#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "WCMP:CP$(CP)2:1$(C):ORDER_ON") {
  field(DESC, "WCMP order on")
  field(ZNAM, "not ordered on")
  field(ONAM, "ordered on")
  field(OMSL, "supervisory")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "WCMP:CP$(CP)2:1$(C):ON_CNCL") {
  field(DESC, "WCMP Cancel ON order")
  field(ZNAM, "not cancelled")
  field(ONAM, "cancelled")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "WCMP:CP$(CP)2:1$(C):ORDER_OFF") {
  field(DESC, "WCMP order off")
  field(ZNAM, "not order off")
  field(ONAM, "order off")
  field(OMSL, "supervisory")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "WCMP:CP$(CP)2:1$(C):OFF_CNCL") {
  field(DESC, "WCMP Cancel OFF order")
  field(ZNAM, "not cancelled")
  field(ONAM, "cancelled")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "WCMP:CP$(CP)2:1$(C):ON_CFRM") {
  field(DESC, "WCMP confirm ON order")
  field(ZNAM, "not confirmed")
  field(ONAM, "confirmed")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
  field(OMSL, "supervisory")
}

record(bo, "WCMP:CP$(CP)2:1$(C):OFF_CFRM") {
  field(DESC, "WCMP confirm OFF order")
  field(ZNAM, "not confirmed")
  field(ONAM, "confirmed")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "WCMP:CP$(CP)2:1$(C):RQST_ON") {
  field(DESC, "WCMP Rqst On")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) Comp_Start_Requested_X B 0")
  field(ZNAM, "not active")
  field(ONAM, "Active")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(ASG, "NOWRITE")
  field(HIGH, "0")
  field(OMSL, "supervisory")
}

record(bo, "WCMP:CP$(CP)2:1$(C):RQST_OFF") {
  field(DESC, "WCMP Rqst Off")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) Normal_Shutdown_X B 0")
  field(ZNAM, "not active")
  field(ONAM, "Active")
  field(ASG, "NOWRITE")
  field(PINI, "NO")
  field(HIGH, "0")
  field(SCAN, "1 second")
  field(OMSL, "supervisory")
}

record(sub, "WCMP:CP$(CP)2:1$(C):ORDER_ONL") {
  field(DESC, "WCMP")
  field(SCAN, ".5 second")
  field(PINI, "NO")
  field(FLNK, "WCMP:CP$(CP)2:1$(C):ORDER_ONT")
  field(INAM, "Icclmom")
  field(SNAM, "Scclmom")
  field(INPA, "WCMP:CP$(CP)2:1$(C):ORDER_ON")
  field(INPB, "WCMP:CP$(CP)2:1$(C):ON_CFRM")
  field(INPC, "WCMP:CP$(CP)2:1$(C):ON_CNCL")
  field(ASG, "NOWRITE")
}

record(bo, "WCMP:CP$(CP)2:1$(C):ORDER_ONT") {
  field(DESC, "WCMP")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "closed_loop")
  field(DOL, "WCMP:CP$(CP)2:1$(C):ORDER_ONL")
  field(OUT, "WCMP:CP$(CP)2:1$(C):RQST_ON")
  field(ZSV, "MAJOR")
  field(ASG, "NOWRITE")
  field(ZNAM, "disabled")
  field(ONAM, "enabled")
  field(OSV, "NO_ALARM")
  field(COSV, "NO_ALARM")
}

record(sub, "WCMP:CP$(CP)2:1$(C):ORDER_OFFL") {
  field(DESC, "WCMP")
  field(SCAN, ".5 second")
  field(PINI, "NO")
  field(FLNK, "WCMP:CP$(CP)2:1$(C):ORDER_OFFT")
  field(INAM, "Icclmom")
  field(SNAM, "Scclmom")
  field(INPA, "WCMP:CP$(CP)2:1$(C):ORDER_OFF")
  field(INPB, "WCMP:CP$(CP)2:1$(C):OFF_CFRM")
  field(INPC, "WCMP:CP$(CP)2:1$(C):OFF_CNCL")
  field(ASG, "NOWRITE")
}

record(bo, "WCMP:CP$(CP)2:1$(C):ORDER_OFFT") {
  field(DESC, "WCMP")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(OMSL, "closed_loop")
  field(DOL, "WCMP:CP$(CP)2:1$(C):ORDER_OFFL")
  field(OUT, "WCMP:CP$(CP)2:1$(C):RQST_OFF")
  field(ZSV, "MAJOR")
  field(ASG, "NOWRITE")
  field(ZNAM, "disabled")
  field(ONAM, "enabled")
  field(OSV, "NO_ALARM")
  field(COSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,416,1.1)
#! Record("WCMP:CP$(CP)2:1$(C):ORDER_ON",80,378,0,1,"WCMP:CP$(CP)2:1$(C):ORDER_ON")
#! Field("WCMP:CP$(CP)2:1$(C):ORDER_ON.VAL",16777215,1,"WCMP:CP$(CP)2:1$(C):ORDER_ON.VAL")
#! Record("WCMP:CP$(CP)2:1$(C):ON_CNCL",80,798,0,1,"WCMP:CP$(CP)2:1$(C):ON_CNCL")
#! Field("WCMP:CP$(CP)2:1$(C):ON_CNCL.VAL",16777215,1,"WCMP:CP$(CP)2:1$(C):ON_CNCL.VAL")
#! Record("WCMP:CP$(CP)2:1$(C):ORDER_OFF",80,1018,0,1,"WCMP:CP$(CP)2:1$(C):ORDER_OFF")
#! Field("WCMP:CP$(CP)2:1$(C):ORDER_OFF.VAL",16777215,1,"WCMP:CP$(CP)2:1$(C):ORDER_OFF.VAL")
#! Record("WCMP:CP$(CP)2:1$(C):OFF_CNCL",80,1458,0,1,"WCMP:CP$(CP)2:1$(C):OFF_CNCL")
#! Field("WCMP:CP$(CP)2:1$(C):OFF_CNCL.VAL",16777215,1,"WCMP:CP$(CP)2:1$(C):OFF_CNCL.VAL")
#! Record("WCMP:CP$(CP)2:1$(C):ON_CFRM",80,578,0,1,"WCMP:CP$(CP)2:1$(C):ON_CFRM")
#! Field("WCMP:CP$(CP)2:1$(C):ON_CFRM.VAL",16777215,1,"WCMP:CP$(CP)2:1$(C):ON_CFRM.VAL")
#! Record("WCMP:CP$(CP)2:1$(C):OFF_CFRM",80,1238,0,1,"WCMP:CP$(CP)2:1$(C):OFF_CFRM")
#! Field("WCMP:CP$(CP)2:1$(C):OFF_CFRM.VAL",16777215,1,"WCMP:CP$(CP)2:1$(C):OFF_CFRM.VAL")
#! Record("WCMP:CP$(CP)2:1$(C):RQST_ON",960,584,0,1,"WCMP:CP$(CP)2:1$(C):RQST_ON")
#! Field("WCMP:CP$(CP)2:1$(C):RQST_ON.VAL",16777215,1,"WCMP:CP$(CP)2:1$(C):RQST_ON.VAL")
#! Record("WCMP:CP$(CP)2:1$(C):RQST_OFF",960,1204,0,1,"WCMP:CP$(CP)2:1$(C):RQST_OFF")
#! Field("WCMP:CP$(CP)2:1$(C):RQST_OFF.VAL",16777215,1,"WCMP:CP$(CP)2:1$(C):RQST_OFF.VAL")
#! Record("WCMP:CP$(CP)2:1$(C):ORDER_ONL",400,524,0,1,"WCMP:CP$(CP)2:1$(C):ORDER_ONL")
#! Field("WCMP:CP$(CP)2:1$(C):ORDER_ONL.FLNK",16777215,1,"WCMP:CP$(CP)2:1$(C):ORDER_ONL.FLNK")
#! Link("WCMP:CP$(CP)2:1$(C):ORDER_ONL.FLNK","WCMP:CP$(CP)2:1$(C):ORDER_ONT")
#! Field("WCMP:CP$(CP)2:1$(C):ORDER_ONL.INPA",16777215,0,"WCMP:CP$(CP)2:1$(C):ORDER_ONL.INPA")
#! Link("WCMP:CP$(CP)2:1$(C):ORDER_ONL.INPA","WCMP:CP$(CP)2:1$(C):ORDER_ON.VAL")
#! Field("WCMP:CP$(CP)2:1$(C):ORDER_ONL.INPB",16777215,0,"WCMP:CP$(CP)2:1$(C):ORDER_ONL.INPB")
#! Link("WCMP:CP$(CP)2:1$(C):ORDER_ONL.INPB","WCMP:CP$(CP)2:1$(C):ON_CFRM.VAL")
#! Field("WCMP:CP$(CP)2:1$(C):ORDER_ONL.INPC",16777215,0,"WCMP:CP$(CP)2:1$(C):ORDER_ONL.INPC")
#! Link("WCMP:CP$(CP)2:1$(C):ORDER_ONL.INPC","WCMP:CP$(CP)2:1$(C):ON_CNCL.VAL")
#! Field("WCMP:CP$(CP)2:1$(C):ORDER_ONL.VAL",16777215,1,"WCMP:CP$(CP)2:1$(C):ORDER_ONL.VAL")
#! Record("WCMP:CP$(CP)2:1$(C):ORDER_ONT",700,522,0,0,"WCMP:CP$(CP)2:1$(C):ORDER_ONT")
#! Field("WCMP:CP$(CP)2:1$(C):ORDER_ONT.DOL",16777215,0,"WCMP:CP$(CP)2:1$(C):ORDER_ONT.DOL")
#! Link("WCMP:CP$(CP)2:1$(C):ORDER_ONT.DOL","WCMP:CP$(CP)2:1$(C):ORDER_ONL.VAL")
#! Field("WCMP:CP$(CP)2:1$(C):ORDER_ONT.OUT",16777215,1,"WCMP:CP$(CP)2:1$(C):ORDER_ONT.OUT")
#! Link("WCMP:CP$(CP)2:1$(C):ORDER_ONT.OUT","WCMP:CP$(CP)2:1$(C):RQST_ON.VAL")
#! Record("WCMP:CP$(CP)2:1$(C):ORDER_OFFL",400,1124,0,1,"WCMP:CP$(CP)2:1$(C):ORDER_OFFL")
#! Field("WCMP:CP$(CP)2:1$(C):ORDER_OFFL.FLNK",16777215,1,"WCMP:CP$(CP)2:1$(C):ORDER_OFFL.FLNK")
#! Link("WCMP:CP$(CP)2:1$(C):ORDER_OFFL.FLNK","WCMP:CP$(CP)2:1$(C):ORDER_OFFT")
#! Field("WCMP:CP$(CP)2:1$(C):ORDER_OFFL.INPA",16777215,0,"WCMP:CP$(CP)2:1$(C):ORDER_OFFL.INPA")
#! Link("WCMP:CP$(CP)2:1$(C):ORDER_OFFL.INPA","WCMP:CP$(CP)2:1$(C):ORDER_OFF.VAL")
#! Field("WCMP:CP$(CP)2:1$(C):ORDER_OFFL.INPC",16777215,0,"WCMP:CP$(CP)2:1$(C):ORDER_OFFL.INPC")
#! Link("WCMP:CP$(CP)2:1$(C):ORDER_OFFL.INPC","WCMP:CP$(CP)2:1$(C):OFF_CNCL.VAL")
#! Field("WCMP:CP$(CP)2:1$(C):ORDER_OFFL.INPB",16777215,0,"WCMP:CP$(CP)2:1$(C):ORDER_OFFL.INPB")
#! Link("WCMP:CP$(CP)2:1$(C):ORDER_OFFL.INPB","WCMP:CP$(CP)2:1$(C):OFF_CFRM.VAL")
#! Field("WCMP:CP$(CP)2:1$(C):ORDER_OFFL.VAL",16777215,1,"WCMP:CP$(CP)2:1$(C):ORDER_OFFL.VAL")
#! Record("WCMP:CP$(CP)2:1$(C):ORDER_OFFT",700,1156,0,0,"WCMP:CP$(CP)2:1$(C):ORDER_OFFT")
#! Field("WCMP:CP$(CP)2:1$(C):ORDER_OFFT.DOL",16777215,0,"WCMP:CP$(CP)2:1$(C):ORDER_OFFT.DOL")
#! Link("WCMP:CP$(CP)2:1$(C):ORDER_OFFT.DOL","WCMP:CP$(CP)2:1$(C):ORDER_OFFL.VAL")
#! Field("WCMP:CP$(CP)2:1$(C):ORDER_OFFT.OUT",16777215,1,"WCMP:CP$(CP)2:1$(C):ORDER_OFFT.OUT")
#! Link("WCMP:CP$(CP)2:1$(C):ORDER_OFFT.OUT","WCMP:CP$(CP)2:1$(C):RQST_OFF.VAL")
#! TextBox(TB1,480,360,780,400,0,"Dialog",12,1,16777215,"Turn On and confirm logic\nTurn Off and confirm logic\n",null)
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CPMP:CP$(CP)2:1$(C):ORDER_ON") {
  field(DESC, "CPMP order on")
  field(ZNAM, "not ordered on")
  field(ONAM, "ordered on")
  field(OMSL, "supervisory")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CPMP:CP$(CP)2:1$(C):ON_CNCL") {
  field(DESC, "CPMP Cancel ON order")
  field(ZNAM, "not cancelled")
  field(ONAM, "cancelled")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CPMP:CP$(CP)2:1$(C):ORDER_OFF") {
  field(DESC, "CPMP order off")
  field(ZNAM, "not order off")
  field(ONAM, "order off")
  field(OMSL, "supervisory")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CPMP:CP$(CP)2:1$(C):OFF_CNCL") {
  field(DESC, "CPMP Cancel OFF order")
  field(ZNAM, "not cancelled")
  field(ONAM, "cancelled")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CPMP:CP$(CP)2:1$(C):ON_CFRM") {
  field(DESC, "CPMP confirm ON order")
  field(ZNAM, "not confirmed")
  field(ONAM, "confirmed")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
  field(OMSL, "supervisory")
}

record(bo, "CPMP:CP$(CP)2:1$(C):OFF_CFRM") {
  field(DESC, "CPMP confirm OFF order")
  field(ZNAM, "not confirmed")
  field(ONAM, "confirmed")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CPMP:CP$(CP)2:1$(C):RQST_ON") {
  field(DESC, "CPMP Rqst On")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) Start_Pump_Request B 0")
  field(ZNAM, "not active")
  field(ONAM, "Active")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(ASG, "NOWRITE")
  field(HIGH, "0")
  field(OMSL, "supervisory")
}

record(bo, "CPMP:CP$(CP)2:1$(C):RQST_OFF") {
  field(DESC, "CPMP Rqst Off")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) Stop_Pump_Request B 0")
  field(ZNAM, "not active")
  field(ONAM, "Active")
  field(ASG, "NOWRITE")
  field(PINI, "NO")
  field(HIGH, "0")
  field(SCAN, "1 second")
  field(OMSL, "supervisory")
}

record(sub, "CPMP:CP$(CP)2:1$(C):ORDER_ONL") {
  field(DESC, "CPMP")
  field(SCAN, ".5 second")
  field(PINI, "NO")
  field(FLNK, "CPMP:CP$(CP)2:1$(C):ORDER_ONT")
  field(INAM, "Icclmom")
  field(SNAM, "Scclmom")
  field(INPA, "CPMP:CP$(CP)2:1$(C):ORDER_ON")
  field(INPB, "CPMP:CP$(CP)2:1$(C):ON_CFRM")
  field(INPC, "CPMP:CP$(CP)2:1$(C):ON_CNCL")
  field(ASG, "NOWRITE")
}

record(bo, "CPMP:CP$(CP)2:1$(C):ORDER_ONT") {
  field(DESC, "CPMP")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "closed_loop")
  field(DOL, "CPMP:CP$(CP)2:1$(C):ORDER_ONL")
  field(OUT, "CPMP:CP$(CP)2:1$(C):RQST_ON")
  field(ZSV, "MAJOR")
  field(ASG, "NOWRITE")
  field(ZNAM, "disabled")
  field(ONAM, "enabled")
  field(OSV, "NO_ALARM")
  field(COSV, "NO_ALARM")
}

