record(longin, "$(dev):$(type)CSR") { field(DESC, "Control/Status Register") field(DTYP, "BusAddress") field(INP, "#C0S0@PAC+0x2000,be16") field(PINI, "YES") field(FLNK, "$(dev):$(type)FWVersion") } record(calc, "$(dev):$(type)FWVersion") { field(DESC, "Firmware Version") field(INPA, "$(dev):$(type)CSR") field(CALC, "(A>>8)&255") } record(bi, "$(dev):$(type)ClockStatus") { field(DESC, "Clock Status") field(DTYP, "BusAddress") field(INP, "#C0S0@PAC+0x2000,be16") field(MASK, "0x10") field(ZNAM, "Present") field(ONAM, "Missing") field(OSV, "MAJOR") field(SCAN, "1 second") field(PINI, "YES") } record(bo, "$(dev):$(type)ClockStatusReset") { field(DESC, "Clock Fault Reset") field(DTYP, "BusAddress") field(OUT, "#C0S0@PAC+0x2000,be16") field(DOL, "1") field(MASK, "0x10") field(ZNAM, "NoReset") field(ONAM, "Reset") field(HIGH, "0.1") field(PINI, "YES") } record(bi, "$(dev):$(type)TrigStatus") { field(DESC, "External Trigger Status") field(DTYP, "BusAddress") field(INP, "#C0S0@PAC+0x2000,be16") field(MASK, "0x08") field(ZNAM, "Present") field(ONAM, "Missing") field(OSV, "MAJOR") field(SCAN, "1 second") field(PINI, "YES") } record(bo, "$(dev):$(type)TrigStatusReset") { field(DESC, "External Trigger Fault Reset") field(DTYP, "BusAddress") field(OUT, "#C0S0@PAC+0x2000,be16") field(DOL, "1") field(MASK, "0x08") field(ZNAM, "NoReset") field(ONAM, "Reset") field(HIGH, "0.1") field(PINI, "YES") } record(mbbo, "$(dev):$(type)TrigModeSetpt") { field(DESC, "Trigger Mode") field(DTYP, "BusAddress") field(OUT, "#C0S0@PAC+0x2000,be16") field(DOL, "0") field(MASK, "0x03") field(NOBT, "2") field(ZRVL, "0") field(ZRST, "External") field(ONVL, "1") field(ONST, "Internal") field(TWVL, "2") field(TWST, "Software") field(PINI, "YES") info(autosaveFields_pass0, "VAL") } record(longout, "$(dev):$(type)SoftTrigger") { field(DESC, "Software Trigger") field(DTYP, "BusAddress") field(OUT, "#C0S0@PAC+0x2020,be16") field(DOL, "1") field(LOPR, "0") field(HOPR, "65535") field(DRVL, "0") field(DRVH, "65535") field(MDEL, "-1") } record(longout, "$(dev):$(type)IntTrigSetpt") { field(DESC, "Internal Trigger Rate") field(DTYP, "BusAddress") field(OUT, "#C0S0@PAC+0x200c,be16") field(LOPR, "0") field(HOPR, "65535") field(DRVL, "0") field(DRVH, "65535") field(EGU, "Ticks") field(MDEL, "-1") field(PINI, "YES") info(autosaveFields_pass0, "VAL") } record(bo, "$(dev):$(type)ClockSetpt") { field(DESC, "Clock Source") field(DTYP, "BusAddress") field(OUT, "#C0S0@PAC+0x200e,be16") field(DOL, "0") field(ZNAM, "External") field(ONAM, "Internal") field(MASK, "1") field(PINI, "YES") field(FLNK, "$(dev):$(type)ClockRate") info(autosaveFields_pass0, "VAL") } record(sel, "$(dev):$(type)ClockRate") { field(DESC, "Clock Rate") field(INPA, "$(rate)") field(INPB, "119") field(HOPR, "120") field(EGU, "MHz") field(PREC, "1") field(SELM, "Specified") field(NVL, "$(dev):$(type)ClockSetpt MS") field(FLNK, "$(dev):$(type)TimeDelta") } record(calc, "$(dev):$(type)TimeDelta") { field(DESC, "Delta Time for Clock") field(EGU, "usec") field(PREC, "2") field(INPA, "$(dev):$(type)ClockRate") field(CALC, "1/A") field(FLNK, "$(dev):$(type)TimeUpd") } record(sub, "$(dev):$(type)TimeUpd") { field(DESC, "Update Plot Time Array") field(ASG, "Internal") field(BRSV, "INVALID") field(SNAM, "subpacTime") field(INPA, "$(dev):$(type)TimeDelta") field(INPL, "$(dev):$(type)Time PP") field(EGU, "usec") field(PREC, "2") } record(waveform, "$(dev):$(type)Time") { field(DESC, "Plot Time Array") field(NELM, "2048") field(FTVL, "FLOAT") field(EGU, "usec") field(PREC, "2") field(HOPR, "20") } record(ao, "$(dev):$(type)PhaseSetpt") { field(DESC, "Phase Shift") field(OUT, "$(dev):$(type)IQUpd.A PP") field(LOPR, "0") field(HOPR, "360") field(DRVL, "0") field(DRVH, "360") field(EGU, "deg") field(MDEL, "-1") field(PREC, "2") field(PINI, "YES") info(autosaveFields_pass0, "VAL") } record(ao, "$(dev):$(type)CycleNum") { field(DESC, "Number of Cycles") field(OUT, "$(dev):$(type)IQUpd.B PP") field(LOPR, "0") field(HOPR, "2048") field(DRVL, "0") field(DRVH, "2048") field(MDEL, "-1") field(PREC, "2") field(PINI, "YES") info(autosaveFields_pass0, "VAL") } record(sub, "$(dev):$(type)IQUpd") { field(DESC, "Update I and Q Arrays") field(ASG, "Internal") field(BRSV, "INVALID") field(SNAM, "subpacIQ") field(INPC, "32767") field(INPK, "$(dev):$(type)ISetpt") field(INPL, "$(dev):$(type)QSetpt") field(FLNK, "$(dev):$(type)IQUpdFan") field(DISV, "0") } record(fanout, "$(dev):$(type)IQUpdFan") { field(DESC, "Process I and Q Arrays") field(ASG, "Internal") field(LNK1, "$(dev):$(type)ISetpt") field(LNK2, "$(dev):$(type)QSetpt") field(FLNK, "$(dev):$(type)IQTOD") } record(stringin, "$(dev):$(type)IQTOD") { field(DESC, "Time and date of last update") field(DTYP, "Soft Timestamp") field(INP, "@%m/%d/%Y %H:%M:%S.%01f") } record(fanout, "$(dev):$(type)IQInit") { field(DESC, "Initialize I and Q Arrays") field(ASG, "Internal") field(LNK1, "$(dev):$(type)PhaseSetpt") field(LNK2, "$(dev):$(type)CycleNum") field(FLNK, "$(dev):$(type)IQUpdGo") field(PINI, "YES") } record(bo, "$(dev):$(type)IQUpdGo") { field(DESC, "Process I and Q Arrays") field(ASG, "Internal") field(DOL, "1") field(OUT, "$(dev):$(type)IQUpd.DISV PP") }