# For LCLS, which contains many BPM eiocs (many clients of this
# database), this db is loaded into a soft ioc instead of one of
# the BPM iocs to reduce the number of channel access links on that ioc.
#

# a few records to host the 'announced charge'
# so that everybody can adjust their gains
record(ao, "VIOC:GUN:BPM:QANN") {
	field(DESC, "Announced Beam Charge")
	field(ADEL, ".01")
	field(LOPR, ".01")
	field(DRVL, ".01")
	field(HOPR, "2")
	field(DRVH, "1")
	field(PREC, "3")
	field(VAL,  ".1")
	field(EGU,  "nC")
	field(PINI, "YES")
        field(FLNK, "VIOC:GUN:BPM:QANNSET PP")
  	info(autosaveFields, "VAL HIHI HIGH LOW LOLO HHSV HSV LSV LLSV DRVH")
}

# Make proxy record to write QANN in order
# to limit access to QANN.DRVH (HW protection)
# QANNSET value will be used to set eioc attenuators
record(ao, "VIOC:GUN:BPM:QANNSET") {
        field(DESC, "Set QANN")
        field(DOL, "VIOC:GUN:BPM:QANN")
        field(OMSL, "closed_loop")
	field(OUT,  "VIOC:GUN:BPM:ATTR.A PP")
	field(ADEL, ".01")
	field(LOPR, ".01")
	field(DRVL, ".01")
	field(HOPR, "2")
	field(DRVH, "1")
	field(PREC, "3")
	field(VAL,  ".1")
	field(EGU,  "nC")
        field(VAL, "1")
        field(ASG, "EOICDESK")
 	field(FLNK, "VIOC:GUN:BPM:QANNF")
  	info(autosaveFields, "DRVH")
}

# Record to copy selected QANNSET fields to QANN
# Sync QANN.DRVH to 'real' QANNSET.DRVH
# Just DRVH for now; want to keep alarms with
# accessible QANN
record(seq, "VIOC:GUN:BPM:QANNF") {
    	field(DESC, "Update QANN fields")
        field(SELM, "All")
     	field(DOL1, "VIOC:GUN:BPM:QANNSET.DRVH CP")
        field(LNK1, "VIOC:GUN:BPM:QANN.DRVH PP")
}


record(ao, "VIOC:GUN:BPM:QREF") {
	field(DESC, "Ann. Charge Ref. Val.")
	field(OUT,  "VIOC:GUN:BPM:ATTR.B PP")
	field(ADEL, ".01")
	field(LOPR, ".01")
	field(DRVL, ".01")
	field(HOPR, "100")
	field(DRVH, "100")
	field(PREC, "3")
	field(VAL,  ".1")
	field(EGU,  "nC")
	field(PINI, "YES")
        field(ASG, "EOICDESK")
  	info(autosaveFields, "VAL")
}

record(calc, "VIOC:GUN:BPM:ATTR") {
	field(DESC, "Reference Attenuation")
	field(EGU,  "dB")
	field(CALC, "20*LOG(a/b)")
        field(ASG, "EOICDESK")
}

record(calcout, "VIOC:GUN:BPM:QANNH") {
  field(DESC, "Calculates QANN.HIHI,.HIGH")
  field(SCAN, "Passive")
  field(CALC, "A*B")
#Feedback charge setpoint
  field(INPA, "FBCK:BCI0:1:CHRGSP CPP")
#Upper limits coefficient
  field(B, "1.1")
  field(OUT, "VIOC:GUN:BPM:QANNHFO PP")
  field(OOPT, "Every Time")
  field(PINI, "YES")
  info(autosaveFields, "INPA B")
}

record(dfanout, "VIOC:GUN:BPM:QANNHFO") {
  field(DESC, "Fanout to QANN.HIHI,HIGH")
  field(OUTA, "VIOC:GUN:BPM:QANN.HIHI PP")
  field(OUTB, "VIOC:GUN:BPM:QANN.HIGH PP")
}

record(calcout, "VIOC:GUN:BPM:QANNL") {
  field(DESC, "Calculates QANN.LOLO,.LOW")
  field(SCAN, "Passive")
  field(CALC, "A*B")
#Feedback charge setpoint
  field(INPA, "FBCK:BCI0:1:CHRGSP CPP")
#Lower limits coefficient
  field(B, "0.9")
  field(OUT, "VIOC:GUN:BPM:QANNLFO PP")
  field(OOPT, "Every Time")
  field(PINI, "YES")
  info(autosaveFields, "INPA B")
}

record(dfanout, "VIOC:GUN:BPM:QANNLFO") {
  field(DESC, "Fanout to QANN.LOLO,LOW")
  field(OUTA, "VIOC:GUN:BPM:QANN.LOLO PP")
  field(OUTB, "VIOC:GUN:BPM:QANN.LOW PP")
}

# Two records for users who prefer bunch charge in # of electrons
# Users set QANNEL, which sets QANN (changes to QANN bypassing QANNNEL
# will be lost). Must restore QANNEL on reboot. 
# New macro qann for QANN PV, which has default of "" to remain 
# backward-compatible with existing db substitutions files.
# IMPORTANT: Only those wishing to use QANNEL should define value for qann macro,
# otherwise QANN will be set to QANNEL's default on boot.
record(ao, "VIOC:GUN:BPM:QANNNEL") {
	field(DESC, "Announced Beam Charge")
	field(ADEL, "1E7")
	field(LOPR, "6.25E7")
	field(DRVL, "6.25E7")
	field(HOPR, "2E10")
	field(DRVH, "2E10")
	field(VAL,  "6.25E8")
	field(EGU,  "Nel")
	field(PINI, "YES")
	field(FLNK, "VIOC:GUN:BPM:QANNNELC")
  	info(autosaveFields, "VAL")
}

record(calcout, "VIOC:GUN:BPM:QANNNELC") {
	field(DESC, "Convert beam charge units")
	field(CALC, "A*1E9*1.6E-19")
	field(INPA, "VIOC:GUN:BPM:QANNNEL")
	field(OUT,  "VIOC:GUN:BPM:QANN PP")
	field(OOPT, "Every Time")
	field(FLNK, "VIOC:GUN:BPM:QANN PP")
}
# per IOC database for stripline BPMs

#record(sub, "VIOC:L202:BPM:FIDP") {
#	field(DESC, "BPM Fiducial Processing")
#	field(SNAM, "bpmEvrFidProcess")
#	#This tells us if there is beam during this cycle...
#	field(INPA, "VIOC:L202:BPM:MODIFIER5.R")
#}

#record(mbbo, "VIOC:L202:BPM:PATTERNSIM") {
#	field(DESC, "Pattern Simulation")
#	field(ZRST, "Off")
#	field(ONST, "Soft")
#	field(TWST, "Raw")
#	field(DOL,  "0")
#	field(PINI, "YES")
#}

record(sub, "VIOC:L202:BPM:EVTM") {
	field(SNAM, "subEventTestTiming")
	field(SCAN, "Event")
	field(EVNT, "40")
}

#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


# per BPM database for stripline BPMs

##############################################
# This is the head of the main processing chain
# that runs at the highest priority.
##############################################

#############################################
# This is the head of the processing chain for
# diagnostics.
##############################################
record(ai, "HL1:SBPM:HL13:GRN") {
  field(DESC, "GRN Strip Amplitude")
  field(DTYP, "Raw Bpm Signal")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "#C0 S0")
  field(EGU, "raw")
#TODO set HOPR/LOPR, alarm limits
  field(SCAN, "I/O Intr")
# The priority determines what scan list we are being
# put on (see drvPadUdpComm.c)
  field(PRIO, "LOW")
  field(FLNK, "HL1:SBPM:HL13:RED")
# HOPR for the energy algorithm is determined as follows:
#
#                      inf        inf
#  1) Fourier relation / h^2 dt = / |H|^2 df = 2 B
#                     0         -inf
#
#  1a) It can be shown that the maximum of the impuls response
#      ha is ~ 2 B
#                               
#  2) The digitizer produces the numbers
#
#     Ai = 2^s (hi/ha)
#
#     where ha is the maximum of the impuls response
#     and 2^s is a scale factor.
#     
#  3) 'Energy algorithm' calculates S = sum( Ai^2 )
#
#                                                     inf
#  4) S = (2^s / ha)^2 sum(hi^2) = K sum(hi^2) Dt ~ K / h^2 dt
#                                                    0
#
#     with K = (2^s / ha)^2 fs
#
#  5) From 4) and 1a) ->  S ~ K ha and therefore
#
#  6) S = 2^(2s) fs/ha = 2^(2s) fs/(2 B)
#
#  7) The strip signals are sqrt(S); hence HOPR is about
#
#     HOPR ~ 2^s  sqrt( fs/2/B )
#
#     with 2^s = 32768, fs=120MHz, B=10MHz it follows
#     that HOPR ~ 1E5; we add some margin...
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL1:SBPM:HL13:RED") {
  field(DESC, "RED Strip Amplitude")
  field(DTYP, "Raw Bpm Signal")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "#C0 S1")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(FLNK, "HL1:SBPM:HL13:BLU")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL1:SBPM:HL13:BLU") {
  field(DESC, "BLU Strip Amplitude")
  field(DTYP, "Raw Bpm Signal")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "#C0 S2")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(FLNK, "HL1:SBPM:HL13:YLO")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL1:SBPM:HL13:YLO") {
  field(DESC, "YLO Strip Amplitude")
  field(DTYP, "Raw Bpm Signal")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "#C0 S3")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

##############################################
# Slowly-scanned diagnostics
##############################################

#
record(waveform, "HL1:SBPM:HL13:REDW") {
  field(DESC, "Raw CAL RED Data")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP, "#C0 S1")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "1 second")
}

record(waveform, "HL1:SBPM:HL13:GRNW") {
  field(DESC, "Raw CAL GRN Data")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP, "#C0 S2")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "1 second")
}

record(waveform, "HL1:SBPM:HL13:RAWDBG") {
  field(DESC, "Raw BEAM Dbg")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
# do not 'wbscan' for now since e.g., an underrange
# condition on the real signal can happen.
  field(INP, "#C0 S7")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "Passive")
}

record(waveform, "HL1:SBPM:HL13:REDDBG") {
  field(DESC, "Raw CAL RED Dbg")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP, "#C0 S8 @wbscan")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "Passive")
}

record(waveform, "HL1:SBPM:HL13:GRNDBG") {
  field(DESC, "Raw CAL GRN Dbg")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP, "#C0 S9 @wbscan")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "Passive")
}

record(ai, "HL1:SBPM:HL13:GRUV") {
  field(DESC, "CAL Gain GRN/RED")
  field(DTYP, "Raw Stripl Calp")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C0 S0")
  field(SCAN, "10 second")
  field(PREC, "4")
  field(LOPR, "0.5")
  field(HOPR, "1.5")
}

record(ai, "HL1:SBPM:HL13:GRU") {
  field(DESC, "CAL Gain GRN/BLU")
  field(DTYP, "Raw Stripl Calp")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C0 S1")
  field(SCAN, "10 second")
  field(PREC, "4")
  field(LOPR, "0.5")
  field(HOPR, "1.5")
  info(autosaveFields, "ASLO")
}

record(ai, "HL1:SBPM:HL13:GRV") {
  field(DESC, "CAL Gain RED/YLO")
  field(DTYP, "Raw Stripl Calp")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C0 S2")
  field(SCAN, "10 second")
  field(PREC, "4")
  field(LOPR, "0.5")
  field(HOPR, "1.5")
  info(autosaveFields, "ASLO")
}

record(ai, "HL1:SBPM:HL13:TGRN") {
  field(DESC, "Green arrival time")
  field(DTYP, "Raw Bpm Signal")
  field(EGU, "ADC Clocks")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C0 S4")
  field(SCAN, "10 second")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "128")
  field(LOLO, "5")
  field(LOW, "8")
  field(HIGH, "60")
  field(HIHI, "70")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
  field(HSV, "MINOR")
  field(HHSV, "MAJOR")
}

record(ai, "HL1:SBPM:HL13:TRED") {
  field(DESC, "Red arrival time")
  field(DTYP, "Raw Bpm Signal")
  field(EGU, "ADC Clocks")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C0 S5")
  field(SCAN, "10 second")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "128")
  field(LOLO, "5")
  field(LOW, "8")
  field(HIGH, "60")
  field(HIHI, "70")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
  field(HSV, "MINOR")
  field(HHSV, "MAJOR")
}

record(ai, "HL1:SBPM:HL13:TBLU") {
  field(DESC, "Blue arrival time")
  field(DTYP, "Raw Bpm Signal")
  field(EGU, "ADC Clocks")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C0 S6")
  field(SCAN, "10 second")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "128")
  field(LOLO, "5")
  field(LOW, "8")
  field(HIGH, "60")
  field(HIHI, "70")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
  field(HSV, "MINOR")
  field(HHSV, "MAJOR")
}

record(ai, "HL1:SBPM:HL13:TYLO") {
  field(DESC, "Yellow arrival time")
  field(DTYP, "Raw Bpm Signal")
  field(EGU, "ADC Clocks")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C0 S7")
  field(SCAN, "10 second")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "128")
  field(LOLO, "5")
  field(LOW, "8")
  field(HIGH, "60")
  field(HIHI, "70")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
  field(HSV, "MINOR")
  field(HHSV, "MAJOR")
}

record(ao, "HL1:SBPM:HL13:PINC_ADJ") {
  field(DESC, "Adjust Pinc. Corr.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL1:SBPM:HL13:CALC.K PP MS")
  field(VAL, "0")
  field(DRVL, "0")
  field(DRVH, "2")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

# QSCL setting:
#
# Q: charge
# Z: impedance
# F: form factor: phi/(2 pi) sin(2 pi f l/c)
#
# Signal =  Q Z F G h(t) = A h(t)  [A] = Vs
#
#                  inf              inf
# Energy =  A^2   / h^2(t) dt = A^2 / |H(w)|^2 dw/2/pi = A^2 B
#                0                 0
#                        
# Measured energy = Sum{ (Vp/32768 * xi)^2 } / fs = S / fs ~ Energy
#
# -> A^2 B = S/fs
#
# With T = sqrt( Sum{ xi^2 } )
#
#    A = sqrt(S)/sqrt(B*fs) = T/sqrt(B*fs) Vp/32768
#
#                      T/32768 Vp
#    Q = A/F/G/Z = -----------------
#                   F G Z sqrt(B*fs)
#
# Vp = { 1.5Vpp/2 (PGA=1) or 2.25Vpp/2 (PGA=0) } / 2 (transformer)
#
# I believe PGA is off (-> Vp ~ .56V)
#
# Z  = 50
#
# G: (calibration uses GRN/BLU -> signal should have the
#    level of the grn/red channels with the additional switch)
#
# Block diagram / parts / gain:
#
# [filt]    [Att1]    [Amp1]   [Att2]    [BPF]      [Amp2]    [pad] [Amp3]   [switch]
# f-17520  hmc540lp3  SBF-5089 hmc540lp3 MBP-140-6-4 SBF-4089  PAT-0 SBF-4089 HMC-197
#
#  -2dB*    -1dB       20dB     -1dB     -4.5         14.8dB   0dB   14.8dB   -0.4dB
#
# *: 1st filter ATT is a wild guess.
#  BPF loss (RLC Catalog, pp.55): (L (nsect+.5) / (% of 3dB BW) + .2) dB
#  with L ~6.2  10MHz/fc=140Mhz filter-> 4.5
#
#  -> Gtot ~ 40.7dB
#
#  subtract cable loss (2dB); Gtot = 86
# 
#                      T/32768 Vp            .56V/32768
#    Q = A/F/G/Z = ----------------- = T/F  ------------------------
#                   F G Z sqrt(B*fs)        86*50*sqrt(10*140)Mhz
#
#      = T/F = 1.06E-7/F nC
#
#    F for a 7% coverage, 4" BPM at 140MHz   .07 sin(2*pi*140e6 4*.0254/3e8)
#      = .021
#
#      => 1.06E-7/.021 nC = 5E-6 nC
#
# (Faraday cup measurement -> (3600/44)^-1 1e-4 -> 1.22E-6
#
record(ao, "HL1:SBPM:HL13:QSCL") {
  field(DESC, "TMIT/Charge Scale")
  field(DTYP, "Soft Channel")
  field(OUT, "HL1:SBPM:HL13:QSCA.A PP MS")
# 5.0E-6 / 1.6E-10 [nC/e-]
  field(VAL, "31250")
  field(EGU, "Nel")
  field(PREC, "3")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

# Adjust TMIT scale for AFE attenuation
record(calcout, "HL1:SBPM:HL13:QSCA") {
  field(DESC, "TMIT ATT Adj. Scale")
  field(INPB, "HL1:SBPM:HL13:ATT1 CP")
  field(INPC, "HL1:SBPM:HL13:ATT2 CP")
  field(CALC, "A*10^((B+C+D)/20)")
# use CA link to deposit into TMIT.ASLO so
# that TMIT is not forced into linkset
# of this record
  field(OUT, "HL1:SBPM:HL13:TMIT.ASLO CA")
  field(EGU, "Nel")
  field(PREC, "3")
  info(autosaveFields, "D")
}

record(ao,    "HL1:SBPM:HL13:ATT1SIMP") {
	field(DESC, "ATT1 Propagator")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL1:SBPM:HL13:ATT1   CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL1:SBPM:HL13:ASIM.A PP")
  	field(IVOA, "Set output to IVOV")
	field(IVOV, "0")
	field(EGU,  "dB")
}

record(ao,    "HL1:SBPM:HL13:ATT2SIMP") {
	field(DESC, "ATT2 Propagator")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL1:SBPM:HL13:ATT2   CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL1:SBPM:HL13:ASIM.C PP")
  	field(IVOA, "Set output to IVOV")
	field(IVOV, "0")
	field(EGU,  "dB")
}

# Attenuate charge either by
# real attenuator settings or
# by fake ones.
# If B, C >= 0 then their
# values will be used instead
# of ATT1, ATT2
record(calcout, "HL1:SBPM:HL13:ASIM") {
  field(DESC, "Q Simul Attenuator")
  field(DTYP, "Soft Channel")
  field(OUT,  "HL1:SBPM:HL13:QSIM.ESLO PP")
# ATT1SIM puts value into A
# set to -1 to use real attenuator settings
# and >=0 to use B instead
  field(B,    "-1")
# ATT2SIM puts value into C
# set to -1 to use real attenuator settings
# and >=0 to use D instead
  field(D,    "-1")
  field(CALC, "10^(((B>=0?B:A)+(D>=0?D:C))/20)")
  field(PINI, "YES")
}

record(ao, "HL1:SBPM:HL13:WSIM") {
  field(DESC, "BPM W Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL1:SBPM:HL13:SIM.G PP")
  field(VAL, "0.07")
  field(EGU, "%")
  field(PINI, "YES")
  field(PREC, "3")
  field(LOPR, "0")
  field(HOPR, "0.25")
}


record(sel, "HL1:SBPM:HL13:STA") {
  field(DESC, "Status Summary")
  field(SELM, "High Signal")
  field(INPA, "HL1:SBPM:HL13:RSTA.SEVR MS NPP")
  field(INPB, "HL1:SBPM:HL13:TMIT.SEVR MS NPP")
  field(INPC, "HL1:SBPM:HL13:Y.SEVR    MS NPP")
  field(INPD, "HL1:SBPM:HL13:X.SEVR    MS NPP")
  field(INPE, "HL1:SBPM:HL13:TGRN.SEVR MS NPP")
  field(INPF, "HL1:SBPM:HL13:TRED.SEVR MS NPP")
  field(INPG, "HL1:SBPM:HL13:TBLU.SEVR MS NPP")
  field(INPH, "HL1:SBPM:HL13:TYLO.SEVR MS NPP")
  field(INPI, "HL1:SBPM:HL13:GRU.SEVR  MS NPP")
  field(INPJ, "HL1:SBPM:HL13:GRV.SEVR  MS NPP")
  field(SCAN, "1 second")
}

# This record really belongs on the
# PAD IOC. We keep them here however
# so we can save/restore. It is more
# confusing but shouldn't matter from
# an efficiency standpoint (they are
# rarely changed).
record(longout, "HL1:SBPM:HL13:ATTO") {
  field(DESC, "AFE Tot. Att. Offset")
# fetched via inlink
#field(OUT,  "HL1:SBPM:HL13:ATTC.B PP")
  field(DRVL, "-10")
  field(DRVH, "30")
  field(LOPR, "-10")
  field(HOPR, "30")
  field(EGU, "dB")
  field(VAL, "0")
  field(PINI, "YES")
  info(autosaveFields, "VAL DRVH HOPR DRVL LOPR")
}

# This record really belongs on the
# PAD IOC. We keep them here however
# so we can save/restore. It is more
# confusing but shouldn't matter from
# an efficiency standpoint (they are
# rarely changed).
record(longout, "HL1:SBPM:HL13:CLAO") {
  field(DESC, "AFE Cal. Att. Offset")
# fetched via inlink
#field(OUT,  "HL1:SBPM:HL13:ATTC.C PP")
  field(DRVL, "-20")
  field(DRVH, "20")
  field(LOPR, "-20")
  field(HOPR, "20")
  field(EGU, "dB")
  field(VAL, "40")
  field(PINI, "YES")
  info(autosaveFields, "VAL DRVH HOPR DRVL LOPR")
}

record(calc, "HL1:SBPM:HL13:STA_ALH") {
  field(DESC, "Status Summary")
  field(SCAN, "1 second")
  field(CALC, "0")
  field(INPA, "HL1:SBPM:HL13:RSTA_ALH.SEVR MS NPP")
  field(INPB, "HL1:SBPM:HL13:GRU.SEVR  MS NPP")
  field(INPC, "HL1:SBPM:HL13:GRV.SEVR  MS NPP")
  field(INPD, "HL1:SBPM:HL13:CHK.SEVR MS NPP")
}

# snapshot PV for the bpm values display
record(ai, "HL1:SBPM:HL13:GRN_SLOW") {
  field(DESC, "GRN snapshot for display")
  field(INP, "HL1:SBPM:HL13:GRN NPP MS")
  field(EGU, "raw")
  field(SCAN, "1 second")
  field(FLNK, "HL1:SBPM:HL13:RED_SLOW")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL1:SBPM:HL13:RED_SLOW") {
  field(DESC, "RED snapshot for display")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "HL1:SBPM:HL13:RED NPP MS")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(FLNK, "HL1:SBPM:HL13:BLU_SLOW")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL1:SBPM:HL13:BLU_SLOW") {
  field(DESC, "BLU snapshot for display")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "HL1:SBPM:HL13:BLU NPP MS")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(FLNK, "HL1:SBPM:HL13:YLO_SLOW")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL1:SBPM:HL13:YLO_SLOW") {
  field(DESC, "YLO snapshot for display")
  field(INP, "HL1:SBPM:HL13:YLO NPP MS")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(sub, "HL1:SBPM:HL13:CALC") {
  field(SNAM, "drvBpmBvectSetupSub")
# E: phi F: psi
# BPM channel number in L
  field(INPL, "0")
  field(SCAN, "Passive")
}

record(bo, "HL1:SBPM:HL13:PINC_ENA") {
  field(DESC, "Simple Pincushion Alg")
  field(DTYP, "BusAddress")
  field(OUT,  "#C0S2@drvBpmStriplPincEna,m32")
  field(MASK, "1")
  field(ZNAM, "DISABLED")
  field(ONAM, "ENABLED")
  field(VAL,  "0")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

record(ao, "HL1:SBPM:HL13:UDR_THRES") {
  field(DESC, "Detection Underrange Threshold")
  field(DTYP, "Bpm Parameters")
  field(OUT,  "#C0S0")
  field(EGU,  "ADC Ticks")
  field(DOL,  "45.26")
  field(PINI, "YES")
  field(DRVL, "0")
  field(DRVH, "32767")
  info(autosaveFields, "VAL")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


# per BPM database for stripline BPMs

######################################
# HEAD of main processing chain
######################################

record(ai, "HL1:SBPM:HL13:X") {
  field(DESC, "X Position")
  field(EGU, "mm")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C0 S11")
  field(SCAN, "I/O Intr")
# The priority determines what scan list we are being
# put on (see drvPadUdpComm.c)
  field(PRIO, "HIGH")
  field(FLNK, "HL1:SBPM:HL13:Y")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
  field(ASG,  "")
  field(TSE, "-2")
  info(autosaveFields, "ASLO LOLO LOW HIGH HIHI HHSV LLSV")
}

record(ai, "HL1:SBPM:HL13:Y") {
  field(DESC, "Y Position")
  field(EGU, "mm")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C0 S12")
  field(FLNK, "HL1:SBPM:HL13:TMIT")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
  field(ASG,  "")
  field(TSE, "-2")
  info(autosaveFields, "ASLO LOLO LOW HIGH HIHI HHSV LLSV")
}

record(ai, "HL1:SBPM:HL13:TMIT") {
  field(DESC, "Charge Estimate")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C0 S13")
  field(EGU, "Nel")
  field(PREC, "3")
  field(LOPR, "0")
  field(HOPR, "1E11")
# FLINK into BSA
  field(FLNK, "HL1:SBPM:HL13:EFX.PROC")
  field(ASG,  "")
  field(TSE, "-2")
  info(autosaveFields, "LOLO LOW HIGH HIHI HHSV LLSV ")
}


######################################
# HEAD of diagnostics processing chain
######################################

# leave RWAV in it's own lockset; don't FLNK
# to 'U' & friends
record(waveform, "HL1:SBPM:HL13:RWAV") {
  field(DESC, "Raw BPM Data")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP,  "#C0 S0")
  field(SCAN, "I/O Intr")
# use LOW or HIGH to end up on the 'diagnostic' 
# scan list (see drvPadUdpComm.c)
  field(PRIO, "LOW")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU,  "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
}

record(ai, "HL1:SBPM:HL13:U") {
  field(DESC, "Raw U Position")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C0 S8")
  field(SCAN, "I/O Intr")
# use LOW or HIGH to end up on the 'diagnostic' 
# scan list (see drvPadUdpComm.c)
  field(PRIO, "LOW")
  field(PREC, "5")
  field(EGU,  "mm")
  field(LOPR, "-0.7")
  field(HOPR, "+0.7")
  field(FLNK, "HL1:SBPM:HL13:V")
}

record(ai, "HL1:SBPM:HL13:V") {
  field(DESC, "Raw V Position")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C0 S9")
  field(SCAN, "Passive")
  field(PREC, "5")
  field(EGU,  "mm")
  field(LOPR, "-0.7")
  field(HOPR, "+0.7")
  field(FLNK, "HL1:SBPM:HL13:PINC")
}

record(ai, "HL1:SBPM:HL13:PINC") {
  field(DESC, "Pin Cushion Corr.")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C0 S10")
  field(SCAN, "Passive")
}

record(longin, "HL1:SBPM:HL13:RSTA") {
  field(DESC, "Status of Raw Processor")
  field(DTYP, "Bpm Raw Status")
  field(INP, "#C0S0")
  field(SCAN, "1 second")
  field(LOLO, "-1")
  field(HIHI, "+1")
  field(HHSV, "INVALID")
  field(LLSV, "INVALID")
  field(FLNK, "HL1:SBPM:HL13:RSTA_ALH")
}


record(calc, "HL1:SBPM:HL13:RSTA_ALH") {
  field(CALC, "A & B")
  field(INPA, "HL1:SBPM:HL13:RSTA")
  field(INPB, "0x30F")
  field(HIHI, "1")
  field(LOLO, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(SCAN, "Passive")
}

######################################
# Input/Parameteres
######################################

record(ao, "HL1:SBPM:HL13:PHI") {
  field(DESC, "Rot Angle")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(EGU, "deg")
  field(PREC, "1")
  field(LOPR, "-180")
  field(HOPR, "+180")
  field(FLNK, "HL1:SBPM:HL13:PHI_SEQ")
}

record(ao, "HL1:SBPM:HL13:PSI") {
  field(DESC, "Axis Sep. Angle")
  field(DTYP, "Soft Channel")
  field(VAL, "90")
  field(EGU, "deg")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "+180")
  field(FLNK, "HL1:SBPM:HL13:PSI_SEQ")
}

#record(dfanout, "HL1:SBPM:HL13:PCMM") {
#  field(DESC, "BPM Scale")
#  field(OUTA, "HL1:SBPM:HL13:USCL PP MS")
#  field(OUTB, "HL1:SBPM:HL13:VSCL PP MS")
#  field(VAL, "12")
#  field(EGU, "mm")
#  field(PREC, "4")
#  field(LOPR, "5")
#  field(HOPR, "15")
#  field(PINI, "YES")
#}

record(ao, "HL1:SBPM:HL13:UOFF") {
  field(DESC, "BPM U Offset")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(EGU, "mm")
  field(PREC, "4")
  field(LOPR, "-5")
  field(HOPR, "+5")
  field(FLNK, "HL1:SBPM:HL13:UOFF_SEQ")
}

record(ao, "HL1:SBPM:HL13:VOFF") {
  field(DESC, "BPM V Offset")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(EGU, "mm")
  field(PREC, "4")
  field(LOPR, "-5")
  field(HOPR, "+5")
  field(FLNK, "HL1:SBPM:HL13:VOFF_SEQ")
}

record(ao, "HL1:SBPM:HL13:USCL") {
  field(DESC, "BPM U Scale")
  field(DTYP, "Soft Channel")
  field(VAL,  "1")
  field(EGU, "mm")
  field(PREC, "4")
  field(FLNK, "HL1:SBPM:HL13:USCL_SEQ")
}

record(ao, "HL1:SBPM:HL13:VSCL") {
  field(DESC, "BPM V Scale")
  field(DTYP, "Soft Channel")
  field(VAL,  "1")
  field(EGU, "mm")
  field(PREC, "4")
  field(FLNK, "HL1:SBPM:HL13:VSCL_SEQ")
}


record(mbbo, "HL1:SBPM:HL13:ACCESS") {
  field(DESC, "BPM On Line")
  field(DTYP, "StreamSwitch")
  field(OUT, "#C0 S0")
  field(ZRVL, "1")
  field(ZRST, "Running")
  field(ZRSV, "NO_ALARM")
  field(ONVL, "1")
  field(ONST, "Maintenance")
  field(ONSV, "MINOR")
  field(TWVL, "1")
  field(TWST, "Test")
  field(TWSV, "MINOR")
  field(THVL, "0")
  field(THST, "OFFLINE")
  field(THSV, "MAJOR")
# set both, rval and val to get it right
# regardless of whether devsup does conversion
# or not.
  field(RVAL, "0")
  field(VAL,  "0")
  field(PINI, "YES")
  field(FLNK, "HL1:SBPM:HL13:SIMOFF")
  info(autosaveFields, "RVAL")
}

#
# Used by higher level software to determine if a PV is in feedback or not.
# May also be used by actuator (magnet and RF) IOC applications to 
# switch output records to "closed_loop" to prevent outside programs from
# changing setpoints when an actuator device is in feedback.
#
record(mbbo, "HL1:SBPM:HL13:FBCK")
{
  field(DESC, "Feedback State")
  field(PINI, "YES")
  field(OMSL, "supervisory")
  field(VAL,  "0")
  field(ZRVL, "0")
  field(ONVL, "1")
  field(TWVL, "2")
# Off - this device can be used in feedback but all feedback loops 
# using it are off.
  field(ZRST, "Off")
# On - this device is being used by one or more feedback loops.
  field(ONST, "On")
# Unavailable - this device is not used by any feedback loop.
  field(TWST, "Unavailable")
  info(autosaveFields, "VAL")
}

# Convenience record holding the MAD name
record(stringin, "HL1:SBPM:HL13:MADN") {
  field(DESC, "MAD Name")
  field(VAL, "SBPMHL13")
  field(PINI, "YES")
}

record(stringin, "SBPMHL13:NAME") {
  field(DESC, "BPM Name")
  field(VAL, "HL1:SBPM:HL13")
  field(PINI, "YES")
}

record(ai, "HL1:SBPM:HL13:X_SLOW") {
#alias("HL1:SBPM:HL13:X1H")
  field(DESC, "X snapshot for display")
  field(EGU, "mm")
  field(INP, "HL1:SBPM:HL13:X MS")
  field(FLNK, "HL1:SBPM:HL13:Y_SLOW")
  field(PREC, "4")
  field(SCAN, "1 second")
  field(LOPR, "-12")
  field(HOPR, "+12")
}

record(ai, "HL1:SBPM:HL13:Y_SLOW") {
#alias("HL1:SBPM:HL13:Y1H")
  field(DESC, "Y snapshot for display")
  field(EGU, "mm")
  field(INP, "HL1:SBPM:HL13:Y NPP MS")
  field(FLNK, "HL1:SBPM:HL13:TMIT_SLOW")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
}

record(ai, "HL1:SBPM:HL13:TMIT_SLOW") {
#alias("HL1:SBPM:HL13:TMIT1H")
  field(DESC, "TMIT snapshot for display")
  field(INP, "HL1:SBPM:HL13:TMIT NPP MS")
  field(EGU, "Nel")
  field(PREC, "3")
  field(LOPR, "0")
  field(HOPR, "1E11")
}

######################################
# Simulation Parameters + Control
######################################

# switch off simulation when going off-line
record(calcout, "HL1:SBPM:HL13:SIMOFF") {
  field(DESC, "Sim Off Propagator")
  field(INPA, "HL1:SBPM:HL13:ACCESS.RVAL")
  field(CALC, "A")
  field(OCAL, "0")
  field(OOPT, "When Zero")
  field(DOPT, "Use OCAL")
  field(OUT,  "HL1:SBPM:HL13:SIMC PP")
}

record(calcout, "HL1:SBPM:HL13:SIM") {
  field(DESC, "BPM Pos. Simulation")
  field(DTYP, "Strip Signal Simulator")
  field(OUT, "0")
#CALC & VAL unused; the real calculation is done
#        in device support. The reason this is a
#        calcout rather than sub is that we want
#        to use the OUT link...
  field(CALC, "A")
  field(INPA, "HL1:SBPM:HL13:USCL")
  field(INPL, "0")
}

# Switch simulation record HL1:SBPM:HL13:SIMCSEQ moved to
# bpmCavity.db.part and bpmStripl.db.part 

record(mbbo, "HL1:SBPM:HL13:SIMC") {
  field(DESC, "Stripl Sim Ctl")
  field(DTYP, "Raw Soft Channel")
  field(OUT,  "HL1:SBPM:HL13:SIMCSEQ.SELN PP")
  field(ZRST, "OFF")
  field(ZRVL, "0x0f")
  field(ONST, "ON")
  field(ONVL, "0x1c0")
  field(TWST, "SOFT")
  field(TWVL, "0x030")
  field(MASK, "-1")
  field(NOBT, "16")
  field(VAL,  "0")
  field(RVAL, "0x0f")
  field(PINI, "YES")
}

record(ao, "HL1:SBPM:HL13:XSIM") {
  field(DESC, "BPM X Pos. Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL1:SBPM:HL13:SIM.B PP")
  field(VAL, "0.5")
  field(EGU, "mm")
  field(PINI, "YES")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
}

record(ao, "HL1:SBPM:HL13:YSIM") {
  field(DESC, "BPM Y Pos. Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL1:SBPM:HL13:SIM.C PP")
  field(VAL, "0.")
  field(EGU, "mm")
  field(PINI, "YES")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
}

record(ao, "HL1:SBPM:HL13:QSIM") {
  field(DESC, "BPM Q Simul.")
  field(DTYP, "Raw Soft Channel")
  field(OUT, "HL1:SBPM:HL13:SIM.D PP")
  field(EGU, "Nel")
  field(ASLO, "6000")
#ESLO is used to add attenuation
  field(LINR, "LINEAR")
  field(VAL, "1E9")
  field(PINI, "YES")
  field(PREC, "4")
  field(LOPR, "0")
  field(HOPR, "1E11")
}

record(ao, "HL1:SBPM:HL13:ROTS") {
  field(DESC, "BPM Rot. Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL1:SBPM:HL13:SIM.E PP")
  field(VAL, "0.")
  field(EGU, "deg")
  field(PINI, "YES")
  field(PREC, "1")
  field(LOPR, "-180")
}

record(ao, "HL1:SBPM:HL13:PSIS") {
  field(DESC, "BPM Angle. Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL1:SBPM:HL13:SIM.F PP")
  field(VAL, "90")
  field(EGU, "deg")
  field(PINI, "YES")
  field(PREC, "1")
  field(LOPR, "0")
}

record(aao, "HL1:SBPM:HL13:DIGISIMW") {
  field(DESC, "VME Digi Sim. Waveform")
  field(DTYP, "VmeDigi Sim Wav")
  field(OUT,  "#C0 S0")
  field(FTVL, "SHORT")
  field(EGU,  "Counts")
  field(HOPR, "32678")
  field(LOPR, "-32768")
# 16384 samples/channel * 4 channels
  field(NELM, "65536")
  field(PINI, "NO")
}

#Used by model/database folks to verify BPM

record(ao, "HL1:SBPM:HL13:Z") {
  field(DESC, "Z Position")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

# MPS interface
record(bo, "HL1:SBPM:HL13:MPSBYP") {
  field(DESC, "MPS Bypass")
  field(DTYP, "BusAddress")
  field(OUT,  "#C0S2@bpmMPS+0,m32")
  field(MASK, "1")
  field(ZNAM, "BYPASSED")
  field(ONAM, "NOT_BYPASSED")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(VAL,  "0")
  field(PINI, "YES")
  field(ASG,  "")
  info(autosaveFields, "VAL")
}

record(bo, "HL1:SBPM:HL13:MPSLTBYP") {
  field(DESC, "MPS Bypass")
  field(DTYP, "BusAddress")
  field(OUT,  "#C1S2@bpmMPS+0,m32")
  field(MASK, "1")
  field(ZNAM, "BYPASSED")
  field(ONAM, "NOT_BYPASSED")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")
  field(VAL,  "0")
  field(PINI, "YES")
  field(ASG,  "")
  info(autosaveFields, "VAL")
}

record(calc, "HL1:SBPM:HL13:MPSIGNRCALC") {
  field(DESC, "MPS ignore if TMIT too low")
  field(CALC, "A<B")
  field(INPA, "HL1:SBPM:HL13:TMIT")
  field(INPB, "HL1:SBPM:HL13:T_MPS_THRES_L")
  field(HIHI, "1")
  field(HHSV, "MAJOR")
  field(ASG, "")
}

record(bi, "HL1:SBPM:HL13:MPSIGNORE") {
  field(DESC, "MPS ignore if TMIT too low")
  field(DTYP, "Raw Soft Channel")
  field(SCAN, "1 second")
  field(INP, "HL1:SBPM:HL13:MPSIGNRCALC PP")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "Not ignored")
  field(ONAM, "Ignored")
  field(PINI, "YES")
  field(ASG, "")
}

# Proxy records for users to set X.AOFF, Y.AOFF
# Placed CAS on X and Y for MPS 
# Feb 2010 - CAS has since been removed, but we'll keep 
# these proxy records as they're already in use

record(ao, "HL1:SBPM:HL13:XAOFF") {
  field(DESC, "X.AOFF val")
#  field(OUT, "HL1:SBPM:HL13:X.AOFF")
  field(PINI, "YES")
  field(EGU, "mm")
  field(PREC, "4")
  field(FLNK, "HL1:SBPM:HL13:XOFF")
  info(autosaveFields, "VAL")
}

record(ao, "HL1:SBPM:HL13:YAOFF") {
  field(DESC, "Y.AOFF val")
#  field(OUT, "HL1:SBPM:HL13:Y.AOFF")
  field(PINI, "YES")
  field(EGU, "mm")
  field(PREC, "4")
  field(FLNK, "HL1:SBPM:HL13:YOFF")
  info(autosaveFields, "VAL")
}

# Add CALC to allow users to maintain
# multiple offsets per plane per BPM

record(calcout, "HL1:SBPM:HL13:XOFF") {
  field(DESC, "Add X offsets")
  field(PREC, "4")
  field(CALC, "A+B+C+D")
  field(INPA, "HL1:SBPM:HL13:XAOFF")
# B-E reserved for undulator offsets
  field(INPB, "")
  field(INPC, "")
  field(INPD, "")
  field(INPE, "")
  field(EGU, "mm")
  field(OUT, "HL1:SBPM:HL13:X.AOFF")
  info(autosaveFields, "B C D E")
}

record(calcout, "HL1:SBPM:HL13:YOFF") {
  field(DESC, "Add Y offsets")
  field(PREC, "4")
  field(CALC, "A+B+C+D")
  field(INPA, "HL1:SBPM:HL13:YAOFF")
# B-E reserved for undulator offsets
  field(INPB, "")
  field(INPC, "")
  field(INPD, "")
  field(INPE, "")
  field(EGU, "mm")
  field(OUT, "HL1:SBPM:HL13:Y.AOFF")
  info(autosaveFields, "B C D E")
}


# Records to set MPS thresholds
record(ao, "HL1:SBPM:HL13:X_MPS_THRES_L") {
  field(DESC, "MPS X Threshold Lo")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C0 S0 @Lo")
  field(VAL,  "-1")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL1:SBPM:HL13:X_MPS_THRES_H") {
  field(DESC, "MPS X Threshold Hi")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C0 S0 @Hi")
  field(VAL,  "1")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL1:SBPM:HL13:Y_MPS_THRES_L") {
  field(DESC, "MPS Y Threshold Lo")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C0 S1 @Lo")
  field(VAL,  "-1")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL1:SBPM:HL13:Y_MPS_THRES_H") {
  field(DESC, "MPS Y Threshold Hi")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C0 S1 @Hi")
  field(VAL,  "1")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL1:SBPM:HL13:T_MPS_THRES_L") {
  field(DESC, "MPS TMIT Threshold Lo")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C0 S2 @Lo")
  field(VAL,  "9.375e7")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL1:SBPM:HL13:T_MPS_THRES_H") {
  field(DESC, "MPS TMIT Threshold Hi")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C0 S2 @Hi")
  field(VAL,  "+1.0E20")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}

record(bi, "HL1:SBPM:HL13:FNET") {
  field(DESC, "BPM data on FNET")
  field(VAL, "$(FN,undefined)")
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(PINI, "YES")
}

# Record to inform users that BPM
# needs TMIT and/or X/Y scale calibration
record(mbbo, "HL1:SBPM:HL13:CHK") {
  field(DESC, "Needs cal/iron")
  field(OMSL, "supervisory")
  field(VAL,  "0")
  field(ZRVL, "0")
  field(ONVL, "1")
  field(TWVL, "2")
  field(THVL, "3")
  field(ZRST, " ")
  field(ONST, "Calibrate")
  field(TWST, "Calibrate&iron")
  field(THST, "Iron")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MINOR")
  field(THSV, "MINOR")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

# Switch simulation record 
record(seq, "HL1:SBPM:HL13:SIMCSEQ") {
  field(DESC, "BPM Sim Ctl Seq")
  field(SELM, "Mask")
  field(SELN, "0")

  field(DO1,  "1")
  field(DO2,  "0")
  field(DO3,  "0")
  field(DO4,  "0") #Passive

#  field(DO5,  "7") # .5 second
  field(DO5,  "9") # .1 second
  field(DO6,  "2")
  field(DO7,  "1")
  field(DO8,  "10")
  field(DO9,  "0")

# LNK 1, 2, 8, 9 only relevant for PADs
# Default macro values are set for PADs; other
# architectures must pass in "" for lnk1 and lnk2
  field(LNK1, "")
  field(LNK2, "")
  field(LNK3, "HL1:SBPM:HL13:SIM.L     PP")
  field(LNK4, "HL1:SBPM:HL13:SIM.SCAN  PP")

  field(LNK5, "HL1:SBPM:HL13:SIM.SCAN  PP")
  field(LNK6, "HL1:SBPM:HL13:SIM.L     PP")
  field(LNK7, "HL1:SBPM:HL13:SIM.L     PP")
  field(LNK8, "")
  field(LNK9, "")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL1:SBPM:HL13:UOFF_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL1:SBPM:HL13:UOFF")
	field(DOL2, "HL1:SBPM:HL13:UOFF")
	field(DOL3, "HL1:SBPM:HL13:UOFF")
	field(DOL4, "HL1:SBPM:HL13:UOFF")
	field(DOL5, "HL1:SBPM:HL13:UOFF")
	field(DOL6, "HL1:SBPM:HL13:UOFF")
	field(DOL7, "HL1:SBPM:HL13:UOFF")
	field(DOL8, "HL1:SBPM:HL13:UOFF")
	field(DOL9, "HL1:SBPM:HL13:UOFF")
	field(DOLA, "HL1:SBPM:HL13:UOFF")
	field(LNK1, "HL1:SBPM:HL13:UOFF_SEL.A PP")
	field(LNK2, "HL1:SBPM:HL13:UOFF_SEL.B PP")
	field(LNK3, "HL1:SBPM:HL13:UOFF_SEL.C PP")
	field(LNK4, "HL1:SBPM:HL13:UOFF_SEL.D PP")
	field(LNK5, "HL1:SBPM:HL13:UOFF_SEL.E PP")
	field(LNK6, "HL1:SBPM:HL13:UOFF_SEL.F PP")
	field(LNK7, "HL1:SBPM:HL13:UOFF_SEL.G PP")
	field(LNK8, "HL1:SBPM:HL13:UOFF_SEL.H PP")
	field(LNK9, "HL1:SBPM:HL13:UOFF_SEL.I PP")
	field(LNKA, "HL1:SBPM:HL13:UOFF_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL1:SBPM:HL13:UOFF_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL1:SBPM:HL13:UOFF_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "0")
	field(B,    "0")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "4")
	field(FLNK, "HL1:SBPM:HL13:UOFF_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL1:SBPM:HL13:UOFF_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL1:SBPM:HL13:UOFF_SEL")
	field(OUTA, "HL1:SBPM:HL13:U.AOFF CA")
	field(OUTB, "HL1:SBPM:HL13:UOFF PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL1:SBPM:HL13:UOFF_CTRL")
{
	field(INPA, "HL1:SBPM:HL13:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL1:SBPM:HL13:UOFF_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL1:SBPM:HL13:VOFF_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL1:SBPM:HL13:VOFF")
	field(DOL2, "HL1:SBPM:HL13:VOFF")
	field(DOL3, "HL1:SBPM:HL13:VOFF")
	field(DOL4, "HL1:SBPM:HL13:VOFF")
	field(DOL5, "HL1:SBPM:HL13:VOFF")
	field(DOL6, "HL1:SBPM:HL13:VOFF")
	field(DOL7, "HL1:SBPM:HL13:VOFF")
	field(DOL8, "HL1:SBPM:HL13:VOFF")
	field(DOL9, "HL1:SBPM:HL13:VOFF")
	field(DOLA, "HL1:SBPM:HL13:VOFF")
	field(LNK1, "HL1:SBPM:HL13:VOFF_SEL.A PP")
	field(LNK2, "HL1:SBPM:HL13:VOFF_SEL.B PP")
	field(LNK3, "HL1:SBPM:HL13:VOFF_SEL.C PP")
	field(LNK4, "HL1:SBPM:HL13:VOFF_SEL.D PP")
	field(LNK5, "HL1:SBPM:HL13:VOFF_SEL.E PP")
	field(LNK6, "HL1:SBPM:HL13:VOFF_SEL.F PP")
	field(LNK7, "HL1:SBPM:HL13:VOFF_SEL.G PP")
	field(LNK8, "HL1:SBPM:HL13:VOFF_SEL.H PP")
	field(LNK9, "HL1:SBPM:HL13:VOFF_SEL.I PP")
	field(LNKA, "HL1:SBPM:HL13:VOFF_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL1:SBPM:HL13:VOFF_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL1:SBPM:HL13:VOFF_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "0")
	field(B,    "0")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "4")
	field(FLNK, "HL1:SBPM:HL13:VOFF_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL1:SBPM:HL13:VOFF_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL1:SBPM:HL13:VOFF_SEL")
	field(OUTA, "HL1:SBPM:HL13:V.AOFF CA")
	field(OUTB, "HL1:SBPM:HL13:VOFF PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL1:SBPM:HL13:VOFF_CTRL")
{
	field(INPA, "HL1:SBPM:HL13:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL1:SBPM:HL13:VOFF_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL1:SBPM:HL13:USCL_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL1:SBPM:HL13:USCL")
	field(DOL2, "HL1:SBPM:HL13:USCL")
	field(DOL3, "HL1:SBPM:HL13:USCL")
	field(DOL4, "HL1:SBPM:HL13:USCL")
	field(DOL5, "HL1:SBPM:HL13:USCL")
	field(DOL6, "HL1:SBPM:HL13:USCL")
	field(DOL7, "HL1:SBPM:HL13:USCL")
	field(DOL8, "HL1:SBPM:HL13:USCL")
	field(DOL9, "HL1:SBPM:HL13:USCL")
	field(DOLA, "HL1:SBPM:HL13:USCL")
	field(LNK1, "HL1:SBPM:HL13:USCL_SEL.A PP")
	field(LNK2, "HL1:SBPM:HL13:USCL_SEL.B PP")
	field(LNK3, "HL1:SBPM:HL13:USCL_SEL.C PP")
	field(LNK4, "HL1:SBPM:HL13:USCL_SEL.D PP")
	field(LNK5, "HL1:SBPM:HL13:USCL_SEL.E PP")
	field(LNK6, "HL1:SBPM:HL13:USCL_SEL.F PP")
	field(LNK7, "HL1:SBPM:HL13:USCL_SEL.G PP")
	field(LNK8, "HL1:SBPM:HL13:USCL_SEL.H PP")
	field(LNK9, "HL1:SBPM:HL13:USCL_SEL.I PP")
	field(LNKA, "HL1:SBPM:HL13:USCL_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL1:SBPM:HL13:USCL_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL1:SBPM:HL13:USCL_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "1")
	field(B,    "1")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "4")
	field(FLNK, "HL1:SBPM:HL13:USCL_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL1:SBPM:HL13:USCL_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL1:SBPM:HL13:USCL_SEL")
	field(OUTA, "HL1:SBPM:HL13:U.ASLO CA")
	field(OUTB, "HL1:SBPM:HL13:USCL PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL1:SBPM:HL13:USCL_CTRL")
{
	field(INPA, "HL1:SBPM:HL13:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL1:SBPM:HL13:USCL_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL1:SBPM:HL13:VSCL_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL1:SBPM:HL13:VSCL")
	field(DOL2, "HL1:SBPM:HL13:VSCL")
	field(DOL3, "HL1:SBPM:HL13:VSCL")
	field(DOL4, "HL1:SBPM:HL13:VSCL")
	field(DOL5, "HL1:SBPM:HL13:VSCL")
	field(DOL6, "HL1:SBPM:HL13:VSCL")
	field(DOL7, "HL1:SBPM:HL13:VSCL")
	field(DOL8, "HL1:SBPM:HL13:VSCL")
	field(DOL9, "HL1:SBPM:HL13:VSCL")
	field(DOLA, "HL1:SBPM:HL13:VSCL")
	field(LNK1, "HL1:SBPM:HL13:VSCL_SEL.A PP")
	field(LNK2, "HL1:SBPM:HL13:VSCL_SEL.B PP")
	field(LNK3, "HL1:SBPM:HL13:VSCL_SEL.C PP")
	field(LNK4, "HL1:SBPM:HL13:VSCL_SEL.D PP")
	field(LNK5, "HL1:SBPM:HL13:VSCL_SEL.E PP")
	field(LNK6, "HL1:SBPM:HL13:VSCL_SEL.F PP")
	field(LNK7, "HL1:SBPM:HL13:VSCL_SEL.G PP")
	field(LNK8, "HL1:SBPM:HL13:VSCL_SEL.H PP")
	field(LNK9, "HL1:SBPM:HL13:VSCL_SEL.I PP")
	field(LNKA, "HL1:SBPM:HL13:VSCL_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL1:SBPM:HL13:VSCL_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL1:SBPM:HL13:VSCL_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "1")
	field(B,    "1")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "4")
	field(FLNK, "HL1:SBPM:HL13:VSCL_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL1:SBPM:HL13:VSCL_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL1:SBPM:HL13:VSCL_SEL")
	field(OUTA, "HL1:SBPM:HL13:V.ASLO CA")
	field(OUTB, "HL1:SBPM:HL13:VSCL PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL1:SBPM:HL13:VSCL_CTRL")
{
	field(INPA, "HL1:SBPM:HL13:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL1:SBPM:HL13:VSCL_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL1:SBPM:HL13:PHI_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL1:SBPM:HL13:PHI")
	field(DOL2, "HL1:SBPM:HL13:PHI")
	field(DOL3, "HL1:SBPM:HL13:PHI")
	field(DOL4, "HL1:SBPM:HL13:PHI")
	field(DOL5, "HL1:SBPM:HL13:PHI")
	field(DOL6, "HL1:SBPM:HL13:PHI")
	field(DOL7, "HL1:SBPM:HL13:PHI")
	field(DOL8, "HL1:SBPM:HL13:PHI")
	field(DOL9, "HL1:SBPM:HL13:PHI")
	field(DOLA, "HL1:SBPM:HL13:PHI")
	field(LNK1, "HL1:SBPM:HL13:PHI_SEL.A PP")
	field(LNK2, "HL1:SBPM:HL13:PHI_SEL.B PP")
	field(LNK3, "HL1:SBPM:HL13:PHI_SEL.C PP")
	field(LNK4, "HL1:SBPM:HL13:PHI_SEL.D PP")
	field(LNK5, "HL1:SBPM:HL13:PHI_SEL.E PP")
	field(LNK6, "HL1:SBPM:HL13:PHI_SEL.F PP")
	field(LNK7, "HL1:SBPM:HL13:PHI_SEL.G PP")
	field(LNK8, "HL1:SBPM:HL13:PHI_SEL.H PP")
	field(LNK9, "HL1:SBPM:HL13:PHI_SEL.I PP")
	field(LNKA, "HL1:SBPM:HL13:PHI_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL1:SBPM:HL13:PHI_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL1:SBPM:HL13:PHI_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "0")
	field(B,    "0")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "1")
	field(FLNK, "HL1:SBPM:HL13:PHI_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL1:SBPM:HL13:PHI_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL1:SBPM:HL13:PHI_SEL")
	field(OUTA, "HL1:SBPM:HL13:CALC.E CA")
	field(OUTB, "HL1:SBPM:HL13:PHI PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL1:SBPM:HL13:PHI_CTRL")
{
	field(INPA, "HL1:SBPM:HL13:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL1:SBPM:HL13:PHI_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL1:SBPM:HL13:PSI_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL1:SBPM:HL13:PSI")
	field(DOL2, "HL1:SBPM:HL13:PSI")
	field(DOL3, "HL1:SBPM:HL13:PSI")
	field(DOL4, "HL1:SBPM:HL13:PSI")
	field(DOL5, "HL1:SBPM:HL13:PSI")
	field(DOL6, "HL1:SBPM:HL13:PSI")
	field(DOL7, "HL1:SBPM:HL13:PSI")
	field(DOL8, "HL1:SBPM:HL13:PSI")
	field(DOL9, "HL1:SBPM:HL13:PSI")
	field(DOLA, "HL1:SBPM:HL13:PSI")
	field(LNK1, "HL1:SBPM:HL13:PSI_SEL.A PP")
	field(LNK2, "HL1:SBPM:HL13:PSI_SEL.B PP")
	field(LNK3, "HL1:SBPM:HL13:PSI_SEL.C PP")
	field(LNK4, "HL1:SBPM:HL13:PSI_SEL.D PP")
	field(LNK5, "HL1:SBPM:HL13:PSI_SEL.E PP")
	field(LNK6, "HL1:SBPM:HL13:PSI_SEL.F PP")
	field(LNK7, "HL1:SBPM:HL13:PSI_SEL.G PP")
	field(LNK8, "HL1:SBPM:HL13:PSI_SEL.H PP")
	field(LNK9, "HL1:SBPM:HL13:PSI_SEL.I PP")
	field(LNKA, "HL1:SBPM:HL13:PSI_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL1:SBPM:HL13:PSI_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL1:SBPM:HL13:PSI_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "90")
	field(B,    "90")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "1")
	field(FLNK, "HL1:SBPM:HL13:PSI_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL1:SBPM:HL13:PSI_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL1:SBPM:HL13:PSI_SEL")
	field(OUTA, "HL1:SBPM:HL13:CALC.F CA")
	field(OUTB, "HL1:SBPM:HL13:PSI PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL1:SBPM:HL13:PSI_CTRL")
{
	field(INPA, "HL1:SBPM:HL13:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL1:SBPM:HL13:PSI_SEL.L PP")
}
record(longout, "HL1:SBPM:HL13:PARMSEL") {
	field(VAL, "0")
	field(PINI, "YES")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


# per BPM database for stripline BPMs

##############################################
# This is the head of the main processing chain
# that runs at the highest priority.
##############################################

#############################################
# This is the head of the processing chain for
# diagnostics.
##############################################
record(ai, "HL2:SBPM:HL14:GRN") {
  field(DESC, "GRN Strip Amplitude")
  field(DTYP, "Raw Bpm Signal")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "#C1 S0")
  field(EGU, "raw")
#TODO set HOPR/LOPR, alarm limits
  field(SCAN, "I/O Intr")
# The priority determines what scan list we are being
# put on (see drvPadUdpComm.c)
  field(PRIO, "LOW")
  field(FLNK, "HL2:SBPM:HL14:RED")
# HOPR for the energy algorithm is determined as follows:
#
#                      inf        inf
#  1) Fourier relation / h^2 dt = / |H|^2 df = 2 B
#                     0         -inf
#
#  1a) It can be shown that the maximum of the impuls response
#      ha is ~ 2 B
#                               
#  2) The digitizer produces the numbers
#
#     Ai = 2^s (hi/ha)
#
#     where ha is the maximum of the impuls response
#     and 2^s is a scale factor.
#     
#  3) 'Energy algorithm' calculates S = sum( Ai^2 )
#
#                                                     inf
#  4) S = (2^s / ha)^2 sum(hi^2) = K sum(hi^2) Dt ~ K / h^2 dt
#                                                    0
#
#     with K = (2^s / ha)^2 fs
#
#  5) From 4) and 1a) ->  S ~ K ha and therefore
#
#  6) S = 2^(2s) fs/ha = 2^(2s) fs/(2 B)
#
#  7) The strip signals are sqrt(S); hence HOPR is about
#
#     HOPR ~ 2^s  sqrt( fs/2/B )
#
#     with 2^s = 32768, fs=120MHz, B=10MHz it follows
#     that HOPR ~ 1E5; we add some margin...
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL14:RED") {
  field(DESC, "RED Strip Amplitude")
  field(DTYP, "Raw Bpm Signal")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "#C1 S1")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(FLNK, "HL2:SBPM:HL14:BLU")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL14:BLU") {
  field(DESC, "BLU Strip Amplitude")
  field(DTYP, "Raw Bpm Signal")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "#C1 S2")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(FLNK, "HL2:SBPM:HL14:YLO")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL14:YLO") {
  field(DESC, "YLO Strip Amplitude")
  field(DTYP, "Raw Bpm Signal")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "#C1 S3")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

##############################################
# Slowly-scanned diagnostics
##############################################

#
record(waveform, "HL2:SBPM:HL14:REDW") {
  field(DESC, "Raw CAL RED Data")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP, "#C1 S1")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "1 second")
}

record(waveform, "HL2:SBPM:HL14:GRNW") {
  field(DESC, "Raw CAL GRN Data")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP, "#C1 S2")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "1 second")
}

record(waveform, "HL2:SBPM:HL14:RAWDBG") {
  field(DESC, "Raw BEAM Dbg")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
# do not 'wbscan' for now since e.g., an underrange
# condition on the real signal can happen.
  field(INP, "#C1 S7")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "Passive")
}

record(waveform, "HL2:SBPM:HL14:REDDBG") {
  field(DESC, "Raw CAL RED Dbg")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP, "#C1 S8 @wbscan")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "Passive")
}

record(waveform, "HL2:SBPM:HL14:GRNDBG") {
  field(DESC, "Raw CAL GRN Dbg")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP, "#C1 S9 @wbscan")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "Passive")
}

record(ai, "HL2:SBPM:HL14:GRUV") {
  field(DESC, "CAL Gain GRN/RED")
  field(DTYP, "Raw Stripl Calp")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C1 S0")
  field(SCAN, "10 second")
  field(PREC, "4")
  field(LOPR, "0.5")
  field(HOPR, "1.5")
}

record(ai, "HL2:SBPM:HL14:GRU") {
  field(DESC, "CAL Gain GRN/BLU")
  field(DTYP, "Raw Stripl Calp")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C1 S1")
  field(SCAN, "10 second")
  field(PREC, "4")
  field(LOPR, "0.5")
  field(HOPR, "1.5")
  info(autosaveFields, "ASLO")
}

record(ai, "HL2:SBPM:HL14:GRV") {
  field(DESC, "CAL Gain RED/YLO")
  field(DTYP, "Raw Stripl Calp")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C1 S2")
  field(SCAN, "10 second")
  field(PREC, "4")
  field(LOPR, "0.5")
  field(HOPR, "1.5")
  info(autosaveFields, "ASLO")
}

record(ai, "HL2:SBPM:HL14:TGRN") {
  field(DESC, "Green arrival time")
  field(DTYP, "Raw Bpm Signal")
  field(EGU, "ADC Clocks")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C1 S4")
  field(SCAN, "10 second")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "128")
  field(LOLO, "5")
  field(LOW, "8")
  field(HIGH, "60")
  field(HIHI, "70")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
  field(HSV, "MINOR")
  field(HHSV, "MAJOR")
}

record(ai, "HL2:SBPM:HL14:TRED") {
  field(DESC, "Red arrival time")
  field(DTYP, "Raw Bpm Signal")
  field(EGU, "ADC Clocks")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C1 S5")
  field(SCAN, "10 second")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "128")
  field(LOLO, "5")
  field(LOW, "8")
  field(HIGH, "60")
  field(HIHI, "70")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
  field(HSV, "MINOR")
  field(HHSV, "MAJOR")
}

record(ai, "HL2:SBPM:HL14:TBLU") {
  field(DESC, "Blue arrival time")
  field(DTYP, "Raw Bpm Signal")
  field(EGU, "ADC Clocks")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C1 S6")
  field(SCAN, "10 second")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "128")
  field(LOLO, "5")
  field(LOW, "8")
  field(HIGH, "60")
  field(HIHI, "70")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
  field(HSV, "MINOR")
  field(HHSV, "MAJOR")
}

record(ai, "HL2:SBPM:HL14:TYLO") {
  field(DESC, "Yellow arrival time")
  field(DTYP, "Raw Bpm Signal")
  field(EGU, "ADC Clocks")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C1 S7")
  field(SCAN, "10 second")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "128")
  field(LOLO, "5")
  field(LOW, "8")
  field(HIGH, "60")
  field(HIHI, "70")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
  field(HSV, "MINOR")
  field(HHSV, "MAJOR")
}

record(ao, "HL2:SBPM:HL14:PINC_ADJ") {
  field(DESC, "Adjust Pinc. Corr.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL14:CALC.K PP MS")
  field(VAL, "0")
  field(DRVL, "0")
  field(DRVH, "2")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

