# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:PADJITTER:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:PADJITTER:SCAN.VAL")
  field(INPB, "120")
  field(OUT, "ALRM:SYS0:PADJITTER:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:PADJITTER:ALHBCURR") {
  field(INP, "PHYS:SYS0:1:PADJITTER_WATCHER NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:PADJITTER:ALHBCHK")
}

record(calc, "ALRM:SYS0:PADJITTER:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:PADJITTER:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:PADJITTER:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:PADJITTER:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:PADJITTER:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:PADJITTER:ALHBERR") {
  field(DESC, "PADJITTER monitoring")
  field(INP, "ALRM:SYS0:PADJITTER:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:PADJITTER:ALHBPREV")
}

record(ai, "ALRM:SYS0:PADJITTER:ALHBPREV") {
  field(INP, "ALRM:SYS0:PADJITTER:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:KLYS_ERR:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:KLYS_ERR:SCAN.VAL")
  field(INPB, "3")
  field(OUT, "ALRM:SYS0:KLYS_ERR:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:KLYS_ERR:ALHBCURR") {
  field(INP, "PHYS:SYS0:1:KLYS_ERR_WATCHER NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:KLYS_ERR:ALHBCHK")
}

record(calc, "ALRM:SYS0:KLYS_ERR:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:KLYS_ERR:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:KLYS_ERR:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:KLYS_ERR:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:KLYS_ERR:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:KLYS_ERR:ALHBERR") {
  field(DESC, "KLYS_ERR monitoring")
  field(INP, "ALRM:SYS0:KLYS_ERR:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:KLYS_ERR:ALHBPREV")
}

record(ai, "ALRM:SYS0:KLYS_ERR:ALHBPREV") {
  field(INP, "ALRM:SYS0:KLYS_ERR:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:SC_INJ_PHA_FFW:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:SC_INJ_PHA_FFW:SCAN.VAL")
  field(INPB, "180")
  field(OUT, "ALRM:SYS0:SC_INJ_PHA_FFW:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:SC_INJ_PHA_FFW:ALHBCURR") {
  field(INP, "PHYS:SYS0:1:SC_INJ_PHA_FFW_WATCHER NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:SC_INJ_PHA_FFW:ALHBCHK")
}

record(calc, "ALRM:SYS0:SC_INJ_PHA_FFW:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:SC_INJ_PHA_FFW:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:SC_INJ_PHA_FFW:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:SC_INJ_PHA_FFW:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:SC_INJ_PHA_FFW:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:SC_INJ_PHA_FFW:ALHBERR") {
  field(DESC, "SC_INJ_PHA_FFW monitoring")
  field(INP, "ALRM:SYS0:SC_INJ_PHA_FFW:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:SC_INJ_PHA_FFW:ALHBPREV")
}

record(ai, "ALRM:SYS0:SC_INJ_PHA_FFW:ALHBPREV") {
  field(INP, "ALRM:SYS0:SC_INJ_PHA_FFW:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:SC_TIMING_PATTERNS:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:SC_TIMING_PATTERNS:SCAN.VAL")
  field(INPB, "10")
  field(OUT, "ALRM:SYS0:SC_TIMING_PATTERNS:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:SC_TIMING_PATTERNS:ALHBCURR") {
  field(INP, "TPG:SYS0:1:PATTERNS_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:SC_TIMING_PATTERNS:ALHBCHK")
}

record(calc, "ALRM:SYS0:SC_TIMING_PATTERNS:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:SC_TIMING_PATTERNS:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:SC_TIMING_PATTERNS:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:SC_TIMING_PATTERNS:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:SC_TIMING_PATTERNS:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:SC_TIMING_PATTERNS:ALHBERR") {
  field(DESC, "SC_TIMING_PATTERNS monitoring")
  field(INP, "ALRM:SYS0:SC_TIMING_PATTERNS:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:SC_TIMING_PATTERNS:ALHBPREV")
}

record(ai, "ALRM:SYS0:SC_TIMING_PATTERNS:ALHBPREV") {
  field(INP, "ALRM:SYS0:SC_TIMING_PATTERNS:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:SC_OUT_LOGIC:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:SC_OUT_LOGIC:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:SC_OUT_LOGIC:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:SC_OUT_LOGIC:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML01:AO476 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:SC_OUT_LOGIC:ALHBCHK")
}

record(calc, "ALRM:SYS0:SC_OUT_LOGIC:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:SC_OUT_LOGIC:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:SC_OUT_LOGIC:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:SC_OUT_LOGIC:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:SC_OUT_LOGIC:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:SC_OUT_LOGIC:ALHBERR") {
  field(DESC, "SC_OUT_LOGIC monitoring")
  field(INP, "ALRM:SYS0:SC_OUT_LOGIC:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:SC_OUT_LOGIC:ALHBPREV")
}

record(ai, "ALRM:SYS0:SC_OUT_LOGIC:ALHBPREV") {
  field(INP, "ALRM:SYS0:SC_OUT_LOGIC:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:MAT_MODEL:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:MAT_MODEL:SCAN.VAL")
  field(INPB, "180")
  field(OUT, "ALRM:SYS0:MAT_MODEL:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:MAT_MODEL:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML00:CALC500 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:MAT_MODEL:ALHBCHK")
}

record(calc, "ALRM:SYS0:MAT_MODEL:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:MAT_MODEL:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:MAT_MODEL:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:MAT_MODEL:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:MAT_MODEL:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:MAT_MODEL:ALHBERR") {
  field(DESC, "MAT_MODEL monitoring")
  field(INP, "ALRM:SYS0:MAT_MODEL:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:MAT_MODEL:ALHBPREV")
}

record(ai, "ALRM:SYS0:MAT_MODEL:ALHBPREV") {
  field(INP, "ALRM:SYS0:MAT_MODEL:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:NC_MPS_REC_FLT:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:NC_MPS_REC_FLT:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:NC_MPS_REC_FLT:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:NC_MPS_REC_FLT:ALHBCURR") {
  field(INP, "PHYS:SYS0:1:NC_MPS_REC_FLT_WATCH NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:NC_MPS_REC_FLT:ALHBCHK")
}

record(calc, "ALRM:SYS0:NC_MPS_REC_FLT:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:NC_MPS_REC_FLT:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:NC_MPS_REC_FLT:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:NC_MPS_REC_FLT:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:NC_MPS_REC_FLT:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:NC_MPS_REC_FLT:ALHBERR") {
  field(DESC, "NC_MPS_REC_FLT monitoring")
  field(INP, "ALRM:SYS0:NC_MPS_REC_FLT:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:NC_MPS_REC_FLT:ALHBPREV")
}

record(ai, "ALRM:SYS0:NC_MPS_REC_FLT:ALHBPREV") {
  field(INP, "ALRM:SYS0:NC_MPS_REC_FLT:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:PATT_PROG:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:PATT_PROG:SCAN.VAL")
  field(INPB, "5")
  field(OUT, "ALRM:SYS0:PATT_PROG:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:PATT_PROG:ALHBCURR") {
  field(INP, "TPG:SYS0:1:PATT_PROG_HRTBT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:PATT_PROG:ALHBCHK")
}

record(calc, "ALRM:SYS0:PATT_PROG:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:PATT_PROG:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:PATT_PROG:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:PATT_PROG:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:PATT_PROG:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:PATT_PROG:ALHBERR") {
  field(DESC, "PATT_PROG monitoring")
  field(INP, "ALRM:SYS0:PATT_PROG:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:PATT_PROG:ALHBPREV")
}

record(ai, "ALRM:SYS0:PATT_PROG:ALHBPREV") {
  field(INP, "ALRM:SYS0:PATT_PROG:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:AF:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:AF:SCAN.VAL")
  field(INPB, "5")
  field(OUT, "ALRM:SYS0:AF:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:AF:ALHBCURR") {
  field(INP, "TPG:SYS0:1:AF_HRTBT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:AF:ALHBCHK")
}

record(calc, "ALRM:SYS0:AF:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:AF:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:AF:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:AF:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:AF:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:AF:ALHBERR") {
  field(DESC, "AF monitoring")
  field(INP, "ALRM:SYS0:AF:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:AF:ALHBPREV")
}

record(ai, "ALRM:SYS0:AF:ALHBPREV") {
  field(INP, "ALRM:SYS0:AF:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:SC_SEL_PHAS_OPT:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:SC_SEL_PHAS_OPT:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:SC_SEL_PHAS_OPT:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:SC_SEL_PHAS_OPT:ALHBCURR") {
  field(INP, "PHYS:SYS0:1:SC_SEL_PHAS_OPT_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:SC_SEL_PHAS_OPT:ALHBCHK")
}

record(calc, "ALRM:SYS0:SC_SEL_PHAS_OPT:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:SC_SEL_PHAS_OPT:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:SC_SEL_PHAS_OPT:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:SC_SEL_PHAS_OPT:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:SC_SEL_PHAS_OPT:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:SC_SEL_PHAS_OPT:ALHBERR") {
  field(DESC, "SC_SEL_PHAS_OPT monitoring")
  field(INP, "ALRM:SYS0:SC_SEL_PHAS_OPT:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:SC_SEL_PHAS_OPT:ALHBPREV")
}

record(ai, "ALRM:SYS0:SC_SEL_PHAS_OPT:ALHBPREV") {
  field(INP, "ALRM:SYS0:SC_SEL_PHAS_OPT:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:HALO:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:HALO:SCAN.VAL")
  field(INPB, "10")
  field(OUT, "ALRM:SYS0:HALO:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:HALO:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML01:AO021 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:HALO:ALHBCHK")
}

record(calc, "ALRM:SYS0:HALO:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:HALO:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:HALO:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:HALO:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:HALO:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:HALO:ALHBERR") {
  field(DESC, "HALO monitoring")
  field(INP, "ALRM:SYS0:HALO:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:HALO:ALHBPREV")
}

record(ai, "ALRM:SYS0:HALO:ALHBPREV") {
  field(INP, "ALRM:SYS0:HALO:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:SC_CAV_QNCH_RESET:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:SC_CAV_QNCH_RESET:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:SC_CAV_QNCH_RESET:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:SC_CAV_QNCH_RESET:ALHBCURR") {
  field(INP, "PHYS:SYS0:1:SC_CAV_QNCH_RESET_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:SC_CAV_QNCH_RESET:ALHBCHK")
}

record(calc, "ALRM:SYS0:SC_CAV_QNCH_RESET:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:SC_CAV_QNCH_RESET:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:SC_CAV_QNCH_RESET:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:SC_CAV_QNCH_RESET:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:SC_CAV_QNCH_RESET:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:SC_CAV_QNCH_RESET:ALHBERR") {
  field(DESC, "SC_CAV_QNCH_RESET monitoring")
  field(INP, "ALRM:SYS0:SC_CAV_QNCH_RESET:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:SC_CAV_QNCH_RESET:ALHBPREV")
}

record(ai, "ALRM:SYS0:SC_CAV_QNCH_RESET:ALHBPREV") {
  field(INP, "ALRM:SYS0:SC_CAV_QNCH_RESET:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:SC_CAV_FAULT:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:SC_CAV_FAULT:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:SC_CAV_FAULT:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:SC_CAV_FAULT:ALHBCURR") {
  field(INP, "PHYS:SYS0:1:SC_CAV_FAULT_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:SC_CAV_FAULT:ALHBCHK")
}

record(calc, "ALRM:SYS0:SC_CAV_FAULT:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:SC_CAV_FAULT:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:SC_CAV_FAULT:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:SC_CAV_FAULT:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:SC_CAV_FAULT:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:SC_CAV_FAULT:ALHBERR") {
  field(DESC, "SC_CAV_FAULT monitoring")
  field(INP, "ALRM:SYS0:SC_CAV_FAULT:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:SC_CAV_FAULT:ALHBPREV")
}

record(ai, "ALRM:SYS0:SC_CAV_FAULT:ALHBPREV") {
  field(INP, "ALRM:SYS0:SC_CAV_FAULT:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:SC_MPS_FLTB0:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:SC_MPS_FLTB0:SCAN.VAL")
  field(INPB, "600")
  field(OUT, "ALRM:SYS0:SC_MPS_FLTB0:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:SC_MPS_FLTB0:ALHBCURR") {
  field(INP, "PHYS:SYS0:0:SCFaultBufferWatcher NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:SC_MPS_FLTB0:ALHBCHK")
}

record(calc, "ALRM:SYS0:SC_MPS_FLTB0:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:SC_MPS_FLTB0:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:SC_MPS_FLTB0:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:SC_MPS_FLTB0:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:SC_MPS_FLTB0:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:SC_MPS_FLTB0:ALHBERR") {
  field(DESC, "SC_MPS_FLTB0 monitoring")
  field(INP, "ALRM:SYS0:SC_MPS_FLTB0:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:SC_MPS_FLTB0:ALHBPREV")
}

record(ai, "ALRM:SYS0:SC_MPS_FLTB0:ALHBPREV") {
  field(INP, "ALRM:SYS0:SC_MPS_FLTB0:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:SC_MPS_FLTB1:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:SC_MPS_FLTB1:SCAN.VAL")
  field(INPB, "600")
  field(OUT, "ALRM:SYS0:SC_MPS_FLTB1:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:SC_MPS_FLTB1:ALHBCURR") {
  field(INP, "PHYS:SYS0:1:SCFaultBufferWatcher NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:SC_MPS_FLTB1:ALHBCHK")
}

record(calc, "ALRM:SYS0:SC_MPS_FLTB1:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:SC_MPS_FLTB1:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:SC_MPS_FLTB1:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:SC_MPS_FLTB1:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:SC_MPS_FLTB1:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:SC_MPS_FLTB1:ALHBERR") {
  field(DESC, "SC_MPS_FLTB1 monitoring")
  field(INP, "ALRM:SYS0:SC_MPS_FLTB1:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:SC_MPS_FLTB1:ALHBPREV")
}

record(ai, "ALRM:SYS0:SC_MPS_FLTB1:ALHBPREV") {
  field(INP, "ALRM:SYS0:SC_MPS_FLTB1:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:SC_MPS_FLTB2:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:SC_MPS_FLTB2:SCAN.VAL")
  field(INPB, "600")
  field(OUT, "ALRM:SYS0:SC_MPS_FLTB2:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:SC_MPS_FLTB2:ALHBCURR") {
  field(INP, "PHYS:SYS0:2:SCFaultBufferWatcher NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:SC_MPS_FLTB2:ALHBCHK")
}

record(calc, "ALRM:SYS0:SC_MPS_FLTB2:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:SC_MPS_FLTB2:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:SC_MPS_FLTB2:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:SC_MPS_FLTB2:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:SC_MPS_FLTB2:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:SC_MPS_FLTB2:ALHBERR") {
  field(DESC, "SC_MPS_FLTB2 monitoring")
  field(INP, "ALRM:SYS0:SC_MPS_FLTB2:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:SC_MPS_FLTB2:ALHBPREV")
}

record(ai, "ALRM:SYS0:SC_MPS_FLTB2:ALHBPREV") {
  field(INP, "ALRM:SYS0:SC_MPS_FLTB2:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:SC_MPS_FLTB3:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:SC_MPS_FLTB3:SCAN.VAL")
  field(INPB, "600")
  field(OUT, "ALRM:SYS0:SC_MPS_FLTB3:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:SC_MPS_FLTB3:ALHBCURR") {
  field(INP, "PHYS:SYS0:3:SCFaultBufferWatcher NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:SC_MPS_FLTB3:ALHBCHK")
}

record(calc, "ALRM:SYS0:SC_MPS_FLTB3:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:SC_MPS_FLTB3:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:SC_MPS_FLTB3:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:SC_MPS_FLTB3:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:SC_MPS_FLTB3:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:SC_MPS_FLTB3:ALHBERR") {
  field(DESC, "SC_MPS_FLTB3 monitoring")
  field(INP, "ALRM:SYS0:SC_MPS_FLTB3:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:SC_MPS_FLTB3:ALHBPREV")
}

record(ai, "ALRM:SYS0:SC_MPS_FLTB3:ALHBPREV") {
  field(INP, "ALRM:SYS0:SC_MPS_FLTB3:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:CU_HXR:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:CU_HXR:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:CU_HXR:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:CU_HXR:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML01:AO060 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:CU_HXR:ALHBCHK")
}

record(calc, "ALRM:SYS0:CU_HXR:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:CU_HXR:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:CU_HXR:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:CU_HXR:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:CU_HXR:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:CU_HXR:ALHBERR") {
  field(DESC, "CU_HXR monitoring")
  field(INP, "ALRM:SYS0:CU_HXR:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:CU_HXR:ALHBPREV")
}

record(ai, "ALRM:SYS0:CU_HXR:ALHBPREV") {
  field(INP, "ALRM:SYS0:CU_HXR:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:CU_SXR:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:CU_SXR:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:CU_SXR:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:CU_SXR:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML01:AO146 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:CU_SXR:ALHBCHK")
}

record(calc, "ALRM:SYS0:CU_SXR:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:CU_SXR:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:CU_SXR:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:CU_SXR:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:CU_SXR:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:CU_SXR:ALHBERR") {
  field(DESC, "CU_SXR monitoring")
  field(INP, "ALRM:SYS0:CU_SXR:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:CU_SXR:ALHBPREV")
}

record(ai, "ALRM:SYS0:CU_SXR:ALHBPREV") {
  field(INP, "ALRM:SYS0:CU_SXR:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:SC_HXR:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:SC_HXR:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:SC_HXR:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:SC_HXR:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML01:AO147 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:SC_HXR:ALHBCHK")
}

record(calc, "ALRM:SYS0:SC_HXR:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:SC_HXR:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:SC_HXR:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:SC_HXR:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:SC_HXR:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:SC_HXR:ALHBERR") {
  field(DESC, "SC_HXR monitoring")
  field(INP, "ALRM:SYS0:SC_HXR:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:SC_HXR:ALHBPREV")
}

record(ai, "ALRM:SYS0:SC_HXR:ALHBPREV") {
  field(INP, "ALRM:SYS0:SC_HXR:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:SC_SXR:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:SC_SXR:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:SC_SXR:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:SC_SXR:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML01:AO149 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:SC_SXR:ALHBCHK")
}

record(calc, "ALRM:SYS0:SC_SXR:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:SC_SXR:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:SC_SXR:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:SC_SXR:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:SC_SXR:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:SC_SXR:ALHBERR") {
  field(DESC, "SC_SXR monitoring")
  field(INP, "ALRM:SYS0:SC_SXR:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:SC_SXR:ALHBPREV")
}

record(ai, "ALRM:SYS0:SC_SXR:ALHBPREV") {
  field(INP, "ALRM:SYS0:SC_SXR:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:SC_BSYD:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:SC_BSYD:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:SC_BSYD:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:SC_BSYD:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML01:AO150 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:SC_BSYD:ALHBCHK")
}

record(calc, "ALRM:SYS0:SC_BSYD:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:SC_BSYD:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:SC_BSYD:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:SC_BSYD:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:SC_BSYD:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:SC_BSYD:ALHBERR") {
  field(DESC, "SC_BSYD monitoring")
  field(INP, "ALRM:SYS0:SC_BSYD:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:SC_BSYD:ALHBPREV")
}

record(ai, "ALRM:SYS0:SC_BSYD:ALHBPREV") {
  field(INP, "ALRM:SYS0:SC_BSYD:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:SC_DIAG0:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:SC_DIAG0:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:SC_DIAG0:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:SC_DIAG0:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML01:AO407 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:SC_DIAG0:ALHBCHK")
}

record(calc, "ALRM:SYS0:SC_DIAG0:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:SC_DIAG0:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:SC_DIAG0:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:SC_DIAG0:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:SC_DIAG0:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:SC_DIAG0:ALHBERR") {
  field(DESC, "SC_DIAG0 monitoring")
  field(INP, "ALRM:SYS0:SC_DIAG0:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:SC_DIAG0:ALHBPREV")
}

record(ai, "ALRM:SYS0:SC_DIAG0:ALHBPREV") {
  field(INP, "ALRM:SYS0:SC_DIAG0:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:BMOD_FB:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:BMOD_FB:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:BMOD_FB:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:BMOD_FB:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML01:AO019 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:BMOD_FB:ALHBCHK")
}

record(calc, "ALRM:SYS0:BMOD_FB:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:BMOD_FB:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:BMOD_FB:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:BMOD_FB:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:BMOD_FB:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:BMOD_FB:ALHBERR") {
  field(DESC, "BMOD_FB monitoring")
  field(INP, "ALRM:SYS0:BMOD_FB:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:BMOD_FB:ALHBPREV")
}

record(ai, "ALRM:SYS0:BMOD_FB:ALHBPREV") {
  field(INP, "ALRM:SYS0:BMOD_FB:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:CHRG_FB:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:CHRG_FB:SCAN.VAL")
  field(INPB, "10")
  field(OUT, "ALRM:SYS0:CHRG_FB:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:CHRG_FB:ALHBCURR") {
  field(INP, "PHYS:SYS0:1:CHRG_FB_WATCH NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:CHRG_FB:ALHBCHK")
}

record(calc, "ALRM:SYS0:CHRG_FB:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:CHRG_FB:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:CHRG_FB:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:CHRG_FB:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:CHRG_FB:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:CHRG_FB:ALHBERR") {
  field(DESC, "CHRG_FB monitoring")
  field(INP, "ALRM:SYS0:CHRG_FB:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:CHRG_FB:ALHBPREV")
}

record(ai, "ALRM:SYS0:CHRG_FB:ALHBPREV") {
  field(INP, "ALRM:SYS0:CHRG_FB:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:CU_CHRG_FB:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:CU_CHRG_FB:SCAN.VAL")
  field(INPB, "10")
  field(OUT, "ALRM:SYS0:CU_CHRG_FB:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:CU_CHRG_FB:ALHBCURR") {
  field(INP, "PHYS:SYS0:1:CU_CHRG_FB_WATCH NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:CU_CHRG_FB:ALHBCHK")
}

record(calc, "ALRM:SYS0:CU_CHRG_FB:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:CU_CHRG_FB:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:CU_CHRG_FB:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:CU_CHRG_FB:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:CU_CHRG_FB:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:CU_CHRG_FB:ALHBERR") {
  field(DESC, "CU_CHRG_FB monitoring")
  field(INP, "ALRM:SYS0:CU_CHRG_FB:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:CU_CHRG_FB:ALHBPREV")
}

record(ai, "ALRM:SYS0:CU_CHRG_FB:ALHBPREV") {
  field(INP, "ALRM:SYS0:CU_CHRG_FB:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:CU_LHWP_FBCK:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:CU_LHWP_FBCK:SCAN.VAL")
  field(INPB, "10")
  field(OUT, "ALRM:SYS0:CU_LHWP_FBCK:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:CU_LHWP_FBCK:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML03:AO105 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:CU_LHWP_FBCK:ALHBCHK")
}

record(calc, "ALRM:SYS0:CU_LHWP_FBCK:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:CU_LHWP_FBCK:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:CU_LHWP_FBCK:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:CU_LHWP_FBCK:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:CU_LHWP_FBCK:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:CU_LHWP_FBCK:ALHBERR") {
  field(DESC, "CU_LHWP_FBCK monitoring")
  field(INP, "ALRM:SYS0:CU_LHWP_FBCK:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:CU_LHWP_FBCK:ALHBPREV")
}

record(ai, "ALRM:SYS0:CU_LHWP_FBCK:ALHBPREV") {
  field(INP, "ALRM:SYS0:CU_LHWP_FBCK:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:SCGUN_GAIN_PHASE_FB:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:SCGUN_GAIN_PHASE_FB:SCAN.VAL")
  field(INPB, "15")
  field(OUT, "ALRM:SYS0:SCGUN_GAIN_PHASE_FB:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:SCGUN_GAIN_PHASE_FB:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML04:AO174 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:SCGUN_GAIN_PHASE_FB:ALHBCHK")
}

record(calc, "ALRM:SYS0:SCGUN_GAIN_PHASE_FB:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:SCGUN_GAIN_PHASE_FB:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:SCGUN_GAIN_PHASE_FB:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:SCGUN_GAIN_PHASE_FB:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:SCGUN_GAIN_PHASE_FB:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:SCGUN_GAIN_PHASE_FB:ALHBERR") {
  field(DESC, "SCGUN_GAIN_PHASE_FB monitoring")
  field(INP, "ALRM:SYS0:SCGUN_GAIN_PHASE_FB:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:SCGUN_GAIN_PHASE_FB:ALHBPREV")
}

record(ai, "ALRM:SYS0:SCGUN_GAIN_PHASE_FB:ALHBPREV") {
  field(INP, "ALRM:SYS0:SCGUN_GAIN_PHASE_FB:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:SC_LFB:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:SC_LFB:SCAN.VAL")
  field(INPB, "10")
  field(OUT, "ALRM:SYS0:SC_LFB:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:SC_LFB:ALHBCURR") {
  field(INP, "PHYS:SYS0:1:SC_LFB_WATCH NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:SC_LFB:ALHBCHK")
}

record(calc, "ALRM:SYS0:SC_LFB:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:SC_LFB:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:SC_LFB:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:SC_LFB:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:SC_LFB:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:SC_LFB:ALHBERR") {
  field(DESC, "SC_LFB monitoring")
  field(INP, "ALRM:SYS0:SC_LFB:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:SC_LFB:ALHBPREV")
}

record(ai, "ALRM:SYS0:SC_LFB:ALHBPREV") {
  field(INP, "ALRM:SYS0:SC_LFB:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:LEM_WAVEFORMS:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:LEM_WAVEFORMS:SCAN.VAL")
  field(INPB, "5")
  field(OUT, "ALRM:SYS0:LEM_WAVEFORMS:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:LEM_WAVEFORMS:ALHBCURR") {
  field(INP, "LEM:SYS0:1:WAVEFORMS_HB NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:LEM_WAVEFORMS:ALHBCHK")
}

record(calc, "ALRM:SYS0:LEM_WAVEFORMS:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:LEM_WAVEFORMS:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:LEM_WAVEFORMS:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:LEM_WAVEFORMS:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:LEM_WAVEFORMS:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:LEM_WAVEFORMS:ALHBERR") {
  field(DESC, "LEM_WAVEFORMS monitoring")
  field(INP, "ALRM:SYS0:LEM_WAVEFORMS:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:LEM_WAVEFORMS:ALHBPREV")
}

record(ai, "ALRM:SYS0:LEM_WAVEFORMS:ALHBPREV") {
  field(INP, "ALRM:SYS0:LEM_WAVEFORMS:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:PHCAVMON:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:PHCAVMON:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:PHCAVMON:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:PHCAVMON:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML00:AO027 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:PHCAVMON:ALHBCHK")
}

record(calc, "ALRM:SYS0:PHCAVMON:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:PHCAVMON:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:PHCAVMON:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:PHCAVMON:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:PHCAVMON:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:PHCAVMON:ALHBERR") {
  field(DESC, "PHCAVMON monitoring")
  field(INP, "ALRM:SYS0:PHCAVMON:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:PHCAVMON:ALHBPREV")
}

record(ai, "ALRM:SYS0:PHCAVMON:ALHBPREV") {
  field(INP, "ALRM:SYS0:PHCAVMON:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:MULTIKNOB:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:MULTIKNOB:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:MULTIKNOB:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:MULTIKNOB:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML00:AO039 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:MULTIKNOB:ALHBCHK")
}

