#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(ai, "DTC:$(loca):$(num)1:ACTUAL_VACT") {
  field(SCAN, ".1 second")
  field(DTYP, "Hytec IP-ADC-8413")
  field(INP, "@$(ai-card):0:DATA")
  field(PREC, "3")
  field(LINR, "LINEAR")
  field(EGUF, "10.0")
  field(EGUL, "-10.0")
  field(EGU, "V")
  field(HOPR, "10")
  field(LOPR, "-10")
  field(DESC, "DTC Ch1 Actual IACT")
  field(HIHI, "$(hihi)")
  field(LOLO, "$(lolo)")
  field(HHSV, "MINOR")
  field(LLSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("DTC:$(loca):$(num)1:ACTUAL_VACT",20,35,0,0,"DTC:$(loca):$(num)1:ACTUAL_VACT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(ai, "DTC:$(loca):$(num)1:HI_VACT") {
  field(SCAN, ".1 second")
  field(DTYP, "Hytec IP-ADC-8413")
  field(INP, "@$(ai-card):1:DATA")
  field(PREC, "3")
  field(LINR, "LINEAR")
  field(EGUF, "10.0")
  field(EGUL, "-10.0")
  field(EGU, "V")
  field(HOPR, "10")
  field(LOPR, "-10")
  field(DESC, "DTC Ch1 High Trip")
  field(HIHI, "$(hihi)")
  field(LOLO, "$(lolo)")
  field(HHSV, "MINOR")
  field(LLSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("DTC:$(loca):$(num)1:HI_VACT",20,35,0,0,"DTC:$(loca):$(num)1:HI_VACT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(ai, "DTC:$(loca):$(num)1:LO_VACT") {
  field(SCAN, ".1 second")
  field(DTYP, "Hytec IP-ADC-8413")
  field(INP, "@$(ai-card):2:DATA")
  field(PREC, "3")
  field(LINR, "LINEAR")
  field(EGUF, "10.0")
  field(EGUL, "-10.0")
  field(EGU, "V")
  field(HOPR, "10")
  field(LOPR, "-10")
  field(DESC, "DTC Ch1 Low Trip")
  field(HIHI, "$(hihi)")
  field(LOLO, "$(lolo)")
  field(HHSV, "MINOR")
  field(LLSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("DTC:$(loca):$(num)1:LO_VACT",20,35,0,0,"DTC:$(loca):$(num)1:LO_VACT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(ai, "DTC:$(loca):$(num)2:ACTUAL_VACT") {
  field(SCAN, ".1 second")
  field(DTYP, "Hytec IP-ADC-8413")
  field(INP, "@$(ai-card):3:DATA")
  field(PREC, "3")
  field(LINR, "LINEAR")
  field(EGUF, "10.0")
  field(EGUL, "-10.0")
  field(EGU, "V")
  field(HOPR, "10")
  field(LOPR, "-10")
  field(DESC, "DTC Ch2 Actual IACT")
  field(HIHI, "$(hihi)")
  field(LOLO, "$(lolo)")
  field(HHSV, "MINOR")
  field(LLSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("DTC:$(loca):$(num)2:ACTUAL_VACT",20,35,0,0,"DTC:$(loca):$(num)2:ACTUAL_VACT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(ai, "DTC:$(loca):$(num)2:HI_VACT") {
  field(SCAN, ".1 second")
  field(DTYP, "Hytec IP-ADC-8413")
  field(INP, "@$(ai-card):4:DATA")
  field(PREC, "3")
  field(LINR, "LINEAR")
  field(EGUF, "10.0")
  field(EGUL, "-10.0")
  field(EGU, "V")
  field(HOPR, "10")
  field(LOPR, "-10")
  field(DESC, "DTC Ch2 High Trip")
  field(HIHI, "$(hihi)")
  field(LOLO, "$(lolo)")
  field(HHSV, "MINOR")
  field(LLSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("DTC:$(loca):$(num)2:HI_VACT",20,35,0,0,"DTC:$(loca):$(num)2:HI_VACT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(ai, "DTC:$(loca):$(num)2:LO_VACT") {
  field(SCAN, ".1 second")
  field(DTYP, "Hytec IP-ADC-8413")
  field(INP, "@$(ai-card):5:DATA")
  field(PREC, "3")
  field(LINR, "LINEAR")
  field(EGUF, "10.0")
  field(EGUL, "-10.0")
  field(EGU, "V")
  field(HOPR, "10")
  field(LOPR, "-10")
  field(DESC, "DTC Ch2 Low Trip")
  field(HIHI, "$(hihi)")
  field(LOLO, "$(lolo)")
  field(HHSV, "MINOR")
  field(LLSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("DTC:$(loca):$(num)2:LO_VACT",20,35,0,0,"DTC:$(loca):$(num)2:LO_VACT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(ai, "DTC:$(loca):$(num)3:ACTUAL_VACT") {
  field(SCAN, ".1 second")
  field(DTYP, "Hytec IP-ADC-8413")
  field(INP, "@$(ai-card):6:DATA")
  field(PREC, "3")
  field(LINR, "LINEAR")
  field(EGUF, "10.0")
  field(EGUL, "-10.0")
  field(EGU, "V")
  field(HOPR, "10")
  field(LOPR, "-10")