# QSCL setting:
#
# Q: charge
# Z: impedance
# F: form factor: phi/(2 pi) sin(2 pi f l/c)
#
# Signal =  Q Z F G h(t) = A h(t)  [A] = Vs
#
#                  inf              inf
# Energy =  A^2   / h^2(t) dt = A^2 / |H(w)|^2 dw/2/pi = A^2 B
#                0                 0
#                        
# Measured energy = Sum{ (Vp/32768 * xi)^2 } / fs = S / fs ~ Energy
#
# -> A^2 B = S/fs
#
# With T = sqrt( Sum{ xi^2 } )
#
#    A = sqrt(S)/sqrt(B*fs) = T/sqrt(B*fs) Vp/32768
#
#                      T/32768 Vp
#    Q = A/F/G/Z = -----------------
#                   F G Z sqrt(B*fs)
#
# Vp = { 1.5Vpp/2 (PGA=1) or 2.25Vpp/2 (PGA=0) } / 2 (transformer)
#
# I believe PGA is off (-> Vp ~ .56V)
#
# Z  = 50
#
# G: (calibration uses GRN/BLU -> signal should have the
#    level of the grn/red channels with the additional switch)
#
# Block diagram / parts / gain:
#
# [filt]    [Att1]    [Amp1]   [Att2]    [BPF]      [Amp2]    [pad] [Amp3]   [switch]
# f-17520  hmc540lp3  SBF-5089 hmc540lp3 MBP-140-6-4 SBF-4089  PAT-0 SBF-4089 HMC-197
#
#  -2dB*    -1dB       20dB     -1dB     -4.5         14.8dB   0dB   14.8dB   -0.4dB
#
# *: 1st filter ATT is a wild guess.
#  BPF loss (RLC Catalog, pp.55): (L (nsect+.5) / (% of 3dB BW) + .2) dB
#  with L ~6.2  10MHz/fc=140Mhz filter-> 4.5
#
#  -> Gtot ~ 40.7dB
#
#  subtract cable loss (2dB); Gtot = 86
# 
#                      T/32768 Vp            .56V/32768
#    Q = A/F/G/Z = ----------------- = T/F  ------------------------
#                   F G Z sqrt(B*fs)        86*50*sqrt(10*140)Mhz
#
#      = T/F = 1.06E-7/F nC
#
#    F for a 7% coverage, 4" BPM at 140MHz   .07 sin(2*pi*140e6 4*.0254/3e8)
#      = .021
#
#      => 1.06E-7/.021 nC = 5E-6 nC
#
# (Faraday cup measurement -> (3600/44)^-1 1e-4 -> 1.22E-6
#
record(ao, "HL2:SBPM:HL14:QSCL") {
  field(DESC, "TMIT/Charge Scale")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL14:QSCA.A PP MS")
# 5.0E-6 / 1.6E-10 [nC/e-]
  field(VAL, "31250")
  field(EGU, "Nel")
  field(PREC, "3")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

# Adjust TMIT scale for AFE attenuation
record(calcout, "HL2:SBPM:HL14:QSCA") {
  field(DESC, "TMIT ATT Adj. Scale")
  field(INPB, "HL2:SBPM:HL14:ATT1 CP")
  field(INPC, "HL2:SBPM:HL14:ATT2 CP")
  field(CALC, "A*10^((B+C+D)/20)")
# use CA link to deposit into TMIT.ASLO so
# that TMIT is not forced into linkset
# of this record
  field(OUT, "HL2:SBPM:HL14:TMIT.ASLO CA")
  field(EGU, "Nel")
  field(PREC, "3")
  info(autosaveFields, "D")
}

record(ao,    "HL2:SBPM:HL14:ATT1SIMP") {
	field(DESC, "ATT1 Propagator")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL2:SBPM:HL14:ATT1   CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL2:SBPM:HL14:ASIM.A PP")
  	field(IVOA, "Set output to IVOV")
	field(IVOV, "0")
	field(EGU,  "dB")
}

record(ao,    "HL2:SBPM:HL14:ATT2SIMP") {
	field(DESC, "ATT2 Propagator")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL2:SBPM:HL14:ATT2   CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL2:SBPM:HL14:ASIM.C PP")
  	field(IVOA, "Set output to IVOV")
	field(IVOV, "0")
	field(EGU,  "dB")
}

# Attenuate charge either by
# real attenuator settings or
# by fake ones.
# If B, C >= 0 then their
# values will be used instead
# of ATT1, ATT2
record(calcout, "HL2:SBPM:HL14:ASIM") {
  field(DESC, "Q Simul Attenuator")
  field(DTYP, "Soft Channel")
  field(OUT,  "HL2:SBPM:HL14:QSIM.ESLO PP")
# ATT1SIM puts value into A
# set to -1 to use real attenuator settings
# and >=0 to use B instead
  field(B,    "-1")
# ATT2SIM puts value into C
# set to -1 to use real attenuator settings
# and >=0 to use D instead
  field(D,    "-1")
  field(CALC, "10^(((B>=0?B:A)+(D>=0?D:C))/20)")
  field(PINI, "YES")
}

record(ao, "HL2:SBPM:HL14:WSIM") {
  field(DESC, "BPM W Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL14:SIM.G PP")
  field(VAL, "0.07")
  field(EGU, "%")
  field(PINI, "YES")
  field(PREC, "3")
  field(LOPR, "0")
  field(HOPR, "0.25")
}


record(sel, "HL2:SBPM:HL14:STA") {
  field(DESC, "Status Summary")
  field(SELM, "High Signal")
  field(INPA, "HL2:SBPM:HL14:RSTA.SEVR MS NPP")
  field(INPB, "HL2:SBPM:HL14:TMIT.SEVR MS NPP")
  field(INPC, "HL2:SBPM:HL14:Y.SEVR    MS NPP")
  field(INPD, "HL2:SBPM:HL14:X.SEVR    MS NPP")
  field(INPE, "HL2:SBPM:HL14:TGRN.SEVR MS NPP")
  field(INPF, "HL2:SBPM:HL14:TRED.SEVR MS NPP")
  field(INPG, "HL2:SBPM:HL14:TBLU.SEVR MS NPP")
  field(INPH, "HL2:SBPM:HL14:TYLO.SEVR MS NPP")
  field(INPI, "HL2:SBPM:HL14:GRU.SEVR  MS NPP")
  field(INPJ, "HL2:SBPM:HL14:GRV.SEVR  MS NPP")
  field(SCAN, "1 second")
}

# This record really belongs on the
# PAD IOC. We keep them here however
# so we can save/restore. It is more
# confusing but shouldn't matter from
# an efficiency standpoint (they are
# rarely changed).
record(longout, "HL2:SBPM:HL14:ATTO") {
  field(DESC, "AFE Tot. Att. Offset")
# fetched via inlink
#field(OUT,  "HL2:SBPM:HL14:ATTC.B PP")
  field(DRVL, "-10")
  field(DRVH, "30")
  field(LOPR, "-10")
  field(HOPR, "30")
  field(EGU, "dB")
  field(VAL, "0")
  field(PINI, "YES")
  info(autosaveFields, "VAL DRVH HOPR DRVL LOPR")
}

# This record really belongs on the
# PAD IOC. We keep them here however
# so we can save/restore. It is more
# confusing but shouldn't matter from
# an efficiency standpoint (they are
# rarely changed).
record(longout, "HL2:SBPM:HL14:CLAO") {
  field(DESC, "AFE Cal. Att. Offset")
# fetched via inlink
#field(OUT,  "HL2:SBPM:HL14:ATTC.C PP")
  field(DRVL, "-20")
  field(DRVH, "20")
  field(LOPR, "-20")
  field(HOPR, "20")
  field(EGU, "dB")
  field(VAL, "40")
  field(PINI, "YES")
  info(autosaveFields, "VAL DRVH HOPR DRVL LOPR")
}

record(calc, "HL2:SBPM:HL14:STA_ALH") {
  field(DESC, "Status Summary")
  field(SCAN, "1 second")
  field(CALC, "0")
  field(INPA, "HL2:SBPM:HL14:RSTA_ALH.SEVR MS NPP")
  field(INPB, "HL2:SBPM:HL14:GRU.SEVR  MS NPP")
  field(INPC, "HL2:SBPM:HL14:GRV.SEVR  MS NPP")
  field(INPD, "HL2:SBPM:HL14:CHK.SEVR MS NPP")
}

# snapshot PV for the bpm values display
record(ai, "HL2:SBPM:HL14:GRN_SLOW") {
  field(DESC, "GRN snapshot for display")
  field(INP, "HL2:SBPM:HL14:GRN NPP MS")
  field(EGU, "raw")
  field(SCAN, "1 second")
  field(FLNK, "HL2:SBPM:HL14:RED_SLOW")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL14:RED_SLOW") {
  field(DESC, "RED snapshot for display")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "HL2:SBPM:HL14:RED NPP MS")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(FLNK, "HL2:SBPM:HL14:BLU_SLOW")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL14:BLU_SLOW") {
  field(DESC, "BLU snapshot for display")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "HL2:SBPM:HL14:BLU NPP MS")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(FLNK, "HL2:SBPM:HL14:YLO_SLOW")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL14:YLO_SLOW") {
  field(DESC, "YLO snapshot for display")
  field(INP, "HL2:SBPM:HL14:YLO NPP MS")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(sub, "HL2:SBPM:HL14:CALC") {
  field(SNAM, "drvBpmBvectSetupSub")
# E: phi F: psi
# BPM channel number in L
  field(INPL, "1")
  field(SCAN, "Passive")
}

record(bo, "HL2:SBPM:HL14:PINC_ENA") {
  field(DESC, "Simple Pincushion Alg")
  field(DTYP, "BusAddress")
  field(OUT,  "#C0S2@drvBpmStriplPincEna,m32")
  field(MASK, "2")
  field(ZNAM, "DISABLED")
  field(ONAM, "ENABLED")
  field(VAL,  "0")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

record(ao, "HL2:SBPM:HL14:UDR_THRES") {
  field(DESC, "Detection Underrange Threshold")
  field(DTYP, "Bpm Parameters")
  field(OUT,  "#C1S0")
  field(EGU,  "ADC Ticks")
  field(DOL,  "45.26")
  field(PINI, "YES")
  field(DRVL, "0")
  field(DRVH, "32767")
  info(autosaveFields, "VAL")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


# per BPM database for stripline BPMs

######################################
# HEAD of main processing chain
######################################

record(ai, "HL2:SBPM:HL14:X") {
  field(DESC, "X Position")
  field(EGU, "mm")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C1 S11")
  field(SCAN, "I/O Intr")
# The priority determines what scan list we are being
# put on (see drvPadUdpComm.c)
  field(PRIO, "HIGH")
  field(FLNK, "HL2:SBPM:HL14:Y")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
  field(ASG,  "")
  field(TSE, "-2")
  info(autosaveFields, "ASLO LOLO LOW HIGH HIHI HHSV LLSV")
}

record(ai, "HL2:SBPM:HL14:Y") {
  field(DESC, "Y Position")
  field(EGU, "mm")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C1 S12")
  field(FLNK, "HL2:SBPM:HL14:TMIT")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
  field(ASG,  "")
  field(TSE, "-2")
  info(autosaveFields, "ASLO LOLO LOW HIGH HIHI HHSV LLSV")
}

record(ai, "HL2:SBPM:HL14:TMIT") {
  field(DESC, "Charge Estimate")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C1 S13")
  field(EGU, "Nel")
  field(PREC, "3")
  field(LOPR, "0")
  field(HOPR, "1E11")
# FLINK into BSA
  field(FLNK, "HL2:SBPM:HL14:EFX.PROC")
  field(ASG,  "")
  field(TSE, "-2")
  info(autosaveFields, "LOLO LOW HIGH HIHI HHSV LLSV ")
}


######################################
# HEAD of diagnostics processing chain
######################################

# leave RWAV in it's own lockset; don't FLNK
# to 'U' & friends
record(waveform, "HL2:SBPM:HL14:RWAV") {
  field(DESC, "Raw BPM Data")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP,  "#C1 S0")
  field(SCAN, "I/O Intr")
# use LOW or HIGH to end up on the 'diagnostic' 
# scan list (see drvPadUdpComm.c)
  field(PRIO, "LOW")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU,  "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
}

record(ai, "HL2:SBPM:HL14:U") {
  field(DESC, "Raw U Position")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C1 S8")
  field(SCAN, "I/O Intr")
# use LOW or HIGH to end up on the 'diagnostic' 
# scan list (see drvPadUdpComm.c)
  field(PRIO, "LOW")
  field(PREC, "5")
  field(EGU,  "mm")
  field(LOPR, "-0.7")
  field(HOPR, "+0.7")
  field(FLNK, "HL2:SBPM:HL14:V")
}

record(ai, "HL2:SBPM:HL14:V") {
  field(DESC, "Raw V Position")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C1 S9")
  field(SCAN, "Passive")
  field(PREC, "5")
  field(EGU,  "mm")
  field(LOPR, "-0.7")
  field(HOPR, "+0.7")
  field(FLNK, "HL2:SBPM:HL14:PINC")
}

record(ai, "HL2:SBPM:HL14:PINC") {
  field(DESC, "Pin Cushion Corr.")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C1 S10")
  field(SCAN, "Passive")
}

record(longin, "HL2:SBPM:HL14:RSTA") {
  field(DESC, "Status of Raw Processor")
  field(DTYP, "Bpm Raw Status")
  field(INP, "#C1S0")
  field(SCAN, "1 second")
  field(LOLO, "-1")
  field(HIHI, "+1")
  field(HHSV, "INVALID")
  field(LLSV, "INVALID")
  field(FLNK, "HL2:SBPM:HL14:RSTA_ALH")
}


record(calc, "HL2:SBPM:HL14:RSTA_ALH") {
  field(CALC, "A & B")
  field(INPA, "HL2:SBPM:HL14:RSTA")
  field(INPB, "0x30F")
  field(HIHI, "1")
  field(LOLO, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(SCAN, "Passive")
}

######################################
# Input/Parameteres
######################################

record(ao, "HL2:SBPM:HL14:PHI") {
  field(DESC, "Rot Angle")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(EGU, "deg")
  field(PREC, "1")
  field(LOPR, "-180")
  field(HOPR, "+180")
  field(FLNK, "HL2:SBPM:HL14:PHI_SEQ")
}

record(ao, "HL2:SBPM:HL14:PSI") {
  field(DESC, "Axis Sep. Angle")
  field(DTYP, "Soft Channel")
  field(VAL, "90")
  field(EGU, "deg")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "+180")
  field(FLNK, "HL2:SBPM:HL14:PSI_SEQ")
}

#record(dfanout, "HL2:SBPM:HL14:PCMM") {
#  field(DESC, "BPM Scale")
#  field(OUTA, "HL2:SBPM:HL14:USCL PP MS")
#  field(OUTB, "HL2:SBPM:HL14:VSCL PP MS")
#  field(VAL, "12")
#  field(EGU, "mm")
#  field(PREC, "4")
#  field(LOPR, "5")
#  field(HOPR, "15")
#  field(PINI, "YES")
#}

record(ao, "HL2:SBPM:HL14:UOFF") {
  field(DESC, "BPM U Offset")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(EGU, "mm")
  field(PREC, "4")
  field(LOPR, "-5")
  field(HOPR, "+5")
  field(FLNK, "HL2:SBPM:HL14:UOFF_SEQ")
}

record(ao, "HL2:SBPM:HL14:VOFF") {
  field(DESC, "BPM V Offset")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(EGU, "mm")
  field(PREC, "4")
  field(LOPR, "-5")
  field(HOPR, "+5")
  field(FLNK, "HL2:SBPM:HL14:VOFF_SEQ")
}

record(ao, "HL2:SBPM:HL14:USCL") {
  field(DESC, "BPM U Scale")
  field(DTYP, "Soft Channel")
  field(VAL,  "1")
  field(EGU, "mm")
  field(PREC, "4")
  field(FLNK, "HL2:SBPM:HL14:USCL_SEQ")
}

record(ao, "HL2:SBPM:HL14:VSCL") {
  field(DESC, "BPM V Scale")
  field(DTYP, "Soft Channel")
  field(VAL,  "1")
  field(EGU, "mm")
  field(PREC, "4")
  field(FLNK, "HL2:SBPM:HL14:VSCL_SEQ")
}


record(mbbo, "HL2:SBPM:HL14:ACCESS") {
  field(DESC, "BPM On Line")
  field(DTYP, "StreamSwitch")
  field(OUT, "#C1 S0")
  field(ZRVL, "1")
  field(ZRST, "Running")
  field(ZRSV, "NO_ALARM")
  field(ONVL, "1")
  field(ONST, "Maintenance")
  field(ONSV, "MINOR")
  field(TWVL, "1")
  field(TWST, "Test")
  field(TWSV, "MINOR")
  field(THVL, "0")
  field(THST, "OFFLINE")
  field(THSV, "MAJOR")
# set both, rval and val to get it right
# regardless of whether devsup does conversion
# or not.
  field(RVAL, "0")
  field(VAL,  "0")
  field(PINI, "YES")
  field(FLNK, "HL2:SBPM:HL14:SIMOFF")
  info(autosaveFields, "RVAL")
}

#
# Used by higher level software to determine if a PV is in feedback or not.
# May also be used by actuator (magnet and RF) IOC applications to 
# switch output records to "closed_loop" to prevent outside programs from
# changing setpoints when an actuator device is in feedback.
#
record(mbbo, "HL2:SBPM:HL14:FBCK")
{
  field(DESC, "Feedback State")
  field(PINI, "YES")
  field(OMSL, "supervisory")
  field(VAL,  "0")
  field(ZRVL, "0")
  field(ONVL, "1")
  field(TWVL, "2")
# Off - this device can be used in feedback but all feedback loops 
# using it are off.
  field(ZRST, "Off")
# On - this device is being used by one or more feedback loops.
  field(ONST, "On")
# Unavailable - this device is not used by any feedback loop.
  field(TWST, "Unavailable")
  info(autosaveFields, "VAL")
}

# Convenience record holding the MAD name
record(stringin, "HL2:SBPM:HL14:MADN") {
  field(DESC, "MAD Name")
  field(VAL, "SBPMHL14")
  field(PINI, "YES")
}

record(stringin, "SBPMHL14:NAME") {
  field(DESC, "BPM Name")
  field(VAL, "HL2:SBPM:HL14")
  field(PINI, "YES")
}

record(ai, "HL2:SBPM:HL14:X_SLOW") {
#alias("HL2:SBPM:HL14:X1H")
  field(DESC, "X snapshot for display")
  field(EGU, "mm")
  field(INP, "HL2:SBPM:HL14:X MS")
  field(FLNK, "HL2:SBPM:HL14:Y_SLOW")
  field(PREC, "4")
  field(SCAN, "1 second")
  field(LOPR, "-12")
  field(HOPR, "+12")
}

record(ai, "HL2:SBPM:HL14:Y_SLOW") {
#alias("HL2:SBPM:HL14:Y1H")
  field(DESC, "Y snapshot for display")
  field(EGU, "mm")
  field(INP, "HL2:SBPM:HL14:Y NPP MS")
  field(FLNK, "HL2:SBPM:HL14:TMIT_SLOW")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
}

record(ai, "HL2:SBPM:HL14:TMIT_SLOW") {
#alias("HL2:SBPM:HL14:TMIT1H")
  field(DESC, "TMIT snapshot for display")
  field(INP, "HL2:SBPM:HL14:TMIT NPP MS")
  field(EGU, "Nel")
  field(PREC, "3")
  field(LOPR, "0")
  field(HOPR, "1E11")
}

######################################
# Simulation Parameters + Control
######################################

# switch off simulation when going off-line
record(calcout, "HL2:SBPM:HL14:SIMOFF") {
  field(DESC, "Sim Off Propagator")
  field(INPA, "HL2:SBPM:HL14:ACCESS.RVAL")
  field(CALC, "A")
  field(OCAL, "0")
  field(OOPT, "When Zero")
  field(DOPT, "Use OCAL")
  field(OUT,  "HL2:SBPM:HL14:SIMC PP")
}

record(calcout, "HL2:SBPM:HL14:SIM") {
  field(DESC, "BPM Pos. Simulation")
  field(DTYP, "Strip Signal Simulator")
  field(OUT, "1")
#CALC & VAL unused; the real calculation is done
#        in device support. The reason this is a
#        calcout rather than sub is that we want
#        to use the OUT link...
  field(CALC, "A")
  field(INPA, "HL2:SBPM:HL14:USCL")
  field(INPL, "0")
}

# Switch simulation record HL2:SBPM:HL14:SIMCSEQ moved to
# bpmCavity.db.part and bpmStripl.db.part 

record(mbbo, "HL2:SBPM:HL14:SIMC") {
  field(DESC, "Stripl Sim Ctl")
  field(DTYP, "Raw Soft Channel")
  field(OUT,  "HL2:SBPM:HL14:SIMCSEQ.SELN PP")
  field(ZRST, "OFF")
  field(ZRVL, "0x0f")
  field(ONST, "ON")
  field(ONVL, "0x1c0")
  field(TWST, "SOFT")
  field(TWVL, "0x030")
  field(MASK, "-1")
  field(NOBT, "16")
  field(VAL,  "0")
  field(RVAL, "0x0f")
  field(PINI, "YES")
}

record(ao, "HL2:SBPM:HL14:XSIM") {
  field(DESC, "BPM X Pos. Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL14:SIM.B PP")
  field(VAL, "0.5")
  field(EGU, "mm")
  field(PINI, "YES")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
}

record(ao, "HL2:SBPM:HL14:YSIM") {
  field(DESC, "BPM Y Pos. Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL14:SIM.C PP")
  field(VAL, "0.")
  field(EGU, "mm")
  field(PINI, "YES")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
}

record(ao, "HL2:SBPM:HL14:QSIM") {
  field(DESC, "BPM Q Simul.")
  field(DTYP, "Raw Soft Channel")
  field(OUT, "HL2:SBPM:HL14:SIM.D PP")
  field(EGU, "Nel")
  field(ASLO, "6000")
#ESLO is used to add attenuation
  field(LINR, "LINEAR")
  field(VAL, "1E9")
  field(PINI, "YES")
  field(PREC, "4")
  field(LOPR, "0")
  field(HOPR, "1E11")
}

record(ao, "HL2:SBPM:HL14:ROTS") {
  field(DESC, "BPM Rot. Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL14:SIM.E PP")
  field(VAL, "0.")
  field(EGU, "deg")
  field(PINI, "YES")
  field(PREC, "1")
  field(LOPR, "-180")
}

record(ao, "HL2:SBPM:HL14:PSIS") {
  field(DESC, "BPM Angle. Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL14:SIM.F PP")
  field(VAL, "90")
  field(EGU, "deg")
  field(PINI, "YES")
  field(PREC, "1")
  field(LOPR, "0")
}

record(aao, "HL2:SBPM:HL14:DIGISIMW") {
  field(DESC, "VME Digi Sim. Waveform")
  field(DTYP, "VmeDigi Sim Wav")
  field(OUT,  "#C1 S0")
  field(FTVL, "SHORT")
  field(EGU,  "Counts")
  field(HOPR, "32678")
  field(LOPR, "-32768")
# 16384 samples/channel * 4 channels
  field(NELM, "65536")
  field(PINI, "NO")
}

#Used by model/database folks to verify BPM

record(ao, "HL2:SBPM:HL14:Z") {
  field(DESC, "Z Position")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

# MPS interface
record(bo, "HL2:SBPM:HL14:MPSBYP") {
  field(DESC, "MPS Bypass")
  field(DTYP, "BusAddress")
  field(OUT,  "#C0S2@bpmMPS+0,m32")
  field(MASK, "2")
  field(ZNAM, "BYPASSED")
  field(ONAM, "NOT_BYPASSED")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(VAL,  "0")
  field(PINI, "YES")
  field(ASG,  "")
  info(autosaveFields, "VAL")
}

record(bo, "HL2:SBPM:HL14:MPSLTBYP") {
  field(DESC, "MPS Bypass")
  field(DTYP, "BusAddress")
  field(OUT,  "#C1S2@bpmMPS+0,m32")
  field(MASK, "2")
  field(ZNAM, "BYPASSED")
  field(ONAM, "NOT_BYPASSED")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")
  field(VAL,  "0")
  field(PINI, "YES")
  field(ASG,  "")
  info(autosaveFields, "VAL")
}

record(calc, "HL2:SBPM:HL14:MPSIGNRCALC") {
  field(DESC, "MPS ignore if TMIT too low")
  field(CALC, "A<B")
  field(INPA, "HL2:SBPM:HL14:TMIT")
  field(INPB, "HL2:SBPM:HL14:T_MPS_THRES_L")
  field(HIHI, "1")
  field(HHSV, "MAJOR")
  field(ASG, "")
}

record(bi, "HL2:SBPM:HL14:MPSIGNORE") {
  field(DESC, "MPS ignore if TMIT too low")
  field(DTYP, "Raw Soft Channel")
  field(SCAN, "1 second")
  field(INP, "HL2:SBPM:HL14:MPSIGNRCALC PP")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "Not ignored")
  field(ONAM, "Ignored")
  field(PINI, "YES")
  field(ASG, "")
}

# Proxy records for users to set X.AOFF, Y.AOFF
# Placed CAS on X and Y for MPS 
# Feb 2010 - CAS has since been removed, but we'll keep 
# these proxy records as they're already in use

record(ao, "HL2:SBPM:HL14:XAOFF") {
  field(DESC, "X.AOFF val")
#  field(OUT, "HL2:SBPM:HL14:X.AOFF")
  field(PINI, "YES")
  field(EGU, "mm")
  field(PREC, "4")
  field(FLNK, "HL2:SBPM:HL14:XOFF")
  info(autosaveFields, "VAL")
}

record(ao, "HL2:SBPM:HL14:YAOFF") {
  field(DESC, "Y.AOFF val")
#  field(OUT, "HL2:SBPM:HL14:Y.AOFF")
  field(PINI, "YES")
  field(EGU, "mm")
  field(PREC, "4")
  field(FLNK, "HL2:SBPM:HL14:YOFF")
  info(autosaveFields, "VAL")
}

# Add CALC to allow users to maintain
# multiple offsets per plane per BPM

record(calcout, "HL2:SBPM:HL14:XOFF") {
  field(DESC, "Add X offsets")
  field(PREC, "4")
  field(CALC, "A+B+C+D")
  field(INPA, "HL2:SBPM:HL14:XAOFF")
# B-E reserved for undulator offsets
  field(INPB, "")
  field(INPC, "")
  field(INPD, "")
  field(INPE, "")
  field(EGU, "mm")
  field(OUT, "HL2:SBPM:HL14:X.AOFF")
  info(autosaveFields, "B C D E")
}

record(calcout, "HL2:SBPM:HL14:YOFF") {
  field(DESC, "Add Y offsets")
  field(PREC, "4")
  field(CALC, "A+B+C+D")
  field(INPA, "HL2:SBPM:HL14:YAOFF")
# B-E reserved for undulator offsets
  field(INPB, "")
  field(INPC, "")
  field(INPD, "")
  field(INPE, "")
  field(EGU, "mm")
  field(OUT, "HL2:SBPM:HL14:Y.AOFF")
  info(autosaveFields, "B C D E")
}


# Records to set MPS thresholds
record(ao, "HL2:SBPM:HL14:X_MPS_THRES_L") {
  field(DESC, "MPS X Threshold Lo")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C1 S0 @Lo")
  field(VAL,  "-1")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL2:SBPM:HL14:X_MPS_THRES_H") {
  field(DESC, "MPS X Threshold Hi")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C1 S0 @Hi")
  field(VAL,  "1")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL2:SBPM:HL14:Y_MPS_THRES_L") {
  field(DESC, "MPS Y Threshold Lo")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C1 S1 @Lo")
  field(VAL,  "-1")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL2:SBPM:HL14:Y_MPS_THRES_H") {
  field(DESC, "MPS Y Threshold Hi")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C1 S1 @Hi")
  field(VAL,  "1")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL2:SBPM:HL14:T_MPS_THRES_L") {
  field(DESC, "MPS TMIT Threshold Lo")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C1 S2 @Lo")
  field(VAL,  "9.375e7")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL2:SBPM:HL14:T_MPS_THRES_H") {
  field(DESC, "MPS TMIT Threshold Hi")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C1 S2 @Hi")
  field(VAL,  "+1.0E20")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}

record(bi, "HL2:SBPM:HL14:FNET") {
  field(DESC, "BPM data on FNET")
  field(VAL, "$(FN,undefined)")
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(PINI, "YES")
}

# Record to inform users that BPM
# needs TMIT and/or X/Y scale calibration
record(mbbo, "HL2:SBPM:HL14:CHK") {
  field(DESC, "Needs cal/iron")
  field(OMSL, "supervisory")
  field(VAL,  "0")
  field(ZRVL, "0")
  field(ONVL, "1")
  field(TWVL, "2")
  field(THVL, "3")
  field(ZRST, " ")
  field(ONST, "Calibrate")
  field(TWST, "Calibrate&iron")
  field(THST, "Iron")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MINOR")
  field(THSV, "MINOR")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

# Switch simulation record 
record(seq, "HL2:SBPM:HL14:SIMCSEQ") {
  field(DESC, "BPM Sim Ctl Seq")
  field(SELM, "Mask")
  field(SELN, "0")

  field(DO1,  "1")
  field(DO2,  "0")
  field(DO3,  "0")
  field(DO4,  "0") #Passive

#  field(DO5,  "7") # .5 second
  field(DO5,  "9") # .1 second
  field(DO6,  "2")
  field(DO7,  "1")
  field(DO8,  "10")
  field(DO9,  "0")

# LNK 1, 2, 8, 9 only relevant for PADs
# Default macro values are set for PADs; other
# architectures must pass in "" for lnk1 and lnk2
  field(LNK1, "")
  field(LNK2, "")
  field(LNK3, "HL2:SBPM:HL14:SIM.L     PP")
  field(LNK4, "HL2:SBPM:HL14:SIM.SCAN  PP")

  field(LNK5, "HL2:SBPM:HL14:SIM.SCAN  PP")
  field(LNK6, "HL2:SBPM:HL14:SIM.L     PP")
  field(LNK7, "HL2:SBPM:HL14:SIM.L     PP")
  field(LNK8, "")
  field(LNK9, "")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL14:UOFF_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL14:UOFF")
	field(DOL2, "HL2:SBPM:HL14:UOFF")
	field(DOL3, "HL2:SBPM:HL14:UOFF")
	field(DOL4, "HL2:SBPM:HL14:UOFF")
	field(DOL5, "HL2:SBPM:HL14:UOFF")
	field(DOL6, "HL2:SBPM:HL14:UOFF")
	field(DOL7, "HL2:SBPM:HL14:UOFF")
	field(DOL8, "HL2:SBPM:HL14:UOFF")
	field(DOL9, "HL2:SBPM:HL14:UOFF")
	field(DOLA, "HL2:SBPM:HL14:UOFF")
	field(LNK1, "HL2:SBPM:HL14:UOFF_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL14:UOFF_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL14:UOFF_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL14:UOFF_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL14:UOFF_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL14:UOFF_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL14:UOFF_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL14:UOFF_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL14:UOFF_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL14:UOFF_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL14:UOFF_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL14:UOFF_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "0")
	field(B,    "0")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "4")
	field(FLNK, "HL2:SBPM:HL14:UOFF_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL14:UOFF_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL14:UOFF_SEL")
	field(OUTA, "HL2:SBPM:HL14:U.AOFF CA")
	field(OUTB, "HL2:SBPM:HL14:UOFF PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL14:UOFF_CTRL")
{
	field(INPA, "HL2:SBPM:HL14:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL14:UOFF_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL14:VOFF_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL14:VOFF")
	field(DOL2, "HL2:SBPM:HL14:VOFF")
	field(DOL3, "HL2:SBPM:HL14:VOFF")
	field(DOL4, "HL2:SBPM:HL14:VOFF")
	field(DOL5, "HL2:SBPM:HL14:VOFF")
	field(DOL6, "HL2:SBPM:HL14:VOFF")
	field(DOL7, "HL2:SBPM:HL14:VOFF")
	field(DOL8, "HL2:SBPM:HL14:VOFF")
	field(DOL9, "HL2:SBPM:HL14:VOFF")
	field(DOLA, "HL2:SBPM:HL14:VOFF")
	field(LNK1, "HL2:SBPM:HL14:VOFF_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL14:VOFF_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL14:VOFF_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL14:VOFF_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL14:VOFF_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL14:VOFF_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL14:VOFF_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL14:VOFF_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL14:VOFF_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL14:VOFF_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL14:VOFF_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL14:VOFF_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "0")
	field(B,    "0")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "4")
	field(FLNK, "HL2:SBPM:HL14:VOFF_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL14:VOFF_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL14:VOFF_SEL")
	field(OUTA, "HL2:SBPM:HL14:V.AOFF CA")
	field(OUTB, "HL2:SBPM:HL14:VOFF PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL14:VOFF_CTRL")
{
	field(INPA, "HL2:SBPM:HL14:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL14:VOFF_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL14:USCL_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL14:USCL")
	field(DOL2, "HL2:SBPM:HL14:USCL")
	field(DOL3, "HL2:SBPM:HL14:USCL")
	field(DOL4, "HL2:SBPM:HL14:USCL")
	field(DOL5, "HL2:SBPM:HL14:USCL")
	field(DOL6, "HL2:SBPM:HL14:USCL")
	field(DOL7, "HL2:SBPM:HL14:USCL")
	field(DOL8, "HL2:SBPM:HL14:USCL")
	field(DOL9, "HL2:SBPM:HL14:USCL")
	field(DOLA, "HL2:SBPM:HL14:USCL")
	field(LNK1, "HL2:SBPM:HL14:USCL_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL14:USCL_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL14:USCL_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL14:USCL_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL14:USCL_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL14:USCL_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL14:USCL_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL14:USCL_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL14:USCL_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL14:USCL_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL14:USCL_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL14:USCL_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "1")
	field(B,    "1")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "4")
	field(FLNK, "HL2:SBPM:HL14:USCL_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL14:USCL_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL14:USCL_SEL")
	field(OUTA, "HL2:SBPM:HL14:U.ASLO CA")
	field(OUTB, "HL2:SBPM:HL14:USCL PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL14:USCL_CTRL")
{
	field(INPA, "HL2:SBPM:HL14:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL14:USCL_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL14:VSCL_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL14:VSCL")
	field(DOL2, "HL2:SBPM:HL14:VSCL")
	field(DOL3, "HL2:SBPM:HL14:VSCL")
	field(DOL4, "HL2:SBPM:HL14:VSCL")
	field(DOL5, "HL2:SBPM:HL14:VSCL")
	field(DOL6, "HL2:SBPM:HL14:VSCL")
	field(DOL7, "HL2:SBPM:HL14:VSCL")
	field(DOL8, "HL2:SBPM:HL14:VSCL")
	field(DOL9, "HL2:SBPM:HL14:VSCL")
	field(DOLA, "HL2:SBPM:HL14:VSCL")
	field(LNK1, "HL2:SBPM:HL14:VSCL_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL14:VSCL_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL14:VSCL_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL14:VSCL_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL14:VSCL_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL14:VSCL_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL14:VSCL_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL14:VSCL_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL14:VSCL_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL14:VSCL_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL14:VSCL_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL14:VSCL_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "1")
	field(B,    "1")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "4")
	field(FLNK, "HL2:SBPM:HL14:VSCL_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL14:VSCL_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL14:VSCL_SEL")
	field(OUTA, "HL2:SBPM:HL14:V.ASLO CA")
	field(OUTB, "HL2:SBPM:HL14:VSCL PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL14:VSCL_CTRL")
{
	field(INPA, "HL2:SBPM:HL14:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL14:VSCL_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL14:PHI_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL14:PHI")
	field(DOL2, "HL2:SBPM:HL14:PHI")
	field(DOL3, "HL2:SBPM:HL14:PHI")
	field(DOL4, "HL2:SBPM:HL14:PHI")
	field(DOL5, "HL2:SBPM:HL14:PHI")
	field(DOL6, "HL2:SBPM:HL14:PHI")
	field(DOL7, "HL2:SBPM:HL14:PHI")
	field(DOL8, "HL2:SBPM:HL14:PHI")
	field(DOL9, "HL2:SBPM:HL14:PHI")
	field(DOLA, "HL2:SBPM:HL14:PHI")
	field(LNK1, "HL2:SBPM:HL14:PHI_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL14:PHI_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL14:PHI_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL14:PHI_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL14:PHI_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL14:PHI_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL14:PHI_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL14:PHI_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL14:PHI_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL14:PHI_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL14:PHI_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL14:PHI_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "0")
	field(B,    "0")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "1")
	field(FLNK, "HL2:SBPM:HL14:PHI_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL14:PHI_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL14:PHI_SEL")
	field(OUTA, "HL2:SBPM:HL14:CALC.E CA")
	field(OUTB, "HL2:SBPM:HL14:PHI PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL14:PHI_CTRL")
{
	field(INPA, "HL2:SBPM:HL14:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL14:PHI_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL14:PSI_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL14:PSI")
	field(DOL2, "HL2:SBPM:HL14:PSI")
	field(DOL3, "HL2:SBPM:HL14:PSI")
	field(DOL4, "HL2:SBPM:HL14:PSI")
	field(DOL5, "HL2:SBPM:HL14:PSI")
	field(DOL6, "HL2:SBPM:HL14:PSI")
	field(DOL7, "HL2:SBPM:HL14:PSI")
	field(DOL8, "HL2:SBPM:HL14:PSI")
	field(DOL9, "HL2:SBPM:HL14:PSI")
	field(DOLA, "HL2:SBPM:HL14:PSI")
	field(LNK1, "HL2:SBPM:HL14:PSI_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL14:PSI_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL14:PSI_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL14:PSI_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL14:PSI_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL14:PSI_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL14:PSI_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL14:PSI_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL14:PSI_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL14:PSI_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL14:PSI_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL14:PSI_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "90")
	field(B,    "90")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "1")
	field(FLNK, "HL2:SBPM:HL14:PSI_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL14:PSI_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL14:PSI_SEL")
	field(OUTA, "HL2:SBPM:HL14:CALC.F CA")
	field(OUTB, "HL2:SBPM:HL14:PSI PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL14:PSI_CTRL")
{
	field(INPA, "HL2:SBPM:HL14:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL14:PSI_SEL.L PP")
}
record(longout, "HL2:SBPM:HL14:PARMSEL") {
	field(VAL, "0")
	field(PINI, "YES")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


# per BPM database for stripline BPMs

##############################################
# This is the head of the main processing chain
# that runs at the highest priority.
##############################################

#############################################
# This is the head of the processing chain for
# diagnostics.
##############################################
record(ai, "HL2:SBPM:HL15:GRN") {
  field(DESC, "GRN Strip Amplitude")
  field(DTYP, "Raw Bpm Signal")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "#C2 S0")
  field(EGU, "raw")
#TODO set HOPR/LOPR, alarm limits
  field(SCAN, "I/O Intr")
# The priority determines what scan list we are being
# put on (see drvPadUdpComm.c)
  field(PRIO, "LOW")
  field(FLNK, "HL2:SBPM:HL15:RED")
# HOPR for the energy algorithm is determined as follows:
#
#                      inf        inf
#  1) Fourier relation / h^2 dt = / |H|^2 df = 2 B
#                     0         -inf
#
#  1a) It can be shown that the maximum of the impuls response
#      ha is ~ 2 B
#                               
#  2) The digitizer produces the numbers
#
#     Ai = 2^s (hi/ha)
#
#     where ha is the maximum of the impuls response
#     and 2^s is a scale factor.
#     
#  3) 'Energy algorithm' calculates S = sum( Ai^2 )
#
#                                                     inf
#  4) S = (2^s / ha)^2 sum(hi^2) = K sum(hi^2) Dt ~ K / h^2 dt
#                                                    0
#
#     with K = (2^s / ha)^2 fs
#
#  5) From 4) and 1a) ->  S ~ K ha and therefore
#
#  6) S = 2^(2s) fs/ha = 2^(2s) fs/(2 B)
#
#  7) The strip signals are sqrt(S); hence HOPR is about
#
#     HOPR ~ 2^s  sqrt( fs/2/B )
#
#     with 2^s = 32768, fs=120MHz, B=10MHz it follows
#     that HOPR ~ 1E5; we add some margin...
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL15:RED") {
  field(DESC, "RED Strip Amplitude")
  field(DTYP, "Raw Bpm Signal")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "#C2 S1")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(FLNK, "HL2:SBPM:HL15:BLU")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL15:BLU") {
  field(DESC, "BLU Strip Amplitude")
  field(DTYP, "Raw Bpm Signal")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "#C2 S2")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(FLNK, "HL2:SBPM:HL15:YLO")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL15:YLO") {
  field(DESC, "YLO Strip Amplitude")
  field(DTYP, "Raw Bpm Signal")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "#C2 S3")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

##############################################
# Slowly-scanned diagnostics
##############################################

#
record(waveform, "HL2:SBPM:HL15:REDW") {
  field(DESC, "Raw CAL RED Data")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP, "#C2 S1")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "1 second")
}

record(waveform, "HL2:SBPM:HL15:GRNW") {
  field(DESC, "Raw CAL GRN Data")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP, "#C2 S2")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "1 second")
}

record(waveform, "HL2:SBPM:HL15:RAWDBG") {
  field(DESC, "Raw BEAM Dbg")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
# do not 'wbscan' for now since e.g., an underrange
# condition on the real signal can happen.
  field(INP, "#C2 S7")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "Passive")
}

record(waveform, "HL2:SBPM:HL15:REDDBG") {
  field(DESC, "Raw CAL RED Dbg")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP, "#C2 S8 @wbscan")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "Passive")
}

record(waveform, "HL2:SBPM:HL15:GRNDBG") {
  field(DESC, "Raw CAL GRN Dbg")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP, "#C2 S9 @wbscan")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "Passive")
}

record(ai, "HL2:SBPM:HL15:GRUV") {
  field(DESC, "CAL Gain GRN/RED")
  field(DTYP, "Raw Stripl Calp")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C2 S0")
  field(SCAN, "10 second")
  field(PREC, "4")
  field(LOPR, "0.5")
  field(HOPR, "1.5")
}

record(ai, "HL2:SBPM:HL15:GRU") {
  field(DESC, "CAL Gain GRN/BLU")
  field(DTYP, "Raw Stripl Calp")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C2 S1")
  field(SCAN, "10 second")
  field(PREC, "4")
  field(LOPR, "0.5")
  field(HOPR, "1.5")
  info(autosaveFields, "ASLO")
}

record(ai, "HL2:SBPM:HL15:GRV") {
  field(DESC, "CAL Gain RED/YLO")
  field(DTYP, "Raw Stripl Calp")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C2 S2")
  field(SCAN, "10 second")
  field(PREC, "4")
  field(LOPR, "0.5")
  field(HOPR, "1.5")
  info(autosaveFields, "ASLO")
}

record(ai, "HL2:SBPM:HL15:TGRN") {
  field(DESC, "Green arrival time")
  field(DTYP, "Raw Bpm Signal")
  field(EGU, "ADC Clocks")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C2 S4")
  field(SCAN, "10 second")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "128")
  field(LOLO, "5")
  field(LOW, "8")
  field(HIGH, "60")
  field(HIHI, "70")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
  field(HSV, "MINOR")
  field(HHSV, "MAJOR")
}

record(ai, "HL2:SBPM:HL15:TRED") {
  field(DESC, "Red arrival time")
  field(DTYP, "Raw Bpm Signal")
  field(EGU, "ADC Clocks")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C2 S5")
  field(SCAN, "10 second")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "128")
  field(LOLO, "5")
  field(LOW, "8")
  field(HIGH, "60")
  field(HIHI, "70")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
  field(HSV, "MINOR")
  field(HHSV, "MAJOR")
}

record(ai, "HL2:SBPM:HL15:TBLU") {
  field(DESC, "Blue arrival time")
  field(DTYP, "Raw Bpm Signal")
  field(EGU, "ADC Clocks")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C2 S6")
  field(SCAN, "10 second")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "128")
  field(LOLO, "5")
  field(LOW, "8")
  field(HIGH, "60")
  field(HIHI, "70")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
  field(HSV, "MINOR")
  field(HHSV, "MAJOR")
}

record(ai, "HL2:SBPM:HL15:TYLO") {
  field(DESC, "Yellow arrival time")
  field(DTYP, "Raw Bpm Signal")
  field(EGU, "ADC Clocks")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C2 S7")
  field(SCAN, "10 second")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "128")
  field(LOLO, "5")
  field(LOW, "8")
  field(HIGH, "60")
  field(HIHI, "70")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
  field(HSV, "MINOR")
  field(HHSV, "MAJOR")
}

record(ao, "HL2:SBPM:HL15:PINC_ADJ") {
  field(DESC, "Adjust Pinc. Corr.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL15:CALC.K PP MS")
  field(VAL, "0")
  field(DRVL, "0")
  field(DRVH, "2")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

# QSCL setting:
#
# Q: charge
# Z: impedance
# F: form factor: phi/(2 pi) sin(2 pi f l/c)
#
# Signal =  Q Z F G h(t) = A h(t)  [A] = Vs
#
#                  inf              inf
# Energy =  A^2   / h^2(t) dt = A^2 / |H(w)|^2 dw/2/pi = A^2 B
#                0                 0
#                        
# Measured energy = Sum{ (Vp/32768 * xi)^2 } / fs = S / fs ~ Energy
#
# -> A^2 B = S/fs
#
# With T = sqrt( Sum{ xi^2 } )
#
#    A = sqrt(S)/sqrt(B*fs) = T/sqrt(B*fs) Vp/32768
#
#                      T/32768 Vp
#    Q = A/F/G/Z = -----------------
#                   F G Z sqrt(B*fs)
#
# Vp = { 1.5Vpp/2 (PGA=1) or 2.25Vpp/2 (PGA=0) } / 2 (transformer)
#
# I believe PGA is off (-> Vp ~ .56V)
#
# Z  = 50
#
# G: (calibration uses GRN/BLU -> signal should have the
#    level of the grn/red channels with the additional switch)
#
# Block diagram / parts / gain:
#
# [filt]    [Att1]    [Amp1]   [Att2]    [BPF]      [Amp2]    [pad] [Amp3]   [switch]
# f-17520  hmc540lp3  SBF-5089 hmc540lp3 MBP-140-6-4 SBF-4089  PAT-0 SBF-4089 HMC-197
#
#  -2dB*    -1dB       20dB     -1dB     -4.5         14.8dB   0dB   14.8dB   -0.4dB
#
# *: 1st filter ATT is a wild guess.
#  BPF loss (RLC Catalog, pp.55): (L (nsect+.5) / (% of 3dB BW) + .2) dB
#  with L ~6.2  10MHz/fc=140Mhz filter-> 4.5
#
#  -> Gtot ~ 40.7dB
#
#  subtract cable loss (2dB); Gtot = 86
# 
#                      T/32768 Vp            .56V/32768
#    Q = A/F/G/Z = ----------------- = T/F  ------------------------
#                   F G Z sqrt(B*fs)        86*50*sqrt(10*140)Mhz
#
#      = T/F = 1.06E-7/F nC
#
#    F for a 7% coverage, 4" BPM at 140MHz   .07 sin(2*pi*140e6 4*.0254/3e8)
#      = .021
#
#      => 1.06E-7/.021 nC = 5E-6 nC
#
# (Faraday cup measurement -> (3600/44)^-1 1e-4 -> 1.22E-6
#
record(ao, "HL2:SBPM:HL15:QSCL") {
  field(DESC, "TMIT/Charge Scale")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL15:QSCA.A PP MS")
# 5.0E-6 / 1.6E-10 [nC/e-]
  field(VAL, "31250")
  field(EGU, "Nel")
  field(PREC, "3")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

# Adjust TMIT scale for AFE attenuation
record(calcout, "HL2:SBPM:HL15:QSCA") {
  field(DESC, "TMIT ATT Adj. Scale")
  field(INPB, "HL2:SBPM:HL15:ATT1 CP")
  field(INPC, "HL2:SBPM:HL15:ATT2 CP")
  field(CALC, "A*10^((B+C+D)/20)")
# use CA link to deposit into TMIT.ASLO so
# that TMIT is not forced into linkset
# of this record
  field(OUT, "HL2:SBPM:HL15:TMIT.ASLO CA")
  field(EGU, "Nel")
  field(PREC, "3")
  info(autosaveFields, "D")
}

record(ao,    "HL2:SBPM:HL15:ATT1SIMP") {
	field(DESC, "ATT1 Propagator")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL2:SBPM:HL15:ATT1   CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL2:SBPM:HL15:ASIM.A PP")
  	field(IVOA, "Set output to IVOV")
	field(IVOV, "0")
	field(EGU,  "dB")
}

record(ao,    "HL2:SBPM:HL15:ATT2SIMP") {
	field(DESC, "ATT2 Propagator")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL2:SBPM:HL15:ATT2   CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL2:SBPM:HL15:ASIM.C PP")
  	field(IVOA, "Set output to IVOV")
	field(IVOV, "0")
	field(EGU,  "dB")
}

# Attenuate charge either by
# real attenuator settings or
# by fake ones.
# If B, C >= 0 then their
# values will be used instead
# of ATT1, ATT2
record(calcout, "HL2:SBPM:HL15:ASIM") {
  field(DESC, "Q Simul Attenuator")
  field(DTYP, "Soft Channel")
  field(OUT,  "HL2:SBPM:HL15:QSIM.ESLO PP")
# ATT1SIM puts value into A
# set to -1 to use real attenuator settings
# and >=0 to use B instead
  field(B,    "-1")
# ATT2SIM puts value into C
# set to -1 to use real attenuator settings
# and >=0 to use D instead
  field(D,    "-1")
  field(CALC, "10^(((B>=0?B:A)+(D>=0?D:C))/20)")
  field(PINI, "YES")
}

record(ao, "HL2:SBPM:HL15:WSIM") {
  field(DESC, "BPM W Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL15:SIM.G PP")
  field(VAL, "0.07")
  field(EGU, "%")
  field(PINI, "YES")
  field(PREC, "3")
  field(LOPR, "0")
  field(HOPR, "0.25")
}


record(sel, "HL2:SBPM:HL15:STA") {
  field(DESC, "Status Summary")
  field(SELM, "High Signal")
  field(INPA, "HL2:SBPM:HL15:RSTA.SEVR MS NPP")
  field(INPB, "HL2:SBPM:HL15:TMIT.SEVR MS NPP")
  field(INPC, "HL2:SBPM:HL15:Y.SEVR    MS NPP")
  field(INPD, "HL2:SBPM:HL15:X.SEVR    MS NPP")
  field(INPE, "HL2:SBPM:HL15:TGRN.SEVR MS NPP")
  field(INPF, "HL2:SBPM:HL15:TRED.SEVR MS NPP")
  field(INPG, "HL2:SBPM:HL15:TBLU.SEVR MS NPP")
  field(INPH, "HL2:SBPM:HL15:TYLO.SEVR MS NPP")
  field(INPI, "HL2:SBPM:HL15:GRU.SEVR  MS NPP")
  field(INPJ, "HL2:SBPM:HL15:GRV.SEVR  MS NPP")
  field(SCAN, "1 second")
}

# This record really belongs on the
# PAD IOC. We keep them here however
# so we can save/restore. It is more
# confusing but shouldn't matter from
# an efficiency standpoint (they are
# rarely changed).
record(longout, "HL2:SBPM:HL15:ATTO") {
  field(DESC, "AFE Tot. Att. Offset")
# fetched via inlink
#field(OUT,  "HL2:SBPM:HL15:ATTC.B PP")
  field(DRVL, "-10")
  field(DRVH, "30")
  field(LOPR, "-10")
  field(HOPR, "30")
  field(EGU, "dB")
  field(VAL, "0")
  field(PINI, "YES")
  info(autosaveFields, "VAL DRVH HOPR DRVL LOPR")
}

# This record really belongs on the
# PAD IOC. We keep them here however
# so we can save/restore. It is more
# confusing but shouldn't matter from
# an efficiency standpoint (they are
# rarely changed).
record(longout, "HL2:SBPM:HL15:CLAO") {
  field(DESC, "AFE Cal. Att. Offset")
# fetched via inlink
#field(OUT,  "HL2:SBPM:HL15:ATTC.C PP")
  field(DRVL, "-20")
  field(DRVH, "20")
  field(LOPR, "-20")
  field(HOPR, "20")
  field(EGU, "dB")
  field(VAL, "40")
  field(PINI, "YES")
  info(autosaveFields, "VAL DRVH HOPR DRVL LOPR")
}

record(calc, "HL2:SBPM:HL15:STA_ALH") {
  field(DESC, "Status Summary")
  field(SCAN, "1 second")
  field(CALC, "0")
  field(INPA, "HL2:SBPM:HL15:RSTA_ALH.SEVR MS NPP")
  field(INPB, "HL2:SBPM:HL15:GRU.SEVR  MS NPP")
  field(INPC, "HL2:SBPM:HL15:GRV.SEVR  MS NPP")
  field(INPD, "HL2:SBPM:HL15:CHK.SEVR MS NPP")
}

# snapshot PV for the bpm values display
record(ai, "HL2:SBPM:HL15:GRN_SLOW") {
  field(DESC, "GRN snapshot for display")
  field(INP, "HL2:SBPM:HL15:GRN NPP MS")
  field(EGU, "raw")
  field(SCAN, "1 second")
  field(FLNK, "HL2:SBPM:HL15:RED_SLOW")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL15:RED_SLOW") {
  field(DESC, "RED snapshot for display")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "HL2:SBPM:HL15:RED NPP MS")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(FLNK, "HL2:SBPM:HL15:BLU_SLOW")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL15:BLU_SLOW") {
  field(DESC, "BLU snapshot for display")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "HL2:SBPM:HL15:BLU NPP MS")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(FLNK, "HL2:SBPM:HL15:YLO_SLOW")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL15:YLO_SLOW") {
  field(DESC, "YLO snapshot for display")
  field(INP, "HL2:SBPM:HL15:YLO NPP MS")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(sub, "HL2:SBPM:HL15:CALC") {
  field(SNAM, "drvBpmBvectSetupSub")
# E: phi F: psi
# BPM channel number in L
  field(INPL, "2")
  field(SCAN, "Passive")
}

record(bo, "HL2:SBPM:HL15:PINC_ENA") {
  field(DESC, "Simple Pincushion Alg")
  field(DTYP, "BusAddress")
  field(OUT,  "#C0S2@drvBpmStriplPincEna,m32")
  field(MASK, "4")
  field(ZNAM, "DISABLED")
  field(ONAM, "ENABLED")
  field(VAL,  "0")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

record(ao, "HL2:SBPM:HL15:UDR_THRES") {
  field(DESC, "Detection Underrange Threshold")
  field(DTYP, "Bpm Parameters")
  field(OUT,  "#C2S0")
  field(EGU,  "ADC Ticks")
  field(DOL,  "45.26")
  field(PINI, "YES")
  field(DRVL, "0")
  field(DRVH, "32767")
  info(autosaveFields, "VAL")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


# per BPM database for stripline BPMs

######################################
# HEAD of main processing chain
######################################

record(ai, "HL2:SBPM:HL15:X") {
  field(DESC, "X Position")
  field(EGU, "mm")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C2 S11")
  field(SCAN, "I/O Intr")
# The priority determines what scan list we are being
# put on (see drvPadUdpComm.c)
  field(PRIO, "HIGH")
  field(FLNK, "HL2:SBPM:HL15:Y")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
  field(ASG,  "")
  field(TSE, "-2")
  info(autosaveFields, "ASLO LOLO LOW HIGH HIHI HHSV LLSV")
}

record(ai, "HL2:SBPM:HL15:Y") {
  field(DESC, "Y Position")
  field(EGU, "mm")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C2 S12")
  field(FLNK, "HL2:SBPM:HL15:TMIT")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
  field(ASG,  "")
  field(TSE, "-2")
  info(autosaveFields, "ASLO LOLO LOW HIGH HIHI HHSV LLSV")
}

record(ai, "HL2:SBPM:HL15:TMIT") {
  field(DESC, "Charge Estimate")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C2 S13")
  field(EGU, "Nel")
  field(PREC, "3")
  field(LOPR, "0")
  field(HOPR, "1E11")
# FLINK into BSA
  field(FLNK, "HL2:SBPM:HL15:EFX.PROC")
  field(ASG,  "")
  field(TSE, "-2")
  info(autosaveFields, "LOLO LOW HIGH HIHI HHSV LLSV ")
}


######################################
# HEAD of diagnostics processing chain
######################################

# leave RWAV in it's own lockset; don't FLNK
# to 'U' & friends
record(waveform, "HL2:SBPM:HL15:RWAV") {
  field(DESC, "Raw BPM Data")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP,  "#C2 S0")
  field(SCAN, "I/O Intr")
# use LOW or HIGH to end up on the 'diagnostic' 
# scan list (see drvPadUdpComm.c)
  field(PRIO, "LOW")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU,  "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
}

record(ai, "HL2:SBPM:HL15:U") {
  field(DESC, "Raw U Position")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C2 S8")
  field(SCAN, "I/O Intr")
# use LOW or HIGH to end up on the 'diagnostic' 
# scan list (see drvPadUdpComm.c)
  field(PRIO, "LOW")
  field(PREC, "5")
  field(EGU,  "mm")
  field(LOPR, "-0.7")
  field(HOPR, "+0.7")
  field(FLNK, "HL2:SBPM:HL15:V")
}

record(ai, "HL2:SBPM:HL15:V") {
  field(DESC, "Raw V Position")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C2 S9")
  field(SCAN, "Passive")
  field(PREC, "5")
  field(EGU,  "mm")
  field(LOPR, "-0.7")
  field(HOPR, "+0.7")
  field(FLNK, "HL2:SBPM:HL15:PINC")
}

record(ai, "HL2:SBPM:HL15:PINC") {
  field(DESC, "Pin Cushion Corr.")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C2 S10")
  field(SCAN, "Passive")
}

record(longin, "HL2:SBPM:HL15:RSTA") {
  field(DESC, "Status of Raw Processor")
  field(DTYP, "Bpm Raw Status")
  field(INP, "#C2S0")
  field(SCAN, "1 second")
  field(LOLO, "-1")
  field(HIHI, "+1")
  field(HHSV, "INVALID")
  field(LLSV, "INVALID")
  field(FLNK, "HL2:SBPM:HL15:RSTA_ALH")
}


record(calc, "HL2:SBPM:HL15:RSTA_ALH") {
  field(CALC, "A & B")
  field(INPA, "HL2:SBPM:HL15:RSTA")
  field(INPB, "0x30F")
  field(HIHI, "1")
  field(LOLO, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(SCAN, "Passive")
}

######################################
# Input/Parameteres
######################################

record(ao, "HL2:SBPM:HL15:PHI") {
  field(DESC, "Rot Angle")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(EGU, "deg")
  field(PREC, "1")
  field(LOPR, "-180")
  field(HOPR, "+180")
  field(FLNK, "HL2:SBPM:HL15:PHI_SEQ")
}

record(ao, "HL2:SBPM:HL15:PSI") {
  field(DESC, "Axis Sep. Angle")
  field(DTYP, "Soft Channel")
  field(VAL, "90")
  field(EGU, "deg")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "+180")
  field(FLNK, "HL2:SBPM:HL15:PSI_SEQ")
}

#record(dfanout, "HL2:SBPM:HL15:PCMM") {
#  field(DESC, "BPM Scale")
#  field(OUTA, "HL2:SBPM:HL15:USCL PP MS")
#  field(OUTB, "HL2:SBPM:HL15:VSCL PP MS")
#  field(VAL, "12")
#  field(EGU, "mm")
#  field(PREC, "4")
#  field(LOPR, "5")
#  field(HOPR, "15")
#  field(PINI, "YES")
#}

record(ao, "HL2:SBPM:HL15:UOFF") {
  field(DESC, "BPM U Offset")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(EGU, "mm")
  field(PREC, "4")
  field(LOPR, "-5")
  field(HOPR, "+5")
  field(FLNK, "HL2:SBPM:HL15:UOFF_SEQ")
}

record(ao, "HL2:SBPM:HL15:VOFF") {
  field(DESC, "BPM V Offset")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(EGU, "mm")
  field(PREC, "4")
  field(LOPR, "-5")
  field(HOPR, "+5")
  field(FLNK, "HL2:SBPM:HL15:VOFF_SEQ")
}

record(ao, "HL2:SBPM:HL15:USCL") {
  field(DESC, "BPM U Scale")
  field(DTYP, "Soft Channel")
  field(VAL,  "1")
  field(EGU, "mm")
  field(PREC, "4")
  field(FLNK, "HL2:SBPM:HL15:USCL_SEQ")
}

record(ao, "HL2:SBPM:HL15:VSCL") {
  field(DESC, "BPM V Scale")
  field(DTYP, "Soft Channel")
  field(VAL,  "1")
  field(EGU, "mm")
  field(PREC, "4")
  field(FLNK, "HL2:SBPM:HL15:VSCL_SEQ")
}


record(mbbo, "HL2:SBPM:HL15:ACCESS") {
  field(DESC, "BPM On Line")
  field(DTYP, "StreamSwitch")
  field(OUT, "#C2 S0")
  field(ZRVL, "1")
  field(ZRST, "Running")
  field(ZRSV, "NO_ALARM")
  field(ONVL, "1")
  field(ONST, "Maintenance")
  field(ONSV, "MINOR")
  field(TWVL, "1")
  field(TWST, "Test")
  field(TWSV, "MINOR")
  field(THVL, "0")
  field(THST, "OFFLINE")
  field(THSV, "MAJOR")
# set both, rval and val to get it right
# regardless of whether devsup does conversion
# or not.
  field(RVAL, "0")
  field(VAL,  "0")
  field(PINI, "YES")
  field(FLNK, "HL2:SBPM:HL15:SIMOFF")
  info(autosaveFields, "RVAL")
}

#
# Used by higher level software to determine if a PV is in feedback or not.
# May also be used by actuator (magnet and RF) IOC applications to 
# switch output records to "closed_loop" to prevent outside programs from
# changing setpoints when an actuator device is in feedback.
#
record(mbbo, "HL2:SBPM:HL15:FBCK")
{
  field(DESC, "Feedback State")
  field(PINI, "YES")
  field(OMSL, "supervisory")
  field(VAL,  "0")
  field(ZRVL, "0")
  field(ONVL, "1")
  field(TWVL, "2")
# Off - this device can be used in feedback but all feedback loops 
# using it are off.
  field(ZRST, "Off")
# On - this device is being used by one or more feedback loops.
  field(ONST, "On")
# Unavailable - this device is not used by any feedback loop.
  field(TWST, "Unavailable")
  info(autosaveFields, "VAL")
}

# Convenience record holding the MAD name
record(stringin, "HL2:SBPM:HL15:MADN") {
  field(DESC, "MAD Name")
  field(VAL, "SBPMHL15")
  field(PINI, "YES")
}

record(stringin, "SBPMHL15:NAME") {
  field(DESC, "BPM Name")
  field(VAL, "HL2:SBPM:HL15")
  field(PINI, "YES")
}

record(ai, "HL2:SBPM:HL15:X_SLOW") {
#alias("HL2:SBPM:HL15:X1H")
  field(DESC, "X snapshot for display")
  field(EGU, "mm")
  field(INP, "HL2:SBPM:HL15:X MS")
  field(FLNK, "HL2:SBPM:HL15:Y_SLOW")
  field(PREC, "4")
  field(SCAN, "1 second")
  field(LOPR, "-12")
  field(HOPR, "+12")
}

record(ai, "HL2:SBPM:HL15:Y_SLOW") {
#alias("HL2:SBPM:HL15:Y1H")
  field(DESC, "Y snapshot for display")
  field(EGU, "mm")
  field(INP, "HL2:SBPM:HL15:Y NPP MS")
  field(FLNK, "HL2:SBPM:HL15:TMIT_SLOW")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
}

record(ai, "HL2:SBPM:HL15:TMIT_SLOW") {
#alias("HL2:SBPM:HL15:TMIT1H")
  field(DESC, "TMIT snapshot for display")
  field(INP, "HL2:SBPM:HL15:TMIT NPP MS")
  field(EGU, "Nel")
  field(PREC, "3")
  field(LOPR, "0")
  field(HOPR, "1E11")
}

######################################
# Simulation Parameters + Control
######################################

# switch off simulation when going off-line
record(calcout, "HL2:SBPM:HL15:SIMOFF") {
  field(DESC, "Sim Off Propagator")
  field(INPA, "HL2:SBPM:HL15:ACCESS.RVAL")
  field(CALC, "A")
  field(OCAL, "0")
  field(OOPT, "When Zero")
  field(DOPT, "Use OCAL")
  field(OUT,  "HL2:SBPM:HL15:SIMC PP")
}

record(calcout, "HL2:SBPM:HL15:SIM") {
  field(DESC, "BPM Pos. Simulation")
  field(DTYP, "Strip Signal Simulator")
  field(OUT, "2")
#CALC & VAL unused; the real calculation is done
#        in device support. The reason this is a
#        calcout rather than sub is that we want
#        to use the OUT link...
  field(CALC, "A")
  field(INPA, "HL2:SBPM:HL15:USCL")
  field(INPL, "0")
}

