# INPA to INPH = Coefficients for the given bunch length monitor. INPH can also
# hold the TMIT PV. You can't use it for both purposes.
# Normally TMIT is from fcom. To get it from CA instead, put the PV in TMIT_LNK
# and define gTmitFromCA=1 in st.cmd.
# STA is one based, and needs to match PADSLOT in the PAD's st.cmd.
# CHNIDX is 4-7. 0-3 are for "Sum", not "Imax".
# INPI = divide by number to be used  when filter is not in
# INPJ = filter in state, 1=filter in
# Note: EVNT isn't an event code, it's 0x7A + STA -1, see epics_event_no in drvBlm.c
record(sub, "BLEN:LI20:3014:AIMAX") {
  field(INPA, "0")
  field(INPB, "5462.5")
  field(INPC, "-0.5")
  field(INPD, "0.75")
  field(INPE, "0")
  field(INPF, "0")
  field(INPG, "0")
  field(INPH, "BPMS:LI20:3156:TMITBR")
  field(INPI, "0")
  field(INPJ, "0")
  field(INPK, "5")
  field(INPL, "4")
  field(SNAM, "fbckSupIpkCalc")
  field(MDEL, "-1")
  field(EGU,  "A")
  field(TSE,  "-2")
  field(SCAN, "Event")
  field(EVNT, "126")
  field(PRIO, "HIGH")
  field(FLNK, "BLEN:LI20:3014:EFAIMAX")
  info(autosaveFields,"INPA INPB INPC INPD INPE INPF INPG INPH INPI")
}
# INPA to INPH = Coefficients for the given bunch length monitor. INPH can also
# hold the TMIT PV. You can't use it for both purposes.
# Normally TMIT is from fcom. To get it from CA instead, put the PV in TMIT_LNK
# and define gTmitFromCA=1 in st.cmd.
# STA is one based, and needs to match PADSLOT in the PAD's st.cmd.
# CHNIDX is 4-7. 0-3 are for "Sum", not "Imax".
# INPI = divide by number to be used  when filter is not in
# INPJ = filter in state, 1=filter in
# Note: EVNT isn't an event code, it's 0x7A + STA -1, see epics_event_no in drvBlm.c
record(sub, "BLEN:LI20:3014:BIMAX") {
  field(INPA, "0")
  field(INPB, "5462.5")
  field(INPC, "-0.5")
  field(INPD, "0.75")
  field(INPE, "0")
  field(INPF, "0")
  field(INPG, "0")
  field(INPH, "BPMS:LI20:3156:TMITBR")
  field(INPI, "0")
  field(INPJ, "0")
  field(INPK, "5")
  field(INPL, "5")
  field(SNAM, "fbckSupIpkCalc")
  field(MDEL, "-1")
  field(EGU,  "A")
  field(TSE,  "-2")
  field(SCAN, "Event")
  field(EVNT, "126")
  field(PRIO, "HIGH")
  field(FLNK, "BLEN:LI20:3014:EFBIMAX")
  info(autosaveFields,"INPA INPB INPC INPD INPE INPF INPG INPH INPI")
}
# INPA to INPH = Coefficients for the given bunch length monitor. INPH can also
# hold the TMIT PV. You can't use it for both purposes.
# Normally TMIT is from fcom. To get it from CA instead, put the PV in TMIT_LNK
# and define gTmitFromCA=1 in st.cmd.
# STA is one based, and needs to match PADSLOT in the PAD's st.cmd.
# CHNIDX is 4-7. 0-3 are for "Sum", not "Imax".
# INPI = divide by number to be used  when filter is not in
# INPJ = filter in state, 1=filter in
# Note: EVNT isn't an event code, it's 0x7A + STA -1, see epics_event_no in drvBlm.c
record(sub, "THZR:LI20:3075:CIMAX") {
  field(INPA, "0")
  field(INPB, "5462.5")
  field(INPC, "-0.5")
  field(INPD, "0.75")
  field(INPE, "0")
  field(INPF, "0")
  field(INPG, "0")
  field(INPH, "BPMS:LI20:3156:TMITBR")
  field(INPI, "0")
  field(INPJ, "0")
  field(INPK, "5")
  field(INPL, "6")
  field(SNAM, "fbckSupIpkCalc")
  field(MDEL, "-1")
  field(EGU,  "A")
  field(TSE,  "-2")
  field(SCAN, "Event")
  field(EVNT, "126")
  field(PRIO, "HIGH")
  field(FLNK, "THZR:LI20:3075:EFCIMAX")
