# This database is deprecated. The records were extracted from the file
# calculatedWF.db after a firmware upgrade. The new firmware does exactly
# what this database does. It is here for compatibility with IOCs
# working with the old firmware.

# NumberSamples0 follows a linear proportionality with the coefficient A0.
# We need to maintain the ratio A0 = ConstantA0/NumberSamples0.
record (calcout, "$(P):A0_NS0") {
  field(DESC, "Change A0, when NumSamp0 changes")
  field(INPA, "$(P):NumSamp0 CP")
  field(INPB, "$(P):A0_CONST CP")
  field(CALC, "A=0? B : B/A")
  field(DOPT, "Use CALC")
  field(OUT, "$(P):CoefA0 PP")
}

# NumberSamples1 follows a linear proportionality with the coefficient A1.
# We need to maintain the ratio A1 = ConstantA1/NumberSamples1.
record (calcout, "$(P):A1_NS1") {
  field(DESC, "Change A1, when NumSamp1 changes")
  field(INPA, "$(P):NumSamp1 CP")
  field(INPB, "$(P):A1_CONST CP")
  field(CALC, "A=0? B : B/A")
  field(DOPT, "Use CALC")
  field(OUT, "$(P):CoefA1 PP")
}

# Constant A0, used by A0_NS0, can be changed in runtime, if needed.
record (ao, "$(P):A0_CONST") {
  field(DESC, "Constant A0, used by A0_NS0")
  info(autosaveFields, "VAL")
}

# Constant A1, used by A1_NS1, can be changed in runtime, if needed.
record (ao, "$(P):A1_CONST") {
  field(DESC, "Constant A1, used by A1_NS1")
  info(autosaveFields, "VAL")
}

# New A0 target, desired by the user
record (ao, "$(P):Reset_A0") {
  field(DESC, "New A0 target, desired by the user")
  field(PREC, "7")
}

# New A1 target, desired by the user
record (ao, "$(P):Reset_A1") {
  field(DESC, "New A1 target, desired by the user")
  field(PREC, "7")
}

# When A0 target changes, A0 constant also changes, based on the value of
# Number Samples 0, in a way that the coefficient A0 hits the desired target.
record (calcout, "$(P):CALC_Const_A0") {
  field(DESC, "Change Const A0, when target A0 changes")
  field(INPA, "$(P):NumSamp0")
  field(INPB, "$(P):Reset_A0 CP")
  field(CALC, "A * B")
  field(DOPT, "Use CALC")
  field(OOPT, "On Change")
  field(OUT, "$(P):A0_CONST PP")
}

# When A1 target changes, A1 constant also changes, based on the value of
# Number Samples 1, in a way that the coefficient A1 hits the desired target.
record (calcout, "$(P):CALC_Const_A1") {
  field(DESC, "Change Cons A1, when target A1 changes")
  field(INPA, "$(P):NumSamp1")
  field(INPB, "$(P):Reset_A1 CP")
  field(CALC, "A * B")
  field(DOPT, "Use CALC")
  field(OOPT, "On Change")
  field(OUT, "$(P):A1_CONST PP")
}