# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS1:BPMRPTR:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS1:BPMRPTR:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS1:BPMRPTR:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS1:BPMRPTR:ALHBCURR") {
  field(INP, "PHYS:SYS1:1:BPMRPTR NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS1:BPMRPTR:ALHBCHK")
}

record(calc, "ALRM:SYS1:BPMRPTR:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS1:BPMRPTR:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS1:BPMRPTR:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS1:BPMRPTR:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS1:BPMRPTR:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS1:BPMRPTR:ALHBERR") {
  field(DESC, "BPMRPTR monitoring")
  field(INP, "ALRM:SYS1:BPMRPTR:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS1:BPMRPTR:ALHBPREV")
}

record(ai, "ALRM:SYS1:BPMRPTR:ALHBPREV") {
  field(INP, "ALRM:SYS1:BPMRPTR:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS1:FACETEGR:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS1:FACETEGR:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS1:FACETEGR:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS1:FACETEGR:ALHBCURR") {
  field(INP, "PHYS:SYS1:1:FEEDBACK NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS1:FACETEGR:ALHBCHK")
}

record(calc, "ALRM:SYS1:FACETEGR:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS1:FACETEGR:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS1:FACETEGR:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS1:FACETEGR:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS1:FACETEGR:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS1:FACETEGR:ALHBERR") {
  field(DESC, "FACETEGR monitoring")
  field(INP, "ALRM:SYS1:FACETEGR:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS1:FACETEGR:ALHBPREV")
}

record(ai, "ALRM:SYS1:FACETEGR:ALHBPREV") {
  field(INP, "ALRM:SYS1:FACETEGR:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS1:LI20FBCK:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS1:LI20FBCK:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS1:LI20FBCK:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS1:LI20FBCK:ALHBCURR") {
  field(INP, "PHYS:LI20:1:TCAVFBCK NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS1:LI20FBCK:ALHBCHK")
}

record(calc, "ALRM:SYS1:LI20FBCK:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS1:LI20FBCK:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS1:LI20FBCK:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS1:LI20FBCK:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS1:LI20FBCK:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS1:LI20FBCK:ALHBERR") {
  field(DESC, "LI20FBCK monitoring")
  field(INP, "ALRM:SYS1:LI20FBCK:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS1:LI20FBCK:ALHBPREV")
}

record(ai, "ALRM:SYS1:LI20FBCK:ALHBPREV") {
  field(INP, "ALRM:SYS1:LI20FBCK:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS1:KLYSCUD:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS1:KLYSCUD:SCAN.VAL")
  field(INPB, "15")
  field(OUT, "ALRM:SYS1:KLYSCUD:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS1:KLYSCUD:ALHBCURR") {
  field(INP, "PHYS:SYS1:1:KLYSCUD NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS1:KLYSCUD:ALHBCHK")
}

record(calc, "ALRM:SYS1:KLYSCUD:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS1:KLYSCUD:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS1:KLYSCUD:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS1:KLYSCUD:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS1:KLYSCUD:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS1:KLYSCUD:ALHBERR") {
  field(DESC, "KLYSCUD monitoring")
  field(INP, "ALRM:SYS1:KLYSCUD:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS1:KLYSCUD:ALHBPREV")
}

record(ai, "ALRM:SYS1:KLYSCUD:ALHBPREV") {
  field(INP, "ALRM:SYS1:KLYSCUD:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS1:OPREP:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS1:OPREP:SCAN.VAL")
  field(INPB, "15")
  field(OUT, "ALRM:SYS1:OPREP:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS1:OPREP:ALHBCURR") {
  field(INP, "SIOC:SYS1:ML00:AO002 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS1:OPREP:ALHBCHK")
}

record(calc, "ALRM:SYS1:OPREP:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS1:OPREP:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS1:OPREP:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS1:OPREP:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS1:OPREP:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS1:OPREP:ALHBERR") {
  field(DESC, "OPREP monitoring")
  field(INP, "ALRM:SYS1:OPREP:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS1:OPREP:ALHBPREV")
}

record(ai, "ALRM:SYS1:OPREP:ALHBPREV") {
  field(INP, "ALRM:SYS1:OPREP:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS1:WSTLOC:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS1:WSTLOC:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS1:WSTLOC:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS1:WSTLOC:ALHBCURR") {
  field(INP, "PHYS:LI20:1:WAIST NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS1:WSTLOC:ALHBCHK")
}

record(calc, "ALRM:SYS1:WSTLOC:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS1:WSTLOC:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS1:WSTLOC:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS1:WSTLOC:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS1:WSTLOC:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS1:WSTLOC:ALHBERR") {
  field(DESC, "WSTLOC monitoring")
  field(INP, "ALRM:SYS1:WSTLOC:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS1:WSTLOC:ALHBPREV")
}