# Switch simulation record HL2:SBPM:HL15:SIMCSEQ moved to
# bpmCavity.db.part and bpmStripl.db.part 

record(mbbo, "HL2:SBPM:HL15:SIMC") {
  field(DESC, "Stripl Sim Ctl")
  field(DTYP, "Raw Soft Channel")
  field(OUT,  "HL2:SBPM:HL15:SIMCSEQ.SELN PP")
  field(ZRST, "OFF")
  field(ZRVL, "0x0f")
  field(ONST, "ON")
  field(ONVL, "0x1c0")
  field(TWST, "SOFT")
  field(TWVL, "0x030")
  field(MASK, "-1")
  field(NOBT, "16")
  field(VAL,  "0")
  field(RVAL, "0x0f")
  field(PINI, "YES")
}

record(ao, "HL2:SBPM:HL15:XSIM") {
  field(DESC, "BPM X Pos. Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL15:SIM.B PP")
  field(VAL, "0.5")
  field(EGU, "mm")
  field(PINI, "YES")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
}

record(ao, "HL2:SBPM:HL15:YSIM") {
  field(DESC, "BPM Y Pos. Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL15:SIM.C PP")
  field(VAL, "0.")
  field(EGU, "mm")
  field(PINI, "YES")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
}

record(ao, "HL2:SBPM:HL15:QSIM") {
  field(DESC, "BPM Q Simul.")
  field(DTYP, "Raw Soft Channel")
  field(OUT, "HL2:SBPM:HL15:SIM.D PP")
  field(EGU, "Nel")
  field(ASLO, "6000")
#ESLO is used to add attenuation
  field(LINR, "LINEAR")
  field(VAL, "1E9")
  field(PINI, "YES")
  field(PREC, "4")
  field(LOPR, "0")
  field(HOPR, "1E11")
}

record(ao, "HL2:SBPM:HL15:ROTS") {
  field(DESC, "BPM Rot. Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL15:SIM.E PP")
  field(VAL, "0.")
  field(EGU, "deg")
  field(PINI, "YES")
  field(PREC, "1")
  field(LOPR, "-180")
}

record(ao, "HL2:SBPM:HL15:PSIS") {
  field(DESC, "BPM Angle. Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL15:SIM.F PP")
  field(VAL, "90")
  field(EGU, "deg")
  field(PINI, "YES")
  field(PREC, "1")
  field(LOPR, "0")
}

record(aao, "HL2:SBPM:HL15:DIGISIMW") {
  field(DESC, "VME Digi Sim. Waveform")
  field(DTYP, "VmeDigi Sim Wav")
  field(OUT,  "#C2 S0")
  field(FTVL, "SHORT")
  field(EGU,  "Counts")
  field(HOPR, "32678")
  field(LOPR, "-32768")
# 16384 samples/channel * 4 channels
  field(NELM, "65536")
  field(PINI, "NO")
}

#Used by model/database folks to verify BPM

record(ao, "HL2:SBPM:HL15:Z") {
  field(DESC, "Z Position")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

# MPS interface
record(bo, "HL2:SBPM:HL15:MPSBYP") {
  field(DESC, "MPS Bypass")
  field(DTYP, "BusAddress")
  field(OUT,  "#C0S2@bpmMPS+0,m32")
  field(MASK, "4")
  field(ZNAM, "BYPASSED")
  field(ONAM, "NOT_BYPASSED")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(VAL,  "0")
  field(PINI, "YES")
  field(ASG,  "")
  info(autosaveFields, "VAL")
}

record(bo, "HL2:SBPM:HL15:MPSLTBYP") {
  field(DESC, "MPS Bypass")
  field(DTYP, "BusAddress")
  field(OUT,  "#C1S2@bpmMPS+0,m32")
  field(MASK, "4")
  field(ZNAM, "BYPASSED")
  field(ONAM, "NOT_BYPASSED")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")
  field(VAL,  "0")
  field(PINI, "YES")
  field(ASG,  "")
  info(autosaveFields, "VAL")
}

record(calc, "HL2:SBPM:HL15:MPSIGNRCALC") {
  field(DESC, "MPS ignore if TMIT too low")
  field(CALC, "A<B")
  field(INPA, "HL2:SBPM:HL15:TMIT")
  field(INPB, "HL2:SBPM:HL15:T_MPS_THRES_L")
  field(HIHI, "1")
  field(HHSV, "MAJOR")
  field(ASG, "")
}

record(bi, "HL2:SBPM:HL15:MPSIGNORE") {
  field(DESC, "MPS ignore if TMIT too low")
  field(DTYP, "Raw Soft Channel")
  field(SCAN, "1 second")
  field(INP, "HL2:SBPM:HL15:MPSIGNRCALC PP")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "Not ignored")
  field(ONAM, "Ignored")
  field(PINI, "YES")
  field(ASG, "")
}

# Proxy records for users to set X.AOFF, Y.AOFF
# Placed CAS on X and Y for MPS 
# Feb 2010 - CAS has since been removed, but we'll keep 
# these proxy records as they're already in use

record(ao, "HL2:SBPM:HL15:XAOFF") {
  field(DESC, "X.AOFF val")
#  field(OUT, "HL2:SBPM:HL15:X.AOFF")
  field(PINI, "YES")
  field(EGU, "mm")
  field(PREC, "4")
  field(FLNK, "HL2:SBPM:HL15:XOFF")
  info(autosaveFields, "VAL")
}

record(ao, "HL2:SBPM:HL15:YAOFF") {
  field(DESC, "Y.AOFF val")
#  field(OUT, "HL2:SBPM:HL15:Y.AOFF")
  field(PINI, "YES")
  field(EGU, "mm")
  field(PREC, "4")
  field(FLNK, "HL2:SBPM:HL15:YOFF")
  info(autosaveFields, "VAL")
}

# Add CALC to allow users to maintain
# multiple offsets per plane per BPM

record(calcout, "HL2:SBPM:HL15:XOFF") {
  field(DESC, "Add X offsets")
  field(PREC, "4")
  field(CALC, "A+B+C+D")
  field(INPA, "HL2:SBPM:HL15:XAOFF")
# B-E reserved for undulator offsets
  field(INPB, "")
  field(INPC, "")
  field(INPD, "")
  field(INPE, "")
  field(EGU, "mm")
  field(OUT, "HL2:SBPM:HL15:X.AOFF")
  info(autosaveFields, "B C D E")
}

record(calcout, "HL2:SBPM:HL15:YOFF") {
  field(DESC, "Add Y offsets")
  field(PREC, "4")
  field(CALC, "A+B+C+D")
  field(INPA, "HL2:SBPM:HL15:YAOFF")
# B-E reserved for undulator offsets
  field(INPB, "")
  field(INPC, "")
  field(INPD, "")
  field(INPE, "")
  field(EGU, "mm")
  field(OUT, "HL2:SBPM:HL15:Y.AOFF")
  info(autosaveFields, "B C D E")
}


# Records to set MPS thresholds
record(ao, "HL2:SBPM:HL15:X_MPS_THRES_L") {
  field(DESC, "MPS X Threshold Lo")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C2 S0 @Lo")
  field(VAL,  "-1")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL2:SBPM:HL15:X_MPS_THRES_H") {
  field(DESC, "MPS X Threshold Hi")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C2 S0 @Hi")
  field(VAL,  "1")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL2:SBPM:HL15:Y_MPS_THRES_L") {
  field(DESC, "MPS Y Threshold Lo")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C2 S1 @Lo")
  field(VAL,  "-1")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL2:SBPM:HL15:Y_MPS_THRES_H") {
  field(DESC, "MPS Y Threshold Hi")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C2 S1 @Hi")
  field(VAL,  "1")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL2:SBPM:HL15:T_MPS_THRES_L") {
  field(DESC, "MPS TMIT Threshold Lo")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C2 S2 @Lo")
  field(VAL,  "9.375e7")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL2:SBPM:HL15:T_MPS_THRES_H") {
  field(DESC, "MPS TMIT Threshold Hi")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C2 S2 @Hi")
  field(VAL,  "+1.0E20")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}

record(bi, "HL2:SBPM:HL15:FNET") {
  field(DESC, "BPM data on FNET")
  field(VAL, "$(FN,undefined)")
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(PINI, "YES")
}

# Record to inform users that BPM
# needs TMIT and/or X/Y scale calibration
record(mbbo, "HL2:SBPM:HL15:CHK") {
  field(DESC, "Needs cal/iron")
  field(OMSL, "supervisory")
  field(VAL,  "0")
  field(ZRVL, "0")
  field(ONVL, "1")
  field(TWVL, "2")
  field(THVL, "3")
  field(ZRST, " ")
  field(ONST, "Calibrate")
  field(TWST, "Calibrate&iron")
  field(THST, "Iron")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MINOR")
  field(THSV, "MINOR")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

# Switch simulation record 
record(seq, "HL2:SBPM:HL15:SIMCSEQ") {
  field(DESC, "BPM Sim Ctl Seq")
  field(SELM, "Mask")
  field(SELN, "0")

  field(DO1,  "1")
  field(DO2,  "0")
  field(DO3,  "0")
  field(DO4,  "0") #Passive

#  field(DO5,  "7") # .5 second
  field(DO5,  "9") # .1 second
  field(DO6,  "2")
  field(DO7,  "1")
  field(DO8,  "10")
  field(DO9,  "0")

# LNK 1, 2, 8, 9 only relevant for PADs
# Default macro values are set for PADs; other
# architectures must pass in "" for lnk1 and lnk2
  field(LNK1, "")
  field(LNK2, "")
  field(LNK3, "HL2:SBPM:HL15:SIM.L     PP")
  field(LNK4, "HL2:SBPM:HL15:SIM.SCAN  PP")

  field(LNK5, "HL2:SBPM:HL15:SIM.SCAN  PP")
  field(LNK6, "HL2:SBPM:HL15:SIM.L     PP")
  field(LNK7, "HL2:SBPM:HL15:SIM.L     PP")
  field(LNK8, "")
  field(LNK9, "")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL15:UOFF_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL15:UOFF")
	field(DOL2, "HL2:SBPM:HL15:UOFF")
	field(DOL3, "HL2:SBPM:HL15:UOFF")
	field(DOL4, "HL2:SBPM:HL15:UOFF")
	field(DOL5, "HL2:SBPM:HL15:UOFF")
	field(DOL6, "HL2:SBPM:HL15:UOFF")
	field(DOL7, "HL2:SBPM:HL15:UOFF")
	field(DOL8, "HL2:SBPM:HL15:UOFF")
	field(DOL9, "HL2:SBPM:HL15:UOFF")
	field(DOLA, "HL2:SBPM:HL15:UOFF")
	field(LNK1, "HL2:SBPM:HL15:UOFF_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL15:UOFF_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL15:UOFF_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL15:UOFF_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL15:UOFF_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL15:UOFF_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL15:UOFF_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL15:UOFF_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL15:UOFF_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL15:UOFF_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL15:UOFF_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL15:UOFF_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "0")
	field(B,    "0")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "4")
	field(FLNK, "HL2:SBPM:HL15:UOFF_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL15:UOFF_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL15:UOFF_SEL")
	field(OUTA, "HL2:SBPM:HL15:U.AOFF CA")
	field(OUTB, "HL2:SBPM:HL15:UOFF PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL15:UOFF_CTRL")
{
	field(INPA, "HL2:SBPM:HL15:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL15:UOFF_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL15:VOFF_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL15:VOFF")
	field(DOL2, "HL2:SBPM:HL15:VOFF")
	field(DOL3, "HL2:SBPM:HL15:VOFF")
	field(DOL4, "HL2:SBPM:HL15:VOFF")
	field(DOL5, "HL2:SBPM:HL15:VOFF")
	field(DOL6, "HL2:SBPM:HL15:VOFF")
	field(DOL7, "HL2:SBPM:HL15:VOFF")
	field(DOL8, "HL2:SBPM:HL15:VOFF")
	field(DOL9, "HL2:SBPM:HL15:VOFF")
	field(DOLA, "HL2:SBPM:HL15:VOFF")
	field(LNK1, "HL2:SBPM:HL15:VOFF_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL15:VOFF_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL15:VOFF_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL15:VOFF_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL15:VOFF_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL15:VOFF_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL15:VOFF_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL15:VOFF_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL15:VOFF_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL15:VOFF_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL15:VOFF_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL15:VOFF_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "0")
	field(B,    "0")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "4")
	field(FLNK, "HL2:SBPM:HL15:VOFF_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL15:VOFF_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL15:VOFF_SEL")
	field(OUTA, "HL2:SBPM:HL15:V.AOFF CA")
	field(OUTB, "HL2:SBPM:HL15:VOFF PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL15:VOFF_CTRL")
{
	field(INPA, "HL2:SBPM:HL15:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL15:VOFF_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL15:USCL_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL15:USCL")
	field(DOL2, "HL2:SBPM:HL15:USCL")
	field(DOL3, "HL2:SBPM:HL15:USCL")
	field(DOL4, "HL2:SBPM:HL15:USCL")
	field(DOL5, "HL2:SBPM:HL15:USCL")
	field(DOL6, "HL2:SBPM:HL15:USCL")
	field(DOL7, "HL2:SBPM:HL15:USCL")
	field(DOL8, "HL2:SBPM:HL15:USCL")
	field(DOL9, "HL2:SBPM:HL15:USCL")
	field(DOLA, "HL2:SBPM:HL15:USCL")
	field(LNK1, "HL2:SBPM:HL15:USCL_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL15:USCL_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL15:USCL_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL15:USCL_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL15:USCL_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL15:USCL_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL15:USCL_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL15:USCL_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL15:USCL_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL15:USCL_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL15:USCL_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL15:USCL_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "1")
	field(B,    "1")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "4")
	field(FLNK, "HL2:SBPM:HL15:USCL_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL15:USCL_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL15:USCL_SEL")
	field(OUTA, "HL2:SBPM:HL15:U.ASLO CA")
	field(OUTB, "HL2:SBPM:HL15:USCL PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL15:USCL_CTRL")
{
	field(INPA, "HL2:SBPM:HL15:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL15:USCL_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL15:VSCL_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL15:VSCL")
	field(DOL2, "HL2:SBPM:HL15:VSCL")
	field(DOL3, "HL2:SBPM:HL15:VSCL")
	field(DOL4, "HL2:SBPM:HL15:VSCL")
	field(DOL5, "HL2:SBPM:HL15:VSCL")
	field(DOL6, "HL2:SBPM:HL15:VSCL")
	field(DOL7, "HL2:SBPM:HL15:VSCL")
	field(DOL8, "HL2:SBPM:HL15:VSCL")
	field(DOL9, "HL2:SBPM:HL15:VSCL")
	field(DOLA, "HL2:SBPM:HL15:VSCL")
	field(LNK1, "HL2:SBPM:HL15:VSCL_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL15:VSCL_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL15:VSCL_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL15:VSCL_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL15:VSCL_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL15:VSCL_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL15:VSCL_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL15:VSCL_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL15:VSCL_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL15:VSCL_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL15:VSCL_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL15:VSCL_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "1")
	field(B,    "1")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "4")
	field(FLNK, "HL2:SBPM:HL15:VSCL_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL15:VSCL_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL15:VSCL_SEL")
	field(OUTA, "HL2:SBPM:HL15:V.ASLO CA")
	field(OUTB, "HL2:SBPM:HL15:VSCL PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL15:VSCL_CTRL")
{
	field(INPA, "HL2:SBPM:HL15:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL15:VSCL_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL15:PHI_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL15:PHI")
	field(DOL2, "HL2:SBPM:HL15:PHI")
	field(DOL3, "HL2:SBPM:HL15:PHI")
	field(DOL4, "HL2:SBPM:HL15:PHI")
	field(DOL5, "HL2:SBPM:HL15:PHI")
	field(DOL6, "HL2:SBPM:HL15:PHI")
	field(DOL7, "HL2:SBPM:HL15:PHI")
	field(DOL8, "HL2:SBPM:HL15:PHI")
	field(DOL9, "HL2:SBPM:HL15:PHI")
	field(DOLA, "HL2:SBPM:HL15:PHI")
	field(LNK1, "HL2:SBPM:HL15:PHI_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL15:PHI_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL15:PHI_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL15:PHI_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL15:PHI_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL15:PHI_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL15:PHI_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL15:PHI_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL15:PHI_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL15:PHI_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL15:PHI_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL15:PHI_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "0")
	field(B,    "0")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "1")
	field(FLNK, "HL2:SBPM:HL15:PHI_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL15:PHI_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL15:PHI_SEL")
	field(OUTA, "HL2:SBPM:HL15:CALC.E CA")
	field(OUTB, "HL2:SBPM:HL15:PHI PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL15:PHI_CTRL")
{
	field(INPA, "HL2:SBPM:HL15:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL15:PHI_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL15:PSI_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL15:PSI")
	field(DOL2, "HL2:SBPM:HL15:PSI")
	field(DOL3, "HL2:SBPM:HL15:PSI")
	field(DOL4, "HL2:SBPM:HL15:PSI")
	field(DOL5, "HL2:SBPM:HL15:PSI")
	field(DOL6, "HL2:SBPM:HL15:PSI")
	field(DOL7, "HL2:SBPM:HL15:PSI")
	field(DOL8, "HL2:SBPM:HL15:PSI")
	field(DOL9, "HL2:SBPM:HL15:PSI")
	field(DOLA, "HL2:SBPM:HL15:PSI")
	field(LNK1, "HL2:SBPM:HL15:PSI_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL15:PSI_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL15:PSI_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL15:PSI_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL15:PSI_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL15:PSI_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL15:PSI_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL15:PSI_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL15:PSI_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL15:PSI_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL15:PSI_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL15:PSI_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "90")
	field(B,    "90")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "1")
	field(FLNK, "HL2:SBPM:HL15:PSI_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL15:PSI_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL15:PSI_SEL")
	field(OUTA, "HL2:SBPM:HL15:CALC.F CA")
	field(OUTB, "HL2:SBPM:HL15:PSI PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL15:PSI_CTRL")
{
	field(INPA, "HL2:SBPM:HL15:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL15:PSI_SEL.L PP")
}
record(longout, "HL2:SBPM:HL15:PARMSEL") {
	field(VAL, "0")
	field(PINI, "YES")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


# per BPM database for stripline BPMs

##############################################
# This is the head of the main processing chain
# that runs at the highest priority.
##############################################

#############################################
# This is the head of the processing chain for
# diagnostics.
##############################################
record(ai, "HL2:SBPM:HL16:GRN") {
  field(DESC, "GRN Strip Amplitude")
  field(DTYP, "Raw Bpm Signal")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "#C3 S0")
  field(EGU, "raw")
#TODO set HOPR/LOPR, alarm limits
  field(SCAN, "I/O Intr")
# The priority determines what scan list we are being
# put on (see drvPadUdpComm.c)
  field(PRIO, "LOW")
  field(FLNK, "HL2:SBPM:HL16:RED")
# HOPR for the energy algorithm is determined as follows:
#
#                      inf        inf
#  1) Fourier relation / h^2 dt = / |H|^2 df = 2 B
#                     0         -inf
#
#  1a) It can be shown that the maximum of the impuls response
#      ha is ~ 2 B
#                               
#  2) The digitizer produces the numbers
#
#     Ai = 2^s (hi/ha)
#
#     where ha is the maximum of the impuls response
#     and 2^s is a scale factor.
#     
#  3) 'Energy algorithm' calculates S = sum( Ai^2 )
#
#                                                     inf
#  4) S = (2^s / ha)^2 sum(hi^2) = K sum(hi^2) Dt ~ K / h^2 dt
#                                                    0
#
#     with K = (2^s / ha)^2 fs
#
#  5) From 4) and 1a) ->  S ~ K ha and therefore
#
#  6) S = 2^(2s) fs/ha = 2^(2s) fs/(2 B)
#
#  7) The strip signals are sqrt(S); hence HOPR is about
#
#     HOPR ~ 2^s  sqrt( fs/2/B )
#
#     with 2^s = 32768, fs=120MHz, B=10MHz it follows
#     that HOPR ~ 1E5; we add some margin...
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL16:RED") {
  field(DESC, "RED Strip Amplitude")
  field(DTYP, "Raw Bpm Signal")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "#C3 S1")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(FLNK, "HL2:SBPM:HL16:BLU")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL16:BLU") {
  field(DESC, "BLU Strip Amplitude")
  field(DTYP, "Raw Bpm Signal")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "#C3 S2")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(FLNK, "HL2:SBPM:HL16:YLO")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL16:YLO") {
  field(DESC, "YLO Strip Amplitude")
  field(DTYP, "Raw Bpm Signal")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "#C3 S3")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

##############################################
# Slowly-scanned diagnostics
##############################################

#
record(waveform, "HL2:SBPM:HL16:REDW") {
  field(DESC, "Raw CAL RED Data")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP, "#C3 S1")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "1 second")
}

record(waveform, "HL2:SBPM:HL16:GRNW") {
  field(DESC, "Raw CAL GRN Data")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP, "#C3 S2")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "1 second")
}

record(waveform, "HL2:SBPM:HL16:RAWDBG") {
  field(DESC, "Raw BEAM Dbg")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
# do not 'wbscan' for now since e.g., an underrange
# condition on the real signal can happen.
  field(INP, "#C3 S7")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "Passive")
}

record(waveform, "HL2:SBPM:HL16:REDDBG") {
  field(DESC, "Raw CAL RED Dbg")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP, "#C3 S8 @wbscan")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "Passive")
}

record(waveform, "HL2:SBPM:HL16:GRNDBG") {
  field(DESC, "Raw CAL GRN Dbg")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP, "#C3 S9 @wbscan")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "Passive")
}

record(ai, "HL2:SBPM:HL16:GRUV") {
  field(DESC, "CAL Gain GRN/RED")
  field(DTYP, "Raw Stripl Calp")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C3 S0")
  field(SCAN, "10 second")
  field(PREC, "4")
  field(LOPR, "0.5")
  field(HOPR, "1.5")
}

record(ai, "HL2:SBPM:HL16:GRU") {
  field(DESC, "CAL Gain GRN/BLU")
  field(DTYP, "Raw Stripl Calp")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C3 S1")
  field(SCAN, "10 second")
  field(PREC, "4")
  field(LOPR, "0.5")
  field(HOPR, "1.5")
  info(autosaveFields, "ASLO")
}

record(ai, "HL2:SBPM:HL16:GRV") {
  field(DESC, "CAL Gain RED/YLO")
  field(DTYP, "Raw Stripl Calp")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C3 S2")
  field(SCAN, "10 second")
  field(PREC, "4")
  field(LOPR, "0.5")
  field(HOPR, "1.5")
  info(autosaveFields, "ASLO")
}

record(ai, "HL2:SBPM:HL16:TGRN") {
  field(DESC, "Green arrival time")
  field(DTYP, "Raw Bpm Signal")
  field(EGU, "ADC Clocks")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C3 S4")
  field(SCAN, "10 second")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "128")
  field(LOLO, "5")
  field(LOW, "8")
  field(HIGH, "60")
  field(HIHI, "70")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
  field(HSV, "MINOR")
  field(HHSV, "MAJOR")
}

record(ai, "HL2:SBPM:HL16:TRED") {
  field(DESC, "Red arrival time")
  field(DTYP, "Raw Bpm Signal")
  field(EGU, "ADC Clocks")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C3 S5")
  field(SCAN, "10 second")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "128")
  field(LOLO, "5")
  field(LOW, "8")
  field(HIGH, "60")
  field(HIHI, "70")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
  field(HSV, "MINOR")
  field(HHSV, "MAJOR")
}

record(ai, "HL2:SBPM:HL16:TBLU") {
  field(DESC, "Blue arrival time")
  field(DTYP, "Raw Bpm Signal")
  field(EGU, "ADC Clocks")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C3 S6")
  field(SCAN, "10 second")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "128")
  field(LOLO, "5")
  field(LOW, "8")
  field(HIGH, "60")
  field(HIHI, "70")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
  field(HSV, "MINOR")
  field(HHSV, "MAJOR")
}

record(ai, "HL2:SBPM:HL16:TYLO") {
  field(DESC, "Yellow arrival time")
  field(DTYP, "Raw Bpm Signal")
  field(EGU, "ADC Clocks")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C3 S7")
  field(SCAN, "10 second")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "128")
  field(LOLO, "5")
  field(LOW, "8")
  field(HIGH, "60")
  field(HIHI, "70")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
  field(HSV, "MINOR")
  field(HHSV, "MAJOR")
}

record(ao, "HL2:SBPM:HL16:PINC_ADJ") {
  field(DESC, "Adjust Pinc. Corr.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL16:CALC.K PP MS")
  field(VAL, "0")
  field(DRVL, "0")
  field(DRVH, "2")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

# QSCL setting:
#
# Q: charge
# Z: impedance
# F: form factor: phi/(2 pi) sin(2 pi f l/c)
#
# Signal =  Q Z F G h(t) = A h(t)  [A] = Vs
#
#                  inf              inf
# Energy =  A^2   / h^2(t) dt = A^2 / |H(w)|^2 dw/2/pi = A^2 B
#                0                 0
#                        
# Measured energy = Sum{ (Vp/32768 * xi)^2 } / fs = S / fs ~ Energy
#
# -> A^2 B = S/fs
#
# With T = sqrt( Sum{ xi^2 } )
#
#    A = sqrt(S)/sqrt(B*fs) = T/sqrt(B*fs) Vp/32768
#
#                      T/32768 Vp
#    Q = A/F/G/Z = -----------------
#                   F G Z sqrt(B*fs)
#
# Vp = { 1.5Vpp/2 (PGA=1) or 2.25Vpp/2 (PGA=0) } / 2 (transformer)
#
# I believe PGA is off (-> Vp ~ .56V)
#
# Z  = 50
#
# G: (calibration uses GRN/BLU -> signal should have the
#    level of the grn/red channels with the additional switch)
#
# Block diagram / parts / gain:
#
# [filt]    [Att1]    [Amp1]   [Att2]    [BPF]      [Amp2]    [pad] [Amp3]   [switch]
# f-17520  hmc540lp3  SBF-5089 hmc540lp3 MBP-140-6-4 SBF-4089  PAT-0 SBF-4089 HMC-197
#
#  -2dB*    -1dB       20dB     -1dB     -4.5         14.8dB   0dB   14.8dB   -0.4dB
#
# *: 1st filter ATT is a wild guess.
#  BPF loss (RLC Catalog, pp.55): (L (nsect+.5) / (% of 3dB BW) + .2) dB
#  with L ~6.2  10MHz/fc=140Mhz filter-> 4.5
#
#  -> Gtot ~ 40.7dB
#
#  subtract cable loss (2dB); Gtot = 86
# 
#                      T/32768 Vp            .56V/32768
#    Q = A/F/G/Z = ----------------- = T/F  ------------------------
#                   F G Z sqrt(B*fs)        86*50*sqrt(10*140)Mhz
#
#      = T/F = 1.06E-7/F nC
#
#    F for a 7% coverage, 4" BPM at 140MHz   .07 sin(2*pi*140e6 4*.0254/3e8)
#      = .021
#
#      => 1.06E-7/.021 nC = 5E-6 nC
#
# (Faraday cup measurement -> (3600/44)^-1 1e-4 -> 1.22E-6
#
record(ao, "HL2:SBPM:HL16:QSCL") {
  field(DESC, "TMIT/Charge Scale")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL16:QSCA.A PP MS")
# 5.0E-6 / 1.6E-10 [nC/e-]
  field(VAL, "31250")
  field(EGU, "Nel")
  field(PREC, "3")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

# Adjust TMIT scale for AFE attenuation
record(calcout, "HL2:SBPM:HL16:QSCA") {
  field(DESC, "TMIT ATT Adj. Scale")
  field(INPB, "HL2:SBPM:HL16:ATT1 CP")
  field(INPC, "HL2:SBPM:HL16:ATT2 CP")
  field(CALC, "A*10^((B+C+D)/20)")
# use CA link to deposit into TMIT.ASLO so
# that TMIT is not forced into linkset
# of this record
  field(OUT, "HL2:SBPM:HL16:TMIT.ASLO CA")
  field(EGU, "Nel")
  field(PREC, "3")
  info(autosaveFields, "D")
}

record(ao,    "HL2:SBPM:HL16:ATT1SIMP") {
	field(DESC, "ATT1 Propagator")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL2:SBPM:HL16:ATT1   CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL2:SBPM:HL16:ASIM.A PP")
  	field(IVOA, "Set output to IVOV")
	field(IVOV, "0")
	field(EGU,  "dB")
}

record(ao,    "HL2:SBPM:HL16:ATT2SIMP") {
	field(DESC, "ATT2 Propagator")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL2:SBPM:HL16:ATT2   CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL2:SBPM:HL16:ASIM.C PP")
  	field(IVOA, "Set output to IVOV")
	field(IVOV, "0")
	field(EGU,  "dB")
}

# Attenuate charge either by
# real attenuator settings or
# by fake ones.
# If B, C >= 0 then their
# values will be used instead
# of ATT1, ATT2
record(calcout, "HL2:SBPM:HL16:ASIM") {
  field(DESC, "Q Simul Attenuator")
  field(DTYP, "Soft Channel")
  field(OUT,  "HL2:SBPM:HL16:QSIM.ESLO PP")
# ATT1SIM puts value into A
# set to -1 to use real attenuator settings
# and >=0 to use B instead
  field(B,    "-1")
# ATT2SIM puts value into C
# set to -1 to use real attenuator settings
# and >=0 to use D instead
  field(D,    "-1")
  field(CALC, "10^(((B>=0?B:A)+(D>=0?D:C))/20)")
  field(PINI, "YES")
}

record(ao, "HL2:SBPM:HL16:WSIM") {
  field(DESC, "BPM W Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL16:SIM.G PP")
  field(VAL, "0.07")
  field(EGU, "%")
  field(PINI, "YES")
  field(PREC, "3")
  field(LOPR, "0")
  field(HOPR, "0.25")
}


record(sel, "HL2:SBPM:HL16:STA") {
  field(DESC, "Status Summary")
  field(SELM, "High Signal")
  field(INPA, "HL2:SBPM:HL16:RSTA.SEVR MS NPP")
  field(INPB, "HL2:SBPM:HL16:TMIT.SEVR MS NPP")
  field(INPC, "HL2:SBPM:HL16:Y.SEVR    MS NPP")
  field(INPD, "HL2:SBPM:HL16:X.SEVR    MS NPP")
  field(INPE, "HL2:SBPM:HL16:TGRN.SEVR MS NPP")
  field(INPF, "HL2:SBPM:HL16:TRED.SEVR MS NPP")
  field(INPG, "HL2:SBPM:HL16:TBLU.SEVR MS NPP")
  field(INPH, "HL2:SBPM:HL16:TYLO.SEVR MS NPP")
  field(INPI, "HL2:SBPM:HL16:GRU.SEVR  MS NPP")
  field(INPJ, "HL2:SBPM:HL16:GRV.SEVR  MS NPP")
  field(SCAN, "1 second")
}

# This record really belongs on the
# PAD IOC. We keep them here however
# so we can save/restore. It is more
# confusing but shouldn't matter from
# an efficiency standpoint (they are
# rarely changed).
record(longout, "HL2:SBPM:HL16:ATTO") {
  field(DESC, "AFE Tot. Att. Offset")
# fetched via inlink
#field(OUT,  "HL2:SBPM:HL16:ATTC.B PP")
  field(DRVL, "-10")
  field(DRVH, "30")
  field(LOPR, "-10")
  field(HOPR, "30")
  field(EGU, "dB")
  field(VAL, "0")
  field(PINI, "YES")
  info(autosaveFields, "VAL DRVH HOPR DRVL LOPR")
}

# This record really belongs on the
# PAD IOC. We keep them here however
# so we can save/restore. It is more
# confusing but shouldn't matter from
# an efficiency standpoint (they are
# rarely changed).
record(longout, "HL2:SBPM:HL16:CLAO") {
  field(DESC, "AFE Cal. Att. Offset")
# fetched via inlink
#field(OUT,  "HL2:SBPM:HL16:ATTC.C PP")
  field(DRVL, "-20")
  field(DRVH, "20")
  field(LOPR, "-20")
  field(HOPR, "20")
  field(EGU, "dB")
  field(VAL, "40")
  field(PINI, "YES")
  info(autosaveFields, "VAL DRVH HOPR DRVL LOPR")
}

record(calc, "HL2:SBPM:HL16:STA_ALH") {
  field(DESC, "Status Summary")
  field(SCAN, "1 second")
  field(CALC, "0")
  field(INPA, "HL2:SBPM:HL16:RSTA_ALH.SEVR MS NPP")
  field(INPB, "HL2:SBPM:HL16:GRU.SEVR  MS NPP")
  field(INPC, "HL2:SBPM:HL16:GRV.SEVR  MS NPP")
  field(INPD, "HL2:SBPM:HL16:CHK.SEVR MS NPP")
}

# snapshot PV for the bpm values display
record(ai, "HL2:SBPM:HL16:GRN_SLOW") {
  field(DESC, "GRN snapshot for display")
  field(INP, "HL2:SBPM:HL16:GRN NPP MS")
  field(EGU, "raw")
  field(SCAN, "1 second")
  field(FLNK, "HL2:SBPM:HL16:RED_SLOW")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL16:RED_SLOW") {
  field(DESC, "RED snapshot for display")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "HL2:SBPM:HL16:RED NPP MS")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(FLNK, "HL2:SBPM:HL16:BLU_SLOW")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL16:BLU_SLOW") {
  field(DESC, "BLU snapshot for display")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "HL2:SBPM:HL16:BLU NPP MS")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(FLNK, "HL2:SBPM:HL16:YLO_SLOW")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL16:YLO_SLOW") {
  field(DESC, "YLO snapshot for display")
  field(INP, "HL2:SBPM:HL16:YLO NPP MS")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(sub, "HL2:SBPM:HL16:CALC") {
  field(SNAM, "drvBpmBvectSetupSub")
# E: phi F: psi
# BPM channel number in L
  field(INPL, "3")
  field(SCAN, "Passive")
}

record(bo, "HL2:SBPM:HL16:PINC_ENA") {
  field(DESC, "Simple Pincushion Alg")
  field(DTYP, "BusAddress")
  field(OUT,  "#C0S2@drvBpmStriplPincEna,m32")
  field(MASK, "8")
  field(ZNAM, "DISABLED")
  field(ONAM, "ENABLED")
  field(VAL,  "0")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

record(ao, "HL2:SBPM:HL16:UDR_THRES") {
  field(DESC, "Detection Underrange Threshold")
  field(DTYP, "Bpm Parameters")
  field(OUT,  "#C3S0")
  field(EGU,  "ADC Ticks")
  field(DOL,  "45.26")
  field(PINI, "YES")
  field(DRVL, "0")
  field(DRVH, "32767")
  info(autosaveFields, "VAL")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


# per BPM database for stripline BPMs

######################################
# HEAD of main processing chain
######################################

record(ai, "HL2:SBPM:HL16:X") {
  field(DESC, "X Position")
  field(EGU, "mm")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C3 S11")
  field(SCAN, "I/O Intr")
# The priority determines what scan list we are being
# put on (see drvPadUdpComm.c)
  field(PRIO, "HIGH")
  field(FLNK, "HL2:SBPM:HL16:Y")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
  field(ASG,  "")
  field(TSE, "-2")
  info(autosaveFields, "ASLO LOLO LOW HIGH HIHI HHSV LLSV")
}

record(ai, "HL2:SBPM:HL16:Y") {
  field(DESC, "Y Position")
  field(EGU, "mm")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C3 S12")
  field(FLNK, "HL2:SBPM:HL16:TMIT")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
  field(ASG,  "")
  field(TSE, "-2")
  info(autosaveFields, "ASLO LOLO LOW HIGH HIHI HHSV LLSV")
}

record(ai, "HL2:SBPM:HL16:TMIT") {
  field(DESC, "Charge Estimate")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C3 S13")
  field(EGU, "Nel")
  field(PREC, "3")
  field(LOPR, "0")
  field(HOPR, "1E11")
# FLINK into BSA
  field(FLNK, "HL2:SBPM:HL16:EFX.PROC")
  field(ASG,  "")
  field(TSE, "-2")
  info(autosaveFields, "LOLO LOW HIGH HIHI HHSV LLSV ")
}


######################################
# HEAD of diagnostics processing chain
######################################

# leave RWAV in it's own lockset; don't FLNK
# to 'U' & friends
record(waveform, "HL2:SBPM:HL16:RWAV") {
  field(DESC, "Raw BPM Data")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP,  "#C3 S0")
  field(SCAN, "I/O Intr")
# use LOW or HIGH to end up on the 'diagnostic' 
# scan list (see drvPadUdpComm.c)
  field(PRIO, "LOW")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU,  "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
}

record(ai, "HL2:SBPM:HL16:U") {
  field(DESC, "Raw U Position")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C3 S8")
  field(SCAN, "I/O Intr")
# use LOW or HIGH to end up on the 'diagnostic' 
# scan list (see drvPadUdpComm.c)
  field(PRIO, "LOW")
  field(PREC, "5")
  field(EGU,  "mm")
  field(LOPR, "-0.7")
  field(HOPR, "+0.7")
  field(FLNK, "HL2:SBPM:HL16:V")
}

record(ai, "HL2:SBPM:HL16:V") {
  field(DESC, "Raw V Position")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C3 S9")
  field(SCAN, "Passive")
  field(PREC, "5")
  field(EGU,  "mm")
  field(LOPR, "-0.7")
  field(HOPR, "+0.7")
  field(FLNK, "HL2:SBPM:HL16:PINC")
}

record(ai, "HL2:SBPM:HL16:PINC") {
  field(DESC, "Pin Cushion Corr.")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C3 S10")
  field(SCAN, "Passive")
}

record(longin, "HL2:SBPM:HL16:RSTA") {
  field(DESC, "Status of Raw Processor")
  field(DTYP, "Bpm Raw Status")
  field(INP, "#C3S0")
  field(SCAN, "1 second")
  field(LOLO, "-1")
  field(HIHI, "+1")
  field(HHSV, "INVALID")
  field(LLSV, "INVALID")
  field(FLNK, "HL2:SBPM:HL16:RSTA_ALH")
}


record(calc, "HL2:SBPM:HL16:RSTA_ALH") {
  field(CALC, "A & B")
  field(INPA, "HL2:SBPM:HL16:RSTA")
  field(INPB, "0x30F")
  field(HIHI, "1")
  field(LOLO, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(SCAN, "Passive")
}

######################################
# Input/Parameteres
######################################

record(ao, "HL2:SBPM:HL16:PHI") {
  field(DESC, "Rot Angle")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(EGU, "deg")
  field(PREC, "1")
  field(LOPR, "-180")
  field(HOPR, "+180")
  field(FLNK, "HL2:SBPM:HL16:PHI_SEQ")
}

record(ao, "HL2:SBPM:HL16:PSI") {
  field(DESC, "Axis Sep. Angle")
  field(DTYP, "Soft Channel")
  field(VAL, "90")
  field(EGU, "deg")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "+180")
  field(FLNK, "HL2:SBPM:HL16:PSI_SEQ")
}

#record(dfanout, "HL2:SBPM:HL16:PCMM") {
#  field(DESC, "BPM Scale")
#  field(OUTA, "HL2:SBPM:HL16:USCL PP MS")
#  field(OUTB, "HL2:SBPM:HL16:VSCL PP MS")
#  field(VAL, "12")
#  field(EGU, "mm")
#  field(PREC, "4")
#  field(LOPR, "5")
#  field(HOPR, "15")
#  field(PINI, "YES")
#}

record(ao, "HL2:SBPM:HL16:UOFF") {
  field(DESC, "BPM U Offset")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(EGU, "mm")
  field(PREC, "4")
  field(LOPR, "-5")
  field(HOPR, "+5")
  field(FLNK, "HL2:SBPM:HL16:UOFF_SEQ")
}

record(ao, "HL2:SBPM:HL16:VOFF") {
  field(DESC, "BPM V Offset")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(EGU, "mm")
  field(PREC, "4")
  field(LOPR, "-5")
  field(HOPR, "+5")
  field(FLNK, "HL2:SBPM:HL16:VOFF_SEQ")
}

record(ao, "HL2:SBPM:HL16:USCL") {
  field(DESC, "BPM U Scale")
  field(DTYP, "Soft Channel")
  field(VAL,  "1")
  field(EGU, "mm")
  field(PREC, "4")
  field(FLNK, "HL2:SBPM:HL16:USCL_SEQ")
}

record(ao, "HL2:SBPM:HL16:VSCL") {
  field(DESC, "BPM V Scale")
  field(DTYP, "Soft Channel")
  field(VAL,  "1")
  field(EGU, "mm")
  field(PREC, "4")
  field(FLNK, "HL2:SBPM:HL16:VSCL_SEQ")
}


record(mbbo, "HL2:SBPM:HL16:ACCESS") {
  field(DESC, "BPM On Line")
  field(DTYP, "StreamSwitch")
  field(OUT, "#C3 S0")
  field(ZRVL, "1")
  field(ZRST, "Running")
  field(ZRSV, "NO_ALARM")
  field(ONVL, "1")
  field(ONST, "Maintenance")
  field(ONSV, "MINOR")
  field(TWVL, "1")
  field(TWST, "Test")
  field(TWSV, "MINOR")
  field(THVL, "0")
  field(THST, "OFFLINE")
  field(THSV, "MAJOR")
# set both, rval and val to get it right
# regardless of whether devsup does conversion
# or not.
  field(RVAL, "0")
  field(VAL,  "0")
  field(PINI, "YES")
  field(FLNK, "HL2:SBPM:HL16:SIMOFF")
  info(autosaveFields, "RVAL")
}

#
# Used by higher level software to determine if a PV is in feedback or not.
# May also be used by actuator (magnet and RF) IOC applications to 
# switch output records to "closed_loop" to prevent outside programs from
# changing setpoints when an actuator device is in feedback.
#
record(mbbo, "HL2:SBPM:HL16:FBCK")
{
  field(DESC, "Feedback State")
  field(PINI, "YES")
  field(OMSL, "supervisory")
  field(VAL,  "0")
  field(ZRVL, "0")
  field(ONVL, "1")
  field(TWVL, "2")
# Off - this device can be used in feedback but all feedback loops 
# using it are off.
  field(ZRST, "Off")
# On - this device is being used by one or more feedback loops.
  field(ONST, "On")
# Unavailable - this device is not used by any feedback loop.
  field(TWST, "Unavailable")
  info(autosaveFields, "VAL")
}

# Convenience record holding the MAD name
record(stringin, "HL2:SBPM:HL16:MADN") {
  field(DESC, "MAD Name")
  field(VAL, "SBPMHL16")
  field(PINI, "YES")
}

record(stringin, "SBPMHL16:NAME") {
  field(DESC, "BPM Name")
  field(VAL, "HL2:SBPM:HL16")
  field(PINI, "YES")
}

record(ai, "HL2:SBPM:HL16:X_SLOW") {
#alias("HL2:SBPM:HL16:X1H")
  field(DESC, "X snapshot for display")
  field(EGU, "mm")
  field(INP, "HL2:SBPM:HL16:X MS")
  field(FLNK, "HL2:SBPM:HL16:Y_SLOW")
  field(PREC, "4")
  field(SCAN, "1 second")
  field(LOPR, "-12")
  field(HOPR, "+12")
}

record(ai, "HL2:SBPM:HL16:Y_SLOW") {
#alias("HL2:SBPM:HL16:Y1H")
  field(DESC, "Y snapshot for display")
  field(EGU, "mm")
  field(INP, "HL2:SBPM:HL16:Y NPP MS")
  field(FLNK, "HL2:SBPM:HL16:TMIT_SLOW")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
}

record(ai, "HL2:SBPM:HL16:TMIT_SLOW") {
#alias("HL2:SBPM:HL16:TMIT1H")
  field(DESC, "TMIT snapshot for display")
  field(INP, "HL2:SBPM:HL16:TMIT NPP MS")
  field(EGU, "Nel")
  field(PREC, "3")
  field(LOPR, "0")
  field(HOPR, "1E11")
}

######################################
# Simulation Parameters + Control
######################################

# switch off simulation when going off-line
record(calcout, "HL2:SBPM:HL16:SIMOFF") {
  field(DESC, "Sim Off Propagator")
  field(INPA, "HL2:SBPM:HL16:ACCESS.RVAL")
  field(CALC, "A")
  field(OCAL, "0")
  field(OOPT, "When Zero")
  field(DOPT, "Use OCAL")
  field(OUT,  "HL2:SBPM:HL16:SIMC PP")
}

record(calcout, "HL2:SBPM:HL16:SIM") {
  field(DESC, "BPM Pos. Simulation")
  field(DTYP, "Strip Signal Simulator")
  field(OUT, "3")
#CALC & VAL unused; the real calculation is done
#        in device support. The reason this is a
#        calcout rather than sub is that we want
#        to use the OUT link...
  field(CALC, "A")
  field(INPA, "HL2:SBPM:HL16:USCL")
  field(INPL, "0")
}

# Switch simulation record HL2:SBPM:HL16:SIMCSEQ moved to
# bpmCavity.db.part and bpmStripl.db.part 

record(mbbo, "HL2:SBPM:HL16:SIMC") {
  field(DESC, "Stripl Sim Ctl")
  field(DTYP, "Raw Soft Channel")
  field(OUT,  "HL2:SBPM:HL16:SIMCSEQ.SELN PP")
  field(ZRST, "OFF")
  field(ZRVL, "0x0f")
  field(ONST, "ON")
  field(ONVL, "0x1c0")
  field(TWST, "SOFT")
  field(TWVL, "0x030")
  field(MASK, "-1")
  field(NOBT, "16")
  field(VAL,  "0")
  field(RVAL, "0x0f")
  field(PINI, "YES")
}

record(ao, "HL2:SBPM:HL16:XSIM") {
  field(DESC, "BPM X Pos. Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL16:SIM.B PP")
  field(VAL, "0.5")
  field(EGU, "mm")
  field(PINI, "YES")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
}

record(ao, "HL2:SBPM:HL16:YSIM") {
  field(DESC, "BPM Y Pos. Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL16:SIM.C PP")
  field(VAL, "0.")
  field(EGU, "mm")
  field(PINI, "YES")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
}

record(ao, "HL2:SBPM:HL16:QSIM") {
  field(DESC, "BPM Q Simul.")
  field(DTYP, "Raw Soft Channel")
  field(OUT, "HL2:SBPM:HL16:SIM.D PP")
  field(EGU, "Nel")
  field(ASLO, "6000")
#ESLO is used to add attenuation
  field(LINR, "LINEAR")
  field(VAL, "1E9")
  field(PINI, "YES")
  field(PREC, "4")
  field(LOPR, "0")
  field(HOPR, "1E11")
}

record(ao, "HL2:SBPM:HL16:ROTS") {
  field(DESC, "BPM Rot. Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL16:SIM.E PP")
  field(VAL, "0.")
  field(EGU, "deg")
  field(PINI, "YES")
  field(PREC, "1")
  field(LOPR, "-180")
}

record(ao, "HL2:SBPM:HL16:PSIS") {
  field(DESC, "BPM Angle. Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL16:SIM.F PP")
  field(VAL, "90")
  field(EGU, "deg")
  field(PINI, "YES")
  field(PREC, "1")
  field(LOPR, "0")
}

record(aao, "HL2:SBPM:HL16:DIGISIMW") {
  field(DESC, "VME Digi Sim. Waveform")
  field(DTYP, "VmeDigi Sim Wav")
  field(OUT,  "#C3 S0")
  field(FTVL, "SHORT")
  field(EGU,  "Counts")
  field(HOPR, "32678")
  field(LOPR, "-32768")
# 16384 samples/channel * 4 channels
  field(NELM, "65536")
  field(PINI, "NO")
}

#Used by model/database folks to verify BPM

record(ao, "HL2:SBPM:HL16:Z") {
  field(DESC, "Z Position")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

# MPS interface
record(bo, "HL2:SBPM:HL16:MPSBYP") {
  field(DESC, "MPS Bypass")
  field(DTYP, "BusAddress")
  field(OUT,  "#C0S2@bpmMPS+0,m32")
  field(MASK, "8")
  field(ZNAM, "BYPASSED")
  field(ONAM, "NOT_BYPASSED")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(VAL,  "0")
  field(PINI, "YES")
  field(ASG,  "")
  info(autosaveFields, "VAL")
}

record(bo, "HL2:SBPM:HL16:MPSLTBYP") {
  field(DESC, "MPS Bypass")
  field(DTYP, "BusAddress")
  field(OUT,  "#C1S2@bpmMPS+0,m32")
  field(MASK, "8")
  field(ZNAM, "BYPASSED")
  field(ONAM, "NOT_BYPASSED")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")
  field(VAL,  "0")
  field(PINI, "YES")
  field(ASG,  "")
  info(autosaveFields, "VAL")
}

record(calc, "HL2:SBPM:HL16:MPSIGNRCALC") {
  field(DESC, "MPS ignore if TMIT too low")
  field(CALC, "A<B")
  field(INPA, "HL2:SBPM:HL16:TMIT")
  field(INPB, "HL2:SBPM:HL16:T_MPS_THRES_L")
  field(HIHI, "1")
  field(HHSV, "MAJOR")
  field(ASG, "")
}

record(bi, "HL2:SBPM:HL16:MPSIGNORE") {
  field(DESC, "MPS ignore if TMIT too low")
  field(DTYP, "Raw Soft Channel")
  field(SCAN, "1 second")
  field(INP, "HL2:SBPM:HL16:MPSIGNRCALC PP")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "Not ignored")
  field(ONAM, "Ignored")
  field(PINI, "YES")
  field(ASG, "")
}

# Proxy records for users to set X.AOFF, Y.AOFF
# Placed CAS on X and Y for MPS 
# Feb 2010 - CAS has since been removed, but we'll keep 
# these proxy records as they're already in use

record(ao, "HL2:SBPM:HL16:XAOFF") {
  field(DESC, "X.AOFF val")
#  field(OUT, "HL2:SBPM:HL16:X.AOFF")
  field(PINI, "YES")
  field(EGU, "mm")
  field(PREC, "4")
  field(FLNK, "HL2:SBPM:HL16:XOFF")
  info(autosaveFields, "VAL")
}

record(ao, "HL2:SBPM:HL16:YAOFF") {
  field(DESC, "Y.AOFF val")
#  field(OUT, "HL2:SBPM:HL16:Y.AOFF")
  field(PINI, "YES")
  field(EGU, "mm")
  field(PREC, "4")
  field(FLNK, "HL2:SBPM:HL16:YOFF")
  info(autosaveFields, "VAL")
}

# Add CALC to allow users to maintain
# multiple offsets per plane per BPM

record(calcout, "HL2:SBPM:HL16:XOFF") {
  field(DESC, "Add X offsets")
  field(PREC, "4")
  field(CALC, "A+B+C+D")
  field(INPA, "HL2:SBPM:HL16:XAOFF")
# B-E reserved for undulator offsets
  field(INPB, "")
  field(INPC, "")
  field(INPD, "")
  field(INPE, "")
  field(EGU, "mm")
  field(OUT, "HL2:SBPM:HL16:X.AOFF")
  info(autosaveFields, "B C D E")
}

record(calcout, "HL2:SBPM:HL16:YOFF") {
  field(DESC, "Add Y offsets")
  field(PREC, "4")
  field(CALC, "A+B+C+D")
  field(INPA, "HL2:SBPM:HL16:YAOFF")
# B-E reserved for undulator offsets
  field(INPB, "")
  field(INPC, "")
  field(INPD, "")
  field(INPE, "")
  field(EGU, "mm")
  field(OUT, "HL2:SBPM:HL16:Y.AOFF")
  info(autosaveFields, "B C D E")
}


# Records to set MPS thresholds
record(ao, "HL2:SBPM:HL16:X_MPS_THRES_L") {
  field(DESC, "MPS X Threshold Lo")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C3 S0 @Lo")
  field(VAL,  "-1")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL2:SBPM:HL16:X_MPS_THRES_H") {
  field(DESC, "MPS X Threshold Hi")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C3 S0 @Hi")
  field(VAL,  "1")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL2:SBPM:HL16:Y_MPS_THRES_L") {
  field(DESC, "MPS Y Threshold Lo")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C3 S1 @Lo")
  field(VAL,  "-1")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL2:SBPM:HL16:Y_MPS_THRES_H") {
  field(DESC, "MPS Y Threshold Hi")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C3 S1 @Hi")
  field(VAL,  "1")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL2:SBPM:HL16:T_MPS_THRES_L") {
  field(DESC, "MPS TMIT Threshold Lo")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C3 S2 @Lo")
  field(VAL,  "9.375e7")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL2:SBPM:HL16:T_MPS_THRES_H") {
  field(DESC, "MPS TMIT Threshold Hi")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C3 S2 @Hi")
  field(VAL,  "+1.0E20")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}

record(bi, "HL2:SBPM:HL16:FNET") {
  field(DESC, "BPM data on FNET")
  field(VAL, "$(FN,undefined)")
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(PINI, "YES")
}

# Record to inform users that BPM
# needs TMIT and/or X/Y scale calibration
record(mbbo, "HL2:SBPM:HL16:CHK") {
  field(DESC, "Needs cal/iron")
  field(OMSL, "supervisory")
  field(VAL,  "0")
  field(ZRVL, "0")
  field(ONVL, "1")
  field(TWVL, "2")
  field(THVL, "3")
  field(ZRST, " ")
  field(ONST, "Calibrate")
  field(TWST, "Calibrate&iron")
  field(THST, "Iron")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MINOR")
  field(THSV, "MINOR")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

# Switch simulation record 
record(seq, "HL2:SBPM:HL16:SIMCSEQ") {
  field(DESC, "BPM Sim Ctl Seq")
  field(SELM, "Mask")
  field(SELN, "0")

  field(DO1,  "1")
  field(DO2,  "0")
  field(DO3,  "0")
  field(DO4,  "0") #Passive

#  field(DO5,  "7") # .5 second
  field(DO5,  "9") # .1 second
  field(DO6,  "2")
  field(DO7,  "1")
  field(DO8,  "10")
  field(DO9,  "0")

# LNK 1, 2, 8, 9 only relevant for PADs
# Default macro values are set for PADs; other
# architectures must pass in "" for lnk1 and lnk2
  field(LNK1, "")
  field(LNK2, "")
  field(LNK3, "HL2:SBPM:HL16:SIM.L     PP")
  field(LNK4, "HL2:SBPM:HL16:SIM.SCAN  PP")

  field(LNK5, "HL2:SBPM:HL16:SIM.SCAN  PP")
  field(LNK6, "HL2:SBPM:HL16:SIM.L     PP")
  field(LNK7, "HL2:SBPM:HL16:SIM.L     PP")
  field(LNK8, "")
  field(LNK9, "")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL16:UOFF_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL16:UOFF")
	field(DOL2, "HL2:SBPM:HL16:UOFF")
	field(DOL3, "HL2:SBPM:HL16:UOFF")
	field(DOL4, "HL2:SBPM:HL16:UOFF")
	field(DOL5, "HL2:SBPM:HL16:UOFF")
	field(DOL6, "HL2:SBPM:HL16:UOFF")
	field(DOL7, "HL2:SBPM:HL16:UOFF")
	field(DOL8, "HL2:SBPM:HL16:UOFF")
	field(DOL9, "HL2:SBPM:HL16:UOFF")
	field(DOLA, "HL2:SBPM:HL16:UOFF")
	field(LNK1, "HL2:SBPM:HL16:UOFF_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL16:UOFF_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL16:UOFF_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL16:UOFF_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL16:UOFF_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL16:UOFF_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL16:UOFF_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL16:UOFF_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL16:UOFF_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL16:UOFF_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL16:UOFF_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL16:UOFF_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "0")
	field(B,    "0")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "4")
	field(FLNK, "HL2:SBPM:HL16:UOFF_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL16:UOFF_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL16:UOFF_SEL")
	field(OUTA, "HL2:SBPM:HL16:U.AOFF CA")
	field(OUTB, "HL2:SBPM:HL16:UOFF PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL16:UOFF_CTRL")
{
	field(INPA, "HL2:SBPM:HL16:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL16:UOFF_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL16:VOFF_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL16:VOFF")
	field(DOL2, "HL2:SBPM:HL16:VOFF")
	field(DOL3, "HL2:SBPM:HL16:VOFF")
	field(DOL4, "HL2:SBPM:HL16:VOFF")
	field(DOL5, "HL2:SBPM:HL16:VOFF")
	field(DOL6, "HL2:SBPM:HL16:VOFF")
	field(DOL7, "HL2:SBPM:HL16:VOFF")
	field(DOL8, "HL2:SBPM:HL16:VOFF")
	field(DOL9, "HL2:SBPM:HL16:VOFF")
	field(DOLA, "HL2:SBPM:HL16:VOFF")
	field(LNK1, "HL2:SBPM:HL16:VOFF_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL16:VOFF_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL16:VOFF_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL16:VOFF_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL16:VOFF_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL16:VOFF_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL16:VOFF_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL16:VOFF_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL16:VOFF_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL16:VOFF_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL16:VOFF_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL16:VOFF_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "0")
	field(B,    "0")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "4")
	field(FLNK, "HL2:SBPM:HL16:VOFF_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL16:VOFF_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL16:VOFF_SEL")
	field(OUTA, "HL2:SBPM:HL16:V.AOFF CA")
	field(OUTB, "HL2:SBPM:HL16:VOFF PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL16:VOFF_CTRL")
{
	field(INPA, "HL2:SBPM:HL16:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL16:VOFF_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL16:USCL_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL16:USCL")
	field(DOL2, "HL2:SBPM:HL16:USCL")
	field(DOL3, "HL2:SBPM:HL16:USCL")
	field(DOL4, "HL2:SBPM:HL16:USCL")
	field(DOL5, "HL2:SBPM:HL16:USCL")
	field(DOL6, "HL2:SBPM:HL16:USCL")
	field(DOL7, "HL2:SBPM:HL16:USCL")
	field(DOL8, "HL2:SBPM:HL16:USCL")
	field(DOL9, "HL2:SBPM:HL16:USCL")
	field(DOLA, "HL2:SBPM:HL16:USCL")
	field(LNK1, "HL2:SBPM:HL16:USCL_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL16:USCL_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL16:USCL_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL16:USCL_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL16:USCL_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL16:USCL_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL16:USCL_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL16:USCL_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL16:USCL_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL16:USCL_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL16:USCL_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL16:USCL_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "1")
	field(B,    "1")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "4")
	field(FLNK, "HL2:SBPM:HL16:USCL_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL16:USCL_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL16:USCL_SEL")
	field(OUTA, "HL2:SBPM:HL16:U.ASLO CA")
	field(OUTB, "HL2:SBPM:HL16:USCL PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL16:USCL_CTRL")
{
	field(INPA, "HL2:SBPM:HL16:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL16:USCL_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL16:VSCL_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL16:VSCL")
	field(DOL2, "HL2:SBPM:HL16:VSCL")
	field(DOL3, "HL2:SBPM:HL16:VSCL")
	field(DOL4, "HL2:SBPM:HL16:VSCL")
	field(DOL5, "HL2:SBPM:HL16:VSCL")
	field(DOL6, "HL2:SBPM:HL16:VSCL")
	field(DOL7, "HL2:SBPM:HL16:VSCL")
	field(DOL8, "HL2:SBPM:HL16:VSCL")
	field(DOL9, "HL2:SBPM:HL16:VSCL")
	field(DOLA, "HL2:SBPM:HL16:VSCL")
	field(LNK1, "HL2:SBPM:HL16:VSCL_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL16:VSCL_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL16:VSCL_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL16:VSCL_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL16:VSCL_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL16:VSCL_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL16:VSCL_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL16:VSCL_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL16:VSCL_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL16:VSCL_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL16:VSCL_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL16:VSCL_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "1")
	field(B,    "1")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "4")
	field(FLNK, "HL2:SBPM:HL16:VSCL_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL16:VSCL_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL16:VSCL_SEL")
	field(OUTA, "HL2:SBPM:HL16:V.ASLO CA")
	field(OUTB, "HL2:SBPM:HL16:VSCL PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL16:VSCL_CTRL")
{
	field(INPA, "HL2:SBPM:HL16:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL16:VSCL_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL16:PHI_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL16:PHI")
	field(DOL2, "HL2:SBPM:HL16:PHI")
	field(DOL3, "HL2:SBPM:HL16:PHI")
	field(DOL4, "HL2:SBPM:HL16:PHI")
	field(DOL5, "HL2:SBPM:HL16:PHI")
	field(DOL6, "HL2:SBPM:HL16:PHI")
	field(DOL7, "HL2:SBPM:HL16:PHI")
	field(DOL8, "HL2:SBPM:HL16:PHI")
	field(DOL9, "HL2:SBPM:HL16:PHI")
	field(DOLA, "HL2:SBPM:HL16:PHI")
	field(LNK1, "HL2:SBPM:HL16:PHI_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL16:PHI_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL16:PHI_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL16:PHI_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL16:PHI_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL16:PHI_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL16:PHI_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL16:PHI_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL16:PHI_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL16:PHI_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL16:PHI_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL16:PHI_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "0")
	field(B,    "0")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "1")
	field(FLNK, "HL2:SBPM:HL16:PHI_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL16:PHI_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL16:PHI_SEL")
	field(OUTA, "HL2:SBPM:HL16:CALC.E CA")
	field(OUTB, "HL2:SBPM:HL16:PHI PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL16:PHI_CTRL")
{
	field(INPA, "HL2:SBPM:HL16:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL16:PHI_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL16:PSI_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL16:PSI")
	field(DOL2, "HL2:SBPM:HL16:PSI")
	field(DOL3, "HL2:SBPM:HL16:PSI")
	field(DOL4, "HL2:SBPM:HL16:PSI")
	field(DOL5, "HL2:SBPM:HL16:PSI")
	field(DOL6, "HL2:SBPM:HL16:PSI")
	field(DOL7, "HL2:SBPM:HL16:PSI")
	field(DOL8, "HL2:SBPM:HL16:PSI")
	field(DOL9, "HL2:SBPM:HL16:PSI")
	field(DOLA, "HL2:SBPM:HL16:PSI")
	field(LNK1, "HL2:SBPM:HL16:PSI_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL16:PSI_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL16:PSI_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL16:PSI_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL16:PSI_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL16:PSI_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL16:PSI_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL16:PSI_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL16:PSI_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL16:PSI_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL16:PSI_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL16:PSI_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "90")
	field(B,    "90")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "1")
	field(FLNK, "HL2:SBPM:HL16:PSI_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL16:PSI_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL16:PSI_SEL")
	field(OUTA, "HL2:SBPM:HL16:CALC.F CA")
	field(OUTB, "HL2:SBPM:HL16:PSI PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL16:PSI_CTRL")
{
	field(INPA, "HL2:SBPM:HL16:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL16:PSI_SEL.L PP")
}
record(longout, "HL2:SBPM:HL16:PARMSEL") {
	field(VAL, "0")
	field(PINI, "YES")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


# per BPM database for stripline BPMs

##############################################
# This is the head of the main processing chain
# that runs at the highest priority.
##############################################

#############################################
# This is the head of the processing chain for
# diagnostics.
##############################################
record(ai, "HL2:SBPM:HL17:GRN") {
  field(DESC, "GRN Strip Amplitude")
  field(DTYP, "Raw Bpm Signal")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "#C4 S0")
  field(EGU, "raw")
#TODO set HOPR/LOPR, alarm limits
  field(SCAN, "I/O Intr")
# The priority determines what scan list we are being
# put on (see drvPadUdpComm.c)
  field(PRIO, "LOW")
  field(FLNK, "HL2:SBPM:HL17:RED")
# HOPR for the energy algorithm is determined as follows:
#
#                      inf        inf
#  1) Fourier relation / h^2 dt = / |H|^2 df = 2 B
#                     0         -inf
#
#  1a) It can be shown that the maximum of the impuls response
#      ha is ~ 2 B
#                               
#  2) The digitizer produces the numbers
#
#     Ai = 2^s (hi/ha)
#
#     where ha is the maximum of the impuls response
#     and 2^s is a scale factor.
#     
#  3) 'Energy algorithm' calculates S = sum( Ai^2 )
#
#                                                     inf
#  4) S = (2^s / ha)^2 sum(hi^2) = K sum(hi^2) Dt ~ K / h^2 dt
#                                                    0
#
#     with K = (2^s / ha)^2 fs
#
#  5) From 4) and 1a) ->  S ~ K ha and therefore
#
#  6) S = 2^(2s) fs/ha = 2^(2s) fs/(2 B)
#
#  7) The strip signals are sqrt(S); hence HOPR is about
#
#     HOPR ~ 2^s  sqrt( fs/2/B )
#
#     with 2^s = 32768, fs=120MHz, B=10MHz it follows
#     that HOPR ~ 1E5; we add some margin...
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL17:RED") {
  field(DESC, "RED Strip Amplitude")
  field(DTYP, "Raw Bpm Signal")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "#C4 S1")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(FLNK, "HL2:SBPM:HL17:BLU")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL17:BLU") {
  field(DESC, "BLU Strip Amplitude")
  field(DTYP, "Raw Bpm Signal")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "#C4 S2")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(FLNK, "HL2:SBPM:HL17:YLO")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL17:YLO") {
  field(DESC, "YLO Strip Amplitude")
  field(DTYP, "Raw Bpm Signal")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "#C4 S3")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

