPB, "CXY:PSI4:5414:ON_CFRM") field(INPC, "CXY:PSI4:5414:ON_CNCL") field(ASG, "NOWRITE") } record(bo, "CXY:PSI4:5414:ORDER_ONT") { field(DESC, "K-Pump #1 Rem Stop") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "closed_loop") field(DOL, "CXY:PSI4:5414:ORDER_ONL") field(OUT, "CXY:PSI4:5414:RQST_ON") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } record(sub, "CXY:PSI4:5414:ORDER_OFFL") { field(DESC, "K-Pump #1 Rem Stop") field(PINI, "NO") field(SCAN, ".5 second") field(FLNK, "CXY:PSI4:5414:ORDER_OFFT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "CXY:PSI4:5414:ORDER_OFF") field(INPB, "CXY:PSI4:5414:OFF_CFRM") field(INPC, "CXY:PSI4:5414:OFF_CNCL") field(ASG, "NOWRITE") } record(bo, "CXY:PSI4:5414:ORDER_OFFT") { field(DESC, "K-Pump #1 Rem Stop") field(DTYP, "Soft Channel") field(PINI, "NO") field(SCAN, "Passive") field(OMSL, "closed_loop") field(DOL, "CXY:PSI4:5414:ORDER_OFFL") field(OUT, "CXY:PSI4:5414:RQST_OFF") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } # End of file record(bo, "PSIQ:PSI1:VPRST:ORDER_ON") { field(DESC, "K-Pump #1 Reset order on") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Ordered On") field(ONAM, "Ordered On") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "PSIQ:PSI1:VPRST:ON_CNCL") { field(DESC, "K-Pump #1 Reset Cancel ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "PSIQ:PSI1:VPRST:ORDER_OFF") { field(DESC, "K-Pump #1 Reset order off") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Order Off") field(ONAM, "Order Off") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "PSIQ:PSI1:VPRST:OFF_CNCL") { field(DESC, "K-Pump #1 Reset Cancel OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "PSIQ:PSI1:VPRST:ON_CFRM") { field(DESC, "K-Pump #1 Reset confirm ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "PSIQ:PSI1:VPRST:OFF_CFRM") { field(DESC, "K-Pump #1 Reset confirm OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "PSIQ:PSI1:VPRST:RQST_ON") { field(DESC, "K-Pump #1 Reset Rqst On") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P1_VP_RST.EN B 0") field(HIGH, "1") field(ASG, "NOWRITE") } record(bo, "PSIQ:PSI1:VPRST:RQST_OFF") { field(DESC, "K-Pump #1 Reset Rqst Off") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P1_VP_RST.DIS B 0") field(HIGH, "1") field(OMSL, "supervisory") field(ASG, "NOWRITE") } record(sub, "PSIQ:PSI1:VPRST:ORDER_ONL") { field(DESC, "K-Pump #1 Reset") field(SCAN, ".5 second") field(PINI, "NO") field(FLNK, "PSIQ:PSI1:VPRST:ORDER_ONT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "PSIQ:PSI1:VPRST:ORDER_ON") field(INPB, "PSIQ:PSI1:VPRST:ON_CFRM") field(INPC, "PSIQ:PSI1:VPRST:ON_CNCL") field(ASG, "NOWRITE") } record(bo, "PSIQ:PSI1:VPRST:ORDER_ONT") { field(DESC, "K-Pump #1 Reset") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "closed_loop") field(DOL, "PSIQ:PSI1:VPRST:ORDER_ONL") field(OUT, "PSIQ:PSI1:VPRST:RQST_ON") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } record(sub, "PSIQ:PSI1:VPRST:ORDER_OFFL") { field(DESC, "K-Pump #1 Reset") field(PINI, "NO") field(SCAN, ".5 second") field(FLNK, "PSIQ:PSI1:VPRST:ORDER_OFFT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "PSIQ:PSI1:VPRST:ORDER_OFF") field(INPB, "PSIQ:PSI1:VPRST:OFF_CFRM") field(INPC, "PSIQ:PSI1:VPRST:OFF_CNCL") field(ASG, "NOWRITE") } record(bo, "PSIQ:PSI1:VPRST:ORDER_OFFT") { field(DESC, "K-Pump #1 Reset") field(DTYP, "Soft Channel") field(PINI, "NO") field(SCAN, "Passive") field(OMSL, "closed_loop") field(DOL, "PSIQ:PSI1:VPRST:ORDER_OFFL") field(OUT, "PSIQ:PSI1:VPRST:RQST_OFF") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } # End of file record(bo, "CSV:PSI4:5411:ORDER_ON") { field(DESC, "K-Pump #1 Bypass Valve order on") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Ordered On") field(ONAM, "Ordered On") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CSV:PSI4:5411:ON_CNCL") { field(DESC, "K-Pump #1 Bypass Valve Cancel ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CSV:PSI4:5411:ORDER_OFF") { field(DESC, "K-Pump #1 Bypass Valve order off") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Order Off") field(ONAM, "Order Off") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CSV:PSI4:5411:OFF_CNCL") { field(DESC, "K-Pump #1 Bypass Valve Cancel OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CSV:PSI4:5411:ON_CFRM") { field(DESC, "K-Pump #1 Bypass Valve confirm ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CSV:PSI4:5411:OFF_CFRM") { field(DESC, "K-Pump #1 Bypass Valve confirm OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CSV:PSI4:5411:RQST_ON") { field(DESC, "K-Pump #1 Bypass Valve Rqst On") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P1_SV45411.EN B 0") field(HIGH, "1") field(ASG, "NOWRITE") } record(bo, "CSV:PSI4:5411:RQST_OFF") { field(DESC, "K-Pump #1 Bypass Valve Rqst Off") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P1_SV45411.DIS B 0") field(HIGH, "1") field(OMSL, "supervisory") field(ASG, "NOWRITE") } record(sub, "CSV:PSI4:5411:ORDER_ONL") { field(DESC, "K-Pump #1 Bypass Valve") field(SCAN, ".5 second") field(PINI, "NO") field(FLNK, "CSV:PSI4:5411:ORDER_ONT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "CSV:PSI4:5411:ORDER_ON") field(INPB, "CSV:PSI4:5411:ON_CFRM") field(INPC, "CSV:PSI4:5411:ON_CNCL") field(ASG, "NOWRITE") } record(bo, "CSV:PSI4:5411:ORDER_ONT") { field(DESC, "K-Pump #1 Bypass Valve") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "closed_loop") field(DOL, "CSV:PSI4:5411:ORDER_ONL") field(OUT, "CSV:PSI4:5411:RQST_ON") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } record(sub, "CSV:PSI4:5411:ORDER_OFFL") { field(DESC, "K-Pump #1 Bypass Valve") field(PINI, "NO") field(SCAN, ".5 second") field(FLNK, "CSV:PSI4:5411:ORDER_OFFT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "CSV:PSI4:5411:ORDER_OFF") field(INPB, "CSV:PSI4:5411:OFF_CFRM") field(INPC, "CSV:PSI4:5411:OFF_CNCL") field(ASG, "NOWRITE") } record(bo, "CSV:PSI4:5411:ORDER_OFFT") { field(DESC, "K-Pump #1 Bypass Valve") field(DTYP, "Soft Channel") field(PINI, "NO") field(SCAN, "Passive") field(OMSL, "closed_loop") field(DOL, "CSV:PSI4:5411:ORDER_OFFL") field(OUT, "CSV:PSI4:5411:RQST_OFF") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } # End of file record(bo, "CSV:PSI4:5412:ORDER_ON") { field(DESC, "K-Pump #1 Suction Valve order on") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Ordered On") field(ONAM, "Ordered On") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CSV:PSI4:5412:ON_CNCL") { field(DESC, "K-Pump #1 Suction Valve Cancel ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CSV:PSI4:5412:ORDER_OFF") { field(DESC, "K-Pump #1 Suction Valve order off") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Order Off") field(ONAM, "Order Off") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CSV:PSI4:5412:OFF_CNCL") { field(DESC, "K-Pump #1 Suction Valve Cancel OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CSV:PSI4:5412:ON_CFRM") { field(DESC, "K-Pump #1 Suction Valve confirm ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CSV:PSI4:5412:OFF_CFRM") { field(DESC, "K-Pump #1 Suction Valve confirm OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CSV:PSI4:5412:RQST_ON") { field(DESC, "K-Pump #1 Suction Valve Rqst On") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P1_SV45412.EN B 0") field(HIGH, "1") field(ASG, "NOWRITE") } record(bo, "CSV:PSI4:5412:RQST_OFF") { field(DESC, "K-Pump #1 Suction Valve Rqst Off") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P1_SV45412.DIS B 0") field(HIGH, "1") field(OMSL, "supervisory") field(ASG, "NOWRITE") } record(sub, "CSV:PSI4:5412:ORDER_ONL") { field(DESC, "K-Pump #1 Suction Valve") field(SCAN, ".5 second") field(PINI, "NO") field(FLNK, "CSV:PSI4:5412:ORDER_ONT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "CSV:PSI4:5412:ORDER_ON") field(INPB, "CSV:PSI4:5412:ON_CFRM") field(INPC, "CSV:PSI4:5412:ON_CNCL") field(ASG, "NOWRITE") } record(bo, "CSV:PSI4:5412:ORDER_ONT") { field(DESC, "K-Pump #1 Suction Valve") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "closed_loop") field(DOL, "CSV:PSI4:5412:ORDER_ONL") field(OUT, "CSV:PSI4:5412:RQST_ON") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } record(sub, "CSV:PSI4:5412:ORDER_OFFL") { field(DESC, "K-Pump #1 Suction Valve") field(PINI, "NO") field(SCAN, ".5 second") field(FLNK, "CSV:PSI4:5412:ORDER_OFFT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "CSV:PSI4:5412:ORDER_OFF") field(INPB, "CSV:PSI4:5412:OFF_CFRM") field(INPC, "CSV:PSI4:5412:OFF_CNCL") field(ASG, "NOWRITE") } record(bo, "CSV:PSI4:5412:ORDER_OFFT") { field(DESC, "K-Pump #1 Suction Valve") field(DTYP, "Soft Channel") field(PINI, "NO") field(SCAN, "Passive") field(OMSL, "closed_loop") field(DOL, "CSV:PSI4:5412:ORDER_OFFL") field(OUT, "CSV:PSI4:5412:RQST_OFF") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } # End of file record(bo, "CSV:PSI7:1050:ORDER_ON") { field(DESC, "K-Pump #1 SLAC GHe Rtn Valve order on") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Ordered On") field(ONAM, "Ordered On") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CSV:PSI7:1050:ON_CNCL") { field(DESC, "K-Pump #1 SLAC GHe Rtn Valve Cancel ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CSV:PSI7:1050:ORDER_OFF") { field(DESC, "K-Pump #1 SLAC GHe Rtn Valve order off") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Order Off") field(ONAM, "Order Off") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CSV:PSI7:1050:OFF_CNCL") { field(DESC, "K-Pump #1 SLAC GHe Rtn Valve Cancel OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CSV:PSI7:1050:ON_CFRM") { field(DESC, "K-Pump #1 SLAC GHe Rtn Valve confirm ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CSV:PSI7:1050:OFF_CFRM") { field(DESC, "K-Pump #1 SLAC GHe Rtn Valve confirm OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CSV:PSI7:1050:RQST_ON") { field(DESC, "K-Pump #1 SLAC GHe Rtn Valve Rqst On") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) C_SV71050.EN B 0") field(HIGH, "1") field(ASG, "NOWRITE") } record(bo, "CSV:PSI7:1050:RQST_OFF") { field(DESC, "K-Pump #1 SLAC GHe Rtn Valve Rqst Off") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) C_SV71050.DIS B 0") field(HIGH, "1") field(OMSL, "supervisory") field(ASG, "NOWRITE") } record(sub, "CSV:PSI7:1050:ORDER_ONL") { field(DESC, "K-Pump #1 SLAC GHe Rtn Valve") field(SCAN, ".5 second") field(PINI, "NO") field(FLNK, "CSV:PSI7:1050:ORDER_ONT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "CSV:PSI7:1050:ORDER_ON") field(INPB, "CSV:PSI7:1050:ON_CFRM") field(INPC, "CSV:PSI7:1050:ON_CNCL") field(ASG, "NOWRITE") } record(bo, "CSV:PSI7:1050:ORDER_ONT") { field(DESC, "K-Pump #1 SLAC GHe Rtn Valve") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "closed_loop") field(DOL, "CSV:PSI7:1050:ORDER_ONL") field(OUT, "CSV:PSI7:1050:RQST_ON") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } record(sub, "CSV:PSI7:1050:ORDER_OFFL") { field(DESC, "K-Pump #1 SLAC GHe Rtn Valve") field(PINI, "NO") field(SCAN, ".5 second") field(FLNK, "CSV:PSI7:1050:ORDER_OFFT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "CSV:PSI7:1050:ORDER_OFF") field(INPB, "CSV:PSI7:1050:OFF_CFRM") field(INPC, "CSV:PSI7:1050:OFF_CNCL") field(ASG, "NOWRITE") } record(bo, "CSV:PSI7:1050:ORDER_OFFT") { field(DESC, "K-Pump #1 SLAC GHe Rtn Valve") field(DTYP, "Soft Channel") field(PINI, "NO") field(SCAN, "Passive") field(OMSL, "closed_loop") field(DOL, "CSV:PSI7:1050:ORDER_OFFL") field(OUT, "CSV:PSI7:1050:RQST_OFF") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } # End of file record(bo, "CHTR:PSI5:5501:ORDER_ON") { field(DESC, "PsiCube Heater 01 LHe Vessel order on") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Ordered On") field(ONAM, "Ordered On") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5501:ON_CNCL") { field(DESC, "PsiCube Heater 01 LHe Vessel Cancel ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5501:ORDER_OFF") { field(DESC, "PsiCube Heater 01 LHe Vessel order off") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Order Off") field(ONAM, "Order Off") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5501:OFF_CNCL") { field(DESC, "PsiCube Heater 01 LHe Vessel Cancel OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5501:ON_CFRM") { field(DESC, "PsiCube Heater 01 LHe Vessel confirm ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5501:OFF_CFRM") { field(DESC, "PsiCube Heater 01 LHe Vessel confirm OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5501:RQST_ON") { field(DESC, "PsiCube Heater 01 LHe Vessel Rqst On") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P1_HT55501.EN B 0") field(HIGH, "1") field(ASG, "NOWRITE") } record(bo, "CHTR:PSI5:5501:RQST_OFF") { field(DESC, "PsiCube Heater 01 LHe Vessel Rqst Off") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P1_HT55501.DIS B 0") field(HIGH, "1") field(OMSL, "supervisory") field(ASG, "NOWRITE") } record(sub, "CHTR:PSI5:5501:ORDER_ONL") { field(DESC, "PsiCube Heater 01 LHe Vessel") field(SCAN, ".5 second") field(PINI, "NO") field(FLNK, "CHTR:PSI5:5501:ORDER_ONT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "CHTR:PSI5:5501:ORDER_ON") field(INPB, "CHTR:PSI5:5501:ON_CFRM") field(INPC, "CHTR:PSI5:5501:ON_CNCL") field(ASG, "NOWRITE") } record(bo, "CHTR:PSI5:5501:ORDER_ONT") { field(DESC, "PsiCube Heater 01 LHe Vessel") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "closed_loop") field(DOL, "CHTR:PSI5:5501:ORDER_ONL") field(OUT, "CHTR:PSI5:5501:RQST_ON") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } record(sub, "CHTR:PSI5:5501:ORDER_OFFL") { field(DESC, "PsiCube Heater 01 LHe Vessel") field(PINI, "NO") field(SCAN, ".5 second") field(FLNK, "CHTR:PSI5:5501:ORDER_OFFT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "CHTR:PSI5:5501:ORDER_OFF") field(INPB, "CHTR:PSI5:5501:OFF_CFRM") field(INPC, "CHTR:PSI5:5501:OFF_CNCL") field(ASG, "NOWRITE") } record(bo, "CHTR:PSI5:5501:ORDER_OFFT") { field(DESC, "PsiCube Heater 01 LHe Vessel") field(DTYP, "Soft Channel") field(PINI, "NO") field(SCAN, "Passive") field(OMSL, "closed_loop") field(DOL, "CHTR:PSI5:5501:ORDER_OFFL") field(OUT, "CHTR:PSI5:5501:RQST_OFF") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } # End of file record(bo, "CHTR:PSI5:5502:ORDER_ON") { field(DESC, "PsiCube Heater 02 order on") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Ordered On") field(ONAM, "Ordered On") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5502:ON_CNCL") { field(DESC, "PsiCube Heater 02 Cancel ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5502:ORDER_OFF") { field(DESC, "PsiCube Heater 02 order off") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Order Off") field(ONAM, "Order Off") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5502:OFF_CNCL") { field(DESC, "PsiCube Heater 02 Cancel OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5502:ON_CFRM") { field(DESC, "PsiCube Heater 02 confirm ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5502:OFF_CFRM") { field(DESC, "PsiCube Heater 02 confirm OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5502:RQST_ON") { field(DESC, "PsiCube Heater 02 Rqst On") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P1_HT55502.EN B 0") field(HIGH, "1") field(ASG, "NOWRITE") } record(bo, "CHTR:PSI5:5502:RQST_OFF") { field(DESC, "PsiCube Heater 02 Rqst Off") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P1_HT55502.DIS B 0") field(HIGH, "1") field(OMSL, "supervisory") field(ASG, "NOWRITE") } record(sub, "CHTR:PSI5:5502:ORDER_ONL") { field(DESC, "PsiCube Heater 02") field(SCAN, ".5 second") field(PINI, "NO") field(FLNK, "CHTR:PSI5:5502:ORDER_ONT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "CHTR:PSI5:5502:ORDER_ON") field(INPB, "CHTR:PSI5:5502:ON_CFRM") field(INPC, "CHTR:PSI5:5502:ON_CNCL") field(ASG, "NOWRITE") } record(bo, "CHTR:PSI5:5502:ORDER_ONT") { field(DESC, "PsiCube Heater 02") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "closed_loop") field(DOL, "CHTR:PSI5:5502:ORDER_ONL") field(OUT, "CHTR:PSI5:5502:RQST_ON") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } record(sub, "CHTR:PSI5:5502:ORDER_OFFL") { field(DESC, "PsiCube Heater 02") field(PINI, "NO") field(SCAN, ".5 second") field(FLNK, "CHTR:PSI5:5502:ORDER_OFFT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "CHTR:PSI5:5502:ORDER_OFF") field(INPB, "CHTR:PSI5:5502:OFF_CFRM") field(INPC, "CHTR:PSI5:5502:OFF_CNCL") field(ASG, "NOWRITE") } record(bo, "CHTR:PSI5:5502:ORDER_OFFT") { field(DESC, "PsiCube Heater 02") field(DTYP, "Soft Channel") field(PINI, "NO") field(SCAN, "Passive") field(OMSL, "closed_loop") field(DOL, "CHTR:PSI5:5502:ORDER_OFFL") field(OUT, "CHTR:PSI5:5502:RQST_OFF") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } # End of file record(bo, "CHTR:PSI5:5503:ORDER_ON") { field(DESC, "PsiCube Heater 03 order on") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Ordered On") field(ONAM, "Ordered On") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5503:ON_CNCL") { field(DESC, "PsiCube Heater 03 Cancel ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5503:ORDER_OFF") { field(DESC, "PsiCube Heater 03 order off") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Order Off") field(ONAM, "Order Off") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5503:OFF_CNCL") { field(DESC, "PsiCube Heater 03 Cancel OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5503:ON_CFRM") { field(DESC, "PsiCube Heater 03 confirm ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5503:OFF_CFRM") { field(DESC, "PsiCube Heater 03 confirm OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5503:RQST_ON") { field(DESC, "PsiCube Heater 03 Rqst On") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P1_HT55503.EN B 0") field(HIGH, "1") field(ASG, "NOWRITE") } record(bo, "CHTR:PSI5:5503:RQST_OFF") { field(DESC, "PsiCube Heater 03 Rqst Off") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P1_HT55503.DIS B 0") field(HIGH, "1") field(OMSL, "supervisory") field(ASG, "NOWRITE") } record(sub, "CHTR:PSI5:5503:ORDER_ONL") { field(DESC, "PsiCube Heater 03") field(SCAN, ".5 second") field(PINI, "NO") field(FLNK, "CHTR:PSI5:5503:ORDER_ONT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "CHTR:PSI5:5503:ORDER_ON") field(INPB, "CHTR:PSI5:5503:ON_CFRM") field(INPC, "CHTR:PSI5:5503:ON_CNCL") field(ASG, "NOWRITE") } record(bo, "CHTR:PSI5:5503:ORDER_ONT") { field(DESC, "PsiCube Heater 03") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "closed_loop") field(DOL, "CHTR:PSI5:5503:ORDER_ONL") field(OUT, "CHTR:PSI5:5503:RQST_ON") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } record(sub, "CHTR:PSI5:5503:ORDER_OFFL") { field(DESC, "PsiCube Heater 03") field(PINI, "NO") field(SCAN, ".5 second") field(FLNK, "CHTR:PSI5:5503:ORDER_OFFT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "CHTR:PSI5:5503:ORDER_OFF") field(INPB, "CHTR:PSI5:5503:OFF_CFRM") field(INPC, "CHTR:PSI5:5503:OFF_CNCL") field(ASG, "NOWRITE") } record(bo, "CHTR:PSI5:5503:ORDER_OFFT") { field(DESC, "PsiCube Heater 03") field(DTYP, "Soft