record(calc, "ALRM:SYS0:MULTIKNOB:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:MULTIKNOB:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:MULTIKNOB:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:MULTIKNOB:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:MULTIKNOB:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:MULTIKNOB:ALHBERR") {
  field(DESC, "MULTIKNOB monitoring")
  field(INP, "ALRM:SYS0:MULTIKNOB:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:MULTIKNOB:ALHBPREV")
}

record(ai, "ALRM:SYS0:MULTIKNOB:ALHBPREV") {
  field(INP, "ALRM:SYS0:MULTIKNOB:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:LASRCAM:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:LASRCAM:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:LASRCAM:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:LASRCAM:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML00:AO068 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:LASRCAM:ALHBCHK")
}

record(calc, "ALRM:SYS0:LASRCAM:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:LASRCAM:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:LASRCAM:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:LASRCAM:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:LASRCAM:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:LASRCAM:ALHBERR") {
  field(DESC, "LASRCAM monitoring")
  field(INP, "ALRM:SYS0:LASRCAM:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:LASRCAM:ALHBPREV")
}

record(ai, "ALRM:SYS0:LASRCAM:ALHBPREV") {
  field(INP, "ALRM:SYS0:LASRCAM:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:LLRFARCH:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:LLRFARCH:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:LLRFARCH:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:LLRFARCH:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML00:AO250 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:LLRFARCH:ALHBCHK")
}

record(calc, "ALRM:SYS0:LLRFARCH:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:LLRFARCH:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:LLRFARCH:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:LLRFARCH:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:LLRFARCH:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:LLRFARCH:ALHBERR") {
  field(DESC, "LLRFARCH monitoring")
  field(INP, "ALRM:SYS0:LLRFARCH:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:LLRFARCH:ALHBPREV")
}

record(ai, "ALRM:SYS0:LLRFARCH:ALHBPREV") {
  field(INP, "ALRM:SYS0:LLRFARCH:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:KLYSCUD:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:KLYSCUD:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:KLYSCUD:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:KLYSCUD:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML00:AO321 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:KLYSCUD:ALHBCHK")
}

record(calc, "ALRM:SYS0:KLYSCUD:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:KLYSCUD:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:KLYSCUD:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:KLYSCUD:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:KLYSCUD:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:KLYSCUD:ALHBERR") {
  field(DESC, "KLYSCUD monitoring")
  field(INP, "ALRM:SYS0:KLYSCUD:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:KLYSCUD:ALHBPREV")
}

record(ai, "ALRM:SYS0:KLYSCUD:ALHBPREV") {
  field(INP, "ALRM:SYS0:KLYSCUD:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:TCAV_FBCK:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:TCAV_FBCK:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:TCAV_FBCK:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:TCAV_FBCK:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML00:AO397 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:TCAV_FBCK:ALHBCHK")
}

record(calc, "ALRM:SYS0:TCAV_FBCK:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:TCAV_FBCK:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:TCAV_FBCK:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:TCAV_FBCK:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:TCAV_FBCK:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:TCAV_FBCK:ALHBERR") {
  field(DESC, "TCAV_FBCK monitoring")
  field(INP, "ALRM:SYS0:TCAV_FBCK:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:TCAV_FBCK:ALHBPREV")
}

record(ai, "ALRM:SYS0:TCAV_FBCK:ALHBPREV") {
  field(INP, "ALRM:SYS0:TCAV_FBCK:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:24HOURCUD:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:24HOURCUD:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:24HOURCUD:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:24HOURCUD:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML00:AO322 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:24HOURCUD:ALHBCHK")
}

record(calc, "ALRM:SYS0:24HOURCUD:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:24HOURCUD:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:24HOURCUD:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:24HOURCUD:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:24HOURCUD:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:24HOURCUD:ALHBERR") {
  field(DESC, "24HOURCUD monitoring")
  field(INP, "ALRM:SYS0:24HOURCUD:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:24HOURCUD:ALHBPREV")
}

record(ai, "ALRM:SYS0:24HOURCUD:ALHBPREV") {
  field(INP, "ALRM:SYS0:24HOURCUD:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:OPUPDATE:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:OPUPDATE:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:OPUPDATE:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:OPUPDATE:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML00:AO323 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:OPUPDATE:ALHBCHK")
}

record(calc, "ALRM:SYS0:OPUPDATE:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:OPUPDATE:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:OPUPDATE:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:OPUPDATE:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:OPUPDATE:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:OPUPDATE:ALHBERR") {
  field(DESC, "OPUPDATE monitoring")
  field(INP, "ALRM:SYS0:OPUPDATE:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:OPUPDATE:ALHBPREV")
}

record(ai, "ALRM:SYS0:OPUPDATE:ALHBPREV") {
  field(INP, "ALRM:SYS0:OPUPDATE:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:GUARDIAN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:GUARDIAN:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:GUARDIAN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:GUARDIAN:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML00:AO451 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:GUARDIAN:ALHBCHK")
}

record(calc, "ALRM:SYS0:GUARDIAN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:GUARDIAN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:GUARDIAN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:GUARDIAN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:GUARDIAN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:GUARDIAN:ALHBERR") {
  field(DESC, "GUARDIAN monitoring")
  field(INP, "ALRM:SYS0:GUARDIAN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:GUARDIAN:ALHBPREV")
}

record(ai, "ALRM:SYS0:GUARDIAN:ALHBPREV") {
  field(INP, "ALRM:SYS0:GUARDIAN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:DUMP_E:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:DUMP_E:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:DUMP_E:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:DUMP_E:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML00:AO559 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:DUMP_E:ALHBCHK")
}

record(calc, "ALRM:SYS0:DUMP_E:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:DUMP_E:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:DUMP_E:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:DUMP_E:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:DUMP_E:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:DUMP_E:ALHBERR") {
  field(DESC, "DUMP_E monitoring")
  field(INP, "ALRM:SYS0:DUMP_E:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:DUMP_E:ALHBPREV")
}

record(ai, "ALRM:SYS0:DUMP_E:ALHBPREV") {
  field(INP, "ALRM:SYS0:DUMP_E:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:MDL_L2FB:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:MDL_L2FB:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:MDL_L2FB:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:MDL_L2FB:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML00:AO520 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:MDL_L2FB:ALHBCHK")
}

record(calc, "ALRM:SYS0:MDL_L2FB:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:MDL_L2FB:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:MDL_L2FB:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:MDL_L2FB:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:MDL_L2FB:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:MDL_L2FB:ALHBERR") {
  field(DESC, "MDL_L2FB monitoring")
  field(INP, "ALRM:SYS0:MDL_L2FB:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:MDL_L2FB:ALHBPREV")
}

record(ai, "ALRM:SYS0:MDL_L2FB:ALHBPREV") {
  field(INP, "ALRM:SYS0:MDL_L2FB:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:BAT:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:BAT:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:BAT:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:BAT:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML00:AO751 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:BAT:ALHBCHK")
}

record(calc, "ALRM:SYS0:BAT:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:BAT:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:BAT:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:BAT:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:BAT:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:BAT:ALHBERR") {
  field(DESC, "BAT monitoring")
  field(INP, "ALRM:SYS0:BAT:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:BAT:ALHBPREV")
}

record(ai, "ALRM:SYS0:BAT:ALHBPREV") {
  field(INP, "ALRM:SYS0:BAT:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:JITTERCUD:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:JITTERCUD:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:JITTERCUD:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:JITTERCUD:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML00:AO516 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:JITTERCUD:ALHBCHK")
}

record(calc, "ALRM:SYS0:JITTERCUD:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:JITTERCUD:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:JITTERCUD:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:JITTERCUD:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:JITTERCUD:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:JITTERCUD:ALHBERR") {
  field(DESC, "JITTERCUD monitoring")
  field(INP, "ALRM:SYS0:JITTERCUD:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:JITTERCUD:ALHBPREV")
}

record(ai, "ALRM:SYS0:JITTERCUD:ALHBPREV") {
  field(INP, "ALRM:SYS0:JITTERCUD:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:PHENGYCTRL:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:PHENGYCTRL:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:PHENGYCTRL:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:PHENGYCTRL:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML00:AO858 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:PHENGYCTRL:ALHBCHK")
}

record(calc, "ALRM:SYS0:PHENGYCTRL:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:PHENGYCTRL:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:PHENGYCTRL:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:PHENGYCTRL:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:PHENGYCTRL:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:PHENGYCTRL:ALHBERR") {
  field(DESC, "PHENGYCTRL monitoring")
  field(INP, "ALRM:SYS0:PHENGYCTRL:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:PHENGYCTRL:ALHBPREV")
}

record(ai, "ALRM:SYS0:PHENGYCTRL:ALHBPREV") {
  field(INP, "ALRM:SYS0:PHENGYCTRL:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:FASTLOG:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:FASTLOG:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:FASTLOG:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:FASTLOG:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML00:AO605 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:FASTLOG:ALHBCHK")
}

record(calc, "ALRM:SYS0:FASTLOG:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:FASTLOG:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:FASTLOG:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:FASTLOG:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:FASTLOG:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:FASTLOG:ALHBERR") {
  field(DESC, "FASTLOG monitoring")
  field(INP, "ALRM:SYS0:FASTLOG:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:FASTLOG:ALHBPREV")
}

record(ai, "ALRM:SYS0:FASTLOG:ALHBPREV") {
  field(INP, "ALRM:SYS0:FASTLOG:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:TIMESLTCHK:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:TIMESLTCHK:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:TIMESLTCHK:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:TIMESLTCHK:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML01:AO250 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:TIMESLTCHK:ALHBCHK")
}

record(calc, "ALRM:SYS0:TIMESLTCHK:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:TIMESLTCHK:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:TIMESLTCHK:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:TIMESLTCHK:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:TIMESLTCHK:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:TIMESLTCHK:ALHBERR") {
  field(DESC, "TIMESLTCHK monitoring")
  field(INP, "ALRM:SYS0:TIMESLTCHK:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:TIMESLTCHK:ALHBPREV")
}

record(ai, "ALRM:SYS0:TIMESLTCHK:ALHBPREV") {
  field(INP, "ALRM:SYS0:TIMESLTCHK:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:GDETSATMON:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:GDETSATMON:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:GDETSATMON:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:GDETSATMON:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML00:AO734 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:GDETSATMON:ALHBCHK")
}

record(calc, "ALRM:SYS0:GDETSATMON:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:GDETSATMON:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:GDETSATMON:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:GDETSATMON:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:GDETSATMON:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:GDETSATMON:ALHBERR") {
  field(DESC, "GDETSATMON monitoring")
  field(INP, "ALRM:SYS0:GDETSATMON:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:GDETSATMON:ALHBPREV")
}

record(ai, "ALRM:SYS0:GDETSATMON:ALHBPREV") {
  field(INP, "ALRM:SYS0:GDETSATMON:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:CUD2WEB:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:CUD2WEB:SCAN.VAL")
  field(INPB, "330")
  field(OUT, "ALRM:SYS0:CUD2WEB:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:CUD2WEB:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML00:AO994 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:CUD2WEB:ALHBCHK")
}

record(calc, "ALRM:SYS0:CUD2WEB:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:CUD2WEB:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:CUD2WEB:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:CUD2WEB:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:CUD2WEB:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:CUD2WEB:ALHBERR") {
  field(DESC, "CUD2WEB monitoring")
  field(INP, "ALRM:SYS0:CUD2WEB:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:CUD2WEB:ALHBPREV")
}

record(ai, "ALRM:SYS0:CUD2WEB:ALHBPREV") {
  field(INP, "ALRM:SYS0:CUD2WEB:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:BPMDISP_CU_HXR:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:BPMDISP_CU_HXR:SCAN.VAL")
  field(INPB, "60")
  field(OUT, "ALRM:SYS0:BPMDISP_CU_HXR:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:BPMDISP_CU_HXR:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML01:AO071 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:BPMDISP_CU_HXR:ALHBCHK")
}

record(calc, "ALRM:SYS0:BPMDISP_CU_HXR:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:BPMDISP_CU_HXR:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:BPMDISP_CU_HXR:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:BPMDISP_CU_HXR:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:BPMDISP_CU_HXR:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:BPMDISP_CU_HXR:ALHBERR") {
  field(DESC, "BPMDISP_CU_HXR monitoring")
  field(INP, "ALRM:SYS0:BPMDISP_CU_HXR:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:BPMDISP_CU_HXR:ALHBPREV")
}

record(ai, "ALRM:SYS0:BPMDISP_CU_HXR:ALHBPREV") {
  field(INP, "ALRM:SYS0:BPMDISP_CU_HXR:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:BPMDISP_CU_SXR:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:BPMDISP_CU_SXR:SCAN.VAL")
  field(INPB, "60")
  field(OUT, "ALRM:SYS0:BPMDISP_CU_SXR:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:BPMDISP_CU_SXR:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML02:AO177 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:BPMDISP_CU_SXR:ALHBCHK")
}

record(calc, "ALRM:SYS0:BPMDISP_CU_SXR:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:BPMDISP_CU_SXR:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:BPMDISP_CU_SXR:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:BPMDISP_CU_SXR:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:BPMDISP_CU_SXR:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:BPMDISP_CU_SXR:ALHBERR") {
  field(DESC, "BPMDISP_CU_SXR monitoring")
  field(INP, "ALRM:SYS0:BPMDISP_CU_SXR:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:BPMDISP_CU_SXR:ALHBPREV")
}

record(ai, "ALRM:SYS0:BPMDISP_CU_SXR:ALHBPREV") {
  field(INP, "ALRM:SYS0:BPMDISP_CU_SXR:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:MCCHAMMER:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:MCCHAMMER:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:MCCHAMMER:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:MCCHAMMER:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML02:AO005 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:MCCHAMMER:ALHBCHK")
}

record(calc, "ALRM:SYS0:MCCHAMMER:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:MCCHAMMER:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:MCCHAMMER:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:MCCHAMMER:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:MCCHAMMER:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:MCCHAMMER:ALHBERR") {
  field(DESC, "MCCHAMMER monitoring")
  field(INP, "ALRM:SYS0:MCCHAMMER:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:MCCHAMMER:ALHBPREV")
}

record(ai, "ALRM:SYS0:MCCHAMMER:ALHBPREV") {
  field(INP, "ALRM:SYS0:MCCHAMMER:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:E_GAIN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:E_GAIN:SCAN.VAL")
  field(INPB, "600")
  field(OUT, "ALRM:SYS0:E_GAIN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:E_GAIN:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML01:AO624 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:E_GAIN:ALHBCHK")
}

record(calc, "ALRM:SYS0:E_GAIN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:E_GAIN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:E_GAIN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:E_GAIN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:E_GAIN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:E_GAIN:ALHBERR") {
  field(DESC, "E_GAIN monitoring")
  field(INP, "ALRM:SYS0:E_GAIN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:E_GAIN:ALHBPREV")
}

record(ai, "ALRM:SYS0:E_GAIN:ALHBPREV") {
  field(INP, "ALRM:SYS0:E_GAIN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:SBAND_DIAG:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:SBAND_DIAG:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:SBAND_DIAG:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:SBAND_DIAG:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML01:AO667 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:SBAND_DIAG:ALHBCHK")
}

record(calc, "ALRM:SYS0:SBAND_DIAG:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:SBAND_DIAG:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:SBAND_DIAG:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:SBAND_DIAG:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:SBAND_DIAG:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:SBAND_DIAG:ALHBERR") {
  field(DESC, "SBAND_DIAG monitoring")
  field(INP, "ALRM:SYS0:SBAND_DIAG:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:SBAND_DIAG:ALHBPREV")
}

record(ai, "ALRM:SYS0:SBAND_DIAG:ALHBPREV") {
  field(INP, "ALRM:SYS0:SBAND_DIAG:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:SBAND_DIAG_DMP:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:SBAND_DIAG_DMP:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:SBAND_DIAG_DMP:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:SBAND_DIAG_DMP:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML01:AO666 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:SBAND_DIAG_DMP:ALHBCHK")
}

record(calc, "ALRM:SYS0:SBAND_DIAG_DMP:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:SBAND_DIAG_DMP:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:SBAND_DIAG_DMP:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:SBAND_DIAG_DMP:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:SBAND_DIAG_DMP:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:SBAND_DIAG_DMP:ALHBERR") {
  field(DESC, "SBAND_DIAG_DMP monitoring")
  field(INP, "ALRM:SYS0:SBAND_DIAG_DMP:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:SBAND_DIAG_DMP:ALHBPREV")
}

record(ai, "ALRM:SYS0:SBAND_DIAG_DMP:ALHBPREV") {
  field(INP, "ALRM:SYS0:SBAND_DIAG_DMP:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:LEM_TRIM:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:LEM_TRIM:SCAN.VAL")
  field(INPB, "2")
  field(OUT, "ALRM:SYS0:LEM_TRIM:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:LEM_TRIM:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML01:AO140 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:LEM_TRIM:ALHBCHK")
}

record(calc, "ALRM:SYS0:LEM_TRIM:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:LEM_TRIM:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:LEM_TRIM:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:LEM_TRIM:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:LEM_TRIM:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:LEM_TRIM:ALHBERR") {
  field(DESC, "LEM_TRIM monitoring")
  field(INP, "ALRM:SYS0:LEM_TRIM:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:LEM_TRIM:ALHBPREV")
}

record(ai, "ALRM:SYS0:LEM_TRIM:ALHBPREV") {
  field(INP, "ALRM:SYS0:LEM_TRIM:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:PROFMON:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:PROFMON:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:PROFMON:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:PROFMON:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML01:AO719 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:PROFMON:ALHBCHK")
}

record(calc, "ALRM:SYS0:PROFMON:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:PROFMON:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:PROFMON:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:PROFMON:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:PROFMON:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:PROFMON:ALHBERR") {
  field(DESC, "PROFMON monitoring")
  field(INP, "ALRM:SYS0:PROFMON:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:PROFMON:ALHBPREV")
}

record(ai, "ALRM:SYS0:PROFMON:ALHBPREV") {
  field(INP, "ALRM:SYS0:PROFMON:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:XTCAVFBCK:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:XTCAVFBCK:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:XTCAVFBCK:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:XTCAVFBCK:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML01:AO162 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:XTCAVFBCK:ALHBCHK")
}

record(calc, "ALRM:SYS0:XTCAVFBCK:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:XTCAVFBCK:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:XTCAVFBCK:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:XTCAVFBCK:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:XTCAVFBCK:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:XTCAVFBCK:ALHBERR") {
  field(DESC, "XTCAVFBCK monitoring")
  field(INP, "ALRM:SYS0:XTCAVFBCK:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:XTCAVFBCK:ALHBPREV")
}

record(ai, "ALRM:SYS0:XTCAVFBCK:ALHBPREV") {
  field(INP, "ALRM:SYS0:XTCAVFBCK:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:XTCAVBFBCK:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:XTCAVBFBCK:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:XTCAVBFBCK:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:XTCAVBFBCK:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML05:AO162 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:XTCAVBFBCK:ALHBCHK")
}

record(calc, "ALRM:SYS0:XTCAVBFBCK:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:XTCAVBFBCK:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:XTCAVBFBCK:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:XTCAVBFBCK:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:XTCAVBFBCK:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:XTCAVBFBCK:ALHBERR") {
  field(DESC, "XTCAVBFBCK monitoring")
  field(INP, "ALRM:SYS0:XTCAVBFBCK:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:XTCAVBFBCK:ALHBPREV")
}

record(ai, "ALRM:SYS0:XTCAVBFBCK:ALHBPREV") {
  field(INP, "ALRM:SYS0:XTCAVBFBCK:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:VITARA1:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:VITARA1:SCAN.VAL")
  field(INPB, "10")
  field(OUT, "ALRM:SYS0:VITARA1:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:VITARA1:ALHBCURR") {
  field(INP, "OSC:LR20:20:FS_WATCHDOG NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:VITARA1:ALHBCHK")
}

record(calc, "ALRM:SYS0:VITARA1:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:VITARA1:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:VITARA1:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:VITARA1:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:VITARA1:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:VITARA1:ALHBERR") {
  field(DESC, "VITARA1 monitoring")
  field(INP, "ALRM:SYS0:VITARA1:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:VITARA1:ALHBPREV")
}

record(ai, "ALRM:SYS0:VITARA1:ALHBPREV") {
  field(INP, "ALRM:SYS0:VITARA1:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:VITARA2:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:VITARA2:SCAN.VAL")
  field(INPB, "10")
  field(OUT, "ALRM:SYS0:VITARA2:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:VITARA2:ALHBCURR") {
  field(INP, "OSC:LR20:10:FS_WATCHDOG NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:VITARA2:ALHBCHK")
}

record(calc, "ALRM:SYS0:VITARA2:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:VITARA2:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:VITARA2:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:VITARA2:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:VITARA2:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:VITARA2:ALHBERR") {
  field(DESC, "VITARA2 monitoring")
  field(INP, "ALRM:SYS0:VITARA2:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:VITARA2:ALHBPREV")
}

record(ai, "ALRM:SYS0:VITARA2:ALHBPREV") {
  field(INP, "ALRM:SYS0:VITARA2:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:FEL_PLS_EM:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:FEL_PLS_EM:SCAN.VAL")
  field(INPB, "5")
  field(OUT, "ALRM:SYS0:FEL_PLS_EM:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:FEL_PLS_EM:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML00:AO000 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:FEL_PLS_EM:ALHBCHK")
}

record(calc, "ALRM:SYS0:FEL_PLS_EM:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:FEL_PLS_EM:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:FEL_PLS_EM:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:FEL_PLS_EM:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:FEL_PLS_EM:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:FEL_PLS_EM:ALHBERR") {
  field(DESC, "FEL_PLS_EM monitoring")
  field(INP, "ALRM:SYS0:FEL_PLS_EM:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:FEL_PLS_EM:ALHBPREV")
}

record(ai, "ALRM:SYS0:FEL_PLS_EM:ALHBPREV") {
  field(INP, "ALRM:SYS0:FEL_PLS_EM:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:OTRDMPMON:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:OTRDMPMON:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:OTRDMPMON:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:OTRDMPMON:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML01:AO424 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:OTRDMPMON:ALHBCHK")
}

record(calc, "ALRM:SYS0:OTRDMPMON:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:OTRDMPMON:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:OTRDMPMON:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:OTRDMPMON:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:OTRDMPMON:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:OTRDMPMON:ALHBERR") {
  field(DESC, "OTRDMPMON monitoring")
  field(INP, "ALRM:SYS0:OTRDMPMON:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:OTRDMPMON:ALHBPREV")
}

record(ai, "ALRM:SYS0:OTRDMPMON:ALHBPREV") {
  field(INP, "ALRM:SYS0:OTRDMPMON:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:TCAV0_MODE:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:TCAV0_MODE:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:TCAV0_MODE:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:TCAV0_MODE:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML00:AO991 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:TCAV0_MODE:ALHBCHK")
}

record(calc, "ALRM:SYS0:TCAV0_MODE:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:TCAV0_MODE:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:TCAV0_MODE:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:TCAV0_MODE:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:TCAV0_MODE:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:TCAV0_MODE:ALHBERR") {
  field(DESC, "TCAV0_MODE monitoring")
  field(INP, "ALRM:SYS0:TCAV0_MODE:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:TCAV0_MODE:ALHBPREV")
}

record(ai, "ALRM:SYS0:TCAV0_MODE:ALHBPREV") {
  field(INP, "ALRM:SYS0:TCAV0_MODE:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:PMORBITCHK:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:PMORBITCHK:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:PMORBITCHK:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:PMORBITCHK:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML01:AO249 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:PMORBITCHK:ALHBCHK")
}

record(calc, "ALRM:SYS0:PMORBITCHK:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:PMORBITCHK:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:PMORBITCHK:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:PMORBITCHK:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:PMORBITCHK:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:PMORBITCHK:ALHBERR") {
  field(DESC, "PMORBITCHK monitoring")
  field(INP, "ALRM:SYS0:PMORBITCHK:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:PMORBITCHK:ALHBPREV")
}

record(ai, "ALRM:SYS0:PMORBITCHK:ALHBPREV") {
  field(INP, "ALRM:SYS0:PMORBITCHK:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:GUI_HRTBT:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:GUI_HRTBT:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:GUI_HRTBT:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:GUI_HRTBT:ALHBCURR") {
  field(INP, "MPS:SYS0:1:GUI_HRTBT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:GUI_HRTBT:ALHBCHK")
}

record(calc, "ALRM:SYS0:GUI_HRTBT:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:GUI_HRTBT:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:GUI_HRTBT:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:GUI_HRTBT:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:GUI_HRTBT:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:GUI_HRTBT:ALHBERR") {
  field(DESC, "GUI_HRTBT monitoring")
  field(INP, "ALRM:SYS0:GUI_HRTBT:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:GUI_HRTBT:ALHBPREV")
}

record(ai, "ALRM:SYS0:GUI_HRTBT:ALHBPREV") {
  field(INP, "ALRM:SYS0:GUI_HRTBT:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:MPSTRIPWATC:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:MPSTRIPWATC:SCAN.VAL")
  field(INPB, "15")
  field(OUT, "ALRM:SYS0:MPSTRIPWATC:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:MPSTRIPWATC:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML00:AO440 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:MPSTRIPWATC:ALHBCHK")
}

record(calc, "ALRM:SYS0:MPSTRIPWATC:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:MPSTRIPWATC:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:MPSTRIPWATC:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:MPSTRIPWATC:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:MPSTRIPWATC:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:MPSTRIPWATC:ALHBERR") {
  field(DESC, "MPSTRIPWATC monitoring")
  field(INP, "ALRM:SYS0:MPSTRIPWATC:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:MPSTRIPWATC:ALHBPREV")
}

record(ai, "ALRM:SYS0:MPSTRIPWATC:ALHBPREV") {
  field(INP, "ALRM:SYS0:MPSTRIPWATC:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:ENJITT_TOL:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:ENJITT_TOL:SCAN.VAL")
  field(INPB, "15")
  field(OUT, "ALRM:SYS0:ENJITT_TOL:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:ENJITT_TOL:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML01:AO535 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:ENJITT_TOL:ALHBCHK")
}

record(calc, "ALRM:SYS0:ENJITT_TOL:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:ENJITT_TOL:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:ENJITT_TOL:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:ENJITT_TOL:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:ENJITT_TOL:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:ENJITT_TOL:ALHBERR") {
  field(DESC, "ENJITT_TOL monitoring")
  field(INP, "ALRM:SYS0:ENJITT_TOL:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:ENJITT_TOL:ALHBPREV")
}

record(ai, "ALRM:SYS0:ENJITT_TOL:ALHBPREV") {
  field(INP, "ALRM:SYS0:ENJITT_TOL:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:UND1BUMPSRV:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:UND1BUMPSRV:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:UND1BUMPSRV:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:UND1BUMPSRV:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML03:AO630 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:UND1BUMPSRV:ALHBCHK")
}

record(calc, "ALRM:SYS0:UND1BUMPSRV:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:UND1BUMPSRV:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:UND1BUMPSRV:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:UND1BUMPSRV:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:UND1BUMPSRV:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:UND1BUMPSRV:ALHBERR") {
  field(DESC, "UND1BUMPSRV monitoring")
  field(INP, "ALRM:SYS0:UND1BUMPSRV:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:UND1BUMPSRV:ALHBPREV")
}

