# PRIM is EPICS device primary
# LOCA is EPICS location
# UNIT is device unit number
# ATTR is EPICS attribute
# DPRIM is SLC digital primary
# MICRO is location of CAMAC hardware
# DUNIT is SLC digital unit number
# DNAME is SLC digital device name
# NAM is state name string
# BITB is channel number, modulo 16, converted to binary notation
# CRAT is crate number
# SLOT is slot number (2 digits; leading 0 if needed)
# ADDR is module port number, 0 for channels 0-15, 1 for channels 16-31

record(bo, "$(PRIM):$(LOCA):$(UNIT):$(ATTR)") {
  field(DESC, "$(DPRIM) $(MICRO) $(DUNIT) $(DNAME)")
  field(ZNAM, "")
  field(ONAM, "$(NAM)")
  field(VAL, "0")
  field(PINI, "YES")
  field(OUT, "$(PRIM):$(LOCA):$(UNIT):$(ATTR)_LOG PP")
  field(ASG, "$(ASG)")
  field(FLNK, "$(PRIM):$(LOCA):$(UNIT):$(ATTR)_CALC")
}

record(calcout, "$(PRIM):$(LOCA):$(UNIT):$(ATTR)_CALC") {
  field(DESC, "")
  field(CALC, "A?B:0")
  field(INPA, "$(PRIM):$(LOCA):$(UNIT):$(ATTR)")
  field(INPB, "$(BITB)")
  field(OOPT, "When Non-zero")
  field(ASG, "$(ASG)")
  field(OUT, "$(PRIM):$(LOCA):$(UNIT):$(ATTR)_HWSET PP")
}

record(mbboDirect, "$(PRIM):$(LOCA):$(UNIT):$(ATTR)_HWSET") {
  field(DESC, "Set HW level off")
  field(DTYP, "IDOM")
  field(OMSL, "closed_loop")
  field(DOL, "$(PRIM):$(LOCA):$(UNIT):$(ATTR)_CALC")
  field(ASG, "$(ASG)")
  field(OUT,  "#B0 C$(CRAT) N$(SLOT) A$(ADDR) F21@LEVEL_SELECT")
}

record(bo, "$(PRIM):$(LOCA):$(UNIT):$(ATTR)_LOG") {
  field(DESC, "Log device state")
  field(VAL, "0")
  field(HIGH, "1")
  field(ASG, "$(ASG)")
  field(ONAM, "$(NAM)")
}

record(stringin, "$(PRIM):$(LOCA):$(UNIT):$(ATTR)_DESC") {
  field(DESC, "Additional desc")
  field(VAL, " ")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}