record(stringin, "CPV:CP$(CP)2:3616:PIDTAG") {
  field(DESC, "P&ID tag alve")
  field(PINI, "YES")
  field(VAL, "C$(CP)PV23616")
}

record(bo, "CPV:CP$(CP)2:3616:CMD") {
  field(DESC, "Valve Command set open/close")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) SV_Override B 2")
  field(ZNAM, "Close")
  field(ONAM, "Open")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

record(bo, "CPV:CP$(CP)2:3616:OVR") {
  field(DESC, "set Auto/Manual")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) SV_Auto_Manual B 2")
  field(ZNAM, "Auto")
  field(ONAM, "Manual")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

record(bi, "CPV:CP$(CP)2:3616:STATUS") {
  field(DESC, "UCB DP Bypass Valve")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV23616")
  field(OSV, "NO_ALARM")
  field(ZNAM, "closed")
  field(ONAM, "open")
  field(ZSV, "MAJOR")
}

record(bi, "CPV:CP$(CP)2:3616:INTERLOCKED") {
  field(DESC, "Valve Interlocked Bit")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV23616.Interlocked")
  field(ZNAM, "OK")
  field(ONAM, "Interlocked")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CPV:CP$(CP)2:3616:PIDTAG",2320,2242,0,1,"CPV:CP$(CP)2:3616:PIDTAG")
#! Record("CPV:CP$(CP)2:3616:CMD",2500,2231,0,1,"CPV:CP$(CP)2:3616:CMD")
#! Record("CPV:CP$(CP)2:3616:OVR",2680,2231,0,1,"CPV:CP$(CP)2:3616:OVR")
#! Record("CPV:CP$(CP)2:3616:STATUS",2320,2359,0,1,"CPV:CP$(CP)2:3616:STATUS")
#! Record("CPV:CP$(CP)2:3616:INTERLOCKED",2500,2452,0,1,"CPV:CP$(CP)2:3616:INTERLOCKED")
#! TextBox(TB0,2580,2140,2780,2220,0,"Dialog",12,1,16777215,"Vacuum Solenoid Valve records\nStatus\nAuto_Manual\nOverride command",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(stringin, "CPV:CP$(CP)2:3636:PIDTAG") {
  field(DESC, "P&ID tag alve")
  field(PINI, "YES")
  field(VAL, "C$(CP)PV23636")
}

record(bo, "CPV:CP$(CP)2:3636:CMD") {
  field(DESC, "Valve Command set open/close")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) SV_Override B 12")
  field(ZNAM, "Close")
  field(ONAM, "Open")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

record(bo, "CPV:CP$(CP)2:3636:OVR") {
  field(DESC, "set Auto/Manual")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) SV_Auto_Manual B 12")
  field(ZNAM, "Auto")
  field(ONAM, "Manual")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

record(bi, "CPV:CP$(CP)2:3636:STATUS") {
  field(DESC, "LCB DP Bypass Valve")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV23636")
  field(OSV, "NO_ALARM")
  field(ZNAM, "closed")
  field(ONAM, "open")
  field(ZSV, "MAJOR")
}

record(bi, "CPV:CP$(CP)2:3636:INTERLOCKED") {
  field(DESC, "Valve Interlocked Bit")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV23636.Interlocked")
  field(ZNAM, "OK")
  field(ONAM, "Interlocked")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CPV:CP$(CP)2:3636:PIDTAG",2320,2242,0,1,"CPV:CP$(CP)2:3636:PIDTAG")
#! Record("CPV:CP$(CP)2:3636:CMD",2500,2231,0,1,"CPV:CP$(CP)2:3636:CMD")
#! Record("CPV:CP$(CP)2:3636:OVR",2680,2231,0,1,"CPV:CP$(CP)2:3636:OVR")
#! Record("CPV:CP$(CP)2:3636:STATUS",2320,2359,0,1,"CPV:CP$(CP)2:3636:STATUS")
#! Record("CPV:CP$(CP)2:3636:INTERLOCKED",2500,2452,0,1,"CPV:CP$(CP)2:3636:INTERLOCKED")
#! TextBox(TB0,2580,2140,2780,2220,0,"Dialog",12,1,16777215,"Vacuum Solenoid Valve records\nStatus\nAuto_Manual\nOverride command",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(stringin, "CPV:CP$(CP)2:3611:PIDTAG") {
  field(DESC, "P&ID tag alve")
  field(PINI, "YES")
  field(VAL, "C$(CP)PV23611")
}

record(bo, "CPV:CP$(CP)2:3611:CMD") {
  field(DESC, "Valve Command set open/close")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) SV_Override B 0")
  field(ZNAM, "Close")
  field(ONAM, "Open")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

record(bo, "CPV:CP$(CP)2:3611:OVR") {
  field(DESC, "set Auto/Manual")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) SV_Auto_Manual B 0")
  field(ZNAM, "Auto")
  field(ONAM, "Manual")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

record(bi, "CPV:CP$(CP)2:3611:STATUS") {
  field(DESC, "UCB Gate Valve")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV23611")
  field(OSV, "NO_ALARM")
  field(ZNAM, "closed")
  field(ONAM, "open")
  field(ZSV, "MAJOR")
}

record(bi, "CPV:CP$(CP)2:3611:INTERLOCKED") {
  field(DESC, "Valve Interlocked Bit")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV23611.Interlocked")
  field(ZNAM, "OK")
  field(ONAM, "Interlocked")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CPV:CP$(CP)2:3611:PIDTAG",2320,2242,0,1,"CPV:CP$(CP)2:3611:PIDTAG")
#! Record("CPV:CP$(CP)2:3611:CMD",2500,2231,0,1,"CPV:CP$(CP)2:3611:CMD")
#! Record("CPV:CP$(CP)2:3611:OVR",2680,2231,0,1,"CPV:CP$(CP)2:3611:OVR")
#! Record("CPV:CP$(CP)2:3611:STATUS",2320,2359,0,1,"CPV:CP$(CP)2:3611:STATUS")
#! Record("CPV:CP$(CP)2:3611:INTERLOCKED",2500,2452,0,1,"CPV:CP$(CP)2:3611:INTERLOCKED")
#! TextBox(TB0,2580,2140,2780,2220,0,"Dialog",12,1,16777215,"Vacuum Solenoid Valve records\nStatus\nAuto_Manual\nOverride command",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(stringin, "CPV:CP$(CP)2:3631:PIDTAG") {
  field(DESC, "P&ID tag alve")
  field(PINI, "YES")
  field(VAL, "C$(CP)PV23631")
}

record(bo, "CPV:CP$(CP)2:3631:CMD") {
  field(DESC, "Valve Command set open/close")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) SV_Override B 10")
  field(ZNAM, "Close")
  field(ONAM, "Open")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

record(bo, "CPV:CP$(CP)2:3631:OVR") {
  field(DESC, "set Auto/Manual")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) SV_Auto_Manual B 10")
  field(ZNAM, "Auto")
  field(ONAM, "Manual")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

record(bi, "CPV:CP$(CP)2:3631:STATUS") {
  field(DESC, "LCB Gate Valve")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV23631")
  field(OSV, "NO_ALARM")
  field(ZNAM, "closed")
  field(ONAM, "open")
  field(ZSV, "MAJOR")
}

record(bi, "CPV:CP$(CP)2:3631:INTERLOCKED") {
  field(DESC, "Valve Interlocked Bit")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV23631.Interlocked")
  field(ZNAM, "OK")
  field(ONAM, "Interlocked")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CPV:CP$(CP)2:3631:PIDTAG",2320,2242,0,1,"CPV:CP$(CP)2:3631:PIDTAG")
#! Record("CPV:CP$(CP)2:3631:CMD",2500,2231,0,1,"CPV:CP$(CP)2:3631:CMD")
#! Record("CPV:CP$(CP)2:3631:OVR",2680,2231,0,1,"CPV:CP$(CP)2:3631:OVR")
#! Record("CPV:CP$(CP)2:3631:STATUS",2320,2359,0,1,"CPV:CP$(CP)2:3631:STATUS")
#! Record("CPV:CP$(CP)2:3631:INTERLOCKED",2500,2452,0,1,"CPV:CP$(CP)2:3631:INTERLOCKED")
#! TextBox(TB0,2580,2140,2780,2220,0,"Dialog",12,1,16777215,"Vacuum Solenoid Valve records\nStatus\nAuto_Manual\nOverride command",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(stringin, "CPV:CP$(CP)2:3614:PIDTAG") {
  field(DESC, "P&ID tag alve")
  field(PINI, "YES")
  field(VAL, "C$(CP)PV23614")
}

record(bo, "CPV:CP$(CP)2:3614:CMD") {
  field(DESC, "Valve Command set open/close")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) SV_Override B 1")
  field(ZNAM, "Close")
  field(ONAM, "Open")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

record(bo, "CPV:CP$(CP)2:3614:OVR") {
  field(DESC, "set Auto/Manual")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) SV_Auto_Manual B 1")
  field(ZNAM, "Auto")
  field(ONAM, "Manual")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

record(bi, "CPV:CP$(CP)2:3614:STATUS") {
  field(DESC, "UCB DP Isolation Vlv")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV23614")
  field(OSV, "NO_ALARM")
  field(ZNAM, "closed")
  field(ONAM, "open")
  field(ZSV, "MAJOR")
}

record(bi, "CPV:CP$(CP)2:3614:INTERLOCKED") {
  field(DESC, "Valve Interlocked Bit")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV23614.Interlocked")
  field(ZNAM, "OK")
  field(ONAM, "Interlocked")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CPV:CP$(CP)2:3614:PIDTAG",2320,2242,0,1,"CPV:CP$(CP)2:3614:PIDTAG")
#! Record("CPV:CP$(CP)2:3614:CMD",2500,2231,0,1,"CPV:CP$(CP)2:3614:CMD")
#! Record("CPV:CP$(CP)2:3614:OVR",2680,2231,0,1,"CPV:CP$(CP)2:3614:OVR")
#! Record("CPV:CP$(CP)2:3614:STATUS",2320,2359,0,1,"CPV:CP$(CP)2:3614:STATUS")
#! Record("CPV:CP$(CP)2:3614:INTERLOCKED",2500,2452,0,1,"CPV:CP$(CP)2:3614:INTERLOCKED")
#! TextBox(TB0,2580,2140,2780,2220,0,"Dialog",12,1,16777215,"Vacuum Solenoid Valve records\nStatus\nAuto_Manual\nOverride command",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(stringin, "CPV:CP$(CP)2:3634:PIDTAG") {
  field(DESC, "P&ID tag alve")
  field(PINI, "YES")
  field(VAL, "C$(CP)PV23634")
}

record(bo, "CPV:CP$(CP)2:3634:CMD") {
  field(DESC, "Valve Command set open/close")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) SV_Override B 11")
  field(ZNAM, "Close")
  field(ONAM, "Open")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

record(bo, "CPV:CP$(CP)2:3634:OVR") {
  field(DESC, "set Auto/Manual")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) SV_Auto_Manual B 11")
  field(ZNAM, "Auto")
  field(ONAM, "Manual")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

record(bi, "CPV:CP$(CP)2:3634:STATUS") {
  field(DESC, "LCB DP Isolation Vlv")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV23634")
  field(OSV, "NO_ALARM")
  field(ZNAM, "closed")
  field(ONAM, "open")
  field(ZSV, "MAJOR")
}

record(bi, "CPV:CP$(CP)2:3634:INTERLOCKED") {
  field(DESC, "Valve Interlocked Bit")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV23634.Interlocked")
  field(ZNAM, "OK")
  field(ONAM, "Interlocked")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CPV:CP$(CP)2:3634:PIDTAG",2320,2242,0,1,"CPV:CP$(CP)2:3634:PIDTAG")
#! Record("CPV:CP$(CP)2:3634:CMD",2500,2231,0,1,"CPV:CP$(CP)2:3634:CMD")
#! Record("CPV:CP$(CP)2:3634:OVR",2680,2231,0,1,"CPV:CP$(CP)2:3634:OVR")
#! Record("CPV:CP$(CP)2:3634:STATUS",2320,2359,0,1,"CPV:CP$(CP)2:3634:STATUS")
#! Record("CPV:CP$(CP)2:3634:INTERLOCKED",2500,2452,0,1,"CPV:CP$(CP)2:3634:INTERLOCKED")
#! TextBox(TB0,2580,2140,2780,2220,0,"Dialog",12,1,16777215,"Vacuum Solenoid Valve records\nStatus\nAuto_Manual\nOverride command",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(stringin, "CPV:CP$(CP)2:2110:PIDTAG") {
  field(DESC, "Cooldown valve 300K")
  field(PINI, "YES")
  field(VAL, "C$(CP)PV22110")
}

record(ao, "CPV:CP$(CP)2:2110:DMIN") {
  field(DESC, "ramp DOWN stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22110.DMIN")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2110:DMAX") {
  field(DESC, "ramp UP stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22110.DMAX")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2110:TOPEN") {
  field(DESC, "valve open temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22110.TOpen")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2110:TCLOSE") {
  field(DESC, "valve close temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22110.TClose")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2110:MVAL") {
  field(DESC, "Valve position requested in manual mode")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22110.MVAL")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(bo, "CPV:CP$(CP)2:2110:MODE") {
  field(DESC, "set Auto or Manual mode")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) PV22110.Mode")
  field(ZNAM, "Auto")
  field(ONAM, "Manual")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CPV:CP$(CP)2:2110:CMD_OUT") {
  field(DESC, "Cooldown valve 300K")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22110O")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2110:TCAL") {
  field(DESC, "Temp diff calc before injection")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22110.TCal")
  field(PREC, "1")
  field(EGU, "K")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2110:ORBV") {
  field(DESC, "Cooldown valve 300K")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22110.ORBV")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(bi, "CPV:CP$(CP)2:2110:INTERLOCKED") {
  field(DESC, "Valve Interlocked Bit")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22110.Interlocked")
  field(ZNAM, "OK")
  field(ONAM, "Interlocked")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(1438,1981,1.0)
#! Record("CPV:CP$(CP)2:2110:PIDTAG",1560,2162,0,1,"CPV:CP$(CP)2:2110:PIDTAG")
#! Record("CPV:CP$(CP)2:2110:DMIN",1760,2312,0,1,"CPV:CP$(CP)2:2110:DMIN")
#! Record("CPV:CP$(CP)2:2110:DMAX",2000,2312,0,1,"CPV:CP$(CP)2:2110:DMAX")
#! Record("CPV:CP$(CP)2:2110:TOPEN",1760,2492,0,1,"CPV:CP$(CP)2:2110:TOPEN")
#! Record("CPV:CP$(CP)2:2110:TCLOSE",2000,2512,0,1,"CPV:CP$(CP)2:2110:TCLOSE")
#! Record("CPV:CP$(CP)2:2110:MVAL",2000,2132,0,1,"CPV:CP$(CP)2:2110:MVAL")
#! Record("CPV:CP$(CP)2:2110:MODE",1567,2291,0,1,"CPV:CP$(CP)2:2110:MODE")
#! Record("CPV:CP$(CP)2:2110:CMD_OUT",2180,2152,0,1,"CPV:CP$(CP)2:2110:CMD_OUT")
#! Record("CPV:CP$(CP)2:2110:TCAL",2182,2332,0,1,"CPV:CP$(CP)2:2110:TCAL")
#! Record("CPV:CP$(CP)2:2110:ORBV",1760,2132,0,1,"CPV:CP$(CP)2:2110:ORBV")
#! Record("CPV:CP$(CP)2:2110:INTERLOCKED",2180,2532,0,1,"CPV:CP$(CP)2:2110:INTERLOCKED")
#! TextBox(TB0,1780,2120,2160,2080,0,"Dialog",12,1,16777215,"4kcb ramped  valve interface\n",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(stringin, "CPV:CP$(CP)2:2115:PIDTAG") {
  field(DESC, "Cooldown valve 80K")
  field(PINI, "YES")
  field(VAL, "C$(CP)PV22115")
}

record(ao, "CPV:CP$(CP)2:2115:DMIN") {
  field(DESC, "ramp DOWN stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22115.DMIN")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2115:DMAX") {
  field(DESC, "ramp UP stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22115.DMAX")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2115:TOPEN") {
  field(DESC, "valve open temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22115.TOpen")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2115:TCLOSE") {
  field(DESC, "valve close temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22115.TClose")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2115:MVAL") {
  field(DESC, "Valve position requested in manual mode")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22115.MVAL")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(bo, "CPV:CP$(CP)2:2115:MODE") {
  field(DESC, "set Auto or Manual mode")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) PV22115.Mode")
  field(ZNAM, "Auto")
  field(ONAM, "Manual")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CPV:CP$(CP)2:2115:CMD_OUT") {
  field(DESC, "Cooldown valve 80K")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22115O")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2115:TCAL") {
  field(DESC, "Temp diff calc before injection")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22115.TCal")
  field(PREC, "1")
  field(EGU, "K")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2115:ORBV") {
  field(DESC, "Cooldown valve 80K")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22115.ORBV")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(bi, "CPV:CP$(CP)2:2115:INTERLOCKED") {
  field(DESC, "Valve Interlocked Bit")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22115.Interlocked")
  field(ZNAM, "OK")
  field(ONAM, "Interlocked")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(1438,1981,1.0)
#! Record("CPV:CP$(CP)2:2115:PIDTAG",1560,2162,0,1,"CPV:CP$(CP)2:2115:PIDTAG")
#! Record("CPV:CP$(CP)2:2115:DMIN",1760,2312,0,1,"CPV:CP$(CP)2:2115:DMIN")
#! Record("CPV:CP$(CP)2:2115:DMAX",2000,2312,0,1,"CPV:CP$(CP)2:2115:DMAX")
#! Record("CPV:CP$(CP)2:2115:TOPEN",1760,2492,0,1,"CPV:CP$(CP)2:2115:TOPEN")
#! Record("CPV:CP$(CP)2:2115:TCLOSE",2000,2512,0,1,"CPV:CP$(CP)2:2115:TCLOSE")
#! Record("CPV:CP$(CP)2:2115:MVAL",2000,2132,0,1,"CPV:CP$(CP)2:2115:MVAL")
#! Record("CPV:CP$(CP)2:2115:MODE",1567,2291,0,1,"CPV:CP$(CP)2:2115:MODE")
#! Record("CPV:CP$(CP)2:2115:CMD_OUT",2180,2152,0,1,"CPV:CP$(CP)2:2115:CMD_OUT")
#! Record("CPV:CP$(CP)2:2115:TCAL",2182,2332,0,1,"CPV:CP$(CP)2:2115:TCAL")
#! Record("CPV:CP$(CP)2:2115:ORBV",1760,2132,0,1,"CPV:CP$(CP)2:2115:ORBV")
#! Record("CPV:CP$(CP)2:2115:INTERLOCKED",2180,2532,0,1,"CPV:CP$(CP)2:2115:INTERLOCKED")
#! TextBox(TB0,1780,2120,2160,2080,0,"Dialog",12,1,16777215,"4kcb ramped  valve interface\n",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(stringin, "CPV:CP$(CP)2:2135:PIDTAG") {
  field(DESC, "Cooldown valve 60K")
  field(PINI, "YES")
  field(VAL, "C$(CP)PV22135")
}

record(ao, "CPV:CP$(CP)2:2135:DMIN") {
  field(DESC, "ramp DOWN stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22135.DMIN")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2135:DMAX") {
  field(DESC, "ramp UP stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22135.DMAX")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2135:TOPEN") {
  field(DESC, "valve open temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22135.TOpen")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2135:TCLOSE") {
  field(DESC, "valve close temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22135.TClose")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2135:MVAL") {
  field(DESC, "Valve position requested in manual mode")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22135.MVAL")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(bo, "CPV:CP$(CP)2:2135:MODE") {
  field(DESC, "set Auto or Manual mode")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) PV22135.Mode")
  field(ZNAM, "Auto")
  field(ONAM, "Manual")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CPV:CP$(CP)2:2135:CMD_OUT") {
  field(DESC, "Cooldown valve 60K")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22135O")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2135:TCAL") {
  field(DESC, "Temp diff calc before injection")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22135.TCal")
  field(PREC, "1")
  field(EGU, "K")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2135:ORBV") {
  field(DESC, "Cooldown valve 60K")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22135.ORBV")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(bi, "CPV:CP$(CP)2:2135:INTERLOCKED") {
  field(DESC, "Valve Interlocked Bit")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22135.Interlocked")
  field(ZNAM, "OK")
  field(ONAM, "Interlocked")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(1438,1981,1.0)
#! Record("CPV:CP$(CP)2:2135:PIDTAG",1560,2162,0,1,"CPV:CP$(CP)2:2135:PIDTAG")
#! Record("CPV:CP$(CP)2:2135:DMIN",1760,2312,0,1,"CPV:CP$(CP)2:2135:DMIN")
#! Record("CPV:CP$(CP)2:2135:DMAX",2000,2312,0,1,"CPV:CP$(CP)2:2135:DMAX")
#! Record("CPV:CP$(CP)2:2135:TOPEN",1760,2492,0,1,"CPV:CP$(CP)2:2135:TOPEN")
#! Record("CPV:CP$(CP)2:2135:TCLOSE",2000,2512,0,1,"CPV:CP$(CP)2:2135:TCLOSE")
#! Record("CPV:CP$(CP)2:2135:MVAL",2000,2132,0,1,"CPV:CP$(CP)2:2135:MVAL")
#! Record("CPV:CP$(CP)2:2135:MODE",1567,2291,0,1,"CPV:CP$(CP)2:2135:MODE")
#! Record("CPV:CP$(CP)2:2135:CMD_OUT",2180,2152,0,1,"CPV:CP$(CP)2:2135:CMD_OUT")
#! Record("CPV:CP$(CP)2:2135:TCAL",2182,2332,0,1,"CPV:CP$(CP)2:2135:TCAL")
#! Record("CPV:CP$(CP)2:2135:ORBV",1760,2132,0,1,"CPV:CP$(CP)2:2135:ORBV")
#! Record("CPV:CP$(CP)2:2135:INTERLOCKED",2180,2532,0,1,"CPV:CP$(CP)2:2135:INTERLOCKED")
#! TextBox(TB0,1780,2120,2160,2080,0,"Dialog",12,1,16777215,"4kcb ramped  valve interface\n",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(stringin, "CPV:CP$(CP)2:2140:PIDTAG") {
  field(DESC, "Cooldown valve 35K")
  field(PINI, "YES")
  field(VAL, "C$(CP)PV22140")
}

record(ao, "CPV:CP$(CP)2:2140:DMIN") {
  field(DESC, "ramp DOWN stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22140.DMIN")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2140:DMAX") {
  field(DESC, "ramp UP stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22140.DMAX")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2140:TOPEN") {
  field(DESC, "valve open temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22140.TOpen")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2140:TCLOSE") {
  field(DESC, "valve close temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22140.TClose")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2140:MVAL") {
  field(DESC, "Valve position requested in manual mode")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22140.MVAL")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(bo, "CPV:CP$(CP)2:2140:MODE") {
  field(DESC, "set Auto or Manual mode")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) PV22140.Mode")
  field(ZNAM, "Auto")
  field(ONAM, "Manual")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CPV:CP$(CP)2:2140:CMD_OUT") {
  field(DESC, "Cooldown valve 35K")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22140O")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2140:TCAL") {
  field(DESC, "Temp diff calc before injection")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22140.TCal")
  field(PREC, "1")
  field(EGU, "K")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2140:ORBV") {
  field(DESC, "Cooldown valve 35K")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22140.ORBV")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(bi, "CPV:CP$(CP)2:2140:INTERLOCKED") {
  field(DESC, "Valve Interlocked Bit")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22140.Interlocked")
  field(ZNAM, "OK")
  field(ONAM, "Interlocked")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(1438,1981,1.0)
#! Record("CPV:CP$(CP)2:2140:PIDTAG",1560,2162,0,1,"CPV:CP$(CP)2:2140:PIDTAG")
#! Record("CPV:CP$(CP)2:2140:DMIN",1760,2312,0,1,"CPV:CP$(CP)2:2140:DMIN")
#! Record("CPV:CP$(CP)2:2140:DMAX",2000,2312,0,1,"CPV:CP$(CP)2:2140:DMAX")
#! Record("CPV:CP$(CP)2:2140:TOPEN",1760,2492,0,1,"CPV:CP$(CP)2:2140:TOPEN")
#! Record("CPV:CP$(CP)2:2140:TCLOSE",2000,2512,0,1,"CPV:CP$(CP)2:2140:TCLOSE")
#! Record("CPV:CP$(CP)2:2140:MVAL",2000,2132,0,1,"CPV:CP$(CP)2:2140:MVAL")
#! Record("CPV:CP$(CP)2:2140:MODE",1567,2291,0,1,"CPV:CP$(CP)2:2140:MODE")
#! Record("CPV:CP$(CP)2:2140:CMD_OUT",2180,2152,0,1,"CPV:CP$(CP)2:2140:CMD_OUT")
#! Record("CPV:CP$(CP)2:2140:TCAL",2182,2332,0,1,"CPV:CP$(CP)2:2140:TCAL")
#! Record("CPV:CP$(CP)2:2140:ORBV",1760,2132,0,1,"CPV:CP$(CP)2:2140:ORBV")
#! Record("CPV:CP$(CP)2:2140:INTERLOCKED",2180,2532,0,1,"CPV:CP$(CP)2:2140:INTERLOCKED")
#! TextBox(TB0,1780,2120,2160,2080,0,"Dialog",12,1,16777215,"4kcb ramped  valve interface\n",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(stringin, "CPV:CP$(CP)2:2150:PIDTAG") {
  field(DESC, "Cooldown valve 30K")
  field(PINI, "YES")
  field(VAL, "C$(CP)PV22150")
}

record(ao, "CPV:CP$(CP)2:2150:DMIN") {
  field(DESC, "ramp DOWN stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22150.DMIN")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2150:DMAX") {
  field(DESC, "ramp UP stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22150.DMAX")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2150:TOPEN") {
  field(DESC, "valve open temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22150.TOpen")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2150:TCLOSE") {
  field(DESC, "valve close temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22150.TClose")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2150:MVAL") {
  field(DESC, "Valve position requested in manual mode")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22150.MVAL")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(bo, "CPV:CP$(CP)2:2150:MODE") {
  field(DESC, "set Auto or Manual mode")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) PV22150.Mode")
  field(ZNAM, "Auto")
  field(ONAM, "Manual")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CPV:CP$(CP)2:2150:CMD_OUT") {
  field(DESC, "Cooldown valve 30K")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22150O")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2150:TCAL") {
  field(DESC, "Temp diff calc before injection")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22150.TCal")
  field(PREC, "1")
  field(EGU, "K")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2150:ORBV") {
  field(DESC, "Cooldown valve 30K")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22150.ORBV")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(bi, "CPV:CP$(CP)2:2150:INTERLOCKED") {
  field(DESC, "Valve Interlocked Bit")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22150.Interlocked")
  field(ZNAM, "OK")
  field(ONAM, "Interlocked")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(1438,1981,1.0)
#! Record("CPV:CP$(CP)2:2150:PIDTAG",1560,2162,0,1,"CPV:CP$(CP)2:2150:PIDTAG")
#! Record("CPV:CP$(CP)2:2150:DMIN",1760,2312,0,1,"CPV:CP$(CP)2:2150:DMIN")
#! Record("CPV:CP$(CP)2:2150:DMAX",2000,2312,0,1,"CPV:CP$(CP)2:2150:DMAX")
#! Record("CPV:CP$(CP)2:2150:TOPEN",1760,2492,0,1,"CPV:CP$(CP)2:2150:TOPEN")
#! Record("CPV:CP$(CP)2:2150:TCLOSE",2000,2512,0,1,"CPV:CP$(CP)2:2150:TCLOSE")
#! Record("CPV:CP$(CP)2:2150:MVAL",2000,2132,0,1,"CPV:CP$(CP)2:2150:MVAL")
#! Record("CPV:CP$(CP)2:2150:MODE",1567,2291,0,1,"CPV:CP$(CP)2:2150:MODE")
#! Record("CPV:CP$(CP)2:2150:CMD_OUT",2180,2152,0,1,"CPV:CP$(CP)2:2150:CMD_OUT")
#! Record("CPV:CP$(CP)2:2150:TCAL",2182,2332,0,1,"CPV:CP$(CP)2:2150:TCAL")
#! Record("CPV:CP$(CP)2:2150:ORBV",1760,2132,0,1,"CPV:CP$(CP)2:2150:ORBV")
#! Record("CPV:CP$(CP)2:2150:INTERLOCKED",2180,2532,0,1,"CPV:CP$(CP)2:2150:INTERLOCKED")
#! TextBox(TB0,1780,2120,2160,2080,0,"Dialog",12,1,16777215,"4kcb ramped  valve interface\n",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(stringin, "CPV:CP$(CP)2:2160:PIDTAG") {
  field(DESC, "Cooldown valve 18K")
  field(PINI, "YES")
  field(VAL, "C$(CP)PV22160")
}

record(ao, "CPV:CP$(CP)2:2160:DMIN") {
  field(DESC, "ramp DOWN stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22160.DMIN")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2160:DMAX") {
  field(DESC, "ramp UP stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22160.DMAX")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2160:TOPEN") {
  field(DESC, "valve open temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22160.TOpen")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2160:TCLOSE") {
  field(DESC, "valve close temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22160.TClose")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2160:MVAL") {
  field(DESC, "Valve position requested in manual mode")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22160.MVAL")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(bo, "CPV:CP$(CP)2:2160:MODE") {
  field(DESC, "set Auto or Manual mode")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) PV22160.Mode")
  field(ZNAM, "Auto")
  field(ONAM, "Manual")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CPV:CP$(CP)2:2160:CMD_OUT") {
  field(DESC, "Cooldown valve 18K")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22160O")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2160:TCAL") {
  field(DESC, "Temp diff calc before injection")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22160.TCal")
  field(PREC, "1")
  field(EGU, "K")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2160:ORBV") {
  field(DESC, "Cooldown valve 18K")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22160.ORBV")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(bi, "CPV:CP$(CP)2:2160:INTERLOCKED") {
  field(DESC, "Valve Interlocked Bit")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22160.Interlocked")
  field(ZNAM, "OK")
  field(ONAM, "Interlocked")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(1438,1981,1.0)
#! Record("CPV:CP$(CP)2:2160:PIDTAG",1560,2162,0,1,"CPV:CP$(CP)2:2160:PIDTAG")
#! Record("CPV:CP$(CP)2:2160:DMIN",1760,2312,0,1,"CPV:CP$(CP)2:2160:DMIN")
#! Record("CPV:CP$(CP)2:2160:DMAX",2000,2312,0,1,"CPV:CP$(CP)2:2160:DMAX")
#! Record("CPV:CP$(CP)2:2160:TOPEN",1760,2492,0,1,"CPV:CP$(CP)2:2160:TOPEN")
#! Record("CPV:CP$(CP)2:2160:TCLOSE",2000,2512,0,1,"CPV:CP$(CP)2:2160:TCLOSE")
#! Record("CPV:CP$(CP)2:2160:MVAL",2000,2132,0,1,"CPV:CP$(CP)2:2160:MVAL")
#! Record("CPV:CP$(CP)2:2160:MODE",1567,2291,0,1,"CPV:CP$(CP)2:2160:MODE")
#! Record("CPV:CP$(CP)2:2160:CMD_OUT",2180,2152,0,1,"CPV:CP$(CP)2:2160:CMD_OUT")
#! Record("CPV:CP$(CP)2:2160:TCAL",2182,2332,0,1,"CPV:CP$(CP)2:2160:TCAL")
#! Record("CPV:CP$(CP)2:2160:ORBV",1760,2132,0,1,"CPV:CP$(CP)2:2160:ORBV")
#! Record("CPV:CP$(CP)2:2160:INTERLOCKED",2180,2532,0,1,"CPV:CP$(CP)2:2160:INTERLOCKED")
#! TextBox(TB0,1780,2120,2160,2080,0,"Dialog",12,1,16777215,"4kcb ramped  valve interface\n",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(stringin, "CPV:CP$(CP)2:2180:PIDTAG") {
  field(DESC, "Cooldown valve 8K")
  field(PINI, "YES")
  field(VAL, "C$(CP)PV22180")
}

record(ao, "CPV:CP$(CP)2:2180:DMIN") {
  field(DESC, "ramp DOWN stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22180.DMIN")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2180:DMAX") {
  field(DESC, "ramp UP stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22180.DMAX")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2180:TOPEN") {
  field(DESC, "valve open temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22180.TOpen")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2180:TCLOSE") {
  field(DESC, "valve close temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22180.TClose")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2180:MVAL") {
  field(DESC, "Valve position requested in manual mode")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22180.MVAL")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(bo, "CPV:CP$(CP)2:2180:MODE") {
  field(DESC, "set Auto or Manual mode")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) PV22180.Mode")
  field(ZNAM, "Auto")
  field(ONAM, "Manual")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CPV:CP$(CP)2:2180:CMD_OUT") {
  field(DESC, "Cooldown valve 8K")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22180O")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2180:TCAL") {
  field(DESC, "Temp diff calc before injection")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22180.TCal")
  field(PREC, "1")
  field(EGU, "K")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2180:ORBV") {
  field(DESC, "Cooldown valve 8K")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22180.ORBV")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(bi, "CPV:CP$(CP)2:2180:INTERLOCKED") {
  field(DESC, "Valve Interlocked Bit")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22180.Interlocked")
  field(ZNAM, "OK")
  field(ONAM, "Interlocked")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(1438,1981,1.0)
#! Record("CPV:CP$(CP)2:2180:PIDTAG",1560,2162,0,1,"CPV:CP$(CP)2:2180:PIDTAG")
#! Record("CPV:CP$(CP)2:2180:DMIN",1760,2312,0,1,"CPV:CP$(CP)2:2180:DMIN")
#! Record("CPV:CP$(CP)2:2180:DMAX",2000,2312,0,1,"CPV:CP$(CP)2:2180:DMAX")
#! Record("CPV:CP$(CP)2:2180:TOPEN",1760,2492,0,1,"CPV:CP$(CP)2:2180:TOPEN")
#! Record("CPV:CP$(CP)2:2180:TCLOSE",2000,2512,0,1,"CPV:CP$(CP)2:2180:TCLOSE")
#! Record("CPV:CP$(CP)2:2180:MVAL",2000,2132,0,1,"CPV:CP$(CP)2:2180:MVAL")
#! Record("CPV:CP$(CP)2:2180:MODE",1567,2291,0,1,"CPV:CP$(CP)2:2180:MODE")
#! Record("CPV:CP$(CP)2:2180:CMD_OUT",2180,2152,0,1,"CPV:CP$(CP)2:2180:CMD_OUT")
#! Record("CPV:CP$(CP)2:2180:TCAL",2182,2332,0,1,"CPV:CP$(CP)2:2180:TCAL")
#! Record("CPV:CP$(CP)2:2180:ORBV",1760,2132,0,1,"CPV:CP$(CP)2:2180:ORBV")
#! Record("CPV:CP$(CP)2:2180:INTERLOCKED",2180,2532,0,1,"CPV:CP$(CP)2:2180:INTERLOCKED")
#! TextBox(TB0,1780,2120,2160,2080,0,"Dialog",12,1,16777215,"4kcb ramped  valve interface\n",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(stringin, "CPV:CP$(CP)2:2190:PIDTAG") {
  field(DESC, "Cooldown valve 5K")
  field(PINI, "YES")
  field(VAL, "C$(CP)PV22190")
}

record(ao, "CPV:CP$(CP)2:2190:DMIN") {
  field(DESC, "ramp DOWN stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22190.DMIN")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2190:DMAX") {
  field(DESC, "ramp UP stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22190.DMAX")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2190:TOPEN") {
  field(DESC, "valve open temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22190.TOpen")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2190:TCLOSE") {
  field(DESC, "valve close temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22190.TClose")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2190:MVAL") {
  field(DESC, "Valve position requested in manual mode")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22190.MVAL")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(bo, "CPV:CP$(CP)2:2190:MODE") {
  field(DESC, "set Auto or Manual mode")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) PV22190.Mode")
  field(ZNAM, "Auto")
  field(ONAM, "Manual")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CPV:CP$(CP)2:2190:CMD_OUT") {
  field(DESC, "Cooldown valve 5K")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22190O")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2190:TCAL") {
  field(DESC, "Temp diff calc before injection")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22190.TCal")
  field(PREC, "1")
  field(EGU, "K")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2190:ORBV") {
  field(DESC, "Cooldown valve 5K")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22190.ORBV")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(bi, "CPV:CP$(CP)2:2190:INTERLOCKED") {
  field(DESC, "Valve Interlocked Bit")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22190.Interlocked")
  field(ZNAM, "OK")
  field(ONAM, "Interlocked")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(1438,1981,1.0)
#! Record("CPV:CP$(CP)2:2190:PIDTAG",1560,2162,0,1,"CPV:CP$(CP)2:2190:PIDTAG")
#! Record("CPV:CP$(CP)2:2190:DMIN",1760,2312,0,1,"CPV:CP$(CP)2:2190:DMIN")
#! Record("CPV:CP$(CP)2:2190:DMAX",2000,2312,0,1,"CPV:CP$(CP)2:2190:DMAX")
#! Record("CPV:CP$(CP)2:2190:TOPEN",1760,2492,0,1,"CPV:CP$(CP)2:2190:TOPEN")
#! Record("CPV:CP$(CP)2:2190:TCLOSE",2000,2512,0,1,"CPV:CP$(CP)2:2190:TCLOSE")
#! Record("CPV:CP$(CP)2:2190:MVAL",2000,2132,0,1,"CPV:CP$(CP)2:2190:MVAL")
#! Record("CPV:CP$(CP)2:2190:MODE",1567,2291,0,1,"CPV:CP$(CP)2:2190:MODE")
#! Record("CPV:CP$(CP)2:2190:CMD_OUT",2180,2152,0,1,"CPV:CP$(CP)2:2190:CMD_OUT")
#! Record("CPV:CP$(CP)2:2190:TCAL",2182,2332,0,1,"CPV:CP$(CP)2:2190:TCAL")
#! Record("CPV:CP$(CP)2:2190:ORBV",1760,2132,0,1,"CPV:CP$(CP)2:2190:ORBV")
#! Record("CPV:CP$(CP)2:2190:INTERLOCKED",2180,2532,0,1,"CPV:CP$(CP)2:2190:INTERLOCKED")
#! TextBox(TB0,1780,2120,2160,2080,0,"Dialog",12,1,16777215,"4kcb ramped  valve interface\n",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(stringin, "CPV:CP$(CP)2:2192:PIDTAG") {
  field(DESC, "Cold Intcpt CD valve")
  field(PINI, "YES")
  field(VAL, "C$(CP)PV22192")
}

record(ao, "CPV:CP$(CP)2:2192:DMIN") {
  field(DESC, "ramp DOWN stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22192.DMIN")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2192:DMAX") {
  field(DESC, "ramp UP stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22192.DMAX")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2192:TOPEN") {
  field(DESC, "valve open temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22192.TOpen")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2192:TCLOSE") {
  field(DESC, "valve close temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22192.TClose")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2192:MVAL") {
  field(DESC, "Valve position requested in manual mode")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22192.MVAL")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(bo, "CPV:CP$(CP)2:2192:MODE") {
  field(DESC, "set Auto or Manual mode")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) PV22192.Mode")
  field(ZNAM, "Auto")
  field(ONAM, "Manual")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CPV:CP$(CP)2:2192:CMD_OUT") {
  field(DESC, "Cold Intcpt CD valve")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22192O")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2192:TCAL") {
  field(DESC, "Temp diff calc before injection")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22192.TCal")
  field(PREC, "1")
  field(EGU, "K")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2192:ORBV") {
  field(DESC, "Cold Intcpt CD valve")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22192.ORBV")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(bi, "CPV:CP$(CP)2:2192:INTERLOCKED") {
  field(DESC, "Valve Interlocked Bit")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22192.Interlocked")
  field(ZNAM, "OK")
  field(ONAM, "Interlocked")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(1438,1981,1.0)
#! Record("CPV:CP$(CP)2:2192:PIDTAG",1560,2162,0,1,"CPV:CP$(CP)2:2192:PIDTAG")
#! Record("CPV:CP$(CP)2:2192:DMIN",1760,2312,0,1,"CPV:CP$(CP)2:2192:DMIN")
#! Record("CPV:CP$(CP)2:2192:DMAX",2000,2312,0,1,"CPV:CP$(CP)2:2192:DMAX")
#! Record("CPV:CP$(CP)2:2192:TOPEN",1760,2492,0,1,"CPV:CP$(CP)2:2192:TOPEN")
#! Record("CPV:CP$(CP)2:2192:TCLOSE",2000,2512,0,1,"CPV:CP$(CP)2:2192:TCLOSE")
#! Record("CPV:CP$(CP)2:2192:MVAL",2000,2132,0,1,"CPV:CP$(CP)2:2192:MVAL")
#! Record("CPV:CP$(CP)2:2192:MODE",1567,2291,0,1,"CPV:CP$(CP)2:2192:MODE")
#! Record("CPV:CP$(CP)2:2192:CMD_OUT",2180,2152,0,1,"CPV:CP$(CP)2:2192:CMD_OUT")
#! Record("CPV:CP$(CP)2:2192:TCAL",2182,2332,0,1,"CPV:CP$(CP)2:2192:TCAL")
#! Record("CPV:CP$(CP)2:2192:ORBV",1760,2132,0,1,"CPV:CP$(CP)2:2192:ORBV")
#! Record("CPV:CP$(CP)2:2192:INTERLOCKED",2180,2532,0,1,"CPV:CP$(CP)2:2192:INTERLOCKED")
#! TextBox(TB0,1780,2120,2160,2080,0,"Dialog",12,1,16777215,"4kcb ramped  valve interface\n",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(stringin, "CPV:CP$(CP)2:2220:PIDTAG") {
  field(DESC, "Warm Shields CD valve")
  field(PINI, "YES")
  field(VAL, "C$(CP)PV22220")
}

record(ao, "CPV:CP$(CP)2:2220:DMIN") {
  field(DESC, "ramp DOWN stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22220.DMIN")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2220:DMAX") {
  field(DESC, "ramp UP stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22220.DMAX")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2220:TOPEN") {
  field(DESC, "valve open temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22220.TOpen")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2220:TCLOSE") {
  field(DESC, "valve close temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22220.TClose")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2220:MVAL") {
  field(DESC, "Valve position requested in manual mode")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22220.MVAL")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(bo, "CPV:CP$(CP)2:2220:MODE") {
  field(DESC, "set Auto or Manual mode")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) PV22220.Mode")
  field(ZNAM, "Auto")
  field(ONAM, "Manual")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CPV:CP$(CP)2:2220:CMD_OUT") {
  field(DESC, "Warm Shields CD valve")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22220O")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2220:TCAL") {
  field(DESC, "Temp diff calc before injection")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22220.TCal")
  field(PREC, "1")
  field(EGU, "K")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2220:ORBV") {
  field(DESC, "Warm Shields CD valve")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22220.ORBV")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(bi, "CPV:CP$(CP)2:2220:INTERLOCKED") {
  field(DESC, "Valve Interlocked Bit")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22220.Interlocked")
  field(ZNAM, "OK")
  field(ONAM, "Interlocked")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(1438,1981,1.0)
#! Record("CPV:CP$(CP)2:2220:PIDTAG",1560,2162,0,1,"CPV:CP$(CP)2:2220:PIDTAG")
#! Record("CPV:CP$(CP)2:2220:DMIN",1760,2312,0,1,"CPV:CP$(CP)2:2220:DMIN")
#! Record("CPV:CP$(CP)2:2220:DMAX",2000,2312,0,1,"CPV:CP$(CP)2:2220:DMAX")
#! Record("CPV:CP$(CP)2:2220:TOPEN",1760,2492,0,1,"CPV:CP$(CP)2:2220:TOPEN")
#! Record("CPV:CP$(CP)2:2220:TCLOSE",2000,2512,0,1,"CPV:CP$(CP)2:2220:TCLOSE")
#! Record("CPV:CP$(CP)2:2220:MVAL",2000,2132,0,1,"CPV:CP$(CP)2:2220:MVAL")
#! Record("CPV:CP$(CP)2:2220:MODE",1567,2291,0,1,"CPV:CP$(CP)2:2220:MODE")
#! Record("CPV:CP$(CP)2:2220:CMD_OUT",2180,2152,0,1,"CPV:CP$(CP)2:2220:CMD_OUT")
#! Record("CPV:CP$(CP)2:2220:TCAL",2182,2332,0,1,"CPV:CP$(CP)2:2220:TCAL")
#! Record("CPV:CP$(CP)2:2220:ORBV",1760,2132,0,1,"CPV:CP$(CP)2:2220:ORBV")
#! Record("CPV:CP$(CP)2:2220:INTERLOCKED",2180,2532,0,1,"CPV:CP$(CP)2:2220:INTERLOCKED")
#! TextBox(TB0,1780,2120,2160,2080,0,"Dialog",12,1,16777215,"4kcb ramped  valve interface\n",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(stringin, "CPV:CP$(CP)2:2225:PIDTAG") {
  field(DESC, "Warm Shields rtn from 80K")
  field(PINI, "YES")
  field(VAL, "C$(CP)PV22225")
}

