#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(ai, "LION:LI24:708:VACT") {
  field(SCAN, ".1 second")
  field(DTYP, "Hytec IP-ADC-8413")
  field(INP, "@ADC-LI24-1-BCS:0:DATA")
  field(PREC, "3")
  field(LINR, "LINEAR")
  field(EGUF, "10.0")
  field(EGUL, "-10.0")
  field(EGU, "V")
  field(HOPR, "10")
  field(LOPR, "-10")
  field(DESC, "BC2LION-1N analog")
  field(HIHI, "1.5")
  field(LOLO, ".2")
  field(HHSV, "MINOR")
  field(LLSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("LION:LI24:708:VACT",20,35,0,0,"LION:LI24:708:VACT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(ai, "LION:LI24:709:VACT") {
  field(SCAN, ".1 second")
  field(DTYP, "Hytec IP-ADC-8413")
  field(INP, "@ADC-LI24-1-BCS:1:DATA")
  field(PREC, "3")
  field(LINR, "LINEAR")
  field(EGUF, "10.0")
  field(EGUL, "-10.0")
  field(EGU, "V")
  field(HOPR, "10")
  field(LOPR, "-10")
  field(DESC, "BC2LION-1S analog")
  field(HIHI, "1.5")
  field(LOLO, ".2")
  field(HHSV, "MINOR")
  field(LLSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("LION:LI24:709:VACT",20,35,0,0,"LION:LI24:709:VACT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(ai, "PICS:LI24:720:VACT") {
  field(SCAN, ".1 second")
  field(DTYP, "Hytec IP-ADC-8413")
  field(INP, "@ADC-LI24-1-BCS:8:DATA")
  field(PREC, "3")
  field(LINR, "LINEAR")
  field(EGUF, "10.0")
  field(EGUL, "-10.0")
  field(EGU, "V")
  field(HOPR, "10")
  field(LOPR, "-10")
  field(DESC, "MON-IC1 analog")
  field(HIHI, "1.5")
  field(LOLO, ".2")
  field(HHSV, "MINOR")
  field(LLSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PICS:LI24:720:VACT",20,35,0,0,"PICS:LI24:720:VACT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(ai, "PICS:LI24:721:VACT") {
  field(SCAN, ".1 second")
  field(DTYP, "Hytec IP-ADC-8413")
  field(INP, "@ADC-LI24-1-BCS:9:DATA")
  field(PREC, "3")
  field(LINR, "LINEAR")
  field(EGUF, "10.0")
  field(EGUL, "-10.0")
  field(EGU, "V")
  field(HOPR, "10")
  field(LOPR, "-10")
  field(DESC, "MON-IC2 analog")
  field(HIHI, "1.5")
  field(LOLO, ".2")
  field(HHSV, "MINOR")
  field(LLSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PICS:LI24:721:VACT",20,35,0,0,"PICS:LI24:721:VACT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(ai, "CHAS:LI24:BC01:VD1VACT") {
  field(SCAN, ".1 second")
  field(DTYP, "Hytec IP-ADC-8413")
  field(INP, "@ADC-LI24-1-BCS:10:DATA")
  field(PREC, "3")
  field(LINR, "LINEAR")
  field(EGUF, "10.0")
  field(EGUL, "-10.0")
  field(EGU, "V")
  field(HOPR, "10")
  field(LOPR, "-10")
  field(DESC, "PIC Chassis volt divider 1")
  field(HIHI, "12")
  field(LOLO, "8")
  field(HHSV, "MINOR")
  field(LLSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("CHAS:LI24:BC01:VD1VACT",20,35,0,0,"CHAS:LI24:BC01:VD1VACT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(ai, "CHAS:LI24:BC01:VD2VACT") {
  field(SCAN, ".1 second")
  field(DTYP, "Hytec IP-ADC-8413")
  field(INP, "@ADC-LI24-1-BCS:11:DATA")
  field(PREC, "3")
  field(LINR, "LINEAR")
  field(EGUF, "10.0")
  field(EGUL, "-10.0")
  field(EGU, "V")
  field(HOPR, "10")
  field(LOPR, "-10")
  field(DESC, "PIC Chassis volt divider 2")
  field(HIHI, "12")
  field(LOLO, "8")
  field(HHSV, "MINOR")
  field(LLSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("CHAS:LI24:BC01:VD2VACT",20,35,0,0,"CHAS:LI24:BC01:VD2VACT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "LION:LI24:708:BCSSTATE") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-LI24-1-BCS P0 B0")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "BC2LION-1N fault state")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("LION:LI24:708:BCSSTATE",2160,2153,0,1,"LION:LI24:708:BCSSTATE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "LION:LI24:709:BCSSTATE") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-LI24-1-BCS P0 B1")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "BC2LION-1S fault state")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("LION:LI24:709:BCSSTATE",2160,2153,0,1,"LION:LI24:709:BCSSTATE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "PICS:LI24:720:BCSSTATE") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-LI24-1-BCS P1 B0")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "MON-IC1 fault state")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("PICS:LI24:720:BCSSTATE",2160,2153,0,1,"PICS:LI24:720:BCSSTATE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "PICS:LI24:721:BCSSTATE") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-LI24-1-BCS P1 B1")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "MON-IC2 fault state")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("PICS:LI24:721:BCSSTATE",2160,2153,0,1,"PICS:LI24:721:BCSSTATE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "LION:LI24:708:BCSMODE") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-LI24-1-BCS P1 B2")
  field(ZNAM, "ACTIVE")
  field(ONAM, "BYPASS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "MINOR")
  field(DESC, "BC2LION-1N bypass mode")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("LION:LI24:708:BCSMODE",2160,2153,0,1,"LION:LI24:708:BCSMODE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "LION:LI24:709:BCSMODE") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-LI24-1-BCS P1 B3")
  field(ZNAM, "ACTIVE")
  field(ONAM, "BYPASS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "MINOR")
  field(DESC, "BC2LION-1S bypass mode")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("LION:LI24:709:BCSMODE",2160,2153,0,1,"LION:LI24:709:BCSMODE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "PICS:LI24:720:BCSMODE") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-LI24-1-BCS P2 B2")
  field(ZNAM, "ACTIVE")
  field(ONAM, "BYPASS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "MINOR")
  field(DESC, "MON-IC1 bypass mode")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("PICS:LI24:720:BCSMODE",2160,2153,0,1,"PICS:LI24:720:BCSMODE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "PICS:LI24:721:BCSMODE") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-LI24-1-BCS P2 B3")
  field(ZNAM, "ACTIVE")
  field(ONAM, "BYPASS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "MINOR")
  field(DESC, "MON-IC2 bypass mode")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("PICS:LI24:721:BCSMODE",2160,2153,0,1,"PICS:LI24:721:BCSMODE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "CHAS:LI24:BC01:HVSTATE") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-LI24-1-BCS P2 B4")
  field(ZNAM, "ON")
  field(ONAM, "OFF")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "MAJOR")