record(sub, "CPMP:CP$(CP)2:1$(C):ORDER_OFFL") {
  field(DESC, "CPMP")
  field(SCAN, ".5 second")
  field(PINI, "NO")
  field(FLNK, "CPMP:CP$(CP)2:1$(C):ORDER_OFFT")
  field(INAM, "Icclmom")
  field(SNAM, "Scclmom")
  field(INPA, "CPMP:CP$(CP)2:1$(C):ORDER_OFF")
  field(INPB, "CPMP:CP$(CP)2:1$(C):OFF_CFRM")
  field(INPC, "CPMP:CP$(CP)2:1$(C):OFF_CNCL")
  field(ASG, "NOWRITE")
}

record(bo, "CPMP:CP$(CP)2:1$(C):ORDER_OFFT") {
  field(DESC, "CPMP")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(OMSL, "closed_loop")
  field(DOL, "CPMP:CP$(CP)2:1$(C):ORDER_OFFL")
  field(OUT, "CPMP:CP$(CP)2:1$(C):RQST_OFF")
  field(ZSV, "MAJOR")
  field(ASG, "NOWRITE")
  field(ZNAM, "disabled")
  field(ONAM, "enabled")
  field(OSV, "NO_ALARM")
  field(COSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,416,1.1)
#! Record("CPMP:CP$(CP)2:1$(C):ORDER_ON",80,378,0,1,"CPMP:CP$(CP)2:1$(C):ORDER_ON")
#! Field("CPMP:CP$(CP)2:1$(C):ORDER_ON.VAL",16777215,1,"CPMP:CP$(CP)2:1$(C):ORDER_ON.VAL")
#! Record("CPMP:CP$(CP)2:1$(C):ON_CNCL",80,798,0,1,"CPMP:CP$(CP)2:1$(C):ON_CNCL")
#! Field("CPMP:CP$(CP)2:1$(C):ON_CNCL.VAL",16777215,1,"CPMP:CP$(CP)2:1$(C):ON_CNCL.VAL")
#! Record("CPMP:CP$(CP)2:1$(C):ORDER_OFF",80,1018,0,1,"CPMP:CP$(CP)2:1$(C):ORDER_OFF")
#! Field("CPMP:CP$(CP)2:1$(C):ORDER_OFF.VAL",16777215,1,"CPMP:CP$(CP)2:1$(C):ORDER_OFF.VAL")
#! Record("CPMP:CP$(CP)2:1$(C):OFF_CNCL",80,1458,0,1,"CPMP:CP$(CP)2:1$(C):OFF_CNCL")
#! Field("CPMP:CP$(CP)2:1$(C):OFF_CNCL.VAL",16777215,1,"CPMP:CP$(CP)2:1$(C):OFF_CNCL.VAL")
#! Record("CPMP:CP$(CP)2:1$(C):ON_CFRM",80,578,0,1,"CPMP:CP$(CP)2:1$(C):ON_CFRM")
#! Field("CPMP:CP$(CP)2:1$(C):ON_CFRM.VAL",16777215,1,"CPMP:CP$(CP)2:1$(C):ON_CFRM.VAL")
#! Record("CPMP:CP$(CP)2:1$(C):OFF_CFRM",80,1238,0,1,"CPMP:CP$(CP)2:1$(C):OFF_CFRM")
#! Field("CPMP:CP$(CP)2:1$(C):OFF_CFRM.VAL",16777215,1,"CPMP:CP$(CP)2:1$(C):OFF_CFRM.VAL")
#! Record("CPMP:CP$(CP)2:1$(C):RQST_ON",960,584,0,1,"CPMP:CP$(CP)2:1$(C):RQST_ON")
#! Field("CPMP:CP$(CP)2:1$(C):RQST_ON.VAL",16777215,1,"CPMP:CP$(CP)2:1$(C):RQST_ON.VAL")
#! Record("CPMP:CP$(CP)2:1$(C):RQST_OFF",960,1204,0,1,"CPMP:CP$(CP)2:1$(C):RQST_OFF")
#! Field("CPMP:CP$(CP)2:1$(C):RQST_OFF.VAL",16777215,1,"CPMP:CP$(CP)2:1$(C):RQST_OFF.VAL")
#! Record("CPMP:CP$(CP)2:1$(C):ORDER_ONL",400,524,0,1,"CPMP:CP$(CP)2:1$(C):ORDER_ONL")
#! Field("CPMP:CP$(CP)2:1$(C):ORDER_ONL.FLNK",16777215,1,"CPMP:CP$(CP)2:1$(C):ORDER_ONL.FLNK")
#! Link("CPMP:CP$(CP)2:1$(C):ORDER_ONL.FLNK","CPMP:CP$(CP)2:1$(C):ORDER_ONT")
#! Field("CPMP:CP$(CP)2:1$(C):ORDER_ONL.INPA",16777215,0,"CPMP:CP$(CP)2:1$(C):ORDER_ONL.INPA")
#! Link("CPMP:CP$(CP)2:1$(C):ORDER_ONL.INPA","CPMP:CP$(CP)2:1$(C):ORDER_ON.VAL")
#! Field("CPMP:CP$(CP)2:1$(C):ORDER_ONL.INPB",16777215,0,"CPMP:CP$(CP)2:1$(C):ORDER_ONL.INPB")
#! Link("CPMP:CP$(CP)2:1$(C):ORDER_ONL.INPB","CPMP:CP$(CP)2:1$(C):ON_CFRM.VAL")
#! Field("CPMP:CP$(CP)2:1$(C):ORDER_ONL.INPC",16777215,0,"CPMP:CP$(CP)2:1$(C):ORDER_ONL.INPC")
#! Link("CPMP:CP$(CP)2:1$(C):ORDER_ONL.INPC","CPMP:CP$(CP)2:1$(C):ON_CNCL.VAL")
#! Field("CPMP:CP$(CP)2:1$(C):ORDER_ONL.VAL",16777215,1,"CPMP:CP$(CP)2:1$(C):ORDER_ONL.VAL")
#! Record("CPMP:CP$(CP)2:1$(C):ORDER_ONT",700,522,0,0,"CPMP:CP$(CP)2:1$(C):ORDER_ONT")
#! Field("CPMP:CP$(CP)2:1$(C):ORDER_ONT.DOL",16777215,0,"CPMP:CP$(CP)2:1$(C):ORDER_ONT.DOL")
#! Link("CPMP:CP$(CP)2:1$(C):ORDER_ONT.DOL","CPMP:CP$(CP)2:1$(C):ORDER_ONL.VAL")
#! Field("CPMP:CP$(CP)2:1$(C):ORDER_ONT.OUT",16777215,1,"CPMP:CP$(CP)2:1$(C):ORDER_ONT.OUT")
#! Link("CPMP:CP$(CP)2:1$(C):ORDER_ONT.OUT","CPMP:CP$(CP)2:1$(C):RQST_ON.VAL")
#! Record("CPMP:CP$(CP)2:1$(C):ORDER_OFFL",400,1124,0,1,"CPMP:CP$(CP)2:1$(C):ORDER_OFFL")
#! Field("CPMP:CP$(CP)2:1$(C):ORDER_OFFL.FLNK",16777215,1,"CPMP:CP$(CP)2:1$(C):ORDER_OFFL.FLNK")
#! Link("CPMP:CP$(CP)2:1$(C):ORDER_OFFL.FLNK","CPMP:CP$(CP)2:1$(C):ORDER_OFFT")
#! Field("CPMP:CP$(CP)2:1$(C):ORDER_OFFL.INPA",16777215,0,"CPMP:CP$(CP)2:1$(C):ORDER_OFFL.INPA")
#! Link("CPMP:CP$(CP)2:1$(C):ORDER_OFFL.INPA","CPMP:CP$(CP)2:1$(C):ORDER_OFF.VAL")
#! Field("CPMP:CP$(CP)2:1$(C):ORDER_OFFL.INPC",16777215,0,"CPMP:CP$(CP)2:1$(C):ORDER_OFFL.INPC")
#! Link("CPMP:CP$(CP)2:1$(C):ORDER_OFFL.INPC","CPMP:CP$(CP)2:1$(C):OFF_CNCL.VAL")
#! Field("CPMP:CP$(CP)2:1$(C):ORDER_OFFL.INPB",16777215,0,"CPMP:CP$(CP)2:1$(C):ORDER_OFFL.INPB")
#! Link("CPMP:CP$(CP)2:1$(C):ORDER_OFFL.INPB","CPMP:CP$(CP)2:1$(C):OFF_CFRM.VAL")
#! Field("CPMP:CP$(CP)2:1$(C):ORDER_OFFL.VAL",16777215,1,"CPMP:CP$(CP)2:1$(C):ORDER_OFFL.VAL")
#! Record("CPMP:CP$(CP)2:1$(C):ORDER_OFFT",700,1156,0,0,"CPMP:CP$(CP)2:1$(C):ORDER_OFFT")
#! Field("CPMP:CP$(CP)2:1$(C):ORDER_OFFT.DOL",16777215,0,"CPMP:CP$(CP)2:1$(C):ORDER_OFFT.DOL")
#! Link("CPMP:CP$(CP)2:1$(C):ORDER_OFFT.DOL","CPMP:CP$(CP)2:1$(C):ORDER_OFFL.VAL")
#! Field("CPMP:CP$(CP)2:1$(C):ORDER_OFFT.OUT",16777215,1,"CPMP:CP$(CP)2:1$(C):ORDER_OFFT.OUT")
#! Link("CPMP:CP$(CP)2:1$(C):ORDER_OFFT.OUT","CPMP:CP$(CP)2:1$(C):RQST_OFF.VAL")
#! TextBox(TB1,480,360,780,400,0,"Dialog",12,1,16777215,"Turn On and confirm logic\nTurn Off and confirm logic\n",null)
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CHTR:CP$(CP)2:1$(C)35:ORDER_ON") {
  field(DESC, "Oil Htr order on")
  field(ZNAM, "not ordered on")
  field(ONAM, "ordered on")
  field(OMSL, "supervisory")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CHTR:CP$(CP)2:1$(C)35:ON_CNCL") {
  field(DESC, "Oil Htr Cancel ON order")
  field(ZNAM, "not cancelled")
  field(ONAM, "cancelled")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CHTR:CP$(CP)2:1$(C)35:ORDER_OFF") {
  field(DESC, "Oil Htr order off")
  field(ZNAM, "not order off")
  field(ONAM, "order off")
  field(OMSL, "supervisory")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CHTR:CP$(CP)2:1$(C)35:OFF_CNCL") {
  field(DESC, "Oil Htr Cancel OFF order")
  field(ZNAM, "not cancelled")
  field(ONAM, "cancelled")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CHTR:CP$(CP)2:1$(C)35:ON_CFRM") {
  field(DESC, "Oil Htr confirm ON order")
  field(ZNAM, "not confirmed")
  field(ONAM, "confirmed")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
  field(OMSL, "supervisory")
}

record(bo, "CHTR:CP$(CP)2:1$(C)35:OFF_CFRM") {
  field(DESC, "Oil Htr confirm OFF order")
  field(ZNAM, "not confirmed")
  field(ONAM, "confirmed")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CHTR:CP$(CP)2:1$(C)35:RQST_ON") {
  field(DESC, "Oil Htr Rqst On")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) Oil_Heater_ON_X B 0")
  field(ZNAM, "not active")
  field(ONAM, "Active")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(ASG, "NOWRITE")
  field(HIGH, "0")
  field(OMSL, "supervisory")
}

record(bo, "CHTR:CP$(CP)2:1$(C)35:RQST_OFF") {
  field(DESC, "Oil Htr Rqst Off")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) Oil_Heater_OFF_X B 0")
  field(ZNAM, "not active")
  field(ONAM, "Active")
  field(ASG, "NOWRITE")
  field(PINI, "NO")
  field(HIGH, "0")
  field(SCAN, "1 second")
  field(OMSL, "supervisory")
}

record(sub, "CHTR:CP$(CP)2:1$(C)35:ORDER_ONL") {
  field(DESC, "Oil Htr")
  field(SCAN, ".5 second")
  field(PINI, "NO")
  field(FLNK, "CHTR:CP$(CP)2:1$(C)35:ORDER_ONT")
  field(INAM, "Icclmom")
  field(SNAM, "Scclmom")
  field(INPA, "CHTR:CP$(CP)2:1$(C)35:ORDER_ON")
  field(INPB, "CHTR:CP$(CP)2:1$(C)35:ON_CFRM")
  field(INPC, "CHTR:CP$(CP)2:1$(C)35:ON_CNCL")
  field(ASG, "NOWRITE")
}

record(bo, "CHTR:CP$(CP)2:1$(C)35:ORDER_ONT") {
  field(DESC, "Oil Htr")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "closed_loop")
  field(DOL, "CHTR:CP$(CP)2:1$(C)35:ORDER_ONL")
  field(OUT, "CHTR:CP$(CP)2:1$(C)35:RQST_ON")
  field(ZSV, "MAJOR")
  field(ASG, "NOWRITE")
  field(ZNAM, "disabled")
  field(ONAM, "enabled")
  field(OSV, "NO_ALARM")
  field(COSV, "NO_ALARM")
}

record(sub, "CHTR:CP$(CP)2:1$(C)35:ORDER_OFFL") {
  field(DESC, "Oil Htr")
  field(SCAN, ".5 second")
  field(PINI, "NO")
  field(FLNK, "CHTR:CP$(CP)2:1$(C)35:ORDER_OFFT")
  field(INAM, "Icclmom")
  field(SNAM, "Scclmom")
  field(INPA, "CHTR:CP$(CP)2:1$(C)35:ORDER_OFF")
  field(INPB, "CHTR:CP$(CP)2:1$(C)35:OFF_CFRM")
  field(INPC, "CHTR:CP$(CP)2:1$(C)35:OFF_CNCL")
  field(ASG, "NOWRITE")
}