record(ao, "CPV:CP$(CP)2:2225:DMIN") {
  field(DESC, "ramp DOWN stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22225.DMIN")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2225:DMAX") {
  field(DESC, "ramp UP stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22225.DMAX")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2225:TOPEN") {
  field(DESC, "valve open temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22225.TOpen")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2225:TCLOSE") {
  field(DESC, "valve close temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22225.TClose")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2225:MVAL") {
  field(DESC, "Valve position requested in manual mode")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22225.MVAL")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(bo, "CPV:CP$(CP)2:2225:MODE") {
  field(DESC, "set Auto or Manual mode")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) PV22225.Mode")
  field(ZNAM, "Auto")
  field(ONAM, "Manual")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CPV:CP$(CP)2:2225:CMD_OUT") {
  field(DESC, "Warm Shields rtn from 80K")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22225O")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2225:TCAL") {
  field(DESC, "Temp diff calc before injection")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22225.TCal")
  field(PREC, "1")
  field(EGU, "K")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2225:ORBV") {
  field(DESC, "Warm Shields rtn from 80K")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22225.ORBV")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(bi, "CPV:CP$(CP)2:2225:INTERLOCKED") {
  field(DESC, "Valve Interlocked Bit")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22225.Interlocked")
  field(ZNAM, "OK")
  field(ONAM, "Interlocked")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(1438,1981,1.0)
#! Record("CPV:CP$(CP)2:2225:PIDTAG",1560,2162,0,1,"CPV:CP$(CP)2:2225:PIDTAG")
#! Record("CPV:CP$(CP)2:2225:DMIN",1760,2312,0,1,"CPV:CP$(CP)2:2225:DMIN")
#! Record("CPV:CP$(CP)2:2225:DMAX",2000,2312,0,1,"CPV:CP$(CP)2:2225:DMAX")
#! Record("CPV:CP$(CP)2:2225:TOPEN",1760,2492,0,1,"CPV:CP$(CP)2:2225:TOPEN")
#! Record("CPV:CP$(CP)2:2225:TCLOSE",2000,2512,0,1,"CPV:CP$(CP)2:2225:TCLOSE")
#! Record("CPV:CP$(CP)2:2225:MVAL",2000,2132,0,1,"CPV:CP$(CP)2:2225:MVAL")
#! Record("CPV:CP$(CP)2:2225:MODE",1567,2291,0,1,"CPV:CP$(CP)2:2225:MODE")
#! Record("CPV:CP$(CP)2:2225:CMD_OUT",2180,2152,0,1,"CPV:CP$(CP)2:2225:CMD_OUT")
#! Record("CPV:CP$(CP)2:2225:TCAL",2182,2332,0,1,"CPV:CP$(CP)2:2225:TCAL")
#! Record("CPV:CP$(CP)2:2225:ORBV",1760,2132,0,1,"CPV:CP$(CP)2:2225:ORBV")
#! Record("CPV:CP$(CP)2:2225:INTERLOCKED",2180,2532,0,1,"CPV:CP$(CP)2:2225:INTERLOCKED")
#! TextBox(TB0,1780,2120,2160,2080,0,"Dialog",12,1,16777215,"4kcb ramped  valve interface\n",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(stringin, "CPV:CP$(CP)2:2245:PIDTAG") {
  field(DESC, "Warm Shields sply from T1")
  field(PINI, "YES")
  field(VAL, "C$(CP)PV22245")
}

record(ao, "CPV:CP$(CP)2:2245:DMIN") {
  field(DESC, "ramp DOWN stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22245.DMIN")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2245:DMAX") {
  field(DESC, "ramp UP stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22245.DMAX")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2245:TOPEN") {
  field(DESC, "valve open temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22245.TOpen")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2245:TCLOSE") {
  field(DESC, "valve close temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22245.TClose")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2245:MVAL") {
  field(DESC, "Valve position requested in manual mode")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22245.MVAL")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(bo, "CPV:CP$(CP)2:2245:MODE") {
  field(DESC, "set Auto or Manual mode")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) PV22245.Mode")
  field(ZNAM, "Auto")
  field(ONAM, "Manual")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CPV:CP$(CP)2:2245:CMD_OUT") {
  field(DESC, "Warm Shields sply from T1")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22245O")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2245:TCAL") {
  field(DESC, "Temp diff calc before injection")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22245.TCal")
  field(PREC, "1")
  field(EGU, "K")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2245:ORBV") {
  field(DESC, "Warm Shields sply from T1")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22245.ORBV")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(bi, "CPV:CP$(CP)2:2245:INTERLOCKED") {
  field(DESC, "Valve Interlocked Bit")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22245.Interlocked")
  field(ZNAM, "OK")
  field(ONAM, "Interlocked")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(1438,1981,1.0)
#! Record("CPV:CP$(CP)2:2245:PIDTAG",1560,2162,0,1,"CPV:CP$(CP)2:2245:PIDTAG")
#! Record("CPV:CP$(CP)2:2245:DMIN",1760,2312,0,1,"CPV:CP$(CP)2:2245:DMIN")
#! Record("CPV:CP$(CP)2:2245:DMAX",2000,2312,0,1,"CPV:CP$(CP)2:2245:DMAX")
#! Record("CPV:CP$(CP)2:2245:TOPEN",1760,2492,0,1,"CPV:CP$(CP)2:2245:TOPEN")
#! Record("CPV:CP$(CP)2:2245:TCLOSE",2000,2512,0,1,"CPV:CP$(CP)2:2245:TCLOSE")
#! Record("CPV:CP$(CP)2:2245:MVAL",2000,2132,0,1,"CPV:CP$(CP)2:2245:MVAL")
#! Record("CPV:CP$(CP)2:2245:MODE",1567,2291,0,1,"CPV:CP$(CP)2:2245:MODE")
#! Record("CPV:CP$(CP)2:2245:CMD_OUT",2180,2152,0,1,"CPV:CP$(CP)2:2245:CMD_OUT")
#! Record("CPV:CP$(CP)2:2245:TCAL",2182,2332,0,1,"CPV:CP$(CP)2:2245:TCAL")
#! Record("CPV:CP$(CP)2:2245:ORBV",1760,2132,0,1,"CPV:CP$(CP)2:2245:ORBV")
#! Record("CPV:CP$(CP)2:2245:INTERLOCKED",2180,2532,0,1,"CPV:CP$(CP)2:2245:INTERLOCKED")
#! TextBox(TB0,1780,2120,2160,2080,0,"Dialog",12,1,16777215,"4kcb ramped  valve interface\n",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(stringin, "CPV:CP$(CP)2:2246:PIDTAG") {
  field(DESC, "T2 Outlet to shields ")
  field(PINI, "YES")
  field(VAL, "C$(CP)PV22246")
}

record(ao, "CPV:CP$(CP)2:2246:DMIN") {
  field(DESC, "ramp DOWN stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22246.DMIN")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2246:DMAX") {
  field(DESC, "ramp UP stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22246.DMAX")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2246:TOPEN") {
  field(DESC, "valve open temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22246.TOpen")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2246:TCLOSE") {
  field(DESC, "valve close temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22246.TClose")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2246:MVAL") {
  field(DESC, "Valve position requested in manual mode")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22246.MVAL")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(bo, "CPV:CP$(CP)2:2246:MODE") {
  field(DESC, "set Auto or Manual mode")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) PV22246.Mode")
  field(ZNAM, "Auto")
  field(ONAM, "Manual")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CPV:CP$(CP)2:2246:CMD_OUT") {
  field(DESC, "T2 Outlet to shields ")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22246O")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2246:TCAL") {
  field(DESC, "Temp diff calc before injection")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22246.TCal")
  field(PREC, "1")
  field(EGU, "K")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2246:ORBV") {
  field(DESC, "T2 Outlet to shields ")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22246.ORBV")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(bi, "CPV:CP$(CP)2:2246:INTERLOCKED") {
  field(DESC, "Valve Interlocked Bit")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22246.Interlocked")
  field(ZNAM, "OK")
  field(ONAM, "Interlocked")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(1438,1981,1.0)
#! Record("CPV:CP$(CP)2:2246:PIDTAG",1560,2162,0,1,"CPV:CP$(CP)2:2246:PIDTAG")
#! Record("CPV:CP$(CP)2:2246:DMIN",1760,2312,0,1,"CPV:CP$(CP)2:2246:DMIN")
#! Record("CPV:CP$(CP)2:2246:DMAX",2000,2312,0,1,"CPV:CP$(CP)2:2246:DMAX")
#! Record("CPV:CP$(CP)2:2246:TOPEN",1760,2492,0,1,"CPV:CP$(CP)2:2246:TOPEN")
#! Record("CPV:CP$(CP)2:2246:TCLOSE",2000,2512,0,1,"CPV:CP$(CP)2:2246:TCLOSE")
#! Record("CPV:CP$(CP)2:2246:MVAL",2000,2132,0,1,"CPV:CP$(CP)2:2246:MVAL")
#! Record("CPV:CP$(CP)2:2246:MODE",1567,2291,0,1,"CPV:CP$(CP)2:2246:MODE")
#! Record("CPV:CP$(CP)2:2246:CMD_OUT",2180,2152,0,1,"CPV:CP$(CP)2:2246:CMD_OUT")
#! Record("CPV:CP$(CP)2:2246:TCAL",2182,2332,0,1,"CPV:CP$(CP)2:2246:TCAL")
#! Record("CPV:CP$(CP)2:2246:ORBV",1760,2132,0,1,"CPV:CP$(CP)2:2246:ORBV")
#! Record("CPV:CP$(CP)2:2246:INTERLOCKED",2180,2532,0,1,"CPV:CP$(CP)2:2246:INTERLOCKED")
#! TextBox(TB0,1780,2120,2160,2080,0,"Dialog",12,1,16777215,"4kcb ramped  valve interface\n",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(stringin, "CPV:CP$(CP)2:2248:PIDTAG") {
  field(DESC, "Warm Shields sply from T2")
  field(PINI, "YES")
  field(VAL, "C$(CP)PV22248")
}

record(ao, "CPV:CP$(CP)2:2248:DMIN") {
  field(DESC, "ramp DOWN stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22248.DMIN")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2248:DMAX") {
  field(DESC, "ramp UP stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22248.DMAX")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2248:TOPEN") {
  field(DESC, "valve open temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22248.TOpen")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2248:TCLOSE") {
  field(DESC, "valve close temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22248.TClose")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2248:MVAL") {
  field(DESC, "Valve position requested in manual mode")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22248.MVAL")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(bo, "CPV:CP$(CP)2:2248:MODE") {
  field(DESC, "set Auto or Manual mode")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) PV22248.Mode")
  field(ZNAM, "Auto")
  field(ONAM, "Manual")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CPV:CP$(CP)2:2248:CMD_OUT") {
  field(DESC, "Warm Shields sply from T2")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22248O")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2248:TCAL") {
  field(DESC, "Temp diff calc before injection")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22248.TCal")
  field(PREC, "1")
  field(EGU, "K")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2248:ORBV") {
  field(DESC, "Warm Shields sply from T2")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22248.ORBV")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(bi, "CPV:CP$(CP)2:2248:INTERLOCKED") {
  field(DESC, "Valve Interlocked Bit")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22248.Interlocked")
  field(ZNAM, "OK")
  field(ONAM, "Interlocked")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(1438,1981,1.0)
#! Record("CPV:CP$(CP)2:2248:PIDTAG",1560,2162,0,1,"CPV:CP$(CP)2:2248:PIDTAG")
#! Record("CPV:CP$(CP)2:2248:DMIN",1760,2312,0,1,"CPV:CP$(CP)2:2248:DMIN")
#! Record("CPV:CP$(CP)2:2248:DMAX",2000,2312,0,1,"CPV:CP$(CP)2:2248:DMAX")
#! Record("CPV:CP$(CP)2:2248:TOPEN",1760,2492,0,1,"CPV:CP$(CP)2:2248:TOPEN")
#! Record("CPV:CP$(CP)2:2248:TCLOSE",2000,2512,0,1,"CPV:CP$(CP)2:2248:TCLOSE")
#! Record("CPV:CP$(CP)2:2248:MVAL",2000,2132,0,1,"CPV:CP$(CP)2:2248:MVAL")
#! Record("CPV:CP$(CP)2:2248:MODE",1567,2291,0,1,"CPV:CP$(CP)2:2248:MODE")
#! Record("CPV:CP$(CP)2:2248:CMD_OUT",2180,2152,0,1,"CPV:CP$(CP)2:2248:CMD_OUT")
#! Record("CPV:CP$(CP)2:2248:TCAL",2182,2332,0,1,"CPV:CP$(CP)2:2248:TCAL")
#! Record("CPV:CP$(CP)2:2248:ORBV",1760,2132,0,1,"CPV:CP$(CP)2:2248:ORBV")
#! Record("CPV:CP$(CP)2:2248:INTERLOCKED",2180,2532,0,1,"CPV:CP$(CP)2:2248:INTERLOCKED")
#! TextBox(TB0,1780,2120,2160,2080,0,"Dialog",12,1,16777215,"4kcb ramped  valve interface\n",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(stringin, "CPV:CP$(CP)2:2249:PIDTAG") {
  field(DESC, "Warm Shields rtn valve")
  field(PINI, "YES")
  field(VAL, "C$(CP)PV22249")
}

record(ao, "CPV:CP$(CP)2:2249:DMIN") {
  field(DESC, "ramp DOWN stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22249.DMIN")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2249:DMAX") {
  field(DESC, "ramp UP stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22249.DMAX")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2249:TOPEN") {
  field(DESC, "valve open temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22249.TOpen")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2249:TCLOSE") {
  field(DESC, "valve close temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22249.TClose")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2249:MVAL") {
  field(DESC, "Valve position requested in manual mode")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22249.MVAL")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(bo, "CPV:CP$(CP)2:2249:MODE") {
  field(DESC, "set Auto or Manual mode")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) PV22249.Mode")
  field(ZNAM, "Auto")
  field(ONAM, "Manual")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CPV:CP$(CP)2:2249:CMD_OUT") {
  field(DESC, "Warm Shields rtn valve")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22249O")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2249:TCAL") {
  field(DESC, "Temp diff calc before injection")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22249.TCal")
  field(PREC, "1")
  field(EGU, "K")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2249:ORBV") {
  field(DESC, "Warm Shields rtn valve")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22249.ORBV")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(bi, "CPV:CP$(CP)2:2249:INTERLOCKED") {
  field(DESC, "Valve Interlocked Bit")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22249.Interlocked")
  field(ZNAM, "OK")
  field(ONAM, "Interlocked")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(1438,1981,1.0)
#! Record("CPV:CP$(CP)2:2249:PIDTAG",1560,2162,0,1,"CPV:CP$(CP)2:2249:PIDTAG")
#! Record("CPV:CP$(CP)2:2249:DMIN",1760,2312,0,1,"CPV:CP$(CP)2:2249:DMIN")
#! Record("CPV:CP$(CP)2:2249:DMAX",2000,2312,0,1,"CPV:CP$(CP)2:2249:DMAX")
#! Record("CPV:CP$(CP)2:2249:TOPEN",1760,2492,0,1,"CPV:CP$(CP)2:2249:TOPEN")
#! Record("CPV:CP$(CP)2:2249:TCLOSE",2000,2512,0,1,"CPV:CP$(CP)2:2249:TCLOSE")
#! Record("CPV:CP$(CP)2:2249:MVAL",2000,2132,0,1,"CPV:CP$(CP)2:2249:MVAL")
#! Record("CPV:CP$(CP)2:2249:MODE",1567,2291,0,1,"CPV:CP$(CP)2:2249:MODE")
#! Record("CPV:CP$(CP)2:2249:CMD_OUT",2180,2152,0,1,"CPV:CP$(CP)2:2249:CMD_OUT")
#! Record("CPV:CP$(CP)2:2249:TCAL",2182,2332,0,1,"CPV:CP$(CP)2:2249:TCAL")
#! Record("CPV:CP$(CP)2:2249:ORBV",1760,2132,0,1,"CPV:CP$(CP)2:2249:ORBV")
#! Record("CPV:CP$(CP)2:2249:INTERLOCKED",2180,2532,0,1,"CPV:CP$(CP)2:2249:INTERLOCKED")
#! TextBox(TB0,1780,2120,2160,2080,0,"Dialog",12,1,16777215,"4kcb ramped  valve interface\n",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(stringin, "CPV:CP$(CP)2:2400:PIDTAG") {
  field(DESC, "HX-1B HP inlet valve")
  field(PINI, "YES")
  field(VAL, "C$(CP)PV22400")
}

record(ao, "CPV:CP$(CP)2:2400:DMIN") {
  field(DESC, "ramp DOWN stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22400.DMIN")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2400:DMAX") {
  field(DESC, "ramp UP stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22400.DMAX")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2400:TOPEN") {
  field(DESC, "valve open temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22400.TOpen")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2400:TCLOSE") {
  field(DESC, "valve close temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22400.TClose")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2400:MVAL") {
  field(DESC, "Valve position requested in manual mode")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22400.MVAL")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(bo, "CPV:CP$(CP)2:2400:MODE") {
  field(DESC, "set Auto or Manual mode")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) PV22400.Mode")
  field(ZNAM, "Auto")
  field(ONAM, "Manual")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CPV:CP$(CP)2:2400:CMD_OUT") {
  field(DESC, "HX-1B HP inlet valve")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22400O")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2400:TCAL") {
  field(DESC, "Temp diff calc before injection")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22400.TCal")
  field(PREC, "1")
  field(EGU, "K")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2400:ORBV") {
  field(DESC, "HX-1B HP inlet valve")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22400.ORBV")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(bi, "CPV:CP$(CP)2:2400:INTERLOCKED") {
  field(DESC, "Valve Interlocked Bit")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22400.Interlocked")
  field(ZNAM, "OK")
  field(ONAM, "Interlocked")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(1438,1981,1.0)
#! Record("CPV:CP$(CP)2:2400:PIDTAG",1560,2162,0,1,"CPV:CP$(CP)2:2400:PIDTAG")
#! Record("CPV:CP$(CP)2:2400:DMIN",1760,2312,0,1,"CPV:CP$(CP)2:2400:DMIN")
#! Record("CPV:CP$(CP)2:2400:DMAX",2000,2312,0,1,"CPV:CP$(CP)2:2400:DMAX")
#! Record("CPV:CP$(CP)2:2400:TOPEN",1760,2492,0,1,"CPV:CP$(CP)2:2400:TOPEN")
#! Record("CPV:CP$(CP)2:2400:TCLOSE",2000,2512,0,1,"CPV:CP$(CP)2:2400:TCLOSE")
#! Record("CPV:CP$(CP)2:2400:MVAL",2000,2132,0,1,"CPV:CP$(CP)2:2400:MVAL")
#! Record("CPV:CP$(CP)2:2400:MODE",1567,2291,0,1,"CPV:CP$(CP)2:2400:MODE")
#! Record("CPV:CP$(CP)2:2400:CMD_OUT",2180,2152,0,1,"CPV:CP$(CP)2:2400:CMD_OUT")
#! Record("CPV:CP$(CP)2:2400:TCAL",2182,2332,0,1,"CPV:CP$(CP)2:2400:TCAL")
#! Record("CPV:CP$(CP)2:2400:ORBV",1760,2132,0,1,"CPV:CP$(CP)2:2400:ORBV")
#! Record("CPV:CP$(CP)2:2400:INTERLOCKED",2180,2532,0,1,"CPV:CP$(CP)2:2400:INTERLOCKED")
#! TextBox(TB0,1780,2120,2160,2080,0,"Dialog",12,1,16777215,"4kcb ramped  valve interface\n",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(stringin, "CPV:CP$(CP)2:2402:PIDTAG") {
  field(DESC, "HX-1A HP inlet valve")
  field(PINI, "YES")
  field(VAL, "C$(CP)PV22402")
}

record(ao, "CPV:CP$(CP)2:2402:DMIN") {
  field(DESC, "ramp DOWN stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22402.DMIN")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2402:DMAX") {
  field(DESC, "ramp UP stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22402.DMAX")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2402:TOPEN") {
  field(DESC, "valve open temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22402.TOpen")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2402:TCLOSE") {
  field(DESC, "valve close temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22402.TClose")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2402:MVAL") {
  field(DESC, "Valve position requested in manual mode")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22402.MVAL")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(bo, "CPV:CP$(CP)2:2402:MODE") {
  field(DESC, "set Auto or Manual mode")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) PV22402.Mode")
  field(ZNAM, "Auto")
  field(ONAM, "Manual")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CPV:CP$(CP)2:2402:CMD_OUT") {
  field(DESC, "HX-1A HP inlet valve")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22402O")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2402:TCAL") {
  field(DESC, "Temp diff calc before injection")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22402.TCal")
  field(PREC, "1")
  field(EGU, "K")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2402:ORBV") {
  field(DESC, "HX-1A HP inlet valve")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22402.ORBV")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(bi, "CPV:CP$(CP)2:2402:INTERLOCKED") {
  field(DESC, "Valve Interlocked Bit")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22402.Interlocked")
  field(ZNAM, "OK")
  field(ONAM, "Interlocked")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(1438,1981,1.0)
#! Record("CPV:CP$(CP)2:2402:PIDTAG",1560,2162,0,1,"CPV:CP$(CP)2:2402:PIDTAG")
#! Record("CPV:CP$(CP)2:2402:DMIN",1760,2312,0,1,"CPV:CP$(CP)2:2402:DMIN")
#! Record("CPV:CP$(CP)2:2402:DMAX",2000,2312,0,1,"CPV:CP$(CP)2:2402:DMAX")
#! Record("CPV:CP$(CP)2:2402:TOPEN",1760,2492,0,1,"CPV:CP$(CP)2:2402:TOPEN")
#! Record("CPV:CP$(CP)2:2402:TCLOSE",2000,2512,0,1,"CPV:CP$(CP)2:2402:TCLOSE")
#! Record("CPV:CP$(CP)2:2402:MVAL",2000,2132,0,1,"CPV:CP$(CP)2:2402:MVAL")
#! Record("CPV:CP$(CP)2:2402:MODE",1567,2291,0,1,"CPV:CP$(CP)2:2402:MODE")
#! Record("CPV:CP$(CP)2:2402:CMD_OUT",2180,2152,0,1,"CPV:CP$(CP)2:2402:CMD_OUT")
#! Record("CPV:CP$(CP)2:2402:TCAL",2182,2332,0,1,"CPV:CP$(CP)2:2402:TCAL")
#! Record("CPV:CP$(CP)2:2402:ORBV",1760,2132,0,1,"CPV:CP$(CP)2:2402:ORBV")
#! Record("CPV:CP$(CP)2:2402:INTERLOCKED",2180,2532,0,1,"CPV:CP$(CP)2:2402:INTERLOCKED")
#! TextBox(TB0,1780,2120,2160,2080,0,"Dialog",12,1,16777215,"4kcb ramped  valve interface\n",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(stringin, "CPV:CP$(CP)2:2415:A:PIDTAG") {
  field(DESC, "80K adsbr A inlet valve")
  field(PINI, "YES")
  field(VAL, "C$(CP)PV22415A")
}

record(ao, "CPV:CP$(CP)2:2415:A:DMIN") {
  field(DESC, "ramp DOWN stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22415A.DMIN")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2415:A:DMAX") {
  field(DESC, "ramp UP stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22415A.DMAX")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2415:A:TOPEN") {
  field(DESC, "valve open temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22415A.TOpen")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2415:A:TCLOSE") {
  field(DESC, "valve close temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22415A.TClose")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2415:A:MVAL") {
  field(DESC, "Valve position requested in manual mode")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22415A.MVAL")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(bo, "CPV:CP$(CP)2:2415:A:MODE") {
  field(DESC, "set Auto or Manual mode")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) PV22415A.Mode")
  field(ZNAM, "Auto")
  field(ONAM, "Manual")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CPV:CP$(CP)2:2415:A:CMD_OUT") {
  field(DESC, "80K adsbr A inlet valve")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22415AO")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2415:A:TCAL") {
  field(DESC, "Temp diff calc before injection")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22415A.TCal")
  field(PREC, "1")
  field(EGU, "K")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2415:A:ORBV") {
  field(DESC, "80K adsbr A inlet valve")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22415A.ORBV")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(bi, "CPV:CP$(CP)2:2415:A:INTERLOCKED") {
  field(DESC, "Valve Interlocked Bit")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22415A.Interlocked")
  field(ZNAM, "OK")
  field(ONAM, "Interlocked")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(1438,1981,1.0)
#! Record("CPV:CP$(CP)2:2415:A:PIDTAG",1560,2162,0,1,"CPV:CP$(CP)2:2415:A:PIDTAG")
#! Record("CPV:CP$(CP)2:2415:A:DMIN",1760,2312,0,1,"CPV:CP$(CP)2:2415:A:DMIN")
#! Record("CPV:CP$(CP)2:2415:A:DMAX",2000,2312,0,1,"CPV:CP$(CP)2:2415:A:DMAX")
#! Record("CPV:CP$(CP)2:2415:A:TOPEN",1760,2492,0,1,"CPV:CP$(CP)2:2415:A:TOPEN")
#! Record("CPV:CP$(CP)2:2415:A:TCLOSE",2000,2512,0,1,"CPV:CP$(CP)2:2415:A:TCLOSE")
#! Record("CPV:CP$(CP)2:2415:A:MVAL",2000,2132,0,1,"CPV:CP$(CP)2:2415:A:MVAL")
#! Record("CPV:CP$(CP)2:2415:A:MODE",1567,2291,0,1,"CPV:CP$(CP)2:2415:A:MODE")
#! Record("CPV:CP$(CP)2:2415:A:CMD_OUT",2180,2152,0,1,"CPV:CP$(CP)2:2415:A:CMD_OUT")
#! Record("CPV:CP$(CP)2:2415:A:TCAL",2182,2332,0,1,"CPV:CP$(CP)2:2415:A:TCAL")
#! Record("CPV:CP$(CP)2:2415:A:ORBV",1760,2132,0,1,"CPV:CP$(CP)2:2415:A:ORBV")
#! Record("CPV:CP$(CP)2:2415:A:INTERLOCKED",2180,2532,0,1,"CPV:CP$(CP)2:2415:A:INTERLOCKED")
#! TextBox(TB0,1780,2120,2160,2080,0,"Dialog",12,1,16777215,"4kcb ramped  valve interface\n",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(stringin, "CPV:CP$(CP)2:2415:B:PIDTAG") {
  field(DESC, "80K adsbr B inlet valve")
  field(PINI, "YES")
  field(VAL, "C$(CP)PV22415B")
}

record(ao, "CPV:CP$(CP)2:2415:B:DMIN") {
  field(DESC, "ramp DOWN stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22415B.DMIN")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2415:B:DMAX") {
  field(DESC, "ramp UP stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22415B.DMAX")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2415:B:TOPEN") {
  field(DESC, "valve open temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22415B.TOpen")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2415:B:TCLOSE") {
  field(DESC, "valve close temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22415B.TClose")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2415:B:MVAL") {
  field(DESC, "Valve position requested in manual mode")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22415B.MVAL")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(bo, "CPV:CP$(CP)2:2415:B:MODE") {
  field(DESC, "set Auto or Manual mode")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) PV22415B.Mode")
  field(ZNAM, "Auto")
  field(ONAM, "Manual")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CPV:CP$(CP)2:2415:B:CMD_OUT") {
  field(DESC, "80K adsbr B inlet valve")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22415BO")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2415:B:TCAL") {
  field(DESC, "Temp diff calc before injection")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22415B.TCal")
  field(PREC, "1")
  field(EGU, "K")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2415:B:ORBV") {
  field(DESC, "80K adsbr B inlet valve")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22415B.ORBV")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(bi, "CPV:CP$(CP)2:2415:B:INTERLOCKED") {
  field(DESC, "Valve Interlocked Bit")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22415B.Interlocked")
  field(ZNAM, "OK")
  field(ONAM, "Interlocked")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(1438,1981,1.0)
#! Record("CPV:CP$(CP)2:2415:B:PIDTAG",1560,2162,0,1,"CPV:CP$(CP)2:2415:B:PIDTAG")
#! Record("CPV:CP$(CP)2:2415:B:DMIN",1760,2312,0,1,"CPV:CP$(CP)2:2415:B:DMIN")
#! Record("CPV:CP$(CP)2:2415:B:DMAX",2000,2312,0,1,"CPV:CP$(CP)2:2415:B:DMAX")
#! Record("CPV:CP$(CP)2:2415:B:TOPEN",1760,2492,0,1,"CPV:CP$(CP)2:2415:B:TOPEN")
#! Record("CPV:CP$(CP)2:2415:B:TCLOSE",2000,2512,0,1,"CPV:CP$(CP)2:2415:B:TCLOSE")
#! Record("CPV:CP$(CP)2:2415:B:MVAL",2000,2132,0,1,"CPV:CP$(CP)2:2415:B:MVAL")
#! Record("CPV:CP$(CP)2:2415:B:MODE",1567,2291,0,1,"CPV:CP$(CP)2:2415:B:MODE")
#! Record("CPV:CP$(CP)2:2415:B:CMD_OUT",2180,2152,0,1,"CPV:CP$(CP)2:2415:B:CMD_OUT")
#! Record("CPV:CP$(CP)2:2415:B:TCAL",2182,2332,0,1,"CPV:CP$(CP)2:2415:B:TCAL")
#! Record("CPV:CP$(CP)2:2415:B:ORBV",1760,2132,0,1,"CPV:CP$(CP)2:2415:B:ORBV")
#! Record("CPV:CP$(CP)2:2415:B:INTERLOCKED",2180,2532,0,1,"CPV:CP$(CP)2:2415:B:INTERLOCKED")
#! TextBox(TB0,1780,2120,2160,2080,0,"Dialog",12,1,16777215,"4kcb ramped  valve interface\n",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(stringin, "CPV:CP$(CP)2:2420:A:PIDTAG") {
  field(DESC, "80K adsbr A outlet valve")
  field(PINI, "YES")
  field(VAL, "C$(CP)PV22420A")
}

record(ao, "CPV:CP$(CP)2:2420:A:DMIN") {
  field(DESC, "ramp DOWN stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22420A.DMIN")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2420:A:DMAX") {
  field(DESC, "ramp UP stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22420A.DMAX")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2420:A:TOPEN") {
  field(DESC, "valve open temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22420A.TOpen")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2420:A:TCLOSE") {
  field(DESC, "valve close temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22420A.TClose")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2420:A:MVAL") {
  field(DESC, "Valve position requested in manual mode")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22420A.MVAL")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(bo, "CPV:CP$(CP)2:2420:A:MODE") {
  field(DESC, "set Auto or Manual mode")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) PV22420A.Mode")
  field(ZNAM, "Auto")
  field(ONAM, "Manual")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CPV:CP$(CP)2:2420:A:CMD_OUT") {
  field(DESC, "80K adsbr A outlet valve")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22420AO")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2420:A:TCAL") {
  field(DESC, "Temp diff calc before injection")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22420A.TCal")
  field(PREC, "1")
  field(EGU, "K")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2420:A:ORBV") {
  field(DESC, "80K adsbr A outlet valve")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22420A.ORBV")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(bi, "CPV:CP$(CP)2:2420:A:INTERLOCKED") {
  field(DESC, "Valve Interlocked Bit")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22420A.Interlocked")
  field(ZNAM, "OK")
  field(ONAM, "Interlocked")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(1438,1981,1.0)
#! Record("CPV:CP$(CP)2:2420:A:PIDTAG",1560,2162,0,1,"CPV:CP$(CP)2:2420:A:PIDTAG")
#! Record("CPV:CP$(CP)2:2420:A:DMIN",1760,2312,0,1,"CPV:CP$(CP)2:2420:A:DMIN")
#! Record("CPV:CP$(CP)2:2420:A:DMAX",2000,2312,0,1,"CPV:CP$(CP)2:2420:A:DMAX")
#! Record("CPV:CP$(CP)2:2420:A:TOPEN",1760,2492,0,1,"CPV:CP$(CP)2:2420:A:TOPEN")
#! Record("CPV:CP$(CP)2:2420:A:TCLOSE",2000,2512,0,1,"CPV:CP$(CP)2:2420:A:TCLOSE")
#! Record("CPV:CP$(CP)2:2420:A:MVAL",2000,2132,0,1,"CPV:CP$(CP)2:2420:A:MVAL")
#! Record("CPV:CP$(CP)2:2420:A:MODE",1567,2291,0,1,"CPV:CP$(CP)2:2420:A:MODE")
#! Record("CPV:CP$(CP)2:2420:A:CMD_OUT",2180,2152,0,1,"CPV:CP$(CP)2:2420:A:CMD_OUT")
#! Record("CPV:CP$(CP)2:2420:A:TCAL",2182,2332,0,1,"CPV:CP$(CP)2:2420:A:TCAL")
#! Record("CPV:CP$(CP)2:2420:A:ORBV",1760,2132,0,1,"CPV:CP$(CP)2:2420:A:ORBV")
#! Record("CPV:CP$(CP)2:2420:A:INTERLOCKED",2180,2532,0,1,"CPV:CP$(CP)2:2420:A:INTERLOCKED")
#! TextBox(TB0,1780,2120,2160,2080,0,"Dialog",12,1,16777215,"4kcb ramped  valve interface\n",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(stringin, "CPV:CP$(CP)2:2420:B:PIDTAG") {
  field(DESC, "80K adsbr B outlet valve")
  field(PINI, "YES")
  field(VAL, "C$(CP)PV22420B")
}

record(ao, "CPV:CP$(CP)2:2420:B:DMIN") {
  field(DESC, "ramp DOWN stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22420B.DMIN")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2420:B:DMAX") {
  field(DESC, "ramp UP stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22420B.DMAX")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2420:B:TOPEN") {
  field(DESC, "valve open temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22420B.TOpen")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2420:B:TCLOSE") {
  field(DESC, "valve close temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22420B.TClose")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2420:B:MVAL") {
  field(DESC, "Valve position requested in manual mode")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22420B.MVAL")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(bo, "CPV:CP$(CP)2:2420:B:MODE") {
  field(DESC, "set Auto or Manual mode")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) PV22420B.Mode")
  field(ZNAM, "Auto")
  field(ONAM, "Manual")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CPV:CP$(CP)2:2420:B:CMD_OUT") {
  field(DESC, "80K adsbr B outlet valve")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22420BO")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2420:B:TCAL") {
  field(DESC, "Temp diff calc before injection")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22420B.TCal")
  field(PREC, "1")
  field(EGU, "K")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2420:B:ORBV") {
  field(DESC, "80K adsbr B outlet valve")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22420B.ORBV")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(bi, "CPV:CP$(CP)2:2420:B:INTERLOCKED") {
  field(DESC, "Valve Interlocked Bit")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22420B.Interlocked")
  field(ZNAM, "OK")
  field(ONAM, "Interlocked")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(1438,1981,1.0)
#! Record("CPV:CP$(CP)2:2420:B:PIDTAG",1560,2162,0,1,"CPV:CP$(CP)2:2420:B:PIDTAG")
#! Record("CPV:CP$(CP)2:2420:B:DMIN",1760,2312,0,1,"CPV:CP$(CP)2:2420:B:DMIN")
#! Record("CPV:CP$(CP)2:2420:B:DMAX",2000,2312,0,1,"CPV:CP$(CP)2:2420:B:DMAX")
#! Record("CPV:CP$(CP)2:2420:B:TOPEN",1760,2492,0,1,"CPV:CP$(CP)2:2420:B:TOPEN")
#! Record("CPV:CP$(CP)2:2420:B:TCLOSE",2000,2512,0,1,"CPV:CP$(CP)2:2420:B:TCLOSE")
#! Record("CPV:CP$(CP)2:2420:B:MVAL",2000,2132,0,1,"CPV:CP$(CP)2:2420:B:MVAL")
#! Record("CPV:CP$(CP)2:2420:B:MODE",1567,2291,0,1,"CPV:CP$(CP)2:2420:B:MODE")
#! Record("CPV:CP$(CP)2:2420:B:CMD_OUT",2180,2152,0,1,"CPV:CP$(CP)2:2420:B:CMD_OUT")
#! Record("CPV:CP$(CP)2:2420:B:TCAL",2182,2332,0,1,"CPV:CP$(CP)2:2420:B:TCAL")
#! Record("CPV:CP$(CP)2:2420:B:ORBV",1760,2132,0,1,"CPV:CP$(CP)2:2420:B:ORBV")
#! Record("CPV:CP$(CP)2:2420:B:INTERLOCKED",2180,2532,0,1,"CPV:CP$(CP)2:2420:B:INTERLOCKED")
#! TextBox(TB0,1780,2120,2160,2080,0,"Dialog",12,1,16777215,"4kcb ramped  valve interface\n",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(stringin, "CPV:CP$(CP)2:2421:PIDTAG") {
  field(DESC, "80K adsbr bypass valve")
  field(PINI, "YES")
  field(VAL, "C$(CP)PV22421")
}

record(ao, "CPV:CP$(CP)2:2421:DMIN") {
  field(DESC, "ramp DOWN stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22421.DMIN")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2421:DMAX") {
  field(DESC, "ramp UP stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22421.DMAX")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2421:TOPEN") {
  field(DESC, "valve open temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22421.TOpen")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2421:TCLOSE") {
  field(DESC, "valve close temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22421.TClose")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2421:MVAL") {
  field(DESC, "Valve position requested in manual mode")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22421.MVAL")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(bo, "CPV:CP$(CP)2:2421:MODE") {
  field(DESC, "set Auto or Manual mode")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) PV22421.Mode")
  field(ZNAM, "Auto")
  field(ONAM, "Manual")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CPV:CP$(CP)2:2421:CMD_OUT") {
  field(DESC, "80K adsbr bypass valve")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22421O")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2421:TCAL") {
  field(DESC, "Temp diff calc before injection")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22421.TCal")
  field(PREC, "1")
  field(EGU, "K")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2421:ORBV") {
  field(DESC, "80K adsbr bypass valve")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22421.ORBV")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(bi, "CPV:CP$(CP)2:2421:INTERLOCKED") {
  field(DESC, "Valve Interlocked Bit")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22421.Interlocked")
  field(ZNAM, "OK")
  field(ONAM, "Interlocked")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(1438,1981,1.0)
#! Record("CPV:CP$(CP)2:2421:PIDTAG",1560,2162,0,1,"CPV:CP$(CP)2:2421:PIDTAG")
#! Record("CPV:CP$(CP)2:2421:DMIN",1760,2312,0,1,"CPV:CP$(CP)2:2421:DMIN")
#! Record("CPV:CP$(CP)2:2421:DMAX",2000,2312,0,1,"CPV:CP$(CP)2:2421:DMAX")
#! Record("CPV:CP$(CP)2:2421:TOPEN",1760,2492,0,1,"CPV:CP$(CP)2:2421:TOPEN")
#! Record("CPV:CP$(CP)2:2421:TCLOSE",2000,2512,0,1,"CPV:CP$(CP)2:2421:TCLOSE")
#! Record("CPV:CP$(CP)2:2421:MVAL",2000,2132,0,1,"CPV:CP$(CP)2:2421:MVAL")
#! Record("CPV:CP$(CP)2:2421:MODE",1567,2291,0,1,"CPV:CP$(CP)2:2421:MODE")
#! Record("CPV:CP$(CP)2:2421:CMD_OUT",2180,2152,0,1,"CPV:CP$(CP)2:2421:CMD_OUT")
#! Record("CPV:CP$(CP)2:2421:TCAL",2182,2332,0,1,"CPV:CP$(CP)2:2421:TCAL")
#! Record("CPV:CP$(CP)2:2421:ORBV",1760,2132,0,1,"CPV:CP$(CP)2:2421:ORBV")
#! Record("CPV:CP$(CP)2:2421:INTERLOCKED",2180,2532,0,1,"CPV:CP$(CP)2:2421:INTERLOCKED")
#! TextBox(TB0,1780,2120,2160,2080,0,"Dialog",12,1,16777215,"4kcb ramped  valve interface\n",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(stringin, "CPV:CP$(CP)2:2460:PIDTAG") {
  field(DESC, "20K adsbr bypass valve")
  field(PINI, "YES")
  field(VAL, "C$(CP)PV22460")
}

record(ao, "CPV:CP$(CP)2:2460:DMIN") {
  field(DESC, "ramp DOWN stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22460.DMIN")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2460:DMAX") {
  field(DESC, "ramp UP stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22460.DMAX")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2460:TOPEN") {
  field(DESC, "valve open temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22460.TOpen")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2460:TCLOSE") {
  field(DESC, "valve close temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22460.TClose")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2460:MVAL") {
  field(DESC, "Valve position requested in manual mode")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22460.MVAL")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(bo, "CPV:CP$(CP)2:2460:MODE") {
  field(DESC, "set Auto or Manual mode")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) PV22460.Mode")
  field(ZNAM, "Auto")
  field(ONAM, "Manual")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CPV:CP$(CP)2:2460:CMD_OUT") {
  field(DESC, "20K adsbr bypass valve")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22460O")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2460:TCAL") {
  field(DESC, "Temp diff calc before injection")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22460.TCal")
  field(PREC, "1")
  field(EGU, "K")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2460:ORBV") {
  field(DESC, "20K adsbr bypass valve")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22460.ORBV")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(bi, "CPV:CP$(CP)2:2460:INTERLOCKED") {
  field(DESC, "Valve Interlocked Bit")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22460.Interlocked")
  field(ZNAM, "OK")
  field(ONAM, "Interlocked")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(1438,1981,1.0)
#! Record("CPV:CP$(CP)2:2460:PIDTAG",1560,2162,0,1,"CPV:CP$(CP)2:2460:PIDTAG")
#! Record("CPV:CP$(CP)2:2460:DMIN",1760,2312,0,1,"CPV:CP$(CP)2:2460:DMIN")
#! Record("CPV:CP$(CP)2:2460:DMAX",2000,2312,0,1,"CPV:CP$(CP)2:2460:DMAX")
#! Record("CPV:CP$(CP)2:2460:TOPEN",1760,2492,0,1,"CPV:CP$(CP)2:2460:TOPEN")
#! Record("CPV:CP$(CP)2:2460:TCLOSE",2000,2512,0,1,"CPV:CP$(CP)2:2460:TCLOSE")
#! Record("CPV:CP$(CP)2:2460:MVAL",2000,2132,0,1,"CPV:CP$(CP)2:2460:MVAL")
#! Record("CPV:CP$(CP)2:2460:MODE",1567,2291,0,1,"CPV:CP$(CP)2:2460:MODE")
#! Record("CPV:CP$(CP)2:2460:CMD_OUT",2180,2152,0,1,"CPV:CP$(CP)2:2460:CMD_OUT")
#! Record("CPV:CP$(CP)2:2460:TCAL",2182,2332,0,1,"CPV:CP$(CP)2:2460:TCAL")
#! Record("CPV:CP$(CP)2:2460:ORBV",1760,2132,0,1,"CPV:CP$(CP)2:2460:ORBV")
#! Record("CPV:CP$(CP)2:2460:INTERLOCKED",2180,2532,0,1,"CPV:CP$(CP)2:2460:INTERLOCKED")
#! TextBox(TB0,1780,2120,2160,2080,0,"Dialog",12,1,16777215,"4kcb ramped  valve interface\n",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(stringin, "CPV:CP$(CP)2:2461:PIDTAG") {
  field(DESC, "20K adsbr inlet valve")
  field(PINI, "YES")
  field(VAL, "C$(CP)PV22461")
}