  field(DESC, "PIC chassis HV on state")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CHAS:LI24:BC01:HVSTATE",2160,2153,0,1,"CHAS:LI24:BC01:HVSTATE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "CHAS:LI24:BC02:HVSTATE") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-LI24-1-BCS P2 B5")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "LION chassis HV state")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CHAS:LI24:BC02:HVSTATE",2160,2153,0,1,"CHAS:LI24:BC02:HVSTATE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "BCS:LI24:1:24VSTATE") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-LI24-1-BCS P2 B6")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "24V power supply status")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BCS:LI24:1:24VSTATE",2160,2153,0,1,"BCS:LI24:1:24VSTATE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "BCS:LI24:1:PICSUM1") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-LI24-2-BCS P0 B0")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "PIC summary 1")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BCS:LI24:1:PICSUM1",2160,2153,0,1,"BCS:LI24:1:PICSUM1")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "BCS:LI24:1:PICSUM2") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-LI24-2-BCS P0 B1")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "PIC summary 2")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BCS:LI24:1:PICSUM2",2160,2153,0,1,"BCS:LI24:1:PICSUM2")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "BCS:LI24:1:LIONPSW1") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-LI24-2-BCS P0 B2")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "LION gas pressure switch 1")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BCS:LI24:1:LIONPSW1",2160,2153,0,1,"BCS:LI24:1:LIONPSW1")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "BCS:LI24:1:LIONPSW2") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-LI24-2-BCS P0 B3")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "LION gas pressure switch 2")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BCS:LI24:1:LIONPSW2",2160,2153,0,1,"BCS:LI24:1:LIONPSW2")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "BCS:LI24:1:PICSUM1MODE") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-LI24-2-BCS P1 B0")
  field(ZNAM, "ACTIVE")
  field(ONAM, "BYPASS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "MINOR")
  field(DESC, "PIC summary 1 bypass mode")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BCS:LI24:1:PICSUM1MODE",2160,2153,0,1,"BCS:LI24:1:PICSUM1MODE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "BCS:LI24:1:PICSUM2MODE") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-LI24-2-BCS P1 B1")
  field(ZNAM, "ACTIVE")
  field(ONAM, "BYPASS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "MINOR")
  field(DESC, "PIC summary 2 bypass mode")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BCS:LI24:1:PICSUM2MODE",2160,2153,0,1,"BCS:LI24:1:PICSUM2MODE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "BCS:LI24:1:LIONPSW1MODE") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-LI24-2-BCS P1 B2")
  field(ZNAM, "ACTIVE")
  field(ONAM, "BYPASS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "MINOR")
  field(DESC, "Pressure switch 1 byps mode")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BCS:LI24:1:LIONPSW1MODE",2160,2153,0,1,"BCS:LI24:1:LIONPSW1MODE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "BCS:LI24:1:LIONPSW2MODE") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-LI24-2-BCS P1 B3")
  field(ZNAM, "ACTIVE")
  field(ONAM, "BYPASS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "MINOR")
  field(DESC, "Pressure switch 2 byps mode")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BCS:LI24:1:LIONPSW2MODE",2160,2153,0,1,"BCS:LI24:1:LIONPSW2MODE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "SBI:LI24:1:SBI_ACC_NS") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-LI24-2-BCS P2 B0")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "ACC not seen in 1 sec")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("SBI:LI24:1:SBI_ACC_NS",2160,2153,0,1,"SBI:LI24:1:SBI_ACC_NS")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "SBI:LI24:1:SBI_STBY_PM") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-LI24-2-BCS P2 B1")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "SBI S24 SBTC permit")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("SBI:LI24:1:SBI_STBY_PM",2160,2153,0,1,"SBI:LI24:1:SBI_STBY_PM")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "SBI:LI24:1:SBI_ACC_OW") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-LI24-2-BCS P2 B2")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "ACC outside 20us window")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("SBI:LI24:1:SBI_ACC_OW",2160,2153,0,1,"SBI:LI24:1:SBI_ACC_OW")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "SBI:LI24:1:SBI_STBY_OW") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-LI24-2-BCS P2 B3")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "Standby outside 4us window")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("SBI:LI24:1:SBI_STBY_OW",2160,2153,0,1,"SBI:LI24:1:SBI_STBY_OW")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "SBI:LI24:1:SBI_STBY2") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-LI24-2-BCS P2 B4")
  field(ZNAM, "NOT_JUMPERED")
  field(ONAM, "JUMPERED")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "MINOR")
  field(DESC, "Standby delay SW2 (MSB)")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("SBI:LI24:1:SBI_STBY2",2160,2153,0,1,"SBI:LI24:1:SBI_STBY2")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "SBI:LI24:1:SBI_STBY1") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-LI24-2-BCS P2 B5")
  field(ZNAM, "NOT_JUMPERED")
  field(ONAM, "JUMPERED")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "MINOR")
  field(DESC, "Standby delay SW1")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("SBI:LI24:1:SBI_STBY1",2160,2153,0,1,"SBI:LI24:1:SBI_STBY1")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "SBI:LI24:1:SBI_STBY0") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-LI24-2-BCS P2 B6")
  field(ZNAM, "NOT_JUMPERED")
  field(ONAM, "JUMPERED")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "MINOR")
  field(DESC, "Standby delay SW0 (LSB)")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("SBI:LI24:1:SBI_STBY0",2160,2153,0,1,"SBI:LI24:1:SBI_STBY0")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "SBI:LI24:1:SBI_BCS_TIU") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-LI24-2-BCS P2 B7")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "SBI Permit")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("SBI:LI24:1:SBI_BCS_TIU",2160,2153,0,1,"SBI:LI24:1:SBI_BCS_TIU")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "SBI:LI24:1:SBI_RATE_ERR") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-LI24-2-BCS P3 B0")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "Standby rate error")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("SBI:LI24:1:SBI_RATE_ERR",2160,2153,0,1,"SBI:LI24:1:SBI_RATE_ERR")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND


record(bo, "CHAS:LI24:BC01:HVONSET") {
  field(DESC, "PIC chassis HV on command")
  field(SCAN, "Passive")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(FLNK, "CHAS:LI24:BC01:HVONSETH")
  field(OUT,  "CHAS:LI24:BC01:HVONSETH")
  field(ZNAM, "HV_OFF")
  field(ONAM, "HV_ON")
  field(ASG,  "DEFAULT")
  field(VAL,  "")
}

record(bo, "CHAS:LI24:BC01:HVONSETH") {
  field(DESC, "PIC chassis HV on command")
  field(SCAN, "Passive")
  field(DTYP, "XYCOM-2445")
  field(OUT, "@DO-LI24-1-BCS P0 B0")
  field(ZNAM, "HV_OFF")
  field(ONAM, "HV_ON")
  field(ASG,  "DEFAULT")
  field(HIGH, ".25")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CHAS:LI24:BC01:HVONSET",2140,2165,0,1,"CHAS:LI24:BC01:HVONSET")
#! Field("CHAS:LI24:BC01:HVONSET.FLNK",16777215,1,"CHAS:LI24:BC01:HVONSET.FLNK")
#! Link("CHAS:LI24:BC01:HVONSET.FLNK","CHAS:LI24:BC01:HVONSETH")
#! Field("CHAS:LI24:BC01:HVONSET.OUT",16777215,1,"CHAS:LI24:BC01:HVONSET.OUT")
#! Link("CHAS:LI24:BC01:HVONSET.OUT","CHAS:LI24:BC01:HVONSETH.VAL")
#! Record("CHAS:LI24:BC01:HVONSETH",2460,2232,0,0,"CHAS:LI24:BC01:HVONSETH")
#! Field("CHAS:LI24:BC01:HVONSETH.VAL",16777215,0,"CHAS:LI24:BC01:HVONSETH.VAL")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND


record(bo, "CHAS:LI24:BC01:HVOFFSET") {
  field(DESC, "PIC chassis HV off command")
  field(SCAN, "Passive")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(FLNK, "CHAS:LI24:BC01:HVOFFSETH")
  field(OUT,  "CHAS:LI24:BC01:HVOFFSETH")
  field(ZNAM, "HV_ON")
  field(ONAM, "HV_OFF")
  field(ASG,  "DEFAULT")
  field(VAL,  "")
}

record(bo, "CHAS:LI24:BC01:HVOFFSETH") {
  field(DESC, "PIC chassis HV off command")
  field(SCAN, "Passive")
  field(DTYP, "XYCOM-2445")
  field(OUT, "@DO-LI24-1-BCS P0 B1")
  field(ZNAM, "HV_ON")
  field(ONAM, "HV_OFF")
  field(ASG,  "DEFAULT")
  field(HIGH, ".25")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CHAS:LI24:BC01:HVOFFSET",2140,2165,0,1,"CHAS:LI24:BC01:HVOFFSET")
#! Field("CHAS:LI24:BC01:HVOFFSET.FLNK",16777215,1,"CHAS:LI24:BC01:HVOFFSET.FLNK")
#! Link("CHAS:LI24:BC01:HVOFFSET.FLNK","CHAS:LI24:BC01:HVOFFSETH")
#! Field("CHAS:LI24:BC01:HVOFFSET.OUT",16777215,1,"CHAS:LI24:BC01:HVOFFSET.OUT")
#! Link("CHAS:LI24:BC01:HVOFFSET.OUT","CHAS:LI24:BC01:HVOFFSETH.VAL")
#! Record("CHAS:LI24:BC01:HVOFFSETH",2460,2232,0,0,"CHAS:LI24:BC01:HVOFFSETH")
#! Field("CHAS:LI24:BC01:HVOFFSETH.VAL",16777215,0,"CHAS:LI24:BC01:HVOFFSETH.VAL")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND


record(bo, "CHAS:LI24:BC01:RESET") {
  field(DESC, "PIC chassis reset command")
  field(SCAN, "Passive")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(FLNK, "CHAS:LI24:BC01:RESETH")
  field(OUT,  "CHAS:LI24:BC01:RESETH")
  field(ZNAM, "NOT_RESET")
  field(ONAM, "RESET")
  field(ASG,  "DEFAULT")
  field(VAL,  "")
}

