#! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(mbbiDirect, "PLC:CP08:CR01:CCAlarmL") { field(DESC, "PLC card fault latches") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) Cryocon_AlarmLatch B 0") field(NOBT, "16") field(PINI, "YES") } record(bo, "PLC:CP08:CR01:CCBYPASS_B0") { field(DESC, "Cryocon bypass 0") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) Cryocon_Byp B 0") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(bo, "PLC:CP08:CR01:CCBYPASS_B1") { field(DESC, "Cryocon fault bypass 1") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) Cryocon_Byp B 1") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(bo, "PLC:CP08:CR01:CCBYPASS_B2") { field(DESC, "Cryocon fault bypass 2") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) Cryocon_Byp B 2") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(bi, "PLC:CP08:CR01:CCALARM") { field(DESC, "Cryocon total Alarm") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) Cryocon_Alarm") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "PLC:CP08:CR01:CC2FAILED") { field(DESC, "cryocon 2 failed") field(SCAN, "2 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) Cryocon2.Failed") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") field(ZNAM, "OK") field(ONAM, "FAULT") } record(bi, "PLC:CP08:CR01:CC1FAILED") { field(DESC, "cryocon 1 failed") field(SCAN, "2 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) Cryocon1.Failed") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") field(ZNAM, "OK") field(ONAM, "FAULT") } record(bi, "PLC:CP08:CR01:CC3FAILED") { field(DESC, "cryocon 3 failed") field(SCAN, "2 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) Cryocon3.Failed") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") field(ZNAM, "OK") field(ONAM, "FAULT") } record(bi, "PLC:CP08:CR01:CC4FAILED") { field(DESC, "cryocon 4 failed") field(SCAN, "2 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) Cryocon4.Failed") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") field(ZNAM, "OK") field(ONAM, "FAULT") } record(bi, "PLC:CP08:CR01:CC5FAILED") { field(DESC, "cryocon 5 failed") field(SCAN, "2 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) Cryocon5.Failed") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") field(ZNAM, "OK") field(ONAM, "FAULT") } record(bi, "PLC:CP08:CR01:CC6FAILED") { field(DESC, "cryocon 6 failed") field(SCAN, "2 second") field(PINI, "YES") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) Cryocon6.Failed") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") field(ZNAM, "OK") field(ONAM, "FAULT") } record(bo, "PLC:CP08:CR01:CCBYPASS_B3") { field(DESC, "Cryocon fault bypass 3") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) Cryocon_Byp B 3") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(bo, "PLC:CP08:CR01:CCBYPASS_B4") { field(DESC, "Cryocon fault bypass 4") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) Cryocon_Byp B 4") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(bo, "PLC:CP08:CR01:CCBYPASS_B5") { field(DESC, "Cryocon fault bypass 5") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) Cryocon_Byp B 5") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(bo, "PLC:CP08:CR01:CCBYPASS_B6") { field(DESC, "Cryocon fault bypass 6") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) Cryocon_Byp B 6") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(mbbiDirect, "PLC:CP08:CR01:Alarm1") { field(DESC, "PLC card faults") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) PLC_Alarm[1] B 0") field(NOBT, "16") field(PINI, "YES") } record(bi, "PLC:CP08:CR01:ALARM1_B0") { field(DESC, "ENet Alarm1 B0") field(SCAN, "2 second") field(DTYP, "Soft Channel") field(INP, "PLC:CP08:CR01:Alarm1.B0") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "PLC:CP08:CR01:ALARM1_B1") { field(DESC, "R2S1 ALARM B1") field(SCAN, "2 second") field(DTYP, "Soft Channel") field(INP, "PLC:CP08:CR01:Alarm1.B1") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "PLC:CP08:CR01:ALARM1_B2") { field(DESC, "R2S2 ALARM B2") field(SCAN, "2 second") field(DTYP, "Soft Channel") field(INP, "PLC:CP08:CR01:Alarm1.B2") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "PLC:CP08:CR01:ALARM1_B3") { field(DESC, "R2S3 ALARM B3") field(SCAN, "2 second") field(DTYP, "Soft Channel") field(INP, "PLC:CP08:CR01:Alarm1.B3") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "PLC:CP08:CR01:ALARM1_B4") { field(DESC, "R2S4 ALARM B4") field(SCAN, "2 second") field(DTYP, "Soft Channel") field(INP, "PLC:CP08:CR01:Alarm1.B4") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "PLC:CP08:CR01:ALARM1_B5") { field(DESC, "R2S5ALARM B5") field(SCAN, "2 second") field(DTYP, "Soft Channel") field(INP, "PLC:CP08:CR01:Alarm1.B5") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "PLC:CP08:CR01:ALARM1_B6") { field(DESC, "R2S6 ALARM B6") field(SCAN, "2 second") field(DTYP, "Soft Channel") field(INP, "PLC:CP08:CR01:Alarm1.B6") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "PLC:CP08:CR01:ALARM1_B7") { field(DESC, "R2S7 ALARM B7") field(SCAN, "2 second") field(DTYP, "Soft Channel") field(INP, "PLC:CP08:CR01:Alarm1.B7") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "PLC:CP08:CR01:ALARM1_B8") { field(DESC, "R2S8 ALARM B8") field(SCAN, "2 second") field(DTYP, "Soft Channel") field(INP, "PLC:CP08:CR01:Alarm1.B8") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(mbbiDirect, "PLC:CP08:CR01:AlarmL1") { field(DESC, "PLC card fault latches") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) PLC_AlarmL[1] B 0") field(NOBT, "16") field(PINI, "YES") } record(mbbiDirect, "PLC:CP08:CR01:CH_R2S1FAULTS") { field(DESC, "PLC card channel faults") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) ChannelFaults[18] B 