# ========================================== # BunchLength Mirror Actuation # ========================================== record(bo, BLEN:LI21:265:BL11_PNEU) { field(DESC, "BL11 Mirror") field(DTYP, "XYCOM-2445") field(OUT, "@bo0 P0 B3") field(ZNAM, "OUT") field(ONAM, "IN") field(PINI, "YES") } # ========================================== # ========================================== # BunchLength Mirror Status # ========================================== record(bi, BLEN:LI21:265:BL11_IN) { field(DESC, "BL11 Mirror In") field(SCAN, ".1 second") field(DTYP, "XYCOM-2440") field(INP, "@bi0 P0 B6") field(ZNAM, "Inactive") field(ZSV, "MAJOR") field(ONAM, "Active") field(FLNK, "BLEN:LI21:265:BL11_OUT") } record(bi, BLEN:LI21:265:BL11_OUT) { field(DESC, "BL11 Mirror Out") field(DTYP, "XYCOM-2440") field(INP, "@bi0 P0 B7") field(ZNAM, "Inactive") field(ONAM, "Active") field(OSV, "MAJOR") field(FLNK, "BLEN:LI21:265:TgtStsCalc") } record(calc, BLEN:LI21:265:TgtStsCalc) { field(INPA,"BLEN:LI21:265:BL11_IN") field(INPB,"BLEN:LI21:265:BL11_OUT") field(CALC,"A*2+B") field(FLNK,"BLEN:LI21:265:TGT_STS") } record(mbbi, "BLEN:LI21:265:TGT_STS") { field(DESC, "BL11 Mirror Status") field(INP, "BLEN:LI21:265:TgtStsCalc") field(ZRVL,"0") field(ZRST,"MOVING") field(ZRSV,"MAJOR") field(ONVL,"1") field(ONST,"OUT") field(ONSV,"MAJOR") field(TWVL,"2") field(TWST,"IN") field(TWSV,"NO_ALARM") field(THVL,"3") field(THST,"INCONSISTENT") field(THSV,"MAJOR") } # ===================================================