record(bo, "CHAS:LI24:BC01:RESETH") {
  field(DESC, "PIC chassis reset command")
  field(SCAN, "Passive")
  field(DTYP, "XYCOM-2445")
  field(OUT, "@DO-LI24-1-BCS P0 B2")
  field(ZNAM, "NOT_RESET")
  field(ONAM, "RESET")
  field(ASG,  "DEFAULT")
  field(HIGH, ".25")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("CHAS:LI24:BC01:RESET",2140,2165,0,1,"CHAS:LI24:BC01:RESET")
#! Field("CHAS:LI24:BC01:RESET.FLNK",16777215,1,"CHAS:LI24:BC01:RESET.FLNK")
#! Link("CHAS:LI24:BC01:RESET.FLNK","CHAS:LI24:BC01:RESETH")
#! Field("CHAS:LI24:BC01:RESET.OUT",16777215,1,"CHAS:LI24:BC01:RESET.OUT")
#! Link("CHAS:LI24:BC01:RESET.OUT","CHAS:LI24:BC01:RESETH.VAL")
#! Record("CHAS:LI24:BC01:RESETH",2460,2232,0,0,"CHAS:LI24:BC01:RESETH")
#! Field("CHAS:LI24:BC01:RESETH.VAL",16777215,0,"CHAS:LI24:BC01:RESETH.VAL")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND


record(bo, "SBI:LI24:1:SBI_STB0_SD") {
  field(DESC, "Stnby Delay expected0, LSB")
  field(SCAN, "Passive")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(FLNK, "SBI:LI24:1:SBI_STB0_SDH")
  field(OUT, "SBI:LI24:1:SBI_STB0_SDH")
  field(ZNAM, "NOT_JUMPERED")
  field(ONAM, "JUMPERED")
  field(ASG, "EOICDESK")
  field(VAL, "1")
  info(autosaveFields_pass0, "VAL")
}

record(bo, "SBI:LI24:1:SBI_STB0_SDH") {
  field(DESC, "Stnby Delay expected0, LSB")
  field(SCAN, "Passive")
  field(DTYP, "XYCOM-2445")
  field(OUT, "@DO-LI24-1-BCS P1 B1")
  field(ZNAM, "NOT_JUMPERED")
  field(ONAM, "JUMPERED")
  field(ASG, "EOICDESK")
  field(HIGH, "")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("SBI:LI24:1:SBI_STB0_SD",2140,2165,0,1,"SBI:LI24:1:SBI_STB0_SD")
#! Field("SBI:LI24:1:SBI_STB0_SD.FLNK",16777215,1,"SBI:LI24:1:SBI_STB0_SD.FLNK")
#! Link("SBI:LI24:1:SBI_STB0_SD.FLNK","SBI:LI24:1:SBI_STB0_SDH")
#! Field("SBI:LI24:1:SBI_STB0_SD.OUT",16777215,1,"SBI:LI24:1:SBI_STB0_SD.OUT")
#! Link("SBI:LI24:1:SBI_STB0_SD.OUT","SBI:LI24:1:SBI_STB0_SDH.VAL")
#! Record("SBI:LI24:1:SBI_STB0_SDH",2460,2232,0,0,"SBI:LI24:1:SBI_STB0_SDH")
#! Field("SBI:LI24:1:SBI_STB0_SDH.VAL",16777215,0,"SBI:LI24:1:SBI_STB0_SDH.VAL")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND


record(bo, "SBI:LI24:1:SBI_STB1_SD") {
  field(DESC, "Stnby Delay expected1")
  field(SCAN, "Passive")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(FLNK, "SBI:LI24:1:SBI_STB1_SDH")
  field(OUT, "SBI:LI24:1:SBI_STB1_SDH")
  field(ZNAM, "NOT_JUMPERED")
  field(ONAM, "JUMPERED")
  field(ASG, "EOICDESK")
  field(VAL, "0")
  info(autosaveFields_pass0, "VAL")
}

record(bo, "SBI:LI24:1:SBI_STB1_SDH") {
  field(DESC, "Stnby Delay expected1")
  field(SCAN, "Passive")
  field(DTYP, "XYCOM-2445")
  field(OUT, "@DO-LI24-1-BCS P1 B2")
  field(ZNAM, "NOT_JUMPERED")
  field(ONAM, "JUMPERED")
  field(ASG, "EOICDESK")
  field(HIGH, "")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("SBI:LI24:1:SBI_STB1_SD",2140,2165,0,1,"SBI:LI24:1:SBI_STB1_SD")
#! Field("SBI:LI24:1:SBI_STB1_SD.FLNK",16777215,1,"SBI:LI24:1:SBI_STB1_SD.FLNK")
#! Link("SBI:LI24:1:SBI_STB1_SD.FLNK","SBI:LI24:1:SBI_STB1_SDH")
#! Field("SBI:LI24:1:SBI_STB1_SD.OUT",16777215,1,"SBI:LI24:1:SBI_STB1_SD.OUT")
#! Link("SBI:LI24:1:SBI_STB1_SD.OUT","SBI:LI24:1:SBI_STB1_SDH.VAL")
#! Record("SBI:LI24:1:SBI_STB1_SDH",2460,2232,0,0,"SBI:LI24:1:SBI_STB1_SDH")
#! Field("SBI:LI24:1:SBI_STB1_SDH.VAL",16777215,0,"SBI:LI24:1:SBI_STB1_SDH.VAL")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND


record(bo, "SBI:LI24:1:SBI_STB2_SD") {
  field(DESC, "Stnby Delay expected2, MSB")
  field(SCAN, "Passive")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(FLNK, "SBI:LI24:1:SBI_STB2_SDH")
  field(OUT, "SBI:LI24:1:SBI_STB2_SDH")
  field(ZNAM, "NOT_JUMPERED")
  field(ONAM, "JUMPERED")
  field(ASG, "EOICDESK")
  field(VAL, "1")
  info(autosaveFields_pass0, "VAL")
}