record(bo, "CHTR:CP$(CP)2:1$(C)35:ORDER_OFFT") {
  field(DESC, "Oil Htr")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(OMSL, "closed_loop")
  field(DOL, "CHTR:CP$(CP)2:1$(C)35:ORDER_OFFL")
  field(OUT, "CHTR:CP$(CP)2:1$(C)35:RQST_OFF")
  field(ZSV, "MAJOR")
  field(ASG, "NOWRITE")
  field(ZNAM, "disabled")
  field(ONAM, "enabled")
  field(OSV, "NO_ALARM")
  field(COSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,416,1.1)
#! Record("CHTR:CP$(CP)2:1$(C)35:ORDER_ON",80,378,0,1,"CHTR:CP$(CP)2:1$(C)35:ORDER_ON")
#! Field("CHTR:CP$(CP)2:1$(C)35:ORDER_ON.VAL",16777215,1,"CHTR:CP$(CP)2:1$(C)35:ORDER_ON.VAL")
#! Record("CHTR:CP$(CP)2:1$(C)35:ON_CNCL",80,798,0,1,"CHTR:CP$(CP)2:1$(C)35:ON_CNCL")
#! Field("CHTR:CP$(CP)2:1$(C)35:ON_CNCL.VAL",16777215,1,"CHTR:CP$(CP)2:1$(C)35:ON_CNCL.VAL")
#! Record("CHTR:CP$(CP)2:1$(C)35:ORDER_OFF",80,1018,0,1,"CHTR:CP$(CP)2:1$(C)35:ORDER_OFF")
#! Field("CHTR:CP$(CP)2:1$(C)35:ORDER_OFF.VAL",16777215,1,"CHTR:CP$(CP)2:1$(C)35:ORDER_OFF.VAL")
#! Record("CHTR:CP$(CP)2:1$(C)35:OFF_CNCL",80,1458,0,1,"CHTR:CP$(CP)2:1$(C)35:OFF_CNCL")
#! Field("CHTR:CP$(CP)2:1$(C)35:OFF_CNCL.VAL",16777215,1,"CHTR:CP$(CP)2:1$(C)35:OFF_CNCL.VAL")
#! Record("CHTR:CP$(CP)2:1$(C)35:ON_CFRM",80,578,0,1,"CHTR:CP$(CP)2:1$(C)35:ON_CFRM")
#! Field("CHTR:CP$(CP)2:1$(C)35:ON_CFRM.VAL",16777215,1,"CHTR:CP$(CP)2:1$(C)35:ON_CFRM.VAL")
#! Record("CHTR:CP$(CP)2:1$(C)35:OFF_CFRM",80,1238,0,1,"CHTR:CP$(CP)2:1$(C)35:OFF_CFRM")
#! Field("CHTR:CP$(CP)2:1$(C)35:OFF_CFRM.VAL",16777215,1,"CHTR:CP$(CP)2:1$(C)35:OFF_CFRM.VAL")
#! Record("CHTR:CP$(CP)2:1$(C)35:RQST_ON",960,584,0,1,"CHTR:CP$(CP)2:1$(C)35:RQST_ON")
#! Field("CHTR:CP$(CP)2:1$(C)35:RQST_ON.VAL",16777215,1,"CHTR:CP$(CP)2:1$(C)35:RQST_ON.VAL")
#! Record("CHTR:CP$(CP)2:1$(C)35:RQST_OFF",960,1204,0,1,"CHTR:CP$(CP)2:1$(C)35:RQST_OFF")
#! Field("CHTR:CP$(CP)2:1$(C)35:RQST_OFF.VAL",16777215,1,"CHTR:CP$(CP)2:1$(C)35:RQST_OFF.VAL")
#! Record("CHTR:CP$(CP)2:1$(C)35:ORDER_ONL",400,524,0,1,"CHTR:CP$(CP)2:1$(C)35:ORDER_ONL")
#! Field("CHTR:CP$(CP)2:1$(C)35:ORDER_ONL.FLNK",16777215,1,"CHTR:CP$(CP)2:1$(C)35:ORDER_ONL.FLNK")
#! Link("CHTR:CP$(CP)2:1$(C)35:ORDER_ONL.FLNK","CHTR:CP$(CP)2:1$(C)35:ORDER_ONT")
#! Field("CHTR:CP$(CP)2:1$(C)35:ORDER_ONL.INPA",16777215,0,"CHTR:CP$(CP)2:1$(C)35:ORDER_ONL.INPA")
#! Link("CHTR:CP$(CP)2:1$(C)35:ORDER_ONL.INPA","CHTR:CP$(CP)2:1$(C)35:ORDER_ON.VAL")
#! Field("CHTR:CP$(CP)2:1$(C)35:ORDER_ONL.INPB",16777215,0,"CHTR:CP$(CP)2:1$(C)35:ORDER_ONL.INPB")
#! Link("CHTR:CP$(CP)2:1$(C)35:ORDER_ONL.INPB","CHTR:CP$(CP)2:1$(C)35:ON_CFRM.VAL")
#! Field("CHTR:CP$(CP)2:1$(C)35:ORDER_ONL.INPC",16777215,0,"CHTR:CP$(CP)2:1$(C)35:ORDER_ONL.INPC")
#! Link("CHTR:CP$(CP)2:1$(C)35:ORDER_ONL.INPC","CHTR:CP$(CP)2:1$(C)35:ON_CNCL.VAL")
#! Field("CHTR:CP$(CP)2:1$(C)35:ORDER_ONL.VAL",16777215,1,"CHTR:CP$(CP)2:1$(C)35:ORDER_ONL.VAL")
#! Record("CHTR:CP$(CP)2:1$(C)35:ORDER_ONT",700,522,0,0,"CHTR:CP$(CP)2:1$(C)35:ORDER_ONT")
#! Field("CHTR:CP$(CP)2:1$(C)35:ORDER_ONT.DOL",16777215,0,"CHTR:CP$(CP)2:1$(C)35:ORDER_ONT.DOL")
#! Link("CHTR:CP$(CP)2:1$(C)35:ORDER_ONT.DOL","CHTR:CP$(CP)2:1$(C)35:ORDER_ONL.VAL")
#! Field("CHTR:CP$(CP)2:1$(C)35:ORDER_ONT.OUT",16777215,1,"CHTR:CP$(CP)2:1$(C)35:ORDER_ONT.OUT")
#! Link("CHTR:CP$(CP)2:1$(C)35:ORDER_ONT.OUT","CHTR:CP$(CP)2:1$(C)35:RQST_ON.VAL")
#! Record("CHTR:CP$(CP)2:1$(C)35:ORDER_OFFL",400,1124,0,1,"CHTR:CP$(CP)2:1$(C)35:ORDER_OFFL")
#! Field("CHTR:CP$(CP)2:1$(C)35:ORDER_OFFL.FLNK",16777215,1,"CHTR:CP$(CP)2:1$(C)35:ORDER_OFFL.FLNK")
#! Link("CHTR:CP$(CP)2:1$(C)35:ORDER_OFFL.FLNK","CHTR:CP$(CP)2:1$(C)35:ORDER_OFFT")
#! Field("CHTR:CP$(CP)2:1$(C)35:ORDER_OFFL.INPA",16777215,0,"CHTR:CP$(CP)2:1$(C)35:ORDER_OFFL.INPA")
#! Link("CHTR:CP$(CP)2:1$(C)35:ORDER_OFFL.INPA","CHTR:CP$(CP)2:1$(C)35:ORDER_OFF.VAL")
#! Field("CHTR:CP$(CP)2:1$(C)35:ORDER_OFFL.INPC",16777215,0,"CHTR:CP$(CP)2:1$(C)35:ORDER_OFFL.INPC")
#! Link("CHTR:CP$(CP)2:1$(C)35:ORDER_OFFL.INPC","CHTR:CP$(CP)2:1$(C)35:OFF_CNCL.VAL")
#! Field("CHTR:CP$(CP)2:1$(C)35:ORDER_OFFL.INPB",16777215,0,"CHTR:CP$(CP)2:1$(C)35:ORDER_OFFL.INPB")
#! Link("CHTR:CP$(CP)2:1$(C)35:ORDER_OFFL.INPB","CHTR:CP$(CP)2:1$(C)35:OFF_CFRM.VAL")
#! Field("CHTR:CP$(CP)2:1$(C)35:ORDER_OFFL.VAL",16777215,1,"CHTR:CP$(CP)2:1$(C)35:ORDER_OFFL.VAL")
#! Record("CHTR:CP$(CP)2:1$(C)35:ORDER_OFFT",700,1156,0,0,"CHTR:CP$(CP)2:1$(C)35:ORDER_OFFT")
#! Field("CHTR:CP$(CP)2:1$(C)35:ORDER_OFFT.DOL",16777215,0,"CHTR:CP$(CP)2:1$(C)35:ORDER_OFFT.DOL")
#! Link("CHTR:CP$(CP)2:1$(C)35:ORDER_OFFT.DOL","CHTR:CP$(CP)2:1$(C)35:ORDER_OFFL.VAL")
#! Field("CHTR:CP$(CP)2:1$(C)35:ORDER_OFFT.OUT",16777215,1,"CHTR:CP$(CP)2:1$(C)35:ORDER_OFFT.OUT")
#! Link("CHTR:CP$(CP)2:1$(C)35:ORDER_OFFT.OUT","CHTR:CP$(CP)2:1$(C)35:RQST_OFF.VAL")
#! TextBox(TB1,480,360,780,400,0,"Dialog",12,1,16777215,"Turn On and confirm logic\nTurn Off and confirm logic\n",null)
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CSV:CP$(CP)2:1$(C)50:ORDER_ON") {
  field(DESC, "SV21X50 controls order on")
  field(ZNAM, "not ordered on")
  field(ONAM, "ordered on")
  field(OMSL, "supervisory")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CSV:CP$(CP)2:1$(C)50:ON_CNCL") {
  field(DESC, "SV21X50 controls Cancel ON order")
  field(ZNAM, "not cancelled")
  field(ONAM, "cancelled")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CSV:CP$(CP)2:1$(C)50:ORDER_OFF") {
  field(DESC, "SV21X50 controls order off")
  field(ZNAM, "not order off")
  field(ONAM, "order off")
  field(OMSL, "supervisory")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CSV:CP$(CP)2:1$(C)50:OFF_CNCL") {
  field(DESC, "SV21X50 controls Cancel OFF order")
  field(ZNAM, "not cancelled")
  field(ONAM, "cancelled")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CSV:CP$(CP)2:1$(C)50:ON_CFRM") {
  field(DESC, "SV21X50 controls confirm ON order")
  field(ZNAM, "not confirmed")
  field(ONAM, "confirmed")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
  field(OMSL, "supervisory")
}

record(bo, "CSV:CP$(CP)2:1$(C)50:OFF_CFRM") {
  field(DESC, "SV21X50 controls confirm OFF order")
  field(ZNAM, "not confirmed")
  field(ONAM, "confirmed")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CSV:CP$(CP)2:1$(C)50:RQST_ON") {
  field(DESC, "SV21X50 controls Rqst On")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) SV21X50.EN B 0")
  field(ZNAM, "not active")
  field(ONAM, "Active")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(ASG, "NOWRITE")
  field(HIGH, "0")
  field(OMSL, "supervisory")
}

record(bo, "CSV:CP$(CP)2:1$(C)50:RQST_OFF") {
  field(DESC, "SV21X50 controls Rqst Off")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) SV21X50.DIS B 0")
  field(ZNAM, "not active")
  field(ONAM, "Active")
  field(ASG, "NOWRITE")
  field(PINI, "NO")
  field(HIGH, "0")
  field(SCAN, "1 second")
  field(OMSL, "supervisory")
}

record(sub, "CSV:CP$(CP)2:1$(C)50:ORDER_ONL") {
  field(DESC, "SV21X50 controls")
  field(SCAN, ".5 second")
  field(PINI, "NO")
  field(FLNK, "CSV:CP$(CP)2:1$(C)50:ORDER_ONT")
  field(INAM, "Icclmom")
  field(SNAM, "Scclmom")
  field(INPA, "CSV:CP$(CP)2:1$(C)50:ORDER_ON")
  field(INPB, "CSV:CP$(CP)2:1$(C)50:ON_CFRM")
  field(INPC, "CSV:CP$(CP)2:1$(C)50:ON_CNCL")
  field(ASG, "NOWRITE")
}

record(bo, "CSV:CP$(CP)2:1$(C)50:ORDER_ONT") {
  field(DESC, "SV21X50 controls")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "closed_loop")
  field(DOL, "CSV:CP$(CP)2:1$(C)50:ORDER_ONL")
  field(OUT, "CSV:CP$(CP)2:1$(C)50:RQST_ON")
  field(ZSV, "MAJOR")
  field(ASG, "NOWRITE")
  field(ZNAM, "disabled")
  field(ONAM, "enabled")
  field(OSV, "NO_ALARM")
  field(COSV, "NO_ALARM")
}

record(sub, "CSV:CP$(CP)2:1$(C)50:ORDER_OFFL") {
  field(DESC, "SV21X50 controls")
  field(SCAN, ".5 second")
  field(PINI, "NO")
  field(FLNK, "CSV:CP$(CP)2:1$(C)50:ORDER_OFFT")
  field(INAM, "Icclmom")
  field(SNAM, "Scclmom")
  field(INPA, "CSV:CP$(CP)2:1$(C)50:ORDER_OFF")
  field(INPB, "CSV:CP$(CP)2:1$(C)50:OFF_CFRM")
  field(INPC, "CSV:CP$(CP)2:1$(C)50:OFF_CNCL")
  field(ASG, "NOWRITE")
}