  info(autosaveFields,"INPA INPB INPC INPD INPE INPF INPG INPH INPI")
}
# INPA to INPH = Coefficients for the given bunch length monitor. INPH can also
# hold the TMIT PV. You can't use it for both purposes.
# Normally TMIT is from fcom. To get it from CA instead, put the PV in TMIT_LNK
# and define gTmitFromCA=1 in st.cmd.
# STA is one based, and needs to match PADSLOT in the PAD's st.cmd.
# CHNIDX is 4-7. 0-3 are for "Sum", not "Imax".
# INPI = divide by number to be used  when filter is not in
# INPJ = filter in state, 1=filter in
# Note: EVNT isn't an event code, it's 0x7A + STA -1, see epics_event_no in drvBlm.c
record(sub, "THZR:LI20:3075:DIMAX") {
  field(INPA, "0")
  field(INPB, "5462.5")
  field(INPC, "-0.5")
  field(INPD, "0.75")
  field(INPE, "0")
  field(INPF, "0")
  field(INPG, "0")
  field(INPH, "BPMS:LI20:3156:TMITBR")
  field(INPI, "0")
  field(INPJ, "0")
  field(INPK, "5")
  field(INPL, "7")
  field(SNAM, "fbckSupIpkCalc")
  field(MDEL, "-1")
  field(EGU,  "A")
  field(TSE,  "-2")
  field(SCAN, "Event")
  field(EVNT, "126")
  field(PRIO, "HIGH")
  field(FLNK, "THZR:LI20:3075:EFDIMAX")
  info(autosaveFields,"INPA INPB INPC INPD INPE INPF INPG INPH INPI")
}
record(mbbo, "BLEN:LI20:3014:BL31_ACCESS") {
	field(DESC, "BPM On Line")
	field(DTYP, "StreamSwitch")
# card: set pad to correct enum for this station (src/llrfMacros.h)
# signal: 0 means reg bpm data (not cal data)
	field(OUT,  "#C5 S0")
	field(ZRVL, "1")
	field(ZRST, "Running")
	field(ZRSV, "NO_ALARM")
	field(ONVL, "1")
	field(ONST, "Maintenance")
	field(ONSV, "MINOR")
	field(TWVL, "1")
	field(TWST, "Test")
	field(TWSV, "MINOR")
	field(THVL, "0")
	field(THST, "OFFLINE")
	field(THSV, "MAJOR")
# set both, rval and val to get it right
# regardless of whether devsup does conversion
# or not.
	field(RVAL, "0")
	field(VAL,  "0")
	field(PINI, "YES")
}
record(waveform, "BLEN:LI20:3014:BL31_WF_CP")
{
        field(DESC, "sums (2nd eth)")
        field(DTYP, "BLM")
        field(SCAN, "I/O Intr") 
        field(NELM, "4")
        field(INP,  "#C5 S0 @RowMajor") 
        #dbfType in base/include/dbFldTypes.h
        field(FTVL, "LONG") 
        field(FLNK, "")
        field(TSE,  "-2")
		field(PRIO, "HIGH") # Measure the effect
}
record(ai,"BLEN:LI20:3014:ARAW")
{
	field(EGU, "")
	field(DESC,"sum A")
	field(DTYP,"BLM")
	field(INP, "#@0 5 0")
	field(SCAN,"I/O Intr")
	field(FLNK,"BLEN:LI20:3014:EFARAW")
#	field(PINI,"YES")
	field(PREC,"3")
	field(HIGH,"0") 	
	field(LOW, "0") 	
	field(HIHI,"0") 	
	field(LOLO,"0") 	
	field(HOPR,"0") 	
	field(LOPR,"0") 	
	field(HSV, "NO_ALARM") 	
	field(LSV, "NO_ALARM") 	
	field(HHSV,"NO_ALARM") 	
	field(LLSV,"NO_ALARM") 	
    field(MDEL,"-1")
	field(PRIO,"HIGH")
	field(TSE, "-2")
}
record(ai,"BLEN:LI20:3014:BRAW")
{
	field(EGU, "")
	field(DESC,"sum B")
	field(DTYP,"BLM")
	field(INP, "#@0 5 1")
	field(SCAN,"I/O Intr")
	field(FLNK,"BLEN:LI20:3014:EFBRAW")
#	field(PINI,"YES")
	field(PREC,"3")
	field(HIGH,"0") 	
	field(LOW, "0") 	
	field(HIHI,"0") 	
	field(LOLO,"0") 	
	field(HOPR,"0") 	
	field(LOPR,"0") 	
	field(HSV, "NO_ALARM") 	
	field(LSV, "NO_ALARM") 	
	field(HHSV,"NO_ALARM") 	
	field(LLSV,"NO_ALARM") 	
    field(MDEL,"-1")
	field(PRIO,"HIGH")
	field(TSE, "-2")
}
record(ai,"THZR:LI20:3075:CRAW")
{
	field(EGU, "")
	field(DESC,"sum C")
	field(DTYP,"BLM")