record(bo, "SBI:LI24:1:SBI_STB2_SDH") {
  field(DESC, "Stnby Delay expected2, MSB")
  field(SCAN, "Passive")
  field(DTYP, "XYCOM-2445")
  field(OUT, "@DO-LI24-1-BCS P1 B3")
  field(ZNAM, "NOT_JUMPERED")
  field(ONAM, "JUMPERED")
  field(ASG, "EOICDESK")
  field(HIGH, "")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("SBI:LI24:1:SBI_STB2_SD",2140,2165,0,1,"SBI:LI24:1:SBI_STB2_SD")
#! Field("SBI:LI24:1:SBI_STB2_SD.FLNK",16777215,1,"SBI:LI24:1:SBI_STB2_SD.FLNK")
#! Link("SBI:LI24:1:SBI_STB2_SD.FLNK","SBI:LI24:1:SBI_STB2_SDH")
#! Field("SBI:LI24:1:SBI_STB2_SD.OUT",16777215,1,"SBI:LI24:1:SBI_STB2_SD.OUT")
#! Link("SBI:LI24:1:SBI_STB2_SD.OUT","SBI:LI24:1:SBI_STB2_SDH.VAL")
#! Record("SBI:LI24:1:SBI_STB2_SDH",2460,2232,0,0,"SBI:LI24:1:SBI_STB2_SDH")
#! Field("SBI:LI24:1:SBI_STB2_SDH.VAL",16777215,0,"SBI:LI24:1:SBI_STB2_SDH.VAL")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND


record(bo, "SBI:LI24:1:SBI_STB0_SR") {
  field(DESC, "Stnby rate bit 0, LSB")
  field(SCAN, "Passive")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(FLNK, "SBI:LI24:1:SBI_STB0_SRH")
  field(OUT, "SBI:LI24:1:SBI_STB0_SRH")
  field(ZNAM, "SET")
  field(ONAM, "NOT_SET")
  field(ASG, "EOICDESK")
  field(VAL, "")
  info(autosaveFields_pass0, "VAL")
}

record(bo, "SBI:LI24:1:SBI_STB0_SRH") {
  field(DESC, "Stnby rate bit 0, LSB")
  field(SCAN, "Passive")
  field(DTYP, "XYCOM-2445")
  field(OUT, "@DO-LI24-1-BCS P1 B4")
  field(ZNAM, "SET")
  field(ONAM, "NOT_SET")
  field(ASG, "EOICDESK")
  field(HIGH, "")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("SBI:LI24:1:SBI_STB0_SR",2140,2165,0,1,"SBI:LI24:1:SBI_STB0_SR")
#! Field("SBI:LI24:1:SBI_STB0_SR.FLNK",16777215,1,"SBI:LI24:1:SBI_STB0_SR.FLNK")
#! Link("SBI:LI24:1:SBI_STB0_SR.FLNK","SBI:LI24:1:SBI_STB0_SRH")
#! Field("SBI:LI24:1:SBI_STB0_SR.OUT",16777215,1,"SBI:LI24:1:SBI_STB0_SR.OUT")
#! Link("SBI:LI24:1:SBI_STB0_SR.OUT","SBI:LI24:1:SBI_STB0_SRH.VAL")
#! Record("SBI:LI24:1:SBI_STB0_SRH",2460,2232,0,0,"SBI:LI24:1:SBI_STB0_SRH")
#! Field("SBI:LI24:1:SBI_STB0_SRH.VAL",16777215,0,"SBI:LI24:1:SBI_STB0_SRH.VAL")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND


record(bo, "SBI:LI24:1:SBI_STB1_SR") {
  field(DESC, "Stnby rate bit 1, MSB")
  field(SCAN, "Passive")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(FLNK, "SBI:LI24:1:SBI_STB1_SRH")
  field(OUT, "SBI:LI24:1:SBI_STB1_SRH")
  field(ZNAM, "SET")
  field(ONAM, "NOT_SET")
  field(ASG, "EOICDESK")
  field(VAL, "")
  info(autosaveFields_pass0, "VAL")
}

record(bo, "SBI:LI24:1:SBI_STB1_SRH") {
  field(DESC, "Stnby rate bit 1, MSB")
  field(SCAN, "Passive")
  field(DTYP, "XYCOM-2445")
  field(OUT, "@DO-LI24-1-BCS P1 B5")
  field(ZNAM, "SET")
  field(ONAM, "NOT_SET")
  field(ASG, "EOICDESK")
  field(HIGH, "")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("SBI:LI24:1:SBI_STB1_SR",2140,2165,0,1,"SBI:LI24:1:SBI_STB1_SR")
#! Field("SBI:LI24:1:SBI_STB1_SR.FLNK",16777215,1,"SBI:LI24:1:SBI_STB1_SR.FLNK")
#! Link("SBI:LI24:1:SBI_STB1_SR.FLNK","SBI:LI24:1:SBI_STB1_SRH")
#! Field("SBI:LI24:1:SBI_STB1_SR.OUT",16777215,1,"SBI:LI24:1:SBI_STB1_SR.OUT")
#! Link("SBI:LI24:1:SBI_STB1_SR.OUT","SBI:LI24:1:SBI_STB1_SRH.VAL")
#! Record("SBI:LI24:1:SBI_STB1_SRH",2460,2232,0,0,"SBI:LI24:1:SBI_STB1_SRH")
#! Field("SBI:LI24:1:SBI_STB1_SRH.VAL",16777215,0,"SBI:LI24:1:SBI_STB1_SRH.VAL")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND


record(mbbi, "LION:LI24:708:BCSSTATESUM") {
  field(DESC, "LION 1A fault summary")
  field(SCAN, "Passive")
  field(DTYP, "Soft Channel")
  field(ZRSV, "MAJOR")
  field(ONSV, "NO_ALARM")
  field(TWSV, "MINOR")
  field(ONST, "OK")
  field(TWST, "BYPASS")
  field(ZRST, "FAULT")
}

record(calcout, "LION:LI24:708:BCSSTATECALC") {
  field(SCAN, ".1 second")
  field(DTYP, "Soft Channel")
  field(FLNK, "LION:LI24:708:BCSSTATESUM PP MS")
  field(INPA, "LION:LI24:708:BCSSTATE MS")
  field(INPB, "LION:LI24:708:BCSMODE MS")
  field(OUT, "LION:LI24:708:BCSSTATESUM NPP MS")
  field(CALC, "B?2:A")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("LION:LI24:708:BCSSTATESUM",400,179,0,0,"LION:LI24:708:BCSSTATESUM")
#! Field("LION:LI24:708:BCSSTATESUM.VAL",16777215,0,"LION:LI24:708:BCSSTATESUM.VAL")
#! Record("LION:LI24:708:BCSSTATECALC",20,166,0,0,"LION:LI24:708:BCSSTATECALC")
#! Field("LION:LI24:708:BCSSTATECALC.FLNK",16777215,1,"LION:LI24:708:BCSSTATECALC.FLNK")
#! Link("LION:LI24:708:BCSSTATECALC.FLNK","LION:LI24:708:BCSSTATESUM")
#! Field("LION:LI24:708:BCSSTATECALC.INPA",16777215,1,"LION:LI24:708:BCSSTATECALC.INPA")
#! Field("LION:LI24:708:BCSSTATECALC.INPB",16777215,1,"LION:LI24:708:BCSSTATECALC.INPB")
#! Field("LION:LI24:708:BCSSTATECALC.OUT",16777215,1,"LION:LI24:708:BCSSTATECALC.OUT")
#! Link("LION:LI24:708:BCSSTATECALC.OUT","LION:LI24:708:BCSSTATESUM.VAL")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND


record(mbbi, "LION:LI24:709:BCSSTATESUM") {
  field(DESC, "LION 1B fault summary")
  field(SCAN, "Passive")
  field(DTYP, "Soft Channel")
  field(ZRSV, "MAJOR")
  field(ONSV, "NO_ALARM")
  field(TWSV, "MINOR")
  field(ONST, "OK")
  field(TWST, "BYPASS")
  field(ZRST, "FAULT")
}

record(calcout, "LION:LI24:709:BCSSTATECALC") {
  field(SCAN, ".1 second")
  field(DTYP, "Soft Channel")
  field(FLNK, "LION:LI24:709:BCSSTATESUM PP MS")
  field(INPA, "LION:LI24:709:BCSSTATE MS")
  field(INPB, "LION:LI24:709:BCSMODE MS")
  field(OUT, "LION:LI24:709:BCSSTATESUM NPP MS")
  field(CALC, "B?2:A")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("LION:LI24:709:BCSSTATESUM",400,179,0,0,"LION:LI24:709:BCSSTATESUM")
#! Field("LION:LI24:709:BCSSTATESUM.VAL",16777215,0,"LION:LI24:709:BCSSTATESUM.VAL")
#! Record("LION:LI24:709:BCSSTATECALC",20,166,0,0,"LION:LI24:709:BCSSTATECALC")
#! Field("LION:LI24:709:BCSSTATECALC.FLNK",16777215,1,"LION:LI24:709:BCSSTATECALC.FLNK")
#! Link("LION:LI24:709:BCSSTATECALC.FLNK","LION:LI24:709:BCSSTATESUM")
#! Field("LION:LI24:709:BCSSTATECALC.INPA",16777215,1,"LION:LI24:709:BCSSTATECALC.INPA")
#! Field("LION:LI24:709:BCSSTATECALC.INPB",16777215,1,"LION:LI24:709:BCSSTATECALC.INPB")
#! Field("LION:LI24:709:BCSSTATECALC.OUT",16777215,1,"LION:LI24:709:BCSSTATECALC.OUT")
#! Link("LION:LI24:709:BCSSTATECALC.OUT","LION:LI24:709:BCSSTATESUM.VAL")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND


record(mbbi, "BCS:LI24:1:PICSUM1SUM") {
  field(DESC, "PIC summary 1 summary")
  field(SCAN, "Passive")
  field(DTYP, "Soft Channel")
  field(ZRSV, "MAJOR")
  field(ONSV, "NO_ALARM")
  field(TWSV, "MINOR")
  field(ONST, "OK")
  field(TWST, "BYPASS")
  field(ZRST, "FAULT")
}

record(calcout, "BCS:LI24:1:PICSUM1CALC") {
  field(SCAN, ".1 second")
  field(DTYP, "Soft Channel")
  field(FLNK, "BCS:LI24:1:PICSUM1SUM PP MS")
  field(INPA, "BCS:LI24:1:PICSUM1 MS")
  field(INPB, "BCS:LI24:1:PICSUM1MODE MS")
  field(OUT, "BCS:LI24:1:PICSUM1SUM NPP MS")
  field(CALC, "B?2:A")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BCS:LI24:1:PICSUM1SUM",400,179,0,0,"BCS:LI24:1:PICSUM1SUM")
#! Field("BCS:LI24:1:PICSUM1SUM.VAL",16777215,0,"BCS:LI24:1:PICSUM1SUM.VAL")
#! Record("BCS:LI24:1:PICSUM1CALC",20,166,0,0,"BCS:LI24:1:PICSUM1CALC")
#! Field("BCS:LI24:1:PICSUM1CALC.FLNK",16777215,1,"BCS:LI24:1:PICSUM1CALC.FLNK")
#! Link("BCS:LI24:1:PICSUM1CALC.FLNK","BCS:LI24:1:PICSUM1SUM")
#! Field("BCS:LI24:1:PICSUM1CALC.INPA",16777215,1,"BCS:LI24:1:PICSUM1CALC.INPA")
#! Field("BCS:LI24:1:PICSUM1CALC.INPB",16777215,1,"BCS:LI24:1:PICSUM1CALC.INPB")
#! Field("BCS:LI24:1:PICSUM1CALC.OUT",16777215,1,"BCS:LI24:1:PICSUM1CALC.OUT")
#! Link("BCS:LI24:1:PICSUM1CALC.OUT","BCS:LI24:1:PICSUM1SUM.VAL")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND


record(mbbi, "BCS:LI24:1:PICSUM2SUM") {
  field(DESC, "PIC summary 2 summary")
  field(SCAN, "Passive")
  field(DTYP, "Soft Channel")
  field(ZRSV, "MAJOR")
  field(ONSV, "NO_ALARM")
  field(TWSV, "MINOR")
  field(ONST, "OK")
  field(TWST, "BYPASS")
  field(ZRST, "FAULT")
}

record(calcout, "BCS:LI24:1:PICSUM2CALC") {
  field(SCAN, ".1 second")
  field(DTYP, "Soft Channel")
  field(FLNK, "BCS:LI24:1:PICSUM2SUM PP MS")
  field(INPA, "BCS:LI24:1:PICSUM2 MS")
  field(INPB, "BCS:LI24:1:PICSUM2MODE MS")
  field(OUT, "BCS:LI24:1:PICSUM2SUM NPP MS")
  field(CALC, "B?2:A")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BCS:LI24:1:PICSUM2SUM",400,179,0,0,"BCS:LI24:1:PICSUM2SUM")
#! Field("BCS:LI24:1:PICSUM2SUM.VAL",16777215,0,"BCS:LI24:1:PICSUM2SUM.VAL")
#! Record("BCS:LI24:1:PICSUM2CALC",20,166,0,0,"BCS:LI24:1:PICSUM2CALC")
#! Field("BCS:LI24:1:PICSUM2CALC.FLNK",16777215,1,"BCS:LI24:1:PICSUM2CALC.FLNK")
#! Link("BCS:LI24:1:PICSUM2CALC.FLNK","BCS:LI24:1:PICSUM2SUM")
#! Field("BCS:LI24:1:PICSUM2CALC.INPA",16777215,1,"BCS:LI24:1:PICSUM2CALC.INPA")
#! Field("BCS:LI24:1:PICSUM2CALC.INPB",16777215,1,"BCS:LI24:1:PICSUM2CALC.INPB")
#! Field("BCS:LI24:1:PICSUM2CALC.OUT",16777215,1,"BCS:LI24:1:PICSUM2CALC.OUT")
#! Link("BCS:LI24:1:PICSUM2CALC.OUT","BCS:LI24:1:PICSUM2SUM.VAL")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND


record(mbbi, "BCS:LI24:1:LIONPSW1SUM") {
  field(DESC, "LION gas prssr swtch 1 sum")
  field(SCAN, "Passive")
  field(DTYP, "Soft Channel")
  field(ZRSV, "MAJOR")
  field(ONSV, "NO_ALARM")
  field(TWSV, "MINOR")
  field(ONST, "OK")
  field(TWST, "BYPASS")
  field(ZRST, "FAULT")
}

record(calcout, "BCS:LI24:1:LIONPSW1CALC") {
  field(SCAN, ".1 second")
  field(DTYP, "Soft Channel")
  field(FLNK, "BCS:LI24:1:LIONPSW1SUM PP MS")
  field(INPA, "BCS:LI24:1:LIONPSW1 MS")
  field(INPB, "BCS:LI24:1:LIONPSW1MODE MS")
  field(OUT, "BCS:LI24:1:LIONPSW1SUM NPP MS")
  field(CALC, "B?2:A")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BCS:LI24:1:LIONPSW1SUM",400,179,0,0,"BCS:LI24:1:LIONPSW1SUM")
#! Field("BCS:LI24:1:LIONPSW1SUM.VAL",16777215,0,"BCS:LI24:1:LIONPSW1SUM.VAL")
#! Record("BCS:LI24:1:LIONPSW1CALC",20,166,0,0,"BCS:LI24:1:LIONPSW1CALC")
#! Field("BCS:LI24:1:LIONPSW1CALC.FLNK",16777215,1,"BCS:LI24:1:LIONPSW1CALC.FLNK")
#! Link("BCS:LI24:1:LIONPSW1CALC.FLNK","BCS:LI24:1:LIONPSW1SUM")
#! Field("BCS:LI24:1:LIONPSW1CALC.INPA",16777215,1,"BCS:LI24:1:LIONPSW1CALC.INPA")
#! Field("BCS:LI24:1:LIONPSW1CALC.INPB",16777215,1,"BCS:LI24:1:LIONPSW1CALC.INPB")
#! Field("BCS:LI24:1:LIONPSW1CALC.OUT",16777215,1,"BCS:LI24:1:LIONPSW1CALC.OUT")
#! Link("BCS:LI24:1:LIONPSW1CALC.OUT","BCS:LI24:1:LIONPSW1SUM.VAL")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND


record(mbbi, "BCS:LI24:1:LIONPSW2SUM") {
  field(DESC, "LION gas prssr swtch 2 sum")
  field(SCAN, "Passive")
  field(DTYP, "Soft Channel")
  field(ZRSV, "MAJOR")
  field(ONSV, "NO_ALARM")
  field(TWSV, "MINOR")
  field(ONST, "OK")
  field(TWST, "BYPASS")
  field(ZRST, "FAULT")
}