record(ai, "ALRM:SYS0:UND1BUMPSRV:ALHBPREV") {
  field(INP, "ALRM:SYS0:UND1BUMPSRV:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:FAST_ORBIT:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:FAST_ORBIT:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:FAST_ORBIT:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:FAST_ORBIT:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML02:AO761 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:FAST_ORBIT:ALHBCHK")
}

record(calc, "ALRM:SYS0:FAST_ORBIT:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:FAST_ORBIT:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:FAST_ORBIT:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:FAST_ORBIT:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:FAST_ORBIT:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:FAST_ORBIT:ALHBERR") {
  field(DESC, "FAST_ORBIT monitoring")
  field(INP, "ALRM:SYS0:FAST_ORBIT:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:FAST_ORBIT:ALHBPREV")
}

record(ai, "ALRM:SYS0:FAST_ORBIT:ALHBPREV") {
  field(INP, "ALRM:SYS0:FAST_ORBIT:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:PCAV_DIAG:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:PCAV_DIAG:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:PCAV_DIAG:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:PCAV_DIAG:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML02:AO802 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:PCAV_DIAG:ALHBCHK")
}

record(calc, "ALRM:SYS0:PCAV_DIAG:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:PCAV_DIAG:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:PCAV_DIAG:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:PCAV_DIAG:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:PCAV_DIAG:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:PCAV_DIAG:ALHBERR") {
  field(DESC, "PCAV_DIAG monitoring")
  field(INP, "ALRM:SYS0:PCAV_DIAG:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:PCAV_DIAG:ALHBPREV")
}

record(ai, "ALRM:SYS0:PCAV_DIAG:ALHBPREV") {
  field(INP, "ALRM:SYS0:PCAV_DIAG:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:ML_IMG_ARCH:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:ML_IMG_ARCH:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:ML_IMG_ARCH:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:ML_IMG_ARCH:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML03:AO091 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:ML_IMG_ARCH:ALHBCHK")
}

record(calc, "ALRM:SYS0:ML_IMG_ARCH:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:ML_IMG_ARCH:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:ML_IMG_ARCH:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:ML_IMG_ARCH:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:ML_IMG_ARCH:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:ML_IMG_ARCH:ALHBERR") {
  field(DESC, "ML_IMG_ARCH monitoring")
  field(INP, "ALRM:SYS0:ML_IMG_ARCH:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:ML_IMG_ARCH:ALHBPREV")
}

record(ai, "ALRM:SYS0:ML_IMG_ARCH:ALHBPREV") {
  field(INP, "ALRM:SYS0:ML_IMG_ARCH:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:BLEM2EPICS:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:BLEM2EPICS:SCAN.VAL")
  field(INPB, "30")
  field(OUT, "ALRM:SYS0:BLEM2EPICS:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:BLEM2EPICS:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML01:AO004 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:BLEM2EPICS:ALHBCHK")
}

record(calc, "ALRM:SYS0:BLEM2EPICS:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:BLEM2EPICS:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:BLEM2EPICS:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:BLEM2EPICS:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:BLEM2EPICS:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:BLEM2EPICS:ALHBERR") {
  field(DESC, "BLEM2EPICS monitoring")
  field(INP, "ALRM:SYS0:BLEM2EPICS:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:BLEM2EPICS:ALHBPREV")
}

record(ai, "ALRM:SYS0:BLEM2EPICS:ALHBPREV") {
  field(INP, "ALRM:SYS0:BLEM2EPICS:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:MOFREQLOCK:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:MOFREQLOCK:SCAN.VAL")
  field(INPB, "5")
  field(OUT, "ALRM:SYS0:MOFREQLOCK:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:MOFREQLOCK:ALHBCURR") {
  field(INP, "SIOC:SYS0:ML03:AO897 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:MOFREQLOCK:ALHBCHK")
}

record(calc, "ALRM:SYS0:MOFREQLOCK:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:MOFREQLOCK:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:MOFREQLOCK:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:MOFREQLOCK:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:MOFREQLOCK:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:MOFREQLOCK:ALHBERR") {
  field(DESC, "MO freq locker monitoring")
  field(INP, "ALRM:SYS0:MOFREQLOCK:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:MOFREQLOCK:ALHBPREV")
}

record(ai, "ALRM:SYS0:MOFREQLOCK:ALHBPREV") {
  field(INP, "ALRM:SYS0:MOFREQLOCK:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:AMPLITUDE1:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:AMPLITUDE1:SCAN.VAL")
  field(INPB, "10")
  field(OUT, "ALRM:SYS0:AMPLITUDE1:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:AMPLITUDE1:ALHBCURR") {
  field(INP, "OSC:LGUN:100:FS_WATCHDOG NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:AMPLITUDE1:ALHBCHK")
}

record(calc, "ALRM:SYS0:AMPLITUDE1:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:AMPLITUDE1:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:AMPLITUDE1:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:AMPLITUDE1:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:AMPLITUDE1:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:AMPLITUDE1:ALHBERR") {
  field(DESC, "AMPLITUDE1 monitoring")
  field(INP, "ALRM:SYS0:AMPLITUDE1:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:AMPLITUDE1:ALHBPREV")
}

record(ai, "ALRM:SYS0:AMPLITUDE1:ALHBPREV") {
  field(INP, "ALRM:SYS0:AMPLITUDE1:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:AMPLITUDE2:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:AMPLITUDE2:SCAN.VAL")
  field(INPB, "10")
  field(OUT, "ALRM:SYS0:AMPLITUDE2:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:AMPLITUDE2:ALHBCURR") {
  field(INP, "OSC:LHTR:100:FS_WATCHDOG NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:AMPLITUDE2:ALHBCHK")
}

record(calc, "ALRM:SYS0:AMPLITUDE2:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:AMPLITUDE2:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:AMPLITUDE2:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:AMPLITUDE2:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:AMPLITUDE2:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:AMPLITUDE2:ALHBERR") {
  field(DESC, "AMPLITUDE2 monitoring")
  field(INP, "ALRM:SYS0:AMPLITUDE2:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:AMPLITUDE2:ALHBPREV")
}

record(ai, "ALRM:SYS0:AMPLITUDE2:ALHBPREV") {
  field(INP, "ALRM:SYS0:AMPLITUDE2:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCM01DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCM01DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCM01DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCM01DMN:ALHBCURR") {
  field(INP, "ACCL:L0B:0100:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCM01DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCM01DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCM01DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCM01DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCM01DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCM01DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCM01DMN:ALHBERR") {
  field(DESC, "RFCM01DMN monitoring")
  field(INP, "ALRM:SYS0:RFCM01DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCM01DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCM01DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCM01DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCM02DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCM02DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCM02DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCM02DMN:ALHBCURR") {
  field(INP, "ACCL:L1B:0200:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCM02DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCM02DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCM02DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCM02DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCM02DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCM02DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCM02DMN:ALHBERR") {
  field(DESC, "RFCM02DMN monitoring")
  field(INP, "ALRM:SYS0:RFCM02DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCM02DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCM02DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCM02DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCM03DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCM03DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCM03DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCM03DMN:ALHBCURR") {
  field(INP, "ACCL:L1B:0300:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCM03DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCM03DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCM03DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCM03DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCM03DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCM03DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCM03DMN:ALHBERR") {
  field(DESC, "RFCM03DMN monitoring")
  field(INP, "ALRM:SYS0:RFCM03DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCM03DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCM03DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCM03DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCMH1DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCMH1DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCMH1DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCMH1DMN:ALHBCURR") {
  field(INP, "ACCL:L1B:H100:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCMH1DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCMH1DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCMH1DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCMH1DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCMH1DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCMH1DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCMH1DMN:ALHBERR") {
  field(DESC, "RFCMH1DMN monitoring")
  field(INP, "ALRM:SYS0:RFCMH1DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCMH1DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCMH1DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCMH1DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCMH2DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCMH2DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCMH2DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCMH2DMN:ALHBCURR") {
  field(INP, "ACCL:L1B:H200:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCMH2DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCMH2DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCMH2DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCMH2DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCMH2DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCMH2DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCMH2DMN:ALHBERR") {
  field(DESC, "RFCMH2DMN monitoring")
  field(INP, "ALRM:SYS0:RFCMH2DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCMH2DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCMH2DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCMH2DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCM04DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCM04DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCM04DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCM04DMN:ALHBCURR") {
  field(INP, "ACCL:L2B:0400:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCM04DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCM04DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCM04DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCM04DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCM04DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCM04DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCM04DMN:ALHBERR") {
  field(DESC, "RFCM04DMN monitoring")
  field(INP, "ALRM:SYS0:RFCM04DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCM04DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCM04DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCM04DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCM05DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCM05DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCM05DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCM05DMN:ALHBCURR") {
  field(INP, "ACCL:L2B:0500:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCM05DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCM05DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCM05DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCM05DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCM05DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCM05DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCM05DMN:ALHBERR") {
  field(DESC, "RFCM05DMN monitoring")
  field(INP, "ALRM:SYS0:RFCM05DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCM05DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCM05DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCM05DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCM06DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCM06DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCM06DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCM06DMN:ALHBCURR") {
  field(INP, "ACCL:L2B:0600:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCM06DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCM06DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCM06DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCM06DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCM06DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCM06DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCM06DMN:ALHBERR") {
  field(DESC, "RFCM06DMN monitoring")
  field(INP, "ALRM:SYS0:RFCM06DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCM06DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCM06DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCM06DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCM07DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCM07DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCM07DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCM07DMN:ALHBCURR") {
  field(INP, "ACCL:L2B:0700:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCM07DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCM07DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCM07DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCM07DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCM07DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCM07DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCM07DMN:ALHBERR") {
  field(DESC, "RFCM07DMN monitoring")
  field(INP, "ALRM:SYS0:RFCM07DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCM07DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCM07DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCM07DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCM08DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCM08DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCM08DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCM08DMN:ALHBCURR") {
  field(INP, "ACCL:L2B:0800:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCM08DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCM08DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCM08DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCM08DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCM08DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCM08DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCM08DMN:ALHBERR") {
  field(DESC, "RFCM08DMN monitoring")
  field(INP, "ALRM:SYS0:RFCM08DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCM08DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCM08DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCM08DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCM09DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCM09DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCM09DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCM09DMN:ALHBCURR") {
  field(INP, "ACCL:L2B:0900:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCM09DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCM09DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCM09DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCM09DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCM09DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCM09DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCM09DMN:ALHBERR") {
  field(DESC, "RFCM09DMN monitoring")
  field(INP, "ALRM:SYS0:RFCM09DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCM09DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCM09DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCM09DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCM10DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCM10DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCM10DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCM10DMN:ALHBCURR") {
  field(INP, "ACCL:L2B:1000:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCM10DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCM10DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCM10DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCM10DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCM10DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCM10DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCM10DMN:ALHBERR") {
  field(DESC, "RFCM10DMN monitoring")
  field(INP, "ALRM:SYS0:RFCM10DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCM10DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCM10DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCM10DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCM11DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCM11DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCM11DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCM11DMN:ALHBCURR") {
  field(INP, "ACCL:L2B:1100:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCM11DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCM11DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCM11DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCM11DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCM11DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCM11DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCM11DMN:ALHBERR") {
  field(DESC, "RFCM11DMN monitoring")
  field(INP, "ALRM:SYS0:RFCM11DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCM11DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCM11DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCM11DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCM12DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCM12DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCM12DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCM12DMN:ALHBCURR") {
  field(INP, "ACCL:L2B:1200:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCM12DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCM12DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCM12DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCM12DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCM12DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCM12DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCM12DMN:ALHBERR") {
  field(DESC, "RFCM12DMN monitoring")
  field(INP, "ALRM:SYS0:RFCM12DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCM12DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCM12DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCM12DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCM13DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCM13DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCM13DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCM13DMN:ALHBCURR") {
  field(INP, "ACCL:L2B:1300:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCM13DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCM13DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCM13DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCM13DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCM13DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCM13DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCM13DMN:ALHBERR") {
  field(DESC, "RFCM13DMN monitoring")
  field(INP, "ALRM:SYS0:RFCM13DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCM13DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCM13DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCM13DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCM14DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCM14DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCM14DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCM14DMN:ALHBCURR") {
  field(INP, "ACCL:L2B:1400:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCM14DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCM14DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCM14DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCM14DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCM14DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCM14DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCM14DMN:ALHBERR") {
  field(DESC, "RFCM14DMN monitoring")
  field(INP, "ALRM:SYS0:RFCM14DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCM14DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCM14DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCM14DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCM15DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCM15DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCM15DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCM15DMN:ALHBCURR") {
  field(INP, "ACCL:L2B:1500:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCM15DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCM15DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCM15DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCM15DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCM15DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCM15DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCM15DMN:ALHBERR") {
  field(DESC, "RFCM15DMN monitoring")
  field(INP, "ALRM:SYS0:RFCM15DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCM15DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCM15DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCM15DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCM16DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCM16DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCM16DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCM16DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:1600:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCM16DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCM16DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCM16DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCM16DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCM16DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCM16DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCM16DMN:ALHBERR") {
  field(DESC, "RFCM16DMN monitoring")
  field(INP, "ALRM:SYS0:RFCM16DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCM16DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCM16DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCM16DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCM17DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCM17DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCM17DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCM17DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:1700:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCM17DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCM17DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCM17DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCM17DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCM17DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCM17DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCM17DMN:ALHBERR") {
  field(DESC, "RFCM17DMN monitoring")
  field(INP, "ALRM:SYS0:RFCM17DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCM17DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCM17DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCM17DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCM18DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCM18DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCM18DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCM18DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:1800:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCM18DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCM18DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCM18DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCM18DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCM18DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCM18DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCM18DMN:ALHBERR") {
  field(DESC, "RFCM18DMN monitoring")
  field(INP, "ALRM:SYS0:RFCM18DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCM18DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCM18DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCM18DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCM19DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCM19DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCM19DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCM19DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:1900:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCM19DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCM19DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCM19DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCM19DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCM19DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCM19DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCM19DMN:ALHBERR") {
  field(DESC, "RFCM19DMN monitoring")
  field(INP, "ALRM:SYS0:RFCM19DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCM19DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCM19DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCM19DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCM20DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCM20DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCM20DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCM20DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:2000:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCM20DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCM20DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCM20DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCM20DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCM20DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCM20DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCM20DMN:ALHBERR") {
  field(DESC, "RFCM20DMN monitoring")
  field(INP, "ALRM:SYS0:RFCM20DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCM20DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCM20DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCM20DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCM21DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCM21DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCM21DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCM21DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:2100:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCM21DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCM21DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCM21DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCM21DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCM21DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCM21DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCM21DMN:ALHBERR") {
  field(DESC, "RFCM21DMN monitoring")
  field(INP, "ALRM:SYS0:RFCM21DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCM21DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCM21DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCM21DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCM22DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCM22DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCM22DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCM22DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:2200:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCM22DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCM22DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCM22DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCM22DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCM22DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCM22DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCM22DMN:ALHBERR") {
  field(DESC, "RFCM22DMN monitoring")
  field(INP, "ALRM:SYS0:RFCM22DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCM22DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCM22DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCM22DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCM23DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCM23DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCM23DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCM23DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:2300:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCM23DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCM23DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCM23DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCM23DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCM23DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCM23DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCM23DMN:ALHBERR") {
  field(DESC, "RFCM23DMN monitoring")
  field(INP, "ALRM:SYS0:RFCM23DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCM23DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCM23DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCM23DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCM24DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCM24DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCM24DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCM24DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:2400:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCM24DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCM24DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCM24DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCM24DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCM24DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCM24DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCM24DMN:ALHBERR") {
  field(DESC, "RFCM24DMN monitoring")
  field(INP, "ALRM:SYS0:RFCM24DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCM24DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCM24DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCM24DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCM25DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCM25DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCM25DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCM25DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:2500:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCM25DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCM25DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCM25DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCM25DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCM25DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCM25DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCM25DMN:ALHBERR") {
  field(DESC, "RFCM25DMN monitoring")
  field(INP, "ALRM:SYS0:RFCM25DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCM25DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCM25DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCM25DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCM26DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCM26DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCM26DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCM26DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:2600:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCM26DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCM26DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCM26DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCM26DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCM26DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCM26DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCM26DMN:ALHBERR") {
  field(DESC, "RFCM26DMN monitoring")
  field(INP, "ALRM:SYS0:RFCM26DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCM26DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCM26DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCM26DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCM27DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCM27DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCM27DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCM27DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:2700:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCM27DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCM27DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCM27DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCM27DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCM27DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCM27DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCM27DMN:ALHBERR") {
  field(DESC, "RFCM27DMN monitoring")
  field(INP, "ALRM:SYS0:RFCM27DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCM27DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCM27DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCM27DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCM28DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCM28DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCM28DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCM28DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:2800:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCM28DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCM28DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCM28DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCM28DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCM28DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCM28DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCM28DMN:ALHBERR") {
  field(DESC, "RFCM28DMN monitoring")
  field(INP, "ALRM:SYS0:RFCM28DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCM28DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCM28DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCM28DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCM29DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCM29DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCM29DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCM29DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:2900:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCM29DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCM29DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCM29DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCM29DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCM29DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCM29DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCM29DMN:ALHBERR") {
  field(DESC, "RFCM29DMN monitoring")
  field(INP, "ALRM:SYS0:RFCM29DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCM29DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCM29DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCM29DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCM30DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCM30DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCM30DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCM30DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:3000:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCM30DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCM30DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCM30DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCM30DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCM30DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCM30DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCM30DMN:ALHBERR") {
  field(DESC, "RFCM30DMN monitoring")
  field(INP, "ALRM:SYS0:RFCM30DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCM30DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCM30DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCM30DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCM31DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCM31DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCM31DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCM31DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:3100:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCM31DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCM31DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCM31DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCM31DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCM31DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCM31DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCM31DMN:ALHBERR") {
  field(DESC, "RFCM31DMN monitoring")
  field(INP, "ALRM:SYS0:RFCM31DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCM31DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCM31DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCM31DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCM32DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCM32DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCM32DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCM32DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:3200:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCM32DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCM32DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCM32DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCM32DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCM32DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCM32DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCM32DMN:ALHBERR") {
  field(DESC, "RFCM32DMN monitoring")
  field(INP, "ALRM:SYS0:RFCM32DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCM32DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCM32DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCM32DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCM33DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCM33DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCM33DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCM33DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:3300:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCM33DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCM33DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCM33DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCM33DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCM33DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCM33DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCM33DMN:ALHBERR") {
  field(DESC, "RFCM33DMN monitoring")
  field(INP, "ALRM:SYS0:RFCM33DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCM33DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCM33DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCM33DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCM34DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCM34DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCM34DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCM34DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:3400:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCM34DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCM34DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCM34DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCM34DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCM34DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCM34DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCM34DMN:ALHBERR") {
  field(DESC, "RFCM34DMN monitoring")
  field(INP, "ALRM:SYS0:RFCM34DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCM34DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCM34DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCM34DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCM35DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCM35DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCM35DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCM35DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:3500:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCM35DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCM35DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCM35DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCM35DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCM35DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCM35DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCM35DMN:ALHBERR") {
  field(DESC, "RFCM35DMN monitoring")
  field(INP, "ALRM:SYS0:RFCM35DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCM35DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCM35DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCM35DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCMRF11DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCMRF11DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCMRF11DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCMRF11DMN:ALHBCURR") {
  field(INP, "ACCL:SYS0:RF11:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCMRF11DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCMRF11DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCMRF11DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCMRF11DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCMRF11DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCMRF11DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCMRF11DMN:ALHBERR") {
  field(DESC, "RFCMRF11DMN monitoring")
  field(INP, "ALRM:SYS0:RFCMRF11DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCMRF11DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCMRF11DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCMRF11DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFCMRF12DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFCMRF12DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFCMRF12DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFCMRF12DMN:ALHBCURR") {
  field(INP, "ACCL:SYS0:RF12:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFCMRF12DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFCMRF12DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFCMRF12DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFCMRF12DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFCMRF12DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFCMRF12DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFCMRF12DMN:ALHBERR") {
  field(DESC, "RFCMRF12DMN monitoring")
  field(INP, "ALRM:SYS0:RFCMRF12DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFCMRF12DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFCMRF12DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFCMRF12DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFAUTOCM01DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFAUTOCM01DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFAUTOCM01DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFAUTOCM01DMN:ALHBCURR") {
  field(INP, "ACCL:L0B:0100:AUTO:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFAUTOCM01DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFAUTOCM01DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFAUTOCM01DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFAUTOCM01DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFAUTOCM01DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFAUTOCM01DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFAUTOCM01DMN:ALHBERR") {
  field(DESC, "RFAUTOCM01DMN monitoring")
  field(INP, "ALRM:SYS0:RFAUTOCM01DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFAUTOCM01DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFAUTOCM01DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFAUTOCM01DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFAUTOCM02DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFAUTOCM02DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFAUTOCM02DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFAUTOCM02DMN:ALHBCURR") {
  field(INP, "ACCL:L1B:0200:AUTO:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFAUTOCM02DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFAUTOCM02DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFAUTOCM02DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFAUTOCM02DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFAUTOCM02DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFAUTOCM02DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFAUTOCM02DMN:ALHBERR") {
  field(DESC, "RFAUTOCM02DMN monitoring")
  field(INP, "ALRM:SYS0:RFAUTOCM02DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFAUTOCM02DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFAUTOCM02DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFAUTOCM02DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFAUTOCM03DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFAUTOCM03DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFAUTOCM03DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFAUTOCM03DMN:ALHBCURR") {
  field(INP, "ACCL:L1B:0300:AUTO:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFAUTOCM03DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFAUTOCM03DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFAUTOCM03DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFAUTOCM03DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFAUTOCM03DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFAUTOCM03DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFAUTOCM03DMN:ALHBERR") {
  field(DESC, "RFAUTOCM03DMN monitoring")
  field(INP, "ALRM:SYS0:RFAUTOCM03DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFAUTOCM03DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFAUTOCM03DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFAUTOCM03DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFAUTOCMH1DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFAUTOCMH1DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFAUTOCMH1DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFAUTOCMH1DMN:ALHBCURR") {
  field(INP, "ACCL:L1B:H100:AUTO:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFAUTOCMH1DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFAUTOCMH1DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFAUTOCMH1DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFAUTOCMH1DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFAUTOCMH1DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFAUTOCMH1DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFAUTOCMH1DMN:ALHBERR") {
  field(DESC, "RFAUTOCMH1DMN monitoring")
  field(INP, "ALRM:SYS0:RFAUTOCMH1DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFAUTOCMH1DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFAUTOCMH1DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFAUTOCMH1DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFAUTOCMH2DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFAUTOCMH2DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFAUTOCMH2DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFAUTOCMH2DMN:ALHBCURR") {
  field(INP, "ACCL:L1B:H200:AUTO:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFAUTOCMH2DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFAUTOCMH2DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFAUTOCMH2DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFAUTOCMH2DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFAUTOCMH2DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFAUTOCMH2DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFAUTOCMH2DMN:ALHBERR") {
  field(DESC, "RFAUTOCMH2DMN monitoring")
  field(INP, "ALRM:SYS0:RFAUTOCMH2DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFAUTOCMH2DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFAUTOCMH2DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFAUTOCMH2DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFAUTOCM04DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFAUTOCM04DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFAUTOCM04DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFAUTOCM04DMN:ALHBCURR") {
  field(INP, "ACCL:L2B:0400:AUTO:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFAUTOCM04DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFAUTOCM04DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFAUTOCM04DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFAUTOCM04DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFAUTOCM04DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFAUTOCM04DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFAUTOCM04DMN:ALHBERR") {
  field(DESC, "RFAUTOCM04DMN monitoring")
  field(INP, "ALRM:SYS0:RFAUTOCM04DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFAUTOCM04DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFAUTOCM04DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFAUTOCM04DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFAUTOCM05DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFAUTOCM05DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFAUTOCM05DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFAUTOCM05DMN:ALHBCURR") {
  field(INP, "ACCL:L2B:0500:AUTO:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFAUTOCM05DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFAUTOCM05DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFAUTOCM05DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFAUTOCM05DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFAUTOCM05DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFAUTOCM05DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFAUTOCM05DMN:ALHBERR") {
  field(DESC, "RFAUTOCM05DMN monitoring")
  field(INP, "ALRM:SYS0:RFAUTOCM05DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFAUTOCM05DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFAUTOCM05DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFAUTOCM05DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFAUTOCM06DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFAUTOCM06DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFAUTOCM06DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFAUTOCM06DMN:ALHBCURR") {
  field(INP, "ACCL:L2B:0600:AUTO:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFAUTOCM06DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFAUTOCM06DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFAUTOCM06DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFAUTOCM06DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFAUTOCM06DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFAUTOCM06DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFAUTOCM06DMN:ALHBERR") {
  field(DESC, "RFAUTOCM06DMN monitoring")
  field(INP, "ALRM:SYS0:RFAUTOCM06DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFAUTOCM06DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFAUTOCM06DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFAUTOCM06DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFAUTOCM07DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFAUTOCM07DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFAUTOCM07DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFAUTOCM07DMN:ALHBCURR") {
  field(INP, "ACCL:L2B:0700:AUTO:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFAUTOCM07DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFAUTOCM07DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFAUTOCM07DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFAUTOCM07DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFAUTOCM07DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFAUTOCM07DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFAUTOCM07DMN:ALHBERR") {
  field(DESC, "RFAUTOCM07DMN monitoring")
  field(INP, "ALRM:SYS0:RFAUTOCM07DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFAUTOCM07DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFAUTOCM07DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFAUTOCM07DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFAUTOCM08DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFAUTOCM08DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFAUTOCM08DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFAUTOCM08DMN:ALHBCURR") {
  field(INP, "ACCL:L2B:0800:AUTO:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFAUTOCM08DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFAUTOCM08DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFAUTOCM08DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFAUTOCM08DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFAUTOCM08DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFAUTOCM08DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFAUTOCM08DMN:ALHBERR") {
  field(DESC, "RFAUTOCM08DMN monitoring")
  field(INP, "ALRM:SYS0:RFAUTOCM08DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFAUTOCM08DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFAUTOCM08DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFAUTOCM08DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFAUTOCM09DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFAUTOCM09DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFAUTOCM09DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFAUTOCM09DMN:ALHBCURR") {
  field(INP, "ACCL:L2B:0900:AUTO:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFAUTOCM09DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFAUTOCM09DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFAUTOCM09DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFAUTOCM09DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFAUTOCM09DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFAUTOCM09DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFAUTOCM09DMN:ALHBERR") {
  field(DESC, "RFAUTOCM09DMN monitoring")
  field(INP, "ALRM:SYS0:RFAUTOCM09DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFAUTOCM09DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFAUTOCM09DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFAUTOCM09DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFAUTOCM10DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFAUTOCM10DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFAUTOCM10DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFAUTOCM10DMN:ALHBCURR") {
  field(INP, "ACCL:L2B:1000:AUTO:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFAUTOCM10DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFAUTOCM10DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFAUTOCM10DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFAUTOCM10DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFAUTOCM10DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFAUTOCM10DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFAUTOCM10DMN:ALHBERR") {
  field(DESC, "RFAUTOCM10DMN monitoring")
  field(INP, "ALRM:SYS0:RFAUTOCM10DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFAUTOCM10DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFAUTOCM10DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFAUTOCM10DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFAUTOCM11DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFAUTOCM11DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFAUTOCM11DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFAUTOCM11DMN:ALHBCURR") {
  field(INP, "ACCL:L2B:1100:AUTO:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFAUTOCM11DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFAUTOCM11DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFAUTOCM11DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFAUTOCM11DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFAUTOCM11DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFAUTOCM11DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFAUTOCM11DMN:ALHBERR") {
  field(DESC, "RFAUTOCM11DMN monitoring")
  field(INP, "ALRM:SYS0:RFAUTOCM11DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFAUTOCM11DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFAUTOCM11DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFAUTOCM11DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFAUTOCM12DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFAUTOCM12DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFAUTOCM12DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFAUTOCM12DMN:ALHBCURR") {
  field(INP, "ACCL:L2B:1200:AUTO:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFAUTOCM12DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFAUTOCM12DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFAUTOCM12DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFAUTOCM12DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFAUTOCM12DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFAUTOCM12DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFAUTOCM12DMN:ALHBERR") {
  field(DESC, "RFAUTOCM12DMN monitoring")
  field(INP, "ALRM:SYS0:RFAUTOCM12DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFAUTOCM12DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFAUTOCM12DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFAUTOCM12DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFAUTOCM13DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFAUTOCM13DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFAUTOCM13DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFAUTOCM13DMN:ALHBCURR") {
  field(INP, "ACCL:L2B:1300:AUTO:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFAUTOCM13DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFAUTOCM13DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFAUTOCM13DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFAUTOCM13DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFAUTOCM13DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFAUTOCM13DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFAUTOCM13DMN:ALHBERR") {
  field(DESC, "RFAUTOCM13DMN monitoring")
  field(INP, "ALRM:SYS0:RFAUTOCM13DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFAUTOCM13DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFAUTOCM13DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFAUTOCM13DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFAUTOCM14DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFAUTOCM14DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFAUTOCM14DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFAUTOCM14DMN:ALHBCURR") {
  field(INP, "ACCL:L2B:1400:AUTO:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFAUTOCM14DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFAUTOCM14DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFAUTOCM14DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFAUTOCM14DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFAUTOCM14DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFAUTOCM14DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFAUTOCM14DMN:ALHBERR") {
  field(DESC, "RFAUTOCM14DMN monitoring")
  field(INP, "ALRM:SYS0:RFAUTOCM14DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFAUTOCM14DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFAUTOCM14DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFAUTOCM14DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFAUTOCM15DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFAUTOCM15DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFAUTOCM15DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFAUTOCM15DMN:ALHBCURR") {
  field(INP, "ACCL:L2B:1500:AUTO:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFAUTOCM15DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFAUTOCM15DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFAUTOCM15DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFAUTOCM15DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFAUTOCM15DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFAUTOCM15DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFAUTOCM15DMN:ALHBERR") {
  field(DESC, "RFAUTOCM15DMN monitoring")
  field(INP, "ALRM:SYS0:RFAUTOCM15DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFAUTOCM15DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFAUTOCM15DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFAUTOCM15DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFAUTOCM16DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFAUTOCM16DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFAUTOCM16DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFAUTOCM16DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:1600:AUTO:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFAUTOCM16DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFAUTOCM16DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFAUTOCM16DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFAUTOCM16DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFAUTOCM16DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFAUTOCM16DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFAUTOCM16DMN:ALHBERR") {
  field(DESC, "RFAUTOCM16DMN monitoring")
  field(INP, "ALRM:SYS0:RFAUTOCM16DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFAUTOCM16DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFAUTOCM16DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFAUTOCM16DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFAUTOCM17DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFAUTOCM17DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFAUTOCM17DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFAUTOCM17DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:1700:AUTO:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFAUTOCM17DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFAUTOCM17DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFAUTOCM17DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFAUTOCM17DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFAUTOCM17DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFAUTOCM17DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFAUTOCM17DMN:ALHBERR") {
  field(DESC, "RFAUTOCM17DMN monitoring")
  field(INP, "ALRM:SYS0:RFAUTOCM17DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFAUTOCM17DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFAUTOCM17DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFAUTOCM17DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFAUTOCM18DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFAUTOCM18DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFAUTOCM18DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFAUTOCM18DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:1800:AUTO:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFAUTOCM18DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFAUTOCM18DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFAUTOCM18DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFAUTOCM18DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFAUTOCM18DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFAUTOCM18DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFAUTOCM18DMN:ALHBERR") {
  field(DESC, "RFAUTOCM18DMN monitoring")
  field(INP, "ALRM:SYS0:RFAUTOCM18DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFAUTOCM18DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFAUTOCM18DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFAUTOCM18DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFAUTOCM19DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFAUTOCM19DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFAUTOCM19DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFAUTOCM19DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:1900:AUTO:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFAUTOCM19DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFAUTOCM19DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFAUTOCM19DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFAUTOCM19DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFAUTOCM19DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFAUTOCM19DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFAUTOCM19DMN:ALHBERR") {
  field(DESC, "RFAUTOCM19DMN monitoring")
  field(INP, "ALRM:SYS0:RFAUTOCM19DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFAUTOCM19DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFAUTOCM19DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFAUTOCM19DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFAUTOCM20DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFAUTOCM20DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFAUTOCM20DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFAUTOCM20DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:2000:AUTO:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFAUTOCM20DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFAUTOCM20DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFAUTOCM20DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFAUTOCM20DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFAUTOCM20DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFAUTOCM20DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFAUTOCM20DMN:ALHBERR") {
  field(DESC, "RFAUTOCM20DMN monitoring")
  field(INP, "ALRM:SYS0:RFAUTOCM20DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFAUTOCM20DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFAUTOCM20DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFAUTOCM20DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFAUTOCM21DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFAUTOCM21DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFAUTOCM21DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFAUTOCM21DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:2100:AUTO:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFAUTOCM21DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFAUTOCM21DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFAUTOCM21DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFAUTOCM21DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFAUTOCM21DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFAUTOCM21DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFAUTOCM21DMN:ALHBERR") {
  field(DESC, "RFAUTOCM21DMN monitoring")
  field(INP, "ALRM:SYS0:RFAUTOCM21DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFAUTOCM21DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFAUTOCM21DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFAUTOCM21DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFAUTOCM22DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFAUTOCM22DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFAUTOCM22DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFAUTOCM22DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:2200:AUTO:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFAUTOCM22DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFAUTOCM22DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFAUTOCM22DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFAUTOCM22DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFAUTOCM22DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFAUTOCM22DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFAUTOCM22DMN:ALHBERR") {
  field(DESC, "RFAUTOCM22DMN monitoring")
  field(INP, "ALRM:SYS0:RFAUTOCM22DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFAUTOCM22DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFAUTOCM22DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFAUTOCM22DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFAUTOCM23DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFAUTOCM23DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFAUTOCM23DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFAUTOCM23DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:2300:AUTO:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFAUTOCM23DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFAUTOCM23DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFAUTOCM23DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFAUTOCM23DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFAUTOCM23DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFAUTOCM23DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFAUTOCM23DMN:ALHBERR") {
  field(DESC, "RFAUTOCM23DMN monitoring")
  field(INP, "ALRM:SYS0:RFAUTOCM23DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFAUTOCM23DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFAUTOCM23DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFAUTOCM23DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFAUTOCM24DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFAUTOCM24DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFAUTOCM24DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFAUTOCM24DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:2400:AUTO:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFAUTOCM24DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFAUTOCM24DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFAUTOCM24DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFAUTOCM24DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFAUTOCM24DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFAUTOCM24DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFAUTOCM24DMN:ALHBERR") {
  field(DESC, "RFAUTOCM24DMN monitoring")
  field(INP, "ALRM:SYS0:RFAUTOCM24DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFAUTOCM24DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFAUTOCM24DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFAUTOCM24DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFAUTOCM25DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFAUTOCM25DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFAUTOCM25DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFAUTOCM25DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:2500:AUTO:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFAUTOCM25DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFAUTOCM25DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFAUTOCM25DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFAUTOCM25DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFAUTOCM25DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFAUTOCM25DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFAUTOCM25DMN:ALHBERR") {
  field(DESC, "RFAUTOCM25DMN monitoring")
  field(INP, "ALRM:SYS0:RFAUTOCM25DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFAUTOCM25DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFAUTOCM25DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFAUTOCM25DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFAUTOCM26DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFAUTOCM26DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFAUTOCM26DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFAUTOCM26DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:2600:AUTO:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFAUTOCM26DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFAUTOCM26DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFAUTOCM26DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFAUTOCM26DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFAUTOCM26DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFAUTOCM26DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFAUTOCM26DMN:ALHBERR") {
  field(DESC, "RFAUTOCM26DMN monitoring")
  field(INP, "ALRM:SYS0:RFAUTOCM26DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFAUTOCM26DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFAUTOCM26DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFAUTOCM26DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFAUTOCM27DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFAUTOCM27DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFAUTOCM27DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFAUTOCM27DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:2700:AUTO:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFAUTOCM27DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFAUTOCM27DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFAUTOCM27DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFAUTOCM27DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFAUTOCM27DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFAUTOCM27DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFAUTOCM27DMN:ALHBERR") {
  field(DESC, "RFAUTOCM27DMN monitoring")
  field(INP, "ALRM:SYS0:RFAUTOCM27DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFAUTOCM27DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFAUTOCM27DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFAUTOCM27DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFAUTOCM28DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFAUTOCM28DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFAUTOCM28DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFAUTOCM28DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:2800:AUTO:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFAUTOCM28DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFAUTOCM28DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFAUTOCM28DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFAUTOCM28DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFAUTOCM28DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFAUTOCM28DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFAUTOCM28DMN:ALHBERR") {
  field(DESC, "RFAUTOCM28DMN monitoring")
  field(INP, "ALRM:SYS0:RFAUTOCM28DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFAUTOCM28DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFAUTOCM28DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFAUTOCM28DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFAUTOCM29DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFAUTOCM29DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFAUTOCM29DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFAUTOCM29DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:2900:AUTO:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFAUTOCM29DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFAUTOCM29DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFAUTOCM29DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFAUTOCM29DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFAUTOCM29DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFAUTOCM29DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFAUTOCM29DMN:ALHBERR") {
  field(DESC, "RFAUTOCM29DMN monitoring")
  field(INP, "ALRM:SYS0:RFAUTOCM29DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFAUTOCM29DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFAUTOCM29DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFAUTOCM29DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFAUTOCM30DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFAUTOCM30DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFAUTOCM30DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFAUTOCM30DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:3000:AUTO:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFAUTOCM30DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFAUTOCM30DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFAUTOCM30DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFAUTOCM30DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFAUTOCM30DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFAUTOCM30DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFAUTOCM30DMN:ALHBERR") {
  field(DESC, "RFAUTOCM30DMN monitoring")
  field(INP, "ALRM:SYS0:RFAUTOCM30DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFAUTOCM30DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFAUTOCM30DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFAUTOCM30DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFAUTOCM31DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFAUTOCM31DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFAUTOCM31DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFAUTOCM31DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:3100:AUTO:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFAUTOCM31DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFAUTOCM31DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFAUTOCM31DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFAUTOCM31DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFAUTOCM31DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFAUTOCM31DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFAUTOCM31DMN:ALHBERR") {
  field(DESC, "RFAUTOCM31DMN monitoring")
  field(INP, "ALRM:SYS0:RFAUTOCM31DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFAUTOCM31DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFAUTOCM31DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFAUTOCM31DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFAUTOCM32DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFAUTOCM32DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFAUTOCM32DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFAUTOCM32DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:3200:AUTO:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFAUTOCM32DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFAUTOCM32DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFAUTOCM32DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFAUTOCM32DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFAUTOCM32DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFAUTOCM32DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFAUTOCM32DMN:ALHBERR") {
  field(DESC, "RFAUTOCM32DMN monitoring")
  field(INP, "ALRM:SYS0:RFAUTOCM32DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFAUTOCM32DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFAUTOCM32DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFAUTOCM32DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFAUTOCM33DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFAUTOCM33DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFAUTOCM33DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFAUTOCM33DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:3300:AUTO:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFAUTOCM33DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFAUTOCM33DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFAUTOCM33DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFAUTOCM33DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFAUTOCM33DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFAUTOCM33DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFAUTOCM33DMN:ALHBERR") {
  field(DESC, "RFAUTOCM33DMN monitoring")
  field(INP, "ALRM:SYS0:RFAUTOCM33DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFAUTOCM33DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFAUTOCM33DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFAUTOCM33DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFAUTOCM34DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFAUTOCM34DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFAUTOCM34DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFAUTOCM34DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:3400:AUTO:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFAUTOCM34DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFAUTOCM34DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFAUTOCM34DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFAUTOCM34DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFAUTOCM34DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFAUTOCM34DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFAUTOCM34DMN:ALHBERR") {
  field(DESC, "RFAUTOCM34DMN monitoring")
  field(INP, "ALRM:SYS0:RFAUTOCM34DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFAUTOCM34DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFAUTOCM34DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFAUTOCM34DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFAUTOCM35DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFAUTOCM35DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFAUTOCM35DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFAUTOCM35DMN:ALHBCURR") {
  field(INP, "ACCL:L3B:3500:AUTO:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFAUTOCM35DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFAUTOCM35DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFAUTOCM35DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFAUTOCM35DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFAUTOCM35DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFAUTOCM35DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFAUTOCM35DMN:ALHBERR") {
  field(DESC, "RFAUTOCM35DMN monitoring")
  field(INP, "ALRM:SYS0:RFAUTOCM35DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFAUTOCM35DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFAUTOCM35DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFAUTOCM35DMN:ALHBCURR NPP NMS")
}