Channel") field(PINI, "NO") field(SCAN, "Passive") field(OMSL, "closed_loop") field(DOL, "CHTR:PSI5:5503:ORDER_OFFL") field(OUT, "CHTR:PSI5:5503:RQST_OFF") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } # End of file record(bo, "CHTR:PSI5:5504:ORDER_ON") { field(DESC, "PsiCube Heater 04 order on") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Ordered On") field(ONAM, "Ordered On") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5504:ON_CNCL") { field(DESC, "PsiCube Heater 04 Cancel ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5504:ORDER_OFF") { field(DESC, "PsiCube Heater 04 order off") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Order Off") field(ONAM, "Order Off") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5504:OFF_CNCL") { field(DESC, "PsiCube Heater 04 Cancel OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5504:ON_CFRM") { field(DESC, "PsiCube Heater 04 confirm ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5504:OFF_CFRM") { field(DESC, "PsiCube Heater 04 confirm OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5504:RQST_ON") { field(DESC, "PsiCube Heater 04 Rqst On") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P1_HT55504.EN B 0") field(HIGH, "1") field(ASG, "NOWRITE") } record(bo, "CHTR:PSI5:5504:RQST_OFF") { field(DESC, "PsiCube Heater 04 Rqst Off") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P1_HT55504.DIS B 0") field(HIGH, "1") field(OMSL, "supervisory") field(ASG, "NOWRITE") } record(sub, "CHTR:PSI5:5504:ORDER_ONL") { field(DESC, "PsiCube Heater 04") field(SCAN, ".5 second") field(PINI, "NO") field(FLNK, "CHTR:PSI5:5504:ORDER_ONT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "CHTR:PSI5:5504:ORDER_ON") field(INPB, "CHTR:PSI5:5504:ON_CFRM") field(INPC, "CHTR:PSI5:5504:ON_CNCL") field(ASG, "NOWRITE") } record(bo, "CHTR:PSI5:5504:ORDER_ONT") { field(DESC, "PsiCube Heater 04") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "closed_loop") field(DOL, "CHTR:PSI5:5504:ORDER_ONL") field(OUT, "CHTR:PSI5:5504:RQST_ON") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } record(sub, "CHTR:PSI5:5504:ORDER_OFFL") { field(DESC, "PsiCube Heater 04") field(PINI, "NO") field(SCAN, ".5 second") field(FLNK, "CHTR:PSI5:5504:ORDER_OFFT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "CHTR:PSI5:5504:ORDER_OFF") field(INPB, "CHTR:PSI5:5504:OFF_CFRM") field(INPC, "CHTR:PSI5:5504:OFF_CNCL") field(ASG, "NOWRITE") } record(bo, "CHTR:PSI5:5504:ORDER_OFFT") { field(DESC, "PsiCube Heater 04") field(DTYP, "Soft Channel") field(PINI, "NO") field(SCAN, "Passive") field(OMSL, "closed_loop") field(DOL, "CHTR:PSI5:5504:ORDER_OFFL") field(OUT, "CHTR:PSI5:5504:RQST_OFF") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } # End of file record(bo, "CHTR:PSI5:5505:ORDER_ON") { field(DESC, "PsiCube Heater 05 order on") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Ordered On") field(ONAM, "Ordered On") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5505:ON_CNCL") { field(DESC, "PsiCube Heater 05 Cancel ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5505:ORDER_OFF") { field(DESC, "PsiCube Heater 05 order off") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Order Off") field(ONAM, "Order Off") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5505:OFF_CNCL") { field(DESC, "PsiCube Heater 05 Cancel OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5505:ON_CFRM") { field(DESC, "PsiCube Heater 05 confirm ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5505:OFF_CFRM") { field(DESC, "PsiCube Heater 05 confirm OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5505:RQST_ON") { field(DESC, "PsiCube Heater 05 Rqst On") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P1_HT55505.EN B 0") field(HIGH, "1") field(ASG, "NOWRITE") } record(bo, "CHTR:PSI5:5505:RQST_OFF") { field(DESC, "PsiCube Heater 05 Rqst Off") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P1_HT55505.DIS B 0") field(HIGH, "1") field(OMSL, "supervisory") field(ASG, "NOWRITE") } record(sub, "CHTR:PSI5:5505:ORDER_ONL") { field(DESC, "PsiCube Heater 05") field(SCAN, ".5 second") field(PINI, "NO") field(FLNK, "CHTR:PSI5:5505:ORDER_ONT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "CHTR:PSI5:5505:ORDER_ON") field(INPB, "CHTR:PSI5:5505:ON_CFRM") field(INPC, "CHTR:PSI5:5505:ON_CNCL") field(ASG, "NOWRITE") } record(bo, "CHTR:PSI5:5505:ORDER_ONT") { field(DESC, "PsiCube Heater 05") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "closed_loop") field(DOL, "CHTR:PSI5:5505:ORDER_ONL") field(OUT, "CHTR:PSI5:5505:RQST_ON") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } record(sub, "CHTR:PSI5:5505:ORDER_OFFL") { field(DESC, "PsiCube Heater 05") field(PINI, "NO") field(SCAN, ".5 second") field(FLNK, "CHTR:PSI5:5505:ORDER_OFFT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "CHTR:PSI5:5505:ORDER_OFF") field(INPB, "CHTR:PSI5:5505:OFF_CFRM") field(INPC, "CHTR:PSI5:5505:OFF_CNCL") field(ASG, "NOWRITE") } record(bo, "CHTR:PSI5:5505:ORDER_OFFT") { field(DESC, "PsiCube Heater 05") field(DTYP, "Soft Channel") field(PINI, "NO") field(SCAN, "Passive") field(OMSL, "closed_loop") field(DOL, "CHTR:PSI5:5505:ORDER_OFFL") field(OUT, "CHTR:PSI5:5505:RQST_OFF") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } # End of file record(bo, "CHTR:PSI5:5506:ORDER_ON") { field(DESC, "PsiCube Heater 06 order on") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Ordered On") field(ONAM, "Ordered On") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5506:ON_CNCL") { field(DESC, "PsiCube Heater 06 Cancel ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5506:ORDER_OFF") { field(DESC, "PsiCube Heater 06 order off") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Order Off") field(ONAM, "Order Off") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5506:OFF_CNCL") { field(DESC, "PsiCube Heater 06 Cancel OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5506:ON_CFRM") { field(DESC, "PsiCube Heater 06 confirm ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5506:OFF_CFRM") { field(DESC, "PsiCube Heater 06 confirm OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5506:RQST_ON") { field(DESC, "PsiCube Heater 06 Rqst On") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P1_HT55506.EN B 0") field(HIGH, "1") field(ASG, "NOWRITE") } record(bo, "CHTR:PSI5:5506:RQST_OFF") { field(DESC, "PsiCube Heater 06 Rqst Off") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P1_HT55506.DIS B 0") field(HIGH, "1") field(OMSL, "supervisory") field(ASG, "NOWRITE") } record(sub, "CHTR:PSI5:5506:ORDER_ONL") { field(DESC, "PsiCube Heater 06") field(SCAN, ".5 second") field(PINI, "NO") field(FLNK, "CHTR:PSI5:5506:ORDER_ONT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "CHTR:PSI5:5506:ORDER_ON") field(INPB, "CHTR:PSI5:5506:ON_CFRM") field(INPC, "CHTR:PSI5:5506:ON_CNCL") field(ASG, "NOWRITE") } record(bo, "CHTR:PSI5:5506:ORDER_ONT") { field(DESC, "PsiCube Heater 06") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "closed_loop") field(DOL, "CHTR:PSI5:5506:ORDER_ONL") field(OUT, "CHTR:PSI5:5506:RQST_ON") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } record(sub, "CHTR:PSI5:5506:ORDER_OFFL") { field(DESC, "PsiCube Heater 06") field(PINI, "NO") field(SCAN, ".5 second") field(FLNK, "CHTR:PSI5:5506:ORDER_OFFT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "CHTR:PSI5:5506:ORDER_OFF") field(INPB, "CHTR:PSI5:5506:OFF_CFRM") field(INPC, "CHTR:PSI5:5506:OFF_CNCL") field(ASG, "NOWRITE") } record(bo, "CHTR:PSI5:5506:ORDER_OFFT") { field(DESC, "PsiCube Heater 06") field(DTYP, "Soft Channel") field(PINI, "NO") field(SCAN, "Passive") field(OMSL, "closed_loop") field(DOL, "CHTR:PSI5:5506:ORDER_OFFL") field(OUT, "CHTR:PSI5:5506:RQST_OFF") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } # End of file record(bo, "CHTR:PSI5:5507:ORDER_ON") { field(DESC, "PsiCube Heater 07 order on") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Ordered On") field(ONAM, "Ordered On") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5507:ON_CNCL") { field(DESC, "PsiCube Heater 07 Cancel ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5507:ORDER_OFF") { field(DESC, "PsiCube Heater 07 order off") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Order Off") field(ONAM, "Order Off") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5507:OFF_CNCL") { field(DESC, "PsiCube Heater 07 Cancel OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5507:ON_CFRM") { field(DESC, "PsiCube Heater 07 confirm ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5507:OFF_CFRM") { field(DESC, "PsiCube Heater 07 confirm OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5507:RQST_ON") { field(DESC, "PsiCube Heater 07 Rqst On") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P1_HT55507.EN B 0") field(HIGH, "1") field(ASG, "NOWRITE") } record(bo, "CHTR:PSI5:5507:RQST_OFF") { field(DESC, "PsiCube Heater 07 Rqst Off") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P1_HT55507.DIS B 0") field(HIGH, "1") field(OMSL, "supervisory") field(ASG, "NOWRITE") } record(sub, "CHTR:PSI5:5507:ORDER_ONL") { field(DESC, "PsiCube Heater 07") field(SCAN, ".5 second") field(PINI, "NO") field(FLNK, "CHTR:PSI5:5507:ORDER_ONT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "CHTR:PSI5:5507:ORDER_ON") field(INPB, "CHTR:PSI5:5507:ON_CFRM") field(INPC, "CHTR:PSI5:5507:ON_CNCL") field(ASG, "NOWRITE") } record(bo, "CHTR:PSI5:5507:ORDER_ONT") { field(DESC, "PsiCube Heater 07") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "closed_loop") field(DOL, "CHTR:PSI5:5507:ORDER_ONL") field(OUT, "CHTR:PSI5:5507:RQST_ON") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } record(sub, "CHTR:PSI5:5507:ORDER_OFFL") { field(DESC, "PsiCube Heater 07") field(PINI, "NO") field(SCAN, ".5 second") field(FLNK, "CHTR:PSI5:5507:ORDER_OFFT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "CHTR:PSI5:5507:ORDER_OFF") field(INPB, "CHTR:PSI5:5507:OFF_CFRM") field(INPC, "CHTR:PSI5:5507:OFF_CNCL") field(ASG, "NOWRITE") } record(bo, "CHTR:PSI5:5507:ORDER_OFFT") { field(DESC, "PsiCube Heater 07") field(DTYP, "Soft Channel") field(PINI, "NO") field(SCAN, "Passive") field(OMSL, "closed_loop") field(DOL, "CHTR:PSI5:5507:ORDER_OFFL") field(OUT, "CHTR:PSI5:5507:RQST_OFF") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } # End of file record(bo, "CHTR:PSI5:5508:ORDER_ON") { field(DESC, "PsiCube Heater 08 order on") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Ordered On") field(ONAM, "Ordered On") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5508:ON_CNCL") { field(DESC, "PsiCube Heater 08 Cancel ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5508:ORDER_OFF") { field(DESC, "PsiCube Heater 08 order off") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Order Off") field(ONAM, "Order Off") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5508:OFF_CNCL") { field(DESC, "PsiCube Heater 08 Cancel OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5508:ON_CFRM") { field(DESC, "PsiCube Heater 08 confirm ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5508:OFF_CFRM") { field(DESC, "PsiCube Heater 08 confirm OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5508:RQST_ON") { field(DESC, "PsiCube Heater 08 Rqst On") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P1_HT55508.EN B 0") field(HIGH, "1") field(ASG, "NOWRITE") } record(bo, "CHTR:PSI5:5508:RQST_OFF") { field(DESC, "PsiCube Heater 08 Rqst Off") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P1_HT55508.DIS B 0") field(HIGH, "1") field(OMSL, "supervisory") field(ASG, "NOWRITE") } record(sub, "CHTR:PSI5:5508:ORDER_ONL") { field(DESC, "PsiCube Heater 08") field(SCAN, ".5 second") field(PINI, "NO") field(FLNK, "CHTR:PSI5:5508:ORDER_ONT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "CHTR:PSI5:5508:ORDER_ON") field(INPB, "CHTR:PSI5:5508:ON_CFRM") field(INPC, "CHTR:PSI5:5508:ON_CNCL") field(ASG, "NOWRITE") } record(bo, "CHTR:PSI5:5508:ORDER_ONT") { field(DESC, "PsiCube Heater 08") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "closed_loop") field(DOL, "CHTR:PSI5:5508:ORDER_ONL") field(OUT, "CHTR:PSI5:5508:RQST_ON") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } record(sub, "CHTR:PSI5:5508:ORDER_OFFL") { field(DESC, "PsiCube Heater 08") field(PINI, "NO") field(SCAN, ".5 second") field(FLNK, "CHTR:PSI5:5508:ORDER_OFFT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "CHTR:PSI5:5508:ORDER_OFF") field(INPB, "CHTR:PSI5:5508:OFF_CFRM") field(INPC, "CHTR:PSI5:5508:OFF_CNCL") field(ASG, "NOWRITE") } record(bo, "CHTR:PSI5:5508:ORDER_OFFT") { field(DESC, "PsiCube Heater 08") field(DTYP, "Soft Channel") field(PINI, "NO") field(SCAN, "Passive") field(OMSL, "closed_loop") field(DOL, "CHTR:PSI5:5508:ORDER_OFFL") field(OUT, "CHTR:PSI5:5508:RQST_OFF") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } # End of file record(bo, "CHTR:PSI5:5509:ORDER_ON") { field(DESC, "PsiCube Heater 09 order on") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Ordered On") field(ONAM, "Ordered On") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5509:ON_CNCL") { field(DESC, "PsiCube Heater 09 Cancel ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5509:ORDER_OFF") { field(DESC, "PsiCube Heater 09 order off") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Order Off") field(ONAM, "Order Off") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5509:OFF_CNCL") { field(DESC, "PsiCube Heater 09 Cancel OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5509:ON_CFRM") { field(DESC, "PsiCube Heater 09 confirm ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5509:OFF_CFRM") { field(DESC, "PsiCube Heater 09 confirm OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5509:RQST_ON") { field(DESC, "PsiCube Heater 09 Rqst On") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P1_HT55509.EN B 0") field(HIGH, "1") field(ASG, "NOWRITE") } record(bo, "CHTR:PSI5:5509:RQST_OFF") { field(DESC, "PsiCube Heater 09 Rqst Off") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P1_HT55509.DIS B 0") field(HIGH, "1") field(OMSL, "supervisory") field(ASG, "NOWRITE") } record(sub, "CHTR:PSI5:5509:ORDER_ONL") { field(DESC, "PsiCube Heater 09") field(SCAN, ".5 second") field(PINI, "NO") field(FLNK, "CHTR:PSI5:5509:ORDER_ONT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "CHTR:PSI5:5509:ORDER_ON") field(INPB, "CHTR:PSI5:5509:ON_CFRM") field(INPC, "CHTR:PSI5:5509:ON_CNCL") field(ASG, "NOWRITE") } record(bo, "CHTR:PSI5:5509:ORDER_ONT") { field(DESC, "PsiCube Heater 09") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "closed_loop") field(DOL, "CHTR:PSI5:5509:ORDER_ONL") field(OUT, "CHTR:PSI5:5509:RQST_ON") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } record(sub, "CHTR:PSI5:5509:ORDER_OFFL") { field(DESC, "PsiCube Heater 09") field(PINI, "NO") field(SCAN, ".5 second") field(FLNK, "CHTR:PSI5:5509:ORDER_OFFT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "CHTR:PSI5:5509:ORDER_OFF") field(INPB, "CHTR:PSI5:5509:OFF_CFRM") field(INPC, "CHTR:PSI5:5509:OFF_CNCL") field(ASG, "NOWRITE") } record(bo, "CHTR:PSI5:5509:ORDER_OFFT") { field(DESC, "PsiCube Heater 09") field(DTYP, "Soft Channel") field(PINI, "NO") field(SCAN, "Passive") field(OMSL, "closed_loop") field(DOL, "CHTR:PSI5:5509:ORDER_OFFL") field(OUT, "CHTR:PSI5:5509:RQST_OFF") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } # End of file record(bo, "CHTR:PSI5:5510:ORDER_ON") { field(DESC, "PsiCube Heater 10 order on") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Ordered On") field(ONAM, "Ordered On") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5510:ON_CNCL") { field(DESC, "PsiCube Heater 10 Cancel ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5510:ORDER_OFF") { field(DESC, "PsiCube Heater 10 order off") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Order Off") field(ONAM, "Order Off") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5510:OFF_CNCL") { field(DESC, "PsiCube Heater 10 Cancel OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5510:ON_CFRM") { field(DESC, "PsiCube Heater 10 confirm ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5510:OFF_CFRM") { field(DESC, "PsiCube Heater 10 confirm OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5510:RQST_ON") { field(DESC, "PsiCube Heater 10 Rqst On") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P1_HT55510.EN B 0") field(HIGH, "1") field(ASG, "NOWRITE") } record(bo, "CHTR:PSI5:5510:RQST_OFF") { field(DESC, "PsiCube Heater 10 Rqst Off") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P1_HT55510.DIS B 0") field(HIGH, "1") field(OMSL, "supervisory") field(ASG, "NOWRITE") } record(sub, "CHTR:PSI5:5510:ORDER_ONL") { field(DESC, "PsiCube Heater 10") field(SCAN, ".5 second") field(PINI, "NO") field(FLNK, "CHTR:PSI5:5510:ORDER_ONT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "CHTR:PSI5:5510:ORDER_ON") field(INPB, "CHTR:PSI5:5510:ON_CFRM") field(INPC, "CHTR:PSI5:5510:ON_CNCL") field(ASG, "NOWRITE") } record(bo, "CHTR:PSI5:5510:ORDER_ONT") { field(DESC, "PsiCube Heater 10") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "closed_loop") field(DOL, "CHTR:PSI5:5510:ORDER_ONL") field(OUT, "CHTR:PSI5:5510:RQST_ON") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } record(sub, "CHTR:PSI5:5510:ORDER_OFFL") { field(DESC, "PsiCube Heater 10") field(PINI, "NO") field(SCAN, ".5 second") field(FLNK, "CHTR:PSI5:5510:ORDER_OFFT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "CHTR:PSI5:5510:ORDER_OFF") field(INPB, "CHTR:PSI5:5510:OFF_CFRM") field(INPC, "CHTR:PSI5:5510:OFF_CNCL") field(ASG, "NOWRITE") } record(bo, "CHTR:PSI5:5510:ORDER_OFFT") { field(DESC, "PsiCube Heater 10") field(DTYP, "Soft Channel") field(PINI, "NO") field(SCAN, "Passive") field(OMSL, "closed_loop") field(DOL, "CHTR:PSI5:5510:ORDER_OFFL") field(OUT, "CHTR:PSI5:5510:RQST_OFF") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } # End of file record(bo, "PSIQ:PSI1:P100:ORDER_ON") { field(DESC, "P100 Vlv Box CD Start order on") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Ordered On") field(ONAM, "Ordered On") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "PSIQ:PSI1:P100:ON_CNCL") { field(DESC, "P100 Vlv Box CD Start Cancel ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "PSIQ:PSI1:P100:ORDER_OFF") { field(DESC, "P100 Vlv Box CD Start order off") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Order Off") field(ONAM, "Order Off") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "PSIQ:PSI1:P100:OFF_CNCL") { field(DESC, "P100 Vlv Box CD Start Cancel OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "PSIQ:PSI1:P100:ON_CFRM") { field(DESC, "P100 Vlv Box CD Start confirm ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "PSIQ:PSI1:P100:OFF_CFRM") { field(DESC, "P100 Vlv Box CD Start confirm OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "PSIQ:PSI1:P100:RQST_ON") { field(DESC, "P100 Vlv Box CD Start Rqst On") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P100_START B 0") field(HIGH, "1") field(ASG, "NOWRITE") } record(bo, "PSIQ:PSI1:P100:RQST_OFF") { field(DESC, "P100 Vlv Box CD Start Rqst Off") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P100_ABORT B 