##############################################
# Slowly-scanned diagnostics
##############################################

#
record(waveform, "HL2:SBPM:HL17:REDW") {
  field(DESC, "Raw CAL RED Data")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP, "#C4 S1")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "1 second")
}

record(waveform, "HL2:SBPM:HL17:GRNW") {
  field(DESC, "Raw CAL GRN Data")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP, "#C4 S2")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "1 second")
}

record(waveform, "HL2:SBPM:HL17:RAWDBG") {
  field(DESC, "Raw BEAM Dbg")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
# do not 'wbscan' for now since e.g., an underrange
# condition on the real signal can happen.
  field(INP, "#C4 S7")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "Passive")
}

record(waveform, "HL2:SBPM:HL17:REDDBG") {
  field(DESC, "Raw CAL RED Dbg")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP, "#C4 S8 @wbscan")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "Passive")
}

record(waveform, "HL2:SBPM:HL17:GRNDBG") {
  field(DESC, "Raw CAL GRN Dbg")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP, "#C4 S9 @wbscan")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "Passive")
}

record(ai, "HL2:SBPM:HL17:GRUV") {
  field(DESC, "CAL Gain GRN/RED")
  field(DTYP, "Raw Stripl Calp")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C4 S0")
  field(SCAN, "10 second")
  field(PREC, "4")
  field(LOPR, "0.5")
  field(HOPR, "1.5")
}

record(ai, "HL2:SBPM:HL17:GRU") {
  field(DESC, "CAL Gain GRN/BLU")
  field(DTYP, "Raw Stripl Calp")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C4 S1")
  field(SCAN, "10 second")
  field(PREC, "4")
  field(LOPR, "0.5")
  field(HOPR, "1.5")
  info(autosaveFields, "ASLO")
}

record(ai, "HL2:SBPM:HL17:GRV") {
  field(DESC, "CAL Gain RED/YLO")
  field(DTYP, "Raw Stripl Calp")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C4 S2")
  field(SCAN, "10 second")
  field(PREC, "4")
  field(LOPR, "0.5")
  field(HOPR, "1.5")
  info(autosaveFields, "ASLO")
}

record(ai, "HL2:SBPM:HL17:TGRN") {
  field(DESC, "Green arrival time")
  field(DTYP, "Raw Bpm Signal")
  field(EGU, "ADC Clocks")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C4 S4")
  field(SCAN, "10 second")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "128")
  field(LOLO, "5")
  field(LOW, "8")
  field(HIGH, "60")
  field(HIHI, "70")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
  field(HSV, "MINOR")
  field(HHSV, "MAJOR")
}

record(ai, "HL2:SBPM:HL17:TRED") {
  field(DESC, "Red arrival time")
  field(DTYP, "Raw Bpm Signal")
  field(EGU, "ADC Clocks")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C4 S5")
  field(SCAN, "10 second")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "128")
  field(LOLO, "5")
  field(LOW, "8")
  field(HIGH, "60")
  field(HIHI, "70")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
  field(HSV, "MINOR")
  field(HHSV, "MAJOR")
}

record(ai, "HL2:SBPM:HL17:TBLU") {
  field(DESC, "Blue arrival time")
  field(DTYP, "Raw Bpm Signal")
  field(EGU, "ADC Clocks")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C4 S6")
  field(SCAN, "10 second")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "128")
  field(LOLO, "5")
  field(LOW, "8")
  field(HIGH, "60")
  field(HIHI, "70")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
  field(HSV, "MINOR")
  field(HHSV, "MAJOR")
}

record(ai, "HL2:SBPM:HL17:TYLO") {
  field(DESC, "Yellow arrival time")
  field(DTYP, "Raw Bpm Signal")
  field(EGU, "ADC Clocks")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C4 S7")
  field(SCAN, "10 second")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "128")
  field(LOLO, "5")
  field(LOW, "8")
  field(HIGH, "60")
  field(HIHI, "70")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
  field(HSV, "MINOR")
  field(HHSV, "MAJOR")
}

record(ao, "HL2:SBPM:HL17:PINC_ADJ") {
  field(DESC, "Adjust Pinc. Corr.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL17:CALC.K PP MS")
  field(VAL, "0")
  field(DRVL, "0")
  field(DRVH, "2")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

# QSCL setting:
#
# Q: charge
# Z: impedance
# F: form factor: phi/(2 pi) sin(2 pi f l/c)
#
# Signal =  Q Z F G h(t) = A h(t)  [A] = Vs
#
#                  inf              inf
# Energy =  A^2   / h^2(t) dt = A^2 / |H(w)|^2 dw/2/pi = A^2 B
#                0                 0
#                        
# Measured energy = Sum{ (Vp/32768 * xi)^2 } / fs = S / fs ~ Energy
#
# -> A^2 B = S/fs
#
# With T = sqrt( Sum{ xi^2 } )
#
#    A = sqrt(S)/sqrt(B*fs) = T/sqrt(B*fs) Vp/32768
#
#                      T/32768 Vp
#    Q = A/F/G/Z = -----------------
#                   F G Z sqrt(B*fs)
#
# Vp = { 1.5Vpp/2 (PGA=1) or 2.25Vpp/2 (PGA=0) } / 2 (transformer)
#
# I believe PGA is off (-> Vp ~ .56V)
#
# Z  = 50
#
# G: (calibration uses GRN/BLU -> signal should have the
#    level of the grn/red channels with the additional switch)
#
# Block diagram / parts / gain:
#
# [filt]    [Att1]    [Amp1]   [Att2]    [BPF]      [Amp2]    [pad] [Amp3]   [switch]
# f-17520  hmc540lp3  SBF-5089 hmc540lp3 MBP-140-6-4 SBF-4089  PAT-0 SBF-4089 HMC-197
#
#  -2dB*    -1dB       20dB     -1dB     -4.5         14.8dB   0dB   14.8dB   -0.4dB
#
# *: 1st filter ATT is a wild guess.
#  BPF loss (RLC Catalog, pp.55): (L (nsect+.5) / (% of 3dB BW) + .2) dB
#  with L ~6.2  10MHz/fc=140Mhz filter-> 4.5
#
#  -> Gtot ~ 40.7dB
#
#  subtract cable loss (2dB); Gtot = 86
# 
#                      T/32768 Vp            .56V/32768
#    Q = A/F/G/Z = ----------------- = T/F  ------------------------
#                   F G Z sqrt(B*fs)        86*50*sqrt(10*140)Mhz
#
#      = T/F = 1.06E-7/F nC
#
#    F for a 7% coverage, 4" BPM at 140MHz   .07 sin(2*pi*140e6 4*.0254/3e8)
#      = .021
#
#      => 1.06E-7/.021 nC = 5E-6 nC
#
# (Faraday cup measurement -> (3600/44)^-1 1e-4 -> 1.22E-6
#
record(ao, "HL2:SBPM:HL17:QSCL") {
  field(DESC, "TMIT/Charge Scale")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL17:QSCA.A PP MS")
# 5.0E-6 / 1.6E-10 [nC/e-]
  field(VAL, "31250")
  field(EGU, "Nel")
  field(PREC, "3")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

# Adjust TMIT scale for AFE attenuation
record(calcout, "HL2:SBPM:HL17:QSCA") {
  field(DESC, "TMIT ATT Adj. Scale")
  field(INPB, "HL2:SBPM:HL17:ATT1 CP")
  field(INPC, "HL2:SBPM:HL17:ATT2 CP")
  field(CALC, "A*10^((B+C+D)/20)")
# use CA link to deposit into TMIT.ASLO so
# that TMIT is not forced into linkset
# of this record
  field(OUT, "HL2:SBPM:HL17:TMIT.ASLO CA")
  field(EGU, "Nel")
  field(PREC, "3")
  info(autosaveFields, "D")
}

record(ao,    "HL2:SBPM:HL17:ATT1SIMP") {
	field(DESC, "ATT1 Propagator")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL2:SBPM:HL17:ATT1   CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL2:SBPM:HL17:ASIM.A PP")
  	field(IVOA, "Set output to IVOV")
	field(IVOV, "0")
	field(EGU,  "dB")
}

record(ao,    "HL2:SBPM:HL17:ATT2SIMP") {
	field(DESC, "ATT2 Propagator")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL2:SBPM:HL17:ATT2   CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL2:SBPM:HL17:ASIM.C PP")
  	field(IVOA, "Set output to IVOV")
	field(IVOV, "0")
	field(EGU,  "dB")
}

# Attenuate charge either by
# real attenuator settings or
# by fake ones.
# If B, C >= 0 then their
# values will be used instead
# of ATT1, ATT2
record(calcout, "HL2:SBPM:HL17:ASIM") {
  field(DESC, "Q Simul Attenuator")
  field(DTYP, "Soft Channel")
  field(OUT,  "HL2:SBPM:HL17:QSIM.ESLO PP")
# ATT1SIM puts value into A
# set to -1 to use real attenuator settings
# and >=0 to use B instead
  field(B,    "-1")
# ATT2SIM puts value into C
# set to -1 to use real attenuator settings
# and >=0 to use D instead
  field(D,    "-1")
  field(CALC, "10^(((B>=0?B:A)+(D>=0?D:C))/20)")
  field(PINI, "YES")
}

record(ao, "HL2:SBPM:HL17:WSIM") {
  field(DESC, "BPM W Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL17:SIM.G PP")
  field(VAL, "0.07")
  field(EGU, "%")
  field(PINI, "YES")
  field(PREC, "3")
  field(LOPR, "0")
  field(HOPR, "0.25")
}


record(sel, "HL2:SBPM:HL17:STA") {
  field(DESC, "Status Summary")
  field(SELM, "High Signal")
  field(INPA, "HL2:SBPM:HL17:RSTA.SEVR MS NPP")
  field(INPB, "HL2:SBPM:HL17:TMIT.SEVR MS NPP")
  field(INPC, "HL2:SBPM:HL17:Y.SEVR    MS NPP")
  field(INPD, "HL2:SBPM:HL17:X.SEVR    MS NPP")
  field(INPE, "HL2:SBPM:HL17:TGRN.SEVR MS NPP")
  field(INPF, "HL2:SBPM:HL17:TRED.SEVR MS NPP")
  field(INPG, "HL2:SBPM:HL17:TBLU.SEVR MS NPP")
  field(INPH, "HL2:SBPM:HL17:TYLO.SEVR MS NPP")
  field(INPI, "HL2:SBPM:HL17:GRU.SEVR  MS NPP")
  field(INPJ, "HL2:SBPM:HL17:GRV.SEVR  MS NPP")
  field(SCAN, "1 second")
}

# This record really belongs on the
# PAD IOC. We keep them here however
# so we can save/restore. It is more
# confusing but shouldn't matter from
# an efficiency standpoint (they are
# rarely changed).
record(longout, "HL2:SBPM:HL17:ATTO") {
  field(DESC, "AFE Tot. Att. Offset")
# fetched via inlink
#field(OUT,  "HL2:SBPM:HL17:ATTC.B PP")
  field(DRVL, "-10")
  field(DRVH, "30")
  field(LOPR, "-10")
  field(HOPR, "30")
  field(EGU, "dB")
  field(VAL, "0")
  field(PINI, "YES")
  info(autosaveFields, "VAL DRVH HOPR DRVL LOPR")
}

# This record really belongs on the
# PAD IOC. We keep them here however
# so we can save/restore. It is more
# confusing but shouldn't matter from
# an efficiency standpoint (they are
# rarely changed).
record(longout, "HL2:SBPM:HL17:CLAO") {
  field(DESC, "AFE Cal. Att. Offset")
# fetched via inlink
#field(OUT,  "HL2:SBPM:HL17:ATTC.C PP")
  field(DRVL, "-20")
  field(DRVH, "20")
  field(LOPR, "-20")
  field(HOPR, "20")
  field(EGU, "dB")
  field(VAL, "40")
  field(PINI, "YES")
  info(autosaveFields, "VAL DRVH HOPR DRVL LOPR")
}

record(calc, "HL2:SBPM:HL17:STA_ALH") {
  field(DESC, "Status Summary")
  field(SCAN, "1 second")
  field(CALC, "0")
  field(INPA, "HL2:SBPM:HL17:RSTA_ALH.SEVR MS NPP")
  field(INPB, "HL2:SBPM:HL17:GRU.SEVR  MS NPP")
  field(INPC, "HL2:SBPM:HL17:GRV.SEVR  MS NPP")
  field(INPD, "HL2:SBPM:HL17:CHK.SEVR MS NPP")
}

# snapshot PV for the bpm values display
record(ai, "HL2:SBPM:HL17:GRN_SLOW") {
  field(DESC, "GRN snapshot for display")
  field(INP, "HL2:SBPM:HL17:GRN NPP MS")
  field(EGU, "raw")
  field(SCAN, "1 second")
  field(FLNK, "HL2:SBPM:HL17:RED_SLOW")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL17:RED_SLOW") {
  field(DESC, "RED snapshot for display")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "HL2:SBPM:HL17:RED NPP MS")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(FLNK, "HL2:SBPM:HL17:BLU_SLOW")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL17:BLU_SLOW") {
  field(DESC, "BLU snapshot for display")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "HL2:SBPM:HL17:BLU NPP MS")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(FLNK, "HL2:SBPM:HL17:YLO_SLOW")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL17:YLO_SLOW") {
  field(DESC, "YLO snapshot for display")
  field(INP, "HL2:SBPM:HL17:YLO NPP MS")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(sub, "HL2:SBPM:HL17:CALC") {
  field(SNAM, "drvBpmBvectSetupSub")
# E: phi F: psi
# BPM channel number in L
  field(INPL, "4")
  field(SCAN, "Passive")
}

record(bo, "HL2:SBPM:HL17:PINC_ENA") {
  field(DESC, "Simple Pincushion Alg")
  field(DTYP, "BusAddress")
  field(OUT,  "#C0S2@drvBpmStriplPincEna,m32")
  field(MASK, "16")
  field(ZNAM, "DISABLED")
  field(ONAM, "ENABLED")
  field(VAL,  "0")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

record(ao, "HL2:SBPM:HL17:UDR_THRES") {
  field(DESC, "Detection Underrange Threshold")
  field(DTYP, "Bpm Parameters")
  field(OUT,  "#C4S0")
  field(EGU,  "ADC Ticks")
  field(DOL,  "45.26")
  field(PINI, "YES")
  field(DRVL, "0")
  field(DRVH, "32767")
  info(autosaveFields, "VAL")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


# per BPM database for stripline BPMs

######################################
# HEAD of main processing chain
######################################

record(ai, "HL2:SBPM:HL17:X") {
  field(DESC, "X Position")
  field(EGU, "mm")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C4 S11")
  field(SCAN, "I/O Intr")
# The priority determines what scan list we are being
# put on (see drvPadUdpComm.c)
  field(PRIO, "HIGH")
  field(FLNK, "HL2:SBPM:HL17:Y")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
  field(ASG,  "")
  field(TSE, "-2")
  info(autosaveFields, "ASLO LOLO LOW HIGH HIHI HHSV LLSV")
}

record(ai, "HL2:SBPM:HL17:Y") {
  field(DESC, "Y Position")
  field(EGU, "mm")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C4 S12")
  field(FLNK, "HL2:SBPM:HL17:TMIT")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
  field(ASG,  "")
  field(TSE, "-2")
  info(autosaveFields, "ASLO LOLO LOW HIGH HIHI HHSV LLSV")
}

record(ai, "HL2:SBPM:HL17:TMIT") {
  field(DESC, "Charge Estimate")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C4 S13")
  field(EGU, "Nel")
  field(PREC, "3")
  field(LOPR, "0")
  field(HOPR, "1E11")
# FLINK into BSA
  field(FLNK, "HL2:SBPM:HL17:EFX.PROC")
  field(ASG,  "")
  field(TSE, "-2")
  info(autosaveFields, "LOLO LOW HIGH HIHI HHSV LLSV ")
}


######################################
# HEAD of diagnostics processing chain
######################################

# leave RWAV in it's own lockset; don't FLNK
# to 'U' & friends
record(waveform, "HL2:SBPM:HL17:RWAV") {
  field(DESC, "Raw BPM Data")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP,  "#C4 S0")
  field(SCAN, "I/O Intr")
# use LOW or HIGH to end up on the 'diagnostic' 
# scan list (see drvPadUdpComm.c)
  field(PRIO, "LOW")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU,  "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
}

record(ai, "HL2:SBPM:HL17:U") {
  field(DESC, "Raw U Position")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C4 S8")
  field(SCAN, "I/O Intr")
# use LOW or HIGH to end up on the 'diagnostic' 
# scan list (see drvPadUdpComm.c)
  field(PRIO, "LOW")
  field(PREC, "5")
  field(EGU,  "mm")
  field(LOPR, "-0.7")
  field(HOPR, "+0.7")
  field(FLNK, "HL2:SBPM:HL17:V")
}

record(ai, "HL2:SBPM:HL17:V") {
  field(DESC, "Raw V Position")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C4 S9")
  field(SCAN, "Passive")
  field(PREC, "5")
  field(EGU,  "mm")
  field(LOPR, "-0.7")
  field(HOPR, "+0.7")
  field(FLNK, "HL2:SBPM:HL17:PINC")
}

record(ai, "HL2:SBPM:HL17:PINC") {
  field(DESC, "Pin Cushion Corr.")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C4 S10")
  field(SCAN, "Passive")
}

record(longin, "HL2:SBPM:HL17:RSTA") {
  field(DESC, "Status of Raw Processor")
  field(DTYP, "Bpm Raw Status")
  field(INP, "#C4S0")
  field(SCAN, "1 second")
  field(LOLO, "-1")
  field(HIHI, "+1")
  field(HHSV, "INVALID")
  field(LLSV, "INVALID")
  field(FLNK, "HL2:SBPM:HL17:RSTA_ALH")
}


record(calc, "HL2:SBPM:HL17:RSTA_ALH") {
  field(CALC, "A & B")
  field(INPA, "HL2:SBPM:HL17:RSTA")
  field(INPB, "0x30F")
  field(HIHI, "1")
  field(LOLO, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(SCAN, "Passive")
}

######################################
# Input/Parameteres
######################################

record(ao, "HL2:SBPM:HL17:PHI") {
  field(DESC, "Rot Angle")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(EGU, "deg")
  field(PREC, "1")
  field(LOPR, "-180")
  field(HOPR, "+180")
  field(FLNK, "HL2:SBPM:HL17:PHI_SEQ")
}

record(ao, "HL2:SBPM:HL17:PSI") {
  field(DESC, "Axis Sep. Angle")
  field(DTYP, "Soft Channel")
  field(VAL, "90")
  field(EGU, "deg")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "+180")
  field(FLNK, "HL2:SBPM:HL17:PSI_SEQ")
}

#record(dfanout, "HL2:SBPM:HL17:PCMM") {
#  field(DESC, "BPM Scale")
#  field(OUTA, "HL2:SBPM:HL17:USCL PP MS")
#  field(OUTB, "HL2:SBPM:HL17:VSCL PP MS")
#  field(VAL, "12")
#  field(EGU, "mm")
#  field(PREC, "4")
#  field(LOPR, "5")
#  field(HOPR, "15")
#  field(PINI, "YES")
#}

record(ao, "HL2:SBPM:HL17:UOFF") {
  field(DESC, "BPM U Offset")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(EGU, "mm")
  field(PREC, "4")
  field(LOPR, "-5")
  field(HOPR, "+5")
  field(FLNK, "HL2:SBPM:HL17:UOFF_SEQ")
}

record(ao, "HL2:SBPM:HL17:VOFF") {
  field(DESC, "BPM V Offset")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(EGU, "mm")
  field(PREC, "4")
  field(LOPR, "-5")
  field(HOPR, "+5")
  field(FLNK, "HL2:SBPM:HL17:VOFF_SEQ")
}

record(ao, "HL2:SBPM:HL17:USCL") {
  field(DESC, "BPM U Scale")
  field(DTYP, "Soft Channel")
  field(VAL,  "1")
  field(EGU, "mm")
  field(PREC, "4")
  field(FLNK, "HL2:SBPM:HL17:USCL_SEQ")
}

record(ao, "HL2:SBPM:HL17:VSCL") {
  field(DESC, "BPM V Scale")
  field(DTYP, "Soft Channel")
  field(VAL,  "1")
  field(EGU, "mm")
  field(PREC, "4")
  field(FLNK, "HL2:SBPM:HL17:VSCL_SEQ")
}


record(mbbo, "HL2:SBPM:HL17:ACCESS") {
  field(DESC, "BPM On Line")
  field(DTYP, "StreamSwitch")
  field(OUT, "#C4 S0")
  field(ZRVL, "1")
  field(ZRST, "Running")
  field(ZRSV, "NO_ALARM")
  field(ONVL, "1")
  field(ONST, "Maintenance")
  field(ONSV, "MINOR")
  field(TWVL, "1")
  field(TWST, "Test")
  field(TWSV, "MINOR")
  field(THVL, "0")
  field(THST, "OFFLINE")
  field(THSV, "MAJOR")
# set both, rval and val to get it right
# regardless of whether devsup does conversion
# or not.
  field(RVAL, "0")
  field(VAL,  "0")
  field(PINI, "YES")
  field(FLNK, "HL2:SBPM:HL17:SIMOFF")
  info(autosaveFields, "RVAL")
}

#
# Used by higher level software to determine if a PV is in feedback or not.
# May also be used by actuator (magnet and RF) IOC applications to 
# switch output records to "closed_loop" to prevent outside programs from
# changing setpoints when an actuator device is in feedback.
#
record(mbbo, "HL2:SBPM:HL17:FBCK")
{
  field(DESC, "Feedback State")
  field(PINI, "YES")
  field(OMSL, "supervisory")
  field(VAL,  "0")
  field(ZRVL, "0")
  field(ONVL, "1")
  field(TWVL, "2")
# Off - this device can be used in feedback but all feedback loops 
# using it are off.
  field(ZRST, "Off")
# On - this device is being used by one or more feedback loops.
  field(ONST, "On")
# Unavailable - this device is not used by any feedback loop.
  field(TWST, "Unavailable")
  info(autosaveFields, "VAL")
}

# Convenience record holding the MAD name
record(stringin, "HL2:SBPM:HL17:MADN") {
  field(DESC, "MAD Name")
  field(VAL, "SBPMHL17")
  field(PINI, "YES")
}

record(stringin, "SBPMHL17:NAME") {
  field(DESC, "BPM Name")
  field(VAL, "HL2:SBPM:HL17")
  field(PINI, "YES")
}

record(ai, "HL2:SBPM:HL17:X_SLOW") {
#alias("HL2:SBPM:HL17:X1H")
  field(DESC, "X snapshot for display")
  field(EGU, "mm")
  field(INP, "HL2:SBPM:HL17:X MS")
  field(FLNK, "HL2:SBPM:HL17:Y_SLOW")
  field(PREC, "4")
  field(SCAN, "1 second")
  field(LOPR, "-12")
  field(HOPR, "+12")
}

record(ai, "HL2:SBPM:HL17:Y_SLOW") {
#alias("HL2:SBPM:HL17:Y1H")
  field(DESC, "Y snapshot for display")
  field(EGU, "mm")
  field(INP, "HL2:SBPM:HL17:Y NPP MS")
  field(FLNK, "HL2:SBPM:HL17:TMIT_SLOW")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
}

record(ai, "HL2:SBPM:HL17:TMIT_SLOW") {
#alias("HL2:SBPM:HL17:TMIT1H")
  field(DESC, "TMIT snapshot for display")
  field(INP, "HL2:SBPM:HL17:TMIT NPP MS")
  field(EGU, "Nel")
  field(PREC, "3")
  field(LOPR, "0")
  field(HOPR, "1E11")
}

######################################
# Simulation Parameters + Control
######################################

# switch off simulation when going off-line
record(calcout, "HL2:SBPM:HL17:SIMOFF") {
  field(DESC, "Sim Off Propagator")
  field(INPA, "HL2:SBPM:HL17:ACCESS.RVAL")
  field(CALC, "A")
  field(OCAL, "0")
  field(OOPT, "When Zero")
  field(DOPT, "Use OCAL")
  field(OUT,  "HL2:SBPM:HL17:SIMC PP")
}

record(calcout, "HL2:SBPM:HL17:SIM") {
  field(DESC, "BPM Pos. Simulation")
  field(DTYP, "Strip Signal Simulator")
  field(OUT, "4")
#CALC & VAL unused; the real calculation is done
#        in device support. The reason this is a
#        calcout rather than sub is that we want
#        to use the OUT link...
  field(CALC, "A")
  field(INPA, "HL2:SBPM:HL17:USCL")
  field(INPL, "0")
}

# Switch simulation record HL2:SBPM:HL17:SIMCSEQ moved to
# bpmCavity.db.part and bpmStripl.db.part 

record(mbbo, "HL2:SBPM:HL17:SIMC") {
  field(DESC, "Stripl Sim Ctl")
  field(DTYP, "Raw Soft Channel")
  field(OUT,  "HL2:SBPM:HL17:SIMCSEQ.SELN PP")
  field(ZRST, "OFF")
  field(ZRVL, "0x0f")
  field(ONST, "ON")
  field(ONVL, "0x1c0")
  field(TWST, "SOFT")
  field(TWVL, "0x030")
  field(MASK, "-1")
  field(NOBT, "16")
  field(VAL,  "0")
  field(RVAL, "0x0f")
  field(PINI, "YES")
}

record(ao, "HL2:SBPM:HL17:XSIM") {
  field(DESC, "BPM X Pos. Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL17:SIM.B PP")
  field(VAL, "0.5")
  field(EGU, "mm")
  field(PINI, "YES")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
}

record(ao, "HL2:SBPM:HL17:YSIM") {
  field(DESC, "BPM Y Pos. Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL17:SIM.C PP")
  field(VAL, "0.")
  field(EGU, "mm")
  field(PINI, "YES")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
}

record(ao, "HL2:SBPM:HL17:QSIM") {
  field(DESC, "BPM Q Simul.")
  field(DTYP, "Raw Soft Channel")
  field(OUT, "HL2:SBPM:HL17:SIM.D PP")
  field(EGU, "Nel")
  field(ASLO, "6000")
#ESLO is used to add attenuation
  field(LINR, "LINEAR")
  field(VAL, "1E9")
  field(PINI, "YES")
  field(PREC, "4")
  field(LOPR, "0")
  field(HOPR, "1E11")
}

record(ao, "HL2:SBPM:HL17:ROTS") {
  field(DESC, "BPM Rot. Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL17:SIM.E PP")
  field(VAL, "0.")
  field(EGU, "deg")
  field(PINI, "YES")
  field(PREC, "1")
  field(LOPR, "-180")
}

record(ao, "HL2:SBPM:HL17:PSIS") {
  field(DESC, "BPM Angle. Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL17:SIM.F PP")
  field(VAL, "90")
  field(EGU, "deg")
  field(PINI, "YES")
  field(PREC, "1")
  field(LOPR, "0")
}

record(aao, "HL2:SBPM:HL17:DIGISIMW") {
  field(DESC, "VME Digi Sim. Waveform")
  field(DTYP, "VmeDigi Sim Wav")
  field(OUT,  "#C4 S0")
  field(FTVL, "SHORT")
  field(EGU,  "Counts")
  field(HOPR, "32678")
  field(LOPR, "-32768")
# 16384 samples/channel * 4 channels
  field(NELM, "65536")
  field(PINI, "NO")
}

#Used by model/database folks to verify BPM

record(ao, "HL2:SBPM:HL17:Z") {
  field(DESC, "Z Position")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

# MPS interface
record(bo, "HL2:SBPM:HL17:MPSBYP") {
  field(DESC, "MPS Bypass")
  field(DTYP, "BusAddress")
  field(OUT,  "#C0S2@bpmMPS+0,m32")
  field(MASK, "16")
  field(ZNAM, "BYPASSED")
  field(ONAM, "NOT_BYPASSED")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(VAL,  "0")
  field(PINI, "YES")
  field(ASG,  "")
  info(autosaveFields, "VAL")
}

record(bo, "HL2:SBPM:HL17:MPSLTBYP") {
  field(DESC, "MPS Bypass")
  field(DTYP, "BusAddress")
  field(OUT,  "#C1S2@bpmMPS+0,m32")
  field(MASK, "16")
  field(ZNAM, "BYPASSED")
  field(ONAM, "NOT_BYPASSED")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")
  field(VAL,  "0")
  field(PINI, "YES")
  field(ASG,  "")
  info(autosaveFields, "VAL")
}

record(calc, "HL2:SBPM:HL17:MPSIGNRCALC") {
  field(DESC, "MPS ignore if TMIT too low")
  field(CALC, "A<B")
  field(INPA, "HL2:SBPM:HL17:TMIT")
  field(INPB, "HL2:SBPM:HL17:T_MPS_THRES_L")
  field(HIHI, "1")
  field(HHSV, "MAJOR")
  field(ASG, "")
}

record(bi, "HL2:SBPM:HL17:MPSIGNORE") {
  field(DESC, "MPS ignore if TMIT too low")
  field(DTYP, "Raw Soft Channel")
  field(SCAN, "1 second")
  field(INP, "HL2:SBPM:HL17:MPSIGNRCALC PP")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "Not ignored")
  field(ONAM, "Ignored")
  field(PINI, "YES")
  field(ASG, "")
}

# Proxy records for users to set X.AOFF, Y.AOFF
# Placed CAS on X and Y for MPS 
# Feb 2010 - CAS has since been removed, but we'll keep 
# these proxy records as they're already in use

record(ao, "HL2:SBPM:HL17:XAOFF") {
  field(DESC, "X.AOFF val")
#  field(OUT, "HL2:SBPM:HL17:X.AOFF")
  field(PINI, "YES")
  field(EGU, "mm")
  field(PREC, "4")
  field(FLNK, "HL2:SBPM:HL17:XOFF")
  info(autosaveFields, "VAL")
}

record(ao, "HL2:SBPM:HL17:YAOFF") {
  field(DESC, "Y.AOFF val")
#  field(OUT, "HL2:SBPM:HL17:Y.AOFF")
  field(PINI, "YES")
  field(EGU, "mm")
  field(PREC, "4")
  field(FLNK, "HL2:SBPM:HL17:YOFF")
  info(autosaveFields, "VAL")
}

# Add CALC to allow users to maintain
# multiple offsets per plane per BPM

record(calcout, "HL2:SBPM:HL17:XOFF") {
  field(DESC, "Add X offsets")
  field(PREC, "4")
  field(CALC, "A+B+C+D")
  field(INPA, "HL2:SBPM:HL17:XAOFF")
# B-E reserved for undulator offsets
  field(INPB, "")
  field(INPC, "")
  field(INPD, "")
  field(INPE, "")
  field(EGU, "mm")
  field(OUT, "HL2:SBPM:HL17:X.AOFF")
  info(autosaveFields, "B C D E")
}

record(calcout, "HL2:SBPM:HL17:YOFF") {
  field(DESC, "Add Y offsets")
  field(PREC, "4")
  field(CALC, "A+B+C+D")
  field(INPA, "HL2:SBPM:HL17:YAOFF")
# B-E reserved for undulator offsets
  field(INPB, "")
  field(INPC, "")
  field(INPD, "")
  field(INPE, "")
  field(EGU, "mm")
  field(OUT, "HL2:SBPM:HL17:Y.AOFF")
  info(autosaveFields, "B C D E")
}


# Records to set MPS thresholds
record(ao, "HL2:SBPM:HL17:X_MPS_THRES_L") {
  field(DESC, "MPS X Threshold Lo")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C4 S0 @Lo")
  field(VAL,  "-1")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL2:SBPM:HL17:X_MPS_THRES_H") {
  field(DESC, "MPS X Threshold Hi")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C4 S0 @Hi")
  field(VAL,  "1")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL2:SBPM:HL17:Y_MPS_THRES_L") {
  field(DESC, "MPS Y Threshold Lo")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C4 S1 @Lo")
  field(VAL,  "-1")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL2:SBPM:HL17:Y_MPS_THRES_H") {
  field(DESC, "MPS Y Threshold Hi")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C4 S1 @Hi")
  field(VAL,  "1")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL2:SBPM:HL17:T_MPS_THRES_L") {
  field(DESC, "MPS TMIT Threshold Lo")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C4 S2 @Lo")
  field(VAL,  "9.375e7")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL2:SBPM:HL17:T_MPS_THRES_H") {
  field(DESC, "MPS TMIT Threshold Hi")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C4 S2 @Hi")
  field(VAL,  "+1.0E20")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}

record(bi, "HL2:SBPM:HL17:FNET") {
  field(DESC, "BPM data on FNET")
  field(VAL, "$(FN,undefined)")
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(PINI, "YES")
}

# Record to inform users that BPM
# needs TMIT and/or X/Y scale calibration
record(mbbo, "HL2:SBPM:HL17:CHK") {
  field(DESC, "Needs cal/iron")
  field(OMSL, "supervisory")
  field(VAL,  "0")
  field(ZRVL, "0")
  field(ONVL, "1")
  field(TWVL, "2")
  field(THVL, "3")
  field(ZRST, " ")
  field(ONST, "Calibrate")
  field(TWST, "Calibrate&iron")
  field(THST, "Iron")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MINOR")
  field(THSV, "MINOR")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

# Switch simulation record 
record(seq, "HL2:SBPM:HL17:SIMCSEQ") {
  field(DESC, "BPM Sim Ctl Seq")
  field(SELM, "Mask")
  field(SELN, "0")

  field(DO1,  "1")
  field(DO2,  "0")
  field(DO3,  "0")
  field(DO4,  "0") #Passive

#  field(DO5,  "7") # .5 second
  field(DO5,  "9") # .1 second
  field(DO6,  "2")
  field(DO7,  "1")
  field(DO8,  "10")
  field(DO9,  "0")

# LNK 1, 2, 8, 9 only relevant for PADs
# Default macro values are set for PADs; other
# architectures must pass in "" for lnk1 and lnk2
  field(LNK1, "")
  field(LNK2, "")
  field(LNK3, "HL2:SBPM:HL17:SIM.L     PP")
  field(LNK4, "HL2:SBPM:HL17:SIM.SCAN  PP")

  field(LNK5, "HL2:SBPM:HL17:SIM.SCAN  PP")
  field(LNK6, "HL2:SBPM:HL17:SIM.L     PP")
  field(LNK7, "HL2:SBPM:HL17:SIM.L     PP")
  field(LNK8, "")
  field(LNK9, "")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL17:UOFF_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL17:UOFF")
	field(DOL2, "HL2:SBPM:HL17:UOFF")
	field(DOL3, "HL2:SBPM:HL17:UOFF")
	field(DOL4, "HL2:SBPM:HL17:UOFF")
	field(DOL5, "HL2:SBPM:HL17:UOFF")
	field(DOL6, "HL2:SBPM:HL17:UOFF")
	field(DOL7, "HL2:SBPM:HL17:UOFF")
	field(DOL8, "HL2:SBPM:HL17:UOFF")
	field(DOL9, "HL2:SBPM:HL17:UOFF")
	field(DOLA, "HL2:SBPM:HL17:UOFF")
	field(LNK1, "HL2:SBPM:HL17:UOFF_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL17:UOFF_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL17:UOFF_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL17:UOFF_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL17:UOFF_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL17:UOFF_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL17:UOFF_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL17:UOFF_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL17:UOFF_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL17:UOFF_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL17:UOFF_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL17:UOFF_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "0")
	field(B,    "0")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "4")
	field(FLNK, "HL2:SBPM:HL17:UOFF_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL17:UOFF_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL17:UOFF_SEL")
	field(OUTA, "HL2:SBPM:HL17:U.AOFF CA")
	field(OUTB, "HL2:SBPM:HL17:UOFF PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL17:UOFF_CTRL")
{
	field(INPA, "HL2:SBPM:HL17:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL17:UOFF_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL17:VOFF_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL17:VOFF")
	field(DOL2, "HL2:SBPM:HL17:VOFF")
	field(DOL3, "HL2:SBPM:HL17:VOFF")
	field(DOL4, "HL2:SBPM:HL17:VOFF")
	field(DOL5, "HL2:SBPM:HL17:VOFF")
	field(DOL6, "HL2:SBPM:HL17:VOFF")
	field(DOL7, "HL2:SBPM:HL17:VOFF")
	field(DOL8, "HL2:SBPM:HL17:VOFF")
	field(DOL9, "HL2:SBPM:HL17:VOFF")
	field(DOLA, "HL2:SBPM:HL17:VOFF")
	field(LNK1, "HL2:SBPM:HL17:VOFF_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL17:VOFF_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL17:VOFF_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL17:VOFF_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL17:VOFF_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL17:VOFF_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL17:VOFF_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL17:VOFF_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL17:VOFF_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL17:VOFF_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL17:VOFF_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL17:VOFF_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "0")
	field(B,    "0")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "4")
	field(FLNK, "HL2:SBPM:HL17:VOFF_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL17:VOFF_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL17:VOFF_SEL")
	field(OUTA, "HL2:SBPM:HL17:V.AOFF CA")
	field(OUTB, "HL2:SBPM:HL17:VOFF PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL17:VOFF_CTRL")
{
	field(INPA, "HL2:SBPM:HL17:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL17:VOFF_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL17:USCL_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL17:USCL")
	field(DOL2, "HL2:SBPM:HL17:USCL")
	field(DOL3, "HL2:SBPM:HL17:USCL")
	field(DOL4, "HL2:SBPM:HL17:USCL")
	field(DOL5, "HL2:SBPM:HL17:USCL")
	field(DOL6, "HL2:SBPM:HL17:USCL")
	field(DOL7, "HL2:SBPM:HL17:USCL")
	field(DOL8, "HL2:SBPM:HL17:USCL")
	field(DOL9, "HL2:SBPM:HL17:USCL")
	field(DOLA, "HL2:SBPM:HL17:USCL")
	field(LNK1, "HL2:SBPM:HL17:USCL_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL17:USCL_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL17:USCL_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL17:USCL_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL17:USCL_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL17:USCL_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL17:USCL_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL17:USCL_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL17:USCL_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL17:USCL_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL17:USCL_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL17:USCL_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "1")
	field(B,    "1")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "4")
	field(FLNK, "HL2:SBPM:HL17:USCL_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL17:USCL_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL17:USCL_SEL")
	field(OUTA, "HL2:SBPM:HL17:U.ASLO CA")
	field(OUTB, "HL2:SBPM:HL17:USCL PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL17:USCL_CTRL")
{
	field(INPA, "HL2:SBPM:HL17:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL17:USCL_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL17:VSCL_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL17:VSCL")
	field(DOL2, "HL2:SBPM:HL17:VSCL")
	field(DOL3, "HL2:SBPM:HL17:VSCL")
	field(DOL4, "HL2:SBPM:HL17:VSCL")
	field(DOL5, "HL2:SBPM:HL17:VSCL")
	field(DOL6, "HL2:SBPM:HL17:VSCL")
	field(DOL7, "HL2:SBPM:HL17:VSCL")
	field(DOL8, "HL2:SBPM:HL17:VSCL")
	field(DOL9, "HL2:SBPM:HL17:VSCL")
	field(DOLA, "HL2:SBPM:HL17:VSCL")
	field(LNK1, "HL2:SBPM:HL17:VSCL_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL17:VSCL_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL17:VSCL_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL17:VSCL_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL17:VSCL_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL17:VSCL_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL17:VSCL_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL17:VSCL_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL17:VSCL_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL17:VSCL_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL17:VSCL_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL17:VSCL_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "1")
	field(B,    "1")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "4")
	field(FLNK, "HL2:SBPM:HL17:VSCL_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL17:VSCL_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL17:VSCL_SEL")
	field(OUTA, "HL2:SBPM:HL17:V.ASLO CA")
	field(OUTB, "HL2:SBPM:HL17:VSCL PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL17:VSCL_CTRL")
{
	field(INPA, "HL2:SBPM:HL17:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL17:VSCL_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL17:PHI_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL17:PHI")
	field(DOL2, "HL2:SBPM:HL17:PHI")
	field(DOL3, "HL2:SBPM:HL17:PHI")
	field(DOL4, "HL2:SBPM:HL17:PHI")
	field(DOL5, "HL2:SBPM:HL17:PHI")
	field(DOL6, "HL2:SBPM:HL17:PHI")
	field(DOL7, "HL2:SBPM:HL17:PHI")
	field(DOL8, "HL2:SBPM:HL17:PHI")
	field(DOL9, "HL2:SBPM:HL17:PHI")
	field(DOLA, "HL2:SBPM:HL17:PHI")
	field(LNK1, "HL2:SBPM:HL17:PHI_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL17:PHI_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL17:PHI_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL17:PHI_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL17:PHI_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL17:PHI_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL17:PHI_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL17:PHI_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL17:PHI_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL17:PHI_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL17:PHI_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL17:PHI_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "0")
	field(B,    "0")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "1")
	field(FLNK, "HL2:SBPM:HL17:PHI_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL17:PHI_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL17:PHI_SEL")
	field(OUTA, "HL2:SBPM:HL17:CALC.E CA")
	field(OUTB, "HL2:SBPM:HL17:PHI PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL17:PHI_CTRL")
{
	field(INPA, "HL2:SBPM:HL17:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL17:PHI_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL17:PSI_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL17:PSI")
	field(DOL2, "HL2:SBPM:HL17:PSI")
	field(DOL3, "HL2:SBPM:HL17:PSI")
	field(DOL4, "HL2:SBPM:HL17:PSI")
	field(DOL5, "HL2:SBPM:HL17:PSI")
	field(DOL6, "HL2:SBPM:HL17:PSI")
	field(DOL7, "HL2:SBPM:HL17:PSI")
	field(DOL8, "HL2:SBPM:HL17:PSI")
	field(DOL9, "HL2:SBPM:HL17:PSI")
	field(DOLA, "HL2:SBPM:HL17:PSI")
	field(LNK1, "HL2:SBPM:HL17:PSI_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL17:PSI_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL17:PSI_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL17:PSI_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL17:PSI_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL17:PSI_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL17:PSI_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL17:PSI_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL17:PSI_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL17:PSI_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL17:PSI_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL17:PSI_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "90")
	field(B,    "90")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "1")
	field(FLNK, "HL2:SBPM:HL17:PSI_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL17:PSI_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL17:PSI_SEL")
	field(OUTA, "HL2:SBPM:HL17:CALC.F CA")
	field(OUTB, "HL2:SBPM:HL17:PSI PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL17:PSI_CTRL")
{
	field(INPA, "HL2:SBPM:HL17:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL17:PSI_SEL.L PP")
}
record(longout, "HL2:SBPM:HL17:PARMSEL") {
	field(VAL, "0")
	field(PINI, "YES")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


# per BPM database for stripline BPMs

##############################################
# This is the head of the main processing chain
# that runs at the highest priority.
##############################################

#############################################
# This is the head of the processing chain for
# diagnostics.
##############################################
record(ai, "HL2:SBPM:HL18:GRN") {
  field(DESC, "GRN Strip Amplitude")
  field(DTYP, "Raw Bpm Signal")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "#C5 S0")
  field(EGU, "raw")
#TODO set HOPR/LOPR, alarm limits
  field(SCAN, "I/O Intr")
# The priority determines what scan list we are being
# put on (see drvPadUdpComm.c)
  field(PRIO, "LOW")
  field(FLNK, "HL2:SBPM:HL18:RED")
# HOPR for the energy algorithm is determined as follows:
#
#                      inf        inf
#  1) Fourier relation / h^2 dt = / |H|^2 df = 2 B
#                     0         -inf
#
#  1a) It can be shown that the maximum of the impuls response
#      ha is ~ 2 B
#                               
#  2) The digitizer produces the numbers
#
#     Ai = 2^s (hi/ha)
#
#     where ha is the maximum of the impuls response
#     and 2^s is a scale factor.
#     
#  3) 'Energy algorithm' calculates S = sum( Ai^2 )
#
#                                                     inf
#  4) S = (2^s / ha)^2 sum(hi^2) = K sum(hi^2) Dt ~ K / h^2 dt
#                                                    0
#
#     with K = (2^s / ha)^2 fs
#
#  5) From 4) and 1a) ->  S ~ K ha and therefore
#
#  6) S = 2^(2s) fs/ha = 2^(2s) fs/(2 B)
#
#  7) The strip signals are sqrt(S); hence HOPR is about
#
#     HOPR ~ 2^s  sqrt( fs/2/B )
#
#     with 2^s = 32768, fs=120MHz, B=10MHz it follows
#     that HOPR ~ 1E5; we add some margin...
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL18:RED") {
  field(DESC, "RED Strip Amplitude")
  field(DTYP, "Raw Bpm Signal")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "#C5 S1")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(FLNK, "HL2:SBPM:HL18:BLU")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL18:BLU") {
  field(DESC, "BLU Strip Amplitude")
  field(DTYP, "Raw Bpm Signal")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "#C5 S2")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(FLNK, "HL2:SBPM:HL18:YLO")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL18:YLO") {
  field(DESC, "YLO Strip Amplitude")
  field(DTYP, "Raw Bpm Signal")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "#C5 S3")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

##############################################
# Slowly-scanned diagnostics
##############################################

#
record(waveform, "HL2:SBPM:HL18:REDW") {
  field(DESC, "Raw CAL RED Data")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP, "#C5 S1")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "1 second")
}

record(waveform, "HL2:SBPM:HL18:GRNW") {
  field(DESC, "Raw CAL GRN Data")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP, "#C5 S2")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "1 second")
}

record(waveform, "HL2:SBPM:HL18:RAWDBG") {
  field(DESC, "Raw BEAM Dbg")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
# do not 'wbscan' for now since e.g., an underrange
# condition on the real signal can happen.
  field(INP, "#C5 S7")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "Passive")
}

record(waveform, "HL2:SBPM:HL18:REDDBG") {
  field(DESC, "Raw CAL RED Dbg")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP, "#C5 S8 @wbscan")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "Passive")
}

record(waveform, "HL2:SBPM:HL18:GRNDBG") {
  field(DESC, "Raw CAL GRN Dbg")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP, "#C5 S9 @wbscan")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "Passive")
}

record(ai, "HL2:SBPM:HL18:GRUV") {
  field(DESC, "CAL Gain GRN/RED")
  field(DTYP, "Raw Stripl Calp")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C5 S0")
  field(SCAN, "10 second")
  field(PREC, "4")
  field(LOPR, "0.5")
  field(HOPR, "1.5")
}

record(ai, "HL2:SBPM:HL18:GRU") {
  field(DESC, "CAL Gain GRN/BLU")
  field(DTYP, "Raw Stripl Calp")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C5 S1")
  field(SCAN, "10 second")
  field(PREC, "4")
  field(LOPR, "0.5")
  field(HOPR, "1.5")
  info(autosaveFields, "ASLO")
}

record(ai, "HL2:SBPM:HL18:GRV") {
  field(DESC, "CAL Gain RED/YLO")
  field(DTYP, "Raw Stripl Calp")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C5 S2")
  field(SCAN, "10 second")
  field(PREC, "4")
  field(LOPR, "0.5")
  field(HOPR, "1.5")
  info(autosaveFields, "ASLO")
}

record(ai, "HL2:SBPM:HL18:TGRN") {
  field(DESC, "Green arrival time")
  field(DTYP, "Raw Bpm Signal")
  field(EGU, "ADC Clocks")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C5 S4")
  field(SCAN, "10 second")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "128")
  field(LOLO, "5")
  field(LOW, "8")
  field(HIGH, "60")
  field(HIHI, "70")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
  field(HSV, "MINOR")
  field(HHSV, "MAJOR")
}

record(ai, "HL2:SBPM:HL18:TRED") {
  field(DESC, "Red arrival time")
  field(DTYP, "Raw Bpm Signal")
  field(EGU, "ADC Clocks")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C5 S5")
  field(SCAN, "10 second")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "128")
  field(LOLO, "5")
  field(LOW, "8")
  field(HIGH, "60")
  field(HIHI, "70")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
  field(HSV, "MINOR")
  field(HHSV, "MAJOR")
}

record(ai, "HL2:SBPM:HL18:TBLU") {
  field(DESC, "Blue arrival time")
  field(DTYP, "Raw Bpm Signal")
  field(EGU, "ADC Clocks")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C5 S6")
  field(SCAN, "10 second")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "128")
  field(LOLO, "5")
  field(LOW, "8")
  field(HIGH, "60")
  field(HIHI, "70")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
  field(HSV, "MINOR")
  field(HHSV, "MAJOR")
}

record(ai, "HL2:SBPM:HL18:TYLO") {
  field(DESC, "Yellow arrival time")
  field(DTYP, "Raw Bpm Signal")
  field(EGU, "ADC Clocks")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C5 S7")
  field(SCAN, "10 second")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "128")
  field(LOLO, "5")
  field(LOW, "8")
  field(HIGH, "60")
  field(HIHI, "70")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
  field(HSV, "MINOR")
  field(HHSV, "MAJOR")
}

record(ao, "HL2:SBPM:HL18:PINC_ADJ") {
  field(DESC, "Adjust Pinc. Corr.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL18:CALC.K PP MS")
  field(VAL, "0")
  field(DRVL, "0")
  field(DRVH, "2")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

# QSCL setting:
#
# Q: charge
# Z: impedance
# F: form factor: phi/(2 pi) sin(2 pi f l/c)
#
# Signal =  Q Z F G h(t) = A h(t)  [A] = Vs
#
#                  inf              inf
# Energy =  A^2   / h^2(t) dt = A^2 / |H(w)|^2 dw/2/pi = A^2 B
#                0                 0
#                        
# Measured energy = Sum{ (Vp/32768 * xi)^2 } / fs = S / fs ~ Energy
#
# -> A^2 B = S/fs
#
# With T = sqrt( Sum{ xi^2 } )
#
#    A = sqrt(S)/sqrt(B*fs) = T/sqrt(B*fs) Vp/32768
#
#                      T/32768 Vp
#    Q = A/F/G/Z = -----------------
#                   F G Z sqrt(B*fs)
#
# Vp = { 1.5Vpp/2 (PGA=1) or 2.25Vpp/2 (PGA=0) } / 2 (transformer)
#
# I believe PGA is off (-> Vp ~ .56V)
#
# Z  = 50
#
# G: (calibration uses GRN/BLU -> signal should have the
#    level of the grn/red channels with the additional switch)
#
# Block diagram / parts / gain:
#
# [filt]    [Att1]    [Amp1]   [Att2]    [BPF]      [Amp2]    [pad] [Amp3]   [switch]
# f-17520  hmc540lp3  SBF-5089 hmc540lp3 MBP-140-6-4 SBF-4089  PAT-0 SBF-4089 HMC-197
#
#  -2dB*    -1dB       20dB     -1dB     -4.5         14.8dB   0dB   14.8dB   -0.4dB
#
# *: 1st filter ATT is a wild guess.
#  BPF loss (RLC Catalog, pp.55): (L (nsect+.5) / (% of 3dB BW) + .2) dB
#  with L ~6.2  10MHz/fc=140Mhz filter-> 4.5
#
#  -> Gtot ~ 40.7dB
#
#  subtract cable loss (2dB); Gtot = 86
# 
#                      T/32768 Vp            .56V/32768
#    Q = A/F/G/Z = ----------------- = T/F  ------------------------
#                   F G Z sqrt(B*fs)        86*50*sqrt(10*140)Mhz
#
#      = T/F = 1.06E-7/F nC
#
#    F for a 7% coverage, 4" BPM at 140MHz   .07 sin(2*pi*140e6 4*.0254/3e8)
#      = .021
#
#      => 1.06E-7/.021 nC = 5E-6 nC
#
# (Faraday cup measurement -> (3600/44)^-1 1e-4 -> 1.22E-6
#
record(ao, "HL2:SBPM:HL18:QSCL") {
  field(DESC, "TMIT/Charge Scale")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL18:QSCA.A PP MS")
# 5.0E-6 / 1.6E-10 [nC/e-]
  field(VAL, "31250")
  field(EGU, "Nel")
  field(PREC, "3")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

# Adjust TMIT scale for AFE attenuation
record(calcout, "HL2:SBPM:HL18:QSCA") {
  field(DESC, "TMIT ATT Adj. Scale")
  field(INPB, "HL2:SBPM:HL18:ATT1 CP")
  field(INPC, "HL2:SBPM:HL18:ATT2 CP")
  field(CALC, "A*10^((B+C+D)/20)")
# use CA link to deposit into TMIT.ASLO so
# that TMIT is not forced into linkset
# of this record
  field(OUT, "HL2:SBPM:HL18:TMIT.ASLO CA")
  field(EGU, "Nel")
  field(PREC, "3")
  info(autosaveFields, "D")
}

record(ao,    "HL2:SBPM:HL18:ATT1SIMP") {
	field(DESC, "ATT1 Propagator")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL2:SBPM:HL18:ATT1   CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL2:SBPM:HL18:ASIM.A PP")
  	field(IVOA, "Set output to IVOV")
	field(IVOV, "0")
	field(EGU,  "dB")
}

record(ao,    "HL2:SBPM:HL18:ATT2SIMP") {
	field(DESC, "ATT2 Propagator")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL2:SBPM:HL18:ATT2   CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL2:SBPM:HL18:ASIM.C PP")
  	field(IVOA, "Set output to IVOV")
	field(IVOV, "0")
	field(EGU,  "dB")
}

# Attenuate charge either by
# real attenuator settings or
# by fake ones.
# If B, C >= 0 then their
# values will be used instead
# of ATT1, ATT2
record(calcout, "HL2:SBPM:HL18:ASIM") {
  field(DESC, "Q Simul Attenuator")
  field(DTYP, "Soft Channel")
  field(OUT,  "HL2:SBPM:HL18:QSIM.ESLO PP")
# ATT1SIM puts value into A
# set to -1 to use real attenuator settings
# and >=0 to use B instead
  field(B,    "-1")
# ATT2SIM puts value into C
# set to -1 to use real attenuator settings
# and >=0 to use D instead
  field(D,    "-1")
  field(CALC, "10^(((B>=0?B:A)+(D>=0?D:C))/20)")
  field(PINI, "YES")
}

record(ao, "HL2:SBPM:HL18:WSIM") {
  field(DESC, "BPM W Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL18:SIM.G PP")
  field(VAL, "0.07")
  field(EGU, "%")
  field(PINI, "YES")
  field(PREC, "3")
  field(LOPR, "0")
  field(HOPR, "0.25")
}


record(sel, "HL2:SBPM:HL18:STA") {
  field(DESC, "Status Summary")
  field(SELM, "High Signal")
  field(INPA, "HL2:SBPM:HL18:RSTA.SEVR MS NPP")
  field(INPB, "HL2:SBPM:HL18:TMIT.SEVR MS NPP")
  field(INPC, "HL2:SBPM:HL18:Y.SEVR    MS NPP")
  field(INPD, "HL2:SBPM:HL18:X.SEVR    MS NPP")
  field(INPE, "HL2:SBPM:HL18:TGRN.SEVR MS NPP")
  field(INPF, "HL2:SBPM:HL18:TRED.SEVR MS NPP")
  field(INPG, "HL2:SBPM:HL18:TBLU.SEVR MS NPP")
  field(INPH, "HL2:SBPM:HL18:TYLO.SEVR MS NPP")
  field(INPI, "HL2:SBPM:HL18:GRU.SEVR  MS NPP")
  field(INPJ, "HL2:SBPM:HL18:GRV.SEVR  MS NPP")
  field(SCAN, "1 second")
}

# This record really belongs on the
# PAD IOC. We keep them here however
# so we can save/restore. It is more
# confusing but shouldn't matter from
# an efficiency standpoint (they are
# rarely changed).
record(longout, "HL2:SBPM:HL18:ATTO") {
  field(DESC, "AFE Tot. Att. Offset")
# fetched via inlink
#field(OUT,  "HL2:SBPM:HL18:ATTC.B PP")
  field(DRVL, "-10")
  field(DRVH, "30")
  field(LOPR, "-10")
  field(HOPR, "30")
  field(EGU, "dB")
  field(VAL, "0")
  field(PINI, "YES")
  info(autosaveFields, "VAL DRVH HOPR DRVL LOPR")
}

# This record really belongs on the
# PAD IOC. We keep them here however
# so we can save/restore. It is more
# confusing but shouldn't matter from
# an efficiency standpoint (they are
# rarely changed).
record(longout, "HL2:SBPM:HL18:CLAO") {
  field(DESC, "AFE Cal. Att. Offset")
# fetched via inlink
#field(OUT,  "HL2:SBPM:HL18:ATTC.C PP")
  field(DRVL, "-20")
  field(DRVH, "20")
  field(LOPR, "-20")
  field(HOPR, "20")
  field(EGU, "dB")
  field(VAL, "40")
  field(PINI, "YES")
  info(autosaveFields, "VAL DRVH HOPR DRVL LOPR")
}

record(calc, "HL2:SBPM:HL18:STA_ALH") {
  field(DESC, "Status Summary")
  field(SCAN, "1 second")
  field(CALC, "0")
  field(INPA, "HL2:SBPM:HL18:RSTA_ALH.SEVR MS NPP")
  field(INPB, "HL2:SBPM:HL18:GRU.SEVR  MS NPP")
  field(INPC, "HL2:SBPM:HL18:GRV.SEVR  MS NPP")
  field(INPD, "HL2:SBPM:HL18:CHK.SEVR MS NPP")
}

# snapshot PV for the bpm values display
record(ai, "HL2:SBPM:HL18:GRN_SLOW") {
  field(DESC, "GRN snapshot for display")
  field(INP, "HL2:SBPM:HL18:GRN NPP MS")
  field(EGU, "raw")
  field(SCAN, "1 second")
  field(FLNK, "HL2:SBPM:HL18:RED_SLOW")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL18:RED_SLOW") {
  field(DESC, "RED snapshot for display")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "HL2:SBPM:HL18:RED NPP MS")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(FLNK, "HL2:SBPM:HL18:BLU_SLOW")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL18:BLU_SLOW") {
  field(DESC, "BLU snapshot for display")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "HL2:SBPM:HL18:BLU NPP MS")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(FLNK, "HL2:SBPM:HL18:YLO_SLOW")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL18:YLO_SLOW") {
  field(DESC, "YLO snapshot for display")
  field(INP, "HL2:SBPM:HL18:YLO NPP MS")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(sub, "HL2:SBPM:HL18:CALC") {
  field(SNAM, "drvBpmBvectSetupSub")
# E: phi F: psi
# BPM channel number in L
  field(INPL, "5")
  field(SCAN, "Passive")
}

record(bo, "HL2:SBPM:HL18:PINC_ENA") {
  field(DESC, "Simple Pincushion Alg")
  field(DTYP, "BusAddress")
  field(OUT,  "#C0S2@drvBpmStriplPincEna,m32")
  field(MASK, "32")
  field(ZNAM, "DISABLED")
  field(ONAM, "ENABLED")
  field(VAL,  "0")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

record(ao, "HL2:SBPM:HL18:UDR_THRES") {
  field(DESC, "Detection Underrange Threshold")
  field(DTYP, "Bpm Parameters")
  field(OUT,  "#C5S0")
  field(EGU,  "ADC Ticks")
  field(DOL,  "45.26")
  field(PINI, "YES")
  field(DRVL, "0")
  field(DRVH, "32767")
  info(autosaveFields, "VAL")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


# per BPM database for stripline BPMs

######################################
# HEAD of main processing chain
######################################

record(ai, "HL2:SBPM:HL18:X") {
  field(DESC, "X Position")
  field(EGU, "mm")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C5 S11")
  field(SCAN, "I/O Intr")
# The priority determines what scan list we are being
# put on (see drvPadUdpComm.c)
  field(PRIO, "HIGH")
  field(FLNK, "HL2:SBPM:HL18:Y")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
  field(ASG,  "")
  field(TSE, "-2")
  info(autosaveFields, "ASLO LOLO LOW HIGH HIHI HHSV LLSV")
}

record(ai, "HL2:SBPM:HL18:Y") {
  field(DESC, "Y Position")
  field(EGU, "mm")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C5 S12")
  field(FLNK, "HL2:SBPM:HL18:TMIT")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
  field(ASG,  "")
  field(TSE, "-2")
  info(autosaveFields, "ASLO LOLO LOW HIGH HIHI HHSV LLSV")
}

record(ai, "HL2:SBPM:HL18:TMIT") {
  field(DESC, "Charge Estimate")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C5 S13")
  field(EGU, "Nel")
  field(PREC, "3")
  field(LOPR, "0")
  field(HOPR, "1E11")
# FLINK into BSA
  field(FLNK, "HL2:SBPM:HL18:EFX.PROC")
  field(ASG,  "")
  field(TSE, "-2")
  info(autosaveFields, "LOLO LOW HIGH HIHI HHSV LLSV ")
}


######################################
# HEAD of diagnostics processing chain
######################################

# leave RWAV in it's own lockset; don't FLNK
# to 'U' & friends
record(waveform, "HL2:SBPM:HL18:RWAV") {
  field(DESC, "Raw BPM Data")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP,  "#C5 S0")
  field(SCAN, "I/O Intr")
# use LOW or HIGH to end up on the 'diagnostic' 
# scan list (see drvPadUdpComm.c)
  field(PRIO, "LOW")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU,  "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
}

record(ai, "HL2:SBPM:HL18:U") {
  field(DESC, "Raw U Position")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C5 S8")
  field(SCAN, "I/O Intr")
# use LOW or HIGH to end up on the 'diagnostic' 
# scan list (see drvPadUdpComm.c)
  field(PRIO, "LOW")
  field(PREC, "5")
  field(EGU,  "mm")
  field(LOPR, "-0.7")
  field(HOPR, "+0.7")
  field(FLNK, "HL2:SBPM:HL18:V")
}

record(ai, "HL2:SBPM:HL18:V") {
  field(DESC, "Raw V Position")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C5 S9")
  field(SCAN, "Passive")
  field(PREC, "5")
  field(EGU,  "mm")
  field(LOPR, "-0.7")
  field(HOPR, "+0.7")
  field(FLNK, "HL2:SBPM:HL18:PINC")
}

record(ai, "HL2:SBPM:HL18:PINC") {
  field(DESC, "Pin Cushion Corr.")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C5 S10")
  field(SCAN, "Passive")
}

record(longin, "HL2:SBPM:HL18:RSTA") {
  field(DESC, "Status of Raw Processor")
  field(DTYP, "Bpm Raw Status")
  field(INP, "#C5S0")
  field(SCAN, "1 second")
  field(LOLO, "-1")
  field(HIHI, "+1")
  field(HHSV, "INVALID")
  field(LLSV, "INVALID")
  field(FLNK, "HL2:SBPM:HL18:RSTA_ALH")
}


record(calc, "HL2:SBPM:HL18:RSTA_ALH") {
  field(CALC, "A & B")
  field(INPA, "HL2:SBPM:HL18:RSTA")
  field(INPB, "0x30F")
  field(HIHI, "1")
  field(LOLO, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(SCAN, "Passive")
}

######################################
# Input/Parameteres
######################################

record(ao, "HL2:SBPM:HL18:PHI") {
  field(DESC, "Rot Angle")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(EGU, "deg")
  field(PREC, "1")
  field(LOPR, "-180")
  field(HOPR, "+180")
  field(FLNK, "HL2:SBPM:HL18:PHI_SEQ")
}

record(ao, "HL2:SBPM:HL18:PSI") {
  field(DESC, "Axis Sep. Angle")
  field(DTYP, "Soft Channel")
  field(VAL, "90")
  field(EGU, "deg")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "+180")
  field(FLNK, "HL2:SBPM:HL18:PSI_SEQ")
}

