# Thermocouple type "T" Reference Conversion from volts to degC # Convert the sam channel volts to current # A - volts # C - sam max voltage # D - simulatation mode (0=Off,1=On) # E - simulatation volts record(calc, "$(NAME)Curr") { field(DESC, "Temp Ref Current") field(CALC, "B?(C-A)/B:0") field(INPA, "$(NAME)VRaw NPP MS") field(INPB, "1005100") field(INPC, "10.24") field(EGU, "Amp") field(PREC, "2") field(FLNK, "$(NAME)Resistance") } record(calcout, "$(NAME)Resistance") { field(DESC, "Temp Ref Resistance") field(CALC, "B?A/B:0") field(IVOA, "Continue normally") field(INPA, "$(NAME)VRaw") field(INPB, "$(NAME)Curr NPP MS") field(EGU, "Ohm") field(PREC, "2") field(OUT, "$(NAME)Tbar.D PP") } # INPD - Resistance record(calc, "$(NAME)Tbar") { field(DESC, "$(DESC)") field(ASG, "Internal") field(CALC, "D>0?(A+B*LOGE(D)+C*(LOGE(D))^3):0") field(INPA, "1.46161E-3") field(INPB, "2.39427E-4") field(INPC, "9.59358E-8") field(PREC, "2") field(FLNK, "$(NAME)Kelvin") } record(calc, "$(NAME)Kelvin") { field(DESC, "$(DESC)") field(DESC, "Temp Ref in Kelvin") field(CALC, "A#0?1.0/A:0") field(INPA, "$(NAME)Tbar") field(EGU , "K") field(PREC, "2") field(FLNK, "$(NAME)Check") } # Convert from Kelvin to Celsius and check for invalid raw data # A - ref temp in Kelvin # B - offset to convert from Kelvin to ref temp in DegC # C - raw data serverity # D - raw data status # E - value that indicates illegal value record(calcout, "$(NAME)Check") { field(DESC, "$(DESC)") field(ASG, "Internal") field(CALC, "C=3&&(D=4||D=6)?E:A-B") field(IVOA, "Continue normally") field(INPA, "$(NAME)Kelvin") field(INPB, "273.15") # If if the raw data has an invalid severity due to # a low or high alarm status, then set the reference # temperature to an illegal value in E, because the # raw data is out of range. field(INPC, "$(NAME)VRaw.SEVR") field(INPD, "$(NAME)VRaw.STAT") field(INPE, "-573.0") field(EGU, "Deg. C") field(OUT, "$(NAME) PP") field(FLNK, "$(NAME)_T") } record(ai, "$(NAME)") { field(DESC, "$(DESC)") field(EGU, "Deg. C") field(PREC, "$(PREC=0)") field(HIHI, "$(HIHI)") field(HIGH, "$(HIGH)") field(LOLO, "$(LOLO)") field(LOW, "$(LOW)") field(HHSV, "$(HHSV)") field(HSV, "$(HSV)") field(HYST, "$(HYST=0)") field(FLNK, "$(NAME)VCor") } # Convert from degC to mV. This pv is # used in the conversion to degC # for SAM Channels 0-14 and 16-30. record(sub, "$(NAME)VCor") { field(DESC, "$(DESC)") field(ASG, "Internal") field(INAM, "InitPoly") field(SNAM, "CalcPolySpear") field(INPA, "0.0E00") field(INPB, "0.387481063640E-01") field(INPC, "0.332922278800E-04") field(INPD, "0.206182434040E-06") field(INPE, "-0.218822568460E-08") field(INPF, "0.109968809280E-10") field(INPG, "-0.308157587720E-13") field(INPH, "0.454791352900E-16") field(INPI, "-0.275129016730E-19") field(INPL, "$(NAME).VAL NPP MS") field(EGU, "mV") field(PREC, "6") field(FLNK, "$(NAME)F") } record(calc, "$(NAME)F") { field(DESC, "$(DESC)") field(CALC, "A*1.8+32") field(INPA, "$(NAME)") field(EGU, "Deg. F") field(PREC, "2") } # Clemens function: to_tctemp(volts,ref_volts) # # Input: # A - reference temperature # B - lower limit range of raw data # C - upper limit range of raw data # # Output: # F - current # G - resistance # H - ref temperature in kelvin # I - ref temperature in celsius # J - voltage error due to temp of ref plane # Note: if this function is working properly # then record(sub, "$(NAME)_T") { field(DESC, "$(DESC)") field(INAM, "InitAnalogCalc") field(SNAM, "AnalogTcRefTemp") field(INPA, "$(NAME)VRaw NPP MS") field(INPB, "$(NAME)VRaw.LOW") field(INPC, "$(NAME)VRaw.HIGH") field(PREC, "$(PREC=0)") field(EGU, "Deg. C") field(BRSV, "INVALID") field(FLNK, "$(NAME)VPlate") } # This is the voltage error due to the temperature of # the reference plane. If the plane were at 0 degC, then # the vplate would be 0. This is used in when calculating # temperatures for SAM channels 0-14 and 15-30. record(ai, "$(NAME)VPlate") { field(DESC, "$(DESC)") field(INP, "$(NAME)_T.J NPP MS") field(PREC, "$(PREC=0)") }