#! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(bo, "WCMP:CP$(CP)2:1$(C):ORDER_ON") { field(DESC, "WCMP order on") field(ZNAM, "not ordered on") field(ONAM, "ordered on") field(OMSL, "supervisory") field(SCAN, "Passive") field(PINI, "NO") field(DTYP, "Soft Channel") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "WCMP:CP$(CP)2:1$(C):ON_CNCL") { field(DESC, "WCMP Cancel ON order") field(ZNAM, "not cancelled") field(ONAM, "cancelled") field(SCAN, "Passive") field(PINI, "NO") field(DTYP, "Soft Channel") field(OMSL, "supervisory") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "WCMP:CP$(CP)2:1$(C):ORDER_OFF") { field(DESC, "WCMP order off") field(ZNAM, "not order off") field(ONAM, "order off") field(OMSL, "supervisory") field(SCAN, "Passive") field(PINI, "NO") field(DTYP, "Soft Channel") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "WCMP:CP$(CP)2:1$(C):OFF_CNCL") { field(DESC, "WCMP Cancel OFF order") field(ZNAM, "not cancelled") field(ONAM, "cancelled") field(SCAN, "Passive") field(PINI, "NO") field(DTYP, "Soft Channel") field(OMSL, "supervisory") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "WCMP:CP$(CP)2:1$(C):ON_CFRM") { field(DESC, "WCMP confirm ON order") field(ZNAM, "not confirmed") field(ONAM, "confirmed") field(SCAN, "Passive") field(PINI, "NO") field(DTYP, "Soft Channel") field(HIGH, "1") field(ASG, "CRYO") field(OMSL, "supervisory") } record(bo, "WCMP:CP$(CP)2:1$(C):OFF_CFRM") { field(DESC, "WCMP confirm OFF order") field(ZNAM, "not confirmed") field(ONAM, "confirmed") field(SCAN, "Passive") field(PINI, "NO") field(DTYP, "Soft Channel") field(OMSL, "supervisory") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "WCMP:CP$(CP)2:1$(C):RQST_ON") { field(DESC, "WCMP Rqst On") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) Comp_Start_Requested_X B 0") field(ZNAM, "not active") field(ONAM, "Active") field(SCAN, "1 second") field(PINI, "NO") field(ASG, "NOWRITE") field(HIGH, "0") field(OMSL, "supervisory") } record(bo, "WCMP:CP$(CP)2:1$(C):RQST_OFF") { field(DESC, "WCMP Rqst Off") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) Normal_Shutdown_X B 0") field(ZNAM, "not active") field(ONAM, "Active") field(ASG, "NOWRITE") field(PINI, "NO") field(HIGH, "0") field(SCAN, "1 second") field(OMSL, "supervisory") } record(sub, "WCMP:CP$(CP)2:1$(C):ORDER_ONL") { field(DESC, "WCMP") field(SCAN, ".5 second") field(PINI, "NO") field(FLNK, "WCMP:CP$(CP)2:1$(C):ORDER_ONT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "WCMP:CP$(CP)2:1$(C):ORDER_ON") field(INPB, "WCMP:CP$(CP)2:1$(C):ON_CFRM") field(INPC, "WCMP:CP$(CP)2:1$(C):ON_CNCL") field(ASG, "NOWRITE") } record(bo, "WCMP:CP$(CP)2:1$(C):ORDER_ONT") { field(DESC, "WCMP") field(SCAN, "Passive") field(PINI, "NO") field(DTYP, "Soft Channel") field(OMSL, "closed_loop") field(DOL, "WCMP:CP$(CP)2:1$(C):ORDER_ONL") field(OUT, "WCMP:CP$(CP)2:1$(C):RQST_ON") field(ZSV, "MAJOR") field(ASG, "NOWRITE") field(ZNAM, "disabled") field(ONAM, "enabled") field(OSV, "NO_ALARM") field(COSV, "NO_ALARM") } record(sub, "WCMP:CP$(CP)2:1$(C):ORDER_OFFL") { field(DESC, "WCMP") field(SCAN, ".5 second") field(PINI, "NO") field(FLNK, "WCMP:CP$(CP)2:1$(C):ORDER_OFFT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "WCMP:CP$(CP)2:1$(C):ORDER_OFF") field(INPB, "WCMP:CP$(CP)2:1$(C):OFF_CFRM") field(INPC, "WCMP:CP$(CP)2:1$(C):OFF_CNCL") field(ASG, "NOWRITE") } record(bo, "WCMP:CP$(CP)2:1$(C):ORDER_OFFT") { field(DESC, "WCMP") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "closed_loop") field(DOL, "WCMP:CP$(CP)2:1$(C):ORDER_OFFL") field(OUT, "WCMP:CP$(CP)2:1$(C):RQST_OFF") field(ZSV, "MAJOR") field(ASG, "NOWRITE") field(ZNAM, "disabled") field(ONAM, "enabled") field(OSV, "NO_ALARM") field(COSV, "NO_ALARM") } #! Further lines contain data used by VisualDCT #! View(0,416,1.1) #! Record("WCMP:CP$(CP)2:1$(C):ORDER_ON",80,378,0,1,"WCMP:CP$(CP)2:1$(C):ORDER_ON") #! Field("WCMP:CP$(CP)2:1$(C):ORDER_ON.VAL",16777215,1,"WCMP:CP$(CP)2:1$(C):ORDER_ON.VAL") #! Record("WCMP:CP$(CP)2:1$(C):ON_CNCL",80,798,0,1,"WCMP:CP$(CP)2:1$(C):ON_CNCL") #! Field("WCMP:CP$(CP)2:1$(C):ON_CNCL.VAL",16777215,1,"WCMP:CP$(CP)2:1$(C):ON_CNCL.VAL") #! Record("WCMP:CP$(CP)2:1$(C):ORDER_OFF",80,1018,0,1,"WCMP:CP$(CP)2:1$(C):ORDER_OFF") #! Field("WCMP:CP$(CP)2:1$(C):ORDER_OFF.VAL",16777215,1,"WCMP:CP$(CP)2:1$(C):ORDER_OFF.VAL") #! Record("WCMP:CP$(CP)2:1$(C):OFF_CNCL",80,1458,0,1,"WCMP:CP$(CP)2:1$(C):OFF_CNCL") #! Field("WCMP:CP$(CP)2:1$(C):OFF_CNCL.VAL",16777215,1,"WCMP:CP$(CP)2:1$(C):OFF_CNCL.VAL") #! Record("WCMP:CP$(CP)2:1$(C):ON_CFRM",80,578,0,1,"WCMP:CP$(CP)2:1$(C):ON_CFRM") #! Field("WCMP:CP$(CP)2:1$(C):ON_CFRM.VAL",16777215,1,"WCMP:CP$(CP)2:1$(C):ON_CFRM.VAL") #! Record("WCMP:CP$(CP)2:1$(C):OFF_CFRM",80,1238,0,1,"WCMP:CP$(CP)2:1$(C):OFF_CFRM") #! Field("WCMP:CP$(CP)2:1$(C):OFF_CFRM.VAL",16777215,1,"WCMP:CP$(CP)2:1$(C):OFF_CFRM.VAL") #! Record("WCMP:CP$(CP)2:1$(C):RQST_ON",960,584,0,1,"WCMP:CP$(CP)2:1$(C):RQST_ON") #! Field("WCMP:CP$(CP)2:1$(C):RQST_ON.VAL",16777215,1,"WCMP:CP$(CP)2:1$(C):RQST_ON.VAL") #! Record("WCMP:CP$(CP)2:1$(C):RQST_OFF",960,1204,0,1,"WCMP:CP$(CP)2:1$(C):RQST_OFF") #! Field("WCMP:CP$(CP)2:1$(C):RQST_OFF.VAL",16777215,1,"WCMP:CP$(CP)2:1$(C):RQST_OFF.VAL") #! Record("WCMP:CP$(CP)2:1$(C):ORDER_ONL",400,524,0,1,"WCMP:CP$(CP)2:1$(C):ORDER_ONL") #! Field("WCMP:CP$(CP)2:1$(C):ORDER_ONL.FLNK",16777215,1,"WCMP:CP$(CP)2:1$(C):ORDER_ONL.FLNK") #! Link("WCMP:CP$(CP)2:1$(C):ORDER_ONL.FLNK","WCMP:CP$(CP)2:1$(C):ORDER_ONT") #! Field("WCMP:CP$(CP)2:1$(C):ORDER_ONL.INPA",16777215,0,"WCMP:CP$(CP)2:1$(C):ORDER_ONL.INPA") #! Link("WCMP:CP$(CP)2:1$(C):ORDER_ONL.INPA","WCMP:CP$(CP)2:1$(C):ORDER_ON.VAL") #! Field("WCMP:CP$(CP)2:1$(C):ORDER_ONL.INPB",16777215,0,"WCMP:CP$(CP)2:1$(C):ORDER_ONL.INPB") #! Link("WCMP:CP$(CP)2:1$(C):ORDER_ONL.INPB","WCMP:CP$(CP)2:1$(C):ON_CFRM.VAL") #! Field("WCMP:CP$(CP)2:1$(C):ORDER_ONL.INPC",16777215,0,"WCMP:CP$(CP)2:1$(C):ORDER_ONL.INPC") #! Link("WCMP:CP$(CP)2:1$(C):ORDER_ONL.INPC","WCMP:CP$(CP)2:1$(C):ON_CNCL.VAL") #! Field("WCMP:CP$(CP)2:1$(C):ORDER_ONL.VAL",16777215,1,"WCMP:CP$(CP)2:1$(C):ORDER_ONL.VAL") #! Record("WCMP:CP$(CP)2:1$(C):ORDER_ONT",700,522,0,0,"WCMP:CP$(CP)2:1$(C):ORDER_ONT") #! Field("WCMP:CP$(CP)2:1$(C):ORDER_ONT.DOL",16777215,0,"WCMP:CP$(CP)2:1$(C):ORDER_ONT.DOL") #! Link("WCMP:CP$(CP)2:1$(C):ORDER_ONT.DOL","WCMP:CP$(CP)2:1$(C):ORDER_ONL.VAL") #! Field("WCMP:CP$(CP)2:1$(C):ORDER_ONT.OUT",16777215,1,"WCMP:CP$(CP)2:1$(C):ORDER_ONT.OUT") #! Link("WCMP:CP$(CP)2:1$(C):ORDER_ONT.OUT","WCMP:CP$(CP)2:1$(C):RQST_ON.VAL") #! Record("WCMP:CP$(CP)2:1$(C):ORDER_OFFL",400,1124,0,1,"WCMP:CP$(CP)2:1$(C):ORDER_OFFL") #! Field("WCMP:CP$(CP)2:1$(C):ORDER_OFFL.FLNK",16777215,1,"WCMP:CP$(CP)2:1$(C):ORDER_OFFL.FLNK") #! Link("WCMP:CP$(CP)2:1$(C):ORDER_OFFL.FLNK","WCMP:CP$(CP)2:1$(C):ORDER_OFFT") #! Field("WCMP:CP$(CP)2:1$(C):ORDER_OFFL.INPA",16777215,0,"WCMP:CP$(CP)2:1$(C):ORDER_OFFL.INPA") #! Link("WCMP:CP$(CP)2:1$(C):ORDER_OFFL.INPA","WCMP:CP$(CP)2:1$(C):ORDER_OFF.VAL") #! Field("WCMP:CP$(CP)2:1$(C):ORDER_OFFL.INPC",16777215,0,"WCMP:CP$(CP)2:1$(C):ORDER_OFFL.INPC") #! Link("WCMP:CP$(CP)2:1$(C):ORDER_OFFL.INPC","WCMP:CP$(CP)2:1$(C):OFF_CNCL.VAL") #! Field("WCMP:CP$(CP)2:1$(C):ORDER_OFFL.INPB",16777215,0,"WCMP:CP$(CP)2:1$(C):ORDER_OFFL.INPB") #! Link("WCMP:CP$(CP)2:1$(C):ORDER_OFFL.INPB","WCMP:CP$(CP)2:1$(C):OFF_CFRM.VAL") #! Field("WCMP:CP$(CP)2:1$(C):ORDER_OFFL.VAL",16777215,1,"WCMP:CP$(CP)2:1$(C):ORDER_OFFL.VAL") #! Record("WCMP:CP$(CP)2:1$(C):ORDER_OFFT",700,1156,0,0,"WCMP:CP$(CP)2:1$(C):ORDER_OFFT") #! Field("WCMP:CP$(CP)2:1$(C):ORDER_OFFT.DOL",16777215,0,"WCMP:CP$(CP)2:1$(C):ORDER_OFFT.DOL") #! Link("WCMP:CP$(CP)2:1$(C):ORDER_OFFT.DOL","WCMP:CP$(CP)2:1$(C):ORDER_OFFL.VAL") #! Field("WCMP:CP$(CP)2:1$(C):ORDER_OFFT.OUT",16777215,1,"WCMP:CP$(CP)2:1$(C):ORDER_OFFT.OUT") #! Link("WCMP:CP$(CP)2:1$(C):ORDER_OFFT.OUT","WCMP:CP$(CP)2:1$(C):RQST_OFF.VAL") #! TextBox(TB1,480,360,780,400,0,"Dialog",12,1,16777215,"Turn On and confirm logic\nTurn Off and confirm logic\n",null) #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(bo, "CPMP:CP$(CP)2:1$(C):ORDER_ON") { field(DESC, "CPMP order on") field(ZNAM, "not ordered on") field(ONAM, "ordered on") field(OMSL, "supervisory") field(SCAN, "Passive") field(PINI, "NO") field(DTYP, "Soft Channel") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CPMP:CP$(CP)2:1$(C):ON_CNCL") { field(DESC, "CPMP Cancel ON order") field(ZNAM, "not cancelled") field(ONAM, "cancelled") field(SCAN, "Passive") field(PINI, "NO") field(DTYP, "Soft Channel") field(OMSL, "supervisory") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CPMP:CP$(CP)2:1$(C):ORDER_OFF") { field(DESC, "CPMP order off") field(ZNAM, "not order off") field(ONAM, "order off") field(OMSL, "supervisory") field(SCAN, "Passive") field(PINI, "NO") field(DTYP, "Soft Channel") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CPMP:CP$(CP)2:1$(C):OFF_CNCL") { field(DESC, "CPMP Cancel OFF order") field(ZNAM, "not cancelled") field(ONAM, "cancelled") field(SCAN, "Passive") field(PINI, "NO") field(DTYP, "Soft Channel") field(OMSL, "supervisory") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CPMP:CP$(CP)2:1$(C):ON_CFRM") { field(DESC, "CPMP confirm ON order") field(ZNAM, "not confirmed") field(ONAM, "confirmed") field(SCAN, "Passive") field(PINI, "NO") field(DTYP, "Soft Channel") field(HIGH, "1") field(ASG, "CRYO") field(OMSL, "supervisory") } record(bo, "CPMP:CP$(CP)2:1$(C):OFF_CFRM") { field(DESC, "CPMP confirm OFF order") field(ZNAM, "not confirmed") field(ONAM, "confirmed") field(SCAN, "Passive") field(PINI, "NO") field(DTYP, "Soft Channel") field(OMSL, "supervisory") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CPMP:CP$(CP)2:1$(C):RQST_ON") { field(DESC, "CPMP Rqst On") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) Run_Pump_Request B 0") field(ZNAM, "not active") field(ONAM, "Active") field(SCAN, "1 second") field(PINI, "NO") field(ASG, "NOWRITE") field(HIGH, "0") field(OMSL, "supervisory") } record(bo, "CPMP:CP$(CP)2:1$(C):RQST_OFF") { field(DESC, "CPMP Rqst Off") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) Stop_Pump_Request B 0") field(ZNAM, "not active") field(ONAM, "Active") field(ASG, "NOWRITE") field(PINI, "NO") field(HIGH, "0") field(SCAN, "1 second") field(OMSL, "supervisory") } record(sub, "CPMP:CP$(CP)2:1$(C):ORDER_ONL") { field(DESC, "CPMP") field(SCAN, ".5 second") field(PINI, "NO") field(FLNK, "CPMP:CP$(CP)2:1$(C):ORDER_ONT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "CPMP:CP$(CP)2:1$(C):ORDER_ON") field(INPB, "CPMP:CP$(CP)2:1$(C):ON_CFRM") field(INPC, "CPMP:CP$(CP)2:1$(C):ON_CNCL") field(ASG, "NOWRITE") } record(bo, "CPMP:CP$(CP)2:1$(C):ORDER_ONT") { field(DESC, "CPMP") field(SCAN, "Passive") field(PINI, "NO") field(DTYP, "Soft Channel") field(OMSL, "closed_loop") field(DOL, "CPMP:CP$(CP)2:1$(C):ORDER_ONL") field(OUT, "CPMP:CP$(CP)2:1$(C):RQST_ON") field(ZSV, "MAJOR") field(ASG, "NOWRITE") field(ZNAM, "disabled") field(ONAM, "enabled") field(OSV, "NO_ALARM") field(COSV, "NO_ALARM") } record(sub, "CPMP:CP$(CP)2:1$(C):ORDER_OFFL") { field(DESC, "CPMP") field(SCAN, ".5 second") field(PINI, "NO") field(FLNK, "CPMP:CP$(CP)2:1$(C):ORDER_OFFT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "CPMP:CP$(CP)2:1$(C):ORDER_OFF") field(INPB, "CPMP:CP$(CP)2:1$(C):OFF_CFRM") field(INPC, "CPMP:CP$(CP)2:1$(C):OFF_CNCL") field(ASG, "NOWRITE") } record(bo, "CPMP:CP$(CP)2:1$(C):ORDER_OFFT") { field(DESC, "CPMP") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "closed_loop") field(DOL, "CPMP:CP$(CP)2:1$(C):ORDER_OFFL") field(OUT, "CPMP:CP$(CP)2:1$(C):RQST_OFF") field(ZSV, "MAJOR") field(ASG, "NOWRITE") field(ZNAM, "disabled") field(ONAM, "enabled") field(OSV, "NO_ALARM") field(COSV, "NO_ALARM") } #! Further lines contain data used by VisualDCT #! View(0,416,1.1) #! Record("CPMP:CP$(CP)2:1$(C):ORDER_ON",80,378,0,1,"CPMP:CP$(CP)2:1$(C):ORDER_ON") #! Field("CPMP:CP$(CP)2:1$(C):ORDER_ON.VAL",16777215,1,"CPMP:CP$(CP)2:1$(C):ORDER_ON.VAL") #! Record("CPMP:CP$(CP)2:1$(C):ON_CNCL",80,798,0,1,"CPMP:CP$(CP)2:1$(C):ON_CNCL") #! Field("CPMP:CP$(CP)2:1$(C):ON_CNCL.VAL",16777215,1,"CPMP:CP$(CP)2:1$(C):ON_CNCL.VAL") #! Record("CPMP:CP$(CP)2:1$(C):ORDER_OFF",80,1018,0,1,"CPMP:CP$(CP)2:1$(C):ORDER_OFF") #! Field("CPMP:CP$(CP)2:1$(C):ORDER_OFF.VAL",16777215,1,"CPMP:CP$(CP)2:1$(C):ORDER_OFF.VAL") #! Record("CPMP:CP$(CP)2:1$(C):OFF_CNCL",80,1458,0,1,"CPMP:CP$(CP)2:1$(C):OFF_CNCL") #! Field("CPMP:CP$(CP)2:1$(C):OFF_CNCL.VAL",16777215,1,"CPMP:CP$(CP)2:1$(C):OFF_CNCL.VAL") #! Record("CPMP:CP$(CP)2:1$(C):ON_CFRM",80,578,0,1,"CPMP:CP$(CP)2:1$(C):ON_CFRM") #! Field("CPMP:CP$(CP)2:1$(C):ON_CFRM.VAL",16777215,1,"CPMP:CP$(CP)2:1$(C):ON_CFRM.VAL") #! Record("CPMP:CP$(CP)2:1$(C):OFF_CFRM",80,1238,0,1,"CPMP:CP$(CP)2:1$(C):OFF_CFRM") #! Field("CPMP:CP$(CP)2:1$(C):OFF_CFRM.VAL",16777215,1,"CPMP:CP$(CP)2:1$(C):OFF_CFRM.VAL") #! Record("CPMP:CP$(CP)2:1$(C):RQST_ON",960,584,0,1,"CPMP:CP$(CP)2:1$(C):RQST_ON") #! Field("CPMP:CP$(CP)2:1$(C):RQST_ON.VAL",16777215,1,"CPMP:CP$(CP)2:1$(C):RQST_ON.VAL") #! Record("CPMP:CP$(CP)2:1$(C):RQST_OFF",960,1204,0,1,"CPMP:CP$(CP)2:1$(C):RQST_OFF") #! Field("CPMP:CP$(CP)2:1$(C):RQST_OFF.VAL",16777215,1,"CPMP:CP$(CP)2:1$(C):RQST_OFF.VAL") #! Record("CPMP:CP$(CP)2:1$(C):ORDER_ONL",400,524,0,1,"CPMP:CP$(CP)2:1$(C):ORDER_ONL") #! Field("CPMP:CP$(CP)2:1$(C):ORDER_ONL.FLNK",16777215,1,"CPMP:CP$(CP)2:1$(C):ORDER_ONL.FLNK") #! Link("CPMP:CP$(CP)2:1$(C):ORDER_ONL.FLNK","CPMP:CP$(CP)2:1$(C):ORDER_ONT") #! Field("CPMP:CP$(CP)2:1$(C):ORDER_ONL.INPA",16777215,0,"CPMP:CP$(CP)2:1$(C):ORDER_ONL.INPA") #! Link("CPMP:CP$(CP)2:1$(C):ORDER_ONL.INPA","CPMP:CP$(CP)2:1$(C):ORDER_ON.VAL") #! Field("CPMP:CP$(CP)2:1$(C):ORDER_ONL.INPB",16777215,0,"CPMP:CP$(CP)2:1$(C):ORDER_ONL.INPB") #! Link("CPMP:CP$(CP)2:1$(C):ORDER_ONL.INPB","CPMP:CP$(CP)2:1$(C):ON_CFRM.VAL") #! Field("CPMP:CP$(CP)2:1$(C):ORDER_ONL.INPC",16777215,0,"CPMP:CP$(CP)2:1$(C):ORDER_ONL.INPC") #! Link("CPMP:CP$(CP)2:1$(C):ORDER_ONL.INPC","CPMP:CP$(CP)2:1$(C):ON_CNCL.VAL") #! Field("CPMP:CP$(CP)2:1$(C):ORDER_ONL.VAL",16777215,1,"CPMP:CP$(CP)2:1$(C):ORDER_ONL.VAL") #! Record("CPMP:CP$(CP)2:1$(C):ORDER_ONT",700,522,0,0,"CPMP:CP$(CP)2:1$(C):ORDER_ONT") #! Field("CPMP:CP$(CP)2:1$(C):ORDER_ONT.DOL",16777215,0,"CPMP:CP$(CP)2:1$(C):ORDER_ONT.DOL") #! Link("CPMP:CP$(CP)2:1$(C):ORDER_ONT.DOL","CPMP:CP$(CP)2:1$(C):ORDER_ONL.VAL") #! Field("CPMP:CP$(CP)2:1$(C):ORDER_ONT.OUT",16777215,1,"CPMP:CP$(CP)2:1$(C):ORDER_ONT.OUT") #! Link("CPMP:CP$(CP)2:1$(C):ORDER_ONT.OUT","CPMP:CP$(CP)2:1$(C):RQST_ON.VAL") #! Record("CPMP:CP$(CP)2:1$(C):ORDER_OFFL",400,1124,0,1,"CPMP:CP$(CP)2:1$(C):ORDER_OFFL") #! Field("CPMP:CP$(CP)2:1$(C):ORDER_OFFL.FLNK",16777215,1,"CPMP:CP$(CP)2:1$(C):ORDER_OFFL.FLNK") #! Link("CPMP:CP$(CP)2:1$(C):ORDER_OFFL.FLNK","CPMP:CP$(CP)2:1$(C):ORDER_OFFT") #! Field("CPMP:CP$(CP)2:1$(C):ORDER_OFFL.INPA",16777215,0,"CPMP:CP$(CP)2:1$(C):ORDER_OFFL.INPA") #! Link("CPMP:CP$(CP)2:1$(C):ORDER_OFFL.INPA","CPMP:CP$(CP)2:1$(C):ORDER_OFF.VAL") #! Field("CPMP:CP$(CP)2:1$(C):ORDER_OFFL.INPC",16777215,0,"CPMP:CP$(CP)2:1$(C):ORDER_OFFL.INPC") #! Link("CPMP:CP$(CP)2:1$(C):ORDER_OFFL.INPC","CPMP:CP$(CP)2:1$(C):OFF_CNCL.VAL") #! Field("CPMP:CP$(CP)2:1$(C):ORDER_OFFL.INPB",16777215,0,"CPMP:CP$(CP)2:1$(C):ORDER_OFFL.INPB") #! Link("CPMP:CP$(CP)2:1$(C):ORDER_OFFL.INPB","CPMP:CP$(CP)2:1$(C):OFF_CFRM.VAL") #! Field("CPMP:CP$(CP)2:1$(C):ORDER_OFFL.VAL",16777215,1,"CPMP:CP$(CP)2:1$(C):ORDER_OFFL.VAL") #! Record("CPMP:CP$(CP)2:1$(C):ORDER_OFFT",700,1156,0,0,"CPMP:CP$(CP)2:1$(C):ORDER_OFFT") #! Field("CPMP:CP$(CP)2:1$(C):ORDER_OFFT.DOL",16777215,0,"CPMP:CP$(CP)2:1$(C):ORDER_OFFT.DOL") #! Link("CPMP:CP$(CP)2:1$(C):ORDER_OFFT.DOL","CPMP:CP$(CP)2:1$(C):ORDER_OFFL.VAL") #! Field("CPMP:CP$(CP)2:1$(C):ORDER_OFFT.OUT",16777215,1,"CPMP:CP$(CP)2:1$(C):ORDER_OFFT.OUT") #! Link("CPMP:CP$(CP)2:1$(C):ORDER_OFFT.OUT","CPMP:CP$(CP)2:1$(C):RQST_OFF.VAL") #! TextBox(TB1,480,360,780,400,0,"Dialog",12,1,16777215,"Turn