record(bo, "CSV:CP$(CP)2:1$(C)50:ORDER_OFFT") {
  field(DESC, "SV21X50 controls")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(OMSL, "closed_loop")
  field(DOL, "CSV:CP$(CP)2:1$(C)50:ORDER_OFFL")
  field(OUT, "CSV:CP$(CP)2:1$(C)50:RQST_OFF")
  field(ZSV, "MAJOR")
  field(ASG, "NOWRITE")
  field(ZNAM, "disabled")
  field(ONAM, "enabled")
  field(OSV, "NO_ALARM")
  field(COSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,416,1.1)
#! Record("CSV:CP$(CP)2:1$(C)50:ORDER_ON",80,378,0,1,"CSV:CP$(CP)2:1$(C)50:ORDER_ON")
#! Field("CSV:CP$(CP)2:1$(C)50:ORDER_ON.VAL",16777215,1,"CSV:CP$(CP)2:1$(C)50:ORDER_ON.VAL")
#! Record("CSV:CP$(CP)2:1$(C)50:ON_CNCL",80,798,0,1,"CSV:CP$(CP)2:1$(C)50:ON_CNCL")
#! Field("CSV:CP$(CP)2:1$(C)50:ON_CNCL.VAL",16777215,1,"CSV:CP$(CP)2:1$(C)50:ON_CNCL.VAL")
#! Record("CSV:CP$(CP)2:1$(C)50:ORDER_OFF",80,1018,0,1,"CSV:CP$(CP)2:1$(C)50:ORDER_OFF")
#! Field("CSV:CP$(CP)2:1$(C)50:ORDER_OFF.VAL",16777215,1,"CSV:CP$(CP)2:1$(C)50:ORDER_OFF.VAL")
#! Record("CSV:CP$(CP)2:1$(C)50:OFF_CNCL",80,1458,0,1,"CSV:CP$(CP)2:1$(C)50:OFF_CNCL")
#! Field("CSV:CP$(CP)2:1$(C)50:OFF_CNCL.VAL",16777215,1,"CSV:CP$(CP)2:1$(C)50:OFF_CNCL.VAL")
#! Record("CSV:CP$(CP)2:1$(C)50:ON_CFRM",80,578,0,1,"CSV:CP$(CP)2:1$(C)50:ON_CFRM")
#! Field("CSV:CP$(CP)2:1$(C)50:ON_CFRM.VAL",16777215,1,"CSV:CP$(CP)2:1$(C)50:ON_CFRM.VAL")
#! Record("CSV:CP$(CP)2:1$(C)50:OFF_CFRM",80,1238,0,1,"CSV:CP$(CP)2:1$(C)50:OFF_CFRM")
#! Field("CSV:CP$(CP)2:1$(C)50:OFF_CFRM.VAL",16777215,1,"CSV:CP$(CP)2:1$(C)50:OFF_CFRM.VAL")
#! Record("CSV:CP$(CP)2:1$(C)50:RQST_ON",960,584,0,1,"CSV:CP$(CP)2:1$(C)50:RQST_ON")
#! Field("CSV:CP$(CP)2:1$(C)50:RQST_ON.VAL",16777215,1,"CSV:CP$(CP)2:1$(C)50:RQST_ON.VAL")
#! Record("CSV:CP$(CP)2:1$(C)50:RQST_OFF",960,1204,0,1,"CSV:CP$(CP)2:1$(C)50:RQST_OFF")
#! Field("CSV:CP$(CP)2:1$(C)50:RQST_OFF.VAL",16777215,1,"CSV:CP$(CP)2:1$(C)50:RQST_OFF.VAL")
#! Record("CSV:CP$(CP)2:1$(C)50:ORDER_ONL",400,524,0,1,"CSV:CP$(CP)2:1$(C)50:ORDER_ONL")
#! Field("CSV:CP$(CP)2:1$(C)50:ORDER_ONL.FLNK",16777215,1,"CSV:CP$(CP)2:1$(C)50:ORDER_ONL.FLNK")
#! Link("CSV:CP$(CP)2:1$(C)50:ORDER_ONL.FLNK","CSV:CP$(CP)2:1$(C)50:ORDER_ONT")
#! Field("CSV:CP$(CP)2:1$(C)50:ORDER_ONL.INPA",16777215,0,"CSV:CP$(CP)2:1$(C)50:ORDER_ONL.INPA")
#! Link("CSV:CP$(CP)2:1$(C)50:ORDER_ONL.INPA","CSV:CP$(CP)2:1$(C)50:ORDER_ON.VAL")
#! Field("CSV:CP$(CP)2:1$(C)50:ORDER_ONL.INPB",16777215,0,"CSV:CP$(CP)2:1$(C)50:ORDER_ONL.INPB")
#! Link("CSV:CP$(CP)2:1$(C)50:ORDER_ONL.INPB","CSV:CP$(CP)2:1$(C)50:ON_CFRM.VAL")
#! Field("CSV:CP$(CP)2:1$(C)50:ORDER_ONL.INPC",16777215,0,"CSV:CP$(CP)2:1$(C)50:ORDER_ONL.INPC")
#! Link("CSV:CP$(CP)2:1$(C)50:ORDER_ONL.INPC","CSV:CP$(CP)2:1$(C)50:ON_CNCL.VAL")
#! Field("CSV:CP$(CP)2:1$(C)50:ORDER_ONL.VAL",16777215,1,"CSV:CP$(CP)2:1$(C)50:ORDER_ONL.VAL")
#! Record("CSV:CP$(CP)2:1$(C)50:ORDER_ONT",700,522,0,0,"CSV:CP$(CP)2:1$(C)50:ORDER_ONT")
#! Field("CSV:CP$(CP)2:1$(C)50:ORDER_ONT.DOL",16777215,0,"CSV:CP$(CP)2:1$(C)50:ORDER_ONT.DOL")
#! Link("CSV:CP$(CP)2:1$(C)50:ORDER_ONT.DOL","CSV:CP$(CP)2:1$(C)50:ORDER_ONL.VAL")
#! Field("CSV:CP$(CP)2:1$(C)50:ORDER_ONT.OUT",16777215,1,"CSV:CP$(CP)2:1$(C)50:ORDER_ONT.OUT")
#! Link("CSV:CP$(CP)2:1$(C)50:ORDER_ONT.OUT","CSV:CP$(CP)2:1$(C)50:RQST_ON.VAL")
#! Record("CSV:CP$(CP)2:1$(C)50:ORDER_OFFL",400,1124,0,1,"CSV:CP$(CP)2:1$(C)50:ORDER_OFFL")
#! Field("CSV:CP$(CP)2:1$(C)50:ORDER_OFFL.FLNK",16777215,1,"CSV:CP$(CP)2:1$(C)50:ORDER_OFFL.FLNK")
#! Link("CSV:CP$(CP)2:1$(C)50:ORDER_OFFL.FLNK","CSV:CP$(CP)2:1$(C)50:ORDER_OFFT")
#! Field("CSV:CP$(CP)2:1$(C)50:ORDER_OFFL.INPA",16777215,0,"CSV:CP$(CP)2:1$(C)50:ORDER_OFFL.INPA")
#! Link("CSV:CP$(CP)2:1$(C)50:ORDER_OFFL.INPA","CSV:CP$(CP)2:1$(C)50:ORDER_OFF.VAL")
#! Field("CSV:CP$(CP)2:1$(C)50:ORDER_OFFL.INPC",16777215,0,"CSV:CP$(CP)2:1$(C)50:ORDER_OFFL.INPC")
#! Link("CSV:CP$(CP)2:1$(C)50:ORDER_OFFL.INPC","CSV:CP$(CP)2:1$(C)50:OFF_CNCL.VAL")
#! Field("CSV:CP$(CP)2:1$(C)50:ORDER_OFFL.INPB",16777215,0,"CSV:CP$(CP)2:1$(C)50:ORDER_OFFL.INPB")
#! Link("CSV:CP$(CP)2:1$(C)50:ORDER_OFFL.INPB","CSV:CP$(CP)2:1$(C)50:OFF_CFRM.VAL")
#! Field("CSV:CP$(CP)2:1$(C)50:ORDER_OFFL.VAL",16777215,1,"CSV:CP$(CP)2:1$(C)50:ORDER_OFFL.VAL")
#! Record("CSV:CP$(CP)2:1$(C)50:ORDER_OFFT",700,1156,0,0,"CSV:CP$(CP)2:1$(C)50:ORDER_OFFT")
#! Field("CSV:CP$(CP)2:1$(C)50:ORDER_OFFT.DOL",16777215,0,"CSV:CP$(CP)2:1$(C)50:ORDER_OFFT.DOL")
#! Link("CSV:CP$(CP)2:1$(C)50:ORDER_OFFT.DOL","CSV:CP$(CP)2:1$(C)50:ORDER_OFFL.VAL")
#! Field("CSV:CP$(CP)2:1$(C)50:ORDER_OFFT.OUT",16777215,1,"CSV:CP$(CP)2:1$(C)50:ORDER_OFFT.OUT")
#! Link("CSV:CP$(CP)2:1$(C)50:ORDER_OFFT.OUT","CSV:CP$(CP)2:1$(C)50:RQST_OFF.VAL")
#! TextBox(TB1,480,360,780,400,0,"Dialog",12,1,16777215,"Turn On and confirm logic\nTurn Off and confirm logic\n",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CSV:CP$(CP)2:1$(C)47:LOAD") {
  field(DESC, "load cmd")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) Load_X B 0")
  field(ZNAM, " no load")
  field(ONAM, "load")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
  field(ASG, "CRYO")
  field(HIGH, "1")
  field(IVOA, "Don't drive outputs")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CSV:CP$(CP)2:1$(C)47:LOAD",2060,2137,0,1,"CSV:CP$(CP)2:1$(C)47:LOAD")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CSV:CP$(CP)2:1$(C)47:UNLOAD") {
  field(DESC, "unload cmd")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) Unload_X B 0")
  field(ZNAM, " no unload")
  field(ONAM, "unload")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
  field(ASG, "CRYO")
  field(HIGH, "1")
  field(IVOA, "Don't drive outputs")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CSV:CP$(CP)2:1$(C)47:UNLOAD",2060,2137,0,1,"CSV:CP$(CP)2:1$(C)47:UNLOAD")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "WCMP:CP$(CP)2:1$(C):AUTO_LOADING") {
  field(DESC, "WCMP auto loading")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) C300_SLIDE_VALVE_AUTO")
  field(ZNAM, "Auto loading Inactive")
  field(ONAM, "Auto loading Active")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("WCMP:CP$(CP)2:1$(C):AUTO_LOADING",2060,2137,0,1,"WCMP:CP$(CP)2:1$(C):AUTO_LOADING")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CHTR:CP$(CP)2:1$(C)35:MMOD") {
  field(DESC, "Man. Mode status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) HTR21X35.mmod")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(bi, "CHTR:CP$(CP)2:1$(C)35:IMOD") {
  field(DESC, "Interlock mode")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) HTR21X35.imod")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(stringin, "CHTR:CP$(CP)2:1$(C)35:TEXT1") {
  field(DESC, "Notes")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  info(autosaveFields, "VAL")
}

record(stringin, "CHTR:CP$(CP)2:1$(C)35:TEXT2") {
  field(DESC, "Notes")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  info(autosaveFields, "VAL")
}

record(bi, "CHTR:CP$(CP)2:1$(C)35:INTERLOCK") {
  field(DESC, "interlock status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) HTR21X35.Interlock_Condition")
  field(ZNAM, "ok")
  field(ONAM, "interlocked")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(bi, "CHTR:CP$(CP)2:1$(C)35:IVAL") {
  field(DESC, "interlock state")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) HTR21X35.ival")
  field(ZNAM, "off")
  field(ONAM, "on")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(bi, "CHTR:CP$(CP)2:1$(C)35:OUTPUT") {
  field(DESC, "actuatorDO output command")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) HTR21X35.Output")
  field(ZNAM, "off")
  field(ONAM, "on")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(bo, "CHTR:CP$(CP)2:1$(C)35:MANUAL") {
  field(DESC, "Manual Mode request ")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) HTR21X35.Manual B 0")
  field(ZNAM, "not manual")
  field(ONAM, "Manual")
  field(ASG, "CRYO")
  field(HIGH, "1")
  field(IVOA, "Don't drive outputs")
}

record(bo, "CHTR:CP$(CP)2:1$(C)35:SEQUENCER") {
  field(DESC, "SEQ Mode request ")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) HTR21X35.Sequencer B 0")
  field(ZNAM, "not sequencer")
  field(ONAM, "Sequencer")
  field(ASG, "CRYO")
  field(HIGH, "1")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CHTR:CP$(CP)2:1$(C)35:MODE") {
  field(DESC, "actuator mode (man,ovr,seq)")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) HTR21X35.MODE")
}

record(bi, "CHTR:CP$(CP)2:1$(C)35:ALM") {
  field(DESC, "Limit SW alarm")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) HTR21X35.ER")
  field(ZNAM, "ok")
  field(ONAM, "alarm")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(bi, "CHTR:CP$(CP)2:1$(C)35:IL_LATCH") {
  field(DESC, "interlock latched indicator")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) HTR21X35.Interlock_Condition_L")
  field(ZNAM, "ok")
  field(ONAM, "latched")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(bo, "CHTR:CP$(CP)2:1$(C)35:IL_RESET") {
  field(DESC, "Interlock Latch Reset")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) HTR21X35.Interlock_Condition_Reset B 0")
  field(ZNAM, "not reset")
  field(ONAM, "RESET")
  field(ASG, "CRYO")
  field(HIGH, "1")
  field(IVOA, "Don't drive outputs")
}

record(bi, "CHTR:CP$(CP)2:1$(C)35:ZSH") {
  field(DESC, "High limit sw value")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) HTR21X35.ZSH")
  field(ZNAM, "not active")
  field(ONAM, "active")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(bi, "CHTR:CP$(CP)2:1$(C)35:ZSL") {
  field(DESC, "low limit sw value")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) HTR21X35.ZSL")
  field(ZNAM, "not active")
  field(ONAM, "active")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(bi, "CHTR:CP$(CP)2:1$(C)35:MVAL") {
  field(DESC, "manual mode output value")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) HTR21X35.mval")
  field(ZNAM, "off")
  field(ONAM, "on")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(stringin, "CHTR:CP$(CP)2:1$(C)35:MODE_STRING") {
  field(DESC, "Actuator (DO) Mode String")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) HTR21X35.Mode_String")
}

record(bi, "CHTR:CP$(CP)2:1$(C)35:SVAL") {
  field(DESC, "sequencer mode output value")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) HTR21X35.sval")
  field(ZNAM, "off")
  field(ONAM, "on")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(stringin, "CHTR:CP$(CP)2:1$(C)35:PIDTAG") {
  field(DESC, "Oil heater 21$(C)35 PIDTAG")
  field(PINI, "YES")
  field(VAL, "HTR21$(C)35")
}

record(bi, "CHTR:CP$(CP)2:1$(C)35:SMOD") {
  field(DESC, "Sequencer mode indicator")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) HTR21X35.smod")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(bi, "CHTR:CP$(CP)2:1$(C)35:CMD_OUT") {
  field(DESC, "rdbk of output signal to the actuator")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) HTR21X35O")
  field(ZNAM, "off")
  field(ONAM, "on")
}

record(mbbiDirect, "CHTR:CP$(CP)2:1$(C)35:SWITCH_DISABLE") {
  field(DESC, "Indicates if switch(es) are  used")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) HTR21X35.Disable B 0")
  field(NOBT, "16")
}

#! Further lines contain data used by VisualDCT
#! View(1599,2252,1.0)
#! Record("CHTR:CP$(CP)2:1$(C)35:MMOD",2500,2499,0,1,"CHTR:CP$(CP)2:1$(C)35:MMOD")
#! Record("CHTR:CP$(CP)2:1$(C)35:IMOD",2680,2499,0,1,"CHTR:CP$(CP)2:1$(C)35:IMOD")
#! Record("CHTR:CP$(CP)2:1$(C)35:TEXT1",1760,2682,0,1,"CHTR:CP$(CP)2:1$(C)35:TEXT1")
#! Record("CHTR:CP$(CP)2:1$(C)35:TEXT2",1760,2782,0,1,"CHTR:CP$(CP)2:1$(C)35:TEXT2")
#! Record("CHTR:CP$(CP)2:1$(C)35:INTERLOCK",2500,2719,0,1,"CHTR:CP$(CP)2:1$(C)35:INTERLOCK")
#! Record("CHTR:CP$(CP)2:1$(C)35:IVAL",2140,2499,0,1,"CHTR:CP$(CP)2:1$(C)35:IVAL")
#! Record("CHTR:CP$(CP)2:1$(C)35:OUTPUT",2680,2279,0,1,"CHTR:CP$(CP)2:1$(C)35:OUTPUT")
#! Record("CHTR:CP$(CP)2:1$(C)35:MANUAL",1960,2265,0,1,"CHTR:CP$(CP)2:1$(C)35:MANUAL")
#! Record("CHTR:CP$(CP)2:1$(C)35:SEQUENCER",2140,2265,0,1,"CHTR:CP$(CP)2:1$(C)35:SEQUENCER")
#! Record("CHTR:CP$(CP)2:1$(C)35:MODE",1760,2274,0,1,"CHTR:CP$(CP)2:1$(C)35:MODE")
#! Record("CHTR:CP$(CP)2:1$(C)35:ALM",1960,2719,0,1,"CHTR:CP$(CP)2:1$(C)35:ALM")
#! Record("CHTR:CP$(CP)2:1$(C)35:IL_LATCH",2320,2719,0,1,"CHTR:CP$(CP)2:1$(C)35:IL_LATCH")
#! Record("CHTR:CP$(CP)2:1$(C)35:IL_RESET",2140,2705,0,1,"CHTR:CP$(CP)2:1$(C)35:IL_RESET")
#! Record("CHTR:CP$(CP)2:1$(C)35:ZSH",2700,2719,0,1,"CHTR:CP$(CP)2:1$(C)35:ZSH")
#! Record("CHTR:CP$(CP)2:1$(C)35:ZSL",2880,2719,0,1,"CHTR:CP$(CP)2:1$(C)35:ZSL")
#! Record("CHTR:CP$(CP)2:1$(C)35:MVAL",2320,2499,0,1,"CHTR:CP$(CP)2:1$(C)35:MVAL")
#! Record("CHTR:CP$(CP)2:1$(C)35:MODE_STRING",1760,2434,0,1,"CHTR:CP$(CP)2:1$(C)35:MODE_STRING")
#! Record("CHTR:CP$(CP)2:1$(C)35:SVAL",1960,2499,0,1,"CHTR:CP$(CP)2:1$(C)35:SVAL")
#! Record("CHTR:CP$(CP)2:1$(C)35:PIDTAG",1760,2582,0,1,"CHTR:CP$(CP)2:1$(C)35:PIDTAG")
#! Record("CHTR:CP$(CP)2:1$(C)35:SMOD",2864,2499,0,1,"CHTR:CP$(CP)2:1$(C)35:SMOD")
#! Record("CHTR:CP$(CP)2:1$(C)35:CMD_OUT",2860,2286,0,1,"CHTR:CP$(CP)2:1$(C)35:CMD_OUT")
#! Record("CHTR:CP$(CP)2:1$(C)35:SWITCH_DISABLE",3060,2720,0,1,"CHTR:CP$(CP)2:1$(C)35:SWITCH_DISABLE")
#! TextBox(TB0,1880,2020,2340,2240,0,"Dialog",12,1,16777215,"Generic Actuator records (DO_Record)\n- NOTE this database is the interface to the DO_Record in PLC codes\n- NOTE each of the components using this database\n             should also use the on_off_confirm database\nMode\nOverride\nInterlock status\nMode status\nText records\n\nNOTE: there are autosave info fields in this file for the \nTEXT1 and TEXT2 strings that DO NOT show in VDCT",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CSV:CP$(CP)2:1$(C)50:MMOD") {
  field(DESC, "Man. Mode status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X50.mmod")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(bi, "CSV:CP$(CP)2:1$(C)50:IMOD") {
  field(DESC, "Interlock mode")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X50.imod")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(stringin, "CSV:CP$(CP)2:1$(C)50:TEXT1") {
  field(DESC, "Notes")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  info(autosaveFields, "VAL")
}

record(stringin, "CSV:CP$(CP)2:1$(C)50:TEXT2") {
  field(DESC, "Notes")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  info(autosaveFields, "VAL")
}

record(bi, "CSV:CP$(CP)2:1$(C)50:INTERLOCK") {
  field(DESC, "interlock status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X50.Interlock_Condition")
  field(ZNAM, "ok")
  field(ONAM, "interlocked")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(bi, "CSV:CP$(CP)2:1$(C)50:IVAL") {
  field(DESC, "interlock state")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X50.ival")
  field(ZNAM, "closed")
  field(ONAM, "open")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(bi, "CSV:CP$(CP)2:1$(C)50:OUTPUT") {
  field(DESC, "actuatorDO output command")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X50.Output")
  field(ZNAM, "closed")
  field(ONAM, "open")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(bo, "CSV:CP$(CP)2:1$(C)50:MANUAL") {
  field(DESC, "Manual Mode request ")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) SV21X50.Manual B 0")
  field(ZNAM, "not manual")
  field(ONAM, "Manual")
  field(ASG, "CRYO")
  field(HIGH, "1")
  field(IVOA, "Don't drive outputs")
}

record(bo, "CSV:CP$(CP)2:1$(C)50:SEQUENCER") {
  field(DESC, "SEQ Mode request ")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) SV21X50.Sequencer B 0")
  field(ZNAM, "not sequencer")
  field(ONAM, "Sequencer")
  field(ASG, "CRYO")
  field(HIGH, "1")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CSV:CP$(CP)2:1$(C)50:MODE") {
  field(DESC, "actuator mode (man,ovr,seq)")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X50.MODE")
}