record(ai, "ALRM:SYS1:WSTLOC:ALHBPREV") {
  field(INP, "ALRM:SYS1:WSTLOC:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS1:FACET:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS1:FACET:SCAN.VAL")
  field(INPB, "10")
  field(OUT, "ALRM:SYS1:FACET:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS1:FACET:ALHBCURR") {
  field(INP, "OSC:LT10:20:FS_WATCHDOG NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS1:FACET:ALHBCHK")
}

record(calc, "ALRM:SYS1:FACET:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS1:FACET:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS1:FACET:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS1:FACET:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS1:FACET:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS1:FACET:ALHBERR") {
  field(DESC, "FACET monitoring")
  field(INP, "ALRM:SYS1:FACET:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS1:FACET:ALHBPREV")
}

record(ai, "ALRM:SYS1:FACET:ALHBPREV") {
  field(INP, "ALRM:SYS1:FACET:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS1:FACETEXP:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS1:FACETEXP:SCAN.VAL")
  field(INPB, "10")
  field(OUT, "ALRM:SYS1:FACETEXP:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS1:FACETEXP:ALHBCURR") {
  field(INP, "OSC:LA20:10:FS_WATCHDOG NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS1:FACETEXP:ALHBCHK")
}

record(calc, "ALRM:SYS1:FACETEXP:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS1:FACETEXP:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS1:FACETEXP:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS1:FACETEXP:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS1:FACETEXP:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS1:FACETEXP:ALHBERR") {
  field(DESC, "FACETEXP monitoring")
  field(INP, "ALRM:SYS1:FACETEXP:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS1:FACETEXP:ALHBPREV")
}

record(ai, "ALRM:SYS1:FACETEXP:ALHBPREV") {
  field(INP, "ALRM:SYS1:FACETEXP:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS1:LI10ENGY:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS1:LI10ENGY:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS1:LI10ENGY:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS1:LI10ENGY:ALHBCURR") {
  field(INP, "SIOC:SYS1:ML00:AO050 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS1:LI10ENGY:ALHBCHK")
}

record(calc, "ALRM:SYS1:LI10ENGY:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS1:LI10ENGY:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS1:LI10ENGY:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS1:LI10ENGY:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS1:LI10ENGY:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS1:LI10ENGY:ALHBERR") {
  field(DESC, "LI10ENGY monitoring")
  field(INP, "ALRM:SYS1:LI10ENGY:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS1:LI10ENGY:ALHBPREV")
}

record(ai, "ALRM:SYS1:LI10ENGY:ALHBPREV") {
  field(INP, "ALRM:SYS1:LI10ENGY:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS1:GUNWATCHER:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS1:GUNWATCHER:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS1:GUNWATCHER:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS1:GUNWATCHER:ALHBCURR") {
  field(INP, "PHYS:IN10:1:GUN NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS1:GUNWATCHER:ALHBCHK")
}

record(calc, "ALRM:SYS1:GUNWATCHER:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS1:GUNWATCHER:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS1:GUNWATCHER:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS1:GUNWATCHER:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS1:GUNWATCHER:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS1:GUNWATCHER:ALHBERR") {
  field(DESC, "GUNWATCHER monitoring")
  field(INP, "ALRM:SYS1:GUNWATCHER:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS1:GUNWATCHER:ALHBPREV")
}

record(ai, "ALRM:SYS1:GUNWATCHER:ALHBPREV") {
  field(INP, "ALRM:SYS1:GUNWATCHER:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS1:CATHSUPP:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS1:CATHSUPP:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS1:CATHSUPP:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS1:CATHSUPP:ALHBCURR") {
  field(INP, "PHYS:IN10:1:CATHSUPP NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS1:CATHSUPP:ALHBCHK")
}

record(calc, "ALRM:SYS1:CATHSUPP:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS1:CATHSUPP:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS1:CATHSUPP:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS1:CATHSUPP:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS1:CATHSUPP:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS1:CATHSUPP:ALHBERR") {
  field(DESC, "CATHSUPP monitoring")
  field(INP, "ALRM:SYS1:CATHSUPP:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS1:CATHSUPP:ALHBPREV")
}

record(ai, "ALRM:SYS1:CATHSUPP:ALHBPREV") {
  field(INP, "ALRM:SYS1:CATHSUPP:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS1:DEFENDER:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS1:DEFENDER:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS1:DEFENDER:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS1:DEFENDER:ALHBCURR") {
  field(INP, "PHYS:LI20:1:DEFENDER NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS1:DEFENDER:ALHBCHK")
}