0") field(HIGH, "1") field(OMSL, "supervisory") field(ASG, "NOWRITE") } record(sub, "PSIQ:PSI1:P100:ORDER_ONL") { field(DESC, "P100 Vlv Box CD Start") field(SCAN, ".5 second") field(PINI, "NO") field(FLNK, "PSIQ:PSI1:P100:ORDER_ONT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "PSIQ:PSI1:P100:ORDER_ON") field(INPB, "PSIQ:PSI1:P100:ON_CFRM") field(INPC, "PSIQ:PSI1:P100:ON_CNCL") field(ASG, "NOWRITE") } record(bo, "PSIQ:PSI1:P100:ORDER_ONT") { field(DESC, "P100 Vlv Box CD Start") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "closed_loop") field(DOL, "PSIQ:PSI1:P100:ORDER_ONL") field(OUT, "PSIQ:PSI1:P100:RQST_ON") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } record(sub, "PSIQ:PSI1:P100:ORDER_OFFL") { field(DESC, "P100 Vlv Box CD Start") field(PINI, "NO") field(SCAN, ".5 second") field(FLNK, "PSIQ:PSI1:P100:ORDER_OFFT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "PSIQ:PSI1:P100:ORDER_OFF") field(INPB, "PSIQ:PSI1:P100:OFF_CFRM") field(INPC, "PSIQ:PSI1:P100:OFF_CNCL") field(ASG, "NOWRITE") } record(bo, "PSIQ:PSI1:P100:ORDER_OFFT") { field(DESC, "P100 Vlv Box CD Start") field(DTYP, "Soft Channel") field(PINI, "NO") field(SCAN, "Passive") field(OMSL, "closed_loop") field(DOL, "PSIQ:PSI1:P100:ORDER_OFFL") field(OUT, "PSIQ:PSI1:P100:RQST_OFF") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } # End of file record(bo, "PSIQ:PSI1:P200:ORDER_ON") { field(DESC, "P200 Psi Blade CD Start order on") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Ordered On") field(ONAM, "Ordered On") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "PSIQ:PSI1:P200:ON_CNCL") { field(DESC, "P200 Psi Blade CD Start Cancel ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "PSIQ:PSI1:P200:ORDER_OFF") { field(DESC, "P200 Psi Blade CD Start order off") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Order Off") field(ONAM, "Order Off") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "PSIQ:PSI1:P200:OFF_CNCL") { field(DESC, "P200 Psi Blade CD Start Cancel OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "PSIQ:PSI1:P200:ON_CFRM") { field(DESC, "P200 Psi Blade CD Start confirm ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "PSIQ:PSI1:P200:OFF_CFRM") { field(DESC, "P200 Psi Blade CD Start confirm OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "PSIQ:PSI1:P200:RQST_ON") { field(DESC, "P200 Psi Blade CD Start Rqst On") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P200_START B 0") field(HIGH, "1") field(ASG, "NOWRITE") } record(bo, "PSIQ:PSI1:P200:RQST_OFF") { field(DESC, "P200 Psi Blade CD Start Rqst Off") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P200_ABORT B 0") field(HIGH, "1") field(OMSL, "supervisory") field(ASG, "NOWRITE") } record(sub, "PSIQ:PSI1:P200:ORDER_ONL") { field(DESC, "P200 Psi Blade CD Start") field(SCAN, ".5 second") field(PINI, "NO") field(FLNK, "PSIQ:PSI1:P200:ORDER_ONT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "PSIQ:PSI1:P200:ORDER_ON") field(INPB, "PSIQ:PSI1:P200:ON_CFRM") field(INPC, "PSIQ:PSI1:P200:ON_CNCL") field(ASG, "NOWRITE") } record(bo, "PSIQ:PSI1:P200:ORDER_ONT") { field(DESC, "P200 Psi Blade CD Start") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "closed_loop") field(DOL, "PSIQ:PSI1:P200:ORDER_ONL") field(OUT, "PSIQ:PSI1:P200:RQST_ON") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } record(sub, "PSIQ:PSI1:P200:ORDER_OFFL") { field(DESC, "P200 Psi Blade CD Start") field(PINI, "NO") field(SCAN, ".5 second") field(FLNK, "PSIQ:PSI1:P200:ORDER_OFFT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "PSIQ:PSI1:P200:ORDER_OFF") field(INPB, "PSIQ:PSI1:P200:OFF_CFRM") field(INPC, "PSIQ:PSI1:P200:OFF_CNCL") field(ASG, "NOWRITE") } record(bo, "PSIQ:PSI1:P200:ORDER_OFFT") { field(DESC, "P200 Psi Blade CD Start") field(DTYP, "Soft Channel") field(PINI, "NO") field(SCAN, "Passive") field(OMSL, "closed_loop") field(DOL, "PSIQ:PSI1:P200:ORDER_OFFL") field(OUT, "PSIQ:PSI1:P200:RQST_OFF") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } # End of file record(bo, "PSIQ:PSI1:P500:ORDER_ON") { field(DESC, "P500 Vlv Box PD Start order on") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Ordered On") field(ONAM, "Ordered On") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "PSIQ:PSI1:P500:ON_CNCL") { field(DESC, "P500 Vlv Box PD Start Cancel ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "PSIQ:PSI1:P500:ORDER_OFF") { field(DESC, "P500 Vlv Box PD Start order off") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Order Off") field(ONAM, "Order Off") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "PSIQ:PSI1:P500:OFF_CNCL") { field(DESC, "P500 Vlv Box PD Start Cancel OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "PSIQ:PSI1:P500:ON_CFRM") { field(DESC, "P500 Vlv Box PD Start confirm ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "PSIQ:PSI1:P500:OFF_CFRM") { field(DESC, "P500 Vlv Box PD Start confirm OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "PSIQ:PSI1:P500:RQST_ON") { field(DESC, "P500 Vlv Box PD Start Rqst On") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P500_START B 0") field(HIGH, "1") field(ASG, "NOWRITE") } record(bo, "PSIQ:PSI1:P500:RQST_OFF") { field(DESC, "P500 Vlv Box PD Start Rqst Off") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P500_ABORT B 0") field(HIGH, "1") field(OMSL, "supervisory") field(ASG, "NOWRITE") } record(sub, "PSIQ:PSI1:P500:ORDER_ONL") { field(DESC, "P500 Vlv Box PD Start") field(SCAN, ".5 second") field(PINI, "NO") field(FLNK, "PSIQ:PSI1:P500:ORDER_ONT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "PSIQ:PSI1:P500:ORDER_ON") field(INPB, "PSIQ:PSI1:P500:ON_CFRM") field(INPC, "PSIQ:PSI1:P500:ON_CNCL") field(ASG, "NOWRITE") } record(bo, "PSIQ:PSI1:P500:ORDER_ONT") { field(DESC, "P500 Vlv Box PD Start") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "closed_loop") field(DOL, "PSIQ:PSI1:P500:ORDER_ONL") field(OUT, "PSIQ:PSI1:P500:RQST_ON") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } record(sub, "PSIQ:PSI1:P500:ORDER_OFFL") { field(DESC, "P500 Vlv Box PD Start") field(PINI, "NO") field(SCAN, ".5 second") field(FLNK, "PSIQ:PSI1:P500:ORDER_OFFT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "PSIQ:PSI1:P500:ORDER_OFF") field(INPB, "PSIQ:PSI1:P500:OFF_CFRM") field(INPC, "PSIQ:PSI1:P500:OFF_CNCL") field(ASG, "NOWRITE") } record(bo, "PSIQ:PSI1:P500:ORDER_OFFT") { field(DESC, "P500 Vlv Box PD Start") field(DTYP, "Soft Channel") field(PINI, "NO") field(SCAN, "Passive") field(OMSL, "closed_loop") field(DOL, "PSIQ:PSI1:P500:ORDER_OFFL") field(OUT, "PSIQ:PSI1:P500:RQST_OFF") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } # End of file record(bo, "PSIQ:PSI1:P900:ORDER_ON") { field(DESC, "P900 Vlv Box PD Stop order on") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Ordered On") field(ONAM, "Ordered On") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "PSIQ:PSI1:P900:ON_CNCL") { field(DESC, "P900 Vlv Box PD Stop Cancel ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "PSIQ:PSI1:P900:ORDER_OFF") { field(DESC, "P900 Vlv Box PD Stop order off") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Order Off") field(ONAM, "Order Off") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "PSIQ:PSI1:P900:OFF_CNCL") { field(DESC, "P900 Vlv Box PD Stop Cancel OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "PSIQ:PSI1:P900:ON_CFRM") { field(DESC, "P900 Vlv Box PD Stop confirm ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "PSIQ:PSI1:P900:OFF_CFRM") { field(DESC, "P900 Vlv Box PD Stop confirm OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "PSIQ:PSI1:P900:RQST_ON") { field(DESC, "P900 Vlv Box PD Stop Rqst On") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P900_STOP B 0") field(HIGH, "1") field(ASG, "NOWRITE") } record(bo, "PSIQ:PSI1:P900:RQST_OFF") { field(DESC, "P900 Vlv Box PD Stop Rqst Off") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P900_ABORT B 0") field(HIGH, "1") field(OMSL, "supervisory") field(ASG, "NOWRITE") } record(sub, "PSIQ:PSI1:P900:ORDER_ONL") { field(DESC, "P900 Vlv Box PD Stop") field(SCAN, ".5 second") field(PINI, "NO") field(FLNK, "PSIQ:PSI1:P900:ORDER_ONT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "PSIQ:PSI1:P900:ORDER_ON") field(INPB, "PSIQ:PSI1:P900:ON_CFRM") field(INPC, "PSIQ:PSI1:P900:ON_CNCL") field(ASG, "NOWRITE") } record(bo, "PSIQ:PSI1:P900:ORDER_ONT") { field(DESC, "P900 Vlv Box PD Stop") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "closed_loop") field(DOL, "PSIQ:PSI1:P900:ORDER_ONL") field(OUT, "PSIQ:PSI1:P900:RQST_ON") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } record(sub, "PSIQ:PSI1:P900:ORDER_OFFL") { field(DESC, "P900 Vlv Box PD Stop") field(PINI, "NO") field(SCAN, ".5 second") field(FLNK, "PSIQ:PSI1:P900:ORDER_OFFT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "PSIQ:PSI1:P900:ORDER_OFF") field(INPB, "PSIQ:PSI1:P900:OFF_CFRM") field(INPC, "PSIQ:PSI1:P900:OFF_CNCL") field(ASG, "NOWRITE") } record(bo, "PSIQ:PSI1:P900:ORDER_OFFT") { field(DESC, "P900 Vlv Box PD Stop") field(DTYP, "Soft Channel") field(PINI, "NO") field(SCAN, "Passive") field(OMSL, "closed_loop") field(DOL, "PSIQ:PSI1:P900:ORDER_OFFL") field(OUT, "PSIQ:PSI1:P900:RQST_OFF") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } # End of file record(bo, "PSIQ:PSI1:P590:ORDER_ON") { field(DESC, "P590 Vlv 2K Trip Stop order on") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Ordered On") field(ONAM, "Ordered On") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "PSIQ:PSI1:P590:ON_CNCL") { field(DESC, "P590 Vlv 2K Trip Stop Cancel ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "PSIQ:PSI1:P590:ORDER_OFF") { field(DESC, "P590 Vlv 2K Trip Stop order off") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Order Off") field(ONAM, "Order Off") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "PSIQ:PSI1:P590:OFF_CNCL") { field(DESC, "P590 Vlv 2K Trip Stop Cancel OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Cancelled") field(ONAM, "Cancelled") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "PSIQ:PSI1:P590:ON_CFRM") { field(DESC, "P590 Vlv 2K Trip Stop confirm ON order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "PSIQ:PSI1:P590:OFF_CFRM") { field(DESC, "P590 Vlv 2K Trip Stop confirm OFF order") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Confirmed") field(ONAM, "Confirmed") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "PSIQ:PSI1:P590:RQST_ON") { field(DESC, "P590 Vlv 2K Trip Stop Rqst On") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(OMSL, "supervisory") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P590_STOP B 0") field(HIGH, "1") field(ASG, "NOWRITE") } record(bo, "PSIQ:PSI1:P590:RQST_OFF") { field(DESC, "P590 Vlv 2K Trip Stop Rqst Off") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "NO") field(ZNAM, "Not Active") field(ONAM, "Active") field(OUT, "@$(PLC_NAME) P590_ABORT B 0") field(HIGH, "1") field(OMSL, "supervisory") field(ASG, "NOWRITE") } record(sub, "PSIQ:PSI1:P590:ORDER_ONL") { field(DESC, "P590 Vlv 2K Trip Stop") field(SCAN, ".5 second") field(PINI, "NO") field(FLNK, "PSIQ:PSI1:P590:ORDER_ONT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "PSIQ:PSI1:P590:ORDER_ON") field(INPB, "PSIQ:PSI1:P590:ON_CFRM") field(INPC, "PSIQ:PSI1:P590:ON_CNCL") field(ASG, "NOWRITE") } record(bo, "PSIQ:PSI1:P590:ORDER_ONT") { field(DESC, "P590 Vlv 2K Trip Stop") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "closed_loop") field(DOL, "PSIQ:PSI1:P590:ORDER_ONL") field(OUT, "PSIQ:PSI1:P590:RQST_ON") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } record(sub, "PSIQ:PSI1:P590:ORDER_OFFL") { field(DESC, "P590 Vlv 2K Trip Stop") field(PINI, "NO") field(SCAN, ".5 second") field(FLNK, "PSIQ:PSI1:P590:ORDER_OFFT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "PSIQ:PSI1:P590:ORDER_OFF") field(INPB, "PSIQ:PSI1:P590:OFF_CFRM") field(INPC, "PSIQ:PSI1:P590:OFF_CNCL") field(ASG, "NOWRITE") } record(bo, "PSIQ:PSI1:P590:ORDER_OFFT") { field(DESC, "P590 Vlv 2K Trip Stop") field(DTYP, "Soft Channel") field(PINI, "NO") field(SCAN, "Passive") field(OMSL, "closed_loop") field(DOL, "PSIQ:PSI1:P590:ORDER_OFFL") field(OUT, "PSIQ:PSI1:P590:RQST_OFF") field(ZNAM, "Disabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(ASG, "NOWRITE") } # End of file record(bi, "CXY:PSI4:5413:MMOD") { field(DESC, "Manual Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_XY45413.mmod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bi, "CXY:PSI4:5413:IMOD") { field(DESC, "Interlock mode") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_XY45413.imod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CXY:PSI4:5413:DESC") { field(DESC, "DO Actuator Description") field(DTYP, "Soft Channel") field(PINI, "YES") field(VAL, "K-Pump #1 Rem Start") info(autosaveFields, "VAL") } record(stringin, "CXY:PSI4:5413:TEXT1") { field(DESC, "Notes 1") field(DTYP, "Soft Channel") field(PINI, "YES") info(autosaveFields, "VAL") } record(stringin, "CXY:PSI4:5413:TEXT2") { field(DESC, "Notes 2") field(DTYP, "Soft Channel") field(PINI, "YES") info(autosaveFields, "VAL") } record(bi, "CXY:PSI4:5413:INTERLOCK") { field(DESC, "Interlock status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_XY45413.Interlock_Condition") field(ZNAM, "Ok") field(ONAM, "Interlocked") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CXY:PSI4:5413:IVAL") { field(DESC, "Interlock state") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_XY45413.ival") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CXY:PSI4:5413:OUTPUT") { field(DESC, "actuatorDO output command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_XY45413.Output") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bo, "CXY:PSI4:5413:MANUAL") { field(DESC, "Manual Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Manual") field(ONAM, "Manual") field(OUT, "@$(PLC_NAME) P1_XY45413.Manual B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bo, "CXY:PSI4:5413:SEQUENCER") { field(DESC, "SEQ Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Sequencer") field(ONAM, "Sequencer") field(OUT, "@$(PLC_NAME) P1_XY45413.Sequencer B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ai, "CXY:PSI4:5413:MODE") { field(DESC, "Actuator mode (man,ovr,seq)") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_XY45413.MODE") } record(bi, "CXY:PSI4:5413:ALM") { field(DESC, "Limit SW alarm") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_XY45413.ER") field(ZNAM, "Ok") field(ONAM, "Alarm") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CXY:PSI4:5413:IL_LATCH") { field(DESC, "Interlock latched indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_XY45413.Interlock_Condition_L") field(ZNAM, "Ok") field(ONAM, "Latched") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CXY:PSI4:5413:IL_RESET") { field(DESC, "Interlock Latch Reset") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Reset") field(ONAM, "Reset") field(OUT, "@$(PLC_NAME) P1_XY45413.Interlock_Condition_Reset B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CXY:PSI4:5413:ZSH") { field(DESC, "High limit sw value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_XY45413.ZSH") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CXY:PSI4:5413:ZSL") { field(DESC, "low limit sw value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_XY45413.ZSL") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CXY:PSI4:5413:MVAL") { field(DESC, "manual mode program command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_XY45413.mval") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CXY:PSI4:5413:MODE_STRING") { field(DESC, "Actuator (DO) Mode String") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_XY45413.Mode_String") } record(bi, "CXY:PSI4:5413:SVAL") { field(DESC, "sequencer mode output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_XY45413.sval") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CXY:PSI4:5413:PIDTAG") { field(DESC, "P1_XY45413 PIDTAG") field(PINI, "YES") field(VAL, "P1_XY45413") } record(bi, "CXY:PSI4:5413:SMOD") { field(DESC, "Sequencer mode indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_XY45413.smod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } # Records added post-SRR-4 record(bi, "CXY:PSI4:5413:OMOD") { field(DESC, "Override mode indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_XY45413.omod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CXY:PSI4:5413:OVERRIDE") { field(DESC, "Override Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Override") field(ONAM, "Override") field(OUT, "@$(PLC_NAME) P1_XY45413.Override B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CXY:PSI4:5413:MAN_OUTPUT") { field(DESC, "manual mode program command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_XY45413.Manual_output") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CXY:PSI4:5413:ON") { field(DESC, "Open command from EPICS") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Open") field(ONAM, "Open") field(OUT, "@$(PLC_NAME) P1_XY45413.EN B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bo, "CXY:PSI4:5413:OFF") { field(DESC, "Close command from EPICS") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Close") field(ONAM, "Close") field(OUT, "@$(PLC_NAME) P1_XY45413.DIS B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CXY:PSI4:5414:MMOD") { field(DESC, "Manual Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_XY45414.mmod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bi, "CXY:PSI4:5414:IMOD") { field(DESC, "Interlock mode") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_XY45414.imod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CXY:PSI4:5414:DESC") { field(DESC, "DO Actuator Description") field(DTYP, "Soft Channel") field(PINI, "YES") field(VAL, "K-Pump #1 Rem Stop") info(autosaveFields, "VAL") } record(stringin, "CXY:PSI4:5414:TEXT1") { field(DESC, "Notes 1") field(DTYP, "Soft Channel") field(PINI, "YES") info(autosaveFields, "VAL") } record(stringin, "CXY:PSI4:5414:TEXT2") { field(DESC, "Notes 2") field(DTYP, "Soft Channel") field(PINI, "YES") info(autosaveFields, "VAL") } record(bi, "CXY:PSI4:5414:INTERLOCK") { field(DESC, "Interlock status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_XY45414.Interlock_Condition") field(ZNAM, "Ok") field(ONAM, "Interlocked") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CXY:PSI4:5414:IVAL") { field(DESC, "Interlock state") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_XY45414.ival") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CXY:PSI4:5414:OUTPUT") { field(DESC, "actuatorDO output command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_XY45414.Output") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bo, "CXY:PSI4:5414:MANUAL") { field(DESC, "Manual Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Manual") field(ONAM, "Manual") field(OUT, "@$(PLC_NAME) P1_XY45414.Manual B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bo, "CXY:PSI4:5414:SEQUENCER") { field(DESC, "SEQ Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Sequencer") field(ONAM, "Sequencer") field(OUT, "@$(PLC_NAME) P1_XY45414.Sequencer