# INP fields for ai records are defined as "@attr multicast_group" # where 'attr' is defined in BLDGdetAttributes # and 'multi_cast_group' is the last number of the four fields in a MC address # typedef enum { # GDET_PULSEID, # GDET_STATUS, # GDET_ENRC_11, # GDET_ENRC_12, # GDET_ENRC_21, # GDET_ENRC_22, # GDET_ENRC_63, # GDET_ENRC_64, #} BLDGdetAttributes; ##### # typedef enum { # /*XRT */ # GDET_FEEGasDetEnergy, /* 0: "239.255.24.2" */ # } BLDGdetMCGroup; ##### record(ai, "$(DEVICE,undefined):GDET_FEEGasDetEnergy_PULSEID") { field(DESC, "Gdet PULSEID") field(SCAN, "I/O Intr") field(DTYP, "BLD_RCVR") field(INP, "@0 2") field(PREC, "5") field(TSE, "-1") field(EGU, "fid") field(FLNK, "$(DEVICE,undefined):EFGDET2_PULSEID") field(PRIO, "HIGH") } record(ai, "$(DEVICE,undefined):GDET_FEEGasDetEnergy_STATUS") { field(DESC, "Gdet STATUS") field(SCAN, "I/O Intr") field(DTYP, "BLD_RCVR") field(INP, "@1 2") field(PREC, "5") field(TSE, "-1") field(EGU, "Raw") field(FLNK, "$(DEVICE,undefined):EFGDET2_STATUS") field(PRIO, "HIGH") } record(ai, "$(DEVICE,undefined):GDET_FEEGasDetEnergy_ENRC_11") { field(DESC, "Gdet ENRC_11") field(SCAN, "I/O Intr") field(DTYP, "BLD_RCVR") field(INP, "@2 2") field(PREC, "5") field(TSE, "-1") field(EGU, "mJ") field(FLNK, "$(DEVICE,undefined):EFGDET2_ENRC_11") field(PRIO, "HIGH") } record(ai, "$(DEVICE,undefined):GDET_FEEGasDetEnergy_ENRC_12") { field(DESC, "Gdet ENRC_12") field(SCAN, "I/O Intr") field(DTYP, "BLD_RCVR") field(INP, "@3 2") field(PREC, "5") field(TSE, "-1") field(EGU, "mJ") field(FLNK, "$(DEVICE,undefined):EFGDET2_ENRC_12") field(PRIO, "HIGH") } record(ai, "$(DEVICE,undefined):GDET_FEEGasDetEnergy_ENRC_21") { field(DESC, "Gdet ENRC_21") field(SCAN, "I/O Intr") field(DTYP, "BLD_RCVR") field(INP, "@4 2") field(PREC, "5") field(TSE, "-1") field(EGU, "mJ") field(FLNK, "$(DEVICE,undefined):EFGDET2_ENRC_21") field(PRIO, "HIGH") } record(ai, "$(DEVICE,undefined):GDET_FEEGasDetEnergy_ENRC_22") { field(DESC, "Gdet ENRC_22") field(SCAN, "I/O Intr") field(DTYP, "BLD_RCVR") field(INP, "@5 2") field(PREC, "5") field(TSE, "-1") field(EGU, "mJ") field(FLNK, "$(DEVICE,undefined):EFGDET2_ENRC_22") field(PRIO, "HIGH") } record(ai, "$(DEVICE,undefined):GDET_FEEGasDetEnergy_ENRC_63") { field(DESC, "Gdet ENRC_63") field(SCAN, "I/O Intr") field(DTYP, "BLD_RCVR") field(INP, "@6 2") field(PREC, "5") field(TSE, "-1") field(EGU, "mJ") field(FLNK, "$(DEVICE,undefined):EFGDET2_ENRC_63") field(PRIO, "HIGH") } record(ai, "$(DEVICE,undefined):GDET_FEEGasDetEnergy_ENRC_64") { field(DESC, "Gdet ENRC_64") field(SCAN, "I/O Intr") field(DTYP, "BLD_RCVR") field(INP, "@7 2") field(PREC, "5") field(TSE, "-1") field(EGU, "mJ") field(FLNK, "$(DEVICE,undefined):EFGDET2_ENRC_64") field(PRIO, "HIGH") } record(longin, "$(DEVICE,undefined):GDET_FEEGasDetEnergy_LATE") { field(DESC, "GDET