On and confirm logic\nTurn Off and confirm logic\n",null) #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(bo, "CHTR:CP$(CP)2:1$(C)35:ORDER_ON") { field(DESC, "Oil Htr order on") field(ZNAM, "not ordered on") field(ONAM, "ordered on") field(OMSL, "supervisory") field(SCAN, "Passive") field(PINI, "NO") field(DTYP, "Soft Channel") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:CP$(CP)2:1$(C)35:ON_CNCL") { field(DESC, "Oil Htr Cancel ON order") field(ZNAM, "not cancelled") field(ONAM, "cancelled") field(SCAN, "Passive") field(PINI, "NO") field(DTYP, "Soft Channel") field(OMSL, "supervisory") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:CP$(CP)2:1$(C)35:ORDER_OFF") { field(DESC, "Oil Htr order off") field(ZNAM, "not order off") field(ONAM, "order off") field(OMSL, "supervisory") field(SCAN, "Passive") field(PINI, "NO") field(DTYP, "Soft Channel") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:CP$(CP)2:1$(C)35:OFF_CNCL") { field(DESC, "Oil Htr Cancel OFF order") field(ZNAM, "not cancelled") field(ONAM, "cancelled") field(SCAN, "Passive") field(PINI, "NO") field(DTYP, "Soft Channel") field(OMSL, "supervisory") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:CP$(CP)2:1$(C)35:ON_CFRM") { field(DESC, "Oil Htr confirm ON order") field(ZNAM, "not confirmed") field(ONAM, "confirmed") field(SCAN, "Passive") field(PINI, "NO") field(DTYP, "Soft Channel") field(HIGH, "1") field(ASG, "CRYO") field(OMSL, "supervisory") } record(bo, "CHTR:CP$(CP)2:1$(C)35:OFF_CFRM") { field(DESC, "Oil Htr confirm OFF order") field(ZNAM, "not confirmed") field(ONAM, "confirmed") field(SCAN, "Passive") field(PINI, "NO") field(DTYP, "Soft Channel") field(OMSL, "supervisory") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CHTR:CP$(CP)2:1$(C)35:RQST_ON") { field(DESC, "Oil Htr Rqst On") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) Oil_Heater_ON_X B 0") field(ZNAM, "not active") field(ONAM, "Active") field(SCAN, "1 second") field(PINI, "NO") field(ASG, "NOWRITE") field(HIGH, "0") field(OMSL, "supervisory") } record(bo, "CHTR:CP$(CP)2:1$(C)35:RQST_OFF") { field(DESC, "Oil Htr Rqst Off") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) Oil_Heater_OFF_X B 0") field(ZNAM, "not active") field(ONAM, "Active") field(ASG, "NOWRITE") field(PINI, "NO") field(HIGH, "0") field(SCAN, "1 second") field(OMSL, "supervisory") } record(sub, "CHTR:CP$(CP)2:1$(C)35:ORDER_ONL") { field(DESC, "Oil Htr") field(SCAN, ".5 second") field(PINI, "NO") field(FLNK, "CHTR:CP$(CP)2:1$(C)35:ORDER_ONT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "CHTR:CP$(CP)2:1$(C)35:ORDER_ON") field(INPB, "CHTR:CP$(CP)2:1$(C)35:ON_CFRM") field(INPC, "CHTR:CP$(CP)2:1$(C)35:ON_CNCL") field(ASG, "NOWRITE") } record(bo, "CHTR:CP$(CP)2:1$(C)35:ORDER_ONT") { field(DESC, "Oil Htr") field(SCAN, "Passive") field(PINI, "NO") field(DTYP, "Soft Channel") field(OMSL, "closed_loop") field(DOL, "CHTR:CP$(CP)2:1$(C)35:ORDER_ONL") field(OUT, "CHTR:CP$(CP)2:1$(C)35:RQST_ON") field(ZSV, "MAJOR") field(ASG, "NOWRITE") field(ZNAM, "disabled") field(ONAM, "enabled") field(OSV, "NO_ALARM") field(COSV, "NO_ALARM") } record(sub, "CHTR:CP$(CP)2:1$(C)35:ORDER_OFFL") { field(DESC, "Oil Htr") field(SCAN, ".5 second") field(PINI, "NO") field(FLNK, "CHTR:CP$(CP)2:1$(C)35:ORDER_OFFT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "CHTR:CP$(CP)2:1$(C)35:ORDER_OFF") field(INPB, "CHTR:CP$(CP)2:1$(C)35:OFF_CFRM") field(INPC, "CHTR:CP$(CP)2:1$(C)35:OFF_CNCL") field(ASG, "NOWRITE") } record(bo, "CHTR:CP$(CP)2:1$(C)35:ORDER_OFFT") { field(DESC, "Oil Htr") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "closed_loop") field(DOL, "CHTR:CP$(CP)2:1$(C)35:ORDER_OFFL") field(OUT, "CHTR:CP$(CP)2:1$(C)35:RQST_OFF") field(ZSV, "MAJOR") field(ASG, "NOWRITE") field(ZNAM, "disabled") field(ONAM, "enabled") field(OSV, "NO_ALARM") field(COSV, "NO_ALARM") } #! Further lines contain data used by VisualDCT #! View(0,416,1.1) #! Record("CHTR:CP$(CP)2:1$(C)35:ORDER_ON",80,378,0,1,"CHTR:CP$(CP)2:1$(C)35:ORDER_ON") #! Field("CHTR:CP$(CP)2:1$(C)35:ORDER_ON.VAL",16777215,1,"CHTR:CP$(CP)2:1$(C)35:ORDER_ON.VAL") #! Record("CHTR:CP$(CP)2:1$(C)35:ON_CNCL",80,798,0,1,"CHTR:CP$(CP)2:1$(C)35:ON_CNCL") #! Field("CHTR:CP$(CP)2:1$(C)35:ON_CNCL.VAL",16777215,1,"CHTR:CP$(CP)2:1$(C)35:ON_CNCL.VAL") #! Record("CHTR:CP$(CP)2:1$(C)35:ORDER_OFF",80,1018,0,1,"CHTR:CP$(CP)2:1$(C)35:ORDER_OFF") #! Field("CHTR:CP$(CP)2:1$(C)35:ORDER_OFF.VAL",16777215,1,"CHTR:CP$(CP)2:1$(C)35:ORDER_OFF.VAL") #! Record("CHTR:CP$(CP)2:1$(C)35:OFF_CNCL",80,1458,0,1,"CHTR:CP$(CP)2:1$(C)35:OFF_CNCL") #! Field("CHTR:CP$(CP)2:1$(C)35:OFF_CNCL.VAL",16777215,1,"CHTR:CP$(CP)2:1$(C)35:OFF_CNCL.VAL") #! Record("CHTR:CP$(CP)2:1$(C)35:ON_CFRM",80,578,0,1,"CHTR:CP$(CP)2:1$(C)35:ON_CFRM") #! Field("CHTR:CP$(CP)2:1$(C)35:ON_CFRM.VAL",16777215,1,"CHTR:CP$(CP)2:1$(C)35:ON_CFRM.VAL") #! Record("CHTR:CP$(CP)2:1$(C)35:OFF_CFRM",80,1238,0,1,"CHTR:CP$(CP)2:1$(C)35:OFF_CFRM") #! Field("CHTR:CP$(CP)2:1$(C)35:OFF_CFRM.VAL",16777215,1,"CHTR:CP$(CP)2:1$(C)35:OFF_CFRM.VAL") #! Record("CHTR:CP$(CP)2:1$(C)35:RQST_ON",960,584,0,1,"CHTR:CP$(CP)2:1$(C)35:RQST_ON") #! Field("CHTR:CP$(CP)2:1$(C)35:RQST_ON.VAL",16777215,1,"CHTR:CP$(CP)2:1$(C)35:RQST_ON.VAL") #! Record("CHTR:CP$(CP)2:1$(C)35:RQST_OFF",960,1204,0,1,"CHTR:CP$(CP)2:1$(C)35:RQST_OFF") #! Field("CHTR:CP$(CP)2:1$(C)35:RQST_OFF.VAL",16777215,1,"CHTR:CP$(CP)2:1$(C)35:RQST_OFF.VAL") #! Record("CHTR:CP$(CP)2:1$(C)35:ORDER_ONL",400,524,0,1,"CHTR:CP$(CP)2:1$(C)35:ORDER_ONL") #! Field("CHTR:CP$(CP)2:1$(C)35:ORDER_ONL.FLNK",16777215,1,"CHTR:CP$(CP)2:1$(C)35:ORDER_ONL.FLNK") #! Link("CHTR:CP$(CP)2:1$(C)35:ORDER_ONL.FLNK","CHTR:CP$(CP)2:1$(C)35:ORDER_ONT") #! Field("CHTR:CP$(CP)2:1$(C)35:ORDER_ONL.INPA",16777215,0,"CHTR:CP$(CP)2:1$(C)35:ORDER_ONL.INPA") #! Link("CHTR:CP$(CP)2:1$(C)35:ORDER_ONL.INPA","CHTR:CP$(CP)2:1$(C)35:ORDER_ON.VAL") #! Field("CHTR:CP$(CP)2:1$(C)35:ORDER_ONL.INPB",16777215,0,"CHTR:CP$(CP)2:1$(C)35:ORDER_ONL.INPB") #! Link("CHTR:CP$(CP)2:1$(C)35:ORDER_ONL.INPB","CHTR:CP$(CP)2:1$(C)35:ON_CFRM.VAL") #! Field("CHTR:CP$(CP)2:1$(C)35:ORDER_ONL.INPC",16777215,0,"CHTR:CP$(CP)2:1$(C)35:ORDER_ONL.INPC") #! Link("CHTR:CP$(CP)2:1$(C)35:ORDER_ONL.INPC","CHTR:CP$(CP)2:1$(C)35:ON_CNCL.VAL") #! Field("CHTR:CP$(CP)2:1$(C)35:ORDER_ONL.VAL",16777215,1,"CHTR:CP$(CP)2:1$(C)35:ORDER_ONL.VAL") #! Record("CHTR:CP$(CP)2:1$(C)35:ORDER_ONT",700,522,0,0,"CHTR:CP$(CP)2:1$(C)35:ORDER_ONT") #! Field("CHTR:CP$(CP)2:1$(C)35:ORDER_ONT.DOL",16777215,0,"CHTR:CP$(CP)2:1$(C)35:ORDER_ONT.DOL") #! Link("CHTR:CP$(CP)2:1$(C)35:ORDER_ONT.DOL","CHTR:CP$(CP)2:1$(C)35:ORDER_ONL.VAL") #! Field("CHTR:CP$(CP)2:1$(C)35:ORDER_ONT.OUT",16777215,1,"CHTR:CP$(CP)2:1$(C)35:ORDER_ONT.OUT") #! Link("CHTR:CP$(CP)2:1$(C)35:ORDER_ONT.OUT","CHTR:CP$(CP)2:1$(C)35:RQST_ON.VAL") #! Record("CHTR:CP$(CP)2:1$(C)35:ORDER_OFFL",400,1124,0,1,"CHTR:CP$(CP)2:1$(C)35:ORDER_OFFL") #! Field("CHTR:CP$(CP)2:1$(C)35:ORDER_OFFL.FLNK",16777215,1,"CHTR:CP$(CP)2:1$(C)35:ORDER_OFFL.FLNK") #! Link("CHTR:CP$(CP)2:1$(C)35:ORDER_OFFL.FLNK","CHTR:CP$(CP)2:1$(C)35:ORDER_OFFT") #! Field("CHTR:CP$(CP)2:1$(C)35:ORDER_OFFL.INPA",16777215,0,"CHTR:CP$(CP)2:1$(C)35:ORDER_OFFL.INPA") #! Link("CHTR:CP$(CP)2:1$(C)35:ORDER_OFFL.INPA","CHTR:CP$(CP)2:1$(C)35:ORDER_OFF.VAL") #! Field("CHTR:CP$(CP)2:1$(C)35:ORDER_OFFL.INPC",16777215,0,"CHTR:CP$(CP)2:1$(C)35:ORDER_OFFL.INPC") #! Link("CHTR:CP$(CP)2:1$(C)35:ORDER_OFFL.INPC","CHTR:CP$(CP)2:1$(C)35:OFF_CNCL.VAL") #! Field("CHTR:CP$(CP)2:1$(C)35:ORDER_OFFL.INPB",16777215,0,"CHTR:CP$(CP)2:1$(C)35:ORDER_OFFL.INPB") #! Link("CHTR:CP$(CP)2:1$(C)35:ORDER_OFFL.INPB","CHTR:CP$(CP)2:1$(C)35:OFF_CFRM.VAL") #! Field("CHTR:CP$(CP)2:1$(C)35:ORDER_OFFL.VAL",16777215,1,"CHTR:CP$(CP)2:1$(C)35:ORDER_OFFL.VAL") #! Record("CHTR:CP$(CP)2:1$(C)35:ORDER_OFFT",700,1156,0,0,"CHTR:CP$(CP)2:1$(C)35:ORDER_OFFT") #! Field("CHTR:CP$(CP)2:1$(C)35:ORDER_OFFT.DOL",16777215,0,"CHTR:CP$(CP)2:1$(C)35:ORDER_OFFT.DOL") #! Link("CHTR:CP$(CP)2:1$(C)35:ORDER_OFFT.DOL","CHTR:CP$(CP)2:1$(C)35:ORDER_OFFL.VAL") #! Field("CHTR:CP$(CP)2:1$(C)35:ORDER_OFFT.OUT",16777215,1,"CHTR:CP$(CP)2:1$(C)35:ORDER_OFFT.OUT") #! Link("CHTR:CP$(CP)2:1$(C)35:ORDER_OFFT.OUT","CHTR:CP$(CP)2:1$(C)35:RQST_OFF.VAL") #! TextBox(TB1,480,360,780,400,0,"Dialog",12,1,16777215,"Turn On and confirm logic\nTurn Off and confirm logic\n",null) #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(bo, "CSV:CP$(CP)2:1$(C)50:ORDER_ON") { field(DESC, "SV21X50 controls order on") field(ZNAM, "not ordered on") field(ONAM, "ordered on") field(OMSL, "supervisory") field(SCAN, "Passive") field(PINI, "NO") field(DTYP, "Soft Channel") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CSV:CP$(CP)2:1$(C)50:ON_CNCL") { field(DESC, "SV21X50 controls Cancel ON order") field(ZNAM, "not cancelled") field(ONAM, "cancelled") field(SCAN, "Passive") field(PINI, "NO") field(DTYP, "Soft Channel") field(OMSL, "supervisory") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CSV:CP$(CP)2:1$(C)50:ORDER_OFF") { field(DESC, "SV21X50 controls order off") field(ZNAM, "not order off") field(ONAM, "order off") field(OMSL, "supervisory") field(SCAN, "Passive") field(PINI, "NO") field(DTYP, "Soft Channel") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CSV:CP$(CP)2:1$(C)50:OFF_CNCL") { field(DESC, "SV21X50 controls Cancel OFF order") field(ZNAM, "not cancelled") field(ONAM, "cancelled") field(SCAN, "Passive") field(PINI, "NO") field(DTYP, "Soft Channel") field(OMSL, "supervisory") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CSV:CP$(CP)2:1$(C)50:ON_CFRM") { field(DESC, "SV21X50 controls confirm ON order") field(ZNAM, "not confirmed") field(ONAM, "confirmed") field(SCAN, "Passive") field(PINI, "NO") field(DTYP, "Soft Channel") field(HIGH, "1") field(ASG, "CRYO") field(OMSL, "supervisory") } record(bo, "CSV:CP$(CP)2:1$(C)50:OFF_CFRM") { field(DESC, "SV21X50 controls confirm OFF order") field(ZNAM, "not confirmed") field(ONAM, "confirmed") field(SCAN, "Passive") field(PINI, "NO") field(DTYP, "Soft Channel") field(OMSL, "supervisory") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CSV:CP$(CP)2:1$(C)50:RQST_ON") { field(DESC, "SV21X50 controls Rqst On") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) SV21X50.EN B 0") field(ZNAM, "not active") field(ONAM, "Active") field(SCAN, "1 second") field(PINI, "NO") field(ASG, "NOWRITE") field(HIGH, "0") field(OMSL, "supervisory") } record(bo, "CSV:CP$(CP)2:1$(C)50:RQST_OFF") { field(DESC, "SV21X50 controls Rqst Off") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) SV21X50.DIS B 0") field(ZNAM, "not active") field(ONAM, "Active") field(ASG, "NOWRITE") field(PINI, "NO") field(HIGH, "0") field(SCAN, "1 second") field(OMSL, "supervisory") } record(sub, "CSV:CP$(CP)2:1$(C)50:ORDER_ONL") { field(DESC, "SV21X50 controls") field(SCAN, ".5 second") field(PINI, "NO") field(FLNK, "CSV:CP$(CP)2:1$(C)50:ORDER_ONT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "CSV:CP$(CP)2:1$(C)50:ORDER_ON") field(INPB, "CSV:CP$(CP)2:1$(C)50:ON_CFRM") field(INPC, "CSV:CP$(CP)2:1$(C)50:ON_CNCL") field(ASG, "NOWRITE") } record(bo, "CSV:CP$(CP)2:1$(C)50:ORDER_ONT") { field(DESC, "SV21X50 controls") field(SCAN, "Passive") field(PINI, "NO") field(DTYP, "Soft Channel") field(OMSL, "closed_loop") field(DOL, "CSV:CP$(CP)2:1$(C)50:ORDER_ONL") field(OUT, "CSV:CP$(CP)2:1$(C)50:RQST_ON") field(ZSV, "MAJOR") field(ASG, "NOWRITE") field(ZNAM, "disabled") field(ONAM, "enabled") field(OSV, "NO_ALARM") field(COSV, "NO_ALARM") } record(sub, "CSV:CP$(CP)2:1$(C)50:ORDER_OFFL") { field(DESC, "SV21X50 controls") field(SCAN, ".5 second") field(PINI, "NO") field(FLNK, "CSV:CP$(CP)2:1$(C)50:ORDER_OFFT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "CSV:CP$(CP)2:1$(C)50:ORDER_OFF") field(INPB, "CSV:CP$(CP)2:1$(C)50:OFF_CFRM") field(INPC, "CSV:CP$(CP)2:1$(C)50:OFF_CNCL") field(ASG, "NOWRITE") } record(bo, "CSV:CP$(CP)2:1$(C)50:ORDER_OFFT") { field(DESC, "SV21X50 