record(ao, "CPV:CP$(CP)2:2461:DMIN") {
  field(DESC, "ramp DOWN stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22461.DMIN")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2461:DMAX") {
  field(DESC, "ramp UP stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22461.DMAX")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2461:TOPEN") {
  field(DESC, "valve open temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22461.TOpen")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2461:TCLOSE") {
  field(DESC, "valve close temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22461.TClose")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2461:MVAL") {
  field(DESC, "Valve position requested in manual mode")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22461.MVAL")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(bo, "CPV:CP$(CP)2:2461:MODE") {
  field(DESC, "set Auto or Manual mode")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) PV22461.Mode")
  field(ZNAM, "Auto")
  field(ONAM, "Manual")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CPV:CP$(CP)2:2461:CMD_OUT") {
  field(DESC, "20K adsbr inlet valve")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22461O")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2461:TCAL") {
  field(DESC, "Temp diff calc before injection")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22461.TCal")
  field(PREC, "1")
  field(EGU, "K")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2461:ORBV") {
  field(DESC, "20K adsbr inlet valve")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22461.ORBV")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(bi, "CPV:CP$(CP)2:2461:INTERLOCKED") {
  field(DESC, "Valve Interlocked Bit")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22461.Interlocked")
  field(ZNAM, "OK")
  field(ONAM, "Interlocked")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(1438,1981,1.0)
#! Record("CPV:CP$(CP)2:2461:PIDTAG",1560,2162,0,1,"CPV:CP$(CP)2:2461:PIDTAG")
#! Record("CPV:CP$(CP)2:2461:DMIN",1760,2312,0,1,"CPV:CP$(CP)2:2461:DMIN")
#! Record("CPV:CP$(CP)2:2461:DMAX",2000,2312,0,1,"CPV:CP$(CP)2:2461:DMAX")
#! Record("CPV:CP$(CP)2:2461:TOPEN",1760,2492,0,1,"CPV:CP$(CP)2:2461:TOPEN")
#! Record("CPV:CP$(CP)2:2461:TCLOSE",2000,2512,0,1,"CPV:CP$(CP)2:2461:TCLOSE")
#! Record("CPV:CP$(CP)2:2461:MVAL",2000,2132,0,1,"CPV:CP$(CP)2:2461:MVAL")
#! Record("CPV:CP$(CP)2:2461:MODE",1567,2291,0,1,"CPV:CP$(CP)2:2461:MODE")
#! Record("CPV:CP$(CP)2:2461:CMD_OUT",2180,2152,0,1,"CPV:CP$(CP)2:2461:CMD_OUT")
#! Record("CPV:CP$(CP)2:2461:TCAL",2182,2332,0,1,"CPV:CP$(CP)2:2461:TCAL")
#! Record("CPV:CP$(CP)2:2461:ORBV",1760,2132,0,1,"CPV:CP$(CP)2:2461:ORBV")
#! Record("CPV:CP$(CP)2:2461:INTERLOCKED",2180,2532,0,1,"CPV:CP$(CP)2:2461:INTERLOCKED")
#! TextBox(TB0,1780,2120,2160,2080,0,"Dialog",12,1,16777215,"4kcb ramped  valve interface\n",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(stringin, "CPV:CP$(CP)2:2466:PIDTAG") {
  field(DESC, "20K adsbr outlet valve")
  field(PINI, "YES")
  field(VAL, "C$(CP)PV22466")
}

record(ao, "CPV:CP$(CP)2:2466:DMIN") {
  field(DESC, "ramp DOWN stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22466.DMIN")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2466:DMAX") {
  field(DESC, "ramp UP stepsize")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22466.DMAX")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2466:TOPEN") {
  field(DESC, "valve open temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22466.TOpen")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2466:TCLOSE") {
  field(DESC, "valve close temperature")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22466.TClose")
  field(EGU, "K")
  field(PREC, "2")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CPV:CP$(CP)2:2466:MVAL") {
  field(DESC, "Valve position requested in manual mode")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) PV22466.MVAL")
  field(EGU, "%")
  field(PREC, "1")
  field(IVOA, "Don't drive outputs")
}

record(bo, "CPV:CP$(CP)2:2466:MODE") {
  field(DESC, "set Auto or Manual mode")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) PV22466.Mode")
  field(ZNAM, "Auto")
  field(ONAM, "Manual")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CPV:CP$(CP)2:2466:CMD_OUT") {
  field(DESC, "20K adsbr outlet valve")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22466O")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2466:TCAL") {
  field(DESC, "Temp diff calc before injection")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22466.TCal")
  field(PREC, "1")
  field(EGU, "K")
  field(ADEL, "0.05")
}

record(ai, "CPV:CP$(CP)2:2466:ORBV") {
  field(DESC, "20K adsbr outlet valve")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22466.ORBV")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.05")
}

record(bi, "CPV:CP$(CP)2:2466:INTERLOCKED") {
  field(DESC, "Valve Interlocked Bit")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PV22466.Interlocked")
  field(ZNAM, "OK")
  field(ONAM, "Interlocked")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(1438,1981,1.0)
#! Record("CPV:CP$(CP)2:2466:PIDTAG",1560,2162,0,1,"CPV:CP$(CP)2:2466:PIDTAG")
#! Record("CPV:CP$(CP)2:2466:DMIN",1760,2312,0,1,"CPV:CP$(CP)2:2466:DMIN")
#! Record("CPV:CP$(CP)2:2466:DMAX",2000,2312,0,1,"CPV:CP$(CP)2:2466:DMAX")
#! Record("CPV:CP$(CP)2:2466:TOPEN",1760,2492,0,1,"CPV:CP$(CP)2:2466:TOPEN")
#! Record("CPV:CP$(CP)2:2466:TCLOSE",2000,2512,0,1,"CPV:CP$(CP)2:2466:TCLOSE")
#! Record("CPV:CP$(CP)2:2466:MVAL",2000,2132,0,1,"CPV:CP$(CP)2:2466:MVAL")
#! Record("CPV:CP$(CP)2:2466:MODE",1567,2291,0,1,"CPV:CP$(CP)2:2466:MODE")
#! Record("CPV:CP$(CP)2:2466:CMD_OUT",2180,2152,0,1,"CPV:CP$(CP)2:2466:CMD_OUT")
#! Record("CPV:CP$(CP)2:2466:TCAL",2182,2332,0,1,"CPV:CP$(CP)2:2466:TCAL")
#! Record("CPV:CP$(CP)2:2466:ORBV",1760,2132,0,1,"CPV:CP$(CP)2:2466:ORBV")
#! Record("CPV:CP$(CP)2:2466:INTERLOCKED",2180,2532,0,1,"CPV:CP$(CP)2:2466:INTERLOCKED")
#! TextBox(TB0,1780,2120,2160,2080,0,"Dialog",12,1,16777215,"4kcb ramped  valve interface\n",null)
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CVAC:CP$(CP)2:3610:ORDER_ON") {
  field(DESC, "UCB vacuum skid order on")
  field(ZNAM, "not ordered on")
  field(ONAM, "ordered on")
  field(OMSL, "supervisory")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CVAC:CP$(CP)2:3610:ON_CNCL") {
  field(DESC, "UCB vacuum skid Cancel ON order")
  field(ZNAM, "not cancelled")
  field(ONAM, "cancelled")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CVAC:CP$(CP)2:3610:ORDER_OFF") {
  field(DESC, "UCB vacuum skid order off")
  field(ZNAM, "not order off")
  field(ONAM, "order off")
  field(OMSL, "supervisory")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CVAC:CP$(CP)2:3610:OFF_CNCL") {
  field(DESC, "UCB vacuum skid Cancel OFF order")
  field(ZNAM, "not cancelled")
  field(ONAM, "cancelled")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CVAC:CP$(CP)2:3610:ON_CFRM") {
  field(DESC, "UCB vacuum skid confirm ON order")
  field(ZNAM, "not confirmed")
  field(ONAM, "confirmed")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
  field(OMSL, "supervisory")
}

record(bo, "CVAC:CP$(CP)2:3610:OFF_CFRM") {
  field(DESC, "UCB vacuum skid confirm OFF order")
  field(ZNAM, "not confirmed")
  field(ONAM, "confirmed")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CVAC:CP$(CP)2:3610:RQST_ON") {
  field(DESC, "UCB vacuum skid Rqst On")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) VAC_CMD B 0")
  field(ZNAM, "not active")
  field(ONAM, "Active")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(ASG, "NOWRITE")
  field(HIGH, "0")
  field(OMSL, "supervisory")
}

record(bo, "CVAC:CP$(CP)2:3610:RQST_OFF") {
  field(DESC, "UCB vacuum skid Rqst Off")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) VAC_CMD B 1")
  field(ZNAM, "not active")
  field(ONAM, "Active")
  field(ASG, "NOWRITE")
  field(PINI, "NO")
  field(HIGH, "0")
  field(SCAN, "1 second")
  field(OMSL, "supervisory")
}

record(sub, "CVAC:CP$(CP)2:3610:ORDER_ONL") {
  field(DESC, "UCB vacuum skid")
  field(SCAN, ".5 second")
  field(PINI, "NO")
  field(FLNK, "CVAC:CP$(CP)2:3610:ORDER_ONT")
  field(INAM, "Icclmom")
  field(SNAM, "Scclmom")
  field(INPA, "CVAC:CP$(CP)2:3610:ORDER_ON")
  field(INPB, "CVAC:CP$(CP)2:3610:ON_CFRM")
  field(INPC, "CVAC:CP$(CP)2:3610:ON_CNCL")
  field(ASG, "NOWRITE")
}

record(bo, "CVAC:CP$(CP)2:3610:ORDER_ONT") {
  field(DESC, "UCB vacuum skid")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "closed_loop")
  field(DOL, "CVAC:CP$(CP)2:3610:ORDER_ONL")
  field(OUT, "CVAC:CP$(CP)2:3610:RQST_ON")
  field(ZSV, "MAJOR")
  field(ASG, "NOWRITE")
  field(ZNAM, "disabled")
  field(ONAM, "enabled")
  field(OSV, "NO_ALARM")
  field(COSV, "NO_ALARM")
}

record(sub, "CVAC:CP$(CP)2:3610:ORDER_OFFL") {
  field(DESC, "UCB vacuum skid")
  field(SCAN, ".5 second")
  field(PINI, "NO")
  field(FLNK, "CVAC:CP$(CP)2:3610:ORDER_OFFT")
  field(INAM, "Icclmom")
  field(SNAM, "Scclmom")
  field(INPA, "CVAC:CP$(CP)2:3610:ORDER_OFF")
  field(INPB, "CVAC:CP$(CP)2:3610:OFF_CFRM")
  field(INPC, "CVAC:CP$(CP)2:3610:OFF_CNCL")
  field(ASG, "NOWRITE")
}

record(bo, "CVAC:CP$(CP)2:3610:ORDER_OFFT") {
  field(DESC, "UCB vacuum skid")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(OMSL, "closed_loop")
  field(DOL, "CVAC:CP$(CP)2:3610:ORDER_OFFL")
  field(OUT, "CVAC:CP$(CP)2:3610:RQST_OFF")
  field(ZSV, "MAJOR")
  field(ASG, "NOWRITE")
  field(ZNAM, "disabled")
  field(ONAM, "enabled")
  field(OSV, "NO_ALARM")
  field(COSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,416,1.1)
#! Record("CVAC:CP$(CP)2:3610:ORDER_ON",80,378,0,1,"CVAC:CP$(CP)2:3610:ORDER_ON")
#! Field("CVAC:CP$(CP)2:3610:ORDER_ON.VAL",16777215,1,"CVAC:CP$(CP)2:3610:ORDER_ON.VAL")
#! Record("CVAC:CP$(CP)2:3610:ON_CNCL",80,798,0,1,"CVAC:CP$(CP)2:3610:ON_CNCL")
#! Field("CVAC:CP$(CP)2:3610:ON_CNCL.VAL",16777215,1,"CVAC:CP$(CP)2:3610:ON_CNCL.VAL")
#! Record("CVAC:CP$(CP)2:3610:ORDER_OFF",80,1018,0,1,"CVAC:CP$(CP)2:3610:ORDER_OFF")
#! Field("CVAC:CP$(CP)2:3610:ORDER_OFF.VAL",16777215,1,"CVAC:CP$(CP)2:3610:ORDER_OFF.VAL")
#! Record("CVAC:CP$(CP)2:3610:OFF_CNCL",80,1458,0,1,"CVAC:CP$(CP)2:3610:OFF_CNCL")
#! Field("CVAC:CP$(CP)2:3610:OFF_CNCL.VAL",16777215,1,"CVAC:CP$(CP)2:3610:OFF_CNCL.VAL")
#! Record("CVAC:CP$(CP)2:3610:ON_CFRM",80,578,0,1,"CVAC:CP$(CP)2:3610:ON_CFRM")
#! Field("CVAC:CP$(CP)2:3610:ON_CFRM.VAL",16777215,1,"CVAC:CP$(CP)2:3610:ON_CFRM.VAL")
#! Record("CVAC:CP$(CP)2:3610:OFF_CFRM",80,1238,0,1,"CVAC:CP$(CP)2:3610:OFF_CFRM")
#! Field("CVAC:CP$(CP)2:3610:OFF_CFRM.VAL",16777215,1,"CVAC:CP$(CP)2:3610:OFF_CFRM.VAL")
#! Record("CVAC:CP$(CP)2:3610:RQST_ON",960,584,0,1,"CVAC:CP$(CP)2:3610:RQST_ON")
#! Field("CVAC:CP$(CP)2:3610:RQST_ON.VAL",16777215,1,"CVAC:CP$(CP)2:3610:RQST_ON.VAL")
#! Record("CVAC:CP$(CP)2:3610:RQST_OFF",960,1204,0,1,"CVAC:CP$(CP)2:3610:RQST_OFF")
#! Field("CVAC:CP$(CP)2:3610:RQST_OFF.VAL",16777215,1,"CVAC:CP$(CP)2:3610:RQST_OFF.VAL")
#! Record("CVAC:CP$(CP)2:3610:ORDER_ONL",400,524,0,1,"CVAC:CP$(CP)2:3610:ORDER_ONL")
#! Field("CVAC:CP$(CP)2:3610:ORDER_ONL.FLNK",16777215,1,"CVAC:CP$(CP)2:3610:ORDER_ONL.FLNK")
#! Link("CVAC:CP$(CP)2:3610:ORDER_ONL.FLNK","CVAC:CP$(CP)2:3610:ORDER_ONT")
#! Field("CVAC:CP$(CP)2:3610:ORDER_ONL.INPA",16777215,0,"CVAC:CP$(CP)2:3610:ORDER_ONL.INPA")
#! Link("CVAC:CP$(CP)2:3610:ORDER_ONL.INPA","CVAC:CP$(CP)2:3610:ORDER_ON.VAL")
#! Field("CVAC:CP$(CP)2:3610:ORDER_ONL.INPB",16777215,0,"CVAC:CP$(CP)2:3610:ORDER_ONL.INPB")
#! Link("CVAC:CP$(CP)2:3610:ORDER_ONL.INPB","CVAC:CP$(CP)2:3610:ON_CFRM.VAL")
#! Field("CVAC:CP$(CP)2:3610:ORDER_ONL.INPC",16777215,0,"CVAC:CP$(CP)2:3610:ORDER_ONL.INPC")
#! Link("CVAC:CP$(CP)2:3610:ORDER_ONL.INPC","CVAC:CP$(CP)2:3610:ON_CNCL.VAL")
#! Field("CVAC:CP$(CP)2:3610:ORDER_ONL.VAL",16777215,1,"CVAC:CP$(CP)2:3610:ORDER_ONL.VAL")
#! Record("CVAC:CP$(CP)2:3610:ORDER_ONT",700,522,0,0,"CVAC:CP$(CP)2:3610:ORDER_ONT")
#! Field("CVAC:CP$(CP)2:3610:ORDER_ONT.DOL",16777215,0,"CVAC:CP$(CP)2:3610:ORDER_ONT.DOL")
#! Link("CVAC:CP$(CP)2:3610:ORDER_ONT.DOL","CVAC:CP$(CP)2:3610:ORDER_ONL.VAL")
#! Field("CVAC:CP$(CP)2:3610:ORDER_ONT.OUT",16777215,1,"CVAC:CP$(CP)2:3610:ORDER_ONT.OUT")
#! Link("CVAC:CP$(CP)2:3610:ORDER_ONT.OUT","CVAC:CP$(CP)2:3610:RQST_ON.VAL")
#! Record("CVAC:CP$(CP)2:3610:ORDER_OFFL",400,1124,0,1,"CVAC:CP$(CP)2:3610:ORDER_OFFL")
#! Field("CVAC:CP$(CP)2:3610:ORDER_OFFL.FLNK",16777215,1,"CVAC:CP$(CP)2:3610:ORDER_OFFL.FLNK")
#! Link("CVAC:CP$(CP)2:3610:ORDER_OFFL.FLNK","CVAC:CP$(CP)2:3610:ORDER_OFFT")
#! Field("CVAC:CP$(CP)2:3610:ORDER_OFFL.INPA",16777215,0,"CVAC:CP$(CP)2:3610:ORDER_OFFL.INPA")
#! Link("CVAC:CP$(CP)2:3610:ORDER_OFFL.INPA","CVAC:CP$(CP)2:3610:ORDER_OFF.VAL")
#! Field("CVAC:CP$(CP)2:3610:ORDER_OFFL.INPC",16777215,0,"CVAC:CP$(CP)2:3610:ORDER_OFFL.INPC")
#! Link("CVAC:CP$(CP)2:3610:ORDER_OFFL.INPC","CVAC:CP$(CP)2:3610:OFF_CNCL.VAL")
#! Field("CVAC:CP$(CP)2:3610:ORDER_OFFL.INPB",16777215,0,"CVAC:CP$(CP)2:3610:ORDER_OFFL.INPB")
#! Link("CVAC:CP$(CP)2:3610:ORDER_OFFL.INPB","CVAC:CP$(CP)2:3610:OFF_CFRM.VAL")
#! Field("CVAC:CP$(CP)2:3610:ORDER_OFFL.VAL",16777215,1,"CVAC:CP$(CP)2:3610:ORDER_OFFL.VAL")
#! Record("CVAC:CP$(CP)2:3610:ORDER_OFFT",700,1156,0,0,"CVAC:CP$(CP)2:3610:ORDER_OFFT")
#! Field("CVAC:CP$(CP)2:3610:ORDER_OFFT.DOL",16777215,0,"CVAC:CP$(CP)2:3610:ORDER_OFFT.DOL")
#! Link("CVAC:CP$(CP)2:3610:ORDER_OFFT.DOL","CVAC:CP$(CP)2:3610:ORDER_OFFL.VAL")
#! Field("CVAC:CP$(CP)2:3610:ORDER_OFFT.OUT",16777215,1,"CVAC:CP$(CP)2:3610:ORDER_OFFT.OUT")
#! Link("CVAC:CP$(CP)2:3610:ORDER_OFFT.OUT","CVAC:CP$(CP)2:3610:RQST_OFF.VAL")
#! TextBox(TB1,480,360,780,400,0,"Dialog",12,1,16777215,"Turn On and confirm logic\nTurn Off and confirm logic\n",null)
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CVAC:CP$(CP)2:3630:ORDER_ON") {
  field(DESC, "LCB vacuum skid order on")
  field(ZNAM, "not ordered on")
  field(ONAM, "ordered on")
  field(OMSL, "supervisory")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CVAC:CP$(CP)2:3630:ON_CNCL") {
  field(DESC, "LCB vacuum skid Cancel ON order")
  field(ZNAM, "not cancelled")
  field(ONAM, "cancelled")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CVAC:CP$(CP)2:3630:ORDER_OFF") {
  field(DESC, "LCB vacuum skid order off")
  field(ZNAM, "not order off")
  field(ONAM, "order off")
  field(OMSL, "supervisory")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CVAC:CP$(CP)2:3630:OFF_CNCL") {
  field(DESC, "LCB vacuum skid Cancel OFF order")
  field(ZNAM, "not cancelled")
  field(ONAM, "cancelled")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CVAC:CP$(CP)2:3630:ON_CFRM") {
  field(DESC, "LCB vacuum skid confirm ON order")
  field(ZNAM, "not confirmed")
  field(ONAM, "confirmed")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
  field(OMSL, "supervisory")
}

record(bo, "CVAC:CP$(CP)2:3630:OFF_CFRM") {
  field(DESC, "LCB vacuum skid confirm OFF order")
  field(ZNAM, "not confirmed")
  field(ONAM, "confirmed")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CVAC:CP$(CP)2:3630:RQST_ON") {
  field(DESC, "LCB vacuum skid Rqst On")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) VAC_CMD B 10")
  field(ZNAM, "not active")
  field(ONAM, "Active")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(ASG, "NOWRITE")
  field(HIGH, "0")
  field(OMSL, "supervisory")
}

record(bo, "CVAC:CP$(CP)2:3630:RQST_OFF") {
  field(DESC, "LCB vacuum skid Rqst Off")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) VAC_CMD B 11")
  field(ZNAM, "not active")
  field(ONAM, "Active")
  field(ASG, "NOWRITE")
  field(PINI, "NO")
  field(HIGH, "0")
  field(SCAN, "1 second")
  field(OMSL, "supervisory")
}

record(sub, "CVAC:CP$(CP)2:3630:ORDER_ONL") {
  field(DESC, "LCB vacuum skid")
  field(SCAN, ".5 second")
  field(PINI, "NO")
  field(FLNK, "CVAC:CP$(CP)2:3630:ORDER_ONT")
  field(INAM, "Icclmom")
  field(SNAM, "Scclmom")
  field(INPA, "CVAC:CP$(CP)2:3630:ORDER_ON")
  field(INPB, "CVAC:CP$(CP)2:3630:ON_CFRM")
  field(INPC, "CVAC:CP$(CP)2:3630:ON_CNCL")
  field(ASG, "NOWRITE")
}

record(bo, "CVAC:CP$(CP)2:3630:ORDER_ONT") {
  field(DESC, "LCB vacuum skid")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "closed_loop")
  field(DOL, "CVAC:CP$(CP)2:3630:ORDER_ONL")
  field(OUT, "CVAC:CP$(CP)2:3630:RQST_ON")
  field(ZSV, "MAJOR")
  field(ASG, "NOWRITE")
  field(ZNAM, "disabled")
  field(ONAM, "enabled")
  field(OSV, "NO_ALARM")
  field(COSV, "NO_ALARM")
}

record(sub, "CVAC:CP$(CP)2:3630:ORDER_OFFL") {
  field(DESC, "LCB vacuum skid")
  field(SCAN, ".5 second")
  field(PINI, "NO")
  field(FLNK, "CVAC:CP$(CP)2:3630:ORDER_OFFT")
  field(INAM, "Icclmom")
  field(SNAM, "Scclmom")
  field(INPA, "CVAC:CP$(CP)2:3630:ORDER_OFF")
  field(INPB, "CVAC:CP$(CP)2:3630:OFF_CFRM")
  field(INPC, "CVAC:CP$(CP)2:3630:OFF_CNCL")
  field(ASG, "NOWRITE")
}

record(bo, "CVAC:CP$(CP)2:3630:ORDER_OFFT") {
  field(DESC, "LCB vacuum skid")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(OMSL, "closed_loop")
  field(DOL, "CVAC:CP$(CP)2:3630:ORDER_OFFL")
  field(OUT, "CVAC:CP$(CP)2:3630:RQST_OFF")
  field(ZSV, "MAJOR")
  field(ASG, "NOWRITE")
  field(ZNAM, "disabled")
  field(ONAM, "enabled")
  field(OSV, "NO_ALARM")
  field(COSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,416,1.1)
#! Record("CVAC:CP$(CP)2:3630:ORDER_ON",80,378,0,1,"CVAC:CP$(CP)2:3630:ORDER_ON")
#! Field("CVAC:CP$(CP)2:3630:ORDER_ON.VAL",16777215,1,"CVAC:CP$(CP)2:3630:ORDER_ON.VAL")
#! Record("CVAC:CP$(CP)2:3630:ON_CNCL",80,798,0,1,"CVAC:CP$(CP)2:3630:ON_CNCL")
#! Field("CVAC:CP$(CP)2:3630:ON_CNCL.VAL",16777215,1,"CVAC:CP$(CP)2:3630:ON_CNCL.VAL")
#! Record("CVAC:CP$(CP)2:3630:ORDER_OFF",80,1018,0,1,"CVAC:CP$(CP)2:3630:ORDER_OFF")
#! Field("CVAC:CP$(CP)2:3630:ORDER_OFF.VAL",16777215,1,"CVAC:CP$(CP)2:3630:ORDER_OFF.VAL")
#! Record("CVAC:CP$(CP)2:3630:OFF_CNCL",80,1458,0,1,"CVAC:CP$(CP)2:3630:OFF_CNCL")
#! Field("CVAC:CP$(CP)2:3630:OFF_CNCL.VAL",16777215,1,"CVAC:CP$(CP)2:3630:OFF_CNCL.VAL")
#! Record("CVAC:CP$(CP)2:3630:ON_CFRM",80,578,0,1,"CVAC:CP$(CP)2:3630:ON_CFRM")
#! Field("CVAC:CP$(CP)2:3630:ON_CFRM.VAL",16777215,1,"CVAC:CP$(CP)2:3630:ON_CFRM.VAL")
#! Record("CVAC:CP$(CP)2:3630:OFF_CFRM",80,1238,0,1,"CVAC:CP$(CP)2:3630:OFF_CFRM")
#! Field("CVAC:CP$(CP)2:3630:OFF_CFRM.VAL",16777215,1,"CVAC:CP$(CP)2:3630:OFF_CFRM.VAL")
#! Record("CVAC:CP$(CP)2:3630:RQST_ON",960,584,0,1,"CVAC:CP$(CP)2:3630:RQST_ON")
#! Field("CVAC:CP$(CP)2:3630:RQST_ON.VAL",16777215,1,"CVAC:CP$(CP)2:3630:RQST_ON.VAL")
#! Record("CVAC:CP$(CP)2:3630:RQST_OFF",960,1204,0,1,"CVAC:CP$(CP)2:3630:RQST_OFF")
#! Field("CVAC:CP$(CP)2:3630:RQST_OFF.VAL",16777215,1,"CVAC:CP$(CP)2:3630:RQST_OFF.VAL")
#! Record("CVAC:CP$(CP)2:3630:ORDER_ONL",400,524,0,1,"CVAC:CP$(CP)2:3630:ORDER_ONL")
#! Field("CVAC:CP$(CP)2:3630:ORDER_ONL.FLNK",16777215,1,"CVAC:CP$(CP)2:3630:ORDER_ONL.FLNK")
#! Link("CVAC:CP$(CP)2:3630:ORDER_ONL.FLNK","CVAC:CP$(CP)2:3630:ORDER_ONT")
#! Field("CVAC:CP$(CP)2:3630:ORDER_ONL.INPA",16777215,0,"CVAC:CP$(CP)2:3630:ORDER_ONL.INPA")
#! Link("CVAC:CP$(CP)2:3630:ORDER_ONL.INPA","CVAC:CP$(CP)2:3630:ORDER_ON.VAL")
#! Field("CVAC:CP$(CP)2:3630:ORDER_ONL.INPB",16777215,0,"CVAC:CP$(CP)2:3630:ORDER_ONL.INPB")
#! Link("CVAC:CP$(CP)2:3630:ORDER_ONL.INPB","CVAC:CP$(CP)2:3630:ON_CFRM.VAL")
#! Field("CVAC:CP$(CP)2:3630:ORDER_ONL.INPC",16777215,0,"CVAC:CP$(CP)2:3630:ORDER_ONL.INPC")
#! Link("CVAC:CP$(CP)2:3630:ORDER_ONL.INPC","CVAC:CP$(CP)2:3630:ON_CNCL.VAL")
#! Field("CVAC:CP$(CP)2:3630:ORDER_ONL.VAL",16777215,1,"CVAC:CP$(CP)2:3630:ORDER_ONL.VAL")
#! Record("CVAC:CP$(CP)2:3630:ORDER_ONT",700,522,0,0,"CVAC:CP$(CP)2:3630:ORDER_ONT")
#! Field("CVAC:CP$(CP)2:3630:ORDER_ONT.DOL",16777215,0,"CVAC:CP$(CP)2:3630:ORDER_ONT.DOL")
#! Link("CVAC:CP$(CP)2:3630:ORDER_ONT.DOL","CVAC:CP$(CP)2:3630:ORDER_ONL.VAL")
#! Field("CVAC:CP$(CP)2:3630:ORDER_ONT.OUT",16777215,1,"CVAC:CP$(CP)2:3630:ORDER_ONT.OUT")
#! Link("CVAC:CP$(CP)2:3630:ORDER_ONT.OUT","CVAC:CP$(CP)2:3630:RQST_ON.VAL")
#! Record("CVAC:CP$(CP)2:3630:ORDER_OFFL",400,1124,0,1,"CVAC:CP$(CP)2:3630:ORDER_OFFL")
#! Field("CVAC:CP$(CP)2:3630:ORDER_OFFL.FLNK",16777215,1,"CVAC:CP$(CP)2:3630:ORDER_OFFL.FLNK")
#! Link("CVAC:CP$(CP)2:3630:ORDER_OFFL.FLNK","CVAC:CP$(CP)2:3630:ORDER_OFFT")
#! Field("CVAC:CP$(CP)2:3630:ORDER_OFFL.INPA",16777215,0,"CVAC:CP$(CP)2:3630:ORDER_OFFL.INPA")
#! Link("CVAC:CP$(CP)2:3630:ORDER_OFFL.INPA","CVAC:CP$(CP)2:3630:ORDER_OFF.VAL")
#! Field("CVAC:CP$(CP)2:3630:ORDER_OFFL.INPC",16777215,0,"CVAC:CP$(CP)2:3630:ORDER_OFFL.INPC")
#! Link("CVAC:CP$(CP)2:3630:ORDER_OFFL.INPC","CVAC:CP$(CP)2:3630:OFF_CNCL.VAL")
#! Field("CVAC:CP$(CP)2:3630:ORDER_OFFL.INPB",16777215,0,"CVAC:CP$(CP)2:3630:ORDER_OFFL.INPB")
#! Link("CVAC:CP$(CP)2:3630:ORDER_OFFL.INPB","CVAC:CP$(CP)2:3630:OFF_CFRM.VAL")
#! Field("CVAC:CP$(CP)2:3630:ORDER_OFFL.VAL",16777215,1,"CVAC:CP$(CP)2:3630:ORDER_OFFL.VAL")
#! Record("CVAC:CP$(CP)2:3630:ORDER_OFFT",700,1156,0,0,"CVAC:CP$(CP)2:3630:ORDER_OFFT")
#! Field("CVAC:CP$(CP)2:3630:ORDER_OFFT.DOL",16777215,0,"CVAC:CP$(CP)2:3630:ORDER_OFFT.DOL")
#! Link("CVAC:CP$(CP)2:3630:ORDER_OFFT.DOL","CVAC:CP$(CP)2:3630:ORDER_OFFL.VAL")
#! Field("CVAC:CP$(CP)2:3630:ORDER_OFFT.OUT",16777215,1,"CVAC:CP$(CP)2:3630:ORDER_OFFT.OUT")
#! Link("CVAC:CP$(CP)2:3630:ORDER_OFFT.OUT","CVAC:CP$(CP)2:3630:RQST_OFF.VAL")
#! TextBox(TB1,480,360,780,400,0,"Dialog",12,1,16777215,"Turn On and confirm logic\nTurn Off and confirm logic\n",null)
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CTBN:CP$(CP)2:1:ORDER_ON") {
  field(DESC, "Turbine 1  order on")
  field(ZNAM, "not ordered on")
  field(ONAM, "ordered on")
  field(OMSL, "supervisory")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CTBN:CP$(CP)2:1:ON_CNCL") {
  field(DESC, "Turbine 1  Cancel ON order")
  field(ZNAM, "not cancelled")
  field(ONAM, "cancelled")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CTBN:CP$(CP)2:1:ORDER_OFF") {
  field(DESC, "Turbine 1  order off")
  field(ZNAM, "not order off")
  field(ONAM, "order off")
  field(OMSL, "supervisory")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CTBN:CP$(CP)2:1:OFF_CNCL") {
  field(DESC, "Turbine 1  Cancel OFF order")
  field(ZNAM, "not cancelled")
  field(ONAM, "cancelled")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CTBN:CP$(CP)2:1:ON_CFRM") {
  field(DESC, "Turbine 1  confirm ON order")
  field(ZNAM, "not confirmed")
  field(ONAM, "confirmed")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
  field(OMSL, "supervisory")
}

record(bo, "CTBN:CP$(CP)2:1:OFF_CFRM") {
  field(DESC, "Turbine 1  confirm OFF order")
  field(ZNAM, "not confirmed")
  field(ONAM, "confirmed")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CTBN:CP$(CP)2:1:RQST_ON") {
  field(DESC, "Turbine 1  Rqst On")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) Turbine_CMD B 1")
  field(ZNAM, "not active")
  field(ONAM, "Active")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(ASG, "NOWRITE")
  field(HIGH, "0")
  field(OMSL, "supervisory")
}

record(bo, "CTBN:CP$(CP)2:1:RQST_OFF") {
  field(DESC, "Turbine 1  Rqst Off")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) Turbine_CMD B 2")
  field(ZNAM, "not active")
  field(ONAM, "Active")
  field(ASG, "NOWRITE")
  field(PINI, "NO")
  field(HIGH, "0")
  field(SCAN, "1 second")
  field(OMSL, "supervisory")
}

record(sub, "CTBN:CP$(CP)2:1:ORDER_ONL") {
  field(DESC, "Turbine 1 ")
  field(SCAN, ".5 second")
  field(PINI, "NO")
  field(FLNK, "CTBN:CP$(CP)2:1:ORDER_ONT")
  field(INAM, "Icclmom")
  field(SNAM, "Scclmom")
  field(INPA, "CTBN:CP$(CP)2:1:ORDER_ON")
  field(INPB, "CTBN:CP$(CP)2:1:ON_CFRM")
  field(INPC, "CTBN:CP$(CP)2:1:ON_CNCL")
  field(ASG, "NOWRITE")
}

record(bo, "CTBN:CP$(CP)2:1:ORDER_ONT") {
  field(DESC, "Turbine 1 ")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "closed_loop")
  field(DOL, "CTBN:CP$(CP)2:1:ORDER_ONL")
  field(OUT, "CTBN:CP$(CP)2:1:RQST_ON")
  field(ZSV, "MAJOR")
  field(ASG, "NOWRITE")
  field(ZNAM, "disabled")
  field(ONAM, "enabled")
  field(OSV, "NO_ALARM")
  field(COSV, "NO_ALARM")
}

record(sub, "CTBN:CP$(CP)2:1:ORDER_OFFL") {
  field(DESC, "Turbine 1 ")
  field(SCAN, ".5 second")
  field(PINI, "NO")
  field(FLNK, "CTBN:CP$(CP)2:1:ORDER_OFFT")
  field(INAM, "Icclmom")
  field(SNAM, "Scclmom")
  field(INPA, "CTBN:CP$(CP)2:1:ORDER_OFF")
  field(INPB, "CTBN:CP$(CP)2:1:OFF_CFRM")
  field(INPC, "CTBN:CP$(CP)2:1:OFF_CNCL")
  field(ASG, "NOWRITE")
}

record(bo, "CTBN:CP$(CP)2:1:ORDER_OFFT") {
  field(DESC, "Turbine 1 ")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(OMSL, "closed_loop")
  field(DOL, "CTBN:CP$(CP)2:1:ORDER_OFFL")
  field(OUT, "CTBN:CP$(CP)2:1:RQST_OFF")
  field(ZSV, "MAJOR")
  field(ASG, "NOWRITE")
  field(ZNAM, "disabled")
  field(ONAM, "enabled")
  field(OSV, "NO_ALARM")
  field(COSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,416,1.1)
#! Record("CTBN:CP$(CP)2:1:ORDER_ON",80,378,0,1,"CTBN:CP$(CP)2:1:ORDER_ON")
#! Field("CTBN:CP$(CP)2:1:ORDER_ON.VAL",16777215,1,"CTBN:CP$(CP)2:1:ORDER_ON.VAL")
#! Record("CTBN:CP$(CP)2:1:ON_CNCL",80,798,0,1,"CTBN:CP$(CP)2:1:ON_CNCL")
#! Field("CTBN:CP$(CP)2:1:ON_CNCL.VAL",16777215,1,"CTBN:CP$(CP)2:1:ON_CNCL.VAL")
#! Record("CTBN:CP$(CP)2:1:ORDER_OFF",80,1018,0,1,"CTBN:CP$(CP)2:1:ORDER_OFF")
#! Field("CTBN:CP$(CP)2:1:ORDER_OFF.VAL",16777215,1,"CTBN:CP$(CP)2:1:ORDER_OFF.VAL")
#! Record("CTBN:CP$(CP)2:1:OFF_CNCL",80,1458,0,1,"CTBN:CP$(CP)2:1:OFF_CNCL")
#! Field("CTBN:CP$(CP)2:1:OFF_CNCL.VAL",16777215,1,"CTBN:CP$(CP)2:1:OFF_CNCL.VAL")
#! Record("CTBN:CP$(CP)2:1:ON_CFRM",80,578,0,1,"CTBN:CP$(CP)2:1:ON_CFRM")
#! Field("CTBN:CP$(CP)2:1:ON_CFRM.VAL",16777215,1,"CTBN:CP$(CP)2:1:ON_CFRM.VAL")
#! Record("CTBN:CP$(CP)2:1:OFF_CFRM",80,1238,0,1,"CTBN:CP$(CP)2:1:OFF_CFRM")
#! Field("CTBN:CP$(CP)2:1:OFF_CFRM.VAL",16777215,1,"CTBN:CP$(CP)2:1:OFF_CFRM.VAL")
#! Record("CTBN:CP$(CP)2:1:RQST_ON",960,584,0,1,"CTBN:CP$(CP)2:1:RQST_ON")
#! Field("CTBN:CP$(CP)2:1:RQST_ON.VAL",16777215,1,"CTBN:CP$(CP)2:1:RQST_ON.VAL")
#! Record("CTBN:CP$(CP)2:1:RQST_OFF",960,1204,0,1,"CTBN:CP$(CP)2:1:RQST_OFF")
#! Field("CTBN:CP$(CP)2:1:RQST_OFF.VAL",16777215,1,"CTBN:CP$(CP)2:1:RQST_OFF.VAL")
#! Record("CTBN:CP$(CP)2:1:ORDER_ONL",400,524,0,1,"CTBN:CP$(CP)2:1:ORDER_ONL")
#! Field("CTBN:CP$(CP)2:1:ORDER_ONL.FLNK",16777215,1,"CTBN:CP$(CP)2:1:ORDER_ONL.FLNK")
#! Link("CTBN:CP$(CP)2:1:ORDER_ONL.FLNK","CTBN:CP$(CP)2:1:ORDER_ONT")
#! Field("CTBN:CP$(CP)2:1:ORDER_ONL.INPA",16777215,0,"CTBN:CP$(CP)2:1:ORDER_ONL.INPA")
#! Link("CTBN:CP$(CP)2:1:ORDER_ONL.INPA","CTBN:CP$(CP)2:1:ORDER_ON.VAL")
#! Field("CTBN:CP$(CP)2:1:ORDER_ONL.INPB",16777215,0,"CTBN:CP$(CP)2:1:ORDER_ONL.INPB")
#! Link("CTBN:CP$(CP)2:1:ORDER_ONL.INPB","CTBN:CP$(CP)2:1:ON_CFRM.VAL")
#! Field("CTBN:CP$(CP)2:1:ORDER_ONL.INPC",16777215,0,"CTBN:CP$(CP)2:1:ORDER_ONL.INPC")
#! Link("CTBN:CP$(CP)2:1:ORDER_ONL.INPC","CTBN:CP$(CP)2:1:ON_CNCL.VAL")
#! Field("CTBN:CP$(CP)2:1:ORDER_ONL.VAL",16777215,1,"CTBN:CP$(CP)2:1:ORDER_ONL.VAL")
#! Record("CTBN:CP$(CP)2:1:ORDER_ONT",700,522,0,0,"CTBN:CP$(CP)2:1:ORDER_ONT")
#! Field("CTBN:CP$(CP)2:1:ORDER_ONT.DOL",16777215,0,"CTBN:CP$(CP)2:1:ORDER_ONT.DOL")
#! Link("CTBN:CP$(CP)2:1:ORDER_ONT.DOL","CTBN:CP$(CP)2:1:ORDER_ONL.VAL")
#! Field("CTBN:CP$(CP)2:1:ORDER_ONT.OUT",16777215,1,"CTBN:CP$(CP)2:1:ORDER_ONT.OUT")
#! Link("CTBN:CP$(CP)2:1:ORDER_ONT.OUT","CTBN:CP$(CP)2:1:RQST_ON.VAL")
#! Record("CTBN:CP$(CP)2:1:ORDER_OFFL",400,1124,0,1,"CTBN:CP$(CP)2:1:ORDER_OFFL")
#! Field("CTBN:CP$(CP)2:1:ORDER_OFFL.FLNK",16777215,1,"CTBN:CP$(CP)2:1:ORDER_OFFL.FLNK")
#! Link("CTBN:CP$(CP)2:1:ORDER_OFFL.FLNK","CTBN:CP$(CP)2:1:ORDER_OFFT")
#! Field("CTBN:CP$(CP)2:1:ORDER_OFFL.INPA",16777215,0,"CTBN:CP$(CP)2:1:ORDER_OFFL.INPA")
#! Link("CTBN:CP$(CP)2:1:ORDER_OFFL.INPA","CTBN:CP$(CP)2:1:ORDER_OFF.VAL")
#! Field("CTBN:CP$(CP)2:1:ORDER_OFFL.INPC",16777215,0,"CTBN:CP$(CP)2:1:ORDER_OFFL.INPC")
#! Link("CTBN:CP$(CP)2:1:ORDER_OFFL.INPC","CTBN:CP$(CP)2:1:OFF_CNCL.VAL")
#! Field("CTBN:CP$(CP)2:1:ORDER_OFFL.INPB",16777215,0,"CTBN:CP$(CP)2:1:ORDER_OFFL.INPB")
#! Link("CTBN:CP$(CP)2:1:ORDER_OFFL.INPB","CTBN:CP$(CP)2:1:OFF_CFRM.VAL")
#! Field("CTBN:CP$(CP)2:1:ORDER_OFFL.VAL",16777215,1,"CTBN:CP$(CP)2:1:ORDER_OFFL.VAL")
#! Record("CTBN:CP$(CP)2:1:ORDER_OFFT",700,1156,0,0,"CTBN:CP$(CP)2:1:ORDER_OFFT")
#! Field("CTBN:CP$(CP)2:1:ORDER_OFFT.DOL",16777215,0,"CTBN:CP$(CP)2:1:ORDER_OFFT.DOL")
#! Link("CTBN:CP$(CP)2:1:ORDER_OFFT.DOL","CTBN:CP$(CP)2:1:ORDER_OFFL.VAL")
#! Field("CTBN:CP$(CP)2:1:ORDER_OFFT.OUT",16777215,1,"CTBN:CP$(CP)2:1:ORDER_OFFT.OUT")
#! Link("CTBN:CP$(CP)2:1:ORDER_OFFT.OUT","CTBN:CP$(CP)2:1:RQST_OFF.VAL")
#! TextBox(TB1,480,360,780,400,0,"Dialog",12,1,16777215,"Turn On and confirm logic\nTurn Off and confirm logic\n",null)
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CTBN:CP$(CP)2:2:ORDER_ON") {
  field(DESC, "Turbine 2  order on")
  field(ZNAM, "not ordered on")
  field(ONAM, "ordered on")
  field(OMSL, "supervisory")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CTBN:CP$(CP)2:2:ON_CNCL") {
  field(DESC, "Turbine 2  Cancel ON order")
  field(ZNAM, "not cancelled")
  field(ONAM, "cancelled")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CTBN:CP$(CP)2:2:ORDER_OFF") {
  field(DESC, "Turbine 2  order off")
  field(ZNAM, "not order off")
  field(ONAM, "order off")
  field(OMSL, "supervisory")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CTBN:CP$(CP)2:2:OFF_CNCL") {
  field(DESC, "Turbine 2  Cancel OFF order")
  field(ZNAM, "not cancelled")
  field(ONAM, "cancelled")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CTBN:CP$(CP)2:2:ON_CFRM") {
  field(DESC, "Turbine 2  confirm ON order")
  field(ZNAM, "not confirmed")
  field(ONAM, "confirmed")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
  field(OMSL, "supervisory")
}

record(bo, "CTBN:CP$(CP)2:2:OFF_CFRM") {
  field(DESC, "Turbine 2  confirm OFF order")
  field(ZNAM, "not confirmed")
  field(ONAM, "confirmed")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CTBN:CP$(CP)2:2:RQST_ON") {
  field(DESC, "Turbine 2  Rqst On")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) Turbine_CMD B 5")
  field(ZNAM, "not active")
  field(ONAM, "Active")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(ASG, "NOWRITE")
  field(HIGH, "0")
  field(OMSL, "supervisory")
}

