record(ai, "MODU:$(MICRO):$(CRAT)$(SLOT):CH$(CHAN)") { field(DESC, "$(NAME)") field(DTYP, "SAM") field(SCAN, "$(SCAN=1 second)") field(INP, "#B0 C$(CRAT) N$(SLOT) F17 A$(CHAN)@DATA") field(EGU, "V") field(PREC, "8") field(ADEL, ".0001") field(HOPR, "10") field(LOPR, "-10") field(PINI, "YES") field(FLNK, "$(NAME)VRaw") # field(SDIS, "MODU:$(MICRO):$(CRAT)$(SLOT):STATUS NPP") } record(ai, "$(NAME)VRaw") { field(DESC, "SAM Card $(SLOT) Ch $(CHAN)") field(INP, "MODU:$(MICRO):$(CRAT)$(SLOT):CH$(CHAN) NPP MS") field(PREC, "8") field(EGU, "V") field(HIGH, "10.0") field(HOPR, "10.0") field(HSV, "INVALID") field(ADEL, "0.0001") field(SIOL, "$(NAME)SimVRaw") field(SIML, "$(NAME)Sim") field(FLNK, "$(NAME)VRaw_T.A") } # If data data is >10V then it # is considered invalid and set to zero. # before being converted to uA # # If thevoltage is >10V, then the data # is considered out of range. # # A - raw data (SAM Channel 0-31) # B = raw data pv severity record(calcout, "$(NAME)VRaw_T") { field(DESC, "$(DESC) Volt") field(CALC, "B#4?A:0") field(INPA, "$(NAME)VRaw NPP MS") field(INPB, "$(NAME)VRaw.SEVR") field(PREC, "8") field(EGU, "V") field(OUT, "$(NAME)Calc.A PP NMS") } # Clemens VMS function uses a # standard slope-offset formula # to convert volts to uA. # # A - raw data (SAM Channel 0-31) # B - used to convert from volts to torr # C - offset, default set to 0 record(calc, "$(NAME)Calc") { field(DESC, "$(DESC) mA") field(CALC, "A*B+C") field(INPA, "$(NAME)VRaw NPP NMS") field(INPB, "$(ESLO=1.0)") field(INPC, "$(EOFF=0.0)") field(EGU, "uA") field(PREC, "1") field(HOPR, "600") field(FLNK, "$(NAME)") } # scondam: 25-Oct-2018: Per SPEAR vacuum team, set the HIHI,HIGH,LOW,LOLO alarm limits. record(ai, "$(NAME)") { field(DESC, "$(DESC) mA") field(INP, "$(NAME)Calc NPP MS") field(EGU, "uA") field(PREC, "1") field(HOPR, "4000") field(HIHI, "4000.0") field(HIGH, "3500.0") field(LOLO, "-550.0") field(LOW, "-500.0") field(HSV, "MINOR") field(LLSV, "MAJOR") field(HYST, "$(HYST=5.0)") field(FLNK, "$(NAME)StateCalc") } # StateCalc and State come from EtherIoc camac_vacuum_pump.db record(calcout, "$(NAME)StateCalc") { field(DESC, "$(DESC) State Calc") field(ASG, "Internal") field(INPA, "$(NAME) MS") field(INPB, "$(NAME).LOLO") field(INPC, "$(NAME).SEVR") field(CALC, "(C<2.5)&&(A