#! Generated by VisualDCT v2.6.1280 #! DBDSTART #! DBD("../../../dbd/cryoControl.dbd") #! DBDEND record(bi, "PLC:$(AREA):$(LOCA):LR_STATUS") { field(DESC, "PLC Local / Remote Status") field(SCAN, "1 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) Local_Remote_Status") field(ZNAM, "Remote") field(ONAM, "Local") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(bi, "PLC:$(AREA):$(LOCA):HSHK") { field(DESC, "EPICS/PLC Handshake Value") field(SCAN, "1 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) EPICS_Handshake_Value") field(ZNAM, "Remote") field(ONAM, "Local") } record(bi, "PLC:$(AREA):$(LOCA):PS1_STATUS") { field(DESC, "PLC Power Supply 1 Status") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) PSPL21X_1") field(ZNAM, "FAULT") field(ONAM, "OK") field(PINI, "YES") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bi, "PLC:$(AREA):$(LOCA):PS2_STATUS") { field(DESC, "PLC Power Supply 2 Status") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) PSPL21X_2") field(ZNAM, "FAULT") field(ONAM, "OK") field(PINI, "YES") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(mbbiDirect, "PLC:$(AREA):$(LOCA):Alarm1") { field(DESC, "PLC card faults") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) PLC_Alarm[0] B 0") } record(mbbiDirect, "PLC:$(AREA):$(LOCA):AlarmL") { field(DESC, "PLC card fault latches") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) PLC_AlarmL[0] B 0") } record(mbbiDirect, "PLC:$(AREA):$(LOCA):StatBit") { field(DESC, "PLC Stat Bit") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) PLC_StatBit[0] B 0") } record(bo, "PLC:$(AREA):$(LOCA):PS1_BYPASS") { field(DESC, "PLC PS1 fault bypassed") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp B 9") field(ZNAM, "ACT") field(ONAM, "BYP") } record(bo, "PLC:$(AREA):$(LOCA):PS2_BYPASS") { field(DESC, "PLC PS1 fault bypassed") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp B 10") field(ZNAM, "ACT") field(ONAM, "BYP") } record(bi, "PLC:$(AREA):$(LOCA):24VPS1_STATUS") { field(DESC, "PLC 24V PS 1 Status") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) PSPL21X_3") field(ZNAM, "FAULT") field(ONAM, "OK") field(PINI, "YES") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bo, "PLC:$(AREA):$(LOCA):24VPS1_BYPASS") { field(DESC, "PLC PS1 fault bypassed") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp B 11") field(ZNAM, "ACT") field(ONAM, "BYP") } record(bi, "PLC:$(AREA):$(LOCA):24VPS2_STATUS") { field(DESC, "PLC 24V PS 2 Status") field(SCAN, "2 second") field(DTYP, "EtherIP") field(INP, "@$(PLC_NAME) PSPL21X_4") field(ZNAM, "FAULT") field(ONAM, "OK") field(PINI, "YES") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } record(bo, "PLC:$(AREA):$(LOCA):24VPS2_BYPASS") { field(DESC, "PLC PS1 fault bypassed") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp B 12") field(ZNAM, "ACT") field(ONAM, "BYP") } record(bo, "PLC:$(AREA):$(LOCA):B0_BYPASS") { field(DESC, "PLC card fault bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp B 0") field(ZNAM, "ACT") field(ONAM, "BYP") } record(bo, "PLC:$(AREA):$(LOCA):B1_BYPASS") { field(DESC, "PLC card fault bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp B 1") field(ZNAM, "ACT") field(ONAM, "BYP") } record(bo, "PLC:$(AREA):$(LOCA):B2_BYPASS") { field(DESC, "PLC