# checks an incrementor PV to see if it's incrementing.
# the incrementors are updated by matlab processes.
# Joe's matlab code
# this will be 0 if old = current (i.e. not incrementing
#function running = check_running(new_string, old_string)
#   running = abs(sign(str2double(new_string)-str2double(old_string)));
#end
# =======================================================
# A has current, B has previous
record(calcout, "ALRM:SYS0:RFAUTOCMRF51DMN:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:RFAUTOCMRF51DMN:SCAN.VAL")
  field(INPB, "1")
  field(OUT, "ALRM:SYS0:RFAUTOCMRF51DMN:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "ALRM:SYS0:RFAUTOCMRF51DMN:ALHBCURR") {
  field(INP, "ACCL:SYS0:RF51:AUTO:DMN_HEARTBEAT NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:RFAUTOCMRF51DMN:ALHBCHK")
}

record(calc, "ALRM:SYS0:RFAUTOCMRF51DMN:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:RFAUTOCMRF51DMN:ALHBCURR NPP MS")
  field(INPB, "ALRM:SYS0:RFAUTOCMRF51DMN:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:RFAUTOCMRF51DMN:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:RFAUTOCMRF51DMN:ALHBERR")
}

# MS will cause this to be invalid if the HBCHK is
record(mbbi, "ALRM:SYS0:RFAUTOCMRF51DMN:ALHBERR") {
  field(DESC, "RFAUTOCMRF51DMN monitoring")
  field(INP, "ALRM:SYS0:RFAUTOCMRF51DMN:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:RFAUTOCMRF51DMN:ALHBPREV")
}

record(ai, "ALRM:SYS0:RFAUTOCMRF51DMN:ALHBPREV") {
  field(INP, "ALRM:SYS0:RFAUTOCMRF51DMN:ALHBCURR NPP NMS")
}

# Joe's matlab code
# for m = 1:num_feedbacks
#    ...
#    incr_ok = check_running(pv_data{n+1}, pv_data_last{n+1}); % the CNTDISP PV
#    green_ok = strcmp('ON', pv_data{n}); % the STATE PV 
#    if green_ok && (~incr_ok) % green, not incrementing
#       error_flag(n) = 1;
#    end
# end
# ======================================================

# check to see if feedback is incrementing (running)
record(calcout, "FBCK:BCI0:1:ALSCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "FBCK:BCI0:1:ALSCAN.VAL")
  field(INPB, "30")
  field(OUT, "FBCK:BCI0:1:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "FBCK:BCI0:1:ALHBCURR") {
  field(INP,  "FBCK:BCI0:1:CNTDISP NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "FBCK:BCI0:1:ALHBCHK")
}

record(calc, "FBCK:BCI0:1:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "FBCK:BCI0:1:ALHBCURR.VAL NPP MS")
  field(INPB, "FBCK:BCI0:1:ALHBPREV.VAL NPP MS")
  field(INPC, "FBCK:BCI0:1:ALHBCURR.SEVR")
  field(FLNK, "FBCK:BCI0:1:ALHBERR")
}

# never in alarm; this is simply the status, not
# the final alarm PV.
record(mbbi, "FBCK:BCI0:1:ALHBERR") {
  field(DESC, "FBCK:BCI0:1 monitoring")
  field(FLNK, "FBCK:BCI0:1:ALFBERRCALC")
  field(INP, "FBCK:BCI0:1:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "FBCK:BCI0:1:ALHBPREV")
}

record(ai, "FBCK:BCI0:1:ALHBPREV") {
  field(INP,  "FBCK:BCI0:1:ALHBCURR NPP MS")
  field(FLNK, "FBCK:BCI0:1:ALFBERRCALC") 
}

# then see if the status is OK, but it's not incrementing
# (it thinks it's good, but it's not)
# feedback is on and not incrementing is an error
# if any input is invalid, then the status is invalid
# ALHBERR has no value severity, so can propagate its severity
# into the calc (to capture invalid)
# STATE itself could be major or minor; simply want to capture an
# invalid status here.
record(calc, "FBCK:BCI0:1:ALFBERRCALC") {
  field(CALC, "C>2||D>2?2:((A=1&&B=1)?1:0)")
  field(INPA, "FBCK:BCI0:1:STATE NPP NMS")
  field(INPB, "FBCK:BCI0:1:ALHBERR NPP NMS")
  field(INPC, "FBCK:BCI0:1:STATE.SEVR")
  field(INPD, "FBCK:BCI0:1:ALHBERR.SEVR")
  field(FLNK, "FBCK:BCI0:1:ALFBERR")
}

record(mbbi, "FBCK:BCI0:1:ALFBERR") {
  field(DESC, "FBCK:BCI0:1 monitoring")
  field(INP, "FBCK:BCI0:1:ALFBERRCALC.VAL NPP MS")
  field(ZRST, "OK")
  field(ONST, "ON_NOT_RUNNING")
  field(TWST, "INVALID")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
}

#record(bi, "FBCK:BCI0:1:ALFBERR") {
#  field(DESC, "FBCK:BCI0:1 monitoring")
#  field(INP, "FBCK:BCI0:1:ALFBERRCALC.VAL NPP MS")
#  field(ZSV, "NO_ALARM")
#  field(OSV, "MAJOR")
#  field(ZNAM, "OK")
#  field(ONAM, "ON_NOT_RUNNING")
#}

# Joe's matlab code
# for m = 1:num_feedbacks
#    ...
#    incr_ok = check_running(pv_data{n+1}, pv_data_last{n+1}); % the CNTDISP PV
#    green_ok = strcmp('ON', pv_data{n}); % the STATE PV 
#    if green_ok && (~incr_ok) % green, not incrementing
#       error_flag(n) = 1;
#    end
# end
# ======================================================

# check to see if feedback is incrementing (running)
record(calcout, "FBCK:B5L0:1:ALSCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "FBCK:B5L0:1:ALSCAN.VAL")
  field(INPB, "30")
  field(OUT, "FBCK:B5L0:1:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "FBCK:B5L0:1:ALHBCURR") {
  field(INP,  "FBCK:B5L0:1:CNTDISP NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "FBCK:B5L0:1:ALHBCHK")
}

record(calc, "FBCK:B5L0:1:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "FBCK:B5L0:1:ALHBCURR.VAL NPP MS")
  field(INPB, "FBCK:B5L0:1:ALHBPREV.VAL NPP MS")
  field(INPC, "FBCK:B5L0:1:ALHBCURR.SEVR")
  field(FLNK, "FBCK:B5L0:1:ALHBERR")
}

# never in alarm; this is simply the status, not
# the final alarm PV.
record(mbbi, "FBCK:B5L0:1:ALHBERR") {
  field(DESC, "FBCK:B5L0:1 monitoring")
  field(FLNK, "FBCK:B5L0:1:ALFBERRCALC")
  field(INP, "FBCK:B5L0:1:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "FBCK:B5L0:1:ALHBPREV")
}

record(ai, "FBCK:B5L0:1:ALHBPREV") {
  field(INP,  "FBCK:B5L0:1:ALHBCURR NPP MS")
  field(FLNK, "FBCK:B5L0:1:ALFBERRCALC") 
}

# then see if the status is OK, but it's not incrementing
# (it thinks it's good, but it's not)
# feedback is on and not incrementing is an error
# if any input is invalid, then the status is invalid
# ALHBERR has no value severity, so can propagate its severity
# into the calc (to capture invalid)
# STATE itself could be major or minor; simply want to capture an
# invalid status here.
record(calc, "FBCK:B5L0:1:ALFBERRCALC") {
  field(CALC, "C>2||D>2?2:((A=1&&B=1)?1:0)")
  field(INPA, "FBCK:B5L0:1:STATE NPP NMS")
  field(INPB, "FBCK:B5L0:1:ALHBERR NPP NMS")
  field(INPC, "FBCK:B5L0:1:STATE.SEVR")
  field(INPD, "FBCK:B5L0:1:ALHBERR.SEVR")
  field(FLNK, "FBCK:B5L0:1:ALFBERR")
}

record(mbbi, "FBCK:B5L0:1:ALFBERR") {
  field(DESC, "FBCK:B5L0:1 monitoring")
  field(INP, "FBCK:B5L0:1:ALFBERRCALC.VAL NPP MS")
  field(ZRST, "OK")
  field(ONST, "ON_NOT_RUNNING")
  field(TWST, "INVALID")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
}

#record(bi, "FBCK:B5L0:1:ALFBERR") {
#  field(DESC, "FBCK:B5L0:1 monitoring")
#  field(INP, "FBCK:B5L0:1:ALFBERRCALC.VAL NPP MS")
#  field(ZSV, "NO_ALARM")
#  field(OSV, "MAJOR")
#  field(ZNAM, "OK")
#  field(ONAM, "ON_NOT_RUNNING")
#}

# Joe's matlab code
# for m = 1:num_feedbacks
#    ...
#    incr_ok = check_running(pv_data{n+1}, pv_data_last{n+1}); % the CNTDISP PV
#    green_ok = strcmp('ON', pv_data{n}); % the STATE PV 
#    if green_ok && (~incr_ok) % green, not incrementing
#       error_flag(n) = 1;
#    end
# end
# ======================================================

# check to see if feedback is incrementing (running)
record(calcout, "FBCK:B1L0:1:ALSCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "FBCK:B1L0:1:ALSCAN.VAL")
  field(INPB, "30")
  field(OUT, "FBCK:B1L0:1:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "FBCK:B1L0:1:ALHBCURR") {
  field(INP,  "FBCK:B1L0:1:CNTDISP NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "FBCK:B1L0:1:ALHBCHK")
}

record(calc, "FBCK:B1L0:1:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "FBCK:B1L0:1:ALHBCURR.VAL NPP MS")
  field(INPB, "FBCK:B1L0:1:ALHBPREV.VAL NPP MS")
  field(INPC, "FBCK:B1L0:1:ALHBCURR.SEVR")
  field(FLNK, "FBCK:B1L0:1:ALHBERR")
}

# never in alarm; this is simply the status, not
# the final alarm PV.
record(mbbi, "FBCK:B1L0:1:ALHBERR") {
  field(DESC, "FBCK:B1L0:1 monitoring")
  field(FLNK, "FBCK:B1L0:1:ALFBERRCALC")
  field(INP, "FBCK:B1L0:1:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "FBCK:B1L0:1:ALHBPREV")
}

record(ai, "FBCK:B1L0:1:ALHBPREV") {
  field(INP,  "FBCK:B1L0:1:ALHBCURR NPP MS")
  field(FLNK, "FBCK:B1L0:1:ALFBERRCALC") 
}

# then see if the status is OK, but it's not incrementing
# (it thinks it's good, but it's not)
# feedback is on and not incrementing is an error
# if any input is invalid, then the status is invalid
# ALHBERR has no value severity, so can propagate its severity
# into the calc (to capture invalid)
# STATE itself could be major or minor; simply want to capture an
# invalid status here.
record(calc, "FBCK:B1L0:1:ALFBERRCALC") {
  field(CALC, "C>2||D>2?2:((A=1&&B=1)?1:0)")
  field(INPA, "FBCK:B1L0:1:STATE NPP NMS")
  field(INPB, "FBCK:B1L0:1:ALHBERR NPP NMS")
  field(INPC, "FBCK:B1L0:1:STATE.SEVR")
  field(INPD, "FBCK:B1L0:1:ALHBERR.SEVR")
  field(FLNK, "FBCK:B1L0:1:ALFBERR")
}

record(mbbi, "FBCK:B1L0:1:ALFBERR") {
  field(DESC, "FBCK:B1L0:1 monitoring")
  field(INP, "FBCK:B1L0:1:ALFBERRCALC.VAL NPP MS")
  field(ZRST, "OK")
  field(ONST, "ON_NOT_RUNNING")
  field(TWST, "INVALID")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
}

#record(bi, "FBCK:B1L0:1:ALFBERR") {
#  field(DESC, "FBCK:B1L0:1 monitoring")
#  field(INP, "FBCK:B1L0:1:ALFBERRCALC.VAL NPP MS")
#  field(ZSV, "NO_ALARM")
#  field(OSV, "MAJOR")
#  field(ZNAM, "OK")
#  field(ONAM, "ON_NOT_RUNNING")
#}

# Joe's matlab code
# for m = 1:num_feedbacks
#    ...
#    incr_ok = check_running(pv_data{n+1}, pv_data_last{n+1}); % the CNTDISP PV
#    green_ok = strcmp('ON', pv_data{n}); % the STATE PV 
#    if green_ok && (~incr_ok) % green, not incrementing
#       error_flag(n) = 1;
#    end
# end
# ======================================================

# check to see if feedback is incrementing (running)
record(calcout, "FBCK:INL0:1:ALSCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "FBCK:INL0:1:ALSCAN.VAL")
  field(INPB, "30")
  field(OUT, "FBCK:INL0:1:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "FBCK:INL0:1:ALHBCURR") {
  field(INP,  "FBCK:INL0:1:CNTDISP NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "FBCK:INL0:1:ALHBCHK")
}

record(calc, "FBCK:INL0:1:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "FBCK:INL0:1:ALHBCURR.VAL NPP MS")
  field(INPB, "FBCK:INL0:1:ALHBPREV.VAL NPP MS")
  field(INPC, "FBCK:INL0:1:ALHBCURR.SEVR")
  field(FLNK, "FBCK:INL0:1:ALHBERR")
}