  field(DESC, "DTC Ch3 Actual IACT")
  field(HIHI, "$(hihi)")
  field(LOLO, "$(lolo)")
  field(HHSV, "MINOR")
  field(LLSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("DTC:$(loca):$(num)3:ACTUAL_VACT",20,35,0,0,"DTC:$(loca):$(num)3:ACTUAL_VACT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(ai, "DTC:$(loca):$(num)3:HI_VACT") {
  field(SCAN, ".1 second")
  field(DTYP, "Hytec IP-ADC-8413")
  field(INP, "@$(ai-card):7:DATA")
  field(PREC, "3")
  field(LINR, "LINEAR")
  field(EGUF, "10.0")
  field(EGUL, "-10.0")
  field(EGU, "V")
  field(HOPR, "10")
  field(LOPR, "-10")
  field(DESC, "DTC Ch3 High Trip")
  field(HIHI, "$(hihi)")
  field(LOLO, "$(lolo)")
  field(HHSV, "MINOR")
  field(LLSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("DTC:$(loca):$(num)3:HI_VACT",20,35,0,0,"DTC:$(loca):$(num)3:HI_VACT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(ai, "DTC:$(loca):$(num)3:LO_VACT") {
  field(SCAN, ".1 second")
  field(DTYP, "Hytec IP-ADC-8413")
  field(INP, "@$(ai-card):8:DATA")
  field(PREC, "3")
  field(LINR, "LINEAR")
  field(EGUF, "10.0")
  field(EGUL, "-10.0")
  field(EGU, "V")
  field(HOPR, "10")
  field(LOPR, "-10")
  field(DESC, "DTC Ch3 Low Trip")
  field(HIHI, "$(hihi)")
  field(LOLO, "$(lolo)")
  field(HHSV, "MINOR")
  field(LLSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("DTC:$(loca):$(num)3:LO_VACT",20,35,0,0,"DTC:$(loca):$(num)3:LO_VACT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(ai, "DTC:$(loca):$(num)4:ACTUAL_VACT") {
  field(SCAN, ".1 second")
  field(DTYP, "Hytec IP-ADC-8413")
  field(INP, "@$(ai-card):9:DATA")
  field(PREC, "3")
  field(LINR, "LINEAR")
  field(EGUF, "10.0")
  field(EGUL, "-10.0")
  field(EGU, "V")
  field(HOPR, "10")
  field(LOPR, "-10")
  field(DESC, "DTC Ch4 Actual IACT")
  field(HIHI, "$(hihi)")
  field(LOLO, "$(lolo)")
  field(HHSV, "MINOR")
  field(LLSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("DTC:$(loca):$(num)4:ACTUAL_VACT",20,35,0,0,"DTC:$(loca):$(num)4:ACTUAL_VACT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(ai, "DTC:$(loca):$(num)4:HI_VACT") {
  field(SCAN, ".1 second")
  field(DTYP, "Hytec IP-ADC-8413")
  field(INP, "@$(ai-card):10:DATA")
  field(PREC, "3")
  field(LINR, "LINEAR")
  field(EGUF, "10.0")
  field(EGUL, "-10.0")
  field(EGU, "V")
  field(HOPR, "10")
  field(LOPR, "-10")
  field(DESC, "DTC Ch4 High Trip")
  field(HIHI, "$(hihi)")
  field(LOLO, "$(lolo)")
  field(HHSV, "MINOR")
  field(LLSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("DTC:$(loca):$(num)4:HI_VACT",20,35,0,0,"DTC:$(loca):$(num)4:HI_VACT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(ai, "DTC:$(loca):$(num)4:LO_VACT") {
  field(SCAN, ".1 second")
  field(DTYP, "Hytec IP-ADC-8413")
  field(INP, "@$(ai-card):11:DATA")
  field(PREC, "3")
  field(LINR, "LINEAR")
  field(EGUF, "10.0")
  field(EGUL, "-10.0")
  field(EGU, "V")
  field(HOPR, "10")
  field(LOPR, "-10")
  field(DESC, "DTC Ch4 Low Trip")
  field(HIHI, "$(hihi)")
  field(LOLO, "$(lolo)")
  field(HHSV, "MINOR")
  field(LLSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("DTC:$(loca):$(num)4:LO_VACT",20,35,0,0,"DTC:$(loca):$(num)4:LO_VACT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "DTC:$(loca):$(num)1:BCSMODE") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@$(bi-card) P$(bi-port) B0")
  field(ZNAM, "BYPASS")
  field(ONAM, "ACTIVE")
  field(ZSV,  "MINOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "DTC Ch1 Bypass mode")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("DTC:$(loca):$(num)1:BCSMODE",2160,2153,0,1,"DTC:$(loca):$(num)1:BCSMODE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "DTC:$(loca):$(num)1:BCSSTATE") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@$(bi-card) P$(bi-port) B1")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "DTC Ch1 fault state")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("DTC:$(loca):$(num)1:BCSSTATE",2160,2153,0,1,"DTC:$(loca):$(num)1:BCSSTATE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "DTC:$(loca):$(num)2:BCSMODE") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@$(bi-card) P$(bi-port) B2")