record(bo, "CTBN:CP$(CP)2:2:RQST_OFF") {
  field(DESC, "Turbine 2  Rqst Off")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) Turbine_CMD B 6")
  field(ZNAM, "not active")
  field(ONAM, "Active")
  field(ASG, "NOWRITE")
  field(PINI, "NO")
  field(HIGH, "0")
  field(SCAN, "1 second")
  field(OMSL, "supervisory")
}

record(sub, "CTBN:CP$(CP)2:2:ORDER_ONL") {
  field(DESC, "Turbine 2 ")
  field(SCAN, ".5 second")
  field(PINI, "NO")
  field(FLNK, "CTBN:CP$(CP)2:2:ORDER_ONT")
  field(INAM, "Icclmom")
  field(SNAM, "Scclmom")
  field(INPA, "CTBN:CP$(CP)2:2:ORDER_ON")
  field(INPB, "CTBN:CP$(CP)2:2:ON_CFRM")
  field(INPC, "CTBN:CP$(CP)2:2:ON_CNCL")
  field(ASG, "NOWRITE")
}

record(bo, "CTBN:CP$(CP)2:2:ORDER_ONT") {
  field(DESC, "Turbine 2 ")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "closed_loop")
  field(DOL, "CTBN:CP$(CP)2:2:ORDER_ONL")
  field(OUT, "CTBN:CP$(CP)2:2:RQST_ON")
  field(ZSV, "MAJOR")
  field(ASG, "NOWRITE")
  field(ZNAM, "disabled")
  field(ONAM, "enabled")
  field(OSV, "NO_ALARM")
  field(COSV, "NO_ALARM")
}

record(sub, "CTBN:CP$(CP)2:2:ORDER_OFFL") {
  field(DESC, "Turbine 2 ")
  field(SCAN, ".5 second")
  field(PINI, "NO")
  field(FLNK, "CTBN:CP$(CP)2:2:ORDER_OFFT")
  field(INAM, "Icclmom")
  field(SNAM, "Scclmom")
  field(INPA, "CTBN:CP$(CP)2:2:ORDER_OFF")
  field(INPB, "CTBN:CP$(CP)2:2:OFF_CFRM")
  field(INPC, "CTBN:CP$(CP)2:2:OFF_CNCL")
  field(ASG, "NOWRITE")
}

record(bo, "CTBN:CP$(CP)2:2:ORDER_OFFT") {
  field(DESC, "Turbine 2 ")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(OMSL, "closed_loop")
  field(DOL, "CTBN:CP$(CP)2:2:ORDER_OFFL")
  field(OUT, "CTBN:CP$(CP)2:2:RQST_OFF")
  field(ZSV, "MAJOR")
  field(ASG, "NOWRITE")
  field(ZNAM, "disabled")
  field(ONAM, "enabled")
  field(OSV, "NO_ALARM")
  field(COSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,416,1.1)
#! Record("CTBN:CP$(CP)2:2:ORDER_ON",80,378,0,1,"CTBN:CP$(CP)2:2:ORDER_ON")
#! Field("CTBN:CP$(CP)2:2:ORDER_ON.VAL",16777215,1,"CTBN:CP$(CP)2:2:ORDER_ON.VAL")
#! Record("CTBN:CP$(CP)2:2:ON_CNCL",80,798,0,1,"CTBN:CP$(CP)2:2:ON_CNCL")
#! Field("CTBN:CP$(CP)2:2:ON_CNCL.VAL",16777215,1,"CTBN:CP$(CP)2:2:ON_CNCL.VAL")
#! Record("CTBN:CP$(CP)2:2:ORDER_OFF",80,1018,0,1,"CTBN:CP$(CP)2:2:ORDER_OFF")
#! Field("CTBN:CP$(CP)2:2:ORDER_OFF.VAL",16777215,1,"CTBN:CP$(CP)2:2:ORDER_OFF.VAL")
#! Record("CTBN:CP$(CP)2:2:OFF_CNCL",80,1458,0,1,"CTBN:CP$(CP)2:2:OFF_CNCL")
#! Field("CTBN:CP$(CP)2:2:OFF_CNCL.VAL",16777215,1,"CTBN:CP$(CP)2:2:OFF_CNCL.VAL")
#! Record("CTBN:CP$(CP)2:2:ON_CFRM",80,578,0,1,"CTBN:CP$(CP)2:2:ON_CFRM")
#! Field("CTBN:CP$(CP)2:2:ON_CFRM.VAL",16777215,1,"CTBN:CP$(CP)2:2:ON_CFRM.VAL")
#! Record("CTBN:CP$(CP)2:2:OFF_CFRM",80,1238,0,1,"CTBN:CP$(CP)2:2:OFF_CFRM")
#! Field("CTBN:CP$(CP)2:2:OFF_CFRM.VAL",16777215,1,"CTBN:CP$(CP)2:2:OFF_CFRM.VAL")
#! Record("CTBN:CP$(CP)2:2:RQST_ON",960,584,0,1,"CTBN:CP$(CP)2:2:RQST_ON")
#! Field("CTBN:CP$(CP)2:2:RQST_ON.VAL",16777215,1,"CTBN:CP$(CP)2:2:RQST_ON.VAL")
#! Record("CTBN:CP$(CP)2:2:RQST_OFF",960,1204,0,1,"CTBN:CP$(CP)2:2:RQST_OFF")
#! Field("CTBN:CP$(CP)2:2:RQST_OFF.VAL",16777215,1,"CTBN:CP$(CP)2:2:RQST_OFF.VAL")
#! Record("CTBN:CP$(CP)2:2:ORDER_ONL",400,524,0,1,"CTBN:CP$(CP)2:2:ORDER_ONL")
#! Field("CTBN:CP$(CP)2:2:ORDER_ONL.FLNK",16777215,1,"CTBN:CP$(CP)2:2:ORDER_ONL.FLNK")
#! Link("CTBN:CP$(CP)2:2:ORDER_ONL.FLNK","CTBN:CP$(CP)2:2:ORDER_ONT")
#! Field("CTBN:CP$(CP)2:2:ORDER_ONL.INPA",16777215,0,"CTBN:CP$(CP)2:2:ORDER_ONL.INPA")
#! Link("CTBN:CP$(CP)2:2:ORDER_ONL.INPA","CTBN:CP$(CP)2:2:ORDER_ON.VAL")
#! Field("CTBN:CP$(CP)2:2:ORDER_ONL.INPB",16777215,0,"CTBN:CP$(CP)2:2:ORDER_ONL.INPB")
#! Link("CTBN:CP$(CP)2:2:ORDER_ONL.INPB","CTBN:CP$(CP)2:2:ON_CFRM.VAL")
#! Field("CTBN:CP$(CP)2:2:ORDER_ONL.INPC",16777215,0,"CTBN:CP$(CP)2:2:ORDER_ONL.INPC")
#! Link("CTBN:CP$(CP)2:2:ORDER_ONL.INPC","CTBN:CP$(CP)2:2:ON_CNCL.VAL")
#! Field("CTBN:CP$(CP)2:2:ORDER_ONL.VAL",16777215,1,"CTBN:CP$(CP)2:2:ORDER_ONL.VAL")
#! Record("CTBN:CP$(CP)2:2:ORDER_ONT",700,522,0,0,"CTBN:CP$(CP)2:2:ORDER_ONT")
#! Field("CTBN:CP$(CP)2:2:ORDER_ONT.DOL",16777215,0,"CTBN:CP$(CP)2:2:ORDER_ONT.DOL")
#! Link("CTBN:CP$(CP)2:2:ORDER_ONT.DOL","CTBN:CP$(CP)2:2:ORDER_ONL.VAL")
#! Field("CTBN:CP$(CP)2:2:ORDER_ONT.OUT",16777215,1,"CTBN:CP$(CP)2:2:ORDER_ONT.OUT")
#! Link("CTBN:CP$(CP)2:2:ORDER_ONT.OUT","CTBN:CP$(CP)2:2:RQST_ON.VAL")
#! Record("CTBN:CP$(CP)2:2:ORDER_OFFL",400,1124,0,1,"CTBN:CP$(CP)2:2:ORDER_OFFL")
#! Field("CTBN:CP$(CP)2:2:ORDER_OFFL.FLNK",16777215,1,"CTBN:CP$(CP)2:2:ORDER_OFFL.FLNK")
#! Link("CTBN:CP$(CP)2:2:ORDER_OFFL.FLNK","CTBN:CP$(CP)2:2:ORDER_OFFT")
#! Field("CTBN:CP$(CP)2:2:ORDER_OFFL.INPA",16777215,0,"CTBN:CP$(CP)2:2:ORDER_OFFL.INPA")
#! Link("CTBN:CP$(CP)2:2:ORDER_OFFL.INPA","CTBN:CP$(CP)2:2:ORDER_OFF.VAL")
#! Field("CTBN:CP$(CP)2:2:ORDER_OFFL.INPC",16777215,0,"CTBN:CP$(CP)2:2:ORDER_OFFL.INPC")
#! Link("CTBN:CP$(CP)2:2:ORDER_OFFL.INPC","CTBN:CP$(CP)2:2:OFF_CNCL.VAL")
#! Field("CTBN:CP$(CP)2:2:ORDER_OFFL.INPB",16777215,0,"CTBN:CP$(CP)2:2:ORDER_OFFL.INPB")
#! Link("CTBN:CP$(CP)2:2:ORDER_OFFL.INPB","CTBN:CP$(CP)2:2:OFF_CFRM.VAL")
#! Field("CTBN:CP$(CP)2:2:ORDER_OFFL.VAL",16777215,1,"CTBN:CP$(CP)2:2:ORDER_OFFL.VAL")
#! Record("CTBN:CP$(CP)2:2:ORDER_OFFT",700,1156,0,0,"CTBN:CP$(CP)2:2:ORDER_OFFT")
#! Field("CTBN:CP$(CP)2:2:ORDER_OFFT.DOL",16777215,0,"CTBN:CP$(CP)2:2:ORDER_OFFT.DOL")
#! Link("CTBN:CP$(CP)2:2:ORDER_OFFT.DOL","CTBN:CP$(CP)2:2:ORDER_OFFL.VAL")
#! Field("CTBN:CP$(CP)2:2:ORDER_OFFT.OUT",16777215,1,"CTBN:CP$(CP)2:2:ORDER_OFFT.OUT")
#! Link("CTBN:CP$(CP)2:2:ORDER_OFFT.OUT","CTBN:CP$(CP)2:2:RQST_OFF.VAL")
#! TextBox(TB1,480,360,780,400,0,"Dialog",12,1,16777215,"Turn On and confirm logic\nTurn Off and confirm logic\n",null)
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CTBN:CP$(CP)2:3:ORDER_ON") {
  field(DESC, "Turbine 3  order on")
  field(ZNAM, "not ordered on")
  field(ONAM, "ordered on")
  field(OMSL, "supervisory")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CTBN:CP$(CP)2:3:ON_CNCL") {
  field(DESC, "Turbine 3  Cancel ON order")
  field(ZNAM, "not cancelled")
  field(ONAM, "cancelled")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CTBN:CP$(CP)2:3:ORDER_OFF") {
  field(DESC, "Turbine 3  order off")
  field(ZNAM, "not order off")
  field(ONAM, "order off")
  field(OMSL, "supervisory")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CTBN:CP$(CP)2:3:OFF_CNCL") {
  field(DESC, "Turbine 3  Cancel OFF order")
  field(ZNAM, "not cancelled")
  field(ONAM, "cancelled")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CTBN:CP$(CP)2:3:ON_CFRM") {
  field(DESC, "Turbine 3  confirm ON order")
  field(ZNAM, "not confirmed")
  field(ONAM, "confirmed")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
  field(OMSL, "supervisory")
}

record(bo, "CTBN:CP$(CP)2:3:OFF_CFRM") {
  field(DESC, "Turbine 3  confirm OFF order")
  field(ZNAM, "not confirmed")
  field(ONAM, "confirmed")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CTBN:CP$(CP)2:3:RQST_ON") {
  field(DESC, "Turbine 3  Rqst On")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) Turbine_CMD B 9")
  field(ZNAM, "not active")
  field(ONAM, "Active")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(ASG, "NOWRITE")
  field(HIGH, "0")
  field(OMSL, "supervisory")
}

record(bo, "CTBN:CP$(CP)2:3:RQST_OFF") {
  field(DESC, "Turbine 3  Rqst Off")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) Turbine_CMD B 10")
  field(ZNAM, "not active")
  field(ONAM, "Active")
  field(ASG, "NOWRITE")
  field(PINI, "NO")
  field(HIGH, "0")
  field(SCAN, "1 second")
  field(OMSL, "supervisory")
}

record(sub, "CTBN:CP$(CP)2:3:ORDER_ONL") {
  field(DESC, "Turbine 3 ")
  field(SCAN, ".5 second")
  field(PINI, "NO")
  field(FLNK, "CTBN:CP$(CP)2:3:ORDER_ONT")
  field(INAM, "Icclmom")
  field(SNAM, "Scclmom")
  field(INPA, "CTBN:CP$(CP)2:3:ORDER_ON")
  field(INPB, "CTBN:CP$(CP)2:3:ON_CFRM")
  field(INPC, "CTBN:CP$(CP)2:3:ON_CNCL")
  field(ASG, "NOWRITE")
}

record(bo, "CTBN:CP$(CP)2:3:ORDER_ONT") {
  field(DESC, "Turbine 3 ")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "closed_loop")
  field(DOL, "CTBN:CP$(CP)2:3:ORDER_ONL")
  field(OUT, "CTBN:CP$(CP)2:3:RQST_ON")
  field(ZSV, "MAJOR")
  field(ASG, "NOWRITE")
  field(ZNAM, "disabled")
  field(ONAM, "enabled")
  field(OSV, "NO_ALARM")
  field(COSV, "NO_ALARM")
}

record(sub, "CTBN:CP$(CP)2:3:ORDER_OFFL") {
  field(DESC, "Turbine 3 ")
  field(SCAN, ".5 second")
  field(PINI, "NO")
  field(FLNK, "CTBN:CP$(CP)2:3:ORDER_OFFT")
  field(INAM, "Icclmom")
  field(SNAM, "Scclmom")
  field(INPA, "CTBN:CP$(CP)2:3:ORDER_OFF")
  field(INPB, "CTBN:CP$(CP)2:3:OFF_CFRM")
  field(INPC, "CTBN:CP$(CP)2:3:OFF_CNCL")
  field(ASG, "NOWRITE")
}

record(bo, "CTBN:CP$(CP)2:3:ORDER_OFFT") {
  field(DESC, "Turbine 3 ")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(OMSL, "closed_loop")
  field(DOL, "CTBN:CP$(CP)2:3:ORDER_OFFL")
  field(OUT, "CTBN:CP$(CP)2:3:RQST_OFF")
  field(ZSV, "MAJOR")
  field(ASG, "NOWRITE")
  field(ZNAM, "disabled")
  field(ONAM, "enabled")
  field(OSV, "NO_ALARM")
  field(COSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,416,1.1)
#! Record("CTBN:CP$(CP)2:3:ORDER_ON",80,378,0,1,"CTBN:CP$(CP)2:3:ORDER_ON")
#! Field("CTBN:CP$(CP)2:3:ORDER_ON.VAL",16777215,1,"CTBN:CP$(CP)2:3:ORDER_ON.VAL")
#! Record("CTBN:CP$(CP)2:3:ON_CNCL",80,798,0,1,"CTBN:CP$(CP)2:3:ON_CNCL")
#! Field("CTBN:CP$(CP)2:3:ON_CNCL.VAL",16777215,1,"CTBN:CP$(CP)2:3:ON_CNCL.VAL")
#! Record("CTBN:CP$(CP)2:3:ORDER_OFF",80,1018,0,1,"CTBN:CP$(CP)2:3:ORDER_OFF")
#! Field("CTBN:CP$(CP)2:3:ORDER_OFF.VAL",16777215,1,"CTBN:CP$(CP)2:3:ORDER_OFF.VAL")
#! Record("CTBN:CP$(CP)2:3:OFF_CNCL",80,1458,0,1,"CTBN:CP$(CP)2:3:OFF_CNCL")
#! Field("CTBN:CP$(CP)2:3:OFF_CNCL.VAL",16777215,1,"CTBN:CP$(CP)2:3:OFF_CNCL.VAL")
#! Record("CTBN:CP$(CP)2:3:ON_CFRM",80,578,0,1,"CTBN:CP$(CP)2:3:ON_CFRM")
#! Field("CTBN:CP$(CP)2:3:ON_CFRM.VAL",16777215,1,"CTBN:CP$(CP)2:3:ON_CFRM.VAL")
#! Record("CTBN:CP$(CP)2:3:OFF_CFRM",80,1238,0,1,"CTBN:CP$(CP)2:3:OFF_CFRM")
#! Field("CTBN:CP$(CP)2:3:OFF_CFRM.VAL",16777215,1,"CTBN:CP$(CP)2:3:OFF_CFRM.VAL")
#! Record("CTBN:CP$(CP)2:3:RQST_ON",960,584,0,1,"CTBN:CP$(CP)2:3:RQST_ON")
#! Field("CTBN:CP$(CP)2:3:RQST_ON.VAL",16777215,1,"CTBN:CP$(CP)2:3:RQST_ON.VAL")
#! Record("CTBN:CP$(CP)2:3:RQST_OFF",960,1204,0,1,"CTBN:CP$(CP)2:3:RQST_OFF")
#! Field("CTBN:CP$(CP)2:3:RQST_OFF.VAL",16777215,1,"CTBN:CP$(CP)2:3:RQST_OFF.VAL")
#! Record("CTBN:CP$(CP)2:3:ORDER_ONL",400,524,0,1,"CTBN:CP$(CP)2:3:ORDER_ONL")
#! Field("CTBN:CP$(CP)2:3:ORDER_ONL.FLNK",16777215,1,"CTBN:CP$(CP)2:3:ORDER_ONL.FLNK")
#! Link("CTBN:CP$(CP)2:3:ORDER_ONL.FLNK","CTBN:CP$(CP)2:3:ORDER_ONT")
#! Field("CTBN:CP$(CP)2:3:ORDER_ONL.INPA",16777215,0,"CTBN:CP$(CP)2:3:ORDER_ONL.INPA")
#! Link("CTBN:CP$(CP)2:3:ORDER_ONL.INPA","CTBN:CP$(CP)2:3:ORDER_ON.VAL")
#! Field("CTBN:CP$(CP)2:3:ORDER_ONL.INPB",16777215,0,"CTBN:CP$(CP)2:3:ORDER_ONL.INPB")
#! Link("CTBN:CP$(CP)2:3:ORDER_ONL.INPB","CTBN:CP$(CP)2:3:ON_CFRM.VAL")
#! Field("CTBN:CP$(CP)2:3:ORDER_ONL.INPC",16777215,0,"CTBN:CP$(CP)2:3:ORDER_ONL.INPC")
#! Link("CTBN:CP$(CP)2:3:ORDER_ONL.INPC","CTBN:CP$(CP)2:3:ON_CNCL.VAL")
#! Field("CTBN:CP$(CP)2:3:ORDER_ONL.VAL",16777215,1,"CTBN:CP$(CP)2:3:ORDER_ONL.VAL")
#! Record("CTBN:CP$(CP)2:3:ORDER_ONT",700,522,0,0,"CTBN:CP$(CP)2:3:ORDER_ONT")
#! Field("CTBN:CP$(CP)2:3:ORDER_ONT.DOL",16777215,0,"CTBN:CP$(CP)2:3:ORDER_ONT.DOL")
#! Link("CTBN:CP$(CP)2:3:ORDER_ONT.DOL","CTBN:CP$(CP)2:3:ORDER_ONL.VAL")
#! Field("CTBN:CP$(CP)2:3:ORDER_ONT.OUT",16777215,1,"CTBN:CP$(CP)2:3:ORDER_ONT.OUT")
#! Link("CTBN:CP$(CP)2:3:ORDER_ONT.OUT","CTBN:CP$(CP)2:3:RQST_ON.VAL")
#! Record("CTBN:CP$(CP)2:3:ORDER_OFFL",400,1124,0,1,"CTBN:CP$(CP)2:3:ORDER_OFFL")
#! Field("CTBN:CP$(CP)2:3:ORDER_OFFL.FLNK",16777215,1,"CTBN:CP$(CP)2:3:ORDER_OFFL.FLNK")
#! Link("CTBN:CP$(CP)2:3:ORDER_OFFL.FLNK","CTBN:CP$(CP)2:3:ORDER_OFFT")
#! Field("CTBN:CP$(CP)2:3:ORDER_OFFL.INPA",16777215,0,"CTBN:CP$(CP)2:3:ORDER_OFFL.INPA")
#! Link("CTBN:CP$(CP)2:3:ORDER_OFFL.INPA","CTBN:CP$(CP)2:3:ORDER_OFF.VAL")
#! Field("CTBN:CP$(CP)2:3:ORDER_OFFL.INPC",16777215,0,"CTBN:CP$(CP)2:3:ORDER_OFFL.INPC")
#! Link("CTBN:CP$(CP)2:3:ORDER_OFFL.INPC","CTBN:CP$(CP)2:3:OFF_CNCL.VAL")
#! Field("CTBN:CP$(CP)2:3:ORDER_OFFL.INPB",16777215,0,"CTBN:CP$(CP)2:3:ORDER_OFFL.INPB")
#! Link("CTBN:CP$(CP)2:3:ORDER_OFFL.INPB","CTBN:CP$(CP)2:3:OFF_CFRM.VAL")
#! Field("CTBN:CP$(CP)2:3:ORDER_OFFL.VAL",16777215,1,"CTBN:CP$(CP)2:3:ORDER_OFFL.VAL")
#! Record("CTBN:CP$(CP)2:3:ORDER_OFFT",700,1156,0,0,"CTBN:CP$(CP)2:3:ORDER_OFFT")
#! Field("CTBN:CP$(CP)2:3:ORDER_OFFT.DOL",16777215,0,"CTBN:CP$(CP)2:3:ORDER_OFFT.DOL")
#! Link("CTBN:CP$(CP)2:3:ORDER_OFFT.DOL","CTBN:CP$(CP)2:3:ORDER_OFFL.VAL")
#! Field("CTBN:CP$(CP)2:3:ORDER_OFFT.OUT",16777215,1,"CTBN:CP$(CP)2:3:ORDER_OFFT.OUT")
#! Link("CTBN:CP$(CP)2:3:ORDER_OFFT.OUT","CTBN:CP$(CP)2:3:RQST_OFF.VAL")
#! TextBox(TB1,480,360,780,400,0,"Dialog",12,1,16777215,"Turn On and confirm logic\nTurn Off and confirm logic\n",null)
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CTBN:CP$(CP)2:4:ORDER_ON") {
  field(DESC, "Turbine 4  order on")
  field(ZNAM, "not ordered on")
  field(ONAM, "ordered on")
  field(OMSL, "supervisory")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CTBN:CP$(CP)2:4:ON_CNCL") {
  field(DESC, "Turbine 4  Cancel ON order")
  field(ZNAM, "not cancelled")
  field(ONAM, "cancelled")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CTBN:CP$(CP)2:4:ORDER_OFF") {
  field(DESC, "Turbine 4  order off")
  field(ZNAM, "not order off")
  field(ONAM, "order off")
  field(OMSL, "supervisory")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CTBN:CP$(CP)2:4:OFF_CNCL") {
  field(DESC, "Turbine 4  Cancel OFF order")
  field(ZNAM, "not cancelled")
  field(ONAM, "cancelled")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CTBN:CP$(CP)2:4:ON_CFRM") {
  field(DESC, "Turbine 4  confirm ON order")
  field(ZNAM, "not confirmed")
  field(ONAM, "confirmed")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
  field(OMSL, "supervisory")
}

record(bo, "CTBN:CP$(CP)2:4:OFF_CFRM") {
  field(DESC, "Turbine 4  confirm OFF order")
  field(ZNAM, "not confirmed")
  field(ONAM, "confirmed")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CTBN:CP$(CP)2:4:RQST_ON") {
  field(DESC, "Turbine 4  Rqst On")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) Turbine_CMD B 13")
  field(ZNAM, "not active")
  field(ONAM, "Active")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(ASG, "NOWRITE")
  field(HIGH, "0")
  field(OMSL, "supervisory")
}

record(bo, "CTBN:CP$(CP)2:4:RQST_OFF") {
  field(DESC, "Turbine 4  Rqst Off")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) Turbine_CMD B 14")
  field(ZNAM, "not active")
  field(ONAM, "Active")
  field(ASG, "NOWRITE")
  field(PINI, "NO")
  field(HIGH, "0")
  field(SCAN, "1 second")
  field(OMSL, "supervisory")
}

record(sub, "CTBN:CP$(CP)2:4:ORDER_ONL") {
  field(DESC, "Turbine 4 ")
  field(SCAN, ".5 second")
  field(PINI, "NO")
  field(FLNK, "CTBN:CP$(CP)2:4:ORDER_ONT")
  field(INAM, "Icclmom")
  field(SNAM, "Scclmom")
  field(INPA, "CTBN:CP$(CP)2:4:ORDER_ON")
  field(INPB, "CTBN:CP$(CP)2:4:ON_CFRM")
  field(INPC, "CTBN:CP$(CP)2:4:ON_CNCL")
  field(ASG, "NOWRITE")
}

record(bo, "CTBN:CP$(CP)2:4:ORDER_ONT") {
  field(DESC, "Turbine 4 ")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "closed_loop")
  field(DOL, "CTBN:CP$(CP)2:4:ORDER_ONL")
  field(OUT, "CTBN:CP$(CP)2:4:RQST_ON")
  field(ZSV, "MAJOR")
  field(ASG, "NOWRITE")
  field(ZNAM, "disabled")
  field(ONAM, "enabled")
  field(OSV, "NO_ALARM")
  field(COSV, "NO_ALARM")
}

record(sub, "CTBN:CP$(CP)2:4:ORDER_OFFL") {
  field(DESC, "Turbine 4 ")
  field(SCAN, ".5 second")
  field(PINI, "NO")
  field(FLNK, "CTBN:CP$(CP)2:4:ORDER_OFFT")
  field(INAM, "Icclmom")
  field(SNAM, "Scclmom")
  field(INPA, "CTBN:CP$(CP)2:4:ORDER_OFF")
  field(INPB, "CTBN:CP$(CP)2:4:OFF_CFRM")
  field(INPC, "CTBN:CP$(CP)2:4:OFF_CNCL")
  field(ASG, "NOWRITE")
}

record(bo, "CTBN:CP$(CP)2:4:ORDER_OFFT") {
  field(DESC, "Turbine 4 ")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(OMSL, "closed_loop")
  field(DOL, "CTBN:CP$(CP)2:4:ORDER_OFFL")
  field(OUT, "CTBN:CP$(CP)2:4:RQST_OFF")
  field(ZSV, "MAJOR")
  field(ASG, "NOWRITE")
  field(ZNAM, "disabled")
  field(ONAM, "enabled")
  field(OSV, "NO_ALARM")
  field(COSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,416,1.1)
#! Record("CTBN:CP$(CP)2:4:ORDER_ON",80,378,0,1,"CTBN:CP$(CP)2:4:ORDER_ON")
#! Field("CTBN:CP$(CP)2:4:ORDER_ON.VAL",16777215,1,"CTBN:CP$(CP)2:4:ORDER_ON.VAL")
#! Record("CTBN:CP$(CP)2:4:ON_CNCL",80,798,0,1,"CTBN:CP$(CP)2:4:ON_CNCL")
#! Field("CTBN:CP$(CP)2:4:ON_CNCL.VAL",16777215,1,"CTBN:CP$(CP)2:4:ON_CNCL.VAL")
#! Record("CTBN:CP$(CP)2:4:ORDER_OFF",80,1018,0,1,"CTBN:CP$(CP)2:4:ORDER_OFF")
#! Field("CTBN:CP$(CP)2:4:ORDER_OFF.VAL",16777215,1,"CTBN:CP$(CP)2:4:ORDER_OFF.VAL")
#! Record("CTBN:CP$(CP)2:4:OFF_CNCL",80,1458,0,1,"CTBN:CP$(CP)2:4:OFF_CNCL")
#! Field("CTBN:CP$(CP)2:4:OFF_CNCL.VAL",16777215,1,"CTBN:CP$(CP)2:4:OFF_CNCL.VAL")
#! Record("CTBN:CP$(CP)2:4:ON_CFRM",80,578,0,1,"CTBN:CP$(CP)2:4:ON_CFRM")
#! Field("CTBN:CP$(CP)2:4:ON_CFRM.VAL",16777215,1,"CTBN:CP$(CP)2:4:ON_CFRM.VAL")
#! Record("CTBN:CP$(CP)2:4:OFF_CFRM",80,1238,0,1,"CTBN:CP$(CP)2:4:OFF_CFRM")
#! Field("CTBN:CP$(CP)2:4:OFF_CFRM.VAL",16777215,1,"CTBN:CP$(CP)2:4:OFF_CFRM.VAL")
#! Record("CTBN:CP$(CP)2:4:RQST_ON",960,584,0,1,"CTBN:CP$(CP)2:4:RQST_ON")
#! Field("CTBN:CP$(CP)2:4:RQST_ON.VAL",16777215,1,"CTBN:CP$(CP)2:4:RQST_ON.VAL")
#! Record("CTBN:CP$(CP)2:4:RQST_OFF",960,1204,0,1,"CTBN:CP$(CP)2:4:RQST_OFF")
#! Field("CTBN:CP$(CP)2:4:RQST_OFF.VAL",16777215,1,"CTBN:CP$(CP)2:4:RQST_OFF.VAL")
#! Record("CTBN:CP$(CP)2:4:ORDER_ONL",400,524,0,1,"CTBN:CP$(CP)2:4:ORDER_ONL")
#! Field("CTBN:CP$(CP)2:4:ORDER_ONL.FLNK",16777215,1,"CTBN:CP$(CP)2:4:ORDER_ONL.FLNK")
#! Link("CTBN:CP$(CP)2:4:ORDER_ONL.FLNK","CTBN:CP$(CP)2:4:ORDER_ONT")
#! Field("CTBN:CP$(CP)2:4:ORDER_ONL.INPA",16777215,0,"CTBN:CP$(CP)2:4:ORDER_ONL.INPA")
#! Link("CTBN:CP$(CP)2:4:ORDER_ONL.INPA","CTBN:CP$(CP)2:4:ORDER_ON.VAL")
#! Field("CTBN:CP$(CP)2:4:ORDER_ONL.INPB",16777215,0,"CTBN:CP$(CP)2:4:ORDER_ONL.INPB")
#! Link("CTBN:CP$(CP)2:4:ORDER_ONL.INPB","CTBN:CP$(CP)2:4:ON_CFRM.VAL")
#! Field("CTBN:CP$(CP)2:4:ORDER_ONL.INPC",16777215,0,"CTBN:CP$(CP)2:4:ORDER_ONL.INPC")
#! Link("CTBN:CP$(CP)2:4:ORDER_ONL.INPC","CTBN:CP$(CP)2:4:ON_CNCL.VAL")
#! Field("CTBN:CP$(CP)2:4:ORDER_ONL.VAL",16777215,1,"CTBN:CP$(CP)2:4:ORDER_ONL.VAL")
#! Record("CTBN:CP$(CP)2:4:ORDER_ONT",700,522,0,0,"CTBN:CP$(CP)2:4:ORDER_ONT")
#! Field("CTBN:CP$(CP)2:4:ORDER_ONT.DOL",16777215,0,"CTBN:CP$(CP)2:4:ORDER_ONT.DOL")
#! Link("CTBN:CP$(CP)2:4:ORDER_ONT.DOL","CTBN:CP$(CP)2:4:ORDER_ONL.VAL")
#! Field("CTBN:CP$(CP)2:4:ORDER_ONT.OUT",16777215,1,"CTBN:CP$(CP)2:4:ORDER_ONT.OUT")
#! Link("CTBN:CP$(CP)2:4:ORDER_ONT.OUT","CTBN:CP$(CP)2:4:RQST_ON.VAL")
#! Record("CTBN:CP$(CP)2:4:ORDER_OFFL",400,1124,0,1,"CTBN:CP$(CP)2:4:ORDER_OFFL")
#! Field("CTBN:CP$(CP)2:4:ORDER_OFFL.FLNK",16777215,1,"CTBN:CP$(CP)2:4:ORDER_OFFL.FLNK")
#! Link("CTBN:CP$(CP)2:4:ORDER_OFFL.FLNK","CTBN:CP$(CP)2:4:ORDER_OFFT")
#! Field("CTBN:CP$(CP)2:4:ORDER_OFFL.INPA",16777215,0,"CTBN:CP$(CP)2:4:ORDER_OFFL.INPA")
#! Link("CTBN:CP$(CP)2:4:ORDER_OFFL.INPA","CTBN:CP$(CP)2:4:ORDER_OFF.VAL")
#! Field("CTBN:CP$(CP)2:4:ORDER_OFFL.INPC",16777215,0,"CTBN:CP$(CP)2:4:ORDER_OFFL.INPC")
#! Link("CTBN:CP$(CP)2:4:ORDER_OFFL.INPC","CTBN:CP$(CP)2:4:OFF_CNCL.VAL")
#! Field("CTBN:CP$(CP)2:4:ORDER_OFFL.INPB",16777215,0,"CTBN:CP$(CP)2:4:ORDER_OFFL.INPB")
#! Link("CTBN:CP$(CP)2:4:ORDER_OFFL.INPB","CTBN:CP$(CP)2:4:OFF_CFRM.VAL")
#! Field("CTBN:CP$(CP)2:4:ORDER_OFFL.VAL",16777215,1,"CTBN:CP$(CP)2:4:ORDER_OFFL.VAL")
#! Record("CTBN:CP$(CP)2:4:ORDER_OFFT",700,1156,0,0,"CTBN:CP$(CP)2:4:ORDER_OFFT")
#! Field("CTBN:CP$(CP)2:4:ORDER_OFFT.DOL",16777215,0,"CTBN:CP$(CP)2:4:ORDER_OFFT.DOL")
#! Link("CTBN:CP$(CP)2:4:ORDER_OFFT.DOL","CTBN:CP$(CP)2:4:ORDER_OFFL.VAL")
#! Field("CTBN:CP$(CP)2:4:ORDER_OFFT.OUT",16777215,1,"CTBN:CP$(CP)2:4:ORDER_OFFT.OUT")
#! Link("CTBN:CP$(CP)2:4:ORDER_OFFT.OUT","CTBN:CP$(CP)2:4:RQST_OFF.VAL")
#! TextBox(TB1,480,360,780,400,0,"Dialog",12,1,16777215,"Turn On and confirm logic\nTurn Off and confirm logic\n",null)
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CCLD:CP$(CP)2:0:ORDER_ON") {
  field(DESC, "Cooldown sequence  order on")
  field(ZNAM, "not ordered on")
  field(ONAM, "ordered on")
  field(OMSL, "supervisory")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CCLD:CP$(CP)2:0:ON_CNCL") {
  field(DESC, "Cooldown sequence  Cancel ON order")
  field(ZNAM, "not cancelled")
  field(ONAM, "cancelled")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CCLD:CP$(CP)2:0:ORDER_OFF") {
  field(DESC, "Cooldown sequence  order off")
  field(ZNAM, "not order off")
  field(ONAM, "order off")
  field(OMSL, "supervisory")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CCLD:CP$(CP)2:0:OFF_CNCL") {
  field(DESC, "Cooldown sequence  Cancel OFF order")
  field(ZNAM, "not cancelled")
  field(ONAM, "cancelled")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CCLD:CP$(CP)2:0:ON_CFRM") {
  field(DESC, "Cooldown sequence  confirm ON order")
  field(ZNAM, "not confirmed")
  field(ONAM, "confirmed")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
  field(OMSL, "supervisory")
}

record(bo, "CCLD:CP$(CP)2:0:OFF_CFRM") {
  field(DESC, "Cooldown sequence  confirm OFF order")
  field(ZNAM, "not confirmed")
  field(ONAM, "confirmed")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CCLD:CP$(CP)2:0:RQST_ON") {
  field(DESC, "Cooldown sequence  Rqst On")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) CBX_CMD B 1")
  field(ZNAM, "not active")
  field(ONAM, "Active")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(ASG, "NOWRITE")
  field(HIGH, "0")
  field(OMSL, "supervisory")
}

record(bo, "CCLD:CP$(CP)2:0:RQST_OFF") {
  field(DESC, "Cooldown sequence  Rqst Off")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) CBX_CMD B 2")
  field(ZNAM, "not active")
  field(ONAM, "Active")
  field(ASG, "NOWRITE")
  field(PINI, "NO")
  field(HIGH, "0")
  field(SCAN, "1 second")
  field(OMSL, "supervisory")
}

record(sub, "CCLD:CP$(CP)2:0:ORDER_ONL") {
  field(DESC, "Cooldown sequence ")
  field(SCAN, ".5 second")
  field(PINI, "NO")
  field(FLNK, "CCLD:CP$(CP)2:0:ORDER_ONT")
  field(INAM, "Icclmom")
  field(SNAM, "Scclmom")
  field(INPA, "CCLD:CP$(CP)2:0:ORDER_ON")
  field(INPB, "CCLD:CP$(CP)2:0:ON_CFRM")
  field(INPC, "CCLD:CP$(CP)2:0:ON_CNCL")
  field(ASG, "NOWRITE")
}

record(bo, "CCLD:CP$(CP)2:0:ORDER_ONT") {
  field(DESC, "Cooldown sequence ")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "closed_loop")
  field(DOL, "CCLD:CP$(CP)2:0:ORDER_ONL")
  field(OUT, "CCLD:CP$(CP)2:0:RQST_ON")
  field(ZSV, "MAJOR")
  field(ASG, "NOWRITE")
  field(ZNAM, "disabled")
  field(ONAM, "enabled")
  field(OSV, "NO_ALARM")
  field(COSV, "NO_ALARM")
}

record(sub, "CCLD:CP$(CP)2:0:ORDER_OFFL") {
  field(DESC, "Cooldown sequence ")
  field(SCAN, ".5 second")
  field(PINI, "NO")
  field(FLNK, "CCLD:CP$(CP)2:0:ORDER_OFFT")
  field(INAM, "Icclmom")
  field(SNAM, "Scclmom")
  field(INPA, "CCLD:CP$(CP)2:0:ORDER_OFF")
  field(INPB, "CCLD:CP$(CP)2:0:OFF_CFRM")
  field(INPC, "CCLD:CP$(CP)2:0:OFF_CNCL")
  field(ASG, "NOWRITE")
}

record(bo, "CCLD:CP$(CP)2:0:ORDER_OFFT") {
  field(DESC, "Cooldown sequence ")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(OMSL, "closed_loop")
  field(DOL, "CCLD:CP$(CP)2:0:ORDER_OFFL")
  field(OUT, "CCLD:CP$(CP)2:0:RQST_OFF")
  field(ZSV, "MAJOR")
  field(ASG, "NOWRITE")
  field(ZNAM, "disabled")
  field(ONAM, "enabled")
  field(OSV, "NO_ALARM")
  field(COSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,416,1.1)
#! Record("CCLD:CP$(CP)2:0:ORDER_ON",80,378,0,1,"CCLD:CP$(CP)2:0:ORDER_ON")
#! Field("CCLD:CP$(CP)2:0:ORDER_ON.VAL",16777215,1,"CCLD:CP$(CP)2:0:ORDER_ON.VAL")
#! Record("CCLD:CP$(CP)2:0:ON_CNCL",80,798,0,1,"CCLD:CP$(CP)2:0:ON_CNCL")
#! Field("CCLD:CP$(CP)2:0:ON_CNCL.VAL",16777215,1,"CCLD:CP$(CP)2:0:ON_CNCL.VAL")
#! Record("CCLD:CP$(CP)2:0:ORDER_OFF",80,1018,0,1,"CCLD:CP$(CP)2:0:ORDER_OFF")
#! Field("CCLD:CP$(CP)2:0:ORDER_OFF.VAL",16777215,1,"CCLD:CP$(CP)2:0:ORDER_OFF.VAL")
#! Record("CCLD:CP$(CP)2:0:OFF_CNCL",80,1458,0,1,"CCLD:CP$(CP)2:0:OFF_CNCL")
#! Field("CCLD:CP$(CP)2:0:OFF_CNCL.VAL",16777215,1,"CCLD:CP$(CP)2:0:OFF_CNCL.VAL")
#! Record("CCLD:CP$(CP)2:0:ON_CFRM",80,578,0,1,"CCLD:CP$(CP)2:0:ON_CFRM")
#! Field("CCLD:CP$(CP)2:0:ON_CFRM.VAL",16777215,1,"CCLD:CP$(CP)2:0:ON_CFRM.VAL")
#! Record("CCLD:CP$(CP)2:0:OFF_CFRM",80,1238,0,1,"CCLD:CP$(CP)2:0:OFF_CFRM")
#! Field("CCLD:CP$(CP)2:0:OFF_CFRM.VAL",16777215,1,"CCLD:CP$(CP)2:0:OFF_CFRM.VAL")
#! Record("CCLD:CP$(CP)2:0:RQST_ON",960,584,0,1,"CCLD:CP$(CP)2:0:RQST_ON")
#! Field("CCLD:CP$(CP)2:0:RQST_ON.VAL",16777215,1,"CCLD:CP$(CP)2:0:RQST_ON.VAL")
#! Record("CCLD:CP$(CP)2:0:RQST_OFF",960,1204,0,1,"CCLD:CP$(CP)2:0:RQST_OFF")
#! Field("CCLD:CP$(CP)2:0:RQST_OFF.VAL",16777215,1,"CCLD:CP$(CP)2:0:RQST_OFF.VAL")
#! Record("CCLD:CP$(CP)2:0:ORDER_ONL",400,524,0,1,"CCLD:CP$(CP)2:0:ORDER_ONL")
#! Field("CCLD:CP$(CP)2:0:ORDER_ONL.FLNK",16777215,1,"CCLD:CP$(CP)2:0:ORDER_ONL.FLNK")
#! Link("CCLD:CP$(CP)2:0:ORDER_ONL.FLNK","CCLD:CP$(CP)2:0:ORDER_ONT")
#! Field("CCLD:CP$(CP)2:0:ORDER_ONL.INPA",16777215,0,"CCLD:CP$(CP)2:0:ORDER_ONL.INPA")
#! Link("CCLD:CP$(CP)2:0:ORDER_ONL.INPA","CCLD:CP$(CP)2:0:ORDER_ON.VAL")
#! Field("CCLD:CP$(CP)2:0:ORDER_ONL.INPB",16777215,0,"CCLD:CP$(CP)2:0:ORDER_ONL.INPB")
#! Link("CCLD:CP$(CP)2:0:ORDER_ONL.INPB","CCLD:CP$(CP)2:0:ON_CFRM.VAL")
#! Field("CCLD:CP$(CP)2:0:ORDER_ONL.INPC",16777215,0,"CCLD:CP$(CP)2:0:ORDER_ONL.INPC")
#! Link("CCLD:CP$(CP)2:0:ORDER_ONL.INPC","CCLD:CP$(CP)2:0:ON_CNCL.VAL")
#! Field("CCLD:CP$(CP)2:0:ORDER_ONL.VAL",16777215,1,"CCLD:CP$(CP)2:0:ORDER_ONL.VAL")
#! Record("CCLD:CP$(CP)2:0:ORDER_ONT",700,522,0,0,"CCLD:CP$(CP)2:0:ORDER_ONT")
#! Field("CCLD:CP$(CP)2:0:ORDER_ONT.DOL",16777215,0,"CCLD:CP$(CP)2:0:ORDER_ONT.DOL")
#! Link("CCLD:CP$(CP)2:0:ORDER_ONT.DOL","CCLD:CP$(CP)2:0:ORDER_ONL.VAL")
#! Field("CCLD:CP$(CP)2:0:ORDER_ONT.OUT",16777215,1,"CCLD:CP$(CP)2:0:ORDER_ONT.OUT")
#! Link("CCLD:CP$(CP)2:0:ORDER_ONT.OUT","CCLD:CP$(CP)2:0:RQST_ON.VAL")
#! Record("CCLD:CP$(CP)2:0:ORDER_OFFL",400,1124,0,1,"CCLD:CP$(CP)2:0:ORDER_OFFL")
#! Field("CCLD:CP$(CP)2:0:ORDER_OFFL.FLNK",16777215,1,"CCLD:CP$(CP)2:0:ORDER_OFFL.FLNK")
#! Link("CCLD:CP$(CP)2:0:ORDER_OFFL.FLNK","CCLD:CP$(CP)2:0:ORDER_OFFT")
#! Field("CCLD:CP$(CP)2:0:ORDER_OFFL.INPA",16777215,0,"CCLD:CP$(CP)2:0:ORDER_OFFL.INPA")
#! Link("CCLD:CP$(CP)2:0:ORDER_OFFL.INPA","CCLD:CP$(CP)2:0:ORDER_OFF.VAL")
#! Field("CCLD:CP$(CP)2:0:ORDER_OFFL.INPC",16777215,0,"CCLD:CP$(CP)2:0:ORDER_OFFL.INPC")
#! Link("CCLD:CP$(CP)2:0:ORDER_OFFL.INPC","CCLD:CP$(CP)2:0:OFF_CNCL.VAL")
#! Field("CCLD:CP$(CP)2:0:ORDER_OFFL.INPB",16777215,0,"CCLD:CP$(CP)2:0:ORDER_OFFL.INPB")
#! Link("CCLD:CP$(CP)2:0:ORDER_OFFL.INPB","CCLD:CP$(CP)2:0:OFF_CFRM.VAL")
#! Field("CCLD:CP$(CP)2:0:ORDER_OFFL.VAL",16777215,1,"CCLD:CP$(CP)2:0:ORDER_OFFL.VAL")
#! Record("CCLD:CP$(CP)2:0:ORDER_OFFT",700,1156,0,0,"CCLD:CP$(CP)2:0:ORDER_OFFT")
#! Field("CCLD:CP$(CP)2:0:ORDER_OFFT.DOL",16777215,0,"CCLD:CP$(CP)2:0:ORDER_OFFT.DOL")
#! Link("CCLD:CP$(CP)2:0:ORDER_OFFT.DOL","CCLD:CP$(CP)2:0:ORDER_OFFL.VAL")
#! Field("CCLD:CP$(CP)2:0:ORDER_OFFT.OUT",16777215,1,"CCLD:CP$(CP)2:0:ORDER_OFFT.OUT")
#! Link("CCLD:CP$(CP)2:0:ORDER_OFFT.OUT","CCLD:CP$(CP)2:0:RQST_OFF.VAL")
#! TextBox(TB1,480,360,780,400,0,"Dialog",12,1,16777215,"Turn On and confirm logic\nTurn Off and confirm logic\n",null)
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CWSH:CP$(CP)2:0:ORDER_ON") {
  field(DESC, "warm shield sequence  order on")
  field(ZNAM, "not ordered on")
  field(ONAM, "ordered on")
  field(OMSL, "supervisory")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CWSH:CP$(CP)2:0:ON_CNCL") {
  field(DESC, "warm shield sequence  Cancel ON order")
  field(ZNAM, "not cancelled")
  field(ONAM, "cancelled")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CWSH:CP$(CP)2:0:ORDER_OFF") {
  field(DESC, "warm shield sequence  order off")
  field(ZNAM, "not order off")
  field(ONAM, "order off")
  field(OMSL, "supervisory")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CWSH:CP$(CP)2:0:OFF_CNCL") {
  field(DESC, "warm shield sequence  Cancel OFF order")
  field(ZNAM, "not cancelled")
  field(ONAM, "cancelled")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CWSH:CP$(CP)2:0:ON_CFRM") {
  field(DESC, "warm shield sequence  confirm ON order")
  field(ZNAM, "not confirmed")
  field(ONAM, "confirmed")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
  field(OMSL, "supervisory")
}