record(calcout, "BCS:LI24:1:LIONPSW2CALC") {
  field(SCAN, ".1 second")
  field(DTYP, "Soft Channel")
  field(FLNK, "BCS:LI24:1:LIONPSW2SUM PP MS")
  field(INPA, "BCS:LI24:1:LIONPSW2 MS")
  field(INPB, "BCS:LI24:1:LIONPSW2MODE MS")
  field(OUT, "BCS:LI24:1:LIONPSW2SUM NPP MS")
  field(CALC, "B?2:A")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BCS:LI24:1:LIONPSW2SUM",400,179,0,0,"BCS:LI24:1:LIONPSW2SUM")
#! Field("BCS:LI24:1:LIONPSW2SUM.VAL",16777215,0,"BCS:LI24:1:LIONPSW2SUM.VAL")
#! Record("BCS:LI24:1:LIONPSW2CALC",20,166,0,0,"BCS:LI24:1:LIONPSW2CALC")
#! Field("BCS:LI24:1:LIONPSW2CALC.FLNK",16777215,1,"BCS:LI24:1:LIONPSW2CALC.FLNK")
#! Link("BCS:LI24:1:LIONPSW2CALC.FLNK","BCS:LI24:1:LIONPSW2SUM")
#! Field("BCS:LI24:1:LIONPSW2CALC.INPA",16777215,1,"BCS:LI24:1:LIONPSW2CALC.INPA")
#! Field("BCS:LI24:1:LIONPSW2CALC.INPB",16777215,1,"BCS:LI24:1:LIONPSW2CALC.INPB")
#! Field("BCS:LI24:1:LIONPSW2CALC.OUT",16777215,1,"BCS:LI24:1:LIONPSW2CALC.OUT")
#! Link("BCS:LI24:1:LIONPSW2CALC.OUT","BCS:LI24:1:LIONPSW2SUM.VAL")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(calcout, "SBI:LI24:1:SBI_DELAYCLC") {
  field(SCAN, "1 second")
  field(DTYP, "Soft Channel")
  field(CALC, "(A==B)&&(C==D)&&(E==F)")
  field(INPA, "SBI:LI24:1:SBI_STB0_SD")
  field(INPB, "SBI:LI24:1:SBI_STBY0")
  field(INPC, "SBI:LI24:1:SBI_STB1_SD")
  field(INPD, "SBI:LI24:1:SBI_STBY1")
  field(INPE, "SBI:LI24:1:SBI_STB2_SD")
  field(INPF, "SBI:LI24:1:SBI_STBY2")
  field(LOLO, "0")
  field(LLSV, "MAJOR")
  field(FLNK, "SBI:LI24:1:SBI_DELAY")
  field(OUT, "SBI:LI24:1:SBI_DELAY")
}


record(bi, "SBI:LI24:1:SBI_DELAY") {
  field(SCAN, "Passive")
  field(DTYP, "Soft Channel")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("SBI:LI24:1:SBI_DELAYCLC",20,-17,0,0,"SBI:LI24:1:SBI_DELAYCLC")
#! Field("SBI:LI24:1:SBI_DELAYCLC.INPA",16777215,1,"SBI:LI24:1:SBI_DELAYCLC.INPA")
#! Field("SBI:LI24:1:SBI_DELAYCLC.INPB",16777215,1,"SBI:LI24:1:SBI_DELAYCLC.INPB")
#! Field("SBI:LI24:1:SBI_DELAYCLC.INPC",16777215,1,"SBI:LI24:1:SBI_DELAYCLC.INPC")
#! Field("SBI:LI24:1:SBI_DELAYCLC.INPD",16777215,1,"SBI:LI24:1:SBI_DELAYCLC.INPD")
#! Field("SBI:LI24:1:SBI_DELAYCLC.INPE",16777215,1,"SBI:LI24:1:SBI_DELAYCLC.INPE")
#! Field("SBI:LI24:1:SBI_DELAYCLC.INPF",16777215,1,"SBI:LI24:1:SBI_DELAYCLC.INPF")
#! Field("SBI:LI24:1:SBI_DELAYCLC.OUT",16777215,1,"SBI:LI24:1:SBI_DELAYCLC.OUT")
#! Link("SBI:LI24:1:SBI_DELAYCLC.OUT","SBI:LI24:1:SBI_DELAY.VAL")
#! Field("SBI:LI24:1:SBI_DELAYCLC.FLNK",16777215,1,"SBI:LI24:1:SBI_DELAYCLC.FLNK")
#! Link("SBI:LI24:1:SBI_DELAYCLC.FLNK","SBI:LI24:1:SBI_DELAY")
#! Record("SBI:LI24:1:SBI_DELAY",460,180,0,0,"SBI:LI24:1:SBI_DELAY")
#! Field("SBI:LI24:1:SBI_DELAY.VAL",16777215,0,"SBI:LI24:1:SBI_DELAY.VAL")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bo, SBI:LI24:1:GUN_SIG) {
  field(DTYP, "Soft Channel")
  field(DOL, "1")
  field(OUT, "SBI:LI24:1:GUN_CLEAR PP")
}

record(bo, SBI:LI24:1:GUN_CLEAR) {
  field(DESC, "Clear status")
  field(DTYP, "XYCOM-2445")
  field(OUT, "@DO-LI24-1-BCS P1 B0")
  field(HIGH, ".1")
}


record(bi, SBI:LI24:1:SBI_NO119) {
  field(DESC, "119 MHz missing")
  field(SCAN, "2 second")
  field(DTYP, "XYCOM-2440")
  field(FLNK, "SBI:LI24:1:GUN_SIG")
  field(INP, "@DI-LI24-2-BCS P3 B1")
  field(ZSV, "MAJOR")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
}