record(calc, "ALRM:SYS1:DEFENDER:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS1:DEFENDER:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS1:DEFENDER:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS1:DEFENDER:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS1:DEFENDER:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS1:DEFENDER:ALHBERR") {
  field(DESC, "DEFENDER monitoring")
  field(INP, "ALRM:SYS1:DEFENDER:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS1:DEFENDER:ALHBPREV")
}

record(ai, "ALRM:SYS1:DEFENDER:ALHBPREV") {
  field(INP, "ALRM:SYS1:DEFENDER:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS1:LA10LASRARCH:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS1:LA10LASRARCH:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS1:LA10LASRARCH:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS1:LA10LASRARCH:ALHBCURR") {
  field(INP, "PHYS:LA10:1:LASR_ARCHIV NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS1:LA10LASRARCH:ALHBCHK")
}

record(calc, "ALRM:SYS1:LA10LASRARCH:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS1:LA10LASRARCH:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS1:LA10LASRARCH:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS1:LA10LASRARCH:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS1:LA10LASRARCH:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS1:LA10LASRARCH:ALHBERR") {
  field(DESC, "LA10LASRARCH monitoring")
  field(INP, "ALRM:SYS1:LA10LASRARCH:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS1:LA10LASRARCH:ALHBPREV")
}

record(ai, "ALRM:SYS1:LA10LASRARCH:ALHBPREV") {
  field(INP, "ALRM:SYS1:LA10LASRARCH:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS1:LA20LASRARCH:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS1:LA20LASRARCH:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS1:LA20LASRARCH:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS1:LA20LASRARCH:ALHBCURR") {
  field(INP, "PHYS:LA20:1:LASR_ARCHIV NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS1:LA20LASRARCH:ALHBCHK")
}

record(calc, "ALRM:SYS1:LA20LASRARCH:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS1:LA20LASRARCH:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS1:LA20LASRARCH:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS1:LA20LASRARCH:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS1:LA20LASRARCH:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS1:LA20LASRARCH:ALHBERR") {
  field(DESC, "LA20LASRARCH monitoring")
  field(INP, "ALRM:SYS1:LA20LASRARCH:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS1:LA20LASRARCH:ALHBPREV")
}

record(ai, "ALRM:SYS1:LA20LASRARCH:ALHBPREV") {
  field(INP, "ALRM:SYS1:LA20LASRARCH:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS1:FASTLASRARCH:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS1:FASTLASRARCH:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS1:FASTLASRARCH:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS1:FASTLASRARCH:ALHBCURR") {
  field(INP, "PHYS:LA10:1:FASTLASR_ARCHIV NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS1:FASTLASRARCH:ALHBCHK")
}

record(calc, "ALRM:SYS1:FASTLASRARCH:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS1:FASTLASRARCH:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS1:FASTLASRARCH:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS1:FASTLASRARCH:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS1:FASTLASRARCH:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS1:FASTLASRARCH:ALHBERR") {
  field(DESC, "FASTLASRARCH monitoring")
  field(INP, "ALRM:SYS1:FASTLASRARCH:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS1:FASTLASRARCH:ALHBPREV")
}

record(ai, "ALRM:SYS1:FASTLASRARCH:ALHBPREV") {
  field(INP, "ALRM:SYS1:FASTLASRARCH:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS1:STEERING:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS1:STEERING:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS1:STEERING:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS1:STEERING:ALHBCURR") {
  field(INP, "PHYS:LA20:1:STEERING NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS1:STEERING:ALHBCHK")
}

record(calc, "ALRM:SYS1:STEERING:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS1:STEERING:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS1:STEERING:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS1:STEERING:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS1:STEERING:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS1:STEERING:ALHBERR") {
  field(DESC, "STEERING monitoring")
  field(INP, "ALRM:SYS1:STEERING:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS1:STEERING:ALHBPREV")
}

record(ai, "ALRM:SYS1:STEERING:ALHBPREV") {
  field(INP, "ALRM:SYS1:STEERING:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS1:BPMCALMGR:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS1:BPMCALMGR:SCAN.VAL")
  field(INPB, "5")
  field(OUT, "ALRM:SYS1:BPMCALMGR:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS1:BPMCALMGR:ALHBCURR") {
  field(INP, "SIOC:SYS1:ML00:AO048 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS1:BPMCALMGR:ALHBCHK")
}

record(calc, "ALRM:SYS1:BPMCALMGR:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS1:BPMCALMGR:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS1:BPMCALMGR:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS1:BPMCALMGR:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS1:BPMCALMGR:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS1:BPMCALMGR:ALHBERR") {
  field(DESC, "BPMCALMGR monitoring")
  field(INP, "ALRM:SYS1:BPMCALMGR:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS1:BPMCALMGR:ALHBPREV")
}