# never in alarm; this is simply the status, not
# the final alarm PV.
record(mbbi, "FBCK:INL0:1:ALHBERR") {
  field(DESC, "FBCK:INL0:1 monitoring")
  field(FLNK, "FBCK:INL0:1:ALFBERRCALC")
  field(INP, "FBCK:INL0:1:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "FBCK:INL0:1:ALHBPREV")
}

record(ai, "FBCK:INL0:1:ALHBPREV") {
  field(INP,  "FBCK:INL0:1:ALHBCURR NPP MS")
  field(FLNK, "FBCK:INL0:1:ALFBERRCALC") 
}

# then see if the status is OK, but it's not incrementing
# (it thinks it's good, but it's not)
# feedback is on and not incrementing is an error
# if any input is invalid, then the status is invalid
# ALHBERR has no value severity, so can propagate its severity
# into the calc (to capture invalid)
# STATE itself could be major or minor; simply want to capture an
# invalid status here.
record(calc, "FBCK:INL0:1:ALFBERRCALC") {
  field(CALC, "C>2||D>2?2:((A=1&&B=1)?1:0)")
  field(INPA, "FBCK:INL0:1:STATE NPP NMS")
  field(INPB, "FBCK:INL0:1:ALHBERR NPP NMS")
  field(INPC, "FBCK:INL0:1:STATE.SEVR")
  field(INPD, "FBCK:INL0:1:ALHBERR.SEVR")
  field(FLNK, "FBCK:INL0:1:ALFBERR")
}

record(mbbi, "FBCK:INL0:1:ALFBERR") {
  field(DESC, "FBCK:INL0:1 monitoring")
  field(INP, "FBCK:INL0:1:ALFBERRCALC.VAL NPP MS")
  field(ZRST, "OK")
  field(ONST, "ON_NOT_RUNNING")
  field(TWST, "INVALID")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
}

#record(bi, "FBCK:INL0:1:ALFBERR") {
#  field(DESC, "FBCK:INL0:1 monitoring")
#  field(INP, "FBCK:INL0:1:ALFBERRCALC.VAL NPP MS")
#  field(ZSV, "NO_ALARM")
#  field(OSV, "MAJOR")
#  field(ZNAM, "OK")
#  field(ONAM, "ON_NOT_RUNNING")
#}

# Joe's matlab code
# for m = 1:num_feedbacks
#    ...
#    incr_ok = check_running(pv_data{n+1}, pv_data_last{n+1}); % the CNTDISP PV
#    green_ok = strcmp('ON', pv_data{n}); % the STATE PV 
#    if green_ok && (~incr_ok) % green, not incrementing
#       error_flag(n) = 1;
#    end
# end
# ======================================================

# check to see if feedback is incrementing (running)
record(calcout, "FBCK:INL1:1:ALSCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "FBCK:INL1:1:ALSCAN.VAL")
  field(INPB, "30")
  field(OUT, "FBCK:INL1:1:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "FBCK:INL1:1:ALHBCURR") {
  field(INP,  "FBCK:INL1:1:CNTDISP NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "FBCK:INL1:1:ALHBCHK")
}

record(calc, "FBCK:INL1:1:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "FBCK:INL1:1:ALHBCURR.VAL NPP MS")
  field(INPB, "FBCK:INL1:1:ALHBPREV.VAL NPP MS")
  field(INPC, "FBCK:INL1:1:ALHBCURR.SEVR")
  field(FLNK, "FBCK:INL1:1:ALHBERR")
}

# never in alarm; this is simply the status, not
# the final alarm PV.
record(mbbi, "FBCK:INL1:1:ALHBERR") {
  field(DESC, "FBCK:INL1:1 monitoring")
  field(FLNK, "FBCK:INL1:1:ALFBERRCALC")
  field(INP, "FBCK:INL1:1:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "FBCK:INL1:1:ALHBPREV")
}

record(ai, "FBCK:INL1:1:ALHBPREV") {
  field(INP,  "FBCK:INL1:1:ALHBCURR NPP MS")
  field(FLNK, "FBCK:INL1:1:ALFBERRCALC") 
}

# then see if the status is OK, but it's not incrementing
# (it thinks it's good, but it's not)
# feedback is on and not incrementing is an error
# if any input is invalid, then the status is invalid
# ALHBERR has no value severity, so can propagate its severity
# into the calc (to capture invalid)
# STATE itself could be major or minor; simply want to capture an
# invalid status here.
record(calc, "FBCK:INL1:1:ALFBERRCALC") {
  field(CALC, "C>2||D>2?2:((A=1&&B=1)?1:0)")
  field(INPA, "FBCK:INL1:1:STATE NPP NMS")
  field(INPB, "FBCK:INL1:1:ALHBERR NPP NMS")
  field(INPC, "FBCK:INL1:1:STATE.SEVR")
  field(INPD, "FBCK:INL1:1:ALHBERR.SEVR")
  field(FLNK, "FBCK:INL1:1:ALFBERR")
}

record(mbbi, "FBCK:INL1:1:ALFBERR") {
  field(DESC, "FBCK:INL1:1 monitoring")
  field(INP, "FBCK:INL1:1:ALFBERRCALC.VAL NPP MS")
  field(ZRST, "OK")
  field(ONST, "ON_NOT_RUNNING")
  field(TWST, "INVALID")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
}

#record(bi, "FBCK:INL1:1:ALFBERR") {
#  field(DESC, "FBCK:INL1:1 monitoring")
#  field(INP, "FBCK:INL1:1:ALFBERRCALC.VAL NPP MS")
#  field(ZSV, "NO_ALARM")
#  field(OSV, "MAJOR")
#  field(ZNAM, "OK")
#  field(ONAM, "ON_NOT_RUNNING")
#}

# Joe's matlab code
# for m = 1:num_feedbacks
#    ...
#    incr_ok = check_running(pv_data{n+1}, pv_data_last{n+1}); % the CNTDISP PV
#    green_ok = strcmp('ON', pv_data{n}); % the STATE PV 
#    if green_ok && (~incr_ok) % green, not incrementing
#       error_flag(n) = 1;
#    end
# end
# ======================================================

# check to see if feedback is incrementing (running)
record(calcout, "FBCK:L2L0:1:ALSCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "FBCK:L2L0:1:ALSCAN.VAL")
  field(INPB, "30")
  field(OUT, "FBCK:L2L0:1:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "FBCK:L2L0:1:ALHBCURR") {
  field(INP,  "FBCK:L2L0:1:CNTDISP NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "FBCK:L2L0:1:ALHBCHK")
}

record(calc, "FBCK:L2L0:1:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "FBCK:L2L0:1:ALHBCURR.VAL NPP MS")
  field(INPB, "FBCK:L2L0:1:ALHBPREV.VAL NPP MS")
  field(INPC, "FBCK:L2L0:1:ALHBCURR.SEVR")
  field(FLNK, "FBCK:L2L0:1:ALHBERR")
}

# never in alarm; this is simply the status, not
# the final alarm PV.
record(mbbi, "FBCK:L2L0:1:ALHBERR") {
  field(DESC, "FBCK:L2L0:1 monitoring")
  field(FLNK, "FBCK:L2L0:1:ALFBERRCALC")
  field(INP, "FBCK:L2L0:1:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "FBCK:L2L0:1:ALHBPREV")
}

record(ai, "FBCK:L2L0:1:ALHBPREV") {
  field(INP,  "FBCK:L2L0:1:ALHBCURR NPP MS")
  field(FLNK, "FBCK:L2L0:1:ALFBERRCALC") 
}

# then see if the status is OK, but it's not incrementing
# (it thinks it's good, but it's not)
# feedback is on and not incrementing is an error
# if any input is invalid, then the status is invalid
# ALHBERR has no value severity, so can propagate its severity
# into the calc (to capture invalid)
# STATE itself could be major or minor; simply want to capture an
# invalid status here.
record(calc, "FBCK:L2L0:1:ALFBERRCALC") {
  field(CALC, "C>2||D>2?2:((A=1&&B=1)?1:0)")
  field(INPA, "FBCK:L2L0:1:STATE NPP NMS")
  field(INPB, "FBCK:L2L0:1:ALHBERR NPP NMS")
  field(INPC, "FBCK:L2L0:1:STATE.SEVR")
  field(INPD, "FBCK:L2L0:1:ALHBERR.SEVR")
  field(FLNK, "FBCK:L2L0:1:ALFBERR")
}

record(mbbi, "FBCK:L2L0:1:ALFBERR") {
  field(DESC, "FBCK:L2L0:1 monitoring")
  field(INP, "FBCK:L2L0:1:ALFBERRCALC.VAL NPP MS")
  field(ZRST, "OK")
  field(ONST, "ON_NOT_RUNNING")
  field(TWST, "INVALID")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
}

#record(bi, "FBCK:L2L0:1:ALFBERR") {
#  field(DESC, "FBCK:L2L0:1 monitoring")
#  field(INP, "FBCK:L2L0:1:ALFBERRCALC.VAL NPP MS")
#  field(ZSV, "NO_ALARM")
#  field(OSV, "MAJOR")
#  field(ZNAM, "OK")
#  field(ONAM, "ON_NOT_RUNNING")
#}

# Joe's matlab code
# for m = 1:num_feedbacks
#    ...
#    incr_ok = check_running(pv_data{n+1}, pv_data_last{n+1}); % the CNTDISP PV
#    green_ok = strcmp('ON', pv_data{n}); % the STATE PV 
#    if green_ok && (~incr_ok) % green, not incrementing
#       error_flag(n) = 1;
#    end
# end
# ======================================================

# check to see if feedback is incrementing (running)
record(calcout, "FBCK:BSY0:1:ALSCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "FBCK:BSY0:1:ALSCAN.VAL")
  field(INPB, "30")
  field(OUT, "FBCK:BSY0:1:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "FBCK:BSY0:1:ALHBCURR") {
  field(INP,  "FBCK:BSY0:1:CNTDISP NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "FBCK:BSY0:1:ALHBCHK")
}

record(calc, "FBCK:BSY0:1:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "FBCK:BSY0:1:ALHBCURR.VAL NPP MS")
  field(INPB, "FBCK:BSY0:1:ALHBPREV.VAL NPP MS")
  field(INPC, "FBCK:BSY0:1:ALHBCURR.SEVR")
  field(FLNK, "FBCK:BSY0:1:ALHBERR")
}

# never in alarm; this is simply the status, not
# the final alarm PV.
record(mbbi, "FBCK:BSY0:1:ALHBERR") {
  field(DESC, "FBCK:BSY0:1 monitoring")
  field(FLNK, "FBCK:BSY0:1:ALFBERRCALC")
  field(INP, "FBCK:BSY0:1:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "FBCK:BSY0:1:ALHBPREV")
}

record(ai, "FBCK:BSY0:1:ALHBPREV") {
  field(INP,  "FBCK:BSY0:1:ALHBCURR NPP MS")
  field(FLNK, "FBCK:BSY0:1:ALFBERRCALC") 
}

# then see if the status is OK, but it's not incrementing
# (it thinks it's good, but it's not)
# feedback is on and not incrementing is an error
# if any input is invalid, then the status is invalid
# ALHBERR has no value severity, so can propagate its severity
# into the calc (to capture invalid)
# STATE itself could be major or minor; simply want to capture an
# invalid status here.
record(calc, "FBCK:BSY0:1:ALFBERRCALC") {
  field(CALC, "C>2||D>2?2:((A=1&&B=1)?1:0)")
  field(INPA, "FBCK:BSY0:1:STATE NPP NMS")
  field(INPB, "FBCK:BSY0:1:ALHBERR NPP NMS")
  field(INPC, "FBCK:BSY0:1:STATE.SEVR")
  field(INPD, "FBCK:BSY0:1:ALHBERR.SEVR")
  field(FLNK, "FBCK:BSY0:1:ALFBERR")
}

record(mbbi, "FBCK:BSY0:1:ALFBERR") {
  field(DESC, "FBCK:BSY0:1 monitoring")
  field(INP, "FBCK:BSY0:1:ALFBERRCALC.VAL NPP MS")
  field(ZRST, "OK")
  field(ONST, "ON_NOT_RUNNING")
  field(TWST, "INVALID")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
}

#record(bi, "FBCK:BSY0:1:ALFBERR") {
#  field(DESC, "FBCK:BSY0:1 monitoring")
#  field(INP, "FBCK:BSY0:1:ALFBERRCALC.VAL NPP MS")
#  field(ZSV, "NO_ALARM")
#  field(OSV, "MAJOR")
#  field(ZNAM, "OK")
#  field(ONAM, "ON_NOT_RUNNING")
#}

# Joe's matlab code
# for m = 1:num_feedbacks
#    ...
#    incr_ok = check_running(pv_data{n+1}, pv_data_last{n+1}); % the CNTDISP PV
#    green_ok = strcmp('ON', pv_data{n}); % the STATE PV 
#    if green_ok && (~incr_ok) % green, not incrementing
#       error_flag(n) = 1;
#    end
# end
# ======================================================

# check to see if feedback is incrementing (running)
record(calcout, "FBCK:LTL0:1:ALSCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "FBCK:LTL0:1:ALSCAN.VAL")
  field(INPB, "30")
  field(OUT, "FBCK:LTL0:1:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "FBCK:LTL0:1:ALHBCURR") {
  field(INP,  "FBCK:LTL0:1:CNTDISP NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "FBCK:LTL0:1:ALHBCHK")
}

record(calc, "FBCK:LTL0:1:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "FBCK:LTL0:1:ALHBCURR.VAL NPP MS")
  field(INPB, "FBCK:LTL0:1:ALHBPREV.VAL NPP MS")
  field(INPC, "FBCK:LTL0:1:ALHBCURR.SEVR")
  field(FLNK, "FBCK:LTL0:1:ALHBERR")
}

# never in alarm; this is simply the status, not
# the final alarm PV.
record(mbbi, "FBCK:LTL0:1:ALHBERR") {
  field(DESC, "FBCK:LTL0:1 monitoring")
  field(FLNK, "FBCK:LTL0:1:ALFBERRCALC")
  field(INP, "FBCK:LTL0:1:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "FBCK:LTL0:1:ALHBPREV")
}

record(ai, "FBCK:LTL0:1:ALHBPREV") {
  field(INP,  "FBCK:LTL0:1:ALHBCURR NPP MS")
  field(FLNK, "FBCK:LTL0:1:ALFBERRCALC") 
}

# then see if the status is OK, but it's not incrementing
# (it thinks it's good, but it's not)
# feedback is on and not incrementing is an error
# if any input is invalid, then the status is invalid
# ALHBERR has no value severity, so can propagate its severity
# into the calc (to capture invalid)
# STATE itself could be major or minor; simply want to capture an
# invalid status here.
record(calc, "FBCK:LTL0:1:ALFBERRCALC") {
  field(CALC, "C>2||D>2?2:((A=1&&B=1)?1:0)")
  field(INPA, "FBCK:LTL0:1:STATE NPP NMS")
  field(INPB, "FBCK:LTL0:1:ALHBERR NPP NMS")
  field(INPC, "FBCK:LTL0:1:STATE.SEVR")
  field(INPD, "FBCK:LTL0:1:ALHBERR.SEVR")
  field(FLNK, "FBCK:LTL0:1:ALFBERR")
}

record(mbbi, "FBCK:LTL0:1:ALFBERR") {
  field(DESC, "FBCK:LTL0:1 monitoring")
  field(INP, "FBCK:LTL0:1:ALFBERRCALC.VAL NPP MS")
  field(ZRST, "OK")
  field(ONST, "ON_NOT_RUNNING")
  field(TWST, "INVALID")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
}

#record(bi, "FBCK:LTL0:1:ALFBERR") {
#  field(DESC, "FBCK:LTL0:1 monitoring")
#  field(INP, "FBCK:LTL0:1:ALFBERRCALC.VAL NPP MS")
#  field(ZSV, "NO_ALARM")
#  field(OSV, "MAJOR")
#  field(ZNAM, "OK")
#  field(ONAM, "ON_NOT_RUNNING")
#}

# Joe's matlab code
# for m = 1:num_feedbacks
#    ...
#    incr_ok = check_running(pv_data{n+1}, pv_data_last{n+1}); % the CNTDISP PV
#    green_ok = strcmp('ON', pv_data{n}); % the STATE PV 
#    if green_ok && (~incr_ok) % green, not incrementing
#       error_flag(n) = 1;
#    end
# end
# ======================================================

# check to see if feedback is incrementing (running)
record(calcout, "FBCK:UND0:1:ALSCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "FBCK:UND0:1:ALSCAN.VAL")
  field(INPB, "30")
  field(OUT, "FBCK:UND0:1:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "FBCK:UND0:1:ALHBCURR") {
  field(INP,  "FBCK:UND0:1:CNTDISP NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "FBCK:UND0:1:ALHBCHK")
}

record(calc, "FBCK:UND0:1:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "FBCK:UND0:1:ALHBCURR.VAL NPP MS")
  field(INPB, "FBCK:UND0:1:ALHBPREV.VAL NPP MS")
  field(INPC, "FBCK:UND0:1:ALHBCURR.SEVR")
  field(FLNK, "FBCK:UND0:1:ALHBERR")
}

# never in alarm; this is simply the status, not
# the final alarm PV.
record(mbbi, "FBCK:UND0:1:ALHBERR") {
  field(DESC, "FBCK:UND0:1 monitoring")
  field(FLNK, "FBCK:UND0:1:ALFBERRCALC")
  field(INP, "FBCK:UND0:1:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "FBCK:UND0:1:ALHBPREV")
}

record(ai, "FBCK:UND0:1:ALHBPREV") {
  field(INP,  "FBCK:UND0:1:ALHBCURR NPP MS")
  field(FLNK, "FBCK:UND0:1:ALFBERRCALC") 
}

# then see if the status is OK, but it's not incrementing
# (it thinks it's good, but it's not)
# feedback is on and not incrementing is an error
# if any input is invalid, then the status is invalid
# ALHBERR has no value severity, so can propagate its severity
# into the calc (to capture invalid)
# STATE itself could be major or minor; simply want to capture an
# invalid status here.
record(calc, "FBCK:UND0:1:ALFBERRCALC") {
  field(CALC, "C>2||D>2?2:((A=1&&B=1)?1:0)")
  field(INPA, "FBCK:UND0:1:STATE NPP NMS")
  field(INPB, "FBCK:UND0:1:ALHBERR NPP NMS")
  field(INPC, "FBCK:UND0:1:STATE.SEVR")
  field(INPD, "FBCK:UND0:1:ALHBERR.SEVR")
  field(FLNK, "FBCK:UND0:1:ALFBERR")
}

record(mbbi, "FBCK:UND0:1:ALFBERR") {
  field(DESC, "FBCK:UND0:1 monitoring")
  field(INP, "FBCK:UND0:1:ALFBERRCALC.VAL NPP MS")
  field(ZRST, "OK")
  field(ONST, "ON_NOT_RUNNING")
  field(TWST, "INVALID")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
}

#record(bi, "FBCK:UND0:1:ALFBERR") {
#  field(DESC, "FBCK:UND0:1 monitoring")
#  field(INP, "FBCK:UND0:1:ALFBERRCALC.VAL NPP MS")
#  field(ZSV, "NO_ALARM")
#  field(OSV, "MAJOR")
#  field(ZNAM, "OK")
#  field(ONAM, "ON_NOT_RUNNING")
#}

# Joe's matlab code
# for m = 1:num_feedbacks
#    ...
#    incr_ok = check_running(pv_data{n+1}, pv_data_last{n+1}); % the CNTDISP PV
#    green_ok = strcmp('ON', pv_data{n}); % the STATE PV 
#    if green_ok && (~incr_ok) % green, not incrementing
#       error_flag(n) = 1;
#    end
# end
# ======================================================

# check to see if feedback is incrementing (running)
record(calcout, "FBCK:L3L0:1:ALSCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "FBCK:L3L0:1:ALSCAN.VAL")
  field(INPB, "30")
  field(OUT, "FBCK:L3L0:1:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "FBCK:L3L0:1:ALHBCURR") {
  field(INP,  "FBCK:L3L0:1:CNTDISP NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "FBCK:L3L0:1:ALHBCHK")
}

record(calc, "FBCK:L3L0:1:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "FBCK:L3L0:1:ALHBCURR.VAL NPP MS")
  field(INPB, "FBCK:L3L0:1:ALHBPREV.VAL NPP MS")
  field(INPC, "FBCK:L3L0:1:ALHBCURR.SEVR")
  field(FLNK, "FBCK:L3L0:1:ALHBERR")
}

# never in alarm; this is simply the status, not
# the final alarm PV.
record(mbbi, "FBCK:L3L0:1:ALHBERR") {
  field(DESC, "FBCK:L3L0:1 monitoring")
  field(FLNK, "FBCK:L3L0:1:ALFBERRCALC")
  field(INP, "FBCK:L3L0:1:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "FBCK:L3L0:1:ALHBPREV")
}

record(ai, "FBCK:L3L0:1:ALHBPREV") {
  field(INP,  "FBCK:L3L0:1:ALHBCURR NPP MS")
  field(FLNK, "FBCK:L3L0:1:ALFBERRCALC") 
}

# then see if the status is OK, but it's not incrementing
# (it thinks it's good, but it's not)
# feedback is on and not incrementing is an error
# if any input is invalid, then the status is invalid
# ALHBERR has no value severity, so can propagate its severity
# into the calc (to capture invalid)
# STATE itself could be major or minor; simply want to capture an
# invalid status here.
record(calc, "FBCK:L3L0:1:ALFBERRCALC") {
  field(CALC, "C>2||D>2?2:((A=1&&B=1)?1:0)")
  field(INPA, "FBCK:L3L0:1:STATE NPP NMS")
  field(INPB, "FBCK:L3L0:1:ALHBERR NPP NMS")
  field(INPC, "FBCK:L3L0:1:STATE.SEVR")
  field(INPD, "FBCK:L3L0:1:ALHBERR.SEVR")
  field(FLNK, "FBCK:L3L0:1:ALFBERR")
}

record(mbbi, "FBCK:L3L0:1:ALFBERR") {
  field(DESC, "FBCK:L3L0:1 monitoring")
  field(INP, "FBCK:L3L0:1:ALFBERRCALC.VAL NPP MS")
  field(ZRST, "OK")
  field(ONST, "ON_NOT_RUNNING")
  field(TWST, "INVALID")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
}

#record(bi, "FBCK:L3L0:1:ALFBERR") {
#  field(DESC, "FBCK:L3L0:1 monitoring")
#  field(INP, "FBCK:L3L0:1:ALFBERRCALC.VAL NPP MS")
#  field(ZSV, "NO_ALARM")
#  field(OSV, "MAJOR")
#  field(ZNAM, "OK")
#  field(ONAM, "ON_NOT_RUNNING")
#}

# Joe's matlab code
# for m = 1:num_feedbacks
#    ...
#    incr_ok = check_running(pv_data{n+1}, pv_data_last{n+1}); % the CNTDISP PV
#    green_ok = strcmp('ON', pv_data{n}); % the STATE PV 
#    if green_ok && (~incr_ok) % green, not incrementing
#       error_flag(n) = 1;
#    end
# end
# ======================================================

# check to see if feedback is incrementing (running)
record(calcout, "FBCK:L280:1:ALSCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "FBCK:L280:1:ALSCAN.VAL")
  field(INPB, "30")
  field(OUT, "FBCK:L280:1:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "FBCK:L280:1:ALHBCURR") {
  field(INP,  "FBCK:L280:1:CNTDISP NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "FBCK:L280:1:ALHBCHK")
}

record(calc, "FBCK:L280:1:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "FBCK:L280:1:ALHBCURR.VAL NPP MS")
  field(INPB, "FBCK:L280:1:ALHBPREV.VAL NPP MS")
  field(INPC, "FBCK:L280:1:ALHBCURR.SEVR")
  field(FLNK, "FBCK:L280:1:ALHBERR")
}

# never in alarm; this is simply the status, not
# the final alarm PV.
record(mbbi, "FBCK:L280:1:ALHBERR") {
  field(DESC, "FBCK:L280:1 monitoring")
  field(FLNK, "FBCK:L280:1:ALFBERRCALC")
  field(INP, "FBCK:L280:1:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "FBCK:L280:1:ALHBPREV")
}

record(ai, "FBCK:L280:1:ALHBPREV") {
  field(INP,  "FBCK:L280:1:ALHBCURR NPP MS")
  field(FLNK, "FBCK:L280:1:ALFBERRCALC") 
}

# then see if the status is OK, but it's not incrementing
# (it thinks it's good, but it's not)
# feedback is on and not incrementing is an error
# if any input is invalid, then the status is invalid
# ALHBERR has no value severity, so can propagate its severity
# into the calc (to capture invalid)
# STATE itself could be major or minor; simply want to capture an
# invalid status here.
record(calc, "FBCK:L280:1:ALFBERRCALC") {
  field(CALC, "C>2||D>2?2:((A=1&&B=1)?1:0)")
  field(INPA, "FBCK:L280:1:STATE NPP NMS")
  field(INPB, "FBCK:L280:1:ALHBERR NPP NMS")
  field(INPC, "FBCK:L280:1:STATE.SEVR")
  field(INPD, "FBCK:L280:1:ALHBERR.SEVR")
  field(FLNK, "FBCK:L280:1:ALFBERR")
}

record(mbbi, "FBCK:L280:1:ALFBERR") {
  field(DESC, "FBCK:L280:1 monitoring")
  field(INP, "FBCK:L280:1:ALFBERRCALC.VAL NPP MS")
  field(ZRST, "OK")
  field(ONST, "ON_NOT_RUNNING")
  field(TWST, "INVALID")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
}

#record(bi, "FBCK:L280:1:ALFBERR") {
#  field(DESC, "FBCK:L280:1 monitoring")
#  field(INP, "FBCK:L280:1:ALFBERRCALC.VAL NPP MS")
#  field(ZSV, "NO_ALARM")
#  field(OSV, "MAJOR")
#  field(ZNAM, "OK")
#  field(ONAM, "ON_NOT_RUNNING")
#}

# Joe's matlab code
# for m = 1:num_feedbacks
#    ...
#    incr_ok = check_running(pv_data{n+1}, pv_data_last{n+1}); % the CNTDISP PV
#    green_ok = strcmp('ON', pv_data{n}); % the STATE PV 
#    if green_ok && (~incr_ok) % green, not incrementing
#       error_flag(n) = 1;
#    end
# end
# ======================================================

# check to see if feedback is incrementing (running)
record(calcout, "FBCK:MDL0:1:ALSCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "FBCK:MDL0:1:ALSCAN.VAL")
  field(INPB, "600")
  field(OUT, "FBCK:MDL0:1:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "FBCK:MDL0:1:ALHBCURR") {
  field(INP,  "FBCK:MDL0:1:CNTDISP NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "FBCK:MDL0:1:ALHBCHK")
}

record(calc, "FBCK:MDL0:1:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "FBCK:MDL0:1:ALHBCURR.VAL NPP MS")
  field(INPB, "FBCK:MDL0:1:ALHBPREV.VAL NPP MS")
  field(INPC, "FBCK:MDL0:1:ALHBCURR.SEVR")
  field(FLNK, "FBCK:MDL0:1:ALHBERR")
}