	field(INP, "#@0 5 2")
	field(SCAN,"I/O Intr")
	field(FLNK,"THZR:LI20:3075:EFCRAW")
#	field(PINI,"YES")
	field(PREC,"3")
	field(HIGH,"0") 	
	field(LOW, "0") 	
	field(HIHI,"0") 	
	field(LOLO,"0") 	
	field(HOPR,"0") 	
	field(LOPR,"0") 	
	field(HSV, "NO_ALARM") 	
	field(LSV, "NO_ALARM") 	
	field(HHSV,"NO_ALARM") 	
	field(LLSV,"NO_ALARM") 	
    field(MDEL,"-1")
	field(PRIO,"HIGH")
	field(TSE, "-2")
}
record(ai,"THZR:LI20:3075:DRAW")
{
	field(EGU, "")
	field(DESC,"sum D")
	field(DTYP,"BLM")
	field(INP, "#@0 5 3")
	field(SCAN,"I/O Intr")
	field(FLNK,"THZR:LI20:3075:EFDRAW")
#	field(PINI,"YES")
	field(PREC,"3")
	field(HIGH,"0") 	
	field(LOW, "0") 	
	field(HIHI,"0") 	
	field(LOLO,"0") 	
	field(HOPR,"0") 	
	field(LOPR,"0") 	
	field(HSV, "NO_ALARM") 	
	field(LSV, "NO_ALARM") 	
	field(HHSV,"NO_ALARM") 	
	field(LLSV,"NO_ALARM") 	
    field(MDEL,"-1")
	field(PRIO,"HIGH")
	field(TSE, "-2")
}
record(ai,"BLEN:LI20:3014:BL31A_S_SUM")
{
	field(EGU, "")
	field(DESC,"sum A for display")
	field(DTYP,"BLM")
	field(INP, "#@0 5 0")
	field(SCAN,"1 second")
	field(FLNK,"")
#	field(PINI,"YES")
	field(PREC,"3")
	field(HIGH,"0") 	
	field(LOW, "0") 	
	field(HIHI,"0") 	
	field(LOLO,"0") 	
	field(HOPR,"0") 	
	field(LOPR,"0") 	
	field(HSV, "NO_ALARM") 	
	field(LSV, "NO_ALARM") 	
	field(HHSV,"NO_ALARM") 	
	field(LLSV,"NO_ALARM") 	
    field(MDEL,"0")
	field(PRIO,"LOW")
	field(TSE, "-2")
}
record(ai,"BLEN:LI20:3014:BL31B_S_SUM")
{
	field(EGU, "")
	field(DESC,"sum B for display")
	field(DTYP,"BLM")
	field(INP, "#@0 5 1")
	field(SCAN,"1 second")
	field(FLNK,"")
#	field(PINI,"YES")
	field(PREC,"3")
	field(HIGH,"0") 	
	field(LOW, "0") 	
	field(HIHI,"0") 	
	field(LOLO,"0") 	
	field(HOPR,"0") 	
	field(LOPR,"0") 	
	field(HSV, "NO_ALARM") 	
	field(LSV, "NO_ALARM") 	
	field(HHSV,"NO_ALARM") 	
	field(LLSV,"NO_ALARM") 	
    field(MDEL,"0")
	field(PRIO,"LOW")
	field(TSE, "-2")
}
record(ai,"BLEN:LI20:3014:BL31A_S_IPK")
{
	field(EGU, "A")
	field(DESC,"Ipk A for display")
	field(DTYP,"BLM")
	field(INP, "#@0 5 4")
	field(SCAN,"1 second")
	field(FLNK,"")
#	field(PINI,"YES")
	field(PREC,"3")
	field(HIGH,"0") 	
	field(LOW, "0") 	
	field(HIHI,"0") 	
	field(LOLO,"0") 	
	field(HOPR,"0") 	
	field(LOPR,"0") 	
	field(HSV, "NO_ALARM") 	
	field(LSV, "NO_ALARM") 	
	field(HHSV,"NO_ALARM") 	
	field(LLSV,"NO_ALARM") 	
    field(MDEL,"0")
	field(PRIO,"LOW")
	field(TSE, "-2")
}
record(ai,"BLEN:LI20:3014:BL31B_S_IPK")
{
	field(EGU, "A")
	field(DESC,"Ipk B for display")
	field(DTYP,"BLM")
	field(INP, "#@0 5 5")
	field(SCAN,"1 second")
	field(FLNK,"")
#	field(PINI,"YES")
	field(PREC,"3")
	field(HIGH,"0") 	
	field(LOW, "0") 	
	field(HIHI,"0") 	
	field(LOLO,"0") 	
	field(HOPR,"0") 	
	field(LOPR,"0") 	
	field(HSV, "NO_ALARM") 	
	field(LSV, "NO_ALARM") 	
	field(HHSV,"NO_ALARM") 	
	field(LLSV,"NO_ALARM") 	
    field(MDEL,"0")
	field(PRIO,"LOW")
	field(TSE, "-2")
}
record(waveform, "BLEN:LI20:3014:RWAV") {
	field(DESC, "Raw PAD Data")
	field(DTYP, "WavBuf")
# card number selects PAD, signal number selects 'kind'
	field(INP,  "#C5S0")
	field(SCAN, "I/O Intr")
# use LOW or HIGH to end up on the 'diagnostic' or 'full-rate' scan list
	field(PRIO, "LOW")
	field(NELM, "2048")
	field(FTVL, "SHORT")
	field(EGU,  "Counts")
	field(HOPR, "32767")
	field(LOPR, "-32768")
	field(TSE,  "-2")
	field(FLNK, "BLEN:LI20:3014:BL31A_S_R_WF")
}