record(ai, "ALRM:SYS1:BPMCALMGR:ALHBPREV") {
  field(INP, "ALRM:SYS1:BPMCALMGR:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS1:FACETCHRGFB:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS1:FACETCHRGFB:SCAN.VAL")
  field(INPB, "60")
  field(OUT, "ALRM:SYS1:FACETCHRGFB:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS1:FACETCHRGFB:ALHBCURR") {
  field(INP, "PHYS:IN10:1:FACET_CHRGFB NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS1:FACETCHRGFB:ALHBCHK")
}

record(calc, "ALRM:SYS1:FACETCHRGFB:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS1:FACETCHRGFB:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS1:FACETCHRGFB:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS1:FACETCHRGFB:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS1:FACETCHRGFB:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS1:FACETCHRGFB:ALHBERR") {
  field(DESC, "FACETCHRGFB monitoring")
  field(INP, "ALRM:SYS1:FACETCHRGFB:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS1:FACETCHRGFB:ALHBPREV")
}

record(ai, "ALRM:SYS1:FACETCHRGFB:ALHBPREV") {
  field(INP, "ALRM:SYS1:FACETCHRGFB:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS1:CAMERA:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS1:CAMERA:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS1:CAMERA:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS1:CAMERA:ALHBCURR") {
  field(INP, "PHYS:SYS1:1:CAMERA NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS1:CAMERA:ALHBCHK")
}

record(calc, "ALRM:SYS1:CAMERA:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS1:CAMERA:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS1:CAMERA:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS1:CAMERA:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS1:CAMERA:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS1:CAMERA:ALHBERR") {
  field(DESC, "CAMERA monitoring")
  field(INP, "ALRM:SYS1:CAMERA:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS1:CAMERA:ALHBPREV")
}

record(ai, "ALRM:SYS1:CAMERA:ALHBPREV") {
  field(INP, "ALRM:SYS1:CAMERA:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS1:MPS_REC_FLT:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS1:MPS_REC_FLT:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS1:MPS_REC_FLT:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS1:MPS_REC_FLT:ALHBCURR") {
  field(INP, "PHYS:SYS1:1:MPS_REC_FLT_WATCH NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS1:MPS_REC_FLT:ALHBCHK")
}

record(calc, "ALRM:SYS1:MPS_REC_FLT:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS1:MPS_REC_FLT:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS1:MPS_REC_FLT:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS1:MPS_REC_FLT:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS1:MPS_REC_FLT:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS1:MPS_REC_FLT:ALHBERR") {
  field(DESC, "MPS_REC_FLT monitoring")
  field(INP, "ALRM:SYS1:MPS_REC_FLT:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS1:MPS_REC_FLT:ALHBPREV")
}

record(ai, "ALRM:SYS1:MPS_REC_FLT:ALHBPREV") {
  field(INP, "ALRM:SYS1:MPS_REC_FLT:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS1:MODEL_SERVER:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS1:MODEL_SERVER:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS1:MODEL_SERVER:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS1:MODEL_SERVER:ALHBCURR") {
  field(INP, "PHYS:SYS1:1:MODEL_SERVER NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS1:MODEL_SERVER:ALHBCHK")
}

record(calc, "ALRM:SYS1:MODEL_SERVER:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS1:MODEL_SERVER:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS1:MODEL_SERVER:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS1:MODEL_SERVER:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS1:MODEL_SERVER:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS1:MODEL_SERVER:ALHBERR") {
  field(DESC, "MODEL_SERVER monitoring")
  field(INP, "ALRM:SYS1:MODEL_SERVER:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS1:MODEL_SERVER:ALHBPREV")
}

record(ai, "ALRM:SYS1:MODEL_SERVER:ALHBPREV") {
  field(INP, "ALRM:SYS1:MODEL_SERVER:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS1:MODEL_SERVER2:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS1:MODEL_SERVER2:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS1:MODEL_SERVER2:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS1:MODEL_SERVER2:ALHBCURR") {
  field(INP, "PHYS:SYS1:1:MODEL_SERVER2 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS1:MODEL_SERVER2:ALHBCHK")
}

record(calc, "ALRM:SYS1:MODEL_SERVER2:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS1:MODEL_SERVER2:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS1:MODEL_SERVER2:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS1:MODEL_SERVER2:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS1:MODEL_SERVER2:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS1:MODEL_SERVER2:ALHBERR") {
  field(DESC, "MODEL_SERVER2 monitoring")
  field(INP, "ALRM:SYS1:MODEL_SERVER2:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS1:MODEL_SERVER2:ALHBPREV")
}

record(ai, "ALRM:SYS1:MODEL_SERVER2:ALHBPREV") {
  field(INP, "ALRM:SYS1:MODEL_SERVER2:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS1:DIAG_SUPPORT:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS1:DIAG_SUPPORT:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS1:DIAG_SUPPORT:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS1:DIAG_SUPPORT:ALHBCURR") {
  field(INP, "PHYS:SYS1:1:DIAG_SUPPORT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS1:DIAG_SUPPORT:ALHBCHK")
}