record(bi, "CSV:CP$(CP)2:1$(C)50:ALM") {
  field(DESC, "Limit SW alarm")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X50.ER")
  field(ZNAM, "ok")
  field(ONAM, "alarm")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(bi, "CSV:CP$(CP)2:1$(C)50:IL_LATCH") {
  field(DESC, "interlock latched indicator")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X50.Interlock_Condition_L")
  field(ZNAM, "ok")
  field(ONAM, "latched")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(bo, "CSV:CP$(CP)2:1$(C)50:IL_RESET") {
  field(DESC, "Interlock Latch Reset")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) SV21X50.Interlock_Condition_Reset B 0")
  field(ZNAM, "not reset")
  field(ONAM, "RESET")
  field(ASG, "CRYO")
  field(HIGH, "1")
  field(IVOA, "Don't drive outputs")
}

record(bi, "CSV:CP$(CP)2:1$(C)50:ZSH") {
  field(DESC, "High limit sw value")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X50.ZSH")
  field(ZNAM, "not active")
  field(ONAM, "active")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(bi, "CSV:CP$(CP)2:1$(C)50:ZSL") {
  field(DESC, "low limit sw value")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X50.ZSL")
  field(ZNAM, "not active")
  field(ONAM, "active")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(bi, "CSV:CP$(CP)2:1$(C)50:MVAL") {
  field(DESC, "manual mode output value")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X50.mval")
  field(ZNAM, "closed")
  field(ONAM, "open")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(stringin, "CSV:CP$(CP)2:1$(C)50:MODE_STRING") {
  field(DESC, "Actuator (DO) Mode String")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X50.Mode_String")
}

record(bi, "CSV:CP$(CP)2:1$(C)50:SVAL") {
  field(DESC, "sequencer mode output value")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X50.sval")
  field(ZNAM, "closed")
  field(ONAM, "open")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(stringin, "CSV:CP$(CP)2:1$(C)50:PIDTAG") {
  field(DESC, "Sol. valve 21$(C)50 PIDTAG")
  field(PINI, "YES")
  field(VAL, "SV21$(C)50")
}

record(bi, "CSV:CP$(CP)2:1$(C)50:SMOD") {
  field(DESC, "Sequencer mode indicator")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X50.smod")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(bi, "CSV:CP$(CP)2:1$(C)50:CMD_OUT") {
  field(DESC, "rdbk of output signal to the actuator")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X50O")
  field(ZNAM, "closed")
  field(ONAM, "open")
}

record(mbbiDirect, "CSV:CP$(CP)2:1$(C)50:SWITCH_DISABLE") {
  field(DESC, "Indicates if switch(es) are  used")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X50.Disable B 0")
  field(NOBT, "16")
}

#! Further lines contain data used by VisualDCT
#! View(1599,2252,1.0)
#! Record("CSV:CP$(CP)2:1$(C)50:MMOD",2500,2499,0,1,"CSV:CP$(CP)2:1$(C)50:MMOD")
#! Record("CSV:CP$(CP)2:1$(C)50:IMOD",2680,2499,0,1,"CSV:CP$(CP)2:1$(C)50:IMOD")
#! Record("CSV:CP$(CP)2:1$(C)50:TEXT1",1760,2682,0,1,"CSV:CP$(CP)2:1$(C)50:TEXT1")
#! Record("CSV:CP$(CP)2:1$(C)50:TEXT2",1760,2782,0,1,"CSV:CP$(CP)2:1$(C)50:TEXT2")
#! Record("CSV:CP$(CP)2:1$(C)50:INTERLOCK",2500,2719,0,1,"CSV:CP$(CP)2:1$(C)50:INTERLOCK")
#! Record("CSV:CP$(CP)2:1$(C)50:IVAL",2140,2499,0,1,"CSV:CP$(CP)2:1$(C)50:IVAL")
#! Record("CSV:CP$(CP)2:1$(C)50:OUTPUT",2680,2279,0,1,"CSV:CP$(CP)2:1$(C)50:OUTPUT")
#! Record("CSV:CP$(CP)2:1$(C)50:MANUAL",1960,2265,0,1,"CSV:CP$(CP)2:1$(C)50:MANUAL")
#! Record("CSV:CP$(CP)2:1$(C)50:SEQUENCER",2140,2265,0,1,"CSV:CP$(CP)2:1$(C)50:SEQUENCER")
#! Record("CSV:CP$(CP)2:1$(C)50:MODE",1760,2274,0,1,"CSV:CP$(CP)2:1$(C)50:MODE")
#! Record("CSV:CP$(CP)2:1$(C)50:ALM",1960,2719,0,1,"CSV:CP$(CP)2:1$(C)50:ALM")
#! Record("CSV:CP$(CP)2:1$(C)50:IL_LATCH",2320,2719,0,1,"CSV:CP$(CP)2:1$(C)50:IL_LATCH")
#! Record("CSV:CP$(CP)2:1$(C)50:IL_RESET",2140,2705,0,1,"CSV:CP$(CP)2:1$(C)50:IL_RESET")
#! Record("CSV:CP$(CP)2:1$(C)50:ZSH",2700,2719,0,1,"CSV:CP$(CP)2:1$(C)50:ZSH")
#! Record("CSV:CP$(CP)2:1$(C)50:ZSL",2880,2719,0,1,"CSV:CP$(CP)2:1$(C)50:ZSL")
#! Record("CSV:CP$(CP)2:1$(C)50:MVAL",2320,2499,0,1,"CSV:CP$(CP)2:1$(C)50:MVAL")
#! Record("CSV:CP$(CP)2:1$(C)50:MODE_STRING",1760,2434,0,1,"CSV:CP$(CP)2:1$(C)50:MODE_STRING")
#! Record("CSV:CP$(CP)2:1$(C)50:SVAL",1960,2499,0,1,"CSV:CP$(CP)2:1$(C)50:SVAL")
#! Record("CSV:CP$(CP)2:1$(C)50:PIDTAG",1760,2582,0,1,"CSV:CP$(CP)2:1$(C)50:PIDTAG")
#! Record("CSV:CP$(CP)2:1$(C)50:SMOD",2864,2499,0,1,"CSV:CP$(CP)2:1$(C)50:SMOD")
#! Record("CSV:CP$(CP)2:1$(C)50:CMD_OUT",2860,2286,0,1,"CSV:CP$(CP)2:1$(C)50:CMD_OUT")
#! Record("CSV:CP$(CP)2:1$(C)50:SWITCH_DISABLE",3060,2720,0,1,"CSV:CP$(CP)2:1$(C)50:SWITCH_DISABLE")
#! TextBox(TB0,1880,2020,2340,2240,0,"Dialog",12,1,16777215,"Generic Actuator records (DO_Record)\n- NOTE this database is the interface to the DO_Record in PLC codes\n- NOTE each of the components using this database\n             should also use the on_off_confirm database\nMode\nOverride\nInterlock status\nMode status\nText records\n\nNOTE: there are autosave info fields in this file for the \nTEXT1 and TEXT2 strings that DO NOT show in VDCT",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CSV:CP$(CP)2:1$(C)47:L:MMOD") {
  field(DESC, "Man. Mode status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X47L.mmod")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(bi, "CSV:CP$(CP)2:1$(C)47:L:IMOD") {
  field(DESC, "Interlock mode")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X47L.imod")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(stringin, "CSV:CP$(CP)2:1$(C)47:L:TEXT1") {
  field(DESC, "Notes")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  info(autosaveFields, "VAL")
}

record(stringin, "CSV:CP$(CP)2:1$(C)47:L:TEXT2") {
  field(DESC, "Notes")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  info(autosaveFields, "VAL")
}

record(bi, "CSV:CP$(CP)2:1$(C)47:L:INTERLOCK") {
  field(DESC, "interlock status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X47L.Interlock_Condition")
  field(ZNAM, "ok")
  field(ONAM, "interlocked")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(bi, "CSV:CP$(CP)2:1$(C)47:L:IVAL") {
  field(DESC, "interlock state")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X47L.ival")
  field(ZNAM, "no load")
  field(ONAM, "load")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(bi, "CSV:CP$(CP)2:1$(C)47:L:OUTPUT") {
  field(DESC, "actuatorDO output command")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X47L.Output")
  field(ZNAM, "no load")
  field(ONAM, "load")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(bo, "CSV:CP$(CP)2:1$(C)47:L:MANUAL") {
  field(DESC, "Manual Mode request ")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) SV21X47L.Manual B 0")
  field(ZNAM, "not manual")
  field(ONAM, "Manual")
  field(ASG, "CRYO")
  field(HIGH, "1")
  field(IVOA, "Don't drive outputs")
}

record(bo, "CSV:CP$(CP)2:1$(C)47:L:SEQUENCER") {
  field(DESC, "SEQ Mode request ")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) SV21X47L.Sequencer B 0")
  field(ZNAM, "not sequencer")
  field(ONAM, "Sequencer")
  field(ASG, "CRYO")
  field(HIGH, "1")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CSV:CP$(CP)2:1$(C)47:L:MODE") {
  field(DESC, "actuator mode (man,ovr,seq)")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X47L.MODE")
}

record(bi, "CSV:CP$(CP)2:1$(C)47:L:ALM") {
  field(DESC, "Limit SW alarm")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X47L.ER")
  field(ZNAM, "ok")
  field(ONAM, "alarm")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(bi, "CSV:CP$(CP)2:1$(C)47:L:IL_LATCH") {
  field(DESC, "interlock latched indicator")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X47L.Interlock_Condition_L")
  field(ZNAM, "ok")
  field(ONAM, "latched")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(bo, "CSV:CP$(CP)2:1$(C)47:L:IL_RESET") {
  field(DESC, "Interlock Latch Reset")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) SV21X47L.Interlock_Condition_Reset B 0")
  field(ZNAM, "not reset")
  field(ONAM, "RESET")
  field(ASG, "CRYO")
  field(HIGH, "1")
  field(IVOA, "Don't drive outputs")
}

record(bi, "CSV:CP$(CP)2:1$(C)47:L:ZSH") {
  field(DESC, "High limit sw value")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X47L.ZSH")
  field(ZNAM, "not active")
  field(ONAM, "active")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(bi, "CSV:CP$(CP)2:1$(C)47:L:ZSL") {
  field(DESC, "low limit sw value")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X47L.ZSL")
  field(ZNAM, "not active")
  field(ONAM, "active")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(bi, "CSV:CP$(CP)2:1$(C)47:L:MVAL") {
  field(DESC, "manual mode output value")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X47L.mval")
  field(ZNAM, "no load")
  field(ONAM, "load")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(stringin, "CSV:CP$(CP)2:1$(C)47:L:MODE_STRING") {
  field(DESC, "Actuator (DO) Mode String")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X47L.Mode_String")
}

record(bi, "CSV:CP$(CP)2:1$(C)47:L:SVAL") {
  field(DESC, "sequencer mode output value")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X47L.sval")
  field(ZNAM, "no load")
  field(ONAM, "load")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(stringin, "CSV:CP$(CP)2:1$(C)47:L:PIDTAG") {
  field(DESC, "Slide valve 21$C()47 Load PIDTAG")
  field(PINI, "YES")
  field(VAL, "SV21$(C)47")
}

record(bi, "CSV:CP$(CP)2:1$(C)47:L:SMOD") {
  field(DESC, "Sequencer mode indicator")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X47L.smod")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(bi, "CSV:CP$(CP)2:1$(C)47:L:CMD_OUT") {
  field(DESC, "rdbk of output signal to the actuator")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X47LO")
  field(ZNAM, "no load")
  field(ONAM, "load")
}

record(mbbiDirect, "CSV:CP$(CP)2:1$(C)47:L:SWITCH_DISABLE") {
  field(DESC, "Indicates if switch(es) are  used")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X47L.Disable B 0")
  field(NOBT, "16")
}

#! Further lines contain data used by VisualDCT
#! View(1599,2252,1.0)
#! Record("CSV:CP$(CP)2:1$(C)47:L:MMOD",2500,2499,0,1,"CSV:CP$(CP)2:1$(C)47:L:MMOD")
#! Record("CSV:CP$(CP)2:1$(C)47:L:IMOD",2680,2499,0,1,"CSV:CP$(CP)2:1$(C)47:L:IMOD")
#! Record("CSV:CP$(CP)2:1$(C)47:L:TEXT1",1760,2682,0,1,"CSV:CP$(CP)2:1$(C)47:L:TEXT1")
#! Record("CSV:CP$(CP)2:1$(C)47:L:TEXT2",1760,2782,0,1,"CSV:CP$(CP)2:1$(C)47:L:TEXT2")
#! Record("CSV:CP$(CP)2:1$(C)47:L:INTERLOCK",2500,2719,0,1,"CSV:CP$(CP)2:1$(C)47:L:INTERLOCK")
#! Record("CSV:CP$(CP)2:1$(C)47:L:IVAL",2140,2499,0,1,"CSV:CP$(CP)2:1$(C)47:L:IVAL")
#! Record("CSV:CP$(CP)2:1$(C)47:L:OUTPUT",2680,2279,0,1,"CSV:CP$(CP)2:1$(C)47:L:OUTPUT")
#! Record("CSV:CP$(CP)2:1$(C)47:L:MANUAL",1960,2265,0,1,"CSV:CP$(CP)2:1$(C)47:L:MANUAL")
#! Record("CSV:CP$(CP)2:1$(C)47:L:SEQUENCER",2140,2265,0,1,"CSV:CP$(CP)2:1$(C)47:L:SEQUENCER")
#! Record("CSV:CP$(CP)2:1$(C)47:L:MODE",1760,2274,0,1,"CSV:CP$(CP)2:1$(C)47:L:MODE")
#! Record("CSV:CP$(CP)2:1$(C)47:L:ALM",1960,2719,0,1,"CSV:CP$(CP)2:1$(C)47:L:ALM")
#! Record("CSV:CP$(CP)2:1$(C)47:L:IL_LATCH",2320,2719,0,1,"CSV:CP$(CP)2:1$(C)47:L:IL_LATCH")
#! Record("CSV:CP$(CP)2:1$(C)47:L:IL_RESET",2140,2705,0,1,"CSV:CP$(CP)2:1$(C)47:L:IL_RESET")
#! Record("CSV:CP$(CP)2:1$(C)47:L:ZSH",2700,2719,0,1,"CSV:CP$(CP)2:1$(C)47:L:ZSH")
#! Record("CSV:CP$(CP)2:1$(C)47:L:ZSL",2880,2719,0,1,"CSV:CP$(CP)2:1$(C)47:L:ZSL")
#! Record("CSV:CP$(CP)2:1$(C)47:L:MVAL",2320,2499,0,1,"CSV:CP$(CP)2:1$(C)47:L:MVAL")
#! Record("CSV:CP$(CP)2:1$(C)47:L:MODE_STRING",1760,2434,0,1,"CSV:CP$(CP)2:1$(C)47:L:MODE_STRING")
#! Record("CSV:CP$(CP)2:1$(C)47:L:SVAL",1960,2499,0,1,"CSV:CP$(CP)2:1$(C)47:L:SVAL")
#! Record("CSV:CP$(CP)2:1$(C)47:L:PIDTAG",1760,2582,0,1,"CSV:CP$(CP)2:1$(C)47:L:PIDTAG")
#! Record("CSV:CP$(CP)2:1$(C)47:L:SMOD",2864,2499,0,1,"CSV:CP$(CP)2:1$(C)47:L:SMOD")
#! Record("CSV:CP$(CP)2:1$(C)47:L:CMD_OUT",2860,2286,0,1,"CSV:CP$(CP)2:1$(C)47:L:CMD_OUT")
#! Record("CSV:CP$(CP)2:1$(C)47:L:SWITCH_DISABLE",3060,2720,0,1,"CSV:CP$(CP)2:1$(C)47:L:SWITCH_DISABLE")
#! TextBox(TB0,1880,2020,2340,2240,0,"Dialog",12,1,16777215,"Generic Actuator records (DO_Record)\n- NOTE this database is the interface to the DO_Record in PLC codes\n- NOTE each of the components using this database\n             should also use the on_off_confirm database\nMode\nOverride\nInterlock status\nMode status\nText records\n\nNOTE: there are autosave info fields in this file for the \nTEXT1 and TEXT2 strings that DO NOT show in VDCT",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CSV:CP$(CP)2:1$(C)47:U:MMOD") {
  field(DESC, "Man. Mode status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X47U.mmod")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(bi, "CSV:CP$(CP)2:1$(C)47:U:IMOD") {
  field(DESC, "Interlock mode")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X47U.imod")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(stringin, "CSV:CP$(CP)2:1$(C)47:U:TEXT1") {
  field(DESC, "Notes")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  info(autosaveFields, "VAL")
}