#record(dfanout, "HL2:SBPM:HL18:PCMM") {
#  field(DESC, "BPM Scale")
#  field(OUTA, "HL2:SBPM:HL18:USCL PP MS")
#  field(OUTB, "HL2:SBPM:HL18:VSCL PP MS")
#  field(VAL, "12")
#  field(EGU, "mm")
#  field(PREC, "4")
#  field(LOPR, "5")
#  field(HOPR, "15")
#  field(PINI, "YES")
#}

record(ao, "HL2:SBPM:HL18:UOFF") {
  field(DESC, "BPM U Offset")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(EGU, "mm")
  field(PREC, "4")
  field(LOPR, "-5")
  field(HOPR, "+5")
  field(FLNK, "HL2:SBPM:HL18:UOFF_SEQ")
}

record(ao, "HL2:SBPM:HL18:VOFF") {
  field(DESC, "BPM V Offset")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(EGU, "mm")
  field(PREC, "4")
  field(LOPR, "-5")
  field(HOPR, "+5")
  field(FLNK, "HL2:SBPM:HL18:VOFF_SEQ")
}

record(ao, "HL2:SBPM:HL18:USCL") {
  field(DESC, "BPM U Scale")
  field(DTYP, "Soft Channel")
  field(VAL,  "1")
  field(EGU, "mm")
  field(PREC, "4")
  field(FLNK, "HL2:SBPM:HL18:USCL_SEQ")
}

record(ao, "HL2:SBPM:HL18:VSCL") {
  field(DESC, "BPM V Scale")
  field(DTYP, "Soft Channel")
  field(VAL,  "1")
  field(EGU, "mm")
  field(PREC, "4")
  field(FLNK, "HL2:SBPM:HL18:VSCL_SEQ")
}


record(mbbo, "HL2:SBPM:HL18:ACCESS") {
  field(DESC, "BPM On Line")
  field(DTYP, "StreamSwitch")
  field(OUT, "#C5 S0")
  field(ZRVL, "1")
  field(ZRST, "Running")
  field(ZRSV, "NO_ALARM")
  field(ONVL, "1")
  field(ONST, "Maintenance")
  field(ONSV, "MINOR")
  field(TWVL, "1")
  field(TWST, "Test")
  field(TWSV, "MINOR")
  field(THVL, "0")
  field(THST, "OFFLINE")
  field(THSV, "MAJOR")
# set both, rval and val to get it right
# regardless of whether devsup does conversion
# or not.
  field(RVAL, "0")
  field(VAL,  "0")
  field(PINI, "YES")
  field(FLNK, "HL2:SBPM:HL18:SIMOFF")
  info(autosaveFields, "RVAL")
}

#
# Used by higher level software to determine if a PV is in feedback or not.
# May also be used by actuator (magnet and RF) IOC applications to 
# switch output records to "closed_loop" to prevent outside programs from
# changing setpoints when an actuator device is in feedback.
#
record(mbbo, "HL2:SBPM:HL18:FBCK")
{
  field(DESC, "Feedback State")
  field(PINI, "YES")
  field(OMSL, "supervisory")
  field(VAL,  "0")
  field(ZRVL, "0")
  field(ONVL, "1")
  field(TWVL, "2")
# Off - this device can be used in feedback but all feedback loops 
# using it are off.
  field(ZRST, "Off")
# On - this device is being used by one or more feedback loops.
  field(ONST, "On")
# Unavailable - this device is not used by any feedback loop.
  field(TWST, "Unavailable")
  info(autosaveFields, "VAL")
}

# Convenience record holding the MAD name
record(stringin, "HL2:SBPM:HL18:MADN") {
  field(DESC, "MAD Name")
  field(VAL, "SBPMHL18")
  field(PINI, "YES")
}

record(stringin, "SBPMHL18:NAME") {
  field(DESC, "BPM Name")
  field(VAL, "HL2:SBPM:HL18")
  field(PINI, "YES")
}

record(ai, "HL2:SBPM:HL18:X_SLOW") {
#alias("HL2:SBPM:HL18:X1H")
  field(DESC, "X snapshot for display")
  field(EGU, "mm")
  field(INP, "HL2:SBPM:HL18:X MS")
  field(FLNK, "HL2:SBPM:HL18:Y_SLOW")
  field(PREC, "4")
  field(SCAN, "1 second")
  field(LOPR, "-12")
  field(HOPR, "+12")
}

record(ai, "HL2:SBPM:HL18:Y_SLOW") {
#alias("HL2:SBPM:HL18:Y1H")
  field(DESC, "Y snapshot for display")
  field(EGU, "mm")
  field(INP, "HL2:SBPM:HL18:Y NPP MS")
  field(FLNK, "HL2:SBPM:HL18:TMIT_SLOW")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
}

record(ai, "HL2:SBPM:HL18:TMIT_SLOW") {
#alias("HL2:SBPM:HL18:TMIT1H")
  field(DESC, "TMIT snapshot for display")
  field(INP, "HL2:SBPM:HL18:TMIT NPP MS")
  field(EGU, "Nel")
  field(PREC, "3")
  field(LOPR, "0")
  field(HOPR, "1E11")
}

######################################
# Simulation Parameters + Control
######################################

# switch off simulation when going off-line
record(calcout, "HL2:SBPM:HL18:SIMOFF") {
  field(DESC, "Sim Off Propagator")
  field(INPA, "HL2:SBPM:HL18:ACCESS.RVAL")
  field(CALC, "A")
  field(OCAL, "0")
  field(OOPT, "When Zero")
  field(DOPT, "Use OCAL")
  field(OUT,  "HL2:SBPM:HL18:SIMC PP")
}

record(calcout, "HL2:SBPM:HL18:SIM") {
  field(DESC, "BPM Pos. Simulation")
  field(DTYP, "Strip Signal Simulator")
  field(OUT, "5")
#CALC & VAL unused; the real calculation is done
#        in device support. The reason this is a
#        calcout rather than sub is that we want
#        to use the OUT link...
  field(CALC, "A")
  field(INPA, "HL2:SBPM:HL18:USCL")
  field(INPL, "0")
}

# Switch simulation record HL2:SBPM:HL18:SIMCSEQ moved to
# bpmCavity.db.part and bpmStripl.db.part 

record(mbbo, "HL2:SBPM:HL18:SIMC") {
  field(DESC, "Stripl Sim Ctl")
  field(DTYP, "Raw Soft Channel")
  field(OUT,  "HL2:SBPM:HL18:SIMCSEQ.SELN PP")
  field(ZRST, "OFF")
  field(ZRVL, "0x0f")
  field(ONST, "ON")
  field(ONVL, "0x1c0")
  field(TWST, "SOFT")
  field(TWVL, "0x030")
  field(MASK, "-1")
  field(NOBT, "16")
  field(VAL,  "0")
  field(RVAL, "0x0f")
  field(PINI, "YES")
}

record(ao, "HL2:SBPM:HL18:XSIM") {
  field(DESC, "BPM X Pos. Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL18:SIM.B PP")
  field(VAL, "0.5")
  field(EGU, "mm")
  field(PINI, "YES")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
}

record(ao, "HL2:SBPM:HL18:YSIM") {
  field(DESC, "BPM Y Pos. Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL18:SIM.C PP")
  field(VAL, "0.")
  field(EGU, "mm")
  field(PINI, "YES")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
}

record(ao, "HL2:SBPM:HL18:QSIM") {
  field(DESC, "BPM Q Simul.")
  field(DTYP, "Raw Soft Channel")
  field(OUT, "HL2:SBPM:HL18:SIM.D PP")
  field(EGU, "Nel")
  field(ASLO, "6000")
#ESLO is used to add attenuation
  field(LINR, "LINEAR")
  field(VAL, "1E9")
  field(PINI, "YES")
  field(PREC, "4")
  field(LOPR, "0")
  field(HOPR, "1E11")
}

record(ao, "HL2:SBPM:HL18:ROTS") {
  field(DESC, "BPM Rot. Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL18:SIM.E PP")
  field(VAL, "0.")
  field(EGU, "deg")
  field(PINI, "YES")
  field(PREC, "1")
  field(LOPR, "-180")
}

record(ao, "HL2:SBPM:HL18:PSIS") {
  field(DESC, "BPM Angle. Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL18:SIM.F PP")
  field(VAL, "90")
  field(EGU, "deg")
  field(PINI, "YES")
  field(PREC, "1")
  field(LOPR, "0")
}

record(aao, "HL2:SBPM:HL18:DIGISIMW") {
  field(DESC, "VME Digi Sim. Waveform")
  field(DTYP, "VmeDigi Sim Wav")
  field(OUT,  "#C5 S0")
  field(FTVL, "SHORT")
  field(EGU,  "Counts")
  field(HOPR, "32678")
  field(LOPR, "-32768")
# 16384 samples/channel * 4 channels
  field(NELM, "65536")
  field(PINI, "NO")
}

#Used by model/database folks to verify BPM

record(ao, "HL2:SBPM:HL18:Z") {
  field(DESC, "Z Position")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

# MPS interface
record(bo, "HL2:SBPM:HL18:MPSBYP") {
  field(DESC, "MPS Bypass")
  field(DTYP, "BusAddress")
  field(OUT,  "#C0S2@bpmMPS+0,m32")
  field(MASK, "32")
  field(ZNAM, "BYPASSED")
  field(ONAM, "NOT_BYPASSED")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(VAL,  "0")
  field(PINI, "YES")
  field(ASG,  "")
  info(autosaveFields, "VAL")
}

record(bo, "HL2:SBPM:HL18:MPSLTBYP") {
  field(DESC, "MPS Bypass")
  field(DTYP, "BusAddress")
  field(OUT,  "#C1S2@bpmMPS+0,m32")
  field(MASK, "32")
  field(ZNAM, "BYPASSED")
  field(ONAM, "NOT_BYPASSED")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")
  field(VAL,  "0")
  field(PINI, "YES")
  field(ASG,  "")
  info(autosaveFields, "VAL")
}

record(calc, "HL2:SBPM:HL18:MPSIGNRCALC") {
  field(DESC, "MPS ignore if TMIT too low")
  field(CALC, "A<B")
  field(INPA, "HL2:SBPM:HL18:TMIT")
  field(INPB, "HL2:SBPM:HL18:T_MPS_THRES_L")
  field(HIHI, "1")
  field(HHSV, "MAJOR")
  field(ASG, "")
}

record(bi, "HL2:SBPM:HL18:MPSIGNORE") {
  field(DESC, "MPS ignore if TMIT too low")
  field(DTYP, "Raw Soft Channel")
  field(SCAN, "1 second")
  field(INP, "HL2:SBPM:HL18:MPSIGNRCALC PP")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "Not ignored")
  field(ONAM, "Ignored")
  field(PINI, "YES")
  field(ASG, "")
}

# Proxy records for users to set X.AOFF, Y.AOFF
# Placed CAS on X and Y for MPS 
# Feb 2010 - CAS has since been removed, but we'll keep 
# these proxy records as they're already in use

record(ao, "HL2:SBPM:HL18:XAOFF") {
  field(DESC, "X.AOFF val")
#  field(OUT, "HL2:SBPM:HL18:X.AOFF")
  field(PINI, "YES")
  field(EGU, "mm")
  field(PREC, "4")
  field(FLNK, "HL2:SBPM:HL18:XOFF")
  info(autosaveFields, "VAL")
}

record(ao, "HL2:SBPM:HL18:YAOFF") {
  field(DESC, "Y.AOFF val")
#  field(OUT, "HL2:SBPM:HL18:Y.AOFF")
  field(PINI, "YES")
  field(EGU, "mm")
  field(PREC, "4")
  field(FLNK, "HL2:SBPM:HL18:YOFF")
  info(autosaveFields, "VAL")
}

# Add CALC to allow users to maintain
# multiple offsets per plane per BPM

record(calcout, "HL2:SBPM:HL18:XOFF") {
  field(DESC, "Add X offsets")
  field(PREC, "4")
  field(CALC, "A+B+C+D")
  field(INPA, "HL2:SBPM:HL18:XAOFF")
# B-E reserved for undulator offsets
  field(INPB, "")
  field(INPC, "")
  field(INPD, "")
  field(INPE, "")
  field(EGU, "mm")
  field(OUT, "HL2:SBPM:HL18:X.AOFF")
  info(autosaveFields, "B C D E")
}

record(calcout, "HL2:SBPM:HL18:YOFF") {
  field(DESC, "Add Y offsets")
  field(PREC, "4")
  field(CALC, "A+B+C+D")
  field(INPA, "HL2:SBPM:HL18:YAOFF")
# B-E reserved for undulator offsets
  field(INPB, "")
  field(INPC, "")
  field(INPD, "")
  field(INPE, "")
  field(EGU, "mm")
  field(OUT, "HL2:SBPM:HL18:Y.AOFF")
  info(autosaveFields, "B C D E")
}


# Records to set MPS thresholds
record(ao, "HL2:SBPM:HL18:X_MPS_THRES_L") {
  field(DESC, "MPS X Threshold Lo")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C5 S0 @Lo")
  field(VAL,  "-1")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL2:SBPM:HL18:X_MPS_THRES_H") {
  field(DESC, "MPS X Threshold Hi")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C5 S0 @Hi")
  field(VAL,  "1")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL2:SBPM:HL18:Y_MPS_THRES_L") {
  field(DESC, "MPS Y Threshold Lo")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C5 S1 @Lo")
  field(VAL,  "-1")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL2:SBPM:HL18:Y_MPS_THRES_H") {
  field(DESC, "MPS Y Threshold Hi")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C5 S1 @Hi")
  field(VAL,  "1")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL2:SBPM:HL18:T_MPS_THRES_L") {
  field(DESC, "MPS TMIT Threshold Lo")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C5 S2 @Lo")
  field(VAL,  "9.375e7")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL2:SBPM:HL18:T_MPS_THRES_H") {
  field(DESC, "MPS TMIT Threshold Hi")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C5 S2 @Hi")
  field(VAL,  "+1.0E20")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}

record(bi, "HL2:SBPM:HL18:FNET") {
  field(DESC, "BPM data on FNET")
  field(VAL, "$(FN,undefined)")
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(PINI, "YES")
}

# Record to inform users that BPM
# needs TMIT and/or X/Y scale calibration
record(mbbo, "HL2:SBPM:HL18:CHK") {
  field(DESC, "Needs cal/iron")
  field(OMSL, "supervisory")
  field(VAL,  "0")
  field(ZRVL, "0")
  field(ONVL, "1")
  field(TWVL, "2")
  field(THVL, "3")
  field(ZRST, " ")
  field(ONST, "Calibrate")
  field(TWST, "Calibrate&iron")
  field(THST, "Iron")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MINOR")
  field(THSV, "MINOR")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

# Switch simulation record 
record(seq, "HL2:SBPM:HL18:SIMCSEQ") {
  field(DESC, "BPM Sim Ctl Seq")
  field(SELM, "Mask")
  field(SELN, "0")

  field(DO1,  "1")
  field(DO2,  "0")
  field(DO3,  "0")
  field(DO4,  "0") #Passive

#  field(DO5,  "7") # .5 second
  field(DO5,  "9") # .1 second
  field(DO6,  "2")
  field(DO7,  "1")
  field(DO8,  "10")
  field(DO9,  "0")

# LNK 1, 2, 8, 9 only relevant for PADs
# Default macro values are set for PADs; other
# architectures must pass in "" for lnk1 and lnk2
  field(LNK1, "")
  field(LNK2, "")
  field(LNK3, "HL2:SBPM:HL18:SIM.L     PP")
  field(LNK4, "HL2:SBPM:HL18:SIM.SCAN  PP")

  field(LNK5, "HL2:SBPM:HL18:SIM.SCAN  PP")
  field(LNK6, "HL2:SBPM:HL18:SIM.L     PP")
  field(LNK7, "HL2:SBPM:HL18:SIM.L     PP")
  field(LNK8, "")
  field(LNK9, "")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL18:UOFF_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL18:UOFF")
	field(DOL2, "HL2:SBPM:HL18:UOFF")
	field(DOL3, "HL2:SBPM:HL18:UOFF")
	field(DOL4, "HL2:SBPM:HL18:UOFF")
	field(DOL5, "HL2:SBPM:HL18:UOFF")
	field(DOL6, "HL2:SBPM:HL18:UOFF")
	field(DOL7, "HL2:SBPM:HL18:UOFF")
	field(DOL8, "HL2:SBPM:HL18:UOFF")
	field(DOL9, "HL2:SBPM:HL18:UOFF")
	field(DOLA, "HL2:SBPM:HL18:UOFF")
	field(LNK1, "HL2:SBPM:HL18:UOFF_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL18:UOFF_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL18:UOFF_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL18:UOFF_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL18:UOFF_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL18:UOFF_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL18:UOFF_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL18:UOFF_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL18:UOFF_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL18:UOFF_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL18:UOFF_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL18:UOFF_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "0")
	field(B,    "0")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "4")
	field(FLNK, "HL2:SBPM:HL18:UOFF_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL18:UOFF_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL18:UOFF_SEL")
	field(OUTA, "HL2:SBPM:HL18:U.AOFF CA")
	field(OUTB, "HL2:SBPM:HL18:UOFF PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL18:UOFF_CTRL")
{
	field(INPA, "HL2:SBPM:HL18:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL18:UOFF_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL18:VOFF_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL18:VOFF")
	field(DOL2, "HL2:SBPM:HL18:VOFF")
	field(DOL3, "HL2:SBPM:HL18:VOFF")
	field(DOL4, "HL2:SBPM:HL18:VOFF")
	field(DOL5, "HL2:SBPM:HL18:VOFF")
	field(DOL6, "HL2:SBPM:HL18:VOFF")
	field(DOL7, "HL2:SBPM:HL18:VOFF")
	field(DOL8, "HL2:SBPM:HL18:VOFF")
	field(DOL9, "HL2:SBPM:HL18:VOFF")
	field(DOLA, "HL2:SBPM:HL18:VOFF")
	field(LNK1, "HL2:SBPM:HL18:VOFF_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL18:VOFF_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL18:VOFF_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL18:VOFF_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL18:VOFF_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL18:VOFF_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL18:VOFF_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL18:VOFF_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL18:VOFF_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL18:VOFF_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL18:VOFF_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL18:VOFF_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "0")
	field(B,    "0")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "4")
	field(FLNK, "HL2:SBPM:HL18:VOFF_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL18:VOFF_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL18:VOFF_SEL")
	field(OUTA, "HL2:SBPM:HL18:V.AOFF CA")
	field(OUTB, "HL2:SBPM:HL18:VOFF PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL18:VOFF_CTRL")
{
	field(INPA, "HL2:SBPM:HL18:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL18:VOFF_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL18:USCL_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL18:USCL")
	field(DOL2, "HL2:SBPM:HL18:USCL")
	field(DOL3, "HL2:SBPM:HL18:USCL")
	field(DOL4, "HL2:SBPM:HL18:USCL")
	field(DOL5, "HL2:SBPM:HL18:USCL")
	field(DOL6, "HL2:SBPM:HL18:USCL")
	field(DOL7, "HL2:SBPM:HL18:USCL")
	field(DOL8, "HL2:SBPM:HL18:USCL")
	field(DOL9, "HL2:SBPM:HL18:USCL")
	field(DOLA, "HL2:SBPM:HL18:USCL")
	field(LNK1, "HL2:SBPM:HL18:USCL_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL18:USCL_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL18:USCL_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL18:USCL_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL18:USCL_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL18:USCL_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL18:USCL_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL18:USCL_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL18:USCL_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL18:USCL_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL18:USCL_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL18:USCL_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "1")
	field(B,    "1")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "4")
	field(FLNK, "HL2:SBPM:HL18:USCL_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL18:USCL_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL18:USCL_SEL")
	field(OUTA, "HL2:SBPM:HL18:U.ASLO CA")
	field(OUTB, "HL2:SBPM:HL18:USCL PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL18:USCL_CTRL")
{
	field(INPA, "HL2:SBPM:HL18:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL18:USCL_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL18:VSCL_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL18:VSCL")
	field(DOL2, "HL2:SBPM:HL18:VSCL")
	field(DOL3, "HL2:SBPM:HL18:VSCL")
	field(DOL4, "HL2:SBPM:HL18:VSCL")
	field(DOL5, "HL2:SBPM:HL18:VSCL")
	field(DOL6, "HL2:SBPM:HL18:VSCL")
	field(DOL7, "HL2:SBPM:HL18:VSCL")
	field(DOL8, "HL2:SBPM:HL18:VSCL")
	field(DOL9, "HL2:SBPM:HL18:VSCL")
	field(DOLA, "HL2:SBPM:HL18:VSCL")
	field(LNK1, "HL2:SBPM:HL18:VSCL_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL18:VSCL_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL18:VSCL_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL18:VSCL_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL18:VSCL_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL18:VSCL_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL18:VSCL_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL18:VSCL_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL18:VSCL_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL18:VSCL_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL18:VSCL_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL18:VSCL_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "1")
	field(B,    "1")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "4")
	field(FLNK, "HL2:SBPM:HL18:VSCL_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL18:VSCL_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL18:VSCL_SEL")
	field(OUTA, "HL2:SBPM:HL18:V.ASLO CA")
	field(OUTB, "HL2:SBPM:HL18:VSCL PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL18:VSCL_CTRL")
{
	field(INPA, "HL2:SBPM:HL18:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL18:VSCL_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL18:PHI_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL18:PHI")
	field(DOL2, "HL2:SBPM:HL18:PHI")
	field(DOL3, "HL2:SBPM:HL18:PHI")
	field(DOL4, "HL2:SBPM:HL18:PHI")
	field(DOL5, "HL2:SBPM:HL18:PHI")
	field(DOL6, "HL2:SBPM:HL18:PHI")
	field(DOL7, "HL2:SBPM:HL18:PHI")
	field(DOL8, "HL2:SBPM:HL18:PHI")
	field(DOL9, "HL2:SBPM:HL18:PHI")
	field(DOLA, "HL2:SBPM:HL18:PHI")
	field(LNK1, "HL2:SBPM:HL18:PHI_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL18:PHI_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL18:PHI_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL18:PHI_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL18:PHI_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL18:PHI_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL18:PHI_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL18:PHI_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL18:PHI_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL18:PHI_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL18:PHI_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL18:PHI_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "0")
	field(B,    "0")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "1")
	field(FLNK, "HL2:SBPM:HL18:PHI_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL18:PHI_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL18:PHI_SEL")
	field(OUTA, "HL2:SBPM:HL18:CALC.E CA")
	field(OUTB, "HL2:SBPM:HL18:PHI PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL18:PHI_CTRL")
{
	field(INPA, "HL2:SBPM:HL18:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL18:PHI_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL18:PSI_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL18:PSI")
	field(DOL2, "HL2:SBPM:HL18:PSI")
	field(DOL3, "HL2:SBPM:HL18:PSI")
	field(DOL4, "HL2:SBPM:HL18:PSI")
	field(DOL5, "HL2:SBPM:HL18:PSI")
	field(DOL6, "HL2:SBPM:HL18:PSI")
	field(DOL7, "HL2:SBPM:HL18:PSI")
	field(DOL8, "HL2:SBPM:HL18:PSI")
	field(DOL9, "HL2:SBPM:HL18:PSI")
	field(DOLA, "HL2:SBPM:HL18:PSI")
	field(LNK1, "HL2:SBPM:HL18:PSI_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL18:PSI_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL18:PSI_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL18:PSI_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL18:PSI_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL18:PSI_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL18:PSI_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL18:PSI_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL18:PSI_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL18:PSI_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL18:PSI_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL18:PSI_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "90")
	field(B,    "90")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "1")
	field(FLNK, "HL2:SBPM:HL18:PSI_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL18:PSI_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL18:PSI_SEL")
	field(OUTA, "HL2:SBPM:HL18:CALC.F CA")
	field(OUTB, "HL2:SBPM:HL18:PSI PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL18:PSI_CTRL")
{
	field(INPA, "HL2:SBPM:HL18:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL18:PSI_SEL.L PP")
}
record(longout, "HL2:SBPM:HL18:PARMSEL") {
	field(VAL, "0")
	field(PINI, "YES")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


# per BPM database for stripline BPMs

##############################################
# This is the head of the main processing chain
# that runs at the highest priority.
##############################################

#############################################
# This is the head of the processing chain for
# diagnostics.
##############################################
record(ai, "HL2:SBPM:HL19:GRN") {
  field(DESC, "GRN Strip Amplitude")
  field(DTYP, "Raw Bpm Signal")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "#C6 S0")
  field(EGU, "raw")
#TODO set HOPR/LOPR, alarm limits
  field(SCAN, "I/O Intr")
# The priority determines what scan list we are being
# put on (see drvPadUdpComm.c)
  field(PRIO, "LOW")
  field(FLNK, "HL2:SBPM:HL19:RED")
# HOPR for the energy algorithm is determined as follows:
#
#                      inf        inf
#  1) Fourier relation / h^2 dt = / |H|^2 df = 2 B
#                     0         -inf
#
#  1a) It can be shown that the maximum of the impuls response
#      ha is ~ 2 B
#                               
#  2) The digitizer produces the numbers
#
#     Ai = 2^s (hi/ha)
#
#     where ha is the maximum of the impuls response
#     and 2^s is a scale factor.
#     
#  3) 'Energy algorithm' calculates S = sum( Ai^2 )
#
#                                                     inf
#  4) S = (2^s / ha)^2 sum(hi^2) = K sum(hi^2) Dt ~ K / h^2 dt
#                                                    0
#
#     with K = (2^s / ha)^2 fs
#
#  5) From 4) and 1a) ->  S ~ K ha and therefore
#
#  6) S = 2^(2s) fs/ha = 2^(2s) fs/(2 B)
#
#  7) The strip signals are sqrt(S); hence HOPR is about
#
#     HOPR ~ 2^s  sqrt( fs/2/B )
#
#     with 2^s = 32768, fs=120MHz, B=10MHz it follows
#     that HOPR ~ 1E5; we add some margin...
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL19:RED") {
  field(DESC, "RED Strip Amplitude")
  field(DTYP, "Raw Bpm Signal")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "#C6 S1")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(FLNK, "HL2:SBPM:HL19:BLU")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL19:BLU") {
  field(DESC, "BLU Strip Amplitude")
  field(DTYP, "Raw Bpm Signal")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "#C6 S2")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(FLNK, "HL2:SBPM:HL19:YLO")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL19:YLO") {
  field(DESC, "YLO Strip Amplitude")
  field(DTYP, "Raw Bpm Signal")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "#C6 S3")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

##############################################
# Slowly-scanned diagnostics
##############################################

#
record(waveform, "HL2:SBPM:HL19:REDW") {
  field(DESC, "Raw CAL RED Data")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP, "#C6 S1")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "1 second")
}

record(waveform, "HL2:SBPM:HL19:GRNW") {
  field(DESC, "Raw CAL GRN Data")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP, "#C6 S2")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "1 second")
}

record(waveform, "HL2:SBPM:HL19:RAWDBG") {
  field(DESC, "Raw BEAM Dbg")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
# do not 'wbscan' for now since e.g., an underrange
# condition on the real signal can happen.
  field(INP, "#C6 S7")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "Passive")
}

record(waveform, "HL2:SBPM:HL19:REDDBG") {
  field(DESC, "Raw CAL RED Dbg")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP, "#C6 S8 @wbscan")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "Passive")
}

record(waveform, "HL2:SBPM:HL19:GRNDBG") {
  field(DESC, "Raw CAL GRN Dbg")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP, "#C6 S9 @wbscan")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "Passive")
}

record(ai, "HL2:SBPM:HL19:GRUV") {
  field(DESC, "CAL Gain GRN/RED")
  field(DTYP, "Raw Stripl Calp")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C6 S0")
  field(SCAN, "10 second")
  field(PREC, "4")
  field(LOPR, "0.5")
  field(HOPR, "1.5")
}

record(ai, "HL2:SBPM:HL19:GRU") {
  field(DESC, "CAL Gain GRN/BLU")
  field(DTYP, "Raw Stripl Calp")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C6 S1")
  field(SCAN, "10 second")
  field(PREC, "4")
  field(LOPR, "0.5")
  field(HOPR, "1.5")
  info(autosaveFields, "ASLO")
}

record(ai, "HL2:SBPM:HL19:GRV") {
  field(DESC, "CAL Gain RED/YLO")
  field(DTYP, "Raw Stripl Calp")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C6 S2")
  field(SCAN, "10 second")
  field(PREC, "4")
  field(LOPR, "0.5")
  field(HOPR, "1.5")
  info(autosaveFields, "ASLO")
}

record(ai, "HL2:SBPM:HL19:TGRN") {
  field(DESC, "Green arrival time")
  field(DTYP, "Raw Bpm Signal")
  field(EGU, "ADC Clocks")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C6 S4")
  field(SCAN, "10 second")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "128")
  field(LOLO, "5")
  field(LOW, "8")
  field(HIGH, "60")
  field(HIHI, "70")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
  field(HSV, "MINOR")
  field(HHSV, "MAJOR")
}

record(ai, "HL2:SBPM:HL19:TRED") {
  field(DESC, "Red arrival time")
  field(DTYP, "Raw Bpm Signal")
  field(EGU, "ADC Clocks")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C6 S5")
  field(SCAN, "10 second")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "128")
  field(LOLO, "5")
  field(LOW, "8")
  field(HIGH, "60")
  field(HIHI, "70")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
  field(HSV, "MINOR")
  field(HHSV, "MAJOR")
}

record(ai, "HL2:SBPM:HL19:TBLU") {
  field(DESC, "Blue arrival time")
  field(DTYP, "Raw Bpm Signal")
  field(EGU, "ADC Clocks")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C6 S6")
  field(SCAN, "10 second")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "128")
  field(LOLO, "5")
  field(LOW, "8")
  field(HIGH, "60")
  field(HIHI, "70")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
  field(HSV, "MINOR")
  field(HHSV, "MAJOR")
}

record(ai, "HL2:SBPM:HL19:TYLO") {
  field(DESC, "Yellow arrival time")
  field(DTYP, "Raw Bpm Signal")
  field(EGU, "ADC Clocks")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C6 S7")
  field(SCAN, "10 second")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "128")
  field(LOLO, "5")
  field(LOW, "8")
  field(HIGH, "60")
  field(HIHI, "70")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
  field(HSV, "MINOR")
  field(HHSV, "MAJOR")
}

record(ao, "HL2:SBPM:HL19:PINC_ADJ") {
  field(DESC, "Adjust Pinc. Corr.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL19:CALC.K PP MS")
  field(VAL, "0")
  field(DRVL, "0")
  field(DRVH, "2")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

# QSCL setting:
#
# Q: charge
# Z: impedance
# F: form factor: phi/(2 pi) sin(2 pi f l/c)
#
# Signal =  Q Z F G h(t) = A h(t)  [A] = Vs
#
#                  inf              inf
# Energy =  A^2   / h^2(t) dt = A^2 / |H(w)|^2 dw/2/pi = A^2 B
#                0                 0
#                        
# Measured energy = Sum{ (Vp/32768 * xi)^2 } / fs = S / fs ~ Energy
#
# -> A^2 B = S/fs
#
# With T = sqrt( Sum{ xi^2 } )
#
#    A = sqrt(S)/sqrt(B*fs) = T/sqrt(B*fs) Vp/32768
#
#                      T/32768 Vp
#    Q = A/F/G/Z = -----------------
#                   F G Z sqrt(B*fs)
#
# Vp = { 1.5Vpp/2 (PGA=1) or 2.25Vpp/2 (PGA=0) } / 2 (transformer)
#
# I believe PGA is off (-> Vp ~ .56V)
#
# Z  = 50
#
# G: (calibration uses GRN/BLU -> signal should have the
#    level of the grn/red channels with the additional switch)
#
# Block diagram / parts / gain:
#
# [filt]    [Att1]    [Amp1]   [Att2]    [BPF]      [Amp2]    [pad] [Amp3]   [switch]
# f-17520  hmc540lp3  SBF-5089 hmc540lp3 MBP-140-6-4 SBF-4089  PAT-0 SBF-4089 HMC-197
#
#  -2dB*    -1dB       20dB     -1dB     -4.5         14.8dB   0dB   14.8dB   -0.4dB
#
# *: 1st filter ATT is a wild guess.
#  BPF loss (RLC Catalog, pp.55): (L (nsect+.5) / (% of 3dB BW) + .2) dB
#  with L ~6.2  10MHz/fc=140Mhz filter-> 4.5
#
#  -> Gtot ~ 40.7dB
#
#  subtract cable loss (2dB); Gtot = 86
# 
#                      T/32768 Vp            .56V/32768
#    Q = A/F/G/Z = ----------------- = T/F  ------------------------
#                   F G Z sqrt(B*fs)        86*50*sqrt(10*140)Mhz
#
#      = T/F = 1.06E-7/F nC
#
#    F for a 7% coverage, 4" BPM at 140MHz   .07 sin(2*pi*140e6 4*.0254/3e8)
#      = .021
#
#      => 1.06E-7/.021 nC = 5E-6 nC
#
# (Faraday cup measurement -> (3600/44)^-1 1e-4 -> 1.22E-6
#
record(ao, "HL2:SBPM:HL19:QSCL") {
  field(DESC, "TMIT/Charge Scale")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL19:QSCA.A PP MS")
# 5.0E-6 / 1.6E-10 [nC/e-]
  field(VAL, "31250")
  field(EGU, "Nel")
  field(PREC, "3")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

# Adjust TMIT scale for AFE attenuation
record(calcout, "HL2:SBPM:HL19:QSCA") {
  field(DESC, "TMIT ATT Adj. Scale")
  field(INPB, "HL2:SBPM:HL19:ATT1 CP")
  field(INPC, "HL2:SBPM:HL19:ATT2 CP")
  field(CALC, "A*10^((B+C+D)/20)")
# use CA link to deposit into TMIT.ASLO so
# that TMIT is not forced into linkset
# of this record
  field(OUT, "HL2:SBPM:HL19:TMIT.ASLO CA")
  field(EGU, "Nel")
  field(PREC, "3")
  info(autosaveFields, "D")
}

record(ao,    "HL2:SBPM:HL19:ATT1SIMP") {
	field(DESC, "ATT1 Propagator")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL2:SBPM:HL19:ATT1   CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL2:SBPM:HL19:ASIM.A PP")
  	field(IVOA, "Set output to IVOV")
	field(IVOV, "0")
	field(EGU,  "dB")
}

record(ao,    "HL2:SBPM:HL19:ATT2SIMP") {
	field(DESC, "ATT2 Propagator")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL2:SBPM:HL19:ATT2   CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL2:SBPM:HL19:ASIM.C PP")
  	field(IVOA, "Set output to IVOV")
	field(IVOV, "0")
	field(EGU,  "dB")
}

# Attenuate charge either by
# real attenuator settings or
# by fake ones.
# If B, C >= 0 then their
# values will be used instead
# of ATT1, ATT2
record(calcout, "HL2:SBPM:HL19:ASIM") {
  field(DESC, "Q Simul Attenuator")
  field(DTYP, "Soft Channel")
  field(OUT,  "HL2:SBPM:HL19:QSIM.ESLO PP")
# ATT1SIM puts value into A
# set to -1 to use real attenuator settings
# and >=0 to use B instead
  field(B,    "-1")
# ATT2SIM puts value into C
# set to -1 to use real attenuator settings
# and >=0 to use D instead
  field(D,    "-1")
  field(CALC, "10^(((B>=0?B:A)+(D>=0?D:C))/20)")
  field(PINI, "YES")
}

record(ao, "HL2:SBPM:HL19:WSIM") {
  field(DESC, "BPM W Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL19:SIM.G PP")
  field(VAL, "0.07")
  field(EGU, "%")
  field(PINI, "YES")
  field(PREC, "3")
  field(LOPR, "0")
  field(HOPR, "0.25")
}


record(sel, "HL2:SBPM:HL19:STA") {
  field(DESC, "Status Summary")
  field(SELM, "High Signal")
  field(INPA, "HL2:SBPM:HL19:RSTA.SEVR MS NPP")
  field(INPB, "HL2:SBPM:HL19:TMIT.SEVR MS NPP")
  field(INPC, "HL2:SBPM:HL19:Y.SEVR    MS NPP")
  field(INPD, "HL2:SBPM:HL19:X.SEVR    MS NPP")
  field(INPE, "HL2:SBPM:HL19:TGRN.SEVR MS NPP")
  field(INPF, "HL2:SBPM:HL19:TRED.SEVR MS NPP")
  field(INPG, "HL2:SBPM:HL19:TBLU.SEVR MS NPP")
  field(INPH, "HL2:SBPM:HL19:TYLO.SEVR MS NPP")
  field(INPI, "HL2:SBPM:HL19:GRU.SEVR  MS NPP")
  field(INPJ, "HL2:SBPM:HL19:GRV.SEVR  MS NPP")
  field(SCAN, "1 second")
}

# This record really belongs on the
# PAD IOC. We keep them here however
# so we can save/restore. It is more
# confusing but shouldn't matter from
# an efficiency standpoint (they are
# rarely changed).
record(longout, "HL2:SBPM:HL19:ATTO") {
  field(DESC, "AFE Tot. Att. Offset")
# fetched via inlink
#field(OUT,  "HL2:SBPM:HL19:ATTC.B PP")
  field(DRVL, "-10")
  field(DRVH, "30")
  field(LOPR, "-10")
  field(HOPR, "30")
  field(EGU, "dB")
  field(VAL, "0")
  field(PINI, "YES")
  info(autosaveFields, "VAL DRVH HOPR DRVL LOPR")
}

# This record really belongs on the
# PAD IOC. We keep them here however
# so we can save/restore. It is more
# confusing but shouldn't matter from
# an efficiency standpoint (they are
# rarely changed).
record(longout, "HL2:SBPM:HL19:CLAO") {
  field(DESC, "AFE Cal. Att. Offset")
# fetched via inlink
#field(OUT,  "HL2:SBPM:HL19:ATTC.C PP")
  field(DRVL, "-20")
  field(DRVH, "20")
  field(LOPR, "-20")
  field(HOPR, "20")
  field(EGU, "dB")
  field(VAL, "40")
  field(PINI, "YES")
  info(autosaveFields, "VAL DRVH HOPR DRVL LOPR")
}

record(calc, "HL2:SBPM:HL19:STA_ALH") {
  field(DESC, "Status Summary")
  field(SCAN, "1 second")
  field(CALC, "0")
  field(INPA, "HL2:SBPM:HL19:RSTA_ALH.SEVR MS NPP")
  field(INPB, "HL2:SBPM:HL19:GRU.SEVR  MS NPP")
  field(INPC, "HL2:SBPM:HL19:GRV.SEVR  MS NPP")
  field(INPD, "HL2:SBPM:HL19:CHK.SEVR MS NPP")
}

# snapshot PV for the bpm values display
record(ai, "HL2:SBPM:HL19:GRN_SLOW") {
  field(DESC, "GRN snapshot for display")
  field(INP, "HL2:SBPM:HL19:GRN NPP MS")
  field(EGU, "raw")
  field(SCAN, "1 second")
  field(FLNK, "HL2:SBPM:HL19:RED_SLOW")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL19:RED_SLOW") {
  field(DESC, "RED snapshot for display")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "HL2:SBPM:HL19:RED NPP MS")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(FLNK, "HL2:SBPM:HL19:BLU_SLOW")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL19:BLU_SLOW") {
  field(DESC, "BLU snapshot for display")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "HL2:SBPM:HL19:BLU NPP MS")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(FLNK, "HL2:SBPM:HL19:YLO_SLOW")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL19:YLO_SLOW") {
  field(DESC, "YLO snapshot for display")
  field(INP, "HL2:SBPM:HL19:YLO NPP MS")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(sub, "HL2:SBPM:HL19:CALC") {
  field(SNAM, "drvBpmBvectSetupSub")
# E: phi F: psi
# BPM channel number in L
  field(INPL, "6")
  field(SCAN, "Passive")
}

record(bo, "HL2:SBPM:HL19:PINC_ENA") {
  field(DESC, "Simple Pincushion Alg")
  field(DTYP, "BusAddress")
  field(OUT,  "#C0S2@drvBpmStriplPincEna,m32")
  field(MASK, "64")
  field(ZNAM, "DISABLED")
  field(ONAM, "ENABLED")
  field(VAL,  "0")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

record(ao, "HL2:SBPM:HL19:UDR_THRES") {
  field(DESC, "Detection Underrange Threshold")
  field(DTYP, "Bpm Parameters")
  field(OUT,  "#C6S0")
  field(EGU,  "ADC Ticks")
  field(DOL,  "45.26")
  field(PINI, "YES")
  field(DRVL, "0")
  field(DRVH, "32767")
  info(autosaveFields, "VAL")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


# per BPM database for stripline BPMs

######################################
# HEAD of main processing chain
######################################

record(ai, "HL2:SBPM:HL19:X") {
  field(DESC, "X Position")
  field(EGU, "mm")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C6 S11")
  field(SCAN, "I/O Intr")
# The priority determines what scan list we are being
# put on (see drvPadUdpComm.c)
  field(PRIO, "HIGH")
  field(FLNK, "HL2:SBPM:HL19:Y")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
  field(ASG,  "")
  field(TSE, "-2")
  info(autosaveFields, "ASLO LOLO LOW HIGH HIHI HHSV LLSV")
}

record(ai, "HL2:SBPM:HL19:Y") {
  field(DESC, "Y Position")
  field(EGU, "mm")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C6 S12")
  field(FLNK, "HL2:SBPM:HL19:TMIT")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
  field(ASG,  "")
  field(TSE, "-2")
  info(autosaveFields, "ASLO LOLO LOW HIGH HIHI HHSV LLSV")
}

record(ai, "HL2:SBPM:HL19:TMIT") {
  field(DESC, "Charge Estimate")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C6 S13")
  field(EGU, "Nel")
  field(PREC, "3")
  field(LOPR, "0")
  field(HOPR, "1E11")
# FLINK into BSA
  field(FLNK, "HL2:SBPM:HL19:EFX.PROC")
  field(ASG,  "")
  field(TSE, "-2")
  info(autosaveFields, "LOLO LOW HIGH HIHI HHSV LLSV ")
}


######################################
# HEAD of diagnostics processing chain
######################################

# leave RWAV in it's own lockset; don't FLNK
# to 'U' & friends
record(waveform, "HL2:SBPM:HL19:RWAV") {
  field(DESC, "Raw BPM Data")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP,  "#C6 S0")
  field(SCAN, "I/O Intr")
# use LOW or HIGH to end up on the 'diagnostic' 
# scan list (see drvPadUdpComm.c)
  field(PRIO, "LOW")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU,  "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
}

record(ai, "HL2:SBPM:HL19:U") {
  field(DESC, "Raw U Position")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C6 S8")
  field(SCAN, "I/O Intr")
# use LOW or HIGH to end up on the 'diagnostic' 
# scan list (see drvPadUdpComm.c)
  field(PRIO, "LOW")
  field(PREC, "5")
  field(EGU,  "mm")
  field(LOPR, "-0.7")
  field(HOPR, "+0.7")
  field(FLNK, "HL2:SBPM:HL19:V")
}

record(ai, "HL2:SBPM:HL19:V") {
  field(DESC, "Raw V Position")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C6 S9")
  field(SCAN, "Passive")
  field(PREC, "5")
  field(EGU,  "mm")
  field(LOPR, "-0.7")
  field(HOPR, "+0.7")
  field(FLNK, "HL2:SBPM:HL19:PINC")
}

record(ai, "HL2:SBPM:HL19:PINC") {
  field(DESC, "Pin Cushion Corr.")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C6 S10")
  field(SCAN, "Passive")
}

record(longin, "HL2:SBPM:HL19:RSTA") {
  field(DESC, "Status of Raw Processor")
  field(DTYP, "Bpm Raw Status")
  field(INP, "#C6S0")
  field(SCAN, "1 second")
  field(LOLO, "-1")
  field(HIHI, "+1")
  field(HHSV, "INVALID")
  field(LLSV, "INVALID")
  field(FLNK, "HL2:SBPM:HL19:RSTA_ALH")
}


record(calc, "HL2:SBPM:HL19:RSTA_ALH") {
  field(CALC, "A & B")
  field(INPA, "HL2:SBPM:HL19:RSTA")
  field(INPB, "0x30F")
  field(HIHI, "1")
  field(LOLO, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(SCAN, "Passive")
}

######################################
# Input/Parameteres
######################################

record(ao, "HL2:SBPM:HL19:PHI") {
  field(DESC, "Rot Angle")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(EGU, "deg")
  field(PREC, "1")
  field(LOPR, "-180")
  field(HOPR, "+180")
  field(FLNK, "HL2:SBPM:HL19:PHI_SEQ")
}

record(ao, "HL2:SBPM:HL19:PSI") {
  field(DESC, "Axis Sep. Angle")
  field(DTYP, "Soft Channel")
  field(VAL, "90")
  field(EGU, "deg")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "+180")
  field(FLNK, "HL2:SBPM:HL19:PSI_SEQ")
}

#record(dfanout, "HL2:SBPM:HL19:PCMM") {
#  field(DESC, "BPM Scale")
#  field(OUTA, "HL2:SBPM:HL19:USCL PP MS")
#  field(OUTB, "HL2:SBPM:HL19:VSCL PP MS")
#  field(VAL, "12")
#  field(EGU, "mm")
#  field(PREC, "4")
#  field(LOPR, "5")
#  field(HOPR, "15")
#  field(PINI, "YES")
#}

record(ao, "HL2:SBPM:HL19:UOFF") {
  field(DESC, "BPM U Offset")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(EGU, "mm")
  field(PREC, "4")
  field(LOPR, "-5")
  field(HOPR, "+5")
  field(FLNK, "HL2:SBPM:HL19:UOFF_SEQ")
}

record(ao, "HL2:SBPM:HL19:VOFF") {
  field(DESC, "BPM V Offset")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(EGU, "mm")
  field(PREC, "4")
  field(LOPR, "-5")
  field(HOPR, "+5")
  field(FLNK, "HL2:SBPM:HL19:VOFF_SEQ")
}

record(ao, "HL2:SBPM:HL19:USCL") {
  field(DESC, "BPM U Scale")
  field(DTYP, "Soft Channel")
  field(VAL,  "1")
  field(EGU, "mm")
  field(PREC, "4")
  field(FLNK, "HL2:SBPM:HL19:USCL_SEQ")
}

record(ao, "HL2:SBPM:HL19:VSCL") {
  field(DESC, "BPM V Scale")
  field(DTYP, "Soft Channel")
  field(VAL,  "1")
  field(EGU, "mm")
  field(PREC, "4")
  field(FLNK, "HL2:SBPM:HL19:VSCL_SEQ")
}


record(mbbo, "HL2:SBPM:HL19:ACCESS") {
  field(DESC, "BPM On Line")
  field(DTYP, "StreamSwitch")
  field(OUT, "#C6 S0")
  field(ZRVL, "1")
  field(ZRST, "Running")
  field(ZRSV, "NO_ALARM")
  field(ONVL, "1")
  field(ONST, "Maintenance")
  field(ONSV, "MINOR")
  field(TWVL, "1")
  field(TWST, "Test")
  field(TWSV, "MINOR")
  field(THVL, "0")
  field(THST, "OFFLINE")
  field(THSV, "MAJOR")
# set both, rval and val to get it right
# regardless of whether devsup does conversion
# or not.
  field(RVAL, "0")
  field(VAL,  "0")
  field(PINI, "YES")
  field(FLNK, "HL2:SBPM:HL19:SIMOFF")
  info(autosaveFields, "RVAL")
}

#
# Used by higher level software to determine if a PV is in feedback or not.
# May also be used by actuator (magnet and RF) IOC applications to 
# switch output records to "closed_loop" to prevent outside programs from
# changing setpoints when an actuator device is in feedback.
#
record(mbbo, "HL2:SBPM:HL19:FBCK")
{
  field(DESC, "Feedback State")
  field(PINI, "YES")
  field(OMSL, "supervisory")
  field(VAL,  "0")
  field(ZRVL, "0")
  field(ONVL, "1")
  field(TWVL, "2")
# Off - this device can be used in feedback but all feedback loops 
# using it are off.
  field(ZRST, "Off")
# On - this device is being used by one or more feedback loops.
  field(ONST, "On")
# Unavailable - this device is not used by any feedback loop.
  field(TWST, "Unavailable")
  info(autosaveFields, "VAL")
}

# Convenience record holding the MAD name
record(stringin, "HL2:SBPM:HL19:MADN") {
  field(DESC, "MAD Name")
  field(VAL, "SBPMHL19")
  field(PINI, "YES")
}

record(stringin, "SBPMHL19:NAME") {
  field(DESC, "BPM Name")
  field(VAL, "HL2:SBPM:HL19")
  field(PINI, "YES")
}

record(ai, "HL2:SBPM:HL19:X_SLOW") {
#alias("HL2:SBPM:HL19:X1H")
  field(DESC, "X snapshot for display")
  field(EGU, "mm")
  field(INP, "HL2:SBPM:HL19:X MS")
  field(FLNK, "HL2:SBPM:HL19:Y_SLOW")
  field(PREC, "4")
  field(SCAN, "1 second")
  field(LOPR, "-12")
  field(HOPR, "+12")
}

record(ai, "HL2:SBPM:HL19:Y_SLOW") {
#alias("HL2:SBPM:HL19:Y1H")
  field(DESC, "Y snapshot for display")
  field(EGU, "mm")
  field(INP, "HL2:SBPM:HL19:Y NPP MS")
  field(FLNK, "HL2:SBPM:HL19:TMIT_SLOW")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
}

record(ai, "HL2:SBPM:HL19:TMIT_SLOW") {
#alias("HL2:SBPM:HL19:TMIT1H")
  field(DESC, "TMIT snapshot for display")
  field(INP, "HL2:SBPM:HL19:TMIT NPP MS")
  field(EGU, "Nel")
  field(PREC, "3")
  field(LOPR, "0")
  field(HOPR, "1E11")
}

######################################
# Simulation Parameters + Control
######################################

# switch off simulation when going off-line
record(calcout, "HL2:SBPM:HL19:SIMOFF") {
  field(DESC, "Sim Off Propagator")
  field(INPA, "HL2:SBPM:HL19:ACCESS.RVAL")
  field(CALC, "A")
  field(OCAL, "0")
  field(OOPT, "When Zero")
  field(DOPT, "Use OCAL")
  field(OUT,  "HL2:SBPM:HL19:SIMC PP")
}

record(calcout, "HL2:SBPM:HL19:SIM") {
  field(DESC, "BPM Pos. Simulation")
  field(DTYP, "Strip Signal Simulator")
  field(OUT, "6")
#CALC & VAL unused; the real calculation is done
#        in device support. The reason this is a
#        calcout rather than sub is that we want
#        to use the OUT link...
  field(CALC, "A")
  field(INPA, "HL2:SBPM:HL19:USCL")
  field(INPL, "0")
}

# Switch simulation record HL2:SBPM:HL19:SIMCSEQ moved to
# bpmCavity.db.part and bpmStripl.db.part 

record(mbbo, "HL2:SBPM:HL19:SIMC") {
  field(DESC, "Stripl Sim Ctl")
  field(DTYP, "Raw Soft Channel")
  field(OUT,  "HL2:SBPM:HL19:SIMCSEQ.SELN PP")
  field(ZRST, "OFF")
  field(ZRVL, "0x0f")
  field(ONST, "ON")
  field(ONVL, "0x1c0")
  field(TWST, "SOFT")
  field(TWVL, "0x030")
  field(MASK, "-1")
  field(NOBT, "16")
  field(VAL,  "0")
  field(RVAL, "0x0f")
  field(PINI, "YES")
}

record(ao, "HL2:SBPM:HL19:XSIM") {
  field(DESC, "BPM X Pos. Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL19:SIM.B PP")
  field(VAL, "0.5")
  field(EGU, "mm")
  field(PINI, "YES")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
}

record(ao, "HL2:SBPM:HL19:YSIM") {
  field(DESC, "BPM Y Pos. Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL19:SIM.C PP")
  field(VAL, "0.")
  field(EGU, "mm")
  field(PINI, "YES")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
}

record(ao, "HL2:SBPM:HL19:QSIM") {
  field(DESC, "BPM Q Simul.")
  field(DTYP, "Raw Soft Channel")
  field(OUT, "HL2:SBPM:HL19:SIM.D PP")
  field(EGU, "Nel")
  field(ASLO, "6000")
#ESLO is used to add attenuation
  field(LINR, "LINEAR")
  field(VAL, "1E9")
  field(PINI, "YES")
  field(PREC, "4")
  field(LOPR, "0")
  field(HOPR, "1E11")
}

record(ao, "HL2:SBPM:HL19:ROTS") {
  field(DESC, "BPM Rot. Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL19:SIM.E PP")
  field(VAL, "0.")
  field(EGU, "deg")
  field(PINI, "YES")
  field(PREC, "1")
  field(LOPR, "-180")
}

record(ao, "HL2:SBPM:HL19:PSIS") {
  field(DESC, "BPM Angle. Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL19:SIM.F PP")
  field(VAL, "90")
  field(EGU, "deg")
  field(PINI, "YES")
  field(PREC, "1")
  field(LOPR, "0")
}

record(aao, "HL2:SBPM:HL19:DIGISIMW") {
  field(DESC, "VME Digi Sim. Waveform")
  field(DTYP, "VmeDigi Sim Wav")
  field(OUT,  "#C6 S0")
  field(FTVL, "SHORT")
  field(EGU,  "Counts")
  field(HOPR, "32678")
  field(LOPR, "-32768")
# 16384 samples/channel * 4 channels
  field(NELM, "65536")
  field(PINI, "NO")
}

#Used by model/database folks to verify BPM

record(ao, "HL2:SBPM:HL19:Z") {
  field(DESC, "Z Position")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

# MPS interface
record(bo, "HL2:SBPM:HL19:MPSBYP") {
  field(DESC, "MPS Bypass")
  field(DTYP, "BusAddress")
  field(OUT,  "#C0S2@bpmMPS+0,m32")
  field(MASK, "64")
  field(ZNAM, "BYPASSED")
  field(ONAM, "NOT_BYPASSED")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(VAL,  "0")
  field(PINI, "YES")
  field(ASG,  "")
  info(autosaveFields, "VAL")
}

record(bo, "HL2:SBPM:HL19:MPSLTBYP") {
  field(DESC, "MPS Bypass")
  field(DTYP, "BusAddress")
  field(OUT,  "#C1S2@bpmMPS+0,m32")
  field(MASK, "64")
  field(ZNAM, "BYPASSED")
  field(ONAM, "NOT_BYPASSED")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")
  field(VAL,  "0")
  field(PINI, "YES")
  field(ASG,  "")
  info(autosaveFields, "VAL")
}

record(calc, "HL2:SBPM:HL19:MPSIGNRCALC") {
  field(DESC, "MPS ignore if TMIT too low")
  field(CALC, "A<B")
  field(INPA, "HL2:SBPM:HL19:TMIT")
  field(INPB, "HL2:SBPM:HL19:T_MPS_THRES_L")
  field(HIHI, "1")
  field(HHSV, "MAJOR")
  field(ASG, "")
}

record(bi, "HL2:SBPM:HL19:MPSIGNORE") {
  field(DESC, "MPS ignore if TMIT too low")
  field(DTYP, "Raw Soft Channel")
  field(SCAN, "1 second")
  field(INP, "HL2:SBPM:HL19:MPSIGNRCALC PP")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "Not ignored")
  field(ONAM, "Ignored")
  field(PINI, "YES")
  field(ASG, "")
}

# Proxy records for users to set X.AOFF, Y.AOFF
# Placed CAS on X and Y for MPS 
# Feb 2010 - CAS has since been removed, but we'll keep 
# these proxy records as they're already in use

record(ao, "HL2:SBPM:HL19:XAOFF") {
  field(DESC, "X.AOFF val")
#  field(OUT, "HL2:SBPM:HL19:X.AOFF")
  field(PINI, "YES")
  field(EGU, "mm")
  field(PREC, "4")
  field(FLNK, "HL2:SBPM:HL19:XOFF")
  info(autosaveFields, "VAL")
}

record(ao, "HL2:SBPM:HL19:YAOFF") {
  field(DESC, "Y.AOFF val")
#  field(OUT, "HL2:SBPM:HL19:Y.AOFF")
  field(PINI, "YES")
  field(EGU, "mm")
  field(PREC, "4")
  field(FLNK, "HL2:SBPM:HL19:YOFF")
  info(autosaveFields, "VAL")
}

# Add CALC to allow users to maintain
# multiple offsets per plane per BPM

record(calcout, "HL2:SBPM:HL19:XOFF") {
  field(DESC, "Add X offsets")
  field(PREC, "4")
  field(CALC, "A+B+C+D")
  field(INPA, "HL2:SBPM:HL19:XAOFF")
# B-E reserved for undulator offsets
  field(INPB, "")
  field(INPC, "")
  field(INPD, "")
  field(INPE, "")
  field(EGU, "mm")
  field(OUT, "HL2:SBPM:HL19:X.AOFF")
  info(autosaveFields, "B C D E")
}

record(calcout, "HL2:SBPM:HL19:YOFF") {
  field(DESC, "Add Y offsets")
  field(PREC, "4")
  field(CALC, "A+B+C+D")
  field(INPA, "HL2:SBPM:HL19:YAOFF")
# B-E reserved for undulator offsets
  field(INPB, "")
  field(INPC, "")
  field(INPD, "")
  field(INPE, "")
  field(EGU, "mm")
  field(OUT, "HL2:SBPM:HL19:Y.AOFF")
  info(autosaveFields, "B C D E")
}


# Records to set MPS thresholds
record(ao, "HL2:SBPM:HL19:X_MPS_THRES_L") {
  field(DESC, "MPS X Threshold Lo")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C6 S0 @Lo")
  field(VAL,  "-1")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL2:SBPM:HL19:X_MPS_THRES_H") {
  field(DESC, "MPS X Threshold Hi")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C6 S0 @Hi")
  field(VAL,  "1")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL2:SBPM:HL19:Y_MPS_THRES_L") {
  field(DESC, "MPS Y Threshold Lo")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C6 S1 @Lo")
  field(VAL,  "-1")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL2:SBPM:HL19:Y_MPS_THRES_H") {
  field(DESC, "MPS Y Threshold Hi")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C6 S1 @Hi")
  field(VAL,  "1")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL2:SBPM:HL19:T_MPS_THRES_L") {
  field(DESC, "MPS TMIT Threshold Lo")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C6 S2 @Lo")
  field(VAL,  "9.375e7")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL2:SBPM:HL19:T_MPS_THRES_H") {
  field(DESC, "MPS TMIT Threshold Hi")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C6 S2 @Hi")
  field(VAL,  "+1.0E20")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}

record(bi, "HL2:SBPM:HL19:FNET") {
  field(DESC, "BPM data on FNET")
  field(VAL, "$(FN,undefined)")
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(PINI, "YES")
}

# Record to inform users that BPM
# needs TMIT and/or X/Y scale calibration
record(mbbo, "HL2:SBPM:HL19:CHK") {
  field(DESC, "Needs cal/iron")
  field(OMSL, "supervisory")
  field(VAL,  "0")
  field(ZRVL, "0")
  field(ONVL, "1")
  field(TWVL, "2")
  field(THVL, "3")
  field(ZRST, " ")
  field(ONST, "Calibrate")
  field(TWST, "Calibrate&iron")
  field(THST, "Iron")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MINOR")
  field(THSV, "MINOR")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

# Switch simulation record 
record(seq, "HL2:SBPM:HL19:SIMCSEQ") {
  field(DESC, "BPM Sim Ctl Seq")
  field(SELM, "Mask")
  field(SELN, "0")

  field(DO1,  "1")
  field(DO2,  "0")
  field(DO3,  "0")
  field(DO4,  "0") #Passive

#  field(DO5,  "7") # .5 second
  field(DO5,  "9") # .1 second
  field(DO6,  "2")
  field(DO7,  "1")
  field(DO8,  "10")
  field(DO9,  "0")