record(bo, "CWSH:CP$(CP)2:0:OFF_CFRM") {
  field(DESC, "warm shield sequence  confirm OFF order")
  field(ZNAM, "not confirmed")
  field(ONAM, "confirmed")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CWSH:CP$(CP)2:0:RQST_ON") {
  field(DESC, "warm shield sequence  Rqst On")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) CBX_CMD B 5")
  field(ZNAM, "not active")
  field(ONAM, "Active")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(ASG, "NOWRITE")
  field(HIGH, "0")
  field(OMSL, "supervisory")
}

record(bo, "CWSH:CP$(CP)2:0:RQST_OFF") {
  field(DESC, "warm shield sequence  Rqst Off")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) CBX_CMD B 6")
  field(ZNAM, "not active")
  field(ONAM, "Active")
  field(ASG, "NOWRITE")
  field(PINI, "NO")
  field(HIGH, "0")
  field(SCAN, "1 second")
  field(OMSL, "supervisory")
}

record(sub, "CWSH:CP$(CP)2:0:ORDER_ONL") {
  field(DESC, "warm shield sequence ")
  field(SCAN, ".5 second")
  field(PINI, "NO")
  field(FLNK, "CWSH:CP$(CP)2:0:ORDER_ONT")
  field(INAM, "Icclmom")
  field(SNAM, "Scclmom")
  field(INPA, "CWSH:CP$(CP)2:0:ORDER_ON")
  field(INPB, "CWSH:CP$(CP)2:0:ON_CFRM")
  field(INPC, "CWSH:CP$(CP)2:0:ON_CNCL")
  field(ASG, "NOWRITE")
}

record(bo, "CWSH:CP$(CP)2:0:ORDER_ONT") {
  field(DESC, "warm shield sequence ")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "closed_loop")
  field(DOL, "CWSH:CP$(CP)2:0:ORDER_ONL")
  field(OUT, "CWSH:CP$(CP)2:0:RQST_ON")
  field(ZSV, "MAJOR")
  field(ASG, "NOWRITE")
  field(ZNAM, "disabled")
  field(ONAM, "enabled")
  field(OSV, "NO_ALARM")
  field(COSV, "NO_ALARM")
}

record(sub, "CWSH:CP$(CP)2:0:ORDER_OFFL") {
  field(DESC, "warm shield sequence ")
  field(SCAN, ".5 second")
  field(PINI, "NO")
  field(FLNK, "CWSH:CP$(CP)2:0:ORDER_OFFT")
  field(INAM, "Icclmom")
  field(SNAM, "Scclmom")
  field(INPA, "CWSH:CP$(CP)2:0:ORDER_OFF")
  field(INPB, "CWSH:CP$(CP)2:0:OFF_CFRM")
  field(INPC, "CWSH:CP$(CP)2:0:OFF_CNCL")
  field(ASG, "NOWRITE")
}

record(bo, "CWSH:CP$(CP)2:0:ORDER_OFFT") {
  field(DESC, "warm shield sequence ")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(OMSL, "closed_loop")
  field(DOL, "CWSH:CP$(CP)2:0:ORDER_OFFL")
  field(OUT, "CWSH:CP$(CP)2:0:RQST_OFF")
  field(ZSV, "MAJOR")
  field(ASG, "NOWRITE")
  field(ZNAM, "disabled")
  field(ONAM, "enabled")
  field(OSV, "NO_ALARM")
  field(COSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,416,1.1)
#! Record("CWSH:CP$(CP)2:0:ORDER_ON",80,378,0,1,"CWSH:CP$(CP)2:0:ORDER_ON")
#! Field("CWSH:CP$(CP)2:0:ORDER_ON.VAL",16777215,1,"CWSH:CP$(CP)2:0:ORDER_ON.VAL")
#! Record("CWSH:CP$(CP)2:0:ON_CNCL",80,798,0,1,"CWSH:CP$(CP)2:0:ON_CNCL")
#! Field("CWSH:CP$(CP)2:0:ON_CNCL.VAL",16777215,1,"CWSH:CP$(CP)2:0:ON_CNCL.VAL")
#! Record("CWSH:CP$(CP)2:0:ORDER_OFF",80,1018,0,1,"CWSH:CP$(CP)2:0:ORDER_OFF")
#! Field("CWSH:CP$(CP)2:0:ORDER_OFF.VAL",16777215,1,"CWSH:CP$(CP)2:0:ORDER_OFF.VAL")
#! Record("CWSH:CP$(CP)2:0:OFF_CNCL",80,1458,0,1,"CWSH:CP$(CP)2:0:OFF_CNCL")
#! Field("CWSH:CP$(CP)2:0:OFF_CNCL.VAL",16777215,1,"CWSH:CP$(CP)2:0:OFF_CNCL.VAL")
#! Record("CWSH:CP$(CP)2:0:ON_CFRM",80,578,0,1,"CWSH:CP$(CP)2:0:ON_CFRM")
#! Field("CWSH:CP$(CP)2:0:ON_CFRM.VAL",16777215,1,"CWSH:CP$(CP)2:0:ON_CFRM.VAL")
#! Record("CWSH:CP$(CP)2:0:OFF_CFRM",80,1238,0,1,"CWSH:CP$(CP)2:0:OFF_CFRM")
#! Field("CWSH:CP$(CP)2:0:OFF_CFRM.VAL",16777215,1,"CWSH:CP$(CP)2:0:OFF_CFRM.VAL")
#! Record("CWSH:CP$(CP)2:0:RQST_ON",960,584,0,1,"CWSH:CP$(CP)2:0:RQST_ON")
#! Field("CWSH:CP$(CP)2:0:RQST_ON.VAL",16777215,1,"CWSH:CP$(CP)2:0:RQST_ON.VAL")
#! Record("CWSH:CP$(CP)2:0:RQST_OFF",960,1204,0,1,"CWSH:CP$(CP)2:0:RQST_OFF")
#! Field("CWSH:CP$(CP)2:0:RQST_OFF.VAL",16777215,1,"CWSH:CP$(CP)2:0:RQST_OFF.VAL")
#! Record("CWSH:CP$(CP)2:0:ORDER_ONL",400,524,0,1,"CWSH:CP$(CP)2:0:ORDER_ONL")
#! Field("CWSH:CP$(CP)2:0:ORDER_ONL.FLNK",16777215,1,"CWSH:CP$(CP)2:0:ORDER_ONL.FLNK")
#! Link("CWSH:CP$(CP)2:0:ORDER_ONL.FLNK","CWSH:CP$(CP)2:0:ORDER_ONT")
#! Field("CWSH:CP$(CP)2:0:ORDER_ONL.INPA",16777215,0,"CWSH:CP$(CP)2:0:ORDER_ONL.INPA")
#! Link("CWSH:CP$(CP)2:0:ORDER_ONL.INPA","CWSH:CP$(CP)2:0:ORDER_ON.VAL")
#! Field("CWSH:CP$(CP)2:0:ORDER_ONL.INPB",16777215,0,"CWSH:CP$(CP)2:0:ORDER_ONL.INPB")
#! Link("CWSH:CP$(CP)2:0:ORDER_ONL.INPB","CWSH:CP$(CP)2:0:ON_CFRM.VAL")
#! Field("CWSH:CP$(CP)2:0:ORDER_ONL.INPC",16777215,0,"CWSH:CP$(CP)2:0:ORDER_ONL.INPC")
#! Link("CWSH:CP$(CP)2:0:ORDER_ONL.INPC","CWSH:CP$(CP)2:0:ON_CNCL.VAL")
#! Field("CWSH:CP$(CP)2:0:ORDER_ONL.VAL",16777215,1,"CWSH:CP$(CP)2:0:ORDER_ONL.VAL")
#! Record("CWSH:CP$(CP)2:0:ORDER_ONT",700,522,0,0,"CWSH:CP$(CP)2:0:ORDER_ONT")
#! Field("CWSH:CP$(CP)2:0:ORDER_ONT.DOL",16777215,0,"CWSH:CP$(CP)2:0:ORDER_ONT.DOL")
#! Link("CWSH:CP$(CP)2:0:ORDER_ONT.DOL","CWSH:CP$(CP)2:0:ORDER_ONL.VAL")
#! Field("CWSH:CP$(CP)2:0:ORDER_ONT.OUT",16777215,1,"CWSH:CP$(CP)2:0:ORDER_ONT.OUT")
#! Link("CWSH:CP$(CP)2:0:ORDER_ONT.OUT","CWSH:CP$(CP)2:0:RQST_ON.VAL")
#! Record("CWSH:CP$(CP)2:0:ORDER_OFFL",400,1124,0,1,"CWSH:CP$(CP)2:0:ORDER_OFFL")
#! Field("CWSH:CP$(CP)2:0:ORDER_OFFL.FLNK",16777215,1,"CWSH:CP$(CP)2:0:ORDER_OFFL.FLNK")
#! Link("CWSH:CP$(CP)2:0:ORDER_OFFL.FLNK","CWSH:CP$(CP)2:0:ORDER_OFFT")
#! Field("CWSH:CP$(CP)2:0:ORDER_OFFL.INPA",16777215,0,"CWSH:CP$(CP)2:0:ORDER_OFFL.INPA")
#! Link("CWSH:CP$(CP)2:0:ORDER_OFFL.INPA","CWSH:CP$(CP)2:0:ORDER_OFF.VAL")
#! Field("CWSH:CP$(CP)2:0:ORDER_OFFL.INPC",16777215,0,"CWSH:CP$(CP)2:0:ORDER_OFFL.INPC")
#! Link("CWSH:CP$(CP)2:0:ORDER_OFFL.INPC","CWSH:CP$(CP)2:0:OFF_CNCL.VAL")
#! Field("CWSH:CP$(CP)2:0:ORDER_OFFL.INPB",16777215,0,"CWSH:CP$(CP)2:0:ORDER_OFFL.INPB")
#! Link("CWSH:CP$(CP)2:0:ORDER_OFFL.INPB","CWSH:CP$(CP)2:0:OFF_CFRM.VAL")
#! Field("CWSH:CP$(CP)2:0:ORDER_OFFL.VAL",16777215,1,"CWSH:CP$(CP)2:0:ORDER_OFFL.VAL")
#! Record("CWSH:CP$(CP)2:0:ORDER_OFFT",700,1156,0,0,"CWSH:CP$(CP)2:0:ORDER_OFFT")
#! Field("CWSH:CP$(CP)2:0:ORDER_OFFT.DOL",16777215,0,"CWSH:CP$(CP)2:0:ORDER_OFFT.DOL")
#! Link("CWSH:CP$(CP)2:0:ORDER_OFFT.DOL","CWSH:CP$(CP)2:0:ORDER_OFFL.VAL")
#! Field("CWSH:CP$(CP)2:0:ORDER_OFFT.OUT",16777215,1,"CWSH:CP$(CP)2:0:ORDER_OFFT.OUT")
#! Link("CWSH:CP$(CP)2:0:ORDER_OFFT.OUT","CWSH:CP$(CP)2:0:RQST_OFF.VAL")
#! TextBox(TB1,480,360,780,400,0,"Dialog",12,1,16777215,"Turn On and confirm logic\nTurn Off and confirm logic\n",null)
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CCSH:CP$(CP)2:0:ORDER_ON") {
  field(DESC, "cold shield sequence  order on")
  field(ZNAM, "not ordered on")
  field(ONAM, "ordered on")
  field(OMSL, "supervisory")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CCSH:CP$(CP)2:0:ON_CNCL") {
  field(DESC, "cold shield sequence  Cancel ON order")
  field(ZNAM, "not cancelled")
  field(ONAM, "cancelled")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CCSH:CP$(CP)2:0:ORDER_OFF") {
  field(DESC, "cold shield sequence  order off")
  field(ZNAM, "not order off")
  field(ONAM, "order off")
  field(OMSL, "supervisory")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CCSH:CP$(CP)2:0:OFF_CNCL") {
  field(DESC, "cold shield sequence  Cancel OFF order")
  field(ZNAM, "not cancelled")
  field(ONAM, "cancelled")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CCSH:CP$(CP)2:0:ON_CFRM") {
  field(DESC, "cold shield sequence  confirm ON order")
  field(ZNAM, "not confirmed")
  field(ONAM, "confirmed")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
  field(OMSL, "supervisory")
}

record(bo, "CCSH:CP$(CP)2:0:OFF_CFRM") {
  field(DESC, "cold shield sequence  confirm OFF order")
  field(ZNAM, "not confirmed")
  field(ONAM, "confirmed")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CCSH:CP$(CP)2:0:RQST_ON") {
  field(DESC, "cold shield sequence  Rqst On")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) CBX_CMD B 13")
  field(ZNAM, "not active")
  field(ONAM, "Active")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(ASG, "NOWRITE")
  field(HIGH, "0")
  field(OMSL, "supervisory")
}

record(bo, "CCSH:CP$(CP)2:0:RQST_OFF") {
  field(DESC, "cold shield sequence  Rqst Off")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) CBX_CMD B 14")
  field(ZNAM, "not active")
  field(ONAM, "Active")
  field(ASG, "NOWRITE")
  field(PINI, "NO")
  field(HIGH, "0")
  field(SCAN, "1 second")
  field(OMSL, "supervisory")
}

record(sub, "CCSH:CP$(CP)2:0:ORDER_ONL") {
  field(DESC, "cold shield sequence ")
  field(SCAN, ".5 second")
  field(PINI, "NO")
  field(FLNK, "CCSH:CP$(CP)2:0:ORDER_ONT")
  field(INAM, "Icclmom")
  field(SNAM, "Scclmom")
  field(INPA, "CCSH:CP$(CP)2:0:ORDER_ON")
  field(INPB, "CCSH:CP$(CP)2:0:ON_CFRM")
  field(INPC, "CCSH:CP$(CP)2:0:ON_CNCL")
  field(ASG, "NOWRITE")
}

record(bo, "CCSH:CP$(CP)2:0:ORDER_ONT") {
  field(DESC, "cold shield sequence ")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "closed_loop")
  field(DOL, "CCSH:CP$(CP)2:0:ORDER_ONL")
  field(OUT, "CCSH:CP$(CP)2:0:RQST_ON")
  field(ZSV, "MAJOR")
  field(ASG, "NOWRITE")
  field(ZNAM, "disabled")
  field(ONAM, "enabled")
  field(OSV, "NO_ALARM")
  field(COSV, "NO_ALARM")
}

record(sub, "CCSH:CP$(CP)2:0:ORDER_OFFL") {
  field(DESC, "cold shield sequence ")
  field(SCAN, ".5 second")
  field(PINI, "NO")
  field(FLNK, "CCSH:CP$(CP)2:0:ORDER_OFFT")
  field(INAM, "Icclmom")
  field(SNAM, "Scclmom")
  field(INPA, "CCSH:CP$(CP)2:0:ORDER_OFF")
  field(INPB, "CCSH:CP$(CP)2:0:OFF_CFRM")
  field(INPC, "CCSH:CP$(CP)2:0:OFF_CNCL")
  field(ASG, "NOWRITE")
}

record(bo, "CCSH:CP$(CP)2:0:ORDER_OFFT") {
  field(DESC, "cold shield sequence ")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(OMSL, "closed_loop")
  field(DOL, "CCSH:CP$(CP)2:0:ORDER_OFFL")
  field(OUT, "CCSH:CP$(CP)2:0:RQST_OFF")
  field(ZSV, "MAJOR")
  field(ASG, "NOWRITE")
  field(ZNAM, "disabled")
  field(ONAM, "enabled")
  field(OSV, "NO_ALARM")
  field(COSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,416,1.1)
#! Record("CCSH:CP$(CP)2:0:ORDER_ON",80,378,0,1,"CCSH:CP$(CP)2:0:ORDER_ON")
#! Field("CCSH:CP$(CP)2:0:ORDER_ON.VAL",16777215,1,"CCSH:CP$(CP)2:0:ORDER_ON.VAL")
#! Record("CCSH:CP$(CP)2:0:ON_CNCL",80,798,0,1,"CCSH:CP$(CP)2:0:ON_CNCL")
#! Field("CCSH:CP$(CP)2:0:ON_CNCL.VAL",16777215,1,"CCSH:CP$(CP)2:0:ON_CNCL.VAL")
#! Record("CCSH:CP$(CP)2:0:ORDER_OFF",80,1018,0,1,"CCSH:CP$(CP)2:0:ORDER_OFF")
#! Field("CCSH:CP$(CP)2:0:ORDER_OFF.VAL",16777215,1,"CCSH:CP$(CP)2:0:ORDER_OFF.VAL")
#! Record("CCSH:CP$(CP)2:0:OFF_CNCL",80,1458,0,1,"CCSH:CP$(CP)2:0:OFF_CNCL")
#! Field("CCSH:CP$(CP)2:0:OFF_CNCL.VAL",16777215,1,"CCSH:CP$(CP)2:0:OFF_CNCL.VAL")
#! Record("CCSH:CP$(CP)2:0:ON_CFRM",80,578,0,1,"CCSH:CP$(CP)2:0:ON_CFRM")
#! Field("CCSH:CP$(CP)2:0:ON_CFRM.VAL",16777215,1,"CCSH:CP$(CP)2:0:ON_CFRM.VAL")
#! Record("CCSH:CP$(CP)2:0:OFF_CFRM",80,1238,0,1,"CCSH:CP$(CP)2:0:OFF_CFRM")
#! Field("CCSH:CP$(CP)2:0:OFF_CFRM.VAL",16777215,1,"CCSH:CP$(CP)2:0:OFF_CFRM.VAL")
#! Record("CCSH:CP$(CP)2:0:RQST_ON",960,584,0,1,"CCSH:CP$(CP)2:0:RQST_ON")
#! Field("CCSH:CP$(CP)2:0:RQST_ON.VAL",16777215,1,"CCSH:CP$(CP)2:0:RQST_ON.VAL")
#! Record("CCSH:CP$(CP)2:0:RQST_OFF",960,1204,0,1,"CCSH:CP$(CP)2:0:RQST_OFF")
#! Field("CCSH:CP$(CP)2:0:RQST_OFF.VAL",16777215,1,"CCSH:CP$(CP)2:0:RQST_OFF.VAL")
#! Record("CCSH:CP$(CP)2:0:ORDER_ONL",400,524,0,1,"CCSH:CP$(CP)2:0:ORDER_ONL")
#! Field("CCSH:CP$(CP)2:0:ORDER_ONL.FLNK",16777215,1,"CCSH:CP$(CP)2:0:ORDER_ONL.FLNK")
#! Link("CCSH:CP$(CP)2:0:ORDER_ONL.FLNK","CCSH:CP$(CP)2:0:ORDER_ONT")
#! Field("CCSH:CP$(CP)2:0:ORDER_ONL.INPA",16777215,0,"CCSH:CP$(CP)2:0:ORDER_ONL.INPA")
#! Link("CCSH:CP$(CP)2:0:ORDER_ONL.INPA","CCSH:CP$(CP)2:0:ORDER_ON.VAL")
#! Field("CCSH:CP$(CP)2:0:ORDER_ONL.INPB",16777215,0,"CCSH:CP$(CP)2:0:ORDER_ONL.INPB")
#! Link("CCSH:CP$(CP)2:0:ORDER_ONL.INPB","CCSH:CP$(CP)2:0:ON_CFRM.VAL")
#! Field("CCSH:CP$(CP)2:0:ORDER_ONL.INPC",16777215,0,"CCSH:CP$(CP)2:0:ORDER_ONL.INPC")
#! Link("CCSH:CP$(CP)2:0:ORDER_ONL.INPC","CCSH:CP$(CP)2:0:ON_CNCL.VAL")
#! Field("CCSH:CP$(CP)2:0:ORDER_ONL.VAL",16777215,1,"CCSH:CP$(CP)2:0:ORDER_ONL.VAL")
#! Record("CCSH:CP$(CP)2:0:ORDER_ONT",700,522,0,0,"CCSH:CP$(CP)2:0:ORDER_ONT")
#! Field("CCSH:CP$(CP)2:0:ORDER_ONT.DOL",16777215,0,"CCSH:CP$(CP)2:0:ORDER_ONT.DOL")
#! Link("CCSH:CP$(CP)2:0:ORDER_ONT.DOL","CCSH:CP$(CP)2:0:ORDER_ONL.VAL")
#! Field("CCSH:CP$(CP)2:0:ORDER_ONT.OUT",16777215,1,"CCSH:CP$(CP)2:0:ORDER_ONT.OUT")
#! Link("CCSH:CP$(CP)2:0:ORDER_ONT.OUT","CCSH:CP$(CP)2:0:RQST_ON.VAL")
#! Record("CCSH:CP$(CP)2:0:ORDER_OFFL",400,1124,0,1,"CCSH:CP$(CP)2:0:ORDER_OFFL")
#! Field("CCSH:CP$(CP)2:0:ORDER_OFFL.FLNK",16777215,1,"CCSH:CP$(CP)2:0:ORDER_OFFL.FLNK")
#! Link("CCSH:CP$(CP)2:0:ORDER_OFFL.FLNK","CCSH:CP$(CP)2:0:ORDER_OFFT")
#! Field("CCSH:CP$(CP)2:0:ORDER_OFFL.INPA",16777215,0,"CCSH:CP$(CP)2:0:ORDER_OFFL.INPA")
#! Link("CCSH:CP$(CP)2:0:ORDER_OFFL.INPA","CCSH:CP$(CP)2:0:ORDER_OFF.VAL")
#! Field("CCSH:CP$(CP)2:0:ORDER_OFFL.INPC",16777215,0,"CCSH:CP$(CP)2:0:ORDER_OFFL.INPC")
#! Link("CCSH:CP$(CP)2:0:ORDER_OFFL.INPC","CCSH:CP$(CP)2:0:OFF_CNCL.VAL")
#! Field("CCSH:CP$(CP)2:0:ORDER_OFFL.INPB",16777215,0,"CCSH:CP$(CP)2:0:ORDER_OFFL.INPB")
#! Link("CCSH:CP$(CP)2:0:ORDER_OFFL.INPB","CCSH:CP$(CP)2:0:OFF_CFRM.VAL")
#! Field("CCSH:CP$(CP)2:0:ORDER_OFFL.VAL",16777215,1,"CCSH:CP$(CP)2:0:ORDER_OFFL.VAL")
#! Record("CCSH:CP$(CP)2:0:ORDER_OFFT",700,1156,0,0,"CCSH:CP$(CP)2:0:ORDER_OFFT")
#! Field("CCSH:CP$(CP)2:0:ORDER_OFFT.DOL",16777215,0,"CCSH:CP$(CP)2:0:ORDER_OFFT.DOL")
#! Link("CCSH:CP$(CP)2:0:ORDER_OFFT.DOL","CCSH:CP$(CP)2:0:ORDER_OFFL.VAL")
#! Field("CCSH:CP$(CP)2:0:ORDER_OFFT.OUT",16777215,1,"CCSH:CP$(CP)2:0:ORDER_OFFT.OUT")
#! Link("CCSH:CP$(CP)2:0:ORDER_OFFT.OUT","CCSH:CP$(CP)2:0:RQST_OFF.VAL")
#! TextBox(TB1,480,360,780,400,0,"Dialog",12,1,16777215,"Turn On and confirm logic\nTurn Off and confirm logic\n",null)
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "C4KS:CP$(CP)2:0:ORDER_ON") {
  field(DESC, "4K supply  TO LINAC  order on")
  field(ZNAM, "not ordered on")
  field(ONAM, "ordered on")
  field(OMSL, "supervisory")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "C4KS:CP$(CP)2:0:ON_CNCL") {
  field(DESC, "4K supply  TO LINAC  Cancel ON order")
  field(ZNAM, "not cancelled")
  field(ONAM, "cancelled")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "C4KS:CP$(CP)2:0:ORDER_OFF") {
  field(DESC, "4K supply  TO LINAC  order off")
  field(ZNAM, "not order off")
  field(ONAM, "order off")
  field(OMSL, "supervisory")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "C4KS:CP$(CP)2:0:OFF_CNCL") {
  field(DESC, "4K supply  TO LINAC  Cancel OFF order")
  field(ZNAM, "not cancelled")
  field(ONAM, "cancelled")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "C4KS:CP$(CP)2:0:ON_CFRM") {
  field(DESC, "4K supply  TO LINAC  confirm ON order")
  field(ZNAM, "not confirmed")
  field(ONAM, "confirmed")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
  field(OMSL, "supervisory")
}

record(bo, "C4KS:CP$(CP)2:0:OFF_CFRM") {
  field(DESC, "4K supply  TO LINAC  confirm OFF order")
  field(ZNAM, "not confirmed")
  field(ONAM, "confirmed")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "C4KS:CP$(CP)2:0:RQST_ON") {
  field(DESC, "4K supply  TO LINAC  Rqst On")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) CBX_CMD B 15")
  field(ZNAM, "not active")
  field(ONAM, "Active")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(ASG, "NOWRITE")
  field(HIGH, "0")
  field(OMSL, "supervisory")
}

record(bo, "C4KS:CP$(CP)2:0:RQST_OFF") {
  field(DESC, "4K supply  TO LINAC  Rqst Off")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) CBX_CMD B 16")
  field(ZNAM, "not active")
  field(ONAM, "Active")
  field(ASG, "NOWRITE")
  field(PINI, "NO")
  field(HIGH, "0")
  field(SCAN, "1 second")
  field(OMSL, "supervisory")
}

record(sub, "C4KS:CP$(CP)2:0:ORDER_ONL") {
  field(DESC, "4K supply  TO LINAC ")
  field(SCAN, ".5 second")
  field(PINI, "NO")
  field(FLNK, "C4KS:CP$(CP)2:0:ORDER_ONT")
  field(INAM, "Icclmom")
  field(SNAM, "Scclmom")
  field(INPA, "C4KS:CP$(CP)2:0:ORDER_ON")
  field(INPB, "C4KS:CP$(CP)2:0:ON_CFRM")
  field(INPC, "C4KS:CP$(CP)2:0:ON_CNCL")
  field(ASG, "NOWRITE")
}

record(bo, "C4KS:CP$(CP)2:0:ORDER_ONT") {
  field(DESC, "4K supply  TO LINAC ")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "closed_loop")
  field(DOL, "C4KS:CP$(CP)2:0:ORDER_ONL")
  field(OUT, "C4KS:CP$(CP)2:0:RQST_ON")
  field(ZSV, "MAJOR")
  field(ASG, "NOWRITE")
  field(ZNAM, "disabled")
  field(ONAM, "enabled")
  field(OSV, "NO_ALARM")
  field(COSV, "NO_ALARM")
}

record(sub, "C4KS:CP$(CP)2:0:ORDER_OFFL") {
  field(DESC, "4K supply  TO LINAC ")
  field(SCAN, ".5 second")
  field(PINI, "NO")
  field(FLNK, "C4KS:CP$(CP)2:0:ORDER_OFFT")
  field(INAM, "Icclmom")
  field(SNAM, "Scclmom")
  field(INPA, "C4KS:CP$(CP)2:0:ORDER_OFF")
  field(INPB, "C4KS:CP$(CP)2:0:OFF_CFRM")
  field(INPC, "C4KS:CP$(CP)2:0:OFF_CNCL")
  field(ASG, "NOWRITE")
}

record(bo, "C4KS:CP$(CP)2:0:ORDER_OFFT") {
  field(DESC, "4K supply  TO LINAC ")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(OMSL, "closed_loop")
  field(DOL, "C4KS:CP$(CP)2:0:ORDER_OFFL")
  field(OUT, "C4KS:CP$(CP)2:0:RQST_OFF")
  field(ZSV, "MAJOR")
  field(ASG, "NOWRITE")
  field(ZNAM, "disabled")
  field(ONAM, "enabled")
  field(OSV, "NO_ALARM")
  field(COSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,416,1.1)
#! Record("C4KS:CP$(CP)2:0:ORDER_ON",80,378,0,1,"C4KS:CP$(CP)2:0:ORDER_ON")
#! Field("C4KS:CP$(CP)2:0:ORDER_ON.VAL",16777215,1,"C4KS:CP$(CP)2:0:ORDER_ON.VAL")
#! Record("C4KS:CP$(CP)2:0:ON_CNCL",80,798,0,1,"C4KS:CP$(CP)2:0:ON_CNCL")
#! Field("C4KS:CP$(CP)2:0:ON_CNCL.VAL",16777215,1,"C4KS:CP$(CP)2:0:ON_CNCL.VAL")
#! Record("C4KS:CP$(CP)2:0:ORDER_OFF",80,1018,0,1,"C4KS:CP$(CP)2:0:ORDER_OFF")
#! Field("C4KS:CP$(CP)2:0:ORDER_OFF.VAL",16777215,1,"C4KS:CP$(CP)2:0:ORDER_OFF.VAL")
#! Record("C4KS:CP$(CP)2:0:OFF_CNCL",80,1458,0,1,"C4KS:CP$(CP)2:0:OFF_CNCL")
#! Field("C4KS:CP$(CP)2:0:OFF_CNCL.VAL",16777215,1,"C4KS:CP$(CP)2:0:OFF_CNCL.VAL")
#! Record("C4KS:CP$(CP)2:0:ON_CFRM",80,578,0,1,"C4KS:CP$(CP)2:0:ON_CFRM")
#! Field("C4KS:CP$(CP)2:0:ON_CFRM.VAL",16777215,1,"C4KS:CP$(CP)2:0:ON_CFRM.VAL")
#! Record("C4KS:CP$(CP)2:0:OFF_CFRM",80,1238,0,1,"C4KS:CP$(CP)2:0:OFF_CFRM")
#! Field("C4KS:CP$(CP)2:0:OFF_CFRM.VAL",16777215,1,"C4KS:CP$(CP)2:0:OFF_CFRM.VAL")
#! Record("C4KS:CP$(CP)2:0:RQST_ON",960,584,0,1,"C4KS:CP$(CP)2:0:RQST_ON")
#! Field("C4KS:CP$(CP)2:0:RQST_ON.VAL",16777215,1,"C4KS:CP$(CP)2:0:RQST_ON.VAL")
#! Record("C4KS:CP$(CP)2:0:RQST_OFF",960,1204,0,1,"C4KS:CP$(CP)2:0:RQST_OFF")
#! Field("C4KS:CP$(CP)2:0:RQST_OFF.VAL",16777215,1,"C4KS:CP$(CP)2:0:RQST_OFF.VAL")
#! Record("C4KS:CP$(CP)2:0:ORDER_ONL",400,524,0,1,"C4KS:CP$(CP)2:0:ORDER_ONL")
#! Field("C4KS:CP$(CP)2:0:ORDER_ONL.FLNK",16777215,1,"C4KS:CP$(CP)2:0:ORDER_ONL.FLNK")
#! Link("C4KS:CP$(CP)2:0:ORDER_ONL.FLNK","C4KS:CP$(CP)2:0:ORDER_ONT")
#! Field("C4KS:CP$(CP)2:0:ORDER_ONL.INPA",16777215,0,"C4KS:CP$(CP)2:0:ORDER_ONL.INPA")
#! Link("C4KS:CP$(CP)2:0:ORDER_ONL.INPA","C4KS:CP$(CP)2:0:ORDER_ON.VAL")
#! Field("C4KS:CP$(CP)2:0:ORDER_ONL.INPB",16777215,0,"C4KS:CP$(CP)2:0:ORDER_ONL.INPB")
#! Link("C4KS:CP$(CP)2:0:ORDER_ONL.INPB","C4KS:CP$(CP)2:0:ON_CFRM.VAL")
#! Field("C4KS:CP$(CP)2:0:ORDER_ONL.INPC",16777215,0,"C4KS:CP$(CP)2:0:ORDER_ONL.INPC")
#! Link("C4KS:CP$(CP)2:0:ORDER_ONL.INPC","C4KS:CP$(CP)2:0:ON_CNCL.VAL")
#! Field("C4KS:CP$(CP)2:0:ORDER_ONL.VAL",16777215,1,"C4KS:CP$(CP)2:0:ORDER_ONL.VAL")
#! Record("C4KS:CP$(CP)2:0:ORDER_ONT",700,522,0,0,"C4KS:CP$(CP)2:0:ORDER_ONT")
#! Field("C4KS:CP$(CP)2:0:ORDER_ONT.DOL",16777215,0,"C4KS:CP$(CP)2:0:ORDER_ONT.DOL")
#! Link("C4KS:CP$(CP)2:0:ORDER_ONT.DOL","C4KS:CP$(CP)2:0:ORDER_ONL.VAL")
#! Field("C4KS:CP$(CP)2:0:ORDER_ONT.OUT",16777215,1,"C4KS:CP$(CP)2:0:ORDER_ONT.OUT")
#! Link("C4KS:CP$(CP)2:0:ORDER_ONT.OUT","C4KS:CP$(CP)2:0:RQST_ON.VAL")
#! Record("C4KS:CP$(CP)2:0:ORDER_OFFL",400,1124,0,1,"C4KS:CP$(CP)2:0:ORDER_OFFL")
#! Field("C4KS:CP$(CP)2:0:ORDER_OFFL.FLNK",16777215,1,"C4KS:CP$(CP)2:0:ORDER_OFFL.FLNK")
#! Link("C4KS:CP$(CP)2:0:ORDER_OFFL.FLNK","C4KS:CP$(CP)2:0:ORDER_OFFT")
#! Field("C4KS:CP$(CP)2:0:ORDER_OFFL.INPA",16777215,0,"C4KS:CP$(CP)2:0:ORDER_OFFL.INPA")
#! Link("C4KS:CP$(CP)2:0:ORDER_OFFL.INPA","C4KS:CP$(CP)2:0:ORDER_OFF.VAL")
#! Field("C4KS:CP$(CP)2:0:ORDER_OFFL.INPC",16777215,0,"C4KS:CP$(CP)2:0:ORDER_OFFL.INPC")
#! Link("C4KS:CP$(CP)2:0:ORDER_OFFL.INPC","C4KS:CP$(CP)2:0:OFF_CNCL.VAL")
#! Field("C4KS:CP$(CP)2:0:ORDER_OFFL.INPB",16777215,0,"C4KS:CP$(CP)2:0:ORDER_OFFL.INPB")
#! Link("C4KS:CP$(CP)2:0:ORDER_OFFL.INPB","C4KS:CP$(CP)2:0:OFF_CFRM.VAL")
#! Field("C4KS:CP$(CP)2:0:ORDER_OFFL.VAL",16777215,1,"C4KS:CP$(CP)2:0:ORDER_OFFL.VAL")
#! Record("C4KS:CP$(CP)2:0:ORDER_OFFT",700,1156,0,0,"C4KS:CP$(CP)2:0:ORDER_OFFT")
#! Field("C4KS:CP$(CP)2:0:ORDER_OFFT.DOL",16777215,0,"C4KS:CP$(CP)2:0:ORDER_OFFT.DOL")
#! Link("C4KS:CP$(CP)2:0:ORDER_OFFT.DOL","C4KS:CP$(CP)2:0:ORDER_OFFL.VAL")
#! Field("C4KS:CP$(CP)2:0:ORDER_OFFT.OUT",16777215,1,"C4KS:CP$(CP)2:0:ORDER_OFFT.OUT")
#! Link("C4KS:CP$(CP)2:0:ORDER_OFFT.OUT","C4KS:CP$(CP)2:0:RQST_OFF.VAL")
#! TextBox(TB1,480,360,780,400,0,"Dialog",12,1,16777215,"Turn On and confirm logic\nTurn Off and confirm logic\n",null)
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CDWR:CP$(CP)2:0:ORDER_ON") {
  field(DESC, "Dewar  sequence  order on")
  field(ZNAM, "not ordered on")
  field(ONAM, "ordered on")
  field(OMSL, "supervisory")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CDWR:CP$(CP)2:0:ON_CNCL") {
  field(DESC, "Dewar  sequence  Cancel ON order")
  field(ZNAM, "not cancelled")
  field(ONAM, "cancelled")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CDWR:CP$(CP)2:0:ORDER_OFF") {
  field(DESC, "Dewar  sequence  order off")
  field(ZNAM, "not order off")
  field(ONAM, "order off")
  field(OMSL, "supervisory")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CDWR:CP$(CP)2:0:OFF_CNCL") {
  field(DESC, "Dewar  sequence  Cancel OFF order")
  field(ZNAM, "not cancelled")
  field(ONAM, "cancelled")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CDWR:CP$(CP)2:0:ON_CFRM") {
  field(DESC, "Dewar  sequence  confirm ON order")
  field(ZNAM, "not confirmed")
  field(ONAM, "confirmed")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(HIGH, "1")
  field(ASG, "CRYO")
  field(OMSL, "supervisory")
}

record(bo, "CDWR:CP$(CP)2:0:OFF_CFRM") {
  field(DESC, "Dewar  sequence  confirm OFF order")
  field(ZNAM, "not confirmed")
  field(ONAM, "confirmed")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "supervisory")
  field(HIGH, "1")
  field(ASG, "CRYO")
}

record(bo, "CDWR:CP$(CP)2:0:RQST_ON") {
  field(DESC, "Dewar  sequence  Rqst On")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) Dewar_CMD B 1")
  field(ZNAM, "not active")
  field(ONAM, "Active")
  field(SCAN, "1 second")
  field(PINI, "NO")
  field(ASG, "NOWRITE")
  field(HIGH, "0")
  field(OMSL, "supervisory")
}

record(bo, "CDWR:CP$(CP)2:0:RQST_OFF") {
  field(DESC, "Dewar  sequence  Rqst Off")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) Dewar_CMD B 2")
  field(ZNAM, "not active")
  field(ONAM, "Active")
  field(ASG, "NOWRITE")
  field(PINI, "NO")
  field(HIGH, "0")
  field(SCAN, "1 second")
  field(OMSL, "supervisory")
}

record(sub, "CDWR:CP$(CP)2:0:ORDER_ONL") {
  field(DESC, "Dewar  sequence ")
  field(SCAN, ".5 second")
  field(PINI, "NO")
  field(FLNK, "CDWR:CP$(CP)2:0:ORDER_ONT")
  field(INAM, "Icclmom")
  field(SNAM, "Scclmom")
  field(INPA, "CDWR:CP$(CP)2:0:ORDER_ON")
  field(INPB, "CDWR:CP$(CP)2:0:ON_CFRM")
  field(INPC, "CDWR:CP$(CP)2:0:ON_CNCL")
  field(ASG, "NOWRITE")
}

record(bo, "CDWR:CP$(CP)2:0:ORDER_ONT") {
  field(DESC, "Dewar  sequence ")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(DTYP, "Soft Channel")
  field(OMSL, "closed_loop")
  field(DOL, "CDWR:CP$(CP)2:0:ORDER_ONL")
  field(OUT, "CDWR:CP$(CP)2:0:RQST_ON")
  field(ZSV, "MAJOR")
  field(ASG, "NOWRITE")
  field(ZNAM, "disabled")
  field(ONAM, "enabled")
  field(OSV, "NO_ALARM")
  field(COSV, "NO_ALARM")
}

record(sub, "CDWR:CP$(CP)2:0:ORDER_OFFL") {
  field(DESC, "Dewar  sequence ")
  field(SCAN, ".5 second")
  field(PINI, "NO")
  field(FLNK, "CDWR:CP$(CP)2:0:ORDER_OFFT")
  field(INAM, "Icclmom")
  field(SNAM, "Scclmom")
  field(INPA, "CDWR:CP$(CP)2:0:ORDER_OFF")
  field(INPB, "CDWR:CP$(CP)2:0:OFF_CFRM")
  field(INPC, "CDWR:CP$(CP)2:0:OFF_CNCL")
  field(ASG, "NOWRITE")
}