0") field(NOBT, "16") field(PINI, "YES") } record(mbbiDirect, "PLC:CP08:CR01:CH_R2S2FAULTS") { field(DESC, "PLC card channel faults") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) ChannelFaults[19] B 0") field(NOBT, "16") field(PINI, "YES") } record(mbbiDirect, "PLC:CP08:CR01:CH_R2S3FAULTS") { field(DESC, "PLC card channel faults") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) ChannelFaults[20] B 0") field(NOBT, "16") field(PINI, "YES") } record(mbbiDirect, "PLC:CP08:CR01:CH_R2S4FAULTS") { field(DESC, "PLC card channel faults") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) ChannelFaults[21] B 0") field(NOBT, "16") field(PINI, "YES") } record(mbbiDirect, "PLC:CP08:CR01:CH_R2S5FAULTS") { field(DESC, "PLC card channel faults") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) ChannelFaults[22] B 0") field(NOBT, "16") field(PINI, "YES") } record(mbbiDirect, "PLC:CP08:CR01:CH_R2S6FAULTS") { field(DESC, "PLC card channel faults") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) ChannelFaults[23] B 0") field(NOBT, "16") field(PINI, "YES") } record(mbbiDirect, "PLC:CP08:CR01:CH_R2S7FAULTS") { field(DESC, "PLC card channel faults") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) ChannelFaults[24] B 0") field(NOBT, "16") field(PINI, "YES") } record(mbbiDirect, "PLC:CP08:CR01:CH_R2S8FAULTS") { field(DESC, "PLC card channel faults") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) ChannelFaults[25] B 0") field(NOBT, "16") field(PINI, "YES") } record(bo, "PLC:CP08:CR01:BYPASS1_B0") { field(DESC, "Enet Card fault bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp[1] B 0") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(bo, "PLC:CP08:CR01:BYPASS1_B1") { field(DESC, "R2S1 card fault bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp[1] B 1") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(bo, "PLC:CP08:CR01:BYPASS1_B2") { field(DESC, "R2S2 card fault bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp[1] B 2") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(bo, "PLC:CP08:CR01:BYPASS1_B3") { field(DESC, "R2S3 card fault bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp[1] B 3") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(bo, "PLC:CP08:CR01:BYPASS1_B4") { field(DESC, "R2S4 card fault bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp[1] B 4") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(bo, "PLC:CP08:CR01:BYPASS1_B5") { field(DESC, "R2S5 card fault bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp[1] B 5") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(bo, "PLC:CP08:CR01:BYPASS1_B6") { field(DESC, "R2S6 card fault bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp[1] B 6") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(bo, "PLC:CP08:CR01:BYPASS1_B7") { field(DESC, "R2S7 card fault bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp[1] B 7") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(bo, "PLC:CP08:CR01:BYPASS1_B8") { field(DESC, "R2S8 card fault bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp[1] B 8") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(mbbiDirect, "PLC:CP08:CR01:CH_FAULTS11") { field(DESC, "PLC card channel faults") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) ChannelFaults[11] B 0") field(NOBT, "16") field(PINI, "YES") } record(mbbiDirect, "PLC:CP08:CR01:CH_FAULTS12") { field(DESC, "PLC card channel faults") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) ChannelFaults[12] B 0") field(NOBT, "16") field(PINI, "YES") } record(mbbiDirect, "PLC:CP08:CR01:CH_FAULTS13") { field(DESC, "PLC card channel faults") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) ChannelFaults[13] B 0") field(NOBT, "16") field(PINI, "YES") } record(mbbiDirect, "PLC:CP08:CR01:CH_FAULTS14") { field(DESC, "PLC card channel faults") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) ChannelFaults[14] B 0") field(NOBT, "16") field(PINI, "YES") } record(mbbiDirect, "PLC:CP08:CR01:CH_FAULTS10") { field(DESC, "PLC card channel faults") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) ChannelFaults[10] B 0") field(NOBT, "16") field(PINI, "YES") } #! Further lines contain data used by VisualDCT #! View(0,273,1.0) #! Record("PLC:CP08:CR01:CCAlarmL",160,1280,0,1,"PLC:CP08:CR01:CCAlarmL") #! Record("PLC:CP08:CR01:CCBYPASS_B0",160,1079,0,1,"PLC:CP08:CR01:CCBYPASS_B0") #! Record("PLC:CP08:CR01:CCBYPASS_B1",360,1079,0,1,"PLC:CP08:CR01:CCBYPASS_B1") #! Record("PLC:CP08:CR01:CCBYPASS_B2",560,1079,0,1,"PLC:CP08:CR01:CCBYPASS_B2") #! Record("PLC:CP08:CR01:CCALARM",160,859,0,1,"PLC:CP08:CR01:CCALARM") #! Record("PLC:CP08:CR01:CC2FAILED",560,859,0,1,"PLC:CP08:CR01:CC2FAILED") #! Record("PLC:CP08:CR01:CC1FAILED",360,859,0,1,"PLC:CP08:CR01:CC1FAILED") #! Record("PLC:CP08:CR01:CC3FAILED",761,859,0,1,"PLC:CP08:CR01:CC3FAILED") #! Record("PLC:CP08:CR01:CC4FAILED",961,859,0,1,"PLC:CP08:CR01:CC4FAILED") #! Record("PLC:CP08:CR01:CC5FAILED",1160,859,0,1,"PLC:CP08:CR01:CC5FAILED") #! Record("PLC:CP08:CR01:CC6FAILED",1360,859,0,1,"PLC:CP08:CR01:CC6FAILED") #! Record("PLC:CP08:CR01:CCBYPASS_B3",762,1079,0,1,"PLC:CP08:CR01:CCBYPASS_B3") #! Record("PLC:CP08:CR01:CCBYPASS_B4",962,1079,0,1,"PLC:CP08:CR01:CCBYPASS_B4") #! Record("PLC:CP08:CR01:CCBYPASS_B5",1160,1079,0,1,"PLC:CP08:CR01:CCBYPASS_B5") #! Record("PLC:CP08:CR01:CCBYPASS_B6",1360,1079,0,1,"PLC:CP08:CR01:CCBYPASS_B6") #! Record("PLC:CP08:CR01:Alarm1",100,2160,0,1,"PLC:CP08:CR01:Alarm1") #! Field("PLC:CP08:CR01:Alarm1.B0",16777215,0,"PLC:CP08:CR01:Alarm1.B0") #! Field("PLC:CP08:CR01:Alarm1.B1",16777215,1,"PLC:CP08:CR01:Alarm1.B1") #! Field("PLC:CP08:CR01:Alarm1.B2",16777215,1,"PLC:CP08:CR01:Alarm1.B2") #! Field("PLC:CP08:CR01:Alarm1.