record(aaiSubArr, "BLEN:LI20:3014:BL31A_S_R_WF") {
	field(DESC,  "Raw ADC data")
	field(INP,   "BLEN:LI20:3014:RWAV")
	field(NELM,  "512")
	field(INDX,  "0")
	field(FTVL, "SHORT")
	field(EGU,  "Counts")
	field(HOPR, "32767")
	field(LOPR, "-32768")
	field(FLNK, "BLEN:LI20:3014:BL31B_S_R_WF")
}

record(aaiSubArr, "BLEN:LI20:3014:BL31B_S_R_WF") {
	field(DESC,  "Raw ADC data")
	field(INP,   "BLEN:LI20:3014:RWAV")
	field(NELM,  "512")
	field(INDX,  "512")
	field(FTVL, "SHORT")
	field(EGU,  "Counts")
	field(HOPR, "32767")
	field(LOPR, "-32768")
	field(FLNK, "BLEN:LI20:3014:THZRA_S_R_WF")
}

record(aaiSubArr, "BLEN:LI20:3014:THZRA_S_R_WF") {
	field(DESC,  "Raw ADC data")
	field(INP,   "BLEN:LI20:3014:RWAV")
	field(NELM,  "512")
	field(INDX,  "1024")
	field(FTVL, "SHORT")
	field(EGU,  "Counts")
	field(HOPR, "32767")
	field(LOPR, "-32768")
	field(FLNK, "BLEN:LI20:3014:THZRB_S_R_WF")
}