# never in alarm; this is simply the status, not
# the final alarm PV.
record(mbbi, "FBCK:MDL0:1:ALHBERR") {
  field(DESC, "FBCK:MDL0:1 monitoring")
  field(FLNK, "FBCK:MDL0:1:ALFBERRCALC")
  field(INP, "FBCK:MDL0:1:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "FBCK:MDL0:1:ALHBPREV")
}

record(ai, "FBCK:MDL0:1:ALHBPREV") {
  field(INP,  "FBCK:MDL0:1:ALHBCURR NPP MS")
  field(FLNK, "FBCK:MDL0:1:ALFBERRCALC") 
}

# then see if the status is OK, but it's not incrementing
# (it thinks it's good, but it's not)
# feedback is on and not incrementing is an error
# if any input is invalid, then the status is invalid
# ALHBERR has no value severity, so can propagate its severity
# into the calc (to capture invalid)
# STATE itself could be major or minor; simply want to capture an
# invalid status here.
record(calc, "FBCK:MDL0:1:ALFBERRCALC") {
  field(CALC, "C>2||D>2?2:((A=1&&B=1)?1:0)")
  field(INPA, "FBCK:MDL0:1:STATE NPP NMS")
  field(INPB, "FBCK:MDL0:1:ALHBERR NPP NMS")
  field(INPC, "FBCK:MDL0:1:STATE.SEVR")
  field(INPD, "FBCK:MDL0:1:ALHBERR.SEVR")
  field(FLNK, "FBCK:MDL0:1:ALFBERR")
}

record(mbbi, "FBCK:MDL0:1:ALFBERR") {
  field(DESC, "FBCK:MDL0:1 monitoring")
  field(INP, "FBCK:MDL0:1:ALFBERRCALC.VAL NPP MS")
  field(ZRST, "OK")
  field(ONST, "ON_NOT_RUNNING")
  field(TWST, "INVALID")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
}

#record(bi, "FBCK:MDL0:1:ALFBERR") {
#  field(DESC, "FBCK:MDL0:1 monitoring")
#  field(INP, "FBCK:MDL0:1:ALFBERRCALC.VAL NPP MS")
#  field(ZSV, "NO_ALARM")
#  field(OSV, "MAJOR")
#  field(ZNAM, "OK")
#  field(ONAM, "ON_NOT_RUNNING")
#}

# VERSION FOR NEW FEEDBACKS (2/2011)
# only changing the names of incrementor PV to COUNTER from CNTDISP 
#
# Joe's matlab code
# for m = 1:num_feedbacks
#    ...
#    incr_ok = check_running(pv_data{n+1}, pv_data_last{n+1}); % the CNTDISP PV
#    green_ok = strcmp('ON', pv_data{n}); % the STATE PV 
#    if green_ok && (~incr_ok) % green, not incrementing
#       error_flag(n) = 1;
#    end
# end
# ======================================================

# check to see if feedback is incrementing (running)
record(calcout, "FBCK:FB01:TR01:ALSCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "FBCK:FB01:TR01:ALSCAN.VAL")
  field(INPB, "30")
  field(OUT, "FBCK:FB01:TR01:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "FBCK:FB01:TR01:ALHBCURR") {
  field(INP,  "FBCK:FB01:TR01:COUNTER NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "FBCK:FB01:TR01:ALHBCHK")
}

record(calc, "FBCK:FB01:TR01:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "FBCK:FB01:TR01:ALHBCURR.VAL NPP MS")
  field(INPB, "FBCK:FB01:TR01:ALHBPREV.VAL NPP MS")
  field(INPC, "FBCK:FB01:TR01:ALHBCURR.SEVR")
  field(FLNK, "FBCK:FB01:TR01:ALHBERR")
}

# never in alarm; this is simply the status, not
# the final alarm PV.
record(mbbi, "FBCK:FB01:TR01:ALHBERR") {
  field(DESC, "FBCK:FB01:TR01 monitoring")
  field(FLNK, "FBCK:FB01:TR01:ALFBERRCALC")
  field(INP, "FBCK:FB01:TR01:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "FBCK:FB01:TR01:ALHBPREV")
}

record(ai, "FBCK:FB01:TR01:ALHBPREV") {
  field(INP,  "FBCK:FB01:TR01:ALHBCURR NPP MS")
  field(FLNK, "FBCK:FB01:TR01:ALFBERRCALC") 
}

# then see if the status is OK, but it's not incrementing
# (it thinks it's good, but it's not)
# feedback is on and not incrementing is an error
# if any input is invalid, then the status is invalid
# ALHBERR has no value severity, so can propagate its severity
# into the calc (to capture invalid)
# STATE itself could be major or minor; simply want to capture an
# invalid status here.
record(calc, "FBCK:FB01:TR01:ALFBERRCALC") {
  field(CALC, "C>2||D>2?2:((A=1&&B=1)?1:0)")
  field(INPA, "FBCK:FB01:TR01:STATE NPP NMS")
  field(INPB, "FBCK:FB01:TR01:ALHBERR NPP NMS")
  field(INPC, "FBCK:FB01:TR01:STATE.SEVR")
  field(INPD, "FBCK:FB01:TR01:ALHBERR.SEVR")
  field(FLNK, "FBCK:FB01:TR01:ALFBERR")
}

record(mbbi, "FBCK:FB01:TR01:ALFBERR") {
  field(DESC, "FBCK:FB01:TR01 monitoring")
  field(INP, "FBCK:FB01:TR01:ALFBERRCALC.VAL NPP MS")
  field(ZRST, "OK")
  field(ONST, "ON_NOT_RUNNING")
  field(TWST, "INVALID")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
}

#record(bi, "FBCK:FB01:TR01:ALFBERR") {
#  field(DESC, "FBCK:FB01:TR01 monitoring")
#  field(INP, "FBCK:FB01:TR01:ALFBERRCALC.VAL NPP MS")
#  field(ZSV, "NO_ALARM")
#  field(OSV, "MAJOR")
#  field(ZNAM, "OK")
#  field(ONAM, "ON_NOT_RUNNING")
#}

# VERSION FOR NEW FEEDBACKS (2/2011)
# only changing the names of incrementor PV to COUNTER from CNTDISP 
#
# Joe's matlab code
# for m = 1:num_feedbacks
#    ...
#    incr_ok = check_running(pv_data{n+1}, pv_data_last{n+1}); % the CNTDISP PV
#    green_ok = strcmp('ON', pv_data{n}); % the STATE PV 
#    if green_ok && (~incr_ok) % green, not incrementing
#       error_flag(n) = 1;
#    end
# end
# ======================================================

# check to see if feedback is incrementing (running)
record(calcout, "FBCK:FB01:TR02:ALSCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "FBCK:FB01:TR02:ALSCAN.VAL")
  field(INPB, "30")
  field(OUT, "FBCK:FB01:TR02:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "FBCK:FB01:TR02:ALHBCURR") {
  field(INP,  "FBCK:FB01:TR02:COUNTER NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "FBCK:FB01:TR02:ALHBCHK")
}

record(calc, "FBCK:FB01:TR02:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "FBCK:FB01:TR02:ALHBCURR.VAL NPP MS")
  field(INPB, "FBCK:FB01:TR02:ALHBPREV.VAL NPP MS")
  field(INPC, "FBCK:FB01:TR02:ALHBCURR.SEVR")
  field(FLNK, "FBCK:FB01:TR02:ALHBERR")
}

# never in alarm; this is simply the status, not
# the final alarm PV.
record(mbbi, "FBCK:FB01:TR02:ALHBERR") {
  field(DESC, "FBCK:FB01:TR02 monitoring")
  field(FLNK, "FBCK:FB01:TR02:ALFBERRCALC")
  field(INP, "FBCK:FB01:TR02:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "FBCK:FB01:TR02:ALHBPREV")
}

record(ai, "FBCK:FB01:TR02:ALHBPREV") {
  field(INP,  "FBCK:FB01:TR02:ALHBCURR NPP MS")
  field(FLNK, "FBCK:FB01:TR02:ALFBERRCALC") 
}

# then see if the status is OK, but it's not incrementing
# (it thinks it's good, but it's not)
# feedback is on and not incrementing is an error
# if any input is invalid, then the status is invalid
# ALHBERR has no value severity, so can propagate its severity
# into the calc (to capture invalid)
# STATE itself could be major or minor; simply want to capture an
# invalid status here.
record(calc, "FBCK:FB01:TR02:ALFBERRCALC") {
  field(CALC, "C>2||D>2?2:((A=1&&B=1)?1:0)")
  field(INPA, "FBCK:FB01:TR02:STATE NPP NMS")
  field(INPB, "FBCK:FB01:TR02:ALHBERR NPP NMS")
  field(INPC, "FBCK:FB01:TR02:STATE.SEVR")
  field(INPD, "FBCK:FB01:TR02:ALHBERR.SEVR")
  field(FLNK, "FBCK:FB01:TR02:ALFBERR")
}

record(mbbi, "FBCK:FB01:TR02:ALFBERR") {
  field(DESC, "FBCK:FB01:TR02 monitoring")
  field(INP, "FBCK:FB01:TR02:ALFBERRCALC.VAL NPP MS")
  field(ZRST, "OK")
  field(ONST, "ON_NOT_RUNNING")
  field(TWST, "INVALID")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
}

#record(bi, "FBCK:FB01:TR02:ALFBERR") {
#  field(DESC, "FBCK:FB01:TR02 monitoring")
#  field(INP, "FBCK:FB01:TR02:ALFBERRCALC.VAL NPP MS")
#  field(ZSV, "NO_ALARM")
#  field(OSV, "MAJOR")
#  field(ZNAM, "OK")
#  field(ONAM, "ON_NOT_RUNNING")
#}

# VERSION FOR NEW FEEDBACKS (2/2011)
# only changing the names of incrementor PV to COUNTER from CNTDISP 
#
# Joe's matlab code
# for m = 1:num_feedbacks
#    ...
#    incr_ok = check_running(pv_data{n+1}, pv_data_last{n+1}); % the CNTDISP PV
#    green_ok = strcmp('ON', pv_data{n}); % the STATE PV 
#    if green_ok && (~incr_ok) % green, not incrementing
#       error_flag(n) = 1;
#    end
# end
# ======================================================

# check to see if feedback is incrementing (running)
record(calcout, "FBCK:FB01:TR03:ALSCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "FBCK:FB01:TR03:ALSCAN.VAL")
  field(INPB, "30")
  field(OUT, "FBCK:FB01:TR03:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "FBCK:FB01:TR03:ALHBCURR") {
  field(INP,  "FBCK:FB01:TR03:COUNTER NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "FBCK:FB01:TR03:ALHBCHK")
}

record(calc, "FBCK:FB01:TR03:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "FBCK:FB01:TR03:ALHBCURR.VAL NPP MS")
  field(INPB, "FBCK:FB01:TR03:ALHBPREV.VAL NPP MS")
  field(INPC, "FBCK:FB01:TR03:ALHBCURR.SEVR")
  field(FLNK, "FBCK:FB01:TR03:ALHBERR")
}

# never in alarm; this is simply the status, not
# the final alarm PV.
record(mbbi, "FBCK:FB01:TR03:ALHBERR") {
  field(DESC, "FBCK:FB01:TR03 monitoring")
  field(FLNK, "FBCK:FB01:TR03:ALFBERRCALC")
  field(INP, "FBCK:FB01:TR03:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "FBCK:FB01:TR03:ALHBPREV")
}

record(ai, "FBCK:FB01:TR03:ALHBPREV") {
  field(INP,  "FBCK:FB01:TR03:ALHBCURR NPP MS")
  field(FLNK, "FBCK:FB01:TR03:ALFBERRCALC") 
}

# then see if the status is OK, but it's not incrementing
# (it thinks it's good, but it's not)
# feedback is on and not incrementing is an error
# if any input is invalid, then the status is invalid
# ALHBERR has no value severity, so can propagate its severity
# into the calc (to capture invalid)
# STATE itself could be major or minor; simply want to capture an
# invalid status here.
record(calc, "FBCK:FB01:TR03:ALFBERRCALC") {
  field(CALC, "C>2||D>2?2:((A=1&&B=1)?1:0)")
  field(INPA, "FBCK:FB01:TR03:STATE NPP NMS")
  field(INPB, "FBCK:FB01:TR03:ALHBERR NPP NMS")
  field(INPC, "FBCK:FB01:TR03:STATE.SEVR")
  field(INPD, "FBCK:FB01:TR03:ALHBERR.SEVR")
  field(FLNK, "FBCK:FB01:TR03:ALFBERR")
}

record(mbbi, "FBCK:FB01:TR03:ALFBERR") {
  field(DESC, "FBCK:FB01:TR03 monitoring")
  field(INP, "FBCK:FB01:TR03:ALFBERRCALC.VAL NPP MS")
  field(ZRST, "OK")
  field(ONST, "ON_NOT_RUNNING")
  field(TWST, "INVALID")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
}

#record(bi, "FBCK:FB01:TR03:ALFBERR") {
#  field(DESC, "FBCK:FB01:TR03 monitoring")
#  field(INP, "FBCK:FB01:TR03:ALFBERRCALC.VAL NPP MS")
#  field(ZSV, "NO_ALARM")
#  field(OSV, "MAJOR")
#  field(ZNAM, "OK")
#  field(ONAM, "ON_NOT_RUNNING")
#}

# VERSION FOR NEW FEEDBACKS (2/2011)
# only changing the names of incrementor PV to COUNTER from CNTDISP 
#
# Joe's matlab code
# for m = 1:num_feedbacks
#    ...
#    incr_ok = check_running(pv_data{n+1}, pv_data_last{n+1}); % the CNTDISP PV
#    green_ok = strcmp('ON', pv_data{n}); % the STATE PV 
#    if green_ok && (~incr_ok) % green, not incrementing
#       error_flag(n) = 1;
#    end
# end
# ======================================================

# check to see if feedback is incrementing (running)
record(calcout, "FBCK:FB01:TR04:ALSCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "FBCK:FB01:TR04:ALSCAN.VAL")
  field(INPB, "30")
  field(OUT, "FBCK:FB01:TR04:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "FBCK:FB01:TR04:ALHBCURR") {
  field(INP,  "FBCK:FB01:TR04:COUNTER NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "FBCK:FB01:TR04:ALHBCHK")
}

record(calc, "FBCK:FB01:TR04:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "FBCK:FB01:TR04:ALHBCURR.VAL NPP MS")
  field(INPB, "FBCK:FB01:TR04:ALHBPREV.VAL NPP MS")
  field(INPC, "FBCK:FB01:TR04:ALHBCURR.SEVR")
  field(FLNK, "FBCK:FB01:TR04:ALHBERR")
}

# never in alarm; this is simply the status, not
# the final alarm PV.
record(mbbi, "FBCK:FB01:TR04:ALHBERR") {
  field(DESC, "FBCK:FB01:TR04 monitoring")
  field(FLNK, "FBCK:FB01:TR04:ALFBERRCALC")
  field(INP, "FBCK:FB01:TR04:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "FBCK:FB01:TR04:ALHBPREV")
}

record(ai, "FBCK:FB01:TR04:ALHBPREV") {
  field(INP,  "FBCK:FB01:TR04:ALHBCURR NPP MS")
  field(FLNK, "FBCK:FB01:TR04:ALFBERRCALC") 
}

# then see if the status is OK, but it's not incrementing
# (it thinks it's good, but it's not)
# feedback is on and not incrementing is an error
# if any input is invalid, then the status is invalid
# ALHBERR has no value severity, so can propagate its severity
# into the calc (to capture invalid)
# STATE itself could be major or minor; simply want to capture an
# invalid status here.
record(calc, "FBCK:FB01:TR04:ALFBERRCALC") {
  field(CALC, "C>2||D>2?2:((A=1&&B=1)?1:0)")
  field(INPA, "FBCK:FB01:TR04:STATE NPP NMS")
  field(INPB, "FBCK:FB01:TR04:ALHBERR NPP NMS")
  field(INPC, "FBCK:FB01:TR04:STATE.SEVR")
  field(INPD, "FBCK:FB01:TR04:ALHBERR.SEVR")
  field(FLNK, "FBCK:FB01:TR04:ALFBERR")
}

record(mbbi, "FBCK:FB01:TR04:ALFBERR") {
  field(DESC, "FBCK:FB01:TR04 monitoring")
  field(INP, "FBCK:FB01:TR04:ALFBERRCALC.VAL NPP MS")
  field(ZRST, "OK")
  field(ONST, "ON_NOT_RUNNING")
  field(TWST, "INVALID")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
}

#record(bi, "FBCK:FB01:TR04:ALFBERR") {
#  field(DESC, "FBCK:FB01:TR04 monitoring")
#  field(INP, "FBCK:FB01:TR04:ALFBERRCALC.VAL NPP MS")
#  field(ZSV, "NO_ALARM")
#  field(OSV, "MAJOR")
#  field(ZNAM, "OK")
#  field(ONAM, "ON_NOT_RUNNING")
#}

# VERSION FOR NEW FEEDBACKS (2/2011)
# only changing the names of incrementor PV to COUNTER from CNTDISP 
#
# Joe's matlab code
# for m = 1:num_feedbacks
#    ...
#    incr_ok = check_running(pv_data{n+1}, pv_data_last{n+1}); % the CNTDISP PV
#    green_ok = strcmp('ON', pv_data{n}); % the STATE PV 
#    if green_ok && (~incr_ok) % green, not incrementing
#       error_flag(n) = 1;
#    end
# end
# ======================================================

# check to see if feedback is incrementing (running)
record(calcout, "FBCK:FB02:TR01:ALSCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "FBCK:FB02:TR01:ALSCAN.VAL")
  field(INPB, "30")
  field(OUT, "FBCK:FB02:TR01:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "FBCK:FB02:TR01:ALHBCURR") {
  field(INP,  "FBCK:FB02:TR01:COUNTER NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "FBCK:FB02:TR01:ALHBCHK")
}

record(calc, "FBCK:FB02:TR01:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "FBCK:FB02:TR01:ALHBCURR.VAL NPP MS")
  field(INPB, "FBCK:FB02:TR01:ALHBPREV.VAL NPP MS")
  field(INPC, "FBCK:FB02:TR01:ALHBCURR.SEVR")
  field(FLNK, "FBCK:FB02:TR01:ALHBERR")
}

# never in alarm; this is simply the status, not
# the final alarm PV.
record(mbbi, "FBCK:FB02:TR01:ALHBERR") {
  field(DESC, "FBCK:FB02:TR01 monitoring")
  field(FLNK, "FBCK:FB02:TR01:ALFBERRCALC")
  field(INP, "FBCK:FB02:TR01:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "FBCK:FB02:TR01:ALHBPREV")
}

record(ai, "FBCK:FB02:TR01:ALHBPREV") {
  field(INP,  "FBCK:FB02:TR01:ALHBCURR NPP MS")
  field(FLNK, "FBCK:FB02:TR01:ALFBERRCALC") 
}

# then see if the status is OK, but it's not incrementing
# (it thinks it's good, but it's not)
# feedback is on and not incrementing is an error
# if any input is invalid, then the status is invalid
# ALHBERR has no value severity, so can propagate its severity
# into the calc (to capture invalid)
# STATE itself could be major or minor; simply want to capture an
# invalid status here.
record(calc, "FBCK:FB02:TR01:ALFBERRCALC") {
  field(CALC, "C>2||D>2?2:((A=1&&B=1)?1:0)")
  field(INPA, "FBCK:FB02:TR01:STATE NPP NMS")
  field(INPB, "FBCK:FB02:TR01:ALHBERR NPP NMS")
  field(INPC, "FBCK:FB02:TR01:STATE.SEVR")
  field(INPD, "FBCK:FB02:TR01:ALHBERR.SEVR")
  field(FLNK, "FBCK:FB02:TR01:ALFBERR")
}

record(mbbi, "FBCK:FB02:TR01:ALFBERR") {
  field(DESC, "FBCK:FB02:TR01 monitoring")
  field(INP, "FBCK:FB02:TR01:ALFBERRCALC.VAL NPP MS")
  field(ZRST, "OK")
  field(ONST, "ON_NOT_RUNNING")
  field(TWST, "INVALID")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
}

#record(bi, "FBCK:FB02:TR01:ALFBERR") {
#  field(DESC, "FBCK:FB02:TR01 monitoring")
#  field(INP, "FBCK:FB02:TR01:ALFBERRCALC.VAL NPP MS")
#  field(ZSV, "NO_ALARM")
#  field(OSV, "MAJOR")
#  field(ZNAM, "OK")
#  field(ONAM, "ON_NOT_RUNNING")
#}

# VERSION FOR NEW FEEDBACKS (2/2011)
# only changing the names of incrementor PV to COUNTER from CNTDISP 
#
# Joe's matlab code
# for m = 1:num_feedbacks
#    ...
#    incr_ok = check_running(pv_data{n+1}, pv_data_last{n+1}); % the CNTDISP PV
#    green_ok = strcmp('ON', pv_data{n}); % the STATE PV 
#    if green_ok && (~incr_ok) % green, not incrementing
#       error_flag(n) = 1;
#    end
# end
# ======================================================

# check to see if feedback is incrementing (running)
record(calcout, "FBCK:FB02:TR02:ALSCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "FBCK:FB02:TR02:ALSCAN.VAL")
  field(INPB, "30")
  field(OUT, "FBCK:FB02:TR02:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "FBCK:FB02:TR02:ALHBCURR") {
  field(INP,  "FBCK:FB02:TR02:COUNTER NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "FBCK:FB02:TR02:ALHBCHK")
}

record(calc, "FBCK:FB02:TR02:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "FBCK:FB02:TR02:ALHBCURR.VAL NPP MS")
  field(INPB, "FBCK:FB02:TR02:ALHBPREV.VAL NPP MS")
  field(INPC, "FBCK:FB02:TR02:ALHBCURR.SEVR")
  field(FLNK, "FBCK:FB02:TR02:ALHBERR")
}

# never in alarm; this is simply the status, not
# the final alarm PV.
record(mbbi, "FBCK:FB02:TR02:ALHBERR") {
  field(DESC, "FBCK:FB02:TR02 monitoring")
  field(FLNK, "FBCK:FB02:TR02:ALFBERRCALC")
  field(INP, "FBCK:FB02:TR02:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "FBCK:FB02:TR02:ALHBPREV")
}

record(ai, "FBCK:FB02:TR02:ALHBPREV") {
  field(INP,  "FBCK:FB02:TR02:ALHBCURR NPP MS")
  field(FLNK, "FBCK:FB02:TR02:ALFBERRCALC") 
}

# then see if the status is OK, but it's not incrementing
# (it thinks it's good, but it's not)
# feedback is on and not incrementing is an error
# if any input is invalid, then the status is invalid
# ALHBERR has no value severity, so can propagate its severity
# into the calc (to capture invalid)
# STATE itself could be major or minor; simply want to capture an
# invalid status here.
record(calc, "FBCK:FB02:TR02:ALFBERRCALC") {
  field(CALC, "C>2||D>2?2:((A=1&&B=1)?1:0)")
  field(INPA, "FBCK:FB02:TR02:STATE NPP NMS")
  field(INPB, "FBCK:FB02:TR02:ALHBERR NPP NMS")
  field(INPC, "FBCK:FB02:TR02:STATE.SEVR")
  field(INPD, "FBCK:FB02:TR02:ALHBERR.SEVR")
  field(FLNK, "FBCK:FB02:TR02:ALFBERR")
}

record(mbbi, "FBCK:FB02:TR02:ALFBERR") {
  field(DESC, "FBCK:FB02:TR02 monitoring")
  field(INP, "FBCK:FB02:TR02:ALFBERRCALC.VAL NPP MS")
  field(ZRST, "OK")
  field(ONST, "ON_NOT_RUNNING")
  field(TWST, "INVALID")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
}

#record(bi, "FBCK:FB02:TR02:ALFBERR") {
#  field(DESC, "FBCK:FB02:TR02 monitoring")
#  field(INP, "FBCK:FB02:TR02:ALFBERRCALC.VAL NPP MS")
#  field(ZSV, "NO_ALARM")
#  field(OSV, "MAJOR")
#  field(ZNAM, "OK")
#  field(ONAM, "ON_NOT_RUNNING")
#}

# VERSION FOR NEW FEEDBACKS (2/2011)
# only changing the names of incrementor PV to COUNTER from CNTDISP 
#
# Joe's matlab code
# for m = 1:num_feedbacks
#    ...
#    incr_ok = check_running(pv_data{n+1}, pv_data_last{n+1}); % the CNTDISP PV
#    green_ok = strcmp('ON', pv_data{n}); % the STATE PV 
#    if green_ok && (~incr_ok) % green, not incrementing
#       error_flag(n) = 1;
#    end
# end
# ======================================================

# check to see if feedback is incrementing (running)
record(calcout, "FBCK:FB02:TR03:ALSCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "FBCK:FB02:TR03:ALSCAN.VAL")
  field(INPB, "30")
  field(OUT, "FBCK:FB02:TR03:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "FBCK:FB02:TR03:ALHBCURR") {
  field(INP,  "FBCK:FB02:TR03:COUNTER NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "FBCK:FB02:TR03:ALHBCHK")
}

record(calc, "FBCK:FB02:TR03:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "FBCK:FB02:TR03:ALHBCURR.VAL NPP MS")
  field(INPB, "FBCK:FB02:TR03:ALHBPREV.VAL NPP MS")
  field(INPC, "FBCK:FB02:TR03:ALHBCURR.SEVR")
  field(FLNK, "FBCK:FB02:TR03:ALHBERR")
}

# never in alarm; this is simply the status, not
# the final alarm PV.
record(mbbi, "FBCK:FB02:TR03:ALHBERR") {
  field(DESC, "FBCK:FB02:TR03 monitoring")
  field(FLNK, "FBCK:FB02:TR03:ALFBERRCALC")
  field(INP, "FBCK:FB02:TR03:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "FBCK:FB02:TR03:ALHBPREV")
}

record(ai, "FBCK:FB02:TR03:ALHBPREV") {
  field(INP,  "FBCK:FB02:TR03:ALHBCURR NPP MS")
  field(FLNK, "FBCK:FB02:TR03:ALFBERRCALC") 
}

# then see if the status is OK, but it's not incrementing
# (it thinks it's good, but it's not)
# feedback is on and not incrementing is an error
# if any input is invalid, then the status is invalid
# ALHBERR has no value severity, so can propagate its severity
# into the calc (to capture invalid)
# STATE itself could be major or minor; simply want to capture an
# invalid status here.
record(calc, "FBCK:FB02:TR03:ALFBERRCALC") {
  field(CALC, "C>2||D>2?2:((A=1&&B=1)?1:0)")
  field(INPA, "FBCK:FB02:TR03:STATE NPP NMS")
  field(INPB, "FBCK:FB02:TR03:ALHBERR NPP NMS")
  field(INPC, "FBCK:FB02:TR03:STATE.SEVR")
  field(INPD, "FBCK:FB02:TR03:ALHBERR.SEVR")
  field(FLNK, "FBCK:FB02:TR03:ALFBERR")
}

record(mbbi, "FBCK:FB02:TR03:ALFBERR") {
  field(DESC, "FBCK:FB02:TR03 monitoring")
  field(INP, "FBCK:FB02:TR03:ALFBERRCALC.VAL NPP MS")
  field(ZRST, "OK")
  field(ONST, "ON_NOT_RUNNING")
  field(TWST, "INVALID")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
}

