## PAD RTEMS startup script for RF Gun Forward/Reflected PAD in RF Hut

chdir("../..")
ld("bin/RTEMS-uC5282/pad-gen.obj")  

## Set app-specific environment variable for the PAD
epicsEnvSet ("EPICS_CA_MAX_ARRAY_BYTES", "1000000")

## /data now mapped by pre...
nfsMountsShow()

lsmod()

## Register all support components
dbLoadDatabase("dbd/pad.dbd")
pad_registerRecordDeviceDriver(pdbbase) 

## Load record instances
dbLoadTemplate("db/padGN2.gen102_template")
dbLoadRecords("db/iocAdmin.db","IOC=EIOC:IN20:RD04")

## Set to 2 so that we see errors
devLongoutPadFlag=2
devLonginPadFlag=2
devWaveformPadFlag=2
devMbboPadFlag=2
devBoPadFlag=2
drvPadFlag=2
drvPadCfgFlag=2
drvPadScalFlag=2
drvPadIntrFlag=2

## For this app, channels 2 and 3 aren't used, so numQ is zero,
## so set drvPadGenFlag=0 to avoid all the msgs that "numQ is zero"
drvPadGenFlag=0

# New: pre maps /data to /u1/lcls/epics/ioc/data/<hostname>
dbRestore("/data/EIOC-IN20-RD04.sav")

iocInit()

# force scalar waveforms to read (once)
dbpf("GUN:IN20:1:GN2_0_SCL_WF.PROC","1")
dbpf("GUN:IN20:1:GN2_1_SCL_WF.PROC","1")
dbpf("GUN:IN20:1:GN2_2_SCL_WF.PROC","1")
dbpf("GUN:IN20:1:GN2_3_SCL_WF.PROC","1")

dbpf("GUN:IN20:1:GN2_4_OFST","0")
dbpf("GUN:IN20:1:GN2_5_OFST","0")
dbpf("GUN:IN20:1:GN2_6_OFST","0")
dbpf("GUN:IN20:1:GN2_7_OFST","0")

dbpf("GUN:IN20:1:GN2_4_SIZE","65536")
dbpf("GUN:IN20:1:GN2_5_SIZE","65536")
dbpf("GUN:IN20:1:GN2_6_SIZE","65536")
dbpf("GUN:IN20:1:GN2_7_SIZE","65536")

padSetDataFileStem("dayle") 	# The stem to start all data files with
                                # Format is "<stem><secPastEpoch>.dat"

# change directory to local mountpoint so that files don't need path to dir in their name
cd("/data") # for lcls-dev

#rtems_gdb_start(0,0)

dbpf("GUN:IN20:1:GN2_0_OFST.PROC","1")
dbpf("GUN:IN20:1:GN2_1_OFST.PROC","1")
dbpf("GUN:IN20:1:GN2_2_OFST.PROC","1")
dbpf("GUN:IN20:1:GN2_3_OFST.PROC","1")
dbpf("GUN:IN20:1:GN2_0_SIZE.PROC","1")
dbpf("GUN:IN20:1:GN2_1_SIZE.PROC","1")
dbpf("GUN:IN20:1:GN2_2_SIZE.PROC","1")
dbpf("GUN:IN20:1:GN2_3_SIZE.PROC","1")

## Start any sequence programs. Note: RTEMS Cexp syntax
# Skip state machine for nonlin test
seq(&sncpad,"PRIM=GUN,LOCA=IN20,UNIT=1,PAD=GN2") 
seq(&trgDetector, "PRIM=GUN,LOCA=IN20,UNIT=1,PAD=GN2")

# for non-lin test
#padSetOperationMode(1)
#dbpf("GUN:IN20:1:GN2_D_CALIB","1")
#padDisableIntr()
#padNonlin(1000)