record(ai, "MODU:$(MICRO):$(CRAT)$(SLOT):CH$(CHAN)") { field(DESC, "$(NAME)") field(DTYP, "SAM") field(SCAN, "$(SCAN=1 second)") field(INP, "#B0 C$(CRAT) N$(SLOT) F17 A$(CHAN)@DATA") field(EGU, "V") field(PREC, "8") field(ADEL, ".0001") field(HOPR, "10") field(LOPR, "-10") field(PINI, "YES") field(FLNK, "$(NAME)VacuumVRaw") # field(SDIS, "MODU:$(MICRO):$(CRAT)$(SLOT):STATUS NPP") } record(ai, "$(NAME)VacuumVRaw") { field(DESC, "SAM Card $(SLOT) Ch $(CHAN)") field(INP, "MODU:$(MICRO):$(CRAT)$(SLOT):CH$(CHAN) NPP MS") field(PREC, "8") field(EGU, "V") field(HIGH, "10.0") field(HOPR, "10.0") field(LOPR, "0.0") field(LOW, "0.0") field(HSV, "INVALID") field(ADEL, "0.0001") field(SIOL, "$(NAME)VacuumSimVRaw") field(SIML, "$(NAME)VacuumSim") field(FLNK, "$(NAME)VacuumVRaw_T.A") } # Determine if data is valid. If it is # then pass it on, otherwise set the raw data # to zero. # A - raw data (SAM Channel 0-31) # B - raw data pv severity record(calcout, "$(NAME)VacuumVRaw_T") { field(DESC, "$(DESC) Volt") field(CALC, "(B#4)&&(A<10.)?A:0") field(INPA, "$(NAME)VacuumVRaw NPP MS") field(INPE, "$(NAME)VacuumVRaw.SEVR") field(PREC, "8") field(EGU, "V") field(OUT, "$(NAME)VacuumCalc.A PP NMS") } # Clemens VMS function: to_vacgauge_330(volts) # # Calculate mrem from voltage. If the # voltage is >10V, then the data # is considered out of range. # # A - raw data (SAM Channel 0-31) # B - used to convert from volts to torr record(calc, "$(NAME)VacuumCalc") { field(CALC, "A=0?A:10**(A-B)") field(DESC, "$(DESC) Torr") field(INPA, "$(NAME)VacuumVRaw_T NPP NMS") field(INPB, "12.0") field(EGU, "Torr") field(PREC, "13") field(HOPR, "1E-6") field(LOPR, "1E-12") field(FLNK, "$(NAME)Vacuum") } record(ai, "$(NAME)Vacuum") { field(DESC, "$(DESC) Torr") field(INP, "$(NAME)VacuumCalc") field(EGU, "Torr") field(PREC, "13") field(HOPR, "1E-6") field(LOPR, "1E-12") field(HYST, "1E-11") field(LOW, "9E-12") field(HIHI, "$(HIHI=5E-7)") field(HIGH, "1E-7") field(HHSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(FLNK, "$(NAME)StateCalc") } # Note: the pvs StatusCalc and State were moved from EtherIoc camac_vacuum_gauge.db record(calcout, "$(NAME)StateCalc") { field(DESC, "$(DESC) State Calc") field(INPA, "$(NAME)Vacuum NPP NMS") field(INPB, "1E-12") field(CALC, "A