B3",16777215,1,"PLC:CP08:CR01:Alarm1.B3") #! Field("PLC:CP08:CR01:Alarm1.B4",16777215,1,"PLC:CP08:CR01:Alarm1.B4") #! Field("PLC:CP08:CR01:Alarm1.B5",16777215,1,"PLC:CP08:CR01:Alarm1.B5") #! Field("PLC:CP08:CR01:Alarm1.B6",16777215,1,"PLC:CP08:CR01:Alarm1.B6") #! Field("PLC:CP08:CR01:Alarm1.B7",16777215,1,"PLC:CP08:CR01:Alarm1.B7") #! Field("PLC:CP08:CR01:Alarm1.B8",16777215,0,"PLC:CP08:CR01:Alarm1.B8") #! Record("PLC:CP08:CR01:ALARM1_B0",340,2079,0,1,"PLC:CP08:CR01:ALARM1_B0") #! Field("PLC:CP08:CR01:ALARM1_B0.INP",16777215,0,"PLC:CP08:CR01:ALARM1_B0.INP") #! Link("PLC:CP08:CR01:ALARM1_B0.INP","PLC:CP08:CR01:Alarm1.B0") #! Record("PLC:CP08:CR01:ALARM1_B1",520,2079,0,1,"PLC:CP08:CR01:ALARM1_B1") #! Field("PLC:CP08:CR01:ALARM1_B1.INP",16777215,0,"PLC:CP08:CR01:ALARM1_B1.INP") #! Link("PLC:CP08:CR01:ALARM1_B1.INP","PLC:CP08:CR01:Alarm1.B1") #! Record("PLC:CP08:CR01:ALARM1_B2",700,2079,0,1,"PLC:CP08:CR01:ALARM1_B2") #! Field("PLC:CP08:CR01:ALARM1_B2.INP",16777215,0,"PLC:CP08:CR01:ALARM1_B2.INP") #! Link("PLC:CP08:CR01:ALARM1_B2.INP","PLC:CP08:CR01:Alarm1.B2") #! Record("PLC:CP08:CR01:ALARM1_B3",880,2079,0,1,"PLC:CP08:CR01:ALARM1_B3") #! Field("PLC:CP08:CR01:ALARM1_B3.INP",16777215,0,"PLC:CP08:CR01:ALARM1_B3.INP") #! Link("PLC:CP08:CR01:ALARM1_B3.INP","PLC:CP08:CR01:Alarm1.B3") #! Record("PLC:CP08:CR01:ALARM1_B4",1060,2079,0,1,"PLC:CP08:CR01:ALARM1_B4") #! Field("PLC:CP08:CR01:ALARM1_B4.INP",16777215,0,"PLC:CP08:CR01:ALARM1_B4.INP") #! Link("PLC:CP08:CR01:ALARM1_B4.INP","PLC:CP08:CR01:Alarm1.B4") #! Record("PLC:CP08:CR01:ALARM1_B5",1240,2079,0,1,"PLC:CP08:CR01:ALARM1_B5") #! Field("PLC:CP08:CR01:ALARM1_B5.INP",16777215,0,"PLC:CP08:CR01:ALARM1_B5.INP") #! Link("PLC:CP08:CR01:ALARM1_B5.INP","PLC:CP08:CR01:Alarm1.B5") #! Record("PLC:CP08:CR01:ALARM1_B6",1420,2079,0,1,"PLC:CP08:CR01:ALARM1_B6") #! Field("PLC:CP08:CR01:ALARM1_B6.INP",16777215,0,"PLC:CP08:CR01:ALARM1_B6.INP") #! Link("PLC:CP08:CR01:ALARM1_B6.INP","PLC:CP08:CR01:Alarm1.B6") #! Record("PLC:CP08:CR01:ALARM1_B7",1600,2079,0,1,"PLC:CP08:CR01:ALARM1_B7") #! Field("PLC:CP08:CR01:ALARM1_B7.INP",16777215,0,"PLC:CP08:CR01:ALARM1_B7.INP") #! Link("PLC:CP08:CR01:ALARM1_B7.INP","PLC:CP08:CR01:Alarm1.B7") #! Record("PLC:CP08:CR01:ALARM1_B8",360,2319,0,1,"PLC:CP08:CR01:ALARM1_B8") #! Field("PLC:CP08:CR01:ALARM1_B8.INP",16777215,0,"PLC:CP08:CR01:ALARM1_B8.INP") #! Link("PLC:CP08:CR01:ALARM1_B8.INP","PLC:CP08:CR01:Alarm1.B8") #! Record("PLC:CP08:CR01:AlarmL1",440,1860,0,1,"PLC:CP08:CR01:AlarmL1") #! Record("PLC:CP08:CR01:CH_R2S1FAULTS",140,600,0,1,"PLC:CP08:CR01:CH_R2S1FAULTS") #! Record("PLC:CP08:CR01:CH_R2S2FAULTS",320,600,0,1,"PLC:CP08:CR01:CH_R2S2FAULTS") #! Record("PLC:CP08:CR01:CH_R2S3FAULTS",500,600,0,1,"PLC:CP08:CR01:CH_R2S3FAULTS") #! Record("PLC:CP08:CR01:CH_R2S4FAULTS",680,600,0,1,"PLC:CP08:CR01:CH_R2S4FAULTS") #! Record("PLC:CP08:CR01:CH_R2S5FAULTS",860,600,0,1,"PLC:CP08:CR01:CH_R2S5FAULTS") #! Record("PLC:CP08:CR01:CH_R2S6FAULTS",1040,600,0,1,"PLC:CP08:CR01:CH_R2S6FAULTS") #! Record("PLC:CP08:CR01:CH_R2S7FAULTS",1220,600,0,1,"PLC:CP08:CR01:CH_R2S7FAULTS") #! Record("PLC:CP08:CR01:CH_R2S8FAULTS",1400,600,0,1,"PLC:CP08:CR01:CH_R2S8FAULTS") #! Record("PLC:CP08:CR01:BYPASS1_B0",80,1619,0,1,"PLC:CP08:CR01:BYPASS1_B0") #! Record("PLC:CP08:CR01:BYPASS1_B1",260,1619,0,1,"PLC:CP08:CR01:BYPASS1_B1") #! Record("PLC:CP08:CR01:BYPASS1_B2",440,1619,0,1,"PLC:CP08:CR01:BYPASS1_B2") #! Record("PLC:CP08:CR01:BYPASS1_B3",620,1619,0,1,"PLC:CP08:CR01:BYPASS1_B3") #! Record("PLC:CP08:CR01:BYPASS1_B4",800,1619,0,1,"PLC:CP08:CR01:BYPASS1_B4") #! Record("PLC:CP08:CR01:BYPASS1_B5",980,1619,0,1,"PLC:CP08:CR01:BYPASS1_B5") #! Record("PLC:CP08:CR01:BYPASS1_B6",1160,1619,0,1,"PLC:CP08:CR01:BYPASS1_B6") #! Record("PLC:CP08:CR01:BYPASS1_B7",1340,1619,0,1,"PLC:CP08:CR01:BYPASS1_B7") #! Record("PLC:CP08:CR01:BYPASS1_B8",1520,1619,0,1,"PLC:CP08:CR01:BYPASS1_B8") #! Record("PLC:CP08:CR01:CH_FAULTS11",460,380,0,1,"PLC:CP08:CR01:CH_FAULTS11") #! Record("PLC:CP08:CR01:CH_FAULTS12",640,380,0,1,"PLC:CP08:CR01:CH_FAULTS12") #! Record("PLC:CP08:CR01:CH_FAULTS13",820,380,0,1,"PLC:CP08:CR01:CH_FAULTS13") #! Record("PLC:CP08:CR01:CH_FAULTS14",1000,380,0,1,"PLC:CP08:CR01:CH_FAULTS14") #! Record("PLC:CP08:CR01:CH_FAULTS10",280,380,0,1,"PLC:CP08:CR01:CH_FAULTS10") #! TextBox(TB0,1840,1900,1960,1900,0,"Dialog",12,1,16777215,"Latches for Alarm1",null) #! TextBox(TB7,340,280,880,320,0,"Dialog",12,1,16777215,"CH_FAULTS1 MBBI word - PLC Card Channel Faults\n - additional needed by utility PLC for R1 Slots 10 - 14\n",null) #! TextBox(TB6,221,559,761,599,0,"Dialog",12,1,16777215,"CH_FAULTS1 MBBI word - PLC Card Channel Faults\n - only those additional needed by utility PLC for rack 2\n",null) #! TextBox(TB5,420,1820,900,1860,0,"Dialog",12,1,16777215,"Alarm Latch 1 - Additional alarm latches for Utilities PLC, Rack 2 Slots\n",null) #! TextBox(TB4,520,2040,1000,2080,0,"Dialog",12,1,16777215,"Alarm 1 - Additional fault alarms for Utilities PLC, Rack 2 Slots\n",null) #! TextBox(TB3,580,1540,1060,1580,0,"Dialog",12,1,16777215,"Alarm Bypasses - Additional for Utilities PLC\n",null) #! TextBox(TB2,160,800,640,840,0,"Dialog",12,1,16777215,"Cryocon Alarms, Bypasses, Latches - 6 Cryocons\n",null) #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(bi, "PLC:CP08:CR01:LR_STATUS") { field(DESC, "PLC Local / Remote Status") field(SCAN, "1 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) Local_Remote_Status") field(ZNAM, "Remote") field(ONAM, "Local") field(ZSV, "NO_ALARM") field(OSV, "MINOR") field(PINI, "YES") } record(mbbiDirect, "PLC:CP08:CR01:Alarm") { field(DESC, "PLC Alarm[0] - card faults") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) PLC_Alarm[0] B 0") field(NOBT, "16") field(PINI, "YES") } record(mbbiDirect, "PLC:CP08:CR01:AlarmL") { field(DESC, "PLC