#For these to provide usable data the coefficients A0 and A1 must be set 1 record(calcout, "$(P):$(CHAN):Calib_Charge") { field(DESC, "Integration of the beam pulse") field(EGU, "mV*ns/ohms") field(SCAN, "1 second") field(INPA, "$(P):$(CHAN):Calib_mV") field(INPB, "$(P):$(CHAN):NumSamp1_H") field(INPC, "$(P):$(CHAN):CLK_PERIOD") field(CALC, "A*B*C/50") } record(calcout, "$(P):$(CHAN):INTEGRAL") { field(DESC, "Integration of the beam pulse") field(EGU, "mV*ns") field(SCAN, "1 second") field(INPA, "$(P):$(CHAN):Calib_Conversion") field(INPB, "$(P):$(CHAN):NumSamp1_H") field(INPC, "$(P):$(CHAN):CLK_PERIOD") field(CALC, "A*B*C") } record(ai, "$(P):$(CHAN):Calib_mV") { field(DESC, "Measured voltage") field(EGU, "mV") field(AOFF, "0") field(ASLO, "0.0192") field(SCAN, "1 second") field(INP, "$(P):$(CHAN):TMIT_PC") field(DTYP, "Raw Soft Channel") field(FLNK, "$(P):$(CHAN):Calib_Charge") info(autosaveFields, "AOFF ASLO") } record(ao, "$(P):$(CHAN):Calib_Conversion") { field(DESC, "ratio of acd counts to mV") field(EGU, "mV/count") field(SCAN, "Passive") field(VAL, "0.0192") info(autosaveFields, "VAL") } record(calcout, "$(P):$(CHAN):Calib_Coef_A0") { field(DESC, "Converts Calib_charge to coef magnitude") field(EGU, "N/A") field(SCAN, "1 second") field(INPA, "$(P):$(CHAN):INTEGRAL") field(INPB, "$(P):$(CHAN):Calib_ratio") field(INPC, "$(P):$(CHAN):Invert_Coef") field(CALC, "C*A/(50*B)") field(OUT, "$(P):$(CHAN):CoefA0") field(FLNK, "$(P):$(CHAN):CoefA0") } record(calcout, "$(P):$(CHAN):Calib_Coef_A1") { field(DESC, "Converts Calib_charge to coef magnitude") field(EGU, "N/A") field(SCAN, "1 second") field(INPA, "$(P):$(CHAN):INTEGRAL") field(INPB, "$(P):$(CHAN):Calib_ratio") field(INPC, "$(P):$(CHAN):Invert_Coef") field(CALC, "-C*A/(50*B)") field(OUT, "$(P):$(CHAN):CoefA1") field(FLNK, "$(P):$(CHAN):CoefA1") } record(ao, "$(P):$(CHAN):Calib_ratio") { field(DESC, "Toroid Response Ratio") field(EGU, "N/A") field(VAL, "0.0754") field(SCAN, "Passive") } record(ao, "$(P):$(CHAN):Invert_Coef") { field(DESC, "If coefA0 should be positive") field(EGU, "N/A") field(VAL, "1") field(SCAN, "Passive") }