B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ai, "CXY:PSI4:5414:MODE") { field(DESC, "Actuator mode (man,ovr,seq)") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_XY45414.MODE") } record(bi, "CXY:PSI4:5414:ALM") { field(DESC, "Limit SW alarm") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_XY45414.ER") field(ZNAM, "Ok") field(ONAM, "Alarm") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CXY:PSI4:5414:IL_LATCH") { field(DESC, "Interlock latched indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_XY45414.Interlock_Condition_L") field(ZNAM, "Ok") field(ONAM, "Latched") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CXY:PSI4:5414:IL_RESET") { field(DESC, "Interlock Latch Reset") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Reset") field(ONAM, "Reset") field(OUT, "@$(PLC_NAME) P1_XY45414.Interlock_Condition_Reset B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CXY:PSI4:5414:ZSH") { field(DESC, "High limit sw value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_XY45414.ZSH") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CXY:PSI4:5414:ZSL") { field(DESC, "low limit sw value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_XY45414.ZSL") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CXY:PSI4:5414:MVAL") { field(DESC, "manual mode program command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_XY45414.mval") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CXY:PSI4:5414:MODE_STRING") { field(DESC, "Actuator (DO) Mode String") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_XY45414.Mode_String") } record(bi, "CXY:PSI4:5414:SVAL") { field(DESC, "sequencer mode output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_XY45414.sval") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CXY:PSI4:5414:PIDTAG") { field(DESC, "P1_XY45414 PIDTAG") field(PINI, "YES") field(VAL, "P1_XY45414") } record(bi, "CXY:PSI4:5414:SMOD") { field(DESC, "Sequencer mode indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_XY45414.smod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } # Records added post-SRR-4 record(bi, "CXY:PSI4:5414:OMOD") { field(DESC, "Override mode indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_XY45414.omod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CXY:PSI4:5414:OVERRIDE") { field(DESC, "Override Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Override") field(ONAM, "Override") field(OUT, "@$(PLC_NAME) P1_XY45414.Override B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CXY:PSI4:5414:MAN_OUTPUT") { field(DESC, "manual mode program command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_XY45414.Manual_output") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CXY:PSI4:5414:ON") { field(DESC, "Open command from EPICS") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Open") field(ONAM, "Open") field(OUT, "@$(PLC_NAME) P1_XY45414.EN B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bo, "CXY:PSI4:5414:OFF") { field(DESC, "Close command from EPICS") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Close") field(ONAM, "Close") field(OUT, "@$(PLC_NAME) P1_XY45414.DIS B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CSV:PSI4:5411:MMOD") { field(DESC, "Manual Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_SV45411.mmod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bi, "CSV:PSI4:5411:IMOD") { field(DESC, "Interlock mode") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_SV45411.imod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CSV:PSI4:5411:DESC") { field(DESC, "DO Actuator Description") field(DTYP, "Soft Channel") field(PINI, "YES") field(VAL, "K-Pump #1 Pilot Bypass Valve") info(autosaveFields, "VAL") } record(stringin, "CSV:PSI4:5411:TEXT1") { field(DESC, "Notes 1") field(DTYP, "Soft Channel") field(PINI, "YES") info(autosaveFields, "VAL") } record(stringin, "CSV:PSI4:5411:TEXT2") { field(DESC, "Notes 2") field(DTYP, "Soft Channel") field(PINI, "YES") info(autosaveFields, "VAL") } record(bi, "CSV:PSI4:5411:INTERLOCK") { field(DESC, "Interlock status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_SV45411.Interlock_Condition") field(ZNAM, "Ok") field(ONAM, "Interlocked") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CSV:PSI4:5411:IVAL") { field(DESC, "Interlock state") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_SV45411.ival") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CSV:PSI4:5411:OUTPUT") { field(DESC, "actuatorDO output command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_SV45411.Output") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bo, "CSV:PSI4:5411:MANUAL") { field(DESC, "Manual Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Manual") field(ONAM, "Manual") field(OUT, "@$(PLC_NAME) P1_SV45411.Manual B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bo, "CSV:PSI4:5411:SEQUENCER") { field(DESC, "SEQ Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Sequencer") field(ONAM, "Sequencer") field(OUT, "@$(PLC_NAME) P1_SV45411.Sequencer B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ai, "CSV:PSI4:5411:MODE") { field(DESC, "Actuator mode (man,ovr,seq)") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_SV45411.MODE") } record(bi, "CSV:PSI4:5411:ALM") { field(DESC, "Limit SW alarm") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_SV45411.ER") field(ZNAM, "Ok") field(ONAM, "Alarm") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CSV:PSI4:5411:IL_LATCH") { field(DESC, "Interlock latched indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_SV45411.Interlock_Condition_L") field(ZNAM, "Ok") field(ONAM, "Latched") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CSV:PSI4:5411:IL_RESET") { field(DESC, "Interlock Latch Reset") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Reset") field(ONAM, "Reset") field(OUT, "@$(PLC_NAME) P1_SV45411.Interlock_Condition_Reset B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CSV:PSI4:5411:ZSH") { field(DESC, "High limit sw value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_SV45411.ZSH") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CSV:PSI4:5411:ZSL") { field(DESC, "low limit sw value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_SV45411.ZSL") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CSV:PSI4:5411:MVAL") { field(DESC, "manual mode program command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_SV45411.mval") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CSV:PSI4:5411:MODE_STRING") { field(DESC, "Actuator (DO) Mode String") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_SV45411.Mode_String") } record(bi, "CSV:PSI4:5411:SVAL") { field(DESC, "sequencer mode output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_SV45411.sval") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CSV:PSI4:5411:PIDTAG") { field(DESC, "P1_SV45411 PIDTAG") field(PINI, "YES") field(VAL, "P1_SV45411") } record(bi, "CSV:PSI4:5411:SMOD") { field(DESC, "Sequencer mode indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_SV45411.smod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } # Records added post-SRR-4 record(bi, "CSV:PSI4:5411:OMOD") { field(DESC, "Override mode indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_SV45411.omod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CSV:PSI4:5411:OVERRIDE") { field(DESC, "Override Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Override") field(ONAM, "Override") field(OUT, "@$(PLC_NAME) P1_SV45411.Override B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CSV:PSI4:5411:MAN_OUTPUT") { field(DESC, "manual mode program command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_SV45411.Manual_output") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CSV:PSI4:5411:OPEN") { field(DESC, "Open command from EPICS") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Open") field(ONAM, "Open") field(OUT, "@$(PLC_NAME) P1_SV45411.EN B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bo, "CSV:PSI4:5411:CLOSE") { field(DESC, "Close command from EPICS") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Close") field(ONAM, "Close") field(OUT, "@$(PLC_NAME) P1_SV45411.DIS B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CSV:PSI4:5412:MMOD") { field(DESC, "Manual Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_SV45412.mmod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bi, "CSV:PSI4:5412:IMOD") { field(DESC, "Interlock mode") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_SV45412.imod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CSV:PSI4:5412:DESC") { field(DESC, "DO Actuator Description") field(DTYP, "Soft Channel") field(PINI, "YES") field(VAL, "K-Pump #1 Pilot Suction Valve") info(autosaveFields, "VAL") } record(stringin, "CSV:PSI4:5412:TEXT1") { field(DESC, "Notes 1") field(DTYP, "Soft Channel") field(PINI, "YES") info(autosaveFields, "VAL") } record(stringin, "CSV:PSI4:5412:TEXT2") { field(DESC, "Notes 2") field(DTYP, "Soft Channel") field(PINI, "YES") info(autosaveFields, "VAL") } record(bi, "CSV:PSI4:5412:INTERLOCK") { field(DESC, "Interlock status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_SV45412.Interlock_Condition") field(ZNAM, "Ok") field(ONAM, "Interlocked") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CSV:PSI4:5412:IVAL") { field(DESC, "Interlock state") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_SV45412.ival") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CSV:PSI4:5412:OUTPUT") { field(DESC, "actuatorDO output command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_SV45412.Output") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bo, "CSV:PSI4:5412:MANUAL") { field(DESC, "Manual Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Manual") field(ONAM, "Manual") field(OUT, "@$(PLC_NAME) P1_SV45412.Manual B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bo, "CSV:PSI4:5412:SEQUENCER") { field(DESC, "SEQ Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Sequencer") field(ONAM, "Sequencer") field(OUT, "@$(PLC_NAME) P1_SV45412.Sequencer B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ai, "CSV:PSI4:5412:MODE") { field(DESC, "Actuator mode (man,ovr,seq)") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_SV45412.MODE") } record(bi, "CSV:PSI4:5412:ALM") { field(DESC, "Limit SW alarm") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_SV45412.ER") field(ZNAM, "Ok") field(ONAM, "Alarm") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CSV:PSI4:5412:IL_LATCH") { field(DESC, "Interlock latched indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_SV45412.Interlock_Condition_L") field(ZNAM, "Ok") field(ONAM, "Latched") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CSV:PSI4:5412:IL_RESET") { field(DESC, "Interlock Latch Reset") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Reset") field(ONAM, "Reset") field(OUT, "@$(PLC_NAME) P1_SV45412.Interlock_Condition_Reset B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CSV:PSI4:5412:ZSH") { field(DESC, "High limit sw value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_SV45412.ZSH") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CSV:PSI4:5412:ZSL") { field(DESC, "low limit sw value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_SV45412.ZSL") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CSV:PSI4:5412:MVAL") { field(DESC, "manual mode program command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_SV45412.mval") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CSV:PSI4:5412:MODE_STRING") { field(DESC, "Actuator (DO) Mode String") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_SV45412.Mode_String") } record(bi, "CSV:PSI4:5412:SVAL") { field(DESC, "sequencer mode output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_SV45412.sval") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CSV:PSI4:5412:PIDTAG") { field(DESC, "P1_SV45412 PIDTAG") field(PINI, "YES") field(VAL, "P1_SV45412") } record(bi, "CSV:PSI4:5412:SMOD") { field(DESC, "Sequencer mode indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_SV45412.smod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } # Records added post-SRR-4 record(bi, "CSV:PSI4:5412:OMOD") { field(DESC, "Override mode indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_SV45412.omod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CSV:PSI4:5412:OVERRIDE") { field(DESC, "Override Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Override") field(ONAM, "Override") field(OUT, "@$(PLC_NAME) P1_SV45412.Override B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CSV:PSI4:5412:MAN_OUTPUT") { field(DESC, "manual mode program command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_SV45412.Manual_output") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CSV:PSI4:5412:OPEN") { field(DESC, "Open command from EPICS") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Open") field(ONAM, "Open") field(OUT, "@$(PLC_NAME) P1_SV45412.EN B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bo, "CSV:PSI4:5412:CLOSE") { field(DESC, "Close command from EPICS") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Close") field(ONAM, "Close") field(OUT, "@$(PLC_NAME) P1_SV45412.DIS B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CSV:PSI7:1050:MMOD") { field(DESC, "Manual Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) C_SV71050.mmod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bi, "CSV:PSI7:1050:IMOD") { field(DESC, "Interlock mode") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) C_SV71050.imod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CSV:PSI7:1050:DESC") { field(DESC, "DO Actuator Description") field(DTYP, "Soft Channel") field(PINI, "YES") field(VAL, "K-Pump #1 SLAC GHe Rtn Valve") info(autosaveFields, "VAL") } record(stringin, "CSV:PSI7:1050:TEXT1") { field(DESC, "Notes 1") field(DTYP, "Soft Channel") field(PINI, "YES") info(autosaveFields, "VAL") } record(stringin, "CSV:PSI7:1050:TEXT2") { field(DESC, "Notes 2") field(DTYP, "Soft Channel") field(PINI, "YES") info(autosaveFields, "VAL") } record(bi, "CSV:PSI7:1050:INTERLOCK") { field(DESC, "Interlock status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) C_SV71050.Interlock_Condition") field(ZNAM, "Ok") field(ONAM, "Interlocked") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CSV:PSI7:1050:IVAL") { field(DESC, "Interlock state") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) C_SV71050.ival") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CSV:PSI7:1050:OUTPUT") { field(DESC, "actuatorDO output command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) C_SV71050.Output") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bo, "CSV:PSI7:1050:MANUAL") { field(DESC, "Manual Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Manual") field(ONAM, "Manual") field(OUT, "@$(PLC_NAME) C_SV71050.Manual B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bo, "CSV:PSI7:1050:SEQUENCER") { field(DESC, "SEQ Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Sequencer") field(ONAM, "Sequencer") field(OUT, "@$(PLC_NAME) C_SV71050.Sequencer B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ai, "CSV:PSI7:1050:MODE") { field(DESC, "Actuator mode (man,ovr,seq)") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) C_SV71050.MODE") } record(bi, "CSV:PSI7:1050:ALM") { field(DESC, "Limit SW alarm") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) C_SV71050.ER") field(ZNAM, "Ok") field(ONAM, "Alarm") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CSV:PSI7:1050:IL_LATCH") { field(DESC, "Interlock latched indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) C_SV71050.Interlock_Condition_L") field(ZNAM, "Ok") field(ONAM, "Latched") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CSV:PSI7:1050:IL_RESET") { field(DESC, "Interlock Latch Reset") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Reset") field(ONAM, "Reset") field(OUT, "@$(PLC_NAME) C_SV71050.Interlock_Condition_Reset B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CSV:PSI7:1050:ZSH") { field(DESC, "High limit sw value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) C_SV71050.ZSH") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CSV:PSI7:1050:ZSL") { field(DESC, "low limit sw value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) C_SV71050.ZSL") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CSV:PSI7:1050:MVAL") { field(DESC, "manual mode program command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) C_SV71050.mval") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CSV:PSI7:1050:MODE_STRING") { field(DESC, "Actuator (DO) Mode String") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) C_SV71050.Mode_String") } record(bi, "CSV:PSI7:1050:SVAL") { field(DESC, "sequencer mode output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) C_SV71050.sval") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CSV:PSI7:1050:PIDTAG") { field(DESC, "C_SV71050 PIDTAG") field(PINI, "YES") field(VAL, "C_SV71050") } record(bi, "CSV:PSI7:1050:SMOD") { field(DESC, "Sequencer mode indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) C_SV71050.smod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } # Records added post-SRR-4 record(bi, "CSV:PSI7:1050:OMOD") { field(DESC, "Override mode indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) C_SV71050.omod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CSV:PSI7:1050:OVERRIDE") { field(DESC, "Override Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Override") field(ONAM, "Override") field(OUT, "@$(PLC_NAME) C_SV71050.Override B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CSV:PSI7:1050:MAN_OUTPUT") { field(DESC, "manual mode program command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) C_SV71050.Manual_output") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CSV:PSI7:1050:OPEN") { field(DESC, "Open command from EPICS") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Open") field(ONAM, "Open") field(OUT, "@$(PLC_NAME) C_SV71050.EN B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bo, "CSV:PSI7:1050:CLOSE") { field(DESC, "Close command from EPICS") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Close") field(ONAM, "Close") field(OUT, "@$(PLC_NAME) C_SV71050.DIS B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CHTR:PSI5:5501:MMOD") { field(DESC, "Manual Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55501.mmod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bi, "CHTR:PSI5:5501:IMOD") { field(DESC, "Interlock mode") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55501.imod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CHTR:PSI5:5501:DESC") { field(DESC, "DO Actuator Description") field(DTYP, "Soft Channel") field(PINI, "YES") field(VAL, "PsiCube Heater 01 in LHe Vessel") info(autosaveFields, "VAL") } record(stringin, "CHTR:PSI5:5501:TEXT1") { field(DESC, "Notes 1") field(DTYP, "Soft Channel") field(PINI, "YES") info(autosaveFields, "VAL") } record(stringin, "CHTR:PSI5:5501:TEXT2") { field(DESC, "Notes 2") field(DTYP, "Soft