card fault bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp B 2") field(ZNAM, "ACT") field(ONAM, "BYP") } record(bo, "PLC:$(AREA):$(LOCA):B3_BYPASS") { field(DESC, "PLC card fault bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp B 3") field(ZNAM, "ACT") field(ONAM, "BYP") } record(bo, "PLC:$(AREA):$(LOCA):B4_BYPASS") { field(DESC, "PLC card fault bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp B 4") field(ZNAM, "ACT") field(ONAM, "BYP") } record(bo, "PLC:$(AREA):$(LOCA):B5_BYPASS") { field(DESC, "PLC card fault bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp B 5") field(ZNAM, "ACT") field(ONAM, "BYP") } record(bo, "PLC:$(AREA):$(LOCA):B6_BYPASS") { field(DESC, "PLC card fault bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp B 6") field(ZNAM, "ACT") field(ONAM, "BYP") } record(bo, "PLC:$(AREA):$(LOCA):B7_BYPASS") { field(DESC, "PLC card fault bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp B 7") field(ZNAM, "ACT") field(ONAM, "BYP") } record(bo, "PLC:$(AREA):$(LOCA):B8_BYPASS") { field(DESC, "PLC card fault bypass") field(SCAN, "Passive") field(DTYP, "EtherIP") field(OUT, "@$(PLC_NAME) PLC_Alarm_Byp B 8") field(ZNAM, "ACT") field(ONAM, "BYP") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:$(AREA):$(LOCA):LR_STATUS",1020,92,0,1,"PLC:$(AREA):$(LOCA):LR_STATUS") #! Record("PLC:$(AREA):$(LOCA):HSHK",20,120,0,0,"PLC:$(AREA):$(LOCA):HSHK") #! Record("PLC:$(AREA):$(LOCA):PS1_STATUS",620,119,0,1,"PLC:$(AREA):$(LOCA):PS1_STATUS") #! Record("PLC:$(AREA):$(LOCA):PS2_STATUS",820,119,0,1,"PLC:$(AREA):$(LOCA):PS2_STATUS") #! Record("PLC:$(AREA):$(LOCA):Alarm1",1020,388,0,1,"PLC:$(AREA):$(LOCA):Alarm1") #! Record("PLC:$(AREA):$(LOCA):AlarmL",1020,268,0,1,"PLC:$(AREA):$(LOCA):AlarmL") #! Record("PLC:$(AREA):$(LOCA):StatBit",1020,508,0,1,"PLC:$(AREA):$(LOCA):StatBit") #! Record("PLC:$(AREA):$(LOCA):PS1_BYPASS",220,320,0,0,"PLC:$(AREA):$(LOCA):PS1_BYPASS") #! Record("PLC:$(AREA):$(LOCA):PS2_BYPASS",420,320,0,1,"PLC:$(AREA):$(LOCA):PS2_BYPASS") #! Record("PLC:$(AREA):$(LOCA):24VPS1_STATUS",420,119,0,1,"PLC:$(AREA):$(LOCA):24VPS1_STATUS") #! Record("PLC:$(AREA):$(LOCA):24VPS1_BYPASS",620,320,0,1,"PLC:$(AREA):$(LOCA):24VPS1_BYPASS") #! Record("PLC:$(AREA):$(LOCA):24VPS2_STATUS",220,119,0,1,"PLC:$(AREA):$(LOCA):24VPS2_STATUS") #! Record("PLC:$(AREA):$(LOCA):24VPS2_BYPASS",820,320,0,1,"PLC:$(AREA):$(LOCA):24VPS2_BYPASS") #! Record("PLC:$(AREA):$(LOCA):B0_BYPASS",223,480,0,1,"PLC:$(AREA):$(LOCA):B0_BYPASS") #! Record("PLC:$(AREA):$(LOCA):B1_BYPASS",423,480,0,1,"PLC:$(AREA):$(LOCA):B1_BYPASS") #! Record("PLC:$(AREA):$(LOCA):B2_BYPASS",620,480,0,1,"PLC:$(AREA):$(LOCA):B2_BYPASS") #! Record("PLC:$(AREA):$(LOCA):B3_BYPASS",820,480,0,1,"PLC:$(AREA):$(LOCA):B3_BYPASS") #! Record("PLC:$(AREA):$(LOCA):B4_BYPASS",223,640,0,1,"PLC:$(AREA):$(LOCA):B4_BYPASS") #! Record("PLC:$(AREA):$(LOCA):B5_BYPASS",423,640,0,1,"PLC:$(AREA):$(LOCA):B5_BYPASS") #! Record("PLC:$(AREA):$(LOCA):B6_BYPASS",620,640,0,1,"PLC:$(AREA):$(LOCA):B6_BYPASS") #! Record("PLC:$(AREA):$(LOCA):B7_BYPASS",820,640,0,1,"PLC:$(AREA):$(LOCA):B7_BYPASS") #! Record("PLC:$(AREA):$(LOCA):B8_BYPASS",1021,640,0,1,"PLC:$(AREA):$(LOCA):B8_BYPASS")