record(stringin, "CSV:CP$(CP)2:1$(C)47:U:TEXT2") {
  field(DESC, "Notes")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  info(autosaveFields, "VAL")
}

record(bi, "CSV:CP$(CP)2:1$(C)47:U:INTERLOCK") {
  field(DESC, "interlock status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X47U.Interlock_Condition")
  field(ZNAM, "ok")
  field(ONAM, "interlocked")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(bi, "CSV:CP$(CP)2:1$(C)47:U:IVAL") {
  field(DESC, "interlock state")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X47U.ival")
  field(ZNAM, "no unload")
  field(ONAM, "unload")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(bi, "CSV:CP$(CP)2:1$(C)47:U:OUTPUT") {
  field(DESC, "actuatorDO output command")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X47U.Output")
  field(ZNAM, "no unload")
  field(ONAM, "unload")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(bo, "CSV:CP$(CP)2:1$(C)47:U:MANUAL") {
  field(DESC, "Manual Mode request ")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) SV21X47U.Manual B 0")
  field(ZNAM, "not manual")
  field(ONAM, "Manual")
  field(ASG, "CRYO")
  field(HIGH, "1")
  field(IVOA, "Don't drive outputs")
}

record(bo, "CSV:CP$(CP)2:1$(C)47:U:SEQUENCER") {
  field(DESC, "SEQ Mode request ")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) SV21X47U.Sequencer B 0")
  field(ZNAM, "not sequencer")
  field(ONAM, "Sequencer")
  field(ASG, "CRYO")
  field(HIGH, "1")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CSV:CP$(CP)2:1$(C)47:U:MODE") {
  field(DESC, "actuator mode (man,ovr,seq)")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X47U.MODE")
}

record(bi, "CSV:CP$(CP)2:1$(C)47:U:ALM") {
  field(DESC, "Limit SW alarm")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X47U.ER")
  field(ZNAM, "ok")
  field(ONAM, "alarm")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(bi, "CSV:CP$(CP)2:1$(C)47:U:IL_LATCH") {
  field(DESC, "interlock latched indicator")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X47U.Interlock_Condition_L")
  field(ZNAM, "ok")
  field(ONAM, "latched")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(bo, "CSV:CP$(CP)2:1$(C)47:U:IL_RESET") {
  field(DESC, "Interlock Latch Reset")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) SV21X47U.Interlock_Condition_Reset B 0")
  field(ZNAM, "not reset")
  field(ONAM, "RESET")
  field(ASG, "CRYO")
  field(HIGH, "1")
  field(IVOA, "Don't drive outputs")
}

record(bi, "CSV:CP$(CP)2:1$(C)47:U:ZSH") {
  field(DESC, "High limit sw value")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X47U.ZSH")
  field(ZNAM, "not active")
  field(ONAM, "active")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(bi, "CSV:CP$(CP)2:1$(C)47:U:ZSL") {
  field(DESC, "low limit sw value")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X47U.ZSL")
  field(ZNAM, "not active")
  field(ONAM, "active")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(bi, "CSV:CP$(CP)2:1$(C)47:U:MVAL") {
  field(DESC, "manual mode output value")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X47U.mval")
  field(ZNAM, "no unload")
  field(ONAM, "unload")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(stringin, "CSV:CP$(CP)2:1$(C)47:U:MODE_STRING") {
  field(DESC, "Actuator (DO) Mode String")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X47U.Mode_String")
}

record(bi, "CSV:CP$(CP)2:1$(C)47:U:SVAL") {
  field(DESC, "sequencer mode output value")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X47U.sval")
  field(ZNAM, "no unload")
  field(ONAM, "unload")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(stringin, "CSV:CP$(CP)2:1$(C)47:U:PIDTAG") {
  field(DESC, "Slide valve 21$(C)47 Unload PIDTAG")
  field(PINI, "YES")
  field(VAL, "SV21$(C)47")
}

record(bi, "CSV:CP$(CP)2:1$(C)47:U:SMOD") {
  field(DESC, "Sequencer mode indicator")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X47U.smod")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(bi, "CSV:CP$(CP)2:1$(C)47:U:CMD_OUT") {
  field(DESC, "rdbk of output signal to the actuator")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X47UO")
  field(ZNAM, "no unload")
  field(ONAM, "unload")
}

record(mbbiDirect, "CSV:CP$(CP)2:1$(C)47:U:SWITCH_DISABLE") {
  field(DESC, "Indicates if switch(es) are  used")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SV21X47U.Disable B 0")
  field(NOBT, "16")
}

#! Further lines contain data used by VisualDCT
#! View(1599,2252,1.0)
#! Record("CSV:CP$(CP)2:1$(C)47:U:MMOD",2500,2499,0,1,"CSV:CP$(CP)2:1$(C)47:U:MMOD")
#! Record("CSV:CP$(CP)2:1$(C)47:U:IMOD",2680,2499,0,1,"CSV:CP$(CP)2:1$(C)47:U:IMOD")
#! Record("CSV:CP$(CP)2:1$(C)47:U:TEXT1",1760,2682,0,1,"CSV:CP$(CP)2:1$(C)47:U:TEXT1")
#! Record("CSV:CP$(CP)2:1$(C)47:U:TEXT2",1760,2782,0,1,"CSV:CP$(CP)2:1$(C)47:U:TEXT2")
#! Record("CSV:CP$(CP)2:1$(C)47:U:INTERLOCK",2500,2719,0,1,"CSV:CP$(CP)2:1$(C)47:U:INTERLOCK")
#! Record("CSV:CP$(CP)2:1$(C)47:U:IVAL",2140,2499,0,1,"CSV:CP$(CP)2:1$(C)47:U:IVAL")
#! Record("CSV:CP$(CP)2:1$(C)47:U:OUTPUT",2680,2279,0,1,"CSV:CP$(CP)2:1$(C)47:U:OUTPUT")
#! Record("CSV:CP$(CP)2:1$(C)47:U:MANUAL",1960,2265,0,1,"CSV:CP$(CP)2:1$(C)47:U:MANUAL")
#! Record("CSV:CP$(CP)2:1$(C)47:U:SEQUENCER",2140,2265,0,1,"CSV:CP$(CP)2:1$(C)47:U:SEQUENCER")
#! Record("CSV:CP$(CP)2:1$(C)47:U:MODE",1760,2274,0,1,"CSV:CP$(CP)2:1$(C)47:U:MODE")
#! Record("CSV:CP$(CP)2:1$(C)47:U:ALM",1960,2719,0,1,"CSV:CP$(CP)2:1$(C)47:U:ALM")
#! Record("CSV:CP$(CP)2:1$(C)47:U:IL_LATCH",2320,2719,0,1,"CSV:CP$(CP)2:1$(C)47:U:IL_LATCH")
#! Record("CSV:CP$(CP)2:1$(C)47:U:IL_RESET",2140,2705,0,1,"CSV:CP$(CP)2:1$(C)47:U:IL_RESET")
#! Record("CSV:CP$(CP)2:1$(C)47:U:ZSH",2700,2719,0,1,"CSV:CP$(CP)2:1$(C)47:U:ZSH")
#! Record("CSV:CP$(CP)2:1$(C)47:U:ZSL",2880,2719,0,1,"CSV:CP$(CP)2:1$(C)47:U:ZSL")
#! Record("CSV:CP$(CP)2:1$(C)47:U:MVAL",2320,2499,0,1,"CSV:CP$(CP)2:1$(C)47:U:MVAL")
#! Record("CSV:CP$(CP)2:1$(C)47:U:MODE_STRING",1760,2434,0,1,"CSV:CP$(CP)2:1$(C)47:U:MODE_STRING")
#! Record("CSV:CP$(CP)2:1$(C)47:U:SVAL",1960,2499,0,1,"CSV:CP$(CP)2:1$(C)47:U:SVAL")
#! Record("CSV:CP$(CP)2:1$(C)47:U:PIDTAG",1760,2582,0,1,"CSV:CP$(CP)2:1$(C)47:U:PIDTAG")
#! Record("CSV:CP$(CP)2:1$(C)47:U:SMOD",2864,2499,0,1,"CSV:CP$(CP)2:1$(C)47:U:SMOD")
#! Record("CSV:CP$(CP)2:1$(C)47:U:CMD_OUT",2860,2286,0,1,"CSV:CP$(CP)2:1$(C)47:U:CMD_OUT")
#! Record("CSV:CP$(CP)2:1$(C)47:U:SWITCH_DISABLE",3060,2720,0,1,"CSV:CP$(CP)2:1$(C)47:U:SWITCH_DISABLE")
#! TextBox(TB0,1880,2020,2340,2240,0,"Dialog",12,1,16777215,"Generic Actuator records (DO_Record)\n- NOTE this database is the interface to the DO_Record in PLC codes\n- NOTE each of the components using this database\n             should also use the on_off_confirm database\nMode\nOverride\nInterlock status\nMode status\nText records\n\nNOTE: there are autosave info fields in this file for the \nTEXT1 and TEXT2 strings that DO NOT show in VDCT",null)
#
record(stringin, "WCMP:CP$(CP)2:1$(C):SD_STRING") {
  field(DESC, "Shutdown status string")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Compressor_Shutdown_String")
}

record(ai, "WCMP:CP$(CP)2:1$(C):STATUS_INT") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Comp_Process_Status")
  field(EGU, "s")
  field(DESC, "Wcmp process status int")
  field(PREC, "2")
  field(ADEL, "0")
  field(PINI, "YES")
}

record(bo, "CMCC:CP$(CP)2:1$(C):ALM_DIS") {
  field(DESC, "MCC alarm latch reset")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) MCCALM21X_DIS B 0")
  field(ZNAM, "A")
  field(ONAM, "I")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(HIGH, "0")
  field(OMSL, "supervisory")
}

record(bo, "WCMP:CP$(CP)2:1$(C):RESET") {
  field(DESC, "Compressor Reset Rqst")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) Compressor_Reset_X B 0")
  field(ZNAM, "disabled")
  field(ONAM, "enabled")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(HIGH, "1")
}

record(stringin, "WCMP:CP$(CP)2:1$(C):SEQ_STRING") {
  field(DESC, "Sequence status string")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Compressor_Sequence_String")
}

record(ai, "WCMP:CP$(CP)2:1$(C):SD_INT") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Compressor_SD_Trigger")
  field(DESC, "Wcmp shutdown integer")
  field(PREC, "0")
  field(ADEL, "0")
  field(PINI, "YES")
}
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CPMP:CP$(CP)2:1$(C):PIDTAG") {
  field(DESC, "STATUS P&IDname")
  field(PINI, "YES")
  field(VAL, "PMP21$(C)")
}


record(bi, "CPMP:CP$(CP)2:1$(C):STATUS") {
  field(DESC, "Oil Pump on/off status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) OP21X")
  field(ZNAM, "off")
  field(ONAM, "on")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CPMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"CPMP:CP$(CP)2:1$(C):PIDTAG")
#! Record("CPMP:CP$(CP)2:1$(C):STATUS",2054,2119,0,1,"CPMP:CP$(CP)2:1$(C):STATUS")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CPMP:CP$(CP)2:1$(C):PIDTAG") {
  field(DESC, "CMD_OUT P&IDname")
  field(PINI, "YES")
  field(VAL, "PMP21$(C)")
}


record(bi, "CPMP:CP$(CP)2:1$(C):CMD_OUT") {
  field(DESC, "Oil Pump on/off Command")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) OPVFD21XO")
  field(ZNAM, "off")
  field(ONAM, "on")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CPMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"CPMP:CP$(CP)2:1$(C):PIDTAG")
#! Record("CPMP:CP$(CP)2:1$(C):CMD_OUT",2054,2119,0,1,"CPMP:CP$(CP)2:1$(C):CMD_OUT")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CPMP:CP$(CP)2:1$(C):PIDTAG") {
  field(DESC, "VFD_FAULT P&IDname")
  field(PINI, "YES")
  field(VAL, "PMP21$(C)")
}


record(bi, "CPMP:CP$(CP)2:1$(C):VFD_FAULT") {
  field(DESC, "Oil Pump VFD Fault")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) OPVFD21XFLT")
  field(ZNAM, "fault")
  field(ONAM, "ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CPMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"CPMP:CP$(CP)2:1$(C):PIDTAG")
#! Record("CPMP:CP$(CP)2:1$(C):VFD_FAULT",2054,2119,0,1,"CPMP:CP$(CP)2:1$(C):VFD_FAULT")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "COHC:CP$(CP)2:1$(C)35:PIDTAG") {
  field(DESC, "CONTACTOR P&IDname")
  field(PINI, "YES")
  field(VAL, "OHC21$(C)35")
}


record(bi, "COHC:CP$(CP)2:1$(C)35:CONTACTOR") {
  field(DESC, "Oil Heater Contactor")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) OHC21X35")
  field(ZNAM, "off")
  field(ONAM, "on")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("COHC:CP$(CP)2:1$(C)35:PIDTAG",2054,2322,0,1,"COHC:CP$(CP)2:1$(C)35:PIDTAG")
#! Record("COHC:CP$(CP)2:1$(C)35:CONTACTOR",2054,2119,0,1,"COHC:CP$(CP)2:1$(C)35:CONTACTOR")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CMCC:CP$(CP)2:1$(C):PIDTAG") {
  field(DESC, "ALM P&IDname")
  field(PINI, "YES")
  field(VAL, "MCC21$(C)")
}


record(bi, "CMCC:CP$(CP)2:1$(C):ALM") {
  field(DESC, "MCC Alarm")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) MCCALM21X")
  field(ZNAM, "fault")
  field(ONAM, "ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CMCC:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"CMCC:CP$(CP)2:1$(C):PIDTAG")
#! Record("CMCC:CP$(CP)2:1$(C):ALM",2054,2119,0,1,"CMCC:CP$(CP)2:1$(C):ALM")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CMCC:CP$(CP)2:1$(C):PIDTAG") {
  field(DESC, "ALM_L P&IDname")
  field(PINI, "YES")
  field(VAL, "MCC21$(C)")
}


record(bi, "CMCC:CP$(CP)2:1$(C):ALM_L") {
  field(DESC, "MCC Alarm Latch")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) MCCALM21XL")
  field(ZNAM, "latched")
  field(ONAM, "off")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CMCC:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"CMCC:CP$(CP)2:1$(C):PIDTAG")
#! Record("CMCC:CP$(CP)2:1$(C):ALM_L",2054,2119,0,1,"CMCC:CP$(CP)2:1$(C):ALM_L")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "WCMP:CP$(CP)2:1$(C):PIDTAG") {
  field(DESC, "STATUS P&IDname")
  field(PINI, "YES")
  field(VAL, "WCMP21$(C)")
}


record(bi, "WCMP:CP$(CP)2:1$(C):STATUS") {
  field(DESC, "WCMP on/off status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) CO21X")
  field(ZNAM, "off")
  field(ONAM, "on")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("WCMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"WCMP:CP$(CP)2:1$(C):PIDTAG")
#! Record("WCMP:CP$(CP)2:1$(C):STATUS",2054,2119,0,1,"WCMP:CP$(CP)2:1$(C):STATUS")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "WCMP:CP$(CP)2:1$(C):PIDTAG") {
  field(DESC, "CMD_OUT P&IDname")
  field(PINI, "YES")
  field(VAL, "WCMP21$(C)")
}


record(bi, "WCMP:CP$(CP)2:1$(C):CMD_OUT") {
  field(DESC, "WCMP on/off Command")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) SO21XO")
  field(ZNAM, "off")
  field(ONAM, "on")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("WCMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"WCMP:CP$(CP)2:1$(C):PIDTAG")
#! Record("WCMP:CP$(CP)2:1$(C):CMD_OUT",2054,2119,0,1,"WCMP:CP$(CP)2:1$(C):CMD_OUT")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "WCMP:CP$(CP)2:1$(C):PIDTAG") {
  field(DESC, "RED_ALM P&IDname")
  field(PINI, "YES")
  field(VAL, "WCMP21$(C)")
}