record(bo, "CDWR:CP$(CP)2:0:ORDER_OFFT") {
  field(DESC, "Dewar  sequence ")
  field(SCAN, "Passive")
  field(PINI, "NO")
  field(OMSL, "closed_loop")
  field(DOL, "CDWR:CP$(CP)2:0:ORDER_OFFL")
  field(OUT, "CDWR:CP$(CP)2:0:RQST_OFF")
  field(ZSV, "MAJOR")
  field(ASG, "NOWRITE")
  field(ZNAM, "disabled")
  field(ONAM, "enabled")
  field(OSV, "NO_ALARM")
  field(COSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,416,1.1)
#! Record("CDWR:CP$(CP)2:0:ORDER_ON",80,378,0,1,"CDWR:CP$(CP)2:0:ORDER_ON")
#! Field("CDWR:CP$(CP)2:0:ORDER_ON.VAL",16777215,1,"CDWR:CP$(CP)2:0:ORDER_ON.VAL")
#! Record("CDWR:CP$(CP)2:0:ON_CNCL",80,798,0,1,"CDWR:CP$(CP)2:0:ON_CNCL")
#! Field("CDWR:CP$(CP)2:0:ON_CNCL.VAL",16777215,1,"CDWR:CP$(CP)2:0:ON_CNCL.VAL")
#! Record("CDWR:CP$(CP)2:0:ORDER_OFF",80,1018,0,1,"CDWR:CP$(CP)2:0:ORDER_OFF")
#! Field("CDWR:CP$(CP)2:0:ORDER_OFF.VAL",16777215,1,"CDWR:CP$(CP)2:0:ORDER_OFF.VAL")
#! Record("CDWR:CP$(CP)2:0:OFF_CNCL",80,1458,0,1,"CDWR:CP$(CP)2:0:OFF_CNCL")
#! Field("CDWR:CP$(CP)2:0:OFF_CNCL.VAL",16777215,1,"CDWR:CP$(CP)2:0:OFF_CNCL.VAL")
#! Record("CDWR:CP$(CP)2:0:ON_CFRM",80,578,0,1,"CDWR:CP$(CP)2:0:ON_CFRM")
#! Field("CDWR:CP$(CP)2:0:ON_CFRM.VAL",16777215,1,"CDWR:CP$(CP)2:0:ON_CFRM.VAL")
#! Record("CDWR:CP$(CP)2:0:OFF_CFRM",80,1238,0,1,"CDWR:CP$(CP)2:0:OFF_CFRM")
#! Field("CDWR:CP$(CP)2:0:OFF_CFRM.VAL",16777215,1,"CDWR:CP$(CP)2:0:OFF_CFRM.VAL")
#! Record("CDWR:CP$(CP)2:0:RQST_ON",960,584,0,1,"CDWR:CP$(CP)2:0:RQST_ON")
#! Field("CDWR:CP$(CP)2:0:RQST_ON.VAL",16777215,1,"CDWR:CP$(CP)2:0:RQST_ON.VAL")
#! Record("CDWR:CP$(CP)2:0:RQST_OFF",960,1204,0,1,"CDWR:CP$(CP)2:0:RQST_OFF")
#! Field("CDWR:CP$(CP)2:0:RQST_OFF.VAL",16777215,1,"CDWR:CP$(CP)2:0:RQST_OFF.VAL")
#! Record("CDWR:CP$(CP)2:0:ORDER_ONL",400,524,0,1,"CDWR:CP$(CP)2:0:ORDER_ONL")
#! Field("CDWR:CP$(CP)2:0:ORDER_ONL.FLNK",16777215,1,"CDWR:CP$(CP)2:0:ORDER_ONL.FLNK")
#! Link("CDWR:CP$(CP)2:0:ORDER_ONL.FLNK","CDWR:CP$(CP)2:0:ORDER_ONT")
#! Field("CDWR:CP$(CP)2:0:ORDER_ONL.INPA",16777215,0,"CDWR:CP$(CP)2:0:ORDER_ONL.INPA")
#! Link("CDWR:CP$(CP)2:0:ORDER_ONL.INPA","CDWR:CP$(CP)2:0:ORDER_ON.VAL")
#! Field("CDWR:CP$(CP)2:0:ORDER_ONL.INPB",16777215,0,"CDWR:CP$(CP)2:0:ORDER_ONL.INPB")
#! Link("CDWR:CP$(CP)2:0:ORDER_ONL.INPB","CDWR:CP$(CP)2:0:ON_CFRM.VAL")
#! Field("CDWR:CP$(CP)2:0:ORDER_ONL.INPC",16777215,0,"CDWR:CP$(CP)2:0:ORDER_ONL.INPC")
#! Link("CDWR:CP$(CP)2:0:ORDER_ONL.INPC","CDWR:CP$(CP)2:0:ON_CNCL.VAL")
#! Field("CDWR:CP$(CP)2:0:ORDER_ONL.VAL",16777215,1,"CDWR:CP$(CP)2:0:ORDER_ONL.VAL")
#! Record("CDWR:CP$(CP)2:0:ORDER_ONT",700,522,0,0,"CDWR:CP$(CP)2:0:ORDER_ONT")
#! Field("CDWR:CP$(CP)2:0:ORDER_ONT.DOL",16777215,0,"CDWR:CP$(CP)2:0:ORDER_ONT.DOL")
#! Link("CDWR:CP$(CP)2:0:ORDER_ONT.DOL","CDWR:CP$(CP)2:0:ORDER_ONL.VAL")
#! Field("CDWR:CP$(CP)2:0:ORDER_ONT.OUT",16777215,1,"CDWR:CP$(CP)2:0:ORDER_ONT.OUT")
#! Link("CDWR:CP$(CP)2:0:ORDER_ONT.OUT","CDWR:CP$(CP)2:0:RQST_ON.VAL")
#! Record("CDWR:CP$(CP)2:0:ORDER_OFFL",400,1124,0,1,"CDWR:CP$(CP)2:0:ORDER_OFFL")
#! Field("CDWR:CP$(CP)2:0:ORDER_OFFL.FLNK",16777215,1,"CDWR:CP$(CP)2:0:ORDER_OFFL.FLNK")
#! Link("CDWR:CP$(CP)2:0:ORDER_OFFL.FLNK","CDWR:CP$(CP)2:0:ORDER_OFFT")
#! Field("CDWR:CP$(CP)2:0:ORDER_OFFL.INPA",16777215,0,"CDWR:CP$(CP)2:0:ORDER_OFFL.INPA")
#! Link("CDWR:CP$(CP)2:0:ORDER_OFFL.INPA","CDWR:CP$(CP)2:0:ORDER_OFF.VAL")
#! Field("CDWR:CP$(CP)2:0:ORDER_OFFL.INPC",16777215,0,"CDWR:CP$(CP)2:0:ORDER_OFFL.INPC")
#! Link("CDWR:CP$(CP)2:0:ORDER_OFFL.INPC","CDWR:CP$(CP)2:0:OFF_CNCL.VAL")
#! Field("CDWR:CP$(CP)2:0:ORDER_OFFL.INPB",16777215,0,"CDWR:CP$(CP)2:0:ORDER_OFFL.INPB")
#! Link("CDWR:CP$(CP)2:0:ORDER_OFFL.INPB","CDWR:CP$(CP)2:0:OFF_CFRM.VAL")
#! Field("CDWR:CP$(CP)2:0:ORDER_OFFL.VAL",16777215,1,"CDWR:CP$(CP)2:0:ORDER_OFFL.VAL")
#! Record("CDWR:CP$(CP)2:0:ORDER_OFFT",700,1156,0,0,"CDWR:CP$(CP)2:0:ORDER_OFFT")
#! Field("CDWR:CP$(CP)2:0:ORDER_OFFT.DOL",16777215,0,"CDWR:CP$(CP)2:0:ORDER_OFFT.DOL")
#! Link("CDWR:CP$(CP)2:0:ORDER_OFFT.DOL","CDWR:CP$(CP)2:0:ORDER_OFFL.VAL")
#! Field("CDWR:CP$(CP)2:0:ORDER_OFFT.OUT",16777215,1,"CDWR:CP$(CP)2:0:ORDER_OFFT.OUT")
#! Link("CDWR:CP$(CP)2:0:ORDER_OFFT.OUT","CDWR:CP$(CP)2:0:RQST_OFF.VAL")
#! TextBox(TB1,480,360,780,400,0,"Dialog",12,1,16777215,"Turn On and confirm logic\nTurn Off and confirm logic\n",null)
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CZSH:CP$(CP)2:2100:LIMIT_SW") {
  field(DESC, "LPL isol. vlv open")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) ZSH22100")
  field(ZNAM, "not open")
  field(ONAM, "open")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(stringin, "CZSH:CP$(CP)2:2100:PIDTAG") {
  field(DESC, "Lmt Swch P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)ZSH22100")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CZSH:CP$(CP)2:2100:LIMIT_SW",2054,2119,0,1,"CZSH:CP$(CP)2:2100:LIMIT_SW")
#! Record("CZSH:CP$(CP)2:2100:PIDTAG",2054,2322,0,1,"CZSH:CP$(CP)2:2100:PIDTAG")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CZSL:CP$(CP)2:2100:LIMIT_SW") {
  field(DESC, "LPL isol. vlv closed")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) ZSL22100")
  field(ZNAM, "not closed")
  field(ONAM, "closed")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(stringin, "CZSL:CP$(CP)2:2100:PIDTAG") {
  field(DESC, "Lmt Swch P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)ZSL22100")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CZSL:CP$(CP)2:2100:LIMIT_SW",2054,2119,0,1,"CZSL:CP$(CP)2:2100:LIMIT_SW")
#! Record("CZSL:CP$(CP)2:2100:PIDTAG",2054,2322,0,1,"CZSL:CP$(CP)2:2100:PIDTAG")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CZSH:CP$(CP)2:2200:LIMIT_SW") {
  field(DESC, "LPR isol. vlv open")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) ZSH22200")
  field(ZNAM, "not open")
  field(ONAM, "open")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(stringin, "CZSH:CP$(CP)2:2200:PIDTAG") {
  field(DESC, "Lmt Swch P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)ZSH22200")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CZSH:CP$(CP)2:2200:LIMIT_SW",2054,2119,0,1,"CZSH:CP$(CP)2:2200:LIMIT_SW")
#! Record("CZSH:CP$(CP)2:2200:PIDTAG",2054,2322,0,1,"CZSH:CP$(CP)2:2200:PIDTAG")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CZSL:CP$(CP)2:2200:LIMIT_SW") {
  field(DESC, "LPR isol. vlv closed")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) ZSL22200")
  field(ZNAM, "not closed")
  field(ONAM, "closed")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(stringin, "CZSL:CP$(CP)2:2200:PIDTAG") {
  field(DESC, "Lmt Swch P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)ZSL22200")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CZSL:CP$(CP)2:2200:LIMIT_SW",2054,2119,0,1,"CZSL:CP$(CP)2:2200:LIMIT_SW")
#! Record("CZSL:CP$(CP)2:2200:PIDTAG",2054,2322,0,1,"CZSL:CP$(CP)2:2200:PIDTAG")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CZSH:CP$(CP)2:2242:LIMIT_SW") {
  field(DESC, "T1 outlet vlv open")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) ZSH22242")
  field(ZNAM, "not open")
  field(ONAM, "open")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(stringin, "CZSH:CP$(CP)2:2242:PIDTAG") {
  field(DESC, "Lmt Swch P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)ZSH22242")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CZSH:CP$(CP)2:2242:LIMIT_SW",2054,2119,0,1,"CZSH:CP$(CP)2:2242:LIMIT_SW")
#! Record("CZSH:CP$(CP)2:2242:PIDTAG",2054,2322,0,1,"CZSH:CP$(CP)2:2242:PIDTAG")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CZSL:CP$(CP)2:2242:LIMIT_SW") {
  field(DESC, "T1 outlet vlv closed")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) ZSL22242")
  field(ZNAM, "not closed")
  field(ONAM, "closed")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(stringin, "CZSL:CP$(CP)2:2242:PIDTAG") {
  field(DESC, "Lmt Swch P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)ZSL22242")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CZSL:CP$(CP)2:2242:LIMIT_SW",2054,2119,0,1,"CZSL:CP$(CP)2:2242:LIMIT_SW")
#! Record("CZSL:CP$(CP)2:2242:PIDTAG",2054,2322,0,1,"CZSL:CP$(CP)2:2242:PIDTAG")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CZSH:CP$(CP)2:2245:LIMIT_SW") {
  field(DESC, "warm shld sply vlv open")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) ZSH22245")
  field(ZNAM, "not open")
  field(ONAM, "open")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(stringin, "CZSH:CP$(CP)2:2245:PIDTAG") {
  field(DESC, "Lmt Swch P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)ZSH22245")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CZSH:CP$(CP)2:2245:LIMIT_SW",2054,2119,0,1,"CZSH:CP$(CP)2:2245:LIMIT_SW")
#! Record("CZSH:CP$(CP)2:2245:PIDTAG",2054,2322,0,1,"CZSH:CP$(CP)2:2245:PIDTAG")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CZSL:CP$(CP)2:2245:LIMIT_SW") {
  field(DESC, "warm shld sply vlv closed")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) ZSL22245")
  field(ZNAM, "not closed")
  field(ONAM, "closed")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(stringin, "CZSL:CP$(CP)2:2245:PIDTAG") {
  field(DESC, "Lmt Swch P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)ZSL22245")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CZSL:CP$(CP)2:2245:LIMIT_SW",2054,2119,0,1,"CZSL:CP$(CP)2:2245:LIMIT_SW")
#! Record("CZSL:CP$(CP)2:2245:PIDTAG",2054,2322,0,1,"CZSL:CP$(CP)2:2245:PIDTAG")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CZSH:CP$(CP)2:2358:LIMIT_SW") {
  field(DESC, "T2 outlet vlv open")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) ZSH22358")
  field(ZNAM, "not open")
  field(ONAM, "open")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(stringin, "CZSH:CP$(CP)2:2358:PIDTAG") {
  field(DESC, "Lmt Swch P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)ZSH22358")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CZSH:CP$(CP)2:2358:LIMIT_SW",2054,2119,0,1,"CZSH:CP$(CP)2:2358:LIMIT_SW")
#! Record("CZSH:CP$(CP)2:2358:PIDTAG",2054,2322,0,1,"CZSH:CP$(CP)2:2358:PIDTAG")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CZSL:CP$(CP)2:2358:LIMIT_SW") {
  field(DESC, "T2 outlet vlv closed")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) ZSL22358")
  field(ZNAM, "not closed")
  field(ONAM, "closed")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(stringin, "CZSL:CP$(CP)2:2358:PIDTAG") {
  field(DESC, "Lmt Swch P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)ZSL22358")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CZSL:CP$(CP)2:2358:LIMIT_SW",2054,2119,0,1,"CZSL:CP$(CP)2:2358:LIMIT_SW")
#! Record("CZSL:CP$(CP)2:2358:PIDTAG",2054,2322,0,1,"CZSL:CP$(CP)2:2358:PIDTAG")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CZSH:CP$(CP)2:2378:LIMIT_SW") {
  field(DESC, "T3 outlet vlv open")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) ZSH22378")
  field(ZNAM, "not open")
  field(ONAM, "open")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(stringin, "CZSH:CP$(CP)2:2378:PIDTAG") {
  field(DESC, "Lmt Swch P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)ZSH22378")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CZSH:CP$(CP)2:2378:LIMIT_SW",2054,2119,0,1,"CZSH:CP$(CP)2:2378:LIMIT_SW")
#! Record("CZSH:CP$(CP)2:2378:PIDTAG",2054,2322,0,1,"CZSH:CP$(CP)2:2378:PIDTAG")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CZSL:CP$(CP)2:2378:LIMIT_SW") {
  field(DESC, "T3 outlet vlv closed")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) ZSL22378")
  field(ZNAM, "not closed")
  field(ONAM, "closed")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(stringin, "CZSL:CP$(CP)2:2378:PIDTAG") {
  field(DESC, "Lmt Swch P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)ZSL22378")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CZSL:CP$(CP)2:2378:LIMIT_SW",2054,2119,0,1,"CZSL:CP$(CP)2:2378:LIMIT_SW")
#! Record("CZSL:CP$(CP)2:2378:PIDTAG",2054,2322,0,1,"CZSL:CP$(CP)2:2378:PIDTAG")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CZSH:CP$(CP)2:2388:LIMIT_SW") {
  field(DESC, "T4 outlet vlv open")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) ZSH22388")
  field(ZNAM, "not open")
  field(ONAM, "open")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(stringin, "CZSH:CP$(CP)2:2388:PIDTAG") {
  field(DESC, "Lmt Swch P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)ZSH22388")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CZSH:CP$(CP)2:2388:LIMIT_SW",2054,2119,0,1,"CZSH:CP$(CP)2:2388:LIMIT_SW")
#! Record("CZSH:CP$(CP)2:2388:PIDTAG",2054,2322,0,1,"CZSH:CP$(CP)2:2388:PIDTAG")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CZSL:CP$(CP)2:2388:LIMIT_SW") {
  field(DESC, "T4 outlet vlv closed")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) ZSL22388")
  field(ZNAM, "not closed")
  field(ONAM, "closed")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(stringin, "CZSL:CP$(CP)2:2388:PIDTAG") {
  field(DESC, "Lmt Swch P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)ZSL22388")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CZSL:CP$(CP)2:2388:LIMIT_SW",2054,2119,0,1,"CZSL:CP$(CP)2:2388:LIMIT_SW")
#! Record("CZSL:CP$(CP)2:2388:PIDTAG",2054,2322,0,1,"CZSL:CP$(CP)2:2388:PIDTAG")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CZSH:CP$(CP)2:3611:LIMIT_SW") {
  field(DESC, "gate vlv open")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) ZSH23611")
  field(ZNAM, "not open")
  field(ONAM, "open")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(stringin, "CZSH:CP$(CP)2:3611:PIDTAG") {
  field(DESC, "Lmt Swch P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)ZSH23611")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CZSH:CP$(CP)2:3611:LIMIT_SW",2054,2119,0,1,"CZSH:CP$(CP)2:3611:LIMIT_SW")
#! Record("CZSH:CP$(CP)2:3611:PIDTAG",2054,2322,0,1,"CZSH:CP$(CP)2:3611:PIDTAG")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CZSL:CP$(CP)2:3611:LIMIT_SW") {
  field(DESC, "gate vlv closed")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) ZSL23611")
  field(ZNAM, "not closed")
  field(ONAM, "closed")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(stringin, "CZSL:CP$(CP)2:3611:PIDTAG") {
  field(DESC, "Lmt Swch P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)ZSL23611")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CZSL:CP$(CP)2:3611:LIMIT_SW",2054,2119,0,1,"CZSL:CP$(CP)2:3611:LIMIT_SW")
#! Record("CZSL:CP$(CP)2:3611:PIDTAG",2054,2322,0,1,"CZSL:CP$(CP)2:3611:PIDTAG")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CZSH:CP$(CP)2:3631:LIMIT_SW") {
  field(DESC, "gate vlv open")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) ZSH23631")
  field(ZNAM, "not open")
  field(ONAM, "open")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(stringin, "CZSH:CP$(CP)2:3631:PIDTAG") {
  field(DESC, "Lmt Swch P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)ZSH23631")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CZSH:CP$(CP)2:3631:LIMIT_SW",2054,2119,0,1,"CZSH:CP$(CP)2:3631:LIMIT_SW")
#! Record("CZSH:CP$(CP)2:3631:PIDTAG",2054,2322,0,1,"CZSH:CP$(CP)2:3631:PIDTAG")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CZSL:CP$(CP)2:3631:LIMIT_SW") {
  field(DESC, "gate vlv closed")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) ZSL23631")
  field(ZNAM, "not closed")
  field(ONAM, "closed")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(stringin, "CZSL:CP$(CP)2:3631:PIDTAG") {
  field(DESC, "Lmt Swch P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)ZSL23631")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CZSL:CP$(CP)2:3631:LIMIT_SW",2054,2119,0,1,"CZSL:CP$(CP)2:3631:LIMIT_SW")
#! Record("CZSL:CP$(CP)2:3631:PIDTAG",2054,2322,0,1,"CZSL:CP$(CP)2:3631:PIDTAG")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CTSH:CP$(CP)2:3630:LIMIT_SW") {
  field(DESC, "LCB over temp snap sw")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) TSH23630")
  field(ZNAM, "over temp")
  field(ONAM, "ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(stringin, "CTSH:CP$(CP)2:3630:PIDTAG") {
  field(DESC, "Lmt Swch P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)TSH23630")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTSH:CP$(CP)2:3630:LIMIT_SW",2054,2119,0,1,"CTSH:CP$(CP)2:3630:LIMIT_SW")
#! Record("CTSH:CP$(CP)2:3630:PIDTAG",2054,2322,0,1,"CTSH:CP$(CP)2:3630:PIDTAG")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CTSH:CP$(CP)2:3610:LIMIT_SW") {
  field(DESC, "UCB over temp snap sw")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) TSH23610")
  field(ZNAM, "over temp")
  field(ONAM, "ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(stringin, "CTSH:CP$(CP)2:3610:PIDTAG") {
  field(DESC, "Lmt Swch P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)TSH23610")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTSH:CP$(CP)2:3610:LIMIT_SW",2054,2119,0,1,"CTSH:CP$(CP)2:3610:LIMIT_SW")
#! Record("CTSH:CP$(CP)2:3610:PIDTAG",2054,2322,0,1,"CTSH:CP$(CP)2:3610:PIDTAG")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CTSH:CP$(CP)2:3631:LIMIT_SW") {
  field(DESC, "LCB pump ready switch")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) TSH23631")
  field(ZNAM, "ready")
  field(ONAM, "not ready")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(stringin, "CTSH:CP$(CP)2:3631:PIDTAG") {
  field(DESC, "Lmt Swch P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)TSH23631")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTSH:CP$(CP)2:3631:LIMIT_SW",2054,2119,0,1,"CTSH:CP$(CP)2:3631:LIMIT_SW")
#! Record("CTSH:CP$(CP)2:3631:PIDTAG",2054,2322,0,1,"CTSH:CP$(CP)2:3631:PIDTAG")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CTSH:CP$(CP)2:3611:LIMIT_SW") {
  field(DESC, "UCB pump ready switch")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) TSH23611")
  field(ZNAM, "ready")
  field(ONAM, "not ready")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

record(stringin, "CTSH:CP$(CP)2:3611:PIDTAG") {
  field(DESC, "Lmt Swch P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)TSH23611")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTSH:CP$(CP)2:3611:LIMIT_SW",2054,2119,0,1,"CTSH:CP$(CP)2:3611:LIMIT_SW")
#! Record("CTSH:CP$(CP)2:3611:PIDTAG",2054,2322,0,1,"CTSH:CP$(CP)2:3611:PIDTAG")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CTSH:CP$(CP)2:3428:LIMIT_SW") {
  field(DESC, "LCB Love 16L over temp")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) TSH23428")
  field(ZNAM, "over temp")
  field(ONAM, "ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(stringin, "CTSH:CP$(CP)2:3428:PIDTAG") {
  field(DESC, "Lmt Swch P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)TSH23428")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTSH:CP$(CP)2:3428:LIMIT_SW",2054,2119,0,1,"CTSH:CP$(CP)2:3428:LIMIT_SW")
#! Record("CTSH:CP$(CP)2:3428:PIDTAG",2054,2322,0,1,"CTSH:CP$(CP)2:3428:PIDTAG")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CTSH:CP$(CP)2:3418:LIMIT_SW") {
  field(DESC, "UCB Love 16L over temp")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) TSH23418")
  field(ZNAM, "over temp")
  field(ONAM, "ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(stringin, "CTSH:CP$(CP)2:3418:PIDTAG") {
  field(DESC, "Lmt Swch P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)TSH23418")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTSH:CP$(CP)2:3418:LIMIT_SW",2054,2119,0,1,"CTSH:CP$(CP)2:3418:LIMIT_SW")
#! Record("CTSH:CP$(CP)2:3418:PIDTAG",2054,2322,0,1,"CTSH:CP$(CP)2:3418:PIDTAG")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CFSL:CP$(CP)2:3428:LIMIT_SW") {
  field(DESC, "LCB Low clng water flow")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) FSL23428")
  field(ZNAM, "low flow")
  field(ONAM, "ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(stringin, "CFSL:CP$(CP)2:3428:PIDTAG") {
  field(DESC, "Lmt Swch P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)FSL23428")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CFSL:CP$(CP)2:3428:LIMIT_SW",2054,2119,0,1,"CFSL:CP$(CP)2:3428:LIMIT_SW")
#! Record("CFSL:CP$(CP)2:3428:PIDTAG",2054,2322,0,1,"CFSL:CP$(CP)2:3428:PIDTAG")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CFSL:CP$(CP)2:3418:LIMIT_SW") {
  field(DESC, "UCB Low clng water flow")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) FSL23418")
  field(ZNAM, "low flow")
  field(ONAM, "ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(stringin, "CFSL:CP$(CP)2:3418:PIDTAG") {
  field(DESC, "Lmt Swch P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)FSL23418")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CFSL:CP$(CP)2:3418:LIMIT_SW",2054,2119,0,1,"CFSL:CP$(CP)2:3418:LIMIT_SW")
#! Record("CFSL:CP$(CP)2:3418:PIDTAG",2054,2322,0,1,"CFSL:CP$(CP)2:3418:PIDTAG")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CPSL:CP$(CP)2:3500:LIMIT_SW") {
  field(DESC, "UCB Low inst. air press")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PSL23500")
  field(ZNAM, "low pressure")
  field(ONAM, "ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(stringin, "CPSL:CP$(CP)2:3500:PIDTAG") {
  field(DESC, "Lmt Swch P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)PSL23500")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CPSL:CP$(CP)2:3500:LIMIT_SW",2054,2119,0,1,"CPSL:CP$(CP)2:3500:LIMIT_SW")
#! Record("CPSL:CP$(CP)2:3500:PIDTAG",2054,2322,0,1,"CPSL:CP$(CP)2:3500:PIDTAG")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bi, "CPSL:CP$(CP)2:3550:LIMIT_SW") {
  field(DESC, "LCB Low inst. air press")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PSL23550")
  field(ZNAM, "low pressure")
  field(ONAM, "ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

record(stringin, "CPSL:CP$(CP)2:3550:PIDTAG") {
  field(DESC, "Lmt Swch P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)PSL23550")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CPSL:CP$(CP)2:3550:LIMIT_SW",2054,2119,0,1,"CPSL:CP$(CP)2:3550:LIMIT_SW")
#! Record("CPSL:CP$(CP)2:3550:PIDTAG",2054,2322,0,1,"CPSL:CP$(CP)2:3550:PIDTAG")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CEV:CP$(CP)2:2137:PIDTAG") {
  field(DESC, "CMD_OUT P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)EV22137")
}


record(bi, "CEV:CP$(CP)2:2137:CMD_OUT") {
  field(DESC, "T1 to ATM valve")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) EV22137")
  field(ZNAM, "close")
  field(ONAM, "open")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CEV:CP$(CP)2:2137:PIDTAG",2054,2322,0,1,"CEV:CP$(CP)2:2137:PIDTAG")
#! Record("CEV:CP$(CP)2:2137:CMD_OUT",2054,2119,0,1,"CEV:CP$(CP)2:2137:CMD_OUT")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CEV:CP$(CP)2:2157:PIDTAG") {
  field(DESC, "CMD_OUT P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)EV22157")
}


record(bi, "CEV:CP$(CP)2:2157:CMD_OUT") {
  field(DESC, "T2 to ATM valve")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) EV22157")
  field(ZNAM, "close")
  field(ONAM, "open")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CEV:CP$(CP)2:2157:PIDTAG",2054,2322,0,1,"CEV:CP$(CP)2:2157:PIDTAG")
#! Record("CEV:CP$(CP)2:2157:CMD_OUT",2054,2119,0,1,"CEV:CP$(CP)2:2157:CMD_OUT")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CEV:CP$(CP)2:2177:PIDTAG") {
  field(DESC, "CMD_OUT P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)EV22177")
}


record(bi, "CEV:CP$(CP)2:2177:CMD_OUT") {
  field(DESC, "T3 to ATM valve")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) EV22177")
  field(ZNAM, "close")
  field(ONAM, "open")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CEV:CP$(CP)2:2177:PIDTAG",2054,2322,0,1,"CEV:CP$(CP)2:2177:PIDTAG")
#! Record("CEV:CP$(CP)2:2177:CMD_OUT",2054,2119,0,1,"CEV:CP$(CP)2:2177:CMD_OUT")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CEV:CP$(CP)2:2187:PIDTAG") {
  field(DESC, "CMD_OUT P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)EV22187")
}


record(bi, "CEV:CP$(CP)2:2187:CMD_OUT") {
  field(DESC, "T4 to ATM valve")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) EV22187")
  field(ZNAM, "close")
  field(ONAM, "open")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CEV:CP$(CP)2:2187:PIDTAG",2054,2322,0,1,"CEV:CP$(CP)2:2187:PIDTAG")
#! Record("CEV:CP$(CP)2:2187:CMD_OUT",2054,2119,0,1,"CEV:CP$(CP)2:2187:CMD_OUT")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CEV:CP$(CP)2:2432:PIDTAG") {
  field(DESC, "CMD_OUT P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)EV22432")
}


record(bi, "CEV:CP$(CP)2:2432:CMD_OUT") {
  field(DESC, "T1 inlet flow booster")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) EV22432")
  field(ZNAM, "close")
  field(ONAM, "open")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CEV:CP$(CP)2:2432:PIDTAG",2054,2322,0,1,"CEV:CP$(CP)2:2432:PIDTAG")
#! Record("CEV:CP$(CP)2:2432:CMD_OUT",2054,2119,0,1,"CEV:CP$(CP)2:2432:CMD_OUT")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CEV:CP$(CP)2:2452:PIDTAG") {
  field(DESC, "CMD_OUT P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)EV22452")
}


record(bi, "CEV:CP$(CP)2:2452:CMD_OUT") {
  field(DESC, "T2 inlet flow booster")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) EV22452")
  field(ZNAM, "close")
  field(ONAM, "open")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CEV:CP$(CP)2:2452:PIDTAG",2054,2322,0,1,"CEV:CP$(CP)2:2452:PIDTAG")
#! Record("CEV:CP$(CP)2:2452:CMD_OUT",2054,2119,0,1,"CEV:CP$(CP)2:2452:CMD_OUT")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CEV:CP$(CP)2:2358:PIDTAG") {
  field(DESC, "CMD_OUT P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)EV22358")
}


record(bi, "CEV:CP$(CP)2:2358:CMD_OUT") {
  field(DESC, "T2 outlet valve")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) EV22388")
  field(ZNAM, "close")
  field(ONAM, "open")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CEV:CP$(CP)2:2358:PIDTAG",2054,2322,0,1,"CEV:CP$(CP)2:2358:PIDTAG")
#! Record("CEV:CP$(CP)2:2358:CMD_OUT",2054,2119,0,1,"CEV:CP$(CP)2:2358:CMD_OUT")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CEV:CP$(CP)2:2472:PIDTAG") {
  field(DESC, "CMD_OUT P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)EV22472")
}


record(bi, "CEV:CP$(CP)2:2472:CMD_OUT") {
  field(DESC, "T3 inlet flow booster")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) EV22472")
  field(ZNAM, "close")
  field(ONAM, "open")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CEV:CP$(CP)2:2472:PIDTAG",2054,2322,0,1,"CEV:CP$(CP)2:2472:PIDTAG")
#! Record("CEV:CP$(CP)2:2472:CMD_OUT",2054,2119,0,1,"CEV:CP$(CP)2:2472:CMD_OUT")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CEV:CP$(CP)2:2378:PIDTAG") {
  field(DESC, "CMD_OUT P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)EV22378")
}


record(bi, "CEV:CP$(CP)2:2378:CMD_OUT") {
  field(DESC, "T3 outlet valve")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) EV22378")
  field(ZNAM, "close")
  field(ONAM, "open")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CEV:CP$(CP)2:2378:PIDTAG",2054,2322,0,1,"CEV:CP$(CP)2:2378:PIDTAG")
#! Record("CEV:CP$(CP)2:2378:CMD_OUT",2054,2119,0,1,"CEV:CP$(CP)2:2378:CMD_OUT")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CEV:CP$(CP)2:2482:PIDTAG") {
  field(DESC, "CMD_OUT P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)EV22482")
}


record(bi, "CEV:CP$(CP)2:2482:CMD_OUT") {
  field(DESC, "T4 inlet flow booster")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) EV22482")
  field(ZNAM, "close")
  field(ONAM, "open")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CEV:CP$(CP)2:2482:PIDTAG",2054,2322,0,1,"CEV:CP$(CP)2:2482:PIDTAG")
#! Record("CEV:CP$(CP)2:2482:CMD_OUT",2054,2119,0,1,"CEV:CP$(CP)2:2482:CMD_OUT")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CEV:CP$(CP)2:2388:PIDTAG") {
  field(DESC, "CMD_OUT P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)EV22388")
}


record(bi, "CEV:CP$(CP)2:2388:CMD_OUT") {
  field(DESC, "T4 outlet valve")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) EV22388")
  field(ZNAM, "close")
  field(ONAM, "open")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CEV:CP$(CP)2:2388:PIDTAG",2054,2322,0,1,"CEV:CP$(CP)2:2388:PIDTAG")
#! Record("CEV:CP$(CP)2:2388:CMD_OUT",2054,2119,0,1,"CEV:CP$(CP)2:2388:CMD_OUT")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CTBN:CP$(CP)2:1:PIDTAG") {
  field(DESC, "TRIP P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)TURBINE1")
}


record(bi, "CTBN:CP$(CP)2:1:TRIP") {
  field(DESC, "T1 trip status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Turbine_CMD B 3")
  field(ZNAM, "no trip")
  field(ONAM, "trip")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTBN:CP$(CP)2:1:PIDTAG",2054,2322,0,1,"CTBN:CP$(CP)2:1:PIDTAG")
#! Record("CTBN:CP$(CP)2:1:TRIP",2054,2119,0,1,"CTBN:CP$(CP)2:1:TRIP")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CTBN:CP$(CP)2:2:PIDTAG") {
  field(DESC, "TRIP P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)TURBINE2")
}


record(bi, "CTBN:CP$(CP)2:2:TRIP") {
  field(DESC, "T2 trip status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Turbine_CMD B 7")
  field(ZNAM, "no trip")
  field(ONAM, "trip")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTBN:CP$(CP)2:2:PIDTAG",2054,2322,0,1,"CTBN:CP$(CP)2:2:PIDTAG")
#! Record("CTBN:CP$(CP)2:2:TRIP",2054,2119,0,1,"CTBN:CP$(CP)2:2:TRIP")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CTBN:CP$(CP)2:3:PIDTAG") {
  field(DESC, "TRIP P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)TURBINE3")
}


record(bi, "CTBN:CP$(CP)2:3:TRIP") {
  field(DESC, "T3 trip status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Turbine_CMD B 11")
  field(ZNAM, "no trip")
  field(ONAM, "trip")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTBN:CP$(CP)2:3:PIDTAG",2054,2322,0,1,"CTBN:CP$(CP)2:3:PIDTAG")
#! Record("CTBN:CP$(CP)2:3:TRIP",2054,2119,0,1,"CTBN:CP$(CP)2:3:TRIP")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CTBN:CP$(CP)2:4:PIDTAG") {
  field(DESC, "TRIP P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)TURBINE4")
}


record(bi, "CTBN:CP$(CP)2:4:TRIP") {
  field(DESC, "T4 trip status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Turbine_CMD B 15")
  field(ZNAM, "no trip")
  field(ONAM, "trip")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTBN:CP$(CP)2:4:PIDTAG",2054,2322,0,1,"CTBN:CP$(CP)2:4:PIDTAG")
#! Record("CTBN:CP$(CP)2:4:TRIP",2054,2119,0,1,"CTBN:CP$(CP)2:4:TRIP")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CCBX:CP$(CP)2:0:PIDTAG") {
  field(DESC, "RL_PERM P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)CBXRETURN")
}


record(bi, "CCBX:CP$(CP)2:0:RL_PERM") {
  field(DESC, "return line perm. status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) ReturnLinePerm")
  field(ZNAM, "permissive off")
  field(ONAM, "permissive on")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CCBX:CP$(CP)2:0:PIDTAG",2054,2322,0,1,"CCBX:CP$(CP)2:0:PIDTAG")
#! Record("CCBX:CP$(CP)2:0:RL_PERM",2054,2119,0,1,"CCBX:CP$(CP)2:0:RL_PERM")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CHTR:CP$(CP)2:2418:A:PIDTAG") {
  field(DESC, "STATUS P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)HTR22418A")
}


record(bi, "CHTR:CP$(CP)2:2418:A:STATUS") {
  field(DESC, "80K bed A heater status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) EHTR22418AR")
  field(ZNAM, "off")
  field(ONAM, "on")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CHTR:CP$(CP)2:2418:A:PIDTAG",2054,2322,0,1,"CHTR:CP$(CP)2:2418:A:PIDTAG")
#! Record("CHTR:CP$(CP)2:2418:A:STATUS",2054,2119,0,1,"CHTR:CP$(CP)2:2418:A:STATUS")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CHTR:CP$(CP)2:2418:B:PIDTAG") {
  field(DESC, "STATUS P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)HTR22418B")
}


record(bi, "CHTR:CP$(CP)2:2418:B:STATUS") {
  field(DESC, "80K bed B heater status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) EHTR22418BR")
  field(ZNAM, "off")
  field(ONAM, "on")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CHTR:CP$(CP)2:2418:B:PIDTAG",2054,2322,0,1,"CHTR:CP$(CP)2:2418:B:PIDTAG")
#! Record("CHTR:CP$(CP)2:2418:B:STATUS",2054,2119,0,1,"CHTR:CP$(CP)2:2418:B:STATUS")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CHTR:CP$(CP)2:2465:PIDTAG") {
  field(DESC, "STATUS P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)HTR22465")
}


record(bi, "CHTR:CP$(CP)2:2465:STATUS") {
  field(DESC, "20K bed heater status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) EHTR22465R")
  field(ZNAM, "off")
  field(ONAM, "on")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CHTR:CP$(CP)2:2465:PIDTAG",2054,2322,0,1,"CHTR:CP$(CP)2:2465:PIDTAG")
#! Record("CHTR:CP$(CP)2:2465:STATUS",2054,2119,0,1,"CHTR:CP$(CP)2:2465:STATUS")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CHTR:CP$(CP)2:2195:PIDTAG") {
  field(DESC, "STATUS P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)HTR22195")
}


record(bi, "CHTR:CP$(CP)2:2195:STATUS") {
  field(DESC, "subcooler heater status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) EHTR22195R")
  field(ZNAM, "off")
  field(ONAM, "on")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CHTR:CP$(CP)2:2195:PIDTAG",2054,2322,0,1,"CHTR:CP$(CP)2:2195:PIDTAG")
#! Record("CHTR:CP$(CP)2:2195:STATUS",2054,2119,0,1,"CHTR:CP$(CP)2:2195:STATUS")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CHTR:CP$(CP)3:1000:PIDTAG") {
  field(DESC, "STATUS P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)HTR31000")
}


record(bi, "CHTR:CP$(CP)3:1000:STATUS") {
  field(DESC, "dewar heater status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) EHTR31000R")
  field(ZNAM, "off")
  field(ONAM, "on")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CHTR:CP$(CP)3:1000:PIDTAG",2054,2322,0,1,"CHTR:CP$(CP)3:1000:PIDTAG")
#! Record("CHTR:CP$(CP)3:1000:STATUS",2054,2119,0,1,"CHTR:CP$(CP)3:1000:STATUS")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CHTR:CP$(CP)2:2191:PIDTAG") {
  field(DESC, "STATUS P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)HTR22191")
}


record(bi, "CHTR:CP$(CP)2:2191:STATUS") {
  field(DESC, "LTTI test htr status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) EHTR22191R")
  field(ZNAM, "off")
  field(ONAM, "on")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CHTR:CP$(CP)2:2191:PIDTAG",2054,2322,0,1,"CHTR:CP$(CP)2:2191:PIDTAG")
#! Record("CHTR:CP$(CP)2:2191:STATUS",2054,2119,0,1,"CHTR:CP$(CP)2:2191:STATUS")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CHTR:CP$(CP)2:2190:PIDTAG") {
  field(DESC, "STATUS P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)HTR22190")
}


record(bi, "CHTR:CP$(CP)2:2190:STATUS") {
  field(DESC, "Sub Atm test htr status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) EHTR22190R")
  field(ZNAM, "off")
  field(ONAM, "on")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CHTR:CP$(CP)2:2190:PIDTAG",2054,2322,0,1,"CHTR:CP$(CP)2:2190:PIDTAG")
#! Record("CHTR:CP$(CP)2:2190:STATUS",2054,2119,0,1,"CHTR:CP$(CP)2:2190:STATUS")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CHTR:CP$(CP)2:2240:PIDTAG") {
  field(DESC, "STATUS P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)HTR22240")
}


record(bi, "CHTR:CP$(CP)2:2240:STATUS") {
  field(DESC, "HTTS test htr status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) EHTR22240R")
  field(ZNAM, "off")
  field(ONAM, "on")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CHTR:CP$(CP)2:2240:PIDTAG",2054,2322,0,1,"CHTR:CP$(CP)2:2240:PIDTAG")
#! Record("CHTR:CP$(CP)2:2240:STATUS",2054,2119,0,1,"CHTR:CP$(CP)2:2240:STATUS")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CVP:CP$(CP)2:3610:PIDTAG") {
  field(DESC, "STATUS P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)VP23610")
}


record(bi, "CVP:CP$(CP)2:3610:STATUS") {
  field(DESC, "UCB rphg pump status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) VP23610R")
  field(ZNAM, "off")
  field(ONAM, "on")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CVP:CP$(CP)2:3610:PIDTAG",2054,2322,0,1,"CVP:CP$(CP)2:3610:PIDTAG")
#! Record("CVP:CP$(CP)2:3610:STATUS",2054,2119,0,1,"CVP:CP$(CP)2:3610:STATUS")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CVP:CP$(CP)2:3630:PIDTAG") {
  field(DESC, "STATUS P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)VP23630")
}


record(bi, "CVP:CP$(CP)2:3630:STATUS") {
  field(DESC, "LCB rphg pump status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) VP23630R")
  field(ZNAM, "off")
  field(ONAM, "on")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CVP:CP$(CP)2:3630:PIDTAG",2054,2322,0,1,"CVP:CP$(CP)2:3630:PIDTAG")
#! Record("CVP:CP$(CP)2:3630:STATUS",2054,2119,0,1,"CVP:CP$(CP)2:3630:STATUS")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CDP:CP$(CP)2:3610:PIDTAG") {
  field(DESC, "STATUS P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)DP23610")
}


record(bi, "CDP:CP$(CP)2:3610:STATUS") {
  field(DESC, "UCB diff. pump status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) DP23610R")
  field(ZNAM, "on")
  field(ONAM, "off")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CDP:CP$(CP)2:3610:PIDTAG",2054,2322,0,1,"CDP:CP$(CP)2:3610:PIDTAG")
#! Record("CDP:CP$(CP)2:3610:STATUS",2054,2119,0,1,"CDP:CP$(CP)2:3610:STATUS")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CDP:CP$(CP)2:3630:PIDTAG") {
  field(DESC, "STATUS P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)DP23630")
}


record(bi, "CDP:CP$(CP)2:3630:STATUS") {
  field(DESC, "LCB diff. pump status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) DP23630R")
  field(ZNAM, "on")
  field(ONAM, "off")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CDP:CP$(CP)2:3630:PIDTAG",2054,2322,0,1,"CDP:CP$(CP)2:3630:PIDTAG")
#! Record("CDP:CP$(CP)2:3630:STATUS",2054,2119,0,1,"CDP:CP$(CP)2:3630:STATUS")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CVAC:CP$(CP)2:3610:PIDTAG") {
  field(DESC, "TRIP P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)UCB_VAC")
}


record(bi, "CVAC:CP$(CP)2:3610:TRIP") {
  field(DESC, "UCB Vacuum trip status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) VAC_CMD B 2")
  field(ZNAM, "no trip")
  field(ONAM, "trip")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CVAC:CP$(CP)2:3610:PIDTAG",2054,2322,0,1,"CVAC:CP$(CP)2:3610:PIDTAG")
#! Record("CVAC:CP$(CP)2:3610:TRIP",2054,2119,0,1,"CVAC:CP$(CP)2:3610:TRIP")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CVAC:CP$(CP)2:3630:PIDTAG") {
  field(DESC, "TRIP P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)LCB_VAC")
}


record(bi, "CVAC:CP$(CP)2:3630:TRIP") {
  field(DESC, "LCB Vacuum trip status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) VAC_CMD B 12")
  field(ZNAM, "no trip")
  field(ONAM, "trip")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CVAC:CP$(CP)2:3630:PIDTAG",2054,2322,0,1,"CVAC:CP$(CP)2:3630:PIDTAG")
#! Record("CVAC:CP$(CP)2:3630:TRIP",2054,2119,0,1,"CVAC:CP$(CP)2:3630:TRIP")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CCBX:CP$(CP)2:0:PIDTAG") {
  field(DESC, "CD_LOGIC_STATUS P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)CBX")
}


record(bi, "CCBX:CP$(CP)2:0:CD_LOGIC_STATUS") {
  field(DESC, "Cooldown logic status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) CD_Logic_Active")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CCBX:CP$(CP)2:0:PIDTAG",2054,2322,0,1,"CCBX:CP$(CP)2:0:PIDTAG")
#! Record("CCBX:CP$(CP)2:0:CD_LOGIC_STATUS",2054,2119,0,1,"CCBX:CP$(CP)2:0:CD_LOGIC_STATUS")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CCBX:CP$(CP)2:0:PIDTAG") {
  field(DESC, "CD_SUBATM_MODE P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)CBX")
}


record(bi, "CCBX:CP$(CP)2:0:CD_SUBATM_MODE") {
  field(DESC, "Cooldown subatmospheric mode")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) CD_Nominal_Logic")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CCBX:CP$(CP)2:0:PIDTAG",2054,2322,0,1,"CCBX:CP$(CP)2:0:PIDTAG")
#! Record("CCBX:CP$(CP)2:0:CD_SUBATM_MODE",2054,2119,0,1,"CCBX:CP$(CP)2:0:CD_SUBATM_MODE")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CCBX:CP$(CP)2:0:PIDTAG") {
  field(DESC, "CD_TRANS_MODE P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)CBX")
}