record(aaiSubArr, "BLEN:LI20:3014:THZRB_S_R_WF") {
	field(DESC,  "Raw ADC data")
	field(INP,   "BLEN:LI20:3014:RWAV")
	field(NELM,  "512")
	field(INDX,  "1536")
	field(FTVL, "SHORT")
	field(EGU,  "Counts")
	field(HOPR, "32767")
	field(LOPR, "-32768")
}
record(aai, "BLEN:LI20:3014:BL31A_S_P_WF") {
	field(DESC, "Processed data for display")
	field(DTYP, "BLM_PROC")
	field(INP,  "#C5S0")
	field(SCAN, "I/O Intr")
	field(PRIO, "LOW")
# FTVL and NELM set from devSup
}
record(aai, "BLEN:LI20:3014:BL31B_S_P_WF") {
	field(DESC, "Processed data for display")
	field(DTYP, "BLM_PROC")
	field(INP,  "#C5S1")
	field(SCAN, "I/O Intr")
	field(PRIO, "LOW")
# FTVL and NELM set from devSup
}
record(aao, "BLEN:LI20:3014:BL31A_SCL_WF") {
	field(DESC, "Processed data for display")
	field(DTYP, "BLM_WEIGHT")
	field(OUT,  "#C5S0")
	field(HOPR, "32767")
	field(LOPR, "-32768")
        field(PINI, "YES")
        info(autosaveFields,"VAL HOPR LOPR")
# FTVL and NELM set from devSup
}
record(aao, "BLEN:LI20:3014:BL31B_SCL_WF") {
	field(DESC, "Processed data for display")
	field(DTYP, "BLM_WEIGHT")
	field(OUT,  "#C5S1")
	field(HOPR, "32767")
	field(LOPR, "-32768")
        field(PINI, "YES")
        info(autosaveFields,"VAL HOPR LOPR")
# FTVL and NELM set from devSup
}

record(bo, THZR:LI20:3075:PNEU) {
  field(DESC, "THZR:LI20:3075 Control")
  field(DTYP, "XYCOM-2445")
  field(OUT, "@bo0 P0 B0")
  field(ZNAM, "INSERT")
  field(ONAM, "RETRACT")
  field(PINI, "YES")
}

record(bi, THZR:LI20:3075:IN) {
  field(DESC, "THZR:LI20:3075 In")
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@bi0 P0 B0")
  field(ZNAM, "Inactive")
  field(ZSV,  "MAJOR")
  field(ONAM, "Active")
  field(FLNK, "THZR:LI20:3075:OUT")
}

record(bi, THZR:LI20:3075:OUT) {
  field(DESC, "THZR:LI20:3075 Out")
  field(DTYP, "XYCOM-2440")
  field(INP, "@bi0 P0 B1")
  field(ZNAM, "Inactive")
  field(ONAM, "Active")
  field(OSV,  "MAJOR")
  field(FLNK, "THZR:LI20:3075:TgtStsCalc")
}

record(calcout, "THZR:LI20:3075:_TRANS") {
  field(DESC, "THZR:LI20:3075 Transition")
  field(CALC, "!A && !B")
  field(INPA, "THZR:LI20:3075:IN  CPP MS")
  field(INPB, "THZR:LI20:3075:OUT CPP MS")
  field(OUT,  "THZR:LI20:3075:_TIMEOUT.VAL PP MS")
  field(OOPT, "On Change")
  field(HIGH, "0.5")
}

record(bo, "THZR:LI20:3075:_TIMEOUT") {
  field(DESC, "THZR:LI20:3075 Timeout")
  field(OUT, "THZR:LI20:3075:TgtStsCalc.C PP MS")
  field(HIGH, "1")
  field(ZNAM, "TIMED OUT")
  field(ONAM, "IN WINDOW")
}

