record(motor,"B122-TUNER:Cell1Motor") { field(DESC,"B00-RF Cell 1") field(OUT, "@asyn(M0,0)") field(DTYP,"asynMotor") field(DIR, "Pos") field(VMAX,"12.7") field(VELO,"6.35") field(VBAS,"1.27") field(ACCL,"0.5") field(BDST,"0") field(BVEL,"1.27") field(BACC,"0.1") field(MRES,"9.921875e-05") field(PREC,"4") field(EGU, "mm") field(DHLM,"39") field(DLLM,"-25") field(INIT,"") field(RLV, "0") field(TWV, "1") field(FOFF,"Frozen") field(FRAC,"1") field(JVEL,"6.35") field(JAR, "12.7") field(ERES,"1") field(RRES,"0.001") field(RDBD,"1") field(RTRY,"10") field(UEIP,"No") field(URIP,"No") field(DLY, "0") field(OMSL,"supervisory") field(CNEN,"Enable") field(SET, "Use") field(OFF, "0") field(PCOF,"0") field(ICOF,"0") field(DCOF,"0") field(RDBL,"") field(PREM,"") field(POST,"") field(FLNK,"") } record(motor,"B122-TUNER:Cell5Motor") { field(DESC,"B00-RF Cell 5") field(OUT, "@asyn(M1,0)") field(DTYP,"asynMotor") field(DIR, "Pos") field(VMAX,"12.7") field(VELO,"6.35") field(VBAS,"1.27") field(ACCL,"0.5") field(BDST,"0") field(BVEL,"1.27") field(BACC,"0.1") field(MRES,"9.921875e-05") field(PREC,"4") field(EGU, "mm") field(DHLM,"16") field(DLLM,"-43") field(INIT,"") field(RLV, "0") field(TWV, "1") field(FOFF,"Frozen") field(FRAC,"1") field(JVEL,"6.35") field(JAR, "12.7") field(ERES,"1") field(RRES,"0.001") field(RDBD,"1") field(RTRY,"10") field(UEIP,"No") field(URIP,"No") field(DLY, "0") field(OMSL,"supervisory") field(CNEN,"Enable") field(SET, "Use") field(OFF, "0") field(PCOF,"0") field(ICOF,"0") field(DCOF,"0") field(RDBL,"") field(PREM,"") field(POST,"") field(FLNK,"") } #=============================================================== # # Abs: Booster RF Tuner Tuner Potentiometer database # # File:tuner_pot.template # # Desc: Booster RF has two tuner motors - # one for moving tuner in Cell1 of the Booster RF cavity # and one for moving the tuner in Cell5 of the same cavity # The motors are controlled via two EtherCAT Beckhoff modules EL7041. # The motor position is readback via potentiometers via EtherCAT Beckhoff module EL3702 AI module. # This database reads the raw counts from the potentiometer via an ADC and converts it first to Volts and then to mm. # The full-scale of the ADC is 0-65535 an corresponds to a range of 20V. # ai record: # ADC Raw counts range of -32767 to +31767 correspond to -10V to +10V # with 0V producing 0 counts at the center of the motor stage. The count->V map is linear. # calc record: # The Volts are converted to mm based on the actual calibration that was done # where 1 Volt potentiometer change resulted due to approximately 5.254 mm motor displacement. # Scale and Offset for the linear conversion can be changed but they will be hard-coded # in the soft-ioctuner-boo-rf.substitutions file. # # Facility: SPEAR3 Booster RF Tuner Controls # # Auth: 28-Oct-2016, S. Condamoor (SCONDAM) # Rev: dd-mmm-yyyy, First Lastname (USERNAME) #-------------------------------------------------------------- # % macro, P, record name prefix # % macro, R, record name # % macro, PORT, asyn port for device # % macro, CH, ADC channel (1 or 2) # % macro, EGUF, Engineering Units Full # % macro, EGUL, Engineering Units Low record(ai, "B122-TUNER:Cell1PosnVolt") { field("DESC", "B00-RF Cell1 posn in V") field("DTYP", "asynInt32") field("INP", "@asyn(AIN0)Ch1Sample.Ch1Value") field("SCAN", "I/O Intr") field("LINR", "LINEAR") field("EGUF", "10") field("EGUL", "-10") field("EGU", "V") field("FLNK", "B122-TUNER:Cell1Posn") info(autosaveFields, "EGUF EGUL") } # # Convert to a 32-bit integer and convert to floating point. # A and B and Alarm Limits will be saved and restored by RDB upon ioc reboot. # # % macro, Offset, Offset for V->mm linear conversion # % macro, Scale, Slope for V->mm linear conversion # % macro, high, HIGH Alarm Limit # % macro, hihi, HIHI Alarm Limit # % macro, high, HIGH Alarm Limit # % macro, lolo, LOLO Alarm Limit # % macro, low, LOW Alarm Limit record(calc,"B122-TUNER:Cell1Posn") { field(DESC, "B00-RF Cell1 posn in mm") # field(ASG, "$(security,undefined)ADMIN") field(PREC, "2") field(EGU, "mm") field(PINI, "YES") field(HIHI, "38.0") field(HIGH, "36.0") field(LOLO, "-24.0") field(LOW, "-22.0") # field(HYST, "0.1") field(HHSV, "MAJOR") field(HSV, "MINOR") field(LLSV, "MAJOR") field(LSV, "MINOR") field(INPA, "B122-TUNER:Cell1PosnVolt