record(ai, "MODU:$(MICRO):$(CRAT)$(SLOT):CH$(CHAN)") { field(DESC, "$(NAME)") field(DTYP, "SAM") field(SCAN, "$(SCAN=1 second)") field(INP, "#B0 C$(CRAT) N$(SLOT) F17 A$(CHAN)@DATA") field(EGU, "V") field(PREC, "8") field(ADEL, ".0001") field(HOPR, "10") field(LOPR, "-10") field(PINI, "YES") field(FLNK, "$(NAME)RateVRaw") # field(SDIS, "MODU:$(MICRO):$(CRAT)$(SLOT):STATUS NPP") } record(ai, "$(NAME)RateVRaw") { field(DESC, "SAM Card $(SLOT) Ch $(CHAN)") field(INP, "MODU:$(MICRO):$(CRAT)$(SLOT):CH$(CHAN) NPP MS") field(PREC, "8") field(EGU, "V") field(HIGH, "10.0") field(HOPR, "10.0") field(LOPR, "0.0") field(LOW, "0.0") field(HSV, "INVALID") field(LSV, "INVALID") field(ADEL, "0.0001") field(SIOL, "$(NAME)RateSimVRaw") field(SIML, "$(NAME)RateSim") field(FLNK, "$(NAME)RateVRaw_T.A") } # Determine if data is valid. If it is # then pass it on, otherwise set the raw data # to zero. # A - raw data (SAM Channel 0-31) # B = raw data pv severity record(calcout, "$(NAME)RateVRaw_T") { field(DESC, "$(DESC) Volt") field(CALC, "B#4?A:0") field(INPA, "$(NAME)RateVRaw NPP MS") field(INPB, "$(NAME)RateVRaw.SEVR") field(PREC, "8") field(EGU, "V") field(OUT, "$(NAME)Rate_CALC.A PP NMS") } # Clemens function: to_bsoic(volts) # Note: the function to_bsoic has been converted # to the EPICS subroutine AnalogBsoicRate # # Calculate mrem from voltage. If the # voltage is <= 0V or >= 10V, then the data # is considered out of range, and invalide. # # A - raw data (SAM Channel 0-31) # B - used to convert from volts to mrem record(calc, "$(NAME)Rate_CALC") { field(DESC, "$(DESC) mrem/h") field(ASG, "Internal") field(CALC, "A?10**(B*A):0") field(INPA, "$(NAME)RateVRaw NPP NMS") field(EGU, "mrem/h") field(PREC, "2") field(INPB, "0.6") field(FLNK, "$(NAME)Rate") } record(ai, "$(NAME)Rate") { field(DESC, "$(DESC) mrem/h") field(INP, "$(NAME)Rate_CALC NPP NMS") field(EGU, "mrem/h") field(PREC, "2") field(HYST, "0.15") field(MDEL, "0.02") field(HOPR, "10") field(HIHI, "$(HIHI=789.082)") field(HIGH, "$(HIGH=5)") field(LOLO, "$(LOLO=1.148)") field(HHSV, "$(HHSV=INVALID)") field(HSV, "$(HSV=MINOR)") field(LLSV, "$(LLSV=MAJOR)") field(FLNK, "$(NAME)ALRM") } # Simulation PVs record(bo, "$(NAME)RateSim") { field(DESC, "Simulation Mode") field(PINI, "YES") field(ZNAM, "Off") field(ONAM, "On") } record(ao, "$(NAME)RateSimVRaw") { field(DESC,"Simulatated Raw Volts") field(EGU, "V") field(HIGH, "10.0") field(HOPR, "10.0") field(LOPR, "0.0") field(LOW, "0.0") field(HSV, "INVALID") field(LSV, "INVALID") field(PINI, "YES") field(VAL, "$(RAW=0.01)") }