BLD Late Packet Cnt") field(EGU, "Count") field(SCAN, "5") field(DTYP, "BusAddress") field(INP, "#C0S2@FEEGasDetEnergy_late_f,m32") } # just write .PROC record(longout, "$(DEVICE,undefined):GDET_FEEGasDetEnergy_LATERST") { field(DESC, "Rst.GDET BLD Late Packet Cnt") field(SCAN, "Passive") field(DTYP, "BusAddress") field(OUT, "#C0S2@FEEGasDetEnergy_late_f,m32") field(VAL, "0") field(PINI, "YES") } record(longin, "$(DEVICE,undefined):GDET_FEEGasDetEnergy_MISS") { field(DESC, "GDET BLD missed Pkt cnt") field(EGU, "Count") field(SCAN, "5") field(DTYP, "BusAddress") field(INP, "#C0S2@FEEGasDetEnergy_miss_f,m32") } # just write .PROC record(longout, "$(DEVICE,undefined):GDET_FEEGasDetEnergy_MISSRST") { field(DESC, "Rst.GDET BLD missed Pkt cnt") field(SCAN, "Passive") field(DTYP, "BusAddress") field(OUT, "#C0S2@FEEGasDetEnergy_miss_f,m32") field(VAL, "0") field(PINI, "YES") } record(longin, "$(DEVICE,undefined):GDET_FEEGasDetEnergy_MAX") { field(DESC, "Max. GDET BLD Latency") field(EGU, "uS") field(SCAN, "5") field(DTYP, "BusAddress") field(INP, "#C0S2@FEEGasDetEnergy_max_f,m32") } # just write .PROC record(longout, "$(DEVICE,undefined):GDET_FEEGasDetEnergy_MAXRST") { field(DESC, "Rst. Max. GDET BLD Latency") field(SCAN, "Passive") field(DTYP, "BusAddress") field(OUT, "#C0S2@FEEGasDetEnergy_max_f,m32") field(VAL, "0") field(PINI, "YES") } record(longin, "$(DEVICE,undefined):GDET_FEEGasDetEnergy_MIN") { field(DESC, "Min. GDET BLD Latency") field(EGU, "uS") field(SCAN, "5") field(DTYP, "BusAddress") field(INP, "#C0S2@FEEGasDetEnergy_min_f,m32") } # just write .PROC record(longout, "$(DEVICE,undefined):GDET_FEEGasDetEnergy_MINRST") { field(DESC, "Rst. Min. GDET BLD Latency") field(SCAN, "Passive") field(DTYP, "BusAddress") field(OUT, "#C0S2@FEEGasDetEnergy_min_f,m32") field(VAL, "0") field(PINI, "YES") } record(longin, "$(DEVICE,undefined):GDET_FEEGasDetEnergy_AVG") { field(DESC, "Num. GDET BLD Lat above avg") field(EGU, "uS") field(SCAN, "5") field(DTYP, "BusAddress") field(INP, "#C0S2@FEEGasDetEnergy_avg_f,m32") } # just write .PROC record(longout, "$(DEVICE,undefined):GDET_FEEGasDetEnergy_AVGRST") { field(DESC, "Rst. Avg GDET BLD Latency") field(SCAN, "Passive") field(DTYP, "BusAddress") field(OUT, "#C0S2@FEEGasDetEnergy_avg_f,m32") field(VAL, "0") field(PINI, "YES") } record(longin, "$(DEVICE,undefined):GDET_FEEGasDetEnergy_DUP") { field(DESC, "GDET BLD Duplicate Packet Cnt") field(EGU, "Count") field(SCAN, "5") field(DTYP, "BusAddress") field(INP, "#C0S2@FEEGasDetEnergy_dup_f,m32") } # just write .PROC record(longout, "$(DEVICE,undefined):GDET_FEEGasDetEnergy_DUPRST") { field(DESC, "Rst.GDET BLD Duplicate Packet Cnt") field(SCAN, "Passive") field(DTYP, "BusAddress") field(OUT, "#C0S2@FEEGasDetEnergy_dup_f,m32") field(VAL, "0") field(PINI, "YES") }