Channel") field(PINI, "YES") info(autosaveFields, "VAL") } record(bi, "CHTR:PSI5:5501:INTERLOCK") { field(DESC, "Interlock status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55501.Interlock_Condition") field(ZNAM, "Ok") field(ONAM, "Interlocked") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5501:IVAL") { field(DESC, "Interlock state") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55501.ival") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5501:OUTPUT") { field(DESC, "actuatorDO output command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55501.Output") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bo, "CHTR:PSI5:5501:MANUAL") { field(DESC, "Manual Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Manual") field(ONAM, "Manual") field(OUT, "@$(PLC_NAME) P1_HT55501.Manual B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5501:SEQUENCER") { field(DESC, "SEQ Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Sequencer") field(ONAM, "Sequencer") field(OUT, "@$(PLC_NAME) P1_HT55501.Sequencer B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ai, "CHTR:PSI5:5501:MODE") { field(DESC, "Actuator mode (man,ovr,seq)") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55501.MODE") } record(bi, "CHTR:PSI5:5501:ALM") { field(DESC, "Limit SW alarm") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55501.ER") field(ZNAM, "Ok") field(ONAM, "Alarm") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5501:IL_LATCH") { field(DESC, "Interlock latched indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55501.Interlock_Condition_L") field(ZNAM, "Ok") field(ONAM, "Latched") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CHTR:PSI5:5501:IL_RESET") { field(DESC, "Interlock Latch Reset") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Reset") field(ONAM, "Reset") field(OUT, "@$(PLC_NAME) P1_HT55501.Interlock_Condition_Reset B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CHTR:PSI5:5501:ZSH") { field(DESC, "High limit sw value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55501.ZSH") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5501:ZSL") { field(DESC, "low limit sw value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55501.ZSL") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5501:MVAL") { field(DESC, "manual mode program command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55501.mval") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CHTR:PSI5:5501:MODE_STRING") { field(DESC, "Actuator (DO) Mode String") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55501.Mode_String") } record(bi, "CHTR:PSI5:5501:SVAL") { field(DESC, "sequencer mode output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55501.sval") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CHTR:PSI5:5501:PIDTAG") { field(DESC, "P1_HT55501 PIDTAG") field(PINI, "YES") field(VAL, "P1_HT55501") } record(bi, "CHTR:PSI5:5501:SMOD") { field(DESC, "Sequencer mode indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55501.smod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } # Records added post-SRR-4 record(bi, "CHTR:PSI5:5501:OMOD") { field(DESC, "Override mode indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55501.omod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CHTR:PSI5:5501:OVERRIDE") { field(DESC, "Override Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Override") field(ONAM, "Override") field(OUT, "@$(PLC_NAME) P1_HT55501.Override B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CHTR:PSI5:5501:MAN_OUTPUT") { field(DESC, "manual mode program command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55501.Manual_output") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CHTR:PSI5:5501:OPEN") { field(DESC, "Open command from EPICS") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Open") field(ONAM, "Open") field(OUT, "@$(PLC_NAME) P1_HT55501.EN B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5501:CLOSE") { field(DESC, "Close command from EPICS") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Close") field(ONAM, "Close") field(OUT, "@$(PLC_NAME) P1_HT55501.DIS B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CHTR:PSI5:5502:MMOD") { field(DESC, "Manual Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55502.mmod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bi, "CHTR:PSI5:5502:IMOD") { field(DESC, "Interlock mode") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55502.imod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CHTR:PSI5:5502:DESC") { field(DESC, "DO Actuator Description") field(DTYP, "Soft Channel") field(PINI, "YES") field(VAL, "PsiCube Heater 02") info(autosaveFields, "VAL") } record(stringin, "CHTR:PSI5:5502:TEXT1") { field(DESC, "Notes 1") field(DTYP, "Soft Channel") field(PINI, "YES") info(autosaveFields, "VAL") } record(stringin, "CHTR:PSI5:5502:TEXT2") { field(DESC, "Notes 2") field(DTYP, "Soft Channel") field(PINI, "YES") info(autosaveFields, "VAL") } record(bi, "CHTR:PSI5:5502:INTERLOCK") { field(DESC, "Interlock status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55502.Interlock_Condition") field(ZNAM, "Ok") field(ONAM, "Interlocked") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5502:IVAL") { field(DESC, "Interlock state") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55502.ival") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5502:OUTPUT") { field(DESC, "actuatorDO output command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55502.Output") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bo, "CHTR:PSI5:5502:MANUAL") { field(DESC, "Manual Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Manual") field(ONAM, "Manual") field(OUT, "@$(PLC_NAME) P1_HT55502.Manual B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5502:SEQUENCER") { field(DESC, "SEQ Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Sequencer") field(ONAM, "Sequencer") field(OUT, "@$(PLC_NAME) P1_HT55502.Sequencer B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ai, "CHTR:PSI5:5502:MODE") { field(DESC, "Actuator mode (man,ovr,seq)") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55502.MODE") } record(bi, "CHTR:PSI5:5502:ALM") { field(DESC, "Limit SW alarm") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55502.ER") field(ZNAM, "Ok") field(ONAM, "Alarm") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5502:IL_LATCH") { field(DESC, "Interlock latched indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55502.Interlock_Condition_L") field(ZNAM, "Ok") field(ONAM, "Latched") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CHTR:PSI5:5502:IL_RESET") { field(DESC, "Interlock Latch Reset") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Reset") field(ONAM, "Reset") field(OUT, "@$(PLC_NAME) P1_HT55502.Interlock_Condition_Reset B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CHTR:PSI5:5502:ZSH") { field(DESC, "High limit sw value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55502.ZSH") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5502:ZSL") { field(DESC, "low limit sw value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55502.ZSL") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5502:MVAL") { field(DESC, "manual mode program command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55502.mval") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CHTR:PSI5:5502:MODE_STRING") { field(DESC, "Actuator (DO) Mode String") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55502.Mode_String") } record(bi, "CHTR:PSI5:5502:SVAL") { field(DESC, "sequencer mode output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55502.sval") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CHTR:PSI5:5502:PIDTAG") { field(DESC, "P1_HT55502 PIDTAG") field(PINI, "YES") field(VAL, "P1_HT55502") } record(bi, "CHTR:PSI5:5502:SMOD") { field(DESC, "Sequencer mode indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55502.smod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } # Records added post-SRR-4 record(bi, "CHTR:PSI5:5502:OMOD") { field(DESC, "Override mode indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55502.omod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CHTR:PSI5:5502:OVERRIDE") { field(DESC, "Override Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Override") field(ONAM, "Override") field(OUT, "@$(PLC_NAME) P1_HT55502.Override B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CHTR:PSI5:5502:MAN_OUTPUT") { field(DESC, "manual mode program command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55502.Manual_output") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CHTR:PSI5:5502:ON") { field(DESC, "Open command from EPICS") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Open") field(ONAM, "Open") field(OUT, "@$(PLC_NAME) P1_HT55502.EN B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5502:OFF") { field(DESC, "Close command from EPICS") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Close") field(ONAM, "Close") field(OUT, "@$(PLC_NAME) P1_HT55502.DIS B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CHTR:PSI5:5503:MMOD") { field(DESC, "Manual Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55503.mmod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bi, "CHTR:PSI5:5503:IMOD") { field(DESC, "Interlock mode") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55503.imod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CHTR:PSI5:5503:DESC") { field(DESC, "DO Actuator Description") field(DTYP, "Soft Channel") field(PINI, "YES") field(VAL, "PsiCube Heater 03") info(autosaveFields, "VAL") } record(stringin, "CHTR:PSI5:5503:TEXT1") { field(DESC, "Notes 1") field(DTYP, "Soft Channel") field(PINI, "YES") info(autosaveFields, "VAL") } record(stringin, "CHTR:PSI5:5503:TEXT2") { field(DESC, "Notes 2") field(DTYP, "Soft Channel") field(PINI, "YES") info(autosaveFields, "VAL") } record(bi, "CHTR:PSI5:5503:INTERLOCK") { field(DESC, "Interlock status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55503.Interlock_Condition") field(ZNAM, "Ok") field(ONAM, "Interlocked") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5503:IVAL") { field(DESC, "Interlock state") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55503.ival") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5503:OUTPUT") { field(DESC, "actuatorDO output command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55503.Output") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bo, "CHTR:PSI5:5503:MANUAL") { field(DESC, "Manual Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Manual") field(ONAM, "Manual") field(OUT, "@$(PLC_NAME) P1_HT55503.Manual B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5503:SEQUENCER") { field(DESC, "SEQ Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Sequencer") field(ONAM, "Sequencer") field(OUT, "@$(PLC_NAME) P1_HT55503.Sequencer B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ai, "CHTR:PSI5:5503:MODE") { field(DESC, "Actuator mode (man,ovr,seq)") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55503.MODE") } record(bi, "CHTR:PSI5:5503:ALM") { field(DESC, "Limit SW alarm") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55503.ER") field(ZNAM, "Ok") field(ONAM, "Alarm") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5503:IL_LATCH") { field(DESC, "Interlock latched indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55503.Interlock_Condition_L") field(ZNAM, "Ok") field(ONAM, "Latched") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CHTR:PSI5:5503:IL_RESET") { field(DESC, "Interlock Latch Reset") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Reset") field(ONAM, "Reset") field(OUT, "@$(PLC_NAME) P1_HT55503.Interlock_Condition_Reset B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CHTR:PSI5:5503:ZSH") { field(DESC, "High limit sw value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55503.ZSH") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5503:ZSL") { field(DESC, "low limit sw value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55503.ZSL") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5503:MVAL") { field(DESC, "manual mode program command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55503.mval") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CHTR:PSI5:5503:MODE_STRING") { field(DESC, "Actuator (DO) Mode String") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55503.Mode_String") } record(bi, "CHTR:PSI5:5503:SVAL") { field(DESC, "sequencer mode output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55503.sval") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CHTR:PSI5:5503:PIDTAG") { field(DESC, "P1_HT55503 PIDTAG") field(PINI, "YES") field(VAL, "P1_HT55503") } record(bi, "CHTR:PSI5:5503:SMOD") { field(DESC, "Sequencer mode indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55503.smod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } # Records added post-SRR-4 record(bi, "CHTR:PSI5:5503:OMOD") { field(DESC, "Override mode indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55503.omod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CHTR:PSI5:5503:OVERRIDE") { field(DESC, "Override Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Override") field(ONAM, "Override") field(OUT, "@$(PLC_NAME) P1_HT55503.Override B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CHTR:PSI5:5503:MAN_OUTPUT") { field(DESC, "manual mode program command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55503.Manual_output") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CHTR:PSI5:5503:ON") { field(DESC, "Open command from EPICS") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Open") field(ONAM, "Open") field(OUT, "@$(PLC_NAME) P1_HT55503.EN B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5503:OFF") { field(DESC, "Close command from EPICS") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Close") field(ONAM, "Close") field(OUT, "@$(PLC_NAME) P1_HT55503.DIS B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CHTR:PSI5:5504:MMOD") { field(DESC, "Manual Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55504.mmod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bi, "CHTR:PSI5:5504:IMOD") { field(DESC, "Interlock mode") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55504.imod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CHTR:PSI5:5504:DESC") { field(DESC, "DO Actuator Description") field(DTYP, "Soft Channel") field(PINI, "YES") field(VAL, "PsiCube Heater 04") info(autosaveFields, "VAL") } record(stringin, "CHTR:PSI5:5504:TEXT1") { field(DESC, "Notes 1") field(DTYP, "Soft Channel") field(PINI, "YES") info(autosaveFields, "VAL") } record(stringin, "CHTR:PSI5:5504:TEXT2") { field(DESC, "Notes 2") field(DTYP, "Soft Channel") field(PINI, "YES") info(autosaveFields, "VAL") } record(bi, "CHTR:PSI5:5504:INTERLOCK") { field(DESC, "Interlock status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55504.Interlock_Condition") field(ZNAM, "Ok") field(ONAM, "Interlocked") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5504:IVAL") { field(DESC, "Interlock state") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55504.ival") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5504:OUTPUT") { field(DESC, "actuatorDO output command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55504.Output") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bo, "CHTR:PSI5:5504:MANUAL") { field(DESC, "Manual Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Manual") field(ONAM, "Manual") field(OUT, "@$(PLC_NAME) P1_HT55504.Manual B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5504:SEQUENCER") { field(DESC, "SEQ Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Sequencer") field(ONAM, "Sequencer") field(OUT, "@$(PLC_NAME) P1_HT55504.Sequencer B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ai, "CHTR:PSI5:5504:MODE") { field(DESC, "Actuator mode (man,ovr,seq)") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55504.MODE") } record(bi, "CHTR:PSI5:5504:ALM") { field(DESC, "Limit SW alarm") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55504.ER") field(ZNAM, "Ok") field(ONAM, "Alarm") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5504:IL_LATCH") { field(DESC, "Interlock latched indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55504.Interlock_Condition_L") field(ZNAM, "Ok") field(ONAM, "Latched") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CHTR:PSI5:5504:IL_RESET") { field(DESC, "Interlock Latch Reset") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Reset") field(ONAM, "Reset") field(OUT, "@$(PLC_NAME) P1_HT55504.Interlock_Condition_Reset B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CHTR:PSI5:5504:ZSH") { field(DESC, "High limit sw value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55504.ZSH") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5504:ZSL") { field(DESC, "low limit sw value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55504.ZSL") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5504:MVAL") { field(DESC, "manual mode program command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55504.mval") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CHTR:PSI5:5504:MODE_STRING") { field(DESC, "Actuator (DO) Mode String") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55504.Mode_String") } record(bi, "CHTR:PSI5:5504:SVAL") { field(DESC, "sequencer mode output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55504.sval") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CHTR:PSI5:5504:PIDTAG") { field(DESC, "P1_HT55504 PIDTAG") field(PINI, "YES") field(VAL, "P1_HT55504") } record(bi, "CHTR:PSI5:5504:SMOD") { field(DESC, "Sequencer mode indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55504.smod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } # Records added post-SRR-4 record(bi, "CHTR:PSI5:5504:OMOD") { field(DESC, "Override mode indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55504.omod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CHTR:PSI5:5504:OVERRIDE") { field(DESC, "Override Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Override") field(ONAM, "Override") field(OUT, "@$(PLC_NAME) P1_HT55504.Override B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CHTR:PSI5:5504:MAN_OUTPUT") { field(DESC, "manual mode program command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55504.Manual_output") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CHTR:PSI5:5504:ON") { field(DESC, "Open command from EPICS") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Open") field(ONAM, "Open") field(OUT, "@$(PLC_NAME) P1_HT55504.EN B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5504:OFF") { field(DESC, "Close command from EPICS") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Close") field(ONAM, "Close") field(OUT, "@$(PLC_NAME) P1_HT55504.DIS B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CHTR:PSI5:5505:MMOD") { field(DESC, "Manual Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55505.mmod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bi, "CHTR:PSI5:5505:IMOD") { field(DESC, "Interlock