record(calc, "ALRM:SYS1:DIAG_SUPPORT:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS1:DIAG_SUPPORT:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS1:DIAG_SUPPORT:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS1:DIAG_SUPPORT:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS1:DIAG_SUPPORT:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS1:DIAG_SUPPORT:ALHBERR") {
  field(DESC, "DIAG_SUPPORT monitoring")
  field(INP, "ALRM:SYS1:DIAG_SUPPORT:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS1:DIAG_SUPPORT:ALHBPREV")
}

record(ai, "ALRM:SYS1:DIAG_SUPPORT:ALHBPREV") {
  field(INP, "ALRM:SYS1:DIAG_SUPPORT:ALHBCURR NPP NMS")
}

# Joe's matlab code
# for m = 1:num_feedbacks
#    ...
#    incr_ok = check_running(pv_data{n+1}, pv_data_last{n+1}); % the CNTDISP PV
#    green_ok = strcmp('ON', pv_data{n}); % the STATE PV 
#    if green_ok && (~incr_ok) % green, not incrementing
#       error_flag(n) = 1;
#    end
# end
# ======================================================

# check to see if feedback is incrementing (running)
record(calcout, "FBCK:FMDL0:1:ALSCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "FBCK:FMDL0:1:ALSCAN.VAL")
  field(INPB, "600")
  field(OUT, "FBCK:FMDL0:1:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "FBCK:FMDL0:1:ALHBCURR") {
  field(INP,  "FBCK:FMDL0:1:CNTDISP NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "FBCK:FMDL0:1:ALHBCHK")
}

record(calc, "FBCK:FMDL0:1:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "FBCK:FMDL0:1:ALHBCURR.VAL NPP MS")
  field(INPB, "FBCK:FMDL0:1:ALHBPREV.VAL NPP MS")
  field(INPC, "FBCK:FMDL0:1:ALHBCURR.SEVR")
  field(FLNK, "FBCK:FMDL0:1:ALHBERR")
}

# never in alarm; this is simply the status, not
# the final alarm PV.
record(mbbi, "FBCK:FMDL0:1:ALHBERR") {
  field(DESC, "FBCK:FMDL0:1 monitoring")
  field(FLNK, "FBCK:FMDL0:1:ALFBERRCALC")
  field(INP, "FBCK:FMDL0:1:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "FBCK:FMDL0:1:ALHBPREV")
}

record(ai, "FBCK:FMDL0:1:ALHBPREV") {
  field(INP,  "FBCK:FMDL0:1:ALHBCURR NPP MS")
  field(FLNK, "FBCK:FMDL0:1:ALFBERRCALC") 
}

# then see if the status is OK, but it's not incrementing
# (it thinks it's good, but it's not)
# feedback is on and not incrementing is an error
# if any input is invalid, then the status is invalid
# ALHBERR has no value severity, so can propagate its severity
# into the calc (to capture invalid)
# STATE itself could be major or minor; simply want to capture an
# invalid status here.
record(calc, "FBCK:FMDL0:1:ALFBERRCALC") {
  field(CALC, "C>2||D>2?2:((A=1&&B=1)?1:0)")
  field(INPA, "FBCK:FMDL0:1:STATE NPP NMS")
  field(INPB, "FBCK:FMDL0:1:ALHBERR NPP NMS")
  field(INPC, "FBCK:FMDL0:1:STATE.SEVR")
  field(INPD, "FBCK:FMDL0:1:ALHBERR.SEVR")
  field(FLNK, "FBCK:FMDL0:1:ALFBERR")
}

record(mbbi, "FBCK:FMDL0:1:ALFBERR") {
  field(DESC, "FBCK:FMDL0:1 monitoring")
  field(INP, "FBCK:FMDL0:1:ALFBERRCALC.VAL NPP MS")
  field(ZRST, "OK")
  field(ONST, "ON_NOT_RUNNING")
  field(TWST, "INVALID")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
}