controls") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "closed_loop") field(DOL, "CSV:CP$(CP)2:1$(C)50:ORDER_OFFL") field(OUT, "CSV:CP$(CP)2:1$(C)50:RQST_OFF") field(ZSV, "MAJOR") field(ASG, "NOWRITE") field(ZNAM, "disabled") field(ONAM, "enabled") field(OSV, "NO_ALARM") field(COSV, "NO_ALARM") } #! Further lines contain data used by VisualDCT #! View(0,416,1.1) #! Record("CSV:CP$(CP)2:1$(C)50:ORDER_ON",80,378,0,1,"CSV:CP$(CP)2:1$(C)50:ORDER_ON") #! Field("CSV:CP$(CP)2:1$(C)50:ORDER_ON.VAL",16777215,1,"CSV:CP$(CP)2:1$(C)50:ORDER_ON.VAL") #! Record("CSV:CP$(CP)2:1$(C)50:ON_CNCL",80,798,0,1,"CSV:CP$(CP)2:1$(C)50:ON_CNCL") #! Field("CSV:CP$(CP)2:1$(C)50:ON_CNCL.VAL",16777215,1,"CSV:CP$(CP)2:1$(C)50:ON_CNCL.VAL") #! Record("CSV:CP$(CP)2:1$(C)50:ORDER_OFF",80,1018,0,1,"CSV:CP$(CP)2:1$(C)50:ORDER_OFF") #! Field("CSV:CP$(CP)2:1$(C)50:ORDER_OFF.VAL",16777215,1,"CSV:CP$(CP)2:1$(C)50:ORDER_OFF.VAL") #! Record("CSV:CP$(CP)2:1$(C)50:OFF_CNCL",80,1458,0,1,"CSV:CP$(CP)2:1$(C)50:OFF_CNCL") #! Field("CSV:CP$(CP)2:1$(C)50:OFF_CNCL.VAL",16777215,1,"CSV:CP$(CP)2:1$(C)50:OFF_CNCL.VAL") #! Record("CSV:CP$(CP)2:1$(C)50:ON_CFRM",80,578,0,1,"CSV:CP$(CP)2:1$(C)50:ON_CFRM") #! Field("CSV:CP$(CP)2:1$(C)50:ON_CFRM.VAL",16777215,1,"CSV:CP$(CP)2:1$(C)50:ON_CFRM.VAL") #! Record("CSV:CP$(CP)2:1$(C)50:OFF_CFRM",80,1238,0,1,"CSV:CP$(CP)2:1$(C)50:OFF_CFRM") #! Field("CSV:CP$(CP)2:1$(C)50:OFF_CFRM.VAL",16777215,1,"CSV:CP$(CP)2:1$(C)50:OFF_CFRM.VAL") #! Record("CSV:CP$(CP)2:1$(C)50:RQST_ON",960,584,0,1,"CSV:CP$(CP)2:1$(C)50:RQST_ON") #! Field("CSV:CP$(CP)2:1$(C)50:RQST_ON.VAL",16777215,1,"CSV:CP$(CP)2:1$(C)50:RQST_ON.VAL") #! Record("CSV:CP$(CP)2:1$(C)50:RQST_OFF",960,1204,0,1,"CSV:CP$(CP)2:1$(C)50:RQST_OFF") #! Field("CSV:CP$(CP)2:1$(C)50:RQST_OFF.VAL",16777215,1,"CSV:CP$(CP)2:1$(C)50:RQST_OFF.VAL") #! Record("CSV:CP$(CP)2:1$(C)50:ORDER_ONL",400,524,0,1,"CSV:CP$(CP)2:1$(C)50:ORDER_ONL") #! Field("CSV:CP$(CP)2:1$(C)50:ORDER_ONL.FLNK",16777215,1,"CSV:CP$(CP)2:1$(C)50:ORDER_ONL.FLNK") #! Link("CSV:CP$(CP)2:1$(C)50:ORDER_ONL.FLNK","CSV:CP$(CP)2:1$(C)50:ORDER_ONT") #! Field("CSV:CP$(CP)2:1$(C)50:ORDER_ONL.INPA",16777215,0,"CSV:CP$(CP)2:1$(C)50:ORDER_ONL.INPA") #! Link("CSV:CP$(CP)2:1$(C)50:ORDER_ONL.INPA","CSV:CP$(CP)2:1$(C)50:ORDER_ON.VAL") #! Field("CSV:CP$(CP)2:1$(C)50:ORDER_ONL.INPB",16777215,0,"CSV:CP$(CP)2:1$(C)50:ORDER_ONL.INPB") #! Link("CSV:CP$(CP)2:1$(C)50:ORDER_ONL.INPB","CSV:CP$(CP)2:1$(C)50:ON_CFRM.VAL") #! Field("CSV:CP$(CP)2:1$(C)50:ORDER_ONL.INPC",16777215,0,"CSV:CP$(CP)2:1$(C)50:ORDER_ONL.INPC") #! Link("CSV:CP$(CP)2:1$(C)50:ORDER_ONL.INPC","CSV:CP$(CP)2:1$(C)50:ON_CNCL.VAL") #! Field("CSV:CP$(CP)2:1$(C)50:ORDER_ONL.VAL",16777215,1,"CSV:CP$(CP)2:1$(C)50:ORDER_ONL.VAL") #! Record("CSV:CP$(CP)2:1$(C)50:ORDER_ONT",700,522,0,0,"CSV:CP$(CP)2:1$(C)50:ORDER_ONT") #! Field("CSV:CP$(CP)2:1$(C)50:ORDER_ONT.DOL",16777215,0,"CSV:CP$(CP)2:1$(C)50:ORDER_ONT.DOL") #! Link("CSV:CP$(CP)2:1$(C)50:ORDER_ONT.DOL","CSV:CP$(CP)2:1$(C)50:ORDER_ONL.VAL") #! Field("CSV:CP$(CP)2:1$(C)50:ORDER_ONT.OUT",16777215,1,"CSV:CP$(CP)2:1$(C)50:ORDER_ONT.OUT") #! Link("CSV:CP$(CP)2:1$(C)50:ORDER_ONT.OUT","CSV:CP$(CP)2:1$(C)50:RQST_ON.VAL") #! Record("CSV:CP$(CP)2:1$(C)50:ORDER_OFFL",400,1124,0,1,"CSV:CP$(CP)2:1$(C)50:ORDER_OFFL") #! Field("CSV:CP$(CP)2:1$(C)50:ORDER_OFFL.FLNK",16777215,1,"CSV:CP$(CP)2:1$(C)50:ORDER_OFFL.FLNK") #! Link("CSV:CP$(CP)2:1$(C)50:ORDER_OFFL.FLNK","CSV:CP$(CP)2:1$(C)50:ORDER_OFFT") #! Field("CSV:CP$(CP)2:1$(C)50:ORDER_OFFL.INPA",16777215,0,"CSV:CP$(CP)2:1$(C)50:ORDER_OFFL.INPA") #! Link("CSV:CP$(CP)2:1$(C)50:ORDER_OFFL.INPA","CSV:CP$(CP)2:1$(C)50:ORDER_OFF.VAL") #! Field("CSV:CP$(CP)2:1$(C)50:ORDER_OFFL.INPC",16777215,0,"CSV:CP$(CP)2:1$(C)50:ORDER_OFFL.INPC") #! Link("CSV:CP$(CP)2:1$(C)50:ORDER_OFFL.INPC","CSV:CP$(CP)2:1$(C)50:OFF_CNCL.VAL") #! Field("CSV:CP$(CP)2:1$(C)50:ORDER_OFFL.INPB",16777215,0,"CSV:CP$(CP)2:1$(C)50:ORDER_OFFL.INPB") #! Link("CSV:CP$(CP)2:1$(C)50:ORDER_OFFL.INPB","CSV:CP$(CP)2:1$(C)50:OFF_CFRM.VAL") #! Field("CSV:CP$(CP)2:1$(C)50:ORDER_OFFL.VAL",16777215,1,"CSV:CP$(CP)2:1$(C)50:ORDER_OFFL.VAL") #! Record("CSV:CP$(CP)2:1$(C)50:ORDER_OFFT",700,1156,0,0,"CSV:CP$(CP)2:1$(C)50:ORDER_OFFT") #! Field("CSV:CP$(CP)2:1$(C)50:ORDER_OFFT.DOL",16777215,0,"CSV:CP$(CP)2:1$(C)50:ORDER_OFFT.DOL") #! Link("CSV:CP$(CP)2:1$(C)50:ORDER_OFFT.DOL","CSV:CP$(CP)2:1$(C)50:ORDER_OFFL.VAL") #! Field("CSV:CP$(CP)2:1$(C)50:ORDER_OFFT.OUT",16777215,1,"CSV:CP$(CP)2:1$(C)50:ORDER_OFFT.OUT") #! Link("CSV:CP$(CP)2:1$(C)50:ORDER_OFFT.OUT","CSV:CP$(CP)2:1$(C)50:RQST_OFF.VAL") #! TextBox(TB1,480,360,780,400,0,"Dialog",12,1,16777215,"Turn On and confirm logic\nTurn Off and confirm logic\n",null) #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(bo, "CVFD:CP$(CP)2:1$(C):ORDER_ON") { field(DESC, "OPVFD21X controls order on") field(ZNAM, "not ordered on") field(ONAM, "ordered on") field(OMSL, "supervisory") field(SCAN, "Passive") field(PINI, "NO") field(DTYP, "Soft Channel") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CVFD:CP$(CP)2:1$(C):ON_CNCL") { field(DESC, "OPVFD21X controls Cancel ON order") field(ZNAM, "not cancelled") field(ONAM, "cancelled") field(SCAN, "Passive") field(PINI, "NO") field(DTYP, "Soft Channel") field(OMSL, "supervisory") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CVFD:CP$(CP)2:1$(C):ORDER_OFF") { field(DESC, "OPVFD21X controls order off") field(ZNAM, "not order off") field(ONAM, "order off") field(OMSL, "supervisory") field(SCAN, "Passive") field(PINI, "NO") field(DTYP, "Soft Channel") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CVFD:CP$(CP)2:1$(C):OFF_CNCL") { field(DESC, "OPVFD21X controls Cancel OFF order") field(ZNAM, "not cancelled") field(ONAM, "cancelled") field(SCAN, "Passive") field(PINI, "NO") field(DTYP, "Soft Channel") field(OMSL, "supervisory") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CVFD:CP$(CP)2:1$(C):ON_CFRM") { field(DESC, "OPVFD21X controls confirm ON order") field(ZNAM, "not confirmed") field(ONAM, "confirmed") field(SCAN, "Passive") field(PINI, "NO") field(DTYP, "Soft Channel") field(HIGH, "1") field(ASG, "CRYO") field(OMSL, "supervisory") } record(bo, "CVFD:CP$(CP)2:1$(C):OFF_CFRM") { field(DESC, "OPVFD21X controls confirm OFF order") field(ZNAM, "not confirmed") field(ONAM, "confirmed") field(SCAN, "Passive") field(PINI, "NO") field(DTYP, "Soft Channel") field(OMSL, "supervisory") field(HIGH, "1") field(ASG, "CRYO") } record(bo, "CVFD:CP$(CP)2:1$(C):RQST_ON") { field(DESC, "OPVFD21X controls Rqst On") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) OPVFD21X.EN B 0") field(ZNAM, "not active") field(ONAM, "Active") field(SCAN, "1 second") field(PINI, "NO") field(ASG, "NOWRITE") field(HIGH, "0") field(OMSL, "supervisory") } record(bo, "CVFD:CP$(CP)2:1$(C):RQST_OFF") { field(DESC, "OPVFD21X controls Rqst Off") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) OPVFD21X.DIS B 0") field(ZNAM, "not active") field(ONAM, "Active") field(ASG, "NOWRITE") field(PINI, "NO") field(HIGH, "0") field(SCAN, "1 second") field(OMSL, "supervisory") } record(sub, "CVFD:CP$(CP)2:1$(C):ORDER_ONL") { field(DESC, "OPVFD21X controls") field(SCAN, ".5 second") field(PINI, "NO") field(FLNK, "CVFD:CP$(CP)2:1$(C):ORDER_ONT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "CVFD:CP$(CP)2:1$(C):ORDER_ON") field(INPB, "CVFD:CP$(CP)2:1$(C):ON_CFRM") field(INPC, "CVFD:CP$(CP)2:1$(C):ON_CNCL") field(ASG, "NOWRITE") } record(bo, "CVFD:CP$(CP)2:1$(C):ORDER_ONT") { field(DESC, "OPVFD21X controls") field(SCAN, "Passive") field(PINI, "NO") field(DTYP, "Soft Channel") field(OMSL, "closed_loop") field(DOL, "CVFD:CP$(CP)2:1$(C):ORDER_ONL") field(OUT, "CVFD:CP$(CP)2:1$(C):RQST_ON") field(ZSV, "MAJOR") field(ASG, "NOWRITE") field(ZNAM, "disabled") field(ONAM, "enabled") field(OSV, "NO_ALARM") field(COSV, "NO_ALARM") } record(sub, "CVFD:CP$(CP)2:1$(C):ORDER_OFFL") { field(DESC, "OPVFD21X controls") field(SCAN, ".5 second") field(PINI, "NO") field(FLNK, "CVFD:CP$(CP)2:1$(C):ORDER_OFFT") field(INAM, "Icclmom") field(SNAM, "Scclmom") field(INPA, "CVFD:CP$(CP)2:1$(C):ORDER_OFF") field(INPB, "CVFD:CP$(CP)2:1$(C):OFF_CFRM") field(INPC, "CVFD:CP$(CP)2:1$(C):OFF_CNCL") field(ASG, "NOWRITE") } record(bo, "CVFD:CP$(CP)2:1$(C):ORDER_OFFT") { field(DESC, "OPVFD21X controls") field(SCAN, "Passive") field(PINI, "NO") field(OMSL, "closed_loop") field(DOL, "CVFD:CP$(CP)2:1$(C):ORDER_OFFL") field(OUT, "CVFD:CP$(CP)2:1$(C):RQST_OFF") field(ZSV, "MAJOR") field(ASG, "NOWRITE") field(ZNAM, "disabled") field(ONAM, "enabled") field(OSV, "NO_ALARM") field(COSV, "NO_ALARM") } #! Further lines contain data used by VisualDCT #! View(0,416,1.1) #! Record("CVFD:CP$(CP)2:1$(C):ORDER_ON",80,378,0,1,"CVFD:CP$(CP)2:1$(C):ORDER_ON") #! Field("CVFD:CP$(CP)2:1$(C):ORDER_ON.VAL",16777215,1,"CVFD:CP$(CP)2:1$(C):ORDER_ON.VAL") #! Record("CVFD:CP$(CP)2:1$(C):ON_CNCL",80,798,0,1,"CVFD:CP$(CP)2:1$(C):ON_CNCL") #! Field("CVFD:CP$(CP)2:1$(C):ON_CNCL.VAL",16777215,1,"CVFD:CP$(CP)2:1$(C):ON_CNCL.VAL") #! Record("CVFD:CP$(CP)2:1$(C):ORDER_OFF",80,1018,0,1,"CVFD:CP$(CP)2:1$(C):ORDER_OFF") #! Field("CVFD:CP$(CP)2:1$(C):ORDER_OFF.VAL",16777215,1,"CVFD:CP$(CP)2:1$(C):ORDER_OFF.VAL") #! Record("CVFD:CP$(CP)2:1$(C):OFF_CNCL",80,1458,0,1,"CVFD:CP$(CP)2:1$(C):OFF_CNCL") #! Field("CVFD:CP$(CP)2:1$(C):OFF_CNCL.VAL",16777215,1,"CVFD:CP$(CP)2:1$(C):OFF_CNCL.VAL") #! Record("CVFD:CP$(CP)2:1$(C):ON_CFRM",80,578,0,1,"CVFD:CP$(CP)2:1$(C):ON_CFRM") #! Field("CVFD:CP$(CP)2:1$(C):ON_CFRM.VAL",16777215,1,"CVFD:CP$(CP)2:1$(C):ON_CFRM.VAL") #! Record("CVFD:CP$(CP)2:1$(C):OFF_CFRM",80,1238,0,1,"CVFD:CP$(CP)2:1$(C):OFF_CFRM") #! Field("CVFD:CP$(CP)2:1$(C):OFF_CFRM.VAL",16777215,1,"CVFD:CP$(CP)2:1$(C):OFF_CFRM.VAL") #! Record("CVFD:CP$(CP)2:1$(C):RQST_ON",960,584,0,1,"CVFD:CP$(CP)2:1$(C):RQST_ON") #! Field("CVFD:CP$(CP)2:1$(C):RQST_ON.VAL",16777215,1,"CVFD:CP$(CP)2:1$(C):RQST_ON.VAL") #! Record("CVFD:CP$(CP)2:1$(C):RQST_OFF",960,1204,0,1,"CVFD:CP$(CP)2:1$(C):RQST_OFF") #! Field("CVFD:CP$(CP)2:1$(C):RQST_OFF.VAL",16777215,1,"CVFD:CP$(CP)2:1$(C):RQST_OFF.VAL") #! Record("CVFD:CP$(CP)2:1$(C):ORDER_ONL",400,524,0,1,"CVFD:CP$(CP)2:1$(C):ORDER_ONL") #! Field("CVFD:CP$(CP)2:1$(C):ORDER_ONL.FLNK",16777215,1,"CVFD:CP$(CP)2:1$(C):ORDER_ONL.FLNK") #! Link("CVFD:CP$(CP)2:1$(C):ORDER_ONL.FLNK","CVFD:CP$(CP)2:1$(C):ORDER_ONT") #! Field("CVFD:CP$(CP)2:1$(C):ORDER_ONL.INPA",16777215,0,"CVFD:CP$(CP)2:1$(C):ORDER_ONL.INPA") #! Link("CVFD:CP$(CP)2:1$(C):ORDER_ONL.INPA","CVFD:CP$(CP)2:1$(C):ORDER_ON.VAL") #! Field("CVFD:CP$(CP)2:1$(C):ORDER_ONL.INPB",16777215,0,"CVFD:CP$(CP)2:1$(C):ORDER_ONL.INPB") #! Link("CVFD:CP$(CP)2:1$(C):ORDER_ONL.INPB","CVFD:CP$(CP)2:1$(C):ON_CFRM.VAL") #! Field("CVFD:CP$(CP)2:1$(C):ORDER_ONL.INPC",16777215,0,"CVFD:CP$(CP)2:1$(C):ORDER_ONL.INPC") #! Link("CVFD:CP$(CP)2:1$(C):ORDER_ONL.INPC","CVFD:CP$(CP)2:1$(C):ON_CNCL.VAL") #! Field("CVFD:CP$(CP)2:1$(C):ORDER_ONL.VAL",16777215,1,"CVFD:CP$(CP)2:1$(C):ORDER_ONL.VAL") #! Record("CVFD:CP$(CP)2:1$(C):ORDER_ONT",700,522,0,0,"CVFD:CP$(CP)2:1$(C):ORDER_ONT") #! Field("CVFD:CP$(CP)2:1$(C):ORDER_ONT.DOL",16777215,0,"CVFD:CP$(CP)2:1$(C):ORDER_ONT.DOL") #! Link("CVFD:CP$(CP)2:1$(C):ORDER_ONT.DOL","CVFD:CP$(CP)2:1$(C):ORDER_ONL.VAL") #! Field("CVFD:CP$(CP)2:1$(C):ORDER_ONT.OUT",16777215,1,"CVFD:CP$(CP)2:1$(C):ORDER_ONT.OUT") #! Link("CVFD:CP$(CP)2:1$(C):ORDER_ONT.OUT","CVFD:CP$(CP)2:1$(C):RQST_ON.VAL") #! Record("CVFD:CP$(CP)2:1$(C):ORDER_OFFL",400,1124,0,1,"CVFD:CP$(CP)2:1$(C):ORDER_OFFL") #! Field("CVFD:CP$(CP)2:1$(C):ORDER_OFFL.FLNK",16777215,1,"CVFD:CP$(CP)2:1$(C):ORDER_OFFL.FLNK") #! Link("CVFD:CP$(CP)2:1$(C):ORDER_OFFL.FLNK","CVFD:CP$(CP)2:1$(C):ORDER_OFFT") #! Field("CVFD:CP$(CP)2:1$(C):ORDER_OFFL.INPA",16777215,0,"CVFD:CP$(CP)2:1$(C):ORDER_OFFL.INPA") #! Link("CVFD:CP$(CP)2:1$(C):ORDER_OFFL.INPA","CVFD:CP$(CP)2:1$(C):ORDER_OFF.VAL") #! Field("CVFD:CP$(CP)2:1$(C):ORDER_OFFL.INPC",16777215,0,"CVFD:CP$(CP)2:1$(C):ORDER_OFFL.INPC") #! Link("CVFD:CP$(CP)2:1$(C):ORDER_OFFL.INPC","CVFD:CP$(CP)2:1$(C):OFF_CNCL.VAL") #! Field("CVFD:CP$(CP)2:1$(C):ORDER_OFFL.INPB",16777215,0,"CVFD:CP$(CP)2:1$(C):ORDER_OFFL.INPB") #! Link("CVFD:CP$(CP)2:1$(C):ORDER_OFFL.INPB","CVFD:CP$(CP)2:1$(C):OFF_CFRM.VAL") #! Field("CVFD:CP$(CP)2:1$(C):ORDER_OFFL.VAL",16777215,1,"CVFD:CP$(CP)2:1$(C):ORDER_OFFL.VAL") #! Record("CVFD:CP$(CP)2:1$(C):ORDER_OFFT",700,1156,0,0,"CVFD:CP$(CP)2:1$(C):ORDER_OFFT") #! Field("CVFD:CP$(CP)2:1$(C):ORDER_OFFT.DOL",16777215,0,"CVFD:CP$(CP)2:1$(C):ORDER_OFFT.DOL") #! Link("CVFD:CP$(CP)2:1$(C):ORDER_OFFT.DOL","CVFD:CP$(CP)2:1$(C):ORDER_OFFL.VAL") #! Field("CVFD:CP$(CP)2:1$(C):ORDER_OFFT.OUT",16777215,1,"CVFD:CP$(CP)2:1$(C):ORDER_OFFT.OUT") #! Link("CVFD:CP$(CP)2:1$(C):ORDER_OFFT.OUT","CVFD:CP$(CP)2:1$(C):RQST_OFF.VAL") #! TextBox(TB1,480,360,780,400,0,"Dialog",12,1,16777215,"Turn On and confirm logic\nTurn Off and confirm logic\n",null) #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(bo, "CSV:CP$(CP)2:1$(C)47:LOAD") { field(DESC, "load cmd") field(PINI, "NO") field(DTYP, "EtherIP") field(OMSL, "supervisory") field(OUT, "@$(PLC_NAME) Load_X B 0") field(ZNAM, " no load") field(ONAM, "load") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") field(ASG, "CRYO") field(HIGH, "1") field(IVOA, "Don't drive outputs") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("CSV:CP$(CP)2:1$(C)47:LOAD",2060,2137,0,1,"CSV:CP$(CP)2:1$(C)47:LOAD") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(bo, "CSV:CP$(CP)2:1$(C)47:UNLOAD") { field(DESC, "unload cmd") field(PINI, "NO") field(DTYP, "EtherIP") field(OMSL, "supervisory") field(OUT, "@$(PLC_NAME) Unload_X B 0") field(ZNAM, " no unload") field(ONAM, "unload") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") field(ASG, "CRYO") field(HIGH, "1") field(IVOA, "Don't drive outputs") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("CSV:CP$(CP)2:1$(C)47:UNLOAD",2060,2137,0,1,"CSV:CP$(CP)2:1$(C)47:UNLOAD") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(bi, "WCMP:CP$(CP)2:1$(C):MMOD") { field(DESC, "Man. Mode status") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SO21X.mmod") field(ZNAM, "inactive") field(ONAM, "active") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bi, "WCMP:CP$(CP)2:1$(C):IMOD") { field(DESC, "Interlock