# Processed when THZR:LI20:3075:_TRANS writes
# to THZR:LI20:3075:_TIMEOUT, which writes to
# this record's C input with "PP"
# Using "CPP" on the A or B inputs
# causes momentary timeout failures
# if channel access causes this record
# to process before _TIMEOUT.
record(calc, "THZR:LI20:3075:TgtStsCalc") {
  field(DESC, "THZR:LI20:3075 State")
  field(CALC, "A||B?A|(B<<1):(C?0:4)")
  field(INPA, "THZR:LI20:3075:IN  NPP MS")
  field(INPB, "THZR:LI20:3075:OUT NPP MS")
  field(PINI, YES )
}

record(mbbi, "THZR:LI20:3075:TGT_STS")
{
  field(DESC, "THZR:LI20:3075 Status")
  field(INP,  "THZR:LI20:3075:TgtStsCalc CPP MS")

  field(ZRVL,"0")
  field(ZRST,"MOVING")
  field(ZRSV,"MINOR")

  field(ONVL,"1")
  field(ONST,"OUT")
  field(ONSV,"NO_ALARM")

  field(TWVL,"2")
  field(TWST,"IN")
  field(TWSV,"NO_ALARM")

  field(THVL,"3")
  field(THST,"INCONSISTENT")
  field(THSV,"MAJOR")

  field(FRVL,"4")
  field(FRST,"LIMITS FAIL")
  field(FRSV,"MAJOR")
}


record(bo, BLEN:LI20:3014:PNEU) {
  field(DESC, "BLEN:LI20:3014 Control")
  field(DTYP, "XYCOM-2445")
  field(OUT, "@bo0 P0 B1")
  field(ZNAM, "INSERT")
  field(ONAM, "RETRACT")
  field(PINI, "YES")
}

record(bi, BLEN:LI20:3014:IN) {
  field(DESC, "BLEN:LI20:3014 In")
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@bi0 P0 B3")
  field(ZNAM, "Inactive")
  field(ZSV,  "MAJOR")
  field(ONAM, "Active")
  field(FLNK, "BLEN:LI20:3014:OUT")
}

record(bi, BLEN:LI20:3014:OUT) {
  field(DESC, "BLEN:LI20:3014 Out")
  field(DTYP, "XYCOM-2440")
  field(INP, "@bi0 P0 B2")
  field(ZNAM, "Inactive")
  field(ONAM, "Active")
  field(OSV,  "MAJOR")
  field(FLNK, "BLEN:LI20:3014:TgtStsCalc")
}

record(calcout, "BLEN:LI20:3014:_TRANS") {
  field(DESC, "BLEN:LI20:3014 Transition")
  field(CALC, "!A && !B")
  field(INPA, "BLEN:LI20:3014:IN  CPP MS")
  field(INPB, "BLEN:LI20:3014:OUT CPP MS")
  field(OUT,  "BLEN:LI20:3014:_TIMEOUT.VAL PP MS")
  field(OOPT, "On Change")
  field(HIGH, "0.5")
}

record(bo, "BLEN:LI20:3014:_TIMEOUT") {
  field(DESC, "BLEN:LI20:3014 Timeout")
  field(OUT, "BLEN:LI20:3014:TgtStsCalc.C PP MS")
  field(HIGH, "1")
  field(ZNAM, "TIMED OUT")
  field(ONAM, "IN WINDOW")
}

# Processed when BLEN:LI20:3014:_TRANS writes
# to BLEN:LI20:3014:_TIMEOUT, which writes to
# this record's C input with "PP"
# Using "CPP" on the A or B inputs
# causes momentary timeout failures
# if channel access causes this record
# to process before _TIMEOUT.
record(calc, "BLEN:LI20:3014:TgtStsCalc") {
  field(DESC, "BLEN:LI20:3014 State")
  field(CALC, "A||B?A|(B<<1):(C?0:4)")
  field(INPA, "BLEN:LI20:3014:IN  NPP MS")
  field(INPB, "BLEN:LI20:3014:OUT NPP MS")
  field(PINI, YES )
}

record(mbbi, "BLEN:LI20:3014:TGT_STS")
{
  field(DESC, "BLEN:LI20:3014 Status")
  field(INP,  "BLEN:LI20:3014:TgtStsCalc CPP MS")

  field(ZRVL,"0")
  field(ZRST,"MOVING")
  field(ZRSV,"MINOR")

  field(ONVL,"1")
  field(ONST,"OUT")
  field(ONSV,"NO_ALARM")

  field(TWVL,"2")
  field(TWST,"IN")
  field(TWSV,"NO_ALARM")

  field(THVL,"3")
  field(THST,"INCONSISTENT")
  field(THSV,"MAJOR")

  field(FRVL,"4")
  field(FRST,"LIMITS FAIL")
  field(FRSV,"MAJOR")
}