# Local oscillator status: # Indicates if oscillator is locked to 119 Mhz reference record(bi, "$(DEV):RCVR_LO_STA") { field(DESC, "Local oscillator status") field(DTYP, "ACROMAG-IP470") field(INP, "@cavBpmDigI_MPS P$(P_LOSTA) B$(B_LOSTA)") field(SCAN, "1 second") field(ZNAM, "Locked") field(ONAM, "Not locked") field(ZSV, "NO_ALARM") field(OSV, "MINOR") } # Written to by RCVR_GAIN PV, see bpmCavity.db.part record(bo, "$(DEV):RCVR_GAIN_OUT") { field(DESC, "Signal gain") field(DTYP, "ACROMAG-IP445") field(OUT, "@cavBpmDigO P$(P_GAIN) B$(B_GAIN)") field(ZNAM, "High") field(ONAM, "Low") } # Set self-test mode record(bo, "$(DEV):RCVR_SELFTST") { field(DESC, "Inject 11 Ghz signal") field(DTYP, "ACROMAG-IP445") field(OUT, "@cavBpmDigO P$(P_TEST) B$(B_TEST)") field(ZNAM, "Off") field(ONAM, "On") field(PINI, "YES") } # Set local oscillator mode: # Lock or unlock wrt 119 MHz reference record(bo, "$(DEV):RCVR_LO_CTL") { field(DESC, "Set local oscillator mode") field(DTYP, "ACROMAG-IP445") field(OUT, "@cavBpmDigO P$(P_LOCTL) B$(B_LOCTL)") field(ZNAM, "Lock") field(ONAM, "Unlock") field(PINI, "YES") info(autosaveFields, "VAL") } # Add VERS record to be compatible with newer receivers # VERS PV used to distinguish between different receiver # designs/generations and used in display visibility rules # Choose VAL=1 as dummy value record(longin, "$(dev):VERS") { field(DESC, "Firmware Vers.") field(VAL, "1") field(PINI, "YES") }