mode") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55505.imod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CHTR:PSI5:5505:DESC") { field(DESC, "DO Actuator Description") field(DTYP, "Soft Channel") field(PINI, "YES") field(VAL, "PsiCube Heater 05") info(autosaveFields, "VAL") } record(stringin, "CHTR:PSI5:5505:TEXT1") { field(DESC, "Notes 1") field(DTYP, "Soft Channel") field(PINI, "YES") info(autosaveFields, "VAL") } record(stringin, "CHTR:PSI5:5505:TEXT2") { field(DESC, "Notes 2") field(DTYP, "Soft Channel") field(PINI, "YES") info(autosaveFields, "VAL") } record(bi, "CHTR:PSI5:5505:INTERLOCK") { field(DESC, "Interlock status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55505.Interlock_Condition") field(ZNAM, "Ok") field(ONAM, "Interlocked") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5505:IVAL") { field(DESC, "Interlock state") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55505.ival") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5505:OUTPUT") { field(DESC, "actuatorDO output command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55505.Output") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bo, "CHTR:PSI5:5505:MANUAL") { field(DESC, "Manual Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Manual") field(ONAM, "Manual") field(OUT, "@$(PLC_NAME) P1_HT55505.Manual B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5505:SEQUENCER") { field(DESC, "SEQ Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Sequencer") field(ONAM, "Sequencer") field(OUT, "@$(PLC_NAME) P1_HT55505.Sequencer B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ai, "CHTR:PSI5:5505:MODE") { field(DESC, "Actuator mode (man,ovr,seq)") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55505.MODE") } record(bi, "CHTR:PSI5:5505:ALM") { field(DESC, "Limit SW alarm") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55505.ER") field(ZNAM, "Ok") field(ONAM, "Alarm") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5505:IL_LATCH") { field(DESC, "Interlock latched indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55505.Interlock_Condition_L") field(ZNAM, "Ok") field(ONAM, "Latched") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CHTR:PSI5:5505:IL_RESET") { field(DESC, "Interlock Latch Reset") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Reset") field(ONAM, "Reset") field(OUT, "@$(PLC_NAME) P1_HT55505.Interlock_Condition_Reset B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CHTR:PSI5:5505:ZSH") { field(DESC, "High limit sw value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55505.ZSH") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5505:ZSL") { field(DESC, "low limit sw value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55505.ZSL") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5505:MVAL") { field(DESC, "manual mode program command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55505.mval") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CHTR:PSI5:5505:MODE_STRING") { field(DESC, "Actuator (DO) Mode String") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55505.Mode_String") } record(bi, "CHTR:PSI5:5505:SVAL") { field(DESC, "sequencer mode output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55505.sval") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CHTR:PSI5:5505:PIDTAG") { field(DESC, "P1_HT55505 PIDTAG") field(PINI, "YES") field(VAL, "P1_HT55505") } record(bi, "CHTR:PSI5:5505:SMOD") { field(DESC, "Sequencer mode indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55505.smod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } # Records added post-SRR-4 record(bi, "CHTR:PSI5:5505:OMOD") { field(DESC, "Override mode indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55505.omod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CHTR:PSI5:5505:OVERRIDE") { field(DESC, "Override Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Override") field(ONAM, "Override") field(OUT, "@$(PLC_NAME) P1_HT55505.Override B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CHTR:PSI5:5505:MAN_OUTPUT") { field(DESC, "manual mode program command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55505.Manual_output") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CHTR:PSI5:5505:ON") { field(DESC, "Open command from EPICS") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Open") field(ONAM, "Open") field(OUT, "@$(PLC_NAME) P1_HT55505.EN B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5505:OFF") { field(DESC, "Close command from EPICS") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Close") field(ONAM, "Close") field(OUT, "@$(PLC_NAME) P1_HT55505.DIS B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CHTR:PSI5:5506:MMOD") { field(DESC, "Manual Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55506.mmod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bi, "CHTR:PSI5:5506:IMOD") { field(DESC, "Interlock mode") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55506.imod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CHTR:PSI5:5506:DESC") { field(DESC, "DO Actuator Description") field(DTYP, "Soft Channel") field(PINI, "YES") field(VAL, "PsiCube Heater 06") info(autosaveFields, "VAL") } record(stringin, "CHTR:PSI5:5506:TEXT1") { field(DESC, "Notes 1") field(DTYP, "Soft Channel") field(PINI, "YES") info(autosaveFields, "VAL") } record(stringin, "CHTR:PSI5:5506:TEXT2") { field(DESC, "Notes 2") field(DTYP, "Soft Channel") field(PINI, "YES") info(autosaveFields, "VAL") } record(bi, "CHTR:PSI5:5506:INTERLOCK") { field(DESC, "Interlock status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55506.Interlock_Condition") field(ZNAM, "Ok") field(ONAM, "Interlocked") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5506:IVAL") { field(DESC, "Interlock state") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55506.ival") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5506:OUTPUT") { field(DESC, "actuatorDO output command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55506.Output") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bo, "CHTR:PSI5:5506:MANUAL") { field(DESC, "Manual Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Manual") field(ONAM, "Manual") field(OUT, "@$(PLC_NAME) P1_HT55506.Manual B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5506:SEQUENCER") { field(DESC, "SEQ Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Sequencer") field(ONAM, "Sequencer") field(OUT, "@$(PLC_NAME) P1_HT55506.Sequencer B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ai, "CHTR:PSI5:5506:MODE") { field(DESC, "Actuator mode (man,ovr,seq)") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55506.MODE") } record(bi, "CHTR:PSI5:5506:ALM") { field(DESC, "Limit SW alarm") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55506.ER") field(ZNAM, "Ok") field(ONAM, "Alarm") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5506:IL_LATCH") { field(DESC, "Interlock latched indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55506.Interlock_Condition_L") field(ZNAM, "Ok") field(ONAM, "Latched") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CHTR:PSI5:5506:IL_RESET") { field(DESC, "Interlock Latch Reset") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Reset") field(ONAM, "Reset") field(OUT, "@$(PLC_NAME) P1_HT55506.Interlock_Condition_Reset B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CHTR:PSI5:5506:ZSH") { field(DESC, "High limit sw value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55506.ZSH") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5506:ZSL") { field(DESC, "low limit sw value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55506.ZSL") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5506:MVAL") { field(DESC, "manual mode program command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55506.mval") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CHTR:PSI5:5506:MODE_STRING") { field(DESC, "Actuator (DO) Mode String") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55506.Mode_String") } record(bi, "CHTR:PSI5:5506:SVAL") { field(DESC, "sequencer mode output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55506.sval") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CHTR:PSI5:5506:PIDTAG") { field(DESC, "P1_HT55506 PIDTAG") field(PINI, "YES") field(VAL, "P1_HT55506") } record(bi, "CHTR:PSI5:5506:SMOD") { field(DESC, "Sequencer mode indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55506.smod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } # Records added post-SRR-4 record(bi, "CHTR:PSI5:5506:OMOD") { field(DESC, "Override mode indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55506.omod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CHTR:PSI5:5506:OVERRIDE") { field(DESC, "Override Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Override") field(ONAM, "Override") field(OUT, "@$(PLC_NAME) P1_HT55506.Override B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CHTR:PSI5:5506:MAN_OUTPUT") { field(DESC, "manual mode program command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55506.Manual_output") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CHTR:PSI5:5506:ON") { field(DESC, "Open command from EPICS") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Open") field(ONAM, "Open") field(OUT, "@$(PLC_NAME) P1_HT55506.EN B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5506:OFF") { field(DESC, "Close command from EPICS") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Close") field(ONAM, "Close") field(OUT, "@$(PLC_NAME) P1_HT55506.DIS B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CHTR:PSI5:5507:MMOD") { field(DESC, "Manual Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55507.mmod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bi, "CHTR:PSI5:5507:IMOD") { field(DESC, "Interlock mode") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55507.imod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CHTR:PSI5:5507:DESC") { field(DESC, "DO Actuator Description") field(DTYP, "Soft Channel") field(PINI, "YES") field(VAL, "PsiCube Heater 07") info(autosaveFields, "VAL") } record(stringin, "CHTR:PSI5:5507:TEXT1") { field(DESC, "Notes 1") field(DTYP, "Soft Channel") field(PINI, "YES") info(autosaveFields, "VAL") } record(stringin, "CHTR:PSI5:5507:TEXT2") { field(DESC, "Notes 2") field(DTYP, "Soft Channel") field(PINI, "YES") info(autosaveFields, "VAL") } record(bi, "CHTR:PSI5:5507:INTERLOCK") { field(DESC, "Interlock status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55507.Interlock_Condition") field(ZNAM, "Ok") field(ONAM, "Interlocked") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5507:IVAL") { field(DESC, "Interlock state") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55507.ival") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5507:OUTPUT") { field(DESC, "actuatorDO output command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55507.Output") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bo, "CHTR:PSI5:5507:MANUAL") { field(DESC, "Manual Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Manual") field(ONAM, "Manual") field(OUT, "@$(PLC_NAME) P1_HT55507.Manual B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5507:SEQUENCER") { field(DESC, "SEQ Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Sequencer") field(ONAM, "Sequencer") field(OUT, "@$(PLC_NAME) P1_HT55507.Sequencer B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ai, "CHTR:PSI5:5507:MODE") { field(DESC, "Actuator mode (man,ovr,seq)") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55507.MODE") } record(bi, "CHTR:PSI5:5507:ALM") { field(DESC, "Limit SW alarm") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55507.ER") field(ZNAM, "Ok") field(ONAM, "Alarm") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5507:IL_LATCH") { field(DESC, "Interlock latched indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55507.Interlock_Condition_L") field(ZNAM, "Ok") field(ONAM, "Latched") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CHTR:PSI5:5507:IL_RESET") { field(DESC, "Interlock Latch Reset") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Reset") field(ONAM, "Reset") field(OUT, "@$(PLC_NAME) P1_HT55507.Interlock_Condition_Reset B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CHTR:PSI5:5507:ZSH") { field(DESC, "High limit sw value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55507.ZSH") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5507:ZSL") { field(DESC, "low limit sw value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55507.ZSL") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5507:MVAL") { field(DESC, "manual mode program command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55507.mval") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CHTR:PSI5:5507:MODE_STRING") { field(DESC, "Actuator (DO) Mode String") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55507.Mode_String") } record(bi, "CHTR:PSI5:5507:SVAL") { field(DESC, "sequencer mode output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55507.sval") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CHTR:PSI5:5507:PIDTAG") { field(DESC, "P1_HT55507 PIDTAG") field(PINI, "YES") field(VAL, "P1_HT55507") } record(bi, "CHTR:PSI5:5507:SMOD") { field(DESC, "Sequencer mode indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55507.smod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } # Records added post-SRR-4 record(bi, "CHTR:PSI5:5507:OMOD") { field(DESC, "Override mode indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55507.omod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CHTR:PSI5:5507:OVERRIDE") { field(DESC, "Override Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Override") field(ONAM, "Override") field(OUT, "@$(PLC_NAME) P1_HT55507.Override B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CHTR:PSI5:5507:MAN_OUTPUT") { field(DESC, "manual mode program command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55507.Manual_output") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CHTR:PSI5:5507:ON") { field(DESC, "Open command from EPICS") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Open") field(ONAM, "Open") field(OUT, "@$(PLC_NAME) P1_HT55507.EN B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5507:OFF") { field(DESC, "Close command from EPICS") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Close") field(ONAM, "Close") field(OUT, "@$(PLC_NAME) P1_HT55507.DIS B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CHTR:PSI5:5508:MMOD") { field(DESC, "Manual Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55508.mmod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bi, "CHTR:PSI5:5508:IMOD") { field(DESC, "Interlock mode") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55508.imod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CHTR:PSI5:5508:DESC") { field(DESC, "DO Actuator Description") field(DTYP, "Soft Channel") field(PINI, "YES") field(VAL, "PsiCube Heater 08") info(autosaveFields, "VAL") } record(stringin, "CHTR:PSI5:5508:TEXT1") { field(DESC, "Notes 1") field(DTYP, "Soft Channel") field(PINI, "YES") info(autosaveFields, "VAL") } record(stringin, "CHTR:PSI5:5508:TEXT2") { field(DESC, "Notes 2") field(DTYP, "Soft Channel") field(PINI, "YES") info(autosaveFields, "VAL") } record(bi, "CHTR:PSI5:5508:INTERLOCK") { field(DESC, "Interlock status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55508.Interlock_Condition") field(ZNAM, "Ok") field(ONAM, "Interlocked") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5508:IVAL") { field(DESC, "Interlock state") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55508.ival") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5508:OUTPUT") { field(DESC, "actuatorDO output command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55508.Output") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bo, "CHTR:PSI5:5508:MANUAL") { field(DESC, "Manual Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Manual") field(ONAM, "Manual") field(OUT, "@$(PLC_NAME) P1_HT55508.Manual B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5508:SEQUENCER") { field(DESC, "SEQ Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Sequencer") field(ONAM, "Sequencer") field(OUT, "@$(PLC_NAME) P1_HT55508.Sequencer B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ai, "CHTR:PSI5:5508:MODE") { field(DESC, "Actuator mode (man,ovr,seq)") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55508.MODE") } record(bi, "CHTR:PSI5:5508:ALM") { field(DESC, "Limit SW alarm") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55508.ER") field(ZNAM, "Ok") field(ONAM, "Alarm") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5508:IL_LATCH") { field(DESC, "Interlock latched indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55508.Interlock_Condition_L") field(ZNAM, "Ok") field(ONAM, "Latched") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CHTR:PSI5:5508:IL_RESET") { field(DESC, "Interlock Latch Reset") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Reset") field(ONAM, "Reset") field(OUT, "@$(PLC_NAME) P1_HT55508.Interlock_Condition_Reset B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CHTR:PSI5:5508:ZSH") { field(DESC, "High limit sw value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55508.ZSH") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5508:ZSL") { field(DESC, "low limit sw value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55508.ZSL") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5508:MVAL") { field(DESC, "manual mode program command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55508.mval") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CHTR:PSI5:5508:MODE_STRING") { field(DESC, "Actuator (DO) Mode String") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55508.Mode_String") } record(bi, "CHTR:PSI5:5508:SVAL") { field(DESC, "sequencer mode output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55508.sval") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CHTR:PSI5:5508:PIDTAG") { field(DESC, "P1_HT55508 PIDTAG") field(PINI, "YES") field(VAL, "P1_HT55508") } record(bi, "CHTR:PSI5:5508:SMOD") { field(DESC, "Sequencer mode indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55508.smod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } # Records added post-SRR-4 record(bi, "CHTR:PSI5:5508:OMOD") { field(DESC, "Override mode indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55508.omod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CHTR:PSI5:5508:OVERRIDE") { field(DESC, "Override Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Override") field(ONAM, "Override") field(OUT, "@$(PLC_NAME) P1_HT55508.Override B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CHTR:PSI5:5508:MAN_OUTPUT") { field(DESC, "manual mode program command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55508.Manual_output") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CHTR:PSI5:5508:ON") { field(DESC, "Open command from