# Template file for HPI 6012 Rad detector display # Use with hpi_6012.proto # 20190613 mdunning record(stringin, "RADM:FEES:90:LOCATION"){ field(DESC, "ND1S") field(VAL, "FEES Z=3782.5m") field(PINI, "1") } record(stringin, "RADM:FEES:90:IOCNAME"){ field(DESC, "IOC name") field(VAL, "sioc-fees-bc01") field(PINI, "1") } # Using streamdevice, this record pushes values to StatusRaw, # DoseRate, and DoseRate.EGU. # Instead of using "I/O Intr" scanning, we scan at 1 Hz so that a read error # is triggered when the device is offline. When a read error is triggered, # we can get stream/asyn to reconnect the port automatically. record(longin, "RADM:FEES:90:NeutronDoseRateRaw"){ field(DESC, "Raw dose rate") field(DTYP, "stream") field(INP, "@hpi_6012.proto read(RADM:FEES:90,Neutron) BREM_TSPORT1") field(EGU, "Cts/sec") field(HIHI, "") field(HIGH, "") field(HSV, "NO_ALARM") field(HHSV, "NO_ALARM") field(HYST, "") field(SCAN, "I/O Intr") field(FLNK, "RADM:FEES:90:NeutronDoseRate") info(autosaveFields, "LOLO LOW HIGH HIHI HYST LLSV LSV HSV HHSV") } record(ai, "RADM:FEES:90:NeutronDoseRate"){ field(DESC, "Dose rate") field(PREC, "2") field(HIHI, "") field(HIGH, "") field(HSV, "NO_ALARM") field(HHSV, "NO_ALARM") field(HYST, "") field(FLNK, "RADM:FEES:90:StatusRaw") info(autosaveFields, "LOLO LOW HIGH HIHI HYST LLSV LSV HSV HHSV") } record(mbbiDirect, "RADM:FEES:90:StatusRaw"){ field(DESC, "Status Byte") field(FLNK, "RADM:FEES:90:Alarm1") } record(bi, "RADM:FEES:90:Alarm1"){ field(DESC, "Alarm 1 (Trip high)") field(INP, "RADM:FEES:90:StatusRaw.B0") field(ZNAM, "OK") field(ONAM, "FAULT") field(OSV, "MAJOR") field(FLNK, "RADM:FEES:90:Alarm2") } record(bi, "RADM:FEES:90:Alarm2"){ field(DESC, "Alarm 2 (Trip low)") field(INP, "RADM:FEES:90:StatusRaw.B1") field(ZNAM, "OK") field(ONAM, "FAULT") field(OSV, "MAJOR") field(FLNK, "RADM:FEES:90:DetectorStatus") } record(bi, "RADM:FEES:90:DetectorStatus"){ field(DESC, "Detector status") field(INP, "RADM:FEES:90:StatusRaw.B2") field(ZNAM, "OK") field(ONAM, "FAIL") field(OSV, "MAJOR") } record(stringin, "RADM:FEES:90:Debug"){ field(DESC, "Raw device output") field(DTYP, "stream") field(SCAN, "I/O Intr") field(INP, "@hpi_6012.proto debug BREM_TSPORT1") field(FLNK, "RADM:FEES:90:Heartbeat") } record(calcout, "RADM:FEES:90:Heartbeat"){ field(DESC, "Heartbeat") field(CALC, "VAL>=100?0:(VAL+1)") field(DOPT, "Use OCAL") field(OCAL, "0") field(OVAL, "0") field(OUT, "RADM:FEES:90:ErrorCount PP") } record(calcout, "RADM:FEES:90:ErrorCount"){ field(DESC, "Errors since last read") field(INPA, "RADM:FEES:90:ErrorCount") field(CALC, "(VAL+2)") field(SCAN, "2 second") field(HIHI, "4") field(HHSV, "MAJOR") field(DOPT, "Use OCAL") field(OCAL, "(A>10)?1:0") field(OUT, "RADM:FEES:90:ReadStatus PP") } record(bi, "RADM:FEES:90:ReadStatus"){ field(DESC, "Read status") field(ZNAM, "OK") field(ONAM, "ERROR") field(OSV, "MAJOR") } record(bo, "RADM:FEES:90:LatchReset"){ field(DESC, "Reset latches") field(ZNAM, "Standby") field(ONAM, "Reset") } record(stringin, "RADM:FEES:90:ReadCheck"){ field(DESC, "Trigger asyn disconnect on read error") field(DTYP, "stream") field(SCAN, "1 second") field(INP, "@hpi_6012.proto readCheck BREM_TSPORT1") } # Template file for HPI 6012 Rad detector display # Use with hpi_6012.proto # 20190613 mdunning record(stringin, "RADM:FEES:100:LOCATION"){ field(DESC, "ND2S") field(VAL, "FEES Z=3795.2m") field(PINI, "1") } record(stringin, "RADM:FEES:100:IOCNAME"){ field(DESC, "IOC name") field(VAL, "sioc-fees-bc01") field(PINI, "1") } # Using streamdevice, this record pushes values to StatusRaw, # DoseRate, and