mode") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SO21X.imod") field(ZNAM, "inactive") field(ONAM, "active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "WCMP:CP$(CP)2:1$(C):TEXT1") { field(DESC, "Notes") field(PINI, "YES") field(DTYP, "Soft Channel") info(autosaveFields, "VAL") } record(stringin, "WCMP:CP$(CP)2:1$(C):TEXT2") { field(DESC, "Notes") field(PINI, "YES") field(DTYP, "Soft Channel") info(autosaveFields, "VAL") } record(bi, "WCMP:CP$(CP)2:1$(C):INTERLOCK") { field(DESC, "interlock status") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SO21X.Interlock_Condition") field(ZNAM, "ok") field(ONAM, "interlocked") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "WCMP:CP$(CP)2:1$(C):IVAL") { field(DESC, "interlock state") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SO21X.ival") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "WCMP:CP$(CP)2:1$(C):OUTPUT") { field(DESC, "actuatorDO output command") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SO21X.Output") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bo, "WCMP:CP$(CP)2:1$(C):MANUAL") { field(DESC, "Manual Mode request ") field(PINI, "NO") field(DTYP, "EtherIP") field(OMSL, "supervisory") field(OUT, "@$(PLC_NAME) SO21X.Manual B 0") field(ZNAM, "not manual") field(ONAM, "Manual") field(ASG, "CRYO") field(HIGH, "1") field(IVOA, "Don't drive outputs") } record(bo, "WCMP:CP$(CP)2:1$(C):SEQUENCER") { field(DESC, "SEQ Mode request ") field(PINI, "NO") field(DTYP, "EtherIP") field(OMSL, "supervisory") field(OUT, "@$(PLC_NAME) SO21X.Sequencer B 0") field(ZNAM, "not sequencer") field(ONAM, "Sequencer") field(ASG, "CRYO") field(HIGH, "1") field(IVOA, "Don't drive outputs") } record(ai, "WCMP:CP$(CP)2:1$(C):MODE") { field(DESC, "actuator mode (man,ovr,seq)") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SO21X.MODE") } record(bi, "WCMP:CP$(CP)2:1$(C):ALM") { field(DESC, "Limit SW alarm") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SO21X.ER") field(ZNAM, "ok") field(ONAM, "alarm") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "WCMP:CP$(CP)2:1$(C):IL_LATCH") { field(DESC, "interlock latched indicator") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SO21X.Interlock_Condition_L") field(ZNAM, "ok") field(ONAM, "latched") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "WCMP:CP$(CP)2:1$(C):IL_RESET") { field(DESC, "Interlock Latch Reset") field(PINI, "NO") field(DTYP, "EtherIP") field(OMSL, "supervisory") field(OUT, "@$(PLC_NAME) SO21X.Interlock_Condition_Reset B 0") field(ZNAM, "not reset") field(ONAM, "RESET") field(ASG, "CRYO") field(HIGH, "1") field(IVOA, "Don't drive outputs") } record(bi, "WCMP:CP$(CP)2:1$(C):ZSH") { field(DESC, "High limit sw value") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SO21X.ZSH") field(ZNAM, "not active") field(ONAM, "active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "WCMP:CP$(CP)2:1$(C):ZSL") { field(DESC, "low limit sw value") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SO21X.ZSL") field(ZNAM, "not active") field(ONAM, "active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "WCMP:CP$(CP)2:1$(C):MVAL") { field(DESC, "manual mode output value") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SO21X.mval") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "WCMP:CP$(CP)2:1$(C):MODE_STRING") { field(DESC, "Actuator (DO) Mode String") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SO21X.Mode_String") } record(bi, "WCMP:CP$(CP)2:1$(C):SVAL") { field(DESC, "sequencer mode output value") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SO21X.sval") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "WCMP:CP$(CP)2:1$(C):PIDTAG") { field(DESC, "Warm Compressor 21$(C) PIDTAG") field(PINI, "YES") field(VAL, "WCMP21$(C)") } record(bi, "WCMP:CP$(CP)2:1$(C):SMOD") { field(DESC, "Sequencer mode indicator") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SO21X.smod") field(ZNAM, "inactive") field(ONAM, "active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "WCMP:CP$(CP)2:1$(C):CMD_OUT") { field(DESC, "rdbk of output signal to the actuator") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SO21XO") field(ZNAM, "off") field(ONAM, "on") } record(mbbiDirect, "WCMP:CP$(CP)2:1$(C):SWITCH_DISABLE") { field(DESC, "Indicates if switch(es) are used") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SO21X.Disable B 0") field(NOBT, "16") } #! Further lines contain data used by VisualDCT #! View(1599,2252,1.0) #! Record("WCMP:CP$(CP)2:1$(C):MMOD",2500,2499,0,1,"WCMP:CP$(CP)2:1$(C):MMOD") #! Record("WCMP:CP$(CP)2:1$(C):IMOD",2680,2499,0,1,"WCMP:CP$(CP)2:1$(C):IMOD") #! Record("WCMP:CP$(CP)2:1$(C):TEXT1",1760,2682,0,1,"WCMP:CP$(CP)2:1$(C):TEXT1") #! Record("WCMP:CP$(CP)2:1$(C):TEXT2",1760,2782,0,1,"WCMP:CP$(CP)2:1$(C):TEXT2") #! Record("WCMP:CP$(CP)2:1$(C):INTERLOCK",2500,2719,0,1,"WCMP:CP$(CP)2:1$(C):INTERLOCK") #! Record("WCMP:CP$(CP)2:1$(C):IVAL",2140,2499,0,1,"WCMP:CP$(CP)2:1$(C):IVAL") #! Record("WCMP:CP$(CP)2:1$(C):OUTPUT",2680,2279,0,1,"WCMP:CP$(CP)2:1$(C):OUTPUT") #! Record("WCMP:CP$(CP)2:1$(C):MANUAL",1960,2265,0,1,"WCMP:CP$(CP)2:1$(C):MANUAL") #! Record("WCMP:CP$(CP)2:1$(C):SEQUENCER",2140,2265,0,1,"WCMP:CP$(CP)2:1$(C):SEQUENCER") #! Record("WCMP:CP$(CP)2:1$(C):MODE",1760,2274,0,1,"WCMP:CP$(CP)2:1$(C):MODE") #! Record("WCMP:CP$(CP)2:1$(C):ALM",1960,2719,0,1,"WCMP:CP$(CP)2:1$(C):ALM") #! Record("WCMP:CP$(CP)2:1$(C):IL_LATCH",2320,2719,0,1,"WCMP:CP$(CP)2:1$(C):IL_LATCH") #! Record("WCMP:CP$(CP)2:1$(C):IL_RESET",2140,2705,0,1,"WCMP:CP$(CP)2:1$(C):IL_RESET") #! Record("WCMP:CP$(CP)2:1$(C):ZSH",2700,2719,0,1,"WCMP:CP$(CP)2:1$(C):ZSH") #! Record("WCMP:CP$(CP)2:1$(C):ZSL",2880,2719,0,1,"WCMP:CP$(CP)2:1$(C):ZSL") #! Record("WCMP:CP$(CP)2:1$(C):MVAL",2320,2499,0,1,"WCMP:CP$(CP)2:1$(C):MVAL") #! Record("WCMP:CP$(CP)2:1$(C):MODE_STRING",1760,2434,0,1,"WCMP:CP$(CP)2:1$(C):MODE_STRING") #! Record("WCMP:CP$(CP)2:1$(C):SVAL",1960,2499,0,1,"WCMP:CP$(CP)2:1$(C):SVAL") #! Record("WCMP:CP$(CP)2:1$(C):PIDTAG",1760,2582,0,1,"WCMP:CP$(CP)2:1$(C):PIDTAG") #! Record("WCMP:CP$(CP)2:1$(C):SMOD",2864,2499,0,1,"WCMP:CP$(CP)2:1$(C):SMOD") #! Record("WCMP:CP$(CP)2:1$(C):CMD_OUT",2860,2286,0,1,"WCMP:CP$(CP)2:1$(C):CMD_OUT") #! Record("WCMP:CP$(CP)2:1$(C):SWITCH_DISABLE",3060,2720,0,1,"WCMP:CP$(CP)2:1$(C):SWITCH_DISABLE") #! TextBox(TB0,1880,2020,2340,2240,0,"Dialog",12,1,16777215,"Generic Actuator records (DO_Record)\n- NOTE this database is the interface to the DO_Record in PLC codes\n- NOTE each of the components using this database\n should also use the on_off_confirm database\nMode\nOverride\nInterlock status\nMode status\nText records\n\nNOTE: there are autosave info fields in this file for the \nTEXT1 and TEXT2 strings that DO NOT show in VDCT",null) #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(bi, "CPMP:CP$(CP)2:1$(C):MMOD") { field(DESC, "Man. Mode status") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) OPVFD21X.mmod") field(ZNAM, "inactive") field(ONAM, "active") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bi, "CPMP:CP$(CP)2:1$(C):IMOD") { field(DESC, "Interlock mode") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) OPVFD21X.imod") field(ZNAM, "inactive") field(ONAM, "active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CPMP:CP$(CP)2:1$(C):TEXT1") { field(DESC, "Notes") field(PINI, "YES") field(DTYP, "Soft Channel") info(autosaveFields, "VAL") } record(stringin, "CPMP:CP$(CP)2:1$(C):TEXT2") { field(DESC, "Notes") field(PINI, "YES") field(DTYP, "Soft Channel") info(autosaveFields, "VAL") } record(bi, "CPMP:CP$(CP)2:1$(C):INTERLOCK") { field(DESC, "interlock status") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) OPVFD21X.Interlock_Condition") field(ZNAM, "ok") field(ONAM, "interlocked") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CPMP:CP$(CP)2:1$(C):IVAL") { field(DESC, "interlock state") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) OPVFD21X.ival") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CPMP:CP$(CP)2:1$(C):OUTPUT") { field(DESC, "actuatorDO output command") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) OPVFD21X.Output") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bo, "CPMP:CP$(CP)2:1$(C):MANUAL") { field(DESC, "Manual Mode request ") field(PINI, "NO") field(DTYP, "EtherIP") field(OMSL, "supervisory") field(OUT, "@$(PLC_NAME) OPVFD21X.Manual B 0") field(ZNAM, "not manual") field(ONAM, "Manual") field(ASG, "CRYO") field(HIGH, "1") field(IVOA, "Don't drive outputs") } record(bo, "CPMP:CP$(CP)2:1$(C):SEQUENCER") { field(DESC, "SEQ Mode request ") field(PINI, "NO") field(DTYP, "EtherIP") field(OMSL, "supervisory") field(OUT, "@$(PLC_NAME) OPVFD21X.Sequencer B 0") field(ZNAM, "not sequencer") field(ONAM, "Sequencer") field(ASG, "CRYO") field(HIGH, "1") field(IVOA, "Don't drive outputs") } record(ai, "CPMP:CP$(CP)2:1$(C):MODE") { field(DESC, "actuator mode (man,ovr,seq)") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) OPVFD21X.MODE") } record(bi, "CPMP:CP$(CP)2:1$(C):ALM") { field(DESC, "Limit SW alarm") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) OPVFD21X.ER") field(ZNAM, "ok") field(ONAM, "alarm") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CPMP:CP$(CP)2:1$(C):IL_LATCH") { field(DESC, "interlock latched indicator") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) OPVFD21X.Interlock_Condition_L") field(ZNAM, "ok") field(ONAM, "latched") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CPMP:CP$(CP)2:1$(C):IL_RESET") { field(DESC, "Interlock Latch Reset") field(PINI, "NO") field(DTYP, "EtherIP") field(OMSL, "supervisory") field(OUT, "@$(PLC_NAME) OPVFD21X.Interlock_Condition_Reset B 0") field(ZNAM, "not reset") field(ONAM, "RESET") field(ASG, "CRYO") field(HIGH, "1") field(IVOA, "Don't drive outputs") } record(bi, "CPMP:CP$(CP)2:1$(C):ZSH") { field(DESC, "High limit sw value") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) OPVFD21X.ZSH") field(ZNAM, "not active") field(ONAM, "active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CPMP:CP$(CP)2:1$(C):ZSL") { field(DESC, "low limit sw value") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) OPVFD21X.ZSL") field(ZNAM, "not active") field(ONAM, "active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CPMP:CP$(CP)2:1$(C):MVAL") { field(DESC, "manual mode output value") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) OPVFD21X.mval") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CPMP:CP$(CP)2:1$(C):MODE_STRING") { field(DESC, "Actuator (DO) Mode String") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) OPVFD21X.Mode_String") } record(bi, "CPMP:CP$(CP)2:1$(C):SVAL") { field(DESC, "sequencer mode output value") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) OPVFD21X.sval") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CPMP:CP$(CP)2:1$(C):PIDTAG") { field(DESC, "Oil pump VFD 21$(C) PIDTAG") field(PINI, "YES") field(VAL, "PVFD21$(C)") } record(bi, "CPMP:CP$(CP)2:1$(C):SMOD") { field(DESC, "Sequencer mode indicator") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) OPVFD21X.smod") field(ZNAM, "inactive") field(ONAM, "active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CPMP:CP$(CP)2:1$(C):CMD_OUT") { field(DESC, "rdbk of output signal to the actuator") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) OPVFD21XO") field(ZNAM, "off") field(ONAM, "on") } record(mbbiDirect, "CPMP:CP$(CP)2:1$(C):SWITCH_DISABLE") { field(DESC, "Indicates if switch(es) are used") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) OPVFD21X.Disable B 0") field(NOBT, "16") } #! Further lines contain data used by VisualDCT #! View(1599,2252,1.0) #! Record("CPMP:CP$(CP)2:1$(C):MMOD",2500,2499,0,1,"CPMP:CP$(CP)2:1$(C):MMOD") #! Record("CPMP:CP$(CP)2:1$(C):IMOD",2680,2499,0,1,"CPMP:CP$(CP)2:1$(C):IMOD") #! Record("CPMP:CP$(CP)2:1$(C):TEXT1",1760,2682,0,1,"CPMP:CP$(CP)2:1$(C):TEXT1") #! Record("CPMP:CP$(CP)2:1$(C):TEXT2",1760,2782,0,1,"CPMP:CP$(CP)2:1$(C):TEXT2") #! Record("CPMP:CP$(CP)2:1$(C):INTERLOCK",2500,2719,0,1,"CPMP:CP$(CP)2:1$(C):INTERLOCK") #! Record("CPMP:CP$(CP)2:1$(C):IVAL",2140,2499,0,1,"CPMP:CP$(CP)2:1$(C):IVAL") #! Record("CPMP:CP$(CP)2:1$(C):OUTPUT",2680,2279,0,1,"CPMP:CP$(CP)2:1$(C):OUTPUT") #! Record("CPMP:CP$(CP)2:1$(C):MANUAL",1960,2265,0,1,"CPMP:CP$(CP)2:1$(C):MANUAL") #! Record("CPMP:CP$(CP)2:1$(C):SEQUENCER",2140,2265,0,1,"CPMP:CP$(CP)2:1$(C):SEQUENCER") #! Record("CPMP:CP$(CP)2:1$(C):MODE",1760,2274,0,1,"CPMP:CP$(CP)2:1$(C):MODE") #! Record("CPMP:CP$(CP)2:1$(C):ALM",1960,2719,0,1,"CPMP:CP$(CP)2:1$(C):ALM") #! Record("CPMP:CP$(CP)2:1$(C):IL_LATCH",2320,2719,0,1,"CPMP:CP$(CP)2:1$(C):IL_LATCH") #! Record("CPMP:CP$(CP)2:1$(C):IL_RESET",2140,2705,0,1,"CPMP:CP$(CP)2:1$(C):IL_RESET") #! Record("CPMP:CP$(CP)2:1$(C):ZSH",2700,2719,0,1,"CPMP:CP$(CP)2:1$(C):ZSH") #! Record("CPMP:CP$(CP)2:1$(C):ZSL",2880,2719,0,1,"CPMP:CP$(CP)2:1$(C):ZSL") #! Record("CPMP:CP$(CP)2:1$(C):MVAL",2320,2499,0,1,"CPMP:CP$(CP)2:1$(C):MVAL") #! Record("CPMP:CP$(CP)2:1$(C):MODE_STRING",1760,2434,0,1,"CPMP:CP$(CP)2:1$(C):MODE_STRING") #! Record("CPMP:CP$(CP)2:1$(C):SVAL",1960,2499,0,1,"CPMP:CP$(CP)2:1$(C):SVAL") #! Record("CPMP:CP$(CP)2:1$(C):PIDTAG",1760,2582,0,1,"CPMP:CP$(CP)2:1$(C):PIDTAG") #! Record("CPMP:CP$(CP)2:1$(C):SMOD",2864,2499,0,1,"CPMP:CP$(CP)2:1$(C):SMOD") #! Record("CPMP:CP$(CP)2:1$(C):CMD_OUT",2860,2286,0,1,"CPMP:CP$(CP)2:1$(C):CMD_OUT") #! Record("CPMP:CP$(CP)2:1$(C):SWITCH_DISABLE",3060,2720,0,1,"CPMP:CP$(CP)2:1$(C):SWITCH_DISABLE") #! TextBox(TB0,1880,2020,2340,2240,0,"Dialog",12,1,16777215,"Generic Actuator records (DO_Record)\n- NOTE this database is the interface to the DO_Record in PLC codes\n- NOTE each of the components using this database\n should also use the on_off_confirm database\nMode\nOverride\nInterlock status\nMode status\nText records\n\nNOTE: there are autosave info fields in this file for the \nTEXT1 and TEXT2 strings that DO NOT show in