card fault latches") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) PLC_AlarmL[0] B 0") field(NOBT, "16") field(PINI, "YES") } record(mbbiDirect, "PLC:CP08:CR01:StatBit") { field(DESC, "PLC Stat Bit") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) PLC_StatBit[0] B 0") field(NOBT, "16") field(PINI, "YES") } record(bi, "PLC:CP08:CR01:ALARM_B2") { field(DESC, "PLC ALARM B2") field(SCAN, "2 second") field(DTYP, "Soft Channel") field(INP, "PLC:CP08:CR01:Alarm.B2") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "PLC:CP08:CR01:ALARM_B3") { field(DESC, "PLC ALARM B3") field(SCAN, "2 second") field(DTYP, "Soft Channel") field(INP, "PLC:CP08:CR01:Alarm.B3") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "PLC:CP08:CR01:ALARM_B4") { field(DESC, "PLC ALARM B4") field(SCAN, "2 second") field(DTYP, "Soft Channel") field(INP, "PLC:CP08:CR01:Alarm.B4") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "PLC:CP08:CR01:STATBIT_B6") { field(DESC, "PLC StatBit 6") field(SCAN, "2 second") field(DTYP, "Soft Channel") field(INP, "PLC:CP08:CR01:StatBit.B6") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bi, "PLC:CP08:CR01:STATBIT_B7") { field(DESC, "PLC StatBit 7") field(SCAN, "2 second") field(DTYP, "Soft Channel") field(INP, "PLC:CP08:CR01:StatBit.B7") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bi, "PLC:CP08:CR01:ALARM_B0") { field(DESC, "PLC R1S0 alarm") field(SCAN, "2 second") field(DTYP, "Soft Channel") field(INP, "PLC:CP08:CR01:Alarm.B0") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "PLC:CP08:CR01:ALARM_B5") { field(DESC, "PLC ALARM B5") field(SCAN, "2 second") field(DTYP, "Soft Channel") field(INP, "PLC:CP08:CR01:Alarm.B5") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "PLC:CP08:CR01:ALARM_B6") { field(DESC, "PLC ALARM B6") field(SCAN, "2 second") field(DTYP, "Soft Channel") field(INP, "PLC:CP08:CR01:Alarm.B6") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "PLC:CP08:CR01:ALARM_B7") { field(DESC, "PLC ALARM B7") field(SCAN, "2 second") field(DTYP, "Soft Channel") field(INP, "PLC:CP08:CR01:Alarm.B7") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "PLC:CP08:CR01:ALARM_B8") { field(DESC, "PLC ALARM B8") field(SCAN, "2 second") field(DTYP, "Soft Channel") field(INP, "PLC:CP08:CR01:Alarm.B8") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "PLC:CP08:CR01:STATBIT_B8") { field(DESC, "PLC StatBit 8") field(SCAN, "2 second") field(DTYP, "Soft Channel") field(INP, "PLC:CP08:CR01:StatBit.B8") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bo, "PLC:CP08:CR01:FAULT_RESET") { field(DESC, "PLC All Faults RESET") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) FaultReset B 0") field(ZNAM, "no reset") field(ONAM, "reset") field(PINI, "NO") field(ASG, "CRYO") field(HIGH, "1") } record(bi, "PLC:CP08:CR01:ALARM_B9") { field(DESC, "PLC ALARM B9") field(SCAN, "2 second") field(DTYP, "Soft Channel") field(INP, "PLC:CP08:CR01:Alarm.B9") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "PLC:CP08:CR01:ALARM_B1") { field(DESC, "PLC Enet Alarm") field(SCAN, "2 second") field(DTYP, "Soft Channel") field(INP, "PLC:CP08:CR01:Alarm.B1") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "PLC:CP08:CR01:STATBIT_B3") { field(DESC, "PLC StatBit 3") field(SCAN, "2 second") field(DTYP, "Soft Channel") field(INP, "PLC:CP08:CR01:StatBit.B3") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bo, "PLC:CP08:CR01:BYPASS_B0") { field(DESC, "PLC fault bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp[0] B 0") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(bo, "PLC:CP08:CR01:BYPASS_B1") { field(DESC, "Enet card fault bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp[0] B 1") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(bo, "PLC:CP08:CR01:BYPASS_B2") { field(DESC, "R1S2 card fault bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp[0] B 2") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(bo, "PLC:CP08:CR01:BYPASS_B3") { field(DESC, "R1S3 card fault bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp[0] B 3") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(bo, "PLC:CP08:CR01:BYPASS_B4") { field(DESC, "R1S4 card fault bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp[0] B 4") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(bo, "PLC:CP08:CR01:BYPASS_B5") { field(DESC, "R1S5 card fault bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp[0] B 5") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(bo, "PLC:CP08:CR01:BYPASS_B6") { field(DESC, "R1S6 card fault bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp[0] B 6") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(bo, "PLC:CP08:CR01:BYPASS_B7") { field(DESC, "R1S7 card fault bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp[0] B 7") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(bo, "PLC:CP08:CR01:BYPASS_B8") { field(DESC, "R1S8 card fault bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp[0] B 8") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(bo, "PLC:CP08:CR01:BYPASS_B9") { field(DESC, "R1S9 card fault bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp[0] B 9") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(bo, "PLC:CP08:CR01:BYPASS_B10") { field(DESC, "R1S10 card fault bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp[0] B 10") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(bo, "PLC:CP08:CR01:BYPASS_B11") { field(DESC, "R1S11 card fault bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp[0] B 11") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(bo, "PLC:CP08:CR01:BYPASS_B12") { field(DESC, "R1S12 card fault bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp[0] B 12") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(bo, "PLC:CP08:CR01:BYPASS_B13") { field(DESC, "R1S13 card fault bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp[0] B 13") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(bo, "PLC:CP08:CR01:BYPASS_B14") { field(DESC, "R1S14 card fault bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp[0] B 14") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(bo, "PLC:CP08:CR01:BYPASS_B15") { field(DESC, "R1S16 card fault bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp[0] B 15") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(bi, "PLC:CP08:CR01:ALARM_B10") { field(DESC, "PLC ALARM B10") field(SCAN, "2 second") field(DTYP, "Soft Channel") field(INP, "PLC:CP08:CR01:Alarm.BA") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "PLC:CP08:CR01:ALARM_B11") { field(DESC, "PLC ALARM B11") field(SCAN, "2 second") field(DTYP, "Soft Channel") field(INP, "PLC:CP08:CR01:Alarm.BB") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(mbbiDirect, "PLC:CP08:CR01:CH_FAULTS3") { field(DESC, "PLC card channel faults") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) ChannelFaults[3] B 0") field(NOBT, "16") field(PINI, "YES") } record(mbbiDirect, "PLC:CP08:CR01:CH_FAULTS4") { field(DESC, "PLC card channel faults") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) ChannelFaults[4] B 0") field(NOBT, "16") field(PINI, "YES") } record(mbbiDirect, "PLC:CP08:CR01:CH_FAULTS5") { field(DESC, "PLC card channel faults") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) ChannelFaults[5] B 0") field(NOBT, "16") field(PINI, "YES") } record(mbbiDirect, "PLC:CP08:CR01:CH_FAULTS1A") { field(DESC, "PLC card channel faults") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) ChannelFaults[1] B 16") field(NOBT, "16") field(PINI, "YES") } record(mbbiDirect, "PLC:CP08:CR01:CH_FAULTS6") { field(DESC, "PLC card channel faults") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) ChannelFaults[6] B 0") field(NOBT, "16") field(PINI, "YES") } record(mbbiDirect, "PLC:CP08:CR01:CH_FAULTS7") { field(DESC, "PLC card channel faults") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) ChannelFaults[7] B 0") field(NOBT, "16") field(PINI, "YES") } record(mbbiDirect, "PLC:CP08:CR01:CH_FAULTS8") { field(DESC, "PLC card channel faults") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) ChannelFaults[8] B 0") field(NOBT, "16") field(PINI, "YES") } record(mbbiDirect, "PLC:CP08:CR01:CH_FAULTS9") { field(DESC, "PLC card channel faults") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) ChannelFaults[9] B 0") field(NOBT, "16") field(PINI, "YES") } record(mbbiDirect, "PLC:CP08:CR01:CH_FAULTS2A") { field(DESC, "PLC card channel faults") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) ChannelFaults[2] B 16") field(NOBT, "16") field(PINI, "YES") } record(mbbiDirect, "PLC:CP08:CR01:CH_FAULTS0A") { field(DESC, "PLC card channel faults") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) ChannelFaults[0] B 16") field(NOBT, "16") field(PINI, "YES") } record(bi, "PLC:CP08:CR01:ALARM_B12") { field(DESC, "PLC ALARM B12") field(SCAN, "2 second") field(DTYP, "Soft Channel") field(INP, "PLC:CP08:CR01:Alarm.BC") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "PLC:CP08:CR01:ALARM_B13") { field(DESC, "PLC ALARM B13") field(SCAN, "2 second") field(DTYP, "Soft Channel") field(INP, "PLC:CP08:CR01:Alarm.BD") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "PLC:CP08:CR01:ALARM_B14") { field(DESC, "PLC ALARM B14") field(SCAN, "2 second") field(DTYP, "Soft Channel") field(INP, "PLC:CP08:CR01:Alarm.BE") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "PLC:CP08:CR01:ALARM_B15") { field(DESC, "PLC ALARM B15") field(SCAN, "2 second") field(DTYP, "Soft Channel") field(INP, "PLC:CP08:CR01:Alarm.BF") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "PLC:CP08:CR01:BYPASS2_B0") { field(DESC, "All Faults Bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp[2] B 0") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(bo, "PLC:CP08:CR01:BYPASS2_B1") { field(DESC, "major Faults bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp[2] B 1") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(bo, "PLC:CP08:CR01:BYPASS2_B2") { field(DESC, "Minor Faults bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp[2] B 2") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(mbbiDirect, "PLC:CP08:CR01:CH_FAULTS4A") { field(DESC, "PLC card channel faults") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) ChannelFaults[4] B 16") field(NOBT, "16") field(PINI, "YES") } record(mbbiDirect, "PLC:CP08:CR01:CH_FAULTS6A") { field(DESC, "PLC card channel faults") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) ChannelFaults[6] B 16") field(NOBT, "16") field(PINI, "YES") } record(mbbiDirect, "PLC:CP08:CR01:CH_FAULTS2") { field(DESC, "PLC card channel faults") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) ChannelFaults[2] B 0") field(NOBT, "16") field(PINI, "YES") } record(mbbiDirect, "PLC:CP08:CR01:CH_FAULTS3A") { field(DESC, "PLC card channel faults") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) ChannelFaults[3] B 16") field(NOBT, "16") field(PINI, "YES") } record(mbbiDirect, "PLC:CP08:CR01:CH_FAULTS0") { field(DESC, "PLC card channel faults") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) ChannelFaults[0] B 0") field(NOBT, "16") field(PINI, "YES") } record(mbbiDirect, "PLC:CP08:CR01:CH_FAULTS1") { field(DESC, "PLC card channel faults") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) ChannelFaults[1] B 0") field(NOBT, "16") field(PINI, "YES") } record(mbbiDirect, "PLC:CP08:CR01:AlarmL2") { field(DESC, "PLC card fault latches") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) PLC_AlarmL[2] B 