# LNK 1, 2, 8, 9 only relevant for PADs
# Default macro values are set for PADs; other
# architectures must pass in "" for lnk1 and lnk2
  field(LNK1, "")
  field(LNK2, "")
  field(LNK3, "HL2:SBPM:HL19:SIM.L     PP")
  field(LNK4, "HL2:SBPM:HL19:SIM.SCAN  PP")

  field(LNK5, "HL2:SBPM:HL19:SIM.SCAN  PP")
  field(LNK6, "HL2:SBPM:HL19:SIM.L     PP")
  field(LNK7, "HL2:SBPM:HL19:SIM.L     PP")
  field(LNK8, "")
  field(LNK9, "")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL19:UOFF_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL19:UOFF")
	field(DOL2, "HL2:SBPM:HL19:UOFF")
	field(DOL3, "HL2:SBPM:HL19:UOFF")
	field(DOL4, "HL2:SBPM:HL19:UOFF")
	field(DOL5, "HL2:SBPM:HL19:UOFF")
	field(DOL6, "HL2:SBPM:HL19:UOFF")
	field(DOL7, "HL2:SBPM:HL19:UOFF")
	field(DOL8, "HL2:SBPM:HL19:UOFF")
	field(DOL9, "HL2:SBPM:HL19:UOFF")
	field(DOLA, "HL2:SBPM:HL19:UOFF")
	field(LNK1, "HL2:SBPM:HL19:UOFF_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL19:UOFF_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL19:UOFF_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL19:UOFF_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL19:UOFF_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL19:UOFF_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL19:UOFF_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL19:UOFF_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL19:UOFF_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL19:UOFF_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL19:UOFF_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL19:UOFF_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "0")
	field(B,    "0")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "4")
	field(FLNK, "HL2:SBPM:HL19:UOFF_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL19:UOFF_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL19:UOFF_SEL")
	field(OUTA, "HL2:SBPM:HL19:U.AOFF CA")
	field(OUTB, "HL2:SBPM:HL19:UOFF PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL19:UOFF_CTRL")
{
	field(INPA, "HL2:SBPM:HL19:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL19:UOFF_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL19:VOFF_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL19:VOFF")
	field(DOL2, "HL2:SBPM:HL19:VOFF")
	field(DOL3, "HL2:SBPM:HL19:VOFF")
	field(DOL4, "HL2:SBPM:HL19:VOFF")
	field(DOL5, "HL2:SBPM:HL19:VOFF")
	field(DOL6, "HL2:SBPM:HL19:VOFF")
	field(DOL7, "HL2:SBPM:HL19:VOFF")
	field(DOL8, "HL2:SBPM:HL19:VOFF")
	field(DOL9, "HL2:SBPM:HL19:VOFF")
	field(DOLA, "HL2:SBPM:HL19:VOFF")
	field(LNK1, "HL2:SBPM:HL19:VOFF_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL19:VOFF_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL19:VOFF_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL19:VOFF_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL19:VOFF_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL19:VOFF_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL19:VOFF_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL19:VOFF_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL19:VOFF_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL19:VOFF_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL19:VOFF_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL19:VOFF_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "0")
	field(B,    "0")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "4")
	field(FLNK, "HL2:SBPM:HL19:VOFF_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL19:VOFF_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL19:VOFF_SEL")
	field(OUTA, "HL2:SBPM:HL19:V.AOFF CA")
	field(OUTB, "HL2:SBPM:HL19:VOFF PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL19:VOFF_CTRL")
{
	field(INPA, "HL2:SBPM:HL19:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL19:VOFF_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL19:USCL_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL19:USCL")
	field(DOL2, "HL2:SBPM:HL19:USCL")
	field(DOL3, "HL2:SBPM:HL19:USCL")
	field(DOL4, "HL2:SBPM:HL19:USCL")
	field(DOL5, "HL2:SBPM:HL19:USCL")
	field(DOL6, "HL2:SBPM:HL19:USCL")
	field(DOL7, "HL2:SBPM:HL19:USCL")
	field(DOL8, "HL2:SBPM:HL19:USCL")
	field(DOL9, "HL2:SBPM:HL19:USCL")
	field(DOLA, "HL2:SBPM:HL19:USCL")
	field(LNK1, "HL2:SBPM:HL19:USCL_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL19:USCL_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL19:USCL_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL19:USCL_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL19:USCL_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL19:USCL_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL19:USCL_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL19:USCL_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL19:USCL_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL19:USCL_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL19:USCL_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL19:USCL_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "1")
	field(B,    "1")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "4")
	field(FLNK, "HL2:SBPM:HL19:USCL_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL19:USCL_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL19:USCL_SEL")
	field(OUTA, "HL2:SBPM:HL19:U.ASLO CA")
	field(OUTB, "HL2:SBPM:HL19:USCL PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL19:USCL_CTRL")
{
	field(INPA, "HL2:SBPM:HL19:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL19:USCL_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL19:VSCL_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL19:VSCL")
	field(DOL2, "HL2:SBPM:HL19:VSCL")
	field(DOL3, "HL2:SBPM:HL19:VSCL")
	field(DOL4, "HL2:SBPM:HL19:VSCL")
	field(DOL5, "HL2:SBPM:HL19:VSCL")
	field(DOL6, "HL2:SBPM:HL19:VSCL")
	field(DOL7, "HL2:SBPM:HL19:VSCL")
	field(DOL8, "HL2:SBPM:HL19:VSCL")
	field(DOL9, "HL2:SBPM:HL19:VSCL")
	field(DOLA, "HL2:SBPM:HL19:VSCL")
	field(LNK1, "HL2:SBPM:HL19:VSCL_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL19:VSCL_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL19:VSCL_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL19:VSCL_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL19:VSCL_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL19:VSCL_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL19:VSCL_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL19:VSCL_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL19:VSCL_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL19:VSCL_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL19:VSCL_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL19:VSCL_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "1")
	field(B,    "1")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "4")
	field(FLNK, "HL2:SBPM:HL19:VSCL_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL19:VSCL_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL19:VSCL_SEL")
	field(OUTA, "HL2:SBPM:HL19:V.ASLO CA")
	field(OUTB, "HL2:SBPM:HL19:VSCL PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL19:VSCL_CTRL")
{
	field(INPA, "HL2:SBPM:HL19:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL19:VSCL_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL19:PHI_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL19:PHI")
	field(DOL2, "HL2:SBPM:HL19:PHI")
	field(DOL3, "HL2:SBPM:HL19:PHI")
	field(DOL4, "HL2:SBPM:HL19:PHI")
	field(DOL5, "HL2:SBPM:HL19:PHI")
	field(DOL6, "HL2:SBPM:HL19:PHI")
	field(DOL7, "HL2:SBPM:HL19:PHI")
	field(DOL8, "HL2:SBPM:HL19:PHI")
	field(DOL9, "HL2:SBPM:HL19:PHI")
	field(DOLA, "HL2:SBPM:HL19:PHI")
	field(LNK1, "HL2:SBPM:HL19:PHI_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL19:PHI_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL19:PHI_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL19:PHI_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL19:PHI_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL19:PHI_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL19:PHI_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL19:PHI_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL19:PHI_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL19:PHI_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL19:PHI_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL19:PHI_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "0")
	field(B,    "0")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "1")
	field(FLNK, "HL2:SBPM:HL19:PHI_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL19:PHI_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL19:PHI_SEL")
	field(OUTA, "HL2:SBPM:HL19:CALC.E CA")
	field(OUTB, "HL2:SBPM:HL19:PHI PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL19:PHI_CTRL")
{
	field(INPA, "HL2:SBPM:HL19:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL19:PHI_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL19:PSI_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL19:PSI")
	field(DOL2, "HL2:SBPM:HL19:PSI")
	field(DOL3, "HL2:SBPM:HL19:PSI")
	field(DOL4, "HL2:SBPM:HL19:PSI")
	field(DOL5, "HL2:SBPM:HL19:PSI")
	field(DOL6, "HL2:SBPM:HL19:PSI")
	field(DOL7, "HL2:SBPM:HL19:PSI")
	field(DOL8, "HL2:SBPM:HL19:PSI")
	field(DOL9, "HL2:SBPM:HL19:PSI")
	field(DOLA, "HL2:SBPM:HL19:PSI")
	field(LNK1, "HL2:SBPM:HL19:PSI_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL19:PSI_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL19:PSI_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL19:PSI_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL19:PSI_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL19:PSI_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL19:PSI_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL19:PSI_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL19:PSI_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL19:PSI_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL19:PSI_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL19:PSI_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "90")
	field(B,    "90")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "1")
	field(FLNK, "HL2:SBPM:HL19:PSI_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL19:PSI_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL19:PSI_SEL")
	field(OUTA, "HL2:SBPM:HL19:CALC.F CA")
	field(OUTB, "HL2:SBPM:HL19:PSI PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL19:PSI_CTRL")
{
	field(INPA, "HL2:SBPM:HL19:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL19:PSI_SEL.L PP")
}
record(longout, "HL2:SBPM:HL19:PARMSEL") {
	field(VAL, "0")
	field(PINI, "YES")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


# per BPM database for stripline BPMs

##############################################
# This is the head of the main processing chain
# that runs at the highest priority.
##############################################

#############################################
# This is the head of the processing chain for
# diagnostics.
##############################################
record(ai, "HL2:SBPM:HL20:GRN") {
  field(DESC, "GRN Strip Amplitude")
  field(DTYP, "Raw Bpm Signal")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "#C7 S0")
  field(EGU, "raw")
#TODO set HOPR/LOPR, alarm limits
  field(SCAN, "I/O Intr")
# The priority determines what scan list we are being
# put on (see drvPadUdpComm.c)
  field(PRIO, "LOW")
  field(FLNK, "HL2:SBPM:HL20:RED")
# HOPR for the energy algorithm is determined as follows:
#
#                      inf        inf
#  1) Fourier relation / h^2 dt = / |H|^2 df = 2 B
#                     0         -inf
#
#  1a) It can be shown that the maximum of the impuls response
#      ha is ~ 2 B
#                               
#  2) The digitizer produces the numbers
#
#     Ai = 2^s (hi/ha)
#
#     where ha is the maximum of the impuls response
#     and 2^s is a scale factor.
#     
#  3) 'Energy algorithm' calculates S = sum( Ai^2 )
#
#                                                     inf
#  4) S = (2^s / ha)^2 sum(hi^2) = K sum(hi^2) Dt ~ K / h^2 dt
#                                                    0
#
#     with K = (2^s / ha)^2 fs
#
#  5) From 4) and 1a) ->  S ~ K ha and therefore
#
#  6) S = 2^(2s) fs/ha = 2^(2s) fs/(2 B)
#
#  7) The strip signals are sqrt(S); hence HOPR is about
#
#     HOPR ~ 2^s  sqrt( fs/2/B )
#
#     with 2^s = 32768, fs=120MHz, B=10MHz it follows
#     that HOPR ~ 1E5; we add some margin...
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL20:RED") {
  field(DESC, "RED Strip Amplitude")
  field(DTYP, "Raw Bpm Signal")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "#C7 S1")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(FLNK, "HL2:SBPM:HL20:BLU")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL20:BLU") {
  field(DESC, "BLU Strip Amplitude")
  field(DTYP, "Raw Bpm Signal")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "#C7 S2")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(FLNK, "HL2:SBPM:HL20:YLO")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL20:YLO") {
  field(DESC, "YLO Strip Amplitude")
  field(DTYP, "Raw Bpm Signal")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "#C7 S3")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

##############################################
# Slowly-scanned diagnostics
##############################################

#
record(waveform, "HL2:SBPM:HL20:REDW") {
  field(DESC, "Raw CAL RED Data")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP, "#C7 S1")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "1 second")
}

record(waveform, "HL2:SBPM:HL20:GRNW") {
  field(DESC, "Raw CAL GRN Data")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP, "#C7 S2")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "1 second")
}

record(waveform, "HL2:SBPM:HL20:RAWDBG") {
  field(DESC, "Raw BEAM Dbg")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
# do not 'wbscan' for now since e.g., an underrange
# condition on the real signal can happen.
  field(INP, "#C7 S7")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "Passive")
}

record(waveform, "HL2:SBPM:HL20:REDDBG") {
  field(DESC, "Raw CAL RED Dbg")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP, "#C7 S8 @wbscan")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "Passive")
}

record(waveform, "HL2:SBPM:HL20:GRNDBG") {
  field(DESC, "Raw CAL GRN Dbg")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP, "#C7 S9 @wbscan")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU, "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
  field(SCAN, "Passive")
}

record(ai, "HL2:SBPM:HL20:GRUV") {
  field(DESC, "CAL Gain GRN/RED")
  field(DTYP, "Raw Stripl Calp")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C7 S0")
  field(SCAN, "10 second")
  field(PREC, "4")
  field(LOPR, "0.5")
  field(HOPR, "1.5")
}

record(ai, "HL2:SBPM:HL20:GRU") {
  field(DESC, "CAL Gain GRN/BLU")
  field(DTYP, "Raw Stripl Calp")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C7 S1")
  field(SCAN, "10 second")
  field(PREC, "4")
  field(LOPR, "0.5")
  field(HOPR, "1.5")
  info(autosaveFields, "ASLO")
}

record(ai, "HL2:SBPM:HL20:GRV") {
  field(DESC, "CAL Gain RED/YLO")
  field(DTYP, "Raw Stripl Calp")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C7 S2")
  field(SCAN, "10 second")
  field(PREC, "4")
  field(LOPR, "0.5")
  field(HOPR, "1.5")
  info(autosaveFields, "ASLO")
}

record(ai, "HL2:SBPM:HL20:TGRN") {
  field(DESC, "Green arrival time")
  field(DTYP, "Raw Bpm Signal")
  field(EGU, "ADC Clocks")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C7 S4")
  field(SCAN, "10 second")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "128")
  field(LOLO, "5")
  field(LOW, "8")
  field(HIGH, "60")
  field(HIHI, "70")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
  field(HSV, "MINOR")
  field(HHSV, "MAJOR")
}

record(ai, "HL2:SBPM:HL20:TRED") {
  field(DESC, "Red arrival time")
  field(DTYP, "Raw Bpm Signal")
  field(EGU, "ADC Clocks")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C7 S5")
  field(SCAN, "10 second")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "128")
  field(LOLO, "5")
  field(LOW, "8")
  field(HIGH, "60")
  field(HIHI, "70")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
  field(HSV, "MINOR")
  field(HHSV, "MAJOR")
}

record(ai, "HL2:SBPM:HL20:TBLU") {
  field(DESC, "Blue arrival time")
  field(DTYP, "Raw Bpm Signal")
  field(EGU, "ADC Clocks")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C7 S6")
  field(SCAN, "10 second")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "128")
  field(LOLO, "5")
  field(LOW, "8")
  field(HIGH, "60")
  field(HIHI, "70")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
  field(HSV, "MINOR")
  field(HHSV, "MAJOR")
}

record(ai, "HL2:SBPM:HL20:TYLO") {
  field(DESC, "Yellow arrival time")
  field(DTYP, "Raw Bpm Signal")
  field(EGU, "ADC Clocks")
# 'card' selects PAD number, 'signal' selects cal coeff
  field(INP, "#C7 S7")
  field(SCAN, "10 second")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "128")
  field(LOLO, "5")
  field(LOW, "8")
  field(HIGH, "60")
  field(HIHI, "70")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
  field(HSV, "MINOR")
  field(HHSV, "MAJOR")
}

record(ao, "HL2:SBPM:HL20:PINC_ADJ") {
  field(DESC, "Adjust Pinc. Corr.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL20:CALC.K PP MS")
  field(VAL, "0")
  field(DRVL, "0")
  field(DRVH, "2")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

# QSCL setting:
#
# Q: charge
# Z: impedance
# F: form factor: phi/(2 pi) sin(2 pi f l/c)
#
# Signal =  Q Z F G h(t) = A h(t)  [A] = Vs
#
#                  inf              inf
# Energy =  A^2   / h^2(t) dt = A^2 / |H(w)|^2 dw/2/pi = A^2 B
#                0                 0
#                        
# Measured energy = Sum{ (Vp/32768 * xi)^2 } / fs = S / fs ~ Energy
#
# -> A^2 B = S/fs
#
# With T = sqrt( Sum{ xi^2 } )
#
#    A = sqrt(S)/sqrt(B*fs) = T/sqrt(B*fs) Vp/32768
#
#                      T/32768 Vp
#    Q = A/F/G/Z = -----------------
#                   F G Z sqrt(B*fs)
#
# Vp = { 1.5Vpp/2 (PGA=1) or 2.25Vpp/2 (PGA=0) } / 2 (transformer)
#
# I believe PGA is off (-> Vp ~ .56V)
#
# Z  = 50
#
# G: (calibration uses GRN/BLU -> signal should have the
#    level of the grn/red channels with the additional switch)
#
# Block diagram / parts / gain:
#
# [filt]    [Att1]    [Amp1]   [Att2]    [BPF]      [Amp2]    [pad] [Amp3]   [switch]
# f-17520  hmc540lp3  SBF-5089 hmc540lp3 MBP-140-6-4 SBF-4089  PAT-0 SBF-4089 HMC-197
#
#  -2dB*    -1dB       20dB     -1dB     -4.5         14.8dB   0dB   14.8dB   -0.4dB
#
# *: 1st filter ATT is a wild guess.
#  BPF loss (RLC Catalog, pp.55): (L (nsect+.5) / (% of 3dB BW) + .2) dB
#  with L ~6.2  10MHz/fc=140Mhz filter-> 4.5
#
#  -> Gtot ~ 40.7dB
#
#  subtract cable loss (2dB); Gtot = 86
# 
#                      T/32768 Vp            .56V/32768
#    Q = A/F/G/Z = ----------------- = T/F  ------------------------
#                   F G Z sqrt(B*fs)        86*50*sqrt(10*140)Mhz
#
#      = T/F = 1.06E-7/F nC
#
#    F for a 7% coverage, 4" BPM at 140MHz   .07 sin(2*pi*140e6 4*.0254/3e8)
#      = .021
#
#      => 1.06E-7/.021 nC = 5E-6 nC
#
# (Faraday cup measurement -> (3600/44)^-1 1e-4 -> 1.22E-6
#
record(ao, "HL2:SBPM:HL20:QSCL") {
  field(DESC, "TMIT/Charge Scale")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL20:QSCA.A PP MS")
# 5.0E-6 / 1.6E-10 [nC/e-]
  field(VAL, "31250")
  field(EGU, "Nel")
  field(PREC, "3")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

# Adjust TMIT scale for AFE attenuation
record(calcout, "HL2:SBPM:HL20:QSCA") {
  field(DESC, "TMIT ATT Adj. Scale")
  field(INPB, "HL2:SBPM:HL20:ATT1 CP")
  field(INPC, "HL2:SBPM:HL20:ATT2 CP")
  field(CALC, "A*10^((B+C+D)/20)")
# use CA link to deposit into TMIT.ASLO so
# that TMIT is not forced into linkset
# of this record
  field(OUT, "HL2:SBPM:HL20:TMIT.ASLO CA")
  field(EGU, "Nel")
  field(PREC, "3")
  info(autosaveFields, "D")
}

record(ao,    "HL2:SBPM:HL20:ATT1SIMP") {
	field(DESC, "ATT1 Propagator")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL2:SBPM:HL20:ATT1   CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL2:SBPM:HL20:ASIM.A PP")
  	field(IVOA, "Set output to IVOV")
	field(IVOV, "0")
	field(EGU,  "dB")
}

record(ao,    "HL2:SBPM:HL20:ATT2SIMP") {
	field(DESC, "ATT2 Propagator")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL2:SBPM:HL20:ATT2   CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL2:SBPM:HL20:ASIM.C PP")
  	field(IVOA, "Set output to IVOV")
	field(IVOV, "0")
	field(EGU,  "dB")
}

# Attenuate charge either by
# real attenuator settings or
# by fake ones.
# If B, C >= 0 then their
# values will be used instead
# of ATT1, ATT2
record(calcout, "HL2:SBPM:HL20:ASIM") {
  field(DESC, "Q Simul Attenuator")
  field(DTYP, "Soft Channel")
  field(OUT,  "HL2:SBPM:HL20:QSIM.ESLO PP")
# ATT1SIM puts value into A
# set to -1 to use real attenuator settings
# and >=0 to use B instead
  field(B,    "-1")
# ATT2SIM puts value into C
# set to -1 to use real attenuator settings
# and >=0 to use D instead
  field(D,    "-1")
  field(CALC, "10^(((B>=0?B:A)+(D>=0?D:C))/20)")
  field(PINI, "YES")
}

record(ao, "HL2:SBPM:HL20:WSIM") {
  field(DESC, "BPM W Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL20:SIM.G PP")
  field(VAL, "0.07")
  field(EGU, "%")
  field(PINI, "YES")
  field(PREC, "3")
  field(LOPR, "0")
  field(HOPR, "0.25")
}


record(sel, "HL2:SBPM:HL20:STA") {
  field(DESC, "Status Summary")
  field(SELM, "High Signal")
  field(INPA, "HL2:SBPM:HL20:RSTA.SEVR MS NPP")
  field(INPB, "HL2:SBPM:HL20:TMIT.SEVR MS NPP")
  field(INPC, "HL2:SBPM:HL20:Y.SEVR    MS NPP")
  field(INPD, "HL2:SBPM:HL20:X.SEVR    MS NPP")
  field(INPE, "HL2:SBPM:HL20:TGRN.SEVR MS NPP")
  field(INPF, "HL2:SBPM:HL20:TRED.SEVR MS NPP")
  field(INPG, "HL2:SBPM:HL20:TBLU.SEVR MS NPP")
  field(INPH, "HL2:SBPM:HL20:TYLO.SEVR MS NPP")
  field(INPI, "HL2:SBPM:HL20:GRU.SEVR  MS NPP")
  field(INPJ, "HL2:SBPM:HL20:GRV.SEVR  MS NPP")
  field(SCAN, "1 second")
}

# This record really belongs on the
# PAD IOC. We keep them here however
# so we can save/restore. It is more
# confusing but shouldn't matter from
# an efficiency standpoint (they are
# rarely changed).
record(longout, "HL2:SBPM:HL20:ATTO") {
  field(DESC, "AFE Tot. Att. Offset")
# fetched via inlink
#field(OUT,  "HL2:SBPM:HL20:ATTC.B PP")
  field(DRVL, "-10")
  field(DRVH, "30")
  field(LOPR, "-10")
  field(HOPR, "30")
  field(EGU, "dB")
  field(VAL, "0")
  field(PINI, "YES")
  info(autosaveFields, "VAL DRVH HOPR DRVL LOPR")
}

# This record really belongs on the
# PAD IOC. We keep them here however
# so we can save/restore. It is more
# confusing but shouldn't matter from
# an efficiency standpoint (they are
# rarely changed).
record(longout, "HL2:SBPM:HL20:CLAO") {
  field(DESC, "AFE Cal. Att. Offset")
# fetched via inlink
#field(OUT,  "HL2:SBPM:HL20:ATTC.C PP")
  field(DRVL, "-20")
  field(DRVH, "20")
  field(LOPR, "-20")
  field(HOPR, "20")
  field(EGU, "dB")
  field(VAL, "40")
  field(PINI, "YES")
  info(autosaveFields, "VAL DRVH HOPR DRVL LOPR")
}

record(calc, "HL2:SBPM:HL20:STA_ALH") {
  field(DESC, "Status Summary")
  field(SCAN, "1 second")
  field(CALC, "0")
  field(INPA, "HL2:SBPM:HL20:RSTA_ALH.SEVR MS NPP")
  field(INPB, "HL2:SBPM:HL20:GRU.SEVR  MS NPP")
  field(INPC, "HL2:SBPM:HL20:GRV.SEVR  MS NPP")
  field(INPD, "HL2:SBPM:HL20:CHK.SEVR MS NPP")
}

# snapshot PV for the bpm values display
record(ai, "HL2:SBPM:HL20:GRN_SLOW") {
  field(DESC, "GRN snapshot for display")
  field(INP, "HL2:SBPM:HL20:GRN NPP MS")
  field(EGU, "raw")
  field(SCAN, "1 second")
  field(FLNK, "HL2:SBPM:HL20:RED_SLOW")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL20:RED_SLOW") {
  field(DESC, "RED snapshot for display")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "HL2:SBPM:HL20:RED NPP MS")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(FLNK, "HL2:SBPM:HL20:BLU_SLOW")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL20:BLU_SLOW") {
  field(DESC, "BLU snapshot for display")
# 'card' selects PAD number, 'signal' selects strip
  field(INP, "HL2:SBPM:HL20:BLU NPP MS")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(FLNK, "HL2:SBPM:HL20:YLO_SLOW")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(ai, "HL2:SBPM:HL20:YLO_SLOW") {
  field(DESC, "YLO snapshot for display")
  field(INP, "HL2:SBPM:HL20:YLO NPP MS")
  field(EGU, "raw")
  field(SCAN, "Passive")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "1.4E5")
  field(LOLO, "1000")
  field(LOW, "2000")
  field(LLSV, "MAJOR")
  field(LSV, "MINOR")
}

record(sub, "HL2:SBPM:HL20:CALC") {
  field(SNAM, "drvBpmBvectSetupSub")
# E: phi F: psi
# BPM channel number in L
  field(INPL, "7")
  field(SCAN, "Passive")
}

record(bo, "HL2:SBPM:HL20:PINC_ENA") {
  field(DESC, "Simple Pincushion Alg")
  field(DTYP, "BusAddress")
  field(OUT,  "#C0S2@drvBpmStriplPincEna,m32")
  field(MASK, "128")
  field(ZNAM, "DISABLED")
  field(ONAM, "ENABLED")
  field(VAL,  "0")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

record(ao, "HL2:SBPM:HL20:UDR_THRES") {
  field(DESC, "Detection Underrange Threshold")
  field(DTYP, "Bpm Parameters")
  field(OUT,  "#C7S0")
  field(EGU,  "ADC Ticks")
  field(DOL,  "45.26")
  field(PINI, "YES")
  field(DRVL, "0")
  field(DRVH, "32767")
  info(autosaveFields, "VAL")
}
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


# per BPM database for stripline BPMs

######################################
# HEAD of main processing chain
######################################

record(ai, "HL2:SBPM:HL20:X") {
  field(DESC, "X Position")
  field(EGU, "mm")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C7 S11")
  field(SCAN, "I/O Intr")
# The priority determines what scan list we are being
# put on (see drvPadUdpComm.c)
  field(PRIO, "HIGH")
  field(FLNK, "HL2:SBPM:HL20:Y")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
  field(ASG,  "")
  field(TSE, "-2")
  info(autosaveFields, "ASLO LOLO LOW HIGH HIHI HHSV LLSV")
}

record(ai, "HL2:SBPM:HL20:Y") {
  field(DESC, "Y Position")
  field(EGU, "mm")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C7 S12")
  field(FLNK, "HL2:SBPM:HL20:TMIT")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
  field(ASG,  "")
  field(TSE, "-2")
  info(autosaveFields, "ASLO LOLO LOW HIGH HIHI HHSV LLSV")
}

record(ai, "HL2:SBPM:HL20:TMIT") {
  field(DESC, "Charge Estimate")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C7 S13")
  field(EGU, "Nel")
  field(PREC, "3")
  field(LOPR, "0")
  field(HOPR, "1E11")
# FLINK into BSA
  field(FLNK, "HL2:SBPM:HL20:EFX.PROC")
  field(ASG,  "")
  field(TSE, "-2")
  info(autosaveFields, "LOLO LOW HIGH HIHI HHSV LLSV ")
}


######################################
# HEAD of diagnostics processing chain
######################################

# leave RWAV in it's own lockset; don't FLNK
# to 'U' & friends
record(waveform, "HL2:SBPM:HL20:RWAV") {
  field(DESC, "Raw BPM Data")
  field(DTYP, "WavBuf")
# 'signal' number selects 'beam', 'calX', 'calY'
  field(INP,  "#C7 S0")
  field(SCAN, "I/O Intr")
# use LOW or HIGH to end up on the 'diagnostic' 
# scan list (see drvPadUdpComm.c)
  field(PRIO, "LOW")
  field(NELM, "512")
  field(FTVL, "SHORT")
  field(EGU,  "Counts")
  field(HOPR, "32768")
  field(LOPR, "-32767")
}

record(ai, "HL2:SBPM:HL20:U") {
  field(DESC, "Raw U Position")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C7 S8")
  field(SCAN, "I/O Intr")
# use LOW or HIGH to end up on the 'diagnostic' 
# scan list (see drvPadUdpComm.c)
  field(PRIO, "LOW")
  field(PREC, "5")
  field(EGU,  "mm")
  field(LOPR, "-0.7")
  field(HOPR, "+0.7")
  field(FLNK, "HL2:SBPM:HL20:V")
}

record(ai, "HL2:SBPM:HL20:V") {
  field(DESC, "Raw V Position")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C7 S9")
  field(SCAN, "Passive")
  field(PREC, "5")
  field(EGU,  "mm")
  field(LOPR, "-0.7")
  field(HOPR, "+0.7")
  field(FLNK, "HL2:SBPM:HL20:PINC")
}

record(ai, "HL2:SBPM:HL20:PINC") {
  field(DESC, "Pin Cushion Corr.")
  field(DTYP, "Raw Bpm Signal")
  field(INP, "#C7 S10")
  field(SCAN, "Passive")
}

record(longin, "HL2:SBPM:HL20:RSTA") {
  field(DESC, "Status of Raw Processor")
  field(DTYP, "Bpm Raw Status")
  field(INP, "#C7S0")
  field(SCAN, "1 second")
  field(LOLO, "-1")
  field(HIHI, "+1")
  field(HHSV, "INVALID")
  field(LLSV, "INVALID")
  field(FLNK, "HL2:SBPM:HL20:RSTA_ALH")
}


record(calc, "HL2:SBPM:HL20:RSTA_ALH") {
  field(CALC, "A & B")
  field(INPA, "HL2:SBPM:HL20:RSTA")
  field(INPB, "0x30F")
  field(HIHI, "1")
  field(LOLO, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(SCAN, "Passive")
}

######################################
# Input/Parameteres
######################################

record(ao, "HL2:SBPM:HL20:PHI") {
  field(DESC, "Rot Angle")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(EGU, "deg")
  field(PREC, "1")
  field(LOPR, "-180")
  field(HOPR, "+180")
  field(FLNK, "HL2:SBPM:HL20:PHI_SEQ")
}

record(ao, "HL2:SBPM:HL20:PSI") {
  field(DESC, "Axis Sep. Angle")
  field(DTYP, "Soft Channel")
  field(VAL, "90")
  field(EGU, "deg")
  field(PREC, "1")
  field(LOPR, "0")
  field(HOPR, "+180")
  field(FLNK, "HL2:SBPM:HL20:PSI_SEQ")
}

#record(dfanout, "HL2:SBPM:HL20:PCMM") {
#  field(DESC, "BPM Scale")
#  field(OUTA, "HL2:SBPM:HL20:USCL PP MS")
#  field(OUTB, "HL2:SBPM:HL20:VSCL PP MS")
#  field(VAL, "12")
#  field(EGU, "mm")
#  field(PREC, "4")
#  field(LOPR, "5")
#  field(HOPR, "15")
#  field(PINI, "YES")
#}

record(ao, "HL2:SBPM:HL20:UOFF") {
  field(DESC, "BPM U Offset")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(EGU, "mm")
  field(PREC, "4")
  field(LOPR, "-5")
  field(HOPR, "+5")
  field(FLNK, "HL2:SBPM:HL20:UOFF_SEQ")
}

record(ao, "HL2:SBPM:HL20:VOFF") {
  field(DESC, "BPM V Offset")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(EGU, "mm")
  field(PREC, "4")
  field(LOPR, "-5")
  field(HOPR, "+5")
  field(FLNK, "HL2:SBPM:HL20:VOFF_SEQ")
}

record(ao, "HL2:SBPM:HL20:USCL") {
  field(DESC, "BPM U Scale")
  field(DTYP, "Soft Channel")
  field(VAL,  "1")
  field(EGU, "mm")
  field(PREC, "4")
  field(FLNK, "HL2:SBPM:HL20:USCL_SEQ")
}

record(ao, "HL2:SBPM:HL20:VSCL") {
  field(DESC, "BPM V Scale")
  field(DTYP, "Soft Channel")
  field(VAL,  "1")
  field(EGU, "mm")
  field(PREC, "4")
  field(FLNK, "HL2:SBPM:HL20:VSCL_SEQ")
}


record(mbbo, "HL2:SBPM:HL20:ACCESS") {
  field(DESC, "BPM On Line")
  field(DTYP, "StreamSwitch")
  field(OUT, "#C7 S0")
  field(ZRVL, "1")
  field(ZRST, "Running")
  field(ZRSV, "NO_ALARM")
  field(ONVL, "1")
  field(ONST, "Maintenance")
  field(ONSV, "MINOR")
  field(TWVL, "1")
  field(TWST, "Test")
  field(TWSV, "MINOR")
  field(THVL, "0")
  field(THST, "OFFLINE")
  field(THSV, "MAJOR")
# set both, rval and val to get it right
# regardless of whether devsup does conversion
# or not.
  field(RVAL, "0")
  field(VAL,  "0")
  field(PINI, "YES")
  field(FLNK, "HL2:SBPM:HL20:SIMOFF")
  info(autosaveFields, "RVAL")
}

#
# Used by higher level software to determine if a PV is in feedback or not.
# May also be used by actuator (magnet and RF) IOC applications to 
# switch output records to "closed_loop" to prevent outside programs from
# changing setpoints when an actuator device is in feedback.
#
record(mbbo, "HL2:SBPM:HL20:FBCK")
{
  field(DESC, "Feedback State")
  field(PINI, "YES")
  field(OMSL, "supervisory")
  field(VAL,  "0")
  field(ZRVL, "0")
  field(ONVL, "1")
  field(TWVL, "2")
# Off - this device can be used in feedback but all feedback loops 
# using it are off.
  field(ZRST, "Off")
# On - this device is being used by one or more feedback loops.
  field(ONST, "On")
# Unavailable - this device is not used by any feedback loop.
  field(TWST, "Unavailable")
  info(autosaveFields, "VAL")
}

# Convenience record holding the MAD name
record(stringin, "HL2:SBPM:HL20:MADN") {
  field(DESC, "MAD Name")
  field(VAL, "SBPMHL20")
  field(PINI, "YES")
}

record(stringin, "SBPMHL20:NAME") {
  field(DESC, "BPM Name")
  field(VAL, "HL2:SBPM:HL20")
  field(PINI, "YES")
}

record(ai, "HL2:SBPM:HL20:X_SLOW") {
#alias("HL2:SBPM:HL20:X1H")
  field(DESC, "X snapshot for display")
  field(EGU, "mm")
  field(INP, "HL2:SBPM:HL20:X MS")
  field(FLNK, "HL2:SBPM:HL20:Y_SLOW")
  field(PREC, "4")
  field(SCAN, "1 second")
  field(LOPR, "-12")
  field(HOPR, "+12")
}

record(ai, "HL2:SBPM:HL20:Y_SLOW") {
#alias("HL2:SBPM:HL20:Y1H")
  field(DESC, "Y snapshot for display")
  field(EGU, "mm")
  field(INP, "HL2:SBPM:HL20:Y NPP MS")
  field(FLNK, "HL2:SBPM:HL20:TMIT_SLOW")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
}

record(ai, "HL2:SBPM:HL20:TMIT_SLOW") {
#alias("HL2:SBPM:HL20:TMIT1H")
  field(DESC, "TMIT snapshot for display")
  field(INP, "HL2:SBPM:HL20:TMIT NPP MS")
  field(EGU, "Nel")
  field(PREC, "3")
  field(LOPR, "0")
  field(HOPR, "1E11")
}

######################################
# Simulation Parameters + Control
######################################

# switch off simulation when going off-line
record(calcout, "HL2:SBPM:HL20:SIMOFF") {
  field(DESC, "Sim Off Propagator")
  field(INPA, "HL2:SBPM:HL20:ACCESS.RVAL")
  field(CALC, "A")
  field(OCAL, "0")
  field(OOPT, "When Zero")
  field(DOPT, "Use OCAL")
  field(OUT,  "HL2:SBPM:HL20:SIMC PP")
}

record(calcout, "HL2:SBPM:HL20:SIM") {
  field(DESC, "BPM Pos. Simulation")
  field(DTYP, "Strip Signal Simulator")
  field(OUT, "7")
#CALC & VAL unused; the real calculation is done
#        in device support. The reason this is a
#        calcout rather than sub is that we want
#        to use the OUT link...
  field(CALC, "A")
  field(INPA, "HL2:SBPM:HL20:USCL")
  field(INPL, "0")
}

# Switch simulation record HL2:SBPM:HL20:SIMCSEQ moved to
# bpmCavity.db.part and bpmStripl.db.part 

record(mbbo, "HL2:SBPM:HL20:SIMC") {
  field(DESC, "Stripl Sim Ctl")
  field(DTYP, "Raw Soft Channel")
  field(OUT,  "HL2:SBPM:HL20:SIMCSEQ.SELN PP")
  field(ZRST, "OFF")
  field(ZRVL, "0x0f")
  field(ONST, "ON")
  field(ONVL, "0x1c0")
  field(TWST, "SOFT")
  field(TWVL, "0x030")
  field(MASK, "-1")
  field(NOBT, "16")
  field(VAL,  "0")
  field(RVAL, "0x0f")
  field(PINI, "YES")
}

record(ao, "HL2:SBPM:HL20:XSIM") {
  field(DESC, "BPM X Pos. Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL20:SIM.B PP")
  field(VAL, "0.5")
  field(EGU, "mm")
  field(PINI, "YES")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
}

record(ao, "HL2:SBPM:HL20:YSIM") {
  field(DESC, "BPM Y Pos. Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL20:SIM.C PP")
  field(VAL, "0.")
  field(EGU, "mm")
  field(PINI, "YES")
  field(PREC, "4")
  field(LOPR, "-12")
  field(HOPR, "+12")
}

record(ao, "HL2:SBPM:HL20:QSIM") {
  field(DESC, "BPM Q Simul.")
  field(DTYP, "Raw Soft Channel")
  field(OUT, "HL2:SBPM:HL20:SIM.D PP")
  field(EGU, "Nel")
  field(ASLO, "6000")
#ESLO is used to add attenuation
  field(LINR, "LINEAR")
  field(VAL, "1E9")
  field(PINI, "YES")
  field(PREC, "4")
  field(LOPR, "0")
  field(HOPR, "1E11")
}

record(ao, "HL2:SBPM:HL20:ROTS") {
  field(DESC, "BPM Rot. Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL20:SIM.E PP")
  field(VAL, "0.")
  field(EGU, "deg")
  field(PINI, "YES")
  field(PREC, "1")
  field(LOPR, "-180")
}

record(ao, "HL2:SBPM:HL20:PSIS") {
  field(DESC, "BPM Angle. Simul.")
  field(DTYP, "Soft Channel")
  field(OUT, "HL2:SBPM:HL20:SIM.F PP")
  field(VAL, "90")
  field(EGU, "deg")
  field(PINI, "YES")
  field(PREC, "1")
  field(LOPR, "0")
}

record(aao, "HL2:SBPM:HL20:DIGISIMW") {
  field(DESC, "VME Digi Sim. Waveform")
  field(DTYP, "VmeDigi Sim Wav")
  field(OUT,  "#C7 S0")
  field(FTVL, "SHORT")
  field(EGU,  "Counts")
  field(HOPR, "32678")
  field(LOPR, "-32768")
# 16384 samples/channel * 4 channels
  field(NELM, "65536")
  field(PINI, "NO")
}

#Used by model/database folks to verify BPM

record(ao, "HL2:SBPM:HL20:Z") {
  field(DESC, "Z Position")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

# MPS interface
record(bo, "HL2:SBPM:HL20:MPSBYP") {
  field(DESC, "MPS Bypass")
  field(DTYP, "BusAddress")
  field(OUT,  "#C0S2@bpmMPS+0,m32")
  field(MASK, "128")
  field(ZNAM, "BYPASSED")
  field(ONAM, "NOT_BYPASSED")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(VAL,  "0")
  field(PINI, "YES")
  field(ASG,  "")
  info(autosaveFields, "VAL")
}

record(bo, "HL2:SBPM:HL20:MPSLTBYP") {
  field(DESC, "MPS Bypass")
  field(DTYP, "BusAddress")
  field(OUT,  "#C1S2@bpmMPS+0,m32")
  field(MASK, "128")
  field(ZNAM, "BYPASSED")
  field(ONAM, "NOT_BYPASSED")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")
  field(VAL,  "0")
  field(PINI, "YES")
  field(ASG,  "")
  info(autosaveFields, "VAL")
}

record(calc, "HL2:SBPM:HL20:MPSIGNRCALC") {
  field(DESC, "MPS ignore if TMIT too low")
  field(CALC, "A<B")
  field(INPA, "HL2:SBPM:HL20:TMIT")
  field(INPB, "HL2:SBPM:HL20:T_MPS_THRES_L")
  field(HIHI, "1")
  field(HHSV, "MAJOR")
  field(ASG, "")
}

record(bi, "HL2:SBPM:HL20:MPSIGNORE") {
  field(DESC, "MPS ignore if TMIT too low")
  field(DTYP, "Raw Soft Channel")
  field(SCAN, "1 second")
  field(INP, "HL2:SBPM:HL20:MPSIGNRCALC PP")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "Not ignored")
  field(ONAM, "Ignored")
  field(PINI, "YES")
  field(ASG, "")
}

# Proxy records for users to set X.AOFF, Y.AOFF
# Placed CAS on X and Y for MPS 
# Feb 2010 - CAS has since been removed, but we'll keep 
# these proxy records as they're already in use

record(ao, "HL2:SBPM:HL20:XAOFF") {
  field(DESC, "X.AOFF val")
#  field(OUT, "HL2:SBPM:HL20:X.AOFF")
  field(PINI, "YES")
  field(EGU, "mm")
  field(PREC, "4")
  field(FLNK, "HL2:SBPM:HL20:XOFF")
  info(autosaveFields, "VAL")
}

record(ao, "HL2:SBPM:HL20:YAOFF") {
  field(DESC, "Y.AOFF val")
#  field(OUT, "HL2:SBPM:HL20:Y.AOFF")
  field(PINI, "YES")
  field(EGU, "mm")
  field(PREC, "4")
  field(FLNK, "HL2:SBPM:HL20:YOFF")
  info(autosaveFields, "VAL")
}

# Add CALC to allow users to maintain
# multiple offsets per plane per BPM

record(calcout, "HL2:SBPM:HL20:XOFF") {
  field(DESC, "Add X offsets")
  field(PREC, "4")
  field(CALC, "A+B+C+D")
  field(INPA, "HL2:SBPM:HL20:XAOFF")
# B-E reserved for undulator offsets
  field(INPB, "")
  field(INPC, "")
  field(INPD, "")
  field(INPE, "")
  field(EGU, "mm")
  field(OUT, "HL2:SBPM:HL20:X.AOFF")
  info(autosaveFields, "B C D E")
}

record(calcout, "HL2:SBPM:HL20:YOFF") {
  field(DESC, "Add Y offsets")
  field(PREC, "4")
  field(CALC, "A+B+C+D")
  field(INPA, "HL2:SBPM:HL20:YAOFF")
# B-E reserved for undulator offsets
  field(INPB, "")
  field(INPC, "")
  field(INPD, "")
  field(INPE, "")
  field(EGU, "mm")
  field(OUT, "HL2:SBPM:HL20:Y.AOFF")
  info(autosaveFields, "B C D E")
}


# Records to set MPS thresholds
record(ao, "HL2:SBPM:HL20:X_MPS_THRES_L") {
  field(DESC, "MPS X Threshold Lo")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C7 S0 @Lo")
  field(VAL,  "-1")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL2:SBPM:HL20:X_MPS_THRES_H") {
  field(DESC, "MPS X Threshold Hi")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C7 S0 @Hi")
  field(VAL,  "1")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL2:SBPM:HL20:Y_MPS_THRES_L") {
  field(DESC, "MPS Y Threshold Lo")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C7 S1 @Lo")
  field(VAL,  "-1")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL2:SBPM:HL20:Y_MPS_THRES_H") {
  field(DESC, "MPS Y Threshold Hi")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C7 S1 @Hi")
  field(VAL,  "1")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL2:SBPM:HL20:T_MPS_THRES_L") {
  field(DESC, "MPS TMIT Threshold Lo")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C7 S2 @Lo")
  field(VAL,  "9.375e7")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}
record(ao, "HL2:SBPM:HL20:T_MPS_THRES_H") {
  field(DESC, "MPS TMIT Threshold Hi")
  field(DTYP, "Bpm Mps Threshold")
  field(OUT,  "#C7 S2 @Hi")
  field(VAL,  "+1.0E20")
  field(EGU,  "mm")
  field(PREC, "4")
  field(PINI, "YES")
  field(ASG, "")
  info(autosaveFields, "VAL")
}

record(bi, "HL2:SBPM:HL20:FNET") {
  field(DESC, "BPM data on FNET")
  field(VAL, "$(FN,undefined)")
  field(ZNAM, "NO")
  field(ONAM, "YES")
  field(PINI, "YES")
}

# Record to inform users that BPM
# needs TMIT and/or X/Y scale calibration
record(mbbo, "HL2:SBPM:HL20:CHK") {
  field(DESC, "Needs cal/iron")
  field(OMSL, "supervisory")
  field(VAL,  "0")
  field(ZRVL, "0")
  field(ONVL, "1")
  field(TWVL, "2")
  field(THVL, "3")
  field(ZRST, " ")
  field(ONST, "Calibrate")
  field(TWST, "Calibrate&iron")
  field(THST, "Iron")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MINOR")
  field(THSV, "MINOR")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

# Switch simulation record 
record(seq, "HL2:SBPM:HL20:SIMCSEQ") {
  field(DESC, "BPM Sim Ctl Seq")
  field(SELM, "Mask")
  field(SELN, "0")

  field(DO1,  "1")
  field(DO2,  "0")
  field(DO3,  "0")
  field(DO4,  "0") #Passive

#  field(DO5,  "7") # .5 second
  field(DO5,  "9") # .1 second
  field(DO6,  "2")
  field(DO7,  "1")
  field(DO8,  "10")
  field(DO9,  "0")

# LNK 1, 2, 8, 9 only relevant for PADs
# Default macro values are set for PADs; other
# architectures must pass in "" for lnk1 and lnk2
  field(LNK1, "")
  field(LNK2, "")
  field(LNK3, "HL2:SBPM:HL20:SIM.L     PP")
  field(LNK4, "HL2:SBPM:HL20:SIM.SCAN  PP")

  field(LNK5, "HL2:SBPM:HL20:SIM.SCAN  PP")
  field(LNK6, "HL2:SBPM:HL20:SIM.L     PP")
  field(LNK7, "HL2:SBPM:HL20:SIM.L     PP")
  field(LNK8, "")
  field(LNK9, "")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL20:UOFF_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL20:UOFF")
	field(DOL2, "HL2:SBPM:HL20:UOFF")
	field(DOL3, "HL2:SBPM:HL20:UOFF")
	field(DOL4, "HL2:SBPM:HL20:UOFF")
	field(DOL5, "HL2:SBPM:HL20:UOFF")
	field(DOL6, "HL2:SBPM:HL20:UOFF")
	field(DOL7, "HL2:SBPM:HL20:UOFF")
	field(DOL8, "HL2:SBPM:HL20:UOFF")
	field(DOL9, "HL2:SBPM:HL20:UOFF")
	field(DOLA, "HL2:SBPM:HL20:UOFF")
	field(LNK1, "HL2:SBPM:HL20:UOFF_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL20:UOFF_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL20:UOFF_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL20:UOFF_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL20:UOFF_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL20:UOFF_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL20:UOFF_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL20:UOFF_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL20:UOFF_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL20:UOFF_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL20:UOFF_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL20:UOFF_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "0")
	field(B,    "0")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "4")
	field(FLNK, "HL2:SBPM:HL20:UOFF_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL20:UOFF_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL20:UOFF_SEL")
	field(OUTA, "HL2:SBPM:HL20:U.AOFF CA")
	field(OUTB, "HL2:SBPM:HL20:UOFF PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL20:UOFF_CTRL")
{
	field(INPA, "HL2:SBPM:HL20:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL20:UOFF_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL20:VOFF_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL20:VOFF")
	field(DOL2, "HL2:SBPM:HL20:VOFF")
	field(DOL3, "HL2:SBPM:HL20:VOFF")
	field(DOL4, "HL2:SBPM:HL20:VOFF")
	field(DOL5, "HL2:SBPM:HL20:VOFF")
	field(DOL6, "HL2:SBPM:HL20:VOFF")
	field(DOL7, "HL2:SBPM:HL20:VOFF")
	field(DOL8, "HL2:SBPM:HL20:VOFF")
	field(DOL9, "HL2:SBPM:HL20:VOFF")
	field(DOLA, "HL2:SBPM:HL20:VOFF")
	field(LNK1, "HL2:SBPM:HL20:VOFF_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL20:VOFF_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL20:VOFF_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL20:VOFF_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL20:VOFF_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL20:VOFF_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL20:VOFF_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL20:VOFF_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL20:VOFF_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL20:VOFF_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL20:VOFF_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL20:VOFF_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "0")
	field(B,    "0")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "4")
	field(FLNK, "HL2:SBPM:HL20:VOFF_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL20:VOFF_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL20:VOFF_SEL")
	field(OUTA, "HL2:SBPM:HL20:V.AOFF CA")
	field(OUTB, "HL2:SBPM:HL20:VOFF PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL20:VOFF_CTRL")
{
	field(INPA, "HL2:SBPM:HL20:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL20:VOFF_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL20:USCL_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL20:USCL")
	field(DOL2, "HL2:SBPM:HL20:USCL")
	field(DOL3, "HL2:SBPM:HL20:USCL")
	field(DOL4, "HL2:SBPM:HL20:USCL")
	field(DOL5, "HL2:SBPM:HL20:USCL")
	field(DOL6, "HL2:SBPM:HL20:USCL")
	field(DOL7, "HL2:SBPM:HL20:USCL")
	field(DOL8, "HL2:SBPM:HL20:USCL")
	field(DOL9, "HL2:SBPM:HL20:USCL")
	field(DOLA, "HL2:SBPM:HL20:USCL")
	field(LNK1, "HL2:SBPM:HL20:USCL_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL20:USCL_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL20:USCL_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL20:USCL_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL20:USCL_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL20:USCL_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL20:USCL_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL20:USCL_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL20:USCL_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL20:USCL_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL20:USCL_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL20:USCL_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "1")
	field(B,    "1")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "4")
	field(FLNK, "HL2:SBPM:HL20:USCL_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL20:USCL_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL20:USCL_SEL")
	field(OUTA, "HL2:SBPM:HL20:U.ASLO CA")
	field(OUTB, "HL2:SBPM:HL20:USCL PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL20:USCL_CTRL")
{
	field(INPA, "HL2:SBPM:HL20:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL20:USCL_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL20:VSCL_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL20:VSCL")
	field(DOL2, "HL2:SBPM:HL20:VSCL")
	field(DOL3, "HL2:SBPM:HL20:VSCL")
	field(DOL4, "HL2:SBPM:HL20:VSCL")
	field(DOL5, "HL2:SBPM:HL20:VSCL")
	field(DOL6, "HL2:SBPM:HL20:VSCL")
	field(DOL7, "HL2:SBPM:HL20:VSCL")
	field(DOL8, "HL2:SBPM:HL20:VSCL")
	field(DOL9, "HL2:SBPM:HL20:VSCL")
	field(DOLA, "HL2:SBPM:HL20:VSCL")
	field(LNK1, "HL2:SBPM:HL20:VSCL_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL20:VSCL_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL20:VSCL_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL20:VSCL_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL20:VSCL_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL20:VSCL_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL20:VSCL_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL20:VSCL_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL20:VSCL_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL20:VSCL_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL20:VSCL_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL20:VSCL_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "1")
	field(B,    "1")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "4")
	field(FLNK, "HL2:SBPM:HL20:VSCL_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL20:VSCL_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL20:VSCL_SEL")
	field(OUTA, "HL2:SBPM:HL20:V.ASLO CA")
	field(OUTB, "HL2:SBPM:HL20:VSCL PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL20:VSCL_CTRL")
{
	field(INPA, "HL2:SBPM:HL20:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL20:VSCL_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL20:PHI_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL20:PHI")
	field(DOL2, "HL2:SBPM:HL20:PHI")
	field(DOL3, "HL2:SBPM:HL20:PHI")
	field(DOL4, "HL2:SBPM:HL20:PHI")
	field(DOL5, "HL2:SBPM:HL20:PHI")
	field(DOL6, "HL2:SBPM:HL20:PHI")
	field(DOL7, "HL2:SBPM:HL20:PHI")
	field(DOL8, "HL2:SBPM:HL20:PHI")
	field(DOL9, "HL2:SBPM:HL20:PHI")
	field(DOLA, "HL2:SBPM:HL20:PHI")
	field(LNK1, "HL2:SBPM:HL20:PHI_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL20:PHI_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL20:PHI_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL20:PHI_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL20:PHI_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL20:PHI_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL20:PHI_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL20:PHI_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL20:PHI_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL20:PHI_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL20:PHI_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL20:PHI_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "0")
	field(B,    "0")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "1")
	field(FLNK, "HL2:SBPM:HL20:PHI_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL20:PHI_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL20:PHI_SEL")
	field(OUTA, "HL2:SBPM:HL20:CALC.E CA")
	field(OUTB, "HL2:SBPM:HL20:PHI PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL20:PHI_CTRL")
{
	field(INPA, "HL2:SBPM:HL20:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL20:PHI_SEL.L PP")
}
# Maintain multiple (up to 10) values of
# a parameter:
# 
# Record holding the parameter $[parm]
# must FLNK -> $[parm]_SEQ
#
# Different values of the parameter 
# $[parm0]..$[parm9] are stored in
# $[parm]_SEL.A .. $[parm]_SEL.J
#
# The actual value of the parameter is
# selected based on the value of a controlling
# PV $[ctrl] using a 'mapping' CALC expression
# $[mapc] to convert the $[ctrl] value into
# the integer range 1..10. 
#
# The selected value of $[parm] is written
# to output link $[outl]
#
# A) When the user writes $[parm] then
#    its value is deposited in the currently
#    selected field of $[parm]_SEL and
#    propagated to $[outl]
#
# B) When the user writes any of $[parm]_SEL.A..J
#    then the value is stored there. If she
#    writes to the currently 'active' field\
#    (as selected by $[ctrl]) then 
#    the $[parm] PV itself is updated and the
#    value is also propagated to $[outl]
#
# C) If the user changes $[ctrl] then the
#    corresponding value $[parm]_SEL.A..J is 
#    propagated to $[outl] and $[parm].
#
# D) At initialization, the value corresponding
#    to the initial setting of $[ctrl] is written
#    to $[outl] and $[parm]
#
# MACROS:
#
# $[parm]  PV holding the parameter
# $[ctrl]  PV that controls the selection of
#          the currently active setting of 
#          $[parm]
# $[outl]  PV where the currently selected 
#          value of $[parm] shall be written-to
#          (if applicable)
# $[prec]  Precision of the $[parm]_SEL variable
#          (should be set to same value as $[parm].PREC)
#
# $[parm0]..$[parm9] initial values of $[parm]
#
# $[mapc]  CALC expression to convert the value
#          of the controlling PV which is available
#          as 'A' to the range 1..10 (or less if
#          less selections are used).
#          E.g., to convert the value of a bo (0/1)
#          you would set mapc to 'A+1' (0..1 -> 1..2)
#
# NOTE:    This sb snippet is loaded/expanded
#          for every parameter under control
#          of $[ctrl]. ALSO, the companion
#          snippet parmCtl.db must be loaded/expanded
#          but only once per controlling PV.
#          

# This record, when scanned (as a result
# of $[parm] being written and processing
# its FLNK to this record] fetches $[parm]
# and deposits the value into the currently
# selected field of the SEL record.
# 
# NOTE: unfortunately, the selection
#       mechanism of the SEQ and SEL
#       records differs: SEQ is 1-based,
#       SEL is 0-based -- now that makes
#       sense, doesn't it?
#
record(seq, "HL2:SBPM:HL20:PSI_SEQ")
{
	field(DESC, "Propagate Parm -> SEL")
	field(DOL1, "HL2:SBPM:HL20:PSI")
	field(DOL2, "HL2:SBPM:HL20:PSI")
	field(DOL3, "HL2:SBPM:HL20:PSI")
	field(DOL4, "HL2:SBPM:HL20:PSI")
	field(DOL5, "HL2:SBPM:HL20:PSI")
	field(DOL6, "HL2:SBPM:HL20:PSI")
	field(DOL7, "HL2:SBPM:HL20:PSI")
	field(DOL8, "HL2:SBPM:HL20:PSI")
	field(DOL9, "HL2:SBPM:HL20:PSI")
	field(DOLA, "HL2:SBPM:HL20:PSI")
	field(LNK1, "HL2:SBPM:HL20:PSI_SEL.A PP")
	field(LNK2, "HL2:SBPM:HL20:PSI_SEL.B PP")
	field(LNK3, "HL2:SBPM:HL20:PSI_SEL.C PP")
	field(LNK4, "HL2:SBPM:HL20:PSI_SEL.D PP")
	field(LNK5, "HL2:SBPM:HL20:PSI_SEL.E PP")
	field(LNK6, "HL2:SBPM:HL20:PSI_SEL.F PP")
	field(LNK7, "HL2:SBPM:HL20:PSI_SEL.G PP")
	field(LNK8, "HL2:SBPM:HL20:PSI_SEL.H PP")
	field(LNK9, "HL2:SBPM:HL20:PSI_SEL.I PP")
	field(LNKA, "HL2:SBPM:HL20:PSI_SEL.J PP")
	field(SELM, "Specified")
	field(SELL, "HL2:SBPM:HL20:PSI_CTRL NPP NMS")
}

# The $[parm]_SEL record holds all possible
# values of $[parm] in the 'A..J' fields.
#
# When processed it updates it's own VAL
# to the currently selected input. Input
# 'L' serves as the (1-based) selector,
# i.e., L==1 selects 'A'->'VAL'.
# 
# When the selected value changes (as a 
# result of SEQ depositing a new value OR
# $[ctrl] changing and updating L) then
# the propagator record attached to the
# FLNK is processed.
#

record(sub, "HL2:SBPM:HL20:PSI_SEL")
{
#	field(INAM, "parmSelSubInit")
	field(SNAM, "parmSelSubProc")
	field(A,    "90")
	field(B,    "90")
	field(C,    "")
	field(D,    "")
	field(E,    "")
	field(F,    "")
	field(G,    "")
	field(H,    "")
	field(I,    "")
	field(J,    "")
	field(PREC, "1")
	field(FLNK, "HL2:SBPM:HL20:PSI_PROP")
  	info(autosaveFields, "A B C D E F G H I J")
}

#
# Finally the dfanout record 
# fetches the currently selected
# value from SEL and propagates it
# to $[outl]. It also updates
# $[parm] itself so that $[parm]
# always reflects the currently
# selected value.
#
record(dfanout,  "HL2:SBPM:HL20:PSI_PROP")
{
	field(OMSL, "closed_loop")
	field(DOL,  "HL2:SBPM:HL20:PSI_SEL")
	field(OUTA, "HL2:SBPM:HL20:CALC.F CA")
	field(OUTB, "HL2:SBPM:HL20:PSI PP")
}

# Drive the SEL record when the 'ctrl' PV changes
# Use a CA link to monitor such changes
record(calcout,  "HL2:SBPM:HL20:PSI_CTRL")
{
	field(INPA, "HL2:SBPM:HL20:PARMSEL CP")
	field(CALC, "A+1")
	field(DOPT, "Use CALC")
	field(OOPT, "On Change")
	field(OUT,  "HL2:SBPM:HL20:PSI_SEL.L PP")
}
record(longout, "HL2:SBPM:HL20:PARMSEL") {
	field(VAL, "0")
	field(PINI, "YES")
}
# bpmAfe.db; database for controlling stripline-BPM AFE
# This database should not be loaded on PADs w/o AFE hardware.
#
# THIS FILE WAS GENERATED WITH msi FROM bpmPadAfe.template or bpmVmeDigiAfe.db AND EXPANDED FOR
#
# !!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!
#  MODE: a -- Use VME IOC PVs
# !!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!
#
# NOTE: The template can be configured by means of proper macro
#       substitutions to 
#        a) operate in 'normal' LCLS stripline BPM mode. In this
#           mode a few CA links to the VME/main IOC are active fetching
#           '$(dev):ACCESS', '$(dev):ATTO' and '$(dev):CLAO' from the
#           main IOC.
#
#        b) standalone mode. In this mode, ACCESS is ignored and 'ATTO' and
#           'CLAO' are instantiated / hosted on the PAD IOC.
#
#        Mode 'a' is chosen by substituting
#        	  'suffix' ='L',
#        	'propomsl' = 'closed_loop'
#        	 'attomsl' = 'supervisory'
#        	   'chrgL' = '<charge PV> CPP'
#        	   'actlL' = '$(dev):ACCESS.RVAL CP'
#        	   'attoL' = '$(dev):ATTO CP'
#        	   'claoL' = '$(dev):CLAO CP'
#
#        Mode 'b' is chosen by substituting
#             'suffix' = '' (empty)
#        	'propomsl' = 'supervisory'
#        	 'attomsl' = 'supervisory'
#        	   'chrgL' = '0'
#        	   'actlL' = '0'
#        	   'attoL' = '0'
#        	   'claoL' = '0'
#
# SUBSTITUTIONS:
#  Substitutions available in main .db file
#    'dev' : device name prefix
#   'chrg' : name of global attenuator PV (for scaling all AFE attenuators with beam charge)(mode a) or '0' (mode b)
#            'chrg' is only available in mode 'a'.
#
#  Substitutions available in the template -- intended to be expanded when generating '.db' with MSI.
#
#  'chrgL' : name of global attenuator PV (for scaling all AFE attenuators with beam charge) + CPP attribute (mode a) or '0' (mode b)
#  'actlL' : name of ACCESS.RVAL PV + CP attribute (mode a) or '0' (mode b)
#  'attoL' : name of ATTO PV + CP attribute (mode a) or '0' (mode b)
#  'claoL' : name of CLAO PV + CP attribute (mode a) or '0' (mode b)
#'attomsl' : default/initial OMSL; if 'supervisory' then the 'ATT' PV controls attenuators
#            if 'closed_loop' then ATT is fetched from it's DOL (=='chrg' PV).
# 'suffix' : see above.
#'propomsl': see above.
#
# LINKS (pointing outside of this file): These links are only used in mode a and set to '0' in mode b.
#     HL1:SBPM:HL13:ATT.DOL  <---- VIOC:GUN:BPM:ATTR CPP    // DEFINED IN: [depends on 'chrg' macro substitution].
#     HL1:SBPM:HL13:ACTL.DOL <---- HL1:SBPM:HL13:ACCESS.RVAL CP // DEFINED IN: associated main IOC database 'IOC-<loc>-BP<unit>bpm.db'
#     HL1:SBPM:HL13:ATTOL.DOL<---- HL1:SBPM:HL13:ATTO CP // DEFINED IN: associated main IOC database 'IOC-<loc>-BP<unit>bpm.db'
#     HL1:SBPM:HL13:CLAOL.DOL<---- HL1:SBPM:HL13:CLAO CP // DEFINED IN: associated main IOC database 'IOC-<loc>-BP<unit>bpm.db'
#
#
#
#  Additional macros added to support other architectures. These macros do NOT need to be populated for PAD AFEs
#  because the default value is set for them:
#
# 	instance - AFE identifier (0,1,... or identifying string)
#	devsup   - device support name (qspiAfe for 'generic' suppport used by SLAC RTM and XTA AFE)
#       type     - AFE flavor, 0 for PAD, 1 for XTA, 2 for RTM

#

record(longout, "HL1:SBPM:HL13:CALA") {
	field(DESC, "AFE Cal. Att.")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE0+1,qspiAfe")
	field(LOPR, "0")
	field(HOPR, "31")
	field(DRVL, "6")
	field(DRVH, "31")
	field(EGU,  "dB")
}

record(longout, "HL1:SBPM:HL13:ATT1") {
	field(DESC, "AFE Att. 1")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE0+2,qspiAfe")
	field(LOPR, "0")
	field(HOPR, "15")
	field(DRVL, "0")
	field(DRVH, "15")
	field(EGU,  "dB")
}

record(longout, "HL1:SBPM:HL13:ATT2") {
	field(DESC, "AFE Att. 2")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE0+3,qspiAfe")
	field(EGU,  "dB")
	field(LOPR, "0")
	field(HOPR, "31")
	field(DRVL, "0")
	field(DRVH, "31")
	field(EGU,  "dB")
}

# AFE FW versions (decimal):
# 4     original LCLS-I FW version
# >=32  ATT2 has 32 dB range; before 16 dB
# 33    200 MHz board
# 34    140 MHz board w/ 6dB PAD removed
# 35    200 MHz board w/ 6dB PAD removed
# > 64  140 MHz board not used with PAD/coldfire (XTA)
# 8     MicroTCA RTM
record(longin, "HL1:SBPM:HL13:VERS") {
	field(DESC, "AFE Firmware Vers.")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(INP,  "#C0S0@AFE0+5,qspiAfe")
	field(LOLO, "3")
	field(LLSV, "MAJOR")
	field(PINI, "YES")
	field(FLNK, "HL1:SBPM:HL13:ATTINIT")
}

record(longout, "HL1:SBPM:HL13:AODL") {
	field(DESC, "Delay Trig -> AMP On")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE0+0x10,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
}

record(longout, "HL1:SBPM:HL13:R1DL") {
	field(DESC, "Delay AMP On -> RF1")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE0+0x11,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
}

record(longout, "HL1:SBPM:HL13:RFWD") {
	field(DESC, "RF Pulse Width")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE0+0x13,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
	info(autosaveFields, "VAL")
}

record(longout, "HL1:SBPM:HL13:OFFT") {
	field(DESC, "Delay RF Off -> Ctrl Sw.")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE0+0x14,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
}

record(longout, "HL1:SBPM:HL13:R2DL") {
	field(DESC, "Ctrl Sw. -> RF2")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE0+0x12,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
}

# This record just issues a CAL trigger
record(longout, "HL1:SBPM:HL13:CALT") {
	field(DESC, "AFE CAL Soft Trigger")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE0+6,qspiAfe")
}

record(mbbo,   "HL1:SBPM:HL13:CALM") {
        field(DESC, "AFE Cal. Mode")
        field(DTYP, "BusAddress")
        field(OUT,  "#C0S0@AFE0+0,softTogAfe")
        field(NOBT, "2")
        field(SHFT, "0")
        field(ZRST, "CAL RED")
        field(ZRVL, "0")
        field(ONST, "CAL GRN")
        field(ONVL, "1")
        field(THST, "CAL NONE")
        field(THVL, "3")
# 'soft toggle' mode. NOTE: LSB must match RED or GRN
# which choses the mode to start with
        field(FRST, "CAL TOGGLE")
        field(FRVL, "4")
        field(VAL,  "4")
        field(PINI, "YES")
}

# Subroutine to set up attenuator limits at ioc startup.
# Attenuator ranges vary among AFE types and FW versions
# This record also in bpmVmeDigiAfePart.db
record(aSub, "HL1:SBPM:HL13:ATTINIT") {
        field(DESC, "Set up AFE att limits")
        field(SNAM, "subAttSetup")
        field(FTA,  "LONG")
        field(INPA, "HL1:SBPM:HL13:VERS")
        field(FTVA, "LONG")
        field(OUTA, "HL1:SBPM:HL13:ATT1.HOPR")
        field(FTVB, "LONG")
        field(OUTB, "HL1:SBPM:HL13:ATT1.DRVH")
        field(FTVC, "LONG")
        field(OUTC, "HL1:SBPM:HL13:ATT2.HOPR")
        field(FTVD, "LONG")
        field(OUTD, "HL1:SBPM:HL13:ATT2.DRVH")
        field(FTVE, "LONG")
        field(OUTE, "HL1:SBPM:HL13:ATT.HOPR")
        field(FTVF, "LONG")
        field(OUTF, "HL1:SBPM:HL13:ATT.DRVH")
        field(FTVG, "LONG")
        field(OUTG, "HL1:SBPM:HL13:ATT.VAL")
        field(FTVH, "LONG")
        field(OUTH, "HL1:SBPM:HL13:ATTC.D")
        field(FTVI, "LONG")
        field(OUTI, "HL1:SBPM:HL13:ATTC.E")
        field(FTVJ, "LONG")
        field(OUTJ, "HL1:SBPM:HL13:ATTC.F")
        field(FTVK, "LONG")
        field(OUTK, "HL1:SBPM:HL13:ATTO.DRVL")
        field(FTVL, "LONG")
        field(OUTL, "HL1:SBPM:HL13:ATTO.LOPR")
        field(FTVM, "LONG")
        field(OUTM, "HL1:SBPM:HL13:ATTO.DRVH")
        field(FTVN, "LONG")
        field(OUTN, "HL1:SBPM:HL13:ATTO.HOPR")
        field(FTVO, "LONG")
        field(OUTO, "HL1:SBPM:HL13:CLAO.DRVL")
        field(FTVP, "LONG")
        field(OUTP, "HL1:SBPM:HL13:CLAO.LOPR")
        field(FTVQ, "LONG")
        field(OUTQ, "HL1:SBPM:HL13:CLAO.DRVH")
        field(FTVR, "LONG")
        field(OUTR, "HL1:SBPM:HL13:CLAO.HOPR")
        field(FLNK, "HL1:SBPM:HL13:ATT")
}