record(bi, "WCMP:CP$(CP)2:1$(C):RED_ALM") {
  field(DESC, "WCMP red alarm")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) COMP21X_RedALM")
  field(ZNAM, "ok")
  field(ONAM, "alarm")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("WCMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"WCMP:CP$(CP)2:1$(C):PIDTAG")
#! Record("WCMP:CP$(CP)2:1$(C):RED_ALM",2054,2119,0,1,"WCMP:CP$(CP)2:1$(C):RED_ALM")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "WCMP:CP$(CP)2:1$(C):PIDTAG") {
  field(DESC, "START_FLT P&IDname")
  field(PINI, "YES")
  field(VAL, "WCMP21$(C)")
}


record(bi, "WCMP:CP$(CP)2:1$(C):START_FLT") {
  field(DESC, "WCMP starter fault")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) OL21X")
  field(ZNAM, "fault")
  field(ONAM, "ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("WCMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"WCMP:CP$(CP)2:1$(C):PIDTAG")
#! Record("WCMP:CP$(CP)2:1$(C):START_FLT",2054,2119,0,1,"WCMP:CP$(CP)2:1$(C):START_FLT")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "WCMP:CP$(CP)2:1$(C):PIDTAG") {
  field(DESC, "ESTOP P&IDname")
  field(PINI, "YES")
  field(VAL, "WCMP21$(C)")
}


record(bi, "WCMP:CP$(CP)2:1$(C):ESTOP") {
  field(DESC, "WCMP ESTOP active")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) ES21X")
  field(ZNAM, "fault")
  field(ONAM, "ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("WCMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"WCMP:CP$(CP)2:1$(C):PIDTAG")
#! Record("WCMP:CP$(CP)2:1$(C):ESTOP",2054,2119,0,1,"WCMP:CP$(CP)2:1$(C):ESTOP")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "WCMP:CP$(CP)2:1$(C):PIDTAG") {
  field(DESC, "LR_MODE P&IDname")
  field(PINI, "YES")
  field(VAL, "WCMP21$(C)")
}


record(bi, "WCMP:CP$(CP)2:1$(C):LR_MODE") {
  field(DESC, "WCMP Local/Remote")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) LR21X")
  field(ZNAM, "REMOTE")
  field(ONAM, "LOCAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("WCMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"WCMP:CP$(CP)2:1$(C):PIDTAG")
#! Record("WCMP:CP$(CP)2:1$(C):LR_MODE",2054,2119,0,1,"WCMP:CP$(CP)2:1$(C):LR_MODE")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "WCMP:CP$(CP)2:1$(C):PIDTAG") {
  field(DESC, "LDNG_ALLWD P&IDname")
  field(PINI, "YES")
  field(VAL, "WCMP21$(C)")
}


record(bi, "WCMP:CP$(CP)2:1$(C):LDNG_ALLWD") {
  field(DESC, "WCMP loading")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Loading_Allowed")
  field(ZNAM, "Loading not allowed")
  field(ONAM, "Loading ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("WCMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"WCMP:CP$(CP)2:1$(C):PIDTAG")
#! Record("WCMP:CP$(CP)2:1$(C):LDNG_ALLWD",2054,2119,0,1,"WCMP:CP$(CP)2:1$(C):LDNG_ALLWD")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "WCMP:CP$(CP)2:1$(C):PIDTAG") {
  field(DESC, "START_PERM P&IDname")
  field(PINI, "YES")
  field(VAL, "WCMP21$(C)")
}


record(bi, "WCMP:CP$(CP)2:1$(C):START_PERM") {
  field(DESC, "WCMP start permissive")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Start_Comp_Permissive")
  field(ZNAM, "not permitted")
  field(ONAM, "permitted")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("WCMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"WCMP:CP$(CP)2:1$(C):PIDTAG")
#! Record("WCMP:CP$(CP)2:1$(C):START_PERM",2054,2119,0,1,"WCMP:CP$(CP)2:1$(C):START_PERM")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "WCMP:CP$(CP)2:1$(C):PIDTAG") {
  field(DESC, "STOP_PERM P&IDname")
  field(PINI, "YES")
  field(VAL, "WCMP21$(C)")
}


record(bi, "WCMP:CP$(CP)2:1$(C):STOP_PERM") {
  field(DESC, "WCMP stop permissive")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Stop_Comp_Permissive")
  field(ZNAM, "not permitted")
  field(ONAM, "permitted")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("WCMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"WCMP:CP$(CP)2:1$(C):PIDTAG")
#! Record("WCMP:CP$(CP)2:1$(C):STOP_PERM",2054,2119,0,1,"WCMP:CP$(CP)2:1$(C):STOP_PERM")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CPMP:CP$(CP)2:1$(C):PIDTAG") {
  field(DESC, "START_PERM P&IDname")
  field(PINI, "YES")
  field(VAL, "PMP21$(C)")
}


record(bi, "CPMP:CP$(CP)2:1$(C):START_PERM") {
  field(DESC, "Pump start permissive")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Start_Pump_Permissive")
  field(ZNAM, "not permitted")
  field(ONAM, "permitted")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CPMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"CPMP:CP$(CP)2:1$(C):PIDTAG")
#! Record("CPMP:CP$(CP)2:1$(C):START_PERM",2054,2119,0,1,"CPMP:CP$(CP)2:1$(C):START_PERM")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CPMP:CP$(CP)2:1$(C):PIDTAG") {
  field(DESC, "STOP_PERM P&IDname")
  field(PINI, "YES")
  field(VAL, "PMP21$(C)")
}


record(bi, "CPMP:CP$(CP)2:1$(C):STOP_PERM") {
  field(DESC, "Pump stop permissive")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Stop_Pump_Permissive")
  field(ZNAM, "not permitted")
  field(ONAM, "permitted")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CPMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"CPMP:CP$(CP)2:1$(C):PIDTAG")
#! Record("CPMP:CP$(CP)2:1$(C):STOP_PERM",2054,2119,0,1,"CPMP:CP$(CP)2:1$(C):STOP_PERM")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "WCMP:CP$(CP)2:1$(C):PIDTAG") {
  field(DESC, "C900_TRIP P&IDname")
  field(PINI, "YES")
  field(VAL, "WCMP21$(C)")
}


record(bi, "WCMP:CP$(CP)2:1$(C):C900_TRIP") {
  field(DESC, "WCMP status trip")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) C900_Trip_Condition")
  field(ZNAM, "ok")
  field(ONAM, "TRIP")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("WCMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"WCMP:CP$(CP)2:1$(C):PIDTAG")
#! Record("WCMP:CP$(CP)2:1$(C):C900_TRIP",2054,2119,0,1,"WCMP:CP$(CP)2:1$(C):C900_TRIP")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "WCMP:CP$(CP)2:1$(C):PIDTAG") {
  field(DESC, "DP1_TRIP P&IDname")
  field(PINI, "YES")
  field(VAL, "WCMP21$(C)")
}


record(bi, "WCMP:CP$(CP)2:1$(C):DP1_TRIP") {
  field(DESC, "Oil Pump DP failed 1")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Oil_Pump_Fail_1")
  field(ZNAM, "ok")
  field(ONAM, "TRIP")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("WCMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"WCMP:CP$(CP)2:1$(C):PIDTAG")
#! Record("WCMP:CP$(CP)2:1$(C):DP1_TRIP",2054,2119,0,1,"WCMP:CP$(CP)2:1$(C):DP1_TRIP")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "WCMP:CP$(CP)2:1$(C):PIDTAG") {
  field(DESC, "DP2_TRIP P&IDname")
  field(PINI, "YES")
  field(VAL, "WCMP21$(C)")
}


record(bi, "WCMP:CP$(CP)2:1$(C):DP2_TRIP") {
  field(DESC, "Oil Pump DP failed 2")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Oil_Pump_Fail_2")
  field(ZNAM, "ok")
  field(ONAM, "TRIP")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("WCMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"WCMP:CP$(CP)2:1$(C):PIDTAG")
#! Record("WCMP:CP$(CP)2:1$(C):DP2_TRIP",2054,2119,0,1,"WCMP:CP$(CP)2:1$(C):DP2_TRIP")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "WCMP:CP$(CP)2:1$(C):PIDTAG") {
  field(DESC, "UNL_TRIP P&IDname")
  field(PINI, "YES")
  field(VAL, "WCMP21$(C)")
}


record(bi, "WCMP:CP$(CP)2:1$(C):UNL_TRIP") {
  field(DESC, "Compressor unload failed")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Comp_Unload_Fail")
  field(ZNAM, "ok")
  field(ONAM, "TRIP")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("WCMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"WCMP:CP$(CP)2:1$(C):PIDTAG")
#! Record("WCMP:CP$(CP)2:1$(C):UNL_TRIP",2054,2119,0,1,"WCMP:CP$(CP)2:1$(C):UNL_TRIP")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "WCMP:CP$(CP)2:1$(C):PIDTAG") {
  field(DESC, "MTR1_TRIP P&IDname")
  field(PINI, "YES")
  field(VAL, "WCMP21$(C)")
}


record(bi, "WCMP:CP$(CP)2:1$(C):MTR1_TRIP") {
  field(DESC, "Motor start fault 1")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Motor_Start_Fault")
  field(ZNAM, "ok")
  field(ONAM, "TRIP")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("WCMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"WCMP:CP$(CP)2:1$(C):PIDTAG")
#! Record("WCMP:CP$(CP)2:1$(C):MTR1_TRIP",2054,2119,0,1,"WCMP:CP$(CP)2:1$(C):MTR1_TRIP")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "WCMP:CP$(CP)2:1$(C):PIDTAG") {
  field(DESC, "CMP_STAT_TRIP P&IDname")
  field(PINI, "YES")
  field(VAL, "WCMP21$(C)")
}


record(bi, "WCMP:CP$(CP)2:1$(C):CMP_STAT_TRIP") {
  field(DESC, "Compressor status trip")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Comp_Status_Trip")
  field(ZNAM, "ok")
  field(ONAM, "TRIP")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("WCMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"WCMP:CP$(CP)2:1$(C):PIDTAG")
#! Record("WCMP:CP$(CP)2:1$(C):CMP_STAT_TRIP",2054,2119,0,1,"WCMP:CP$(CP)2:1$(C):CMP_STAT_TRIP")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "WCMP:CP$(CP)2:1$(C):PIDTAG") {
  field(DESC, "OP_STAT_TRIP P&IDname")
  field(PINI, "YES")
  field(VAL, "WCMP21$(C)")
}


record(bi, "WCMP:CP$(CP)2:1$(C):OP_STAT_TRIP") {
  field(DESC, "Oil Pump status trip")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) OP_Status_Trip")
  field(ZNAM, "ok")
  field(ONAM, "TRIP")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("WCMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"WCMP:CP$(CP)2:1$(C):PIDTAG")
#! Record("WCMP:CP$(CP)2:1$(C):OP_STAT_TRIP",2054,2119,0,1,"WCMP:CP$(CP)2:1$(C):OP_STAT_TRIP")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "WCMP:CP$(CP)2:1$(C):PIDTAG") {
  field(DESC, "OIL_DP_TRIP P&IDname")
  field(PINI, "YES")
  field(VAL, "WCMP21$(C)")
}


record(bi, "WCMP:CP$(CP)2:1$(C):OIL_DP_TRIP") {
  field(DESC, "Low Oil DiffPress trip")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Oil_DP_Trip")
  field(ZNAM, "ok")
  field(ONAM, "TRIP")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("WCMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"WCMP:CP$(CP)2:1$(C):PIDTAG")
#! Record("WCMP:CP$(CP)2:1$(C):OIL_DP_TRIP",2054,2119,0,1,"WCMP:CP$(CP)2:1$(C):OIL_DP_TRIP")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "WCMP:CP$(CP)2:1$(C):PIDTAG") {
  field(DESC, "OP_DISPR_TRIP P&IDname")
  field(PINI, "YES")
  field(VAL, "WCMP21$(C)")
}


record(bi, "WCMP:CP$(CP)2:1$(C):OP_DISPR_TRIP") {
  field(DESC, "Oil Pump Disch Press trip")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) OP_Dis_Pr_Trip")
  field(ZNAM, "ok")
  field(ONAM, "TRIP")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("WCMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"WCMP:CP$(CP)2:1$(C):PIDTAG")
#! Record("WCMP:CP$(CP)2:1$(C):OP_DISPR_TRIP",2054,2119,0,1,"WCMP:CP$(CP)2:1$(C):OP_DISPR_TRIP")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "WCMP:CP$(CP)2:1$(C):PIDTAG") {
  field(DESC, "C100_ALARM P&IDname")
  field(PINI, "YES")
  field(VAL, "WCMP21$(C)")
}


record(bi, "WCMP:CP$(CP)2:1$(C):C100_ALARM") {
  field(DESC, "WCMP summary alarm")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) C100_CMP21X_ALARM")
  field(ZNAM, "ok")
  field(ONAM, "ALARM")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("WCMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"WCMP:CP$(CP)2:1$(C):PIDTAG")
#! Record("WCMP:CP$(CP)2:1$(C):C100_ALARM",2054,2119,0,1,"WCMP:CP$(CP)2:1$(C):C100_ALARM")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../dbd/cryoTest.dbd")
#! DBDEND


record(ao, "WCMP:CP$(CP)2:1$(C)0:SV_SET") {
  field(DESC, "Suction Pressure To Load")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(PREC, "2")
  field(EGU, "bara")
  field(ADEL, "0.01")
  field(IVOA, "Don't drive outputs")
  field(OUT, "@$(PLC_NAME) Suction_Pressure")
}

record(stringin, "WCMP:CP$(CP)2:1$(C)0:PIDTAG") {
  field(DESC, "SV_SET PIDtag")
  field(PINI, "YES")
  field(VAL, "")
}

#! Further lines contain data used by VisualDCT
#! View(1774,1984,1.0)
#! Record("WCMP:CP$(CP)2:1$(C)0:SV_SET",2060,2119,0,1,"WCMP:CP$(CP)2:1$(C)0:SV_SET")
#! Record("WCMP:CP$(CP)2:1$(C)0:PIDTAG",2340,2142,0,1,"WCMP:CP$(CP)2:1$(C)0:PIDTAG")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../dbd/cryoTest.dbd")
#! DBDEND


record(ao, "WCMP:CP$(CP)2:2$(C)0:SV_SET") {
  field(DESC, "Discharge Pressure To Load")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(PREC, "2")
  field(EGU, "bara")
  field(ADEL, "0.01")
  field(IVOA, "Don't drive outputs")
  field(OUT, "@$(PLC_NAME) Discharge_Pressure")
}

record(stringin, "WCMP:CP$(CP)2:2$(C)0:PIDTAG") {
  field(DESC, "SV_SET PIDtag")
  field(PINI, "YES")
  field(VAL, "")
}

#! Further lines contain data used by VisualDCT
#! View(1774,1984,1.0)
#! Record("WCMP:CP$(CP)2:2$(C)0:SV_SET",2060,2119,0,1,"WCMP:CP$(CP)2:2$(C)0:SV_SET")
#! Record("WCMP:CP$(CP)2:2$(C)0:PIDTAG",2340,2142,0,1,"WCMP:CP$(CP)2:2$(C)0:PIDTAG")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../dbd/cryoTest.dbd")
#! DBDEND


record(ao, "WCMP:CP$(CP)2:3$(C)0:SV_SET") {
  field(DESC, "Slide Valve % To Load")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(PREC, "2")
  field(EGU, "%")
  field(ADEL, "0.01")
  field(IVOA, "Don't drive outputs")
  field(OUT, "@$(PLC_NAME) Slide_Valve_Load")
}

record(stringin, "WCMP:CP$(CP)2:3$(C)0:PIDTAG") {
  field(DESC, "SV_SET PIDtag")
  field(PINI, "YES")
  field(VAL, "")
}

#! Further lines contain data used by VisualDCT
#! View(1774,1984,1.0)
#! Record("WCMP:CP$(CP)2:3$(C)0:SV_SET",2060,2119,0,1,"WCMP:CP$(CP)2:3$(C)0:SV_SET")
#! Record("WCMP:CP$(CP)2:3$(C)0:PIDTAG",2340,2142,0,1,"WCMP:CP$(CP)2:3$(C)0:PIDTAG")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../dbd/cryoTest.dbd")
#! DBDEND


record(ao, "WCMP:CP$(CP)2:4$(C)0:SV_SET") {
  field(DESC, "Slide Valve % To Unload")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(PREC, "2")
  field(EGU, "%")
  field(ADEL, "0.01")
  field(IVOA, "Don't drive outputs")
  field(OUT, "@$(PLC_NAME) Slide_Valve_Unload")
}

record(stringin, "WCMP:CP$(CP)2:4$(C)0:PIDTAG") {
  field(DESC, "SV_SET PIDtag")
  field(PINI, "YES")
  field(VAL, "")
}