#record(bi, "FBCK:FB02:TR03:ALFBERR") {
#  field(DESC, "FBCK:FB02:TR03 monitoring")
#  field(INP, "FBCK:FB02:TR03:ALFBERRCALC.VAL NPP MS")
#  field(ZSV, "NO_ALARM")
#  field(OSV, "MAJOR")
#  field(ZNAM, "OK")
#  field(ONAM, "ON_NOT_RUNNING")
#}

# VERSION FOR NEW FEEDBACKS (2/2011)
# only changing the names of incrementor PV to COUNTER from CNTDISP 
#
# Joe's matlab code
# for m = 1:num_feedbacks
#    ...
#    incr_ok = check_running(pv_data{n+1}, pv_data_last{n+1}); % the CNTDISP PV
#    green_ok = strcmp('ON', pv_data{n}); % the STATE PV 
#    if green_ok && (~incr_ok) % green, not incrementing
#       error_flag(n) = 1;
#    end
# end
# ======================================================

# check to see if feedback is incrementing (running)
record(calcout, "FBCK:FB02:TR04:ALSCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "FBCK:FB02:TR04:ALSCAN.VAL")
  field(INPB, "30")
  field(OUT, "FBCK:FB02:TR04:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "FBCK:FB02:TR04:ALHBCURR") {
  field(INP,  "FBCK:FB02:TR04:COUNTER NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "FBCK:FB02:TR04:ALHBCHK")
}

record(calc, "FBCK:FB02:TR04:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "FBCK:FB02:TR04:ALHBCURR.VAL NPP MS")
  field(INPB, "FBCK:FB02:TR04:ALHBPREV.VAL NPP MS")
  field(INPC, "FBCK:FB02:TR04:ALHBCURR.SEVR")
  field(FLNK, "FBCK:FB02:TR04:ALHBERR")
}

# never in alarm; this is simply the status, not
# the final alarm PV.
record(mbbi, "FBCK:FB02:TR04:ALHBERR") {
  field(DESC, "FBCK:FB02:TR04 monitoring")
  field(FLNK, "FBCK:FB02:TR04:ALFBERRCALC")
  field(INP, "FBCK:FB02:TR04:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "FBCK:FB02:TR04:ALHBPREV")
}

record(ai, "FBCK:FB02:TR04:ALHBPREV") {
  field(INP,  "FBCK:FB02:TR04:ALHBCURR NPP MS")
  field(FLNK, "FBCK:FB02:TR04:ALFBERRCALC") 
}

# then see if the status is OK, but it's not incrementing
# (it thinks it's good, but it's not)
# feedback is on and not incrementing is an error
# if any input is invalid, then the status is invalid
# ALHBERR has no value severity, so can propagate its severity
# into the calc (to capture invalid)
# STATE itself could be major or minor; simply want to capture an
# invalid status here.
record(calc, "FBCK:FB02:TR04:ALFBERRCALC") {
  field(CALC, "C>2||D>2?2:((A=1&&B=1)?1:0)")
  field(INPA, "FBCK:FB02:TR04:STATE NPP NMS")
  field(INPB, "FBCK:FB02:TR04:ALHBERR NPP NMS")
  field(INPC, "FBCK:FB02:TR04:STATE.SEVR")
  field(INPD, "FBCK:FB02:TR04:ALHBERR.SEVR")
  field(FLNK, "FBCK:FB02:TR04:ALFBERR")
}

record(mbbi, "FBCK:FB02:TR04:ALFBERR") {
  field(DESC, "FBCK:FB02:TR04 monitoring")
  field(INP, "FBCK:FB02:TR04:ALFBERRCALC.VAL NPP MS")
  field(ZRST, "OK")
  field(ONST, "ON_NOT_RUNNING")
  field(TWST, "INVALID")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
}

#record(bi, "FBCK:FB02:TR04:ALFBERR") {
#  field(DESC, "FBCK:FB02:TR04 monitoring")
#  field(INP, "FBCK:FB02:TR04:ALFBERRCALC.VAL NPP MS")
#  field(ZSV, "NO_ALARM")
#  field(OSV, "MAJOR")
#  field(ZNAM, "OK")
#  field(ONAM, "ON_NOT_RUNNING")
#}

# VERSION FOR NEW FEEDBACKS (2/2011)
# only changing the names of incrementor PV to COUNTER from CNTDISP 
#
# Joe's matlab code
# for m = 1:num_feedbacks
#    ...
#    incr_ok = check_running(pv_data{n+1}, pv_data_last{n+1}); % the CNTDISP PV
#    green_ok = strcmp('ON', pv_data{n}); % the STATE PV 
#    if green_ok && (~incr_ok) % green, not incrementing
#       error_flag(n) = 1;
#    end
# end
# ======================================================

# check to see if feedback is incrementing (running)
record(calcout, "FBCK:FB03:TR01:ALSCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "FBCK:FB03:TR01:ALSCAN.VAL")
  field(INPB, "30")
  field(OUT, "FBCK:FB03:TR01:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "FBCK:FB03:TR01:ALHBCURR") {
  field(INP,  "FBCK:FB03:TR01:COUNTER NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "FBCK:FB03:TR01:ALHBCHK")
}

record(calc, "FBCK:FB03:TR01:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "FBCK:FB03:TR01:ALHBCURR.VAL NPP MS")
  field(INPB, "FBCK:FB03:TR01:ALHBPREV.VAL NPP MS")
  field(INPC, "FBCK:FB03:TR01:ALHBCURR.SEVR")
  field(FLNK, "FBCK:FB03:TR01:ALHBERR")
}

# never in alarm; this is simply the status, not
# the final alarm PV.
record(mbbi, "FBCK:FB03:TR01:ALHBERR") {
  field(DESC, "FBCK:FB03:TR01 monitoring")
  field(FLNK, "FBCK:FB03:TR01:ALFBERRCALC")
  field(INP, "FBCK:FB03:TR01:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "FBCK:FB03:TR01:ALHBPREV")
}

record(ai, "FBCK:FB03:TR01:ALHBPREV") {
  field(INP,  "FBCK:FB03:TR01:ALHBCURR NPP MS")
  field(FLNK, "FBCK:FB03:TR01:ALFBERRCALC") 
}

# then see if the status is OK, but it's not incrementing
# (it thinks it's good, but it's not)
# feedback is on and not incrementing is an error
# if any input is invalid, then the status is invalid
# ALHBERR has no value severity, so can propagate its severity
# into the calc (to capture invalid)
# STATE itself could be major or minor; simply want to capture an
# invalid status here.
record(calc, "FBCK:FB03:TR01:ALFBERRCALC") {
  field(CALC, "C>2||D>2?2:((A=1&&B=1)?1:0)")
  field(INPA, "FBCK:FB03:TR01:STATE NPP NMS")
  field(INPB, "FBCK:FB03:TR01:ALHBERR NPP NMS")
  field(INPC, "FBCK:FB03:TR01:STATE.SEVR")
  field(INPD, "FBCK:FB03:TR01:ALHBERR.SEVR")
  field(FLNK, "FBCK:FB03:TR01:ALFBERR")
}

record(mbbi, "FBCK:FB03:TR01:ALFBERR") {
  field(DESC, "FBCK:FB03:TR01 monitoring")
  field(INP, "FBCK:FB03:TR01:ALFBERRCALC.VAL NPP MS")
  field(ZRST, "OK")
  field(ONST, "ON_NOT_RUNNING")
  field(TWST, "INVALID")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
}

#record(bi, "FBCK:FB03:TR01:ALFBERR") {
#  field(DESC, "FBCK:FB03:TR01 monitoring")
#  field(INP, "FBCK:FB03:TR01:ALFBERRCALC.VAL NPP MS")
#  field(ZSV, "NO_ALARM")
#  field(OSV, "MAJOR")
#  field(ZNAM, "OK")
#  field(ONAM, "ON_NOT_RUNNING")
#}

# VERSION FOR NEW FEEDBACKS (2/2011)
# only changing the names of incrementor PV to COUNTER from CNTDISP 
#
# Joe's matlab code
# for m = 1:num_feedbacks
#    ...
#    incr_ok = check_running(pv_data{n+1}, pv_data_last{n+1}); % the CNTDISP PV
#    green_ok = strcmp('ON', pv_data{n}); % the STATE PV 
#    if green_ok && (~incr_ok) % green, not incrementing
#       error_flag(n) = 1;
#    end
# end
# ======================================================

# check to see if feedback is incrementing (running)
record(calcout, "FBCK:FB04:LG01:ALSCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "FBCK:FB04:LG01:ALSCAN.VAL")
  field(INPB, "30")
  field(OUT, "FBCK:FB04:LG01:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "FBCK:FB04:LG01:ALHBCURR") {
  field(INP,  "FBCK:FB04:LG01:COUNTER NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "FBCK:FB04:LG01:ALHBCHK")
}

record(calc, "FBCK:FB04:LG01:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "FBCK:FB04:LG01:ALHBCURR.VAL NPP MS")
  field(INPB, "FBCK:FB04:LG01:ALHBPREV.VAL NPP MS")
  field(INPC, "FBCK:FB04:LG01:ALHBCURR.SEVR")
  field(FLNK, "FBCK:FB04:LG01:ALHBERR")
}

# never in alarm; this is simply the status, not
# the final alarm PV.
record(mbbi, "FBCK:FB04:LG01:ALHBERR") {
  field(DESC, "FBCK:FB04:LG01 monitoring")
  field(FLNK, "FBCK:FB04:LG01:ALFBERRCALC")
  field(INP, "FBCK:FB04:LG01:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "FBCK:FB04:LG01:ALHBPREV")
}

record(ai, "FBCK:FB04:LG01:ALHBPREV") {
  field(INP,  "FBCK:FB04:LG01:ALHBCURR NPP MS")
  field(FLNK, "FBCK:FB04:LG01:ALFBERRCALC") 
}

# then see if the status is OK, but it's not incrementing
# (it thinks it's good, but it's not)
# feedback is on and not incrementing is an error
# if any input is invalid, then the status is invalid
# ALHBERR has no value severity, so can propagate its severity
# into the calc (to capture invalid)
# STATE itself could be major or minor; simply want to capture an
# invalid status here.
record(calc, "FBCK:FB04:LG01:ALFBERRCALC") {
  field(CALC, "C>2||D>2?2:((A=1&&B=1)?1:0)")
  field(INPA, "FBCK:FB04:LG01:STATE NPP NMS")
  field(INPB, "FBCK:FB04:LG01:ALHBERR NPP NMS")
  field(INPC, "FBCK:FB04:LG01:STATE.SEVR")
  field(INPD, "FBCK:FB04:LG01:ALHBERR.SEVR")
  field(FLNK, "FBCK:FB04:LG01:ALFBERR")
}

record(mbbi, "FBCK:FB04:LG01:ALFBERR") {
  field(DESC, "FBCK:FB04:LG01 monitoring")
  field(INP, "FBCK:FB04:LG01:ALFBERRCALC.VAL NPP MS")
  field(ZRST, "OK")
  field(ONST, "ON_NOT_RUNNING")
  field(TWST, "INVALID")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
}

#record(bi, "FBCK:FB04:LG01:ALFBERR") {
#  field(DESC, "FBCK:FB04:LG01 monitoring")
#  field(INP, "FBCK:FB04:LG01:ALFBERRCALC.VAL NPP MS")
#  field(ZSV, "NO_ALARM")
#  field(OSV, "MAJOR")
#  field(ZNAM, "OK")
#  field(ONAM, "ON_NOT_RUNNING")
#}

# VERSION FOR NEW FEEDBACKS (2/2011)
# only changing the names of incrementor PV to COUNTER from CNTDISP 
#
# Joe's matlab code
# for m = 1:num_feedbacks
#    ...
#    incr_ok = check_running(pv_data{n+1}, pv_data_last{n+1}); % the CNTDISP PV
#    green_ok = strcmp('ON', pv_data{n}); % the STATE PV 
#    if green_ok && (~incr_ok) % green, not incrementing
#       error_flag(n) = 1;
#    end
# end
# ======================================================

# check to see if feedback is incrementing (running)
record(calcout, "FBCK:FB02:GN01:ALSCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "FBCK:FB02:GN01:ALSCAN.VAL")
  field(INPB, "30")
  field(OUT, "FBCK:FB02:GN01:ALHBCURR.VAL PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(ai, "FBCK:FB02:GN01:ALHBCURR") {
  field(INP,  "FBCK:FB02:GN01:COUNTER NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "FBCK:FB02:GN01:ALHBCHK")
}

record(calc, "FBCK:FB02:GN01:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "FBCK:FB02:GN01:ALHBCURR.VAL NPP MS")
  field(INPB, "FBCK:FB02:GN01:ALHBPREV.VAL NPP MS")
  field(INPC, "FBCK:FB02:GN01:ALHBCURR.SEVR")
  field(FLNK, "FBCK:FB02:GN01:ALHBERR")
}

# never in alarm; this is simply the status, not
# the final alarm PV.
record(mbbi, "FBCK:FB02:GN01:ALHBERR") {
  field(DESC, "FBCK:FB02:GN01 monitoring")
  field(FLNK, "FBCK:FB02:GN01:ALFBERRCALC")
  field(INP, "FBCK:FB02:GN01:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "FBCK:FB02:GN01:ALHBPREV")
}

record(ai, "FBCK:FB02:GN01:ALHBPREV") {
  field(INP,  "FBCK:FB02:GN01:ALHBCURR NPP MS")
  field(FLNK, "FBCK:FB02:GN01:ALFBERRCALC") 
}

# then see if the status is OK, but it's not incrementing
# (it thinks it's good, but it's not)
# feedback is on and not incrementing is an error
# if any input is invalid, then the status is invalid
# ALHBERR has no value severity, so can propagate its severity
# into the calc (to capture invalid)
# STATE itself could be major or minor; simply want to capture an
# invalid status here.
record(calc, "FBCK:FB02:GN01:ALFBERRCALC") {
  field(CALC, "C>2||D>2?2:((A=1&&B=1)?1:0)")
  field(INPA, "FBCK:FB02:GN01:STATE NPP NMS")
  field(INPB, "FBCK:FB02:GN01:ALHBERR NPP NMS")
  field(INPC, "FBCK:FB02:GN01:STATE.SEVR")
  field(INPD, "FBCK:FB02:GN01:ALHBERR.SEVR")
  field(FLNK, "FBCK:FB02:GN01:ALFBERR")
}

record(mbbi, "FBCK:FB02:GN01:ALFBERR") {
  field(DESC, "FBCK:FB02:GN01 monitoring")
  field(INP, "FBCK:FB02:GN01:ALFBERRCALC.VAL NPP MS")
  field(ZRST, "OK")
  field(ONST, "ON_NOT_RUNNING")
  field(TWST, "INVALID")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
}

#record(bi, "FBCK:FB02:GN01:ALFBERR") {
#  field(DESC, "FBCK:FB02:GN01 monitoring")
#  field(INP, "FBCK:FB02:GN01:ALFBERRCALC.VAL NPP MS")
#  field(ZSV, "NO_ALARM")
#  field(OSV, "MAJOR")
#  field(ZNAM, "OK")
#  field(ONAM, "ON_NOT_RUNNING")
#}

# sets high and low alarm limits based on a tol
# desired value and tols value are set in ML PVs
# =======================================================
record(calc, "ALRM:SYS0:BC1:ALTOLERR") {
  field(CALC, "(A>(B+C))||(A<(B-C))?1:0")
  field(SCAN, "5 second")
  field(INPA, "BMLN:LI21:235:LVPOS NPP MS")
  field(INPB, "SIOC:SYS0:ML00:AO117 NPP MS")
  field(INPC, "SIOC:SYS0:ML00:AO142 NPP MS")
  field(HIHI, "1")
  field(HHSV, "MAJOR")
  field(LOLO, "-1")
  field(LLSV, "MAJOR")
}

# sets high and low alarm limits based on a tol
# desired value and tols value are set in ML PVs
# =======================================================
record(calc, "ALRM:SYS0:BC2:ALTOLERR") {
  field(CALC, "(A>(B+C))||(A<(B-C))?1:0")
  field(SCAN, "5 second")
  field(INPA, "BMLN:LI24:805:LVPOS NPP MS")
  field(INPB, "SIOC:SYS0:ML00:AO120 NPP MS")
  field(INPC, "SIOC:SYS0:ML00:AO145 NPP MS")
  field(HIHI, "1")
  field(HHSV, "MAJOR")
  field(LOLO, "-1")
  field(LLSV, "MAJOR")
}

# Joe's matlab code:
#function mag_ok = check_MADDNAME(bend_txt, btrim_txt)
#btrim_min = -1.1;
#btrim_max = -1;
#if abs(bend) < 1e-3 % bend is off
#    if (btrim < btrim_max) && (btrim > btrim_min)
#        mag_ok = 1; % OK
#    else
#        mag_ok = 0;
#    end
#else  % Bend is ON
#    if abs(btrim) < .02;
#        mag_ok = 1;
#    else
#        mag_ok = 0;
#    end
#end
#end
# =================================================

# First of all, is the BEND ON?  1 = YES, 0 = NO
record(calc, "BEND:IN20:231:ALMGNTON") {
  field(CALC, "(ABS(A)<B)?0:1")
  field(SCAN, "1 second")
  field(INPA, "BEND:IN20:231:BACT NPP NMS")
  field(INPB, ".001")
  field(FLNK, "ALRM:SYS0:BXG:MAGSINV")
}

# calculate whether the magnet is in error
# with respect to BEND on-ness and BTRM:BACT values
# if either magnet is INVALID, then this calc is set to
# 2 (invalid)

# first, is either magnet BACT invalid?
# this has to be a separate record to keep the
# calc expression in ALMGNTERRCALC short enough!
# 1 if yes, 0 if no
record(calc, "ALRM:SYS0:BXG:MAGSINV") {
  field(CALC, "A>2||B>2?1:0")
  field(INPA, "BEND:IN20:231:BACT.SEVR")
  field(INPB, "BTRM:IN20:231:BACT.SEVR")
  field(FLNK, "ALRM:SYS0:BXG:ALMGNTERRCALC")
}
record(calc, "ALRM:SYS0:BXG:ALMGNTERRCALC") {
  field(CALC, "F=1?2:A=1?(ABS(B)<E?0:1):(B>C&&B<D?0:1)")
  field(INPA, "BEND:IN20:231:ALMGNTON")
  field(INPB, "BTRM:IN20:231:BACT")
  field(INPC, "-0.8")
  field(INPD, "-0.5")
  field(INPE, ".02")
  field(INPF, "ALRM:SYS0:BXG:MAGSINV")
  field(FLNK, "ALRM:SYS0:BXG:ALMGNTERR")
}

# put the result into a bi for names and alarm statuses
# 0 is good, 1 is bad, 2 is invalid
record(mbbi, "ALRM:SYS0:BXG:ALMGNTERR") {
  field(DESC, "BXG Checking")
  field(INP, "ALRM:SYS0:BXG:ALMGNTERRCALC.VAL")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "OK")
  field(ONST, "FAULT")
  field(TWST, "INVALID")
}

# Joe's watcher code
# if bitand(str2double(tmp),2^15) % klystron deactivated
#    error_flag(n) = 1;
# end
# ===================================================== 
# make "deactivated" mask
record(calc, KLYS:ACTIVE:MASK) {
  field(CALC, "2**15")
  field(PINI, "YES")
}

# USE A HARDCODED NUMBER INSTEAD: THE CALC'ed VALUE DOES NOT WORK!
# do the bitwise and and see if non-0
# 1 if DEACTIVATED, 0 if ACTIVE
# SWRD comes from VMS and has no SEVR
# therefore, invalid indicates that this channel is
# unavailable, which will make the final result invalid.
record(calc, LI21:KLYS:3:ALDEACTCALC) {
  field(CALC, "A&B?1:0")
  field(INPA, "LI21:KLYS:31:SWRD NPP MS")
  field(INPB, "32768")
  field(SCAN, "1 second")
  field(FLNK, "LI21:KLYS:3:ALDEACT")
}

# put the result into a bi for state names and alarm statuses
record(bi, "LI21:KLYS:3:ALDEACT") {
  field(DESC, "LI21:KLYS:3 check")
  field(INP, "LI21:KLYS:3:ALDEACTCALC.VAL NPP MS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "ACTIVE")
  field(ONAM, "DEACTIVATED")
}

# Joe's watcher code
# if bitand(str2double(tmp),2^15) % klystron deactivated
#    error_flag(n) = 1;
# end
# ===================================================== 
# make "deactivated" mask
record(calc, KLYS:ACTIVE:MASK) {
  field(CALC, "2**15")
  field(PINI, "YES")
}

# USE A HARDCODED NUMBER INSTEAD: THE CALC'ed VALUE DOES NOT WORK!
# do the bitwise and and see if non-0
# 1 if DEACTIVATED, 0 if ACTIVE
# SWRD comes from VMS and has no SEVR
# therefore, invalid indicates that this channel is
# unavailable, which will make the final result invalid.
record(calc, LI21:KLYS:4:ALDEACTCALC) {
  field(CALC, "A&B?1:0")
  field(INPA, "LI21:KLYS:41:SWRD NPP MS")
  field(INPB, "32768")
  field(SCAN, "1 second")
  field(FLNK, "LI21:KLYS:4:ALDEACT")
}

# put the result into a bi for state names and alarm statuses
record(bi, "LI21:KLYS:4:ALDEACT") {
  field(DESC, "LI21:KLYS:4 check")
  field(INP, "LI21:KLYS:4:ALDEACTCALC.VAL NPP MS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "ACTIVE")
  field(ONAM, "DEACTIVATED")
}

# Joe's watcher code
# if bitand(str2double(tmp),2^15) % klystron deactivated
#    error_flag(n) = 1;
# end
# ===================================================== 
# make "deactivated" mask
record(calc, KLYS:ACTIVE:MASK) {
  field(CALC, "2**15")
  field(PINI, "YES")
}

# USE A HARDCODED NUMBER INSTEAD: THE CALC'ed VALUE DOES NOT WORK!
# do the bitwise and and see if non-0
# 1 if DEACTIVATED, 0 if ACTIVE
# SWRD comes from VMS and has no SEVR
# therefore, invalid indicates that this channel is
# unavailable, which will make the final result invalid.
record(calc, LI21:KLYS:5:ALDEACTCALC) {
  field(CALC, "A&B?1:0")
  field(INPA, "LI21:KLYS:51:SWRD NPP MS")
  field(INPB, "32768")
  field(SCAN, "1 second")
  field(FLNK, "LI21:KLYS:5:ALDEACT")
}

# put the result into a bi for state names and alarm statuses
record(bi, "LI21:KLYS:5:ALDEACT") {
  field(DESC, "LI21:KLYS:5 check")
  field(INP, "LI21:KLYS:5:ALDEACTCALC.VAL NPP MS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "ACTIVE")
  field(ONAM, "DEACTIVATED")
}

# Joe's watcher code
# if bitand(str2double(tmp),2^15) % klystron deactivated
#    error_flag(n) = 1;
# end
# ===================================================== 
# make "deactivated" mask
record(calc, KLYS:ACTIVE:MASK) {
  field(CALC, "2**15")
  field(PINI, "YES")
}

# USE A HARDCODED NUMBER INSTEAD: THE CALC'ed VALUE DOES NOT WORK!
# do the bitwise and and see if non-0
# 1 if DEACTIVATED, 0 if ACTIVE
# SWRD comes from VMS and has no SEVR
# therefore, invalid indicates that this channel is
# unavailable, which will make the final result invalid.
record(calc, LI21:KLYS:6:ALDEACTCALC) {
  field(CALC, "A&B?1:0")
  field(INPA, "LI21:KLYS:61:SWRD NPP MS")
  field(INPB, "32768")
  field(SCAN, "1 second")
  field(FLNK, "LI21:KLYS:6:ALDEACT")
}

# put the result into a bi for state names and alarm statuses
record(bi, "LI21:KLYS:6:ALDEACT") {
  field(DESC, "LI21:KLYS:6 check")
  field(INP, "LI21:KLYS:6:ALDEACTCALC.VAL NPP MS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "ACTIVE")
  field(ONAM, "DEACTIVATED")
}

# Joe's matlab code:
# ...
# %if (bdes ~= bcon)
# if abs((bdes - bcon))/max(abs(bdes), abs(bcon)) > 2e-4
#    error_flag(n) = 1;
# end
# ===========================================================

# BDES is not at BCON, within tolerance

# to avoid divide-by-zero
record(calc, "SOLN:IN20:121:TESTFOR0") {
  field(DESC, "SOLN:IN20:121 monitoring")
  field(SCAN, "1 second")
  field(CALC, "(A=0&&B=0)?1:0")
  field(INPA, "SOLN:IN20:121:BDES")
  field(INPB, "SOLN:IN20:121:BCON")
  field(FLNK, "SOLN:IN20:121:PVSINV")
}

# check for invalid PVs
record(calc, "SOLN:IN20:121:PVSINV") {
  field(CALC, "A>2||B>2?1:0")
  field(INPA, "SOLN:IN20:121:BDES.SEVR")
  field(INPB, "SOLN:IN20:121:BCON.SEVR")
  field(FLNK, "SOLN:IN20:121:ALDESERRCALC")
}

# do the calc
record(calc, "SOLN:IN20:121:ALDESERRCALC") {
  field(DESC, "SOLN:IN20:121 monitoring")
  field(CALC, "D=1?0:ABS(A-B)/MAX(ABS(A),ABS(B))>C?1:0")
  field(INPA, "SOLN:IN20:121:BDES")
  field(INPB, "SOLN:IN20:121:BCON")
  field(INPC, .0002)
  field(INPD, "SOLN:IN20:121:TESTFOR0")
  field(FLNK, "SOLN:IN20:121:ALDESERRSEVR")
}

# combine the calc with the possibility of invalid PVs 
# which sets the final result invalid
record(calc, "SOLN:IN20:121:ALDESERRSEVR") {
  field(DESC, "SOLN:IN20:121 monitoring")
  field(CALC, "B=1?2:A")
  field(INPA, "SOLN:IN20:121:ALDESERRCALC")
  field(INPB, "SOLN:IN20:121:PVSINV")
  field(FLNK, "SOLN:IN20:121:ALDESERR")
}

# put the result into a bi for names and alarm statuses
record(mbbi, "SOLN:IN20:121:ALDESERR") {
  field(DESC, "SOLN:IN20:121 monitoring")
  field(INP, "SOLN:IN20:121:ALDESERRSEVR.VAL")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "OK")
  field(ONST, "FAULT")
  field(TWST, "INVALID")
}

# Joe's matlab code:
# ...
# %if (bdes ~= bcon)
# if abs((bdes - bcon))/max(abs(bdes), abs(bcon)) > 2e-4
#    error_flag(n) = 1;
# end
# ===========================================================

# BDES is not at BCON, within tolerance

# to avoid divide-by-zero
record(calc, "QUAD:IN20:121:TESTFOR0") {
  field(DESC, "QUAD:IN20:121 monitoring")
  field(SCAN, "1 second")
  field(CALC, "(A=0&&B=0)?1:0")
  field(INPA, "QUAD:IN20:121:BDES")
  field(INPB, "QUAD:IN20:121:BCON")
  field(FLNK, "QUAD:IN20:121:PVSINV")
}

