# PRIM is EPICS device primary # LOCA is EPICS location # UNIT is device unit number # ATTR is EPICS attribute # DPRIM is SLC digital primary # MICRO is location of CAMAC hardware # NAM is state name string # BITB is channel number, modulo 16-31, converted to binary notation # CRAT is crate number # SLOT is slot number (2 digits; leading 0 if needed) # Pulse On selected channel 16-31, bit=1 pulse out, bit=0 nochange. # If the output is off, it will pulse on for the defined time interval. # If the output is on prior to the command, it will go off after # the defined time interval. The pulse period may be set by a prior # F17A0. If it has not been preset, the default pulse period is used. record(bo, "$(NAME)") { field(DESC, "$(DESC)") field(ZNAM, "Reset") field(ONAM, "Reset") field(FLNK, "MODU:$(MICRO):$(CRAT)$(SLOT):HWPULSEON") } record(longout, "MODU:$(MICRO):$(CRAT)$(SLOT):HWPULSEONARG") { field(DESC, "IDOM pulse on chan") field(PINI, "YES") field(VAL, "$(CHAN)") } record(mbboDirect, "MODU:$(MICRO):$(CRAT)$(SLOT):HWPULSEON") { field(DESC, "IDOM Pulse On Ch") field(DTYP, "IDOM") field(OUT, "#B0 C$(CRAT) N$(SLOT) A1 F19@PULSE") field(DOL, "MODU:$(MICRO):$(CRAT)$(SLOT):HWPULSEONARG") field(OMSL, "closed_loop") }