#record(bi, "FBCK:FMDL0:1:ALFBERR") {
#  field(DESC, "FBCK:FMDL0:1 monitoring")
#  field(INP, "FBCK:FMDL0:1:ALFBERRCALC.VAL NPP MS")
#  field(ZSV, "NO_ALARM")
#  field(OSV, "MAJOR")
#  field(ZNAM, "OK")
#  field(ONAM, "ON_NOT_RUNNING")
#}


record(bo, F2:WATCHER:FACETSUPPORT_STAT) {
  field(DESC, "Running Status for Facet Support IOC")
  field(SCAN, "Passive")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(OMSL, "supervisory")
  field(HIGH, "3")
  field(ZNAM, "OFF")
  field(ONAM, "RUNNING")
  field(ZSV, "MAJOR")
}

record(bo, F2:WATCHER:KEEPALIVE) {
  field(OUT, "F2:WATCHER:FACETSUPPORT_STAT PP")
  field(VAL, "1")
  field(PINI, "YES")
  field(FLNK, "F2:WATCHER:FACETSUPPORT_STAT")
  field(SCAN, "1 second")
}

record(bo, F2:WATCHER:WAISTLOCATOR_STAT) {
  field(DESC, "Waist Locater Running Status")
  field(SCAN, "Passive")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(OMSL, "supervisory")
  field(HIGH, "3")
  field(ZNAM, "OFF")
  field(ONAM, "RUNNING")
  field(ZSV, "MAJOR")
  field(COSV, "NO_ALARM")
}

record(bo, F2:WATCHER:GUNWATCHER_STAT) {
  field(DESC, "Gun Watcher Running Status")
  field(SCAN, "Passive")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(OMSL, "supervisory")
  field(HIGH, "3")
  field(ZNAM, "OFF")
  field(ONAM, "RUNNING")
  field(ZSV, "MAJOR")
}

record(bo, F2:WATCHER:CATHODESUPPORT_STAT) {
  field(DESC, "Cathode Support Running Status")
  field(SCAN, "Passive")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(OMSL, "supervisory")
  field(HIGH, "3")
  field(ZNAM, "OFF")
  field(ONAM, "RUNNING")
  field(ZSV, "MAJOR")
}

record(bo, F2:WATCHER:FEEDBACKS_STAT) {
  field(DESC, "Gun Watcher Running Status")
  field(SCAN, "Passive")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(OMSL, "supervisory")
  field(HIGH, "3")
  field(ZNAM, "OFF")
  field(ONAM, "RUNNING")
  field(ZSV, "MAJOR")
}

record(bo, F2:WATCHER:BPMREPEATER_STAT) {
  field(DESC, "BPM Repeater Status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(OMSL, "closed_loop")
  field(ZNAM, "RUNNING")
  field(ONAM, "OFF")
  field(DOL, "ALRM:SYS1:BPMRPTR:ALHBCHK CA MS")
  field(OSV, "MAJOR")
}

record(bo, F2:WATCHER:TCAVFEEDBACK_STAT) {
  field(DESC, "TCAV Feedback Status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(OMSL, "closed_loop")
  field(ZNAM, "RUNNING")
  field(ONAM, "OFF")
  field(DOL, "ALRM:SYS1:LI20FBCK:ALHBCHK CA MS")
  field(OSV, "MAJOR")
}

record(bo, F2:WATCHER:VITARA_STAT) {
  field(DESC, "FACET Vitara Status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(OMSL, "closed_loop")
  field(ZNAM, "RUNNING")
  field(ONAM, "OFF")
  field(DOL, "ALRM:SYS1:FACET:ALHBCHK CA MS")
  field(OSV, "MAJOR")
}

record(bo, F2:WATCHER:KLYSCUD_STAT) {
  field(DESC, "Klystron CUD Status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(OMSL, "closed_loop")
  field(ZNAM, "RUNNING")
  field(ONAM, "OFF")
  field(DOL, "ALRM:SYS1:KLYSCUD:ALHBCHK CA MS")
  field(OSV, "MAJOR")
}

record(calc, F2:WATCHER:WATCHER_STAT) {
  field(SCAN, "1 second")
  field(INPA, "F2:WATCHER:FACETSUPPORT_STAT NPP MS")
  field(INPB, "F2:WATCHER:WAISTLOCATOR_STAT NPP MS")
  field(INPC, "F2:WATCHER:GUNWATCHER_STAT NPP MS")
  field(INPD, "F2:WATCHER:CATHODESUPPORT_STAT NPP MS")
  field(INPE, "F2:WATCHER:FEEDBACKS_STAT NPP MS")
  field(INPF, "F2:WATCHER:DIFFPUMP_STAT NPP MS")
  field(INPG, "F2:WATCHER:S10LASERARCHIVER_STAT NPP MS")
  field(INPH, "F2:WATCHER:S20LASERARCHIVER_STAT NPP MS")
  field(INPI, "F2:WATCHER:FASTLASERARCHIVER_STAT NPP MS")
  field(INPJ, "F2:WATCHER:MDLFF_STAT NPP MS")
  field(INPK, "F2:WATCHER:ORBIT_STAT NPP MS")
  field(INPL, "F2:WATCHER:WATCHER_STAT1 PP MS")
}

record(bo, F2:WATCHER:DEFENDER_STAT) {
  field(DESC, "Defender Status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(OMSL, "closed_loop")
  field(ZNAM, "RUNNING")
  field(ONAM, "OFF")
  field(DOL, "ALRM:SYS1:DEFENDER:ALHBCHK CA MS")
  field(OSV, "MAJOR")
}