# check for invalid PVs
record(calc, "QUAD:IN20:121:PVSINV") {
  field(CALC, "A>2||B>2?1:0")
  field(INPA, "QUAD:IN20:121:BDES.SEVR")
  field(INPB, "QUAD:IN20:121:BCON.SEVR")
  field(FLNK, "QUAD:IN20:121:ALDESERRCALC")
}

# do the calc
record(calc, "QUAD:IN20:121:ALDESERRCALC") {
  field(DESC, "QUAD:IN20:121 monitoring")
  field(CALC, "D=1?0:ABS(A-B)/MAX(ABS(A),ABS(B))>C?1:0")
  field(INPA, "QUAD:IN20:121:BDES")
  field(INPB, "QUAD:IN20:121:BCON")
  field(INPC, .0002)
  field(INPD, "QUAD:IN20:121:TESTFOR0")
  field(FLNK, "QUAD:IN20:121:ALDESERRSEVR")
}

# combine the calc with the possibility of invalid PVs 
# which sets the final result invalid
record(calc, "QUAD:IN20:121:ALDESERRSEVR") {
  field(DESC, "QUAD:IN20:121 monitoring")
  field(CALC, "B=1?2:A")
  field(INPA, "QUAD:IN20:121:ALDESERRCALC")
  field(INPB, "QUAD:IN20:121:PVSINV")
  field(FLNK, "QUAD:IN20:121:ALDESERR")
}

# put the result into a bi for names and alarm statuses
record(mbbi, "QUAD:IN20:121:ALDESERR") {
  field(DESC, "QUAD:IN20:121 monitoring")
  field(INP, "QUAD:IN20:121:ALDESERRSEVR.VAL")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "OK")
  field(ONST, "FAULT")
  field(TWST, "INVALID")
}

# Joe's matlab code:
# ...
# %if (bdes ~= bcon)
# if abs((bdes - bcon))/max(abs(bdes), abs(bcon)) > 2e-4
#    error_flag(n) = 1;
# end
# ===========================================================

# BDES is not at BCON, within tolerance

# to avoid divide-by-zero
record(calc, "QUAD:IN20:122:TESTFOR0") {
  field(DESC, "QUAD:IN20:122 monitoring")
  field(SCAN, "1 second")
  field(CALC, "(A=0&&B=0)?1:0")
  field(INPA, "QUAD:IN20:122:BDES")
  field(INPB, "QUAD:IN20:122:BCON")
  field(FLNK, "QUAD:IN20:122:PVSINV")
}

# check for invalid PVs
record(calc, "QUAD:IN20:122:PVSINV") {
  field(CALC, "A>2||B>2?1:0")
  field(INPA, "QUAD:IN20:122:BDES.SEVR")
  field(INPB, "QUAD:IN20:122:BCON.SEVR")
  field(FLNK, "QUAD:IN20:122:ALDESERRCALC")
}

# do the calc
record(calc, "QUAD:IN20:122:ALDESERRCALC") {
  field(DESC, "QUAD:IN20:122 monitoring")
  field(CALC, "D=1?0:ABS(A-B)/MAX(ABS(A),ABS(B))>C?1:0")
  field(INPA, "QUAD:IN20:122:BDES")
  field(INPB, "QUAD:IN20:122:BCON")
  field(INPC, .0002)
  field(INPD, "QUAD:IN20:122:TESTFOR0")
  field(FLNK, "QUAD:IN20:122:ALDESERRSEVR")
}

# combine the calc with the possibility of invalid PVs 
# which sets the final result invalid
record(calc, "QUAD:IN20:122:ALDESERRSEVR") {
  field(DESC, "QUAD:IN20:122 monitoring")
  field(CALC, "B=1?2:A")
  field(INPA, "QUAD:IN20:122:ALDESERRCALC")
  field(INPB, "QUAD:IN20:122:PVSINV")
  field(FLNK, "QUAD:IN20:122:ALDESERR")
}

# put the result into a bi for names and alarm statuses
record(mbbi, "QUAD:IN20:122:ALDESERR") {
  field(DESC, "QUAD:IN20:122 monitoring")
  field(INP, "QUAD:IN20:122:ALDESERRSEVR.VAL")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "OK")
  field(ONST, "FAULT")
  field(TWST, "INVALID")
}

# Joe's matlab code:
# ...
# %if (bdes ~= bcon)
# if abs((bdes - bcon))/max(abs(bdes), abs(bcon)) > 2e-4
#    error_flag(n) = 1;
# end
# ===========================================================

# BDES is not at BCON, within tolerance

# to avoid divide-by-zero
record(calc, "QUAD:IN20:525:TESTFOR0") {
  field(DESC, "QUAD:IN20:525 monitoring")
  field(SCAN, "1 second")
  field(CALC, "(A=0&&B=0)?1:0")
  field(INPA, "QUAD:IN20:525:BDES")
  field(INPB, "QUAD:IN20:525:BCON")
  field(FLNK, "QUAD:IN20:525:PVSINV")
}

# check for invalid PVs
record(calc, "QUAD:IN20:525:PVSINV") {
  field(CALC, "A>2||B>2?1:0")
  field(INPA, "QUAD:IN20:525:BDES.SEVR")
  field(INPB, "QUAD:IN20:525:BCON.SEVR")
  field(FLNK, "QUAD:IN20:525:ALDESERRCALC")
}

# do the calc
record(calc, "QUAD:IN20:525:ALDESERRCALC") {
  field(DESC, "QUAD:IN20:525 monitoring")
  field(CALC, "D=1?0:ABS(A-B)/MAX(ABS(A),ABS(B))>C?1:0")
  field(INPA, "QUAD:IN20:525:BDES")
  field(INPB, "QUAD:IN20:525:BCON")
  field(INPC, .0002)
  field(INPD, "QUAD:IN20:525:TESTFOR0")
  field(FLNK, "QUAD:IN20:525:ALDESERRSEVR")
}

# combine the calc with the possibility of invalid PVs 
# which sets the final result invalid
record(calc, "QUAD:IN20:525:ALDESERRSEVR") {
  field(DESC, "QUAD:IN20:525 monitoring")
  field(CALC, "B=1?2:A")
  field(INPA, "QUAD:IN20:525:ALDESERRCALC")
  field(INPB, "QUAD:IN20:525:PVSINV")
  field(FLNK, "QUAD:IN20:525:ALDESERR")
}

# put the result into a bi for names and alarm statuses
record(mbbi, "QUAD:IN20:525:ALDESERR") {
  field(DESC, "QUAD:IN20:525 monitoring")
  field(INP, "QUAD:IN20:525:ALDESERRSEVR.VAL")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "OK")
  field(ONST, "FAULT")
  field(TWST, "INVALID")
}

# Joe's matlab code:
# ...
# %if (bdes ~= bcon)
# if abs((bdes - bcon))/max(abs(bdes), abs(bcon)) > 2e-4
#    error_flag(n) = 1;
# end
# ===========================================================

# BDES is not at BCON, within tolerance

# to avoid divide-by-zero
record(calc, "QUAD:LI21:278:TESTFOR0") {
  field(DESC, "QUAD:LI21:278 monitoring")
  field(SCAN, "1 second")
  field(CALC, "(A=0&&B=0)?1:0")
  field(INPA, "QUAD:LI21:278:BDES")
  field(INPB, "QUAD:LI21:278:BCON")
  field(FLNK, "QUAD:LI21:278:PVSINV")
}

# check for invalid PVs
record(calc, "QUAD:LI21:278:PVSINV") {
  field(CALC, "A>2||B>2?1:0")
  field(INPA, "QUAD:LI21:278:BDES.SEVR")
  field(INPB, "QUAD:LI21:278:BCON.SEVR")
  field(FLNK, "QUAD:LI21:278:ALDESERRCALC")
}

# do the calc
record(calc, "QUAD:LI21:278:ALDESERRCALC") {
  field(DESC, "QUAD:LI21:278 monitoring")
  field(CALC, "D=1?0:ABS(A-B)/MAX(ABS(A),ABS(B))>C?1:0")
  field(INPA, "QUAD:LI21:278:BDES")
  field(INPB, "QUAD:LI21:278:BCON")
  field(INPC, .0002)
  field(INPD, "QUAD:LI21:278:TESTFOR0")
  field(FLNK, "QUAD:LI21:278:ALDESERRSEVR")
}

# combine the calc with the possibility of invalid PVs 
# which sets the final result invalid
record(calc, "QUAD:LI21:278:ALDESERRSEVR") {
  field(DESC, "QUAD:LI21:278 monitoring")
  field(CALC, "B=1?2:A")
  field(INPA, "QUAD:LI21:278:ALDESERRCALC")
  field(INPB, "QUAD:LI21:278:PVSINV")
  field(FLNK, "QUAD:LI21:278:ALDESERR")
}

# put the result into a bi for names and alarm statuses
record(mbbi, "QUAD:LI21:278:ALDESERR") {
  field(DESC, "QUAD:LI21:278 monitoring")
  field(INP, "QUAD:LI21:278:ALDESERRSEVR.VAL")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "OK")
  field(ONST, "FAULT")
  field(TWST, "INVALID")
}

# Joe's watcher code
# n = laser_steer_loop1_num;
# str = pv_data{n};
# if ~strcmp(str, 'Close Loop') %bad status
#    error_flag(n) = 1;
# end
# n = laser_steer_loop2_num;
# str = pv_data{n};
# if ~strcmp(str, 'Close Loop') %bad status
#    error_flag(n) = 1;
# end
# ===============================================
# (lasr):POS_FDBK PV
#    1 is Close Loop
#    0 is Open Loop
 
# 1 if NOT CLOSE LOOP, 0 CLOSE LOOP
record(calc, LASR:IN20:160:ALCLLPERRCALC) {
  field(CALC, "B>2?2:A=1?0:1")
  field(INPA, "LASR:IN20:160:POS_FDBK")
  field(INPB, "LASR:IN20:160:POS_FDBK.SEVR")
  field(SCAN, "1 second")
  field(FLNK, "LASR:IN20:160:ALCLLPERR")
}

# put the result into a bi for state names and alarm statuses
record(mbbi, "LASR:IN20:160:ALCLLPERR") {
  field(DESC, "LASR:IN20:160 alarm")
  field(INP, "LASR:IN20:160:ALCLLPERRCALC.VAL")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "CLOSE")
  field(ONST, "NOT_CLOSE")
  field(TWST, "INVALID")
}

# checks to see if the 6X6 feedback is ok.
# If the incrementor is not running, it's not ok
# FBCK is always FB6X6
# ENPV0 - 6 are all the enable/disable PVs for the 6X6 feedback
# If they are ALL "disabled", then it's ok if the
# incrementor isn't running.  Otherwise, incrementor
# not running is an error condition.
# The enable/disable PVs are SIOC:SYS0:AO290 through 296
# ====================================================================

# check to see if feedback is incrementing (running)
# calcout to take care of scan rate > 10 seconds
record(calcout, "ALRM:SYS0:FB6X6:SCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:FB6X6:SCAN.VAL")
  field(INPB, "20")
  field(OUT, "ALRM:SYS0:FB6X6:ALHBCURR.H PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(calc, "ALRM:SYS0:FB6X6:ALHBCURR") {
  field(CALC, "A")
  field(INPA,  "SIOC:SYS0:ML00:AO047 NPP MS")
  field(SCAN, "Passive")
  field(FLNK, "ALRM:SYS0:FB6X6:ALHBCHK")
}

record(calc, "ALRM:SYS0:FB6X6:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:FB6X6:ALHBCURR.VAL NPP MS")
  field(INPB, "ALRM:SYS0:FB6X6:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:FB6X6:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:FB6X6:ALHBERR")
}

# never in alarm; this is simply the status, not
# the final alarm PV.
record(mbbi, "ALRM:SYS0:FB6X6:ALHBERR") {
  field(DESC, "6X6 FB monitoring")
  field(FLNK, "ALRM:SYS0:FB6X6:ALFBERRCALC")
  field(INP, "ALRM:SYS0:FB6X6:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:FB6X6:ALHBPREV")
}

record(ai, "ALRM:SYS0:FB6X6:ALHBPREV") {
  field(INP,  "ALRM:SYS0:FB6X6:ALHBCURR NPP MS")
  field(FLNK, "ALRM:SYS0:FB6X6:ENABLED") 
}

# then see if the status is OK, but it's not incrementing
# (it thinks it's good, but it's not)
# feedback is on and not incrementing is an error
# if any input is invalid, then the status is invalid
# ALHBERR has no value severity, so can propagate its severity
# into the calc (to capture invalid)
# STATE itself could be major or minor; simply want to capture an
# invalid status here.

# this one checks to see if any of the enable PVs are ENABLED (1)
# it will also be invalid if any of the enable PVs are invalid.
record(calc, "ALRM:SYS0:FB6X6:ENABLED") {
  field(CALC, "A+B+C+D+E+F+G>0?1:0")
  field(INPA, "SIOC:SYS0:ML00:AO290 NPP MS")
  field(INPB, "SIOC:SYS0:ML00:AO292 NPP MS")
  field(INPC, "SIOC:SYS0:ML00:AO293 NPP MS")
  field(INPD, "SIOC:SYS0:ML00:AO294 NPP MS")
  field(INPE, "SIOC:SYS0:ML00:AO295 NPP MS")
  field(INPF, "SIOC:SYS0:ML00:AO296 NPP MS")
  field(FLNK, "ALRM:SYS0:FB6X6:ALFBERRCALC") 
}

record(calc, "ALRM:SYS0:FB6X6:ALFBERRCALC") {
  field(CALC, "C>2||D>2?2:((A=1&&B=1)?1:0)")
  field(INPA, "ALRM:SYS0:FB6X6:ENABLED NPP NMS")
  field(INPB, "ALRM:SYS0:FB6X6:ALHBERR NPP NMS")
  field(INPC, "ALRM:SYS0:FB6X6:ENABLED.SEVR")
  field(INPD, "ALRM:SYS0:FB6X6:ALHBERR.SEVR")
  field(FLNK, "ALRM:SYS0:FB6X6:ALFBERR")
}

record(mbbi, "ALRM:SYS0:FB6X6:ALFBERR") {
  field(DESC, "6X6 FB monitoring")
  field(INP, "ALRM:SYS0:FB6X6:ALFBERRCALC.VAL NPP MS")
  field(ZRST, "OK")
  field(ONST, "ON_NOT_RUNNING")
  field(TWST, "INVALID")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(FLNK, "ALRM:SYS0:LNG:STATECALC")
}

# =============================================
# now the part that checks to see if any longitudinal
# FB is running (Joe's, Diane's).  Error conditions are:
#  - No lng fbck running 
#  - Both lng fbcks running
#
# Joe's fbck PV is $(FBCK):ALFBERR
# Diane's fbck PV is FBCK:LNG:1:STATE
# The summary PV is ALRM:SYS0:LNG:STATE

record(calc, "ALRM:SYS0:LNG:STATECALC") {
  field(DESC, "lng fbckstat calc")
  field(CALC, "C>2||D>2?3:A=1&&B=0?2:A=0&&B=1?1:0")
  field(INPA, "ALRM:SYS0:FB6X6:ALHBERR NPP NMS")
  field(INPB, "FBCK:LNG:1:STATE NPP NMS")
  field(INPC, "ALRM:SYS0:FB6X6:ALHBERR.SEVR")
  field(INPD, "FBCK:LNG:1:STATE.SEVR")
  field(FLNK, "ALRM:SYS0:LNG:STATE")
}

record(mbbi, "ALRM:SYS0:LNG:STATE") {
  field(DESC, "lng fbck status")
  field(INP, "ALRM:SYS0:LNG:STATECALC.VAL NPP MS")
  field(ZRST, "ONE_RUNNING")
  field(ONST, "BOTH_RUNNING")
  field(TWST, "NONE_RUNNING")
  field(THST, "INVALID")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
}

# checks: 
#  AO058 is the so-called Fancy Phase Shift Mode
#  if any LNG0-8 is running, AO058 should be 0
#  if 6X6 is running, AO058 should be 1
#
# =============================================================================================
#SIOC:SYS0:ML00:AO058 = SIOC:SYS0:ML00:AO058

# first see what the lng feedback state is: 
#  both, none, 6x6 only or lng only
record(calcout, "ALRM:SYS0:LNG:ALLSTATESCAN") {
  field(CALC, "A=B?0:A+1")
  field(SCAN, "1 second")
  field(INPA, "ALRM:SYS0:LNG:ALLSTATESCAN.VAL")
  field(INPB, "10")
  field(OUT, "ALRM:SYS0:LNG:ALLSTATECALC.H PP")
  field(DOPT, "Use CALC")
  field(OOPT, "Transition To Zero")
}

record(calc, "ALRM:SYS0:LNG:ALLSTATECALC") {
  field(DESC, "lng fbckstat calc")
  field(CALC, "C>2||D>2?4:A=1?2:A=2?3:B=1?1:0")
  field(INPA, "ALRM:SYS0:LNG:STATE NPP NMS")
  field(INPB, "FBCK:LNG:1:STATE NPP NMS")
  field(INPC, "ALRM:SYS0:LNG:STATE.SEVR")
  field(INPD, "FBCK:LNG:1:STATE.SEVR")
  field(FLNK, "ALRM:SYS0:LNG:ALLSTATE")
}

record(mbbi, "ALRM:SYS0:LNG:ALLSTATE") {
  field(DESC, "FPSM Check")
  field(INP, "ALRM:SYS0:LNG:ALLSTATECALC.VAL NPP MS")
  field(ZRST, "EXCL_6X6")
  field(ONST, "EXCL_LNG")
  field(TWST, "BOTH_RUNNING")
  field(THST, "NONE_RUNNING")
  field(FRST, "INVALID")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "NO_ALARM")
  field(TWSV, "MAJOR")
  field(THSV, "MINOR")
  field(FRSV, "INVALID")
  field(FLNK, "ALRM:SYS0:FPSM:OKCALC")
}

# now check against the Fancy Phase Shift Mode, like this:
#   NO_ALARM if: (good operating conditions)
#      AO058 is 0 and LNG fbcks are running exclusively.
#      AO058 is 1 and your 6X6 fbck is running exclusively.
# 
#   MAJOR if: (this could drive the beam nuts)
#      AO058 is 1 and LNG fbcks are running exclusively.
#      Both feedbacks are running
#
#   MINOR if  (This results in no feedback, but beam will still run)
#      AO058 is 0 and your 6X6 fbck is running exclusively. 
#      neither of the feedbacks are running.

record(calc, "ALRM:SYS0:FPSM:OKCALC") {
  field(CALC, "C>2||D>2?2:(A=0&&B=1)||(A=1&&B=0)?1:0")
  field(INPA, "ALRM:SYS0:LNG:ALLSTATE NPP NMS")
  field(INPB, "SIOC:SYS0:ML00:AO058 NPP NMS")
  field(INPC, "ALRM:SYS0:LNG:ALLSTATE.SEVR")
  field(INPD, "SIOC:SYS0:ML00:AO058.SEVR")
  field(FLNK, "ALRM:SYS0:FPSM:MAJORCALC")
}

record(calc, "ALRM:SYS0:FPSM:MAJORCALC") {
  field(CALC, "C>2||D>2?2:(B=1&&A=1)||A=2?1:0")
  field(INPA, "ALRM:SYS0:LNG:ALLSTATE NPP NMS")
  field(INPB, "SIOC:SYS0:ML00:AO058 NPP NMS")
  field(INPC, "ALRM:SYS0:LNG:ALLSTATE.SEVR")
  field(INPD, "SIOC:SYS0:ML00:AO058.SEVR")
  field(FLNK, "ALRM:SYS0:FPSM:MINORCALC")
}

record(calc, "ALRM:SYS0:FPSM:MINORCALC") {
  field(CALC, "C>2||D>2?2:(B=0&&A=0)||A=3?1:0")
  field(INPA, "ALRM:SYS0:LNG:ALLSTATE NPP NMS")
  field(INPB, "SIOC:SYS0:ML00:AO058 NPP NMS")
  field(INPC, "ALRM:SYS0:LNG:ALLSTATE.SEVR")
  field(INPD, "SIOC:SYS0:ML00:AO058.SEVR")
  field(FLNK, "ALRM:SYS0:FPSM:STATECALC")
}

record(calc, "ALRM:SYS0:FPSM:STATECALC") {
  field(DESC, "Fancy Phase Shift Mode calc")
  field(CALC, "A>1||B>1||C>1?3:B=1?1:C=1?2:0")
  field(INPA, "ALRM:SYS0:FPSM:OKCALC NPP NMS")
  field(INPB, "ALRM:SYS0:FPSM:MAJORCALC NPP NMS")
  field(INPC, "ALRM:SYS0:FPSM:MINORCALC NPP NMS")
  field(FLNK, "ALRM:SYS0:FPSM:STATE")
}

record(mbbi, "ALRM:SYS0:FPSM:STATE") {
  field(DESC, "FPSM Check")
  field(INP, "ALRM:SYS0:FPSM:STATECALC.VAL NPP MS")
  field(ZRST, "OK")
  field(ONST, "ERROR")
  field(TWST, "WARNING")
  field(THST, "INVALID")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "MINOR")
  field(THSV, "INVALID")
}

# this is a generalized version of watcherFbckCheck.db 
# ======================================================

# check to see if feedback is incrementing (running)
record(ai, "ALRM:SYS0:BSYSTR:ALHBCURR") {
  field(INP,  "SIOC:SYS0:ML00:AO460 NPP MS")
  field(SCAN, "10 second")
  field(FLNK, "ALRM:SYS0:BSYSTR:ALHBCHK")
}

record(calc, "ALRM:SYS0:BSYSTR:ALHBCHK") {
  field(CALC, "C>2?2:(A=B?1:0)")
  field(INPA, "ALRM:SYS0:BSYSTR:ALHBCURR.VAL NPP MS")
  field(INPB, "ALRM:SYS0:BSYSTR:ALHBPREV.VAL NPP MS")
  field(INPC, "ALRM:SYS0:BSYSTR:ALHBCURR.SEVR")
  field(FLNK, "ALRM:SYS0:BSYSTR:ALHBERR")
}

# never in alarm; this is simply the status, not
# the final alarm PV.
record(mbbi, "ALRM:SYS0:BSYSTR:ALHBERR") {
  field(DESC, "ALRM:SYS0:BSYSTR Monitoring")
  field(FLNK, "ALRM:SYS0:BSYSTR:ALFBERRCALC")
  field(INP, "ALRM:SYS0:BSYSTR:ALHBCHK.VAL NPP MS")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
  field(ZRST, "RUNNING")
  field(ONST, "NOT_RUNNING")
  field(TWST, "INVALID")
  field(FLNK, "ALRM:SYS0:BSYSTR:ALHBPREV")
}

record(ai, "ALRM:SYS0:BSYSTR:ALHBPREV") {
  field(INP,  "ALRM:SYS0:BSYSTR:ALHBCURR NPP MS")
  field(FLNK, "ALRM:SYS0:BSYSTR:ALFBERRCALC") 
}

# then see if the status is OK, but it's not incrementing
# (it thinks it's good, but it's not)
# on and not incrementing is an error
# if any input is invalid, then the status is invalid
# ALHBERR has no value severity, so can propagate its severity
# into the calc (to capture invalid)
# STATE itself could be major or minor; simply want to capture an
# invalid status here.
record(calc, "ALRM:SYS0:BSYSTR:ALFBERRCALC") {
  field(CALC, "C>2||D>2?2:((A>0&&B=1)?1:0)")
  field(INPA, "SIOC:SYS0:ML00:AO455 NPP NMS")
  field(INPB, "ALRM:SYS0:BSYSTR:ALHBERR NPP NMS")
  field(INPC, "SIOC:SYS0:ML00:AO455.SEVR")
  field(INPD, "ALRM:SYS0:BSYSTR:ALHBERR.SEVR")
  field(FLNK, "ALRM:SYS0:BSYSTR:ALFBERR")
}

record(mbbi, "ALRM:SYS0:BSYSTR:ALFBERR") {
  field(DESC, "ALRM:SYS0:BSYSTR Monitoring")
  field(INP, "ALRM:SYS0:BSYSTR:ALFBERRCALC.VAL NPP MS")
  field(ZRST, "OK")
  field(ONST, "ON_NOT_RUNNING")
  field(TWST, "INVALID")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
}

# this is in error if:
#   ABS(PV1 - PV2) > TOL
#   PV3 and PV4 are the severities for PV1 and PV2
#   with the option of passing in 0 (for VMS PVs which 
#   have no .SEVR for example)
# ======================================================

record(calc, "ALRM:SYS0:KLYS29PHAS:DIFFCALC") {
  field(CALC, "C>2||D>2?2:ABS(A-B)>=E?1:0")
  field(SCAN, "5 second")
  field(INPA, "ACCL:LI29:0:KLY_PDES NPP NMS")
  field(INPB, "LI29:SBST:1:PDES NPP NMS")
  field(INPC, "ACCL:LI29:0:KLY_PDES.SEVR")
  field(INPD, "0")
  field(INPE, "2")
  field(FLNK, "ALRM:SYS0:KLYS29PHAS:DIFFERR")
}

record(mbbi, "ALRM:SYS0:KLYS29PHAS:DIFFERR") {
  field(DESC, "Diff Check")
  field(INP, "ALRM:SYS0:KLYS29PHAS:DIFFCALC.VAL NPP MS")
  field(ZRST, "OK")
  field(ONST, "PHAS_NO_SYNC")
  field(TWST, "INVALID")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
}

# this is in error if:
#   ABS(PV1 - PV2) > TOL
#   PV3 and PV4 are the severities for PV1 and PV2
#   with the option of passing in 0 (for VMS PVs which 
#   have no .SEVR for example)
# ======================================================

record(calc, "ALRM:SYS0:KLYS30PHAS:DIFFCALC") {
  field(CALC, "C>2||D>2?2:ABS(A-B)>=E?1:0")
  field(SCAN, "5 second")
  field(INPA, "ACCL:LI30:0:KLY_PDES NPP NMS")
  field(INPB, "LI30:SBST:1:PDES NPP NMS")
  field(INPC, "ACCL:LI30:0:KLY_PDES.SEVR")
  field(INPD, "0")
  field(INPE, "2")
  field(FLNK, "ALRM:SYS0:KLYS30PHAS:DIFFERR")
}

record(mbbi, "ALRM:SYS0:KLYS30PHAS:DIFFERR") {
  field(DESC, "Diff Check")
  field(INP, "ALRM:SYS0:KLYS30PHAS:DIFFCALC.VAL NPP MS")
  field(ZRST, "OK")
  field(ONST, "PHAS_NO_SYNC")
  field(TWST, "INVALID")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "INVALID")
}

# sets alarm limits for PV or PV.FIELD INPA.
# =======================================================
record(ai, "ALRM:SYS0:WSL246:PVALRM") {
  field(DESC, "ALARM for WIRE:LTUH:246:MOTR.RBV")
  field(SCAN, "10 second")
  field(INP, "WIRE:LTUH:246:MOTR.RBV NPP MS")
  field(LLSV, "MAJOR")
  field(LOLO, "15000")
  field(HHSV, "NO_ALARM")
  field(HIHI, "0")
  field(HSV, "NO_ALARM")
  field(HIGH, "0")
  field(LSV, "NO_ALARM")
  field(LOW, "0")
}