record(bi, "CCBX:CP$(CP)2:0:CD_TRANS_MODE") {
  field(DESC, "Cooldown transient mode")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) CD_Transient_Logic")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CCBX:CP$(CP)2:0:PIDTAG",2054,2322,0,1,"CCBX:CP$(CP)2:0:PIDTAG")
#! Record("CCBX:CP$(CP)2:0:CD_TRANS_MODE",2054,2119,0,1,"CCBX:CP$(CP)2:0:CD_TRANS_MODE")
#! Generated by VisualDCT v2.6.1280
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(stringin, "CCBX:CP$(CP)2:0:PIDTAG") {
  field(DESC, "WS_LOGIC_STATUS P&IDname")
  field(PINI, "YES")
  field(VAL, "C$(CP)CBX")
}


record(bi, "CCBX:CP$(CP)2:0:WS_LOGIC_STATUS") {
  field(DESC, "WrmShld vlv rtn logic status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) WarmShld_Logic_Active")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CCBX:CP$(CP)2:0:PIDTAG",2054,2322,0,1,"CCBX:CP$(CP)2:0:PIDTAG")
#! Record("CCBX:CP$(CP)2:0:WS_LOGIC_STATUS",2054,2119,0,1,"CCBX:CP$(CP)2:0:WS_LOGIC_STATUS")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CHTR:CP$(CP)2:2418:A:CMD_OUT") {
  field(DESC, "80K bed A heater cmd")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) EHTR22418ACMD")
  field(ZNAM, "off")
  field(ONAM, "on")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CHTR:CP$(CP)2:2418:A:CMD_OUT",2060,2137,0,1,"CHTR:CP$(CP)2:2418:A:CMD_OUT")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CHTR:CP$(CP)2:2418:B:CMD_OUT") {
  field(DESC, "80K bed B heater cmd")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) EHTR22418BCMD")
  field(ZNAM, "off")
  field(ONAM, "on")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CHTR:CP$(CP)2:2418:B:CMD_OUT",2060,2137,0,1,"CHTR:CP$(CP)2:2418:B:CMD_OUT")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CHTR:CP$(CP)2:2465:CMD_OUT") {
  field(DESC, "20K bed heater cmd")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) EHTR22465CMD")
  field(ZNAM, "off")
  field(ONAM, "on")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CHTR:CP$(CP)2:2465:CMD_OUT",2060,2137,0,1,"CHTR:CP$(CP)2:2465:CMD_OUT")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CHTR:CP$(CP)2:2195:CMD_OUT") {
  field(DESC, "subcooler heater cmd")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) EHTR22195CMD")
  field(ZNAM, "off")
  field(ONAM, "on")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CHTR:CP$(CP)2:2195:CMD_OUT",2060,2137,0,1,"CHTR:CP$(CP)2:2195:CMD_OUT")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CHTR:CP$(CP)3:1000:CMD_OUT") {
  field(DESC, "dewar heater cmd")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) EHTR31000CMD")
  field(ZNAM, "off")
  field(ONAM, "on")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CHTR:CP$(CP)3:1000:CMD_OUT",2060,2137,0,1,"CHTR:CP$(CP)3:1000:CMD_OUT")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CHTR:CP$(CP)2:2191:CMD_OUT") {
  field(DESC, "LTTI test heater cmd")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) EHTR22191CMD")
  field(ZNAM, "off")
  field(ONAM, "on")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CHTR:CP$(CP)2:2191:CMD_OUT",2060,2137,0,1,"CHTR:CP$(CP)2:2191:CMD_OUT")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CHTR:CP$(CP)2:2190:CMD_OUT") {
  field(DESC, "Sub Atm test heater cmd")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) EHTR22190CMD")
  field(ZNAM, "off")
  field(ONAM, "on")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CHTR:CP$(CP)2:2190:CMD_OUT",2060,2137,0,1,"CHTR:CP$(CP)2:2190:CMD_OUT")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CHTR:CP$(CP)2:2240:CMD_OUT") {
  field(DESC, "HTTS test heater cmd")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) EHTR22240CMD")
  field(ZNAM, "off")
  field(ONAM, "on")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CHTR:CP$(CP)2:2240:CMD_OUT",2060,2137,0,1,"CHTR:CP$(CP)2:2240:CMD_OUT")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CCBX:CP$(CP)2:0:EN_80KBEDA") {
  field(DESC, "80K Bed A enble/dsble cmd")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) CBX_CMD B 7")
  field(ZNAM, "disabled")
  field(ONAM, "enabled")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CCBX:CP$(CP)2:0:EN_80KBEDA",2060,2137,0,1,"CCBX:CP$(CP)2:0:EN_80KBEDA")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CCBX:CP$(CP)2:0:EN_80KBEDB") {
  field(DESC, "80K Bed B enble/disble cmd")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) CBX_CMD B 9")
  field(ZNAM, "disabled")
  field(ONAM, "enabled")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CCBX:CP$(CP)2:0:EN_80KBEDB",2060,2137,0,1,"CCBX:CP$(CP)2:0:EN_80KBEDB")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CCBX:CP$(CP)2:0:EN_20KBED") {
  field(DESC, "20K Bed enable/disable cmd")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) CBX_CMD B 11")
  field(ZNAM, "disabled")
  field(ONAM, "enabled")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CCBX:CP$(CP)2:0:EN_20KBED",2060,2137,0,1,"CCBX:CP$(CP)2:0:EN_20KBED")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CCBX:CP$(CP)2:0:LN2AUTH") {
  field(DESC, "LN2 authorize cmd")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) LN2Auth B 0")
  field(ZNAM, "PUSH to allow")
  field(ONAM, "Authorized")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CCBX:CP$(CP)2:0:LN2AUTH",2060,2137,0,1,"CCBX:CP$(CP)2:0:LN2AUTH")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CPV:CP$(CP)2:2405:CMD") {
  field(DESC, "Bearing Gas cmd")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) PV22405.CMD B 0")
  field(ZNAM, "PUSH to Start")
  field(ONAM, "ON")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CPV:CP$(CP)2:2405:CMD",2060,2137,0,1,"CPV:CP$(CP)2:2405:CMD")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CTBN:CP$(CP)2:1:AUTH") {
  field(DESC, "T1 authorize cmd")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) Turbine_CMD B 4")
  field(ZNAM, "PUSH to authorize T1")
  field(ONAM, "T1 Authorized")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTBN:CP$(CP)2:1:AUTH",2060,2137,0,1,"CTBN:CP$(CP)2:1:AUTH")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CTBN:CP$(CP)2:2:AUTH") {
  field(DESC, "T2 authorize cmd")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) Turbine_CMD B 8")
  field(ZNAM, "PUSH to authorize T2")
  field(ONAM, "T2 Authorized")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTBN:CP$(CP)2:2:AUTH",2060,2137,0,1,"CTBN:CP$(CP)2:2:AUTH")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CTBN:CP$(CP)2:3:AUTH") {
  field(DESC, "T3 authorize cmd")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) Turbine_CMD B 12")
  field(ZNAM, "PUSH to authorize T3")
  field(ONAM, "T3 Authorized")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTBN:CP$(CP)2:3:AUTH",2060,2137,0,1,"CTBN:CP$(CP)2:3:AUTH")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CTBN:CP$(CP)2:4:AUTH") {
  field(DESC, "T4 authorize cmd")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) Turbine_CMD B 16")
  field(ZNAM, "PUSH to authorize T4")
  field(ONAM, "T4 Authorized")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
  field(ASG, "CRYO")
  field(HIGH, "0")
  field(IVOA, "Don't drive outputs")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTBN:CP$(CP)2:4:AUTH",2060,2137,0,1,"CTBN:CP$(CP)2:4:AUTH")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CPV:CP$(CP)2:2421:IL_RESET") {
  field(DESC, "80K adsbr bypass valve")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) PV22421IR B 0")
  field(ZNAM, "no reset")
  field(ONAM, "reset")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
  field(ASG, "CRYO")
  field(HIGH, "1")
  field(IVOA, "Don't drive outputs")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CPV:CP$(CP)2:2421:IL_RESET",2060,2137,0,1,"CPV:CP$(CP)2:2421:IL_RESET")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CHTR:CP$(CP)2:2418:A:IL_RESET") {
  field(DESC, "80K Bed htrA IL reset")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) EHTR22418AIR B 0")
  field(ZNAM, "no reset")
  field(ONAM, "reset")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
  field(ASG, "CRYO")
  field(HIGH, "1")
  field(IVOA, "Don't drive outputs")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CHTR:CP$(CP)2:2418:A:IL_RESET",2060,2137,0,1,"CHTR:CP$(CP)2:2418:A:IL_RESET")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CHTR:CP$(CP)2:2418:B:IL_RESET") {
  field(DESC, "80K Bed htrB IL reset")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) EHTR22418BIR B 0")
  field(ZNAM, "no reset")
  field(ONAM, "reset")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
  field(ASG, "CRYO")
  field(HIGH, "1")
  field(IVOA, "Don't drive outputs")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CHTR:CP$(CP)2:2418:B:IL_RESET",2060,2137,0,1,"CHTR:CP$(CP)2:2418:B:IL_RESET")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CHTR:CP$(CP)2:2465:IL_RESET") {
  field(DESC, "20K Bed htr IL reset")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) EHTR22465IR B 0")
  field(ZNAM, "no reset")
  field(ONAM, "reset")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
  field(ASG, "CRYO")
  field(HIGH, "1")
  field(IVOA, "Don't drive outputs")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CHTR:CP$(CP)2:2465:IL_RESET",2060,2137,0,1,"CHTR:CP$(CP)2:2465:IL_RESET")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CPV:CP$(CP)2:2460:IL_RESET") {
  field(DESC, "20K adsbr bypass valve")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) PV22460IR B 0")
  field(ZNAM, "no reset")
  field(ONAM, "reset")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
  field(ASG, "CRYO")
  field(HIGH, "1")
  field(IVOA, "Don't drive outputs")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CPV:CP$(CP)2:2460:IL_RESET",2060,2137,0,1,"CPV:CP$(CP)2:2460:IL_RESET")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CHTR:CP$(CP)2:2195:IL_RESET") {
  field(DESC, "subcooler htr IL reset")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) EHTR22195IR B 0")
  field(ZNAM, "no reset")
  field(ONAM, "reset")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
  field(ASG, "CRYO")
  field(HIGH, "1")
  field(IVOA, "Don't drive outputs")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CHTR:CP$(CP)2:2195:IL_RESET",2060,2137,0,1,"CHTR:CP$(CP)2:2195:IL_RESET")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CHTR:CP$(CP)3:1000:IL_RESET") {
  field(DESC, "dewar htr IL reset")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) EHTR31000IR B 0")
  field(ZNAM, "no reset")
  field(ONAM, "reset")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
  field(ASG, "CRYO")
  field(HIGH, "1")
  field(IVOA, "Don't drive outputs")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CHTR:CP$(CP)3:1000:IL_RESET",2060,2137,0,1,"CHTR:CP$(CP)3:1000:IL_RESET")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CPSL:CP$(CP)2:3500:TRLO_RESET") {
  field(DESC, "TripLo reset")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) PSL23500TripLoR B 0")
  field(ZNAM, "no reset")
  field(ONAM, "reset")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
  field(ASG, "CRYO")
  field(HIGH, "1")
  field(IVOA, "Don't drive outputs")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CPSL:CP$(CP)2:3500:TRLO_RESET",2060,2137,0,1,"CPSL:CP$(CP)2:3500:TRLO_RESET")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CPSL:CP$(CP)2:3550:TRLO_RESET") {
  field(DESC, "TripLo reset")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) PSL23550TripLoR B 0")
  field(ZNAM, "no reset")
  field(ONAM, "reset")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
  field(ASG, "CRYO")
  field(HIGH, "1")
  field(IVOA, "Don't drive outputs")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CPSL:CP$(CP)2:3550:TRLO_RESET",2060,2137,0,1,"CPSL:CP$(CP)2:3550:TRLO_RESET")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CTDT:CP$(CP)2:2400:NTRHI_RESET") {
  field(DESC, "NTripHi reset")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) TDT22400NTripHiR B 0")
  field(ZNAM, "no reset")
  field(ONAM, "reset")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
  field(ASG, "CRYO")
  field(HIGH, "1")
  field(IVOA, "Don't drive outputs")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTDT:CP$(CP)2:2400:NTRHI_RESET",2060,2137,0,1,"CTDT:CP$(CP)2:2400:NTRHI_RESET")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CTDT:CP$(CP)2:2400:MTRHI_RESET") {
  field(DESC, "MTripHi reset")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) TDT22400MTripHiR B 0")
  field(ZNAM, "no reset")
  field(ONAM, "reset")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
  field(ASG, "CRYO")
  field(HIGH, "1")
  field(IVOA, "Don't drive outputs")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTDT:CP$(CP)2:2400:MTRHI_RESET",2060,2137,0,1,"CTDT:CP$(CP)2:2400:MTRHI_RESET")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CTDT:CP$(CP)2:2400:LTRHI_RESET") {
  field(DESC, "LTripHi reset")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) TDT22400LTripHiR B 0")
  field(ZNAM, "no reset")
  field(ONAM, "reset")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
  field(ASG, "CRYO")
  field(HIGH, "1")
  field(IVOA, "Don't drive outputs")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTDT:CP$(CP)2:2400:LTRHI_RESET",2060,2137,0,1,"CTDT:CP$(CP)2:2400:LTRHI_RESET")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CTDT:CP$(CP)2:2412:NTRHI_RESET") {
  field(DESC, "NTripHi reset")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) TDT22412NTripHiR B 0")
  field(ZNAM, "no reset")
  field(ONAM, "reset")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
  field(ASG, "CRYO")
  field(HIGH, "1")
  field(IVOA, "Don't drive outputs")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTDT:CP$(CP)2:2412:NTRHI_RESET",2060,2137,0,1,"CTDT:CP$(CP)2:2412:NTRHI_RESET")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CTDT:CP$(CP)2:2412:MTRHI_RESET") {
  field(DESC, "MTripHi reset")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) TDT22412MTripHiR B 0")
  field(ZNAM, "no reset")
  field(ONAM, "reset")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
  field(ASG, "CRYO")
  field(HIGH, "1")
  field(IVOA, "Don't drive outputs")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTDT:CP$(CP)2:2412:MTRHI_RESET",2060,2137,0,1,"CTDT:CP$(CP)2:2412:MTRHI_RESET")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CTDT:CP$(CP)2:2411:LTRHI_RESET") {
  field(DESC, "LTripHi reset")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) TDT22411LTripHiR B 0")
  field(ZNAM, "no reset")
  field(ONAM, "reset")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
  field(ASG, "CRYO")
  field(HIGH, "1")
  field(IVOA, "Don't drive outputs")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTDT:CP$(CP)2:2411:LTRHI_RESET",2060,2137,0,1,"CTDT:CP$(CP)2:2411:LTRHI_RESET")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CTT:CP$(CP)2:2413:TRHI_RESET") {
  field(DESC, "TripHi reset")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) TT22413TripHiR B 0")
  field(ZNAM, "no reset")
  field(ONAM, "reset")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
  field(ASG, "CRYO")
  field(HIGH, "1")
  field(IVOA, "Don't drive outputs")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTT:CP$(CP)2:2413:TRHI_RESET",2060,2137,0,1,"CTT:CP$(CP)2:2413:TRHI_RESET")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoControl.dbd")
#! DBDEND


record(bo, "CTDT:CP$(CP)2:2393:TRHI_RESET") {
  field(DESC, "TripHi reset")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(OMSL, "supervisory")
  field(OUT, "@$(PLC_NAME) TDT22393TripHiR B 0")
  field(ZNAM, "no reset")
  field(ONAM, "reset")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
  field(ASG, "CRYO")
  field(HIGH, "1")
  field(IVOA, "Don't drive outputs")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTDT:CP$(CP)2:2393:TRHI_RESET",2060,2137,0,1,"CTDT:CP$(CP)2:2393:TRHI_RESET")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(stringin, "CTBN:CP$(CP)2:1:SD_STRING") {
  field(DESC, "T1 shutdown string")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) T1_SD_String")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("CTBN:CP$(CP)2:1:SD_STRING",340,94,0,0,"CTBN:CP$(CP)2:1:SD_STRING")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(stringin, "CTBN:CP$(CP)2:2:SD_STRING") {
  field(DESC, "T2 shutdown string")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) T2_SD_String")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("CTBN:CP$(CP)2:2:SD_STRING",340,94,0,0,"CTBN:CP$(CP)2:2:SD_STRING")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(stringin, "CTBN:CP$(CP)2:3:SD_STRING") {
  field(DESC, "T3 shutdown string")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) T3_SD_String")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("CTBN:CP$(CP)2:3:SD_STRING",340,94,0,0,"CTBN:CP$(CP)2:3:SD_STRING")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(stringin, "CTBN:CP$(CP)2:4:SD_STRING") {
  field(DESC, "T4 shutdown string")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) T4_SD_String")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("CTBN:CP$(CP)2:4:SD_STRING",340,94,0,0,"CTBN:CP$(CP)2:4:SD_STRING")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(stringin, "CCBX:CP$(CP)2:0:CD_TRIP_STR") {
  field(DESC, "Cooldown trip string")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) CD_Trip_String")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("CCBX:CP$(CP)2:0:CD_TRIP_STR",340,94,0,0,"CCBX:CP$(CP)2:0:CD_TRIP_STR")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(stringin, "CVAC:CP$(CP)2:3610:VACTRIP_STR") {
  field(DESC, "UCB vac trip string")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) UCB_Vac_Trip_String")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("CVAC:CP$(CP)2:3610:VACTRIP_STR",340,94,0,0,"CVAC:CP$(CP)2:3610:VACTRIP_STR")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(stringin, "CVAC:CP$(CP)2:3630:VACTRIP_STR") {
  field(DESC, "LCB vac trip string")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) LCB_Vac_Trip_String")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("CVAC:CP$(CP)2:3630:VACTRIP_STR",340,94,0,0,"CVAC:CP$(CP)2:3630:VACTRIP_STR")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(ao, "CTBN:CP$(CP)2:1:ATFT_MIN") {
  field(DESC, "Brake Temp Attenuator Min")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T1_ATFT_ATmin")
  field(PREC, "2")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:1:ATFT_MAX") {
  field(DESC, "Brake Temp Attenuator Max")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T1_ATFT_ATmax")
  field(PREC, "2")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:1:ATFT1") {
  field(DESC, "Brake Temp Attenuator FT1")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T1_ATFT_FT1")
  field(PREC, "2")
  field(EGU, "K")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:1:ATFT2") {
  field(DESC, "Brake Temp Attenuator FT2")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T1_ATFT_FT2")
  field(PREC, "2")
  field(EGU, "K")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}


record(ai, "CTBN:CP$(CP)2:1:ATFT") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) T1_Attenuate[1]")
  field(EGUF, "10")
  field(DESC, "Brake Temp Attenuator")
  field(PREC, "2")
  field(ADEL, "0.01")
  field(MDEL, "0.01")
  field(PINI, "YES")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTBN:CP$(CP)2:1:ATFT_MIN",2120,2206,0,1,"CTBN:CP$(CP)2:1:ATFT_MIN")
#! Record("CTBN:CP$(CP)2:1:ATFT_MAX",2299,2206,0,1,"CTBN:CP$(CP)2:1:ATFT_MAX")
#! Record("CTBN:CP$(CP)2:1:ATFT1",2480,2192,0,1,"CTBN:CP$(CP)2:1:ATFT1")
#! Record("CTBN:CP$(CP)2:1:ATFT2",2660,2192,0,1,"CTBN:CP$(CP)2:1:ATFT2")
#! TextBox(TB0,2340,2140,2640,2180,0,"Dialog",12,1,16777215,"Turbine Brake Temperature Attenuator",null)
#! Record("CTBN:CP$(CP)2:1:ATFT",2120,2379,0,1,"CTBN:CP$(CP)2:1:ATFT")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(ao, "CTBN:CP$(CP)2:2:ATFT_MIN") {
  field(DESC, "Brake Temp Attenuator Min")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T2_ATFT_ATmin")
  field(PREC, "2")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:2:ATFT_MAX") {
  field(DESC, "Brake Temp Attenuator Max")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T2_ATFT_ATmax")
  field(PREC, "2")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:2:ATFT1") {
  field(DESC, "Brake Temp Attenuator FT1")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T2_ATFT_FT1")
  field(PREC, "2")
  field(EGU, "K")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:2:ATFT2") {
  field(DESC, "Brake Temp Attenuator FT2")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T2_ATFT_FT2")
  field(PREC, "2")
  field(EGU, "K")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}


record(ai, "CTBN:CP$(CP)2:2:ATFT") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) T2_Attenuate[1]")
  field(EGUF, "10")
  field(DESC, "Brake Temp Attenuator")
  field(PREC, "2")
  field(ADEL, "0.01")
  field(MDEL, "0.01")
  field(PINI, "YES")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTBN:CP$(CP)2:2:ATFT_MIN",2120,2206,0,1,"CTBN:CP$(CP)2:2:ATFT_MIN")
#! Record("CTBN:CP$(CP)2:2:ATFT_MAX",2299,2206,0,1,"CTBN:CP$(CP)2:2:ATFT_MAX")
#! Record("CTBN:CP$(CP)2:2:ATFT1",2480,2192,0,1,"CTBN:CP$(CP)2:2:ATFT1")
#! Record("CTBN:CP$(CP)2:2:ATFT2",2660,2192,0,1,"CTBN:CP$(CP)2:2:ATFT2")
#! TextBox(TB0,2340,2140,2640,2180,0,"Dialog",12,1,16777215,"Turbine Brake Temperature Attenuator",null)
#! Record("CTBN:CP$(CP)2:2:ATFT",2120,2379,0,1,"CTBN:CP$(CP)2:2:ATFT")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(ao, "CTBN:CP$(CP)2:3:ATFT_MIN") {
  field(DESC, "Brake Temp Attenuator Min")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T3_ATFT_ATmin")
  field(PREC, "2")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:3:ATFT_MAX") {
  field(DESC, "Brake Temp Attenuator Max")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T3_ATFT_ATmax")
  field(PREC, "2")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:3:ATFT1") {
  field(DESC, "Brake Temp Attenuator FT1")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T3_ATFT_FT1")
  field(PREC, "2")
  field(EGU, "K")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:3:ATFT2") {
  field(DESC, "Brake Temp Attenuator FT2")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T3_ATFT_FT2")
  field(PREC, "2")
  field(EGU, "K")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}


record(ai, "CTBN:CP$(CP)2:3:ATFT") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) T3_Attenuate[1]")
  field(EGUF, "10")
  field(DESC, "Brake Temp Attenuator")
  field(PREC, "2")
  field(ADEL, "0.01")
  field(MDEL, "0.01")
  field(PINI, "YES")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTBN:CP$(CP)2:3:ATFT_MIN",2120,2206,0,1,"CTBN:CP$(CP)2:3:ATFT_MIN")
#! Record("CTBN:CP$(CP)2:3:ATFT_MAX",2299,2206,0,1,"CTBN:CP$(CP)2:3:ATFT_MAX")
#! Record("CTBN:CP$(CP)2:3:ATFT1",2480,2192,0,1,"CTBN:CP$(CP)2:3:ATFT1")
#! Record("CTBN:CP$(CP)2:3:ATFT2",2660,2192,0,1,"CTBN:CP$(CP)2:3:ATFT2")
#! TextBox(TB0,2340,2140,2640,2180,0,"Dialog",12,1,16777215,"Turbine Brake Temperature Attenuator",null)
#! Record("CTBN:CP$(CP)2:3:ATFT",2120,2379,0,1,"CTBN:CP$(CP)2:3:ATFT")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(ao, "CTBN:CP$(CP)2:4:ATFT_MIN") {
  field(DESC, "Brake Temp Attenuator Min")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T4_ATFT_ATmin")
  field(PREC, "2")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:4:ATFT_MAX") {
  field(DESC, "Brake Temp Attenuator Max")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T4_ATFT_ATmax")
  field(PREC, "2")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:4:ATFT1") {
  field(DESC, "Brake Temp Attenuator FT1")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T4_ATFT_FT1")
  field(PREC, "2")
  field(EGU, "K")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:4:ATFT2") {
  field(DESC, "Brake Temp Attenuator FT2")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T4_ATFT_FT2")
  field(PREC, "2")
  field(EGU, "K")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}


record(ai, "CTBN:CP$(CP)2:4:ATFT") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) T4_Attenuate[1]")
  field(EGUF, "10")
  field(DESC, "Brake Temp Attenuator")
  field(PREC, "2")
  field(ADEL, "0.01")
  field(MDEL, "0.01")
  field(PINI, "YES")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTBN:CP$(CP)2:4:ATFT_MIN",2120,2206,0,1,"CTBN:CP$(CP)2:4:ATFT_MIN")
#! Record("CTBN:CP$(CP)2:4:ATFT_MAX",2299,2206,0,1,"CTBN:CP$(CP)2:4:ATFT_MAX")
#! Record("CTBN:CP$(CP)2:4:ATFT1",2480,2192,0,1,"CTBN:CP$(CP)2:4:ATFT1")
#! Record("CTBN:CP$(CP)2:4:ATFT2",2660,2192,0,1,"CTBN:CP$(CP)2:4:ATFT2")
#! TextBox(TB0,2340,2140,2640,2180,0,"Dialog",12,1,16777215,"Turbine Brake Temperature Attenuator",null)
#! Record("CTBN:CP$(CP)2:4:ATFT",2120,2379,0,1,"CTBN:CP$(CP)2:4:ATFT")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(ao, "CTBN:CP$(CP)2:1:ATBT_MIN") {
  field(DESC, "Bearing Temp Attenuator Min")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T1_ATBT_ATmin")
  field(PREC, "2")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:1:ATBT_MAX") {
  field(DESC, "Bearing Temp Attenuator Max")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T1_ATBT_ATmax")
  field(PREC, "2")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:1:ATBT1") {
  field(DESC, "Bearing Temp Attenuator BT1")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T1_ATBT_BT1")
  field(PREC, "2")
  field(EGU, "K")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:1:ATBT2") {
  field(DESC, "Bearing Temp Attenuator BT2")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T1_ATBT_BT2")
  field(PREC, "2")
  field(EGU, "K")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CTBN:CP$(CP)2:1:ATBT") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) T1_Attenuate[2]")
  field(EGUF, "10")
  field(DESC, "Bearing Temp Attenuator")
  field(PREC, "2")
  field(ADEL, "0.01")
  field(MDEL, "0.01")
  field(PINI, "YES")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTBN:CP$(CP)2:1:ATBT_MIN",2120,2206,0,1,"CTBN:CP$(CP)2:1:ATBT_MIN")
#! Record("CTBN:CP$(CP)2:1:ATBT_MAX",2299,2206,0,1,"CTBN:CP$(CP)2:1:ATBT_MAX")
#! Record("CTBN:CP$(CP)2:1:ATBT1",2480,2192,0,1,"CTBN:CP$(CP)2:1:ATBT1")
#! Record("CTBN:CP$(CP)2:1:ATBT2",2660,2192,0,1,"CTBN:CP$(CP)2:1:ATBT2")
#! Record("CTBN:CP$(CP)2:1:ATBT",2135,2419,0,1,"CTBN:CP$(CP)2:1:ATBT")
#! TextBox(TB0,2340,2140,2640,2180,0,"Dialog",12,1,16777215,"Turbine Bearing Temperature Attenuator",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(ao, "CTBN:CP$(CP)2:2:ATBT_MIN") {
  field(DESC, "Bearing Temp Attenuator Min")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T2_ATBT_ATmin")
  field(PREC, "2")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:2:ATBT_MAX") {
  field(DESC, "Bearing Temp Attenuator Max")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T2_ATBT_ATmax")
  field(PREC, "2")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:2:ATBT1") {
  field(DESC, "Bearing Temp Attenuator BT1")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T2_ATBT_BT1")
  field(PREC, "2")
  field(EGU, "K")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:2:ATBT2") {
  field(DESC, "Bearing Temp Attenuator BT2")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T2_ATBT_BT2")
  field(PREC, "2")
  field(EGU, "K")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CTBN:CP$(CP)2:2:ATBT") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) T2_Attenuate[2]")
  field(EGUF, "10")
  field(DESC, "Bearing Temp Attenuator")
  field(PREC, "2")
  field(ADEL, "0.01")
  field(MDEL, "0.01")
  field(PINI, "YES")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTBN:CP$(CP)2:2:ATBT_MIN",2120,2206,0,1,"CTBN:CP$(CP)2:2:ATBT_MIN")
#! Record("CTBN:CP$(CP)2:2:ATBT_MAX",2299,2206,0,1,"CTBN:CP$(CP)2:2:ATBT_MAX")
#! Record("CTBN:CP$(CP)2:2:ATBT1",2480,2192,0,1,"CTBN:CP$(CP)2:2:ATBT1")
#! Record("CTBN:CP$(CP)2:2:ATBT2",2660,2192,0,1,"CTBN:CP$(CP)2:2:ATBT2")
#! Record("CTBN:CP$(CP)2:2:ATBT",2135,2419,0,1,"CTBN:CP$(CP)2:2:ATBT")
#! TextBox(TB0,2340,2140,2640,2180,0,"Dialog",12,1,16777215,"Turbine Bearing Temperature Attenuator",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(ao, "CTBN:CP$(CP)2:3:ATBT_MIN") {
  field(DESC, "Bearing Temp Attenuator Min")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T3_ATBT_ATmin")
  field(PREC, "2")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:3:ATBT_MAX") {
  field(DESC, "Bearing Temp Attenuator Max")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T3_ATBT_ATmax")
  field(PREC, "2")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:3:ATBT1") {
  field(DESC, "Bearing Temp Attenuator BT1")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T3_ATBT_BT1")
  field(PREC, "2")
  field(EGU, "K")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:3:ATBT2") {
  field(DESC, "Bearing Temp Attenuator BT2")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T3_ATBT_BT2")
  field(PREC, "2")
  field(EGU, "K")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CTBN:CP$(CP)2:3:ATBT") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) T3_Attenuate[2]")
  field(EGUF, "10")
  field(DESC, "Bearing Temp Attenuator")
  field(PREC, "2")
  field(ADEL, "0.01")
  field(MDEL, "0.01")
  field(PINI, "YES")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTBN:CP$(CP)2:3:ATBT_MIN",2120,2206,0,1,"CTBN:CP$(CP)2:3:ATBT_MIN")
#! Record("CTBN:CP$(CP)2:3:ATBT_MAX",2299,2206,0,1,"CTBN:CP$(CP)2:3:ATBT_MAX")
#! Record("CTBN:CP$(CP)2:3:ATBT1",2480,2192,0,1,"CTBN:CP$(CP)2:3:ATBT1")
#! Record("CTBN:CP$(CP)2:3:ATBT2",2660,2192,0,1,"CTBN:CP$(CP)2:3:ATBT2")
#! Record("CTBN:CP$(CP)2:3:ATBT",2135,2419,0,1,"CTBN:CP$(CP)2:3:ATBT")
#! TextBox(TB0,2340,2140,2640,2180,0,"Dialog",12,1,16777215,"Turbine Bearing Temperature Attenuator",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(ao, "CTBN:CP$(CP)2:4:ATBT_MIN") {
  field(DESC, "Bearing Temp Attenuator Min")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T4_ATBT_ATmin")
  field(PREC, "2")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:4:ATBT_MAX") {
  field(DESC, "Bearing Temp Attenuator Max")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T4_ATBT_ATmax")
  field(PREC, "2")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:4:ATBT1") {
  field(DESC, "Bearing Temp Attenuator BT1")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T4_ATBT_BT1")
  field(PREC, "2")
  field(EGU, "K")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:4:ATBT2") {
  field(DESC, "Bearing Temp Attenuator BT2")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T4_ATBT_BT2")
  field(PREC, "2")
  field(EGU, "K")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CTBN:CP$(CP)2:4:ATBT") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) T4_Attenuate[2]")
  field(EGUF, "10")
  field(DESC, "Bearing Temp Attenuator")
  field(PREC, "2")
  field(ADEL, "0.01")
  field(MDEL, "0.01")
  field(PINI, "YES")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTBN:CP$(CP)2:4:ATBT_MIN",2120,2206,0,1,"CTBN:CP$(CP)2:4:ATBT_MIN")
#! Record("CTBN:CP$(CP)2:4:ATBT_MAX",2299,2206,0,1,"CTBN:CP$(CP)2:4:ATBT_MAX")
#! Record("CTBN:CP$(CP)2:4:ATBT1",2480,2192,0,1,"CTBN:CP$(CP)2:4:ATBT1")
#! Record("CTBN:CP$(CP)2:4:ATBT2",2660,2192,0,1,"CTBN:CP$(CP)2:4:ATBT2")
#! Record("CTBN:CP$(CP)2:4:ATBT",2135,2419,0,1,"CTBN:CP$(CP)2:4:ATBT")
#! TextBox(TB0,2340,2140,2640,2180,0,"Dialog",12,1,16777215,"Turbine Bearing Temperature Attenuator",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(ao, "CTBN:CP$(CP)2:1:ATDT_MIN") {
  field(DESC, "Discharge Temp Attenuator Min")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T1_ATDT_ATmin")
  field(PREC, "2")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:1:ATDT_MAX") {
  field(DESC, "Discharge Temp Attenuator Max")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T1_ATDT_ATmax")
  field(PREC, "2")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:1:ATDT1") {
  field(DESC, "Discharge Temp Attenuator TT1")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T1_ATDT_TT1")
  field(PREC, "2")
  field(EGU, "K")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:1:ATDT2") {
  field(DESC, "Discharge Temp Attenuator TT2")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T1_ATDT_TT2")
  field(PREC, "2")
  field(EGU, "K")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CTBN:CP$(CP)2:1:ATDT") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) T1_Attenuate[4]")
  field(EGUF, "10")
  field(DESC, "Discharge Temp Attenuator")
  field(PREC, "2")
  field(ADEL, "0.01")
  field(MDEL, "0.01")
  field(PINI, "YES")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTBN:CP$(CP)2:1:ATDT_MIN",2120,2206,0,1,"CTBN:CP$(CP)2:1:ATDT_MIN")
#! Record("CTBN:CP$(CP)2:1:ATDT_MAX",2299,2206,0,1,"CTBN:CP$(CP)2:1:ATDT_MAX")
#! Record("CTBN:CP$(CP)2:1:ATDT1",2480,2192,0,1,"CTBN:CP$(CP)2:1:ATDT1")
#! Record("CTBN:CP$(CP)2:1:ATDT2",2660,2192,0,1,"CTBN:CP$(CP)2:1:ATDT2")
#! TextBox(TB0,2340,2140,2640,2180,0,"Dialog",12,1,16777215,"Turbine Discharge Temperature Attenuator",null)
#! Record("CTBN:CP$(CP)2:1:ATDT",2100,2399,0,1,"CTBN:CP$(CP)2:1:ATDT")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(ao, "CTBN:CP$(CP)2:2:ATDT_MIN") {
  field(DESC, "Discharge Temp Attenuator Min")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T2_ATDT_ATmin")
  field(PREC, "2")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:2:ATDT_MAX") {
  field(DESC, "Discharge Temp Attenuator Max")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T2_ATDT_ATmax")
  field(PREC, "2")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:2:ATDT1") {
  field(DESC, "Discharge Temp Attenuator TT1")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T2_ATDT_TT1")
  field(PREC, "2")
  field(EGU, "K")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:2:ATDT2") {
  field(DESC, "Discharge Temp Attenuator TT2")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T2_ATDT_TT2")
  field(PREC, "2")
  field(EGU, "K")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CTBN:CP$(CP)2:2:ATDT") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) T2_Attenuate[4]")
  field(EGUF, "10")
  field(DESC, "Discharge Temp Attenuator")
  field(PREC, "2")
  field(ADEL, "0.01")
  field(MDEL, "0.01")
  field(PINI, "YES")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTBN:CP$(CP)2:2:ATDT_MIN",2120,2206,0,1,"CTBN:CP$(CP)2:2:ATDT_MIN")
#! Record("CTBN:CP$(CP)2:2:ATDT_MAX",2299,2206,0,1,"CTBN:CP$(CP)2:2:ATDT_MAX")
#! Record("CTBN:CP$(CP)2:2:ATDT1",2480,2192,0,1,"CTBN:CP$(CP)2:2:ATDT1")
#! Record("CTBN:CP$(CP)2:2:ATDT2",2660,2192,0,1,"CTBN:CP$(CP)2:2:ATDT2")
#! TextBox(TB0,2340,2140,2640,2180,0,"Dialog",12,1,16777215,"Turbine Discharge Temperature Attenuator",null)
#! Record("CTBN:CP$(CP)2:2:ATDT",2100,2399,0,1,"CTBN:CP$(CP)2:2:ATDT")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(ao, "CTBN:CP$(CP)2:3:ATDT_MIN") {
  field(DESC, "Discharge Temp Attenuator Min")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T3_ATDT_ATmin")
  field(PREC, "2")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:3:ATDT_MAX") {
  field(DESC, "Discharge Temp Attenuator Max")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T3_ATDT_ATmax")
  field(PREC, "2")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:3:ATDT1") {
  field(DESC, "Discharge Temp Attenuator TT1")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T3_ATDT_TT1")
  field(PREC, "2")
  field(EGU, "K")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:3:ATDT2") {
  field(DESC, "Discharge Temp Attenuator TT2")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T3_ATDT_TT2")
  field(PREC, "2")
  field(EGU, "K")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CTBN:CP$(CP)2:3:ATDT") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) T3_Attenuate[4]")
  field(EGUF, "10")
  field(DESC, "Discharge Temp Attenuator")
  field(PREC, "2")
  field(ADEL, "0.01")
  field(MDEL, "0.01")
  field(PINI, "YES")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTBN:CP$(CP)2:3:ATDT_MIN",2120,2206,0,1,"CTBN:CP$(CP)2:3:ATDT_MIN")
#! Record("CTBN:CP$(CP)2:3:ATDT_MAX",2299,2206,0,1,"CTBN:CP$(CP)2:3:ATDT_MAX")
#! Record("CTBN:CP$(CP)2:3:ATDT1",2480,2192,0,1,"CTBN:CP$(CP)2:3:ATDT1")
#! Record("CTBN:CP$(CP)2:3:ATDT2",2660,2192,0,1,"CTBN:CP$(CP)2:3:ATDT2")
#! TextBox(TB0,2340,2140,2640,2180,0,"Dialog",12,1,16777215,"Turbine Discharge Temperature Attenuator",null)
#! Record("CTBN:CP$(CP)2:3:ATDT",2100,2399,0,1,"CTBN:CP$(CP)2:3:ATDT")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(ao, "CTBN:CP$(CP)2:1:ATDL_MIN") {
  field(DESC, "Dewar Level Attenuator Min")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T1_ATDL_ATmin")
  field(PREC, "2")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:1:ATDL_MAX") {
  field(DESC, "Dewar Level Attenuator Max")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T1_ATDL_ATmax")
  field(PREC, "2")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:1:ATDL1") {
  field(DESC, "Dewar Level Attenuator DL1")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T1_ATDL_DL1")
  field(PREC, "2")
  field(EGU, "%")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:1:ATDL2") {
  field(DESC, "Dewar Level Attenuator DL2")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T1_ATDL_DL2")
  field(PREC, "2")
  field(EGU, "%")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}


record(ai, "CTBN:CP$(CP)2:1:ATDL") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) T1_Attenuate[5]")
  field(EGUF, "10")
  field(DESC, "Dewar Level Attenuator")
  field(PREC, "2")
  field(ADEL, "0.01")
  field(MDEL, "0.01")
  field(PINI, "YES")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTBN:CP$(CP)2:1:ATDL_MIN",2120,2206,0,1,"CTBN:CP$(CP)2:1:ATDL_MIN")
#! Record("CTBN:CP$(CP)2:1:ATDL_MAX",2299,2206,0,1,"CTBN:CP$(CP)2:1:ATDL_MAX")
#! Record("CTBN:CP$(CP)2:1:ATDL1",2480,2192,0,1,"CTBN:CP$(CP)2:1:ATDL1")
#! Record("CTBN:CP$(CP)2:1:ATDL2",2660,2192,0,1,"CTBN:CP$(CP)2:1:ATDL2")
#! TextBox(TB0,2340,2140,2640,2180,0,"Dialog",12,1,16777215,"Turbine Dewar Level Temperature Attenuator",null)
#! Record("CTBN:CP$(CP)2:1:ATDL",2120,2399,0,1,"CTBN:CP$(CP)2:1:ATDL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(ao, "CTBN:CP$(CP)2:2:ATDL_MIN") {
  field(DESC, "Dewar Level Attenuator Min")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T2_ATDL_ATmin")
  field(PREC, "2")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:2:ATDL_MAX") {
  field(DESC, "Dewar Level Attenuator Max")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T2_ATDL_ATmax")
  field(PREC, "2")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:2:ATDL1") {
  field(DESC, "Dewar Level Attenuator DL1")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T2_ATDL_DL1")
  field(PREC, "2")
  field(EGU, "%")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:2:ATDL2") {
  field(DESC, "Dewar Level Attenuator DL2")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T2_ATDL_DL2")
  field(PREC, "2")
  field(EGU, "%")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}


record(ai, "CTBN:CP$(CP)2:2:ATDL") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) T2_Attenuate[5]")
  field(EGUF, "10")
  field(DESC, "Dewar Level Attenuator")
  field(PREC, "2")
  field(ADEL, "0.01")
  field(MDEL, "0.01")
  field(PINI, "YES")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTBN:CP$(CP)2:2:ATDL_MIN",2120,2206,0,1,"CTBN:CP$(CP)2:2:ATDL_MIN")
#! Record("CTBN:CP$(CP)2:2:ATDL_MAX",2299,2206,0,1,"CTBN:CP$(CP)2:2:ATDL_MAX")
#! Record("CTBN:CP$(CP)2:2:ATDL1",2480,2192,0,1,"CTBN:CP$(CP)2:2:ATDL1")
#! Record("CTBN:CP$(CP)2:2:ATDL2",2660,2192,0,1,"CTBN:CP$(CP)2:2:ATDL2")
#! TextBox(TB0,2340,2140,2640,2180,0,"Dialog",12,1,16777215,"Turbine Dewar Level Temperature Attenuator",null)
#! Record("CTBN:CP$(CP)2:2:ATDL",2120,2399,0,1,"CTBN:CP$(CP)2:2:ATDL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(ao, "CTBN:CP$(CP)2:3:ATDL_MIN") {
  field(DESC, "Dewar Level Attenuator Min")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T3_ATDL_ATmin")
  field(PREC, "2")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:3:ATDL_MAX") {
  field(DESC, "Dewar Level Attenuator Max")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T3_ATDL_ATmax")
  field(PREC, "2")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:3:ATDL1") {
  field(DESC, "Dewar Level Attenuator DL1")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T3_ATDL_DL1")
  field(PREC, "2")
  field(EGU, "%")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:3:ATDL2") {
  field(DESC, "Dewar Level Attenuator DL2")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T3_ATDL_DL2")
  field(PREC, "2")
  field(EGU, "%")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}


record(ai, "CTBN:CP$(CP)2:3:ATDL") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) T3_Attenuate[5]")
  field(EGUF, "10")
  field(DESC, "Dewar Level Attenuator")
  field(PREC, "2")
  field(ADEL, "0.01")
  field(MDEL, "0.01")
  field(PINI, "YES")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTBN:CP$(CP)2:3:ATDL_MIN",2120,2206,0,1,"CTBN:CP$(CP)2:3:ATDL_MIN")
#! Record("CTBN:CP$(CP)2:3:ATDL_MAX",2299,2206,0,1,"CTBN:CP$(CP)2:3:ATDL_MAX")
#! Record("CTBN:CP$(CP)2:3:ATDL1",2480,2192,0,1,"CTBN:CP$(CP)2:3:ATDL1")
#! Record("CTBN:CP$(CP)2:3:ATDL2",2660,2192,0,1,"CTBN:CP$(CP)2:3:ATDL2")
#! TextBox(TB0,2340,2140,2640,2180,0,"Dialog",12,1,16777215,"Turbine Dewar Level Temperature Attenuator",null)
#! Record("CTBN:CP$(CP)2:3:ATDL",2120,2399,0,1,"CTBN:CP$(CP)2:3:ATDL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(ao, "CTBN:CP$(CP)2:3:ATLP_MIN") {
  field(DESC, "Low Pressure Attenuator Min")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T3_ATLP_ATmin")
  field(PREC, "2")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:3:ATLP_MAX") {
  field(DESC, "Low Pressure Attenuator Max")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T3_ATLP_ATmax")
  field(PREC, "2")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:3:ATLP1") {
  field(DESC, "Low Pressure Attenuator LP1")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T3_ATLP_LP1")
  field(PREC, "2")
  field(EGU, "bara")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ao, "CTBN:CP$(CP)2:3:ATLP2") {
  field(DESC, "Dewar Level Attenuator DL2")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T3_ATLP_LP2")
  field(PREC, "2")
  field(EGU, "bara")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CTBN:CP$(CP)2:3:ATLP") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) T3_Attenuate[3]")
  field(EGUF, "10")
  field(DESC, "Low Pressure Attenuator")
  field(PREC, "2")
  field(ADEL, "0.01")
  field(MDEL, "0.01")
  field(PINI, "YES")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CTBN:CP$(CP)2:3:ATLP_MIN",2120,2206,0,1,"CTBN:CP$(CP)2:3:ATLP_MIN")
#! Record("CTBN:CP$(CP)2:3:ATLP_MAX",2299,2206,0,1,"CTBN:CP$(CP)2:3:ATLP_MAX")
#! Record("CTBN:CP$(CP)2:3:ATLP1",2480,2192,0,1,"CTBN:CP$(CP)2:3:ATLP1")
#! Record("CTBN:CP$(CP)2:3:ATLP2",2660,2192,0,1,"CTBN:CP$(CP)2:3:ATLP2")
#! Record("CTBN:CP$(CP)2:3:ATLP",2120,2379,0,1,"CTBN:CP$(CP)2:3:ATLP")
#! TextBox(TB0,2340,2140,2640,2180,0,"Dialog",12,1,16777215,"Turbine Low Pressure Temperature Attenuator",null)
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND



record(ao, "CTBN:CP$(CP)2:1:ATOP_SP") {
  field(DESC, "Operator Attenuator Setpoint")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T1_ATOP")
  field(PREC, "2")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CTBN:CP$(CP)2:1:ATOP") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) T1_Attenuate[0]")
  field(EGUF, "10")
  field(DESC, "Operator Attenuator")
  field(PREC, "2")
  field(ADEL, "0.01")
  field(MDEL, "0.01")
  field(PINI, "YES")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! TextBox(TB0,2340,2140,2640,2180,0,"Dialog",12,1,16777215,"Turbine Operator Attenuator",null)
#! Record("CTBN:CP$(CP)2:1:ATOP_SP",2480,2186,0,1,"CTBN:CP$(CP)2:1:ATOP_SP")
#! Record("CTBN:CP$(CP)2:1:ATOP",2280,2179,0,1,"CTBN:CP$(CP)2:1:ATOP")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND



record(ao, "CTBN:CP$(CP)2:2:ATOP_SP") {
  field(DESC, "Operator Attenuator Setpoint")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T2_ATOP")
  field(PREC, "2")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CTBN:CP$(CP)2:2:ATOP") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) T2_Attenuate[0]")
  field(EGUF, "10")
  field(DESC, "Operator Attenuator")
  field(PREC, "2")
  field(ADEL, "0.01")
  field(MDEL, "0.01")
  field(PINI, "YES")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! TextBox(TB0,2340,2140,2640,2180,0,"Dialog",12,1,16777215,"Turbine Operator Attenuator",null)
#! Record("CTBN:CP$(CP)2:2:ATOP_SP",2480,2186,0,1,"CTBN:CP$(CP)2:2:ATOP_SP")
#! Record("CTBN:CP$(CP)2:2:ATOP",2280,2179,0,1,"CTBN:CP$(CP)2:2:ATOP")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND



record(ao, "CTBN:CP$(CP)2:3:ATOP_SP") {
  field(DESC, "Operator Attenuator Setpoint")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T3_ATOP")
  field(PREC, "2")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CTBN:CP$(CP)2:3:ATOP") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) T3_Attenuate[0]")
  field(EGUF, "10")
  field(DESC, "Operator Attenuator")
  field(PREC, "2")
  field(ADEL, "0.01")
  field(MDEL, "0.01")
  field(PINI, "YES")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! TextBox(TB0,2340,2140,2640,2180,0,"Dialog",12,1,16777215,"Turbine Operator Attenuator",null)
#! Record("CTBN:CP$(CP)2:3:ATOP_SP",2480,2186,0,1,"CTBN:CP$(CP)2:3:ATOP_SP")
#! Record("CTBN:CP$(CP)2:3:ATOP",2280,2179,0,1,"CTBN:CP$(CP)2:3:ATOP")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND



record(ao, "CTBN:CP$(CP)2:4:ATOP_SP") {
  field(DESC, "Operator Attenuator Setpoint")
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC_NAME) T4_ATOP")
  field(PREC, "2")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(IVOA, "Don't drive outputs")
}

record(ai, "CTBN:CP$(CP)2:4:ATOP") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) T4_Attenuate[0]")
  field(EGUF, "10")
  field(DESC, "Operator Attenuator")
  field(PREC, "2")
  field(ADEL, "0.01")
  field(MDEL, "0.01")
  field(PINI, "YES")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! TextBox(TB0,2340,2140,2640,2180,0,"Dialog",12,1,16777215,"Turbine Operator Attenuator",null)
#! Record("CTBN:CP$(CP)2:4:ATOP_SP",2480,2186,0,1,"CTBN:CP$(CP)2:4:ATOP_SP")
#! Record("CTBN:CP$(CP)2:4:ATOP",2280,2179,0,1,"CTBN:CP$(CP)2:4:ATOP")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(mbbiDirect, "CTBN:CP$(CP)2:1:STATE") {
  field(DESC, "Turbine seq states 0-7")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Turbine_State B 0")
  field(NOBT, "8")
}

record(bi, "CTBN:CP$(CP)2:1:B1") {
  field(DESC, "X511")
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(INP, "CTBN:CP$(CP)2:1:STATE.B1")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(PINI, "YES")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

record(bi, "CTBN:CP$(CP)2:1:B2") {
  field(DESC, "X512")
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(INP, "CTBN:CP$(CP)2:1:STATE.B2")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(PINI, "YES")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

record(bi, "CTBN:CP$(CP)2:1:B3") {
  field(DESC, "X513")
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(INP, "CTBN:CP$(CP)2:1:STATE.B3")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(PINI, "YES")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

record(bi, "CTBN:CP$(CP)2:1:B4") {
  field(DESC, "X514")
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(INP, "CTBN:CP$(CP)2:1:STATE.B4")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(PINI, "YES")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

record(bi, "CTBN:CP$(CP)2:1:B5") {
  field(DESC, "X515")
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(INP, "CTBN:CP$(CP)2:1:STATE.B5")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(PINI, "YES")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

record(bi, "CTBN:CP$(CP)2:1:B6") {
  field(DESC, "X516")
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(INP, "CTBN:CP$(CP)2:1:STATE.B6")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(PINI, "YES")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

record(bi, "CTBN:CP$(CP)2:1:B7") {
  field(DESC, "X517")
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(INP, "CTBN:CP$(CP)2:1:STATE.B7")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(PINI, "YES")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

record(bi, "CTBN:CP$(CP)2:1:B0") {
  field(DESC, "X510")
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(INP, "CTBN:CP$(CP)2:1:STATE.B0")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(PINI, "YES")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("CTBN:CP$(CP)2:1:STATE",40,100,0,0,"CTBN:CP$(CP)2:1:STATE")
#! Field("CTBN:CP$(CP)2:1:STATE.B3",16777215,1,"CTBN:CP$(CP)2:1:STATE.B3")
#! Field("CTBN:CP$(CP)2:1:STATE.B1",16777215,1,"CTBN:CP$(CP)2:1:STATE.B1")
#! Field("CTBN:CP$(CP)2:1:STATE.B2",16777215,1,"CTBN:CP$(CP)2:1:STATE.B2")
#! Field("CTBN:CP$(CP)2:1:STATE.B4",16777215,1,"CTBN:CP$(CP)2:1:STATE.B4")
#! Field("CTBN:CP$(CP)2:1:STATE.B5",16777215,1,"CTBN:CP$(CP)2:1:STATE.B5")
#! Field("CTBN:CP$(CP)2:1:STATE.B6",16777215,1,"CTBN:CP$(CP)2:1:STATE.B6")
#! Field("CTBN:CP$(CP)2:1:STATE.B7",16777215,1,"CTBN:CP$(CP)2:1:STATE.B7")
#! Field("CTBN:CP$(CP)2:1:STATE.B0",16777215,0,"CTBN:CP$(CP)2:1:STATE.B0")
#! Record("CTBN:CP$(CP)2:1:B1",500,119,0,1,"CTBN:CP$(CP)2:1:B1")
#! Field("CTBN:CP$(CP)2:1:B1.INP",16777215,0,"CTBN:CP$(CP)2:1:B1.INP")
#! Link("CTBN:CP$(CP)2:1:B1.INP","CTBN:CP$(CP)2:1:STATE.B1")
#! Record("CTBN:CP$(CP)2:1:B2",680,159,0,1,"CTBN:CP$(CP)2:1:B2")
#! Field("CTBN:CP$(CP)2:1:B2.INP",16777215,0,"CTBN:CP$(CP)2:1:B2.INP")
#! Link("CTBN:CP$(CP)2:1:B2.INP","CTBN:CP$(CP)2:1:STATE.B2")
#! Record("CTBN:CP$(CP)2:1:B3",882,199,0,1,"CTBN:CP$(CP)2:1:B3")
#! Field("CTBN:CP$(CP)2:1:B3.INP",16777215,0,"CTBN:CP$(CP)2:1:B3.INP")
#! Link("CTBN:CP$(CP)2:1:B3.INP","CTBN:CP$(CP)2:1:STATE.B3")
#! Record("CTBN:CP$(CP)2:1:B4",320,419,0,1,"CTBN:CP$(CP)2:1:B4")
#! Field("CTBN:CP$(CP)2:1:B4.INP",16777215,0,"CTBN:CP$(CP)2:1:B4.INP")
#! Link("CTBN:CP$(CP)2:1:B4.INP","CTBN:CP$(CP)2:1:STATE.B4")
#! Record("CTBN:CP$(CP)2:1:B5",501,439,0,1,"CTBN:CP$(CP)2:1:B5")
#! Field("CTBN:CP$(CP)2:1:B5.INP",16777215,0,"CTBN:CP$(CP)2:1:B5.INP")
#! Link("CTBN:CP$(CP)2:1:B5.INP","CTBN:CP$(CP)2:1:STATE.B5")
#! Record("CTBN:CP$(CP)2:1:B6",694,479,0,1,"CTBN:CP$(CP)2:1:B6")
#! Field("CTBN:CP$(CP)2:1:B6.INP",16777215,0,"CTBN:CP$(CP)2:1:B6.INP")
#! Link("CTBN:CP$(CP)2:1:B6.INP","CTBN:CP$(CP)2:1:STATE.B6")
#! Record("CTBN:CP$(CP)2:1:B7",880,519,0,1,"CTBN:CP$(CP)2:1:B7")
#! Field("CTBN:CP$(CP)2:1:B7.INP",16777215,0,"CTBN:CP$(CP)2:1:B7.INP")
#! Link("CTBN:CP$(CP)2:1:B7.INP","CTBN:CP$(CP)2:1:STATE.B7")
#! Record("CTBN:CP$(CP)2:1:B0",320,99,0,1,"CTBN:CP$(CP)2:1:B0")
#! Field("CTBN:CP$(CP)2:1:B0.INP",16777215,0,"CTBN:CP$(CP)2:1:B0.INP")
#! Link("CTBN:CP$(CP)2:1:B0.INP","CTBN:CP$(CP)2:1:STATE.B0")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(mbbiDirect, "CTBN:CP$(CP)2:2:STATE") {
  field(DESC, "Turbine seq states 8-15")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Turbine_State B 8")
  field(NOBT, "8")
}

record(bi, "CTBN:CP$(CP)2:2:B1") {
  field(DESC, "X521")
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(INP, "CTBN:CP$(CP)2:2:STATE.B1")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(PINI, "YES")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

record(bi, "CTBN:CP$(CP)2:2:B2") {
  field(DESC, "X522")
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(INP, "CTBN:CP$(CP)2:2:STATE.B2")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(PINI, "YES")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

record(bi, "CTBN:CP$(CP)2:2:B3") {
  field(DESC, "X523")
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(INP, "CTBN:CP$(CP)2:2:STATE.B3")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(PINI, "YES")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

record(bi, "CTBN:CP$(CP)2:2:B4") {
  field(DESC, "X524")
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(INP, "CTBN:CP$(CP)2:2:STATE.B4")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(PINI, "YES")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

record(bi, "CTBN:CP$(CP)2:2:B5") {
  field(DESC, "X525")
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(INP, "CTBN:CP$(CP)2:2:STATE.B5")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(PINI, "YES")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

record(bi, "CTBN:CP$(CP)2:2:B6") {
  field(DESC, "X526")
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(INP, "CTBN:CP$(CP)2:2:STATE.B6")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(PINI, "YES")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

record(bi, "CTBN:CP$(CP)2:2:B7") {
  field(DESC, "X527")
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(INP, "CTBN:CP$(CP)2:2:STATE.B7")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(PINI, "YES")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

record(bi, "CTBN:CP$(CP)2:2:B0") {
  field(DESC, "X520")
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(INP, "CTBN:CP$(CP)2:2:STATE.B0")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(PINI, "YES")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("CTBN:CP$(CP)2:2:STATE",40,100,0,0,"CTBN:CP$(CP)2:2:STATE")
#! Field("CTBN:CP$(CP)2:2:STATE.B3",16777215,1,"CTBN:CP$(CP)2:2:STATE.B3")
#! Field("CTBN:CP$(CP)2:2:STATE.B1",16777215,1,"CTBN:CP$(CP)2:2:STATE.B1")
#! Field("CTBN:CP$(CP)2:2:STATE.B2",16777215,1,"CTBN:CP$(CP)2:2:STATE.B2")
#! Field("CTBN:CP$(CP)2:2:STATE.B4",16777215,1,"CTBN:CP$(CP)2:2:STATE.B4")
#! Field("CTBN:CP$(CP)2:2:STATE.B5",16777215,1,"CTBN:CP$(CP)2:2:STATE.B5")
#! Field("CTBN:CP$(CP)2:2:STATE.B6",16777215,1,"CTBN:CP$(CP)2:2:STATE.B6")
#! Field("CTBN:CP$(CP)2:2:STATE.B7",16777215,1,"CTBN:CP$(CP)2:2:STATE.B7")
#! Field("CTBN:CP$(CP)2:2:STATE.B0",16777215,0,"CTBN:CP$(CP)2:2:STATE.B0")
#! Record("CTBN:CP$(CP)2:2:B1",500,119,0,1,"CTBN:CP$(CP)2:2:B1")
#! Field("CTBN:CP$(CP)2:2:B1.INP",16777215,0,"CTBN:CP$(CP)2:2:B1.INP")
#! Link("CTBN:CP$(CP)2:2:B1.INP","CTBN:CP$(CP)2:2:STATE.B1")
#! Record("CTBN:CP$(CP)2:2:B2",680,159,0,1,"CTBN:CP$(CP)2:2:B2")
#! Field("CTBN:CP$(CP)2:2:B2.INP",16777215,0,"CTBN:CP$(CP)2:2:B2.INP")
#! Link("CTBN:CP$(CP)2:2:B2.INP","CTBN:CP$(CP)2:2:STATE.B2")
#! Record("CTBN:CP$(CP)2:2:B3",882,199,0,1,"CTBN:CP$(CP)2:2:B3")
#! Field("CTBN:CP$(CP)2:2:B3.INP",16777215,0,"CTBN:CP$(CP)2:2:B3.INP")
#! Link("CTBN:CP$(CP)2:2:B3.INP","CTBN:CP$(CP)2:2:STATE.B3")
#! Record("CTBN:CP$(CP)2:2:B4",320,419,0,1,"CTBN:CP$(CP)2:2:B4")
#! Field("CTBN:CP$(CP)2:2:B4.INP",16777215,0,"CTBN:CP$(CP)2:2:B4.INP")
#! Link("CTBN:CP$(CP)2:2:B4.INP","CTBN:CP$(CP)2:2:STATE.B4")
#! Record("CTBN:CP$(CP)2:2:B5",501,439,0,1,"CTBN:CP$(CP)2:2:B5")
#! Field("CTBN:CP$(CP)2:2:B5.INP",16777215,0,"CTBN:CP$(CP)2:2:B5.INP")
#! Link("CTBN:CP$(CP)2:2:B5.INP","CTBN:CP$(CP)2:2:STATE.B5")
#! Record("CTBN:CP$(CP)2:2:B6",694,479,0,1,"CTBN:CP$(CP)2:2:B6")
#! Field("CTBN:CP$(CP)2:2:B6.INP",16777215,0,"CTBN:CP$(CP)2:2:B6.INP")
#! Link("CTBN:CP$(CP)2:2:B6.INP","CTBN:CP$(CP)2:2:STATE.B6")
#! Record("CTBN:CP$(CP)2:2:B7",880,519,0,1,"CTBN:CP$(CP)2:2:B7")
#! Field("CTBN:CP$(CP)2:2:B7.INP",16777215,0,"CTBN:CP$(CP)2:2:B7.INP")
#! Link("CTBN:CP$(CP)2:2:B7.INP","CTBN:CP$(CP)2:2:STATE.B7")
#! Record("CTBN:CP$(CP)2:2:B0",320,99,0,1,"CTBN:CP$(CP)2:2:B0")
#! Field("CTBN:CP$(CP)2:2:B0.INP",16777215,0,"CTBN:CP$(CP)2:2:B0.INP")
#! Link("CTBN:CP$(CP)2:2:B0.INP","CTBN:CP$(CP)2:2:STATE.B0")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(mbbiDirect, "CTBN:CP$(CP)2:3:STATE") {
  field(DESC, "Turbine seq states 16-23")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Turbine_State B 16")
  field(NOBT, "8")
}

record(bi, "CTBN:CP$(CP)2:3:B1") {
  field(DESC, "X531")
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(INP, "CTBN:CP$(CP)2:3:STATE.B1")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(PINI, "YES")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

record(bi, "CTBN:CP$(CP)2:3:B2") {
  field(DESC, "X532")
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(INP, "CTBN:CP$(CP)2:3:STATE.B2")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(PINI, "YES")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

record(bi, "CTBN:CP$(CP)2:3:B3") {
  field(DESC, "X533")
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(INP, "CTBN:CP$(CP)2:3:STATE.B3")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(PINI, "YES")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

record(bi, "CTBN:CP$(CP)2:3:B4") {
  field(DESC, "X534")
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(INP, "CTBN:CP$(CP)2:3:STATE.B4")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(PINI, "YES")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

record(bi, "CTBN:CP$(CP)2:3:B5") {
  field(DESC, "X535")
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(INP, "CTBN:CP$(CP)2:3:STATE.B5")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(PINI, "YES")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

record(bi, "CTBN:CP$(CP)2:3:B6") {
  field(DESC, "X536")
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(INP, "CTBN:CP$(CP)2:3:STATE.B6")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(PINI, "YES")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

record(bi, "CTBN:CP$(CP)2:3:B7") {
  field(DESC, "X537")
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(INP, "CTBN:CP$(CP)2:3:STATE.B7")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(PINI, "YES")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

record(bi, "CTBN:CP$(CP)2:3:B0") {
  field(DESC, "X530")
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(INP, "CTBN:CP$(CP)2:3:STATE.B0")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(PINI, "YES")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("CTBN:CP$(CP)2:3:STATE",40,100,0,0,"CTBN:CP$(CP)2:3:STATE")
#! Field("CTBN:CP$(CP)2:3:STATE.B3",16777215,1,"CTBN:CP$(CP)2:3:STATE.B3")
#! Field("CTBN:CP$(CP)2:3:STATE.B1",16777215,1,"CTBN:CP$(CP)2:3:STATE.B1")
#! Field("CTBN:CP$(CP)2:3:STATE.B2",16777215,1,"CTBN:CP$(CP)2:3:STATE.B2")
#! Field("CTBN:CP$(CP)2:3:STATE.B4",16777215,1,"CTBN:CP$(CP)2:3:STATE.B4")
#! Field("CTBN:CP$(CP)2:3:STATE.B5",16777215,1,"CTBN:CP$(CP)2:3:STATE.B5")
#! Field("CTBN:CP$(CP)2:3:STATE.B6",16777215,1,"CTBN:CP$(CP)2:3:STATE.B6")
#! Field("CTBN:CP$(CP)2:3:STATE.B7",16777215,1,"CTBN:CP$(CP)2:3:STATE.B7")
#! Field("CTBN:CP$(CP)2:3:STATE.B0",16777215,0,"CTBN:CP$(CP)2:3:STATE.B0")
#! Record("CTBN:CP$(CP)2:3:B1",500,119,0,1,"CTBN:CP$(CP)2:3:B1")
#! Field("CTBN:CP$(CP)2:3:B1.INP",16777215,0,"CTBN:CP$(CP)2:3:B1.INP")
#! Link("CTBN:CP$(CP)2:3:B1.INP","CTBN:CP$(CP)2:3:STATE.B1")
#! Record("CTBN:CP$(CP)2:3:B2",680,159,0,1,"CTBN:CP$(CP)2:3:B2")
#! Field("CTBN:CP$(CP)2:3:B2.INP",16777215,0,"CTBN:CP$(CP)2:3:B2.INP")
#! Link("CTBN:CP$(CP)2:3:B2.INP","CTBN:CP$(CP)2:3:STATE.B2")
#! Record("CTBN:CP$(CP)2:3:B3",882,199,0,1,"CTBN:CP$(CP)2:3:B3")
#! Field("CTBN:CP$(CP)2:3:B3.INP",16777215,0,"CTBN:CP$(CP)2:3:B3.INP")
#! Link("CTBN:CP$(CP)2:3:B3.INP","CTBN:CP$(CP)2:3:STATE.B3")
#! Record("CTBN:CP$(CP)2:3:B4",320,419,0,1,"CTBN:CP$(CP)2:3:B4")
#! Field("CTBN:CP$(CP)2:3:B4.INP",16777215,0,"CTBN:CP$(CP)2:3:B4.INP")
#! Link("CTBN:CP$(CP)2:3:B4.INP","CTBN:CP$(CP)2:3:STATE.B4")
#! Record("CTBN:CP$(CP)2:3:B5",501,439,0,1,"CTBN:CP$(CP)2:3:B5")
#! Field("CTBN:CP$(CP)2:3:B5.INP",16777215,0,"CTBN:CP$(CP)2:3:B5.INP")
#! Link("CTBN:CP$(CP)2:3:B5.INP","CTBN:CP$(CP)2:3:STATE.B5")
#! Record("CTBN:CP$(CP)2:3:B6",694,479,0,1,"CTBN:CP$(CP)2:3:B6")
#! Field("CTBN:CP$(CP)2:3:B6.INP",16777215,0,"CTBN:CP$(CP)2:3:B6.INP")
#! Link("CTBN:CP$(CP)2:3:B6.INP","CTBN:CP$(CP)2:3:STATE.B6")
#! Record("CTBN:CP$(CP)2:3:B7",880,519,0,1,"CTBN:CP$(CP)2:3:B7")
#! Field("CTBN:CP$(CP)2:3:B7.INP",16777215,0,"CTBN:CP$(CP)2:3:B7.INP")
#! Link("CTBN:CP$(CP)2:3:B7.INP","CTBN:CP$(CP)2:3:STATE.B7")
#! Record("CTBN:CP$(CP)2:3:B0",320,99,0,1,"CTBN:CP$(CP)2:3:B0")
#! Field("CTBN:CP$(CP)2:3:B0.INP",16777215,0,"CTBN:CP$(CP)2:3:B0.INP")
#! Link("CTBN:CP$(CP)2:3:B0.INP","CTBN:CP$(CP)2:3:STATE.B0")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(mbbiDirect, "CTBN:CP$(CP)2:4:STATE") {
  field(DESC, "Turbine seq states 24-31")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Turbine_State B 24")
  field(NOBT, "8")
}

record(bi, "CTBN:CP$(CP)2:4:B1") {
  field(DESC, "X541")
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(INP, "CTBN:CP$(CP)2:4:STATE.B1")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(PINI, "YES")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

record(bi, "CTBN:CP$(CP)2:4:B2") {
  field(DESC, "X542")
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(INP, "CTBN:CP$(CP)2:4:STATE.B2")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(PINI, "YES")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

record(bi, "CTBN:CP$(CP)2:4:B3") {
  field(DESC, "X543")
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(INP, "CTBN:CP$(CP)2:4:STATE.B3")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(PINI, "YES")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

record(bi, "CTBN:CP$(CP)2:4:B4") {
  field(DESC, "X544")
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(INP, "CTBN:CP$(CP)2:4:STATE.B4")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(PINI, "YES")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

record(bi, "CTBN:CP$(CP)2:4:B5") {
  field(DESC, "X545")
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(INP, "CTBN:CP$(CP)2:4:STATE.B5")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(PINI, "YES")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

record(bi, "CTBN:CP$(CP)2:4:B6") {
  field(DESC, "X546")
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(INP, "CTBN:CP$(CP)2:4:STATE.B6")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(PINI, "YES")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

record(bi, "CTBN:CP$(CP)2:4:B7") {
  field(DESC, "X547")
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(INP, "CTBN:CP$(CP)2:4:STATE.B7")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(PINI, "YES")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

record(bi, "CTBN:CP$(CP)2:4:B0") {
  field(DESC, "X540")
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(INP, "CTBN:CP$(CP)2:4:STATE.B0")
  field(ZNAM, "inactive")
  field(ONAM, "active")
  field(PINI, "YES")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("CTBN:CP$(CP)2:4:STATE",40,100,0,0,"CTBN:CP$(CP)2:4:STATE")
#! Field("CTBN:CP$(CP)2:4:STATE.B3",16777215,1,"CTBN:CP$(CP)2:4:STATE.B3")
#! Field("CTBN:CP$(CP)2:4:STATE.B1",16777215,1,"CTBN:CP$(CP)2:4:STATE.B1")
#! Field("CTBN:CP$(CP)2:4:STATE.B2",16777215,1,"CTBN:CP$(CP)2:4:STATE.B2")
#! Field("CTBN:CP$(CP)2:4:STATE.B4",16777215,1,"CTBN:CP$(CP)2:4:STATE.B4")
#! Field("CTBN:CP$(CP)2:4:STATE.B5",16777215,1,"CTBN:CP$(CP)2:4:STATE.B5")
#! Field("CTBN:CP$(CP)2:4:STATE.B6",16777215,1,"CTBN:CP$(CP)2:4:STATE.B6")
#! Field("CTBN:CP$(CP)2:4:STATE.B7",16777215,1,"CTBN:CP$(CP)2:4:STATE.B7")
#! Field("CTBN:CP$(CP)2:4:STATE.B0",16777215,0,"CTBN:CP$(CP)2:4:STATE.B0")
#! Record("CTBN:CP$(CP)2:4:B1",500,119,0,1,"CTBN:CP$(CP)2:4:B1")
#! Field("CTBN:CP$(CP)2:4:B1.INP",16777215,0,"CTBN:CP$(CP)2:4:B1.INP")
#! Link("CTBN:CP$(CP)2:4:B1.INP","CTBN:CP$(CP)2:4:STATE.B1")
#! Record("CTBN:CP$(CP)2:4:B2",680,159,0,1,"CTBN:CP$(CP)2:4:B2")
#! Field("CTBN:CP$(CP)2:4:B2.INP",16777215,0,"CTBN:CP$(CP)2:4:B2.INP")
#! Link("CTBN:CP$(CP)2:4:B2.INP","CTBN:CP$(CP)2:4:STATE.B2")
#! Record("CTBN:CP$(CP)2:4:B3",882,199,0,1,"CTBN:CP$(CP)2:4:B3")
#! Field("CTBN:CP$(CP)2:4:B3.INP",16777215,0,"CTBN:CP$(CP)2:4:B3.INP")
#! Link("CTBN:CP$(CP)2:4:B3.INP","CTBN:CP$(CP)2:4:STATE.B3")
#! Record("CTBN:CP$(CP)2:4:B4",320,419,0,1,"CTBN:CP$(CP)2:4:B4")
#! Field("CTBN:CP$(CP)2:4:B4.INP",16777215,0,"CTBN:CP$(CP)2:4:B4.INP")
#! Link("CTBN:CP$(CP)2:4:B4.INP","CTBN:CP$(CP)2:4:STATE.B4")
#! Record("CTBN:CP$(CP)2:4:B5",501,439,0,1,"CTBN:CP$(CP)2:4:B5")
#! Field("CTBN:CP$(CP)2:4:B5.INP",16777215,0,"CTBN:CP$(CP)2:4:B5.INP")
#! Link("CTBN:CP$(CP)2:4:B5.INP","CTBN:CP$(CP)2:4:STATE.B5")
#! Record("CTBN:CP$(CP)2:4:B6",694,479,0,1,"CTBN:CP$(CP)2:4:B6")
#! Field("CTBN:CP$(CP)2:4:B6.INP",16777215,0,"CTBN:CP$(CP)2:4:B6.INP")
#! Link("CTBN:CP$(CP)2:4:B6.INP","CTBN:CP$(CP)2:4:STATE.B6")
#! Record("CTBN:CP$(CP)2:4:B7",880,519,0,1,"CTBN:CP$(CP)2:4:B7")
#! Field("CTBN:CP$(CP)2:4:B7.INP",16777215,0,"CTBN:CP$(CP)2:4:B7.INP")
#! Link("CTBN:CP$(CP)2:4:B7.INP","CTBN:CP$(CP)2:4:STATE.B7")
#! Record("CTBN:CP$(CP)2:4:B0",320,99,0,1,"CTBN:CP$(CP)2:4:B0")
#! Field("CTBN:CP$(CP)2:4:B0.INP",16777215,0,"CTBN:CP$(CP)2:4:B0.INP")
#! Link("CTBN:CP$(CP)2:4:B0.INP","CTBN:CP$(CP)2:4:STATE.B0")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(mbbiDirect, "CVAC:CP$(CP)2:3610:STATE") {
  field(DESC, "UCB Vacuum Seq state")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) VAC_State B 0")
  field(NOBT, "8")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("CVAC:CP$(CP)2:3610:STATE",340,80,0,0,"CVAC:CP$(CP)2:3610:STATE")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(mbbiDirect, "CVAC:CP$(CP)2:3630:STATE") {
  field(DESC, "LCB Vacuum Seq state")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) VAC_State B 10")
  field(NOBT, "8")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("CVAC:CP$(CP)2:3630:STATE",340,80,0,0,"CVAC:CP$(CP)2:3630:STATE")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(mbbiDirect, "CDWR:CP$(CP)2:0:STATE") {
  field(DESC, "dewar seq states 0-10")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Dewar_State B 0")
  field(NOBT, "16")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("CDWR:CP$(CP)2:0:STATE",340,80,0,0,"CDWR:CP$(CP)2:0:STATE")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(mbbiDirect, "CCBX:CP$(CP)2:0:INTERLOCK1") {
  field(DESC, "coldbox interlock1 b0-15")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Interlock1 B 0")
  field(NOBT, "16")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("CCBX:CP$(CP)2:0:INTERLOCK1",340,80,0,0,"CCBX:CP$(CP)2:0:INTERLOCK1")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(mbbiDirect, "CCBX:CP$(CP)2:0:INTERLOCK1A") {
  field(DESC, "coldbox interlock1 b16-31")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Interlock1 B 16")
  field(NOBT, "16")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("CCBX:CP$(CP)2:0:INTERLOCK1A",340,80,0,0,"CCBX:CP$(CP)2:0:INTERLOCK1A")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(mbbiDirect, "CCBX:CP$(CP)2:0:INTERLOCK2") {
  field(DESC, "coldbox interlock2 b0-15")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Interlock2 B 0")
  field(NOBT, "16")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("CCBX:CP$(CP)2:0:INTERLOCK2",340,80,0,0,"CCBX:CP$(CP)2:0:INTERLOCK2")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(mbbiDirect, "CCBX:CP$(CP)2:0:INTERLOCK2A") {
  field(DESC, "coldbox interlock2 b16-31")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Interlock2 B 16")
  field(NOBT, "16")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("CCBX:CP$(CP)2:0:INTERLOCK2A",340,80,0,0,"CCBX:CP$(CP)2:0:INTERLOCK2A")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(mbbiDirect, "CVAC:CP$(CP)2:3610:INTERLOCKS") {
  field(DESC, "UCB vac interlock2 b15-18")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Interlock2 B 15")
  field(NOBT, "4")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("CVAC:CP$(CP)2:3610:INTERLOCKS",340,80,0,0,"CVAC:CP$(CP)2:3610:INTERLOCKS")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(mbbiDirect, "CVAC:CP$(CP)2:3630:INTERLOCKS") {
  field(DESC, "LCB vac interlock2 b19-22")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Interlock2 B 19")
  field(NOBT, "4")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("CVAC:CP$(CP)2:3630:INTERLOCKS",340,80,0,0,"CVAC:CP$(CP)2:3630:INTERLOCKS")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(mbbiDirect, "CCBX:CP$(CP)2:0:TURBINE_ILS") {
  field(DESC, "TBN IL2 b11-14 (b10 not used)")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Interlock2 B 10")
  field(NOBT, "4")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("CCBX:CP$(CP)2:0:TURBINE_ILS",340,80,0,0,"CCBX:CP$(CP)2:0:TURBINE_ILS")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(mbbiDirect, "CCBX:CP$(CP)2:0:CD_STATE1") {
  field(DESC, "cooldown Seq states b0-15")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) CD_State B 0")
  field(NOBT, "16")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("CCBX:CP$(CP)2:0:CD_STATE1",340,80,0,0,"CCBX:CP$(CP)2:0:CD_STATE1")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(mbbiDirect, "CCBX:CP$(CP)2:0:CD_STATE2") {
  field(DESC, "cooldown Seq states b20-24")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) CD_State B 20")
  field(NOBT, "16")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("CCBX:CP$(CP)2:0:CD_STATE2",340,80,0,0,"CCBX:CP$(CP)2:0:CD_STATE2")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(mbbiDirect, "CCBX:CP$(CP)2:0:CSHLD_STATE") {
  field(DESC, "cold shield states b0-10")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) CShld_State B 0")
  field(NOBT, "10")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("CCBX:CP$(CP)2:0:CSHLD_STATE",340,80,0,0,"CCBX:CP$(CP)2:0:CSHLD_STATE")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(mbbiDirect, "CCBX:CP$(CP)2:0:WSHLD_STATE") {
  field(DESC, "warm shield states b0-15")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) WShld_State B 0")
  field(NOBT, "16")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("CCBX:CP$(CP)2:0:WSHLD_STATE",340,80,0,0,"CCBX:CP$(CP)2:0:WSHLD_STATE")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(mbbiDirect, "CCBX:CP$(CP)2:0:PS_STATE") {
  field(DESC, "PS states b0-5")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) PS_State B 0")
  field(NOBT, "6")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("CCBX:CP$(CP)2:0:PS_STATE",340,80,0,0,"CCBX:CP$(CP)2:0:PS_STATE")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../../dbd/cryoplant.dbd")
#! DBDEND


record(bi, "CVAC:CP$(CP)2:MANUALSTATUS") {
  field(DESC, "Any valve in system in manual indication")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) Anything_in_Manual")
  field(ZNAM, "Nothing")
  field(ONAM, "Something")
  field(OSV,  "MINOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("CVAC:CP$(CP)2:MANUALSTATUS)",340,80,0,0,"CVAC:CP$(CP)2:MANUALSTATUS")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../dbd/cryoTest.dbd")
#! DBDEND


record(ao, "CTIC:CP$(CP)2:2400:C0") {
  field(DESC, "PV22400 fully open abv CO")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.1")
  field(IVOA, "Don't drive outputs")
  field(OUT, "@$(PLC_NAME) TIC22400_C0")
}

record(stringin, "CTIC:CP$(CP)2:2400:PIDTAG") {
  field(DESC, "C0 PIDtag")
  field(PINI, "YES")
  field(VAL, "C$(CP)TIC22400")
}

#! Further lines contain data used by VisualDCT
#! View(1774,1984,1.0)
#! Record("CTIC:CP$(CP)2:2400:C0",2060,2119,0,1,"CTIC:CP$(CP)2:2400:C0")
#! Record("CTIC:CP$(CP)2:2400:PIDTAG",2340,2142,0,1,"CTIC:CP$(CP)2:2400:PIDTAG")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../dbd/cryoTest.dbd")
#! DBDEND


record(ao, "CTIC:CP$(CP)2:2400:C2") {
  field(DESC, "PV22402 begin clsng at C2")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(PREC, "1")
  field(EGU, "%")
  field(ADEL, "0.1")
  field(IVOA, "Don't drive outputs")
  field(OUT, "@$(PLC_NAME) TIC22400_C2")
}

record(stringin, "CTIC:CP$(CP)2:2400:PIDTAG") {
  field(DESC, "C2 PIDtag")
  field(PINI, "YES")
  field(VAL, "C$(CP)TIC22400")
}

#! Further lines contain data used by VisualDCT
#! View(1774,1984,1.0)
#! Record("CTIC:CP$(CP)2:2400:C2",2060,2119,0,1,"CTIC:CP$(CP)2:2400:C2")
#! Record("CTIC:CP$(CP)2:2400:PIDTAG",2340,2142,0,1,"CTIC:CP$(CP)2:2400:PIDTAG")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../dbd/cryoTest.dbd")
#! DBDEND


record(ao, "CHTR:CP$(CP)2:2190:RQST") {
  field(DESC, "Sub Atm test heater W rqst")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(PREC, "2")
  field(EGU, "W")
  field(ADEL, "0.01")
  field(IVOA, "Don't drive outputs")
  field(OUT, "@$(PLC_NAME) EHTR22190RQST")
}

record(stringin, "CHTR:CP$(CP)2:2190:PIDTAG") {
  field(DESC, "RQST PIDtag")
  field(PINI, "YES")
  field(VAL, "C$(CP)HTR22190")
}

#! Further lines contain data used by VisualDCT
#! View(1774,1984,1.0)
#! Record("CHTR:CP$(CP)2:2190:RQST",2060,2119,0,1,"CHTR:CP$(CP)2:2190:RQST")
#! Record("CHTR:CP$(CP)2:2190:PIDTAG",2340,2142,0,1,"CHTR:CP$(CP)2:2190:PIDTAG")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../dbd/cryoTest.dbd")
#! DBDEND


record(ao, "CHTR:CP$(CP)2:2191:RQST") {
  field(DESC, "LTTI test heater W rqst")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(PREC, "2")
  field(EGU, "W")
  field(ADEL, "0.01")
  field(IVOA, "Don't drive outputs")
  field(OUT, "@$(PLC_NAME) EHTR22191RQST")
}

record(stringin, "CHTR:CP$(CP)2:2191:PIDTAG") {
  field(DESC, "RQST PIDtag")
  field(PINI, "YES")
  field(VAL, "C$(CP)HTR22191")
}

#! Further lines contain data used by VisualDCT
#! View(1774,1984,1.0)
#! Record("CHTR:CP$(CP)2:2191:RQST",2060,2119,0,1,"CHTR:CP$(CP)2:2191:RQST")
#! Record("CHTR:CP$(CP)2:2191:PIDTAG",2340,2142,0,1,"CHTR:CP$(CP)2:2191:PIDTAG")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../dbd/cryoTest.dbd")
#! DBDEND


record(ao, "CHTR:CP$(CP)2:2240:RQST") {
  field(DESC, "HTTS test heater W rqst")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(PREC, "2")
  field(EGU, "W")
  field(ADEL, "0.01")
  field(IVOA, "Don't drive outputs")
  field(OUT, "@$(PLC_NAME) EHTR22240RQST")
}

record(stringin, "CHTR:CP$(CP)2:2240:PIDTAG") {
  field(DESC, "RQST PIDtag")
  field(PINI, "YES")
  field(VAL, "C$(CP)HTR22240")
}

#! Further lines contain data used by VisualDCT
#! View(1774,1984,1.0)
#! Record("CHTR:CP$(CP)2:2240:RQST",2060,2119,0,1,"CHTR:CP$(CP)2:2240:RQST")
#! Record("CHTR:CP$(CP)2:2240:PIDTAG",2340,2142,0,1,"CHTR:CP$(CP)2:2240:PIDTAG")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../dbd/cryoTest.dbd")
#! DBDEND


record(ao, "CTDT:CP$(CP)2:2520:A:SP") {
  field(DESC, "DT22520A setpoint")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(PREC, "3")
  field(EGU, "K")
  field(ADEL, "0.001")
  field(IVOA, "Don't drive outputs")
  field(OUT, "@$(PLC_NAME) TDT22520A_SP")
}

record(stringin, "CTDT:CP$(CP)2:2520:A:PIDTAG") {
  field(DESC, "SP PIDtag")
  field(PINI, "YES")
  field(VAL, "C$(CP)TDT22520A")
}

#! Further lines contain data used by VisualDCT
#! View(1774,1984,1.0)
#! Record("CTDT:CP$(CP)2:2520:A:SP",2060,2119,0,1,"CTDT:CP$(CP)2:2520:A:SP")
#! Record("CTDT:CP$(CP)2:2520:A:PIDTAG",2340,2142,0,1,"CTDT:CP$(CP)2:2520:A:PIDTAG")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBD("../../dbd/cryoTest.dbd")
#! DBDEND


record(ao, "CTDT:CP$(CP)2:2520:B:SP") {
  field(DESC, "DT22520B setpoint")
  field(ASG, "CRYO")
  field(PINI, "NO")
  field(DTYP, "EtherIP")
  field(PREC, "3")
  field(EGU, "K")
  field(ADEL, "0.001")
  field(IVOA, "Don't drive outputs")
  field(OUT, "@$(PLC_NAME) TDT22520B_SP")
}

record(stringin, "CTDT:CP$(CP)2:2520:B:PIDTAG") {
  field(DESC, "SP PIDtag")
  field(PINI, "YES")
  field(VAL, "C$(CP)TDT22520B")
}

#! Further lines contain data used by VisualDCT
#! View(1774,1984,1.0)
#! Record("CTDT:CP$(CP)2:2520:B:SP",2060,2119,0,1,"CTDT:CP$(CP)2:2520:B:SP")
#! Record("CTDT:CP$(CP)2:2520:B:PIDTAG",2340,2142,0,1,"CTDT:CP$(CP)2:2520:B:PIDTAG")
record(ai, "CVAC:CP$(CP)2:3610:RPTMRPRE") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) UCB_T1.PRE")
  field(EGU, "ms")
  field(DESC, "X411 UCB Rgh Pmp Tmr Preset")
  field(ADEL, "0")
  field(MDEL, "0")
  field(PINI, "YES")
}

record(ai, "CVAC:CP$(CP)2:3610:RPTMRACC") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) UCB_T1.ACC")
  field(EGU, "ms")
  field(DESC, "X411 UCB Rgh Pmp Tmr Accum.")
  field(ADEL, "0")
  field(MDEL, "0")
  field(PINI, "YES")
}


record(ai, "CVAC:CP$(CP)2:3630:RPTMRPRE") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) LCB_T1.PRE")
  field(EGU, "ms")
  field(DESC, "X411 LCB Rgh Pmp Tmr Preset")
  field(ADEL, "0")
  field(MDEL, "0")
  field(PINI, "YES")
}

record(ai, "CVAC:CP$(CP)2:3630:RPTMRACC") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) LCB_T1.ACC")
  field(EGU, "ms")
  field(DESC, "X411 LCB Rgh Pmp Tmr Accum.")
  field(ADEL, "0")
  field(MDEL, "0")
  field(PINI, "YES")
}


record(ai, "CVAC:CP$(CP)2:3610:DPTMRPRE") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) DP23610TON.PRE")
  field(EGU, "ms")
  field(DESC, "X413 UCB Diff Pmp Tmr Preset")
  field(ADEL, "0")
  field(MDEL, "0")
  field(PINI, "YES")
}

record(ai, "CVAC:CP$(CP)2:3610:DPTMRACC") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) DP23610TON.ACC")
  field(EGU, "ms")
  field(DESC, "X413 UCB Diff Pmp Tmr Accum.")
  field(ADEL, "0")
  field(MDEL, "0")
  field(PINI, "YES")
}


record(ai, "CVAC:CP$(CP)2:3630:DPTMRPRE") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) DP23630TON.PRE")
  field(EGU, "ms")
  field(DESC, "X413 LCB Diff Pmp Tmr Preset")
  field(ADEL, "0")
  field(MDEL, "0")
  field(PINI, "YES")
}

record(ai, "CVAC:CP$(CP)2:3630:DPTMRACC") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC_NAME) DP23630TON.ACC")
  field(EGU, "ms")
  field(DESC, "X413 LCB Diff Pmp Tmr Accum.")
  field(ADEL, "0")
  field(MDEL, "0")
  field(PINI, "YES")
}