EPICS") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Open") field(ONAM, "Open") field(OUT, "@$(PLC_NAME) P1_HT55508.EN B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5508:OFF") { field(DESC, "Close command from EPICS") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Close") field(ONAM, "Close") field(OUT, "@$(PLC_NAME) P1_HT55508.DIS B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CHTR:PSI5:5509:MMOD") { field(DESC, "Manual Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55509.mmod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bi, "CHTR:PSI5:5509:IMOD") { field(DESC, "Interlock mode") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55509.imod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CHTR:PSI5:5509:DESC") { field(DESC, "DO Actuator Description") field(DTYP, "Soft Channel") field(PINI, "YES") field(VAL, "PsiCube Heater 09") info(autosaveFields, "VAL") } record(stringin, "CHTR:PSI5:5509:TEXT1") { field(DESC, "Notes 1") field(DTYP, "Soft Channel") field(PINI, "YES") info(autosaveFields, "VAL") } record(stringin, "CHTR:PSI5:5509:TEXT2") { field(DESC, "Notes 2") field(DTYP, "Soft Channel") field(PINI, "YES") info(autosaveFields, "VAL") } record(bi, "CHTR:PSI5:5509:INTERLOCK") { field(DESC, "Interlock status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55509.Interlock_Condition") field(ZNAM, "Ok") field(ONAM, "Interlocked") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5509:IVAL") { field(DESC, "Interlock state") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55509.ival") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5509:OUTPUT") { field(DESC, "actuatorDO output command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55509.Output") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bo, "CHTR:PSI5:5509:MANUAL") { field(DESC, "Manual Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Manual") field(ONAM, "Manual") field(OUT, "@$(PLC_NAME) P1_HT55509.Manual B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5509:SEQUENCER") { field(DESC, "SEQ Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Sequencer") field(ONAM, "Sequencer") field(OUT, "@$(PLC_NAME) P1_HT55509.Sequencer B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ai, "CHTR:PSI5:5509:MODE") { field(DESC, "Actuator mode (man,ovr,seq)") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55509.MODE") } record(bi, "CHTR:PSI5:5509:ALM") { field(DESC, "Limit SW alarm") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55509.ER") field(ZNAM, "Ok") field(ONAM, "Alarm") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5509:IL_LATCH") { field(DESC, "Interlock latched indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55509.Interlock_Condition_L") field(ZNAM, "Ok") field(ONAM, "Latched") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CHTR:PSI5:5509:IL_RESET") { field(DESC, "Interlock Latch Reset") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Reset") field(ONAM, "Reset") field(OUT, "@$(PLC_NAME) P1_HT55509.Interlock_Condition_Reset B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CHTR:PSI5:5509:ZSH") { field(DESC, "High limit sw value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55509.ZSH") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5509:ZSL") { field(DESC, "low limit sw value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55509.ZSL") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5509:MVAL") { field(DESC, "manual mode program command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55509.mval") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CHTR:PSI5:5509:MODE_STRING") { field(DESC, "Actuator (DO) Mode String") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55509.Mode_String") } record(bi, "CHTR:PSI5:5509:SVAL") { field(DESC, "sequencer mode output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55509.sval") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CHTR:PSI5:5509:PIDTAG") { field(DESC, "P1_HT55509 PIDTAG") field(PINI, "YES") field(VAL, "P1_HT55509") } record(bi, "CHTR:PSI5:5509:SMOD") { field(DESC, "Sequencer mode indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55509.smod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } # Records added post-SRR-4 record(bi, "CHTR:PSI5:5509:OMOD") { field(DESC, "Override mode indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55509.omod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CHTR:PSI5:5509:OVERRIDE") { field(DESC, "Override Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Override") field(ONAM, "Override") field(OUT, "@$(PLC_NAME) P1_HT55509.Override B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CHTR:PSI5:5509:MAN_OUTPUT") { field(DESC, "manual mode program command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55509.Manual_output") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CHTR:PSI5:5509:ON") { field(DESC, "Open command from EPICS") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Open") field(ONAM, "Open") field(OUT, "@$(PLC_NAME) P1_HT55509.EN B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5509:OFF") { field(DESC, "Close command from EPICS") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Close") field(ONAM, "Close") field(OUT, "@$(PLC_NAME) P1_HT55509.DIS B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CHTR:PSI5:5510:MMOD") { field(DESC, "Manual Mode status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55510.mmod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bi, "CHTR:PSI5:5510:IMOD") { field(DESC, "Interlock mode") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55510.imod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CHTR:PSI5:5510:DESC") { field(DESC, "DO Actuator Description") field(DTYP, "Soft Channel") field(PINI, "YES") field(VAL, "PsiCube Heater 10") info(autosaveFields, "VAL") } record(stringin, "CHTR:PSI5:5510:TEXT1") { field(DESC, "Notes 1") field(DTYP, "Soft Channel") field(PINI, "YES") info(autosaveFields, "VAL") } record(stringin, "CHTR:PSI5:5510:TEXT2") { field(DESC, "Notes 2") field(DTYP, "Soft Channel") field(PINI, "YES") info(autosaveFields, "VAL") } record(bi, "CHTR:PSI5:5510:INTERLOCK") { field(DESC, "Interlock status") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55510.Interlock_Condition") field(ZNAM, "Ok") field(ONAM, "Interlocked") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5510:IVAL") { field(DESC, "Interlock state") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55510.ival") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5510:OUTPUT") { field(DESC, "actuatorDO output command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55510.Output") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bo, "CHTR:PSI5:5510:MANUAL") { field(DESC, "Manual Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Manual") field(ONAM, "Manual") field(OUT, "@$(PLC_NAME) P1_HT55510.Manual B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5510:SEQUENCER") { field(DESC, "SEQ Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Sequencer") field(ONAM, "Sequencer") field(OUT, "@$(PLC_NAME) P1_HT55510.Sequencer B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ai, "CHTR:PSI5:5510:MODE") { field(DESC, "Actuator mode (man,ovr,seq)") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55510.MODE") } record(bi, "CHTR:PSI5:5510:ALM") { field(DESC, "Limit SW alarm") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55510.ER") field(ZNAM, "Ok") field(ONAM, "Alarm") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5510:IL_LATCH") { field(DESC, "Interlock latched indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55510.Interlock_Condition_L") field(ZNAM, "Ok") field(ONAM, "Latched") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CHTR:PSI5:5510:IL_RESET") { field(DESC, "Interlock Latch Reset") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Reset") field(ONAM, "Reset") field(OUT, "@$(PLC_NAME) P1_HT55510.Interlock_Condition_Reset B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CHTR:PSI5:5510:ZSH") { field(DESC, "High limit sw value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55510.ZSH") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5510:ZSL") { field(DESC, "low limit sw value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55510.ZSL") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:PSI5:5510:MVAL") { field(DESC, "manual mode program command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55510.mval") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CHTR:PSI5:5510:MODE_STRING") { field(DESC, "Actuator (DO) Mode String") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55510.Mode_String") } record(bi, "CHTR:PSI5:5510:SVAL") { field(DESC, "sequencer mode output value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55510.sval") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CHTR:PSI5:5510:PIDTAG") { field(DESC, "P1_HT55510 PIDTAG") field(PINI, "YES") field(VAL, "P1_HT55510") } record(bi, "CHTR:PSI5:5510:SMOD") { field(DESC, "Sequencer mode indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55510.smod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } # Records added post-SRR-4 record(bi, "CHTR:PSI5:5510:OMOD") { field(DESC, "Override mode indicator") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55510.omod") field(ZNAM, "Inactive") field(ONAM, "Active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CHTR:PSI5:5510:OVERRIDE") { field(DESC, "Override Mode request ") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Override") field(ONAM, "Override") field(OUT, "@$(PLC_NAME) P1_HT55510.Override B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bi, "CHTR:PSI5:5510:MAN_OUTPUT") { field(DESC, "manual mode program command") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_HT55510.Manual_output") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CHTR:PSI5:5510:ON") { field(DESC, "Open command from EPICS") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Open") field(ONAM, "Open") field(OUT, "@$(PLC_NAME) P1_HT55510.EN B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(bo, "CHTR:PSI5:5510:OFF") { field(DESC, "Close command from EPICS") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Not Close") field(ONAM, "Close") field(OUT, "@$(PLC_NAME) P1_HT55510.DIS B 0") field(HIGH, "1") field(OMSL, "supervisory") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(stringin, "CXS:PSI8:6501:PIDTAG") { field(DESC, "STATUS P&IDname") field(PINI, "YES") field(VAL, "P1_XS86501") } record(bi, "CXS:PSI8:6501:STATUS") { field(DESC, "Chill #1 System #1 Status") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) P1_XS86501") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("CXS:PSI8:6501:PIDTAG",2054,2322,0,1,"CXS:PSI8:6501:PIDTAG") #! Record("CXS:PSI8:6501:STATUS",2054,2119,0,1,"CXS:PSI8:6501:STATUS") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(stringin, "CXA:PSI8:6503:PIDTAG") { field(DESC, "ALARM P&IDname") field(PINI, "YES") field(VAL, "P1_XA86503") } record(bi, "CXA:PSI8:6503:ALARM") { field(DESC, "Chill #1 System #1 Alarm") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) P1_XA86503") field(ZNAM, "no alarm") field(ONAM, "alarm") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("CXA:PSI8:6503:PIDTAG",2054,2322,0,1,"CXA:PSI8:6503:PIDTAG") #! Record("CXA:PSI8:6503:ALARM",2054,2119,0,1,"CXA:PSI8:6503:ALARM") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(stringin, "CXS:PSI4:5420:PIDTAG") { field(DESC, "STATUS P&IDname") field(PINI, "YES") field(VAL, "P1_XS45420") } record(bi, "CXS:PSI4:5420:STATUS") { field(DESC, "Liquid Ring Pump #1 Status") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) P1_XS45420") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("CXS:PSI4:5420:PIDTAG",2054,2322,0,1,"CXS:PSI4:5420:PIDTAG") #! Record("CXS:PSI4:5420:STATUS",2054,2119,0,1,"CXS:PSI4:5420:STATUS") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(stringin, "CXS:PSI4:5421:PIDTAG") { field(DESC, "STATUS P&IDname") field(PINI, "YES") field(VAL, "P1_XS45421") } record(bi, "CXS:PSI4:5421:STATUS") { field(DESC, "Booster Pump #1 Status") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) P1_XS45421") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("CXS:PSI4:5421:PIDTAG",2054,2322,0,1,"CXS:PSI4:5421:PIDTAG") #! Record("CXS:PSI4:5421:STATUS",2054,2119,0,1,"CXS:PSI4:5421:STATUS") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(stringin, "CXS:PSI4:5422:PIDTAG") { field(DESC, "STATUS P&IDname") field(PINI, "YES") field(VAL, "P1_XS45422") } record(bi, "CXS:PSI4:5422:STATUS") { field(DESC, "Seal Pump #1 Status") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) P1_XS45422") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("CXS:PSI4:5422:PIDTAG",2054,2322,0,1,"CXS:PSI4:5422:PIDTAG") #! Record("CXS:PSI4:5422:STATUS",2054,2119,0,1,"CXS:PSI4:5422:STATUS") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(stringin, "PSIQ:PSI1:3:PIDTAG") { field(DESC, "OK P&IDname") field(PINI, "YES") field(VAL, "HRS_00_00_OK") } record(bi, "PSIQ:PSI1:3:OK") { field(DESC, "SLAC System OK") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) HRS_00_00_OK") field(ZNAM, "ok") field(ONAM, "not ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("PSIQ:PSI1:3:PIDTAG",2054,2322,0,1,"PSIQ:PSI1:3:PIDTAG") #! Record("PSIQ:PSI1:3:OK",2054,2119,0,1,"PSIQ:PSI1:3:OK") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(stringin, "PSIQ:PSI1:4:PIDTAG") { field(DESC, "OK P&IDname") field(PINI, "YES") field(VAL, "HRS_AX_RC_OK") } record(bi, "PSIQ:PSI1:4:OK") { field(DESC, "SLAC Recovery Sytem OK") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) HRS_AX_RC_OK") field(ZNAM, "ok") field(ONAM, "not ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("PSIQ:PSI1:4:PIDTAG",2054,2322,0,1,"PSIQ:PSI1:4:PIDTAG") #! Record("PSIQ:PSI1:4:OK",2054,2119,0,1,"PSIQ:PSI1:4:OK") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(stringin, "PSIQ:PSI1:5:PIDTAG") { field(DESC, "OK P&IDname") field(PINI, "YES") field(VAL, "PSQ_PV_00_RUNNING") } record(bi, "PSIQ:PSI1:5:OK") { field(DESC, "Kinney System Running") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) PSQ_PV_00_RUNNING") field(ZNAM, "ok") field(ONAM, "not ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("PSIQ:PSI1:5:PIDTAG",2054,2322,0,1,"PSIQ:PSI1:5:PIDTAG") #! Record("PSIQ:PSI1:5:OK",2054,2119,0,1,"PSIQ:PSI1:5:OK") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(stringin, "PSIQ:PSI1:6:PIDTAG") { field(DESC, "OK P&IDname") field(PINI, "YES") field(VAL, "PSQ_AX_CW_OK") } record(bi, "PSIQ:PSI1:6:OK") { field(DESC, "PsiQ Chiller System OK") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) PSQ_AX_CW_OK") field(ZNAM, "ok") field(ONAM, "not ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("PSIQ:PSI1:6:PIDTAG",2054,2322,0,1,"PSIQ:PSI1:6:PIDTAG") #! Record("PSIQ:PSI1:6:OK",2054,2119,0,1,"PSIQ:PSI1:6:OK") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(stringin, "PSIQ:PSI1:P100:PIDTAG") { field(DESC, "NOMINAL P&IDname") field(PINI, "YES") field(VAL, "P100_NOMINAL") } record(bi, "PSIQ:PSI1:P100:NOMINAL") { field(DESC, "P100 Nominal Status") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) P100_NOMINAL") field(ZNAM, "not nominal") field(ONAM, "nominal") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("PSIQ:PSI1:P100:PIDTAG",2054,2322,0,1,"PSIQ:PSI1:P100:PIDTAG") #! Record("PSIQ:PSI1:P100:NOMINAL",2054,2119,0,1,"PSIQ:PSI1:P100:NOMINAL") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(stringin, "PSIQ:PSI1:P200:PIDTAG") { field(DESC, "NOMINAL P&IDname") field(PINI, "YES") field(VAL, "P200_NOMINAL") } record(bi, "PSIQ:PSI1:P200:NOMINAL") { field(DESC, "P200 Nominal Status") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) P200_NOMINAL") field(ZNAM, "not nominal") field(ONAM, "nominal") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("PSIQ:PSI1:P200:PIDTAG",2054,2322,0,1,"PSIQ:PSI1:P200:PIDTAG") #! Record("PSIQ:PSI1:P200:NOMINAL",2054,2119,0,1,"PSIQ:PSI1:P200:NOMINAL") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(stringin, "PSIQ:PSI1:P500:PIDTAG") { field(DESC, "NOMINAL P&IDname") field(PINI, "YES") field(VAL, "P500_NOMINAL") } record(bi, "PSIQ:PSI1:P500:NOMINAL") { field(DESC, "P500 Nominal Status") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) P500_NOMINAL") field(ZNAM, "not nominal") field(ONAM, "nominal") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("PSIQ:PSI1:P500:PIDTAG",2054,2322,0,1,"PSIQ:PSI1:P500:PIDTAG") #! Record("PSIQ:PSI1:P500:NOMINAL",2054,2119,0,1,"PSIQ:PSI1:P500:NOMINAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(bo, "PSIQ:PSI1:P590:TRIP_RESET") { field(DESC, "P590 Trip Reset") field(PINI, "NO") field(DTYP, "EtherIP") field(OMSL, "supervisory") field(OUT, "@$(PLC_NAME) P590_TRIP_RESET") field(ZNAM, "No Reset") field(ONAM, "Reset") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") field(ASG, "CRYO") field(HIGH, "1") field(IVOA, "Don't drive outputs") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("PSIQ:PSI1:P590:TRIP_RESET",2060,2137,0,1,"PSIQ:PSI1:P590:TRIP_RESET") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(bo, "PSIQ:PSI1:P999:TRIP_RESET") { field(DESC, "P999 Trip Reset") field(PINI, "NO") field(DTYP, "EtherIP") field(OMSL, "supervisory") field(OUT, "@$(PLC_NAME) P999_TRIP_RESET") field(ZNAM, "No Reset") field(ONAM, "Reset") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") field(ASG, "CRYO") field(HIGH, "1") field(IVOA, "Don't drive outputs") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("PSIQ:PSI1:P999:TRIP_RESET",2060,2137,0,1,"PSIQ:PSI1:P999:TRIP_RESET") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(bo, "PSIQ:PSI1:P590:ACK") { field(DESC, "P590 Operator Ack") field(PINI, "NO") field(DTYP, "EtherIP") field(OMSL, "supervisory") field(OUT, "@$(PLC_NAME) P590_OPERATOR_ACK") field(ZNAM, "No Ack") field(ONAM, "Ack") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") field(ASG, "CRYO") field(HIGH, "1") field(IVOA, "Don't drive outputs") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("PSIQ:PSI1:P590:ACK",2060,2137,0,1,"PSIQ:PSI1:P590:ACK") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(bo, "PSIQ:PSI4:5000:RESET") { field(DESC, "P1 Kinney Pump Reset") field(PINI, "NO") field(DTYP, "EtherIP") field(OMSL, "supervisory") field(OUT, "@$(PLC_NAME) P1_VP_RST") field(ZNAM, "No Reset") field(ONAM, "Reset") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") field(ASG, "CRYO") field(HIGH, "1") field(IVOA, "Don't drive outputs") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("PSIQ:PSI4:5000:RESET",2060,2137,0,1,"PSIQ:PSI4:5000:RESET") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(bo, "PSIQ:PSI1:P900:ACK") { field(DESC, "P900 Operator Ack") field(PINI, "NO") field(DTYP, "EtherIP") field(OMSL, "supervisory") field(OUT, "@$(PLC_NAME) P900_OPERATOR_ACK") field(ZNAM, "No Ack") field(ONAM, "Ack") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") field(ASG, "CRYO") field(HIGH, "1") field(IVOA, "Don't drive outputs") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("PSIQ:PSI1:P900:ACK",2060,2137,0,1,"PSIQ:PSI1:P900:ACK") record(stringin, "PSIQ:PSI1:P590:TRIP_STR") { field(DESC, "P590 