  field(ZNAM, "BYPASS")
  field(ONAM, "ACTIVE")
  field(ZSV,  "MINOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "DTC Ch2 Bypass mode")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("DTC:$(loca):$(num)2:BCSMODE",2160,2153,0,1,"DTC:$(loca):$(num)2:BCSMODE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "DTC:$(loca):$(num)2:BCSSTATE") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@$(bi-card) P$(bi-port) B3")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "DTC Ch2 fault state")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("DTC:$(loca):$(num)2:BCSSTATE",2160,2153,0,1,"DTC:$(loca):$(num)2:BCSSTATE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "DTC:$(loca):$(num)3:BCSMODE") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@$(bi-card) P$(bi-port) B4")
  field(ZNAM, "BYPASS")
  field(ONAM, "ACTIVE")
  field(ZSV,  "MINOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "DTC Ch3 Bypass mode")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("DTC:$(loca):$(num)3:BCSMODE",2160,2153,0,1,"DTC:$(loca):$(num)3:BCSMODE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "DTC:$(loca):$(num)3:BCSSTATE") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@$(bi-card) P$(bi-port) B5")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "DTC Ch3 fault state")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("DTC:$(loca):$(num)3:BCSSTATE",2160,2153,0,1,"DTC:$(loca):$(num)3:BCSSTATE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "DTC:$(loca):$(num)4:BCSMODE") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@$(bi-card) P$(bi-port) B6")
  field(ZNAM, "BYPASS")
  field(ONAM, "ACTIVE")
  field(ZSV,  "MINOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "DTC Ch4 Bypass mode")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("DTC:$(loca):$(num)4:BCSMODE",2160,2153,0,1,"DTC:$(loca):$(num)4:BCSMODE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "DTC:$(loca):$(num)4:BCSSTATE") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@$(bi-card) P$(bi-port) B7")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "DTC Ch4 fault state")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("DTC:$(loca):$(num)4:BCSSTATE",2160,2153,0,1,"DTC:$(loca):$(num)4:BCSSTATE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND


record(bo, "DTC:$(loca):$(num):RESET") {
  field(DESC, "$(bld) DTC$(num) reset")
  field(SCAN, "Passive")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(FLNK, "DTC:$(loca):$(num):RESETH")
  field(OUT,  "DTC:$(loca):$(num):RESETH")
  field(ZNAM, "NOT_RESET")
  field(ONAM, "RESET")
  field(ASG,  "DEFAULT")
  field(VAL,  "")
}

record(bo, "DTC:$(loca):$(num):RESETH") {
  field(DESC, "$(bld) DTC$(num) reset")
  field(SCAN, "Passive")
  field(DTYP, "XYCOM-2445")
  field(OUT, "@$(bo-card) P$(bo-port) B$(bo-bit)")
  field(ZNAM, "NOT_RESET")
  field(ONAM, "RESET")
  field(ASG,  "DEFAULT")
  field(HIGH, "0.25")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("DTC:$(loca):$(num):RESET",2140,2165,0,1,"DTC:$(loca):$(num):RESET")
#! Field("DTC:$(loca):$(num):RESET.FLNK",16777215,1,"DTC:$(loca):$(num):RESET.FLNK")
#! Link("DTC:$(loca):$(num):RESET.FLNK","DTC:$(loca):$(num):RESETH")
#! Field("DTC:$(loca):$(num):RESET.OUT",16777215,1,"DTC:$(loca):$(num):RESET.OUT")
#! Link("DTC:$(loca):$(num):RESET.OUT","DTC:$(loca):$(num):RESETH.VAL")
#! Record("DTC:$(loca):$(num):RESETH",2460,2232,0,0,"DTC:$(loca):$(num):RESETH")
#! Field("DTC:$(loca):$(num):RESETH.VAL",16777215,0,"DTC:$(loca):$(num):RESETH.VAL")