0") field(NOBT, "16") field(PINI, "YES") } record(mbbiDirect, "PLC:CP08:CR01:Alarm2") { field(DESC, "PLC Alarm[0] - card faults") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) PLC_Alarm[2] B 0") field(NOBT, "16") field(PINI, "YES") } record(bi, "PLC:CP08:CR01:ALARM2_B0") { field(DESC, "All Alarms alarm") field(SCAN, "2 second") field(DTYP, "Soft Channel") field(INP, "PLC:CP08:CR01:Alarm2.B0") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "PLC:CP08:CR01:ALARM2_B1") { field(DESC, "Major Alarms") field(SCAN, "2 second") field(DTYP, "Soft Channel") field(INP, "PLC:CP08:CR01:Alarm2.B1") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "PLC:CP08:CR01:ALARM2_B2") { field(DESC, "Minor Alarms") field(SCAN, "2 second") field(DTYP, "Soft Channel") field(INP, "PLC:CP08:CR01:Alarm2.B2") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "PLC:CP08:CR01:ALARM2_B3") { field(DESC, "Alarm 2 B3") field(SCAN, "2 second") field(DTYP, "Soft Channel") field(INP, "PLC:CP08:CR01:Alarm2.B3") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "PLC:CP08:CR01:ALARM2_B4") { field(DESC, "Alarm 2 B4") field(SCAN, "2 second") field(DTYP, "Soft Channel") field(INP, "PLC:CP08:CR01:Alarm2.B4") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "PLC:CP08:CR01:ALARM2_B5") { field(DESC, "Alarm 2 B5") field(SCAN, "2 second") field(DTYP, "Soft Channel") field(INP, "PLC:CP08:CR01:Alarm2.B5") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "PLC:CP08:CR01:ALARM2_B6") { field(DESC, "PLC ALARM2 B6") field(SCAN, "2 second") field(DTYP, "Soft Channel") field(INP, "PLC:CP08:CR01:Alarm2.B6") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "PLC:CP08:CR01:ALARM2_B7") { field(DESC, "Alarm2 B7") field(SCAN, "2 second") field(DTYP, "Soft Channel") field(INP, "PLC:CP08:CR01:Alarm2.B7") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "PLC:CP08:CR01:ALARM2_B8") { field(DESC, "PLC ALARM2 B8") field(SCAN, "2 second") field(DTYP, "Soft Channel") field(INP, "PLC:CP08:CR01:Alarm2.B8") field(ZNAM, "OK") field(ONAM, "FAULT") field(PINI, "YES") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bo, "PLC:CP08:CR01:BYPASS2_B3") { field(DESC, "Minor Faults bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp[2] B 3") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(bo, "PLC:CP08:CR01:BYPASS2_B4") { field(DESC, "Minor Faults bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp[2] B 4") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(bo, "PLC:CP08:CR01:BYPASS2_B5") { field(DESC, "Minor Faults bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp[2] B 5") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(bo, "PLC:CP08:CR01:BYPASS2_B6") { field(DESC, "Minor Faults bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp[2] B 6") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(bo, "PLC:CP08:CR01:BYPASS2_B7") { field(DESC, "Minor Faults bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp[2] B 7") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } record(bo, "PLC:CP08:CR01:BYPASS2_B8") { field(DESC, "Minor Faults bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp[2] B 8") field(ZNAM, "ACT") field(ONAM, "BYP") field(ASG, "CRYO") field(PINI, "NO") field(HIGH, "0") } #! Further lines contain data used by VisualDCT #! View(0,1466,0.9) #! Record("PLC:CP08:CR01:LR_STATUS",1540,777,0,1,"PLC:CP08:CR01:LR_STATUS") #! Record("PLC:CP08:CR01:Alarm",80,799,0,1,"PLC:CP08:CR01:Alarm") #! Field("PLC:CP08:CR01:Alarm.B2",16777215,1,"PLC:CP08:CR01:Alarm.B2") #! Field("PLC:CP08:CR01:Alarm.B3",16777215,1,"PLC:CP08:CR01:Alarm.B3") #! Field("PLC:CP08:CR01:Alarm.B4",16777215,1,"PLC:CP08:CR01:Alarm.B4") #! Field("PLC:CP08:CR01:Alarm.B5",16777215,1,"PLC:CP08:CR01:Alarm.B5") #! Field("PLC:CP08:CR01:Alarm.B6",16777215,1,"PLC:CP08:CR01:Alarm.B6") #! Field("PLC:CP08:CR01:Alarm.B8",16777215,1,"PLC:CP08:CR01:Alarm.B8") #! Field("PLC:CP08:CR01:Alarm.B7",16777215,1,"PLC:CP08:CR01:Alarm.B7") #! Field("PLC:CP08:CR01:Alarm.B9",16777215,1,"PLC:CP08:CR01:Alarm.B9") #! Field("PLC:CP08:CR01:Alarm.B0",16777215,0,"PLC:CP08:CR01:Alarm.B0") #! Field("PLC:CP08:CR01:Alarm.B1",16777215,1,"PLC:CP08:CR01:Alarm.B1") #! Field("PLC:CP08:CR01:Alarm.BA",16777215,1,"PLC:CP08:CR01:Alarm.BA") #! Field("PLC:CP08:CR01:Alarm.BB",16777215,1,"PLC:CP08:CR01:Alarm.BB") #! Field("PLC:CP08:CR01:Alarm.BC",16777215,0,"PLC:CP08:CR01:Alarm.BC") #! Field("PLC:CP08:CR01:Alarm.BD",16777215,1,"PLC:CP08:CR01:Alarm.BD") #! Field("PLC:CP08:CR01:Alarm.BE",16777215,1,"PLC:CP08:CR01:Alarm.BE") #! Field("PLC:CP08:CR01:Alarm.BF",16777215,1,"PLC:CP08:CR01:Alarm.BF") #! Record("PLC:CP08:CR01:AlarmL",1180,1259,0,1,"PLC:CP08:CR01:AlarmL") #! Record("PLC:CP08:CR01:StatBit",60,1639,0,1,"PLC:CP08:CR01:StatBit") #! Field("PLC:CP08:CR01:StatBit.B6",16777215,1,"PLC:CP08:CR01:StatBit.B6") #! Field("PLC:CP08:CR01:StatBit.B8",16777215,1,"PLC:CP08:CR01:StatBit.B8") #! Field("PLC:CP08:CR01:StatBit.B7",16777215,1,"PLC:CP08:CR01:StatBit.B7") #! Field("PLC:CP08:CR01:StatBit.B3",16777215,1,"PLC:CP08:CR01:StatBit.B3") #! Record("PLC:CP08:CR01:ALARM_B2",680,717,0,1,"PLC:CP08:CR01:ALARM_B2") #! Field("PLC:CP08:CR01:ALARM_B2.INP",16777215,0,"PLC:CP08:CR01:ALARM_B2.INP") #! Link("PLC:CP08:CR01:ALARM_B2.INP","PLC:CP08:CR01:Alarm.B2") #! Record("PLC:CP08:CR01:ALARM_B3",860,717,0,1,"PLC:CP08:CR01:ALARM_B3") #! Field("PLC:CP08:CR01:ALARM_B3.INP",16777215,0,"PLC:CP08:CR01:ALARM_B3.INP") #! Link("PLC:CP08:CR01:ALARM_B3.INP","PLC:CP08:CR01:Alarm.B3") #! Record("PLC:CP08:CR01:ALARM_B4",1040,717,0,1,"PLC:CP08:CR01:ALARM_B4") #! Field("PLC:CP08:CR01:ALARM_B4.INP",16777215,0,"PLC:CP08:CR01:ALARM_B4.INP") #! Link("PLC:CP08:CR01:ALARM_B4.INP","PLC:CP08:CR01:Alarm.B4") #! Record("PLC:CP08:CR01:STATBIT_B6