record(calc, F2:WATCHER:WATCHER_STAT1) {
  field(SCAN, "Passive")
  field(INPA, "F2:WATCHER:BPMREPEATER_STAT NPP MS")
  field(INPB, "F2:WATCHER:TCAVFEEDBACK_STAT NPP MS")
  field(INPC, "F2:WATCHER:CHARGEFEEDBACK_STAT.VAL NPP MS")
  field(INPD, "F2:WATCHER:VITARA_STAT NPP MS")
  field(INPE, "F2:WATCHER:KLYSCUD_STAT NPP MS")
  field(INPF, "F2:WATCHER:DEFENDER_STAT NPP MS")
  field(INPG, "F2:WATCHER:LASERSTEERING_STAT NPP MS")
  field(INPH, "F2:WATCHER:CAMERA_STAT NPP MS")
  field(INPI, "F2:WATCHER:MODEL_SERVER_STAT NPP MS")
  field(INPJ, "F2:WATCHER:MODEL_SERVER2_STAT NPP MS")
  field(INPK, "F2:WATCHER:DIAG_SUPPORT_STAT NPP MS")
}

record(bo, F2:WATCHER:LASERSTEERING_STAT) {
  field(DESC, "Laser Steering Status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(OMSL, "closed_loop")
  field(ZNAM, "RUNNING")
  field(ONAM, "OFF")
  field(DOL, "ALRM:SYS1:STEERING:ALHBCHK CA MS")
  field(OSV, "MAJOR")
}

record(bo, F2:WATCHER:DIFFPUMP_STAT) {
  field(DESC, "Differential Pumping Status")
  field(SCAN, "Passive")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(OMSL, "supervisory")
  field(HIGH, "3")
  field(ZNAM, "OFF")
  field(ONAM, "RUNNING")
  field(ZSV, "MAJOR")
}

record(bo, F2:WATCHER:S10LASERARCHIVER_STAT) {
  field(DESC, "S10 Laser Archiver Status")
  field(SCAN, "Passive")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(OMSL, "supervisory")
  field(HIGH, "3")
  field(ZNAM, "OFF")
  field(ONAM, "RUNNING")
  field(ZSV, "MAJOR")
}

record(bo, F2:WATCHER:S20LASERARCHIVER_STAT) {
  field(DESC, "S20 Laser Archiver Status")
  field(SCAN, "Passive")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(OMSL, "supervisory")
  field(HIGH, "3")
  field(ZNAM, "OFF")
  field(ONAM, "RUNNING")
  field(ZSV, "MAJOR")
}

record(bo, F2:WATCHER:FASTLASERARCHIVER_STAT) {
  field(DESC, "S20 Laser Archiver Status")
  field(SCAN, "Passive")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(OMSL, "supervisory")
  field(HIGH, "3")
  field(ZNAM, "OFF")
  field(ONAM, "RUNNING")
  field(ZSV, "MAJOR")
}

record(bo, F2:WATCHER:CHARGEFEEDBACK_STAT) {
  field(DESC, "OP Repeater Status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(OMSL, "closed_loop")
  field(ZNAM, "RUNNING")
  field(ONAM, "OFF")
  field(DOL, "ALRM:SYS1:FACETCHRGFB:ALHBCHK CA MS")
  field(OSV, "MAJOR")
}

record(bo, F2:WATCHER:MDLFF_STAT) {
  field(DESC, "MDL Feedforward Status")
  field(SCAN, "Passive")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(OMSL, "supervisory")
  field(HIGH, "3")
  field(ZNAM, "OFF")
  field(ONAM, "RUNNING")
  field(ZSV, "MAJOR")
}

record(bo, F2:WATCHER:ORBIT_STAT) {
  field(DESC, "Orbit Watcher Status")
  field(SCAN, "Passive")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(OMSL, "supervisory")
  field(HIGH, "3")
  field(ZNAM, "OFF")
  field(ONAM, "RUNNING")
  field(ZSV, "MAJOR")
}

record(bo, F2:MATLABSERVER:STAT1:OPI20) {
  field(VAL, "0")
  field(HIGH, "90")
  field(PINI, "YES")
  field(OMSL, "supervisory")
  field(ZNAM, "OFF")
  field(ONAM, "RUNNING")
  field(ZSV, "MAJOR")
}

record(bo, F2:MATLABSERVER:STAT1:OPI21) {
  field(VAL, "0")
  field(HIGH, "90")
  field(PINI, "YES")
  field(OMSL, "supervisory")
  field(ZNAM, "OFF")
  field(ONAM, "RUNNING")
  field(ZSV, "MAJOR")
}