#! Further lines contain data used by VisualDCT
#! View(1774,1984,1.0)
#! Record("WCMP:CP$(CP)2:4$(C)0:SV_SET",2060,2119,0,1,"WCMP:CP$(CP)2:4$(C)0:SV_SET")
#! Record("WCMP:CP$(CP)2:4$(C)0:PIDTAG",2340,2142,0,1,"WCMP:CP$(CP)2:4$(C)0:PIDTAG")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../dbd/cryoTest.dbd")
#! DBDEND


record(ao, "WCMP:CP$(CP)2:5$(C)0:SV_SET") {
  field(DESC, "Bypass Valve % To Load")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(PREC, "2")
  field(EGU, "%")
  field(ADEL, "0.01")
  field(IVOA, "Don't drive outputs")
  field(OUT, "@$(PLC_NAME) Bypass_Valve_Position_Load")
}

record(stringin, "WCMP:CP$(CP)2:5$(C)0:PIDTAG") {
  field(DESC, "SV_SET PIDtag")
  field(PINI, "YES")
  field(VAL, "")
}

#! Further lines contain data used by VisualDCT
#! View(1774,1984,1.0)
#! Record("WCMP:CP$(CP)2:5$(C)0:SV_SET",2060,2119,0,1,"WCMP:CP$(CP)2:5$(C)0:SV_SET")
#! Record("WCMP:CP$(CP)2:5$(C)0:PIDTAG",2340,2142,0,1,"WCMP:CP$(CP)2:5$(C)0:PIDTAG")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../dbd/cryoTest.dbd")
#! DBDEND


record(ao, "WCMP:CP$(CP)2:6$(C)0:SV_SET") {
  field(DESC, "Bypass Valve % To Unload")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(PREC, "2")
  field(EGU, "%")
  field(ADEL, "0.01")
  field(IVOA, "Don't drive outputs")
  field(OUT, "@$(PLC_NAME) Bypass_Valve_Position_Unload")
}

record(stringin, "WCMP:CP$(CP)2:6$(C)0:PIDTAG") {
  field(DESC, "SV_SET PIDtag")
  field(PINI, "YES")
  field(VAL, "")
}

#! Further lines contain data used by VisualDCT
#! View(1774,1984,1.0)
#! Record("WCMP:CP$(CP)2:6$(C)0:SV_SET",2060,2119,0,1,"WCMP:CP$(CP)2:6$(C)0:SV_SET")
#! Record("WCMP:CP$(CP)2:6$(C)0:PIDTAG",2340,2142,0,1,"WCMP:CP$(CP)2:6$(C)0:PIDTAG")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../dbd/cryoTest.dbd")
#! DBDEND


record(ao, "WCMP:CP$(CP)2:7$(C)0:SV_SET") {
  field(DESC, "Compressor Number")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(PREC, "0")
  field(EGU, "")
  field(ADEL, "0.01")
  field(IVOA, "Don't drive outputs")
  field(OUT, "@$(PLC_NAME) Compressor_Number")
}

record(stringin, "WCMP:CP$(CP)2:7$(C)0:PIDTAG") {
  field(DESC, "SV_SET PIDtag")
  field(PINI, "YES")
  field(VAL, "")
}

#! Further lines contain data used by VisualDCT
#! View(1774,1984,1.0)
#! Record("WCMP:CP$(CP)2:7$(C)0:SV_SET",2060,2119,0,1,"WCMP:CP$(CP)2:7$(C)0:SV_SET")
#! Record("WCMP:CP$(CP)2:7$(C)0:PIDTAG",2340,2142,0,1,"WCMP:CP$(CP)2:7$(C)0:PIDTAG")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../dbd/cryoTest.dbd")
#! DBDEND


record(ao, "WCMP:CP$(CP)2:8$(C)0:SV_SET") {
  field(DESC, "Oil DP Target 2")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(PREC, "2")
  field(EGU, "bara")
  field(ADEL, "0.01")
  field(IVOA, "Don't drive outputs")
  field(OUT, "@$(PLC_NAME) Oil_DP_Target2")
}

record(stringin, "WCMP:CP$(CP)2:8$(C)0:PIDTAG") {
  field(DESC, "SV_SET PIDtag")
  field(PINI, "YES")
  field(VAL, "")
}

#! Further lines contain data used by VisualDCT
#! View(1774,1984,1.0)
#! Record("WCMP:CP$(CP)2:8$(C)0:SV_SET",2060,2119,0,1,"WCMP:CP$(CP)2:8$(C)0:SV_SET")
#! Record("WCMP:CP$(CP)2:8$(C)0:PIDTAG",2340,2142,0,1,"WCMP:CP$(CP)2:8$(C)0:PIDTAG")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../dbd/cryoTest.dbd")
#! DBDEND


record(ao, "WCMP:CP$(CP)2:9$(C)0:SV_SET") {
  field(DESC, "Dis Press For Loading")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(PREC, "2")
  field(EGU, "bara")
  field(ADEL, "0.01")
  field(IVOA, "Don't drive outputs")
  field(OUT, "@$(PLC_NAME) Dis_Press_For_Loading")
}

record(stringin, "WCMP:CP$(CP)2:9$(C)0:PIDTAG") {
  field(DESC, "SV_SET PIDtag")
  field(PINI, "YES")
  field(VAL, "")
}

#! Further lines contain data used by VisualDCT
#! View(1774,1984,1.0)
#! Record("WCMP:CP$(CP)2:9$(C)0:SV_SET",2060,2119,0,1,"WCMP:CP$(CP)2:9$(C)0:SV_SET")
#! Record("WCMP:CP$(CP)2:9$(C)0:PIDTAG",2340,2142,0,1,"WCMP:CP$(CP)2:9$(C)0:PIDTAG")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../dbd/cryoTest.dbd")
#! DBDEND


record(ao, "WCMP:CP$(CP)2:10$(C)0:SV_SET") {
  field(DESC, "Oil Pump Discharge Pressure Trip TH")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(PREC, "2")
  field(EGU, "bara")
  field(ADEL, "0.01")
  field(IVOA, "Don't drive outputs")
  field(OUT, "@$(PLC_NAME) OP_Dis_Pr_TH")
}

record(stringin, "WCMP:CP$(CP)2:10$(C)0:PIDTAG") {
  field(DESC, "SV_SET PIDtag")
  field(PINI, "YES")
  field(VAL, "")
}

#! Further lines contain data used by VisualDCT
#! View(1774,1984,1.0)
#! Record("WCMP:CP$(CP)2:10$(C)0:SV_SET",2060,2119,0,1,"WCMP:CP$(CP)2:10$(C)0:SV_SET")
#! Record("WCMP:CP$(CP)2:10$(C)0:PIDTAG",2340,2142,0,1,"WCMP:CP$(CP)2:10$(C)0:PIDTAG")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CPSL:CP$(CP)2:1$(C)01:LIMIT_SW") {
  field(DESC, "Low Suction Pressure ")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PSL21X01")
  field(ZNAM, "fault")
  field(ONAM, "ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(stringin, "CPSL:CP$(CP)2:1$(C)01:PIDTAG") {
  field(DESC, "Lmt Swch P&IDname")
  field(PINI, "YES")
  field(VAL, "PSL21$(C)01")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CPSL:CP$(CP)2:1$(C)01:LIMIT_SW",2054,2119,0,1,"CPSL:CP$(CP)2:1$(C)01:LIMIT_SW")
#! Record("CPSL:CP$(CP)2:1$(C)01:PIDTAG",2054,2322,0,1,"CPSL:CP$(CP)2:1$(C)01:PIDTAG")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CPSH:CP$(CP)2:1$(C)12:LIMIT_SW") {
  field(DESC, "High Discharge Pressure ")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PSH21X12")
  field(ZNAM, "fault")
  field(ONAM, "ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(stringin, "CPSH:CP$(CP)2:1$(C)12:PIDTAG") {
  field(DESC, "Lmt Swch P&IDname")
  field(PINI, "YES")
  field(VAL, "PSH21$(C)12")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CPSH:CP$(CP)2:1$(C)12:LIMIT_SW",2054,2119,0,1,"CPSH:CP$(CP)2:1$(C)12:LIMIT_SW")
#! Record("CPSH:CP$(CP)2:1$(C)12:PIDTAG",2054,2322,0,1,"CPSH:CP$(CP)2:1$(C)12:PIDTAG")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CTSH:CP$(CP)2:1$(C)12:LIMIT_SW") {
  field(DESC, "High Discharge Temperature")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) TSH21X12")
  field(ZNAM, "fault")
  field(ONAM, "ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(stringin, "CTSH:CP$(CP)2:1$(C)12:PIDTAG") {
  field(DESC, "Lmt Swch P&IDname")
  field(PINI, "YES")
  field(VAL, "TSH21$(C)12")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTSH:CP$(CP)2:1$(C)12:LIMIT_SW",2054,2119,0,1,"CTSH:CP$(CP)2:1$(C)12:LIMIT_SW")
#! Record("CTSH:CP$(CP)2:1$(C)12:PIDTAG",2054,2322,0,1,"CTSH:CP$(CP)2:1$(C)12:PIDTAG")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CPDL:CP$(CP)2:1$(C)46:LIMIT_SW") {
  field(DESC, "Low Oil Diff. Press  ")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PDSL21X46")
  field(ZNAM, "fault")
  field(ONAM, "ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(stringin, "CPDL:CP$(CP)2:1$(C)46:PIDTAG") {
  field(DESC, "Lmt Swch P&IDname")
  field(PINI, "YES")
  field(VAL, "PDLS21$(C)46")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CPDL:CP$(CP)2:1$(C)46:LIMIT_SW",2054,2119,0,1,"CPDL:CP$(CP)2:1$(C)46:LIMIT_SW")
#! Record("CPDL:CP$(CP)2:1$(C)46:PIDTAG",2054,2322,0,1,"CPDL:CP$(CP)2:1$(C)46:PIDTAG")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CSVL:CP$(CP)2:1$(C)50:LIMIT_SW") {
  field(DESC, "Oil Return Valve SW")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) LS21X50")
  field(ZNAM, "not closed")
  field(ONAM, "closed")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

record(stringin, "CSVL:CP$(CP)2:1$(C)50:PIDTAG") {
  field(DESC, "Lmt Swch P&IDname")
  field(PINI, "YES")
  field(VAL, "LS21$(C)50")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CSVL:CP$(CP)2:1$(C)50:LIMIT_SW",2054,2119,0,1,"CSVL:CP$(CP)2:1$(C)50:LIMIT_SW")
#! Record("CSVL:CP$(CP)2:1$(C)50:PIDTAG",2054,2322,0,1,"CSVL:CP$(CP)2:1$(C)50:PIDTAG")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CZSH:CP$(CP)2:1$(C)47:LIMIT_SW") {
  field(DESC, "Fully loaded")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) ZSH21X47")
  field(ZNAM, "not max")
  field(ONAM, "max")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

record(stringin, "CZSH:CP$(CP)2:1$(C)47:PIDTAG") {
  field(DESC, "Lmt Swch P&IDname")
  field(PINI, "YES")
  field(VAL, "ZSH21$(C)47")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CZSH:CP$(CP)2:1$(C)47:LIMIT_SW",2054,2119,0,1,"CZSH:CP$(CP)2:1$(C)47:LIMIT_SW")
#! Record("CZSH:CP$(CP)2:1$(C)47:PIDTAG",2054,2322,0,1,"CZSH:CP$(CP)2:1$(C)47:PIDTAG")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CZSL:CP$(CP)2:1$(C)47:LIMIT_SW") {
  field(DESC, "Fully unloaded")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) ZSL21X47")
  field(ZNAM, "not min")
  field(ONAM, "min")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

record(stringin, "CZSL:CP$(CP)2:1$(C)47:PIDTAG") {
  field(DESC, "Lmt Swch P&IDname")
  field(PINI, "YES")
  field(VAL, "ZSL21$(C)47")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CZSL:CP$(CP)2:1$(C)47:LIMIT_SW",2054,2119,0,1,"CZSL:CP$(CP)2:1$(C)47:LIMIT_SW")
#! Record("CZSL:CP$(CP)2:1$(C)47:PIDTAG",2054,2322,0,1,"CZSL:CP$(CP)2:1$(C)47:PIDTAG")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CTSH:CP$(CP)2:1$(C)35:LIMIT_SW") {
  field(DESC, "High Oil Temp SW")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) TSH21X35")
  field(ZNAM, "fault")
  field(ONAM, "ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(stringin, "CTSH:CP$(CP)2:1$(C)35:PIDTAG") {
  field(DESC, "Lmt Swch P&IDname")
  field(PINI, "YES")
  field(VAL, "TSH21$(C)35")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTSH:CP$(CP)2:1$(C)35:LIMIT_SW",2054,2119,0,1,"CTSH:CP$(CP)2:1$(C)35:LIMIT_SW")
#! Record("CTSH:CP$(CP)2:1$(C)35:PIDTAG",2054,2322,0,1,"CTSH:CP$(CP)2:1$(C)35:PIDTAG")
#
record(ai, "WCMP:CP$(CP)2:1$(C):LLTMR") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Load_Limit_TMR_Sec")
  field(EGU, "s")
  field(DESC, "Load Limit Tmr Secs")
  field(ADEL, "0")
  field(PINI, "YES")
}

#
record(ai, "WCMP:CP$(CP)2:1$(C):ARTM") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Anti_Recycle_Minutes")
  field(EGU, "min")
  field(DESC, "Anti Recylce Minutes")
  field(ADEL, "0")
  field(PINI, "YES")
}

#
record(ai, "WCMP:CP$(CP)2:1$(C):ARTS") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Anti_Recycle_Seconds")
  field(EGU, "s")
  field(DESC, "Anti Recycle Seconds")
  field(ADEL, "0")
  field(PINI, "YES")
}

#
record(ai, "WCMP:CP$(CP)2:1$(C):ODTMR") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Oil_Drain_Timer_Seconds")
  field(EGU, "s")
  field(DESC, "Oil Drain Tmr Seconds")
  field(ADEL, "0")
  field(PINI, "YES")
}

#
record(ai, "WCMP:CP$(CP)2:1$(C):SOUTMR") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Stop_Unload_TMR_Sec")
  field(EGU, "s")
  field(DESC, "Stop Unload Tmr Secs")
  field(ADEL, "0")
  field(PINI, "YES")
}

#
record(ai, "WCMP:CP$(CP)2:1$(C):OPTMR1") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Oil_DP_Timer_Seconds")
  field(EGU, "s")
  field(DESC, "Oil DP Timer Seconds")
  field(ADEL, "0")
  field(PINI, "YES")
}

#
record(ai, "WCMP:CP$(CP)2:1$(C):OPTMR2") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Oil_Buildup_Tmr_Seconds")
  field(EGU, "s")
  field(DESC, "Oil Buildup Tmr Secs")
  field(ADEL, "0")
  field(PINI, "YES")
}

#
record(ai, "WCMP:CP$(CP)2:1$(C):STUTMR") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) ZT21X47_TMR_Sec")
  field(EGU, "s")
  field(DESC, "ZT21X47 Timer Seconds")
  field(ADEL, "0")
  field(PINI, "YES")
}

#
record(ai, "WCMP:CP$(CP)2:1$(C):MRTMR") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Motor_Start_Tmr_Seconds")
  field(EGU, "s")
  field(DESC, "Motor Start Tmr Secs")
  field(ADEL, "0")
  field(PINI, "YES")
}

#
record(ai, "WCMP:CP$(CP)2:1$(C):CMPRTM") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) TIMER_Comp_Run_Hours_Minutes")
  field(EGU, "min")
  field(DESC, "CMP Run Tmr Minutes")
  field(ADEL, "0")
  field(PINI, "YES")
}

#
record(ai, "WCMP:CP$(CP)2:1$(C):CMPRTH") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Timer_Comp_Run_Hours_Old_Time")
  field(EGU, "hrs")
  field(DESC, "CMP Run Tmr Hours")
  field(ADEL, "0")
  field(PINI, "YES")
}