DoseRate.EGU. # Instead of using "I/O Intr" scanning, we scan at 1 Hz so that a read error # is triggered when the device is offline. When a read error is triggered, # we can get stream/asyn to reconnect the port automatically. record(longin, "RADM:FEES:100:NeutronDoseRateRaw"){ field(DESC, "Raw dose rate") field(DTYP, "stream") field(INP, "@hpi_6012.proto read(RADM:FEES:100,Neutron) BREM_TSPORT2") field(EGU, "Cts/sec") field(HIHI, "") field(HIGH, "") field(HSV, "NO_ALARM") field(HHSV, "NO_ALARM") field(HYST, "") field(SCAN, "I/O Intr") field(FLNK, "RADM:FEES:100:NeutronDoseRate") info(autosaveFields, "LOLO LOW HIGH HIHI HYST LLSV LSV HSV HHSV") } record(ai, "RADM:FEES:100:NeutronDoseRate"){ field(DESC, "Dose rate") field(PREC, "2") field(HIHI, "") field(HIGH, "") field(HSV, "NO_ALARM") field(HHSV, "NO_ALARM") field(HYST, "") field(FLNK, "RADM:FEES:100:StatusRaw") info(autosaveFields, "LOLO LOW HIGH HIHI HYST LLSV LSV HSV HHSV") } record(mbbiDirect, "RADM:FEES:100:StatusRaw"){ field(DESC, "Status Byte") field(FLNK, "RADM:FEES:100:Alarm1") } record(bi, "RADM:FEES:100:Alarm1"){ field(DESC, "Alarm 1 (Trip high)") field(INP, "RADM:FEES:100:StatusRaw.B0") field(ZNAM, "OK") field(ONAM, "FAULT") field(OSV, "MAJOR") field(FLNK, "RADM:FEES:100:Alarm2") } record(bi, "RADM:FEES:100:Alarm2"){ field(DESC, "Alarm 2 (Trip low)") field(INP, "RADM:FEES:100:StatusRaw.B1") field(ZNAM, "OK") field(ONAM, "FAULT") field(OSV, "MAJOR") field(FLNK, "RADM:FEES:100:DetectorStatus") } record(bi, "RADM:FEES:100:DetectorStatus"){ field(DESC, "Detector status") field(INP, "RADM:FEES:100:StatusRaw.B2") field(ZNAM, "OK") field(ONAM, "FAIL") field(OSV, "MAJOR") } record(stringin, "RADM:FEES:100:Debug"){ field(DESC, "Raw device output") field(DTYP, "stream") field(SCAN, "I/O Intr") field(INP, "@hpi_6012.proto debug BREM_TSPORT2") field(FLNK, "RADM:FEES:100:Heartbeat") } record(calcout, "RADM:FEES:100:Heartbeat"){ field(DESC, "Heartbeat") field(CALC, "VAL>=100?0:(VAL+1)") field(DOPT, "Use OCAL") field(OCAL, "0") field(OVAL, "0") field(OUT, "RADM:FEES:100:ErrorCount PP") } record(calcout, "RADM:FEES:100:ErrorCount"){ field(DESC, "Errors since last read") field(INPA, "RADM:FEES:100:ErrorCount") field(CALC, "(VAL+2)") field(SCAN, "2 second") field(HIHI, "4") field(HHSV, "MAJOR") field(DOPT, "Use OCAL") field(OCAL, "(A>10)?1:0") field(OUT, "RADM:FEES:100:ReadStatus PP") } record(bi, "RADM:FEES:100:ReadStatus"){ field(DESC, "Read status") field(ZNAM, "OK") field(ONAM, "ERROR") field(OSV, "MAJOR") } record(bo, "RADM:FEES:100:LatchReset"){ field(DESC, "Reset latches") field(ZNAM, "Standby") field(ONAM, "Reset") } record(stringin, "RADM:FEES:100:ReadCheck"){ field(DESC, "Trigger asyn disconnect on read error") field(DTYP, "stream") field(SCAN, "1 second") field(INP, "@hpi_6012.proto readCheck BREM_TSPORT2") } # Template for software latch # Set latched PV to "Latched" when input PV goes high (alarm state). # Reset to "Not_Latched" when input PV is back to low and any reset PV goes high. # There can be multiple reset PVs: one internal and two external. # If external resets are not needed, just don't set the macro. record(calcout, "RADM:FEES:90:Alarm1LatchCalc"){ field(DESC, "Latch calc") field(ASG, "Internal") field(INPA, "RADM:FEES:90:Alarm1 CP") field(CALC, "A?1:0") field(OOPT, "Transition To Non-zero") field(OUT, "RADM:FEES:90:Alarm1Latch PP") } record(bo, "RADM:FEES:90:Alarm1Reset"){ field(DESC, "Latch reset") field(ZNAM, "Standby") field(ONAM, "Reset") field(OUT, "RADM:FEES:90:Alarm1ResetCalc PP") } record(calcout, "RADM:FEES:90:Alarm1ResetCalc"){ field(DESC, "Latch reset calc") field(ASG, "Internal") field(INPA, "RADM:FEES:90:Alarm1Reset") field(INPB, "RADM:FEES:90:LatchReset CP") field(INPC, "RADM:FEES:90:Alarm1Reset CP") field(INPD, "RADM:FEES:90:Alarm1") field(CALC, "((A || B || C) && D=0)?0:1") field(OOPT, "When Zero") field(OUT, "RADM:FEES:90:Alarm1Latch PP") field(PINI, "1") } record(bi, "RADM:FEES:90:Alarm1Latch"){ field(DESC, "Latch") field(INP, "RADM:FEES:90:Alarm1LatchCalc") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } # Template for software latch # Set latched PV to "Latched" when input PV goes high (alarm state). # Reset to "Not_Latched" when input PV is back to low and any reset PV goes high. # There can be multiple reset PVs: one internal and two external. # If external resets are not needed, just don't set the macro. record(calcout, "RADM:FEES:90:Alarm2LatchCalc"){ field(DESC, "Latch calc") field(ASG, "Internal") field(INPA, "RADM:FEES:90:Alarm2 CP") field(CALC, "A?1:0") field(OOPT, "Transition To Non-zero") field(OUT, "RADM:FEES:90:Alarm2Latch PP") } record(bo, "RADM:FEES:90:Alarm2Reset"){ field(DESC, "Latch reset") field(ZNAM, "Standby") field(ONAM, "Reset") field(OUT, "RADM:FEES:90:Alarm2ResetCalc PP") } record(calcout, "RADM:FEES:90:Alarm2ResetCalc"){ field(DESC, "Latch reset calc") field(ASG, "Internal") field(INPA, "RADM:FEES:90:Alarm2Reset") field(INPB, "RADM:FEES:90:LatchReset CP") field(INPC, "RADM:FEES:90:Alarm2Reset CP") field(INPD, "RADM:FEES:90:Alarm2") field(CALC, "((A || B || C) && D=0)?0:1") field(OOPT, "When Zero") field(OUT, "RADM:FEES:90:Alarm2Latch PP") field(PINI, "1") } record(bi, "RADM:FEES:90:Alarm2Latch"){ field(DESC, "Latch") field(INP, "RADM:FEES:90:Alarm2LatchCalc") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } # Template for software latch # Set latched PV to "Latched" when input PV goes high (alarm state). # Reset to "Not_Latched" when input PV is back to low and any reset PV goes high. # There can be multiple reset PVs: one internal and two external. # If external resets are not needed, just don't set the macro. record(calcout, "RADM:FEES:90:DetectorStatusLatchCalc"){ field(DESC, "Latch calc") field(ASG, "Internal") field(INPA, "RADM:FEES:90:DetectorStatus CP") field(CALC, "A?1:0") field(OOPT, "Transition To Non-zero") field(OUT, "RADM:FEES:90:DetectorStatusLatch PP") } record(bo, "RADM:FEES:90:DetectorStatusReset"){ field(DESC, "Latch reset") field(ZNAM, "Standby") field(ONAM, "Reset") field(OUT, "RADM:FEES:90:DetectorStatusResetCalc PP") } record(calcout, "RADM:FEES:90:DetectorStatusResetCalc"){ field(DESC, "Latch reset calc") field(ASG, "Internal") field(INPA, "RADM:FEES:90:DetectorStatusReset") field(INPB, "RADM:FEES:90:LatchReset CP") field(INPC, "RADM:FEES:90:DetectorStatusReset CP") field(INPD, "RADM:FEES:90:DetectorStatus") field(CALC, "((A || B || C) && D=0)?0:1") field(OOPT, "When Zero") field(OUT, "RADM:FEES:90:DetectorStatusLatch PP") field(PINI, "1") } record(bi, "RADM:FEES:90:DetectorStatusLatch"){ field(DESC, "Latch") field(INP, "RADM:FEES:90:DetectorStatusLatchCalc") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } # Template for software latch # Set latched PV to "Latched" when input PV goes high (alarm state). # Reset to "Not_Latched" when input PV is back to low and any reset PV goes high. # There can be multiple reset PVs: one internal and two external. # If external resets are not needed, just don't set the macro. record(calcout, "RADM:FEES:100:Alarm1LatchCalc"){ field(DESC, "Latch calc") field(ASG, "Internal") field(INPA, "RADM:FEES:100:Alarm1 