MS") field(B, "0.0") field(C, "5.26936") field(CALC, "B+(C*A)") field("FLNK", "B122-TUNER:Cell1PosnCalib") info(autosaveFields, "LOW LOLO HIGH HIHI B C") } # # Calculate polynomial: x is raw counts from adc and a-h are polynomial coefficients # f = a*x^0 + b*x^1 + c*x^2 + d*x^3 + e*x^4 + f*x^5 + g*x^6 + h*x^7 # record(calc, "B122-TUNER:Cell1PosnCalib") { field(DESC, "B00-RF Cell1 posn in mm") # field(ASG, "$(security,undefined)ADMIN") field(SCAN, "Passive") field(A, "0") field(B, "0") field(C, "0") field(D, "0") field(E, "0") field(F, "0") field(G, "0") field(H, "0") field(INPL, "B122-TUNER:Cell1PosnVolt.RVAL") field(PREC, "2") field(EGU, "mm") field(PINI, "YES") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(CALC, "A*L^0+B*L^1+C*L^2+D*L^3+E*L^4+F*L^5+G*L^6+H*L^7") info(autosaveFields, "LOW LOLO HIGH HIHI A B C D E F G H") } #=============================================================== # # Abs: Booster RF Tuner Tuner Potentiometer database # # File:tuner_pot.template # # Desc: Booster RF has two tuner motors - # one for moving tuner in Cell1 of the Booster RF cavity # and one for moving the tuner in Cell5 of the same cavity # The motors are controlled via two EtherCAT Beckhoff modules EL7041. # The motor position is readback via potentiometers via EtherCAT Beckhoff module EL3702 AI module. # This database reads the raw counts from the potentiometer via an ADC and converts it first to Volts and then to mm. # The full-scale of the ADC is 0-65535 an corresponds to a range of 20V. # ai record: # ADC Raw counts range of -32767 to +31767 correspond to -10V to +10V # with 0V producing 0 counts at the center of the motor stage. The count->V map is linear. # calc record: # The Volts are converted to mm based on the actual calibration that was done # where 1 Volt potentiometer change resulted due to approximately 5.254 mm motor displacement. # Scale and Offset for the linear conversion can be changed but they will be hard-coded # in the soft-ioctuner-boo-rf.substitutions file. # # Facility: SPEAR3 Booster RF Tuner Controls # # Auth: 28-Oct-2016, S. Condamoor (SCONDAM) # Rev: dd-mmm-yyyy, First Lastname (USERNAME) #-------------------------------------------------------------- # % macro, P, record name prefix # % macro, R, record name # % macro, PORT, asyn port for device # % macro, CH, ADC channel (1 or 2) # % macro, EGUF, Engineering Units Full # % macro, EGUL, Engineering Units Low record(ai, "B122-TUNER:Cell5PosnVolt") { field("DESC", "B00-RF Cell2 posn in V") field("DTYP", "asynInt32") field("INP", "@asyn(AIN0)Ch2Sample.Ch2Value") field("SCAN", "I/O Intr") field("LINR", "LINEAR") field("EGUF", "10") field("EGUL", "-10") field("EGU", "V") field("FLNK", "B122-TUNER:Cell5Posn") info(autosaveFields, "EGUF EGUL") } # # Convert to a 32-bit integer and convert to floating point. # A and B and Alarm Limits will be saved and restored by RDB upon ioc reboot. # # % macro, Offset, Offset for V->mm linear conversion # % macro, Scale, Slope for V->mm linear conversion # % macro, high, HIGH Alarm Limit # % macro, hihi, HIHI Alarm Limit # % macro, high, HIGH Alarm Limit # % macro, lolo, LOLO Alarm Limit # % macro, low, LOW Alarm Limit record(calc,"B122-TUNER:Cell5Posn") { field(DESC, "B00-RF Cell2 posn in mm") # field(ASG, "$(security,undefined)ADMIN") field(PREC, "2") field(EGU, "mm") field(PINI, "YES") field(HIHI, "15.0") field(HIGH, "13.0") field(LOLO, "-42.0") field(LOW, "-40.0") # field(HYST, "0.1") field(HHSV, "MAJOR") field(HSV, "MINOR") field(LLSV, "MAJOR") field(LSV, "MINOR") field(INPA, "B122-TUNER:Cell5PosnVolt MS") field(B, "0.0") field(C, "5.26936") field(CALC, "B+(C*A)") field("FLNK", "B122-TUNER:Cell5PosnCalib") info(autosaveFields, "LOW LOLO HIGH HIHI B C") } # # Calculate polynomial: x is raw counts from adc and a-h are polynomial coefficients # f = a*x^0 + b*x^1 + c*x^2 + d*x^3 + e*x^4 + f*x^5 + g*x^6 + h*x^7 # record(calc, "B122-TUNER:Cell5PosnCalib") { field(DESC, "B00-RF Cell2 posn in mm") # field(ASG, "$(security,undefined)ADMIN") field(SCAN, "Passive") field(A, "0") field(B, "0") field(C, "0") field(D, "0") field(E, "0") field(F, "0") field(G, "0") field(H, "0") field(INPL, "B122-TUNER:Cell5PosnVolt.RVAL") field(PREC, "2") field(EGU, "mm") field(PINI, "YES") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(CALC, "A*L^0+B*L^1+C*L^2+D*L^3+E*L^4+F*L^5+G*L^6+H*L^7") info(autosaveFields, "LOW LOLO HIGH HIHI A B C D E F G H") }