VDCT",null) #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(bi, "CHTR:CP$(CP)2:1$(C)35:MMOD") { field(DESC, "Man. Mode status") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) HTR21X35.mmod") field(ZNAM, "inactive") field(ONAM, "active") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bi, "CHTR:CP$(CP)2:1$(C)35:IMOD") { field(DESC, "Interlock mode") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) HTR21X35.imod") field(ZNAM, "inactive") field(ONAM, "active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CHTR:CP$(CP)2:1$(C)35:TEXT1") { field(DESC, "Notes") field(PINI, "YES") field(DTYP, "Soft Channel") info(autosaveFields, "VAL") } record(stringin, "CHTR:CP$(CP)2:1$(C)35:TEXT2") { field(DESC, "Notes") field(PINI, "YES") field(DTYP, "Soft Channel") info(autosaveFields, "VAL") } record(bi, "CHTR:CP$(CP)2:1$(C)35:INTERLOCK") { field(DESC, "interlock status") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) HTR21X35.Interlock_Condition") field(ZNAM, "ok") field(ONAM, "interlocked") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:CP$(CP)2:1$(C)35:IVAL") { field(DESC, "interlock state") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) HTR21X35.ival") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:CP$(CP)2:1$(C)35:OUTPUT") { field(DESC, "actuatorDO output command") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) HTR21X35.Output") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bo, "CHTR:CP$(CP)2:1$(C)35:MANUAL") { field(DESC, "Manual Mode request ") field(PINI, "NO") field(DTYP, "EtherIP") field(OMSL, "supervisory") field(OUT, "@$(PLC_NAME) HTR21X35.Manual B 0") field(ZNAM, "not manual") field(ONAM, "Manual") field(ASG, "CRYO") field(HIGH, "1") field(IVOA, "Don't drive outputs") } record(bo, "CHTR:CP$(CP)2:1$(C)35:SEQUENCER") { field(DESC, "SEQ Mode request ") field(PINI, "NO") field(DTYP, "EtherIP") field(OMSL, "supervisory") field(OUT, "@$(PLC_NAME) HTR21X35.Sequencer B 0") field(ZNAM, "not sequencer") field(ONAM, "Sequencer") field(ASG, "CRYO") field(HIGH, "1") field(IVOA, "Don't drive outputs") } record(ai, "CHTR:CP$(CP)2:1$(C)35:MODE") { field(DESC, "actuator mode (man,ovr,seq)") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) HTR21X35.MODE") } record(bi, "CHTR:CP$(CP)2:1$(C)35:ALM") { field(DESC, "Limit SW alarm") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) HTR21X35.ER") field(ZNAM, "ok") field(ONAM, "alarm") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:CP$(CP)2:1$(C)35:IL_LATCH") { field(DESC, "interlock latched indicator") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) HTR21X35.Interlock_Condition_L") field(ZNAM, "ok") field(ONAM, "latched") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CHTR:CP$(CP)2:1$(C)35:IL_RESET") { field(DESC, "Interlock Latch Reset") field(PINI, "NO") field(DTYP, "EtherIP") field(OMSL, "supervisory") field(OUT, "@$(PLC_NAME) HTR21X35.Interlock_Condition_Reset B 0") field(ZNAM, "not reset") field(ONAM, "RESET") field(ASG, "CRYO") field(HIGH, "1") field(IVOA, "Don't drive outputs") } record(bi, "CHTR:CP$(CP)2:1$(C)35:ZSH") { field(DESC, "High limit sw value") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) HTR21X35.ZSH") field(ZNAM, "not active") field(ONAM, "active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:CP$(CP)2:1$(C)35:ZSL") { field(DESC, "low limit sw value") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) HTR21X35.ZSL") field(ZNAM, "not active") field(ONAM, "active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:CP$(CP)2:1$(C)35:MVAL") { field(DESC, "manual mode output value") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) HTR21X35.mval") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CHTR:CP$(CP)2:1$(C)35:MODE_STRING") { field(DESC, "Actuator (DO) Mode String") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) HTR21X35.Mode_String") } record(bi, "CHTR:CP$(CP)2:1$(C)35:SVAL") { field(DESC, "sequencer mode output value") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) HTR21X35.sval") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CHTR:CP$(CP)2:1$(C)35:PIDTAG") { field(DESC, "Oil heater 21$(C)35 PIDTAG") field(PINI, "YES") field(VAL, "HTR21$(C)35") } record(bi, "CHTR:CP$(CP)2:1$(C)35:SMOD") { field(DESC, "Sequencer mode indicator") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) HTR21X35.smod") field(ZNAM, "inactive") field(ONAM, "active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CHTR:CP$(CP)2:1$(C)35:CMD_OUT") { field(DESC, "rdbk of output signal to the actuator") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) HTR21X35O") field(ZNAM, "off") field(ONAM, "on") } record(mbbiDirect, "CHTR:CP$(CP)2:1$(C)35:SWITCH_DISABLE") { field(DESC, "Indicates if switch(es) are used") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) HTR21X35.Disable B 0") field(NOBT, "16") } #! Further lines contain data used by VisualDCT #! View(1599,2252,1.0) #! Record("CHTR:CP$(CP)2:1$(C)35:MMOD",2500,2499,0,1,"CHTR:CP$(CP)2:1$(C)35:MMOD") #! Record("CHTR:CP$(CP)2:1$(C)35:IMOD",2680,2499,0,1,"CHTR:CP$(CP)2:1$(C)35:IMOD") #! Record("CHTR:CP$(CP)2:1$(C)35:TEXT1",1760,2682,0,1,"CHTR:CP$(CP)2:1$(C)35:TEXT1") #! Record("CHTR:CP$(CP)2:1$(C)35:TEXT2",1760,2782,0,1,"CHTR:CP$(CP)2:1$(C)35:TEXT2") #! Record("CHTR:CP$(CP)2:1$(C)35:INTERLOCK",2500,2719,0,1,"CHTR:CP$(CP)2:1$(C)35:INTERLOCK") #! Record("CHTR:CP$(CP)2:1$(C)35:IVAL",2140,2499,0,1,"CHTR:CP$(CP)2:1$(C)35:IVAL") #! Record("CHTR:CP$(CP)2:1$(C)35:OUTPUT",2680,2279,0,1,"CHTR:CP$(CP)2:1$(C)35:OUTPUT") #! Record("CHTR:CP$(CP)2:1$(C)35:MANUAL",1960,2265,0,1,"CHTR:CP$(CP)2:1$(C)35:MANUAL") #! Record("CHTR:CP$(CP)2:1$(C)35:SEQUENCER",2140,2265,0,1,"CHTR:CP$(CP)2:1$(C)35:SEQUENCER") #! Record("CHTR:CP$(CP)2:1$(C)35:MODE",1760,2274,0,1,"CHTR:CP$(CP)2:1$(C)35:MODE") #! Record("CHTR:CP$(CP)2:1$(C)35:ALM",1960,2719,0,1,"CHTR:CP$(CP)2:1$(C)35:ALM") #! Record("CHTR:CP$(CP)2:1$(C)35:IL_LATCH",2320,2719,0,1,"CHTR:CP$(CP)2:1$(C)35:IL_LATCH") #! Record("CHTR:CP$(CP)2:1$(C)35:IL_RESET",2140,2705,0,1,"CHTR:CP$(CP)2:1$(C)35:IL_RESET") #! Record("CHTR:CP$(CP)2:1$(C)35:ZSH",2700,2719,0,1,"CHTR:CP$(CP)2:1$(C)35:ZSH") #! Record("CHTR:CP$(CP)2:1$(C)35:ZSL",2880,2719,0,1,"CHTR:CP$(CP)2:1$(C)35:ZSL") #! Record("CHTR:CP$(CP)2:1$(C)35:MVAL",2320,2499,0,1,"CHTR:CP$(CP)2:1$(C)35:MVAL") #! Record("CHTR:CP$(CP)2:1$(C)35:MODE_STRING",1760,2434,0,1,"CHTR:CP$(CP)2:1$(C)35:MODE_STRING") #! Record("CHTR:CP$(CP)2:1$(C)35:SVAL",1960,2499,0,1,"CHTR:CP$(CP)2:1$(C)35:SVAL") #! Record("CHTR:CP$(CP)2:1$(C)35:PIDTAG",1760,2582,0,1,"CHTR:CP$(CP)2:1$(C)35:PIDTAG") #! Record("CHTR:CP$(CP)2:1$(C)35:SMOD",2864,2499,0,1,"CHTR:CP$(CP)2:1$(C)35:SMOD") #! Record("CHTR:CP$(CP)2:1$(C)35:CMD_OUT",2860,2286,0,1,"CHTR:CP$(CP)2:1$(C)35:CMD_OUT") #! Record("CHTR:CP$(CP)2:1$(C)35:SWITCH_DISABLE",3060,2720,0,1,"CHTR:CP$(CP)2:1$(C)35:SWITCH_DISABLE") #! TextBox(TB0,1880,2020,2340,2240,0,"Dialog",12,1,16777215,"Generic Actuator records (DO_Record)\n- NOTE this database is the interface to the DO_Record in PLC codes\n- NOTE each of the components using this database\n should also use the on_off_confirm database\nMode\nOverride\nInterlock status\nMode status\nText records\n\nNOTE: there are autosave info fields in this file for the \nTEXT1 and TEXT2 strings that DO NOT show in VDCT",null) #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(bi, "CSV:CP$(CP)2:1$(C)50:MMOD") { field(DESC, "Man. Mode status") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X50.mmod") field(ZNAM, "inactive") field(ONAM, "active") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bi, "CSV:CP$(CP)2:1$(C)50:IMOD") { field(DESC, "Interlock mode") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X50.imod") field(ZNAM, "inactive") field(ONAM, "active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CSV:CP$(CP)2:1$(C)50:TEXT1") { field(DESC, "Notes") field(PINI, "YES") field(DTYP, "Soft Channel") info(autosaveFields, "VAL") } record(stringin, "CSV:CP$(CP)2:1$(C)50:TEXT2") { field(DESC, "Notes") field(PINI, "YES") field(DTYP, "Soft Channel") info(autosaveFields, "VAL") } record(bi, "CSV:CP$(CP)2:1$(C)50:INTERLOCK") { field(DESC, "interlock status") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X50.Interlock_Condition") field(ZNAM, "ok") field(ONAM, "interlocked") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CSV:CP$(CP)2:1$(C)50:IVAL") { field(DESC, "interlock state") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X50.ival") field(ZNAM, "closed") field(ONAM, "open") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CSV:CP$(CP)2:1$(C)50:OUTPUT") { field(DESC, "actuatorDO output command") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X50.Output") field(ZNAM, "closed") field(ONAM, "open") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bo, "CSV:CP$(CP)2:1$(C)50:MANUAL") { field(DESC, "Manual Mode request ") field(PINI, "NO") field(DTYP, "EtherIP") field(OMSL, "supervisory") field(OUT, "@$(PLC_NAME) SV21X50.Manual B 0") field(ZNAM, "not manual") field(ONAM, "Manual") field(ASG, "CRYO") field(HIGH, "1") field(IVOA, "Don't drive outputs") } record(bo, "CSV:CP$(CP)2:1$(C)50:SEQUENCER") { field(DESC, "SEQ Mode request ") field(PINI, "NO") field(DTYP, "EtherIP") field(OMSL, "supervisory") field(OUT, "@$(PLC_NAME) SV21X50.Sequencer B 0") field(ZNAM, "not sequencer") field(ONAM, "Sequencer") field(ASG, "CRYO") field(HIGH, "1") field(IVOA, "Don't drive outputs") } record(ai, "CSV:CP$(CP)2:1$(C)50:MODE") { field(DESC, "actuator mode (man,ovr,seq)") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X50.MODE") } record(bi, "CSV:CP$(CP)2:1$(C)50:ALM") { field(DESC, "Limit SW alarm") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X50.ER") field(ZNAM, "ok") field(ONAM, "alarm") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CSV:CP$(CP)2:1$(C)50:IL_LATCH") { field(DESC, "interlock latched indicator") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X50.Interlock_Condition_L") field(ZNAM, "ok") field(ONAM, "latched") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CSV:CP$(CP)2:1$(C)50:IL_RESET") { field(DESC, "Interlock Latch Reset") field(PINI, "NO") field(DTYP, "EtherIP") field(OMSL, "supervisory") field(OUT, "@$(PLC_NAME) SV21X50.Interlock_Condition_Reset B 0") field(ZNAM, "not reset") field(ONAM, "RESET") field(ASG, "CRYO") field(HIGH, "1") field(IVOA, "Don't drive outputs") } record(bi, "CSV:CP$(CP)2:1$(C)50:ZSH") { field(DESC, "High limit sw value") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X50.ZSH") field(ZNAM, "not active") field(ONAM, "active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CSV:CP$(CP)2:1$(C)50:ZSL") { field(DESC, "low limit sw value") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X50.ZSL") field(ZNAM, "not active") field(ONAM, "active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CSV:CP$(CP)2:1$(C)50:MVAL") { field(DESC, "manual mode output value") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X50.mval") field(ZNAM, "closed") field(ONAM, "open") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CSV:CP$(CP)2:1$(C)50:MODE_STRING") { field(DESC, "Actuator (DO) Mode String") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X50.Mode_String") } record(bi, "CSV:CP$(CP)2:1$(C)50:SVAL") { field(DESC, "sequencer mode output value") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X50.sval") field(ZNAM, "closed") field(ONAM, "open") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CSV:CP$(CP)2:1$(C)50:PIDTAG") { field(DESC, "Sol. valve 21$(C)50 PIDTAG") field(PINI, "YES") field(VAL, "SV21$(C)50") } record(bi, "CSV:CP$(CP)2:1$(C)50:SMOD") { field(DESC, "Sequencer mode indicator") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X50.smod") field(ZNAM, "inactive") field(ONAM, "active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CSV:CP$(CP)2:1$(C)50:CMD_OUT") { field(DESC, "rdbk of output signal to the actuator") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X50O") field(ZNAM, "closed") field(ONAM, "open") } record(mbbiDirect, "CSV:CP$(CP)2:1$(C)50:SWITCH_DISABLE") { field(DESC, "Indicates if switch(es) are used") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X50.Disable B 0") field(NOBT, "16") } #! Further lines contain data used by VisualDCT #! View(1599,2252,1.0) #! Record("CSV:CP$(CP)2:1$(C)50:MMOD",2500,2499,0,1,"CSV:CP$(CP)2:1$(C)50:MMOD") #! Record("CSV:CP$(CP)2:1$(C)50:IMOD",2680,2499,0,1,"CSV:CP$(CP)2:1$(C)50:IMOD") #! Record("CSV:CP$(CP)2:1$(C)50:TEXT1",1760,2682,0,1,"CSV:CP$(CP)2:1$(C)50:TEXT1") #! Record("CSV:CP$(CP)2:1$(C)50:TEXT2",1760,2782,0,1,"CSV:CP$(CP)2:1$(C)50:TEXT2") #! Record("CSV:CP$(CP)2:1$(C)50:INTERLOCK",2500,2719,0,1,"CSV:CP$(CP)2:1$(C)50:INTERLOCK") #! Record("CSV:CP$(CP)2:1$(C)50:IVAL",2140,2499,0,1,"CSV:CP$(CP)2:1$(C)50:IVAL") #! Record("CSV:CP$(CP)2:1$(C)50:OUTPUT",2680,2279,0,1,"CSV:CP$(CP)2:1$(C)50:OUTPUT") #! Record("CSV:CP$(CP)2:1$(C)50:MANUAL",1960,2265,0,1,"CSV:CP$(CP)2:1$(C)50:MANUAL") #! Record("CSV:CP$(CP)2:1$(C)50:SEQUENCER",2140,2265,0,1,"CSV:CP$(CP)2:1$(C)50:SEQUENCER") #! Record("CSV:CP$(CP)2:1$(C)50:MODE",1760,2274,0,1,"CSV:CP$(CP)2:1$(C)50:MODE") #! Record("CSV:CP$(CP)2:1$(C)50:ALM",1960,2719,0,1,"CSV:CP$(CP)2:1$(C)50:ALM") #! Record("CSV:CP$(CP)2:1$(C)50:IL_LATCH",2320,2719,0,1,"CSV:CP$(CP)2:1$(C)50:IL_LATCH") #! Record("CSV:CP$(CP)2:1$(C)50:IL_RESET",2140,2705,0,1,"CSV:CP$(CP)2:1$(C)50:IL_RESET") #! Record("CSV:CP$(CP)2:1$(C)50:ZSH",2700,2719,0,1,"CSV:CP$(CP)2:1$(C)50:ZSH") #! Record("CSV:CP$(CP)2:1$(C)50:ZSL",2880,2719,0,1,"CSV:CP$(CP)2:1$(C)50:ZSL") #! Record("CSV:CP$(CP)2:1$(C)50:MVAL",2320,2499,0,1,"CSV:CP$(CP)2:1$(C)50:MVAL") #! Record("CSV:CP$(CP)2:1$(C)50:MODE_STRING",1760,2434,0,1,"CSV:CP$(CP)2:1$(C)50:MODE_STRING") #! Record("CSV:CP$(CP)2:1$(C)50:SVAL",1960,2499,0,1,"CSV:CP$(CP)2:1$(C)50:SVAL") #! Record("CSV:CP$(CP)2:1$(C)50:PIDTAG",1760,2582,0,1,"CSV:CP$(CP)2:1$(C)50:PIDTAG") #! Record("CSV:CP$(CP)2:1$(C)50:SMOD",2864,2499,0,1,"CSV:CP$(CP)2:1$(C)50:SMOD") #! Record("CSV:CP$(CP)2:1$(C)50:CMD_OUT",2860,2286,0,1,"CSV:CP$(CP)2:1$(C)50:CMD_OUT") #! Record("CSV:CP$(CP)2:1$(C)50:SWITCH_DISABLE",3060,2720,0,1,"CSV:CP$(CP)2:1$(C)50:SWITCH_DISABLE") #! TextBox(TB0,1880,2020,2340,2240,0,"Dialog",12,1,16777215,"Generic