# Total attenuation (but ATTO is still added to this)
record(longout, "HL1:SBPM:HL13:ATT") {
	field(DESC, "AFE Total Attenuation")
	field(OUT,  "HL1:SBPM:HL13:ATTC.A PP")
	field(DRVL, "0")
	field(DRVH, "30")
	field(LOPR, "0")
	field(HOPR, "30")
	field(EGU,  "dB")
	field(DOL,  "VIOC:GUN:BPM:ATTR CPP")
	field(OMSL, "supervisory")
	field(VAL,  "30")
}

# This subroutine record performs the
# following operation (ATTC.D defines
# the breakpoint where ATT1 kicks in 
# -- it depends on losses and gains:
#    BPT = G1 + L1 - L2
# with
#  G1: gain of 1st stage,
#  L1: loss + NF upstream of 1st stage,
#  L2: loss between 1st and 2nd stage + NF of 2nd stage
#
# if L1 : 2dB cable, 3dB 1st Filter, 1dB Att1 residual, 2.8dB NF =  8.8dB
#    L2 : 1dB Att2 residual, 4.5dB BPF, 3dB NF                   =  8.5dB
#    G1 :                                                        = 20.0dB
#
# -> breakpoint ~ 20dB
#
#-----------------------------------------------------------------------------
# New RTM AFE characteristics are different (assume 140 ft LMR: 2.2db/100ft):
#    L1 : 3.1 dB cable, 4.5 dB 1st BPF, 1.1 dB att1, 3.3dB NF    = 12.0dB
#    L2 : 1.1 dB att2, 2.7 dB NF, 1 dB BPF                       =  4.8dB
#    G1 :                                                        = 16.0dB
#
# -> breakpoint ~ 23dB
#
#-----------------------------------------------------------------------------
#
# Semantics of the different fields
#  A: Total attenuation (ATT records deposits value there)
#  B: ATTO
#  C: CLAO
#  D: BPT Breakpoint (see above)
#  E: (ATT1MAX) max. ATT1 attenuation (depends on version, set by ATTINIT)
#  F: (ATT2MAX) max. ATT2 attenuation (depends on version, set by ATTINIT)
#
# if ( (T=ATT+ATTO) > ATT1MAX + ATT2MAX )
#    T = ATT1MAX + ATT2MAX
# endif
#
# if ( (A1 = floor((T - BPT)/2)) < 0 )
#    A1 = 0;
#    A2 = T;
# else
#    if (A1 > ATT1MAX) 
#      A1 = ATT1MAX;
#    endif
#    A2 = T - A1
# endif
#
# if ( A2 > ATT2MAX )
#    A1 = A2-ATT2MAX
#    A2 = ATT2MAX
# endif
#
#    CA = CLAO + ATT1MAX + ATT2MAX - ATT
# if ( CA < 0 )
#    CA = 0
# else if ( CA > ACMAX )
#    CA = ACMAX
# endif
#
# Then, it writes three links:
#  HL1:SBPM:HL13:ATT1 = A1
#  HL1:SBPM:HL13:ATT2 = A2
#  HL1:SBPM:HL13:CALA = CA
#

record(sub, "HL1:SBPM:HL13:ATTC") {
	# Note: this record uses it's name to calculate
	# db link addresses to ATT1, ATT2, CALA
	field(DESC, "AFE Total Att. Calc.")
	# initialize fields to max. attenuation:
	# During init:
	#    1. hw initializes to max
	#    2. this record holds max
	#    3. PINI of the placeholder PVs (ATT, ATTO & friends)
	#       trickle in and cause the total attenuation to
	#       go down...
	field(A,    "30")
	field(B,    "0")
	field(C,    "60")
	field(D,    "20")
	field(EGU,  "dB")
	field(INAM, "subAttIni")
	field(SNAM, "subAtt")
}

#propagate 'ACCESS.RVAL' state to 
#attenuator control
#This record is unused in stdalone mode 'b'
record(bo, "HL1:SBPM:HL13:ACTL") {
	field(DESC, "ATT OMSL Ctrl")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL1:SBPM:HL13:ACCESS.RVAL CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL1:SBPM:HL13:ATT.OMSL PP")
}

###
### Keep 'ATTO' and 'CLAO' on the main/VME IOC.
### It is more confusing but then we don't have
### to restore anything across reboots on the PAD
### IOC...
###
### This db now used for AFEs controlled by either
### a VME IOC or a PAD IOC. Use the same db for 
### both for simplicity.
###
### NOTE: We could use the INPB / INPC
###       links of ATTC directly but we DONT.
###       Potentially, ATTC can be processed
###       on every shot -- we don't want the
###       links to be fetched every time for
###       efficiency reasons. Hence the 'propagator'
###       records which monitor ATTO/CLAO and
###       write to ATTC.B ATTC.C only when
###       necessary...
record(longout, "HL1:SBPM:HL13:ATTOL") {
	field(DESC, "ATTO Propagator")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL1:SBPM:HL13:ATTO CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL1:SBPM:HL13:ATTC.B PP")
	field(EGU,  "dB")
}

record(longout, "HL1:SBPM:HL13:CLAOL") {
	field(DESC, "CLAO Propagator")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL1:SBPM:HL13:CLAO CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL1:SBPM:HL13:ATTC.C PP")
	field(EGU,  "dB")
}
# Records only needed for RTM AFE

record(longout, "HL1:SBPM:HL13:TRIG2BEAM") {
	field(DESC, "Trigger -> ADC trig")
	field(DTYP, "BusAddress")
	field(OUT,  "#C0S0@AFE0+0x15,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVH, "255")
	field(PINI, "YES")
	info(autosaveFields, "VAL")
}

record(longout, "HL1:SBPM:HL13:RF2RED") {
	field(DESC, "Red RF -> ADC trig")
	field(DTYP, "BusAddress")
	field(OUT,  "#C0S0@AFE0+0x16,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVH, "255")
	field(VAL,  "6")
	field(PINI, "YES")
	info(autosaveFields, "VAL")
}

record(longout, "HL1:SBPM:HL13:RF2GRN") {
	field(DESC, "Grn RF -> ADC trig")
	field(DTYP, "BusAddress")
	field(OUT,  "#C0S0@AFE0+0x17,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVH, "255")
	field(VAL,  "6")
	field(PINI, "YES")
	info(autosaveFields, "VAL")
}
# bpmAfe.db; database for controlling stripline-BPM AFE
# This database should not be loaded on PADs w/o AFE hardware.
#
# THIS FILE WAS GENERATED WITH msi FROM bpmPadAfe.template or bpmVmeDigiAfe.db AND EXPANDED FOR
#
# !!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!
#  MODE: a -- Use VME IOC PVs
# !!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!
#
# NOTE: The template can be configured by means of proper macro
#       substitutions to 
#        a) operate in 'normal' LCLS stripline BPM mode. In this
#           mode a few CA links to the VME/main IOC are active fetching
#           '$(dev):ACCESS', '$(dev):ATTO' and '$(dev):CLAO' from the
#           main IOC.
#
#        b) standalone mode. In this mode, ACCESS is ignored and 'ATTO' and
#           'CLAO' are instantiated / hosted on the PAD IOC.
#
#        Mode 'a' is chosen by substituting
#        	  'suffix' ='L',
#        	'propomsl' = 'closed_loop'
#        	 'attomsl' = 'supervisory'
#        	   'chrgL' = '<charge PV> CPP'
#        	   'actlL' = '$(dev):ACCESS.RVAL CP'
#        	   'attoL' = '$(dev):ATTO CP'
#        	   'claoL' = '$(dev):CLAO CP'
#
#        Mode 'b' is chosen by substituting
#             'suffix' = '' (empty)
#        	'propomsl' = 'supervisory'
#        	 'attomsl' = 'supervisory'
#        	   'chrgL' = '0'
#        	   'actlL' = '0'
#        	   'attoL' = '0'
#        	   'claoL' = '0'
#
# SUBSTITUTIONS:
#  Substitutions available in main .db file
#    'dev' : device name prefix
#   'chrg' : name of global attenuator PV (for scaling all AFE attenuators with beam charge)(mode a) or '0' (mode b)
#            'chrg' is only available in mode 'a'.
#
#  Substitutions available in the template -- intended to be expanded when generating '.db' with MSI.
#
#  'chrgL' : name of global attenuator PV (for scaling all AFE attenuators with beam charge) + CPP attribute (mode a) or '0' (mode b)
#  'actlL' : name of ACCESS.RVAL PV + CP attribute (mode a) or '0' (mode b)
#  'attoL' : name of ATTO PV + CP attribute (mode a) or '0' (mode b)
#  'claoL' : name of CLAO PV + CP attribute (mode a) or '0' (mode b)
#'attomsl' : default/initial OMSL; if 'supervisory' then the 'ATT' PV controls attenuators
#            if 'closed_loop' then ATT is fetched from it's DOL (=='chrg' PV).
# 'suffix' : see above.
#'propomsl': see above.
#
# LINKS (pointing outside of this file): These links are only used in mode a and set to '0' in mode b.
#     HL2:SBPM:HL14:ATT.DOL  <---- VIOC:GUN:BPM:ATTR CPP    // DEFINED IN: [depends on 'chrg' macro substitution].
#     HL2:SBPM:HL14:ACTL.DOL <---- HL2:SBPM:HL14:ACCESS.RVAL CP // DEFINED IN: associated main IOC database 'IOC-<loc>-BP<unit>bpm.db'
#     HL2:SBPM:HL14:ATTOL.DOL<---- HL2:SBPM:HL14:ATTO CP // DEFINED IN: associated main IOC database 'IOC-<loc>-BP<unit>bpm.db'
#     HL2:SBPM:HL14:CLAOL.DOL<---- HL2:SBPM:HL14:CLAO CP // DEFINED IN: associated main IOC database 'IOC-<loc>-BP<unit>bpm.db'
#
#
#
#  Additional macros added to support other architectures. These macros do NOT need to be populated for PAD AFEs
#  because the default value is set for them:
#
# 	instance - AFE identifier (0,1,... or identifying string)
#	devsup   - device support name (qspiAfe for 'generic' suppport used by SLAC RTM and XTA AFE)
#       type     - AFE flavor, 0 for PAD, 1 for XTA, 2 for RTM

#

record(longout, "HL2:SBPM:HL14:CALA") {
	field(DESC, "AFE Cal. Att.")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE1+1,qspiAfe")
	field(LOPR, "0")
	field(HOPR, "31")
	field(DRVL, "6")
	field(DRVH, "31")
	field(EGU,  "dB")
}

record(longout, "HL2:SBPM:HL14:ATT1") {
	field(DESC, "AFE Att. 1")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE1+2,qspiAfe")
	field(LOPR, "0")
	field(HOPR, "15")
	field(DRVL, "0")
	field(DRVH, "15")
	field(EGU,  "dB")
}

record(longout, "HL2:SBPM:HL14:ATT2") {
	field(DESC, "AFE Att. 2")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE1+3,qspiAfe")
	field(EGU,  "dB")
	field(LOPR, "0")
	field(HOPR, "31")
	field(DRVL, "0")
	field(DRVH, "31")
	field(EGU,  "dB")
}

# AFE FW versions (decimal):
# 4     original LCLS-I FW version
# >=32  ATT2 has 32 dB range; before 16 dB
# 33    200 MHz board
# 34    140 MHz board w/ 6dB PAD removed
# 35    200 MHz board w/ 6dB PAD removed
# > 64  140 MHz board not used with PAD/coldfire (XTA)
# 8     MicroTCA RTM
record(longin, "HL2:SBPM:HL14:VERS") {
	field(DESC, "AFE Firmware Vers.")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(INP,  "#C0S0@AFE1+5,qspiAfe")
	field(LOLO, "3")
	field(LLSV, "MAJOR")
	field(PINI, "YES")
	field(FLNK, "HL2:SBPM:HL14:ATTINIT")
}

record(longout, "HL2:SBPM:HL14:AODL") {
	field(DESC, "Delay Trig -> AMP On")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE1+0x10,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
}

record(longout, "HL2:SBPM:HL14:R1DL") {
	field(DESC, "Delay AMP On -> RF1")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE1+0x11,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
}

record(longout, "HL2:SBPM:HL14:RFWD") {
	field(DESC, "RF Pulse Width")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE1+0x13,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
	info(autosaveFields, "VAL")
}

record(longout, "HL2:SBPM:HL14:OFFT") {
	field(DESC, "Delay RF Off -> Ctrl Sw.")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE1+0x14,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
}

record(longout, "HL2:SBPM:HL14:R2DL") {
	field(DESC, "Ctrl Sw. -> RF2")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE1+0x12,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
}

# This record just issues a CAL trigger
record(longout, "HL2:SBPM:HL14:CALT") {
	field(DESC, "AFE CAL Soft Trigger")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE1+6,qspiAfe")
}

record(mbbo,   "HL2:SBPM:HL14:CALM") {
        field(DESC, "AFE Cal. Mode")
        field(DTYP, "BusAddress")
        field(OUT,  "#C0S0@AFE1+0,softTogAfe")
        field(NOBT, "2")
        field(SHFT, "0")
        field(ZRST, "CAL RED")
        field(ZRVL, "0")
        field(ONST, "CAL GRN")
        field(ONVL, "1")
        field(THST, "CAL NONE")
        field(THVL, "3")
# 'soft toggle' mode. NOTE: LSB must match RED or GRN
# which choses the mode to start with
        field(FRST, "CAL TOGGLE")
        field(FRVL, "4")
        field(VAL,  "4")
        field(PINI, "YES")
}

# Subroutine to set up attenuator limits at ioc startup.
# Attenuator ranges vary among AFE types and FW versions
# This record also in bpmVmeDigiAfePart.db
record(aSub, "HL2:SBPM:HL14:ATTINIT") {
        field(DESC, "Set up AFE att limits")
        field(SNAM, "subAttSetup")
        field(FTA,  "LONG")
        field(INPA, "HL2:SBPM:HL14:VERS")
        field(FTVA, "LONG")
        field(OUTA, "HL2:SBPM:HL14:ATT1.HOPR")
        field(FTVB, "LONG")
        field(OUTB, "HL2:SBPM:HL14:ATT1.DRVH")
        field(FTVC, "LONG")
        field(OUTC, "HL2:SBPM:HL14:ATT2.HOPR")
        field(FTVD, "LONG")
        field(OUTD, "HL2:SBPM:HL14:ATT2.DRVH")
        field(FTVE, "LONG")
        field(OUTE, "HL2:SBPM:HL14:ATT.HOPR")
        field(FTVF, "LONG")
        field(OUTF, "HL2:SBPM:HL14:ATT.DRVH")
        field(FTVG, "LONG")
        field(OUTG, "HL2:SBPM:HL14:ATT.VAL")
        field(FTVH, "LONG")
        field(OUTH, "HL2:SBPM:HL14:ATTC.D")
        field(FTVI, "LONG")
        field(OUTI, "HL2:SBPM:HL14:ATTC.E")
        field(FTVJ, "LONG")
        field(OUTJ, "HL2:SBPM:HL14:ATTC.F")
        field(FTVK, "LONG")
        field(OUTK, "HL2:SBPM:HL14:ATTO.DRVL")
        field(FTVL, "LONG")
        field(OUTL, "HL2:SBPM:HL14:ATTO.LOPR")
        field(FTVM, "LONG")
        field(OUTM, "HL2:SBPM:HL14:ATTO.DRVH")
        field(FTVN, "LONG")
        field(OUTN, "HL2:SBPM:HL14:ATTO.HOPR")
        field(FTVO, "LONG")
        field(OUTO, "HL2:SBPM:HL14:CLAO.DRVL")
        field(FTVP, "LONG")
        field(OUTP, "HL2:SBPM:HL14:CLAO.LOPR")
        field(FTVQ, "LONG")
        field(OUTQ, "HL2:SBPM:HL14:CLAO.DRVH")
        field(FTVR, "LONG")
        field(OUTR, "HL2:SBPM:HL14:CLAO.HOPR")
        field(FLNK, "HL2:SBPM:HL14:ATT")
}

# Total attenuation (but ATTO is still added to this)
record(longout, "HL2:SBPM:HL14:ATT") {
	field(DESC, "AFE Total Attenuation")
	field(OUT,  "HL2:SBPM:HL14:ATTC.A PP")
	field(DRVL, "0")
	field(DRVH, "30")
	field(LOPR, "0")
	field(HOPR, "30")
	field(EGU,  "dB")
	field(DOL,  "VIOC:GUN:BPM:ATTR CPP")
	field(OMSL, "supervisory")
	field(VAL,  "30")
}

# This subroutine record performs the
# following operation (ATTC.D defines
# the breakpoint where ATT1 kicks in 
# -- it depends on losses and gains:
#    BPT = G1 + L1 - L2
# with
#  G1: gain of 1st stage,
#  L1: loss + NF upstream of 1st stage,
#  L2: loss between 1st and 2nd stage + NF of 2nd stage
#
# if L1 : 2dB cable, 3dB 1st Filter, 1dB Att1 residual, 2.8dB NF =  8.8dB
#    L2 : 1dB Att2 residual, 4.5dB BPF, 3dB NF                   =  8.5dB
#    G1 :                                                        = 20.0dB
#
# -> breakpoint ~ 20dB
#
#-----------------------------------------------------------------------------
# New RTM AFE characteristics are different (assume 140 ft LMR: 2.2db/100ft):
#    L1 : 3.1 dB cable, 4.5 dB 1st BPF, 1.1 dB att1, 3.3dB NF    = 12.0dB
#    L2 : 1.1 dB att2, 2.7 dB NF, 1 dB BPF                       =  4.8dB
#    G1 :                                                        = 16.0dB
#
# -> breakpoint ~ 23dB
#
#-----------------------------------------------------------------------------
#
# Semantics of the different fields
#  A: Total attenuation (ATT records deposits value there)
#  B: ATTO
#  C: CLAO
#  D: BPT Breakpoint (see above)
#  E: (ATT1MAX) max. ATT1 attenuation (depends on version, set by ATTINIT)
#  F: (ATT2MAX) max. ATT2 attenuation (depends on version, set by ATTINIT)
#
# if ( (T=ATT+ATTO) > ATT1MAX + ATT2MAX )
#    T = ATT1MAX + ATT2MAX
# endif
#
# if ( (A1 = floor((T - BPT)/2)) < 0 )
#    A1 = 0;
#    A2 = T;
# else
#    if (A1 > ATT1MAX) 
#      A1 = ATT1MAX;
#    endif
#    A2 = T - A1
# endif
#
# if ( A2 > ATT2MAX )
#    A1 = A2-ATT2MAX
#    A2 = ATT2MAX
# endif
#
#    CA = CLAO + ATT1MAX + ATT2MAX - ATT
# if ( CA < 0 )
#    CA = 0
# else if ( CA > ACMAX )
#    CA = ACMAX
# endif
#
# Then, it writes three links:
#  HL2:SBPM:HL14:ATT1 = A1
#  HL2:SBPM:HL14:ATT2 = A2
#  HL2:SBPM:HL14:CALA = CA
#

record(sub, "HL2:SBPM:HL14:ATTC") {
	# Note: this record uses it's name to calculate
	# db link addresses to ATT1, ATT2, CALA
	field(DESC, "AFE Total Att. Calc.")
	# initialize fields to max. attenuation:
	# During init:
	#    1. hw initializes to max
	#    2. this record holds max
	#    3. PINI of the placeholder PVs (ATT, ATTO & friends)
	#       trickle in and cause the total attenuation to
	#       go down...
	field(A,    "30")
	field(B,    "0")
	field(C,    "60")
	field(D,    "20")
	field(EGU,  "dB")
	field(INAM, "subAttIni")
	field(SNAM, "subAtt")
}

#propagate 'ACCESS.RVAL' state to 
#attenuator control
#This record is unused in stdalone mode 'b'
record(bo, "HL2:SBPM:HL14:ACTL") {
	field(DESC, "ATT OMSL Ctrl")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL2:SBPM:HL14:ACCESS.RVAL CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL2:SBPM:HL14:ATT.OMSL PP")
}

###
### Keep 'ATTO' and 'CLAO' on the main/VME IOC.
### It is more confusing but then we don't have
### to restore anything across reboots on the PAD
### IOC...
###
### This db now used for AFEs controlled by either
### a VME IOC or a PAD IOC. Use the same db for 
### both for simplicity.
###
### NOTE: We could use the INPB / INPC
###       links of ATTC directly but we DONT.
###       Potentially, ATTC can be processed
###       on every shot -- we don't want the
###       links to be fetched every time for
###       efficiency reasons. Hence the 'propagator'
###       records which monitor ATTO/CLAO and
###       write to ATTC.B ATTC.C only when
###       necessary...
record(longout, "HL2:SBPM:HL14:ATTOL") {
	field(DESC, "ATTO Propagator")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL2:SBPM:HL14:ATTO CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL2:SBPM:HL14:ATTC.B PP")
	field(EGU,  "dB")
}

record(longout, "HL2:SBPM:HL14:CLAOL") {
	field(DESC, "CLAO Propagator")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL2:SBPM:HL14:CLAO CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL2:SBPM:HL14:ATTC.C PP")
	field(EGU,  "dB")
}
# Records only needed for RTM AFE

record(longout, "HL2:SBPM:HL14:TRIG2BEAM") {
	field(DESC, "Trigger -> ADC trig")
	field(DTYP, "BusAddress")
	field(OUT,  "#C0S0@AFE1+0x15,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVH, "255")
	field(PINI, "YES")
	info(autosaveFields, "VAL")
}

record(longout, "HL2:SBPM:HL14:RF2RED") {
	field(DESC, "Red RF -> ADC trig")
	field(DTYP, "BusAddress")
	field(OUT,  "#C0S0@AFE1+0x16,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVH, "255")
	field(VAL,  "6")
	field(PINI, "YES")
	info(autosaveFields, "VAL")
}

record(longout, "HL2:SBPM:HL14:RF2GRN") {
	field(DESC, "Grn RF -> ADC trig")
	field(DTYP, "BusAddress")
	field(OUT,  "#C0S0@AFE1+0x17,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVH, "255")
	field(VAL,  "6")
	field(PINI, "YES")
	info(autosaveFields, "VAL")
}
# bpmAfe.db; database for controlling stripline-BPM AFE
# This database should not be loaded on PADs w/o AFE hardware.
#
# THIS FILE WAS GENERATED WITH msi FROM bpmPadAfe.template or bpmVmeDigiAfe.db AND EXPANDED FOR
#
# !!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!
#  MODE: a -- Use VME IOC PVs
# !!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!
#
# NOTE: The template can be configured by means of proper macro
#       substitutions to 
#        a) operate in 'normal' LCLS stripline BPM mode. In this
#           mode a few CA links to the VME/main IOC are active fetching
#           '$(dev):ACCESS', '$(dev):ATTO' and '$(dev):CLAO' from the
#           main IOC.
#
#        b) standalone mode. In this mode, ACCESS is ignored and 'ATTO' and
#           'CLAO' are instantiated / hosted on the PAD IOC.
#
#        Mode 'a' is chosen by substituting
#        	  'suffix' ='L',
#        	'propomsl' = 'closed_loop'
#        	 'attomsl' = 'supervisory'
#        	   'chrgL' = '<charge PV> CPP'
#        	   'actlL' = '$(dev):ACCESS.RVAL CP'
#        	   'attoL' = '$(dev):ATTO CP'
#        	   'claoL' = '$(dev):CLAO CP'
#
#        Mode 'b' is chosen by substituting
#             'suffix' = '' (empty)
#        	'propomsl' = 'supervisory'
#        	 'attomsl' = 'supervisory'
#        	   'chrgL' = '0'
#        	   'actlL' = '0'
#        	   'attoL' = '0'
#        	   'claoL' = '0'
#
# SUBSTITUTIONS:
#  Substitutions available in main .db file
#    'dev' : device name prefix
#   'chrg' : name of global attenuator PV (for scaling all AFE attenuators with beam charge)(mode a) or '0' (mode b)
#            'chrg' is only available in mode 'a'.
#
#  Substitutions available in the template -- intended to be expanded when generating '.db' with MSI.
#
#  'chrgL' : name of global attenuator PV (for scaling all AFE attenuators with beam charge) + CPP attribute (mode a) or '0' (mode b)
#  'actlL' : name of ACCESS.RVAL PV + CP attribute (mode a) or '0' (mode b)
#  'attoL' : name of ATTO PV + CP attribute (mode a) or '0' (mode b)
#  'claoL' : name of CLAO PV + CP attribute (mode a) or '0' (mode b)
#'attomsl' : default/initial OMSL; if 'supervisory' then the 'ATT' PV controls attenuators
#            if 'closed_loop' then ATT is fetched from it's DOL (=='chrg' PV).
# 'suffix' : see above.
#'propomsl': see above.
#
# LINKS (pointing outside of this file): These links are only used in mode a and set to '0' in mode b.
#     HL2:SBPM:HL15:ATT.DOL  <---- VIOC:GUN:BPM:ATTR CPP    // DEFINED IN: [depends on 'chrg' macro substitution].
#     HL2:SBPM:HL15:ACTL.DOL <---- HL2:SBPM:HL15:ACCESS.RVAL CP // DEFINED IN: associated main IOC database 'IOC-<loc>-BP<unit>bpm.db'
#     HL2:SBPM:HL15:ATTOL.DOL<---- HL2:SBPM:HL15:ATTO CP // DEFINED IN: associated main IOC database 'IOC-<loc>-BP<unit>bpm.db'
#     HL2:SBPM:HL15:CLAOL.DOL<---- HL2:SBPM:HL15:CLAO CP // DEFINED IN: associated main IOC database 'IOC-<loc>-BP<unit>bpm.db'
#
#
#
#  Additional macros added to support other architectures. These macros do NOT need to be populated for PAD AFEs
#  because the default value is set for them:
#
# 	instance - AFE identifier (0,1,... or identifying string)
#	devsup   - device support name (qspiAfe for 'generic' suppport used by SLAC RTM and XTA AFE)
#       type     - AFE flavor, 0 for PAD, 1 for XTA, 2 for RTM

#

record(longout, "HL2:SBPM:HL15:CALA") {
	field(DESC, "AFE Cal. Att.")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE2+1,qspiAfe")
	field(LOPR, "0")
	field(HOPR, "31")
	field(DRVL, "6")
	field(DRVH, "31")
	field(EGU,  "dB")
}

record(longout, "HL2:SBPM:HL15:ATT1") {
	field(DESC, "AFE Att. 1")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE2+2,qspiAfe")
	field(LOPR, "0")
	field(HOPR, "15")
	field(DRVL, "0")
	field(DRVH, "15")
	field(EGU,  "dB")
}

record(longout, "HL2:SBPM:HL15:ATT2") {
	field(DESC, "AFE Att. 2")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE2+3,qspiAfe")
	field(EGU,  "dB")
	field(LOPR, "0")
	field(HOPR, "31")
	field(DRVL, "0")
	field(DRVH, "31")
	field(EGU,  "dB")
}

# AFE FW versions (decimal):
# 4     original LCLS-I FW version
# >=32  ATT2 has 32 dB range; before 16 dB
# 33    200 MHz board
# 34    140 MHz board w/ 6dB PAD removed
# 35    200 MHz board w/ 6dB PAD removed
# > 64  140 MHz board not used with PAD/coldfire (XTA)
# 8     MicroTCA RTM
record(longin, "HL2:SBPM:HL15:VERS") {
	field(DESC, "AFE Firmware Vers.")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(INP,  "#C0S0@AFE2+5,qspiAfe")
	field(LOLO, "3")
	field(LLSV, "MAJOR")
	field(PINI, "YES")
	field(FLNK, "HL2:SBPM:HL15:ATTINIT")
}

record(longout, "HL2:SBPM:HL15:AODL") {
	field(DESC, "Delay Trig -> AMP On")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE2+0x10,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
}

record(longout, "HL2:SBPM:HL15:R1DL") {
	field(DESC, "Delay AMP On -> RF1")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE2+0x11,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
}

record(longout, "HL2:SBPM:HL15:RFWD") {
	field(DESC, "RF Pulse Width")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE2+0x13,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
	info(autosaveFields, "VAL")
}

record(longout, "HL2:SBPM:HL15:OFFT") {
	field(DESC, "Delay RF Off -> Ctrl Sw.")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE2+0x14,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
}

record(longout, "HL2:SBPM:HL15:R2DL") {
	field(DESC, "Ctrl Sw. -> RF2")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE2+0x12,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
}

# This record just issues a CAL trigger
record(longout, "HL2:SBPM:HL15:CALT") {
	field(DESC, "AFE CAL Soft Trigger")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE2+6,qspiAfe")
}

record(mbbo,   "HL2:SBPM:HL15:CALM") {
        field(DESC, "AFE Cal. Mode")
        field(DTYP, "BusAddress")
        field(OUT,  "#C0S0@AFE2+0,softTogAfe")
        field(NOBT, "2")
        field(SHFT, "0")
        field(ZRST, "CAL RED")
        field(ZRVL, "0")
        field(ONST, "CAL GRN")
        field(ONVL, "1")
        field(THST, "CAL NONE")
        field(THVL, "3")
# 'soft toggle' mode. NOTE: LSB must match RED or GRN
# which choses the mode to start with
        field(FRST, "CAL TOGGLE")
        field(FRVL, "4")
        field(VAL,  "4")
        field(PINI, "YES")
}

# Subroutine to set up attenuator limits at ioc startup.
# Attenuator ranges vary among AFE types and FW versions
# This record also in bpmVmeDigiAfePart.db
record(aSub, "HL2:SBPM:HL15:ATTINIT") {
        field(DESC, "Set up AFE att limits")
        field(SNAM, "subAttSetup")
        field(FTA,  "LONG")
        field(INPA, "HL2:SBPM:HL15:VERS")
        field(FTVA, "LONG")
        field(OUTA, "HL2:SBPM:HL15:ATT1.HOPR")
        field(FTVB, "LONG")
        field(OUTB, "HL2:SBPM:HL15:ATT1.DRVH")
        field(FTVC, "LONG")
        field(OUTC, "HL2:SBPM:HL15:ATT2.HOPR")
        field(FTVD, "LONG")
        field(OUTD, "HL2:SBPM:HL15:ATT2.DRVH")
        field(FTVE, "LONG")
        field(OUTE, "HL2:SBPM:HL15:ATT.HOPR")
        field(FTVF, "LONG")
        field(OUTF, "HL2:SBPM:HL15:ATT.DRVH")
        field(FTVG, "LONG")
        field(OUTG, "HL2:SBPM:HL15:ATT.VAL")
        field(FTVH, "LONG")
        field(OUTH, "HL2:SBPM:HL15:ATTC.D")
        field(FTVI, "LONG")
        field(OUTI, "HL2:SBPM:HL15:ATTC.E")
        field(FTVJ, "LONG")
        field(OUTJ, "HL2:SBPM:HL15:ATTC.F")
        field(FTVK, "LONG")
        field(OUTK, "HL2:SBPM:HL15:ATTO.DRVL")
        field(FTVL, "LONG")
        field(OUTL, "HL2:SBPM:HL15:ATTO.LOPR")
        field(FTVM, "LONG")
        field(OUTM, "HL2:SBPM:HL15:ATTO.DRVH")
        field(FTVN, "LONG")
        field(OUTN, "HL2:SBPM:HL15:ATTO.HOPR")
        field(FTVO, "LONG")
        field(OUTO, "HL2:SBPM:HL15:CLAO.DRVL")
        field(FTVP, "LONG")
        field(OUTP, "HL2:SBPM:HL15:CLAO.LOPR")
        field(FTVQ, "LONG")
        field(OUTQ, "HL2:SBPM:HL15:CLAO.DRVH")
        field(FTVR, "LONG")
        field(OUTR, "HL2:SBPM:HL15:CLAO.HOPR")
        field(FLNK, "HL2:SBPM:HL15:ATT")
}

# Total attenuation (but ATTO is still added to this)
record(longout, "HL2:SBPM:HL15:ATT") {
	field(DESC, "AFE Total Attenuation")
	field(OUT,  "HL2:SBPM:HL15:ATTC.A PP")
	field(DRVL, "0")
	field(DRVH, "30")
	field(LOPR, "0")
	field(HOPR, "30")
	field(EGU,  "dB")
	field(DOL,  "VIOC:GUN:BPM:ATTR CPP")
	field(OMSL, "supervisory")
	field(VAL,  "30")
}

# This subroutine record performs the
# following operation (ATTC.D defines
# the breakpoint where ATT1 kicks in 
# -- it depends on losses and gains:
#    BPT = G1 + L1 - L2
# with
#  G1: gain of 1st stage,
#  L1: loss + NF upstream of 1st stage,
#  L2: loss between 1st and 2nd stage + NF of 2nd stage
#
# if L1 : 2dB cable, 3dB 1st Filter, 1dB Att1 residual, 2.8dB NF =  8.8dB
#    L2 : 1dB Att2 residual, 4.5dB BPF, 3dB NF                   =  8.5dB
#    G1 :                                                        = 20.0dB
#
# -> breakpoint ~ 20dB
#
#-----------------------------------------------------------------------------
# New RTM AFE characteristics are different (assume 140 ft LMR: 2.2db/100ft):
#    L1 : 3.1 dB cable, 4.5 dB 1st BPF, 1.1 dB att1, 3.3dB NF    = 12.0dB
#    L2 : 1.1 dB att2, 2.7 dB NF, 1 dB BPF                       =  4.8dB
#    G1 :                                                        = 16.0dB
#
# -> breakpoint ~ 23dB
#
#-----------------------------------------------------------------------------
#
# Semantics of the different fields
#  A: Total attenuation (ATT records deposits value there)
#  B: ATTO
#  C: CLAO
#  D: BPT Breakpoint (see above)
#  E: (ATT1MAX) max. ATT1 attenuation (depends on version, set by ATTINIT)
#  F: (ATT2MAX) max. ATT2 attenuation (depends on version, set by ATTINIT)
#
# if ( (T=ATT+ATTO) > ATT1MAX + ATT2MAX )
#    T = ATT1MAX + ATT2MAX
# endif
#
# if ( (A1 = floor((T - BPT)/2)) < 0 )
#    A1 = 0;
#    A2 = T;
# else
#    if (A1 > ATT1MAX) 
#      A1 = ATT1MAX;
#    endif
#    A2 = T - A1
# endif
#
# if ( A2 > ATT2MAX )
#    A1 = A2-ATT2MAX
#    A2 = ATT2MAX
# endif
#
#    CA = CLAO + ATT1MAX + ATT2MAX - ATT
# if ( CA < 0 )
#    CA = 0
# else if ( CA > ACMAX )
#    CA = ACMAX
# endif
#
# Then, it writes three links:
#  HL2:SBPM:HL15:ATT1 = A1
#  HL2:SBPM:HL15:ATT2 = A2
#  HL2:SBPM:HL15:CALA = CA
#

record(sub, "HL2:SBPM:HL15:ATTC") {
	# Note: this record uses it's name to calculate
	# db link addresses to ATT1, ATT2, CALA
	field(DESC, "AFE Total Att. Calc.")
	# initialize fields to max. attenuation:
	# During init:
	#    1. hw initializes to max
	#    2. this record holds max
	#    3. PINI of the placeholder PVs (ATT, ATTO & friends)
	#       trickle in and cause the total attenuation to
	#       go down...
	field(A,    "30")
	field(B,    "0")
	field(C,    "60")
	field(D,    "20")
	field(EGU,  "dB")
	field(INAM, "subAttIni")
	field(SNAM, "subAtt")
}

#propagate 'ACCESS.RVAL' state to 
#attenuator control
#This record is unused in stdalone mode 'b'
record(bo, "HL2:SBPM:HL15:ACTL") {
	field(DESC, "ATT OMSL Ctrl")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL2:SBPM:HL15:ACCESS.RVAL CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL2:SBPM:HL15:ATT.OMSL PP")
}

###
### Keep 'ATTO' and 'CLAO' on the main/VME IOC.
### It is more confusing but then we don't have
### to restore anything across reboots on the PAD
### IOC...
###
### This db now used for AFEs controlled by either
### a VME IOC or a PAD IOC. Use the same db for 
### both for simplicity.
###
### NOTE: We could use the INPB / INPC
###       links of ATTC directly but we DONT.
###       Potentially, ATTC can be processed
###       on every shot -- we don't want the
###       links to be fetched every time for
###       efficiency reasons. Hence the 'propagator'
###       records which monitor ATTO/CLAO and
###       write to ATTC.B ATTC.C only when
###       necessary...
record(longout, "HL2:SBPM:HL15:ATTOL") {
	field(DESC, "ATTO Propagator")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL2:SBPM:HL15:ATTO CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL2:SBPM:HL15:ATTC.B PP")
	field(EGU,  "dB")
}

record(longout, "HL2:SBPM:HL15:CLAOL") {
	field(DESC, "CLAO Propagator")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL2:SBPM:HL15:CLAO CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL2:SBPM:HL15:ATTC.C PP")
	field(EGU,  "dB")
}
# Records only needed for RTM AFE

record(longout, "HL2:SBPM:HL15:TRIG2BEAM") {
	field(DESC, "Trigger -> ADC trig")
	field(DTYP, "BusAddress")
	field(OUT,  "#C0S0@AFE2+0x15,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVH, "255")
	field(PINI, "YES")
	info(autosaveFields, "VAL")
}

record(longout, "HL2:SBPM:HL15:RF2RED") {
	field(DESC, "Red RF -> ADC trig")
	field(DTYP, "BusAddress")
	field(OUT,  "#C0S0@AFE2+0x16,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVH, "255")
	field(VAL,  "6")
	field(PINI, "YES")
	info(autosaveFields, "VAL")
}

record(longout, "HL2:SBPM:HL15:RF2GRN") {
	field(DESC, "Grn RF -> ADC trig")
	field(DTYP, "BusAddress")
	field(OUT,  "#C0S0@AFE2+0x17,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVH, "255")
	field(VAL,  "6")
	field(PINI, "YES")
	info(autosaveFields, "VAL")
}
# bpmAfe.db; database for controlling stripline-BPM AFE
# This database should not be loaded on PADs w/o AFE hardware.
#
# THIS FILE WAS GENERATED WITH msi FROM bpmPadAfe.template or bpmVmeDigiAfe.db AND EXPANDED FOR
#
# !!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!
#  MODE: a -- Use VME IOC PVs
# !!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!
#
# NOTE: The template can be configured by means of proper macro
#       substitutions to 
#        a) operate in 'normal' LCLS stripline BPM mode. In this
#           mode a few CA links to the VME/main IOC are active fetching
#           '$(dev):ACCESS', '$(dev):ATTO' and '$(dev):CLAO' from the
#           main IOC.
#
#        b) standalone mode. In this mode, ACCESS is ignored and 'ATTO' and
#           'CLAO' are instantiated / hosted on the PAD IOC.
#
#        Mode 'a' is chosen by substituting
#        	  'suffix' ='L',
#        	'propomsl' = 'closed_loop'
#        	 'attomsl' = 'supervisory'
#        	   'chrgL' = '<charge PV> CPP'
#        	   'actlL' = '$(dev):ACCESS.RVAL CP'
#        	   'attoL' = '$(dev):ATTO CP'
#        	   'claoL' = '$(dev):CLAO CP'
#
#        Mode 'b' is chosen by substituting
#             'suffix' = '' (empty)
#        	'propomsl' = 'supervisory'
#        	 'attomsl' = 'supervisory'
#        	   'chrgL' = '0'
#        	   'actlL' = '0'
#        	   'attoL' = '0'
#        	   'claoL' = '0'
#
# SUBSTITUTIONS:
#  Substitutions available in main .db file
#    'dev' : device name prefix
#   'chrg' : name of global attenuator PV (for scaling all AFE attenuators with beam charge)(mode a) or '0' (mode b)
#            'chrg' is only available in mode 'a'.
#
#  Substitutions available in the template -- intended to be expanded when generating '.db' with MSI.
#
#  'chrgL' : name of global attenuator PV (for scaling all AFE attenuators with beam charge) + CPP attribute (mode a) or '0' (mode b)
#  'actlL' : name of ACCESS.RVAL PV + CP attribute (mode a) or '0' (mode b)
#  'attoL' : name of ATTO PV + CP attribute (mode a) or '0' (mode b)
#  'claoL' : name of CLAO PV + CP attribute (mode a) or '0' (mode b)
#'attomsl' : default/initial OMSL; if 'supervisory' then the 'ATT' PV controls attenuators
#            if 'closed_loop' then ATT is fetched from it's DOL (=='chrg' PV).
# 'suffix' : see above.
#'propomsl': see above.
#
# LINKS (pointing outside of this file): These links are only used in mode a and set to '0' in mode b.
#     HL2:SBPM:HL16:ATT.DOL  <---- VIOC:GUN:BPM:ATTR CPP    // DEFINED IN: [depends on 'chrg' macro substitution].
#     HL2:SBPM:HL16:ACTL.DOL <---- HL2:SBPM:HL16:ACCESS.RVAL CP // DEFINED IN: associated main IOC database 'IOC-<loc>-BP<unit>bpm.db'
#     HL2:SBPM:HL16:ATTOL.DOL<---- HL2:SBPM:HL16:ATTO CP // DEFINED IN: associated main IOC database 'IOC-<loc>-BP<unit>bpm.db'
#     HL2:SBPM:HL16:CLAOL.DOL<---- HL2:SBPM:HL16:CLAO CP // DEFINED IN: associated main IOC database 'IOC-<loc>-BP<unit>bpm.db'
#
#
#
#  Additional macros added to support other architectures. These macros do NOT need to be populated for PAD AFEs
#  because the default value is set for them:
#
# 	instance - AFE identifier (0,1,... or identifying string)
#	devsup   - device support name (qspiAfe for 'generic' suppport used by SLAC RTM and XTA AFE)
#       type     - AFE flavor, 0 for PAD, 1 for XTA, 2 for RTM

#

record(longout, "HL2:SBPM:HL16:CALA") {
	field(DESC, "AFE Cal. Att.")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE3+1,qspiAfe")
	field(LOPR, "0")
	field(HOPR, "31")
	field(DRVL, "6")
	field(DRVH, "31")
	field(EGU,  "dB")
}

record(longout, "HL2:SBPM:HL16:ATT1") {
	field(DESC, "AFE Att. 1")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE3+2,qspiAfe")
	field(LOPR, "0")
	field(HOPR, "15")
	field(DRVL, "0")
	field(DRVH, "15")
	field(EGU,  "dB")
}

record(longout, "HL2:SBPM:HL16:ATT2") {
	field(DESC, "AFE Att. 2")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE3+3,qspiAfe")
	field(EGU,  "dB")
	field(LOPR, "0")
	field(HOPR, "31")
	field(DRVL, "0")
	field(DRVH, "31")
	field(EGU,  "dB")
}

# AFE FW versions (decimal):
# 4     original LCLS-I FW version
# >=32  ATT2 has 32 dB range; before 16 dB
# 33    200 MHz board
# 34    140 MHz board w/ 6dB PAD removed
# 35    200 MHz board w/ 6dB PAD removed
# > 64  140 MHz board not used with PAD/coldfire (XTA)
# 8     MicroTCA RTM
record(longin, "HL2:SBPM:HL16:VERS") {
	field(DESC, "AFE Firmware Vers.")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(INP,  "#C0S0@AFE3+5,qspiAfe")
	field(LOLO, "3")
	field(LLSV, "MAJOR")
	field(PINI, "YES")
	field(FLNK, "HL2:SBPM:HL16:ATTINIT")
}

record(longout, "HL2:SBPM:HL16:AODL") {
	field(DESC, "Delay Trig -> AMP On")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE3+0x10,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
}

record(longout, "HL2:SBPM:HL16:R1DL") {
	field(DESC, "Delay AMP On -> RF1")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE3+0x11,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
}

record(longout, "HL2:SBPM:HL16:RFWD") {
	field(DESC, "RF Pulse Width")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE3+0x13,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
	info(autosaveFields, "VAL")
}

record(longout, "HL2:SBPM:HL16:OFFT") {
	field(DESC, "Delay RF Off -> Ctrl Sw.")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE3+0x14,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
}

record(longout, "HL2:SBPM:HL16:R2DL") {
	field(DESC, "Ctrl Sw. -> RF2")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE3+0x12,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
}

# This record just issues a CAL trigger
record(longout, "HL2:SBPM:HL16:CALT") {
	field(DESC, "AFE CAL Soft Trigger")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE3+6,qspiAfe")
}

record(mbbo,   "HL2:SBPM:HL16:CALM") {
        field(DESC, "AFE Cal. Mode")
        field(DTYP, "BusAddress")
        field(OUT,  "#C0S0@AFE3+0,softTogAfe")
        field(NOBT, "2")
        field(SHFT, "0")
        field(ZRST, "CAL RED")
        field(ZRVL, "0")
        field(ONST, "CAL GRN")
        field(ONVL, "1")
        field(THST, "CAL NONE")
        field(THVL, "3")
# 'soft toggle' mode. NOTE: LSB must match RED or GRN
# which choses the mode to start with
        field(FRST, "CAL TOGGLE")
        field(FRVL, "4")
        field(VAL,  "4")
        field(PINI, "YES")
}

# Subroutine to set up attenuator limits at ioc startup.
# Attenuator ranges vary among AFE types and FW versions
# This record also in bpmVmeDigiAfePart.db
record(aSub, "HL2:SBPM:HL16:ATTINIT") {
        field(DESC, "Set up AFE att limits")
        field(SNAM, "subAttSetup")
        field(FTA,  "LONG")
        field(INPA, "HL2:SBPM:HL16:VERS")
        field(FTVA, "LONG")
        field(OUTA, "HL2:SBPM:HL16:ATT1.HOPR")
        field(FTVB, "LONG")
        field(OUTB, "HL2:SBPM:HL16:ATT1.DRVH")
        field(FTVC, "LONG")
        field(OUTC, "HL2:SBPM:HL16:ATT2.HOPR")
        field(FTVD, "LONG")
        field(OUTD, "HL2:SBPM:HL16:ATT2.DRVH")
        field(FTVE, "LONG")
        field(OUTE, "HL2:SBPM:HL16:ATT.HOPR")
        field(FTVF, "LONG")
        field(OUTF, "HL2:SBPM:HL16:ATT.DRVH")
        field(FTVG, "LONG")
        field(OUTG, "HL2:SBPM:HL16:ATT.VAL")
        field(FTVH, "LONG")
        field(OUTH, "HL2:SBPM:HL16:ATTC.D")
        field(FTVI, "LONG")
        field(OUTI, "HL2:SBPM:HL16:ATTC.E")
        field(FTVJ, "LONG")
        field(OUTJ, "HL2:SBPM:HL16:ATTC.F")
        field(FTVK, "LONG")
        field(OUTK, "HL2:SBPM:HL16:ATTO.DRVL")
        field(FTVL, "LONG")
        field(OUTL, "HL2:SBPM:HL16:ATTO.LOPR")
        field(FTVM, "LONG")
        field(OUTM, "HL2:SBPM:HL16:ATTO.DRVH")
        field(FTVN, "LONG")
        field(OUTN, "HL2:SBPM:HL16:ATTO.HOPR")
        field(FTVO, "LONG")
        field(OUTO, "HL2:SBPM:HL16:CLAO.DRVL")
        field(FTVP, "LONG")
        field(OUTP, "HL2:SBPM:HL16:CLAO.LOPR")
        field(FTVQ, "LONG")
        field(OUTQ, "HL2:SBPM:HL16:CLAO.DRVH")
        field(FTVR, "LONG")
        field(OUTR, "HL2:SBPM:HL16:CLAO.HOPR")
        field(FLNK, "HL2:SBPM:HL16:ATT")
}

# Total attenuation (but ATTO is still added to this)
record(longout, "HL2:SBPM:HL16:ATT") {
	field(DESC, "AFE Total Attenuation")
	field(OUT,  "HL2:SBPM:HL16:ATTC.A PP")
	field(DRVL, "0")
	field(DRVH, "30")
	field(LOPR, "0")
	field(HOPR, "30")
	field(EGU,  "dB")
	field(DOL,  "VIOC:GUN:BPM:ATTR CPP")
	field(OMSL, "supervisory")
	field(VAL,  "30")
}

# This subroutine record performs the
# following operation (ATTC.D defines
# the breakpoint where ATT1 kicks in 
# -- it depends on losses and gains:
#    BPT = G1 + L1 - L2
# with
#  G1: gain of 1st stage,
#  L1: loss + NF upstream of 1st stage,
#  L2: loss between 1st and 2nd stage + NF of 2nd stage
#
# if L1 : 2dB cable, 3dB 1st Filter, 1dB Att1 residual, 2.8dB NF =  8.8dB
#    L2 : 1dB Att2 residual, 4.5dB BPF, 3dB NF                   =  8.5dB
#    G1 :                                                        = 20.0dB
#
# -> breakpoint ~ 20dB
#
#-----------------------------------------------------------------------------
# New RTM AFE characteristics are different (assume 140 ft LMR: 2.2db/100ft):
#    L1 : 3.1 dB cable, 4.5 dB 1st BPF, 1.1 dB att1, 3.3dB NF    = 12.0dB
#    L2 : 1.1 dB att2, 2.7 dB NF, 1 dB BPF                       =  4.8dB
#    G1 :                                                        = 16.0dB
#
# -> breakpoint ~ 23dB
#
#-----------------------------------------------------------------------------
#
# Semantics of the different fields
#  A: Total attenuation (ATT records deposits value there)
#  B: ATTO
#  C: CLAO
#  D: BPT Breakpoint (see above)
#  E: (ATT1MAX) max. ATT1 attenuation (depends on version, set by ATTINIT)
#  F: (ATT2MAX) max. ATT2 attenuation (depends on version, set by ATTINIT)
#
# if ( (T=ATT+ATTO) > ATT1MAX + ATT2MAX )
#    T = ATT1MAX + ATT2MAX
# endif
#
# if ( (A1 = floor((T - BPT)/2)) < 0 )
#    A1 = 0;
#    A2 = T;
# else
#    if (A1 > ATT1MAX) 
#      A1 = ATT1MAX;
#    endif
#    A2 = T - A1
# endif
#
# if ( A2 > ATT2MAX )
#    A1 = A2-ATT2MAX
#    A2 = ATT2MAX
# endif
#
#    CA = CLAO + ATT1MAX + ATT2MAX - ATT
# if ( CA < 0 )
#    CA = 0
# else if ( CA > ACMAX )
#    CA = ACMAX
# endif
#
# Then, it writes three links:
#  HL2:SBPM:HL16:ATT1 = A1
#  HL2:SBPM:HL16:ATT2 = A2
#  HL2:SBPM:HL16:CALA = CA
#

record(sub, "HL2:SBPM:HL16:ATTC") {
	# Note: this record uses it's name to calculate
	# db link addresses to ATT1, ATT2, CALA
	field(DESC, "AFE Total Att. Calc.")
	# initialize fields to max. attenuation:
	# During init:
	#    1. hw initializes to max
	#    2. this record holds max
	#    3. PINI of the placeholder PVs (ATT, ATTO & friends)
	#       trickle in and cause the total attenuation to
	#       go down...
	field(A,    "30")
	field(B,    "0")
	field(C,    "60")
	field(D,    "20")
	field(EGU,  "dB")
	field(INAM, "subAttIni")
	field(SNAM, "subAtt")
}

#propagate 'ACCESS.RVAL' state to 
#attenuator control
#This record is unused in stdalone mode 'b'
record(bo, "HL2:SBPM:HL16:ACTL") {
	field(DESC, "ATT OMSL Ctrl")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL2:SBPM:HL16:ACCESS.RVAL CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL2:SBPM:HL16:ATT.OMSL PP")
}

###
### Keep 'ATTO' and 'CLAO' on the main/VME IOC.
### It is more confusing but then we don't have
### to restore anything across reboots on the PAD
### IOC...
###
### This db now used for AFEs controlled by either
### a VME IOC or a PAD IOC. Use the same db for 
### both for simplicity.
###
### NOTE: We could use the INPB / INPC
###       links of ATTC directly but we DONT.
###       Potentially, ATTC can be processed
###       on every shot -- we don't want the
###       links to be fetched every time for
###       efficiency reasons. Hence the 'propagator'
###       records which monitor ATTO/CLAO and
###       write to ATTC.B ATTC.C only when
###       necessary...
record(longout, "HL2:SBPM:HL16:ATTOL") {
	field(DESC, "ATTO Propagator")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL2:SBPM:HL16:ATTO CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL2:SBPM:HL16:ATTC.B PP")
	field(EGU,  "dB")
}

record(longout, "HL2:SBPM:HL16:CLAOL") {
	field(DESC, "CLAO Propagator")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL2:SBPM:HL16:CLAO CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL2:SBPM:HL16:ATTC.C PP")
	field(EGU,  "dB")
}
# Records only needed for RTM AFE

record(longout, "HL2:SBPM:HL16:TRIG2BEAM") {
	field(DESC, "Trigger -> ADC trig")
	field(DTYP, "BusAddress")
	field(OUT,  "#C0S0@AFE3+0x15,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVH, "255")
	field(PINI, "YES")
	info(autosaveFields, "VAL")
}

record(longout, "HL2:SBPM:HL16:RF2RED") {
	field(DESC, "Red RF -> ADC trig")
	field(DTYP, "BusAddress")
	field(OUT,  "#C0S0@AFE3+0x16,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVH, "255")
	field(VAL,  "6")
	field(PINI, "YES")
	info(autosaveFields, "VAL")
}

record(longout, "HL2:SBPM:HL16:RF2GRN") {
	field(DESC, "Grn RF -> ADC trig")
	field(DTYP, "BusAddress")
	field(OUT,  "#C0S0@AFE3+0x17,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVH, "255")
	field(VAL,  "6")
	field(PINI, "YES")
	info(autosaveFields, "VAL")
}
# bpmAfe.db; database for controlling stripline-BPM AFE
# This database should not be loaded on PADs w/o AFE hardware.
#
# THIS FILE WAS GENERATED WITH msi FROM bpmPadAfe.template or bpmVmeDigiAfe.db AND EXPANDED FOR
#
# !!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!
#  MODE: a -- Use VME IOC PVs
# !!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!
#
# NOTE: The template can be configured by means of proper macro
#       substitutions to 
#        a) operate in 'normal' LCLS stripline BPM mode. In this
#           mode a few CA links to the VME/main IOC are active fetching
#           '$(dev):ACCESS', '$(dev):ATTO' and '$(dev):CLAO' from the
#           main IOC.
#
#        b) standalone mode. In this mode, ACCESS is ignored and 'ATTO' and
#           'CLAO' are instantiated / hosted on the PAD IOC.
#
#        Mode 'a' is chosen by substituting
#        	  'suffix' ='L',
#        	'propomsl' = 'closed_loop'
#        	 'attomsl' = 'supervisory'
#        	   'chrgL' = '<charge PV> CPP'
#        	   'actlL' = '$(dev):ACCESS.RVAL CP'
#        	   'attoL' = '$(dev):ATTO CP'
#        	   'claoL' = '$(dev):CLAO CP'
#
#        Mode 'b' is chosen by substituting
#             'suffix' = '' (empty)
#        	'propomsl' = 'supervisory'
#        	 'attomsl' = 'supervisory'
#        	   'chrgL' = '0'
#        	   'actlL' = '0'
#        	   'attoL' = '0'
#        	   'claoL' = '0'
#
# SUBSTITUTIONS:
#  Substitutions available in main .db file
#    'dev' : device name prefix
#   'chrg' : name of global attenuator PV (for scaling all AFE attenuators with beam charge)(mode a) or '0' (mode b)
#            'chrg' is only available in mode 'a'.
#
#  Substitutions available in the template -- intended to be expanded when generating '.db' with MSI.
#
#  'chrgL' : name of global attenuator PV (for scaling all AFE attenuators with beam charge) + CPP attribute (mode a) or '0' (mode b)
#  'actlL' : name of ACCESS.RVAL PV + CP attribute (mode a) or '0' (mode b)
#  'attoL' : name of ATTO PV + CP attribute (mode a) or '0' (mode b)
#  'claoL' : name of CLAO PV + CP attribute (mode a) or '0' (mode b)
#'attomsl' : default/initial OMSL; if 'supervisory' then the 'ATT' PV controls attenuators
#            if 'closed_loop' then ATT is fetched from it's DOL (=='chrg' PV).
# 'suffix' : see above.
#'propomsl': see above.
#
# LINKS (pointing outside of this file): These links are only used in mode a and set to '0' in mode b.
#     HL2:SBPM:HL17:ATT.DOL  <---- VIOC:GUN:BPM:ATTR CPP    // DEFINED IN: [depends on 'chrg' macro substitution].
#     HL2:SBPM:HL17:ACTL.DOL <---- HL2:SBPM:HL17:ACCESS.RVAL CP // DEFINED IN: associated main IOC database 'IOC-<loc>-BP<unit>bpm.db'
#     HL2:SBPM:HL17:ATTOL.DOL<---- HL2:SBPM:HL17:ATTO CP // DEFINED IN: associated main IOC database 'IOC-<loc>-BP<unit>bpm.db'
#     HL2:SBPM:HL17:CLAOL.DOL<---- HL2:SBPM:HL17:CLAO CP // DEFINED IN: associated main IOC database 'IOC-<loc>-BP<unit>bpm.db'
#
#
#
#  Additional macros added to support other architectures. These macros do NOT need to be populated for PAD AFEs
#  because the default value is set for them:
#
# 	instance - AFE identifier (0,1,... or identifying string)
#	devsup   - device support name (qspiAfe for 'generic' suppport used by SLAC RTM and XTA AFE)
#       type     - AFE flavor, 0 for PAD, 1 for XTA, 2 for RTM

#

record(longout, "HL2:SBPM:HL17:CALA") {
	field(DESC, "AFE Cal. Att.")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE4+1,qspiAfe")
	field(LOPR, "0")
	field(HOPR, "31")
	field(DRVL, "6")
	field(DRVH, "31")
	field(EGU,  "dB")
}

record(longout, "HL2:SBPM:HL17:ATT1") {
	field(DESC, "AFE Att. 1")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE4+2,qspiAfe")
	field(LOPR, "0")
	field(HOPR, "15")
	field(DRVL, "0")
	field(DRVH, "15")
	field(EGU,  "dB")
}

record(longout, "HL2:SBPM:HL17:ATT2") {
	field(DESC, "AFE Att. 2")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE4+3,qspiAfe")
	field(EGU,  "dB")
	field(LOPR, "0")
	field(HOPR, "31")
	field(DRVL, "0")
	field(DRVH, "31")
	field(EGU,  "dB")
}

# AFE FW versions (decimal):
# 4     original LCLS-I FW version
# >=32  ATT2 has 32 dB range; before 16 dB
# 33    200 MHz board
# 34    140 MHz board w/ 6dB PAD removed
# 35    200 MHz board w/ 6dB PAD removed
# > 64  140 MHz board not used with PAD/coldfire (XTA)
# 8     MicroTCA RTM
record(longin, "HL2:SBPM:HL17:VERS") {
	field(DESC, "AFE Firmware Vers.")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(INP,  "#C0S0@AFE4+5,qspiAfe")
	field(LOLO, "3")
	field(LLSV, "MAJOR")
	field(PINI, "YES")
	field(FLNK, "HL2:SBPM:HL17:ATTINIT")
}

record(longout, "HL2:SBPM:HL17:AODL") {
	field(DESC, "Delay Trig -> AMP On")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE4+0x10,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
}

record(longout, "HL2:SBPM:HL17:R1DL") {
	field(DESC, "Delay AMP On -> RF1")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE4+0x11,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
}

record(longout, "HL2:SBPM:HL17:RFWD") {
	field(DESC, "RF Pulse Width")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE4+0x13,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
	info(autosaveFields, "VAL")
}

record(longout, "HL2:SBPM:HL17:OFFT") {
	field(DESC, "Delay RF Off -> Ctrl Sw.")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE4+0x14,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
}

record(longout, "HL2:SBPM:HL17:R2DL") {
	field(DESC, "Ctrl Sw. -> RF2")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE4+0x12,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
}

# This record just issues a CAL trigger
record(longout, "HL2:SBPM:HL17:CALT") {
	field(DESC, "AFE CAL Soft Trigger")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE4+6,qspiAfe")
}

record(mbbo,   "HL2:SBPM:HL17:CALM") {
        field(DESC, "AFE Cal. Mode")
        field(DTYP, "BusAddress")
        field(OUT,  "#C0S0@AFE4+0,softTogAfe")
        field(NOBT, "2")
        field(SHFT, "0")
        field(ZRST, "CAL RED")
        field(ZRVL, "0")
        field(ONST, "CAL GRN")
        field(ONVL, "1")
        field(THST, "CAL NONE")
        field(THVL, "3")
# 'soft toggle' mode. NOTE: LSB must match RED or GRN
# which choses the mode to start with
        field(FRST, "CAL TOGGLE")
        field(FRVL, "4")
        field(VAL,  "4")
        field(PINI, "YES")
}

# Subroutine to set up attenuator limits at ioc startup.
# Attenuator ranges vary among AFE types and FW versions
# This record also in bpmVmeDigiAfePart.db
record(aSub, "HL2:SBPM:HL17:ATTINIT") {
        field(DESC, "Set up AFE att limits")
        field(SNAM, "subAttSetup")
        field(FTA,  "LONG")
        field(INPA, "HL2:SBPM:HL17:VERS")
        field(FTVA, "LONG")
        field(OUTA, "HL2:SBPM:HL17:ATT1.HOPR")
        field(FTVB, "LONG")
        field(OUTB, "HL2:SBPM:HL17:ATT1.DRVH")
        field(FTVC, "LONG")
        field(OUTC, "HL2:SBPM:HL17:ATT2.HOPR")
        field(FTVD, "LONG")
        field(OUTD, "HL2:SBPM:HL17:ATT2.DRVH")
        field(FTVE, "LONG")
        field(OUTE, "HL2:SBPM:HL17:ATT.HOPR")
        field(FTVF, "LONG")
        field(OUTF, "HL2:SBPM:HL17:ATT.DRVH")
        field(FTVG, "LONG")
        field(OUTG, "HL2:SBPM:HL17:ATT.VAL")
        field(FTVH, "LONG")
        field(OUTH, "HL2:SBPM:HL17:ATTC.D")
        field(FTVI, "LONG")
        field(OUTI, "HL2:SBPM:HL17:ATTC.E")
        field(FTVJ, "LONG")
        field(OUTJ, "HL2:SBPM:HL17:ATTC.F")
        field(FTVK, "LONG")
        field(OUTK, "HL2:SBPM:HL17:ATTO.DRVL")
        field(FTVL, "LONG")
        field(OUTL, "HL2:SBPM:HL17:ATTO.LOPR")
        field(FTVM, "LONG")
        field(OUTM, "HL2:SBPM:HL17:ATTO.DRVH")
        field(FTVN, "LONG")
        field(OUTN, "HL2:SBPM:HL17:ATTO.HOPR")
        field(FTVO, "LONG")
        field(OUTO, "HL2:SBPM:HL17:CLAO.DRVL")
        field(FTVP, "LONG")
        field(OUTP, "HL2:SBPM:HL17:CLAO.LOPR")
        field(FTVQ, "LONG")
        field(OUTQ, "HL2:SBPM:HL17:CLAO.DRVH")
        field(FTVR, "LONG")
        field(OUTR, "HL2:SBPM:HL17:CLAO.HOPR")
        field(FLNK, "HL2:SBPM:HL17:ATT")
}