record(bo, F2:MATLABSERVER:STAT1:OPI22) {
  field(VAL, "0")
  field(HIGH, "90")
  field(PINI, "YES")
  field(OMSL, "supervisory")
  field(ZNAM, "OFF")
  field(ONAM, "RUNNING")
  field(ZSV, "MAJOR")
}

record(bo, F2:MATLABSERVER:STAT1:OPI23) {
  field(VAL, "0")
  field(HIGH, "90")
  field(PINI, "YES")
  field(OMSL, "supervisory")
  field(ZNAM, "OFF")
  field(ONAM, "RUNNING")
  field(ZSV, "MAJOR")
}

record(bo, F2:MATLABSERVER:STAT2:OPI20) {
  field(VAL, "0")
  field(HIGH, "90")
  field(PINI, "YES")
  field(OMSL, "supervisory")
  field(ZNAM, "OFF")
  field(ONAM, "RUNNING")
  field(ZSV, "MAJOR")
}

record(bo, F2:MATLABSERVER:STAT2:OPI21) {
  field(VAL, "0")
  field(HIGH, "90")
  field(PINI, "YES")
  field(OMSL, "supervisory")
  field(ZNAM, "OFF")
  field(ONAM, "RUNNING")
  field(ZSV, "MAJOR")
}

record(bo, F2:MATLABSERVER:STAT2:OPI22) {
  field(VAL, "0")
  field(HIGH, "90")
  field(PINI, "YES")
  field(OMSL, "supervisory")
  field(ZNAM, "OFF")
  field(ONAM, "RUNNING")
  field(ZSV, "MAJOR")
}

record(bo, F2:MATLABSERVER:STAT2:OPI23) {
  field(VAL, "0")
  field(HIGH, "90")
  field(PINI, "YES")
  field(OMSL, "supervisory")
  field(ZNAM, "OFF")
  field(ONAM, "RUNNING")
  field(ZSV, "MAJOR")
}

record(bo, F2:MATLABSERVER:STAT3:OPI20) {
  field(VAL, "0")
  field(HIGH, "90")
  field(PINI, "YES")
  field(OMSL, "supervisory")
  field(ZNAM, "OFF")
  field(ONAM, "RUNNING")
  field(ZSV, "MAJOR")
}

record(bo, F2:MATLABSERVER:STAT3:OPI21) {
  field(VAL, "0")
  field(HIGH, "90")
  field(PINI, "YES")
  field(OMSL, "supervisory")
  field(ZNAM, "OFF")
  field(ONAM, "RUNNING")
  field(ZSV, "MAJOR")
}

record(bo, F2:MATLABSERVER:STAT3:OPI22) {
  field(VAL, "0")
  field(HIGH, "90")
  field(PINI, "YES")
  field(OMSL, "supervisory")
  field(ZNAM, "OFF")
  field(ONAM, "RUNNING")
  field(ZSV, "MAJOR")
}

record(bo, F2:MATLABSERVER:STAT3:OPI23) {
  field(VAL, "0")
  field(HIGH, "90")
  field(PINI, "YES")
  field(OMSL, "supervisory")
  field(ZNAM, "OFF")
  field(ONAM, "RUNNING")
  field(ZSV, "MAJOR")
}


record(bo, F2:WATCHER:CAMERA_STAT) {
  field(DESC, "Klystron CUD Status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(OMSL, "closed_loop")
  field(ZNAM, "RUNNING")
  field(ONAM, "OFF")
  field(DOL, "ALRM:SYS1:CAMERA:ALHBCHK CA MS")
  field(OSV, "MAJOR")
}

record(bo, F2:WATCHER:MODEL_SERVER_STAT) {
  field(DESC, "Model Server Status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(OMSL, "closed_loop")
  field(ZNAM, "RUNNING")
  field(ONAM, "OFF")
  field(DOL, "ALRM:SYS1:MODEL_SERVER:ALHBCHK CA MS")
  field(OSV, "MAJOR")
}

record(bo, F2:WATCHER:MODEL_SERVER2_STAT) {
  field(DESC, "Model Server2 Status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(OMSL, "closed_loop")
  field(ZNAM, "RUNNING")
  field(ONAM, "OFF")
  field(DOL, "ALRM:SYS1:MODEL_SERVER2:ALHBCHK CA MS")
  field(OSV, "MAJOR")
}

record(bo, F2:WATCHER:DIAG_SUPPORT_STAT) {
  field(DESC, "Diag Support Status")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(VAL, "0")
  field(OMSL, "closed_loop")
  field(ZNAM, "RUNNING")
  field(ONAM, "OFF")
  field(DOL, "ALRM:SYS1:DIAG_SUPPORT:ALHBCHK CA MS")
  field(OSV, "MAJOR")
}