",540,1817,0,1,"PLC:CP08:CR01:STATBIT_B6") #! Field("PLC:CP08:CR01:STATBIT_B6.INP",16777215,0,"PLC:CP08:CR01:STATBIT_B6.INP") #! Link("PLC:CP08:CR01:STATBIT_B6.INP","PLC:CP08:CR01:StatBit.B6") #! Record("PLC:CP08:CR01:STATBIT_B7",720,1817,0,1,"PLC:CP08:CR01:STATBIT_B7") #! Field("PLC:CP08:CR01:STATBIT_B7.INP",16777215,0,"PLC:CP08:CR01:STATBIT_B7.INP") #! Link("PLC:CP08:CR01:STATBIT_B7.INP","PLC:CP08:CR01:StatBit.B7") #! Record("PLC:CP08:CR01:ALARM_B0",320,717,0,1,"PLC:CP08:CR01:ALARM_B0") #! Field("PLC:CP08:CR01:ALARM_B0.INP",16777215,0,"PLC:CP08:CR01:ALARM_B0.INP") #! Link("PLC:CP08:CR01:ALARM_B0.INP","PLC:CP08:CR01:Alarm.B0") #! Record("PLC:CP08:CR01:ALARM_B5",1220,717,0,1,"PLC:CP08:CR01:ALARM_B5") #! Field("PLC:CP08:CR01:ALARM_B5.INP",16777215,0,"PLC:CP08:CR01:ALARM_B5.INP") #! Link("PLC:CP08:CR01:ALARM_B5.INP","PLC:CP08:CR01:Alarm.B5") #! Record("PLC:CP08:CR01:ALARM_B6",360,957,0,1,"PLC:CP08:CR01:ALARM_B6") #! Field("PLC:CP08:CR01:ALARM_B6.INP",16777215,0,"PLC:CP08:CR01:ALARM_B6.INP") #! Link("PLC:CP08:CR01:ALARM_B6.INP","PLC:CP08:CR01:Alarm.B6") #! Record("PLC:CP08:CR01:ALARM_B7",540,957,0,1,"PLC:CP08:CR01:ALARM_B7") #! Field("PLC:CP08:CR01:ALARM_B7.INP",16777215,0,"PLC:CP08:CR01:ALARM_B7.INP") #! Link("PLC:CP08:CR01:ALARM_B7.INP","PLC:CP08:CR01:Alarm.B7") #! Record("PLC:CP08:CR01:ALARM_B8",720,957,0,1,"PLC:CP08:CR01:ALARM_B8") #! Field("PLC:CP08:CR01:ALARM_B8.INP",16777215,0,"PLC:CP08:CR01:ALARM_B8.INP") #! Link("PLC:CP08:CR01:ALARM_B8.INP","PLC:CP08:CR01:Alarm.B8") #! Record("PLC:CP08:CR01:STATBIT_B8",900,1817,0,1,"PLC:CP08:CR01:STATBIT_B8") #! Field("PLC:CP08:CR01:STATBIT_B8.INP",16777215,0,"PLC:CP08:CR01:STATBIT_B8.INP") #! Link("PLC:CP08:CR01:STATBIT_B8.INP","PLC:CP08:CR01:StatBit.B8") #! Record("PLC:CP08:CR01:FAULT_RESET",1540,1037,0,1,"PLC:CP08:CR01:FAULT_RESET") #! Record("PLC:CP08:CR01:ALARM_B9",900,957,0,1,"PLC:CP08:CR01:ALARM_B9") #! Field("PLC:CP08:CR01:ALARM_B9.INP",16777215,0,"PLC:CP08:CR01:ALARM_B9.INP") #! Link("PLC:CP08:CR01:ALARM_B9.INP","PLC:CP08:CR01:Alarm.B9") #! Record("PLC:CP08:CR01:ALARM_B1",500,717,0,1,"PLC:CP08:CR01:ALARM_B1") #! Field("PLC:CP08:CR01:ALARM_B1.INP",16777215,0,"PLC:CP08:CR01:ALARM_B1.INP") #! Link("PLC:CP08:CR01:ALARM_B1.INP","PLC:CP08:CR01:Alarm.B1") #! Record("PLC:CP08:CR01:STATBIT_B3",340,1777,0,1,"PLC:CP08:CR01:STATBIT_B3") #! Field("PLC:CP08:CR01:STATBIT_B3.INP",16777215,0,"PLC:CP08:CR01:STATBIT_B3.INP") #! Link("PLC:CP08:CR01:STATBIT_B3.INP","PLC:CP08:CR01:StatBit.B3") #! Record("PLC:CP08:CR01:BYPASS_B0",20,97,0,1,"PLC:CP08:CR01:BYPASS_B0") #! Record("PLC:CP08:CR01:BYPASS_B1",200,97,0,1,"PLC:CP08:CR01:BYPASS_B1") #! Record("PLC:CP08:CR01:BYPASS_B2",380,97,0,1,"PLC:CP08:CR01:BYPASS_B2") #! Record("PLC:CP08:CR01:BYPASS_B3",560,97,0,1,"PLC:CP08:CR01:BYPASS_B3") #! Record("PLC:CP08:CR01:BYPASS_B4",740,97,0,1,"PLC:CP08:CR01:BYPASS_B4") #! Record("PLC:CP08:CR01:BYPASS_B5",920,97,0,1,"PLC:CP08:CR01:BYPASS_B5") #! Record("PLC:CP08:CR01:BYPASS_B6",1100,97,0,1,"PLC:CP08:CR01:BYPASS_B6") #! Record("PLC:CP08:CR01:BYPASS_B7",1280,97,0,1,"PLC:CP08:CR01:BYPASS_B7") #! Record("PLC:CP08:CR01:BYPASS_B8",20,377,0,1,"PLC:CP08:CR01:BYPASS_B8") #! Record("PLC:CP08:CR01:BYPASS_B9",200,377,0,1,"PLC:CP08:CR01:BYPASS_B9") #! Record("PLC:CP08:CR01:BYPASS_B10",380,377,0,1,"PLC:CP08:CR01:BYPASS_B10") #! Record("PLC:CP08:CR01:BYPASS_B11",560,377,0,1,"PLC:CP08:CR01:BYPASS_B11") #! Record("PLC:CP08:CR01:BYPASS_B12",740,377,0,1,"PLC:CP08:CR01:BYPASS_B12") #! Record("PLC:CP08:CR01:BYPASS_B13",920,377,0,1,"PLC:CP08:CR01:BYPASS_B13") #! Record("PLC:CP08:CR01:BYPASS_B14",1100,377,0,1,"PLC:CP08:CR01:BYPASS_B14") #! Record("PLC:CP08:CR01:BYPASS_B15",1280,377,0,1,"PLC:CP08:CR01:BYPASS_B15") #! Record("PLC:CP08:CR01:ALARM_B10",1083,957,0,1,"PLC:CP08:CR01:ALARM_B10") #! Field("PLC:CP08:CR01:ALARM_B10.INP",16777215,0,"PLC:CP08:CR01:ALARM_B10.INP") #! Link("PLC:CP08:CR01:ALARM_B10.INP","PLC:CP08:CR01:Alarm.BA") #! Record("PLC:CP08:CR01:ALARM_B11",1260,957,0,1,"PLC:CP08:CR01:ALARM_B11") #! Field("PLC:CP08:CR01:ALARM_B11.INP",16777215,0,"PLC:CP08:CR01:ALARM_B11.INP") #! Link("PLC:CP08:CR01:ALARM_B11.INP","PLC:CP08:CR01:Alarm.BB") #! Record("PLC:CP08:CR01:CH_FAULTS3",680,2099,0,1,"PLC:CP08:CR01:CH_FAULTS3") #! Record("PLC:CP08:CR01:CH_FAULTS4",860,2099,0,1,"PLC:CP08:CR01:CH_FAULTS4") #! Record("PLC:CP08:CR01:CH_FAULTS5",1040,2099,0,1,"PLC:CP08:CR01:CH_FAULTS5") #! Record("PLC:CP08:CR01:CH_FAULTS1A",280,2259,0,1,"PLC:CP08:CR01:CH_FAULTS1A") #! Record("PLC:CP08:CR01:CH_FAULTS6",1220,2099,0,1,"PLC:CP08:CR01:CH_FAULTS6") #! Record("PLC:CP08:CR01:CH_FAULTS7",1400,2099,0,1,"PLC:CP08:CR01:CH_FAULTS7") #! Record("PLC:CP08:CR01:CH_FAULTS8",1580,2099,0,1,"PLC:CP08:CR01:CH_FAULTS8") #! Record("PLC:CP08:CR01:CH_FAULTS9",1760,2099,0,1,"PLC:CP08:CR01:CH_FAULTS9") #! Record("PLC:CP08:CR01:CH_FAULTS2A",480,2259,0,1,"PLC:CP08:CR01:CH_FAULTS2A") #! Record("PLC:CP08:CR01:CH_FAULTS0A",100,2259,0,1,"PLC:CP08:CR01:CH_FAULTS0A") #! Record("PLC:CP08:CR01:ALARM_B12",366,1197,0,1,"PLC:CP08:CR01:ALARM_B12") #! Field("PLC:CP08:CR01:ALARM_B12.INP",16777215,0,"PLC:CP08:CR01:ALARM_B12.INP") #! Link("PLC:CP08:CR01:ALARM_B12.INP","PLC:CP08:CR01:Alarm.BC") #! Record("PLC:CP08:CR01:ALARM_B13",546,1197,0,1,"PLC:CP08:CR01:ALARM_B13") #! Field("PLC:CP08:CR01:ALARM_B13.INP",16777215,0,"PLC:CP08:CR01:ALARM_B13.INP") #! Link("PLC:CP08:CR01:ALARM_B13.INP","PLC:CP08:CR01:Alarm.BD") #! Record("PLC:CP08:CR01:ALARM_B14",729,1197,0,1,"PLC:CP08:CR01:ALARM_B14") #! Field("PLC:CP08:CR01:ALARM_B14.INP",16777215,0,"PLC:CP08:CR01:ALARM_B14.INP") #! Link("PLC:CP08:CR01:ALARM_B14.INP","PLC:CP08:CR01:Alarm.BE") #! Record("PLC:CP08:CR01:ALARM_B15",906,1197,0,1,"PLC:CP08:CR01:ALARM_B15") #! Field("PLC:CP08:CR01:ALARM_B15.INP",16777215,0,"PLC:CP08:CR01:ALARM_B15.INP") #! Link("PLC:CP08:CR01:ALARM_B15.INP","PLC:CP08:CR01:Alarm.BF") #! Record("PLC:CP08:CR01:BYPASS2_B0",380,2817,0,1,"PLC:CP08:CR01:BYPASS2_B0") #! Record("PLC:CP08:CR01:BYPASS2_B1",560,2817,0,1,"PLC:CP08:CR01:BYPASS2_B1") #! Record("PLC:CP08:CR01:BYPASS2_B2",740,2817,0,1,"PLC:CP08:CR01:BYPASS2_B2") #! Record("PLC:CP08:CR01:CH_FAULTS4A",860,2259,0,1,"PLC:CP08:CR01:CH_FAULTS4A") #! Record("PLC:CP08:CR01:CH_FAULTS6A",1220,2259,0,1,"PLC:CP08:CR01:CH_FAULTS6A") #! Record("PLC:CP08:CR01:CH_FAULTS2",480,2099,0,1,"PLC:CP08:CR01:CH_FAULTS2") #! Record("PLC:CP08:CR01:CH_FAULTS3A",680,2259,0,1,"PLC:CP08:CR01:CH_FAULTS3A") #! Record("PLC:CP08:CR01:CH_FAULTS0",101,2099,0,1,"PLC:CP08:CR01:CH_FAULTS0") #! Record("PLC:CP08:CR01:CH_FAULTS1",301,2099,0,1,"PLC:CP08:CR01:CH_FAULTS1") #! Record("PLC:CP08:CR01:AlarmL2",1402,1259,0,1,"PLC:CP08:CR01:AlarmL2") #! Record("PLC:CP08:CR01:Alarm2",100,2499,0,1,"PLC:CP08:CR01:Alarm2") #! Field("PLC:CP08:CR01:Alarm2.B0",16777215,1,"PLC:CP08:CR01:Alarm2.B0") #! Field("PLC:CP08:CR01:Alarm2.B1",16777215,1,"PLC:CP08:CR01:Alarm2.B1") #! Field("PLC:CP08:CR01:Alarm2.B2",16777215,1,"PLC:CP08:CR01:Alarm2.B2") #! Field("PLC:CP08:CR01:Alarm2.B3",16777215,1,"PLC:CP08:CR01:Alarm2.B3") #! Field("PLC:CP08:CR01:Alarm2.B4",16777215,1,"PLC:CP08:CR01:Alarm2.B4") #! Field("PLC:CP08:CR01:Alarm2.B5",16777215,1,"PLC:CP08:CR01:Alarm2.B5") #! Field("PLC:CP08:CR01:Alarm2.B7",16777215,1,"PLC:CP08:CR01:Alarm2.B7") #! Field("PLC:CP08:CR01:Alarm2.B8",16777215,1,"PLC:CP08:CR01:Alarm2.B8") #! Field("PLC:CP08:CR01:Alarm2.B6",16777215,1,"PLC:CP08:CR01:Alarm2.B6") #! Record("PLC:CP08:CR01:ALARM2_B0",380,2497,0,1,"PLC:CP08:CR01:ALARM2_B0") #! Field("PLC:CP08:CR01:ALARM2_B0.INP",16777215,0,"PLC:CP08:CR01:ALARM2_B0.INP") #! Link("PLC:CP08:CR01:ALARM2_B0.INP","PLC:CP08:CR01:Alarm2.B0") #! Record("PLC:CP08:CR01:ALARM2_B1",560,2497,0,1,"PLC:CP08:CR01:ALARM2_B1") #! Field("PLC:CP08:CR01:ALARM2_B1.INP",16777215,0,"PLC:CP08:CR01:ALARM2_B1.INP") #! Link("PLC:CP08:CR01:ALARM2_B1.INP","PLC:CP08:CR01:Alarm2.B1") #! Record("PLC:CP08:CR01:ALARM2_B2",740,2497,0,1,"PLC:CP08:CR01:ALARM2_B2") #! Field("PLC:CP08:CR01:ALARM2_B2.INP",16777215,0,"PLC:CP08:CR01:ALARM2_B2.INP") #! Link("PLC:CP08:CR01:ALARM2_B2.INP","PLC:CP08:CR01:Alarm2.B2") #! Record("PLC:CP08:CR01:ALARM2_B3",920,2497,0,1,"PLC:CP08:CR01:ALARM2_B3") #! Field("PLC:CP08:CR01:ALARM2_B3.INP",16777215,0,"PLC:CP08:CR01:ALARM2_B3.INP") #! Link("PLC:CP08:CR01:ALARM2_B3.INP","PLC:CP08:CR01:Alarm2.B3") #! Record("PLC:CP08:CR01:ALARM2_B4",1100,2497,0,1,"PLC:CP08:CR01:ALARM2_B4") #! Field("PLC:CP08:CR01:ALARM2_B4.INP",16777215,0,"PLC:CP08:CR01:ALARM2_B4.INP") #! Link("PLC:CP08:CR01:ALARM2_B4.INP","PLC:CP08:CR01:Alarm2.B4") #! Record("PLC:CP08:CR01:ALARM2_B5",1280,2497,0,1,"PLC:CP08:CR01:ALARM2_B5") #! Field("PLC:CP08:CR01:ALARM2_B5.INP",16777215,0,"PLC:CP08:CR01:ALARM2_B5.INP") #! Link("PLC:CP08:CR01:ALARM2_B5.INP","PLC:CP08:CR01:Alarm2.B5") #! Record("PLC:CP08:CR01:ALARM2_B6",1460,2497,0,1,"PLC:CP08:CR01:ALARM2_B6") #! Field("PLC:CP08:CR01:ALARM2_B6.INP",16777215,0,"PLC:CP08:CR01:ALARM2_B6.INP") #! Link("PLC:CP08:CR01:ALARM2_B6.INP","PLC:CP08:CR01:Alarm2.B6") #! Record("PLC:CP08:CR01:ALARM2_B7",1640,2497,0,1,"PLC:CP08:CR01:ALARM2_B7") #! Field("PLC:CP08:CR01:ALARM2_B7.INP",16777215,0,"PLC:CP08:CR01:ALARM2_B7.INP") #! Link("PLC:CP08:CR01:ALARM2_B7.INP","PLC:CP08:CR01:Alarm2.B7") #! Record("PLC:CP08:CR01:ALARM2_B8",1820,2497,0,1,"PLC:CP08:CR01:ALARM2_B8") #! Field("PLC:CP08:CR01:ALARM2_B8.INP",16777215,0,"PLC:CP08:CR01:ALARM2_B8.INP") #! Link("PLC:CP08:CR01:ALARM2_B8.INP","PLC:CP08:CR01:Alarm2.B8") #! Record("PLC:CP08:CR01:BYPASS2_B3",921,2817,0,1,"PLC:CP08:CR01:BYPASS2_B3") #! Record("PLC:CP08:CR01:BYPASS2_B4",1100,2817,0,1,"PLC:CP08:CR01:BYPASS2_B4") #! Record("PLC:CP08:CR01:BYPASS2_B5",1280,2817,0,1,"PLC:CP08:CR01:BYPASS2_B5") #! Record("PLC:CP08:CR01:BYPASS2_B6",1460,2817,0,1,"PLC:CP08:CR01:BYPASS2_B6") #! Record("PLC:CP08:CR01:BYPASS2_B7",1640,2817,0,1,"PLC:CP08:CR01:BYPASS2_B7") #! Record("PLC:CP08:CR01:BYPASS2_B8",1820,2817,0,1,"PLC:CP08:CR01:BYPASS2_B8") #! TextBox(TB4,500,1680,940,1720,0,"Dialog",18,1,16777215,"StatBit MBBI word - PLC Status Bits ",null) #! TextBox(TB3,440,20,960,60,0,"Dialog",18,1,16777215,"PLC RACK 1 SLOT 1 - 7 Alarm Bypass[0] Records\n - First 7 slots\n",null) #! TextBox(TB2,600,620,1120,660,0,"Dialog",18,1,16777215,"Alarm MBBI word - PLC CARD Alarm Status (by SLOT)\n",null) #! TextBox(TB0,80,600,480,680,0,"Dialog",12,1,16777215,"Each bit represents the alarm status for a PLC crate SLOT. \nB0 not used\nB1 for Ethernet card alarm, usually\nOther Alarms B2-B15 are assigned per PLC SLot 2 - 15",null) #! TextBox(TB9,1500,40,2020,260,0,"Dialog",14,1,16777215,"PLC STATUS \nThis vdb includes the common PLC Status records needed by\nall PLCs for the cryoplant. The Warm Compressor PLC has the \nleast number of required records, so this vdb reflects\nthe Warm Compressor PLC status. \n\nIn the case where the status is represented by a \nsingle bit (Bypasses and Alarms) the records for the \nentire word (bits 1 to 15) are in this database. The \nrecords will be instantiated for all PLCs, but the \nCompressor PLC will not display or archive the extras.\n",null) #! TextBox(TB8,1540,1000,1760,1020,0,"Dialog",12,1,16777215,"FAULT_RESET - reset PLC faults\n",null) #! TextBox(TB7,1540,760,1760,780,0,"Dialog",12,1,16777215,"LR_STATUS - Local/Remote Status\n",null) #! TextBox(TB6,280,2040,820,2100,0,"Dialog",12,1,16777215,"CH_FAULTS1 MBBI word - PLC Card Channel Faults\n - All PLCs use first rack up to slot 9\n - individual PLCs have records for slots above 9, and 2nd rack\n",null) #! TextBox(TB5,1120,1240,1560,1280,0,"Dialog",18,1,16777215,"AlarmL MBBI word - Alarm Latch Status\n",null)