# Total attenuation (but ATTO is still added to this)
record(longout, "HL2:SBPM:HL17:ATT") {
	field(DESC, "AFE Total Attenuation")
	field(OUT,  "HL2:SBPM:HL17:ATTC.A PP")
	field(DRVL, "0")
	field(DRVH, "30")
	field(LOPR, "0")
	field(HOPR, "30")
	field(EGU,  "dB")
	field(DOL,  "VIOC:GUN:BPM:ATTR CPP")
	field(OMSL, "supervisory")
	field(VAL,  "30")
}

# This subroutine record performs the
# following operation (ATTC.D defines
# the breakpoint where ATT1 kicks in 
# -- it depends on losses and gains:
#    BPT = G1 + L1 - L2
# with
#  G1: gain of 1st stage,
#  L1: loss + NF upstream of 1st stage,
#  L2: loss between 1st and 2nd stage + NF of 2nd stage
#
# if L1 : 2dB cable, 3dB 1st Filter, 1dB Att1 residual, 2.8dB NF =  8.8dB
#    L2 : 1dB Att2 residual, 4.5dB BPF, 3dB NF                   =  8.5dB
#    G1 :                                                        = 20.0dB
#
# -> breakpoint ~ 20dB
#
#-----------------------------------------------------------------------------
# New RTM AFE characteristics are different (assume 140 ft LMR: 2.2db/100ft):
#    L1 : 3.1 dB cable, 4.5 dB 1st BPF, 1.1 dB att1, 3.3dB NF    = 12.0dB
#    L2 : 1.1 dB att2, 2.7 dB NF, 1 dB BPF                       =  4.8dB
#    G1 :                                                        = 16.0dB
#
# -> breakpoint ~ 23dB
#
#-----------------------------------------------------------------------------
#
# Semantics of the different fields
#  A: Total attenuation (ATT records deposits value there)
#  B: ATTO
#  C: CLAO
#  D: BPT Breakpoint (see above)
#  E: (ATT1MAX) max. ATT1 attenuation (depends on version, set by ATTINIT)
#  F: (ATT2MAX) max. ATT2 attenuation (depends on version, set by ATTINIT)
#
# if ( (T=ATT+ATTO) > ATT1MAX + ATT2MAX )
#    T = ATT1MAX + ATT2MAX
# endif
#
# if ( (A1 = floor((T - BPT)/2)) < 0 )
#    A1 = 0;
#    A2 = T;
# else
#    if (A1 > ATT1MAX) 
#      A1 = ATT1MAX;
#    endif
#    A2 = T - A1
# endif
#
# if ( A2 > ATT2MAX )
#    A1 = A2-ATT2MAX
#    A2 = ATT2MAX
# endif
#
#    CA = CLAO + ATT1MAX + ATT2MAX - ATT
# if ( CA < 0 )
#    CA = 0
# else if ( CA > ACMAX )
#    CA = ACMAX
# endif
#
# Then, it writes three links:
#  HL2:SBPM:HL17:ATT1 = A1
#  HL2:SBPM:HL17:ATT2 = A2
#  HL2:SBPM:HL17:CALA = CA
#

record(sub, "HL2:SBPM:HL17:ATTC") {
	# Note: this record uses it's name to calculate
	# db link addresses to ATT1, ATT2, CALA
	field(DESC, "AFE Total Att. Calc.")
	# initialize fields to max. attenuation:
	# During init:
	#    1. hw initializes to max
	#    2. this record holds max
	#    3. PINI of the placeholder PVs (ATT, ATTO & friends)
	#       trickle in and cause the total attenuation to
	#       go down...
	field(A,    "30")
	field(B,    "0")
	field(C,    "60")
	field(D,    "20")
	field(EGU,  "dB")
	field(INAM, "subAttIni")
	field(SNAM, "subAtt")
}

#propagate 'ACCESS.RVAL' state to 
#attenuator control
#This record is unused in stdalone mode 'b'
record(bo, "HL2:SBPM:HL17:ACTL") {
	field(DESC, "ATT OMSL Ctrl")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL2:SBPM:HL17:ACCESS.RVAL CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL2:SBPM:HL17:ATT.OMSL PP")
}

###
### Keep 'ATTO' and 'CLAO' on the main/VME IOC.
### It is more confusing but then we don't have
### to restore anything across reboots on the PAD
### IOC...
###
### This db now used for AFEs controlled by either
### a VME IOC or a PAD IOC. Use the same db for 
### both for simplicity.
###
### NOTE: We could use the INPB / INPC
###       links of ATTC directly but we DONT.
###       Potentially, ATTC can be processed
###       on every shot -- we don't want the
###       links to be fetched every time for
###       efficiency reasons. Hence the 'propagator'
###       records which monitor ATTO/CLAO and
###       write to ATTC.B ATTC.C only when
###       necessary...
record(longout, "HL2:SBPM:HL17:ATTOL") {
	field(DESC, "ATTO Propagator")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL2:SBPM:HL17:ATTO CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL2:SBPM:HL17:ATTC.B PP")
	field(EGU,  "dB")
}

record(longout, "HL2:SBPM:HL17:CLAOL") {
	field(DESC, "CLAO Propagator")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL2:SBPM:HL17:CLAO CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL2:SBPM:HL17:ATTC.C PP")
	field(EGU,  "dB")
}
# Records only needed for RTM AFE

record(longout, "HL2:SBPM:HL17:TRIG2BEAM") {
	field(DESC, "Trigger -> ADC trig")
	field(DTYP, "BusAddress")
	field(OUT,  "#C0S0@AFE4+0x15,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVH, "255")
	field(PINI, "YES")
	info(autosaveFields, "VAL")
}

record(longout, "HL2:SBPM:HL17:RF2RED") {
	field(DESC, "Red RF -> ADC trig")
	field(DTYP, "BusAddress")
	field(OUT,  "#C0S0@AFE4+0x16,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVH, "255")
	field(VAL,  "6")
	field(PINI, "YES")
	info(autosaveFields, "VAL")
}

record(longout, "HL2:SBPM:HL17:RF2GRN") {
	field(DESC, "Grn RF -> ADC trig")
	field(DTYP, "BusAddress")
	field(OUT,  "#C0S0@AFE4+0x17,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVH, "255")
	field(VAL,  "6")
	field(PINI, "YES")
	info(autosaveFields, "VAL")
}
# bpmAfe.db; database for controlling stripline-BPM AFE
# This database should not be loaded on PADs w/o AFE hardware.
#
# THIS FILE WAS GENERATED WITH msi FROM bpmPadAfe.template or bpmVmeDigiAfe.db AND EXPANDED FOR
#
# !!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!
#  MODE: a -- Use VME IOC PVs
# !!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!
#
# NOTE: The template can be configured by means of proper macro
#       substitutions to 
#        a) operate in 'normal' LCLS stripline BPM mode. In this
#           mode a few CA links to the VME/main IOC are active fetching
#           '$(dev):ACCESS', '$(dev):ATTO' and '$(dev):CLAO' from the
#           main IOC.
#
#        b) standalone mode. In this mode, ACCESS is ignored and 'ATTO' and
#           'CLAO' are instantiated / hosted on the PAD IOC.
#
#        Mode 'a' is chosen by substituting
#        	  'suffix' ='L',
#        	'propomsl' = 'closed_loop'
#        	 'attomsl' = 'supervisory'
#        	   'chrgL' = '<charge PV> CPP'
#        	   'actlL' = '$(dev):ACCESS.RVAL CP'
#        	   'attoL' = '$(dev):ATTO CP'
#        	   'claoL' = '$(dev):CLAO CP'
#
#        Mode 'b' is chosen by substituting
#             'suffix' = '' (empty)
#        	'propomsl' = 'supervisory'
#        	 'attomsl' = 'supervisory'
#        	   'chrgL' = '0'
#        	   'actlL' = '0'
#        	   'attoL' = '0'
#        	   'claoL' = '0'
#
# SUBSTITUTIONS:
#  Substitutions available in main .db file
#    'dev' : device name prefix
#   'chrg' : name of global attenuator PV (for scaling all AFE attenuators with beam charge)(mode a) or '0' (mode b)
#            'chrg' is only available in mode 'a'.
#
#  Substitutions available in the template -- intended to be expanded when generating '.db' with MSI.
#
#  'chrgL' : name of global attenuator PV (for scaling all AFE attenuators with beam charge) + CPP attribute (mode a) or '0' (mode b)
#  'actlL' : name of ACCESS.RVAL PV + CP attribute (mode a) or '0' (mode b)
#  'attoL' : name of ATTO PV + CP attribute (mode a) or '0' (mode b)
#  'claoL' : name of CLAO PV + CP attribute (mode a) or '0' (mode b)
#'attomsl' : default/initial OMSL; if 'supervisory' then the 'ATT' PV controls attenuators
#            if 'closed_loop' then ATT is fetched from it's DOL (=='chrg' PV).
# 'suffix' : see above.
#'propomsl': see above.
#
# LINKS (pointing outside of this file): These links are only used in mode a and set to '0' in mode b.
#     HL2:SBPM:HL18:ATT.DOL  <---- VIOC:GUN:BPM:ATTR CPP    // DEFINED IN: [depends on 'chrg' macro substitution].
#     HL2:SBPM:HL18:ACTL.DOL <---- HL2:SBPM:HL18:ACCESS.RVAL CP // DEFINED IN: associated main IOC database 'IOC-<loc>-BP<unit>bpm.db'
#     HL2:SBPM:HL18:ATTOL.DOL<---- HL2:SBPM:HL18:ATTO CP // DEFINED IN: associated main IOC database 'IOC-<loc>-BP<unit>bpm.db'
#     HL2:SBPM:HL18:CLAOL.DOL<---- HL2:SBPM:HL18:CLAO CP // DEFINED IN: associated main IOC database 'IOC-<loc>-BP<unit>bpm.db'
#
#
#
#  Additional macros added to support other architectures. These macros do NOT need to be populated for PAD AFEs
#  because the default value is set for them:
#
# 	instance - AFE identifier (0,1,... or identifying string)
#	devsup   - device support name (qspiAfe for 'generic' suppport used by SLAC RTM and XTA AFE)
#       type     - AFE flavor, 0 for PAD, 1 for XTA, 2 for RTM

#

record(longout, "HL2:SBPM:HL18:CALA") {
	field(DESC, "AFE Cal. Att.")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE5+1,qspiAfe")
	field(LOPR, "0")
	field(HOPR, "31")
	field(DRVL, "6")
	field(DRVH, "31")
	field(EGU,  "dB")
}

record(longout, "HL2:SBPM:HL18:ATT1") {
	field(DESC, "AFE Att. 1")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE5+2,qspiAfe")
	field(LOPR, "0")
	field(HOPR, "15")
	field(DRVL, "0")
	field(DRVH, "15")
	field(EGU,  "dB")
}

record(longout, "HL2:SBPM:HL18:ATT2") {
	field(DESC, "AFE Att. 2")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE5+3,qspiAfe")
	field(EGU,  "dB")
	field(LOPR, "0")
	field(HOPR, "31")
	field(DRVL, "0")
	field(DRVH, "31")
	field(EGU,  "dB")
}

# AFE FW versions (decimal):
# 4     original LCLS-I FW version
# >=32  ATT2 has 32 dB range; before 16 dB
# 33    200 MHz board
# 34    140 MHz board w/ 6dB PAD removed
# 35    200 MHz board w/ 6dB PAD removed
# > 64  140 MHz board not used with PAD/coldfire (XTA)
# 8     MicroTCA RTM
record(longin, "HL2:SBPM:HL18:VERS") {
	field(DESC, "AFE Firmware Vers.")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(INP,  "#C0S0@AFE5+5,qspiAfe")
	field(LOLO, "3")
	field(LLSV, "MAJOR")
	field(PINI, "YES")
	field(FLNK, "HL2:SBPM:HL18:ATTINIT")
}

record(longout, "HL2:SBPM:HL18:AODL") {
	field(DESC, "Delay Trig -> AMP On")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE5+0x10,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
}

record(longout, "HL2:SBPM:HL18:R1DL") {
	field(DESC, "Delay AMP On -> RF1")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE5+0x11,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
}

record(longout, "HL2:SBPM:HL18:RFWD") {
	field(DESC, "RF Pulse Width")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE5+0x13,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
	info(autosaveFields, "VAL")
}

record(longout, "HL2:SBPM:HL18:OFFT") {
	field(DESC, "Delay RF Off -> Ctrl Sw.")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE5+0x14,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
}

record(longout, "HL2:SBPM:HL18:R2DL") {
	field(DESC, "Ctrl Sw. -> RF2")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE5+0x12,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
}

# This record just issues a CAL trigger
record(longout, "HL2:SBPM:HL18:CALT") {
	field(DESC, "AFE CAL Soft Trigger")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE5+6,qspiAfe")
}

record(mbbo,   "HL2:SBPM:HL18:CALM") {
        field(DESC, "AFE Cal. Mode")
        field(DTYP, "BusAddress")
        field(OUT,  "#C0S0@AFE5+0,softTogAfe")
        field(NOBT, "2")
        field(SHFT, "0")
        field(ZRST, "CAL RED")
        field(ZRVL, "0")
        field(ONST, "CAL GRN")
        field(ONVL, "1")
        field(THST, "CAL NONE")
        field(THVL, "3")
# 'soft toggle' mode. NOTE: LSB must match RED or GRN
# which choses the mode to start with
        field(FRST, "CAL TOGGLE")
        field(FRVL, "4")
        field(VAL,  "4")
        field(PINI, "YES")
}

# Subroutine to set up attenuator limits at ioc startup.
# Attenuator ranges vary among AFE types and FW versions
# This record also in bpmVmeDigiAfePart.db
record(aSub, "HL2:SBPM:HL18:ATTINIT") {
        field(DESC, "Set up AFE att limits")
        field(SNAM, "subAttSetup")
        field(FTA,  "LONG")
        field(INPA, "HL2:SBPM:HL18:VERS")
        field(FTVA, "LONG")
        field(OUTA, "HL2:SBPM:HL18:ATT1.HOPR")
        field(FTVB, "LONG")
        field(OUTB, "HL2:SBPM:HL18:ATT1.DRVH")
        field(FTVC, "LONG")
        field(OUTC, "HL2:SBPM:HL18:ATT2.HOPR")
        field(FTVD, "LONG")
        field(OUTD, "HL2:SBPM:HL18:ATT2.DRVH")
        field(FTVE, "LONG")
        field(OUTE, "HL2:SBPM:HL18:ATT.HOPR")
        field(FTVF, "LONG")
        field(OUTF, "HL2:SBPM:HL18:ATT.DRVH")
        field(FTVG, "LONG")
        field(OUTG, "HL2:SBPM:HL18:ATT.VAL")
        field(FTVH, "LONG")
        field(OUTH, "HL2:SBPM:HL18:ATTC.D")
        field(FTVI, "LONG")
        field(OUTI, "HL2:SBPM:HL18:ATTC.E")
        field(FTVJ, "LONG")
        field(OUTJ, "HL2:SBPM:HL18:ATTC.F")
        field(FTVK, "LONG")
        field(OUTK, "HL2:SBPM:HL18:ATTO.DRVL")
        field(FTVL, "LONG")
        field(OUTL, "HL2:SBPM:HL18:ATTO.LOPR")
        field(FTVM, "LONG")
        field(OUTM, "HL2:SBPM:HL18:ATTO.DRVH")
        field(FTVN, "LONG")
        field(OUTN, "HL2:SBPM:HL18:ATTO.HOPR")
        field(FTVO, "LONG")
        field(OUTO, "HL2:SBPM:HL18:CLAO.DRVL")
        field(FTVP, "LONG")
        field(OUTP, "HL2:SBPM:HL18:CLAO.LOPR")
        field(FTVQ, "LONG")
        field(OUTQ, "HL2:SBPM:HL18:CLAO.DRVH")
        field(FTVR, "LONG")
        field(OUTR, "HL2:SBPM:HL18:CLAO.HOPR")
        field(FLNK, "HL2:SBPM:HL18:ATT")
}

# Total attenuation (but ATTO is still added to this)
record(longout, "HL2:SBPM:HL18:ATT") {
	field(DESC, "AFE Total Attenuation")
	field(OUT,  "HL2:SBPM:HL18:ATTC.A PP")
	field(DRVL, "0")
	field(DRVH, "30")
	field(LOPR, "0")
	field(HOPR, "30")
	field(EGU,  "dB")
	field(DOL,  "VIOC:GUN:BPM:ATTR CPP")
	field(OMSL, "supervisory")
	field(VAL,  "30")
}

# This subroutine record performs the
# following operation (ATTC.D defines
# the breakpoint where ATT1 kicks in 
# -- it depends on losses and gains:
#    BPT = G1 + L1 - L2
# with
#  G1: gain of 1st stage,
#  L1: loss + NF upstream of 1st stage,
#  L2: loss between 1st and 2nd stage + NF of 2nd stage
#
# if L1 : 2dB cable, 3dB 1st Filter, 1dB Att1 residual, 2.8dB NF =  8.8dB
#    L2 : 1dB Att2 residual, 4.5dB BPF, 3dB NF                   =  8.5dB
#    G1 :                                                        = 20.0dB
#
# -> breakpoint ~ 20dB
#
#-----------------------------------------------------------------------------
# New RTM AFE characteristics are different (assume 140 ft LMR: 2.2db/100ft):
#    L1 : 3.1 dB cable, 4.5 dB 1st BPF, 1.1 dB att1, 3.3dB NF    = 12.0dB
#    L2 : 1.1 dB att2, 2.7 dB NF, 1 dB BPF                       =  4.8dB
#    G1 :                                                        = 16.0dB
#
# -> breakpoint ~ 23dB
#
#-----------------------------------------------------------------------------
#
# Semantics of the different fields
#  A: Total attenuation (ATT records deposits value there)
#  B: ATTO
#  C: CLAO
#  D: BPT Breakpoint (see above)
#  E: (ATT1MAX) max. ATT1 attenuation (depends on version, set by ATTINIT)
#  F: (ATT2MAX) max. ATT2 attenuation (depends on version, set by ATTINIT)
#
# if ( (T=ATT+ATTO) > ATT1MAX + ATT2MAX )
#    T = ATT1MAX + ATT2MAX
# endif
#
# if ( (A1 = floor((T - BPT)/2)) < 0 )
#    A1 = 0;
#    A2 = T;
# else
#    if (A1 > ATT1MAX) 
#      A1 = ATT1MAX;
#    endif
#    A2 = T - A1
# endif
#
# if ( A2 > ATT2MAX )
#    A1 = A2-ATT2MAX
#    A2 = ATT2MAX
# endif
#
#    CA = CLAO + ATT1MAX + ATT2MAX - ATT
# if ( CA < 0 )
#    CA = 0
# else if ( CA > ACMAX )
#    CA = ACMAX
# endif
#
# Then, it writes three links:
#  HL2:SBPM:HL18:ATT1 = A1
#  HL2:SBPM:HL18:ATT2 = A2
#  HL2:SBPM:HL18:CALA = CA
#

record(sub, "HL2:SBPM:HL18:ATTC") {
	# Note: this record uses it's name to calculate
	# db link addresses to ATT1, ATT2, CALA
	field(DESC, "AFE Total Att. Calc.")
	# initialize fields to max. attenuation:
	# During init:
	#    1. hw initializes to max
	#    2. this record holds max
	#    3. PINI of the placeholder PVs (ATT, ATTO & friends)
	#       trickle in and cause the total attenuation to
	#       go down...
	field(A,    "30")
	field(B,    "0")
	field(C,    "60")
	field(D,    "20")
	field(EGU,  "dB")
	field(INAM, "subAttIni")
	field(SNAM, "subAtt")
}

#propagate 'ACCESS.RVAL' state to 
#attenuator control
#This record is unused in stdalone mode 'b'
record(bo, "HL2:SBPM:HL18:ACTL") {
	field(DESC, "ATT OMSL Ctrl")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL2:SBPM:HL18:ACCESS.RVAL CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL2:SBPM:HL18:ATT.OMSL PP")
}

###
### Keep 'ATTO' and 'CLAO' on the main/VME IOC.
### It is more confusing but then we don't have
### to restore anything across reboots on the PAD
### IOC...
###
### This db now used for AFEs controlled by either
### a VME IOC or a PAD IOC. Use the same db for 
### both for simplicity.
###
### NOTE: We could use the INPB / INPC
###       links of ATTC directly but we DONT.
###       Potentially, ATTC can be processed
###       on every shot -- we don't want the
###       links to be fetched every time for
###       efficiency reasons. Hence the 'propagator'
###       records which monitor ATTO/CLAO and
###       write to ATTC.B ATTC.C only when
###       necessary...
record(longout, "HL2:SBPM:HL18:ATTOL") {
	field(DESC, "ATTO Propagator")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL2:SBPM:HL18:ATTO CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL2:SBPM:HL18:ATTC.B PP")
	field(EGU,  "dB")
}

record(longout, "HL2:SBPM:HL18:CLAOL") {
	field(DESC, "CLAO Propagator")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL2:SBPM:HL18:CLAO CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL2:SBPM:HL18:ATTC.C PP")
	field(EGU,  "dB")
}
# Records only needed for RTM AFE

record(longout, "HL2:SBPM:HL18:TRIG2BEAM") {
	field(DESC, "Trigger -> ADC trig")
	field(DTYP, "BusAddress")
	field(OUT,  "#C0S0@AFE5+0x15,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVH, "255")
	field(PINI, "YES")
	info(autosaveFields, "VAL")
}

record(longout, "HL2:SBPM:HL18:RF2RED") {
	field(DESC, "Red RF -> ADC trig")
	field(DTYP, "BusAddress")
	field(OUT,  "#C0S0@AFE5+0x16,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVH, "255")
	field(VAL,  "6")
	field(PINI, "YES")
	info(autosaveFields, "VAL")
}

record(longout, "HL2:SBPM:HL18:RF2GRN") {
	field(DESC, "Grn RF -> ADC trig")
	field(DTYP, "BusAddress")
	field(OUT,  "#C0S0@AFE5+0x17,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVH, "255")
	field(VAL,  "6")
	field(PINI, "YES")
	info(autosaveFields, "VAL")
}
# bpmAfe.db; database for controlling stripline-BPM AFE
# This database should not be loaded on PADs w/o AFE hardware.
#
# THIS FILE WAS GENERATED WITH msi FROM bpmPadAfe.template or bpmVmeDigiAfe.db AND EXPANDED FOR
#
# !!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!
#  MODE: a -- Use VME IOC PVs
# !!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!
#
# NOTE: The template can be configured by means of proper macro
#       substitutions to 
#        a) operate in 'normal' LCLS stripline BPM mode. In this
#           mode a few CA links to the VME/main IOC are active fetching
#           '$(dev):ACCESS', '$(dev):ATTO' and '$(dev):CLAO' from the
#           main IOC.
#
#        b) standalone mode. In this mode, ACCESS is ignored and 'ATTO' and
#           'CLAO' are instantiated / hosted on the PAD IOC.
#
#        Mode 'a' is chosen by substituting
#        	  'suffix' ='L',
#        	'propomsl' = 'closed_loop'
#        	 'attomsl' = 'supervisory'
#        	   'chrgL' = '<charge PV> CPP'
#        	   'actlL' = '$(dev):ACCESS.RVAL CP'
#        	   'attoL' = '$(dev):ATTO CP'
#        	   'claoL' = '$(dev):CLAO CP'
#
#        Mode 'b' is chosen by substituting
#             'suffix' = '' (empty)
#        	'propomsl' = 'supervisory'
#        	 'attomsl' = 'supervisory'
#        	   'chrgL' = '0'
#        	   'actlL' = '0'
#        	   'attoL' = '0'
#        	   'claoL' = '0'
#
# SUBSTITUTIONS:
#  Substitutions available in main .db file
#    'dev' : device name prefix
#   'chrg' : name of global attenuator PV (for scaling all AFE attenuators with beam charge)(mode a) or '0' (mode b)
#            'chrg' is only available in mode 'a'.
#
#  Substitutions available in the template -- intended to be expanded when generating '.db' with MSI.
#
#  'chrgL' : name of global attenuator PV (for scaling all AFE attenuators with beam charge) + CPP attribute (mode a) or '0' (mode b)
#  'actlL' : name of ACCESS.RVAL PV + CP attribute (mode a) or '0' (mode b)
#  'attoL' : name of ATTO PV + CP attribute (mode a) or '0' (mode b)
#  'claoL' : name of CLAO PV + CP attribute (mode a) or '0' (mode b)
#'attomsl' : default/initial OMSL; if 'supervisory' then the 'ATT' PV controls attenuators
#            if 'closed_loop' then ATT is fetched from it's DOL (=='chrg' PV).
# 'suffix' : see above.
#'propomsl': see above.
#
# LINKS (pointing outside of this file): These links are only used in mode a and set to '0' in mode b.
#     HL2:SBPM:HL19:ATT.DOL  <---- VIOC:GUN:BPM:ATTR CPP    // DEFINED IN: [depends on 'chrg' macro substitution].
#     HL2:SBPM:HL19:ACTL.DOL <---- HL2:SBPM:HL19:ACCESS.RVAL CP // DEFINED IN: associated main IOC database 'IOC-<loc>-BP<unit>bpm.db'
#     HL2:SBPM:HL19:ATTOL.DOL<---- HL2:SBPM:HL19:ATTO CP // DEFINED IN: associated main IOC database 'IOC-<loc>-BP<unit>bpm.db'
#     HL2:SBPM:HL19:CLAOL.DOL<---- HL2:SBPM:HL19:CLAO CP // DEFINED IN: associated main IOC database 'IOC-<loc>-BP<unit>bpm.db'
#
#
#
#  Additional macros added to support other architectures. These macros do NOT need to be populated for PAD AFEs
#  because the default value is set for them:
#
# 	instance - AFE identifier (0,1,... or identifying string)
#	devsup   - device support name (qspiAfe for 'generic' suppport used by SLAC RTM and XTA AFE)
#       type     - AFE flavor, 0 for PAD, 1 for XTA, 2 for RTM

#

record(longout, "HL2:SBPM:HL19:CALA") {
	field(DESC, "AFE Cal. Att.")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE6+1,qspiAfe")
	field(LOPR, "0")
	field(HOPR, "31")
	field(DRVL, "6")
	field(DRVH, "31")
	field(EGU,  "dB")
}

record(longout, "HL2:SBPM:HL19:ATT1") {
	field(DESC, "AFE Att. 1")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE6+2,qspiAfe")
	field(LOPR, "0")
	field(HOPR, "15")
	field(DRVL, "0")
	field(DRVH, "15")
	field(EGU,  "dB")
}

record(longout, "HL2:SBPM:HL19:ATT2") {
	field(DESC, "AFE Att. 2")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE6+3,qspiAfe")
	field(EGU,  "dB")
	field(LOPR, "0")
	field(HOPR, "31")
	field(DRVL, "0")
	field(DRVH, "31")
	field(EGU,  "dB")
}

# AFE FW versions (decimal):
# 4     original LCLS-I FW version
# >=32  ATT2 has 32 dB range; before 16 dB
# 33    200 MHz board
# 34    140 MHz board w/ 6dB PAD removed
# 35    200 MHz board w/ 6dB PAD removed
# > 64  140 MHz board not used with PAD/coldfire (XTA)
# 8     MicroTCA RTM
record(longin, "HL2:SBPM:HL19:VERS") {
	field(DESC, "AFE Firmware Vers.")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(INP,  "#C0S0@AFE6+5,qspiAfe")
	field(LOLO, "3")
	field(LLSV, "MAJOR")
	field(PINI, "YES")
	field(FLNK, "HL2:SBPM:HL19:ATTINIT")
}

record(longout, "HL2:SBPM:HL19:AODL") {
	field(DESC, "Delay Trig -> AMP On")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE6+0x10,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
}

record(longout, "HL2:SBPM:HL19:R1DL") {
	field(DESC, "Delay AMP On -> RF1")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE6+0x11,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
}

record(longout, "HL2:SBPM:HL19:RFWD") {
	field(DESC, "RF Pulse Width")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE6+0x13,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
	info(autosaveFields, "VAL")
}

record(longout, "HL2:SBPM:HL19:OFFT") {
	field(DESC, "Delay RF Off -> Ctrl Sw.")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE6+0x14,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
}

record(longout, "HL2:SBPM:HL19:R2DL") {
	field(DESC, "Ctrl Sw. -> RF2")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE6+0x12,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
}

# This record just issues a CAL trigger
record(longout, "HL2:SBPM:HL19:CALT") {
	field(DESC, "AFE CAL Soft Trigger")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE6+6,qspiAfe")
}

record(mbbo,   "HL2:SBPM:HL19:CALM") {
        field(DESC, "AFE Cal. Mode")
        field(DTYP, "BusAddress")
        field(OUT,  "#C0S0@AFE6+0,softTogAfe")
        field(NOBT, "2")
        field(SHFT, "0")
        field(ZRST, "CAL RED")
        field(ZRVL, "0")
        field(ONST, "CAL GRN")
        field(ONVL, "1")
        field(THST, "CAL NONE")
        field(THVL, "3")
# 'soft toggle' mode. NOTE: LSB must match RED or GRN
# which choses the mode to start with
        field(FRST, "CAL TOGGLE")
        field(FRVL, "4")
        field(VAL,  "4")
        field(PINI, "YES")
}

# Subroutine to set up attenuator limits at ioc startup.
# Attenuator ranges vary among AFE types and FW versions
# This record also in bpmVmeDigiAfePart.db
record(aSub, "HL2:SBPM:HL19:ATTINIT") {
        field(DESC, "Set up AFE att limits")
        field(SNAM, "subAttSetup")
        field(FTA,  "LONG")
        field(INPA, "HL2:SBPM:HL19:VERS")
        field(FTVA, "LONG")
        field(OUTA, "HL2:SBPM:HL19:ATT1.HOPR")
        field(FTVB, "LONG")
        field(OUTB, "HL2:SBPM:HL19:ATT1.DRVH")
        field(FTVC, "LONG")
        field(OUTC, "HL2:SBPM:HL19:ATT2.HOPR")
        field(FTVD, "LONG")
        field(OUTD, "HL2:SBPM:HL19:ATT2.DRVH")
        field(FTVE, "LONG")
        field(OUTE, "HL2:SBPM:HL19:ATT.HOPR")
        field(FTVF, "LONG")
        field(OUTF, "HL2:SBPM:HL19:ATT.DRVH")
        field(FTVG, "LONG")
        field(OUTG, "HL2:SBPM:HL19:ATT.VAL")
        field(FTVH, "LONG")
        field(OUTH, "HL2:SBPM:HL19:ATTC.D")
        field(FTVI, "LONG")
        field(OUTI, "HL2:SBPM:HL19:ATTC.E")
        field(FTVJ, "LONG")
        field(OUTJ, "HL2:SBPM:HL19:ATTC.F")
        field(FTVK, "LONG")
        field(OUTK, "HL2:SBPM:HL19:ATTO.DRVL")
        field(FTVL, "LONG")
        field(OUTL, "HL2:SBPM:HL19:ATTO.LOPR")
        field(FTVM, "LONG")
        field(OUTM, "HL2:SBPM:HL19:ATTO.DRVH")
        field(FTVN, "LONG")
        field(OUTN, "HL2:SBPM:HL19:ATTO.HOPR")
        field(FTVO, "LONG")
        field(OUTO, "HL2:SBPM:HL19:CLAO.DRVL")
        field(FTVP, "LONG")
        field(OUTP, "HL2:SBPM:HL19:CLAO.LOPR")
        field(FTVQ, "LONG")
        field(OUTQ, "HL2:SBPM:HL19:CLAO.DRVH")
        field(FTVR, "LONG")
        field(OUTR, "HL2:SBPM:HL19:CLAO.HOPR")
        field(FLNK, "HL2:SBPM:HL19:ATT")
}

# Total attenuation (but ATTO is still added to this)
record(longout, "HL2:SBPM:HL19:ATT") {
	field(DESC, "AFE Total Attenuation")
	field(OUT,  "HL2:SBPM:HL19:ATTC.A PP")
	field(DRVL, "0")
	field(DRVH, "30")
	field(LOPR, "0")
	field(HOPR, "30")
	field(EGU,  "dB")
	field(DOL,  "VIOC:GUN:BPM:ATTR CPP")
	field(OMSL, "supervisory")
	field(VAL,  "30")
}

# This subroutine record performs the
# following operation (ATTC.D defines
# the breakpoint where ATT1 kicks in 
# -- it depends on losses and gains:
#    BPT = G1 + L1 - L2
# with
#  G1: gain of 1st stage,
#  L1: loss + NF upstream of 1st stage,
#  L2: loss between 1st and 2nd stage + NF of 2nd stage
#
# if L1 : 2dB cable, 3dB 1st Filter, 1dB Att1 residual, 2.8dB NF =  8.8dB
#    L2 : 1dB Att2 residual, 4.5dB BPF, 3dB NF                   =  8.5dB
#    G1 :                                                        = 20.0dB
#
# -> breakpoint ~ 20dB
#
#-----------------------------------------------------------------------------
# New RTM AFE characteristics are different (assume 140 ft LMR: 2.2db/100ft):
#    L1 : 3.1 dB cable, 4.5 dB 1st BPF, 1.1 dB att1, 3.3dB NF    = 12.0dB
#    L2 : 1.1 dB att2, 2.7 dB NF, 1 dB BPF                       =  4.8dB
#    G1 :                                                        = 16.0dB
#
# -> breakpoint ~ 23dB
#
#-----------------------------------------------------------------------------
#
# Semantics of the different fields
#  A: Total attenuation (ATT records deposits value there)
#  B: ATTO
#  C: CLAO
#  D: BPT Breakpoint (see above)
#  E: (ATT1MAX) max. ATT1 attenuation (depends on version, set by ATTINIT)
#  F: (ATT2MAX) max. ATT2 attenuation (depends on version, set by ATTINIT)
#
# if ( (T=ATT+ATTO) > ATT1MAX + ATT2MAX )
#    T = ATT1MAX + ATT2MAX
# endif
#
# if ( (A1 = floor((T - BPT)/2)) < 0 )
#    A1 = 0;
#    A2 = T;
# else
#    if (A1 > ATT1MAX) 
#      A1 = ATT1MAX;
#    endif
#    A2 = T - A1
# endif
#
# if ( A2 > ATT2MAX )
#    A1 = A2-ATT2MAX
#    A2 = ATT2MAX
# endif
#
#    CA = CLAO + ATT1MAX + ATT2MAX - ATT
# if ( CA < 0 )
#    CA = 0
# else if ( CA > ACMAX )
#    CA = ACMAX
# endif
#
# Then, it writes three links:
#  HL2:SBPM:HL19:ATT1 = A1
#  HL2:SBPM:HL19:ATT2 = A2
#  HL2:SBPM:HL19:CALA = CA
#

record(sub, "HL2:SBPM:HL19:ATTC") {
	# Note: this record uses it's name to calculate
	# db link addresses to ATT1, ATT2, CALA
	field(DESC, "AFE Total Att. Calc.")
	# initialize fields to max. attenuation:
	# During init:
	#    1. hw initializes to max
	#    2. this record holds max
	#    3. PINI of the placeholder PVs (ATT, ATTO & friends)
	#       trickle in and cause the total attenuation to
	#       go down...
	field(A,    "30")
	field(B,    "0")
	field(C,    "60")
	field(D,    "20")
	field(EGU,  "dB")
	field(INAM, "subAttIni")
	field(SNAM, "subAtt")
}

#propagate 'ACCESS.RVAL' state to 
#attenuator control
#This record is unused in stdalone mode 'b'
record(bo, "HL2:SBPM:HL19:ACTL") {
	field(DESC, "ATT OMSL Ctrl")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL2:SBPM:HL19:ACCESS.RVAL CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL2:SBPM:HL19:ATT.OMSL PP")
}

###
### Keep 'ATTO' and 'CLAO' on the main/VME IOC.
### It is more confusing but then we don't have
### to restore anything across reboots on the PAD
### IOC...
###
### This db now used for AFEs controlled by either
### a VME IOC or a PAD IOC. Use the same db for 
### both for simplicity.
###
### NOTE: We could use the INPB / INPC
###       links of ATTC directly but we DONT.
###       Potentially, ATTC can be processed
###       on every shot -- we don't want the
###       links to be fetched every time for
###       efficiency reasons. Hence the 'propagator'
###       records which monitor ATTO/CLAO and
###       write to ATTC.B ATTC.C only when
###       necessary...
record(longout, "HL2:SBPM:HL19:ATTOL") {
	field(DESC, "ATTO Propagator")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL2:SBPM:HL19:ATTO CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL2:SBPM:HL19:ATTC.B PP")
	field(EGU,  "dB")
}

record(longout, "HL2:SBPM:HL19:CLAOL") {
	field(DESC, "CLAO Propagator")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL2:SBPM:HL19:CLAO CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL2:SBPM:HL19:ATTC.C PP")
	field(EGU,  "dB")
}
# Records only needed for RTM AFE

record(longout, "HL2:SBPM:HL19:TRIG2BEAM") {
	field(DESC, "Trigger -> ADC trig")
	field(DTYP, "BusAddress")
	field(OUT,  "#C0S0@AFE6+0x15,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVH, "255")
	field(PINI, "YES")
	info(autosaveFields, "VAL")
}

record(longout, "HL2:SBPM:HL19:RF2RED") {
	field(DESC, "Red RF -> ADC trig")
	field(DTYP, "BusAddress")
	field(OUT,  "#C0S0@AFE6+0x16,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVH, "255")
	field(VAL,  "6")
	field(PINI, "YES")
	info(autosaveFields, "VAL")
}

record(longout, "HL2:SBPM:HL19:RF2GRN") {
	field(DESC, "Grn RF -> ADC trig")
	field(DTYP, "BusAddress")
	field(OUT,  "#C0S0@AFE6+0x17,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVH, "255")
	field(VAL,  "6")
	field(PINI, "YES")
	info(autosaveFields, "VAL")
}
# bpmAfe.db; database for controlling stripline-BPM AFE
# This database should not be loaded on PADs w/o AFE hardware.
#
# THIS FILE WAS GENERATED WITH msi FROM bpmPadAfe.template or bpmVmeDigiAfe.db AND EXPANDED FOR
#
# !!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!
#  MODE: a -- Use VME IOC PVs
# !!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!
#
# NOTE: The template can be configured by means of proper macro
#       substitutions to 
#        a) operate in 'normal' LCLS stripline BPM mode. In this
#           mode a few CA links to the VME/main IOC are active fetching
#           '$(dev):ACCESS', '$(dev):ATTO' and '$(dev):CLAO' from the
#           main IOC.
#
#        b) standalone mode. In this mode, ACCESS is ignored and 'ATTO' and
#           'CLAO' are instantiated / hosted on the PAD IOC.
#
#        Mode 'a' is chosen by substituting
#        	  'suffix' ='L',
#        	'propomsl' = 'closed_loop'
#        	 'attomsl' = 'supervisory'
#        	   'chrgL' = '<charge PV> CPP'
#        	   'actlL' = '$(dev):ACCESS.RVAL CP'
#        	   'attoL' = '$(dev):ATTO CP'
#        	   'claoL' = '$(dev):CLAO CP'
#
#        Mode 'b' is chosen by substituting
#             'suffix' = '' (empty)
#        	'propomsl' = 'supervisory'
#        	 'attomsl' = 'supervisory'
#        	   'chrgL' = '0'
#        	   'actlL' = '0'
#        	   'attoL' = '0'
#        	   'claoL' = '0'
#
# SUBSTITUTIONS:
#  Substitutions available in main .db file
#    'dev' : device name prefix
#   'chrg' : name of global attenuator PV (for scaling all AFE attenuators with beam charge)(mode a) or '0' (mode b)
#            'chrg' is only available in mode 'a'.
#
#  Substitutions available in the template -- intended to be expanded when generating '.db' with MSI.
#
#  'chrgL' : name of global attenuator PV (for scaling all AFE attenuators with beam charge) + CPP attribute (mode a) or '0' (mode b)
#  'actlL' : name of ACCESS.RVAL PV + CP attribute (mode a) or '0' (mode b)
#  'attoL' : name of ATTO PV + CP attribute (mode a) or '0' (mode b)
#  'claoL' : name of CLAO PV + CP attribute (mode a) or '0' (mode b)
#'attomsl' : default/initial OMSL; if 'supervisory' then the 'ATT' PV controls attenuators
#            if 'closed_loop' then ATT is fetched from it's DOL (=='chrg' PV).
# 'suffix' : see above.
#'propomsl': see above.
#
# LINKS (pointing outside of this file): These links are only used in mode a and set to '0' in mode b.
#     HL2:SBPM:HL20:ATT.DOL  <---- VIOC:GUN:BPM:ATTR CPP    // DEFINED IN: [depends on 'chrg' macro substitution].
#     HL2:SBPM:HL20:ACTL.DOL <---- HL2:SBPM:HL20:ACCESS.RVAL CP // DEFINED IN: associated main IOC database 'IOC-<loc>-BP<unit>bpm.db'
#     HL2:SBPM:HL20:ATTOL.DOL<---- HL2:SBPM:HL20:ATTO CP // DEFINED IN: associated main IOC database 'IOC-<loc>-BP<unit>bpm.db'
#     HL2:SBPM:HL20:CLAOL.DOL<---- HL2:SBPM:HL20:CLAO CP // DEFINED IN: associated main IOC database 'IOC-<loc>-BP<unit>bpm.db'
#
#
#
#  Additional macros added to support other architectures. These macros do NOT need to be populated for PAD AFEs
#  because the default value is set for them:
#
# 	instance - AFE identifier (0,1,... or identifying string)
#	devsup   - device support name (qspiAfe for 'generic' suppport used by SLAC RTM and XTA AFE)
#       type     - AFE flavor, 0 for PAD, 1 for XTA, 2 for RTM

#

record(longout, "HL2:SBPM:HL20:CALA") {
	field(DESC, "AFE Cal. Att.")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE7+1,qspiAfe")
	field(LOPR, "0")
	field(HOPR, "31")
	field(DRVL, "6")
	field(DRVH, "31")
	field(EGU,  "dB")
}

record(longout, "HL2:SBPM:HL20:ATT1") {
	field(DESC, "AFE Att. 1")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE7+2,qspiAfe")
	field(LOPR, "0")
	field(HOPR, "15")
	field(DRVL, "0")
	field(DRVH, "15")
	field(EGU,  "dB")
}

record(longout, "HL2:SBPM:HL20:ATT2") {
	field(DESC, "AFE Att. 2")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE7+3,qspiAfe")
	field(EGU,  "dB")
	field(LOPR, "0")
	field(HOPR, "31")
	field(DRVL, "0")
	field(DRVH, "31")
	field(EGU,  "dB")
}

# AFE FW versions (decimal):
# 4     original LCLS-I FW version
# >=32  ATT2 has 32 dB range; before 16 dB
# 33    200 MHz board
# 34    140 MHz board w/ 6dB PAD removed
# 35    200 MHz board w/ 6dB PAD removed
# > 64  140 MHz board not used with PAD/coldfire (XTA)
# 8     MicroTCA RTM
record(longin, "HL2:SBPM:HL20:VERS") {
	field(DESC, "AFE Firmware Vers.")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(INP,  "#C0S0@AFE7+5,qspiAfe")
	field(LOLO, "3")
	field(LLSV, "MAJOR")
	field(PINI, "YES")
	field(FLNK, "HL2:SBPM:HL20:ATTINIT")
}

record(longout, "HL2:SBPM:HL20:AODL") {
	field(DESC, "Delay Trig -> AMP On")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE7+0x10,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
}

record(longout, "HL2:SBPM:HL20:R1DL") {
	field(DESC, "Delay AMP On -> RF1")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE7+0x11,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
}

record(longout, "HL2:SBPM:HL20:RFWD") {
	field(DESC, "RF Pulse Width")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE7+0x13,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
	info(autosaveFields, "VAL")
}

record(longout, "HL2:SBPM:HL20:OFFT") {
	field(DESC, "Delay RF Off -> Ctrl Sw.")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE7+0x14,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
}

record(longout, "HL2:SBPM:HL20:R2DL") {
	field(DESC, "Ctrl Sw. -> RF2")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE7+0x12,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVL, "255")
}

# This record just issues a CAL trigger
record(longout, "HL2:SBPM:HL20:CALT") {
	field(DESC, "AFE CAL Soft Trigger")
	field(DTYP, "BusAddress")
# address is chip-select << 8 + register
	field(OUT,  "#C0S0@AFE7+6,qspiAfe")
}

record(mbbo,   "HL2:SBPM:HL20:CALM") {
        field(DESC, "AFE Cal. Mode")
        field(DTYP, "BusAddress")
        field(OUT,  "#C0S0@AFE7+0,softTogAfe")
        field(NOBT, "2")
        field(SHFT, "0")
        field(ZRST, "CAL RED")
        field(ZRVL, "0")
        field(ONST, "CAL GRN")
        field(ONVL, "1")
        field(THST, "CAL NONE")
        field(THVL, "3")
# 'soft toggle' mode. NOTE: LSB must match RED or GRN
# which choses the mode to start with
        field(FRST, "CAL TOGGLE")
        field(FRVL, "4")
        field(VAL,  "4")
        field(PINI, "YES")
}

# Subroutine to set up attenuator limits at ioc startup.
# Attenuator ranges vary among AFE types and FW versions
# This record also in bpmVmeDigiAfePart.db
record(aSub, "HL2:SBPM:HL20:ATTINIT") {
        field(DESC, "Set up AFE att limits")
        field(SNAM, "subAttSetup")
        field(FTA,  "LONG")
        field(INPA, "HL2:SBPM:HL20:VERS")
        field(FTVA, "LONG")
        field(OUTA, "HL2:SBPM:HL20:ATT1.HOPR")
        field(FTVB, "LONG")
        field(OUTB, "HL2:SBPM:HL20:ATT1.DRVH")
        field(FTVC, "LONG")
        field(OUTC, "HL2:SBPM:HL20:ATT2.HOPR")
        field(FTVD, "LONG")
        field(OUTD, "HL2:SBPM:HL20:ATT2.DRVH")
        field(FTVE, "LONG")
        field(OUTE, "HL2:SBPM:HL20:ATT.HOPR")
        field(FTVF, "LONG")
        field(OUTF, "HL2:SBPM:HL20:ATT.DRVH")
        field(FTVG, "LONG")
        field(OUTG, "HL2:SBPM:HL20:ATT.VAL")
        field(FTVH, "LONG")
        field(OUTH, "HL2:SBPM:HL20:ATTC.D")
        field(FTVI, "LONG")
        field(OUTI, "HL2:SBPM:HL20:ATTC.E")
        field(FTVJ, "LONG")
        field(OUTJ, "HL2:SBPM:HL20:ATTC.F")
        field(FTVK, "LONG")
        field(OUTK, "HL2:SBPM:HL20:ATTO.DRVL")
        field(FTVL, "LONG")
        field(OUTL, "HL2:SBPM:HL20:ATTO.LOPR")
        field(FTVM, "LONG")
        field(OUTM, "HL2:SBPM:HL20:ATTO.DRVH")
        field(FTVN, "LONG")
        field(OUTN, "HL2:SBPM:HL20:ATTO.HOPR")
        field(FTVO, "LONG")
        field(OUTO, "HL2:SBPM:HL20:CLAO.DRVL")
        field(FTVP, "LONG")
        field(OUTP, "HL2:SBPM:HL20:CLAO.LOPR")
        field(FTVQ, "LONG")
        field(OUTQ, "HL2:SBPM:HL20:CLAO.DRVH")
        field(FTVR, "LONG")
        field(OUTR, "HL2:SBPM:HL20:CLAO.HOPR")
        field(FLNK, "HL2:SBPM:HL20:ATT")
}

# Total attenuation (but ATTO is still added to this)
record(longout, "HL2:SBPM:HL20:ATT") {
	field(DESC, "AFE Total Attenuation")
	field(OUT,  "HL2:SBPM:HL20:ATTC.A PP")
	field(DRVL, "0")
	field(DRVH, "30")
	field(LOPR, "0")
	field(HOPR, "30")
	field(EGU,  "dB")
	field(DOL,  "VIOC:GUN:BPM:ATTR CPP")
	field(OMSL, "supervisory")
	field(VAL,  "30")
}

# This subroutine record performs the
# following operation (ATTC.D defines
# the breakpoint where ATT1 kicks in 
# -- it depends on losses and gains:
#    BPT = G1 + L1 - L2
# with
#  G1: gain of 1st stage,
#  L1: loss + NF upstream of 1st stage,
#  L2: loss between 1st and 2nd stage + NF of 2nd stage
#
# if L1 : 2dB cable, 3dB 1st Filter, 1dB Att1 residual, 2.8dB NF =  8.8dB
#    L2 : 1dB Att2 residual, 4.5dB BPF, 3dB NF                   =  8.5dB
#    G1 :                                                        = 20.0dB
#
# -> breakpoint ~ 20dB
#
#-----------------------------------------------------------------------------
# New RTM AFE characteristics are different (assume 140 ft LMR: 2.2db/100ft):
#    L1 : 3.1 dB cable, 4.5 dB 1st BPF, 1.1 dB att1, 3.3dB NF    = 12.0dB
#    L2 : 1.1 dB att2, 2.7 dB NF, 1 dB BPF                       =  4.8dB
#    G1 :                                                        = 16.0dB
#
# -> breakpoint ~ 23dB
#
#-----------------------------------------------------------------------------
#
# Semantics of the different fields
#  A: Total attenuation (ATT records deposits value there)
#  B: ATTO
#  C: CLAO
#  D: BPT Breakpoint (see above)
#  E: (ATT1MAX) max. ATT1 attenuation (depends on version, set by ATTINIT)
#  F: (ATT2MAX) max. ATT2 attenuation (depends on version, set by ATTINIT)
#
# if ( (T=ATT+ATTO) > ATT1MAX + ATT2MAX )
#    T = ATT1MAX + ATT2MAX
# endif
#
# if ( (A1 = floor((T - BPT)/2)) < 0 )
#    A1 = 0;
#    A2 = T;
# else
#    if (A1 > ATT1MAX) 
#      A1 = ATT1MAX;
#    endif
#    A2 = T - A1
# endif
#
# if ( A2 > ATT2MAX )
#    A1 = A2-ATT2MAX
#    A2 = ATT2MAX
# endif
#
#    CA = CLAO + ATT1MAX + ATT2MAX - ATT
# if ( CA < 0 )
#    CA = 0
# else if ( CA > ACMAX )
#    CA = ACMAX
# endif
#
# Then, it writes three links:
#  HL2:SBPM:HL20:ATT1 = A1
#  HL2:SBPM:HL20:ATT2 = A2
#  HL2:SBPM:HL20:CALA = CA
#

record(sub, "HL2:SBPM:HL20:ATTC") {
	# Note: this record uses it's name to calculate
	# db link addresses to ATT1, ATT2, CALA
	field(DESC, "AFE Total Att. Calc.")
	# initialize fields to max. attenuation:
	# During init:
	#    1. hw initializes to max
	#    2. this record holds max
	#    3. PINI of the placeholder PVs (ATT, ATTO & friends)
	#       trickle in and cause the total attenuation to
	#       go down...
	field(A,    "30")
	field(B,    "0")
	field(C,    "60")
	field(D,    "20")
	field(EGU,  "dB")
	field(INAM, "subAttIni")
	field(SNAM, "subAtt")
}

#propagate 'ACCESS.RVAL' state to 
#attenuator control
#This record is unused in stdalone mode 'b'
record(bo, "HL2:SBPM:HL20:ACTL") {
	field(DESC, "ATT OMSL Ctrl")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL2:SBPM:HL20:ACCESS.RVAL CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL2:SBPM:HL20:ATT.OMSL PP")
}

###
### Keep 'ATTO' and 'CLAO' on the main/VME IOC.
### It is more confusing but then we don't have
### to restore anything across reboots on the PAD
### IOC...
###
### This db now used for AFEs controlled by either
### a VME IOC or a PAD IOC. Use the same db for 
### both for simplicity.
###
### NOTE: We could use the INPB / INPC
###       links of ATTC directly but we DONT.
###       Potentially, ATTC can be processed
###       on every shot -- we don't want the
###       links to be fetched every time for
###       efficiency reasons. Hence the 'propagator'
###       records which monitor ATTO/CLAO and
###       write to ATTC.B ATTC.C only when
###       necessary...
record(longout, "HL2:SBPM:HL20:ATTOL") {
	field(DESC, "ATTO Propagator")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL2:SBPM:HL20:ATTO CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL2:SBPM:HL20:ATTC.B PP")
	field(EGU,  "dB")
}

record(longout, "HL2:SBPM:HL20:CLAOL") {
	field(DESC, "CLAO Propagator")
	field(DTYP, "Soft Channel")
	field(DOL,  "HL2:SBPM:HL20:CLAO CP")
	field(OMSL, "closed_loop")
	field(OUT,  "HL2:SBPM:HL20:ATTC.C PP")
	field(EGU,  "dB")
}
# Records only needed for RTM AFE

record(longout, "HL2:SBPM:HL20:TRIG2BEAM") {
	field(DESC, "Trigger -> ADC trig")
	field(DTYP, "BusAddress")
	field(OUT,  "#C0S0@AFE7+0x15,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVH, "255")
	field(PINI, "YES")
	info(autosaveFields, "VAL")
}

record(longout, "HL2:SBPM:HL20:RF2RED") {
	field(DESC, "Red RF -> ADC trig")
	field(DTYP, "BusAddress")
	field(OUT,  "#C0S0@AFE7+0x16,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVH, "255")
	field(VAL,  "6")
	field(PINI, "YES")
	info(autosaveFields, "VAL")
}

record(longout, "HL2:SBPM:HL20:RF2GRN") {
	field(DESC, "Grn RF -> ADC trig")
	field(DTYP, "BusAddress")
	field(OUT,  "#C0S0@AFE7+0x17,qspiAfe")
	field(EGU,  "33ns")
	field(LOPR, "1")
	field(DRVL, "1")
	field(HOPR, "255")
	field(DRVH, "255")
	field(VAL,  "6")
	field(PINI, "YES")
	info(autosaveFields, "VAL")
}
# Registers on Struck AMC

# Digitizer AMC FW version
record(stringin, "HL1:SBPM:HL13:DIGIVERS") {
	field(DESC, "Digitizer Firmware Vers.")
	field(DTYP, "sis8300Digi")
# address is digitizer base address + register
	field(INP,  "#C0S0@0x4F8(8)")
	field(PINI, "YES")
}

# Firmware date
record(stringin, "HL1:SBPM:HL13:DIGIVERS_DATE") {
	field(DESC, "Firmware Vers. Date")
	field(DTYP, "sis8300Digi")
# address is digitizer base address + register
	field(INP,  "#C0S0@0x4FE(8)")
	field(PINI, "YES")
}

# System ID
record(stringin, "HL1:SBPM:HL13:DIGI_SYSID") {
	field(DESC, "Digitizer System ID")
	field(DTYP, "sis8300Digi")
# address is digitizer base address + register
	field(INP,  "#C0S0@0x4FA(8)")
	field(PINI, "YES")
}

# Sub Type
record(stringin, "HL1:SBPM:HL13:SUBSYS") {
	field(DESC, "Subsystem type")
	field(DTYP, "sis8300Digi")
# address is digitizer base address + register
	field(INP,  "#C0S0@0x4FC(8)")
	field(PINI, "YES")
}
# Registers on Struck AMC

# Digitizer AMC FW version
record(stringin, "HL2:SBPM:HL14:DIGIVERS") {
	field(DESC, "Digitizer Firmware Vers.")
	field(DTYP, "sis8300Digi")
# address is digitizer base address + register
	field(INP,  "#C1S0@0x4F8(8)")
	field(PINI, "YES")
}

# Firmware date
record(stringin, "HL2:SBPM:HL14:DIGIVERS_DATE") {
	field(DESC, "Firmware Vers. Date")
	field(DTYP, "sis8300Digi")
# address is digitizer base address + register
	field(INP,  "#C1S0@0x4FE(8)")
	field(PINI, "YES")
}

# System ID
record(stringin, "HL2:SBPM:HL14:DIGI_SYSID") {
	field(DESC, "Digitizer System ID")
	field(DTYP, "sis8300Digi")
# address is digitizer base address + register
	field(INP,  "#C1S0@0x4FA(8)")
	field(PINI, "YES")
}

# Sub Type
record(stringin, "HL2:SBPM:HL14:SUBSYS") {
	field(DESC, "Subsystem type")
	field(DTYP, "sis8300Digi")
# address is digitizer base address + register
	field(INP,  "#C1S0@0x4FC(8)")
	field(PINI, "YES")
}
# Registers on Struck AMC

# Digitizer AMC FW version
record(stringin, "HL2:SBPM:HL15:DIGIVERS") {
	field(DESC, "Digitizer Firmware Vers.")
	field(DTYP, "sis8300Digi")
# address is digitizer base address + register
	field(INP,  "#C2S0@0x4F8(8)")
	field(PINI, "YES")
}

# Firmware date
record(stringin, "HL2:SBPM:HL15:DIGIVERS_DATE") {
	field(DESC, "Firmware Vers. Date")
	field(DTYP, "sis8300Digi")
# address is digitizer base address + register
	field(INP,  "#C2S0@0x4FE(8)")
	field(PINI, "YES")
}

# System ID
record(stringin, "HL2:SBPM:HL15:DIGI_SYSID") {
	field(DESC, "Digitizer System ID")
	field(DTYP, "sis8300Digi")
# address is digitizer base address + register
	field(INP,  "#C2S0@0x4FA(8)")
	field(PINI, "YES")
}

# Sub Type
record(stringin, "HL2:SBPM:HL15:SUBSYS") {
	field(DESC, "Subsystem type")
	field(DTYP, "sis8300Digi")
# address is digitizer base address + register
	field(INP,  "#C2S0@0x4FC(8)")
	field(PINI, "YES")
}
# Registers on Struck AMC

# Digitizer AMC FW version
record(stringin, "HL2:SBPM:HL16:DIGIVERS") {
	field(DESC, "Digitizer Firmware Vers.")
	field(DTYP, "sis8300Digi")
# address is digitizer base address + register
	field(INP,  "#C3S0@0x4F8(8)")
	field(PINI, "YES")
}

# Firmware date
record(stringin, "HL2:SBPM:HL16:DIGIVERS_DATE") {
	field(DESC, "Firmware Vers. Date")
	field(DTYP, "sis8300Digi")
# address is digitizer base address + register
	field(INP,  "#C3S0@0x4FE(8)")
	field(PINI, "YES")
}

# System ID
record(stringin, "HL2:SBPM:HL16:DIGI_SYSID") {
	field(DESC, "Digitizer System ID")
	field(DTYP, "sis8300Digi")
# address is digitizer base address + register
	field(INP,  "#C3S0@0x4FA(8)")
	field(PINI, "YES")
}

# Sub Type
record(stringin, "HL2:SBPM:HL16:SUBSYS") {
	field(DESC, "Subsystem type")
	field(DTYP, "sis8300Digi")
# address is digitizer base address + register
	field(INP,  "#C3S0@0x4FC(8)")
	field(PINI, "YES")
}
# Registers on Struck AMC

# Digitizer AMC FW version
record(stringin, "HL2:SBPM:HL17:DIGIVERS") {
	field(DESC, "Digitizer Firmware Vers.")
	field(DTYP, "sis8300Digi")
# address is digitizer base address + register
	field(INP,  "#C4S0@0x4F8(8)")
	field(PINI, "YES")
}

# Firmware date
record(stringin, "HL2:SBPM:HL17:DIGIVERS_DATE") {
	field(DESC, "Firmware Vers. Date")
	field(DTYP, "sis8300Digi")
# address is digitizer base address + register
	field(INP,  "#C4S0@0x4FE(8)")
	field(PINI, "YES")
}

# System ID
record(stringin, "HL2:SBPM:HL17:DIGI_SYSID") {
	field(DESC, "Digitizer System ID")
	field(DTYP, "sis8300Digi")
# address is digitizer base address + register
	field(INP,  "#C4S0@0x4FA(8)")
	field(PINI, "YES")
}

# Sub Type
record(stringin, "HL2:SBPM:HL17:SUBSYS") {
	field(DESC, "Subsystem type")
	field(DTYP, "sis8300Digi")
# address is digitizer base address + register
	field(INP,  "#C4S0@0x4FC(8)")
	field(PINI, "YES")
}
# Registers on Struck AMC

# Digitizer AMC FW version
record(stringin, "HL2:SBPM:HL18:DIGIVERS") {
	field(DESC, "Digitizer Firmware Vers.")
	field(DTYP, "sis8300Digi")
# address is digitizer base address + register
	field(INP,  "#C5S0@0x4F8(8)")
	field(PINI, "YES")
}

# Firmware date
record(stringin, "HL2:SBPM:HL18:DIGIVERS_DATE") {
	field(DESC, "Firmware Vers. Date")
	field(DTYP, "sis8300Digi")
# address is digitizer base address + register
	field(INP,  "#C5S0@0x4FE(8)")
	field(PINI, "YES")
}

# System ID
record(stringin, "HL2:SBPM:HL18:DIGI_SYSID") {
	field(DESC, "Digitizer System ID")
	field(DTYP, "sis8300Digi")
# address is digitizer base address + register
	field(INP,  "#C5S0@0x4FA(8)")
	field(PINI, "YES")
}

# Sub Type
record(stringin, "HL2:SBPM:HL18:SUBSYS") {
	field(DESC, "Subsystem type")
	field(DTYP, "sis8300Digi")
# address is digitizer base address + register
	field(INP,  "#C5S0@0x4FC(8)")
	field(PINI, "YES")
}
# Registers on Struck AMC

# Digitizer AMC FW version
record(stringin, "HL2:SBPM:HL19:DIGIVERS") {
	field(DESC, "Digitizer Firmware Vers.")
	field(DTYP, "sis8300Digi")
# address is digitizer base address + register
	field(INP,  "#C6S0@0x4F8(8)")
	field(PINI, "YES")
}

# Firmware date
record(stringin, "HL2:SBPM:HL19:DIGIVERS_DATE") {
	field(DESC, "Firmware Vers. Date")
	field(DTYP, "sis8300Digi")
# address is digitizer base address + register
	field(INP,  "#C6S0@0x4FE(8)")
	field(PINI, "YES")
}

# System ID
record(stringin, "HL2:SBPM:HL19:DIGI_SYSID") {
	field(DESC, "Digitizer System ID")
	field(DTYP, "sis8300Digi")
# address is digitizer base address + register
	field(INP,  "#C6S0@0x4FA(8)")
	field(PINI, "YES")
}

# Sub Type
record(stringin, "HL2:SBPM:HL19:SUBSYS") {
	field(DESC, "Subsystem type")
	field(DTYP, "sis8300Digi")
# address is digitizer base address + register
	field(INP,  "#C6S0@0x4FC(8)")
	field(PINI, "YES")
}
# Registers on Struck AMC

# Digitizer AMC FW version
record(stringin, "HL2:SBPM:HL20:DIGIVERS") {
	field(DESC, "Digitizer Firmware Vers.")
	field(DTYP, "sis8300Digi")
# address is digitizer base address + register
	field(INP,  "#C7S0@0x4F8(8)")
	field(PINI, "YES")
}

# Firmware date
record(stringin, "HL2:SBPM:HL20:DIGIVERS_DATE") {
	field(DESC, "Firmware Vers. Date")
	field(DTYP, "sis8300Digi")
# address is digitizer base address + register
	field(INP,  "#C7S0@0x4FE(8)")
	field(PINI, "YES")
}

# System ID
record(stringin, "HL2:SBPM:HL20:DIGI_SYSID") {
	field(DESC, "Digitizer System ID")
	field(DTYP, "sis8300Digi")
# address is digitizer base address + register
	field(INP,  "#C7S0@0x4FA(8)")
	field(PINI, "YES")
}

# Sub Type
record(stringin, "HL2:SBPM:HL20:SUBSYS") {
	field(DESC, "Subsystem type")
	field(DTYP, "sis8300Digi")
# address is digitizer base address + register
	field(INP,  "#C7S0@0x4FC(8)")
	field(PINI, "YES")
}