Trip String") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P590_SD_STRING") } record(stringin, "PSIQ:PSI1:P999:TRIP_STR") { field(DESC, "P999 Trip String") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P999_SD_STRING") } # NEW common attenuator file (post SRR-$) # on/off commands are separate, using common/on_off_confirm.vdb # alarms and trips are still listed in 4kcb_alarms.substitutions record(bi, "CPV:PSI5:5201:ATT_SLOPE") { field(DESC, "Attenuator slope") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_PV55201_ATT.slope") field(ZNAM, "Negative") field(ONAM, "Positive") } record(bo, "CPV:PSI5:5201:ATT_DISABLE") { field(DESC, "Attenuator disable") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Enable") field(ONAM, "Disable") field(OUT, "@$(PLC_NAME) P1_PV55201_ATT.disable") field(ASG, "CRYO") } record(ai, "CPV:PSI5:5201:ATT_PV") { field(DESC, "Attenuator PV Value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_PV55201_ATT.PV") field(PREC, "2") field(ADEL, "0.01") } record(ai, "CPV:PSI5:5201:ATT_ATMIN") { field(DESC, "Attn Min Y axis") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_PV55201_ATT.ATmin") field(PREC, "2") field(ADEL, "0.01") } record(ai, "CPV:PSI5:5201:ATT_ATMAX") { field(DESC, "Attn Max Y axis") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_PV55201_ATT.ATmax") field(PREC, "2") field(ADEL, "0.01") } record(ai, "CPV:PSI5:5201:ATT_OUT") { field(DESC, "Attenuation Value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_PV55201_ATT.Output") field(PREC, "2") field(ADEL, "0.01") } record(ao, "CPV:PSI5:5201:ATT_Y1") { field(DESC, "4kcb Dewar Level Attn Y Min") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) P1_PV55201_ATT.Y1") field(PREC, "2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPV:PSI5:5201:ATT_Y2") { field(DESC, "4kcb Dewar Level Attn Y Max") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) P1_PV55201_ATT.Y2") field(PREC, "2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPV:PSI5:5201:ATT_X1") { field(DESC, "4kcb Dewar Level Attn X Min") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) P1_PV55201_ATT.X1") field(PREC, "2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPV:PSI5:5201:ATT_X2") { field(DESC, "4kcb Dewar Level Attn X Max") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) P1_PV55201_ATT.X2") field(PREC, "2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } # # End of file # # NEW common attenuator file (post SRR-$) # on/off commands are separate, using common/on_off_confirm.vdb # alarms and trips are still listed in 4kcb_alarms.substitutions record(bi, "CPV:PSI5:5206:ATT_SLOPE") { field(DESC, "Attenuator slope") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_PV55206_ATT.slope") field(ZNAM, "Negative") field(ONAM, "Positive") } record(bo, "CPV:PSI5:5206:ATT_DISABLE") { field(DESC, "Attenuator disable") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Enable") field(ONAM, "Disable") field(OUT, "@$(PLC_NAME) P1_PV55206_ATT.disable") field(ASG, "CRYO") } record(ai, "CPV:PSI5:5206:ATT_PV") { field(DESC, "Attenuator PV Value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_PV55206_ATT.PV") field(PREC, "2") field(ADEL, "0.01") } record(ai, "CPV:PSI5:5206:ATT_ATMIN") { field(DESC, "Attn Min Y axis") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_PV55206_ATT.ATmin") field(PREC, "2") field(ADEL, "0.01") } record(ai, "CPV:PSI5:5206:ATT_ATMAX") { field(DESC, "Attn Max Y axis") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_PV55206_ATT.ATmax") field(PREC, "2") field(ADEL, "0.01") } record(ai, "CPV:PSI5:5206:ATT_OUT") { field(DESC, "Attenuation Value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_PV55206_ATT.Output") field(PREC, "2") field(ADEL, "0.01") } record(ao, "CPV:PSI5:5206:ATT_Y1") { field(DESC, "Cooldown DT Attn Y Min") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) P1_PV55206_ATT.Y1") field(PREC, "2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPV:PSI5:5206:ATT_Y2") { field(DESC, "Cooldown DT Attn Y Max") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) P1_PV55206_ATT.Y2") field(PREC, "2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPV:PSI5:5206:ATT_X1") { field(DESC, "Cooldown DT Attn X Min") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) P1_PV55206_ATT.X1") field(PREC, "2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPV:PSI5:5206:ATT_X2") { field(DESC, "Cooldown DT Attn X Max") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) P1_PV55206_ATT.X2") field(PREC, "2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } # # End of file # # NEW common attenuator file (post SRR-$) # on/off commands are separate, using common/on_off_confirm.vdb # alarms and trips are still listed in 4kcb_alarms.substitutions record(bi, "CPV:PSI5:5302:ATT_SLOPE") { field(DESC, "Attenuator slope") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_PV55302_ATT.slope") field(ZNAM, "Negative") field(ONAM, "Positive") } record(bo, "CPV:PSI5:5302:ATT_DISABLE") { field(DESC, "Attenuator disable") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Enable") field(ONAM, "Disable") field(OUT, "@$(PLC_NAME) P1_PV55302_ATT.disable") field(ASG, "CRYO") } record(ai, "CPV:PSI5:5302:ATT_PV") { field(DESC, "Attenuator PV Value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_PV55302_ATT.PV") field(PREC, "2") field(ADEL, "0.01") } record(ai, "CPV:PSI5:5302:ATT_ATMIN") { field(DESC, "Attn Min Y axis") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_PV55302_ATT.ATmin") field(PREC, "2") field(ADEL, "0.01") } record(ai, "CPV:PSI5:5302:ATT_ATMAX") { field(DESC, "Attn Max Y axis") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_PV55302_ATT.ATmax") field(PREC, "2") field(ADEL, "0.01") } record(ai, "CPV:PSI5:5302:ATT_OUT") { field(DESC, "Attenuation Value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_PV55302_ATT.Output") field(PREC, "2") field(ADEL, "0.01") } record(ao, "CPV:PSI5:5302:ATT_Y1") { field(DESC, "PSI Blade Press. Attn Y Min") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) P1_PV55302_ATT.Y1") field(PREC, "2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPV:PSI5:5302:ATT_Y2") { field(DESC, "PSI Blade Press. Attn Y Max") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) P1_PV55302_ATT.Y2") field(PREC, "2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPV:PSI5:5302:ATT_X1") { field(DESC, "PSI Blade Press. Attn X Min") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) P1_PV55302_ATT.X1") field(PREC, "2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPV:PSI5:5302:ATT_X2") { field(DESC, "PSI Blade Press. Attn X Max") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) P1_PV55302_ATT.X2") field(PREC, "2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } # # End of file # # NEW common attenuator file (post SRR-$) # on/off commands are separate, using common/on_off_confirm.vdb # alarms and trips are still listed in 4kcb_alarms.substitutions record(bi, "CPV:PSI8:8523:ATT_SLOPE") { field(DESC, "Attenuator slope") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_PV88523_ATT.slope") field(ZNAM, "Negative") field(ONAM, "Positive") } record(bo, "CPV:PSI8:8523:ATT_DISABLE") { field(DESC, "Attenuator disable") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Enable") field(ONAM, "Disable") field(OUT, "@$(PLC_NAME) P1_PV88523_ATT.disable") field(ASG, "CRYO") } record(ai, "CPV:PSI8:8523:ATT_PV") { field(DESC, "Attenuator PV Value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_PV88523_ATT.PV") field(PREC, "2") field(ADEL, "0.01") } record(ai, "CPV:PSI8:8523:ATT_ATMIN") { field(DESC, "Attn Min Y axis") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_PV88523_ATT.ATmin") field(PREC, "2") field(ADEL, "0.01") } record(ai, "CPV:PSI8:8523:ATT_ATMAX") { field(DESC, "Attn Max Y axis") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_PV88523_ATT.ATmax") field(PREC, "2") field(ADEL, "0.01") } record(ai, "CPV:PSI8:8523:ATT_OUT") { field(DESC, "Attenuation Value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_PV88523_ATT.Output") field(PREC, "2") field(ADEL, "0.01") } record(ao, "CPV:PSI8:8523:ATT_Y1") { field(DESC, "Cooldown DT Attn Y Min") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) P1_PV88523_ATT.Y1") field(PREC, "2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPV:PSI8:8523:ATT_Y2") { field(DESC, "Cooldown DT Attn Y Max") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) P1_PV88523_ATT.Y2") field(PREC, "2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPV:PSI8:8523:ATT_X1") { field(DESC, "Cooldown DT Attn X Min") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) P1_PV88523_ATT.X1") field(PREC, "2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPV:PSI8:8523:ATT_X2") { field(DESC, "Cooldown DT Attn X Max") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) P1_PV88523_ATT.X2") field(PREC, "2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } # # End of file # # NEW common attenuator file (post SRR-$) # on/off commands are separate, using common/on_off_confirm.vdb # alarms and trips are still listed in 4kcb_alarms.substitutions record(bi, "CPV:PSI8:8531:ATT_SLOPE") { field(DESC, "Attenuator slope") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_PV88531_ATT.slope") field(ZNAM, "Negative") field(ONAM, "Positive") } record(bo, "CPV:PSI8:8531:ATT_DISABLE") { field(DESC, "Attenuator disable") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Enable") field(ONAM, "Disable") field(OUT, "@$(PLC_NAME) P1_PV88531_ATT.disable") field(ASG, "CRYO") } record(ai, "CPV:PSI8:8531:ATT_PV") { field(DESC, "Attenuator PV Value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_PV88531_ATT.PV") field(PREC, "2") field(ADEL, "0.01") } record(ai, "CPV:PSI8:8531:ATT_ATMIN") { field(DESC, "Attn Min Y axis") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_PV88531_ATT.ATmin") field(PREC, "2") field(ADEL, "0.01") } record(ai, "CPV:PSI8:8531:ATT_ATMAX") { field(DESC, "Attn Max Y axis") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_PV88531_ATT.ATmax") field(PREC, "2") field(ADEL, "0.01") } record(ai, "CPV:PSI8:8531:ATT_OUT") { field(DESC, "Attenuation Value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) P1_PV88531_ATT.Output") field(PREC, "2") field(ADEL, "0.01") } record(ao, "CPV:PSI8:8531:ATT_Y1") { field(DESC, "Cooldown DT Attn Y Min") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) P1_PV88531_ATT.Y1") field(PREC, "2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPV:PSI8:8531:ATT_Y2") { field(DESC, "Cooldown DT Attn Y Max") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) P1_PV88531_ATT.Y2") field(PREC, "2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPV:PSI8:8531:ATT_X1") { field(DESC, "Cooldown DT Attn X Min") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) P1_PV88531_ATT.X1") field(PREC, "2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPV:PSI8:8531:ATT_X2") { field(DESC, "Cooldown DT Attn X Max") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) P1_PV88531_ATT.X2") field(PREC, "2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } # # End of file # # NEW common attenuator file (post SRR-$) # on/off commands are separate, using common/on_off_confirm.vdb # alarms and trips are still listed in 4kcb_alarms.substitutions record(bi, "CPV:PSI4:CD_TE:ATT_SLOPE") { field(DESC, "Attenuator slope") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) CD_TE_ATT.slope") field(ZNAM, "Negative") field(ONAM, "Positive") } record(bo, "CPV:PSI4:CD_TE:ATT_DISABLE") { field(DESC, "Attenuator disable") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Enable") field(ONAM, "Disable") field(OUT, "@$(PLC_NAME) CD_TE_ATT.disable") field(ASG, "CRYO") } record(ai, "CPV:PSI4:CD_TE:ATT_PV") { field(DESC, "Attenuator PV Value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) CD_TE_ATT.PV") field(PREC, "2") field(ADEL, "0.01") } record(ai, "CPV:PSI4:CD_TE:ATT_ATMIN") { field(DESC, "Attn Min Y axis") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) CD_TE_ATT.ATmin") field(PREC, "2") field(ADEL, "0.01") } record(ai, "CPV:PSI4:CD_TE:ATT_ATMAX") { field(DESC, "Attn Max Y axis") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) CD_TE_ATT.ATmax") field(PREC, "2") field(ADEL, "0.01") } record(ai, "CPV:PSI4:CD_TE:ATT_OUT") { field(DESC, "Attenuation Value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) CD_TE_ATT.Output") field(PREC, "2") field(ADEL, "0.01") } record(ao, "CPV:PSI4:CD_TE:ATT_Y1") { field(DESC, "Cooldown Temp. Attn Y Min") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) CD_TE_ATT.Y1") field(PREC, "2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPV:PSI4:CD_TE:ATT_Y2") { field(DESC, "Cooldown Temp. Attn Y Max") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) CD_TE_ATT.Y2") field(PREC, "2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPV:PSI4:CD_TE:ATT_X1") { field(DESC, "Cooldown Temp. Attn X Min") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) CD_TE_ATT.X1") field(PREC, "2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPV:PSI4:CD_TE:ATT_X2") { field(DESC, "Cooldown Temp. Attn X Max") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) CD_TE_ATT.X2") field(PREC, "2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } # # End of file # # NEW common attenuator file (post SRR-$) # on/off commands are separate, using common/on_off_confirm.vdb # alarms and trips are still listed in 4kcb_alarms.substitutions record(bi, "CPV:PSI4:HE_PT:ATT_SLOPE") { field(DESC, "Attenuator slope") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) HE_PT_ATT.slope") field(ZNAM, "Negative") field(ONAM, "Positive") } record(bo, "CPV:PSI4:HE_PT:ATT_DISABLE") { field(DESC, "Attenuator disable") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Enable") field(ONAM, "Disable") field(OUT, "@$(PLC_NAME) HE_PT_ATT.disable") field(ASG, "CRYO") } record(ai, "CPV:PSI4:HE_PT:ATT_PV") { field(DESC, "Attenuator PV Value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) HE_PT_ATT.PV") field(PREC, "2") field(ADEL, "0.01") } record(ai, "CPV:PSI4:HE_PT:ATT_ATMIN") { field(DESC, "Attn Min Y axis") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) HE_PT_ATT.ATmin") field(PREC, "2") field(ADEL, "0.01") } record(ai, "CPV:PSI4:HE_PT:ATT_ATMAX") { field(DESC, "Attn Max Y axis") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) HE_PT_ATT.ATmax") field(PREC, "2") field(ADEL, "0.01") } record(ai, "CPV:PSI4:HE_PT:ATT_OUT") { field(DESC, "Attenuation Value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) HE_PT_ATT.Output") field(PREC, "2") field(ADEL, "0.01") } record(ao, "CPV:PSI4:HE_PT:ATT_Y1") { field(DESC, "Cooldown Press. Attn Y Min") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) HE_PT_ATT.Y1") field(PREC, "2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPV:PSI4:HE_PT:ATT_Y2") { field(DESC, "Cooldown Press. Attn Y Max") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) HE_PT_ATT.Y2") field(PREC, "2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPV:PSI4:HE_PT:ATT_X1") { field(DESC, "Cooldown Press. Attn X Min") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) HE_PT_ATT.X1") field(PREC, "2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPV:PSI4:HE_PT:ATT_X2") { field(DESC, "Cooldown Press. Attn X Max") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) HE_PT_ATT.X2") field(PREC, "2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } # # End of file # # NEW common attenuator file (post SRR-$) # on/off commands are separate, using common/on_off_confirm.vdb # alarms and trips are still listed in 4kcb_alarms.substitutions record(bi, "CPV:PSI4:HRS_RC:ATT_SLOPE") { field(DESC, "Attenuator slope") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) HRS_RC_ATT.slope") field(ZNAM, "Negative") field(ONAM, "Positive") } record(bo, "CPV:PSI4:HRS_RC:ATT_DISABLE") { field(DESC, "Attenuator disable") field(DTYP, "EtherIP") field(PINI, "NO") field(ZNAM, "Enable") field(ONAM, "Disable") field(OUT, "@$(PLC_NAME) HRS_RC_ATT.disable") field(ASG, "CRYO") } record(ai, "CPV:PSI4:HRS_RC:ATT_PV") { field(DESC, "Attenuator PV Value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) HRS_RC_ATT.PV") field(PREC, "2") field(ADEL, "0.01") } record(ai, "CPV:PSI4:HRS_RC:ATT_ATMIN") { field(DESC, "Attn Min Y axis") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) HRS_RC_ATT.ATmin") field(PREC, "2") field(ADEL, "0.01") } record(ai, "CPV:PSI4:HRS_RC:ATT_ATMAX") { field(DESC, "Attn Max Y axis") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) HRS_RC_ATT.ATmax") field(PREC, "2") field(ADEL, "0.01") } record(ai, "CPV:PSI4:HRS_RC:ATT_OUT") { field(DESC, "Attenuation Value") field(DTYP, "EtherIP") field(SCAN, "1 second") field(PINI, "YES") field(INP, "@$(PLC_NAME) HRS_RC_ATT.Output") field(PREC, "2") field(ADEL, "0.01") } record(ao, "CPV:PSI4:HRS_RC:ATT_Y1") { field(DESC, "Cooldown RC Flow Attn Y Min") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) HRS_RC_ATT.Y1") field(PREC, "2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPV:PSI4:HRS_RC:ATT_Y2") { field(DESC, "Cooldown RC Flow Attn Y Max") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) HRS_RC_ATT.Y2") field(PREC, "2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPV:PSI4:HRS_RC:ATT_X1") { field(DESC, "Cooldown RC Flow Attn X Min") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) HRS_RC_ATT.X1") field(PREC, "2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } record(ao, "CPV:PSI4:HRS_RC:ATT_X2") { field(DESC, "Cooldown RC Flow Attn X Max") field(DTYP, "EtherIP") field(PINI, "NO") field(OUT, "@$(PLC_NAME) HRS_RC_ATT.X2") field(PREC, "2") field(IVOA, "Don't drive outputs") field(ASG, "CRYO") } # # End of file # #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBD("../../dbd/cryoTest.dbd") #! DBDEND record(ao, "PSIQ:PSI1:0:CD_RATE") { field(DESC, "Cooldown Rate") field(ASG, "CRYO") field(PINI, "NO") field(DTYP, "EtherIP") field(PREC, "2") field(EGU, "k/hr") field(ADEL, "0") field(IVOA, "Don't drive outputs") field(OUT, "@$(PLC_NAME) PSQ_CD_RATE") } record(stringin, "PSIQ:PSI1:0:PIDTAG") { field(DESC, "CD_RATE PIDtag") field(PINI, "YES") field(VAL, "PSQ_CD_RATE") } #! Further lines contain data used by VisualDCT #! View(1774,1984,1.0) #! Record("PSIQ:PSI1:0:CD_RATE",2060,2119,0,1,"PSIQ:PSI1:0:CD_RATE") #! Record("PSIQ:PSI1:0:PIDTAG",2340,2142,0,1,"PSIQ:PSI1:0:PIDTAG") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBD("../../dbd/cryoTest.dbd") #! DBDEND record(ao, "PSIQ:PSI1:0:LANDING") { field(DESC, "Pumpdown Landing") field(ASG, "CRYO") field(PINI, "NO") field(DTYP, "EtherIP") field(PREC, "2") field(EGU, "mbar") field(ADEL, "0") field(IVOA, "Don't drive outputs") field(OUT, "@$(PLC_NAME) PSQ_Landing_Pr") } record(stringin, "PSIQ:PSI1:0:PIDTAG") { field(DESC, "LANDING PIDtag") field(PINI, "YES") field(VAL, "PSQ_Landing_Pr") } #! Further lines contain data used by VisualDCT #! View(1774,1984,1.0) #! Record("PSIQ:PSI1:0:LANDING",2060,2119,0,1,"PSIQ:PSI1:0:LANDING") #! Record("PSIQ:PSI1:0:PIDTAG",2340,2142,0,1,"PSIQ:PSI1:0:PIDTAG")