Actuator records (DO_Record)\n- NOTE this database is the interface to the DO_Record in PLC codes\n- NOTE each of the components using this database\n should also use the on_off_confirm database\nMode\nOverride\nInterlock status\nMode status\nText records\n\nNOTE: there are autosave info fields in this file for the \nTEXT1 and TEXT2 strings that DO NOT show in VDCT",null) #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(bi, "CSV:CP$(CP)2:1$(C)47:L:MMOD") { field(DESC, "Man. Mode status") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X47L.mmod") field(ZNAM, "inactive") field(ONAM, "active") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bi, "CSV:CP$(CP)2:1$(C)47:L:IMOD") { field(DESC, "Interlock mode") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X47L.imod") field(ZNAM, "inactive") field(ONAM, "active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CSV:CP$(CP)2:1$(C)47:L:TEXT1") { field(DESC, "Notes") field(PINI, "YES") field(DTYP, "Soft Channel") info(autosaveFields, "VAL") } record(stringin, "CSV:CP$(CP)2:1$(C)47:L:TEXT2") { field(DESC, "Notes") field(PINI, "YES") field(DTYP, "Soft Channel") info(autosaveFields, "VAL") } record(bi, "CSV:CP$(CP)2:1$(C)47:L:INTERLOCK") { field(DESC, "interlock status") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X47L.Interlock_Condition") field(ZNAM, "ok") field(ONAM, "interlocked") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CSV:CP$(CP)2:1$(C)47:L:IVAL") { field(DESC, "interlock state") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X47L.ival") field(ZNAM, "no load") field(ONAM, "load") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CSV:CP$(CP)2:1$(C)47:L:OUTPUT") { field(DESC, "actuatorDO output command") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X47L.Output") field(ZNAM, "no load") field(ONAM, "load") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bo, "CSV:CP$(CP)2:1$(C)47:L:MANUAL") { field(DESC, "Manual Mode request ") field(PINI, "NO") field(DTYP, "EtherIP") field(OMSL, "supervisory") field(OUT, "@$(PLC_NAME) SV21X47L.Manual B 0") field(ZNAM, "not manual") field(ONAM, "Manual") field(ASG, "CRYO") field(HIGH, "1") field(IVOA, "Don't drive outputs") } record(bo, "CSV:CP$(CP)2:1$(C)47:L:SEQUENCER") { field(DESC, "SEQ Mode request ") field(PINI, "NO") field(DTYP, "EtherIP") field(OMSL, "supervisory") field(OUT, "@$(PLC_NAME) SV21X47L.Sequencer B 0") field(ZNAM, "not sequencer") field(ONAM, "Sequencer") field(ASG, "CRYO") field(HIGH, "1") field(IVOA, "Don't drive outputs") } record(ai, "CSV:CP$(CP)2:1$(C)47:L:MODE") { field(DESC, "actuator mode (man,ovr,seq)") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X47L.MODE") } record(bi, "CSV:CP$(CP)2:1$(C)47:L:ALM") { field(DESC, "Limit SW alarm") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X47L.ER") field(ZNAM, "ok") field(ONAM, "alarm") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CSV:CP$(CP)2:1$(C)47:L:IL_LATCH") { field(DESC, "interlock latched indicator") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X47L.Interlock_Condition_L") field(ZNAM, "ok") field(ONAM, "latched") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CSV:CP$(CP)2:1$(C)47:L:IL_RESET") { field(DESC, "Interlock Latch Reset") field(PINI, "NO") field(DTYP, "EtherIP") field(OMSL, "supervisory") field(OUT, "@$(PLC_NAME) SV21X47L.Interlock_Condition_Reset B 0") field(ZNAM, "not reset") field(ONAM, "RESET") field(ASG, "CRYO") field(HIGH, "1") field(IVOA, "Don't drive outputs") } record(bi, "CSV:CP$(CP)2:1$(C)47:L:ZSH") { field(DESC, "High limit sw value") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X47L.ZSH") field(ZNAM, "not active") field(ONAM, "active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CSV:CP$(CP)2:1$(C)47:L:ZSL") { field(DESC, "low limit sw value") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X47L.ZSL") field(ZNAM, "not active") field(ONAM, "active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CSV:CP$(CP)2:1$(C)47:L:MVAL") { field(DESC, "manual mode output value") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X47L.mval") field(ZNAM, "no load") field(ONAM, "load") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CSV:CP$(CP)2:1$(C)47:L:MODE_STRING") { field(DESC, "Actuator (DO) Mode String") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X47L.Mode_String") } record(bi, "CSV:CP$(CP)2:1$(C)47:L:SVAL") { field(DESC, "sequencer mode output value") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X47L.sval") field(ZNAM, "no load") field(ONAM, "load") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CSV:CP$(CP)2:1$(C)47:L:PIDTAG") { field(DESC, "Slide valve 21$C()47 Load PIDTAG") field(PINI, "YES") field(VAL, "SV21$(C)47") } record(bi, "CSV:CP$(CP)2:1$(C)47:L:SMOD") { field(DESC, "Sequencer mode indicator") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X47L.smod") field(ZNAM, "inactive") field(ONAM, "active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CSV:CP$(CP)2:1$(C)47:L:CMD_OUT") { field(DESC, "rdbk of output signal to the actuator") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X47LO") field(ZNAM, "no load") field(ONAM, "load") } record(mbbiDirect, "CSV:CP$(CP)2:1$(C)47:L:SWITCH_DISABLE") { field(DESC, "Indicates if switch(es) are used") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X47L.Disable B 0") field(NOBT, "16") } #! Further lines contain data used by VisualDCT #! View(1599,2252,1.0) #! Record("CSV:CP$(CP)2:1$(C)47:L:MMOD",2500,2499,0,1,"CSV:CP$(CP)2:1$(C)47:L:MMOD") #! Record("CSV:CP$(CP)2:1$(C)47:L:IMOD",2680,2499,0,1,"CSV:CP$(CP)2:1$(C)47:L:IMOD") #! Record("CSV:CP$(CP)2:1$(C)47:L:TEXT1",1760,2682,0,1,"CSV:CP$(CP)2:1$(C)47:L:TEXT1") #! Record("CSV:CP$(CP)2:1$(C)47:L:TEXT2",1760,2782,0,1,"CSV:CP$(CP)2:1$(C)47:L:TEXT2") #! Record("CSV:CP$(CP)2:1$(C)47:L:INTERLOCK",2500,2719,0,1,"CSV:CP$(CP)2:1$(C)47:L:INTERLOCK") #! Record("CSV:CP$(CP)2:1$(C)47:L:IVAL",2140,2499,0,1,"CSV:CP$(CP)2:1$(C)47:L:IVAL") #! Record("CSV:CP$(CP)2:1$(C)47:L:OUTPUT",2680,2279,0,1,"CSV:CP$(CP)2:1$(C)47:L:OUTPUT") #! Record("CSV:CP$(CP)2:1$(C)47:L:MANUAL",1960,2265,0,1,"CSV:CP$(CP)2:1$(C)47:L:MANUAL") #! Record("CSV:CP$(CP)2:1$(C)47:L:SEQUENCER",2140,2265,0,1,"CSV:CP$(CP)2:1$(C)47:L:SEQUENCER") #! Record("CSV:CP$(CP)2:1$(C)47:L:MODE",1760,2274,0,1,"CSV:CP$(CP)2:1$(C)47:L:MODE") #! Record("CSV:CP$(CP)2:1$(C)47:L:ALM",1960,2719,0,1,"CSV:CP$(CP)2:1$(C)47:L:ALM") #! Record("CSV:CP$(CP)2:1$(C)47:L:IL_LATCH",2320,2719,0,1,"CSV:CP$(CP)2:1$(C)47:L:IL_LATCH") #! Record("CSV:CP$(CP)2:1$(C)47:L:IL_RESET",2140,2705,0,1,"CSV:CP$(CP)2:1$(C)47:L:IL_RESET") #! Record("CSV:CP$(CP)2:1$(C)47:L:ZSH",2700,2719,0,1,"CSV:CP$(CP)2:1$(C)47:L:ZSH") #! Record("CSV:CP$(CP)2:1$(C)47:L:ZSL",2880,2719,0,1,"CSV:CP$(CP)2:1$(C)47:L:ZSL") #! Record("CSV:CP$(CP)2:1$(C)47:L:MVAL",2320,2499,0,1,"CSV:CP$(CP)2:1$(C)47:L:MVAL") #! Record("CSV:CP$(CP)2:1$(C)47:L:MODE_STRING",1760,2434,0,1,"CSV:CP$(CP)2:1$(C)47:L:MODE_STRING") #! Record("CSV:CP$(CP)2:1$(C)47:L:SVAL",1960,2499,0,1,"CSV:CP$(CP)2:1$(C)47:L:SVAL") #! Record("CSV:CP$(CP)2:1$(C)47:L:PIDTAG",1760,2582,0,1,"CSV:CP$(CP)2:1$(C)47:L:PIDTAG") #! Record("CSV:CP$(CP)2:1$(C)47:L:SMOD",2864,2499,0,1,"CSV:CP$(CP)2:1$(C)47:L:SMOD") #! Record("CSV:CP$(CP)2:1$(C)47:L:CMD_OUT",2860,2286,0,1,"CSV:CP$(CP)2:1$(C)47:L:CMD_OUT") #! Record("CSV:CP$(CP)2:1$(C)47:L:SWITCH_DISABLE",3060,2720,0,1,"CSV:CP$(CP)2:1$(C)47:L:SWITCH_DISABLE") #! TextBox(TB0,1880,2020,2340,2240,0,"Dialog",12,1,16777215,"Generic Actuator records (DO_Record)\n- NOTE this database is the interface to the DO_Record in PLC codes\n- NOTE each of the components using this database\n should also use the on_off_confirm database\nMode\nOverride\nInterlock status\nMode status\nText records\n\nNOTE: there are autosave info fields in this file for the \nTEXT1 and TEXT2 strings that DO NOT show in VDCT",null) #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(bi, "CSV:CP$(CP)2:1$(C)47:U:MMOD") { field(DESC, "Man. Mode status") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X47U.mmod") field(ZNAM, "inactive") field(ONAM, "active") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bi, "CSV:CP$(CP)2:1$(C)47:U:IMOD") { field(DESC, "Interlock mode") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X47U.imod") field(ZNAM, "inactive") field(ONAM, "active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CSV:CP$(CP)2:1$(C)47:U:TEXT1") { field(DESC, "Notes") field(PINI, "YES") field(DTYP, "Soft Channel") info(autosaveFields, "VAL") } record(stringin, "CSV:CP$(CP)2:1$(C)47:U:TEXT2") { field(DESC, "Notes") field(PINI, "YES") field(DTYP, "Soft Channel") info(autosaveFields, "VAL") } record(bi, "CSV:CP$(CP)2:1$(C)47:U:INTERLOCK") { field(DESC, "interlock status") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X47U.Interlock_Condition") field(ZNAM, "ok") field(ONAM, "interlocked") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CSV:CP$(CP)2:1$(C)47:U:IVAL") { field(DESC, "interlock state") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X47U.ival") field(ZNAM, "no unload") field(ONAM, "unload") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CSV:CP$(CP)2:1$(C)47:U:OUTPUT") { field(DESC, "actuatorDO output command") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X47U.Output") field(ZNAM, "no unload") field(ONAM, "unload") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bo, "CSV:CP$(CP)2:1$(C)47:U:MANUAL") { field(DESC, "Manual Mode request ") field(PINI, "NO") field(DTYP, "EtherIP") field(OMSL, "supervisory") field(OUT, "@$(PLC_NAME) SV21X47U.Manual B 0") field(ZNAM, "not manual") field(ONAM, "Manual") field(ASG, "CRYO") field(HIGH, "1") field(IVOA, "Don't drive outputs") } record(bo, "CSV:CP$(CP)2:1$(C)47:U:SEQUENCER") { field(DESC, "SEQ Mode request ") field(PINI, "NO") field(DTYP, "EtherIP") field(OMSL, "supervisory") field(OUT, "@$(PLC_NAME) SV21X47U.Sequencer B 0") field(ZNAM, "not sequencer") field(ONAM, "Sequencer") field(ASG, "CRYO") field(HIGH, "1") field(IVOA, "Don't drive outputs") } record(ai, "CSV:CP$(CP)2:1$(C)47:U:MODE") { field(DESC, "actuator mode (man,ovr,seq)") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X47U.MODE") } record(bi, "CSV:CP$(CP)2:1$(C)47:U:ALM") { field(DESC, "Limit SW alarm") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X47U.ER") field(ZNAM, "ok") field(ONAM, "alarm") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CSV:CP$(CP)2:1$(C)47:U:IL_LATCH") { field(DESC, "interlock latched indicator") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X47U.Interlock_Condition_L") field(ZNAM, "ok") field(ONAM, "latched") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "CSV:CP$(CP)2:1$(C)47:U:IL_RESET") { field(DESC, "Interlock Latch Reset") field(PINI, "NO") field(DTYP, "EtherIP") field(OMSL, "supervisory") field(OUT, "@$(PLC_NAME) SV21X47U.Interlock_Condition_Reset B 0") field(ZNAM, "not reset") field(ONAM, "RESET") field(ASG, "CRYO") field(HIGH, "1") field(IVOA, "Don't drive outputs") } record(bi, "CSV:CP$(CP)2:1$(C)47:U:ZSH") { field(DESC, "High limit sw value") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X47U.ZSH") field(ZNAM, "not active") field(ONAM, "active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CSV:CP$(CP)2:1$(C)47:U:ZSL") { field(DESC, "low limit sw value") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X47U.ZSL") field(ZNAM, "not active") field(ONAM, "active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CSV:CP$(CP)2:1$(C)47:U:MVAL") { field(DESC, "manual mode output value") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X47U.mval") field(ZNAM, "no unload") field(ONAM, "unload") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CSV:CP$(CP)2:1$(C)47:U:MODE_STRING") { field(DESC, "Actuator (DO) Mode String") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X47U.Mode_String") } record(bi, "CSV:CP$(CP)2:1$(C)47:U:SVAL") { field(DESC, "sequencer mode output value") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X47U.sval") field(ZNAM, "no unload") field(ONAM, "unload") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(stringin, "CSV:CP$(CP)2:1$(C)47:U:PIDTAG") { field(DESC, "Slide valve 21$(C)47 Unload PIDTAG") field(PINI, "YES") field(VAL, "SV21$(C)47") } record(bi, "CSV:CP$(CP)2:1$(C)47:U:SMOD") { field(DESC, "Sequencer mode indicator") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X47U.smod") field(ZNAM, "inactive") field(ONAM, "active") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "CSV:CP$(CP)2:1$(C)47:U:CMD_OUT") { field(DESC, "rdbk of output signal to the actuator") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X47UO") field(ZNAM, "no unload") field(ONAM, "unload") } record(mbbiDirect, "CSV:CP$(CP)2:1$(C)47:U:SWITCH_DISABLE") { field(DESC, "Indicates if switch(es) are used") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) SV21X47U.Disable B 0") field(NOBT, "16") } #! Further lines contain data used by VisualDCT #! View(1599,2252,1.0) #! Record("CSV:CP$(CP)2:1$(C)47:U:MMOD",2500,2499,0,1,"CSV:CP$(CP)2:1$(C)47:U:MMOD") #! Record("CSV:CP$(CP)2:1$(C)47:U:IMOD",2680,2499,0,1,"CSV:CP$(CP)2:1$(C)47:U:IMOD") #! Record("CSV:CP$(CP)2:1$(C)47:U:TEXT1",1760,2682,0,1,"CSV:CP$(CP)2:1$(C)47:U:TEXT1") #! Record("CSV:CP$(CP)2:1$(C)47:U:TEXT2",1760,2782,0,1,"CSV:CP$(CP)2:1$(C)47:U:TEXT2") #! Record("CSV:CP$(CP)2:1$(C)47:U:INTERLOCK",2500,2719,0,1,"CSV:CP$(CP)2:1$(C)47:U:INTERLOCK") #! Record("CSV:CP$(CP)2:1$(C)47:U:IVAL",2140,2499,0,1,"CSV:CP$(CP)2:1$(C)47:U:IVAL") #! Record("CSV:CP$(CP)2:1$(C)47:U:OUTPUT",2680,2279,0,1,"CSV:CP$(CP)2:1$(C)47:U:OUTPUT") #! Record("CSV:CP$(CP)2:1$(C)47:U:MANUAL",1960,2265,0,1,"CSV:CP$(CP)2:1$(C)47:U:MANUAL") #! Record("CSV:CP$(CP)2:1$(C)47:U:SEQUENCER",2140,2265,0,1,"CSV:CP$(CP)2:1$(C)47:U:SEQUENCER") #! Record("CSV:CP$(CP)2:1$(C)47:U:MODE",1760,2274,0,1,"CSV:CP$(CP)2:1$(C)47:U:MODE") #! Record("CSV:CP$(CP)2:1$(C)47:U:ALM",1960,2719,0,1,"CSV:CP$(CP)2:1$(C)47:U:ALM") #! Record("CSV:CP$(CP)2:1$(C)47:U:IL_LATCH",2320,2719,0,1,"CSV:CP$(CP)2:1$(C)47:U:IL_LATCH") #! Record("CSV:CP$(CP)2:1$(C)47:U:IL_RESET",2140,2705,0,1,"CSV:CP$(CP)2:1$(C)47:U:IL_RESET") #! Record("CSV:CP$(CP)2:1$(C)47:U:ZSH",2700,2719,0,1,"CSV:CP$(CP)2:1$(C)47:U:ZSH") #! Record("CSV:CP$(CP)2:1$(C)47:U:ZSL",2880,2719,0,1,"CSV:CP$(CP)2:1$(C)47:U:ZSL") #! Record("CSV:CP$(CP)2:1$(C)47:U:MVAL",2320,2499,0,1,"CSV:CP$(CP)2:1$(C)47:U:MVAL") #! Record("CSV:CP$(CP)2:1$(C)47:U:MODE_STRING",1760,2434,0,1,"CSV:CP$(CP)2:1$(C)47:U:MODE_STRING") #! Record("CSV:CP$(CP)2:1$(C)47:U:SVAL",1960,2499,0,1,"CSV:CP$(CP)2:1$(C)47:U:SVAL") #! Record("CSV:CP$(CP)2:1$(C)47:U:PIDTAG",1760,2582,0,1,"CSV:CP$(CP)2:1$(C)47:U:PIDTAG") #! Record("CSV:CP$(CP)2:1$(C)47:U:SMOD",2864,2499,0,1,"CSV:CP$(CP)2:1$(C)47:U:SMOD") #! Record("CSV:CP$(CP)2:1$(C)47:U:CMD_OUT",2860,2286,0,1,"CSV:CP$(CP)2:1$(C)47:U:CMD_OUT") #! Record("CSV:CP$(CP)2:1$(C)47:U:SWITCH_DISABLE",3060,2720,0,1,"CSV:CP$(CP)2:1$(C)47:U:SWITCH_DISABLE") #! TextBox(TB0,1880,2020,2340,2240,0,"Dialog",12,1,16777215,"Generic Actuator records (DO_Record)\n- NOTE this database is the interface to the DO_Record in PLC codes\n- NOTE each of the components using this database\n should also use the on_off_confirm database\nMode\nOverride\nInterlock status\nMode status\nText records\n\nNOTE: there are autosave info fields in this file for the \nTEXT1 and TEXT2 strings that DO NOT show in VDCT",null) #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(stringin, "WCMP:CP$(CP)2:1$(C):SD_STRING") { field(DESC, "Shutdown status string") field(SCAN, "1 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) Compressor_Shutdown_String") } record(ai, "WCMP:CP$(CP)2:1$(C):STATUS_INT") { field(SCAN, "1 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) Comp_Process_Status") field(EGU, "s") field(DESC, "Wcmp process status int") field(PREC, "2") field(ADEL, "0") field(MDEL, "0") field(PINI, "YES") } record(bo, "CMCC:CP$(CP)2:1$(C):ALM_DIS") { field(DESC, "MCC alarm latch reset") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) MCCALM21X_DIS B 0") field(ZNAM, "A") field(ONAM, "I") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") field(OMSL, "supervisory") } record(bo, "WCMP:CP$(CP)2:1$(C):RESET") { field(DESC, "Compressor Reset Rqst") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) Compressor_Reset_X B 0") field(ZNAM, "disabled") field(ONAM, "enabled") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "1") } record(stringin, "WCMP:CP$(CP)2:1$(C):SEQ_STRING") { field(DESC, "Sequence status string") field(SCAN, "1 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) Compressor_Sequence_String") } record(ai, "WCMP:CP$(CP)2:1$(C):SD_INT") { field(SCAN, "1 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) Compressor_SD_Trigger") field(DESC, "Wcmp shutdown integer") field(PREC, "0") field(ADEL, "0") field(MDEL, "0") field(PINI, "YES") } #! Further lines contain data used by VisualDCT #! View(1980,2269,1.0) #! Record("WCMP:CP$(CP)2:1$(C):SD_STRING",2360,2488,0,1,"WCMP:CP$(CP)2:1$(C):SD_STRING") #! Record("WCMP:CP$(CP)2:1$(C):STATUS_INT",2180,2479,0,1,"WCMP:CP$(CP)2:1$(C):STATUS_INT") #! Record("CMCC:CP$(CP)2:1$(C):ALM_DIS",2540,2479,0,1,"CMCC:CP$(CP)2:1$(C):ALM_DIS") #! Record("WCMP:CP$(CP)2:1$(C):RESET",2360,2612,0,1,"WCMP:CP$(CP)2:1$(C):RESET") #! Record("WCMP:CP$(CP)2:1$(C):SEQ_STRING",2721,2488,0,1,"WCMP:CP$(CP)2:1$(C):SEQ_STRING") #! TextBox(TB0,2220,2340,2640,2420,0,"Dialog",12,1,16777215,"Warm Compressor miscellaneous inputs and outputs\nCompressor last shutdown status string and integer\nMCC Alarm Latch reset\nwcmp alarm reset\n\n",null) #! TextBox(TB3,2860,2320,3080,2400,0,"Dialog",12,1,16777215,"Alarm RESETS\nMCC Alarm\nWarm compressor alarms",null) #! TextBox(TB1,2860,2320,3240,2280,0,"Dialog",12,1,16777215,"Warm Compressor Miscellaneous outputs\n",null) #! Record("WCMP:CP$(CP)2:1$(C):SD_INT",2182,2692,0,1,"WCMP:CP$(CP)2:1$(C):SD_INT") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(stringin, "CPMP:CP$(CP)2:1$(C):PIDTAG") { field(DESC, "STATUS P&IDname") field(PINI, "YES") field(VAL, "PMP21$(C)") } record(bi, "CPMP:CP$(CP)2:1$(C):STATUS") { field(DESC, "Oil Pump on/off status") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) OP21X") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("CPMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"CPMP:CP$(CP)2:1$(C):PIDTAG") #! Record("CPMP:CP$(CP)2:1$(C):STATUS",2054,2119,0,1,"CPMP:CP$(CP)2:1$(C):STATUS") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(stringin, "CPMP:CP$(CP)2:1$(C):PIDTAG") { field(DESC, "VFD_FAULT P&IDname") field(PINI, "YES") field(VAL, "PMP21$(C)") } record(bi, "CPMP:CP$(CP)2:1$(C):VFD_FAULT") { field(DESC, "Oil Pump VFD Fault") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) OPVFD21XFLT") field(ZNAM, "fault") field(ONAM, "ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("CPMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"CPMP:CP$(CP)2:1$(C):PIDTAG") #! Record("CPMP:CP$(CP)2:1$(C):VFD_FAULT",2054,2119,0,1,"CPMP:CP$(CP)2:1$(C):VFD_FAULT") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(stringin, "COHC:CP$(CP)2:1$(C)35:PIDTAG") { field(DESC, "CONTACTOR P&IDname") field(PINI, "YES") field(VAL, "OHC21$(C)35") } record(bi, "COHC:CP$(CP)2:1$(C)35:CONTACTOR") { field(DESC, "Oil Heater Contactor") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) OHC21X35") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("COHC:CP$(CP)2:1$(C)35:PIDTAG",2054,2322,0,1,"COHC:CP$(CP)2:1$(C)35:PIDTAG") #! Record("COHC:CP$(CP)2:1$(C)35:CONTACTOR",2054,2119,0,1,"COHC:CP$(CP)2:1$(C)35:CONTACTOR") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(stringin, "CMCC:CP$(CP)2:1$(C):PIDTAG") { field(DESC, "ALM P&IDname") field(PINI, "YES") field(VAL, "MCC21$(C)") } record(bi, "CMCC:CP$(CP)2:1$(C):ALM") { field(DESC, "MCC Alarm") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) MCCALM21X") field(ZNAM, "fault") field(ONAM, "ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("CMCC:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"CMCC:CP$(CP)2:1$(C):PIDTAG") #! Record("CMCC:CP$(CP)2:1$(C):ALM",2054,2119,0,1,"CMCC:CP$(CP)2:1$(C):ALM") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(stringin, "CMCC:CP$(CP)2:1$(C):PIDTAG") { field(DESC, "ALM_L P&IDname") field(PINI, "YES") field(VAL, "MCC21$(C)") } record(bi, "CMCC:CP$(CP)2:1$(C):ALM_L") { field(DESC, "MCC Alarm Latch") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) MCCALM21XL") field(ZNAM, "latched") field(ONAM, "off") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("CMCC:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"CMCC:CP$(CP)2:1$(C):PIDTAG") #! Record("CMCC:CP$(CP)2:1$(C):ALM_L",2054,2119,0,1,"CMCC:CP$(CP)2:1$(C):ALM_L") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(stringin, "WCMP:CP$(CP)2:1$(C):PIDTAG") { field(DESC, "STATUS P&IDname") field(PINI, "YES") field(VAL, "WCMP21$(C)") } record(bi, "WCMP:CP$(CP)2:1$(C):STATUS") { field(DESC, "wcmp on/off status") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) CO21X") field(ZNAM, "off") field(ONAM, "on") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("WCMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"WCMP:CP$(CP)2:1$(C):PIDTAG") #! Record("WCMP:CP$(CP)2:1$(C):STATUS",2054,2119,0,1,"WCMP:CP$(CP)2:1$(C):STATUS") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(stringin, "WCMP:CP$(CP)2:1$(C):PIDTAG") { field(DESC, "RED_ALM P&IDname") field(PINI, "YES") field(VAL, "WCMP21$(C)") } record(bi, "WCMP:CP$(CP)2:1$(C):RED_ALM") { field(DESC, "wcmp red alarm") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) COMP21X_RedALM") field(ZNAM, "ok") field(ONAM, "alarm") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("WCMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"WCMP:CP$(CP)2:1$(C):PIDTAG") #! Record("WCMP:CP$(CP)2:1$(C):RED_ALM",2054,2119,0,1,"WCMP:CP$(CP)2:1$(C):RED_ALM") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(stringin, "WCMP:CP$(CP)2:1$(C):PIDTAG") { field(DESC, "START_FLT P&IDname") field(PINI, "YES") field(VAL, "WCMP21$(C)") } record(bi, "WCMP:CP$(CP)2:1$(C):START_FLT") { field(DESC, "wcmp starter fault") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) OL21X") field(ZNAM, "fault") field(ONAM, "ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("WCMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"WCMP:CP$(CP)2:1$(C):PIDTAG") #! Record("WCMP:CP$(CP)2:1$(C):START_FLT",2054,2119,0,1,"WCMP:CP$(CP)2:1$(C):START_FLT") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(stringin, "WCMP:CP$(CP)2:1$(C):PIDTAG") { field(DESC, "ESTOP P&IDname") field(PINI, "YES") field(VAL, "WCMP21$(C)") } record(bi, "WCMP:CP$(CP)2:1$(C):ESTOP") { field(DESC, "wcmp ESTOP active") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) ES21X") field(ZNAM, "fault") field(ONAM, "ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("WCMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"WCMP:CP$(CP)2:1$(C):PIDTAG") #! Record("WCMP:CP$(CP)2:1$(C):ESTOP",2054,2119,0,1,"WCMP:CP$(CP)2:1$(C):ESTOP") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(stringin, "WCMP:CP$(CP)2:1$(C):PIDTAG") { field(DESC, "LR_MODE P&IDname") field(PINI, "YES") field(VAL, "WCMP21$(C)") } record(bi, "WCMP:CP$(CP)2:1$(C):LR_MODE") { field(DESC, "wcmp Local/Remote") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) LR21X") field(ZNAM, "REMOTE") field(ONAM, "LOCAL") field(ZSV, "NO_ALARM") field(OSV, "MINOR") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("WCMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"WCMP:CP$(CP)2:1$(C):PIDTAG") #! Record("WCMP:CP$(CP)2:1$(C):LR_MODE",2054,2119,0,1,"WCMP:CP$(CP)2:1$(C):LR_MODE") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(stringin, "WCMP:CP$(CP)2:1$(C):PIDTAG") { field(DESC, "LDNG_ALLWD P&IDname") field(PINI, "YES") field(VAL, "WCMP21$(C)") } record(bi, "WCMP:CP$(CP)2:1$(C):LDNG_ALLWD") { field(DESC, "wcmp loading") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) Loading_Allowed") field(ZNAM, "Loading not allowed") field(ONAM, "Loading ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("WCMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"WCMP:CP$(CP)2:1$(C):PIDTAG") #! Record("WCMP:CP$(CP)2:1$(C):LDNG_ALLWD",2054,2119,0,1,"WCMP:CP$(CP)2:1$(C):LDNG_ALLWD") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(stringin, "WCMP:CP$(CP)2:1$(C):PIDTAG") { field(DESC, "RUN_PERM P&IDname") field(PINI, "YES") field(VAL, "WCMP21$(C)") } record(bi, "WCMP:CP$(CP)2:1$(C):RUN_PERM") { field(DESC, "wcmp run permissive") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) Run_Comp_Permissive") field(ZNAM, "not permitted") field(ONAM, "permitted") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("WCMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"WCMP:CP$(CP)2:1$(C):PIDTAG") #! Record("WCMP:CP$(CP)2:1$(C):RUN_PERM",2054,2119,0,1,"WCMP:CP$(CP)2:1$(C):RUN_PERM") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(stringin, "WCMP:CP$(CP)2:1$(C):PIDTAG") { field(DESC, "STOP_PERM P&IDname") field(PINI, "YES") field(VAL, "WCMP21$(C)") } record(bi, "WCMP:CP$(CP)2:1$(C):STOP_PERM") { field(DESC, "wcmp stop permissive") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) Stop_Comp_Permissive") field(ZNAM, "not permitted") field(ONAM, "permitted") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("WCMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"WCMP:CP$(CP)2:1$(C):PIDTAG") #! Record("WCMP:CP$(CP)2:1$(C):STOP_PERM",2054,2119,0,1,"WCMP:CP$(CP)2:1$(C):STOP_PERM") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(stringin, "CPMP:CP$(CP)2:1$(C):PIDTAG") { field(DESC, "RUN_PERM P&IDname") field(PINI, "YES") field(VAL, "PMP21$(C)") } record(bi, "CPMP:CP$(CP)2:1$(C):RUN_PERM") { field(DESC, "pump run permissive") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) Run_Pump_Permissive") field(ZNAM, "not permitted") field(ONAM, "permitted") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("CPMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"CPMP:CP$(CP)2:1$(C):PIDTAG") #! Record("CPMP:CP$(CP)2:1$(C):RUN_PERM",2054,2119,0,1,"CPMP:CP$(CP)2:1$(C):RUN_PERM") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(stringin, "CPMP:CP$(CP)2:1$(C):PIDTAG") { field(DESC, "STOP_PERM P&IDname") field(PINI, "YES") field(VAL, "PMP21$(C)") } record(bi, "CPMP:CP$(CP)2:1$(C):STOP_PERM") { field(DESC, "pump stop permissive") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) Stop_Pump_Permissive") field(ZNAM, "not permitted") field(ONAM, "permitted") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("CPMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"CPMP:CP$(CP)2:1$(C):PIDTAG") #! Record("CPMP:CP$(CP)2:1$(C):STOP_PERM",2054,2119,0,1,"CPMP:CP$(CP)2:1$(C):STOP_PERM") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(stringin, "WCMP:CP$(CP)2:1$(C):PIDTAG") { field(DESC, "C900_TRIP P&IDname") field(PINI, "YES") field(VAL, "WCMP21$(C)") } record(bi, "WCMP:CP$(CP)2:1$(C):C900_TRIP") { field(DESC, "wcmp status trip") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) C900_Trip_Condition") field(ZNAM, "ok") field(ONAM, "TRIP") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("WCMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"WCMP:CP$(CP)2:1$(C):PIDTAG") #! Record("WCMP:CP$(CP)2:1$(C):C900_TRIP",2054,2119,0,1,"WCMP:CP$(CP)2:1$(C):C900_TRIP") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(stringin, "WCMP:CP$(CP)2:1$(C):PIDTAG") { field(DESC, "DP1_TRIP P&IDname") field(PINI, "YES") field(VAL, "WCMP21$(C)") } record(bi, "WCMP:CP$(CP)2:1$(C):DP1_TRIP") { field(DESC, "Oil Pump DP failed 1") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) Oil_Pump_Fail_1") field(ZNAM, "ok") field(ONAM, "TRIP") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("WCMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"WCMP:CP$(CP)2:1$(C):PIDTAG") #! Record("WCMP:CP$(CP)2:1$(C):DP1_TRIP",2054,2119,0,1,"WCMP:CP$(CP)2:1$(C):DP1_TRIP") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(stringin, "WCMP:CP$(CP)2:1$(C):PIDTAG") { field(DESC, "DP2_TRIP P&IDname") field(PINI, "YES") field(VAL, "WCMP21$(C)") } record(bi, "WCMP:CP$(CP)2:1$(C):DP2_TRIP") { field(DESC, "Oil Pump DP failed 2") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) Oil_Pump_Fail_2") field(ZNAM, "ok") field(ONAM, "TRIP") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("WCMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"WCMP:CP$(CP)2:1$(C):PIDTAG") #! Record("WCMP:CP$(CP)2:1$(C):DP2_TRIP",2054,2119,0,1,"WCMP:CP$(CP)2:1$(C):DP2_TRIP") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(stringin, "WCMP:CP$(CP)2:1$(C):PIDTAG") { field(DESC, "UNL_TRIP P&IDname") field(PINI, "YES") field(VAL, "WCMP21$(C)") } record(bi, "WCMP:CP$(CP)2:1$(C):UNL_TRIP") { field(DESC, "Compressor unload failed") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) Comp_Unload_Fail") field(ZNAM, "ok") field(ONAM, "TRIP") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("WCMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"WCMP:CP$(CP)2:1$(C):PIDTAG") #! Record("WCMP:CP$(CP)2:1$(C):UNL_TRIP",2054,2119,0,1,"WCMP:CP$(CP)2:1$(C):UNL_TRIP") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(stringin, "WCMP:CP$(CP)2:1$(C):PIDTAG") { field(DESC, "MTR1_TRIP P&IDname") field(PINI, "YES") field(VAL, "WCMP21$(C)") } record(bi, "WCMP:CP$(CP)2:1$(C):MTR1_TRIP") { field(DESC, "Motor start fault 1") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) Motor_Start_Fault") field(ZNAM, "ok") field(ONAM, "TRIP") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("WCMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"WCMP:CP$(CP)2:1$(C):PIDTAG") #! Record("WCMP:CP$(CP)2:1$(C):MTR1_TRIP",2054,2119,0,1,"WCMP:CP$(CP)2:1$(C):MTR1_TRIP") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(stringin, "WCMP:CP$(CP)2:1$(C):PIDTAG") { field(DESC, "CMP_STAT_TRIP P&IDname") field(PINI, "YES") field(VAL, "WCMP21$(C)") } record(bi, "WCMP:CP$(CP)2:1$(C):CMP_STAT_TRIP") { field(DESC, "Compressor status trip") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) Comp_Status_Trip") field(ZNAM, "ok") field(ONAM, "TRIP") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("WCMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"WCMP:CP$(CP)2:1$(C):PIDTAG") #! Record("WCMP:CP$(CP)2:1$(C):CMP_STAT_TRIP",2054,2119,0,1,"WCMP:CP$(CP)2:1$(C):CMP_STAT_TRIP") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(stringin, "WCMP:CP$(CP)2:1$(C):PIDTAG") { field(DESC, "OP_STAT_TRIP P&IDname") field(PINI, "YES") field(VAL, "WCMP21$(C)") } record(bi, "WCMP:CP$(CP)2:1$(C):OP_STAT_TRIP") { field(DESC, "Oil Pump status trip") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) OP_Status_Trip") field(ZNAM, "ok") field(ONAM, "TRIP") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("WCMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"WCMP:CP$(CP)2:1$(C):PIDTAG") #! Record("WCMP:CP$(CP)2:1$(C):OP_STAT_TRIP",2054,2119,0,1,"WCMP:CP$(CP)2:1$(C):OP_STAT_TRIP") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(stringin, "WCMP:CP$(CP)2:1$(C):PIDTAG") { field(DESC, "OIL_DP_TRIP P&IDname") field(PINI, "YES") field(VAL, "WCMP21$(C)") } record(bi, "WCMP:CP$(CP)2:1$(C):OIL_DP_TRIP") { field(DESC, "Low Oil DiffPress trip") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) Oil_DP_Trip") field(ZNAM, "ok") field(ONAM, "TRIP") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("WCMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"WCMP:CP$(CP)2:1$(C):PIDTAG") #! Record("WCMP:CP$(CP)2:1$(C):OIL_DP_TRIP",2054,2119,0,1,"WCMP:CP$(CP)2:1$(C):OIL_DP_TRIP") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(stringin, "WCMP:CP$(CP)2:1$(C):PIDTAG") { field(DESC, "OP_DISPR_TRIP P&IDname") field(PINI, "YES") field(VAL, "WCMP21$(C)") } record(bi, "WCMP:CP$(CP)2:1$(C):OP_DISPR_TRIP") { field(DESC, "Oil Pump Disch Press trip") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) OP_Dis_Pr_Trip") field(ZNAM, "ok") field(ONAM, "TRIP") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("WCMP:CP$(CP)2:1$(C):PIDTAG",2054,2322,0,1,"WCMP:CP$(CP)2:1$(C):PIDTAG") #! Record("WCMP:CP$(CP)2:1$(C):OP_DISPR_TRIP",2054,2119,0,1,"WCMP:CP$(CP)2:1$(C):OP_DISPR_TRIP") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(bi, "CPSL:CP$(CP)2:1$(C)01:LIMIT_SW") { field(DESC, "Low Suction Pressure ") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) PSL21X01") field(ZNAM, "fault") field(ONAM, "ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(stringin, "CPSL:CP$(CP)2:1$(C)01:PIDTAG") { field(DESC, "Lmt Swch P&IDname") field(PINI, "YES") field(VAL, "PSL21$(C)01") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("CPSL:CP$(CP)2:1$(C)01:LIMIT_SW",2054,2119,0,1,"CPSL:CP$(CP)2:1$(C)01:LIMIT_SW") #! Record("CPSL:CP$(CP)2:1$(C)01:PIDTAG",2054,2322,0,1,"CPSL:CP$(CP)2:1$(C)01:PIDTAG") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(bi, "CPSH:CP$(CP)2:1$(C)12:LIMIT_SW") { field(DESC, "High Disch. Pressure ") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) PSH21X12") field(ZNAM, "fault") field(ONAM, "ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(stringin, "CPSH:CP$(CP)2:1$(C)12:PIDTAG") { field(DESC, "Lmt Swch P&IDname") field(PINI, "YES") field(VAL, "PSH21$(C)12") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("CPSH:CP$(CP)2:1$(C)12:LIMIT_SW",2054,2119,0,1,"CPSH:CP$(CP)2:1$(C)12:LIMIT_SW") #! Record("CPSH:CP$(CP)2:1$(C)12:PIDTAG",2054,2322,0,1,"CPSH:CP$(CP)2:1$(C)12:PIDTAG") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(bi, "CTSH:CP$(CP)2:1$(C)12:LIMIT_SW") { field(DESC, "High Disch. Temp ") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) TSH21X12") field(ZNAM, "fault") field(ONAM, "ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(stringin, "CTSH:CP$(CP)2:1$(C)12:PIDTAG") { field(DESC, "Lmt Swch P&IDname") field(PINI, "YES") field(VAL, "TSH21$(C)12") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("CTSH:CP$(CP)2:1$(C)12:LIMIT_SW",2054,2119,0,1,"CTSH:CP$(CP)2:1$(C)12:LIMIT_SW") #! Record("CTSH:CP$(CP)2:1$(C)12:PIDTAG",2054,2322,0,1,"CTSH:CP$(CP)2:1$(C)12:PIDTAG") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(bi, "CPDL:CP$(CP)2:1$(C)46:LIMIT_SW") { field(DESC, "Low Oil Diff. Press ") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) PDSL21X46") field(ZNAM, "fault") field(ONAM, "ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(stringin, "CPDL:CP$(CP)2:1$(C)46:PIDTAG") { field(DESC, "Lmt Swch P&IDname") field(PINI, "YES") field(VAL, "PDLS21$(C)46") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("CPDL:CP$(CP)2:1$(C)46:LIMIT_SW",2054,2119,0,1,"CPDL:CP$(CP)2:1$(C)46:LIMIT_SW") #! Record("CPDL:CP$(CP)2:1$(C)46:PIDTAG",2054,2322,0,1,"CPDL:CP$(CP)2:1$(C)46:PIDTAG") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(bi, "CSVL:CP$(CP)2:1$(C)50:LIMIT_SW") { field(DESC, "Oil Return Valve SW") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) LS21X50") field(ZNAM, "not closed") field(ONAM, "closed") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") } record(stringin, "CSVL:CP$(CP)2:1$(C)50:PIDTAG") { field(DESC, "Lmt Swch P&IDname") field(PINI, "YES") field(VAL, "LS21$(C)50") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("CSVL:CP$(CP)2:1$(C)50:LIMIT_SW",2054,2119,0,1,"CSVL:CP$(CP)2:1$(C)50:LIMIT_SW") #! Record("CSVL:CP$(CP)2:1$(C)50:PIDTAG",2054,2322,0,1,"CSVL:CP$(CP)2:1$(C)50:PIDTAG") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(bi, "CZSH:CP$(CP)2:1$(C)47:LIMIT_SW") { field(DESC, "fully loaded") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) ZSH21X47") field(ZNAM, "not max") field(ONAM, "max") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") } record(stringin, "CZSH:CP$(CP)2:1$(C)47:PIDTAG") { field(DESC, "Lmt Swch P&IDname") field(PINI, "YES") field(VAL, "ZSH21$(C)47") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("CZSH:CP$(CP)2:1$(C)47:LIMIT_SW",2054,2119,0,1,"CZSH:CP$(CP)2:1$(C)47:LIMIT_SW") #! Record("CZSH:CP$(CP)2:1$(C)47:PIDTAG",2054,2322,0,1,"CZSH:CP$(CP)2:1$(C)47:PIDTAG") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(bi, "CZSL:CP$(CP)2:1$(C)47:LIMIT_SW") { field(DESC, "fully unloaded") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) ZSL21X47") field(ZNAM, "not min") field(ONAM, "min") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") } record(stringin, "CZSL:CP$(CP)2:1$(C)47:PIDTAG") { field(DESC, "Lmt Swch P&IDname") field(PINI, "YES") field(VAL, "ZSL21$(C)47") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("CZSL:CP$(CP)2:1$(C)47:LIMIT_SW",2054,2119,0,1,"CZSL:CP$(CP)2:1$(C)47:LIMIT_SW") #! Record("CZSL:CP$(CP)2:1$(C)47:PIDTAG",2054,2322,0,1,"CZSL:CP$(CP)2:1$(C)47:PIDTAG") #! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(bi, "CTSH:CP$(CP)2:1$(C)35:LIMIT_SW") { field(DESC, "High Oil Temp SW") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) TSH21X35") field(ZNAM, "fault") field(ONAM, "ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(stringin, "CTSH:CP$(CP)2:1$(C)35:PIDTAG") { field(DESC, "Lmt Swch P&IDname") field(PINI, "YES") field(VAL, "TSH21$(C)35") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("CTSH:CP$(CP)2:1$(C)35:LIMIT_SW",2054,2119,0,1,"CTSH:CP$(CP)2:1$(C)35:LIMIT_SW") #! Record("CTSH:CP$(CP)2:1$(C)35:PIDTAG",2054,2322,0,1,"CTSH:CP$(CP)2:1$(C)35:PIDTAG") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(ai, "WCMP:CP$(CP)2:1$(C):LLTMR") { field(SCAN, "1 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) Load_Limit_TMR_Sec") field(EGU, "s") field(DESC, "Load Limit Tmr Secs") field(ADEL, "0") field(MDEL, "0") field(PINI, "YES") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("WCMP:CP$(CP)2:1$(C):LLTMR",2209,2232,0,1,"WCMP:CP$(CP)2:1$(C):LLTMR") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(ai, "WCMP:CP$(CP)2:1$(C):ARTM") { field(SCAN, "1 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) Anti_Recycle_Minutes") field(EGU, "min") field(DESC, "Anti Recylce Minutes") field(ADEL, "0") field(MDEL, "0") field(PINI, "YES") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("WCMP:CP$(CP)2:1$(C):ARTM",2209,2232,0,1,"WCMP:CP$(CP)2:1$(C):ARTM") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(ai, "WCMP:CP$(CP)2:1$(C):ARTS") { field(SCAN, "1 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) Anti_Recycle_Seconds") field(EGU, "s") field(DESC, "Anti Recycle Seconds") field(ADEL, "0") field(MDEL, "0") field(PINI, "YES") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("WCMP:CP$(CP)2:1$(C):ARTS",2209,2232,0,1,"WCMP:CP$(CP)2:1$(C):ARTS") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(ai, "WCMP:CP$(CP)2:1$(C):ODTMR") { field(SCAN, "1 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) Oil_Drain_Timer_Seconds") field(EGU, "s") field(DESC, "Oil Drain Tmr Seconds") field(ADEL, "0") field(MDEL, "0") field(PINI, "YES") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("WCMP:CP$(CP)2:1$(C):ODTMR",2209,2232,0,1,"WCMP:CP$(CP)2:1$(C):ODTMR") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(ai, "WCMP:CP$(CP)2:1$(C):SOUTMR") { field(SCAN, "1 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) Stop_Unload_TMR_Sec") field(EGU, "s") field(DESC, "Stop Unload Tmr Secs") field(ADEL, "0") field(MDEL, "0") field(PINI, "YES") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("WCMP:CP$(CP)2:1$(C):SOUTMR",2209,2232,0,1,"WCMP:CP$(CP)2:1$(C):SOUTMR") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(ai, "WCMP:CP$(CP)2:1$(C):OPTMR1") { field(SCAN, "1 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) Oil_DP_Timer_Seconds") field(EGU, "s") field(DESC, "Oil DP Timer Seconds") field(ADEL, "0") field(MDEL, "0") field(PINI, "YES") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("WCMP:CP$(CP)2:1$(C):OPTMR1",2209,2232,0,1,"WCMP:CP$(CP)2:1$(C):OPTMR1") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(ai, "WCMP:CP$(CP)2:1$(C):OPTMR2") { field(SCAN, "1 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) Oil_Buildup_Tmr_Seconds") field(EGU, "s") field(DESC, "Oil Buildup Tmr Secs") field(ADEL, "0") field(MDEL, "0") field(PINI, "YES") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("WCMP:CP$(CP)2:1$(C):OPTMR2",2209,2232,0,1,"WCMP:CP$(CP)2:1$(C):OPTMR2") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(ai, "WCMP:CP$(CP)2:1$(C):STUTMR") { field(SCAN, "1 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) ZT21X47_TMR_Sec") field(EGU, "s") field(DESC, "ZT21X47 Timer Seconds") field(ADEL, "0") field(MDEL, "0") field(PINI, "YES") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("WCMP:CP$(CP)2:1$(C):STUTMR",2209,2232,0,1,"WCMP:CP$(CP)2:1$(C):STUTMR") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(ai, "WCMP:CP$(CP)2:1$(C):MRTMR") { field(SCAN, "1 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) Motor_Start_Tmr_Seconds") field(EGU, "s") field(DESC, "Motor Start Tmr Secs") field(ADEL, "0") field(MDEL, "0") field(PINI, "YES") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("WCMP:CP$(CP)2:1$(C):MRTMR",2209,2232,0,1,"WCMP:CP$(CP)2:1$(C):MRTMR") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(ai, "WCMP:CP$(CP)2:1$(C):CMPRTM") { field(SCAN, "1 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) TIMER_Comp_Run_Hours_Minutes") field(EGU, "min") field(DESC, "CMP Run Tmr Minutes") field(ADEL, "0") field(MDEL, "0") field(PINI, "YES") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("WCMP:CP$(CP)2:1$(C):CMPRTM",2209,2232,0,1,"WCMP:CP$(CP)2:1$(C):CMPRTM") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(ai, "WCMP:CP$(CP)2:1$(C):CMPRTH") { field(SCAN, "1 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) Timer_Comp_Run_Hours_Old_Time") field(EGU, "hrs") field(DESC, "CMP Run Tmr Hours") field(ADEL, "0") field(MDEL, "0") field(PINI, "YES") } #! Further lines contain data used by VisualDCT #! View(2000,2115,1.0) #! Record("WCMP:CP$(CP)2:1$(C):CMPRTH",2209,2232,0,1,"WCMP:CP$(CP)2:1$(C):CMPRTH")