CP") field(CALC, "A?1:0") field(OOPT, "Transition To Non-zero") field(OUT, "RADM:FEES:100:Alarm1Latch PP") } record(bo, "RADM:FEES:100:Alarm1Reset"){ field(DESC, "Latch reset") field(ZNAM, "Standby") field(ONAM, "Reset") field(OUT, "RADM:FEES:100:Alarm1ResetCalc PP") } record(calcout, "RADM:FEES:100:Alarm1ResetCalc"){ field(DESC, "Latch reset calc") field(ASG, "Internal") field(INPA, "RADM:FEES:100:Alarm1Reset") field(INPB, "RADM:FEES:100:LatchReset CP") field(INPC, "RADM:FEES:100:Alarm1Reset CP") field(INPD, "RADM:FEES:100:Alarm1") field(CALC, "((A || B || C) && D=0)?0:1") field(OOPT, "When Zero") field(OUT, "RADM:FEES:100:Alarm1Latch PP") field(PINI, "1") } record(bi, "RADM:FEES:100:Alarm1Latch"){ field(DESC, "Latch") field(INP, "RADM:FEES:100:Alarm1LatchCalc") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } # Template for software latch # Set latched PV to "Latched" when input PV goes high (alarm state). # Reset to "Not_Latched" when input PV is back to low and any reset PV goes high. # There can be multiple reset PVs: one internal and two external. # If external resets are not needed, just don't set the macro. record(calcout, "RADM:FEES:100:Alarm2LatchCalc"){ field(DESC, "Latch calc") field(ASG, "Internal") field(INPA, "RADM:FEES:100:Alarm2 CP") field(CALC, "A?1:0") field(OOPT, "Transition To Non-zero") field(OUT, "RADM:FEES:100:Alarm2Latch PP") } record(bo, "RADM:FEES:100:Alarm2Reset"){ field(DESC, "Latch reset") field(ZNAM, "Standby") field(ONAM, "Reset") field(OUT, "RADM:FEES:100:Alarm2ResetCalc PP") } record(calcout, "RADM:FEES:100:Alarm2ResetCalc"){ field(DESC, "Latch reset calc") field(ASG, "Internal") field(INPA, "RADM:FEES:100:Alarm2Reset") field(INPB, "RADM:FEES:100:LatchReset CP") field(INPC, "RADM:FEES:100:Alarm2Reset CP") field(INPD, "RADM:FEES:100:Alarm2") field(CALC, "((A || B || C) && D=0)?0:1") field(OOPT, "When Zero") field(OUT, "RADM:FEES:100:Alarm2Latch PP") field(PINI, "1") } record(bi, "RADM:FEES:100:Alarm2Latch"){ field(DESC, "Latch") field(INP, "RADM:FEES:100:Alarm2LatchCalc") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } # Template for software latch # Set latched PV to "Latched" when input PV goes high (alarm state). # Reset to "Not_Latched" when input PV is back to low and any reset PV goes high. # There can be multiple reset PVs: one internal and two external. # If external resets are not needed, just don't set the macro. record(calcout, "RADM:FEES:100:DetectorStatusLatchCalc"){ field(DESC, "Latch calc") field(ASG, "Internal") field(INPA, "RADM:FEES:100:DetectorStatus CP") field(CALC, "A?1:0") field(OOPT, "Transition To Non-zero") field(OUT, "RADM:FEES:100:DetectorStatusLatch PP") } record(bo, "RADM:FEES:100:DetectorStatusReset"){ field(DESC, "Latch reset") field(ZNAM, "Standby") field(ONAM, "Reset") field(OUT, "RADM:FEES:100:DetectorStatusResetCalc PP") } record(calcout, "RADM:FEES:100:DetectorStatusResetCalc"){ field(DESC, "Latch reset calc") field(ASG, "Internal") field(INPA, "RADM:FEES:100:DetectorStatusReset") field(INPB, "RADM:FEES:100:LatchReset CP") field(INPC, "RADM:FEES:100:DetectorStatusReset CP") field(INPD, "RADM:FEES:100:DetectorStatus") field(CALC, "((A || B || C) && D=0)?0:1") field(OOPT, "When Zero") field(OUT, "RADM:FEES:100:DetectorStatusLatch PP") field(PINI, "1") } record(bi, "RADM:FEES:100:DetectorStatusLatch"){ field(DESC, "Latch") field(INP, "RADM:FEES:100:DetectorStatusLatchCalc") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(asyn,"SIOC:FEES:BC01:ASYN") { field(DTYP,"asynRecordDevice") field(PORT,"BREM_TSPORT1") field(ADDR,"0") field(OMAX,"0") field(IMAX,"0") }